Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:39
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 08:39:23
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 926.63 | 443.29 | 443.29 |
Net Site Energy | 875.97 | 419.06 | 419.06 |
Total Source Energy | 2399.84 | 1148.07 | 1148.07 |
Net Source Energy | 2239.41 | 1071.32 | 1071.32 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 256.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 152.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 65.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 669.89 | 256.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 256.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 5.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 41.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 152.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 65.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 256.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 5.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 41.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 152.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 65.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 152.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 106.57 | 122.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 320.47 | 122.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 152.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 106.57 | 122.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 320.47 | 122.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 53.095 | 7.93 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -2.44 | -0.4 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 50.656 | 7.56 |
Electricity Coming From Utility | 619.241 | 92.44 |
Surplus Electricity Going To Utility | 0.011 | 0.00 |
Net Electricity From Utility | 619.230 | 92.44 |
Total On-Site and Utility Electric Sources | 669.886 | 100.00 |
Total Electricity End Uses | 669.886 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1575.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:39 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 11.5884 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 13.7658 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 7.5320 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 10.0873 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 10.0873 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 11.5884 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 13.7658 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 12.9393 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 12.9393 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 12.9393 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 7.5320 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 7.5557 | 6.19 | 4.3000 | |
Total | 2090.32 | 10.0873 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 10.0873 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 10.0873 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-16:49 | 10-JAN-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 110771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8890.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7436.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 58345.16 | 110771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 110771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 16261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8890.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7436.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 278.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 17.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 879.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 130.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 481.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 205.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2121.53 | 278.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 133.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 420.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 230.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1014.93 | 133.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 133.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 420.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 230.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1014.93 | 133.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.46 |
SMSTORE1 DIRECT AIR | 0.828858 |
SMSTORE2 DIRECT AIR | 0.967971 |
SMSTORE3 DIRECT AIR | 0.966831 |
SMSTORE4 DIRECT AIR | 0.964556 |
LGSTORE2 DIRECT AIR | 1.45 |
SMSTORE5 DIRECT AIR | 0.779231 |
SMSTORE6 DIRECT AIR | 0.769815 |
SMSTORE7 DIRECT AIR | 0.752241 |
SMSTORE8 DIRECT AIR | 0.780760 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.00 | 1.00 | 1.46 |
PSZ-AC_2:2 | 0.828858 | 0.828858 | 0.828858 | 0.828858 | 0.844796 | 0.844796 | 1.00 | 0.981133 | 0.844796 |
PSZ-AC_3:3 | 0.967971 | 0.967971 | 0.967971 | 0.967971 | 0.967971 | 0.967971 | 1.00 | 1.00 | 0.967971 |
PSZ-AC_4:4 | 0.966831 | 0.966831 | 0.966831 | 0.966831 | 0.966831 | 0.966831 | 1.00 | 1.00 | 0.966831 |
PSZ-AC_5:5 | 0.964556 | 0.964556 | 0.964556 | 0.964556 | 0.964556 | 0.964556 | 1.00 | 1.00 | 0.964556 |
PSZ-AC_6:6 | 1.45 | 1.45 | 1.45 | 1.45 | 1.51 | 1.51 | 1.00 | 0.965458 | 1.51 |
PSZ-AC_7:7 | 0.779231 | 0.779231 | 0.779231 | 0.779231 | 0.794475 | 0.794475 | 1.00 | 0.980812 | 0.794475 |
PSZ-AC_8:8 | 0.769815 | 0.769815 | 0.769815 | 0.769815 | 0.786279 | 0.786279 | 1.00 | 0.979061 | 0.786279 |
PSZ-AC_9:9 | 0.752241 | 0.752241 | 0.752241 | 0.752241 | 0.771512 | 0.771512 | 1.00 | 0.975022 | 0.771512 |
PSZ-AC_10:10 | 0.780760 | 0.780760 | 0.780760 | 0.780760 | 0.780760 | 0.780760 | 1.00 | 1.00 | 0.780760 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.46 |
PSZ-AC_2:2_OA_CONTROLLER | 0.844796 |
PSZ-AC_3:3_OA_CONTROLLER | 0.967971 |
PSZ-AC_4:4_OA_CONTROLLER | 0.966831 |
PSZ-AC_5:5_OA_CONTROLLER | 0.964556 |
PSZ-AC_6:6_OA_CONTROLLER | 1.51 |
PSZ-AC_7:7_OA_CONTROLLER | 0.794475 |
PSZ-AC_8:8_OA_CONTROLLER | 0.786279 |
PSZ-AC_9:9_OA_CONTROLLER | 0.771512 |
PSZ-AC_10:10_OA_CONTROLLER | 0.780760 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.46 | 1560.06 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 0.844796 | 935.32 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 0.967971 | 1071.70 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.966831 | 1070.44 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 0.964556 | 1067.92 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.51 | 1610.83 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.794475 | 879.61 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.786279 | 870.54 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.771512 | 854.19 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 0.780760 | 864.42 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.46 | 1.46 | 1.46 | 0.962240 | 24134.08 | 45490.43 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 0.844796 | 0.844796 | 0.844796 | 0.844796 | 13984.38 | 25004.35 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 0.967971 | 0.967971 | 0.967971 | 0.967971 | 16477.24 | 28150.70 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 0.966831 | 0.966831 | 0.966831 | 0.966831 | 16507.61 | 28124.91 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 0.964556 | 0.964556 | 0.964556 | 0.964556 | 16429.03 | 28073.45 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.51 | 1.51 | 1.51 | 0.993553 | 24919.45 | 45387.28 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.794475 | 0.794475 | 0.794475 | 0.794475 | 13151.39 | 23881.93 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.786279 | 0.786279 | 0.786279 | 0.786279 | 13015.71 | 23668.96 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.771512 | 0.771512 | 0.771512 | 0.771512 | 12771.26 | 23271.48 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 0.780760 | 0.780760 | 0.780760 | 0.780760 | 12924.34 | 23916.67 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.46 | 0.728970 | 0.971960 | 24134.08 | 12067.04 | 0.800660 | 0.800660 |
PSZ-AC_2:2 COOLING COIL | 0.844800 | 0.422398 | 0.563200 | 13984.38 | 6992.19 | 0.800660 | 0.800660 |
PSZ-AC_3:3 COOLING COIL | 0.967970 | 0.483986 | 0.645313 | 16477.24 | 8238.62 | 0.800530 | 0.800530 |
PSZ-AC_4:4 COOLING COIL | 0.966830 | 0.483415 | 0.644553 | 16507.61 | 8253.81 | 0.800450 | 0.800450 |
PSZ-AC_5:5 COOLING COIL | 0.964560 | 0.482278 | 0.643040 | 16429.03 | 8214.51 | 0.800310 | 0.800310 |
PSZ-AC_6:6 COOLING COIL | 1.51 | 0.752692 | 1.00 | 24919.45 | 12459.73 | 0.800660 | 0.800660 |
PSZ-AC_7:7 COOLING COIL | 0.794480 | 0.397238 | 0.529653 | 13151.39 | 6575.69 | 0.800660 | 0.800660 |
PSZ-AC_8:8 COOLING COIL | 0.786280 | 0.393139 | 0.524187 | 13015.71 | 6507.85 | 0.800660 | 0.800660 |
PSZ-AC_9:9 COOLING COIL | 0.771510 | 0.385756 | 0.514340 | 12771.26 | 6385.63 | 0.800660 | 0.800660 |
PSZ-AC_10:10 COOLING COIL | 0.780760 | 0.390380 | 0.520507 | 12924.34 | 6462.17 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 45490.43 |
PSZ-AC_2:2 HEATING COIL | 25004.35 |
PSZ-AC_3:3 HEATING COIL | 28150.70 |
PSZ-AC_4:4 HEATING COIL | 28124.91 |
PSZ-AC_5:5 HEATING COIL | 28073.45 |
PSZ-AC_6:6 HEATING COIL | 45387.28 |
PSZ-AC_7:7 HEATING COIL | 23881.93 |
PSZ-AC_8:8 HEATING COIL | 23668.96 |
PSZ-AC_9:9 HEATING COIL | 23271.48 |
PSZ-AC_10:10 HEATING COIL | 23916.67 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 11.588 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.888 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 13.766 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 18.066 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 7.532 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.832 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 2630.745 | 7.551 | 46.768 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2630.745 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1406.513 | 4.037 | 25.004 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1406.513 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1319.493 | 7.575 | 46.916 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1319.493 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1078.411 | 6.191 | 38.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1078.411 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 2624.046 | 7.532 | 46.649 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2624.046 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.4286 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.099 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.37371027E-12 | 0.68594845E-15 | -0.12863262E-12 | 0.13303556E-15 |
23 | 6 | 0.32748130E-07 | 0.12499873E-09 | 0.74678710E-08 | -0.15730520E-12 |
24 | 5 | -0.21059623E-03 | 0.10441617E-05 | -0.10801544E-03 | 0.73682644E-08 |
25 | 4 | 0.31581162 | 0.49728803E-03 | 0.10820905 | -0.36942064E-04 |
26 | 3 | -7.7342764 | 0.15111690E-01 | -2.4778213 | 0.31304292E-01 |
27 | 2 | 42.413636 | 0.52806348E-01 | 15.833102 | -0.35052424 |
28 | 1 | -81.726940 | 0.23470004E-01 | -29.650437 | 1.1037915 |
29 | 0 | 46.824331 | 0.46514506E-03 | 16.279406 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 35 | 1 | VerySmooth | 1.408 | 1.408 | 1.000 | 0.210 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 4.57814E-002 | 0.12126 | 0.67915 | 0.67915 | 0.29000 | 0.15345 | 0.21878 | 0.00000 | 0.84000 | 0.84000 | 8.56546E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 16380.95352 | 19657.14422 | 1.21495 | 1.45794 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 26.40000 | 8.40708E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 17078.29886 | 20493.95863 | 0.74411 | 0.89293 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 9641.22524 | 11569.47029 | 0.69071 | 0.82886 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 8228.99022 | 9874.78827 | 0.35854 | 0.43025 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11190.03208 | 13428.03850 | 0.80664 | 0.96797 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.39928E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 8317.35939 | 9980.83127 | 0.36239 | 0.43487 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11177.42452 | 13412.90942 | 0.80569 | 0.96683 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.39928E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 8402.36688 | 10082.84025 | 0.36609 | 0.43931 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11151.45365 | 13381.74438 | 0.80380 | 0.96456 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.39928E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 8566.49663 | 10279.79595 | 0.37324 | 0.44789 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 16971.79585 | 20366.15502 | 1.21115 | 1.45339 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 16516.38875 | 19819.66650 | 0.71963 | 0.86355 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 9079.32963 | 10895.19555 | 0.64936 | 0.77923 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 8831.16293 | 10597.39552 | 0.38478 | 0.46173 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 8972.71251 | 10767.25501 | 0.64151 | 0.76982 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 8837.63584 | 10605.16301 | 0.38506 | 0.46207 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 8773.89985 | 10528.67982 | 0.62687 | 0.75224 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 9124.81623 | 10949.77948 | 0.39757 | 0.47708 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 8768.38480 | 10522.06175 | 0.65063 | 0.78076 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 23.39700 | 8.40238E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 10896.82756 | 13076.19307 | 0.47477 | 0.56972 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 20590.52 | 1.45794 | 1.45794 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 32711.50 | 0.89293 | 0.89293 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 11354.44 | 0.84480 | 0.84480 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 15988.88 | 0.43025 | 0.43025 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 12253.65 | 0.96797 | 0.96797 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 16093.38 | 0.43487 | 0.43487 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 12238.64 | 0.96683 | 0.96683 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 16193.90 | 0.43931 | 0.43931 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 12208.03 | 0.96456 | 0.96456 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 16387.99 | 0.44789 | 0.44789 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 20492.76 | 1.50538 | 1.50538 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 32047.09 | 0.86355 | 0.86355 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 10471.22 | 0.79448 | 0.79448 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 16700.96 | 0.46173 | 0.46173 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 10372.66 | 0.78628 | 0.78628 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 16708.62 | 0.46207 | 0.46207 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 10239.96 | 0.77151 | 0.77151 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 17048.22 | 0.47708 | 0.47708 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 10321.21 | 0.78076 | 0.78076 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 19143.60 | 0.56972 | 0.56972 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.45794 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.82886 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.96797 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.96683 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.96456 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.45339 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.77923 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.76982 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.75224 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.78076 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.45794 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.45794 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.45794 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.45794 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.45794 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.45794 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.82886 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.82886 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.82886 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.82886 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.84480 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.84480 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.98113 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.96797 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.96797 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.96797 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.96797 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96797 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 0.96797 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.96683 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.96683 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.96683 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.96683 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96683 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.96683 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.96456 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.96456 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.96456 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.96456 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96456 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 0.96456 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.45339 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.45339 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.45339 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.45339 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.50538 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.50538 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 0.96546 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.77923 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.77923 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.77923 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.77923 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.79448 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.79448 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.98081 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.76982 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.76982 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.76982 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.76982 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.78628 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.78628 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.97906 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.75224 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.75224 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.75224 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.75224 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.77151 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.77151 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.97502 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.78076 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.78076 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.78076 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.78076 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.78076 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 0.78076 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.45794 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 0.84480 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 0.96797 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 0.96683 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 0.96456 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.50538 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.79448 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.78628 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.77151 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 0.78076 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.45794 |
102 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.45794 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1560.06428 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.45794 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.45794 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.45794 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96224 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.45794 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.72897 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.97196 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24134.08000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12067.04000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
115 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24134.08000 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 45490.43334 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
119 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 45490.43334 |
120 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.84480 |
121 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.84480 |
122 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 935.32378 |
123 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.84480 |
124 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.84480 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.84480 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.84480 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.84480 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.42240 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.56320 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 13984.38000 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6992.19000 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13984.38000 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25004.34545 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
138 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 25004.34545 |
139 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96797 |
140 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96797 |
141 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1071.69762 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96797 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96797 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96797 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96797 |
146 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96797 |
147 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48399 |
148 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64531 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16477.24000 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8238.62000 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80053 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80053 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16477.24000 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28150.70008 |
155 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
157 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 28150.70008 |
158 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96683 |
159 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96683 |
160 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1070.43530 |
161 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96683 |
162 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96683 |
163 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96683 |
164 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96683 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96683 |
166 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48342 |
167 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64455 |
168 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16507.61000 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8253.80500 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80045 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80045 |
172 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16507.61000 |
173 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28124.91335 |
174 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
176 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 28124.91335 |
177 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96456 |
178 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96456 |
179 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1067.91638 |
180 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96456 |
181 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96456 |
182 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96456 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96456 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96456 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48228 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64304 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16429.03000 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8214.51500 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80031 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80031 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16429.03000 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28073.44994 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
194 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
195 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 28073.44994 |
196 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.50538 |
197 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.50538 |
198 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1610.83209 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.50538 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.50538 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.50538 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.99355 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.50538 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.75269 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.00359 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24919.45000 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12459.72500 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24919.45000 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 45387.27850 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
213 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
214 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 45387.27850 |
215 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.79448 |
216 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.79448 |
217 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 879.61015 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.79448 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.79448 |
220 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.79448 |
221 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.79448 |
222 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.79448 |
223 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.39724 |
224 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.52965 |
225 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 13151.39000 |
226 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6575.69500 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
229 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13151.39000 |
230 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23881.92615 |
231 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
232 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
233 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 23881.92615 |
234 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.78628 |
235 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.78628 |
236 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 870.53564 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.78628 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.78628 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.78628 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.78628 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.78628 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.39314 |
243 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.52419 |
244 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 13015.71000 |
245 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6507.85500 |
246 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
247 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13015.71000 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23668.95920 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
251 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
252 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 23668.95920 |
253 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.77151 |
254 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.77151 |
255 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 854.18618 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.77151 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.77151 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.77151 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77151 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.77151 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.38576 |
262 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.51434 |
263 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 12771.26000 |
264 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6385.63000 |
265 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
266 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12771.26000 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23271.47689 |
269 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
270 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
271 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 23271.47689 |
272 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.78076 |
273 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.78076 |
274 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 864.42471 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.78076 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.78076 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.78076 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.78076 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.78076 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.39038 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.52051 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 12924.34000 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6462.17000 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12924.34000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23916.66592 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 23916.66592 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 22991.5 | 11.54 | 11.54 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 13322.3 | 12.29 | 12.29 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 15718.3 | 12.37 | 12.37 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 15749.6 | 12.38 | 12.38 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 15672.8 | 12.37 | 12.37 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 23739.7 | 11.54 | 11.54 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 12528.7 | 12.29 | 12.29 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 12399.5 | 12.29 | 12.29 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 12166.6 | 12.29 | 12.29 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 12312.5 | 12.29 | 12.29 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.5496922737E-002 | 0.1466781076 | Pass | Pass | 0.2790536639 | 1.1837369734 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.2057032486E-002 | 0.1275206336 | Pass | Pass | 8.4336681475E-002 | 0.2505518306 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 2.8983500996E-002 | 0.1457608643 | Pass | Pass | 0.1921964066 | 1.3632636834 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.7045128497E-002 | 0.1774869020 | Pass | Pass | 0.1175886692 | 0.3992167348 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.7592751671E-002 | 0.2061664649 | Pass | Pass | 0.3326159647 | 2.9819553163 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.5772269576E-002 | 0.2343010126 | Pass | Pass | 3.6960855457E-002 | 0.1199115682 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.5586256949E-002 | 0.2404939660 | Pass | Pass | 3.4546037314E-002 | 0.1001588210 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.6747294865E-002 | 0.2422982549 | Pass | Pass | 3.3451634946E-002 | 0.1018024454 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.1431207781E-002 | 0.2593154347 | Pass | Pass | 2.9786820725E-002 | 9.3721308950E-002 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 6.9605638462E-002 | 0.3366850836 | Pass | Pass | 2.5035251361E-002 | 8.3218010805E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3464.40 | 231.05 | 0.00 | 470.85 | 61.23 | 4227.56 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 1.408 | 0.210 | 0.290 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 1.408 | 0.210 | 0.290 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 7.5512 | 348.39 | 2630.74 | LightsWired | LTG_SCH_BASE_LPD1 | 81.37 | 168.00 | 80.49 | 0.0000 | Y | 39.75 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 4.0372 | 348.39 | 1406.51 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 24.96 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 7.5749 | 174.19 | 1319.49 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 82.90 | 168.00 | 81.97 | 0.0000 | Y | 20.30 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 6.1909 | 174.19 | 1078.41 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 19.14 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 7.5320 | 348.39 | 2624.05 | LightsWired | LTG_SCH_BASE_LPD2 | 60.23 | 168.00 | 58.11 | 0.0000 | Y | 28.62 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 5.0436 | 4180.64 | 21085.58 | 277.79 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 437.57 | AstronomicalClock | - | 42.50 | 42.50 | 3.49 | |
EXTERIOR_LIGHTS_B | 1882.64 | AstronomicalClock | - | 83.54 | 63.02 | 22.27 | |
EXTERIOR_LIGHTS_C | 1466.47 | AstronomicalClock | - | 83.54 | 56.02 | 15.42 | |
Exterior Lighting Total | 3786.68 | 41.18 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24134.08 | 19323.19 | 4810.89 | 0.80 | 3.99 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 13984.38 | 11196.73 | 2787.65 | 0.80 | 4.32 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16477.24 | 13190.52 | 3286.72 | 0.80 | 4.32 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16507.61 | 13213.52 | 3294.09 | 0.80 | 4.32 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16429.03 | 13148.32 | 3280.71 | 0.80 | 4.32 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24919.45 | 19952.01 | 4967.44 | 0.80 | 3.99 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 13151.39 | 10529.79 | 2621.60 | 0.80 | 4.32 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 13015.71 | 10421.16 | 2594.55 | 0.80 | 4.32 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 12771.26 | 10225.44 | 2545.82 | 0.80 | 4.32 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 12924.34 | 10348.00 | 2576.34 | 0.80 | 4.32 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 22991.5 | 11.54 | 11.54 | ||||
PSZ-AC_2:2 COOLING COIL | 13322.3 | 12.29 | 12.29 | ||||
PSZ-AC_3:3 COOLING COIL | 15718.3 | 12.37 | 12.37 | ||||
PSZ-AC_4:4 COOLING COIL | 15749.6 | 12.38 | 12.38 | ||||
PSZ-AC_5:5 COOLING COIL | 15672.8 | 12.37 | 12.37 | ||||
PSZ-AC_6:6 COOLING COIL | 23739.7 | 11.54 | 11.54 | ||||
PSZ-AC_7:7 COOLING COIL | 12528.7 | 12.29 | 12.29 | ||||
PSZ-AC_8:8 COOLING COIL | 12399.5 | 12.29 | 12.29 | ||||
PSZ-AC_9:9 COOLING COIL | 12166.6 | 12.29 | 12.29 | ||||
PSZ-AC_10:10 COOLING COIL | 12312.5 | 12.29 | 12.29 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 45490.43 | 0.88 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 25004.35 | 0.88 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 28150.70 | 0.88 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 28124.91 | 0.88 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 28073.45 | 0.88 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 45387.28 | 0.88 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 23881.93 | 0.88 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 23668.96 | 0.88 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 23271.48 | 0.88 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 23916.67 | 0.88 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.46 | 1560.06 | 1070.05 | 1.00 | 1.37 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.84 | 935.32 | 1107.16 | 1.00 | 1.45 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.97 | 1071.70 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.97 | 1070.44 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.96 | 1067.92 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.51 | 1610.83 | 1070.05 | 1.00 | 1.36 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.79 | 879.61 | 1107.16 | 1.00 | 1.47 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.79 | 870.54 | 1107.16 | 1.00 | 1.47 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.77 | 854.19 | 1107.16 | 1.00 | 1.47 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.78 | 864.42 | 1107.16 | 1.00 | 1.47 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 16380.95 | 19657.14 | 56.42 | 1.215 | 1.458 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 23.89 | 23.89 | 0.00912 | 26.40 | 0.00841 | 0.411 | 0.00 |
SMSTORE1 | 9641.23 | 11569.47 | 66.42 | 0.691 | 0.829 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.88 | 0.00972 | 22.94 | 0.00840 | 0.206 | 0.00 |
SMSTORE2 | 11190.03 | 13428.04 | 77.09 | 0.807 | 0.968 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.88 | 0.01002 | 21.39 | 0.00840 | 0.206 | 0.00 |
SMSTORE3 | 11177.42 | 13412.91 | 77.00 | 0.806 | 0.967 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.88 | 0.01004 | 21.39 | 0.00840 | 0.206 | 0.00 |
SMSTORE4 | 11151.45 | 13381.74 | 76.82 | 0.804 | 0.965 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.88 | 0.01002 | 21.39 | 0.00840 | 0.206 | 0.00 |
LGSTORE2 | 16971.80 | 20366.16 | 58.46 | 1.211 | 1.453 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.88 | 0.01007 | 22.94 | 0.00840 | 0.411 | 0.00 |
SMSTORE5 | 9079.33 | 10895.20 | 62.55 | 0.649 | 0.779 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.88 | 0.00987 | 22.94 | 0.00840 | 0.206 | 0.00 |
SMSTORE6 | 8972.71 | 10767.26 | 61.81 | 0.642 | 0.770 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.88 | 0.00991 | 22.94 | 0.00840 | 0.206 | 0.00 |
SMSTORE7 | 8773.90 | 10528.68 | 60.44 | 0.627 | 0.752 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.88 | 0.00998 | 22.94 | 0.00840 | 0.206 | 0.00 |
SMSTORE8 | 8768.38 | 10522.06 | 60.40 | 0.651 | 0.781 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 23.89 | 23.89 | 0.00954 | 23.40 | 0.00840 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 17078.30 | 20493.96 | 58.83 | 0.744 | 0.893 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00675 | -4.30 | 0.00266 | 0.411 | 0.00 |
SMSTORE1 | 8228.99 | 9874.79 | 56.69 | 0.359 | 0.430 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00664 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE2 | 8317.36 | 9980.83 | 57.30 | 0.362 | 0.435 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00664 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE3 | 8402.37 | 10082.84 | 57.88 | 0.366 | 0.439 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00665 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE4 | 8566.50 | 10279.80 | 59.01 | 0.373 | 0.448 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00667 | -4.30 | 0.00266 | 0.206 | 0.00 |
LGSTORE2 | 16516.39 | 19819.67 | 56.89 | 0.720 | 0.864 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00676 | -4.30 | 0.00266 | 0.411 | 0.00 |
SMSTORE5 | 8831.16 | 10597.40 | 60.84 | 0.385 | 0.462 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE6 | 8837.64 | 10605.16 | 60.88 | 0.385 | 0.462 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE7 | 9124.82 | 10949.78 | 62.86 | 0.398 | 0.477 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00672 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE8 | 10896.83 | 13076.19 | 75.07 | 0.475 | 0.570 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00680 | -4.30 | 0.00266 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.46 | 1.46 | 0.89 | 0.89 | 1.4579 | 1.4579 | 1.4579 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 0.84 | 0.84 | 0.43 | 0.43 | 0.8448 | 0.8289 | 0.8448 | 0.9811 | 1.0000 |
PSZ-AC_3:3 | 0.97 | 0.97 | 0.43 | 0.43 | 0.9680 | 0.9680 | 0.9680 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 0.97 | 0.97 | 0.44 | 0.44 | 0.9668 | 0.9668 | 0.9668 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 0.96 | 0.96 | 0.45 | 0.45 | 0.9646 | 0.9646 | 0.9646 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.51 | 1.51 | 0.86 | 0.86 | 1.5054 | 1.4534 | 1.5054 | 0.9655 | 1.0000 |
PSZ-AC_7:7 | 0.79 | 0.79 | 0.46 | 0.46 | 0.7945 | 0.7792 | 0.7945 | 0.9808 | 1.0000 |
PSZ-AC_8:8 | 0.79 | 0.79 | 0.46 | 0.46 | 0.7863 | 0.7698 | 0.7863 | 0.9791 | 1.0000 |
PSZ-AC_9:9 | 0.77 | 0.77 | 0.48 | 0.48 | 0.7715 | 0.7522 | 0.7715 | 0.9750 | 1.0000 |
PSZ-AC_10:10 | 0.78 | 0.78 | 0.57 | 0.57 | 0.7808 | 0.7808 | 0.7808 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 24134.080 | 19323.192 | 1.457940 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 12067.04 | 11237.02 | 0.971960 | 25.48 | 17.14 | 0.00891534 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 42.3351 | 23.89 | 0.00911520 | 48.8262 | 16299.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 45490.433 | 45490.433 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 45490.43 | 45490.43 | 1.457940 | 13.94 | 9.45 | 0.00559493 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 28.2234 | 21.11 | 0.00674993 | 42.9763 | 17078.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 13984.380 | 11196.734 | 0.844800 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6992.19 | 6535.90 | 0.563200 | 25.44 | 17.11 | 0.00889147 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 36.5301 | 23.89 | 0.00905673 | 48.5173 | 9641.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 25004.345 | 25004.345 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 25004.35 | 25004.35 | 0.844796 | 14.92 | 9.97 | 0.00566773 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 24.3535 | 21.11 | 0.00663681 | 42.2640 | 8228.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 16477.240 | 13190.525 | 0.967970 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8238.62 | 6710.53 | 0.645313 | 24.28 | 17.36 | 0.00967261 | 12.80 | 12.00 | 0.00850000 | 21.39 | 0.00839928 | 15.25 | 31.8818 | 23.88 | 0.01001630 | 53.5948 | 10371.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 28150.700 | 28150.700 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28150.70 | 28150.70 | 0.967971 | 15.71 | 10.45 | 0.00579683 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.2545 | 21.11 | 0.00664416 | 42.3103 | 8317.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 16507.610 | 13213.516 | 0.966830 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8253.81 | 6701.65 | 0.644553 | 24.28 | 17.38 | 0.00969260 | 12.80 | 12.00 | 0.00850000 | 21.39 | 0.00839928 | 15.25 | 31.9194 | 23.88 | 0.01004221 | 53.7315 | 10378.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 28124.913 | 28124.913 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28124.91 | 28124.91 | 0.966831 | 15.70 | 10.46 | 0.00580219 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.2796 | 21.11 | 0.00665224 | 42.3612 | 8402.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 16429.030 | 13148.317 | 0.964560 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8214.51 | 6685.67 | 0.643040 | 24.28 | 17.37 | 0.00967736 | 12.80 | 12.00 | 0.00850000 | 21.39 | 0.00839928 | 15.25 | 31.9945 | 23.88 | 0.01002388 | 53.6347 | 10333.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 28073.450 | 28073.450 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28073.45 | 28073.45 | 0.964556 | 15.69 | 10.46 | 0.00581292 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.3298 | 21.11 | 0.00666842 | 42.4632 | 8566.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 24919.450 | 19952.007 | 1.505380 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 12459.73 | 11595.11 | 1.003587 | 25.48 | 17.15 | 0.00891940 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 41.0010 | 23.89 | 0.00912228 | 48.8636 | 16971.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 45387.279 | 45387.279 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 45387.28 | 45387.28 | 1.505384 | 14.16 | 9.60 | 0.00563527 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 27.3339 | 21.11 | 0.00675535 | 43.0101 | 16516.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 13151.390 | 10529.792 | 0.794480 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6575.69 | 6133.06 | 0.529653 | 25.49 | 17.14 | 0.00890634 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 38.8438 | 23.89 | 0.00909780 | 48.7341 | 9079.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 23881.926 | 23881.926 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 23881.93 | 23881.93 | 0.794475 | 14.53 | 9.77 | 0.00564751 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 25.8960 | 21.11 | 0.00669235 | 42.6140 | 8831.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 13015.710 | 10421.158 | 0.786280 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6507.85 | 6068.32 | 0.524187 | 25.50 | 17.15 | 0.00890800 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 39.2489 | 23.89 | 0.00910279 | 48.7604 | 8972.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 23668.959 | 23668.959 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 23668.96 | 23668.96 | 0.786279 | 14.46 | 9.73 | 0.00563713 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 26.1660 | 21.11 | 0.00669305 | 42.6184 | 8837.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 12771.260 | 10225.437 | 0.771510 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6385.63 | 5952.44 | 0.514340 | 25.51 | 17.15 | 0.00891022 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 40.0003 | 23.89 | 0.00910964 | 48.7966 | 8773.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 23271.477 | 23271.477 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 23271.48 | 23271.48 | 0.771512 | 14.33 | 9.67 | 0.00563528 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 26.6668 | 21.11 | 0.00671808 | 42.7762 | 9124.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 12924.340 | 10348.002 | 0.780760 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6462.17 | 6027.32 | 0.520507 | 25.41 | 17.11 | 0.00890392 | 12.80 | 12.00 | 0.00850000 | 26.10 | 0.00840660 | 16.93 | 39.5264 | 23.89 | 0.00909668 | 48.7281 | 8745.35 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 23916.666 | 23916.666 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 23916.67 | 23916.67 | 0.780760 | 14.41 | 9.79 | 0.00570997 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 26.3509 | 21.11 | 0.00680208 | 43.3062 | 10896.83 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24134.080 | 19323.192 | 1.457940 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4132 | 1004.8586 | 1.1914 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.457940 | 1.73694843 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | Sensible | 12067.04 | 11237.02 | 1.0000 | 1.15796594 | 0.971960 | 25.48 | 17.14 | 0.00891534 | 48318.7 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12067.04 | 26.40 | 0.00840708 | 17.04 | 0.41148071 | 42.3351 | 23.89 | 0.00911520 | 23.89 | 0.00911520 | 48.8262 | 16299.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 45490.433 | 45490.433 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.457940 | 1.73694843 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 45490.43 | 45490.43 | 1.0000 | 1.73694843 | 1.457940 | 13.94 | 9.45 | 0.00559493 | 28141.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45490.43 | -4.30 | 0.00265759 | -4.30 | 0.41148071 | 28.2234 | 21.11 | 0.00674993 | 21.11 | 0.00674993 | 42.9763 | 17078.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13984.380 | 11196.734 | 0.844800 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3688 | 1004.8586 | 1.1914 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.844796 | 1.00646685 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 6992.19 | 6535.90 | 1.0000 | 0.67098072 | 0.563200 | 25.44 | 17.11 | 0.00889147 | 48217.7 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6992.19 | 26.40 | 0.00840708 | 17.04 | 0.20573751 | 36.5301 | 23.89 | 0.00905673 | 23.89 | 0.00905673 | 48.5173 | 9641.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25004.345 | 25004.345 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.844796 | 1.00646685 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 25004.35 | 25004.35 | 1.0000 | 1.00646685 | 0.844796 | 14.92 | 9.97 | 0.00566773 | 29324.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25004.35 | -4.30 | 0.00265759 | -4.30 | 0.20573751 | 24.3535 | 21.11 | 0.00663681 | 21.11 | 0.00663681 | 42.2640 | 8228.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16477.240 | 13190.525 | 0.967970 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8209 | 1004.8586 | 1.1914 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.967971 | 1.15321363 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | Sensible | 8238.62 | 6710.53 | 1.0000 | 0.76880824 | 0.645313 | 24.28 | 17.36 | 0.00967261 | 49027.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8238.62 | 21.39 | 0.00839928 | 15.25 | 0.20573751 | 31.8818 | 23.91 | 0.01001630 | 23.88 | 0.01001630 | 53.5948 | 10371.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28150.700 | 28150.700 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.967971 | 1.15321363 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28150.70 | 28150.70 | 1.0000 | 1.15321363 | 0.967971 | 15.71 | 10.45 | 0.00579683 | 30450.2 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28150.70 | -4.30 | 0.00265759 | -4.30 | 0.20573751 | 21.2545 | 21.11 | 0.00664416 | 21.11 | 0.00664416 | 42.3103 | 8317.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16507.610 | 13213.516 | 0.966830 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8581 | 1004.8586 | 1.1914 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.966831 | 1.15185530 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | Sensible | 8253.81 | 6701.65 | 1.0000 | 0.76790280 | 0.644553 | 24.28 | 17.38 | 0.00969260 | 49078.0 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8253.81 | 21.39 | 0.00839928 | 15.25 | 0.20573751 | 31.9194 | 23.91 | 0.01004221 | 23.88 | 0.01004221 | 53.7315 | 10378.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28124.913 | 28124.913 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.966831 | 1.15185530 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28124.91 | 28124.91 | 1.0000 | 1.15185530 | 0.966831 | 15.70 | 10.46 | 0.00580219 | 30457.3 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28124.91 | -4.30 | 0.00265759 | -4.30 | 0.20573751 | 21.2796 | 21.11 | 0.00665224 | 21.11 | 0.00665224 | 42.3612 | 8402.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16429.030 | 13148.317 | 0.964560 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8297 | 1004.8586 | 1.1914 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.964556 | 1.14914479 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | Sensible | 8214.51 | 6685.67 | 1.0000 | 0.76609986 | 0.643040 | 24.28 | 17.37 | 0.00967736 | 49037.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8214.51 | 21.39 | 0.00839928 | 15.25 | 0.20573751 | 31.9945 | 23.91 | 0.01002388 | 23.88 | 0.01002388 | 53.6347 | 10333.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28073.450 | 28073.450 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.964556 | 1.14914479 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28073.45 | 28073.45 | 1.0000 | 1.14914479 | 0.964556 | 15.69 | 10.46 | 0.00581292 | 30471.5 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28073.45 | -4.30 | 0.00265759 | -4.30 | 0.20573751 | 21.3298 | 21.11 | 0.00666842 | 21.11 | 0.00666842 | 42.4632 | 8566.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24919.450 | 19952.007 | 1.505380 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4207 | 1004.8586 | 1.1914 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.505384 | 1.79347242 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 12459.73 | 11595.11 | 1.0000 | 1.19564507 | 1.003587 | 25.48 | 17.15 | 0.00891940 | 48332.7 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12459.73 | 26.40 | 0.00840708 | 17.04 | 0.41148071 | 41.0010 | 23.89 | 0.00912228 | 23.89 | 0.00912228 | 48.8636 | 16971.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 45387.279 | 45387.279 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.505384 | 1.79347242 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 45387.28 | 45387.28 | 1.0000 | 1.79347242 | 1.505384 | 14.16 | 9.60 | 0.00563527 | 28473.3 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45387.28 | -4.30 | 0.00265759 | -4.30 | 0.41148071 | 27.3339 | 21.11 | 0.00675535 | 21.11 | 0.00675535 | 43.0101 | 16516.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13151.390 | 10529.792 | 0.794480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3964 | 1004.8586 | 1.1914 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.794475 | 0.94651550 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 6575.69 | 6133.06 | 1.0000 | 0.63101416 | 0.529653 | 25.49 | 17.14 | 0.00890634 | 48314.1 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6575.69 | 26.40 | 0.00840708 | 17.04 | 0.20573751 | 38.8438 | 23.89 | 0.00909780 | 23.89 | 0.00909780 | 48.7341 | 9079.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23881.926 | 23881.926 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.794475 | 0.94651550 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 23881.93 | 23881.93 | 1.0000 | 0.94651550 | 0.794475 | 14.53 | 9.77 | 0.00564751 | 28875.0 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23881.93 | -4.30 | 0.00265759 | -4.30 | 0.20573751 | 25.8960 | 21.11 | 0.00669235 | 21.11 | 0.00669235 | 42.6140 | 8831.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13015.710 | 10421.158 | 0.786280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3995 | 1004.8586 | 1.1914 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.786279 | 0.93675077 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 6507.85 | 6068.32 | 1.0000 | 0.62450132 | 0.524187 | 25.50 | 17.15 | 0.00890800 | 48325.5 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6507.85 | 26.40 | 0.00840708 | 17.04 | 0.20573751 | 39.2489 | 23.89 | 0.00910279 | 23.89 | 0.00910279 | 48.7604 | 8972.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23668.959 | 23668.959 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.786279 | 0.93675077 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 23668.96 | 23668.96 | 1.0000 | 0.93675077 | 0.786279 | 14.46 | 9.73 | 0.00563713 | 28779.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23668.96 | -4.30 | 0.00265759 | -4.30 | 0.20573751 | 26.1660 | 21.11 | 0.00669305 | 21.11 | 0.00669305 | 42.6184 | 8837.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12771.260 | 10225.437 | 0.771510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4036 | 1004.8586 | 1.1914 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.771512 | 0.91915773 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 6385.63 | 5952.44 | 1.0000 | 0.61277028 | 0.514340 | 25.51 | 17.15 | 0.00891022 | 48341.0 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6385.63 | 26.40 | 0.00840708 | 17.04 | 0.20573751 | 40.0003 | 23.89 | 0.00910964 | 23.89 | 0.00910964 | 48.7966 | 8773.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23271.477 | 23271.477 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.771512 | 0.91915773 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 23271.48 | 23271.48 | 1.0000 | 0.91915773 | 0.771512 | 14.33 | 9.67 | 0.00563528 | 28645.3 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23271.48 | -4.30 | 0.00265759 | -4.30 | 0.20573751 | 26.6668 | 21.11 | 0.00671808 | 21.11 | 0.00671808 | 42.7762 | 9124.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12924.340 | 10348.002 | 0.780760 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3919 | 1004.8586 | 1.1914 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.780760 | 0.93017502 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 6462.17 | 6027.32 | 1.0000 | 0.62011707 | 0.520507 | 25.41 | 17.11 | 0.00890392 | 48226.8 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6462.17 | 26.10 | 0.00840660 | 16.93 | 0.20573751 | 39.5264 | 23.89 | 0.00909668 | 23.89 | 0.00909668 | 48.7281 | 8745.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23916.666 | 23916.666 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.780760 | 0.93017502 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 23916.67 | 23916.67 | 1.0000 | 0.93017502 | 0.780760 | 14.41 | 9.79 | 0.00570997 | 28915.3 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23916.67 | -4.30 | 0.00265759 | -4.30 | 0.20573751 | 26.3509 | 21.11 | 0.00680208 | 21.11 | 0.00680208 | 43.3062 | 10896.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.46 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.84 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.97 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.97 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.96 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.51 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.79 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.79 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.77 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.78 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
LGSTORE1 | LGSTORE1_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE1 | SMSTORE1_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE2 | SMSTORE2_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE3 | SMSTORE3_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE4 | SMSTORE4_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LGSTORE2 | LGSTORE2_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE5 | SMSTORE5_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE6 | SMSTORE6_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE7 | SMSTORE7_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE8 | SMSTORE8_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1107.67 | 4555.17 | 624.17 |
SMSTORE1 | 704.00 | 3976.00 | 85.00 |
SMSTORE2 | 811.00 | 2968.33 | 231.17 |
SMSTORE3 | 841.17 | 3013.33 | 283.83 |
SMSTORE4 | 858.50 | 3133.50 | 374.00 |
LGSTORE2 | 852.33 | 3214.00 | 544.17 |
SMSTORE5 | 771.17 | 3158.83 | 538.83 |
SMSTORE6 | 783.00 | 3192.33 | 570.67 |
SMSTORE7 | 874.33 | 3301.00 | 712.17 |
SMSTORE8 | 1380.00 | 3464.00 | 1287.83 |
Facility | 2257.00 | 5052.00 | 1575.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 5.83 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 13.17 | 0.00 | 0.00 | 0.00 |
Facility | 19.33 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.623 | 0.223 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.709 | 0.242 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.838 | 0.317 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.830 | 0.317 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.800 | 0.317 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 0.696 | 0.304 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.789 | 0.339 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.781 | 0.339 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.758 | 0.339 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.736 | 0.350 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.436 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.436 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.436 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 0.459 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.459 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.459 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.459 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.459 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.212 |
SMSTORE1 | PSZ-AC_2:2 | 8.47 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
LGSTORE2 | PSZ-AC_6:6 | 24.76 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.212 |
SMSTORE5 | PSZ-AC_7:7 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE6 | PSZ-AC_8:8 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE7 | PSZ-AC_9:9 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE8 | PSZ-AC_10:10 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
Total Facility | 120.91 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 1.274 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 6472355.41 | 0.00 | 6472355.41 | 2543634.56 | 9015989.97 | 7870781.79 | 3179.28 | 4514.67 | 1066.06 | 2.08 |
SMSTORE1 | 3683256.59 | 0.00 | 3683256.59 | 1325656.62 | 5008913.21 | 3935374.10 | 4159.35 | 2763.26 | 1837.40 | 27.25 |
SMSTORE2 | 3300072.16 | 0.00 | 3300072.16 | 1347989.39 | 4648061.55 | 3701819.01 | 4342.69 | 3077.83 | 1339.47 | 97.06 |
SMSTORE3 | 3267331.70 | 0.00 | 3267331.70 | 1347989.39 | 4615321.09 | 3701819.01 | 4344.69 | 3110.67 | 1304.64 | 90.72 |
SMSTORE4 | 3145603.34 | 0.00 | 3145603.34 | 1347989.39 | 4493592.73 | 3701819.01 | 4351.19 | 3229.67 | 1179.14 | 73.56 |
LGSTORE2 | 4999334.44 | 0.00 | 4999334.44 | 2452525.89 | 7451860.33 | 7907875.00 | 4727.75 | 3345.00 | 687.25 | 16.50 |
SMSTORE5 | 2840144.08 | 0.00 | 2840144.08 | 1353368.44 | 4193512.52 | 3953920.18 | 4723.08 | 3156.67 | 880.25 | 46.75 |
SMSTORE6 | 2809701.05 | 0.00 | 2809701.05 | 1353368.44 | 4163069.49 | 3953920.18 | 4724.17 | 3185.33 | 850.50 | 40.67 |
SMSTORE7 | 2721129.80 | 0.00 | 2721129.80 | 1353368.44 | 4074498.24 | 3953920.18 | 4727.42 | 3277.00 | 755.58 | 18.25 |
SMSTORE8 | 2638705.11 | 0.00 | 2638705.11 | 1541468.51 | 4180173.62 | 3953920.18 | 4728.50 | 3392.67 | 638.83 | 1.83 |
Total Facility | 35877633.68 | 0.00 | 35877633.68 | 15967359.07 | 51844992.76 | 46635168.64 | 4728.75 | 5006.17 | 1969.31 | 157.22 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.3077 | 0.0000 | 0.3077 | 0.1105 | 0.4182 | 0.2682 | 260.19 | 4514.67 | 1065.14 |
SMSTORE1 | 0.1748 | 0.0000 | 0.1748 | 0.0599 | 0.2347 | 0.1341 | 1243.26 | 2763.09 | 1833.65 |
SMSTORE2 | 0.2066 | 0.0000 | 0.2066 | 0.0785 | 0.2851 | 0.1285 | 0.00 | 3077.00 | 1318.00 |
SMSTORE3 | 0.2047 | 0.0000 | 0.2047 | 0.0785 | 0.2832 | 0.1285 | 0.00 | 3108.67 | 1286.33 |
SMSTORE4 | 0.1974 | 0.0000 | 0.1974 | 0.0785 | 0.2759 | 0.1285 | 0.00 | 3228.33 | 1166.67 |
LGSTORE2 | 0.3441 | 0.0000 | 0.3441 | 0.1507 | 0.4948 | 0.2958 | 0.00 | 3345.00 | 685.00 |
SMSTORE5 | 0.1949 | 0.0000 | 0.1949 | 0.0838 | 0.2787 | 0.1479 | 0.00 | 3156.50 | 873.50 |
SMSTORE6 | 0.1929 | 0.0000 | 0.1929 | 0.0838 | 0.2767 | 0.1479 | 0.00 | 3185.17 | 844.83 |
SMSTORE7 | 0.1872 | 0.0000 | 0.1872 | 0.0838 | 0.2710 | 0.1479 | 0.00 | 3277.00 | 753.00 |
SMSTORE8 | 0.1817 | 0.0000 | 0.1817 | 0.0866 | 0.2684 | 0.1479 | 0.00 | 3392.67 | 637.33 |
Total Facility | 2.1920 | 0.0000 | 2.1920 | 0.8945 | 3.0865 | 1.6752 | 1360.76 | 5002.51 | 1949.39 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 9186830.88 | 0.00 | 9186830.88 | 7870781.79 | 3178.44 | 0.17 | 5581.39 | 2.08 |
PSZ-AC_2:2 | 5227893.76 | 0.00 | 5227893.76 | 3935374.10 | 4084.47 | 3.17 | 4672.36 | 27.25 |
PSZ-AC_3:3 | 4684014.41 | 0.00 | 4684014.41 | 3701819.01 | 4312.69 | 1.67 | 4445.64 | 96.72 |
PSZ-AC_4:4 | 4637543.68 | 0.00 | 4637543.68 | 3701819.01 | 4316.86 | 2.17 | 4440.97 | 90.39 |
PSZ-AC_5:5 | 4464766.42 | 0.00 | 4464766.42 | 3701819.01 | 4331.44 | 1.33 | 4427.22 | 73.39 |
PSZ-AC_6:6 | 7096009.76 | 0.00 | 7096009.76 | 7907875.00 | 4727.08 | 0.08 | 4032.83 | 16.33 |
PSZ-AC_7:7 | 4031207.55 | 0.00 | 4031207.55 | 3953920.18 | 4716.58 | 1.00 | 4042.42 | 46.58 |
PSZ-AC_8:8 | 3987997.71 | 0.00 | 3987997.71 | 3953920.18 | 4718.50 | 0.42 | 4041.08 | 40.00 |
PSZ-AC_9:9 | 3862282.57 | 0.00 | 3862282.57 | 3953920.18 | 4725.67 | 0.08 | 4034.25 | 18.08 |
PSZ-AC_10:10 | 3745291.67 | 0.00 | 3745291.67 | 3953920.18 | 4728.50 | 0.00 | 4031.50 | 1.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.4368 | 0.0000 | 0.4368 | 0.2682 | 259.69 | 0.17 | 5580.14 |
PSZ-AC_2:2 | 0.2481 | 0.0000 | 0.2481 | 0.1341 | 1174.72 | 3.00 | 4662.28 |
PSZ-AC_3:3 | 0.2933 | 0.0000 | 0.2933 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2906 | 0.0000 | 0.2906 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2802 | 0.0000 | 0.2802 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.4884 | 0.0000 | 0.4884 | 0.2958 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2766 | 0.0000 | 0.2766 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2738 | 0.0000 | 0.2738 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2657 | 0.0000 | 0.2657 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2580 | 0.0000 | 0.2580 | 0.1479 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 373.47 | 831.75 | 0.00 | 0.00 | 0.00 | 4388.17 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 266.56 | 1840.26 | 0.00 | 0.00 | 0.00 | 2771.33 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 200.89 | 1215.83 | 0.00 | 0.00 | 0.00 | 3075.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 195.72 | 1183.67 | 0.00 | 0.00 | 0.00 | 3106.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 179.72 | 1063.83 | 0.00 | 0.00 | 0.00 | 3224.83 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 271.00 | 484.08 | 0.00 | 0.00 | 0.00 | 3291.25 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 184.58 | 735.50 | 0.00 | 0.00 | 0.00 | 3156.50 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 182.75 | 702.08 | 0.00 | 0.00 | 0.00 | 3185.17 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 168.08 | 603.00 | 0.00 | 0.00 | 0.00 | 3277.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 151.33 | 489.67 | 0.00 | 0.00 | 0.00 | 3390.83 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.0268 | 0.6012 | 0.0000 | 0.0000 | 0.0000 | 0.3806 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.8883 | 0.3750 | 0.0000 | 0.0000 | 0.0000 | 0.1925 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 1.0330 | 0.4707 | 0.0000 | 0.0000 | 0.0000 | 0.1808 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 1.0310 | 0.4709 | 0.0000 | 0.0000 | 0.0000 | 0.1808 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 1.0287 | 0.4690 | 0.0000 | 0.0000 | 0.0000 | 0.1808 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 1.0590 | 0.6664 | 0.0000 | 0.0000 | 0.0000 | 0.4165 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.8488 | 0.4361 | 0.0000 | 0.0000 | 0.0000 | 0.2087 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.8409 | 0.4329 | 0.0000 | 0.0000 | 0.0000 | 0.2087 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.8229 | 0.4275 | 0.0000 | 0.0000 | 0.0000 | 0.2085 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.8358 | 0.4270 | 0.0000 | 0.0000 | 0.0000 | 0.2082 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 835 |
Defaulted Fields | 817 |
Fields with Defaults | 2693 |
Autosized Fields | 174 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 669.89 | 2102.83 | 29-JAN-08:00 | 58345.16 | 21-JUL-16:50 |
Electricity:Building | 405.94 | 891.83 | 01-JAN-00:20 | 25756.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 90.96 | 148.64 | 01-JAN-00:20 | 4765.21 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 405.94 | 891.83 | 01-JAN-00:20 | 25756.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 64.71 | 75.00 | 01-JAN-00:20 | 3421.96 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 64.71 | 75.00 | 01-JAN-00:20 | 3421.96 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 52.56 | 74.32 | 01-JAN-00:20 | 2762.01 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 39.44 | 37.50 | 01-JAN-00:20 | 2090.38 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 39.44 | 37.50 | 01-JAN-00:20 | 2090.38 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 47.80 | 148.64 | 01-JAN-00:10 | 3421.36 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 28.62 | 75.00 | 01-JAN-00:10 | 2078.11 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 28.62 | 75.00 | 01-JAN-00:10 | 2078.11 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityProduced:Facility | 50.66 | -0.00 | 12-JAN-16:30 | 10606.91 | 18-JUN-12:30 |
ElectricityProduced:Plant | 50.66 | -0.00 | 12-JAN-16:30 | 10606.91 | 18-JUN-12:30 |
Photovoltaic:ElectricityProduced | 53.09 | 0.00 | 01-JAN-00:10 | 11042.29 | 18-JUN-12:30 |
PowerConversion:ElectricityProduced | -2.44 | -435.38 | 18-JUN-12:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 65.02 | 1211.00 | 01-JAN-08:10 | 11860.28 | 19-JAN-13:50 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 619.24 | 0.00 | 30-APR-06:50 | 53463.50 | 21-JUL-16:50 |
ElectricityPurchased:Plant | 619.24 | 0.00 | 30-APR-06:50 | 53463.50 | 21-JUL-16:50 |
Cogeneration:ElectricityPurchased | 619.24 | 0.00 | 30-APR-06:50 | 53463.50 | 21-JUL-16:50 |
General:Cogeneration:ElectricityPurchased | 619.24 | 0.00 | 30-APR-06:50 | 53463.50 | 21-JUL-16:50 |
ElectricitySurplusSold:Facility | 0.01 | 0.00 | 01-JAN-00:10 | 1403.33 | 21-MAY-07:00 |
ElectricitySurplusSold:Plant | 0.01 | 0.00 | 01-JAN-00:10 | 1403.33 | 21-MAY-07:00 |
Cogeneration:ElectricitySurplusSold | 0.01 | 0.00 | 01-JAN-00:10 | 1403.33 | 21-MAY-07:00 |
General:Cogeneration:ElectricitySurplusSold | 0.01 | 0.00 | 01-JAN-00:10 | 1403.33 | 21-MAY-07:00 |
ElectricityNet:Facility | 619.23 | -1403.33 | 21-MAY-07:00 | 53463.50 | 21-JUL-16:50 |
ElectricityNet:Plant | 619.23 | -1403.33 | 21-MAY-07:00 | 53463.50 | 21-JUL-16:50 |
Cogeneration:ElectricityNet | 619.23 | -1403.33 | 21-MAY-07:00 | 53463.50 | 21-JUL-16:50 |
General:Cogeneration:ElectricityNet | 619.23 | -1403.33 | 21-MAY-07:00 | 53463.50 | 21-JUL-16:50 |
Electricity:HVAC | 157.74 | 0.00 | 01-JAN-00:10 | 25841.08 | 22-JUL-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 5.56 | 0.00 | 01-JAN-00:10 | 16932.96 | 22-JUL-15:00 |
General:Cooling:Electricity | 5.56 | 0.00 | 01-JAN-00:10 | 16932.96 | 22-JUL-15:00 |
Fans:Electricity | 152.18 | 0.00 | 01-JAN-00:10 | 9596.58 | 10-JAN-08:10 |
General:Fans:Electricity | 152.18 | 0.00 | 01-JAN-00:10 | 9596.58 | 10-JAN-08:10 |
ExteriorLights:Electricity | 41.18 | 0.00 | 01-JAN-08:20 | 3786.68 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 41.18 | 0.00 | 01-JAN-08:20 | 3786.68 | 01-JAN-06:10 |
WaterSystems:Electricity | 65.02 | 1211.00 | 01-JAN-08:10 | 11860.28 | 19-JAN-13:50 |
Water Heater:WaterSystems:Electricity | 65.02 | 1211.00 | 01-JAN-08:10 | 11860.28 | 19-JAN-13:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 256.74 | 0.00 | 01-JAN-00:10 | 110771.04 | 10-JAN-08:10 |
NaturalGas:HVAC | 256.74 | 0.00 | 01-JAN-00:10 | 110771.04 | 10-JAN-08:10 |
Heating:NaturalGas | 256.74 | 0.00 | 01-JAN-00:10 | 110771.04 | 10-JAN-08:10 |
General:Heating:NaturalGas | 256.74 | 0.00 | 01-JAN-00:10 | 110771.04 | 10-JAN-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 502.83 | 0.00 | 01-JAN-00:10 | 191181.44 | 10-JAN-08:10 |
EnergyTransfer:Building | 252.03 | 0.00 | 01-JAN-00:10 | 93702.92 | 10-JAN-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 53.66 | 0.00 | 01-JAN-00:10 | 17019.55 | 10-JAN-08:10 |
Heating:EnergyTransfer | 97.44 | 0.00 | 01-JAN-00:10 | 93702.92 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 13.43 | 0.00 | 01-JAN-00:10 | 17019.55 | 10-JAN-08:10 |
General:Heating:EnergyTransfer | 97.44 | 0.00 | 01-JAN-00:10 | 93702.92 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 13.43 | 0.00 | 01-JAN-00:10 | 17019.55 | 10-JAN-08:10 |
Cooling:EnergyTransfer | 154.59 | 0.00 | 01-JAN-00:10 | 58225.95 | 22-JUL-15:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 40.23 | 0.00 | 01-JAN-00:10 | 9789.28 | 22-JUL-16:20 |
General:Cooling:EnergyTransfer | 154.59 | 0.00 | 01-JAN-00:10 | 58225.95 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 40.23 | 0.00 | 01-JAN-00:10 | 9789.28 | 22-JUL-16:20 |
EnergyTransfer:Zone:SMSTORE1 | 24.99 | 0.00 | 01-JAN-00:10 | 7925.64 | 29-APR-18:20 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 3.87 | 0.00 | 01-JAN-00:10 | 6135.91 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 3.87 | 0.00 | 01-JAN-00:10 | 6135.91 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 21.11 | 0.00 | 01-JAN-00:10 | 7925.64 | 29-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 21.11 | 0.00 | 01-JAN-00:10 | 7925.64 | 29-APR-18:20 |
EnergyTransfer:Zone:SMSTORE2 | 19.48 | 0.00 | 01-JAN-00:10 | 6790.86 | 10-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 5.40 | 0.00 | 01-JAN-00:10 | 6790.86 | 10-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 5.40 | 0.00 | 01-JAN-00:10 | 6790.86 | 10-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 14.08 | 0.00 | 01-JAN-00:10 | 5290.14 | 22-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 14.08 | 0.00 | 01-JAN-00:10 | 5290.14 | 22-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 19.49 | 0.00 | 01-JAN-00:10 | 7403.73 | 10-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 6.11 | 0.00 | 01-JAN-00:10 | 7403.73 | 10-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 6.11 | 0.00 | 01-JAN-00:10 | 7403.73 | 10-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 13.38 | 0.00 | 01-JAN-00:10 | 5276.10 | 22-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 13.38 | 0.00 | 01-JAN-00:10 | 5276.10 | 22-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 18.93 | 0.00 | 01-JAN-00:10 | 8141.63 | 10-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 7.40 | 0.00 | 01-JAN-00:10 | 8141.63 | 10-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 7.40 | 0.00 | 01-JAN-00:10 | 8141.63 | 10-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 11.52 | 0.00 | 01-JAN-00:10 | 5129.33 | 22-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 11.52 | 0.00 | 01-JAN-00:10 | 5129.33 | 22-JUL-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 36.55 | 0.00 | 01-JAN-00:10 | 17999.72 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 14.25 | 0.00 | 01-JAN-00:10 | 17999.72 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 14.25 | 0.00 | 01-JAN-00:10 | 17999.72 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 22.29 | 0.00 | 01-JAN-00:10 | 9588.05 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 22.29 | 0.00 | 01-JAN-00:10 | 9588.05 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 18.00 | 0.00 | 01-JAN-00:10 | 9192.33 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 8.72 | 0.00 | 01-JAN-00:10 | 9192.33 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 8.72 | 0.00 | 01-JAN-00:10 | 9192.33 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 9.28 | 0.00 | 01-JAN-00:10 | 4966.33 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 9.28 | 0.00 | 01-JAN-00:10 | 4966.33 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 18.02 | 0.00 | 01-JAN-00:10 | 9201.10 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 9.09 | 0.00 | 01-JAN-00:10 | 9201.10 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 9.09 | 0.00 | 01-JAN-00:10 | 9201.10 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 8.94 | 0.00 | 01-JAN-00:10 | 4912.54 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 8.94 | 0.00 | 01-JAN-00:10 | 4912.54 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 18.64 | 0.00 | 01-JAN-00:10 | 10437.41 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 10.91 | 0.00 | 01-JAN-00:10 | 10437.41 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 10.91 | 0.00 | 01-JAN-00:10 | 10437.41 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 7.73 | 0.00 | 01-JAN-00:10 | 4786.41 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 7.73 | 0.00 | 01-JAN-00:10 | 4786.41 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 24.28 | 0.00 | 01-JAN-00:10 | 14360.34 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 18.26 | 0.00 | 01-JAN-00:10 | 14360.34 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 18.26 | 0.00 | 01-JAN-00:10 | 14360.34 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 6.02 | 0.00 | 01-JAN-00:10 | 4814.44 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 6.02 | 0.00 | 01-JAN-00:10 | 4814.44 | 22-JUL-15:00 |
EnergyTransfer:HVAC | 250.80 | 0.00 | 01-JAN-00:10 | 97478.52 | 10-JAN-08:10 |
HeatingCoils:EnergyTransfer | 225.93 | 0.00 | 01-JAN-00:10 | 97478.52 | 10-JAN-08:10 |
CoolingCoils:EnergyTransfer | 24.87 | 0.00 | 01-JAN-00:10 | 78993.64 | 22-JUL-15:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 13.432 | -40.231 | 0.000 | 0.000 | 25.789 | 64.707 | 26.249 | 10.718 | 0.000 | 0.065 | 0.003 | 0.000 | -7.362 | 0.000 | -32.985 | -60.382 |
SMSTORE1 | 0.000 | 0.000 | 3.872 | -21.114 | 0.000 | 0.000 | 12.559 | 39.440 | 13.125 | 5.278 | 0.000 | 0.035 | 0.000 | 0.000 | -3.885 | 0.000 | -17.508 | -31.802 |
SMSTORE2 | 0.000 | 0.000 | 5.402 | -14.078 | 0.000 | 0.000 | 7.636 | 28.854 | 10.421 | 5.268 | 0.000 | 0.035 | 0.000 | 0.000 | -3.866 | 0.000 | -17.860 | -21.812 |
SMSTORE3 | 0.000 | 0.000 | 6.106 | -13.384 | 0.000 | 0.000 | 7.648 | 28.854 | 10.421 | 5.278 | 0.000 | 0.035 | 0.001 | 0.000 | -3.826 | 0.000 | -17.799 | -23.333 |
SMSTORE4 | 0.000 | 0.000 | 7.403 | -11.523 | 0.000 | 0.000 | 7.677 | 28.854 | 10.421 | 5.300 | 0.000 | 0.035 | 0.000 | 0.000 | -3.771 | 0.000 | -17.671 | -26.725 |
LGSTORE2 | 0.000 | 0.000 | 14.254 | -22.292 | 0.000 | 0.000 | 26.708 | 28.624 | 19.173 | 10.690 | 0.000 | 0.063 | 0.000 | 0.000 | -7.298 | 0.000 | -31.408 | -38.513 |
SMSTORE5 | 0.000 | 0.000 | 8.718 | -9.280 | 0.000 | 0.000 | 13.290 | 14.614 | 9.586 | 5.324 | 0.000 | 0.035 | 0.000 | 0.000 | -3.659 | 0.000 | -17.426 | -21.202 |
SMSTORE6 | 0.000 | 0.000 | 9.087 | -8.936 | 0.000 | 0.000 | 13.301 | 14.614 | 9.586 | 5.331 | 0.000 | 0.035 | 0.000 | 0.000 | -3.644 | 0.000 | -17.396 | -21.979 |
SMSTORE7 | 0.000 | 0.000 | 10.908 | -7.734 | 0.000 | 0.000 | 13.342 | 14.614 | 9.586 | 5.354 | 0.000 | 0.035 | 0.000 | 0.000 | -3.586 | 0.000 | -17.278 | -25.241 |
SMSTORE8 | 0.000 | 0.000 | 18.256 | -6.023 | 0.000 | 0.000 | 13.404 | 14.614 | 9.586 | 5.409 | 0.000 | 0.036 | 0.000 | 0.000 | -3.390 | 0.000 | -19.609 | -32.285 |
Total Facility | 0.000 | 0.000 | 97.438 | -154.595 | 0.000 | 0.000 | 141.353 | 277.790 | 128.154 | 63.949 | 0.000 | 0.410 | 0.006 | 0.000 | -44.288 | 0.000 | -206.939 | -303.274 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 22-JUL-16:20 | 0.00 | 0.00 | 0.00 | -9789.29 | 0.00 | 0.00 | 1970.14 | 3421.96 | 1343.25 | 684.58 | 0.00 | 1468.77 | 900.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 14-AUG-20:44 | 0.00 | 0.00 | 0.00 | -15510.10 | 0.00 | 0.00 | 591.04 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 12265.63 | 0.00 | -105.23 | 0.00 | -3.34 | 0.00 |
SMSTORE2 | 23-JUL-07:03 | 0.00 | 0.00 | 0.00 | -7758.93 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 37.19 | 0.00 | 0.00 | 7781.82 | 0.00 | -0.00 | 0.00 | -134.89 | 0.00 |
SMSTORE3 | 23-JUL-07:03 | 0.00 | 0.00 | 0.00 | -7873.92 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 37.01 | 0.00 | 0.00 | 7897.02 | 0.00 | -0.00 | 0.00 | -134.93 | 0.00 |
SMSTORE4 | 23-JUL-07:03 | 0.00 | 0.00 | 0.00 | -6692.99 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 38.24 | 0.00 | 0.00 | 6714.53 | 0.00 | -0.00 | 0.00 | -134.59 | 0.00 |
LGSTORE2 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | -9588.34 | 0.00 | 0.00 | 3152.23 | 2078.11 | 1343.25 | 1312.92 | 0.00 | 1457.96 | 243.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | -4966.41 | 0.00 | 0.00 | 1576.08 | 1062.01 | 671.63 | 655.87 | 0.00 | 811.64 | 189.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | -4912.62 | 0.00 | 0.00 | 1576.08 | 1062.01 | 671.63 | 656.11 | 0.00 | 811.64 | 135.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | -4786.49 | 0.00 | 0.00 | 1576.08 | 1062.01 | 671.63 | 656.49 | 0.00 | 811.64 | 8.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | -4814.52 | 0.00 | 0.00 | 1576.08 | 1062.01 | 671.63 | 656.67 | 0.00 | 831.59 | 16.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | -58225.82 | 0.00 | 0.00 | 12707.24 | 17697.17 | 8059.50 | 7877.03 | 0.00 | 9448.97 | 2435.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 20-NOV-08:61 | 0.00 | 0.00 | 45907.73 | 0.00 | 0.00 | 0.00 | 251.66 | 75.00 | 74.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -427.96 | 0.00 | -787.28 | -45093.77 |
SMSTORE1 | 17-FEB-08:61 | 0.00 | 0.00 | 25208.15 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 143.65 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -517.81 | -24908.30 |
SMSTORE2 | 19-FEB-08:61 | 0.00 | 0.00 | 28051.79 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29.73 | 0.00 | -486.84 | -27610.03 |
SMSTORE3 | 19-FEB-08:61 | 0.00 | 0.00 | 28027.44 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27.04 | 0.00 | -481.65 | -27593.56 |
SMSTORE4 | 19-FEB-08:61 | 0.00 | 0.00 | 27979.32 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24.33 | 0.00 | -475.75 | -27554.06 |
LGSTORE2 | 20-NOV-08:61 | 0.00 | 0.00 | 45822.41 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -411.50 | 0.00 | -751.97 | -44807.58 |
SMSTORE5 | 20-NOV-08:61 | 0.00 | 0.00 | 24109.84 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -205.58 | 0.00 | -419.37 | -23559.21 |
SMSTORE6 | 20-NOV-08:61 | 0.00 | 0.00 | 23900.60 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -204.49 | 0.00 | -417.34 | -23353.08 |
SMSTORE7 | 20-NOV-08:61 | 0.00 | 0.00 | 23511.28 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -199.99 | 0.00 | -408.42 | -22977.19 |
SMSTORE8 | 10-JAN-08:13 | 0.00 | 0.00 | 24176.02 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -60.13 | 0.00 | -653.77 | -23536.45 |
Total Facility | 10-JAN-08:61 | 0.00 | 0.00 | 221883.36 | 0.00 | 0.00 | 0.00 | 734.80 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1587.13 | 0.00 | -6802.03 | -216131.24 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.4579 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.4579 | 0.2822 | 1.0000 | Not calculated | 0.4115 | 0.2822 | ||
PSZ-AC_2:2 | 0.8289 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8448 | 0.2435 | 1.0000 | Not calculated | 0.2057 | 0.2435 | ||
PSZ-AC_3:3 | 0.9680 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9680 | 0.2125 | 1.0000 | Not calculated | 0.2057 | 0.2125 | ||
PSZ-AC_4:4 | 0.9668 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9668 | 0.2128 | 1.0000 | Not calculated | 0.2057 | 0.2128 | ||
PSZ-AC_5:5 | 0.9646 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9646 | 0.2133 | 1.0000 | Not calculated | 0.2057 | 0.2133 | ||
PSZ-AC_6:6 | 1.4534 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.5054 | 0.2733 | 1.0000 | Not calculated | 0.4115 | 0.2733 | ||
PSZ-AC_7:7 | 0.7792 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.7945 | 0.2590 | 1.0000 | Not calculated | 0.2057 | 0.2590 | ||
PSZ-AC_8:8 | 0.7698 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.7863 | 0.2617 | 1.0000 | Not calculated | 0.2057 | 0.2617 | ||
PSZ-AC_9:9 | 0.7522 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.7715 | 0.2667 | 1.0000 | Not calculated | 0.2057 | 0.2667 | ||
PSZ-AC_10:10 | 0.7808 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.7808 | 0.2635 | 1.0000 | Not calculated | 0.2057 | 0.2635 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.4579 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.4579 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2822 | ||
PSZ-AC_2:2 | 0.8289 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8289 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2482 | ||
PSZ-AC_3:3 | 0.9680 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9680 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2125 | ||
PSZ-AC_4:4 | 0.9668 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9668 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2128 | ||
PSZ-AC_5:5 | 0.9646 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9646 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2133 | ||
PSZ-AC_6:6 | 1.4534 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.4534 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2831 | ||
PSZ-AC_7:7 | 0.7792 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.7792 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2640 | ||
PSZ-AC_8:8 | 0.7698 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.7698 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2673 | ||
PSZ-AC_9:9 | 0.7522 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.7522 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2735 | ||
PSZ-AC_10:10 | 0.7808 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.7808 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2635 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.003540 | 56.2505 | 0.000610 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.003540 | 56.2505 | 0.000610 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.003540 | 56.25 | 0.000610 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.003540 | 56.25 | 0.000610 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4579 | 1.4579 | 1.4579 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8289 | 0.8289 | 0.8289 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9680 | 0.9680 | 0.9680 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9668 | 0.9668 | 0.9668 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9646 | 0.9646 | 0.9646 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4534 | 1.4534 | 1.4534 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7792 | 0.7792 | 0.7792 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7698 | 0.7698 | 0.7698 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7522 | 0.7522 | 0.7522 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7808 | 0.7808 | 0.7808 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.4579 | 1.4579 | 1.4579 | 1.4579 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.8289 | 0.8448 | 0.8289 | 0.8289 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9680 | 0.9680 | 0.9680 | 0.9680 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9668 | 0.9668 | 0.9668 | 0.9668 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9646 | 0.9646 | 0.9646 | 0.9646 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.4534 | 1.5054 | 1.4534 | 1.4534 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.7792 | 0.7945 | 0.7792 | 0.7792 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.7698 | 0.7863 | 0.7698 | 0.7698 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.7522 | 0.7715 | 0.7522 | 0.7522 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.7808 | 0.7808 | 0.7808 | 0.7808 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4579 | 1.4579 | 1.4579 | No | 0.4115 | 0.4608 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8289 | 0.8289 | 0.8289 | No | 0.2057 | 0.4782 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9680 | 0.9680 | 0.9680 | No | 0.2057 | 0.4731 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9668 | 0.9668 | 0.9668 | No | 0.2057 | 0.4683 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9646 | 0.9646 | 0.9646 | No | 0.2057 | 0.4593 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4534 | 1.4534 | 1.4534 | No | 0.4115 | 0.4765 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7792 | 0.7792 | 0.7792 | No | 0.2057 | 0.4456 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7698 | 0.7698 | 0.7698 | No | 0.2057 | 0.4453 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7522 | 0.7522 | 0.7522 | No | 0.2057 | 0.4312 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7808 | 0.7808 | 0.7808 | No | 0.2057 | 0.3611 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.4579 | 1.4579 | 1.4579 | 1.4579 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.8289 | 0.8289 | 0.8289 | 0.8289 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9680 | 0.9680 | 0.9680 | 0.9680 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9668 | 0.9668 | 0.9668 | 0.9668 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9646 | 0.9646 | 0.9646 | 0.9646 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.4534 | 1.4534 | 1.4534 | 1.4534 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.7792 | 0.7792 | 0.7792 | 0.7792 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.7698 | 0.7698 | 0.7698 | 0.7698 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.7522 | 0.7522 | 0.7522 | 0.7522 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.7808 | 0.7808 | 0.7808 | 0.7808 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 256.74 | 110771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 5.56 | 16932.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 277.79 | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 41.18 | 3786.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 152.18 | 9596.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 65.02 | 11860.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 669.89 |
Natural Gas | 0.00 | 256.74 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 926.63 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 53.09 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 132.89 |
Space Heating | 0.00 |
Space Cooling | 2.66 |
Fans (All) | 72.80 |
Service Water Heating | 31.11 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 320.47 |
Subtotal | 320.47 |
Natural Gas [MJ/m2] | |
Space Heating | 122.82 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 122.82 |
Subtotal | 122.82 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 29.98 |
Space Heating | 27.71 |
Space Cooling | 0.60 |
Fans (All) | 16.42 |
Service Water Heating | 7.02 |
Receptacle Equipment | 13.83 |
Miscellaneous | 4.44 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3140. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3200. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4323. | 8760. |
LTG_SCH_BASE_LPD1 | 4243. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3479. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 87600.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25475.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25475.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25475.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93211.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 25475.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93211.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 48610.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 486102.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8758.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1.67 | 0.00 | 0.00 | 0.00 |
Average | 8759.53 | 0.47 | 0.00 | 0.00 | 0.00 |
Sum | 87595.33 | 4.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25474.17 | 0.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25474.17 | 0.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25474.17 | 0.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93211.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 25474.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93211.00 | 0.83 | 0.00 | 0.00 | 0.00 |
Average | 48609.95 | 0.25 | 0.00 | 0.00 | 0.00 |
Sum | 486099.50 | 2.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:23
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100874E+10 | 7498.81 | 10-JAN-21:53 | -5.0 | -7.7 | 0.106569E+10 | 1275.40 | 16-JAN-18:00 | 4.00 | 3.53 |
February | 0.969886E+09 | 5085.75 | 17-FEB-00:12 | -1.3 | -1.3 | 0.961998E+09 | 1275.40 | 04-FEB-13:09 | -1.3 | -1.3 |
March | 0.137340E+10 | 4421.93 | 14-MAR-22:05 | 1.00 | 0.19 | 0.105652E+10 | 1279.64 | 19-MAR-17:19 | 11.67 | 10.77 |
April | 0.373385E+10 | 7049.30 | 30-APR-16:13 | 24.00 | 12.95 | 0.110464E+10 | 1685.85 | 30-APR-12:09 | 24.00 | 12.95 |
May | 0.425037E+10 | 5302.15 | 23-MAY-17:10 | 18.00 | 13.65 | 0.117113E+10 | 1685.85 | 21-MAY-17:00 | 18.00 | 13.65 |
June | 0.517456E+10 | 8502.99 | 13-JUN-17:00 | 27.00 | 17.53 | 0.128735E+10 | 1685.91 | 25-JUN-17:30 | 21.50 | 17.05 |
July | 0.634116E+10 | 9789.28 | 22-JUL-16:20 | 29.00 | 16.57 | 0.138982E+10 | 1685.93 | 23-JUL-17:10 | 21.00 | 16.54 |
August | 0.638586E+10 | 8370.22 | 14-AUG-17:00 | 27.00 | 14.39 | 0.139197E+10 | 1685.93 | 18-AUG-12:00 | 21.00 | 16.54 |
September | 0.518635E+10 | 6983.47 | 13-SEP-16:10 | 23.00 | 16.14 | 0.133119E+10 | 1685.92 | 10-SEP-16:10 | 23.00 | 16.14 |
October | 0.347814E+10 | 5425.73 | 03-OCT-19:00 | 6.00 | 5.05 | 0.112605E+10 | 1590.90 | 07-OCT-12:00 | 17.00 | 9.21 |
November | 0.154317E+10 | 3695.74 | 03-NOV-23:05 | 4.00 | 2.72 | 0.103088E+10 | 1275.40 | 24-NOV-13:09 | 12.17 | 11.07 |
December | 0.785830E+09 | 6937.13 | 30-DEC-18:23 | 0.00 | -0.9 | 0.107094E+10 | 1275.40 | 17-DEC-18:00 | 0.00 | -0.9 |
Annual Sum or Average | 0.402313E+11 | 0.139882E+11 | ||||||||
Minimum of Months | 0.785830E+09 | 3695.74 | -5.0 | -7.7 | 0.961998E+09 | 1275.40 | -1.3 | -1.3 | ||
Maximum of Months | 0.638586E+10 | 9789.28 | 29.00 | 17.53 | 0.139197E+10 | 1685.93 | 24.00 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.494247E+09 | 1970.36 | 19-JAN-18:10 | 4.67 | 4.12 | 0.550381E+09 | 767.16 | 29-JAN-18:00 | 9.00 | 8.43 |
February | 0.464178E+09 | 1932.23 | 27-FEB-18:40 | 5.67 | 5.50 | 0.496260E+09 | 757.66 | 05-FEB-18:00 | 5.67 | 5.50 |
March | 0.653853E+09 | 1904.54 | 23-MAR-19:00 | 6.00 | 4.60 | 0.549808E+09 | 784.03 | 19-MAR-17:00 | 6.00 | 4.60 |
April | 0.156295E+10 | 15215.00 | 29-APR-18:40 | 18.67 | 11.76 | 0.610145E+09 | 842.91 | 30-APR-17:00 | 24.00 | 13.13 |
May | 0.181052E+10 | 14859.90 | 21-MAY-17:09 | 20.00 | 12.86 | 0.647630E+09 | 842.90 | 07-MAY-17:00 | 20.00 | 12.86 |
June | 0.283961E+10 | 12854.30 | 25-JUN-17:08 | 21.17 | 15.04 | 0.672690E+09 | 842.91 | 25-JUN-17:10 | 21.17 | 15.04 |
July | 0.379010E+10 | 13152.42 | 21-JUL-20:23 | 19.00 | 14.59 | 0.704774E+09 | 842.93 | 23-JUL-17:10 | 21.00 | 16.54 |
August | 0.400222E+10 | 15509.79 | 14-AUG-20:44 | 18.62 | 11.98 | 0.696582E+09 | 842.93 | 18-AUG-12:00 | 21.00 | 16.54 |
September | 0.308993E+10 | 13319.08 | 24-SEP-17:50 | 19.33 | 14.40 | 0.681181E+09 | 842.93 | 10-SEP-16:10 | 19.33 | 14.40 |
October | 0.133177E+10 | 3858.65 | 01-OCT-17:10 | 11.83 | 8.82 | 0.627889E+09 | 842.90 | 01-OCT-17:00 | 11.00 | 8.39 |
November | 0.701236E+09 | 2166.10 | 03-NOV-17:30 | 4.50 | 3.19 | 0.540932E+09 | 775.58 | 05-NOV-17:00 | 6.00 | 5.05 |
December | 0.373220E+09 | 1600.32 | 20-DEC-19:10 | 7.67 | 7.21 | 0.550380E+09 | 722.58 | 17-DEC-18:00 | 7.67 | 7.21 |
Annual Sum or Average | 0.211138E+11 | 0.732865E+10 | ||||||||
Minimum of Months | 0.373220E+09 | 1600.32 | 4.50 | 3.19 | 0.496260E+09 | 722.58 | 5.67 | 4.60 | ||
Maximum of Months | 0.400222E+10 | 15509.79 | 21.17 | 15.04 | 0.704774E+09 | 842.93 | 24.00 | 16.54 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280683E+09 | 2385.69 | 11-JAN-19:45 | -4.2 | -5.5 | 0.317452E+09 | 637.68 | 21-JAN-13:09 | 7.83 | 6.08 |
February | 0.284292E+09 | 1655.46 | 27-FEB-18:10 | 6.67 | 6.23 | 0.288169E+09 | 637.68 | 04-FEB-13:09 | 6.67 | 6.23 |
March | 0.431994E+09 | 1733.43 | 10-MAR-18:30 | 6.15 | 4.16 | 0.327241E+09 | 691.05 | 25-MAR-12:00 | 14.00 | 11.22 |
April | 0.107791E+10 | 3550.16 | 30-APR-15:00 | 24.00 | 13.13 | 0.356939E+09 | 842.90 | 22-APR-12:09 | 24.00 | 13.13 |
May | 0.125136E+10 | 2978.42 | 23-MAY-17:10 | 18.00 | 13.65 | 0.383991E+09 | 842.90 | 27-MAY-12:09 | 15.83 | 10.60 |
June | 0.186736E+10 | 4472.82 | 13-JUN-17:00 | 27.00 | 17.53 | 0.413055E+09 | 842.89 | 24-JUN-12:20 | 16.67 | 12.61 |
July | 0.251139E+10 | 7757.77 | 23-JUL-07:03 | 18.17 | 14.53 | 0.418679E+09 | 842.91 | 22-JUL-12:09 | 18.17 | 14.53 |
August | 0.274831E+10 | 4366.62 | 14-AUG-16:20 | 26.33 | 15.41 | 0.430960E+09 | 842.92 | 19-AUG-12:00 | 21.00 | 15.44 |
September | 0.203209E+10 | 3787.88 | 13-SEP-16:10 | 23.00 | 16.14 | 0.409044E+09 | 842.89 | 02-SEP-12:30 | 23.00 | 16.14 |
October | 0.919127E+09 | 2359.30 | 02-OCT-17:20 | 11.33 | 8.60 | 0.363125E+09 | 842.90 | 07-OCT-12:20 | 16.33 | 10.17 |
November | 0.469882E+09 | 1985.34 | 03-NOV-17:30 | 4.50 | 3.19 | 0.308891E+09 | 642.24 | 25-NOV-13:39 | 10.00 | 5.65 |
December | 0.203873E+09 | 1450.72 | 30-DEC-11:55 | 3.00 | -0.4 | 0.316804E+09 | 637.68 | 23-DEC-13:09 | 3.00 | -0.4 |
Annual Sum or Average | 0.140783E+11 | 0.433435E+10 | ||||||||
Minimum of Months | 0.203873E+09 | 1450.72 | -4.2 | -5.5 | 0.288169E+09 | 637.68 | 3.00 | -0.4 | ||
Maximum of Months | 0.274831E+10 | 7757.77 | 27.00 | 17.53 | 0.430960E+09 | 842.92 | 24.00 | 16.14 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231591E+09 | 1638.18 | 19-JAN-18:10 | 4.67 | 4.12 | 0.317317E+09 | 637.68 | 21-JAN-13:09 | 7.83 | 6.08 |
February | 0.243815E+09 | 1632.10 | 16-FEB-20:55 | -1.0 | -1.0 | 0.288128E+09 | 637.68 | 04-FEB-13:09 | -1.0 | -1.0 |
March | 0.379161E+09 | 1681.45 | 10-MAR-18:20 | 6.43 | 4.33 | 0.326884E+09 | 685.58 | 25-MAR-12:00 | 14.00 | 11.22 |
April | 0.100579E+10 | 3461.49 | 30-APR-15:00 | 24.00 | 13.13 | 0.353685E+09 | 842.90 | 22-APR-12:09 | 24.00 | 13.13 |
May | 0.119055E+10 | 2858.08 | 23-MAY-17:10 | 18.00 | 13.65 | 0.380383E+09 | 842.90 | 27-MAY-12:09 | 15.83 | 10.60 |
June | 0.179604E+10 | 4412.38 | 13-JUN-17:00 | 27.00 | 17.53 | 0.412364E+09 | 842.89 | 24-JUN-12:20 | 16.67 | 12.61 |
July | 0.245868E+10 | 7872.76 | 23-JUL-07:03 | 18.17 | 14.53 | 0.418477E+09 | 842.91 | 22-JUL-12:09 | 18.17 | 14.53 |
August | 0.270607E+10 | 4321.01 | 14-AUG-16:20 | 26.33 | 15.41 | 0.430945E+09 | 842.92 | 19-AUG-12:00 | 21.00 | 15.44 |
September | 0.196457E+10 | 3749.02 | 13-SEP-16:10 | 23.00 | 16.14 | 0.408870E+09 | 842.89 | 09-SEP-12:09 | 23.00 | 16.14 |
October | 0.835859E+09 | 2262.75 | 03-OCT-17:20 | 12.00 | 8.35 | 0.359996E+09 | 842.90 | 07-OCT-12:20 | 16.33 | 10.17 |
November | 0.404555E+09 | 1965.23 | 10-NOV-19:00 | 5.00 | 4.51 | 0.308260E+09 | 637.70 | 25-NOV-13:09 | 10.00 | 5.84 |
December | 0.167226E+09 | 2104.62 | 29-DEC-19:55 | -2.0 | -3.5 | 0.316800E+09 | 637.68 | 23-DEC-13:09 | -2.0 | -3.5 |
Annual Sum or Average | 0.133839E+11 | 0.432211E+10 | ||||||||
Minimum of Months | 0.167226E+09 | 1632.10 | -2.0 | -3.5 | 0.288128E+09 | 637.68 | -2.0 | -3.5 | ||
Maximum of Months | 0.270607E+10 | 7872.76 | 27.00 | 17.53 | 0.430945E+09 | 842.92 | 24.00 | 16.14 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165406E+09 | 1580.41 | 03-JAN-19:05 | 2.08 | 1.45 | 0.317193E+09 | 637.68 | 21-JAN-13:09 | 7.83 | 6.08 |
February | 0.173727E+09 | 1344.39 | 09-FEB-18:10 | 3.83 | 3.45 | 0.288102E+09 | 637.68 | 04-FEB-13:09 | 3.83 | 3.45 |
March | 0.289495E+09 | 1561.19 | 30-MAR-18:00 | 7.00 | 4.68 | 0.326325E+09 | 673.55 | 25-MAR-12:00 | 7.00 | 4.68 |
April | 0.840372E+09 | 3189.02 | 30-APR-15:00 | 24.00 | 13.13 | 0.346999E+09 | 842.90 | 22-APR-12:09 | 24.00 | 13.13 |
May | 0.102173E+10 | 2569.86 | 23-MAY-17:10 | 18.00 | 13.65 | 0.371924E+09 | 842.90 | 27-MAY-12:09 | 15.83 | 10.60 |
June | 0.152461E+10 | 4204.22 | 13-JUN-17:00 | 27.00 | 17.53 | 0.409087E+09 | 842.89 | 24-JUN-12:20 | 16.67 | 12.61 |
July | 0.221718E+10 | 6691.87 | 23-JUL-07:03 | 18.17 | 14.53 | 0.417636E+09 | 842.91 | 22-JUL-12:09 | 18.17 | 14.53 |
August | 0.249256E+10 | 4168.32 | 14-AUG-16:20 | 26.33 | 15.41 | 0.430875E+09 | 842.92 | 19-AUG-12:00 | 21.00 | 15.44 |
September | 0.170727E+10 | 3581.03 | 13-SEP-16:10 | 23.00 | 16.14 | 0.407879E+09 | 842.90 | 09-SEP-12:09 | 23.00 | 16.14 |
October | 0.670907E+09 | 1714.06 | 06-OCT-17:10 | 15.33 | 8.98 | 0.352968E+09 | 842.90 | 07-OCT-12:50 | 16.83 | 9.46 |
November | 0.304226E+09 | 1865.60 | 10-NOV-18:30 | 5.50 | 5.00 | 0.307507E+09 | 637.69 | 25-NOV-13:09 | 10.00 | 5.84 |
December | 0.115085E+09 | 1567.96 | 27-DEC-19:05 | 2.17 | 1.67 | 0.316786E+09 | 637.68 | 23-DEC-13:09 | 2.17 | 1.67 |
Annual Sum or Average | 0.115226E+11 | 0.429328E+10 | ||||||||
Minimum of Months | 0.115085E+09 | 1344.39 | 2.08 | 1.45 | 0.288102E+09 | 637.68 | 2.17 | 1.67 | ||
Maximum of Months | 0.249256E+10 | 6691.87 | 27.00 | 17.53 | 0.430875E+09 | 842.92 | 24.00 | 16.14 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130400E+09 | 4055.65 | 13-JAN-11:45 | 7.17 | 5.20 | 0.108442E+10 | 1700.53 | 07-JAN-15:39 | 7.17 | 5.20 |
February | 0.131277E+09 | 5360.38 | 23-FEB-19:33 | 1.33 | 1.33 | 0.987307E+09 | 1700.53 | 04-FEB-15:20 | 1.33 | 1.33 |
March | 0.317240E+09 | 4781.81 | 03-MAR-11:15 | 5.00 | 4.09 | 0.111839E+10 | 1700.53 | 04-MAR-15:20 | 6.00 | 4.07 |
April | 0.201965E+10 | 5930.37 | 30-APR-15:00 | 24.00 | 13.13 | 0.112595E+10 | 2247.81 | 29-APR-14:00 | 24.00 | 13.13 |
May | 0.255286E+10 | 5019.51 | 01-MAY-13:00 | 8.00 | 6.09 | 0.118953E+10 | 2108.30 | 27-MAY-14:09 | 15.67 | 10.94 |
June | 0.341453E+10 | 7146.68 | 13-JUN-17:00 | 27.00 | 17.53 | 0.132213E+10 | 2247.82 | 24-JUN-14:20 | 18.67 | 13.47 |
July | 0.400159E+10 | 9588.05 | 22-JUL-15:00 | 29.00 | 17.00 | 0.140336E+10 | 2247.82 | 22-JUL-14:00 | 29.00 | 17.00 |
August | 0.420687E+10 | 7347.01 | 14-AUG-16:20 | 26.33 | 15.41 | 0.147627E+10 | 2247.89 | 19-AUG-14:00 | 20.00 | 15.13 |
September | 0.334413E+10 | 6474.16 | 13-SEP-14:20 | 23.00 | 16.22 | 0.135557E+10 | 2247.84 | 23-SEP-14:39 | 19.00 | 14.78 |
October | 0.176874E+10 | 4283.30 | 03-OCT-19:00 | 6.00 | 5.05 | 0.113319E+10 | 2247.39 | 07-OCT-14:00 | 19.00 | 10.10 |
November | 0.351384E+09 | 3630.97 | 03-NOV-13:35 | 9.00 | 5.60 | 0.104452E+10 | 1700.53 | 04-NOV-14:30 | 9.00 | 6.58 |
December | 53060953.34 | 4759.73 | 12-DEC-18:45 | 4.00 | 3.12 | 0.108625E+10 | 1700.53 | 02-DEC-15:00 | 4.00 | 3.12 |
Annual Sum or Average | 0.222917E+11 | 0.143269E+11 | ||||||||
Minimum of Months | 53060953.34 | 3630.97 | 1.33 | 1.33 | 0.987307E+09 | 1700.53 | 1.33 | 1.33 | ||
Maximum of Months | 0.420687E+10 | 9588.05 | 29.00 | 17.53 | 0.147627E+10 | 2247.89 | 29.00 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 56339103.65 | 1233.17 | 21-JAN-12:00 | 7.00 | 5.55 | 0.542177E+09 | 850.24 | 07-JAN-15:00 | 7.00 | 5.55 |
February | 53584341.57 | 1964.43 | 23-FEB-19:15 | 1.67 | 1.67 | 0.493631E+09 | 850.24 | 04-FEB-15:30 | 1.67 | 1.67 |
March | 0.136588E+09 | 1935.32 | 15-MAR-17:25 | 3.00 | 2.16 | 0.559193E+09 | 850.27 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.752746E+09 | 3043.89 | 30-APR-15:00 | 24.00 | 13.13 | 0.570482E+09 | 1123.87 | 29-APR-14:00 | 24.00 | 13.13 |
May | 0.930452E+09 | 2006.05 | 01-MAY-13:00 | 8.00 | 6.09 | 0.605383E+09 | 1093.63 | 27-MAY-14:09 | 15.67 | 10.94 |
June | 0.131577E+10 | 3674.53 | 13-JUN-17:00 | 27.00 | 17.53 | 0.676476E+09 | 1123.86 | 17-JUN-14:50 | 16.00 | 12.75 |
July | 0.182541E+10 | 4966.33 | 22-JUL-15:00 | 29.00 | 17.00 | 0.708157E+09 | 1123.87 | 22-JUL-14:09 | 29.00 | 17.00 |
August | 0.204197E+10 | 3802.36 | 14-AUG-16:20 | 26.33 | 15.41 | 0.739264E+09 | 1123.89 | 12-AUG-14:09 | 26.33 | 15.41 |
September | 0.137954E+10 | 3308.95 | 13-SEP-14:30 | 23.00 | 16.22 | 0.690630E+09 | 1123.84 | 09-SEP-14:09 | 23.00 | 16.22 |
October | 0.617861E+09 | 1631.67 | 03-OCT-19:00 | 6.00 | 5.05 | 0.575914E+09 | 1123.86 | 07-OCT-14:30 | 18.00 | 10.02 |
November | 0.148179E+09 | 1525.73 | 25-NOV-14:35 | 9.33 | 5.40 | 0.522327E+09 | 850.24 | 18-NOV-15:09 | 9.33 | 5.40 |
December | 21448510.67 | 1592.25 | 22-DEC-19:35 | 4.33 | 3.72 | 0.543110E+09 | 850.24 | 09-DEC-15:20 | 4.33 | 3.72 |
Annual Sum or Average | 0.927988E+10 | 0.722674E+10 | ||||||||
Minimum of Months | 21448510.67 | 1233.17 | 1.67 | 1.67 | 0.493631E+09 | 850.24 | 1.67 | 1.67 | ||
Maximum of Months | 0.204197E+10 | 4966.33 | 29.00 | 17.53 | 0.739264E+09 | 1123.89 | 29.00 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52833516.97 | 1722.05 | 14-JAN-11:35 | 7.00 | 6.83 | 0.542163E+09 | 850.24 | 07-JAN-15:09 | 7.00 | 6.83 |
February | 44565630.57 | 1211.38 | 04-FEB-12:00 | 8.00 | 5.24 | 0.493638E+09 | 850.24 | 04-FEB-15:39 | 7.67 | 5.90 |
March | 0.123595E+09 | 1884.22 | 02-MAR-19:45 | 2.33 | 1.77 | 0.559165E+09 | 850.25 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.718231E+09 | 2972.58 | 30-APR-15:00 | 24.00 | 13.13 | 0.568980E+09 | 1123.87 | 29-APR-14:00 | 24.00 | 13.13 |
May | 0.889509E+09 | 2001.43 | 01-MAY-13:00 | 8.00 | 6.09 | 0.603132E+09 | 1087.50 | 27-MAY-14:09 | 15.67 | 10.94 |
June | 0.127711E+10 | 3593.98 | 13-JUN-17:00 | 27.00 | 17.53 | 0.673520E+09 | 1123.85 | 17-JUN-14:00 | 16.00 | 12.58 |
July | 0.176718E+10 | 4912.54 | 22-JUL-15:00 | 29.00 | 17.00 | 0.707090E+09 | 1123.87 | 22-JUL-14:09 | 29.00 | 17.00 |
August | 0.197583E+10 | 3738.88 | 14-AUG-16:20 | 26.33 | 15.41 | 0.739215E+09 | 1123.89 | 12-AUG-14:09 | 26.33 | 15.41 |
September | 0.133940E+10 | 3245.15 | 13-SEP-14:30 | 23.00 | 16.22 | 0.689307E+09 | 1123.84 | 09-SEP-14:09 | 23.00 | 16.22 |
October | 0.594008E+09 | 1629.57 | 03-OCT-19:00 | 6.00 | 5.05 | 0.574000E+09 | 1123.85 | 07-OCT-14:00 | 19.00 | 10.10 |
November | 0.134534E+09 | 1326.03 | 25-NOV-12:00 | 10.00 | 5.90 | 0.522314E+09 | 850.24 | 25-NOV-15:39 | 8.33 | 4.99 |
December | 19309476.24 | 1839.74 | 21-DEC-19:15 | 2.67 | 2.67 | 0.543099E+09 | 850.24 | 02-DEC-15:09 | 2.67 | 2.67 |
Annual Sum or Average | 0.893611E+10 | 0.721562E+10 | ||||||||
Minimum of Months | 19309476.24 | 1211.38 | 2.33 | 1.77 | 0.493638E+09 | 850.24 | 2.67 | 2.67 | ||
Maximum of Months | 0.197583E+10 | 4912.54 | 29.00 | 17.53 | 0.739215E+09 | 1123.89 | 29.00 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26653859.51 | 1483.05 | 26-JAN-19:45 | 5.33 | 4.84 | 0.542179E+09 | 850.24 | 07-JAN-15:39 | 5.33 | 4.84 |
February | 19569264.79 | 1503.45 | 08-FEB-19:05 | 5.17 | 4.46 | 0.493640E+09 | 850.24 | 04-FEB-15:39 | 5.17 | 4.46 |
March | 70056423.88 | 1847.22 | 04-MAR-11:35 | 6.33 | 3.86 | 0.559167E+09 | 850.24 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.596032E+09 | 2766.66 | 30-APR-15:00 | 24.00 | 13.13 | 0.564733E+09 | 1123.84 | 29-APR-14:00 | 24.00 | 13.13 |
May | 0.752694E+09 | 1968.82 | 01-MAY-13:00 | 8.00 | 6.09 | 0.596053E+09 | 1061.04 | 27-MAY-14:20 | 15.33 | 10.81 |
June | 0.114641E+10 | 3395.95 | 13-JUN-17:00 | 27.00 | 17.53 | 0.662255E+09 | 1123.84 | 24-JUN-14:09 | 18.83 | 13.61 |
July | 0.157928E+10 | 4786.41 | 22-JUL-15:00 | 29.00 | 17.00 | 0.702806E+09 | 1123.87 | 22-JUL-14:09 | 29.00 | 17.00 |
August | 0.175270E+10 | 3546.80 | 14-AUG-16:20 | 26.33 | 15.41 | 0.738788E+09 | 1123.89 | 12-AUG-14:09 | 26.33 | 15.41 |
September | 0.119178E+10 | 3067.62 | 13-SEP-14:40 | 23.00 | 16.22 | 0.682177E+09 | 1123.84 | 09-SEP-14:09 | 23.00 | 16.22 |
October | 0.502587E+09 | 1594.01 | 03-OCT-19:00 | 6.00 | 5.05 | 0.567707E+09 | 1123.73 | 07-OCT-14:00 | 19.00 | 10.10 |
November | 86985670.31 | 1525.79 | 17-NOV-19:55 | 5.00 | 4.09 | 0.522234E+09 | 850.24 | 18-NOV-15:20 | 8.67 | 6.28 |
December | 9266684.83 | 2067.81 | 21-DEC-18:35 | 2.33 | 2.33 | 0.543098E+09 | 850.24 | 02-DEC-15:20 | 2.33 | 2.33 |
Annual Sum or Average | 0.773401E+10 | 0.717484E+10 | ||||||||
Minimum of Months | 9266684.83 | 1483.05 | 2.33 | 2.33 | 0.493640E+09 | 850.24 | 2.33 | 2.33 | ||
Maximum of Months | 0.175270E+10 | 4786.41 | 29.00 | 17.53 | 0.738788E+09 | 1123.89 | 29.00 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2501549.23 | 1549.99 | 20-JAN-11:15 | 6.67 | 5.72 | 0.542192E+09 | 850.24 | 07-JAN-15:09 | 6.67 | 5.72 |
February | 1346877.08 | 940.15 | 22-FEB-11:40 | 10.00 | 8.60 | 0.493633E+09 | 850.24 | 18-FEB-15:39 | 10.00 | 8.60 |
March | 6852028.16 | 1081.38 | 31-MAR-17:50 | 8.17 | 4.55 | 0.559174E+09 | 850.24 | 04-MAR-15:39 | 8.17 | 4.55 |
April | 0.398995E+09 | 2548.64 | 30-APR-15:00 | 24.00 | 13.13 | 0.560537E+09 | 1123.84 | 29-APR-14:00 | 24.00 | 13.13 |
May | 0.491987E+09 | 1545.14 | 01-MAY-14:40 | 9.33 | 7.44 | 0.587301E+09 | 1017.21 | 27-MAY-14:09 | 15.67 | 10.94 |
June | 0.963551E+09 | 3281.38 | 13-JUN-17:00 | 27.00 | 17.53 | 0.643370E+09 | 1123.85 | 24-JUN-14:09 | 18.83 | 13.61 |
July | 0.134246E+10 | 4814.44 | 22-JUL-15:00 | 29.00 | 17.00 | 0.695039E+09 | 1123.87 | 22-JUL-14:09 | 29.00 | 17.00 |
August | 0.146857E+10 | 3360.56 | 14-AUG-16:20 | 26.33 | 15.41 | 0.736420E+09 | 1123.89 | 12-AUG-14:09 | 26.33 | 15.41 |
September | 0.101342E+10 | 2931.98 | 13-SEP-14:20 | 23.00 | 16.22 | 0.668918E+09 | 1123.85 | 09-SEP-14:09 | 23.00 | 16.22 |
October | 0.320659E+09 | 1478.67 | 03-OCT-19:00 | 6.00 | 5.05 | 0.560298E+09 | 1108.64 | 07-OCT-14:00 | 19.00 | 10.10 |
November | 12403080.18 | 1252.31 | 15-NOV-19:00 | 7.00 | 6.47 | 0.522239E+09 | 850.24 | 04-NOV-14:20 | 7.00 | 6.47 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 | 3.53 | 0.543112E+09 | 850.24 | 02-DEC-15:20 | 8.67 | 7.78 |
Annual Sum or Average | 0.602274E+10 | 0.711223E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.00 | 3.53 | 0.493633E+09 | 850.24 | 6.67 | 4.55 | ||
Maximum of Months | 0.146857E+10 | 4814.44 | 29.00 | 17.53 | 0.736420E+09 | 1123.89 | 29.00 | 17.00 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296559E+10 | 45901.44 | 31-JAN-08:61 | 1.17 |
February | 0.228326E+10 | 45905.47 | 17-FEB-08:61 | -2.3 |
March | 0.203413E+10 | 45904.97 | 03-MAR-08:61 | 3.17 |
April | 0.364275E+09 | 45763.81 | 08-APR-07:01 | 2.50 |
May | 0.189719E+09 | 45739.55 | 05-MAY-07:01 | 7.17 |
June | 55307124.80 | 8672.16 | 08-JUN-07:02 | 10.17 |
July | 46338599.40 | 769.44 | 23-JUL-07:07 | 18.17 |
August | 55980210.58 | 583.90 | 25-AUG-08:00 | 17.00 |
September | 59488203.95 | 606.46 | 21-SEP-07:05 | 8.00 |
October | 0.360597E+09 | 45873.96 | 23-OCT-07:01 | 4.50 |
November | 0.154807E+10 | 45907.68 | 20-NOV-08:61 | 1.33 |
December | 0.346873E+10 | 45893.44 | 15-DEC-08:61 | 1.33 |
Annual Sum or Average | 0.134315E+11 | |||
Minimum of Months | 46338599.40 | 583.90 | -2.3 | |
Maximum of Months | 0.346873E+10 | 45907.68 | 18.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.916959E+09 | 25204.96 | 31-JAN-08:61 | 1.17 |
February | 0.602802E+09 | 25208.21 | 17-FEB-08:61 | -2.3 |
March | 0.487443E+09 | 25207.71 | 03-MAR-08:61 | 3.17 |
April | 0.103375E+09 | 20406.07 | 01-APR-07:01 | 4.17 |
May | 87030374.66 | 917.34 | 28-MAY-08:00 | 9.00 |
June | 39812241.30 | 891.64 | 08-JUN-07:02 | 10.17 |
July | 21085667.03 | 1168.16 | 23-JUL-07:07 | 18.17 |
August | 7247248.44 | 754.97 | 24-AUG-07:10 | 13.50 |
September | 46976983.65 | 891.49 | 08-SEP-08:00 | 12.00 |
October | 98073507.07 | 8809.97 | 23-OCT-07:01 | 4.50 |
November | 0.360956E+09 | 25207.69 | 20-NOV-08:61 | 1.33 |
December | 0.109991E+10 | 25202.55 | 15-DEC-08:61 | 1.33 |
Annual Sum or Average | 0.387167E+10 | |||
Minimum of Months | 7247248.44 | 754.97 | -2.3 | |
Maximum of Months | 0.109991E+10 | 25208.21 | 18.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124309E+10 | 28033.08 | 10-JAN-07:01 | -4.3 |
February | 0.891746E+09 | 28051.80 | 19-FEB-08:61 | 1.17 |
March | 0.722192E+09 | 27690.01 | 05-MAR-08:62 | 3.33 |
April | 0.140627E+09 | 13905.84 | 02-APR-07:02 | 5.17 |
May | 94481805.63 | 1197.79 | 06-MAY-06:05 | 3.50 |
June | 41689967.68 | 963.22 | 07-JUN-07:00 | 10.00 |
July | 30047244.40 | 1567.25 | 22-JUL-17:12 | 29.33 |
August | 14215578.48 | 828.07 | 24-AUG-06:10 | 8.83 |
September | 51883882.14 | 959.21 | 20-SEP-06:50 | 6.83 |
October | 0.121141E+09 | 9065.27 | 23-OCT-06:03 | 4.00 |
November | 0.599861E+09 | 27698.60 | 20-NOV-07:02 | 1.00 |
December | 0.145148E+10 | 28042.12 | 31-DEC-08:61 | 0.00 |
Annual Sum or Average | 0.540246E+10 | |||
Minimum of Months | 14215578.48 | 828.07 | -4.3 | |
Maximum of Months | 0.145148E+10 | 28051.80 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138956E+10 | 28009.07 | 10-JAN-07:01 | -4.3 |
February | 0.101536E+10 | 28027.45 | 19-FEB-08:61 | 1.17 |
March | 0.835740E+09 | 27666.04 | 05-MAR-08:62 | 3.33 |
April | 0.161896E+09 | 17592.26 | 02-APR-07:02 | 5.17 |
May | 97623560.93 | 2453.42 | 06-MAY-06:05 | 3.50 |
June | 48632837.89 | 961.08 | 07-JUN-07:00 | 10.00 |
July | 33735355.18 | 1566.91 | 22-JUL-17:12 | 29.33 |
August | 17721186.55 | 837.50 | 30-AUG-06:10 | 9.50 |
September | 58988859.20 | 998.88 | 21-SEP-07:00 | 7.00 |
October | 0.142923E+09 | 13004.11 | 23-OCT-06:03 | 4.00 |
November | 0.709261E+09 | 27685.54 | 19-NOV-08:62 | 4.00 |
December | 0.159505E+10 | 28017.72 | 31-DEC-08:61 | 0.00 |
Annual Sum or Average | 0.610649E+10 | |||
Minimum of Months | 17721186.55 | 837.50 | -4.3 | |
Maximum of Months | 0.159505E+10 | 28027.45 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163948E+10 | 27961.11 | 10-JAN-07:01 | -4.3 |
February | 0.122719E+10 | 27979.33 | 19-FEB-08:61 | 1.17 |
March | 0.104466E+10 | 27621.67 | 05-MAR-08:62 | 3.33 |
April | 0.204724E+09 | 21895.82 | 02-APR-07:02 | 5.17 |
May | 0.114359E+09 | 5034.25 | 07-MAY-07:03 | 8.33 |
June | 66280508.84 | 982.61 | 04-JUN-08:00 | 13.00 |
July | 45904497.85 | 1569.33 | 22-JUL-17:12 | 29.33 |
August | 32481143.65 | 861.94 | 13-AUG-07:10 | 13.17 |
September | 74164291.91 | 1000.67 | 21-SEP-07:00 | 7.00 |
October | 0.205138E+09 | 17098.52 | 23-OCT-06:03 | 4.00 |
November | 0.896031E+09 | 27639.03 | 19-NOV-08:62 | 4.00 |
December | 0.185247E+10 | 27969.62 | 31-DEC-08:61 | 0.00 |
Annual Sum or Average | 0.740289E+10 | |||
Minimum of Months | 32481143.65 | 861.94 | -4.3 | |
Maximum of Months | 0.185247E+10 | 27979.33 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.320252E+10 | 45814.72 | 31-JAN-08:61 | 1.17 |
February | 0.234577E+10 | 45814.25 | 17-FEB-08:61 | -2.3 |
March | 0.200379E+10 | 45813.69 | 03-MAR-08:61 | 3.17 |
April | 0.421972E+09 | 45765.13 | 02-APR-08:61 | 7.33 |
May | 0.183749E+09 | 45651.04 | 05-MAY-07:01 | 7.17 |
June | 58697685.29 | 8952.27 | 08-JUN-07:02 | 10.17 |
July | 54826766.69 | 1896.31 | 22-JUL-17:12 | 29.33 |
August | 56804896.40 | 611.83 | 08-AUG-08:00 | 17.00 |
September | 61212209.81 | 634.67 | 21-SEP-07:05 | 8.00 |
October | 0.469340E+09 | 45792.66 | 23-OCT-07:01 | 4.50 |
November | 0.176403E+10 | 45822.42 | 20-NOV-08:61 | 1.33 |
December | 0.363093E+10 | 45806.23 | 18-DEC-08:61 | 1.00 |
Annual Sum or Average | 0.142536E+11 | |||
Minimum of Months | 54826766.69 | 611.83 | -2.3 | |
Maximum of Months | 0.363093E+10 | 45822.42 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187629E+10 | 24105.78 | 31-JAN-08:61 | 1.17 |
February | 0.140663E+10 | 24105.80 | 17-FEB-08:61 | -2.3 |
March | 0.122656E+10 | 24104.91 | 03-MAR-08:61 | 3.17 |
April | 0.281102E+09 | 24078.93 | 02-APR-08:61 | 7.33 |
May | 0.156880E+09 | 24016.31 | 05-MAY-07:01 | 7.17 |
June | 74011285.40 | 5025.84 | 08-JUN-07:02 | 10.17 |
July | 58460602.59 | 1455.82 | 22-JUL-17:12 | 29.33 |
August | 55421247.71 | 775.83 | 28-AUG-07:50 | 17.33 |
September | 77957967.63 | 836.13 | 08-SEP-08:00 | 12.00 |
October | 0.323950E+09 | 24094.13 | 23-OCT-07:01 | 4.50 |
November | 0.107944E+10 | 24109.85 | 20-NOV-08:61 | 1.33 |
December | 0.210119E+10 | 24101.65 | 27-DEC-08:61 | -1.0 |
Annual Sum or Average | 0.871790E+10 | |||
Minimum of Months | 55421247.71 | 775.83 | -2.3 | |
Maximum of Months | 0.210119E+10 | 24109.85 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194316E+10 | 23896.04 | 31-JAN-08:61 | 1.17 |
February | 0.146308E+10 | 23896.21 | 17-FEB-08:61 | -2.3 |
March | 0.128521E+10 | 23895.69 | 03-MAR-08:61 | 3.17 |
April | 0.303016E+09 | 23869.81 | 02-APR-08:61 | 7.33 |
May | 0.170150E+09 | 23808.29 | 05-MAY-07:01 | 7.17 |
June | 76108236.89 | 7508.42 | 08-JUN-07:02 | 10.17 |
July | 61377771.12 | 1449.64 | 22-JUL-17:12 | 29.33 |
August | 61177164.71 | 782.21 | 30-AUG-07:50 | 13.67 |
September | 79031913.57 | 828.15 | 08-SEP-08:00 | 12.00 |
October | 0.351013E+09 | 23884.53 | 23-OCT-07:01 | 4.50 |
November | 0.113151E+10 | 23900.60 | 20-NOV-08:61 | 1.33 |
December | 0.216226E+10 | 23892.06 | 27-DEC-08:61 | -1.0 |
Annual Sum or Average | 0.908711E+10 | |||
Minimum of Months | 61177164.71 | 782.21 | -2.3 | |
Maximum of Months | 0.216226E+10 | 23900.60 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226647E+10 | 23506.98 | 31-JAN-08:61 | 1.17 |
February | 0.176145E+10 | 23507.23 | 17-FEB-08:61 | -2.3 |
March | 0.156834E+10 | 23506.60 | 03-MAR-08:61 | 3.17 |
April | 0.404386E+09 | 23479.92 | 02-APR-08:61 | 7.33 |
May | 0.243249E+09 | 23421.59 | 05-MAY-07:01 | 7.17 |
June | 83510629.27 | 16279.93 | 08-JUN-07:02 | 10.17 |
July | 73179145.20 | 1439.69 | 22-JUL-17:12 | 29.33 |
August | 77463375.57 | 800.02 | 10-AUG-08:00 | 17.00 |
September | 82197393.34 | 814.75 | 08-SEP-08:00 | 12.00 |
October | 0.470640E+09 | 23495.27 | 23-OCT-07:01 | 4.50 |
November | 0.137915E+10 | 23511.29 | 20-NOV-08:61 | 1.33 |
December | 0.249819E+10 | 23502.63 | 18-DEC-08:61 | 1.00 |
Annual Sum or Average | 0.109082E+11 | |||
Minimum of Months | 73179145.20 | 800.02 | -2.3 | |
Maximum of Months | 0.249819E+10 | 23511.29 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.359239E+10 | 24176.07 | 10-JAN-08:13 | -5.3 |
February | 0.296861E+10 | 24142.16 | 17-FEB-08:61 | -2.3 |
March | 0.276372E+10 | 24141.18 | 03-MAR-08:61 | 3.17 |
April | 0.799252E+09 | 24110.57 | 02-APR-08:61 | 7.33 |
May | 0.562822E+09 | 24046.08 | 05-MAY-07:01 | 7.17 |
June | 0.116701E+09 | 23713.74 | 08-JUN-07:02 | 10.17 |
July | 91830522.11 | 10684.27 | 05-JUL-07:03 | 12.17 |
August | 84952447.85 | 812.72 | 08-AUG-08:00 | 17.00 |
September | 90154067.88 | 4699.94 | 07-SEP-07:05 | 10.33 |
October | 0.963492E+09 | 24126.20 | 23-OCT-07:01 | 4.50 |
November | 0.233126E+10 | 24146.73 | 20-NOV-08:61 | 1.33 |
December | 0.389101E+10 | 24150.05 | 26-DEC-08:13 | 1.33 |
Annual Sum or Average | 0.182562E+11 | |||
Minimum of Months | 84952447.85 | 812.72 | -5.3 | |
Maximum of Months | 0.389101E+10 | 24176.07 | 17.00 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.549253E+10 | 3421.96 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.496476E+10 | 3421.96 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.549777E+10 | 3421.96 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.532115E+10 | 3421.96 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.549253E+10 | 3421.96 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.532179E+10 | 3421.96 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.549708E+10 | 3421.96 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.549285E+10 | 3421.96 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.532602E+10 | 3421.96 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.549253E+10 | 3421.96 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.530585E+10 | 3421.96 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.550226E+10 | 3421.96 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.647071E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.496476E+10 | 3421.96 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.550226E+10 | 3421.96 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.334781E+10 | 2090.38 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.302613E+10 | 2090.38 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.335104E+10 | 2090.38 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.324334E+10 | 2090.38 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.334781E+10 | 2090.38 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.324377E+10 | 2090.38 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.335056E+10 | 2090.38 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.334803E+10 | 2090.38 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.324631E+10 | 2090.38 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.334781E+10 | 2090.38 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.323401E+10 | 2090.38 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.335375E+10 | 2090.38 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.394404E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.302613E+10 | 2090.38 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.335375E+10 | 2090.38 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.241466E+10 | 2078.11 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.218750E+10 | 2078.11 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.247235E+10 | 2078.11 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.234375E+10 | 2078.11 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.244351E+10 | 2078.11 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.238702E+10 | 2078.11 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.240024E+10 | 2078.11 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.247235E+10 | 2078.11 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.234375E+10 | 2078.11 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.241466E+10 | 2078.11 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.234375E+10 | 2078.11 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.240024E+10 | 2078.11 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.286238E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.218750E+10 | 2078.11 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.247235E+10 | 2078.11 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378822E+10 |
February | 0.305697E+10 | 0.496476E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341374E+10 |
March | 0.335708E+10 | 0.549777E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323339E+10 |
April | 0.327081E+10 | 0.532115E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262329.00 | 0.230913E+10 |
May | 0.336680E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18093.50 | 0.279620E+10 |
June | 0.325380E+10 | 0.532179E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10780258.69 | 0.208671E+10 |
July | 0.339353E+10 | 0.549708E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47466294.47 | 0.180687E+10 |
August | 0.334857E+10 | 0.549285E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6334371.32 | 0.147627E+10 |
September | 0.327932E+10 | 0.532602E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184512E+10 |
October | 0.338624E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258080E+10 |
November | 0.327446E+10 | 0.530585E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340357E+10 |
December | 0.340325E+10 | 0.550226E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424487E+10 |
Annual Sum or Average | 0.397770E+11 | 0.647071E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64861346.98 | 0.329849E+11 |
Minimum of Months | 0.305697E+10 | 0.496476E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147627E+10 |
Maximum of Months | 0.340325E+10 | 0.550226E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47466294.47 | 0.424487E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204794E+10 |
February | 0.152844E+10 | 0.302613E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180596E+10 |
March | 0.167849E+10 | 0.335104E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174950E+10 |
April | 0.163536E+10 | 0.324334E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 144845.99 | 0.131297E+10 |
May | 0.168335E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9971.32 | 0.149937E+10 |
June | 0.162685E+10 | 0.324377E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5884246.54 | 0.110150E+10 |
July | 0.169671E+10 | 0.335056E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25991736.48 | 0.903724E+09 |
August | 0.167424E+10 | 0.334803E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3452235.10 | 0.725350E+09 |
September | 0.163961E+10 | 0.324631E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.955626E+09 |
October | 0.169307E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143496E+10 |
November | 0.163718E+10 | 0.323401E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177809E+10 |
December | 0.170157E+10 | 0.335375E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219287E+10 |
Annual Sum or Average | 0.198880E+11 | 0.394404E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35483035.44 | 0.175079E+11 |
Minimum of Months | 0.152844E+10 | 0.302613E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725350E+09 |
Maximum of Months | 0.170157E+10 | 0.335375E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25991736.48 | 0.219287E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205722E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182379E+10 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175723E+10 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.132839E+10 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9969.87 | 0.154678E+10 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5845707.15 | 0.115186E+10 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25656783.84 | 0.951536E+09 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452140.34 | 0.762786E+09 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988816E+09 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145841E+10 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180137E+10 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223140E+10 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35033705.51 | 0.178596E+11 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762786E+09 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25656783.84 | 0.223140E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205598E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182231E+10 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175568E+10 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.131584E+10 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9969.78 | 0.153078E+10 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5845823.32 | 0.114791E+10 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25654279.24 | 0.949643E+09 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452134.49 | 0.762166E+09 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987167E+09 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144577E+10 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179738E+10 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222863E+10 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35031311.15 | 0.177993E+11 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762166E+09 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25654279.24 | 0.222863E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205483E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182087E+10 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175389E+10 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.129100E+10 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9970.08 | 0.149511E+10 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5846208.39 | 0.113221E+10 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25669860.11 | 0.943221E+09 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452126.80 | 0.760208E+09 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.981216E+09 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141919E+10 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179325E+10 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222597E+10 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35047269.70 | 0.176710E+11 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760208E+09 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25669860.11 | 0.222597E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.241466E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370519E+10 |
February | 0.313522E+10 | 0.218750E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329629E+10 |
March | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316146E+10 |
April | 0.338259E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 123960.25 | 0.222140E+10 |
May | 0.349753E+10 | 0.244351E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17879.54 | 0.257829E+10 |
June | 0.343071E+10 | 0.238702E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10514936.08 | 0.192220E+10 |
July | 0.344942E+10 | 0.240024E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46249656.05 | 0.167340E+10 |
August | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6206821.42 | 0.138826E+10 |
September | 0.338259E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170936E+10 |
October | 0.344359E+10 | 0.241466E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244697E+10 |
November | 0.331698E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325511E+10 |
December | 0.344942E+10 | 0.240024E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404987E+10 |
Annual Sum or Average | 0.410346E+11 | 0.286238E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63113253.35 | 0.314078E+11 |
Minimum of Months | 0.313522E+10 | 0.218750E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138826E+10 |
Maximum of Months | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46249656.05 | 0.404987E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205631E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182311E+10 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175440E+10 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.124209E+10 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9968.35 | 0.143112E+10 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5847937.60 | 0.107972E+10 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25720139.44 | 0.925768E+09 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452152.73 | 0.760414E+09 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961242E+09 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136588E+10 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179490E+10 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223113E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35099302.43 | 0.174261E+11 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760414E+09 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25720139.44 | 0.223113E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205602E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182269E+10 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175407E+10 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.123895E+10 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9968.37 | 0.142516E+10 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5848111.01 | 0.107260E+10 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25725344.82 | 0.922372E+09 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452151.76 | 0.759594E+09 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957900E+09 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136140E+10 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179426E+10 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223051E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35104680.27 | 0.173955E+11 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759594E+09 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25725344.82 | 0.223051E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205463E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182059E+10 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175295E+10 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.122981E+10 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9968.70 | 0.140553E+10 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5848637.45 | 0.104545E+10 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25740484.95 | 0.908676E+09 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452141.58 | 0.755630E+09 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940423E+09 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134610E+10 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179130E+10 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222702E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35120336.99 | 0.172781E+11 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755630E+09 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25740484.95 | 0.222702E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217556E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200059E+10 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185845E+10 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69520.41 | 0.133685E+10 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10175.53 | 0.169895E+10 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6050941.99 | 0.125375E+10 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26586388.11 | 0.113267E+10 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3579444.99 | 0.940072E+09 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110982E+10 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151821E+10 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203032E+10 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255335E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36296471.02 | 0.196086E+11 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940072E+09 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26586388.11 | 0.255335E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 3421.96 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8006.93 | 11-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 3421.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6020.31 | 24-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 3421.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6220.37 | 15-MAR-12:00 |
April | 4050.04 | 01-APR-12:09 | 3421.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.89 | 30-APR-17:00 | 4388.34 | 10-APR-11:10 |
May | 4050.04 | 05-MAY-12:09 | 3421.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.16 | 22-MAY-15:00 | 4506.69 | 01-MAY-15:00 |
June | 4050.04 | 02-JUN-12:09 | 3421.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 905.89 | 13-JUN-17:00 | 3712.20 | 07-JUN-11:05 |
July | 4050.04 | 01-JUL-12:09 | 3421.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1477.96 | 22-JUL-15:00 | 3172.85 | 04-JUL-14:00 |
August | 4050.04 | 04-AUG-12:09 | 3421.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 903.22 | 14-AUG-17:00 | 2483.39 | 30-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 3421.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 3427.62 | 30-SEP-11:10 |
October | 4050.04 | 01-OCT-12:09 | 3421.96 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3955.48 | 27-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 3421.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6537.86 | 28-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 3421.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 7437.13 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2483.39 | |||||
Maximum of Months | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1477.96 | 8006.93 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2090.38 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 2090.38 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2090.38 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2024.96 | 01-APR-12:09 | 2090.38 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 30-APR-17:00 | 2416.41 | 10-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 2090.38 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 22-MAY-15:00 | 2603.23 | 01-MAY-15:00 |
June | 2024.96 | 02-JUN-12:09 | 2090.38 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 13-JUN-17:00 | 2303.63 | 07-JUN-11:05 |
July | 2024.96 | 01-JUL-12:09 | 2090.38 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1945.03 | 04-JUL-14:00 |
August | 2024.96 | 04-AUG-12:09 | 2090.38 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.80 | 30-AUG-17:00 |
September | 2024.96 | 01-SEP-12:09 | 2090.38 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2006.91 | 08-SEP-11:10 |
October | 2024.96 | 01-OCT-12:09 | 2090.38 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 2090.38 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2090.38 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.80 | |||||
Maximum of Months | 2024.96 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 22-MAY-15:00 | 2633.33 | 01-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.46 | 13-JUN-17:00 | 2343.04 | 07-JUN-11:05 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1958.54 | 04-JUL-14:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.81 | 30-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2043.96 | 08-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.81 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 22-MAY-15:00 | 2625.13 | 01-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.46 | 13-JUN-17:00 | 2322.09 | 07-JUN-11:05 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1942.65 | 04-JUL-14:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.81 | 30-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2033.80 | 08-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2181.38 | 27-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.81 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 22-MAY-15:00 | 2582.73 | 01-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.46 | 13-JUN-17:00 | 2244.47 | 07-JUN-11:05 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1888.70 | 04-JUL-14:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.81 | 30-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1980.04 | 08-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.81 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2078.11 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 7953.76 | 11-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 2078.11 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5964.69 | 24-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 2078.11 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6220.37 | 15-MAR-12:00 |
April | 5400.05 | 01-APR-14:09 | 2078.11 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 | 30-APR-15:00 | 4338.71 | 10-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 2078.11 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.80 | 22-MAY-15:00 | 4310.79 | 01-MAY-15:00 |
June | 5400.05 | 03-JUN-14:09 | 2078.11 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 893.62 | 13-JUN-17:00 | 3607.37 | 07-JUN-11:05 |
July | 5400.05 | 01-JUL-14:09 | 2078.11 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1457.96 | 22-JUL-15:00 | 3009.41 | 04-JUL-14:00 |
August | 5400.05 | 05-AUG-14:09 | 2078.11 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 892.94 | 14-AUG-17:00 | 2418.36 | 30-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 2078.11 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 3346.98 | 30-SEP-11:10 |
October | 5400.05 | 07-OCT-14:09 | 2078.11 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3929.21 | 27-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 2078.11 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6449.59 | 28-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2078.11 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 7352.49 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2418.36 | |||||
Maximum of Months | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1457.96 | 7953.76 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 22-MAY-15:00 | 2445.95 | 01-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 13-JUN-17:00 | 2037.31 | 07-JUN-11:05 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1732.36 | 04-JUL-14:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.80 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1938.40 | 30-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.80 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 22-MAY-15:00 | 2434.25 | 01-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.46 | 13-JUN-17:00 | 2018.76 | 07-JUN-11:05 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1717.45 | 04-JUL-14:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.80 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1930.38 | 30-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.80 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 22-MAY-15:00 | 2392.77 | 01-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.46 | 13-JUN-17:00 | 2006.49 | 07-JUN-11:05 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1667.24 | 04-JUL-14:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.80 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1883.94 | 30-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.80 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4485.13 | 11-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3378.03 | 24-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 30-APR-15:00 | 2465.64 | 10-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.96 | 22-MAY-15:00 | 2483.74 | 01-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 509.69 | 13-JUN-17:00 | 2076.78 | 07-JUN-11:05 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 831.59 | 22-JUL-15:00 | 1654.89 | 27-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 507.51 | 14-AUG-17:00 | 1408.82 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1864.90 | 30-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2215.69 | 27-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3678.60 | 28-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4178.83 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1408.82 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 831.59 | 4485.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7498.81 | 10-JAN-21:53 | 6075.06 | 10265.87 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.23 |
February | 5085.75 | 17-FEB-00:12 | 1350.01 | 720.45 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.46 |
March | 4421.93 | 14-MAR-22:05 | 675.01 | 3602.07 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7049.30 | 30-APR-16:13 | 12150.11 | 10265.87 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 29.57 | 0.00 |
May | 5302.15 | 23-MAY-17:10 | 3375.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.64 |
June | 8502.99 | 13-JUN-17:00 | 3375.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 905.89 | 0.00 |
July | 9789.28 | 22-JUL-16:20 | 3375.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1468.77 | 0.00 |
August | 8370.22 | 14-AUG-17:00 | 3375.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 903.22 | 0.00 |
September | 6983.47 | 13-SEP-16:10 | 3375.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.03 |
October | 5425.73 | 03-OCT-19:00 | 3375.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 655.58 |
November | 3695.74 | 03-NOV-23:05 | 675.01 | 3602.07 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.89 |
December | 6937.13 | 30-DEC-18:23 | 10125.10 | 10265.87 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 961.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3695.74 | 675.01 | 720.45 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9789.28 | 12150.11 | 10265.87 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1468.77 | 961.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1970.36 | 19-JAN-18:10 | 1687.47 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.85 |
February | 1932.23 | 27-FEB-18:40 | 1687.47 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.48 |
March | 1904.54 | 23-MAR-19:00 | 1687.47 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.36 |
April | 15215.00 | 29-APR-18:40 | 5062.40 | 6271.14 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.59 |
May | 14859.90 | 21-MAY-17:09 | 16199.69 | 16723.04 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.26 |
June | 12854.30 | 25-JUN-17:08 | 12149.77 | 12542.28 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.51 |
July | 13152.42 | 21-JUL-20:23 | 6074.88 | 12542.28 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 |
August | 15509.79 | 14-AUG-20:44 | 7087.36 | 14632.66 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
September | 13319.08 | 24-SEP-17:50 | 12149.77 | 12542.28 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.11 |
October | 3858.65 | 01-OCT-17:10 | 4049.92 | 4180.76 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.16 |
November | 2166.10 | 03-NOV-17:30 | 1687.47 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.95 |
December | 1600.32 | 20-DEC-19:10 | 1687.47 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1600.32 | 1687.47 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 | |
Maximum of Months | 15509.79 | 16199.69 | 16723.04 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2385.69 | 11-JAN-19:45 | 1349.97 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.40 |
February | 1655.46 | 27-FEB-18:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.42 |
March | 1733.43 | 10-MAR-18:30 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.98 |
April | 3550.16 | 30-APR-15:00 | 674.99 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 0.00 |
May | 2978.42 | 23-MAY-17:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.63 |
June | 4472.82 | 13-JUN-17:00 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 497.46 | 0.00 |
July | 7757.77 | 23-JUL-07:03 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.89 |
August | 4366.62 | 14-AUG-16:20 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 393.04 | 0.00 |
September | 3787.88 | 13-SEP-16:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.66 |
October | 2359.30 | 02-OCT-17:20 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.32 |
November | 1985.34 | 03-NOV-17:30 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.81 |
December | 1450.72 | 30-DEC-11:55 | 1349.97 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1450.72 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7757.77 | 1687.47 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 497.46 | 573.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1638.18 | 19-JAN-18:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.85 |
February | 1632.10 | 16-FEB-20:55 | 337.49 | 2055.69 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.91 |
March | 1681.45 | 10-MAR-18:20 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.25 |
April | 3461.49 | 30-APR-15:00 | 674.99 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 0.00 |
May | 2858.08 | 23-MAY-17:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.63 |
June | 4412.38 | 13-JUN-17:00 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 497.46 | 0.00 |
July | 7872.76 | 23-JUL-07:03 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.93 |
August | 4321.01 | 14-AUG-16:20 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 393.04 | 0.00 |
September | 3749.02 | 13-SEP-16:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.66 |
October | 2262.75 | 03-OCT-17:20 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.60 |
November | 1965.23 | 10-NOV-19:00 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.12 |
December | 2104.62 | 29-DEC-19:55 | 1349.97 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1632.10 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7872.76 | 1687.47 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 497.46 | 578.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1580.41 | 03-JAN-19:05 | 1349.97 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.66 |
February | 1344.39 | 09-FEB-18:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.00 |
March | 1561.19 | 30-MAR-18:00 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.57 |
April | 3189.02 | 30-APR-15:00 | 674.99 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 0.00 |
May | 2569.86 | 23-MAY-17:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.63 |
June | 4204.22 | 13-JUN-17:00 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 497.46 | 0.00 |
July | 6691.87 | 23-JUL-07:03 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.59 |
August | 4168.32 | 14-AUG-16:20 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 393.04 | 0.00 |
September | 3581.03 | 13-SEP-16:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.66 |
October | 1714.06 | 06-OCT-17:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.25 |
November | 1865.60 | 10-NOV-18:30 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.18 |
December | 1567.96 | 27-DEC-19:05 | 1349.97 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1344.39 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6691.87 | 1687.47 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 497.46 | 465.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4055.65 | 13-JAN-11:45 | 5805.05 | 4156.22 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.83 |
February | 5360.38 | 23-FEB-19:33 | 5265.05 | 6234.32 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.58 |
March | 4781.81 | 03-MAR-11:15 | 5805.05 | 4156.22 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 641.94 |
April | 5930.37 | 30-APR-15:00 | 4657.54 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 | 0.00 |
May | 5019.51 | 01-MAY-13:00 | 4792.55 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4259.52 |
June | 7146.68 | 13-JUN-17:00 | 4792.55 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 893.62 | 0.00 |
July | 9588.05 | 22-JUL-15:00 | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1457.96 | 0.00 |
August | 7347.01 | 14-AUG-16:20 | 4792.55 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 706.10 | 0.00 |
September | 6474.16 | 13-SEP-14:20 | 4657.54 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.00 |
October | 4283.30 | 03-OCT-19:00 | 1755.02 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633.11 |
November | 3630.97 | 03-NOV-13:35 | 6750.06 | 4156.22 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3726.92 |
December | 4759.73 | 12-DEC-18:45 | 4590.04 | 4156.22 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 751.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3630.97 | 1755.02 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9588.05 | 6750.06 | 6234.32 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1457.96 | 4259.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1233.17 | 21-JAN-12:00 | 1957.46 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.06 |
February | 1964.43 | 23-FEB-19:15 | 1754.97 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.02 |
March | 1935.32 | 15-MAR-17:25 | 2294.96 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.16 |
April | 3043.89 | 30-APR-15:00 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 0.00 |
May | 2006.05 | 01-MAY-13:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2415.56 |
June | 3674.53 | 13-JUN-17:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 0.00 |
July | 4966.33 | 22-JUL-15:00 | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 0.00 |
August | 3802.36 | 14-AUG-16:20 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 393.04 | 0.00 |
September | 3308.95 | 13-SEP-14:30 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.34 |
October | 1631.67 | 03-OCT-19:00 | 877.48 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.39 |
November | 1525.73 | 25-NOV-14:35 | 5197.40 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2025.08 |
December | 1592.25 | 22-DEC-19:35 | 1754.97 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1233.17 | 877.48 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4966.33 | 5197.40 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 2415.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1722.05 | 14-JAN-11:35 | 3914.92 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.62 |
February | 1211.38 | 04-FEB-12:00 | 1957.46 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.15 |
March | 1884.22 | 02-MAR-19:45 | 1754.97 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.39 |
April | 2972.58 | 30-APR-15:00 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 0.00 |
May | 2001.43 | 01-MAY-13:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2403.86 |
June | 3593.98 | 13-JUN-17:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 497.46 | 0.00 |
July | 4912.54 | 22-JUL-15:00 | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 0.00 |
August | 3738.88 | 14-AUG-16:20 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 393.04 | 0.00 |
September | 3245.15 | 13-SEP-14:30 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.34 |
October | 1629.57 | 03-OCT-19:00 | 877.48 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.63 |
November | 1326.03 | 25-NOV-12:00 | 1957.46 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.66 |
December | 1839.74 | 21-DEC-19:15 | 1754.97 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1211.38 | 877.48 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4912.54 | 3914.92 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 2403.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1483.05 | 26-JAN-19:45 | 1754.97 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.28 |
February | 1503.45 | 08-FEB-19:05 | 1754.97 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.06 |
March | 1847.22 | 04-MAR-11:35 | 3914.92 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.70 |
April | 2766.66 | 30-APR-15:00 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 0.00 |
May | 1968.82 | 01-MAY-13:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2361.58 |
June | 3395.95 | 13-JUN-17:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 497.46 | 0.00 |
July | 4786.41 | 22-JUL-15:00 | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 0.00 |
August | 3546.80 | 14-AUG-16:20 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 393.04 | 0.00 |
September | 3067.62 | 13-SEP-14:40 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.34 |
October | 1594.01 | 03-OCT-19:00 | 877.48 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.23 |
November | 1525.79 | 17-NOV-19:55 | 1754.97 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.72 |
December | 2067.81 | 21-DEC-18:35 | 2294.96 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1483.05 | 877.48 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4786.41 | 3914.92 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 2361.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1549.99 | 20-JAN-11:15 | 2902.44 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.83 |
February | 940.15 | 22-FEB-11:40 | 1451.22 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.91 |
March | 1081.38 | 31-MAR-17:50 | 1147.48 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.75 |
April | 2548.64 | 30-APR-15:00 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 0.00 |
May | 1545.14 | 01-MAY-14:40 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2211.80 |
June | 3281.38 | 13-JUN-17:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 509.69 | 0.00 |
July | 4814.44 | 22-JUL-15:00 | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 831.59 | 0.00 |
August | 3360.56 | 14-AUG-16:20 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 403.21 | 0.00 |
September | 2931.98 | 13-SEP-14:20 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.51 |
October | 1478.67 | 03-OCT-19:00 | 877.48 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.16 |
November | 1252.31 | 15-NOV-19:00 | 1147.48 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.56 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4814.44 | 2902.44 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 831.59 | 2211.80 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.577688E+11 | 50636.56 | 07-JAN-17:40 | 0.549741E+11 | 110771.04 | 10-JAN-08:09 |
February | 0.517467E+11 | 48377.32 | 04-FEB-17:30 | 0.446217E+11 | 96670.52 | 17-FEB-08:09 |
March | 0.571884E+11 | 48851.98 | 13-MAR-18:49 | 0.394321E+11 | 76816.10 | 15-MAR-12:09 |
April | 0.539617E+11 | 51408.97 | 30-APR-15:00 | 0.897248E+10 | 58051.25 | 01-APR-07:10 |
May | 0.553601E+11 | 49595.16 | 22-MAY-15:20 | 0.511530E+10 | 35580.42 | 05-MAY-07:10 |
June | 0.548537E+11 | 53817.18 | 13-JUN-15:39 | 0.143005E+09 | 13957.75 | 08-JUN-07:10 |
July | 0.563972E+11 | 58345.16 | 21-JUL-16:49 | 8574014.20 | 4069.24 | 05-JUL-07:10 |
August | 0.575567E+11 | 53822.81 | 14-AUG-16:49 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.551497E+11 | 52889.91 | 13-SEP-15:20 | 10652950.32 | 2516.16 | 07-SEP-07:10 |
October | 0.565221E+11 | 46059.42 | 24-OCT-18:40 | 0.101390E+11 | 55116.49 | 23-OCT-07:10 |
November | 0.555892E+11 | 46278.23 | 26-NOV-16:40 | 0.343552E+11 | 89065.27 | 29-NOV-08:09 |
December | 0.577917E+11 | 46466.19 | 28-DEC-17:19 | 0.589691E+11 | 99740.22 | 30-DEC-08:09 |
Annual Sum or Average | 0.669886E+12 | 0.256741E+12 | ||||
Minimum of Months | 0.517467E+11 | 46059.42 | 0.00 | 0.00 | ||
Maximum of Months | 0.577917E+11 | 58345.16 | 0.589691E+11 | 110771.04 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.130825E+10 | 3642.38 | 11-JAN-12:30 | 0.00 | 0.00 |
February | 0.203360E+10 | 6040.18 | 27-FEB-12:30 | 0.00 | 0.00 |
March | 0.266996E+10 | 7366.76 | 28-MAR-11:30 | 0.00 | 0.00 |
April | 0.597405E+10 | 9493.75 | 26-APR-12:30 | 0.00 | 0.00 |
May | 0.725305E+10 | 10468.88 | 19-MAY-12:09 | 0.00 | 0.00 |
June | 0.740366E+10 | 10606.91 | 18-JUN-12:30 | 0.00 | 0.00 |
July | 0.767301E+10 | 10321.64 | 01-JUL-11:00 | 0.00 | 0.00 |
August | 0.659721E+10 | 9332.74 | 05-AUG-12:30 | 0.00 | 0.00 |
September | 0.487795E+10 | 8018.68 | 09-SEP-12:09 | 0.00 | 0.00 |
October | 0.263500E+10 | 6561.10 | 03-OCT-12:09 | 0.00 | 0.00 |
November | 0.133464E+10 | 4466.93 | 03-NOV-12:20 | 0.00 | 0.00 |
December | 0.895836E+09 | 3469.36 | 03-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.506562E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.895836E+09 | 3469.36 | 0.00 | 0.00 | |
Maximum of Months | 0.767301E+10 | 10606.91 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.234911E+11 | 0.491319E+10 | 0.108325E+11 | 0.00 | 0.129299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560221E+10 | 0.00 |
February | 0.212624E+11 | 0.391626E+10 | 0.980803E+10 | 0.00 | 0.116766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508340E+10 | 0.00 |
March | 0.238408E+11 | 0.362042E+10 | 0.110075E+11 | 0.00 | 0.130688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565093E+10 | 0.00 |
April | 0.227839E+11 | 0.278069E+10 | 0.105079E+11 | 0.00 | 0.123281E+11 | 0.00 | 0.00 | 0.171853E+09 | 0.00 | 0.00 | 0.00 | 0.538928E+10 | 0.00 |
May | 0.236617E+11 | 0.233155E+10 | 0.109147E+11 | 0.00 | 0.128319E+11 | 0.00 | 0.00 | 92898470.06 | 0.00 | 0.00 | 0.00 | 0.552740E+10 | 0.00 |
June | 0.230409E+11 | 0.199600E+10 | 0.106386E+11 | 0.00 | 0.127116E+11 | 0.00 | 0.00 | 0.116456E+10 | 0.00 | 0.00 | 0.00 | 0.530201E+10 | 0.00 |
July | 0.234131E+11 | 0.215189E+10 | 0.107945E+11 | 0.00 | 0.128823E+11 | 0.00 | 0.00 | 0.176273E+10 | 0.00 | 0.00 | 0.00 | 0.539268E+10 | 0.00 |
August | 0.238328E+11 | 0.259753E+10 | 0.110006E+11 | 0.00 | 0.131758E+11 | 0.00 | 0.00 | 0.152138E+10 | 0.00 | 0.00 | 0.00 | 0.542853E+10 | 0.00 |
September | 0.227918E+11 | 0.318965E+10 | 0.105148E+11 | 0.00 | 0.125667E+11 | 0.00 | 0.00 | 0.845254E+09 | 0.00 | 0.00 | 0.00 | 0.524155E+10 | 0.00 |
October | 0.234911E+11 | 0.403847E+10 | 0.108325E+11 | 0.00 | 0.126851E+11 | 0.00 | 0.00 | 578381.28 | 0.00 | 0.00 | 0.00 | 0.547443E+10 | 0.00 |
November | 0.227593E+11 | 0.455740E+10 | 0.104978E+11 | 0.00 | 0.124204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535428E+10 | 0.00 |
December | 0.234215E+11 | 0.508813E+10 | 0.108050E+11 | 0.00 | 0.129020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557499E+10 | 0.00 |
Annual Sum or Average | 0.277790E+12 | 0.411812E+11 | 0.128154E+12 | 0.00 | 0.152179E+12 | 0.00 | 0.00 | 0.555926E+10 | 0.00 | 0.00 | 0.00 | 0.650217E+11 | 0.00 |
Minimum of Months | 0.212624E+11 | 0.199600E+10 | 0.980803E+10 | 0.00 | 0.116766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508340E+10 | 0.00 |
Maximum of Months | 0.238408E+11 | 0.508813E+10 | 0.110075E+11 | 0.00 | 0.131758E+11 | 0.00 | 0.00 | 0.176273E+10 | 0.00 | 0.00 | 0.00 | 0.565093E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.549741E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.446217E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.394321E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.897248E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.511530E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.143005E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 8574014.20 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 10652950.32 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.101390E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.343552E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.589691E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.256741E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.589691E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17697.17 | 01-JAN-11:09 | 3786.68 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 9596.58 | 10-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 17697.17 | 01-FEB-10:09 | 3786.68 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 9526.96 | 17-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 17697.17 | 01-MAR-10:09 | 3786.68 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 9402.70 | 04-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 17697.17 | 01-APR-09:09 | 3786.68 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 9274.77 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 17697.17 | 01-MAY-09:09 | 3786.68 | 01-MAY-19:19 | 8059.50 | 01-MAY-09:09 | 0.00 | 9160.95 | 05-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 17697.17 | 01-JUN-09:09 | 3786.68 | 01-JUN-19:00 | 8059.50 | 01-JUN-09:09 | 0.00 | 8964.53 | 07-JUN-11:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 17697.17 | 01-JUL-09:09 | 3786.68 | 01-JUL-20:19 | 8059.50 | 01-JUL-09:09 | 0.00 | 8936.12 | 22-JUL-16:19 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 17697.17 | 01-AUG-09:09 | 3786.68 | 01-AUG-19:49 | 8059.50 | 01-AUG-09:09 | 0.00 | 8882.49 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 17697.17 | 01-SEP-09:09 | 3786.68 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 8882.49 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 17697.17 | 01-OCT-10:09 | 3786.68 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 9243.02 | 23-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 17697.17 | 01-NOV-09:09 | 3786.68 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 9470.95 | 29-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 17697.17 | 01-DEC-10:09 | 3786.68 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 9558.49 | 30-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 17697.17 | 3786.68 | 8059.50 | 0.00 | 8882.49 | 0.00 | 0.00 | |||||
Maximum of Months | 17697.17 | 3786.68 | 8059.50 | 0.00 | 9596.58 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 11860.28 | 19-JAN-13:50 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 11819.98 | 04-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 10742.86 | 13-MAR-14:09 | 0.00 | 01-MAR-00:10 |
April | 10232.63 | 30-APR-14:00 | 0.00 | 0.00 | 0.00 | 9701.86 | 13-APR-11:39 | 0.00 | 01-APR-00:10 |
May | 8380.48 | 22-MAY-14:00 | 0.00 | 0.00 | 0.00 | 9723.32 | 19-MAY-12:30 | 0.00 | 01-MAY-00:10 |
June | 14857.14 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | 8266.04 | 21-JUN-13:09 | 0.00 | 01-JUN-00:10 |
July | 16932.96 | 22-JUL-14:00 | 0.00 | 0.00 | 0.00 | 9707.76 | 08-JUL-13:09 | 0.00 | 01-JUL-00:10 |
August | 13861.16 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 7587.58 | 25-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 10201.30 | 13-SEP-16:10 | 0.00 | 0.00 | 0.00 | 9712.58 | 26-SEP-12:09 | 0.00 | 01-SEP-00:10 |
October | 311.48 | 12-OCT-20:19 | 0.00 | 0.00 | 0.00 | 9681.17 | 28-OCT-16:40 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 9162.74 | 10-NOV-12:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 9724.65 | 26-DEC-14:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7587.58 | 0.00 | |||
Maximum of Months | 16932.96 | 0.00 | 0.00 | 0.00 | 11860.28 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 50636.56 | 07-JAN-17:40 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 9285.16 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 48377.32 | 04-FEB-17:30 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 9142.38 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 48851.98 | 13-MAR-18:49 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 9056.31 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 51408.97 | 30-APR-15:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 8882.49 | 0.00 | 0.00 | 9230.80 | 0.00 |
May | 49595.16 | 22-MAY-15:20 | 17697.17 | 8059.50 | 0.00 | 0.00 | 8882.49 | 0.00 | 0.00 | 7398.39 | 0.00 |
June | 53817.18 | 13-JUN-15:39 | 17697.17 | 8059.50 | 0.00 | 0.00 | 8882.49 | 0.00 | 0.00 | 13762.49 | 0.00 |
July | 58345.16 | 21-JUL-16:49 | 17697.17 | 8059.50 | 0.00 | 0.00 | 8890.90 | 0.00 | 0.00 | 16261.30 | 0.00 |
August | 53822.81 | 14-AUG-16:49 | 17697.17 | 8059.50 | 0.00 | 0.00 | 8882.49 | 0.00 | 0.00 | 13743.41 | 0.00 |
September | 52889.91 | 13-SEP-15:20 | 17697.17 | 8059.50 | 0.00 | 0.00 | 8882.49 | 0.00 | 0.00 | 9794.06 | 0.00 |
October | 46059.42 | 24-OCT-18:40 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 8960.86 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 46278.23 | 26-NOV-16:40 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 9193.16 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 46466.19 | 28-DEC-17:19 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 9357.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 46059.42 | 17697.17 | 8059.50 | 0.00 | 0.00 | 8882.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 58345.16 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 9357.56 | 0.00 | 0.00 | 16261.30 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 110771.04 | 10-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 96670.52 | 17-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 76816.10 | 15-MAR-12:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 58051.25 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 35580.42 | 05-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 13957.75 | 08-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 4069.24 | 05-JUL-07:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 2516.16 | 07-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 55116.49 | 23-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 89065.27 | 29-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 99740.22 | 30-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 110771.04 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
February | 1.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 1.67 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
December | 1.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Annual Sum or Average | 5.83 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
February | 3.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
March | 1.83 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
December | 3.83 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Annual Sum or Average | 13.17 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.83 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.09 | 169.33 | 21.08 | 169.33 | 21.07 |
February | 448.00 | 21.08 | 100.17 | 21.06 | 100.17 | 21.05 |
March | 497.00 | 21.08 | 97.50 | 21.07 | 97.50 | 21.06 |
April | 453.50 | 21.51 | 16.00 | 21.49 | 16.00 | 21.47 |
May | 451.67 | 21.73 | 6.50 | 21.74 | 1.83 | 21.74 |
June | 287.00 | 22.82 | 51.50 | 22.99 | 0.00 | 22.99 |
July | 143.33 | 23.14 | 169.67 | 23.55 | 0.00 | 23.55 |
August | 77.17 | 23.55 | 191.17 | 23.79 | 0.00 | 23.79 |
September | 229.50 | 23.14 | 66.50 | 23.31 | 0.00 | 23.31 |
October | 496.00 | 21.54 | 1.50 | 21.54 | 1.50 | 21.54 |
November | 480.00 | 21.10 | 52.33 | 21.09 | 52.33 | 21.08 |
December | 496.00 | 21.08 | 185.50 | 21.07 | 185.50 | 21.06 |
Annual Sum or Average | 4555.17 | 21.56 | 1107.67 | 21.70 | 624.17 | 21.63 |
Minimum of Months | 77.17 | 21.08 | 1.50 | 21.06 | 0.00 | 21.05 |
Maximum of Months | 497.00 | 23.55 | 191.17 | 23.79 | 185.50 | 23.79 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.42 | 43.33 | 21.40 | 43.33 | 21.38 |
February | 448.00 | 21.41 | 4.50 | 21.41 | 4.50 | 21.41 |
March | 497.00 | 21.50 | 3.33 | 21.50 | 3.33 | 21.49 |
April | 432.33 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
May | 408.67 | 22.87 | 7.83 | 22.89 | 0.00 | 22.89 |
June | 104.83 | 23.59 | 83.00 | 23.72 | 0.00 | 23.72 |
July | 42.50 | 23.77 | 194.00 | 23.87 | 0.00 | 23.87 |
August | 33.67 | 23.87 | 224.83 | 23.89 | 0.00 | 23.89 |
September | 81.00 | 23.76 | 109.33 | 23.83 | 0.00 | 23.83 |
October | 456.00 | 22.57 | 0.00 | 22.57 | 0.00 | 22.57 |
November | 480.00 | 21.59 | 4.50 | 21.59 | 4.50 | 21.59 |
December | 496.00 | 21.38 | 29.33 | 21.36 | 29.33 | 21.35 |
Annual Sum or Average | 3976.00 | 22.00 | 704.00 | 22.24 | 85.00 | 22.22 |
Minimum of Months | 33.67 | 21.38 | 0.00 | 21.36 | 0.00 | 21.35 |
Maximum of Months | 497.00 | 23.87 | 224.83 | 23.89 | 43.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 82.17 | 21.12 | 82.17 | 21.12 |
February | 336.00 | 21.11 | 31.00 | 21.11 | 31.00 | 21.11 |
March | 379.00 | 21.15 | 26.33 | 21.15 | 26.33 | 21.14 |
April | 318.17 | 22.20 | 2.67 | 22.21 | 1.00 | 22.21 |
May | 304.17 | 22.59 | 7.33 | 22.62 | 0.00 | 22.62 |
June | 73.50 | 23.54 | 82.17 | 23.81 | 0.00 | 23.81 |
July | 34.00 | 23.73 | 177.67 | 23.98 | 0.00 | 23.98 |
August | 25.00 | 23.86 | 210.83 | 24.00 | 0.00 | 24.00 |
September | 57.50 | 23.65 | 100.17 | 23.87 | 0.00 | 23.87 |
October | 341.00 | 22.22 | 0.00 | 22.22 | 0.00 | 22.22 |
November | 360.00 | 21.19 | 16.00 | 21.19 | 16.00 | 21.19 |
December | 369.00 | 21.11 | 74.67 | 21.11 | 74.67 | 21.11 |
Annual Sum or Average | 2968.33 | 21.68 | 811.00 | 22.01 | 231.17 | 21.96 |
Minimum of Months | 25.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.86 | 210.83 | 24.00 | 82.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 98.00 | 21.11 | 98.00 | 21.11 |
February | 336.00 | 21.11 | 39.83 | 21.11 | 39.83 | 21.11 |
March | 379.00 | 21.14 | 36.00 | 21.14 | 36.00 | 21.13 |
April | 326.33 | 22.13 | 4.33 | 22.14 | 2.67 | 22.13 |
May | 306.17 | 22.47 | 6.00 | 22.50 | 0.00 | 22.50 |
June | 87.50 | 23.51 | 76.33 | 23.76 | 0.00 | 23.76 |
July | 41.00 | 23.70 | 174.33 | 23.96 | 0.00 | 23.96 |
August | 26.00 | 23.85 | 204.17 | 24.00 | 0.00 | 24.00 |
September | 62.50 | 23.64 | 94.83 | 23.85 | 0.00 | 23.85 |
October | 348.83 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
November | 360.00 | 21.17 | 21.17 | 21.17 | 21.17 | 21.16 |
December | 369.00 | 21.11 | 86.17 | 21.11 | 86.17 | 21.11 |
Annual Sum or Average | 3013.33 | 21.67 | 841.17 | 21.97 | 283.83 | 21.91 |
Minimum of Months | 26.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.85 | 204.17 | 24.00 | 98.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 118.83 | 21.11 | 118.83 | 21.11 |
February | 336.00 | 21.11 | 51.50 | 21.11 | 51.50 | 21.11 |
March | 379.00 | 21.12 | 50.17 | 21.12 | 50.17 | 21.12 |
April | 337.17 | 21.98 | 6.83 | 21.98 | 5.33 | 21.96 |
May | 315.50 | 22.22 | 4.00 | 22.24 | 0.00 | 22.24 |
June | 120.67 | 23.35 | 58.33 | 23.58 | 0.00 | 23.58 |
July | 57.50 | 23.60 | 158.00 | 23.91 | 0.00 | 23.91 |
August | 32.50 | 23.83 | 187.17 | 23.99 | 0.00 | 23.99 |
September | 84.17 | 23.57 | 75.50 | 23.78 | 0.00 | 23.78 |
October | 371.00 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
November | 360.00 | 21.14 | 29.17 | 21.14 | 29.17 | 21.14 |
December | 369.00 | 21.11 | 119.00 | 21.11 | 119.00 | 21.11 |
Annual Sum or Average | 3133.50 | 21.66 | 858.50 | 21.89 | 374.00 | 21.83 |
Minimum of Months | 32.50 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.83 | 187.17 | 23.99 | 119.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 144.00 | 21.11 | 144.00 | 21.11 |
February | 308.00 | 21.11 | 83.33 | 21.11 | 83.33 | 21.11 |
March | 348.00 | 21.11 | 84.17 | 21.11 | 84.17 | 21.11 |
April | 317.67 | 21.46 | 7.67 | 21.45 | 7.67 | 21.44 |
May | 327.33 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
June | 231.17 | 22.67 | 23.00 | 22.78 | 0.00 | 22.78 |
July | 101.67 | 22.99 | 111.33 | 23.48 | 0.00 | 23.48 |
August | 46.17 | 23.57 | 133.50 | 23.83 | 0.00 | 23.83 |
September | 186.00 | 23.07 | 40.33 | 23.22 | 0.00 | 23.22 |
October | 340.00 | 21.45 | 0.50 | 21.45 | 0.50 | 21.45 |
November | 330.00 | 21.11 | 50.33 | 21.11 | 50.33 | 21.11 |
December | 338.00 | 21.11 | 174.17 | 21.11 | 174.17 | 21.11 |
Annual Sum or Average | 3214.00 | 21.56 | 852.33 | 21.68 | 544.17 | 21.61 |
Minimum of Months | 46.17 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.57 | 174.17 | 23.83 | 174.17 | 23.83 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 141.83 | 21.11 | 141.83 | 21.11 |
February | 308.00 | 21.11 | 83.17 | 21.11 | 83.17 | 21.11 |
March | 348.00 | 21.11 | 86.00 | 21.11 | 86.00 | 21.11 |
April | 319.83 | 21.61 | 10.00 | 21.60 | 9.67 | 21.59 |
May | 322.67 | 21.84 | 0.00 | 21.84 | 0.00 | 21.84 |
June | 212.83 | 23.00 | 18.83 | 23.08 | 0.00 | 23.08 |
July | 93.83 | 23.32 | 92.67 | 23.63 | 0.00 | 23.63 |
August | 45.00 | 23.83 | 92.33 | 23.91 | 0.00 | 23.91 |
September | 160.67 | 23.44 | 28.17 | 23.52 | 0.00 | 23.52 |
October | 340.00 | 21.61 | 0.83 | 21.61 | 0.83 | 21.61 |
November | 330.00 | 21.11 | 51.00 | 21.11 | 51.00 | 21.11 |
December | 338.00 | 21.11 | 166.33 | 21.11 | 166.33 | 21.11 |
Annual Sum or Average | 3158.83 | 21.64 | 771.17 | 21.70 | 538.83 | 21.63 |
Minimum of Months | 45.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.83 | 166.33 | 23.91 | 166.33 | 23.91 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 146.50 | 21.11 | 146.50 | 21.11 |
February | 308.00 | 21.11 | 89.17 | 21.11 | 89.17 | 21.11 |
March | 348.00 | 21.11 | 92.17 | 21.11 | 92.17 | 21.11 |
April | 320.50 | 21.59 | 11.33 | 21.58 | 11.17 | 21.56 |
May | 325.83 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
June | 222.67 | 22.96 | 15.67 | 23.03 | 0.00 | 23.03 |
July | 99.17 | 23.29 | 88.00 | 23.59 | 0.00 | 23.59 |
August | 49.83 | 23.83 | 83.00 | 23.91 | 0.00 | 23.91 |
September | 170.33 | 23.41 | 25.50 | 23.49 | 0.00 | 23.49 |
October | 340.00 | 21.58 | 1.33 | 21.57 | 1.33 | 21.57 |
November | 330.00 | 21.11 | 55.50 | 21.11 | 55.50 | 21.11 |
December | 338.00 | 21.11 | 174.83 | 21.11 | 174.83 | 21.11 |
Annual Sum or Average | 3192.33 | 21.64 | 783.00 | 21.69 | 570.67 | 21.62 |
Minimum of Months | 49.83 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.83 | 174.83 | 23.91 | 174.83 | 23.91 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 164.17 | 21.11 | 164.17 | 21.11 |
February | 308.00 | 21.11 | 116.00 | 21.11 | 116.00 | 21.11 |
March | 348.00 | 21.11 | 119.17 | 21.11 | 119.17 | 21.11 |
April | 326.83 | 21.56 | 18.33 | 21.54 | 18.33 | 21.51 |
May | 334.17 | 21.74 | 0.83 | 21.74 | 0.83 | 21.74 |
June | 247.67 | 22.78 | 14.17 | 22.84 | 0.00 | 22.84 |
July | 121.67 | 23.18 | 72.33 | 23.46 | 0.00 | 23.46 |
August | 63.83 | 23.76 | 58.00 | 23.86 | 0.00 | 23.86 |
September | 202.83 | 23.26 | 17.67 | 23.32 | 0.00 | 23.32 |
October | 340.00 | 21.47 | 3.83 | 21.47 | 3.83 | 21.46 |
November | 330.00 | 21.11 | 71.00 | 21.11 | 71.00 | 21.11 |
December | 338.00 | 21.11 | 218.83 | 21.11 | 218.83 | 21.11 |
Annual Sum or Average | 3301.00 | 21.64 | 874.33 | 21.64 | 712.17 | 21.56 |
Minimum of Months | 63.83 | 21.11 | 0.83 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.76 | 218.83 | 23.86 | 218.83 | 23.86 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 244.17 | 21.11 | 244.17 | 21.11 |
February | 308.00 | 21.11 | 236.50 | 21.11 | 236.50 | 21.11 |
March | 348.00 | 21.11 | 258.50 | 21.11 | 258.50 | 21.11 |
April | 328.83 | 21.50 | 45.67 | 21.45 | 45.67 | 21.41 |
May | 338.17 | 21.61 | 16.00 | 21.58 | 16.00 | 21.56 |
June | 276.33 | 22.48 | 13.50 | 22.54 | 0.50 | 22.54 |
July | 162.17 | 23.03 | 40.00 | 23.21 | 0.00 | 23.21 |
August | 112.33 | 23.59 | 34.17 | 23.67 | 0.00 | 23.67 |
September | 242.17 | 23.01 | 5.00 | 23.03 | 0.00 | 23.03 |
October | 340.00 | 21.35 | 25.00 | 21.33 | 25.00 | 21.31 |
November | 330.00 | 21.11 | 147.83 | 21.11 | 147.83 | 21.11 |
December | 338.00 | 21.11 | 313.67 | 21.11 | 313.67 | 21.11 |
Annual Sum or Average | 3464.00 | 21.63 | 1380.00 | 21.54 | 1287.83 | 21.45 |
Minimum of Months | 112.33 | 21.11 | 5.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.59 | 313.67 | 23.67 | 313.67 | 23.67 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.08661 | 33.38849 | -0.5043 | 10.48845 |
February | 448.00000 | 21.08133 | 34.34816 | -0.4921 | 10.17121 |
March | 497.00000 | 21.08426 | 34.53675 | -0.4801 | 9.92988 |
April | 479.00000 | 21.63763 | 34.68099 | -0.2707 | 7.64289 |
May | 496.00000 | 21.91735 | 40.40979 | -1.2586 | 39.83663 |
June | 481.00000 | 23.22931 | 46.47306 | -0.7513 | 18.17625 |
July | 495.00000 | 23.66050 | 46.77791 | -0.5839 | 12.89312 |
August | 497.00000 | 23.83178 | 46.70543 | -0.5300 | 11.12463 |
September | 479.00000 | 23.51202 | 44.87750 | -0.6707 | 15.25096 |
October | 496.00000 | 21.53951 | 43.56836 | -0.2492 | 6.89358 |
November | 480.00000 | 21.09822 | 38.60211 | -0.4358 | 9.08247 |
December | 496.00000 | 21.07975 | 32.40108 | -0.5263 | 10.89458 |
Annual Sum or Average | 5840.00000 | 22.06779 | 39.75963 | -0.5637 | 13.57116 |
Minimum of Months | 448.00000 | 21.07975 | 32.40108 | -1.2586 | 6.89358 |
Maximum of Months | 497.00000 | 23.83178 | 46.77791 | -0.2492 | 39.83663 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.42494 | 36.55251 | -0.3725 | 8.26328 |
February | 448.00000 | 21.41411 | 37.26819 | -0.3633 | 7.98612 |
March | 497.00000 | 21.49825 | 37.23388 | -0.3377 | 7.75210 |
April | 479.00000 | 22.70466 | 35.19840 | -0.0220 | 6.08754 |
May | 496.00000 | 23.04774 | 39.39581 | -0.9061 | 23.77291 |
June | 481.00000 | 23.80975 | 44.54734 | -0.5636 | 11.95429 |
July | 495.00000 | 23.87096 | 45.78840 | -0.5058 | 10.51580 |
August | 497.00000 | 23.88693 | 46.03383 | -0.4954 | 10.25095 |
September | 479.00000 | 23.86326 | 43.37322 | -0.5497 | 11.52027 |
October | 496.00000 | 22.67828 | 43.47790 | 0.01441 | 6.01224 |
November | 480.00000 | 21.59399 | 40.90348 | -0.2863 | 7.15061 |
December | 496.00000 | 21.37555 | 35.16856 | -0.4031 | 8.62320 |
Annual Sum or Average | 5840.00000 | 22.60255 | 40.43172 | -0.4001 | 10.01647 |
Minimum of Months | 448.00000 | 21.37555 | 35.16856 | -0.9061 | 6.01224 |
Maximum of Months | 497.00000 | 23.88693 | 46.03383 | 0.01441 | 23.77291 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11876 | 32.67298 | -0.4635 | 9.63273 |
February | 336.00000 | 21.11243 | 33.85079 | -0.4470 | 9.23941 |
March | 379.00000 | 21.15006 | 33.26305 | -0.4330 | 9.00644 |
April | 360.00000 | 22.40675 | 31.85638 | -0.0957 | 6.58571 |
May | 375.00000 | 22.84159 | 37.38270 | -0.9631 | 26.30005 |
June | 366.00000 | 23.85383 | 43.73107 | -0.5499 | 11.71007 |
July | 369.00000 | 23.94519 | 45.26780 | -0.4844 | 10.16008 |
August | 379.00000 | 23.96672 | 45.63647 | -0.4727 | 9.85127 |
September | 360.00000 | 23.89382 | 42.78555 | -0.5395 | 11.37175 |
October | 371.00000 | 22.35231 | 40.76501 | -0.0625 | 6.30463 |
November | 360.00000 | 21.19379 | 37.60024 | -0.3893 | 8.31967 |
December | 369.00000 | 21.10982 | 31.60118 | -0.4852 | 9.98762 |
Annual Sum or Average | 4395.00000 | 22.42097 | 38.07013 | -0.4500 | 10.74106 |
Minimum of Months | 336.00000 | 21.10982 | 31.60118 | -0.9631 | 6.30463 |
Maximum of Months | 379.00000 | 23.96672 | 45.63647 | -0.0625 | 26.30005 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11416 | 32.68336 | -0.4745 | 9.84750 |
February | 336.00000 | 21.11093 | 33.85426 | -0.4565 | 9.41842 |
March | 379.00000 | 21.13915 | 33.28404 | -0.4437 | 9.19938 |
April | 360.00000 | 22.30865 | 32.03503 | -0.1234 | 6.72444 |
May | 375.00000 | 22.73563 | 37.60953 | -1.0027 | 28.05523 |
June | 366.00000 | 23.83210 | 43.80720 | -0.5618 | 12.04156 |
July | 369.00000 | 23.93769 | 45.30048 | -0.4901 | 10.29855 |
August | 379.00000 | 23.96494 | 45.65015 | -0.4756 | 9.90865 |
September | 360.00000 | 23.88515 | 42.83441 | -0.5466 | 11.55054 |
October | 371.00000 | 22.25733 | 41.01103 | -0.0897 | 6.41156 |
November | 360.00000 | 21.17113 | 37.65504 | -0.4035 | 8.54288 |
December | 369.00000 | 21.10970 | 31.60175 | -0.4946 | 10.18303 |
Annual Sum or Average | 4395.00000 | 22.38926 | 38.14663 | -0.4648 | 11.05317 |
Minimum of Months | 336.00000 | 21.10970 | 31.60175 | -1.0027 | 6.41156 |
Maximum of Months | 379.00000 | 23.96494 | 45.65015 | -0.0897 | 28.05523 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11028 | 32.69221 | -0.4881 | 10.12137 |
February | 336.00000 | 21.10995 | 33.85673 | -0.4692 | 9.66747 |
March | 379.00000 | 21.12372 | 33.31382 | -0.4589 | 9.48182 |
April | 360.00000 | 22.10533 | 32.42898 | -0.1788 | 6.97694 |
May | 375.00000 | 22.48662 | 38.15788 | -1.0937 | 32.13456 |
June | 366.00000 | 23.73217 | 44.15487 | -0.6095 | 13.44422 |
July | 369.00000 | 23.90606 | 45.44076 | -0.5119 | 10.84639 |
August | 379.00000 | 23.95689 | 45.71392 | -0.4872 | 10.14582 |
September | 360.00000 | 23.84301 | 43.03243 | -0.5737 | 12.27044 |
October | 371.00000 | 22.04867 | 41.54851 | -0.1466 | 6.56235 |
November | 360.00000 | 21.14430 | 37.72024 | -0.4215 | 8.83581 |
December | 369.00000 | 21.10891 | 31.60372 | -0.5075 | 10.45721 |
Annual Sum or Average | 4395.00000 | 22.31463 | 38.34252 | -0.4969 | 11.79041 |
Minimum of Months | 336.00000 | 21.10891 | 31.60372 | -1.0937 | 6.56235 |
Maximum of Months | 379.00000 | 23.95689 | 45.71392 | -0.1466 | 32.13456 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10988 | 34.42652 | -0.5176 | 10.73838 |
February | 308.00000 | 21.10978 | 35.52387 | -0.4984 | 10.25174 |
March | 348.00000 | 21.10973 | 34.96694 | -0.4905 | 10.09804 |
April | 330.00000 | 21.55130 | 35.19082 | -0.3010 | 7.89070 |
May | 344.00000 | 21.77276 | 41.47438 | -1.3108 | 42.26732 |
June | 336.00000 | 23.03696 | 47.77358 | -0.8158 | 20.52616 |
July | 338.00000 | 23.61377 | 47.81290 | -0.6042 | 13.59142 |
August | 348.00000 | 23.85223 | 47.49831 | -0.5275 | 11.01554 |
September | 330.00000 | 23.41877 | 45.99871 | -0.7031 | 16.22657 |
October | 340.00000 | 21.44705 | 44.61366 | -0.2837 | 7.17378 |
November | 330.00000 | 21.10953 | 39.52422 | -0.4568 | 9.45145 |
December | 338.00000 | 21.10984 | 33.29910 | -0.5381 | 11.12298 |
Annual Sum or Average | 4030.00000 | 22.02755 | 40.71549 | -0.5889 | 14.25883 |
Minimum of Months | 308.00000 | 21.10953 | 33.29910 | -1.3108 | 7.17378 |
Maximum of Months | 348.00000 | 23.85223 | 47.81290 | -0.2837 | 42.26732 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10955 | 34.28774 | -0.5170 | 10.72087 |
February | 308.00000 | 21.10955 | 35.37949 | -0.4991 | 10.26494 |
March | 348.00000 | 21.10964 | 34.82716 | -0.4924 | 10.13478 |
April | 330.00000 | 21.68751 | 34.71681 | -0.2891 | 7.82511 |
May | 344.00000 | 21.96274 | 40.83905 | -1.2821 | 41.00100 |
June | 336.00000 | 23.31665 | 46.82538 | -0.7641 | 18.54669 |
July | 338.00000 | 23.74272 | 47.14255 | -0.5897 | 12.94081 |
August | 348.00000 | 23.89960 | 46.93541 | -0.5326 | 11.07452 |
September | 330.00000 | 23.66548 | 45.01454 | -0.6566 | 14.57827 |
October | 340.00000 | 21.60753 | 44.09938 | -0.2640 | 7.11857 |
November | 330.00000 | 21.11133 | 39.36132 | -0.4588 | 9.48714 |
December | 338.00000 | 21.10983 | 33.14324 | -0.5364 | 11.08265 |
Annual Sum or Average | 4030.00000 | 22.12698 | 40.25335 | -0.5752 | 13.79347 |
Minimum of Months | 308.00000 | 21.10955 | 33.14324 | -1.2821 | 7.11857 |
Maximum of Months | 348.00000 | 23.89960 | 47.14255 | -0.2640 | 41.00100 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10917 | 34.28820 | -0.5205 | 10.79556 |
February | 308.00000 | 21.10983 | 35.37886 | -0.5028 | 10.34292 |
March | 348.00000 | 21.10932 | 34.82770 | -0.4963 | 10.21548 |
April | 330.00000 | 21.66175 | 34.77315 | -0.2984 | 7.92332 |
May | 344.00000 | 21.92440 | 40.92905 | -1.2992 | 41.81804 |
June | 336.00000 | 23.26611 | 46.97712 | -0.7843 | 19.28204 |
July | 338.00000 | 23.72316 | 47.22764 | -0.6005 | 13.27598 |
August | 348.00000 | 23.89708 | 46.98059 | -0.5381 | 11.20340 |
September | 330.00000 | 23.64033 | 45.10569 | -0.6683 | 14.94368 |
October | 340.00000 | 21.57570 | 44.17061 | -0.2746 | 7.19890 |
November | 330.00000 | 21.11063 | 39.36386 | -0.4627 | 9.56295 |
December | 338.00000 | 21.10963 | 33.14400 | -0.5393 | 11.14797 |
Annual Sum or Average | 4030.00000 | 22.11067 | 40.30312 | -0.5838 | 14.03942 |
Minimum of Months | 308.00000 | 21.10917 | 33.14400 | -1.2992 | 7.19890 |
Maximum of Months | 348.00000 | 23.89708 | 47.22764 | -0.2746 | 41.81804 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10959 | 34.28664 | -0.5331 | 11.07677 |
February | 308.00000 | 21.10994 | 35.37888 | -0.5164 | 10.63528 |
March | 348.00000 | 21.10948 | 34.82693 | -0.5097 | 10.50001 |
April | 330.00000 | 21.58810 | 34.93421 | -0.3244 | 8.21143 |
May | 344.00000 | 21.80238 | 41.21795 | -1.3514 | 44.30728 |
June | 336.00000 | 23.07163 | 47.54289 | -0.8564 | 22.02024 |
July | 338.00000 | 23.64315 | 47.54433 | -0.6376 | 14.51748 |
August | 348.00000 | 23.87893 | 47.15806 | -0.5566 | 11.66964 |
September | 330.00000 | 23.50711 | 45.52275 | -0.7212 | 16.71895 |
October | 340.00000 | 21.47007 | 44.40030 | -0.3082 | 7.46977 |
November | 330.00000 | 21.10941 | 39.36791 | -0.4752 | 9.81067 |
December | 338.00000 | 21.10958 | 33.14507 | -0.5511 | 11.42107 |
Annual Sum or Average | 4030.00000 | 22.04986 | 40.48378 | -0.6135 | 14.93023 |
Minimum of Months | 308.00000 | 21.10941 | 33.14507 | -1.3514 | 7.46977 |
Maximum of Months | 348.00000 | 23.87893 | 47.54433 | -0.3082 | 44.30728 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10994 | 34.18270 | -0.5849 | 12.32429 |
February | 308.00000 | 21.10986 | 35.16658 | -0.5706 | 11.89247 |
March | 348.00000 | 21.10985 | 34.68310 | -0.5616 | 11.68787 |
April | 330.00000 | 21.51188 | 34.89506 | -0.3721 | 8.91051 |
May | 344.00000 | 21.64599 | 41.28688 | -1.4456 | 48.96641 |
June | 336.00000 | 22.73176 | 48.16761 | -0.9907 | 27.62080 |
July | 338.00000 | 23.48595 | 47.86122 | -0.7136 | 17.17363 |
August | 348.00000 | 23.79979 | 47.35805 | -0.6104 | 13.21381 |
September | 330.00000 | 23.24502 | 45.89767 | -0.8281 | 20.71473 |
October | 340.00000 | 21.34506 | 44.36318 | -0.3721 | 8.27175 |
November | 330.00000 | 21.10954 | 39.08344 | -0.5214 | 10.79927 |
December | 338.00000 | 21.11000 | 32.84322 | -0.6030 | 12.70525 |
Annual Sum or Average | 4030.00000 | 21.95001 | 40.52394 | -0.6829 | 17.09566 |
Minimum of Months | 308.00000 | 21.10954 | 32.84322 | -1.4456 | 8.27175 |
Maximum of Months | 348.00000 | 23.79979 | 48.16761 | -0.3721 | 48.96641 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.204577E+09 | 49286716.32 | 17.50 | 0.203814E+09 | 763638.34 | 0.00 | 0.73 | 30-APR-16:13 | 0.00 | 01-APR-00:10 | 7713.69 | 30-APR-16:20 | 7713.69 | 30-APR-16:20 | 157.59 | 30-APR-19:40 | 1793.85 | 30-APR-16:20 | 0.00 | 01-APR-00:10 |
May | 83370147.05 | 20909881.85 | 11.83 | 72914882.77 | 10455264.27 | 0.00 | 0.55 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5719.03 | 22-MAY-15:00 | 5158.99 | 22-MAY-15:00 | 569.79 | 22-MAY-14:00 | 1393.57 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.105041E+10 | 0.246348E+09 | 61.67 | 0.861964E+09 | 0.188443E+09 | 0.00 | 0.96 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 11463.49 | 13-JUN-17:00 | 10298.31 | 13-JUN-17:00 | 4997.67 | 25-JUN-18:00 | 2570.33 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.178717E+10 | 0.428416E+09 | 130.22 | 0.153080E+10 | 0.256371E+09 | 0.00 | 1.00 | 21-JUL-16:50 | 0.00 | 01-JUL-00:10 | 12394.90 | 22-JUL-16:20 | 12394.90 | 22-JUL-16:20 | 2442.77 | 23-JUL-17:02 | 2877.59 | 22-JUL-16:20 | 0.00 | 01-JUL-00:10 |
August | 0.148642E+10 | 0.361456E+09 | 157.83 | 0.123168E+10 | 0.254746E+09 | 0.00 | 0.90 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 10155.15 | 14-AUG-17:00 | 10155.15 | 14-AUG-17:00 | 1896.89 | 17-AUG-14:00 | 2357.84 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.792907E+09 | 0.192159E+09 | 72.83 | 0.666842E+09 | 0.126065E+09 | 0.00 | 0.72 | 13-SEP-16:10 | 0.00 | 01-SEP-00:10 | 8018.60 | 13-SEP-16:10 | 6821.43 | 13-SEP-16:10 | 1636.60 | 12-SEP-14:00 | 1824.66 | 13-SEP-16:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.540485E+10 | 0.129858E+10 | 451.89 | 0.456801E+10 | 0.836844E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.178717E+10 | 0.428416E+09 | 157.83 | 0.153080E+10 | 0.256371E+09 | 0.00 | 1.00 | 0.00 | 12394.90 | 12394.90 | 4997.67 | 2877.59 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.152611E+09 | 31482330.57 | 20.59 | 0.151807E+09 | 803956.12 | 0.00 | 1.00 | 29-APR-18:01 | 0.00 | 01-APR-00:10 | 13508.92 | 30-APR-19:10 | 13508.92 | 30-APR-19:10 | 1961.63 | 30-APR-20:00 | 2597.71 | 30-APR-19:10 | 0.00 | 01-APR-00:10 |
May | 70354702.35 | 14705440.83 | 11.88 | 66666270.35 | 3688432.01 | 0.00 | 1.00 | 21-MAY-17:01 | 0.00 | 01-MAY-00:10 | 13594.98 | 21-MAY-18:11 | 13541.39 | 21-MAY-17:51 | 614.96 | 21-MAY-18:00 | 2542.15 | 21-MAY-18:11 | 0.00 | 01-MAY-00:10 |
June | 0.618744E+09 | 0.126497E+09 | 64.69 | 0.535710E+09 | 83033823.81 | 0.00 | 1.00 | 12-JUN-20:02 | 0.00 | 01-JUN-00:10 | 14917.82 | 25-JUN-17:53 | 12090.19 | 25-JUN-17:02 | 6279.99 | 25-JUN-17:53 | 2774.48 | 25-JUN-17:53 | 0.00 | 01-JUN-00:10 |
July | 0.950419E+09 | 0.197391E+09 | 104.98 | 0.860095E+09 | 90324326.84 | 0.00 | 1.00 | 09-JUL-17:02 | 0.00 | 01-JUL-00:10 | 14324.74 | 23-JUL-17:02 | 12448.77 | 22-JUL-20:32 | 4888.35 | 23-JUL-19:13 | 2717.60 | 22-JUL-20:40 | 0.00 | 01-JUL-00:10 |
August | 0.747604E+09 | 0.157492E+09 | 126.59 | 0.660257E+09 | 87347234.57 | 0.00 | 1.00 | 06-AUG-17:01 | 0.00 | 01-AUG-00:10 | 13904.34 | 13-AUG-17:02 | 13284.53 | 14-AUG-20:08 | 3428.23 | 13-AUG-17:02 | 2601.89 | 13-AUG-17:02 | 0.00 | 01-AUG-00:10 |
September | 0.453493E+09 | 95965954.40 | 75.61 | 0.399123E+09 | 54370481.05 | 0.00 | 1.00 | 10-SEP-17:02 | 0.00 | 01-SEP-00:10 | 14221.87 | 10-SEP-17:02 | 11612.86 | 24-SEP-17:02 | 4912.51 | 10-SEP-18:03 | 2656.60 | 10-SEP-17:02 | 0.00 | 01-SEP-00:10 |
October | 2522038.68 | 573229.48 | 5.17 | 2196889.61 | 325149.07 | 0.00 | 0.23 | 12-OCT-20:20 | 0.00 | 01-OCT-00:10 | 1400.33 | 12-OCT-20:20 | 1218.83 | 12-OCT-20:20 | 183.80 | 08-OCT-17:10 | 311.48 | 12-OCT-20:20 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.299575E+10 | 0.624106E+09 | 409.51 | 0.267586E+10 | 0.319893E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.950419E+09 | 0.197391E+09 | 126.59 | 0.860095E+09 | 90324326.84 | 0.00 | 1.00 | 0.00 | 14917.82 | 13541.39 | 6279.99 | 2774.48 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 61128946.27 | 13135617.99 | 13.17 | 61118996.62 | 9949.65 | 0.00 | 0.60 | 30-APR-15:00 | 0.00 | 01-APR-00:10 | 4638.48 | 30-APR-15:00 | 4638.48 | 30-APR-15:00 | 5.68 | 28-APR-15:00 | 976.00 | 30-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 43456296.68 | 9505786.72 | 9.00 | 40882269.27 | 2574027.41 | 0.00 | 0.51 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 3967.01 | 22-MAY-15:00 | 3766.72 | 22-MAY-15:00 | 229.89 | 22-MAY-14:00 | 850.80 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.509501E+09 | 0.107598E+09 | 64.25 | 0.447747E+09 | 61754189.50 | 0.00 | 0.79 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 6652.60 | 13-JUN-17:00 | 6132.15 | 13-JUN-17:00 | 1096.55 | 26-JUN-16:10 | 1373.68 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.672864E+09 | 0.144191E+09 | 84.64 | 0.625617E+09 | 47246978.26 | 0.00 | 0.85 | 22-JUL-13:00 | 0.00 | 01-JUL-00:10 | 7245.38 | 22-JUL-13:00 | 7186.39 | 22-JUL-13:00 | 1072.43 | 23-JUL-07:03 | 1499.66 | 22-JUL-13:00 | 0.00 | 01-JUL-00:10 |
August | 0.561191E+09 | 0.121525E+09 | 106.83 | 0.500922E+09 | 60269356.22 | 0.00 | 0.74 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 6010.88 | 14-AUG-17:00 | 6010.88 | 14-AUG-17:00 | 882.95 | 17-AUG-14:00 | 1274.92 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.353132E+09 | 76794333.84 | 65.17 | 0.315961E+09 | 37170805.70 | 0.00 | 0.57 | 13-SEP-16:10 | 0.00 | 01-SEP-00:10 | 4559.00 | 13-SEP-16:10 | 4072.07 | 13-SEP-16:10 | 664.36 | 12-SEP-14:00 | 945.04 | 13-SEP-16:10 | 0.00 | 01-SEP-00:10 |
October | 941.64 | 222.08 | 4.00 | 940.50 | 1.14 | 0.00 | 0.00 | 11-OCT-11:20 | 0.00 | 01-OCT-00:10 | 0.16 | 11-OCT-11:20 | 0.16 | 11-OCT-11:20 | 0.00 | 11-OCT-09:50 | 0.04 | 11-OCT-11:20 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.220127E+10 | 0.472749E+09 | 347.06 | 0.199225E+10 | 0.209025E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.672864E+09 | 0.144191E+09 | 106.83 | 0.625617E+09 | 61754189.50 | 0.00 | 0.85 | 0.00 | 7245.38 | 7186.39 | 1096.55 | 1499.66 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 58094710.77 | 12497787.53 | 11.67 | 58094684.34 | 26.43 | 0.00 | 0.59 | 30-APR-15:00 | 0.00 | 01-APR-00:10 | 4548.55 | 30-APR-15:00 | 4548.55 | 30-APR-15:00 | 0.03 | 28-APR-15:10 | 960.15 | 30-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 39779591.37 | 8748201.44 | 8.50 | 37455251.95 | 2324339.41 | 0.00 | 0.49 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 3783.04 | 22-MAY-15:00 | 3590.71 | 22-MAY-15:00 | 215.48 | 22-MAY-14:00 | 816.36 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.496705E+09 | 0.105115E+09 | 61.00 | 0.436359E+09 | 60345586.92 | 0.00 | 0.78 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 6588.01 | 13-JUN-17:00 | 6070.48 | 13-JUN-17:00 | 1083.69 | 26-JUN-16:10 | 1363.41 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.662452E+09 | 0.142069E+09 | 81.47 | 0.616091E+09 | 46360485.40 | 0.00 | 0.85 | 22-JUL-13:00 | 0.00 | 01-JUL-00:10 | 7230.11 | 22-JUL-13:00 | 7171.09 | 22-JUL-13:00 | 1105.09 | 23-JUL-07:03 | 1497.76 | 22-JUL-13:00 | 0.00 | 01-JUL-00:10 |
August | 0.547874E+09 | 0.118766E+09 | 104.00 | 0.489034E+09 | 58839966.42 | 0.00 | 0.74 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 5965.24 | 14-AUG-17:00 | 5965.24 | 14-AUG-17:00 | 877.21 | 17-AUG-14:00 | 1267.45 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.339631E+09 | 73988847.79 | 61.67 | 0.304001E+09 | 35630101.71 | 0.00 | 0.57 | 13-SEP-16:10 | 0.00 | 01-SEP-00:10 | 4515.56 | 13-SEP-16:10 | 4032.89 | 13-SEP-16:10 | 645.18 | 12-SEP-14:00 | 937.56 | 13-SEP-16:10 | 0.00 | 01-SEP-00:10 |
October | 1625.10 | 383.34 | 5.50 | 1625.10 | -0.0 | 0.00 | 0.00 | 11-OCT-11:20 | 0.00 | 01-OCT-00:10 | 0.28 | 11-OCT-11:20 | 0.28 | 11-OCT-11:20 | 0.00 | 02-OCT-15:30 | 0.06 | 11-OCT-11:20 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.214454E+10 | 0.461185E+09 | 333.81 | 0.194104E+10 | 0.203501E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.662452E+09 | 0.142069E+09 | 104.00 | 0.616091E+09 | 60345586.92 | 0.00 | 0.85 | 0.00 | 7230.11 | 7171.09 | 1105.09 | 1497.76 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 50585792.60 | 10933043.87 | 8.50 | 50585782.65 | 9.94 | 0.00 | 0.56 | 30-APR-15:00 | 0.00 | 01-APR-00:10 | 4273.57 | 30-APR-15:00 | 4273.57 | 30-APR-15:00 | 0.02 | 28-APR-15:10 | 909.65 | 30-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 33080740.91 | 7352026.34 | 7.67 | 31182563.70 | 1898177.22 | 0.00 | 0.45 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 3405.45 | 22-MAY-15:00 | 3229.92 | 22-MAY-15:00 | 186.26 | 22-MAY-14:00 | 743.57 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.454657E+09 | 96743627.60 | 54.17 | 0.399340E+09 | 55317522.38 | 0.00 | 0.76 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 6367.14 | 13-JUN-17:00 | 5859.90 | 13-JUN-17:00 | 1026.90 | 26-JUN-16:10 | 1325.09 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.612205E+09 | 0.131712E+09 | 73.64 | 0.570703E+09 | 41501833.35 | 0.00 | 0.84 | 22-JUL-13:00 | 0.00 | 01-JUL-00:10 | 7082.28 | 22-JUL-13:00 | 7021.86 | 22-JUL-13:00 | 788.73 | 23-JUL-13:00 | 1472.05 | 22-JUL-13:00 | 0.00 | 01-JUL-00:10 |
August | 0.492942E+09 | 0.107138E+09 | 93.00 | 0.441108E+09 | 51834899.35 | 0.00 | 0.72 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 5810.95 | 14-AUG-17:00 | 5810.95 | 14-AUG-17:00 | 835.27 | 17-AUG-14:00 | 1239.50 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.293888E+09 | 64339501.21 | 56.50 | 0.263475E+09 | 30413573.03 | 0.00 | 0.55 | 13-SEP-16:10 | 0.00 | 01-SEP-00:10 | 4327.95 | 13-SEP-16:10 | 3864.28 | 13-SEP-16:10 | 570.61 | 12-SEP-14:00 | 903.35 | 13-SEP-16:10 | 0.00 | 01-SEP-00:10 |
October | 507.56 | 119.51 | 3.00 | 507.56 | 0.00 | 0.00 | 0.00 | 11-OCT-10:50 | 0.00 | 01-OCT-00:10 | 0.19 | 11-OCT-10:50 | 0.19 | 11-OCT-10:50 | 0.00 | 11-OCT-11:00 | 0.04 | 11-OCT-10:50 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.193736E+10 | 0.418218E+09 | 296.47 | 0.175639E+10 | 0.180966E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.612205E+09 | 0.131712E+09 | 93.00 | 0.570703E+09 | 55317522.38 | 0.00 | 0.84 | 0.00 | 7082.28 | 7021.86 | 1026.90 | 1472.05 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 86538624.07 | 21541212.20 | 9.67 | 86061563.24 | 477060.82 | 0.00 | 0.62 | 30-APR-15:00 | 0.00 | 01-APR-00:10 | 6618.42 | 30-APR-15:00 | 6618.42 | 30-APR-15:00 | 57.90 | 29-APR-15:00 | 1588.29 | 30-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 46776883.10 | 11910135.10 | 4.50 | 41582275.02 | 5194608.08 | 0.00 | 0.48 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5141.48 | 22-MAY-15:00 | 4549.27 | 22-MAY-15:00 | 592.21 | 22-MAY-15:00 | 1274.68 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.754049E+09 | 0.181040E+09 | 47.17 | 0.625319E+09 | 0.128731E+09 | 0.00 | 0.86 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 10305.84 | 13-JUN-17:00 | 9119.80 | 13-JUN-17:00 | 2181.43 | 26-JUN-16:20 | 2382.06 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.118914E+10 | 0.286935E+09 | 93.25 | 0.103557E+10 | 0.153568E+09 | 0.00 | 1.00 | 22-JUL-14:40 | 0.00 | 01-JUL-00:10 | 12555.45 | 22-JUL-15:00 | 12555.45 | 22-JUL-15:00 | 1640.57 | 23-JUL-16:00 | 2896.51 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.117240E+10 | 0.286742E+09 | 117.33 | 0.972664E+09 | 0.199738E+09 | 0.00 | 0.81 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 9268.74 | 14-AUG-17:00 | 9268.74 | 14-AUG-17:00 | 1958.99 | 17-AUG-14:40 | 2208.85 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.592542E+09 | 0.145917E+09 | 57.17 | 0.505368E+09 | 87174198.66 | 0.00 | 0.67 | 13-SEP-14:30 | 0.00 | 01-SEP-00:10 | 7553.25 | 13-SEP-14:40 | 6305.34 | 13-SEP-14:20 | 1483.46 | 12-SEP-14:10 | 1746.24 | 13-SEP-14:40 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.384145E+10 | 0.934086E+09 | 329.08 | 0.326656E+10 | 0.574883E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.118914E+10 | 0.286935E+09 | 117.33 | 0.103557E+10 | 0.199738E+09 | 0.00 | 1.00 | 0.00 | 12555.45 | 12555.45 | 2181.43 | 2896.51 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 42127039.31 | 9060856.58 | 7.17 | 42127039.31 | -0.0 | 0.00 | 0.64 | 30-APR-15:00 | 0.00 | 01-APR-00:10 | 3946.14 | 30-APR-15:00 | 3946.14 | 30-APR-15:00 | 0.00 | 30-APR-14:00 | 822.34 | 30-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 25476258.00 | 5645932.41 | 6.17 | 23803408.06 | 1672849.94 | 0.00 | 0.49 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 3044.51 | 22-MAY-15:00 | 2824.17 | 22-MAY-15:00 | 220.33 | 22-MAY-15:00 | 655.80 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.391328E+09 | 82170556.62 | 43.33 | 0.339359E+09 | 51968891.74 | 0.00 | 0.84 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5769.61 | 13-JUN-17:00 | 5220.08 | 13-JUN-17:00 | 961.33 | 26-JUN-16:10 | 1169.63 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.547728E+09 | 0.115174E+09 | 68.58 | 0.505990E+09 | 41737458.81 | 0.00 | 0.99 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 | 6995.75 | 22-JUL-15:00 | 6995.75 | 22-JUL-15:00 | 719.58 | 23-JUL-16:00 | 1410.57 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.475923E+09 | 0.101927E+09 | 82.17 | 0.420280E+09 | 55643431.46 | 0.00 | 0.81 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 5332.00 | 14-AUG-17:00 | 5332.00 | 14-AUG-17:00 | 849.77 | 17-AUG-14:40 | 1107.75 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.258932E+09 | 56018914.66 | 51.17 | 0.231504E+09 | 27427625.83 | 0.00 | 0.63 | 13-SEP-14:40 | 0.00 | 01-SEP-00:10 | 4050.61 | 13-SEP-14:40 | 3541.10 | 13-SEP-14:30 | 582.44 | 12-SEP-14:10 | 826.10 | 13-SEP-14:40 | 0.00 | 01-SEP-00:10 |
October | 13920.95 | 3271.35 | 0.17 | 13920.95 | 0.00 | 0.00 | 0.00 | 07-OCT-13:40 | 0.00 | 01-OCT-00:10 | 23.20 | 07-OCT-13:40 | 23.20 | 07-OCT-13:40 | 0.00 | 07-OCT-13:40 | 5.45 | 07-OCT-13:40 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.174153E+10 | 0.370000E+09 | 258.75 | 0.156308E+10 | 0.178450E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.547728E+09 | 0.115174E+09 | 82.17 | 0.505990E+09 | 55643431.46 | 0.00 | 0.99 | 0.00 | 6995.75 | 6995.75 | 961.33 | 1410.57 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 40460448.78 | 8710469.05 | 7.17 | 40460448.78 | -0.0 | 0.00 | 0.63 | 30-APR-15:00 | 0.00 | 01-APR-00:10 | 3865.76 | 30-APR-15:00 | 3865.76 | 30-APR-15:00 | 0.00 | 30-APR-12:00 | 806.90 | 30-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 24173540.31 | 5367720.44 | 5.33 | 22588735.84 | 1584804.46 | 0.00 | 0.48 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 2950.66 | 22-MAY-15:00 | 2736.44 | 22-MAY-15:00 | 214.22 | 22-MAY-15:00 | 637.20 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.377505E+09 | 79398000.02 | 43.17 | 0.327355E+09 | 50150018.83 | 0.00 | 0.83 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5671.99 | 13-JUN-17:00 | 5130.50 | 13-JUN-17:00 | 936.64 | 26-JUN-16:10 | 1151.40 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.533106E+09 | 0.112124E+09 | 67.50 | 0.492948E+09 | 40157737.39 | 0.00 | 0.99 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 | 6932.89 | 22-JUL-15:00 | 6932.89 | 22-JUL-15:00 | 706.91 | 23-JUL-16:00 | 1397.42 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.460625E+09 | 98726559.75 | 81.00 | 0.407092E+09 | 53532930.39 | 0.00 | 0.80 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 5259.73 | 14-AUG-17:00 | 5259.73 | 14-AUG-17:00 | 833.97 | 17-AUG-14:40 | 1093.48 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.248259E+09 | 53776031.93 | 50.33 | 0.222055E+09 | 26203457.20 | 0.00 | 0.62 | 13-SEP-14:40 | 0.00 | 01-SEP-00:10 | 3975.71 | 13-SEP-14:40 | 3474.90 | 13-SEP-14:30 | 562.94 | 12-SEP-14:10 | 811.88 | 13-SEP-14:40 | 0.00 | 01-SEP-00:10 |
October | 4923.58 | 1155.52 | 0.17 | 4923.58 | 0.00 | 0.00 | 0.00 | 07-OCT-16:10 | 0.00 | 01-OCT-00:10 | 8.21 | 07-OCT-16:10 | 8.21 | 07-OCT-16:10 | 0.00 | 07-OCT-16:10 | 1.93 | 07-OCT-16:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.168413E+10 | 0.358104E+09 | 254.67 | 0.151250E+10 | 0.171629E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.533106E+09 | 0.112124E+09 | 81.00 | 0.492948E+09 | 53532930.39 | 0.00 | 0.99 | 0.00 | 6932.89 | 6932.89 | 936.64 | 1397.42 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 36098232.14 | 7804152.58 | 5.00 | 36098232.14 | 0.00 | 0.00 | 0.61 | 30-APR-15:00 | 0.00 | 01-APR-00:10 | 3643.52 | 30-APR-15:00 | 3643.52 | 30-APR-15:00 | 0.00 | 30-APR-15:10 | 765.27 | 30-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 20827073.81 | 4652365.32 | 4.83 | 19466823.09 | 1360250.72 | 0.00 | 0.46 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 2724.20 | 22-MAY-15:00 | 2524.91 | 22-MAY-15:00 | 199.30 | 22-MAY-15:00 | 592.52 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.340469E+09 | 71993847.58 | 39.83 | 0.295194E+09 | 45275418.57 | 0.00 | 0.82 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5439.14 | 13-JUN-17:00 | 4916.24 | 13-JUN-17:00 | 877.78 | 26-JUN-15:00 | 1109.27 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.493194E+09 | 0.103840E+09 | 62.17 | 0.457508E+09 | 35686242.52 | 0.00 | 0.99 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 | 6790.43 | 22-JUL-15:00 | 6790.43 | 22-JUL-15:00 | 676.02 | 23-JUL-16:00 | 1369.30 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.411994E+09 | 88606400.27 | 75.67 | 0.365148E+09 | 46846125.54 | 0.00 | 0.79 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 5056.57 | 14-AUG-17:00 | 5056.57 | 14-AUG-17:00 | 791.16 | 17-AUG-14:40 | 1055.57 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.213304E+09 | 46411247.78 | 44.00 | 0.190865E+09 | 22439247.48 | 0.00 | 0.61 | 13-SEP-14:40 | 0.00 | 01-SEP-00:10 | 3769.34 | 13-SEP-14:40 | 3293.02 | 13-SEP-14:40 | 504.96 | 12-SEP-14:10 | 773.80 | 13-SEP-14:40 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.151589E+10 | 0.323308E+09 | 231.50 | 0.136428E+10 | 0.151607E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.493194E+09 | 0.103840E+09 | 75.67 | 0.457508E+09 | 46846125.54 | 0.00 | 0.99 | 0.00 | 6790.43 | 6790.43 | 877.78 | 1369.30 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 33936532.94 | 7400581.31 | 4.83 | 33936532.94 | -0.0 | 0.00 | 0.57 | 30-APR-15:00 | 0.00 | 01-APR-00:10 | 3435.80 | 30-APR-15:00 | 3435.80 | 30-APR-15:00 | 0.00 | 30-APR-15:10 | 729.21 | 30-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 18208865.81 | 4100979.61 | 4.00 | 17023045.09 | 1185820.72 | 0.00 | 0.42 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 2521.27 | 22-MAY-15:00 | 2336.24 | 22-MAY-15:00 | 185.02 | 22-MAY-15:00 | 553.80 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.318176E+09 | 67657355.75 | 38.33 | 0.276175E+09 | 42001028.90 | 0.00 | 0.80 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5327.46 | 13-JUN-17:00 | 4812.04 | 13-JUN-17:00 | 828.80 | 26-JUN-15:00 | 1093.67 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.480950E+09 | 0.100881E+09 | 51.33 | 0.447802E+09 | 33148028.55 | 0.00 | 0.99 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 | 6828.73 | 22-JUL-15:00 | 6828.73 | 22-JUL-15:00 | 690.52 | 23-JUL-13:00 | 1379.26 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.365888E+09 | 79003734.29 | 66.67 | 0.325625E+09 | 40262985.43 | 0.00 | 0.76 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 4872.99 | 14-AUG-17:00 | 4872.99 | 14-AUG-17:00 | 747.37 | 17-AUG-14:10 | 1026.95 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.182115E+09 | 39882995.96 | 41.00 | 0.162337E+09 | 19777950.81 | 0.00 | 0.58 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 | 3614.42 | 13-SEP-14:20 | 3160.42 | 13-SEP-14:20 | 472.53 | 12-SEP-14:10 | 747.94 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.139927E+10 | 0.298926E+09 | 206.17 | 0.126290E+10 | 0.136376E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.480950E+09 | 0.100881E+09 | 66.67 | 0.447802E+09 | 42001028.90 | 0.00 | 0.99 | 0.00 | 6828.73 | 6828.73 | 828.80 | 1379.26 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.68 | 48.91 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.97 | 46.97 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 24.10 | 39.83 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 73.18 | 33.50 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 55.20 | 29.49 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 51.97 | 24.19 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.86 | 22.84 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 76.12 | 25.01 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 89.52 | 31.27 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 55.39 | 37.58 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.14 | 44.58 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.44 | 54.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 53.05 | 36.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 24.10 | 22.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 89.52 | 54.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.68 | 48.91 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.97 | 46.97 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 24.10 | 39.83 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 73.18 | 33.50 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 55.20 | 29.49 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 51.97 | 24.19 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.86 | 22.84 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 76.12 | 25.01 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 89.52 | 31.27 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 55.39 | 37.58 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.14 | 44.58 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.44 | 54.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 53.05 | 36.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 24.10 | 22.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 89.52 | 54.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.68 | 48.91 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.97 | 46.97 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 24.10 | 39.83 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 73.18 | 33.50 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 55.20 | 29.49 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 51.97 | 24.19 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.86 | 22.84 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 76.12 | 25.01 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 89.52 | 31.27 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 55.39 | 37.58 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.14 | 44.58 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.44 | 54.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 53.05 | 36.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 24.10 | 22.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 89.52 | 54.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.68 | 48.91 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.97 | 46.97 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 24.10 | 39.83 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 73.18 | 33.50 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 55.20 | 29.49 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 51.97 | 24.19 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.86 | 22.84 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 76.12 | 25.01 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 89.52 | 31.27 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 55.39 | 37.58 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.14 | 44.58 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.44 | 54.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 53.05 | 36.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 24.10 | 22.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 89.52 | 54.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.86 | 22.88 | 11.99 | 47.76 | 58.42 | 0.00 | 0.00 | 0.00 |
February | 42.12 | 25.94 | 16.18 | 60.16 | 56.07 | 0.00 | 0.00 | 0.00 |
March | 25.63 | 7.44 | 18.19 | 29.07 | 47.59 | 0.00 | 0.00 | 0.00 |
April | 52.13 | 22.92 | 29.21 | 88.01 | 40.06 | 0.00 | 0.00 | 0.00 |
May | 42.54 | 12.81 | 29.73 | 66.44 | 35.23 | 0.00 | 0.00 | 0.00 |
June | 39.18 | 8.40 | 30.78 | 62.53 | 28.91 | 0.00 | 0.00 | 0.00 |
July | 42.31 | 12.09 | 30.22 | 73.17 | 27.32 | 0.00 | 0.00 | 0.00 |
August | 49.98 | 21.61 | 28.37 | 91.48 | 29.96 | 0.00 | 0.00 | 0.00 |
September | 60.21 | 34.97 | 25.24 | 107.61 | 37.43 | 0.00 | 0.00 | 0.00 |
October | 42.25 | 24.86 | 17.40 | 66.61 | 44.93 | 0.00 | 0.00 | 0.00 |
November | 30.35 | 18.73 | 11.62 | 42.30 | 53.24 | 0.00 | 0.00 | 0.00 |
December | 24.19 | 15.74 | 8.45 | 31.84 | 65.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.41 | 18.95 | 21.46 | 63.82 | 43.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.19 | 7.44 | 8.45 | 29.07 | 27.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.21 | 34.97 | 30.78 | 107.61 | 65.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.86 | 22.88 | 11.99 | 47.76 | 58.42 | 0.00 | 0.00 | 0.00 |
February | 42.12 | 25.94 | 16.18 | 60.16 | 56.07 | 0.00 | 0.00 | 0.00 |
March | 25.63 | 7.44 | 18.19 | 29.07 | 47.59 | 0.00 | 0.00 | 0.00 |
April | 52.13 | 22.92 | 29.21 | 88.01 | 40.06 | 0.00 | 0.00 | 0.00 |
May | 42.54 | 12.81 | 29.73 | 66.44 | 35.23 | 0.00 | 0.00 | 0.00 |
June | 39.18 | 8.40 | 30.78 | 62.53 | 28.91 | 0.00 | 0.00 | 0.00 |
July | 42.31 | 12.09 | 30.22 | 73.17 | 27.32 | 0.00 | 0.00 | 0.00 |
August | 49.98 | 21.61 | 28.37 | 91.48 | 29.96 | 0.00 | 0.00 | 0.00 |
September | 60.21 | 34.97 | 25.24 | 107.61 | 37.43 | 0.00 | 0.00 | 0.00 |
October | 42.25 | 24.86 | 17.40 | 66.61 | 44.93 | 0.00 | 0.00 | 0.00 |
November | 30.35 | 18.73 | 11.62 | 42.30 | 53.24 | 0.00 | 0.00 | 0.00 |
December | 24.19 | 15.74 | 8.45 | 31.84 | 65.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.41 | 18.95 | 21.46 | 63.82 | 43.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.19 | 7.44 | 8.45 | 29.07 | 27.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.21 | 34.97 | 30.78 | 107.61 | 65.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.24 | 51.12 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.43 | 49.21 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 23.52 | 42.08 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 71.70 | 36.29 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 53.53 | 32.27 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 50.72 | 25.65 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.20 | 23.69 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.73 | 25.63 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 88.74 | 32.46 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 54.22 | 40.81 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 34.72 | 46.99 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.13 | 57.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 52.25 | 38.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 23.52 | 23.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 88.74 | 57.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.24 | 51.12 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.43 | 49.21 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 23.52 | 42.08 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 71.70 | 36.29 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 53.53 | 32.27 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 50.72 | 25.65 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.20 | 23.69 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.73 | 25.63 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 88.74 | 32.46 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 54.22 | 40.81 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 34.72 | 46.99 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.13 | 57.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 52.25 | 38.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 23.52 | 23.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 88.74 | 57.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.86 | 22.88 | 11.99 | 47.24 | 61.06 | 0.00 | 0.00 | 0.00 |
February | 42.12 | 25.94 | 16.18 | 59.51 | 58.73 | 0.00 | 0.00 | 0.00 |
March | 25.63 | 7.44 | 18.19 | 28.37 | 50.28 | 0.00 | 0.00 | 0.00 |
April | 52.13 | 22.92 | 29.21 | 86.24 | 43.37 | 0.00 | 0.00 | 0.00 |
May | 42.54 | 12.81 | 29.73 | 64.46 | 38.51 | 0.00 | 0.00 | 0.00 |
June | 39.18 | 8.40 | 30.78 | 61.05 | 30.65 | 0.00 | 0.00 | 0.00 |
July | 42.31 | 12.09 | 30.22 | 72.39 | 28.33 | 0.00 | 0.00 | 0.00 |
August | 49.98 | 21.61 | 28.37 | 91.03 | 30.70 | 0.00 | 0.00 | 0.00 |
September | 60.21 | 34.97 | 25.24 | 106.69 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 42.25 | 24.86 | 17.40 | 65.23 | 48.76 | 0.00 | 0.00 | 0.00 |
November | 30.35 | 18.73 | 11.62 | 41.80 | 56.11 | 0.00 | 0.00 | 0.00 |
December | 24.19 | 15.74 | 8.45 | 31.48 | 68.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.41 | 18.95 | 21.46 | 62.87 | 46.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.19 | 7.44 | 8.45 | 28.37 | 28.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.21 | 34.97 | 30.78 | 106.69 | 68.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.36 | 50.33 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.55 | 48.49 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 23.62 | 41.46 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 71.69 | 36.15 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 53.47 | 32.32 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 50.59 | 26.26 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.05 | 24.40 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.67 | 26.37 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 88.71 | 33.08 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 54.25 | 40.58 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 34.82 | 46.17 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.23 | 56.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 52.26 | 38.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 23.62 | 24.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 88.71 | 56.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.36 | 50.33 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.55 | 48.49 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 23.62 | 41.46 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 71.69 | 36.15 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 53.47 | 32.32 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 50.59 | 26.26 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.05 | 24.40 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.67 | 26.37 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 88.71 | 33.08 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 54.25 | 40.58 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 34.82 | 46.17 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.23 | 56.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 52.26 | 38.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 23.62 | 24.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 88.71 | 56.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.67 | 22.75 | 11.92 | 47.13 | 59.79 | 0.00 | 0.00 | 0.00 |
February | 41.89 | 25.80 | 16.09 | 59.33 | 57.57 | 0.00 | 0.00 | 0.00 |
March | 25.49 | 7.40 | 18.09 | 28.33 | 49.27 | 0.00 | 0.00 | 0.00 |
April | 51.84 | 22.79 | 29.05 | 85.77 | 42.97 | 0.00 | 0.00 | 0.00 |
May | 42.31 | 12.74 | 29.57 | 64.03 | 38.38 | 0.00 | 0.00 | 0.00 |
June | 38.97 | 8.35 | 30.61 | 60.56 | 31.19 | 0.00 | 0.00 | 0.00 |
July | 42.08 | 12.02 | 30.06 | 71.82 | 29.01 | 0.00 | 0.00 | 0.00 |
August | 49.71 | 21.50 | 28.21 | 90.45 | 31.40 | 0.00 | 0.00 | 0.00 |
September | 59.88 | 34.78 | 25.10 | 106.07 | 39.37 | 0.00 | 0.00 | 0.00 |
October | 42.02 | 24.72 | 17.30 | 64.91 | 48.24 | 0.00 | 0.00 | 0.00 |
November | 30.19 | 18.62 | 11.56 | 41.70 | 54.84 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.66 | 8.41 | 31.43 | 66.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.19 | 18.85 | 21.34 | 62.53 | 45.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.06 | 7.40 | 8.41 | 28.33 | 29.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.88 | 34.78 | 30.61 | 106.07 | 66.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.44 | 49.79 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.63 | 48.01 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 23.71 | 40.99 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 71.91 | 35.63 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 53.70 | 31.84 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 50.68 | 26.05 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.10 | 24.26 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.69 | 26.28 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 88.76 | 32.90 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 54.40 | 39.98 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 34.90 | 45.60 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.28 | 55.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 52.36 | 38.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 23.71 | 24.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 88.76 | 55.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.44 | 49.79 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.63 | 48.01 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 23.71 | 40.99 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 71.91 | 35.63 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 53.70 | 31.84 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 50.68 | 26.05 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.10 | 24.26 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.69 | 26.28 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 88.76 | 32.90 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 54.40 | 39.98 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 34.90 | 45.60 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.28 | 55.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 52.36 | 38.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 23.71 | 24.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 88.76 | 55.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.67 | 22.75 | 11.92 | 47.22 | 59.15 | 0.00 | 0.00 | 0.00 |
February | 41.89 | 25.80 | 16.09 | 59.42 | 56.99 | 0.00 | 0.00 | 0.00 |
March | 25.49 | 7.40 | 18.09 | 28.44 | 48.71 | 0.00 | 0.00 | 0.00 |
April | 51.84 | 22.79 | 29.05 | 86.03 | 42.35 | 0.00 | 0.00 | 0.00 |
May | 42.31 | 12.74 | 29.57 | 64.30 | 37.80 | 0.00 | 0.00 | 0.00 |
June | 38.97 | 8.35 | 30.61 | 60.67 | 30.94 | 0.00 | 0.00 | 0.00 |
July | 42.08 | 12.02 | 30.06 | 71.88 | 28.85 | 0.00 | 0.00 | 0.00 |
August | 49.71 | 21.50 | 28.21 | 90.48 | 31.29 | 0.00 | 0.00 | 0.00 |
September | 59.88 | 34.78 | 25.10 | 106.14 | 39.15 | 0.00 | 0.00 | 0.00 |
October | 42.02 | 24.72 | 17.30 | 65.09 | 47.52 | 0.00 | 0.00 | 0.00 |
November | 30.19 | 18.62 | 11.56 | 41.79 | 54.16 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.66 | 8.41 | 31.49 | 66.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.19 | 18.85 | 21.34 | 62.65 | 45.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.06 | 7.40 | 8.41 | 28.44 | 28.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.88 | 34.78 | 30.61 | 106.14 | 66.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.53 | 49.30 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.73 | 47.54 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 23.83 | 40.53 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 72.35 | 34.86 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 54.21 | 31.01 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 51.03 | 25.50 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.29 | 23.92 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.79 | 26.03 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 88.94 | 32.47 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 54.73 | 39.05 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.00 | 45.06 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.34 | 55.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 52.57 | 37.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 23.83 | 23.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 88.94 | 55.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.53 | 49.30 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.73 | 47.54 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 23.83 | 40.53 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 72.35 | 34.86 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 54.21 | 31.01 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 51.03 | 25.50 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.29 | 23.92 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.79 | 26.03 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 88.94 | 32.47 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 54.73 | 39.05 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.00 | 45.06 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.34 | 55.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 52.57 | 37.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 23.83 | 23.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 88.94 | 55.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.67 | 22.75 | 11.92 | 47.34 | 58.57 | 0.00 | 0.00 | 0.00 |
February | 41.89 | 25.80 | 16.09 | 59.55 | 56.44 | 0.00 | 0.00 | 0.00 |
March | 25.49 | 7.40 | 18.09 | 28.60 | 48.16 | 0.00 | 0.00 | 0.00 |
April | 51.84 | 22.79 | 29.05 | 86.55 | 41.44 | 0.00 | 0.00 | 0.00 |
May | 42.31 | 12.74 | 29.57 | 64.91 | 36.82 | 0.00 | 0.00 | 0.00 |
June | 38.97 | 8.35 | 30.61 | 61.08 | 30.30 | 0.00 | 0.00 | 0.00 |
July | 42.08 | 12.02 | 30.06 | 72.11 | 28.44 | 0.00 | 0.00 | 0.00 |
August | 49.71 | 21.50 | 28.21 | 90.60 | 31.00 | 0.00 | 0.00 | 0.00 |
September | 59.88 | 34.78 | 25.10 | 106.36 | 38.64 | 0.00 | 0.00 | 0.00 |
October | 42.02 | 24.72 | 17.30 | 65.49 | 46.42 | 0.00 | 0.00 | 0.00 |
November | 30.19 | 18.62 | 11.56 | 41.91 | 53.51 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.66 | 8.41 | 31.56 | 65.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.19 | 18.85 | 21.34 | 62.91 | 44.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.06 | 7.40 | 8.41 | 28.60 | 28.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.88 | 34.78 | 30.61 | 106.36 | 65.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.72 | 48.22 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.98 | 46.46 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 24.07 | 39.52 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 73.14 | 33.35 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 55.22 | 29.36 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 51.98 | 24.12 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.67 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.86 | 25.39 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 89.47 | 31.32 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 55.44 | 37.26 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.18 | 43.95 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.46 | 54.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 53.02 | 36.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 24.07 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 89.47 | 54.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.72 | 48.22 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.98 | 46.46 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 24.07 | 39.52 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 73.14 | 33.35 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 55.22 | 29.36 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 51.98 | 24.12 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.67 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.86 | 25.39 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 89.47 | 31.32 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 55.44 | 37.26 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.18 | 43.95 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.46 | 54.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 53.02 | 36.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 24.07 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 89.47 | 54.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.72 | 48.22 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.98 | 46.46 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 24.07 | 39.52 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 73.14 | 33.35 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 55.22 | 29.36 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 51.98 | 24.12 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.67 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.86 | 25.39 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 89.47 | 31.32 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 55.44 | 37.26 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.18 | 43.95 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.46 | 54.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 53.02 | 36.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 24.07 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 89.47 | 54.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.72 | 48.22 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.98 | 46.46 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 24.07 | 39.52 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 73.14 | 33.35 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 55.22 | 29.36 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 51.98 | 24.12 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.67 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.86 | 25.39 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 89.47 | 31.32 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 55.44 | 37.26 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.18 | 43.95 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.46 | 54.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 53.02 | 36.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 24.07 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 89.47 | 54.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.67 | 22.75 | 11.92 | 47.56 | 57.29 | 0.00 | 0.00 | 0.00 |
February | 41.89 | 25.80 | 16.09 | 59.84 | 55.15 | 0.00 | 0.00 | 0.00 |
March | 25.49 | 7.40 | 18.09 | 28.88 | 46.96 | 0.00 | 0.00 | 0.00 |
April | 51.84 | 22.79 | 29.05 | 87.48 | 39.65 | 0.00 | 0.00 | 0.00 |
May | 42.31 | 12.74 | 29.57 | 66.10 | 34.87 | 0.00 | 0.00 | 0.00 |
June | 38.97 | 8.35 | 30.61 | 62.21 | 28.67 | 0.00 | 0.00 | 0.00 |
July | 42.08 | 12.02 | 30.06 | 72.55 | 27.39 | 0.00 | 0.00 | 0.00 |
August | 49.71 | 21.50 | 28.21 | 90.68 | 30.24 | 0.00 | 0.00 | 0.00 |
September | 59.88 | 34.78 | 25.10 | 106.97 | 37.29 | 0.00 | 0.00 | 0.00 |
October | 42.02 | 24.72 | 17.30 | 66.31 | 44.30 | 0.00 | 0.00 | 0.00 |
November | 30.19 | 18.62 | 11.56 | 42.12 | 52.20 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.66 | 8.41 | 31.69 | 64.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.19 | 18.85 | 21.34 | 63.44 | 43.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.06 | 7.40 | 8.41 | 28.88 | 27.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.88 | 34.78 | 30.61 | 106.97 | 64.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.67 | 22.75 | 11.92 | 47.56 | 57.29 | 0.00 | 0.00 | 0.00 |
February | 41.89 | 25.80 | 16.09 | 59.84 | 55.15 | 0.00 | 0.00 | 0.00 |
March | 25.49 | 7.40 | 18.09 | 28.88 | 46.96 | 0.00 | 0.00 | 0.00 |
April | 51.84 | 22.79 | 29.05 | 87.48 | 39.65 | 0.00 | 0.00 | 0.00 |
May | 42.31 | 12.74 | 29.57 | 66.10 | 34.87 | 0.00 | 0.00 | 0.00 |
June | 38.97 | 8.35 | 30.61 | 62.21 | 28.67 | 0.00 | 0.00 | 0.00 |
July | 42.08 | 12.02 | 30.06 | 72.55 | 27.39 | 0.00 | 0.00 | 0.00 |
August | 49.71 | 21.50 | 28.21 | 90.68 | 30.24 | 0.00 | 0.00 | 0.00 |
September | 59.88 | 34.78 | 25.10 | 106.97 | 37.29 | 0.00 | 0.00 | 0.00 |
October | 42.02 | 24.72 | 17.30 | 66.31 | 44.30 | 0.00 | 0.00 | 0.00 |
November | 30.19 | 18.62 | 11.56 | 42.12 | 52.20 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.66 | 8.41 | 31.69 | 64.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.19 | 18.85 | 21.34 | 63.44 | 43.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.06 | 7.40 | 8.41 | 28.88 | 27.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.88 | 34.78 | 30.61 | 106.97 | 64.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.59 | 48.40 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.82 | 46.62 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 23.93 | 39.61 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 72.91 | 33.37 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 54.94 | 29.41 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 51.62 | 24.24 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.43 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.69 | 25.34 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 89.09 | 31.49 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 55.21 | 37.36 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.07 | 44.07 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.36 | 54.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 52.81 | 36.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 23.93 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 89.09 | 54.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.59 | 48.40 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.82 | 46.62 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 23.93 | 39.61 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 72.91 | 33.37 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 54.94 | 29.41 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 51.62 | 24.24 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.43 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.69 | 25.34 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 89.09 | 31.49 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 55.21 | 37.36 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.07 | 44.07 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.36 | 54.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 52.81 | 36.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 23.93 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 89.09 | 54.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.67 | 22.75 | 11.92 | 47.41 | 57.48 | 0.00 | 0.00 | 0.00 |
February | 41.89 | 25.80 | 16.09 | 59.66 | 55.33 | 0.00 | 0.00 | 0.00 |
March | 25.49 | 7.40 | 18.09 | 28.72 | 47.06 | 0.00 | 0.00 | 0.00 |
April | 51.84 | 22.79 | 29.05 | 87.23 | 39.67 | 0.00 | 0.00 | 0.00 |
May | 42.31 | 12.74 | 29.57 | 65.79 | 34.93 | 0.00 | 0.00 | 0.00 |
June | 38.97 | 8.35 | 30.61 | 61.79 | 28.80 | 0.00 | 0.00 | 0.00 |
July | 42.08 | 12.02 | 30.06 | 72.28 | 27.38 | 0.00 | 0.00 | 0.00 |
August | 49.71 | 21.50 | 28.21 | 90.49 | 30.17 | 0.00 | 0.00 | 0.00 |
September | 59.88 | 34.78 | 25.10 | 106.55 | 37.48 | 0.00 | 0.00 | 0.00 |
October | 42.02 | 24.72 | 17.30 | 66.05 | 44.41 | 0.00 | 0.00 | 0.00 |
November | 30.19 | 18.62 | 11.56 | 42.00 | 52.33 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.66 | 8.41 | 31.59 | 64.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.19 | 18.85 | 21.34 | 63.21 | 43.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.06 | 7.40 | 8.41 | 28.72 | 27.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.88 | 34.78 | 30.61 | 106.55 | 64.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.61 | 48.26 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.85 | 46.48 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 23.97 | 39.47 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 73.00 | 33.20 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 55.06 | 29.22 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 51.76 | 24.06 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.52 | 22.89 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.74 | 25.23 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 89.17 | 31.35 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 55.29 | 37.16 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.10 | 43.92 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.38 | 54.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 52.88 | 36.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 23.97 | 22.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 89.17 | 54.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.61 | 48.26 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.85 | 46.48 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 23.97 | 39.47 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 73.00 | 33.20 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 55.06 | 29.22 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 51.76 | 24.06 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.52 | 22.89 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.74 | 25.23 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 89.17 | 31.35 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 55.29 | 37.16 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.10 | 43.92 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.38 | 54.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 52.88 | 36.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 23.97 | 22.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 89.17 | 54.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.67 | 22.75 | 11.92 | 47.44 | 57.32 | 0.00 | 0.00 | 0.00 |
February | 41.89 | 25.80 | 16.09 | 59.71 | 55.17 | 0.00 | 0.00 | 0.00 |
March | 25.49 | 7.40 | 18.09 | 28.76 | 46.90 | 0.00 | 0.00 | 0.00 |
April | 51.84 | 22.79 | 29.05 | 87.33 | 39.47 | 0.00 | 0.00 | 0.00 |
May | 42.31 | 12.74 | 29.57 | 65.93 | 34.70 | 0.00 | 0.00 | 0.00 |
June | 38.97 | 8.35 | 30.61 | 61.97 | 28.58 | 0.00 | 0.00 | 0.00 |
July | 42.08 | 12.02 | 30.06 | 72.40 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 49.71 | 21.50 | 28.21 | 90.55 | 30.05 | 0.00 | 0.00 | 0.00 |
September | 59.88 | 34.78 | 25.10 | 106.64 | 37.32 | 0.00 | 0.00 | 0.00 |
October | 42.02 | 24.72 | 17.30 | 66.15 | 44.17 | 0.00 | 0.00 | 0.00 |
November | 30.19 | 18.62 | 11.56 | 42.03 | 52.15 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.66 | 8.41 | 31.61 | 64.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.19 | 18.85 | 21.34 | 63.29 | 43.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.06 | 7.40 | 8.41 | 28.76 | 27.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.88 | 34.78 | 30.61 | 106.64 | 64.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.71 | 47.68 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.99 | 45.88 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 24.10 | 38.91 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 73.24 | 32.63 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 55.42 | 28.56 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 52.27 | 23.39 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.84 | 22.42 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.93 | 24.85 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 89.51 | 30.75 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 55.53 | 36.47 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.19 | 43.35 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.45 | 53.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 53.10 | 35.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 24.10 | 22.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 89.51 | 53.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 39.71 | 47.68 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 49.99 | 45.88 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 24.10 | 38.91 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 73.24 | 32.63 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 55.42 | 28.56 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 52.27 | 23.39 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 60.84 | 22.42 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 75.93 | 24.85 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 89.51 | 30.75 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 55.53 | 36.47 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.19 | 43.35 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.45 | 53.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 53.10 | 35.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 24.10 | 22.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 89.51 | 53.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.67 | 22.75 | 11.92 | 47.57 | 56.63 | 0.00 | 0.00 | 0.00 |
February | 41.89 | 25.80 | 16.09 | 59.87 | 54.45 | 0.00 | 0.00 | 0.00 |
March | 25.49 | 7.40 | 18.09 | 28.92 | 46.23 | 0.00 | 0.00 | 0.00 |
April | 51.84 | 22.79 | 29.05 | 87.63 | 38.79 | 0.00 | 0.00 | 0.00 |
May | 42.31 | 12.74 | 29.57 | 66.36 | 33.92 | 0.00 | 0.00 | 0.00 |
June | 38.97 | 8.35 | 30.61 | 62.57 | 27.80 | 0.00 | 0.00 | 0.00 |
July | 42.08 | 12.02 | 30.06 | 72.78 | 26.67 | 0.00 | 0.00 | 0.00 |
August | 49.71 | 21.50 | 28.21 | 90.78 | 29.59 | 0.00 | 0.00 | 0.00 |
September | 59.88 | 34.78 | 25.10 | 107.04 | 36.60 | 0.00 | 0.00 | 0.00 |
October | 42.02 | 24.72 | 17.30 | 66.44 | 43.35 | 0.00 | 0.00 | 0.00 |
November | 30.19 | 18.62 | 11.56 | 42.14 | 51.48 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.66 | 8.41 | 31.69 | 63.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.19 | 18.85 | 21.34 | 63.56 | 42.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.06 | 7.40 | 8.41 | 28.92 | 26.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.88 | 34.78 | 30.61 | 107.04 | 63.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 40.10 | 45.44 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 50.48 | 43.52 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 24.58 | 36.80 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 73.76 | 30.83 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 56.16 | 26.54 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 53.27 | 21.59 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 61.55 | 20.96 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 76.44 | 23.46 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 90.19 | 29.01 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 56.02 | 34.51 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.50 | 41.31 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.71 | 51.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 53.65 | 33.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 24.58 | 20.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 90.19 | 51.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.00 | 19.03 | 9.97 | 40.10 | 45.44 | 0.00 | 0.00 | 0.00 |
February | 35.04 | 21.58 | 13.46 | 50.48 | 43.52 | 0.00 | 0.00 | 0.00 |
March | 21.32 | 6.19 | 15.13 | 24.58 | 36.80 | 0.00 | 0.00 | 0.00 |
April | 43.36 | 19.07 | 24.30 | 73.76 | 30.83 | 0.00 | 0.00 | 0.00 |
May | 35.39 | 10.65 | 24.73 | 56.16 | 26.54 | 0.00 | 0.00 | 0.00 |
June | 32.59 | 6.99 | 25.60 | 53.27 | 21.59 | 0.00 | 0.00 | 0.00 |
July | 35.20 | 10.06 | 25.14 | 61.55 | 20.96 | 0.00 | 0.00 | 0.00 |
August | 41.57 | 17.98 | 23.60 | 76.44 | 23.46 | 0.00 | 0.00 | 0.00 |
September | 50.08 | 29.09 | 20.99 | 90.19 | 29.01 | 0.00 | 0.00 | 0.00 |
October | 35.15 | 20.68 | 14.47 | 56.02 | 34.51 | 0.00 | 0.00 | 0.00 |
November | 25.25 | 15.58 | 9.67 | 35.50 | 41.31 | 0.00 | 0.00 | 0.00 |
December | 20.13 | 13.09 | 7.03 | 26.71 | 51.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.62 | 15.76 | 17.85 | 53.65 | 33.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 6.19 | 7.03 | 24.58 | 20.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.08 | 29.09 | 25.60 | 90.19 | 51.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.67 | 22.75 | 11.92 | 48.03 | 53.96 | 0.00 | 0.00 | 0.00 |
February | 41.89 | 25.80 | 16.09 | 60.46 | 51.65 | 0.00 | 0.00 | 0.00 |
March | 25.49 | 7.40 | 18.09 | 29.51 | 43.70 | 0.00 | 0.00 | 0.00 |
April | 51.84 | 22.79 | 29.05 | 88.25 | 36.65 | 0.00 | 0.00 | 0.00 |
May | 42.31 | 12.74 | 29.57 | 67.25 | 31.53 | 0.00 | 0.00 | 0.00 |
June | 38.97 | 8.35 | 30.61 | 63.77 | 25.68 | 0.00 | 0.00 | 0.00 |
July | 42.08 | 12.02 | 30.06 | 73.62 | 24.94 | 0.00 | 0.00 | 0.00 |
August | 49.71 | 21.50 | 28.21 | 91.39 | 27.95 | 0.00 | 0.00 | 0.00 |
September | 59.88 | 34.78 | 25.10 | 107.86 | 34.54 | 0.00 | 0.00 | 0.00 |
October | 42.02 | 24.72 | 17.30 | 67.02 | 41.03 | 0.00 | 0.00 | 0.00 |
November | 30.19 | 18.62 | 11.56 | 42.52 | 49.05 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.66 | 8.41 | 32.01 | 60.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.19 | 18.85 | 21.34 | 64.22 | 40.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.06 | 7.40 | 8.41 | 29.51 | 24.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.88 | 34.78 | 30.61 | 107.86 | 60.76 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.106273E+09 | 0.130992E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120889E+09 | 0.113630E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 64552868.05 | 0.106686E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.189691E+09 | 86843856.74 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.147857E+09 | 78987667.59 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.134712E+09 | 62700761.77 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.163001E+09 | 61182329.31 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.203869E+09 | 66990336.95 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.232025E+09 | 81039410.18 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.148353E+09 | 0.100661E+09 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 91081032.18 | 0.115550E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70809553.71 | 0.146800E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.167311E+10 | 0.115206E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 64552868.05 | 61182329.31 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.232025E+09 | 0.146800E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.106273E+09 | 0.130992E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120889E+09 | 0.113630E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 64552868.05 | 0.106686E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.189691E+09 | 86843856.74 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.147857E+09 | 78987667.59 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.134712E+09 | 62700761.77 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.163001E+09 | 61182329.31 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.203869E+09 | 66990336.95 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.232025E+09 | 81039410.18 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.148353E+09 | 0.100661E+09 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 91081032.18 | 0.115550E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70809553.71 | 0.146800E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.167311E+10 | 0.115206E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 64552868.05 | 61182329.31 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.232025E+09 | 0.146800E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.106273E+09 | 0.130992E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120889E+09 | 0.113630E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 64552868.05 | 0.106686E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.189691E+09 | 86843856.74 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.147857E+09 | 78987667.59 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.134712E+09 | 62700761.77 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.163001E+09 | 61182329.31 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.203869E+09 | 66990336.95 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.232025E+09 | 81039410.18 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.148353E+09 | 0.100661E+09 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 91081032.18 | 0.115550E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70809553.71 | 0.146800E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.167311E+10 | 0.115206E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 64552868.05 | 61182329.31 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.232025E+09 | 0.146800E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.106273E+09 | 0.130992E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120889E+09 | 0.113630E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 64552868.05 | 0.106686E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.189691E+09 | 86843856.74 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.147857E+09 | 78987667.59 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.134712E+09 | 62700761.77 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.163001E+09 | 61182329.31 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.203869E+09 | 66990336.95 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.232025E+09 | 81039410.18 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.148353E+09 | 0.100661E+09 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 91081032.18 | 0.115550E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70809553.71 | 0.146800E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.167311E+10 | 0.115206E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 64552868.05 | 61182329.31 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.232025E+09 | 0.146800E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93382341.62 | 61275006.48 | 32107335.14 | 0.127933E+09 | 0.156463E+09 |
February | 0.101908E+09 | 62760518.38 | 39147177.37 | 0.145529E+09 | 0.135636E+09 |
March | 68654452.07 | 19923602.45 | 48730849.63 | 77863021.22 | 0.127471E+09 |
April | 0.135119E+09 | 59409212.62 | 75709647.14 | 0.228112E+09 | 0.103841E+09 |
May | 0.113938E+09 | 34304606.09 | 79633282.44 | 0.177949E+09 | 94358337.63 |
June | 0.101554E+09 | 21770957.12 | 79783263.99 | 0.162079E+09 | 74947163.77 |
July | 0.113329E+09 | 32383885.60 | 80945474.84 | 0.195985E+09 | 73186476.20 |
August | 0.133865E+09 | 57889017.19 | 75975807.41 | 0.245013E+09 | 80245780.24 |
September | 0.156060E+09 | 90647657.60 | 65412045.00 | 0.278926E+09 | 97012775.05 |
October | 0.113167E+09 | 66575933.53 | 46591486.22 | 0.178413E+09 | 0.120345E+09 |
November | 78672283.80 | 48540884.42 | 30131399.38 | 0.109645E+09 | 0.138009E+09 |
December | 64799527.83 | 42161660.61 | 22637867.22 | 85292279.31 | 0.175134E+09 |
Annual Sum or Average | 0.127445E+10 | 0.597643E+09 | 0.676806E+09 | 0.201274E+10 | 0.137665E+10 |
Minimum of Months | 64799527.83 | 19923602.45 | 22637867.22 | 77863021.22 | 73186476.20 |
Maximum of Months | 0.156060E+09 | 90647657.60 | 80945474.84 | 0.278926E+09 | 0.175134E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93382341.62 | 61275006.48 | 32107335.14 | 0.127933E+09 | 0.156463E+09 |
February | 0.101908E+09 | 62760518.38 | 39147177.37 | 0.145529E+09 | 0.135636E+09 |
March | 68654452.07 | 19923602.45 | 48730849.63 | 77863021.22 | 0.127471E+09 |
April | 0.135119E+09 | 59409212.62 | 75709647.14 | 0.228112E+09 | 0.103841E+09 |
May | 0.113938E+09 | 34304606.09 | 79633282.44 | 0.177949E+09 | 94358337.63 |
June | 0.101554E+09 | 21770957.12 | 79783263.99 | 0.162079E+09 | 74947163.77 |
July | 0.113329E+09 | 32383885.60 | 80945474.84 | 0.195985E+09 | 73186476.20 |
August | 0.133865E+09 | 57889017.19 | 75975807.41 | 0.245013E+09 | 80245780.24 |
September | 0.156060E+09 | 90647657.60 | 65412045.00 | 0.278926E+09 | 97012775.05 |
October | 0.113167E+09 | 66575933.53 | 46591486.22 | 0.178413E+09 | 0.120345E+09 |
November | 78672283.80 | 48540884.42 | 30131399.38 | 0.109645E+09 | 0.138009E+09 |
December | 64799527.83 | 42161660.61 | 22637867.22 | 85292279.31 | 0.175134E+09 |
Annual Sum or Average | 0.127445E+10 | 0.597643E+09 | 0.676806E+09 | 0.201274E+10 | 0.137665E+10 |
Minimum of Months | 64799527.83 | 19923602.45 | 22637867.22 | 77863021.22 | 73186476.20 |
Maximum of Months | 0.156060E+09 | 90647657.60 | 80945474.84 | 0.278926E+09 | 0.175134E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.105100E+09 | 0.136919E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.119588E+09 | 0.119051E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 62993741.11 | 0.112718E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.185842E+09 | 94057565.04 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.143385E+09 | 86424374.56 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.131471E+09 | 66488573.37 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.161228E+09 | 63460284.21 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.202840E+09 | 68646113.03 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.230006E+09 | 84128539.32 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.145234E+09 | 0.109307E+09 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 89990905.87 | 0.121806E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 69997094.72 | 0.153265E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.164768E+10 | 0.121627E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 62993741.11 | 63460284.21 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.230006E+09 | 0.153265E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.105100E+09 | 0.136919E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.119588E+09 | 0.119051E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 62993741.11 | 0.112718E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.185842E+09 | 94057565.04 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.143385E+09 | 86424374.56 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.131471E+09 | 66488573.37 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.161228E+09 | 63460284.21 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.202840E+09 | 68646113.03 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.230006E+09 | 84128539.32 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.145234E+09 | 0.109307E+09 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 89990905.87 | 0.121806E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 69997094.72 | 0.153265E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.164768E+10 | 0.121627E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 62993741.11 | 63460284.21 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.230006E+09 | 0.153265E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93382341.62 | 61275006.48 | 32107335.14 | 0.126527E+09 | 0.163536E+09 |
February | 0.101908E+09 | 62760518.38 | 39147177.37 | 0.143975E+09 | 0.142082E+09 |
March | 68654452.07 | 19923602.45 | 48730849.63 | 75987783.59 | 0.134662E+09 |
April | 0.135119E+09 | 59409212.62 | 75709647.14 | 0.223543E+09 | 0.112407E+09 |
May | 0.113938E+09 | 34304606.09 | 79633282.44 | 0.172645E+09 | 0.103151E+09 |
June | 0.101554E+09 | 21770957.12 | 79783263.99 | 0.158238E+09 | 79433434.52 |
July | 0.113329E+09 | 32383885.60 | 80945474.84 | 0.193890E+09 | 75884039.62 |
August | 0.133865E+09 | 57889017.19 | 75975807.41 | 0.243806E+09 | 82219206.47 |
September | 0.156060E+09 | 90647657.60 | 65412045.00 | 0.276551E+09 | 0.100683E+09 |
October | 0.113167E+09 | 66575933.53 | 46591486.22 | 0.174714E+09 | 0.130608E+09 |
November | 78672283.80 | 48540884.42 | 30131399.38 | 0.108348E+09 | 0.145441E+09 |
December | 64799527.83 | 42161660.61 | 22637867.22 | 84323020.85 | 0.182828E+09 |
Annual Sum or Average | 0.127445E+10 | 0.597643E+09 | 0.676806E+09 | 0.198255E+10 | 0.145293E+10 |
Minimum of Months | 64799527.83 | 19923602.45 | 22637867.22 | 75987783.59 | 75884039.62 |
Maximum of Months | 0.156060E+09 | 90647657.60 | 80945474.84 | 0.276551E+09 | 0.182828E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.105426E+09 | 0.134804E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.119864E+09 | 0.117317E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 63253033.86 | 0.111040E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.185828E+09 | 93702918.81 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.143204E+09 | 86576384.82 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.131127E+09 | 68064833.35 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.160842E+09 | 65348025.31 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.202663E+09 | 70639436.12 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.229925E+09 | 85749191.50 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.145306E+09 | 0.108697E+09 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 90263143.55 | 0.119681E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70255346.85 | 0.151131E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.164796E+10 | 0.121275E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 63253033.86 | 65348025.31 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.229925E+09 | 0.151131E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.105426E+09 | 0.134804E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.119864E+09 | 0.117317E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 63253033.86 | 0.111040E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.185828E+09 | 93702918.81 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.143204E+09 | 86576384.82 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.131127E+09 | 68064833.35 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.160842E+09 | 65348025.31 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.202663E+09 | 70639436.12 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.229925E+09 | 85749191.50 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.145306E+09 | 0.108697E+09 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 90263143.55 | 0.119681E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70255346.85 | 0.151131E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.164796E+10 | 0.121275E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 63253033.86 | 65348025.31 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.229925E+09 | 0.151131E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92872055.60 | 60940170.38 | 31931885.22 | 0.126232E+09 | 0.160145E+09 |
February | 0.101351E+09 | 62417564.72 | 38933258.36 | 0.143525E+09 | 0.139268E+09 |
March | 68279291.13 | 19814730.30 | 48464560.83 | 75889469.51 | 0.131952E+09 |
April | 0.134381E+09 | 59084572.11 | 75295933.22 | 0.222309E+09 | 0.111384E+09 |
May | 0.113315E+09 | 34117149.23 | 79198127.89 | 0.171486E+09 | 0.102785E+09 |
June | 0.100999E+09 | 21651990.14 | 79347289.87 | 0.156963E+09 | 80853756.05 |
July | 0.112710E+09 | 32206924.48 | 80503149.84 | 0.192374E+09 | 77688238.87 |
August | 0.133133E+09 | 57572683.76 | 75560639.06 | 0.242266E+09 | 84109996.86 |
September | 0.155207E+09 | 90152315.21 | 65054602.13 | 0.274944E+09 | 0.102039E+09 |
October | 0.112549E+09 | 66212130.61 | 46336887.93 | 0.173847E+09 | 0.129193E+09 |
November | 78242380.61 | 48275633.68 | 29966746.92 | 0.108085E+09 | 0.142152E+09 |
December | 64445432.04 | 41931269.02 | 22514163.03 | 84174507.82 | 0.179325E+09 |
Annual Sum or Average | 0.126748E+10 | 0.594377E+09 | 0.673107E+09 | 0.197209E+10 | 0.144089E+10 |
Minimum of Months | 64445432.04 | 19814730.30 | 22514163.03 | 75889469.51 | 77688238.87 |
Maximum of Months | 0.155207E+09 | 90152315.21 | 80503149.84 | 0.274944E+09 | 0.179325E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.105635E+09 | 0.133358E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120057E+09 | 0.116134E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 63495631.93 | 0.109799E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.186402E+09 | 92356644.92 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.143818E+09 | 85281395.36 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.131367E+09 | 67512277.40 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.160975E+09 | 64989508.69 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.202729E+09 | 70384149.97 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.230062E+09 | 85265276.81 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.145717E+09 | 0.107091E+09 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 90462235.71 | 0.118200E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70388574.86 | 0.149688E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.165111E+10 | 0.120006E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 63495631.93 | 64989508.69 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.230062E+09 | 0.149688E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.105635E+09 | 0.133358E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120057E+09 | 0.116134E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 63495631.93 | 0.109799E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.186402E+09 | 92356644.92 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.143818E+09 | 85281395.36 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.131367E+09 | 67512277.40 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.160975E+09 | 64989508.69 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.202729E+09 | 70384149.97 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.230062E+09 | 85265276.81 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.145717E+09 | 0.107091E+09 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 90462235.71 | 0.118200E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70388574.86 | 0.149688E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.165111E+10 | 0.120006E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 63495631.93 | 64989508.69 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.230062E+09 | 0.149688E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92872055.60 | 60940170.38 | 31931885.22 | 0.126487E+09 | 0.158421E+09 |
February | 0.101351E+09 | 62417564.72 | 38933258.36 | 0.143760E+09 | 0.137859E+09 |
March | 68279291.13 | 19814730.30 | 48464560.83 | 76183402.08 | 0.130472E+09 |
April | 0.134381E+09 | 59084572.11 | 75295933.22 | 0.222996E+09 | 0.109783E+09 |
May | 0.113315E+09 | 34117149.23 | 79198127.89 | 0.172222E+09 | 0.101252E+09 |
June | 0.100999E+09 | 21651990.14 | 79347289.87 | 0.157251E+09 | 80198291.27 |
July | 0.112710E+09 | 32206924.48 | 80503149.84 | 0.192534E+09 | 77262804.32 |
August | 0.133133E+09 | 57572683.76 | 75560639.06 | 0.242346E+09 | 83807006.33 |
September | 0.155207E+09 | 90152315.21 | 65054602.13 | 0.275108E+09 | 0.101465E+09 |
October | 0.112549E+09 | 66212130.61 | 46336887.93 | 0.174339E+09 | 0.127286E+09 |
November | 78242380.61 | 48275633.68 | 29966746.92 | 0.108325E+09 | 0.140388E+09 |
December | 64445432.04 | 41931269.02 | 22514163.03 | 84336049.57 | 0.177606E+09 |
Annual Sum or Average | 0.126748E+10 | 0.594377E+09 | 0.673107E+09 | 0.197589E+10 | 0.142580E+10 |
Minimum of Months | 64445432.04 | 19814730.30 | 22514163.03 | 76183402.08 | 77262804.32 |
Maximum of Months | 0.155207E+09 | 90152315.21 | 80503149.84 | 0.275108E+09 | 0.177606E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.105885E+09 | 0.132052E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120313E+09 | 0.115019E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 63830411.75 | 0.108565E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.187532E+09 | 90368365.19 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.145195E+09 | 83045574.21 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.132261E+09 | 66104712.50 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.161471E+09 | 64059694.20 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.202989E+09 | 69725104.99 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.230536E+09 | 84159083.55 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.146602E+09 | 0.104602E+09 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 90717131.68 | 0.116787E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70559118.75 | 0.148302E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.165789E+10 | 0.118279E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 63830411.75 | 64059694.20 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.230536E+09 | 0.148302E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.105885E+09 | 0.132052E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120313E+09 | 0.115019E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 63830411.75 | 0.108565E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.187532E+09 | 90368365.19 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.145195E+09 | 83045574.21 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.132261E+09 | 66104712.50 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.161471E+09 | 64059694.20 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.202989E+09 | 69725104.99 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.230536E+09 | 84159083.55 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.146602E+09 | 0.104602E+09 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 90717131.68 | 0.116787E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70559118.75 | 0.148302E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.165789E+10 | 0.118279E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 63830411.75 | 64059694.20 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.230536E+09 | 0.148302E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92872055.60 | 60940170.38 | 31931885.22 | 0.126791E+09 | 0.156863E+09 |
February | 0.101351E+09 | 62417564.72 | 38933258.36 | 0.144071E+09 | 0.136532E+09 |
March | 68279291.13 | 19814730.30 | 48464560.83 | 76589025.65 | 0.129002E+09 |
April | 0.134381E+09 | 59084572.11 | 75295933.22 | 0.224346E+09 | 0.107423E+09 |
May | 0.113315E+09 | 34117149.23 | 79198127.89 | 0.173864E+09 | 98605988.85 |
June | 0.100999E+09 | 21651990.14 | 79347289.87 | 0.158324E+09 | 78534656.06 |
July | 0.112710E+09 | 32206924.48 | 80503149.84 | 0.193131E+09 | 76164565.25 |
August | 0.133133E+09 | 57572683.76 | 75560639.06 | 0.242661E+09 | 83027651.80 |
September | 0.155207E+09 | 90152315.21 | 65054602.13 | 0.275680E+09 | 0.100155E+09 |
October | 0.112549E+09 | 66212130.61 | 46336887.93 | 0.175396E+09 | 0.124333E+09 |
November | 78242380.61 | 48275633.68 | 29966746.92 | 0.108633E+09 | 0.138706E+09 |
December | 64445432.04 | 41931269.02 | 22514163.03 | 84543418.43 | 0.175954E+09 |
Annual Sum or Average | 0.126748E+10 | 0.594377E+09 | 0.673107E+09 | 0.198403E+10 | 0.140530E+10 |
Minimum of Months | 64445432.04 | 19814730.30 | 22514163.03 | 76589025.65 | 76164565.25 |
Maximum of Months | 0.155207E+09 | 90152315.21 | 80503149.84 | 0.275680E+09 | 0.175954E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.106390E+09 | 0.129165E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120909E+09 | 0.112392E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 64477035.10 | 0.105859E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.189583E+09 | 86430778.05 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.147905E+09 | 78624988.98 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.134743E+09 | 62513601.40 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.162492E+09 | 61672876.90 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.203181E+09 | 67999992.06 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.231900E+09 | 81187852.45 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.148496E+09 | 99801514.98 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 91178900.05 | 0.113906E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70858451.77 | 0.144956E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.167211E+10 | 0.114451E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 64477035.10 | 61672876.90 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.231900E+09 | 0.144956E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.106390E+09 | 0.129165E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120909E+09 | 0.112392E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 64477035.10 | 0.105859E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.189583E+09 | 86430778.05 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.147905E+09 | 78624988.98 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.134743E+09 | 62513601.40 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.162492E+09 | 61672876.90 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.203181E+09 | 67999992.06 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.231900E+09 | 81187852.45 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.148496E+09 | 99801514.98 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 91178900.05 | 0.113906E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70858451.77 | 0.144956E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.167211E+10 | 0.114451E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 64477035.10 | 61672876.90 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.231900E+09 | 0.144956E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.106390E+09 | 0.129165E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120909E+09 | 0.112392E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 64477035.10 | 0.105859E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.189583E+09 | 86430778.05 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.147905E+09 | 78624988.98 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.134743E+09 | 62513601.40 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.162492E+09 | 61672876.90 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.203181E+09 | 67999992.06 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.231900E+09 | 81187852.45 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.148496E+09 | 99801514.98 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 91178900.05 | 0.113906E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70858451.77 | 0.144956E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.167211E+10 | 0.114451E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 64477035.10 | 61672876.90 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.231900E+09 | 0.144956E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.106390E+09 | 0.129165E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120909E+09 | 0.112392E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 64477035.10 | 0.105859E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.189583E+09 | 86430778.05 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.147905E+09 | 78624988.98 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.134743E+09 | 62513601.40 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.162492E+09 | 61672876.90 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.203181E+09 | 67999992.06 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.231900E+09 | 81187852.45 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.148496E+09 | 99801514.98 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 91178900.05 | 0.113906E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70858451.77 | 0.144956E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.167211E+10 | 0.114451E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 64477035.10 | 61672876.90 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.231900E+09 | 0.144956E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92872055.60 | 60940170.38 | 31931885.22 | 0.127386E+09 | 0.153437E+09 |
February | 0.101351E+09 | 62417564.72 | 38933258.36 | 0.144766E+09 | 0.133427E+09 |
March | 68279291.13 | 19814730.30 | 48464560.83 | 77357852.72 | 0.125787E+09 |
April | 0.134381E+09 | 59084572.11 | 75295933.22 | 0.226750E+09 | 0.102765E+09 |
May | 0.113315E+09 | 34117149.23 | 79198127.89 | 0.177041E+09 | 93397513.22 |
June | 0.100999E+09 | 21651990.14 | 79347289.87 | 0.161240E+09 | 74302476.03 |
July | 0.112710E+09 | 32206924.48 | 80503149.84 | 0.194321E+09 | 73349684.18 |
August | 0.133133E+09 | 57572683.76 | 75560639.06 | 0.242867E+09 | 80985494.91 |
September | 0.155207E+09 | 90152315.21 | 65054602.13 | 0.277262E+09 | 96642910.48 |
October | 0.112549E+09 | 66212130.61 | 46336887.93 | 0.177618E+09 | 0.118650E+09 |
November | 78242380.61 | 48275633.68 | 29966746.92 | 0.109172E+09 | 0.135290E+09 |
December | 64445432.04 | 41931269.02 | 22514163.03 | 84890847.57 | 0.172002E+09 |
Annual Sum or Average | 0.126748E+10 | 0.594377E+09 | 0.673107E+09 | 0.200067E+10 | 0.136004E+10 |
Minimum of Months | 64445432.04 | 19814730.30 | 22514163.03 | 77357852.72 | 73349684.18 |
Maximum of Months | 0.155207E+09 | 90152315.21 | 80503149.84 | 0.277262E+09 | 0.172002E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92872055.60 | 60940170.38 | 31931885.22 | 0.127386E+09 | 0.153437E+09 |
February | 0.101351E+09 | 62417564.72 | 38933258.36 | 0.144766E+09 | 0.133427E+09 |
March | 68279291.13 | 19814730.30 | 48464560.83 | 77357852.72 | 0.125787E+09 |
April | 0.134381E+09 | 59084572.11 | 75295933.22 | 0.226750E+09 | 0.102765E+09 |
May | 0.113315E+09 | 34117149.23 | 79198127.89 | 0.177041E+09 | 93397513.22 |
June | 0.100999E+09 | 21651990.14 | 79347289.87 | 0.161240E+09 | 74302476.03 |
July | 0.112710E+09 | 32206924.48 | 80503149.84 | 0.194321E+09 | 73349684.18 |
August | 0.133133E+09 | 57572683.76 | 75560639.06 | 0.242867E+09 | 80985494.91 |
September | 0.155207E+09 | 90152315.21 | 65054602.13 | 0.277262E+09 | 96642910.48 |
October | 0.112549E+09 | 66212130.61 | 46336887.93 | 0.177618E+09 | 0.118650E+09 |
November | 78242380.61 | 48275633.68 | 29966746.92 | 0.109172E+09 | 0.135290E+09 |
December | 64445432.04 | 41931269.02 | 22514163.03 | 84890847.57 | 0.172002E+09 |
Annual Sum or Average | 0.126748E+10 | 0.594377E+09 | 0.673107E+09 | 0.200067E+10 | 0.136004E+10 |
Minimum of Months | 64445432.04 | 19814730.30 | 22514163.03 | 77357852.72 | 73349684.18 |
Maximum of Months | 0.155207E+09 | 90152315.21 | 80503149.84 | 0.277262E+09 | 0.172002E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.106030E+09 | 0.129622E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120524E+09 | 0.112784E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 64090964.66 | 0.106093E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.188981E+09 | 86488242.01 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.147158E+09 | 78768567.47 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.133790E+09 | 62818763.22 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.161844E+09 | 61672683.52 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.202716E+09 | 67857879.11 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.230930E+09 | 81621377.45 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.147873E+09 | 0.100076E+09 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 90903785.82 | 0.114220E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70605173.88 | 0.145707E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.166545E+10 | 0.114773E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 64090964.66 | 61672683.52 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.230930E+09 | 0.145707E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.106030E+09 | 0.129622E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120524E+09 | 0.112784E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 64090964.66 | 0.106093E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.188981E+09 | 86488242.01 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.147158E+09 | 78768567.47 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.133790E+09 | 62818763.22 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.161844E+09 | 61672683.52 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.202716E+09 | 67857879.11 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.230930E+09 | 81621377.45 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.147873E+09 | 0.100076E+09 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 90903785.82 | 0.114220E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70605173.88 | 0.145707E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.166545E+10 | 0.114773E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 64090964.66 | 61672683.52 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.230930E+09 | 0.145707E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92872055.60 | 60940170.38 | 31931885.22 | 0.126982E+09 | 0.153957E+09 |
February | 0.101351E+09 | 62417564.72 | 38933258.36 | 0.144340E+09 | 0.133863E+09 |
March | 68279291.13 | 19814730.30 | 48464560.83 | 76921744.17 | 0.126049E+09 |
April | 0.134381E+09 | 59084572.11 | 75295933.22 | 0.226090E+09 | 0.102816E+09 |
May | 0.113315E+09 | 34117149.23 | 79198127.89 | 0.176212E+09 | 93544870.80 |
June | 0.100999E+09 | 21651990.14 | 79347289.87 | 0.160162E+09 | 74646733.57 |
July | 0.112710E+09 | 32206924.48 | 80503149.84 | 0.193601E+09 | 73339555.09 |
August | 0.133133E+09 | 57572683.76 | 75560639.06 | 0.242361E+09 | 80814439.16 |
September | 0.155207E+09 | 90152315.21 | 65054602.13 | 0.276170E+09 | 97145063.78 |
October | 0.112549E+09 | 66212130.61 | 46336887.93 | 0.176920E+09 | 0.118955E+09 |
November | 78242380.61 | 48275633.68 | 29966746.92 | 0.108869E+09 | 0.135640E+09 |
December | 64445432.04 | 41931269.02 | 22514163.03 | 84608923.09 | 0.172858E+09 |
Annual Sum or Average | 0.126748E+10 | 0.594377E+09 | 0.673107E+09 | 0.199324E+10 | 0.136363E+10 |
Minimum of Months | 64445432.04 | 19814730.30 | 22514163.03 | 76921744.17 | 73339555.09 |
Maximum of Months | 0.155207E+09 | 90152315.21 | 80503149.84 | 0.276170E+09 | 0.172858E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.106101E+09 | 0.129270E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120607E+09 | 0.112450E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 64189346.10 | 0.105728E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.189208E+09 | 86058169.29 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.147473E+09 | 78251796.76 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.134169E+09 | 62350600.95 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.162099E+09 | 61320862.37 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.202865E+09 | 67576562.18 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.231136E+09 | 81267883.44 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.148076E+09 | 99531453.74 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 90973726.90 | 0.113836E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70648662.95 | 0.145381E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.166755E+10 | 0.114302E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 64189346.10 | 61320862.37 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.231136E+09 | 0.145381E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.106101E+09 | 0.129270E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120607E+09 | 0.112450E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 64189346.10 | 0.105728E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.189208E+09 | 86058169.29 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.147473E+09 | 78251796.76 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.134169E+09 | 62350600.95 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.162099E+09 | 61320862.37 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.202865E+09 | 67576562.18 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.231136E+09 | 81267883.44 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.148076E+09 | 99531453.74 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 90973726.90 | 0.113836E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70648662.95 | 0.145381E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.166755E+10 | 0.114302E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 64189346.10 | 61320862.37 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.231136E+09 | 0.145381E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92872055.60 | 60940170.38 | 31931885.22 | 0.127069E+09 | 0.153536E+09 |
February | 0.101351E+09 | 62417564.72 | 38933258.36 | 0.144442E+09 | 0.133465E+09 |
March | 68279291.13 | 19814730.30 | 48464560.83 | 77041623.65 | 0.125612E+09 |
April | 0.134381E+09 | 59084572.11 | 75295933.22 | 0.226362E+09 | 0.102304E+09 |
May | 0.113315E+09 | 34117149.23 | 79198127.89 | 0.176590E+09 | 92931904.25 |
June | 0.100999E+09 | 21651990.14 | 79347289.87 | 0.160616E+09 | 74092265.93 |
July | 0.112710E+09 | 32206924.48 | 80503149.84 | 0.193907E+09 | 72923003.50 |
August | 0.133133E+09 | 57572683.76 | 75560639.06 | 0.242542E+09 | 80481018.40 |
September | 0.155207E+09 | 90152315.21 | 65054602.13 | 0.276416E+09 | 96725108.92 |
October | 0.112549E+09 | 66212130.61 | 46336887.93 | 0.177163E+09 | 0.118308E+09 |
November | 78242380.61 | 48275633.68 | 29966746.92 | 0.108953E+09 | 0.135180E+09 |
December | 64445432.04 | 41931269.02 | 22514163.03 | 84661684.49 | 0.172469E+09 |
Annual Sum or Average | 0.126748E+10 | 0.594377E+09 | 0.673107E+09 | 0.199576E+10 | 0.135803E+10 |
Minimum of Months | 64445432.04 | 19814730.30 | 22514163.03 | 77041623.65 | 72923003.50 |
Maximum of Months | 0.155207E+09 | 90152315.21 | 80503149.84 | 0.276416E+09 | 0.172469E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.106372E+09 | 0.127714E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120926E+09 | 0.110994E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 64539877.12 | 0.104223E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.189849E+09 | 84583536.08 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.148433E+09 | 76483343.06 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.135475E+09 | 60635678.04 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.162958E+09 | 60054457.42 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.203368E+09 | 66551431.19 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.231998E+09 | 79702579.32 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.148726E+09 | 97671091.27 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 91207550.70 | 0.112372E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70833353.10 | 0.143776E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.167469E+10 | 0.112476E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 64539877.12 | 60054457.42 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.231998E+09 | 0.143776E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.106372E+09 | 0.127714E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.120926E+09 | 0.110994E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 64539877.12 | 0.104223E+09 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.189849E+09 | 84583536.08 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.148433E+09 | 76483343.06 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.135475E+09 | 60635678.04 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.162958E+09 | 60054457.42 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.203368E+09 | 66551431.19 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.231998E+09 | 79702579.32 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.148726E+09 | 97671091.27 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 91207550.70 | 0.112372E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 70833353.10 | 0.143776E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.167469E+10 | 0.112476E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 64539877.12 | 60054457.42 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.231998E+09 | 0.143776E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92872055.60 | 60940170.38 | 31931885.22 | 0.127399E+09 | 0.151681E+09 |
February | 0.101351E+09 | 62417564.72 | 38933258.36 | 0.144829E+09 | 0.131733E+09 |
March | 68279291.13 | 19814730.30 | 48464560.83 | 77466093.53 | 0.123820E+09 |
April | 0.134381E+09 | 59084572.11 | 75295933.22 | 0.227132E+09 | 0.100553E+09 |
May | 0.113315E+09 | 34117149.23 | 79198127.89 | 0.177741E+09 | 90842330.60 |
June | 0.100999E+09 | 21651990.14 | 79347289.87 | 0.162174E+09 | 72065346.38 |
July | 0.112710E+09 | 32206924.48 | 80503149.84 | 0.194935E+09 | 71425534.22 |
August | 0.133133E+09 | 57572683.76 | 75560639.06 | 0.243148E+09 | 79267151.12 |
September | 0.155207E+09 | 90152315.21 | 65054602.13 | 0.277445E+09 | 94873202.65 |
October | 0.112549E+09 | 66212130.61 | 46336887.93 | 0.177940E+09 | 0.116100E+09 |
November | 78242380.61 | 48275633.68 | 29966746.92 | 0.109237E+09 | 0.133440E+09 |
December | 64445432.04 | 41931269.02 | 22514163.03 | 84885529.92 | 0.170560E+09 |
Annual Sum or Average | 0.126748E+10 | 0.594377E+09 | 0.673107E+09 | 0.200433E+10 | 0.133636E+10 |
Minimum of Months | 64445432.04 | 19814730.30 | 22514163.03 | 77466093.53 | 71425534.22 |
Maximum of Months | 0.155207E+09 | 90152315.21 | 80503149.84 | 0.277445E+09 | 0.170560E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.107391E+09 | 0.121712E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.122110E+09 | 0.105287E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 65832392.24 | 98552451.64 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.191173E+09 | 79906854.59 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.150413E+09 | 71078043.53 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.138075E+09 | 55972307.44 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.164845E+09 | 56130258.27 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.204731E+09 | 62821899.30 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.233774E+09 | 75182841.77 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.150034E+09 | 92440278.17 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 92015768.63 | 0.107072E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 71542662.51 | 0.137200E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.169194E+10 | 0.106336E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 65832392.24 | 55972307.44 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.233774E+09 | 0.137200E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77679187.05 | 50971014.52 | 26708172.54 | 0.107391E+09 | 0.121712E+09 |
February | 84770919.45 | 52206723.05 | 32564196.41 | 0.122110E+09 | 0.105287E+09 |
March | 57109534.12 | 16573253.73 | 40536280.39 | 65832392.24 | 98552451.64 |
April | 0.112397E+09 | 49418972.15 | 62978329.09 | 0.191173E+09 | 79906854.59 |
May | 94778117.59 | 28535950.88 | 66242166.72 | 0.150413E+09 | 71078043.53 |
June | 84476885.04 | 18109957.64 | 66366927.41 | 0.138075E+09 | 55972307.44 |
July | 94271919.46 | 26938218.34 | 67333701.13 | 0.164845E+09 | 56130258.27 |
August | 0.111354E+09 | 48154412.46 | 63199731.90 | 0.204731E+09 | 62821899.30 |
September | 0.129817E+09 | 75404366.91 | 54412369.52 | 0.233774E+09 | 75182841.77 |
October | 94137210.68 | 55380538.80 | 38756671.88 | 0.150034E+09 | 92440278.17 |
November | 65442769.41 | 40378259.69 | 25064509.71 | 92015768.63 | 0.107072E+09 |
December | 53902853.10 | 35071764.79 | 18831088.32 | 71542662.51 | 0.137200E+09 |
Annual Sum or Average | 0.106014E+10 | 0.497143E+09 | 0.562994E+09 | 0.169194E+10 | 0.106336E+10 |
Minimum of Months | 53902853.10 | 16573253.73 | 18831088.32 | 65832392.24 | 55972307.44 |
Maximum of Months | 0.129817E+09 | 75404366.91 | 67333701.13 | 0.233774E+09 | 0.137200E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92872055.60 | 60940170.38 | 31931885.22 | 0.128636E+09 | 0.144522E+09 |
February | 0.101351E+09 | 62417564.72 | 38933258.36 | 0.146264E+09 | 0.124943E+09 |
March | 68279291.13 | 19814730.30 | 48464560.83 | 79036498.34 | 0.117057E+09 |
April | 0.134381E+09 | 59084572.11 | 75295933.22 | 0.228732E+09 | 94994830.65 |
May | 0.113315E+09 | 34117149.23 | 79198127.89 | 0.180125E+09 | 84458006.79 |
June | 0.100999E+09 | 21651990.14 | 79347289.87 | 0.165279E+09 | 66554942.17 |
July | 0.112710E+09 | 32206924.48 | 80503149.84 | 0.197195E+09 | 66791053.59 |
August | 0.133133E+09 | 57572683.76 | 75560639.06 | 0.244785E+09 | 74852085.02 |
September | 0.155207E+09 | 90152315.21 | 65054602.13 | 0.279566E+09 | 89523809.17 |
October | 0.112549E+09 | 66212130.61 | 46336887.93 | 0.179515E+09 | 0.109890E+09 |
November | 78242380.61 | 48275633.68 | 29966746.92 | 0.110219E+09 | 0.127136E+09 |
December | 64445432.04 | 41931269.02 | 22514163.03 | 85745775.04 | 0.162738E+09 |
Annual Sum or Average | 0.126748E+10 | 0.594377E+09 | 0.673107E+09 | 0.202510E+10 | 0.126346E+10 |
Minimum of Months | 64445432.04 | 19814730.30 | 22514163.03 | 79036498.34 | 66554942.17 |
Maximum of Months | 0.155207E+09 | 90152315.21 | 80503149.84 | 0.279566E+09 | 0.162738E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 254.24 | 312.46 | 185.74 | 121.88 | 63.86 | 0.00 | 0.00 |
February | 320.19 | 300.01 | 224.41 | 138.21 | 86.21 | 0.00 | 0.00 |
March | 154.55 | 254.51 | 136.55 | 39.63 | 96.93 | 0.00 | 0.00 |
April | 468.75 | 214.14 | 277.71 | 122.10 | 155.61 | 0.00 | 0.00 |
May | 353.69 | 188.42 | 226.62 | 68.23 | 158.39 | 0.00 | 0.00 |
June | 332.95 | 154.59 | 208.73 | 44.75 | 163.98 | 0.00 | 0.00 |
July | 389.78 | 146.02 | 225.41 | 64.41 | 161.00 | 0.00 | 0.00 |
August | 487.42 | 159.97 | 266.26 | 115.14 | 151.12 | 0.00 | 0.00 |
September | 573.28 | 199.92 | 320.75 | 186.31 | 134.44 | 0.00 | 0.00 |
October | 354.78 | 240.19 | 225.09 | 132.42 | 92.67 | 0.00 | 0.00 |
November | 225.16 | 284.81 | 161.70 | 99.77 | 61.93 | 0.00 | 0.00 |
December | 169.44 | 350.01 | 128.89 | 83.86 | 45.03 | 0.00 | 0.00 |
Annual Sum or Average | 339.86 | 233.43 | 215.29 | 100.96 | 114.33 | 0.00 | 0.00 |
Minimum of Months | 154.55 | 146.02 | 128.89 | 39.63 | 45.03 | 0.00 | 0.00 |
Maximum of Months | 573.28 | 350.01 | 320.75 | 186.31 | 163.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 125.72 | 163.30 | 92.87 | 60.94 | 31.93 | 0.00 | 0.00 |
February | 158.38 | 157.15 | 112.21 | 69.10 | 43.10 | 0.00 | 0.00 |
March | 75.41 | 134.44 | 68.28 | 19.81 | 48.46 | 0.00 | 0.00 |
April | 229.64 | 115.94 | 138.86 | 61.05 | 77.80 | 0.00 | 0.00 |
May | 171.53 | 103.05 | 113.31 | 34.12 | 79.20 | 0.00 | 0.00 |
June | 162.49 | 81.95 | 104.36 | 22.37 | 81.99 | 0.00 | 0.00 |
July | 192.78 | 75.72 | 112.71 | 32.21 | 80.50 | 0.00 | 0.00 |
August | 242.49 | 81.96 | 133.13 | 57.57 | 75.56 | 0.00 | 0.00 |
September | 284.17 | 103.76 | 160.38 | 93.15 | 67.22 | 0.00 | 0.00 |
October | 173.68 | 130.38 | 112.55 | 66.21 | 46.34 | 0.00 | 0.00 |
November | 111.24 | 150.10 | 80.85 | 49.88 | 30.96 | 0.00 | 0.00 |
December | 83.75 | 182.70 | 64.44 | 41.93 | 22.51 | 0.00 | 0.00 |
Annual Sum or Average | 167.36 | 123.21 | 107.65 | 50.48 | 57.17 | 0.00 | 0.00 |
Minimum of Months | 75.41 | 75.72 | 64.44 | 19.81 | 22.51 | 0.00 | 0.00 |
Maximum of Months | 284.17 | 182.70 | 160.38 | 93.15 | 81.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 125.85 | 160.45 | 92.68 | 60.81 | 31.87 | 0.00 | 0.00 |
February | 158.42 | 154.56 | 111.98 | 68.96 | 43.01 | 0.00 | 0.00 |
March | 75.57 | 132.18 | 68.14 | 19.77 | 48.36 | 0.00 | 0.00 |
April | 229.15 | 115.27 | 138.57 | 60.93 | 77.64 | 0.00 | 0.00 |
May | 170.96 | 103.02 | 113.08 | 34.05 | 79.03 | 0.00 | 0.00 |
June | 161.74 | 83.71 | 104.15 | 22.33 | 81.82 | 0.00 | 0.00 |
July | 191.93 | 77.80 | 112.48 | 32.14 | 80.34 | 0.00 | 0.00 |
August | 241.78 | 84.15 | 132.86 | 57.45 | 75.40 | 0.00 | 0.00 |
September | 283.49 | 105.53 | 160.05 | 92.96 | 67.08 | 0.00 | 0.00 |
October | 173.41 | 129.40 | 112.31 | 66.07 | 46.24 | 0.00 | 0.00 |
November | 111.35 | 147.19 | 80.68 | 49.78 | 30.90 | 0.00 | 0.00 |
December | 83.89 | 179.80 | 64.31 | 41.84 | 22.47 | 0.00 | 0.00 |
Annual Sum or Average | 167.05 | 122.60 | 107.43 | 50.38 | 57.05 | 0.00 | 0.00 |
Minimum of Months | 75.57 | 77.80 | 64.31 | 19.77 | 22.47 | 0.00 | 0.00 |
Maximum of Months | 283.49 | 179.80 | 160.05 | 92.96 | 81.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 126.10 | 158.73 | 92.68 | 60.81 | 31.87 | 0.00 | 0.00 |
February | 158.68 | 153.00 | 111.98 | 68.96 | 43.01 | 0.00 | 0.00 |
March | 75.86 | 130.70 | 68.14 | 19.77 | 48.36 | 0.00 | 0.00 |
April | 229.86 | 113.62 | 138.57 | 60.93 | 77.64 | 0.00 | 0.00 |
May | 171.69 | 101.48 | 113.08 | 34.05 | 79.03 | 0.00 | 0.00 |
June | 162.03 | 83.03 | 104.15 | 22.33 | 81.82 | 0.00 | 0.00 |
July | 192.09 | 77.38 | 112.48 | 32.14 | 80.34 | 0.00 | 0.00 |
August | 241.86 | 83.85 | 132.86 | 57.45 | 75.40 | 0.00 | 0.00 |
September | 283.65 | 104.94 | 160.05 | 92.96 | 67.08 | 0.00 | 0.00 |
October | 173.90 | 127.49 | 112.31 | 66.07 | 46.24 | 0.00 | 0.00 |
November | 111.59 | 145.37 | 80.68 | 49.78 | 30.90 | 0.00 | 0.00 |
December | 84.05 | 178.09 | 64.31 | 41.84 | 22.47 | 0.00 | 0.00 |
Annual Sum or Average | 167.37 | 121.32 | 107.43 | 50.38 | 57.05 | 0.00 | 0.00 |
Minimum of Months | 75.86 | 77.38 | 64.31 | 19.77 | 22.47 | 0.00 | 0.00 |
Maximum of Months | 283.65 | 178.09 | 160.05 | 92.96 | 81.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 126.40 | 157.17 | 92.68 | 60.81 | 31.87 | 0.00 | 0.00 |
February | 159.02 | 151.53 | 111.98 | 68.96 | 43.01 | 0.00 | 0.00 |
March | 76.26 | 129.23 | 68.14 | 19.77 | 48.36 | 0.00 | 0.00 |
April | 231.25 | 111.17 | 138.57 | 60.93 | 77.64 | 0.00 | 0.00 |
May | 173.33 | 98.83 | 113.08 | 34.05 | 79.03 | 0.00 | 0.00 |
June | 163.14 | 81.31 | 104.15 | 22.33 | 81.82 | 0.00 | 0.00 |
July | 192.68 | 76.27 | 112.48 | 32.14 | 80.34 | 0.00 | 0.00 |
August | 242.17 | 83.06 | 132.86 | 57.45 | 75.40 | 0.00 | 0.00 |
September | 284.24 | 103.58 | 160.05 | 92.96 | 67.08 | 0.00 | 0.00 |
October | 174.96 | 124.53 | 112.31 | 66.07 | 46.24 | 0.00 | 0.00 |
November | 111.91 | 143.63 | 80.68 | 49.78 | 30.90 | 0.00 | 0.00 |
December | 84.25 | 176.43 | 64.31 | 41.84 | 22.47 | 0.00 | 0.00 |
Annual Sum or Average | 168.06 | 119.57 | 107.43 | 50.38 | 57.05 | 0.00 | 0.00 |
Minimum of Months | 76.26 | 76.27 | 64.31 | 19.77 | 22.47 | 0.00 | 0.00 |
Maximum of Months | 284.24 | 176.43 | 160.05 | 92.96 | 81.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 254.01 | 307.47 | 185.36 | 121.63 | 63.73 | 0.00 | 0.00 |
February | 319.60 | 296.14 | 223.95 | 137.92 | 86.03 | 0.00 | 0.00 |
March | 154.06 | 252.02 | 136.27 | 39.55 | 96.73 | 0.00 | 0.00 |
April | 467.53 | 212.67 | 277.14 | 121.85 | 155.29 | 0.00 | 0.00 |
May | 353.08 | 187.16 | 226.16 | 68.09 | 158.07 | 0.00 | 0.00 |
June | 332.35 | 153.80 | 208.30 | 44.65 | 163.64 | 0.00 | 0.00 |
July | 387.77 | 146.88 | 224.95 | 64.28 | 160.67 | 0.00 | 0.00 |
August | 484.79 | 162.03 | 265.71 | 114.91 | 150.81 | 0.00 | 0.00 |
September | 571.81 | 199.86 | 320.09 | 185.93 | 134.17 | 0.00 | 0.00 |
October | 354.40 | 237.64 | 224.63 | 132.15 | 92.48 | 0.00 | 0.00 |
November | 224.95 | 280.17 | 161.36 | 99.56 | 61.80 | 0.00 | 0.00 |
December | 169.21 | 344.92 | 128.62 | 83.69 | 44.93 | 0.00 | 0.00 |
Annual Sum or Average | 338.97 | 231.42 | 214.85 | 100.75 | 114.10 | 0.00 | 0.00 |
Minimum of Months | 154.06 | 146.88 | 128.62 | 39.55 | 44.93 | 0.00 | 0.00 |
Maximum of Months | 571.81 | 344.92 | 320.09 | 185.93 | 163.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 126.58 | 154.27 | 92.68 | 60.81 | 31.87 | 0.00 | 0.00 |
February | 159.30 | 148.57 | 111.98 | 68.96 | 43.01 | 0.00 | 0.00 |
March | 76.58 | 126.28 | 68.14 | 19.77 | 48.36 | 0.00 | 0.00 |
April | 233.04 | 106.40 | 138.57 | 60.93 | 77.64 | 0.00 | 0.00 |
May | 175.67 | 93.74 | 113.08 | 34.05 | 79.03 | 0.00 | 0.00 |
June | 165.02 | 77.27 | 104.15 | 22.33 | 81.82 | 0.00 | 0.00 |
July | 193.13 | 73.43 | 112.48 | 32.14 | 80.34 | 0.00 | 0.00 |
August | 241.86 | 80.84 | 132.86 | 57.45 | 75.40 | 0.00 | 0.00 |
September | 284.73 | 100.46 | 160.05 | 92.96 | 67.08 | 0.00 | 0.00 |
October | 176.47 | 119.14 | 112.31 | 66.07 | 46.24 | 0.00 | 0.00 |
November | 112.14 | 140.46 | 80.68 | 49.78 | 30.90 | 0.00 | 0.00 |
December | 84.31 | 173.34 | 64.31 | 41.84 | 22.47 | 0.00 | 0.00 |
Annual Sum or Average | 168.83 | 116.03 | 107.43 | 50.38 | 57.05 | 0.00 | 0.00 |
Minimum of Months | 76.58 | 73.43 | 64.31 | 19.77 | 22.47 | 0.00 | 0.00 |
Maximum of Months | 284.73 | 173.34 | 160.05 | 92.96 | 81.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 126.67 | 153.85 | 92.68 | 60.81 | 31.87 | 0.00 | 0.00 |
February | 159.41 | 148.13 | 111.98 | 68.96 | 43.01 | 0.00 | 0.00 |
March | 76.70 | 125.85 | 68.14 | 19.77 | 48.36 | 0.00 | 0.00 |
April | 233.32 | 105.87 | 138.57 | 60.93 | 77.64 | 0.00 | 0.00 |
May | 176.05 | 93.13 | 113.08 | 34.05 | 79.03 | 0.00 | 0.00 |
June | 165.49 | 76.69 | 104.15 | 22.33 | 81.82 | 0.00 | 0.00 |
July | 193.44 | 73.02 | 112.48 | 32.14 | 80.34 | 0.00 | 0.00 |
August | 242.04 | 80.51 | 132.86 | 57.45 | 75.40 | 0.00 | 0.00 |
September | 284.99 | 100.02 | 160.05 | 92.96 | 67.08 | 0.00 | 0.00 |
October | 176.72 | 118.49 | 112.31 | 66.07 | 46.24 | 0.00 | 0.00 |
November | 112.23 | 139.99 | 80.68 | 49.78 | 30.90 | 0.00 | 0.00 |
December | 84.36 | 172.95 | 64.31 | 41.84 | 22.47 | 0.00 | 0.00 |
Annual Sum or Average | 169.04 | 115.55 | 107.43 | 50.38 | 57.05 | 0.00 | 0.00 |
Minimum of Months | 76.70 | 73.02 | 64.31 | 19.77 | 22.47 | 0.00 | 0.00 |
Maximum of Months | 284.99 | 172.95 | 160.05 | 92.96 | 81.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 126.99 | 152.00 | 92.68 | 60.81 | 31.87 | 0.00 | 0.00 |
February | 159.84 | 146.21 | 111.98 | 68.96 | 43.01 | 0.00 | 0.00 |
March | 77.12 | 124.05 | 68.14 | 19.77 | 48.36 | 0.00 | 0.00 |
April | 234.12 | 104.06 | 138.57 | 60.93 | 77.64 | 0.00 | 0.00 |
May | 177.20 | 91.03 | 113.08 | 34.05 | 79.03 | 0.00 | 0.00 |
June | 167.10 | 74.59 | 104.15 | 22.33 | 81.82 | 0.00 | 0.00 |
July | 194.46 | 71.51 | 112.48 | 32.14 | 80.34 | 0.00 | 0.00 |
August | 242.64 | 79.29 | 132.86 | 57.45 | 75.40 | 0.00 | 0.00 |
September | 286.05 | 98.10 | 160.05 | 92.96 | 67.08 | 0.00 | 0.00 |
October | 177.49 | 116.28 | 112.31 | 66.07 | 46.24 | 0.00 | 0.00 |
November | 112.52 | 138.19 | 80.68 | 49.78 | 30.90 | 0.00 | 0.00 |
December | 84.58 | 171.04 | 64.31 | 41.84 | 22.47 | 0.00 | 0.00 |
Annual Sum or Average | 169.76 | 113.71 | 107.43 | 50.38 | 57.05 | 0.00 | 0.00 |
Minimum of Months | 77.12 | 71.51 | 64.31 | 19.77 | 22.47 | 0.00 | 0.00 |
Maximum of Months | 286.05 | 171.04 | 160.05 | 92.96 | 81.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 128.22 | 144.84 | 92.68 | 60.81 | 31.87 | 0.00 | 0.00 |
February | 161.41 | 138.69 | 111.98 | 68.96 | 43.01 | 0.00 | 0.00 |
March | 78.67 | 117.29 | 68.14 | 19.77 | 48.36 | 0.00 | 0.00 |
April | 235.76 | 98.31 | 138.57 | 60.93 | 77.64 | 0.00 | 0.00 |
May | 179.57 | 84.61 | 113.08 | 34.05 | 79.03 | 0.00 | 0.00 |
June | 170.30 | 68.87 | 104.15 | 22.33 | 81.82 | 0.00 | 0.00 |
July | 196.72 | 66.85 | 112.48 | 32.14 | 80.34 | 0.00 | 0.00 |
August | 244.27 | 74.86 | 132.86 | 57.45 | 75.40 | 0.00 | 0.00 |
September | 288.24 | 92.55 | 160.05 | 92.96 | 67.08 | 0.00 | 0.00 |
October | 179.06 | 110.05 | 112.31 | 66.07 | 46.24 | 0.00 | 0.00 |
November | 113.52 | 131.67 | 80.68 | 49.78 | 30.90 | 0.00 | 0.00 |
December | 85.44 | 163.21 | 64.31 | 41.84 | 22.47 | 0.00 | 0.00 |
Annual Sum or Average | 171.52 | 107.50 | 107.43 | 50.38 | 57.05 | 0.00 | 0.00 |
Minimum of Months | 78.67 | 66.85 | 64.31 | 19.77 | 22.47 | 0.00 | 0.00 |
Maximum of Months | 288.24 | 163.21 | 160.05 | 92.96 | 81.82 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.680959E+09 | 0.836891E+09 | 0.497481E+09 | 0.326434E+09 | 0.171047E+09 | 0.00 | 0.00 |
February | 0.774614E+09 | 0.725791E+09 | 0.542899E+09 | 0.334348E+09 | 0.208551E+09 | 0.00 | 0.00 |
March | 0.413937E+09 | 0.681688E+09 | 0.365747E+09 | 0.106140E+09 | 0.259607E+09 | 0.00 | 0.00 |
April | 0.121499E+10 | 0.555056E+09 | 0.719827E+09 | 0.316494E+09 | 0.403333E+09 | 0.00 | 0.00 |
May | 0.947324E+09 | 0.504667E+09 | 0.606988E+09 | 0.182753E+09 | 0.424235E+09 | 0.00 | 0.00 |
June | 0.863006E+09 | 0.400696E+09 | 0.541016E+09 | 0.115982E+09 | 0.425034E+09 | 0.00 | 0.00 |
July | 0.104398E+10 | 0.391102E+09 | 0.603746E+09 | 0.172521E+09 | 0.431226E+09 | 0.00 | 0.00 |
August | 0.130550E+10 | 0.428453E+09 | 0.713146E+09 | 0.308396E+09 | 0.404751E+09 | 0.00 | 0.00 |
September | 0.148595E+10 | 0.518183E+09 | 0.831386E+09 | 0.482913E+09 | 0.348474E+09 | 0.00 | 0.00 |
October | 0.950238E+09 | 0.643335E+09 | 0.602884E+09 | 0.354674E+09 | 0.248210E+09 | 0.00 | 0.00 |
November | 0.583614E+09 | 0.738218E+09 | 0.419116E+09 | 0.258595E+09 | 0.160521E+09 | 0.00 | 0.00 |
December | 0.453822E+09 | 0.937470E+09 | 0.345210E+09 | 0.224610E+09 | 0.120600E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107179E+11 | 0.736155E+10 | 0.678945E+10 | 0.318386E+10 | 0.360559E+10 | 0.00 | 0.00 |
Minimum of Months | 0.413937E+09 | 0.391102E+09 | 0.345210E+09 | 0.106140E+09 | 0.120600E+09 | 0.00 | 0.00 |
Maximum of Months | 0.148595E+10 | 0.937470E+09 | 0.831386E+09 | 0.482913E+09 | 0.431226E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.336726E+09 | 0.437374E+09 | 0.248741E+09 | 0.163217E+09 | 85523680.21 | 0.00 | 0.00 |
February | 0.383152E+09 | 0.380184E+09 | 0.271450E+09 | 0.167174E+09 | 0.104276E+09 | 0.00 | 0.00 |
March | 0.201975E+09 | 0.360097E+09 | 0.182874E+09 | 53070109.90 | 0.129803E+09 | 0.00 | 0.00 |
April | 0.595226E+09 | 0.300522E+09 | 0.359913E+09 | 0.158247E+09 | 0.201666E+09 | 0.00 | 0.00 |
May | 0.459415E+09 | 0.276000E+09 | 0.303494E+09 | 91376507.85 | 0.212118E+09 | 0.00 | 0.00 |
June | 0.421179E+09 | 0.212410E+09 | 0.270508E+09 | 57990872.39 | 0.212517E+09 | 0.00 | 0.00 |
July | 0.516346E+09 | 0.202804E+09 | 0.301873E+09 | 86260322.27 | 0.215613E+09 | 0.00 | 0.00 |
August | 0.649486E+09 | 0.219511E+09 | 0.356573E+09 | 0.154198E+09 | 0.202375E+09 | 0.00 | 0.00 |
September | 0.736564E+09 | 0.268939E+09 | 0.415693E+09 | 0.241456E+09 | 0.174237E+09 | 0.00 | 0.00 |
October | 0.465181E+09 | 0.349223E+09 | 0.301442E+09 | 0.177337E+09 | 0.124105E+09 | 0.00 | 0.00 |
November | 0.288329E+09 | 0.389053E+09 | 0.209558E+09 | 0.129297E+09 | 80260418.81 | 0.00 | 0.00 |
December | 0.224317E+09 | 0.489356E+09 | 0.172605E+09 | 0.112305E+09 | 60300043.85 | 0.00 | 0.00 |
Annual Sum or Average | 0.527790E+10 | 0.388547E+10 | 0.339472E+10 | 0.159193E+10 | 0.180279E+10 | 0.00 | 0.00 |
Minimum of Months | 0.201975E+09 | 0.202804E+09 | 0.172605E+09 | 53070109.90 | 60300043.85 | 0.00 | 0.00 |
Maximum of Months | 0.736564E+09 | 0.489356E+09 | 0.415693E+09 | 0.241456E+09 | 0.215613E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.337082E+09 | 0.429752E+09 | 0.248230E+09 | 0.162882E+09 | 85348230.30 | 0.00 | 0.00 |
February | 0.383254E+09 | 0.373901E+09 | 0.270893E+09 | 0.166831E+09 | 0.104062E+09 | 0.00 | 0.00 |
March | 0.202395E+09 | 0.354032E+09 | 0.182498E+09 | 52961237.75 | 0.129537E+09 | 0.00 | 0.00 |
April | 0.593966E+09 | 0.298790E+09 | 0.359175E+09 | 0.157923E+09 | 0.201253E+09 | 0.00 | 0.00 |
May | 0.457894E+09 | 0.275938E+09 | 0.302872E+09 | 91189050.98 | 0.211682E+09 | 0.00 | 0.00 |
June | 0.419218E+09 | 0.216983E+09 | 0.269953E+09 | 57871905.41 | 0.212081E+09 | 0.00 | 0.00 |
July | 0.514058E+09 | 0.208384E+09 | 0.301254E+09 | 86083361.15 | 0.215171E+09 | 0.00 | 0.00 |
August | 0.647592E+09 | 0.225389E+09 | 0.355842E+09 | 0.153882E+09 | 0.201960E+09 | 0.00 | 0.00 |
September | 0.734795E+09 | 0.273538E+09 | 0.414840E+09 | 0.240961E+09 | 0.173879E+09 | 0.00 | 0.00 |
October | 0.464459E+09 | 0.346587E+09 | 0.300823E+09 | 0.176973E+09 | 0.123850E+09 | 0.00 | 0.00 |
November | 0.288611E+09 | 0.381513E+09 | 0.209128E+09 | 0.129032E+09 | 80095766.35 | 0.00 | 0.00 |
December | 0.224685E+09 | 0.481587E+09 | 0.172251E+09 | 0.112075E+09 | 60176339.66 | 0.00 | 0.00 |
Annual Sum or Average | 0.526801E+10 | 0.386639E+10 | 0.338776E+10 | 0.158866E+10 | 0.179910E+10 | 0.00 | 0.00 |
Minimum of Months | 0.202395E+09 | 0.208384E+09 | 0.172251E+09 | 52961237.75 | 60176339.66 | 0.00 | 0.00 |
Maximum of Months | 0.734795E+09 | 0.481587E+09 | 0.414840E+09 | 0.240961E+09 | 0.215171E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.337757E+09 | 0.425137E+09 | 0.248230E+09 | 0.162882E+09 | 85348230.30 | 0.00 | 0.00 |
February | 0.383873E+09 | 0.370127E+09 | 0.270893E+09 | 0.166831E+09 | 0.104062E+09 | 0.00 | 0.00 |
March | 0.203174E+09 | 0.350068E+09 | 0.182498E+09 | 52961237.75 | 0.129537E+09 | 0.00 | 0.00 |
April | 0.595800E+09 | 0.294496E+09 | 0.359175E+09 | 0.157923E+09 | 0.201253E+09 | 0.00 | 0.00 |
May | 0.459859E+09 | 0.271814E+09 | 0.302872E+09 | 91189050.98 | 0.211682E+09 | 0.00 | 0.00 |
June | 0.419985E+09 | 0.215223E+09 | 0.269953E+09 | 57871905.41 | 0.212081E+09 | 0.00 | 0.00 |
July | 0.514484E+09 | 0.207242E+09 | 0.301254E+09 | 86083361.15 | 0.215171E+09 | 0.00 | 0.00 |
August | 0.647805E+09 | 0.224575E+09 | 0.355842E+09 | 0.153882E+09 | 0.201960E+09 | 0.00 | 0.00 |
September | 0.735231E+09 | 0.271995E+09 | 0.414840E+09 | 0.240961E+09 | 0.173879E+09 | 0.00 | 0.00 |
October | 0.465772E+09 | 0.341469E+09 | 0.300823E+09 | 0.176973E+09 | 0.123850E+09 | 0.00 | 0.00 |
November | 0.289250E+09 | 0.376788E+09 | 0.209128E+09 | 0.129032E+09 | 80095766.35 | 0.00 | 0.00 |
December | 0.225113E+09 | 0.476983E+09 | 0.172251E+09 | 0.112075E+09 | 60176339.66 | 0.00 | 0.00 |
Annual Sum or Average | 0.527810E+10 | 0.382592E+10 | 0.338776E+10 | 0.158866E+10 | 0.179910E+10 | 0.00 | 0.00 |
Minimum of Months | 0.203174E+09 | 0.207242E+09 | 0.172251E+09 | 52961237.75 | 60176339.66 | 0.00 | 0.00 |
Maximum of Months | 0.735231E+09 | 0.476983E+09 | 0.414840E+09 | 0.240961E+09 | 0.215171E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.338561E+09 | 0.420965E+09 | 0.248230E+09 | 0.162882E+09 | 85348230.30 | 0.00 | 0.00 |
February | 0.384696E+09 | 0.366570E+09 | 0.270893E+09 | 0.166831E+09 | 0.104062E+09 | 0.00 | 0.00 |
March | 0.204250E+09 | 0.346133E+09 | 0.182498E+09 | 52961237.75 | 0.129537E+09 | 0.00 | 0.00 |
April | 0.599410E+09 | 0.288160E+09 | 0.359175E+09 | 0.157923E+09 | 0.201253E+09 | 0.00 | 0.00 |
May | 0.464255E+09 | 0.264697E+09 | 0.302872E+09 | 91189050.98 | 0.211682E+09 | 0.00 | 0.00 |
June | 0.422846E+09 | 0.210744E+09 | 0.269953E+09 | 57871905.41 | 0.212081E+09 | 0.00 | 0.00 |
July | 0.516073E+09 | 0.204284E+09 | 0.301254E+09 | 86083361.15 | 0.215171E+09 | 0.00 | 0.00 |
August | 0.648639E+09 | 0.222478E+09 | 0.355842E+09 | 0.153882E+09 | 0.201960E+09 | 0.00 | 0.00 |
September | 0.736752E+09 | 0.268474E+09 | 0.414840E+09 | 0.240961E+09 | 0.173879E+09 | 0.00 | 0.00 |
October | 0.468599E+09 | 0.333536E+09 | 0.300823E+09 | 0.176973E+09 | 0.123850E+09 | 0.00 | 0.00 |
November | 0.290067E+09 | 0.372279E+09 | 0.209128E+09 | 0.129032E+09 | 80095766.35 | 0.00 | 0.00 |
December | 0.225661E+09 | 0.472557E+09 | 0.172251E+09 | 0.112075E+09 | 60176339.66 | 0.00 | 0.00 |
Annual Sum or Average | 0.529981E+10 | 0.377088E+10 | 0.338776E+10 | 0.158866E+10 | 0.179910E+10 | 0.00 | 0.00 |
Minimum of Months | 0.204250E+09 | 0.204284E+09 | 0.172251E+09 | 52961237.75 | 60176339.66 | 0.00 | 0.00 |
Maximum of Months | 0.736752E+09 | 0.472557E+09 | 0.414840E+09 | 0.240961E+09 | 0.215171E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.680334E+09 | 0.823533E+09 | 0.496461E+09 | 0.325764E+09 | 0.170696E+09 | 0.00 | 0.00 |
February | 0.773168E+09 | 0.716422E+09 | 0.541785E+09 | 0.333662E+09 | 0.208123E+09 | 0.00 | 0.00 |
March | 0.412624E+09 | 0.675009E+09 | 0.364997E+09 | 0.105922E+09 | 0.259074E+09 | 0.00 | 0.00 |
April | 0.121183E+10 | 0.551253E+09 | 0.718350E+09 | 0.315845E+09 | 0.402505E+09 | 0.00 | 0.00 |
May | 0.945700E+09 | 0.501295E+09 | 0.605743E+09 | 0.182378E+09 | 0.423365E+09 | 0.00 | 0.00 |
June | 0.861453E+09 | 0.398659E+09 | 0.539906E+09 | 0.115744E+09 | 0.424162E+09 | 0.00 | 0.00 |
July | 0.103861E+10 | 0.393391E+09 | 0.602508E+09 | 0.172167E+09 | 0.430341E+09 | 0.00 | 0.00 |
August | 0.129846E+10 | 0.433971E+09 | 0.711683E+09 | 0.307763E+09 | 0.403920E+09 | 0.00 | 0.00 |
September | 0.148212E+10 | 0.518037E+09 | 0.829681E+09 | 0.481922E+09 | 0.347759E+09 | 0.00 | 0.00 |
October | 0.949218E+09 | 0.636506E+09 | 0.601647E+09 | 0.353946E+09 | 0.247700E+09 | 0.00 | 0.00 |
November | 0.583059E+09 | 0.726204E+09 | 0.418256E+09 | 0.258064E+09 | 0.160192E+09 | 0.00 | 0.00 |
December | 0.453216E+09 | 0.923826E+09 | 0.344502E+09 | 0.224150E+09 | 0.120353E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106898E+11 | 0.729810E+10 | 0.677552E+10 | 0.317733E+10 | 0.359819E+10 | 0.00 | 0.00 |
Minimum of Months | 0.412624E+09 | 0.393391E+09 | 0.344502E+09 | 0.105922E+09 | 0.120353E+09 | 0.00 | 0.00 |
Maximum of Months | 0.148212E+10 | 0.923826E+09 | 0.829681E+09 | 0.481922E+09 | 0.430341E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.339042E+09 | 0.413199E+09 | 0.248230E+09 | 0.162882E+09 | 85348230.30 | 0.00 | 0.00 |
February | 0.385388E+09 | 0.359430E+09 | 0.270893E+09 | 0.166831E+09 | 0.104062E+09 | 0.00 | 0.00 |
March | 0.205103E+09 | 0.338234E+09 | 0.182498E+09 | 52961237.75 | 0.129537E+09 | 0.00 | 0.00 |
April | 0.604052E+09 | 0.275793E+09 | 0.359175E+09 | 0.157923E+09 | 0.201253E+09 | 0.00 | 0.00 |
May | 0.470528E+09 | 0.251082E+09 | 0.302872E+09 | 91189050.98 | 0.211682E+09 | 0.00 | 0.00 |
June | 0.427742E+09 | 0.200284E+09 | 0.269953E+09 | 57871905.41 | 0.212081E+09 | 0.00 | 0.00 |
July | 0.517289E+09 | 0.196685E+09 | 0.301254E+09 | 86083361.15 | 0.215171E+09 | 0.00 | 0.00 |
August | 0.647792E+09 | 0.216530E+09 | 0.355842E+09 | 0.153882E+09 | 0.201960E+09 | 0.00 | 0.00 |
September | 0.738031E+09 | 0.260388E+09 | 0.414840E+09 | 0.240961E+09 | 0.173879E+09 | 0.00 | 0.00 |
October | 0.472666E+09 | 0.319106E+09 | 0.300823E+09 | 0.176973E+09 | 0.123850E+09 | 0.00 | 0.00 |
November | 0.290676E+09 | 0.364081E+09 | 0.209128E+09 | 0.129032E+09 | 80095766.35 | 0.00 | 0.00 |
December | 0.225819E+09 | 0.464273E+09 | 0.172251E+09 | 0.112075E+09 | 60176339.66 | 0.00 | 0.00 |
Annual Sum or Average | 0.532413E+10 | 0.365908E+10 | 0.338776E+10 | 0.158866E+10 | 0.179910E+10 | 0.00 | 0.00 |
Minimum of Months | 0.205103E+09 | 0.196685E+09 | 0.172251E+09 | 52961237.75 | 60176339.66 | 0.00 | 0.00 |
Maximum of Months | 0.738031E+09 | 0.464273E+09 | 0.414840E+09 | 0.240961E+09 | 0.215171E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.339271E+09 | 0.412076E+09 | 0.248230E+09 | 0.162882E+09 | 85348230.30 | 0.00 | 0.00 |
February | 0.385656E+09 | 0.358364E+09 | 0.270893E+09 | 0.166831E+09 | 0.104062E+09 | 0.00 | 0.00 |
March | 0.205420E+09 | 0.337068E+09 | 0.182498E+09 | 52961237.75 | 0.129537E+09 | 0.00 | 0.00 |
April | 0.604777E+09 | 0.274420E+09 | 0.359175E+09 | 0.157923E+09 | 0.201253E+09 | 0.00 | 0.00 |
May | 0.471536E+09 | 0.249435E+09 | 0.302872E+09 | 91189050.98 | 0.211682E+09 | 0.00 | 0.00 |
June | 0.428954E+09 | 0.198793E+09 | 0.269953E+09 | 57871905.41 | 0.212081E+09 | 0.00 | 0.00 |
July | 0.518104E+09 | 0.195565E+09 | 0.301254E+09 | 86083361.15 | 0.215171E+09 | 0.00 | 0.00 |
August | 0.648272E+09 | 0.215634E+09 | 0.355842E+09 | 0.153882E+09 | 0.201960E+09 | 0.00 | 0.00 |
September | 0.738687E+09 | 0.259261E+09 | 0.414840E+09 | 0.240961E+09 | 0.173879E+09 | 0.00 | 0.00 |
October | 0.473315E+09 | 0.317371E+09 | 0.300823E+09 | 0.176973E+09 | 0.123850E+09 | 0.00 | 0.00 |
November | 0.290901E+09 | 0.362852E+09 | 0.209128E+09 | 0.129032E+09 | 80095766.35 | 0.00 | 0.00 |
December | 0.225959E+09 | 0.463232E+09 | 0.172251E+09 | 0.112075E+09 | 60176339.66 | 0.00 | 0.00 |
Annual Sum or Average | 0.533085E+10 | 0.364407E+10 | 0.338776E+10 | 0.158866E+10 | 0.179910E+10 | 0.00 | 0.00 |
Minimum of Months | 0.205420E+09 | 0.195565E+09 | 0.172251E+09 | 52961237.75 | 60176339.66 | 0.00 | 0.00 |
Maximum of Months | 0.738687E+09 | 0.463232E+09 | 0.414840E+09 | 0.240961E+09 | 0.215171E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.340143E+09 | 0.407109E+09 | 0.248230E+09 | 0.162882E+09 | 85348230.30 | 0.00 | 0.00 |
February | 0.386680E+09 | 0.353720E+09 | 0.270893E+09 | 0.166831E+09 | 0.104062E+09 | 0.00 | 0.00 |
March | 0.206546E+09 | 0.332266E+09 | 0.182498E+09 | 52961237.75 | 0.129537E+09 | 0.00 | 0.00 |
April | 0.606829E+09 | 0.269720E+09 | 0.359175E+09 | 0.157923E+09 | 0.201253E+09 | 0.00 | 0.00 |
May | 0.474607E+09 | 0.243808E+09 | 0.302872E+09 | 91189050.98 | 0.211682E+09 | 0.00 | 0.00 |
June | 0.433124E+09 | 0.193337E+09 | 0.269953E+09 | 57871905.41 | 0.212081E+09 | 0.00 | 0.00 |
July | 0.520851E+09 | 0.191534E+09 | 0.301254E+09 | 86083361.15 | 0.215171E+09 | 0.00 | 0.00 |
August | 0.649885E+09 | 0.212370E+09 | 0.355842E+09 | 0.153882E+09 | 0.201960E+09 | 0.00 | 0.00 |
September | 0.741440E+09 | 0.254278E+09 | 0.414840E+09 | 0.240961E+09 | 0.173879E+09 | 0.00 | 0.00 |
October | 0.475392E+09 | 0.311442E+09 | 0.300823E+09 | 0.176973E+09 | 0.123850E+09 | 0.00 | 0.00 |
November | 0.291652E+09 | 0.358183E+09 | 0.209128E+09 | 0.129032E+09 | 80095766.35 | 0.00 | 0.00 |
December | 0.226552E+09 | 0.458113E+09 | 0.172251E+09 | 0.112075E+09 | 60176339.66 | 0.00 | 0.00 |
Annual Sum or Average | 0.535370E+10 | 0.358588E+10 | 0.338776E+10 | 0.158866E+10 | 0.179910E+10 | 0.00 | 0.00 |
Minimum of Months | 0.206546E+09 | 0.191534E+09 | 0.172251E+09 | 52961237.75 | 60176339.66 | 0.00 | 0.00 |
Maximum of Months | 0.741440E+09 | 0.458113E+09 | 0.414840E+09 | 0.240961E+09 | 0.215171E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.343418E+09 | 0.387946E+09 | 0.248230E+09 | 0.162882E+09 | 85348230.30 | 0.00 | 0.00 |
February | 0.390483E+09 | 0.335516E+09 | 0.270893E+09 | 0.166831E+09 | 0.104062E+09 | 0.00 | 0.00 |
March | 0.210701E+09 | 0.314162E+09 | 0.182498E+09 | 52961237.75 | 0.129537E+09 | 0.00 | 0.00 |
April | 0.611079E+09 | 0.254808E+09 | 0.359175E+09 | 0.157923E+09 | 0.201253E+09 | 0.00 | 0.00 |
May | 0.480951E+09 | 0.226613E+09 | 0.302872E+09 | 91189050.98 | 0.211682E+09 | 0.00 | 0.00 |
June | 0.441428E+09 | 0.178499E+09 | 0.269953E+09 | 57871905.41 | 0.212081E+09 | 0.00 | 0.00 |
July | 0.526885E+09 | 0.179051E+09 | 0.301254E+09 | 86083361.15 | 0.215171E+09 | 0.00 | 0.00 |
August | 0.654246E+09 | 0.200496E+09 | 0.355842E+09 | 0.153882E+09 | 0.201960E+09 | 0.00 | 0.00 |
September | 0.747113E+09 | 0.239889E+09 | 0.414840E+09 | 0.240961E+09 | 0.173879E+09 | 0.00 | 0.00 |
October | 0.479582E+09 | 0.294770E+09 | 0.300823E+09 | 0.176973E+09 | 0.123850E+09 | 0.00 | 0.00 |
November | 0.294250E+09 | 0.341280E+09 | 0.209128E+09 | 0.129032E+09 | 80095766.35 | 0.00 | 0.00 |
December | 0.228831E+09 | 0.437137E+09 | 0.172251E+09 | 0.112075E+09 | 60176339.66 | 0.00 | 0.00 |
Annual Sum or Average | 0.540897E+10 | 0.339017E+10 | 0.338776E+10 | 0.158866E+10 | 0.179910E+10 | 0.00 | 0.00 |
Minimum of Months | 0.210701E+09 | 0.178499E+09 | 0.172251E+09 | 52961237.75 | 60176339.66 | 0.00 | 0.00 |
Maximum of Months | 0.747113E+09 | 0.437137E+09 | 0.414840E+09 | 0.240961E+09 | 0.215171E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.362772E+09 | -238919066.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123853312.0 | 58.99 | 0.00 | 0.00 |
February | 0.330398E+09 | -218404024.8 | 0.00 | 0.00 | 672.00 | 0.00 | -111994252.5 | 58.99 | 0.00 | 0.00 |
March | 0.367811E+09 | -244116309.6 | 0.00 | 0.00 | 744.00 | 0.00 | -123695164.1 | 58.99 | 0.00 | 0.00 |
April | 0.346364E+09 | -228766010.5 | 0.00 | 0.00 | 720.00 | 0.00 | -117598358.2 | 58.99 | 0.00 | 0.00 |
May | 0.350872E+09 | -230440964.7 | 0.00 | 0.00 | 744.00 | 0.00 | -120430904.6 | 58.99 | 0.00 | 0.00 |
June | 0.331270E+09 | -219061143.9 | 0.00 | 0.00 | 720.00 | 0.00 | -112208407.0 | 58.99 | 0.00 | 0.00 |
July | 0.331516E+09 | -217090895.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114424857.0 | 58.99 | 0.00 | 0.00 |
August | 0.333760E+09 | -219928929.5 | 0.00 | 0.00 | 744.00 | 0.00 | -113831187.1 | 58.99 | 0.00 | 0.00 |
September | 0.323399E+09 | -212067506.1 | 0.00 | 0.00 | 720.00 | 0.00 | -111331586.3 | 58.99 | 0.00 | 0.00 |
October | 0.343183E+09 | -221708310.0 | 0.00 | 0.00 | 744.00 | 0.00 | -121474887.7 | 58.99 | 0.00 | 0.00 |
November | 0.339474E+09 | -220046192.5 | 0.00 | 0.00 | 720.00 | 0.00 | -119428009.9 | 58.99 | 0.00 | 0.00 |
December | 0.358714E+09 | -234599807.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124113742.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.411953E+10 | -0.270515E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141438E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.323399E+09 | -244116309.6 | 0.00 | 0.00 | 672.00 | 0.00 | -124113742.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.367811E+09 | -212067506.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111331586.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.361155E+09 | -238921885.2 | 0.00 | 0.00 | 744.00 | 0.00 | -122233397.9 | 58.99 | 0.00 | 0.00 |
February | 0.328891E+09 | -218400578.0 | 0.00 | 0.00 | 672.00 | 0.00 | -110490120.9 | 58.99 | 0.00 | 0.00 |
March | 0.365982E+09 | -244118005.5 | 0.00 | 0.00 | 744.00 | 0.00 | -121863717.9 | 58.99 | 0.00 | 0.00 |
April | 0.342864E+09 | -228768876.1 | 0.00 | 0.00 | 720.00 | 0.00 | -114095556.1 | 58.99 | 0.00 | 0.00 |
May | 0.347084E+09 | -230433686.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116650251.8 | 58.99 | 0.00 | 0.00 |
June | 0.329166E+09 | -219061680.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110104216.9 | 58.99 | 0.00 | 0.00 |
July | 0.330427E+09 | -217086786.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113340262.4 | 58.99 | 0.00 | 0.00 |
August | 0.333141E+09 | -219930443.5 | 0.00 | 0.00 | 744.00 | 0.00 | -113210168.3 | 58.99 | 0.00 | 0.00 |
September | 0.321964E+09 | -212074861.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109889620.5 | 58.99 | 0.00 | 0.00 |
October | 0.339434E+09 | -221709394.9 | 0.00 | 0.00 | 744.00 | 0.00 | -117724578.6 | 58.99 | 0.00 | 0.00 |
November | 0.337529E+09 | -220045872.5 | 0.00 | 0.00 | 720.00 | 0.00 | -117483167.9 | 58.99 | 0.00 | 0.00 |
December | 0.357159E+09 | -234596241.9 | 0.00 | 0.00 | 744.00 | 0.00 | -122563169.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.409480E+10 | -0.270515E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138965E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.321964E+09 | -244118005.5 | 0.00 | 0.00 | 672.00 | 0.00 | -122563169.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.365982E+09 | -212074861.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109889620.5 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.333756E+09 | -210105611.3 | 0.00 | 0.00 | 744.00 | 0.00 | -123649933.1 | 58.99 | 0.00 | 0.00 |
February | 0.303920E+09 | -192216922.7 | 0.00 | 0.00 | 672.00 | 0.00 | -111703514.0 | 58.99 | 0.00 | 0.00 |
March | 0.341011E+09 | -217871775.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123139362.2 | 58.99 | 0.00 | 0.00 |
April | 0.316046E+09 | -201214303.1 | 0.00 | 0.00 | 720.00 | 0.00 | -114831531.9 | 58.98 | 0.00 | 0.00 |
May | 0.321518E+09 | -204365535.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117152738.7 | 58.99 | 0.00 | 0.00 |
June | 0.304918E+09 | -195098379.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109819438.8 | 58.99 | 0.00 | 0.00 |
July | 0.302627E+09 | -189801339.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112825287.2 | 58.99 | 0.00 | 0.00 |
August | 0.309123E+09 | -196439477.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112683222.6 | 58.99 | 0.00 | 0.00 |
September | 0.296037E+09 | -186377292.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109659587.4 | 58.99 | 0.00 | 0.00 |
October | 0.313645E+09 | -194980009.4 | 0.00 | 0.00 | 744.00 | 0.00 | -118664620.7 | 58.99 | 0.00 | 0.00 |
November | 0.313178E+09 | -194261066.7 | 0.00 | 0.00 | 720.00 | 0.00 | -118916833.6 | 59.01 | 0.00 | 0.00 |
December | 0.328754E+09 | -204785961.6 | 0.00 | 0.00 | 744.00 | 0.00 | -123968483.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.378453E+10 | -0.238752E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139701E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.296037E+09 | -217871775.9 | 0.00 | 0.00 | 672.00 | 0.00 | -123968483.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.341011E+09 | -186377292.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109659587.4 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.334106E+09 | -210109845.0 | 0.00 | 0.00 | 744.00 | 0.00 | -123995756.9 | 58.99 | 0.00 | 0.00 |
February | 0.304208E+09 | -192209316.6 | 0.00 | 0.00 | 672.00 | 0.00 | -111998559.5 | 58.99 | 0.00 | 0.00 |
March | 0.341342E+09 | -217879294.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123462763.0 | 58.99 | 0.00 | 0.00 |
April | 0.316551E+09 | -201209757.0 | 0.00 | 0.00 | 720.00 | 0.00 | -115341547.6 | 58.99 | 0.00 | 0.00 |
May | 0.322026E+09 | -204351984.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117674242.6 | 58.99 | 0.00 | 0.00 |
June | 0.305105E+09 | -195107856.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109997415.3 | 58.99 | 0.00 | 0.00 |
July | 0.302744E+09 | -189803776.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112940094.1 | 58.99 | 0.00 | 0.00 |
August | 0.309190E+09 | -196439578.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112750555.3 | 58.99 | 0.00 | 0.00 |
September | 0.296181E+09 | -186375501.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109805715.6 | 58.99 | 0.00 | 0.00 |
October | 0.314174E+09 | -194972435.7 | 0.00 | 0.00 | 744.00 | 0.00 | -119201211.9 | 59.00 | 0.00 | 0.00 |
November | 0.313535E+09 | -194303025.8 | 0.00 | 0.00 | 720.00 | 0.00 | -119231548.3 | 58.99 | 0.00 | 0.00 |
December | 0.329085E+09 | -204775294.4 | 0.00 | 0.00 | 744.00 | 0.00 | -124309396.7 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378825E+10 | -0.238754E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140071E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.296181E+09 | -217879294.4 | 0.00 | 0.00 | 672.00 | 0.00 | -124309396.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.341342E+09 | -186375501.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109805715.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.323788E+09 | -198584232.7 | 0.00 | 0.00 | 744.00 | 0.00 | -125203835.7 | 58.99 | 0.00 | 0.00 |
February | 0.294852E+09 | -181740025.0 | 0.00 | 0.00 | 672.00 | 0.00 | -113111683.6 | 59.00 | 0.00 | 0.00 |
March | 0.330811E+09 | -206149533.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124661200.4 | 59.00 | 0.00 | 0.00 |
April | 0.308577E+09 | -190392040.7 | 0.00 | 0.00 | 720.00 | 0.00 | -118184990.1 | 58.99 | 0.00 | 0.00 |
May | 0.314317E+09 | -193261542.0 | 0.00 | 0.00 | 744.00 | 0.00 | -121055301.1 | 58.99 | 0.00 | 0.00 |
June | 0.297346E+09 | -184607661.3 | 0.00 | 0.00 | 720.00 | 0.00 | -112737875.3 | 58.99 | 0.00 | 0.00 |
July | 0.294018E+09 | -179510693.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114507487.8 | 58.99 | 0.00 | 0.00 |
August | 0.299590E+09 | -185872781.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113717597.2 | 58.99 | 0.00 | 0.00 |
September | 0.288106E+09 | -176367470.3 | 0.00 | 0.00 | 720.00 | 0.00 | -111738284.6 | 58.99 | 0.00 | 0.00 |
October | 0.306545E+09 | -184272607.4 | 0.00 | 0.00 | 744.00 | 0.00 | -122272618.7 | 59.00 | 0.00 | 0.00 |
November | 0.303966E+09 | -183512017.8 | 0.00 | 0.00 | 720.00 | 0.00 | -120454223.1 | 58.99 | 0.00 | 0.00 |
December | 0.319200E+09 | -193676529.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125523805.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.368112E+10 | -0.225795E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.142317E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.288106E+09 | -206149533.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125523805.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.330811E+09 | -176367470.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111738284.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.323745E+09 | -198584534.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125160812.8 | 58.99 | 0.00 | 0.00 |
February | 0.294816E+09 | -181731442.6 | 0.00 | 0.00 | 672.00 | 0.00 | -113084887.5 | 59.01 | 0.00 | 0.00 |
March | 0.330787E+09 | -206151389.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124635343.9 | 59.00 | 0.00 | 0.00 |
April | 0.308369E+09 | -190403101.9 | 0.00 | 0.00 | 720.00 | 0.00 | -117965435.1 | 58.99 | 0.00 | 0.00 |
May | 0.313992E+09 | -193267535.5 | 0.00 | 0.00 | 744.00 | 0.00 | -120724005.2 | 58.99 | 0.00 | 0.00 |
June | 0.296823E+09 | -184612524.2 | 0.00 | 0.00 | 720.00 | 0.00 | -112210279.8 | 58.99 | 0.00 | 0.00 |
July | 0.293783E+09 | -179512994.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114270065.0 | 58.99 | 0.00 | 0.00 |
August | 0.299509E+09 | -185850070.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113659246.2 | 59.00 | 0.00 | 0.00 |
September | 0.287618E+09 | -176375374.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111242185.2 | 58.99 | 0.00 | 0.00 |
October | 0.306259E+09 | -184289518.4 | 0.00 | 0.00 | 744.00 | 0.00 | -121969203.0 | 58.99 | 0.00 | 0.00 |
November | 0.303946E+09 | -183508757.3 | 0.00 | 0.00 | 720.00 | 0.00 | -120437247.3 | 58.99 | 0.00 | 0.00 |
December | 0.319127E+09 | -193685133.4 | 0.00 | 0.00 | 744.00 | 0.00 | -125442104.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.367877E+10 | -0.225797E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.142080E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.287618E+09 | -206151389.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125442104.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.330787E+09 | -176375374.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111242185.2 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.323825E+09 | -198584277.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125240628.3 | 58.99 | 0.00 | 0.00 |
February | 0.294891E+09 | -181750211.5 | 0.00 | 0.00 | 672.00 | 0.00 | -113140774.3 | 59.00 | 0.00 | 0.00 |
March | 0.330870E+09 | -206149028.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124721277.3 | 59.00 | 0.00 | 0.00 |
April | 0.308531E+09 | -190389163.1 | 0.00 | 0.00 | 720.00 | 0.00 | -118141539.2 | 58.99 | 0.00 | 0.00 |
May | 0.314190E+09 | -193261347.7 | 0.00 | 0.00 | 744.00 | 0.00 | -120928952.0 | 58.99 | 0.00 | 0.00 |
June | 0.297046E+09 | -184606385.5 | 0.00 | 0.00 | 720.00 | 0.00 | -112439312.4 | 58.99 | 0.00 | 0.00 |
July | 0.293922E+09 | -179493927.2 | 0.00 | 0.00 | 744.00 | 0.00 | -114427628.3 | 58.99 | 0.00 | 0.00 |
August | 0.299598E+09 | -185860745.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113737639.0 | 59.00 | 0.00 | 0.00 |
September | 0.287746E+09 | -176375736.4 | 0.00 | 0.00 | 720.00 | 0.00 | -111370532.3 | 58.99 | 0.00 | 0.00 |
October | 0.306436E+09 | -184291157.7 | 0.00 | 0.00 | 744.00 | 0.00 | -122144594.4 | 58.99 | 0.00 | 0.00 |
November | 0.304029E+09 | -183506317.6 | 0.00 | 0.00 | 720.00 | 0.00 | -120522968.7 | 58.99 | 0.00 | 0.00 |
December | 0.319193E+09 | -193690993.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125501518.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.368028E+10 | -0.225796E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.142232E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.287746E+09 | -206149028.1 | 0.00 | 0.00 | 672.00 | 0.00 | -125501518.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.330870E+09 | -176375736.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111370532.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 195.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 215.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 417.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 410.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 234.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 171.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.968490E+10 | 45490.43 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.814031E+10 | 45490.43 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.724766E+10 | 45490.43 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171539E+10 | 45490.43 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.963134E+09 | 45490.43 | 05-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5840818.13 | 8153.41 | 08-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185363E+10 | 45490.43 | 19-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.620047E+10 | 45490.43 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104963E+11 | 45490.43 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.463077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104963E+11 | 45490.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.239864E+10 | 25004.35 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181654E+10 | 25004.35 | 02-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139085E+10 | 25004.35 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72068134.76 | 20137.11 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3292911.05 | 457.69 | 17-MAY-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 69271608.44 | 8134.65 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111346E+10 | 25004.35 | 03-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270429E+10 | 25004.35 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.956840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.270429E+10 | 25004.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.270708E+10 | 28150.70 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.207603E+10 | 28150.70 | 12-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162043E+10 | 28150.70 | 04-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128815E+09 | 13750.60 | 02-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2572344.97 | 426.13 | 17-MAY-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116760E+09 | 8740.71 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134264E+10 | 28150.70 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.298974E+10 | 28150.70 | 03-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.298974E+10 | 28150.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.290435E+10 | 28124.91 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224234E+10 | 28124.91 | 12-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178656E+10 | 28124.91 | 04-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178416E+09 | 17683.78 | 02-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9205007.31 | 1780.67 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178653E+09 | 13001.71 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151446E+10 | 28124.91 | 19-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.317280E+10 | 28124.91 | 03-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.317280E+10 | 28124.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.322478E+10 | 28073.45 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.252859E+10 | 28073.45 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208663E+10 | 28073.45 | 03-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.277057E+09 | 22272.62 | 02-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 50110552.21 | 4612.78 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.305869E+09 | 17428.19 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179976E+10 | 28073.45 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348719E+10 | 28073.45 | 01-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.348719E+10 | 28073.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.886301E+10 | 45387.28 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.724428E+10 | 45387.28 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.670546E+10 | 45387.28 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186274E+10 | 45387.28 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112650E+10 | 45387.28 | 05-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21755053.60 | 8410.32 | 08-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.216059E+10 | 45387.28 | 15-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.603663E+10 | 45387.28 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.936172E+10 | 45387.28 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.433827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.936172E+10 | 45387.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.406529E+10 | 23881.93 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327084E+10 | 23881.93 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.291012E+10 | 23881.93 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.631765E+09 | 23881.93 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.329543E+09 | 23881.93 | 05-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1917840.91 | 4375.39 | 08-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.755203E+09 | 23881.93 | 15-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.258526E+10 | 23881.93 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.433109E+10 | 23881.93 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.433109E+10 | 23881.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.414780E+10 | 23668.96 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.334758E+10 | 23668.96 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.299427E+10 | 23668.96 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.686418E+09 | 23668.96 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.378370E+09 | 23668.96 | 05-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3689189.95 | 6978.63 | 08-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.810654E+09 | 23668.96 | 15-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.266285E+10 | 23668.96 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.440649E+10 | 23668.96 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.440649E+10 | 23668.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.452027E+10 | 23271.48 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.369176E+10 | 23271.48 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.335457E+10 | 23271.48 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.895206E+09 | 23271.48 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.559069E+09 | 23271.48 | 05-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16509186.68 | 16150.07 | 08-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101841E+10 | 23271.48 | 14-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297983E+10 | 23271.48 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.477514E+10 | 23271.48 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.477514E+10 | 23271.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.586109E+10 | 23916.67 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.490883E+10 | 23916.67 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.460372E+10 | 23916.67 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144791E+10 | 23916.67 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107967E+10 | 23916.67 | 02-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76132685.51 | 23916.67 | 06-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7545132.49 | 10742.80 | 05-JUL-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9374596.28 | 4428.45 | 07-SEP-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165325E+10 | 23916.67 | 04-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.399722E+10 | 23916.67 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.616802E+10 | 23916.67 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.616802E+10 | 23916.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.204577E+09 | 0.203814E+09 | 7713.69 | 30-APR-16:20 | 7713.69 | 0.00 |
May | 0.00 | 0.00 | 83370147.05 | 72914882.77 | 5719.03 | 22-MAY-15:00 | 5158.99 | 0.00 |
June | 0.00 | 0.00 | 0.105041E+10 | 0.861964E+09 | 11463.49 | 13-JUN-17:00 | 10298.31 | 0.00 |
July | 0.00 | 0.00 | 0.178717E+10 | 0.153080E+10 | 12394.90 | 22-JUL-16:20 | 12394.90 | 0.00 |
August | 0.00 | 0.00 | 0.148642E+10 | 0.123168E+10 | 10155.15 | 14-AUG-17:00 | 10155.15 | 0.00 |
September | 0.00 | 0.00 | 0.792907E+09 | 0.666842E+09 | 8018.60 | 13-SEP-16:10 | 6821.43 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.540485E+10 | 0.456801E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.178717E+10 | 0.153080E+10 | 12394.90 | 12394.90 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.152611E+09 | 0.151807E+09 | 13508.92 | 30-APR-19:10 | 13508.92 | 0.00 |
May | 0.00 | 0.00 | 70354702.35 | 66666270.35 | 13594.98 | 21-MAY-18:11 | 13480.14 | 0.00 |
June | 0.00 | 0.00 | 0.618744E+09 | 0.535710E+09 | 14917.82 | 25-JUN-17:53 | 8637.83 | 0.00 |
July | 0.00 | 0.00 | 0.950419E+09 | 0.860095E+09 | 14324.74 | 23-JUL-17:02 | 10304.98 | 0.00 |
August | 0.00 | 0.00 | 0.747604E+09 | 0.660257E+09 | 13904.34 | 13-AUG-17:02 | 10476.12 | 0.00 |
September | 0.00 | 0.00 | 0.453493E+09 | 0.399123E+09 | 14221.87 | 10-SEP-17:02 | 9371.70 | 0.00 |
October | 0.00 | 0.00 | 2522038.68 | 2196889.61 | 1400.33 | 12-OCT-20:20 | 1218.83 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.299575E+10 | 0.267586E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.950419E+09 | 0.860095E+09 | 14917.82 | 13508.92 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 61128946.27 | 61118996.62 | 4638.48 | 30-APR-15:00 | 4638.48 | 0.00 |
May | 0.00 | 0.00 | 43456296.68 | 40882269.27 | 3967.01 | 22-MAY-15:00 | 3766.72 | 0.00 |
June | 0.00 | 0.00 | 0.509501E+09 | 0.447747E+09 | 6652.60 | 13-JUN-17:00 | 6132.15 | 0.00 |
July | 0.00 | 0.00 | 0.672864E+09 | 0.625617E+09 | 7245.38 | 22-JUL-13:00 | 7186.39 | 0.00 |
August | 0.00 | 0.00 | 0.561191E+09 | 0.500922E+09 | 6010.88 | 14-AUG-17:00 | 6010.88 | 0.00 |
September | 0.00 | 0.00 | 0.353132E+09 | 0.315961E+09 | 4559.00 | 13-SEP-16:10 | 4072.07 | 0.00 |
October | 0.00 | 0.00 | 941.64 | 940.50 | 0.16 | 11-OCT-11:20 | 0.16 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.220127E+10 | 0.199225E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.672864E+09 | 0.625617E+09 | 7245.38 | 7186.39 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 58094710.77 | 58094684.34 | 4548.55 | 30-APR-15:00 | 4548.55 | 0.00 |
May | 0.00 | 0.00 | 39779591.37 | 37455251.95 | 3783.04 | 22-MAY-15:00 | 3590.71 | 0.00 |
June | 0.00 | 0.00 | 0.496705E+09 | 0.436359E+09 | 6588.01 | 13-JUN-17:00 | 6070.48 | 0.00 |
July | 0.00 | 0.00 | 0.662452E+09 | 0.616091E+09 | 7230.11 | 22-JUL-13:00 | 7171.09 | 0.00 |
August | 0.00 | 0.00 | 0.547874E+09 | 0.489034E+09 | 5965.24 | 14-AUG-17:00 | 5965.24 | 0.00 |
September | 0.00 | 0.00 | 0.339631E+09 | 0.304001E+09 | 4515.56 | 13-SEP-16:10 | 4032.89 | 0.00 |
October | 0.00 | 0.00 | 1625.10 | 1625.10 | 0.28 | 11-OCT-11:20 | 0.28 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.214454E+10 | 0.194104E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.662452E+09 | 0.616091E+09 | 7230.11 | 7171.09 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 50585792.60 | 50585782.65 | 4273.57 | 30-APR-15:00 | 4273.57 | 0.00 |
May | 0.00 | 0.00 | 33080740.91 | 31182563.70 | 3405.45 | 22-MAY-15:00 | 3229.92 | 0.00 |
June | 0.00 | 0.00 | 0.454657E+09 | 0.399340E+09 | 6367.14 | 13-JUN-17:00 | 5859.90 | 0.00 |
July | 0.00 | 0.00 | 0.612205E+09 | 0.570703E+09 | 7082.28 | 22-JUL-13:00 | 7021.86 | 0.00 |
August | 0.00 | 0.00 | 0.492942E+09 | 0.441108E+09 | 5810.95 | 14-AUG-17:00 | 5810.95 | 0.00 |
September | 0.00 | 0.00 | 0.293888E+09 | 0.263475E+09 | 4327.95 | 13-SEP-16:10 | 3864.28 | 0.00 |
October | 0.00 | 0.00 | 507.56 | 507.56 | 0.19 | 11-OCT-10:50 | 0.19 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.193736E+10 | 0.175639E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.612205E+09 | 0.570703E+09 | 7082.28 | 7021.86 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 86538624.07 | 86061563.24 | 6618.42 | 30-APR-15:00 | 6618.42 | 0.00 |
May | 0.00 | 0.00 | 46776883.10 | 41582275.02 | 5141.48 | 22-MAY-15:00 | 4549.27 | 0.00 |
June | 0.00 | 0.00 | 0.754049E+09 | 0.625319E+09 | 10305.84 | 13-JUN-17:00 | 9119.80 | 0.00 |
July | 0.00 | 0.00 | 0.118914E+10 | 0.103557E+10 | 12555.45 | 22-JUL-15:00 | 12555.45 | 0.00 |
August | 0.00 | 0.00 | 0.117240E+10 | 0.972664E+09 | 9268.74 | 14-AUG-17:00 | 9268.74 | 0.00 |
September | 0.00 | 0.00 | 0.592542E+09 | 0.505368E+09 | 7553.25 | 13-SEP-14:40 | 6301.45 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.384145E+10 | 0.326656E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.118914E+10 | 0.103557E+10 | 12555.45 | 12555.45 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 42127039.31 | 42127039.31 | 3946.14 | 30-APR-15:00 | 3946.14 | 0.00 |
May | 0.00 | 0.00 | 25476258.00 | 23803408.06 | 3044.51 | 22-MAY-15:00 | 2824.17 | 0.00 |
June | 0.00 | 0.00 | 0.391328E+09 | 0.339359E+09 | 5769.61 | 13-JUN-17:00 | 5220.08 | 0.00 |
July | 0.00 | 0.00 | 0.547728E+09 | 0.505990E+09 | 6995.75 | 22-JUL-15:00 | 6995.75 | 0.00 |
August | 0.00 | 0.00 | 0.475923E+09 | 0.420280E+09 | 5332.00 | 14-AUG-17:00 | 5332.00 | 0.00 |
September | 0.00 | 0.00 | 0.258932E+09 | 0.231504E+09 | 4050.61 | 13-SEP-14:40 | 3540.29 | 0.00 |
October | 0.00 | 0.00 | 13920.95 | 13920.95 | 23.20 | 07-OCT-13:40 | 23.20 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.174153E+10 | 0.156308E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.547728E+09 | 0.505990E+09 | 6995.75 | 6995.75 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 40460448.78 | 40460448.78 | 3865.76 | 30-APR-15:00 | 3865.76 | 0.00 |
May | 0.00 | 0.00 | 24173540.31 | 22588735.84 | 2950.66 | 22-MAY-15:00 | 2736.44 | 0.00 |
June | 0.00 | 0.00 | 0.377505E+09 | 0.327355E+09 | 5671.99 | 13-JUN-17:00 | 5130.50 | 0.00 |
July | 0.00 | 0.00 | 0.533106E+09 | 0.492948E+09 | 6932.89 | 22-JUL-15:00 | 6932.89 | 0.00 |
August | 0.00 | 0.00 | 0.460625E+09 | 0.407092E+09 | 5259.73 | 14-AUG-17:00 | 5259.73 | 0.00 |
September | 0.00 | 0.00 | 0.248259E+09 | 0.222055E+09 | 3975.71 | 13-SEP-14:40 | 3474.41 | 0.00 |
October | 0.00 | 0.00 | 4923.58 | 4923.58 | 8.21 | 07-OCT-16:10 | 8.21 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168413E+10 | 0.151250E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.533106E+09 | 0.492948E+09 | 6932.89 | 6932.89 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 36098232.14 | 36098232.14 | 3643.52 | 30-APR-15:00 | 3643.52 | 0.00 |
May | 0.00 | 0.00 | 20827073.81 | 19466823.09 | 2724.20 | 22-MAY-15:00 | 2524.91 | 0.00 |
June | 0.00 | 0.00 | 0.340469E+09 | 0.295194E+09 | 5439.14 | 13-JUN-17:00 | 4916.24 | 0.00 |
July | 0.00 | 0.00 | 0.493194E+09 | 0.457508E+09 | 6790.43 | 22-JUL-15:00 | 6790.43 | 0.00 |
August | 0.00 | 0.00 | 0.411994E+09 | 0.365148E+09 | 5056.57 | 14-AUG-17:00 | 5056.57 | 0.00 |
September | 0.00 | 0.00 | 0.213304E+09 | 0.190865E+09 | 3769.34 | 13-SEP-14:40 | 3293.02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.151589E+10 | 0.136428E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.493194E+09 | 0.457508E+09 | 6790.43 | 6790.43 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 33936532.94 | 33936532.94 | 3435.80 | 30-APR-15:00 | 3435.80 | 0.00 |
May | 0.00 | 0.00 | 18208865.81 | 17023045.09 | 2521.27 | 22-MAY-15:00 | 2336.24 | 0.00 |
June | 0.00 | 0.00 | 0.318176E+09 | 0.276175E+09 | 5327.46 | 13-JUN-17:00 | 4812.04 | 0.00 |
July | 0.00 | 0.00 | 0.480950E+09 | 0.447802E+09 | 6828.73 | 22-JUL-15:00 | 6828.73 | 0.00 |
August | 0.00 | 0.00 | 0.365888E+09 | 0.325625E+09 | 4872.99 | 14-AUG-17:00 | 4872.99 | 0.00 |
September | 0.00 | 0.00 | 0.182115E+09 | 0.162337E+09 | 3614.42 | 13-SEP-14:20 | 3160.42 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.139927E+10 | 0.126290E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.480950E+09 | 0.447802E+09 | 6828.73 | 6828.73 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133241E+10 | 0.41 | 1560.06 | 01-JAN-08:61 | 0.89 |
February | 0.119253E+10 | 0.40 | 1560.06 | 01-FEB-08:61 | 0.88 |
March | 0.128645E+10 | 0.40 | 1560.06 | 01-MAR-08:61 | 0.88 |
April | 0.113159E+10 | 0.37 | 1560.06 | 01-APR-07:01 | 0.89 |
May | 0.115205E+10 | 0.37 | 1560.06 | 05-MAY-07:01 | 0.89 |
June | 0.110090E+10 | 0.36 | 791.80 | 08-JUN-07:02 | 0.62 |
July | 0.113243E+10 | 0.36 | 677.65 | 22-JUL-16:20 | 0.56 |
August | 0.113448E+10 | 0.36 | 624.03 | 25-AUG-19:50 | 0.53 |
September | 0.109853E+10 | 0.36 | 624.03 | 09-SEP-14:30 | 0.53 |
October | 0.117037E+10 | 0.37 | 1560.06 | 19-OCT-07:01 | 0.88 |
November | 0.122197E+10 | 0.39 | 1560.06 | 01-NOV-07:01 | 0.89 |
December | 0.135365E+10 | 0.41 | 1560.06 | 01-DEC-08:61 | 0.89 |
Annual Sum or Average | 0.143074E+11 | 0.38 | |||
Minimum of Months | 0.109853E+10 | 0.36 | 624.03 | 0.53 | |
Maximum of Months | 0.135365E+10 | 0.41 | 1560.06 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.126970E+10 | 0.47 | 935.32 | 01-JAN-09:09 | 0.91 |
February | 0.114820E+10 | 0.46 | 935.32 | 01-FEB-11:40 | 0.91 |
March | 0.128962E+10 | 0.47 | 935.32 | 01-MAR-09:50 | 0.91 |
April | 0.131936E+10 | 0.54 | 935.32 | 01-APR-08:30 | 0.92 |
May | 0.141135E+10 | 0.58 | 935.32 | 17-MAY-15:00 | 0.91 |
June | 0.161463E+10 | 0.62 | 935.32 | 03-JUN-14:50 | 0.91 |
July | 0.166349E+10 | 0.61 | 935.32 | 06-JUL-13:40 | 0.91 |
August | 0.169137E+10 | 0.62 | 935.32 | 15-AUG-08:40 | 0.91 |
September | 0.163072E+10 | 0.62 | 935.32 | 18-SEP-10:30 | 0.91 |
October | 0.132968E+10 | 0.53 | 935.32 | 07-OCT-11:30 | 0.91 |
November | 0.123238E+10 | 0.46 | 935.32 | 01-NOV-11:30 | 0.91 |
December | 0.126274E+10 | 0.46 | 935.32 | 01-DEC-08:15 | 0.91 |
Annual Sum or Average | 0.168633E+11 | 0.54 | |||
Minimum of Months | 0.114820E+10 | 0.46 | 935.32 | 0.91 | |
Maximum of Months | 0.169137E+10 | 0.62 | 935.32 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.155096E+10 | 0.50 | 1071.70 | 01-JAN-08:40 | 0.92 |
February | 0.140435E+10 | 0.50 | 1071.70 | 02-FEB-09:50 | 0.92 |
March | 0.158183E+10 | 0.50 | 1071.70 | 04-MAR-14:20 | 0.92 |
April | 0.150466E+10 | 0.50 | 1071.70 | 02-APR-11:40 | 0.92 |
May | 0.156639E+10 | 0.50 | 1071.70 | 06-MAY-06:05 | 0.92 |
June | 0.152781E+10 | 0.50 | 1071.70 | 20-JUN-16:30 | 0.91 |
July | 0.154324E+10 | 0.49 | 1071.70 | 06-JUL-13:10 | 0.91 |
August | 0.158183E+10 | 0.50 | 1071.70 | 05-AUG-07:50 | 0.91 |
September | 0.150466E+10 | 0.49 | 1071.70 | 09-SEP-14:20 | 0.91 |
October | 0.155096E+10 | 0.49 | 1071.70 | 15-OCT-13:30 | 0.91 |
November | 0.150466E+10 | 0.50 | 1071.70 | 01-NOV-09:40 | 0.92 |
December | 0.154324E+10 | 0.49 | 1071.70 | 01-DEC-10:50 | 0.92 |
Annual Sum or Average | 0.183646E+11 | 0.50 | |||
Minimum of Months | 0.140435E+10 | 0.49 | 1071.70 | 0.91 | |
Maximum of Months | 0.158183E+10 | 0.50 | 1071.70 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154913E+10 | 0.50 | 1070.44 | 02-JAN-21:00 | 0.92 |
February | 0.140270E+10 | 0.50 | 1070.44 | 07-FEB-13:40 | 0.91 |
March | 0.157996E+10 | 0.50 | 1070.44 | 01-MAR-09:50 | 0.92 |
April | 0.150289E+10 | 0.50 | 1070.44 | 04-APR-15:20 | 0.92 |
May | 0.156455E+10 | 0.50 | 1070.44 | 05-MAY-07:50 | 0.92 |
June | 0.152601E+10 | 0.50 | 1070.44 | 09-JUN-14:10 | 0.91 |
July | 0.154143E+10 | 0.49 | 1070.44 | 24-JUL-06:30 | 0.91 |
August | 0.157996E+10 | 0.50 | 1070.44 | 01-AUG-08:50 | 0.91 |
September | 0.150289E+10 | 0.49 | 1070.44 | 11-SEP-07:50 | 0.91 |
October | 0.154913E+10 | 0.49 | 1070.44 | 02-OCT-15:20 | 0.91 |
November | 0.150289E+10 | 0.50 | 1070.44 | 03-NOV-13:20 | 0.92 |
December | 0.154143E+10 | 0.49 | 1070.44 | 01-DEC-20:00 | 0.92 |
Annual Sum or Average | 0.183430E+11 | 0.50 | |||
Minimum of Months | 0.140270E+10 | 0.49 | 1070.44 | 0.91 | |
Maximum of Months | 0.157996E+10 | 0.50 | 1070.44 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154549E+10 | 0.50 | 1067.92 | 01-JAN-09:30 | 0.92 |
February | 0.139940E+10 | 0.50 | 1067.92 | 01-FEB-11:10 | 0.91 |
March | 0.157624E+10 | 0.50 | 1067.92 | 01-MAR-08:07 | 0.92 |
April | 0.149935E+10 | 0.50 | 1067.92 | 01-APR-07:20 | 0.92 |
May | 0.156087E+10 | 0.50 | 1067.92 | 04-MAY-16:20 | 0.91 |
June | 0.152242E+10 | 0.50 | 1067.92 | 12-JUN-13:30 | 0.91 |
July | 0.153780E+10 | 0.49 | 1067.92 | 03-JUL-10:40 | 0.91 |
August | 0.157624E+10 | 0.50 | 1067.92 | 04-AUG-06:10 | 0.91 |
September | 0.149935E+10 | 0.49 | 1067.92 | 01-SEP-15:10 | 0.91 |
October | 0.154549E+10 | 0.49 | 1067.92 | 06-OCT-10:50 | 0.92 |
November | 0.149935E+10 | 0.50 | 1067.92 | 01-NOV-07:20 | 0.92 |
December | 0.153780E+10 | 0.49 | 1067.92 | 02-DEC-08:20 | 0.92 |
Annual Sum or Average | 0.182998E+11 | 0.50 | |||
Minimum of Months | 0.139940E+10 | 0.49 | 1067.92 | 0.91 | |
Maximum of Months | 0.157624E+10 | 0.50 | 1067.92 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.104930E+10 | 0.30 | 1610.83 | 01-JAN-09:01 | 0.89 |
February | 0.933648E+09 | 0.30 | 1610.83 | 01-FEB-08:61 | 0.88 |
March | 0.102192E+10 | 0.30 | 1610.83 | 01-MAR-08:61 | 0.88 |
April | 0.874721E+09 | 0.28 | 1610.83 | 01-APR-07:01 | 0.89 |
May | 0.893837E+09 | 0.27 | 1610.83 | 05-MAY-07:01 | 0.88 |
June | 0.849436E+09 | 0.27 | 823.43 | 08-JUN-07:02 | 0.63 |
July | 0.855964E+09 | 0.26 | 669.97 | 22-JUL-15:00 | 0.55 |
August | 0.879128E+09 | 0.27 | 644.33 | 06-AUG-14:20 | 0.53 |
September | 0.835055E+09 | 0.27 | 644.33 | 11-SEP-18:40 | 0.53 |
October | 0.906580E+09 | 0.28 | 1610.83 | 15-OCT-08:61 | 0.88 |
November | 0.963602E+09 | 0.29 | 1610.83 | 01-NOV-07:01 | 0.89 |
December | 0.105528E+10 | 0.30 | 1610.83 | 01-DEC-08:61 | 0.88 |
Annual Sum or Average | 0.111185E+11 | 0.28 | |||
Minimum of Months | 0.835055E+09 | 0.26 | 644.33 | 0.53 | |
Maximum of Months | 0.105528E+10 | 0.30 | 1610.83 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.117481E+10 | 0.46 | 879.61 | 08-JAN-16:20 | 0.92 |
February | 0.106398E+10 | 0.46 | 879.61 | 04-FEB-14:30 | 0.92 |
March | 0.120014E+10 | 0.47 | 879.61 | 02-MAR-16:20 | 0.92 |
April | 0.113997E+10 | 0.46 | 879.61 | 01-APR-07:02 | 0.92 |
May | 0.118747E+10 | 0.46 | 879.61 | 04-MAY-09:30 | 0.91 |
June | 0.115897E+10 | 0.46 | 879.61 | 21-JUN-11:30 | 0.91 |
July | 0.116847E+10 | 0.45 | 879.61 | 21-JUL-16:40 | 0.91 |
August | 0.120014E+10 | 0.46 | 879.61 | 10-AUG-15:10 | 0.91 |
September | 0.113997E+10 | 0.46 | 879.61 | 11-SEP-13:20 | 0.91 |
October | 0.117481E+10 | 0.46 | 879.61 | 13-OCT-16:50 | 0.91 |
November | 0.113997E+10 | 0.46 | 879.61 | 01-NOV-18:00 | 0.91 |
December | 0.116847E+10 | 0.45 | 879.61 | 01-DEC-13:50 | 0.92 |
Annual Sum or Average | 0.139172E+11 | 0.46 | |||
Minimum of Months | 0.106398E+10 | 0.45 | 879.61 | 0.91 | |
Maximum of Months | 0.120014E+10 | 0.47 | 879.61 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116269E+10 | 0.46 | 870.54 | 04-JAN-09:40 | 0.92 |
February | 0.105300E+10 | 0.46 | 870.54 | 01-FEB-10:20 | 0.91 |
March | 0.118776E+10 | 0.47 | 870.54 | 06-MAR-13:20 | 0.91 |
April | 0.112821E+10 | 0.46 | 870.54 | 03-APR-11:15 | 0.92 |
May | 0.117522E+10 | 0.46 | 870.54 | 03-MAY-09:50 | 0.91 |
June | 0.114702E+10 | 0.46 | 870.54 | 01-JUN-07:03 | 0.91 |
July | 0.115642E+10 | 0.45 | 870.54 | 22-JUL-16:50 | 0.91 |
August | 0.118776E+10 | 0.46 | 870.54 | 21-AUG-15:00 | 0.91 |
September | 0.112821E+10 | 0.46 | 870.54 | 10-SEP-12:10 | 0.91 |
October | 0.116269E+10 | 0.46 | 870.54 | 12-OCT-08:40 | 0.91 |
November | 0.112821E+10 | 0.46 | 870.54 | 02-NOV-10:30 | 0.91 |
December | 0.115642E+10 | 0.45 | 870.54 | 04-DEC-18:10 | 0.91 |
Annual Sum or Average | 0.137736E+11 | 0.46 | |||
Minimum of Months | 0.105300E+10 | 0.45 | 870.54 | 0.91 | |
Maximum of Months | 0.118776E+10 | 0.47 | 870.54 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.114085E+10 | 0.46 | 854.19 | 01-JAN-09:04 | 0.92 |
February | 0.103322E+10 | 0.46 | 854.19 | 01-FEB-09:40 | 0.92 |
March | 0.116545E+10 | 0.47 | 854.19 | 02-MAR-18:40 | 0.92 |
April | 0.110703E+10 | 0.46 | 854.19 | 01-APR-13:20 | 0.92 |
May | 0.115315E+10 | 0.46 | 854.19 | 03-MAY-10:20 | 0.91 |
June | 0.112548E+10 | 0.46 | 854.19 | 07-JUN-15:20 | 0.91 |
July | 0.113470E+10 | 0.45 | 854.19 | 06-JUL-14:30 | 0.91 |
August | 0.116545E+10 | 0.46 | 854.19 | 06-AUG-09:50 | 0.91 |
September | 0.110703E+10 | 0.46 | 854.19 | 01-SEP-07:10 | 0.91 |
October | 0.114085E+10 | 0.46 | 854.19 | 06-OCT-08:40 | 0.92 |
November | 0.110703E+10 | 0.46 | 854.19 | 01-NOV-07:10 | 0.92 |
December | 0.113470E+10 | 0.45 | 854.19 | 02-DEC-11:40 | 0.91 |
Annual Sum or Average | 0.135149E+11 | 0.46 | |||
Minimum of Months | 0.103322E+10 | 0.45 | 854.19 | 0.91 | |
Maximum of Months | 0.116545E+10 | 0.47 | 854.19 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.115453E+10 | 0.46 | 864.42 | 23-JAN-19:30 | 0.91 |
February | 0.104561E+10 | 0.46 | 864.42 | 17-FEB-11:40 | 0.92 |
March | 0.117942E+10 | 0.47 | 864.42 | 01-MAR-08:08 | 0.92 |
April | 0.112029E+10 | 0.46 | 864.42 | 03-APR-14:30 | 0.92 |
May | 0.116697E+10 | 0.46 | 864.42 | 04-MAY-14:10 | 0.91 |
June | 0.113897E+10 | 0.46 | 864.42 | 01-JUN-07:30 | 0.91 |
July | 0.114830E+10 | 0.45 | 864.42 | 03-JUL-07:03 | 0.91 |
August | 0.117942E+10 | 0.46 | 864.42 | 04-AUG-19:40 | 0.91 |
September | 0.112029E+10 | 0.46 | 864.42 | 08-SEP-08:20 | 0.91 |
October | 0.115453E+10 | 0.46 | 864.42 | 07-OCT-07:50 | 0.92 |
November | 0.112029E+10 | 0.46 | 864.42 | 05-NOV-12:50 | 0.92 |
December | 0.114830E+10 | 0.45 | 864.42 | 01-DEC-08:08 | 0.92 |
Annual Sum or Average | 0.136769E+11 | 0.46 | |||
Minimum of Months | 0.104561E+10 | 0.45 | 864.42 | 0.91 | |
Maximum of Months | 0.117942E+10 | 0.47 | 864.42 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.133241E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.119253E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.128645E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.118087E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.117296E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.134725E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.156085E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.149593E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.129069E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.117037E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.122197E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.135365E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.156059E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.117037E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.156085E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.126970E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.114820E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.128962E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.135085E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.142606E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.174112E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.186088E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.184886E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.172668E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.133025E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.123238E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.126274E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.174874E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.114820E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.186088E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.155096E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.140435E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.158183E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.151780E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.157590E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.163541E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.168744E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.170335E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.158146E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.155096E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.150466E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.154324E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.188374E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.140435E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.170335E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.154913E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.140270E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.157996E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.151539E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.157330E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.163113E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.168350E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.169873E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.157688E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.154913E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.150289E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.154143E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.188042E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.140270E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.169873E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.154549E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.139940E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.157624E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.151029E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.156822E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.161917E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.166951E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.168338E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.156369E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.154549E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.149935E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.153780E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.187180E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.139940E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.168338E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.104930E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.933648E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.102192E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.896263E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.905748E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.103048E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.114290E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.116587E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.980973E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.906580E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.963602E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.105528E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.120526E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.896263E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.116587E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.117481E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.106398E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.120014E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.114904E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.119312E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.124114E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.128365E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.130207E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.119599E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.117481E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.113997E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.116847E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.142872E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.106398E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.130207E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.116269E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.105300E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.118776E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.113692E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.118059E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.122642E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.126854E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.128649E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.118199E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.116269E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.112821E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.115642E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.141317E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.105300E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.128649E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.114085E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.103322E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.116545E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.111483E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.115780E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.119747E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.123854E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.125406E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.115344E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.114085E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.110703E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.113470E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.138382E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103322E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.125406E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.115453E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.104561E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.117942E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.112769E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.117107E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.120662E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.124918E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.125842E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.116018E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.115453E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.112029E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.114830E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.139759E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.104561E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.125842E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.133241E+10 | 0.00 | 0.968490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119253E+10 | 0.00 | 0.814031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128645E+10 | 0.00 | 0.724766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113159E+10 | 0.204577E+09 | 0.171539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115205E+10 | 83370147.05 | 0.963134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110090E+10 | 0.105041E+10 | 5840818.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113243E+10 | 0.178717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113448E+10 | 0.148642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109853E+10 | 0.792907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117037E+10 | 0.00 | 0.185363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122197E+10 | 0.00 | 0.620047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135365E+10 | 0.00 | 0.104963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143074E+11 | 0.540485E+10 | 0.463077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135365E+10 | 0.178717E+10 | 0.104963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.126970E+10 | 0.00 | 0.239864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114820E+10 | 0.00 | 0.181654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128962E+10 | 0.00 | 0.139085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131936E+10 | 0.152611E+09 | 72068134.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141135E+10 | 70354702.35 | 3292911.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161463E+10 | 0.618744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166349E+10 | 0.950419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169137E+10 | 0.747604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163072E+10 | 0.453493E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132968E+10 | 2522038.68 | 69271608.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123238E+10 | 0.00 | 0.111346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126274E+10 | 0.00 | 0.270429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168633E+11 | 0.299575E+10 | 0.956840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169137E+10 | 0.950419E+09 | 0.270429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.155096E+10 | 0.00 | 0.270708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140435E+10 | 0.00 | 0.207603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158183E+10 | 0.00 | 0.162043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150466E+10 | 61128946.27 | 0.128815E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156639E+10 | 43456296.68 | 2572344.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152781E+10 | 0.509501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154324E+10 | 0.672864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158183E+10 | 0.561191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150466E+10 | 0.353132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155096E+10 | 941.64 | 0.116760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150466E+10 | 0.00 | 0.134264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154324E+10 | 0.00 | 0.298974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183646E+11 | 0.220127E+10 | 0.109841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158183E+10 | 0.672864E+09 | 0.298974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154913E+10 | 0.00 | 0.290435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140270E+10 | 0.00 | 0.224234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157996E+10 | 0.00 | 0.178656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150289E+10 | 58094710.77 | 0.178416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156455E+10 | 39779591.37 | 9205007.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152601E+10 | 0.496705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154143E+10 | 0.662452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157996E+10 | 0.547874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150289E+10 | 0.339631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154913E+10 | 1625.10 | 0.178653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150289E+10 | 0.00 | 0.151446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154143E+10 | 0.00 | 0.317280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183430E+11 | 0.214454E+10 | 0.119868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157996E+10 | 0.662452E+09 | 0.317280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154549E+10 | 0.00 | 0.322478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139940E+10 | 0.00 | 0.252859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157624E+10 | 0.00 | 0.208663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149935E+10 | 50585792.60 | 0.277057E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156087E+10 | 33080740.91 | 50110552.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152242E+10 | 0.454657E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153780E+10 | 0.612205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157624E+10 | 0.492942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149935E+10 | 0.293888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154549E+10 | 507.56 | 0.305869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149935E+10 | 0.00 | 0.179976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153780E+10 | 0.00 | 0.348719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182998E+11 | 0.193736E+10 | 0.137600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157624E+10 | 0.612205E+09 | 0.348719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.104930E+10 | 0.00 | 0.886301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.933648E+09 | 0.00 | 0.724428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102192E+10 | 0.00 | 0.670546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.874721E+09 | 86538624.07 | 0.186274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.893837E+09 | 46776883.10 | 0.112650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.849436E+09 | 0.754049E+09 | 21755053.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.855964E+09 | 0.118914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.879128E+09 | 0.117240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.835055E+09 | 0.592542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.906580E+09 | 0.00 | 0.216059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.963602E+09 | 0.00 | 0.603663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105528E+10 | 0.00 | 0.936172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111185E+11 | 0.384145E+10 | 0.433827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.835055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.105528E+10 | 0.118914E+10 | 0.936172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.117481E+10 | 0.00 | 0.406529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106398E+10 | 0.00 | 0.327084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120014E+10 | 0.00 | 0.291012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113997E+10 | 42127039.31 | 0.631765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118747E+10 | 25476258.00 | 0.329543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115897E+10 | 0.391328E+09 | 1917840.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116847E+10 | 0.547728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.120014E+10 | 0.475923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113997E+10 | 0.258932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117481E+10 | 13920.95 | 0.755203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113997E+10 | 0.00 | 0.258526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116847E+10 | 0.00 | 0.433109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139172E+11 | 0.174153E+10 | 0.188810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.106398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.120014E+10 | 0.547728E+09 | 0.433109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.116269E+10 | 0.00 | 0.414780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105300E+10 | 0.00 | 0.334758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118776E+10 | 0.00 | 0.299427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112821E+10 | 40460448.78 | 0.686418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117522E+10 | 24173540.31 | 0.378370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114702E+10 | 0.377505E+09 | 3689189.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115642E+10 | 0.533106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118776E+10 | 0.460625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112821E+10 | 0.248259E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116269E+10 | 4923.58 | 0.810654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112821E+10 | 0.00 | 0.266285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115642E+10 | 0.00 | 0.440649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137736E+11 | 0.168413E+10 | 0.194381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.105300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118776E+10 | 0.533106E+09 | 0.440649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.114085E+10 | 0.00 | 0.452027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103322E+10 | 0.00 | 0.369176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116545E+10 | 0.00 | 0.335457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110703E+10 | 36098232.14 | 0.895206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115315E+10 | 20827073.81 | 0.559069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112548E+10 | 0.340469E+09 | 16509186.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113470E+10 | 0.493194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116545E+10 | 0.411994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110703E+10 | 0.213304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114085E+10 | 0.00 | 0.101841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110703E+10 | 0.00 | 0.297983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113470E+10 | 0.00 | 0.477514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135149E+11 | 0.151589E+10 | 0.218108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116545E+10 | 0.493194E+09 | 0.477514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.115453E+10 | 0.00 | 0.586109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104561E+10 | 0.00 | 0.490883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117942E+10 | 0.00 | 0.460372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112029E+10 | 33936532.94 | 0.144791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116697E+10 | 18208865.81 | 0.107967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113897E+10 | 0.318176E+09 | 76132685.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114830E+10 | 0.480950E+09 | 7545132.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117942E+10 | 0.365888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112029E+10 | 0.182115E+09 | 9374596.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115453E+10 | 0.00 | 0.165325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112029E+10 | 0.00 | 0.399722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114830E+10 | 0.00 | 0.616802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136769E+11 | 0.139927E+10 | 0.298127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117942E+10 | 0.480950E+09 | 0.616802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.133241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113159E+10 | 0.00 | 0.00 | 0.00 | 49286716.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115205E+10 | 0.00 | 0.00 | 0.00 | 20909881.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110090E+10 | 0.00 | 0.00 | 0.00 | 0.246348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113243E+10 | 0.00 | 0.00 | 0.00 | 0.428416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113448E+10 | 0.00 | 0.00 | 0.00 | 0.361456E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109853E+10 | 0.00 | 0.00 | 0.00 | 0.192159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143074E+11 | 0.00 | 0.00 | 0.00 | 0.129858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135365E+10 | 0.00 | 0.00 | 0.00 | 0.428416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.126970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131936E+10 | 0.00 | 0.00 | 0.00 | 31482330.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141135E+10 | 0.00 | 0.00 | 0.00 | 14705440.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161463E+10 | 0.00 | 0.00 | 0.00 | 0.126497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166349E+10 | 0.00 | 0.00 | 0.00 | 0.197391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169137E+10 | 0.00 | 0.00 | 0.00 | 0.157492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163072E+10 | 0.00 | 0.00 | 0.00 | 95965954.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132968E+10 | 0.00 | 0.00 | 0.00 | 573229.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168633E+11 | 0.00 | 0.00 | 0.00 | 0.624106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169137E+10 | 0.00 | 0.00 | 0.00 | 0.197391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.155096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150466E+10 | 0.00 | 0.00 | 0.00 | 13135617.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156639E+10 | 0.00 | 0.00 | 0.00 | 9505786.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152781E+10 | 0.00 | 0.00 | 0.00 | 0.107598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154324E+10 | 0.00 | 0.00 | 0.00 | 0.144191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158183E+10 | 0.00 | 0.00 | 0.00 | 0.121525E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150466E+10 | 0.00 | 0.00 | 0.00 | 76794333.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155096E+10 | 0.00 | 0.00 | 0.00 | 222.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183646E+11 | 0.00 | 0.00 | 0.00 | 0.472749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158183E+10 | 0.00 | 0.00 | 0.00 | 0.144191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150289E+10 | 0.00 | 0.00 | 0.00 | 12497787.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156455E+10 | 0.00 | 0.00 | 0.00 | 8748201.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152601E+10 | 0.00 | 0.00 | 0.00 | 0.105115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154143E+10 | 0.00 | 0.00 | 0.00 | 0.142069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157996E+10 | 0.00 | 0.00 | 0.00 | 0.118766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150289E+10 | 0.00 | 0.00 | 0.00 | 73988847.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154913E+10 | 0.00 | 0.00 | 0.00 | 383.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183430E+11 | 0.00 | 0.00 | 0.00 | 0.461185E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157996E+10 | 0.00 | 0.00 | 0.00 | 0.142069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149935E+10 | 0.00 | 0.00 | 0.00 | 10933043.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156087E+10 | 0.00 | 0.00 | 0.00 | 7352026.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152242E+10 | 0.00 | 0.00 | 0.00 | 96743627.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153780E+10 | 0.00 | 0.00 | 0.00 | 0.131712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157624E+10 | 0.00 | 0.00 | 0.00 | 0.107138E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149935E+10 | 0.00 | 0.00 | 0.00 | 64339501.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154549E+10 | 0.00 | 0.00 | 0.00 | 119.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182998E+11 | 0.00 | 0.00 | 0.00 | 0.418218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157624E+10 | 0.00 | 0.00 | 0.00 | 0.131712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.104930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.933648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.874721E+09 | 0.00 | 0.00 | 0.00 | 21541212.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.893837E+09 | 0.00 | 0.00 | 0.00 | 11910135.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.849436E+09 | 0.00 | 0.00 | 0.00 | 0.181040E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.855964E+09 | 0.00 | 0.00 | 0.00 | 0.286935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.879128E+09 | 0.00 | 0.00 | 0.00 | 0.286742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.835055E+09 | 0.00 | 0.00 | 0.00 | 0.145917E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.906580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.963602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111185E+11 | 0.00 | 0.00 | 0.00 | 0.934086E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.835055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.105528E+10 | 0.00 | 0.00 | 0.00 | 0.286935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.117481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113997E+10 | 0.00 | 0.00 | 0.00 | 9060856.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118747E+10 | 0.00 | 0.00 | 0.00 | 5645932.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115897E+10 | 0.00 | 0.00 | 0.00 | 82170556.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116847E+10 | 0.00 | 0.00 | 0.00 | 0.115174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.120014E+10 | 0.00 | 0.00 | 0.00 | 0.101927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113997E+10 | 0.00 | 0.00 | 0.00 | 56018914.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117481E+10 | 0.00 | 0.00 | 0.00 | 3271.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139172E+11 | 0.00 | 0.00 | 0.00 | 0.370000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.106398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.120014E+10 | 0.00 | 0.00 | 0.00 | 0.115174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.116269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112821E+10 | 0.00 | 0.00 | 0.00 | 8710469.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117522E+10 | 0.00 | 0.00 | 0.00 | 5367720.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114702E+10 | 0.00 | 0.00 | 0.00 | 79398000.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115642E+10 | 0.00 | 0.00 | 0.00 | 0.112124E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118776E+10 | 0.00 | 0.00 | 0.00 | 98726559.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112821E+10 | 0.00 | 0.00 | 0.00 | 53776031.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116269E+10 | 0.00 | 0.00 | 0.00 | 1155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137736E+11 | 0.00 | 0.00 | 0.00 | 0.358104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.105300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118776E+10 | 0.00 | 0.00 | 0.00 | 0.112124E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.114085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110703E+10 | 0.00 | 0.00 | 0.00 | 7804152.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115315E+10 | 0.00 | 0.00 | 0.00 | 4652365.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112548E+10 | 0.00 | 0.00 | 0.00 | 71993847.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113470E+10 | 0.00 | 0.00 | 0.00 | 0.103840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116545E+10 | 0.00 | 0.00 | 0.00 | 88606400.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110703E+10 | 0.00 | 0.00 | 0.00 | 46411247.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135149E+11 | 0.00 | 0.00 | 0.00 | 0.323308E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116545E+10 | 0.00 | 0.00 | 0.00 | 0.103840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.115453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112029E+10 | 0.00 | 0.00 | 0.00 | 7400581.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116697E+10 | 0.00 | 0.00 | 0.00 | 4100979.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113897E+10 | 0.00 | 0.00 | 0.00 | 67657355.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114830E+10 | 0.00 | 0.00 | 0.00 | 0.100881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117942E+10 | 0.00 | 0.00 | 0.00 | 79003734.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112029E+10 | 0.00 | 0.00 | 0.00 | 39882995.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136769E+11 | 0.00 | 0.00 | 0.00 | 0.298926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117942E+10 | 0.00 | 0.00 | 0.00 | 0.100881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.460586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525089E+10 | 0.00 | 0.00 | 0.34 |
February | 0.428686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444545E+10 | 0.00 | 0.00 | 0.35 |
March | 0.465323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401968E+10 | 0.00 | 0.00 | 0.35 |
April | 0.580275E+10 | 0.00 | 0.00 | 1072632.27 | 964451.15 | 0.469308E+09 | 0.545124E+09 | 0.00 | 0.37 |
May | 0.584466E+10 | 0.00 | 0.00 | 1037207.35 | 0.00 | 0.258457E+09 | 0.801337E+09 | 0.00 | 0.37 |
June | 0.349043E+10 | 43441372.41 | 0.00 | 3940159.65 | 0.00 | 0.00 | 0.269278E+10 | 0.00 | 0.44 |
July | 0.139684E+10 | 56339679.76 | 0.00 | 8948456.23 | 661633.54 | 0.00 | 0.538909E+10 | 0.00 | 0.57 |
August | 0.393372E+09 | 88914.78 | 0.00 | 10737847.43 | 0.00 | 0.00 | 0.672937E+10 | 0.00 | 0.65 |
September | 0.236307E+10 | 0.00 | 0.00 | 5605943.53 | 0.00 | 0.00 | 0.409511E+10 | 0.00 | 0.49 |
October | 0.617192E+10 | 0.00 | 0.00 | 15484.03 | 0.00 | 0.754946E+09 | 26890107.56 | 0.00 | 0.35 |
November | 0.478786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335589E+10 | 0.00 | 0.00 | 0.34 |
December | 0.432997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560726E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.481268E+11 | 99869966.95 | 0.00 | 31357730.49 | 1626084.69 | 0.241619E+11 | 0.202797E+11 | 0.00 | 0.42 |
Minimum of Months | 0.393372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.617192E+10 | 56339679.76 | 0.00 | 10737847.43 | 964451.15 | 0.560726E+10 | 0.672937E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.173941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190706E+10 | 0.00 | 0.00 | 0.25 |
February | 0.151651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165402E+10 | 0.00 | 0.00 | 0.26 |
March | 0.187808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136973E+10 | 0.00 | 0.00 | 0.26 |
April | 0.215527E+10 | 0.00 | 0.00 | 1119513.63 | 88197.04 | 55698216.30 | 0.919028E+09 | 0.00 | 0.36 |
May | 0.204634E+10 | 0.00 | 0.00 | 1457006.16 | 0.00 | 0.00 | 0.144341E+10 | 0.00 | 0.39 |
June | 0.471291E+09 | 17821519.08 | 0.00 | 4225734.37 | 0.00 | 0.00 | 0.386150E+10 | 0.00 | 0.65 |
July | 0.170355E+09 | 25432702.95 | 0.00 | 6030800.65 | 839118.16 | 0.00 | 0.491576E+10 | 0.00 | 0.87 |
August | 34886081.08 | 21871.21 | 0.00 | 6914346.74 | 0.00 | 0.00 | 0.550763E+10 | 0.00 | 1.06 |
September | 0.198980E+09 | 0.00 | 0.00 | 5118589.55 | 0.00 | 0.00 | 0.457312E+10 | 0.00 | 0.77 |
October | 0.210639E+10 | 0.00 | 0.00 | 753072.04 | 0.00 | 4332023.94 | 0.934208E+09 | 0.00 | 0.29 |
November | 0.202330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101624E+10 | 0.00 | 0.00 | 0.26 |
December | 0.129924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229388E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.156400E+11 | 43276093.24 | 0.00 | 25619063.13 | 927315.21 | 0.830096E+10 | 0.221547E+11 | 0.00 | 0.47 |
Minimum of Months | 34886081.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.215527E+10 | 25432702.95 | 0.00 | 6914346.74 | 839118.16 | 0.229388E+10 | 0.550763E+10 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224263E+10 | 0.00 | 0.00 | 0.26 |
February | 0.118148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186362E+10 | 0.00 | 0.00 | 0.26 |
March | 0.153634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158262E+10 | 0.00 | 0.00 | 0.26 |
April | 0.201691E+10 | 0.00 | 0.00 | 571797.38 | 462565.56 | 0.113660E+09 | 0.581609E+09 | 0.00 | 0.34 |
May | 0.204533E+10 | 753.53 | 0.00 | 741096.37 | 0.00 | 0.00 | 0.831625E+09 | 0.00 | 0.35 |
June | 0.599715E+09 | 9320886.10 | 0.00 | 2523265.28 | 0.00 | 0.00 | 0.251565E+10 | 0.00 | 0.54 |
July | 0.300186E+09 | 19734088.45 | 0.00 | 3583193.46 | 951230.89 | 0.00 | 0.336241E+10 | 0.00 | 0.73 |
August | 0.197347E+09 | 16308.06 | 0.00 | 4510738.42 | 0.00 | 0.00 | 0.387890E+10 | 0.00 | 0.91 |
September | 0.445819E+09 | 0.00 | 0.00 | 3170607.49 | 0.00 | 0.00 | 0.295646E+10 | 0.00 | 0.66 |
October | 0.201535E+10 | 0.00 | 0.00 | 407131.40 | 0.00 | 68635972.64 | 0.579441E+09 | 0.00 | 0.28 |
November | 0.161709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127090E+10 | 0.00 | 0.00 | 0.26 |
December | 0.103791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242967E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.142409E+11 | 29072036.15 | 0.00 | 15507829.80 | 1413796.44 | 0.957173E+10 | 0.147061E+11 | 0.00 | 0.42 |
Minimum of Months | 0.197347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.204533E+10 | 19734088.45 | 0.00 | 4510738.42 | 951230.89 | 0.242967E+10 | 0.387890E+10 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240630E+10 | 0.00 | 0.00 | 0.26 |
February | 0.109157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195323E+10 | 0.00 | 0.00 | 0.26 |
March | 0.141242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170407E+10 | 0.00 | 0.00 | 0.26 |
April | 0.199256E+10 | 0.00 | 0.00 | 516750.54 | 490147.70 | 0.149472E+09 | 0.525449E+09 | 0.00 | 0.33 |
May | 0.205783E+10 | 0.00 | 0.00 | 668726.23 | 0.00 | 1166133.41 | 0.758242E+09 | 0.00 | 0.34 |
June | 0.654590E+09 | 9191729.02 | 0.00 | 2388681.83 | 0.00 | 0.00 | 0.239025E+10 | 0.00 | 0.53 |
July | 0.331364E+09 | 19706112.94 | 0.00 | 3493673.55 | 953168.58 | 0.00 | 0.328148E+10 | 0.00 | 0.72 |
August | 0.211948E+09 | 15383.06 | 0.00 | 4441427.70 | 0.00 | 0.00 | 0.382885E+10 | 0.00 | 0.90 |
September | 0.461295E+09 | 0.00 | 0.00 | 3053068.76 | 0.00 | 0.00 | 0.287552E+10 | 0.00 | 0.65 |
October | 0.194417E+10 | 0.00 | 0.00 | 335656.96 | 0.00 | 0.158858E+09 | 0.512419E+09 | 0.00 | 0.27 |
November | 0.149931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138390E+10 | 0.00 | 0.00 | 0.26 |
December | 0.922674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254489E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.136625E+11 | 28913225.02 | 0.00 | 14897985.59 | 1443316.28 | 0.103019E+11 | 0.141722E+11 | 0.00 | 0.42 |
Minimum of Months | 0.211948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.205783E+10 | 19706112.94 | 0.00 | 4441427.70 | 953168.58 | 0.254489E+10 | 0.382885E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.839772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264839E+10 | 0.00 | 0.00 | 0.26 |
February | 0.932588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211204E+10 | 0.00 | 0.00 | 0.26 |
March | 0.119518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191771E+10 | 0.00 | 0.00 | 0.26 |
April | 0.192638E+10 | 0.00 | 0.00 | 378234.72 | 585549.45 | 0.217155E+09 | 0.413235E+09 | 0.00 | 0.32 |
May | 0.205007E+10 | 0.00 | 0.00 | 489594.58 | 0.00 | 33499701.17 | 0.584056E+09 | 0.00 | 0.32 |
June | 0.888794E+09 | 8806464.87 | 0.00 | 1869687.46 | 0.00 | 0.00 | 0.189423E+10 | 0.00 | 0.49 |
July | 0.396219E+09 | 19459672.43 | 0.00 | 3097805.03 | 972639.89 | 0.00 | 0.300273E+10 | 0.00 | 0.68 |
August | 0.248870E+09 | 12137.67 | 0.00 | 4086675.93 | 0.00 | 0.00 | 0.361051E+10 | 0.00 | 0.86 |
September | 0.540515E+09 | 0.00 | 0.00 | 2588229.66 | 0.00 | 0.00 | 0.255823E+10 | 0.00 | 0.61 |
October | 0.191820E+10 | 0.00 | 0.00 | 132410.98 | 0.00 | 0.358995E+09 | 0.228853E+09 | 0.00 | 0.27 |
November | 0.123497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164258E+10 | 0.00 | 0.00 | 0.26 |
December | 0.717361E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275008E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.128889E+11 | 28278274.97 | 0.00 | 12642638.37 | 1558189.34 | 0.116805E+11 | 0.122918E+11 | 0.00 | 0.40 |
Minimum of Months | 0.248870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.205007E+10 | 19459672.43 | 0.00 | 4086675.93 | 972639.89 | 0.275008E+10 | 0.361051E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645988E+10 | 0.00 | 0.00 | 0.27 |
February | 0.126272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530955E+10 | 0.00 | 0.00 | 0.27 |
March | 0.204732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470437E+10 | 0.00 | 0.00 | 0.28 |
April | 0.400956E+10 | 0.00 | 0.00 | 377127.16 | 724708.08 | 0.630960E+09 | 0.312762E+09 | 0.00 | 0.29 |
May | 0.450509E+10 | 0.00 | 0.00 | 331996.79 | 0.00 | 0.207045E+09 | 0.340263E+09 | 0.00 | 0.29 |
June | 0.315707E+10 | 12202114.88 | 0.00 | 1909540.36 | 0.00 | 0.00 | 0.118999E+10 | 0.00 | 0.34 |
July | 0.118696E+10 | 28452747.95 | 0.00 | 4670110.73 | 1769206.04 | 0.00 | 0.344050E+10 | 0.00 | 0.42 |
August | 0.323063E+09 | 0.00 | 0.00 | 6624795.09 | 0.00 | 0.00 | 0.463498E+10 | 0.00 | 0.50 |
September | 0.224560E+10 | 0.00 | 0.00 | 2856503.49 | 0.00 | 0.00 | 0.218042E+10 | 0.00 | 0.38 |
October | 0.393308E+10 | 0.00 | 0.00 | 20924.69 | 0.00 | 0.109285E+10 | 31199660.69 | 0.00 | 0.27 |
November | 0.199830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421307E+10 | 0.00 | 0.00 | 0.27 |
December | 0.592282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689739E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.263151E+11 | 40654862.83 | 0.00 | 16790998.30 | 2493914.12 | 0.295151E+11 | 0.121301E+11 | 0.00 | 0.32 |
Minimum of Months | 0.323063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.450509E+10 | 28452747.95 | 0.00 | 6624795.09 | 1769206.04 | 0.689739E+10 | 0.463498E+10 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.435820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330746E+10 | 0.00 | 0.00 | 0.27 |
February | 0.531115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274232E+10 | 0.00 | 0.00 | 0.27 |
March | 0.871281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249103E+10 | 0.00 | 0.00 | 0.28 |
April | 0.189800E+10 | 0.00 | 0.00 | 209858.76 | 347037.32 | 0.408747E+09 | 0.237988E+09 | 0.00 | 0.30 |
May | 0.210703E+10 | 0.00 | 0.00 | 214955.28 | 0.00 | 0.189096E+09 | 0.311828E+09 | 0.00 | 0.30 |
June | 0.141441E+10 | 5565643.47 | 0.00 | 1102352.49 | 0.00 | 0.00 | 0.102400E+10 | 0.00 | 0.41 |
July | 0.515247E+09 | 13033816.95 | 0.00 | 2491699.46 | 1257565.61 | 0.00 | 0.237610E+10 | 0.00 | 0.55 |
August | 0.123168E+09 | 0.00 | 0.00 | 3419218.63 | 0.00 | 0.00 | 0.314300E+10 | 0.00 | 0.69 |
September | 0.823359E+09 | 0.00 | 0.00 | 1724990.62 | 0.00 | 0.00 | 0.180662E+10 | 0.00 | 0.48 |
October | 0.186416E+10 | 0.00 | 0.00 | 15979.61 | 0.00 | 0.661460E+09 | 32674172.20 | 0.00 | 0.27 |
November | 0.858481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223326E+10 | 0.00 | 0.00 | 0.27 |
December | 0.246453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348354E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.116885E+11 | 18599460.42 | 0.00 | 9179054.84 | 1604602.94 | 0.155169E+11 | 0.893222E+10 | 0.00 | 0.36 |
Minimum of Months | 0.123168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.210703E+10 | 13033816.95 | 0.00 | 3419218.63 | 1257565.61 | 0.348354E+10 | 0.314300E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.408052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333515E+10 | 0.00 | 0.00 | 0.27 |
February | 0.482096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279144E+10 | 0.00 | 0.00 | 0.27 |
March | 0.807938E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255429E+10 | 0.00 | 0.00 | 0.28 |
April | 0.184456E+10 | 0.00 | 0.00 | 194880.64 | 354730.42 | 0.461971E+09 | 0.224783E+09 | 0.00 | 0.30 |
May | 0.206148E+10 | 0.00 | 0.00 | 190032.47 | 0.00 | 0.238963E+09 | 0.289217E+09 | 0.00 | 0.30 |
June | 0.146828E+10 | 5429249.76 | 0.00 | 1018851.41 | 0.00 | 679664.41 | 0.928269E+09 | 0.00 | 0.40 |
July | 0.533981E+09 | 12948040.33 | 0.00 | 2387207.24 | 1258209.24 | 0.00 | 0.229489E+10 | 0.00 | 0.54 |
August | 0.123823E+09 | 0.00 | 0.00 | 3303465.83 | 0.00 | 0.00 | 0.306982E+10 | 0.00 | 0.67 |
September | 0.873310E+09 | 0.00 | 0.00 | 1625837.94 | 0.00 | 0.00 | 0.171125E+10 | 0.00 | 0.47 |
October | 0.181170E+10 | 0.00 | 0.00 | 13347.72 | 0.00 | 0.708611E+09 | 28925953.94 | 0.00 | 0.27 |
November | 0.810918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228079E+10 | 0.00 | 0.00 | 0.27 |
December | 0.217053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351296E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.114432E+11 | 18377290.10 | 0.00 | 8733623.25 | 1612939.66 | 0.158848E+11 | 0.854716E+10 | 0.00 | 0.36 |
Minimum of Months | 0.123823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.206148E+10 | 12948040.33 | 0.00 | 3303465.83 | 1258209.24 | 0.351296E+10 | 0.306982E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.277569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346574E+10 | 0.00 | 0.00 | 0.27 |
February | 0.241125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303249E+10 | 0.00 | 0.00 | 0.27 |
March | 0.543378E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281887E+10 | 0.00 | 0.00 | 0.28 |
April | 0.168189E+10 | 0.00 | 0.00 | 151462.76 | 385483.82 | 0.635401E+09 | 0.178024E+09 | 0.00 | 0.30 |
May | 0.192816E+10 | 0.00 | 0.00 | 128060.39 | 0.00 | 0.415494E+09 | 0.192255E+09 | 0.00 | 0.29 |
June | 0.157340E+10 | 5096818.68 | 0.00 | 787573.34 | 0.00 | 4705516.15 | 0.695691E+09 | 0.00 | 0.38 |
July | 0.603240E+09 | 13264059.11 | 0.00 | 2050548.13 | 832988.03 | 0.00 | 0.203026E+10 | 0.00 | 0.50 |
August | 0.151280E+09 | 0.00 | 0.00 | 2902756.21 | 0.00 | 0.00 | 0.281600E+10 | 0.00 | 0.63 |
September | 0.107372E+10 | 0.00 | 0.00 | 1264922.59 | 0.00 | 0.00 | 0.136158E+10 | 0.00 | 0.45 |
October | 0.164049E+10 | 0.00 | 0.00 | 6487.34 | 0.00 | 0.862649E+09 | 16772114.12 | 0.00 | 0.27 |
November | 0.596677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249484E+10 | 0.00 | 0.00 | 0.27 |
December | 72714788.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365743E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.103836E+11 | 18360877.79 | 0.00 | 7291810.76 | 1218471.85 | 0.173876E+11 | 0.729058E+10 | 0.00 | 0.35 |
Minimum of Months | 72714788.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.192816E+10 | 13264059.11 | 0.00 | 2902756.21 | 832988.03 | 0.365743E+10 | 0.281600E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 21968369.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371283E+10 | 0.00 | 0.00 | 0.27 |
February | 9751322.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324796E+10 | 0.00 | 0.00 | 0.27 |
March | 69116712.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328109E+10 | 0.00 | 0.00 | 0.28 |
April | 0.124867E+10 | 0.00 | 0.00 | 122680.33 | 476740.09 | 0.106171E+10 | 0.138399E+09 | 0.00 | 0.29 |
May | 0.153354E+10 | 0.00 | 0.00 | 79464.75 | 0.00 | 0.809131E+09 | 0.113951E+09 | 0.00 | 0.29 |
June | 0.155918E+10 | 4975456.03 | 0.00 | 603005.83 | 123915.31 | 35270109.75 | 0.502165E+09 | 0.00 | 0.37 |
July | 0.738734E+09 | 12479154.32 | 0.00 | 1584915.71 | 3134649.62 | 0.00 | 0.161778E+10 | 0.00 | 0.46 |
August | 0.270484E+09 | 0.00 | 0.00 | 2369442.65 | 9766.07 | 0.00 | 0.240971E+10 | 0.00 | 0.58 |
September | 0.125789E+10 | 0.00 | 0.00 | 941298.79 | 0.00 | 1073356.66 | 0.984387E+09 | 0.00 | 0.43 |
October | 0.108576E+10 | 0.00 | 0.00 | 727.56 | 0.00 | 0.136902E+10 | 5737059.80 | 0.00 | 0.27 |
November | 0.115374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295343E+10 | 0.00 | 0.00 | 0.27 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370562E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.791048E+10 | 17454610.36 | 0.00 | 5701535.61 | 3745071.09 | 0.201771E+11 | 0.577213E+10 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.155918E+10 | 12479154.32 | 0.00 | 2369442.65 | 3134649.62 | 0.371283E+10 | 0.240971E+10 | 0.00 | 0.58 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:39:23
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.692416E+11 | 0.260668E+11 | 0.00 | 0.481680E+11 | 0.659689E+10 |
February | 0.120791E+12 | 0.233464E+11 | 0.00 | 0.422606E+11 | 0.535461E+10 |
March | 0.161311E+12 | 0.226479E+11 | 0.00 | 0.429858E+11 | 0.473186E+10 |
April | 0.450444E+12 | 0.168638E+11 | 0.00 | 0.336305E+11 | 0.201471E+10 |
May | 0.545846E+12 | 0.196740E+11 | 0.00 | 0.343536E+11 | 0.111224E+10 |
June | 0.561172E+12 | 0.150097E+11 | 0.00 | 0.329094E+11 | 0.649326E+10 |
July | 0.571007E+12 | 0.127285E+11 | 0.00 | 0.376946E+11 | 0.969298E+10 |
August | 0.466030E+12 | 0.105546E+11 | 0.00 | 0.417606E+11 | 0.824425E+10 |
September | 0.336972E+12 | 0.134539E+11 | 0.00 | 0.354170E+11 | 0.457474E+10 |
October | 0.138601E+12 | 0.187012E+11 | 0.00 | 0.337270E+11 | 0.121980E+10 |
November | 0.426609E+11 | 0.233517E+11 | 0.00 | 0.398612E+11 | 0.412262E+10 |
December | 0.317308E+09 | 0.286530E+11 | 0.00 | 0.480830E+11 | 0.707630E+10 |
Annual Sum or Average | 0.346440E+13 | 0.231051E+12 | 0.00 | 0.470851E+12 | 0.612343E+11 |
Minimum of Months | 0.317308E+09 | 0.105546E+11 | 0.00 | 0.329094E+11 | 0.111224E+10 |
Maximum of Months | 0.571007E+12 | 0.286530E+11 | 0.00 | 0.481680E+11 | 0.969298E+10 |