Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:39
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 08:39:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 983.73 | 470.61 | 470.61 |
Net Site Energy | 915.87 | 438.15 | 438.15 |
Total Source Energy | 3115.24 | 1490.32 | 1490.32 |
Net Source Energy | 2900.31 | 1387.50 | 1387.50 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 381.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 96.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 58.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 983.62 | 0.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 381.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 41.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 96.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 58.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 381.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 41.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 96.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 58.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 152.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 256.74 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 470.56 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 152.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 256.74 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 470.56 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 70.848 | 7.20 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -2.98 | -0.3 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 67.866 | 6.90 |
Electricity Coming From Utility | 915.753 | 93.10 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 915.753 | 93.10 |
Total On-Site and Utility Electric Sources | 983.619 | 100.00 |
Total Electricity End Uses | 983.619 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1547.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:39 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 11.5884 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 13.7658 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 7.5320 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 10.0873 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 10.0873 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 11.5884 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 13.7658 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 12.9393 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 12.9393 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 12.9393 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 7.5320 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 7.5557 | 6.19 | 4.3000 | |
Total | 2090.32 | 10.0873 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 10.0873 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 10.0873 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUL-13:30 | 04-FEB-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 20815.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 50855.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7998.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5430.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 90041.90 | 20815.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 20815.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 50855.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7998.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5430.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1209.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 879.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 129.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 304.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 186.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3115.12 | 0.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 578.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 420.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 145.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1490.26 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 578.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 420.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 145.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1490.26 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.04 |
SMSTORE1 DIRECT AIR | 1.04 |
SMSTORE2 DIRECT AIR | 1.06 |
SMSTORE3 DIRECT AIR | 1.06 |
SMSTORE4 DIRECT AIR | 1.05 |
LGSTORE2 DIRECT AIR | 1.89 |
SMSTORE5 DIRECT AIR | 0.988734 |
SMSTORE6 DIRECT AIR | 0.984512 |
SMSTORE7 DIRECT AIR | 0.988892 |
SMSTORE8 DIRECT AIR | 1.18 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.04 | 2.04 | 2.04 | 2.04 | 2.04 | 2.04 | 1.00 | 1.00 | 2.04 |
PSZ-AC_2:2 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
PSZ-AC_3:3 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
PSZ-AC_4:4 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
PSZ-AC_5:5 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
PSZ-AC_6:6 | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.00 | 1.000000 | 1.89 |
PSZ-AC_7:7 | 0.988734 | 0.988734 | 0.988734 | 0.988734 | 0.988734 | 0.988734 | 1.00 | 1.000000 | 0.988734 |
PSZ-AC_8:8 | 0.984512 | 0.984512 | 0.984512 | 0.984512 | 0.984512 | 0.984512 | 1.00 | 1.00 | 0.984512 |
PSZ-AC_9:9 | 0.988892 | 0.988892 | 0.988892 | 0.988892 | 0.988892 | 0.988892 | 1.00 | 1.00 | 0.988892 |
PSZ-AC_10:10 | 1.18 | 1.18 | 1.18 | 1.18 | 1.18 | 1.18 | 1.00 | 1.000000 | 1.18 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.04 |
PSZ-AC_2:2_OA_CONTROLLER | 1.04 |
PSZ-AC_3:3_OA_CONTROLLER | 1.06 |
PSZ-AC_4:4_OA_CONTROLLER | 1.06 |
PSZ-AC_5:5_OA_CONTROLLER | 1.05 |
PSZ-AC_6:6_OA_CONTROLLER | 1.89 |
PSZ-AC_7:7_OA_CONTROLLER | 0.988734 |
PSZ-AC_8:8_OA_CONTROLLER | 0.984512 |
PSZ-AC_9:9_OA_CONTROLLER | 0.988892 |
PSZ-AC_10:10_OA_CONTROLLER | 1.18 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.04 | 2185.23 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1156.64 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1169.00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1173.62 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1165.69 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.89 | 2018.69 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.988734 | 1094.69 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.984512 | 1090.01 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.988892 | 1094.86 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.18 | 1301.21 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.04 | 2.04 | 2.04 | 1.35 | 50712.19 | 52796.10 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.689498 | 25942.24 | 26936.90 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.696865 | 26219.43 | 27191.75 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.699618 | 26323.01 | 27286.98 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 0.694892 | 26145.18 | 27123.49 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.89 | 1.89 | 1.89 | 1.25 | 46847.46 | 49242.77 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.988734 | 0.988734 | 0.988734 | 0.652564 | 24552.62 | 25659.29 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.984512 | 0.984512 | 0.984512 | 0.649778 | 24447.77 | 25562.89 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.988892 | 0.988892 | 0.988892 | 0.652669 | 24556.55 | 25662.90 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.18 | 1.18 | 1.18 | 0.775678 | 29184.74 | 29918.18 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.04 | 1.02 | 1.36 | 50712.19 | 25356.10 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.04 | 0.522347 | 0.696460 | 25942.24 | 12971.12 | 0.701080 | 0.701080 |
PSZ-AC_3:3 COOLING COIL | 1.06 | 0.527928 | 0.703907 | 26219.43 | 13109.72 | 0.701080 | 0.701080 |
PSZ-AC_4:4 COOLING COIL | 1.06 | 0.530014 | 0.706687 | 26323.01 | 13161.50 | 0.701080 | 0.701080 |
PSZ-AC_5:5 COOLING COIL | 1.05 | 0.526433 | 0.701913 | 26145.18 | 13072.59 | 0.701080 | 0.701080 |
PSZ-AC_6:6 COOLING COIL | 1.89 | 0.943274 | 1.26 | 46847.46 | 23423.73 | 0.701080 | 0.701080 |
PSZ-AC_7:7 COOLING COIL | 0.988730 | 0.494367 | 0.659153 | 24552.62 | 12276.31 | 0.701080 | 0.701080 |
PSZ-AC_8:8 COOLING COIL | 0.984510 | 0.492256 | 0.656340 | 24447.77 | 12223.89 | 0.701080 | 0.701080 |
PSZ-AC_9:9 COOLING COIL | 0.988890 | 0.494446 | 0.659260 | 24556.55 | 12278.27 | 0.701080 | 0.701080 |
PSZ-AC_10:10 COOLING COIL | 1.18 | 0.587635 | 0.783513 | 29184.74 | 14592.37 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 52796.10 |
PSZ-AC_2:2 HEATING COIL | 26936.90 |
PSZ-AC_3:3 HEATING COIL | 27191.75 |
PSZ-AC_4:4 HEATING COIL | 27286.98 |
PSZ-AC_5:5 HEATING COIL | 27123.49 |
PSZ-AC_6:6 HEATING COIL | 49242.77 |
PSZ-AC_7:7 HEATING COIL | 25659.29 |
PSZ-AC_8:8 HEATING COIL | 25562.89 |
PSZ-AC_9:9 HEATING COIL | 25662.90 |
PSZ-AC_10:10 HEATING COIL | 29918.18 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 11.588 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.888 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 13.766 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 18.066 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 7.532 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.832 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 2630.745 | 7.551 | 46.768 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2630.745 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1406.513 | 4.037 | 25.004 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1406.513 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1319.493 | 7.575 | 46.916 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1319.493 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1078.411 | 6.191 | 38.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1078.411 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 2624.046 | 7.532 | 46.649 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2624.046 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7383 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.27626373E-12 | 0.13670118E-14 | -0.80430638E-13 | 0.78416590E-16 |
23 | 6 | 0.25658824E-07 | 0.27941242E-09 | 0.59030768E-08 | -0.11909973E-12 |
24 | 5 | -0.17468948E-03 | 0.24402707E-05 | -0.90039107E-04 | 0.58437388E-08 |
25 | 4 | 0.27392503 | 0.12091412E-02 | 0.93138911E-01 | -0.31018751E-04 |
26 | 3 | -6.9050330 | 0.38055846E-01 | -2.2317352 | 0.27239655E-01 |
27 | 2 | 39.679098 | 0.13717309 | 14.824430 | -0.32006664 |
28 | 1 | -79.631803 | 0.62641324E-01 | -28.746304 | 1.0591428 |
29 | 0 | 46.824345 | 0.12749544E-02 | 16.300917 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 35 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 23150.58830 | 27780.70596 | 1.70182 | 2.04218 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 32.93200 | 1.71667E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 13355.70940 | 16026.85128 | 0.57646 | 0.69176 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11842.80584 | 14211.36700 | 0.87058 | 1.04469 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.20000 | 1.71672E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 6466.34186 | 7759.61023 | 0.27910 | 0.33492 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11969.39204 | 14363.27045 | 0.87988 | 1.05586 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.14417 | 1.71671E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 6529.76388 | 7835.71665 | 0.28184 | 0.33821 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 12016.82506 | 14420.19007 | 0.88336 | 1.06003 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.08833 | 1.71670E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 6591.19860 | 7909.43832 | 0.28449 | 0.34139 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11935.65362 | 14322.78434 | 0.87739 | 1.05287 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.08833 | 1.71670E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 6727.14658 | 8072.57590 | 0.29036 | 0.34843 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 21387.36189 | 25664.83426 | 1.57212 | 1.88655 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.08833 | 1.71670E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 12765.02079 | 15318.02494 | 0.55097 | 0.66116 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11208.68729 | 13450.42474 | 0.82395 | 0.98873 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.08833 | 1.71670E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 6897.48479 | 8276.98175 | 0.29771 | 0.35725 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11160.82546 | 13392.99055 | 0.82043 | 0.98451 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.08833 | 1.71670E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 6902.17670 | 8282.61204 | 0.29791 | 0.35750 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11210.79923 | 13452.95908 | 0.82408 | 0.98889 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.03250 | 1.71669E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 7133.46885 | 8560.16262 | 0.30790 | 0.36948 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 13325.45067 | 15990.54081 | 0.97939 | 1.17527 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 32.86500 | 1.71666E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 8625.65913 | 10350.79095 | 0.37230 | 0.44676 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 31904.00 | 2.04218 | 2.04218 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 21964.68 | 0.69176 | 0.69176 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16308.64 | 1.04469 | 1.04469 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 10732.18 | 0.33492 | 0.33492 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16454.43 | 1.05586 | 1.05586 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 10807.18 | 0.33821 | 0.33821 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16509.14 | 1.06003 | 1.06003 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 10879.83 | 0.34139 | 0.34139 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 16413.45 | 1.05287 | 1.05287 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 11040.59 | 0.34843 | 0.34843 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 29889.84 | 1.88655 | 1.88655 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 21266.20 | 0.66116 | 0.66116 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 15550.53 | 0.98873 | 0.98873 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 11242.02 | 0.35725 | 0.35725 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 15493.83 | 0.98451 | 0.98451 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 11247.56 | 0.35750 | 0.35750 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 15548.14 | 0.98889 | 0.98889 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 11521.07 | 0.36948 | 0.36948 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 17976.49 | 1.17527 | 1.17527 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 13285.59 | 0.44676 | 0.44676 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.04218 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04469 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05586 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06003 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05287 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.88655 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98873 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98451 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98889 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.17527 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.04218 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.04218 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.04218 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.04218 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.04218 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.04218 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04469 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04469 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04469 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04469 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04469 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04469 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05586 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05586 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05586 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05586 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05586 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05586 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06003 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06003 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06003 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06003 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06003 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06003 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05287 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05287 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05287 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05287 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05287 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05287 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.88655 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.88655 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.88655 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.88655 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.88655 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.88655 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98873 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98873 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98873 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98873 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98873 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98873 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98451 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98451 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98451 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98451 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98451 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98451 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98889 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98889 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98889 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98889 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98889 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98889 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.17527 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.17527 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.17527 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.17527 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.17527 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.17527 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.04218 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.04469 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.05586 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.06003 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.05287 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.88655 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.98873 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.98451 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.98889 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.17527 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.04218 |
102 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.04218 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2185.22908 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.04218 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.04218 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.04218 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.34784 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.04218 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.02109 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.36145 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 50712.19000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 25356.09500 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
115 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 50712.19000 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 52796.10395 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
119 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 52796.10395 |
120 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04469 |
121 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04469 |
122 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1156.64231 |
123 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04469 |
124 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04469 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04469 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68950 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04469 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52235 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69646 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25942.24000 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12971.12000 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25942.24000 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26936.90466 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
138 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 26936.90466 |
139 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05586 |
140 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05586 |
141 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1169.00054 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05586 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05586 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05586 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69687 |
146 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05586 |
147 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52793 |
148 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70391 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26219.43000 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13109.71500 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26219.43000 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27191.74592 |
155 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
157 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 27191.74592 |
158 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06003 |
159 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06003 |
160 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1173.61900 |
161 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06003 |
162 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06003 |
163 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06003 |
164 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69962 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06003 |
166 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53001 |
167 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70669 |
168 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26323.01000 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13161.50500 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
172 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26323.01000 |
173 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27286.98417 |
174 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
176 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 27286.98417 |
177 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05287 |
178 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05287 |
179 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1165.69041 |
180 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05287 |
181 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05287 |
182 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05287 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69489 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05287 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52643 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70191 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26145.18000 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13072.59000 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26145.18000 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27123.48549 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
194 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
195 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 27123.48549 |
196 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.88655 |
197 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.88655 |
198 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2018.69473 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.88655 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.88655 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.88655 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.24512 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.88655 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.94327 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.25770 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 46847.46000 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 23423.73000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 46847.46000 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 49242.77380 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
213 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
214 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 49242.77380 |
215 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98873 |
216 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98873 |
217 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1094.68552 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98873 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98873 |
220 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98873 |
221 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65256 |
222 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98873 |
223 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49437 |
224 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65915 |
225 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24552.62000 |
226 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12276.31000 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
229 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24552.62000 |
230 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25659.28935 |
231 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
232 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
233 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 25659.28935 |
234 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98451 |
235 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98451 |
236 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1090.01078 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98451 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98451 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98451 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.64978 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98451 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49226 |
243 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65634 |
244 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24447.77000 |
245 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12223.88500 |
246 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
247 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24447.77000 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25562.89030 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
251 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
252 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 25562.89030 |
253 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98889 |
254 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98889 |
255 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1094.86083 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98889 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98889 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98889 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65267 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98889 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49445 |
262 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65926 |
263 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24556.55000 |
264 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12278.27500 |
265 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
266 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24556.55000 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25662.90225 |
269 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
270 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
271 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 25662.90225 |
272 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.17527 |
273 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.17527 |
274 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1301.20970 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.17527 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.17527 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.17527 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77568 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.17527 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58763 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.78351 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29184.74000 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14592.37000 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29184.74000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29918.18471 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 29918.18471 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 49101.1 | 12.27 | 12.27 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 25118.1 | 12.46 | 12.46 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 25386.4 | 12.46 | 12.46 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 25486.7 | 12.46 | 12.46 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 25314.6 | 12.46 | 12.46 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 45359.1 | 12.27 | 12.27 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 23772.6 | 12.46 | 12.46 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 23671.1 | 12.46 | 12.46 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 23776.4 | 12.46 | 12.46 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 28257.6 | 12.46 | 12.46 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 1.6868461215E-002 | 5.9236206631E-002 | Pass | Pass | 0.2259336237 | 2.3290413228 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 2.0064515198E-002 | 8.6376518223E-002 | Pass | Pass | 3.7592237236E-002 | 0.1268927953 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.2867831312E-002 | 0.1210417138 | Pass | Pass | 0.1685131043 | 1.4047318595 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.2898339613E-002 | 0.1212619793 | Pass | Pass | 0.1668847296 | 1.3881684322 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.1569879484E-002 | 0.1137499134 | Pass | Pass | 0.1601827778 | 1.3228773543 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.3508626370E-002 | 0.1186507619 | Pass | Pass | 0.1759044971 | 1.4767755434 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 3.1970018541E-002 | 0.1155613353 | Pass | Pass | 0.1518341395 | 1.2887314079 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 3.1696420178E-002 | 0.1136778482 | Pass | Pass | 0.1503610488 | 1.2748622296 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 3.0789807587E-002 | 0.1068148925 | Pass | Pass | 0.1478980044 | 1.2465058155 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 3.6244801955E-002 | 0.1084581053 | Pass | Pass | 0.1866874922 | 1.3974631835 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3058.49 | -315.6 | 0.00 | -474.7 | 2011.71 | 4279.83 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.231 | 0.254 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.860 | 0.231 | 0.254 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.860 | 0.231 | 0.254 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 7.5512 | 348.39 | 2630.74 | LightsWired | LTG_SCH_BASE_LPD1 | 81.37 | 168.00 | 80.49 | 0.0000 | Y | 39.75 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 4.0372 | 348.39 | 1406.51 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 24.96 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 7.5749 | 174.19 | 1319.49 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 82.90 | 168.00 | 81.97 | 0.0000 | Y | 20.30 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 6.1909 | 174.19 | 1078.41 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 19.14 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 7.5320 | 348.39 | 2624.05 | LightsWired | LTG_SCH_BASE_LPD2 | 60.23 | 168.00 | 58.11 | 0.0000 | Y | 28.62 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 5.0436 | 4180.64 | 21085.58 | 277.79 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 437.57 | AstronomicalClock | - | 41.82 | 41.82 | 3.44 | |
EXTERIOR_LIGHTS_B | 1882.64 | AstronomicalClock | - | 83.82 | 62.82 | 22.20 | |
EXTERIOR_LIGHTS_C | 1466.47 | AstronomicalClock | - | 83.82 | 55.82 | 15.37 | |
Exterior Lighting Total | 3786.68 | 41.00 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 50712.19 | 35553.30 | 15158.89 | 0.70 | 3.92 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25942.24 | 18187.59 | 7754.65 | 0.70 | 3.99 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26219.43 | 18381.92 | 7837.51 | 0.70 | 3.99 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26323.01 | 18454.54 | 7868.47 | 0.70 | 3.99 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26145.18 | 18329.86 | 7815.32 | 0.70 | 3.99 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 46847.46 | 32843.82 | 14003.64 | 0.70 | 3.92 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24552.62 | 17213.35 | 7339.27 | 0.70 | 3.99 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24447.77 | 17139.84 | 7307.93 | 0.70 | 3.99 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24556.55 | 17216.11 | 7340.44 | 0.70 | 3.99 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29184.74 | 20460.84 | 8723.90 | 0.70 | 3.99 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 49101.1 | 12.27 | 12.27 | ||||
PSZ-AC_2:2 COOLING COIL | 25118.1 | 12.46 | 12.46 | ||||
PSZ-AC_3:3 COOLING COIL | 25386.4 | 12.46 | 12.46 | ||||
PSZ-AC_4:4 COOLING COIL | 25486.7 | 12.46 | 12.46 | ||||
PSZ-AC_5:5 COOLING COIL | 25314.6 | 12.46 | 12.46 | ||||
PSZ-AC_6:6 COOLING COIL | 45359.1 | 12.27 | 12.27 | ||||
PSZ-AC_7:7 COOLING COIL | 23772.6 | 12.46 | 12.46 | ||||
PSZ-AC_8:8 COOLING COIL | 23671.1 | 12.46 | 12.46 | ||||
PSZ-AC_9:9 COOLING COIL | 23776.4 | 12.46 | 12.46 | ||||
PSZ-AC_10:10 COOLING COIL | 28257.6 | 12.46 | 12.46 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 52796.10 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 26936.90 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 27191.75 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 27286.98 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 27123.49 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 49242.77 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 25659.29 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 25562.89 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 25662.90 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 29918.18 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.04 | 2185.23 | 1070.05 | 1.00 | 1.31 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1156.64 | 1107.16 | 1.00 | 1.39 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1169.00 | 1107.16 | 1.00 | 1.39 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1173.62 | 1107.16 | 1.00 | 1.39 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1165.69 | 1107.16 | 1.00 | 1.39 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.89 | 2018.69 | 1070.05 | 1.00 | 1.32 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1094.69 | 1107.16 | 1.00 | 1.41 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1090.01 | 1107.16 | 1.00 | 1.41 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1094.86 | 1107.16 | 1.00 | 1.41 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.18 | 1301.21 | 1107.16 | 1.00 | 1.36 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 23150.59 | 27780.71 | 79.74 | 1.702 | 2.042 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 23.89 | 23.88 | 0.01060 | 32.93 | 0.01717 | 0.411 | 0.00 |
SMSTORE1 | 11842.81 | 14211.37 | 81.58 | 0.871 | 1.045 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 23.89 | 23.88 | 0.01066 | 33.20 | 0.01717 | 0.206 | 0.00 |
SMSTORE2 | 11969.39 | 14363.27 | 82.46 | 0.880 | 1.056 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.88 | 0.01064 | 33.14 | 0.01717 | 0.206 | 0.00 |
SMSTORE3 | 12016.83 | 14420.19 | 82.78 | 0.883 | 1.060 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.88 | 0.01064 | 33.09 | 0.01717 | 0.206 | 0.00 |
SMSTORE4 | 11935.65 | 14322.78 | 82.22 | 0.877 | 1.053 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.88 | 0.01065 | 33.09 | 0.01717 | 0.206 | 0.00 |
LGSTORE2 | 21387.36 | 25664.83 | 73.67 | 1.572 | 1.887 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.88 | 0.01067 | 33.09 | 0.01717 | 0.411 | 0.00 |
SMSTORE5 | 11208.69 | 13450.42 | 77.22 | 0.824 | 0.989 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.88 | 0.01076 | 33.09 | 0.01717 | 0.206 | 0.00 |
SMSTORE6 | 11160.83 | 13392.99 | 76.89 | 0.820 | 0.985 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.88 | 0.01076 | 33.09 | 0.01717 | 0.206 | 0.00 |
SMSTORE7 | 11210.80 | 13452.96 | 77.23 | 0.824 | 0.989 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.88 | 0.01075 | 33.03 | 0.01717 | 0.206 | 0.00 |
SMSTORE8 | 13325.45 | 15990.54 | 91.80 | 0.979 | 1.175 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.88 | 0.01056 | 32.87 | 0.01717 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 13355.71 | 16026.85 | 46.00 | 0.576 | 0.692 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00761 | 8.70 | 0.00699 | 0.411 | 0.00 |
SMSTORE1 | 6466.34 | 7759.61 | 44.55 | 0.279 | 0.335 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00758 | 8.70 | 0.00699 | 0.206 | 0.00 |
SMSTORE2 | 6529.76 | 7835.72 | 44.98 | 0.282 | 0.338 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00758 | 8.70 | 0.00699 | 0.206 | 0.00 |
SMSTORE3 | 6591.20 | 7909.44 | 45.41 | 0.284 | 0.341 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00759 | 8.70 | 0.00699 | 0.206 | 0.00 |
SMSTORE4 | 6727.15 | 8072.58 | 46.34 | 0.290 | 0.348 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00759 | 8.70 | 0.00699 | 0.206 | 0.00 |
LGSTORE2 | 12765.02 | 15318.02 | 43.97 | 0.551 | 0.661 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00761 | 8.70 | 0.00699 | 0.411 | 0.00 |
SMSTORE5 | 6897.48 | 8276.98 | 47.52 | 0.298 | 0.357 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00759 | 8.70 | 0.00699 | 0.206 | 0.00 |
SMSTORE6 | 6902.18 | 8282.61 | 47.55 | 0.298 | 0.357 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00760 | 8.70 | 0.00699 | 0.206 | 0.00 |
SMSTORE7 | 7133.47 | 8560.16 | 49.14 | 0.308 | 0.369 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00760 | 8.70 | 0.00699 | 0.206 | 0.00 |
SMSTORE8 | 8625.66 | 10350.79 | 59.42 | 0.372 | 0.447 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00762 | 8.70 | 0.00699 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.04 | 2.04 | 0.69 | 0.69 | 2.0422 | 2.0422 | 2.0422 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.04 | 1.04 | 0.33 | 0.33 | 1.0447 | 1.0447 | 1.0447 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.06 | 1.06 | 0.34 | 0.34 | 1.0559 | 1.0559 | 1.0559 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.06 | 1.06 | 0.34 | 0.34 | 1.0600 | 1.0600 | 1.0600 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.05 | 1.05 | 0.35 | 0.35 | 1.0529 | 1.0529 | 1.0529 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.89 | 1.89 | 0.66 | 0.66 | 1.8865 | 1.8865 | 1.8865 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.99 | 0.99 | 0.36 | 0.36 | 0.9887 | 0.9887 | 0.9887 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 0.98 | 0.98 | 0.36 | 0.36 | 0.9845 | 0.9845 | 0.9845 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 0.99 | 0.99 | 0.37 | 0.37 | 0.9889 | 0.9889 | 0.9889 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.18 | 1.18 | 0.45 | 0.45 | 1.1753 | 1.1753 | 1.1753 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 50712.190 | 35553.302 | 2.042180 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 25356.10 | 16153.80 | 1.361453 | 26.63 | 20.00 | 0.01193108 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 30.2236 | 23.88 | 0.01060489 | 57.2353 | 23108.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 52796.104 | 52796.104 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 52796.10 | 52796.10 | 2.042180 | 18.61 | 13.44 | 0.00748427 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 20.1491 | 21.11 | 0.00760828 | 48.8288 | 13355.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 25942.240 | 18187.586 | 1.044690 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 12971.12 | 8248.62 | 0.696460 | 26.61 | 20.00 | 0.01194417 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 29.5405 | 23.88 | 0.01066332 | 57.5456 | 11842.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 26936.905 | 26936.905 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 26936.90 | 26936.90 | 1.044694 | 18.67 | 13.44 | 0.00746573 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 19.6936 | 21.11 | 0.00758169 | 48.6603 | 6466.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 26219.430 | 18381.918 | 1.055860 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 13109.72 | 8357.29 | 0.703907 | 26.59 | 19.97 | 0.01191667 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 29.2280 | 23.88 | 0.01064557 | 57.4514 | 11966.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 27191.746 | 27191.746 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27191.75 | 27191.75 | 1.055856 | 18.69 | 13.46 | 0.00746865 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 19.4854 | 21.11 | 0.00758380 | 48.6736 | 6529.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 26323.010 | 18454.536 | 1.060030 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 13161.50 | 8398.01 | 0.706687 | 26.59 | 19.96 | 0.01190646 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 29.1130 | 23.88 | 0.01063898 | 57.4164 | 12012.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 27286.984 | 27286.984 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27286.98 | 27286.98 | 1.060028 | 18.70 | 13.46 | 0.00747074 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 19.4087 | 21.11 | 0.00758583 | 48.6865 | 6591.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 26145.180 | 18329.863 | 1.052870 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 13072.59 | 8327.86 | 0.701913 | 26.60 | 19.98 | 0.01192439 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 29.3110 | 23.88 | 0.01065057 | 57.4779 | 11931.52 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 27123.485 | 27123.485 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27123.49 | 27123.49 | 1.052867 | 18.68 | 13.46 | 0.00747378 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 19.5407 | 21.11 | 0.00759057 | 48.7166 | 6727.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 46847.460 | 32843.817 | 1.886550 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23423.73 | 14723.56 | 1.257700 | 26.78 | 20.16 | 0.01209410 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 32.7169 | 23.88 | 0.01067809 | 57.6226 | 21377.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 49242.774 | 49242.774 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 49242.77 | 49242.77 | 1.886547 | 18.40 | 13.35 | 0.00747827 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 21.8113 | 21.11 | 0.00761367 | 48.8629 | 12765.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 24552.620 | 17213.351 | 0.988730 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 12276.31 | 7704.05 | 0.659153 | 26.72 | 20.14 | 0.01209495 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 31.2124 | 23.88 | 0.01076108 | 58.0640 | 11201.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 25659.289 | 25659.289 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 25659.29 | 25659.29 | 0.988734 | 18.53 | 13.39 | 0.00746967 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 20.8082 | 21.11 | 0.00759495 | 48.7444 | 6897.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 24447.770 | 17139.843 | 0.984510 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 12223.89 | 7663.34 | 0.656340 | 26.73 | 20.15 | 0.01210675 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 31.3462 | 23.88 | 0.01076873 | 58.1046 | 11153.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 25562.890 | 25562.890 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 25562.89 | 25562.89 | 0.984512 | 18.52 | 13.39 | 0.00746929 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 20.8974 | 21.11 | 0.00759516 | 48.7457 | 6902.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 24556.550 | 17216.106 | 0.988890 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 12278.27 | 7704.93 | 0.659260 | 26.72 | 20.14 | 0.01209547 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 31.2073 | 23.88 | 0.01076143 | 58.0659 | 11199.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 25662.902 | 25662.902 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 25662.90 | 25662.90 | 0.988892 | 18.53 | 13.40 | 0.00747560 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 20.8048 | 21.11 | 0.00760242 | 48.7918 | 7133.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 29184.740 | 20460.838 | 1.175270 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 14592.37 | 9448.20 | 0.783513 | 26.35 | 19.75 | 0.01171922 | 12.80 | 12.09 | 0.00850000 | 32.87 | 0.01716657 | 25.24 | 26.2583 | 23.88 | 0.01056327 | 57.0154 | 13325.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 29918.185 | 29918.185 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29918.18 | 29918.18 | 1.175269 | 18.94 | 13.59 | 0.00750833 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 17.5056 | 21.11 | 0.00761771 | 48.8891 | 8625.66 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 50712.190 | 35553.302 | 2.042180 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.0193 | 1004.8586 | 1.2027 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.042180 | 2.45620933 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 25356.10 | 16153.80 | 1.0000 | 1.63747293 | 1.361453 | 26.63 | 20.00 | 0.01193108 | 57189.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25356.10 | 33.20 | 0.01716721 | 25.32 | 0.41148071 | 30.2236 | 23.88 | 0.01060489 | 23.88 | 0.01060489 | 57.2353 | 23108.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52796.104 | 52796.104 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.042180 | 2.45620933 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 52796.10 | 52796.10 | 1.0000 | 2.45620933 | 2.042180 | 18.61 | 13.44 | 0.00748427 | 37675.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52796.10 | 8.70 | 0.00699286 | 8.70 | 0.41148071 | 20.1491 | 21.11 | 0.00760828 | 21.11 | 0.00760828 | 48.8288 | 13355.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25942.240 | 18187.586 | 1.044690 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.0436 | 1004.8586 | 1.2027 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.044694 | 1.25649439 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 12971.12 | 8248.62 | 1.0000 | 0.83765956 | 0.696460 | 26.61 | 20.00 | 0.01194417 | 57204.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12971.12 | 33.20 | 0.01716721 | 25.32 | 0.20573751 | 29.5405 | 23.88 | 0.01066332 | 23.88 | 0.01066332 | 57.5456 | 11842.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26936.905 | 26936.905 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.044694 | 1.25649439 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 26936.90 | 26936.90 | 1.0000 | 1.25649439 | 1.044694 | 18.67 | 13.44 | 0.00746573 | 37686.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26936.90 | 8.70 | 0.00699286 | 8.70 | 0.20573751 | 19.6936 | 21.11 | 0.00758169 | 21.11 | 0.00758169 | 48.6603 | 6466.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26219.430 | 18381.918 | 1.055860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.9925 | 1004.8586 | 1.2027 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.055856 | 1.26991949 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 13109.72 | 8357.29 | 1.0000 | 0.84661595 | 0.703907 | 26.59 | 19.97 | 0.01191667 | 57114.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13109.72 | 33.20 | 0.01716721 | 25.32 | 0.20573751 | 29.2280 | 23.88 | 0.01064557 | 23.88 | 0.01064557 | 57.4514 | 11966.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27191.746 | 27191.746 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.055856 | 1.26991949 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27191.75 | 27191.75 | 1.0000 | 1.26991949 | 1.055856 | 18.69 | 13.46 | 0.00746865 | 37720.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27191.75 | 8.70 | 0.00699286 | 8.70 | 0.20573751 | 19.4854 | 21.11 | 0.00758380 | 21.11 | 0.00758380 | 48.6736 | 6529.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26323.010 | 18454.536 | 1.060030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.9735 | 1004.8586 | 1.2027 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.060028 | 1.27493667 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 13161.50 | 8398.01 | 1.0000 | 0.84995957 | 0.706687 | 26.59 | 19.96 | 0.01190646 | 57081.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13161.50 | 33.20 | 0.01716721 | 25.32 | 0.20573751 | 29.1130 | 23.88 | 0.01063898 | 23.88 | 0.01063898 | 57.4164 | 12012.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27286.984 | 27286.984 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.060028 | 1.27493667 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27286.98 | 27286.98 | 1.0000 | 1.27493667 | 1.060028 | 18.70 | 13.46 | 0.00747074 | 37735.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27286.98 | 8.70 | 0.00699286 | 8.70 | 0.20573751 | 19.4087 | 21.11 | 0.00758583 | 21.11 | 0.00758583 | 48.6865 | 6591.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26145.180 | 18329.863 | 1.052870 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.0068 | 1004.8586 | 1.2027 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.052867 | 1.26632361 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 13072.59 | 8327.86 | 1.0000 | 0.84421849 | 0.701913 | 26.60 | 19.98 | 0.01192439 | 57139.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13072.59 | 33.20 | 0.01716721 | 25.32 | 0.20573751 | 29.3110 | 23.88 | 0.01065057 | 23.88 | 0.01065057 | 57.4779 | 11931.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27123.485 | 27123.485 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.052867 | 1.26632361 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27123.49 | 27123.49 | 1.0000 | 1.26632361 | 1.052867 | 18.68 | 13.46 | 0.00747378 | 37726.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27123.49 | 8.70 | 0.00699286 | 8.70 | 0.20573751 | 19.5407 | 21.11 | 0.00759057 | 21.11 | 0.00759057 | 48.7166 | 6727.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 46847.460 | 32843.817 | 1.886550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.3223 | 1004.8586 | 1.2027 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.886547 | 2.26902382 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 23423.73 | 14723.56 | 1.0000 | 1.51268476 | 1.257700 | 26.78 | 20.16 | 0.01209410 | 57759.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23423.73 | 33.20 | 0.01716721 | 25.32 | 0.41148071 | 32.7169 | 23.88 | 0.01067809 | 23.88 | 0.01067809 | 57.6226 | 21377.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 49242.774 | 49242.774 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.886547 | 2.26902382 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 49242.77 | 49242.77 | 1.0000 | 2.26902382 | 1.886547 | 18.40 | 13.35 | 0.00747827 | 37450.3 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49242.77 | 8.70 | 0.00699286 | 8.70 | 0.41148071 | 21.8113 | 21.11 | 0.00761367 | 21.11 | 0.00761367 | 48.8629 | 12765.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24552.620 | 17213.351 | 0.988730 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.3239 | 1004.8586 | 1.2027 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.988734 | 1.18918891 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 12276.31 | 7704.05 | 1.0000 | 0.79278938 | 0.659153 | 26.72 | 20.14 | 0.01209495 | 57696.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12276.31 | 33.20 | 0.01716721 | 25.32 | 0.20573751 | 31.2124 | 23.88 | 0.01076108 | 23.88 | 0.01076108 | 58.0640 | 11201.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25659.289 | 25659.289 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.988734 | 1.18918891 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 25659.29 | 25659.29 | 1.0000 | 1.18918891 | 0.988734 | 18.53 | 13.39 | 0.00746967 | 37555.3 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25659.29 | 8.70 | 0.00699286 | 8.70 | 0.20573751 | 20.8082 | 21.11 | 0.00759495 | 21.11 | 0.00759495 | 48.7444 | 6897.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24447.770 | 17139.843 | 0.984510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.3458 | 1004.8586 | 1.2027 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.984512 | 1.18411061 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 12223.89 | 7663.34 | 1.0000 | 0.78940567 | 0.656340 | 26.73 | 20.15 | 0.01210675 | 57735.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12223.89 | 33.20 | 0.01716721 | 25.32 | 0.20573751 | 31.3462 | 23.88 | 0.01076873 | 23.88 | 0.01076873 | 58.1046 | 11153.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25562.890 | 25562.890 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.984512 | 1.18411061 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 25562.89 | 25562.89 | 1.0000 | 1.18411061 | 0.984512 | 18.52 | 13.39 | 0.00746929 | 37543.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25562.89 | 8.70 | 0.00699286 | 8.70 | 0.20573751 | 20.8974 | 21.11 | 0.00759516 | 21.11 | 0.00759516 | 48.7457 | 6902.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24556.550 | 17216.106 | 0.988890 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.3249 | 1004.8586 | 1.2027 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.988892 | 1.18937936 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 12278.27 | 7704.93 | 1.0000 | 0.79291767 | 0.659260 | 26.72 | 20.14 | 0.01209547 | 57698.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12278.27 | 33.20 | 0.01716721 | 25.32 | 0.20573751 | 31.2073 | 23.88 | 0.01076143 | 23.88 | 0.01076143 | 58.0659 | 11199.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25662.902 | 25662.902 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.988892 | 1.18937936 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 25662.90 | 25662.90 | 1.0000 | 1.18937936 | 0.988892 | 18.53 | 13.40 | 0.00747560 | 37570.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25662.90 | 8.70 | 0.00699286 | 8.70 | 0.20573751 | 20.8048 | 21.11 | 0.00760242 | 21.11 | 0.00760242 | 48.7918 | 7133.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29184.740 | 20460.838 | 1.175270 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.6254 | 1004.8586 | 1.2027 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.175269 | 1.41354217 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 14592.37 | 9448.20 | 1.0000 | 0.94236199 | 0.783513 | 26.35 | 19.75 | 0.01171922 | 56363.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14592.37 | 32.87 | 0.01716657 | 25.24 | 0.20573751 | 26.2583 | 23.88 | 0.01056327 | 23.88 | 0.01056327 | 57.0154 | 13325.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29918.185 | 29918.185 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.175269 | 1.41354217 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 29918.18 | 29918.18 | 1.0000 | 1.41354217 | 1.175269 | 18.94 | 13.59 | 0.00750833 | 38070.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29918.18 | 8.70 | 0.00699286 | 8.70 | 0.20573751 | 17.5056 | 21.11 | 0.00761771 | 21.11 | 0.00761771 | 48.8891 | 8625.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
LGSTORE1 | LGSTORE1_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE1 | SMSTORE1_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE2 | SMSTORE2_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE3 | SMSTORE3_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE4 | SMSTORE4_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LGSTORE2 | LGSTORE2_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE5 | SMSTORE5_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE6 | SMSTORE6_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE7 | SMSTORE7_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE8 | SMSTORE8_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 5103.50 | 1030.50 | 790.50 |
SMSTORE1 | 4919.50 | 815.50 | 625.17 |
SMSTORE2 | 3906.17 | 990.67 | 848.67 |
SMSTORE3 | 3899.83 | 979.83 | 833.83 |
SMSTORE4 | 3880.67 | 1060.50 | 898.50 |
LGSTORE2 | 3523.00 | 1327.33 | 1162.83 |
SMSTORE5 | 3472.67 | 1390.00 | 1207.67 |
SMSTORE6 | 3461.17 | 1413.50 | 1224.83 |
SMSTORE7 | 3450.17 | 1433.50 | 1230.33 |
SMSTORE8 | 3505.67 | 1084.33 | 868.17 |
Facility | 5245.83 | 1892.33 | 1547.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.17 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.67 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.33 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.33 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.33 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 0.83 | 0.00 | 0.00 |
Facility | 0.00 | 1.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.548 | 0.349 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.467 | 0.386 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.525 | 0.505 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.525 | 0.505 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.525 | 0.505 | 0.000 | 0.000 |
LGSTORE2 | 24.81 | 56.25 | 1805.20 | 0.605 | 0.473 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.605 | 0.539 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.605 | 0.539 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.605 | 0.539 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.605 | 0.560 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.441 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.005 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.439 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.439 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.439 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.81 | 56.25 | 1805.20 | 0.465 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.465 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.465 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.465 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.464 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.212 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE2 | PSZ-AC_3:3 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE3 | PSZ-AC_4:4 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE4 | PSZ-AC_5:5 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
LGSTORE2 | PSZ-AC_6:6 | 24.81 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.212 |
SMSTORE5 | PSZ-AC_7:7 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE6 | PSZ-AC_8:8 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE7 | PSZ-AC_9:9 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE8 | PSZ-AC_10:10 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
Total Facility | 121.09 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 1.274 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 5717024.02 | 0.00 | 5717024.02 | 3922069.04 | 9639093.05 | 7870781.79 | 2817.00 | 5943.00 | 0.00 | 103.00 |
SMSTORE1 | 2444157.83 | 0.00 | 2444157.83 | 2084204.97 | 4528362.81 | 3935374.10 | 4302.67 | 4457.33 | 0.00 | 103.00 |
SMSTORE2 | 2172709.30 | 0.00 | 2172709.30 | 2120315.80 | 4293025.10 | 3701819.01 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE3 | 2172709.31 | 0.00 | 2172709.31 | 2120315.80 | 4293025.11 | 3701819.01 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE4 | 2172709.48 | 0.00 | 2172709.48 | 2120315.80 | 4293025.28 | 3701819.01 | 4000.00 | 4760.00 | 0.00 | 365.00 |
LGSTORE2 | 4570579.31 | 0.00 | 4570579.31 | 3775854.81 | 8346434.12 | 7907875.00 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE5 | 2285272.90 | 0.00 | 2285272.90 | 2129269.13 | 4414542.03 | 3953920.18 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE6 | 2285272.86 | 0.00 | 2285272.86 | 2129269.13 | 4414542.00 | 3953920.18 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE7 | 2285272.93 | 0.00 | 2285272.93 | 2129269.13 | 4414542.07 | 3953920.18 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE8 | 2285278.43 | 0.00 | 2285278.43 | 2433207.91 | 4718486.34 | 3953920.18 | 4365.00 | 4395.00 | 0.00 | 365.00 |
Total Facility | 28390986.38 | 0.00 | 28390986.38 | 24964091.53 | 53355077.91 | 46635168.64 | 4365.00 | 6246.00 | 0.00 | 730.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.2682 | 0.0000 | 0.2682 | 0.1706 | 0.4388 | 0.2682 | 0.00 | 5840.00 | 0.00 |
SMSTORE1 | 0.1144 | 0.0000 | 0.1144 | 0.0943 | 0.2087 | 0.1341 | 1485.67 | 4354.33 | 0.00 |
SMSTORE2 | 0.1285 | 0.0000 | 0.1285 | 0.1235 | 0.2520 | 0.1285 | 0.00 | 4395.00 | 0.00 |
SMSTORE3 | 0.1285 | 0.0000 | 0.1285 | 0.1235 | 0.2520 | 0.1285 | 0.00 | 4395.00 | 0.00 |
SMSTORE4 | 0.1285 | 0.0000 | 0.1285 | 0.1235 | 0.2520 | 0.1285 | 0.00 | 4395.00 | 0.00 |
LGSTORE2 | 0.2958 | 0.0000 | 0.2958 | 0.2311 | 0.5269 | 0.2958 | 0.00 | 4030.00 | 0.00 |
SMSTORE5 | 0.1479 | 0.0000 | 0.1479 | 0.1316 | 0.2795 | 0.1479 | 0.00 | 4030.00 | 0.00 |
SMSTORE6 | 0.1479 | 0.0000 | 0.1479 | 0.1316 | 0.2795 | 0.1479 | 0.00 | 4030.00 | 0.00 |
SMSTORE7 | 0.1479 | 0.0000 | 0.1479 | 0.1316 | 0.2795 | 0.1479 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.1479 | 0.0000 | 0.1479 | 0.1368 | 0.2847 | 0.1479 | 0.00 | 4030.00 | 0.00 |
Total Facility | 1.6555 | 0.0000 | 1.6555 | 1.3982 | 3.0537 | 1.6752 | 1485.67 | 5943.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 8270152.87 | 0.00 | 8270152.87 | 7870781.79 | 2817.00 | 0.00 | 5943.00 | 103.00 |
PSZ-AC_2:2 | 3535688.03 | 0.00 | 3535688.03 | 3935374.10 | 4243.00 | 5.33 | 4511.67 | 103.00 |
PSZ-AC_3:3 | 3143003.50 | 0.00 | 3143003.50 | 3701819.01 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_4:4 | 3143003.50 | 0.00 | 3143003.50 | 3701819.01 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_5:5 | 3143003.50 | 0.00 | 3143003.50 | 3701819.01 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_6:6 | 6611740.72 | 0.00 | 6611740.72 | 7907875.00 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_7:7 | 3305845.30 | 0.00 | 3305845.30 | 3953920.18 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_8:8 | 3305845.30 | 0.00 | 3305845.30 | 3953920.18 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_9:9 | 3305845.30 | 0.00 | 3305845.30 | 3953920.18 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_10:10 | 3305845.30 | 0.00 | 3305845.30 | 3953920.18 | 4365.00 | 0.00 | 4395.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.3879 | 0.0000 | 0.3879 | 0.2682 | 0.00 | 0.00 | 5840.00 |
PSZ-AC_2:2 | 0.1655 | 0.0000 | 0.1655 | 0.1341 | 1426.00 | 5.33 | 4408.67 |
PSZ-AC_3:3 | 0.1859 | 0.0000 | 0.1859 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.1859 | 0.0000 | 0.1859 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.1859 | 0.0000 | 0.1859 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.4279 | 0.0000 | 0.4279 | 0.2958 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2140 | 0.0000 | 0.2140 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2140 | 0.0000 | 0.2140 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2140 | 0.0000 | 0.2140 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2140 | 0.0000 | 0.2140 | 0.1479 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.3879 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.1655 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.1859 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.1859 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.1859 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.4280 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2140 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2140 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2140 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2140 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 835 |
Defaulted Fields | 817 |
Fields with Defaults | 2693 |
Autosized Fields | 174 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 983.62 | 2102.83 | 01-JAN-07:20 | 90041.90 | 29-JUL-13:30 |
Electricity:Building | 405.94 | 891.83 | 01-JAN-00:20 | 25756.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 90.96 | 148.64 | 01-JAN-00:20 | 4765.21 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 405.94 | 891.83 | 01-JAN-00:20 | 25756.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 64.71 | 75.00 | 01-JAN-00:20 | 3421.96 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 64.71 | 75.00 | 01-JAN-00:20 | 3421.96 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 52.56 | 74.32 | 01-JAN-00:20 | 2762.01 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 39.44 | 37.50 | 01-JAN-00:20 | 2090.38 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 39.44 | 37.50 | 01-JAN-00:20 | 2090.38 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 47.80 | 148.64 | 01-JAN-00:10 | 3421.36 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 28.62 | 75.00 | 01-JAN-00:10 | 2078.11 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 28.62 | 75.00 | 01-JAN-00:10 | 2078.11 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityProduced:Facility | 67.87 | -0.00 | 03-APR-18:30 | 11018.55 | 06-MAY-11:30 |
ElectricityProduced:Plant | 67.87 | -0.00 | 03-APR-18:30 | 11018.55 | 06-MAY-11:30 |
Photovoltaic:ElectricityProduced | 70.85 | 0.00 | 01-JAN-00:10 | 11475.14 | 06-MAY-11:30 |
PowerConversion:ElectricityProduced | -2.98 | -456.59 | 06-MAY-11:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 58.77 | 1211.00 | 11-JUN-08:10 | 11779.33 | 10-JAN-12:40 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 915.75 | 228.47 | 29-MAY-07:00 | 85993.97 | 28-JUL-16:40 |
ElectricityPurchased:Plant | 915.75 | 228.47 | 29-MAY-07:00 | 85993.97 | 28-JUL-16:40 |
Cogeneration:ElectricityPurchased | 915.75 | 228.47 | 29-MAY-07:00 | 85993.97 | 28-JUL-16:40 |
General:Cogeneration:ElectricityPurchased | 915.75 | 228.47 | 29-MAY-07:00 | 85993.97 | 28-JUL-16:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 915.75 | 228.47 | 29-MAY-07:00 | 85993.97 | 28-JUL-16:40 |
ElectricityNet:Plant | 915.75 | 228.47 | 29-MAY-07:00 | 85993.97 | 28-JUL-16:40 |
Cogeneration:ElectricityNet | 915.75 | 228.47 | 29-MAY-07:00 | 85993.97 | 28-JUL-16:40 |
General:Cogeneration:ElectricityNet | 915.75 | 228.47 | 29-MAY-07:00 | 85993.97 | 28-JUL-16:40 |
Electricity:HVAC | 477.90 | 0.00 | 01-JAN-00:10 | 60340.30 | 29-JUL-14:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 381.89 | 0.00 | 01-JAN-00:10 | 52146.78 | 29-JUL-14:00 |
General:Cooling:Electricity | 381.89 | 0.00 | 01-JAN-00:10 | 52146.78 | 29-JUL-14:00 |
Fans:Electricity | 96.01 | 0.00 | 01-JAN-00:10 | 8364.09 | 22-AUG-13:00 |
General:Fans:Electricity | 96.01 | 0.00 | 01-JAN-00:10 | 8364.09 | 22-AUG-13:00 |
ExteriorLights:Electricity | 41.00 | 0.00 | 01-JAN-07:20 | 3786.68 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 41.00 | 0.00 | 01-JAN-07:20 | 3786.68 | 01-JAN-06:10 |
WaterSystems:Electricity | 58.77 | 1211.00 | 11-JUN-08:10 | 11779.33 | 10-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 58.77 | 1211.00 | 11-JUN-08:10 | 11779.33 | 10-JAN-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.11 | 0.00 | 01-JAN-00:10 | 20815.34 | 04-FEB-08:10 |
NaturalGas:HVAC | 0.11 | 0.00 | 01-JAN-00:10 | 20815.34 | 04-FEB-08:10 |
Heating:NaturalGas | 0.11 | 0.00 | 01-JAN-00:10 | 20815.34 | 04-FEB-08:10 |
General:Heating:NaturalGas | 0.11 | 0.00 | 01-JAN-00:10 | 20815.34 | 04-FEB-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2462.48 | 0.00 | 01-JAN-00:10 | 321300.75 | 22-AUG-13:00 |
EnergyTransfer:Building | 832.59 | 0.00 | 01-JAN-00:10 | 106778.42 | 29-JUL-16:00 |
EnergyTransfer:Zone:LGSTORE1 | 170.75 | 0.00 | 01-JAN-00:10 | 18635.25 | 29-JUL-16:10 |
Heating:EnergyTransfer | 3.70 | 0.00 | 01-JAN-00:10 | 13004.02 | 29-JUL-17:20 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.27 | 0.00 | 01-JAN-00:10 | 1842.64 | 21-JUL-07:20 |
General:Heating:EnergyTransfer | 3.70 | 0.00 | 01-JAN-00:10 | 13004.02 | 29-JUL-17:20 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.27 | 0.00 | 01-JAN-00:10 | 1842.64 | 21-JUL-07:20 |
Cooling:EnergyTransfer | 828.89 | 0.00 | 01-JAN-00:10 | 106778.42 | 29-JUL-16:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 170.48 | 0.00 | 01-JAN-00:10 | 18635.25 | 29-JUL-16:10 |
General:Cooling:EnergyTransfer | 828.89 | 0.00 | 01-JAN-00:10 | 106778.42 | 29-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 170.48 | 0.00 | 01-JAN-00:10 | 18635.25 | 29-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 88.18 | 0.00 | 01-JAN-00:10 | 9030.16 | 29-JUL-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.13 | 0.00 | 01-JAN-00:10 | 903.52 | 02-SEP-07:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.13 | 0.00 | 01-JAN-00:10 | 903.52 | 02-SEP-07:20 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 88.05 | 0.00 | 01-JAN-00:10 | 9030.16 | 29-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 88.05 | 0.00 | 01-JAN-00:10 | 9030.16 | 29-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE2 | 68.13 | 0.00 | 01-JAN-00:10 | 8950.86 | 29-JUL-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 0.53 | 0.00 | 01-JAN-00:10 | 1414.54 | 29-JUL-17:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 0.53 | 0.00 | 01-JAN-00:10 | 1414.54 | 29-JUL-17:20 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 67.60 | 0.00 | 01-JAN-00:10 | 8950.86 | 29-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 67.60 | 0.00 | 01-JAN-00:10 | 8950.86 | 29-JUL-14:00 |
EnergyTransfer:Zone:SMSTORE3 | 68.32 | 0.00 | 01-JAN-00:10 | 8984.01 | 29-JUL-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 0.52 | 0.00 | 01-JAN-00:10 | 1415.09 | 29-JUL-17:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 0.52 | 0.00 | 01-JAN-00:10 | 1415.09 | 29-JUL-17:20 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 67.80 | 0.00 | 01-JAN-00:10 | 8984.01 | 29-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 67.80 | 0.00 | 01-JAN-00:10 | 8984.01 | 29-JUL-14:00 |
EnergyTransfer:Zone:SMSTORE4 | 66.60 | 0.00 | 01-JAN-00:10 | 8882.19 | 29-JUL-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 0.53 | 0.00 | 01-JAN-00:10 | 1418.36 | 29-JUL-17:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 0.53 | 0.00 | 01-JAN-00:10 | 1418.36 | 29-JUL-17:20 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 66.07 | 0.00 | 01-JAN-00:10 | 8882.19 | 29-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 66.07 | 0.00 | 01-JAN-00:10 | 8882.19 | 29-JUL-14:00 |
EnergyTransfer:Zone:LGSTORE2 | 117.43 | 0.00 | 01-JAN-00:10 | 16711.24 | 29-JUL-14:40 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 0.56 | 0.00 | 01-JAN-00:10 | 2910.29 | 29-JUL-17:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 0.56 | 0.00 | 01-JAN-00:10 | 2910.29 | 29-JUL-17:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 116.86 | 0.00 | 01-JAN-00:10 | 16711.24 | 29-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 116.86 | 0.00 | 01-JAN-00:10 | 16711.24 | 29-JUL-14:40 |
EnergyTransfer:Zone:SMSTORE5 | 60.84 | 0.00 | 01-JAN-00:10 | 8843.54 | 29-JUL-14:40 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.28 | 0.00 | 01-JAN-00:10 | 1475.99 | 29-JUL-17:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 0.28 | 0.00 | 01-JAN-00:10 | 1475.99 | 29-JUL-17:20 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 60.55 | 0.00 | 01-JAN-00:10 | 8843.54 | 29-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 60.55 | 0.00 | 01-JAN-00:10 | 8843.54 | 29-JUL-14:40 |
EnergyTransfer:Zone:SMSTORE6 | 60.36 | 0.00 | 01-JAN-00:10 | 8816.77 | 29-JUL-14:40 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.29 | 0.00 | 01-JAN-00:10 | 1475.49 | 29-JUL-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 0.29 | 0.00 | 01-JAN-00:10 | 1475.49 | 29-JUL-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 60.07 | 0.00 | 01-JAN-00:10 | 8816.77 | 29-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 60.07 | 0.00 | 01-JAN-00:10 | 8816.77 | 29-JUL-14:40 |
EnergyTransfer:Zone:SMSTORE7 | 60.09 | 0.00 | 01-JAN-00:10 | 8897.51 | 29-JUL-14:40 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.29 | 0.00 | 01-JAN-00:10 | 1477.64 | 29-JUL-17:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 0.29 | 0.00 | 01-JAN-00:10 | 1477.64 | 29-JUL-17:20 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 59.80 | 0.00 | 01-JAN-00:10 | 8897.51 | 29-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 59.80 | 0.00 | 01-JAN-00:10 | 8897.51 | 29-JUL-14:40 |
EnergyTransfer:Zone:SMSTORE8 | 71.90 | 0.00 | 01-JAN-00:10 | 10726.61 | 29-JUL-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.30 | 0.00 | 01-JAN-00:10 | 6482.79 | 04-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 0.30 | 0.00 | 01-JAN-00:10 | 6482.79 | 04-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 71.60 | 0.00 | 01-JAN-00:10 | 10726.61 | 29-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 71.60 | 0.00 | 01-JAN-00:10 | 10726.61 | 29-JUL-14:10 |
EnergyTransfer:HVAC | 1629.89 | 0.00 | 01-JAN-00:10 | 222090.95 | 22-AUG-13:00 |
HeatingCoils:EnergyTransfer | 0.09 | 0.00 | 01-JAN-00:10 | 16652.27 | 04-FEB-08:10 |
CoolingCoils:EnergyTransfer | 1629.80 | 0.00 | 01-JAN-00:10 | 222090.95 | 22-AUG-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.269 | -170.478 | 0.000 | 0.000 | 23.232 | 64.707 | 26.249 | 17.151 | 0.000 | 15.357 | 30.585 | 0.000 | -2.935 | 0.000 | -4.136 | -0.002 |
SMSTORE1 | 0.000 | 0.000 | 0.128 | -88.053 | 0.000 | 0.000 | 11.612 | 39.440 | 13.125 | 8.599 | 0.000 | 8.528 | 10.093 | 0.000 | -1.480 | 0.000 | -1.992 | -0.000 |
SMSTORE2 | 0.000 | 0.000 | 0.525 | -67.600 | 0.000 | 0.000 | 6.978 | 28.854 | 10.421 | 8.522 | 0.000 | 8.378 | 7.670 | 0.000 | -1.598 | 0.000 | -2.150 | -0.000 |
SMSTORE3 | 0.000 | 0.000 | 0.522 | -67.798 | 0.000 | 0.000 | 6.978 | 28.854 | 10.421 | 8.519 | 0.000 | 8.374 | 7.882 | 0.000 | -1.604 | 0.000 | -2.149 | -0.001 |
SMSTORE4 | 0.000 | 0.000 | 0.532 | -66.066 | 0.000 | 0.000 | 6.980 | 28.854 | 10.421 | 8.531 | 0.000 | 8.380 | 6.072 | 0.000 | -1.577 | 0.000 | -2.126 | -0.001 |
LGSTORE2 | 0.000 | 0.000 | 0.565 | -116.861 | 0.000 | 0.000 | 23.957 | 28.624 | 19.173 | 17.087 | 0.000 | 14.748 | 19.555 | 0.000 | -3.019 | 0.000 | -3.828 | -0.000 |
SMSTORE5 | 0.000 | 0.000 | 0.285 | -60.553 | 0.000 | 0.000 | 11.980 | 14.614 | 9.586 | 8.555 | 0.000 | 8.398 | 10.718 | 0.000 | -1.484 | 0.000 | -2.099 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 0.286 | -60.073 | 0.000 | 0.000 | 11.981 | 14.614 | 9.586 | 8.561 | 0.000 | 8.400 | 10.213 | 0.000 | -1.476 | 0.000 | -2.092 | -0.000 |
SMSTORE7 | 0.000 | 0.000 | 0.289 | -59.796 | 0.000 | 0.000 | 11.983 | 14.614 | 9.586 | 8.561 | 0.000 | 8.400 | 9.897 | 0.000 | -1.465 | 0.000 | -2.070 | -0.000 |
SMSTORE8 | 0.000 | 0.000 | 0.299 | -71.595 | 0.000 | 0.000 | 11.982 | 14.614 | 9.586 | 8.475 | 0.000 | 8.747 | 22.107 | 0.000 | -1.448 | 0.000 | -2.768 | -0.000 |
Total Facility | 0.000 | 0.000 | 3.700 | -828.873 | 0.000 | 0.000 | 127.662 | 277.790 | 128.154 | 102.560 | 0.000 | 97.710 | 134.791 | 0.000 | -18.088 | 0.000 | -25.408 | -0.005 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -34847.41 | 0.00 | 0.00 | 175.13 | 75.00 | 74.62 | 28.15 | 0.00 | 56.60 | 34437.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 02-JUL-07:02 | 0.00 | 0.00 | 0.00 | -19087.50 | 0.00 | 0.00 | 85.39 | 37.50 | 37.31 | 122.32 | 0.00 | 43.05 | 18761.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 18-OCT-06:02 | 0.00 | 0.00 | 0.00 | -18193.78 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 1.53 | 18159.01 | 0.00 | -41.08 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 18-OCT-06:02 | 0.00 | 0.00 | 0.00 | -18283.45 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 1.45 | 18249.34 | 0.00 | -41.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 18-OCT-06:02 | 0.00 | 0.00 | 0.00 | -18068.69 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 1.81 | 18032.56 | 0.00 | -40.01 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -32630.11 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 31.39 | 0.00 | 52.62 | 32397.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -17024.60 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 17.14 | 0.00 | 33.19 | 16899.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -16938.65 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 17.59 | 0.00 | 33.71 | 16813.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -16949.45 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 17.99 | 0.00 | 36.91 | 16820.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -19086.29 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 17.67 | 0.00 | 47.09 | 18947.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -163013.83 | 0.00 | 0.00 | 557.98 | 450.00 | 1452.23 | 225.13 | 0.00 | 454.87 | 159873.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 04-FEB-08:62 | 0.00 | 0.00 | 5752.64 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 186.85 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1298.95 | -4789.17 |
SMSTORE1 | 15-AUG-07:05 | 0.00 | 0.00 | 1465.63 | 0.00 | 0.00 | 0.00 | 84.38 | 37.50 | 37.31 | 162.99 | 0.00 | 210.88 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1998.69 |
SMSTORE2 | 29-JUL-17:12 | 0.00 | 0.00 | 1631.79 | 0.00 | 0.00 | 0.00 | 83.22 | 1027.84 | 373.13 | 318.85 | 0.00 | 353.02 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3787.85 |
SMSTORE3 | 29-JUL-17:12 | 0.00 | 0.00 | 1633.31 | 0.00 | 0.00 | 0.00 | 83.18 | 1027.84 | 373.13 | 318.68 | 0.00 | 352.91 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3789.04 |
SMSTORE4 | 29-JUL-17:12 | 0.00 | 0.00 | 1632.99 | 0.00 | 0.00 | 0.00 | 83.37 | 1027.84 | 373.13 | 319.24 | 0.00 | 353.59 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3790.16 |
LGSTORE2 | 29-JUL-17:12 | 0.00 | 0.00 | 3293.32 | 0.00 | 0.00 | 0.00 | 369.63 | 1093.75 | 746.25 | 636.63 | 0.00 | 630.73 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6770.30 |
SMSTORE5 | 29-JUL-17:12 | 0.00 | 0.00 | 1681.87 | 0.00 | 0.00 | 0.00 | 184.97 | 558.95 | 373.13 | 322.08 | 0.00 | 356.16 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3477.16 |
SMSTORE6 | 29-JUL-17:12 | 0.00 | 0.00 | 1679.95 | 0.00 | 0.00 | 0.00 | 185.08 | 558.95 | 373.13 | 322.34 | 0.00 | 356.30 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3475.74 |
SMSTORE7 | 29-JUL-17:12 | 0.00 | 0.00 | 1682.87 | 0.00 | 0.00 | 0.00 | 184.82 | 558.95 | 373.13 | 321.38 | 0.00 | 356.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3477.14 |
SMSTORE8 | 04-FEB-08:62 | 0.00 | 0.00 | 27493.96 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 125.81 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -776.73 | -26917.36 |
Total Facility | 04-FEB-08:62 | -10134.47 | 10134.47 | 34864.68 | -10134.47 | 0.00 | 0.00 | 346.34 | 450.00 | 1450.75 | 1052.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7920.08 | -20109.68 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0422 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0422 | 0.2015 | 1.0000 | Not calculated | 0.4115 | 0.2015 | ||
PSZ-AC_2:2 | 1.0447 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0447 | 0.1969 | 1.0000 | Not calculated | 0.2057 | 0.1969 | ||
PSZ-AC_3:3 | 1.0559 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0559 | 0.1949 | 1.0000 | Not calculated | 0.2057 | 0.1949 | ||
PSZ-AC_4:4 | 1.0600 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0600 | 0.1941 | 1.0000 | Not calculated | 0.2057 | 0.1941 | ||
PSZ-AC_5:5 | 1.0529 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0529 | 0.1954 | 1.0000 | Not calculated | 0.2057 | 0.1954 | ||
PSZ-AC_6:6 | 1.8865 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8865 | 0.2181 | 1.0000 | Not calculated | 0.4115 | 0.2181 | ||
PSZ-AC_7:7 | 0.9887 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9887 | 0.2081 | 1.0000 | Not calculated | 0.2057 | 0.2081 | ||
PSZ-AC_8:8 | 0.9845 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9845 | 0.2090 | 1.0000 | Not calculated | 0.2057 | 0.2090 | ||
PSZ-AC_9:9 | 0.9889 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9889 | 0.2080 | 1.0000 | Not calculated | 0.2057 | 0.2080 | ||
PSZ-AC_10:10 | 1.1753 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1753 | 0.1751 | 1.0000 | Not calculated | 0.2057 | 0.1751 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0422 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0422 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2015 | ||
PSZ-AC_2:2 | 1.0447 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0447 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1969 | ||
PSZ-AC_3:3 | 1.0559 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0559 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1949 | ||
PSZ-AC_4:4 | 1.0600 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0600 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1941 | ||
PSZ-AC_5:5 | 1.0529 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0529 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1954 | ||
PSZ-AC_6:6 | 1.8865 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8865 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2181 | ||
PSZ-AC_7:7 | 0.9887 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9887 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2081 | ||
PSZ-AC_8:8 | 0.9845 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9845 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2090 | ||
PSZ-AC_9:9 | 0.9889 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9889 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2080 | ||
PSZ-AC_10:10 | 1.1753 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1753 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1751 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.003540 | 56.2505 | 0.000610 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.003540 | 56.2505 | 0.000610 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.003540 | 56.25 | 0.000610 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.003540 | 56.25 | 0.000610 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0422 | 2.0422 | 2.0422 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0447 | 1.0447 | 1.0447 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0559 | 1.0559 | 1.0559 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0600 | 1.0600 | 1.0600 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0529 | 1.0529 | 1.0529 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8865 | 1.8865 | 1.8865 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9887 | 0.9887 | 0.9887 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9845 | 0.9845 | 0.9845 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9889 | 0.9889 | 0.9889 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1753 | 1.1753 | 1.1753 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0422 | 2.0422 | 2.0422 | 2.0422 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0447 | 1.0447 | 1.0447 | 1.0447 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0559 | 1.0559 | 1.0559 | 1.0559 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0600 | 1.0600 | 1.0600 | 1.0600 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0529 | 1.0529 | 1.0529 | 1.0529 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8865 | 1.8865 | 1.8865 | 1.8865 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9887 | 0.9887 | 0.9887 | 0.9887 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9845 | 0.9845 | 0.9845 | 0.9845 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9889 | 0.9889 | 0.9889 | 0.9889 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.1753 | 1.1753 | 1.1753 | 1.1753 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0422 | 2.0422 | 2.0422 | No | 0.4115 | 0.5948 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0447 | 1.0447 | 1.0447 | No | 0.2057 | 0.6143 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0559 | 1.0559 | 1.0559 | No | 0.2057 | 0.6083 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0600 | 1.0600 | 1.0600 | No | 0.2057 | 0.6026 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0529 | 1.0529 | 1.0529 | No | 0.2057 | 0.5905 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8865 | 1.8865 | 1.8865 | No | 0.4115 | 0.6224 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9887 | 0.9887 | 0.9887 | No | 0.2057 | 0.5759 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9845 | 0.9845 | 0.9845 | No | 0.2057 | 0.5755 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9889 | 0.9889 | 0.9889 | No | 0.2057 | 0.5568 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1753 | 1.1753 | 1.1753 | No | 0.2057 | 0.4605 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0422 | 2.0422 | 2.0422 | 2.0422 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0447 | 1.0447 | 1.0447 | 1.0447 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0559 | 1.0559 | 1.0559 | 1.0559 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0600 | 1.0600 | 1.0600 | 1.0600 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0529 | 1.0529 | 1.0529 | 1.0529 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8865 | 1.8865 | 1.8865 | 1.8865 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9887 | 0.9887 | 0.9887 | 0.9887 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9845 | 0.9845 | 0.9845 | 0.9845 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9889 | 0.9889 | 0.9889 | 0.9889 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.1753 | 1.1753 | 1.1753 | 1.1753 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.11 | 20815.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 381.89 | 52146.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 277.79 | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 41.00 | 3786.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 96.01 | 8364.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 58.77 | 11779.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 983.62 |
Natural Gas | 0.00 | 0.11 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 983.73 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 70.85 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 132.89 |
Space Heating | 0.00 |
Space Cooling | 182.69 |
Fans (All) | 45.93 |
Service Water Heating | 28.11 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 470.56 |
Subtotal | 470.56 |
Natural Gas [MJ/m2] | |
Space Heating | 0.06 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.06 |
Subtotal | 0.06 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 28.24 |
Space Heating | 0.01 |
Space Cooling | 38.82 |
Fans (All) | 9.76 |
Service Water Heating | 5.97 |
Receptacle Equipment | 13.03 |
Miscellaneous | 4.17 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3140. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3200. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4323. | 8760. |
LTG_SCH_BASE_LPD1 | 4243. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3479. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8268.83 | 491.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8184.17 | 575.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8296.67 | 463.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8386.67 | 373.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8413.17 | 346.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8419.33 | 340.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8421.83 | 338.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8226.17 | 533.83 | 0.00 | 0.00 | 0.00 |
Min | 8184.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 575.83 | 0.00 | 0.00 | 0.00 |
Average | 8413.65 | 346.35 | 0.00 | 0.00 | 0.00 |
Sum | 84136.50 | 3463.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25417.50 | 57.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25417.33 | 57.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25421.83 | 53.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93047.00 | 164.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45832.00 | 80.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45832.00 | 80.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45832.00 | 80.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45814.00 | 98.00 | 0.00 | 0.00 | 0.00 |
Min | 25417.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93047.00 | 164.00 | 0.00 | 0.00 | 0.00 |
Average | 48543.17 | 67.03 | 0.00 | 0.00 | 0.00 |
Sum | 485431.67 | 670.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 5956.67 | 2803.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 7445.50 | 1314.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 4270.83 | 4489.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 4287.17 | 4472.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 4231.00 | 4529.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 4045.33 | 4714.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 4034.83 | 4725.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 4017.00 | 4743.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 4049.33 | 4710.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 4321.83 | 4438.17 | 0.00 | 0.00 | 0.00 |
Min | 4017.00 | 1314.50 | 0.00 | 0.00 | 0.00 |
Max | 7445.50 | 4743.00 | 0.00 | 0.00 | 0.00 |
Average | 4665.95 | 4094.05 | 0.00 | 0.00 | 0.00 |
Sum | 46659.50 | 40940.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 75368.83 | 13672.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 36290.33 | 7486.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 19512.33 | 5962.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 19572.00 | 5903.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 19224.50 | 6250.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 60350.50 | 32860.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 28825.83 | 17086.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 28637.83 | 17274.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 28719.83 | 17192.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 34220.50 | 11691.50 | 0.00 | 0.00 | 0.00 |
Min | 19224.50 | 5903.00 | 0.00 | 0.00 | 0.00 |
Max | 75368.83 | 32860.50 | 0.00 | 0.00 | 0.00 |
Average | 35072.25 | 13537.95 | 0.00 | 0.00 | 0.00 |
Sum | 350722.50 | 135379.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:19
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.880937E+10 | 25995.36 | 14-JAN-08:62 | 21.15 | 19.82 | 0.140636E+10 | 1686.02 | 07-JAN-13:00 | 21.15 | 19.82 |
February | 0.954487E+10 | 28361.17 | 18-FEB-08:62 | 23.40 | 20.75 | 0.126900E+10 | 1686.02 | 19-FEB-17:10 | 26.42 | 21.64 |
March | 0.108485E+11 | 25459.88 | 05-MAR-08:62 | 23.98 | 22.69 | 0.139327E+10 | 1686.00 | 04-MAR-13:30 | 23.98 | 22.69 |
April | 0.131896E+11 | 29777.78 | 14-APR-07:03 | 24.18 | 22.69 | 0.136151E+10 | 1686.03 | 09-APR-17:19 | 24.18 | 22.69 |
May | 0.161448E+11 | 31866.36 | 09-MAY-07:03 | 25.68 | 20.64 | 0.140170E+10 | 1686.04 | 28-MAY-12:09 | 30.55 | 25.86 |
June | 0.167894E+11 | 30706.08 | 12-JUN-07:01 | 26.47 | 24.56 | 0.135473E+10 | 1686.07 | 11-JUN-12:39 | 26.47 | 24.56 |
July | 0.189547E+11 | 34301.35 | 02-JUL-07:02 | 25.97 | 21.70 | 0.141293E+10 | 1686.05 | 07-JUL-12:20 | 33.33 | 23.94 |
August | 0.180780E+11 | 31629.71 | 08-AUG-07:02 | 28.07 | 24.21 | 0.139424E+10 | 1686.06 | 11-AUG-12:39 | 29.60 | 24.54 |
September | 0.179223E+11 | 31981.47 | 11-SEP-07:01 | 26.78 | 24.35 | 0.136533E+10 | 1686.07 | 16-SEP-12:39 | 30.40 | 23.98 |
October | 0.168726E+11 | 34856.44 | 18-OCT-07:02 | 25.18 | 18.80 | 0.140985E+10 | 1686.07 | 13-OCT-12:39 | 25.18 | 18.80 |
November | 0.131942E+11 | 30877.92 | 20-NOV-08:62 | 24.50 | 20.57 | 0.136281E+10 | 1686.04 | 03-NOV-12:50 | 24.50 | 20.57 |
December | 0.101327E+11 | 32576.82 | 01-DEC-08:62 | 23.48 | 18.65 | 0.141376E+10 | 1686.02 | 02-DEC-13:39 | 26.50 | 20.46 |
Annual Sum or Average | 0.170481E+12 | 0.165455E+11 | ||||||||
Minimum of Months | 0.880937E+10 | 25459.88 | 21.15 | 18.65 | 0.126900E+10 | 1686.00 | 21.15 | 18.80 | ||
Maximum of Months | 0.189547E+11 | 34856.44 | 28.07 | 24.56 | 0.141376E+10 | 1686.07 | 33.33 | 25.86 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.493652E+10 | 14790.27 | 14-JAN-08:62 | 21.15 | 19.82 | 0.703977E+09 | 843.17 | 15-JAN-18:30 | 18.30 | 16.71 |
February | 0.516088E+10 | 16365.39 | 18-FEB-08:62 | 23.40 | 20.75 | 0.635638E+09 | 843.00 | 11-FEB-13:00 | 23.40 | 20.75 |
March | 0.574926E+10 | 15320.57 | 05-MAR-08:62 | 23.98 | 22.69 | 0.697578E+09 | 842.98 | 05-MAR-13:09 | 27.88 | 23.38 |
April | 0.680358E+10 | 16296.04 | 14-APR-07:03 | 24.18 | 22.69 | 0.680760E+09 | 843.12 | 23-APR-17:30 | 26.15 | 20.95 |
May | 0.819004E+10 | 18062.41 | 22-MAY-07:02 | 25.28 | 21.64 | 0.700838E+09 | 843.09 | 28-MAY-17:19 | 24.43 | 23.17 |
June | 0.853637E+10 | 17650.78 | 12-JUN-07:01 | 26.47 | 24.56 | 0.677350E+09 | 843.01 | 02-JUN-12:39 | 26.47 | 24.56 |
July | 0.950481E+10 | 19089.22 | 02-JUL-07:02 | 25.97 | 21.70 | 0.706448E+09 | 843.01 | 16-JUL-17:30 | 29.15 | 23.59 |
August | 0.908613E+10 | 17874.01 | 28-AUG-07:02 | 25.73 | 24.26 | 0.697095E+09 | 843.01 | 18-AUG-12:09 | 25.73 | 24.26 |
September | 0.903357E+10 | 18433.14 | 04-SEP-07:02 | 24.27 | 22.84 | 0.682646E+09 | 843.08 | 03-SEP-17:00 | 24.27 | 22.84 |
October | 0.863211E+10 | 18889.50 | 18-OCT-07:02 | 25.18 | 18.80 | 0.704904E+09 | 843.03 | 08-OCT-17:40 | 25.18 | 18.80 |
November | 0.692782E+10 | 17523.58 | 20-NOV-08:62 | 24.50 | 20.57 | 0.681474E+09 | 843.07 | 23-NOV-18:19 | 26.70 | 23.84 |
December | 0.549300E+10 | 18200.61 | 01-DEC-08:62 | 23.48 | 18.65 | 0.707637E+09 | 843.10 | 25-DEC-18:19 | 24.23 | 22.98 |
Annual Sum or Average | 0.880541E+11 | 0.827635E+10 | ||||||||
Minimum of Months | 0.493652E+10 | 14790.27 | 21.15 | 18.65 | 0.635638E+09 | 842.98 | 18.30 | 16.71 | ||
Maximum of Months | 0.950481E+10 | 19089.22 | 26.47 | 24.56 | 0.707637E+09 | 843.17 | 29.15 | 24.56 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355670E+10 | 14039.18 | 14-JAN-07:03 | 21.93 | 20.13 | 0.418898E+09 | 842.98 | 07-JAN-13:00 | 21.93 | 20.13 |
February | 0.382508E+10 | 14620.95 | 18-FEB-07:03 | 23.80 | 20.78 | 0.380735E+09 | 842.99 | 11-FEB-13:00 | 23.80 | 20.78 |
March | 0.427494E+10 | 15080.23 | 28-MAR-06:03 | 21.02 | 19.85 | 0.429917E+09 | 842.97 | 04-MAR-13:30 | 21.02 | 19.85 |
April | 0.511780E+10 | 15656.47 | 17-APR-06:03 | 18.98 | 16.80 | 0.410666E+09 | 842.99 | 08-APR-12:00 | 18.98 | 16.80 |
May | 0.636147E+10 | 16499.95 | 09-MAY-06:03 | 24.18 | 19.97 | 0.426109E+09 | 842.95 | 13-MAY-12:00 | 30.60 | 23.08 |
June | 0.672309E+10 | 15013.14 | 17-JUN-06:02 | 25.10 | 21.21 | 0.417083E+09 | 843.00 | 03-JUN-12:09 | 25.10 | 21.21 |
July | 0.743707E+10 | 15218.51 | 02-JUL-07:02 | 25.97 | 21.70 | 0.420264E+09 | 842.96 | 15-JUL-12:09 | 30.68 | 24.89 |
August | 0.723987E+10 | 15179.90 | 08-AUG-06:02 | 26.38 | 23.78 | 0.431781E+09 | 842.95 | 05-AUG-12:00 | 26.38 | 23.78 |
September | 0.707465E+10 | 15013.62 | 14-SEP-06:02 | 24.40 | 22.82 | 0.411099E+09 | 843.01 | 16-SEP-12:30 | 30.30 | 23.90 |
October | 0.672157E+10 | 18198.61 | 18-OCT-06:02 | 25.00 | 18.59 | 0.420595E+09 | 842.99 | 07-OCT-12:09 | 25.00 | 18.59 |
November | 0.530225E+10 | 15636.70 | 21-NOV-07:02 | 25.18 | 21.19 | 0.405971E+09 | 842.99 | 25-NOV-13:00 | 26.70 | 21.73 |
December | 0.396720E+10 | 14804.26 | 01-DEC-07:02 | 23.30 | 18.59 | 0.418579E+09 | 842.99 | 02-DEC-13:30 | 26.40 | 20.37 |
Annual Sum or Average | 0.676017E+11 | 0.499170E+10 | ||||||||
Minimum of Months | 0.355670E+10 | 14039.18 | 18.98 | 16.80 | 0.380735E+09 | 842.95 | 18.98 | 16.80 | ||
Maximum of Months | 0.743707E+10 | 18198.61 | 26.38 | 23.78 | 0.431781E+09 | 843.01 | 30.68 | 24.89 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.352167E+10 | 14086.86 | 14-JAN-07:03 | 21.93 | 20.13 | 0.418819E+09 | 842.98 | 07-JAN-13:00 | 21.93 | 20.13 |
February | 0.379785E+10 | 14679.73 | 18-FEB-07:03 | 23.80 | 20.78 | 0.380686E+09 | 842.98 | 11-FEB-13:00 | 23.80 | 20.78 |
March | 0.425729E+10 | 15284.89 | 28-MAR-06:03 | 21.02 | 19.85 | 0.429859E+09 | 842.97 | 04-MAR-13:30 | 21.02 | 19.85 |
April | 0.512927E+10 | 15779.19 | 17-APR-06:03 | 18.98 | 16.80 | 0.410666E+09 | 842.99 | 08-APR-12:00 | 18.98 | 16.80 |
May | 0.638855E+10 | 16579.43 | 09-MAY-06:03 | 24.18 | 19.97 | 0.426110E+09 | 842.95 | 13-MAY-12:00 | 30.60 | 23.08 |
June | 0.677055E+10 | 15108.43 | 17-JUN-06:02 | 25.10 | 21.21 | 0.417086E+09 | 843.00 | 03-JUN-12:09 | 25.10 | 21.21 |
July | 0.749735E+10 | 15332.12 | 02-JUL-07:02 | 25.97 | 21.70 | 0.420270E+09 | 843.01 | 08-JUL-12:09 | 31.78 | 24.73 |
August | 0.728646E+10 | 15280.68 | 08-AUG-06:02 | 26.38 | 23.78 | 0.431785E+09 | 842.95 | 05-AUG-12:00 | 26.38 | 23.78 |
September | 0.713322E+10 | 15110.56 | 14-SEP-06:02 | 24.40 | 22.82 | 0.411104E+09 | 843.01 | 16-SEP-12:30 | 30.30 | 23.90 |
October | 0.676527E+10 | 18288.31 | 18-OCT-06:02 | 25.00 | 18.59 | 0.420598E+09 | 842.99 | 07-OCT-12:09 | 25.00 | 18.59 |
November | 0.530720E+10 | 15713.02 | 21-NOV-07:02 | 25.18 | 21.19 | 0.405964E+09 | 842.99 | 25-NOV-13:00 | 26.70 | 21.73 |
December | 0.394516E+10 | 14869.59 | 01-DEC-07:02 | 23.30 | 18.59 | 0.418522E+09 | 842.99 | 02-DEC-13:30 | 26.40 | 20.37 |
Annual Sum or Average | 0.677998E+11 | 0.499147E+10 | ||||||||
Minimum of Months | 0.352167E+10 | 14086.86 | 18.98 | 16.80 | 0.380686E+09 | 842.95 | 18.98 | 16.80 | ||
Maximum of Months | 0.749735E+10 | 18288.31 | 26.38 | 23.78 | 0.431785E+09 | 843.01 | 31.78 | 24.73 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335015E+10 | 13885.50 | 14-JAN-07:03 | 21.93 | 20.13 | 0.418528E+09 | 842.98 | 07-JAN-13:00 | 21.93 | 20.13 |
February | 0.364293E+10 | 14477.02 | 18-FEB-07:03 | 23.80 | 20.78 | 0.380451E+09 | 842.98 | 11-FEB-13:00 | 23.80 | 20.78 |
March | 0.408915E+10 | 14027.07 | 28-MAR-06:03 | 21.02 | 19.85 | 0.429547E+09 | 842.97 | 04-MAR-13:30 | 21.02 | 19.85 |
April | 0.498061E+10 | 15623.53 | 17-APR-06:03 | 18.98 | 16.80 | 0.410634E+09 | 842.98 | 08-APR-12:00 | 18.98 | 16.80 |
May | 0.624782E+10 | 16379.85 | 09-MAY-06:03 | 24.18 | 19.97 | 0.426081E+09 | 842.94 | 20-MAY-12:09 | 30.60 | 22.19 |
June | 0.664079E+10 | 14891.27 | 17-JUN-06:02 | 25.10 | 21.21 | 0.417059E+09 | 842.99 | 03-JUN-12:09 | 25.10 | 21.21 |
July | 0.737454E+10 | 15118.20 | 02-JUL-07:02 | 25.97 | 21.70 | 0.420243E+09 | 843.01 | 08-JUL-12:09 | 31.78 | 24.73 |
August | 0.715258E+10 | 15056.61 | 08-AUG-06:02 | 26.38 | 23.78 | 0.431757E+09 | 842.96 | 05-AUG-12:00 | 26.38 | 23.78 |
September | 0.701196E+10 | 14887.71 | 14-SEP-06:02 | 24.40 | 22.82 | 0.411077E+09 | 843.00 | 16-SEP-12:30 | 30.30 | 23.90 |
October | 0.663563E+10 | 18073.52 | 18-OCT-06:02 | 25.00 | 18.59 | 0.420570E+09 | 842.99 | 07-OCT-12:09 | 25.00 | 18.59 |
November | 0.515976E+10 | 15503.32 | 21-NOV-07:02 | 25.18 | 21.19 | 0.405919E+09 | 842.99 | 25-NOV-13:00 | 26.70 | 21.73 |
December | 0.378191E+10 | 14637.72 | 01-DEC-07:02 | 23.30 | 18.59 | 0.418277E+09 | 842.99 | 02-DEC-13:39 | 26.50 | 20.46 |
Annual Sum or Average | 0.660678E+11 | 0.499014E+10 | ||||||||
Minimum of Months | 0.335015E+10 | 13885.50 | 18.98 | 16.80 | 0.380451E+09 | 842.94 | 18.98 | 16.80 | ||
Maximum of Months | 0.737454E+10 | 18073.52 | 26.38 | 23.78 | 0.431757E+09 | 843.01 | 31.78 | 24.73 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.579599E+10 | 24051.19 | 14-JAN-08:62 | 21.15 | 19.82 | 0.142867E+10 | 2248.00 | 07-JAN-15:09 | 21.15 | 19.82 |
February | 0.636593E+10 | 26216.55 | 18-FEB-08:62 | 23.40 | 20.75 | 0.130156E+10 | 2248.04 | 11-FEB-15:39 | 23.40 | 20.75 |
March | 0.718411E+10 | 23630.19 | 14-MAR-07:03 | 23.48 | 22.62 | 0.147189E+10 | 2247.99 | 25-MAR-14:00 | 26.70 | 20.96 |
April | 0.879228E+10 | 28090.53 | 17-APR-07:03 | 19.60 | 17.17 | 0.140978E+10 | 2248.07 | 15-APR-14:00 | 19.60 | 17.17 |
May | 0.111020E+11 | 29537.74 | 09-MAY-07:03 | 25.68 | 20.64 | 0.145770E+10 | 2248.03 | 06-MAY-14:09 | 25.68 | 20.64 |
June | 0.118122E+11 | 27038.84 | 02-JUN-07:02 | 26.78 | 23.63 | 0.142982E+10 | 2247.91 | 17-JUN-14:20 | 29.40 | 22.66 |
July | 0.131375E+11 | 28185.06 | 06-JUL-07:02 | 25.55 | 22.29 | 0.143852E+10 | 2247.81 | 22-JUL-14:39 | 30.77 | 25.76 |
August | 0.127311E+11 | 28365.95 | 23-AUG-07:02 | 28.17 | 24.99 | 0.148009E+10 | 2247.98 | 05-AUG-14:39 | 28.17 | 24.99 |
September | 0.124903E+11 | 28054.40 | 14-SEP-07:02 | 24.78 | 23.34 | 0.141056E+10 | 2247.81 | 02-SEP-14:09 | 24.78 | 23.34 |
October | 0.117971E+11 | 32637.59 | 18-OCT-07:02 | 25.18 | 18.80 | 0.143565E+10 | 2247.96 | 28-OCT-14:20 | 28.70 | 23.07 |
November | 0.908885E+10 | 28194.17 | 21-NOV-08:62 | 26.20 | 21.56 | 0.138166E+10 | 2248.01 | 18-NOV-15:09 | 26.20 | 21.56 |
December | 0.656613E+10 | 27262.29 | 01-DEC-08:62 | 23.48 | 18.65 | 0.143217E+10 | 2248.03 | 02-DEC-15:00 | 25.60 | 20.31 |
Annual Sum or Average | 0.116864E+12 | 0.170781E+11 | ||||||||
Minimum of Months | 0.579599E+10 | 23630.19 | 19.60 | 17.17 | 0.130156E+10 | 2247.81 | 19.60 | 17.17 | ||
Maximum of Months | 0.131375E+11 | 32637.59 | 28.17 | 24.99 | 0.148009E+10 | 2248.07 | 30.77 | 25.76 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292202E+10 | 11612.46 | 14-JAN-08:62 | 21.15 | 19.82 | 0.713861E+09 | 1123.97 | 07-JAN-15:09 | 21.15 | 19.82 |
February | 0.324978E+10 | 13658.62 | 18-FEB-08:62 | 23.40 | 20.75 | 0.650422E+09 | 1123.99 | 11-FEB-15:39 | 23.40 | 20.75 |
March | 0.365877E+10 | 11851.23 | 14-MAR-07:03 | 23.48 | 22.62 | 0.735443E+09 | 1123.94 | 04-MAR-15:00 | 23.48 | 22.62 |
April | 0.454304E+10 | 14588.20 | 17-APR-07:03 | 19.60 | 17.17 | 0.704862E+09 | 1124.01 | 15-APR-14:00 | 19.60 | 17.17 |
May | 0.578237E+10 | 15425.65 | 09-MAY-07:03 | 25.68 | 20.64 | 0.728821E+09 | 1123.98 | 06-MAY-14:09 | 25.68 | 20.64 |
June | 0.616088E+10 | 14126.68 | 02-JUN-07:02 | 26.78 | 23.63 | 0.714881E+09 | 1123.92 | 17-JUN-14:20 | 29.40 | 22.66 |
July | 0.687726E+10 | 14726.60 | 06-JUL-07:02 | 25.55 | 22.29 | 0.719230E+09 | 1123.87 | 22-JUL-14:39 | 30.77 | 25.76 |
August | 0.665243E+10 | 14834.21 | 23-AUG-07:02 | 28.17 | 24.99 | 0.740014E+09 | 1123.96 | 05-AUG-14:39 | 28.17 | 24.99 |
September | 0.652255E+10 | 14651.15 | 14-SEP-07:02 | 24.78 | 23.34 | 0.705251E+09 | 1123.87 | 02-SEP-14:09 | 24.78 | 23.34 |
October | 0.615266E+10 | 17028.66 | 18-OCT-07:02 | 25.18 | 18.80 | 0.717798E+09 | 1123.95 | 28-OCT-14:20 | 28.70 | 23.07 |
November | 0.470071E+10 | 14724.64 | 21-NOV-08:62 | 26.20 | 21.56 | 0.690801E+09 | 1123.98 | 18-NOV-15:00 | 26.20 | 21.56 |
December | 0.333164E+10 | 14210.47 | 01-DEC-08:62 | 23.48 | 18.65 | 0.715773E+09 | 1123.98 | 02-DEC-15:50 | 25.78 | 20.31 |
Annual Sum or Average | 0.605541E+11 | 0.853716E+10 | ||||||||
Minimum of Months | 0.292202E+10 | 11612.46 | 19.60 | 17.17 | 0.650422E+09 | 1123.87 | 19.60 | 17.17 | ||
Maximum of Months | 0.687726E+10 | 17028.66 | 28.17 | 24.99 | 0.740014E+09 | 1124.01 | 30.77 | 25.76 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.287326E+10 | 11271.28 | 14-JAN-08:62 | 21.15 | 19.82 | 0.713519E+09 | 1123.97 | 07-JAN-15:09 | 21.15 | 19.82 |
February | 0.320287E+10 | 13579.83 | 18-FEB-08:62 | 23.40 | 20.75 | 0.650239E+09 | 1123.99 | 11-FEB-15:39 | 23.40 | 20.75 |
March | 0.361114E+10 | 11527.52 | 14-MAR-07:03 | 23.48 | 22.62 | 0.735221E+09 | 1123.94 | 04-MAR-15:00 | 23.48 | 22.62 |
April | 0.450347E+10 | 14520.65 | 17-APR-07:03 | 19.60 | 17.17 | 0.704856E+09 | 1124.01 | 15-APR-14:00 | 19.60 | 17.17 |
May | 0.574453E+10 | 15345.27 | 09-MAY-07:03 | 25.68 | 20.64 | 0.728816E+09 | 1123.98 | 06-MAY-14:09 | 25.68 | 20.64 |
June | 0.612747E+10 | 14046.24 | 02-JUN-07:02 | 26.78 | 23.63 | 0.714878E+09 | 1123.92 | 17-JUN-14:20 | 29.40 | 22.66 |
July | 0.684505E+10 | 14640.87 | 06-JUL-07:02 | 25.55 | 22.29 | 0.719225E+09 | 1123.87 | 22-JUL-14:39 | 30.77 | 25.76 |
August | 0.661843E+10 | 14744.83 | 23-AUG-07:02 | 28.17 | 24.99 | 0.740011E+09 | 1123.96 | 05-AUG-14:39 | 28.17 | 24.99 |
September | 0.649123E+10 | 14566.97 | 14-SEP-07:02 | 24.78 | 23.34 | 0.705246E+09 | 1123.87 | 02-SEP-14:09 | 24.78 | 23.34 |
October | 0.611678E+10 | 16942.69 | 18-OCT-07:02 | 25.18 | 18.80 | 0.717793E+09 | 1123.95 | 28-OCT-14:20 | 28.70 | 23.07 |
November | 0.465921E+10 | 14644.56 | 21-NOV-08:62 | 26.20 | 21.56 | 0.690789E+09 | 1123.98 | 18-NOV-15:00 | 26.20 | 21.56 |
December | 0.328065E+10 | 14126.03 | 01-DEC-08:62 | 23.48 | 18.65 | 0.715562E+09 | 1123.98 | 02-DEC-15:50 | 25.78 | 20.31 |
Annual Sum or Average | 0.600741E+11 | 0.853616E+10 | ||||||||
Minimum of Months | 0.287326E+10 | 11271.28 | 19.60 | 17.17 | 0.650239E+09 | 1123.87 | 19.60 | 17.17 | ||
Maximum of Months | 0.684505E+10 | 16942.69 | 28.17 | 24.99 | 0.740011E+09 | 1124.01 | 30.77 | 25.76 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276682E+10 | 10213.96 | 14-JAN-08:62 | 21.15 | 19.82 | 0.712608E+09 | 1123.87 | 07-JAN-15:09 | 21.15 | 19.82 |
February | 0.310847E+10 | 12540.36 | 18-FEB-08:62 | 23.40 | 20.75 | 0.649716E+09 | 1123.99 | 11-FEB-15:20 | 23.40 | 20.75 |
March | 0.352928E+10 | 11259.59 | 05-MAR-09:02 | 24.50 | 22.85 | 0.734739E+09 | 1123.95 | 04-MAR-15:00 | 24.50 | 22.85 |
April | 0.446455E+10 | 14428.08 | 17-APR-07:03 | 19.60 | 17.17 | 0.704846E+09 | 1124.00 | 15-APR-14:00 | 19.60 | 17.17 |
May | 0.574473E+10 | 14532.10 | 08-MAY-07:03 | 25.00 | 19.79 | 0.728814E+09 | 1123.98 | 06-MAY-14:09 | 25.00 | 19.79 |
June | 0.616132E+10 | 14071.51 | 02-JUN-07:02 | 26.78 | 23.63 | 0.714880E+09 | 1123.92 | 17-JUN-14:20 | 29.40 | 22.66 |
July | 0.690162E+10 | 14671.52 | 06-JUL-07:02 | 25.55 | 22.29 | 0.719231E+09 | 1123.87 | 22-JUL-14:39 | 30.77 | 25.76 |
August | 0.665936E+10 | 14804.73 | 23-AUG-07:02 | 28.17 | 24.99 | 0.740012E+09 | 1123.95 | 05-AUG-14:39 | 28.17 | 24.99 |
September | 0.654335E+10 | 14621.17 | 14-SEP-07:02 | 24.78 | 23.34 | 0.705251E+09 | 1123.87 | 02-SEP-14:09 | 24.78 | 23.34 |
October | 0.613031E+10 | 16953.54 | 18-OCT-07:02 | 25.18 | 18.80 | 0.717793E+09 | 1123.94 | 28-OCT-14:20 | 28.70 | 23.07 |
November | 0.461303E+10 | 14632.67 | 21-NOV-08:62 | 26.20 | 21.56 | 0.690749E+09 | 1123.98 | 18-NOV-15:50 | 26.20 | 21.56 |
December | 0.317380E+10 | 14103.98 | 01-DEC-08:62 | 23.48 | 18.65 | 0.714921E+09 | 1123.98 | 02-DEC-15:50 | 25.78 | 20.31 |
Annual Sum or Average | 0.597966E+11 | 0.853356E+10 | ||||||||
Minimum of Months | 0.276682E+10 | 10213.96 | 19.60 | 17.17 | 0.649716E+09 | 1123.87 | 19.60 | 17.17 | ||
Maximum of Months | 0.690162E+10 | 16953.54 | 28.17 | 24.99 | 0.740012E+09 | 1124.00 | 30.77 | 25.76 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304028E+10 | 8191.69 | 14-JAN-08:62 | 21.15 | 19.82 | 0.712327E+09 | 1123.87 | 07-JAN-15:00 | 21.15 | 19.82 |
February | 0.350223E+10 | 10746.89 | 18-FEB-08:62 | 23.40 | 20.75 | 0.649218E+09 | 1123.89 | 11-FEB-15:00 | 23.40 | 20.75 |
March | 0.406941E+10 | 10758.28 | 05-MAR-09:02 | 24.50 | 22.85 | 0.736001E+09 | 1123.99 | 04-MAR-15:39 | 24.50 | 22.85 |
April | 0.538339E+10 | 13781.25 | 16-APR-08:62 | 24.08 | 21.61 | 0.704945E+09 | 1124.00 | 08-APR-14:09 | 24.08 | 21.61 |
May | 0.702366E+10 | 15188.10 | 18-MAY-07:02 | 26.88 | 21.86 | 0.728951E+09 | 1123.99 | 13-MAY-14:20 | 26.88 | 21.86 |
June | 0.760233E+10 | 16010.84 | 06-JUN-07:02 | 26.38 | 24.66 | 0.715019E+09 | 1123.89 | 17-JUN-14:00 | 29.40 | 22.43 |
July | 0.860897E+10 | 16634.09 | 06-JUL-07:02 | 25.55 | 22.29 | 0.719458E+09 | 1123.87 | 22-JUL-14:50 | 31.23 | 26.06 |
August | 0.815252E+10 | 17467.57 | 23-AUG-07:02 | 28.17 | 24.99 | 0.740143E+09 | 1123.97 | 05-AUG-14:09 | 28.17 | 24.99 |
September | 0.808082E+10 | 16504.51 | 14-SEP-07:02 | 24.78 | 23.34 | 0.705442E+09 | 1124.02 | 02-SEP-14:39 | 24.78 | 23.34 |
October | 0.736470E+10 | 19092.96 | 18-OCT-07:02 | 25.18 | 18.80 | 0.717943E+09 | 1123.91 | 21-OCT-14:00 | 28.90 | 20.91 |
November | 0.534860E+10 | 16033.22 | 20-NOV-08:62 | 24.50 | 20.57 | 0.690745E+09 | 1123.93 | 04-NOV-14:00 | 24.50 | 20.57 |
December | 0.342013E+10 | 14069.09 | 01-DEC-08:62 | 23.48 | 18.65 | 0.714020E+09 | 1123.98 | 09-DEC-15:00 | 26.10 | 22.26 |
Annual Sum or Average | 0.715970E+11 | 0.853421E+10 | ||||||||
Minimum of Months | 0.304028E+10 | 8191.69 | 21.15 | 18.65 | 0.649218E+09 | 1123.87 | 21.15 | 19.82 | ||
Maximum of Months | 0.860897E+10 | 19092.96 | 28.17 | 24.99 | 0.740143E+09 | 1124.02 | 31.23 | 26.06 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4045212.80 | 1193.19 | 07-JAN-08:07 | 22.98 |
February | 9915980.08 | 5752.67 | 04-FEB-08:62 | 7.25 |
March | 14455403.99 | 1621.37 | 05-MAR-08:05 | 23.98 |
April | 21267008.55 | 2095.19 | 12-APR-07:05 | 25.78 |
May | 37545616.61 | 2325.44 | 14-MAY-07:05 | 26.78 |
June | 31714905.72 | 2475.77 | 29-JUN-07:05 | 27.48 |
July | 35899432.58 | 2799.01 | 16-JUL-07:05 | 28.40 |
August | 31138273.00 | 2808.82 | 17-AUG-07:05 | 28.48 |
September | 27152908.77 | 2409.91 | 18-SEP-07:05 | 27.70 |
October | 29302105.59 | 2247.81 | 02-OCT-07:05 | 26.97 |
November | 16839235.31 | 2008.46 | 29-NOV-08:05 | 25.10 |
December | 9941393.79 | 1735.84 | 01-DEC-08:05 | 23.48 |
Annual Sum or Average | 0.269217E+09 | |||
Minimum of Months | 4045212.80 | 1193.19 | 7.25 | |
Maximum of Months | 37545616.61 | 5752.67 | 28.48 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2377443.92 | 703.10 | 06-JAN-08:07 | 23.40 |
February | 4497888.90 | 1001.01 | 11-FEB-08:05 | 24.50 |
March | 8023093.01 | 936.86 | 05-MAR-08:05 | 23.98 |
April | 12034769.59 | 1156.10 | 12-APR-07:05 | 25.78 |
May | 16616803.71 | 1220.13 | 09-MAY-07:05 | 25.68 |
June | 13872550.06 | 1424.47 | 09-JUN-07:05 | 28.40 |
July | 15280556.42 | 1369.97 | 11-JUL-07:05 | 27.88 |
August | 14158323.03 | 1465.66 | 15-AUG-07:05 | 28.48 |
September | 12954652.99 | 1329.19 | 09-SEP-07:04 | 27.88 |
October | 13948192.56 | 1211.42 | 02-OCT-07:05 | 26.97 |
November | 8628036.08 | 1083.76 | 29-NOV-08:05 | 25.10 |
December | 5271645.73 | 962.74 | 01-DEC-08:05 | 23.48 |
Annual Sum or Average | 0.127664E+09 | |||
Minimum of Months | 2377443.92 | 703.10 | 23.40 | |
Maximum of Months | 16616803.71 | 1465.66 | 28.48 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5292027.92 | 697.92 | 07-JAN-07:07 | 22.80 |
February | 8454394.16 | 878.06 | 18-FEB-07:05 | 23.80 |
March | 16775972.05 | 828.02 | 05-MAR-08:05 | 23.98 |
April | 33776893.54 | 1256.76 | 15-APR-17:12 | 31.13 |
May | 58956868.54 | 1394.66 | 29-MAY-16:12 | 32.77 |
June | 75492236.37 | 1230.30 | 15-JUN-06:05 | 27.20 |
July | 79489724.84 | 1631.73 | 29-JUL-17:12 | 34.03 |
August | 74842659.21 | 1337.70 | 11-AUG-06:05 | 28.30 |
September | 74372052.90 | 1215.88 | 22-SEP-06:06 | 27.80 |
October | 55673021.97 | 1058.67 | 30-OCT-06:07 | 26.70 |
November | 31134176.84 | 1030.44 | 29-NOV-07:05 | 25.00 |
December | 10825268.22 | 790.47 | 07-DEC-07:05 | 23.40 |
Annual Sum or Average | 0.525085E+09 | |||
Minimum of Months | 5292027.92 | 697.92 | 22.80 | |
Maximum of Months | 79489724.84 | 1631.73 | 34.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5355975.50 | 701.28 | 07-JAN-07:07 | 22.80 |
February | 8525866.76 | 881.30 | 18-FEB-07:05 | 23.80 |
March | 16912257.46 | 833.33 | 05-MAR-08:05 | 23.98 |
April | 33916392.05 | 1258.70 | 15-APR-17:12 | 31.13 |
May | 58675791.86 | 1396.12 | 29-MAY-16:12 | 32.77 |
June | 74836317.49 | 1232.75 | 15-JUN-06:05 | 27.20 |
July | 78378079.87 | 1633.25 | 29-JUL-17:12 | 34.03 |
August | 73956618.08 | 1245.65 | 15-AUG-06:05 | 27.38 |
September | 73903746.05 | 1238.33 | 22-SEP-06:06 | 27.80 |
October | 55651497.63 | 1054.22 | 30-OCT-06:07 | 26.70 |
November | 31227031.37 | 1036.38 | 29-NOV-07:05 | 25.00 |
December | 10910516.22 | 795.25 | 07-DEC-07:05 | 23.40 |
Annual Sum or Average | 0.522250E+09 | |||
Minimum of Months | 5355975.50 | 701.28 | 22.80 | |
Maximum of Months | 78378079.87 | 1633.25 | 34.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5430530.59 | 652.85 | 07-JAN-07:07 | 22.80 |
February | 8792481.99 | 869.92 | 18-FEB-07:05 | 23.80 |
March | 17367802.55 | 833.28 | 05-MAR-08:05 | 23.98 |
April | 34299427.83 | 1258.77 | 15-APR-17:12 | 31.13 |
May | 59164900.46 | 1396.29 | 29-MAY-16:12 | 32.77 |
June | 76359186.37 | 1250.07 | 15-JUN-06:05 | 27.20 |
July | 81029395.49 | 1632.93 | 29-JUL-17:12 | 34.03 |
August | 75544475.29 | 1360.85 | 11-AUG-06:05 | 28.30 |
September | 75031178.04 | 1199.46 | 22-SEP-06:06 | 27.80 |
October | 56422961.16 | 1072.99 | 30-OCT-06:07 | 26.70 |
November | 31859986.31 | 1042.84 | 29-NOV-07:05 | 25.00 |
December | 10972537.06 | 787.08 | 07-DEC-07:05 | 23.40 |
Annual Sum or Average | 0.532275E+09 | |||
Minimum of Months | 5430530.59 | 652.85 | 22.80 | |
Maximum of Months | 81029395.49 | 1632.93 | 34.03 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7833306.34 | 1129.62 | 01-JAN-09:07 | 23.17 |
February | 15681493.00 | 1612.77 | 11-FEB-08:05 | 24.50 |
March | 22568582.60 | 1496.47 | 05-MAR-09:05 | 24.50 |
April | 49667420.47 | 2511.19 | 15-APR-17:12 | 31.13 |
May | 65325396.68 | 2848.30 | 29-MAY-16:02 | 33.03 |
June | 66467637.66 | 2408.79 | 11-JUN-08:06 | 28.58 |
July | 87702196.73 | 3293.20 | 29-JUL-17:12 | 34.03 |
August | 60589800.80 | 2581.71 | 17-AUG-07:05 | 28.48 |
September | 77100158.00 | 2394.23 | 17-SEP-16:12 | 31.10 |
October | 62474934.34 | 2247.22 | 29-OCT-08:06 | 27.48 |
November | 30904633.71 | 1863.19 | 23-NOV-09:06 | 25.68 |
December | 18628209.70 | 1754.07 | 10-DEC-09:06 | 25.87 |
Annual Sum or Average | 0.564944E+09 | |||
Minimum of Months | 7833306.34 | 1129.62 | 23.17 | |
Maximum of Months | 87702196.73 | 3293.20 | 34.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4599398.38 | 595.00 | 01-JAN-09:07 | 23.17 |
February | 9113203.39 | 857.55 | 11-FEB-08:05 | 24.50 |
March | 12709541.87 | 814.77 | 05-MAR-09:05 | 24.50 |
April | 26582609.16 | 1289.55 | 15-APR-17:12 | 31.13 |
May | 31739415.49 | 1431.95 | 29-MAY-16:12 | 32.77 |
June | 31091255.03 | 1279.68 | 09-JUN-07:05 | 28.40 |
July | 43103025.35 | 1681.80 | 29-JUL-17:12 | 34.03 |
August | 29798179.73 | 1351.98 | 17-AUG-07:05 | 28.48 |
September | 38983612.63 | 1215.28 | 17-SEP-16:12 | 31.10 |
October | 31387806.63 | 1169.49 | 29-OCT-08:06 | 27.48 |
November | 15649277.44 | 984.13 | 23-NOV-09:06 | 25.68 |
December | 10137225.56 | 893.04 | 10-DEC-09:06 | 25.87 |
Annual Sum or Average | 0.284895E+09 | |||
Minimum of Months | 4599398.38 | 595.00 | 23.17 | |
Maximum of Months | 43103025.35 | 1681.80 | 34.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4761263.83 | 585.18 | 01-JAN-09:07 | 23.17 |
February | 9403943.03 | 990.76 | 04-FEB-08:06 | 7.25 |
March | 12770458.11 | 812.01 | 05-MAR-09:05 | 24.50 |
April | 26533040.49 | 1288.91 | 15-APR-17:12 | 31.13 |
May | 31745760.59 | 1431.18 | 29-MAY-16:12 | 32.77 |
June | 31207713.28 | 1275.68 | 09-JUN-07:05 | 28.40 |
July | 43177907.56 | 1679.88 | 29-JUL-17:12 | 34.03 |
August | 29935285.01 | 1347.01 | 17-AUG-07:05 | 28.48 |
September | 38948125.33 | 1214.08 | 17-SEP-16:12 | 31.10 |
October | 31447414.98 | 1165.62 | 29-OCT-08:06 | 27.48 |
November | 15627672.23 | 974.86 | 23-NOV-09:06 | 25.68 |
December | 10140248.99 | 883.92 | 10-DEC-09:06 | 25.87 |
Annual Sum or Average | 0.285699E+09 | |||
Minimum of Months | 4761263.83 | 585.18 | 7.25 | |
Maximum of Months | 43177907.56 | 1679.88 | 34.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5155943.26 | 553.51 | 01-JAN-09:07 | 23.17 |
February | 10886822.70 | 1618.10 | 04-FEB-08:62 | 7.25 |
March | 13046584.61 | 814.66 | 05-MAR-09:05 | 24.50 |
April | 26405436.03 | 1289.86 | 15-APR-17:12 | 31.13 |
May | 31423013.89 | 1433.40 | 29-MAY-16:12 | 32.77 |
June | 31699843.77 | 1295.32 | 09-JUN-07:05 | 28.40 |
July | 43842197.03 | 1682.81 | 29-JUL-17:12 | 34.03 |
August | 31272012.35 | 1361.60 | 17-AUG-07:05 | 28.48 |
September | 38312143.26 | 1216.43 | 17-SEP-16:12 | 31.10 |
October | 31321453.88 | 1188.33 | 29-OCT-08:06 | 27.48 |
November | 15455668.41 | 965.23 | 29-NOV-08:05 | 25.10 |
December | 10172777.33 | 848.45 | 10-DEC-09:06 | 25.87 |
Annual Sum or Average | 0.288994E+09 | |||
Minimum of Months | 5155943.26 | 553.51 | 7.25 | |
Maximum of Months | 43842197.03 | 1682.81 | 34.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8062883.86 | 2705.80 | 25-JAN-08:65 | 10.18 |
February | 23159424.13 | 27493.96 | 04-FEB-08:62 | 7.25 |
March | 21033340.61 | 5289.11 | 16-MAR-07:05 | 6.97 |
April | 25937525.38 | 1324.29 | 15-APR-17:12 | 31.13 |
May | 29843690.95 | 1466.37 | 29-MAY-16:12 | 32.77 |
June | 27319258.27 | 1376.07 | 29-JUN-07:05 | 27.48 |
July | 39124025.25 | 1703.58 | 29-JUL-17:12 | 34.03 |
August | 27782504.48 | 1539.99 | 17-AUG-07:05 | 28.48 |
September | 35793308.37 | 1331.14 | 02-SEP-07:05 | 26.97 |
October | 30946254.85 | 1316.39 | 29-OCT-08:06 | 27.48 |
November | 16501433.19 | 1118.23 | 23-NOV-09:06 | 25.68 |
December | 13094354.45 | 1851.21 | 15-DEC-08:65 | 8.68 |
Annual Sum or Average | 0.298598E+09 | |||
Minimum of Months | 8062883.86 | 1118.23 | 6.97 | |
Maximum of Months | 39124025.25 | 27493.96 | 34.03 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.549253E+10 | 3421.96 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.496476E+10 | 3421.96 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.549777E+10 | 3421.96 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.532115E+10 | 3421.96 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.549253E+10 | 3421.96 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.532179E+10 | 3421.96 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.549708E+10 | 3421.96 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.549285E+10 | 3421.96 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.532602E+10 | 3421.96 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.549253E+10 | 3421.96 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.530585E+10 | 3421.96 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.550226E+10 | 3421.96 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.647071E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.496476E+10 | 3421.96 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.550226E+10 | 3421.96 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.334781E+10 | 2090.38 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.302613E+10 | 2090.38 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.335104E+10 | 2090.38 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.324334E+10 | 2090.38 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.334781E+10 | 2090.38 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.324377E+10 | 2090.38 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.335056E+10 | 2090.38 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.334803E+10 | 2090.38 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.324631E+10 | 2090.38 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.334781E+10 | 2090.38 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.323401E+10 | 2090.38 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.335375E+10 | 2090.38 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.394404E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.302613E+10 | 2090.38 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.335375E+10 | 2090.38 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.241466E+10 | 2078.11 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.218750E+10 | 2078.11 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.247235E+10 | 2078.11 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.234375E+10 | 2078.11 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.244351E+10 | 2078.11 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.238702E+10 | 2078.11 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.240024E+10 | 2078.11 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.247235E+10 | 2078.11 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.234375E+10 | 2078.11 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.241466E+10 | 2078.11 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.234375E+10 | 2078.11 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.240024E+10 | 2078.11 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.286238E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.218750E+10 | 2078.11 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.247235E+10 | 2078.11 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229238E+09 | 0.114409E+10 |
February | 0.305697E+10 | 0.496476E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394720E+09 | 0.647238E+09 |
March | 0.335708E+10 | 0.549777E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430022E+09 | 0.745379E+09 |
April | 0.327081E+10 | 0.532115E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.981410E+09 | 0.153977E+09 |
May | 0.336680E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176860E+10 | 45725514.93 |
June | 0.325380E+10 | 0.532179E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192351E+10 | 8655346.87 |
July | 0.339353E+10 | 0.549708E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247680E+10 | 11827496.39 |
August | 0.334857E+10 | 0.549285E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220166E+10 | 18618893.42 |
September | 0.327932E+10 | 0.532602E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206306E+10 | 14357775.24 |
October | 0.338624E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168123E+10 | 33525079.55 |
November | 0.327446E+10 | 0.530585E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883571E+09 | 0.318445E+09 |
December | 0.340325E+10 | 0.550226E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322802E+09 | 0.994401E+09 |
Annual Sum or Average | 0.397770E+11 | 0.647071E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153566E+11 | 0.413624E+10 |
Minimum of Months | 0.305697E+10 | 0.496476E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229238E+09 | 8655346.87 |
Maximum of Months | 0.340325E+10 | 0.550226E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247680E+10 | 0.114409E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128333E+09 | 0.592135E+09 |
February | 0.152844E+10 | 0.302613E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220078E+09 | 0.291536E+09 |
March | 0.167849E+10 | 0.335104E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239108E+09 | 0.355881E+09 |
April | 0.163536E+10 | 0.324334E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547940E+09 | 60402121.16 |
May | 0.168335E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977912E+09 | 17498393.62 |
June | 0.162685E+10 | 0.324377E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106128E+10 | 3324403.76 |
July | 0.169671E+10 | 0.335056E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138307E+10 | 4867881.88 |
August | 0.167424E+10 | 0.334803E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121808E+10 | 8752459.80 |
September | 0.163961E+10 | 0.324631E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114425E+10 | 4195963.19 |
October | 0.169307E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935695E+09 | 10979894.41 |
November | 0.163718E+10 | 0.323401E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491848E+09 | 0.138277E+09 |
December | 0.170157E+10 | 0.335375E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180872E+09 | 0.503717E+09 |
Annual Sum or Average | 0.198880E+11 | 0.394404E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852845E+10 | 0.199157E+10 |
Minimum of Months | 0.152844E+10 | 0.302613E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128333E+09 | 3324403.76 |
Maximum of Months | 0.170157E+10 | 0.335375E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138307E+10 | 0.592135E+09 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126989E+09 | 0.614474E+09 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216505E+09 | 0.320232E+09 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235073E+09 | 0.380132E+09 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534752E+09 | 77479568.44 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960246E+09 | 25912280.15 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104776E+10 | 5930246.31 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136034E+10 | 9300746.13 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120238E+10 | 10280953.58 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112417E+10 | 7107385.14 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912076E+09 | 15541629.04 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481775E+09 | 0.154550E+09 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175603E+09 | 0.528676E+09 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837766E+10 | 0.214962E+10 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126989E+09 | 5930246.31 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136034E+10 | 0.614474E+09 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126991E+09 | 0.613625E+09 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216509E+09 | 0.319372E+09 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235078E+09 | 0.379449E+09 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534696E+09 | 77751652.98 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959935E+09 | 26441675.33 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104709E+10 | 6186433.79 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135973E+10 | 9653566.68 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120169E+10 | 10421646.65 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112342E+10 | 7414335.97 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911662E+09 | 16013879.64 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481688E+09 | 0.154594E+09 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175607E+09 | 0.528007E+09 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837409E+10 | 0.214893E+10 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126991E+09 | 6186433.79 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135973E+10 | 0.613625E+09 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126998E+09 | 0.610439E+09 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216539E+09 | 0.315526E+09 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235105E+09 | 0.374851E+09 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534867E+09 | 75736258.00 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960634E+09 | 24684183.63 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104828E+10 | 5736440.14 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136051E+10 | 9166968.35 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120279E+10 | 10145115.94 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112433E+10 | 6938822.79 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912356E+09 | 15039586.76 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482057E+09 | 0.152701E+09 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175641E+09 | 0.524880E+09 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838010E+10 | 0.212585E+10 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126998E+09 | 5736440.14 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136051E+10 | 0.610439E+09 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.241466E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222952E+09 | 0.108271E+10 |
February | 0.313522E+10 | 0.218750E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380401E+09 | 0.577138E+09 |
March | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413165E+09 | 0.672700E+09 |
April | 0.338259E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940069E+09 | 0.140734E+09 |
May | 0.349753E+10 | 0.244351E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169208E+10 | 43254412.25 |
June | 0.343071E+10 | 0.238702E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185004E+10 | 10662696.33 |
July | 0.344942E+10 | 0.240024E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238955E+10 | 15844202.06 |
August | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211988E+10 | 18536213.27 |
September | 0.338259E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197935E+10 | 13683830.78 |
October | 0.344359E+10 | 0.241466E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160439E+10 | 30013941.59 |
November | 0.331698E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.848073E+09 | 0.284418E+09 |
December | 0.344942E+10 | 0.240024E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308184E+09 | 0.937877E+09 |
Annual Sum or Average | 0.410346E+11 | 0.286238E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147481E+11 | 0.382758E+10 |
Minimum of Months | 0.313522E+10 | 0.218750E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222952E+09 | 10662696.33 |
Maximum of Months | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238955E+10 | 0.108271E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127056E+09 | 0.604350E+09 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216639E+09 | 0.311815E+09 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235227E+09 | 0.367396E+09 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535695E+09 | 73617788.88 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963179E+09 | 22104507.06 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105231E+10 | 5393158.10 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136184E+10 | 8216288.44 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120636E+10 | 10029993.21 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112679E+10 | 6639741.90 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914238E+09 | 14974856.42 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483259E+09 | 0.153156E+09 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175654E+09 | 0.521340E+09 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839825E+10 | 0.209903E+10 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127056E+09 | 5393158.10 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136184E+10 | 0.604350E+09 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127060E+09 | 0.602670E+09 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216649E+09 | 0.310395E+09 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235236E+09 | 0.365845E+09 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535757E+09 | 73206205.64 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963368E+09 | 21848060.00 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105253E+10 | 5332445.70 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136201E+10 | 8152708.80 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120656E+10 | 9988544.39 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112696E+10 | 6563930.10 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914407E+09 | 14817713.64 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483381E+09 | 0.152721E+09 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175667E+09 | 0.519991E+09 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839958E+10 | 0.209153E+10 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127060E+09 | 5332445.70 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136201E+10 | 0.602670E+09 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127065E+09 | 0.597718E+09 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216663E+09 | 0.305835E+09 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235243E+09 | 0.361621E+09 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535798E+09 | 71923018.39 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963682E+09 | 21136683.50 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105265E+10 | 5197792.52 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136195E+10 | 8145344.91 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120661E+10 | 9920975.68 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112682E+10 | 6489680.26 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914526E+09 | 14514837.87 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483634E+09 | 0.151335E+09 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175683E+09 | 0.515749E+09 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840033E+10 | 0.206959E+10 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127065E+09 | 5197792.52 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136195E+10 | 0.597718E+09 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131007E+09 | 0.709425E+09 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224783E+09 | 0.445290E+09 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244824E+09 | 0.491549E+09 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553341E+09 | 0.125697E+09 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100904E+10 | 40022273.39 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111040E+10 | 10848786.24 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140503E+10 | 15788851.53 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126442E+10 | 14751472.11 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117542E+10 | 16921869.78 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.946327E+09 | 32785828.34 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501552E+09 | 0.232301E+09 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180702E+09 | 0.632329E+09 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874684E+10 | 0.276771E+10 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131007E+09 | 10848786.24 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140503E+10 | 0.709425E+09 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 3421.96 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2368.07 | 02-JAN-15:00 | 4689.25 | 24-JAN-12:05 |
February | 4050.04 | 03-FEB-13:09 | 3421.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2611.32 | 11-FEB-14:00 | 4511.05 | 03-FEB-12:05 |
March | 4050.04 | 03-MAR-13:09 | 3421.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2613.16 | 13-MAR-16:00 | 4950.86 | 15-MAR-11:05 |
April | 4050.04 | 01-APR-12:09 | 3421.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3881.94 | 17-APR-15:00 | 1598.08 | 25-APR-16:00 |
May | 4050.04 | 05-MAY-12:09 | 3421.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4899.77 | 22-MAY-13:00 | 1092.68 | 10-MAY-15:00 |
June | 4050.04 | 02-JUN-12:09 | 3421.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3871.01 | 11-JUN-13:00 | 521.58 | 05-JUN-15:00 |
July | 4050.04 | 01-JUL-12:09 | 3421.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5358.49 | 29-JUL-16:00 | 530.64 | 02-JUL-16:00 |
August | 4050.04 | 04-AUG-12:09 | 3421.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4697.13 | 23-AUG-13:00 | 817.24 | 28-AUG-12:00 |
September | 4050.04 | 01-SEP-12:09 | 3421.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3946.64 | 20-SEP-14:00 | 96.80 | 19-SEP-24:00 |
October | 4050.04 | 01-OCT-12:09 | 3421.96 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3861.62 | 14-OCT-13:00 | 1060.04 | 26-OCT-14:00 |
November | 4050.04 | 03-NOV-12:09 | 3421.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2865.55 | 17-NOV-15:00 | 2775.87 | 12-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 3421.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2410.08 | 10-DEC-15:00 | 5174.17 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2368.07 | 96.80 | |||||
Maximum of Months | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5358.49 | 5174.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2090.38 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1336.03 | 02-JAN-15:00 | 2640.75 | 24-JAN-12:05 |
February | 2024.96 | 03-FEB-13:09 | 2090.38 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1471.22 | 11-FEB-14:00 | 2599.97 | 03-FEB-12:05 |
March | 2024.96 | 03-MAR-13:09 | 2090.38 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.70 | 13-MAR-16:00 | 2880.16 | 15-MAR-11:05 |
April | 2024.96 | 01-APR-12:09 | 2090.38 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2182.61 | 17-APR-15:00 | 901.59 | 25-APR-16:00 |
May | 2024.96 | 05-MAY-12:09 | 2090.38 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2750.93 | 22-MAY-13:00 | 607.66 | 10-MAY-15:00 |
June | 2024.96 | 02-JUN-12:09 | 2090.38 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2187.35 | 11-JUN-13:00 | 296.13 | 05-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 2090.38 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 29-JUL-16:00 | 298.91 | 02-JUL-16:00 |
August | 2024.96 | 04-AUG-12:09 | 2090.38 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.87 | 23-AUG-13:00 | 462.52 | 28-AUG-12:00 |
September | 2024.96 | 01-SEP-12:09 | 2090.38 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.41 | 20-SEP-14:00 | 33.75 | 26-SEP-07:02 |
October | 2024.96 | 01-OCT-12:09 | 2090.38 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.62 | 14-OCT-13:00 | 598.04 | 26-OCT-14:00 |
November | 2024.96 | 03-NOV-12:09 | 2090.38 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.65 | 17-NOV-15:00 | 1558.33 | 12-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2090.38 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.69 | 10-DEC-15:00 | 2926.00 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1336.03 | 33.75 | |||||
Maximum of Months | 2024.96 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 2926.00 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.96 | 02-JAN-15:00 | 2640.27 | 24-JAN-12:05 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1470.92 | 11-FEB-14:00 | 2602.44 | 03-FEB-12:05 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.66 | 13-MAR-16:00 | 2885.60 | 15-MAR-11:05 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2182.60 | 17-APR-15:00 | 901.59 | 25-APR-16:00 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2750.93 | 22-MAY-13:00 | 607.66 | 10-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2187.00 | 11-JUN-13:00 | 296.13 | 05-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 29-JUL-16:00 | 770.58 | 02-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.87 | 23-AUG-13:00 | 462.52 | 28-AUG-12:00 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.41 | 20-SEP-14:00 | 514.78 | 04-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.62 | 14-OCT-13:00 | 598.04 | 26-OCT-14:00 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.59 | 17-NOV-15:00 | 1569.06 | 12-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.62 | 10-DEC-15:00 | 2926.29 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.96 | 296.13 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 2926.29 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.95 | 02-JAN-15:00 | 2638.45 | 24-JAN-12:05 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1470.93 | 11-FEB-14:00 | 2601.63 | 03-FEB-12:05 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.65 | 13-MAR-16:00 | 2885.89 | 15-MAR-11:05 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2182.60 | 17-APR-15:00 | 901.59 | 25-APR-16:00 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2750.93 | 22-MAY-13:00 | 607.66 | 10-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2186.99 | 11-JUN-13:00 | 296.13 | 05-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 29-JUL-16:00 | 774.62 | 02-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.87 | 23-AUG-13:00 | 462.52 | 28-AUG-12:00 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.41 | 20-SEP-14:00 | 521.94 | 04-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.62 | 14-OCT-13:00 | 598.04 | 26-OCT-14:00 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.58 | 17-NOV-15:00 | 1564.05 | 12-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.62 | 10-DEC-15:00 | 2924.84 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.95 | 296.13 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 2924.84 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.95 | 02-JAN-15:00 | 2631.59 | 24-JAN-12:05 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1470.95 | 11-FEB-14:00 | 2594.32 | 03-FEB-12:05 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.65 | 13-MAR-16:00 | 2879.33 | 15-MAR-11:05 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2182.60 | 17-APR-15:00 | 901.59 | 25-APR-16:00 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2750.93 | 22-MAY-13:00 | 607.66 | 10-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2187.00 | 11-JUN-13:00 | 296.13 | 05-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 29-JUL-16:00 | 763.38 | 02-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.87 | 23-AUG-13:00 | 462.52 | 28-AUG-12:00 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.41 | 20-SEP-14:00 | 511.27 | 04-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.62 | 14-OCT-13:00 | 598.04 | 26-OCT-14:00 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.58 | 17-NOV-15:00 | 1545.75 | 12-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.61 | 10-DEC-15:00 | 2918.23 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.95 | 296.13 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 2918.23 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2078.11 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2341.75 | 02-JAN-15:00 | 4593.08 | 24-JAN-12:05 |
February | 5400.05 | 04-FEB-15:09 | 2078.11 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2579.35 | 11-FEB-14:00 | 4435.89 | 03-FEB-12:05 |
March | 5400.05 | 04-MAR-15:09 | 2078.11 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2569.81 | 13-MAR-16:00 | 4924.58 | 15-MAR-11:05 |
April | 5400.05 | 01-APR-14:09 | 2078.11 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3827.65 | 17-APR-15:00 | 1580.28 | 25-APR-16:00 |
May | 5400.05 | 06-MAY-14:09 | 2078.11 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4825.32 | 22-MAY-13:00 | 1067.32 | 10-MAY-15:00 |
June | 5400.05 | 03-JUN-14:09 | 2078.11 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3832.96 | 11-JUN-13:00 | 518.57 | 05-JUN-15:00 |
July | 5400.05 | 01-JUL-14:09 | 2078.11 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5305.93 | 29-JUL-16:00 | 1302.06 | 02-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 2078.11 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4625.14 | 23-AUG-13:00 | 810.32 | 28-AUG-12:00 |
September | 5400.05 | 02-SEP-14:09 | 2078.11 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3870.95 | 20-SEP-14:00 | 879.54 | 04-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 2078.11 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3818.61 | 14-OCT-13:00 | 1048.23 | 26-OCT-14:00 |
November | 5400.05 | 04-NOV-14:09 | 2078.11 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2833.58 | 17-NOV-15:00 | 2617.96 | 12-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2078.11 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2357.76 | 10-DEC-15:00 | 5087.80 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2341.75 | 518.57 | |||||
Maximum of Months | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5305.93 | 5087.80 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1336.02 | 02-JAN-15:00 | 2606.28 | 24-JAN-12:05 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1471.26 | 11-FEB-14:00 | 2502.78 | 03-FEB-12:05 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.76 | 13-MAR-16:00 | 2784.54 | 15-MAR-11:05 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2182.69 | 17-APR-15:00 | 901.59 | 25-APR-16:00 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2750.99 | 22-MAY-13:00 | 607.66 | 10-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2187.34 | 11-JUN-13:00 | 296.13 | 05-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 29-JUL-16:00 | 721.28 | 02-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.87 | 23-AUG-13:00 | 462.52 | 28-AUG-12:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.41 | 20-SEP-14:00 | 477.96 | 04-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.62 | 14-OCT-13:00 | 598.04 | 26-OCT-14:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.64 | 17-NOV-15:00 | 1479.74 | 12-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.70 | 10-DEC-15:00 | 2886.00 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1336.02 | 296.13 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 2886.00 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1336.02 | 02-JAN-15:00 | 2602.01 | 24-JAN-12:05 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1471.26 | 11-FEB-14:00 | 2490.64 | 03-FEB-12:05 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.76 | 13-MAR-16:00 | 2774.43 | 15-MAR-11:05 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2182.69 | 17-APR-15:00 | 901.59 | 25-APR-16:00 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2750.99 | 22-MAY-13:00 | 607.66 | 10-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2187.34 | 11-JUN-13:00 | 296.13 | 05-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 29-JUL-16:00 | 718.15 | 02-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.87 | 23-AUG-13:00 | 462.52 | 28-AUG-12:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.41 | 20-SEP-14:00 | 475.24 | 04-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.62 | 14-OCT-13:00 | 598.04 | 26-OCT-14:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.64 | 17-NOV-15:00 | 1473.72 | 12-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.70 | 10-DEC-15:00 | 2871.86 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1336.02 | 296.13 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 2871.86 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1336.03 | 02-JAN-15:00 | 2589.13 | 24-JAN-12:05 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1471.26 | 11-FEB-14:00 | 2452.99 | 03-FEB-12:05 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.74 | 13-MAR-16:00 | 2754.18 | 15-MAR-11:05 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2182.69 | 17-APR-15:00 | 901.59 | 25-APR-16:00 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2750.99 | 22-MAY-13:00 | 607.66 | 10-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2187.34 | 11-JUN-13:00 | 296.13 | 05-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 29-JUL-16:00 | 721.58 | 02-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.87 | 23-AUG-13:00 | 462.52 | 28-AUG-12:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.41 | 20-SEP-14:00 | 479.13 | 04-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.62 | 14-OCT-13:00 | 598.04 | 26-OCT-14:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.63 | 17-NOV-15:00 | 1457.95 | 12-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.69 | 10-DEC-15:00 | 2836.34 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1336.03 | 296.13 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 2836.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1362.27 | 02-JAN-15:00 | 2703.34 | 24-JAN-12:05 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1503.63 | 11-FEB-14:00 | 2482.75 | 03-FEB-12:05 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1508.04 | 13-MAR-16:00 | 2956.65 | 15-MAR-11:05 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2237.10 | 17-APR-15:00 | 919.39 | 25-APR-16:00 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2826.10 | 22-MAY-13:00 | 633.02 | 10-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2225.31 | 11-JUN-13:00 | 299.14 | 05-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3080.42 | 29-JUL-16:00 | 829.45 | 02-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2708.86 | 23-AUG-13:00 | 469.44 | 28-AUG-12:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281.11 | 20-SEP-14:00 | 616.15 | 04-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2221.62 | 14-OCT-13:00 | 609.85 | 26-OCT-14:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1648.45 | 17-NOV-15:00 | 1484.02 | 12-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1394.88 | 10-DEC-15:00 | 2926.62 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1362.27 | 299.14 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3080.42 | 2956.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25995.36 | 14-JAN-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.18 |
February | 28361.17 | 18-FEB-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.80 |
March | 25459.88 | 05-MAR-08:62 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 |
April | 29777.78 | 14-APR-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 | 0.00 |
May | 31866.36 | 09-MAY-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 145.87 | 0.00 |
June | 30706.08 | 12-JUN-07:01 | 2362.52 | 525.00 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 90.64 | 0.00 |
July | 34301.35 | 02-JUL-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 74.04 | 0.00 |
August | 31629.71 | 08-AUG-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 229.28 | 0.00 |
September | 31981.47 | 11-SEP-07:01 | 2700.03 | 600.00 | 597.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.63 | 0.00 |
October | 34856.44 | 18-OCT-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 56.60 | 0.00 |
November | 30877.92 | 20-NOV-08:62 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3.90 | 0.00 |
December | 32576.82 | 01-DEC-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 25459.88 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34856.44 | 2700.03 | 600.00 | 597.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.28 | 236.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14790.27 | 14-JAN-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.71 |
February | 16365.39 | 18-FEB-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.60 |
March | 15320.57 | 05-MAR-08:62 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 |
April | 16296.04 | 14-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 7.42 | 0.00 |
May | 18062.41 | 22-MAY-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 0.00 |
June | 17650.78 | 12-JUN-07:01 | 1181.23 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 52.05 | 0.00 |
July | 19089.22 | 02-JUL-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 0.00 |
August | 17874.01 | 28-AUG-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 32.88 | 0.00 |
September | 18433.14 | 04-SEP-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.40 |
October | 18889.50 | 18-OCT-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 31.55 | 0.00 |
November | 17523.58 | 20-NOV-08:62 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 | 0.00 |
December | 18200.61 | 01-DEC-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14790.27 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19089.22 | 1181.23 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 52.05 | 122.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14039.18 | 14-JAN-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 |
February | 14620.95 | 18-FEB-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 |
March | 15080.23 | 28-MAR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 |
April | 15656.47 | 17-APR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 |
May | 16499.95 | 09-MAY-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 | 0.00 |
June | 15013.14 | 17-JUN-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 0.00 |
July | 15218.51 | 02-JUL-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 27.19 | 0.00 |
August | 15179.90 | 08-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 | 0.00 |
September | 15013.62 | 14-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 |
October | 18198.61 | 18-OCT-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 0.00 |
November | 15636.70 | 21-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 | 0.00 |
December | 14804.26 | 01-DEC-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14039.18 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18198.61 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 27.19 | 15.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14086.86 | 14-JAN-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.81 |
February | 14679.73 | 18-FEB-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.69 |
March | 15284.89 | 28-MAR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 |
April | 15779.19 | 17-APR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 |
May | 16579.43 | 09-MAY-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 0.00 |
June | 15108.43 | 17-JUN-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 0.00 |
July | 15332.12 | 02-JUL-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 | 0.00 |
August | 15280.68 | 08-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 | 0.00 |
September | 15110.56 | 14-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 |
October | 18288.31 | 18-OCT-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.45 | 0.00 |
November | 15713.02 | 21-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 | 0.00 |
December | 14869.59 | 01-DEC-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14086.86 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18288.31 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 | 15.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13885.50 | 14-JAN-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.45 |
February | 14477.02 | 18-FEB-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 |
March | 14027.07 | 28-MAR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 |
April | 15623.53 | 17-APR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.69 |
May | 16379.85 | 09-MAY-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 | 0.00 |
June | 14891.27 | 17-JUN-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 0.00 |
July | 15118.20 | 02-JUL-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 29.18 | 0.00 |
August | 15056.61 | 08-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 0.00 |
September | 14887.71 | 14-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 |
October | 18073.52 | 18-OCT-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 | 0.00 |
November | 15503.32 | 21-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 | 0.00 |
December | 14637.72 | 01-DEC-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13885.50 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18073.52 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 29.18 | 15.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24051.19 | 14-JAN-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.08 |
February | 26216.55 | 18-FEB-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.30 |
March | 23630.19 | 14-MAR-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 |
April | 28090.53 | 17-APR-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.28 |
May | 29537.74 | 09-MAY-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 125.00 | 0.00 |
June | 27038.84 | 02-JUN-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 141.34 | 0.00 |
July | 28185.06 | 06-JUL-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 68.15 | 0.00 |
August | 28365.95 | 23-AUG-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 208.16 | 0.00 |
September | 28054.40 | 14-SEP-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 4.81 | 0.00 |
October | 32637.59 | 18-OCT-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 52.62 | 0.00 |
November | 28194.17 | 21-NOV-08:62 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 113.49 | 0.00 |
December | 27262.29 | 01-DEC-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23630.19 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32637.59 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 208.16 | 329.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11612.46 | 14-JAN-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.56 |
February | 13658.62 | 18-FEB-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.42 |
March | 11851.23 | 14-MAR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.48 |
April | 14588.20 | 17-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.79 |
May | 15425.65 | 09-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 73.11 | 0.00 |
June | 14126.68 | 02-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.18 | 0.00 |
July | 14726.60 | 06-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.78 | 0.00 |
August | 14834.21 | 23-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 121.77 | 0.00 |
September | 14651.15 | 14-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 | 0.00 |
October | 17028.66 | 18-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.19 | 0.00 |
November | 14724.64 | 21-NOV-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.58 | 0.00 |
December | 14210.47 | 01-DEC-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11612.46 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17028.66 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 121.77 | 184.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11271.28 | 14-JAN-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.42 |
February | 13579.83 | 18-FEB-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.66 |
March | 11527.52 | 14-MAR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.32 |
April | 14520.65 | 17-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.43 |
May | 15345.27 | 09-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 73.63 | 0.00 |
June | 14046.24 | 02-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.62 | 0.00 |
July | 14640.87 | 06-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.26 | 0.00 |
August | 14744.83 | 23-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 122.28 | 0.00 |
September | 14566.97 | 14-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.82 | 0.00 |
October | 16942.69 | 18-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.71 | 0.00 |
November | 14644.56 | 21-NOV-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.15 | 0.00 |
December | 14126.03 | 01-DEC-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11271.28 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16942.69 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 122.28 | 184.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10213.96 | 14-JAN-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.96 |
February | 12540.36 | 18-FEB-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.82 |
March | 11259.59 | 05-MAR-09:02 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 | 0.00 |
April | 14428.08 | 17-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.72 |
May | 14532.10 | 08-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 40.55 | 0.00 |
June | 14071.51 | 02-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.92 | 0.00 |
July | 14671.52 | 06-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.67 | 0.00 |
August | 14804.73 | 23-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 123.67 | 0.00 |
September | 14621.17 | 14-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.27 | 0.00 |
October | 16953.54 | 18-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.91 | 0.00 |
November | 14632.67 | 21-NOV-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.81 | 0.00 |
December | 14103.98 | 01-DEC-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10213.96 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16953.54 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 123.67 | 182.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8191.69 | 14-JAN-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.42 |
February | 10746.89 | 18-FEB-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.56 |
March | 10758.28 | 05-MAR-09:02 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 24.19 | 0.00 |
April | 13781.25 | 16-APR-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 0.00 |
May | 15188.10 | 18-MAY-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.82 | 0.00 |
June | 16010.84 | 06-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.10 | 0.00 |
July | 16634.09 | 06-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.19 | 0.00 |
August | 17467.57 | 23-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 126.81 | 0.00 |
September | 16504.51 | 14-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 | 0.00 |
October | 19092.96 | 18-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.09 | 0.00 |
November | 16033.22 | 20-NOV-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 | 0.00 |
December | 14069.09 | 01-DEC-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8191.69 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19092.96 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 126.81 | 139.42 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.664548E+11 | 72109.60 | 02-JAN-13:00 | 7295112.19 | 2473.56 | 25-JAN-08:09 |
February | 0.638007E+11 | 78545.13 | 11-FEB-14:20 | 56353243.72 | 20815.34 | 04-FEB-08:09 |
March | 0.721247E+11 | 70985.68 | 04-MAR-13:39 | 42592386.84 | 11804.00 | 16-MAR-07:30 |
April | 0.760171E+11 | 76237.04 | 13-APR-12:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.880589E+11 | 83195.97 | 29-MAY-13:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.910942E+11 | 84671.03 | 24-JUN-12:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.975697E+11 | 90041.90 | 29-JUL-13:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.972040E+11 | 89943.10 | 20-AUG-12:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.929418E+11 | 88479.60 | 09-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.902045E+11 | 86485.98 | 03-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.785425E+11 | 75572.50 | 03-NOV-13:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.696057E+11 | 72663.98 | 10-DEC-13:00 | 8745275.84 | 2325.14 | 15-DEC-08:09 |
Annual Sum or Average | 0.983619E+12 | 0.114986E+09 | ||||
Minimum of Months | 0.638007E+11 | 70985.68 | 0.00 | 0.00 | ||
Maximum of Months | 0.975697E+11 | 90041.90 | 56353243.72 | 20815.34 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.421670E+10 | 8810.02 | 24-JAN-12:30 | 0.00 | 0.00 |
February | 0.466165E+10 | 9655.82 | 25-FEB-12:30 | 0.00 | 0.00 |
March | 0.628694E+10 | 11002.85 | 15-MAR-12:30 | 0.00 | 0.00 |
April | 0.689954E+10 | 10593.33 | 19-APR-12:30 | 0.00 | 0.00 |
May | 0.695785E+10 | 11018.55 | 06-MAY-11:30 | 0.00 | 0.00 |
June | 0.639846E+10 | 10341.87 | 06-JUN-11:30 | 0.00 | 0.00 |
July | 0.709487E+10 | 10162.97 | 07-JUL-12:30 | 0.00 | 0.00 |
August | 0.654338E+10 | 9789.33 | 02-AUG-11:30 | 0.00 | 0.00 |
September | 0.562333E+10 | 10045.13 | 17-SEP-11:30 | 0.00 | 0.00 |
October | 0.515160E+10 | 9437.38 | 06-OCT-11:30 | 0.00 | 0.00 |
November | 0.412458E+10 | 7892.77 | 06-NOV-12:09 | 0.00 | 0.00 |
December | 0.390684E+10 | 7605.59 | 31-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.678657E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.390684E+10 | 7605.59 | 0.00 | 0.00 | |
Maximum of Months | 0.709487E+10 | 11018.55 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.234911E+11 | 0.410663E+10 | 0.108325E+11 | 0.00 | 0.783426E+10 | 0.00 | 0.00 | 0.151074E+11 | 0.00 | 0.00 | 0.00 | 0.508300E+10 | 0.00 |
February | 0.212624E+11 | 0.348003E+10 | 0.980803E+10 | 0.00 | 0.710310E+10 | 0.00 | 0.00 | 0.175574E+11 | 0.00 | 0.00 | 0.00 | 0.458981E+10 | 0.00 |
March | 0.238408E+11 | 0.354317E+10 | 0.110075E+11 | 0.00 | 0.798054E+10 | 0.00 | 0.00 | 0.206754E+11 | 0.00 | 0.00 | 0.00 | 0.507736E+10 | 0.00 |
April | 0.227839E+11 | 0.312604E+10 | 0.105079E+11 | 0.00 | 0.764097E+10 | 0.00 | 0.00 | 0.271238E+11 | 0.00 | 0.00 | 0.00 | 0.483440E+10 | 0.00 |
May | 0.236617E+11 | 0.295699E+10 | 0.109147E+11 | 0.00 | 0.805673E+10 | 0.00 | 0.00 | 0.375153E+11 | 0.00 | 0.00 | 0.00 | 0.495347E+10 | 0.00 |
June | 0.230409E+11 | 0.273752E+10 | 0.106386E+11 | 0.00 | 0.810625E+10 | 0.00 | 0.00 | 0.418095E+11 | 0.00 | 0.00 | 0.00 | 0.476147E+10 | 0.00 |
July | 0.234131E+11 | 0.286838E+10 | 0.107945E+11 | 0.00 | 0.869256E+10 | 0.00 | 0.00 | 0.469243E+11 | 0.00 | 0.00 | 0.00 | 0.487688E+10 | 0.00 |
August | 0.238328E+11 | 0.310922E+10 | 0.110006E+11 | 0.00 | 0.869785E+10 | 0.00 | 0.00 | 0.456470E+11 | 0.00 | 0.00 | 0.00 | 0.491647E+10 | 0.00 |
September | 0.227918E+11 | 0.330098E+10 | 0.105148E+11 | 0.00 | 0.827326E+10 | 0.00 | 0.00 | 0.432892E+11 | 0.00 | 0.00 | 0.00 | 0.477186E+10 | 0.00 |
October | 0.234911E+11 | 0.372493E+10 | 0.108325E+11 | 0.00 | 0.814366E+10 | 0.00 | 0.00 | 0.390384E+11 | 0.00 | 0.00 | 0.00 | 0.497400E+10 | 0.00 |
November | 0.227593E+11 | 0.388489E+10 | 0.104978E+11 | 0.00 | 0.765667E+10 | 0.00 | 0.00 | 0.288811E+11 | 0.00 | 0.00 | 0.00 | 0.486267E+10 | 0.00 |
December | 0.234215E+11 | 0.416570E+10 | 0.108050E+11 | 0.00 | 0.782809E+10 | 0.00 | 0.00 | 0.183192E+11 | 0.00 | 0.00 | 0.00 | 0.506618E+10 | 0.00 |
Annual Sum or Average | 0.277790E+12 | 0.410045E+11 | 0.128154E+12 | 0.00 | 0.960139E+11 | 0.00 | 0.00 | 0.381888E+12 | 0.00 | 0.00 | 0.00 | 0.587676E+11 | 0.00 |
Minimum of Months | 0.212624E+11 | 0.273752E+10 | 0.980803E+10 | 0.00 | 0.710310E+10 | 0.00 | 0.00 | 0.151074E+11 | 0.00 | 0.00 | 0.00 | 0.458981E+10 | 0.00 |
Maximum of Months | 0.238408E+11 | 0.416570E+10 | 0.110075E+11 | 0.00 | 0.869785E+10 | 0.00 | 0.00 | 0.469243E+11 | 0.00 | 0.00 | 0.00 | 0.508300E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 7295112.19 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 56353243.72 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 42592386.84 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 8745275.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.114986E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 56353243.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17697.17 | 01-JAN-11:09 | 3786.68 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 6470.59 | 14-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 17697.17 | 01-FEB-10:09 | 3786.68 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 6735.95 | 18-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 17697.17 | 01-MAR-10:09 | 3786.68 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 6684.07 | 06-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 17697.17 | 01-APR-09:09 | 3786.68 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 6865.04 | 13-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 17697.17 | 01-MAY-09:09 | 3786.68 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 7145.13 | 15-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 17697.17 | 01-JUN-09:09 | 3786.68 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 7649.75 | 12-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 17697.17 | 01-JUL-09:09 | 3786.68 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 8255.40 | 29-JUL-12:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 17697.17 | 01-AUG-09:09 | 3786.68 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 8364.09 | 22-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 17697.17 | 01-SEP-09:09 | 3786.68 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 8030.13 | 22-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 17697.17 | 01-OCT-10:09 | 3786.68 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 8028.07 | 30-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 17697.17 | 01-NOV-09:09 | 3786.68 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 6963.73 | 05-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 17697.17 | 01-DEC-10:09 | 3786.68 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 6808.01 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 17697.17 | 3786.68 | 8059.50 | 0.00 | 6470.59 | 0.00 | 0.00 | |||||
Maximum of Months | 17697.17 | 3786.68 | 8059.50 | 0.00 | 8364.09 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 35810.26 | 02-JAN-14:30 | 0.00 | 0.00 | 0.00 | 11779.33 | 10-JAN-12:39 | 0.00 | 01-JAN-00:10 |
February | 39640.02 | 11-FEB-13:00 | 0.00 | 0.00 | 0.00 | 9675.16 | 06-FEB-13:39 | 0.00 | 01-FEB-00:10 |
March | 33501.53 | 13-MAR-16:10 | 0.00 | 0.00 | 0.00 | 7541.77 | 15-MAR-11:50 | 0.00 | 01-MAR-00:10 |
April | 39197.51 | 14-APR-14:00 | 0.00 | 0.00 | 0.00 | 9664.59 | 19-APR-12:50 | 0.00 | 01-APR-00:10 |
May | 46027.47 | 29-MAY-12:00 | 0.00 | 0.00 | 0.00 | 7745.95 | 22-MAY-12:09 | 0.00 | 01-MAY-00:10 |
June | 45301.01 | 24-JUN-12:00 | 0.00 | 0.00 | 0.00 | 9602.20 | 11-JUN-10:50 | 0.00 | 01-JUN-00:10 |
July | 52146.78 | 29-JUL-13:00 | 0.00 | 0.00 | 0.00 | 9650.33 | 08-JUL-13:30 | 0.00 | 01-JUL-00:10 |
August | 51597.64 | 22-AUG-12:00 | 0.00 | 0.00 | 0.00 | 7531.81 | 29-AUG-14:20 | 0.00 | 01-AUG-00:10 |
September | 49344.29 | 22-SEP-12:00 | 0.00 | 0.00 | 0.00 | 8997.81 | 26-SEP-12:50 | 0.00 | 01-SEP-00:10 |
October | 47050.09 | 14-OCT-12:00 | 0.00 | 0.00 | 0.00 | 9666.71 | 30-OCT-12:50 | 0.00 | 01-OCT-00:10 |
November | 40289.51 | 10-NOV-13:00 | 0.00 | 0.00 | 0.00 | 9669.87 | 16-NOV-13:39 | 0.00 | 01-NOV-00:10 |
December | 35996.32 | 10-DEC-13:00 | 0.00 | 0.00 | 0.00 | 7554.93 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 33501.53 | 0.00 | 0.00 | 0.00 | 7531.81 | 0.00 | |||
Maximum of Months | 52146.78 | 0.00 | 0.00 | 0.00 | 11779.33 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 72109.60 | 02-JAN-13:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5512.56 | 0.00 | 0.00 | 35368.07 | 0.00 |
February | 78545.13 | 11-FEB-14:20 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5921.41 | 0.00 | 0.00 | 38287.62 | 0.00 |
March | 70985.68 | 04-MAR-13:39 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5379.86 | 0.00 | 0.00 | 32507.96 | 0.00 |
April | 76237.04 | 13-APR-12:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5669.15 | 0.00 | 0.00 | 37259.16 | 0.00 |
May | 83195.97 | 29-MAY-13:09 | 17697.17 | 8059.50 | 0.00 | 0.00 | 6934.91 | 0.00 | 0.00 | 45092.00 | 0.00 |
June | 84671.03 | 24-JUN-12:20 | 17697.17 | 8059.50 | 0.00 | 0.00 | 7010.18 | 0.00 | 0.00 | 43812.78 | 0.00 |
July | 90041.90 | 29-JUL-13:30 | 17697.17 | 8059.50 | 0.00 | 0.00 | 7998.87 | 0.00 | 0.00 | 50855.82 | 0.00 |
August | 89943.10 | 20-AUG-12:09 | 17697.17 | 8059.50 | 0.00 | 0.00 | 8036.62 | 0.00 | 0.00 | 49685.89 | 0.00 |
September | 88479.60 | 09-SEP-12:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 8022.44 | 0.00 | 0.00 | 49264.92 | 0.00 |
October | 86485.98 | 03-OCT-12:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 7347.42 | 0.00 | 0.00 | 46156.81 | 0.00 |
November | 75572.50 | 03-NOV-13:50 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5922.35 | 0.00 | 0.00 | 38456.09 | 0.00 |
December | 72663.98 | 10-DEC-13:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5494.02 | 0.00 | 0.00 | 35996.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 70985.68 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5379.86 | 0.00 | 0.00 | 32507.96 | 0.00 | |
Maximum of Months | 90041.90 | 17697.17 | 8059.50 | 0.00 | 0.00 | 8036.62 | 0.00 | 0.00 | 50855.82 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2473.56 | 25-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 20815.34 | 04-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 11804.00 | 16-MAR-07:30 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 2325.14 | 15-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 20815.34 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 24.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.54 | 0.00 | 24.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 24.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 24.50 | 0.00 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.54 | 0.00 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.00 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.50 | 0.00 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.00 | 24.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.51 | 0.00 | 24.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.51 | 0.00 | 24.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.51 | 0.00 | 24.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.00 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.50 | 0.00 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.00 | 24.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.54 | 0.00 | 24.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.56 | 0.00 | 24.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 24.54 | 0.00 | 24.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.56 | 0.00 | 24.56 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 93.83 | 23.50 | 297.83 | 23.79 | 22.00 | 23.80 |
February | 73.00 | 23.49 | 301.67 | 23.81 | 21.83 | 23.82 |
March | 90.00 | 23.43 | 358.83 | 23.79 | 36.50 | 23.80 |
April | 18.17 | 23.82 | 436.50 | 23.89 | 14.00 | 23.89 |
May | 74.50 | 23.89 | 495.83 | 23.89 | 74.50 | 23.89 |
June | 118.83 | 23.89 | 481.00 | 23.89 | 118.83 | 23.89 |
July | 93.17 | 23.89 | 495.00 | 23.89 | 93.17 | 23.89 |
August | 125.83 | 23.89 | 497.00 | 23.89 | 125.83 | 23.89 |
September | 75.33 | 23.89 | 479.00 | 23.89 | 75.33 | 23.89 |
October | 81.83 | 23.89 | 495.83 | 23.89 | 81.83 | 23.89 |
November | 87.33 | 23.81 | 422.17 | 23.88 | 75.00 | 23.88 |
December | 98.67 | 23.57 | 342.83 | 23.82 | 51.67 | 23.82 |
Annual Sum or Average | 1030.50 | 23.75 | 5103.50 | 23.87 | 790.50 | 23.87 |
Minimum of Months | 18.17 | 23.43 | 297.83 | 23.79 | 14.00 | 23.80 |
Maximum of Months | 125.83 | 23.89 | 497.00 | 23.89 | 125.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.00 | 23.64 | 272.50 | 23.84 | 14.50 | 23.84 |
February | 52.83 | 23.67 | 271.83 | 23.85 | 13.50 | 23.86 |
March | 71.17 | 23.53 | 331.00 | 23.83 | 24.00 | 23.83 |
April | 13.50 | 23.86 | 398.33 | 23.89 | 10.67 | 23.89 |
May | 51.50 | 23.89 | 485.33 | 23.89 | 51.50 | 23.89 |
June | 99.33 | 23.89 | 481.00 | 23.89 | 99.33 | 23.89 |
July | 80.67 | 23.89 | 493.83 | 23.89 | 80.67 | 23.89 |
August | 112.50 | 23.89 | 497.00 | 23.89 | 112.50 | 23.89 |
September | 57.00 | 23.89 | 478.17 | 23.89 | 57.00 | 23.89 |
October | 61.17 | 23.89 | 487.50 | 23.89 | 61.17 | 23.89 |
November | 74.17 | 23.85 | 405.00 | 23.88 | 65.33 | 23.88 |
December | 69.67 | 23.68 | 318.00 | 23.85 | 35.00 | 23.85 |
Annual Sum or Average | 815.50 | 23.80 | 4919.50 | 23.88 | 625.17 | 23.88 |
Minimum of Months | 13.50 | 23.53 | 271.83 | 23.83 | 10.67 | 23.83 |
Maximum of Months | 112.50 | 23.89 | 497.00 | 23.89 | 112.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 65.50 | 23.70 | 243.17 | 23.93 | 23.00 | 23.94 |
February | 50.17 | 23.72 | 241.17 | 23.97 | 21.83 | 23.98 |
March | 70.83 | 23.65 | 279.33 | 23.95 | 32.00 | 23.96 |
April | 17.83 | 24.34 | 334.50 | 24.05 | 16.83 | 24.06 |
May | 67.83 | 24.18 | 375.00 | 24.07 | 67.83 | 24.09 |
June | 131.33 | 24.18 | 366.00 | 24.09 | 131.33 | 24.11 |
July | 111.83 | 24.26 | 369.00 | 24.12 | 111.83 | 24.15 |
August | 140.83 | 24.18 | 379.00 | 24.09 | 140.83 | 24.11 |
September | 96.33 | 24.34 | 360.00 | 24.13 | 96.33 | 24.17 |
October | 80.50 | 24.29 | 371.00 | 24.10 | 80.50 | 24.13 |
November | 84.67 | 24.11 | 327.00 | 24.04 | 79.00 | 24.06 |
December | 73.00 | 23.84 | 261.00 | 23.97 | 47.33 | 23.99 |
Annual Sum or Average | 990.67 | 24.09 | 3906.17 | 24.05 | 848.67 | 24.08 |
Minimum of Months | 17.83 | 23.65 | 241.17 | 23.93 | 16.83 | 23.94 |
Maximum of Months | 140.83 | 24.34 | 379.00 | 24.13 | 140.83 | 24.17 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 66.67 | 23.69 | 241.33 | 23.92 | 23.33 | 23.94 |
February | 52.00 | 23.72 | 240.50 | 23.96 | 22.33 | 23.98 |
March | 72.00 | 23.64 | 278.33 | 23.94 | 32.67 | 23.95 |
April | 17.83 | 24.36 | 334.67 | 24.05 | 16.83 | 24.07 |
May | 67.83 | 24.19 | 375.00 | 24.07 | 67.83 | 24.09 |
June | 128.00 | 24.19 | 366.00 | 24.10 | 128.00 | 24.12 |
July | 108.67 | 24.27 | 369.00 | 24.12 | 108.67 | 24.15 |
August | 138.17 | 24.19 | 379.00 | 24.09 | 138.17 | 24.11 |
September | 91.50 | 24.35 | 360.00 | 24.13 | 91.50 | 24.17 |
October | 78.50 | 24.30 | 371.00 | 24.10 | 78.50 | 24.13 |
November | 84.50 | 24.10 | 326.00 | 24.04 | 78.67 | 24.06 |
December | 74.17 | 23.83 | 259.00 | 23.96 | 47.33 | 23.99 |
Annual Sum or Average | 979.83 | 24.09 | 3899.83 | 24.05 | 833.83 | 24.08 |
Minimum of Months | 17.83 | 23.64 | 240.50 | 23.92 | 16.83 | 23.94 |
Maximum of Months | 138.17 | 24.36 | 379.00 | 24.13 | 138.17 | 24.17 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.83 | 23.66 | 237.67 | 23.91 | 25.50 | 23.92 |
February | 57.67 | 23.68 | 238.50 | 23.95 | 24.33 | 23.96 |
March | 82.67 | 23.63 | 274.50 | 23.92 | 37.50 | 23.94 |
April | 20.00 | 24.29 | 333.67 | 24.05 | 19.00 | 24.06 |
May | 72.00 | 24.18 | 375.00 | 24.07 | 72.00 | 24.08 |
June | 137.33 | 24.17 | 366.00 | 24.09 | 137.33 | 24.11 |
July | 114.17 | 24.25 | 369.00 | 24.12 | 114.17 | 24.14 |
August | 146.00 | 24.17 | 379.00 | 24.09 | 146.00 | 24.11 |
September | 102.33 | 24.31 | 360.00 | 24.12 | 102.33 | 24.16 |
October | 84.33 | 24.28 | 371.00 | 24.10 | 84.33 | 24.12 |
November | 93.00 | 24.09 | 322.33 | 24.04 | 86.67 | 24.06 |
December | 78.17 | 23.79 | 254.00 | 23.95 | 49.33 | 23.97 |
Annual Sum or Average | 1060.50 | 24.06 | 3880.67 | 24.05 | 898.50 | 24.07 |
Minimum of Months | 20.00 | 23.63 | 237.67 | 23.91 | 19.00 | 23.92 |
Maximum of Months | 146.00 | 24.31 | 379.00 | 24.12 | 146.00 | 24.16 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 92.17 | 23.70 | 207.00 | 23.85 | 41.33 | 23.87 |
February | 71.00 | 23.71 | 213.67 | 23.88 | 38.50 | 23.89 |
March | 101.17 | 23.67 | 243.50 | 23.85 | 55.67 | 23.87 |
April | 28.17 | 24.13 | 304.17 | 23.97 | 27.33 | 23.98 |
May | 91.00 | 24.04 | 344.00 | 23.97 | 91.00 | 23.98 |
June | 176.33 | 23.99 | 336.00 | 23.96 | 176.33 | 23.97 |
July | 157.67 | 24.05 | 338.00 | 24.00 | 157.67 | 24.01 |
August | 182.17 | 23.99 | 348.00 | 23.96 | 182.17 | 23.96 |
September | 137.33 | 24.07 | 330.00 | 24.00 | 137.33 | 24.01 |
October | 99.00 | 24.09 | 340.00 | 23.99 | 99.00 | 24.01 |
November | 103.67 | 23.96 | 293.50 | 23.94 | 98.67 | 23.95 |
December | 87.67 | 23.76 | 225.17 | 23.89 | 57.83 | 23.92 |
Annual Sum or Average | 1327.33 | 23.94 | 3523.00 | 23.94 | 1162.83 | 23.96 |
Minimum of Months | 28.17 | 23.67 | 207.00 | 23.85 | 27.33 | 23.87 |
Maximum of Months | 182.17 | 24.13 | 348.00 | 24.00 | 182.17 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 99.83 | 23.69 | 193.83 | 23.84 | 43.17 | 23.86 |
February | 78.00 | 23.71 | 202.00 | 23.87 | 41.33 | 23.89 |
March | 107.00 | 23.67 | 236.33 | 23.85 | 56.83 | 23.87 |
April | 31.17 | 24.10 | 297.83 | 23.97 | 30.00 | 23.98 |
May | 94.33 | 24.04 | 344.00 | 23.97 | 94.33 | 23.98 |
June | 181.17 | 23.98 | 336.00 | 23.96 | 181.17 | 23.96 |
July | 162.67 | 24.04 | 338.00 | 23.99 | 162.67 | 24.00 |
August | 187.00 | 23.98 | 348.00 | 23.96 | 187.00 | 23.96 |
September | 146.67 | 24.06 | 330.00 | 23.99 | 146.67 | 24.01 |
October | 103.33 | 24.07 | 339.50 | 23.98 | 103.33 | 24.00 |
November | 106.67 | 23.96 | 288.67 | 23.94 | 101.00 | 23.95 |
December | 92.17 | 23.75 | 218.50 | 23.89 | 60.17 | 23.91 |
Annual Sum or Average | 1390.00 | 23.93 | 3472.67 | 23.94 | 1207.67 | 23.96 |
Minimum of Months | 31.17 | 23.67 | 193.83 | 23.84 | 30.00 | 23.86 |
Maximum of Months | 187.00 | 24.10 | 348.00 | 23.99 | 187.00 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 102.67 | 23.68 | 190.17 | 23.83 | 44.00 | 23.86 |
February | 80.50 | 23.70 | 198.83 | 23.87 | 42.67 | 23.88 |
March | 109.17 | 23.66 | 235.33 | 23.84 | 57.83 | 23.86 |
April | 32.17 | 24.09 | 297.33 | 23.97 | 31.00 | 23.98 |
May | 96.83 | 24.04 | 344.00 | 23.96 | 96.83 | 23.98 |
June | 182.67 | 23.98 | 336.00 | 23.96 | 182.67 | 23.96 |
July | 164.67 | 24.04 | 338.00 | 23.99 | 164.67 | 24.00 |
August | 188.83 | 23.98 | 348.00 | 23.96 | 188.83 | 23.96 |
September | 148.50 | 24.06 | 330.00 | 23.99 | 148.50 | 24.01 |
October | 105.00 | 24.07 | 339.50 | 23.98 | 105.00 | 24.00 |
November | 108.33 | 23.96 | 286.50 | 23.94 | 102.17 | 23.95 |
December | 94.17 | 23.74 | 217.50 | 23.88 | 60.67 | 23.90 |
Annual Sum or Average | 1413.50 | 23.93 | 3461.17 | 23.94 | 1224.83 | 23.96 |
Minimum of Months | 32.17 | 23.66 | 190.17 | 23.83 | 31.00 | 23.86 |
Maximum of Months | 188.83 | 24.09 | 348.00 | 23.99 | 188.83 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 108.67 | 23.62 | 184.33 | 23.81 | 45.17 | 23.83 |
February | 86.67 | 23.67 | 197.17 | 23.85 | 46.00 | 23.87 |
March | 112.50 | 23.63 | 234.50 | 23.83 | 58.83 | 23.85 |
April | 34.00 | 24.08 | 297.33 | 23.96 | 32.50 | 23.98 |
May | 97.00 | 24.04 | 344.00 | 23.96 | 97.00 | 23.98 |
June | 182.33 | 23.98 | 336.00 | 23.96 | 182.33 | 23.96 |
July | 162.33 | 24.04 | 338.00 | 23.99 | 162.33 | 24.00 |
August | 186.50 | 23.98 | 348.00 | 23.96 | 186.50 | 23.96 |
September | 146.33 | 24.06 | 330.00 | 24.00 | 146.33 | 24.01 |
October | 104.83 | 24.07 | 339.50 | 23.98 | 104.83 | 24.00 |
November | 110.33 | 23.95 | 285.00 | 23.94 | 103.67 | 23.95 |
December | 102.00 | 23.69 | 216.33 | 23.86 | 64.83 | 23.88 |
Annual Sum or Average | 1433.50 | 23.91 | 3450.17 | 23.94 | 1230.33 | 23.95 |
Minimum of Months | 34.00 | 23.62 | 184.33 | 23.81 | 32.50 | 23.83 |
Maximum of Months | 186.50 | 24.08 | 348.00 | 24.00 | 186.50 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 108.67 | 23.55 | 197.17 | 23.79 | 40.67 | 23.81 |
February | 80.50 | 23.59 | 212.83 | 23.84 | 40.83 | 23.86 |
March | 106.67 | 23.65 | 242.83 | 23.84 | 54.50 | 23.86 |
April | 27.67 | 24.22 | 307.33 | 23.98 | 26.33 | 24.00 |
May | 75.00 | 24.10 | 344.00 | 23.98 | 75.00 | 24.00 |
June | 113.83 | 24.05 | 336.00 | 23.98 | 113.83 | 23.99 |
July | 87.00 | 24.21 | 338.00 | 24.03 | 87.00 | 24.06 |
August | 128.83 | 24.04 | 348.00 | 23.97 | 128.83 | 23.99 |
September | 77.50 | 24.23 | 330.00 | 24.03 | 77.50 | 24.06 |
October | 80.00 | 24.16 | 340.00 | 24.00 | 80.00 | 24.03 |
November | 95.00 | 23.96 | 293.17 | 23.94 | 87.83 | 23.95 |
December | 103.67 | 23.60 | 216.33 | 23.83 | 55.83 | 23.86 |
Annual Sum or Average | 1084.33 | 23.91 | 3505.67 | 23.94 | 868.17 | 23.97 |
Minimum of Months | 27.67 | 23.55 | 197.17 | 23.79 | 26.33 | 23.81 |
Maximum of Months | 128.83 | 24.23 | 348.00 | 24.03 | 128.83 | 24.06 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.81096 | 49.73153 | 0.42873 | 9.28152 |
February | 448.00000 | 23.82421 | 49.76553 | 0.44933 | 9.69297 |
March | 497.00000 | 23.80374 | 51.42916 | 0.46324 | 10.09343 |
April | 479.00000 | 23.88547 | 54.10339 | 0.53066 | 11.01784 |
May | 496.00000 | 23.88946 | 59.34549 | -0.2675 | 6.59022 |
June | 481.00000 | 23.89090 | 62.11034 | -0.2288 | 6.17688 |
July | 495.00000 | 23.89107 | 61.13121 | -0.2127 | 6.05044 |
August | 497.00000 | 23.89130 | 62.37781 | -0.2178 | 6.10132 |
September | 479.00000 | 23.89072 | 61.09443 | -0.2173 | 6.09722 |
October | 496.00000 | 23.89012 | 59.28396 | 0.60322 | 12.71327 |
November | 480.00000 | 23.87440 | 56.88426 | 0.54824 | 11.55765 |
December | 496.00000 | 23.82417 | 53.44232 | 0.47394 | 10.13476 |
Annual Sum or Average | 5840.00000 | 23.86395 | 56.76210 | 0.19442 | 8.78563 |
Minimum of Months | 448.00000 | 23.80374 | 49.73153 | -0.2675 | 6.05044 |
Maximum of Months | 497.00000 | 23.89130 | 62.37781 | 0.60322 | 12.71327 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.84856 | 47.55997 | 0.42564 | 9.07804 |
February | 448.00000 | 23.86216 | 48.00102 | 0.44279 | 9.39194 |
March | 497.00000 | 23.83654 | 49.57474 | 0.45152 | 9.66696 |
April | 479.00000 | 23.88623 | 52.28853 | 0.50346 | 10.41885 |
May | 496.00000 | 23.88925 | 57.44609 | -0.3106 | 7.12339 |
June | 481.00000 | 23.89065 | 60.37608 | -0.2725 | 6.64970 |
July | 495.00000 | 23.89096 | 59.67114 | -0.2619 | 6.55037 |
August | 497.00000 | 23.89092 | 60.79037 | -0.2649 | 6.58575 |
September | 479.00000 | 23.89014 | 59.49179 | -0.2647 | 6.58460 |
October | 496.00000 | 23.88963 | 57.32386 | 0.56934 | 11.89356 |
November | 480.00000 | 23.88053 | 54.83477 | 0.52410 | 10.96181 |
December | 496.00000 | 23.85773 | 51.00129 | 0.46275 | 9.76581 |
Annual Sum or Average | 5840.00000 | 23.87610 | 54.89893 | 0.16529 | 8.71771 |
Minimum of Months | 448.00000 | 23.83654 | 47.55997 | -0.3106 | 6.55037 |
Maximum of Months | 497.00000 | 23.89096 | 60.79037 | 0.56934 | 11.89356 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.91240 | 48.74771 | 0.45078 | 9.65393 |
February | 336.00000 | 23.94184 | 49.16552 | 0.47127 | 10.10151 |
March | 379.00000 | 23.92678 | 50.66307 | 0.47943 | 10.38179 |
April | 360.00000 | 24.02462 | 54.29801 | 0.54911 | 11.50726 |
May | 375.00000 | 24.05074 | 59.70242 | -0.2443 | 6.57028 |
June | 366.00000 | 24.06221 | 62.78319 | -0.2017 | 6.21556 |
July | 369.00000 | 24.07637 | 62.32228 | -0.1828 | 6.13050 |
August | 379.00000 | 24.06007 | 63.32586 | -0.1930 | 6.14832 |
September | 360.00000 | 24.07397 | 62.02161 | -0.1874 | 6.15747 |
October | 371.00000 | 24.05794 | 59.60078 | 0.62595 | 13.44075 |
November | 360.00000 | 24.00925 | 57.06049 | 0.57174 | 12.14872 |
December | 369.00000 | 23.93237 | 52.46852 | 0.49169 | 10.48762 |
Annual Sum or Average | 4395.00000 | 24.01099 | 56.89657 | 0.21637 | 9.06276 |
Minimum of Months | 336.00000 | 23.91240 | 48.74771 | -0.2443 | 6.13050 |
Maximum of Months | 379.00000 | 24.07637 | 63.32586 | 0.62595 | 13.44075 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.90767 | 48.79802 | 0.44862 | 9.62594 |
February | 336.00000 | 23.93862 | 49.21620 | 0.46963 | 10.07992 |
March | 379.00000 | 23.92364 | 50.68876 | 0.47816 | 10.36704 |
April | 360.00000 | 24.02455 | 54.27771 | 0.54936 | 11.51261 |
May | 375.00000 | 24.05092 | 59.64964 | -0.2435 | 6.56278 |
June | 366.00000 | 24.06271 | 62.68319 | -0.2001 | 6.20578 |
July | 369.00000 | 24.07707 | 62.20347 | -0.1809 | 6.12003 |
August | 379.00000 | 24.06054 | 63.23146 | -0.1916 | 6.13971 |
September | 360.00000 | 24.07466 | 61.89903 | -0.1855 | 6.14729 |
October | 371.00000 | 24.05838 | 59.51324 | 0.62678 | 13.46431 |
November | 360.00000 | 24.00866 | 57.04268 | 0.57159 | 12.14868 |
December | 369.00000 | 23.92918 | 52.51919 | 0.49036 | 10.46793 |
Annual Sum or Average | 4395.00000 | 24.01000 | 56.85966 | 0.21656 | 9.05433 |
Minimum of Months | 336.00000 | 23.90767 | 48.79802 | -0.2435 | 6.12003 |
Maximum of Months | 379.00000 | 24.07707 | 63.23146 | 0.62678 | 13.46431 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.89152 | 49.09849 | 0.44239 | 9.53989 |
February | 336.00000 | 23.92519 | 49.51627 | 0.46419 | 10.00174 |
March | 379.00000 | 23.90772 | 50.99334 | 0.47244 | 10.29181 |
April | 360.00000 | 24.02055 | 54.55505 | 0.54708 | 11.45552 |
May | 375.00000 | 24.04728 | 59.93016 | -0.2465 | 6.58010 |
June | 366.00000 | 24.05926 | 62.95694 | -0.2026 | 6.21088 |
July | 369.00000 | 24.07379 | 62.44180 | -0.1832 | 6.12145 |
August | 379.00000 | 24.05716 | 63.50014 | -0.1940 | 6.14359 |
September | 360.00000 | 24.07132 | 62.14826 | -0.1878 | 6.14939 |
October | 371.00000 | 24.05486 | 59.76419 | 0.62539 | 13.42045 |
November | 360.00000 | 24.00356 | 57.34293 | 0.56926 | 12.09467 |
December | 369.00000 | 23.91528 | 52.85949 | 0.48531 | 10.38984 |
Annual Sum or Average | 4395.00000 | 24.00259 | 57.14162 | 0.21315 | 9.01777 |
Minimum of Months | 336.00000 | 23.89152 | 49.09849 | -0.2465 | 6.12145 |
Maximum of Months | 379.00000 | 24.07379 | 63.50014 | 0.62539 | 13.42045 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.83909 | 50.88652 | 0.43324 | 9.35850 |
February | 308.00000 | 23.86388 | 51.35556 | 0.45610 | 9.82014 |
March | 348.00000 | 23.83308 | 52.79413 | 0.46180 | 10.07730 |
April | 330.00000 | 23.94611 | 56.35682 | 0.54070 | 11.28265 |
May | 344.00000 | 23.94482 | 61.81484 | -0.2639 | 6.64136 |
June | 336.00000 | 23.94386 | 64.88911 | -0.2217 | 6.21595 |
July | 338.00000 | 23.96991 | 64.24486 | -0.1967 | 6.08887 |
August | 348.00000 | 23.94130 | 65.44574 | -0.2122 | 6.14579 |
September | 330.00000 | 23.96709 | 63.95294 | -0.2012 | 6.13153 |
October | 340.00000 | 23.95774 | 61.49489 | 0.61821 | 13.18144 |
November | 330.00000 | 23.92183 | 59.28406 | 0.56154 | 11.84718 |
December | 338.00000 | 23.86465 | 54.71588 | 0.47794 | 10.24423 |
Annual Sum or Average | 4030.00000 | 23.91620 | 58.98670 | 0.20148 | 8.90418 |
Minimum of Months | 308.00000 | 23.83308 | 50.88652 | -0.2639 | 6.08887 |
Maximum of Months | 348.00000 | 23.96991 | 65.44574 | 0.61821 | 13.18144 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.83275 | 50.90830 | 0.42136 | 9.15271 |
February | 308.00000 | 23.85880 | 51.40182 | 0.44322 | 9.58680 |
March | 348.00000 | 23.82643 | 52.85629 | 0.44817 | 9.82638 |
April | 330.00000 | 23.94547 | 56.44561 | 0.52699 | 10.97010 |
May | 344.00000 | 23.94428 | 61.94875 | -0.2856 | 6.88613 |
June | 336.00000 | 23.94323 | 65.08045 | -0.2445 | 6.43234 |
July | 338.00000 | 23.96916 | 64.42981 | -0.2211 | 6.29598 |
August | 348.00000 | 23.94085 | 65.63624 | -0.2350 | 6.35279 |
September | 330.00000 | 23.96639 | 64.14663 | -0.2252 | 6.33700 |
October | 340.00000 | 23.95713 | 61.63907 | 0.60261 | 12.77718 |
November | 330.00000 | 23.92112 | 59.41477 | 0.54836 | 11.53500 |
December | 338.00000 | 23.86011 | 54.80081 | 0.46593 | 10.00881 |
Annual Sum or Average | 4030.00000 | 23.91390 | 59.10991 | 0.18406 | 8.83331 |
Minimum of Months | 308.00000 | 23.82643 | 50.90830 | -0.2856 | 6.29598 |
Maximum of Months | 348.00000 | 23.96916 | 65.63624 | 0.60261 | 12.77718 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.82526 | 51.00695 | 0.41795 | 9.11201 |
February | 308.00000 | 23.85468 | 51.49984 | 0.44056 | 9.55247 |
March | 348.00000 | 23.82208 | 52.94955 | 0.44569 | 9.79606 |
April | 330.00000 | 23.94514 | 56.52446 | 0.52589 | 10.94509 |
May | 344.00000 | 23.94404 | 62.02816 | -0.2871 | 6.90278 |
June | 336.00000 | 23.94302 | 65.15409 | -0.2458 | 6.44438 |
July | 338.00000 | 23.96889 | 64.49501 | -0.2223 | 6.30596 |
August | 348.00000 | 23.94066 | 65.70785 | -0.2363 | 6.36389 |
September | 330.00000 | 23.96613 | 64.21289 | -0.2265 | 6.34716 |
October | 340.00000 | 23.95685 | 61.71094 | 0.60172 | 12.75369 |
November | 330.00000 | 23.92044 | 59.50320 | 0.54715 | 11.50944 |
December | 338.00000 | 23.85491 | 54.91983 | 0.46313 | 9.96848 |
Annual Sum or Average | 4030.00000 | 23.91194 | 59.19352 | 0.18229 | 8.82018 |
Minimum of Months | 308.00000 | 23.82208 | 51.00695 | -0.2871 | 6.30596 |
Maximum of Months | 348.00000 | 23.96889 | 65.70785 | 0.60172 | 12.75369 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.80279 | 51.23670 | 0.41148 | 9.06337 |
February | 308.00000 | 23.84196 | 51.70864 | 0.43658 | 9.53048 |
March | 348.00000 | 23.81066 | 53.12681 | 0.44298 | 9.79504 |
April | 330.00000 | 23.94458 | 56.62136 | 0.52727 | 10.97767 |
May | 344.00000 | 23.94392 | 62.05182 | -0.2836 | 6.86187 |
June | 336.00000 | 23.94317 | 65.09021 | -0.2411 | 6.40000 |
July | 338.00000 | 23.96922 | 64.39017 | -0.2169 | 6.26055 |
August | 348.00000 | 23.94073 | 65.63720 | -0.2316 | 6.32101 |
September | 330.00000 | 23.96642 | 64.11332 | -0.2214 | 6.30388 |
October | 340.00000 | 23.95687 | 61.69662 | 0.60438 | 12.82271 |
November | 330.00000 | 23.91828 | 59.60423 | 0.54770 | 11.53539 |
December | 338.00000 | 23.83748 | 55.18619 | 0.45797 | 9.92381 |
Annual Sum or Average | 4030.00000 | 23.90646 | 59.25515 | 0.18313 | 8.80293 |
Minimum of Months | 308.00000 | 23.80279 | 51.23670 | -0.2836 | 6.26055 |
Maximum of Months | 348.00000 | 23.96922 | 65.63720 | 0.60438 | 12.82271 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.78264 | 50.80855 | 0.41390 | 9.24297 |
February | 308.00000 | 23.82864 | 51.22106 | 0.44641 | 9.84354 |
March | 348.00000 | 23.82369 | 52.47722 | 0.46197 | 10.20143 |
April | 330.00000 | 23.95048 | 55.51719 | 0.55603 | 11.66813 |
May | 344.00000 | 23.95137 | 60.41148 | -0.2309 | 6.34899 |
June | 336.00000 | 23.95081 | 62.91404 | -0.1842 | 5.95761 |
July | 338.00000 | 23.98167 | 61.90225 | -0.1495 | 5.84315 |
August | 348.00000 | 23.94762 | 63.56398 | -0.1752 | 5.92127 |
September | 330.00000 | 23.97717 | 61.85399 | -0.1585 | 5.89971 |
October | 340.00000 | 23.96527 | 60.08576 | 0.63799 | 13.73792 |
November | 330.00000 | 23.91884 | 58.47426 | 0.56759 | 12.06300 |
December | 338.00000 | 23.80806 | 54.80695 | 0.45674 | 10.10260 |
Annual Sum or Average | 4030.00000 | 23.90743 | 57.88086 | 0.21735 | 8.88577 |
Minimum of Months | 308.00000 | 23.78264 | 50.80855 | -0.2309 | 5.84315 |
Maximum of Months | 348.00000 | 23.98167 | 63.56398 | 0.63799 | 13.73792 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.127193E+11 | 0.314021E+10 | 437.76 | 0.851499E+10 | 0.420433E+10 | 0.00 | 1.00 | 07-JAN-08:63 | 0.00 | 01-JAN-00:05 | 53096.22 | 14-JAN-08:62 | 29174.65 | 14-JAN-08:62 | 23921.57 | 14-JAN-08:62 | 10670.41 | 14-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.146551E+11 | 0.360295E+10 | 405.93 | 0.101440E+11 | 0.451106E+10 | 0.00 | 1.00 | 02-FEB-08:63 | 0.00 | 01-FEB-00:10 | 55908.78 | 11-FEB-08:62 | 32488.08 | 18-FEB-08:62 | 25903.00 | 11-FEB-08:62 | 11516.77 | 11-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.177798E+11 | 0.432002E+10 | 456.72 | 0.117204E+11 | 0.605937E+10 | 0.00 | 1.00 | 04-MAR-08:63 | 0.00 | 01-MAR-00:10 | 56339.58 | 14-MAR-07:03 | 29486.24 | 05-MAR-08:62 | 28278.44 | 14-MAR-07:03 | 11463.40 | 05-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.230644E+11 | 0.561193E+10 | 477.19 | 0.154753E+11 | 0.758911E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 56015.96 | 13-APR-07:03 | 34248.64 | 14-APR-07:03 | 25641.39 | 13-APR-07:03 | 11657.86 | 12-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.318938E+11 | 0.761872E+10 | 498.10 | 0.198118E+11 | 0.120820E+11 | 0.00 | 1.00 | 02-MAY-07:03 | 0.00 | 01-MAY-00:10 | 57028.53 | 29-MAY-07:02 | 36911.22 | 09-MAY-07:03 | 29900.33 | 29-MAY-07:02 | 11809.05 | 31-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.357551E+11 | 0.841305E+10 | 486.29 | 0.209942E+11 | 0.147609E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 56612.59 | 08-JUN-07:02 | 34544.65 | 14-JUN-07:03 | 26894.18 | 19-JUN-07:02 | 12018.24 | 09-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.397826E+11 | 0.942879E+10 | 500.72 | 0.238474E+11 | 0.159352E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 55991.23 | 09-JUL-07:01 | 38543.86 | 02-JUL-07:02 | 24624.90 | 09-JUL-07:03 | 11992.89 | 09-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.387039E+11 | 0.911302E+10 | 502.02 | 0.226506E+11 | 0.160533E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 56395.55 | 20-AUG-07:01 | 36664.21 | 08-AUG-07:02 | 26544.17 | 14-AUG-07:02 | 12099.73 | 20-AUG-07:04 | 0.00 | 01-AUG-00:10 |
September | 0.371713E+11 | 0.875001E+10 | 484.03 | 0.222074E+11 | 0.149639E+11 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 56530.77 | 19-SEP-07:01 | 35682.78 | 11-SEP-07:01 | 26130.52 | 20-SEP-07:03 | 11936.60 | 22-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.334521E+11 | 0.790216E+10 | 498.39 | 0.205050E+11 | 0.129471E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 57294.84 | 03-OCT-07:02 | 39368.32 | 18-OCT-07:02 | 30142.26 | 03-OCT-07:04 | 11827.91 | 02-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.247591E+11 | 0.586783E+10 | 470.78 | 0.152072E+11 | 0.955187E+10 | 0.00 | 1.00 | 03-NOV-07:03 | 0.00 | 01-NOV-00:10 | 57190.57 | 30-NOV-08:62 | 34921.72 | 09-NOV-08:62 | 29550.42 | 30-NOV-08:62 | 11688.45 | 21-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.162587E+11 | 0.391390E+10 | 449.98 | 0.102448E+11 | 0.601383E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-01:05 | 55931.34 | 09-DEC-08:62 | 37102.96 | 01-DEC-08:62 | 24968.38 | 09-DEC-08:62 | 11538.94 | 09-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.325995E+12 | 0.776826E+11 | 5667.92 | 0.201323E+12 | 0.124672E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.127193E+11 | 0.314021E+10 | 405.93 | 0.851499E+10 | 0.420433E+10 | 0.00 | 1.00 | 0.00 | 53096.22 | 29174.65 | 23921.57 | 10670.41 | 0.00 | |||||||
Maximum of Months | 0.397826E+11 | 0.942879E+10 | 502.02 | 0.238474E+11 | 0.160533E+11 | 0.00 | 1.00 | 0.00 | 57294.84 | 39368.32 | 30142.26 | 12099.73 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.715863E+10 | 0.173605E+10 | 462.85 | 0.495769E+10 | 0.220093E+10 | 0.00 | 1.00 | 02-JAN-14:20 | 0.00 | 01-JAN-00:05 | 25822.92 | 14-JAN-08:62 | 16575.68 | 14-JAN-08:62 | 9247.24 | 14-JAN-08:62 | 5159.54 | 14-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.785565E+10 | 0.189950E+10 | 426.93 | 0.555864E+10 | 0.229701E+10 | 0.00 | 1.00 | 02-FEB-08:63 | 0.00 | 01-FEB-00:10 | 27766.95 | 11-FEB-08:62 | 18732.53 | 18-FEB-08:62 | 9862.11 | 11-FEB-08:62 | 5740.49 | 11-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.921819E+10 | 0.220853E+10 | 467.89 | 0.622016E+10 | 0.299803E+10 | 0.00 | 1.00 | 04-MAR-08:63 | 0.00 | 01-MAR-00:10 | 28071.39 | 14-MAR-07:03 | 17664.20 | 05-MAR-08:62 | 11292.24 | 14-MAR-07:03 | 5714.63 | 05-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.115766E+11 | 0.277977E+10 | 477.86 | 0.788252E+10 | 0.369409E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 27871.65 | 13-APR-07:03 | 18617.99 | 14-APR-07:03 | 10045.52 | 13-APR-07:03 | 5816.97 | 12-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.157110E+11 | 0.371139E+10 | 499.05 | 0.989740E+10 | 0.581361E+10 | 0.00 | 1.00 | 02-MAY-07:03 | 0.00 | 01-MAY-00:10 | 28170.06 | 27-MAY-07:02 | 20525.15 | 22-MAY-07:02 | 11227.52 | 27-MAY-07:02 | 5900.38 | 31-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.176061E+11 | 0.409431E+10 | 487.09 | 0.104743E+11 | 0.713176E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 28112.39 | 18-JUN-07:02 | 19957.71 | 23-JUN-07:02 | 10704.17 | 08-JUN-07:03 | 6031.67 | 08-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.194976E+11 | 0.457022E+10 | 501.66 | 0.118009E+11 | 0.769670E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 27828.27 | 09-JUL-07:01 | 21430.49 | 02-JUL-07:02 | 9785.09 | 09-JUL-07:03 | 6009.55 | 09-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.189653E+11 | 0.441440E+10 | 502.23 | 0.112154E+11 | 0.774990E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 28042.51 | 14-AUG-07:02 | 20455.15 | 08-AUG-07:02 | 10401.17 | 27-AUG-07:03 | 6073.88 | 20-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.182543E+11 | 0.424680E+10 | 485.19 | 0.110290E+11 | 0.722524E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 28081.83 | 19-SEP-07:01 | 20540.03 | 04-SEP-07:02 | 10416.58 | 19-SEP-07:03 | 5977.37 | 22-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.165776E+11 | 0.386747E+10 | 498.54 | 0.103198E+11 | 0.625780E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 28363.11 | 03-OCT-07:02 | 21351.88 | 18-OCT-07:02 | 11792.68 | 03-OCT-07:02 | 5926.72 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.125996E+11 | 0.294498E+10 | 474.23 | 0.791839E+10 | 0.468116E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 28418.26 | 30-NOV-08:62 | 19877.34 | 09-NOV-08:62 | 11895.93 | 30-NOV-08:62 | 5854.07 | 30-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.869813E+10 | 0.206670E+10 | 471.24 | 0.567240E+10 | 0.302573E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-01:05 | 27692.08 | 09-DEC-08:62 | 20710.11 | 01-DEC-08:62 | 9222.81 | 07-DEC-08:62 | 5746.84 | 09-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.163719E+12 | 0.385401E+11 | 5754.76 | 0.102947E+12 | 0.607720E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.715863E+10 | 0.173605E+10 | 426.93 | 0.495769E+10 | 0.220093E+10 | 0.00 | 1.00 | 0.00 | 25822.92 | 16575.68 | 9222.81 | 5159.54 | 0.00 | |||||||
Maximum of Months | 0.194976E+11 | 0.457022E+10 | 502.23 | 0.118009E+11 | 0.774990E+10 | 0.00 | 1.00 | 0.00 | 28418.26 | 21430.49 | 11895.93 | 6073.88 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.523738E+10 | 0.126706E+10 | 317.18 | 0.356469E+10 | 0.167269E+10 | 0.00 | 1.00 | 01-JAN-08:63 | 0.00 | 01-JAN-00:05 | 28778.25 | 14-JAN-07:03 | 15998.88 | 14-JAN-07:03 | 12779.37 | 14-JAN-07:03 | 5704.42 | 14-JAN-07:03 | 0.00 | 01-JAN-00:05 |
February | 0.598529E+10 | 0.144630E+10 | 297.92 | 0.418469E+10 | 0.180061E+10 | 0.00 | 1.00 | 02-FEB-07:03 | 0.00 | 01-FEB-00:10 | 29093.64 | 11-FEB-07:03 | 16870.66 | 18-FEB-07:03 | 14033.00 | 19-FEB-08:62 | 5826.97 | 11-FEB-07:03 | 0.00 | 01-FEB-00:10 |
March | 0.704740E+10 | 0.168349E+10 | 331.71 | 0.467006E+10 | 0.237734E+10 | 0.00 | 1.00 | 04-MAR-07:03 | 0.00 | 01-MAR-00:10 | 29496.59 | 06-MAR-07:03 | 16986.27 | 28-MAR-06:03 | 15734.61 | 06-MAR-07:03 | 5832.10 | 05-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.904765E+10 | 0.216538E+10 | 349.18 | 0.605600E+10 | 0.299166E+10 | 0.00 | 1.00 | 01-APR-06:03 | 0.00 | 01-APR-00:05 | 29036.66 | 13-APR-06:02 | 17596.94 | 25-APR-06:03 | 13299.53 | 13-APR-06:02 | 5880.48 | 12-APR-06:03 | 0.00 | 01-APR-00:05 |
May | 0.126630E+11 | 0.297543E+10 | 369.33 | 0.783544E+10 | 0.482758E+10 | 0.00 | 1.00 | 02-MAY-06:03 | 0.00 | 01-MAY-00:10 | 30167.83 | 29-MAY-07:02 | 18990.96 | 09-MAY-06:03 | 17745.44 | 29-MAY-07:02 | 5996.31 | 14-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.143421E+11 | 0.329464E+10 | 362.35 | 0.831831E+10 | 0.602383E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 29988.41 | 19-JUN-06:02 | 16946.78 | 17-JUN-06:02 | 17016.99 | 19-JUN-06:02 | 6097.34 | 08-JUN-06:03 | 0.00 | 01-JUN-00:10 |
July | 0.158386E+11 | 0.368121E+10 | 366.23 | 0.936051E+10 | 0.647807E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 29980.42 | 10-JUL-06:01 | 17254.00 | 02-JUL-07:02 | 16521.68 | 24-JUL-06:03 | 6104.81 | 16-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.156376E+11 | 0.360577E+10 | 375.78 | 0.904009E+10 | 0.659748E+10 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 30221.20 | 28-AUG-06:02 | 17308.39 | 08-AUG-06:02 | 17263.58 | 28-AUG-06:02 | 6144.17 | 20-AUG-07:04 | 0.00 | 01-AUG-00:10 |
September | 0.147648E+11 | 0.339414E+10 | 356.02 | 0.869782E+10 | 0.606700E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 29845.61 | 18-SEP-06:01 | 17072.97 | 09-SEP-06:01 | 15626.53 | 25-SEP-06:04 | 6062.20 | 22-SEP-06:03 | 0.00 | 01-SEP-00:05 |
October | 0.133530E+11 | 0.308894E+10 | 365.10 | 0.814738E+10 | 0.520560E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 30198.72 | 02-OCT-06:02 | 20595.11 | 18-OCT-06:02 | 18060.51 | 30-OCT-06:03 | 5974.75 | 30-OCT-06:05 | 0.00 | 01-OCT-00:10 |
November | 0.998534E+10 | 0.231890E+10 | 345.48 | 0.615566E+10 | 0.382968E+10 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 30015.62 | 05-NOV-07:02 | 17834.15 | 21-NOV-07:02 | 16800.37 | 05-NOV-07:03 | 5924.19 | 04-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 0.638370E+10 | 0.151228E+10 | 325.38 | 0.410599E+10 | 0.227771E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 29342.47 | 11-DEC-07:02 | 16710.26 | 01-DEC-07:02 | 15461.38 | 26-DEC-07:03 | 5847.83 | 09-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.130286E+12 | 0.304335E+11 | 4161.64 | 0.801366E+11 | 0.501492E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.523738E+10 | 0.126706E+10 | 297.92 | 0.356469E+10 | 0.167269E+10 | 0.00 | 1.00 | 0.00 | 28778.25 | 15998.88 | 12779.37 | 5704.42 | 0.00 | |||||||
Maximum of Months | 0.158386E+11 | 0.368121E+10 | 375.78 | 0.936051E+10 | 0.659748E+10 | 0.00 | 1.00 | 0.00 | 30221.20 | 20595.11 | 18060.51 | 6144.17 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.519831E+10 | 0.125863E+10 | 315.35 | 0.353331E+10 | 0.166500E+10 | 0.00 | 1.00 | 01-JAN-08:63 | 0.00 | 01-JAN-00:05 | 28892.97 | 14-JAN-07:03 | 16060.37 | 14-JAN-07:03 | 12832.59 | 14-JAN-07:03 | 5727.02 | 14-JAN-07:03 | 0.00 | 01-JAN-00:05 |
February | 0.595370E+10 | 0.143993E+10 | 296.17 | 0.416059E+10 | 0.179311E+10 | 0.00 | 1.00 | 02-FEB-07:03 | 0.00 | 01-FEB-00:10 | 29209.20 | 11-FEB-07:03 | 16942.39 | 18-FEB-07:03 | 14088.91 | 19-FEB-08:62 | 5850.01 | 11-FEB-07:03 | 0.00 | 01-FEB-00:10 |
March | 0.702899E+10 | 0.168022E+10 | 331.46 | 0.465564E+10 | 0.237335E+10 | 0.00 | 1.00 | 04-MAR-07:03 | 0.00 | 01-MAR-00:10 | 29614.56 | 06-MAR-07:03 | 17238.83 | 28-MAR-06:03 | 15791.40 | 06-MAR-07:03 | 5855.14 | 05-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.906459E+10 | 0.217049E+10 | 349.43 | 0.606990E+10 | 0.299470E+10 | 0.00 | 1.00 | 01-APR-06:03 | 0.00 | 01-APR-00:05 | 29153.51 | 13-APR-06:02 | 17787.03 | 25-APR-06:03 | 13345.04 | 13-APR-06:02 | 5903.77 | 12-APR-06:03 | 0.00 | 01-APR-00:05 |
May | 0.127021E+11 | 0.298567E+10 | 369.48 | 0.786536E+10 | 0.483672E+10 | 0.00 | 1.00 | 02-MAY-06:03 | 0.00 | 01-MAY-00:10 | 30290.08 | 29-MAY-07:02 | 19084.19 | 09-MAY-06:03 | 17796.64 | 29-MAY-07:02 | 6020.02 | 14-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.144102E+11 | 0.331071E+10 | 362.42 | 0.836887E+10 | 0.604132E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 30113.44 | 19-JUN-06:02 | 17051.38 | 17-JUN-06:02 | 17044.39 | 19-JUN-06:02 | 6121.41 | 08-JUN-06:03 | 0.00 | 01-JUN-00:10 |
July | 0.159234E+11 | 0.370111E+10 | 366.53 | 0.942440E+10 | 0.649895E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 30114.28 | 10-JUL-06:01 | 17374.90 | 02-JUL-07:02 | 16522.03 | 24-JUL-06:03 | 6128.93 | 16-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.157045E+11 | 0.362180E+10 | 376.24 | 0.909004E+10 | 0.661450E+10 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 30347.71 | 28-AUG-06:02 | 17418.79 | 08-AUG-06:02 | 17276.26 | 28-AUG-06:02 | 6168.33 | 20-AUG-07:04 | 0.00 | 01-AUG-00:10 |
September | 0.148470E+11 | 0.341305E+10 | 355.98 | 0.875946E+10 | 0.608757E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 29977.98 | 18-SEP-06:01 | 17196.27 | 09-SEP-06:01 | 15619.92 | 25-SEP-06:04 | 6086.08 | 22-SEP-06:03 | 0.00 | 01-SEP-00:05 |
October | 0.134144E+11 | 0.310349E+10 | 365.10 | 0.819366E+10 | 0.522074E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 30318.03 | 02-OCT-06:02 | 20698.10 | 18-OCT-06:02 | 18078.15 | 30-OCT-06:05 | 5998.03 | 30-OCT-06:05 | 0.00 | 01-OCT-00:10 |
November | 0.999557E+10 | 0.232243E+10 | 345.44 | 0.616321E+10 | 0.383236E+10 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 30137.99 | 05-NOV-07:02 | 17922.58 | 21-NOV-07:02 | 16839.01 | 05-NOV-07:03 | 5947.59 | 04-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 0.635626E+10 | 0.150680E+10 | 324.55 | 0.408722E+10 | 0.226904E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 29463.92 | 11-DEC-07:02 | 16786.66 | 01-DEC-07:02 | 15519.36 | 26-DEC-07:03 | 5871.01 | 09-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.130599E+12 | 0.305143E+11 | 4158.13 | 0.803716E+11 | 0.502274E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.519831E+10 | 0.125863E+10 | 296.17 | 0.353331E+10 | 0.166500E+10 | 0.00 | 1.00 | 0.00 | 28892.97 | 16060.37 | 12832.59 | 5727.02 | 0.00 | |||||||
Maximum of Months | 0.159234E+11 | 0.370111E+10 | 376.24 | 0.942440E+10 | 0.661450E+10 | 0.00 | 1.00 | 0.00 | 30347.71 | 20698.10 | 18078.15 | 6168.33 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.497733E+10 | 0.120716E+10 | 309.60 | 0.336101E+10 | 0.161633E+10 | 0.00 | 1.00 | 01-JAN-08:63 | 0.00 | 01-JAN-00:05 | 28686.68 | 14-JAN-07:03 | 15830.71 | 14-JAN-07:03 | 12855.97 | 14-JAN-07:03 | 5687.59 | 14-JAN-07:03 | 0.00 | 01-JAN-00:05 |
February | 0.575329E+10 | 0.139418E+10 | 292.00 | 0.400517E+10 | 0.174812E+10 | 0.00 | 1.00 | 10-FEB-07:03 | 0.00 | 01-FEB-00:10 | 29003.98 | 11-FEB-07:03 | 16710.66 | 18-FEB-07:03 | 14088.13 | 19-FEB-08:62 | 5810.24 | 11-FEB-07:03 | 0.00 | 01-FEB-00:10 |
March | 0.680843E+10 | 0.163018E+10 | 328.38 | 0.448599E+10 | 0.232244E+10 | 0.00 | 1.00 | 04-MAR-07:03 | 0.00 | 01-MAR-00:10 | 29403.67 | 06-MAR-07:03 | 15700.50 | 28-MAR-06:03 | 15763.07 | 06-MAR-07:03 | 5815.33 | 05-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.886542E+10 | 0.212588E+10 | 349.18 | 0.591729E+10 | 0.294813E+10 | 0.00 | 1.00 | 01-APR-06:03 | 0.00 | 01-APR-00:05 | 28947.96 | 13-APR-06:02 | 17309.27 | 17-APR-06:03 | 13372.52 | 13-APR-06:02 | 5863.56 | 12-APR-06:03 | 0.00 | 01-APR-00:05 |
May | 0.125077E+11 | 0.294263E+10 | 369.71 | 0.772039E+10 | 0.478733E+10 | 0.00 | 1.00 | 02-MAY-06:03 | 0.00 | 01-MAY-00:10 | 30072.74 | 29-MAY-07:02 | 18853.27 | 09-MAY-06:03 | 17771.06 | 29-MAY-07:02 | 5979.31 | 14-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.142265E+11 | 0.326946E+10 | 362.23 | 0.823324E+10 | 0.599326E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 29900.34 | 19-JUN-06:02 | 16817.15 | 17-JUN-06:02 | 16997.19 | 19-JUN-06:02 | 6080.09 | 08-JUN-06:03 | 0.00 | 01-JUN-00:10 |
July | 0.157503E+11 | 0.366062E+10 | 366.38 | 0.929410E+10 | 0.645616E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 29901.98 | 10-JUL-06:01 | 17153.42 | 02-JUL-07:02 | 16467.96 | 24-JUL-06:03 | 6087.53 | 16-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.155138E+11 | 0.357830E+10 | 376.18 | 0.894958E+10 | 0.656421E+10 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 30135.37 | 28-AUG-06:02 | 17180.32 | 08-AUG-06:02 | 17242.85 | 28-AUG-06:02 | 6126.75 | 20-AUG-07:04 | 0.00 | 01-AUG-00:10 |
September | 0.146773E+11 | 0.337454E+10 | 355.82 | 0.863251E+10 | 0.604480E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 29767.07 | 18-SEP-06:01 | 16950.47 | 09-SEP-06:01 | 15557.12 | 25-SEP-06:04 | 6045.03 | 22-SEP-06:03 | 0.00 | 01-SEP-00:05 |
October | 0.132357E+11 | 0.306366E+10 | 365.17 | 0.805902E+10 | 0.517665E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 30113.21 | 02-OCT-06:02 | 20462.17 | 18-OCT-06:02 | 18031.95 | 30-OCT-06:03 | 5957.84 | 30-OCT-06:05 | 0.00 | 01-OCT-00:10 |
November | 0.979362E+10 | 0.227793E+10 | 345.28 | 0.601180E+10 | 0.378183E+10 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 29926.87 | 05-NOV-07:02 | 17693.99 | 21-NOV-07:02 | 16822.00 | 05-NOV-07:03 | 5907.42 | 04-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 0.613479E+10 | 0.145608E+10 | 320.56 | 0.392264E+10 | 0.221215E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 29255.10 | 11-DEC-07:02 | 16530.21 | 01-DEC-07:02 | 15489.82 | 26-DEC-07:03 | 5831.15 | 09-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.128244E+12 | 0.299806E+11 | 4140.48 | 0.785927E+11 | 0.496514E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.497733E+10 | 0.120716E+10 | 292.00 | 0.336101E+10 | 0.161633E+10 | 0.00 | 1.00 | 0.00 | 28686.68 | 15700.50 | 12855.97 | 5687.59 | 0.00 | |||||||
Maximum of Months | 0.157503E+11 | 0.366062E+10 | 376.18 | 0.929410E+10 | 0.656421E+10 | 0.00 | 1.00 | 0.00 | 30135.37 | 20462.17 | 18031.95 | 6126.75 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.876682E+10 | 0.214459E+10 | 291.43 | 0.570831E+10 | 0.305850E+10 | 0.00 | 1.00 | 01-JAN-09:03 | 0.00 | 01-JAN-00:05 | 48957.92 | 14-JAN-08:62 | 26786.78 | 14-JAN-08:62 | 22171.13 | 14-JAN-08:62 | 9842.29 | 14-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.104110E+11 | 0.254458E+10 | 288.06 | 0.706635E+10 | 0.334463E+10 | 0.00 | 1.00 | 11-FEB-08:62 | 0.00 | 01-FEB-00:10 | 51711.09 | 11-FEB-08:62 | 29847.38 | 18-FEB-08:62 | 24445.37 | 11-FEB-08:62 | 10641.38 | 11-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.123635E+11 | 0.297949E+10 | 323.31 | 0.790562E+10 | 0.445789E+10 | 0.00 | 1.00 | 04-MAR-08:63 | 0.00 | 01-MAR-00:10 | 52696.13 | 06-MAR-08:62 | 27108.80 | 14-MAR-07:03 | 28357.43 | 06-MAR-08:62 | 10660.08 | 05-MAR-09:02 | 0.00 | 01-MAR-00:10 |
April | 0.163887E+11 | 0.394688E+10 | 340.32 | 0.106714E+11 | 0.571730E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 51536.79 | 13-APR-07:03 | 30843.99 | 17-APR-07:03 | 23137.42 | 13-APR-07:03 | 10761.41 | 12-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.234556E+11 | 0.552735E+10 | 360.06 | 0.141346E+11 | 0.932099E+10 | 0.00 | 1.00 | 02-MAY-07:03 | 0.00 | 01-MAY-00:10 | 53897.92 | 29-MAY-08:62 | 34063.19 | 09-MAY-07:03 | 31826.93 | 29-MAY-08:62 | 10986.81 | 14-MAY-08:03 | 0.00 | 01-MAY-00:10 |
June | 0.268741E+11 | 0.620111E+10 | 353.35 | 0.151574E+11 | 0.117167E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 53548.48 | 19-JUN-07:02 | 31057.14 | 02-JUN-07:02 | 30304.95 | 19-JUN-07:02 | 11125.91 | 11-JUN-08:04 | 0.00 | 01-JUN-00:10 |
July | 0.297994E+11 | 0.696736E+10 | 355.08 | 0.172038E+11 | 0.125956E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 53654.24 | 10-JUL-07:01 | 32395.81 | 07-JUL-07:03 | 29530.89 | 24-JUL-07:03 | 11260.01 | 23-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.293478E+11 | 0.680933E+10 | 368.01 | 0.165217E+11 | 0.128262E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 53995.82 | 28-AUG-07:02 | 32722.98 | 08-AUG-07:02 | 30904.50 | 28-AUG-07:02 | 11230.67 | 20-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.277335E+11 | 0.641241E+10 | 345.00 | 0.159278E+11 | 0.118057E+11 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 53367.49 | 18-SEP-07:01 | 31641.48 | 14-SEP-07:02 | 28201.69 | 25-SEP-07:04 | 11026.92 | 22-SEP-07:03 | 0.00 | 01-SEP-00:05 |
October | 0.248241E+11 | 0.576736E+10 | 354.40 | 0.147566E+11 | 0.100676E+11 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 53957.47 | 30-OCT-07:02 | 36681.88 | 18-OCT-07:02 | 32531.56 | 30-OCT-07:05 | 10984.55 | 29-OCT-08:04 | 0.00 | 01-OCT-00:10 |
November | 0.182093E+11 | 0.424674E+10 | 337.79 | 0.108277E+11 | 0.738151E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 53812.95 | 05-NOV-08:62 | 32124.70 | 21-NOV-08:62 | 31032.07 | 05-NOV-08:62 | 10784.81 | 21-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.108834E+11 | 0.259456E+10 | 307.60 | 0.672109E+10 | 0.416227E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 52376.37 | 10-DEC-09:02 | 30964.33 | 01-DEC-08:62 | 26704.67 | 24-DEC-09:03 | 10802.20 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.239057E+12 | 0.561417E+11 | 4024.40 | 0.142602E+12 | 0.964548E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.876682E+10 | 0.214459E+10 | 288.06 | 0.570831E+10 | 0.305850E+10 | 0.00 | 1.00 | 0.00 | 48957.92 | 26786.78 | 22171.13 | 9842.29 | 0.00 | |||||||
Maximum of Months | 0.297994E+11 | 0.696736E+10 | 368.01 | 0.172038E+11 | 0.128262E+11 | 0.00 | 1.00 | 0.00 | 53995.82 | 36681.88 | 32531.56 | 11260.01 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.449457E+10 | 0.108175E+10 | 286.60 | 0.292385E+10 | 0.157072E+10 | 0.00 | 1.00 | 01-JAN-09:03 | 0.00 | 01-JAN-00:05 | 23682.21 | 14-JAN-08:62 | 12933.85 | 14-JAN-08:62 | 10748.36 | 14-JAN-08:62 | 4678.97 | 14-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.536155E+10 | 0.128969E+10 | 287.31 | 0.364053E+10 | 0.172102E+10 | 0.00 | 1.00 | 11-FEB-08:62 | 0.00 | 01-FEB-00:10 | 26686.81 | 18-FEB-08:62 | 15667.86 | 18-FEB-08:62 | 12518.24 | 11-FEB-08:62 | 5398.08 | 18-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.636246E+10 | 0.150916E+10 | 321.47 | 0.406512E+10 | 0.229734E+10 | 0.00 | 1.00 | 04-MAR-08:63 | 0.00 | 01-MAR-00:10 | 27638.64 | 06-MAR-08:62 | 13652.14 | 14-MAR-07:03 | 14916.70 | 06-MAR-08:62 | 5489.17 | 05-MAR-09:02 | 0.00 | 01-MAR-00:10 |
April | 0.848276E+10 | 0.201061E+10 | 340.65 | 0.552447E+10 | 0.295830E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 27000.30 | 13-APR-07:03 | 16146.27 | 17-APR-07:03 | 12089.47 | 13-APR-07:03 | 5540.64 | 12-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.121886E+11 | 0.282689E+10 | 361.62 | 0.734587E+10 | 0.484268E+10 | 0.00 | 1.00 | 03-MAY-07:03 | 0.00 | 01-MAY-00:10 | 28247.78 | 29-MAY-08:62 | 17883.96 | 09-MAY-07:03 | 16750.24 | 29-MAY-08:62 | 5657.11 | 14-MAY-08:03 | 0.00 | 01-MAY-00:10 |
June | 0.139763E+11 | 0.317397E+10 | 355.59 | 0.788217E+10 | 0.609409E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 28093.92 | 26-JUN-07:02 | 16303.12 | 02-JUN-07:02 | 15965.06 | 19-JUN-07:02 | 5728.84 | 11-JUN-08:04 | 0.00 | 01-JUN-00:10 |
July | 0.155263E+11 | 0.357272E+10 | 355.51 | 0.896218E+10 | 0.656414E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 28161.08 | 10-JUL-07:01 | 17010.75 | 07-JUL-07:03 | 15603.76 | 24-JUL-07:03 | 5797.74 | 23-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.152759E+11 | 0.348785E+10 | 368.49 | 0.859892E+10 | 0.667699E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 28312.83 | 28-AUG-07:02 | 17200.88 | 08-AUG-07:02 | 16347.34 | 28-AUG-07:03 | 5782.75 | 20-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.144323E+11 | 0.328370E+10 | 346.46 | 0.828847E+10 | 0.614386E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 27998.45 | 18-SEP-07:01 | 16623.29 | 14-SEP-07:02 | 14891.56 | 25-SEP-07:04 | 5677.81 | 22-SEP-07:03 | 0.00 | 01-SEP-00:05 |
October | 0.129167E+11 | 0.295259E+10 | 356.12 | 0.767878E+10 | 0.523789E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 28278.99 | 30-OCT-07:02 | 19237.74 | 18-OCT-07:02 | 17134.60 | 30-OCT-07:05 | 5655.81 | 29-OCT-08:04 | 0.00 | 01-OCT-00:10 |
November | 0.944017E+10 | 0.216638E+10 | 338.81 | 0.561348E+10 | 0.382670E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 28229.56 | 05-NOV-08:62 | 16859.15 | 21-NOV-08:62 | 16353.25 | 05-NOV-08:62 | 5552.62 | 21-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.559676E+10 | 0.131268E+10 | 306.68 | 0.345390E+10 | 0.214285E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 27472.79 | 10-DEC-09:02 | 16245.28 | 01-DEC-08:62 | 13995.45 | 11-DEC-08:62 | 5562.24 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.124054E+12 | 0.286680E+11 | 4025.31 | 0.739777E+11 | 0.500766E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.449457E+10 | 0.108175E+10 | 286.60 | 0.292385E+10 | 0.157072E+10 | 0.00 | 1.00 | 0.00 | 23682.21 | 12933.85 | 10748.36 | 4678.97 | 0.00 | |||||||
Maximum of Months | 0.155263E+11 | 0.357272E+10 | 368.49 | 0.896218E+10 | 0.667699E+10 | 0.00 | 1.00 | 0.00 | 28312.83 | 19237.74 | 17134.60 | 5797.74 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.442844E+10 | 0.106608E+10 | 283.51 | 0.287415E+10 | 0.155429E+10 | 0.00 | 1.00 | 01-JAN-09:03 | 0.00 | 01-JAN-00:05 | 23000.59 | 14-JAN-08:62 | 12521.30 | 14-JAN-08:62 | 10479.29 | 14-JAN-08:62 | 4544.78 | 14-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.529764E+10 | 0.127474E+10 | 286.31 | 0.359243E+10 | 0.170521E+10 | 0.00 | 1.00 | 11-FEB-08:62 | 0.00 | 01-FEB-00:10 | 26572.71 | 18-FEB-08:62 | 15573.43 | 18-FEB-08:62 | 12244.94 | 11-FEB-08:62 | 5375.02 | 18-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.629666E+10 | 0.149380E+10 | 320.26 | 0.401617E+10 | 0.228049E+10 | 0.00 | 1.00 | 05-MAR-09:02 | 0.00 | 01-MAR-00:10 | 27518.45 | 06-MAR-08:62 | 13256.23 | 14-MAR-07:03 | 14871.39 | 06-MAR-08:62 | 5465.70 | 05-MAR-09:02 | 0.00 | 01-MAR-00:10 |
April | 0.842638E+10 | 0.199734E+10 | 340.61 | 0.548255E+10 | 0.294383E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 26886.42 | 13-APR-07:03 | 16064.97 | 17-APR-07:03 | 12068.05 | 13-APR-07:03 | 5517.02 | 12-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.121325E+11 | 0.281352E+10 | 361.66 | 0.730562E+10 | 0.482689E+10 | 0.00 | 1.00 | 03-MAY-07:03 | 0.00 | 01-MAY-00:10 | 28127.13 | 29-MAY-08:62 | 17785.65 | 09-MAY-07:03 | 16697.01 | 29-MAY-08:62 | 5632.95 | 14-MAY-08:03 | 0.00 | 01-MAY-00:10 |
June | 0.139263E+11 | 0.316188E+10 | 355.56 | 0.784646E+10 | 0.607984E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 27973.96 | 26-JUN-07:02 | 16209.90 | 02-JUN-07:02 | 15910.47 | 19-JUN-07:02 | 5704.38 | 11-JUN-08:04 | 0.00 | 01-JUN-00:10 |
July | 0.154793E+11 | 0.356099E+10 | 355.51 | 0.892785E+10 | 0.655141E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 28040.94 | 10-JUL-07:01 | 16911.65 | 07-JUL-07:03 | 15546.02 | 24-JUL-07:03 | 5772.97 | 23-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.152251E+11 | 0.347541E+10 | 368.44 | 0.856260E+10 | 0.666252E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 28191.91 | 28-AUG-07:02 | 17100.18 | 08-AUG-07:02 | 16291.74 | 28-AUG-07:03 | 5758.02 | 20-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.143864E+11 | 0.327244E+10 | 346.53 | 0.825511E+10 | 0.613131E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 27879.13 | 18-SEP-07:01 | 16525.20 | 14-SEP-07:02 | 14835.72 | 25-SEP-07:04 | 5653.57 | 22-SEP-07:03 | 0.00 | 01-SEP-00:05 |
October | 0.128644E+11 | 0.294007E+10 | 356.15 | 0.764050E+10 | 0.522390E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 28158.21 | 30-OCT-07:02 | 19137.38 | 18-OCT-07:02 | 17072.62 | 30-OCT-07:05 | 5631.65 | 29-OCT-08:04 | 0.00 | 01-OCT-00:10 |
November | 0.938019E+10 | 0.215244E+10 | 338.48 | 0.556968E+10 | 0.381052E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 28109.28 | 05-NOV-08:62 | 16766.16 | 21-NOV-08:62 | 16300.15 | 05-NOV-08:62 | 5528.94 | 21-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.552346E+10 | 0.129550E+10 | 305.02 | 0.340158E+10 | 0.212188E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 27354.47 | 10-DEC-09:02 | 16144.47 | 01-DEC-08:62 | 13952.12 | 11-DEC-08:62 | 5538.48 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.123367E+12 | 0.285042E+11 | 4018.03 | 0.734747E+11 | 0.498921E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.442844E+10 | 0.106608E+10 | 283.51 | 0.287415E+10 | 0.155429E+10 | 0.00 | 1.00 | 0.00 | 23000.59 | 12521.30 | 10479.29 | 4544.78 | 0.00 | |||||||
Maximum of Months | 0.154793E+11 | 0.356099E+10 | 368.44 | 0.892785E+10 | 0.666252E+10 | 0.00 | 1.00 | 0.00 | 28191.91 | 19137.38 | 17072.62 | 5772.97 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.429496E+10 | 0.103558E+10 | 276.76 | 0.277471E+10 | 0.152026E+10 | 0.00 | 1.00 | 01-JAN-09:03 | 0.00 | 01-JAN-00:05 | 20866.21 | 14-JAN-08:62 | 11247.10 | 14-JAN-08:62 | 9619.11 | 14-JAN-08:62 | 4125.13 | 14-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.517852E+10 | 0.124831E+10 | 283.06 | 0.350346E+10 | 0.167507E+10 | 0.00 | 1.00 | 11-FEB-08:62 | 0.00 | 01-FEB-00:10 | 24614.46 | 18-FEB-08:62 | 14305.58 | 18-FEB-08:62 | 10994.67 | 11-FEB-08:62 | 4981.16 | 18-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.619341E+10 | 0.147131E+10 | 317.35 | 0.394036E+10 | 0.225305E+10 | 0.00 | 1.00 | 05-MAR-09:02 | 0.00 | 01-MAR-00:10 | 27627.96 | 06-MAR-08:62 | 13191.98 | 05-MAR-09:02 | 15007.01 | 06-MAR-08:62 | 5489.86 | 05-MAR-09:02 | 0.00 | 01-MAR-00:10 |
April | 0.837594E+10 | 0.198726E+10 | 340.07 | 0.544597E+10 | 0.292997E+10 | 0.00 | 1.00 | 01-APR-14:50 | 0.00 | 01-APR-00:05 | 26996.14 | 13-APR-07:03 | 15962.54 | 17-APR-07:03 | 12181.84 | 13-APR-07:03 | 5541.10 | 12-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.121340E+11 | 0.281553E+10 | 361.70 | 0.730839E+10 | 0.482564E+10 | 0.00 | 1.00 | 03-MAY-07:03 | 0.00 | 01-MAY-00:10 | 28252.29 | 29-MAY-08:62 | 16803.01 | 08-MAY-07:03 | 16831.60 | 29-MAY-08:62 | 5658.09 | 14-MAY-08:03 | 0.00 | 01-MAY-00:10 |
June | 0.139757E+11 | 0.317396E+10 | 355.26 | 0.788239E+10 | 0.609333E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 28091.12 | 26-JUN-07:02 | 16259.54 | 02-JUN-07:02 | 16024.67 | 19-JUN-07:02 | 5729.76 | 11-JUN-08:04 | 0.00 | 01-JUN-00:10 |
July | 0.155592E+11 | 0.358016E+10 | 355.32 | 0.898697E+10 | 0.657221E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 28162.02 | 10-JUL-07:01 | 16969.31 | 07-JUL-07:03 | 15609.62 | 24-JUL-07:03 | 5798.70 | 23-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.152816E+11 | 0.348932E+10 | 368.26 | 0.860522E+10 | 0.667641E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 28317.35 | 28-AUG-07:02 | 17156.23 | 08-AUG-07:02 | 16387.28 | 28-AUG-07:03 | 5783.66 | 20-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.144627E+11 | 0.329039E+10 | 346.88 | 0.831090E+10 | 0.615181E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 28002.40 | 18-SEP-07:01 | 16595.33 | 14-SEP-07:02 | 14885.98 | 25-SEP-07:04 | 5678.70 | 22-SEP-07:03 | 0.00 | 01-SEP-00:05 |
October | 0.128854E+11 | 0.294600E+10 | 356.08 | 0.765635E+10 | 0.522901E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 28283.50 | 30-OCT-07:02 | 19178.58 | 18-OCT-07:02 | 17171.39 | 30-OCT-07:05 | 5653.25 | 29-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.932135E+10 | 0.214080E+10 | 337.55 | 0.552612E+10 | 0.379523E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 28225.82 | 05-NOV-08:62 | 16784.88 | 21-NOV-08:62 | 16410.19 | 05-NOV-08:62 | 5553.07 | 21-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.538099E+10 | 0.126318E+10 | 297.92 | 0.330077E+10 | 0.208022E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 27465.66 | 10-DEC-09:02 | 16146.81 | 01-DEC-08:62 | 14059.94 | 11-DEC-08:62 | 5563.09 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.123044E+12 | 0.284418E+11 | 3996.21 | 0.732416E+11 | 0.498022E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.429496E+10 | 0.103558E+10 | 276.76 | 0.277471E+10 | 0.152026E+10 | 0.00 | 1.00 | 0.00 | 20866.21 | 11247.10 | 9619.11 | 4125.13 | 0.00 | |||||||
Maximum of Months | 0.155592E+11 | 0.358016E+10 | 368.26 | 0.898697E+10 | 0.667641E+10 | 0.00 | 1.00 | 0.00 | 28317.35 | 19178.58 | 17171.39 | 5798.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.481291E+10 | 0.117026E+10 | 278.24 | 0.316068E+10 | 0.165223E+10 | 0.00 | 1.00 | 14-JAN-08:62 | 0.00 | 01-JAN-00:05 | 18381.05 | 14-JAN-08:62 | 9036.81 | 02-JAN-14:00 | 9457.28 | 14-JAN-08:62 | 3612.18 | 14-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.582750E+10 | 0.141720E+10 | 282.64 | 0.399443E+10 | 0.183307E+10 | 0.00 | 1.00 | 11-FEB-08:62 | 0.00 | 01-FEB-00:10 | 23005.27 | 18-FEB-08:62 | 12257.93 | 18-FEB-08:62 | 11376.18 | 11-FEB-08:62 | 4624.30 | 18-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.709237E+10 | 0.169925E+10 | 322.01 | 0.459203E+10 | 0.250034E+10 | 0.00 | 1.00 | 05-MAR-09:02 | 0.00 | 01-MAR-00:10 | 28410.19 | 05-MAR-09:02 | 12729.60 | 05-MAR-09:02 | 15680.58 | 05-MAR-09:02 | 5633.66 | 05-MAR-09:02 | 0.00 | 01-MAR-00:10 |
April | 0.975236E+10 | 0.232829E+10 | 341.90 | 0.646642E+10 | 0.328594E+10 | 0.00 | 1.00 | 12-APR-07:03 | 0.00 | 01-APR-00:05 | 32179.73 | 13-APR-07:03 | 16115.79 | 16-APR-08:62 | 16657.05 | 13-APR-07:03 | 6477.35 | 13-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.140938E+11 | 0.329820E+10 | 362.40 | 0.869410E+10 | 0.539966E+10 | 0.00 | 1.00 | 03-MAY-07:03 | 0.00 | 01-MAY-00:10 | 33577.00 | 29-MAY-08:62 | 17855.19 | 18-MAY-07:02 | 20732.32 | 29-MAY-08:04 | 6717.76 | 14-MAY-08:03 | 0.00 | 01-MAY-00:10 |
June | 0.162221E+11 | 0.371643E+10 | 356.17 | 0.942916E+10 | 0.679299E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 33604.85 | 26-JUN-07:02 | 18712.15 | 06-JUN-07:02 | 19349.55 | 19-JUN-07:02 | 6806.84 | 11-JUN-08:04 | 0.00 | 01-JUN-00:10 |
July | 0.181022E+11 | 0.420111E+10 | 356.07 | 0.108044E+11 | 0.729784E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 33618.92 | 10-JUL-07:01 | 19263.82 | 06-JUL-07:02 | 18994.57 | 31-JUL-07:03 | 6891.73 | 23-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.175737E+11 | 0.405181E+10 | 369.11 | 0.102085E+11 | 0.736523E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 33654.32 | 28-AUG-07:02 | 20234.25 | 08-AUG-07:02 | 19913.97 | 13-AUG-08:62 | 6866.07 | 20-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.167996E+11 | 0.385168E+10 | 347.98 | 0.995157E+10 | 0.684806E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 33557.37 | 18-SEP-07:01 | 18990.35 | 14-SEP-07:02 | 18239.24 | 18-SEP-07:04 | 6755.08 | 09-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.147641E+11 | 0.340667E+10 | 356.63 | 0.899182E+10 | 0.577230E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 33614.09 | 30-OCT-07:03 | 21891.79 | 18-OCT-07:02 | 21163.52 | 30-OCT-07:05 | 6710.63 | 09-OCT-08:03 | 0.00 | 01-OCT-00:10 |
November | 0.105058E+11 | 0.244271E+10 | 337.04 | 0.636340E+10 | 0.414240E+10 | 0.00 | 1.00 | 03-NOV-07:03 | 0.00 | 01-NOV-00:10 | 33675.25 | 05-NOV-08:62 | 18588.68 | 21-NOV-08:62 | 20238.87 | 05-NOV-08:62 | 6622.89 | 21-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.588951E+10 | 0.139753E+10 | 291.97 | 0.366252E+10 | 0.222699E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 32841.74 | 10-DEC-09:02 | 16167.13 | 01-DEC-08:62 | 17449.18 | 11-DEC-08:62 | 6611.34 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.141436E+12 | 0.329811E+11 | 4002.17 | 0.863190E+11 | 0.551170E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.481291E+10 | 0.117026E+10 | 278.24 | 0.316068E+10 | 0.165223E+10 | 0.00 | 1.00 | 0.00 | 18381.05 | 9036.81 | 9457.28 | 3612.18 | 0.00 | |||||||
Maximum of Months | 0.181022E+11 | 0.420111E+10 | 369.11 | 0.108044E+11 | 0.736523E+10 | 0.00 | 1.00 | 0.00 | 33675.25 | 21891.79 | 21163.52 | 6891.73 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.44 | 33.18 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.56 | 27.47 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.87 | 22.62 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.71 | 14.97 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.71 | 6.73 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 56.34 | 2.97 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 63.12 | 4.34 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.90 | 3.02 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 87.22 | 5.56 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.13 | 8.77 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.48 | 16.81 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.70 | 28.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.98 | 14.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.71 | 2.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.44 | 33.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.44 | 33.18 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.56 | 27.47 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.87 | 22.62 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.71 | 14.97 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.71 | 6.73 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 56.34 | 2.97 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 63.12 | 4.34 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.90 | 3.02 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 87.22 | 5.56 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.13 | 8.77 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.48 | 16.81 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.70 | 28.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.98 | 14.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.71 | 2.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.44 | 33.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.44 | 33.18 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.56 | 27.47 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.87 | 22.62 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.71 | 14.97 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.71 | 6.73 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 56.34 | 2.97 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 63.12 | 4.34 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.90 | 3.02 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 87.22 | 5.56 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.13 | 8.77 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.48 | 16.81 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.70 | 28.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.98 | 14.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.71 | 2.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.44 | 33.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.44 | 33.18 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.56 | 27.47 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.87 | 22.62 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.71 | 14.97 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.71 | 6.73 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 56.34 | 2.97 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 63.12 | 4.34 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.90 | 3.02 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 87.22 | 5.56 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.13 | 8.77 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.48 | 16.81 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.70 | 28.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.98 | 14.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.71 | 2.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.44 | 33.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.35 | 52.85 | 28.50 | 135.22 | 39.58 | 0.00 | 0.00 | 0.00 |
February | 73.59 | 42.58 | 31.01 | 129.38 | 32.79 | 0.00 | 0.00 | 0.00 |
March | 56.50 | 23.89 | 32.61 | 100.93 | 27.05 | 0.00 | 0.00 | 0.00 |
April | 38.42 | 6.74 | 31.68 | 75.29 | 17.98 | 0.00 | 0.00 | 0.00 |
May | 30.79 | 0.67 | 30.12 | 65.45 | 8.19 | 0.00 | 0.00 | 0.00 |
June | 29.35 | 0.06 | 29.30 | 67.23 | 3.60 | 0.00 | 0.00 | 0.00 |
July | 31.43 | 0.29 | 31.14 | 75.36 | 5.25 | 0.00 | 0.00 | 0.00 |
August | 35.67 | 3.01 | 32.66 | 81.12 | 3.66 | 0.00 | 0.00 | 0.00 |
September | 45.67 | 11.19 | 34.48 | 104.39 | 6.69 | 0.00 | 0.00 | 0.00 |
October | 62.80 | 29.46 | 33.34 | 127.28 | 10.61 | 0.00 | 0.00 | 0.00 |
November | 71.45 | 39.88 | 31.57 | 130.33 | 20.16 | 0.00 | 0.00 | 0.00 |
December | 78.40 | 49.45 | 28.95 | 133.14 | 34.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.86 | 21.58 | 31.28 | 101.95 | 17.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.35 | 0.06 | 28.50 | 65.45 | 3.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.35 | 52.85 | 34.48 | 135.22 | 39.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.35 | 52.85 | 28.50 | 135.22 | 39.58 | 0.00 | 0.00 | 0.00 |
February | 73.59 | 42.58 | 31.01 | 129.38 | 32.79 | 0.00 | 0.00 | 0.00 |
March | 56.50 | 23.89 | 32.61 | 100.93 | 27.05 | 0.00 | 0.00 | 0.00 |
April | 38.42 | 6.74 | 31.68 | 75.29 | 17.98 | 0.00 | 0.00 | 0.00 |
May | 30.79 | 0.67 | 30.12 | 65.45 | 8.19 | 0.00 | 0.00 | 0.00 |
June | 29.35 | 0.06 | 29.30 | 67.23 | 3.60 | 0.00 | 0.00 | 0.00 |
July | 31.43 | 0.29 | 31.14 | 75.36 | 5.25 | 0.00 | 0.00 | 0.00 |
August | 35.67 | 3.01 | 32.66 | 81.12 | 3.66 | 0.00 | 0.00 | 0.00 |
September | 45.67 | 11.19 | 34.48 | 104.39 | 6.69 | 0.00 | 0.00 | 0.00 |
October | 62.80 | 29.46 | 33.34 | 127.28 | 10.61 | 0.00 | 0.00 | 0.00 |
November | 71.45 | 39.88 | 31.57 | 130.33 | 20.16 | 0.00 | 0.00 | 0.00 |
December | 78.40 | 49.45 | 28.95 | 133.14 | 34.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.86 | 21.58 | 31.28 | 101.95 | 17.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.35 | 0.06 | 28.50 | 65.45 | 3.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.35 | 52.85 | 34.48 | 135.22 | 39.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 111.89 | 33.87 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.11 | 28.07 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.55 | 23.03 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.86 | 15.00 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 55.25 | 6.59 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 57.14 | 2.92 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 64.01 | 4.18 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 68.78 | 2.87 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 88.01 | 5.44 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.50 | 8.56 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.44 | 16.88 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.31 | 29.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 85.21 | 14.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 55.25 | 2.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 111.89 | 33.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 111.89 | 33.87 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.11 | 28.07 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.55 | 23.03 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.86 | 15.00 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 55.25 | 6.59 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 57.14 | 2.92 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 64.01 | 4.18 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 68.78 | 2.87 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 88.01 | 5.44 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.50 | 8.56 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.44 | 16.88 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.31 | 29.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 85.21 | 14.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 55.25 | 2.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 111.89 | 33.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.35 | 52.85 | 28.50 | 134.61 | 40.40 | 0.00 | 0.00 | 0.00 |
February | 73.59 | 42.58 | 31.01 | 128.89 | 33.50 | 0.00 | 0.00 | 0.00 |
March | 56.50 | 23.89 | 32.61 | 100.59 | 27.54 | 0.00 | 0.00 | 0.00 |
April | 38.42 | 6.74 | 31.68 | 75.49 | 18.01 | 0.00 | 0.00 | 0.00 |
May | 30.79 | 0.67 | 30.12 | 66.09 | 8.02 | 0.00 | 0.00 | 0.00 |
June | 29.35 | 0.06 | 29.30 | 68.18 | 3.55 | 0.00 | 0.00 | 0.00 |
July | 31.43 | 0.29 | 31.14 | 76.42 | 5.07 | 0.00 | 0.00 | 0.00 |
August | 35.67 | 3.01 | 32.66 | 82.17 | 3.47 | 0.00 | 0.00 | 0.00 |
September | 45.67 | 11.19 | 34.48 | 105.34 | 6.55 | 0.00 | 0.00 | 0.00 |
October | 62.80 | 29.46 | 33.34 | 127.74 | 10.36 | 0.00 | 0.00 | 0.00 |
November | 71.45 | 39.88 | 31.57 | 130.32 | 20.25 | 0.00 | 0.00 | 0.00 |
December | 78.40 | 49.45 | 28.95 | 132.72 | 35.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.86 | 21.58 | 31.28 | 102.25 | 17.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.35 | 0.06 | 28.50 | 66.09 | 3.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.35 | 52.85 | 34.48 | 134.61 | 40.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 111.92 | 34.65 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.13 | 28.99 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.46 | 24.03 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.60 | 16.41 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.80 | 8.16 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.54 | 3.80 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.63 | 5.55 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.53 | 3.98 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.36 | 6.54 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.08 | 10.43 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.35 | 18.31 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.31 | 30.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.61 | 15.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.80 | 3.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 111.92 | 34.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 111.92 | 34.65 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.13 | 28.99 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.46 | 24.03 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.60 | 16.41 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.80 | 8.16 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.54 | 3.80 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.63 | 5.55 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.53 | 3.98 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.36 | 6.54 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.08 | 10.43 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.35 | 18.31 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.31 | 30.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.61 | 15.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.80 | 3.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 111.92 | 34.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 133.91 | 41.07 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 128.20 | 34.37 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 99.93 | 28.54 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 74.77 | 19.56 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 65.22 | 9.83 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 65.99 | 4.58 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 74.43 | 6.67 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 80.31 | 4.79 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 102.87 | 7.83 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 126.58 | 12.50 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.50 | 21.81 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.00 | 36.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 101.01 | 18.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 65.22 | 4.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 133.91 | 41.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 111.97 | 34.51 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.17 | 28.88 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.49 | 23.96 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.59 | 16.47 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.76 | 8.29 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.43 | 3.94 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.54 | 5.76 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.44 | 4.14 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.23 | 6.71 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.04 | 10.61 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.34 | 18.35 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.34 | 30.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.58 | 15.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.76 | 3.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 111.97 | 34.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 111.97 | 34.51 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.17 | 28.88 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.49 | 23.96 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.59 | 16.47 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.76 | 8.29 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.43 | 3.94 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.54 | 5.76 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.44 | 4.14 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.23 | 6.71 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.04 | 10.61 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.34 | 18.35 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.34 | 30.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.58 | 15.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.76 | 3.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 111.97 | 34.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 133.96 | 40.90 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 128.25 | 34.24 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 99.96 | 28.46 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 74.75 | 19.63 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 65.18 | 9.97 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 65.86 | 4.75 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 74.32 | 6.92 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 80.21 | 4.98 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 102.72 | 8.03 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 126.53 | 12.72 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.50 | 21.85 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.03 | 35.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 100.97 | 18.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 65.18 | 4.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 133.96 | 40.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.12 | 34.14 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.32 | 28.51 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.63 | 23.61 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.68 | 16.20 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.85 | 8.04 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.58 | 3.78 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.64 | 5.57 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.56 | 3.94 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.35 | 6.55 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.10 | 10.37 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.44 | 18.07 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.46 | 30.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.70 | 15.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.85 | 3.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.12 | 34.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.12 | 34.14 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.32 | 28.51 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.63 | 23.61 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.68 | 16.20 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.85 | 8.04 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.58 | 3.78 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.64 | 5.57 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.56 | 3.94 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.35 | 6.55 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.10 | 10.37 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.44 | 18.07 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.46 | 30.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.70 | 15.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.85 | 3.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.12 | 34.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 134.14 | 40.47 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 128.43 | 33.82 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 100.14 | 28.05 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 74.86 | 19.30 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 65.29 | 9.69 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 66.03 | 4.56 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 74.44 | 6.70 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 80.34 | 4.75 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 102.86 | 7.84 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 126.60 | 12.44 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.61 | 21.53 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.18 | 35.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 101.11 | 18.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 65.29 | 4.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 134.14 | 40.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.57 | 33.21 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.75 | 27.57 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 84.05 | 22.71 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.77 | 15.46 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.70 | 7.37 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.65 | 3.40 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.49 | 5.12 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.54 | 3.46 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.39 | 6.16 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.04 | 9.77 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.60 | 17.34 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.85 | 29.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.83 | 15.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.70 | 3.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.57 | 33.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.57 | 33.21 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.75 | 27.57 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 84.05 | 22.71 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.77 | 15.46 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.70 | 7.37 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.65 | 3.40 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.49 | 5.12 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.54 | 3.46 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.39 | 6.16 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.04 | 9.77 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.60 | 17.34 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.85 | 29.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.83 | 15.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.70 | 3.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.57 | 33.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.57 | 33.21 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.75 | 27.57 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 84.05 | 22.71 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.77 | 15.46 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.70 | 7.37 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.65 | 3.40 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.49 | 5.12 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.54 | 3.46 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.39 | 6.16 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.04 | 9.77 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.60 | 17.34 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.85 | 29.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.83 | 15.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.70 | 3.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.57 | 33.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.57 | 33.21 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.75 | 27.57 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 84.05 | 22.71 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.77 | 15.46 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.70 | 7.37 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.65 | 3.40 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.49 | 5.12 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.54 | 3.46 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.39 | 6.16 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.04 | 9.77 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.60 | 17.34 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.85 | 29.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.83 | 15.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.70 | 3.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.57 | 33.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 134.64 | 39.38 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 128.90 | 32.71 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 100.60 | 26.99 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 74.96 | 18.44 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 65.12 | 8.89 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 66.11 | 4.09 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 74.26 | 6.15 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 80.31 | 4.16 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 102.90 | 7.36 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 126.52 | 11.72 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.77 | 20.66 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.60 | 34.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 101.25 | 17.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 65.12 | 4.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 134.64 | 39.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 134.64 | 39.38 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 128.90 | 32.71 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 100.60 | 26.99 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 74.96 | 18.44 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 65.12 | 8.89 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 66.11 | 4.09 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 74.26 | 6.15 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 80.31 | 4.16 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 102.90 | 7.36 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 126.52 | 11.72 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.77 | 20.66 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.60 | 34.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 101.25 | 17.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 65.12 | 4.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 134.64 | 39.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.42 | 33.03 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.60 | 27.36 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.96 | 22.46 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.83 | 15.17 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.94 | 7.04 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 56.09 | 3.20 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.87 | 4.84 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.92 | 3.20 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.72 | 5.92 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.11 | 9.41 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.54 | 17.05 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.69 | 28.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.94 | 14.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.94 | 3.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.42 | 33.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.42 | 33.03 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.60 | 27.36 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.96 | 22.46 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.83 | 15.17 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.94 | 7.04 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 56.09 | 3.20 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.87 | 4.84 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.92 | 3.20 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.72 | 5.92 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.11 | 9.41 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.54 | 17.05 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.69 | 28.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.94 | 14.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.94 | 3.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.42 | 33.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 134.51 | 39.16 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 128.78 | 32.46 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 100.53 | 26.70 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 75.05 | 18.10 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 65.40 | 8.51 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 66.63 | 3.85 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 74.71 | 5.83 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 80.76 | 3.86 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 103.29 | 7.09 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 126.62 | 11.30 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.74 | 20.32 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.46 | 34.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 101.40 | 17.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 65.40 | 3.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 134.51 | 39.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.50 | 32.89 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.68 | 27.23 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 84.03 | 22.34 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.87 | 15.09 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.99 | 6.98 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 56.15 | 3.16 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.92 | 4.80 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.97 | 3.17 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.76 | 5.89 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.15 | 9.35 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.58 | 16.97 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.76 | 28.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 85.00 | 14.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.99 | 3.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.50 | 32.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.50 | 32.89 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.68 | 27.23 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 84.03 | 22.34 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.87 | 15.09 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.99 | 6.98 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 56.15 | 3.16 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.92 | 4.80 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.97 | 3.17 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.76 | 5.89 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.15 | 9.35 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.58 | 16.97 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.76 | 28.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 85.00 | 14.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.99 | 3.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.50 | 32.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 134.60 | 38.99 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 128.87 | 32.30 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 100.62 | 26.56 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 75.10 | 18.00 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 65.46 | 8.44 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 66.69 | 3.81 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 74.77 | 5.78 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 80.82 | 3.81 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 103.34 | 7.05 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 126.67 | 11.23 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.80 | 20.22 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.54 | 34.14 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 101.47 | 17.46 | 0.83 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 65.46 | 3.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 134.60 | 38.99 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.68 | 32.52 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.84 | 26.89 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 84.13 | 22.07 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.88 | 14.98 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.94 | 6.97 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 56.02 | 3.19 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.78 | 4.89 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.84 | 3.21 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.61 | 5.96 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.09 | 9.38 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.62 | 16.86 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.91 | 28.47 | 2.17 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 85.00 | 14.56 | 2.17 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.94 | 3.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.68 | 32.52 | 2.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.68 | 32.52 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.84 | 26.89 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 84.13 | 22.07 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.88 | 14.98 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.94 | 6.97 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 56.02 | 3.19 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.78 | 4.89 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.84 | 3.21 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.61 | 5.96 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.09 | 9.38 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.62 | 16.86 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.91 | 28.47 | 2.17 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 85.00 | 14.56 | 2.17 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.94 | 3.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.68 | 32.52 | 2.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 134.82 | 38.56 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 129.06 | 31.91 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 100.74 | 26.24 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 75.10 | 17.87 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 65.40 | 8.42 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 66.54 | 3.85 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 74.60 | 5.89 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 80.66 | 3.87 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 103.16 | 7.13 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 126.59 | 11.26 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.84 | 20.09 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.72 | 33.74 | 2.17 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 101.46 | 17.34 | 2.17 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 65.40 | 3.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 134.82 | 38.56 | 2.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.71 | 31.27 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.74 | 25.72 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.73 | 21.11 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.14 | 14.65 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 53.87 | 7.20 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 54.41 | 3.52 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 61.15 | 5.55 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 66.33 | 3.75 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 84.92 | 6.50 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.10 | 9.91 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.13 | 16.70 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.94 | 27.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.15 | 14.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 53.87 | 3.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.71 | 31.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.71 | 31.27 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.74 | 25.72 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.73 | 21.11 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.14 | 14.65 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 53.87 | 7.20 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 54.41 | 3.52 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 61.15 | 5.55 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 66.33 | 3.75 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 84.92 | 6.50 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.10 | 9.91 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.13 | 16.70 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.94 | 27.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.15 | 14.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 53.87 | 3.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.71 | 31.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 134.86 | 37.09 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 128.94 | 30.54 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 100.26 | 25.11 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 74.22 | 17.49 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 64.12 | 8.70 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 64.63 | 4.25 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 72.66 | 6.68 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 78.87 | 4.53 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 101.15 | 7.78 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 125.41 | 11.89 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.26 | 19.92 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.76 | 32.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 100.45 | 17.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 64.12 | 4.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 134.86 | 37.09 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301154E+09 | 88864181.91 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260203E+09 | 66443475.05 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224639E+09 | 60575359.85 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162549E+09 | 38809406.57 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146532E+09 | 18021218.31 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.146023E+09 | 7694081.42 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.169054E+09 | 11613352.98 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181861E+09 | 8084230.85 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.226087E+09 | 14403640.86 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284249E+09 | 23480831.34 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281184E+09 | 43563105.90 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296504E+09 | 77355681.92 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.268004E+10 | 0.458909E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.146023E+09 | 7694081.42 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301154E+09 | 88864181.91 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301154E+09 | 88864181.91 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260203E+09 | 66443475.05 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224639E+09 | 60575359.85 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162549E+09 | 38809406.57 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146532E+09 | 18021218.31 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.146023E+09 | 7694081.42 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.169054E+09 | 11613352.98 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181861E+09 | 8084230.85 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.226087E+09 | 14403640.86 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284249E+09 | 23480831.34 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281184E+09 | 43563105.90 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296504E+09 | 77355681.92 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.268004E+10 | 0.458909E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.146023E+09 | 7694081.42 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301154E+09 | 88864181.91 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301154E+09 | 88864181.91 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260203E+09 | 66443475.05 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224639E+09 | 60575359.85 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162549E+09 | 38809406.57 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146532E+09 | 18021218.31 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.146023E+09 | 7694081.42 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.169054E+09 | 11613352.98 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181861E+09 | 8084230.85 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.226087E+09 | 14403640.86 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284249E+09 | 23480831.34 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281184E+09 | 43563105.90 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296504E+09 | 77355681.92 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.268004E+10 | 0.458909E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.146023E+09 | 7694081.42 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301154E+09 | 88864181.91 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301154E+09 | 88864181.91 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260203E+09 | 66443475.05 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224639E+09 | 60575359.85 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162549E+09 | 38809406.57 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146532E+09 | 18021218.31 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.146023E+09 | 7694081.42 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.169054E+09 | 11613352.98 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181861E+09 | 8084230.85 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.226087E+09 | 14403640.86 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284249E+09 | 23480831.34 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281184E+09 | 43563105.90 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296504E+09 | 77355681.92 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.268004E+10 | 0.458909E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.146023E+09 | 7694081.42 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301154E+09 | 88864181.91 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217893E+09 | 0.141560E+09 | 76332922.34 | 0.362171E+09 | 0.106010E+09 |
February | 0.178041E+09 | 0.103018E+09 | 75022280.27 | 0.312985E+09 | 79319846.02 |
March | 0.151341E+09 | 63985630.17 | 87355061.31 | 0.270321E+09 | 72455790.57 |
April | 99589279.77 | 17464117.24 | 82125162.53 | 0.195141E+09 | 46603334.37 |
May | 82464880.31 | 1784107.94 | 80680772.37 | 0.175307E+09 | 21941823.23 |
June | 76086867.95 | 143588.68 | 75943279.27 | 0.174269E+09 | 9335210.44 |
July | 84184000.02 | 780312.19 | 83403687.84 | 0.201833E+09 | 14071237.36 |
August | 95546157.45 | 8062706.75 | 87483450.71 | 0.217276E+09 | 9790301.57 |
September | 0.118366E+09 | 29005905.56 | 89360332.65 | 0.270584E+09 | 17352241.13 |
October | 0.168203E+09 | 78915766.21 | 89287404.19 | 0.340896E+09 | 28410631.27 |
November | 0.185205E+09 | 0.103365E+09 | 81839996.85 | 0.337824E+09 | 52262525.06 |
December | 0.209988E+09 | 0.132449E+09 | 77539527.74 | 0.356615E+09 | 92254370.29 |
Annual Sum or Average | 0.166691E+10 | 0.680534E+09 | 0.986374E+09 | 0.321522E+10 | 0.549808E+09 |
Minimum of Months | 76086867.95 | 143588.68 | 75022280.27 | 0.174269E+09 | 9335210.44 |
Maximum of Months | 0.217893E+09 | 0.141560E+09 | 89360332.65 | 0.362171E+09 | 0.106010E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217893E+09 | 0.141560E+09 | 76332922.34 | 0.362171E+09 | 0.106010E+09 |
February | 0.178041E+09 | 0.103018E+09 | 75022280.27 | 0.312985E+09 | 79319846.02 |
March | 0.151341E+09 | 63985630.17 | 87355061.31 | 0.270321E+09 | 72455790.57 |
April | 99589279.77 | 17464117.24 | 82125162.53 | 0.195141E+09 | 46603334.37 |
May | 82464880.31 | 1784107.94 | 80680772.37 | 0.175307E+09 | 21941823.23 |
June | 76086867.95 | 143588.68 | 75943279.27 | 0.174269E+09 | 9335210.44 |
July | 84184000.02 | 780312.19 | 83403687.84 | 0.201833E+09 | 14071237.36 |
August | 95546157.45 | 8062706.75 | 87483450.71 | 0.217276E+09 | 9790301.57 |
September | 0.118366E+09 | 29005905.56 | 89360332.65 | 0.270584E+09 | 17352241.13 |
October | 0.168203E+09 | 78915766.21 | 89287404.19 | 0.340896E+09 | 28410631.27 |
November | 0.185205E+09 | 0.103365E+09 | 81839996.85 | 0.337824E+09 | 52262525.06 |
December | 0.209988E+09 | 0.132449E+09 | 77539527.74 | 0.356615E+09 | 92254370.29 |
Annual Sum or Average | 0.166691E+10 | 0.680534E+09 | 0.986374E+09 | 0.321522E+10 | 0.549808E+09 |
Minimum of Months | 76086867.95 | 143588.68 | 75022280.27 | 0.174269E+09 | 9335210.44 |
Maximum of Months | 0.217893E+09 | 0.141560E+09 | 89360332.65 | 0.362171E+09 | 0.106010E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.299692E+09 | 90724264.04 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.259117E+09 | 67910960.17 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.223793E+09 | 61683373.45 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162944E+09 | 38869646.87 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.147979E+09 | 17641116.20 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.148095E+09 | 7574623.27 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.171445E+09 | 11202081.15 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.184222E+09 | 7675840.54 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.228124E+09 | 14097817.22 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.285243E+09 | 22927274.23 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281085E+09 | 43760985.51 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.295454E+09 | 78866801.35 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.268719E+10 | 0.462935E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.147979E+09 | 7574623.27 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.299692E+09 | 90724264.04 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.299692E+09 | 90724264.04 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.259117E+09 | 67910960.17 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.223793E+09 | 61683373.45 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162944E+09 | 38869646.87 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.147979E+09 | 17641116.20 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.148095E+09 | 7574623.27 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.171445E+09 | 11202081.15 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.184222E+09 | 7675840.54 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.228124E+09 | 14097817.22 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.285243E+09 | 22927274.23 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281085E+09 | 43760985.51 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.295454E+09 | 78866801.35 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.268719E+10 | 0.462935E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.147979E+09 | 7574623.27 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.299692E+09 | 90724264.04 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217893E+09 | 0.141560E+09 | 76332922.34 | 0.360541E+09 | 0.108202E+09 |
February | 0.178041E+09 | 0.103018E+09 | 75022280.27 | 0.311799E+09 | 81036051.34 |
March | 0.151341E+09 | 63985630.17 | 87355061.31 | 0.269419E+09 | 73753915.95 |
April | 99589279.77 | 17464117.24 | 82125162.53 | 0.195662E+09 | 46672053.19 |
May | 82464880.31 | 1784107.94 | 80680772.37 | 0.177022E+09 | 21480966.78 |
June | 76086867.95 | 143588.68 | 75943279.27 | 0.176727E+09 | 9200286.86 |
July | 84184000.02 | 780312.19 | 83403687.84 | 0.204681E+09 | 13586331.07 |
August | 95546157.45 | 8062706.75 | 87483450.71 | 0.220087E+09 | 9297057.24 |
September | 0.118366E+09 | 29005905.56 | 89360332.65 | 0.273046E+09 | 16983428.32 |
October | 0.168203E+09 | 78915766.21 | 89287404.19 | 0.342144E+09 | 27752274.28 |
November | 0.185205E+09 | 0.103365E+09 | 81839996.85 | 0.337797E+09 | 52489139.80 |
December | 0.209988E+09 | 0.132449E+09 | 77539527.74 | 0.355485E+09 | 94022688.05 |
Annual Sum or Average | 0.166691E+10 | 0.680534E+09 | 0.986374E+09 | 0.322441E+10 | 0.554477E+09 |
Minimum of Months | 76086867.95 | 143588.68 | 75022280.27 | 0.176727E+09 | 9200286.86 |
Maximum of Months | 0.217893E+09 | 0.141560E+09 | 89360332.65 | 0.360541E+09 | 0.108202E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.299764E+09 | 92797135.34 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.259161E+09 | 70130601.74 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.223546E+09 | 64352575.73 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162264E+09 | 42540680.83 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146770E+09 | 21859816.18 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.143971E+09 | 9854675.41 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167758E+09 | 14857582.79 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.180870E+09 | 10655722.09 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.223843E+09 | 16953727.65 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284125E+09 | 27925385.92 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280831E+09 | 47463389.01 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.295459E+09 | 81577497.71 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.266836E+10 | 0.500969E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.143971E+09 | 9854675.41 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.299764E+09 | 92797135.34 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.299764E+09 | 92797135.34 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.259161E+09 | 70130601.74 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.223546E+09 | 64352575.73 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162264E+09 | 42540680.83 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146770E+09 | 21859816.18 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.143971E+09 | 9854675.41 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167758E+09 | 14857582.79 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.180870E+09 | 10655722.09 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.223843E+09 | 16953727.65 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284125E+09 | 27925385.92 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280831E+09 | 47463389.01 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.295459E+09 | 81577497.71 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.266836E+10 | 0.500969E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.143971E+09 | 9854675.41 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.299764E+09 | 92797135.34 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.358654E+09 | 0.110000E+09 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.310144E+09 | 83157456.16 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.267659E+09 | 76443257.55 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.193805E+09 | 50689484.81 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.174698E+09 | 26317821.10 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.171044E+09 | 11877447.42 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.199356E+09 | 17864222.23 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.215096E+09 | 12832715.91 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.266636E+09 | 20284707.05 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.339028E+09 | 33488672.45 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.335672E+09 | 56526143.09 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.353545E+09 | 96644048.49 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.318534E+10 | 0.596126E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.171044E+09 | 11877447.42 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.358654E+09 | 0.110000E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.299891E+09 | 92421941.11 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.259263E+09 | 69856969.99 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.223612E+09 | 64176741.96 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162228E+09 | 42693190.18 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146675E+09 | 22196129.71 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.143686E+09 | 10217388.63 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167513E+09 | 15425435.70 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.180639E+09 | 11079182.35 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.223508E+09 | 17395137.40 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284009E+09 | 28411271.28 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280817E+09 | 47557035.21 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.295530E+09 | 81335993.63 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.266737E+10 | 0.502766E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.143686E+09 | 10217388.63 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.299891E+09 | 92421941.11 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.299891E+09 | 92421941.11 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.259263E+09 | 69856969.99 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.223612E+09 | 64176741.96 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162228E+09 | 42693190.18 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146675E+09 | 22196129.71 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.143686E+09 | 10217388.63 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167513E+09 | 15425435.70 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.180639E+09 | 11079182.35 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.223508E+09 | 17395137.40 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284009E+09 | 28411271.28 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280817E+09 | 47557035.21 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.295530E+09 | 81335993.63 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.266737E+10 | 0.502766E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.143686E+09 | 10217388.63 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.299891E+09 | 92421941.11 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.358807E+09 | 0.109556E+09 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.310265E+09 | 82835498.53 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.267737E+09 | 76236355.35 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.193763E+09 | 50869275.53 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.174585E+09 | 26713809.18 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.170711E+09 | 12312797.01 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.199068E+09 | 18539949.51 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.214829E+09 | 13342605.40 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.266243E+09 | 20812069.69 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.338888E+09 | 34062897.76 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.335656E+09 | 56636756.33 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.353629E+09 | 96359311.77 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.318418E+10 | 0.598278E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.170711E+09 | 12312797.01 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.358807E+09 | 0.109556E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.300293E+09 | 91433300.55 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.259623E+09 | 68977396.82 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224005E+09 | 63224021.80 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162466E+09 | 41977961.32 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146922E+09 | 21537464.35 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.144059E+09 | 9798886.92 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167774E+09 | 14929469.78 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.180943E+09 | 10559778.05 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.223813E+09 | 16978563.66 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284182E+09 | 27778100.86 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281069E+09 | 46840580.55 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.295864E+09 | 80391090.27 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267101E+10 | 0.494427E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.144059E+09 | 9798886.92 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.300293E+09 | 91433300.55 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.300293E+09 | 91433300.55 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.259623E+09 | 68977396.82 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224005E+09 | 63224021.80 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162466E+09 | 41977961.32 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146922E+09 | 21537464.35 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.144059E+09 | 9798886.92 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167774E+09 | 14929469.78 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.180943E+09 | 10559778.05 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.223813E+09 | 16978563.66 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284182E+09 | 27778100.86 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281069E+09 | 46840580.55 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.295864E+09 | 80391090.27 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267101E+10 | 0.494427E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.144059E+09 | 9798886.92 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.300293E+09 | 91433300.55 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.359289E+09 | 0.108394E+09 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.310697E+09 | 81805715.58 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.268208E+09 | 75122354.22 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.194049E+09 | 50033158.65 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.174879E+09 | 25945411.85 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.171145E+09 | 11814948.37 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.199375E+09 | 17954775.37 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.215182E+09 | 12724092.35 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.266601E+09 | 20321316.96 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.339096E+09 | 33321672.35 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.335959E+09 | 55797202.16 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.354032E+09 | 95250657.52 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.318851E+10 | 0.588486E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.171145E+09 | 11814948.37 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.359289E+09 | 0.108394E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301504E+09 | 88943753.93 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260664E+09 | 66692450.20 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.225122E+09 | 60825605.77 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162699E+09 | 40084350.08 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146521E+09 | 19752200.91 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.144245E+09 | 8815534.96 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167366E+09 | 13706716.61 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.180886E+09 | 9273891.87 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.223932E+09 | 15954595.42 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284023E+09 | 26178000.94 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281479E+09 | 44941021.16 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296890E+09 | 78070012.17 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267533E+10 | 0.473238E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.144245E+09 | 8815534.96 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301504E+09 | 88943753.93 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301504E+09 | 88943753.93 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260664E+09 | 66692450.20 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.225122E+09 | 60825605.77 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162699E+09 | 40084350.08 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146521E+09 | 19752200.91 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.144245E+09 | 8815534.96 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167366E+09 | 13706716.61 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.180886E+09 | 9273891.87 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.223932E+09 | 15954595.42 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284023E+09 | 26178000.94 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281479E+09 | 44941021.16 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296890E+09 | 78070012.17 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267533E+10 | 0.473238E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.144245E+09 | 8815534.96 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301504E+09 | 88943753.93 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301504E+09 | 88943753.93 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260664E+09 | 66692450.20 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.225122E+09 | 60825605.77 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162699E+09 | 40084350.08 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146521E+09 | 19752200.91 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.144245E+09 | 8815534.96 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167366E+09 | 13706716.61 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.180886E+09 | 9273891.87 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.223932E+09 | 15954595.42 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284023E+09 | 26178000.94 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281479E+09 | 44941021.16 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296890E+09 | 78070012.17 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267533E+10 | 0.473238E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.144245E+09 | 8815534.96 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301504E+09 | 88943753.93 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301504E+09 | 88943753.93 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260664E+09 | 66692450.20 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.225122E+09 | 60825605.77 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162699E+09 | 40084350.08 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146521E+09 | 19752200.91 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.144245E+09 | 8815534.96 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167366E+09 | 13706716.61 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.180886E+09 | 9273891.87 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.223932E+09 | 15954595.42 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284023E+09 | 26178000.94 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281479E+09 | 44941021.16 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296890E+09 | 78070012.17 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267533E+10 | 0.473238E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.144245E+09 | 8815534.96 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301504E+09 | 88943753.93 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.360627E+09 | 0.105468E+09 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.311841E+09 | 79127697.85 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.269444E+09 | 72300308.26 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.194293E+09 | 47786278.24 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.174413E+09 | 23814292.70 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.171366E+09 | 10608769.48 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.198904E+09 | 16469424.14 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.215103E+09 | 11149704.66 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.266715E+09 | 19079342.44 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.338858E+09 | 31391748.83 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.336371E+09 | 53543787.27 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.355147E+09 | 92527402.10 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.319308E+10 | 0.563267E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.171366E+09 | 10608769.48 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.360627E+09 | 0.105468E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.360627E+09 | 0.105468E+09 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.311841E+09 | 79127697.85 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.269444E+09 | 72300308.26 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.194293E+09 | 47786278.24 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.174413E+09 | 23814292.70 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.171366E+09 | 10608769.48 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.198904E+09 | 16469424.14 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.215103E+09 | 11149704.66 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.266715E+09 | 19079342.44 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.338858E+09 | 31391748.83 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.336371E+09 | 53543787.27 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.355147E+09 | 92527402.10 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.319308E+10 | 0.563267E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.171366E+09 | 10608769.48 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.360627E+09 | 0.105468E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301094E+09 | 88468148.32 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260315E+09 | 66189657.70 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224876E+09 | 60150236.20 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162851E+09 | 39324137.20 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.147159E+09 | 18860267.83 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.145389E+09 | 8283985.57 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.168397E+09 | 12966685.67 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181915E+09 | 8583929.83 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.224766E+09 | 15357000.58 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284213E+09 | 25198274.49 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281325E+09 | 44184977.23 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296470E+09 | 77546690.65 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267877E+10 | 0.465114E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.145389E+09 | 8283985.57 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301094E+09 | 88468148.32 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301094E+09 | 88468148.32 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260315E+09 | 66189657.70 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224876E+09 | 60150236.20 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162851E+09 | 39324137.20 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.147159E+09 | 18860267.83 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.145389E+09 | 8283985.57 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.168397E+09 | 12966685.67 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181915E+09 | 8583929.83 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.224766E+09 | 15357000.58 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284213E+09 | 25198274.49 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281325E+09 | 44184977.23 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296470E+09 | 77546690.65 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267877E+10 | 0.465114E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.145389E+09 | 8283985.57 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301094E+09 | 88468148.32 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.360263E+09 | 0.104890E+09 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.311540E+09 | 78525435.31 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.269263E+09 | 71505509.44 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.194525E+09 | 46903797.59 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.175171E+09 | 22783691.81 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.172696E+09 | 9987095.07 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.200111E+09 | 15608487.50 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.216306E+09 | 10333901.69 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.267720E+09 | 18370663.09 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.339151E+09 | 30256327.93 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.336287E+09 | 52660851.02 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.354775E+09 | 91889240.81 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.319781E+10 | 0.553715E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.172696E+09 | 9987095.07 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.360263E+09 | 0.104890E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301312E+09 | 88091047.19 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260505E+09 | 65866236.15 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.225066E+09 | 59837038.74 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162966E+09 | 39121821.30 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.147283E+09 | 18701959.14 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.145538E+09 | 8201284.44 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.168516E+09 | 12867422.21 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.182049E+09 | 8479871.02 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.224893E+09 | 15272877.08 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284310E+09 | 25037392.64 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281452E+09 | 43976233.65 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296661E+09 | 77174897.70 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.268055E+10 | 0.462628E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.145538E+09 | 8201284.44 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301312E+09 | 88091047.19 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301312E+09 | 88091047.19 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260505E+09 | 65866236.15 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.225066E+09 | 59837038.74 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162966E+09 | 39121821.30 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.147283E+09 | 18701959.14 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.145538E+09 | 8201284.44 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.168516E+09 | 12867422.21 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.182049E+09 | 8479871.02 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.224893E+09 | 15272877.08 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284310E+09 | 25037392.64 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281452E+09 | 43976233.65 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296661E+09 | 77174897.70 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.268055E+10 | 0.462628E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.145538E+09 | 8201284.44 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301312E+09 | 88091047.19 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.360523E+09 | 0.104444E+09 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.311767E+09 | 78144226.71 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.269489E+09 | 71136557.61 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.194663E+09 | 46664524.44 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.175318E+09 | 22596151.32 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.172871E+09 | 9887848.35 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.200253E+09 | 15490006.03 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.216464E+09 | 10208806.06 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.267870E+09 | 18269713.42 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.339268E+09 | 30065560.04 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.336440E+09 | 52413586.79 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.355004E+09 | 91449843.37 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.319993E+10 | 0.550771E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.172871E+09 | 9887848.35 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.360523E+09 | 0.104444E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301794E+09 | 87107426.03 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260879E+09 | 65048928.52 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.225335E+09 | 59108967.44 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162973E+09 | 38820373.67 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.147162E+09 | 18655686.00 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.145204E+09 | 8279915.80 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.168156E+09 | 13097375.79 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181696E+09 | 8610906.50 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.224494E+09 | 15438000.49 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284146E+09 | 25113254.49 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281537E+09 | 43688594.51 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.297053E+09 | 76253332.52 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.268043E+10 | 0.459223E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.145204E+09 | 8279915.80 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301794E+09 | 87107426.03 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301794E+09 | 87107426.03 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260879E+09 | 65048928.52 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.225335E+09 | 59108967.44 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162973E+09 | 38820373.67 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.147162E+09 | 18655686.00 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.145204E+09 | 8279915.80 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.168156E+09 | 13097375.79 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181696E+09 | 8610906.50 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.224494E+09 | 15438000.49 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284146E+09 | 25113254.49 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281537E+09 | 43688594.51 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.297053E+09 | 76253332.52 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.268043E+10 | 0.459223E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.145204E+09 | 8279915.80 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301794E+09 | 87107426.03 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.361096E+09 | 0.103288E+09 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.312214E+09 | 77189966.18 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.269809E+09 | 70286236.11 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.194671E+09 | 46317154.20 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.175173E+09 | 22550421.90 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.172472E+09 | 9988020.92 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.199822E+09 | 15770005.74 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.216045E+09 | 10374181.39 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.267396E+09 | 18474140.21 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.339071E+09 | 30163366.40 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.336540E+09 | 52080706.49 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.355471E+09 | 90369479.80 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.319978E+10 | 0.546851E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.172472E+09 | 9988020.92 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.361096E+09 | 0.103288E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301891E+09 | 83754206.26 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260652E+09 | 62225662.16 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224274E+09 | 56533702.87 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.161059E+09 | 37977771.50 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.144286E+09 | 19281585.45 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.141042E+09 | 9126130.73 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.163793E+09 | 14872126.82 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.177648E+09 | 10056905.26 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.220107E+09 | 16847619.49 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.281511E+09 | 26533947.41 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280286E+09 | 43289254.91 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.297148E+09 | 73328856.34 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.265370E+10 | 0.453828E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.141042E+09 | 9126130.73 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301891E+09 | 83754206.26 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301891E+09 | 83754206.26 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260652E+09 | 62225662.16 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224274E+09 | 56533702.87 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.161059E+09 | 37977771.50 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.144286E+09 | 19281585.45 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.141042E+09 | 9126130.73 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.163793E+09 | 14872126.82 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.177648E+09 | 10056905.26 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.220107E+09 | 16847619.49 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.281511E+09 | 26533947.41 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280286E+09 | 43289254.91 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.297148E+09 | 73328856.34 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.265370E+10 | 0.453828E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.141042E+09 | 9126130.73 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301891E+09 | 83754206.26 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.361199E+09 | 99338442.12 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.311927E+09 | 73881915.02 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.268528E+09 | 67267164.07 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.192369E+09 | 45333166.80 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.171737E+09 | 23301914.82 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.167517E+09 | 11008103.06 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.194607E+09 | 17883872.48 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.211238E+09 | 12126884.30 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.262175E+09 | 20177333.08 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.335905E+09 | 31854988.12 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.335029E+09 | 51625652.27 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.355572E+09 | 86927511.70 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.316780E+10 | 0.540727E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.167517E+09 | 11008103.06 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.361199E+09 | 99338442.12 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 720.19 | 211.87 | 433.39 | 281.56 | 151.83 | 0.00 | 0.00 |
February | 688.98 | 175.44 | 392.07 | 226.86 | 165.21 | 0.00 | 0.00 |
March | 537.33 | 144.57 | 301.02 | 127.27 | 173.75 | 0.00 | 0.00 |
April | 401.42 | 95.85 | 204.69 | 35.89 | 168.79 | 0.00 | 0.00 |
May | 349.74 | 43.30 | 164.02 | 3.55 | 160.47 | 0.00 | 0.00 |
June | 359.81 | 19.08 | 156.38 | 0.30 | 156.09 | 0.00 | 0.00 |
July | 403.18 | 27.85 | 167.44 | 1.55 | 165.89 | 0.00 | 0.00 |
August | 433.84 | 19.38 | 190.04 | 16.04 | 174.01 | 0.00 | 0.00 |
September | 557.68 | 35.62 | 243.28 | 59.62 | 183.66 | 0.00 | 0.00 |
October | 679.05 | 56.28 | 334.56 | 156.96 | 177.59 | 0.00 | 0.00 |
November | 694.59 | 107.55 | 380.65 | 212.45 | 168.21 | 0.00 | 0.00 |
December | 709.10 | 184.41 | 417.67 | 263.44 | 154.23 | 0.00 | 0.00 |
Annual Sum or Average | 543.84 | 93.08 | 281.59 | 114.96 | 166.63 | 0.00 | 0.00 |
Minimum of Months | 349.74 | 19.08 | 156.38 | 0.30 | 151.83 | 0.00 | 0.00 |
Maximum of Months | 720.19 | 211.87 | 433.39 | 281.56 | 183.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 358.40 | 108.14 | 216.70 | 140.78 | 75.91 | 0.00 | 0.00 |
February | 343.10 | 89.64 | 196.03 | 113.43 | 82.60 | 0.00 | 0.00 |
March | 267.70 | 73.60 | 150.51 | 63.63 | 86.87 | 0.00 | 0.00 |
April | 201.21 | 48.00 | 102.34 | 17.95 | 84.40 | 0.00 | 0.00 |
May | 176.59 | 21.19 | 82.01 | 1.77 | 80.24 | 0.00 | 0.00 |
June | 182.45 | 9.39 | 78.19 | 0.15 | 78.04 | 0.00 | 0.00 |
July | 204.44 | 13.44 | 83.72 | 0.78 | 82.95 | 0.00 | 0.00 |
August | 219.73 | 9.20 | 95.02 | 8.02 | 87.00 | 0.00 | 0.00 |
September | 281.36 | 17.43 | 121.64 | 29.81 | 91.83 | 0.00 | 0.00 |
October | 340.74 | 27.48 | 167.28 | 78.48 | 88.80 | 0.00 | 0.00 |
November | 347.21 | 54.02 | 190.33 | 106.22 | 84.10 | 0.00 | 0.00 |
December | 353.34 | 93.99 | 208.83 | 131.72 | 77.11 | 0.00 | 0.00 |
Annual Sum or Average | 272.67 | 46.94 | 140.79 | 57.48 | 83.31 | 0.00 | 0.00 |
Minimum of Months | 176.59 | 9.20 | 78.19 | 0.15 | 75.91 | 0.00 | 0.00 |
Maximum of Months | 358.40 | 108.14 | 216.70 | 140.78 | 91.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 357.74 | 110.36 | 216.25 | 140.49 | 75.76 | 0.00 | 0.00 |
February | 342.45 | 92.35 | 195.63 | 113.20 | 82.43 | 0.00 | 0.00 |
March | 266.86 | 76.59 | 150.20 | 63.50 | 86.70 | 0.00 | 0.00 |
April | 199.97 | 52.38 | 102.13 | 17.91 | 84.22 | 0.00 | 0.00 |
May | 174.82 | 26.15 | 81.84 | 1.77 | 80.07 | 0.00 | 0.00 |
June | 177.08 | 12.19 | 78.03 | 0.15 | 77.88 | 0.00 | 0.00 |
July | 199.70 | 17.76 | 83.55 | 0.77 | 82.78 | 0.00 | 0.00 |
August | 215.37 | 12.75 | 94.83 | 8.00 | 86.82 | 0.00 | 0.00 |
September | 275.59 | 20.91 | 121.39 | 29.75 | 91.64 | 0.00 | 0.00 |
October | 338.74 | 33.36 | 166.94 | 78.32 | 88.61 | 0.00 | 0.00 |
November | 346.19 | 58.43 | 189.94 | 106.01 | 83.93 | 0.00 | 0.00 |
December | 352.62 | 97.00 | 208.41 | 131.45 | 76.96 | 0.00 | 0.00 |
Annual Sum or Average | 270.23 | 50.67 | 140.51 | 57.36 | 83.14 | 0.00 | 0.00 |
Minimum of Months | 174.82 | 12.19 | 78.03 | 0.15 | 75.76 | 0.00 | 0.00 |
Maximum of Months | 357.74 | 110.36 | 216.25 | 140.49 | 91.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 357.90 | 109.92 | 216.25 | 140.49 | 75.76 | 0.00 | 0.00 |
February | 342.59 | 91.99 | 195.63 | 113.20 | 82.43 | 0.00 | 0.00 |
March | 266.94 | 76.38 | 150.20 | 63.50 | 86.70 | 0.00 | 0.00 |
April | 199.93 | 52.57 | 102.13 | 17.91 | 84.22 | 0.00 | 0.00 |
May | 174.71 | 26.55 | 81.84 | 1.77 | 80.07 | 0.00 | 0.00 |
June | 176.73 | 12.63 | 78.03 | 0.15 | 77.88 | 0.00 | 0.00 |
July | 199.41 | 18.44 | 83.55 | 0.77 | 82.78 | 0.00 | 0.00 |
August | 215.09 | 13.25 | 94.83 | 8.00 | 86.82 | 0.00 | 0.00 |
September | 275.18 | 21.45 | 121.39 | 29.75 | 91.64 | 0.00 | 0.00 |
October | 338.60 | 33.93 | 166.94 | 78.32 | 88.61 | 0.00 | 0.00 |
November | 346.18 | 58.55 | 189.94 | 106.01 | 83.93 | 0.00 | 0.00 |
December | 352.71 | 96.71 | 208.41 | 131.45 | 76.96 | 0.00 | 0.00 |
Annual Sum or Average | 270.13 | 50.86 | 140.51 | 57.36 | 83.14 | 0.00 | 0.00 |
Minimum of Months | 174.71 | 12.63 | 78.03 | 0.15 | 75.76 | 0.00 | 0.00 |
Maximum of Months | 357.90 | 109.92 | 216.25 | 140.49 | 91.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 358.38 | 108.74 | 216.25 | 140.49 | 75.76 | 0.00 | 0.00 |
February | 343.06 | 90.84 | 195.63 | 113.20 | 82.43 | 0.00 | 0.00 |
March | 267.41 | 75.26 | 150.20 | 63.50 | 86.70 | 0.00 | 0.00 |
April | 200.22 | 51.69 | 102.13 | 17.91 | 84.22 | 0.00 | 0.00 |
May | 175.00 | 25.77 | 81.84 | 1.77 | 80.07 | 0.00 | 0.00 |
June | 177.18 | 12.12 | 78.03 | 0.15 | 77.88 | 0.00 | 0.00 |
July | 199.72 | 17.85 | 83.55 | 0.77 | 82.78 | 0.00 | 0.00 |
August | 215.45 | 12.63 | 94.83 | 8.00 | 86.82 | 0.00 | 0.00 |
September | 275.55 | 20.94 | 121.39 | 29.75 | 91.64 | 0.00 | 0.00 |
October | 338.81 | 33.18 | 166.94 | 78.32 | 88.61 | 0.00 | 0.00 |
November | 346.49 | 57.67 | 189.94 | 106.01 | 83.93 | 0.00 | 0.00 |
December | 353.11 | 95.59 | 208.41 | 131.45 | 76.96 | 0.00 | 0.00 |
Annual Sum or Average | 270.50 | 50.02 | 140.51 | 57.36 | 83.14 | 0.00 | 0.00 |
Minimum of Months | 175.00 | 12.12 | 78.03 | 0.15 | 75.76 | 0.00 | 0.00 |
Maximum of Months | 358.38 | 108.74 | 216.25 | 140.49 | 91.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 719.56 | 211.59 | 432.50 | 280.99 | 151.52 | 0.00 | 0.00 |
February | 688.80 | 175.69 | 391.26 | 226.39 | 164.87 | 0.00 | 0.00 |
March | 537.40 | 144.83 | 300.40 | 127.01 | 173.39 | 0.00 | 0.00 |
April | 401.00 | 98.73 | 204.27 | 35.82 | 168.45 | 0.00 | 0.00 |
May | 349.05 | 47.28 | 163.69 | 3.54 | 160.15 | 0.00 | 0.00 |
June | 354.83 | 21.79 | 156.06 | 0.29 | 155.77 | 0.00 | 0.00 |
July | 398.47 | 32.77 | 167.10 | 1.55 | 165.55 | 0.00 | 0.00 |
August | 430.76 | 22.17 | 189.65 | 16.00 | 173.65 | 0.00 | 0.00 |
September | 551.37 | 39.34 | 242.78 | 59.49 | 183.29 | 0.00 | 0.00 |
October | 677.20 | 62.53 | 333.87 | 156.64 | 177.23 | 0.00 | 0.00 |
November | 693.93 | 110.67 | 379.87 | 212.01 | 167.86 | 0.00 | 0.00 |
December | 708.58 | 185.68 | 416.81 | 262.90 | 153.91 | 0.00 | 0.00 |
Annual Sum or Average | 541.84 | 95.75 | 281.01 | 114.73 | 166.29 | 0.00 | 0.00 |
Minimum of Months | 349.05 | 21.79 | 156.06 | 0.29 | 151.52 | 0.00 | 0.00 |
Maximum of Months | 719.56 | 211.59 | 432.50 | 280.99 | 183.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 359.34 | 105.22 | 216.25 | 140.49 | 75.76 | 0.00 | 0.00 |
February | 343.99 | 87.18 | 195.63 | 113.20 | 82.43 | 0.00 | 0.00 |
March | 268.45 | 71.61 | 150.20 | 63.50 | 86.70 | 0.00 | 0.00 |
April | 200.70 | 48.44 | 102.13 | 17.91 | 84.22 | 0.00 | 0.00 |
May | 175.29 | 22.59 | 81.84 | 1.77 | 80.07 | 0.00 | 0.00 |
June | 178.81 | 10.24 | 78.03 | 0.15 | 77.88 | 0.00 | 0.00 |
July | 200.46 | 15.51 | 83.55 | 0.77 | 82.78 | 0.00 | 0.00 |
August | 216.60 | 10.27 | 94.83 | 8.00 | 86.82 | 0.00 | 0.00 |
September | 276.72 | 18.94 | 121.39 | 29.75 | 91.64 | 0.00 | 0.00 |
October | 338.85 | 30.11 | 166.94 | 78.32 | 88.61 | 0.00 | 0.00 |
November | 346.81 | 54.41 | 189.94 | 106.01 | 83.93 | 0.00 | 0.00 |
December | 353.84 | 92.21 | 208.41 | 131.45 | 76.96 | 0.00 | 0.00 |
Annual Sum or Average | 271.29 | 47.06 | 140.51 | 57.36 | 83.14 | 0.00 | 0.00 |
Minimum of Months | 175.29 | 10.24 | 78.03 | 0.15 | 75.76 | 0.00 | 0.00 |
Maximum of Months | 359.34 | 105.22 | 216.25 | 140.49 | 91.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 359.60 | 104.77 | 216.25 | 140.49 | 75.76 | 0.00 | 0.00 |
February | 344.24 | 86.75 | 195.63 | 113.20 | 82.43 | 0.00 | 0.00 |
March | 268.68 | 71.24 | 150.20 | 63.50 | 86.70 | 0.00 | 0.00 |
April | 200.85 | 48.19 | 102.13 | 17.91 | 84.22 | 0.00 | 0.00 |
May | 175.43 | 22.40 | 81.84 | 1.77 | 80.07 | 0.00 | 0.00 |
June | 178.99 | 10.14 | 78.03 | 0.15 | 77.88 | 0.00 | 0.00 |
July | 200.60 | 15.39 | 83.55 | 0.77 | 82.78 | 0.00 | 0.00 |
August | 216.76 | 10.14 | 94.83 | 8.00 | 86.82 | 0.00 | 0.00 |
September | 276.87 | 18.83 | 121.39 | 29.75 | 91.64 | 0.00 | 0.00 |
October | 338.97 | 29.92 | 166.94 | 78.32 | 88.61 | 0.00 | 0.00 |
November | 346.97 | 54.15 | 189.94 | 106.01 | 83.93 | 0.00 | 0.00 |
December | 354.06 | 91.77 | 208.41 | 131.45 | 76.96 | 0.00 | 0.00 |
Annual Sum or Average | 271.47 | 46.80 | 140.51 | 57.36 | 83.14 | 0.00 | 0.00 |
Minimum of Months | 175.43 | 10.14 | 78.03 | 0.15 | 75.76 | 0.00 | 0.00 |
Maximum of Months | 359.60 | 104.77 | 216.25 | 140.49 | 91.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 360.17 | 103.61 | 216.25 | 140.49 | 75.76 | 0.00 | 0.00 |
February | 344.73 | 85.68 | 195.63 | 113.20 | 82.43 | 0.00 | 0.00 |
March | 269.00 | 70.38 | 150.20 | 63.50 | 86.70 | 0.00 | 0.00 |
April | 200.85 | 47.82 | 102.13 | 17.91 | 84.22 | 0.00 | 0.00 |
May | 175.29 | 22.35 | 81.84 | 1.77 | 80.07 | 0.00 | 0.00 |
June | 178.58 | 10.24 | 78.03 | 0.15 | 77.88 | 0.00 | 0.00 |
July | 200.17 | 15.67 | 83.55 | 0.77 | 82.78 | 0.00 | 0.00 |
August | 216.34 | 10.30 | 94.83 | 8.00 | 86.82 | 0.00 | 0.00 |
September | 276.38 | 19.04 | 121.39 | 29.75 | 91.64 | 0.00 | 0.00 |
October | 338.77 | 30.01 | 166.94 | 78.32 | 88.61 | 0.00 | 0.00 |
November | 347.07 | 53.80 | 189.94 | 106.01 | 83.93 | 0.00 | 0.00 |
December | 354.53 | 90.68 | 208.41 | 131.45 | 76.96 | 0.00 | 0.00 |
Annual Sum or Average | 271.46 | 46.46 | 140.51 | 57.36 | 83.14 | 0.00 | 0.00 |
Minimum of Months | 175.29 | 10.24 | 78.03 | 0.15 | 75.76 | 0.00 | 0.00 |
Maximum of Months | 360.17 | 103.61 | 216.25 | 140.49 | 91.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 360.28 | 99.63 | 216.25 | 140.49 | 75.76 | 0.00 | 0.00 |
February | 344.42 | 81.98 | 195.63 | 113.20 | 82.43 | 0.00 | 0.00 |
March | 267.73 | 67.33 | 150.20 | 63.50 | 86.70 | 0.00 | 0.00 |
April | 198.49 | 46.79 | 102.13 | 17.91 | 84.22 | 0.00 | 0.00 |
May | 171.86 | 23.10 | 81.84 | 1.77 | 80.07 | 0.00 | 0.00 |
June | 173.46 | 11.29 | 78.03 | 0.15 | 77.88 | 0.00 | 0.00 |
July | 194.96 | 17.78 | 83.55 | 0.77 | 82.78 | 0.00 | 0.00 |
August | 211.52 | 12.04 | 94.83 | 8.00 | 86.82 | 0.00 | 0.00 |
September | 270.98 | 20.78 | 121.39 | 29.75 | 91.64 | 0.00 | 0.00 |
October | 335.62 | 31.71 | 166.94 | 78.32 | 88.61 | 0.00 | 0.00 |
November | 345.52 | 53.32 | 189.94 | 106.01 | 83.93 | 0.00 | 0.00 |
December | 354.64 | 87.21 | 208.41 | 131.45 | 76.96 | 0.00 | 0.00 |
Annual Sum or Average | 268.75 | 45.93 | 140.51 | 57.36 | 83.14 | 0.00 | 0.00 |
Minimum of Months | 171.86 | 11.29 | 78.03 | 0.15 | 75.76 | 0.00 | 0.00 |
Maximum of Months | 360.28 | 99.63 | 216.25 | 140.49 | 91.64 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.192896E+10 | 0.567478E+09 | 0.116080E+10 | 0.754143E+09 | 0.406653E+09 | 0.00 | 0.00 |
February | 0.166678E+10 | 0.424413E+09 | 0.948487E+09 | 0.548817E+09 | 0.399671E+09 | 0.00 | 0.00 |
March | 0.143920E+10 | 0.387213E+09 | 0.806246E+09 | 0.340875E+09 | 0.465372E+09 | 0.00 | 0.00 |
April | 0.104048E+10 | 0.248444E+09 | 0.530548E+09 | 93037654.60 | 0.437510E+09 | 0.00 | 0.00 |
May | 0.936740E+09 | 0.115965E+09 | 0.439320E+09 | 9504586.80 | 0.429816E+09 | 0.00 | 0.00 |
June | 0.932628E+09 | 49443826.02 | 0.405342E+09 | 764948.74 | 0.404577E+09 | 0.00 | 0.00 |
July | 0.107988E+10 | 74592883.59 | 0.448479E+09 | 4157004.61 | 0.444322E+09 | 0.00 | 0.00 |
August | 0.116199E+10 | 51911551.43 | 0.509009E+09 | 42952948.32 | 0.466056E+09 | 0.00 | 0.00 |
September | 0.144551E+10 | 92315408.92 | 0.630580E+09 | 0.154525E+09 | 0.476055E+09 | 0.00 | 0.00 |
October | 0.181878E+10 | 0.150739E+09 | 0.896079E+09 | 0.420413E+09 | 0.475666E+09 | 0.00 | 0.00 |
November | 0.180038E+10 | 0.278774E+09 | 0.986652E+09 | 0.550661E+09 | 0.435991E+09 | 0.00 | 0.00 |
December | 0.189925E+10 | 0.493931E+09 | 0.111868E+10 | 0.705602E+09 | 0.413081E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.171506E+11 | 0.293522E+10 | 0.888022E+10 | 0.362545E+10 | 0.525477E+10 | 0.00 | 0.00 |
Minimum of Months | 0.932628E+09 | 49443826.02 | 0.405342E+09 | 764948.74 | 0.399671E+09 | 0.00 | 0.00 |
Maximum of Months | 0.192896E+10 | 0.567478E+09 | 0.116080E+10 | 0.754143E+09 | 0.476055E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.959926E+09 | 0.289651E+09 | 0.580398E+09 | 0.377072E+09 | 0.203327E+09 | 0.00 | 0.00 |
February | 0.830033E+09 | 0.216857E+09 | 0.474244E+09 | 0.274408E+09 | 0.199835E+09 | 0.00 | 0.00 |
March | 0.717004E+09 | 0.197120E+09 | 0.403123E+09 | 0.170437E+09 | 0.232686E+09 | 0.00 | 0.00 |
April | 0.521549E+09 | 0.124411E+09 | 0.265274E+09 | 46518827.30 | 0.218755E+09 | 0.00 | 0.00 |
May | 0.472976E+09 | 56758771.86 | 0.219660E+09 | 4752293.40 | 0.214908E+09 | 0.00 | 0.00 |
June | 0.472915E+09 | 24348077.33 | 0.202671E+09 | 382474.37 | 0.202289E+09 | 0.00 | 0.00 |
July | 0.547570E+09 | 35988994.92 | 0.224239E+09 | 2078502.30 | 0.222161E+09 | 0.00 | 0.00 |
August | 0.588528E+09 | 24645332.11 | 0.254504E+09 | 21476474.16 | 0.233028E+09 | 0.00 | 0.00 |
September | 0.729292E+09 | 45177549.16 | 0.315290E+09 | 77262462.94 | 0.238027E+09 | 0.00 | 0.00 |
October | 0.912628E+09 | 73604026.17 | 0.448039E+09 | 0.210206E+09 | 0.237833E+09 | 0.00 | 0.00 |
November | 0.899965E+09 | 0.140010E+09 | 0.493326E+09 | 0.275330E+09 | 0.217996E+09 | 0.00 | 0.00 |
December | 0.946391E+09 | 0.251756E+09 | 0.559342E+09 | 0.352801E+09 | 0.206541E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.859878E+10 | 0.148033E+10 | 0.444011E+10 | 0.181273E+10 | 0.262738E+10 | 0.00 | 0.00 |
Minimum of Months | 0.472915E+09 | 24348077.33 | 0.202671E+09 | 382474.37 | 0.199835E+09 | 0.00 | 0.00 |
Maximum of Months | 0.959926E+09 | 0.289651E+09 | 0.580398E+09 | 0.377072E+09 | 0.238027E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.958182E+09 | 0.295594E+09 | 0.579208E+09 | 0.376298E+09 | 0.202909E+09 | 0.00 | 0.00 |
February | 0.828467E+09 | 0.223418E+09 | 0.473271E+09 | 0.273845E+09 | 0.199425E+09 | 0.00 | 0.00 |
March | 0.714752E+09 | 0.205148E+09 | 0.402296E+09 | 0.170088E+09 | 0.232209E+09 | 0.00 | 0.00 |
April | 0.518332E+09 | 0.135770E+09 | 0.264730E+09 | 46423394.97 | 0.218306E+09 | 0.00 | 0.00 |
May | 0.468237E+09 | 70036917.68 | 0.219209E+09 | 4742544.18 | 0.214467E+09 | 0.00 | 0.00 |
June | 0.458983E+09 | 31583613.84 | 0.202255E+09 | 381689.73 | 0.201874E+09 | 0.00 | 0.00 |
July | 0.534870E+09 | 47576989.90 | 0.223779E+09 | 2074238.30 | 0.221705E+09 | 0.00 | 0.00 |
August | 0.576834E+09 | 34141669.13 | 0.253982E+09 | 21432415.65 | 0.232550E+09 | 0.00 | 0.00 |
September | 0.714321E+09 | 54191046.20 | 0.314643E+09 | 77103960.73 | 0.237539E+09 | 0.00 | 0.00 |
October | 0.907279E+09 | 89339116.78 | 0.447120E+09 | 0.209775E+09 | 0.237345E+09 | 0.00 | 0.00 |
November | 0.897333E+09 | 0.151453E+09 | 0.492314E+09 | 0.274766E+09 | 0.217548E+09 | 0.00 | 0.00 |
December | 0.944463E+09 | 0.259799E+09 | 0.558194E+09 | 0.352077E+09 | 0.206117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.852205E+10 | 0.159805E+10 | 0.443100E+10 | 0.180901E+10 | 0.262199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.458983E+09 | 31583613.84 | 0.202255E+09 | 381689.73 | 0.199425E+09 | 0.00 | 0.00 |
Maximum of Months | 0.958182E+09 | 0.295594E+09 | 0.579208E+09 | 0.376298E+09 | 0.237539E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.958589E+09 | 0.294400E+09 | 0.579208E+09 | 0.376298E+09 | 0.202909E+09 | 0.00 | 0.00 |
February | 0.828791E+09 | 0.222549E+09 | 0.473271E+09 | 0.273845E+09 | 0.199425E+09 | 0.00 | 0.00 |
March | 0.714960E+09 | 0.204590E+09 | 0.402296E+09 | 0.170088E+09 | 0.232209E+09 | 0.00 | 0.00 |
April | 0.518219E+09 | 0.136255E+09 | 0.264730E+09 | 46423394.97 | 0.218306E+09 | 0.00 | 0.00 |
May | 0.467934E+09 | 71105509.52 | 0.219209E+09 | 4742544.18 | 0.214467E+09 | 0.00 | 0.00 |
June | 0.458082E+09 | 32745649.90 | 0.202255E+09 | 381689.73 | 0.201874E+09 | 0.00 | 0.00 |
July | 0.534093E+09 | 49390115.83 | 0.223779E+09 | 2074238.30 | 0.221705E+09 | 0.00 | 0.00 |
August | 0.576102E+09 | 35497423.44 | 0.253982E+09 | 21432415.65 | 0.232550E+09 | 0.00 | 0.00 |
September | 0.713259E+09 | 55601009.93 | 0.314643E+09 | 77103960.73 | 0.237539E+09 | 0.00 | 0.00 |
October | 0.906906E+09 | 90885202.24 | 0.447120E+09 | 0.209775E+09 | 0.237345E+09 | 0.00 | 0.00 |
November | 0.897289E+09 | 0.151750E+09 | 0.492314E+09 | 0.274766E+09 | 0.217548E+09 | 0.00 | 0.00 |
December | 0.944689E+09 | 0.259031E+09 | 0.558194E+09 | 0.352077E+09 | 0.206117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.851891E+10 | 0.160380E+10 | 0.443100E+10 | 0.180901E+10 | 0.262199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.458082E+09 | 32745649.90 | 0.202255E+09 | 381689.73 | 0.199425E+09 | 0.00 | 0.00 |
Maximum of Months | 0.958589E+09 | 0.294400E+09 | 0.579208E+09 | 0.376298E+09 | 0.237539E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.959874E+09 | 0.291261E+09 | 0.579208E+09 | 0.376298E+09 | 0.202909E+09 | 0.00 | 0.00 |
February | 0.829942E+09 | 0.219760E+09 | 0.473271E+09 | 0.273845E+09 | 0.199425E+09 | 0.00 | 0.00 |
March | 0.716218E+09 | 0.201570E+09 | 0.402296E+09 | 0.170088E+09 | 0.232209E+09 | 0.00 | 0.00 |
April | 0.518979E+09 | 0.133989E+09 | 0.264730E+09 | 46423394.97 | 0.218306E+09 | 0.00 | 0.00 |
May | 0.468721E+09 | 69019846.25 | 0.219209E+09 | 4742544.18 | 0.214467E+09 | 0.00 | 0.00 |
June | 0.459260E+09 | 31410268.81 | 0.202255E+09 | 381689.73 | 0.201874E+09 | 0.00 | 0.00 |
July | 0.534922E+09 | 47812817.59 | 0.223779E+09 | 2074238.30 | 0.221705E+09 | 0.00 | 0.00 |
August | 0.577065E+09 | 33841267.76 | 0.253982E+09 | 21432415.65 | 0.232550E+09 | 0.00 | 0.00 |
September | 0.714225E+09 | 54276866.13 | 0.314643E+09 | 77103960.73 | 0.237539E+09 | 0.00 | 0.00 |
October | 0.907460E+09 | 88877575.17 | 0.447120E+09 | 0.209775E+09 | 0.237345E+09 | 0.00 | 0.00 |
November | 0.898096E+09 | 0.149478E+09 | 0.492314E+09 | 0.274766E+09 | 0.217548E+09 | 0.00 | 0.00 |
December | 0.945760E+09 | 0.256033E+09 | 0.558194E+09 | 0.352077E+09 | 0.206117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.853052E+10 | 0.157733E+10 | 0.443100E+10 | 0.180901E+10 | 0.262199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.459260E+09 | 31410268.81 | 0.202255E+09 | 381689.73 | 0.199425E+09 | 0.00 | 0.00 |
Maximum of Months | 0.959874E+09 | 0.291261E+09 | 0.579208E+09 | 0.376298E+09 | 0.237539E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.192727E+10 | 0.566711E+09 | 0.115842E+10 | 0.752596E+09 | 0.405819E+09 | 0.00 | 0.00 |
February | 0.166634E+10 | 0.425025E+09 | 0.946541E+09 | 0.547691E+09 | 0.398851E+09 | 0.00 | 0.00 |
March | 0.143937E+10 | 0.387903E+09 | 0.804592E+09 | 0.340175E+09 | 0.464417E+09 | 0.00 | 0.00 |
April | 0.103938E+10 | 0.255909E+09 | 0.529460E+09 | 92846789.93 | 0.436613E+09 | 0.00 | 0.00 |
May | 0.934907E+09 | 0.126634E+09 | 0.438419E+09 | 9485088.36 | 0.428934E+09 | 0.00 | 0.00 |
June | 0.919710E+09 | 56478221.15 | 0.404511E+09 | 763379.46 | 0.403747E+09 | 0.00 | 0.00 |
July | 0.106727E+10 | 87764790.30 | 0.447559E+09 | 4148476.60 | 0.443410E+09 | 0.00 | 0.00 |
August | 0.115375E+10 | 59391075.16 | 0.507965E+09 | 42864831.31 | 0.465100E+09 | 0.00 | 0.00 |
September | 0.142915E+10 | 0.101973E+09 | 0.629286E+09 | 0.154208E+09 | 0.475078E+09 | 0.00 | 0.00 |
October | 0.181381E+10 | 0.167493E+09 | 0.894241E+09 | 0.419550E+09 | 0.474690E+09 | 0.00 | 0.00 |
November | 0.179866E+10 | 0.286851E+09 | 0.984628E+09 | 0.549531E+09 | 0.435097E+09 | 0.00 | 0.00 |
December | 0.189785E+10 | 0.497335E+09 | 0.111639E+10 | 0.704155E+09 | 0.412234E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170875E+11 | 0.301947E+10 | 0.886200E+10 | 0.361801E+10 | 0.524399E+10 | 0.00 | 0.00 |
Minimum of Months | 0.919710E+09 | 56478221.15 | 0.404511E+09 | 763379.46 | 0.398851E+09 | 0.00 | 0.00 |
Maximum of Months | 0.192727E+10 | 0.566711E+09 | 0.115842E+10 | 0.752596E+09 | 0.475078E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.962452E+09 | 0.281826E+09 | 0.579208E+09 | 0.376298E+09 | 0.202909E+09 | 0.00 | 0.00 |
February | 0.832169E+09 | 0.210904E+09 | 0.473271E+09 | 0.273845E+09 | 0.199425E+09 | 0.00 | 0.00 |
March | 0.719016E+09 | 0.191806E+09 | 0.402296E+09 | 0.170088E+09 | 0.232209E+09 | 0.00 | 0.00 |
April | 0.520225E+09 | 0.125551E+09 | 0.264730E+09 | 46423394.97 | 0.218306E+09 | 0.00 | 0.00 |
May | 0.469487E+09 | 60502262.27 | 0.219209E+09 | 4742544.18 | 0.214467E+09 | 0.00 | 0.00 |
June | 0.463473E+09 | 26553724.70 | 0.202255E+09 | 381689.73 | 0.201874E+09 | 0.00 | 0.00 |
July | 0.536904E+09 | 41540909.66 | 0.223779E+09 | 2074238.30 | 0.221705E+09 | 0.00 | 0.00 |
August | 0.580133E+09 | 27499026.09 | 0.253982E+09 | 21432415.65 | 0.232550E+09 | 0.00 | 0.00 |
September | 0.717251E+09 | 49083117.98 | 0.314643E+09 | 77103960.73 | 0.237539E+09 | 0.00 | 0.00 |
October | 0.907576E+09 | 80652077.23 | 0.447120E+09 | 0.209775E+09 | 0.237345E+09 | 0.00 | 0.00 |
November | 0.898937E+09 | 0.141030E+09 | 0.492314E+09 | 0.274766E+09 | 0.217548E+09 | 0.00 | 0.00 |
December | 0.947716E+09 | 0.246982E+09 | 0.558194E+09 | 0.352077E+09 | 0.206117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.855534E+10 | 0.148393E+10 | 0.443100E+10 | 0.180901E+10 | 0.262199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.463473E+09 | 26553724.70 | 0.202255E+09 | 381689.73 | 0.199425E+09 | 0.00 | 0.00 |
Maximum of Months | 0.962452E+09 | 0.281826E+09 | 0.579208E+09 | 0.376298E+09 | 0.237539E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.963147E+09 | 0.280626E+09 | 0.579208E+09 | 0.376298E+09 | 0.202909E+09 | 0.00 | 0.00 |
February | 0.832776E+09 | 0.209877E+09 | 0.473271E+09 | 0.273845E+09 | 0.199425E+09 | 0.00 | 0.00 |
March | 0.719621E+09 | 0.190810E+09 | 0.402296E+09 | 0.170088E+09 | 0.232209E+09 | 0.00 | 0.00 |
April | 0.520594E+09 | 0.124907E+09 | 0.264730E+09 | 46423394.97 | 0.218306E+09 | 0.00 | 0.00 |
May | 0.469882E+09 | 59998603.40 | 0.219209E+09 | 4742544.18 | 0.214467E+09 | 0.00 | 0.00 |
June | 0.463946E+09 | 26289412.60 | 0.202255E+09 | 381689.73 | 0.201874E+09 | 0.00 | 0.00 |
July | 0.537284E+09 | 41223597.45 | 0.223779E+09 | 2074238.30 | 0.221705E+09 | 0.00 | 0.00 |
August | 0.580559E+09 | 27164947.96 | 0.253982E+09 | 21432415.65 | 0.232550E+09 | 0.00 | 0.00 |
September | 0.717653E+09 | 48813717.46 | 0.314643E+09 | 77103960.73 | 0.237539E+09 | 0.00 | 0.00 |
October | 0.907887E+09 | 80139632.74 | 0.447120E+09 | 0.209775E+09 | 0.237345E+09 | 0.00 | 0.00 |
November | 0.899344E+09 | 0.140365E+09 | 0.492314E+09 | 0.274766E+09 | 0.217548E+09 | 0.00 | 0.00 |
December | 0.948326E+09 | 0.245800E+09 | 0.558194E+09 | 0.352077E+09 | 0.206117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.856102E+10 | 0.147602E+10 | 0.443100E+10 | 0.180901E+10 | 0.262199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.463946E+09 | 26289412.60 | 0.202255E+09 | 381689.73 | 0.199425E+09 | 0.00 | 0.00 |
Maximum of Months | 0.963147E+09 | 0.280626E+09 | 0.579208E+09 | 0.376298E+09 | 0.237539E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.964683E+09 | 0.277502E+09 | 0.579208E+09 | 0.376298E+09 | 0.202909E+09 | 0.00 | 0.00 |
February | 0.833972E+09 | 0.207287E+09 | 0.473271E+09 | 0.273845E+09 | 0.199425E+09 | 0.00 | 0.00 |
March | 0.720479E+09 | 0.188504E+09 | 0.402296E+09 | 0.170088E+09 | 0.232209E+09 | 0.00 | 0.00 |
April | 0.520615E+09 | 0.123957E+09 | 0.264730E+09 | 46423394.97 | 0.218306E+09 | 0.00 | 0.00 |
May | 0.469497E+09 | 59860046.28 | 0.219209E+09 | 4742544.18 | 0.214467E+09 | 0.00 | 0.00 |
June | 0.462877E+09 | 26546185.01 | 0.202255E+09 | 381689.73 | 0.201874E+09 | 0.00 | 0.00 |
July | 0.536133E+09 | 41963898.52 | 0.223779E+09 | 2074238.30 | 0.221705E+09 | 0.00 | 0.00 |
August | 0.579434E+09 | 27593303.05 | 0.253982E+09 | 21432415.65 | 0.232550E+09 | 0.00 | 0.00 |
September | 0.716382E+09 | 49348464.43 | 0.314643E+09 | 77103960.73 | 0.237539E+09 | 0.00 | 0.00 |
October | 0.907363E+09 | 80389157.98 | 0.447120E+09 | 0.209775E+09 | 0.237345E+09 | 0.00 | 0.00 |
November | 0.899613E+09 | 0.139457E+09 | 0.492314E+09 | 0.274766E+09 | 0.217548E+09 | 0.00 | 0.00 |
December | 0.949577E+09 | 0.242876E+09 | 0.558194E+09 | 0.352077E+09 | 0.206117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.856063E+10 | 0.146529E+10 | 0.443100E+10 | 0.180901E+10 | 0.262199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.462877E+09 | 26546185.01 | 0.202255E+09 | 381689.73 | 0.199425E+09 | 0.00 | 0.00 |
Maximum of Months | 0.964683E+09 | 0.277502E+09 | 0.579208E+09 | 0.376298E+09 | 0.237539E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.964981E+09 | 0.266847E+09 | 0.579208E+09 | 0.376298E+09 | 0.202909E+09 | 0.00 | 0.00 |
February | 0.833231E+09 | 0.198333E+09 | 0.473271E+09 | 0.273845E+09 | 0.199425E+09 | 0.00 | 0.00 |
March | 0.717076E+09 | 0.180334E+09 | 0.402296E+09 | 0.170088E+09 | 0.232209E+09 | 0.00 | 0.00 |
April | 0.514486E+09 | 0.121288E+09 | 0.264730E+09 | 46423394.97 | 0.218306E+09 | 0.00 | 0.00 |
May | 0.460309E+09 | 61864519.68 | 0.219209E+09 | 4742544.18 | 0.214467E+09 | 0.00 | 0.00 |
June | 0.449599E+09 | 29258152.56 | 0.202255E+09 | 381689.73 | 0.201874E+09 | 0.00 | 0.00 |
July | 0.522191E+09 | 47627322.05 | 0.223779E+09 | 2074238.30 | 0.221705E+09 | 0.00 | 0.00 |
August | 0.566531E+09 | 32237981.58 | 0.253982E+09 | 21432415.65 | 0.232550E+09 | 0.00 | 0.00 |
September | 0.702388E+09 | 53871550.22 | 0.314643E+09 | 77103960.73 | 0.237539E+09 | 0.00 | 0.00 |
October | 0.898925E+09 | 84921917.50 | 0.447120E+09 | 0.209775E+09 | 0.237345E+09 | 0.00 | 0.00 |
November | 0.895600E+09 | 0.138204E+09 | 0.492314E+09 | 0.274766E+09 | 0.217548E+09 | 0.00 | 0.00 |
December | 0.949868E+09 | 0.233585E+09 | 0.558194E+09 | 0.352077E+09 | 0.206117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.847519E+10 | 0.144837E+10 | 0.443100E+10 | 0.180901E+10 | 0.262199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.449599E+09 | 29258152.56 | 0.202255E+09 | 381689.73 | 0.199425E+09 | 0.00 | 0.00 |
Maximum of Months | 0.964981E+09 | 0.266847E+09 | 0.579208E+09 | 0.376298E+09 | 0.237539E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.281734E+09 | -168215096.3 | 0.00 | 0.00 | 744.00 | 0.00 | -113519267.8 | 58.99 | 0.00 | 0.00 |
February | 0.253723E+09 | -151269877.8 | 0.00 | 0.00 | 672.00 | 0.00 | -102453258.4 | 58.99 | 0.00 | 0.00 |
March | 0.278218E+09 | -164978001.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113240234.4 | 58.99 | 0.00 | 0.00 |
April | 0.259158E+09 | -150282406.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108875315.2 | 58.99 | 0.00 | 0.00 |
May | 0.259762E+09 | -147767610.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111994477.9 | 58.99 | 0.00 | 0.00 |
June | 0.246648E+09 | -138594763.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108053363.3 | 58.99 | 0.00 | 0.00 |
July | 0.249416E+09 | -137808986.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111606583.6 | 58.99 | 0.00 | 0.00 |
August | 0.253951E+09 | -142418067.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111533166.2 | 58.99 | 0.00 | 0.00 |
September | 0.249449E+09 | -141459284.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107989399.1 | 58.99 | 0.00 | 0.00 |
October | 0.264113E+09 | -152296400.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111816911.0 | 59.00 | 0.00 | 0.00 |
November | 0.263255E+09 | -154419468.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108835070.9 | 58.99 | 0.00 | 0.00 |
December | 0.279275E+09 | -166055392.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113219870.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.313870E+10 | -0.181557E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132314E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.246648E+09 | -168215096.3 | 0.00 | 0.00 | 672.00 | 0.00 | -113519267.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.281734E+09 | -137808986.3 | 0.00 | 0.00 | 744.00 | 0.00 | -102453258.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.281306E+09 | -168213560.5 | 0.00 | 0.00 | 744.00 | 0.00 | -113092286.1 | 58.99 | 0.00 | 0.00 |
February | 0.253330E+09 | -151264536.5 | 0.00 | 0.00 | 672.00 | 0.00 | -102065018.0 | 58.99 | 0.00 | 0.00 |
March | 0.277867E+09 | -164985614.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112881137.5 | 58.99 | 0.00 | 0.00 |
April | 0.259003E+09 | -150285302.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108717979.8 | 58.99 | 0.00 | 0.00 |
May | 0.259687E+09 | -147766276.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111920903.7 | 58.99 | 0.00 | 0.00 |
June | 0.246641E+09 | -138599079.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108041710.7 | 58.99 | 0.00 | 0.00 |
July | 0.249415E+09 | -137810887.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111604478.2 | 58.99 | 0.00 | 0.00 |
August | 0.253989E+09 | -142414371.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111574675.1 | 58.99 | 0.00 | 0.00 |
September | 0.249468E+09 | -141459375.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108008493.6 | 58.99 | 0.00 | 0.00 |
October | 0.264087E+09 | -152307808.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111778890.2 | 58.99 | 0.00 | 0.00 |
November | 0.263087E+09 | -154419434.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108667484.9 | 58.99 | 0.00 | 0.00 |
December | 0.278919E+09 | -166054543.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112864704.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.313680E+10 | -0.181558E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132122E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.246641E+09 | -168213560.5 | 0.00 | 0.00 | 672.00 | 0.00 | -113092286.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.281306E+09 | -137810887.2 | 0.00 | 0.00 | 744.00 | 0.00 | -102065018.0 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.260447E+09 | -147921216.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112525593.7 | 58.99 | 0.00 | 0.00 |
February | 0.234555E+09 | -133132607.5 | 0.00 | 0.00 | 672.00 | 0.00 | -101422170.9 | 58.99 | 0.00 | 0.00 |
March | 0.259265E+09 | -147224478.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112040474.3 | 58.99 | 0.00 | 0.00 |
April | 0.239691E+09 | -132196478.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107494847.0 | 58.99 | 0.00 | 0.00 |
May | 0.241468E+09 | -131058852.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110409401.3 | 58.99 | 0.00 | 0.00 |
June | 0.229808E+09 | -123442714.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106364838.6 | 58.99 | 0.00 | 0.00 |
July | 0.230160E+09 | -120448505.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109711710.9 | 59.00 | 0.00 | 0.00 |
August | 0.237093E+09 | -127202320.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109890985.5 | 58.99 | 0.00 | 0.00 |
September | 0.230494E+09 | -124344483.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106149885.6 | 58.99 | 0.00 | 0.00 |
October | 0.244087E+09 | -133947784.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110138774.0 | 58.99 | 0.00 | 0.00 |
November | 0.243901E+09 | -136377780.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107523004.8 | 58.98 | 0.00 | 0.00 |
December | 0.257046E+09 | -144949446.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112096444.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.290801E+10 | -0.160225E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130577E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.229808E+09 | -147921216.0 | 0.00 | 0.00 | 672.00 | 0.00 | -112525593.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.260447E+09 | -120448505.5 | 0.00 | 0.00 | 744.00 | 0.00 | -101422170.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.260511E+09 | -147920049.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112591253.2 | 58.99 | 0.00 | 0.00 |
February | 0.234601E+09 | -133129723.6 | 0.00 | 0.00 | 672.00 | 0.00 | -101471148.0 | 58.99 | 0.00 | 0.00 |
March | 0.259298E+09 | -147218746.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112078764.4 | 59.00 | 0.00 | 0.00 |
April | 0.239664E+09 | -132195157.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107469171.0 | 58.99 | 0.00 | 0.00 |
May | 0.241409E+09 | -131061422.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110347385.3 | 58.99 | 0.00 | 0.00 |
June | 0.229715E+09 | -123443967.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106271104.3 | 58.99 | 0.00 | 0.00 |
July | 0.230043E+09 | -120462698.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109580388.9 | 58.99 | 0.00 | 0.00 |
August | 0.237004E+09 | -127198557.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109805251.4 | 58.99 | 0.00 | 0.00 |
September | 0.230382E+09 | -124341061.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106041070.5 | 58.99 | 0.00 | 0.00 |
October | 0.243997E+09 | -133962771.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110034258.2 | 58.99 | 0.00 | 0.00 |
November | 0.243893E+09 | -136299916.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107592589.6 | 59.01 | 0.00 | 0.00 |
December | 0.257080E+09 | -144962700.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112117582.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.290760E+10 | -0.160220E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130540E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.229715E+09 | -147920049.9 | 0.00 | 0.00 | 672.00 | 0.00 | -112591253.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.260511E+09 | -120462698.8 | 0.00 | 0.00 | 744.00 | 0.00 | -101471148.0 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.253071E+09 | -139759969.4 | 0.00 | 0.00 | 744.00 | 0.00 | -113311343.1 | 59.01 | 0.00 | 0.00 |
February | 0.227984E+09 | -125903033.7 | 0.00 | 0.00 | 672.00 | 0.00 | -102080801.1 | 58.99 | 0.00 | 0.00 |
March | 0.252065E+09 | -139320841.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112743721.1 | 58.99 | 0.00 | 0.00 |
April | 0.233059E+09 | -125088124.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107971001.1 | 58.99 | 0.00 | 0.00 |
May | 0.234778E+09 | -123936119.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110841620.5 | 58.99 | 0.00 | 0.00 |
June | 0.223545E+09 | -116821147.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106723924.7 | 58.98 | 0.00 | 0.00 |
July | 0.223933E+09 | -113960560.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109972535.4 | 58.99 | 0.00 | 0.00 |
August | 0.230631E+09 | -120348428.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110282291.4 | 58.99 | 0.00 | 0.00 |
September | 0.224110E+09 | -117684310.1 | 0.00 | 0.00 | 720.00 | 0.00 | -106425642.1 | 58.98 | 0.00 | 0.00 |
October | 0.237075E+09 | -126607580.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110467779.8 | 58.99 | 0.00 | 0.00 |
November | 0.236817E+09 | -128783117.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108033522.0 | 58.99 | 0.00 | 0.00 |
December | 0.249809E+09 | -137103579.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112705375.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.282688E+10 | -0.151532E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131156E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.223545E+09 | -139759969.4 | 0.00 | 0.00 | 672.00 | 0.00 | -113311343.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.253071E+09 | -113960560.5 | 0.00 | 0.00 | 744.00 | 0.00 | -102080801.1 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.253127E+09 | -139767184.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113359612.7 | 59.01 | 0.00 | 0.00 |
February | 0.228038E+09 | -125918250.3 | 0.00 | 0.00 | 672.00 | 0.00 | -102120009.8 | 58.98 | 0.00 | 0.00 |
March | 0.252130E+09 | -139309726.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112820437.1 | 58.99 | 0.00 | 0.00 |
April | 0.233128E+09 | -125090401.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108038098.3 | 58.99 | 0.00 | 0.00 |
May | 0.234856E+09 | -123929020.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110926789.9 | 58.99 | 0.00 | 0.00 |
June | 0.223655E+09 | -116806475.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106848290.9 | 58.99 | 0.00 | 0.00 |
July | 0.224046E+09 | -113945873.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110100411.3 | 58.99 | 0.00 | 0.00 |
August | 0.230739E+09 | -120375066.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110363960.4 | 58.98 | 0.00 | 0.00 |
September | 0.224223E+09 | -117656399.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106566633.4 | 58.99 | 0.00 | 0.00 |
October | 0.237165E+09 | -126601809.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110563017.6 | 58.99 | 0.00 | 0.00 |
November | 0.236889E+09 | -128768071.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108120450.3 | 58.99 | 0.00 | 0.00 |
December | 0.249874E+09 | -137083229.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112791139.9 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282787E+10 | -0.151525E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131262E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.223655E+09 | -139767184.7 | 0.00 | 0.00 | 672.00 | 0.00 | -113359612.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.253127E+09 | -113945873.8 | 0.00 | 0.00 | 744.00 | 0.00 | -102120009.8 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.253196E+09 | -139777070.1 | 0.00 | 0.00 | 744.00 | 0.00 | -113419262.5 | 59.00 | 0.00 | 0.00 |
February | 0.228096E+09 | -125936423.5 | 0.00 | 0.00 | 672.00 | 0.00 | -102159538.7 | 58.98 | 0.00 | 0.00 |
March | 0.252184E+09 | -139308706.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112875774.4 | 58.99 | 0.00 | 0.00 |
April | 0.233162E+09 | -125107553.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108054013.1 | 58.99 | 0.00 | 0.00 |
May | 0.234890E+09 | -123939627.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110950562.0 | 58.99 | 0.00 | 0.00 |
June | 0.223670E+09 | -116792326.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106878083.5 | 58.99 | 0.00 | 0.00 |
July | 0.224068E+09 | -113928977.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110138970.4 | 58.99 | 0.00 | 0.00 |
August | 0.230760E+09 | -120351374.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110408164.2 | 58.99 | 0.00 | 0.00 |
September | 0.224247E+09 | -117682374.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106564979.4 | 58.99 | 0.00 | 0.00 |
October | 0.237202E+09 | -126605392.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110596574.7 | 58.99 | 0.00 | 0.00 |
November | 0.236924E+09 | -128781147.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108142663.0 | 58.99 | 0.00 | 0.00 |
December | 0.249937E+09 | -137116066.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112821401.2 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.282834E+10 | -0.151533E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131301E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.223670E+09 | -139777070.1 | 0.00 | 0.00 | 672.00 | 0.00 | -113419262.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.253196E+09 | -113928977.2 | 0.00 | 0.00 | 744.00 | 0.00 | -102159538.7 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 287.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 304.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 362.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 389.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 388.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 348.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 349.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 323.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 314.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4111.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9756157.10 | 8487.45 | 04-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6980563.01 | 2986.76 | 16-MAR-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16736720.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9756157.10 | 8487.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 65972.39 | 355.17 | 04-FEB-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65972.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 65972.39 | 355.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 222191.58 | 405.46 | 04-FEB-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 222191.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 222191.58 | 405.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1190155.29 | 560.03 | 04-FEB-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1190155.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1190155.29 | 560.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5255642.79 | 3322.65 | 04-FEB-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2961117.11 | 1915.55 | 16-MAR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8216759.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5255642.79 | 3322.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2669229.59 | 1565.00 | 04-FEB-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1193162.89 | 826.81 | 16-MAR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3862392.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2669229.59 | 1565.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3161694.34 | 2281.81 | 04-FEB-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1538515.67 | 948.87 | 16-MAR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4700210.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3161694.34 | 2281.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5397634.55 | 2947.70 | 04-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3057791.60 | 1146.65 | 16-MAR-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8455426.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5397634.55 | 2947.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5836089.75 | 3782.62 | 25-JAN-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17363917.35 | 29918.18 | 04-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18342759.19 | 6978.55 | 16-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6996220.67 | 3052.82 | 15-DEC-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48538986.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18342759.19 | 29918.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.127193E+11 | 0.851499E+10 | 53096.22 | 14-JAN-08:62 | 29174.65 | 0.00 |
February | 0.00 | 0.00 | 0.146551E+11 | 0.101440E+11 | 55908.78 | 11-FEB-08:62 | 30005.78 | 0.00 |
March | 0.00 | 0.00 | 0.177798E+11 | 0.117204E+11 | 56339.58 | 14-MAR-07:03 | 28061.14 | 0.00 |
April | 0.00 | 0.00 | 0.230644E+11 | 0.154753E+11 | 56015.96 | 13-APR-07:03 | 30374.56 | 0.00 |
May | 0.00 | 0.00 | 0.318938E+11 | 0.198118E+11 | 57028.53 | 29-MAY-07:02 | 27128.20 | 0.00 |
June | 0.00 | 0.00 | 0.357551E+11 | 0.209942E+11 | 56612.59 | 08-JUN-07:02 | 30037.28 | 0.00 |
July | 0.00 | 0.00 | 0.397826E+11 | 0.238474E+11 | 55991.23 | 09-JUL-07:01 | 31651.57 | 0.00 |
August | 0.00 | 0.00 | 0.387039E+11 | 0.226506E+11 | 56395.55 | 20-AUG-07:01 | 30905.24 | 0.00 |
September | 0.00 | 0.00 | 0.371713E+11 | 0.222074E+11 | 56530.77 | 19-SEP-07:01 | 30771.91 | 0.00 |
October | 0.00 | 0.00 | 0.334521E+11 | 0.205050E+11 | 57294.84 | 03-OCT-07:02 | 27276.23 | 0.00 |
November | 0.00 | 0.00 | 0.247591E+11 | 0.152072E+11 | 57190.57 | 30-NOV-08:62 | 27640.15 | 0.00 |
December | 0.00 | 0.00 | 0.162587E+11 | 0.102448E+11 | 55931.34 | 09-DEC-08:62 | 30962.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.325995E+12 | 0.201323E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.127193E+11 | 0.851499E+10 | 53096.22 | 27128.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.397826E+11 | 0.238474E+11 | 57294.84 | 31651.57 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.715863E+10 | 0.495769E+10 | 25822.92 | 14-JAN-08:62 | 16575.68 | 0.00 |
February | 0.00 | 0.00 | 0.785565E+10 | 0.555864E+10 | 27766.95 | 11-FEB-08:62 | 17904.84 | 0.00 |
March | 0.00 | 0.00 | 0.921819E+10 | 0.622016E+10 | 28071.39 | 14-MAR-07:03 | 16779.16 | 0.00 |
April | 0.00 | 0.00 | 0.115766E+11 | 0.788252E+10 | 27871.65 | 13-APR-07:03 | 17826.13 | 0.00 |
May | 0.00 | 0.00 | 0.157110E+11 | 0.989740E+10 | 28170.06 | 27-MAY-07:02 | 16942.54 | 0.00 |
June | 0.00 | 0.00 | 0.176061E+11 | 0.104743E+11 | 28112.39 | 18-JUN-07:02 | 17562.26 | 0.00 |
July | 0.00 | 0.00 | 0.194976E+11 | 0.118009E+11 | 27828.27 | 09-JUL-07:01 | 18298.27 | 0.00 |
August | 0.00 | 0.00 | 0.189653E+11 | 0.112154E+11 | 28042.51 | 14-AUG-07:02 | 17659.46 | 0.00 |
September | 0.00 | 0.00 | 0.182543E+11 | 0.110290E+11 | 28081.83 | 19-SEP-07:01 | 17896.88 | 0.00 |
October | 0.00 | 0.00 | 0.165776E+11 | 0.103198E+11 | 28363.11 | 03-OCT-07:02 | 16570.43 | 0.00 |
November | 0.00 | 0.00 | 0.125996E+11 | 0.791839E+10 | 28418.26 | 30-NOV-08:62 | 16522.32 | 0.00 |
December | 0.00 | 0.00 | 0.869813E+10 | 0.567240E+10 | 27692.08 | 09-DEC-08:62 | 18523.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.163719E+12 | 0.102947E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.715863E+10 | 0.495769E+10 | 25822.92 | 16522.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.194976E+11 | 0.118009E+11 | 28418.26 | 18523.65 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.523738E+10 | 0.356469E+10 | 28778.25 | 14-JAN-07:03 | 15998.88 | 0.00 |
February | 0.00 | 0.00 | 0.598529E+10 | 0.418469E+10 | 29093.64 | 11-FEB-07:03 | 15173.60 | 0.00 |
March | 0.00 | 0.00 | 0.704740E+10 | 0.467006E+10 | 29496.59 | 06-MAR-07:03 | 13761.98 | 0.00 |
April | 0.00 | 0.00 | 0.904765E+10 | 0.605600E+10 | 29036.66 | 13-APR-06:02 | 15737.13 | 0.00 |
May | 0.00 | 0.00 | 0.126630E+11 | 0.783544E+10 | 30167.83 | 29-MAY-07:02 | 12422.39 | 0.00 |
June | 0.00 | 0.00 | 0.143421E+11 | 0.831831E+10 | 29988.41 | 19-JUN-06:02 | 12971.42 | 0.00 |
July | 0.00 | 0.00 | 0.158386E+11 | 0.936051E+10 | 29980.42 | 10-JUL-06:01 | 14003.73 | 0.00 |
August | 0.00 | 0.00 | 0.156376E+11 | 0.904009E+10 | 30221.20 | 28-AUG-06:02 | 12957.62 | 0.00 |
September | 0.00 | 0.00 | 0.147648E+11 | 0.869782E+10 | 29845.61 | 18-SEP-06:01 | 14465.44 | 0.00 |
October | 0.00 | 0.00 | 0.133530E+11 | 0.814738E+10 | 30198.72 | 02-OCT-06:02 | 12608.15 | 0.00 |
November | 0.00 | 0.00 | 0.998534E+10 | 0.615566E+10 | 30015.62 | 05-NOV-07:02 | 13227.57 | 0.00 |
December | 0.00 | 0.00 | 0.638370E+10 | 0.410599E+10 | 29342.47 | 11-DEC-07:02 | 14580.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.130286E+12 | 0.801366E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.523738E+10 | 0.356469E+10 | 28778.25 | 12422.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.158386E+11 | 0.936051E+10 | 30221.20 | 15998.88 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.519831E+10 | 0.353331E+10 | 28892.97 | 14-JAN-07:03 | 16060.37 | 0.00 |
February | 0.00 | 0.00 | 0.595370E+10 | 0.416059E+10 | 29209.20 | 11-FEB-07:03 | 15227.36 | 0.00 |
March | 0.00 | 0.00 | 0.702899E+10 | 0.465564E+10 | 29614.56 | 06-MAR-07:03 | 13823.15 | 0.00 |
April | 0.00 | 0.00 | 0.906459E+10 | 0.606990E+10 | 29153.51 | 13-APR-06:02 | 15808.48 | 0.00 |
May | 0.00 | 0.00 | 0.127021E+11 | 0.786536E+10 | 30290.08 | 29-MAY-07:02 | 12493.45 | 0.00 |
June | 0.00 | 0.00 | 0.144102E+11 | 0.836887E+10 | 30113.44 | 19-JUN-06:02 | 13069.05 | 0.00 |
July | 0.00 | 0.00 | 0.159234E+11 | 0.942440E+10 | 30114.28 | 10-JUL-06:01 | 14160.17 | 0.00 |
August | 0.00 | 0.00 | 0.157045E+11 | 0.909004E+10 | 30347.71 | 28-AUG-06:02 | 13071.45 | 0.00 |
September | 0.00 | 0.00 | 0.148470E+11 | 0.875946E+10 | 29977.98 | 18-SEP-06:01 | 14613.73 | 0.00 |
October | 0.00 | 0.00 | 0.134144E+11 | 0.819366E+10 | 30318.03 | 02-OCT-06:02 | 12710.92 | 0.00 |
November | 0.00 | 0.00 | 0.999557E+10 | 0.616321E+10 | 30137.99 | 05-NOV-07:02 | 13313.55 | 0.00 |
December | 0.00 | 0.00 | 0.635626E+10 | 0.408722E+10 | 29463.92 | 11-DEC-07:02 | 14672.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.130599E+12 | 0.803716E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.519831E+10 | 0.353331E+10 | 28892.97 | 12493.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.159234E+11 | 0.942440E+10 | 30347.71 | 16060.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.497733E+10 | 0.336101E+10 | 28686.68 | 14-JAN-07:03 | 15830.71 | 0.00 |
February | 0.00 | 0.00 | 0.575329E+10 | 0.400517E+10 | 29003.98 | 11-FEB-07:03 | 14983.21 | 0.00 |
March | 0.00 | 0.00 | 0.680843E+10 | 0.448599E+10 | 29403.67 | 06-MAR-07:03 | 13640.60 | 0.00 |
April | 0.00 | 0.00 | 0.886542E+10 | 0.591729E+10 | 28947.96 | 13-APR-06:02 | 15575.44 | 0.00 |
May | 0.00 | 0.00 | 0.125077E+11 | 0.772039E+10 | 30072.74 | 29-MAY-07:02 | 12301.68 | 0.00 |
June | 0.00 | 0.00 | 0.142265E+11 | 0.823324E+10 | 29900.34 | 19-JUN-06:02 | 12903.15 | 0.00 |
July | 0.00 | 0.00 | 0.157503E+11 | 0.929410E+10 | 29901.98 | 10-JUL-06:01 | 13990.93 | 0.00 |
August | 0.00 | 0.00 | 0.155138E+11 | 0.894958E+10 | 30135.37 | 28-AUG-06:02 | 12892.52 | 0.00 |
September | 0.00 | 0.00 | 0.146773E+11 | 0.863251E+10 | 29767.07 | 18-SEP-06:01 | 14445.78 | 0.00 |
October | 0.00 | 0.00 | 0.132357E+11 | 0.805902E+10 | 30113.21 | 02-OCT-06:02 | 12551.13 | 0.00 |
November | 0.00 | 0.00 | 0.979362E+10 | 0.601180E+10 | 29926.87 | 05-NOV-07:02 | 13114.95 | 0.00 |
December | 0.00 | 0.00 | 0.613479E+10 | 0.392264E+10 | 29255.10 | 11-DEC-07:02 | 14496.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.128244E+12 | 0.785927E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.497733E+10 | 0.336101E+10 | 28686.68 | 12301.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.157503E+11 | 0.929410E+10 | 30135.37 | 15830.71 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.876682E+10 | 0.570831E+10 | 48957.92 | 14-JAN-08:62 | 26786.78 | 0.00 |
February | 0.00 | 0.00 | 0.104110E+11 | 0.706635E+10 | 51711.09 | 11-FEB-08:62 | 27265.73 | 0.00 |
March | 0.00 | 0.00 | 0.123635E+11 | 0.790562E+10 | 52696.13 | 06-MAR-08:62 | 24338.70 | 0.00 |
April | 0.00 | 0.00 | 0.163887E+11 | 0.106714E+11 | 51536.79 | 13-APR-07:03 | 28399.37 | 0.00 |
May | 0.00 | 0.00 | 0.234556E+11 | 0.141346E+11 | 53897.92 | 29-MAY-08:62 | 22070.99 | 0.00 |
June | 0.00 | 0.00 | 0.268741E+11 | 0.151574E+11 | 53548.48 | 19-JUN-07:02 | 23243.53 | 0.00 |
July | 0.00 | 0.00 | 0.297994E+11 | 0.172038E+11 | 53654.24 | 10-JUL-07:01 | 24944.62 | 0.00 |
August | 0.00 | 0.00 | 0.293478E+11 | 0.165217E+11 | 53995.82 | 28-AUG-07:02 | 23091.32 | 0.00 |
September | 0.00 | 0.00 | 0.277335E+11 | 0.159278E+11 | 53367.49 | 18-SEP-07:01 | 25661.93 | 0.00 |
October | 0.00 | 0.00 | 0.248241E+11 | 0.147566E+11 | 53957.47 | 30-OCT-07:02 | 21597.94 | 0.00 |
November | 0.00 | 0.00 | 0.182093E+11 | 0.108277E+11 | 53812.95 | 05-NOV-08:62 | 22780.88 | 0.00 |
December | 0.00 | 0.00 | 0.108834E+11 | 0.672109E+10 | 52376.37 | 10-DEC-09:02 | 26327.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.239057E+12 | 0.142602E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.876682E+10 | 0.570831E+10 | 48957.92 | 21597.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.297994E+11 | 0.172038E+11 | 53995.82 | 28399.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.449457E+10 | 0.292385E+10 | 23682.21 | 14-JAN-08:62 | 12933.85 | 0.00 |
February | 0.00 | 0.00 | 0.536155E+10 | 0.364053E+10 | 26686.81 | 18-FEB-08:62 | 15667.86 | 0.00 |
March | 0.00 | 0.00 | 0.636246E+10 | 0.406512E+10 | 27638.64 | 06-MAR-08:62 | 12721.94 | 0.00 |
April | 0.00 | 0.00 | 0.848276E+10 | 0.552447E+10 | 27000.30 | 13-APR-07:03 | 14910.83 | 0.00 |
May | 0.00 | 0.00 | 0.121886E+11 | 0.734587E+10 | 28247.78 | 29-MAY-08:62 | 11497.54 | 0.00 |
June | 0.00 | 0.00 | 0.139763E+11 | 0.788217E+10 | 28093.92 | 26-JUN-07:02 | 12701.02 | 0.00 |
July | 0.00 | 0.00 | 0.155263E+11 | 0.896218E+10 | 28161.08 | 10-JUL-07:01 | 12981.67 | 0.00 |
August | 0.00 | 0.00 | 0.152759E+11 | 0.859892E+10 | 28312.83 | 28-AUG-07:02 | 11970.66 | 0.00 |
September | 0.00 | 0.00 | 0.144323E+11 | 0.828847E+10 | 27998.45 | 18-SEP-07:01 | 13388.78 | 0.00 |
October | 0.00 | 0.00 | 0.129167E+11 | 0.767878E+10 | 28278.99 | 30-OCT-07:02 | 11231.13 | 0.00 |
November | 0.00 | 0.00 | 0.944017E+10 | 0.561348E+10 | 28229.56 | 05-NOV-08:62 | 11876.31 | 0.00 |
December | 0.00 | 0.00 | 0.559676E+10 | 0.345390E+10 | 27472.79 | 10-DEC-09:02 | 13727.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124054E+12 | 0.739777E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.449457E+10 | 0.292385E+10 | 23682.21 | 11231.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.155263E+11 | 0.896218E+10 | 28312.83 | 15667.86 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.442844E+10 | 0.287415E+10 | 23000.59 | 14-JAN-08:62 | 12521.30 | 0.00 |
February | 0.00 | 0.00 | 0.529764E+10 | 0.359243E+10 | 26572.71 | 18-FEB-08:62 | 15573.43 | 0.00 |
March | 0.00 | 0.00 | 0.629666E+10 | 0.401617E+10 | 27518.45 | 06-MAR-08:62 | 12647.06 | 0.00 |
April | 0.00 | 0.00 | 0.842638E+10 | 0.548255E+10 | 26886.42 | 13-APR-07:03 | 14818.37 | 0.00 |
May | 0.00 | 0.00 | 0.121325E+11 | 0.730562E+10 | 28127.13 | 29-MAY-08:62 | 11430.12 | 0.00 |
June | 0.00 | 0.00 | 0.139263E+11 | 0.784646E+10 | 27973.96 | 26-JUN-07:02 | 12634.53 | 0.00 |
July | 0.00 | 0.00 | 0.154793E+11 | 0.892785E+10 | 28040.94 | 10-JUL-07:01 | 12918.42 | 0.00 |
August | 0.00 | 0.00 | 0.152251E+11 | 0.856260E+10 | 28191.91 | 28-AUG-07:02 | 11904.41 | 0.00 |
September | 0.00 | 0.00 | 0.143864E+11 | 0.825511E+10 | 27879.13 | 18-SEP-07:01 | 13324.59 | 0.00 |
October | 0.00 | 0.00 | 0.128644E+11 | 0.764050E+10 | 28158.21 | 30-OCT-07:02 | 11170.54 | 0.00 |
November | 0.00 | 0.00 | 0.938019E+10 | 0.556968E+10 | 28109.28 | 05-NOV-08:62 | 11809.13 | 0.00 |
December | 0.00 | 0.00 | 0.552346E+10 | 0.340158E+10 | 27354.47 | 10-DEC-09:02 | 13645.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.123367E+12 | 0.734747E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.442844E+10 | 0.287415E+10 | 23000.59 | 11170.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.154793E+11 | 0.892785E+10 | 28191.91 | 15573.43 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.429496E+10 | 0.277471E+10 | 20866.21 | 14-JAN-08:62 | 11247.10 | 0.00 |
February | 0.00 | 0.00 | 0.517852E+10 | 0.350346E+10 | 24614.46 | 18-FEB-08:62 | 14305.58 | 0.00 |
March | 0.00 | 0.00 | 0.619341E+10 | 0.394036E+10 | 27627.96 | 06-MAR-08:62 | 12620.95 | 0.00 |
April | 0.00 | 0.00 | 0.837594E+10 | 0.544597E+10 | 26996.14 | 13-APR-07:03 | 14814.30 | 0.00 |
May | 0.00 | 0.00 | 0.121340E+11 | 0.730839E+10 | 28252.29 | 29-MAY-08:62 | 11420.69 | 0.00 |
June | 0.00 | 0.00 | 0.139757E+11 | 0.788239E+10 | 28091.12 | 26-JUN-07:02 | 12661.75 | 0.00 |
July | 0.00 | 0.00 | 0.155592E+11 | 0.898697E+10 | 28162.02 | 10-JUL-07:01 | 12969.01 | 0.00 |
August | 0.00 | 0.00 | 0.152816E+11 | 0.860522E+10 | 28317.35 | 28-AUG-07:02 | 11931.17 | 0.00 |
September | 0.00 | 0.00 | 0.144627E+11 | 0.831090E+10 | 28002.40 | 18-SEP-07:01 | 13391.92 | 0.00 |
October | 0.00 | 0.00 | 0.128854E+11 | 0.765635E+10 | 28283.50 | 30-OCT-07:02 | 11198.47 | 0.00 |
November | 0.00 | 0.00 | 0.932135E+10 | 0.552612E+10 | 28225.82 | 05-NOV-08:62 | 11815.63 | 0.00 |
December | 0.00 | 0.00 | 0.538099E+10 | 0.330077E+10 | 27465.66 | 10-DEC-09:02 | 13647.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.123044E+12 | 0.732416E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.429496E+10 | 0.277471E+10 | 20866.21 | 11198.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.155592E+11 | 0.898697E+10 | 28317.35 | 14814.30 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.481291E+10 | 0.316068E+10 | 18381.05 | 14-JAN-08:62 | 8923.77 | 0.00 |
February | 0.00 | 0.00 | 0.582750E+10 | 0.399443E+10 | 23005.27 | 18-FEB-08:62 | 12257.93 | 0.00 |
March | 0.00 | 0.00 | 0.709237E+10 | 0.459203E+10 | 28410.19 | 05-MAR-09:02 | 12729.60 | 0.00 |
April | 0.00 | 0.00 | 0.975236E+10 | 0.646642E+10 | 32179.73 | 13-APR-07:03 | 15522.68 | 0.00 |
May | 0.00 | 0.00 | 0.140938E+11 | 0.869410E+10 | 33577.00 | 29-MAY-08:62 | 12881.27 | 0.00 |
June | 0.00 | 0.00 | 0.162221E+11 | 0.942916E+10 | 33604.85 | 26-JUN-07:02 | 14516.11 | 0.00 |
July | 0.00 | 0.00 | 0.181022E+11 | 0.108044E+11 | 33618.92 | 10-JUL-07:01 | 15021.59 | 0.00 |
August | 0.00 | 0.00 | 0.175737E+11 | 0.102085E+11 | 33654.32 | 28-AUG-07:02 | 14119.17 | 0.00 |
September | 0.00 | 0.00 | 0.167996E+11 | 0.995157E+10 | 33557.37 | 18-SEP-07:01 | 15398.64 | 0.00 |
October | 0.00 | 0.00 | 0.147641E+11 | 0.899182E+10 | 33614.09 | 30-OCT-07:03 | 12471.62 | 0.00 |
November | 0.00 | 0.00 | 0.105058E+11 | 0.636340E+10 | 33675.25 | 05-NOV-08:62 | 13436.38 | 0.00 |
December | 0.00 | 0.00 | 0.588951E+10 | 0.366252E+10 | 32841.74 | 10-DEC-09:02 | 15549.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.141436E+12 | 0.863190E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.481291E+10 | 0.316068E+10 | 18381.05 | 8923.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.181022E+11 | 0.108044E+11 | 33675.25 | 15549.95 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158621E+10 | 0.36 | 2074.89 | 14-JAN-08:62 | 0.84 |
February | 0.143613E+10 | 0.36 | 2185.23 | 11-FEB-08:62 | 0.86 |
March | 0.159340E+10 | 0.36 | 2185.23 | 05-MAR-08:62 | 0.86 |
April | 0.153803E+10 | 0.36 | 2185.23 | 12-APR-07:03 | 0.86 |
May | 0.160190E+10 | 0.36 | 2185.23 | 03-MAY-07:03 | 0.87 |
June | 0.158814E+10 | 0.36 | 2185.23 | 01-JUN-07:02 | 0.86 |
July | 0.170435E+10 | 0.37 | 2185.23 | 01-JUL-07:02 | 0.86 |
August | 0.168894E+10 | 0.37 | 2185.23 | 01-AUG-07:01 | 0.86 |
September | 0.162765E+10 | 0.37 | 2185.23 | 01-SEP-07:02 | 0.86 |
October | 0.162178E+10 | 0.36 | 2185.23 | 01-OCT-07:01 | 0.86 |
November | 0.153790E+10 | 0.36 | 2185.23 | 03-NOV-07:03 | 0.87 |
December | 0.159370E+10 | 0.36 | 2185.23 | 01-DEC-08:62 | 0.87 |
Annual Sum or Average | 0.191181E+11 | 0.36 | |||
Minimum of Months | 0.143613E+10 | 0.36 | 2074.89 | 0.84 | |
Maximum of Months | 0.170435E+10 | 0.37 | 2185.23 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.689378E+09 | 0.39 | 1062.45 | 14-JAN-08:62 | 0.86 |
February | 0.627412E+09 | 0.39 | 1156.64 | 11-FEB-08:62 | 0.90 |
March | 0.707491E+09 | 0.39 | 1156.64 | 05-MAR-08:62 | 0.90 |
April | 0.691924E+09 | 0.38 | 1156.64 | 12-APR-07:03 | 0.90 |
May | 0.741303E+09 | 0.38 | 1156.64 | 03-MAY-07:03 | 0.90 |
June | 0.750605E+09 | 0.39 | 1156.64 | 01-JUN-07:02 | 0.90 |
July | 0.805649E+09 | 0.39 | 1156.64 | 01-JUL-07:02 | 0.90 |
August | 0.798393E+09 | 0.39 | 1156.64 | 01-AUG-07:01 | 0.90 |
September | 0.769263E+09 | 0.39 | 1156.64 | 01-SEP-07:02 | 0.90 |
October | 0.753682E+09 | 0.38 | 1156.64 | 01-OCT-07:01 | 0.90 |
November | 0.696701E+09 | 0.38 | 1156.64 | 04-NOV-07:02 | 0.90 |
December | 0.699726E+09 | 0.39 | 1156.64 | 07-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.873153E+10 | 0.39 | |||
Minimum of Months | 0.627412E+09 | 0.38 | 1062.45 | 0.86 | |
Maximum of Months | 0.805649E+09 | 0.39 | 1156.64 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.677040E+09 | 0.30 | 1169.00 | 14-JAN-07:03 | 0.89 |
February | 0.613430E+09 | 0.30 | 1169.00 | 11-FEB-07:03 | 0.89 |
March | 0.691356E+09 | 0.30 | 1169.00 | 05-MAR-08:62 | 0.89 |
April | 0.658035E+09 | 0.30 | 1169.00 | 12-APR-06:03 | 0.89 |
May | 0.689671E+09 | 0.30 | 1169.00 | 03-MAY-06:03 | 0.90 |
June | 0.685341E+09 | 0.30 | 1169.00 | 01-JUN-06:02 | 0.89 |
July | 0.723147E+09 | 0.30 | 1169.00 | 01-JUL-06:02 | 0.89 |
August | 0.730481E+09 | 0.31 | 1169.00 | 01-AUG-06:01 | 0.89 |
September | 0.692661E+09 | 0.30 | 1169.00 | 01-SEP-06:02 | 0.89 |
October | 0.691323E+09 | 0.30 | 1169.00 | 01-OCT-07:01 | 0.89 |
November | 0.659152E+09 | 0.30 | 1169.00 | 03-NOV-06:02 | 0.89 |
December | 0.674239E+09 | 0.29 | 1169.00 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.818588E+10 | 0.30 | |||
Minimum of Months | 0.613430E+09 | 0.29 | 1169.00 | 0.89 | |
Maximum of Months | 0.730481E+09 | 0.31 | 1169.00 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.679707E+09 | 0.30 | 1173.62 | 14-JAN-07:03 | 0.89 |
February | 0.615824E+09 | 0.30 | 1173.62 | 11-FEB-07:03 | 0.89 |
March | 0.694074E+09 | 0.30 | 1173.62 | 05-MAR-08:62 | 0.89 |
April | 0.660633E+09 | 0.30 | 1173.62 | 12-APR-06:03 | 0.89 |
May | 0.692342E+09 | 0.30 | 1173.62 | 03-MAY-06:03 | 0.90 |
June | 0.687949E+09 | 0.30 | 1173.62 | 01-JUN-06:02 | 0.89 |
July | 0.725893E+09 | 0.30 | 1173.62 | 01-JUL-06:02 | 0.89 |
August | 0.733077E+09 | 0.31 | 1173.62 | 01-AUG-06:01 | 0.89 |
September | 0.695421E+09 | 0.30 | 1173.62 | 01-SEP-06:02 | 0.89 |
October | 0.694004E+09 | 0.30 | 1173.62 | 01-OCT-07:01 | 0.89 |
November | 0.661749E+09 | 0.30 | 1173.62 | 01-NOV-06:03 | 0.89 |
December | 0.676894E+09 | 0.29 | 1173.62 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.821757E+10 | 0.30 | |||
Minimum of Months | 0.615824E+09 | 0.29 | 1173.62 | 0.89 | |
Maximum of Months | 0.733077E+09 | 0.31 | 1173.62 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.675005E+09 | 0.29 | 1165.69 | 14-JAN-07:03 | 0.89 |
February | 0.611572E+09 | 0.30 | 1165.69 | 11-FEB-07:03 | 0.89 |
March | 0.689188E+09 | 0.30 | 1165.69 | 05-MAR-08:62 | 0.89 |
April | 0.655928E+09 | 0.30 | 1165.69 | 12-APR-06:03 | 0.89 |
May | 0.687403E+09 | 0.30 | 1165.69 | 03-MAY-06:03 | 0.90 |
June | 0.682412E+09 | 0.30 | 1165.69 | 01-JUN-06:02 | 0.89 |
July | 0.719969E+09 | 0.30 | 1165.69 | 01-JUL-06:02 | 0.89 |
August | 0.726983E+09 | 0.31 | 1165.69 | 01-AUG-06:01 | 0.89 |
September | 0.689860E+09 | 0.30 | 1165.69 | 01-SEP-06:02 | 0.89 |
October | 0.688704E+09 | 0.30 | 1165.69 | 01-OCT-07:01 | 0.89 |
November | 0.657041E+09 | 0.30 | 1165.69 | 03-NOV-06:02 | 0.89 |
December | 0.672211E+09 | 0.29 | 1165.69 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.815628E+10 | 0.30 | |||
Minimum of Months | 0.611572E+09 | 0.29 | 1165.69 | 0.89 | |
Maximum of Months | 0.726983E+09 | 0.31 | 1165.69 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107896E+10 | 0.26 | 1913.82 | 14-JAN-08:62 | 0.84 |
February | 0.978766E+09 | 0.26 | 2018.69 | 11-FEB-08:62 | 0.86 |
March | 0.110294E+10 | 0.27 | 2018.69 | 05-MAR-09:02 | 0.86 |
April | 0.105201E+10 | 0.26 | 2018.69 | 12-APR-07:03 | 0.86 |
May | 0.111628E+10 | 0.27 | 2018.69 | 03-MAY-07:03 | 0.87 |
June | 0.113895E+10 | 0.28 | 2018.69 | 01-JUN-07:02 | 0.86 |
July | 0.123073E+10 | 0.28 | 2018.69 | 01-JUL-07:02 | 0.86 |
August | 0.123395E+10 | 0.29 | 2018.69 | 01-AUG-07:01 | 0.86 |
September | 0.116559E+10 | 0.28 | 2018.69 | 01-SEP-07:02 | 0.86 |
October | 0.113385E+10 | 0.27 | 2018.69 | 01-OCT-08:62 | 0.86 |
November | 0.105481E+10 | 0.26 | 2018.69 | 03-NOV-07:03 | 0.86 |
December | 0.107433E+10 | 0.26 | 2018.69 | 01-DEC-08:62 | 0.87 |
Annual Sum or Average | 0.133612E+11 | 0.27 | |||
Minimum of Months | 0.978766E+09 | 0.26 | 1913.82 | 0.84 | |
Maximum of Months | 0.123395E+10 | 0.29 | 2018.69 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.585050E+09 | 0.27 | 941.60 | 14-JAN-08:62 | 0.84 |
February | 0.530674E+09 | 0.27 | 1094.69 | 18-FEB-08:62 | 0.89 |
March | 0.597969E+09 | 0.28 | 1094.69 | 05-MAR-09:02 | 0.89 |
April | 0.570253E+09 | 0.27 | 1094.69 | 12-APR-07:03 | 0.89 |
May | 0.605222E+09 | 0.28 | 1094.69 | 03-MAY-07:03 | 0.90 |
June | 0.617154E+09 | 0.29 | 1094.69 | 01-JUN-07:02 | 0.89 |
July | 0.667731E+09 | 0.29 | 1094.69 | 01-JUL-07:02 | 0.89 |
August | 0.669013E+09 | 0.30 | 1094.69 | 01-AUG-07:01 | 0.89 |
September | 0.631742E+09 | 0.29 | 1094.69 | 01-SEP-07:02 | 0.89 |
October | 0.614530E+09 | 0.28 | 1094.69 | 01-OCT-08:62 | 0.89 |
November | 0.571669E+09 | 0.27 | 1094.69 | 03-NOV-07:03 | 0.89 |
December | 0.582490E+09 | 0.27 | 1094.69 | 01-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.724350E+10 | 0.28 | |||
Minimum of Months | 0.530674E+09 | 0.27 | 941.60 | 0.84 | |
Maximum of Months | 0.669013E+09 | 0.30 | 1094.69 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.582535E+09 | 0.27 | 909.33 | 14-JAN-08:62 | 0.82 |
February | 0.528408E+09 | 0.27 | 1090.01 | 18-FEB-08:62 | 0.89 |
March | 0.595385E+09 | 0.28 | 1090.01 | 05-MAR-09:02 | 0.89 |
April | 0.567811E+09 | 0.27 | 1090.01 | 12-APR-07:03 | 0.89 |
May | 0.602769E+09 | 0.28 | 1090.01 | 04-MAY-07:02 | 0.89 |
June | 0.614925E+09 | 0.29 | 1090.01 | 01-JUN-07:02 | 0.89 |
July | 0.665631E+09 | 0.29 | 1090.01 | 01-JUL-07:02 | 0.89 |
August | 0.666767E+09 | 0.30 | 1090.01 | 01-AUG-07:01 | 0.89 |
September | 0.629618E+09 | 0.29 | 1090.01 | 01-SEP-07:02 | 0.89 |
October | 0.612153E+09 | 0.28 | 1090.01 | 01-OCT-08:62 | 0.89 |
November | 0.569224E+09 | 0.27 | 1090.01 | 03-NOV-07:03 | 0.89 |
December | 0.579978E+09 | 0.27 | 1090.01 | 01-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.721520E+10 | 0.28 | |||
Minimum of Months | 0.528408E+09 | 0.27 | 909.33 | 0.82 | |
Maximum of Months | 0.666767E+09 | 0.30 | 1090.01 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.585052E+09 | 0.27 | 804.60 | 14-JAN-08:62 | 0.77 |
February | 0.530673E+09 | 0.27 | 993.47 | 18-FEB-08:62 | 0.86 |
March | 0.597949E+09 | 0.28 | 1094.86 | 05-MAR-09:02 | 0.89 |
April | 0.570172E+09 | 0.27 | 1094.86 | 12-APR-07:03 | 0.89 |
May | 0.605246E+09 | 0.28 | 1094.86 | 04-MAY-07:02 | 0.89 |
June | 0.617763E+09 | 0.29 | 1094.86 | 01-JUN-07:02 | 0.89 |
July | 0.669264E+09 | 0.29 | 1094.86 | 01-JUL-07:02 | 0.89 |
August | 0.670001E+09 | 0.30 | 1094.86 | 01-AUG-07:01 | 0.89 |
September | 0.632943E+09 | 0.29 | 1094.86 | 01-SEP-07:02 | 0.89 |
October | 0.614526E+09 | 0.28 | 1094.86 | 01-OCT-08:62 | 0.89 |
November | 0.571467E+09 | 0.27 | 1094.86 | 03-NOV-07:03 | 0.89 |
December | 0.582436E+09 | 0.27 | 1094.86 | 01-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.724749E+10 | 0.28 | |||
Minimum of Months | 0.530673E+09 | 0.27 | 804.60 | 0.77 | |
Maximum of Months | 0.670001E+09 | 0.30 | 1094.86 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.695327E+09 | 0.27 | 632.76 | 14-JAN-08:62 | 0.61 |
February | 0.630212E+09 | 0.27 | 1301.21 | 04-FEB-08:62 | 0.91 |
March | 0.710787E+09 | 0.28 | 1087.85 | 05-MAR-09:02 | 0.82 |
April | 0.676172E+09 | 0.27 | 1277.13 | 13-APR-07:03 | 0.88 |
May | 0.714598E+09 | 0.28 | 1301.21 | 04-MAY-07:02 | 0.89 |
June | 0.723014E+09 | 0.28 | 1301.21 | 01-JUN-07:02 | 0.89 |
July | 0.780195E+09 | 0.29 | 1301.21 | 01-JUL-07:02 | 0.89 |
August | 0.780248E+09 | 0.29 | 1301.21 | 01-AUG-07:01 | 0.89 |
September | 0.738511E+09 | 0.29 | 1301.21 | 01-SEP-07:02 | 0.89 |
October | 0.719106E+09 | 0.28 | 1301.21 | 01-OCT-08:62 | 0.89 |
November | 0.676962E+09 | 0.27 | 1301.21 | 04-NOV-07:02 | 0.89 |
December | 0.692092E+09 | 0.27 | 1301.21 | 09-DEC-08:62 | 0.89 |
Annual Sum or Average | 0.853723E+10 | 0.28 | |||
Minimum of Months | 0.630212E+09 | 0.27 | 632.76 | 0.61 | |
Maximum of Months | 0.780248E+09 | 0.29 | 1301.21 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.472642E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.503907E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.591342E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.714996E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.922061E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.100012E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.111331E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.108020E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.103777E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.952393E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.740573E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.550760E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.968007E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.472642E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.111331E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.242543E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.252691E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.291602E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.347169E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.445270E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.484492E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.537587E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.521279E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.501607E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.462115E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.364168E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.276643E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.472716E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.242543E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.537587E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.194410E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.205973E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.237484E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.282342E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.366510E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.397998E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.440435E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.433625E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.408680E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.378026E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.297805E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.218652E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.386194E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.194410E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.440435E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.193834E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.205575E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.237429E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.283112E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.367801E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.399866E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.442701E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.435488E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.410847E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.379749E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.298418E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.218369E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.387319E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.193834E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.442701E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.188217E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.200575E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.231936E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.278181E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.363003E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.395187E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.438059E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.430528E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.406440E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.375236E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.293497E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.212829E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.381369E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.188217E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.438059E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.322355E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.352335E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.408243E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.499889E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.664362E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.734006E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.819809E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.804327E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.757800E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.690121E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.530154E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.366888E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.695029E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.322355E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.819809E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.166680E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.182036E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.210713E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.258087E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.343211E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.379112E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.424045E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.415687E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.391544E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.356712E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.273805E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.189517E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.359115E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.166680E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.424045E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.164861E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.180315E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.208918E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.256515E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.341628E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.377681E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.422662E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.414218E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.390206E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.355222E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.272167E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.187547E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.357194E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.164861E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.422662E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.162063E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.177899E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.206925E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.255744E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.342077E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.379173E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.424943E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.415932E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.392334E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.356052E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.271227E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.184562E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.356893E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.162063E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.424943E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.186559E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.204741E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.241003E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.300447E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.401280E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.443944E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.498130E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.483206E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.459019E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.412578E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.311967E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.208962E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.415184E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.186559E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.498130E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158621E+10 | 0.127193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143613E+10 | 0.146551E+11 | 9756157.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159340E+10 | 0.177798E+11 | 6980563.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153803E+10 | 0.230644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160190E+10 | 0.318938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158814E+10 | 0.357551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.170435E+10 | 0.397826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168894E+10 | 0.387039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162765E+10 | 0.371713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162178E+10 | 0.334521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153790E+10 | 0.247591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159370E+10 | 0.162587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191181E+11 | 0.325995E+12 | 16736720.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143613E+10 | 0.127193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170435E+10 | 0.397826E+11 | 9756157.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.689378E+09 | 0.715863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.627412E+09 | 0.785565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.707491E+09 | 0.921819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.691924E+09 | 0.115766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.741303E+09 | 0.157110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.750605E+09 | 0.176061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.805649E+09 | 0.194976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.798393E+09 | 0.189653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.769263E+09 | 0.182543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.753682E+09 | 0.165776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.696701E+09 | 0.125996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.699726E+09 | 0.869813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.873153E+10 | 0.163719E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.627412E+09 | 0.715863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.805649E+09 | 0.194976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.677040E+09 | 0.523738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.613430E+09 | 0.598529E+10 | 65972.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.691356E+09 | 0.704740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.658035E+09 | 0.904765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.689671E+09 | 0.126630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.685341E+09 | 0.143421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.723147E+09 | 0.158386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.730481E+09 | 0.156376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.692661E+09 | 0.147648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.691323E+09 | 0.133530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.659152E+09 | 0.998534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.674239E+09 | 0.638370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.818588E+10 | 0.130286E+12 | 65972.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.613430E+09 | 0.523738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.730481E+09 | 0.158386E+11 | 65972.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.679707E+09 | 0.519831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.615824E+09 | 0.595370E+10 | 222191.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.694074E+09 | 0.702899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.660633E+09 | 0.906459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.692342E+09 | 0.127021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.687949E+09 | 0.144102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.725893E+09 | 0.159234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.733077E+09 | 0.157045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.695421E+09 | 0.148470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.694004E+09 | 0.134144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.661749E+09 | 0.999557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.676894E+09 | 0.635626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.821757E+10 | 0.130599E+12 | 222191.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.615824E+09 | 0.519831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.733077E+09 | 0.159234E+11 | 222191.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.675005E+09 | 0.497733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.611572E+09 | 0.575329E+10 | 1190155.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.689188E+09 | 0.680843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.655928E+09 | 0.886542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.687403E+09 | 0.125077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.682412E+09 | 0.142265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.719969E+09 | 0.157503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.726983E+09 | 0.155138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.689860E+09 | 0.146773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.688704E+09 | 0.132357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.657041E+09 | 0.979362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.672211E+09 | 0.613479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.815628E+10 | 0.128244E+12 | 1190155.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.611572E+09 | 0.497733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.726983E+09 | 0.157503E+11 | 1190155.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.107896E+10 | 0.876682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.978766E+09 | 0.104110E+11 | 5255642.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110294E+10 | 0.123635E+11 | 2961117.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105201E+10 | 0.163887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111628E+10 | 0.234556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113895E+10 | 0.268741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123073E+10 | 0.297994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123395E+10 | 0.293478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116559E+10 | 0.277335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113385E+10 | 0.248241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105481E+10 | 0.182093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107433E+10 | 0.108834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133612E+11 | 0.239057E+12 | 8216759.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.978766E+09 | 0.876682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.123395E+10 | 0.297994E+11 | 5255642.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.585050E+09 | 0.449457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530674E+09 | 0.536155E+10 | 2669229.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.597969E+09 | 0.636246E+10 | 1193162.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.570253E+09 | 0.848276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.605222E+09 | 0.121886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.617154E+09 | 0.139763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.667731E+09 | 0.155263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.669013E+09 | 0.152759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.631742E+09 | 0.144323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.614530E+09 | 0.129167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.571669E+09 | 0.944017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.582490E+09 | 0.559676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.724350E+10 | 0.124054E+12 | 3862392.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530674E+09 | 0.449457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.669013E+09 | 0.155263E+11 | 2669229.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.582535E+09 | 0.442844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.528408E+09 | 0.529764E+10 | 3161694.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.595385E+09 | 0.629666E+10 | 1538515.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.567811E+09 | 0.842638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.602769E+09 | 0.121325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.614925E+09 | 0.139263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.665631E+09 | 0.154793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.666767E+09 | 0.152251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.629618E+09 | 0.143864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.612153E+09 | 0.128644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.569224E+09 | 0.938019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.579978E+09 | 0.552346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.721520E+10 | 0.123367E+12 | 4700210.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.528408E+09 | 0.442844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.666767E+09 | 0.154793E+11 | 3161694.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.585052E+09 | 0.429496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530673E+09 | 0.517852E+10 | 5397634.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.597949E+09 | 0.619341E+10 | 3057791.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.570172E+09 | 0.837594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.605246E+09 | 0.121340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.617763E+09 | 0.139757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.669264E+09 | 0.155592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.670001E+09 | 0.152816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.632943E+09 | 0.144627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.614526E+09 | 0.128854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.571467E+09 | 0.932135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.582436E+09 | 0.538099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.724749E+10 | 0.123044E+12 | 8455426.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530673E+09 | 0.429496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.670001E+09 | 0.155592E+11 | 5397634.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.695327E+09 | 0.481291E+10 | 5836089.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.630212E+09 | 0.582750E+10 | 17363917.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.710787E+09 | 0.709237E+10 | 18342759.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.676172E+09 | 0.975236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.714598E+09 | 0.140938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.723014E+09 | 0.162221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.780195E+09 | 0.181022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.780248E+09 | 0.175737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.738511E+09 | 0.167996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.719106E+09 | 0.147641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676962E+09 | 0.105058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.692092E+09 | 0.588951E+10 | 6996220.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.853723E+10 | 0.141436E+12 | 48538986.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.630212E+09 | 0.481291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.780248E+09 | 0.181022E+11 | 18342759.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.158621E+10 | 0.00 | 0.00 | 0.00 | 0.314021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143613E+10 | 0.00 | 0.00 | 0.00 | 0.360295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159340E+10 | 0.00 | 0.00 | 0.00 | 0.432002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153803E+10 | 0.00 | 0.00 | 0.00 | 0.561193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160190E+10 | 0.00 | 0.00 | 0.00 | 0.761872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158814E+10 | 0.00 | 0.00 | 0.00 | 0.841305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.170435E+10 | 0.00 | 0.00 | 0.00 | 0.942879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168894E+10 | 0.00 | 0.00 | 0.00 | 0.911302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162765E+10 | 0.00 | 0.00 | 0.00 | 0.875001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162178E+10 | 0.00 | 0.00 | 0.00 | 0.790216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153790E+10 | 0.00 | 0.00 | 0.00 | 0.586783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159370E+10 | 0.00 | 0.00 | 0.00 | 0.391390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191181E+11 | 0.00 | 0.00 | 0.00 | 0.776826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143613E+10 | 0.00 | 0.00 | 0.00 | 0.314021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170435E+10 | 0.00 | 0.00 | 0.00 | 0.942879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.689378E+09 | 0.00 | 0.00 | 0.00 | 0.173605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.627412E+09 | 0.00 | 0.00 | 0.00 | 0.189950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.707491E+09 | 0.00 | 0.00 | 0.00 | 0.220853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.691924E+09 | 0.00 | 0.00 | 0.00 | 0.277977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.741303E+09 | 0.00 | 0.00 | 0.00 | 0.371139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.750605E+09 | 0.00 | 0.00 | 0.00 | 0.409431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.805649E+09 | 0.00 | 0.00 | 0.00 | 0.457022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.798393E+09 | 0.00 | 0.00 | 0.00 | 0.441440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.769263E+09 | 0.00 | 0.00 | 0.00 | 0.424680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.753682E+09 | 0.00 | 0.00 | 0.00 | 0.386747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.696701E+09 | 0.00 | 0.00 | 0.00 | 0.294498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.699726E+09 | 0.00 | 0.00 | 0.00 | 0.206670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.873153E+10 | 0.00 | 0.00 | 0.00 | 0.385401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.627412E+09 | 0.00 | 0.00 | 0.00 | 0.173605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.805649E+09 | 0.00 | 0.00 | 0.00 | 0.457022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.677040E+09 | 0.00 | 0.00 | 0.00 | 0.126706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.613430E+09 | 0.00 | 0.00 | 0.00 | 0.144630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.691356E+09 | 0.00 | 0.00 | 0.00 | 0.168349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.658035E+09 | 0.00 | 0.00 | 0.00 | 0.216538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.689671E+09 | 0.00 | 0.00 | 0.00 | 0.297543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.685341E+09 | 0.00 | 0.00 | 0.00 | 0.329464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.723147E+09 | 0.00 | 0.00 | 0.00 | 0.368121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.730481E+09 | 0.00 | 0.00 | 0.00 | 0.360577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.692661E+09 | 0.00 | 0.00 | 0.00 | 0.339414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.691323E+09 | 0.00 | 0.00 | 0.00 | 0.308894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.659152E+09 | 0.00 | 0.00 | 0.00 | 0.231890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.674239E+09 | 0.00 | 0.00 | 0.00 | 0.151228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.818588E+10 | 0.00 | 0.00 | 0.00 | 0.304335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.613430E+09 | 0.00 | 0.00 | 0.00 | 0.126706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.730481E+09 | 0.00 | 0.00 | 0.00 | 0.368121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.679707E+09 | 0.00 | 0.00 | 0.00 | 0.125863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.615824E+09 | 0.00 | 0.00 | 0.00 | 0.143993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.694074E+09 | 0.00 | 0.00 | 0.00 | 0.168022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.660633E+09 | 0.00 | 0.00 | 0.00 | 0.217049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.692342E+09 | 0.00 | 0.00 | 0.00 | 0.298567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.687949E+09 | 0.00 | 0.00 | 0.00 | 0.331071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.725893E+09 | 0.00 | 0.00 | 0.00 | 0.370111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.733077E+09 | 0.00 | 0.00 | 0.00 | 0.362180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.695421E+09 | 0.00 | 0.00 | 0.00 | 0.341305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.694004E+09 | 0.00 | 0.00 | 0.00 | 0.310349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.661749E+09 | 0.00 | 0.00 | 0.00 | 0.232243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.676894E+09 | 0.00 | 0.00 | 0.00 | 0.150680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.821757E+10 | 0.00 | 0.00 | 0.00 | 0.305143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.615824E+09 | 0.00 | 0.00 | 0.00 | 0.125863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.733077E+09 | 0.00 | 0.00 | 0.00 | 0.370111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.675005E+09 | 0.00 | 0.00 | 0.00 | 0.120716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.611572E+09 | 0.00 | 0.00 | 0.00 | 0.139418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.689188E+09 | 0.00 | 0.00 | 0.00 | 0.163018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.655928E+09 | 0.00 | 0.00 | 0.00 | 0.212588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.687403E+09 | 0.00 | 0.00 | 0.00 | 0.294263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.682412E+09 | 0.00 | 0.00 | 0.00 | 0.326946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.719969E+09 | 0.00 | 0.00 | 0.00 | 0.366062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.726983E+09 | 0.00 | 0.00 | 0.00 | 0.357830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.689860E+09 | 0.00 | 0.00 | 0.00 | 0.337454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.688704E+09 | 0.00 | 0.00 | 0.00 | 0.306366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.657041E+09 | 0.00 | 0.00 | 0.00 | 0.227793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.672211E+09 | 0.00 | 0.00 | 0.00 | 0.145608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.815628E+10 | 0.00 | 0.00 | 0.00 | 0.299806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.611572E+09 | 0.00 | 0.00 | 0.00 | 0.120716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.726983E+09 | 0.00 | 0.00 | 0.00 | 0.366062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.107896E+10 | 0.00 | 0.00 | 0.00 | 0.214459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.978766E+09 | 0.00 | 0.00 | 0.00 | 0.254458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110294E+10 | 0.00 | 0.00 | 0.00 | 0.297949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105201E+10 | 0.00 | 0.00 | 0.00 | 0.394688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111628E+10 | 0.00 | 0.00 | 0.00 | 0.552735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113895E+10 | 0.00 | 0.00 | 0.00 | 0.620111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123073E+10 | 0.00 | 0.00 | 0.00 | 0.696736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123395E+10 | 0.00 | 0.00 | 0.00 | 0.680933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116559E+10 | 0.00 | 0.00 | 0.00 | 0.641241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113385E+10 | 0.00 | 0.00 | 0.00 | 0.576736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105481E+10 | 0.00 | 0.00 | 0.00 | 0.424674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107433E+10 | 0.00 | 0.00 | 0.00 | 0.259456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133612E+11 | 0.00 | 0.00 | 0.00 | 0.561417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.978766E+09 | 0.00 | 0.00 | 0.00 | 0.214459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.123395E+10 | 0.00 | 0.00 | 0.00 | 0.696736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.585050E+09 | 0.00 | 0.00 | 0.00 | 0.108175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530674E+09 | 0.00 | 0.00 | 0.00 | 0.128969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.597969E+09 | 0.00 | 0.00 | 0.00 | 0.150916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.570253E+09 | 0.00 | 0.00 | 0.00 | 0.201061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.605222E+09 | 0.00 | 0.00 | 0.00 | 0.282689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.617154E+09 | 0.00 | 0.00 | 0.00 | 0.317397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.667731E+09 | 0.00 | 0.00 | 0.00 | 0.357272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.669013E+09 | 0.00 | 0.00 | 0.00 | 0.348785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.631742E+09 | 0.00 | 0.00 | 0.00 | 0.328370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.614530E+09 | 0.00 | 0.00 | 0.00 | 0.295259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.571669E+09 | 0.00 | 0.00 | 0.00 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.582490E+09 | 0.00 | 0.00 | 0.00 | 0.131268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.724350E+10 | 0.00 | 0.00 | 0.00 | 0.286680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530674E+09 | 0.00 | 0.00 | 0.00 | 0.108175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.669013E+09 | 0.00 | 0.00 | 0.00 | 0.357272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.582535E+09 | 0.00 | 0.00 | 0.00 | 0.106608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.528408E+09 | 0.00 | 0.00 | 0.00 | 0.127474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.595385E+09 | 0.00 | 0.00 | 0.00 | 0.149380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.567811E+09 | 0.00 | 0.00 | 0.00 | 0.199734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.602769E+09 | 0.00 | 0.00 | 0.00 | 0.281352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.614925E+09 | 0.00 | 0.00 | 0.00 | 0.316188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.665631E+09 | 0.00 | 0.00 | 0.00 | 0.356099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.666767E+09 | 0.00 | 0.00 | 0.00 | 0.347541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.629618E+09 | 0.00 | 0.00 | 0.00 | 0.327244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.612153E+09 | 0.00 | 0.00 | 0.00 | 0.294007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.569224E+09 | 0.00 | 0.00 | 0.00 | 0.215244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.579978E+09 | 0.00 | 0.00 | 0.00 | 0.129550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.721520E+10 | 0.00 | 0.00 | 0.00 | 0.285042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.528408E+09 | 0.00 | 0.00 | 0.00 | 0.106608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.666767E+09 | 0.00 | 0.00 | 0.00 | 0.356099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.585052E+09 | 0.00 | 0.00 | 0.00 | 0.103558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530673E+09 | 0.00 | 0.00 | 0.00 | 0.124831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.597949E+09 | 0.00 | 0.00 | 0.00 | 0.147131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.570172E+09 | 0.00 | 0.00 | 0.00 | 0.198726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.605246E+09 | 0.00 | 0.00 | 0.00 | 0.281553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.617763E+09 | 0.00 | 0.00 | 0.00 | 0.317396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.669264E+09 | 0.00 | 0.00 | 0.00 | 0.358016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.670001E+09 | 0.00 | 0.00 | 0.00 | 0.348932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.632943E+09 | 0.00 | 0.00 | 0.00 | 0.329039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.614526E+09 | 0.00 | 0.00 | 0.00 | 0.294600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.571467E+09 | 0.00 | 0.00 | 0.00 | 0.214080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.582436E+09 | 0.00 | 0.00 | 0.00 | 0.126318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.724749E+10 | 0.00 | 0.00 | 0.00 | 0.284418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530673E+09 | 0.00 | 0.00 | 0.00 | 0.103558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.670001E+09 | 0.00 | 0.00 | 0.00 | 0.358016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.695327E+09 | 0.00 | 0.00 | 0.00 | 0.117026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.630212E+09 | 0.00 | 0.00 | 0.00 | 0.141720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.710787E+09 | 0.00 | 0.00 | 0.00 | 0.169925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.676172E+09 | 0.00 | 0.00 | 0.00 | 0.232829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.714598E+09 | 0.00 | 0.00 | 0.00 | 0.329820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.723014E+09 | 0.00 | 0.00 | 0.00 | 0.371643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.780195E+09 | 0.00 | 0.00 | 0.00 | 0.420111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.780248E+09 | 0.00 | 0.00 | 0.00 | 0.405181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.738511E+09 | 0.00 | 0.00 | 0.00 | 0.385168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.719106E+09 | 0.00 | 0.00 | 0.00 | 0.340667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676962E+09 | 0.00 | 0.00 | 0.00 | 0.244271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.692092E+09 | 0.00 | 0.00 | 0.00 | 0.139753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.853723E+10 | 0.00 | 0.00 | 0.00 | 0.329811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.630212E+09 | 0.00 | 0.00 | 0.00 | 0.117026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.780248E+09 | 0.00 | 0.00 | 0.00 | 0.420111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.430612E+09 | 0.172214E+10 | 0.00 | 5210035.90 | 15495462.27 | 0.00 | 0.146150E+10 | 0.00 | 0.37 |
February | 0.360892E+09 | 0.195727E+10 | 0.00 | 3261556.56 | 13756885.90 | 7028686.60 | 0.549903E+09 | 0.00 | 0.37 |
March | 0.363819E+09 | 0.305817E+10 | 0.00 | 2923494.64 | 21909710.99 | 1224253.19 | 0.615854E+09 | 0.00 | 0.37 |
April | 12869892.41 | 0.461519E+10 | 0.00 | 1091095.17 | 43912211.31 | 0.00 | 84237004.01 | 0.00 | 0.37 |
May | 0.00 | 0.849511E+10 | 0.00 | 0.00 | 77869162.08 | 0.00 | 0.00 | 0.00 | 0.37 |
June | 0.00 | 0.108519E+11 | 0.00 | 0.00 | 96089073.91 | 0.00 | 0.00 | 0.00 | 0.37 |
July | 0.00 | 0.121458E+11 | 0.00 | 0.00 | 0.120968E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.118720E+11 | 0.00 | 0.00 | 0.107910E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
September | 0.00 | 0.110329E+11 | 0.00 | 0.00 | 88967353.91 | 0.00 | 0.00 | 0.00 | 0.37 |
October | 0.00 | 0.905034E+10 | 0.00 | 38002.64 | 79693188.62 | 0.00 | 17335.45 | 0.00 | 0.37 |
November | 62170156.05 | 0.585565E+10 | 0.00 | 1659738.50 | 50771357.91 | 0.00 | 0.321623E+09 | 0.00 | 0.37 |
December | 0.361051E+09 | 0.281314E+10 | 0.00 | 4240262.24 | 26977736.01 | 0.00 | 0.113380E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.159141E+10 | 0.834696E+11 | 0.00 | 18424185.65 | 0.744320E+09 | 8252939.79 | 0.416693E+10 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.172214E+10 | 0.00 | 0.00 | 13756885.90 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.430612E+09 | 0.121458E+11 | 0.00 | 5210035.90 | 0.120968E+09 | 7028686.60 | 0.146150E+10 | 0.00 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.138713E+09 | 0.847214E+09 | 0.00 | 2877019.56 | 14023523.58 | 0.00 | 0.526936E+09 | 0.00 | 0.30 |
February | 92991067.46 | 0.946921E+09 | 0.00 | 1763610.95 | 12496256.00 | 0.00 | 0.189757E+09 | 0.00 | 0.30 |
March | 0.142287E+09 | 0.139627E+10 | 0.00 | 1536075.08 | 23115231.75 | 0.00 | 0.228907E+09 | 0.00 | 0.31 |
April | 4239809.08 | 0.208849E+10 | 0.00 | 532372.68 | 36869562.51 | 0.00 | 28280535.04 | 0.00 | 0.31 |
May | 0.00 | 0.380918E+10 | 0.00 | 0.00 | 54768203.47 | 0.00 | 0.00 | 0.00 | 0.32 |
June | 0.00 | 0.487603E+10 | 0.00 | 0.00 | 61778206.39 | 0.00 | 0.00 | 0.00 | 0.33 |
July | 0.00 | 0.549680E+10 | 0.00 | 0.00 | 73635616.85 | 0.00 | 0.00 | 0.00 | 0.33 |
August | 0.00 | 0.535229E+10 | 0.00 | 0.00 | 67518227.09 | 0.00 | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.498785E+10 | 0.00 | 0.00 | 59226586.92 | 0.00 | 0.00 | 0.00 | 0.33 |
October | 0.00 | 0.407402E+10 | 0.00 | 0.00 | 56765760.22 | 0.00 | 0.00 | 0.00 | 0.32 |
November | 26878573.86 | 0.266020E+10 | 0.00 | 882014.52 | 39743665.22 | 0.00 | 78033005.80 | 0.00 | 0.31 |
December | 0.102605E+09 | 0.129065E+10 | 0.00 | 2330019.29 | 26453392.75 | 0.00 | 0.414084E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.507715E+09 | 0.378259E+11 | 0.00 | 9921112.06 | 0.526394E+09 | 0.00 | 0.146600E+10 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.847214E+09 | 0.00 | 0.00 | 12496256.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.142287E+09 | 0.549680E+10 | 0.00 | 2877019.56 | 73635616.85 | 0.00 | 0.526936E+09 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.263270E+09 | 0.648778E+09 | 0.00 | 1860416.00 | 27538689.78 | 0.00 | 0.435590E+09 | 0.00 | 0.28 |
February | 0.163045E+09 | 0.767458E+09 | 0.00 | 971568.07 | 31259114.15 | 0.00 | 0.142601E+09 | 0.00 | 0.28 |
March | 0.224012E+09 | 0.106514E+10 | 0.00 | 982217.63 | 64048206.62 | 0.00 | 0.166829E+09 | 0.00 | 0.28 |
April | 13345120.70 | 0.163064E+10 | 0.00 | 495658.84 | 0.101310E+09 | 0.00 | 37593976.06 | 0.00 | 0.28 |
May | 26256.13 | 0.297171E+10 | 0.00 | 32067.14 | 0.190749E+09 | 0.00 | 68318.31 | 0.00 | 0.28 |
June | 0.00 | 0.374090E+10 | 0.00 | 25088.04 | 0.262138E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
July | 0.00 | 0.426893E+10 | 0.00 | 0.00 | 0.281554E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.419322E+10 | 0.00 | 14126.20 | 0.275074E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
September | 0.00 | 0.379586E+10 | 0.00 | 6406.54 | 0.251004E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
October | 136962.52 | 0.312928E+10 | 0.00 | 72277.71 | 0.197181E+09 | 0.00 | 139282.08 | 0.00 | 0.28 |
November | 46964888.44 | 0.203980E+10 | 0.00 | 685420.28 | 0.134616E+09 | 0.00 | 66340570.35 | 0.00 | 0.28 |
December | 0.202944E+09 | 0.930284E+09 | 0.00 | 1718564.33 | 49133882.16 | 0.00 | 0.350339E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.913745E+09 | 0.291820E+11 | 0.00 | 6863810.78 | 0.186560E+10 | 0.00 | 0.119950E+10 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.648778E+09 | 0.00 | 0.00 | 27538689.78 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.263270E+09 | 0.426893E+10 | 0.00 | 1860416.00 | 0.281554E+09 | 0.00 | 0.435590E+09 | 0.00 | 0.29 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.269731E+09 | 0.646677E+09 | 0.00 | 1827207.06 | 27482946.43 | 0.00 | 0.429761E+09 | 0.00 | 0.28 |
February | 0.164095E+09 | 0.763772E+09 | 0.00 | 967447.94 | 31483922.65 | 0.00 | 0.141330E+09 | 0.00 | 0.28 |
March | 0.227383E+09 | 0.106415E+10 | 0.00 | 976536.34 | 63943937.46 | 0.00 | 0.163545E+09 | 0.00 | 0.28 |
April | 13147897.87 | 0.163239E+10 | 0.00 | 503022.88 | 0.101292E+09 | 0.00 | 37528395.84 | 0.00 | 0.28 |
May | 26528.90 | 0.297712E+10 | 0.00 | 34768.49 | 0.190933E+09 | 0.00 | 68491.42 | 0.00 | 0.28 |
June | 0.00 | 0.375323E+10 | 0.00 | 26021.73 | 0.260209E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
July | 0.00 | 0.428414E+10 | 0.00 | 0.00 | 0.278635E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.420551E+10 | 0.00 | 15055.93 | 0.272971E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
September | 0.00 | 0.380879E+10 | 0.00 | 7030.94 | 0.250527E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
October | 134958.62 | 0.313798E+10 | 0.00 | 74765.86 | 0.197602E+09 | 0.00 | 136871.05 | 0.00 | 0.28 |
November | 45456934.02 | 0.204159E+10 | 0.00 | 689456.39 | 0.134846E+09 | 0.00 | 67689932.95 | 0.00 | 0.28 |
December | 0.206652E+09 | 0.928329E+09 | 0.00 | 1698324.87 | 49004435.97 | 0.00 | 0.348045E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.926627E+09 | 0.292437E+11 | 0.00 | 6819638.45 | 0.185893E+10 | 0.00 | 0.118811E+10 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.646677E+09 | 0.00 | 0.00 | 27482946.43 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.269731E+09 | 0.428414E+10 | 0.00 | 1827207.06 | 0.278635E+09 | 0.00 | 0.429761E+09 | 0.00 | 0.29 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.288167E+09 | 0.629563E+09 | 0.00 | 1687427.34 | 27058201.82 | 0.00 | 0.416725E+09 | 0.00 | 0.28 |
February | 0.173804E+09 | 0.743252E+09 | 0.00 | 935779.79 | 31416091.32 | 0.00 | 0.133081E+09 | 0.00 | 0.28 |
March | 0.241131E+09 | 0.104129E+10 | 0.00 | 912477.33 | 63009259.87 | 0.00 | 0.150715E+09 | 0.00 | 0.28 |
April | 15446435.22 | 0.160837E+10 | 0.00 | 477365.74 | 0.100152E+09 | 0.00 | 36234942.78 | 0.00 | 0.28 |
May | 41739.79 | 0.294934E+10 | 0.00 | 29787.46 | 0.190763E+09 | 0.00 | 65402.71 | 0.00 | 0.28 |
June | 0.00 | 0.372585E+10 | 0.00 | 24717.53 | 0.260545E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
July | 0.00 | 0.425827E+10 | 0.00 | 0.00 | 0.280953E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.417509E+10 | 0.00 | 14171.03 | 0.275815E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
September | 0.00 | 0.378506E+10 | 0.00 | 6444.45 | 0.250112E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
October | 118144.52 | 0.311465E+10 | 0.00 | 70310.46 | 0.196130E+09 | 0.00 | 168591.96 | 0.00 | 0.28 |
November | 48225104.03 | 0.201548E+10 | 0.00 | 647049.00 | 0.134728E+09 | 0.00 | 66842981.70 | 0.00 | 0.28 |
December | 0.227188E+09 | 0.909319E+09 | 0.00 | 1583233.39 | 48297890.32 | 0.00 | 0.335983E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.994120E+09 | 0.289555E+11 | 0.00 | 6388763.50 | 0.185898E+10 | 0.00 | 0.113982E+10 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.629563E+09 | 0.00 | 0.00 | 27058201.82 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.288167E+09 | 0.425827E+10 | 0.00 | 1687427.34 | 0.280953E+09 | 0.00 | 0.416725E+09 | 0.00 | 0.29 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.517776E+09 | 0.124028E+10 | 0.00 | 3099276.82 | 28308078.95 | 0.00 | 0.981428E+09 | 0.00 | 0.29 |
February | 0.317392E+09 | 0.145770E+10 | 0.00 | 2092694.37 | 32405770.87 | 1575592.41 | 0.273908E+09 | 0.00 | 0.29 |
March | 0.423120E+09 | 0.209478E+10 | 0.00 | 2005284.74 | 53643748.81 | 0.00 | 0.403986E+09 | 0.00 | 0.30 |
April | 10287234.53 | 0.333156E+10 | 0.00 | 941964.83 | 95560564.73 | 0.00 | 79769219.81 | 0.00 | 0.30 |
May | 0.00 | 0.624366E+10 | 0.00 | 7357.48 | 0.143170E+09 | 0.00 | 16357.52 | 0.00 | 0.30 |
June | 0.00 | 0.799756E+10 | 0.00 | 43570.22 | 0.182157E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.912394E+10 | 0.00 | 0.00 | 0.249874E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.896398E+10 | 0.00 | 0.00 | 0.196477E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.813276E+10 | 0.00 | 0.00 | 0.207586E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
October | 6840.80 | 0.661582E+10 | 0.00 | 49787.64 | 0.165071E+09 | 0.00 | 31489.61 | 0.00 | 0.30 |
November | 53650798.10 | 0.428445E+10 | 0.00 | 1154984.30 | 0.102039E+09 | 0.00 | 0.140275E+09 | 0.00 | 0.29 |
December | 0.390513E+09 | 0.181848E+10 | 0.00 | 2869699.18 | 62379168.50 | 0.00 | 0.858622E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.171275E+10 | 0.613050E+11 | 0.00 | 12264619.57 | 0.151867E+10 | 1575592.41 | 0.273804E+10 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.124028E+10 | 0.00 | 0.00 | 28308078.95 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.517776E+09 | 0.912394E+10 | 0.00 | 3099276.82 | 0.249874E+09 | 1575592.41 | 0.981428E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.280051E+09 | 0.613448E+09 | 0.00 | 1507903.16 | 14408762.64 | 0.00 | 0.463437E+09 | 0.00 | 0.29 |
February | 0.160447E+09 | 0.722897E+09 | 0.00 | 1040926.54 | 15697728.40 | 786270.57 | 0.131827E+09 | 0.00 | 0.29 |
March | 0.219390E+09 | 0.103839E+10 | 0.00 | 982670.48 | 25845410.99 | 0.00 | 0.188934E+09 | 0.00 | 0.30 |
April | 5143295.28 | 0.165580E+10 | 0.00 | 475913.27 | 47164692.32 | 0.00 | 39231341.10 | 0.00 | 0.30 |
May | 0.00 | 0.310881E+10 | 0.00 | 3604.93 | 69158354.42 | 0.00 | 10940.47 | 0.00 | 0.30 |
June | 0.00 | 0.398185E+10 | 0.00 | 25419.74 | 86597512.19 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.454334E+10 | 0.00 | 0.00 | 0.122875E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.446080E+10 | 0.00 | 0.00 | 97147870.92 | 0.00 | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.404615E+10 | 0.00 | 0.00 | 0.102311E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
October | 786.46 | 0.329221E+10 | 0.00 | 26472.64 | 81411154.12 | 0.00 | 14802.34 | 0.00 | 0.30 |
November | 27688272.40 | 0.212866E+10 | 0.00 | 578431.41 | 48932883.86 | 0.00 | 68353313.18 | 0.00 | 0.29 |
December | 0.196534E+09 | 0.899661E+09 | 0.00 | 1395764.11 | 30205214.89 | 0.00 | 0.425382E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.889254E+09 | 0.304920E+11 | 0.00 | 6037106.28 | 0.741755E+09 | 786270.57 | 0.131719E+10 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.613448E+09 | 0.00 | 0.00 | 14408762.64 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.280051E+09 | 0.454334E+10 | 0.00 | 1507903.16 | 0.122875E+09 | 786270.57 | 0.463437E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.293170E+09 | 0.607420E+09 | 0.00 | 1459040.38 | 14733527.40 | 0.00 | 0.451620E+09 | 0.00 | 0.29 |
February | 0.163260E+09 | 0.715478E+09 | 0.00 | 1034044.86 | 16324688.09 | 786383.43 | 0.129884E+09 | 0.00 | 0.29 |
March | 0.223104E+09 | 0.103091E+10 | 0.00 | 960628.21 | 25686411.87 | 0.00 | 0.185684E+09 | 0.00 | 0.30 |
April | 5143392.81 | 0.164762E+10 | 0.00 | 471099.36 | 47476194.37 | 0.00 | 39515882.59 | 0.00 | 0.30 |
May | 0.00 | 0.310012E+10 | 0.00 | 3397.97 | 69251447.80 | 0.00 | 10268.09 | 0.00 | 0.30 |
June | 0.00 | 0.397391E+10 | 0.00 | 25139.41 | 86679781.70 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.453653E+10 | 0.00 | 0.00 | 0.122710E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.445304E+10 | 0.00 | 0.00 | 96973584.97 | 0.00 | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.403958E+10 | 0.00 | 0.00 | 0.101965E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
October | 878.99 | 0.328399E+10 | 0.00 | 26193.63 | 81926801.22 | 0.00 | 15015.95 | 0.00 | 0.30 |
November | 27779349.34 | 0.212066E+10 | 0.00 | 571871.56 | 48517751.26 | 0.00 | 68793521.18 | 0.00 | 0.29 |
December | 0.202578E+09 | 0.892604E+09 | 0.00 | 1358477.04 | 30262402.98 | 0.00 | 0.422399E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.915036E+09 | 0.304019E+11 | 0.00 | 5909892.43 | 0.742507E+09 | 786383.43 | 0.129792E+10 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.607420E+09 | 0.00 | 0.00 | 14733527.40 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.293170E+09 | 0.453653E+10 | 0.00 | 1459040.38 | 0.122710E+09 | 786383.43 | 0.451620E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.332462E+09 | 0.595458E+09 | 0.00 | 1342704.23 | 15222786.03 | 0.00 | 0.414179E+09 | 0.00 | 0.29 |
February | 0.160529E+09 | 0.701147E+09 | 0.00 | 982397.33 | 17388764.93 | 5030002.02 | 0.129330E+09 | 0.00 | 0.29 |
March | 0.224591E+09 | 0.101796E+10 | 0.00 | 915087.56 | 25438935.19 | 0.00 | 0.184658E+09 | 0.00 | 0.30 |
April | 7521406.05 | 0.163885E+10 | 0.00 | 455969.50 | 46622287.25 | 0.00 | 37499596.18 | 0.00 | 0.30 |
May | 0.00 | 0.309733E+10 | 0.00 | 2484.10 | 68982398.15 | 0.00 | 6572.56 | 0.00 | 0.30 |
June | 0.00 | 0.397904E+10 | 0.00 | 23399.79 | 87735667.56 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.454586E+10 | 0.00 | 0.00 | 0.124078E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.445889E+10 | 0.00 | 0.00 | 98442294.10 | 0.00 | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.405000E+10 | 0.00 | 0.00 | 0.101980E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
October | 0.00 | 0.328588E+10 | 0.00 | 25549.55 | 81498215.94 | 0.00 | 14597.93 | 0.00 | 0.30 |
November | 29812042.40 | 0.211194E+10 | 0.00 | 555841.18 | 48563051.11 | 0.00 | 67662647.82 | 0.00 | 0.29 |
December | 0.214571E+09 | 0.880100E+09 | 0.00 | 1247557.46 | 30562220.06 | 0.00 | 0.417138E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.969487E+09 | 0.303625E+11 | 0.00 | 5550990.70 | 0.746515E+09 | 5030002.02 | 0.125049E+10 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.595458E+09 | 0.00 | 0.00 | 15222786.03 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.332462E+09 | 0.454586E+10 | 0.00 | 1342704.23 | 0.124078E+09 | 5030002.02 | 0.417138E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.335555E+09 | 0.627522E+09 | 0.00 | 1394475.84 | 15372109.87 | 3652687.56 | 0.381828E+09 | 0.00 | 0.29 |
February | 0.149458E+09 | 0.733312E+09 | 0.00 | 979222.94 | 13983584.63 | 7851097.08 | 0.117532E+09 | 0.00 | 0.29 |
March | 0.193575E+09 | 0.106974E+10 | 0.00 | 1010846.38 | 21533050.58 | 11333910.20 | 0.198262E+09 | 0.00 | 0.30 |
April | 7494547.05 | 0.173708E+10 | 0.00 | 493638.33 | 39899446.94 | 0.00 | 33934007.36 | 0.00 | 0.30 |
May | 0.00 | 0.324969E+10 | 0.00 | 46609.34 | 61742171.90 | 0.00 | 1289.21 | 0.00 | 0.30 |
June | 0.00 | 0.418339E+10 | 0.00 | 24463.47 | 79086672.45 | 0.00 | 4058.73 | 0.00 | 0.30 |
July | 0.00 | 0.479012E+10 | 0.00 | 0.00 | 0.113016E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.466243E+10 | 0.00 | 8570.81 | 89512220.72 | 0.00 | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.426022E+10 | 0.00 | 896.33 | 93394410.43 | 0.00 | 0.00 | 0.00 | 0.30 |
October | 18760.26 | 0.343623E+10 | 0.00 | 133796.62 | 74418400.11 | 0.00 | 40637.65 | 0.00 | 0.30 |
November | 27055164.70 | 0.220862E+10 | 0.00 | 573597.51 | 44672585.57 | 0.00 | 58522521.04 | 0.00 | 0.29 |
December | 0.216105E+09 | 0.922478E+09 | 0.00 | 1158871.29 | 28537489.34 | 4663191.78 | 0.397550E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.929261E+09 | 0.318808E+11 | 0.00 | 5824988.86 | 0.675168E+09 | 27500886.62 | 0.118767E+10 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.627522E+09 | 0.00 | 0.00 | 13983584.63 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.335555E+09 | 0.479012E+10 | 0.00 | 1394475.84 | 0.113016E+09 | 11333910.20 | 0.397550E+09 | 0.00 | 0.30 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:39:19
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.184910E+12 | -169071333.2 | 0.00 | 0.107673E+11 | 0.771975E+11 |
February | 0.203918E+12 | -0.596980E+10 | 0.00 | 0.568148E+09 | 0.898479E+11 |
March | 0.284069E+12 | -0.849667E+10 | 0.00 | -0.718237E+10 | 0.106875E+12 |
April | 0.316705E+12 | -0.192873E+11 | 0.00 | -0.253784E+11 | 0.140169E+12 |
May | 0.310359E+12 | -0.352169E+11 | 0.00 | -0.537987E+11 | 0.196997E+12 |
June | 0.282569E+12 | -0.425201E+11 | 0.00 | -0.737384E+11 | 0.223124E+12 |
July | 0.309350E+12 | -0.485978E+11 | 0.00 | -0.819711E+11 | 0.248183E+12 |
August | 0.325296E+12 | -0.473065E+11 | 0.00 | -0.820022E+11 | 0.242876E+12 |
September | 0.249706E+12 | -0.437872E+11 | 0.00 | -0.732678E+11 | 0.230818E+12 |
October | 0.237229E+12 | -0.366022E+11 | 0.00 | -0.591651E+11 | 0.207326E+12 |
November | 0.172247E+12 | -0.221130E+11 | 0.00 | -0.299339E+11 | 0.152871E+12 |
December | 0.182131E+12 | -0.557291E+10 | 0.00 | 0.365633E+09 | 0.954266E+11 |
Annual Sum or Average | 0.305849E+13 | -0.315639E+12 | 0.00 | -0.474737E+12 | 0.201171E+13 |
Minimum of Months | 0.172247E+12 | -0.485978E+11 | 0.00 | -0.820022E+11 | 0.771975E+11 |
Maximum of Months | 0.325296E+12 | -169071333.2 | 0.00 | 0.107673E+11 | 0.248183E+12 |