Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:39
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 08:39:22
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1057.06 | 505.69 | 505.69 |
Net Site Energy | 989.97 | 473.60 | 473.60 |
Total Source Energy | 3339.47 | 1597.59 | 1597.59 |
Net Source Energy | 3127.01 | 1495.95 | 1495.95 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 421.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 125.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 58.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1053.11 | 3.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 3.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 421.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 40.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 125.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 58.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 421.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 40.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 125.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 58.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 152.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 290.01 | 1.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 503.80 | 1.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 152.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 290.01 | 1.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 503.80 | 1.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 70.047 | 6.65 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -2.96 | -0.3 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 67.087 | 6.37 |
Electricity Coming From Utility | 986.019 | 93.63 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 986.019 | 93.63 |
Total On-Site and Utility Electric Sources | 1053.106 | 100.00 |
Total Electricity End Uses | 1053.106 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1155.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:39 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 11.5884 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 13.7658 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 7.5320 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 10.0873 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 10.0873 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 11.5884 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 13.7658 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 12.9393 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 12.9393 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 12.9393 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 7.5320 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 7.5557 | 6.19 | 4.3000 | |
Total | 2090.32 | 10.0873 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 10.0873 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 10.0873 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 01-JUL-12:00 | 02-JAN-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 109187.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 74292.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12273.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7530.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 119852.83 | 109187.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 109187.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 74292.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 12273.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7530.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1335.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 879.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 129.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 398.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 185.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3335.19 | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 638.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 420.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 190.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 88.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1595.54 | 2.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 638.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 420.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 190.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 88.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1595.54 | 2.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.68 |
SMSTORE1 DIRECT AIR | 1.36 |
SMSTORE2 DIRECT AIR | 1.37 |
SMSTORE3 DIRECT AIR | 1.37 |
SMSTORE4 DIRECT AIR | 1.37 |
LGSTORE2 DIRECT AIR | 2.46 |
SMSTORE5 DIRECT AIR | 1.30 |
SMSTORE6 DIRECT AIR | 1.30 |
SMSTORE7 DIRECT AIR | 1.30 |
SMSTORE8 DIRECT AIR | 1.53 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.68 | 2.68 | 2.68 | 2.68 | 2.68 | 2.68 | 1.00 | 1.00 | 2.68 |
PSZ-AC_2:2 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.00 | 1.000000 | 1.36 |
PSZ-AC_3:3 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.00 | 1.00 | 1.37 |
PSZ-AC_4:4 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.00 | 1.000000 | 1.37 |
PSZ-AC_5:5 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.00 | 1.00 | 1.37 |
PSZ-AC_6:6 | 2.46 | 2.46 | 2.46 | 2.46 | 2.46 | 2.46 | 1.00 | 1.00 | 2.46 |
PSZ-AC_7:7 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.00 | 1.30 |
PSZ-AC_8:8 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.00 | 1.30 |
PSZ-AC_9:9 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.00 | 1.30 |
PSZ-AC_10:10 | 1.53 | 1.53 | 1.53 | 1.53 | 1.53 | 1.53 | 1.00 | 1.000000 | 1.53 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.68 |
PSZ-AC_2:2_OA_CONTROLLER | 1.36 |
PSZ-AC_3:3_OA_CONTROLLER | 1.37 |
PSZ-AC_4:4_OA_CONTROLLER | 1.37 |
PSZ-AC_5:5_OA_CONTROLLER | 1.37 |
PSZ-AC_6:6_OA_CONTROLLER | 2.46 |
PSZ-AC_7:7_OA_CONTROLLER | 1.30 |
PSZ-AC_8:8_OA_CONTROLLER | 1.30 |
PSZ-AC_9:9_OA_CONTROLLER | 1.30 |
PSZ-AC_10:10_OA_CONTROLLER | 1.53 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.68 | 2869.72 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.36 | 1505.39 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.37 | 1516.57 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.37 | 1521.60 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.37 | 1514.19 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.46 | 2629.65 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.30 | 1441.00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.30 | 1436.48 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.30 | 1444.34 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.53 | 1639.36 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.68 | 2.68 | 2.68 | 1.77 | 62497.78 | 66944.00 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.36 | 1.36 | 1.36 | 0.897391 | 31660.18 | 33889.90 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.37 | 1.37 | 1.37 | 0.904061 | 31848.72 | 34115.08 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.37 | 1.37 | 1.37 | 0.907057 | 31933.14 | 34216.23 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.37 | 1.37 | 1.37 | 0.902639 | 31808.70 | 34067.08 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.46 | 2.46 | 2.46 | 1.62 | 58269.97 | 61945.03 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 0.859011 | 30577.29 | 32594.18 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 0.856312 | 30500.96 | 32503.07 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 0.860998 | 30633.52 | 32661.26 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.53 | 1.53 | 1.53 | 1.01 | 34672.42 | 37730.62 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.68 | 1.34 | 1.79 | 62497.78 | 31248.89 | 0.721160 | 0.721160 |
PSZ-AC_2:2 COOLING COIL | 1.36 | 0.679842 | 0.906453 | 31660.18 | 15830.09 | 0.721370 | 0.721370 |
PSZ-AC_3:3 COOLING COIL | 1.37 | 0.684895 | 0.913193 | 31848.72 | 15924.36 | 0.721750 | 0.721750 |
PSZ-AC_4:4 COOLING COIL | 1.37 | 0.687164 | 0.916220 | 31933.14 | 15966.57 | 0.721930 | 0.721930 |
PSZ-AC_5:5 COOLING COIL | 1.37 | 0.683817 | 0.911753 | 31808.70 | 15904.35 | 0.721670 | 0.721670 |
PSZ-AC_6:6 COOLING COIL | 2.46 | 1.23 | 1.64 | 58269.97 | 29134.99 | 0.715670 | 0.715670 |
PSZ-AC_7:7 COOLING COIL | 1.30 | 0.650766 | 0.867687 | 30577.29 | 15288.65 | 0.719050 | 0.719050 |
PSZ-AC_8:8 COOLING COIL | 1.30 | 0.648721 | 0.864960 | 30500.96 | 15250.48 | 0.718880 | 0.718880 |
PSZ-AC_9:9 COOLING COIL | 1.30 | 0.652271 | 0.869693 | 30633.52 | 15316.76 | 0.719180 | 0.719180 |
PSZ-AC_10:10 COOLING COIL | 1.53 | 0.766025 | 1.02 | 34672.42 | 17336.21 | 0.730920 | 0.730920 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 66944.00 |
PSZ-AC_2:2 HEATING COIL | 33889.90 |
PSZ-AC_3:3 HEATING COIL | 34115.08 |
PSZ-AC_4:4 HEATING COIL | 34216.23 |
PSZ-AC_5:5 HEATING COIL | 34067.08 |
PSZ-AC_6:6 HEATING COIL | 61945.03 |
PSZ-AC_7:7 HEATING COIL | 32594.18 |
PSZ-AC_8:8 HEATING COIL | 32503.07 |
PSZ-AC_9:9 HEATING COIL | 32661.26 |
PSZ-AC_10:10 HEATING COIL | 37730.62 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 11.588 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.888 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 13.766 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 18.066 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 7.532 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.832 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 2630.745 | 7.551 | 46.768 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2630.745 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1406.513 | 4.037 | 25.004 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1406.513 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1319.493 | 7.575 | 46.916 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1319.493 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1078.411 | 6.191 | 38.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1078.411 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 2624.046 | 7.532 | 46.649 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2624.046 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7383 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.27626373E-12 | 0.13670118E-14 | -0.80430638E-13 | 0.78416590E-16 |
23 | 6 | 0.25658824E-07 | 0.27941242E-09 | 0.59030768E-08 | -0.11909973E-12 |
24 | 5 | -0.17468948E-03 | 0.24402707E-05 | -0.90039107E-04 | 0.58437388E-08 |
25 | 4 | 0.27392503 | 0.12091412E-02 | 0.93138911E-01 | -0.31018751E-04 |
26 | 3 | -6.9050330 | 0.38055846E-01 | -2.2317352 | 0.27239655E-01 |
27 | 2 | 39.679098 | 0.13717309 | 14.824430 | -0.32006664 |
28 | 1 | -79.631803 | 0.62641324E-01 | -28.746304 | 1.0591428 |
29 | 0 | 46.824345 | 0.12749544E-02 | 16.300917 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 35 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 29602.27247 | 35522.72697 | 2.23489 | 2.68186 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 41.80600 | 9.15758E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 15229.82811 | 18275.79374 | 0.67355 | 0.80827 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 15008.14178 | 18009.77013 | 1.13307 | 1.35968 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | 42.00000 | 9.15790E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 7490.88406 | 8989.06087 | 0.33129 | 0.39755 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 15119.68687 | 18143.62425 | 1.14149 | 1.36979 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 7556.86701 | 9068.24041 | 0.33421 | 0.40105 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 15169.79292 | 18203.75150 | 1.14527 | 1.37433 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 7626.65479 | 9151.98575 | 0.33729 | 0.40475 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 15095.90792 | 18115.08951 | 1.13970 | 1.36763 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 7774.55428 | 9329.46514 | 0.34384 | 0.41260 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 27126.00250 | 32551.20299 | 2.04793 | 2.45751 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 14744.79915 | 17693.75898 | 0.65210 | 0.78253 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 14366.26529 | 17239.51835 | 1.08461 | 1.30153 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 7987.77824 | 9585.33388 | 0.35327 | 0.42392 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 14321.13227 | 17185.35872 | 1.08120 | 1.29744 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 7991.59268 | 9589.91121 | 0.35343 | 0.42412 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 14399.49828 | 17279.39794 | 1.08712 | 1.30454 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 8242.98438 | 9891.58125 | 0.36455 | 0.43746 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 16911.18927 | 20293.42712 | 1.27671 | 1.53205 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 41.51500 | 9.15709E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 9749.92914 | 11699.91497 | 0.43120 | 0.51744 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 43846.86 | 2.68186 | 2.68186 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 25196.92 | 0.80827 | 0.80827 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 22175.35 | 1.35968 | 1.35968 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 12451.72 | 0.39755 | 0.39755 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 22307.50 | 1.36979 | 1.36979 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 12529.74 | 0.40105 | 0.40105 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 22366.86 | 1.37433 | 1.37433 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 12612.27 | 0.40475 | 0.40475 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 22279.33 | 1.36763 | 1.36763 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 12787.16 | 0.41260 | 0.41260 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 40926.76 | 2.45751 | 2.45751 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 24623.37 | 0.78253 | 0.78253 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 21414.93 | 1.30153 | 1.30153 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 13039.31 | 0.42392 | 0.42392 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 21361.47 | 1.29744 | 1.29744 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 13043.82 | 0.42412 | 0.42412 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 21454.30 | 1.30454 | 1.30454 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 13341.09 | 0.43746 | 0.43746 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 24321.63 | 1.53205 | 1.53205 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 15123.07 | 0.51744 | 0.51744 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.68186 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.35968 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.36979 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.37433 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.36763 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.45751 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.30153 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.29744 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.30454 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.53205 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.68186 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.68186 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.68186 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.68186 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.68186 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.68186 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.35968 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35968 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.35968 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.35968 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.35968 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.35968 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.36979 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36979 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.36979 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36979 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.36979 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.36979 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.37433 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37433 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.37433 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.37433 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.37433 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.37433 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.36763 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36763 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.36763 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36763 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.36763 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.36763 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.45751 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.45751 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.45751 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.45751 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.45751 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.45751 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.30153 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.30153 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.30153 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.30153 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.30153 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.30153 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.29744 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.29744 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.29744 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.29744 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.29744 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.29744 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.30454 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.30454 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.30454 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.30454 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.30454 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.30454 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.53205 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.53205 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.53205 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.53205 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.53205 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.53205 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.68186 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.35968 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.36979 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.37433 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.36763 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.45751 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.30153 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.29744 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.30454 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.53205 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.68186 |
102 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.68186 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2869.72130 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.68186 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.68186 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.68186 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.77003 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.68186 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.34093 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.78791 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 62497.78000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 31248.89000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72116 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72116 |
115 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 62497.78000 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 66944.00426 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
119 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 66944.00426 |
120 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.35968 |
121 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.35968 |
122 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1505.38610 |
123 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.35968 |
124 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.35968 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.35968 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.89739 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.35968 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67984 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.90645 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31660.18000 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15830.09000 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72137 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72137 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31660.18000 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33889.90225 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
138 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 33889.90225 |
139 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.36979 |
140 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.36979 |
141 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1516.57433 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.36979 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.36979 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.36979 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90406 |
146 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.36979 |
147 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68489 |
148 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.91319 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31848.72000 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15924.36000 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72175 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72175 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31848.72000 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34115.08472 |
155 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
157 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 34115.08472 |
158 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.37433 |
159 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.37433 |
160 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1521.60014 |
161 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.37433 |
162 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.37433 |
163 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.37433 |
164 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90706 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.37433 |
166 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68716 |
167 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.91622 |
168 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31933.14000 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15966.57000 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72193 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72193 |
172 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31933.14000 |
173 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34216.23232 |
174 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
176 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 34216.23232 |
177 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.36763 |
178 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.36763 |
179 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1514.18894 |
180 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.36763 |
181 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.36763 |
182 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.36763 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90264 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.36763 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68382 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.91175 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31808.70000 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15904.35000 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72167 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72167 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31808.70000 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34067.07909 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
194 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
195 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 34067.07909 |
196 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.45751 |
197 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.45751 |
198 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2629.65470 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.45751 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.45751 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.45751 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.62196 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.45751 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.22876 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.63834 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 58269.97000 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 29134.98500 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71567 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71567 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 58269.97000 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 61945.02829 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
213 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
214 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 61945.02829 |
215 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.30153 |
216 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.30153 |
217 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1441.00225 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.30153 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.30153 |
220 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.30153 |
221 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85901 |
222 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.30153 |
223 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65077 |
224 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.86769 |
225 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30577.29000 |
226 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15288.64500 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71905 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71905 |
229 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30577.29000 |
230 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32594.17653 |
231 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
232 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
233 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 32594.17653 |
234 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.29744 |
235 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.29744 |
236 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1436.47522 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.29744 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.29744 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.29744 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85631 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.29744 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64872 |
243 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.86496 |
244 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30500.96000 |
245 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15250.48000 |
246 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71888 |
247 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71888 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30500.96000 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32503.06813 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
251 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
252 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 32503.06813 |
253 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.30454 |
254 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.30454 |
255 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1444.33538 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.30454 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.30454 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.30454 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.86100 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.30454 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65227 |
262 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.86969 |
263 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30633.52000 |
264 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15316.76000 |
265 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71918 |
266 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71918 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30633.52000 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32661.25819 |
269 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
270 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
271 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 32661.25819 |
272 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.53205 |
273 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.53205 |
274 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1639.36495 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.53205 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.53205 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.53205 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.01115 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.53205 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.76602 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02137 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34672.42000 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17336.21000 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73092 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73092 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34672.42000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37730.62448 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 37730.62448 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 60384.6 | 12.15 | 12.15 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 30588.8 | 12.33 | 12.33 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 30769.4 | 12.33 | 12.33 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 30850.3 | 12.32 | 12.32 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 30731.1 | 12.33 | 12.33 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 56332.9 | 12.18 | 12.18 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 29551.6 | 12.35 | 12.35 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 29478.5 | 12.35 | 12.35 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 29605.5 | 12.35 | 12.35 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 33465.9 | 12.27 | 12.27 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 4.8426653214E-002 | 0.1547571680 | Pass | Pass | 0.2509124886 | 1.3934062798 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 6.6247031514E-002 | 0.1057381183 | Pass | Pass | 8.4481001255E-002 | 0.2479876421 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 4.1499862712E-002 | 0.1522178300 | Pass | Pass | 0.1649924617 | 0.7523505526 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.7841632601E-002 | 0.1653388481 | Pass | Pass | 0.3590404866 | 2.1169995786 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.7805652373E-002 | 0.1794351225 | Pass | Pass | 0.4197800459 | 2.3327180401 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.3077036180E-002 | 0.2148583783 | Pass | Pass | 0.2157967255 | 0.6545570301 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.3526711676E-002 | 0.2201380846 | Pass | Pass | 0.1678679594 | 0.6757829391 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.3219209939E-002 | 0.2234165563 | Pass | Pass | 0.1761707757 | 0.7147371400 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.7147729439E-002 | 0.2415396378 | Pass | Pass | 0.1768401541 | 0.8441705280 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 5.7652597151E-002 | 0.2977376032 | Pass | Pass | 7.7484927587 | 91.1563321549 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2593.55 | -290.8 | 0.00 | -434.4 | 2056.46 | 3924.84 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.231 | 0.254 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.860 | 0.231 | 0.254 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.860 | 0.231 | 0.254 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 7.5512 | 348.39 | 2630.74 | LightsWired | LTG_SCH_BASE_LPD1 | 81.37 | 168.00 | 80.49 | 0.0000 | Y | 39.75 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 4.0372 | 348.39 | 1406.51 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 24.96 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 7.5749 | 174.19 | 1319.49 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 82.90 | 168.00 | 81.97 | 0.0000 | Y | 20.30 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 6.1909 | 174.19 | 1078.41 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 19.14 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 7.5320 | 348.39 | 2624.05 | LightsWired | LTG_SCH_BASE_LPD2 | 60.23 | 168.00 | 58.11 | 0.0000 | Y | 28.62 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 5.0436 | 4180.64 | 21085.58 | 277.79 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 437.57 | AstronomicalClock | - | 41.75 | 41.75 | 3.43 | |
EXTERIOR_LIGHTS_B | 1882.64 | AstronomicalClock | - | 83.75 | 62.75 | 22.18 | |
EXTERIOR_LIGHTS_C | 1466.47 | AstronomicalClock | - | 83.75 | 55.75 | 15.35 | |
Exterior Lighting Total | 3786.68 | 40.95 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 62497.78 | 45070.90 | 17426.88 | 0.72 | 3.92 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31660.18 | 22838.70 | 8821.48 | 0.72 | 3.99 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31848.72 | 22986.81 | 8861.91 | 0.72 | 3.99 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31933.14 | 23053.49 | 8879.65 | 0.72 | 3.99 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31808.70 | 22955.38 | 8853.32 | 0.72 | 3.99 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 58269.97 | 41702.07 | 16567.90 | 0.72 | 3.92 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30577.29 | 21986.60 | 8590.69 | 0.72 | 3.99 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30500.96 | 21926.53 | 8574.43 | 0.72 | 3.99 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30633.52 | 22031.01 | 8602.51 | 0.72 | 3.99 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34672.42 | 25342.77 | 9329.65 | 0.73 | 3.99 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 60384.6 | 12.15 | 12.15 | ||||
PSZ-AC_2:2 COOLING COIL | 30588.8 | 12.33 | 12.33 | ||||
PSZ-AC_3:3 COOLING COIL | 30769.4 | 12.33 | 12.33 | ||||
PSZ-AC_4:4 COOLING COIL | 30850.3 | 12.32 | 12.32 | ||||
PSZ-AC_5:5 COOLING COIL | 30731.1 | 12.33 | 12.33 | ||||
PSZ-AC_6:6 COOLING COIL | 56332.9 | 12.18 | 12.18 | ||||
PSZ-AC_7:7 COOLING COIL | 29551.6 | 12.35 | 12.35 | ||||
PSZ-AC_8:8 COOLING COIL | 29478.5 | 12.35 | 12.35 | ||||
PSZ-AC_9:9 COOLING COIL | 29605.5 | 12.35 | 12.35 | ||||
PSZ-AC_10:10 COOLING COIL | 33465.9 | 12.27 | 12.27 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 66944.00 | 0.81 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 33889.90 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 34115.08 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 34216.23 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 34067.08 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 61945.03 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 32594.18 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 32503.07 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 32661.26 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 37730.62 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.68 | 2869.72 | 1070.05 | 1.00 | 1.28 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.36 | 1505.39 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.37 | 1516.57 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.37 | 1521.60 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.37 | 1514.19 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.46 | 2629.65 | 1070.05 | 1.00 | 1.29 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.30 | 1441.00 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.30 | 1436.48 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.30 | 1444.34 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.53 | 1639.36 | 1070.05 | 1.00 | 1.36 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 29602.27 | 35522.73 | 101.96 | 2.235 | 2.682 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 23.89 | 23.89 | 0.00768 | 41.81 | 0.00916 | 0.411 | 0.00 |
SMSTORE1 | 15008.14 | 18009.77 | 103.39 | 1.133 | 1.360 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | 23.89 | 23.89 | 0.00769 | 42.00 | 0.00916 | 0.206 | 0.00 |
SMSTORE2 | 15119.69 | 18143.62 | 104.16 | 1.141 | 1.370 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00769 | 42.00 | 0.00916 | 0.206 | 0.00 |
SMSTORE3 | 15169.79 | 18203.75 | 104.50 | 1.145 | 1.374 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00768 | 42.00 | 0.00916 | 0.206 | 0.00 |
SMSTORE4 | 15095.91 | 18115.09 | 103.99 | 1.140 | 1.368 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00769 | 42.00 | 0.00916 | 0.206 | 0.00 |
LGSTORE2 | 27126.00 | 32551.20 | 93.43 | 2.048 | 2.458 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00772 | 42.00 | 0.00916 | 0.411 | 0.00 |
SMSTORE5 | 14366.27 | 17239.52 | 98.97 | 1.085 | 1.302 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00772 | 42.00 | 0.00916 | 0.206 | 0.00 |
SMSTORE6 | 14321.13 | 17185.36 | 98.66 | 1.081 | 1.297 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00772 | 42.00 | 0.00916 | 0.206 | 0.00 |
SMSTORE7 | 14399.50 | 17279.40 | 99.20 | 1.087 | 1.305 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00771 | 42.00 | 0.00916 | 0.206 | 0.00 |
SMSTORE8 | 16911.19 | 20293.43 | 116.50 | 1.277 | 1.532 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 23.89 | 23.89 | 0.00764 | 41.52 | 0.00916 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 15229.83 | 18275.79 | 52.46 | 0.674 | 0.808 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00736 | 6.30 | 0.00607 | 0.411 | 0.00 |
SMSTORE1 | 7490.88 | 8989.06 | 51.60 | 0.331 | 0.398 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00729 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE2 | 7556.87 | 9068.24 | 52.06 | 0.334 | 0.401 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00729 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE3 | 7626.65 | 9151.99 | 52.54 | 0.337 | 0.405 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00730 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE4 | 7774.55 | 9329.47 | 53.56 | 0.344 | 0.413 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00730 | 6.30 | 0.00607 | 0.206 | 0.00 |
LGSTORE2 | 14744.80 | 17693.76 | 50.79 | 0.652 | 0.783 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00735 | 6.30 | 0.00607 | 0.411 | 0.00 |
SMSTORE5 | 7987.78 | 9585.33 | 55.03 | 0.353 | 0.424 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00731 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE6 | 7991.59 | 9589.91 | 55.05 | 0.353 | 0.424 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00731 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE7 | 8242.98 | 9891.58 | 56.79 | 0.365 | 0.437 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00732 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE8 | 9749.93 | 11699.91 | 67.17 | 0.431 | 0.517 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00738 | 6.30 | 0.00607 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.68 | 2.68 | 0.81 | 0.81 | 2.6819 | 2.6819 | 2.6819 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.36 | 1.36 | 0.40 | 0.40 | 1.3597 | 1.3597 | 1.3597 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.37 | 1.37 | 0.40 | 0.40 | 1.3698 | 1.3698 | 1.3698 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.37 | 1.37 | 0.40 | 0.40 | 1.3743 | 1.3743 | 1.3743 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.37 | 1.37 | 0.41 | 0.41 | 1.3676 | 1.3676 | 1.3676 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.46 | 2.46 | 0.78 | 0.78 | 2.4575 | 2.4575 | 2.4575 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.30 | 1.30 | 0.42 | 0.42 | 1.3015 | 1.3015 | 1.3015 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.30 | 1.30 | 0.42 | 0.42 | 1.2974 | 1.2974 | 1.2974 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.30 | 1.30 | 0.44 | 0.44 | 1.3045 | 1.3045 | 1.3045 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.53 | 1.53 | 0.52 | 0.52 | 1.5320 | 1.5320 | 1.5320 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 62497.780 | 45070.899 | 2.681860 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 31248.89 | 27949.91 | 1.787907 | 27.56 | 16.86 | 0.00790406 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 23.0147 | 23.89 | 0.00767672 | 40.6104 | 29590.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 66944.004 | 66944.004 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 66944.00 | 66944.00 | 2.681864 | 18.84 | 12.99 | 0.00716214 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.3431 | 21.11 | 0.00735966 | 46.1165 | 15229.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 31660.180 | 22838.704 | 1.359680 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | 15830.09 | 14145.44 | 0.906453 | 27.55 | 16.87 | 0.00791181 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 22.6970 | 23.89 | 0.00768965 | 40.6780 | 15008.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 33889.902 | 33889.902 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33889.90 | 33889.90 | 1.359684 | 18.87 | 12.95 | 0.00710637 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.1313 | 21.11 | 0.00729072 | 45.6899 | 7490.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 31848.720 | 22986.814 | 1.369790 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 15924.36 | 14236.62 | 0.913193 | 27.53 | 16.86 | 0.00790669 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 22.5295 | 23.89 | 0.00768555 | 40.6566 | 15119.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 34115.085 | 34115.085 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34115.08 | 34115.08 | 1.369789 | 18.88 | 12.96 | 0.00710951 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.0196 | 21.11 | 0.00729282 | 45.7029 | 7556.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 31933.140 | 23053.492 | 1.374330 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 15966.57 | 14277.57 | 0.916220 | 27.52 | 16.85 | 0.00790435 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 22.4550 | 23.89 | 0.00768365 | 40.6466 | 15169.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 34216.232 | 34216.232 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34216.23 | 34216.23 | 1.374329 | 18.89 | 12.97 | 0.00711291 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.9700 | 21.11 | 0.00729611 | 45.7233 | 7626.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 31808.700 | 22955.385 | 1.367630 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 15904.35 | 14217.19 | 0.911753 | 27.54 | 16.86 | 0.00790782 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 22.5650 | 23.89 | 0.00768647 | 40.6614 | 15095.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 34067.079 | 34067.079 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34067.08 | 34067.08 | 1.367635 | 18.88 | 12.97 | 0.00711816 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.0433 | 21.11 | 0.00730334 | 45.7681 | 7774.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 58269.970 | 41702.069 | 2.457510 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 29134.99 | 25922.08 | 1.638340 | 27.81 | 17.00 | 0.00796166 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 25.1157 | 23.89 | 0.00772109 | 40.8422 | 27126.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 61945.028 | 61945.028 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 61945.03 | 61945.03 | 2.457513 | 18.63 | 12.89 | 0.00713765 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 16.7438 | 21.11 | 0.00735190 | 46.0683 | 14744.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 30577.290 | 21986.600 | 1.301530 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 15288.65 | 13620.40 | 0.867687 | 27.67 | 16.93 | 0.00794364 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 23.7110 | 23.89 | 0.00771566 | 40.8139 | 14366.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 32594.177 | 32594.177 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32594.18 | 32594.18 | 1.301532 | 18.77 | 12.92 | 0.00711694 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.8073 | 21.11 | 0.00731306 | 45.8283 | 7987.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 30500.960 | 21926.530 | 1.297440 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 15250.48 | 13583.46 | 0.864960 | 27.68 | 16.94 | 0.00794594 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 23.7858 | 23.89 | 0.00771754 | 40.8237 | 14321.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 32503.068 | 32503.068 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32503.07 | 32503.07 | 1.297443 | 18.76 | 12.92 | 0.00711650 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.8572 | 21.11 | 0.00731327 | 45.8296 | 7991.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 30633.520 | 22031.015 | 1.304540 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 15316.76 | 13647.59 | 0.869693 | 27.67 | 16.93 | 0.00794196 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 23.6563 | 23.89 | 0.00771429 | 40.8067 | 14399.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 32661.258 | 32661.258 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32661.26 | 32661.26 | 1.304542 | 18.77 | 12.93 | 0.00712695 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.7709 | 21.11 | 0.00732441 | 45.8986 | 8242.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 34672.420 | 25342.765 | 1.532050 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 17336.21 | 15589.11 | 1.021367 | 27.17 | 16.68 | 0.00784133 | 12.80 | 10.34 | 0.00700000 | 41.68 | 0.00915736 | 22.17 | 20.1434 | 23.89 | 0.00763684 | 40.4021 | 16901.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 37730.624 | 37730.624 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37730.62 | 37730.62 | 1.532049 | 19.12 | 13.14 | 0.00720093 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 13.4289 | 21.11 | 0.00737600 | 46.2185 | 9749.93 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 62497.780 | 45070.899 | 2.681860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5333 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.681864 | 3.14793301 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | Sensible | 31248.89 | 27949.91 | 1.0000 | 2.09861885 | 1.787907 | 27.56 | 16.86 | 0.00790406 | 47866.9 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31248.89 | 42.00 | 0.00915790 | 22.26 | 0.41148071 | 23.0147 | 23.89 | 0.00767672 | 23.89 | 0.00767672 | 40.6104 | 29590.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 66944.004 | 66944.004 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.681864 | 3.14793301 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 66944.00 | 66944.00 | 1.0000 | 3.14793301 | 2.681864 | 18.84 | 12.99 | 0.00716214 | 37090.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 66944.00 | 6.30 | 0.00607234 | 6.30 | 0.41148071 | 15.3431 | 21.11 | 0.00735966 | 21.11 | 0.00735966 | 46.1165 | 15229.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31660.180 | 22838.704 | 1.359680 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5477 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.359684 | 1.59597739 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | Sensible | 15830.09 | 14145.44 | 1.0000 | 1.06398174 | 0.906453 | 27.55 | 16.87 | 0.00791181 | 47878.1 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15830.09 | 42.00 | 0.00915790 | 22.26 | 0.20573751 | 22.6970 | 23.89 | 0.00768965 | 23.89 | 0.00768965 | 40.6780 | 15008.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33889.902 | 33889.902 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.359684 | 1.59597739 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 33889.90 | 33889.90 | 1.0000 | 1.59597739 | 1.359684 | 18.87 | 12.95 | 0.00710637 | 36981.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33889.90 | 6.30 | 0.00607234 | 6.30 | 0.20573751 | 15.1313 | 21.11 | 0.00729072 | 21.11 | 0.00729072 | 45.6899 | 7490.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31848.720 | 22986.814 | 1.369790 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5381 | 1004.8586 | 1.1738 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.369789 | 1.60783891 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 15924.36 | 14236.62 | 1.0000 | 1.07189306 | 0.913193 | 27.53 | 16.86 | 0.00790669 | 47844.4 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15924.36 | 42.00 | 0.00915790 | 22.26 | 0.20573751 | 22.5295 | 23.89 | 0.00768555 | 23.89 | 0.00768555 | 40.6566 | 15119.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34115.085 | 34115.085 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.369789 | 1.60783891 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 34115.08 | 34115.08 | 1.0000 | 1.60783891 | 1.369789 | 18.88 | 12.96 | 0.00710951 | 37006.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34115.08 | 6.30 | 0.00607234 | 6.30 | 0.20573751 | 15.0196 | 21.11 | 0.00729282 | 21.11 | 0.00729282 | 45.7029 | 7556.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31933.140 | 23053.492 | 1.374330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5338 | 1004.8586 | 1.1738 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.374329 | 1.61316717 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 15966.57 | 14277.57 | 1.0000 | 1.07544571 | 0.916220 | 27.52 | 16.85 | 0.00790435 | 47829.2 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15966.57 | 42.00 | 0.00915790 | 22.26 | 0.20573751 | 22.4550 | 23.89 | 0.00768365 | 23.89 | 0.00768365 | 40.6466 | 15169.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34216.232 | 34216.232 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.374329 | 1.61316717 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 34216.23 | 34216.23 | 1.0000 | 1.61316717 | 1.374329 | 18.89 | 12.97 | 0.00711291 | 37022.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34216.23 | 6.30 | 0.00607234 | 6.30 | 0.20573751 | 14.9700 | 21.11 | 0.00729611 | 21.11 | 0.00729611 | 45.7233 | 7626.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31808.700 | 22955.385 | 1.367630 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5402 | 1004.8586 | 1.1738 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.367635 | 1.60530997 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 15904.35 | 14217.19 | 1.0000 | 1.07020281 | 0.911753 | 27.54 | 16.86 | 0.00790782 | 47851.6 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15904.35 | 42.00 | 0.00915790 | 22.26 | 0.20573751 | 22.5650 | 23.89 | 0.00768647 | 23.89 | 0.00768647 | 40.6614 | 15095.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34067.079 | 34067.079 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.367635 | 1.60530997 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 34067.08 | 34067.08 | 1.0000 | 1.60530997 | 1.367635 | 18.88 | 12.97 | 0.00711816 | 37024.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34067.08 | 6.30 | 0.00607234 | 6.30 | 0.20573751 | 15.0433 | 21.11 | 0.00730334 | 21.11 | 0.00730334 | 45.7681 | 7774.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 58269.970 | 41702.069 | 2.457510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6403 | 1004.8586 | 1.1738 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.457513 | 2.88459261 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 29134.99 | 25922.08 | 1.0000 | 1.92305967 | 1.638340 | 27.81 | 17.00 | 0.00796166 | 48271.4 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29134.99 | 42.00 | 0.00915790 | 22.26 | 0.41148071 | 25.1157 | 23.89 | 0.00772109 | 23.89 | 0.00772109 | 40.8422 | 27126.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61945.028 | 61945.028 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.457513 | 2.88459261 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 61945.03 | 61945.03 | 1.0000 | 2.88459261 | 2.457513 | 18.63 | 12.89 | 0.00713765 | 36817.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61945.03 | 6.30 | 0.00607234 | 6.30 | 0.41148071 | 16.7438 | 21.11 | 0.00735190 | 21.11 | 0.00735190 | 46.0683 | 14744.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30577.290 | 21986.600 | 1.301530 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6068 | 1004.8586 | 1.1738 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.301532 | 1.52771905 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 15288.65 | 13620.40 | 1.0000 | 1.01847799 | 0.867687 | 27.67 | 16.93 | 0.00794364 | 48084.1 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15288.65 | 42.00 | 0.00915790 | 22.26 | 0.20573751 | 23.7110 | 23.89 | 0.00771566 | 23.89 | 0.00771566 | 40.8139 | 14366.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32594.177 | 32594.177 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.301532 | 1.52771905 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32594.18 | 32594.18 | 1.0000 | 1.52771905 | 1.301532 | 18.77 | 12.92 | 0.00711694 | 36906.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32594.18 | 6.30 | 0.00607234 | 6.30 | 0.20573751 | 15.8073 | 21.11 | 0.00731306 | 21.11 | 0.00731306 | 45.8283 | 7987.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30500.960 | 21926.530 | 1.297440 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6111 | 1004.8586 | 1.1738 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.297443 | 1.52291959 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 15250.48 | 13583.46 | 1.0000 | 1.01527747 | 0.864960 | 27.68 | 16.94 | 0.00794594 | 48099.2 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15250.48 | 42.00 | 0.00915790 | 22.26 | 0.20573751 | 23.7858 | 23.89 | 0.00771754 | 23.89 | 0.00771754 | 40.8237 | 14321.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32503.068 | 32503.068 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.297443 | 1.52291959 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32503.07 | 32503.07 | 1.0000 | 1.52291959 | 1.297443 | 18.76 | 12.92 | 0.00711650 | 36897.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32503.07 | 6.30 | 0.00607234 | 6.30 | 0.20573751 | 15.8572 | 21.11 | 0.00731327 | 21.11 | 0.00731327 | 45.8296 | 7991.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30633.520 | 22031.015 | 1.304540 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6037 | 1004.8586 | 1.1738 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.304542 | 1.53125276 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 15316.76 | 13647.59 | 1.0000 | 1.02083339 | 0.869693 | 27.67 | 16.93 | 0.00794196 | 48073.1 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15316.76 | 42.00 | 0.00915790 | 22.26 | 0.20573751 | 23.6563 | 23.89 | 0.00771429 | 23.89 | 0.00771429 | 40.8067 | 14399.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32661.258 | 32661.258 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.304542 | 1.53125276 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32661.26 | 32661.26 | 1.0000 | 1.53125276 | 1.304542 | 18.77 | 12.93 | 0.00712695 | 36937.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32661.26 | 6.30 | 0.00607234 | 6.30 | 0.20573751 | 15.7709 | 21.11 | 0.00732441 | 21.11 | 0.00732441 | 45.8986 | 8242.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34672.420 | 25342.765 | 1.532050 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4166 | 1004.8586 | 1.1738 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.532049 | 1.79829695 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | Sensible | 17336.21 | 15589.11 | 1.0000 | 1.19886534 | 1.021367 | 27.17 | 16.68 | 0.00784133 | 47311.7 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17336.21 | 41.68 | 0.00915736 | 22.17 | 0.20573751 | 20.1434 | 23.89 | 0.00763684 | 23.89 | 0.00763684 | 40.4021 | 16901.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37730.624 | 37730.624 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.532049 | 1.79829695 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 37730.62 | 37730.62 | 1.0000 | 1.79829695 | 1.532049 | 19.12 | 13.14 | 0.00720093 | 37477.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37730.62 | 6.30 | 0.00607234 | 6.30 | 0.20573751 | 13.4289 | 21.11 | 0.00737600 | 21.11 | 0.00737600 | 46.2185 | 9749.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
LGSTORE1 | LGSTORE1_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE1 | SMSTORE1_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE2 | SMSTORE2_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE3 | SMSTORE3_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE4 | SMSTORE4_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LGSTORE2 | LGSTORE2_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE5 | SMSTORE5_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE6 | SMSTORE6_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE7 | SMSTORE7_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE8 | SMSTORE8_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3837.50 | 1800.00 | 925.50 |
SMSTORE1 | 3691.50 | 1448.00 | 778.33 |
SMSTORE2 | 2962.17 | 1399.50 | 858.33 |
SMSTORE3 | 2954.50 | 1423.83 | 846.83 |
SMSTORE4 | 2927.83 | 1491.33 | 858.50 |
LGSTORE2 | 2629.67 | 1522.33 | 851.67 |
SMSTORE5 | 2548.17 | 1577.33 | 866.00 |
SMSTORE6 | 2535.67 | 1603.33 | 869.67 |
SMSTORE7 | 2532.33 | 1631.83 | 859.00 |
SMSTORE8 | 2664.00 | 1526.83 | 747.50 |
Facility | 3986.67 | 2369.67 | 1155.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 0.50 | 0.00 | 0.50 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 2.33 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 3.50 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 2.50 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 3.33 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 3.17 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 3.17 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 3.33 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 5.50 | 0.00 | 0.00 |
Facility | 0.00 | 9.00 | 0.00 | 0.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.553 | 0.333 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.460 | 0.375 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.530 | 0.494 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.530 | 0.494 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.530 | 0.494 | 0.000 | 0.000 |
LGSTORE2 | 24.77 | 56.25 | 1805.20 | 0.610 | 0.462 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.610 | 0.527 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.610 | 0.527 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.610 | 0.527 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.610 | 0.536 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.421 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.419 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.419 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.419 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.77 | 56.25 | 1805.20 | 0.443 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.443 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.443 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.443 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.442 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.212 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
LGSTORE2 | PSZ-AC_6:6 | 24.77 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.212 |
SMSTORE5 | PSZ-AC_7:7 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE6 | PSZ-AC_8:8 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE7 | PSZ-AC_9:9 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE8 | PSZ-AC_10:10 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
Total Facility | 120.95 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 1.274 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 5717038.94 | 0.00 | 5717038.94 | 3505960.47 | 9222999.41 | 7870781.79 | 2817.00 | 5943.00 | 0.00 | 103.00 |
SMSTORE1 | 2386495.93 | 0.00 | 2386495.93 | 1952020.86 | 4338516.79 | 3935374.10 | 4302.58 | 4457.42 | 0.00 | 103.00 |
SMSTORE2 | 2172713.67 | 0.00 | 2172713.67 | 1960785.24 | 4133498.91 | 3701819.01 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE3 | 2172714.22 | 0.00 | 2172714.22 | 1960785.24 | 4133499.46 | 3701819.01 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE4 | 2172715.26 | 0.00 | 2172715.26 | 1960785.24 | 4133500.50 | 3701819.01 | 4000.00 | 4760.00 | 0.00 | 365.00 |
LGSTORE2 | 4570610.07 | 0.00 | 4570610.07 | 3452391.79 | 8023001.86 | 7907875.00 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE5 | 2285286.03 | 0.00 | 2285286.03 | 1964207.59 | 4249493.62 | 3953920.18 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE6 | 2285286.19 | 0.00 | 2285286.19 | 1964207.59 | 4249493.78 | 3953920.18 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE7 | 2285286.44 | 0.00 | 2285286.44 | 1964207.59 | 4249494.03 | 3953920.18 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE8 | 2285342.41 | 0.00 | 2285342.41 | 2060429.81 | 4345772.21 | 3953920.18 | 4365.00 | 4395.00 | 0.00 | 365.92 |
Total Facility | 28333489.18 | 0.00 | 28333489.18 | 22745781.39 | 51079270.57 | 46635168.64 | 4365.00 | 6246.00 | 0.00 | 730.92 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.2682 | 0.0000 | 0.2682 | 0.1614 | 0.4296 | 0.2682 | 0.00 | 5840.00 | 0.00 |
SMSTORE1 | 0.1116 | 0.0000 | 0.1116 | 0.0910 | 0.2027 | 0.1341 | 1485.58 | 4354.42 | 0.00 |
SMSTORE2 | 0.1285 | 0.0000 | 0.1285 | 0.1198 | 0.2483 | 0.1285 | 0.00 | 4395.00 | 0.00 |
SMSTORE3 | 0.1285 | 0.0000 | 0.1285 | 0.1198 | 0.2483 | 0.1285 | 0.00 | 4395.00 | 0.00 |
SMSTORE4 | 0.1285 | 0.0000 | 0.1285 | 0.1198 | 0.2483 | 0.1285 | 0.00 | 4395.00 | 0.00 |
LGSTORE2 | 0.2958 | 0.0000 | 0.2958 | 0.2239 | 0.5197 | 0.2958 | 0.00 | 4030.00 | 0.00 |
SMSTORE5 | 0.1479 | 0.0000 | 0.1479 | 0.1278 | 0.2757 | 0.1479 | 0.00 | 4030.00 | 0.00 |
SMSTORE6 | 0.1479 | 0.0000 | 0.1479 | 0.1278 | 0.2757 | 0.1479 | 0.00 | 4030.00 | 0.00 |
SMSTORE7 | 0.1479 | 0.0000 | 0.1479 | 0.1278 | 0.2757 | 0.1479 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.1479 | 0.0000 | 0.1479 | 0.1299 | 0.2778 | 0.1479 | 0.00 | 4030.00 | 0.00 |
Total Facility | 1.6527 | 0.0000 | 1.6527 | 1.3490 | 3.0017 | 1.6752 | 1485.58 | 5943.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 7876771.52 | 0.00 | 7876771.52 | 7870781.79 | 2817.00 | 0.00 | 5943.00 | 103.00 |
PSZ-AC_2:2 | 3288057.96 | 0.00 | 3288057.96 | 3935374.10 | 4253.17 | 5.58 | 4501.25 | 103.00 |
PSZ-AC_3:3 | 2993502.16 | 0.00 | 2993502.16 | 3701819.01 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_4:4 | 2993502.16 | 0.00 | 2993502.16 | 3701819.01 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_5:5 | 2993502.16 | 0.00 | 2993502.16 | 3701819.01 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_6:6 | 6297244.06 | 0.00 | 6297244.06 | 7907875.00 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_7:7 | 3148598.17 | 0.00 | 3148598.17 | 3953920.18 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_8:8 | 3148598.17 | 0.00 | 3148598.17 | 3953920.18 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_9:9 | 3148598.17 | 0.00 | 3148598.17 | 3953920.18 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_10:10 | 3148678.37 | 0.00 | 3148678.37 | 3953920.18 | 4365.00 | 0.00 | 4395.00 | 365.92 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.3695 | 0.0000 | 0.3695 | 0.2682 | 0.00 | 0.00 | 5840.00 |
PSZ-AC_2:2 | 0.1538 | 0.0000 | 0.1538 | 0.1341 | 1436.17 | 5.58 | 4398.25 |
PSZ-AC_3:3 | 0.1770 | 0.0000 | 0.1770 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.1770 | 0.0000 | 0.1770 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.1770 | 0.0000 | 0.1770 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.4076 | 0.0000 | 0.4076 | 0.2958 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2038 | 0.0000 | 0.2038 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2038 | 0.0000 | 0.2038 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2038 | 0.0000 | 0.2038 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2038 | 0.0000 | 0.2038 | 0.1479 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5911.22 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4395.92 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.3695 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.1547 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.1771 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.1771 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.1771 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.4077 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2038 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2038 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2038 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2038 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 835 |
Defaulted Fields | 817 |
Fields with Defaults | 2693 |
Autosized Fields | 174 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1053.11 | 2102.83 | 01-JAN-07:50 | 119852.83 | 01-JUL-13:00 |
Electricity:Building | 405.94 | 891.83 | 01-JAN-00:20 | 25756.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 90.96 | 148.64 | 01-JAN-00:20 | 4765.21 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 405.94 | 891.83 | 01-JAN-00:20 | 25756.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 64.71 | 75.00 | 01-JAN-00:20 | 3421.96 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 64.71 | 75.00 | 01-JAN-00:20 | 3421.96 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 52.56 | 74.32 | 01-JAN-00:20 | 2762.01 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 39.44 | 37.50 | 01-JAN-00:20 | 2090.38 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 39.44 | 37.50 | 01-JAN-00:20 | 2090.38 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 47.80 | 148.64 | 01-JAN-00:10 | 3421.36 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 28.62 | 75.00 | 01-JAN-00:10 | 2078.11 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 28.62 | 75.00 | 01-JAN-00:10 | 2078.11 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityProduced:Facility | 67.09 | -0.00 | 03-JAN-17:30 | 11206.30 | 04-JUN-12:20 |
ElectricityProduced:Plant | 67.09 | -0.00 | 03-JAN-17:30 | 11206.30 | 04-JUN-12:20 |
Photovoltaic:ElectricityProduced | 70.05 | 0.00 | 01-JAN-00:10 | 11672.74 | 04-JUN-12:20 |
PowerConversion:ElectricityProduced | -2.96 | -466.44 | 04-JUN-12:20 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 58.67 | 1211.00 | 03-JAN-08:10 | 11790.47 | 13-NOV-13:30 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 986.02 | 0.00 | 29-MAY-07:00 | 112351.57 | 10-JUN-17:00 |
ElectricityPurchased:Plant | 986.02 | 0.00 | 29-MAY-07:00 | 112351.57 | 10-JUN-17:00 |
Cogeneration:ElectricityPurchased | 986.02 | 0.00 | 29-MAY-07:00 | 112351.57 | 10-JUN-17:00 |
General:Cogeneration:ElectricityPurchased | 986.02 | 0.00 | 29-MAY-07:00 | 112351.57 | 10-JUN-17:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 61.49 | 29-MAY-07:00 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 61.49 | 29-MAY-07:00 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 61.49 | 29-MAY-07:00 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 61.49 | 29-MAY-07:00 |
ElectricityNet:Facility | 986.02 | -61.49 | 29-MAY-07:00 | 112351.57 | 10-JUN-17:00 |
ElectricityNet:Plant | 986.02 | -61.49 | 29-MAY-07:00 | 112351.57 | 10-JUN-17:00 |
Cogeneration:ElectricityNet | 986.02 | -61.49 | 29-MAY-07:00 | 112351.57 | 10-JUN-17:00 |
General:Cogeneration:ElectricityNet | 986.02 | -61.49 | 29-MAY-07:00 | 112351.57 | 10-JUN-17:00 |
Electricity:HVAC | 547.54 | 0.00 | 01-JAN-00:10 | 87178.40 | 22-JUN-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 421.61 | 0.00 | 01-JAN-00:10 | 75490.70 | 10-JUN-16:00 |
General:Cooling:Electricity | 421.61 | 0.00 | 01-JAN-00:10 | 75490.70 | 10-JUN-16:00 |
Fans:Electricity | 125.92 | 0.00 | 01-JAN-00:10 | 12273.33 | 01-JUL-13:00 |
General:Fans:Electricity | 125.92 | 0.00 | 01-JAN-00:10 | 12273.33 | 01-JUL-13:00 |
ExteriorLights:Electricity | 40.95 | 0.00 | 01-JAN-07:20 | 3786.68 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 40.95 | 0.00 | 01-JAN-07:20 | 3786.68 | 01-JAN-06:10 |
WaterSystems:Electricity | 58.67 | 1211.00 | 03-JAN-08:10 | 11790.47 | 13-NOV-13:30 |
Water Heater:WaterSystems:Electricity | 58.67 | 1211.00 | 03-JAN-08:10 | 11790.47 | 13-NOV-13:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3.95 | 0.00 | 01-JAN-00:10 | 109187.11 | 02-JAN-08:10 |
NaturalGas:HVAC | 3.95 | 0.00 | 01-JAN-00:10 | 109187.11 | 02-JAN-08:10 |
Heating:NaturalGas | 3.95 | 0.00 | 01-JAN-00:10 | 109187.11 | 02-JAN-08:10 |
General:Heating:NaturalGas | 3.95 | 0.00 | 01-JAN-00:10 | 109187.11 | 02-JAN-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2554.23 | 0.00 | 01-JAN-00:10 | 412830.32 | 01-JUL-13:00 |
EnergyTransfer:Building | 917.00 | 0.00 | 01-JAN-00:10 | 151216.00 | 12-JUN-16:10 |
EnergyTransfer:Zone:LGSTORE1 | 183.94 | 0.00 | 01-JAN-00:10 | 25491.49 | 08-JUN-16:20 |
Heating:EnergyTransfer | 7.10 | 0.00 | 01-JAN-00:10 | 75111.60 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.36 | 0.00 | 01-JAN-00:10 | 12315.60 | 01-JAN-08:10 |
General:Heating:EnergyTransfer | 7.10 | 0.00 | 01-JAN-00:10 | 75111.60 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.36 | 0.00 | 01-JAN-00:10 | 12315.60 | 01-JAN-08:10 |
Cooling:EnergyTransfer | 909.91 | 0.00 | 01-JAN-00:10 | 151216.00 | 12-JUN-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 183.58 | 0.00 | 01-JAN-00:10 | 25491.49 | 08-JUN-16:20 |
General:Cooling:EnergyTransfer | 909.91 | 0.00 | 01-JAN-00:10 | 151216.00 | 12-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 183.58 | 0.00 | 01-JAN-00:10 | 25491.49 | 08-JUN-16:20 |
EnergyTransfer:Zone:SMSTORE1 | 94.11 | 0.00 | 01-JAN-00:10 | 12250.63 | 08-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.12 | 0.00 | 01-JAN-00:10 | 3538.60 | 01-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.12 | 0.00 | 01-JAN-00:10 | 3538.60 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 93.99 | 0.00 | 01-JAN-00:10 | 12250.63 | 08-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 93.99 | 0.00 | 01-JAN-00:10 | 12250.63 | 08-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE2 | 75.07 | 0.00 | 01-JAN-00:10 | 12508.07 | 12-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 0.97 | 0.00 | 01-JAN-00:10 | 6077.09 | 01-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 0.97 | 0.00 | 01-JAN-00:10 | 6077.09 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 74.10 | 0.00 | 01-JAN-00:10 | 12508.07 | 12-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 74.10 | 0.00 | 01-JAN-00:10 | 12508.07 | 12-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 75.39 | 0.00 | 01-JAN-00:10 | 12638.26 | 12-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 0.98 | 0.00 | 01-JAN-00:10 | 6602.65 | 01-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 0.98 | 0.00 | 01-JAN-00:10 | 6602.65 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 74.41 | 0.00 | 01-JAN-00:10 | 12638.26 | 12-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 74.41 | 0.00 | 01-JAN-00:10 | 12638.26 | 12-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE4 | 73.71 | 0.00 | 01-JAN-00:10 | 12614.05 | 12-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.02 | 0.00 | 01-JAN-00:10 | 7121.23 | 01-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.02 | 0.00 | 01-JAN-00:10 | 7121.23 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 72.68 | 0.00 | 01-JAN-00:10 | 12614.05 | 12-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 72.68 | 0.00 | 01-JAN-00:10 | 12614.05 | 12-JUN-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 130.35 | 0.00 | 01-JAN-00:10 | 23807.89 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.04 | 0.00 | 01-JAN-00:10 | 15866.05 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 1.04 | 0.00 | 01-JAN-00:10 | 15866.05 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 129.31 | 0.00 | 01-JAN-00:10 | 23807.89 | 12-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 129.31 | 0.00 | 01-JAN-00:10 | 23807.89 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE5 | 67.96 | 0.00 | 01-JAN-00:10 | 12732.99 | 12-JUN-14:30 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.54 | 0.00 | 01-JAN-00:10 | 8260.55 | 01-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 0.54 | 0.00 | 01-JAN-00:10 | 8260.55 | 01-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 67.42 | 0.00 | 01-JAN-00:10 | 12732.99 | 12-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 67.42 | 0.00 | 01-JAN-00:10 | 12732.99 | 12-JUN-14:30 |
EnergyTransfer:Zone:SMSTORE6 | 67.53 | 0.00 | 01-JAN-00:10 | 12715.53 | 12-JUN-14:30 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.56 | 0.00 | 01-JAN-00:10 | 8395.05 | 01-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 0.56 | 0.00 | 01-JAN-00:10 | 8395.05 | 01-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 66.97 | 0.00 | 01-JAN-00:10 | 12715.53 | 12-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 66.97 | 0.00 | 01-JAN-00:10 | 12715.53 | 12-JUN-14:30 |
EnergyTransfer:Zone:SMSTORE7 | 67.59 | 0.00 | 01-JAN-00:10 | 12895.21 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.62 | 0.00 | 01-JAN-00:10 | 9019.75 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 0.62 | 0.00 | 01-JAN-00:10 | 9019.75 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 66.97 | 0.00 | 01-JAN-00:10 | 12895.21 | 12-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 66.97 | 0.00 | 01-JAN-00:10 | 12895.21 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE8 | 81.34 | 0.00 | 01-JAN-00:10 | 15834.37 | 12-JUN-12:20 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.87 | 0.00 | 01-JAN-00:10 | 12048.33 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 0.87 | 0.00 | 01-JAN-00:10 | 12048.33 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 80.48 | 0.00 | 01-JAN-00:10 | 15834.37 | 12-JUN-12:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 80.48 | 0.00 | 01-JAN-00:10 | 15834.37 | 12-JUN-12:20 |
EnergyTransfer:HVAC | 1637.23 | 0.00 | 01-JAN-00:10 | 291739.72 | 01-JUL-14:00 |
HeatingCoils:EnergyTransfer | 3.17 | 0.00 | 01-JAN-00:10 | 87512.50 | 02-JAN-08:10 |
CoolingCoils:EnergyTransfer | 1634.06 | 0.00 | 01-JAN-00:10 | 291739.72 | 01-JUL-14:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.364 | -183.579 | 0.000 | 0.000 | 23.326 | 64.707 | 26.249 | 20.643 | 0.000 | 25.300 | 32.270 | 0.000 | -4.330 | 0.000 | -4.951 | -0.001 |
SMSTORE1 | 0.000 | 0.000 | 0.125 | -93.986 | 0.000 | 0.000 | 11.636 | 39.440 | 13.125 | 10.359 | 0.000 | 14.234 | 10.044 | 0.000 | -2.220 | 0.000 | -2.756 | -0.000 |
SMSTORE2 | 0.000 | 0.000 | 0.974 | -74.098 | 0.000 | 0.000 | 6.999 | 28.854 | 10.421 | 10.199 | 0.000 | 14.056 | 7.643 | 0.000 | -2.270 | 0.000 | -2.778 | -0.001 |
SMSTORE3 | 0.000 | 0.000 | 0.985 | -74.404 | 0.000 | 0.000 | 7.002 | 28.854 | 10.421 | 10.189 | 0.000 | 14.051 | 7.927 | 0.000 | -2.263 | 0.000 | -2.761 | -0.001 |
SMSTORE4 | 0.000 | 0.000 | 1.020 | -72.684 | 0.000 | 0.000 | 7.007 | 28.854 | 10.421 | 10.208 | 0.000 | 14.055 | 6.078 | 0.000 | -2.232 | 0.000 | -2.728 | -0.000 |
LGSTORE2 | 0.000 | 0.000 | 1.041 | -129.311 | 0.000 | 0.000 | 24.069 | 28.624 | 19.173 | 20.473 | 0.000 | 24.663 | 20.302 | 0.000 | -4.317 | 0.000 | -4.715 | -0.000 |
SMSTORE5 | 0.000 | 0.000 | 0.541 | -67.421 | 0.000 | 0.000 | 12.040 | 14.614 | 9.586 | 10.267 | 0.000 | 14.066 | 11.101 | 0.000 | -2.142 | 0.000 | -2.651 | -0.001 |
SMSTORE6 | 0.000 | 0.000 | 0.558 | -66.970 | 0.000 | 0.000 | 12.044 | 14.614 | 9.586 | 10.274 | 0.000 | 14.067 | 10.596 | 0.000 | -2.132 | 0.000 | -2.637 | -0.000 |
SMSTORE7 | 0.000 | 0.000 | 0.623 | -66.970 | 0.000 | 0.000 | 12.054 | 14.614 | 9.586 | 10.271 | 0.000 | 14.065 | 10.469 | 0.000 | -2.112 | 0.000 | -2.600 | -0.001 |
SMSTORE8 | 0.000 | 0.000 | 0.867 | -80.474 | 0.000 | 0.000 | 12.057 | 14.614 | 9.586 | 10.146 | 0.000 | 14.395 | 23.674 | 0.000 | -2.060 | 0.000 | -2.805 | -0.003 |
Total Facility | 0.000 | 0.000 | 7.096 | -909.897 | 0.000 | 0.000 | 128.232 | 277.790 | 128.154 | 123.028 | 0.000 | 162.952 | 140.104 | 0.000 | -26.078 | 0.000 | -31.382 | -0.009 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-MAY-07:01 | 0.00 | 0.00 | 0.00 | -52716.42 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 344.32 | 0.00 | 311.61 | 51911.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 06-MAY-07:01 | 0.00 | 0.00 | 0.00 | -26486.12 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 176.00 | 0.00 | 176.47 | 26059.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 06-MAY-06:01 | 0.00 | 0.00 | 0.00 | -27380.85 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 47.91 | 0.00 | 4.66 | 27253.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 06-MAY-06:01 | 0.00 | 0.00 | 0.00 | -27493.22 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 45.50 | 0.00 | 4.54 | 27368.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 06-MAY-06:01 | 0.00 | 0.00 | 0.00 | -27317.34 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 47.35 | 0.00 | 4.69 | 27190.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -50036.18 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 622.64 | 0.00 | 427.61 | 48837.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -26194.96 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 313.64 | 0.00 | 241.01 | 25565.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -26133.35 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 313.58 | 0.00 | 240.84 | 25504.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -26259.52 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 311.59 | 0.00 | 239.04 | 25634.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -30179.70 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 295.43 | 0.00 | 271.43 | 29538.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-MAY-07:01 | 0.00 | 0.00 | 0.00 | -246846.13 | 0.00 | 0.00 | 295.50 | 450.00 | 1450.75 | 2134.26 | 0.00 | 2158.43 | 240357.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 02-JAN-08:61 | 0.00 | 0.00 | 63680.35 | 0.00 | 0.00 | 0.00 | 250.14 | 75.00 | 74.62 | 80.79 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -903.14 | -63257.77 |
SMSTORE1 | 02-JAN-08:61 | 0.00 | 0.00 | 28171.57 | 0.00 | 0.00 | 0.00 | 120.39 | 37.50 | 37.31 | 21.29 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -546.89 | -27841.16 |
SMSTORE2 | 01-JAN-08:62 | 0.00 | 0.00 | 31510.84 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8.87 | 0.00 | -510.50 | -31066.28 |
SMSTORE3 | 01-JAN-08:62 | 0.00 | 0.00 | 31874.19 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.04 | 0.00 | -495.79 | -31453.18 |
SMSTORE4 | 01-JAN-08:62 | 0.00 | 0.00 | 31778.24 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 6.35 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -483.40 | -31376.01 |
LGSTORE2 | 01-JAN-09:01 | 0.00 | 0.00 | 59702.89 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 625.82 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -696.24 | -59781.11 |
SMSTORE5 | 01-JAN-09:01 | 0.00 | 0.00 | 31459.31 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 313.39 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -397.71 | -31449.31 |
SMSTORE6 | 01-JAN-09:01 | 0.00 | 0.00 | 31379.84 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 314.85 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -395.10 | -31373.92 |
SMSTORE7 | 01-JAN-09:01 | 0.00 | 0.00 | 31562.40 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 320.38 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -384.85 | -31572.25 |
SMSTORE8 | 01-JAN-09:01 | 0.00 | 0.00 | 36421.50 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 337.71 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -362.83 | -36470.69 |
Total Facility | 02-JAN-08:61 | 0.00 | 0.00 | 288158.11 | 0.00 | 0.00 | 0.00 | 717.35 | 450.00 | 1452.23 | 585.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5776.86 | -285586.27 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.6819 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.6819 | 0.1534 | 1.0000 | Not calculated | 0.4115 | 0.1534 | ||
PSZ-AC_2:2 | 1.3597 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3597 | 0.1513 | 1.0000 | Not calculated | 0.2057 | 0.1513 | ||
PSZ-AC_3:3 | 1.3698 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3698 | 0.1502 | 1.0000 | Not calculated | 0.2057 | 0.1502 | ||
PSZ-AC_4:4 | 1.3743 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3743 | 0.1497 | 1.0000 | Not calculated | 0.2057 | 0.1497 | ||
PSZ-AC_5:5 | 1.3676 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3676 | 0.1504 | 1.0000 | Not calculated | 0.2057 | 0.1504 | ||
PSZ-AC_6:6 | 2.4575 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.4575 | 0.1674 | 1.0000 | Not calculated | 0.4115 | 0.1674 | ||
PSZ-AC_7:7 | 1.3015 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3015 | 0.1581 | 1.0000 | Not calculated | 0.2057 | 0.1581 | ||
PSZ-AC_8:8 | 1.2974 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2974 | 0.1586 | 1.0000 | Not calculated | 0.2057 | 0.1586 | ||
PSZ-AC_9:9 | 1.3045 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3045 | 0.1577 | 1.0000 | Not calculated | 0.2057 | 0.1577 | ||
PSZ-AC_10:10 | 1.5320 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.5320 | 0.1343 | 1.0000 | Not calculated | 0.2057 | 0.1343 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.6819 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.6819 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1534 | ||
PSZ-AC_2:2 | 1.3597 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3597 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1513 | ||
PSZ-AC_3:3 | 1.3698 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3698 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1502 | ||
PSZ-AC_4:4 | 1.3743 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3743 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1497 | ||
PSZ-AC_5:5 | 1.3676 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3676 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1504 | ||
PSZ-AC_6:6 | 2.4575 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.4575 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1674 | ||
PSZ-AC_7:7 | 1.3015 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3015 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1581 | ||
PSZ-AC_8:8 | 1.2974 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2974 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1586 | ||
PSZ-AC_9:9 | 1.3045 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3045 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1577 | ||
PSZ-AC_10:10 | 1.5320 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.5320 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1343 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.003540 | 56.2505 | 0.000610 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.003540 | 56.2505 | 0.000610 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.003540 | 56.25 | 0.000610 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.003540 | 56.25 | 0.000610 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6819 | 2.6819 | 2.6819 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3597 | 1.3597 | 1.3597 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3698 | 1.3698 | 1.3698 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3743 | 1.3743 | 1.3743 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3676 | 1.3676 | 1.3676 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4575 | 2.4575 | 2.4575 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3015 | 1.3015 | 1.3015 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2974 | 1.2974 | 1.2974 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3045 | 1.3045 | 1.3045 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5320 | 1.5320 | 1.5320 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.6819 | 2.6819 | 2.6819 | 2.6819 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.3597 | 1.3597 | 1.3597 | 1.3597 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.3698 | 1.3698 | 1.3698 | 1.3698 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.3743 | 1.3743 | 1.3743 | 1.3743 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3676 | 1.3676 | 1.3676 | 1.3676 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.4575 | 2.4575 | 2.4575 | 2.4575 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.3015 | 1.3015 | 1.3015 | 1.3015 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.2974 | 1.2974 | 1.2974 | 1.2974 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.3045 | 1.3045 | 1.3045 | 1.3045 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.5320 | 1.5320 | 1.5320 | 1.5320 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6819 | 2.6819 | 2.6819 | No | 0.4115 | 0.5091 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3597 | 1.3597 | 1.3597 | No | 0.2057 | 0.5175 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3698 | 1.3698 | 1.3698 | No | 0.2057 | 0.5130 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3743 | 1.3743 | 1.3743 | No | 0.2057 | 0.5083 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3676 | 1.3676 | 1.3676 | No | 0.2057 | 0.4986 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4575 | 2.4575 | 2.4575 | No | 0.4115 | 0.5258 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3015 | 1.3015 | 1.3015 | No | 0.2057 | 0.4853 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2974 | 1.2974 | 1.2974 | No | 0.2057 | 0.4851 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3045 | 1.3045 | 1.3045 | No | 0.2057 | 0.4703 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5320 | 1.5320 | 1.5320 | No | 0.2057 | 0.3976 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.6819 | 2.6819 | 2.6819 | 2.6819 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.3597 | 1.3597 | 1.3597 | 1.3597 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.3698 | 1.3698 | 1.3698 | 1.3698 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.3743 | 1.3743 | 1.3743 | 1.3743 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3676 | 1.3676 | 1.3676 | 1.3676 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.4575 | 2.4575 | 2.4575 | 2.4575 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.3015 | 1.3015 | 1.3015 | 1.3015 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.2974 | 1.2974 | 1.2974 | 1.2974 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.3045 | 1.3045 | 1.3045 | 1.3045 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.5320 | 1.5320 | 1.5320 | 1.5320 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.50 |
Number of hours not met | 0.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 3.95 | 109187.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 421.61 | 75490.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 277.79 | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 40.95 | 3786.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 125.92 | 12273.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 58.67 | 11790.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1053.11 |
Natural Gas | 0.00 | 3.95 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1057.06 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 70.05 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 132.89 |
Space Heating | 0.00 |
Space Cooling | 201.70 |
Fans (All) | 60.24 |
Service Water Heating | 28.07 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 503.80 |
Subtotal | 503.80 |
Natural Gas [MJ/m2] | |
Space Heating | 1.89 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 1.89 |
Subtotal | 1.89 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 26.28 |
Space Heating | 0.37 |
Space Cooling | 39.89 |
Fans (All) | 11.91 |
Service Water Heating | 5.55 |
Receptacle Equipment | 12.12 |
Miscellaneous | 3.87 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3140. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3200. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4323. | 8760. |
LTG_SCH_BASE_LPD1 | 4243. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3479. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8503.50 | 256.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8666.00 | 94.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7478.83 | 1280.50 | 0.67 | 0.00 | 0.00 |
SMSTORE3 | 7386.50 | 1371.17 | 2.33 | 0.00 | 0.00 |
SMSTORE4 | 7509.00 | 1249.67 | 1.33 | 0.00 | 0.00 |
LGSTORE2 | 7899.33 | 859.83 | 0.83 | 0.00 | 0.00 |
SMSTORE5 | 7985.17 | 774.17 | 0.67 | 0.00 | 0.00 |
SMSTORE6 | 7992.00 | 767.33 | 0.67 | 0.00 | 0.00 |
SMSTORE7 | 7967.17 | 790.50 | 2.33 | 0.00 | 0.00 |
SMSTORE8 | 7537.00 | 1203.33 | 19.67 | 0.00 | 0.00 |
Min | 7386.50 | 94.00 | 0.00 | 0.00 | 0.00 |
Max | 8666.00 | 1371.17 | 19.67 | 0.00 | 0.00 |
Average | 7892.45 | 864.70 | 2.85 | 0.00 | 0.00 |
Sum | 78924.50 | 8647.00 | 28.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25376.17 | 98.50 | 0.33 | 0.00 | 0.00 |
SMSTORE3 | 25375.83 | 98.83 | 0.33 | 0.00 | 0.00 |
SMSTORE4 | 25378.17 | 96.50 | 0.33 | 0.00 | 0.00 |
LGSTORE2 | 92970.00 | 239.00 | 2.00 | 0.00 | 0.00 |
SMSTORE5 | 45790.00 | 121.00 | 1.00 | 0.00 | 0.00 |
SMSTORE6 | 45791.00 | 120.00 | 1.00 | 0.00 | 0.00 |
SMSTORE7 | 45790.50 | 120.50 | 1.00 | 0.00 | 0.00 |
SMSTORE8 | 45776.50 | 134.00 | 1.50 | 0.00 | 0.00 |
Min | 25375.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 92970.00 | 239.00 | 2.00 | 0.00 | 0.00 |
Average | 48506.62 | 102.83 | 0.75 | 0.00 | 0.00 |
Sum | 485066.17 | 1028.33 | 7.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 7032.33 | 1727.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 7641.00 | 1119.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 6149.50 | 2610.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 6144.17 | 2615.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 6155.17 | 2604.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 6234.83 | 2525.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 6245.83 | 2514.00 | 0.17 | 0.00 | 0.00 |
SMSTORE6 | 6245.67 | 2514.17 | 0.17 | 0.00 | 0.00 |
SMSTORE7 | 6258.00 | 2501.67 | 0.33 | 0.00 | 0.00 |
SMSTORE8 | 6252.00 | 2494.67 | 13.33 | 0.00 | 0.00 |
Min | 6144.17 | 1119.00 | 0.00 | 0.00 | 0.00 |
Max | 7641.00 | 2615.83 | 13.33 | 0.00 | 0.00 |
Average | 6435.85 | 2322.75 | 1.40 | 0.00 | 0.00 |
Sum | 64358.50 | 23227.50 | 14.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 77548.33 | 11492.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 37934.50 | 5842.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 21034.17 | 4440.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 21082.00 | 4393.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 21010.83 | 4464.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 75200.83 | 18010.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 36860.67 | 9051.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 36835.00 | 9077.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 36913.17 | 8998.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 38069.67 | 7842.33 | 0.00 | 0.00 | 0.00 |
Min | 21010.83 | 4393.00 | 0.00 | 0.00 | 0.00 |
Max | 77548.33 | 18010.17 | 0.00 | 0.00 | 0.00 |
Average | 40248.92 | 8361.28 | 0.00 | 0.00 | 0.00 |
Sum | 402489.17 | 83612.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348522E+10 | 5992.70 | 12-JAN-15:00 | 23.60 | 14.20 | 0.134463E+10 | 1685.91 | 08-JAN-18:00 | 23.60 | 14.20 |
February | 0.581452E+10 | 10213.28 | 22-FEB-15:00 | 27.10 | 16.20 | 0.125780E+10 | 1685.96 | 20-FEB-18:00 | 27.10 | 16.20 |
March | 0.117735E+11 | 17572.51 | 28-MAR-16:10 | 35.40 | 18.76 | 0.139648E+10 | 1686.04 | 12-MAR-17:19 | 35.40 | 18.76 |
April | 0.184071E+11 | 51775.18 | 28-APR-07:02 | 29.48 | 17.52 | 0.136167E+10 | 1686.14 | 16-APR-17:10 | 29.48 | 17.52 |
May | 0.234069E+11 | 52716.67 | 06-MAY-07:01 | 30.00 | 17.75 | 0.140192E+10 | 1686.17 | 07-MAY-16:10 | 42.17 | 21.49 |
June | 0.234878E+11 | 49578.38 | 07-JUN-07:01 | 34.92 | 19.62 | 0.135490E+10 | 1686.15 | 03-JUN-12:30 | 34.92 | 19.62 |
July | 0.227278E+11 | 44003.50 | 07-JUL-07:01 | 33.33 | 24.39 | 0.141312E+10 | 1686.05 | 09-JUL-17:00 | 35.40 | 27.44 |
August | 0.215183E+11 | 41056.54 | 14-AUG-07:01 | 28.90 | 26.43 | 0.139439E+10 | 1686.06 | 26-AUG-12:09 | 32.65 | 28.45 |
September | 0.193220E+11 | 42989.54 | 26-SEP-07:02 | 25.87 | 19.87 | 0.136541E+10 | 1686.09 | 22-SEP-12:50 | 25.87 | 19.87 |
October | 0.175571E+11 | 44965.64 | 03-OCT-07:02 | 24.75 | 17.83 | 0.140970E+10 | 1686.04 | 08-OCT-17:00 | 29.40 | 19.91 |
November | 0.110739E+11 | 13658.61 | 08-NOV-15:00 | 29.90 | 18.01 | 0.136215E+10 | 1686.03 | 05-NOV-16:00 | 29.90 | 18.01 |
December | 0.500513E+10 | 8071.28 | 01-DEC-14:00 | 23.50 | 13.07 | 0.138882E+10 | 1685.94 | 03-DEC-13:09 | 24.08 | 14.17 |
Annual Sum or Average | 0.183579E+12 | 0.164510E+11 | ||||||||
Minimum of Months | 0.348522E+10 | 5992.70 | 23.50 | 13.07 | 0.125780E+10 | 1685.91 | 23.60 | 14.17 | ||
Maximum of Months | 0.234878E+11 | 52716.67 | 35.40 | 26.43 | 0.141312E+10 | 1686.17 | 42.17 | 28.45 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189173E+10 | 3447.71 | 12-JAN-15:00 | 23.60 | 14.20 | 0.687770E+09 | 843.08 | 08-JAN-18:19 | 23.60 | 14.20 |
February | 0.338528E+10 | 5449.21 | 22-FEB-15:00 | 27.10 | 16.20 | 0.632675E+09 | 843.18 | 05-FEB-18:19 | 27.10 | 16.20 |
March | 0.645383E+10 | 10287.85 | 11-MAR-08:63 | 24.43 | 17.41 | 0.698547E+09 | 843.17 | 19-MAR-17:49 | 23.57 | 15.04 |
April | 0.944183E+10 | 26277.16 | 28-APR-07:02 | 29.48 | 17.52 | 0.680825E+09 | 843.23 | 23-APR-17:40 | 29.48 | 17.52 |
May | 0.117500E+11 | 26486.40 | 06-MAY-07:01 | 30.00 | 17.75 | 0.700934E+09 | 843.05 | 07-MAY-12:00 | 40.90 | 21.35 |
June | 0.116433E+11 | 25451.97 | 05-JUN-07:01 | 32.63 | 21.35 | 0.677418E+09 | 843.13 | 18-JUN-17:49 | 32.62 | 23.52 |
July | 0.112931E+11 | 23854.24 | 07-JUL-07:01 | 33.33 | 24.39 | 0.706519E+09 | 843.02 | 09-JUL-12:09 | 33.33 | 25.98 |
August | 0.106651E+11 | 22690.62 | 14-AUG-07:01 | 28.90 | 26.43 | 0.697158E+09 | 843.15 | 20-AUG-17:00 | 26.30 | 25.51 |
September | 0.965339E+10 | 23574.09 | 26-SEP-07:02 | 25.87 | 19.87 | 0.682677E+09 | 843.04 | 03-SEP-17:19 | 25.87 | 19.87 |
October | 0.898477E+10 | 24839.12 | 02-OCT-07:02 | 24.92 | 18.38 | 0.704833E+09 | 843.08 | 29-OCT-17:40 | 27.90 | 19.31 |
November | 0.597049E+10 | 7199.75 | 04-NOV-14:00 | 30.30 | 17.17 | 0.681317E+09 | 843.09 | 26-NOV-18:40 | 22.03 | 14.98 |
December | 0.285349E+10 | 4559.17 | 02-DEC-14:00 | 24.10 | 13.15 | 0.701598E+09 | 843.12 | 17-DEC-18:19 | 17.53 | 14.18 |
Annual Sum or Average | 0.939863E+11 | 0.825227E+10 | ||||||||
Minimum of Months | 0.189173E+10 | 3447.71 | 23.60 | 13.15 | 0.632675E+09 | 843.02 | 17.53 | 14.18 | ||
Maximum of Months | 0.117500E+11 | 26486.40 | 33.33 | 26.43 | 0.706519E+09 | 843.23 | 40.90 | 25.98 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125933E+10 | 3133.33 | 12-JAN-15:00 | 23.60 | 14.20 | 0.403350E+09 | 842.90 | 14-JAN-13:00 | 21.60 | 15.18 |
February | 0.240072E+10 | 5268.65 | 22-FEB-14:00 | 27.00 | 16.33 | 0.377359E+09 | 842.92 | 18-FEB-13:09 | 27.00 | 16.33 |
March | 0.495177E+10 | 15267.11 | 30-MAR-06:03 | 21.25 | 16.72 | 0.431274E+09 | 842.98 | 11-MAR-13:09 | 21.25 | 16.72 |
April | 0.749845E+10 | 26917.21 | 20-APR-06:02 | 26.07 | 17.13 | 0.411381E+09 | 842.98 | 01-APR-12:09 | 26.07 | 17.13 |
May | 0.960651E+10 | 27380.64 | 06-MAY-06:01 | 29.38 | 17.57 | 0.427027E+09 | 843.00 | 13-MAY-12:09 | 31.58 | 22.16 |
June | 0.954526E+10 | 24839.46 | 07-JUN-06:01 | 33.87 | 19.45 | 0.417860E+09 | 843.03 | 03-JUN-12:09 | 33.87 | 19.45 |
July | 0.899149E+10 | 20967.72 | 07-JUL-06:01 | 32.27 | 25.09 | 0.420827E+09 | 842.98 | 29-JUL-12:09 | 31.93 | 26.84 |
August | 0.862321E+10 | 18984.10 | 03-AUG-06:01 | 28.43 | 23.36 | 0.432205E+09 | 842.94 | 19-AUG-12:09 | 30.15 | 27.29 |
September | 0.764319E+10 | 21579.58 | 27-SEP-06:02 | 23.70 | 20.40 | 0.411333E+09 | 843.03 | 23-SEP-12:00 | 23.70 | 20.40 |
October | 0.705346E+10 | 24009.88 | 02-OCT-06:02 | 22.92 | 17.86 | 0.420748E+09 | 843.00 | 14-OCT-12:09 | 30.13 | 20.41 |
November | 0.456674E+10 | 7248.29 | 04-NOV-13:00 | 30.10 | 17.26 | 0.405583E+09 | 842.96 | 04-NOV-12:09 | 30.10 | 17.26 |
December | 0.195899E+10 | 4496.28 | 02-DEC-14:00 | 24.10 | 13.15 | 0.412297E+09 | 842.91 | 09-DEC-13:20 | 18.77 | 12.68 |
Annual Sum or Average | 0.740991E+11 | 0.497124E+10 | ||||||||
Minimum of Months | 0.125933E+10 | 3133.33 | 21.25 | 13.15 | 0.377359E+09 | 842.90 | 18.77 | 12.68 | ||
Maximum of Months | 0.960651E+10 | 27380.64 | 33.87 | 25.09 | 0.432205E+09 | 843.03 | 33.87 | 27.29 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115315E+10 | 3019.18 | 12-JAN-15:00 | 23.60 | 14.20 | 0.401349E+09 | 842.90 | 14-JAN-13:00 | 21.60 | 15.18 |
February | 0.233203E+10 | 5219.03 | 22-FEB-14:00 | 27.00 | 16.33 | 0.377058E+09 | 842.92 | 18-FEB-13:09 | 27.00 | 16.33 |
March | 0.494504E+10 | 15526.71 | 30-MAR-06:03 | 21.25 | 16.72 | 0.431260E+09 | 842.98 | 11-MAR-13:09 | 21.25 | 16.72 |
April | 0.755462E+10 | 27047.43 | 20-APR-06:02 | 26.07 | 17.13 | 0.411385E+09 | 842.98 | 01-APR-12:09 | 26.07 | 17.13 |
May | 0.971826E+10 | 27493.01 | 06-MAY-06:01 | 29.38 | 17.57 | 0.427038E+09 | 843.00 | 13-MAY-12:09 | 31.58 | 22.16 |
June | 0.965173E+10 | 25013.85 | 07-JUN-06:01 | 33.87 | 19.45 | 0.417870E+09 | 843.03 | 03-JUN-12:09 | 33.87 | 19.45 |
July | 0.910624E+10 | 21185.78 | 07-JUL-06:01 | 32.27 | 25.09 | 0.420838E+09 | 842.98 | 29-JUL-12:09 | 31.93 | 26.84 |
August | 0.870894E+10 | 19116.41 | 03-AUG-06:01 | 28.43 | 23.36 | 0.432213E+09 | 842.94 | 19-AUG-12:09 | 30.15 | 27.29 |
September | 0.771439E+10 | 21707.20 | 27-SEP-06:02 | 23.70 | 20.40 | 0.411340E+09 | 843.03 | 23-SEP-12:00 | 23.70 | 20.40 |
October | 0.710616E+10 | 24205.96 | 02-OCT-06:02 | 22.92 | 17.86 | 0.420752E+09 | 843.00 | 14-OCT-12:09 | 30.13 | 20.41 |
November | 0.454444E+10 | 7248.37 | 04-NOV-13:00 | 30.10 | 17.26 | 0.405556E+09 | 842.96 | 04-NOV-12:09 | 30.10 | 17.26 |
December | 0.187055E+10 | 4453.68 | 02-DEC-14:00 | 24.10 | 13.15 | 0.411741E+09 | 842.91 | 02-DEC-13:09 | 24.10 | 13.15 |
Annual Sum or Average | 0.744055E+11 | 0.496840E+10 | ||||||||
Minimum of Months | 0.115315E+10 | 3019.18 | 21.25 | 13.15 | 0.377058E+09 | 842.90 | 21.25 | 13.15 | ||
Maximum of Months | 0.971826E+10 | 27493.01 | 33.87 | 25.09 | 0.432213E+09 | 843.03 | 33.87 | 27.29 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.981079E+09 | 2785.61 | 12-JAN-15:00 | 23.60 | 14.20 | 0.397964E+09 | 842.90 | 14-JAN-13:00 | 21.60 | 15.18 |
February | 0.215669E+10 | 5058.69 | 22-FEB-14:00 | 27.00 | 16.33 | 0.376267E+09 | 842.92 | 18-FEB-13:09 | 27.00 | 16.33 |
March | 0.476189E+10 | 14155.85 | 30-MAR-06:03 | 21.25 | 16.72 | 0.431160E+09 | 842.98 | 11-MAR-13:09 | 21.25 | 16.72 |
April | 0.741387E+10 | 26806.25 | 20-APR-06:02 | 26.07 | 17.13 | 0.411357E+09 | 842.98 | 01-APR-12:09 | 26.07 | 17.13 |
May | 0.960440E+10 | 27317.14 | 06-MAY-06:01 | 29.38 | 17.57 | 0.427011E+09 | 843.00 | 13-MAY-12:09 | 31.58 | 22.16 |
June | 0.954162E+10 | 24835.58 | 12-JUN-06:01 | 34.87 | 19.39 | 0.417844E+09 | 843.02 | 03-JUN-12:09 | 34.87 | 19.39 |
July | 0.900834E+10 | 20981.86 | 07-JUL-06:01 | 32.27 | 25.09 | 0.420814E+09 | 842.97 | 29-JUL-12:09 | 31.93 | 26.84 |
August | 0.859213E+10 | 18892.55 | 03-AUG-06:01 | 28.43 | 23.36 | 0.432186E+09 | 842.93 | 19-AUG-12:09 | 30.15 | 27.29 |
September | 0.759617E+10 | 21509.44 | 27-SEP-06:02 | 23.70 | 20.40 | 0.411313E+09 | 843.02 | 23-SEP-12:00 | 23.70 | 20.40 |
October | 0.696826E+10 | 24062.81 | 02-OCT-06:02 | 22.92 | 17.86 | 0.420724E+09 | 843.00 | 14-OCT-12:09 | 30.13 | 20.41 |
November | 0.437564E+10 | 7111.08 | 04-NOV-13:00 | 30.10 | 17.26 | 0.405454E+09 | 842.96 | 04-NOV-12:09 | 30.10 | 17.26 |
December | 0.168482E+10 | 4294.75 | 02-DEC-14:00 | 24.10 | 13.15 | 0.410476E+09 | 842.91 | 02-DEC-13:09 | 24.10 | 13.15 |
Annual Sum or Average | 0.726849E+11 | 0.496257E+10 | ||||||||
Minimum of Months | 0.981079E+09 | 2785.61 | 21.25 | 13.15 | 0.376267E+09 | 842.90 | 21.25 | 13.15 | ||
Maximum of Months | 0.960440E+10 | 27317.14 | 34.87 | 25.09 | 0.432186E+09 | 843.02 | 34.87 | 27.29 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178891E+10 | 5154.05 | 12-JAN-15:10 | 23.55 | 14.25 | 0.134735E+10 | 2247.81 | 28-JAN-15:39 | 18.27 | 11.45 |
February | 0.367752E+10 | 9282.68 | 22-FEB-15:10 | 27.00 | 16.16 | 0.128671E+10 | 2247.85 | 18-FEB-15:00 | 27.00 | 16.16 |
March | 0.838393E+10 | 16598.67 | 11-MAR-08:63 | 24.43 | 17.41 | 0.147889E+10 | 2248.02 | 11-MAR-15:00 | 30.20 | 19.50 |
April | 0.131907E+11 | 48471.99 | 28-APR-07:02 | 29.48 | 17.52 | 0.141106E+10 | 2248.04 | 15-APR-14:00 | 29.48 | 17.52 |
May | 0.171887E+11 | 50035.36 | 29-MAY-08:61 | 32.12 | 19.78 | 0.145958E+10 | 2248.14 | 27-MAY-14:50 | 32.12 | 19.78 |
June | 0.171197E+11 | 46061.78 | 07-JUN-07:01 | 34.92 | 19.62 | 0.143108E+10 | 2247.81 | 17-JUN-14:39 | 38.47 | 25.74 |
July | 0.160799E+11 | 41281.13 | 07-JUL-07:01 | 33.33 | 24.39 | 0.143985E+10 | 2248.04 | 22-JUL-14:20 | 29.57 | 26.96 |
August | 0.153868E+11 | 37710.88 | 08-AUG-07:01 | 30.50 | 24.42 | 0.148084E+10 | 2247.94 | 19-AUG-14:09 | 28.02 | 26.43 |
September | 0.135240E+11 | 40310.25 | 27-SEP-07:02 | 24.98 | 20.39 | 0.141082E+10 | 2247.81 | 02-SEP-14:09 | 24.98 | 20.39 |
October | 0.124502E+11 | 43462.01 | 02-OCT-07:02 | 24.92 | 18.38 | 0.143621E+10 | 2247.99 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.764475E+10 | 13256.05 | 04-NOV-14:20 | 30.27 | 17.30 | 0.138110E+10 | 2247.92 | 04-NOV-14:00 | 30.20 | 17.55 |
December | 0.287779E+10 | 7558.82 | 02-DEC-14:30 | 24.00 | 13.17 | 0.140231E+10 | 2247.87 | 02-DEC-15:00 | 22.70 | 13.55 |
Annual Sum or Average | 0.129313E+12 | 0.169658E+11 | ||||||||
Minimum of Months | 0.178891E+10 | 5154.05 | 23.55 | 13.17 | 0.128671E+10 | 2247.81 | 18.27 | 11.45 | ||
Maximum of Months | 0.171887E+11 | 50035.36 | 34.92 | 24.42 | 0.148084E+10 | 2248.14 | 38.47 | 26.96 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.791250E+09 | 2596.02 | 12-JAN-15:10 | 23.55 | 14.25 | 0.670187E+09 | 1123.87 | 14-JAN-15:20 | 21.57 | 15.20 |
February | 0.181079E+10 | 4843.84 | 22-FEB-15:10 | 27.00 | 16.16 | 0.642654E+09 | 1123.89 | 18-FEB-15:00 | 27.00 | 16.16 |
March | 0.433844E+10 | 8422.27 | 28-MAR-15:00 | 35.60 | 18.50 | 0.739416E+09 | 1123.98 | 11-MAR-15:00 | 35.60 | 18.50 |
April | 0.694062E+10 | 25292.56 | 28-APR-07:02 | 29.48 | 17.52 | 0.705501E+09 | 1123.97 | 22-APR-14:00 | 29.48 | 17.52 |
May | 0.908534E+10 | 26194.53 | 29-MAY-08:61 | 32.12 | 19.78 | 0.729754E+09 | 1124.04 | 27-MAY-14:39 | 32.12 | 19.78 |
June | 0.902838E+10 | 24160.29 | 07-JUN-07:01 | 34.92 | 19.62 | 0.715508E+09 | 1123.87 | 17-JUN-14:09 | 38.42 | 25.70 |
July | 0.845887E+10 | 21652.89 | 07-JUL-07:01 | 33.33 | 24.39 | 0.719891E+09 | 1123.98 | 22-JUL-14:20 | 29.57 | 26.96 |
August | 0.806955E+10 | 19784.54 | 08-AUG-07:01 | 30.50 | 24.42 | 0.740387E+09 | 1123.93 | 19-AUG-14:09 | 28.02 | 26.43 |
September | 0.709229E+10 | 21093.59 | 27-SEP-07:02 | 24.98 | 20.39 | 0.705375E+09 | 1123.87 | 02-SEP-14:09 | 24.98 | 20.39 |
October | 0.651191E+10 | 22712.43 | 02-OCT-07:02 | 24.92 | 18.38 | 0.718078E+09 | 1123.96 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.393737E+10 | 6982.85 | 04-NOV-14:20 | 30.27 | 17.30 | 0.690526E+09 | 1123.92 | 04-NOV-14:00 | 30.20 | 17.55 |
December | 0.135724E+10 | 3887.68 | 02-DEC-14:30 | 24.00 | 13.17 | 0.699785E+09 | 1123.90 | 02-DEC-15:00 | 22.70 | 13.55 |
Annual Sum or Average | 0.674221E+11 | 0.847706E+10 | ||||||||
Minimum of Months | 0.791250E+09 | 2596.02 | 23.55 | 13.17 | 0.642654E+09 | 1123.87 | 21.57 | 13.55 | ||
Maximum of Months | 0.908534E+10 | 26194.53 | 35.60 | 24.42 | 0.740387E+09 | 1124.04 | 38.42 | 26.96 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.759137E+09 | 2530.16 | 12-JAN-15:10 | 23.55 | 14.25 | 0.668070E+09 | 1123.87 | 14-JAN-15:20 | 21.57 | 15.20 |
February | 0.175966E+10 | 4787.16 | 22-FEB-15:10 | 27.00 | 16.16 | 0.642034E+09 | 1123.89 | 18-FEB-15:00 | 27.00 | 16.16 |
March | 0.428353E+10 | 8381.74 | 28-MAR-15:00 | 35.60 | 18.50 | 0.739373E+09 | 1123.98 | 11-MAR-15:00 | 35.60 | 18.50 |
April | 0.690123E+10 | 25226.56 | 28-APR-07:02 | 29.48 | 17.52 | 0.705496E+09 | 1123.97 | 22-APR-14:00 | 29.48 | 17.52 |
May | 0.905326E+10 | 26132.93 | 29-MAY-08:61 | 32.12 | 19.78 | 0.729751E+09 | 1124.04 | 27-MAY-14:39 | 32.12 | 19.78 |
June | 0.899679E+10 | 24085.26 | 07-JUN-07:01 | 34.92 | 19.62 | 0.715504E+09 | 1123.87 | 17-JUN-14:09 | 38.42 | 25.70 |
July | 0.843300E+10 | 21579.13 | 07-JUL-07:01 | 33.33 | 24.39 | 0.719887E+09 | 1123.98 | 22-JUL-14:20 | 29.57 | 26.96 |
August | 0.804182E+10 | 19723.92 | 08-AUG-07:01 | 30.50 | 24.42 | 0.740383E+09 | 1123.93 | 19-AUG-14:09 | 28.02 | 26.43 |
September | 0.706447E+10 | 21017.08 | 27-SEP-07:02 | 24.98 | 20.39 | 0.705371E+09 | 1123.87 | 02-SEP-14:09 | 24.98 | 20.39 |
October | 0.647669E+10 | 22650.63 | 02-OCT-07:02 | 24.92 | 18.38 | 0.718073E+09 | 1123.96 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.388994E+10 | 6941.13 | 04-NOV-14:20 | 30.27 | 17.30 | 0.690493E+09 | 1123.92 | 04-NOV-14:00 | 30.20 | 17.55 |
December | 0.131084E+10 | 3837.56 | 02-DEC-14:30 | 24.00 | 13.17 | 0.698670E+09 | 1123.90 | 02-DEC-15:00 | 22.70 | 13.55 |
Annual Sum or Average | 0.669704E+11 | 0.847310E+10 | ||||||||
Minimum of Months | 0.759137E+09 | 2530.16 | 23.55 | 13.17 | 0.642034E+09 | 1123.87 | 21.57 | 13.55 | ||
Maximum of Months | 0.905326E+10 | 26132.93 | 35.60 | 24.42 | 0.740383E+09 | 1124.04 | 38.42 | 26.96 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.680052E+09 | 2383.58 | 12-JAN-15:10 | 23.55 | 14.25 | 0.663072E+09 | 1123.87 | 14-JAN-15:20 | 21.57 | 15.20 |
February | 0.163178E+10 | 4677.98 | 22-FEB-15:10 | 27.00 | 16.16 | 0.640180E+09 | 1123.89 | 18-FEB-15:00 | 27.00 | 16.16 |
March | 0.416684E+10 | 8367.81 | 28-MAR-15:00 | 35.60 | 18.50 | 0.739192E+09 | 1123.98 | 11-MAR-15:00 | 35.60 | 18.50 |
April | 0.690726E+10 | 25298.20 | 28-APR-07:02 | 29.48 | 17.52 | 0.705495E+09 | 1123.97 | 22-APR-14:00 | 29.48 | 17.52 |
May | 0.914559E+10 | 26259.10 | 29-MAY-08:61 | 32.12 | 19.78 | 0.729758E+09 | 1124.05 | 27-MAY-14:39 | 32.12 | 19.78 |
June | 0.910279E+10 | 24271.72 | 07-JUN-07:01 | 34.92 | 19.62 | 0.715511E+09 | 1123.87 | 17-JUN-14:09 | 38.42 | 25.70 |
July | 0.855334E+10 | 21795.22 | 07-JUL-07:01 | 33.33 | 24.39 | 0.719899E+09 | 1123.98 | 22-JUL-14:20 | 29.57 | 26.96 |
August | 0.815402E+10 | 19945.07 | 08-AUG-07:01 | 30.50 | 24.42 | 0.740393E+09 | 1123.93 | 19-AUG-14:09 | 28.02 | 26.43 |
September | 0.714253E+10 | 21152.79 | 27-SEP-07:02 | 24.98 | 20.39 | 0.705379E+09 | 1123.87 | 02-SEP-14:09 | 24.98 | 20.39 |
October | 0.649580E+10 | 22777.16 | 02-OCT-07:02 | 24.92 | 18.38 | 0.718074E+09 | 1123.96 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.379798E+10 | 6904.12 | 04-NOV-14:20 | 30.27 | 17.30 | 0.690365E+09 | 1123.92 | 04-NOV-14:00 | 30.20 | 17.55 |
December | 0.119284E+10 | 3702.33 | 02-DEC-14:30 | 24.00 | 13.17 | 0.695574E+09 | 1123.90 | 02-DEC-15:00 | 22.70 | 13.55 |
Annual Sum or Average | 0.669708E+11 | 0.846289E+10 | ||||||||
Minimum of Months | 0.680052E+09 | 2383.58 | 23.55 | 13.17 | 0.640180E+09 | 1123.87 | 21.57 | 13.55 | ||
Maximum of Months | 0.914559E+10 | 26259.10 | 35.60 | 24.42 | 0.740393E+09 | 1124.05 | 38.42 | 26.96 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.616199E+09 | 2578.61 | 12-JAN-15:10 | 23.55 | 14.25 | 0.663185E+09 | 1123.87 | 14-JAN-15:20 | 21.57 | 15.20 |
February | 0.172947E+10 | 5342.15 | 22-FEB-14:00 | 27.00 | 16.33 | 0.638005E+09 | 1123.88 | 18-FEB-15:00 | 27.00 | 16.33 |
March | 0.471387E+10 | 9500.80 | 28-MAR-15:00 | 35.60 | 18.50 | 0.738781E+09 | 1123.99 | 11-MAR-15:00 | 35.60 | 18.50 |
April | 0.833291E+10 | 28466.60 | 28-APR-07:02 | 29.48 | 17.52 | 0.705638E+09 | 1123.98 | 15-APR-14:20 | 29.48 | 17.52 |
May | 0.112177E+11 | 30179.44 | 29-MAY-08:61 | 32.12 | 19.78 | 0.729931E+09 | 1124.07 | 27-MAY-14:39 | 32.12 | 19.78 |
June | 0.111521E+11 | 28434.33 | 13-JUN-07:01 | 32.87 | 23.76 | 0.715655E+09 | 1123.87 | 17-JUN-14:50 | 38.48 | 25.75 |
July | 0.105154E+11 | 25466.49 | 07-JUL-07:01 | 33.33 | 24.39 | 0.720125E+09 | 1123.90 | 22-JUL-14:09 | 29.58 | 26.98 |
August | 0.100858E+11 | 22799.57 | 09-AUG-07:01 | 30.30 | 25.37 | 0.740582E+09 | 1123.92 | 19-AUG-14:09 | 28.02 | 26.43 |
September | 0.876223E+10 | 24474.24 | 27-SEP-07:02 | 24.98 | 20.39 | 0.705576E+09 | 1123.87 | 02-SEP-14:20 | 24.98 | 20.39 |
October | 0.783585E+10 | 25990.15 | 02-OCT-07:02 | 24.92 | 18.38 | 0.718245E+09 | 1123.96 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.432494E+10 | 7812.19 | 04-NOV-14:10 | 30.28 | 17.23 | 0.690174E+09 | 1123.92 | 04-NOV-14:00 | 30.20 | 17.55 |
December | 0.118952E+10 | 3987.42 | 01-DEC-14:00 | 23.50 | 13.07 | 0.694005E+09 | 1123.89 | 09-DEC-15:30 | 19.35 | 13.13 |
Annual Sum or Average | 0.804760E+11 | 0.845990E+10 | ||||||||
Minimum of Months | 0.616199E+09 | 2578.61 | 23.50 | 13.07 | 0.638005E+09 | 1123.87 | 19.35 | 13.13 | ||
Maximum of Months | 0.112177E+11 | 30179.44 | 35.60 | 25.37 | 0.740582E+09 | 1124.07 | 38.48 | 26.98 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122992E+09 | 63681.07 | 02-JAN-08:61 | 7.38 |
February | 3596840.62 | 3588.78 | 11-FEB-08:62 | 11.12 |
March | 7183254.24 | 1992.94 | 11-MAR-08:07 | 24.43 |
April | 43945820.33 | 3839.42 | 28-APR-07:03 | 29.48 |
May | 40299367.92 | 4733.64 | 01-MAY-07:03 | 33.43 |
June | 26623183.16 | 4838.31 | 07-JUN-07:04 | 34.92 |
July | 25531658.02 | 4353.12 | 05-JUL-07:05 | 33.75 |
August | 26160892.99 | 3606.99 | 09-AUG-07:04 | 30.30 |
September | 35073868.76 | 3305.40 | 22-SEP-07:04 | 28.37 |
October | 25578209.52 | 2950.50 | 04-OCT-07:04 | 26.28 |
November | 297422.46 | 357.41 | 09-NOV-08:10 | 19.90 |
December | 6914195.70 | 13603.13 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.364197E+09 | |||
Minimum of Months | 297422.46 | 357.41 | 7.38 | |
Maximum of Months | 0.122992E+09 | 63681.07 | 34.92 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21601258.05 | 28172.90 | 02-JAN-08:61 | 7.38 |
February | 5211.43 | 8.69 | 25-FEB-08:20 | 18.77 |
March | 3117964.97 | 1133.48 | 11-MAR-08:07 | 24.43 |
April | 22364236.31 | 1950.86 | 28-APR-07:03 | 29.48 |
May | 16160507.91 | 2418.23 | 01-MAY-07:03 | 33.43 |
June | 10496581.13 | 2586.55 | 12-JUN-07:04 | 35.90 |
July | 9559320.56 | 2267.49 | 02-JUL-07:04 | 33.57 |
August | 10163778.42 | 1869.93 | 25-AUG-07:04 | 29.60 |
September | 16878377.55 | 1602.92 | 13-SEP-07:04 | 26.98 |
October | 13923380.60 | 1605.80 | 04-OCT-07:04 | 26.28 |
November | 251984.30 | 296.21 | 09-NOV-08:10 | 19.90 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.124523E+09 | |||
Minimum of Months | 0.00 | 0.00 | 7.38 | |
Maximum of Months | 22364236.31 | 28172.90 | 35.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 45887402.64 | 31511.57 | 01-JAN-08:62 | 8.17 |
February | 2341504.62 | 466.87 | 20-FEB-17:25 | 23.80 |
March | 33796744.14 | 1278.06 | 12-MAR-16:12 | 31.07 |
April | 0.135087E+09 | 2212.68 | 16-APR-16:11 | 38.97 |
May | 0.167736E+09 | 2554.64 | 28-MAY-16:11 | 42.10 |
June | 0.169876E+09 | 2748.40 | 10-JUN-17:11 | 42.30 |
July | 0.130284E+09 | 2385.64 | 02-JUL-16:11 | 40.37 |
August | 0.111127E+09 | 1885.86 | 06-AUG-16:11 | 36.20 |
September | 0.103513E+09 | 1697.25 | 24-SEP-16:11 | 34.57 |
October | 65990424.68 | 1744.71 | 01-OCT-16:11 | 35.13 |
November | 8075177.99 | 861.76 | 04-NOV-17:12 | 27.33 |
December | 158113.64 | 73.41 | 24-DEC-17:50 | 19.20 |
Annual Sum or Average | 0.973873E+09 | |||
Minimum of Months | 158113.64 | 73.41 | 8.17 | |
Maximum of Months | 0.169876E+09 | 31511.57 | 42.30 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61287924.60 | 31874.94 | 01-JAN-08:62 | 8.17 |
February | 2526051.13 | 470.85 | 20-FEB-17:25 | 23.80 |
March | 34005588.65 | 1279.71 | 12-MAR-16:12 | 31.07 |
April | 0.134476E+09 | 2213.22 | 16-APR-16:11 | 38.97 |
May | 0.166504E+09 | 2554.80 | 28-MAY-16:11 | 42.10 |
June | 0.169472E+09 | 2749.26 | 10-JUN-17:11 | 42.30 |
July | 0.129306E+09 | 2385.45 | 02-JUL-16:11 | 40.37 |
August | 0.109980E+09 | 1886.34 | 06-AUG-16:11 | 36.20 |
September | 0.102805E+09 | 1698.15 | 24-SEP-16:11 | 34.57 |
October | 65921286.51 | 1745.65 | 01-OCT-16:11 | 35.13 |
November | 8149383.20 | 863.88 | 04-NOV-17:12 | 27.33 |
December | 258734.29 | 93.10 | 24-DEC-17:40 | 19.50 |
Annual Sum or Average | 0.984693E+09 | |||
Minimum of Months | 258734.29 | 93.10 | 8.17 | |
Maximum of Months | 0.169472E+09 | 31874.94 | 42.30 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 84308488.68 | 31778.99 | 01-JAN-08:62 | 8.17 |
February | 2942720.50 | 473.11 | 20-FEB-17:25 | 23.80 |
March | 34975729.78 | 1280.22 | 12-MAR-16:12 | 31.07 |
April | 0.135687E+09 | 2213.07 | 16-APR-16:11 | 38.97 |
May | 0.168089E+09 | 2554.79 | 28-MAY-16:11 | 42.10 |
June | 0.170324E+09 | 2749.51 | 10-JUN-17:11 | 42.30 |
July | 0.131472E+09 | 2384.25 | 02-JUL-16:11 | 40.37 |
August | 0.111686E+09 | 1886.04 | 06-AUG-16:11 | 36.20 |
September | 0.104410E+09 | 1697.97 | 24-SEP-16:11 | 34.57 |
October | 66504149.52 | 1745.48 | 01-OCT-16:11 | 35.13 |
November | 8423385.29 | 865.88 | 04-NOV-17:12 | 27.33 |
December | 1322117.59 | 957.55 | 23-DEC-07:40 | 6.70 |
Annual Sum or Average | 0.102014E+10 | |||
Minimum of Months | 1322117.59 | 473.11 | 6.70 | |
Maximum of Months | 0.170324E+09 | 31778.99 | 42.30 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226633E+09 | 59703.46 | 01-JAN-09:01 | 9.20 |
February | 6746614.50 | 1707.94 | 02-FEB-08:05 | 8.07 |
March | 32444647.82 | 2534.43 | 12-MAR-16:12 | 31.07 |
April | 0.124976E+09 | 4509.63 | 16-APR-16:11 | 38.97 |
May | 0.131984E+09 | 5330.15 | 28-MAY-16:01 | 42.20 |
June | 0.107874E+09 | 5705.10 | 11-JUN-16:01 | 43.35 |
July | 0.117302E+09 | 4909.54 | 02-JUL-16:01 | 40.38 |
August | 85184829.70 | 3815.36 | 06-AUG-16:11 | 36.20 |
September | 0.102649E+09 | 3415.66 | 24-SEP-16:11 | 34.57 |
October | 83067978.64 | 3518.31 | 01-OCT-16:11 | 35.13 |
November | 14529013.18 | 1658.37 | 04-NOV-17:12 | 27.33 |
December | 7124797.36 | 13533.85 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.104052E+10 | |||
Minimum of Months | 6746614.50 | 1658.37 | 7.55 | |
Maximum of Months | 0.226633E+09 | 59703.46 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136060E+09 | 31459.60 | 01-JAN-09:01 | 9.20 |
February | 4922255.44 | 1201.86 | 11-FEB-08:62 | 11.12 |
March | 18705524.36 | 1301.02 | 12-MAR-16:12 | 31.07 |
April | 64775429.54 | 2282.27 | 16-APR-16:11 | 38.97 |
May | 61985850.66 | 2667.27 | 28-MAY-16:01 | 42.20 |
June | 50119269.65 | 2855.22 | 11-JUN-16:01 | 43.35 |
July | 56873267.38 | 2458.87 | 02-JUL-16:11 | 40.37 |
August | 40095925.90 | 1940.37 | 06-AUG-16:11 | 36.20 |
September | 49883215.38 | 1741.13 | 24-SEP-16:11 | 34.57 |
October | 43522752.16 | 1793.13 | 01-OCT-16:11 | 35.13 |
November | 8721942.96 | 876.31 | 04-NOV-17:12 | 27.33 |
December | 4928083.91 | 7801.13 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.540593E+09 | |||
Minimum of Months | 4922255.44 | 876.31 | 7.55 | |
Maximum of Months | 0.136060E+09 | 31459.60 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149220E+09 | 31380.13 | 01-JAN-09:01 | 9.20 |
February | 6587548.33 | 2991.40 | 11-FEB-08:62 | 11.12 |
March | 19069272.69 | 1300.22 | 12-MAR-16:12 | 31.07 |
April | 64833092.58 | 2281.49 | 16-APR-16:11 | 38.97 |
May | 62063562.39 | 2667.82 | 28-MAY-16:01 | 42.20 |
June | 50115256.64 | 2855.59 | 11-JUN-16:01 | 43.35 |
July | 56969916.71 | 2458.57 | 02-JUL-16:01 | 40.38 |
August | 40103902.62 | 1939.34 | 06-AUG-16:11 | 36.20 |
September | 49900229.33 | 1740.17 | 24-SEP-16:11 | 34.57 |
October | 43596186.99 | 1792.26 | 01-OCT-16:11 | 35.13 |
November | 8777087.25 | 876.19 | 04-NOV-17:12 | 27.33 |
December | 6630865.03 | 9411.42 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.557867E+09 | |||
Minimum of Months | 6587548.33 | 876.19 | 7.55 | |
Maximum of Months | 0.149220E+09 | 31380.13 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198297E+09 | 31562.69 | 01-JAN-09:01 | 9.20 |
February | 15208225.38 | 9244.53 | 11-FEB-08:62 | 11.12 |
March | 20575786.70 | 1304.51 | 12-MAR-16:12 | 31.07 |
April | 64142185.73 | 2283.24 | 16-APR-16:11 | 38.97 |
May | 62456947.41 | 2665.07 | 28-MAY-16:01 | 42.20 |
June | 50264623.13 | 2851.81 | 11-JUN-16:01 | 43.35 |
July | 56402960.75 | 2458.12 | 02-JUL-16:11 | 40.37 |
August | 40243900.46 | 1939.71 | 06-AUG-16:11 | 36.20 |
September | 49389955.57 | 1741.50 | 24-SEP-16:11 | 34.57 |
October | 43384876.16 | 1793.41 | 01-OCT-16:11 | 35.13 |
November | 9104695.79 | 880.34 | 04-NOV-17:12 | 27.33 |
December | 13465469.76 | 14489.15 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.622937E+09 | |||
Minimum of Months | 9104695.79 | 880.34 | 7.55 | |
Maximum of Months | 0.198297E+09 | 31562.69 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370344E+09 | 36421.82 | 01-JAN-09:01 | 9.20 |
February | 70023757.58 | 29036.47 | 11-FEB-08:62 | 11.12 |
March | 26500036.41 | 1339.00 | 12-MAR-16:12 | 31.07 |
April | 59826149.68 | 2308.98 | 16-APR-16:11 | 38.97 |
May | 55332631.52 | 2658.95 | 28-MAY-16:11 | 42.10 |
June | 45241984.63 | 2859.09 | 10-JUN-17:11 | 42.30 |
July | 48546432.60 | 2472.05 | 02-JUL-16:11 | 40.37 |
August | 32392544.51 | 1953.35 | 06-AUG-16:11 | 36.20 |
September | 44129784.79 | 1866.58 | 22-SEP-07:04 | 28.37 |
October | 42407153.53 | 1816.44 | 01-OCT-16:11 | 35.13 |
November | 9664868.31 | 916.99 | 04-NOV-17:12 | 27.33 |
December | 62155114.09 | 31144.62 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.866565E+09 | |||
Minimum of Months | 9664868.31 | 916.99 | 7.55 | |
Maximum of Months | 0.370344E+09 | 36421.82 | 42.30 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.549253E+10 | 3421.96 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.496476E+10 | 3421.96 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.549777E+10 | 3421.96 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.532115E+10 | 3421.96 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.549253E+10 | 3421.96 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.532179E+10 | 3421.96 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.549708E+10 | 3421.96 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.549285E+10 | 3421.96 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.532602E+10 | 3421.96 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.549253E+10 | 3421.96 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.530585E+10 | 3421.96 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.550226E+10 | 3421.96 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.647071E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.496476E+10 | 3421.96 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.550226E+10 | 3421.96 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.334781E+10 | 2090.38 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.302613E+10 | 2090.38 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.335104E+10 | 2090.38 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.324334E+10 | 2090.38 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.334781E+10 | 2090.38 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.324377E+10 | 2090.38 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.335056E+10 | 2090.38 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.334803E+10 | 2090.38 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.324631E+10 | 2090.38 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.334781E+10 | 2090.38 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.323401E+10 | 2090.38 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.335375E+10 | 2090.38 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.394404E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.302613E+10 | 2090.38 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.335375E+10 | 2090.38 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.241466E+10 | 2078.11 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.218750E+10 | 2078.11 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.247235E+10 | 2078.11 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.234375E+10 | 2078.11 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.244351E+10 | 2078.11 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.238702E+10 | 2078.11 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.240024E+10 | 2078.11 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.247235E+10 | 2078.11 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.234375E+10 | 2078.11 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.241466E+10 | 2078.11 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.234375E+10 | 2078.11 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.240024E+10 | 2078.11 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.286238E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.218750E+10 | 2078.11 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.247235E+10 | 2078.11 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194057E+10 |
February | 0.305697E+10 | 0.496476E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120651E+09 | 0.820142E+09 |
March | 0.335708E+10 | 0.549777E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122859E+10 | 0.197075E+09 |
April | 0.327081E+10 | 0.532115E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329589E+10 | 10332376.56 |
May | 0.336680E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466326E+10 | 2485890.38 |
June | 0.325380E+10 | 0.532179E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423136E+10 | 1307075.33 |
July | 0.339353E+10 | 0.549708E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341258E+10 | 663693.42 |
August | 0.334857E+10 | 0.549285E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289218E+10 | 1105401.47 |
September | 0.327932E+10 | 0.532602E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252526E+10 | 2114839.56 |
October | 0.338624E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218203E+10 | 36932380.24 |
November | 0.327446E+10 | 0.530585E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743424E+09 | 0.253056E+09 |
December | 0.340325E+10 | 0.550226E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5212153.26 | 0.168532E+10 |
Annual Sum or Average | 0.397770E+11 | 0.647071E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253004E+11 | 0.495111E+10 |
Minimum of Months | 0.305697E+10 | 0.496476E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 663693.42 |
Maximum of Months | 0.340325E+10 | 0.550226E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466326E+10 | 0.194057E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110639E+10 |
February | 0.152844E+10 | 0.302613E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68407362.82 | 0.446231E+09 |
March | 0.167849E+10 | 0.335104E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695274E+09 | 93283178.10 |
April | 0.163536E+10 | 0.324334E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185739E+10 | 4186308.87 |
May | 0.168335E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261149E+10 | 778005.80 |
June | 0.162685E+10 | 0.324377E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237964E+10 | 389711.12 |
July | 0.169671E+10 | 0.335056E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190479E+10 | 186439.43 |
August | 0.167424E+10 | 0.334803E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162521E+10 | 302718.92 |
September | 0.163961E+10 | 0.324631E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142691E+10 | 572115.88 |
October | 0.169307E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123915E+10 | 18711976.39 |
November | 0.163718E+10 | 0.323401E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422976E+09 | 0.136986E+09 |
December | 0.170157E+10 | 0.335375E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2960586.90 | 0.947833E+09 |
Annual Sum or Average | 0.198880E+11 | 0.394404E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142342E+11 | 0.275585E+10 |
Minimum of Months | 0.152844E+10 | 0.302613E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186439.43 |
Maximum of Months | 0.170157E+10 | 0.335375E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261149E+10 | 0.110639E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109259E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68321031.46 | 0.459281E+09 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685072E+09 | 0.102557E+09 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183523E+10 | 5192249.90 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258600E+10 | 1008920.45 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236077E+10 | 509957.98 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187551E+10 | 231932.73 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160538E+10 | 724314.99 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140483E+10 | 999324.02 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121372E+10 | 19514974.77 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418254E+09 | 0.144968E+09 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2960879.78 | 0.950031E+09 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140560E+11 | 0.277761E+10 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231932.73 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258600E+10 | 0.109259E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108136E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68321615.16 | 0.457330E+09 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685035E+09 | 0.102478E+09 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183488E+10 | 5262654.62 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258489E+10 | 1081694.51 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236004E+10 | 553080.74 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187426E+10 | 255122.74 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160474E+10 | 783042.98 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140444E+10 | 1111754.01 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121347E+10 | 19556649.43 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418259E+09 | 0.144764E+09 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2961008.07 | 0.946485E+09 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140513E+11 | 0.276103E+10 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255122.74 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258489E+10 | 0.108136E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106341E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68322522.03 | 0.452520E+09 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685235E+09 | 0.101280E+09 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183530E+10 | 5104034.80 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258561E+10 | 994158.43 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236057E+10 | 527387.18 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187510E+10 | 226032.88 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160533E+10 | 707965.48 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140484E+10 | 961407.86 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121379E+10 | 19460132.97 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418302E+09 | 0.143858E+09 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2961321.82 | 0.939237E+09 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140554E+11 | 0.272829E+10 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226032.88 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258561E+10 | 0.106341E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.241466E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181727E+10 |
February | 0.313522E+10 | 0.218750E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119673E+09 | 0.787932E+09 |
March | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120169E+10 | 0.181678E+09 |
April | 0.338259E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321919E+10 | 9865504.69 |
May | 0.349753E+10 | 0.244351E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454118E+10 | 2021052.45 |
June | 0.343071E+10 | 0.238702E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414337E+10 | 1256754.89 |
July | 0.344942E+10 | 0.240024E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329473E+10 | 388935.57 |
August | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281730E+10 | 1258191.02 |
September | 0.338259E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246121E+10 | 2063573.47 |
October | 0.344359E+10 | 0.241466E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212689E+10 | 36313320.29 |
November | 0.331698E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732551E+09 | 0.252250E+09 |
December | 0.344942E+10 | 0.240024E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5187152.91 | 0.162278E+10 |
Annual Sum or Average | 0.410346E+11 | 0.286238E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246630E+11 | 0.471507E+10 |
Minimum of Months | 0.313522E+10 | 0.218750E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388935.57 |
Maximum of Months | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454118E+10 | 0.181727E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102143E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68325543.70 | 0.441600E+09 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685996E+09 | 99320784.19 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183635E+10 | 5189522.81 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258792E+10 | 970760.34 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236253E+10 | 611783.56 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187681E+10 | 180920.54 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160665E+10 | 565776.48 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140485E+10 | 952355.13 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121484E+10 | 20261299.08 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418432E+09 | 0.142321E+09 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2962485.94 | 0.917426E+09 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140657E+11 | 0.265083E+10 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180920.54 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258792E+10 | 0.102143E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101460E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68326000.04 | 0.439358E+09 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686059E+09 | 98850558.84 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183647E+10 | 5151205.64 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258806E+10 | 958558.79 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236264E+10 | 606713.01 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187695E+10 | 179059.39 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160675E+10 | 554443.13 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140494E+10 | 934265.30 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121493E+10 | 20230959.99 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418445E+09 | 0.141966E+09 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2962491.17 | 0.913569E+09 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140665E+11 | 0.263696E+10 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179059.39 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258806E+10 | 0.101460E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998443E+09 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68327077.01 | 0.432534E+09 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686158E+09 | 97042111.10 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183650E+10 | 5038491.16 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258774E+10 | 930184.60 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236239E+10 | 612223.69 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187632E+10 | 176378.72 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160638E+10 | 573689.15 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140473E+10 | 926409.33 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121482E+10 | 20183364.93 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418463E+09 | 0.140768E+09 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2962539.66 | 0.903124E+09 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140648E+11 | 0.260035E+10 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176378.72 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258774E+10 | 0.998443E+09 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104735E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69158665.91 | 0.482612E+09 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695818E+09 | 0.130599E+09 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187643E+10 | 8020124.20 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266921E+10 | 2423214.87 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242371E+10 | 1545535.36 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194238E+10 | 597554.76 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164423E+10 | 1842015.36 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142603E+10 | 3330647.08 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122383E+10 | 24819931.12 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421181E+09 | 0.154214E+09 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2990505.63 | 0.947350E+09 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143950E+11 | 0.280470E+10 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597554.76 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266921E+10 | 0.104735E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 3421.96 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4043.28 | 15-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 3421.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1446.88 | 22-FEB-15:00 | 3614.44 | 10-FEB-12:05 |
March | 4050.04 | 03-MAR-13:09 | 3421.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.38 | 28-MAR-15:00 | 1577.45 | 18-MAR-17:00 |
April | 4050.04 | 01-APR-12:09 | 3421.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7285.70 | 15-APR-15:00 | 290.96 | 10-APR-07:10 |
May | 4050.04 | 05-MAY-12:09 | 3421.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8779.56 | 03-MAY-15:00 | 60.51 | 13-MAY-05:00 |
June | 4050.04 | 02-JUN-12:09 | 3421.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8804.82 | 06-JUN-15:00 | 75.46 | 18-JUN-05:00 |
July | 4050.04 | 01-JUL-12:09 | 3421.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7081.27 | 07-JUL-15:00 | 65.19 | 19-JUL-03:00 |
August | 4050.04 | 04-AUG-12:09 | 3421.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5868.59 | 07-AUG-15:00 | 65.82 | 15-AUG-24:00 |
September | 4050.04 | 01-SEP-12:09 | 3421.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5404.75 | 29-SEP-13:00 | 45.74 | 07-SEP-07:02 |
October | 4050.04 | 01-OCT-12:09 | 3421.96 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5498.77 | 02-OCT-14:00 | 505.76 | 11-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 3421.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2857.74 | 04-NOV-14:00 | 2233.31 | 30-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 3421.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 323.62 | 28-DEC-14:00 | 4850.35 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.74 | |||||
Maximum of Months | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8804.82 | 4850.35 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2090.38 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2370.79 | 15-JAN-17:50 |
February | 2024.96 | 03-FEB-13:09 | 2090.38 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.05 | 22-FEB-15:00 | 2222.04 | 10-FEB-12:05 |
March | 2024.96 | 03-MAR-13:09 | 2090.38 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2024.96 | 01-APR-12:09 | 2090.38 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.51 | 15-APR-15:00 | 161.50 | 10-APR-07:05 |
May | 2024.96 | 05-MAY-12:09 | 2090.38 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.51 | 03-MAY-15:00 | 18.43 | 13-MAY-05:00 |
June | 2024.96 | 02-JUN-12:09 | 2090.38 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.93 | 07-JUN-16:00 | 22.64 | 18-JUN-05:00 |
July | 2024.96 | 01-JUL-12:09 | 2090.38 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 18.87 | 19-JUL-03:00 |
August | 2024.96 | 04-AUG-12:09 | 2090.38 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.37 | 07-AUG-15:00 | 26.33 | 16-AUG-07:01 |
September | 2024.96 | 01-SEP-12:09 | 2090.38 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.83 | 29-SEP-13:00 | 17.92 | 07-SEP-07:02 |
October | 2024.96 | 01-OCT-12:09 | 2090.38 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.91 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 2090.38 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2090.38 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.33 | 28-DEC-14:00 | 2893.79 | 21-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.92 | |||||
Maximum of Months | 2024.96 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.93 | 2893.79 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2308.27 | 15-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.05 | 22-FEB-15:00 | 2227.43 | 10-FEB-12:05 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.51 | 15-APR-15:00 | 165.43 | 22-APR-18:10 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.52 | 03-MAY-15:00 | 20.73 | 15-MAY-03:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.93 | 07-JUN-16:00 | 26.64 | 18-JUN-05:00 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 20.65 | 19-JUL-03:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.37 | 07-AUG-15:00 | 127.47 | 20-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057.03 | 29-SEP-13:00 | 38.33 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.91 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.33 | 28-DEC-14:00 | 2882.46 | 21-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.65 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.93 | 2882.46 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2287.50 | 15-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.05 | 22-FEB-15:00 | 2213.75 | 10-FEB-12:05 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.51 | 15-APR-15:00 | 166.06 | 22-APR-18:10 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.52 | 03-MAY-15:00 | 22.56 | 15-MAY-03:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.93 | 07-JUN-16:00 | 27.74 | 18-JUN-05:00 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 21.16 | 19-JUL-03:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.37 | 07-AUG-15:00 | 134.01 | 20-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057.03 | 29-SEP-13:00 | 47.02 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.91 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.34 | 28-DEC-14:00 | 2865.59 | 21-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.16 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.93 | 2865.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2245.30 | 15-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.05 | 22-FEB-15:00 | 2160.21 | 10-FEB-12:05 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.51 | 15-APR-15:00 | 162.10 | 22-APR-18:10 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.52 | 03-MAY-15:00 | 21.60 | 15-MAY-03:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.93 | 07-JUN-16:00 | 27.15 | 18-JUN-05:00 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 20.36 | 19-JUL-03:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.37 | 07-AUG-15:00 | 123.50 | 20-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057.05 | 29-SEP-13:00 | 37.83 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.91 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.34 | 28-DEC-14:00 | 2820.15 | 21-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.93 | 2820.15 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2078.11 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3811.12 | 01-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 2078.11 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1440.85 | 22-FEB-15:00 | 3579.78 | 10-FEB-12:05 |
March | 5400.05 | 04-MAR-15:09 | 2078.11 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.37 | 28-MAR-15:00 | 1566.20 | 18-MAR-17:00 |
April | 5400.05 | 01-APR-14:09 | 2078.11 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7154.68 | 15-APR-15:00 | 284.90 | 10-APR-07:05 |
May | 5400.05 | 06-MAY-14:09 | 2078.11 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8712.18 | 03-MAY-15:00 | 41.31 | 15-MAY-03:00 |
June | 5400.05 | 03-JUN-14:09 | 2078.11 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8728.08 | 07-JUN-16:00 | 98.48 | 18-JUN-07:01 |
July | 5400.05 | 01-JUL-14:09 | 2078.11 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7038.45 | 07-JUL-15:00 | 38.19 | 19-JUL-03:00 |
August | 5400.05 | 05-AUG-14:09 | 2078.11 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5820.44 | 07-AUG-15:00 | 193.55 | 20-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 2078.11 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5355.90 | 29-SEP-13:00 | 73.16 | 04-SEP-07:01 |
October | 5400.05 | 07-OCT-14:09 | 2078.11 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5471.29 | 02-OCT-14:00 | 502.15 | 11-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 2078.11 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2849.02 | 04-NOV-14:00 | 2227.74 | 30-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2078.11 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.45 | 28-DEC-14:00 | 4741.33 | 21-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.19 | |||||
Maximum of Months | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8728.08 | 4741.33 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2178.04 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.03 | 22-FEB-15:00 | 2025.74 | 10-FEB-12:05 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.43 | 15-APR-15:00 | 161.89 | 10-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.46 | 03-MAY-15:00 | 20.58 | 15-MAY-03:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.18 | 07-JUN-16:00 | 52.37 | 18-JUN-07:01 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 18.63 | 19-JUL-03:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.38 | 07-AUG-15:00 | 88.13 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.78 | 29-SEP-13:00 | 40.17 | 04-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.77 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.68 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.50 | 28-DEC-14:00 | 2690.07 | 21-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.18 | 2690.07 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2178.04 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.03 | 22-FEB-15:00 | 2005.37 | 10-FEB-12:05 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.42 | 15-APR-15:00 | 161.76 | 10-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.46 | 03-MAY-15:00 | 20.51 | 15-MAY-03:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.18 | 07-JUN-16:00 | 51.93 | 18-JUN-07:01 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 18.53 | 19-JUL-03:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.38 | 07-AUG-15:00 | 85.39 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.78 | 29-SEP-13:00 | 39.98 | 04-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.77 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.68 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.50 | 28-DEC-14:00 | 2674.20 | 21-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.53 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.18 | 2674.20 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2178.04 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.03 | 22-FEB-15:00 | 1942.24 | 10-FEB-12:05 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.43 | 15-APR-15:00 | 161.24 | 10-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.45 | 03-MAY-15:00 | 20.37 | 15-MAY-03:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 07-JUN-16:00 | 51.93 | 18-JUN-07:01 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 18.36 | 19-JUL-03:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.38 | 07-AUG-15:00 | 91.19 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.77 | 29-SEP-13:00 | 40.38 | 04-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.75 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.68 | 04-NOV-14:00 | 1272.83 | 30-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.50 | 28-DEC-14:00 | 2629.61 | 21-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.36 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 2629.61 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2182.29 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 829.03 | 22-FEB-15:00 | 1809.19 | 10-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 905.42 | 18-MAR-17:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4208.31 | 15-APR-15:00 | 199.88 | 22-APR-18:10 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5040.75 | 03-MAY-15:00 | 53.29 | 15-MAY-03:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5080.09 | 06-JUN-15:00 | 66.86 | 18-JUN-07:01 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4061.93 | 07-JUL-15:00 | 48.23 | 19-JUL-03:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3370.53 | 07-AUG-15:00 | 214.81 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3105.34 | 29-SEP-13:00 | 115.39 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3151.95 | 02-OCT-14:00 | 290.29 | 11-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1636.39 | 04-NOV-14:00 | 1278.40 | 30-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 185.80 | 28-DEC-14:00 | 2601.98 | 21-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.23 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5080.09 | 2601.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5992.70 | 12-JAN-15:00 | 2700.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.42 |
February | 10213.28 | 22-FEB-15:00 | 2700.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1446.88 | 0.00 |
March | 17572.51 | 28-MAR-16:10 | 3375.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4992.35 | 0.00 |
April | 51775.18 | 28-APR-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 350.19 | 0.00 |
May | 52716.67 | 06-MAY-07:01 | 0.00 | 600.00 | 589.11 | 0.00 | 0.00 | 0.00 | 0.00 | 311.61 | 0.00 |
June | 49578.38 | 07-JUN-07:01 | 3375.03 | 750.00 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 619.91 | 0.00 |
July | 44003.50 | 07-JUL-07:01 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 489.15 | 0.00 |
August | 41056.54 | 14-AUG-07:01 | 3037.53 | 675.00 | 671.62 | 0.00 | 0.00 | 0.00 | 0.00 | 196.50 | 0.00 |
September | 42989.54 | 26-SEP-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 72.92 | 0.00 |
October | 44965.64 | 03-OCT-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 44.97 | 0.00 |
November | 13658.61 | 08-NOV-15:00 | 2700.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2680.93 | 0.00 |
December | 8071.28 | 01-DEC-14:00 | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5992.70 | 0.00 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52716.67 | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4992.35 | 181.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3447.71 | 12-JAN-15:00 | 1349.97 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.16 |
February | 5449.21 | 22-FEB-15:00 | 1349.97 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 823.05 | 0.00 |
March | 10287.85 | 11-MAR-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 16.24 | 0.00 |
April | 26277.16 | 28-APR-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 190.59 | 0.00 |
May | 26486.40 | 06-MAY-07:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 176.47 | 0.00 |
June | 25451.97 | 05-JUN-07:01 | 1687.47 | 375.00 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 251.54 | 0.00 |
July | 23854.24 | 07-JUL-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 275.15 | 0.00 |
August | 22690.62 | 14-AUG-07:01 | 1518.72 | 337.50 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 118.07 | 0.00 |
September | 23574.09 | 26-SEP-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 47.02 | 0.00 |
October | 24839.12 | 02-OCT-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 26.99 | 0.00 |
November | 7199.75 | 04-NOV-14:00 | 1349.97 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 0.00 |
December | 4559.17 | 02-DEC-14:00 | 2024.96 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3447.71 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26486.40 | 2024.96 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 78.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3133.33 | 12-JAN-15:00 | 1012.48 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.16 |
February | 5268.65 | 22-FEB-14:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 797.43 | 0.00 |
March | 15267.11 | 30-MAR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
April | 26917.21 | 20-APR-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 3.63 | 0.00 |
May | 27380.64 | 06-MAY-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 4.66 | 0.00 |
June | 24839.46 | 07-JUN-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 18.35 | 0.00 |
July | 20967.72 | 07-JUL-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 5.80 | 0.00 |
August | 18984.10 | 03-AUG-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 | 0.00 |
September | 21579.58 | 27-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
October | 24009.88 | 02-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
November | 7248.29 | 04-NOV-13:00 | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.96 | 0.00 |
December | 4496.28 | 02-DEC-14:00 | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3133.33 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27380.64 | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.96 | 78.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3019.18 | 12-JAN-15:00 | 1012.48 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.15 |
February | 5219.03 | 22-FEB-14:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 797.43 | 0.00 |
March | 15526.71 | 30-MAR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
April | 27047.43 | 20-APR-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 0.00 |
May | 27493.01 | 06-MAY-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 4.54 | 0.00 |
June | 25013.85 | 07-JUN-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 18.11 | 0.00 |
July | 21185.78 | 07-JUL-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 0.00 |
August | 19116.41 | 03-AUG-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 | 0.00 |
September | 21707.20 | 27-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 24205.96 | 02-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
November | 7248.37 | 04-NOV-13:00 | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.96 | 0.00 |
December | 4453.68 | 02-DEC-14:00 | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3019.18 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27493.01 | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.96 | 78.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2785.61 | 12-JAN-15:00 | 1012.48 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.15 |
February | 5058.69 | 22-FEB-14:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 797.43 | 0.00 |
March | 14155.85 | 30-MAR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
April | 26806.25 | 20-APR-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 | 0.00 |
May | 27317.14 | 06-MAY-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 4.69 | 0.00 |
June | 24835.58 | 12-JUN-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 16.86 | 0.00 |
July | 20981.86 | 07-JUL-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 5.76 | 0.00 |
August | 18892.55 | 03-AUG-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 | 0.00 |
September | 21509.44 | 27-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
October | 24062.81 | 02-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
November | 7111.08 | 04-NOV-13:00 | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.96 | 0.00 |
December | 4294.75 | 02-DEC-14:00 | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2785.61 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27317.14 | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.96 | 78.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5154.05 | 12-JAN-15:10 | 4657.54 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.01 |
February | 9282.68 | 22-FEB-15:10 | 4657.54 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1397.18 | 0.00 |
March | 16598.67 | 11-MAR-08:63 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 30.36 | 0.00 |
April | 48471.99 | 28-APR-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 326.28 | 0.00 |
May | 50035.36 | 29-MAY-08:61 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 427.61 | 0.00 |
June | 46061.78 | 07-JUN-07:01 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 584.58 | 0.00 |
July | 41281.13 | 07-JUL-07:01 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 457.17 | 0.00 |
August | 37710.88 | 08-AUG-07:01 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 269.08 | 0.00 |
September | 40310.25 | 27-SEP-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 37.57 | 0.00 |
October | 43462.01 | 02-OCT-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 0.00 |
November | 13256.05 | 04-NOV-14:20 | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2832.61 | 0.00 |
December | 7558.82 | 02-DEC-14:30 | 5197.55 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 46.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5154.05 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50035.36 | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2832.61 | 160.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2596.02 | 12-JAN-15:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.30 |
February | 4843.84 | 22-FEB-15:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 798.02 | 0.00 |
March | 8422.27 | 28-MAR-15:00 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 0.00 |
April | 25292.56 | 28-APR-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 189.26 | 0.00 |
May | 26194.53 | 29-MAY-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 241.01 | 0.00 |
June | 24160.29 | 07-JUN-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 334.83 | 0.00 |
July | 21652.89 | 07-JUL-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 263.66 | 0.00 |
August | 19784.54 | 08-AUG-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 156.25 | 0.00 |
September | 21093.59 | 27-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.05 | 0.00 |
October | 22712.43 | 02-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 | 0.00 |
November | 6982.85 | 04-NOV-14:20 | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.38 | 0.00 |
December | 3887.68 | 02-DEC-14:30 | 2598.70 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 26.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2596.02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26194.53 | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 91.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2530.16 | 12-JAN-15:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.30 |
February | 4787.16 | 22-FEB-15:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 798.02 | 0.00 |
March | 8381.74 | 28-MAR-15:00 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 0.00 |
April | 25226.56 | 28-APR-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 189.93 | 0.00 |
May | 26132.93 | 29-MAY-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 240.84 | 0.00 |
June | 24085.26 | 07-JUN-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 335.06 | 0.00 |
July | 21579.13 | 07-JUL-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 263.89 | 0.00 |
August | 19723.92 | 08-AUG-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 156.27 | 0.00 |
September | 21017.08 | 27-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.47 | 0.00 |
October | 22650.63 | 02-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 | 0.00 |
November | 6941.13 | 04-NOV-14:20 | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.38 | 0.00 |
December | 3837.56 | 02-DEC-14:30 | 2598.70 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 26.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2530.16 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26132.93 | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 91.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2383.58 | 12-JAN-15:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.29 |
February | 4677.98 | 22-FEB-15:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 798.02 | 0.00 |
March | 8367.81 | 28-MAR-15:00 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 0.00 |
April | 25298.20 | 28-APR-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 191.79 | 0.00 |
May | 26259.10 | 29-MAY-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 239.04 | 0.00 |
June | 24271.72 | 07-JUN-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 332.75 | 0.00 |
July | 21795.22 | 07-JUL-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 261.31 | 0.00 |
August | 19945.07 | 08-AUG-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 153.62 | 0.00 |
September | 21152.79 | 27-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.23 | 0.00 |
October | 22777.16 | 02-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 | 0.00 |
November | 6904.12 | 04-NOV-14:20 | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.38 | 0.00 |
December | 3702.33 | 02-DEC-14:30 | 2598.70 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 26.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2383.58 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26259.10 | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 91.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2578.61 | 12-JAN-15:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.90 |
February | 5342.15 | 22-FEB-14:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 801.67 | 0.00 |
March | 9500.80 | 28-MAR-15:00 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 0.00 |
April | 28466.60 | 28-APR-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 206.82 | 0.00 |
May | 30179.44 | 29-MAY-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 271.43 | 0.00 |
June | 28434.33 | 13-JUN-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 213.66 | 0.00 |
July | 25466.49 | 07-JUL-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 262.22 | 0.00 |
August | 22799.57 | 09-AUG-07:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 141.18 | 0.00 |
September | 24474.24 | 27-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.32 | 0.00 |
October | 25990.15 | 02-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 | 0.00 |
November | 7812.19 | 04-NOV-14:10 | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1631.32 | 0.00 |
December | 3987.42 | 01-DEC-14:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2578.61 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30179.44 | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 103.81 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.557298E+11 | 49774.02 | 14-JAN-14:50 | 0.333358E+10 | 109187.11 | 02-JAN-08:09 |
February | 0.565782E+11 | 59517.92 | 22-FEB-13:00 | 0.275731E+09 | 23008.11 | 02-FEB-08:09 |
March | 0.762694E+11 | 76156.48 | 28-MAR-13:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.899872E+11 | 92873.61 | 16-APR-14:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.110792E+12 | 105780.88 | 03-MAY-16:19 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.114143E+12 | 116472.89 | 10-JUN-16:40 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.115771E+12 | 119852.83 | 01-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.114628E+12 | 109494.66 | 27-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.101336E+12 | 98277.90 | 14-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.888279E+11 | 87581.77 | 04-OCT-13:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.707287E+11 | 71282.49 | 06-NOV-13:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.583153E+11 | 54601.41 | 28-DEC-14:09 | 0.344449E+09 | 41029.07 | 23-DEC-08:09 |
Annual Sum or Average | 0.105311E+13 | 0.395376E+10 | ||||
Minimum of Months | 0.557298E+11 | 49774.02 | 0.00 | 0.00 | ||
Maximum of Months | 0.115771E+12 | 119852.83 | 0.333358E+10 | 109187.11 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.402901E+10 | 7586.81 | 31-JAN-12:30 | 0.00 | 0.00 |
February | 0.448575E+10 | 8540.92 | 18-FEB-12:30 | 0.00 | 0.00 |
March | 0.630728E+10 | 9505.57 | 26-MAR-12:30 | 0.00 | 0.00 |
April | 0.750571E+10 | 10536.02 | 30-APR-11:00 | 0.00 | 0.00 |
May | 0.799482E+10 | 10989.58 | 28-MAY-12:30 | 0.00 | 0.00 |
June | 0.725367E+10 | 11206.30 | 04-JUN-12:20 | 0.00 | 0.00 |
July | 0.560707E+10 | 9357.62 | 04-JUL-12:30 | 0.00 | 0.00 |
August | 0.494304E+10 | 8694.15 | 06-AUG-12:30 | 0.00 | 0.00 |
September | 0.487586E+10 | 8569.00 | 27-SEP-12:20 | 0.00 | 0.00 |
October | 0.551502E+10 | 8716.12 | 03-OCT-12:30 | 0.00 | 0.00 |
November | 0.466333E+10 | 7797.25 | 02-NOV-11:00 | 0.00 | 0.00 |
December | 0.390655E+10 | 6758.53 | 02-DEC-12:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.670871E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.390655E+10 | 6758.53 | 0.00 | 0.00 | |
Maximum of Months | 0.799482E+10 | 11206.30 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.234911E+11 | 0.414298E+10 | 0.108325E+11 | 0.00 | 0.102149E+11 | 0.00 | 0.00 | 0.181587E+10 | 0.00 | 0.00 | 0.00 | 0.523246E+10 | 0.00 |
February | 0.212624E+11 | 0.352547E+10 | 0.980803E+10 | 0.00 | 0.920766E+10 | 0.00 | 0.00 | 0.807746E+10 | 0.00 | 0.00 | 0.00 | 0.469724E+10 | 0.00 |
March | 0.238408E+11 | 0.355226E+10 | 0.110075E+11 | 0.00 | 0.103599E+11 | 0.00 | 0.00 | 0.223764E+11 | 0.00 | 0.00 | 0.00 | 0.513263E+10 | 0.00 |
April | 0.227839E+11 | 0.309423E+10 | 0.105079E+11 | 0.00 | 0.996469E+10 | 0.00 | 0.00 | 0.388096E+11 | 0.00 | 0.00 | 0.00 | 0.482687E+10 | 0.00 |
May | 0.236617E+11 | 0.289565E+10 | 0.109147E+11 | 0.00 | 0.110473E+11 | 0.00 | 0.00 | 0.574019E+11 | 0.00 | 0.00 | 0.00 | 0.487061E+10 | 0.00 |
June | 0.230409E+11 | 0.263983E+10 | 0.106386E+11 | 0.00 | 0.113503E+11 | 0.00 | 0.00 | 0.618359E+11 | 0.00 | 0.00 | 0.00 | 0.463776E+10 | 0.00 |
July | 0.234131E+11 | 0.281613E+10 | 0.107945E+11 | 0.00 | 0.116062E+11 | 0.00 | 0.00 | 0.624130E+11 | 0.00 | 0.00 | 0.00 | 0.472778E+10 | 0.00 |
August | 0.238328E+11 | 0.305923E+10 | 0.110006E+11 | 0.00 | 0.115888E+11 | 0.00 | 0.00 | 0.603607E+11 | 0.00 | 0.00 | 0.00 | 0.478626E+10 | 0.00 |
September | 0.227918E+11 | 0.328962E+10 | 0.105148E+11 | 0.00 | 0.103414E+11 | 0.00 | 0.00 | 0.497029E+11 | 0.00 | 0.00 | 0.00 | 0.469516E+10 | 0.00 |
October | 0.234911E+11 | 0.375674E+10 | 0.108325E+11 | 0.00 | 0.102397E+11 | 0.00 | 0.00 | 0.355479E+11 | 0.00 | 0.00 | 0.00 | 0.496002E+10 | 0.00 |
November | 0.227593E+11 | 0.393260E+10 | 0.104978E+11 | 0.00 | 0.987140E+10 | 0.00 | 0.00 | 0.187476E+11 | 0.00 | 0.00 | 0.00 | 0.492003E+10 | 0.00 |
December | 0.234215E+11 | 0.424976E+10 | 0.108050E+11 | 0.00 | 0.101295E+11 | 0.00 | 0.00 | 0.452584E+10 | 0.00 | 0.00 | 0.00 | 0.518375E+10 | 0.00 |
Annual Sum or Average | 0.277790E+12 | 0.409545E+11 | 0.128154E+12 | 0.00 | 0.125922E+12 | 0.00 | 0.00 | 0.421615E+12 | 0.00 | 0.00 | 0.00 | 0.586706E+11 | 0.00 |
Minimum of Months | 0.212624E+11 | 0.263983E+10 | 0.980803E+10 | 0.00 | 0.920766E+10 | 0.00 | 0.00 | 0.181587E+10 | 0.00 | 0.00 | 0.00 | 0.463776E+10 | 0.00 |
Maximum of Months | 0.238408E+11 | 0.424976E+10 | 0.110075E+11 | 0.00 | 0.116062E+11 | 0.00 | 0.00 | 0.624130E+11 | 0.00 | 0.00 | 0.00 | 0.523246E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.333358E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.275731E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.344449E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.395376E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.333358E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17697.17 | 01-JAN-11:09 | 3786.68 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 9295.23 | 02-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 17697.17 | 01-FEB-10:09 | 3786.68 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 7489.03 | 02-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 17697.17 | 01-MAR-10:09 | 3786.68 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 7007.32 | 06-MAR-19:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 17697.17 | 01-APR-09:09 | 3786.68 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 8626.08 | 17-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 17697.17 | 01-MAY-09:09 | 3786.68 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 10194.84 | 17-MAY-16:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 17697.17 | 01-JUN-09:09 | 3786.68 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 12123.84 | 22-JUN-16:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 17697.17 | 01-JUL-09:09 | 3786.68 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 12273.33 | 01-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 17697.17 | 01-AUG-09:09 | 3786.68 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 11540.27 | 27-AUG-14:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 17697.17 | 01-SEP-09:09 | 3786.68 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 9897.37 | 14-SEP-16:19 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 17697.17 | 01-OCT-10:09 | 3786.68 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 8563.23 | 04-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 17697.17 | 01-NOV-09:09 | 3786.68 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7007.32 | 01-NOV-19:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 17697.17 | 01-DEC-10:09 | 3786.68 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 7866.42 | 23-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 17697.17 | 3786.68 | 8059.50 | 0.00 | 7007.32 | 0.00 | 0.00 | |||||
Maximum of Months | 17697.17 | 3786.68 | 8059.50 | 0.00 | 12273.33 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 11047.09 | 12-JAN-15:09 | 0.00 | 0.00 | 0.00 | 9685.12 | 21-JAN-14:09 | 0.00 | 01-JAN-00:10 |
February | 21306.05 | 22-FEB-13:00 | 0.00 | 0.00 | 0.00 | 7568.86 | 06-FEB-13:00 | 0.00 | 01-FEB-00:10 |
March | 38831.57 | 28-MAR-16:10 | 0.00 | 0.00 | 0.00 | 9653.26 | 10-MAR-12:09 | 0.00 | 01-MAR-00:10 |
April | 54907.18 | 16-APR-14:00 | 0.00 | 0.00 | 0.00 | 7550.88 | 11-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 66005.63 | 17-MAY-16:30 | 0.00 | 0.00 | 0.00 | 7541.27 | 16-MAY-12:00 | 0.00 | 01-MAY-00:10 |
June | 75490.70 | 10-JUN-15:00 | 0.00 | 0.00 | 0.00 | 7532.91 | 20-JUN-12:00 | 0.00 | 01-JUN-00:10 |
July | 74292.39 | 01-JUL-12:00 | 0.00 | 0.00 | 0.00 | 8667.80 | 19-JUL-13:39 | 0.00 | 01-JUL-00:10 |
August | 68685.30 | 27-AUG-14:09 | 0.00 | 0.00 | 0.00 | 9637.93 | 16-AUG-13:50 | 0.00 | 01-AUG-00:10 |
September | 59816.38 | 14-SEP-16:10 | 0.00 | 0.00 | 0.00 | 9506.78 | 15-SEP-12:39 | 0.00 | 01-SEP-00:10 |
October | 48943.55 | 02-OCT-12:00 | 0.00 | 0.00 | 0.00 | 7550.84 | 28-OCT-13:09 | 0.00 | 01-OCT-00:10 |
November | 30218.83 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 | 11790.47 | 13-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 14806.97 | 28-DEC-13:00 | 0.00 | 0.00 | 0.00 | 9666.96 | 19-DEC-12:09 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11047.09 | 0.00 | 0.00 | 0.00 | 7532.91 | 0.00 | |||
Maximum of Months | 75490.70 | 0.00 | 0.00 | 0.00 | 11790.47 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 49774.02 | 14-JAN-14:50 | 17697.17 | 8059.50 | 0.00 | 0.00 | 7007.32 | 0.00 | 0.00 | 9443.45 | 0.00 |
February | 59517.92 | 22-FEB-13:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 7007.32 | 0.00 | 0.00 | 21306.05 | 0.00 |
March | 76156.48 | 28-MAR-13:50 | 17697.17 | 8059.50 | 0.00 | 0.00 | 7007.32 | 0.00 | 0.00 | 36570.92 | 0.00 |
April | 92873.61 | 16-APR-14:50 | 17697.17 | 8059.50 | 0.00 | 0.00 | 8135.55 | 0.00 | 0.00 | 54714.36 | 0.00 |
May | 105780.88 | 03-MAY-16:19 | 17697.17 | 8059.50 | 0.00 | 0.00 | 9782.33 | 0.00 | 0.00 | 64821.32 | 0.00 |
June | 116472.89 | 10-JUN-16:40 | 17697.17 | 8059.50 | 0.00 | 0.00 | 11389.01 | 0.00 | 0.00 | 73911.10 | 0.00 |
July | 119852.83 | 01-JUL-12:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 12273.33 | 0.00 | 0.00 | 74292.39 | 0.00 |
August | 109494.66 | 27-AUG-12:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 11293.05 | 0.00 | 0.00 | 67036.76 | 0.00 |
September | 98277.90 | 14-SEP-16:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 9827.24 | 0.00 | 0.00 | 59379.76 | 0.00 |
October | 87581.77 | 04-OCT-13:20 | 17697.17 | 8059.50 | 0.00 | 0.00 | 7111.35 | 0.00 | 0.00 | 47169.96 | 0.00 |
November | 71282.49 | 06-NOV-13:09 | 17697.17 | 8059.50 | 0.00 | 0.00 | 7007.32 | 0.00 | 0.00 | 28846.82 | 0.00 |
December | 54601.41 | 28-DEC-14:09 | 17697.17 | 8059.50 | 0.00 | 0.00 | 7007.32 | 0.00 | 0.00 | 14270.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 49774.02 | 17697.17 | 8059.50 | 0.00 | 0.00 | 7007.32 | 0.00 | 0.00 | 9443.45 | 0.00 | |
Maximum of Months | 119852.83 | 17697.17 | 8059.50 | 0.00 | 0.00 | 12273.33 | 0.00 | 0.00 | 74292.39 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 109187.11 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 23008.11 | 02-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 41029.07 | 23-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 109187.11 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.50 | 0.50 | 24.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 24.50 | 0.50 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.50 | 0.50 | 24.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.59 | 0.00 | 24.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.62 | 0.00 | 24.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 24.59 | 0.00 | 24.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.62 | 0.00 | 24.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.00 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.62 | 0.00 | 24.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.61 | 0.00 | 24.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.50 | 24.59 | 0.00 | 24.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.62 | 0.00 | 24.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.52 | 0.00 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.61 | 0.00 | 24.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.67 | 0.00 | 24.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.50 | 24.62 | 0.00 | 24.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.67 | 0.00 | 24.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.66 | 0.00 | 24.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.71 | 0.00 | 24.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.66 | 0.00 | 24.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.33 | 24.69 | 0.00 | 24.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.71 | 0.00 | 24.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.61 | 0.00 | 24.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.70 | 0.00 | 24.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.63 | 0.00 | 24.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 24.67 | 0.00 | 24.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.70 | 0.00 | 24.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.62 | 0.00 | 24.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.70 | 0.00 | 24.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.64 | 0.00 | 24.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 24.67 | 0.00 | 24.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.70 | 0.00 | 24.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.65 | 0.00 | 24.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.73 | 0.00 | 24.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.66 | 0.00 | 24.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.33 | 24.68 | 0.00 | 24.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.73 | 0.00 | 24.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.81 | 0.00 | 26.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.05 | 0.00 | 25.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.72 | 0.00 | 24.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.53 | 0.00 | 24.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.50 | 25.21 | 0.00 | 25.21 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.81 | 0.00 | 26.81 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 395.83 | 22.88 | 1.50 | 22.88 | 0.50 | 22.88 |
February | 155.67 | 23.02 | 54.83 | 23.25 | 0.00 | 23.25 |
March | 44.17 | 23.49 | 236.50 | 23.83 | 0.00 | 23.83 |
April | 5.17 | 23.88 | 382.67 | 23.89 | 0.00 | 23.89 |
May | 15.00 | 23.89 | 496.00 | 23.89 | 15.00 | 23.89 |
June | 97.83 | 23.89 | 481.00 | 23.89 | 97.83 | 23.89 |
July | 273.83 | 23.89 | 495.00 | 23.89 | 273.83 | 23.89 |
August | 328.33 | 23.89 | 497.00 | 23.89 | 328.33 | 23.89 |
September | 207.17 | 23.89 | 479.00 | 23.89 | 207.17 | 23.89 |
October | 4.50 | 23.84 | 460.33 | 23.89 | 2.83 | 23.89 |
November | 42.33 | 23.49 | 237.67 | 23.83 | 0.00 | 23.83 |
December | 230.17 | 23.01 | 16.00 | 23.07 | 0.00 | 23.07 |
Annual Sum or Average | 1800.00 | 23.46 | 3837.50 | 23.75 | 925.50 | 23.77 |
Minimum of Months | 4.50 | 22.88 | 1.50 | 22.88 | 0.00 | 22.88 |
Maximum of Months | 395.83 | 23.89 | 497.00 | 23.89 | 328.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 313.17 | 23.18 | 3.50 | 23.18 | 0.00 | 23.18 |
February | 113.00 | 23.28 | 48.50 | 23.46 | 0.00 | 23.46 |
March | 31.17 | 23.69 | 210.50 | 23.86 | 0.00 | 23.86 |
April | 2.50 | 23.87 | 348.17 | 23.89 | 0.00 | 23.89 |
May | 10.00 | 23.89 | 495.67 | 23.89 | 10.00 | 23.89 |
June | 87.00 | 23.89 | 480.83 | 23.89 | 87.00 | 23.89 |
July | 237.33 | 23.89 | 495.00 | 23.89 | 237.33 | 23.89 |
August | 278.50 | 23.89 | 497.00 | 23.89 | 278.50 | 23.89 |
September | 165.33 | 23.89 | 478.83 | 23.89 | 165.33 | 23.89 |
October | 2.17 | 23.76 | 417.33 | 23.89 | 0.17 | 23.89 |
November | 30.50 | 23.65 | 197.50 | 23.86 | 0.00 | 23.86 |
December | 177.33 | 23.30 | 18.67 | 23.36 | 0.00 | 23.36 |
Annual Sum or Average | 1448.00 | 23.61 | 3691.50 | 23.81 | 778.33 | 23.82 |
Minimum of Months | 2.17 | 23.18 | 3.50 | 23.18 | 0.00 | 23.18 |
Maximum of Months | 313.17 | 23.89 | 497.00 | 23.89 | 278.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 273.50 | 22.98 | 2.00 | 22.99 | 0.00 | 22.99 |
February | 87.67 | 23.07 | 49.50 | 23.45 | 0.00 | 23.45 |
March | 22.50 | 23.78 | 208.17 | 24.09 | 0.50 | 24.09 |
April | 4.33 | 27.03 | 295.00 | 24.19 | 3.00 | 24.23 |
May | 23.83 | 26.20 | 374.83 | 24.27 | 23.83 | 24.38 |
June | 105.00 | 24.55 | 366.00 | 24.23 | 105.00 | 24.29 |
July | 247.17 | 24.23 | 369.00 | 24.18 | 247.17 | 24.19 |
August | 289.00 | 24.16 | 379.00 | 24.13 | 289.00 | 24.14 |
September | 185.50 | 24.19 | 360.00 | 24.13 | 185.50 | 24.15 |
October | 4.33 | 26.13 | 349.67 | 24.11 | 4.33 | 24.13 |
November | 18.50 | 23.51 | 198.67 | 24.01 | 0.00 | 24.01 |
December | 138.17 | 23.09 | 10.33 | 23.16 | 0.00 | 23.16 |
Annual Sum or Average | 1399.50 | 23.84 | 2962.17 | 24.03 | 858.33 | 24.08 |
Minimum of Months | 4.33 | 22.98 | 2.00 | 22.99 | 0.00 | 22.99 |
Maximum of Months | 289.00 | 27.03 | 379.00 | 24.27 | 289.00 | 24.38 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 295.50 | 22.96 | 0.67 | 22.96 | 0.00 | 22.96 |
February | 92.67 | 23.05 | 46.00 | 23.41 | 0.00 | 23.41 |
March | 22.17 | 23.76 | 207.50 | 24.08 | 0.50 | 24.09 |
April | 4.50 | 27.06 | 296.50 | 24.19 | 3.17 | 24.24 |
May | 24.00 | 26.27 | 374.83 | 24.27 | 24.00 | 24.39 |
June | 103.50 | 24.57 | 366.00 | 24.24 | 103.50 | 24.30 |
July | 242.33 | 24.24 | 369.00 | 24.18 | 242.33 | 24.20 |
August | 285.83 | 24.16 | 379.00 | 24.13 | 285.83 | 24.14 |
September | 183.33 | 24.20 | 360.00 | 24.13 | 183.33 | 24.15 |
October | 4.17 | 26.24 | 350.33 | 24.11 | 4.17 | 24.13 |
November | 18.83 | 23.49 | 196.67 | 24.00 | 0.00 | 24.00 |
December | 147.00 | 23.08 | 8.00 | 23.13 | 0.00 | 23.13 |
Annual Sum or Average | 1423.83 | 23.81 | 2954.50 | 24.02 | 846.83 | 24.07 |
Minimum of Months | 4.17 | 22.96 | 0.67 | 22.96 | 0.00 | 22.96 |
Maximum of Months | 295.50 | 27.06 | 379.00 | 24.27 | 285.83 | 24.39 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 313.67 | 22.89 | 0.67 | 22.89 | 0.17 | 22.89 |
February | 105.33 | 23.03 | 41.83 | 23.34 | 0.00 | 23.34 |
March | 26.33 | 23.71 | 200.67 | 24.07 | 0.50 | 24.08 |
April | 4.00 | 26.98 | 293.17 | 24.19 | 2.67 | 24.22 |
May | 24.33 | 26.14 | 375.00 | 24.26 | 24.33 | 24.37 |
June | 105.00 | 24.55 | 366.00 | 24.23 | 105.00 | 24.29 |
July | 245.67 | 24.23 | 369.00 | 24.17 | 245.67 | 24.19 |
August | 288.83 | 24.16 | 379.00 | 24.13 | 288.83 | 24.14 |
September | 185.67 | 24.19 | 360.00 | 24.13 | 185.67 | 24.14 |
October | 5.67 | 25.55 | 349.50 | 24.10 | 5.67 | 24.13 |
November | 21.83 | 23.45 | 188.67 | 23.99 | 0.00 | 23.99 |
December | 165.00 | 23.05 | 4.33 | 23.08 | 0.00 | 23.08 |
Annual Sum or Average | 1491.33 | 23.76 | 2927.83 | 24.00 | 858.50 | 24.05 |
Minimum of Months | 4.00 | 22.89 | 0.67 | 22.89 | 0.00 | 22.89 |
Maximum of Months | 313.67 | 26.98 | 379.00 | 24.26 | 288.83 | 24.37 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 312.83 | 22.85 | 0.17 | 22.84 | 0.17 | 22.84 |
February | 131.67 | 23.24 | 28.50 | 23.37 | 0.00 | 23.37 |
March | 23.50 | 23.70 | 165.50 | 23.94 | 0.33 | 23.95 |
April | 3.17 | 27.74 | 262.50 | 24.05 | 2.67 | 24.09 |
May | 20.00 | 25.28 | 344.00 | 24.06 | 20.00 | 24.13 |
June | 97.83 | 24.14 | 336.00 | 24.01 | 97.83 | 24.04 |
July | 248.83 | 24.04 | 338.00 | 24.02 | 248.83 | 24.03 |
August | 292.00 | 23.97 | 348.00 | 23.97 | 292.00 | 23.97 |
September | 180.83 | 24.04 | 330.00 | 24.00 | 180.83 | 24.01 |
October | 9.00 | 24.85 | 321.00 | 24.00 | 9.00 | 24.02 |
November | 16.00 | 23.58 | 156.00 | 23.92 | 0.00 | 23.92 |
December | 186.67 | 23.14 | 0.00 | 23.14 | 0.00 | 23.14 |
Annual Sum or Average | 1522.33 | 23.63 | 2629.67 | 23.85 | 851.67 | 23.89 |
Minimum of Months | 3.17 | 22.85 | 0.00 | 22.84 | 0.00 | 22.84 |
Maximum of Months | 312.83 | 27.74 | 348.00 | 24.06 | 292.00 | 24.13 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 315.17 | 22.81 | 0.17 | 22.80 | 0.17 | 22.80 |
February | 144.50 | 23.28 | 20.50 | 23.36 | 0.00 | 23.36 |
March | 30.17 | 23.71 | 146.00 | 23.94 | 0.17 | 23.94 |
April | 3.67 | 27.19 | 236.00 | 24.06 | 2.67 | 24.11 |
May | 21.50 | 25.12 | 344.00 | 24.06 | 21.50 | 24.12 |
June | 99.50 | 24.13 | 336.00 | 24.01 | 99.50 | 24.03 |
July | 251.83 | 24.04 | 338.00 | 24.02 | 251.83 | 24.03 |
August | 294.50 | 23.97 | 348.00 | 23.97 | 294.50 | 23.97 |
September | 184.83 | 24.03 | 330.00 | 23.99 | 184.83 | 24.00 |
October | 10.83 | 24.62 | 314.33 | 24.00 | 10.83 | 24.02 |
November | 20.17 | 23.63 | 135.17 | 23.92 | 0.00 | 23.92 |
December | 200.67 | 23.17 | 0.00 | 23.17 | 0.00 | 23.17 |
Annual Sum or Average | 1577.33 | 23.62 | 2548.17 | 23.84 | 866.00 | 23.88 |
Minimum of Months | 3.67 | 22.81 | 0.00 | 22.80 | 0.00 | 22.80 |
Maximum of Months | 315.17 | 27.19 | 348.00 | 24.06 | 294.50 | 24.12 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 316.67 | 22.77 | 0.33 | 22.77 | 0.33 | 22.77 |
February | 152.33 | 23.27 | 19.17 | 23.35 | 0.00 | 23.35 |
March | 32.00 | 23.70 | 143.00 | 23.93 | 0.17 | 23.94 |
April | 3.83 | 27.04 | 232.83 | 24.06 | 2.67 | 24.11 |
May | 21.50 | 25.11 | 344.00 | 24.06 | 21.50 | 24.12 |
June | 100.17 | 24.13 | 336.00 | 24.01 | 100.17 | 24.03 |
July | 253.33 | 24.04 | 338.00 | 24.02 | 253.33 | 24.02 |
August | 295.17 | 23.97 | 348.00 | 23.97 | 295.17 | 23.97 |
September | 185.17 | 24.03 | 330.00 | 23.99 | 185.17 | 24.00 |
October | 11.17 | 24.59 | 313.33 | 24.00 | 11.17 | 24.02 |
November | 22.00 | 23.64 | 131.00 | 23.92 | 0.00 | 23.92 |
December | 210.00 | 23.16 | 0.00 | 23.16 | 0.00 | 23.16 |
Annual Sum or Average | 1603.33 | 23.61 | 2535.67 | 23.84 | 869.67 | 23.88 |
Minimum of Months | 3.83 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
Maximum of Months | 316.67 | 27.04 | 348.00 | 24.06 | 295.17 | 24.12 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 319.83 | 22.69 | 0.83 | 22.69 | 0.83 | 22.68 |
February | 163.67 | 23.23 | 15.50 | 23.29 | 0.00 | 23.29 |
March | 38.00 | 23.66 | 139.50 | 23.91 | 0.17 | 23.92 |
April | 4.17 | 26.79 | 237.00 | 24.06 | 2.67 | 24.11 |
May | 21.67 | 25.13 | 344.00 | 24.06 | 21.67 | 24.12 |
June | 97.83 | 24.14 | 336.00 | 24.01 | 97.83 | 24.04 |
July | 249.00 | 24.04 | 338.00 | 24.02 | 249.00 | 24.03 |
August | 293.00 | 23.97 | 348.00 | 23.97 | 293.00 | 23.97 |
September | 182.33 | 24.03 | 330.00 | 23.99 | 182.33 | 24.00 |
October | 11.50 | 24.58 | 314.00 | 24.00 | 11.50 | 24.02 |
November | 24.67 | 23.59 | 129.50 | 23.90 | 0.00 | 23.90 |
December | 226.17 | 23.11 | 0.00 | 23.11 | 0.00 | 23.11 |
Annual Sum or Average | 1631.83 | 23.57 | 2532.33 | 23.82 | 859.00 | 23.86 |
Minimum of Months | 4.17 | 22.69 | 0.00 | 22.69 | 0.00 | 22.68 |
Maximum of Months | 319.83 | 26.79 | 348.00 | 24.06 | 293.00 | 24.12 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 318.17 | 22.66 | 3.33 | 22.64 | 3.33 | 22.62 |
February | 161.50 | 23.10 | 22.00 | 23.20 | 0.00 | 23.20 |
March | 42.00 | 23.53 | 169.83 | 23.89 | 0.50 | 23.90 |
April | 5.33 | 27.25 | 284.33 | 24.06 | 4.00 | 24.12 |
May | 22.33 | 25.35 | 344.00 | 24.08 | 22.33 | 24.15 |
June | 86.33 | 24.23 | 336.00 | 24.03 | 86.33 | 24.07 |
July | 215.00 | 24.09 | 338.00 | 24.04 | 215.00 | 24.06 |
August | 247.17 | 24.00 | 348.00 | 23.98 | 247.17 | 23.99 |
September | 160.17 | 24.08 | 330.00 | 24.01 | 160.17 | 24.03 |
October | 9.17 | 25.51 | 325.17 | 24.03 | 8.67 | 24.07 |
November | 26.50 | 23.46 | 163.33 | 23.89 | 0.00 | 23.89 |
December | 233.17 | 23.04 | 0.00 | 23.04 | 0.00 | 23.04 |
Annual Sum or Average | 1526.83 | 23.53 | 2664.00 | 23.82 | 747.50 | 23.87 |
Minimum of Months | 5.33 | 22.66 | 0.00 | 22.64 | 0.00 | 22.62 |
Maximum of Months | 318.17 | 27.25 | 348.00 | 24.08 | 247.17 | 24.15 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.07870 | 42.05250 | 0.11182 | 6.33586 |
February | 448.00000 | 23.58730 | 42.89986 | 0.28155 | 7.25735 |
March | 497.00000 | 23.85438 | 42.35166 | 0.40744 | 8.64984 |
April | 479.00000 | 23.88870 | 41.66892 | 0.48846 | 10.11404 |
May | 496.00000 | 23.89133 | 49.97137 | -0.2457 | 6.38361 |
June | 481.00000 | 23.89228 | 55.88040 | -0.1862 | 5.85450 |
July | 495.00000 | 23.89305 | 62.72912 | -0.1496 | 5.57192 |
August | 497.00000 | 23.89250 | 64.52960 | -0.1511 | 5.59619 |
September | 479.00000 | 23.89101 | 61.58955 | -0.1967 | 5.92595 |
October | 496.00000 | 23.88694 | 47.71457 | 0.52404 | 10.85142 |
November | 480.00000 | 23.85466 | 42.42852 | 0.40951 | 8.64939 |
December | 496.00000 | 23.48069 | 40.76256 | 0.23128 | 6.87511 |
Annual Sum or Average | 5840.00000 | 23.75766 | 49.59306 | 0.12577 | 7.33592 |
Minimum of Months | 448.00000 | 23.07870 | 40.76256 | -0.2457 | 5.57192 |
Maximum of Months | 497.00000 | 23.89305 | 64.52960 | 0.52404 | 10.85142 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.42963 | 42.10477 | 0.20481 | 6.54357 |
February | 448.00000 | 23.73380 | 41.65149 | 0.31897 | 7.42670 |
March | 497.00000 | 23.87678 | 41.07445 | 0.40302 | 8.49932 |
April | 479.00000 | 23.88834 | 41.02999 | 0.46217 | 9.55307 |
May | 496.00000 | 23.89117 | 49.04636 | -0.2985 | 6.95079 |
June | 481.00000 | 23.89169 | 54.90992 | -0.2458 | 6.36956 |
July | 495.00000 | 23.89217 | 61.55479 | -0.2068 | 5.99552 |
August | 497.00000 | 23.89195 | 63.21162 | -0.2080 | 6.03678 |
September | 479.00000 | 23.89064 | 59.84249 | -0.2507 | 6.44382 |
October | 496.00000 | 23.88653 | 46.03453 | 0.49163 | 10.15320 |
November | 480.00000 | 23.87450 | 40.94719 | 0.40017 | 8.43518 |
December | 496.00000 | 23.68001 | 39.98434 | 0.28180 | 7.04748 |
Annual Sum or Average | 5840.00000 | 23.81889 | 48.49661 | 0.11125 | 7.45193 |
Minimum of Months | 448.00000 | 23.42963 | 39.98434 | -0.2985 | 5.99552 |
Maximum of Months | 497.00000 | 23.89217 | 63.21162 | 0.49163 | 10.15320 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.21702 | 39.95943 | 0.14494 | 6.42946 |
February | 336.00000 | 23.72524 | 40.86199 | 0.31226 | 7.52109 |
March | 379.00000 | 24.00738 | 40.87228 | 0.43209 | 9.11408 |
April | 360.00000 | 24.10227 | 40.51276 | 0.50700 | 10.72179 |
May | 375.00000 | 24.14427 | 49.35206 | -0.2166 | 6.75198 |
June | 366.00000 | 24.14261 | 55.74934 | -0.1609 | 6.33349 |
July | 369.00000 | 24.13552 | 63.40139 | -0.1182 | 6.09206 |
August | 379.00000 | 24.10369 | 65.65711 | -0.1242 | 5.95853 |
September | 360.00000 | 24.10037 | 62.20167 | -0.1679 | 6.16859 |
October | 371.00000 | 24.07185 | 46.88883 | 0.54351 | 11.43995 |
November | 360.00000 | 23.96670 | 40.68199 | 0.42539 | 8.93097 |
December | 369.00000 | 23.60632 | 38.40638 | 0.25933 | 6.96871 |
Annual Sum or Average | 4395.00000 | 23.94492 | 48.78863 | 0.15112 | 7.69837 |
Minimum of Months | 336.00000 | 23.21702 | 38.40638 | -0.2166 | 5.95853 |
Maximum of Months | 379.00000 | 24.14427 | 65.65711 | 0.54351 | 11.43995 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.15254 | 40.15622 | 0.12410 | 6.37211 |
February | 336.00000 | 23.70631 | 40.96345 | 0.30469 | 7.46267 |
March | 379.00000 | 24.00612 | 40.89036 | 0.43163 | 9.10814 |
April | 360.00000 | 24.10294 | 40.50074 | 0.50888 | 10.76451 |
May | 375.00000 | 24.14558 | 49.29403 | -0.2122 | 6.72164 |
June | 366.00000 | 24.14392 | 55.66163 | -0.1569 | 6.31759 |
July | 369.00000 | 24.13691 | 63.25600 | -0.1143 | 6.08632 |
August | 379.00000 | 24.10475 | 65.53322 | -0.1214 | 5.95289 |
September | 360.00000 | 24.10132 | 62.10006 | -0.1653 | 6.15707 |
October | 371.00000 | 24.07245 | 46.85770 | 0.54506 | 11.47732 |
November | 360.00000 | 23.96414 | 40.71379 | 0.42411 | 8.91294 |
December | 369.00000 | 23.58002 | 38.52480 | 0.24954 | 6.90988 |
Annual Sum or Average | 4395.00000 | 23.93612 | 48.78002 | 0.14959 | 7.68296 |
Minimum of Months | 336.00000 | 23.15254 | 38.52480 | -0.2122 | 5.95289 |
Maximum of Months | 379.00000 | 24.14558 | 65.53322 | 0.54506 | 11.47732 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.04528 | 40.47391 | 0.09262 | 6.27836 |
February | 336.00000 | 23.66132 | 41.20471 | 0.28872 | 7.33334 |
March | 379.00000 | 23.99676 | 41.02165 | 0.42561 | 9.00582 |
April | 360.00000 | 24.09948 | 40.54913 | 0.50556 | 10.68637 |
May | 375.00000 | 24.14252 | 49.36350 | -0.2149 | 6.72546 |
June | 366.00000 | 24.14086 | 55.76701 | -0.1593 | 6.31005 |
July | 369.00000 | 24.13402 | 63.39088 | -0.1159 | 6.07437 |
August | 379.00000 | 24.10162 | 65.71485 | -0.1234 | 5.94328 |
September | 360.00000 | 24.09795 | 62.29198 | -0.1678 | 6.15575 |
October | 371.00000 | 24.06894 | 46.97708 | 0.54248 | 11.41150 |
November | 360.00000 | 23.95391 | 40.84941 | 0.41822 | 8.81609 |
December | 369.00000 | 23.52519 | 38.76515 | 0.23140 | 6.80562 |
Annual Sum or Average | 4395.00000 | 23.91549 | 48.93935 | 0.14176 | 7.62545 |
Minimum of Months | 336.00000 | 23.04528 | 38.76515 | -0.2149 | 5.94328 |
Maximum of Months | 379.00000 | 24.14252 | 65.71485 | 0.54248 | 11.41150 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.92990 | 42.22963 | 0.05480 | 6.05759 |
February | 308.00000 | 23.62724 | 42.56509 | 0.27293 | 7.08135 |
March | 348.00000 | 23.91301 | 42.15092 | 0.41016 | 8.68724 |
April | 330.00000 | 23.97942 | 41.76319 | 0.49288 | 10.33152 |
May | 344.00000 | 23.99133 | 50.91697 | -0.2363 | 6.62251 |
June | 336.00000 | 23.97586 | 57.39981 | -0.1832 | 6.11241 |
July | 338.00000 | 24.00406 | 65.05371 | -0.1325 | 5.93230 |
August | 348.00000 | 23.96037 | 67.46141 | -0.1443 | 5.80048 |
September | 330.00000 | 23.97410 | 63.91073 | -0.1868 | 6.09703 |
October | 340.00000 | 23.97081 | 48.14066 | 0.53390 | 11.15285 |
November | 330.00000 | 23.91003 | 41.84148 | 0.40999 | 8.62493 |
December | 338.00000 | 23.47598 | 40.53044 | 0.21351 | 6.63189 |
Annual Sum or Average | 4030.00000 | 23.81030 | 50.40951 | 0.12346 | 7.42446 |
Minimum of Months | 308.00000 | 22.92990 | 40.53044 | -0.2363 | 5.80048 |
Maximum of Months | 348.00000 | 24.00406 | 67.46141 | 0.53390 | 11.15285 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.88611 | 42.16463 | 0.03798 | 6.01798 |
February | 308.00000 | 23.61547 | 42.52843 | 0.26060 | 6.95578 |
March | 348.00000 | 23.91243 | 42.14678 | 0.39720 | 8.46138 |
April | 330.00000 | 23.97884 | 41.74302 | 0.47492 | 9.95734 |
May | 344.00000 | 23.99079 | 50.97845 | -0.2648 | 6.90847 |
June | 336.00000 | 23.97533 | 57.56446 | -0.2119 | 6.34035 |
July | 338.00000 | 24.00332 | 65.35299 | -0.1590 | 6.08260 |
August | 348.00000 | 23.95974 | 67.82029 | -0.1693 | 5.95762 |
September | 330.00000 | 23.97326 | 64.18568 | -0.2106 | 6.28661 |
October | 340.00000 | 23.97040 | 48.23689 | 0.51752 | 10.78335 |
November | 330.00000 | 23.90946 | 41.84501 | 0.39767 | 8.41203 |
December | 338.00000 | 23.45877 | 40.45547 | 0.20119 | 6.54858 |
Annual Sum or Average | 4030.00000 | 23.80381 | 50.49892 | 0.10393 | 7.39090 |
Minimum of Months | 308.00000 | 22.88611 | 40.45547 | -0.2648 | 5.95762 |
Maximum of Months | 348.00000 | 24.00332 | 67.82029 | 0.51752 | 10.78335 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.84921 | 42.26271 | 0.02656 | 6.00869 |
February | 308.00000 | 23.59916 | 42.61140 | 0.25373 | 6.90920 |
March | 348.00000 | 23.91034 | 42.18901 | 0.39453 | 8.42119 |
April | 330.00000 | 23.97855 | 41.75975 | 0.47349 | 9.92817 |
May | 344.00000 | 23.99060 | 51.00227 | -0.2662 | 6.92318 |
June | 336.00000 | 23.97515 | 57.59849 | -0.2133 | 6.35104 |
July | 338.00000 | 24.00310 | 65.39253 | -0.1601 | 6.08812 |
August | 348.00000 | 23.95957 | 67.86634 | -0.1704 | 5.96388 |
September | 330.00000 | 23.97302 | 64.23290 | -0.2118 | 6.29542 |
October | 340.00000 | 23.97012 | 48.27029 | 0.51638 | 10.75781 |
November | 330.00000 | 23.90777 | 41.88601 | 0.39543 | 8.37720 |
December | 338.00000 | 23.43501 | 40.54116 | 0.19285 | 6.50999 |
Annual Sum or Average | 4030.00000 | 23.79700 | 50.54794 | 0.10059 | 7.37633 |
Minimum of Months | 308.00000 | 22.84921 | 40.54116 | -0.2662 | 5.96388 |
Maximum of Months | 348.00000 | 24.00310 | 67.86634 | 0.51638 | 10.75781 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.76119 | 42.49749 | 0.00229 | 6.02815 |
February | 308.00000 | 23.54903 | 42.84503 | 0.23726 | 6.83191 |
March | 348.00000 | 23.90163 | 42.30621 | 0.39016 | 8.37122 |
April | 330.00000 | 23.97851 | 41.77069 | 0.47605 | 9.98339 |
May | 344.00000 | 23.99099 | 50.95987 | -0.2592 | 6.85116 |
June | 336.00000 | 23.97551 | 57.51288 | -0.2060 | 6.29241 |
July | 338.00000 | 24.00378 | 65.22438 | -0.1528 | 6.05143 |
August | 348.00000 | 23.96007 | 67.68026 | -0.1636 | 5.92374 |
September | 330.00000 | 23.97348 | 64.11771 | -0.2057 | 6.24850 |
October | 340.00000 | 23.97028 | 48.27247 | 0.51930 | 10.82523 |
November | 330.00000 | 23.90145 | 41.98742 | 0.39272 | 8.34657 |
December | 338.00000 | 23.36575 | 40.77443 | 0.17277 | 6.44480 |
Annual Sum or Average | 4030.00000 | 23.77888 | 50.57432 | 0.09836 | 7.34856 |
Minimum of Months | 308.00000 | 22.76119 | 40.77443 | -0.2592 | 5.92374 |
Maximum of Months | 348.00000 | 24.00378 | 67.68026 | 0.51930 | 10.82523 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.73548 | 42.55176 | -0.0119 | 6.15378 |
February | 308.00000 | 23.48701 | 43.00466 | 0.22353 | 6.93201 |
March | 348.00000 | 23.88285 | 42.40974 | 0.40373 | 8.71443 |
April | 330.00000 | 23.98620 | 41.63282 | 0.52680 | 11.11626 |
May | 344.00000 | 23.99985 | 50.38112 | -0.1694 | 6.15649 |
June | 336.00000 | 23.98313 | 56.45673 | -0.1193 | 5.80664 |
July | 338.00000 | 24.01595 | 63.46292 | -0.0744 | 5.84538 |
August | 348.00000 | 23.96974 | 65.52146 | -0.0901 | 5.65605 |
September | 330.00000 | 23.98427 | 62.39831 | -0.1367 | 5.87201 |
October | 340.00000 | 23.97968 | 47.72571 | 0.56488 | 11.92908 |
November | 330.00000 | 23.89362 | 41.95505 | 0.41155 | 8.73663 |
December | 338.00000 | 23.30504 | 40.82301 | 0.15630 | 6.52392 |
Annual Sum or Average | 4030.00000 | 23.77017 | 49.93163 | 0.13892 | 7.44989 |
Minimum of Months | 308.00000 | 22.73548 | 40.82301 | -0.1694 | 5.65605 |
Maximum of Months | 348.00000 | 24.01595 | 65.52146 | 0.56488 | 11.92908 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.148935E+10 | 0.396531E+09 | 164.83 | 0.132330E+10 | 0.166047E+09 | 0.00 | 0.31 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 7587.50 | 12-JAN-15:00 | 7037.62 | 12-JAN-15:00 | 1315.86 | 14-JAN-14:00 | 2008.75 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.626964E+10 | 0.165171E+10 | 321.50 | 0.541684E+10 | 0.852799E+09 | 0.00 | 0.53 | 22-FEB-15:00 | 0.00 | 01-FEB-00:10 | 13768.41 | 22-FEB-15:00 | 12476.09 | 22-FEB-15:00 | 3471.17 | 25-FEB-18:05 | 3644.62 | 22-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.166694E+11 | 0.445087E+10 | 467.50 | 0.142954E+11 | 0.237397E+10 | 0.00 | 0.86 | 28-MAR-16:30 | 0.00 | 01-MAR-00:10 | 26101.14 | 11-MAR-08:63 | 23009.67 | 28-MAR-16:10 | 6654.00 | 11-MAR-08:63 | 6624.48 | 28-MAR-16:30 | 0.00 | 01-MAR-00:10 |
April | 0.276709E+11 | 0.782366E+10 | 481.63 | 0.247182E+11 | 0.295268E+10 | 0.00 | 1.00 | 02-APR-07:03 | 0.00 | 01-APR-00:05 | 63398.92 | 27-APR-07:02 | 59826.29 | 28-APR-07:02 | 11846.17 | 27-APR-07:02 | 14906.90 | 27-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.399831E+11 | 0.113690E+11 | 501.77 | 0.321441E+11 | 0.783893E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 68446.06 | 24-MAY-07:02 | 59753.70 | 06-MAY-07:01 | 28544.94 | 24-MAY-07:02 | 15712.14 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.448228E+11 | 0.123118E+11 | 488.88 | 0.321831E+11 | 0.126397E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 69251.40 | 26-JUN-07:01 | 56873.02 | 07-JUN-07:01 | 32017.05 | 26-JUN-07:03 | 16116.76 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.500637E+11 | 0.126240E+11 | 502.76 | 0.301909E+11 | 0.198728E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 70295.61 | 25-JUL-07:01 | 50546.66 | 07-JUL-07:01 | 35000.67 | 25-JUL-07:03 | 15818.87 | 05-JUL-07:01 | 0.00 | 01-JUL-00:03 |
August | 0.493092E+11 | 0.119856E+11 | 503.34 | 0.279562E+11 | 0.213530E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 69745.04 | 10-AUG-07:01 | 46665.53 | 14-AUG-07:01 | 32152.00 | 10-AUG-07:04 | 15181.38 | 08-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.409028E+11 | 0.100785E+11 | 486.10 | 0.248787E+11 | 0.160242E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 69421.48 | 03-SEP-07:01 | 49197.58 | 26-SEP-07:02 | 31082.51 | 03-SEP-07:03 | 14766.10 | 22-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.273454E+11 | 0.713897E+10 | 493.22 | 0.216599E+11 | 0.568551E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 65807.97 | 11-OCT-07:02 | 51821.68 | 03-OCT-07:02 | 19753.69 | 12-OCT-07:03 | 14254.92 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.141744E+11 | 0.370741E+10 | 445.33 | 0.120981E+11 | 0.207631E+10 | 0.00 | 0.69 | 08-NOV-15:00 | 0.00 | 01-NOV-00:10 | 18940.22 | 09-NOV-14:30 | 16984.33 | 04-NOV-14:00 | 3746.02 | 08-NOV-18:00 | 4987.64 | 08-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.353337E+10 | 0.934268E+09 | 288.83 | 0.304545E+10 | 0.487922E+09 | 0.00 | 0.40 | 03-DEC-14:00 | 0.00 | 01-DEC-00:10 | 10098.55 | 28-DEC-15:00 | 9390.93 | 03-DEC-14:00 | 1570.34 | 16-DEC-14:00 | 2645.93 | 28-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.322234E+12 | 0.844722E+11 | 5145.70 | 0.229910E+12 | 0.923239E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.148935E+10 | 0.396531E+09 | 164.83 | 0.132330E+10 | 0.166047E+09 | 0.00 | 0.31 | 0.00 | 7587.50 | 7037.62 | 1315.86 | 2008.75 | 0.00 | |||||||
Maximum of Months | 0.500637E+11 | 0.126240E+11 | 503.34 | 0.321831E+11 | 0.213530E+11 | 0.00 | 1.00 | 0.00 | 70295.61 | 59826.29 | 35000.67 | 16116.76 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.141569E+10 | 0.369158E+09 | 290.19 | 0.122221E+10 | 0.193477E+09 | 0.00 | 0.34 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4293.60 | 12-JAN-15:00 | 3998.27 | 12-JAN-15:00 | 913.27 | 15-JAN-18:30 | 1106.76 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.398013E+10 | 0.102409E+10 | 374.00 | 0.342785E+10 | 0.552272E+09 | 0.00 | 0.55 | 22-FEB-15:00 | 0.00 | 01-FEB-00:10 | 7275.22 | 22-FEB-15:00 | 6608.65 | 22-FEB-15:00 | 1827.18 | 25-FEB-18:05 | 1881.47 | 22-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.890115E+10 | 0.232671E+10 | 480.58 | 0.769208E+10 | 0.120908E+10 | 0.00 | 0.93 | 11-MAR-08:63 | 0.00 | 01-MAR-00:10 | 14585.90 | 11-MAR-08:63 | 11889.44 | 11-MAR-08:63 | 2999.22 | 10-MAR-18:00 | 3247.65 | 28-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.136622E+11 | 0.380646E+10 | 481.18 | 0.122612E+11 | 0.140102E+10 | 0.00 | 1.00 | 02-APR-07:03 | 0.00 | 01-APR-00:05 | 31586.65 | 17-APR-07:01 | 30419.33 | 28-APR-07:02 | 4369.19 | 19-APR-07:02 | 7356.60 | 27-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.194371E+11 | 0.546373E+10 | 502.02 | 0.157219E+11 | 0.371518E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 33717.53 | 24-MAY-07:02 | 30108.11 | 06-MAY-07:01 | 10570.21 | 24-MAY-07:02 | 7797.02 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.216526E+11 | 0.588205E+10 | 488.71 | 0.156237E+11 | 0.602889E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 33904.26 | 18-JUN-07:01 | 29138.40 | 07-JUN-07:01 | 11264.34 | 18-JUN-07:01 | 7975.80 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.242584E+11 | 0.604685E+10 | 502.85 | 0.147317E+11 | 0.952670E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 34274.71 | 25-JUL-07:01 | 27368.36 | 07-JUL-07:01 | 13157.62 | 25-JUL-07:03 | 7841.63 | 02-JUL-07:01 | 0.00 | 01-JUL-00:03 |
August | 0.238943E+11 | 0.573897E+10 | 503.38 | 0.136416E+11 | 0.102528E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 34142.62 | 10-AUG-07:01 | 25747.80 | 14-AUG-07:01 | 12118.77 | 27-AUG-13:00 | 7522.88 | 08-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.198062E+11 | 0.482081E+10 | 486.17 | 0.121811E+11 | 0.762514E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 34026.27 | 03-SEP-07:01 | 27175.79 | 29-SEP-07:02 | 11692.37 | 03-SEP-07:03 | 7267.58 | 22-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.136080E+11 | 0.350036E+10 | 494.79 | 0.109079E+11 | 0.270007E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 32541.68 | 11-OCT-07:02 | 28267.58 | 02-OCT-07:02 | 6549.77 | 12-OCT-07:03 | 7009.33 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.777154E+10 | 0.199044E+10 | 460.50 | 0.668133E+10 | 0.109021E+10 | 0.00 | 0.71 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 9824.73 | 04-NOV-13:00 | 9027.46 | 04-NOV-13:00 | 1874.30 | 08-NOV-18:00 | 2561.78 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.278150E+10 | 0.719496E+09 | 389.86 | 0.236193E+10 | 0.419570E+09 | 0.00 | 0.44 | 03-DEC-14:00 | 0.00 | 01-DEC-01:10 | 5605.11 | 03-DEC-14:00 | 5254.56 | 03-DEC-14:00 | 1082.22 | 10-DEC-18:20 | 1430.04 | 03-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.161169E+12 | 0.416891E+11 | 5454.26 | 0.116454E+12 | 0.447144E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.141569E+10 | 0.369158E+09 | 290.19 | 0.122221E+10 | 0.193477E+09 | 0.00 | 0.34 | 0.00 | 4293.60 | 3998.27 | 913.27 | 1106.76 | 0.00 | |||||||
Maximum of Months | 0.242584E+11 | 0.604685E+10 | 503.38 | 0.157219E+11 | 0.102528E+11 | 0.00 | 1.00 | 0.00 | 34274.71 | 30419.33 | 13157.62 | 7975.80 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.739448E+09 | 0.192962E+09 | 147.33 | 0.669140E+09 | 70307825.04 | 0.00 | 0.32 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 3950.31 | 12-JAN-15:00 | 3692.06 | 12-JAN-15:00 | 740.89 | 14-JAN-14:00 | 1025.77 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.275217E+10 | 0.711721E+09 | 237.83 | 0.242529E+10 | 0.326880E+09 | 0.00 | 0.53 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 | 7038.65 | 22-FEB-14:00 | 6416.01 | 22-FEB-14:00 | 1507.94 | 25-FEB-16:00 | 1826.80 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.693435E+10 | 0.182235E+10 | 348.03 | 0.604202E+10 | 0.892337E+09 | 0.00 | 1.00 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 | 23441.08 | 11-MAR-07:03 | 17043.36 | 30-MAR-06:03 | 6861.49 | 11-MAR-07:03 | 4867.65 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 |
April | 0.109814E+11 | 0.305105E+10 | 353.42 | 0.987893E+10 | 0.110249E+10 | 0.00 | 1.00 | 02-APR-07:03 | 0.00 | 01-APR-00:05 | 33482.16 | 17-APR-06:01 | 30743.27 | 28-APR-06:02 | 8371.90 | 17-APR-06:01 | 7487.31 | 27-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.160311E+11 | 0.447812E+10 | 374.48 | 0.129129E+11 | 0.311824E+10 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 35022.12 | 23-MAY-06:02 | 30986.01 | 06-MAY-06:01 | 15287.17 | 23-MAY-06:02 | 7695.53 | 04-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.179193E+11 | 0.481076E+10 | 365.95 | 0.127820E+11 | 0.513724E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 36620.49 | 26-JUN-06:01 | 28580.95 | 07-JUN-06:01 | 21508.66 | 26-JUN-06:04 | 7965.90 | 12-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.197498E+11 | 0.484552E+10 | 369.28 | 0.117083E+11 | 0.804150E+10 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 36652.50 | 23-JUL-07:01 | 24261.36 | 07-JUL-06:01 | 22208.38 | 24-JUL-06:04 | 7909.51 | 02-JUL-07:13 | 0.00 | 01-JUL-00:03 |
August | 0.199055E+11 | 0.471881E+10 | 378.02 | 0.110870E+11 | 0.881842E+10 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 36732.27 | 21-AUG-06:03 | 21810.28 | 03-AUG-06:01 | 23249.85 | 28-AUG-06:05 | 7571.53 | 08-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.161652E+11 | 0.388652E+10 | 357.83 | 0.973361E+10 | 0.643161E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:05 | 36739.86 | 04-SEP-07:01 | 24530.01 | 27-SEP-06:02 | 22812.26 | 11-SEP-06:04 | 7330.29 | 22-SEP-06:01 | 0.00 | 01-SEP-00:05 |
October | 0.109053E+11 | 0.280720E+10 | 362.15 | 0.872645E+10 | 0.217881E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 34290.31 | 01-OCT-07:02 | 27053.85 | 02-OCT-06:02 | 12437.82 | 12-OCT-06:03 | 7093.38 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.598942E+10 | 0.154358E+10 | 321.17 | 0.523313E+10 | 0.756289E+09 | 0.00 | 0.71 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 9905.75 | 04-NOV-13:00 | 9081.14 | 04-NOV-13:00 | 1936.00 | 09-NOV-07:05 | 2581.50 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.172702E+10 | 0.447701E+09 | 238.67 | 0.152130E+10 | 0.205717E+09 | 0.00 | 0.41 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5170.89 | 02-DEC-14:00 | 5143.09 | 02-DEC-14:00 | 851.95 | 16-DEC-14:00 | 1324.71 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.129800E+12 | 0.333163E+11 | 3854.17 | 0.927201E+11 | 0.370798E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.739448E+09 | 0.192962E+09 | 147.33 | 0.669140E+09 | 70307825.04 | 0.00 | 0.32 | 0.00 | 3950.31 | 3692.06 | 740.89 | 1025.77 | 0.00 | |||||||
Maximum of Months | 0.199055E+11 | 0.484552E+10 | 378.02 | 0.129129E+11 | 0.881842E+10 | 0.00 | 1.00 | 0.00 | 36739.86 | 30986.01 | 23249.85 | 7965.90 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.665951E+09 | 0.174060E+09 | 138.50 | 0.602271E+09 | 63680097.52 | 0.00 | 0.31 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 3829.47 | 12-JAN-15:00 | 3579.96 | 12-JAN-15:00 | 723.38 | 14-JAN-14:00 | 997.00 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.268048E+10 | 0.694223E+09 | 236.33 | 0.236317E+10 | 0.317310E+09 | 0.00 | 0.53 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 | 6983.96 | 22-FEB-14:00 | 6368.44 | 22-FEB-14:00 | 1498.73 | 25-FEB-16:00 | 1815.08 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.692697E+10 | 0.182120E+10 | 346.53 | 0.603817E+10 | 0.888799E+09 | 0.00 | 1.00 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 | 23645.36 | 11-MAR-07:03 | 17362.66 | 30-MAR-06:03 | 6910.27 | 11-MAR-07:03 | 4909.66 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 |
April | 0.110419E+11 | 0.306678E+10 | 353.43 | 0.993846E+10 | 0.110349E+10 | 0.00 | 1.00 | 02-APR-07:03 | 0.00 | 01-APR-00:05 | 33601.76 | 17-APR-06:01 | 30853.37 | 28-APR-06:02 | 8257.80 | 17-APR-06:01 | 7508.19 | 27-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.161568E+11 | 0.451054E+10 | 374.51 | 0.130298E+11 | 0.312707E+10 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 35115.05 | 23-MAY-06:02 | 31102.60 | 06-MAY-06:01 | 15205.62 | 23-MAY-06:02 | 7717.51 | 04-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.180448E+11 | 0.484259E+10 | 365.78 | 0.128934E+11 | 0.515141E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 36717.55 | 26-JUN-06:01 | 28763.29 | 07-JUN-06:01 | 21467.45 | 26-JUN-06:04 | 7990.93 | 12-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.198963E+11 | 0.488064E+10 | 369.29 | 0.118288E+11 | 0.806754E+10 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 36749.65 | 23-JUL-07:01 | 24484.13 | 07-JUL-06:01 | 22158.87 | 24-JUL-06:04 | 7930.57 | 02-JUL-07:13 | 0.00 | 01-JUL-00:03 |
August | 0.200187E+11 | 0.474551E+10 | 378.14 | 0.111780E+11 | 0.884067E+10 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 36829.63 | 21-AUG-06:02 | 21951.31 | 03-AUG-06:01 | 23188.59 | 28-AUG-06:06 | 7591.61 | 08-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.162567E+11 | 0.390767E+10 | 357.72 | 0.980850E+10 | 0.644817E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:05 | 36837.24 | 04-SEP-07:01 | 24674.43 | 27-SEP-06:02 | 22823.15 | 11-SEP-06:04 | 7350.13 | 22-SEP-06:01 | 0.00 | 01-SEP-00:05 |
October | 0.109648E+11 | 0.282173E+10 | 362.36 | 0.878206E+10 | 0.218273E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 34396.40 | 01-OCT-07:02 | 27267.25 | 02-OCT-06:02 | 12608.98 | 12-OCT-06:03 | 7113.07 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.596538E+10 | 0.153840E+10 | 320.83 | 0.521403E+10 | 0.751357E+09 | 0.00 | 0.71 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 9902.86 | 04-NOV-13:00 | 9083.27 | 04-NOV-13:00 | 1916.86 | 09-NOV-07:05 | 2582.08 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.163783E+10 | 0.425297E+09 | 234.17 | 0.144382E+10 | 0.194011E+09 | 0.00 | 0.41 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5127.16 | 02-DEC-14:00 | 5102.52 | 02-DEC-14:00 | 836.00 | 16-DEC-14:00 | 1311.79 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.130257E+12 | 0.334286E+11 | 3837.60 | 0.931204E+11 | 0.371362E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.665951E+09 | 0.174060E+09 | 138.50 | 0.602271E+09 | 63680097.52 | 0.00 | 0.31 | 0.00 | 3829.47 | 3579.96 | 723.38 | 997.00 | 0.00 | |||||||
Maximum of Months | 0.200187E+11 | 0.488064E+10 | 378.14 | 0.130298E+11 | 0.884067E+10 | 0.00 | 1.00 | 0.00 | 36837.24 | 31102.60 | 23188.59 | 7990.93 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.536710E+09 | 0.140709E+09 | 119.17 | 0.483896E+09 | 52814118.26 | 0.00 | 0.29 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 3582.62 | 12-JAN-15:00 | 3343.48 | 12-JAN-15:00 | 681.68 | 14-JAN-14:00 | 937.09 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.249134E+10 | 0.647383E+09 | 228.17 | 0.219558E+10 | 0.295753E+09 | 0.00 | 0.52 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 | 6815.03 | 22-FEB-14:00 | 6205.19 | 22-FEB-14:00 | 1446.48 | 25-FEB-16:00 | 1775.88 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.672186E+10 | 0.177159E+10 | 340.86 | 0.585171E+10 | 0.870149E+09 | 0.00 | 1.00 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 | 21223.90 | 11-MAR-07:03 | 15698.76 | 30-MAR-06:03 | 6354.15 | 11-MAR-07:03 | 4409.77 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 |
April | 0.108904E+11 | 0.302896E+10 | 353.37 | 0.979302E+10 | 0.109736E+10 | 0.00 | 1.00 | 02-APR-07:03 | 0.00 | 01-APR-00:05 | 33460.16 | 17-APR-06:01 | 30688.06 | 28-APR-06:02 | 8284.66 | 17-APR-06:01 | 7476.74 | 27-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.160256E+11 | 0.447613E+10 | 374.08 | 0.129097E+11 | 0.311595E+10 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 34973.33 | 23-MAY-06:02 | 30928.03 | 06-MAY-06:01 | 15283.24 | 23-MAY-06:02 | 7685.26 | 04-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.179099E+11 | 0.480805E+10 | 365.82 | 0.127771E+11 | 0.513274E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 36574.50 | 26-JUN-06:03 | 28541.90 | 07-JUN-06:01 | 21472.14 | 26-JUN-06:04 | 7959.55 | 12-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.197629E+11 | 0.484834E+10 | 369.08 | 0.117238E+11 | 0.803913E+10 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 36606.47 | 23-JUL-07:01 | 24269.75 | 07-JUL-06:01 | 22155.60 | 24-JUL-06:04 | 7899.40 | 02-JUL-07:13 | 0.00 | 01-JUL-00:03 |
August | 0.198584E+11 | 0.470800E+10 | 378.06 | 0.110541E+11 | 0.880429E+10 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 36686.14 | 21-AUG-06:02 | 21717.82 | 03-AUG-06:01 | 23173.47 | 28-AUG-06:06 | 7562.02 | 08-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.160998E+11 | 0.387165E+10 | 357.52 | 0.968440E+10 | 0.641538E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:05 | 36693.73 | 04-SEP-07:01 | 24450.12 | 27-SEP-06:02 | 22851.79 | 11-SEP-06:04 | 7321.15 | 22-SEP-06:01 | 0.00 | 01-SEP-00:05 |
October | 0.108050E+11 | 0.278443E+10 | 362.10 | 0.864009E+10 | 0.216488E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 34251.43 | 01-OCT-07:02 | 27096.02 | 02-OCT-06:02 | 12094.65 | 12-OCT-06:03 | 7084.26 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.577739E+10 | 0.149336E+10 | 317.00 | 0.504297E+10 | 0.734421E+09 | 0.00 | 0.71 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 9762.01 | 04-NOV-13:00 | 8943.06 | 04-NOV-13:00 | 1817.00 | 08-NOV-18:00 | 2549.96 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.144160E+10 | 0.375492E+09 | 221.67 | 0.127060E+10 | 0.170997E+09 | 0.00 | 0.40 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 4969.29 | 02-DEC-14:00 | 4940.65 | 02-DEC-14:00 | 801.91 | 16-DEC-14:00 | 1274.89 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.128321E+12 | 0.329541E+11 | 3786.89 | 0.914270E+11 | 0.368939E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.536710E+09 | 0.140709E+09 | 119.17 | 0.483896E+09 | 52814118.26 | 0.00 | 0.29 | 0.00 | 3582.62 | 3343.48 | 681.68 | 937.09 | 0.00 | |||||||
Maximum of Months | 0.198584E+11 | 0.484834E+10 | 378.06 | 0.129097E+11 | 0.880429E+10 | 0.00 | 1.00 | 0.00 | 36693.73 | 30928.03 | 23173.47 | 7959.55 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.769908E+09 | 0.205724E+09 | 96.00 | 0.675705E+09 | 94202545.71 | 0.00 | 0.29 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 6673.57 | 12-JAN-15:10 | 6061.61 | 12-JAN-15:10 | 1319.50 | 14-JAN-15:10 | 1772.99 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.429617E+10 | 0.113760E+10 | 219.83 | 0.370801E+10 | 0.588155E+09 | 0.00 | 0.53 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 | 13088.77 | 22-FEB-14:00 | 11635.57 | 22-FEB-14:00 | 3198.71 | 25-FEB-16:00 | 3446.57 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.124585E+11 | 0.333065E+10 | 336.28 | 0.106554E+11 | 0.180308E+10 | 0.00 | 0.92 | 11-MAR-08:63 | 0.00 | 01-MAR-00:10 | 26977.35 | 11-MAR-08:63 | 21728.01 | 28-MAR-15:00 | 7873.86 | 11-MAR-08:63 | 6260.95 | 28-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 0.205409E+11 | 0.577864E+10 | 343.48 | 0.183417E+11 | 0.219929E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 61115.19 | 17-APR-07:01 | 55674.68 | 28-APR-07:02 | 16279.98 | 17-APR-07:03 | 13947.68 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.305606E+11 | 0.863560E+10 | 365.03 | 0.243658E+11 | 0.619475E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 63986.07 | 21-MAY-08:61 | 56187.65 | 29-MAY-08:61 | 26772.70 | 21-MAY-08:04 | 14665.36 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.342760E+11 | 0.931019E+10 | 358.06 | 0.241235E+11 | 0.101525E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 66912.75 | 26-JUN-07:03 | 52711.71 | 07-JUN-07:01 | 39461.40 | 26-JUN-07:04 | 15059.98 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.376277E+11 | 0.930238E+10 | 357.88 | 0.217913E+11 | 0.158364E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 66962.68 | 23-JUL-08:61 | 47278.22 | 07-JUL-07:01 | 40277.59 | 24-JUL-07:05 | 14812.44 | 02-JUL-08:12 | 0.00 | 01-JUL-00:03 |
August | 0.380507E+11 | 0.908672E+10 | 369.59 | 0.205822E+11 | 0.174685E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 67173.34 | 21-AUG-07:02 | 42772.42 | 09-AUG-07:01 | 42227.67 | 28-AUG-07:06 | 14155.00 | 07-AUG-07:12 | 0.00 | 01-AUG-00:10 |
September | 0.305445E+11 | 0.739460E+10 | 345.72 | 0.179207E+11 | 0.126237E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 67203.80 | 04-SEP-08:61 | 46226.65 | 27-SEP-07:02 | 41914.59 | 11-SEP-07:04 | 13814.66 | 24-SEP-08:02 | 0.00 | 01-SEP-00:05 |
October | 0.203331E+11 | 0.528826E+10 | 350.91 | 0.159827E+11 | 0.435041E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 62541.07 | 01-OCT-08:62 | 49193.68 | 03-OCT-07:02 | 21325.26 | 01-OCT-08:62 | 13260.24 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.105419E+11 | 0.276687E+10 | 316.58 | 0.901239E+10 | 0.152954E+10 | 0.00 | 0.73 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 18718.74 | 04-NOV-14:40 | 17131.12 | 04-NOV-14:10 | 3693.21 | 08-NOV-18:00 | 4946.84 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.217024E+10 | 0.575682E+09 | 185.75 | 0.187295E+10 | 0.297294E+09 | 0.00 | 0.39 | 02-DEC-14:10 | 0.00 | 01-DEC-00:10 | 8894.15 | 28-DEC-14:00 | 8668.92 | 02-DEC-14:10 | 1547.65 | 16-DEC-14:40 | 2346.66 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.242170E+12 | 0.628129E+11 | 3645.11 | 0.169032E+12 | 0.731379E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.769908E+09 | 0.205724E+09 | 96.00 | 0.675705E+09 | 94202545.71 | 0.00 | 0.29 | 0.00 | 6673.57 | 6061.61 | 1319.50 | 1772.99 | 0.00 | |||||||
Maximum of Months | 0.380507E+11 | 0.931019E+10 | 369.59 | 0.243658E+11 | 0.174685E+11 | 0.00 | 1.00 | 0.00 | 67203.80 | 56187.65 | 42227.67 | 15059.98 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.350389E+09 | 92154811.96 | 86.33 | 0.308303E+09 | 42086105.12 | 0.00 | 0.28 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3390.77 | 12-JAN-15:10 | 3100.37 | 12-JAN-15:10 | 644.04 | 14-JAN-15:10 | 887.10 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.217190E+10 | 0.566106E+09 | 217.83 | 0.188670E+10 | 0.285199E+09 | 0.00 | 0.53 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 | 6775.35 | 22-FEB-14:00 | 6067.05 | 22-FEB-15:10 | 1602.04 | 25-FEB-16:00 | 1756.08 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.644777E+10 | 0.169606E+10 | 336.28 | 0.553990E+10 | 0.907865E+09 | 0.00 | 0.86 | 28-MAR-15:00 | 0.00 | 01-MAR-00:10 | 13020.60 | 11-MAR-08:63 | 11441.40 | 28-MAR-15:00 | 3763.81 | 11-MAR-08:63 | 3229.07 | 28-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 0.107002E+11 | 0.296142E+10 | 343.63 | 0.957978E+10 | 0.112040E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 32107.23 | 17-APR-07:01 | 29205.50 | 28-APR-07:02 | 8219.55 | 17-APR-07:01 | 7191.36 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.159590E+11 | 0.443914E+10 | 365.78 | 0.127536E+11 | 0.320545E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 33598.43 | 21-MAY-08:61 | 29520.25 | 29-MAY-08:61 | 13761.00 | 21-MAY-08:02 | 7558.49 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.178828E+11 | 0.478277E+10 | 358.14 | 0.126119E+11 | 0.527092E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 35112.61 | 26-JUN-07:03 | 27735.35 | 07-JUN-07:01 | 20852.38 | 26-JUN-07:04 | 7765.39 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.196384E+11 | 0.477825E+10 | 358.14 | 0.113938E+11 | 0.824458E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 35138.81 | 23-JUL-08:61 | 24888.89 | 07-JUL-07:01 | 21405.92 | 24-JUL-07:05 | 7636.26 | 02-JUL-08:12 | 0.00 | 01-JUL-00:03 |
August | 0.198415E+11 | 0.466301E+10 | 370.04 | 0.107471E+11 | 0.909439E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 35249.36 | 21-AUG-07:02 | 22540.25 | 08-AUG-07:01 | 22398.62 | 28-AUG-07:06 | 7297.56 | 07-AUG-07:12 | 0.00 | 01-AUG-00:10 |
September | 0.159265E+11 | 0.379313E+10 | 347.15 | 0.935978E+10 | 0.656670E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 35265.34 | 04-SEP-08:61 | 24379.18 | 27-SEP-07:02 | 22195.69 | 11-SEP-07:04 | 7122.21 | 24-SEP-08:02 | 0.00 | 01-SEP-00:05 |
October | 0.105757E+11 | 0.270627E+10 | 351.79 | 0.834321E+10 | 0.223251E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 32845.22 | 01-OCT-08:62 | 25940.42 | 03-OCT-07:02 | 11212.13 | 01-OCT-08:62 | 6836.19 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.545184E+10 | 0.140778E+10 | 316.17 | 0.468446E+10 | 0.767381E+09 | 0.00 | 0.73 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 9773.16 | 06-NOV-14:00 | 8970.23 | 04-NOV-14:20 | 1899.61 | 08-NOV-18:00 | 2537.56 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.106234E+10 | 0.277322E+09 | 179.17 | 0.923472E+09 | 0.138869E+09 | 0.00 | 0.38 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 | 4564.14 | 02-DEC-14:20 | 4490.45 | 02-DEC-14:20 | 766.38 | 16-DEC-14:40 | 1180.68 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.126008E+12 | 0.321634E+11 | 3630.45 | 0.881321E+11 | 0.378763E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.350389E+09 | 92154811.96 | 86.33 | 0.308303E+09 | 42086105.12 | 0.00 | 0.28 | 0.00 | 3390.77 | 3100.37 | 644.04 | 887.10 | 0.00 | |||||||
Maximum of Months | 0.198415E+11 | 0.478277E+10 | 370.04 | 0.127536E+11 | 0.909439E+10 | 0.00 | 1.00 | 0.00 | 35265.34 | 29520.25 | 22398.62 | 7765.39 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.326230E+09 | 85881698.03 | 81.83 | 0.286549E+09 | 39680928.08 | 0.00 | 0.28 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3318.38 | 12-JAN-15:10 | 3032.73 | 12-JAN-15:10 | 628.93 | 14-JAN-15:10 | 869.33 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.211631E+10 | 0.552198E+09 | 215.58 | 0.183835E+10 | 0.277955E+09 | 0.00 | 0.53 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 | 6712.39 | 22-FEB-14:00 | 6008.59 | 22-FEB-15:10 | 1580.24 | 25-FEB-16:00 | 1741.30 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.638334E+10 | 0.168019E+10 | 334.78 | 0.548247E+10 | 0.900867E+09 | 0.00 | 0.86 | 28-MAR-15:00 | 0.00 | 01-MAR-00:10 | 12593.72 | 11-MAR-08:63 | 11399.06 | 28-MAR-15:00 | 3658.71 | 11-MAR-08:63 | 3217.95 | 28-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 0.106556E+11 | 0.294957E+10 | 343.63 | 0.953792E+10 | 0.111763E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 32026.62 | 17-APR-07:01 | 29125.84 | 28-APR-07:02 | 8212.86 | 17-APR-07:01 | 7173.21 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.159199E+11 | 0.442807E+10 | 365.78 | 0.127190E+11 | 0.320089E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 33513.75 | 21-MAY-08:61 | 29446.92 | 29-MAY-08:61 | 13741.24 | 21-MAY-08:02 | 7539.56 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.178423E+11 | 0.477152E+10 | 358.17 | 0.125779E+11 | 0.526441E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 35024.96 | 26-JUN-07:01 | 27649.35 | 07-JUN-07:01 | 20811.13 | 26-JUN-07:04 | 7746.20 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.196020E+11 | 0.476860E+10 | 358.10 | 0.113656E+11 | 0.823645E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 35051.10 | 23-JUL-08:03 | 24804.67 | 07-JUL-07:01 | 21363.98 | 24-JUL-07:05 | 7617.09 | 02-JUL-08:12 | 0.00 | 01-JUL-00:03 |
August | 0.198019E+11 | 0.465288E+10 | 370.02 | 0.107170E+11 | 0.908494E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 35161.37 | 21-AUG-07:02 | 22469.57 | 08-AUG-07:01 | 22343.48 | 28-AUG-07:06 | 7279.34 | 07-AUG-07:12 | 0.00 | 01-AUG-00:10 |
September | 0.158873E+11 | 0.378331E+10 | 347.20 | 0.932965E+10 | 0.655768E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 35177.31 | 04-SEP-08:61 | 24289.28 | 27-SEP-07:02 | 22156.31 | 11-SEP-07:04 | 7104.43 | 24-SEP-08:02 | 0.00 | 01-SEP-00:05 |
October | 0.105322E+11 | 0.269549E+10 | 351.51 | 0.830549E+10 | 0.222671E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 32763.19 | 01-OCT-08:62 | 25849.10 | 03-OCT-07:02 | 11199.67 | 01-OCT-08:62 | 6819.12 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.539614E+10 | 0.139419E+10 | 315.00 | 0.463491E+10 | 0.761234E+09 | 0.00 | 0.73 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 9726.21 | 06-NOV-14:00 | 8926.71 | 04-NOV-14:20 | 1890.43 | 08-NOV-18:00 | 2526.73 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.101362E+10 | 0.264821E+09 | 172.33 | 0.881698E+09 | 0.131925E+09 | 0.00 | 0.38 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 | 4511.91 | 02-DEC-14:20 | 4438.14 | 02-DEC-14:20 | 750.61 | 16-DEC-14:40 | 1164.74 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.125477E+12 | 0.320267E+11 | 3613.93 | 0.876764E+11 | 0.378004E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.326230E+09 | 85881698.03 | 81.83 | 0.286549E+09 | 39680928.08 | 0.00 | 0.28 | 0.00 | 3318.38 | 3032.73 | 628.93 | 869.33 | 0.00 | |||||||
Maximum of Months | 0.198019E+11 | 0.477152E+10 | 370.02 | 0.127190E+11 | 0.908494E+10 | 0.00 | 1.00 | 0.00 | 35177.31 | 29446.92 | 22343.48 | 7746.20 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.277783E+09 | 73301251.60 | 73.33 | 0.243301E+09 | 34482482.26 | 0.00 | 0.27 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3162.78 | 12-JAN-15:10 | 2889.36 | 12-JAN-15:10 | 595.61 | 14-JAN-15:10 | 831.51 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.198815E+10 | 0.520319E+09 | 209.58 | 0.172850E+10 | 0.259655E+09 | 0.00 | 0.52 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 | 6591.25 | 22-FEB-14:00 | 5902.65 | 22-FEB-15:10 | 1528.29 | 25-FEB-16:00 | 1714.85 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.625299E+10 | 0.164951E+10 | 330.61 | 0.536952E+10 | 0.883478E+09 | 0.00 | 0.86 | 28-MAR-15:00 | 0.00 | 01-MAR-00:10 | 11572.44 | 29-MAR-13:00 | 11388.29 | 28-MAR-15:00 | 3251.02 | 11-MAR-08:63 | 3218.65 | 28-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 0.106652E+11 | 0.295382E+10 | 344.08 | 0.954837E+10 | 0.111682E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 32161.56 | 17-APR-07:01 | 29243.17 | 28-APR-07:02 | 8239.49 | 17-APR-07:01 | 7203.97 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.160260E+11 | 0.445828E+10 | 365.66 | 0.128168E+11 | 0.320917E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 33656.38 | 21-MAY-08:61 | 29589.28 | 29-MAY-08:61 | 13789.59 | 21-MAY-08:02 | 7572.93 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.179700E+11 | 0.480681E+10 | 358.05 | 0.126902E+11 | 0.527975E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 35177.18 | 26-JUN-07:01 | 27857.43 | 07-JUN-07:01 | 20925.47 | 26-JUN-07:04 | 7781.23 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.197611E+11 | 0.480864E+10 | 358.14 | 0.114935E+11 | 0.826767E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 35203.43 | 23-JUL-08:61 | 25037.16 | 07-JUL-07:01 | 21454.35 | 24-JUL-07:05 | 7650.22 | 02-JUL-08:12 | 0.00 | 01-JUL-00:03 |
August | 0.199557E+11 | 0.469009E+10 | 369.61 | 0.108357E+11 | 0.912007E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 35314.18 | 21-AUG-07:03 | 22707.55 | 08-AUG-07:01 | 22379.08 | 28-AUG-07:06 | 7310.98 | 07-AUG-07:12 | 0.00 | 01-AUG-00:10 |
September | 0.159926E+11 | 0.380921E+10 | 347.23 | 0.941334E+10 | 0.657929E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 35330.19 | 04-SEP-08:61 | 24443.93 | 27-SEP-07:02 | 22284.75 | 11-SEP-07:04 | 7135.31 | 24-SEP-08:02 | 0.00 | 01-SEP-00:05 |
October | 0.105564E+11 | 0.270236E+10 | 351.29 | 0.832881E+10 | 0.222762E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 32905.96 | 01-OCT-08:62 | 25989.91 | 03-OCT-07:02 | 11213.19 | 01-OCT-08:62 | 6848.78 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.529459E+10 | 0.137027E+10 | 311.67 | 0.454728E+10 | 0.747313E+09 | 0.00 | 0.72 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 9691.21 | 09-NOV-13:50 | 8892.91 | 04-NOV-14:20 | 1878.23 | 08-NOV-18:00 | 2520.96 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.906479E+09 | 0.237371E+09 | 155.67 | 0.790381E+09 | 0.116099E+09 | 0.00 | 0.36 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 | 4376.90 | 02-DEC-14:20 | 4305.14 | 02-DEC-14:20 | 716.39 | 16-DEC-14:40 | 1133.53 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.125647E+12 | 0.320800E+11 | 3574.91 | 0.878057E+11 | 0.378414E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.277783E+09 | 73301251.60 | 73.33 | 0.243301E+09 | 34482482.26 | 0.00 | 0.27 | 0.00 | 3162.78 | 2889.36 | 595.61 | 831.51 | 0.00 | |||||||
Maximum of Months | 0.199557E+11 | 0.480864E+10 | 369.61 | 0.128168E+11 | 0.912007E+10 | 0.00 | 1.00 | 0.00 | 35330.19 | 29589.28 | 22379.08 | 7781.23 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.323349E+09 | 85391568.17 | 76.67 | 0.288563E+09 | 34785092.21 | 0.00 | 0.25 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3408.26 | 12-JAN-15:10 | 3162.52 | 12-JAN-15:10 | 598.47 | 14-JAN-15:10 | 898.90 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.218153E+10 | 0.572109E+09 | 209.25 | 0.192738E+10 | 0.254150E+09 | 0.00 | 0.51 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 | 7343.26 | 22-FEB-14:00 | 6652.79 | 22-FEB-14:00 | 1515.93 | 25-FEB-16:00 | 1914.72 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.690438E+10 | 0.182721E+10 | 324.83 | 0.601183E+10 | 0.892551E+09 | 0.00 | 0.84 | 28-MAR-15:00 | 0.00 | 01-MAR-00:10 | 13112.53 | 29-MAR-13:00 | 12599.82 | 28-MAR-15:00 | 3143.95 | 10-MAR-18:00 | 3563.32 | 28-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 0.122403E+11 | 0.338920E+10 | 344.60 | 0.110765E+11 | 0.116375E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 36497.04 | 17-APR-07:01 | 33212.00 | 28-APR-07:02 | 9359.72 | 17-APR-07:01 | 8158.43 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.184390E+11 | 0.514335E+10 | 366.92 | 0.150162E+11 | 0.342274E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 38555.70 | 24-MAY-07:02 | 34061.66 | 29-MAY-08:61 | 17896.01 | 24-MAY-07:02 | 8592.58 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.204804E+11 | 0.550945E+10 | 359.08 | 0.148682E+11 | 0.561223E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 39815.12 | 26-JUN-07:01 | 32566.00 | 07-JUN-07:01 | 24676.68 | 26-JUN-07:04 | 8814.69 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.224818E+11 | 0.550979E+10 | 359.71 | 0.135881E+11 | 0.889367E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 39844.83 | 23-JUL-08:61 | 29205.81 | 07-JUL-07:01 | 24401.27 | 23-JUL-08:04 | 8661.46 | 02-JUL-08:14 | 0.00 | 01-JUL-00:03 |
August | 0.226798E+11 | 0.537107E+10 | 370.95 | 0.128977E+11 | 0.978216E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 39970.19 | 21-AUG-07:03 | 26160.46 | 09-AUG-07:01 | 24887.94 | 28-AUG-07:06 | 8278.20 | 08-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.181696E+11 | 0.435746E+10 | 348.23 | 0.111460E+11 | 0.702363E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 39988.31 | 04-SEP-08:61 | 28629.63 | 27-SEP-07:02 | 25006.73 | 11-SEP-07:04 | 8075.81 | 24-SEP-08:02 | 0.00 | 01-SEP-00:05 |
October | 0.121269E+11 | 0.310280E+10 | 350.95 | 0.977053E+10 | 0.235634E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 37280.62 | 01-OCT-08:62 | 30099.48 | 03-OCT-07:02 | 12044.13 | 01-OCT-08:62 | 7754.11 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.592412E+10 | 0.153530E+10 | 308.42 | 0.516838E+10 | 0.755745E+09 | 0.00 | 0.71 | 09-NOV-13:40 | 0.00 | 01-NOV-00:10 | 10862.63 | 09-NOV-13:30 | 9882.71 | 04-NOV-14:10 | 1937.69 | 08-NOV-18:00 | 2783.91 | 04-NOV-14:10 | 0.00 | 01-NOV-00:10 |
December | 0.102413E+10 | 0.268385E+09 | 156.67 | 0.908335E+09 | 0.115793E+09 | 0.00 | 0.34 | 02-DEC-14:10 | 0.00 | 01-DEC-00:10 | 4727.51 | 28-DEC-14:00 | 4626.52 | 02-DEC-14:10 | 744.66 | 16-DEC-14:30 | 1237.89 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.142975E+12 | 0.366715E+11 | 3576.30 | 0.102668E+12 | 0.403076E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.323349E+09 | 85391568.17 | 76.67 | 0.288563E+09 | 34785092.21 | 0.00 | 0.25 | 0.00 | 3408.26 | 3162.52 | 598.47 | 898.90 | 0.00 | |||||||
Maximum of Months | 0.226798E+11 | 0.550979E+10 | 370.95 | 0.150162E+11 | 0.978216E+10 | 0.00 | 1.00 | 0.00 | 39988.31 | 34061.66 | 25006.73 | 8814.69 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.05 | 55.51 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.25 | 44.25 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.94 | 26.17 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 99.19 | 8.64 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 92.05 | 1.31 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 89.82 | 1.03 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 83.81 | 0.27 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 78.14 | 0.90 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 88.39 | 3.82 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.62 | 20.95 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.39 | 40.56 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.36 | 55.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.37 | 21.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 78.14 | 0.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.39 | 55.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.05 | 55.51 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.25 | 44.25 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.94 | 26.17 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 99.19 | 8.64 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 92.05 | 1.31 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 89.82 | 1.03 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 83.81 | 0.27 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 78.14 | 0.90 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 88.39 | 3.82 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.62 | 20.95 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.39 | 40.56 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.36 | 55.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.37 | 21.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 78.14 | 0.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.39 | 55.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.05 | 55.51 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.25 | 44.25 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.94 | 26.17 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 99.19 | 8.64 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 92.05 | 1.31 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 89.82 | 1.03 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 83.81 | 0.27 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 78.14 | 0.90 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 88.39 | 3.82 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.62 | 20.95 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.39 | 40.56 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.36 | 55.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.37 | 21.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 78.14 | 0.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.39 | 55.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.05 | 55.51 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.25 | 44.25 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.94 | 26.17 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 99.19 | 8.64 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 92.05 | 1.31 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 89.82 | 1.03 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 83.81 | 0.27 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 78.14 | 0.90 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 88.39 | 3.82 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.62 | 20.95 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.39 | 40.56 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.36 | 55.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.37 | 21.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 78.14 | 0.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.39 | 55.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.37 | 49.44 | 31.93 | 122.75 | 66.14 | 0.00 | 0.00 | 0.00 |
February | 77.37 | 42.98 | 34.40 | 126.54 | 52.74 | 0.00 | 0.00 | 0.00 |
March | 66.16 | 29.22 | 36.94 | 125.91 | 31.28 | 0.00 | 0.00 | 0.00 |
April | 46.47 | 13.11 | 33.35 | 118.57 | 10.35 | 0.00 | 0.00 | 0.00 |
May | 33.42 | 2.47 | 30.94 | 109.54 | 1.59 | 0.00 | 0.00 | 0.00 |
June | 30.57 | 0.52 | 30.05 | 106.91 | 1.23 | 0.00 | 0.00 | 0.00 |
July | 31.88 | 0.44 | 31.45 | 99.81 | 0.33 | 0.00 | 0.00 | 0.00 |
August | 33.82 | 1.81 | 32.02 | 93.27 | 1.08 | 0.00 | 0.00 | 0.00 |
September | 45.34 | 11.77 | 33.57 | 105.72 | 4.58 | 0.00 | 0.00 | 0.00 |
October | 78.01 | 43.56 | 34.45 | 156.52 | 25.06 | 0.00 | 0.00 | 0.00 |
November | 97.44 | 64.40 | 33.03 | 170.89 | 48.43 | 0.00 | 0.00 | 0.00 |
December | 86.96 | 54.49 | 32.47 | 135.05 | 66.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.96 | 26.09 | 32.87 | 122.56 | 25.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.57 | 0.44 | 30.05 | 93.27 | 0.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.44 | 64.40 | 36.94 | 170.89 | 66.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.37 | 49.44 | 31.93 | 122.75 | 66.14 | 0.00 | 0.00 | 0.00 |
February | 77.37 | 42.98 | 34.40 | 126.54 | 52.74 | 0.00 | 0.00 | 0.00 |
March | 66.16 | 29.22 | 36.94 | 125.91 | 31.28 | 0.00 | 0.00 | 0.00 |
April | 46.47 | 13.11 | 33.35 | 118.57 | 10.35 | 0.00 | 0.00 | 0.00 |
May | 33.42 | 2.47 | 30.94 | 109.54 | 1.59 | 0.00 | 0.00 | 0.00 |
June | 30.57 | 0.52 | 30.05 | 106.91 | 1.23 | 0.00 | 0.00 | 0.00 |
July | 31.88 | 0.44 | 31.45 | 99.81 | 0.33 | 0.00 | 0.00 | 0.00 |
August | 33.82 | 1.81 | 32.02 | 93.27 | 1.08 | 0.00 | 0.00 | 0.00 |
September | 45.34 | 11.77 | 33.57 | 105.72 | 4.58 | 0.00 | 0.00 | 0.00 |
October | 78.01 | 43.56 | 34.45 | 156.52 | 25.06 | 0.00 | 0.00 | 0.00 |
November | 97.44 | 64.40 | 33.03 | 170.89 | 48.43 | 0.00 | 0.00 | 0.00 |
December | 86.96 | 54.49 | 32.47 | 135.05 | 66.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.96 | 26.09 | 32.87 | 122.56 | 25.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.57 | 0.44 | 30.05 | 93.27 | 0.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.44 | 64.40 | 36.94 | 170.89 | 66.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 100.77 | 58.09 | 9.83 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 104.29 | 45.89 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.68 | 26.83 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 99.84 | 8.78 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 93.44 | 1.27 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 91.53 | 1.02 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 85.46 | 0.24 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 79.56 | 0.80 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 89.33 | 3.55 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.99 | 20.86 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.11 | 41.04 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 111.37 | 57.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.74 | 22.05 | 9.83 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 79.56 | 0.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.11 | 58.09 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 100.77 | 58.09 | 9.83 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 104.29 | 45.89 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.68 | 26.83 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 99.84 | 8.78 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 93.44 | 1.27 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 91.53 | 1.02 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 85.46 | 0.24 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 79.56 | 0.80 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 89.33 | 3.55 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.99 | 20.86 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.11 | 41.04 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 111.37 | 57.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.74 | 22.05 | 9.83 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 79.56 | 0.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.11 | 58.09 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.37 | 49.44 | 31.93 | 121.24 | 69.19 | 10.17 | 0.00 | 0.00 |
February | 77.37 | 42.98 | 34.40 | 125.43 | 54.67 | 0.00 | 0.00 | 0.00 |
March | 66.16 | 29.22 | 36.94 | 125.61 | 32.06 | 0.00 | 0.00 | 0.00 |
April | 46.47 | 13.11 | 33.35 | 119.36 | 10.52 | 0.00 | 0.00 | 0.00 |
May | 33.42 | 2.47 | 30.94 | 111.17 | 1.54 | 0.00 | 0.00 | 0.00 |
June | 30.57 | 0.52 | 30.05 | 108.93 | 1.21 | 0.00 | 0.00 | 0.00 |
July | 31.88 | 0.44 | 31.45 | 101.76 | 0.30 | 0.00 | 0.00 | 0.00 |
August | 33.82 | 1.81 | 32.02 | 94.96 | 0.97 | 0.00 | 0.00 | 0.00 |
September | 45.34 | 11.77 | 33.57 | 106.86 | 4.26 | 0.00 | 0.00 | 0.00 |
October | 78.01 | 43.56 | 34.45 | 156.99 | 24.95 | 0.00 | 0.00 | 0.00 |
November | 97.44 | 64.40 | 33.03 | 170.60 | 49.00 | 0.00 | 0.00 | 0.00 |
December | 86.96 | 54.49 | 32.47 | 133.89 | 68.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.96 | 26.09 | 32.87 | 123.01 | 26.31 | 10.17 | 0.00 | 0.00 |
Minimum of Months | 30.57 | 0.44 | 30.05 | 94.96 | 0.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.44 | 64.40 | 36.94 | 170.60 | 69.19 | 10.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 101.17 | 56.79 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 104.40 | 45.92 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.46 | 28.02 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.18 | 9.95 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 90.09 | 1.76 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.05 | 1.43 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.60 | 0.38 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.92 | 1.33 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.70 | 4.90 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.51 | 22.82 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.09 | 42.06 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 111.59 | 57.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.34 | 22.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.92 | 0.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.09 | 57.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 101.17 | 56.79 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 104.40 | 45.92 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.46 | 28.02 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.18 | 9.95 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 90.09 | 1.76 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.05 | 1.43 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.60 | 0.38 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.92 | 1.33 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.70 | 4.90 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.51 | 22.82 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.09 | 42.06 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 111.59 | 57.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.34 | 22.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.92 | 0.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.09 | 57.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 121.06 | 67.28 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 124.87 | 54.39 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 124.67 | 33.27 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 116.78 | 11.84 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 106.68 | 2.13 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 104.28 | 1.70 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 96.72 | 0.47 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 91.38 | 1.59 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 104.38 | 5.83 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 155.58 | 27.11 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 169.64 | 49.90 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 133.42 | 67.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 120.72 | 26.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 91.38 | 0.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 169.64 | 67.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 101.47 | 55.95 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 104.54 | 45.53 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.47 | 27.99 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.07 | 10.12 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.72 | 1.90 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 87.62 | 1.52 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.10 | 0.42 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.62 | 1.43 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.58 | 5.14 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.47 | 23.01 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.12 | 41.97 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 111.77 | 56.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.24 | 22.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.62 | 0.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.12 | 56.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 101.47 | 55.95 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 104.54 | 45.53 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.47 | 27.99 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.07 | 10.12 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.72 | 1.90 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 87.62 | 1.52 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.10 | 0.42 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.62 | 1.43 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.58 | 5.14 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.47 | 23.01 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.12 | 41.97 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 111.77 | 56.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.24 | 22.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.62 | 0.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.12 | 56.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 121.43 | 66.28 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 125.04 | 53.94 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 124.68 | 33.24 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 116.64 | 12.04 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 106.24 | 2.30 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 103.77 | 1.80 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 96.13 | 0.52 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 91.02 | 1.71 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 104.24 | 6.12 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 155.52 | 27.33 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 169.67 | 49.79 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 133.64 | 66.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 120.60 | 26.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 91.02 | 0.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 169.67 | 66.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 101.91 | 55.00 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 104.82 | 44.93 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.60 | 27.64 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.20 | 9.92 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.90 | 1.82 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 87.84 | 1.47 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.28 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.79 | 1.34 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.67 | 4.95 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.53 | 22.78 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.24 | 41.63 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.08 | 55.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.43 | 22.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.79 | 0.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.24 | 55.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 101.91 | 55.00 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 104.82 | 44.93 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.60 | 27.64 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.20 | 9.92 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.90 | 1.82 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 87.84 | 1.47 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.28 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.79 | 1.34 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.67 | 4.95 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.53 | 22.78 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.24 | 41.63 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.08 | 55.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.43 | 22.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.79 | 0.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.24 | 55.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 121.95 | 65.15 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 125.37 | 53.23 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 124.85 | 32.82 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 116.80 | 11.80 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 106.45 | 2.21 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 104.03 | 1.75 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 96.34 | 0.48 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 91.22 | 1.61 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 104.35 | 5.90 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 155.60 | 27.05 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 169.82 | 49.40 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 134.01 | 66.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 120.83 | 26.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 91.22 | 0.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 169.82 | 66.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.92 | 53.08 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.53 | 43.58 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.93 | 26.65 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.36 | 9.36 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.95 | 1.64 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.02 | 1.38 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.20 | 0.32 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.83 | 1.13 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.63 | 4.47 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.49 | 22.08 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.53 | 40.76 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.86 | 54.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.71 | 21.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.83 | 0.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.53 | 54.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.92 | 53.08 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.53 | 43.58 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.93 | 26.65 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.36 | 9.36 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.95 | 1.64 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.02 | 1.38 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.20 | 0.32 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.83 | 1.13 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.63 | 4.47 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.49 | 22.08 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.53 | 40.76 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.86 | 54.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.71 | 21.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.83 | 0.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.53 | 54.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.92 | 53.08 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.53 | 43.58 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.93 | 26.65 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.36 | 9.36 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.95 | 1.64 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.02 | 1.38 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.20 | 0.32 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.83 | 1.13 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.63 | 4.47 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.49 | 22.08 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.53 | 40.76 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.86 | 54.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.71 | 21.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.83 | 0.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.53 | 54.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.92 | 53.08 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.53 | 43.58 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.93 | 26.65 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.36 | 9.36 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.95 | 1.64 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.02 | 1.38 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.20 | 0.32 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.83 | 1.13 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.63 | 4.47 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.49 | 22.08 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.53 | 40.76 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.86 | 54.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.71 | 21.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.83 | 0.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.53 | 54.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 123.11 | 62.89 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 126.19 | 51.64 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 125.22 | 31.65 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 117.00 | 11.13 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 106.54 | 1.98 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 104.28 | 1.63 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 96.28 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 91.28 | 1.35 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 104.29 | 5.32 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 155.54 | 26.23 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 170.14 | 48.37 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 134.91 | 64.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 121.16 | 25.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 91.28 | 0.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 170.14 | 64.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 123.11 | 62.89 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 126.19 | 51.64 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 125.22 | 31.65 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 117.00 | 11.13 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 106.54 | 1.98 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 104.28 | 1.63 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 96.28 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 91.28 | 1.35 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 104.29 | 5.32 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 155.54 | 26.23 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 170.14 | 48.37 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 134.91 | 64.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 121.16 | 25.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 91.28 | 0.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 170.14 | 64.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.85 | 52.92 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.42 | 43.46 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.94 | 26.43 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.71 | 9.14 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 90.74 | 1.52 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.90 | 1.31 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 82.03 | 0.27 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 77.44 | 1.01 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.95 | 4.19 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.59 | 21.78 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.47 | 40.57 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.78 | 54.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.01 | 21.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 77.44 | 0.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.47 | 54.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.85 | 52.92 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.42 | 43.46 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.94 | 26.43 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.71 | 9.14 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 90.74 | 1.52 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.90 | 1.31 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 82.03 | 0.27 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 77.44 | 1.01 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.95 | 4.19 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.59 | 21.78 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.47 | 40.57 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.78 | 54.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.01 | 21.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 77.44 | 0.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.47 | 54.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 123.08 | 62.69 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 126.10 | 51.49 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 125.25 | 31.40 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 117.41 | 10.87 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 107.45 | 1.84 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 105.29 | 1.55 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 97.23 | 0.34 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 91.99 | 1.21 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 104.69 | 4.99 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 155.68 | 25.87 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 170.10 | 48.14 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 134.85 | 64.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 121.53 | 25.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 91.99 | 0.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 170.10 | 64.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 103.02 | 52.60 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.55 | 43.23 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 105.01 | 26.31 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.76 | 9.08 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 90.80 | 1.50 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.96 | 1.30 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 82.08 | 0.27 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 77.49 | 1.00 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.99 | 4.16 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.62 | 21.73 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.53 | 40.47 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.93 | 54.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.09 | 21.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 77.49 | 0.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.53 | 54.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 103.02 | 52.60 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.55 | 43.23 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 105.01 | 26.31 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.76 | 9.08 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 90.80 | 1.50 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.96 | 1.30 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 82.08 | 0.27 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 77.49 | 1.00 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.99 | 4.16 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.62 | 21.73 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.53 | 40.47 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.93 | 54.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.09 | 21.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 77.49 | 0.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.53 | 54.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 123.28 | 62.31 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 126.26 | 51.21 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 125.34 | 31.25 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 117.48 | 10.81 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 107.52 | 1.82 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 105.37 | 1.53 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 97.29 | 0.33 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 92.05 | 1.19 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 104.73 | 4.95 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 155.72 | 25.80 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 170.17 | 48.02 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 135.03 | 64.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 121.62 | 25.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 92.05 | 0.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 170.17 | 64.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 103.39 | 51.78 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.88 | 42.55 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 105.15 | 25.98 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.69 | 9.05 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 90.52 | 1.55 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.61 | 1.33 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.64 | 0.29 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 77.14 | 1.06 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.81 | 4.30 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.56 | 21.77 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.64 | 40.22 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 113.31 | 53.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.05 | 21.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 77.14 | 0.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.64 | 53.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 103.39 | 51.78 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.88 | 42.55 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 105.15 | 25.98 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.69 | 9.05 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 90.52 | 1.55 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.61 | 1.33 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.64 | 0.29 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 77.14 | 1.06 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.81 | 4.30 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.56 | 21.77 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.64 | 40.22 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 113.31 | 53.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.05 | 21.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 77.14 | 0.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.64 | 53.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 123.72 | 61.34 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 126.65 | 50.41 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 125.51 | 30.86 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 117.39 | 10.77 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 107.18 | 1.88 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 104.94 | 1.57 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 96.76 | 0.35 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 91.64 | 1.27 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 104.52 | 5.12 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 155.65 | 25.86 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 170.31 | 47.72 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 135.48 | 63.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 121.57 | 24.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 91.64 | 0.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 170.31 | 63.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 103.81 | 49.33 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 106.28 | 40.27 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 105.02 | 24.75 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 97.33 | 9.03 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 87.93 | 1.84 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 85.54 | 1.51 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 78.25 | 0.43 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 74.41 | 1.55 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 86.13 | 5.37 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 129.58 | 22.32 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.50 | 39.37 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 113.80 | 51.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 100.82 | 20.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 74.41 | 0.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.50 | 51.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 103.81 | 49.33 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 106.28 | 40.27 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 105.02 | 24.75 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 97.33 | 9.03 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 87.93 | 1.84 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 85.54 | 1.51 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 78.25 | 0.43 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 74.41 | 1.55 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 86.13 | 5.37 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 129.58 | 22.32 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.50 | 39.37 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 113.80 | 51.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 100.82 | 20.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 74.41 | 0.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.50 | 51.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 124.23 | 58.45 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 127.13 | 47.73 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 125.35 | 29.41 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 115.75 | 10.75 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 104.09 | 2.23 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 101.27 | 1.79 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 92.74 | 0.53 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 88.37 | 1.86 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 102.50 | 6.39 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 154.46 | 26.52 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 170.13 | 46.72 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 136.07 | 60.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 120.09 | 24.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 88.37 | 0.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 170.13 | 60.73 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.273333E+09 | 0.148683E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.254613E+09 | 0.107060E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281073E+09 | 70100208.65 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.257098E+09 | 22403744.96 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.246542E+09 | 3500283.94 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.232824E+09 | 2669356.11 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.224468E+09 | 718603.90 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.209297E+09 | 2398102.66 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.229118E+09 | 9899698.56 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349850E+09 | 56120518.48 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369071E+09 | 0.105135E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.300947E+09 | 0.149292E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.322823E+10 | 0.677981E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.209297E+09 | 718603.90 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369071E+09 | 0.149292E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.273333E+09 | 0.148683E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.254613E+09 | 0.107060E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281073E+09 | 70100208.65 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.257098E+09 | 22403744.96 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.246542E+09 | 3500283.94 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.232824E+09 | 2669356.11 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.224468E+09 | 718603.90 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.209297E+09 | 2398102.66 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.229118E+09 | 9899698.56 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349850E+09 | 56120518.48 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369071E+09 | 0.105135E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.300947E+09 | 0.149292E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.322823E+10 | 0.677981E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.209297E+09 | 718603.90 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369071E+09 | 0.149292E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.273333E+09 | 0.148683E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.254613E+09 | 0.107060E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281073E+09 | 70100208.65 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.257098E+09 | 22403744.96 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.246542E+09 | 3500283.94 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.232824E+09 | 2669356.11 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.224468E+09 | 718603.90 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.209297E+09 | 2398102.66 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.229118E+09 | 9899698.56 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349850E+09 | 56120518.48 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369071E+09 | 0.105135E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.300947E+09 | 0.149292E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.322823E+10 | 0.677981E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.209297E+09 | 718603.90 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369071E+09 | 0.149292E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.273333E+09 | 0.148683E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.254613E+09 | 0.107060E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281073E+09 | 70100208.65 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.257098E+09 | 22403744.96 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.246542E+09 | 3500283.94 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.232824E+09 | 2669356.11 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.224468E+09 | 718603.90 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.209297E+09 | 2398102.66 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.229118E+09 | 9899698.56 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349850E+09 | 56120518.48 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369071E+09 | 0.105135E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.300947E+09 | 0.149292E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.322823E+10 | 0.677981E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.209297E+09 | 718603.90 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369071E+09 | 0.149292E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217946E+09 | 0.132430E+09 | 85516520.10 | 0.328763E+09 | 0.177139E+09 |
February | 0.187180E+09 | 0.103965E+09 | 83215016.38 | 0.306120E+09 | 0.127580E+09 |
March | 0.177191E+09 | 78263865.55 | 98927289.16 | 0.337231E+09 | 83789231.40 |
April | 0.120445E+09 | 33993239.84 | 86451574.42 | 0.307340E+09 | 26827729.55 |
May | 89502914.32 | 6625648.30 | 82877266.02 | 0.293385E+09 | 4262410.45 |
June | 79231083.54 | 1352056.67 | 77879026.87 | 0.277116E+09 | 3188247.66 |
July | 85400424.35 | 1174612.92 | 84225811.42 | 0.267322E+09 | 881592.48 |
August | 90591769.04 | 4838283.52 | 85753485.52 | 0.249802E+09 | 2895744.79 |
September | 0.117528E+09 | 30504638.05 | 87023336.16 | 0.274022E+09 | 11866741.85 |
October | 0.208935E+09 | 0.116668E+09 | 92266344.01 | 0.419229E+09 | 67111448.08 |
November | 0.252552E+09 | 0.166931E+09 | 85620431.03 | 0.442955E+09 | 0.125525E+09 |
December | 0.232909E+09 | 0.145947E+09 | 86961903.03 | 0.361708E+09 | 0.177967E+09 |
Annual Sum or Average | 0.185941E+10 | 0.822694E+09 | 0.103672E+10 | 0.386499E+10 | 0.809034E+09 |
Minimum of Months | 79231083.54 | 1174612.92 | 77879026.87 | 0.249802E+09 | 881592.48 |
Maximum of Months | 0.252552E+09 | 0.166931E+09 | 98927289.16 | 0.442955E+09 | 0.177967E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217946E+09 | 0.132430E+09 | 85516520.10 | 0.328763E+09 | 0.177139E+09 |
February | 0.187180E+09 | 0.103965E+09 | 83215016.38 | 0.306120E+09 | 0.127580E+09 |
March | 0.177191E+09 | 78263865.55 | 98927289.16 | 0.337231E+09 | 83789231.40 |
April | 0.120445E+09 | 33993239.84 | 86451574.42 | 0.307340E+09 | 26827729.55 |
May | 89502914.32 | 6625648.30 | 82877266.02 | 0.293385E+09 | 4262410.45 |
June | 79231083.54 | 1352056.67 | 77879026.87 | 0.277116E+09 | 3188247.66 |
July | 85400424.35 | 1174612.92 | 84225811.42 | 0.267322E+09 | 881592.48 |
August | 90591769.04 | 4838283.52 | 85753485.52 | 0.249802E+09 | 2895744.79 |
September | 0.117528E+09 | 30504638.05 | 87023336.16 | 0.274022E+09 | 11866741.85 |
October | 0.208935E+09 | 0.116668E+09 | 92266344.01 | 0.419229E+09 | 67111448.08 |
November | 0.252552E+09 | 0.166931E+09 | 85620431.03 | 0.442955E+09 | 0.125525E+09 |
December | 0.232909E+09 | 0.145947E+09 | 86961903.03 | 0.361708E+09 | 0.177967E+09 |
Annual Sum or Average | 0.185941E+10 | 0.822694E+09 | 0.103672E+10 | 0.386499E+10 | 0.809034E+09 |
Minimum of Months | 79231083.54 | 1174612.92 | 77879026.87 | 0.249802E+09 | 881592.48 |
Maximum of Months | 0.252552E+09 | 0.166931E+09 | 98927289.16 | 0.442955E+09 | 0.177967E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.269896E+09 | 0.155597E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.252307E+09 | 0.111016E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280371E+09 | 71864478.45 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.258788E+09 | 22762075.17 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.250262E+09 | 3390790.27 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.237233E+09 | 2635464.71 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.228892E+09 | 642822.30 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.213095E+09 | 2148474.93 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.231550E+09 | 9196670.32 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.350850E+09 | 55880455.15 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.368361E+09 | 0.106384E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.298283E+09 | 0.153908E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.323989E+10 | 0.695426E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.213095E+09 | 642822.30 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.368361E+09 | 0.155597E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.269896E+09 | 0.155597E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.252307E+09 | 0.111016E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280371E+09 | 71864478.45 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.258788E+09 | 22762075.17 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.250262E+09 | 3390790.27 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.237233E+09 | 2635464.71 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.228892E+09 | 642822.30 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.213095E+09 | 2148474.93 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.231550E+09 | 9196670.32 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.350850E+09 | 55880455.15 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.368361E+09 | 0.106384E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.298283E+09 | 0.153908E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.323989E+10 | 0.695426E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.213095E+09 | 642822.30 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.368361E+09 | 0.155597E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217946E+09 | 0.132430E+09 | 85516520.10 | 0.324740E+09 | 0.185319E+09 |
February | 0.187180E+09 | 0.103965E+09 | 83215016.38 | 0.303446E+09 | 0.132256E+09 |
March | 0.177191E+09 | 78263865.55 | 98927289.16 | 0.336446E+09 | 85880444.82 |
April | 0.120445E+09 | 33993239.84 | 86451574.42 | 0.309371E+09 | 27256074.15 |
May | 89502914.32 | 6625648.30 | 82877266.02 | 0.297759E+09 | 4132388.41 |
June | 79231083.54 | 1352056.67 | 77879026.87 | 0.282341E+09 | 3147994.09 |
July | 85400424.35 | 1174612.92 | 84225811.42 | 0.272561E+09 | 791606.77 |
August | 90591769.04 | 4838283.52 | 85753485.52 | 0.254343E+09 | 2592401.08 |
September | 0.117528E+09 | 30504638.05 | 87023336.16 | 0.276971E+09 | 11029559.28 |
October | 0.208935E+09 | 0.116668E+09 | 92266344.01 | 0.420488E+09 | 66813079.37 |
November | 0.252552E+09 | 0.166931E+09 | 85620431.03 | 0.442188E+09 | 0.126999E+09 |
December | 0.232909E+09 | 0.145947E+09 | 86961903.03 | 0.358605E+09 | 0.183432E+09 |
Annual Sum or Average | 0.185941E+10 | 0.822694E+09 | 0.103672E+10 | 0.387926E+10 | 0.829650E+09 |
Minimum of Months | 79231083.54 | 1174612.92 | 77879026.87 | 0.254343E+09 | 791606.77 |
Maximum of Months | 0.252552E+09 | 0.166931E+09 | 98927289.16 | 0.442188E+09 | 0.185319E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.270963E+09 | 0.152116E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.252559E+09 | 0.111082E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.279776E+09 | 75053236.07 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.254494E+09 | 25800515.63 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.241306E+09 | 4705910.21 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.228215E+09 | 3707123.65 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.218551E+09 | 1029301.27 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.206032E+09 | 3557281.63 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227308E+09 | 12690452.74 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349571E+09 | 61129434.87 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.368298E+09 | 0.109010E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.298873E+09 | 0.152674E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.319595E+10 | 0.712556E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.206032E+09 | 1029301.27 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.368298E+09 | 0.152674E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.270963E+09 | 0.152116E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.252559E+09 | 0.111082E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.279776E+09 | 75053236.07 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.254494E+09 | 25800515.63 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.241306E+09 | 4705910.21 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.228215E+09 | 3707123.65 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.218551E+09 | 1029301.27 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.206032E+09 | 3557281.63 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227308E+09 | 12690452.74 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349571E+09 | 61129434.87 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.368298E+09 | 0.109010E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.298873E+09 | 0.152674E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.319595E+10 | 0.712556E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.206032E+09 | 1029301.27 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.368298E+09 | 0.152674E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.324241E+09 | 0.180192E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.302092E+09 | 0.131581E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.333914E+09 | 89117174.65 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.302690E+09 | 30690651.79 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.285738E+09 | 5698187.80 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.270282E+09 | 4395041.24 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.259048E+09 | 1258037.96 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.244741E+09 | 4258811.85 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.270548E+09 | 15106535.20 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.416700E+09 | 72598047.83 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.439696E+09 | 0.129344E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.357355E+09 | 0.180944E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.380704E+10 | 0.845184E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.244741E+09 | 1258037.96 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.439696E+09 | 0.180944E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.271789E+09 | 0.149862E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.252901E+09 | 0.110151E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.279799E+09 | 74981519.54 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.254193E+09 | 26239898.41 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.240305E+09 | 5079304.23 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.227100E+09 | 3934479.95 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.217219E+09 | 1137296.73 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.205224E+09 | 3821196.53 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227015E+09 | 13335173.30 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349442E+09 | 61638135.14 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.368368E+09 | 0.108775E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.299364E+09 | 0.151376E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.319272E+10 | 0.710331E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.205224E+09 | 1137296.73 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.368368E+09 | 0.151376E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.271789E+09 | 0.149862E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.252901E+09 | 0.110151E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.279799E+09 | 74981519.54 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.254193E+09 | 26239898.41 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.240305E+09 | 5079304.23 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.227100E+09 | 3934479.95 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.217219E+09 | 1137296.73 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.205224E+09 | 3821196.53 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227015E+09 | 13335173.30 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349442E+09 | 61638135.14 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.368368E+09 | 0.108775E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.299364E+09 | 0.151376E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.319272E+10 | 0.710331E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.205224E+09 | 1137296.73 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.368368E+09 | 0.151376E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.325227E+09 | 0.177520E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.302503E+09 | 0.130480E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.333942E+09 | 89032698.22 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.302330E+09 | 31212307.34 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.284557E+09 | 6148915.51 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.268960E+09 | 4667849.80 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.257474E+09 | 1389892.30 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.243785E+09 | 4574620.90 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.270200E+09 | 15871962.44 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.416544E+09 | 73202893.39 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.439781E+09 | 0.129065E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.357941E+09 | 0.179407E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.380324E+10 | 0.842573E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.243785E+09 | 1389892.30 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.439781E+09 | 0.179407E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.272954E+09 | 0.147312E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.253572E+09 | 0.108702E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280168E+09 | 74028276.56 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.254534E+09 | 25703835.48 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.240788E+09 | 4875735.18 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.227674E+09 | 3822244.05 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.217700E+09 | 1051985.60 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.205669E+09 | 3601064.12 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227239E+09 | 12836535.66 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349617E+09 | 61005873.67 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.368697E+09 | 0.107900E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.300203E+09 | 0.149701E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.319882E+10 | 0.700540E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.205669E+09 | 1051985.60 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.368697E+09 | 0.149701E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.272954E+09 | 0.147312E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.253572E+09 | 0.108702E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280168E+09 | 74028276.56 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.254534E+09 | 25703835.48 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.240788E+09 | 4875735.18 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.227674E+09 | 3822244.05 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.217700E+09 | 1051985.60 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.205669E+09 | 3601064.12 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227239E+09 | 12836535.66 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349617E+09 | 61005873.67 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.368697E+09 | 0.107900E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.300203E+09 | 0.149701E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.319882E+10 | 0.700540E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.205669E+09 | 1051985.60 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.368697E+09 | 0.149701E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.326619E+09 | 0.174506E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.303305E+09 | 0.128772E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.334386E+09 | 87910129.96 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.302738E+09 | 30581083.23 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.285123E+09 | 5906178.73 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.269635E+09 | 4532783.97 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.258036E+09 | 1287999.13 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.244311E+09 | 4314593.03 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.270467E+09 | 15285644.19 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.416755E+09 | 72458227.34 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.440176E+09 | 0.128034E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.358944E+09 | 0.177428E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.381049E+10 | 0.831016E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.244311E+09 | 1287999.13 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.440176E+09 | 0.177428E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.275648E+09 | 0.142166E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.255299E+09 | 0.105432E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281045E+09 | 71368709.20 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.254954E+09 | 24252575.51 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.240914E+09 | 4380362.30 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.228156E+09 | 3570373.92 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.217496E+09 | 844312.52 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.205793E+09 | 3023401.43 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227126E+09 | 11586099.51 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349508E+09 | 59150781.16 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369430E+09 | 0.105648E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.302285E+09 | 0.145998E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.320765E+10 | 0.677420E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.205793E+09 | 844312.52 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369430E+09 | 0.145998E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.275648E+09 | 0.142166E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.255299E+09 | 0.105432E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281045E+09 | 71368709.20 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.254954E+09 | 24252575.51 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.240914E+09 | 4380362.30 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.228156E+09 | 3570373.92 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.217496E+09 | 844312.52 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.205793E+09 | 3023401.43 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227126E+09 | 11586099.51 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349508E+09 | 59150781.16 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369430E+09 | 0.105648E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.302285E+09 | 0.145998E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.320765E+10 | 0.677420E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.205793E+09 | 844312.52 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369430E+09 | 0.145998E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.275648E+09 | 0.142166E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.255299E+09 | 0.105432E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281045E+09 | 71368709.20 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.254954E+09 | 24252575.51 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.240914E+09 | 4380362.30 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.228156E+09 | 3570373.92 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.217496E+09 | 844312.52 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.205793E+09 | 3023401.43 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227126E+09 | 11586099.51 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349508E+09 | 59150781.16 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369430E+09 | 0.105648E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.302285E+09 | 0.145998E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.320765E+10 | 0.677420E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.205793E+09 | 844312.52 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369430E+09 | 0.145998E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.275648E+09 | 0.142166E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.255299E+09 | 0.105432E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281045E+09 | 71368709.20 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.254954E+09 | 24252575.51 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.240914E+09 | 4380362.30 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.228156E+09 | 3570373.92 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.217496E+09 | 844312.52 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.205793E+09 | 3023401.43 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227126E+09 | 11586099.51 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349508E+09 | 59150781.16 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369430E+09 | 0.105648E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.302285E+09 | 0.145998E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.320765E+10 | 0.677420E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.205793E+09 | 844312.52 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369430E+09 | 0.145998E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.329751E+09 | 0.168442E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.305285E+09 | 0.124926E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.335392E+09 | 84766614.65 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.303256E+09 | 28842127.00 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.285363E+09 | 5295883.06 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.270293E+09 | 4225070.10 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.257872E+09 | 1031310.76 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.244490E+09 | 3616523.46 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.270330E+09 | 13778374.93 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.416600E+09 | 70250891.73 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.440991E+09 | 0.125370E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.361347E+09 | 0.173056E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.382097E+10 | 0.803602E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.244490E+09 | 1031310.76 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.440991E+09 | 0.173056E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.329751E+09 | 0.168442E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.305285E+09 | 0.124926E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.335392E+09 | 84766614.65 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.303256E+09 | 28842127.00 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.285363E+09 | 5295883.06 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.270293E+09 | 4225070.10 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.257872E+09 | 1031310.76 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.244490E+09 | 3616523.46 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.270330E+09 | 13778374.93 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.416600E+09 | 70250891.73 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.440991E+09 | 0.125370E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.361347E+09 | 0.173056E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.382097E+10 | 0.803602E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.244490E+09 | 1031310.76 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.440991E+09 | 0.173056E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.275484E+09 | 0.141743E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.255038E+09 | 0.105143E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281060E+09 | 70796802.31 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.255850E+09 | 23680815.04 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.243037E+09 | 4065925.21 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.230424E+09 | 3388148.27 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.219702E+09 | 735991.54 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.207416E+09 | 2702655.22 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227965E+09 | 10865809.80 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349770E+09 | 58345916.18 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369272E+09 | 0.105167E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.302075E+09 | 0.145719E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.321709E+10 | 0.672354E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.207416E+09 | 735991.54 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369272E+09 | 0.145719E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.275484E+09 | 0.141743E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.255038E+09 | 0.105143E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281060E+09 | 70796802.31 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.255850E+09 | 23680815.04 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.243037E+09 | 4065925.21 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.230424E+09 | 3388148.27 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.219702E+09 | 735991.54 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.207416E+09 | 2702655.22 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227965E+09 | 10865809.80 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349770E+09 | 58345916.18 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369272E+09 | 0.105167E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.302075E+09 | 0.145719E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.321709E+10 | 0.672354E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.207416E+09 | 735991.54 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369272E+09 | 0.145719E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.329654E+09 | 0.167915E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.305071E+09 | 0.124563E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.335479E+09 | 84089839.06 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.304325E+09 | 28171714.40 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.287787E+09 | 4923253.91 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.272909E+09 | 4010012.66 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.260417E+09 | 901296.38 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.246393E+09 | 3238126.27 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.271349E+09 | 12929618.92 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.416970E+09 | 69293725.54 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.440892E+09 | 0.124788E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.361188E+09 | 0.172702E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.383244E+10 | 0.797527E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.246393E+09 | 901296.38 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.440892E+09 | 0.172702E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.275928E+09 | 0.140884E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.255356E+09 | 0.104573E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281253E+09 | 70469359.43 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.255995E+09 | 23543728.75 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.243197E+09 | 4027542.41 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.230595E+09 | 3360982.78 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.219844E+09 | 725280.80 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.207543E+09 | 2667766.76 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.228060E+09 | 10781299.76 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349853E+09 | 58191868.49 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369426E+09 | 0.104890E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.302473E+09 | 0.145047E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.321952E+10 | 0.669162E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.207543E+09 | 725280.80 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369426E+09 | 0.145047E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.275928E+09 | 0.140884E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.255356E+09 | 0.104573E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281253E+09 | 70469359.43 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.255995E+09 | 23543728.75 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.243197E+09 | 4027542.41 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.230595E+09 | 3360982.78 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.219844E+09 | 725280.80 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.207543E+09 | 2667766.76 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.228060E+09 | 10781299.76 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349853E+09 | 58191868.49 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369426E+09 | 0.104890E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.302473E+09 | 0.145047E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.321952E+10 | 0.669162E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.207543E+09 | 725280.80 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369426E+09 | 0.145047E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.330186E+09 | 0.166900E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.305451E+09 | 0.123889E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.335712E+09 | 83701593.92 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.304499E+09 | 28008558.98 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.287976E+09 | 4876550.56 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.273113E+09 | 3977671.14 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.260585E+09 | 889244.21 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.246545E+09 | 3196294.97 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.271463E+09 | 12829170.90 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.417072E+09 | 69111344.85 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.441077E+09 | 0.124460E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.361664E+09 | 0.171905E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.383534E+10 | 0.793744E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.246545E+09 | 889244.21 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.441077E+09 | 0.171905E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.276918E+09 | 0.138674E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.256151E+09 | 0.102927E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281635E+09 | 69585347.57 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.255804E+09 | 23459654.58 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.242439E+09 | 4147484.61 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.229670E+09 | 3437717.48 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.218654E+09 | 768088.00 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.206620E+09 | 2830261.60 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227604E+09 | 11153537.49 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349695E+09 | 58319236.78 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369725E+09 | 0.104238E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.303479E+09 | 0.143163E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.321839E+10 | 0.662703E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.206620E+09 | 768088.00 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369725E+09 | 0.143163E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.276918E+09 | 0.138674E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.256151E+09 | 0.102927E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281635E+09 | 69585347.57 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.255804E+09 | 23459654.58 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.242439E+09 | 4147484.61 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.229670E+09 | 3437717.48 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.218654E+09 | 768088.00 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.206620E+09 | 2830261.60 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227604E+09 | 11153537.49 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349695E+09 | 58319236.78 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369725E+09 | 0.104238E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.303479E+09 | 0.143163E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.321839E+10 | 0.662703E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.206620E+09 | 768088.00 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369725E+09 | 0.143163E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.331367E+09 | 0.164291E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.306399E+09 | 0.121948E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.336170E+09 | 82663525.20 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.304267E+09 | 27913602.29 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.287071E+09 | 5025019.81 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.272004E+09 | 4070491.00 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.259164E+09 | 941028.40 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.245442E+09 | 3393603.08 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.270914E+09 | 13276971.92 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.416880E+09 | 69270380.55 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.441434E+09 | 0.123693E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.362863E+09 | 0.169680E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.383398E+10 | 0.786168E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.245442E+09 | 941028.40 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.441434E+09 | 0.169680E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.278045E+09 | 0.132121E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.257123E+09 | 97424635.14 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281286E+09 | 66293916.94 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.252282E+09 | 23405395.92 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.235506E+09 | 4918535.71 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.221709E+09 | 3916430.27 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.209593E+09 | 1146468.09 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.199288E+09 | 4150358.80 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.223246E+09 | 13921959.68 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.347078E+09 | 59791282.07 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369358E+09 | 0.102035E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.304812E+09 | 0.137218E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.317932E+10 | 0.646343E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.199288E+09 | 1146468.09 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369358E+09 | 0.137218E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.278045E+09 | 0.132121E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.257123E+09 | 97424635.14 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281286E+09 | 66293916.94 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.252282E+09 | 23405395.92 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.235506E+09 | 4918535.71 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.221709E+09 | 3916430.27 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.209593E+09 | 1146468.09 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.199288E+09 | 4150358.80 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.223246E+09 | 13921959.68 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.347078E+09 | 59791282.07 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369358E+09 | 0.102035E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.304812E+09 | 0.137218E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.317932E+10 | 0.646343E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.199288E+09 | 1146468.09 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369358E+09 | 0.137218E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.332728E+09 | 0.156542E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.307559E+09 | 0.115462E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.335733E+09 | 78781983.84 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.300026E+09 | 27853312.93 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.278800E+09 | 5966015.56 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.262487E+09 | 4641568.27 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.248392E+09 | 1409563.04 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.236691E+09 | 4974849.49 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.265676E+09 | 16572330.02 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.413716E+09 | 71024597.59 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.440974E+09 | 0.121090E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.364448E+09 | 0.162647E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.378723E+10 | 0.766965E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.236691E+09 | 1409563.04 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.440974E+09 | 0.162647E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 653.70 | 354.32 | 433.50 | 263.40 | 170.09 | 0.00 | 0.00 |
February | 674.06 | 282.49 | 412.19 | 228.94 | 183.25 | 0.00 | 0.00 |
March | 671.58 | 167.26 | 352.43 | 155.67 | 196.77 | 0.00 | 0.00 |
April | 633.90 | 55.27 | 247.55 | 69.87 | 177.68 | 0.00 | 0.00 |
May | 587.27 | 8.41 | 178.02 | 13.18 | 164.84 | 0.00 | 0.00 |
June | 573.12 | 6.58 | 162.84 | 2.78 | 160.07 | 0.00 | 0.00 |
July | 534.84 | 1.73 | 169.86 | 2.34 | 167.53 | 0.00 | 0.00 |
August | 499.10 | 5.74 | 180.19 | 9.62 | 170.56 | 0.00 | 0.00 |
September | 565.01 | 24.43 | 241.56 | 62.70 | 178.86 | 0.00 | 0.00 |
October | 835.52 | 133.92 | 415.57 | 232.05 | 183.52 | 0.00 | 0.00 |
November | 911.34 | 259.10 | 519.07 | 343.10 | 175.98 | 0.00 | 0.00 |
December | 719.54 | 355.85 | 463.26 | 290.29 | 172.97 | 0.00 | 0.00 |
Annual Sum or Average | 654.58 | 137.30 | 314.11 | 138.98 | 175.13 | 0.00 | 0.00 |
Minimum of Months | 499.10 | 1.73 | 162.84 | 2.34 | 160.07 | 0.00 | 0.00 |
Maximum of Months | 911.34 | 355.85 | 519.07 | 343.10 | 196.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 322.78 | 185.38 | 216.75 | 131.70 | 85.05 | 0.00 | 0.00 |
February | 334.02 | 146.45 | 206.10 | 114.47 | 91.62 | 0.00 | 0.00 |
March | 334.97 | 85.73 | 176.22 | 77.83 | 98.38 | 0.00 | 0.00 |
April | 319.04 | 28.08 | 123.78 | 34.93 | 88.84 | 0.00 | 0.00 |
May | 298.04 | 4.07 | 89.01 | 6.59 | 82.42 | 0.00 | 0.00 |
June | 291.98 | 3.25 | 81.42 | 1.39 | 80.03 | 0.00 | 0.00 |
July | 272.68 | 0.78 | 84.93 | 1.17 | 83.76 | 0.00 | 0.00 |
August | 254.08 | 2.57 | 90.09 | 4.81 | 85.28 | 0.00 | 0.00 |
September | 285.52 | 11.35 | 120.78 | 31.35 | 89.43 | 0.00 | 0.00 |
October | 418.98 | 66.67 | 207.79 | 116.03 | 91.76 | 0.00 | 0.00 |
November | 454.83 | 131.08 | 259.54 | 171.55 | 87.99 | 0.00 | 0.00 |
December | 356.62 | 183.41 | 231.63 | 145.15 | 86.48 | 0.00 | 0.00 |
Annual Sum or Average | 328.48 | 70.41 | 157.05 | 69.49 | 87.57 | 0.00 | 0.00 |
Minimum of Months | 254.08 | 0.78 | 81.42 | 1.17 | 80.03 | 0.00 | 0.00 |
Maximum of Months | 454.83 | 185.38 | 259.54 | 171.55 | 98.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 323.39 | 180.86 | 216.30 | 131.43 | 84.87 | 0.00 | 0.00 |
February | 333.67 | 146.22 | 205.67 | 114.24 | 91.44 | 0.00 | 0.00 |
March | 333.58 | 89.32 | 175.86 | 77.67 | 98.18 | 0.00 | 0.00 |
April | 313.15 | 31.75 | 123.52 | 34.86 | 88.66 | 0.00 | 0.00 |
May | 286.87 | 5.64 | 88.83 | 6.58 | 82.25 | 0.00 | 0.00 |
June | 280.37 | 4.56 | 81.26 | 1.39 | 79.87 | 0.00 | 0.00 |
July | 259.91 | 1.24 | 84.76 | 1.17 | 83.59 | 0.00 | 0.00 |
August | 245.22 | 4.25 | 89.91 | 4.80 | 85.11 | 0.00 | 0.00 |
September | 279.77 | 15.62 | 120.53 | 31.28 | 89.25 | 0.00 | 0.00 |
October | 416.61 | 72.75 | 207.36 | 115.79 | 91.57 | 0.00 | 0.00 |
November | 453.82 | 134.01 | 259.00 | 171.20 | 87.81 | 0.00 | 0.00 |
December | 356.59 | 181.56 | 231.15 | 144.85 | 86.31 | 0.00 | 0.00 |
Annual Sum or Average | 323.41 | 71.99 | 156.73 | 69.35 | 87.39 | 0.00 | 0.00 |
Minimum of Months | 245.22 | 1.24 | 81.26 | 1.17 | 79.87 | 0.00 | 0.00 |
Maximum of Months | 453.82 | 181.56 | 259.00 | 171.20 | 98.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 324.37 | 178.18 | 216.30 | 131.43 | 84.87 | 0.00 | 0.00 |
February | 334.12 | 145.00 | 205.67 | 114.24 | 91.44 | 0.00 | 0.00 |
March | 333.61 | 89.23 | 175.86 | 77.67 | 98.18 | 0.00 | 0.00 |
April | 312.78 | 32.29 | 123.52 | 34.86 | 88.66 | 0.00 | 0.00 |
May | 285.68 | 6.09 | 88.83 | 6.58 | 82.25 | 0.00 | 0.00 |
June | 279.00 | 4.84 | 81.26 | 1.39 | 79.87 | 0.00 | 0.00 |
July | 258.33 | 1.37 | 84.76 | 1.17 | 83.59 | 0.00 | 0.00 |
August | 244.26 | 4.56 | 89.91 | 4.80 | 85.11 | 0.00 | 0.00 |
September | 279.41 | 16.41 | 120.53 | 31.28 | 89.25 | 0.00 | 0.00 |
October | 416.45 | 73.36 | 207.36 | 115.79 | 91.57 | 0.00 | 0.00 |
November | 453.90 | 133.72 | 259.00 | 171.20 | 87.81 | 0.00 | 0.00 |
December | 357.18 | 180.02 | 231.15 | 144.85 | 86.31 | 0.00 | 0.00 |
Annual Sum or Average | 323.08 | 71.77 | 156.73 | 69.35 | 87.39 | 0.00 | 0.00 |
Minimum of Months | 244.26 | 1.37 | 81.26 | 1.17 | 79.87 | 0.00 | 0.00 |
Maximum of Months | 453.90 | 180.02 | 259.00 | 171.20 | 98.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 325.76 | 175.15 | 216.30 | 131.43 | 84.87 | 0.00 | 0.00 |
February | 335.01 | 143.09 | 205.67 | 114.24 | 91.44 | 0.00 | 0.00 |
March | 334.05 | 88.10 | 175.86 | 77.67 | 98.18 | 0.00 | 0.00 |
April | 313.20 | 31.63 | 123.52 | 34.86 | 88.66 | 0.00 | 0.00 |
May | 286.25 | 5.85 | 88.83 | 6.58 | 82.25 | 0.00 | 0.00 |
June | 279.70 | 4.70 | 81.26 | 1.39 | 79.87 | 0.00 | 0.00 |
July | 258.90 | 1.27 | 84.76 | 1.17 | 83.59 | 0.00 | 0.00 |
August | 244.79 | 4.30 | 89.91 | 4.80 | 85.11 | 0.00 | 0.00 |
September | 279.69 | 15.80 | 120.53 | 31.28 | 89.25 | 0.00 | 0.00 |
October | 416.66 | 72.61 | 207.36 | 115.79 | 91.57 | 0.00 | 0.00 |
November | 454.31 | 132.65 | 259.00 | 171.20 | 87.81 | 0.00 | 0.00 |
December | 358.18 | 178.03 | 231.15 | 144.85 | 86.31 | 0.00 | 0.00 |
Annual Sum or Average | 323.70 | 70.78 | 156.73 | 69.35 | 87.39 | 0.00 | 0.00 |
Minimum of Months | 244.79 | 1.27 | 81.26 | 1.17 | 79.87 | 0.00 | 0.00 |
Maximum of Months | 454.31 | 178.03 | 259.00 | 171.20 | 98.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 657.89 | 338.09 | 432.61 | 262.86 | 169.74 | 0.00 | 0.00 |
February | 674.51 | 277.60 | 411.35 | 228.47 | 182.87 | 0.00 | 0.00 |
March | 670.16 | 169.88 | 351.71 | 155.35 | 196.36 | 0.00 | 0.00 |
April | 627.44 | 59.68 | 247.04 | 69.72 | 177.32 | 0.00 | 0.00 |
May | 572.87 | 10.50 | 177.66 | 13.15 | 164.51 | 0.00 | 0.00 |
June | 560.65 | 8.77 | 162.51 | 2.77 | 159.74 | 0.00 | 0.00 |
July | 517.37 | 2.03 | 169.51 | 2.33 | 167.18 | 0.00 | 0.00 |
August | 489.90 | 7.22 | 179.82 | 9.60 | 170.21 | 0.00 | 0.00 |
September | 559.09 | 28.51 | 241.06 | 62.57 | 178.49 | 0.00 | 0.00 |
October | 833.05 | 140.79 | 414.72 | 231.58 | 183.14 | 0.00 | 0.00 |
November | 910.38 | 259.77 | 518.01 | 342.39 | 175.62 | 0.00 | 0.00 |
December | 721.26 | 347.26 | 462.31 | 289.70 | 172.61 | 0.00 | 0.00 |
Annual Sum or Average | 649.18 | 136.89 | 313.47 | 138.69 | 174.77 | 0.00 | 0.00 |
Minimum of Months | 489.90 | 2.03 | 162.51 | 2.33 | 159.74 | 0.00 | 0.00 |
Maximum of Months | 910.38 | 347.26 | 518.01 | 342.39 | 196.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 328.79 | 168.53 | 216.30 | 131.43 | 84.87 | 0.00 | 0.00 |
February | 336.95 | 138.41 | 205.67 | 114.24 | 91.44 | 0.00 | 0.00 |
March | 335.13 | 84.26 | 175.86 | 77.67 | 98.18 | 0.00 | 0.00 |
April | 314.82 | 29.14 | 123.52 | 34.86 | 88.66 | 0.00 | 0.00 |
May | 288.93 | 4.87 | 88.83 | 6.58 | 82.25 | 0.00 | 0.00 |
June | 283.08 | 4.16 | 81.26 | 1.39 | 79.87 | 0.00 | 0.00 |
July | 261.28 | 0.89 | 84.76 | 1.17 | 83.59 | 0.00 | 0.00 |
August | 246.87 | 3.23 | 89.91 | 4.80 | 85.11 | 0.00 | 0.00 |
September | 280.59 | 13.37 | 120.53 | 31.28 | 89.25 | 0.00 | 0.00 |
October | 416.86 | 69.44 | 207.36 | 115.79 | 91.57 | 0.00 | 0.00 |
November | 455.03 | 129.29 | 259.00 | 171.20 | 87.81 | 0.00 | 0.00 |
December | 360.42 | 173.29 | 231.15 | 144.85 | 86.31 | 0.00 | 0.00 |
Annual Sum or Average | 325.55 | 67.93 | 156.73 | 69.35 | 87.39 | 0.00 | 0.00 |
Minimum of Months | 246.87 | 0.89 | 81.26 | 1.17 | 79.87 | 0.00 | 0.00 |
Maximum of Months | 455.03 | 173.29 | 259.00 | 171.20 | 98.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 329.32 | 167.51 | 216.30 | 131.43 | 84.87 | 0.00 | 0.00 |
February | 337.37 | 137.66 | 205.67 | 114.24 | 91.44 | 0.00 | 0.00 |
March | 335.36 | 83.87 | 175.86 | 77.67 | 98.18 | 0.00 | 0.00 |
April | 315.00 | 28.97 | 123.52 | 34.86 | 88.66 | 0.00 | 0.00 |
May | 289.12 | 4.83 | 88.83 | 6.58 | 82.25 | 0.00 | 0.00 |
June | 283.30 | 4.13 | 81.26 | 1.39 | 79.87 | 0.00 | 0.00 |
July | 261.45 | 0.87 | 84.76 | 1.17 | 83.59 | 0.00 | 0.00 |
August | 247.02 | 3.19 | 89.91 | 4.80 | 85.11 | 0.00 | 0.00 |
September | 280.70 | 13.27 | 120.53 | 31.28 | 89.25 | 0.00 | 0.00 |
October | 416.96 | 69.26 | 207.36 | 115.79 | 91.57 | 0.00 | 0.00 |
November | 455.22 | 128.95 | 259.00 | 171.20 | 87.81 | 0.00 | 0.00 |
December | 360.89 | 172.49 | 231.15 | 144.85 | 86.31 | 0.00 | 0.00 |
Annual Sum or Average | 325.80 | 67.61 | 156.73 | 69.35 | 87.39 | 0.00 | 0.00 |
Minimum of Months | 247.02 | 0.87 | 81.26 | 1.17 | 79.87 | 0.00 | 0.00 |
Maximum of Months | 455.22 | 172.49 | 259.00 | 171.20 | 98.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 330.50 | 164.89 | 216.30 | 131.43 | 84.87 | 0.00 | 0.00 |
February | 338.42 | 135.50 | 205.67 | 114.24 | 91.44 | 0.00 | 0.00 |
March | 335.81 | 82.82 | 175.86 | 77.67 | 98.18 | 0.00 | 0.00 |
April | 314.77 | 28.87 | 123.52 | 34.86 | 88.66 | 0.00 | 0.00 |
May | 288.21 | 4.97 | 88.83 | 6.58 | 82.25 | 0.00 | 0.00 |
June | 282.15 | 4.22 | 81.26 | 1.39 | 79.87 | 0.00 | 0.00 |
July | 260.03 | 0.92 | 84.76 | 1.17 | 83.59 | 0.00 | 0.00 |
August | 245.92 | 3.38 | 89.91 | 4.80 | 85.11 | 0.00 | 0.00 |
September | 280.14 | 13.73 | 120.53 | 31.28 | 89.25 | 0.00 | 0.00 |
October | 416.77 | 69.41 | 207.36 | 115.79 | 91.57 | 0.00 | 0.00 |
November | 455.59 | 128.15 | 259.00 | 171.20 | 87.81 | 0.00 | 0.00 |
December | 362.09 | 170.25 | 231.15 | 144.85 | 86.31 | 0.00 | 0.00 |
Annual Sum or Average | 325.68 | 66.96 | 156.73 | 69.35 | 87.39 | 0.00 | 0.00 |
Minimum of Months | 245.92 | 0.92 | 81.26 | 1.17 | 79.87 | 0.00 | 0.00 |
Maximum of Months | 455.59 | 170.25 | 259.00 | 171.20 | 98.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 331.85 | 157.10 | 216.30 | 131.43 | 84.87 | 0.00 | 0.00 |
February | 339.70 | 128.27 | 205.67 | 114.24 | 91.44 | 0.00 | 0.00 |
March | 335.39 | 78.92 | 175.86 | 77.67 | 98.18 | 0.00 | 0.00 |
April | 310.41 | 28.81 | 123.52 | 34.86 | 88.66 | 0.00 | 0.00 |
May | 279.95 | 5.90 | 88.83 | 6.58 | 82.25 | 0.00 | 0.00 |
June | 272.34 | 4.81 | 81.26 | 1.39 | 79.87 | 0.00 | 0.00 |
July | 249.24 | 1.38 | 84.76 | 1.17 | 83.59 | 0.00 | 0.00 |
August | 237.18 | 4.96 | 89.91 | 4.80 | 85.11 | 0.00 | 0.00 |
September | 274.76 | 17.14 | 120.53 | 31.28 | 89.25 | 0.00 | 0.00 |
October | 413.63 | 71.16 | 207.36 | 115.79 | 91.57 | 0.00 | 0.00 |
November | 455.13 | 125.45 | 259.00 | 171.20 | 87.81 | 0.00 | 0.00 |
December | 363.68 | 163.19 | 231.15 | 144.85 | 86.31 | 0.00 | 0.00 |
Annual Sum or Average | 321.72 | 65.31 | 156.73 | 69.35 | 87.39 | 0.00 | 0.00 |
Minimum of Months | 237.18 | 1.38 | 81.26 | 1.17 | 79.87 | 0.00 | 0.00 |
Maximum of Months | 455.13 | 163.19 | 259.00 | 171.20 | 98.18 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.175086E+10 | 0.949010E+09 | 0.116108E+10 | 0.705501E+09 | 0.455577E+09 | 0.00 | 0.00 |
February | 0.163069E+10 | 0.683400E+09 | 0.997176E+09 | 0.553860E+09 | 0.443316E+09 | 0.00 | 0.00 |
March | 0.179876E+10 | 0.447979E+09 | 0.943961E+09 | 0.416940E+09 | 0.527021E+09 | 0.00 | 0.00 |
April | 0.164307E+10 | 0.143270E+09 | 0.641653E+09 | 0.181094E+09 | 0.460559E+09 | 0.00 | 0.00 |
May | 0.157293E+10 | 22522619.65 | 0.476814E+09 | 35297219.41 | 0.441517E+09 | 0.00 | 0.00 |
June | 0.148553E+10 | 17053142.92 | 0.422093E+09 | 7202893.78 | 0.414890E+09 | 0.00 | 0.00 |
July | 0.143251E+10 | 4637247.12 | 0.454959E+09 | 6257586.91 | 0.448701E+09 | 0.00 | 0.00 |
August | 0.133679E+10 | 15381961.60 | 0.482615E+09 | 25775282.24 | 0.456840E+09 | 0.00 | 0.00 |
September | 0.146451E+10 | 63331040.78 | 0.626114E+09 | 0.162509E+09 | 0.463605E+09 | 0.00 | 0.00 |
October | 0.223786E+10 | 0.358704E+09 | 0.111307E+10 | 0.621533E+09 | 0.491536E+09 | 0.00 | 0.00 |
November | 0.236219E+10 | 0.671590E+09 | 0.134543E+10 | 0.889304E+09 | 0.456131E+09 | 0.00 | 0.00 |
December | 0.192720E+10 | 0.953104E+09 | 0.124079E+10 | 0.777515E+09 | 0.463277E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.206429E+11 | 0.432998E+10 | 0.990576E+10 | 0.438279E+10 | 0.552297E+10 | 0.00 | 0.00 |
Minimum of Months | 0.133679E+10 | 4637247.12 | 0.422093E+09 | 6257586.91 | 0.414890E+09 | 0.00 | 0.00 |
Maximum of Months | 0.236219E+10 | 0.953104E+09 | 0.134543E+10 | 0.889304E+09 | 0.527021E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.864531E+09 | 0.496512E+09 | 0.580539E+09 | 0.352751E+09 | 0.227789E+09 | 0.00 | 0.00 |
February | 0.808060E+09 | 0.354288E+09 | 0.498588E+09 | 0.276930E+09 | 0.221658E+09 | 0.00 | 0.00 |
March | 0.897188E+09 | 0.229609E+09 | 0.471981E+09 | 0.208470E+09 | 0.263511E+09 | 0.00 | 0.00 |
April | 0.826948E+09 | 72779886.75 | 0.320826E+09 | 90547127.65 | 0.230279E+09 | 0.00 | 0.00 |
May | 0.798281E+09 | 10912322.28 | 0.238407E+09 | 17648609.70 | 0.220759E+09 | 0.00 | 0.00 |
June | 0.756807E+09 | 8418783.61 | 0.211046E+09 | 3601446.89 | 0.207445E+09 | 0.00 | 0.00 |
July | 0.730345E+09 | 2076892.70 | 0.227479E+09 | 3128793.45 | 0.224351E+09 | 0.00 | 0.00 |
August | 0.680532E+09 | 6888507.09 | 0.241308E+09 | 12887641.12 | 0.228420E+09 | 0.00 | 0.00 |
September | 0.740070E+09 | 29422301.03 | 0.313057E+09 | 81254607.36 | 0.231802E+09 | 0.00 | 0.00 |
October | 0.112219E+10 | 0.178574E+09 | 0.556535E+09 | 0.310767E+09 | 0.245768E+09 | 0.00 | 0.00 |
November | 0.117891E+10 | 0.339767E+09 | 0.672717E+09 | 0.444652E+09 | 0.228065E+09 | 0.00 | 0.00 |
December | 0.955171E+09 | 0.491248E+09 | 0.620396E+09 | 0.388757E+09 | 0.231639E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.103590E+11 | 0.222050E+10 | 0.495288E+10 | 0.219139E+10 | 0.276149E+10 | 0.00 | 0.00 |
Minimum of Months | 0.680532E+09 | 2076892.70 | 0.211046E+09 | 3128793.45 | 0.207445E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117891E+10 | 0.496512E+09 | 0.672717E+09 | 0.444652E+09 | 0.263511E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.866167E+09 | 0.484424E+09 | 0.579348E+09 | 0.352027E+09 | 0.227321E+09 | 0.00 | 0.00 |
February | 0.807209E+09 | 0.353746E+09 | 0.497565E+09 | 0.276362E+09 | 0.221203E+09 | 0.00 | 0.00 |
March | 0.893465E+09 | 0.239224E+09 | 0.471012E+09 | 0.208042E+09 | 0.262970E+09 | 0.00 | 0.00 |
April | 0.811677E+09 | 82291457.60 | 0.320168E+09 | 90361372.24 | 0.229807E+09 | 0.00 | 0.00 |
May | 0.768348E+09 | 15108658.87 | 0.237918E+09 | 17612403.98 | 0.220306E+09 | 0.00 | 0.00 |
June | 0.726712E+09 | 11808604.92 | 0.210613E+09 | 3594058.60 | 0.207019E+09 | 0.00 | 0.00 |
July | 0.696150E+09 | 3316223.18 | 0.227013E+09 | 3122374.80 | 0.223890E+09 | 0.00 | 0.00 |
August | 0.656804E+09 | 11373028.01 | 0.240812E+09 | 12861202.41 | 0.227951E+09 | 0.00 | 0.00 |
September | 0.725164E+09 | 40487201.36 | 0.312415E+09 | 81087915.35 | 0.231327E+09 | 0.00 | 0.00 |
October | 0.111584E+10 | 0.194857E+09 | 0.555393E+09 | 0.310129E+09 | 0.245264E+09 | 0.00 | 0.00 |
November | 0.117629E+10 | 0.347365E+09 | 0.671337E+09 | 0.443740E+09 | 0.227598E+09 | 0.00 | 0.00 |
December | 0.955101E+09 | 0.486292E+09 | 0.619123E+09 | 0.387960E+09 | 0.231164E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101989E+11 | 0.227029E+10 | 0.494272E+10 | 0.218690E+10 | 0.275582E+10 | 0.00 | 0.00 |
Minimum of Months | 0.656804E+09 | 3316223.18 | 0.210613E+09 | 3122374.80 | 0.207019E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117629E+10 | 0.486292E+09 | 0.671337E+09 | 0.443740E+09 | 0.262970E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.868804E+09 | 0.477243E+09 | 0.579348E+09 | 0.352027E+09 | 0.227321E+09 | 0.00 | 0.00 |
February | 0.808305E+09 | 0.350782E+09 | 0.497565E+09 | 0.276362E+09 | 0.221203E+09 | 0.00 | 0.00 |
March | 0.893540E+09 | 0.238996E+09 | 0.471012E+09 | 0.208042E+09 | 0.262970E+09 | 0.00 | 0.00 |
April | 0.810715E+09 | 83691831.31 | 0.320168E+09 | 90361372.24 | 0.229807E+09 | 0.00 | 0.00 |
May | 0.765165E+09 | 16305992.22 | 0.237918E+09 | 17612403.98 | 0.220306E+09 | 0.00 | 0.00 |
June | 0.723160E+09 | 12536264.36 | 0.210613E+09 | 3594058.60 | 0.207019E+09 | 0.00 | 0.00 |
July | 0.691912E+09 | 3663901.69 | 0.227013E+09 | 3122374.80 | 0.223890E+09 | 0.00 | 0.00 |
August | 0.654232E+09 | 12216653.78 | 0.240812E+09 | 12861202.41 | 0.227951E+09 | 0.00 | 0.00 |
September | 0.724230E+09 | 42542002.30 | 0.312415E+09 | 81087915.35 | 0.231327E+09 | 0.00 | 0.00 |
October | 0.111543E+10 | 0.196479E+09 | 0.555393E+09 | 0.310129E+09 | 0.245264E+09 | 0.00 | 0.00 |
November | 0.117652E+10 | 0.346615E+09 | 0.671337E+09 | 0.443740E+09 | 0.227598E+09 | 0.00 | 0.00 |
December | 0.956669E+09 | 0.482159E+09 | 0.619123E+09 | 0.387960E+09 | 0.231164E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101887E+11 | 0.226323E+10 | 0.494272E+10 | 0.218690E+10 | 0.275582E+10 | 0.00 | 0.00 |
Minimum of Months | 0.654232E+09 | 3663901.69 | 0.210613E+09 | 3122374.80 | 0.207019E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117652E+10 | 0.482159E+09 | 0.671337E+09 | 0.443740E+09 | 0.262970E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.872527E+09 | 0.469129E+09 | 0.579348E+09 | 0.352027E+09 | 0.227321E+09 | 0.00 | 0.00 |
February | 0.810449E+09 | 0.346175E+09 | 0.497565E+09 | 0.276362E+09 | 0.221203E+09 | 0.00 | 0.00 |
March | 0.894722E+09 | 0.235966E+09 | 0.471012E+09 | 0.208042E+09 | 0.262970E+09 | 0.00 | 0.00 |
April | 0.811806E+09 | 81988375.01 | 0.320168E+09 | 90361372.24 | 0.229807E+09 | 0.00 | 0.00 |
May | 0.766698E+09 | 15656350.85 | 0.237918E+09 | 17612403.98 | 0.220306E+09 | 0.00 | 0.00 |
June | 0.724983E+09 | 12176532.71 | 0.210613E+09 | 3594058.60 | 0.207019E+09 | 0.00 | 0.00 |
July | 0.693436E+09 | 3391496.54 | 0.227013E+09 | 3122374.80 | 0.223890E+09 | 0.00 | 0.00 |
August | 0.655649E+09 | 11516440.67 | 0.240812E+09 | 12861202.41 | 0.227951E+09 | 0.00 | 0.00 |
September | 0.724946E+09 | 40958643.68 | 0.312415E+09 | 81087915.35 | 0.231327E+09 | 0.00 | 0.00 |
October | 0.111599E+10 | 0.194470E+09 | 0.555393E+09 | 0.310129E+09 | 0.245264E+09 | 0.00 | 0.00 |
November | 0.117757E+10 | 0.343833E+09 | 0.671337E+09 | 0.443740E+09 | 0.227598E+09 | 0.00 | 0.00 |
December | 0.959350E+09 | 0.476829E+09 | 0.619123E+09 | 0.387960E+09 | 0.231164E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102081E+11 | 0.223209E+10 | 0.494272E+10 | 0.218690E+10 | 0.275582E+10 | 0.00 | 0.00 |
Minimum of Months | 0.655649E+09 | 3391496.54 | 0.210613E+09 | 3122374.80 | 0.207019E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117757E+10 | 0.476829E+09 | 0.671337E+09 | 0.443740E+09 | 0.262970E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.176209E+10 | 0.905546E+09 | 0.115870E+10 | 0.704054E+09 | 0.454643E+09 | 0.00 | 0.00 |
February | 0.163176E+10 | 0.671579E+09 | 0.995131E+09 | 0.552724E+09 | 0.442407E+09 | 0.00 | 0.00 |
March | 0.179496E+10 | 0.455007E+09 | 0.942025E+09 | 0.416085E+09 | 0.525940E+09 | 0.00 | 0.00 |
April | 0.162633E+10 | 0.154694E+09 | 0.640337E+09 | 0.180723E+09 | 0.459614E+09 | 0.00 | 0.00 |
May | 0.153438E+10 | 28109972.77 | 0.475836E+09 | 35224807.95 | 0.440611E+09 | 0.00 | 0.00 |
June | 0.145321E+10 | 22731400.79 | 0.421227E+09 | 7188117.20 | 0.414039E+09 | 0.00 | 0.00 |
July | 0.138573E+10 | 5439218.88 | 0.454026E+09 | 6244749.61 | 0.447781E+09 | 0.00 | 0.00 |
August | 0.131215E+10 | 19326349.42 | 0.481625E+09 | 25722404.83 | 0.455903E+09 | 0.00 | 0.00 |
September | 0.144916E+10 | 73900387.19 | 0.624829E+09 | 0.162176E+09 | 0.462654E+09 | 0.00 | 0.00 |
October | 0.223123E+10 | 0.377105E+09 | 0.111079E+10 | 0.620258E+09 | 0.490528E+09 | 0.00 | 0.00 |
November | 0.235970E+10 | 0.673334E+09 | 0.134267E+10 | 0.887480E+09 | 0.455195E+09 | 0.00 | 0.00 |
December | 0.193183E+10 | 0.930103E+09 | 0.123825E+10 | 0.775920E+09 | 0.462327E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.204725E+11 | 0.431688E+10 | 0.988544E+10 | 0.437380E+10 | 0.551164E+10 | 0.00 | 0.00 |
Minimum of Months | 0.131215E+10 | 5439218.88 | 0.421227E+09 | 6244749.61 | 0.414039E+09 | 0.00 | 0.00 |
Maximum of Months | 0.235970E+10 | 0.930103E+09 | 0.134267E+10 | 0.887480E+09 | 0.525940E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.880622E+09 | 0.451401E+09 | 0.579348E+09 | 0.352027E+09 | 0.227321E+09 | 0.00 | 0.00 |
February | 0.815147E+09 | 0.334850E+09 | 0.497565E+09 | 0.276362E+09 | 0.221203E+09 | 0.00 | 0.00 |
March | 0.897600E+09 | 0.225683E+09 | 0.471012E+09 | 0.208042E+09 | 0.262970E+09 | 0.00 | 0.00 |
April | 0.816024E+09 | 75533181.57 | 0.320168E+09 | 90361372.24 | 0.229807E+09 | 0.00 | 0.00 |
May | 0.773861E+09 | 13054149.65 | 0.237918E+09 | 17612403.98 | 0.220306E+09 | 0.00 | 0.00 |
June | 0.733756E+09 | 10786159.83 | 0.210613E+09 | 3594058.60 | 0.207019E+09 | 0.00 | 0.00 |
July | 0.699821E+09 | 2372951.68 | 0.227013E+09 | 3122374.80 | 0.223890E+09 | 0.00 | 0.00 |
August | 0.661225E+09 | 8642961.58 | 0.240812E+09 | 12861202.41 | 0.227951E+09 | 0.00 | 0.00 |
September | 0.727279E+09 | 34660978.21 | 0.312415E+09 | 81087915.35 | 0.231327E+09 | 0.00 | 0.00 |
October | 0.111651E+10 | 0.185985E+09 | 0.555393E+09 | 0.310129E+09 | 0.245264E+09 | 0.00 | 0.00 |
November | 0.117944E+10 | 0.335122E+09 | 0.671337E+09 | 0.443740E+09 | 0.227598E+09 | 0.00 | 0.00 |
December | 0.965338E+09 | 0.464140E+09 | 0.619123E+09 | 0.387960E+09 | 0.231164E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102666E+11 | 0.214223E+10 | 0.494272E+10 | 0.218690E+10 | 0.275582E+10 | 0.00 | 0.00 |
Minimum of Months | 0.661225E+09 | 2372951.68 | 0.210613E+09 | 3122374.80 | 0.207019E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117944E+10 | 0.464140E+09 | 0.671337E+09 | 0.443740E+09 | 0.262970E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.882043E+09 | 0.448668E+09 | 0.579348E+09 | 0.352027E+09 | 0.227321E+09 | 0.00 | 0.00 |
February | 0.816163E+09 | 0.333034E+09 | 0.497565E+09 | 0.276362E+09 | 0.221203E+09 | 0.00 | 0.00 |
March | 0.898218E+09 | 0.224640E+09 | 0.471012E+09 | 0.208042E+09 | 0.262970E+09 | 0.00 | 0.00 |
April | 0.816489E+09 | 75095725.68 | 0.320168E+09 | 90361372.24 | 0.229807E+09 | 0.00 | 0.00 |
May | 0.774369E+09 | 12930235.61 | 0.237918E+09 | 17612403.98 | 0.220306E+09 | 0.00 | 0.00 |
June | 0.734302E+09 | 10699378.83 | 0.210613E+09 | 3594058.60 | 0.207019E+09 | 0.00 | 0.00 |
July | 0.700273E+09 | 2339463.08 | 0.227013E+09 | 3122374.80 | 0.223890E+09 | 0.00 | 0.00 |
August | 0.661631E+09 | 8531291.70 | 0.240812E+09 | 12861202.41 | 0.227951E+09 | 0.00 | 0.00 |
September | 0.727583E+09 | 34391397.03 | 0.312415E+09 | 81087915.35 | 0.231327E+09 | 0.00 | 0.00 |
October | 0.111678E+10 | 0.185495E+09 | 0.555393E+09 | 0.310129E+09 | 0.245264E+09 | 0.00 | 0.00 |
November | 0.117993E+10 | 0.334239E+09 | 0.671337E+09 | 0.443740E+09 | 0.227598E+09 | 0.00 | 0.00 |
December | 0.966610E+09 | 0.462000E+09 | 0.619123E+09 | 0.387960E+09 | 0.231164E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102744E+11 | 0.213206E+10 | 0.494272E+10 | 0.218690E+10 | 0.275582E+10 | 0.00 | 0.00 |
Minimum of Months | 0.661631E+09 | 2339463.08 | 0.210613E+09 | 3122374.80 | 0.207019E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117993E+10 | 0.462000E+09 | 0.671337E+09 | 0.443740E+09 | 0.262970E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.885203E+09 | 0.441640E+09 | 0.579348E+09 | 0.352027E+09 | 0.227321E+09 | 0.00 | 0.00 |
February | 0.818701E+09 | 0.327802E+09 | 0.497565E+09 | 0.276362E+09 | 0.221203E+09 | 0.00 | 0.00 |
March | 0.899440E+09 | 0.221834E+09 | 0.471012E+09 | 0.208042E+09 | 0.262970E+09 | 0.00 | 0.00 |
April | 0.815873E+09 | 74832581.30 | 0.320168E+09 | 90361372.24 | 0.229807E+09 | 0.00 | 0.00 |
May | 0.771947E+09 | 13318679.97 | 0.237918E+09 | 17612403.98 | 0.220306E+09 | 0.00 | 0.00 |
June | 0.731344E+09 | 10945697.91 | 0.210613E+09 | 3594058.60 | 0.207019E+09 | 0.00 | 0.00 |
July | 0.696472E+09 | 2476535.95 | 0.227013E+09 | 3122374.80 | 0.223890E+09 | 0.00 | 0.00 |
August | 0.658683E+09 | 9053782.61 | 0.240812E+09 | 12861202.41 | 0.227951E+09 | 0.00 | 0.00 |
September | 0.726122E+09 | 35583813.21 | 0.312415E+09 | 81087915.35 | 0.231327E+09 | 0.00 | 0.00 |
October | 0.111627E+10 | 0.185909E+09 | 0.555393E+09 | 0.310129E+09 | 0.245264E+09 | 0.00 | 0.00 |
November | 0.118088E+10 | 0.332168E+09 | 0.671337E+09 | 0.443740E+09 | 0.227598E+09 | 0.00 | 0.00 |
December | 0.969820E+09 | 0.456006E+09 | 0.619123E+09 | 0.387960E+09 | 0.231164E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102708E+11 | 0.211157E+10 | 0.494272E+10 | 0.218690E+10 | 0.275582E+10 | 0.00 | 0.00 |
Minimum of Months | 0.658683E+09 | 2476535.95 | 0.210613E+09 | 3122374.80 | 0.207019E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118088E+10 | 0.456006E+09 | 0.671337E+09 | 0.443740E+09 | 0.262970E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.888818E+09 | 0.420783E+09 | 0.579348E+09 | 0.352027E+09 | 0.227321E+09 | 0.00 | 0.00 |
February | 0.821805E+09 | 0.310310E+09 | 0.497565E+09 | 0.276362E+09 | 0.221203E+09 | 0.00 | 0.00 |
March | 0.898304E+09 | 0.211370E+09 | 0.471012E+09 | 0.208042E+09 | 0.262970E+09 | 0.00 | 0.00 |
April | 0.804590E+09 | 74663694.06 | 0.320168E+09 | 90361372.24 | 0.229807E+09 | 0.00 | 0.00 |
May | 0.749809E+09 | 15801687.39 | 0.237918E+09 | 17612403.98 | 0.220306E+09 | 0.00 | 0.00 |
June | 0.705903E+09 | 12473542.04 | 0.210613E+09 | 3594058.60 | 0.207019E+09 | 0.00 | 0.00 |
July | 0.667577E+09 | 3701982.61 | 0.227013E+09 | 3122374.80 | 0.223890E+09 | 0.00 | 0.00 |
August | 0.635266E+09 | 13275164.48 | 0.240812E+09 | 12861202.41 | 0.227951E+09 | 0.00 | 0.00 |
September | 0.712167E+09 | 44415703.20 | 0.312415E+09 | 81087915.35 | 0.231327E+09 | 0.00 | 0.00 |
October | 0.110787E+10 | 0.190607E+09 | 0.555393E+09 | 0.310129E+09 | 0.245264E+09 | 0.00 | 0.00 |
November | 0.117969E+10 | 0.325160E+09 | 0.671337E+09 | 0.443740E+09 | 0.227598E+09 | 0.00 | 0.00 |
December | 0.974072E+09 | 0.437082E+09 | 0.619123E+09 | 0.387960E+09 | 0.231164E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101459E+11 | 0.205964E+10 | 0.494272E+10 | 0.218690E+10 | 0.275582E+10 | 0.00 | 0.00 |
Minimum of Months | 0.635266E+09 | 3701982.61 | 0.210613E+09 | 3122374.80 | 0.207019E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117969E+10 | 0.437082E+09 | 0.671337E+09 | 0.443740E+09 | 0.262970E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.304236E+09 | -186900533.3 | 0.00 | 0.00 | 744.00 | 0.00 | -117335839.7 | 59.00 | 0.00 | 0.00 |
February | 0.270105E+09 | -166084927.7 | 0.00 | 0.00 | 672.00 | 0.00 | -104020054.7 | 58.99 | 0.00 | 0.00 |
March | 0.287839E+09 | -174470919.6 | 0.00 | 0.00 | 744.00 | 0.00 | -113367677.0 | 58.99 | 0.00 | 0.00 |
April | 0.258005E+09 | -149533462.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108471967.1 | 58.98 | 0.00 | 0.00 |
May | 0.247781E+09 | -136565107.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111216307.7 | 58.99 | 0.00 | 0.00 |
June | 0.227201E+09 | -119848265.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107352779.4 | 58.99 | 0.00 | 0.00 |
July | 0.226442E+09 | -115656734.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110785451.1 | 58.99 | 0.00 | 0.00 |
August | 0.233240E+09 | -122268151.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110971885.9 | 58.99 | 0.00 | 0.00 |
September | 0.237103E+09 | -129347782.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107754941.5 | 58.99 | 0.00 | 0.00 |
October | 0.262226E+09 | -150062097.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112164395.3 | 58.99 | 0.00 | 0.00 |
November | 0.271938E+09 | -162148953.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109789136.3 | 58.99 | 0.00 | 0.00 |
December | 0.297386E+09 | -181756517.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115629936.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.312350E+10 | -0.179464E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132886E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.226442E+09 | -186900533.3 | 0.00 | 0.00 | 672.00 | 0.00 | -117335839.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.304236E+09 | -115656734.1 | 0.00 | 0.00 | 744.00 | 0.00 | -104020054.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.302697E+09 | -186925818.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115771634.5 | 58.99 | 0.00 | 0.00 |
February | 0.269272E+09 | -166092676.7 | 0.00 | 0.00 | 672.00 | 0.00 | -103179125.9 | 58.99 | 0.00 | 0.00 |
March | 0.287425E+09 | -174467357.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112957911.5 | 58.99 | 0.00 | 0.00 |
April | 0.257916E+09 | -149520349.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108395203.2 | 58.99 | 0.00 | 0.00 |
May | 0.247829E+09 | -136558455.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111270715.5 | 58.99 | 0.00 | 0.00 |
June | 0.227321E+09 | -119845817.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107475016.4 | 58.99 | 0.00 | 0.00 |
July | 0.226603E+09 | -115662599.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110940233.3 | 58.99 | 0.00 | 0.00 |
August | 0.233383E+09 | -122267232.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111115384.1 | 58.99 | 0.00 | 0.00 |
September | 0.237196E+09 | -129348192.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107847827.6 | 58.99 | 0.00 | 0.00 |
October | 0.262168E+09 | -150064944.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112103432.5 | 58.99 | 0.00 | 0.00 |
November | 0.271615E+09 | -162148668.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109466373.3 | 58.99 | 0.00 | 0.00 |
December | 0.296344E+09 | -181754654.2 | 0.00 | 0.00 | 744.00 | 0.00 | -114589003.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.311977E+10 | -0.179466E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132511E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.226603E+09 | -186925818.2 | 0.00 | 0.00 | 672.00 | 0.00 | -115771634.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.302697E+09 | -115662599.4 | 0.00 | 0.00 | 744.00 | 0.00 | -103179125.9 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.281093E+09 | -164376490.8 | 0.00 | 0.00 | 744.00 | 0.00 | -116716792.6 | 58.99 | 0.00 | 0.00 |
February | 0.249339E+09 | -146194364.0 | 0.00 | 0.00 | 672.00 | 0.00 | -103144881.1 | 58.99 | 0.00 | 0.00 |
March | 0.267627E+09 | -155694307.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111932240.4 | 58.99 | 0.00 | 0.00 |
April | 0.237988E+09 | -131507608.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106480362.2 | 58.99 | 0.00 | 0.00 |
May | 0.229976E+09 | -121170266.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108805762.5 | 58.99 | 0.00 | 0.00 |
June | 0.211830E+09 | -106755549.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105074646.3 | 58.98 | 0.00 | 0.00 |
July | 0.209490E+09 | -101118154.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108372267.4 | 58.99 | 0.00 | 0.00 |
August | 0.218192E+09 | -109215217.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108976773.3 | 58.99 | 0.00 | 0.00 |
September | 0.219552E+09 | -113723181.1 | 0.00 | 0.00 | 720.00 | 0.00 | -105829286.4 | 58.99 | 0.00 | 0.00 |
October | 0.242393E+09 | -131999399.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110393867.5 | 58.99 | 0.00 | 0.00 |
November | 0.251922E+09 | -143155883.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108766033.7 | 58.99 | 0.00 | 0.00 |
December | 0.273626E+09 | -158647029.2 | 0.00 | 0.00 | 744.00 | 0.00 | -114978908.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.289303E+10 | -0.158356E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130947E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.209490E+09 | -164376490.8 | 0.00 | 0.00 | 672.00 | 0.00 | -116716792.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.281093E+09 | -101118154.2 | 0.00 | 0.00 | 744.00 | 0.00 | -103144881.1 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.281510E+09 | -164354886.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117155246.1 | 59.00 | 0.00 | 0.00 |
February | 0.249520E+09 | -146176267.4 | 0.00 | 0.00 | 672.00 | 0.00 | -103344163.7 | 59.00 | 0.00 | 0.00 |
March | 0.267637E+09 | -155694222.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111942669.2 | 58.99 | 0.00 | 0.00 |
April | 0.237888E+09 | -131506056.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106382405.8 | 58.99 | 0.00 | 0.00 |
May | 0.229782E+09 | -121155051.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108626913.6 | 58.99 | 0.00 | 0.00 |
June | 0.211648E+09 | -106777799.5 | 0.00 | 0.00 | 720.00 | 0.00 | -104870105.7 | 58.98 | 0.00 | 0.00 |
July | 0.209290E+09 | -101116894.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108172758.4 | 58.99 | 0.00 | 0.00 |
August | 0.218026E+09 | -109211215.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108814747.6 | 58.99 | 0.00 | 0.00 |
September | 0.219424E+09 | -113729306.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105694896.2 | 58.99 | 0.00 | 0.00 |
October | 0.242309E+09 | -132004584.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110304362.9 | 58.99 | 0.00 | 0.00 |
November | 0.251967E+09 | -143168159.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108798395.6 | 58.99 | 0.00 | 0.00 |
December | 0.273865E+09 | -158645368.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115219217.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.289287E+10 | -0.158354E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130933E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.209290E+09 | -164354886.2 | 0.00 | 0.00 | 672.00 | 0.00 | -117155246.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.281510E+09 | -101116894.9 | 0.00 | 0.00 | 744.00 | 0.00 | -103344163.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.274134E+09 | -155358741.9 | 0.00 | 0.00 | 744.00 | 0.00 | -118775546.3 | 58.99 | 0.00 | 0.00 |
February | 0.242542E+09 | -138244038.7 | 0.00 | 0.00 | 672.00 | 0.00 | -104297867.4 | 58.99 | 0.00 | 0.00 |
March | 0.260064E+09 | -147311358.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112752631.5 | 58.99 | 0.00 | 0.00 |
April | 0.231412E+09 | -124450582.1 | 0.00 | 0.00 | 720.00 | 0.00 | -106961558.8 | 58.99 | 0.00 | 0.00 |
May | 0.223700E+09 | -114592066.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109108244.0 | 58.99 | 0.00 | 0.00 |
June | 0.206369E+09 | -100973496.9 | 0.00 | 0.00 | 720.00 | 0.00 | -105395835.0 | 58.99 | 0.00 | 0.00 |
July | 0.204117E+09 | -95631771.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108485389.5 | 58.99 | 0.00 | 0.00 |
August | 0.212582E+09 | -103334942.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109246901.8 | 58.99 | 0.00 | 0.00 |
September | 0.213738E+09 | -107602882.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106135234.7 | 59.00 | 0.00 | 0.00 |
October | 0.235570E+09 | -124750325.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110819933.7 | 58.99 | 0.00 | 0.00 |
November | 0.244650E+09 | -135236489.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109413418.8 | 58.98 | 0.00 | 0.00 |
December | 0.266408E+09 | -150033819.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116374329.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.281529E+10 | -0.149752E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131777E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.204117E+09 | -155358741.9 | 0.00 | 0.00 | 672.00 | 0.00 | -118775546.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.274134E+09 | -95631771.1 | 0.00 | 0.00 | 744.00 | 0.00 | -104297867.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.274258E+09 | -155358320.0 | 0.00 | 0.00 | 744.00 | 0.00 | -118899653.6 | 58.99 | 0.00 | 0.00 |
February | 0.242590E+09 | -138241183.0 | 0.00 | 0.00 | 672.00 | 0.00 | -104349247.2 | 58.99 | 0.00 | 0.00 |
March | 0.260121E+09 | -147296360.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112825134.4 | 59.00 | 0.00 | 0.00 |
April | 0.231522E+09 | -124458295.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107063996.5 | 58.99 | 0.00 | 0.00 |
May | 0.223836E+09 | -114569019.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109266533.7 | 58.99 | 0.00 | 0.00 |
June | 0.206544E+09 | -101012167.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105531551.2 | 58.98 | 0.00 | 0.00 |
July | 0.204261E+09 | -95628785.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108632033.3 | 58.99 | 0.00 | 0.00 |
August | 0.212726E+09 | -103322234.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109404102.0 | 58.99 | 0.00 | 0.00 |
September | 0.213871E+09 | -107636031.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106234645.6 | 58.99 | 0.00 | 0.00 |
October | 0.235676E+09 | -124758302.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110917829.8 | 58.99 | 0.00 | 0.00 |
November | 0.244709E+09 | -135239944.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109469324.5 | 58.98 | 0.00 | 0.00 |
December | 0.266471E+09 | -150032926.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116437821.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.281659E+10 | -0.149755E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131903E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.204261E+09 | -155358320.0 | 0.00 | 0.00 | 672.00 | 0.00 | -118899653.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.274258E+09 | -95628785.1 | 0.00 | 0.00 | 744.00 | 0.00 | -104349247.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.274434E+09 | -155353106.2 | 0.00 | 0.00 | 744.00 | 0.00 | -119080851.1 | 58.99 | 0.00 | 0.00 |
February | 0.242697E+09 | -138243686.1 | 0.00 | 0.00 | 672.00 | 0.00 | -104453244.3 | 58.99 | 0.00 | 0.00 |
March | 0.260177E+09 | -147321120.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112856336.7 | 58.99 | 0.00 | 0.00 |
April | 0.231556E+09 | -124453382.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107102933.8 | 58.99 | 0.00 | 0.00 |
May | 0.223866E+09 | -114591260.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109274925.1 | 58.99 | 0.00 | 0.00 |
June | 0.206556E+09 | -100999545.0 | 0.00 | 0.00 | 720.00 | 0.00 | -105556921.9 | 58.99 | 0.00 | 0.00 |
July | 0.204284E+09 | -95627487.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108656197.7 | 58.99 | 0.00 | 0.00 |
August | 0.212750E+09 | -103335818.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109413989.9 | 58.99 | 0.00 | 0.00 |
September | 0.213884E+09 | -107598545.2 | 0.00 | 0.00 | 720.00 | 0.00 | -106285222.6 | 59.00 | 0.00 | 0.00 |
October | 0.235699E+09 | -124747188.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110951927.9 | 58.99 | 0.00 | 0.00 |
November | 0.244756E+09 | -135192216.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109563803.1 | 59.00 | 0.00 | 0.00 |
December | 0.266607E+09 | -150034802.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116571766.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.281727E+10 | -0.149750E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131977E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.204284E+09 | -155353106.2 | 0.00 | 0.00 | 672.00 | 0.00 | -119080851.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.274434E+09 | -95627487.1 | 0.00 | 0.00 | 744.00 | 0.00 | -104453244.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 319.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 364.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 372.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 317.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 315.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.325642E+09 | 66944.00 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27269883.19 | 5017.76 | 11-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36906255.57 | 16226.87 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.325642E+09 | 66944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 55435641.51 | 29741.89 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1090931.56 | 805.91 | 23-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56526573.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55435641.51 | 29741.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112671E+09 | 33870.07 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 212247.27 | 469.70 | 02-FEB-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3427101.86 | 871.75 | 23-DEC-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116310E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112671E+09 | 33870.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.150345E+09 | 34216.23 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 934279.55 | 519.65 | 02-FEB-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6175038.55 | 1149.81 | 23-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.150345E+09 | 34216.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.207391E+09 | 34067.08 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4109787.57 | 792.88 | 02-FEB-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12126925.18 | 2286.48 | 23-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.207391E+09 | 34067.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.464156E+09 | 61945.03 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29649381.82 | 3857.33 | 02-FEB-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36226159.83 | 16194.61 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.530031E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.464156E+09 | 61945.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.251939E+09 | 32594.18 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15311199.49 | 1889.72 | 11-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19023498.96 | 9128.01 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.251939E+09 | 32594.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.269137E+09 | 32503.07 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18706807.32 | 3731.16 | 11-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22449923.96 | 10803.41 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.310294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.269137E+09 | 32503.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.329088E+09 | 32661.26 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 32338370.38 | 10203.94 | 11-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 37258177.84 | 16111.32 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.398684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.329088E+09 | 32661.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.505079E+09 | 37730.62 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 92389435.53 | 31419.84 | 11-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101331E+09 | 34113.31 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.698799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.505079E+09 | 37730.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.148935E+10 | 0.132330E+10 | 7587.50 | 12-JAN-15:00 | 7037.62 | 0.00 |
February | 0.00 | 0.00 | 0.626964E+10 | 0.541684E+10 | 13768.41 | 22-FEB-15:00 | 12476.09 | 0.00 |
March | 0.00 | 0.00 | 0.166694E+11 | 0.142954E+11 | 26101.14 | 11-MAR-08:63 | 19447.13 | 0.00 |
April | 0.00 | 0.00 | 0.276709E+11 | 0.247182E+11 | 63398.92 | 27-APR-07:02 | 51552.75 | 0.00 |
May | 0.00 | 0.00 | 0.399831E+11 | 0.321441E+11 | 68446.06 | 24-MAY-07:02 | 39901.11 | 0.00 |
June | 0.00 | 0.00 | 0.448228E+11 | 0.321831E+11 | 69251.40 | 26-JUN-07:01 | 37721.67 | 0.00 |
July | 0.00 | 0.00 | 0.500637E+11 | 0.301909E+11 | 70295.61 | 25-JUL-07:01 | 35655.15 | 0.00 |
August | 0.00 | 0.00 | 0.493092E+11 | 0.279562E+11 | 69745.04 | 10-AUG-07:01 | 38802.53 | 0.00 |
September | 0.00 | 0.00 | 0.409028E+11 | 0.248787E+11 | 69421.48 | 03-SEP-07:01 | 38891.10 | 0.00 |
October | 0.00 | 0.00 | 0.273454E+11 | 0.216599E+11 | 65807.97 | 11-OCT-07:02 | 47944.52 | 0.00 |
November | 0.00 | 0.00 | 0.141744E+11 | 0.120981E+11 | 18940.22 | 09-NOV-14:30 | 16583.31 | 0.00 |
December | 0.00 | 0.00 | 0.353337E+10 | 0.304545E+10 | 10098.55 | 28-DEC-15:00 | 8964.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.322234E+12 | 0.229910E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.148935E+10 | 0.132330E+10 | 7587.50 | 7037.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.500637E+11 | 0.321831E+11 | 70295.61 | 51552.75 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.141569E+10 | 0.122221E+10 | 4293.60 | 12-JAN-15:00 | 3998.27 | 0.00 |
February | 0.00 | 0.00 | 0.398013E+10 | 0.342785E+10 | 7275.22 | 22-FEB-15:00 | 6608.65 | 0.00 |
March | 0.00 | 0.00 | 0.890115E+10 | 0.769208E+10 | 14585.90 | 11-MAR-08:63 | 11889.44 | 0.00 |
April | 0.00 | 0.00 | 0.136622E+11 | 0.122612E+11 | 31586.65 | 17-APR-07:01 | 28406.55 | 0.00 |
May | 0.00 | 0.00 | 0.194371E+11 | 0.157219E+11 | 33717.53 | 24-MAY-07:02 | 23147.33 | 0.00 |
June | 0.00 | 0.00 | 0.216526E+11 | 0.156237E+11 | 33904.26 | 18-JUN-07:01 | 22639.92 | 0.00 |
July | 0.00 | 0.00 | 0.242584E+11 | 0.147317E+11 | 34274.71 | 25-JUL-07:01 | 21524.20 | 0.00 |
August | 0.00 | 0.00 | 0.238943E+11 | 0.136416E+11 | 34142.62 | 10-AUG-07:01 | 22524.28 | 0.00 |
September | 0.00 | 0.00 | 0.198062E+11 | 0.121811E+11 | 34026.27 | 03-SEP-07:01 | 22816.02 | 0.00 |
October | 0.00 | 0.00 | 0.136080E+11 | 0.109079E+11 | 32541.68 | 11-OCT-07:02 | 26690.07 | 0.00 |
November | 0.00 | 0.00 | 0.777154E+10 | 0.668133E+10 | 9824.73 | 04-NOV-13:00 | 9027.46 | 0.00 |
December | 0.00 | 0.00 | 0.278150E+10 | 0.236193E+10 | 5605.11 | 03-DEC-14:00 | 5254.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161169E+12 | 0.116454E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.141569E+10 | 0.122221E+10 | 4293.60 | 3998.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.242584E+11 | 0.157219E+11 | 34274.71 | 28406.55 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.739448E+09 | 0.669140E+09 | 3950.31 | 12-JAN-15:00 | 3692.06 | 0.00 |
February | 0.00 | 0.00 | 0.275217E+10 | 0.242529E+10 | 7038.65 | 22-FEB-14:00 | 6416.01 | 0.00 |
March | 0.00 | 0.00 | 0.693435E+10 | 0.604202E+10 | 23441.08 | 11-MAR-07:03 | 16579.58 | 0.00 |
April | 0.00 | 0.00 | 0.109814E+11 | 0.987893E+10 | 33482.16 | 17-APR-06:01 | 25110.25 | 0.00 |
May | 0.00 | 0.00 | 0.160311E+11 | 0.129129E+11 | 35022.12 | 23-MAY-06:02 | 19734.96 | 0.00 |
June | 0.00 | 0.00 | 0.179193E+11 | 0.127820E+11 | 36620.49 | 26-JUN-06:01 | 15308.60 | 0.00 |
July | 0.00 | 0.00 | 0.197498E+11 | 0.117083E+11 | 36652.50 | 23-JUL-07:01 | 15765.52 | 0.00 |
August | 0.00 | 0.00 | 0.199055E+11 | 0.110870E+11 | 36732.27 | 21-AUG-06:03 | 14406.05 | 0.00 |
September | 0.00 | 0.00 | 0.161652E+11 | 0.973361E+10 | 36739.86 | 04-SEP-07:01 | 16011.49 | 0.00 |
October | 0.00 | 0.00 | 0.109053E+11 | 0.872645E+10 | 34290.31 | 01-OCT-07:02 | 22622.62 | 0.00 |
November | 0.00 | 0.00 | 0.598942E+10 | 0.523313E+10 | 9905.75 | 04-NOV-13:00 | 9081.14 | 0.00 |
December | 0.00 | 0.00 | 0.172702E+10 | 0.152130E+10 | 5170.89 | 02-DEC-14:00 | 5143.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.129800E+12 | 0.927201E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.739448E+09 | 0.669140E+09 | 3950.31 | 3692.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.199055E+11 | 0.129129E+11 | 36739.86 | 25110.25 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.665951E+09 | 0.602271E+09 | 3829.47 | 12-JAN-15:00 | 3579.96 | 0.00 |
February | 0.00 | 0.00 | 0.268048E+10 | 0.236317E+10 | 6983.96 | 22-FEB-14:00 | 6368.44 | 0.00 |
March | 0.00 | 0.00 | 0.692697E+10 | 0.603817E+10 | 23645.36 | 11-MAR-07:03 | 16735.10 | 0.00 |
April | 0.00 | 0.00 | 0.110419E+11 | 0.993846E+10 | 33601.76 | 17-APR-06:01 | 25343.96 | 0.00 |
May | 0.00 | 0.00 | 0.161568E+11 | 0.130298E+11 | 35115.05 | 23-MAY-06:02 | 19909.44 | 0.00 |
June | 0.00 | 0.00 | 0.180448E+11 | 0.128934E+11 | 36717.55 | 26-JUN-06:01 | 15485.45 | 0.00 |
July | 0.00 | 0.00 | 0.198963E+11 | 0.118288E+11 | 36749.65 | 23-JUL-07:01 | 15909.09 | 0.00 |
August | 0.00 | 0.00 | 0.200187E+11 | 0.111780E+11 | 36829.63 | 21-AUG-06:02 | 14683.18 | 0.00 |
September | 0.00 | 0.00 | 0.162567E+11 | 0.980850E+10 | 36837.24 | 04-SEP-07:01 | 16175.15 | 0.00 |
October | 0.00 | 0.00 | 0.109648E+11 | 0.878206E+10 | 34396.40 | 01-OCT-07:02 | 22773.77 | 0.00 |
November | 0.00 | 0.00 | 0.596538E+10 | 0.521403E+10 | 9902.86 | 04-NOV-13:00 | 9083.27 | 0.00 |
December | 0.00 | 0.00 | 0.163783E+10 | 0.144382E+10 | 5127.16 | 02-DEC-14:00 | 5102.52 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.130257E+12 | 0.931204E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.665951E+09 | 0.602271E+09 | 3829.47 | 3579.96 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.200187E+11 | 0.130298E+11 | 36837.24 | 25343.96 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.536710E+09 | 0.483896E+09 | 3582.62 | 12-JAN-15:00 | 3343.48 | 0.00 |
February | 0.00 | 0.00 | 0.249134E+10 | 0.219558E+10 | 6815.03 | 22-FEB-14:00 | 6205.19 | 0.00 |
March | 0.00 | 0.00 | 0.672186E+10 | 0.585171E+10 | 21223.90 | 11-MAR-07:03 | 14869.75 | 0.00 |
April | 0.00 | 0.00 | 0.108904E+11 | 0.979302E+10 | 33460.16 | 17-APR-06:01 | 25175.50 | 0.00 |
May | 0.00 | 0.00 | 0.160256E+11 | 0.129097E+11 | 34973.33 | 23-MAY-06:02 | 19690.08 | 0.00 |
June | 0.00 | 0.00 | 0.179099E+11 | 0.127771E+11 | 36574.50 | 26-JUN-06:03 | 15151.57 | 0.00 |
July | 0.00 | 0.00 | 0.197629E+11 | 0.117238E+11 | 36606.47 | 23-JUL-07:01 | 15719.14 | 0.00 |
August | 0.00 | 0.00 | 0.198584E+11 | 0.110541E+11 | 36686.14 | 21-AUG-06:02 | 14521.88 | 0.00 |
September | 0.00 | 0.00 | 0.160998E+11 | 0.968440E+10 | 36693.73 | 04-SEP-07:01 | 16020.04 | 0.00 |
October | 0.00 | 0.00 | 0.108050E+11 | 0.864009E+10 | 34251.43 | 01-OCT-07:02 | 22586.32 | 0.00 |
November | 0.00 | 0.00 | 0.577739E+10 | 0.504297E+10 | 9762.01 | 04-NOV-13:00 | 8943.06 | 0.00 |
December | 0.00 | 0.00 | 0.144160E+10 | 0.127060E+10 | 4969.29 | 02-DEC-14:00 | 4940.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.128321E+12 | 0.914270E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.536710E+09 | 0.483896E+09 | 3582.62 | 3343.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.198584E+11 | 0.129097E+11 | 36693.73 | 25175.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.769908E+09 | 0.675705E+09 | 6673.57 | 12-JAN-15:10 | 6061.61 | 0.00 |
February | 0.00 | 0.00 | 0.429617E+10 | 0.370801E+10 | 13088.77 | 22-FEB-14:00 | 11635.57 | 0.00 |
March | 0.00 | 0.00 | 0.124585E+11 | 0.106554E+11 | 26977.35 | 11-MAR-08:63 | 19103.49 | 0.00 |
April | 0.00 | 0.00 | 0.205409E+11 | 0.183417E+11 | 61115.19 | 17-APR-07:01 | 45408.98 | 0.00 |
May | 0.00 | 0.00 | 0.305606E+11 | 0.243658E+11 | 63986.07 | 21-MAY-08:61 | 38231.54 | 0.00 |
June | 0.00 | 0.00 | 0.342760E+11 | 0.241235E+11 | 66912.75 | 26-JUN-07:03 | 27572.32 | 0.00 |
July | 0.00 | 0.00 | 0.376277E+11 | 0.217913E+11 | 66962.68 | 23-JUL-08:61 | 28017.95 | 0.00 |
August | 0.00 | 0.00 | 0.380507E+11 | 0.205822E+11 | 67173.34 | 21-AUG-07:02 | 26433.86 | 0.00 |
September | 0.00 | 0.00 | 0.305445E+11 | 0.179207E+11 | 67203.80 | 04-SEP-08:61 | 28565.03 | 0.00 |
October | 0.00 | 0.00 | 0.203331E+11 | 0.159827E+11 | 62541.07 | 01-OCT-08:62 | 41215.81 | 0.00 |
November | 0.00 | 0.00 | 0.105419E+11 | 0.901239E+10 | 18718.74 | 04-NOV-14:40 | 17070.36 | 0.00 |
December | 0.00 | 0.00 | 0.217024E+10 | 0.187295E+10 | 8894.15 | 28-DEC-14:00 | 7774.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.242170E+12 | 0.169032E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.769908E+09 | 0.675705E+09 | 6673.57 | 6061.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.380507E+11 | 0.243658E+11 | 67203.80 | 45408.98 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.350389E+09 | 0.308303E+09 | 3390.77 | 12-JAN-15:10 | 3100.37 | 0.00 |
February | 0.00 | 0.00 | 0.217190E+10 | 0.188670E+10 | 6775.35 | 22-FEB-14:00 | 6052.89 | 0.00 |
March | 0.00 | 0.00 | 0.644777E+10 | 0.553990E+10 | 13020.60 | 11-MAR-08:63 | 9256.79 | 0.00 |
April | 0.00 | 0.00 | 0.107002E+11 | 0.957978E+10 | 32107.23 | 17-APR-07:01 | 23887.68 | 0.00 |
May | 0.00 | 0.00 | 0.159590E+11 | 0.127536E+11 | 33598.43 | 21-MAY-08:61 | 20074.63 | 0.00 |
June | 0.00 | 0.00 | 0.178828E+11 | 0.126119E+11 | 35112.61 | 26-JUN-07:03 | 14341.00 | 0.00 |
July | 0.00 | 0.00 | 0.196384E+11 | 0.113938E+11 | 35138.81 | 23-JUL-08:61 | 14591.89 | 0.00 |
August | 0.00 | 0.00 | 0.198415E+11 | 0.107471E+11 | 35249.36 | 21-AUG-07:02 | 13647.58 | 0.00 |
September | 0.00 | 0.00 | 0.159265E+11 | 0.935978E+10 | 35265.34 | 04-SEP-08:61 | 14821.49 | 0.00 |
October | 0.00 | 0.00 | 0.105757E+11 | 0.834321E+10 | 32845.22 | 01-OCT-08:62 | 21633.09 | 0.00 |
November | 0.00 | 0.00 | 0.545184E+10 | 0.468446E+10 | 9773.16 | 06-NOV-14:00 | 8060.00 | 0.00 |
December | 0.00 | 0.00 | 0.106234E+10 | 0.923472E+09 | 4564.14 | 02-DEC-14:20 | 4490.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126008E+12 | 0.881321E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.350389E+09 | 0.308303E+09 | 3390.77 | 3100.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.198415E+11 | 0.127536E+11 | 35265.34 | 23887.68 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.326230E+09 | 0.286549E+09 | 3318.38 | 12-JAN-15:10 | 3032.73 | 0.00 |
February | 0.00 | 0.00 | 0.211631E+10 | 0.183835E+10 | 6712.39 | 22-FEB-14:00 | 5994.03 | 0.00 |
March | 0.00 | 0.00 | 0.638334E+10 | 0.548247E+10 | 12593.72 | 11-MAR-08:63 | 8935.01 | 0.00 |
April | 0.00 | 0.00 | 0.106556E+11 | 0.953792E+10 | 32026.62 | 17-APR-07:01 | 23813.76 | 0.00 |
May | 0.00 | 0.00 | 0.159199E+11 | 0.127190E+11 | 33513.75 | 21-MAY-08:61 | 20007.28 | 0.00 |
June | 0.00 | 0.00 | 0.178423E+11 | 0.125779E+11 | 35024.96 | 26-JUN-07:01 | 14433.77 | 0.00 |
July | 0.00 | 0.00 | 0.196020E+11 | 0.113656E+11 | 35051.10 | 23-JUL-08:03 | 14398.80 | 0.00 |
August | 0.00 | 0.00 | 0.198019E+11 | 0.107170E+11 | 35161.37 | 21-AUG-07:02 | 13599.00 | 0.00 |
September | 0.00 | 0.00 | 0.158873E+11 | 0.932965E+10 | 35177.31 | 04-SEP-08:61 | 14773.13 | 0.00 |
October | 0.00 | 0.00 | 0.105322E+11 | 0.830549E+10 | 32763.19 | 01-OCT-08:62 | 21563.52 | 0.00 |
November | 0.00 | 0.00 | 0.539614E+10 | 0.463491E+10 | 9726.21 | 06-NOV-14:00 | 8017.87 | 0.00 |
December | 0.00 | 0.00 | 0.101362E+10 | 0.881698E+09 | 4511.91 | 02-DEC-14:20 | 4438.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.125477E+12 | 0.876764E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.326230E+09 | 0.286549E+09 | 3318.38 | 3032.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.198019E+11 | 0.127190E+11 | 35177.31 | 23813.76 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.277783E+09 | 0.243301E+09 | 3162.78 | 12-JAN-15:10 | 2889.36 | 0.00 |
February | 0.00 | 0.00 | 0.198815E+10 | 0.172850E+10 | 6591.25 | 22-FEB-14:00 | 5883.27 | 0.00 |
March | 0.00 | 0.00 | 0.625299E+10 | 0.536952E+10 | 11572.44 | 29-MAR-13:00 | 9399.20 | 0.00 |
April | 0.00 | 0.00 | 0.106652E+11 | 0.954837E+10 | 32161.56 | 17-APR-07:01 | 23922.07 | 0.00 |
May | 0.00 | 0.00 | 0.160260E+11 | 0.128168E+11 | 33656.38 | 21-MAY-08:61 | 20105.90 | 0.00 |
June | 0.00 | 0.00 | 0.179700E+11 | 0.126902E+11 | 35177.18 | 26-JUN-07:01 | 14482.53 | 0.00 |
July | 0.00 | 0.00 | 0.197611E+11 | 0.114935E+11 | 35203.43 | 23-JUL-08:61 | 14621.21 | 0.00 |
August | 0.00 | 0.00 | 0.199557E+11 | 0.108357E+11 | 35314.18 | 21-AUG-07:03 | 13570.23 | 0.00 |
September | 0.00 | 0.00 | 0.159926E+11 | 0.941334E+10 | 35330.19 | 04-SEP-08:61 | 14861.63 | 0.00 |
October | 0.00 | 0.00 | 0.105564E+11 | 0.832881E+10 | 32905.96 | 01-OCT-08:62 | 21692.77 | 0.00 |
November | 0.00 | 0.00 | 0.529459E+10 | 0.454728E+10 | 9691.21 | 09-NOV-13:50 | 8271.31 | 0.00 |
December | 0.00 | 0.00 | 0.906479E+09 | 0.790381E+09 | 4376.90 | 02-DEC-14:20 | 4305.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.125647E+12 | 0.878057E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.277783E+09 | 0.243301E+09 | 3162.78 | 2889.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.199557E+11 | 0.128168E+11 | 35330.19 | 23922.07 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.323349E+09 | 0.288563E+09 | 3408.26 | 12-JAN-15:10 | 3162.52 | 0.00 |
February | 0.00 | 0.00 | 0.218153E+10 | 0.192738E+10 | 7343.26 | 22-FEB-14:00 | 6652.79 | 0.00 |
March | 0.00 | 0.00 | 0.690438E+10 | 0.601183E+10 | 13112.53 | 29-MAR-13:00 | 10836.02 | 0.00 |
April | 0.00 | 0.00 | 0.122403E+11 | 0.110765E+11 | 36497.04 | 17-APR-07:01 | 27137.32 | 0.00 |
May | 0.00 | 0.00 | 0.184390E+11 | 0.150162E+11 | 38555.70 | 24-MAY-07:02 | 20659.69 | 0.00 |
June | 0.00 | 0.00 | 0.204804E+11 | 0.148682E+11 | 39815.12 | 26-JUN-07:01 | 15446.05 | 0.00 |
July | 0.00 | 0.00 | 0.224818E+11 | 0.135881E+11 | 39844.83 | 23-JUL-08:61 | 15806.15 | 0.00 |
August | 0.00 | 0.00 | 0.226798E+11 | 0.128977E+11 | 39970.19 | 21-AUG-07:03 | 15789.36 | 0.00 |
September | 0.00 | 0.00 | 0.181696E+11 | 0.111460E+11 | 39988.31 | 04-SEP-08:61 | 16956.52 | 0.00 |
October | 0.00 | 0.00 | 0.121269E+11 | 0.977053E+10 | 37280.62 | 01-OCT-08:62 | 25236.49 | 0.00 |
November | 0.00 | 0.00 | 0.592412E+10 | 0.516838E+10 | 10862.63 | 09-NOV-13:30 | 9367.71 | 0.00 |
December | 0.00 | 0.00 | 0.102413E+10 | 0.908335E+09 | 4727.51 | 28-DEC-14:00 | 4215.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142975E+12 | 0.102668E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.323349E+09 | 0.288563E+09 | 3408.26 | 3162.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.226798E+11 | 0.150162E+11 | 39988.31 | 27137.32 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.209110E+10 | 0.37 | 2869.72 | 01-JAN-08:62 | 0.89 |
February | 0.188508E+10 | 0.37 | 1276.95 | 11-FEB-08:62 | 0.58 |
March | 0.209099E+10 | 0.37 | 1147.89 | 04-MAR-14:40 | 0.54 |
April | 0.202257E+10 | 0.37 | 2869.72 | 16-APR-07:02 | 0.89 |
May | 0.217672E+10 | 0.38 | 2869.72 | 01-MAY-07:01 | 0.89 |
June | 0.220535E+10 | 0.39 | 2869.72 | 01-JUN-07:02 | 0.89 |
July | 0.227682E+10 | 0.38 | 2869.72 | 01-JUL-07:01 | 0.89 |
August | 0.224754E+10 | 0.38 | 2869.72 | 01-AUG-07:01 | 0.88 |
September | 0.207082E+10 | 0.37 | 2869.72 | 01-SEP-07:01 | 0.89 |
October | 0.208459E+10 | 0.37 | 2869.72 | 01-OCT-07:02 | 0.89 |
November | 0.201248E+10 | 0.37 | 1147.89 | 01-NOV-21:20 | 0.54 |
December | 0.209194E+10 | 0.37 | 1565.25 | 23-DEC-08:62 | 0.66 |
Annual Sum or Average | 0.252560E+11 | 0.37 | |||
Minimum of Months | 0.188508E+10 | 0.37 | 1147.89 | 0.54 | |
Maximum of Months | 0.227682E+10 | 0.39 | 2869.72 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.838913E+09 | 0.38 | 1394.83 | 02-JAN-08:61 | 0.89 |
February | 0.774761E+09 | 0.39 | 602.15 | 03-FEB-15:30 | 0.56 |
March | 0.892432E+09 | 0.39 | 602.15 | 01-MAR-12:50 | 0.56 |
April | 0.889509E+09 | 0.39 | 1505.39 | 16-APR-07:02 | 0.92 |
May | 0.999395E+09 | 0.39 | 1505.39 | 01-MAY-07:01 | 0.93 |
June | 0.103375E+10 | 0.40 | 1505.39 | 01-JUN-07:02 | 0.92 |
July | 0.107667E+10 | 0.40 | 1505.39 | 01-JUL-07:01 | 0.92 |
August | 0.105640E+10 | 0.40 | 1505.39 | 01-AUG-07:01 | 0.92 |
September | 0.945563E+09 | 0.39 | 1505.39 | 01-SEP-07:01 | 0.92 |
October | 0.911176E+09 | 0.39 | 1505.39 | 01-OCT-07:02 | 0.92 |
November | 0.848831E+09 | 0.39 | 602.15 | 01-NOV-09:30 | 0.56 |
December | 0.844317E+09 | 0.39 | 623.63 | 23-DEC-08:30 | 0.57 |
Annual Sum or Average | 0.111117E+11 | 0.39 | |||
Minimum of Months | 0.774761E+09 | 0.38 | 602.15 | 0.56 | |
Maximum of Months | 0.107667E+10 | 0.40 | 1505.39 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.880920E+09 | 0.30 | 1510.04 | 01-JAN-08:62 | 0.92 |
February | 0.794933E+09 | 0.30 | 619.16 | 02-FEB-08:05 | 0.57 |
March | 0.895483E+09 | 0.31 | 975.48 | 11-MAR-07:03 | 0.74 |
April | 0.854080E+09 | 0.30 | 1516.57 | 03-APR-06:02 | 0.92 |
May | 0.930806E+09 | 0.31 | 1516.57 | 01-MAY-06:01 | 0.93 |
June | 0.951258E+09 | 0.32 | 1516.57 | 01-JUN-06:02 | 0.92 |
July | 0.965556E+09 | 0.32 | 1516.57 | 01-JUL-06:01 | 0.92 |
August | 0.971026E+09 | 0.32 | 1516.57 | 01-AUG-06:01 | 0.91 |
September | 0.872555E+09 | 0.31 | 1516.57 | 01-SEP-06:01 | 0.91 |
October | 0.879644E+09 | 0.30 | 1516.57 | 01-OCT-07:02 | 0.92 |
November | 0.851708E+09 | 0.30 | 606.63 | 02-NOV-10:30 | 0.56 |
December | 0.873638E+09 | 0.30 | 629.88 | 23-DEC-08:04 | 0.58 |
Annual Sum or Average | 0.107216E+11 | 0.31 | |||
Minimum of Months | 0.794933E+09 | 0.30 | 606.63 | 0.56 | |
Maximum of Months | 0.971026E+09 | 0.32 | 1516.57 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.884835E+09 | 0.30 | 1521.60 | 01-JAN-08:62 | 0.92 |
February | 0.797587E+09 | 0.30 | 622.51 | 02-FEB-08:05 | 0.57 |
March | 0.898454E+09 | 0.31 | 986.25 | 11-MAR-07:03 | 0.74 |
April | 0.856997E+09 | 0.30 | 1521.60 | 03-APR-06:02 | 0.92 |
May | 0.934962E+09 | 0.31 | 1521.60 | 01-MAY-06:01 | 0.93 |
June | 0.955766E+09 | 0.32 | 1521.60 | 01-JUN-06:02 | 0.92 |
July | 0.970561E+09 | 0.32 | 1521.60 | 01-JUL-06:01 | 0.92 |
August | 0.975277E+09 | 0.32 | 1521.60 | 01-AUG-06:01 | 0.91 |
September | 0.875774E+09 | 0.31 | 1521.60 | 01-SEP-06:01 | 0.91 |
October | 0.882632E+09 | 0.30 | 1521.60 | 01-OCT-07:02 | 0.92 |
November | 0.854531E+09 | 0.30 | 608.64 | 01-NOV-07:00 | 0.56 |
December | 0.876606E+09 | 0.30 | 639.32 | 23-DEC-07:20 | 0.58 |
Annual Sum or Average | 0.107640E+11 | 0.31 | |||
Minimum of Months | 0.797587E+09 | 0.30 | 608.64 | 0.56 | |
Maximum of Months | 0.975277E+09 | 0.32 | 1521.60 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.882064E+09 | 0.30 | 1514.19 | 01-JAN-08:62 | 0.92 |
February | 0.793787E+09 | 0.30 | 626.82 | 02-FEB-08:05 | 0.57 |
March | 0.894044E+09 | 0.31 | 855.91 | 11-MAR-07:03 | 0.69 |
April | 0.852636E+09 | 0.30 | 1514.19 | 03-APR-06:02 | 0.92 |
May | 0.929480E+09 | 0.31 | 1514.19 | 01-MAY-06:01 | 0.93 |
June | 0.949844E+09 | 0.32 | 1514.19 | 01-JUN-06:02 | 0.92 |
July | 0.964958E+09 | 0.32 | 1514.19 | 01-JUL-06:01 | 0.92 |
August | 0.969030E+09 | 0.32 | 1514.19 | 01-AUG-06:01 | 0.91 |
September | 0.870520E+09 | 0.31 | 1514.19 | 01-SEP-06:01 | 0.91 |
October | 0.878165E+09 | 0.30 | 1514.19 | 01-OCT-07:02 | 0.92 |
November | 0.850369E+09 | 0.30 | 605.68 | 01-NOV-06:05 | 0.56 |
December | 0.872496E+09 | 0.30 | 666.65 | 23-DEC-07:40 | 0.60 |
Annual Sum or Average | 0.107074E+11 | 0.31 | |||
Minimum of Months | 0.793787E+09 | 0.30 | 605.68 | 0.56 | |
Maximum of Months | 0.969030E+09 | 0.32 | 1514.19 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141669E+10 | 0.27 | 2629.65 | 01-JAN-09:01 | 0.89 |
February | 0.127309E+10 | 0.27 | 1150.11 | 02-FEB-08:05 | 0.57 |
March | 0.143516E+10 | 0.28 | 1051.86 | 06-MAR-20:50 | 0.54 |
April | 0.137390E+10 | 0.27 | 2629.65 | 09-APR-08:62 | 0.90 |
May | 0.154851E+10 | 0.29 | 2629.65 | 01-MAY-07:01 | 0.90 |
June | 0.160364E+10 | 0.30 | 2629.65 | 01-JUN-07:02 | 0.89 |
July | 0.163422E+10 | 0.29 | 2629.65 | 01-JUL-07:01 | 0.89 |
August | 0.164119E+10 | 0.29 | 2629.65 | 01-AUG-07:01 | 0.88 |
September | 0.143917E+10 | 0.28 | 2629.65 | 01-SEP-07:01 | 0.89 |
October | 0.140920E+10 | 0.27 | 2629.65 | 01-OCT-08:62 | 0.89 |
November | 0.136321E+10 | 0.27 | 1051.86 | 02-NOV-18:00 | 0.54 |
December | 0.139822E+10 | 0.27 | 1464.35 | 23-DEC-08:62 | 0.67 |
Annual Sum or Average | 0.175362E+11 | 0.28 | |||
Minimum of Months | 0.127309E+10 | 0.27 | 1051.86 | 0.54 | |
Maximum of Months | 0.164119E+10 | 0.30 | 2629.65 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.776524E+09 | 0.28 | 1441.00 | 01-JAN-09:01 | 0.92 |
February | 0.697621E+09 | 0.28 | 626.53 | 11-FEB-08:62 | 0.59 |
March | 0.786441E+09 | 0.29 | 576.40 | 25-MAR-14:50 | 0.56 |
April | 0.752979E+09 | 0.28 | 1441.00 | 09-APR-08:62 | 0.93 |
May | 0.850350E+09 | 0.30 | 1441.00 | 01-MAY-07:01 | 0.93 |
June | 0.880431E+09 | 0.31 | 1441.00 | 01-JUN-07:02 | 0.92 |
July | 0.896107E+09 | 0.30 | 1441.00 | 01-JUL-07:01 | 0.92 |
August | 0.899577E+09 | 0.31 | 1441.00 | 01-AUG-07:01 | 0.91 |
September | 0.788301E+09 | 0.29 | 1441.00 | 01-SEP-07:01 | 0.92 |
October | 0.772070E+09 | 0.28 | 1441.00 | 01-OCT-08:62 | 0.92 |
November | 0.747016E+09 | 0.28 | 576.40 | 30-NOV-19:40 | 0.56 |
December | 0.766196E+09 | 0.28 | 818.53 | 23-DEC-08:62 | 0.70 |
Annual Sum or Average | 0.961361E+10 | 0.29 | |||
Minimum of Months | 0.697621E+09 | 0.28 | 576.40 | 0.56 | |
Maximum of Months | 0.899577E+09 | 0.31 | 1441.00 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.774559E+09 | 0.28 | 1436.48 | 01-JAN-09:01 | 0.92 |
February | 0.695520E+09 | 0.28 | 673.53 | 11-FEB-08:62 | 0.62 |
March | 0.783971E+09 | 0.29 | 574.59 | 05-MAR-10:00 | 0.56 |
April | 0.750599E+09 | 0.28 | 1436.48 | 09-APR-08:62 | 0.93 |
May | 0.847915E+09 | 0.30 | 1436.48 | 01-MAY-07:01 | 0.93 |
June | 0.877973E+09 | 0.31 | 1436.48 | 01-JUN-07:02 | 0.92 |
July | 0.893763E+09 | 0.30 | 1436.48 | 01-JUL-07:01 | 0.92 |
August | 0.897137E+09 | 0.31 | 1436.48 | 01-AUG-07:01 | 0.91 |
September | 0.785965E+09 | 0.29 | 1436.48 | 01-SEP-07:01 | 0.92 |
October | 0.769639E+09 | 0.28 | 1436.48 | 01-OCT-08:62 | 0.92 |
November | 0.744669E+09 | 0.28 | 574.59 | 07-NOV-09:20 | 0.56 |
December | 0.763881E+09 | 0.28 | 861.06 | 23-DEC-08:62 | 0.72 |
Annual Sum or Average | 0.958559E+10 | 0.29 | |||
Minimum of Months | 0.695520E+09 | 0.28 | 574.59 | 0.56 | |
Maximum of Months | 0.897137E+09 | 0.31 | 1436.48 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.780353E+09 | 0.28 | 1444.34 | 01-JAN-09:01 | 0.92 |
February | 0.699685E+09 | 0.28 | 848.48 | 11-FEB-08:62 | 0.71 |
March | 0.788260E+09 | 0.29 | 577.73 | 01-MAR-19:40 | 0.56 |
April | 0.754715E+09 | 0.28 | 1444.34 | 16-APR-08:61 | 0.92 |
May | 0.853974E+09 | 0.30 | 1444.34 | 01-MAY-07:01 | 0.93 |
June | 0.884558E+09 | 0.31 | 1444.34 | 01-JUN-07:02 | 0.92 |
July | 0.900991E+09 | 0.30 | 1444.34 | 01-JUL-07:01 | 0.92 |
August | 0.903951E+09 | 0.31 | 1444.34 | 01-AUG-07:01 | 0.91 |
September | 0.791318E+09 | 0.29 | 1444.34 | 01-SEP-07:01 | 0.92 |
October | 0.773901E+09 | 0.28 | 1444.34 | 01-OCT-08:62 | 0.92 |
November | 0.748743E+09 | 0.28 | 577.73 | 01-NOV-19:20 | 0.56 |
December | 0.768451E+09 | 0.28 | 1005.22 | 23-DEC-08:62 | 0.78 |
Annual Sum or Average | 0.964890E+10 | 0.29 | |||
Minimum of Months | 0.699685E+09 | 0.28 | 577.73 | 0.56 | |
Maximum of Months | 0.903951E+09 | 0.31 | 1444.34 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.888981E+09 | 0.27 | 1639.36 | 01-JAN-09:01 | 0.89 |
February | 0.795599E+09 | 0.27 | 1474.85 | 11-FEB-08:62 | 0.85 |
March | 0.894700E+09 | 0.28 | 655.75 | 08-MAR-10:30 | 0.54 |
April | 0.856707E+09 | 0.27 | 1639.36 | 16-APR-08:61 | 0.89 |
May | 0.975234E+09 | 0.29 | 1639.36 | 01-MAY-07:01 | 0.90 |
June | 0.100768E+10 | 0.30 | 1639.36 | 01-JUN-07:02 | 0.89 |
July | 0.102657E+10 | 0.29 | 1639.36 | 01-JUL-07:01 | 0.89 |
August | 0.102766E+10 | 0.30 | 1639.36 | 01-AUG-07:01 | 0.88 |
September | 0.901395E+09 | 0.28 | 1639.36 | 01-SEP-07:01 | 0.88 |
October | 0.878720E+09 | 0.27 | 1639.36 | 01-OCT-08:62 | 0.89 |
November | 0.849847E+09 | 0.27 | 655.75 | 10-NOV-20:15 | 0.54 |
December | 0.873735E+09 | 0.27 | 1545.06 | 23-DEC-08:62 | 0.87 |
Annual Sum or Average | 0.109768E+11 | 0.28 | |||
Minimum of Months | 0.795599E+09 | 0.27 | 655.75 | 0.54 | |
Maximum of Months | 0.102766E+10 | 0.30 | 1639.36 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.248764E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.353678E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.654186E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.984623E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.135457E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.145171E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.149008E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.142332E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.121493E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.922356E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.571989E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.302621E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.109728E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.248764E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.149008E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.120807E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.179885E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.321914E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.469597E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.646312E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.691580E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.712351E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.679538E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.576637E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.441153E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.283927E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.156381E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.528009E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.120807E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.712351E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.107388E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.150665E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.271784E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.390513E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.540892E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.576202E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.581107E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.568983E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.475908E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.368684E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.239529E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.132134E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.440379E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.107388E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.581107E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.105890E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.149181E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.271965E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.392378E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.544550E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.579836E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.585120E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.572078E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.478344E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.370437E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.239293E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.130190E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.441926E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.105890E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.585120E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.102277E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.144117E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.266564E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.388159E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.540561E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.575789E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.581330E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.567703E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.474217E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.366260E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.234373E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.124799E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.436615E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.102277E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.581330E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.162241E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.241069E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.476581E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.715254E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.101841E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.109138E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.109366E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.107279E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.883377E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.669746E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.413008E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.197390E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.803491E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.162241E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.109366E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.868679E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.126373E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.248250E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.371440E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.528949E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.566320E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.567436E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.556258E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.458143E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.347834E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.215479E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.104352E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.417770E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.868679E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.567436E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.860441E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.124772E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.246416E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.370017E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.527598E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.564949E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.566237E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.555002E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.456927E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.346513E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.213885E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.102870E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.416123E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.860441E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.566237E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.853655E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.122000E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.243777E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.370853E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.531226E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.569137E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.570963E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.559404E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.460053E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.347626E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.211901E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.100582E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.417289E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.853655E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.570963E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.974373E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.136771E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.272191E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.424591E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.611858E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.651713E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.653636E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.639873E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.525886E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.398152E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.238514E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.114212E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.476483E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.974373E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.653636E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.209110E+10 | 0.148935E+10 | 0.325642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188508E+10 | 0.626964E+10 | 27269883.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209099E+10 | 0.166694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202257E+10 | 0.276709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.217672E+10 | 0.399831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.220535E+10 | 0.448228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.227682E+10 | 0.500637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.224754E+10 | 0.493092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.207082E+10 | 0.409028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208459E+10 | 0.273454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201248E+10 | 0.141744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209194E+10 | 0.353337E+10 | 36906255.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252560E+11 | 0.322234E+12 | 0.389818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.188508E+10 | 0.148935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227682E+10 | 0.500637E+11 | 0.325642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.838913E+09 | 0.141569E+10 | 55435641.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.774761E+09 | 0.398013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.892432E+09 | 0.890115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.889509E+09 | 0.136622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.999395E+09 | 0.194371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103375E+10 | 0.216526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107667E+10 | 0.242584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105640E+10 | 0.238943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.945563E+09 | 0.198062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.911176E+09 | 0.136080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.848831E+09 | 0.777154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.844317E+09 | 0.278150E+10 | 1090931.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111117E+11 | 0.161169E+12 | 56526573.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.774761E+09 | 0.141569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107667E+10 | 0.242584E+11 | 55435641.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.880920E+09 | 0.739448E+09 | 0.112671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.794933E+09 | 0.275217E+10 | 212247.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.895483E+09 | 0.693435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.854080E+09 | 0.109814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.930806E+09 | 0.160311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.951258E+09 | 0.179193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.965556E+09 | 0.197498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.971026E+09 | 0.199055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.872555E+09 | 0.161652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.879644E+09 | 0.109053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.851708E+09 | 0.598942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.873638E+09 | 0.172702E+10 | 3427101.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107216E+11 | 0.129800E+12 | 0.116310E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.794933E+09 | 0.739448E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.971026E+09 | 0.199055E+11 | 0.112671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.884835E+09 | 0.665951E+09 | 0.150345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.797587E+09 | 0.268048E+10 | 934279.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.898454E+09 | 0.692697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.856997E+09 | 0.110419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.934962E+09 | 0.161568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.955766E+09 | 0.180448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.970561E+09 | 0.198963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.975277E+09 | 0.200187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.875774E+09 | 0.162567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.882632E+09 | 0.109648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.854531E+09 | 0.596538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.876606E+09 | 0.163783E+10 | 6175038.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107640E+11 | 0.130257E+12 | 0.157454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.797587E+09 | 0.665951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.975277E+09 | 0.200187E+11 | 0.150345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.882064E+09 | 0.536710E+09 | 0.207391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.793787E+09 | 0.249134E+10 | 4109787.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.894044E+09 | 0.672186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.852636E+09 | 0.108904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.929480E+09 | 0.160256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.949844E+09 | 0.179099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.964958E+09 | 0.197629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.969030E+09 | 0.198584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.870520E+09 | 0.160998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.878165E+09 | 0.108050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.850369E+09 | 0.577739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.872496E+09 | 0.144160E+10 | 12126925.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107074E+11 | 0.128321E+12 | 0.223627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.793787E+09 | 0.536710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.969030E+09 | 0.198584E+11 | 0.207391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141669E+10 | 0.769908E+09 | 0.464156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127309E+10 | 0.429617E+10 | 29649381.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143516E+10 | 0.124585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137390E+10 | 0.205409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154851E+10 | 0.305606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160364E+10 | 0.342760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163422E+10 | 0.376277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164119E+10 | 0.380507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143917E+10 | 0.305445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140920E+10 | 0.203331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136321E+10 | 0.105419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139822E+10 | 0.217024E+10 | 36226159.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175362E+11 | 0.242170E+12 | 0.530031E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127309E+10 | 0.769908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164119E+10 | 0.380507E+11 | 0.464156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.776524E+09 | 0.350389E+09 | 0.251939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.697621E+09 | 0.217190E+10 | 15311199.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.786441E+09 | 0.644777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.752979E+09 | 0.107002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.850350E+09 | 0.159590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.880431E+09 | 0.178828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.896107E+09 | 0.196384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.899577E+09 | 0.198415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.788301E+09 | 0.159265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.772070E+09 | 0.105757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.747016E+09 | 0.545184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.766196E+09 | 0.106234E+10 | 19023498.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.961361E+10 | 0.126008E+12 | 0.286274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.697621E+09 | 0.350389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.899577E+09 | 0.198415E+11 | 0.251939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.774559E+09 | 0.326230E+09 | 0.269137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.695520E+09 | 0.211631E+10 | 18706807.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.783971E+09 | 0.638334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.750599E+09 | 0.106556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.847915E+09 | 0.159199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.877973E+09 | 0.178423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.893763E+09 | 0.196020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.897137E+09 | 0.198019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.785965E+09 | 0.158873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.769639E+09 | 0.105322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.744669E+09 | 0.539614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.763881E+09 | 0.101362E+10 | 22449923.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.958559E+10 | 0.125477E+12 | 0.310294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.695520E+09 | 0.326230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.897137E+09 | 0.198019E+11 | 0.269137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.780353E+09 | 0.277783E+09 | 0.329088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.699685E+09 | 0.198815E+10 | 32338370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.788260E+09 | 0.625299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.754715E+09 | 0.106652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.853974E+09 | 0.160260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.884558E+09 | 0.179700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.900991E+09 | 0.197611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.903951E+09 | 0.199557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.791318E+09 | 0.159926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.773901E+09 | 0.105564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.748743E+09 | 0.529459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.768451E+09 | 0.906479E+09 | 37258177.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.964890E+10 | 0.125647E+12 | 0.398684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.699685E+09 | 0.277783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.903951E+09 | 0.199557E+11 | 0.329088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.888981E+09 | 0.323349E+09 | 0.505079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.795599E+09 | 0.218153E+10 | 92389435.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.894700E+09 | 0.690438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.856707E+09 | 0.122403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.975234E+09 | 0.184390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100768E+10 | 0.204804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102657E+10 | 0.224818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102766E+10 | 0.226798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.901395E+09 | 0.181696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.878720E+09 | 0.121269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.849847E+09 | 0.592412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.873735E+09 | 0.102413E+10 | 0.101331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109768E+11 | 0.142975E+12 | 0.698799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.795599E+09 | 0.323349E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.102766E+10 | 0.226798E+11 | 0.505079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.209110E+10 | 0.00 | 0.00 | 0.00 | 0.396531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188508E+10 | 0.00 | 0.00 | 0.00 | 0.165171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209099E+10 | 0.00 | 0.00 | 0.00 | 0.445087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202257E+10 | 0.00 | 0.00 | 0.00 | 0.782366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.217672E+10 | 0.00 | 0.00 | 0.00 | 0.113690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.220535E+10 | 0.00 | 0.00 | 0.00 | 0.123118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.227682E+10 | 0.00 | 0.00 | 0.00 | 0.126240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.224754E+10 | 0.00 | 0.00 | 0.00 | 0.119856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.207082E+10 | 0.00 | 0.00 | 0.00 | 0.100785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208459E+10 | 0.00 | 0.00 | 0.00 | 0.713897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201248E+10 | 0.00 | 0.00 | 0.00 | 0.370741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209194E+10 | 0.00 | 0.00 | 0.00 | 0.934268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252560E+11 | 0.00 | 0.00 | 0.00 | 0.844722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.188508E+10 | 0.00 | 0.00 | 0.00 | 0.396531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227682E+10 | 0.00 | 0.00 | 0.00 | 0.126240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.838913E+09 | 0.00 | 0.00 | 0.00 | 0.369158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.774761E+09 | 0.00 | 0.00 | 0.00 | 0.102409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.892432E+09 | 0.00 | 0.00 | 0.00 | 0.232671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.889509E+09 | 0.00 | 0.00 | 0.00 | 0.380646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.999395E+09 | 0.00 | 0.00 | 0.00 | 0.546373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103375E+10 | 0.00 | 0.00 | 0.00 | 0.588205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107667E+10 | 0.00 | 0.00 | 0.00 | 0.604685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105640E+10 | 0.00 | 0.00 | 0.00 | 0.573897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.945563E+09 | 0.00 | 0.00 | 0.00 | 0.482081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.911176E+09 | 0.00 | 0.00 | 0.00 | 0.350036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.848831E+09 | 0.00 | 0.00 | 0.00 | 0.199044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.844317E+09 | 0.00 | 0.00 | 0.00 | 0.719496E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111117E+11 | 0.00 | 0.00 | 0.00 | 0.416891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.774761E+09 | 0.00 | 0.00 | 0.00 | 0.369158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107667E+10 | 0.00 | 0.00 | 0.00 | 0.604685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.880920E+09 | 0.00 | 0.00 | 0.00 | 0.192962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.794933E+09 | 0.00 | 0.00 | 0.00 | 0.711721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.895483E+09 | 0.00 | 0.00 | 0.00 | 0.182235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.854080E+09 | 0.00 | 0.00 | 0.00 | 0.305105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.930806E+09 | 0.00 | 0.00 | 0.00 | 0.447812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.951258E+09 | 0.00 | 0.00 | 0.00 | 0.481076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.965556E+09 | 0.00 | 0.00 | 0.00 | 0.484552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.971026E+09 | 0.00 | 0.00 | 0.00 | 0.471881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.872555E+09 | 0.00 | 0.00 | 0.00 | 0.388652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.879644E+09 | 0.00 | 0.00 | 0.00 | 0.280720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.851708E+09 | 0.00 | 0.00 | 0.00 | 0.154358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.873638E+09 | 0.00 | 0.00 | 0.00 | 0.447701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107216E+11 | 0.00 | 0.00 | 0.00 | 0.333163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.794933E+09 | 0.00 | 0.00 | 0.00 | 0.192962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.971026E+09 | 0.00 | 0.00 | 0.00 | 0.484552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.884835E+09 | 0.00 | 0.00 | 0.00 | 0.174060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.797587E+09 | 0.00 | 0.00 | 0.00 | 0.694223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.898454E+09 | 0.00 | 0.00 | 0.00 | 0.182120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.856997E+09 | 0.00 | 0.00 | 0.00 | 0.306678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.934962E+09 | 0.00 | 0.00 | 0.00 | 0.451054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.955766E+09 | 0.00 | 0.00 | 0.00 | 0.484259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.970561E+09 | 0.00 | 0.00 | 0.00 | 0.488064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.975277E+09 | 0.00 | 0.00 | 0.00 | 0.474551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.875774E+09 | 0.00 | 0.00 | 0.00 | 0.390767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.882632E+09 | 0.00 | 0.00 | 0.00 | 0.282173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.854531E+09 | 0.00 | 0.00 | 0.00 | 0.153840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.876606E+09 | 0.00 | 0.00 | 0.00 | 0.425297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107640E+11 | 0.00 | 0.00 | 0.00 | 0.334286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.797587E+09 | 0.00 | 0.00 | 0.00 | 0.174060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.975277E+09 | 0.00 | 0.00 | 0.00 | 0.488064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.882064E+09 | 0.00 | 0.00 | 0.00 | 0.140709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.793787E+09 | 0.00 | 0.00 | 0.00 | 0.647383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.894044E+09 | 0.00 | 0.00 | 0.00 | 0.177159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.852636E+09 | 0.00 | 0.00 | 0.00 | 0.302896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.929480E+09 | 0.00 | 0.00 | 0.00 | 0.447613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.949844E+09 | 0.00 | 0.00 | 0.00 | 0.480805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.964958E+09 | 0.00 | 0.00 | 0.00 | 0.484834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.969030E+09 | 0.00 | 0.00 | 0.00 | 0.470800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.870520E+09 | 0.00 | 0.00 | 0.00 | 0.387165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.878165E+09 | 0.00 | 0.00 | 0.00 | 0.278443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.850369E+09 | 0.00 | 0.00 | 0.00 | 0.149336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.872496E+09 | 0.00 | 0.00 | 0.00 | 0.375492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107074E+11 | 0.00 | 0.00 | 0.00 | 0.329541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.793787E+09 | 0.00 | 0.00 | 0.00 | 0.140709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.969030E+09 | 0.00 | 0.00 | 0.00 | 0.484834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.141669E+10 | 0.00 | 0.00 | 0.00 | 0.205724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127309E+10 | 0.00 | 0.00 | 0.00 | 0.113760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143516E+10 | 0.00 | 0.00 | 0.00 | 0.333065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137390E+10 | 0.00 | 0.00 | 0.00 | 0.577864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154851E+10 | 0.00 | 0.00 | 0.00 | 0.863560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160364E+10 | 0.00 | 0.00 | 0.00 | 0.931019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163422E+10 | 0.00 | 0.00 | 0.00 | 0.930238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164119E+10 | 0.00 | 0.00 | 0.00 | 0.908672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143917E+10 | 0.00 | 0.00 | 0.00 | 0.739460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140920E+10 | 0.00 | 0.00 | 0.00 | 0.528826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136321E+10 | 0.00 | 0.00 | 0.00 | 0.276687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139822E+10 | 0.00 | 0.00 | 0.00 | 0.575682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175362E+11 | 0.00 | 0.00 | 0.00 | 0.628129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127309E+10 | 0.00 | 0.00 | 0.00 | 0.205724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164119E+10 | 0.00 | 0.00 | 0.00 | 0.931019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.776524E+09 | 0.00 | 0.00 | 0.00 | 92154811.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.697621E+09 | 0.00 | 0.00 | 0.00 | 0.566106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.786441E+09 | 0.00 | 0.00 | 0.00 | 0.169606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.752979E+09 | 0.00 | 0.00 | 0.00 | 0.296142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.850350E+09 | 0.00 | 0.00 | 0.00 | 0.443914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.880431E+09 | 0.00 | 0.00 | 0.00 | 0.478277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.896107E+09 | 0.00 | 0.00 | 0.00 | 0.477825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.899577E+09 | 0.00 | 0.00 | 0.00 | 0.466301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.788301E+09 | 0.00 | 0.00 | 0.00 | 0.379313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.772070E+09 | 0.00 | 0.00 | 0.00 | 0.270627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.747016E+09 | 0.00 | 0.00 | 0.00 | 0.140778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.766196E+09 | 0.00 | 0.00 | 0.00 | 0.277322E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.961361E+10 | 0.00 | 0.00 | 0.00 | 0.321634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.697621E+09 | 0.00 | 0.00 | 0.00 | 92154811.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.899577E+09 | 0.00 | 0.00 | 0.00 | 0.478277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.774559E+09 | 0.00 | 0.00 | 0.00 | 85881698.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.695520E+09 | 0.00 | 0.00 | 0.00 | 0.552198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.783971E+09 | 0.00 | 0.00 | 0.00 | 0.168019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.750599E+09 | 0.00 | 0.00 | 0.00 | 0.294957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.847915E+09 | 0.00 | 0.00 | 0.00 | 0.442807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.877973E+09 | 0.00 | 0.00 | 0.00 | 0.477152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.893763E+09 | 0.00 | 0.00 | 0.00 | 0.476860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.897137E+09 | 0.00 | 0.00 | 0.00 | 0.465288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.785965E+09 | 0.00 | 0.00 | 0.00 | 0.378331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.769639E+09 | 0.00 | 0.00 | 0.00 | 0.269549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.744669E+09 | 0.00 | 0.00 | 0.00 | 0.139419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.763881E+09 | 0.00 | 0.00 | 0.00 | 0.264821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.958559E+10 | 0.00 | 0.00 | 0.00 | 0.320267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.695520E+09 | 0.00 | 0.00 | 0.00 | 85881698.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.897137E+09 | 0.00 | 0.00 | 0.00 | 0.477152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.780353E+09 | 0.00 | 0.00 | 0.00 | 73301251.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.699685E+09 | 0.00 | 0.00 | 0.00 | 0.520319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.788260E+09 | 0.00 | 0.00 | 0.00 | 0.164951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.754715E+09 | 0.00 | 0.00 | 0.00 | 0.295382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.853974E+09 | 0.00 | 0.00 | 0.00 | 0.445828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.884558E+09 | 0.00 | 0.00 | 0.00 | 0.480681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.900991E+09 | 0.00 | 0.00 | 0.00 | 0.480864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.903951E+09 | 0.00 | 0.00 | 0.00 | 0.469009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.791318E+09 | 0.00 | 0.00 | 0.00 | 0.380921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.773901E+09 | 0.00 | 0.00 | 0.00 | 0.270236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.748743E+09 | 0.00 | 0.00 | 0.00 | 0.137027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.768451E+09 | 0.00 | 0.00 | 0.00 | 0.237371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.964890E+10 | 0.00 | 0.00 | 0.00 | 0.320800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.699685E+09 | 0.00 | 0.00 | 0.00 | 73301251.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.903951E+09 | 0.00 | 0.00 | 0.00 | 0.480864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.888981E+09 | 0.00 | 0.00 | 0.00 | 85391568.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.795599E+09 | 0.00 | 0.00 | 0.00 | 0.572109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.894700E+09 | 0.00 | 0.00 | 0.00 | 0.182721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.856707E+09 | 0.00 | 0.00 | 0.00 | 0.338920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.975234E+09 | 0.00 | 0.00 | 0.00 | 0.514335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100768E+10 | 0.00 | 0.00 | 0.00 | 0.550945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102657E+10 | 0.00 | 0.00 | 0.00 | 0.550979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102766E+10 | 0.00 | 0.00 | 0.00 | 0.537107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.901395E+09 | 0.00 | 0.00 | 0.00 | 0.435746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.878720E+09 | 0.00 | 0.00 | 0.00 | 0.310280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.849847E+09 | 0.00 | 0.00 | 0.00 | 0.153530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.873735E+09 | 0.00 | 0.00 | 0.00 | 0.268385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109768E+11 | 0.00 | 0.00 | 0.00 | 0.366715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.795599E+09 | 0.00 | 0.00 | 0.00 | 85391568.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.102766E+10 | 0.00 | 0.00 | 0.00 | 0.550979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.329735E+10 | 0.00 | 0.00 | 2961630.95 | 0.00 | 0.247910E+09 | 0.168049E+10 | 0.00 | 0.37 |
February | 0.108539E+10 | 96140251.77 | 0.00 | 6529213.68 | 0.00 | 24175123.56 | 0.148371E+10 | 0.00 | 0.37 |
March | 0.170993E+09 | 0.178379E+10 | 0.00 | 4507927.20 | 2410352.42 | 0.00 | 0.435620E+09 | 0.00 | 0.37 |
April | 1734993.33 | 0.549154E+10 | 0.00 | 303115.46 | 44052806.64 | 0.00 | 13873605.13 | 0.00 | 0.37 |
May | 0.00 | 0.108355E+11 | 0.00 | 11477.28 | 78636422.14 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.138922E+11 | 0.00 | 0.00 | 92183312.00 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.169137E+11 | 0.00 | 0.00 | 91167607.89 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.168796E+11 | 0.00 | 0.00 | 99742420.33 | 0.00 | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.129406E+11 | 0.00 | 0.00 | 0.111972E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
October | 14611789.08 | 0.502105E+10 | 0.00 | 570229.68 | 35970693.54 | 0.00 | 38202096.50 | 0.00 | 0.37 |
November | 0.261116E+09 | 0.880786E+09 | 0.00 | 6745552.82 | 0.00 | 0.00 | 0.109410E+10 | 0.00 | 0.37 |
December | 0.206076E+10 | 2954762.03 | 0.00 | 6332411.93 | 0.00 | 21639932.21 | 0.263475E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.689195E+10 | 0.847380E+11 | 0.00 | 27961559.01 | 0.556135E+09 | 0.293725E+09 | 0.738074E+10 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.329735E+10 | 0.169137E+11 | 0.00 | 6745552.82 | 0.111972E+09 | 0.247910E+09 | 0.263475E+10 | 0.00 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.898691E+09 | 0.00 | 0.00 | 2458453.38 | 0.00 | 65233795.65 | 0.861826E+09 | 0.00 | 0.28 |
February | 0.337314E+09 | 52954169.92 | 0.00 | 3975827.42 | 0.00 | 0.00 | 0.458910E+09 | 0.00 | 0.29 |
March | 55300675.08 | 0.848827E+09 | 0.00 | 2317845.28 | 3074098.75 | 0.00 | 0.104721E+09 | 0.00 | 0.30 |
April | 557949.02 | 0.241694E+10 | 0.00 | 209063.83 | 26928112.66 | 0.00 | 3152115.40 | 0.00 | 0.31 |
May | 0.00 | 0.481431E+10 | 0.00 | 0.00 | 39748305.65 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.620542E+10 | 0.00 | 0.00 | 41512251.06 | 0.00 | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.758827E+10 | 0.00 | 0.00 | 49917108.58 | 0.00 | 0.00 | 0.00 | 0.34 |
August | 0.00 | 0.755677E+10 | 0.00 | 0.00 | 53317344.05 | 0.00 | 0.00 | 0.00 | 0.34 |
September | 0.00 | 0.568437E+10 | 0.00 | 0.00 | 66933654.52 | 0.00 | 0.00 | 0.00 | 0.33 |
October | 1008287.37 | 0.226599E+10 | 0.00 | 90738.91 | 28567377.85 | 0.00 | 2410642.26 | 0.00 | 0.31 |
November | 70214462.96 | 0.458315E+09 | 0.00 | 3504710.69 | 530662.09 | 0.00 | 0.243766E+09 | 0.00 | 0.30 |
December | 0.602902E+09 | 1799512.19 | 0.00 | 4216701.15 | 0.00 | 0.00 | 0.895122E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.196599E+10 | 0.378940E+11 | 0.00 | 16773340.66 | 0.310529E+09 | 65233795.65 | 0.256991E+10 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.898691E+09 | 0.758827E+10 | 0.00 | 4216701.15 | 66933654.52 | 65233795.65 | 0.895122E+09 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108671E+10 | 2777.29 | 0.00 | 1253385.89 | 0.00 | 79669129.43 | 0.536679E+09 | 0.00 | 0.28 |
February | 0.480603E+09 | 52557614.24 | 0.00 | 2269513.54 | 250933.58 | 0.00 | 0.331247E+09 | 0.00 | 0.28 |
March | 98641983.94 | 0.709402E+09 | 0.00 | 1405635.78 | 35440896.25 | 0.00 | 0.121303E+09 | 0.00 | 0.29 |
April | 777534.79 | 0.200376E+10 | 0.00 | 129313.09 | 0.130389E+09 | 0.00 | 3049276.87 | 0.00 | 0.28 |
May | 272.06 | 0.388409E+10 | 0.00 | 45117.45 | 0.258866E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.482822E+10 | 0.00 | 0.00 | 0.338211E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
July | 0.00 | 0.569610E+10 | 0.00 | 0.00 | 0.385797E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.581913E+10 | 0.00 | 0.00 | 0.396337E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
September | 0.00 | 0.433542E+10 | 0.00 | 0.00 | 0.312487E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 7223015.54 | 0.182123E+10 | 0.00 | 438464.40 | 0.111139E+09 | 0.00 | 29184881.09 | 0.00 | 0.28 |
November | 0.173523E+09 | 0.412618E+09 | 0.00 | 1801541.65 | 7503411.78 | 0.00 | 0.222601E+09 | 0.00 | 0.28 |
December | 0.820797E+09 | 1978858.05 | 0.00 | 2516170.81 | 0.00 | 0.00 | 0.623640E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.266827E+10 | 0.295645E+11 | 0.00 | 9859142.61 | 0.197642E+10 | 79669129.43 | 0.186770E+10 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 2777.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.108671E+10 | 0.581913E+10 | 0.00 | 2516170.81 | 0.396337E+09 | 79669129.43 | 0.623640E+09 | 0.00 | 0.29 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110693E+10 | 806.19 | 0.00 | 1111554.68 | 0.00 | 92849651.42 | 0.491679E+09 | 0.00 | 0.28 |
February | 0.484554E+09 | 51763995.51 | 0.00 | 2190605.98 | 249050.10 | 0.00 | 0.326925E+09 | 0.00 | 0.28 |
March | 0.100098E+09 | 0.708402E+09 | 0.00 | 1410380.42 | 35364970.07 | 0.00 | 0.119949E+09 | 0.00 | 0.29 |
April | 783224.53 | 0.200512E+10 | 0.00 | 134780.10 | 0.129880E+09 | 0.00 | 3015814.28 | 0.00 | 0.28 |
May | 1201.78 | 0.389181E+10 | 0.00 | 47128.16 | 0.256908E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.484041E+10 | 0.00 | 0.00 | 0.335005E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
July | 0.00 | 0.571196E+10 | 0.00 | 0.00 | 0.385440E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.583394E+10 | 0.00 | 0.00 | 0.395161E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
September | 0.00 | 0.434668E+10 | 0.00 | 0.00 | 0.311549E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 6836068.85 | 0.182385E+10 | 0.00 | 448858.91 | 0.111221E+09 | 0.00 | 29323599.44 | 0.00 | 0.28 |
November | 0.178116E+09 | 0.411413E+09 | 0.00 | 1787917.06 | 7471659.13 | 0.00 | 0.218592E+09 | 0.00 | 0.28 |
December | 0.830165E+09 | 1893715.23 | 0.00 | 2384029.15 | 0.00 | 0.00 | 0.613756E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.270748E+10 | 0.296273E+11 | 0.00 | 9515254.46 | 0.196825E+10 | 92849651.42 | 0.180324E+10 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 806.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.110693E+10 | 0.583394E+10 | 0.00 | 2384029.15 | 0.395161E+09 | 92849651.42 | 0.613756E+09 | 0.00 | 0.29 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112887E+10 | 0.00 | 0.00 | 867376.25 | 0.00 | 0.138861E+09 | 0.404819E+09 | 0.00 | 0.28 |
February | 0.498971E+09 | 50162975.48 | 0.00 | 1980073.77 | 240925.56 | 0.00 | 0.312301E+09 | 0.00 | 0.28 |
March | 0.110313E+09 | 0.701031E+09 | 0.00 | 1317353.13 | 36133512.48 | 0.00 | 0.111739E+09 | 0.00 | 0.29 |
April | 780607.61 | 0.200096E+10 | 0.00 | 127215.21 | 0.130500E+09 | 0.00 | 3061403.95 | 0.00 | 0.28 |
May | 99.39 | 0.388344E+10 | 0.00 | 44955.81 | 0.258860E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.482776E+10 | 0.00 | 0.00 | 0.337353E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
July | 0.00 | 0.569797E+10 | 0.00 | 0.00 | 0.385559E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.581440E+10 | 0.00 | 0.00 | 0.395406E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
September | 0.00 | 0.432683E+10 | 0.00 | 0.00 | 0.312552E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 7335305.13 | 0.181453E+10 | 0.00 | 423257.57 | 0.110760E+09 | 0.00 | 30139921.65 | 0.00 | 0.28 |
November | 0.193211E+09 | 0.406623E+09 | 0.00 | 1681012.51 | 7469139.58 | 0.00 | 0.206705E+09 | 0.00 | 0.28 |
December | 0.845750E+09 | 1777304.59 | 0.00 | 2084402.12 | 0.00 | 7327310.25 | 0.590023E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.278523E+10 | 0.295255E+11 | 0.00 | 8525646.37 | 0.197483E+10 | 0.146189E+09 | 0.165879E+10 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.112887E+10 | 0.581440E+10 | 0.00 | 2084402.12 | 0.395406E+09 | 0.138861E+09 | 0.590023E+09 | 0.00 | 0.29 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.224334E+10 | 0.00 | 0.00 | 1346102.45 | 0.00 | 0.354103E+09 | 0.825837E+09 | 0.00 | 0.29 |
February | 0.825128E+09 | 70151298.24 | 0.00 | 4012508.37 | 135806.85 | 24488201.30 | 0.789534E+09 | 0.00 | 0.29 |
March | 0.147187E+09 | 0.149652E+10 | 0.00 | 3048977.30 | 26530304.79 | 0.00 | 0.227791E+09 | 0.00 | 0.30 |
April | 1304728.74 | 0.437466E+10 | 0.00 | 137223.06 | 0.122735E+09 | 0.00 | 2922152.84 | 0.00 | 0.30 |
May | 0.00 | 0.853731E+10 | 0.00 | 8127.22 | 0.183221E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
June | 0.00 | 0.106204E+11 | 0.00 | 0.00 | 0.207497E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
July | 0.00 | 0.123583E+11 | 0.00 | 0.00 | 0.310783E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
August | 0.00 | 0.128459E+11 | 0.00 | 0.00 | 0.255086E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.945378E+10 | 0.00 | 3437.96 | 0.268711E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
October | 10527930.36 | 0.397505E+10 | 0.00 | 428123.81 | 0.102633E+09 | 0.00 | 23789887.04 | 0.00 | 0.30 |
November | 0.218320E+09 | 0.799736E+09 | 0.00 | 3227869.35 | 10803615.07 | 0.00 | 0.441136E+09 | 0.00 | 0.29 |
December | 0.162435E+10 | 625974.66 | 0.00 | 3449085.73 | 0.00 | 12793839.87 | 0.140686E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.507016E+10 | 0.645323E+11 | 0.00 | 15661455.24 | 0.148814E+10 | 0.391385E+09 | 0.371787E+10 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.224334E+10 | 0.128459E+11 | 0.00 | 4012508.37 | 0.310783E+09 | 0.354103E+09 | 0.140686E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.113585E+10 | 0.00 | 0.00 | 570615.89 | 0.00 | 0.190195E+09 | 0.356514E+09 | 0.00 | 0.29 |
February | 0.423778E+09 | 35583713.99 | 0.00 | 1941514.12 | 68018.67 | 12846123.12 | 0.374198E+09 | 0.00 | 0.29 |
March | 74745616.86 | 0.747102E+09 | 0.00 | 1516698.25 | 13374563.34 | 0.00 | 0.110851E+09 | 0.00 | 0.30 |
April | 690927.73 | 0.218785E+10 | 0.00 | 68839.72 | 63102979.76 | 0.00 | 1396808.50 | 0.00 | 0.30 |
May | 0.00 | 0.426829E+10 | 0.00 | 3479.88 | 85198048.52 | 0.00 | 0.00 | 0.00 | 0.30 |
June | 0.00 | 0.530050E+10 | 0.00 | 0.00 | 94938509.21 | 0.00 | 0.00 | 0.00 | 0.31 |
July | 0.00 | 0.614996E+10 | 0.00 | 0.00 | 0.150698E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
August | 0.00 | 0.638397E+10 | 0.00 | 0.00 | 0.124421E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.469967E+10 | 0.00 | 6998.25 | 0.130802E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
October | 5190940.35 | 0.197708E+10 | 0.00 | 213026.07 | 50891503.24 | 0.00 | 12447719.72 | 0.00 | 0.30 |
November | 0.110044E+09 | 0.398804E+09 | 0.00 | 1617603.76 | 5279899.71 | 0.00 | 0.218382E+09 | 0.00 | 0.29 |
December | 0.847326E+09 | 337803.44 | 0.00 | 1615187.75 | 0.00 | 7399133.41 | 0.651447E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.259763E+10 | 0.321491E+11 | 0.00 | 7553963.69 | 0.718774E+09 | 0.210440E+09 | 0.172524E+10 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.113585E+10 | 0.638397E+10 | 0.00 | 1941514.12 | 0.150698E+09 | 0.190195E+09 | 0.651447E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114089E+10 | 0.00 | 0.00 | 523761.82 | 0.00 | 0.207553E+09 | 0.326345E+09 | 0.00 | 0.29 |
February | 0.425271E+09 | 35211993.01 | 0.00 | 1877746.47 | 68498.36 | 18977751.88 | 0.366263E+09 | 0.00 | 0.29 |
March | 76434788.09 | 0.744321E+09 | 0.00 | 1487174.08 | 13576525.75 | 0.00 | 0.109869E+09 | 0.00 | 0.30 |
April | 689964.46 | 0.218622E+10 | 0.00 | 68920.31 | 63097738.81 | 0.00 | 1409152.30 | 0.00 | 0.30 |
May | 0.00 | 0.426552E+10 | 0.00 | 3410.54 | 85393100.47 | 0.00 | 0.00 | 0.00 | 0.30 |
June | 0.00 | 0.529663E+10 | 0.00 | 0.00 | 95126438.63 | 0.00 | 0.00 | 0.00 | 0.31 |
July | 0.00 | 0.614491E+10 | 0.00 | 0.00 | 0.151437E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
August | 0.00 | 0.637887E+10 | 0.00 | 0.00 | 0.124320E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.469479E+10 | 0.00 | 7065.02 | 0.130676E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
October | 5363262.08 | 0.197340E+10 | 0.00 | 209213.61 | 51236813.95 | 0.00 | 12484118.37 | 0.00 | 0.30 |
November | 0.113925E+09 | 0.396937E+09 | 0.00 | 1586963.60 | 5283802.88 | 0.00 | 0.215746E+09 | 0.00 | 0.29 |
December | 0.872079E+09 | 319853.93 | 0.00 | 1533514.56 | 0.00 | 12241572.49 | 0.619534E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.263465E+10 | 0.321171E+11 | 0.00 | 7297770.01 | 0.720216E+09 | 0.238772E+09 | 0.165165E+10 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.114089E+10 | 0.637887E+10 | 0.00 | 1877746.47 | 0.151437E+09 | 0.207553E+09 | 0.619534E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114547E+10 | 0.00 | 0.00 | 430669.03 | 0.00 | 0.233832E+09 | 0.276646E+09 | 0.00 | 0.29 |
February | 0.424185E+09 | 34321859.42 | 0.00 | 1725922.22 | 69441.96 | 33940590.68 | 0.349366E+09 | 0.00 | 0.29 |
March | 80164955.99 | 0.737787E+09 | 0.00 | 1421862.93 | 14186139.56 | 0.00 | 0.107250E+09 | 0.00 | 0.30 |
April | 689247.57 | 0.218494E+10 | 0.00 | 66803.56 | 63319816.53 | 0.00 | 1463550.58 | 0.00 | 0.30 |
May | 0.00 | 0.426944E+10 | 0.00 | 3320.98 | 85724147.18 | 0.00 | 0.00 | 0.00 | 0.30 |
June | 0.00 | 0.530643E+10 | 0.00 | 0.00 | 94330204.42 | 0.00 | 0.00 | 0.00 | 0.31 |
July | 0.00 | 0.616539E+10 | 0.00 | 0.00 | 0.149283E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
August | 0.00 | 0.640226E+10 | 0.00 | 0.00 | 0.121791E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.470729E+10 | 0.00 | 7378.60 | 0.130183E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
October | 5548863.98 | 0.197401E+10 | 0.00 | 201084.95 | 50724378.67 | 0.00 | 12659678.86 | 0.00 | 0.30 |
November | 0.119924E+09 | 0.392939E+09 | 0.00 | 1496634.81 | 5291552.98 | 0.00 | 0.211705E+09 | 0.00 | 0.29 |
December | 0.918712E+09 | 278286.35 | 0.00 | 1333666.41 | 0.00 | 32501433.74 | 0.543499E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.269470E+10 | 0.321751E+11 | 0.00 | 6687343.48 | 0.714904E+09 | 0.300274E+09 | 0.150259E+10 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.114547E+10 | 0.640226E+10 | 0.00 | 1725922.22 | 0.149283E+09 | 0.233832E+09 | 0.543499E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105943E+10 | 0.00 | 0.00 | 468767.48 | 0.00 | 0.303033E+09 | 0.283872E+09 | 0.00 | 0.29 |
February | 0.379282E+09 | 34366525.71 | 0.00 | 1865184.00 | 62861.24 | 60530949.20 | 0.346642E+09 | 0.00 | 0.29 |
March | 78561002.09 | 0.735903E+09 | 0.00 | 1549569.02 | 14909736.62 | 0.00 | 0.105725E+09 | 0.00 | 0.30 |
April | 917666.68 | 0.219917E+10 | 0.00 | 78250.12 | 56987934.18 | 0.00 | 1504387.16 | 0.00 | 0.30 |
May | 0.00 | 0.432499E+10 | 0.00 | 6939.07 | 74800747.27 | 0.00 | 0.00 | 0.00 | 0.30 |
June | 0.00 | 0.540996E+10 | 0.00 | 12740.14 | 86181397.32 | 0.00 | 0.00 | 0.00 | 0.31 |
July | 0.00 | 0.634479E+10 | 0.00 | 0.00 | 0.130643E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
August | 0.00 | 0.664008E+10 | 0.00 | 0.00 | 0.101975E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.488219E+10 | 0.00 | 19596.79 | 0.123757E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
October | 6542401.69 | 0.202953E+10 | 0.00 | 194142.53 | 48099762.03 | 0.00 | 11120897.79 | 0.00 | 0.30 |
November | 0.123183E+09 | 0.398455E+09 | 0.00 | 1671311.18 | 5045339.21 | 0.00 | 0.201013E+09 | 0.00 | 0.29 |
December | 0.851666E+09 | 270328.61 | 0.00 | 1434107.42 | 0.00 | 95593977.45 | 0.516186E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.249958E+10 | 0.329997E+11 | 0.00 | 7300607.75 | 0.642462E+09 | 0.459158E+09 | 0.146606E+10 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.105943E+10 | 0.664008E+10 | 0.00 | 1865184.00 | 0.130643E+09 | 0.303033E+09 | 0.516186E+09 | 0.00 | 0.31 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.148340E+12 | 0.150233E+11 | 0.00 | 0.475883E+11 | 0.937338E+10 |
February | 0.174456E+12 | 0.575882E+10 | 0.00 | 0.260904E+11 | 0.390601E+11 |
March | 0.246063E+12 | -0.793269E+10 | 0.00 | -0.154301E+10 | 0.106977E+12 |
April | 0.284108E+12 | -0.233571E+11 | 0.00 | -0.370998E+11 | 0.177859E+12 |
May | 0.307285E+12 | -0.429097E+11 | 0.00 | -0.751528E+11 | 0.261940E+12 |
June | 0.286936E+12 | -0.508129E+11 | 0.00 | -0.992428E+11 | 0.290637E+12 |
July | 0.235222E+12 | -0.623477E+11 | 0.00 | -0.117385E+12 | 0.315255E+12 |
August | 0.200084E+12 | -0.630888E+11 | 0.00 | -0.117121E+12 | 0.313676E+12 |
September | 0.209133E+12 | -0.479290E+11 | 0.00 | -0.890235E+11 | 0.255454E+12 |
October | 0.202180E+12 | -0.218807E+11 | 0.00 | -0.300054E+11 | 0.173301E+12 |
November | 0.167453E+12 | -0.405154E+10 | 0.00 | 0.130667E+11 | 0.910344E+11 |
December | 0.132290E+12 | 0.127646E+11 | 0.00 | 0.453914E+11 | 0.218924E+11 |
Annual Sum or Average | 0.259355E+13 | -0.290763E+12 | 0.00 | -0.434437E+12 | 0.205646E+13 |
Minimum of Months | 0.132290E+12 | -0.630888E+11 | 0.00 | -0.117385E+12 | 0.937338E+10 |
Maximum of Months | 0.307285E+12 | 0.150233E+11 | 0.00 | 0.475883E+11 | 0.315255E+12 |