Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:39
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:39:21
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 798.44 | 381.97 | 381.97 |
Net Site Energy | 718.97 | 343.95 | 343.95 |
Total Source Energy | 2448.54 | 1171.37 | 1171.37 |
Net Source Energy | 2196.87 | 1050.97 | 1050.97 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 38.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 149.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 102.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 61.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 759.97 | 38.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 38.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 149.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 40.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 102.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 61.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 38.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 149.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 40.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 102.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 61.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 152.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 149.77 | 18.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 363.57 | 18.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 152.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 149.77 | 18.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 363.57 | 18.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 82.877 | 10.91 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -3.41 | -0.4 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 79.467 | 10.46 |
Electricity Coming From Utility | 680.532 | 89.55 |
Surplus Electricity Going To Utility | 0.024 | 0.00 |
Net Electricity From Utility | 680.508 | 89.54 |
Total On-Site and Utility Electric Sources | 759.975 | 100.00 |
Total Electricity End Uses | 759.975 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 828.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:39 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 11.5884 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 13.7658 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 7.5320 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 10.0873 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 10.0873 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 11.5884 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 13.7658 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 12.9393 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 12.9393 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 12.9393 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 7.5320 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 7.5557 | 6.19 | 4.3000 | |
Total | 2090.32 | 10.0873 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 10.0873 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 10.0873 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-JUL-16:49 | 27-DEC-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 106819.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 35423.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6557.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5424.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 73161.98 | 106819.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 106819.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 35423.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6557.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5424.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 41.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 472.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 879.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 129.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 324.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 194.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2406.84 | 41.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 19.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 225.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 420.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 93.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1151.42 | 19.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 19.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 225.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 420.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 93.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1151.42 | 19.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.22 |
SMSTORE1 DIRECT AIR | 1.15 |
SMSTORE2 DIRECT AIR | 1.16 |
SMSTORE3 DIRECT AIR | 1.17 |
SMSTORE4 DIRECT AIR | 1.16 |
LGSTORE2 DIRECT AIR | 2.08 |
SMSTORE5 DIRECT AIR | 1.08 |
SMSTORE6 DIRECT AIR | 1.08 |
SMSTORE7 DIRECT AIR | 1.08 |
SMSTORE8 DIRECT AIR | 1.23 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.22 | 2.22 | 2.22 | 2.22 | 2.22 | 2.22 | 1.00 | 1.00 | 2.22 |
PSZ-AC_2:2 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.00 | 1.00 | 1.15 |
PSZ-AC_3:3 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.00 | 1.00 | 1.16 |
PSZ-AC_4:4 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.00 | 1.00 | 1.17 |
PSZ-AC_5:5 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.00 | 1.00 | 1.16 |
PSZ-AC_6:6 | 2.08 | 2.08 | 2.08 | 2.08 | 2.08 | 2.08 | 1.00 | 1.00 | 2.08 |
PSZ-AC_7:7 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.000000 | 1.08 |
PSZ-AC_8:8 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.00 | 1.08 |
PSZ-AC_9:9 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.00 | 1.08 |
PSZ-AC_10:10 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.00 | 1.00 | 1.23 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.22 |
PSZ-AC_2:2_OA_CONTROLLER | 1.15 |
PSZ-AC_3:3_OA_CONTROLLER | 1.16 |
PSZ-AC_4:4_OA_CONTROLLER | 1.17 |
PSZ-AC_5:5_OA_CONTROLLER | 1.16 |
PSZ-AC_6:6_OA_CONTROLLER | 2.08 |
PSZ-AC_7:7_OA_CONTROLLER | 1.08 |
PSZ-AC_8:8_OA_CONTROLLER | 1.08 |
PSZ-AC_9:9_OA_CONTROLLER | 1.08 |
PSZ-AC_10:10_OA_CONTROLLER | 1.23 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.22 | 2378.18 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.15 | 1270.64 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.16 | 1286.90 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.17 | 1292.45 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.16 | 1282.91 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.08 | 2226.35 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.08 | 1197.87 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.08 | 1191.87 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.08 | 1193.21 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.23 | 1365.84 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.22 | 2.22 | 2.22 | 1.47 | 42527.35 | 55422.80 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 0.757453 | 21842.89 | 28433.04 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 0.767146 | 22079.98 | 28724.20 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.17 | 1.17 | 1.17 | 0.770455 | 22160.83 | 28823.61 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 0.764771 | 22022.41 | 28652.85 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.08 | 2.08 | 2.08 | 1.37 | 40263.20 | 52609.30 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 0.714073 | 20787.06 | 27129.94 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 0.710499 | 20699.73 | 27022.58 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 0.711297 | 20719.63 | 27046.53 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.23 | 1.23 | 1.23 | 0.814203 | 22938.64 | 30138.17 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.22 | 1.11 | 1.48 | 42527.35 | 21263.67 | 0.794060 | 0.794060 |
PSZ-AC_2:2 COOLING COIL | 1.15 | 0.573828 | 0.765107 | 21842.89 | 10921.44 | 0.796770 | 0.796770 |
PSZ-AC_3:3 COOLING COIL | 1.16 | 0.581171 | 0.774893 | 22079.98 | 11039.99 | 0.797380 | 0.797380 |
PSZ-AC_4:4 COOLING COIL | 1.17 | 0.583678 | 0.778240 | 22160.83 | 11080.42 | 0.797590 | 0.797590 |
PSZ-AC_5:5 COOLING COIL | 1.16 | 0.579372 | 0.772493 | 22022.41 | 11011.20 | 0.797220 | 0.797220 |
PSZ-AC_6:6 COOLING COIL | 2.08 | 1.04 | 1.39 | 40263.20 | 20131.60 | 0.789500 | 0.789500 |
PSZ-AC_7:7 COOLING COIL | 1.08 | 0.540965 | 0.721287 | 20787.06 | 10393.53 | 0.792770 | 0.792770 |
PSZ-AC_8:8 COOLING COIL | 1.08 | 0.538257 | 0.717673 | 20699.73 | 10349.86 | 0.792510 | 0.792510 |
PSZ-AC_9:9 COOLING COIL | 1.08 | 0.538861 | 0.718480 | 20719.63 | 10359.82 | 0.792560 | 0.792560 |
PSZ-AC_10:10 COOLING COIL | 1.23 | 0.616820 | 0.822427 | 22938.64 | 11469.32 | 0.800310 | 0.800310 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 55422.80 |
PSZ-AC_2:2 HEATING COIL | 28433.04 |
PSZ-AC_3:3 HEATING COIL | 28724.20 |
PSZ-AC_4:4 HEATING COIL | 28823.61 |
PSZ-AC_5:5 HEATING COIL | 28652.85 |
PSZ-AC_6:6 HEATING COIL | 52609.30 |
PSZ-AC_7:7 HEATING COIL | 27129.94 |
PSZ-AC_8:8 HEATING COIL | 27022.58 |
PSZ-AC_9:9 HEATING COIL | 27046.53 |
PSZ-AC_10:10 HEATING COIL | 30138.17 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 11.588 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.888 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 13.766 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 18.066 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 7.532 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.832 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 2630.745 | 7.551 | 46.768 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2630.745 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1406.513 | 4.037 | 25.004 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1406.513 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1319.493 | 7.575 | 46.916 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1319.493 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1078.411 | 6.191 | 38.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1078.411 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 2624.046 | 7.532 | 46.649 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2624.046 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6887 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.218 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.33074266E-12 | 0.10604805E-14 | -0.10376772E-12 | 0.10050050E-15 |
23 | 6 | 0.29711555E-07 | 0.19576406E-09 | 0.67975929E-08 | -0.14079383E-12 |
24 | 5 | -0.19537397E-03 | 0.16642354E-05 | -0.10041974E-03 | 0.67165186E-08 |
25 | 4 | 0.29828781 | 0.80514357E-03 | 0.10189302 | -0.34439683E-04 |
26 | 3 | -7.3878975 | 0.24810408E-01 | -2.3749899 | 0.29604922E-01 |
27 | 2 | 41.272027 | 0.87780140E-01 | 15.412956 | -0.33780550 |
28 | 1 | -80.852930 | 0.39442104E-01 | -29.274215 | 1.0851646 |
29 | 0 | 46.824337 | 0.79011109E-03 | 16.288086 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 35 | 1 | VerySmooth | 1.408 | 1.408 | 1.000 | 0.210 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 4.57814E-002 | 0.12126 | 0.67915 | 0.67915 | 0.29000 | 0.15345 | 0.21878 | 0.00000 | 0.84000 | 0.84000 | 8.56546E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 21829.10343 | 26194.92412 | 1.85208 | 2.22250 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10000 | 6.87148E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 18064.74023 | 21677.68827 | 0.89790 | 1.07748 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11272.20554 | 13526.64665 | 0.95638 | 1.14766 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 8456.01373 | 10147.21648 | 0.42030 | 0.50436 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11416.45114 | 13699.74136 | 0.96862 | 1.16234 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 8557.90495 | 10269.48594 | 0.42537 | 0.51044 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11465.68230 | 13758.81876 | 0.97280 | 1.16736 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 8652.99585 | 10383.59502 | 0.43009 | 0.51611 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11381.08406 | 13657.30088 | 0.96562 | 1.15874 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 8826.69477 | 10592.03373 | 0.43873 | 0.52647 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 20435.35754 | 24522.42905 | 1.73384 | 2.08061 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 17172.26573 | 20606.71888 | 0.85355 | 1.02426 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 10626.61262 | 12751.93514 | 0.90161 | 1.08193 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 9127.49512 | 10952.99414 | 0.45368 | 0.54442 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 10573.42586 | 12688.11103 | 0.89710 | 1.07651 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 9129.01680 | 10954.82016 | 0.45376 | 0.54451 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 10585.29186 | 12702.35023 | 0.89810 | 1.07772 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 9412.77865 | 11295.33438 | 0.46786 | 0.56143 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 12116.52979 | 14539.83574 | 1.02803 | 1.23364 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 37.45000 | 6.87043E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 11478.21951 | 13773.86341 | 0.57051 | 0.68461 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 31997.42 | 2.22250 | 2.22250 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 32721.81 | 1.07748 | 1.07748 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16422.18 | 1.14766 | 1.14766 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 15679.29 | 0.50436 | 0.50436 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16588.92 | 1.16234 | 1.16234 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 15799.78 | 0.51044 | 0.51044 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16646.12 | 1.16736 | 1.16736 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 15912.22 | 0.51611 | 0.51611 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 16546.10 | 1.15874 | 1.15874 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 16117.63 | 0.52647 | 0.52647 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 30334.60 | 2.08061 | 2.08061 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 31666.54 | 1.02426 | 1.02426 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 15648.79 | 1.08193 | 1.08193 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 16473.33 | 0.54442 | 0.54442 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 15585.83 | 1.07651 | 1.07651 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 16475.13 | 0.54451 | 0.54451 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 15598.34 | 1.07772 | 1.07772 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 16810.69 | 0.56143 | 0.56143 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 17282.92 | 1.23364 | 1.23364 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 19253.02 | 0.68461 | 0.68461 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.22250 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14766 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16234 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16736 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.15874 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.08061 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08193 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07651 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07772 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.23364 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.22250 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.22250 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.22250 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.22250 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.22250 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.22250 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14766 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14766 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14766 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14766 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14766 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14766 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.16234 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.16234 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.16234 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16234 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.16234 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.16234 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.16736 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.16736 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.16736 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16736 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.16736 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.16736 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.15874 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.15874 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.15874 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.15874 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.15874 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.15874 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.08061 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.08061 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.08061 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.08061 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.08061 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.08061 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.08193 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08193 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.08193 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.08193 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.08193 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.08193 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07651 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07651 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07651 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07651 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07651 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.07651 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07772 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07772 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07772 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07772 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07772 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.07772 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.23364 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.23364 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.23364 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.23364 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.23364 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.23364 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.22250 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.14766 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.16234 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.16736 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.15874 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.08061 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.08193 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.07651 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.07772 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.23364 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.22250 |
102 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.22250 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2378.18139 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.22250 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.22250 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.22250 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.46685 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.22250 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.11125 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.48167 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 42527.35000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21263.67500 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79406 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79406 |
115 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 42527.35000 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 55422.79872 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
119 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 55422.79872 |
120 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14766 |
121 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14766 |
122 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1270.63814 |
123 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14766 |
124 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14766 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14766 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75745 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14766 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57383 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76511 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21842.89000 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10921.44500 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79677 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79677 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21842.89000 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28433.04094 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
138 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 28433.04094 |
139 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.16234 |
140 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.16234 |
141 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1286.89759 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.16234 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16234 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16234 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76715 |
146 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.16234 |
147 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58117 |
148 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77489 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22079.98000 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11039.99000 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79738 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79738 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22079.98000 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28724.19855 |
155 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
157 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 28724.19855 |
158 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.16736 |
159 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.16736 |
160 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1292.44928 |
161 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.16736 |
162 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16736 |
163 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16736 |
164 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77046 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.16736 |
166 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58368 |
167 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77824 |
168 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22160.83000 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11080.41500 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79759 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79759 |
172 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22160.83000 |
173 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28823.61289 |
174 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
176 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 28823.61289 |
177 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.15874 |
178 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.15874 |
179 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1282.91309 |
180 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.15874 |
181 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.15874 |
182 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.15874 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76477 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.15874 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57937 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77249 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22022.41000 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11011.20500 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79722 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79722 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22022.41000 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28652.84595 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
194 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
195 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 28652.84595 |
196 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.08061 |
197 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.08061 |
198 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2226.35102 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.08061 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.08061 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.08061 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.37320 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.08061 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.04030 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.38707 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40263.20000 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20131.60000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78950 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78950 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40263.20000 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 52609.29967 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
213 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
214 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 52609.29967 |
215 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.08193 |
216 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.08193 |
217 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1197.86750 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.08193 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.08193 |
220 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.08193 |
221 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71407 |
222 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.08193 |
223 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54096 |
224 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.72129 |
225 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20787.06000 |
226 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10393.53000 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79277 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79277 |
229 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20787.06000 |
230 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27129.93819 |
231 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
232 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
233 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 27129.93819 |
234 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07651 |
235 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07651 |
236 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1191.87221 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07651 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07651 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07651 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71050 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07651 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53826 |
243 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71767 |
244 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20699.73000 |
245 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10349.86500 |
246 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79251 |
247 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79251 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20699.73000 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27022.58039 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
251 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
252 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 27022.58039 |
253 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07772 |
254 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07772 |
255 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1193.20961 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07772 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07772 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07772 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71130 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07772 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53886 |
262 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71848 |
263 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20719.63000 |
264 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10359.81500 |
265 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79256 |
266 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79256 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20719.63000 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27046.52981 |
269 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
270 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
271 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 27046.52981 |
272 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.23364 |
273 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.23364 |
274 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1365.83585 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.23364 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.23364 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.23364 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.81420 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.23364 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61682 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.82243 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22938.64000 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11469.32000 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80031 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80031 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22938.64000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30138.17394 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 30138.17394 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 40782.0 | 11.73 | 11.73 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 20941.7 | 11.89 | 11.89 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 21167.3 | 11.88 | 11.88 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 21244.2 | 11.88 | 11.88 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 21112.5 | 11.88 | 11.88 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 38628.9 | 11.76 | 11.76 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 19937.3 | 11.91 | 11.91 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 19854.3 | 11.91 | 11.91 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 19873.2 | 11.91 | 11.91 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 21970.2 | 11.83 | 11.83 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 5.7278590311E-002 | 4.9702902651E-002 | Pass | Pass | 3.5306332606E-002 | 0.1064845099 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.0263176959E-002 | 6.1391062922E-002 | Pass | Pass | 9.0476651575E-002 | 0.3548681616 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.1118514283E-002 | 5.7068889658E-002 | Pass | Pass | 2.7074436089E-002 | 0.1015256690 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.2148532076E-002 | 5.5960693180E-002 | Pass | Pass | 2.5390747834E-002 | 9.4188773813E-002 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 5.0075178741E-002 | 5.8983912430E-002 | Pass | Pass | 8.0081076963E-002 | 0.4159916138 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 5.5905873522E-002 | 0.1183587354 | Pass | Pass | 7.8596465100E-002 | 0.3155550301 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 5.5208705413E-002 | 0.1315454301 | Pass | Pass | 7.8418182620E-002 | 0.3798978499 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 5.2857861204E-002 | 0.1389698148 | Pass | Pass | 0.1684840856 | 0.9966426681 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.7460073999E-002 | 0.1408516485 | Pass | Pass | 0.2200932268 | 1.0509404270 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 5.6764041995E-002 | 0.2336717859 | Pass | Pass | 0.1184010087 | 0.4630341201 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3175.82 | 43.70 | 0.00 | 116.12 | 729.05 | 4064.71 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 1.408 | 0.210 | 0.290 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 1.408 | 0.210 | 0.290 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 7.5512 | 348.39 | 2630.74 | LightsWired | LTG_SCH_BASE_LPD1 | 81.37 | 168.00 | 80.49 | 0.0000 | Y | 39.75 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 4.0372 | 348.39 | 1406.51 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 24.96 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 7.5749 | 174.19 | 1319.49 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 82.90 | 168.00 | 81.97 | 0.0000 | Y | 20.30 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 6.1909 | 174.19 | 1078.41 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 19.14 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 7.5320 | 348.39 | 2624.05 | LightsWired | LTG_SCH_BASE_LPD2 | 60.23 | 168.00 | 58.11 | 0.0000 | Y | 28.62 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 5.0436 | 4180.64 | 21085.58 | 277.79 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 437.57 | AstronomicalClock | - | 41.77 | 41.77 | 3.43 | |
EXTERIOR_LIGHTS_B | 1882.64 | AstronomicalClock | - | 83.77 | 62.77 | 22.18 | |
EXTERIOR_LIGHTS_C | 1466.47 | AstronomicalClock | - | 83.77 | 55.77 | 15.35 | |
Exterior Lighting Total | 3786.68 | 40.96 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 42527.35 | 33769.27 | 8758.08 | 0.79 | 3.92 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21842.89 | 17403.76 | 4439.13 | 0.80 | 3.99 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22079.98 | 17606.13 | 4473.85 | 0.80 | 3.99 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22160.83 | 17675.26 | 4485.57 | 0.80 | 3.99 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22022.41 | 17556.71 | 4465.70 | 0.80 | 3.99 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40263.20 | 31787.80 | 8475.40 | 0.79 | 3.92 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20787.06 | 16479.36 | 4307.70 | 0.79 | 3.99 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20699.73 | 16404.74 | 4294.99 | 0.79 | 3.99 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20719.63 | 16421.55 | 4298.08 | 0.79 | 3.99 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22938.64 | 18358.02 | 4580.62 | 0.80 | 3.99 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 40782.0 | 11.73 | 11.73 | ||||
PSZ-AC_2:2 COOLING COIL | 20941.7 | 11.89 | 11.89 | ||||
PSZ-AC_3:3 COOLING COIL | 21167.3 | 11.88 | 11.88 | ||||
PSZ-AC_4:4 COOLING COIL | 21244.2 | 11.88 | 11.88 | ||||
PSZ-AC_5:5 COOLING COIL | 21112.5 | 11.88 | 11.88 | ||||
PSZ-AC_6:6 COOLING COIL | 38628.9 | 11.76 | 11.76 | ||||
PSZ-AC_7:7 COOLING COIL | 19937.3 | 11.91 | 11.91 | ||||
PSZ-AC_8:8 COOLING COIL | 19854.3 | 11.91 | 11.91 | ||||
PSZ-AC_9:9 COOLING COIL | 19873.2 | 11.91 | 11.91 | ||||
PSZ-AC_10:10 COOLING COIL | 21970.2 | 11.83 | 11.83 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 55422.80 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 28433.04 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 28724.20 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 28823.61 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 28652.85 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 52609.30 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 27129.94 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 27022.58 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 27046.53 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 30138.17 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.22 | 2378.18 | 1070.05 | 1.00 | 1.30 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.15 | 1270.64 | 1107.16 | 1.00 | 1.37 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.16 | 1286.90 | 1107.16 | 1.00 | 1.37 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.17 | 1292.45 | 1107.16 | 1.00 | 1.37 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.16 | 1282.91 | 1107.16 | 1.00 | 1.37 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.08 | 2226.35 | 1070.05 | 1.00 | 1.31 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1197.87 | 1107.16 | 1.00 | 1.38 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1191.87 | 1107.16 | 1.00 | 1.38 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1193.21 | 1107.16 | 1.00 | 1.38 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.23 | 1365.84 | 1107.16 | 1.00 | 1.35 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 21829.10 | 26194.92 | 75.19 | 1.852 | 2.223 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.89 | 0.00748 | 38.10 | 0.00687 | 0.411 | 0.00 |
SMSTORE1 | 11272.21 | 13526.65 | 77.65 | 0.956 | 1.148 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00747 | 37.99 | 0.00687 | 0.206 | 0.00 |
SMSTORE2 | 11416.45 | 13699.74 | 78.65 | 0.969 | 1.162 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00746 | 37.99 | 0.00687 | 0.206 | 0.00 |
SMSTORE3 | 11465.68 | 13758.82 | 78.99 | 0.973 | 1.167 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00746 | 37.88 | 0.00687 | 0.206 | 0.00 |
SMSTORE4 | 11381.08 | 13657.30 | 78.40 | 0.966 | 1.159 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00746 | 37.88 | 0.00687 | 0.206 | 0.00 |
LGSTORE2 | 20435.36 | 24522.43 | 70.39 | 1.734 | 2.081 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00752 | 37.88 | 0.00687 | 0.411 | 0.00 |
SMSTORE5 | 10626.61 | 12751.94 | 73.21 | 0.902 | 1.082 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00749 | 37.88 | 0.00687 | 0.206 | 0.00 |
SMSTORE6 | 10573.43 | 12688.11 | 72.84 | 0.897 | 1.077 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00750 | 37.88 | 0.00687 | 0.206 | 0.00 |
SMSTORE7 | 10585.29 | 12702.35 | 72.92 | 0.898 | 1.078 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00749 | 37.88 | 0.00687 | 0.206 | 0.00 |
SMSTORE8 | 12116.53 | 14539.84 | 83.47 | 1.028 | 1.234 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.89 | 0.00743 | 37.45 | 0.00687 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 18064.74 | 21677.69 | 62.22 | 0.898 | 1.077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00687 | -5.20 | 0.00281 | 0.411 | 0.00 |
SMSTORE1 | 8456.01 | 10147.22 | 58.25 | 0.420 | 0.504 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00676 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE2 | 8557.90 | 10269.49 | 58.95 | 0.425 | 0.510 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00677 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE3 | 8653.00 | 10383.60 | 59.61 | 0.430 | 0.516 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00678 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE4 | 8826.69 | 10592.03 | 60.81 | 0.439 | 0.526 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00679 | -5.20 | 0.00281 | 0.206 | 0.00 |
LGSTORE2 | 17172.27 | 20606.72 | 59.15 | 0.854 | 1.024 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00688 | -5.20 | 0.00281 | 0.411 | 0.00 |
SMSTORE5 | 9127.50 | 10952.99 | 62.88 | 0.454 | 0.544 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00682 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE6 | 9129.02 | 10954.82 | 62.89 | 0.454 | 0.545 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00682 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE7 | 9412.78 | 11295.33 | 64.84 | 0.468 | 0.561 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00684 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE8 | 11478.22 | 13773.86 | 79.07 | 0.571 | 0.685 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00691 | -5.20 | 0.00281 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.22 | 2.22 | 1.08 | 1.08 | 2.2225 | 2.2225 | 2.2225 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.15 | 1.15 | 0.50 | 0.50 | 1.1477 | 1.1477 | 1.1477 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.16 | 1.16 | 0.51 | 0.51 | 1.1623 | 1.1623 | 1.1623 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.17 | 1.17 | 0.52 | 0.52 | 1.1674 | 1.1674 | 1.1674 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.16 | 1.16 | 0.53 | 0.53 | 1.1587 | 1.1587 | 1.1587 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.08 | 2.08 | 1.02 | 1.02 | 2.0806 | 2.0806 | 2.0806 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.08 | 1.08 | 0.54 | 0.54 | 1.0819 | 1.0819 | 1.0819 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.08 | 1.08 | 0.54 | 0.54 | 1.0765 | 1.0765 | 1.0765 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.08 | 1.08 | 0.56 | 0.56 | 1.0777 | 1.0777 | 1.0777 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.23 | 1.23 | 0.68 | 0.68 | 1.2336 | 1.2336 | 1.2336 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 42527.350 | 33769.268 | 2.222500 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21263.67 | 20357.49 | 1.481667 | 27.53 | 15.19 | 0.00737068 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 27.7715 | 23.89 | 0.00748410 | 35.2328 | 21829.10 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 55422.799 | 55422.799 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 55422.80 | 55422.80 | 2.222501 | 16.24 | 9.86 | 0.00611476 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 18.5143 | 21.11 | 0.00686599 | 38.3132 | 18064.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 21842.890 | 17403.759 | 1.147660 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 10921.44 | 10466.81 | 0.765107 | 27.48 | 15.17 | 0.00736088 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 26.8900 | 23.89 | 0.00746778 | 35.1567 | 11272.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 28433.041 | 28433.041 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28433.04 | 28433.04 | 1.147657 | 16.39 | 9.86 | 0.00605274 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 17.9267 | 21.11 | 0.00676139 | 37.7357 | 8456.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 22079.980 | 17606.134 | 1.162340 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 11039.99 | 10583.23 | 0.774893 | 27.45 | 15.16 | 0.00735804 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 26.5504 | 23.89 | 0.00746273 | 35.1332 | 11412.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 28724.199 | 28724.199 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28724.20 | 28724.20 | 1.162342 | 16.45 | 9.90 | 0.00606905 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 17.7002 | 21.11 | 0.00677032 | 37.7850 | 8557.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 22160.830 | 17675.256 | 1.167360 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 11080.42 | 10622.95 | 0.778240 | 27.43 | 15.15 | 0.00735708 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 26.4363 | 23.89 | 0.00746102 | 35.1252 | 11461.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 28823.613 | 28823.613 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28823.61 | 28823.61 | 1.167357 | 16.47 | 9.92 | 0.00607880 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 17.6242 | 21.11 | 0.00677850 | 37.8303 | 8653.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 22022.410 | 17556.706 | 1.158740 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 11011.20 | 10554.91 | 0.772493 | 27.45 | 15.16 | 0.00735877 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 26.6329 | 23.89 | 0.00746402 | 35.1392 | 11376.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 28652.846 | 28652.846 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28652.85 | 28652.85 | 1.158744 | 16.44 | 9.91 | 0.00608604 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 17.7552 | 21.11 | 0.00679363 | 37.9138 | 8826.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 40263.200 | 31787.796 | 2.080610 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 20131.60 | 19237.70 | 1.387073 | 27.71 | 15.27 | 0.00739023 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 29.6654 | 23.89 | 0.00751820 | 35.3914 | 20425.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 52609.300 | 52609.300 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 52609.30 | 52609.30 | 2.080610 | 15.90 | 9.68 | 0.00607082 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 19.7769 | 21.11 | 0.00687509 | 38.3629 | 17172.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 20787.060 | 16479.358 | 1.081930 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 10393.53 | 9948.29 | 0.721287 | 27.63 | 15.23 | 0.00737459 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 28.5237 | 23.89 | 0.00749283 | 35.2732 | 10619.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 27129.938 | 27129.938 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 27129.94 | 27129.94 | 1.081929 | 16.11 | 9.75 | 0.00605589 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 19.0158 | 21.11 | 0.00681843 | 38.0507 | 9127.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 20699.730 | 16404.743 | 1.076510 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 10349.86 | 9905.46 | 0.717673 | 27.65 | 15.24 | 0.00737574 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 28.6673 | 23.89 | 0.00749499 | 35.2833 | 10566.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 27022.580 | 27022.580 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 27022.58 | 27022.58 | 1.076514 | 16.08 | 9.73 | 0.00605219 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 19.1115 | 21.11 | 0.00681860 | 38.0517 | 9129.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 20719.630 | 16421.550 | 1.077720 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 10359.82 | 9915.19 | 0.718480 | 27.64 | 15.24 | 0.00737552 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 28.6351 | 23.89 | 0.00749456 | 35.2813 | 10576.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 27046.530 | 27046.530 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 27046.53 | 27046.53 | 1.077722 | 16.09 | 9.75 | 0.00607099 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 19.0900 | 21.11 | 0.00684077 | 38.1741 | 9412.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 22938.640 | 18358.023 | 1.233640 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 11469.32 | 11014.40 | 0.822427 | 27.21 | 15.06 | 0.00733886 | 12.80 | 9.33 | 0.00700000 | 37.56 | 0.00687061 | 18.01 | 25.0159 | 23.89 | 0.00743276 | 34.9937 | 12116.53 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 30138.174 | 30138.174 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30138.17 | 30138.17 | 1.233640 | 16.72 | 10.17 | 0.00622663 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 16.6773 | 21.11 | 0.00691080 | 38.5618 | 11478.22 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 42527.350 | 33769.268 | 2.222500 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5417 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.222501 | 2.32102857 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 21263.67 | 20357.49 | 1.0000 | 1.54735152 | 1.481667 | 27.53 | 15.19 | 0.00737068 | 46469.2 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21263.67 | 38.10 | 0.00687148 | 18.17 | 0.41148071 | 27.7715 | 23.89 | 0.00748410 | 23.89 | 0.00748410 | 35.2328 | 21829.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 55422.799 | 55422.799 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.222501 | 2.32102857 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 55422.80 | 55422.80 | 1.0000 | 2.32102857 | 2.222501 | 16.24 | 9.86 | 0.00611476 | 31792.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 55422.80 | -5.20 | 0.00280840 | -5.20 | 0.41148071 | 18.5143 | 21.11 | 0.00686599 | 21.11 | 0.00686599 | 38.3132 | 18064.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21842.890 | 17403.759 | 1.147660 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5235 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.147657 | 1.19853430 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 10921.44 | 10466.81 | 1.0000 | 0.79902517 | 0.765107 | 27.48 | 15.17 | 0.00736088 | 46394.8 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10921.44 | 38.10 | 0.00687148 | 18.17 | 0.20573751 | 26.8900 | 23.89 | 0.00746778 | 23.89 | 0.00746778 | 35.1567 | 11272.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28433.041 | 28433.041 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.147657 | 1.19853430 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28433.04 | 28433.04 | 1.0000 | 1.19853430 | 1.147657 | 16.39 | 9.86 | 0.00605274 | 31792.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28433.04 | -5.20 | 0.00280840 | -5.20 | 0.20573751 | 17.9267 | 21.11 | 0.00676139 | 21.11 | 0.00676139 | 37.7357 | 8456.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22079.980 | 17606.134 | 1.162340 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5182 | 1004.8586 | 1.0443 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.162342 | 1.21387110 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 11039.99 | 10583.23 | 1.0000 | 0.80924570 | 0.774893 | 27.45 | 15.16 | 0.00735804 | 46355.6 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11039.99 | 38.10 | 0.00687148 | 18.17 | 0.20573751 | 26.5504 | 23.89 | 0.00746273 | 23.89 | 0.00746273 | 35.1332 | 11412.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28724.199 | 28724.199 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.162342 | 1.21387110 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28724.20 | 28724.20 | 1.0000 | 1.21387110 | 1.162342 | 16.45 | 9.90 | 0.00606905 | 31894.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28724.20 | -5.20 | 0.00280840 | -5.20 | 0.20573751 | 17.7002 | 21.11 | 0.00677032 | 21.11 | 0.00677032 | 37.7850 | 8557.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22160.830 | 17675.256 | 1.167360 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5164 | 1004.8586 | 1.0443 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.167357 | 1.21910775 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 11080.42 | 10622.95 | 1.0000 | 0.81274073 | 0.778240 | 27.43 | 15.15 | 0.00735708 | 46342.3 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11080.42 | 38.10 | 0.00687148 | 18.17 | 0.20573751 | 26.4363 | 23.89 | 0.00746102 | 23.89 | 0.00746102 | 35.1252 | 11461.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28823.613 | 28823.613 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.167357 | 1.21910775 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28823.61 | 28823.61 | 1.0000 | 1.21910775 | 1.167357 | 16.47 | 9.92 | 0.00607880 | 31939.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28823.61 | -5.20 | 0.00280840 | -5.20 | 0.20573751 | 17.6242 | 21.11 | 0.00677850 | 21.11 | 0.00677850 | 37.8303 | 8653.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22022.410 | 17556.706 | 1.158740 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5196 | 1004.8586 | 1.0443 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.158744 | 1.21011270 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 11011.20 | 10554.91 | 1.0000 | 0.80673930 | 0.772493 | 27.45 | 15.16 | 0.00735877 | 46365.6 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11011.20 | 38.10 | 0.00687148 | 18.17 | 0.20573751 | 26.6329 | 23.89 | 0.00746402 | 23.89 | 0.00746402 | 35.1392 | 11376.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28652.846 | 28652.846 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.158744 | 1.21011270 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28652.85 | 28652.85 | 1.0000 | 1.21011270 | 1.158744 | 16.44 | 9.91 | 0.00608604 | 31923.0 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28652.85 | -5.20 | 0.00280840 | -5.20 | 0.20573751 | 17.7552 | 21.11 | 0.00679363 | 21.11 | 0.00679363 | 37.9138 | 8826.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40263.200 | 31787.796 | 2.080610 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5781 | 1004.8586 | 1.0443 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.080610 | 2.17284701 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 20131.60 | 19237.70 | 1.0000 | 1.44856470 | 1.387073 | 27.71 | 15.27 | 0.00739023 | 46703.2 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20131.60 | 38.10 | 0.00687148 | 18.17 | 0.41148071 | 29.6654 | 23.89 | 0.00751820 | 23.89 | 0.00751820 | 35.3914 | 20425.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52609.300 | 52609.300 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.080610 | 2.17284701 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 52609.30 | 52609.30 | 1.0000 | 2.17284701 | 2.080610 | 15.90 | 9.68 | 0.00607082 | 31344.2 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52609.30 | -5.20 | 0.00280840 | -5.20 | 0.41148071 | 19.7769 | 21.11 | 0.00687509 | 21.11 | 0.00687509 | 38.3629 | 17172.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20787.060 | 16479.358 | 1.081930 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5490 | 1004.8586 | 1.0443 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.081929 | 1.12989312 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 10393.53 | 9948.29 | 1.0000 | 0.75326255 | 0.721287 | 27.63 | 15.23 | 0.00737459 | 46589.3 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10393.53 | 38.10 | 0.00687148 | 18.17 | 0.20573751 | 28.5237 | 23.89 | 0.00749283 | 23.89 | 0.00749283 | 35.2732 | 10619.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27129.938 | 27129.938 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.081929 | 1.12989312 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 27129.94 | 27129.94 | 1.0000 | 1.12989312 | 1.081929 | 16.11 | 9.75 | 0.00605589 | 31509.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27129.94 | -5.20 | 0.00280840 | -5.20 | 0.20573751 | 19.0158 | 21.11 | 0.00681843 | 21.11 | 0.00681843 | 38.0507 | 9127.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20699.730 | 16404.743 | 1.076510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5511 | 1004.8586 | 1.0443 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.076514 | 1.12423804 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 10349.86 | 9905.46 | 1.0000 | 0.74948904 | 0.717673 | 27.65 | 15.24 | 0.00737574 | 46606.1 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10349.86 | 38.10 | 0.00687148 | 18.17 | 0.20573751 | 28.6673 | 23.89 | 0.00749499 | 23.89 | 0.00749499 | 35.2833 | 10566.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27022.580 | 27022.580 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.076514 | 1.12423804 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 27022.58 | 27022.58 | 1.0000 | 1.12423804 | 1.076514 | 16.08 | 9.73 | 0.00605219 | 31474.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27022.58 | -5.20 | 0.00280840 | -5.20 | 0.20573751 | 19.1115 | 21.11 | 0.00681860 | 21.11 | 0.00681860 | 38.0517 | 9129.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20719.630 | 16421.550 | 1.077720 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5507 | 1004.8586 | 1.0443 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.077722 | 1.12549955 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 10359.82 | 9915.19 | 1.0000 | 0.75033146 | 0.718480 | 27.64 | 15.24 | 0.00737552 | 46602.7 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10359.82 | 38.10 | 0.00687148 | 18.17 | 0.20573751 | 28.6351 | 23.89 | 0.00749456 | 23.89 | 0.00749456 | 35.2813 | 10576.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27046.530 | 27046.530 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.077722 | 1.12549955 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 27046.53 | 27046.53 | 1.0000 | 1.12549955 | 1.077722 | 16.09 | 9.75 | 0.00607099 | 31528.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27046.53 | -5.20 | 0.00280840 | -5.20 | 0.20573751 | 19.0900 | 21.11 | 0.00684077 | 21.11 | 0.00684077 | 38.1741 | 9412.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22938.640 | 18358.023 | 1.233640 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4826 | 1004.8586 | 1.0443 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.233640 | 1.28832991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 11469.32 | 11014.40 | 1.0000 | 0.85888627 | 0.822427 | 27.21 | 15.06 | 0.00733886 | 46069.3 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11469.32 | 37.56 | 0.00687061 | 18.01 | 0.20573751 | 25.0159 | 23.89 | 0.00743276 | 23.89 | 0.00743276 | 34.9937 | 12116.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30138.174 | 30138.174 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.233640 | 1.28832991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30138.17 | 30138.17 | 1.0000 | 1.28832991 | 1.233640 | 16.72 | 10.17 | 0.00622663 | 32566.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30138.17 | -5.20 | 0.00280840 | -5.20 | 0.20573751 | 16.6773 | 21.11 | 0.00691080 | 21.11 | 0.00691080 | 38.5618 | 11478.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 2.22 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.15 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.16 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.17 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.16 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 2.08 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.08 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.08 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.08 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.23 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
LGSTORE1 | LGSTORE1_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE1 | SMSTORE1_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE2 | SMSTORE2_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE3 | SMSTORE3_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE4 | SMSTORE4_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LGSTORE2 | LGSTORE2_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE5 | SMSTORE5_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE6 | SMSTORE6_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE7 | SMSTORE7_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE8 | SMSTORE8_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 2246.17 | 3006.00 | 369.83 |
SMSTORE1 | 1976.17 | 2877.50 | 109.00 |
SMSTORE2 | 1663.33 | 2139.17 | 168.00 |
SMSTORE3 | 1685.67 | 2145.83 | 187.17 |
SMSTORE4 | 1695.83 | 2187.67 | 222.50 |
LGSTORE2 | 1572.83 | 2087.50 | 274.33 |
SMSTORE5 | 1532.00 | 2134.50 | 295.17 |
SMSTORE6 | 1544.67 | 2152.17 | 317.33 |
SMSTORE7 | 1609.67 | 2175.83 | 387.00 |
SMSTORE8 | 1926.50 | 2165.83 | 591.33 |
Facility | 2806.50 | 3374.67 | 828.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 1.17 | 0.00 | 0.00 | 0.00 |
Facility | 1.83 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.824 | 0.224 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.742 | 0.239 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.830 | 0.312 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.825 | 0.312 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.805 | 0.312 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 0.813 | 0.299 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.818 | 0.332 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.811 | 0.332 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.797 | 0.332 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.820 | 0.351 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.439 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.438 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.438 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 0.462 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.462 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.462 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.462 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.461 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.212 |
SMSTORE1 | PSZ-AC_2:2 | 8.47 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
LGSTORE2 | PSZ-AC_6:6 | 24.76 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.212 |
SMSTORE5 | PSZ-AC_7:7 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE6 | PSZ-AC_8:8 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE7 | PSZ-AC_9:9 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE8 | PSZ-AC_10:10 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
Total Facility | 120.91 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 1.274 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 8600381.76 | 0.00 | 8600381.76 | 2654284.96 | 11254666.72 | 7870781.79 | 3112.19 | 4198.75 | 1449.06 | 25.39 |
SMSTORE1 | 3880153.93 | 0.00 | 3880153.93 | 1335851.20 | 5216005.13 | 3935374.10 | 4257.76 | 3006.83 | 1495.40 | 31.40 |
SMSTORE2 | 3391963.86 | 0.00 | 3391963.86 | 1373042.31 | 4765006.17 | 3701819.01 | 4273.82 | 3338.83 | 1147.34 | 136.51 |
SMSTORE3 | 3374415.15 | 0.00 | 3374415.15 | 1373042.31 | 4747457.45 | 3701819.01 | 4273.32 | 3360.75 | 1125.93 | 135.48 |
SMSTORE4 | 3290330.61 | 0.00 | 3290330.61 | 1373042.31 | 4663372.91 | 3701819.01 | 4276.16 | 3420.25 | 1063.59 | 129.66 |
LGSTORE2 | 6024502.04 | 0.00 | 6024502.04 | 2517504.51 | 8542006.55 | 7907875.00 | 4664.37 | 3246.67 | 848.96 | 88.83 |
SMSTORE5 | 3035030.81 | 0.00 | 3035030.81 | 1381311.82 | 4416342.63 | 3953920.18 | 4663.57 | 3272.08 | 824.34 | 88.84 |
SMSTORE6 | 3008421.99 | 0.00 | 3008421.99 | 1381311.82 | 4389733.82 | 3953920.18 | 4664.12 | 3297.33 | 798.55 | 86.63 |
SMSTORE7 | 2955127.40 | 0.00 | 2955127.40 | 1381311.82 | 4336439.22 | 3953920.18 | 4667.92 | 3355.50 | 736.58 | 82.06 |
SMSTORE8 | 3045469.95 | 0.00 | 3045469.95 | 1677204.46 | 4722674.41 | 3953920.18 | 4666.83 | 3400.37 | 692.79 | 74.40 |
Total Facility | 40605797.49 | 0.00 | 40605797.49 | 16447907.52 | 57053705.01 | 46635168.64 | 4674.16 | 4733.37 | 1818.90 | 240.71 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4061 | 0.0000 | 0.4061 | 0.1106 | 0.5167 | 0.2682 | 210.75 | 4198.75 | 1430.50 |
SMSTORE1 | 0.1828 | 0.0000 | 0.1828 | 0.0589 | 0.2417 | 0.1341 | 1358.83 | 3006.33 | 1474.83 |
SMSTORE2 | 0.2044 | 0.0000 | 0.2044 | 0.0768 | 0.2813 | 0.1285 | 0.00 | 3337.83 | 1057.17 |
SMSTORE3 | 0.2032 | 0.0000 | 0.2032 | 0.0768 | 0.2801 | 0.1285 | 0.00 | 3360.25 | 1034.75 |
SMSTORE4 | 0.1984 | 0.0000 | 0.1984 | 0.0768 | 0.2752 | 0.1285 | 0.00 | 3420.25 | 974.75 |
LGSTORE2 | 0.4009 | 0.0000 | 0.4009 | 0.1476 | 0.5485 | 0.2958 | 0.00 | 3246.33 | 783.67 |
SMSTORE5 | 0.2017 | 0.0000 | 0.2017 | 0.0820 | 0.2837 | 0.1479 | 0.00 | 3271.75 | 758.25 |
SMSTORE6 | 0.2000 | 0.0000 | 0.2000 | 0.0820 | 0.2820 | 0.1479 | 0.00 | 3296.50 | 733.50 |
SMSTORE7 | 0.1966 | 0.0000 | 0.1966 | 0.0820 | 0.2786 | 0.1479 | 0.00 | 3355.00 | 675.00 |
SMSTORE8 | 0.2021 | 0.0000 | 0.2021 | 0.0865 | 0.2887 | 0.1479 | 0.00 | 3400.33 | 629.67 |
Total Facility | 2.3961 | 0.0000 | 2.3961 | 0.8802 | 3.2763 | 1.6752 | 1449.86 | 4730.33 | 1739.60 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 9379812.05 | 0.00 | 9379812.05 | 7870781.79 | 3110.63 | 0.33 | 5649.03 | 25.39 |
PSZ-AC_2:2 | 4231807.04 | 0.00 | 4231807.04 | 3935374.10 | 4238.26 | 4.17 | 4517.57 | 31.40 |
PSZ-AC_3:3 | 3699364.98 | 0.00 | 3699364.98 | 3701819.01 | 4271.26 | 0.33 | 4488.41 | 136.01 |
PSZ-AC_4:4 | 3680224.80 | 0.00 | 3680224.80 | 3701819.01 | 4270.32 | 0.67 | 4489.01 | 135.48 |
PSZ-AC_5:5 | 3588517.36 | 0.00 | 3588517.36 | 3701819.01 | 4274.82 | 0.33 | 4484.84 | 129.58 |
PSZ-AC_6:6 | 6570466.30 | 0.00 | 6570466.30 | 7907875.00 | 4662.96 | 0.33 | 4096.71 | 88.67 |
PSZ-AC_7:7 | 3310075.59 | 0.00 | 3310075.59 | 3953920.18 | 4662.57 | 0.00 | 4097.42 | 88.84 |
PSZ-AC_8:8 | 3281051.05 | 0.00 | 3281051.05 | 3953920.18 | 4663.03 | 0.25 | 4096.72 | 86.55 |
PSZ-AC_9:9 | 3222914.77 | 0.00 | 3222914.77 | 3953920.18 | 4666.67 | 0.33 | 4093.00 | 81.81 |
PSZ-AC_10:10 | 3321437.71 | 0.00 | 3321437.71 | 3953920.18 | 4665.83 | 0.00 | 4094.17 | 74.40 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.4429 | 0.0000 | 0.4429 | 0.2682 | 209.53 | 0.33 | 5630.14 |
PSZ-AC_2:2 | 0.1994 | 0.0000 | 0.1994 | 0.1341 | 1340.00 | 4.17 | 4495.83 |
PSZ-AC_3:3 | 0.2230 | 0.0000 | 0.2230 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2216 | 0.0000 | 0.2216 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2164 | 0.0000 | 0.2164 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.4372 | 0.0000 | 0.4372 | 0.2958 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2199 | 0.0000 | 0.2199 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2181 | 0.0000 | 0.2181 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2144 | 0.0000 | 0.2144 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2204 | 0.0000 | 0.2204 | 0.1479 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 751.33 | 802.45 | 0.00 | 0.00 | 0.00 | 4119.75 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 666.85 | 1139.67 | 0.00 | 0.00 | 0.00 | 3506.82 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 578.82 | 658.69 | 0.00 | 0.00 | 0.00 | 3293.50 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 571.75 | 635.47 | 0.00 | 0.00 | 0.00 | 3323.25 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 540.55 | 603.78 | 0.00 | 0.00 | 0.00 | 3380.25 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 467.11 | 454.73 | 0.00 | 0.00 | 0.00 | 3196.83 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 456.86 | 432.82 | 0.00 | 0.00 | 0.00 | 3229.17 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 446.74 | 415.98 | 0.00 | 0.00 | 0.00 | 3253.83 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 417.11 | 378.20 | 0.00 | 0.00 | 0.00 | 3316.50 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 391.72 | 341.85 | 0.00 | 0.00 | 0.00 | 3370.83 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.2020 | 0.6106 | 0.0000 | 0.0000 | 0.0000 | 0.2953 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.6072 | 0.2616 | 0.0000 | 0.0000 | 0.0000 | 0.1354 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.6281 | 0.3239 | 0.0000 | 0.0000 | 0.0000 | 0.1400 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.6311 | 0.3252 | 0.0000 | 0.0000 | 0.0000 | 0.1401 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.6258 | 0.3224 | 0.0000 | 0.0000 | 0.0000 | 0.1401 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 1.1243 | 0.6141 | 0.0000 | 0.0000 | 0.0000 | 0.3229 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.5850 | 0.3147 | 0.0000 | 0.0000 | 0.0000 | 0.1615 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.5824 | 0.3151 | 0.0000 | 0.0000 | 0.0000 | 0.1616 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.5818 | 0.3213 | 0.0000 | 0.0000 | 0.0000 | 0.1615 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.6672 | 0.3528 | 0.0000 | 0.0000 | 0.0000 | 0.1616 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 835 |
Defaulted Fields | 817 |
Fields with Defaults | 2693 |
Autosized Fields | 174 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 759.97 | 2102.83 | 01-JAN-07:20 | 73161.98 | 03-JUL-16:50 |
Electricity:Building | 405.94 | 891.83 | 01-JAN-00:20 | 25756.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 90.96 | 148.64 | 01-JAN-00:20 | 4765.21 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 405.94 | 891.83 | 01-JAN-00:20 | 25756.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 64.71 | 75.00 | 01-JAN-00:20 | 3421.96 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 64.71 | 75.00 | 01-JAN-00:20 | 3421.96 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 52.56 | 74.32 | 01-JAN-00:20 | 2762.01 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 39.44 | 37.50 | 01-JAN-00:20 | 2090.38 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 39.44 | 37.50 | 01-JAN-00:20 | 2090.38 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 47.80 | 148.64 | 01-JAN-00:10 | 3421.36 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 28.62 | 75.00 | 01-JAN-00:10 | 2078.11 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 28.62 | 75.00 | 01-JAN-00:10 | 2078.11 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityProduced:Facility | 79.47 | -0.00 | 06-MAY-05:30 | 11250.00 | 22-APR-11:30 |
ElectricityProduced:Plant | 79.47 | -0.00 | 06-MAY-05:30 | 11250.00 | 22-APR-11:30 |
Photovoltaic:ElectricityProduced | 82.88 | 0.00 | 01-JAN-00:10 | 12199.36 | 22-APR-12:30 |
PowerConversion:ElectricityProduced | -3.41 | -949.36 | 22-APR-12:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 61.45 | 1211.00 | 02-JAN-08:10 | 11831.29 | 29-DEC-14:40 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 680.53 | 0.00 | 19-FEB-08:00 | 72496.94 | 03-JUL-16:50 |
ElectricityPurchased:Plant | 680.53 | 0.00 | 19-FEB-08:00 | 72496.94 | 03-JUL-16:50 |
Cogeneration:ElectricityPurchased | 680.53 | 0.00 | 19-FEB-08:00 | 72496.94 | 03-JUL-16:50 |
General:Cogeneration:ElectricityPurchased | 680.53 | 0.00 | 19-FEB-08:00 | 72496.94 | 03-JUL-16:50 |
ElectricitySurplusSold:Facility | 0.02 | 0.00 | 01-JAN-00:10 | 1505.65 | 28-MAY-07:00 |
ElectricitySurplusSold:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 1505.65 | 28-MAY-07:00 |
Cogeneration:ElectricitySurplusSold | 0.02 | 0.00 | 01-JAN-00:10 | 1505.65 | 28-MAY-07:00 |
General:Cogeneration:ElectricitySurplusSold | 0.02 | 0.00 | 01-JAN-00:10 | 1505.65 | 28-MAY-07:00 |
ElectricityNet:Facility | 680.51 | -1505.65 | 28-MAY-07:00 | 72496.94 | 03-JUL-16:50 |
ElectricityNet:Plant | 680.51 | -1505.65 | 28-MAY-07:00 | 72496.94 | 03-JUL-16:50 |
Cogeneration:ElectricityNet | 680.51 | -1505.65 | 28-MAY-07:00 | 72496.94 | 03-JUL-16:50 |
General:Cogeneration:ElectricityNet | 680.51 | -1505.65 | 28-MAY-07:00 | 72496.94 | 03-JUL-16:50 |
Electricity:HVAC | 251.62 | 0.00 | 01-JAN-00:10 | 42618.01 | 02-JUN-16:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 149.05 | 0.00 | 01-JAN-00:10 | 35926.85 | 02-JUN-16:20 |
General:Cooling:Electricity | 149.05 | 0.00 | 01-JAN-00:10 | 35926.85 | 02-JUN-16:20 |
Fans:Electricity | 102.57 | 0.00 | 01-JAN-00:10 | 8126.81 | 27-DEC-08:10 |
General:Fans:Electricity | 102.57 | 0.00 | 01-JAN-00:10 | 8126.81 | 27-DEC-08:10 |
ExteriorLights:Electricity | 40.96 | 0.00 | 01-JAN-07:20 | 3786.68 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 40.96 | 0.00 | 01-JAN-07:20 | 3786.68 | 01-JAN-06:10 |
WaterSystems:Electricity | 61.45 | 1211.00 | 02-JAN-08:10 | 11831.29 | 29-DEC-14:40 |
Water Heater:WaterSystems:Electricity | 61.45 | 1211.00 | 02-JAN-08:10 | 11831.29 | 29-DEC-14:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 38.47 | 0.00 | 01-JAN-00:10 | 106819.10 | 27-DEC-08:10 |
NaturalGas:HVAC | 38.47 | 0.00 | 01-JAN-00:10 | 106819.10 | 27-DEC-08:10 |
Heating:NaturalGas | 38.47 | 0.00 | 01-JAN-00:10 | 106819.10 | 27-DEC-08:10 |
General:Heating:NaturalGas | 38.47 | 0.00 | 01-JAN-00:10 | 106819.10 | 27-DEC-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1118.00 | 0.00 | 01-JAN-00:10 | 216561.26 | 07-AUG-16:10 |
EnergyTransfer:Building | 514.92 | 0.00 | 01-JAN-00:10 | 90965.00 | 07-AUG-16:10 |
EnergyTransfer:Zone:LGSTORE1 | 107.08 | 0.00 | 01-JAN-00:10 | 16109.77 | 28-JAN-08:10 |
Heating:EnergyTransfer | 18.41 | 0.00 | 01-JAN-00:10 | 81970.58 | 27-DEC-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 2.27 | 0.00 | 01-JAN-00:10 | 16109.77 | 28-JAN-08:10 |
General:Heating:EnergyTransfer | 18.41 | 0.00 | 01-JAN-00:10 | 81970.58 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 2.27 | 0.00 | 01-JAN-00:10 | 16109.77 | 28-JAN-08:10 |
Cooling:EnergyTransfer | 496.51 | 0.00 | 01-JAN-00:10 | 90965.00 | 07-AUG-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 104.82 | 0.00 | 01-JAN-00:10 | 15431.34 | 07-AUG-16:10 |
General:Cooling:EnergyTransfer | 496.51 | 0.00 | 01-JAN-00:10 | 90965.00 | 07-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 104.82 | 0.00 | 01-JAN-00:10 | 15431.34 | 07-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 56.57 | 0.00 | 01-JAN-00:10 | 8182.86 | 26-OCT-20:20 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.52 | 0.00 | 01-JAN-00:10 | 4873.58 | 28-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.52 | 0.00 | 01-JAN-00:10 | 4873.58 | 28-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 56.05 | 0.00 | 01-JAN-00:10 | 8182.86 | 26-OCT-20:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 56.05 | 0.00 | 01-JAN-00:10 | 8182.86 | 26-OCT-20:20 |
EnergyTransfer:Zone:SMSTORE2 | 43.12 | 0.00 | 01-JAN-00:10 | 7620.50 | 07-AUG-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.08 | 0.00 | 01-JAN-00:10 | 5262.87 | 28-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.08 | 0.00 | 01-JAN-00:10 | 5262.87 | 28-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 42.04 | 0.00 | 01-JAN-00:10 | 7620.50 | 07-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 42.04 | 0.00 | 01-JAN-00:10 | 7620.50 | 07-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 42.98 | 0.00 | 01-JAN-00:10 | 7694.73 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.19 | 0.00 | 01-JAN-00:10 | 5729.78 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.19 | 0.00 | 01-JAN-00:10 | 5729.78 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 41.79 | 0.00 | 01-JAN-00:10 | 7694.73 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 41.79 | 0.00 | 01-JAN-00:10 | 7694.73 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 41.30 | 0.00 | 01-JAN-00:10 | 7626.94 | 07-AUG-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.42 | 0.00 | 01-JAN-00:10 | 6512.50 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.42 | 0.00 | 01-JAN-00:10 | 6512.50 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 39.88 | 0.00 | 01-JAN-00:10 | 7626.94 | 07-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 39.88 | 0.00 | 01-JAN-00:10 | 7626.94 | 07-AUG-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 72.50 | 0.00 | 01-JAN-00:10 | 15592.52 | 27-DEC-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 2.57 | 0.00 | 01-JAN-00:10 | 15592.52 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 2.57 | 0.00 | 01-JAN-00:10 | 15592.52 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 69.92 | 0.00 | 01-JAN-00:10 | 14457.44 | 03-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 69.92 | 0.00 | 01-JAN-00:10 | 14457.44 | 03-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE5 | 36.97 | 0.00 | 01-JAN-00:10 | 8068.10 | 27-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 1.50 | 0.00 | 01-JAN-00:10 | 8068.10 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 1.50 | 0.00 | 01-JAN-00:10 | 8068.10 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 35.47 | 0.00 | 01-JAN-00:10 | 7595.53 | 03-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 35.47 | 0.00 | 01-JAN-00:10 | 7595.53 | 03-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 36.51 | 0.00 | 01-JAN-00:10 | 8251.79 | 27-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 1.62 | 0.00 | 01-JAN-00:10 | 8251.79 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 1.62 | 0.00 | 01-JAN-00:10 | 8251.79 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 34.90 | 0.00 | 01-JAN-00:10 | 7571.85 | 03-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 34.90 | 0.00 | 01-JAN-00:10 | 7571.85 | 03-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 35.94 | 0.00 | 01-JAN-00:10 | 9302.95 | 27-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 2.11 | 0.00 | 01-JAN-00:10 | 9302.95 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 2.11 | 0.00 | 01-JAN-00:10 | 9302.95 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 33.83 | 0.00 | 01-JAN-00:10 | 7642.39 | 03-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 33.83 | 0.00 | 01-JAN-00:10 | 7642.39 | 03-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 41.94 | 0.00 | 01-JAN-00:10 | 13865.70 | 02-MAR-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 4.13 | 0.00 | 01-JAN-00:10 | 13865.70 | 02-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 4.13 | 0.00 | 01-JAN-00:10 | 13865.70 | 02-MAR-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 37.81 | 0.00 | 01-JAN-00:10 | 9214.50 | 03-JUL-12:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 37.81 | 0.00 | 01-JAN-00:10 | 9214.50 | 03-JUL-12:50 |
EnergyTransfer:HVAC | 603.08 | 0.00 | 01-JAN-00:10 | 127135.55 | 26-JUL-14:10 |
HeatingCoils:EnergyTransfer | 30.77 | 0.00 | 01-JAN-00:10 | 85455.28 | 27-DEC-08:10 |
CoolingCoils:EnergyTransfer | 572.31 | 0.00 | 01-JAN-00:10 | 127135.55 | 26-JUL-14:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 2.267 | -104.816 | 0.000 | 0.000 | 24.039 | 64.707 | 26.249 | 18.129 | 0.000 | 7.118 | 0.003 | 0.000 | -4.579 | 0.000 | -12.919 | -20.195 |
SMSTORE1 | 0.000 | 0.000 | 0.521 | -56.053 | 0.000 | 0.000 | 11.877 | 39.440 | 13.125 | 9.024 | 0.000 | 3.829 | 0.001 | 0.000 | -2.379 | 0.000 | -6.304 | -13.079 |
SMSTORE2 | 0.000 | 0.000 | 1.080 | -42.043 | 0.000 | 0.000 | 7.187 | 28.854 | 10.421 | 8.979 | 0.000 | 3.785 | 0.002 | 0.000 | -2.419 | 0.000 | -6.474 | -9.370 |
SMSTORE3 | 0.000 | 0.000 | 1.188 | -41.789 | 0.000 | 0.000 | 7.200 | 28.854 | 10.421 | 8.986 | 0.000 | 3.783 | 0.001 | 0.000 | -2.401 | 0.000 | -6.422 | -9.819 |
SMSTORE4 | 0.000 | 0.000 | 1.418 | -39.879 | 0.000 | 0.000 | 7.223 | 28.854 | 10.421 | 9.003 | 0.000 | 3.786 | 0.001 | 0.000 | -2.368 | 0.000 | -6.329 | -12.130 |
LGSTORE2 | 0.000 | 0.000 | 2.573 | -69.921 | 0.000 | 0.000 | 24.884 | 28.624 | 19.173 | 18.028 | 0.000 | 6.846 | 0.001 | 0.000 | -4.598 | 0.000 | -11.519 | -14.089 |
SMSTORE5 | 0.000 | 0.000 | 1.501 | -35.470 | 0.000 | 0.000 | 12.456 | 14.614 | 9.586 | 9.009 | 0.000 | 3.802 | 0.001 | 0.000 | -2.286 | 0.000 | -6.221 | -6.992 |
SMSTORE6 | 0.000 | 0.000 | 1.618 | -34.896 | 0.000 | 0.000 | 12.469 | 14.614 | 9.586 | 9.017 | 0.000 | 3.802 | 0.001 | 0.000 | -2.273 | 0.000 | -6.189 | -7.749 |
SMSTORE7 | 0.000 | 0.000 | 2.109 | -33.827 | 0.000 | 0.000 | 12.502 | 14.614 | 9.586 | 9.032 | 0.000 | 3.804 | 0.001 | 0.000 | -2.240 | 0.000 | -6.103 | -9.476 |
SMSTORE8 | 0.000 | 0.000 | 4.130 | -37.811 | 0.000 | 0.000 | 12.537 | 14.614 | 9.586 | 9.042 | 0.000 | 4.048 | 0.002 | 0.000 | -2.136 | 0.000 | -7.947 | -6.065 |
Total Facility | 0.000 | 0.000 | 18.406 | -496.506 | 0.000 | 0.000 | 132.374 | 277.790 | 128.154 | 108.249 | 0.000 | 44.604 | 0.013 | 0.000 | -27.680 | 0.000 | -76.427 | -108.963 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 03-JUL-07:01 | 0.00 | 0.00 | 0.00 | -36986.99 | 0.00 | 0.00 | 165.58 | 75.00 | 74.62 | 306.48 | 0.00 | 125.19 | 36240.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 03-JUL-07:01 | 0.00 | 0.00 | 0.00 | -19011.99 | 0.00 | 0.00 | 82.99 | 37.50 | 37.31 | 154.04 | 0.00 | 59.79 | 18640.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 06-JUN-06:02 | 0.00 | 0.00 | 0.00 | -20740.30 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 14.64 | 0.00 | 0.00 | 20656.56 | 0.00 | -0.00 | 0.00 | -5.22 | 0.00 |
SMSTORE3 | 06-JUN-06:02 | 0.00 | 0.00 | 0.00 | -20859.59 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 13.87 | 0.00 | 0.00 | 20776.77 | 0.00 | -0.00 | 0.00 | -5.38 | 0.00 |
SMSTORE4 | 06-JUN-06:02 | 0.00 | 0.00 | 0.00 | -20642.42 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 14.93 | 0.00 | 0.00 | 20558.22 | 0.00 | -0.00 | 0.00 | -5.05 | 0.00 |
LGSTORE2 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -35227.60 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 35204.59 | 0.00 | -36.42 | 0.00 | -89.22 | 0.00 |
SMSTORE5 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -18189.53 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 18181.15 | 0.00 | -17.92 | 0.00 | -48.02 | 0.00 |
SMSTORE6 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -18092.21 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 18083.26 | 0.00 | -17.66 | 0.00 | -47.72 | 0.00 |
SMSTORE7 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -18069.07 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 18059.10 | 0.00 | -17.50 | 0.00 | -46.85 | 0.00 |
SMSTORE8 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -19986.55 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 19983.72 | 0.00 | -18.71 | 0.00 | -52.78 | 0.00 |
Total Facility | 03-JUL-07:01 | 0.00 | 0.00 | 0.00 | -175848.51 | 0.00 | 0.00 | 544.09 | 450.00 | 1452.23 | 1836.28 | 0.00 | 763.95 | 170801.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 19-DEC-08:61 | 0.00 | 0.00 | 55689.67 | 0.00 | 0.00 | 0.00 | 251.07 | 75.00 | 74.62 | 331.01 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -818.80 | -55602.58 |
SMSTORE1 | 03-FEB-08:61 | 0.00 | 0.00 | 28577.94 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 213.73 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -450.61 | -28415.38 |
SMSTORE2 | 31-DEC-08:61 | 0.00 | 0.00 | 28405.68 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 398.80 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -493.84 | -28385.45 |
SMSTORE3 | 31-DEC-08:61 | 0.00 | 0.00 | 28498.76 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 401.43 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -489.40 | -28485.60 |
SMSTORE4 | 31-DEC-08:61 | 0.00 | 0.00 | 28340.74 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 404.05 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -484.23 | -28335.36 |
LGSTORE2 | 19-DEC-08:61 | 0.00 | 0.00 | 52957.51 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 334.05 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -810.77 | -52629.42 |
SMSTORE5 | 19-DEC-08:61 | 0.00 | 0.00 | 27323.40 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 167.93 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -451.64 | -27114.01 |
SMSTORE6 | 19-DEC-08:61 | 0.00 | 0.00 | 27218.54 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 169.24 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -449.56 | -27012.54 |
SMSTORE7 | 19-DEC-08:61 | 0.00 | 0.00 | 27245.90 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 173.73 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -441.92 | -27052.04 |
SMSTORE8 | 19-DEC-08:61 | 0.00 | 0.00 | 30250.46 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 190.88 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -415.42 | -30100.24 |
Total Facility | 27-DEC-08:61 | 0.00 | 0.00 | 256490.41 | 0.00 | 0.00 | 0.00 | 732.17 | 450.00 | 1452.23 | 2802.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6012.40 | -255914.82 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.2225 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.2225 | 0.1851 | 1.0000 | Not calculated | 0.4115 | 0.1851 | ||
PSZ-AC_2:2 | 1.1477 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1477 | 0.1793 | 1.0000 | Not calculated | 0.2057 | 0.1793 | ||
PSZ-AC_3:3 | 1.1623 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1623 | 0.1770 | 1.0000 | Not calculated | 0.2057 | 0.1770 | ||
PSZ-AC_4:4 | 1.1674 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1674 | 0.1762 | 1.0000 | Not calculated | 0.2057 | 0.1762 | ||
PSZ-AC_5:5 | 1.1587 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1587 | 0.1776 | 1.0000 | Not calculated | 0.2057 | 0.1776 | ||
PSZ-AC_6:6 | 2.0806 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0806 | 0.1978 | 1.0000 | Not calculated | 0.4115 | 0.1978 | ||
PSZ-AC_7:7 | 1.0819 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0819 | 0.1902 | 1.0000 | Not calculated | 0.2057 | 0.1902 | ||
PSZ-AC_8:8 | 1.0765 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0765 | 0.1911 | 1.0000 | Not calculated | 0.2057 | 0.1911 | ||
PSZ-AC_9:9 | 1.0777 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0777 | 0.1909 | 1.0000 | Not calculated | 0.2057 | 0.1909 | ||
PSZ-AC_10:10 | 1.2336 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2336 | 0.1668 | 1.0000 | Not calculated | 0.2057 | 0.1668 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.2225 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.2225 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1851 | ||
PSZ-AC_2:2 | 1.1477 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1477 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1793 | ||
PSZ-AC_3:3 | 1.1623 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1623 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1770 | ||
PSZ-AC_4:4 | 1.1674 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1674 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1762 | ||
PSZ-AC_5:5 | 1.1587 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1587 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1776 | ||
PSZ-AC_6:6 | 2.0806 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0806 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1978 | ||
PSZ-AC_7:7 | 1.0819 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0819 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1902 | ||
PSZ-AC_8:8 | 1.0765 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0765 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1911 | ||
PSZ-AC_9:9 | 1.0777 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0777 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1909 | ||
PSZ-AC_10:10 | 1.2336 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2336 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1668 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.003540 | 56.2505 | 0.000610 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.003540 | 56.2505 | 0.000610 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.003540 | 56.25 | 0.000610 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.003540 | 56.25 | 0.000610 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2225 | 2.2225 | 2.2225 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1477 | 1.1477 | 1.1477 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1623 | 1.1623 | 1.1623 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1674 | 1.1674 | 1.1674 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1587 | 1.1587 | 1.1587 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0806 | 2.0806 | 2.0806 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0819 | 1.0819 | 1.0819 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0765 | 1.0765 | 1.0765 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0777 | 1.0777 | 1.0777 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2336 | 1.2336 | 1.2336 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.2225 | 2.2225 | 2.2225 | 2.2225 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1477 | 1.1477 | 1.1477 | 1.1477 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1623 | 1.1623 | 1.1623 | 1.1623 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1674 | 1.1674 | 1.1674 | 1.1674 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1587 | 1.1587 | 1.1587 | 1.1587 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.0806 | 2.0806 | 2.0806 | 2.0806 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0819 | 1.0819 | 1.0819 | 1.0819 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0765 | 1.0765 | 1.0765 | 1.0765 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0777 | 1.0777 | 1.0777 | 1.0777 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2336 | 1.2336 | 1.2336 | 1.2336 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2225 | 2.2225 | 2.2225 | No | 0.4115 | 0.3819 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1477 | 1.1477 | 1.1477 | No | 0.2057 | 0.4079 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1623 | 1.1623 | 1.1623 | No | 0.2057 | 0.4031 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1674 | 1.1674 | 1.1674 | No | 0.2057 | 0.3986 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1587 | 1.1587 | 1.1587 | No | 0.2057 | 0.3908 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0806 | 2.0806 | 2.0806 | No | 0.4115 | 0.4017 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0819 | 1.0819 | 1.0819 | No | 0.2057 | 0.3779 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0765 | 1.0765 | 1.0765 | No | 0.2057 | 0.3778 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0777 | 1.0777 | 1.0777 | No | 0.2057 | 0.3665 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2336 | 1.2336 | 1.2336 | No | 0.2057 | 0.3005 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.2225 | 2.2225 | 2.2225 | 2.2225 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1477 | 1.1477 | 1.1477 | 1.1477 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1623 | 1.1623 | 1.1623 | 1.1623 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1674 | 1.1674 | 1.1674 | 1.1674 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1587 | 1.1587 | 1.1587 | 1.1587 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.0806 | 2.0806 | 2.0806 | 2.0806 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0819 | 1.0819 | 1.0819 | 1.0819 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0765 | 1.0765 | 1.0765 | 1.0765 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0777 | 1.0777 | 1.0777 | 1.0777 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2336 | 1.2336 | 1.2336 | 1.2336 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 38.47 | 106819.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 149.05 | 35926.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 277.79 | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 40.96 | 3786.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 102.57 | 8126.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 61.45 | 11831.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 759.97 |
Natural Gas | 0.00 | 38.47 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 798.44 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 82.88 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 132.89 |
Space Heating | 0.00 |
Space Cooling | 71.30 |
Fans (All) | 49.07 |
Service Water Heating | 29.40 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 363.57 |
Subtotal | 363.57 |
Natural Gas [MJ/m2] | |
Space Heating | 18.40 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 18.40 |
Subtotal | 18.40 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 34.79 |
Space Heating | 4.82 |
Space Cooling | 18.67 |
Fans (All) | 12.85 |
Service Water Heating | 7.70 |
Receptacle Equipment | 16.05 |
Miscellaneous | 5.13 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3140. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3200. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4323. | 8760. |
LTG_SCH_BASE_LPD1 | 4243. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3479. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8725.50 | 34.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8719.33 | 40.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8726.50 | 33.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8730.67 | 29.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8737.83 | 22.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8739.50 | 20.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8739.50 | 20.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8699.33 | 60.67 | 0.00 | 0.00 | 0.00 |
Min | 8699.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 60.67 | 0.00 | 0.00 | 0.00 |
Average | 8733.82 | 26.18 | 0.00 | 0.00 | 0.00 |
Sum | 87338.17 | 261.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25458.67 | 16.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25458.33 | 16.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25460.50 | 14.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93144.00 | 67.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45883.50 | 28.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45884.50 | 27.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45885.00 | 27.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45869.00 | 43.00 | 0.00 | 0.00 | 0.00 |
Min | 25458.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93144.00 | 67.00 | 0.00 | 0.00 | 0.00 |
Average | 48586.15 | 24.05 | 0.00 | 0.00 | 0.00 |
Sum | 485861.50 | 240.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8589.67 | 170.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8735.83 | 24.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8527.67 | 232.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8521.33 | 238.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8533.17 | 226.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8527.00 | 233.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8539.83 | 220.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8542.50 | 217.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8550.00 | 210.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8492.83 | 267.17 | 0.00 | 0.00 | 0.00 |
Min | 8492.83 | 24.17 | 0.00 | 0.00 | 0.00 |
Max | 8735.83 | 267.17 | 0.00 | 0.00 | 0.00 |
Average | 8555.98 | 204.02 | 0.00 | 0.00 | 0.00 |
Sum | 85559.83 | 2040.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 88883.50 | 157.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43734.00 | 43.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25423.17 | 51.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25423.67 | 51.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25424.00 | 51.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93013.67 | 197.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45805.00 | 107.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45801.67 | 110.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45801.67 | 110.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45771.17 | 140.83 | 0.00 | 0.00 | 0.00 |
Min | 25423.17 | 43.00 | 0.00 | 0.00 | 0.00 |
Max | 93013.67 | 197.33 | 0.00 | 0.00 | 0.00 |
Average | 48508.15 | 102.05 | 0.00 | 0.00 | 0.00 |
Sum | 485081.50 | 1020.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:21
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301403E+10 | 4005.75 | 04-JAN-22:00 | 4.40 | -1.6 | 0.116264E+10 | 1638.05 | 13-JAN-13:00 | 17.80 | 8.76 |
February | 0.275376E+10 | 4783.63 | 08-FEB-20:00 | 3.90 | -0.7 | 0.112042E+10 | 1685.85 | 19-FEB-17:49 | 21.28 | 7.71 |
March | 0.337749E+10 | 5421.86 | 16-MAR-17:10 | 20.92 | 7.82 | 0.132082E+10 | 1685.85 | 19-MAR-16:49 | 20.37 | 7.83 |
April | 0.715385E+10 | 10657.28 | 30-APR-16:05 | 30.50 | 12.87 | 0.135593E+10 | 1685.87 | 29-APR-12:09 | 30.50 | 12.87 |
May | 0.111911E+11 | 23089.86 | 31-MAY-07:03 | 25.37 | 12.75 | 0.140129E+10 | 1685.96 | 28-MAY-12:09 | 25.37 | 12.75 |
June | 0.144928E+11 | 35552.65 | 17-JUN-07:02 | 24.78 | 15.73 | 0.135454E+10 | 1685.96 | 23-JUN-12:09 | 27.57 | 16.83 |
July | 0.156282E+11 | 36986.91 | 03-JUL-07:01 | 27.98 | 16.41 | 0.141283E+10 | 1686.00 | 04-JUL-17:00 | 26.10 | 19.85 |
August | 0.152939E+11 | 35748.44 | 07-AUG-07:01 | 26.47 | 16.94 | 0.139408E+10 | 1685.99 | 18-AUG-12:30 | 26.95 | 18.05 |
September | 0.139658E+11 | 30699.32 | 13-SEP-07:02 | 22.88 | 17.65 | 0.136515E+10 | 1686.00 | 03-SEP-17:00 | 22.88 | 17.65 |
October | 0.100093E+11 | 36802.29 | 02-OCT-07:02 | 22.02 | 15.21 | 0.140881E+10 | 1686.01 | 08-OCT-17:40 | 24.07 | 17.00 |
November | 0.497416E+10 | 7949.54 | 09-NOV-15:00 | 23.30 | 12.64 | 0.129412E+10 | 1685.92 | 03-NOV-12:00 | 23.30 | 12.64 |
December | 0.296273E+10 | 4354.15 | 18-DEC-18:20 | 5.40 | -2.3 | 0.114726E+10 | 1672.05 | 10-DEC-13:00 | 5.40 | -2.3 |
Annual Sum or Average | 0.104817E+12 | 0.157379E+11 | ||||||||
Minimum of Months | 0.275376E+10 | 4005.75 | 3.90 | -2.3 | 0.112042E+10 | 1638.05 | 5.40 | -2.3 | ||
Maximum of Months | 0.156282E+11 | 36986.91 | 30.50 | 17.65 | 0.141283E+10 | 1686.01 | 30.50 | 19.85 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138868E+10 | 2309.66 | 01-JAN-18:10 | 12.52 | 7.66 | 0.625729E+09 | 842.90 | 01-JAN-18:00 | 11.10 | 7.09 |
February | 0.151398E+10 | 15307.59 | 19-FEB-18:47 | 19.27 | 6.84 | 0.591373E+09 | 842.90 | 19-FEB-17:10 | 19.27 | 6.84 |
March | 0.209703E+10 | 15527.94 | 19-MAR-17:08 | 19.17 | 7.66 | 0.678997E+09 | 842.90 | 19-MAR-16:19 | 19.17 | 7.66 |
April | 0.432252E+10 | 15671.60 | 15-APR-21:00 | 18.90 | 6.31 | 0.676886E+09 | 842.91 | 29-APR-12:09 | 27.30 | 15.21 |
May | 0.618415E+10 | 15204.14 | 06-MAY-21:45 | 19.78 | 8.10 | 0.698821E+09 | 842.95 | 28-MAY-12:09 | 29.78 | 17.88 |
June | 0.762074E+10 | 18437.34 | 17-JUN-07:02 | 24.78 | 15.73 | 0.676776E+09 | 842.95 | 23-JUN-12:09 | 27.57 | 16.83 |
July | 0.807967E+10 | 19011.94 | 03-JUL-07:01 | 27.98 | 16.41 | 0.706258E+09 | 842.98 | 08-JUL-12:09 | 28.68 | 20.13 |
August | 0.791121E+10 | 18578.75 | 28-AUG-07:02 | 22.38 | 15.17 | 0.696550E+09 | 842.96 | 18-AUG-12:30 | 22.38 | 15.17 |
September | 0.724409E+10 | 15964.26 | 13-SEP-07:02 | 22.88 | 17.65 | 0.680079E+09 | 842.97 | 08-SEP-12:20 | 22.88 | 17.65 |
October | 0.552805E+10 | 18867.57 | 02-OCT-07:02 | 22.02 | 15.21 | 0.701763E+09 | 842.98 | 08-OCT-17:10 | 24.32 | 17.29 |
November | 0.284170E+10 | 15590.70 | 08-NOV-21:09 | 18.95 | 9.81 | 0.660396E+09 | 842.94 | 03-NOV-12:50 | 18.95 | 9.81 |
December | 0.132199E+10 | 2335.67 | 18-DEC-18:20 | 5.40 | -2.3 | 0.616912E+09 | 842.90 | 17-DEC-18:00 | 5.40 | -2.3 |
Annual Sum or Average | 0.560538E+11 | 0.801054E+10 | ||||||||
Minimum of Months | 0.132199E+10 | 2309.66 | 5.40 | -2.3 | 0.591373E+09 | 842.90 | 5.40 | -2.3 | ||
Maximum of Months | 0.807967E+10 | 19011.94 | 27.98 | 17.65 | 0.706258E+09 | 842.98 | 29.78 | 20.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113496E+10 | 1985.54 | 06-JAN-08:61 | -0.6 | -4.4 | 0.355783E+09 | 720.54 | 07-JAN-13:00 | 13.90 | 6.19 |
February | 0.113481E+10 | 2460.93 | 22-FEB-14:00 | 21.70 | 7.92 | 0.342541E+09 | 842.89 | 11-FEB-13:00 | 21.70 | 7.92 |
March | 0.149090E+10 | 2921.51 | 16-MAR-16:10 | 22.02 | 8.30 | 0.412028E+09 | 842.89 | 25-MAR-12:20 | 19.07 | 8.79 |
April | 0.297494E+10 | 5299.57 | 21-APR-14:00 | 32.20 | 15.21 | 0.409297E+09 | 842.91 | 29-APR-12:09 | 27.30 | 15.21 |
May | 0.457713E+10 | 14709.58 | 31-MAY-06:03 | 23.58 | 11.53 | 0.426078E+09 | 842.91 | 27-MAY-12:09 | 23.58 | 11.53 |
June | 0.592217E+10 | 20738.70 | 06-JUN-06:02 | 22.57 | 13.18 | 0.417316E+09 | 842.92 | 03-JUN-12:09 | 22.57 | 13.18 |
July | 0.615371E+10 | 19256.27 | 03-JUL-06:01 | 26.88 | 16.13 | 0.420429E+09 | 842.97 | 08-JUL-12:09 | 28.68 | 20.13 |
August | 0.612225E+10 | 19724.93 | 28-AUG-06:02 | 20.37 | 14.83 | 0.431908E+09 | 842.95 | 12-AUG-12:09 | 20.37 | 14.83 |
September | 0.547481E+10 | 16476.73 | 13-SEP-06:02 | 22.30 | 17.43 | 0.410885E+09 | 842.95 | 09-SEP-12:09 | 22.30 | 17.43 |
October | 0.395952E+10 | 19997.00 | 02-OCT-06:02 | 22.70 | 15.09 | 0.419902E+09 | 842.94 | 28-OCT-12:39 | 21.67 | 13.60 |
November | 0.202247E+10 | 4173.80 | 09-NOV-14:00 | 23.30 | 12.45 | 0.388099E+09 | 842.90 | 18-NOV-13:00 | 19.40 | 6.83 |
December | 0.107615E+10 | 2238.19 | 18-DEC-18:20 | 5.40 | -2.3 | 0.348906E+09 | 842.89 | 09-DEC-13:00 | 5.40 | -2.3 |
Annual Sum or Average | 0.420438E+11 | 0.478317E+10 | ||||||||
Minimum of Months | 0.107615E+10 | 1985.54 | -0.6 | -4.4 | 0.342541E+09 | 720.54 | 5.40 | -2.3 | ||
Maximum of Months | 0.615371E+10 | 20738.70 | 32.20 | 17.43 | 0.431908E+09 | 842.97 | 28.68 | 20.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104228E+10 | 1916.52 | 05-JAN-19:00 | 7.20 | -1.0 | 0.351823E+09 | 712.63 | 07-JAN-13:00 | 13.90 | 6.19 |
February | 0.105652E+10 | 2314.57 | 22-FEB-14:00 | 21.70 | 7.92 | 0.339657E+09 | 842.87 | 11-FEB-13:00 | 21.70 | 7.92 |
March | 0.139375E+10 | 2835.45 | 16-MAR-16:10 | 22.02 | 8.30 | 0.410370E+09 | 842.89 | 25-MAR-12:39 | 19.23 | 8.73 |
April | 0.293984E+10 | 5293.75 | 21-APR-14:00 | 32.20 | 15.21 | 0.409224E+09 | 842.91 | 29-APR-12:09 | 27.30 | 15.21 |
May | 0.459993E+10 | 15078.60 | 31-MAY-06:03 | 23.58 | 11.53 | 0.426079E+09 | 842.91 | 27-MAY-12:09 | 23.58 | 11.53 |
June | 0.597378E+10 | 20857.97 | 06-JUN-06:02 | 22.57 | 13.18 | 0.417320E+09 | 842.92 | 03-JUN-12:09 | 22.57 | 13.18 |
July | 0.620800E+10 | 19349.85 | 03-JUL-06:01 | 26.88 | 16.13 | 0.420434E+09 | 842.97 | 08-JUL-12:09 | 28.68 | 20.13 |
August | 0.617576E+10 | 19885.66 | 28-AUG-06:02 | 20.37 | 14.83 | 0.431913E+09 | 842.95 | 12-AUG-12:09 | 20.37 | 14.83 |
September | 0.551479E+10 | 16570.63 | 13-SEP-06:02 | 22.30 | 17.43 | 0.410888E+09 | 842.95 | 09-SEP-12:09 | 22.30 | 17.43 |
October | 0.395344E+10 | 20120.99 | 02-OCT-06:02 | 22.70 | 15.09 | 0.419891E+09 | 842.94 | 28-OCT-12:39 | 21.67 | 13.60 |
November | 0.193876E+10 | 4120.01 | 09-NOV-14:00 | 23.30 | 12.45 | 0.387262E+09 | 842.90 | 18-NOV-13:00 | 19.40 | 6.83 |
December | 0.992950E+09 | 2174.83 | 18-DEC-18:20 | 5.40 | -2.3 | 0.345463E+09 | 842.89 | 09-DEC-13:00 | 5.40 | -2.3 |
Annual Sum or Average | 0.417898E+11 | 0.477032E+10 | ||||||||
Minimum of Months | 0.992950E+09 | 1916.52 | 5.40 | -2.3 | 0.339657E+09 | 712.63 | 5.40 | -2.3 | ||
Maximum of Months | 0.620800E+10 | 20857.97 | 32.20 | 17.43 | 0.431913E+09 | 842.97 | 28.68 | 20.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.902782E+09 | 1870.77 | 05-JAN-19:00 | 7.20 | -1.0 | 0.345878E+09 | 702.42 | 03-JAN-17:10 | 7.20 | -1.0 |
February | 0.920616E+09 | 2274.71 | 08-FEB-19:00 | 5.00 | 0.53 | 0.334614E+09 | 840.36 | 11-FEB-13:00 | 18.90 | 6.65 |
March | 0.120307E+10 | 2616.50 | 16-MAR-16:10 | 22.02 | 8.30 | 0.406620E+09 | 842.89 | 25-MAR-12:00 | 19.40 | 8.67 |
April | 0.274110E+10 | 5145.05 | 21-APR-14:00 | 32.20 | 15.21 | 0.408855E+09 | 842.91 | 29-APR-12:09 | 27.30 | 15.21 |
May | 0.442259E+10 | 13858.24 | 31-MAY-06:03 | 23.58 | 11.53 | 0.426031E+09 | 842.91 | 27-MAY-12:09 | 23.58 | 11.53 |
June | 0.582188E+10 | 20640.83 | 06-JUN-06:02 | 22.57 | 13.18 | 0.417287E+09 | 842.92 | 03-JUN-12:09 | 22.57 | 13.18 |
July | 0.606656E+10 | 19212.76 | 03-JUL-06:01 | 26.88 | 16.13 | 0.420401E+09 | 842.97 | 08-JUL-12:09 | 28.68 | 20.13 |
August | 0.602946E+10 | 19683.39 | 28-AUG-06:02 | 20.37 | 14.83 | 0.431880E+09 | 842.95 | 12-AUG-12:09 | 20.37 | 14.83 |
September | 0.536551E+10 | 16344.53 | 13-SEP-06:02 | 22.30 | 17.43 | 0.410855E+09 | 842.95 | 09-SEP-12:09 | 22.30 | 17.43 |
October | 0.377898E+10 | 19881.09 | 02-OCT-06:02 | 22.70 | 15.09 | 0.419773E+09 | 842.94 | 28-OCT-12:39 | 21.67 | 13.60 |
November | 0.176099E+10 | 3942.11 | 09-NOV-14:00 | 23.30 | 12.45 | 0.385323E+09 | 842.90 | 18-NOV-13:00 | 19.40 | 6.83 |
December | 0.866024E+09 | 2112.73 | 18-DEC-19:00 | 5.00 | -2.3 | 0.339827E+09 | 839.78 | 09-DEC-13:00 | 5.00 | -2.3 |
Annual Sum or Average | 0.398796E+11 | 0.474734E+10 | ||||||||
Minimum of Months | 0.866024E+09 | 1870.77 | 5.00 | -2.3 | 0.334614E+09 | 702.42 | 5.00 | -2.3 | ||
Maximum of Months | 0.606656E+10 | 20640.83 | 32.20 | 17.43 | 0.431880E+09 | 842.97 | 28.68 | 20.13 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165523E+10 | 3416.36 | 07-JAN-11:40 | 8.67 | 2.79 | 0.115389E+10 | 1994.91 | 03-JAN-17:10 | 8.67 | 2.79 |
February | 0.162549E+10 | 4009.30 | 08-FEB-17:40 | 7.77 | 0.87 | 0.112638E+10 | 2247.77 | 11-FEB-15:00 | 20.00 | 6.94 |
March | 0.205222E+10 | 4916.11 | 16-MAR-14:50 | 22.80 | 8.82 | 0.137516E+10 | 2247.79 | 25-MAR-14:00 | 21.10 | 8.87 |
April | 0.463333E+10 | 9618.84 | 21-APR-14:30 | 32.20 | 15.35 | 0.140277E+10 | 2247.80 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.770252E+10 | 25395.71 | 30-MAY-07:03 | 25.78 | 12.49 | 0.145784E+10 | 2247.80 | 27-MAY-14:09 | 25.78 | 12.49 |
June | 0.102955E+11 | 34713.82 | 18-JUN-08:62 | 26.47 | 16.53 | 0.143020E+10 | 2247.86 | 03-JUN-14:30 | 26.47 | 16.53 |
July | 0.107122E+11 | 35220.43 | 03-JUL-07:01 | 27.98 | 16.41 | 0.143874E+10 | 2248.01 | 01-JUL-14:20 | 27.98 | 16.41 |
August | 0.106782E+11 | 35057.23 | 28-AUG-07:02 | 22.38 | 15.17 | 0.148061E+10 | 2247.85 | 12-AUG-14:09 | 22.38 | 15.17 |
September | 0.948958E+10 | 29133.51 | 13-SEP-07:02 | 22.88 | 17.65 | 0.141009E+10 | 2247.91 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.652845E+10 | 35222.34 | 02-OCT-07:02 | 22.02 | 15.21 | 0.143317E+10 | 2247.86 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.298744E+10 | 7141.86 | 09-NOV-14:00 | 23.30 | 12.45 | 0.129991E+10 | 2247.71 | 18-NOV-15:00 | 19.40 | 6.83 |
December | 0.156183E+10 | 4378.61 | 26-DEC-18:55 | 1.70 | -0.4 | 0.114194E+10 | 2153.12 | 09-DEC-15:20 | 1.70 | -0.4 |
Annual Sum or Average | 0.699220E+11 | 0.161507E+11 | ||||||||
Minimum of Months | 0.156183E+10 | 3416.36 | 1.70 | -0.4 | 0.112638E+10 | 1994.91 | 1.70 | -0.4 | ||
Maximum of Months | 0.107122E+11 | 35222.34 | 32.20 | 17.65 | 0.148061E+10 | 2248.01 | 30.10 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.746342E+09 | 1644.91 | 07-JAN-11:40 | 8.67 | 2.79 | 0.573749E+09 | 997.43 | 03-JAN-17:10 | 8.67 | 2.79 |
February | 0.735171E+09 | 1959.87 | 08-FEB-17:40 | 7.77 | 0.87 | 0.560171E+09 | 1123.76 | 11-FEB-15:00 | 20.00 | 6.94 |
March | 0.934898E+09 | 2443.09 | 16-MAR-15:00 | 22.80 | 8.72 | 0.683881E+09 | 1123.85 | 25-MAR-14:09 | 20.18 | 8.75 |
April | 0.232234E+10 | 4995.79 | 21-APR-14:40 | 32.20 | 15.40 | 0.700888E+09 | 1123.87 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.395997E+10 | 12851.91 | 30-MAY-07:03 | 25.78 | 12.49 | 0.728873E+09 | 1123.87 | 27-MAY-14:09 | 25.78 | 12.49 |
June | 0.533222E+10 | 17847.60 | 18-JUN-08:62 | 26.47 | 16.53 | 0.715059E+09 | 1123.90 | 03-JUN-14:20 | 26.47 | 16.53 |
July | 0.555161E+10 | 18115.44 | 03-JUL-07:01 | 27.98 | 16.41 | 0.719323E+09 | 1123.98 | 01-JUL-14:20 | 27.98 | 16.41 |
August | 0.552465E+10 | 18110.98 | 28-AUG-07:02 | 22.38 | 15.17 | 0.740262E+09 | 1123.89 | 12-AUG-14:09 | 22.38 | 15.17 |
September | 0.489905E+10 | 14992.79 | 13-SEP-07:02 | 22.88 | 17.65 | 0.705005E+09 | 1123.92 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.332159E+10 | 18186.55 | 02-OCT-07:02 | 22.02 | 15.21 | 0.716430E+09 | 1123.90 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.143457E+10 | 3630.33 | 09-NOV-14:00 | 23.30 | 12.45 | 0.648543E+09 | 1123.83 | 18-NOV-15:09 | 19.40 | 6.83 |
December | 0.707675E+09 | 1991.31 | 27-DEC-13:55 | 6.70 | 2.04 | 0.568345E+09 | 1062.27 | 09-DEC-15:20 | 6.70 | 2.04 |
Annual Sum or Average | 0.354701E+11 | 0.806053E+10 | ||||||||
Minimum of Months | 0.707675E+09 | 1644.91 | 6.70 | 0.87 | 0.560171E+09 | 997.43 | 6.70 | 2.04 | ||
Maximum of Months | 0.555161E+10 | 18186.55 | 32.20 | 17.65 | 0.740262E+09 | 1123.98 | 30.10 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.705910E+09 | 1617.63 | 07-JAN-11:50 | 9.03 | 3.04 | 0.571120E+09 | 997.43 | 03-JAN-17:19 | 9.03 | 3.04 |
February | 0.689598E+09 | 1913.19 | 08-FEB-17:30 | 8.05 | 0.97 | 0.557645E+09 | 1118.26 | 11-FEB-15:00 | 20.00 | 6.94 |
March | 0.875933E+09 | 2346.85 | 16-MAR-15:00 | 22.80 | 8.72 | 0.680643E+09 | 1123.85 | 25-MAR-14:09 | 20.18 | 8.75 |
April | 0.225503E+10 | 4938.82 | 21-APR-14:40 | 32.20 | 15.40 | 0.700336E+09 | 1123.87 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.390753E+10 | 12454.18 | 30-MAY-07:03 | 25.78 | 12.49 | 0.728855E+09 | 1123.87 | 27-MAY-14:09 | 25.78 | 12.49 |
June | 0.529007E+10 | 17774.84 | 18-JUN-08:62 | 26.47 | 16.53 | 0.715054E+09 | 1123.90 | 03-JUN-14:20 | 26.47 | 16.53 |
July | 0.551256E+10 | 18042.48 | 03-JUL-07:01 | 27.98 | 16.41 | 0.719317E+09 | 1123.98 | 01-JUL-14:20 | 27.98 | 16.41 |
August | 0.548709E+10 | 18025.06 | 28-AUG-07:02 | 22.38 | 15.17 | 0.740257E+09 | 1123.89 | 12-AUG-14:09 | 22.38 | 15.17 |
September | 0.486130E+10 | 14915.88 | 13-SEP-07:02 | 22.88 | 17.65 | 0.705000E+09 | 1123.92 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.326850E+10 | 18089.26 | 02-OCT-07:02 | 22.02 | 15.21 | 0.716253E+09 | 1123.90 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.137527E+10 | 3551.96 | 09-NOV-14:00 | 23.30 | 12.45 | 0.646681E+09 | 1123.83 | 18-NOV-15:09 | 19.40 | 6.83 |
December | 0.667361E+09 | 1515.58 | 30-DEC-12:00 | 6.70 | 2.03 | 0.566434E+09 | 1054.75 | 09-DEC-15:20 | 6.70 | 2.03 |
Annual Sum or Average | 0.348962E+11 | 0.804759E+10 | ||||||||
Minimum of Months | 0.667361E+09 | 1515.58 | 6.70 | 0.97 | 0.557645E+09 | 997.43 | 6.70 | 2.03 | ||
Maximum of Months | 0.551256E+10 | 18089.26 | 32.20 | 17.65 | 0.740257E+09 | 1123.98 | 30.10 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.585045E+09 | 1783.47 | 27-JAN-13:05 | 7.88 | -0.6 | 0.565372E+09 | 981.73 | 03-JAN-17:19 | 7.88 | -0.6 |
February | 0.564683E+09 | 1816.33 | 08-FEB-18:50 | 5.37 | 0.58 | 0.551248E+09 | 1096.52 | 11-FEB-15:00 | 20.00 | 6.94 |
March | 0.730941E+09 | 2120.56 | 16-MAR-15:00 | 22.80 | 8.72 | 0.672366E+09 | 1123.86 | 25-MAR-14:39 | 20.73 | 8.83 |
April | 0.209092E+10 | 4823.50 | 21-APR-14:40 | 32.20 | 15.40 | 0.698597E+09 | 1123.87 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.379616E+10 | 10775.66 | 30-MAY-07:03 | 25.78 | 12.49 | 0.728776E+09 | 1123.87 | 27-MAY-14:09 | 25.78 | 12.49 |
June | 0.525793E+10 | 17769.29 | 18-JUN-08:62 | 26.47 | 16.53 | 0.715051E+09 | 1123.89 | 03-JUN-14:20 | 26.47 | 16.53 |
July | 0.550805E+10 | 18053.48 | 03-JUL-07:01 | 27.98 | 16.41 | 0.719314E+09 | 1123.97 | 01-JUL-14:20 | 27.98 | 16.41 |
August | 0.548905E+10 | 18027.69 | 07-AUG-07:01 | 26.47 | 16.94 | 0.740258E+09 | 1123.89 | 12-AUG-14:09 | 31.97 | 18.69 |
September | 0.484695E+10 | 14881.34 | 13-SEP-07:02 | 22.88 | 17.65 | 0.704997E+09 | 1123.92 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.315356E+10 | 18066.13 | 02-OCT-07:02 | 22.02 | 15.21 | 0.715579E+09 | 1123.90 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.124547E+10 | 3404.88 | 09-NOV-14:00 | 23.30 | 12.45 | 0.641481E+09 | 1123.84 | 18-NOV-15:09 | 19.40 | 6.83 |
December | 0.558955E+09 | 1740.63 | 02-DEC-15:10 | 8.80 | 2.55 | 0.562061E+09 | 1039.03 | 09-DEC-15:20 | 17.03 | 6.92 |
Annual Sum or Average | 0.338277E+11 | 0.801510E+10 | ||||||||
Minimum of Months | 0.558955E+09 | 1740.63 | 5.37 | -0.6 | 0.551248E+09 | 981.73 | 7.88 | -0.6 | ||
Maximum of Months | 0.550805E+10 | 18066.13 | 32.20 | 17.65 | 0.740258E+09 | 1123.97 | 31.97 | 18.69 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358151E+09 | 1425.31 | 27-JAN-15:45 | 9.40 | 0.75 | 0.559720E+09 | 956.97 | 03-JAN-17:19 | 9.40 | 0.75 |
February | 0.326128E+09 | 1458.71 | 08-FEB-16:00 | 10.00 | 2.00 | 0.543427E+09 | 1065.30 | 18-FEB-15:00 | 20.00 | 8.60 |
March | 0.512657E+09 | 1909.79 | 16-MAR-14:20 | 22.80 | 9.14 | 0.662671E+09 | 1123.86 | 25-MAR-14:00 | 21.10 | 8.87 |
April | 0.216487E+10 | 5275.90 | 21-APR-14:20 | 32.20 | 15.31 | 0.696937E+09 | 1123.87 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.429349E+10 | 8421.51 | 31-MAY-07:03 | 25.37 | 12.75 | 0.728728E+09 | 1123.87 | 27-MAY-14:09 | 25.37 | 12.75 |
June | 0.620825E+10 | 19660.32 | 18-JUN-08:62 | 26.47 | 16.53 | 0.715143E+09 | 1123.90 | 03-JUN-14:20 | 26.47 | 16.53 |
July | 0.660005E+10 | 19941.77 | 03-JUL-07:01 | 27.98 | 16.41 | 0.719462E+09 | 1124.00 | 01-JUL-14:20 | 27.98 | 16.41 |
August | 0.661424E+10 | 19818.28 | 28-AUG-07:02 | 22.38 | 15.17 | 0.740393E+09 | 1123.90 | 05-AUG-14:20 | 22.38 | 15.17 |
September | 0.583622E+10 | 16300.24 | 13-SEP-07:02 | 22.88 | 17.65 | 0.705127E+09 | 1123.92 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.342568E+10 | 19983.81 | 02-OCT-07:02 | 22.02 | 15.21 | 0.713702E+09 | 1123.89 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.111568E+10 | 3626.93 | 09-NOV-14:00 | 23.30 | 12.45 | 0.635244E+09 | 1123.85 | 18-NOV-15:00 | 19.40 | 6.83 |
December | 0.356145E+09 | 1526.14 | 29-DEC-13:05 | 8.98 | 2.64 | 0.558809E+09 | 1029.86 | 09-DEC-15:20 | 8.98 | 2.64 |
Annual Sum or Average | 0.378116E+11 | 0.797936E+10 | ||||||||
Minimum of Months | 0.326128E+09 | 1425.31 | 8.98 | 0.75 | 0.543427E+09 | 956.97 | 8.98 | 0.75 | ||
Maximum of Months | 0.661424E+10 | 19983.81 | 32.20 | 17.65 | 0.740393E+09 | 1124.00 | 30.10 | 18.50 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.534561E+09 | 55670.88 | 06-JAN-08:61 | -0.6 |
February | 0.382911E+09 | 55686.31 | 03-FEB-08:61 | -2.0 |
March | 0.248727E+09 | 55676.78 | 02-MAR-08:61 | -0.9 |
April | 79448425.50 | 918.06 | 11-APR-07:15 | 5.97 |
May | 31421313.86 | 1679.34 | 31-MAY-07:05 | 25.37 |
June | 31703563.59 | 1938.70 | 17-JUN-07:04 | 24.78 |
July | 30222540.25 | 1858.64 | 06-JUL-07:05 | 23.77 |
August | 31008008.16 | 1925.45 | 24-AUG-07:04 | 23.95 |
September | 27470250.93 | 1828.21 | 22-SEP-07:05 | 21.47 |
October | 46047124.41 | 1948.02 | 02-OCT-07:04 | 22.02 |
November | 0.135637E+09 | 55649.81 | 28-NOV-08:61 | 2.48 |
December | 0.687763E+09 | 55689.63 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.226692E+10 | |||
Minimum of Months | 27470250.93 | 918.06 | -2.3 | |
Maximum of Months | 0.687763E+09 | 55689.63 | 25.37 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 90426447.59 | 28571.61 | 27-JAN-08:61 | -3.5 |
February | 74778597.48 | 28577.99 | 03-FEB-08:61 | -2.0 |
March | 63455947.61 | 28577.66 | 02-MAR-08:61 | -0.9 |
April | 31155057.39 | 554.22 | 20-APR-07:10 | 20.60 |
May | 11374918.39 | 959.26 | 31-MAY-07:05 | 25.37 |
June | 16730643.58 | 1041.52 | 06-JUN-07:05 | 24.78 |
July | 14225881.69 | 1024.68 | 12-JUL-07:05 | 23.27 |
August | 15505152.36 | 1046.02 | 11-AUG-07:05 | 24.18 |
September | 14092591.76 | 995.82 | 22-SEP-07:05 | 21.47 |
October | 11014735.94 | 1046.88 | 02-OCT-07:04 | 22.02 |
November | 42457942.18 | 22552.64 | 28-NOV-08:61 | 2.48 |
December | 0.135303E+09 | 28571.27 | 29-DEC-08:61 | -0.1 |
Annual Sum or Average | 0.520521E+09 | |||
Minimum of Months | 11014735.94 | 554.22 | -3.5 | |
Maximum of Months | 0.135303E+09 | 28577.99 | 25.37 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135401E+09 | 28388.94 | 28-JAN-07:01 | -2.9 |
February | 90368772.47 | 28158.23 | 03-FEB-07:02 | -5.1 |
March | 68632502.38 | 27404.46 | 02-MAR-07:02 | -1.6 |
April | 60571210.57 | 1084.35 | 30-APR-16:12 | 30.40 |
May | 76100776.72 | 1367.04 | 29-MAY-16:12 | 33.13 |
June | 0.119948E+09 | 1804.98 | 18-JUN-16:11 | 37.20 |
July | 0.104230E+09 | 1907.17 | 02-JUL-16:11 | 38.13 |
August | 91852228.10 | 1685.44 | 06-AUG-16:11 | 36.10 |
September | 52961617.12 | 1291.28 | 17-SEP-16:12 | 32.43 |
October | 22156347.08 | 1191.98 | 01-OCT-16:12 | 31.50 |
November | 51539928.15 | 17432.73 | 28-NOV-07:02 | 0.87 |
December | 0.206467E+09 | 28405.69 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.108023E+10 | |||
Minimum of Months | 22156347.08 | 1084.35 | -5.1 | |
Maximum of Months | 0.206467E+09 | 28405.69 | 38.13 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171941E+09 | 28482.00 | 28-JAN-07:01 | -2.9 |
February | 0.106931E+09 | 28258.77 | 02-FEB-07:02 | -4.0 |
March | 73338350.39 | 28262.39 | 02-MAR-07:02 | -1.6 |
April | 62498001.02 | 1085.87 | 30-APR-16:12 | 30.40 |
May | 76364306.10 | 1368.40 | 29-MAY-16:12 | 33.13 |
June | 0.119803E+09 | 1806.14 | 18-JUN-16:11 | 37.20 |
July | 0.103752E+09 | 1908.51 | 02-JUL-16:11 | 38.13 |
August | 91334402.30 | 1686.61 | 06-AUG-16:11 | 36.10 |
September | 52917590.52 | 1292.84 | 17-SEP-16:12 | 32.43 |
October | 23200214.51 | 1193.64 | 01-OCT-16:12 | 31.50 |
November | 57658467.76 | 20058.79 | 28-NOV-07:02 | 0.87 |
December | 0.248545E+09 | 28498.76 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.118828E+10 | |||
Minimum of Months | 23200214.51 | 1085.87 | -4.0 | |
Maximum of Months | 0.248545E+09 | 28498.76 | 38.13 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243009E+09 | 28324.16 | 28-JAN-07:01 | -2.9 |
February | 0.140717E+09 | 28104.35 | 02-FEB-07:02 | -4.0 |
March | 89019847.53 | 28107.95 | 02-MAR-07:02 | -1.6 |
April | 69073413.31 | 1085.98 | 30-APR-16:12 | 30.40 |
May | 79599297.81 | 1368.54 | 29-MAY-16:12 | 33.13 |
June | 0.120489E+09 | 1805.57 | 18-JUN-16:11 | 37.20 |
July | 0.104698E+09 | 1908.00 | 02-JUL-16:11 | 38.13 |
August | 92198786.23 | 1685.85 | 06-AUG-16:11 | 36.10 |
September | 53557332.84 | 1292.40 | 17-SEP-16:12 | 32.43 |
October | 28525747.74 | 1193.53 | 01-OCT-16:12 | 31.50 |
November | 68392574.04 | 22976.12 | 28-NOV-07:02 | 0.87 |
December | 0.329122E+09 | 28340.74 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.141840E+10 | |||
Minimum of Months | 28525747.74 | 1085.98 | -4.0 | |
Maximum of Months | 0.329122E+09 | 28340.74 | 38.13 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.559912E+09 | 52938.80 | 06-JAN-08:61 | -0.6 |
February | 0.332462E+09 | 52950.14 | 02-FEB-08:61 | -1.7 |
March | 0.213174E+09 | 52950.48 | 02-MAR-08:61 | -0.9 |
April | 0.108777E+09 | 2138.47 | 30-APR-16:12 | 30.40 |
May | 86987818.90 | 2793.12 | 21-MAY-16:02 | 33.57 |
June | 92634063.85 | 3661.04 | 18-JUN-16:11 | 37.20 |
July | 0.104033E+09 | 3882.34 | 02-JUL-16:02 | 38.22 |
August | 92371716.48 | 3405.81 | 06-AUG-16:11 | 36.10 |
September | 61221266.74 | 2573.58 | 17-SEP-16:12 | 32.43 |
October | 58251854.98 | 2366.39 | 01-OCT-16:12 | 31.50 |
November | 0.140795E+09 | 52928.07 | 28-NOV-08:61 | 2.48 |
December | 0.722529E+09 | 52957.52 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.257315E+10 | |||
Minimum of Months | 58251854.98 | 2138.47 | -2.3 | |
Maximum of Months | 0.722529E+09 | 52957.52 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.341482E+09 | 27314.17 | 06-JAN-08:61 | -0.6 |
February | 0.199783E+09 | 27319.99 | 02-FEB-08:61 | -1.7 |
March | 0.126733E+09 | 27320.24 | 02-MAR-08:61 | -0.9 |
April | 59940477.80 | 1095.61 | 30-APR-16:12 | 30.40 |
May | 45788994.74 | 1410.71 | 21-MAY-16:02 | 33.57 |
June | 47719697.34 | 1856.67 | 18-JUN-16:11 | 37.20 |
July | 52416611.43 | 1965.95 | 02-JUL-16:11 | 38.13 |
August | 47273524.61 | 1728.76 | 06-AUG-16:11 | 36.10 |
September | 32374511.27 | 1312.34 | 17-SEP-16:12 | 32.43 |
October | 32820696.80 | 1207.85 | 01-OCT-16:12 | 31.50 |
November | 82119611.97 | 27308.04 | 28-NOV-08:61 | 2.48 |
December | 0.432972E+09 | 27323.41 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.150143E+10 | |||
Minimum of Months | 32374511.27 | 1095.61 | -2.3 | |
Maximum of Months | 0.432972E+09 | 27323.41 | 38.13 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382015E+09 | 27209.61 | 06-JAN-08:61 | -0.6 |
February | 0.220918E+09 | 27215.22 | 02-FEB-08:61 | -1.7 |
March | 0.144696E+09 | 27215.46 | 02-MAR-08:61 | -0.9 |
April | 61013255.48 | 1094.60 | 30-APR-16:12 | 30.40 |
May | 46358087.15 | 1411.24 | 21-MAY-16:02 | 33.57 |
June | 47670291.30 | 1855.40 | 18-JUN-16:11 | 37.20 |
July | 52570946.43 | 1964.83 | 02-JUL-16:11 | 38.13 |
August | 47267452.37 | 1727.34 | 06-AUG-16:11 | 36.10 |
September | 32156368.38 | 1310.91 | 17-SEP-16:12 | 32.43 |
October | 34084759.03 | 1206.54 | 01-OCT-16:12 | 31.50 |
November | 85772671.85 | 27203.51 | 28-NOV-08:61 | 2.48 |
December | 0.463524E+09 | 27218.54 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.161805E+10 | |||
Minimum of Months | 32156368.38 | 1094.60 | -2.3 | |
Maximum of Months | 0.463524E+09 | 27218.54 | 38.13 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.522951E+09 | 27235.95 | 06-JAN-08:61 | -0.6 |
February | 0.315005E+09 | 27242.05 | 02-FEB-08:61 | -1.7 |
March | 0.219381E+09 | 27242.60 | 02-MAR-08:61 | -0.9 |
April | 65990419.84 | 3954.16 | 01-APR-07:03 | 11.02 |
May | 48366715.25 | 1413.50 | 21-MAY-16:02 | 33.57 |
June | 47460757.55 | 1856.27 | 18-JUN-16:11 | 37.20 |
July | 52582734.17 | 1964.96 | 02-JUL-16:11 | 38.13 |
August | 47241803.57 | 1727.51 | 06-AUG-16:11 | 36.10 |
September | 33191899.91 | 1312.08 | 17-SEP-16:12 | 32.43 |
October | 38617800.24 | 1208.95 | 01-OCT-16:12 | 31.50 |
November | 0.114204E+09 | 27229.48 | 28-NOV-08:61 | 2.48 |
December | 0.603609E+09 | 27245.91 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.210860E+10 | |||
Minimum of Months | 33191899.91 | 1208.95 | -2.3 | |
Maximum of Months | 0.603609E+09 | 27245.91 | 38.13 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110527E+10 | 30232.59 | 06-JAN-08:61 | -0.6 |
February | 0.715809E+09 | 30243.69 | 03-FEB-08:61 | -2.0 |
March | 0.559413E+09 | 30240.73 | 02-MAR-08:61 | -0.9 |
April | 93011498.58 | 22542.15 | 12-APR-07:02 | 7.35 |
May | 53470541.32 | 1441.42 | 29-MAY-16:12 | 33.13 |
June | 45420572.10 | 1893.75 | 18-JUN-16:11 | 37.20 |
July | 51711724.39 | 1997.74 | 02-JUL-16:11 | 38.13 |
August | 46638851.43 | 1760.36 | 06-AUG-16:11 | 36.10 |
September | 35380659.54 | 1349.11 | 17-SEP-16:12 | 32.43 |
October | 47473727.09 | 1246.81 | 01-OCT-16:12 | 31.50 |
November | 0.246360E+09 | 30219.49 | 28-NOV-08:61 | 2.48 |
December | 0.113042E+10 | 30250.46 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.413037E+10 | |||
Minimum of Months | 35380659.54 | 1246.81 | -2.3 | |
Maximum of Months | 0.113042E+10 | 30250.46 | 38.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.549253E+10 | 3421.96 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.496476E+10 | 3421.96 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.549777E+10 | 3421.96 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.532115E+10 | 3421.96 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.549253E+10 | 3421.96 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.532179E+10 | 3421.96 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.549708E+10 | 3421.96 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.549285E+10 | 3421.96 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.532602E+10 | 3421.96 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.549253E+10 | 3421.96 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.530585E+10 | 3421.96 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.550226E+10 | 3421.96 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.647071E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.496476E+10 | 3421.96 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.550226E+10 | 3421.96 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.334781E+10 | 2090.38 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.302613E+10 | 2090.38 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.335104E+10 | 2090.38 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.324334E+10 | 2090.38 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.334781E+10 | 2090.38 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.324377E+10 | 2090.38 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.335056E+10 | 2090.38 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.334803E+10 | 2090.38 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.324631E+10 | 2090.38 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.334781E+10 | 2090.38 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.323401E+10 | 2090.38 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.335375E+10 | 2090.38 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.394404E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.302613E+10 | 2090.38 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.335375E+10 | 2090.38 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.241466E+10 | 2078.11 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.218750E+10 | 2078.11 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.247235E+10 | 2078.11 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.234375E+10 | 2078.11 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.244351E+10 | 2078.11 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.238702E+10 | 2078.11 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.240024E+10 | 2078.11 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.247235E+10 | 2078.11 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.234375E+10 | 2078.11 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.241466E+10 | 2078.11 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.234375E+10 | 2078.11 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.240024E+10 | 2078.11 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.286238E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.218750E+10 | 2078.11 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.247235E+10 | 2078.11 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257456E+10 |
February | 0.305697E+10 | 0.496476E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187983E+10 |
March | 0.335708E+10 | 0.549777E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4486640.23 | 0.167222E+10 |
April | 0.327081E+10 | 0.532115E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420080E+09 | 0.705429E+09 |
May | 0.336680E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100305E+10 | 0.248653E+09 |
June | 0.325380E+10 | 0.532179E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169017E+10 | 77188721.80 |
July | 0.339353E+10 | 0.549708E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153946E+10 | 51889630.47 |
August | 0.334857E+10 | 0.549285E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130055E+10 | 0.109665E+09 |
September | 0.327932E+10 | 0.532602E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934375E+09 | 0.131411E+09 |
October | 0.338624E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226051E+09 | 0.783098E+09 |
November | 0.327446E+10 | 0.530585E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 925.12 | 0.200982E+10 |
December | 0.340325E+10 | 0.550226E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267514E+10 |
Annual Sum or Average | 0.397770E+11 | 0.647071E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711822E+10 | 0.129189E+11 |
Minimum of Months | 0.305697E+10 | 0.496476E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51889630.47 |
Maximum of Months | 0.340325E+10 | 0.550226E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169017E+10 | 0.267514E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131077E+10 |
February | 0.152844E+10 | 0.302613E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937659E+09 |
March | 0.167849E+10 | 0.335104E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2423270.64 | 0.809111E+09 |
April | 0.163536E+10 | 0.324334E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225045E+09 | 0.307403E+09 |
May | 0.168335E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534697E+09 | 89478001.63 |
June | 0.162685E+10 | 0.324377E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902150E+09 | 25119386.69 |
July | 0.169671E+10 | 0.335056E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.827271E+09 | 16733155.16 |
August | 0.167424E+10 | 0.334803E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701486E+09 | 39780659.57 |
September | 0.163961E+10 | 0.324631E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512539E+09 | 47200621.13 |
October | 0.169307E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123301E+09 | 0.351408E+09 |
November | 0.163718E+10 | 0.323401E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 503.07 | 0.986917E+09 |
December | 0.170157E+10 | 0.335375E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138199E+10 |
Annual Sum or Average | 0.198880E+11 | 0.394404E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382891E+10 | 0.630357E+10 |
Minimum of Months | 0.152844E+10 | 0.302613E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16733155.16 |
Maximum of Months | 0.170157E+10 | 0.335375E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902150E+09 | 0.138199E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132147E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957752E+09 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.20 | 0.841049E+09 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219061E+09 | 0.326321E+09 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526797E+09 | 98816792.95 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898200E+09 | 28402830.03 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818784E+09 | 22100834.81 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695040E+09 | 43516489.42 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504558E+09 | 56313970.11 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119864E+09 | 0.373653E+09 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 503.07 | 0.101507E+10 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138943E+10 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378473E+10 | 0.647389E+10 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22100834.81 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898200E+09 | 0.138943E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130555E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.946212E+09 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.20 | 0.833591E+09 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219120E+09 | 0.325550E+09 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526614E+09 | 99050351.54 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897699E+09 | 28852159.60 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818227E+09 | 22587784.77 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694649E+09 | 43982419.07 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504479E+09 | 56628516.16 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119825E+09 | 0.373575E+09 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 503.07 | 0.101120E+10 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137545E+10 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378303E+10 | 0.642223E+10 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22587784.77 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897699E+09 | 0.137545E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128357E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927741E+09 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.20 | 0.819246E+09 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219486E+09 | 0.322429E+09 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527249E+09 | 97344032.19 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898553E+09 | 27902095.60 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818993E+09 | 21675046.41 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695197E+09 | 43086483.90 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504639E+09 | 55837412.44 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119924E+09 | 0.371884E+09 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 503.07 | 0.100352E+10 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135431E+10 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378647E+10 | 0.632854E+10 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21675046.41 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898553E+09 | 0.135431E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.241466E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231222E+10 |
February | 0.313522E+10 | 0.218750E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167270E+10 |
March | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4361872.63 | 0.148415E+10 |
April | 0.338259E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397728E+09 | 0.602215E+09 |
May | 0.349753E+10 | 0.244351E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.955547E+09 | 0.190361E+09 |
June | 0.343071E+10 | 0.238702E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162767E+10 | 54840453.45 |
July | 0.344942E+10 | 0.240024E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148137E+10 | 43157407.66 |
August | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125594E+10 | 84711848.33 |
September | 0.338259E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907575E+09 | 0.110234E+09 |
October | 0.344359E+10 | 0.241466E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216067E+09 | 0.697318E+09 |
November | 0.331698E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 890.83 | 0.183080E+10 |
December | 0.344942E+10 | 0.240024E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243670E+10 |
Annual Sum or Average | 0.410346E+11 | 0.286238E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684626E+10 | 0.115194E+11 |
Minimum of Months | 0.313522E+10 | 0.218750E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43157407.66 |
Maximum of Months | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162767E+10 | 0.243670E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125590E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902795E+09 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.20 | 0.795854E+09 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220847E+09 | 0.320565E+09 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530056E+09 | 98127799.61 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902673E+09 | 27474123.51 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822393E+09 | 21464138.61 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697586E+09 | 43639682.68 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505354E+09 | 56928589.65 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120212E+09 | 0.374787E+09 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.56 | 0.994423E+09 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132941E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380155E+10 | 0.622137E+10 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21464138.61 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902673E+09 | 0.132941E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124964E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.896939E+09 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.22 | 0.788627E+09 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221007E+09 | 0.318748E+09 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530233E+09 | 97651936.41 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902845E+09 | 27284531.91 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822558E+09 | 21300017.15 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697694E+09 | 43493673.32 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505396E+09 | 56772678.37 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120241E+09 | 0.373996E+09 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 0.990075E+09 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132480E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380240E+10 | 0.618932E+10 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21300017.15 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902845E+09 | 0.132480E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123481E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881039E+09 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.56 | 0.769381E+09 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221409E+09 | 0.312732E+09 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530662E+09 | 95775543.27 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903072E+09 | 26688326.02 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822654E+09 | 20875677.64 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697695E+09 | 43158665.49 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505399E+09 | 56453409.27 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120286E+09 | 0.371212E+09 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.56 | 0.977567E+09 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131325E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380360E+10 | 0.610295E+10 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20875677.64 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903072E+09 | 0.131325E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152622E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112888E+10 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2547934.85 | 0.101643E+10 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237780E+09 | 0.459199E+09 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574432E+09 | 0.176255E+09 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976198E+09 | 56970174.57 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876911E+09 | 46948967.96 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738390E+09 | 83018430.62 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517574E+09 | 0.109143E+09 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124530E+09 | 0.526623E+09 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 522.19 | 0.123418E+10 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158266E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404836E+10 | 0.794652E+10 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46948967.96 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976198E+09 | 0.158266E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 3421.96 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4759.78 | 26-JAN-12:10 |
February | 4050.04 | 03-FEB-13:09 | 3421.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4456.18 | 08-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 3421.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 295.61 | 22-MAR-13:00 | 4306.07 | 01-MAR-18:00 |
April | 4050.04 | 01-APR-12:09 | 3421.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2329.01 | 21-APR-15:00 | 2921.20 | 06-APR-12:00 |
May | 4050.04 | 05-MAY-12:09 | 3421.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2978.24 | 19-MAY-14:00 | 1256.29 | 01-MAY-12:00 |
June | 4050.04 | 02-JUN-12:09 | 3421.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3757.00 | 02-JUN-16:00 | 751.63 | 28-JUN-02:00 |
July | 4050.04 | 01-JUL-12:09 | 3421.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3667.80 | 03-JUL-17:00 | 605.29 | 08-JUL-15:00 |
August | 4050.04 | 04-AUG-12:09 | 3421.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3392.53 | 07-AUG-16:00 | 810.91 | 14-AUG-11:10 |
September | 4050.04 | 01-SEP-12:09 | 3421.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.35 | 19-SEP-14:00 | 1642.13 | 23-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 3421.96 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2302.69 | 01-OCT-15:00 | 2863.63 | 24-OCT-11:10 |
November | 4050.04 | 03-NOV-12:09 | 3421.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 03-NOV-16:00 | 4314.21 | 26-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 3421.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5586.01 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.29 | |||||
Maximum of Months | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3757.00 | 5586.01 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2090.38 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2614.12 | 26-JAN-12:10 |
February | 2024.96 | 03-FEB-13:09 | 2090.38 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2383.81 | 08-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2090.38 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2090.38 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1670.11 | 11-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 2090.38 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2024.96 | 02-JUN-12:09 | 2090.38 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.34 | 02-JUN-16:00 | 223.79 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 2090.38 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.12 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2024.96 | 04-AUG-12:09 | 2090.38 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.05 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 2090.38 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.74 | 23-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 2090.38 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1597.30 | 24-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 2090.38 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2090.38 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.79 | |||||
Maximum of Months | 2024.96 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.34 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2613.89 | 26-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2368.73 | 08-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1675.19 | 11-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.35 | 02-JUN-16:00 | 229.74 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.32 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.05 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.72 | 23-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1598.97 | 24-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.74 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.35 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2613.89 | 26-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2350.55 | 08-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1669.47 | 11-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.35 | 02-JUN-16:00 | 231.06 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.32 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.05 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.72 | 23-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1598.89 | 24-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.06 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.35 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2613.89 | 26-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2313.52 | 08-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1643.78 | 11-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.35 | 02-JUN-16:00 | 227.95 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.32 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.05 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.71 | 23-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1593.96 | 24-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.46 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.95 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.35 | 3072.46 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2078.11 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4695.52 | 26-JAN-12:10 |
February | 5400.05 | 04-FEB-15:09 | 2078.11 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4041.17 | 08-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 2078.11 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 285.58 | 22-MAR-13:00 | 4193.35 | 01-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 2078.11 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2194.06 | 21-APR-15:00 | 2844.27 | 11-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 2078.11 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2853.75 | 19-MAY-14:00 | 1206.11 | 01-MAY-12:00 |
June | 5400.05 | 03-JUN-14:09 | 2078.11 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3682.82 | 02-JUN-16:00 | 441.13 | 28-JUN-02:00 |
July | 5400.05 | 01-JUL-14:09 | 2078.11 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3564.44 | 03-JUL-17:00 | 585.90 | 08-JUL-15:00 |
August | 5400.05 | 05-AUG-14:09 | 2078.11 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3310.43 | 07-AUG-16:00 | 804.87 | 14-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 2078.11 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2472.51 | 19-SEP-14:00 | 1605.63 | 23-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 2078.11 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2247.00 | 01-OCT-15:00 | 2834.95 | 24-OCT-11:10 |
November | 5400.05 | 04-NOV-14:09 | 2078.11 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 | 08-NOV-15:00 | 4192.77 | 26-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2078.11 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5518.47 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.13 | |||||
Maximum of Months | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3682.82 | 5518.47 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2613.89 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2231.57 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1569.90 | 11-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.78 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.31 | 02-JUN-16:00 | 219.34 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.04 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.00 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.70 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1575.26 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 08-NOV-15:00 | 2329.09 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.34 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.31 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2613.89 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2231.42 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1557.47 | 11-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.78 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.31 | 02-JUN-16:00 | 218.68 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.03 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.00 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.70 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1571.05 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 08-NOV-15:00 | 2329.09 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.68 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.31 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2613.89 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2231.40 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1522.38 | 11-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.79 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.31 | 02-JUN-16:00 | 216.99 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.03 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.00 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.70 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1548.04 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 08-NOV-15:00 | 2329.09 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.99 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.31 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2678.15 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2519.17 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 168.54 | 22-MAR-13:00 | 2442.80 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.25 | 21-APR-15:00 | 1652.60 | 06-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.53 | 19-MAY-14:00 | 718.98 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2122.45 | 02-JUN-16:00 | 510.08 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2083.25 | 03-JUL-17:00 | 344.67 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1922.03 | 07-AUG-16:00 | 464.06 | 14-AUG-01:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1410.22 | 19-SEP-14:00 | 929.12 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1304.62 | 01-OCT-15:00 | 1512.80 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 03-NOV-16:00 | 2450.53 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3140.15 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.67 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2122.45 | 3140.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4005.75 | 04-JAN-22:00 | 2025.02 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.23 |
February | 4783.63 | 08-FEB-20:00 | 3375.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.60 |
March | 5421.86 | 16-MAR-17:10 | 3375.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.09 |
April | 10657.28 | 30-APR-16:05 | 16200.15 | 13687.83 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1709.19 | 0.00 |
May | 23089.86 | 31-MAY-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 53.51 | 0.00 |
June | 35552.65 | 17-JUN-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 25.84 | 0.00 |
July | 36986.91 | 03-JUL-07:01 | 2700.03 | 600.00 | 597.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.19 | 0.00 |
August | 35748.44 | 07-AUG-07:01 | 2700.03 | 600.00 | 597.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.53 | 0.00 |
September | 30699.32 | 13-SEP-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.12 |
October | 36802.29 | 02-OCT-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.38 |
November | 7949.54 | 09-NOV-15:00 | 2700.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.88 |
December | 4354.15 | 18-DEC-18:20 | 3375.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4005.75 | 0.00 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36986.91 | 16200.15 | 13687.83 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1709.19 | 1176.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2309.66 | 01-JAN-18:10 | 4049.92 | 4180.76 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.95 |
February | 15307.59 | 19-FEB-18:47 | 12149.77 | 12542.28 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.32 |
March | 15527.94 | 19-MAR-17:08 | 16199.69 | 16723.04 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.98 |
April | 15671.60 | 15-APR-21:00 | 7087.36 | 14632.66 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15204.14 | 06-MAY-21:45 | 8099.84 | 16723.04 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
June | 18437.34 | 17-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.77 | 0.00 |
July | 19011.94 | 03-JUL-07:01 | 1349.97 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 59.79 | 0.00 |
August | 18578.75 | 28-AUG-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.88 |
September | 15964.26 | 13-SEP-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 |
October | 18867.57 | 02-OCT-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.62 |
November | 15590.70 | 08-NOV-21:09 | 7087.36 | 14632.66 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.06 |
December | 2335.67 | 18-DEC-18:20 | 1687.47 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2309.66 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19011.94 | 16199.69 | 16723.04 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.79 | 371.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1985.54 | 06-JAN-08:61 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.67 |
February | 2460.93 | 22-FEB-14:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.31 |
March | 2921.51 | 16-MAR-16:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.01 |
April | 5299.57 | 21-APR-14:00 | 1012.48 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.54 | 0.00 |
May | 14709.58 | 31-MAY-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
June | 20738.70 | 06-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 |
July | 19256.27 | 03-JUL-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | 0.00 |
August | 19724.93 | 28-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.25 |
September | 16476.73 | 13-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 |
October | 19997.00 | 02-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.79 |
November | 4173.80 | 09-NOV-14:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 2238.19 | 18-DEC-18:20 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1985.54 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20738.70 | 1687.47 | 1952.90 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.54 | 484.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1916.52 | 05-JAN-19:00 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.45 |
February | 2314.57 | 22-FEB-14:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.31 |
March | 2835.45 | 16-MAR-16:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.01 |
April | 5293.75 | 21-APR-14:00 | 1012.48 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.54 | 0.00 |
May | 15078.60 | 31-MAY-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
June | 20857.97 | 06-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.38 |
July | 19349.85 | 03-JUL-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 0.00 |
August | 19885.66 | 28-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 |
September | 16570.63 | 13-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 |
October | 20120.99 | 02-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 |
November | 4120.01 | 09-NOV-14:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 2174.83 | 18-DEC-18:20 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1916.52 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20857.97 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.54 | 364.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1870.77 | 05-JAN-19:00 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.94 |
February | 2274.71 | 08-FEB-19:00 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.85 |
March | 2616.50 | 16-MAR-16:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.01 |
April | 5145.05 | 21-APR-14:00 | 1012.48 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.54 | 0.00 |
May | 13858.24 | 31-MAY-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
June | 20640.83 | 06-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 |
July | 19212.76 | 03-JUL-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 0.00 |
August | 19683.39 | 28-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 |
September | 16344.53 | 13-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.69 |
October | 19881.09 | 02-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.63 |
November | 3942.11 | 09-NOV-14:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 2112.73 | 18-DEC-19:00 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1870.77 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20640.83 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.54 | 501.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3416.36 | 07-JAN-11:40 | 3915.04 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.51 |
February | 4009.30 | 08-FEB-17:40 | 4792.55 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3871.11 |
March | 4916.11 | 16-MAR-14:50 | 4657.54 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.23 |
April | 9618.84 | 21-APR-14:30 | 4657.54 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2189.18 | 0.00 |
May | 25395.71 | 30-MAY-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 74.85 | 0.00 |
June | 34713.82 | 18-JUN-08:62 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 63.80 | 0.00 |
July | 35220.43 | 03-JUL-07:01 | 0.00 | 600.00 | 589.11 | 0.00 | 0.00 | 0.00 | 0.00 | 91.43 | 0.00 |
August | 35057.23 | 28-AUG-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.09 |
September | 29133.51 | 13-SEP-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.96 |
October | 35222.34 | 02-OCT-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.22 |
November | 7141.86 | 09-NOV-14:00 | 4792.55 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.17 |
December | 4378.61 | 26-DEC-18:55 | 4590.04 | 4156.22 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3416.36 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35222.34 | 4792.55 | 4156.22 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2189.18 | 3871.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1644.91 | 07-JAN-11:40 | 1957.46 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.76 |
February | 1959.87 | 08-FEB-17:40 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2131.63 |
March | 2443.09 | 16-MAR-15:00 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.71 |
April | 4995.79 | 21-APR-14:40 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 0.00 |
May | 12851.91 | 30-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 40.80 | 0.00 |
June | 17847.60 | 18-JUN-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 36.34 | 0.00 |
July | 18115.44 | 03-JUL-07:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 50.64 | 0.00 |
August | 18110.98 | 28-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.27 |
September | 14992.79 | 13-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.54 |
October | 18186.55 | 02-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.02 |
November | 3630.33 | 09-NOV-14:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 1991.31 | 27-DEC-13:55 | 4792.41 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2129.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1644.91 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18186.55 | 4792.41 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 2131.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1617.63 | 07-JAN-11:50 | 1957.46 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.49 |
February | 1913.19 | 08-FEB-17:30 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2078.48 |
March | 2346.85 | 16-MAR-15:00 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.71 |
April | 4938.82 | 21-APR-14:40 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 0.00 |
May | 12454.18 | 30-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 40.90 | 0.00 |
June | 17774.84 | 18-JUN-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 36.69 | 0.00 |
July | 18042.48 | 03-JUL-07:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 50.72 | 0.00 |
August | 18025.06 | 28-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 |
September | 14915.88 | 13-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.34 |
October | 18089.26 | 02-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.72 |
November | 3551.96 | 09-NOV-14:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 1515.58 | 30-DEC-12:00 | 1957.46 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1515.58 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18089.26 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 2078.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1783.47 | 27-JAN-13:05 | 4792.41 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1951.78 |
February | 1816.33 | 08-FEB-18:50 | 1147.48 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.83 |
March | 2120.56 | 16-MAR-15:00 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.71 |
April | 4823.50 | 21-APR-14:40 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 0.00 |
May | 10775.66 | 30-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 41.27 | 0.00 |
June | 17769.29 | 18-JUN-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 38.54 | 0.00 |
July | 18053.48 | 03-JUL-07:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 50.86 | 0.00 |
August | 18027.69 | 07-AUG-07:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 0.00 |
September | 14881.34 | 13-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.31 |
October | 18066.13 | 02-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.85 |
November | 3404.88 | 09-NOV-14:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 1740.63 | 02-DEC-15:10 | 5399.90 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1829.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1740.63 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18066.13 | 5399.90 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 1951.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1425.31 | 27-JAN-15:45 | 4657.41 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1697.46 |
February | 1458.71 | 08-FEB-16:00 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1922.94 |
March | 1909.79 | 16-MAR-14:20 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.23 |
April | 5275.90 | 21-APR-14:20 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1339.13 | 0.00 |
May | 8421.51 | 31-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 31.57 | 0.00 |
June | 19660.32 | 18-JUN-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 43.38 | 0.00 |
July | 19941.77 | 03-JUL-07:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 58.50 | 0.00 |
August | 19818.28 | 28-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.51 |
September | 16300.24 | 13-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.06 |
October | 19983.81 | 02-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.78 |
November | 3626.93 | 09-NOV-14:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.57 |
December | 1526.14 | 29-DEC-13:05 | 4792.41 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1820.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1425.31 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19983.81 | 4792.41 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1339.13 | 1922.94 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.527769E+11 | 44856.00 | 05-JAN-17:19 | 0.114504E+11 | 100959.28 | 28-JAN-08:09 |
February | 0.476989E+11 | 43145.85 | 16-FEB-17:49 | 0.593401E+10 | 101450.65 | 03-FEB-08:09 |
March | 0.535866E+11 | 49455.36 | 22-MAR-14:50 | 0.310061E+10 | 97073.16 | 02-MAR-08:09 |
April | 0.587543E+11 | 59619.63 | 21-APR-14:50 | 34531894.72 | 6622.38 | 01-APR-07:10 |
May | 0.697983E+11 | 64035.26 | 30-MAY-14:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.772314E+11 | 72700.72 | 15-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.814299E+11 | 73161.98 | 03-JUL-16:49 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.790847E+11 | 71610.76 | 04-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.729506E+11 | 67594.21 | 01-SEP-14:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.622795E+11 | 64534.43 | 03-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.516183E+11 | 49649.86 | 08-NOV-14:20 | 0.251643E+10 | 65544.71 | 28-NOV-08:09 |
December | 0.527652E+11 | 46430.93 | 29-DEC-17:00 | 0.154305E+11 | 106819.10 | 27-DEC-08:09 |
Annual Sum or Average | 0.759975E+12 | 0.384666E+11 | ||||
Minimum of Months | 0.476989E+11 | 43145.85 | 0.00 | 0.00 | ||
Maximum of Months | 0.814299E+11 | 73161.98 | 0.154305E+11 | 106819.10 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.424014E+10 | 8111.27 | 27-JAN-12:30 | 0.00 | 0.00 |
February | 0.480713E+10 | 9525.44 | 24-FEB-11:39 | 0.00 | 0.00 |
March | 0.715135E+10 | 11160.44 | 29-MAR-12:20 | 0.00 | 0.00 |
April | 0.823669E+10 | 11250.00 | 22-APR-11:30 | 0.00 | 0.00 |
May | 0.912139E+10 | 11250.00 | 05-MAY-11:09 | 0.00 | 0.00 |
June | 0.904268E+10 | 10920.56 | 10-JUN-11:00 | 0.00 | 0.00 |
July | 0.815090E+10 | 10464.13 | 22-JUL-11:00 | 0.00 | 0.00 |
August | 0.764503E+10 | 10264.07 | 09-AUG-12:30 | 0.00 | 0.00 |
September | 0.690369E+10 | 10298.07 | 09-SEP-12:30 | 0.00 | 0.00 |
October | 0.564943E+10 | 9314.57 | 05-OCT-11:30 | 0.00 | 0.00 |
November | 0.452756E+10 | 8266.32 | 05-NOV-11:39 | 0.00 | 0.00 |
December | 0.399101E+10 | 7201.26 | 29-DEC-11:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.794670E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.399101E+10 | 7201.26 | 0.00 | 0.00 | |
Maximum of Months | 0.912139E+10 | 11250.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.234911E+11 | 0.427021E+10 | 0.108325E+11 | 0.00 | 0.874516E+10 | 0.00 | 0.00 | 1043441.46 | 0.00 | 0.00 | 0.00 | 0.543694E+10 | 0.00 |
February | 0.212624E+11 | 0.357773E+10 | 0.980803E+10 | 0.00 | 0.787688E+10 | 0.00 | 0.00 | 0.264651E+09 | 0.00 | 0.00 | 0.00 | 0.490928E+10 | 0.00 |
March | 0.238408E+11 | 0.356362E+10 | 0.110075E+11 | 0.00 | 0.882209E+10 | 0.00 | 0.00 | 0.944242E+09 | 0.00 | 0.00 | 0.00 | 0.540837E+10 | 0.00 |
April | 0.227839E+11 | 0.304879E+10 | 0.105079E+11 | 0.00 | 0.834793E+10 | 0.00 | 0.00 | 0.897623E+10 | 0.00 | 0.00 | 0.00 | 0.508956E+10 | 0.00 |
May | 0.236617E+11 | 0.280704E+10 | 0.109147E+11 | 0.00 | 0.865310E+10 | 0.00 | 0.00 | 0.186045E+11 | 0.00 | 0.00 | 0.00 | 0.515717E+10 | 0.00 |
June | 0.230409E+11 | 0.254440E+10 | 0.106386E+11 | 0.00 | 0.848291E+10 | 0.00 | 0.00 | 0.276135E+11 | 0.00 | 0.00 | 0.00 | 0.491116E+10 | 0.00 |
July | 0.234131E+11 | 0.270480E+10 | 0.107945E+11 | 0.00 | 0.863199E+10 | 0.00 | 0.00 | 0.308985E+11 | 0.00 | 0.00 | 0.00 | 0.498696E+10 | 0.00 |
August | 0.238328E+11 | 0.299789E+10 | 0.110006E+11 | 0.00 | 0.877275E+10 | 0.00 | 0.00 | 0.274580E+11 | 0.00 | 0.00 | 0.00 | 0.502254E+10 | 0.00 |
September | 0.227918E+11 | 0.327145E+10 | 0.105148E+11 | 0.00 | 0.835994E+10 | 0.00 | 0.00 | 0.231169E+11 | 0.00 | 0.00 | 0.00 | 0.489584E+10 | 0.00 |
October | 0.234911E+11 | 0.379763E+10 | 0.108325E+11 | 0.00 | 0.865056E+10 | 0.00 | 0.00 | 0.103671E+11 | 0.00 | 0.00 | 0.00 | 0.514058E+10 | 0.00 |
November | 0.227593E+11 | 0.402348E+10 | 0.104978E+11 | 0.00 | 0.843555E+10 | 0.00 | 0.00 | 0.800076E+09 | 0.00 | 0.00 | 0.00 | 0.510205E+10 | 0.00 |
December | 0.234215E+11 | 0.435655E+10 | 0.108050E+11 | 0.00 | 0.879234E+10 | 0.00 | 0.00 | 653502.19 | 0.00 | 0.00 | 0.00 | 0.538917E+10 | 0.00 |
Annual Sum or Average | 0.277790E+12 | 0.409636E+11 | 0.128154E+12 | 0.00 | 0.102571E+12 | 0.00 | 0.00 | 0.149046E+12 | 0.00 | 0.00 | 0.00 | 0.614496E+11 | 0.00 |
Minimum of Months | 0.212624E+11 | 0.254440E+10 | 0.980803E+10 | 0.00 | 0.787688E+10 | 0.00 | 0.00 | 653502.19 | 0.00 | 0.00 | 0.00 | 0.489584E+10 | 0.00 |
Maximum of Months | 0.238408E+11 | 0.435655E+10 | 0.110075E+11 | 0.00 | 0.882209E+10 | 0.00 | 0.00 | 0.308985E+11 | 0.00 | 0.00 | 0.00 | 0.543694E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.114504E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.593401E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.310061E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 34531894.72 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.251643E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.154305E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.384666E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.154305E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17697.17 | 01-JAN-11:09 | 3786.68 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 8002.75 | 28-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 17697.17 | 01-FEB-10:09 | 3786.68 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 8013.80 | 03-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 17697.17 | 01-MAR-10:09 | 3786.68 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 7921.83 | 02-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 17697.17 | 01-APR-09:09 | 3786.68 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 6017.89 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 17697.17 | 01-MAY-09:09 | 3786.68 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 6444.49 | 31-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 17697.17 | 01-JUN-09:09 | 3786.68 | 01-JUN-19:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 7173.36 | 15-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 17697.17 | 01-JUL-09:09 | 3786.68 | 01-JUL-19:19 | 8059.50 | 01-JUL-09:09 | 0.00 | 7498.08 | 03-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 17697.17 | 01-AUG-09:09 | 3786.68 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 7498.08 | 07-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 17697.17 | 01-SEP-09:09 | 3786.68 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 7466.88 | 23-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 17697.17 | 01-OCT-10:09 | 3786.68 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 7173.36 | 02-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 17697.17 | 01-NOV-09:09 | 3786.68 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7257.80 | 28-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 17697.17 | 01-DEC-10:09 | 3786.68 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 8126.81 | 27-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 17697.17 | 3786.68 | 8059.50 | 0.00 | 6017.89 | 0.00 | 0.00 | |||||
Maximum of Months | 17697.17 | 3786.68 | 8059.50 | 0.00 | 8126.81 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 256.41 | 01-JAN-18:10 | 0.00 | 0.00 | 0.00 | 9710.99 | 10-JAN-13:50 | 0.00 | 01-JAN-00:10 |
February | 6341.30 | 20-FEB-15:30 | 0.00 | 0.00 | 0.00 | 9709.82 | 27-FEB-13:09 | 0.00 | 01-FEB-00:10 |
March | 9647.76 | 22-MAR-12:00 | 0.00 | 0.00 | 0.00 | 9703.32 | 09-MAR-14:09 | 0.00 | 01-MAR-00:10 |
April | 22568.86 | 21-APR-14:30 | 0.00 | 0.00 | 0.00 | 9669.58 | 28-APR-11:20 | 0.00 | 01-APR-00:10 |
May | 27769.15 | 19-MAY-16:10 | 0.00 | 0.00 | 0.00 | 9235.79 | 08-MAY-13:50 | 0.00 | 01-MAY-00:10 |
June | 35926.85 | 02-JUN-16:19 | 0.00 | 0.00 | 0.00 | 7918.01 | 27-JUN-09:39 | 0.00 | 01-JUN-00:10 |
July | 35872.00 | 03-JUL-16:10 | 0.00 | 0.00 | 0.00 | 9665.97 | 17-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 35110.33 | 07-AUG-16:10 | 0.00 | 0.00 | 0.00 | 8775.44 | 04-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 29394.50 | 02-SEP-12:00 | 0.00 | 0.00 | 0.00 | 7560.24 | 30-SEP-12:39 | 0.00 | 01-SEP-00:10 |
October | 29030.52 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 7568.77 | 30-OCT-12:50 | 0.00 | 01-OCT-00:10 |
November | 11736.15 | 09-NOV-13:00 | 0.00 | 0.00 | 0.00 | 9554.48 | 06-NOV-12:50 | 0.00 | 01-NOV-00:10 |
December | 226.54 | 15-DEC-21:19 | 0.00 | 0.00 | 0.00 | 11831.29 | 29-DEC-14:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 226.54 | 0.00 | 0.00 | 0.00 | 7560.24 | 0.00 | |||
Maximum of Months | 35926.85 | 0.00 | 0.00 | 0.00 | 11831.29 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 44856.00 | 05-JAN-17:19 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 5913.67 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 43145.85 | 16-FEB-17:49 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 6043.43 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 49455.36 | 22-MAR-14:50 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5874.49 | 0.00 | 0.00 | 8147.54 | 0.00 |
April | 59619.63 | 21-APR-14:50 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5874.49 | 0.00 | 0.00 | 22550.55 | 0.00 |
May | 64035.26 | 30-MAY-14:09 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5874.49 | 0.00 | 0.00 | 26969.60 | 0.00 |
June | 72700.72 | 15-JUN-14:50 | 17697.17 | 8059.50 | 0.00 | 0.00 | 6587.31 | 0.00 | 0.00 | 34924.34 | 0.00 |
July | 73161.98 | 03-JUL-16:49 | 17697.17 | 8059.50 | 0.00 | 0.00 | 6557.54 | 0.00 | 0.00 | 35423.13 | 0.00 |
August | 71610.76 | 04-AUG-13:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5896.21 | 0.00 | 0.00 | 31182.43 | 0.00 |
September | 67594.21 | 01-SEP-14:30 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5874.49 | 0.00 | 0.00 | 28423.36 | 0.00 |
October | 64534.43 | 03-OCT-14:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5874.49 | 0.00 | 0.00 | 27468.53 | 0.00 |
November | 49649.86 | 08-NOV-14:20 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5874.49 | 0.00 | 0.00 | 10450.23 | 0.00 |
December | 46430.93 | 29-DEC-17:00 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 6396.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 43145.85 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5874.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73161.98 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 6587.31 | 0.00 | 0.00 | 35423.13 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 100959.28 | 28-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 101450.65 | 03-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 97073.16 | 02-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 6622.38 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 65544.71 | 28-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 106819.10 | 27-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 106819.10 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Annual Sum or Average | 0.67 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
February | 0.33 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
March | 0.17 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Annual Sum or Average | 1.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.74 | 61.00 | 21.67 | 61.00 | 21.61 |
February | 448.00 | 22.29 | 49.83 | 22.16 | 49.83 | 22.06 |
March | 497.00 | 22.95 | 26.33 | 22.85 | 26.33 | 22.77 |
April | 320.67 | 23.69 | 4.00 | 23.69 | 0.00 | 23.69 |
May | 108.67 | 23.86 | 143.67 | 23.88 | 0.00 | 23.88 |
June | 14.50 | 23.88 | 293.83 | 23.89 | 0.00 | 23.89 |
July | 60.17 | 23.89 | 494.50 | 23.89 | 60.17 | 23.89 |
August | 35.67 | 23.89 | 473.00 | 23.89 | 35.67 | 23.89 |
September | 50.00 | 23.88 | 391.83 | 23.89 | 40.67 | 23.89 |
October | 86.17 | 23.79 | 217.17 | 23.86 | 16.83 | 23.86 |
November | 393.17 | 23.03 | 17.83 | 23.03 | 6.17 | 23.00 |
December | 496.00 | 21.61 | 73.17 | 21.53 | 73.17 | 21.48 |
Annual Sum or Average | 3006.00 | 22.63 | 2246.17 | 23.05 | 369.83 | 23.00 |
Minimum of Months | 14.50 | 21.61 | 4.00 | 21.53 | 0.00 | 21.48 |
Maximum of Months | 497.00 | 23.89 | 494.50 | 23.89 | 73.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 491.50 | 22.51 | 6.33 | 22.50 | 6.33 | 22.49 |
February | 448.00 | 22.96 | 3.83 | 22.94 | 3.83 | 22.93 |
March | 493.67 | 23.40 | 2.67 | 23.39 | 2.67 | 23.38 |
April | 298.00 | 23.75 | 4.83 | 23.75 | 0.00 | 23.75 |
May | 96.50 | 23.76 | 125.50 | 23.83 | 0.00 | 23.83 |
June | 11.33 | 23.72 | 268.17 | 23.88 | 0.00 | 23.88 |
July | 36.50 | 23.89 | 494.50 | 23.89 | 36.50 | 23.89 |
August | 22.00 | 23.81 | 468.00 | 23.88 | 20.67 | 23.88 |
September | 39.33 | 23.68 | 369.33 | 23.85 | 21.33 | 23.85 |
October | 76.33 | 23.76 | 212.83 | 23.85 | 9.67 | 23.85 |
November | 368.33 | 23.38 | 12.17 | 23.40 | 0.00 | 23.40 |
December | 496.00 | 22.36 | 8.00 | 22.34 | 8.00 | 22.32 |
Annual Sum or Average | 2877.50 | 23.07 | 1976.17 | 23.39 | 109.00 | 23.39 |
Minimum of Months | 11.33 | 22.36 | 2.67 | 22.34 | 0.00 | 22.32 |
Maximum of Months | 496.00 | 23.89 | 494.50 | 23.89 | 36.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 22.05 | 19.83 | 22.00 | 19.83 | 21.96 |
February | 336.00 | 22.61 | 13.33 | 22.56 | 13.33 | 22.50 |
March | 378.50 | 23.22 | 5.17 | 23.19 | 5.17 | 23.17 |
April | 200.67 | 23.76 | 14.00 | 23.86 | 0.00 | 23.86 |
May | 60.33 | 23.88 | 125.33 | 24.18 | 0.00 | 24.18 |
June | 8.67 | 24.07 | 232.00 | 24.19 | 0.33 | 24.20 |
July | 52.17 | 24.21 | 367.67 | 24.11 | 52.17 | 24.12 |
August | 22.17 | 24.16 | 369.67 | 24.08 | 22.17 | 24.09 |
September | 26.00 | 23.96 | 303.67 | 24.07 | 21.67 | 24.06 |
October | 44.50 | 23.78 | 175.67 | 24.02 | 7.33 | 24.02 |
November | 270.17 | 23.17 | 11.83 | 23.19 | 0.83 | 23.19 |
December | 369.00 | 21.89 | 25.17 | 21.84 | 25.17 | 21.80 |
Annual Sum or Average | 2139.17 | 22.81 | 1663.33 | 23.34 | 168.00 | 23.32 |
Minimum of Months | 8.67 | 21.89 | 5.17 | 21.84 | 0.00 | 21.80 |
Maximum of Months | 378.50 | 24.21 | 369.67 | 24.19 | 52.17 | 24.20 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.94 | 25.83 | 21.89 | 25.83 | 21.84 |
February | 336.00 | 22.52 | 16.17 | 22.46 | 16.17 | 22.40 |
March | 379.00 | 23.17 | 6.83 | 23.13 | 6.83 | 23.10 |
April | 204.33 | 23.76 | 14.00 | 23.85 | 0.00 | 23.85 |
May | 58.33 | 23.88 | 126.67 | 24.18 | 0.00 | 24.18 |
June | 8.50 | 24.16 | 234.00 | 24.20 | 0.50 | 24.20 |
July | 52.50 | 24.24 | 367.83 | 24.11 | 52.50 | 24.13 |
August | 21.83 | 24.20 | 370.67 | 24.08 | 21.83 | 24.09 |
September | 25.67 | 23.96 | 304.33 | 24.07 | 21.50 | 24.06 |
October | 45.00 | 23.78 | 176.00 | 24.01 | 7.83 | 24.01 |
November | 274.67 | 23.14 | 11.17 | 23.15 | 2.00 | 23.14 |
December | 369.00 | 21.80 | 32.17 | 21.74 | 32.17 | 21.70 |
Annual Sum or Average | 2145.83 | 22.75 | 1685.67 | 23.29 | 187.17 | 23.27 |
Minimum of Months | 8.50 | 21.80 | 6.83 | 21.74 | 0.00 | 21.70 |
Maximum of Months | 379.00 | 24.24 | 370.67 | 24.20 | 52.50 | 24.20 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.79 | 35.67 | 21.73 | 35.67 | 21.68 |
February | 336.00 | 22.37 | 22.83 | 22.29 | 22.83 | 22.22 |
March | 379.00 | 23.05 | 11.00 | 22.99 | 11.00 | 22.94 |
April | 216.83 | 23.73 | 12.17 | 23.81 | 0.00 | 23.81 |
May | 65.17 | 23.87 | 121.83 | 24.17 | 0.00 | 24.17 |
June | 9.00 | 24.06 | 231.50 | 24.19 | 0.50 | 24.19 |
July | 53.67 | 24.19 | 367.67 | 24.11 | 53.67 | 24.12 |
August | 22.67 | 24.15 | 369.67 | 24.08 | 22.67 | 24.08 |
September | 26.67 | 23.96 | 301.17 | 24.06 | 22.00 | 24.06 |
October | 51.67 | 23.76 | 170.83 | 23.99 | 8.33 | 23.99 |
November | 287.00 | 23.09 | 8.83 | 23.08 | 3.17 | 23.06 |
December | 369.00 | 21.65 | 42.67 | 21.60 | 42.67 | 21.55 |
Annual Sum or Average | 2187.67 | 22.66 | 1695.83 | 23.21 | 222.50 | 23.18 |
Minimum of Months | 9.00 | 21.65 | 8.83 | 21.60 | 0.00 | 21.55 |
Maximum of Months | 379.00 | 24.19 | 369.67 | 24.19 | 53.67 | 24.19 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.57 | 44.83 | 21.52 | 44.83 | 21.48 |
February | 308.00 | 22.19 | 32.83 | 22.08 | 32.83 | 22.00 |
March | 348.00 | 22.92 | 15.83 | 22.84 | 15.83 | 22.77 |
April | 226.67 | 23.74 | 6.83 | 23.77 | 0.00 | 23.77 |
May | 69.17 | 23.88 | 100.83 | 24.01 | 0.00 | 24.01 |
June | 5.33 | 24.18 | 202.50 | 24.00 | 0.33 | 24.01 |
July | 65.50 | 24.05 | 335.50 | 23.99 | 65.50 | 24.00 |
August | 20.33 | 24.13 | 336.67 | 23.97 | 20.33 | 23.98 |
September | 16.33 | 23.96 | 270.50 | 23.97 | 12.83 | 23.97 |
October | 64.33 | 23.78 | 153.00 | 23.92 | 9.33 | 23.92 |
November | 285.83 | 23.01 | 5.67 | 22.98 | 4.67 | 22.95 |
December | 338.00 | 21.45 | 67.83 | 21.40 | 67.83 | 21.36 |
Annual Sum or Average | 2087.50 | 22.57 | 1572.83 | 23.05 | 274.33 | 23.00 |
Minimum of Months | 5.33 | 21.45 | 5.67 | 21.40 | 0.00 | 21.36 |
Maximum of Months | 348.00 | 24.18 | 336.67 | 24.01 | 67.83 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.53 | 50.50 | 21.48 | 50.50 | 21.44 |
February | 308.00 | 22.14 | 37.83 | 22.03 | 37.83 | 21.94 |
March | 348.00 | 22.87 | 18.83 | 22.78 | 18.83 | 22.70 |
April | 238.33 | 23.73 | 5.50 | 23.76 | 0.00 | 23.76 |
May | 82.33 | 23.88 | 90.50 | 24.00 | 0.00 | 24.00 |
June | 9.33 | 23.97 | 180.50 | 24.01 | 0.17 | 24.01 |
July | 65.50 | 24.02 | 334.50 | 23.98 | 65.50 | 23.99 |
August | 20.00 | 24.07 | 332.00 | 23.96 | 20.00 | 23.97 |
September | 18.00 | 23.95 | 260.50 | 23.97 | 13.17 | 23.97 |
October | 74.67 | 23.79 | 141.67 | 23.92 | 9.50 | 23.91 |
November | 292.33 | 23.01 | 5.33 | 22.97 | 5.33 | 22.94 |
December | 338.00 | 21.42 | 74.33 | 21.37 | 74.33 | 21.33 |
Annual Sum or Average | 2134.50 | 22.57 | 1532.00 | 23.02 | 295.17 | 22.95 |
Minimum of Months | 9.33 | 21.42 | 5.33 | 21.37 | 0.00 | 21.33 |
Maximum of Months | 348.00 | 24.07 | 334.50 | 24.01 | 74.33 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.49 | 56.33 | 21.44 | 56.33 | 21.40 |
February | 308.00 | 22.10 | 42.67 | 21.98 | 42.67 | 21.88 |
March | 348.00 | 22.82 | 22.50 | 22.71 | 22.50 | 22.62 |
April | 245.67 | 23.72 | 5.17 | 23.75 | 0.00 | 23.75 |
May | 84.33 | 23.88 | 89.33 | 24.00 | 0.00 | 24.00 |
June | 10.17 | 23.97 | 179.00 | 24.01 | 0.17 | 24.01 |
July | 65.83 | 24.01 | 334.33 | 23.98 | 65.83 | 23.99 |
August | 20.00 | 24.03 | 331.17 | 23.96 | 20.00 | 23.96 |
September | 18.83 | 23.95 | 259.33 | 23.97 | 13.33 | 23.97 |
October | 79.33 | 23.78 | 138.00 | 23.91 | 9.67 | 23.91 |
November | 294.00 | 22.97 | 6.00 | 22.93 | 6.00 | 22.90 |
December | 338.00 | 21.40 | 80.83 | 21.34 | 80.83 | 21.30 |
Annual Sum or Average | 2152.17 | 22.55 | 1544.67 | 22.99 | 317.33 | 22.92 |
Minimum of Months | 10.17 | 21.40 | 5.17 | 21.34 | 0.00 | 21.30 |
Maximum of Months | 348.00 | 24.03 | 334.33 | 24.01 | 80.83 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.41 | 75.83 | 21.36 | 75.83 | 21.32 |
February | 308.00 | 21.99 | 58.83 | 21.85 | 58.83 | 21.74 |
March | 348.00 | 22.68 | 34.50 | 22.54 | 34.50 | 22.42 |
April | 254.83 | 23.67 | 4.33 | 23.70 | 0.00 | 23.70 |
May | 86.83 | 23.87 | 87.67 | 23.99 | 0.00 | 23.99 |
June | 10.00 | 23.97 | 180.50 | 24.00 | 0.17 | 24.01 |
July | 66.17 | 24.01 | 334.50 | 23.98 | 66.17 | 23.99 |
August | 20.33 | 24.06 | 332.17 | 23.96 | 20.33 | 23.97 |
September | 19.33 | 23.94 | 260.00 | 23.97 | 13.67 | 23.97 |
October | 86.50 | 23.74 | 133.50 | 23.88 | 9.67 | 23.88 |
November | 297.83 | 22.87 | 7.67 | 22.82 | 7.67 | 22.78 |
December | 338.00 | 21.34 | 100.17 | 21.28 | 100.17 | 21.25 |
Annual Sum or Average | 2175.83 | 22.48 | 1609.67 | 22.91 | 387.00 | 22.82 |
Minimum of Months | 10.00 | 21.34 | 4.33 | 21.28 | 0.00 | 21.25 |
Maximum of Months | 348.00 | 24.06 | 334.50 | 24.00 | 100.17 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.33 | 136.17 | 21.27 | 136.17 | 21.23 |
February | 308.00 | 21.86 | 103.67 | 21.67 | 103.67 | 21.56 |
March | 348.00 | 22.51 | 62.00 | 22.30 | 62.00 | 22.15 |
April | 262.83 | 23.61 | 8.67 | 23.61 | 2.83 | 23.59 |
May | 76.17 | 23.84 | 105.50 | 23.99 | 0.00 | 23.99 |
June | 4.50 | 24.57 | 226.83 | 24.00 | 1.00 | 24.01 |
July | 57.67 | 24.17 | 336.33 | 24.01 | 57.67 | 24.03 |
August | 23.17 | 24.31 | 342.50 | 23.98 | 23.17 | 24.00 |
September | 18.17 | 24.10 | 284.67 | 23.98 | 14.00 | 23.99 |
October | 88.00 | 23.59 | 139.33 | 23.83 | 10.00 | 23.83 |
November | 301.33 | 22.73 | 24.17 | 22.61 | 24.17 | 22.51 |
December | 338.00 | 21.29 | 156.67 | 21.23 | 156.67 | 21.20 |
Annual Sum or Average | 2165.83 | 22.38 | 1926.50 | 22.80 | 591.33 | 22.65 |
Minimum of Months | 4.50 | 21.29 | 8.67 | 21.23 | 0.00 | 21.20 |
Maximum of Months | 348.00 | 24.57 | 342.50 | 24.01 | 156.67 | 24.03 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.74488 | 23.67707 | -0.3384 | 8.28199 |
February | 448.00000 | 22.29294 | 19.53136 | -0.2443 | 7.54913 |
March | 497.00000 | 22.94678 | 18.14488 | -0.0948 | 6.42982 |
April | 479.00000 | 23.75541 | 20.46515 | 0.17715 | 6.10714 |
May | 496.00000 | 23.88327 | 30.03650 | -0.5615 | 11.93974 |
June | 481.00000 | 23.88771 | 34.62281 | -0.4607 | 9.58079 |
July | 495.00000 | 23.88917 | 48.95213 | -0.3432 | 7.52239 |
August | 497.00000 | 23.88854 | 45.00378 | -0.3741 | 8.01401 |
September | 479.00000 | 23.88875 | 43.06509 | -0.4006 | 8.55990 |
October | 496.00000 | 23.86958 | 36.64251 | 0.36585 | 8.03249 |
November | 480.00000 | 23.18633 | 23.45070 | 0.04547 | 6.35141 |
December | 496.00000 | 21.60635 | 20.69457 | -0.3908 | 8.81143 |
Annual Sum or Average | 5840.00000 | 23.23941 | 30.44319 | -0.2188 | 8.10810 |
Minimum of Months | 448.00000 | 21.60635 | 18.14488 | -0.5615 | 6.10714 |
Maximum of Months | 497.00000 | 23.88917 | 48.95213 | 0.36585 | 11.93974 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 22.52710 | 25.54450 | -0.1419 | 6.38976 |
February | 448.00000 | 22.95766 | 20.03368 | -0.0745 | 6.02723 |
March | 497.00000 | 23.40661 | 18.14844 | 0.03124 | 5.76258 |
April | 479.00000 | 23.80131 | 21.03300 | 0.20645 | 6.12014 |
May | 496.00000 | 23.85057 | 30.73520 | -0.5662 | 11.96201 |
June | 481.00000 | 23.87541 | 34.93218 | -0.4791 | 9.91015 |
July | 495.00000 | 23.88514 | 48.03037 | -0.3739 | 7.97135 |
August | 497.00000 | 23.87193 | 44.64386 | -0.4045 | 8.50103 |
September | 479.00000 | 23.84515 | 42.40575 | -0.4394 | 9.25435 |
October | 496.00000 | 23.85018 | 36.43400 | 0.35942 | 7.88377 |
November | 480.00000 | 23.49812 | 23.53627 | 0.12558 | 6.13635 |
December | 496.00000 | 22.35557 | 22.70361 | -0.2026 | 6.70048 |
Annual Sum or Average | 5840.00000 | 23.47822 | 30.76915 | -0.1642 | 7.73081 |
Minimum of Months | 448.00000 | 22.35557 | 18.14844 | -0.5662 | 5.76258 |
Maximum of Months | 497.00000 | 23.88514 | 48.03037 | 0.35942 | 11.96201 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.05073 | 21.72951 | -0.2548 | 7.30958 |
February | 336.00000 | 22.61290 | 18.11006 | -0.1519 | 6.59171 |
March | 379.00000 | 23.22386 | 16.74102 | -0.0140 | 6.03713 |
April | 360.00000 | 23.91880 | 20.35128 | 0.22382 | 6.42672 |
May | 375.00000 | 24.04680 | 29.25346 | -0.5210 | 11.19455 |
June | 366.00000 | 24.08717 | 33.57025 | -0.4267 | 9.30778 |
July | 369.00000 | 24.09497 | 48.38169 | -0.3097 | 7.44661 |
August | 379.00000 | 24.07277 | 44.72589 | -0.3446 | 7.85218 |
September | 360.00000 | 24.04954 | 42.54176 | -0.3748 | 8.29983 |
October | 371.00000 | 23.98146 | 35.47114 | 0.38278 | 8.33274 |
November | 360.00000 | 23.35444 | 22.45266 | 0.09500 | 6.35869 |
December | 369.00000 | 21.88980 | 19.20438 | -0.3095 | 7.76056 |
Annual Sum or Average | 4395.00000 | 23.45377 | 29.47050 | -0.1683 | 7.75629 |
Minimum of Months | 336.00000 | 21.88980 | 16.74102 | -0.5210 | 6.03713 |
Maximum of Months | 379.00000 | 24.09497 | 48.38169 | 0.38278 | 11.19455 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.94354 | 21.86378 | -0.2859 | 7.59559 |
February | 336.00000 | 22.52241 | 18.22938 | -0.1783 | 6.79212 |
March | 379.00000 | 23.16753 | 16.82602 | -0.0324 | 6.10654 |
April | 360.00000 | 23.91347 | 20.35943 | 0.22089 | 6.41187 |
May | 375.00000 | 24.04694 | 29.23992 | -0.5199 | 11.17278 |
June | 366.00000 | 24.08788 | 33.56032 | -0.4241 | 9.26476 |
July | 369.00000 | 24.09575 | 48.34624 | -0.3072 | 7.41866 |
August | 379.00000 | 24.07343 | 44.70711 | -0.3422 | 7.82062 |
September | 360.00000 | 24.04997 | 42.52412 | -0.3729 | 8.27141 |
October | 371.00000 | 23.98034 | 35.47670 | 0.38227 | 8.32540 |
November | 360.00000 | 23.32344 | 22.51294 | 0.08387 | 6.36994 |
December | 369.00000 | 21.79798 | 19.29554 | -0.3368 | 8.06927 |
Annual Sum or Average | 4395.00000 | 23.42240 | 29.50399 | -0.1771 | 7.81391 |
Minimum of Months | 336.00000 | 21.79798 | 16.82602 | -0.5199 | 6.10654 |
Maximum of Months | 379.00000 | 24.09575 | 48.34624 | 0.38227 | 11.17278 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.78703 | 22.04878 | -0.3293 | 8.04888 |
February | 336.00000 | 22.36889 | 18.43482 | -0.2206 | 7.16593 |
March | 379.00000 | 23.04793 | 17.01311 | -0.0677 | 6.25551 |
April | 360.00000 | 23.88689 | 20.40757 | 0.20818 | 6.33691 |
May | 375.00000 | 24.04128 | 29.28143 | -0.5276 | 11.33685 |
June | 366.00000 | 24.08379 | 33.59220 | -0.4297 | 9.34845 |
July | 369.00000 | 24.09171 | 48.46068 | -0.3117 | 7.45754 |
August | 379.00000 | 24.06947 | 44.77720 | -0.3470 | 7.87509 |
September | 360.00000 | 24.04572 | 42.59061 | -0.3783 | 8.34739 |
October | 371.00000 | 23.96944 | 35.53786 | 0.37579 | 8.22864 |
November | 360.00000 | 23.25308 | 22.66105 | 0.06179 | 6.36942 |
December | 369.00000 | 21.65179 | 19.43697 | -0.3775 | 8.56183 |
Annual Sum or Average | 4395.00000 | 23.36415 | 29.61186 | -0.1962 | 7.95576 |
Minimum of Months | 336.00000 | 21.65179 | 17.01311 | -0.5276 | 6.25551 |
Maximum of Months | 379.00000 | 24.09171 | 48.46068 | 0.37579 | 11.33685 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.57374 | 23.76236 | -0.3916 | 8.81494 |
February | 308.00000 | 22.18522 | 20.03942 | -0.2779 | 7.70528 |
March | 348.00000 | 22.91800 | 18.53019 | -0.1136 | 6.35834 |
April | 330.00000 | 23.82789 | 22.00193 | 0.18906 | 6.13859 |
May | 344.00000 | 23.94896 | 31.06837 | -0.5531 | 11.79949 |
June | 336.00000 | 23.95405 | 35.13381 | -0.4587 | 9.67626 |
July | 338.00000 | 23.97555 | 49.66766 | -0.3383 | 7.65276 |
August | 348.00000 | 23.95487 | 45.90489 | -0.3737 | 8.14334 |
September | 330.00000 | 23.95436 | 43.54406 | -0.4002 | 8.62811 |
October | 340.00000 | 23.90649 | 36.68982 | 0.36163 | 7.97787 |
November | 330.00000 | 23.12804 | 24.34536 | 0.02534 | 6.32334 |
December | 338.00000 | 21.45480 | 21.19031 | -0.4369 | 9.39386 |
Annual Sum or Average | 4030.00000 | 23.23845 | 31.08087 | -0.2315 | 8.22856 |
Minimum of Months | 308.00000 | 21.45480 | 18.53019 | -0.5531 | 6.13859 |
Maximum of Months | 348.00000 | 23.97555 | 49.66766 | 0.36163 | 11.79949 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.53303 | 23.67066 | -0.4075 | 9.03074 |
February | 308.00000 | 22.14255 | 19.96668 | -0.2943 | 7.88069 |
March | 348.00000 | 22.86972 | 18.50083 | -0.1323 | 6.45815 |
April | 330.00000 | 23.81872 | 21.89670 | 0.17578 | 6.04218 |
May | 344.00000 | 23.94744 | 30.96384 | -0.5719 | 12.23179 |
June | 336.00000 | 23.95278 | 35.04593 | -0.4815 | 10.11895 |
July | 338.00000 | 23.97396 | 49.68849 | -0.3611 | 7.97410 |
August | 348.00000 | 23.95362 | 45.89393 | -0.3961 | 8.49076 |
September | 330.00000 | 23.95323 | 43.52680 | -0.4218 | 8.98827 |
October | 340.00000 | 23.90422 | 36.63168 | 0.34919 | 7.78686 |
November | 330.00000 | 23.10783 | 24.27736 | 0.01176 | 6.30542 |
December | 338.00000 | 21.42326 | 21.07162 | -0.4499 | 9.59080 |
Annual Sum or Average | 4030.00000 | 23.22177 | 31.01913 | -0.2492 | 8.42008 |
Minimum of Months | 308.00000 | 21.42326 | 18.50083 | -0.5719 | 6.04218 |
Maximum of Months | 348.00000 | 23.97396 | 49.68849 | 0.34919 | 12.23179 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.49462 | 23.71793 | -0.4208 | 9.22408 |
February | 308.00000 | 22.09883 | 20.02388 | -0.3087 | 8.04583 |
March | 348.00000 | 22.81683 | 18.59358 | -0.1492 | 6.56759 |
April | 330.00000 | 23.80472 | 21.93068 | 0.16855 | 6.01550 |
May | 344.00000 | 23.94649 | 30.97517 | -0.5753 | 12.31850 |
June | 336.00000 | 23.95249 | 35.05485 | -0.4838 | 10.16424 |
July | 338.00000 | 23.97359 | 49.72600 | -0.3630 | 8.00144 |
August | 348.00000 | 23.95338 | 45.91360 | -0.3980 | 8.52094 |
September | 330.00000 | 23.95288 | 43.54503 | -0.4239 | 9.02458 |
October | 340.00000 | 23.89985 | 36.66296 | 0.34597 | 7.74405 |
November | 330.00000 | 23.07007 | 24.36210 | -0.0008 | 6.32339 |
December | 338.00000 | 21.39648 | 21.09410 | -0.4601 | 9.76074 |
Annual Sum or Average | 4030.00000 | 23.20358 | 31.05779 | -0.2566 | 8.48744 |
Minimum of Months | 308.00000 | 21.39648 | 18.59358 | -0.5753 | 6.01550 |
Maximum of Months | 348.00000 | 23.97359 | 49.72600 | 0.34597 | 12.31850 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.41265 | 23.80403 | -0.4500 | 9.69106 |
February | 308.00000 | 21.98774 | 20.16082 | -0.3436 | 8.49350 |
March | 348.00000 | 22.68107 | 18.82623 | -0.1891 | 6.88798 |
April | 330.00000 | 23.75783 | 22.02714 | 0.15060 | 5.98821 |
May | 344.00000 | 23.94258 | 31.00008 | -0.5799 | 12.45295 |
June | 336.00000 | 23.95228 | 35.06776 | -0.4821 | 10.12957 |
July | 338.00000 | 23.97343 | 49.75657 | -0.3599 | 7.95362 |
August | 348.00000 | 23.95344 | 45.92211 | -0.3946 | 8.46842 |
September | 330.00000 | 23.95270 | 43.54962 | -0.4215 | 8.98805 |
October | 340.00000 | 23.88303 | 36.74035 | 0.33943 | 7.67396 |
November | 330.00000 | 22.96444 | 24.57163 | -0.0317 | 6.41476 |
December | 338.00000 | 21.33621 | 21.14319 | -0.4836 | 10.18451 |
Annual Sum or Average | 4030.00000 | 23.15712 | 31.13820 | -0.2712 | 8.62065 |
Minimum of Months | 308.00000 | 21.33621 | 18.82623 | -0.5799 | 5.98821 |
Maximum of Months | 348.00000 | 23.97343 | 49.75657 | 0.33943 | 12.45295 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.33342 | 23.58944 | -0.5032 | 10.73304 |
February | 308.00000 | 21.85741 | 20.18514 | -0.4038 | 9.49124 |
March | 348.00000 | 22.51482 | 18.84960 | -0.2515 | 7.58995 |
April | 330.00000 | 23.70308 | 21.93628 | 0.13247 | 6.05673 |
May | 344.00000 | 23.94135 | 30.70245 | -0.5607 | 12.09079 |
June | 336.00000 | 23.95750 | 34.89043 | -0.4345 | 9.23674 |
July | 338.00000 | 23.98165 | 49.38949 | -0.3063 | 7.25288 |
August | 348.00000 | 23.96063 | 45.62209 | -0.3400 | 7.69622 |
September | 330.00000 | 23.96055 | 43.15231 | -0.3688 | 8.18768 |
October | 340.00000 | 23.84261 | 36.70365 | 0.33917 | 7.80001 |
November | 330.00000 | 22.83460 | 24.53001 | -0.0769 | 6.72899 |
December | 338.00000 | 21.29164 | 20.89713 | -0.5256 | 11.10111 |
Annual Sum or Average | 4030.00000 | 23.10614 | 30.95997 | -0.2753 | 8.66793 |
Minimum of Months | 308.00000 | 21.29164 | 18.84960 | -0.5607 | 6.05673 |
Maximum of Months | 348.00000 | 23.98165 | 49.38949 | 0.33917 | 12.09079 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 18.94 | 5.19 | 0.17 | 18.94 | 0.00 | 0.00 | 0.00 | 03-JAN-13:10 | 0.00 | 01-JAN-00:10 | 0.03 | 03-JAN-13:10 | 0.03 | 03-JAN-13:10 | 0.00 | 03-JAN-13:10 | 0.01 | 03-JAN-13:10 | 0.00 | 01-JAN-00:10 |
February | 0.219917E+09 | 58835642.28 | 29.33 | 0.219917E+09 | 0.00 | 0.00 | 0.31 | 20-FEB-16:00 | 0.00 | 01-FEB-00:10 | 5007.86 | 20-FEB-16:00 | 5007.86 | 20-FEB-16:00 | 0.00 | 20-FEB-15:20 | 1317.29 | 20-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.672490E+09 | 0.179652E+09 | 71.92 | 0.672490E+09 | -0.0 | 0.00 | 0.39 | 14-MAR-16:30 | 0.00 | 01-MAR-00:10 | 6448.64 | 14-MAR-16:30 | 6448.64 | 14-MAR-16:30 | 0.00 | 22-MAR-15:40 | 1694.38 | 14-MAR-16:30 | 0.00 | 01-MAR-00:10 |
April | 0.684460E+10 | 0.183804E+10 | 302.13 | 0.682213E+10 | 22464520.04 | 0.00 | 0.78 | 30-APR-16:03 | 0.00 | 01-APR-00:10 | 13921.06 | 30-APR-16:05 | 13921.06 | 30-APR-16:05 | 691.01 | 18-APR-18:00 | 3760.36 | 21-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.139707E+11 | 0.376868E+10 | 450.83 | 0.135375E+11 | 0.433196E+09 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 26208.32 | 31-MAY-07:03 | 26208.32 | 31-MAY-07:03 | 3013.33 | 24-MAY-13:10 | 5838.98 | 31-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.200680E+11 | 0.557920E+10 | 480.73 | 0.192893E+11 | 0.778716E+09 | 0.00 | 1.00 | 01-JUN-16:10 | 0.00 | 01-JUN-00:10 | 42980.49 | 19-JUN-07:02 | 40643.22 | 08-JUN-07:02 | 6835.96 | 19-JUN-07:02 | 9312.46 | 08-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.244701E+11 | 0.636032E+10 | 496.47 | 0.202111E+11 | 0.425897E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 46174.21 | 20-JUL-07:03 | 41231.12 | 03-JUL-07:01 | 25119.57 | 19-JUL-07:03 | 9570.88 | 03-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.213986E+11 | 0.560066E+10 | 487.57 | 0.188416E+11 | 0.255705E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 45936.07 | 02-AUG-07:03 | 39910.80 | 07-AUG-07:01 | 20568.87 | 02-AUG-07:03 | 9518.24 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.180433E+11 | 0.459804E+10 | 458.09 | 0.156154E+11 | 0.242783E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 45193.45 | 23-SEP-07:03 | 31061.17 | 13-SEP-07:02 | 20762.11 | 14-SEP-07:03 | 9285.10 | 23-SEP-07:03 | 0.00 | 01-SEP-00:05 |
October | 0.810006E+10 | 0.204840E+10 | 316.16 | 0.723309E+10 | 0.866967E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 42048.27 | 02-OCT-07:02 | 35995.19 | 02-OCT-07:02 | 11910.35 | 05-OCT-07:03 | 8796.87 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.586451E+09 | 0.151632E+09 | 55.00 | 0.579150E+09 | 7300891.31 | 0.00 | 0.48 | 09-NOV-15:00 | 0.00 | 01-NOV-00:10 | 8209.86 | 09-NOV-15:00 | 8209.86 | 09-NOV-15:00 | 575.78 | 03-NOV-13:00 | 2068.17 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.114374E+12 | 0.301834E+11 | 3148.40 | 0.103022E+12 | 0.113525E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.244701E+11 | 0.636032E+10 | 496.47 | 0.202111E+11 | 0.425897E+10 | 0.00 | 1.00 | 0.00 | 46174.21 | 41231.12 | 25119.57 | 9570.88 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 3850557.85 | 1015182.83 | 4.25 | 3848117.28 | 2440.57 | 0.00 | 0.25 | 01-JAN-18:10 | 0.00 | 01-JAN-00:10 | 2030.62 | 01-JAN-18:10 | 2022.49 | 01-JAN-18:10 | 8.14 | 01-JAN-18:10 | 512.82 | 01-JAN-18:10 | 0.00 | 01-JAN-00:10 |
February | 0.196527E+09 | 49656356.24 | 37.66 | 0.196497E+09 | 29788.75 | 0.00 | 1.00 | 19-FEB-18:01 | 0.00 | 01-FEB-00:10 | 20555.52 | 19-FEB-18:01 | 20555.52 | 19-FEB-18:01 | 63.16 | 27-FEB-21:30 | 4144.73 | 19-FEB-18:01 | 0.00 | 01-FEB-00:10 |
March | 0.535239E+09 | 0.136051E+09 | 88.58 | 0.535239E+09 | 40.85 | 0.00 | 1.00 | 12-MAR-17:01 | 0.00 | 01-MAR-00:10 | 20555.52 | 12-MAR-17:20 | 20555.52 | 19-MAR-17:08 | 0.02 | 10-MAR-19:10 | 4224.41 | 26-MAR-17:01 | 0.00 | 01-MAR-00:10 |
April | 0.430020E+10 | 0.108988E+10 | 296.39 | 0.428017E+10 | 20027184.85 | 0.00 | 1.00 | 01-APR-21:01 | 0.00 | 01-APR-00:10 | 21267.78 | 18-APR-21:00 | 20779.60 | 29-APR-20:19 | 2476.57 | 18-APR-21:00 | 4396.11 | 29-APR-20:19 | 0.00 | 01-APR-00:10 |
May | 0.776874E+10 | 0.201944E+10 | 440.37 | 0.749306E+10 | 0.275678E+09 | 0.00 | 1.00 | 02-MAY-20:01 | 0.00 | 01-MAY-00:10 | 22252.34 | 27-MAY-21:00 | 20739.63 | 18-MAY-23:30 | 7302.56 | 24-MAY-21:42 | 4661.17 | 27-MAY-20:40 | 0.00 | 01-MAY-00:10 |
June | 0.103225E+11 | 0.280948E+10 | 474.70 | 0.990493E+10 | 0.417553E+09 | 0.00 | 1.00 | 02-JUN-12:50 | 0.00 | 01-JUN-00:10 | 22236.23 | 29-JUN-22:32 | 21017.48 | 08-JUN-07:02 | 5990.55 | 23-JUN-20:02 | 4721.81 | 08-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.123839E+11 | 0.316605E+10 | 493.22 | 0.102793E+11 | 0.210459E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 23662.36 | 19-JUL-07:03 | 21268.79 | 03-JUL-07:01 | 13741.22 | 19-JUL-07:03 | 4839.41 | 03-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.110259E+11 | 0.282221E+10 | 480.23 | 0.967850E+10 | 0.134735E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 23412.00 | 03-AUG-07:02 | 20776.06 | 07-AUG-07:01 | 10875.96 | 01-AUG-20:57 | 4796.25 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.980950E+10 | 0.241465E+10 | 430.81 | 0.848248E+10 | 0.132702E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 23095.74 | 03-SEP-22:55 | 20707.29 | 28-SEP-21:36 | 11622.56 | 03-SEP-22:55 | 4726.64 | 09-SEP-20:00 | 0.00 | 01-SEP-00:05 |
October | 0.484972E+10 | 0.116987E+10 | 305.58 | 0.432740E+10 | 0.522318E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 23035.30 | 03-OCT-20:03 | 20555.52 | 20-OCT-20:57 | 10572.20 | 03-OCT-21:58 | 4715.13 | 03-OCT-20:03 | 0.00 | 01-OCT-00:10 |
November | 0.401273E+09 | 0.100381E+09 | 69.02 | 0.396626E+09 | 4647486.16 | 0.00 | 1.00 | 08-NOV-21:01 | 0.00 | 01-NOV-00:10 | 20555.52 | 08-NOV-21:09 | 20555.52 | 08-NOV-21:09 | 617.19 | 09-NOV-22:10 | 4144.73 | 08-NOV-21:09 | 0.00 | 01-NOV-00:10 |
December | 2487091.70 | 653502.19 | 1.83 | 2487091.70 | -0.0 | 0.00 | 0.21 | 10-DEC-18:10 | 0.00 | 01-DEC-00:10 | 1670.54 | 10-DEC-18:10 | 1670.54 | 10-DEC-18:10 | 0.00 | 15-DEC-21:20 | 426.57 | 10-DEC-18:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.615998E+11 | 0.157793E+11 | 3122.66 | 0.555806E+11 | 0.601921E+10 | 0.00 | ||||||||||||||
Minimum of Months | 2487091.70 | 653502.19 | 1.83 | 2487091.70 | -0.0 | 0.00 | 0.21 | 0.00 | 1670.54 | 1670.54 | 0.00 | 426.57 | 0.00 | |||||||
Maximum of Months | 0.123839E+11 | 0.316605E+10 | 493.22 | 0.102793E+11 | 0.210459E+10 | 0.00 | 1.00 | 0.00 | 23662.36 | 21268.79 | 13741.22 | 4839.41 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 105105.36 | 28208.14 | 0.67 | 105105.36 | -0.0 | 0.00 | 0.01 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 | 115.00 | 03-JAN-15:00 | 115.00 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 | 30.84 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.117306E+09 | 30804115.04 | 30.50 | 0.117306E+09 | 0.00 | 0.00 | 0.29 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 2447.90 | 20-FEB-15:00 | 2447.90 | 20-FEB-15:00 | 0.00 | 21-FEB-15:10 | 635.52 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.401672E+09 | 0.104768E+09 | 77.08 | 0.401672E+09 | 28.40 | 0.00 | 0.42 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3594.13 | 22-MAR-13:00 | 3594.13 | 22-MAR-13:00 | 0.01 | 10-MAR-19:00 | 932.05 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.282601E+10 | 0.743606E+09 | 226.75 | 0.281644E+10 | 9569765.81 | 0.00 | 0.76 | 21-APR-14:00 | 0.00 | 01-APR-00:10 | 7013.01 | 21-APR-14:00 | 7013.01 | 21-APR-14:00 | 337.11 | 18-APR-18:00 | 1932.35 | 21-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.559553E+10 | 0.148313E+10 | 339.06 | 0.543623E+10 | 0.159291E+09 | 0.00 | 1.00 | 30-MAY-06:03 | 0.00 | 01-MAY-00:10 | 15575.35 | 31-MAY-06:03 | 15575.35 | 31-MAY-06:03 | 2182.22 | 28-MAY-07:03 | 3288.97 | 31-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.796054E+10 | 0.217579E+10 | 356.70 | 0.766013E+10 | 0.300410E+09 | 0.00 | 1.00 | 02-JUN-06:03 | 0.00 | 01-JUN-00:10 | 22048.15 | 19-JUN-06:02 | 21313.12 | 03-JUN-06:02 | 5042.87 | 04-JUN-07:03 | 4686.35 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.953991E+10 | 0.243732E+10 | 363.28 | 0.787019E+10 | 0.166973E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 23880.26 | 17-JUL-06:02 | 21564.29 | 03-JUL-06:01 | 13474.02 | 17-JUL-06:02 | 4869.71 | 16-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.841068E+10 | 0.215707E+10 | 367.21 | 0.735264E+10 | 0.105804E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 23783.16 | 03-AUG-06:02 | 21119.89 | 27-AUG-07:02 | 11060.82 | 03-AUG-06:02 | 4821.64 | 06-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.724584E+10 | 0.182494E+10 | 343.16 | 0.632259E+10 | 0.923247E+09 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 23332.04 | 23-SEP-06:02 | 16101.96 | 13-SEP-06:02 | 11280.79 | 14-SEP-06:03 | 4683.49 | 23-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.341792E+10 | 0.850168E+09 | 257.35 | 0.308649E+10 | 0.331426E+09 | 0.00 | 1.00 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 | 21684.34 | 02-OCT-06:02 | 19844.58 | 02-OCT-06:02 | 7203.65 | 04-OCT-06:03 | 4506.20 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.321854E+09 | 81694282.66 | 62.83 | 0.318045E+09 | 3808662.33 | 0.00 | 0.49 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4327.55 | 09-NOV-14:00 | 4327.55 | 09-NOV-14:00 | 307.13 | 03-NOV-12:50 | 1064.54 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.458374E+11 | 0.118893E+11 | 2424.58 | 0.413819E+11 | 0.445551E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.953991E+10 | 0.243732E+10 | 367.21 | 0.787019E+10 | 0.166973E+10 | 0.00 | 1.00 | 0.00 | 23880.26 | 21564.29 | 13474.02 | 4869.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 24.81 | 6.68 | 0.33 | 24.81 | -0.0 | 0.00 | 0.00 | 03-JAN-12:50 | 0.00 | 01-JAN-00:10 | 0.04 | 03-JAN-12:50 | 0.04 | 03-JAN-12:50 | 0.00 | 01-JAN-00:10 | 0.01 | 03-JAN-12:50 | 0.00 | 01-JAN-00:10 |
February | 99970310.08 | 26372389.66 | 29.33 | 99970310.08 | -0.0 | 0.00 | 0.27 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 2246.14 | 20-FEB-15:00 | 2246.14 | 20-FEB-15:00 | 0.00 | 22-FEB-14:50 | 586.84 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.369612E+09 | 96699867.13 | 74.75 | 0.369612E+09 | 18.45 | 0.00 | 0.41 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3486.27 | 22-MAR-13:00 | 3486.27 | 22-MAR-13:00 | 0.01 | 10-MAR-19:00 | 907.29 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.279968E+10 | 0.737716E+09 | 226.67 | 0.279024E+10 | 9436506.26 | 0.00 | 0.76 | 21-APR-14:00 | 0.00 | 01-APR-00:10 | 7009.41 | 21-APR-14:00 | 7009.41 | 21-APR-14:00 | 333.55 | 18-APR-18:00 | 1932.92 | 21-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.561761E+10 | 0.148905E+10 | 339.06 | 0.545741E+10 | 0.160190E+09 | 0.00 | 1.00 | 30-MAY-06:03 | 0.00 | 01-MAY-00:10 | 15977.10 | 31-MAY-06:03 | 15977.10 | 31-MAY-06:03 | 2298.04 | 28-MAY-07:03 | 3456.56 | 30-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.801576E+10 | 0.218979E+10 | 356.87 | 0.771333E+10 | 0.302429E+09 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 22133.02 | 19-JUN-06:02 | 21406.80 | 03-JUN-06:02 | 5179.81 | 04-JUN-07:03 | 4703.99 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.960479E+10 | 0.245287E+10 | 363.25 | 0.792701E+10 | 0.167778E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 23969.96 | 17-JUL-06:02 | 21672.74 | 03-JUL-06:01 | 13506.53 | 17-JUL-06:02 | 4887.83 | 16-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.847106E+10 | 0.217161E+10 | 367.54 | 0.740606E+10 | 0.106500E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 23871.15 | 03-AUG-06:02 | 21201.01 | 27-AUG-07:02 | 11092.55 | 03-AUG-06:02 | 4839.69 | 06-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.728928E+10 | 0.183546E+10 | 343.33 | 0.636063E+10 | 0.928649E+09 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 23418.80 | 23-SEP-06:02 | 16171.00 | 13-SEP-06:02 | 11316.25 | 14-SEP-06:03 | 4700.81 | 23-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.341104E+10 | 0.848927E+09 | 256.18 | 0.308107E+10 | 0.329972E+09 | 0.00 | 1.00 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 | 21765.71 | 02-OCT-06:02 | 19933.03 | 02-OCT-06:02 | 7368.21 | 04-OCT-06:03 | 4523.08 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.305054E+09 | 77525754.91 | 60.17 | 0.301402E+09 | 3651493.81 | 0.00 | 0.48 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4274.44 | 09-NOV-14:00 | 4274.44 | 09-NOV-14:00 | 298.10 | 03-NOV-12:50 | 1053.52 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.459838E+11 | 0.119260E+11 | 2417.47 | 0.415067E+11 | 0.447711E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.960479E+10 | 0.245287E+10 | 367.54 | 0.792701E+10 | 0.167778E+10 | 0.00 | 1.00 | 0.00 | 23969.96 | 21672.74 | 13506.53 | 4887.83 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 20.78 | 5.59 | 0.17 | 20.78 | -0.0 | 0.00 | 0.00 | 03-JAN-13:10 | 0.00 | 01-JAN-00:10 | 0.03 | 03-JAN-13:10 | 0.03 | 03-JAN-13:10 | 0.00 | 01-JAN-00:10 | 0.01 | 03-JAN-13:10 | 0.00 | 01-JAN-00:10 |
February | 76729961.94 | 20382788.24 | 25.17 | 76729961.94 | -0.0 | 0.00 | 0.24 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 1948.68 | 20-FEB-15:00 | 1948.68 | 20-FEB-15:00 | 0.00 | 22-FEB-15:20 | 513.55 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.310269E+09 | 81632507.24 | 66.08 | 0.310269E+09 | 2.48 | 0.00 | 0.38 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3235.50 | 22-MAR-13:00 | 3235.50 | 22-MAR-13:00 | 0.00 | 10-MAR-19:00 | 847.76 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.265894E+10 | 0.703817E+09 | 221.33 | 0.265005E+10 | 8892127.30 | 0.00 | 0.75 | 21-APR-14:00 | 0.00 | 01-APR-00:10 | 6856.89 | 21-APR-14:00 | 6856.89 | 21-APR-14:00 | 323.32 | 18-APR-18:00 | 1896.44 | 21-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.545474E+10 | 0.145018E+10 | 333.89 | 0.529851E+10 | 0.156232E+09 | 0.00 | 1.00 | 30-MAY-06:03 | 0.00 | 01-MAY-00:10 | 14646.61 | 31-MAY-06:03 | 14646.61 | 31-MAY-06:03 | 1829.56 | 28-MAY-07:03 | 3173.93 | 30-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.785608E+10 | 0.215112E+10 | 356.73 | 0.756008E+10 | 0.295996E+09 | 0.00 | 1.00 | 02-JUN-16:10 | 0.00 | 01-JUN-00:10 | 21991.73 | 19-JUN-06:02 | 21202.40 | 08-JUN-06:02 | 4815.93 | 04-JUN-07:03 | 4673.96 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.943849E+10 | 0.241494E+10 | 363.48 | 0.778159E+10 | 0.165690E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 23818.17 | 17-JUL-06:02 | 21516.50 | 03-JUL-06:01 | 13441.92 | 17-JUL-06:02 | 4856.78 | 16-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.830864E+10 | 0.213418E+10 | 367.17 | 0.726276E+10 | 0.104588E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 23719.74 | 03-AUG-06:02 | 21061.51 | 27-AUG-07:02 | 11055.56 | 03-AUG-06:02 | 4809.00 | 06-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.713367E+10 | 0.180012E+10 | 342.29 | 0.622223E+10 | 0.911439E+09 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 23269.44 | 23-SEP-06:02 | 16036.82 | 13-SEP-06:02 | 10997.02 | 22-SEP-06:02 | 4671.06 | 23-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.328985E+10 | 0.820926E+09 | 250.51 | 0.297051E+10 | 0.319338E+09 | 0.00 | 1.00 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 | 21625.14 | 02-OCT-06:02 | 19774.95 | 02-OCT-06:02 | 6695.27 | 04-OCT-06:03 | 4493.94 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.269037E+09 | 68560871.57 | 53.50 | 0.265751E+09 | 3285189.26 | 0.00 | 0.47 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4095.43 | 09-NOV-14:00 | 4095.43 | 09-NOV-14:00 | 275.05 | 03-NOV-12:50 | 1013.77 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.447965E+11 | 0.116459E+11 | 2380.32 | 0.403985E+11 | 0.439797E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.943849E+10 | 0.241494E+10 | 367.17 | 0.778159E+10 | 0.165690E+10 | 0.00 | 1.00 | 0.00 | 23818.17 | 21516.50 | 13441.92 | 4856.78 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.127349E+09 | 34466360.35 | 22.17 | 0.127349E+09 | -0.0 | 0.00 | 0.24 | 20-FEB-15:20 | 0.00 | 01-FEB-00:10 | 3652.89 | 20-FEB-15:20 | 3652.89 | 20-FEB-15:20 | 0.00 | 20-FEB-15:20 | 978.37 | 20-FEB-15:20 | 0.00 | 01-FEB-00:10 |
March | 0.510030E+09 | 0.137014E+09 | 61.00 | 0.510030E+09 | 0.00 | 0.00 | 0.38 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 5876.49 | 22-MAR-13:00 | 5876.49 | 22-MAR-13:00 | 0.00 | 14-MAR-15:40 | 1568.21 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.482870E+10 | 0.130332E+10 | 218.25 | 0.480847E+10 | 20234198.89 | 0.00 | 0.79 | 21-APR-14:30 | 0.00 | 01-APR-00:10 | 13589.31 | 21-APR-14:30 | 13589.31 | 21-APR-14:30 | 694.45 | 18-APR-17:00 | 3754.62 | 21-APR-14:20 | 0.00 | 01-APR-00:10 |
May | 0.102047E+11 | 0.275640E+10 | 333.08 | 0.987936E+10 | 0.325334E+09 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 28937.21 | 30-MAY-07:03 | 28937.21 | 30-MAY-07:03 | 3464.54 | 24-MAY-13:00 | 6486.45 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.148405E+11 | 0.412482E+10 | 348.69 | 0.142529E+11 | 0.587571E+09 | 0.00 | 1.00 | 01-JUN-14:50 | 0.00 | 01-JUN-00:10 | 40506.30 | 19-JUN-07:02 | 39169.71 | 05-JUN-07:02 | 8476.93 | 04-JUN-08:62 | 8831.42 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.176099E+11 | 0.455373E+10 | 350.46 | 0.144288E+11 | 0.318103E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 43571.86 | 19-JUL-07:03 | 39120.91 | 03-JUL-07:01 | 25326.54 | 19-JUL-07:03 | 9201.52 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.156349E+11 | 0.406316E+10 | 358.38 | 0.135836E+11 | 0.205130E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 43331.15 | 03-AUG-07:02 | 38825.82 | 07-AUG-07:01 | 19169.65 | 14-AUG-07:02 | 9037.49 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.134909E+11 | 0.344293E+10 | 334.81 | 0.116767E+11 | 0.181417E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 42508.70 | 23-SEP-07:03 | 29524.76 | 13-SEP-07:02 | 18493.85 | 14-SEP-07:03 | 8859.19 | 10-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.604378E+10 | 0.153035E+10 | 240.47 | 0.538415E+10 | 0.659633E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 39732.94 | 02-OCT-07:02 | 34209.48 | 02-OCT-07:02 | 11040.74 | 05-OCT-07:03 | 8313.37 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.449988E+09 | 0.116816E+09 | 46.83 | 0.443106E+09 | 6881811.29 | 0.00 | 0.46 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 7383.67 | 09-NOV-14:00 | 7383.67 | 09-NOV-14:00 | 562.21 | 03-NOV-13:00 | 1863.41 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.837406E+11 | 0.220630E+11 | 2314.14 | 0.750945E+11 | 0.864615E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.176099E+11 | 0.455373E+10 | 358.38 | 0.144288E+11 | 0.318103E+10 | 0.00 | 1.00 | 0.00 | 43571.86 | 39169.71 | 25326.54 | 9201.52 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 56208037.87 | 14985226.63 | 21.33 | 56208037.87 | 0.00 | 0.00 | 0.23 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 1789.13 | 20-FEB-15:30 | 1789.13 | 20-FEB-15:30 | 0.00 | 19-FEB-16:00 | 472.27 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 0.238181E+09 | 63020198.92 | 56.83 | 0.238181E+09 | -0.0 | 0.00 | 0.37 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 2915.60 | 22-MAR-13:00 | 2915.60 | 22-MAR-13:00 | 0.00 | 14-MAR-16:20 | 767.29 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.246110E+10 | 0.653292E+09 | 216.08 | 0.245177E+10 | 9327750.74 | 0.00 | 0.79 | 21-APR-14:30 | 0.00 | 01-APR-00:10 | 7015.02 | 21-APR-14:40 | 7015.02 | 21-APR-14:40 | 338.23 | 18-APR-17:00 | 1904.46 | 21-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.524886E+10 | 0.139358E+10 | 331.08 | 0.508683E+10 | 0.162031E+09 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 14692.94 | 30-MAY-07:03 | 14692.94 | 30-MAY-07:03 | 1759.80 | 24-MAY-13:00 | 3236.13 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.764390E+10 | 0.208868E+10 | 349.36 | 0.735206E+10 | 0.291839E+09 | 0.00 | 1.00 | 01-JUN-14:40 | 0.00 | 01-JUN-00:10 | 20915.95 | 19-JUN-07:02 | 20273.45 | 05-JUN-07:02 | 4051.79 | 04-JUN-08:62 | 4480.81 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.906951E+10 | 0.230589E+10 | 352.15 | 0.745406E+10 | 0.161545E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 22403.84 | 18-JUL-07:03 | 20204.15 | 03-JUL-07:01 | 12219.72 | 19-JUL-07:03 | 4667.14 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.804785E+10 | 0.205624E+10 | 358.42 | 0.701371E+10 | 0.103414E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 22373.22 | 03-AUG-07:02 | 20186.16 | 07-AUG-07:01 | 9853.24 | 14-AUG-07:02 | 4583.38 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.694127E+10 | 0.174139E+10 | 334.33 | 0.602649E+10 | 0.914774E+09 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 21948.80 | 23-SEP-07:03 | 15315.53 | 13-SEP-07:02 | 8989.09 | 23-SEP-07:03 | 4458.99 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.309717E+10 | 0.770881E+09 | 237.94 | 0.276711E+10 | 0.330059E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 20515.39 | 02-OCT-07:02 | 17764.12 | 02-OCT-07:02 | 5249.78 | 05-OCT-07:03 | 4217.19 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.221515E+09 | 56530012.56 | 45.00 | 0.218472E+09 | 3043332.14 | 0.00 | 0.46 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3772.27 | 09-NOV-14:00 | 3772.27 | 09-NOV-14:00 | 265.69 | 03-NOV-13:00 | 936.52 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.430256E+11 | 0.111445E+11 | 2302.53 | 0.386649E+11 | 0.436067E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.906951E+10 | 0.230589E+10 | 358.42 | 0.745406E+10 | 0.161545E+10 | 0.00 | 1.00 | 0.00 | 22403.84 | 20273.45 | 12219.72 | 4667.14 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 122.70 | 33.03 | 1.00 | 122.70 | 0.00 | 0.00 | 0.00 | 03-JAN-17:00 | 0.00 | 01-JAN-00:10 | 0.07 | 03-JAN-17:00 | 0.07 | 03-JAN-17:00 | 0.00 | 03-JAN-16:50 | 0.02 | 03-JAN-17:00 | 0.00 | 01-JAN-00:10 |
February | 49952883.14 | 13342014.04 | 20.83 | 49952883.14 | -0.0 | 0.00 | 0.22 | 20-FEB-15:40 | 0.00 | 01-FEB-00:10 | 1704.27 | 20-FEB-15:40 | 1704.27 | 20-FEB-15:40 | 0.00 | 21-FEB-16:00 | 451.01 | 20-FEB-15:40 | 0.00 | 01-FEB-00:10 |
March | 0.219362E+09 | 58175928.67 | 53.50 | 0.219362E+09 | 0.00 | 0.00 | 0.36 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 2818.24 | 22-MAR-13:00 | 2818.24 | 22-MAR-13:00 | 0.00 | 14-MAR-16:10 | 743.67 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.240903E+10 | 0.640482E+09 | 213.50 | 0.239995E+10 | 9082329.53 | 0.00 | 0.79 | 21-APR-14:30 | 0.00 | 01-APR-00:10 | 6955.66 | 21-APR-14:40 | 6955.66 | 21-APR-14:40 | 333.08 | 18-APR-17:00 | 1889.91 | 21-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.519697E+10 | 0.138067E+10 | 329.50 | 0.503638E+10 | 0.160596E+09 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 14208.87 | 30-MAY-07:03 | 14208.87 | 30-MAY-07:03 | 1750.46 | 24-MAY-13:00 | 3129.86 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.759745E+10 | 0.207655E+10 | 349.36 | 0.730765E+10 | 0.289804E+09 | 0.00 | 1.00 | 01-JUN-14:40 | 0.00 | 01-JUN-00:10 | 20827.39 | 19-JUN-07:02 | 20187.38 | 05-JUN-07:02 | 3990.91 | 04-JUN-08:62 | 4461.09 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.902063E+10 | 0.229370E+10 | 352.19 | 0.741188E+10 | 0.160875E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 22309.60 | 18-JUL-07:03 | 20117.09 | 03-JUL-07:01 | 11904.42 | 19-JUL-07:03 | 4647.21 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.800421E+10 | 0.204532E+10 | 358.42 | 0.697520E+10 | 0.102901E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 22279.24 | 03-AUG-07:02 | 20090.16 | 07-AUG-07:01 | 9817.09 | 14-AUG-07:02 | 4563.79 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.689904E+10 | 0.173109E+10 | 333.99 | 0.598886E+10 | 0.910185E+09 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 21856.28 | 23-SEP-07:03 | 15242.62 | 13-SEP-07:02 | 8960.19 | 23-SEP-07:03 | 4440.19 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.305724E+10 | 0.761425E+09 | 236.35 | 0.273108E+10 | 0.326154E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 20428.50 | 02-OCT-07:02 | 17679.92 | 02-OCT-07:02 | 5140.96 | 05-OCT-07:03 | 4199.34 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.209005E+09 | 53403683.95 | 41.83 | 0.206106E+09 | 2898901.97 | 0.00 | 0.45 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3693.21 | 09-NOV-14:00 | 3693.21 | 09-NOV-14:00 | 255.56 | 03-NOV-13:00 | 918.66 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.426629E+11 | 0.110542E+11 | 2290.48 | 0.383264E+11 | 0.433648E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.902063E+10 | 0.229370E+10 | 358.42 | 0.741188E+10 | 0.160875E+10 | 0.00 | 1.00 | 0.00 | 22309.60 | 20187.38 | 11904.42 | 4647.21 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 35630826.12 | 9562773.93 | 17.00 | 35630826.12 | 0.00 | 0.00 | 0.20 | 20-FEB-15:40 | 0.00 | 01-FEB-00:10 | 1495.89 | 20-FEB-15:40 | 1495.89 | 20-FEB-15:40 | 0.00 | 20-FEB-16:20 | 398.60 | 20-FEB-15:40 | 0.00 | 01-FEB-00:10 |
March | 0.178397E+09 | 47604673.72 | 45.50 | 0.178397E+09 | -0.0 | 0.00 | 0.33 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 2597.23 | 22-MAR-13:00 | 2597.23 | 22-MAR-13:00 | 0.00 | 22-MAR-14:20 | 690.27 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.228945E+10 | 0.611619E+09 | 207.00 | 0.228111E+10 | 8343969.48 | 0.00 | 0.78 | 21-APR-14:30 | 0.00 | 01-APR-00:10 | 6840.90 | 21-APR-14:40 | 6840.90 | 21-APR-14:40 | 315.95 | 18-APR-17:00 | 1865.03 | 21-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.509573E+10 | 0.135702E+10 | 326.56 | 0.493881E+10 | 0.156914E+09 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 12188.66 | 30-MAY-07:03 | 12188.66 | 30-MAY-07:03 | 1736.58 | 24-MAY-13:00 | 2686.35 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.756382E+10 | 0.206913E+10 | 349.15 | 0.727782E+10 | 0.286003E+09 | 0.00 | 1.00 | 01-JUN-14:40 | 0.00 | 01-JUN-00:10 | 20844.88 | 19-JUN-07:02 | 20113.47 | 18-JUN-08:62 | 3710.40 | 04-JUN-08:62 | 4462.47 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.901223E+10 | 0.229232E+10 | 351.50 | 0.740793E+10 | 0.160430E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 22328.62 | 18-JUL-07:03 | 20136.44 | 03-JUL-07:01 | 10638.87 | 19-JUL-07:03 | 4650.56 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.800652E+10 | 0.204593E+10 | 357.93 | 0.698178E+10 | 0.102474E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 22298.73 | 03-AUG-07:02 | 20102.82 | 07-AUG-07:01 | 9833.74 | 14-AUG-07:02 | 4567.48 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.688738E+10 | 0.172843E+10 | 333.53 | 0.597972E+10 | 0.907661E+09 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 21875.65 | 23-SEP-07:03 | 15246.91 | 13-SEP-07:02 | 8977.57 | 23-SEP-07:03 | 4444.29 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.298146E+10 | 0.743960E+09 | 229.97 | 0.266372E+10 | 0.317734E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 20446.00 | 02-OCT-07:02 | 17687.02 | 02-OCT-07:02 | 4811.38 | 05-OCT-07:03 | 4202.96 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.183436E+09 | 47028159.45 | 35.83 | 0.180900E+09 | 2536034.33 | 0.00 | 0.43 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3546.38 | 09-NOV-14:00 | 3546.38 | 09-NOV-14:00 | 229.14 | 03-NOV-13:00 | 886.19 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.422341E+11 | 0.109526E+11 | 2253.96 | 0.379258E+11 | 0.430824E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.901223E+10 | 0.229232E+10 | 357.93 | 0.740793E+10 | 0.160430E+10 | 0.00 | 1.00 | 0.00 | 22328.62 | 20136.44 | 10638.87 | 4650.56 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 23077779.45 | 6242879.25 | 12.67 | 23077779.45 | 0.00 | 0.00 | 0.16 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 1341.35 | 20-FEB-15:30 | 1341.35 | 20-FEB-15:30 | 0.00 | 20-FEB-15:40 | 360.80 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 0.147085E+09 | 39623698.46 | 39.00 | 0.147085E+09 | 0.00 | 0.00 | 0.30 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 2570.99 | 22-MAR-13:00 | 2570.99 | 22-MAR-13:00 | 0.00 | 21-MAR-16:50 | 689.37 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.244118E+10 | 0.654464E+09 | 202.58 | 0.243410E+10 | 7081563.26 | 0.00 | 0.76 | 21-APR-14:10 | 0.00 | 01-APR-00:10 | 7362.33 | 21-APR-14:20 | 7362.33 | 21-APR-14:20 | 273.84 | 18-APR-17:00 | 2020.92 | 21-APR-14:10 | 0.00 | 01-APR-00:10 |
May | 0.565590E+10 | 0.150638E+10 | 325.67 | 0.549259E+10 | 0.163315E+09 | 0.00 | 0.91 | 31-MAY-07:03 | 0.00 | 01-MAY-00:10 | 9569.91 | 31-MAY-07:03 | 9569.91 | 31-MAY-07:03 | 1799.66 | 24-MAY-13:00 | 2493.05 | 30-MAY-14:10 | 0.00 | 01-MAY-00:10 |
June | 0.862189E+10 | 0.234894E+10 | 347.10 | 0.831632E+10 | 0.305565E+09 | 0.00 | 1.00 | 01-JUN-15:00 | 0.00 | 01-JUN-00:10 | 23183.47 | 19-JUN-07:02 | 22462.13 | 18-JUN-08:62 | 3836.50 | 04-JUN-08:62 | 4975.91 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.103460E+11 | 0.262140E+10 | 352.63 | 0.858992E+10 | 0.175605E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 24774.59 | 17-JUL-07:02 | 22430.10 | 03-JUL-07:01 | 10791.76 | 18-JUL-07:03 | 5178.01 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.930924E+10 | 0.236167E+10 | 356.42 | 0.818702E+10 | 0.112222E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24753.90 | 03-AUG-07:02 | 22022.39 | 27-AUG-08:62 | 10744.40 | 14-AUG-07:02 | 5100.04 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.803190E+10 | 0.199985E+10 | 332.22 | 0.702834E+10 | 0.100355E+10 | 0.00 | 1.00 | 02-SEP-07:03 | 0.00 | 01-SEP-00:05 | 24162.64 | 03-SEP-08:62 | 16790.13 | 13-SEP-07:02 | 9438.73 | 23-SEP-07:03 | 4927.89 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.329755E+10 | 0.822243E+09 | 225.11 | 0.296574E+10 | 0.331815E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 22677.71 | 02-OCT-07:02 | 19628.46 | 02-OCT-07:02 | 4316.65 | 05-OCT-07:03 | 4661.24 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.180939E+09 | 46503804.21 | 31.50 | 0.178894E+09 | 2045315.59 | 0.00 | 0.42 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3789.26 | 09-NOV-14:00 | 3789.26 | 09-NOV-14:00 | 209.64 | 03-NOV-13:00 | 950.56 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.480547E+11 | 0.124073E+11 | 2224.90 | 0.433631E+11 | 0.469164E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.103460E+11 | 0.262140E+10 | 356.42 | 0.858992E+10 | 0.175605E+10 | 0.00 | 1.00 | 0.00 | 24774.59 | 22462.13 | 10791.76 | 5178.01 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 119.49 | 39.98 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 112.17 | 35.63 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 93.77 | 32.07 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.74 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.66 | 11.63 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 54.27 | 5.72 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 55.16 | 4.62 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 66.37 | 6.79 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.73 | 13.83 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.56 | 22.71 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 125.49 | 36.57 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 120.76 | 43.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.79 | 22.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.66 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 125.49 | 43.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 119.49 | 39.98 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 112.17 | 35.63 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 93.77 | 32.07 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.74 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.66 | 11.63 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 54.27 | 5.72 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 55.16 | 4.62 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 66.37 | 6.79 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.73 | 13.83 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.56 | 22.71 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 125.49 | 36.57 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 120.76 | 43.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.79 | 22.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.66 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 125.49 | 43.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 119.49 | 39.98 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 112.17 | 35.63 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 93.77 | 32.07 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.74 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.66 | 11.63 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 54.27 | 5.72 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 55.16 | 4.62 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 66.37 | 6.79 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.73 | 13.83 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.56 | 22.71 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 125.49 | 36.57 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 120.76 | 43.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.79 | 22.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.66 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 125.49 | 43.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 119.49 | 39.98 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 112.17 | 35.63 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 93.77 | 32.07 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.74 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.66 | 11.63 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 54.27 | 5.72 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 55.16 | 4.62 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 66.37 | 6.79 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.73 | 13.83 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.56 | 22.71 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 125.49 | 36.57 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 120.76 | 43.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.79 | 22.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.66 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 125.49 | 43.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.70 | 63.68 | 20.02 | 143.74 | 47.83 | 0.00 | 0.00 | 0.00 |
February | 75.84 | 53.24 | 22.60 | 134.93 | 42.66 | 0.00 | 0.00 | 0.00 |
March | 59.45 | 33.09 | 26.36 | 112.82 | 38.42 | 0.00 | 0.00 | 0.00 |
April | 39.23 | 12.77 | 26.46 | 83.78 | 23.82 | 0.00 | 0.00 | 0.00 |
May | 28.39 | 2.74 | 25.66 | 64.29 | 14.06 | 0.00 | 0.00 | 0.00 |
June | 24.98 | 0.87 | 24.10 | 64.86 | 6.93 | 0.00 | 0.00 | 0.00 |
July | 25.31 | 1.50 | 23.80 | 66.02 | 5.58 | 0.00 | 0.00 | 0.00 |
August | 31.41 | 6.82 | 24.59 | 79.53 | 8.19 | 0.00 | 0.00 | 0.00 |
September | 49.04 | 23.96 | 25.08 | 113.71 | 16.64 | 0.00 | 0.00 | 0.00 |
October | 69.19 | 46.21 | 22.98 | 136.47 | 27.24 | 0.00 | 0.00 | 0.00 |
November | 85.57 | 65.29 | 20.28 | 150.89 | 43.80 | 0.00 | 0.00 | 0.00 |
December | 86.10 | 65.01 | 21.09 | 145.22 | 52.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.73 | 31.15 | 23.59 | 107.85 | 27.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.98 | 0.87 | 20.02 | 64.29 | 5.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 86.10 | 65.29 | 26.46 | 150.89 | 52.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.70 | 63.68 | 20.02 | 143.74 | 47.83 | 0.00 | 0.00 | 0.00 |
February | 75.84 | 53.24 | 22.60 | 134.93 | 42.66 | 0.00 | 0.00 | 0.00 |
March | 59.45 | 33.09 | 26.36 | 112.82 | 38.42 | 0.00 | 0.00 | 0.00 |
April | 39.23 | 12.77 | 26.46 | 83.78 | 23.82 | 0.00 | 0.00 | 0.00 |
May | 28.39 | 2.74 | 25.66 | 64.29 | 14.06 | 0.00 | 0.00 | 0.00 |
June | 24.98 | 0.87 | 24.10 | 64.86 | 6.93 | 0.00 | 0.00 | 0.00 |
July | 25.31 | 1.50 | 23.80 | 66.02 | 5.58 | 0.00 | 0.00 | 0.00 |
August | 31.41 | 6.82 | 24.59 | 79.53 | 8.19 | 0.00 | 0.00 | 0.00 |
September | 49.04 | 23.96 | 25.08 | 113.71 | 16.64 | 0.00 | 0.00 | 0.00 |
October | 69.19 | 46.21 | 22.98 | 136.47 | 27.24 | 0.00 | 0.00 | 0.00 |
November | 85.57 | 65.29 | 20.28 | 150.89 | 43.80 | 0.00 | 0.00 | 0.00 |
December | 86.10 | 65.01 | 21.09 | 145.22 | 52.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.73 | 31.15 | 23.59 | 107.85 | 27.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.98 | 0.87 | 20.02 | 64.29 | 5.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 86.10 | 65.29 | 26.46 | 150.89 | 52.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 118.36 | 42.50 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 110.91 | 37.87 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 92.57 | 33.83 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.28 | 20.40 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.65 | 11.79 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 54.56 | 5.78 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 55.50 | 4.62 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 66.68 | 6.76 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.89 | 13.69 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.40 | 22.83 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 124.73 | 37.71 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 119.65 | 46.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.38 | 23.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.65 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 124.73 | 46.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 118.36 | 42.50 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 110.91 | 37.87 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 92.57 | 33.83 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.28 | 20.40 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.65 | 11.79 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 54.56 | 5.78 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 55.50 | 4.62 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 66.68 | 6.76 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.89 | 13.69 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.40 | 22.83 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 124.73 | 37.71 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 119.65 | 46.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.38 | 23.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.65 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 124.73 | 46.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.70 | 63.68 | 20.02 | 142.42 | 50.82 | 0.00 | 0.00 | 0.00 |
February | 75.84 | 53.24 | 22.60 | 133.45 | 45.32 | 0.00 | 0.00 | 0.00 |
March | 59.45 | 33.09 | 26.36 | 111.41 | 40.52 | 0.00 | 0.00 | 0.00 |
April | 39.23 | 12.77 | 26.46 | 83.25 | 24.53 | 0.00 | 0.00 | 0.00 |
May | 28.39 | 2.74 | 25.66 | 64.28 | 14.25 | 0.00 | 0.00 | 0.00 |
June | 24.98 | 0.87 | 24.10 | 65.20 | 7.00 | 0.00 | 0.00 | 0.00 |
July | 25.31 | 1.50 | 23.80 | 66.42 | 5.59 | 0.00 | 0.00 | 0.00 |
August | 31.41 | 6.82 | 24.59 | 79.90 | 8.15 | 0.00 | 0.00 | 0.00 |
September | 49.04 | 23.96 | 25.08 | 113.91 | 16.47 | 0.00 | 0.00 | 0.00 |
October | 69.19 | 46.21 | 22.98 | 136.30 | 27.39 | 0.00 | 0.00 | 0.00 |
November | 85.57 | 65.29 | 20.28 | 150.01 | 45.15 | 0.00 | 0.00 | 0.00 |
December | 86.10 | 65.01 | 21.09 | 143.92 | 55.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.73 | 31.15 | 23.59 | 107.37 | 28.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.98 | 0.87 | 20.02 | 64.28 | 5.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 86.10 | 65.29 | 26.46 | 150.01 | 55.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 118.64 | 41.82 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 111.11 | 37.51 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 92.68 | 33.79 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.10 | 21.20 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.20 | 12.83 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.49 | 6.53 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 54.40 | 5.44 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.83 | 7.69 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.64 | 15.11 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.25 | 23.87 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 124.87 | 37.88 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 119.92 | 45.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.12 | 24.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.20 | 5.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 124.87 | 45.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 118.64 | 41.82 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 111.11 | 37.51 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 92.68 | 33.79 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.10 | 21.20 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.20 | 12.83 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.49 | 6.53 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 54.40 | 5.44 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.83 | 7.69 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.64 | 15.11 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.25 | 23.87 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 124.87 | 37.88 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 119.92 | 45.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.12 | 24.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.20 | 5.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 124.87 | 45.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.24 | 63.33 | 19.91 | 141.97 | 49.74 | 0.00 | 0.00 | 0.00 |
February | 75.42 | 52.95 | 22.48 | 132.96 | 44.65 | 0.00 | 0.00 | 0.00 |
March | 59.12 | 32.90 | 26.22 | 110.93 | 40.26 | 0.00 | 0.00 | 0.00 |
April | 39.02 | 12.70 | 26.32 | 82.58 | 25.35 | 0.00 | 0.00 | 0.00 |
May | 28.24 | 2.72 | 25.52 | 63.41 | 15.41 | 0.00 | 0.00 | 0.00 |
June | 24.84 | 0.87 | 23.97 | 63.60 | 7.87 | 0.00 | 0.00 | 0.00 |
July | 25.17 | 1.50 | 23.67 | 64.78 | 6.54 | 0.00 | 0.00 | 0.00 |
August | 31.24 | 6.78 | 24.46 | 78.48 | 9.22 | 0.00 | 0.00 | 0.00 |
September | 48.77 | 23.83 | 24.94 | 113.00 | 18.06 | 0.00 | 0.00 | 0.00 |
October | 68.81 | 45.96 | 22.85 | 135.38 | 28.46 | 0.00 | 0.00 | 0.00 |
November | 85.11 | 64.93 | 20.17 | 149.35 | 45.10 | 0.00 | 0.00 | 0.00 |
December | 85.63 | 64.65 | 20.98 | 143.44 | 54.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.44 | 30.98 | 23.46 | 106.49 | 28.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.84 | 0.87 | 19.91 | 63.41 | 6.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.63 | 64.93 | 26.32 | 149.35 | 54.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 118.87 | 41.17 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 111.33 | 36.98 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 92.86 | 33.41 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.14 | 21.11 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.18 | 12.87 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.43 | 6.62 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 54.33 | 5.54 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.78 | 7.78 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.62 | 15.20 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.25 | 23.85 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 124.98 | 37.60 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 120.13 | 44.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.19 | 23.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.18 | 5.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 124.98 | 44.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 118.87 | 41.17 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 111.33 | 36.98 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 92.86 | 33.41 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.14 | 21.11 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.18 | 12.87 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.43 | 6.62 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 54.33 | 5.54 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.78 | 7.78 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.62 | 15.20 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.25 | 23.85 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 124.98 | 37.60 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 120.13 | 44.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.19 | 23.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.18 | 5.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 124.98 | 44.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.24 | 63.33 | 19.91 | 142.25 | 48.97 | 0.00 | 0.00 | 0.00 |
February | 75.42 | 52.95 | 22.48 | 133.21 | 44.02 | 0.00 | 0.00 | 0.00 |
March | 59.12 | 32.90 | 26.22 | 111.15 | 39.80 | 0.00 | 0.00 | 0.00 |
April | 39.02 | 12.70 | 26.32 | 82.62 | 25.24 | 0.00 | 0.00 | 0.00 |
May | 28.24 | 2.72 | 25.52 | 63.38 | 15.46 | 0.00 | 0.00 | 0.00 |
June | 24.84 | 0.87 | 23.97 | 63.53 | 7.98 | 0.00 | 0.00 | 0.00 |
July | 25.17 | 1.50 | 23.67 | 64.70 | 6.65 | 0.00 | 0.00 | 0.00 |
August | 31.24 | 6.78 | 24.46 | 78.43 | 9.33 | 0.00 | 0.00 | 0.00 |
September | 48.77 | 23.83 | 24.94 | 112.98 | 18.17 | 0.00 | 0.00 | 0.00 |
October | 68.81 | 45.96 | 22.85 | 135.38 | 28.44 | 0.00 | 0.00 | 0.00 |
November | 85.11 | 64.93 | 20.17 | 149.48 | 44.77 | 0.00 | 0.00 | 0.00 |
December | 85.63 | 64.65 | 20.98 | 143.70 | 53.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.44 | 30.98 | 23.46 | 106.57 | 28.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.84 | 0.87 | 19.91 | 63.38 | 6.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.63 | 64.93 | 26.32 | 149.48 | 53.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 119.18 | 40.49 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 111.65 | 36.34 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 93.18 | 32.87 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.28 | 20.83 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.26 | 12.70 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.52 | 6.50 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 54.41 | 5.42 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.84 | 7.65 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.67 | 15.05 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.32 | 23.66 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 125.18 | 37.23 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 120.43 | 44.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.35 | 23.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.26 | 5.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 125.18 | 44.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 119.18 | 40.49 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 111.65 | 36.34 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 93.18 | 32.87 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.28 | 20.83 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.26 | 12.70 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.52 | 6.50 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 54.41 | 5.42 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.84 | 7.65 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.67 | 15.05 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.32 | 23.66 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 125.18 | 37.23 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 120.43 | 44.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.35 | 23.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.26 | 5.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 125.18 | 44.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.24 | 63.33 | 19.91 | 142.61 | 48.16 | 0.00 | 0.00 | 0.00 |
February | 75.42 | 52.95 | 22.48 | 133.60 | 43.27 | 0.00 | 0.00 | 0.00 |
March | 59.12 | 32.90 | 26.22 | 111.53 | 39.17 | 0.00 | 0.00 | 0.00 |
April | 39.02 | 12.70 | 26.32 | 82.79 | 24.90 | 0.00 | 0.00 | 0.00 |
May | 28.24 | 2.72 | 25.52 | 63.48 | 15.26 | 0.00 | 0.00 | 0.00 |
June | 24.84 | 0.87 | 23.97 | 63.64 | 7.83 | 0.00 | 0.00 | 0.00 |
July | 25.17 | 1.50 | 23.67 | 64.79 | 6.51 | 0.00 | 0.00 | 0.00 |
August | 31.24 | 6.78 | 24.46 | 78.50 | 9.18 | 0.00 | 0.00 | 0.00 |
September | 48.77 | 23.83 | 24.94 | 113.04 | 17.99 | 0.00 | 0.00 | 0.00 |
October | 68.81 | 45.96 | 22.85 | 135.47 | 28.21 | 0.00 | 0.00 | 0.00 |
November | 85.11 | 64.93 | 20.17 | 149.72 | 44.33 | 0.00 | 0.00 | 0.00 |
December | 85.63 | 64.65 | 20.98 | 144.06 | 52.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.44 | 30.98 | 23.46 | 106.77 | 28.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.84 | 0.87 | 19.91 | 63.48 | 6.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.63 | 64.93 | 26.32 | 149.72 | 52.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 119.70 | 39.28 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 112.21 | 35.22 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 93.69 | 31.83 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.39 | 20.16 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.10 | 12.23 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.32 | 6.19 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 54.15 | 5.12 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.58 | 7.30 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.43 | 14.62 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.31 | 23.20 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 125.51 | 36.48 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 120.94 | 43.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.47 | 22.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.10 | 5.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 125.51 | 43.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 119.70 | 39.28 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 112.21 | 35.22 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 93.69 | 31.83 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.39 | 20.16 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.10 | 12.23 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.32 | 6.19 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 54.15 | 5.12 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.58 | 7.30 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.43 | 14.62 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.31 | 23.20 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 125.51 | 36.48 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 120.94 | 43.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.47 | 22.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.10 | 5.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 125.51 | 43.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 119.70 | 39.28 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 112.21 | 35.22 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 93.69 | 31.83 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.39 | 20.16 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.10 | 12.23 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.32 | 6.19 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 54.15 | 5.12 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.58 | 7.30 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.43 | 14.62 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.31 | 23.20 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 125.51 | 36.48 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 120.94 | 43.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.47 | 22.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.10 | 5.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 125.51 | 43.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 119.70 | 39.28 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 112.21 | 35.22 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 93.69 | 31.83 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.39 | 20.16 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.10 | 12.23 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.32 | 6.19 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 54.15 | 5.12 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.58 | 7.30 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.43 | 14.62 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.31 | 23.20 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 125.51 | 36.48 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 120.94 | 43.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.47 | 22.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.10 | 5.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 125.51 | 43.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.24 | 63.33 | 19.91 | 143.20 | 46.73 | 0.00 | 0.00 | 0.00 |
February | 75.42 | 52.95 | 22.48 | 134.24 | 41.94 | 0.00 | 0.00 | 0.00 |
March | 59.12 | 32.90 | 26.22 | 112.11 | 37.93 | 0.00 | 0.00 | 0.00 |
April | 39.02 | 12.70 | 26.32 | 82.93 | 24.10 | 0.00 | 0.00 | 0.00 |
May | 28.24 | 2.72 | 25.52 | 63.29 | 14.69 | 0.00 | 0.00 | 0.00 |
June | 24.84 | 0.87 | 23.97 | 63.42 | 7.46 | 0.00 | 0.00 | 0.00 |
July | 25.17 | 1.50 | 23.67 | 64.49 | 6.15 | 0.00 | 0.00 | 0.00 |
August | 31.24 | 6.78 | 24.46 | 78.19 | 8.76 | 0.00 | 0.00 | 0.00 |
September | 48.77 | 23.83 | 24.94 | 112.75 | 17.48 | 0.00 | 0.00 | 0.00 |
October | 68.81 | 45.96 | 22.85 | 135.43 | 27.67 | 0.00 | 0.00 | 0.00 |
November | 85.11 | 64.93 | 20.17 | 150.09 | 43.44 | 0.00 | 0.00 | 0.00 |
December | 85.63 | 64.65 | 20.98 | 144.65 | 51.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.44 | 30.98 | 23.46 | 106.89 | 27.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.84 | 0.87 | 19.91 | 63.29 | 6.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.63 | 64.93 | 26.32 | 150.09 | 51.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.24 | 63.33 | 19.91 | 143.20 | 46.73 | 0.00 | 0.00 | 0.00 |
February | 75.42 | 52.95 | 22.48 | 134.24 | 41.94 | 0.00 | 0.00 | 0.00 |
March | 59.12 | 32.90 | 26.22 | 112.11 | 37.93 | 0.00 | 0.00 | 0.00 |
April | 39.02 | 12.70 | 26.32 | 82.93 | 24.10 | 0.00 | 0.00 | 0.00 |
May | 28.24 | 2.72 | 25.52 | 63.29 | 14.69 | 0.00 | 0.00 | 0.00 |
June | 24.84 | 0.87 | 23.97 | 63.42 | 7.46 | 0.00 | 0.00 | 0.00 |
July | 25.17 | 1.50 | 23.67 | 64.49 | 6.15 | 0.00 | 0.00 | 0.00 |
August | 31.24 | 6.78 | 24.46 | 78.19 | 8.76 | 0.00 | 0.00 | 0.00 |
September | 48.77 | 23.83 | 24.94 | 112.75 | 17.48 | 0.00 | 0.00 | 0.00 |
October | 68.81 | 45.96 | 22.85 | 135.43 | 27.67 | 0.00 | 0.00 | 0.00 |
November | 85.11 | 64.93 | 20.17 | 150.09 | 43.44 | 0.00 | 0.00 | 0.00 |
December | 85.63 | 64.65 | 20.98 | 144.65 | 51.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.44 | 30.98 | 23.46 | 106.89 | 27.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.84 | 0.87 | 19.91 | 63.29 | 6.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.63 | 64.93 | 26.32 | 150.09 | 51.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 119.53 | 39.18 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 112.06 | 35.12 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 93.57 | 31.69 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.33 | 20.02 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.13 | 12.07 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.49 | 6.04 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 54.28 | 4.97 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.65 | 7.14 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.38 | 14.45 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.17 | 23.08 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 125.37 | 36.40 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 120.79 | 43.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.42 | 22.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.13 | 4.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 125.37 | 43.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 119.53 | 39.18 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 112.06 | 35.12 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 93.57 | 31.69 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.33 | 20.02 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.13 | 12.07 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.49 | 6.04 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 54.28 | 4.97 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.65 | 7.14 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.38 | 14.45 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.17 | 23.08 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 125.37 | 36.40 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 120.79 | 43.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.42 | 22.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.13 | 4.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 125.37 | 43.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.24 | 63.33 | 19.91 | 143.04 | 46.61 | 0.00 | 0.00 | 0.00 |
February | 75.42 | 52.95 | 22.48 | 134.09 | 41.82 | 0.00 | 0.00 | 0.00 |
March | 59.12 | 32.90 | 26.22 | 111.99 | 37.77 | 0.00 | 0.00 | 0.00 |
April | 39.02 | 12.70 | 26.32 | 82.86 | 23.94 | 0.00 | 0.00 | 0.00 |
May | 28.24 | 2.72 | 25.52 | 63.33 | 14.50 | 0.00 | 0.00 | 0.00 |
June | 24.84 | 0.87 | 23.97 | 63.61 | 7.28 | 0.00 | 0.00 | 0.00 |
July | 25.17 | 1.50 | 23.67 | 64.64 | 5.98 | 0.00 | 0.00 | 0.00 |
August | 31.24 | 6.78 | 24.46 | 78.27 | 8.57 | 0.00 | 0.00 | 0.00 |
September | 48.77 | 23.83 | 24.94 | 112.70 | 17.27 | 0.00 | 0.00 | 0.00 |
October | 68.81 | 45.96 | 22.85 | 135.29 | 27.53 | 0.00 | 0.00 | 0.00 |
November | 85.11 | 64.93 | 20.17 | 149.95 | 43.34 | 0.00 | 0.00 | 0.00 |
December | 85.63 | 64.65 | 20.98 | 144.49 | 51.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.44 | 30.98 | 23.46 | 106.85 | 27.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.84 | 0.87 | 19.91 | 63.33 | 5.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.63 | 64.93 | 26.32 | 149.95 | 51.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 119.64 | 38.94 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 112.19 | 34.87 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 93.73 | 31.43 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.42 | 19.88 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.18 | 12.01 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.53 | 6.01 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 54.31 | 4.94 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.67 | 7.11 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.40 | 14.41 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.21 | 23.01 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 125.49 | 36.20 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 120.88 | 42.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.50 | 22.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.18 | 4.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 125.49 | 42.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 119.64 | 38.94 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 112.19 | 34.87 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 93.73 | 31.43 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.42 | 19.88 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.18 | 12.01 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.53 | 6.01 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 54.31 | 4.94 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.67 | 7.11 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.40 | 14.41 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.21 | 23.01 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 125.49 | 36.20 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 120.88 | 42.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.50 | 22.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.18 | 4.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 125.49 | 42.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.24 | 63.33 | 19.91 | 143.17 | 46.32 | 0.00 | 0.00 | 0.00 |
February | 75.42 | 52.95 | 22.48 | 134.24 | 41.53 | 0.00 | 0.00 | 0.00 |
March | 59.12 | 32.90 | 26.22 | 112.19 | 37.46 | 0.00 | 0.00 | 0.00 |
April | 39.02 | 12.70 | 26.32 | 82.96 | 23.78 | 0.00 | 0.00 | 0.00 |
May | 28.24 | 2.72 | 25.52 | 63.38 | 14.43 | 0.00 | 0.00 | 0.00 |
June | 24.84 | 0.87 | 23.97 | 63.65 | 7.25 | 0.00 | 0.00 | 0.00 |
July | 25.17 | 1.50 | 23.67 | 64.68 | 5.94 | 0.00 | 0.00 | 0.00 |
August | 31.24 | 6.78 | 24.46 | 78.30 | 8.53 | 0.00 | 0.00 | 0.00 |
September | 48.77 | 23.83 | 24.94 | 112.72 | 17.22 | 0.00 | 0.00 | 0.00 |
October | 68.81 | 45.96 | 22.85 | 135.34 | 27.44 | 0.00 | 0.00 | 0.00 |
November | 85.11 | 64.93 | 20.17 | 150.10 | 43.11 | 0.00 | 0.00 | 0.00 |
December | 85.63 | 64.65 | 20.98 | 144.60 | 51.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.44 | 30.98 | 23.46 | 106.94 | 26.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.84 | 0.87 | 19.91 | 63.38 | 5.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.63 | 64.93 | 26.32 | 150.10 | 51.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 119.90 | 38.27 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 112.52 | 34.18 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 94.11 | 30.72 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.64 | 19.49 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.25 | 11.86 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.53 | 5.97 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 54.28 | 4.93 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.64 | 7.11 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.39 | 14.39 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.30 | 22.82 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 125.81 | 35.66 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 121.12 | 42.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.65 | 22.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.25 | 4.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 125.81 | 42.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 119.90 | 38.27 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 112.52 | 34.18 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 94.11 | 30.72 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.64 | 19.49 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.25 | 11.86 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.53 | 5.97 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 54.28 | 4.93 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.64 | 7.11 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 94.39 | 14.39 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.30 | 22.82 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 125.81 | 35.66 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 121.12 | 42.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.65 | 22.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.25 | 4.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 125.81 | 42.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.24 | 63.33 | 19.91 | 143.47 | 45.53 | 0.00 | 0.00 | 0.00 |
February | 75.42 | 52.95 | 22.48 | 134.64 | 40.71 | 0.00 | 0.00 | 0.00 |
March | 59.12 | 32.90 | 26.22 | 112.64 | 36.61 | 0.00 | 0.00 | 0.00 |
April | 39.02 | 12.70 | 26.32 | 83.23 | 23.31 | 0.00 | 0.00 | 0.00 |
May | 28.24 | 2.72 | 25.52 | 63.47 | 14.26 | 0.00 | 0.00 | 0.00 |
June | 24.84 | 0.87 | 23.97 | 63.65 | 7.20 | 0.00 | 0.00 | 0.00 |
July | 25.17 | 1.50 | 23.67 | 64.64 | 5.93 | 0.00 | 0.00 | 0.00 |
August | 31.24 | 6.78 | 24.46 | 78.26 | 8.53 | 0.00 | 0.00 | 0.00 |
September | 48.77 | 23.83 | 24.94 | 112.71 | 17.20 | 0.00 | 0.00 | 0.00 |
October | 68.81 | 45.96 | 22.85 | 135.45 | 27.21 | 0.00 | 0.00 | 0.00 |
November | 85.11 | 64.93 | 20.17 | 150.48 | 42.47 | 0.00 | 0.00 | 0.00 |
December | 85.63 | 64.65 | 20.98 | 144.89 | 50.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.44 | 30.98 | 23.46 | 107.12 | 26.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.84 | 0.87 | 19.91 | 63.47 | 5.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.63 | 64.93 | 26.32 | 150.48 | 50.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 120.46 | 36.12 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 113.21 | 31.95 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 94.78 | 28.46 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.92 | 18.13 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.17 | 11.27 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.05 | 5.86 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 53.66 | 4.99 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.03 | 7.23 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 93.94 | 14.46 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.35 | 22.18 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 126.36 | 34.03 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 121.67 | 40.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.74 | 21.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.05 | 4.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 126.36 | 40.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.62 | 52.97 | 16.65 | 120.46 | 36.12 | 0.00 | 0.00 | 0.00 |
February | 63.08 | 44.28 | 18.80 | 113.21 | 31.95 | 0.00 | 0.00 | 0.00 |
March | 49.45 | 27.52 | 21.93 | 94.78 | 28.46 | 0.00 | 0.00 | 0.00 |
April | 32.64 | 10.62 | 22.01 | 69.92 | 18.13 | 0.00 | 0.00 | 0.00 |
May | 23.62 | 2.28 | 21.34 | 53.17 | 11.27 | 0.00 | 0.00 | 0.00 |
June | 20.78 | 0.73 | 20.05 | 53.05 | 5.86 | 0.00 | 0.00 | 0.00 |
July | 21.05 | 1.25 | 19.80 | 53.66 | 4.99 | 0.00 | 0.00 | 0.00 |
August | 26.13 | 5.67 | 20.46 | 65.03 | 7.23 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.93 | 20.86 | 93.94 | 14.46 | 0.00 | 0.00 | 0.00 |
October | 57.56 | 38.44 | 19.11 | 113.35 | 22.18 | 0.00 | 0.00 | 0.00 |
November | 71.18 | 54.31 | 16.87 | 126.36 | 34.03 | 0.00 | 0.00 | 0.00 |
December | 71.62 | 54.08 | 17.55 | 121.67 | 40.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.53 | 25.91 | 19.62 | 89.74 | 21.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.78 | 0.73 | 16.65 | 53.05 | 4.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.62 | 54.31 | 22.01 | 126.36 | 40.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.24 | 63.33 | 19.91 | 144.16 | 42.98 | 0.00 | 0.00 | 0.00 |
February | 75.42 | 52.95 | 22.48 | 135.47 | 38.06 | 0.00 | 0.00 | 0.00 |
March | 59.12 | 32.90 | 26.22 | 113.45 | 33.93 | 0.00 | 0.00 | 0.00 |
April | 39.02 | 12.70 | 26.32 | 83.57 | 21.70 | 0.00 | 0.00 | 0.00 |
May | 28.24 | 2.72 | 25.52 | 63.37 | 13.56 | 0.00 | 0.00 | 0.00 |
June | 24.84 | 0.87 | 23.97 | 63.07 | 7.07 | 0.00 | 0.00 | 0.00 |
July | 25.17 | 1.50 | 23.67 | 63.90 | 6.01 | 0.00 | 0.00 | 0.00 |
August | 31.24 | 6.78 | 24.46 | 77.53 | 8.68 | 0.00 | 0.00 | 0.00 |
September | 48.77 | 23.83 | 24.94 | 112.17 | 17.29 | 0.00 | 0.00 | 0.00 |
October | 68.81 | 45.96 | 22.85 | 135.50 | 26.45 | 0.00 | 0.00 | 0.00 |
November | 85.11 | 64.93 | 20.17 | 151.14 | 40.54 | 0.00 | 0.00 | 0.00 |
December | 85.63 | 64.65 | 20.98 | 145.55 | 48.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.44 | 30.98 | 23.46 | 107.23 | 25.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.84 | 0.87 | 19.91 | 63.07 | 6.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.63 | 64.93 | 26.32 | 151.14 | 48.15 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.320050E+09 | 0.107092E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.271369E+09 | 86188132.27 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.251141E+09 | 85889036.43 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.180758E+09 | 51342160.90 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.143716E+09 | 31154706.86 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.140664E+09 | 14825190.60 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.147749E+09 | 12366335.88 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.177765E+09 | 18189049.24 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.245549E+09 | 35856553.50 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.304155E+09 | 60813798.02 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.325266E+09 | 94794781.09 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.323433E+09 | 0.117129E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.283161E+10 | 0.715641E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.140664E+09 | 12366335.88 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.325266E+09 | 0.117129E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.320050E+09 | 0.107092E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.271369E+09 | 86188132.27 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.251141E+09 | 85889036.43 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.180758E+09 | 51342160.90 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.143716E+09 | 31154706.86 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.140664E+09 | 14825190.60 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.147749E+09 | 12366335.88 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.177765E+09 | 18189049.24 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.245549E+09 | 35856553.50 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.304155E+09 | 60813798.02 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.325266E+09 | 94794781.09 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.323433E+09 | 0.117129E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.283161E+10 | 0.715641E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.140664E+09 | 12366335.88 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.325266E+09 | 0.117129E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.320050E+09 | 0.107092E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.271369E+09 | 86188132.27 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.251141E+09 | 85889036.43 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.180758E+09 | 51342160.90 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.143716E+09 | 31154706.86 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.140664E+09 | 14825190.60 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.147749E+09 | 12366335.88 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.177765E+09 | 18189049.24 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.245549E+09 | 35856553.50 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.304155E+09 | 60813798.02 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.325266E+09 | 94794781.09 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.323433E+09 | 0.117129E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.283161E+10 | 0.715641E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.140664E+09 | 12366335.88 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.325266E+09 | 0.117129E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.320050E+09 | 0.107092E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.271369E+09 | 86188132.27 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.251141E+09 | 85889036.43 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.180758E+09 | 51342160.90 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.143716E+09 | 31154706.86 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.140664E+09 | 14825190.60 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.147749E+09 | 12366335.88 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.177765E+09 | 18189049.24 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.245549E+09 | 35856553.50 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.304155E+09 | 60813798.02 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.325266E+09 | 94794781.09 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.323433E+09 | 0.117129E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.283161E+10 | 0.715641E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.140664E+09 | 12366335.88 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.325266E+09 | 0.117129E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.224174E+09 | 0.170556E+09 | 53618815.37 | 0.385005E+09 | 0.128107E+09 |
February | 0.183466E+09 | 0.128790E+09 | 54676389.59 | 0.326433E+09 | 0.103192E+09 |
March | 0.159223E+09 | 88616025.34 | 70606825.69 | 0.302179E+09 | 0.102910E+09 |
April | 0.101691E+09 | 33100685.65 | 68589954.11 | 0.217163E+09 | 61736759.84 |
May | 76043113.33 | 7326234.06 | 68716879.27 | 0.172201E+09 | 37652175.08 |
June | 64743525.58 | 2266135.09 | 62477390.49 | 0.168119E+09 | 17961330.50 |
July | 67786055.60 | 4029785.57 | 63756270.04 | 0.176835E+09 | 14951100.28 |
August | 84133976.08 | 18269677.05 | 65864299.02 | 0.213019E+09 | 21938523.29 |
September | 0.127113E+09 | 62102532.78 | 65010272.49 | 0.294748E+09 | 43131109.45 |
October | 0.185319E+09 | 0.123782E+09 | 61537722.22 | 0.365515E+09 | 72953603.18 |
November | 0.221805E+09 | 0.169234E+09 | 52571040.46 | 0.391107E+09 | 0.113522E+09 |
December | 0.230617E+09 | 0.174123E+09 | 56494565.22 | 0.388952E+09 | 0.140180E+09 |
Annual Sum or Average | 0.172612E+10 | 0.982195E+09 | 0.743920E+09 | 0.340128E+10 | 0.858235E+09 |
Minimum of Months | 64743525.58 | 2266135.09 | 52571040.46 | 0.168119E+09 | 14951100.28 |
Maximum of Months | 0.230617E+09 | 0.174123E+09 | 70606825.69 | 0.391107E+09 | 0.140180E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.224174E+09 | 0.170556E+09 | 53618815.37 | 0.385005E+09 | 0.128107E+09 |
February | 0.183466E+09 | 0.128790E+09 | 54676389.59 | 0.326433E+09 | 0.103192E+09 |
March | 0.159223E+09 | 88616025.34 | 70606825.69 | 0.302179E+09 | 0.102910E+09 |
April | 0.101691E+09 | 33100685.65 | 68589954.11 | 0.217163E+09 | 61736759.84 |
May | 76043113.33 | 7326234.06 | 68716879.27 | 0.172201E+09 | 37652175.08 |
June | 64743525.58 | 2266135.09 | 62477390.49 | 0.168119E+09 | 17961330.50 |
July | 67786055.60 | 4029785.57 | 63756270.04 | 0.176835E+09 | 14951100.28 |
August | 84133976.08 | 18269677.05 | 65864299.02 | 0.213019E+09 | 21938523.29 |
September | 0.127113E+09 | 62102532.78 | 65010272.49 | 0.294748E+09 | 43131109.45 |
October | 0.185319E+09 | 0.123782E+09 | 61537722.22 | 0.365515E+09 | 72953603.18 |
November | 0.221805E+09 | 0.169234E+09 | 52571040.46 | 0.391107E+09 | 0.113522E+09 |
December | 0.230617E+09 | 0.174123E+09 | 56494565.22 | 0.388952E+09 | 0.140180E+09 |
Annual Sum or Average | 0.172612E+10 | 0.982195E+09 | 0.743920E+09 | 0.340128E+10 | 0.858235E+09 |
Minimum of Months | 64743525.58 | 2266135.09 | 52571040.46 | 0.168119E+09 | 14951100.28 |
Maximum of Months | 0.230617E+09 | 0.174123E+09 | 70606825.69 | 0.391107E+09 | 0.140180E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.317026E+09 | 0.113844E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.268324E+09 | 91624187.35 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.247938E+09 | 90608812.82 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.179586E+09 | 52876969.91 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.143708E+09 | 31565048.37 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.141418E+09 | 14969405.12 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.148652E+09 | 12386343.44 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.178592E+09 | 18095646.70 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.245951E+09 | 35474482.39 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303727E+09 | 61156046.04 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.323307E+09 | 97744214.64 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.320480E+09 | 0.123385E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.281871E+10 | 0.743729E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.141418E+09 | 12386343.44 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.323307E+09 | 0.123385E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.317026E+09 | 0.113844E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.268324E+09 | 91624187.35 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.247938E+09 | 90608812.82 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.179586E+09 | 52876969.91 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.143708E+09 | 31565048.37 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.141418E+09 | 14969405.12 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.148652E+09 | 12386343.44 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.178592E+09 | 18095646.70 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.245951E+09 | 35474482.39 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303727E+09 | 61156046.04 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.323307E+09 | 97744214.64 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.320480E+09 | 0.123385E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.281871E+10 | 0.743729E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.141418E+09 | 12386343.44 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.323307E+09 | 0.123385E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.224174E+09 | 0.170556E+09 | 53618815.37 | 0.381449E+09 | 0.136110E+09 |
February | 0.183466E+09 | 0.128790E+09 | 54676389.59 | 0.322838E+09 | 0.109648E+09 |
March | 0.159223E+09 | 88616025.34 | 70606825.69 | 0.298396E+09 | 0.108532E+09 |
April | 0.101691E+09 | 33100685.65 | 68589954.11 | 0.215774E+09 | 63585184.70 |
May | 76043113.33 | 7326234.06 | 68716879.27 | 0.172175E+09 | 38164269.16 |
June | 64743525.58 | 2266135.09 | 62477390.49 | 0.168993E+09 | 18145926.25 |
July | 67786055.60 | 4029785.57 | 63756270.04 | 0.177904E+09 | 14981304.41 |
August | 84133976.08 | 18269677.05 | 65864299.02 | 0.214015E+09 | 21834235.04 |
September | 0.127113E+09 | 62102532.78 | 65010272.49 | 0.295261E+09 | 42681386.74 |
October | 0.185319E+09 | 0.123782E+09 | 61537722.22 | 0.365053E+09 | 73364288.08 |
November | 0.221805E+09 | 0.169234E+09 | 52571040.46 | 0.388821E+09 | 0.117024E+09 |
December | 0.230617E+09 | 0.174123E+09 | 56494565.22 | 0.385468E+09 | 0.147598E+09 |
Annual Sum or Average | 0.172612E+10 | 0.982195E+09 | 0.743920E+09 | 0.338615E+10 | 0.891668E+09 |
Minimum of Months | 64743525.58 | 2266135.09 | 52571040.46 | 0.168993E+09 | 14981304.41 |
Maximum of Months | 0.230617E+09 | 0.174123E+09 | 70606825.69 | 0.388821E+09 | 0.147598E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.317766E+09 | 0.112004E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.268805E+09 | 90739912.16 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.248236E+09 | 90512851.44 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.179113E+09 | 54962116.90 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142489E+09 | 34369610.27 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.138638E+09 | 16932598.96 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.145692E+09 | 14578904.82 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.176320E+09 | 20587758.15 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.245312E+09 | 39177970.22 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303330E+09 | 63931536.25 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.323652E+09 | 98176146.87 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.321184E+09 | 0.121780E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.281054E+10 | 0.757754E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.138638E+09 | 14578904.82 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.323652E+09 | 0.121780E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.317766E+09 | 0.112004E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.268805E+09 | 90739912.16 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.248236E+09 | 90512851.44 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.179113E+09 | 54962116.90 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142489E+09 | 34369610.27 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.138638E+09 | 16932598.96 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.145692E+09 | 14578904.82 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.176320E+09 | 20587758.15 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.245312E+09 | 39177970.22 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303330E+09 | 63931536.25 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.323652E+09 | 98176146.87 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.321184E+09 | 0.121780E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.281054E+10 | 0.757754E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.138638E+09 | 14578904.82 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.323652E+09 | 0.121780E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222949E+09 | 0.169624E+09 | 53325816.38 | 0.380246E+09 | 0.133220E+09 |
February | 0.182464E+09 | 0.128086E+09 | 54377611.51 | 0.321647E+09 | 0.108027E+09 |
March | 0.158353E+09 | 88131784.76 | 70220996.04 | 0.297122E+09 | 0.107837E+09 |
April | 0.101135E+09 | 32919807.59 | 68215145.62 | 0.214044E+09 | 65695022.66 |
May | 75627577.19 | 7286200.00 | 68341377.19 | 0.169824E+09 | 41278445.26 |
June | 64389735.83 | 2253751.84 | 62135983.99 | 0.164847E+09 | 20402294.30 |
July | 67415640.00 | 4007764.88 | 63407875.12 | 0.173493E+09 | 17517766.62 |
August | 83674227.58 | 18169842.75 | 65504384.82 | 0.210211E+09 | 24685738.97 |
September | 0.126418E+09 | 61763174.67 | 64655025.10 | 0.292905E+09 | 46816815.86 |
October | 0.184307E+09 | 0.123105E+09 | 61201450.52 | 0.362591E+09 | 76226899.53 |
November | 0.220593E+09 | 0.168310E+09 | 52283767.02 | 0.387109E+09 | 0.116897E+09 |
December | 0.229357E+09 | 0.173171E+09 | 56185851.75 | 0.384202E+09 | 0.144924E+09 |
Annual Sum or Average | 0.171668E+10 | 0.976828E+09 | 0.739855E+09 | 0.335824E+10 | 0.903528E+09 |
Minimum of Months | 64389735.83 | 2253751.84 | 52283767.02 | 0.164847E+09 | 17517766.62 |
Maximum of Months | 0.229357E+09 | 0.173171E+09 | 70220996.04 | 0.387109E+09 | 0.144924E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.318389E+09 | 0.110275E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.269322E+09 | 89454795.52 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.248712E+09 | 89472148.57 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.179199E+09 | 54727803.37 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142439E+09 | 34482240.17 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.138494E+09 | 17161641.36 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.145530E+09 | 14829262.58 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.176191E+09 | 20846007.15 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.245255E+09 | 39403526.97 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303334E+09 | 63889228.30 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.323943E+09 | 97466390.56 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.321752E+09 | 0.120234E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.281256E+10 | 0.752242E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.138494E+09 | 14829262.58 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.323943E+09 | 0.120234E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.318389E+09 | 0.110275E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.269322E+09 | 89454795.52 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.248712E+09 | 89472148.57 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.179199E+09 | 54727803.37 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142439E+09 | 34482240.17 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.138494E+09 | 17161641.36 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.145530E+09 | 14829262.58 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.176191E+09 | 20846007.15 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.245255E+09 | 39403526.97 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303334E+09 | 63889228.30 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.323943E+09 | 97466390.56 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.321752E+09 | 0.120234E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.281256E+10 | 0.752242E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.138494E+09 | 14829262.58 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.323943E+09 | 0.120234E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222949E+09 | 0.169624E+09 | 53325816.38 | 0.380990E+09 | 0.131168E+09 |
February | 0.182464E+09 | 0.128086E+09 | 54377611.51 | 0.322266E+09 | 0.106503E+09 |
March | 0.158353E+09 | 88131784.76 | 70220996.04 | 0.297692E+09 | 0.106602E+09 |
April | 0.101135E+09 | 32919807.59 | 68215145.62 | 0.214148E+09 | 65416849.09 |
May | 75627577.19 | 7286200.00 | 68341377.19 | 0.169764E+09 | 41412686.61 |
June | 64389735.83 | 2253751.84 | 62135983.99 | 0.164677E+09 | 20675998.93 |
July | 67415640.00 | 4007764.88 | 63407875.12 | 0.173301E+09 | 17817013.23 |
August | 83674227.58 | 18169842.75 | 65504384.82 | 0.210058E+09 | 24993839.06 |
September | 0.126418E+09 | 61763174.67 | 64655025.10 | 0.292836E+09 | 47084925.33 |
October | 0.184307E+09 | 0.123105E+09 | 61201450.52 | 0.362597E+09 | 76177327.82 |
November | 0.220593E+09 | 0.168310E+09 | 52283767.02 | 0.387457E+09 | 0.116055E+09 |
December | 0.229357E+09 | 0.173171E+09 | 56185851.75 | 0.384882E+09 | 0.143087E+09 |
Annual Sum or Average | 0.171668E+10 | 0.976828E+09 | 0.739855E+09 | 0.336067E+10 | 0.896993E+09 |
Minimum of Months | 64389735.83 | 2253751.84 | 52283767.02 | 0.164677E+09 | 17817013.23 |
Maximum of Months | 0.229357E+09 | 0.173171E+09 | 70220996.04 | 0.387457E+09 | 0.143087E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.319208E+09 | 0.108442E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.270110E+09 | 87913024.81 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.249570E+09 | 88037777.78 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.179572E+09 | 53981907.84 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142661E+09 | 34014966.22 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.138728E+09 | 16847409.78 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.145732E+09 | 14517069.34 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.176359E+09 | 20501755.68 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.245380E+09 | 39008445.94 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303529E+09 | 63372520.08 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.324466E+09 | 96495653.93 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.322558E+09 | 0.118549E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.281787E+10 | 0.741682E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.138728E+09 | 14517069.34 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.324466E+09 | 0.118549E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.319208E+09 | 0.108442E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.270110E+09 | 87913024.81 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.249570E+09 | 88037777.78 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.179572E+09 | 53981907.84 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142661E+09 | 34014966.22 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.138728E+09 | 16847409.78 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.145732E+09 | 14517069.34 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.176359E+09 | 20501755.68 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.245380E+09 | 39008445.94 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303529E+09 | 63372520.08 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.324466E+09 | 96495653.93 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.322558E+09 | 0.118549E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.281787E+10 | 0.741682E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.138728E+09 | 14517069.34 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.324466E+09 | 0.118549E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222949E+09 | 0.169624E+09 | 53325816.38 | 0.381967E+09 | 0.128995E+09 |
February | 0.182464E+09 | 0.128086E+09 | 54377611.51 | 0.323207E+09 | 0.104677E+09 |
March | 0.158353E+09 | 88131784.76 | 70220996.04 | 0.298715E+09 | 0.104902E+09 |
April | 0.101135E+09 | 32919807.59 | 68215145.62 | 0.214596E+09 | 64534670.54 |
May | 75627577.19 | 7286200.00 | 68341377.19 | 0.170031E+09 | 40859793.98 |
June | 64389735.83 | 2253751.84 | 62135983.99 | 0.164954E+09 | 20302918.58 |
July | 67415640.00 | 4007764.88 | 63407875.12 | 0.173541E+09 | 17447699.41 |
August | 83674227.58 | 18169842.75 | 65504384.82 | 0.210258E+09 | 24587134.49 |
September | 0.126418E+09 | 61763174.67 | 64655025.10 | 0.292987E+09 | 46618793.92 |
October | 0.184307E+09 | 0.123105E+09 | 61201450.52 | 0.362832E+09 | 75565623.52 |
November | 0.220593E+09 | 0.168310E+09 | 52283767.02 | 0.388081E+09 | 0.114904E+09 |
December | 0.229357E+09 | 0.173171E+09 | 56185851.75 | 0.385844E+09 | 0.141089E+09 |
Annual Sum or Average | 0.171668E+10 | 0.976828E+09 | 0.739855E+09 | 0.336701E+10 | 0.884484E+09 |
Minimum of Months | 64389735.83 | 2253751.84 | 52283767.02 | 0.164954E+09 | 17447699.41 |
Maximum of Months | 0.229357E+09 | 0.173171E+09 | 70220996.04 | 0.388081E+09 | 0.141089E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.320596E+09 | 0.105201E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.271453E+09 | 85200002.88 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.250932E+09 | 85250717.56 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.179872E+09 | 52260338.65 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142211E+09 | 32758938.00 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.138212E+09 | 16049963.72 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.145042E+09 | 13712589.43 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.175662E+09 | 19565013.00 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.244762E+09 | 37904632.75 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303486E+09 | 62144680.79 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.325316E+09 | 94558740.62 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.323926E+09 | 0.115526E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.282147E+10 | 0.720133E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.138212E+09 | 13712589.43 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.325316E+09 | 0.115526E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.320596E+09 | 0.105201E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.271453E+09 | 85200002.88 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.250932E+09 | 85250717.56 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.179872E+09 | 52260338.65 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142211E+09 | 32758938.00 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.138212E+09 | 16049963.72 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.145042E+09 | 13712589.43 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.175662E+09 | 19565013.00 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.244762E+09 | 37904632.75 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303486E+09 | 62144680.79 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.325316E+09 | 94558740.62 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.323926E+09 | 0.115526E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.282147E+10 | 0.720133E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.138212E+09 | 13712589.43 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.325316E+09 | 0.115526E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.320596E+09 | 0.105201E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.271453E+09 | 85200002.88 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.250932E+09 | 85250717.56 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.179872E+09 | 52260338.65 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142211E+09 | 32758938.00 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.138212E+09 | 16049963.72 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.145042E+09 | 13712589.43 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.175662E+09 | 19565013.00 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.244762E+09 | 37904632.75 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303486E+09 | 62144680.79 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.325316E+09 | 94558740.62 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.323926E+09 | 0.115526E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.282147E+10 | 0.720133E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.138212E+09 | 13712589.43 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.325316E+09 | 0.115526E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.320596E+09 | 0.105201E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.271453E+09 | 85200002.88 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.250932E+09 | 85250717.56 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.179872E+09 | 52260338.65 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142211E+09 | 32758938.00 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.138212E+09 | 16049963.72 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.145042E+09 | 13712589.43 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.175662E+09 | 19565013.00 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.244762E+09 | 37904632.75 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303486E+09 | 62144680.79 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.325316E+09 | 94558740.62 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.323926E+09 | 0.115526E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.282147E+10 | 0.720133E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.138212E+09 | 13712589.43 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.325316E+09 | 0.115526E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222949E+09 | 0.169624E+09 | 53325816.38 | 0.383558E+09 | 0.125161E+09 |
February | 0.182464E+09 | 0.128086E+09 | 54377611.51 | 0.324755E+09 | 0.101459E+09 |
March | 0.158353E+09 | 88131784.76 | 70220996.04 | 0.300287E+09 | 0.101590E+09 |
April | 0.101135E+09 | 32919807.59 | 68215145.62 | 0.214942E+09 | 62474332.37 |
May | 75627577.19 | 7286200.00 | 68341377.19 | 0.169513E+09 | 39341754.47 |
June | 64389735.83 | 2253751.84 | 62135983.99 | 0.164372E+09 | 19330246.85 |
July | 67415640.00 | 4007764.88 | 63407875.12 | 0.172738E+09 | 16471650.28 |
August | 83674227.58 | 18169842.75 | 65504384.82 | 0.209434E+09 | 23454150.68 |
September | 0.126418E+09 | 61763174.67 | 64655025.10 | 0.292237E+09 | 45295687.42 |
October | 0.184307E+09 | 0.123105E+09 | 61201450.52 | 0.362742E+09 | 74102380.76 |
November | 0.220593E+09 | 0.168310E+09 | 52283767.02 | 0.389040E+09 | 0.112606E+09 |
December | 0.229357E+09 | 0.173171E+09 | 56185851.75 | 0.387422E+09 | 0.137505E+09 |
Annual Sum or Average | 0.171668E+10 | 0.976828E+09 | 0.739855E+09 | 0.337104E+10 | 0.858791E+09 |
Minimum of Months | 64389735.83 | 2253751.84 | 52283767.02 | 0.164372E+09 | 16471650.28 |
Maximum of Months | 0.229357E+09 | 0.173171E+09 | 70220996.04 | 0.389040E+09 | 0.137505E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222949E+09 | 0.169624E+09 | 53325816.38 | 0.383558E+09 | 0.125161E+09 |
February | 0.182464E+09 | 0.128086E+09 | 54377611.51 | 0.324755E+09 | 0.101459E+09 |
March | 0.158353E+09 | 88131784.76 | 70220996.04 | 0.300287E+09 | 0.101590E+09 |
April | 0.101135E+09 | 32919807.59 | 68215145.62 | 0.214942E+09 | 62474332.37 |
May | 75627577.19 | 7286200.00 | 68341377.19 | 0.169513E+09 | 39341754.47 |
June | 64389735.83 | 2253751.84 | 62135983.99 | 0.164372E+09 | 19330246.85 |
July | 67415640.00 | 4007764.88 | 63407875.12 | 0.172738E+09 | 16471650.28 |
August | 83674227.58 | 18169842.75 | 65504384.82 | 0.209434E+09 | 23454150.68 |
September | 0.126418E+09 | 61763174.67 | 64655025.10 | 0.292237E+09 | 45295687.42 |
October | 0.184307E+09 | 0.123105E+09 | 61201450.52 | 0.362742E+09 | 74102380.76 |
November | 0.220593E+09 | 0.168310E+09 | 52283767.02 | 0.389040E+09 | 0.112606E+09 |
December | 0.229357E+09 | 0.173171E+09 | 56185851.75 | 0.387422E+09 | 0.137505E+09 |
Annual Sum or Average | 0.171668E+10 | 0.976828E+09 | 0.739855E+09 | 0.337104E+10 | 0.858791E+09 |
Minimum of Months | 64389735.83 | 2253751.84 | 52283767.02 | 0.164372E+09 | 16471650.28 |
Maximum of Months | 0.229357E+09 | 0.173171E+09 | 70220996.04 | 0.389040E+09 | 0.137505E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.320159E+09 | 0.104940E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.271101E+09 | 84950582.12 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.250609E+09 | 84885524.68 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.179698E+09 | 51885313.23 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142308E+09 | 32322547.23 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.138654E+09 | 15661728.22 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.145375E+09 | 13319230.99 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.175831E+09 | 19133597.49 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.244627E+09 | 37444560.80 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303113E+09 | 61822813.28 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.324949E+09 | 94336964.04 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.323518E+09 | 0.115361E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.281994E+10 | 0.716064E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.138654E+09 | 13319230.99 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.324949E+09 | 0.115361E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.320159E+09 | 0.104940E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.271101E+09 | 84950582.12 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.250609E+09 | 84885524.68 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.179698E+09 | 51885313.23 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142308E+09 | 32322547.23 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.138654E+09 | 15661728.22 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.145375E+09 | 13319230.99 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.175831E+09 | 19133597.49 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.244627E+09 | 37444560.80 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303113E+09 | 61822813.28 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.324949E+09 | 94336964.04 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.323518E+09 | 0.115361E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.281994E+10 | 0.716064E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.138654E+09 | 13319230.99 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.324949E+09 | 0.115361E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222949E+09 | 0.169624E+09 | 53325816.38 | 0.383112E+09 | 0.124840E+09 |
February | 0.182464E+09 | 0.128086E+09 | 54377611.51 | 0.324396E+09 | 0.101162E+09 |
March | 0.158353E+09 | 88131784.76 | 70220996.04 | 0.299965E+09 | 0.101161E+09 |
April | 0.101135E+09 | 32919807.59 | 68215145.62 | 0.214761E+09 | 62046019.93 |
May | 75627577.19 | 7286200.00 | 68341377.19 | 0.169621E+09 | 38846241.36 |
June | 64389735.83 | 2253751.84 | 62135983.99 | 0.164866E+09 | 18880504.23 |
July | 67415640.00 | 4007764.88 | 63407875.12 | 0.173122E+09 | 16012852.72 |
August | 83674227.58 | 18169842.75 | 65504384.82 | 0.209640E+09 | 22952644.10 |
September | 0.126418E+09 | 61763174.67 | 64655025.10 | 0.292109E+09 | 44761270.59 |
October | 0.184307E+09 | 0.123105E+09 | 61201450.52 | 0.362357E+09 | 73725444.72 |
November | 0.220593E+09 | 0.168310E+09 | 52283767.02 | 0.388671E+09 | 0.112339E+09 |
December | 0.229357E+09 | 0.173171E+09 | 56185851.75 | 0.386999E+09 | 0.137301E+09 |
Annual Sum or Average | 0.171668E+10 | 0.976828E+09 | 0.739855E+09 | 0.336962E+10 | 0.854028E+09 |
Minimum of Months | 64389735.83 | 2253751.84 | 52283767.02 | 0.164866E+09 | 16012852.72 |
Maximum of Months | 0.229357E+09 | 0.173171E+09 | 70220996.04 | 0.388671E+09 | 0.137301E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.320447E+09 | 0.104284E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.271409E+09 | 84364055.75 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.251040E+09 | 84187789.67 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.179934E+09 | 51534422.19 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142426E+09 | 32168670.33 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.138751E+09 | 15578492.39 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.145465E+09 | 13240069.51 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.175903E+09 | 19053553.54 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.244684E+09 | 37342983.31 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303226E+09 | 61622714.53 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.325273E+09 | 93825932.79 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.323766E+09 | 0.114847E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.282232E+10 | 0.712050E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.138751E+09 | 13240069.51 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.325273E+09 | 0.114847E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.320447E+09 | 0.104284E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.271409E+09 | 84364055.75 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.251040E+09 | 84187789.67 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.179934E+09 | 51534422.19 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142426E+09 | 32168670.33 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.138751E+09 | 15578492.39 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.145465E+09 | 13240069.51 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.175903E+09 | 19053553.54 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.244684E+09 | 37342983.31 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303226E+09 | 61622714.53 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.325273E+09 | 93825932.79 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.323766E+09 | 0.114847E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.282232E+10 | 0.712050E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.138751E+09 | 13240069.51 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.325273E+09 | 0.114847E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222949E+09 | 0.169624E+09 | 53325816.38 | 0.383457E+09 | 0.124061E+09 |
February | 0.182464E+09 | 0.128086E+09 | 54377611.51 | 0.324764E+09 | 0.100466E+09 |
March | 0.158353E+09 | 88131784.76 | 70220996.04 | 0.300479E+09 | 0.100332E+09 |
April | 0.101135E+09 | 32919807.59 | 68215145.62 | 0.215045E+09 | 61629414.13 |
May | 75627577.19 | 7286200.00 | 68341377.19 | 0.169762E+09 | 38662472.53 |
June | 64389735.83 | 2253751.84 | 62135983.99 | 0.164982E+09 | 18780938.38 |
July | 67415640.00 | 4007764.88 | 63407875.12 | 0.173229E+09 | 15918378.94 |
August | 83674227.58 | 18169842.75 | 65504384.82 | 0.209726E+09 | 22857296.45 |
September | 0.126418E+09 | 61763174.67 | 64655025.10 | 0.292179E+09 | 44640375.97 |
October | 0.184307E+09 | 0.123105E+09 | 61201450.52 | 0.362492E+09 | 73487238.08 |
November | 0.220593E+09 | 0.168310E+09 | 52283767.02 | 0.389057E+09 | 0.111731E+09 |
December | 0.229357E+09 | 0.173171E+09 | 56185851.75 | 0.387298E+09 | 0.136691E+09 |
Annual Sum or Average | 0.171668E+10 | 0.976828E+09 | 0.739855E+09 | 0.337247E+10 | 0.849258E+09 |
Minimum of Months | 64389735.83 | 2253751.84 | 52283767.02 | 0.164982E+09 | 15918378.94 |
Maximum of Months | 0.229357E+09 | 0.173171E+09 | 70220996.04 | 0.389057E+09 | 0.136691E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.321134E+09 | 0.102510E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.272203E+09 | 82694570.02 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.252065E+09 | 82271253.27 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.180519E+09 | 50507816.10 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142630E+09 | 31764038.03 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.138744E+09 | 15481621.26 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.145385E+09 | 13210730.33 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.175803E+09 | 19052272.91 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.244647E+09 | 37293921.85 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303465E+09 | 61109034.47 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.326092E+09 | 92428396.06 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.324404E+09 | 0.113366E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.282709E+10 | 0.701689E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.138744E+09 | 13210730.33 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.326092E+09 | 0.113366E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.321134E+09 | 0.102510E+09 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.272203E+09 | 82694570.02 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.252065E+09 | 82271253.27 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.180519E+09 | 50507816.10 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142630E+09 | 31764038.03 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.138744E+09 | 15481621.26 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.145385E+09 | 13210730.33 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.175803E+09 | 19052272.91 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.244647E+09 | 37293921.85 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303465E+09 | 61109034.47 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.326092E+09 | 92428396.06 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.324404E+09 | 0.113366E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.282709E+10 | 0.701689E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.138744E+09 | 13210730.33 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.326092E+09 | 0.113366E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222949E+09 | 0.169624E+09 | 53325816.38 | 0.384281E+09 | 0.121956E+09 |
February | 0.182464E+09 | 0.128086E+09 | 54377611.51 | 0.325713E+09 | 98486285.05 |
March | 0.158353E+09 | 88131784.76 | 70220996.04 | 0.301704E+09 | 98062417.27 |
April | 0.101135E+09 | 32919807.59 | 68215145.62 | 0.215743E+09 | 60413397.27 |
May | 75627577.19 | 7286200.00 | 68341377.19 | 0.170007E+09 | 38184664.56 |
June | 64389735.83 | 2253751.84 | 62135983.99 | 0.164971E+09 | 18668387.33 |
July | 67415640.00 | 4007764.88 | 63407875.12 | 0.173132E+09 | 15887361.56 |
August | 83674227.58 | 18169842.75 | 65504384.82 | 0.209605E+09 | 22859490.32 |
September | 0.126418E+09 | 61763174.67 | 64655025.10 | 0.292134E+09 | 44586072.49 |
October | 0.184307E+09 | 0.123105E+09 | 61201450.52 | 0.362779E+09 | 72880362.62 |
November | 0.220593E+09 | 0.168310E+09 | 52283767.02 | 0.390035E+09 | 0.110074E+09 |
December | 0.229357E+09 | 0.173171E+09 | 56185851.75 | 0.388063E+09 | 0.134934E+09 |
Annual Sum or Average | 0.171668E+10 | 0.976828E+09 | 0.739855E+09 | 0.337817E+10 | 0.836993E+09 |
Minimum of Months | 64389735.83 | 2253751.84 | 52283767.02 | 0.164971E+09 | 15887361.56 |
Maximum of Months | 0.229357E+09 | 0.173171E+09 | 70220996.04 | 0.390035E+09 | 0.134934E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.322651E+09 | 96751698.74 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.273877E+09 | 77291453.26 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.253857E+09 | 76215025.01 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.181245E+09 | 46995105.19 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142408E+09 | 30196306.39 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.137507E+09 | 15179680.29 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.143728E+09 | 13373552.65 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.174187E+09 | 19369237.79 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.243499E+09 | 37480227.23 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303598E+09 | 59397312.73 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.327527E+09 | 88211696.30 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.325885E+09 | 0.108325E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.282997E+10 | 0.668786E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.137507E+09 | 13373552.65 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.327527E+09 | 0.108325E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186477E+09 | 0.141875E+09 | 44602286.87 | 0.322651E+09 | 96751698.74 |
February | 0.152615E+09 | 0.107132E+09 | 45482019.63 | 0.273877E+09 | 77291453.26 |
March | 0.132448E+09 | 73714373.49 | 58733597.01 | 0.253857E+09 | 76215025.01 |
April | 84590363.56 | 27534481.44 | 57055882.12 | 0.181245E+09 | 46995105.19 |
May | 63255719.68 | 6094256.11 | 57161463.57 | 0.142408E+09 | 30196306.39 |
June | 53856268.19 | 1885062.30 | 51971205.89 | 0.137507E+09 | 15179680.29 |
July | 56387167.01 | 3352137.69 | 53035029.32 | 0.143728E+09 | 13373552.65 |
August | 69986024.68 | 15197452.07 | 54788572.61 | 0.174187E+09 | 19369237.79 |
September | 0.105738E+09 | 51659384.17 | 54078158.99 | 0.243499E+09 | 37480227.23 |
October | 0.154156E+09 | 0.102967E+09 | 51189552.03 | 0.303598E+09 | 59397312.73 |
November | 0.184507E+09 | 0.140776E+09 | 43730705.56 | 0.327527E+09 | 88211696.30 |
December | 0.191837E+09 | 0.144842E+09 | 46994451.23 | 0.325885E+09 | 0.108325E+09 |
Annual Sum or Average | 0.143585E+10 | 0.817030E+09 | 0.618823E+09 | 0.282997E+10 | 0.668786E+09 |
Minimum of Months | 53856268.19 | 1885062.30 | 43730705.56 | 0.137507E+09 | 13373552.65 |
Maximum of Months | 0.191837E+09 | 0.144842E+09 | 58733597.01 | 0.327527E+09 | 0.108325E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222949E+09 | 0.169624E+09 | 53325816.38 | 0.386109E+09 | 0.115130E+09 |
February | 0.182464E+09 | 0.128086E+09 | 54377611.51 | 0.327721E+09 | 92081506.13 |
March | 0.158353E+09 | 88131784.76 | 70220996.04 | 0.303854E+09 | 90886417.33 |
April | 0.101135E+09 | 32919807.59 | 68215145.62 | 0.216607E+09 | 56250416.51 |
May | 75627577.19 | 7286200.00 | 68341377.19 | 0.169732E+09 | 36327667.51 |
June | 64389735.83 | 2253751.84 | 62135983.99 | 0.163484E+09 | 18317147.43 |
July | 67415640.00 | 4007764.88 | 63407875.12 | 0.171141E+09 | 16088636.98 |
August | 83674227.58 | 18169842.75 | 65504384.82 | 0.207660E+09 | 23245746.88 |
September | 0.126418E+09 | 61763174.67 | 64655025.10 | 0.290744E+09 | 44813306.11 |
October | 0.184307E+09 | 0.123105E+09 | 61201450.52 | 0.362929E+09 | 70855864.06 |
November | 0.220593E+09 | 0.168310E+09 | 52283767.02 | 0.391746E+09 | 0.105077E+09 |
December | 0.229357E+09 | 0.173171E+09 | 56185851.75 | 0.389846E+09 | 0.128952E+09 |
Annual Sum or Average | 0.171668E+10 | 0.976828E+09 | 0.739855E+09 | 0.338157E+10 | 0.798026E+09 |
Minimum of Months | 64389735.83 | 2253751.84 | 52283767.02 | 0.163484E+09 | 16088636.98 |
Maximum of Months | 0.229357E+09 | 0.173171E+09 | 70220996.04 | 0.391746E+09 | 0.128952E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 765.46 | 255.59 | 445.88 | 339.24 | 106.65 | 0.00 | 0.00 |
February | 718.56 | 227.82 | 404.01 | 283.61 | 120.40 | 0.00 | 0.00 |
March | 600.70 | 205.11 | 316.70 | 176.26 | 140.44 | 0.00 | 0.00 |
April | 446.51 | 126.87 | 209.01 | 68.03 | 140.97 | 0.00 | 0.00 |
May | 343.21 | 74.64 | 151.25 | 14.57 | 136.68 | 0.00 | 0.00 |
June | 346.79 | 36.74 | 133.07 | 4.66 | 128.41 | 0.00 | 0.00 |
July | 352.70 | 29.63 | 134.83 | 8.02 | 126.81 | 0.00 | 0.00 |
August | 424.54 | 43.55 | 167.34 | 36.34 | 131.00 | 0.00 | 0.00 |
September | 606.36 | 88.61 | 261.26 | 127.64 | 133.62 | 0.00 | 0.00 |
October | 727.17 | 145.30 | 368.60 | 246.20 | 122.40 | 0.00 | 0.00 |
November | 803.73 | 233.88 | 455.88 | 347.83 | 108.05 | 0.00 | 0.00 |
December | 773.46 | 279.60 | 458.70 | 346.33 | 112.37 | 0.00 | 0.00 |
Annual Sum or Average | 574.87 | 145.20 | 291.59 | 165.92 | 125.67 | 0.00 | 0.00 |
Minimum of Months | 343.21 | 29.63 | 133.07 | 4.66 | 106.65 | 0.00 | 0.00 |
Maximum of Months | 803.73 | 279.60 | 458.70 | 347.83 | 140.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 379.14 | 135.83 | 222.94 | 169.62 | 53.32 | 0.00 | 0.00 |
February | 355.28 | 121.07 | 202.01 | 141.81 | 60.20 | 0.00 | 0.00 |
March | 296.55 | 108.18 | 158.35 | 88.13 | 70.22 | 0.00 | 0.00 |
April | 221.82 | 65.33 | 104.50 | 34.02 | 70.49 | 0.00 | 0.00 |
May | 171.59 | 37.82 | 75.63 | 7.29 | 68.34 | 0.00 | 0.00 |
June | 174.32 | 18.55 | 66.53 | 2.33 | 64.21 | 0.00 | 0.00 |
July | 177.42 | 14.84 | 67.41 | 4.01 | 63.41 | 0.00 | 0.00 |
August | 213.26 | 21.66 | 83.67 | 18.17 | 65.50 | 0.00 | 0.00 |
September | 303.69 | 43.84 | 130.63 | 63.82 | 66.81 | 0.00 | 0.00 |
October | 363.09 | 73.06 | 184.30 | 123.10 | 61.20 | 0.00 | 0.00 |
November | 399.47 | 120.57 | 227.94 | 173.91 | 54.02 | 0.00 | 0.00 |
December | 383.22 | 147.24 | 229.35 | 173.17 | 56.18 | 0.00 | 0.00 |
Annual Sum or Average | 286.14 | 75.44 | 145.80 | 82.96 | 62.84 | 0.00 | 0.00 |
Minimum of Months | 171.59 | 14.84 | 66.53 | 2.33 | 53.32 | 0.00 | 0.00 |
Maximum of Months | 399.47 | 147.24 | 229.35 | 173.91 | 70.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 379.25 | 133.37 | 222.49 | 169.27 | 53.21 | 0.00 | 0.00 |
February | 355.18 | 119.67 | 201.59 | 141.51 | 60.08 | 0.00 | 0.00 |
March | 296.29 | 107.85 | 158.02 | 87.95 | 70.07 | 0.00 | 0.00 |
April | 220.78 | 67.75 | 104.29 | 33.95 | 70.34 | 0.00 | 0.00 |
May | 169.80 | 41.08 | 75.47 | 7.27 | 68.20 | 0.00 | 0.00 |
June | 170.57 | 20.94 | 66.40 | 2.32 | 64.07 | 0.00 | 0.00 |
July | 173.57 | 17.43 | 67.28 | 4.00 | 63.28 | 0.00 | 0.00 |
August | 210.14 | 24.59 | 83.50 | 18.13 | 65.37 | 0.00 | 0.00 |
September | 302.29 | 48.29 | 130.36 | 63.69 | 66.67 | 0.00 | 0.00 |
October | 361.88 | 76.20 | 183.92 | 122.85 | 61.07 | 0.00 | 0.00 |
November | 399.08 | 120.85 | 227.47 | 173.56 | 53.91 | 0.00 | 0.00 |
December | 383.28 | 145.04 | 228.88 | 172.81 | 56.07 | 0.00 | 0.00 |
Annual Sum or Average | 284.73 | 76.71 | 145.50 | 82.79 | 62.71 | 0.00 | 0.00 |
Minimum of Months | 169.80 | 17.43 | 66.40 | 2.32 | 53.21 | 0.00 | 0.00 |
Maximum of Months | 399.08 | 145.04 | 228.88 | 173.56 | 70.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 379.99 | 131.32 | 222.49 | 169.27 | 53.21 | 0.00 | 0.00 |
February | 355.87 | 117.98 | 201.59 | 141.51 | 60.08 | 0.00 | 0.00 |
March | 296.86 | 106.61 | 158.02 | 87.95 | 70.07 | 0.00 | 0.00 |
April | 220.89 | 67.47 | 104.29 | 33.95 | 70.34 | 0.00 | 0.00 |
May | 169.74 | 41.21 | 75.47 | 7.27 | 68.20 | 0.00 | 0.00 |
June | 170.40 | 21.22 | 66.40 | 2.32 | 64.07 | 0.00 | 0.00 |
July | 173.37 | 17.73 | 67.28 | 4.00 | 63.28 | 0.00 | 0.00 |
August | 209.99 | 24.90 | 83.50 | 18.13 | 65.37 | 0.00 | 0.00 |
September | 302.22 | 48.57 | 130.36 | 63.69 | 66.67 | 0.00 | 0.00 |
October | 361.88 | 76.15 | 183.92 | 122.85 | 61.07 | 0.00 | 0.00 |
November | 399.44 | 119.98 | 227.47 | 173.56 | 53.91 | 0.00 | 0.00 |
December | 383.96 | 143.20 | 228.88 | 172.81 | 56.07 | 0.00 | 0.00 |
Annual Sum or Average | 284.94 | 76.15 | 145.50 | 82.79 | 62.71 | 0.00 | 0.00 |
Minimum of Months | 169.74 | 17.73 | 66.40 | 2.32 | 53.21 | 0.00 | 0.00 |
Maximum of Months | 399.44 | 143.20 | 228.88 | 173.56 | 70.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 380.97 | 129.14 | 222.49 | 169.27 | 53.21 | 0.00 | 0.00 |
February | 356.91 | 115.95 | 201.59 | 141.51 | 60.08 | 0.00 | 0.00 |
March | 297.88 | 104.90 | 158.02 | 87.95 | 70.07 | 0.00 | 0.00 |
April | 221.35 | 66.55 | 104.29 | 33.95 | 70.34 | 0.00 | 0.00 |
May | 170.01 | 40.65 | 75.47 | 7.27 | 68.20 | 0.00 | 0.00 |
June | 170.68 | 20.83 | 66.40 | 2.32 | 64.07 | 0.00 | 0.00 |
July | 173.61 | 17.35 | 67.28 | 4.00 | 63.28 | 0.00 | 0.00 |
August | 210.19 | 24.49 | 83.50 | 18.13 | 65.37 | 0.00 | 0.00 |
September | 302.37 | 48.08 | 130.36 | 63.69 | 66.67 | 0.00 | 0.00 |
October | 362.12 | 75.53 | 183.92 | 122.85 | 61.07 | 0.00 | 0.00 |
November | 400.08 | 118.79 | 227.47 | 173.56 | 53.91 | 0.00 | 0.00 |
December | 384.92 | 141.20 | 228.88 | 172.81 | 56.07 | 0.00 | 0.00 |
Annual Sum or Average | 285.48 | 75.08 | 145.50 | 82.79 | 62.71 | 0.00 | 0.00 |
Minimum of Months | 170.01 | 17.35 | 66.40 | 2.32 | 53.21 | 0.00 | 0.00 |
Maximum of Months | 400.08 | 141.20 | 228.88 | 173.56 | 70.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 765.20 | 250.57 | 444.97 | 338.54 | 106.43 | 0.00 | 0.00 |
February | 717.31 | 224.75 | 403.19 | 283.03 | 120.16 | 0.00 | 0.00 |
March | 598.98 | 203.17 | 316.05 | 175.90 | 140.15 | 0.00 | 0.00 |
April | 443.43 | 128.85 | 208.58 | 67.89 | 140.68 | 0.00 | 0.00 |
May | 338.96 | 78.30 | 150.94 | 14.54 | 136.40 | 0.00 | 0.00 |
June | 340.12 | 39.68 | 132.79 | 4.65 | 128.15 | 0.00 | 0.00 |
July | 345.60 | 32.78 | 134.55 | 8.00 | 126.55 | 0.00 | 0.00 |
August | 418.73 | 46.73 | 167.00 | 36.26 | 130.74 | 0.00 | 0.00 |
September | 603.21 | 93.44 | 260.72 | 127.38 | 133.34 | 0.00 | 0.00 |
October | 724.10 | 148.14 | 367.85 | 245.70 | 122.15 | 0.00 | 0.00 |
November | 802.22 | 232.81 | 454.94 | 347.12 | 107.83 | 0.00 | 0.00 |
December | 773.05 | 275.21 | 457.76 | 345.62 | 112.14 | 0.00 | 0.00 |
Annual Sum or Average | 571.66 | 145.80 | 290.99 | 165.58 | 125.41 | 0.00 | 0.00 |
Minimum of Months | 338.96 | 32.78 | 132.79 | 4.65 | 106.43 | 0.00 | 0.00 |
Maximum of Months | 802.22 | 275.21 | 457.76 | 347.12 | 140.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 382.11 | 124.97 | 222.49 | 169.27 | 53.21 | 0.00 | 0.00 |
February | 358.22 | 112.05 | 201.59 | 141.51 | 60.08 | 0.00 | 0.00 |
March | 299.13 | 101.15 | 158.02 | 87.95 | 70.07 | 0.00 | 0.00 |
April | 221.51 | 63.97 | 104.29 | 33.95 | 70.34 | 0.00 | 0.00 |
May | 169.59 | 38.64 | 75.47 | 7.27 | 68.20 | 0.00 | 0.00 |
June | 170.59 | 19.37 | 66.40 | 2.32 | 64.07 | 0.00 | 0.00 |
July | 173.19 | 15.92 | 67.28 | 4.00 | 63.28 | 0.00 | 0.00 |
August | 209.57 | 22.86 | 83.50 | 18.13 | 65.37 | 0.00 | 0.00 |
September | 301.45 | 46.16 | 130.36 | 63.69 | 66.67 | 0.00 | 0.00 |
October | 361.63 | 73.69 | 183.92 | 122.85 | 61.07 | 0.00 | 0.00 |
November | 400.68 | 116.13 | 227.47 | 173.56 | 53.91 | 0.00 | 0.00 |
December | 386.06 | 137.40 | 228.88 | 172.81 | 56.07 | 0.00 | 0.00 |
Annual Sum or Average | 285.69 | 72.49 | 145.50 | 82.79 | 62.71 | 0.00 | 0.00 |
Minimum of Months | 169.59 | 15.92 | 66.40 | 2.32 | 53.21 | 0.00 | 0.00 |
Maximum of Months | 400.68 | 137.40 | 228.88 | 173.56 | 70.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 382.45 | 124.19 | 222.49 | 169.27 | 53.21 | 0.00 | 0.00 |
February | 358.62 | 111.27 | 201.59 | 141.51 | 60.08 | 0.00 | 0.00 |
March | 299.64 | 100.32 | 158.02 | 87.95 | 70.07 | 0.00 | 0.00 |
April | 221.80 | 63.54 | 104.29 | 33.95 | 70.34 | 0.00 | 0.00 |
May | 169.73 | 38.46 | 75.47 | 7.27 | 68.20 | 0.00 | 0.00 |
June | 170.71 | 19.27 | 66.40 | 2.32 | 64.07 | 0.00 | 0.00 |
July | 173.30 | 15.83 | 67.28 | 4.00 | 63.28 | 0.00 | 0.00 |
August | 209.65 | 22.76 | 83.50 | 18.13 | 65.37 | 0.00 | 0.00 |
September | 301.52 | 46.04 | 130.36 | 63.69 | 66.67 | 0.00 | 0.00 |
October | 361.76 | 73.45 | 183.92 | 122.85 | 61.07 | 0.00 | 0.00 |
November | 401.08 | 115.50 | 227.47 | 173.56 | 53.91 | 0.00 | 0.00 |
December | 386.36 | 136.79 | 228.88 | 172.81 | 56.07 | 0.00 | 0.00 |
Annual Sum or Average | 285.93 | 72.09 | 145.50 | 82.79 | 62.71 | 0.00 | 0.00 |
Minimum of Months | 169.73 | 15.83 | 66.40 | 2.32 | 53.21 | 0.00 | 0.00 |
Maximum of Months | 401.08 | 136.79 | 228.88 | 173.56 | 70.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 383.27 | 122.08 | 222.49 | 169.27 | 53.21 | 0.00 | 0.00 |
February | 359.67 | 109.08 | 201.59 | 141.51 | 60.08 | 0.00 | 0.00 |
March | 300.86 | 98.05 | 158.02 | 87.95 | 70.07 | 0.00 | 0.00 |
April | 222.52 | 62.28 | 104.29 | 33.95 | 70.34 | 0.00 | 0.00 |
May | 169.98 | 37.97 | 75.47 | 7.27 | 68.20 | 0.00 | 0.00 |
June | 170.70 | 19.15 | 66.40 | 2.32 | 64.07 | 0.00 | 0.00 |
July | 173.20 | 15.80 | 67.28 | 4.00 | 63.28 | 0.00 | 0.00 |
August | 209.53 | 22.76 | 83.50 | 18.13 | 65.37 | 0.00 | 0.00 |
September | 301.48 | 45.98 | 130.36 | 63.69 | 66.67 | 0.00 | 0.00 |
October | 362.05 | 72.84 | 183.92 | 122.85 | 61.07 | 0.00 | 0.00 |
November | 402.09 | 113.79 | 227.47 | 173.56 | 53.91 | 0.00 | 0.00 |
December | 387.12 | 135.03 | 228.88 | 172.81 | 56.07 | 0.00 | 0.00 |
Annual Sum or Average | 286.41 | 71.04 | 145.50 | 82.79 | 62.71 | 0.00 | 0.00 |
Minimum of Months | 169.98 | 15.80 | 66.40 | 2.32 | 53.21 | 0.00 | 0.00 |
Maximum of Months | 402.09 | 135.03 | 228.88 | 173.56 | 70.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 385.08 | 115.23 | 222.49 | 169.27 | 53.21 | 0.00 | 0.00 |
February | 361.89 | 101.96 | 201.59 | 141.51 | 60.08 | 0.00 | 0.00 |
March | 303.00 | 90.84 | 158.02 | 87.95 | 70.07 | 0.00 | 0.00 |
April | 223.42 | 57.96 | 104.29 | 33.95 | 70.34 | 0.00 | 0.00 |
May | 169.71 | 36.11 | 75.47 | 7.27 | 68.20 | 0.00 | 0.00 |
June | 169.17 | 18.78 | 66.40 | 2.32 | 64.07 | 0.00 | 0.00 |
July | 171.22 | 15.99 | 67.28 | 4.00 | 63.28 | 0.00 | 0.00 |
August | 207.60 | 23.14 | 83.50 | 18.13 | 65.37 | 0.00 | 0.00 |
September | 300.05 | 46.21 | 130.36 | 63.69 | 66.67 | 0.00 | 0.00 |
October | 362.20 | 70.81 | 183.92 | 122.85 | 61.07 | 0.00 | 0.00 |
November | 403.86 | 108.60 | 227.47 | 173.56 | 53.91 | 0.00 | 0.00 |
December | 388.90 | 129.03 | 228.88 | 172.81 | 56.07 | 0.00 | 0.00 |
Annual Sum or Average | 286.70 | 67.72 | 145.50 | 82.79 | 62.71 | 0.00 | 0.00 |
Minimum of Months | 169.17 | 15.99 | 66.40 | 2.32 | 53.21 | 0.00 | 0.00 |
Maximum of Months | 403.86 | 129.03 | 228.88 | 173.56 | 70.34 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.205021E+10 | 0.684579E+09 | 0.119426E+10 | 0.908611E+09 | 0.285647E+09 | 0.00 | 0.00 |
February | 0.173834E+10 | 0.551137E+09 | 0.977390E+09 | 0.686109E+09 | 0.291281E+09 | 0.00 | 0.00 |
March | 0.160892E+10 | 0.549375E+09 | 0.848238E+09 | 0.472090E+09 | 0.376148E+09 | 0.00 | 0.00 |
April | 0.115736E+10 | 0.328841E+09 | 0.541743E+09 | 0.176339E+09 | 0.365403E+09 | 0.00 | 0.00 |
May | 0.919263E+09 | 0.199922E+09 | 0.405109E+09 | 39029492.58 | 0.366080E+09 | 0.00 | 0.00 |
June | 0.898891E+09 | 95221517.37 | 0.344912E+09 | 12072519.39 | 0.332840E+09 | 0.00 | 0.00 |
July | 0.944663E+09 | 79365327.94 | 0.361121E+09 | 21468121.88 | 0.339653E+09 | 0.00 | 0.00 |
August | 0.113710E+10 | 0.116631E+09 | 0.448212E+09 | 97329162.41 | 0.350883E+09 | 0.00 | 0.00 |
September | 0.157169E+10 | 0.229688E+09 | 0.677176E+09 | 0.330843E+09 | 0.346333E+09 | 0.00 | 0.00 |
October | 0.194765E+10 | 0.389162E+09 | 0.987263E+09 | 0.659429E+09 | 0.327834E+09 | 0.00 | 0.00 |
November | 0.208328E+10 | 0.606223E+09 | 0.118164E+10 | 0.901573E+09 | 0.280065E+09 | 0.00 | 0.00 |
December | 0.207164E+10 | 0.748877E+09 | 0.122858E+10 | 0.927615E+09 | 0.300967E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.181290E+11 | 0.457902E+10 | 0.919564E+10 | 0.523251E+10 | 0.396313E+10 | 0.00 | 0.00 |
Minimum of Months | 0.898891E+09 | 79365327.94 | 0.344912E+09 | 12072519.39 | 0.280065E+09 | 0.00 | 0.00 |
Maximum of Months | 0.208328E+10 | 0.748877E+09 | 0.122858E+10 | 0.927615E+09 | 0.376148E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101550E+10 | 0.363797E+09 | 0.597129E+09 | 0.454306E+09 | 0.142823E+09 | 0.00 | 0.00 |
February | 0.859486E+09 | 0.292896E+09 | 0.488695E+09 | 0.343055E+09 | 0.145640E+09 | 0.00 | 0.00 |
March | 0.794273E+09 | 0.289749E+09 | 0.424119E+09 | 0.236045E+09 | 0.188074E+09 | 0.00 | 0.00 |
April | 0.574946E+09 | 0.169339E+09 | 0.270871E+09 | 88169648.54 | 0.182702E+09 | 0.00 | 0.00 |
May | 0.459589E+09 | 0.101293E+09 | 0.202555E+09 | 19514746.29 | 0.183040E+09 | 0.00 | 0.00 |
June | 0.451830E+09 | 48084255.45 | 0.172456E+09 | 6036259.69 | 0.166420E+09 | 0.00 | 0.00 |
July | 0.475207E+09 | 39752735.33 | 0.180560E+09 | 10734060.94 | 0.169826E+09 | 0.00 | 0.00 |
August | 0.571198E+09 | 58024673.78 | 0.224106E+09 | 48664581.20 | 0.175441E+09 | 0.00 | 0.00 |
September | 0.787162E+09 | 0.113630E+09 | 0.338588E+09 | 0.165421E+09 | 0.173167E+09 | 0.00 | 0.00 |
October | 0.972508E+09 | 0.195676E+09 | 0.493632E+09 | 0.329715E+09 | 0.163917E+09 | 0.00 | 0.00 |
November | 0.103544E+10 | 0.312513E+09 | 0.590819E+09 | 0.450786E+09 | 0.140032E+09 | 0.00 | 0.00 |
December | 0.102643E+10 | 0.394368E+09 | 0.614291E+09 | 0.463808E+09 | 0.150483E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.902356E+10 | 0.237912E+10 | 0.459782E+10 | 0.261625E+10 | 0.198157E+10 | 0.00 | 0.00 |
Minimum of Months | 0.451830E+09 | 39752735.33 | 0.172456E+09 | 6036259.69 | 0.140032E+09 | 0.00 | 0.00 |
Maximum of Months | 0.103544E+10 | 0.394368E+09 | 0.614291E+09 | 0.463808E+09 | 0.188074E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101578E+10 | 0.357229E+09 | 0.595904E+09 | 0.453374E+09 | 0.142530E+09 | 0.00 | 0.00 |
February | 0.859256E+09 | 0.289507E+09 | 0.487693E+09 | 0.342351E+09 | 0.145342E+09 | 0.00 | 0.00 |
March | 0.793593E+09 | 0.288862E+09 | 0.423249E+09 | 0.235561E+09 | 0.187688E+09 | 0.00 | 0.00 |
April | 0.572270E+09 | 0.175619E+09 | 0.270316E+09 | 87988770.48 | 0.182327E+09 | 0.00 | 0.00 |
May | 0.454802E+09 | 0.110017E+09 | 0.202139E+09 | 19474712.22 | 0.182664E+09 | 0.00 | 0.00 |
June | 0.442122E+09 | 54266505.60 | 0.172102E+09 | 6023876.44 | 0.166078E+09 | 0.00 | 0.00 |
July | 0.464877E+09 | 46674834.44 | 0.180190E+09 | 10712040.25 | 0.169478E+09 | 0.00 | 0.00 |
August | 0.562849E+09 | 65860777.01 | 0.223646E+09 | 48564746.90 | 0.175082E+09 | 0.00 | 0.00 |
September | 0.783529E+09 | 0.125173E+09 | 0.337893E+09 | 0.165082E+09 | 0.172811E+09 | 0.00 | 0.00 |
October | 0.969250E+09 | 0.204090E+09 | 0.492619E+09 | 0.329038E+09 | 0.163581E+09 | 0.00 | 0.00 |
November | 0.103441E+10 | 0.313250E+09 | 0.589607E+09 | 0.449862E+09 | 0.139745E+09 | 0.00 | 0.00 |
December | 0.102657E+10 | 0.388484E+09 | 0.613031E+09 | 0.462856E+09 | 0.150175E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.897931E+10 | 0.241903E+10 | 0.458839E+10 | 0.261089E+10 | 0.197750E+10 | 0.00 | 0.00 |
Minimum of Months | 0.442122E+09 | 46674834.44 | 0.172102E+09 | 6023876.44 | 0.139745E+09 | 0.00 | 0.00 |
Maximum of Months | 0.103441E+10 | 0.388484E+09 | 0.613031E+09 | 0.462856E+09 | 0.187688E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101777E+10 | 0.351718E+09 | 0.595904E+09 | 0.453374E+09 | 0.142530E+09 | 0.00 | 0.00 |
February | 0.860910E+09 | 0.285412E+09 | 0.487693E+09 | 0.342351E+09 | 0.145342E+09 | 0.00 | 0.00 |
March | 0.795117E+09 | 0.285546E+09 | 0.423249E+09 | 0.235561E+09 | 0.187688E+09 | 0.00 | 0.00 |
April | 0.572546E+09 | 0.174872E+09 | 0.270316E+09 | 87988770.48 | 0.182327E+09 | 0.00 | 0.00 |
May | 0.454642E+09 | 0.110377E+09 | 0.202139E+09 | 19474712.22 | 0.182664E+09 | 0.00 | 0.00 |
June | 0.441664E+09 | 54998370.63 | 0.172102E+09 | 6023876.44 | 0.166078E+09 | 0.00 | 0.00 |
July | 0.464359E+09 | 47474918.38 | 0.180190E+09 | 10712040.25 | 0.169478E+09 | 0.00 | 0.00 |
August | 0.562439E+09 | 66684971.15 | 0.223646E+09 | 48564746.90 | 0.175082E+09 | 0.00 | 0.00 |
September | 0.783346E+09 | 0.125892E+09 | 0.337893E+09 | 0.165082E+09 | 0.172811E+09 | 0.00 | 0.00 |
October | 0.969266E+09 | 0.203956E+09 | 0.492619E+09 | 0.329038E+09 | 0.163581E+09 | 0.00 | 0.00 |
November | 0.103534E+10 | 0.310988E+09 | 0.589607E+09 | 0.449862E+09 | 0.139745E+09 | 0.00 | 0.00 |
December | 0.102839E+10 | 0.383554E+09 | 0.613031E+09 | 0.462856E+09 | 0.150175E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.898579E+10 | 0.240147E+10 | 0.458839E+10 | 0.261089E+10 | 0.197750E+10 | 0.00 | 0.00 |
Minimum of Months | 0.441664E+09 | 47474918.38 | 0.172102E+09 | 6023876.44 | 0.139745E+09 | 0.00 | 0.00 |
Maximum of Months | 0.103534E+10 | 0.383554E+09 | 0.613031E+09 | 0.462856E+09 | 0.187688E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102038E+10 | 0.345879E+09 | 0.595904E+09 | 0.453374E+09 | 0.142530E+09 | 0.00 | 0.00 |
February | 0.863427E+09 | 0.280503E+09 | 0.487693E+09 | 0.342351E+09 | 0.145342E+09 | 0.00 | 0.00 |
March | 0.797854E+09 | 0.280978E+09 | 0.423249E+09 | 0.235561E+09 | 0.187688E+09 | 0.00 | 0.00 |
April | 0.573740E+09 | 0.172498E+09 | 0.270316E+09 | 87988770.48 | 0.182327E+09 | 0.00 | 0.00 |
May | 0.455352E+09 | 0.108889E+09 | 0.202139E+09 | 19474712.22 | 0.182664E+09 | 0.00 | 0.00 |
June | 0.442408E+09 | 53996865.58 | 0.172102E+09 | 6023876.44 | 0.166078E+09 | 0.00 | 0.00 |
July | 0.465005E+09 | 46481119.12 | 0.180190E+09 | 10712040.25 | 0.169478E+09 | 0.00 | 0.00 |
August | 0.562975E+09 | 65589953.39 | 0.223646E+09 | 48564746.90 | 0.175082E+09 | 0.00 | 0.00 |
September | 0.783746E+09 | 0.124636E+09 | 0.337893E+09 | 0.165082E+09 | 0.172811E+09 | 0.00 | 0.00 |
October | 0.969891E+09 | 0.202311E+09 | 0.492619E+09 | 0.329038E+09 | 0.163581E+09 | 0.00 | 0.00 |
November | 0.103701E+10 | 0.307895E+09 | 0.589607E+09 | 0.449862E+09 | 0.139745E+09 | 0.00 | 0.00 |
December | 0.103096E+10 | 0.378187E+09 | 0.613031E+09 | 0.462856E+09 | 0.150175E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.900275E+10 | 0.236784E+10 | 0.458839E+10 | 0.261089E+10 | 0.197750E+10 | 0.00 | 0.00 |
Minimum of Months | 0.442408E+09 | 46481119.12 | 0.172102E+09 | 6023876.44 | 0.139745E+09 | 0.00 | 0.00 |
Maximum of Months | 0.103701E+10 | 0.378187E+09 | 0.613031E+09 | 0.462856E+09 | 0.187688E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.204950E+10 | 0.671128E+09 | 0.119181E+10 | 0.906747E+09 | 0.285061E+09 | 0.00 | 0.00 |
February | 0.173532E+10 | 0.543718E+09 | 0.975385E+09 | 0.684702E+09 | 0.290683E+09 | 0.00 | 0.00 |
March | 0.160430E+10 | 0.544183E+09 | 0.846497E+09 | 0.471121E+09 | 0.375376E+09 | 0.00 | 0.00 |
April | 0.114937E+10 | 0.333988E+09 | 0.540631E+09 | 0.175978E+09 | 0.364654E+09 | 0.00 | 0.00 |
May | 0.907866E+09 | 0.209717E+09 | 0.404278E+09 | 38949424.45 | 0.365329E+09 | 0.00 | 0.00 |
June | 0.881590E+09 | 0.102859E+09 | 0.344205E+09 | 12047752.88 | 0.332157E+09 | 0.00 | 0.00 |
July | 0.925642E+09 | 87793073.18 | 0.360380E+09 | 21424080.51 | 0.338956E+09 | 0.00 | 0.00 |
August | 0.112152E+10 | 0.125167E+09 | 0.447293E+09 | 97129493.80 | 0.350163E+09 | 0.00 | 0.00 |
September | 0.156352E+10 | 0.242209E+09 | 0.675787E+09 | 0.330164E+09 | 0.345623E+09 | 0.00 | 0.00 |
October | 0.193943E+10 | 0.396783E+09 | 0.985238E+09 | 0.658077E+09 | 0.327161E+09 | 0.00 | 0.00 |
November | 0.207934E+10 | 0.603447E+09 | 0.117921E+10 | 0.899723E+09 | 0.279490E+09 | 0.00 | 0.00 |
December | 0.207055E+10 | 0.737114E+09 | 0.122606E+10 | 0.925712E+09 | 0.300350E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.180279E+11 | 0.459810E+10 | 0.917678E+10 | 0.522177E+10 | 0.395500E+10 | 0.00 | 0.00 |
Minimum of Months | 0.881590E+09 | 87793073.18 | 0.344205E+09 | 12047752.88 | 0.279490E+09 | 0.00 | 0.00 |
Maximum of Months | 0.207934E+10 | 0.737114E+09 | 0.122606E+10 | 0.925712E+09 | 0.375376E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102343E+10 | 0.334719E+09 | 0.595904E+09 | 0.453374E+09 | 0.142530E+09 | 0.00 | 0.00 |
February | 0.866598E+09 | 0.271063E+09 | 0.487693E+09 | 0.342351E+09 | 0.145342E+09 | 0.00 | 0.00 |
March | 0.801183E+09 | 0.270932E+09 | 0.423249E+09 | 0.235561E+09 | 0.187688E+09 | 0.00 | 0.00 |
April | 0.574157E+09 | 0.165816E+09 | 0.270316E+09 | 87988770.48 | 0.182327E+09 | 0.00 | 0.00 |
May | 0.454235E+09 | 0.103490E+09 | 0.202139E+09 | 19474712.22 | 0.182664E+09 | 0.00 | 0.00 |
June | 0.442172E+09 | 50203095.60 | 0.172102E+09 | 6023876.44 | 0.166078E+09 | 0.00 | 0.00 |
July | 0.463872E+09 | 42650737.53 | 0.180190E+09 | 10712040.25 | 0.169478E+09 | 0.00 | 0.00 |
August | 0.561302E+09 | 61219319.14 | 0.223646E+09 | 48564746.90 | 0.175082E+09 | 0.00 | 0.00 |
September | 0.781362E+09 | 0.119650E+09 | 0.337893E+09 | 0.165082E+09 | 0.172811E+09 | 0.00 | 0.00 |
October | 0.968584E+09 | 0.197371E+09 | 0.492619E+09 | 0.329038E+09 | 0.163581E+09 | 0.00 | 0.00 |
November | 0.103857E+10 | 0.301012E+09 | 0.589607E+09 | 0.449862E+09 | 0.139745E+09 | 0.00 | 0.00 |
December | 0.103403E+10 | 0.368023E+09 | 0.613031E+09 | 0.462856E+09 | 0.150175E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.900950E+10 | 0.228615E+10 | 0.458839E+10 | 0.261089E+10 | 0.197750E+10 | 0.00 | 0.00 |
Minimum of Months | 0.442172E+09 | 42650737.53 | 0.172102E+09 | 6023876.44 | 0.139745E+09 | 0.00 | 0.00 |
Maximum of Months | 0.103857E+10 | 0.368023E+09 | 0.613031E+09 | 0.462856E+09 | 0.187688E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102435E+10 | 0.332630E+09 | 0.595904E+09 | 0.453374E+09 | 0.142530E+09 | 0.00 | 0.00 |
February | 0.867583E+09 | 0.269194E+09 | 0.487693E+09 | 0.342351E+09 | 0.145342E+09 | 0.00 | 0.00 |
March | 0.802559E+09 | 0.268708E+09 | 0.423249E+09 | 0.235561E+09 | 0.187688E+09 | 0.00 | 0.00 |
April | 0.574913E+09 | 0.164698E+09 | 0.270316E+09 | 87988770.48 | 0.182327E+09 | 0.00 | 0.00 |
May | 0.454612E+09 | 0.102999E+09 | 0.202139E+09 | 19474712.22 | 0.182664E+09 | 0.00 | 0.00 |
June | 0.442484E+09 | 49937290.95 | 0.172102E+09 | 6023876.44 | 0.166078E+09 | 0.00 | 0.00 |
July | 0.464158E+09 | 42397999.67 | 0.180190E+09 | 10712040.25 | 0.169478E+09 | 0.00 | 0.00 |
August | 0.561531E+09 | 60963741.00 | 0.223646E+09 | 48564746.90 | 0.175082E+09 | 0.00 | 0.00 |
September | 0.781546E+09 | 0.119326E+09 | 0.337893E+09 | 0.165082E+09 | 0.172811E+09 | 0.00 | 0.00 |
October | 0.968945E+09 | 0.196732E+09 | 0.492619E+09 | 0.329038E+09 | 0.163581E+09 | 0.00 | 0.00 |
November | 0.103960E+10 | 0.299383E+09 | 0.589607E+09 | 0.449862E+09 | 0.139745E+09 | 0.00 | 0.00 |
December | 0.103483E+10 | 0.366385E+09 | 0.613031E+09 | 0.462856E+09 | 0.150175E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.901711E+10 | 0.227335E+10 | 0.458839E+10 | 0.261089E+10 | 0.197750E+10 | 0.00 | 0.00 |
Minimum of Months | 0.442484E+09 | 42397999.67 | 0.172102E+09 | 6023876.44 | 0.139745E+09 | 0.00 | 0.00 |
Maximum of Months | 0.103960E+10 | 0.366385E+09 | 0.613031E+09 | 0.462856E+09 | 0.187688E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102655E+10 | 0.326976E+09 | 0.595904E+09 | 0.453374E+09 | 0.142530E+09 | 0.00 | 0.00 |
February | 0.870118E+09 | 0.263875E+09 | 0.487693E+09 | 0.342351E+09 | 0.145342E+09 | 0.00 | 0.00 |
March | 0.805834E+09 | 0.262605E+09 | 0.423249E+09 | 0.235561E+09 | 0.187688E+09 | 0.00 | 0.00 |
April | 0.576781E+09 | 0.161429E+09 | 0.270316E+09 | 87988770.48 | 0.182327E+09 | 0.00 | 0.00 |
May | 0.455266E+09 | 0.101711E+09 | 0.202139E+09 | 19474712.22 | 0.182664E+09 | 0.00 | 0.00 |
June | 0.442458E+09 | 49630707.99 | 0.172102E+09 | 6023876.44 | 0.166078E+09 | 0.00 | 0.00 |
July | 0.463902E+09 | 42308214.80 | 0.180190E+09 | 10712040.25 | 0.169478E+09 | 0.00 | 0.00 |
August | 0.561212E+09 | 60963775.26 | 0.223646E+09 | 48564746.90 | 0.175082E+09 | 0.00 | 0.00 |
September | 0.781428E+09 | 0.119173E+09 | 0.337893E+09 | 0.165082E+09 | 0.172811E+09 | 0.00 | 0.00 |
October | 0.969709E+09 | 0.195098E+09 | 0.492619E+09 | 0.329038E+09 | 0.163581E+09 | 0.00 | 0.00 |
November | 0.104222E+10 | 0.294931E+09 | 0.589607E+09 | 0.449862E+09 | 0.139745E+09 | 0.00 | 0.00 |
December | 0.103687E+10 | 0.361664E+09 | 0.613031E+09 | 0.462856E+09 | 0.150175E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.903235E+10 | 0.224037E+10 | 0.458839E+10 | 0.261089E+10 | 0.197750E+10 | 0.00 | 0.00 |
Minimum of Months | 0.442458E+09 | 42308214.80 | 0.172102E+09 | 6023876.44 | 0.139745E+09 | 0.00 | 0.00 |
Maximum of Months | 0.104222E+10 | 0.361664E+09 | 0.613031E+09 | 0.462856E+09 | 0.187688E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103141E+10 | 0.308633E+09 | 0.595904E+09 | 0.453374E+09 | 0.142530E+09 | 0.00 | 0.00 |
February | 0.875475E+09 | 0.246664E+09 | 0.487693E+09 | 0.342351E+09 | 0.145342E+09 | 0.00 | 0.00 |
March | 0.811567E+09 | 0.243316E+09 | 0.423249E+09 | 0.235561E+09 | 0.187688E+09 | 0.00 | 0.00 |
April | 0.579096E+09 | 0.150241E+09 | 0.270316E+09 | 87988770.48 | 0.182327E+09 | 0.00 | 0.00 |
May | 0.454547E+09 | 96719129.42 | 0.202139E+09 | 19474712.22 | 0.182664E+09 | 0.00 | 0.00 |
June | 0.438498E+09 | 48675589.52 | 0.172102E+09 | 6023876.44 | 0.166078E+09 | 0.00 | 0.00 |
July | 0.458597E+09 | 42835293.53 | 0.180190E+09 | 10712040.25 | 0.169478E+09 | 0.00 | 0.00 |
August | 0.556034E+09 | 61983395.23 | 0.223646E+09 | 48564746.90 | 0.175082E+09 | 0.00 | 0.00 |
September | 0.777741E+09 | 0.119773E+09 | 0.337893E+09 | 0.165082E+09 | 0.172811E+09 | 0.00 | 0.00 |
October | 0.970124E+09 | 0.189650E+09 | 0.492619E+09 | 0.329038E+09 | 0.163581E+09 | 0.00 | 0.00 |
November | 0.104680E+10 | 0.281500E+09 | 0.589607E+09 | 0.449862E+09 | 0.139745E+09 | 0.00 | 0.00 |
December | 0.104162E+10 | 0.345602E+09 | 0.613031E+09 | 0.462856E+09 | 0.150175E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.904151E+10 | 0.213559E+10 | 0.458839E+10 | 0.261089E+10 | 0.197750E+10 | 0.00 | 0.00 |
Minimum of Months | 0.438498E+09 | 42835293.53 | 0.172102E+09 | 6023876.44 | 0.139745E+09 | 0.00 | 0.00 |
Maximum of Months | 0.104680E+10 | 0.345602E+09 | 0.613031E+09 | 0.462856E+09 | 0.187688E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.336891E+09 | -215182403.7 | 0.00 | 0.00 | 744.00 | 0.00 | -121708579.8 | 59.00 | 0.00 | 0.00 |
February | 0.303750E+09 | -195215312.8 | 0.00 | 0.00 | 672.00 | 0.00 | -108534810.6 | 58.99 | 0.00 | 0.00 |
March | 0.329685E+09 | -211651580.2 | 0.00 | 0.00 | 744.00 | 0.00 | -118033626.7 | 58.99 | 0.00 | 0.00 |
April | 0.299419E+09 | -188696406.9 | 0.00 | 0.00 | 720.00 | 0.00 | -110722269.3 | 58.99 | 0.00 | 0.00 |
May | 0.292274E+09 | -179187744.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113086505.5 | 58.99 | 0.00 | 0.00 |
June | 0.270026E+09 | -161377053.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108649232.4 | 58.99 | 0.00 | 0.00 |
July | 0.267286E+09 | -155331484.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111954977.1 | 58.99 | 0.00 | 0.00 |
August | 0.270740E+09 | -158721744.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112018514.2 | 58.99 | 0.00 | 0.00 |
September | 0.268593E+09 | -159859148.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108733727.8 | 58.99 | 0.00 | 0.00 |
October | 0.290743E+09 | -177586585.4 | 0.00 | 0.00 | 744.00 | 0.00 | -113156020.2 | 58.99 | 0.00 | 0.00 |
November | 0.299514E+09 | -186783569.5 | 0.00 | 0.00 | 720.00 | 0.00 | -112730436.8 | 58.99 | 0.00 | 0.00 |
December | 0.329762E+09 | -207551847.3 | 0.00 | 0.00 | 744.00 | 0.00 | -122209748.3 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.355868E+10 | -0.219714E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.136154E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.267286E+09 | -215182403.7 | 0.00 | 0.00 | 672.00 | 0.00 | -122209748.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.336891E+09 | -155331484.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108534810.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.333988E+09 | -215190255.9 | 0.00 | 0.00 | 744.00 | 0.00 | -118797581.3 | 58.99 | 0.00 | 0.00 |
February | 0.301371E+09 | -195214810.3 | 0.00 | 0.00 | 672.00 | 0.00 | -106156189.3 | 59.00 | 0.00 | 0.00 |
March | 0.327589E+09 | -211653681.9 | 0.00 | 0.00 | 744.00 | 0.00 | -115935344.3 | 58.99 | 0.00 | 0.00 |
April | 0.298755E+09 | -188704008.6 | 0.00 | 0.00 | 720.00 | 0.00 | -110050910.0 | 58.99 | 0.00 | 0.00 |
May | 0.292043E+09 | -179192884.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112850176.6 | 58.99 | 0.00 | 0.00 |
June | 0.269900E+09 | -161376242.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108523453.1 | 58.99 | 0.00 | 0.00 |
July | 0.267216E+09 | -155344025.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111872293.1 | 58.99 | 0.00 | 0.00 |
August | 0.270721E+09 | -158714304.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112006270.1 | 58.99 | 0.00 | 0.00 |
September | 0.268633E+09 | -159853465.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108779621.1 | 58.99 | 0.00 | 0.00 |
October | 0.290522E+09 | -177583707.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112937969.7 | 58.99 | 0.00 | 0.00 |
November | 0.298140E+09 | -186797529.7 | 0.00 | 0.00 | 720.00 | 0.00 | -111342804.9 | 58.99 | 0.00 | 0.00 |
December | 0.326996E+09 | -207558245.2 | 0.00 | 0.00 | 744.00 | 0.00 | -119437867.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.354587E+10 | -0.219718E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.134869E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.267216E+09 | -215190255.9 | 0.00 | 0.00 | 672.00 | 0.00 | -119437867.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.333988E+09 | -155344025.4 | 0.00 | 0.00 | 744.00 | 0.00 | -106156189.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.309618E+09 | -189227879.4 | 0.00 | 0.00 | 744.00 | 0.00 | -120390273.6 | 58.99 | 0.00 | 0.00 |
February | 0.279011E+09 | -171820602.1 | 0.00 | 0.00 | 672.00 | 0.00 | -107189914.3 | 58.99 | 0.00 | 0.00 |
March | 0.305458E+09 | -188895673.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116562621.6 | 58.99 | 0.00 | 0.00 |
April | 0.275260E+09 | -165931791.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109328391.1 | 59.00 | 0.00 | 0.00 |
May | 0.270405E+09 | -158959019.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111445832.4 | 58.99 | 0.00 | 0.00 |
June | 0.250506E+09 | -143679472.2 | 0.00 | 0.00 | 720.00 | 0.00 | -106826102.2 | 59.00 | 0.00 | 0.00 |
July | 0.245786E+09 | -135791983.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109994453.5 | 58.99 | 0.00 | 0.00 |
August | 0.252019E+09 | -141762409.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110256714.6 | 58.99 | 0.00 | 0.00 |
September | 0.247744E+09 | -140474979.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107269385.0 | 59.01 | 0.00 | 0.00 |
October | 0.268150E+09 | -156204807.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111944951.9 | 58.99 | 0.00 | 0.00 |
November | 0.276672E+09 | -164927833.6 | 0.00 | 0.00 | 720.00 | 0.00 | -111744365.4 | 58.99 | 0.00 | 0.00 |
December | 0.302132E+09 | -181169189.2 | 0.00 | 0.00 | 744.00 | 0.00 | -120963290.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.328276E+10 | -0.193885E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.134392E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.245786E+09 | -189227879.4 | 0.00 | 0.00 | 672.00 | 0.00 | -120963290.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.309618E+09 | -135791983.0 | 0.00 | 0.00 | 744.00 | 0.00 | -106826102.2 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.310221E+09 | -189237862.2 | 0.00 | 0.00 | 744.00 | 0.00 | -120983634.3 | 58.99 | 0.00 | 0.00 |
February | 0.279472E+09 | -171808161.7 | 0.00 | 0.00 | 672.00 | 0.00 | -107664255.1 | 58.99 | 0.00 | 0.00 |
March | 0.305841E+09 | -188893860.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116947629.5 | 58.99 | 0.00 | 0.00 |
April | 0.275332E+09 | -165952014.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109380412.8 | 59.00 | 0.00 | 0.00 |
May | 0.270363E+09 | -158960867.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111402325.4 | 58.99 | 0.00 | 0.00 |
June | 0.250419E+09 | -143682006.1 | 0.00 | 0.00 | 720.00 | 0.00 | -106736533.0 | 59.00 | 0.00 | 0.00 |
July | 0.245682E+09 | -135792610.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109889345.0 | 58.99 | 0.00 | 0.00 |
August | 0.251929E+09 | -141761024.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110168307.3 | 58.99 | 0.00 | 0.00 |
September | 0.247673E+09 | -140477689.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107195665.3 | 59.01 | 0.00 | 0.00 |
October | 0.268164E+09 | -156207054.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111956796.4 | 58.99 | 0.00 | 0.00 |
November | 0.276917E+09 | -164925928.1 | 0.00 | 0.00 | 720.00 | 0.00 | -111990890.3 | 58.99 | 0.00 | 0.00 |
December | 0.302675E+09 | -181167484.1 | 0.00 | 0.00 | 744.00 | 0.00 | -121507349.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.328469E+10 | -0.193887E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.134582E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.245682E+09 | -189237862.2 | 0.00 | 0.00 | 672.00 | 0.00 | -121507349.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.310221E+09 | -135792610.0 | 0.00 | 0.00 | 744.00 | 0.00 | -106736533.0 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.301893E+09 | -178850579.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123042380.1 | 58.99 | 0.00 | 0.00 |
February | 0.271950E+09 | -162484200.0 | 0.00 | 0.00 | 672.00 | 0.00 | -109466262.5 | 58.99 | 0.00 | 0.00 |
March | 0.297513E+09 | -178714056.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118798461.2 | 59.00 | 0.00 | 0.00 |
April | 0.267464E+09 | -157067330.5 | 0.00 | 0.00 | 720.00 | 0.00 | -110396634.8 | 58.99 | 0.00 | 0.00 |
May | 0.262490E+09 | -150354261.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112136053.0 | 58.98 | 0.00 | 0.00 |
June | 0.243351E+09 | -135987610.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107363642.2 | 58.99 | 0.00 | 0.00 |
July | 0.238877E+09 | -128421112.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110455866.7 | 58.99 | 0.00 | 0.00 |
August | 0.244860E+09 | -134143192.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110716940.5 | 58.99 | 0.00 | 0.00 |
September | 0.240679E+09 | -132950269.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107728781.5 | 59.00 | 0.00 | 0.00 |
October | 0.260282E+09 | -147622864.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112659536.0 | 58.99 | 0.00 | 0.00 |
November | 0.269041E+09 | -155771027.1 | 0.00 | 0.00 | 720.00 | 0.00 | -113269496.3 | 58.99 | 0.00 | 0.00 |
December | 0.294812E+09 | -171341283.0 | 0.00 | 0.00 | 744.00 | 0.00 | -123470979.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.319321E+10 | -0.183371E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135951E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.238877E+09 | -178850579.7 | 0.00 | 0.00 | 672.00 | 0.00 | -123470979.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.301893E+09 | -128421112.7 | 0.00 | 0.00 | 744.00 | 0.00 | -107363642.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.302024E+09 | -178854644.6 | 0.00 | 0.00 | 744.00 | 0.00 | -123169756.0 | 58.99 | 0.00 | 0.00 |
February | 0.272058E+09 | -162480654.7 | 0.00 | 0.00 | 672.00 | 0.00 | -109577801.6 | 58.99 | 0.00 | 0.00 |
March | 0.297657E+09 | -178735604.6 | 0.00 | 0.00 | 744.00 | 0.00 | -118921648.1 | 58.99 | 0.00 | 0.00 |
April | 0.267528E+09 | -157043373.8 | 0.00 | 0.00 | 720.00 | 0.00 | -110484496.2 | 59.00 | 0.00 | 0.00 |
May | 0.262547E+09 | -150310381.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112236824.1 | 59.00 | 0.00 | 0.00 |
June | 0.243443E+09 | -135990345.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107452510.8 | 58.99 | 0.00 | 0.00 |
July | 0.238970E+09 | -128435805.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110534511.8 | 58.98 | 0.00 | 0.00 |
August | 0.244968E+09 | -134126648.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110841773.7 | 59.00 | 0.00 | 0.00 |
September | 0.240762E+09 | -132982263.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107779778.5 | 58.99 | 0.00 | 0.00 |
October | 0.260344E+09 | -147636050.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112707942.4 | 58.99 | 0.00 | 0.00 |
November | 0.269126E+09 | -155776283.3 | 0.00 | 0.00 | 720.00 | 0.00 | -113350116.2 | 58.99 | 0.00 | 0.00 |
December | 0.294906E+09 | -171353273.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123553015.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.319434E+10 | -0.183373E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.136061E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.238970E+09 | -178854644.6 | 0.00 | 0.00 | 672.00 | 0.00 | -123553015.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.302024E+09 | -128435805.0 | 0.00 | 0.00 | 744.00 | 0.00 | -107452510.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.302239E+09 | -178860108.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123379315.1 | 58.99 | 0.00 | 0.00 |
February | 0.272280E+09 | -162474313.8 | 0.00 | 0.00 | 672.00 | 0.00 | -109805288.8 | 59.00 | 0.00 | 0.00 |
March | 0.297913E+09 | -178724966.4 | 0.00 | 0.00 | 744.00 | 0.00 | -119188434.0 | 58.99 | 0.00 | 0.00 |
April | 0.267654E+09 | -157070291.6 | 0.00 | 0.00 | 720.00 | 0.00 | -110583693.3 | 58.99 | 0.00 | 0.00 |
May | 0.262598E+09 | -150351214.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112246901.9 | 58.98 | 0.00 | 0.00 |
June | 0.243478E+09 | -135994645.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107483759.0 | 58.99 | 0.00 | 0.00 |
July | 0.239008E+09 | -128422068.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110585543.7 | 58.99 | 0.00 | 0.00 |
August | 0.244992E+09 | -134139534.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110852747.2 | 58.99 | 0.00 | 0.00 |
September | 0.240793E+09 | -133011420.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107781351.6 | 58.98 | 0.00 | 0.00 |
October | 0.260415E+09 | -147645570.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112769750.2 | 58.99 | 0.00 | 0.00 |
November | 0.269328E+09 | -155761684.4 | 0.00 | 0.00 | 720.00 | 0.00 | -113566342.5 | 58.99 | 0.00 | 0.00 |
December | 0.295078E+09 | -171356819.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123721156.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.319578E+10 | -0.183381E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.136196E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.239008E+09 | -178860108.4 | 0.00 | 0.00 | 672.00 | 0.00 | -123721156.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.302239E+09 | -128422068.9 | 0.00 | 0.00 | 744.00 | 0.00 | -107483759.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.134120E+10 | 55422.80 | 05-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.763996E+09 | 55422.80 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.380984E+09 | 55422.80 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 149690.71 | 249.48 | 11-APR-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.296776E+09 | 55422.80 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200899E+10 | 55422.80 | 04-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.479210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.200899E+10 | 55422.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151888E+09 | 28433.04 | 26-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 67825806.20 | 28433.04 | 02-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34274643.84 | 28433.04 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32871096.76 | 22280.92 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.328415E+09 | 28433.04 | 20-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.615274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.328415E+09 | 28433.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.331064E+09 | 28724.20 | 27-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139748E+09 | 28724.20 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 61755698.13 | 27912.68 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 76139187.53 | 17638.90 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.556599E+09 | 28724.20 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.556599E+09 | 28724.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.418035E+09 | 28823.61 | 27-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174197E+09 | 28823.61 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77086004.59 | 28823.61 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94235365.08 | 20421.54 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.654601E+09 | 28823.61 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.654601E+09 | 28823.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.580756E+09 | 28652.85 | 26-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.252064E+09 | 28652.85 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119708E+09 | 28652.85 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123755E+09 | 23520.48 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.832864E+09 | 28652.85 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.832864E+09 | 28652.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154236E+10 | 52609.30 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.731286E+09 | 52609.30 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352648E+09 | 52609.30 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.350429E+09 | 52609.30 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210765E+10 | 52609.30 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.508437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.210765E+10 | 52609.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.853949E+09 | 27129.94 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.411621E+09 | 27129.94 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199432E+09 | 27129.94 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189117E+09 | 27129.94 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114410E+10 | 27129.94 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114410E+10 | 27129.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.926286E+09 | 27022.58 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.458018E+09 | 27022.58 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228180E+09 | 27022.58 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201682E+09 | 27022.58 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121118E+10 | 27022.58 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.302534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121118E+10 | 27022.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116387E+10 | 27046.53 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.622583E+09 | 27046.53 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.331294E+09 | 27046.53 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1002362.84 | 3626.86 | 01-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247515E+09 | 27046.53 | 27-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144178E+10 | 27046.53 | 02-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.380804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144178E+10 | 27046.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185094E+10 | 30138.17 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112587E+10 | 30138.17 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.695128E+09 | 30138.17 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26473462.23 | 23086.55 | 12-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.400624E+09 | 30138.17 | 27-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205826E+10 | 30138.17 | 01-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.615730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.205826E+10 | 30138.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 18.94 | 18.94 | 0.03 | 03-JAN-13:10 | 0.03 | 0.00 |
February | 0.00 | 0.00 | 0.219917E+09 | 0.219917E+09 | 5007.86 | 20-FEB-16:00 | 5007.86 | 0.00 |
March | 0.00 | 0.00 | 0.672490E+09 | 0.672490E+09 | 6448.64 | 14-MAR-16:30 | 6448.64 | 0.00 |
April | 0.00 | 0.00 | 0.684460E+10 | 0.682213E+10 | 13921.06 | 30-APR-16:05 | 13921.06 | 0.00 |
May | 0.00 | 0.00 | 0.139707E+11 | 0.135375E+11 | 26208.32 | 31-MAY-07:03 | 26208.32 | 0.00 |
June | 0.00 | 0.00 | 0.200680E+11 | 0.192893E+11 | 42980.49 | 19-JUN-07:02 | 36144.53 | 0.00 |
July | 0.00 | 0.00 | 0.244701E+11 | 0.202111E+11 | 46174.21 | 20-JUL-07:03 | 27562.75 | 0.00 |
August | 0.00 | 0.00 | 0.213986E+11 | 0.188416E+11 | 45936.07 | 02-AUG-07:03 | 25367.20 | 0.00 |
September | 0.00 | 0.00 | 0.180433E+11 | 0.156154E+11 | 45193.45 | 23-SEP-07:03 | 25538.45 | 0.00 |
October | 0.00 | 0.00 | 0.810006E+10 | 0.723309E+10 | 42048.27 | 02-OCT-07:02 | 35995.19 | 0.00 |
November | 0.00 | 0.00 | 0.586451E+09 | 0.579150E+09 | 8209.86 | 09-NOV-15:00 | 8209.86 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.114374E+12 | 0.103022E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.244701E+11 | 0.202111E+11 | 46174.21 | 36144.53 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3850557.85 | 3848117.28 | 2030.62 | 01-JAN-18:10 | 2022.49 | 0.00 |
February | 0.00 | 0.00 | 0.196527E+09 | 0.196497E+09 | 20555.52 | 19-FEB-18:01 | 20555.52 | 0.00 |
March | 0.00 | 0.00 | 0.535239E+09 | 0.535239E+09 | 20555.52 | 12-MAR-17:20 | 20555.52 | 0.00 |
April | 0.00 | 0.00 | 0.430020E+10 | 0.428017E+10 | 21267.78 | 18-APR-21:00 | 18791.21 | 0.00 |
May | 0.00 | 0.00 | 0.776874E+10 | 0.749306E+10 | 22252.34 | 27-MAY-21:00 | 16405.71 | 0.00 |
June | 0.00 | 0.00 | 0.103225E+11 | 0.990493E+10 | 22236.23 | 29-JUN-22:32 | 16855.01 | 0.00 |
July | 0.00 | 0.00 | 0.123839E+11 | 0.102793E+11 | 23662.36 | 19-JUL-07:03 | 9921.14 | 0.00 |
August | 0.00 | 0.00 | 0.110259E+11 | 0.967850E+10 | 23412.00 | 03-AUG-07:02 | 14048.51 | 0.00 |
September | 0.00 | 0.00 | 0.980950E+10 | 0.848248E+10 | 23095.74 | 03-SEP-22:55 | 11473.18 | 0.00 |
October | 0.00 | 0.00 | 0.484972E+10 | 0.432740E+10 | 23035.30 | 03-OCT-20:03 | 13613.56 | 0.00 |
November | 0.00 | 0.00 | 0.401273E+09 | 0.396626E+09 | 20555.52 | 08-NOV-21:09 | 20555.52 | 0.00 |
December | 0.00 | 0.00 | 2487091.70 | 2487091.70 | 1670.54 | 10-DEC-18:10 | 1670.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.615998E+11 | 0.555806E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 2487091.70 | 2487091.70 | 1670.54 | 1670.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.123839E+11 | 0.102793E+11 | 23662.36 | 20555.52 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 105105.36 | 105105.36 | 115.00 | 03-JAN-15:00 | 115.00 | 0.00 |
February | 0.00 | 0.00 | 0.117306E+09 | 0.117306E+09 | 2447.90 | 20-FEB-15:00 | 2447.90 | 0.00 |
March | 0.00 | 0.00 | 0.401672E+09 | 0.401672E+09 | 3594.13 | 22-MAR-13:00 | 3594.13 | 0.00 |
April | 0.00 | 0.00 | 0.282601E+10 | 0.281644E+10 | 7013.01 | 21-APR-14:00 | 7013.01 | 0.00 |
May | 0.00 | 0.00 | 0.559553E+10 | 0.543623E+10 | 15575.35 | 31-MAY-06:03 | 15575.35 | 0.00 |
June | 0.00 | 0.00 | 0.796054E+10 | 0.766013E+10 | 22048.15 | 19-JUN-06:02 | 18936.55 | 0.00 |
July | 0.00 | 0.00 | 0.953991E+10 | 0.787019E+10 | 23880.26 | 17-JUL-06:02 | 10406.24 | 0.00 |
August | 0.00 | 0.00 | 0.841068E+10 | 0.735264E+10 | 23783.16 | 03-AUG-06:02 | 12722.35 | 0.00 |
September | 0.00 | 0.00 | 0.724584E+10 | 0.632259E+10 | 23332.04 | 23-SEP-06:02 | 13227.83 | 0.00 |
October | 0.00 | 0.00 | 0.341792E+10 | 0.308649E+10 | 21684.34 | 02-OCT-06:02 | 19844.58 | 0.00 |
November | 0.00 | 0.00 | 0.321854E+09 | 0.318045E+09 | 4327.55 | 09-NOV-14:00 | 4327.55 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.458374E+11 | 0.413819E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.953991E+10 | 0.787019E+10 | 23880.26 | 19844.58 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 24.81 | 24.81 | 0.04 | 03-JAN-12:50 | 0.04 | 0.00 |
February | 0.00 | 0.00 | 99970310.08 | 99970310.08 | 2246.14 | 20-FEB-15:00 | 2246.14 | 0.00 |
March | 0.00 | 0.00 | 0.369612E+09 | 0.369612E+09 | 3486.27 | 22-MAR-13:00 | 3486.27 | 0.00 |
April | 0.00 | 0.00 | 0.279968E+10 | 0.279024E+10 | 7009.41 | 21-APR-14:00 | 7009.41 | 0.00 |
May | 0.00 | 0.00 | 0.561761E+10 | 0.545741E+10 | 15977.10 | 31-MAY-06:03 | 15977.10 | 0.00 |
June | 0.00 | 0.00 | 0.801576E+10 | 0.771333E+10 | 22133.02 | 19-JUN-06:02 | 19032.97 | 0.00 |
July | 0.00 | 0.00 | 0.960479E+10 | 0.792701E+10 | 23969.96 | 17-JUL-06:02 | 10463.43 | 0.00 |
August | 0.00 | 0.00 | 0.847106E+10 | 0.740606E+10 | 23871.15 | 03-AUG-06:02 | 12778.60 | 0.00 |
September | 0.00 | 0.00 | 0.728928E+10 | 0.636063E+10 | 23418.80 | 23-SEP-06:02 | 13287.87 | 0.00 |
October | 0.00 | 0.00 | 0.341104E+10 | 0.308107E+10 | 21765.71 | 02-OCT-06:02 | 19933.03 | 0.00 |
November | 0.00 | 0.00 | 0.305054E+09 | 0.301402E+09 | 4274.44 | 09-NOV-14:00 | 4274.44 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.459838E+11 | 0.415067E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.960479E+10 | 0.792701E+10 | 23969.96 | 19933.03 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 20.78 | 20.78 | 0.03 | 03-JAN-13:10 | 0.03 | 0.00 |
February | 0.00 | 0.00 | 76729961.94 | 76729961.94 | 1948.68 | 20-FEB-15:00 | 1948.68 | 0.00 |
March | 0.00 | 0.00 | 0.310269E+09 | 0.310269E+09 | 3235.50 | 22-MAR-13:00 | 3235.50 | 0.00 |
April | 0.00 | 0.00 | 0.265894E+10 | 0.265005E+10 | 6856.89 | 21-APR-14:00 | 6856.89 | 0.00 |
May | 0.00 | 0.00 | 0.545474E+10 | 0.529851E+10 | 14646.61 | 31-MAY-06:03 | 14646.61 | 0.00 |
June | 0.00 | 0.00 | 0.785608E+10 | 0.756008E+10 | 21991.73 | 19-JUN-06:02 | 18888.96 | 0.00 |
July | 0.00 | 0.00 | 0.943849E+10 | 0.778159E+10 | 23818.17 | 17-JUL-06:02 | 10376.26 | 0.00 |
August | 0.00 | 0.00 | 0.830864E+10 | 0.726276E+10 | 23719.74 | 03-AUG-06:02 | 12664.18 | 0.00 |
September | 0.00 | 0.00 | 0.713367E+10 | 0.622223E+10 | 23269.44 | 23-SEP-06:02 | 13172.66 | 0.00 |
October | 0.00 | 0.00 | 0.328985E+10 | 0.297051E+10 | 21625.14 | 02-OCT-06:02 | 19774.95 | 0.00 |
November | 0.00 | 0.00 | 0.269037E+09 | 0.265751E+09 | 4095.43 | 09-NOV-14:00 | 4095.43 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.447965E+11 | 0.403985E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.943849E+10 | 0.778159E+10 | 23818.17 | 19774.95 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.127349E+09 | 0.127349E+09 | 3652.89 | 20-FEB-15:20 | 3652.89 | 0.00 |
March | 0.00 | 0.00 | 0.510030E+09 | 0.510030E+09 | 5876.49 | 22-MAR-13:00 | 5876.49 | 0.00 |
April | 0.00 | 0.00 | 0.482870E+10 | 0.480847E+10 | 13589.31 | 21-APR-14:30 | 13589.31 | 0.00 |
May | 0.00 | 0.00 | 0.102047E+11 | 0.987936E+10 | 28937.21 | 30-MAY-07:03 | 28937.21 | 0.00 |
June | 0.00 | 0.00 | 0.148405E+11 | 0.142529E+11 | 40506.30 | 19-JUN-07:02 | 34921.89 | 0.00 |
July | 0.00 | 0.00 | 0.176099E+11 | 0.144288E+11 | 43571.86 | 19-JUL-07:03 | 18245.32 | 0.00 |
August | 0.00 | 0.00 | 0.156349E+11 | 0.135836E+11 | 43331.15 | 03-AUG-07:02 | 25012.59 | 0.00 |
September | 0.00 | 0.00 | 0.134909E+11 | 0.116767E+11 | 42508.70 | 23-SEP-07:03 | 24995.14 | 0.00 |
October | 0.00 | 0.00 | 0.604378E+10 | 0.538415E+10 | 39732.94 | 02-OCT-07:02 | 34209.48 | 0.00 |
November | 0.00 | 0.00 | 0.449988E+09 | 0.443106E+09 | 7383.67 | 09-NOV-14:00 | 7383.67 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.837406E+11 | 0.750945E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.176099E+11 | 0.144288E+11 | 43571.86 | 34921.89 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 56208037.87 | 56208037.87 | 1789.13 | 20-FEB-15:30 | 1789.13 | 0.00 |
March | 0.00 | 0.00 | 0.238181E+09 | 0.238181E+09 | 2915.60 | 22-MAR-13:00 | 2915.60 | 0.00 |
April | 0.00 | 0.00 | 0.246110E+10 | 0.245177E+10 | 7015.02 | 21-APR-14:40 | 7015.02 | 0.00 |
May | 0.00 | 0.00 | 0.524886E+10 | 0.508683E+10 | 14692.94 | 30-MAY-07:03 | 14692.94 | 0.00 |
June | 0.00 | 0.00 | 0.764390E+10 | 0.735206E+10 | 20915.95 | 19-JUN-07:02 | 18134.52 | 0.00 |
July | 0.00 | 0.00 | 0.906951E+10 | 0.745406E+10 | 22403.84 | 18-JUL-07:03 | 12621.24 | 0.00 |
August | 0.00 | 0.00 | 0.804785E+10 | 0.701371E+10 | 22373.22 | 03-AUG-07:02 | 12972.25 | 0.00 |
September | 0.00 | 0.00 | 0.694127E+10 | 0.602649E+10 | 21948.80 | 23-SEP-07:03 | 12959.71 | 0.00 |
October | 0.00 | 0.00 | 0.309717E+10 | 0.276711E+10 | 20515.39 | 02-OCT-07:02 | 17764.12 | 0.00 |
November | 0.00 | 0.00 | 0.221515E+09 | 0.218472E+09 | 3772.27 | 09-NOV-14:00 | 3772.27 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.430256E+11 | 0.386649E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.906951E+10 | 0.745406E+10 | 22403.84 | 18134.52 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 122.70 | 122.70 | 0.07 | 03-JAN-17:00 | 0.07 | 0.00 |
February | 0.00 | 0.00 | 49952883.14 | 49952883.14 | 1704.27 | 20-FEB-15:40 | 1704.27 | 0.00 |
March | 0.00 | 0.00 | 0.219362E+09 | 0.219362E+09 | 2818.24 | 22-MAR-13:00 | 2818.24 | 0.00 |
April | 0.00 | 0.00 | 0.240903E+10 | 0.239995E+10 | 6955.66 | 21-APR-14:40 | 6955.66 | 0.00 |
May | 0.00 | 0.00 | 0.519697E+10 | 0.503638E+10 | 14208.87 | 30-MAY-07:03 | 14208.87 | 0.00 |
June | 0.00 | 0.00 | 0.759745E+10 | 0.730765E+10 | 20827.39 | 19-JUN-07:02 | 18048.38 | 0.00 |
July | 0.00 | 0.00 | 0.902063E+10 | 0.741188E+10 | 22309.60 | 18-JUL-07:03 | 12558.99 | 0.00 |
August | 0.00 | 0.00 | 0.800421E+10 | 0.697520E+10 | 22279.24 | 03-AUG-07:02 | 12907.98 | 0.00 |
September | 0.00 | 0.00 | 0.689904E+10 | 0.598886E+10 | 21856.28 | 23-SEP-07:03 | 12896.08 | 0.00 |
October | 0.00 | 0.00 | 0.305724E+10 | 0.273108E+10 | 20428.50 | 02-OCT-07:02 | 17679.92 | 0.00 |
November | 0.00 | 0.00 | 0.209005E+09 | 0.206106E+09 | 3693.21 | 09-NOV-14:00 | 3693.21 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.426629E+11 | 0.383264E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.902063E+10 | 0.741188E+10 | 22309.60 | 18048.38 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 35630826.12 | 35630826.12 | 1495.89 | 20-FEB-15:40 | 1495.89 | 0.00 |
March | 0.00 | 0.00 | 0.178397E+09 | 0.178397E+09 | 2597.23 | 22-MAR-13:00 | 2597.23 | 0.00 |
April | 0.00 | 0.00 | 0.228945E+10 | 0.228111E+10 | 6840.90 | 21-APR-14:40 | 6840.90 | 0.00 |
May | 0.00 | 0.00 | 0.509573E+10 | 0.493881E+10 | 12188.66 | 30-MAY-07:03 | 12188.66 | 0.00 |
June | 0.00 | 0.00 | 0.756382E+10 | 0.727782E+10 | 20844.88 | 19-JUN-07:02 | 18053.34 | 0.00 |
July | 0.00 | 0.00 | 0.901223E+10 | 0.740793E+10 | 22328.62 | 18-JUL-07:03 | 12552.40 | 0.00 |
August | 0.00 | 0.00 | 0.800652E+10 | 0.698178E+10 | 22298.73 | 03-AUG-07:02 | 12908.55 | 0.00 |
September | 0.00 | 0.00 | 0.688738E+10 | 0.597972E+10 | 21875.65 | 23-SEP-07:03 | 12898.08 | 0.00 |
October | 0.00 | 0.00 | 0.298146E+10 | 0.266372E+10 | 20446.00 | 02-OCT-07:02 | 17687.02 | 0.00 |
November | 0.00 | 0.00 | 0.183436E+09 | 0.180900E+09 | 3546.38 | 09-NOV-14:00 | 3546.38 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.422341E+11 | 0.379258E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.901223E+10 | 0.740793E+10 | 22328.62 | 18053.34 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 23077779.45 | 23077779.45 | 1341.35 | 20-FEB-15:30 | 1341.35 | 0.00 |
March | 0.00 | 0.00 | 0.147085E+09 | 0.147085E+09 | 2570.99 | 22-MAR-13:00 | 2570.99 | 0.00 |
April | 0.00 | 0.00 | 0.244118E+10 | 0.243410E+10 | 7362.33 | 21-APR-14:20 | 7362.33 | 0.00 |
May | 0.00 | 0.00 | 0.565590E+10 | 0.549259E+10 | 9569.91 | 31-MAY-07:03 | 9569.91 | 0.00 |
June | 0.00 | 0.00 | 0.862189E+10 | 0.831632E+10 | 23183.47 | 19-JUN-07:02 | 19781.56 | 0.00 |
July | 0.00 | 0.00 | 0.103460E+11 | 0.858992E+10 | 24774.59 | 17-JUL-07:02 | 15832.83 | 0.00 |
August | 0.00 | 0.00 | 0.930924E+10 | 0.818702E+10 | 24753.90 | 03-AUG-07:02 | 14181.83 | 0.00 |
September | 0.00 | 0.00 | 0.803190E+10 | 0.702834E+10 | 24162.64 | 03-SEP-08:62 | 15171.27 | 0.00 |
October | 0.00 | 0.00 | 0.329755E+10 | 0.296574E+10 | 22677.71 | 02-OCT-07:02 | 19628.46 | 0.00 |
November | 0.00 | 0.00 | 0.180939E+09 | 0.178894E+09 | 3789.26 | 09-NOV-14:00 | 3789.26 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.480547E+11 | 0.433631E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.103460E+11 | 0.858992E+10 | 24774.59 | 19781.56 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.176071E+10 | 0.42 | 2378.18 | 05-JAN-08:61 | 1.02 |
February | 0.158143E+10 | 0.42 | 2378.18 | 01-FEB-08:61 | 1.01 |
March | 0.174274E+10 | 0.42 | 2378.18 | 01-MAR-08:61 | 1.01 |
April | 0.167120E+10 | 0.42 | 957.70 | 11-APR-08:30 | 0.62 |
May | 0.172607E+10 | 0.41 | 1386.75 | 31-MAY-07:03 | 0.77 |
June | 0.168383E+10 | 0.42 | 2378.18 | 07-JUN-07:02 | 1.01 |
July | 0.173323E+10 | 0.41 | 2378.18 | 02-JUL-07:02 | 1.00 |
August | 0.173367E+10 | 0.41 | 2378.18 | 01-AUG-07:02 | 1.00 |
September | 0.167626E+10 | 0.41 | 2378.18 | 03-SEP-07:02 | 1.00 |
October | 0.172630E+10 | 0.41 | 2378.18 | 02-OCT-07:02 | 1.00 |
November | 0.167545E+10 | 0.42 | 2378.18 | 28-NOV-08:61 | 1.01 |
December | 0.178493E+10 | 0.43 | 2378.18 | 04-DEC-08:61 | 1.01 |
Annual Sum or Average | 0.204958E+11 | 0.42 | |||
Minimum of Months | 0.158143E+10 | 0.41 | 957.70 | 0.62 | |
Maximum of Months | 0.178493E+10 | 0.43 | 2378.18 | 1.02 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.712239E+09 | 0.35 | 1270.64 | 26-JAN-08:61 | 1.05 |
February | 0.695489E+09 | 0.39 | 1270.64 | 02-FEB-08:61 | 1.05 |
March | 0.828278E+09 | 0.41 | 1270.64 | 02-MAR-08:61 | 1.05 |
April | 0.787348E+09 | 0.41 | 508.26 | 03-APR-07:10 | 0.63 |
May | 0.793665E+09 | 0.42 | 912.68 | 31-MAY-07:03 | 0.89 |
June | 0.784080E+09 | 0.44 | 1270.64 | 07-JUN-07:02 | 1.04 |
July | 0.818967E+09 | 0.44 | 1270.64 | 02-JUL-07:02 | 1.03 |
August | 0.817469E+09 | 0.43 | 1270.64 | 01-AUG-07:02 | 1.03 |
September | 0.785120E+09 | 0.42 | 1270.64 | 03-SEP-07:02 | 1.03 |
October | 0.853624E+09 | 0.42 | 1270.64 | 02-OCT-07:02 | 1.04 |
November | 0.826866E+09 | 0.41 | 1105.68 | 28-NOV-08:61 | 0.98 |
December | 0.705209E+09 | 0.35 | 1270.64 | 20-DEC-08:61 | 1.05 |
Annual Sum or Average | 0.940835E+10 | 0.41 | |||
Minimum of Months | 0.695489E+09 | 0.35 | 508.26 | 0.63 | |
Maximum of Months | 0.853624E+09 | 0.44 | 1270.64 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.753859E+09 | 0.35 | 1286.90 | 27-JAN-07:02 | 1.05 |
February | 0.678297E+09 | 0.35 | 1286.90 | 03-FEB-07:02 | 1.05 |
March | 0.761444E+09 | 0.35 | 1265.08 | 02-MAR-07:02 | 1.04 |
April | 0.722722E+09 | 0.34 | 514.76 | 22-APR-16:20 | 0.64 |
May | 0.752479E+09 | 0.35 | 900.22 | 31-MAY-06:03 | 0.88 |
June | 0.736159E+09 | 0.35 | 1286.90 | 03-JUN-06:02 | 1.04 |
July | 0.744299E+09 | 0.34 | 1286.90 | 02-JUL-07:02 | 1.03 |
August | 0.762262E+09 | 0.35 | 1286.90 | 01-AUG-06:02 | 1.03 |
September | 0.724094E+09 | 0.34 | 1286.90 | 03-SEP-07:02 | 1.03 |
October | 0.745231E+09 | 0.34 | 1286.90 | 02-OCT-06:02 | 1.04 |
November | 0.724768E+09 | 0.34 | 988.91 | 28-NOV-07:02 | 0.93 |
December | 0.756215E+09 | 0.35 | 1286.90 | 04-DEC-07:02 | 1.05 |
Annual Sum or Average | 0.886183E+10 | 0.34 | |||
Minimum of Months | 0.678297E+09 | 0.34 | 514.76 | 0.64 | |
Maximum of Months | 0.762262E+09 | 0.35 | 1286.90 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.759420E+09 | 0.35 | 1292.45 | 27-JAN-07:02 | 1.05 |
February | 0.682137E+09 | 0.35 | 1292.45 | 02-FEB-07:02 | 1.05 |
March | 0.765136E+09 | 0.35 | 1292.45 | 02-MAR-07:02 | 1.05 |
April | 0.725840E+09 | 0.34 | 516.98 | 06-APR-10:30 | 0.63 |
May | 0.755740E+09 | 0.35 | 929.30 | 31-MAY-06:03 | 0.89 |
June | 0.739365E+09 | 0.35 | 1292.45 | 03-JUN-06:02 | 1.04 |
July | 0.747577E+09 | 0.34 | 1292.45 | 02-JUL-07:02 | 1.03 |
August | 0.765637E+09 | 0.35 | 1292.45 | 01-AUG-06:02 | 1.03 |
September | 0.727305E+09 | 0.34 | 1292.45 | 03-SEP-07:02 | 1.03 |
October | 0.748455E+09 | 0.34 | 1292.45 | 02-OCT-06:02 | 1.04 |
November | 0.728375E+09 | 0.34 | 1066.40 | 28-NOV-07:02 | 0.96 |
December | 0.762062E+09 | 0.35 | 1292.45 | 04-DEC-07:02 | 1.05 |
Annual Sum or Average | 0.890705E+10 | 0.34 | |||
Minimum of Months | 0.682137E+09 | 0.34 | 516.98 | 0.63 | |
Maximum of Months | 0.765637E+09 | 0.35 | 1292.45 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.758255E+09 | 0.35 | 1282.91 | 26-JAN-07:02 | 1.05 |
February | 0.679223E+09 | 0.35 | 1282.91 | 02-FEB-07:02 | 1.05 |
March | 0.760648E+09 | 0.35 | 1282.91 | 02-MAR-07:02 | 1.05 |
April | 0.720484E+09 | 0.34 | 513.17 | 10-APR-09:50 | 0.63 |
May | 0.750135E+09 | 0.35 | 832.50 | 31-MAY-06:03 | 0.85 |
June | 0.733672E+09 | 0.35 | 1282.91 | 05-JUN-06:02 | 1.04 |
July | 0.741962E+09 | 0.34 | 1282.91 | 02-JUL-07:02 | 1.03 |
August | 0.759802E+09 | 0.35 | 1282.91 | 01-AUG-06:02 | 1.03 |
September | 0.721746E+09 | 0.34 | 1282.91 | 03-SEP-07:02 | 1.03 |
October | 0.742890E+09 | 0.34 | 1282.91 | 02-OCT-06:02 | 1.04 |
November | 0.723809E+09 | 0.34 | 1145.03 | 28-NOV-07:02 | 0.99 |
December | 0.761333E+09 | 0.35 | 1282.91 | 04-DEC-07:02 | 1.05 |
Annual Sum or Average | 0.885396E+10 | 0.34 | |||
Minimum of Months | 0.679223E+09 | 0.34 | 513.17 | 0.63 | |
Maximum of Months | 0.761333E+09 | 0.35 | 1282.91 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.122857E+10 | 0.31 | 2226.35 | 02-JAN-08:61 | 1.01 |
February | 0.109577E+10 | 0.31 | 2226.35 | 01-FEB-08:61 | 1.01 |
March | 0.122401E+10 | 0.31 | 2226.35 | 01-MAR-08:61 | 1.01 |
April | 0.115414E+10 | 0.31 | 890.54 | 21-APR-08:70 | 0.61 |
May | 0.120243E+10 | 0.31 | 1567.59 | 30-MAY-07:03 | 0.85 |
June | 0.118082E+10 | 0.31 | 2226.35 | 05-JUN-07:02 | 1.00 |
July | 0.119282E+10 | 0.30 | 2226.35 | 02-JUL-08:62 | 1.00 |
August | 0.122011E+10 | 0.31 | 2226.35 | 01-AUG-07:02 | 1.00 |
September | 0.115624E+10 | 0.30 | 2226.35 | 03-SEP-08:62 | 1.00 |
October | 0.118969E+10 | 0.30 | 2226.35 | 02-OCT-07:02 | 1.00 |
November | 0.116304E+10 | 0.31 | 2226.35 | 28-NOV-08:61 | 1.01 |
December | 0.123651E+10 | 0.31 | 2226.35 | 03-DEC-09:01 | 1.01 |
Annual Sum or Average | 0.142441E+11 | 0.31 | |||
Minimum of Months | 0.109577E+10 | 0.30 | 890.54 | 0.61 | |
Maximum of Months | 0.123651E+10 | 0.31 | 2226.35 | 1.01 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.662571E+09 | 0.32 | 1197.87 | 02-JAN-08:61 | 1.04 |
February | 0.590481E+09 | 0.32 | 1197.87 | 01-FEB-08:61 | 1.05 |
March | 0.659031E+09 | 0.33 | 1197.87 | 01-MAR-08:61 | 1.05 |
April | 0.620975E+09 | 0.32 | 479.15 | 02-APR-09:50 | 0.64 |
May | 0.646948E+09 | 0.32 | 825.30 | 30-MAY-07:03 | 0.87 |
June | 0.635465E+09 | 0.32 | 1197.87 | 05-JUN-07:02 | 1.04 |
July | 0.641809E+09 | 0.31 | 1197.87 | 02-JUL-08:62 | 1.03 |
August | 0.656451E+09 | 0.32 | 1197.87 | 01-AUG-07:02 | 1.03 |
September | 0.621999E+09 | 0.31 | 1197.87 | 03-SEP-08:62 | 1.03 |
October | 0.640091E+09 | 0.31 | 1197.87 | 02-OCT-07:02 | 1.04 |
November | 0.625985E+09 | 0.32 | 1197.87 | 28-NOV-08:61 | 1.05 |
December | 0.666808E+09 | 0.32 | 1197.87 | 03-DEC-09:01 | 1.05 |
Annual Sum or Average | 0.766861E+10 | 0.32 | |||
Minimum of Months | 0.590481E+09 | 0.31 | 479.15 | 0.64 | |
Maximum of Months | 0.666808E+09 | 0.33 | 1197.87 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.661259E+09 | 0.32 | 1191.87 | 01-JAN-09:01 | 1.04 |
February | 0.588796E+09 | 0.32 | 1191.87 | 01-FEB-08:61 | 1.05 |
March | 0.656515E+09 | 0.33 | 1191.87 | 01-MAR-08:61 | 1.05 |
April | 0.617867E+09 | 0.32 | 476.75 | 07-APR-16:30 | 0.64 |
May | 0.643702E+09 | 0.32 | 791.36 | 30-MAY-07:03 | 0.85 |
June | 0.632271E+09 | 0.32 | 1191.87 | 05-JUN-07:02 | 1.04 |
July | 0.638593E+09 | 0.31 | 1191.87 | 02-JUL-08:62 | 1.03 |
August | 0.653176E+09 | 0.32 | 1191.87 | 01-AUG-07:02 | 1.03 |
September | 0.618859E+09 | 0.31 | 1191.87 | 03-SEP-08:62 | 1.03 |
October | 0.636884E+09 | 0.31 | 1191.87 | 02-OCT-07:02 | 1.04 |
November | 0.623204E+09 | 0.32 | 1191.87 | 28-NOV-08:61 | 1.05 |
December | 0.665366E+09 | 0.32 | 1191.87 | 03-DEC-09:01 | 1.05 |
Annual Sum or Average | 0.763649E+10 | 0.32 | |||
Minimum of Months | 0.588796E+09 | 0.31 | 476.75 | 0.64 | |
Maximum of Months | 0.665366E+09 | 0.33 | 1191.87 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.668268E+09 | 0.33 | 1193.21 | 01-JAN-09:01 | 1.04 |
February | 0.593802E+09 | 0.32 | 1193.21 | 01-FEB-08:61 | 1.05 |
March | 0.659975E+09 | 0.33 | 1193.21 | 01-MAR-08:61 | 1.05 |
April | 0.618586E+09 | 0.32 | 573.29 | 01-APR-07:03 | 0.71 |
May | 0.644384E+09 | 0.32 | 647.90 | 30-MAY-07:03 | 0.76 |
June | 0.632795E+09 | 0.32 | 1193.21 | 05-JUN-07:02 | 1.04 |
July | 0.639277E+09 | 0.31 | 1193.21 | 02-JUL-08:62 | 1.03 |
August | 0.653991E+09 | 0.32 | 1193.21 | 01-AUG-07:02 | 1.03 |
September | 0.619463E+09 | 0.31 | 1193.21 | 03-SEP-08:62 | 1.03 |
October | 0.637587E+09 | 0.31 | 1193.21 | 02-OCT-07:02 | 1.04 |
November | 0.625112E+09 | 0.32 | 1193.21 | 27-NOV-08:61 | 1.05 |
December | 0.672188E+09 | 0.33 | 1193.21 | 02-DEC-08:61 | 1.05 |
Annual Sum or Average | 0.766543E+10 | 0.32 | |||
Minimum of Months | 0.593802E+09 | 0.31 | 573.29 | 0.71 | |
Maximum of Months | 0.672188E+09 | 0.33 | 1193.21 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.780014E+09 | 0.33 | 1365.84 | 01-JAN-09:01 | 1.05 |
February | 0.691460E+09 | 0.33 | 1365.84 | 01-FEB-08:61 | 1.05 |
March | 0.764320E+09 | 0.33 | 1365.84 | 01-MAR-08:61 | 1.05 |
April | 0.708769E+09 | 0.32 | 1174.09 | 12-APR-07:02 | 0.98 |
May | 0.737551E+09 | 0.32 | 546.33 | 21-MAY-14:00 | 0.63 |
June | 0.724456E+09 | 0.32 | 1365.84 | 15-JUN-07:02 | 1.05 |
July | 0.733458E+09 | 0.31 | 1365.84 | 02-JUL-08:62 | 1.03 |
August | 0.750179E+09 | 0.32 | 1365.84 | 01-AUG-07:02 | 1.03 |
September | 0.708854E+09 | 0.31 | 1365.84 | 03-SEP-08:62 | 1.03 |
October | 0.729795E+09 | 0.31 | 1365.84 | 02-OCT-07:02 | 1.04 |
November | 0.718943E+09 | 0.32 | 1365.84 | 27-NOV-08:61 | 1.05 |
December | 0.781718E+09 | 0.33 | 1365.84 | 01-DEC-08:62 | 1.05 |
Annual Sum or Average | 0.882952E+10 | 0.32 | |||
Minimum of Months | 0.691460E+09 | 0.31 | 546.33 | 0.63 | |
Maximum of Months | 0.781718E+09 | 0.33 | 1365.84 | 1.05 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.176071E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.164026E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.192239E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.350924E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.549475E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.726303E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.809355E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.733433E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.627430E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.377470E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.182708E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.178493E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.506793E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.164026E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.809355E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.713254E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.745145E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.964329E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.187722E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.281310E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.359356E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.398502E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.363968E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.319977E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.202350E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.927247E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.705863E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.251877E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.705863E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.398502E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.753887E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.709101E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.866212E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.146633E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.223561E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.291195E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.318161E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.291933E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.254903E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.159540E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.806463E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.756215E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.207511E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.709101E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.318161E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.759420E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.708509E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.861836E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.146356E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.224479E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.292915E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.320045E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.293725E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.256276E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.159738E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.805901E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.762062E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.208331E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.708509E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.320045E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.758255E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.699606E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.842280E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.142430E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.220032E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.288480E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.315690E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.289398E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.252186E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.156382E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.792369E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.761333E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.204998E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.699606E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.315690E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.122857E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.113023E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.136102E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.245746E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.395884E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.530563E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.574656E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.528327E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.459917E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.272005E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.127985E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.123651E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.363072E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.113023E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.574656E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.662571E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.605466E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.722052E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.127427E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.204052E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.272415E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.294770E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.271269E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.236339E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.141097E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.682515E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.666808E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.188131E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.605466E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.294770E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.661259E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.602138E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.714691E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.125835E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.202437E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.270882E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.293229E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.269849E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.234995E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.139831E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.676608E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.665366E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.186907E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.602138E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.293229E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.668268E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.603365E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.707580E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.123021E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.200141E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.270192E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.293159E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.269992E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.234789E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.138155E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.672140E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.672188E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.186180E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.603365E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.293159E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.780014E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.697703E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.803944E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.136323E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.224393E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.307340E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.335486E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.311185E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.270870E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.155204E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.765447E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.781718E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.212368E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.697703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.335486E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.176071E+10 | 18.94 | 0.134120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158143E+10 | 0.219917E+09 | 0.763996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174274E+10 | 0.672490E+09 | 0.380984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167120E+10 | 0.684460E+10 | 149690.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172607E+10 | 0.139707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168383E+10 | 0.200680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.173323E+10 | 0.244701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173367E+10 | 0.213986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167626E+10 | 0.180433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172630E+10 | 0.810006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167545E+10 | 0.586451E+09 | 0.296776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178493E+10 | 0.00 | 0.200899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204958E+11 | 0.114374E+12 | 0.479210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178493E+10 | 0.244701E+11 | 0.200899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.712239E+09 | 3850557.85 | 0.151888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.695489E+09 | 0.188466E+09 | 67825806.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.828278E+09 | 0.521246E+09 | 34274643.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.787348E+09 | 0.407961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.793665E+09 | 0.755686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.784080E+09 | 0.102347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.818967E+09 | 0.123175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.817469E+09 | 0.108630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.785120E+09 | 0.945065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.853624E+09 | 0.461611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.826866E+09 | 0.397063E+09 | 32871096.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.705209E+09 | 2487091.70 | 0.328415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.940835E+10 | 0.602315E+11 | 0.615274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.695489E+09 | 2487091.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.853624E+09 | 0.123175E+11 | 0.328415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.753859E+09 | 105105.36 | 0.331064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.678297E+09 | 0.117306E+09 | 0.139748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.761444E+09 | 0.401672E+09 | 61755698.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.722722E+09 | 0.282601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.752479E+09 | 0.559553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.736159E+09 | 0.796054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.744299E+09 | 0.953991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.762262E+09 | 0.841068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.724094E+09 | 0.724584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.745231E+09 | 0.341792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724768E+09 | 0.321854E+09 | 76139187.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.756215E+09 | 0.00 | 0.556599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.886183E+10 | 0.458374E+11 | 0.116531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.678297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.762262E+09 | 0.953991E+10 | 0.556599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.759420E+09 | 24.81 | 0.418035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.682137E+09 | 99970310.08 | 0.174197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.765136E+09 | 0.369612E+09 | 77086004.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.725840E+09 | 0.279968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.755740E+09 | 0.561761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.739365E+09 | 0.801576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.747577E+09 | 0.960479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.765637E+09 | 0.847106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.727305E+09 | 0.728928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.748455E+09 | 0.341104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.728375E+09 | 0.305054E+09 | 94235365.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.762062E+09 | 0.00 | 0.654601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.890705E+10 | 0.459838E+11 | 0.141815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.682137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.765637E+09 | 0.960479E+10 | 0.654601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.758255E+09 | 20.78 | 0.580756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.679223E+09 | 76729961.94 | 0.252064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.760648E+09 | 0.310269E+09 | 0.119708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.720484E+09 | 0.265894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.750135E+09 | 0.545474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.733672E+09 | 0.785608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.741962E+09 | 0.943849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.759802E+09 | 0.830864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.721746E+09 | 0.713367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.742890E+09 | 0.328985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.723809E+09 | 0.269037E+09 | 0.123755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.761333E+09 | 0.00 | 0.832864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.885396E+10 | 0.447965E+11 | 0.190915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.679223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.761333E+09 | 0.943849E+10 | 0.832864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.122857E+10 | 0.00 | 0.154236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109577E+10 | 0.127349E+09 | 0.731286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122401E+10 | 0.510030E+09 | 0.352648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115414E+10 | 0.482870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120243E+10 | 0.102047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118082E+10 | 0.148405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119282E+10 | 0.176099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122011E+10 | 0.156349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115624E+10 | 0.134909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118969E+10 | 0.604378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116304E+10 | 0.449988E+09 | 0.350429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123651E+10 | 0.00 | 0.210765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142441E+11 | 0.837406E+11 | 0.508437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.123651E+10 | 0.176099E+11 | 0.210765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.662571E+09 | 0.00 | 0.853949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.590481E+09 | 56208037.87 | 0.411621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.659031E+09 | 0.238181E+09 | 0.199432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.620975E+09 | 0.246110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.646948E+09 | 0.524886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.635465E+09 | 0.764390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.641809E+09 | 0.906951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.656451E+09 | 0.804785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.621999E+09 | 0.694127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.640091E+09 | 0.309717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.625985E+09 | 0.221515E+09 | 0.189117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.666808E+09 | 0.00 | 0.114410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.766861E+10 | 0.430256E+11 | 0.279822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.590481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.666808E+09 | 0.906951E+10 | 0.114410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.661259E+09 | 122.70 | 0.926286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.588796E+09 | 49952883.14 | 0.458018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.656515E+09 | 0.219362E+09 | 0.228180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.617867E+09 | 0.240903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.643702E+09 | 0.519697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.632271E+09 | 0.759745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.638593E+09 | 0.902063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.653176E+09 | 0.800421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.618859E+09 | 0.689904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.636884E+09 | 0.305724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.623204E+09 | 0.209005E+09 | 0.201682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.665366E+09 | 0.00 | 0.121118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.763649E+10 | 0.426629E+11 | 0.302534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.588796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.665366E+09 | 0.902063E+10 | 0.121118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.668268E+09 | 0.00 | 0.116387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.593802E+09 | 35630826.12 | 0.622583E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.659975E+09 | 0.178397E+09 | 0.331294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.618586E+09 | 0.228945E+10 | 1002362.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.644384E+09 | 0.509573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.632795E+09 | 0.756382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.639277E+09 | 0.901223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.653991E+09 | 0.800652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.619463E+09 | 0.688738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.637587E+09 | 0.298146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.625112E+09 | 0.183436E+09 | 0.247515E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.672188E+09 | 0.00 | 0.144178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.766543E+10 | 0.422341E+11 | 0.380804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.593802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.672188E+09 | 0.901223E+10 | 0.144178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.780014E+09 | 0.00 | 0.185094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.691460E+09 | 23077779.45 | 0.112587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.764320E+09 | 0.147085E+09 | 0.695128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.708769E+09 | 0.244118E+10 | 26473462.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.737551E+09 | 0.565590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.724456E+09 | 0.862189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.733458E+09 | 0.103460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.750179E+09 | 0.930924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.708854E+09 | 0.803190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.729795E+09 | 0.329755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.718943E+09 | 0.180939E+09 | 0.400624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.781718E+09 | 0.00 | 0.205826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.882952E+10 | 0.480547E+11 | 0.615730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.691460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.781718E+09 | 0.103460E+11 | 0.205826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.176071E+10 | 0.00 | 0.00 | 0.00 | 5.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158143E+10 | 0.00 | 0.00 | 0.00 | 58835642.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174274E+10 | 0.00 | 0.00 | 0.00 | 0.179652E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167120E+10 | 0.00 | 0.00 | 0.00 | 0.183804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172607E+10 | 0.00 | 0.00 | 0.00 | 0.376868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168383E+10 | 0.00 | 0.00 | 0.00 | 0.557920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.173323E+10 | 0.00 | 0.00 | 0.00 | 0.636032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173367E+10 | 0.00 | 0.00 | 0.00 | 0.560066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167626E+10 | 0.00 | 0.00 | 0.00 | 0.459804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172630E+10 | 0.00 | 0.00 | 0.00 | 0.204840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167545E+10 | 0.00 | 0.00 | 0.00 | 0.151632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204958E+11 | 0.00 | 0.00 | 0.00 | 0.301834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178493E+10 | 0.00 | 0.00 | 0.00 | 0.636032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.712239E+09 | 0.00 | 0.00 | 0.00 | 1015182.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.695489E+09 | 0.00 | 0.00 | 0.00 | 49656356.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.828278E+09 | 0.00 | 0.00 | 0.00 | 0.136051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.787348E+09 | 0.00 | 0.00 | 0.00 | 0.108988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.793665E+09 | 0.00 | 0.00 | 0.00 | 0.201944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.784080E+09 | 0.00 | 0.00 | 0.00 | 0.280948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.818967E+09 | 0.00 | 0.00 | 0.00 | 0.316605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.817469E+09 | 0.00 | 0.00 | 0.00 | 0.282221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.785120E+09 | 0.00 | 0.00 | 0.00 | 0.241465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.853624E+09 | 0.00 | 0.00 | 0.00 | 0.116987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.826866E+09 | 0.00 | 0.00 | 0.00 | 0.100381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.705209E+09 | 0.00 | 0.00 | 0.00 | 653502.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.940835E+10 | 0.00 | 0.00 | 0.00 | 0.157793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.695489E+09 | 0.00 | 0.00 | 0.00 | 653502.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.853624E+09 | 0.00 | 0.00 | 0.00 | 0.316605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.753859E+09 | 0.00 | 0.00 | 0.00 | 28208.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.678297E+09 | 0.00 | 0.00 | 0.00 | 30804115.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.761444E+09 | 0.00 | 0.00 | 0.00 | 0.104768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.722722E+09 | 0.00 | 0.00 | 0.00 | 0.743606E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.752479E+09 | 0.00 | 0.00 | 0.00 | 0.148313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.736159E+09 | 0.00 | 0.00 | 0.00 | 0.217579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.744299E+09 | 0.00 | 0.00 | 0.00 | 0.243732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.762262E+09 | 0.00 | 0.00 | 0.00 | 0.215707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.724094E+09 | 0.00 | 0.00 | 0.00 | 0.182494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.745231E+09 | 0.00 | 0.00 | 0.00 | 0.850168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724768E+09 | 0.00 | 0.00 | 0.00 | 81694282.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.756215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.886183E+10 | 0.00 | 0.00 | 0.00 | 0.118893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.678297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.762262E+09 | 0.00 | 0.00 | 0.00 | 0.243732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.759420E+09 | 0.00 | 0.00 | 0.00 | 6.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.682137E+09 | 0.00 | 0.00 | 0.00 | 26372389.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.765136E+09 | 0.00 | 0.00 | 0.00 | 96699867.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.725840E+09 | 0.00 | 0.00 | 0.00 | 0.737716E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.755740E+09 | 0.00 | 0.00 | 0.00 | 0.148905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.739365E+09 | 0.00 | 0.00 | 0.00 | 0.218979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.747577E+09 | 0.00 | 0.00 | 0.00 | 0.245287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.765637E+09 | 0.00 | 0.00 | 0.00 | 0.217161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.727305E+09 | 0.00 | 0.00 | 0.00 | 0.183546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.748455E+09 | 0.00 | 0.00 | 0.00 | 0.848927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.728375E+09 | 0.00 | 0.00 | 0.00 | 77525754.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.762062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.890705E+10 | 0.00 | 0.00 | 0.00 | 0.119260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.682137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.765637E+09 | 0.00 | 0.00 | 0.00 | 0.245287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.758255E+09 | 0.00 | 0.00 | 0.00 | 5.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.679223E+09 | 0.00 | 0.00 | 0.00 | 20382788.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.760648E+09 | 0.00 | 0.00 | 0.00 | 81632507.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.720484E+09 | 0.00 | 0.00 | 0.00 | 0.703817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.750135E+09 | 0.00 | 0.00 | 0.00 | 0.145018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.733672E+09 | 0.00 | 0.00 | 0.00 | 0.215112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.741962E+09 | 0.00 | 0.00 | 0.00 | 0.241494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.759802E+09 | 0.00 | 0.00 | 0.00 | 0.213418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.721746E+09 | 0.00 | 0.00 | 0.00 | 0.180012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.742890E+09 | 0.00 | 0.00 | 0.00 | 0.820926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.723809E+09 | 0.00 | 0.00 | 0.00 | 68560871.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.761333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.885396E+10 | 0.00 | 0.00 | 0.00 | 0.116459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.679223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.761333E+09 | 0.00 | 0.00 | 0.00 | 0.241494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.122857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109577E+10 | 0.00 | 0.00 | 0.00 | 34466360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122401E+10 | 0.00 | 0.00 | 0.00 | 0.137014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115414E+10 | 0.00 | 0.00 | 0.00 | 0.130332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120243E+10 | 0.00 | 0.00 | 0.00 | 0.275640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118082E+10 | 0.00 | 0.00 | 0.00 | 0.412482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119282E+10 | 0.00 | 0.00 | 0.00 | 0.455373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122011E+10 | 0.00 | 0.00 | 0.00 | 0.406316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115624E+10 | 0.00 | 0.00 | 0.00 | 0.344293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118969E+10 | 0.00 | 0.00 | 0.00 | 0.153035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116304E+10 | 0.00 | 0.00 | 0.00 | 0.116816E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142441E+11 | 0.00 | 0.00 | 0.00 | 0.220630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.123651E+10 | 0.00 | 0.00 | 0.00 | 0.455373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.662571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.590481E+09 | 0.00 | 0.00 | 0.00 | 14985226.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.659031E+09 | 0.00 | 0.00 | 0.00 | 63020198.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.620975E+09 | 0.00 | 0.00 | 0.00 | 0.653292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.646948E+09 | 0.00 | 0.00 | 0.00 | 0.139358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.635465E+09 | 0.00 | 0.00 | 0.00 | 0.208868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.641809E+09 | 0.00 | 0.00 | 0.00 | 0.230589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.656451E+09 | 0.00 | 0.00 | 0.00 | 0.205624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.621999E+09 | 0.00 | 0.00 | 0.00 | 0.174139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.640091E+09 | 0.00 | 0.00 | 0.00 | 0.770881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.625985E+09 | 0.00 | 0.00 | 0.00 | 56530012.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.666808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.766861E+10 | 0.00 | 0.00 | 0.00 | 0.111445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.590481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.666808E+09 | 0.00 | 0.00 | 0.00 | 0.230589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.661259E+09 | 0.00 | 0.00 | 0.00 | 33.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.588796E+09 | 0.00 | 0.00 | 0.00 | 13342014.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.656515E+09 | 0.00 | 0.00 | 0.00 | 58175928.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.617867E+09 | 0.00 | 0.00 | 0.00 | 0.640482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.643702E+09 | 0.00 | 0.00 | 0.00 | 0.138067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.632271E+09 | 0.00 | 0.00 | 0.00 | 0.207655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.638593E+09 | 0.00 | 0.00 | 0.00 | 0.229370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.653176E+09 | 0.00 | 0.00 | 0.00 | 0.204532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.618859E+09 | 0.00 | 0.00 | 0.00 | 0.173109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.636884E+09 | 0.00 | 0.00 | 0.00 | 0.761425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.623204E+09 | 0.00 | 0.00 | 0.00 | 53403683.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.665366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.763649E+10 | 0.00 | 0.00 | 0.00 | 0.110542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.588796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.665366E+09 | 0.00 | 0.00 | 0.00 | 0.229370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.668268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.593802E+09 | 0.00 | 0.00 | 0.00 | 9562773.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.659975E+09 | 0.00 | 0.00 | 0.00 | 47604673.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.618586E+09 | 0.00 | 0.00 | 0.00 | 0.611619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.644384E+09 | 0.00 | 0.00 | 0.00 | 0.135702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.632795E+09 | 0.00 | 0.00 | 0.00 | 0.206913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.639277E+09 | 0.00 | 0.00 | 0.00 | 0.229232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.653991E+09 | 0.00 | 0.00 | 0.00 | 0.204593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.619463E+09 | 0.00 | 0.00 | 0.00 | 0.172843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.637587E+09 | 0.00 | 0.00 | 0.00 | 0.743960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.625112E+09 | 0.00 | 0.00 | 0.00 | 47028159.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.672188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.766543E+10 | 0.00 | 0.00 | 0.00 | 0.109526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.593802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.672188E+09 | 0.00 | 0.00 | 0.00 | 0.229232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.780014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.691460E+09 | 0.00 | 0.00 | 0.00 | 6242879.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.764320E+09 | 0.00 | 0.00 | 0.00 | 39623698.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.708769E+09 | 0.00 | 0.00 | 0.00 | 0.654464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.737551E+09 | 0.00 | 0.00 | 0.00 | 0.150638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.724456E+09 | 0.00 | 0.00 | 0.00 | 0.234894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.733458E+09 | 0.00 | 0.00 | 0.00 | 0.262140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.750179E+09 | 0.00 | 0.00 | 0.00 | 0.236167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.708854E+09 | 0.00 | 0.00 | 0.00 | 0.199985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.729795E+09 | 0.00 | 0.00 | 0.00 | 0.822243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.718943E+09 | 0.00 | 0.00 | 0.00 | 46503804.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.781718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.882952E+10 | 0.00 | 0.00 | 0.00 | 0.124073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.691460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.781718E+09 | 0.00 | 0.00 | 0.00 | 0.262140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.553734E+10 | 0.00 | 0.00 | 222119.62 | 0.00 | 0.531088E+09 | 0.320108E+09 | 0.00 | 0.36 |
February | 0.383905E+10 | 0.00 | 0.00 | 1426319.18 | 0.00 | 0.257335E+09 | 0.119567E+10 | 0.00 | 0.46 |
March | 0.283971E+10 | 94023.94 | 0.00 | 3294006.97 | 0.00 | 0.145424E+09 | 0.257421E+10 | 0.00 | 0.57 |
April | 0.428645E+09 | 0.303855E+09 | 0.00 | 9979166.20 | 543163.30 | 0.00 | 0.284267E+10 | 0.00 | 0.69 |
May | 28700234.71 | 0.133528E+10 | 0.00 | 8014786.46 | 1541213.77 | 0.00 | 0.137586E+10 | 0.00 | 0.61 |
June | 1852864.48 | 0.290478E+10 | 0.00 | 1893700.88 | 0.00 | 0.00 | 0.164810E+09 | 0.00 | 0.45 |
July | 0.00 | 0.500764E+10 | 0.00 | 441288.63 | 4942401.26 | 0.00 | 29317935.32 | 0.00 | 0.41 |
August | 537944.64 | 0.320313E+10 | 0.00 | 2363362.01 | 486159.60 | 0.00 | 0.416570E+09 | 0.00 | 0.55 |
September | 3599076.18 | 0.227453E+10 | 0.00 | 8381815.32 | 17963.58 | 0.00 | 0.133567E+10 | 0.00 | 0.69 |
October | 0.144563E+09 | 0.527005E+09 | 0.00 | 15286796.63 | 0.00 | 0.00 | 0.522494E+10 | 0.00 | 0.91 |
November | 0.260744E+10 | 0.00 | 0.00 | 5586938.73 | 0.00 | 0.105375E+09 | 0.447994E+10 | 0.00 | 0.60 |
December | 0.606832E+10 | 0.00 | 0.00 | 5706.42 | 0.00 | 0.778845E+09 | 21351806.28 | 0.00 | 0.35 |
Annual Sum or Average | 0.214998E+11 | 0.155563E+11 | 0.00 | 56896007.05 | 7530901.51 | 0.181807E+10 | 0.199811E+11 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 5706.42 | 0.00 | 0.00 | 21351806.28 | 0.00 | 0.35 |
Maximum of Months | 0.606832E+10 | 0.500764E+10 | 0.00 | 15286796.63 | 4942401.26 | 0.778845E+09 | 0.522494E+10 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.207226E+10 | 0.00 | 0.00 | 426434.04 | 0.00 | 45916307.93 | 0.438256E+09 | 0.00 | 0.29 |
February | 0.137799E+10 | 0.00 | 0.00 | 1232022.67 | 0.00 | 21176064.33 | 0.101396E+10 | 0.00 | 0.45 |
March | 0.772949E+09 | 61731.50 | 0.00 | 2763657.60 | 0.00 | 16593205.03 | 0.208625E+10 | 0.00 | 0.62 |
April | 99900916.22 | 0.146065E+09 | 0.00 | 4606483.59 | 0.00 | 0.00 | 0.157222E+10 | 0.00 | 0.63 |
May | 7914254.06 | 0.634206E+09 | 0.00 | 3380126.92 | 238871.64 | 0.00 | 0.606496E+09 | 0.00 | 0.51 |
June | 0.00 | 0.132724E+10 | 0.00 | 758175.55 | 0.00 | 0.00 | 63767666.56 | 0.00 | 0.37 |
July | 0.00 | 0.232619E+10 | 0.00 | 11681.50 | 12536839.62 | 0.00 | 88550.72 | 0.00 | 0.35 |
August | 38673.51 | 0.150057E+10 | 0.00 | 936298.68 | 827639.84 | 0.00 | 0.178314E+09 | 0.00 | 0.47 |
September | 320952.18 | 0.116065E+10 | 0.00 | 2753565.84 | 0.00 | 0.00 | 0.503977E+09 | 0.00 | 0.55 |
October | 29396665.98 | 0.263292E+09 | 0.00 | 6817317.83 | 44282.70 | 0.00 | 0.265444E+10 | 0.00 | 0.86 |
November | 0.687420E+09 | 0.00 | 0.00 | 4015801.51 | 0.00 | 5646814.07 | 0.306352E+10 | 0.00 | 0.64 |
December | 0.224829E+10 | 0.00 | 0.00 | 188167.62 | 0.00 | 0.146627E+09 | 0.215681E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.729647E+10 | 0.735827E+10 | 0.00 | 27889733.34 | 13647633.79 | 0.235960E+09 | 0.123970E+11 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 11681.50 | 0.00 | 0.00 | 88550.72 | 0.00 | 0.27 |
Maximum of Months | 0.224829E+10 | 0.232619E+10 | 0.00 | 6817317.83 | 12536839.62 | 0.146627E+09 | 0.306352E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193569E+10 | 0.00 | 0.00 | 167063.38 | 0.00 | 0.146557E+09 | 0.203830E+09 | 0.00 | 0.27 |
February | 0.138753E+10 | 0.00 | 0.00 | 600000.65 | 0.00 | 63718666.47 | 0.495755E+09 | 0.00 | 0.38 |
March | 0.982352E+09 | 125065.55 | 0.00 | 1532530.06 | 0.00 | 27869715.79 | 0.110137E+10 | 0.00 | 0.50 |
April | 0.218345E+09 | 0.136827E+09 | 0.00 | 2088702.04 | 3543019.39 | 0.00 | 0.976948E+09 | 0.00 | 0.52 |
May | 32180272.71 | 0.556158E+09 | 0.00 | 1371908.59 | 20663227.87 | 0.00 | 0.473095E+09 | 0.00 | 0.46 |
June | 584590.88 | 0.114575E+10 | 0.00 | 734729.04 | 57352377.85 | 0.00 | 0.112880E+09 | 0.00 | 0.37 |
July | 199338.00 | 0.186967E+10 | 0.00 | 162184.71 | 0.116300E+09 | 0.00 | 6696625.72 | 0.00 | 0.33 |
August | 3291588.71 | 0.123299E+10 | 0.00 | 920818.01 | 60210025.35 | 0.00 | 0.211378E+09 | 0.00 | 0.46 |
September | 18150522.66 | 0.900598E+09 | 0.00 | 1256197.42 | 25047845.21 | 0.00 | 0.289962E+09 | 0.00 | 0.47 |
October | 0.133193E+09 | 0.207602E+09 | 0.00 | 4250689.67 | 8887409.37 | 0.00 | 0.173035E+10 | 0.00 | 0.68 |
November | 0.870023E+09 | 0.00 | 0.00 | 2453698.80 | 0.00 | 26136395.50 | 0.180498E+10 | 0.00 | 0.53 |
December | 0.205941E+10 | 0.00 | 0.00 | 33270.43 | 0.00 | 0.269396E+09 | 53548911.56 | 0.00 | 0.26 |
Annual Sum or Average | 0.764095E+10 | 0.604971E+10 | 0.00 | 15571792.78 | 0.292004E+09 | 0.533678E+09 | 0.746079E+10 | 0.00 | 0.44 |
Minimum of Months | 199338.00 | 0.00 | 0.00 | 33270.43 | 0.00 | 0.00 | 6696625.72 | 0.00 | 0.26 |
Maximum of Months | 0.205941E+10 | 0.186967E+10 | 0.00 | 4250689.67 | 0.116300E+09 | 0.269396E+09 | 0.180498E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.191200E+10 | 0.00 | 0.00 | 112654.56 | 0.00 | 0.185601E+09 | 0.149198E+09 | 0.00 | 0.27 |
February | 0.137796E+10 | 0.00 | 0.00 | 519894.72 | 0.00 | 80084466.35 | 0.446548E+09 | 0.00 | 0.37 |
March | 0.100361E+10 | 125828.94 | 0.00 | 1380633.03 | 0.00 | 36013460.90 | 0.101709E+10 | 0.00 | 0.49 |
April | 0.221545E+09 | 0.136821E+09 | 0.00 | 2054267.41 | 3568476.38 | 0.00 | 0.965448E+09 | 0.00 | 0.52 |
May | 32450432.42 | 0.557207E+09 | 0.00 | 1402068.07 | 20642699.74 | 0.00 | 0.477130E+09 | 0.00 | 0.47 |
June | 585741.31 | 0.114699E+10 | 0.00 | 760202.84 | 57091182.60 | 0.00 | 0.113454E+09 | 0.00 | 0.37 |
July | 201119.28 | 0.187441E+10 | 0.00 | 169222.24 | 0.117370E+09 | 0.00 | 6885564.28 | 0.00 | 0.33 |
August | 3315968.86 | 0.123560E+10 | 0.00 | 947593.38 | 60397039.91 | 0.00 | 0.212122E+09 | 0.00 | 0.46 |
September | 18150184.66 | 0.902696E+09 | 0.00 | 1276927.95 | 25263754.46 | 0.00 | 0.292596E+09 | 0.00 | 0.47 |
October | 0.136514E+09 | 0.207493E+09 | 0.00 | 4240256.42 | 8836400.63 | 0.00 | 0.172924E+10 | 0.00 | 0.68 |
November | 0.900264E+09 | 0.00 | 0.00 | 2319308.98 | 0.00 | 35089252.07 | 0.171214E+10 | 0.00 | 0.52 |
December | 0.200925E+10 | 0.00 | 0.00 | 18841.29 | 0.00 | 0.315671E+09 | 34044462.11 | 0.00 | 0.26 |
Annual Sum or Average | 0.761585E+10 | 0.606135E+10 | 0.00 | 15201870.91 | 0.293170E+09 | 0.652459E+09 | 0.715589E+10 | 0.00 | 0.43 |
Minimum of Months | 201119.28 | 0.00 | 0.00 | 18841.29 | 0.00 | 0.00 | 6885564.28 | 0.00 | 0.26 |
Maximum of Months | 0.200925E+10 | 0.187441E+10 | 0.00 | 4240256.42 | 0.117370E+09 | 0.315671E+09 | 0.172924E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.182412E+10 | 0.00 | 0.00 | 58635.01 | 0.00 | 0.282479E+09 | 87726065.03 | 0.00 | 0.26 |
February | 0.134987E+10 | 0.00 | 0.00 | 398855.90 | 0.00 | 0.105486E+09 | 0.372999E+09 | 0.00 | 0.36 |
March | 0.105126E+10 | 124080.10 | 0.00 | 1094199.85 | 0.00 | 49855922.60 | 0.839397E+09 | 0.00 | 0.46 |
April | 0.234514E+09 | 0.136664E+09 | 0.00 | 1844797.98 | 3696874.65 | 0.00 | 0.880063E+09 | 0.00 | 0.50 |
May | 41637761.89 | 0.554826E+09 | 0.00 | 1272029.26 | 20861664.57 | 0.00 | 0.442234E+09 | 0.00 | 0.46 |
June | 573989.07 | 0.114379E+10 | 0.00 | 699603.92 | 57954379.38 | 0.00 | 0.112578E+09 | 0.00 | 0.37 |
July | 0.00 | 0.186150E+10 | 0.00 | 159575.16 | 0.116436E+09 | 0.00 | 6718849.43 | 0.00 | 0.33 |
August | 3363638.61 | 0.122816E+10 | 0.00 | 904159.16 | 60090700.86 | 0.00 | 0.211028E+09 | 0.00 | 0.46 |
September | 18122961.57 | 0.895509E+09 | 0.00 | 1198251.60 | 24832702.98 | 0.00 | 0.283482E+09 | 0.00 | 0.46 |
October | 0.154880E+09 | 0.203676E+09 | 0.00 | 3992633.60 | 9218836.18 | 0.00 | 0.164077E+10 | 0.00 | 0.67 |
November | 0.947244E+09 | 0.00 | 0.00 | 2015842.06 | 0.00 | 63080852.76 | 0.150492E+10 | 0.00 | 0.49 |
December | 0.188439E+10 | 0.00 | 0.00 | 2315.10 | 0.00 | 0.435999E+09 | 6360818.47 | 0.00 | 0.26 |
Annual Sum or Average | 0.750998E+10 | 0.602425E+10 | 0.00 | 13640898.59 | 0.293091E+09 | 0.936900E+09 | 0.638828E+10 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2315.10 | 0.00 | 0.00 | 6360818.47 | 0.00 | 0.26 |
Maximum of Months | 0.188439E+10 | 0.186150E+10 | 0.00 | 3992633.60 | 0.116436E+09 | 0.435999E+09 | 0.164077E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.389531E+10 | 0.00 | 0.00 | 49710.68 | 0.00 | 0.576111E+09 | 96816630.86 | 0.00 | 0.27 |
February | 0.289880E+10 | 0.00 | 0.00 | 559672.68 | 0.00 | 0.187244E+09 | 0.627686E+09 | 0.00 | 0.34 |
March | 0.223732E+10 | 0.00 | 0.00 | 1636874.99 | 0.00 | 0.100974E+09 | 0.149269E+10 | 0.00 | 0.42 |
April | 0.350622E+09 | 0.181710E+09 | 0.00 | 4062457.50 | 3751690.14 | 0.00 | 0.159958E+10 | 0.00 | 0.45 |
May | 21072670.36 | 0.104794E+10 | 0.00 | 2360121.38 | 28951650.47 | 0.00 | 0.664398E+09 | 0.00 | 0.41 |
June | 0.00 | 0.238570E+10 | 0.00 | 622525.34 | 37234433.26 | 0.00 | 87509930.38 | 0.00 | 0.33 |
July | 0.00 | 0.379447E+10 | 0.00 | 118435.21 | 70938064.86 | 0.00 | 1948935.99 | 0.00 | 0.30 |
August | 22972.71 | 0.252771E+10 | 0.00 | 1082871.36 | 35875355.07 | 0.00 | 0.292293E+09 | 0.00 | 0.40 |
September | 15634756.76 | 0.186687E+10 | 0.00 | 2345476.07 | 19585633.76 | 0.00 | 0.400559E+09 | 0.00 | 0.42 |
October | 0.179639E+09 | 0.416701E+09 | 0.00 | 6957553.06 | 4880095.85 | 0.00 | 0.307191E+10 | 0.00 | 0.60 |
November | 0.208949E+10 | 0.00 | 0.00 | 3035382.25 | 0.00 | 0.126693E+09 | 0.256235E+10 | 0.00 | 0.44 |
December | 0.392986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.955369E+09 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.156178E+11 | 0.122211E+11 | 0.00 | 22831080.52 | 0.201217E+09 | 0.194639E+10 | 0.108977E+11 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.392986E+10 | 0.379447E+10 | 0.00 | 6957553.06 | 70938064.86 | 0.955369E+09 | 0.307191E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.185541E+10 | 0.00 | 0.00 | 13223.69 | 0.00 | 0.366988E+09 | 33390795.04 | 0.00 | 0.27 |
February | 0.142707E+10 | 0.00 | 0.00 | 235427.60 | 0.00 | 0.119662E+09 | 0.279237E+09 | 0.00 | 0.34 |
March | 0.114133E+10 | 0.00 | 0.00 | 719108.71 | 0.00 | 68030537.67 | 0.662498E+09 | 0.00 | 0.42 |
April | 0.191075E+09 | 96288362.91 | 0.00 | 1927517.59 | 2145507.08 | 0.00 | 0.771005E+09 | 0.00 | 0.45 |
May | 15905029.55 | 0.533135E+09 | 0.00 | 1156297.97 | 15149134.77 | 0.00 | 0.329629E+09 | 0.00 | 0.42 |
June | 0.00 | 0.120296E+10 | 0.00 | 306529.55 | 18228563.01 | 0.00 | 46178456.78 | 0.00 | 0.33 |
July | 0.00 | 0.189527E+10 | 0.00 | 56473.44 | 38223627.91 | 0.00 | 1008420.24 | 0.00 | 0.30 |
August | 99151.43 | 0.126803E+10 | 0.00 | 551431.62 | 17144877.40 | 0.00 | 0.154006E+09 | 0.00 | 0.41 |
September | 8095998.63 | 0.935264E+09 | 0.00 | 1184497.83 | 10783286.92 | 0.00 | 0.204817E+09 | 0.00 | 0.43 |
October | 0.100698E+09 | 0.208697E+09 | 0.00 | 3518458.04 | 2496530.09 | 0.00 | 0.154231E+10 | 0.00 | 0.61 |
November | 0.103405E+10 | 0.00 | 0.00 | 1443021.38 | 0.00 | 99999196.73 | 0.123117E+10 | 0.00 | 0.44 |
December | 0.184661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574852E+09 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.762035E+10 | 0.613964E+10 | 0.00 | 11111987.44 | 0.104172E+09 | 0.122953E+10 | 0.525525E+10 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.185541E+10 | 0.189527E+10 | 0.00 | 3518458.04 | 38223627.91 | 0.574852E+09 | 0.154231E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179230E+10 | 0.00 | 0.00 | 7499.45 | 0.00 | 0.427469E+09 | 23755249.20 | 0.00 | 0.27 |
February | 0.141829E+10 | 0.00 | 0.00 | 206508.46 | 0.00 | 0.143826E+09 | 0.245685E+09 | 0.00 | 0.33 |
March | 0.114242E+10 | 0.00 | 0.00 | 642014.71 | 0.00 | 89757884.44 | 0.603310E+09 | 0.00 | 0.41 |
April | 0.209532E+09 | 96176795.85 | 0.00 | 1837984.11 | 2185681.81 | 0.00 | 0.731054E+09 | 0.00 | 0.44 |
May | 18650561.24 | 0.532330E+09 | 0.00 | 1125687.68 | 15226126.84 | 0.00 | 0.321189E+09 | 0.00 | 0.41 |
June | 0.00 | 0.120189E+10 | 0.00 | 293001.83 | 18259751.42 | 0.00 | 45929478.80 | 0.00 | 0.33 |
July | 0.00 | 0.189076E+10 | 0.00 | 55557.86 | 38499599.18 | 0.00 | 994487.99 | 0.00 | 0.30 |
August | 113330.42 | 0.126537E+10 | 0.00 | 546456.61 | 17126074.60 | 0.00 | 0.153074E+09 | 0.00 | 0.41 |
September | 8362145.90 | 0.932525E+09 | 0.00 | 1166649.04 | 10832914.83 | 0.00 | 0.202305E+09 | 0.00 | 0.42 |
October | 0.107763E+09 | 0.207472E+09 | 0.00 | 3439932.47 | 2500834.09 | 0.00 | 0.151461E+10 | 0.00 | 0.61 |
November | 0.103909E+10 | 0.00 | 0.00 | 1337378.86 | 0.00 | 0.121620E+09 | 0.115961E+10 | 0.00 | 0.43 |
December | 0.180224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612794E+09 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.753875E+10 | 0.612653E+10 | 0.00 | 10658671.07 | 0.104631E+09 | 0.139547E+10 | 0.500152E+10 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.180224E+10 | 0.189076E+10 | 0.00 | 3439932.47 | 38499599.18 | 0.612794E+09 | 0.151461E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.158436E+10 | 0.00 | 0.00 | 185.40 | 0.00 | 0.634029E+09 | 3287502.57 | 0.00 | 0.27 |
February | 0.133811E+10 | 0.00 | 0.00 | 147074.62 | 0.00 | 0.235213E+09 | 0.192768E+09 | 0.00 | 0.32 |
March | 0.111681E+10 | 0.00 | 0.00 | 478147.75 | 0.00 | 0.148736E+09 | 0.486686E+09 | 0.00 | 0.39 |
April | 0.256360E+09 | 95930568.75 | 0.00 | 1623061.78 | 2329397.92 | 0.00 | 0.629739E+09 | 0.00 | 0.43 |
May | 22787683.95 | 0.531056E+09 | 0.00 | 1041437.15 | 15285666.54 | 0.00 | 0.302264E+09 | 0.00 | 0.41 |
June | 7165.18 | 0.119986E+10 | 0.00 | 261125.97 | 18288291.17 | 0.00 | 45701043.25 | 0.00 | 0.33 |
July | 0.00 | 0.188756E+10 | 0.00 | 52254.13 | 38138263.00 | 0.00 | 953677.83 | 0.00 | 0.30 |
August | 221435.24 | 0.126367E+10 | 0.00 | 544123.85 | 17466743.80 | 0.00 | 0.152005E+09 | 0.00 | 0.41 |
September | 8576518.29 | 0.930872E+09 | 0.00 | 1138928.93 | 10861211.36 | 0.00 | 0.197593E+09 | 0.00 | 0.42 |
October | 0.148044E+09 | 0.205655E+09 | 0.00 | 3258257.37 | 2496347.87 | 0.00 | 0.142485E+10 | 0.00 | 0.59 |
November | 0.105743E+10 | 0.00 | 0.00 | 1103951.12 | 0.00 | 0.165171E+09 | 0.100216E+10 | 0.00 | 0.41 |
December | 0.159156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808775E+09 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.712427E+10 | 0.611462E+10 | 0.00 | 9648548.08 | 0.104866E+09 | 0.199192E+10 | 0.443801E+10 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.159156E+10 | 0.188756E+10 | 0.00 | 3258257.37 | 38138263.00 | 0.808775E+09 | 0.142485E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105838E+10 | 0.00 | 0.00 | 0.27 |
February | 0.972729E+09 | 0.00 | 0.00 | 99396.05 | 0.00 | 0.592468E+09 | 0.155410E+09 | 0.00 | 0.32 |
March | 0.974189E+09 | 0.00 | 0.00 | 321443.66 | 0.00 | 0.324953E+09 | 0.356193E+09 | 0.00 | 0.38 |
April | 0.285697E+09 | 99863177.57 | 0.00 | 1576184.48 | 2354801.70 | 4395227.24 | 0.572744E+09 | 0.00 | 0.44 |
May | 19523645.73 | 0.549120E+09 | 0.00 | 1085586.85 | 15702475.33 | 0.00 | 0.302055E+09 | 0.00 | 0.43 |
June | 4093855.85 | 0.121401E+10 | 0.00 | 253653.00 | 18255664.32 | 0.00 | 48581496.71 | 0.00 | 0.34 |
July | 67934.95 | 0.191719E+10 | 0.00 | 91895.54 | 35707791.38 | 0.00 | 3282281.94 | 0.00 | 0.31 |
August | 1892238.43 | 0.129088E+10 | 0.00 | 636875.96 | 16610048.19 | 0.00 | 0.169759E+09 | 0.00 | 0.43 |
September | 8314710.29 | 0.954633E+09 | 0.00 | 1288424.46 | 9793403.83 | 0.00 | 0.219694E+09 | 0.00 | 0.45 |
October | 0.196148E+09 | 0.212614E+09 | 0.00 | 3419683.17 | 2363634.58 | 0.00 | 0.142104E+10 | 0.00 | 0.64 |
November | 0.101107E+10 | 0.00 | 0.00 | 1004411.27 | 0.00 | 0.278038E+09 | 0.885446E+09 | 0.00 | 0.42 |
December | 0.116286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120361E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.575653E+10 | 0.623832E+10 | 0.00 | 9777554.43 | 0.100788E+09 | 0.346184E+10 | 0.413420E+10 | 0.00 | 0.39 |
Minimum of Months | 67934.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.116286E+10 | 0.191719E+10 | 0.00 | 3419683.17 | 35707791.38 | 0.120361E+10 | 0.142104E+10 | 0.00 | 0.64 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:39:21
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.175169E+12 | 0.177962E+11 | 0.00 | 0.300587E+11 | 0.229509E+10 |
February | 0.187073E+12 | 0.130890E+11 | 0.00 | 0.246468E+11 | 0.245412E+10 |
March | 0.291543E+12 | 0.119180E+11 | 0.00 | 0.256665E+11 | 0.514670E+10 |
April | 0.319786E+12 | 0.372555E+10 | 0.00 | 0.126673E+11 | 0.428420E+11 |
May | 0.347134E+12 | -0.286712E+10 | 0.00 | -0.140135E+10 | 0.884140E+11 |
June | 0.347746E+12 | -0.865792E+10 | 0.00 | -0.143027E+11 | 0.128104E+12 |
July | 0.343616E+12 | -0.134074E+11 | 0.00 | -0.248650E+11 | 0.151394E+12 |
August | 0.312921E+12 | -0.861047E+10 | 0.00 | -0.141455E+11 | 0.134076E+12 |
September | 0.282573E+12 | -0.580260E+10 | 0.00 | -0.784147E+10 | 0.114889E+12 |
October | 0.244506E+12 | 0.402332E+10 | 0.00 | 0.206591E+11 | 0.519129E+11 |
November | 0.182002E+12 | 0.139673E+11 | 0.00 | 0.328866E+11 | 0.443191E+10 |
December | 0.141751E+12 | 0.185215E+11 | 0.00 | 0.320867E+11 | 0.308925E+10 |
Annual Sum or Average | 0.317582E+13 | 0.436954E+11 | 0.00 | 0.116116E+12 | 0.729048E+12 |
Minimum of Months | 0.141751E+12 | -0.134074E+11 | 0.00 | -0.248650E+11 | 0.229509E+10 |
Maximum of Months | 0.347746E+12 | 0.185215E+11 | 0.00 | 0.328866E+11 | 0.151394E+12 |