Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:39
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 08:39:24
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 906.75 | 433.79 | 433.79 |
Net Site Energy | 838.53 | 401.15 | 401.15 |
Total Source Energy | 2848.91 | 1362.91 | 1362.91 |
Net Source Energy | 2632.86 | 1259.55 | 1259.55 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 10.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 293.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 95.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 59.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 895.82 | 10.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 10.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 293.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 40.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 95.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 59.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 10.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 293.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 40.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 95.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 59.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 152.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 214.77 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 428.56 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 152.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 214.77 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 428.56 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 71.214 | 7.95 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -2.99 | -0.3 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 68.220 | 7.62 |
Electricity Coming From Utility | 827.599 | 92.38 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 827.599 | 92.38 |
Total On-Site and Utility Electric Sources | 895.819 | 100.00 |
Total Electricity End Uses | 895.819 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1670.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:39 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 11.5884 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 13.7658 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 7.5320 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 10.0873 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 10.0873 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 11.5884 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 13.7658 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 12.9393 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 12.9393 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 12.9393 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 7.5320 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 7.5557 | 6.19 | 4.3000 | |
Total | 2090.32 | 10.0873 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 10.0873 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 10.0873 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-SEP-14:39 | 05-FEB-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 79209.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 60619.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9807.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5413.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 101597.74 | 79209.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 79209.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 60619.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9807.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5413.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 11.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 929.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 879.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 129.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 302.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 189.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2837.06 | 11.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 5.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 444.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 420.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 144.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1357.24 | 5.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 5.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 444.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 420.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 144.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1357.24 | 5.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.01 |
SMSTORE1 DIRECT AIR | 1.05 |
SMSTORE2 DIRECT AIR | 1.06 |
SMSTORE3 DIRECT AIR | 1.07 |
SMSTORE4 DIRECT AIR | 1.06 |
LGSTORE2 DIRECT AIR | 1.89 |
SMSTORE5 DIRECT AIR | 0.994784 |
SMSTORE6 DIRECT AIR | 0.990594 |
SMSTORE7 DIRECT AIR | 0.994059 |
SMSTORE8 DIRECT AIR | 1.15 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.01 | 2.01 | 2.01 | 2.01 | 2.01 | 2.01 | 1.00 | 1.00 | 2.01 |
PSZ-AC_2:2 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
PSZ-AC_3:3 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
PSZ-AC_4:4 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.00 | 1.00 | 1.07 |
PSZ-AC_5:5 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
PSZ-AC_6:6 | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.00 | 1.00 | 1.89 |
PSZ-AC_7:7 | 0.994784 | 0.994784 | 0.994784 | 0.994784 | 0.994784 | 0.994784 | 1.00 | 1.00 | 0.994784 |
PSZ-AC_8:8 | 0.990594 | 0.990594 | 0.990594 | 0.990594 | 0.990594 | 0.990594 | 1.00 | 1.00 | 0.990594 |
PSZ-AC_9:9 | 0.994059 | 0.994059 | 0.994059 | 0.994059 | 0.994059 | 0.994059 | 1.00 | 1.00 | 0.994059 |
PSZ-AC_10:10 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.00 | 1.00 | 1.15 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.01 |
PSZ-AC_2:2_OA_CONTROLLER | 1.05 |
PSZ-AC_3:3_OA_CONTROLLER | 1.06 |
PSZ-AC_4:4_OA_CONTROLLER | 1.07 |
PSZ-AC_5:5_OA_CONTROLLER | 1.06 |
PSZ-AC_6:6_OA_CONTROLLER | 1.89 |
PSZ-AC_7:7_OA_CONTROLLER | 0.994784 |
PSZ-AC_8:8_OA_CONTROLLER | 0.990594 |
PSZ-AC_9:9_OA_CONTROLLER | 0.994059 |
PSZ-AC_10:10_OA_CONTROLLER | 1.15 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.01 | 2153.87 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1163.92 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1177.07 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1181.86 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1173.69 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.89 | 2027.30 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.994784 | 1101.38 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.990594 | 1096.74 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.994059 | 1100.58 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.15 | 1278.24 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.01 | 2.01 | 2.01 | 1.33 | 49984.34 | 54187.42 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 0.693836 | 26105.44 | 28117.67 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.701674 | 26400.37 | 28388.95 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 0.704528 | 26507.75 | 28487.72 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.699663 | 26324.71 | 28319.35 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.89 | 1.89 | 1.89 | 1.25 | 47047.14 | 51485.64 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.994784 | 0.994784 | 0.994784 | 0.656557 | 24702.85 | 26827.59 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.990594 | 0.990594 | 0.990594 | 0.653792 | 24598.81 | 26731.90 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.994059 | 0.994059 | 0.994059 | 0.656079 | 24684.85 | 26811.03 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 0.761988 | 28669.66 | 30476.45 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.01 | 1.01 | 1.34 | 49984.34 | 24992.17 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.05 | 0.525633 | 0.700847 | 26105.44 | 13052.72 | 0.701080 | 0.701080 |
PSZ-AC_3:3 COOLING COIL | 1.06 | 0.531571 | 0.708760 | 26400.37 | 13200.18 | 0.701080 | 0.701080 |
PSZ-AC_4:4 COOLING COIL | 1.07 | 0.533733 | 0.711647 | 26507.75 | 13253.88 | 0.701080 | 0.701080 |
PSZ-AC_5:5 COOLING COIL | 1.06 | 0.530048 | 0.706733 | 26324.71 | 13162.35 | 0.701080 | 0.701080 |
PSZ-AC_6:6 COOLING COIL | 1.89 | 0.947294 | 1.26 | 47047.14 | 23523.57 | 0.701080 | 0.701080 |
PSZ-AC_7:7 COOLING COIL | 0.994780 | 0.497392 | 0.663187 | 24702.85 | 12351.42 | 0.701080 | 0.701080 |
PSZ-AC_8:8 COOLING COIL | 0.990590 | 0.495297 | 0.660393 | 24598.81 | 12299.41 | 0.701080 | 0.701080 |
PSZ-AC_9:9 COOLING COIL | 0.994060 | 0.497029 | 0.662707 | 24684.85 | 12342.42 | 0.701080 | 0.701080 |
PSZ-AC_10:10 COOLING COIL | 1.15 | 0.577264 | 0.769687 | 28669.66 | 14334.83 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 54187.42 |
PSZ-AC_2:2 HEATING COIL | 28117.67 |
PSZ-AC_3:3 HEATING COIL | 28388.95 |
PSZ-AC_4:4 HEATING COIL | 28487.72 |
PSZ-AC_5:5 HEATING COIL | 28319.35 |
PSZ-AC_6:6 HEATING COIL | 51485.64 |
PSZ-AC_7:7 HEATING COIL | 26827.59 |
PSZ-AC_8:8 HEATING COIL | 26731.90 |
PSZ-AC_9:9 HEATING COIL | 26811.03 |
PSZ-AC_10:10 HEATING COIL | 30476.45 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 11.588 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.888 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 13.766 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 18.066 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 7.532 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.832 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 2630.745 | 7.551 | 46.768 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2630.745 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1406.513 | 4.037 | 25.004 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1406.513 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1319.493 | 7.575 | 46.916 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1319.493 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1078.411 | 6.191 | 38.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1078.411 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 2624.046 | 7.532 | 46.649 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2624.046 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7374 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.122 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.30765797E-12 | 0.12488460E-14 | -0.98016509E-13 | 0.16213517E-15 |
23 | 6 | 0.29136061E-07 | 0.20843390E-09 | 0.66705746E-08 | -0.13769473E-12 |
24 | 5 | -0.19246395E-03 | 0.17782628E-05 | -0.98963596E-04 | 0.65927994E-08 |
25 | 4 | 0.29490032 | 0.86304157E-03 | 0.10067388 | -0.33959898E-04 |
26 | 3 | -7.3208521 | 0.26669396E-01 | -2.3550924 | 0.29276239E-01 |
27 | 2 | 41.050957 | 0.94592451E-01 | 15.331444 | -0.33534308 |
28 | 1 | -80.683573 | 0.42595651E-01 | -29.201163 | 1.0815555 |
29 | 0 | 46.824338 | 0.85510937E-03 | 16.289814 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 35 | 1 | VerySmooth | 1.408 | 1.408 | 1.000 | 0.210 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 4.57814E-002 | 0.12126 | 0.67915 | 0.67915 | 0.29000 | 0.15345 | 0.21878 | 0.00000 | 0.84000 | 0.84000 | 8.56546E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 22827.72676 | 27393.27211 | 1.67739 | 2.01287 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65364E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 15575.82467 | 18690.98960 | 0.67201 | 0.80641 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11922.13489 | 14306.56187 | 0.87606 | 1.05127 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65364E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 7698.50307 | 9238.20369 | 0.33215 | 0.39857 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 12056.87424 | 14468.24909 | 0.88595 | 1.06314 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 7759.99322 | 9311.99186 | 0.33480 | 0.40176 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 12105.90966 | 14527.09159 | 0.88956 | 1.06747 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 7824.12742 | 9388.95290 | 0.33757 | 0.40508 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 12022.32513 | 14426.79015 | 0.88341 | 1.06010 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 7963.98265 | 9556.77918 | 0.34360 | 0.41232 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 21486.87825 | 25784.25390 | 1.57882 | 1.89459 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 14946.93083 | 17936.31700 | 0.64488 | 0.77385 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11281.68053 | 13538.01663 | 0.82899 | 0.99478 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 8145.89248 | 9775.07097 | 0.35145 | 0.42174 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11234.17029 | 13481.00435 | 0.82550 | 0.99059 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 8154.01202 | 9784.81442 | 0.35180 | 0.42216 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11273.46898 | 13528.16278 | 0.82838 | 0.99406 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 8404.70093 | 10085.64112 | 0.36261 | 0.43514 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 13095.57035 | 15714.68442 | 0.96211 | 1.15453 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 33.50500 | 1.65356E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 9955.91987 | 11947.10384 | 0.42953 | 0.51544 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 31953.35 | 2.01287 | 2.01287 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 26631.32 | 0.80641 | 0.80641 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16577.17 | 1.05127 | 1.05127 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 13209.86 | 0.39857 | 0.39857 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16736.02 | 1.06314 | 1.06314 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 13282.57 | 0.40176 | 0.40176 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16793.19 | 1.06747 | 1.06747 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 13358.41 | 0.40508 | 0.40508 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 16694.57 | 1.06010 | 1.06010 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 13523.80 | 0.41232 | 0.41232 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 30365.33 | 1.89459 | 1.89459 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 25887.69 | 0.77385 | 0.77385 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 15817.68 | 0.99478 | 0.99478 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 13738.91 | 0.42174 | 0.42174 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 15761.49 | 0.99059 | 0.99059 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 13748.51 | 0.42216 | 0.42216 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 15806.60 | 0.99406 | 0.99406 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 14044.96 | 0.43514 | 0.43514 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 17864.76 | 1.15453 | 1.15453 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 15879.25 | 0.51544 | 0.51544 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.01287 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05127 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06314 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06747 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06010 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.89459 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99478 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99059 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99406 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.15453 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.01287 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.01287 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.01287 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.01287 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.01287 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.01287 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05127 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05127 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05127 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05127 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05127 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05127 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06314 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06314 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06314 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06314 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06314 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06314 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06747 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06747 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06747 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06747 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06747 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06747 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06010 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06010 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06010 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06010 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06010 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06010 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.89459 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.89459 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.89459 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.89459 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.89459 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.89459 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99478 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99478 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99478 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99478 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99478 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.99478 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99059 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99059 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99059 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99059 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99059 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.99059 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99406 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99406 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99406 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99406 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99406 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.99406 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.15453 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.15453 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.15453 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.15453 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.15453 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.15453 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.01287 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.05127 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.06314 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.06747 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.06010 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.89459 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.99478 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.99059 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.99406 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.15453 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.01287 |
102 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.01287 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2153.86535 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.01287 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.01287 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.01287 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.32849 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.01287 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.00643 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.34191 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 49984.34000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 24992.17000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
115 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 49984.34000 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 54187.41511 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
119 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 54187.41511 |
120 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05127 |
121 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05127 |
122 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1163.91842 |
123 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05127 |
124 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05127 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05127 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69384 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05127 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52563 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70085 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26105.44000 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13052.72000 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26105.44000 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28117.67426 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
138 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 28117.67426 |
139 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06314 |
140 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06314 |
141 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1177.06802 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06314 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06314 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06314 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70167 |
146 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06314 |
147 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53157 |
148 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70876 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26400.37000 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13200.18500 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26400.37000 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28388.95411 |
155 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
157 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 28388.95411 |
158 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06747 |
159 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06747 |
160 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1181.85536 |
161 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06747 |
162 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06747 |
163 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06747 |
164 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70453 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06747 |
166 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53373 |
167 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71165 |
168 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26507.75000 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13253.87500 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
172 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26507.75000 |
173 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28487.71501 |
174 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
176 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 28487.71501 |
177 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06010 |
178 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06010 |
179 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1173.69446 |
180 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06010 |
181 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06010 |
182 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06010 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69966 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06010 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53005 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70673 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26324.71000 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13162.35500 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26324.71000 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28319.34875 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
194 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
195 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 28319.34875 |
196 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.89459 |
197 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.89459 |
198 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2027.29909 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.89459 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.89459 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.89459 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.25043 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.89459 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.94729 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.26306 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 47047.14000 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 23523.57000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 47047.14000 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 51485.64371 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
213 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
214 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 51485.64371 |
215 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99478 |
216 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.99478 |
217 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1101.38335 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99478 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99478 |
220 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99478 |
221 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65656 |
222 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.99478 |
223 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49739 |
224 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66319 |
225 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24702.85000 |
226 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12351.42500 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
229 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24702.85000 |
230 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26827.59282 |
231 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
232 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
233 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 26827.59282 |
234 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99059 |
235 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.99059 |
236 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1096.74486 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99059 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99059 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99059 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65379 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.99059 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49530 |
243 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66039 |
244 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24598.81000 |
245 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12299.40500 |
246 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
247 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24598.81000 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26731.89981 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
251 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
252 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 26731.89981 |
253 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99406 |
254 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.99406 |
255 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1100.58110 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99406 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99406 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99406 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65608 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.99406 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49703 |
262 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66271 |
263 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24684.85000 |
264 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12342.42500 |
265 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
266 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24684.85000 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26811.03202 |
269 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
270 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
271 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 26811.03202 |
272 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.15453 |
273 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.15453 |
274 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1278.24485 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.15453 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.15453 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.15453 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76199 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.15453 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57726 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76969 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28669.66000 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14334.83000 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28669.66000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30476.44605 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 30476.44605 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 48396.4 | 12.27 | 12.27 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 25276.1 | 12.46 | 12.46 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 25561.6 | 12.46 | 12.46 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 25665.6 | 12.46 | 12.46 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 25488.4 | 12.46 | 12.46 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 45552.5 | 12.27 | 12.27 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 23918.1 | 12.46 | 12.46 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 23817.3 | 12.46 | 12.46 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 23900.6 | 12.46 | 12.46 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 27758.8 | 12.46 | 12.46 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 1.3293412546E-002 | 4.9698267209E-002 | Pass | Pass | 3.7002150510E-002 | 9.5699518540E-002 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 2.0198294622E-002 | 8.4813083138E-002 | Pass | Pass | 3.8464824047E-002 | 9.8473874641E-002 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.3369436336E-002 | 0.1121876452 | Pass | Pass | 1.5176947829 | 12.4201907030 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.3256925464E-002 | 0.1117942700 | Pass | Pass | 1.4154202580 | 11.5555470866 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.1673179638E-002 | 0.1033598768 | Pass | Pass | 0.6889115989 | 6.7990272025 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 2.9141012474E-002 | 8.8646655280E-002 | Pass | Pass | 2.9491538964 | 26.3896665101 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 2.8943253341E-002 | 8.5467418698E-002 | Pass | Pass | 0.9187317026 | 9.8589946558 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 2.8499176809E-002 | 8.2690873347E-002 | Pass | Pass | 0.8682499576 | 9.1955332413 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 2.7315544824E-002 | 7.5205375161E-002 | Pass | Pass | 0.7164353070 | 7.2498314052 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 2.9863493102E-002 | 7.5321376996E-002 | Pass | Pass | 0.3941143663 | 3.8160282058 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3134.78 | -209.7 | 0.00 | -207.4 | 1538.86 | 4256.51 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 1.408 | 0.210 | 0.290 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 1.408 | 0.210 | 0.290 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 7.5512 | 348.39 | 2630.74 | LightsWired | LTG_SCH_BASE_LPD1 | 81.37 | 168.00 | 80.49 | 0.0000 | Y | 39.75 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 4.0372 | 348.39 | 1406.51 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 24.96 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 7.5749 | 174.19 | 1319.49 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 82.90 | 168.00 | 81.97 | 0.0000 | Y | 20.30 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 6.1909 | 174.19 | 1078.41 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 19.14 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 7.5320 | 348.39 | 2624.05 | LightsWired | LTG_SCH_BASE_LPD2 | 60.23 | 168.00 | 58.11 | 0.0000 | Y | 28.62 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 5.0436 | 4180.64 | 21085.58 | 277.79 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 437.57 | AstronomicalClock | - | 41.73 | 41.73 | 3.43 | |
EXTERIOR_LIGHTS_B | 1882.64 | AstronomicalClock | - | 83.73 | 62.73 | 22.17 | |
EXTERIOR_LIGHTS_C | 1466.47 | AstronomicalClock | - | 83.73 | 55.73 | 15.34 | |
Exterior Lighting Total | 3786.68 | 40.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 49984.34 | 35043.02 | 14941.32 | 0.70 | 3.92 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26105.44 | 18302.00 | 7803.44 | 0.70 | 3.99 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26400.37 | 18508.77 | 7891.60 | 0.70 | 3.99 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26507.75 | 18584.05 | 7923.70 | 0.70 | 3.99 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26324.71 | 18455.73 | 7868.98 | 0.70 | 3.99 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 47047.14 | 32983.81 | 14063.33 | 0.70 | 3.92 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24702.85 | 17318.67 | 7384.18 | 0.70 | 3.99 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24598.81 | 17245.73 | 7353.08 | 0.70 | 3.99 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24684.85 | 17306.05 | 7378.80 | 0.70 | 3.99 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28669.66 | 20099.73 | 8569.93 | 0.70 | 3.99 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 48396.4 | 12.27 | 12.27 | ||||
PSZ-AC_2:2 COOLING COIL | 25276.1 | 12.46 | 12.46 | ||||
PSZ-AC_3:3 COOLING COIL | 25561.6 | 12.46 | 12.46 | ||||
PSZ-AC_4:4 COOLING COIL | 25665.6 | 12.46 | 12.46 | ||||
PSZ-AC_5:5 COOLING COIL | 25488.4 | 12.46 | 12.46 | ||||
PSZ-AC_6:6 COOLING COIL | 45552.5 | 12.27 | 12.27 | ||||
PSZ-AC_7:7 COOLING COIL | 23918.1 | 12.46 | 12.46 | ||||
PSZ-AC_8:8 COOLING COIL | 23817.3 | 12.46 | 12.46 | ||||
PSZ-AC_9:9 COOLING COIL | 23900.6 | 12.46 | 12.46 | ||||
PSZ-AC_10:10 COOLING COIL | 27758.8 | 12.46 | 12.46 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 54187.42 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 28117.67 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 28388.95 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 28487.72 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 28319.35 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 51485.64 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 26827.59 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 26731.90 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 26811.03 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 30476.45 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.01 | 2153.87 | 1070.05 | 1.00 | 1.31 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1163.92 | 1107.16 | 1.00 | 1.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1177.07 | 1107.16 | 1.00 | 1.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1181.86 | 1107.16 | 1.00 | 1.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1173.69 | 1107.16 | 1.00 | 1.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.89 | 2027.30 | 1070.05 | 1.00 | 1.32 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1101.38 | 1107.16 | 1.00 | 1.40 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1096.74 | 1107.16 | 1.00 | 1.40 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1100.58 | 1107.16 | 1.00 | 1.40 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.15 | 1278.24 | 1107.16 | 1.00 | 1.37 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 22827.73 | 27393.27 | 78.63 | 1.677 | 2.013 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 23.89 | 23.88 | 0.01046 | 33.90 | 0.01654 | 0.411 | 0.00 |
SMSTORE1 | 11922.13 | 14306.56 | 82.13 | 0.876 | 1.051 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.88 | 0.01050 | 33.90 | 0.01654 | 0.206 | 0.00 |
SMSTORE2 | 12056.87 | 14468.25 | 83.06 | 0.886 | 1.063 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01049 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE3 | 12105.91 | 14527.09 | 83.40 | 0.890 | 1.067 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01048 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE4 | 12022.33 | 14426.79 | 82.82 | 0.883 | 1.060 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01049 | 33.83 | 0.01654 | 0.206 | 0.00 |
LGSTORE2 | 21486.88 | 25784.25 | 74.01 | 1.579 | 1.895 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01052 | 33.83 | 0.01654 | 0.411 | 0.00 |
SMSTORE5 | 11281.68 | 13538.02 | 77.72 | 0.829 | 0.995 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01059 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE6 | 11234.17 | 13481.00 | 77.39 | 0.825 | 0.991 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01060 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE7 | 11273.47 | 13528.16 | 77.66 | 0.828 | 0.994 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01059 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE8 | 13095.57 | 15714.68 | 90.21 | 0.962 | 1.155 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 23.89 | 23.88 | 0.01042 | 33.50 | 0.01654 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 15575.82 | 18690.99 | 53.65 | 0.672 | 0.806 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00702 | 4.60 | 0.00526 | 0.411 | 0.00 |
SMSTORE1 | 7698.50 | 9238.20 | 53.03 | 0.332 | 0.399 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00695 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE2 | 7759.99 | 9311.99 | 53.46 | 0.335 | 0.402 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00695 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE3 | 7824.13 | 9388.95 | 53.90 | 0.338 | 0.405 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00696 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE4 | 7963.98 | 9556.78 | 54.86 | 0.344 | 0.412 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00697 | 4.60 | 0.00526 | 0.206 | 0.00 |
LGSTORE2 | 14946.93 | 17936.32 | 51.48 | 0.645 | 0.774 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00703 | 4.60 | 0.00526 | 0.411 | 0.00 |
SMSTORE5 | 8145.89 | 9775.07 | 56.12 | 0.351 | 0.422 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00698 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE6 | 8154.01 | 9784.81 | 56.17 | 0.352 | 0.422 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00698 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE7 | 8404.70 | 10085.64 | 57.90 | 0.363 | 0.435 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00700 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE8 | 9955.92 | 11947.10 | 68.59 | 0.430 | 0.515 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00705 | 4.60 | 0.00526 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.01 | 2.01 | 0.81 | 0.81 | 2.0129 | 2.0129 | 2.0129 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.05 | 1.05 | 0.40 | 0.40 | 1.0513 | 1.0513 | 1.0513 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.06 | 1.06 | 0.40 | 0.40 | 1.0631 | 1.0631 | 1.0631 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.07 | 1.07 | 0.41 | 0.41 | 1.0675 | 1.0675 | 1.0675 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.06 | 1.06 | 0.41 | 0.41 | 1.0601 | 1.0601 | 1.0601 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.89 | 1.89 | 0.77 | 0.77 | 1.8946 | 1.8946 | 1.8946 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.99 | 0.99 | 0.42 | 0.42 | 0.9948 | 0.9948 | 0.9948 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 0.99 | 0.99 | 0.42 | 0.42 | 0.9906 | 0.9906 | 0.9906 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 0.99 | 0.99 | 0.44 | 0.44 | 0.9941 | 0.9941 | 0.9941 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.15 | 1.15 | 0.52 | 0.52 | 1.1545 | 1.1545 | 1.1545 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 49984.340 | 35043.021 | 2.012870 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24992.17 | 16373.40 | 1.341913 | 26.80 | 19.88 | 0.01170373 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 30.6637 | 23.88 | 0.01046197 | 56.4946 | 22827.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 54187.415 | 54187.415 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 54187.42 | 54187.42 | 2.012869 | 17.73 | 12.28 | 0.00666272 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 20.4425 | 21.11 | 0.00702389 | 45.1409 | 15575.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 26105.440 | 18302.002 | 1.051270 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 13052.72 | 8558.15 | 0.700847 | 26.74 | 19.85 | 0.01168445 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 29.3556 | 23.88 | 0.01050386 | 56.7176 | 11922.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 28117.674 | 28117.674 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28117.67 | 28117.67 | 1.051266 | 17.88 | 12.30 | 0.00661775 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.5705 | 21.11 | 0.00694882 | 44.6641 | 7698.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 26400.370 | 18508.771 | 1.063140 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 13200.18 | 8676.49 | 0.708760 | 26.72 | 19.82 | 0.01165687 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 29.0278 | 23.88 | 0.01048599 | 56.6227 | 12056.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 28388.954 | 28388.954 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28388.95 | 28388.95 | 1.063143 | 17.91 | 12.32 | 0.00662470 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.3518 | 21.11 | 0.00695285 | 44.6897 | 7759.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 26507.750 | 18584.053 | 1.067470 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 13253.88 | 8719.57 | 0.711647 | 26.71 | 19.81 | 0.01164705 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 28.9101 | 23.88 | 0.01047962 | 56.5889 | 12104.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 28487.715 | 28487.715 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28487.72 | 28487.72 | 1.067467 | 17.93 | 12.33 | 0.00662991 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.2734 | 21.11 | 0.00695765 | 44.7203 | 7824.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 26324.710 | 18455.728 | 1.060100 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 13162.35 | 8645.98 | 0.706733 | 26.72 | 19.83 | 0.01166405 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 29.1111 | 23.88 | 0.01049066 | 56.6475 | 12021.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 28319.349 | 28319.349 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28319.35 | 28319.35 | 1.060096 | 17.90 | 12.33 | 0.00663644 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.4074 | 21.11 | 0.00696859 | 44.7898 | 7963.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 47047.140 | 32983.809 | 1.894590 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23523.57 | 15252.35 | 1.263060 | 26.92 | 20.01 | 0.01182802 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 32.5781 | 23.88 | 0.01052147 | 56.8099 | 21483.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 51485.644 | 51485.644 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 51485.64 | 51485.64 | 1.894588 | 17.52 | 12.18 | 0.00664195 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 21.7187 | 21.11 | 0.00702616 | 45.1550 | 14946.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 24702.850 | 17318.674 | 0.994780 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 12351.42 | 7998.76 | 0.663187 | 26.85 | 19.99 | 0.01182360 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 31.0226 | 23.88 | 0.01059446 | 57.1985 | 11279.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 26827.593 | 26827.593 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 26827.59 | 26827.59 | 0.994784 | 17.69 | 12.23 | 0.00662372 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 20.6816 | 21.11 | 0.00698005 | 44.8627 | 8145.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 24598.810 | 17245.734 | 0.990590 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 12299.41 | 7957.59 | 0.660393 | 26.86 | 20.00 | 0.01183437 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 31.1538 | 23.88 | 0.01060148 | 57.2358 | 11231.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 26731.900 | 26731.900 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 26731.90 | 26731.90 | 0.990594 | 17.68 | 12.22 | 0.00662277 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 20.7691 | 21.11 | 0.00698075 | 44.8671 | 8154.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 24684.850 | 17306.055 | 0.994060 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 12342.42 | 7991.44 | 0.662707 | 26.85 | 19.99 | 0.01182573 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 31.0450 | 23.88 | 0.01059586 | 57.2059 | 11269.92 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 26811.032 | 26811.032 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 26811.03 | 26811.03 | 0.994059 | 17.69 | 12.24 | 0.00663808 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 20.6967 | 21.11 | 0.00699847 | 44.9798 | 8404.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 28669.660 | 20099.725 | 1.154530 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 14334.83 | 9531.99 | 0.769687 | 26.50 | 19.64 | 0.01150659 | 12.80 | 12.09 | 0.00850000 | 33.50 | 0.01653563 | 25.03 | 26.7300 | 23.88 | 0.01041608 | 56.2516 | 13095.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 30476.446 | 30476.446 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30476.45 | 30476.45 | 1.154527 | 18.17 | 12.53 | 0.00673070 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 17.8201 | 21.11 | 0.00705022 | 45.3095 | 9955.92 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 49984.340 | 35043.021 | 2.012870 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5967 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.012869 | 2.42181776 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 24992.17 | 16373.40 | 1.0000 | 1.61454570 | 1.341913 | 26.80 | 19.88 | 0.01170373 | 56779.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24992.17 | 33.90 | 0.01653638 | 25.13 | 0.41148071 | 30.6637 | 23.88 | 0.01046197 | 23.88 | 0.01046197 | 56.4946 | 22827.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 54187.415 | 54187.415 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.012869 | 2.42181776 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 54187.42 | 54187.42 | 1.0000 | 2.42181776 | 2.012869 | 17.73 | 12.28 | 0.00666272 | 34702.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54187.42 | 4.60 | 0.00525715 | 4.60 | 0.41148071 | 20.4425 | 21.11 | 0.00702389 | 21.11 | 0.00702389 | 45.1409 | 15575.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26105.440 | 18302.002 | 1.051270 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5608 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.051266 | 1.26484854 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 13052.72 | 8558.15 | 1.0000 | 0.84323551 | 0.700847 | 26.74 | 19.85 | 0.01168445 | 56671.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13052.72 | 33.90 | 0.01653638 | 25.13 | 0.20573751 | 29.3556 | 23.88 | 0.01050386 | 23.88 | 0.01050386 | 56.7176 | 11922.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28117.674 | 28117.674 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.051266 | 1.26484854 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28117.67 | 28117.67 | 1.0000 | 1.26484854 | 1.051266 | 17.88 | 12.30 | 0.00661775 | 34734.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28117.67 | 4.60 | 0.00525715 | 4.60 | 0.20573751 | 19.5705 | 21.11 | 0.00694882 | 21.11 | 0.00694882 | 44.6641 | 7698.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26400.370 | 18508.771 | 1.063140 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5095 | 1004.8586 | 1.2032 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.063143 | 1.27913842 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 13200.18 | 8676.49 | 1.0000 | 0.85275657 | 0.708760 | 26.72 | 19.82 | 0.01165687 | 56578.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13200.18 | 33.90 | 0.01653638 | 25.13 | 0.20573751 | 29.0278 | 23.88 | 0.01048599 | 23.88 | 0.01048599 | 56.6227 | 12056.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28388.954 | 28388.954 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.063143 | 1.27913842 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28388.95 | 28388.95 | 1.0000 | 1.27913842 | 1.063143 | 17.91 | 12.32 | 0.00662470 | 34788.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28388.95 | 4.60 | 0.00525715 | 4.60 | 0.20573751 | 19.3518 | 21.11 | 0.00695285 | 21.11 | 0.00695285 | 44.6897 | 7759.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26507.750 | 18584.053 | 1.067470 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4913 | 1004.8586 | 1.2032 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.067467 | 1.28434090 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 13253.88 | 8719.57 | 1.0000 | 0.85622971 | 0.711647 | 26.71 | 19.81 | 0.01164705 | 56545.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13253.88 | 33.90 | 0.01653638 | 25.13 | 0.20573751 | 28.9101 | 23.88 | 0.01047962 | 23.88 | 0.01047962 | 56.5889 | 12104.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28487.715 | 28487.715 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.067467 | 1.28434090 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28487.72 | 28487.72 | 1.0000 | 1.28434090 | 1.067467 | 17.93 | 12.33 | 0.00662991 | 34815.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28487.72 | 4.60 | 0.00525715 | 4.60 | 0.20573751 | 19.2734 | 21.11 | 0.00695765 | 21.11 | 0.00695765 | 44.7203 | 7824.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26324.710 | 18455.728 | 1.060100 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5229 | 1004.8586 | 1.2032 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.060096 | 1.27547232 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 13162.35 | 8645.98 | 1.0000 | 0.85031815 | 0.706733 | 26.72 | 19.83 | 0.01166405 | 56602.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13162.35 | 33.90 | 0.01653638 | 25.13 | 0.20573751 | 29.1111 | 23.88 | 0.01049066 | 23.88 | 0.01049066 | 56.6475 | 12021.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28319.349 | 28319.349 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.060096 | 1.27547232 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28319.35 | 28319.35 | 1.0000 | 1.27547232 | 1.060096 | 17.90 | 12.33 | 0.00663644 | 34809.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28319.35 | 4.60 | 0.00525715 | 4.60 | 0.20573751 | 19.4074 | 21.11 | 0.00696859 | 21.11 | 0.00696859 | 44.7898 | 7963.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 47047.140 | 32983.809 | 1.894590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.8277 | 1004.8586 | 1.2032 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.894588 | 2.27950598 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 23523.57 | 15252.35 | 1.0000 | 1.51967198 | 1.263060 | 26.92 | 20.01 | 0.01182802 | 57228.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23523.57 | 33.90 | 0.01653638 | 25.13 | 0.41148071 | 32.5781 | 23.88 | 0.01052147 | 23.88 | 0.01052147 | 56.8099 | 21483.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 51485.644 | 51485.644 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.894588 | 2.27950598 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 51485.64 | 51485.64 | 1.0000 | 2.27950598 | 1.894588 | 17.52 | 12.18 | 0.00664195 | 34435.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51485.64 | 4.60 | 0.00525715 | 4.60 | 0.41148071 | 21.7187 | 21.11 | 0.00702616 | 21.11 | 0.00702616 | 45.1550 | 14946.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24702.850 | 17318.674 | 0.994780 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.8195 | 1004.8586 | 1.2032 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.994784 | 1.19689069 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 12351.42 | 7998.76 | 1.0000 | 0.79792424 | 0.663187 | 26.85 | 19.99 | 0.01182360 | 57140.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12351.42 | 33.90 | 0.01653638 | 25.13 | 0.20573751 | 31.0226 | 23.88 | 0.01059446 | 23.88 | 0.01059446 | 57.1985 | 11279.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26827.593 | 26827.593 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.994784 | 1.19689069 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 26827.59 | 26827.59 | 1.0000 | 1.19689069 | 0.994784 | 17.69 | 12.23 | 0.00662372 | 34563.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26827.59 | 4.60 | 0.00525715 | 4.60 | 0.20573751 | 20.6816 | 21.11 | 0.00698005 | 21.11 | 0.00698005 | 44.8627 | 8145.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24598.810 | 17245.734 | 0.990590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.8395 | 1004.8586 | 1.2032 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.990594 | 1.19184997 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 12299.41 | 7957.59 | 1.0000 | 0.79456340 | 0.660393 | 26.86 | 20.00 | 0.01183437 | 57177.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12299.41 | 33.90 | 0.01653638 | 25.13 | 0.20573751 | 31.1538 | 23.88 | 0.01060148 | 23.88 | 0.01060148 | 57.2358 | 11231.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26731.900 | 26731.900 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.990594 | 1.19184997 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 26731.90 | 26731.90 | 1.0000 | 1.19184997 | 0.990594 | 17.68 | 12.22 | 0.00662277 | 34545.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26731.90 | 4.60 | 0.00525715 | 4.60 | 0.20573751 | 20.7691 | 21.11 | 0.00698075 | 21.11 | 0.00698075 | 44.8671 | 8154.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24684.850 | 17306.055 | 0.994060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.8234 | 1004.8586 | 1.2032 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.994059 | 1.19601888 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 12342.42 | 7991.44 | 1.0000 | 0.79734672 | 0.662707 | 26.85 | 19.99 | 0.01182573 | 57148.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12342.42 | 33.90 | 0.01653638 | 25.13 | 0.20573751 | 31.0450 | 23.88 | 0.01059586 | 23.88 | 0.01059586 | 57.2059 | 11269.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26811.032 | 26811.032 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.994059 | 1.19601888 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 26811.03 | 26811.03 | 1.0000 | 1.19601888 | 0.994059 | 17.69 | 12.24 | 0.00663808 | 34596.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26811.03 | 4.60 | 0.00525715 | 4.60 | 0.20573751 | 20.6967 | 21.11 | 0.00699847 | 21.11 | 0.00699847 | 44.9798 | 8404.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28669.660 | 20099.725 | 1.154530 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2302 | 1004.8586 | 1.2032 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.154527 | 1.38908888 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | Sensible | 14334.83 | 9531.99 | 1.0000 | 0.92606152 | 0.769687 | 26.50 | 19.64 | 0.01150659 | 55967.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14334.83 | 33.50 | 0.01653563 | 25.03 | 0.20573751 | 26.7300 | 23.88 | 0.01041608 | 23.88 | 0.01041608 | 56.2516 | 13095.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30476.446 | 30476.446 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.154527 | 1.38908888 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30476.45 | 30476.45 | 1.0000 | 1.38908888 | 1.154527 | 18.17 | 12.53 | 0.00673070 | 35314.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30476.45 | 4.60 | 0.00525715 | 4.60 | 0.20573751 | 17.8201 | 21.11 | 0.00705022 | 21.11 | 0.00705022 | 45.3095 | 9955.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 2.01 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 1.05 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 1.06 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 1.07 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 1.06 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 1.89 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 0.99 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 0.99 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 0.99 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 1.15 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
LGSTORE1 | LGSTORE1_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE1 | SMSTORE1_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE2 | SMSTORE2_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE3 | SMSTORE3_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE4 | SMSTORE4_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LGSTORE2 | LGSTORE2_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE5 | SMSTORE5_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE6 | SMSTORE6_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE7 | SMSTORE7_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE8 | SMSTORE8_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 4270.83 | 2002.83 | 954.17 |
SMSTORE1 | 4132.33 | 1645.67 | 728.17 |
SMSTORE2 | 3249.17 | 1619.33 | 878.83 |
SMSTORE3 | 3238.33 | 1639.17 | 872.67 |
SMSTORE4 | 3211.17 | 1771.17 | 956.00 |
LGSTORE2 | 2896.67 | 2054.33 | 1242.83 |
SMSTORE5 | 2863.17 | 2113.50 | 1269.17 |
SMSTORE6 | 2852.33 | 2154.17 | 1295.67 |
SMSTORE7 | 2835.50 | 2218.50 | 1328.67 |
SMSTORE8 | 2876.17 | 2014.50 | 1129.67 |
Facility | 4453.00 | 2951.50 | 1670.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.17 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.17 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.17 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.17 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.17 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.17 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.17 | 0.00 | 0.00 |
SMSTORE8 | 0.17 | 0.33 | 0.00 | 0.00 |
Facility | 0.17 | 0.50 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.674 | 0.345 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.623 | 0.384 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.688 | 0.504 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.685 | 0.504 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.676 | 0.504 | 0.000 | 0.000 |
LGSTORE2 | 24.78 | 56.25 | 1805.20 | 0.730 | 0.472 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.735 | 0.538 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.731 | 0.538 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.726 | 0.538 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.744 | 0.553 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.435 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.435 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.435 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.78 | 56.25 | 1805.20 | 0.459 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.459 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.459 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.459 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.459 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.212 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
LGSTORE2 | PSZ-AC_6:6 | 24.78 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.212 |
SMSTORE5 | PSZ-AC_7:7 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE6 | PSZ-AC_8:8 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE7 | PSZ-AC_9:9 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE8 | PSZ-AC_10:10 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
Total Facility | 120.98 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 1.274 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 6960685.20 | 0.00 | 6960685.20 | 3838649.30 | 10799334.51 | 7870781.79 | 3166.89 | 4635.69 | 957.41 | 11.54 |
SMSTORE1 | 3219223.51 | 0.00 | 3219223.51 | 2068521.06 | 5287744.57 | 3935374.10 | 4336.78 | 3408.92 | 1014.30 | 13.08 |
SMSTORE2 | 2705643.79 | 0.00 | 2705643.79 | 2094113.03 | 4799756.82 | 3701819.01 | 4331.37 | 3733.00 | 695.63 | 68.05 |
SMSTORE3 | 2693341.32 | 0.00 | 2693341.32 | 2094113.03 | 4787454.35 | 3701819.01 | 4332.67 | 3751.33 | 675.99 | 66.57 |
SMSTORE4 | 2654213.71 | 0.00 | 2654213.71 | 2094113.03 | 4748326.74 | 3701819.01 | 4338.26 | 3791.33 | 630.41 | 62.36 |
LGSTORE2 | 5236291.62 | 0.00 | 5236291.62 | 3717029.21 | 8953320.83 | 7907875.00 | 4714.04 | 3478.33 | 567.63 | 41.67 |
SMSTORE5 | 2632947.90 | 0.00 | 2632947.90 | 2101897.61 | 4734845.51 | 3953920.18 | 4713.54 | 3495.67 | 550.79 | 41.04 |
SMSTORE6 | 2619944.05 | 0.00 | 2619944.05 | 2101897.61 | 4721841.66 | 3953920.18 | 4714.57 | 3505.83 | 539.60 | 39.27 |
SMSTORE7 | 2598640.83 | 0.00 | 2598640.83 | 2101897.61 | 4700538.44 | 3953920.18 | 4717.57 | 3532.50 | 509.93 | 30.02 |
SMSTORE8 | 2658339.84 | 0.00 | 2658339.84 | 2340335.64 | 4998675.49 | 3953920.18 | 4720.67 | 3549.33 | 490.00 | 15.97 |
Total Facility | 33979271.78 | 0.00 | 33979271.78 | 24552567.14 | 58531838.91 | 46635168.64 | 4724.41 | 5171.78 | 1246.61 | 124.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.3308 | 0.0000 | 0.3308 | 0.1689 | 0.4997 | 0.2682 | 248.77 | 4635.69 | 955.54 |
SMSTORE1 | 0.1529 | 0.0000 | 0.1529 | 0.0942 | 0.2471 | 0.1341 | 1419.37 | 3408.92 | 1011.72 |
SMSTORE2 | 0.1687 | 0.0000 | 0.1687 | 0.1236 | 0.2923 | 0.1285 | 0.00 | 3732.17 | 662.83 |
SMSTORE3 | 0.1680 | 0.0000 | 0.1680 | 0.1236 | 0.2916 | 0.1285 | 0.00 | 3750.50 | 644.50 |
SMSTORE4 | 0.1658 | 0.0000 | 0.1658 | 0.1236 | 0.2894 | 0.1285 | 0.00 | 3790.67 | 604.33 |
LGSTORE2 | 0.3581 | 0.0000 | 0.3581 | 0.2310 | 0.5891 | 0.2958 | 0.00 | 3478.33 | 551.67 |
SMSTORE5 | 0.1801 | 0.0000 | 0.1801 | 0.1317 | 0.3118 | 0.1479 | 0.00 | 3495.17 | 534.83 |
SMSTORE6 | 0.1793 | 0.0000 | 0.1793 | 0.1317 | 0.3110 | 0.1479 | 0.00 | 3505.67 | 524.33 |
SMSTORE7 | 0.1780 | 0.0000 | 0.1780 | 0.1317 | 0.3097 | 0.1479 | 0.00 | 3532.33 | 497.67 |
SMSTORE8 | 0.1823 | 0.0000 | 0.1823 | 0.1354 | 0.3178 | 0.1479 | 0.00 | 3549.33 | 480.67 |
Total Facility | 2.0640 | 0.0000 | 2.0640 | 1.3954 | 3.4594 | 1.6752 | 1527.87 | 5168.86 | 1216.31 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 10076357.56 | 0.00 | 10076357.56 | 7870781.79 | 3160.89 | 0.17 | 5598.94 | 11.37 |
PSZ-AC_2:2 | 4660190.11 | 0.00 | 4660190.11 | 3935374.10 | 4239.15 | 8.25 | 4512.60 | 13.08 |
PSZ-AC_3:3 | 3916716.09 | 0.00 | 3916716.09 | 3701819.01 | 4323.37 | 0.33 | 4436.30 | 67.71 |
PSZ-AC_4:4 | 3898906.39 | 0.00 | 3898906.39 | 3701819.01 | 4324.84 | 0.50 | 4434.66 | 66.41 |
PSZ-AC_5:5 | 3842263.71 | 0.00 | 3842263.71 | 3701819.01 | 4329.17 | 0.33 | 4430.49 | 62.19 |
PSZ-AC_6:6 | 7580108.68 | 0.00 | 7580108.68 | 7907875.00 | 4709.71 | 0.50 | 4049.79 | 41.67 |
PSZ-AC_7:7 | 3811481.35 | 0.00 | 3811481.35 | 3953920.18 | 4709.96 | 0.17 | 4049.88 | 41.04 |
PSZ-AC_8:8 | 3792655.18 | 0.00 | 3792655.18 | 3953920.18 | 4711.32 | 0.00 | 4048.68 | 39.27 |
PSZ-AC_9:9 | 3761810.61 | 0.00 | 3761810.61 | 3953920.18 | 4713.57 | 0.42 | 4046.02 | 30.02 |
PSZ-AC_10:10 | 3848222.55 | 0.00 | 3848222.55 | 3953920.18 | 4718.50 | 0.33 | 4041.16 | 15.64 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.4789 | 0.0000 | 0.4789 | 0.2682 | 243.77 | 0.17 | 5596.06 |
PSZ-AC_2:2 | 0.2214 | 0.0000 | 0.2214 | 0.1341 | 1323.74 | 7.92 | 4508.35 |
PSZ-AC_3:3 | 0.2442 | 0.0000 | 0.2442 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2432 | 0.0000 | 0.2432 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2401 | 0.0000 | 0.2401 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5184 | 0.0000 | 0.5184 | 0.2958 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2607 | 0.0000 | 0.2607 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2595 | 0.0000 | 0.2595 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2577 | 0.0000 | 0.2577 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2640 | 0.0000 | 0.2640 | 0.1479 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 330.71 | 716.20 | 0.00 | 0.00 | 0.00 | 4578.36 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 329.63 | 882.39 | 0.00 | 0.00 | 0.00 | 4326.19 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 293.26 | 468.87 | 0.00 | 0.00 | 0.00 | 3700.58 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 285.60 | 457.89 | 0.00 | 0.00 | 0.00 | 3717.92 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 274.26 | 428.93 | 0.00 | 0.00 | 0.00 | 3754.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 281.71 | 340.29 | 0.00 | 0.00 | 0.00 | 3449.67 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 267.54 | 337.83 | 0.00 | 0.00 | 0.00 | 3465.67 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 264.10 | 328.67 | 0.00 | 0.00 | 0.00 | 3476.50 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 254.49 | 301.36 | 0.00 | 0.00 | 0.00 | 3504.17 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 229.39 | 290.92 | 0.00 | 0.00 | 0.00 | 3525.33 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.4455 | 0.7553 | 0.0000 | 0.0000 | 0.0000 | 0.3905 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.7351 | 0.3521 | 0.0000 | 0.0000 | 0.0000 | 0.1722 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.7623 | 0.4091 | 0.0000 | 0.0000 | 0.0000 | 0.1858 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.7663 | 0.4123 | 0.0000 | 0.0000 | 0.0000 | 0.1858 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.7610 | 0.4117 | 0.0000 | 0.0000 | 0.0000 | 0.1858 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 1.3584 | 0.7817 | 0.0000 | 0.0000 | 0.0000 | 0.4278 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.7137 | 0.4033 | 0.0000 | 0.0000 | 0.0000 | 0.2140 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.7103 | 0.4000 | 0.0000 | 0.0000 | 0.0000 | 0.2139 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.7142 | 0.4015 | 0.0000 | 0.0000 | 0.0000 | 0.2138 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.8279 | 0.4430 | 0.0000 | 0.0000 | 0.0000 | 0.2136 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 835 |
Defaulted Fields | 817 |
Fields with Defaults | 2693 |
Autosized Fields | 174 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 895.82 | 2102.83 | 01-JAN-07:30 | 101597.74 | 10-SEP-14:40 |
Electricity:Building | 405.94 | 891.83 | 01-JAN-00:20 | 25756.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 90.96 | 148.64 | 01-JAN-00:20 | 4765.21 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 405.94 | 891.83 | 01-JAN-00:20 | 25756.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 64.71 | 75.00 | 01-JAN-00:20 | 3421.96 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 64.71 | 75.00 | 01-JAN-00:20 | 3421.96 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 52.56 | 74.32 | 01-JAN-00:20 | 2762.01 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 39.44 | 37.50 | 01-JAN-00:20 | 2090.38 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 39.44 | 37.50 | 01-JAN-00:20 | 2090.38 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 47.80 | 148.64 | 01-JAN-00:10 | 3421.36 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 28.62 | 75.00 | 01-JAN-00:10 | 2078.11 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 28.62 | 75.00 | 01-JAN-00:10 | 2078.11 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityProduced:Facility | 68.22 | -0.00 | 16-DEC-07:20 | 10852.00 | 10-APR-12:30 |
ElectricityProduced:Plant | 68.22 | -0.00 | 16-DEC-07:20 | 10852.00 | 10-APR-12:30 |
Photovoltaic:ElectricityProduced | 71.21 | 0.00 | 01-JAN-00:10 | 11299.94 | 10-APR-12:30 |
PowerConversion:ElectricityProduced | -2.99 | -447.94 | 10-APR-12:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 59.84 | 1211.00 | 05-JAN-08:10 | 11639.76 | 01-JAN-08:30 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 827.60 | 244.62 | 11-JUN-07:00 | 94731.60 | 10-SEP-14:40 |
ElectricityPurchased:Plant | 827.60 | 244.62 | 11-JUN-07:00 | 94731.60 | 10-SEP-14:40 |
Cogeneration:ElectricityPurchased | 827.60 | 244.62 | 11-JUN-07:00 | 94731.60 | 10-SEP-14:40 |
General:Cogeneration:ElectricityPurchased | 827.60 | 244.62 | 11-JUN-07:00 | 94731.60 | 10-SEP-14:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 827.60 | 244.62 | 11-JUN-07:00 | 94731.60 | 10-SEP-14:40 |
ElectricityNet:Plant | 827.60 | 244.62 | 11-JUN-07:00 | 94731.60 | 10-SEP-14:40 |
Cogeneration:ElectricityNet | 827.60 | 244.62 | 11-JUN-07:00 | 94731.60 | 10-SEP-14:40 |
General:Cogeneration:ElectricityNet | 827.60 | 244.62 | 11-JUN-07:00 | 94731.60 | 10-SEP-14:40 |
Electricity:HVAC | 389.10 | 0.00 | 01-JAN-00:10 | 71161.00 | 10-SEP-14:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 293.53 | 0.00 | 01-JAN-00:10 | 61241.62 | 10-SEP-14:10 |
General:Cooling:Electricity | 293.53 | 0.00 | 01-JAN-00:10 | 61241.62 | 10-SEP-14:10 |
Fans:Electricity | 95.57 | 0.00 | 01-JAN-00:10 | 9982.40 | 10-SEP-13:00 |
General:Fans:Electricity | 95.57 | 0.00 | 01-JAN-00:10 | 9982.40 | 10-SEP-13:00 |
ExteriorLights:Electricity | 40.93 | 0.00 | 01-JAN-07:30 | 3786.68 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 40.93 | 0.00 | 01-JAN-07:30 | 3786.68 | 01-JAN-06:10 |
WaterSystems:Electricity | 59.84 | 1211.00 | 05-JAN-08:10 | 11639.76 | 01-JAN-08:30 |
Water Heater:WaterSystems:Electricity | 59.84 | 1211.00 | 05-JAN-08:10 | 11639.76 | 01-JAN-08:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 10.93 | 0.00 | 01-JAN-00:10 | 79209.54 | 05-FEB-09:10 |
NaturalGas:HVAC | 10.93 | 0.00 | 01-JAN-00:10 | 79209.54 | 05-FEB-09:10 |
Heating:NaturalGas | 10.93 | 0.00 | 01-JAN-00:10 | 79209.54 | 05-FEB-09:10 |
General:Heating:NaturalGas | 10.93 | 0.00 | 01-JAN-00:10 | 79209.54 | 05-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1928.04 | 0.00 | 01-JAN-00:10 | 362181.08 | 10-SEP-13:00 |
EnergyTransfer:Building | 676.16 | 0.00 | 01-JAN-00:10 | 110538.17 | 10-SEP-14:10 |
EnergyTransfer:Zone:LGSTORE1 | 138.32 | 0.00 | 01-JAN-00:10 | 18122.48 | 10-SEP-15:00 |
Heating:EnergyTransfer | 7.93 | 0.00 | 01-JAN-00:10 | 54791.97 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.88 | 0.00 | 01-JAN-00:10 | 13809.51 | 05-FEB-08:10 |
General:Heating:EnergyTransfer | 7.93 | 0.00 | 01-JAN-00:10 | 54791.97 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.88 | 0.00 | 01-JAN-00:10 | 13809.51 | 05-FEB-08:10 |
Cooling:EnergyTransfer | 668.24 | 0.00 | 01-JAN-00:10 | 110538.17 | 10-SEP-14:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 137.43 | 0.00 | 01-JAN-00:10 | 18122.48 | 10-SEP-15:00 |
General:Cooling:EnergyTransfer | 668.24 | 0.00 | 01-JAN-00:10 | 110538.17 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 137.43 | 0.00 | 01-JAN-00:10 | 18122.48 | 10-SEP-15:00 |
EnergyTransfer:Zone:SMSTORE1 | 73.42 | 0.00 | 01-JAN-00:10 | 9332.56 | 10-SEP-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.30 | 0.00 | 01-JAN-00:10 | 2778.43 | 05-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.30 | 0.00 | 01-JAN-00:10 | 2778.43 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 73.12 | 0.00 | 01-JAN-00:10 | 9332.56 | 10-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 73.12 | 0.00 | 01-JAN-00:10 | 9332.56 | 10-SEP-13:00 |
EnergyTransfer:Zone:SMSTORE2 | 56.42 | 0.00 | 01-JAN-00:10 | 9242.15 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 0.66 | 0.00 | 01-JAN-00:10 | 3918.61 | 05-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 0.66 | 0.00 | 01-JAN-00:10 | 3918.61 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 55.76 | 0.00 | 01-JAN-00:10 | 9242.15 | 10-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 55.76 | 0.00 | 01-JAN-00:10 | 9242.15 | 10-SEP-14:00 |
EnergyTransfer:Zone:SMSTORE3 | 56.36 | 0.00 | 01-JAN-00:10 | 9291.97 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 0.68 | 0.00 | 01-JAN-00:10 | 4396.39 | 05-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 0.68 | 0.00 | 01-JAN-00:10 | 4396.39 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 55.68 | 0.00 | 01-JAN-00:10 | 9291.97 | 10-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 55.68 | 0.00 | 01-JAN-00:10 | 9291.97 | 10-SEP-14:00 |
EnergyTransfer:Zone:SMSTORE4 | 54.58 | 0.00 | 01-JAN-00:10 | 9207.70 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 0.74 | 0.00 | 01-JAN-00:10 | 4931.56 | 05-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 0.74 | 0.00 | 01-JAN-00:10 | 4931.56 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 53.84 | 0.00 | 01-JAN-00:10 | 9207.70 | 10-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 53.84 | 0.00 | 01-JAN-00:10 | 9207.70 | 10-SEP-14:00 |
EnergyTransfer:Zone:LGSTORE2 | 95.68 | 0.00 | 01-JAN-00:10 | 17320.33 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.11 | 0.00 | 01-JAN-00:10 | 11458.75 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 1.11 | 0.00 | 01-JAN-00:10 | 11458.75 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 94.57 | 0.00 | 01-JAN-00:10 | 17320.33 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 94.57 | 0.00 | 01-JAN-00:10 | 17320.33 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE5 | 49.43 | 0.00 | 01-JAN-00:10 | 9217.79 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.65 | 0.00 | 01-JAN-00:10 | 6135.50 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 0.65 | 0.00 | 01-JAN-00:10 | 6135.50 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 48.78 | 0.00 | 01-JAN-00:10 | 9217.79 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 48.78 | 0.00 | 01-JAN-00:10 | 9217.79 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 48.92 | 0.00 | 01-JAN-00:10 | 9191.49 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.69 | 0.00 | 01-JAN-00:10 | 6325.00 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 0.69 | 0.00 | 01-JAN-00:10 | 6325.00 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 48.23 | 0.00 | 01-JAN-00:10 | 9191.49 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 48.23 | 0.00 | 01-JAN-00:10 | 9191.49 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 48.24 | 0.00 | 01-JAN-00:10 | 9285.09 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.81 | 0.00 | 01-JAN-00:10 | 7245.62 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 0.81 | 0.00 | 01-JAN-00:10 | 7245.62 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 47.42 | 0.00 | 01-JAN-00:10 | 9285.09 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 47.42 | 0.00 | 01-JAN-00:10 | 9285.09 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 54.79 | 0.00 | 01-JAN-00:10 | 12152.38 | 05-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 1.40 | 0.00 | 01-JAN-00:10 | 12152.38 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 1.40 | 0.00 | 01-JAN-00:10 | 12152.38 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 53.39 | 0.00 | 01-JAN-00:10 | 10949.22 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 53.39 | 0.00 | 01-JAN-00:10 | 10949.22 | 10-SEP-14:10 |
EnergyTransfer:HVAC | 1251.88 | 0.00 | 01-JAN-00:10 | 254181.82 | 10-SEP-13:00 |
HeatingCoils:EnergyTransfer | 8.75 | 0.00 | 01-JAN-00:10 | 63367.64 | 05-FEB-09:10 |
CoolingCoils:EnergyTransfer | 1243.14 | 0.00 | 01-JAN-00:10 | 254181.82 | 10-SEP-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.884 | -137.433 | 0.000 | 0.000 | 23.539 | 64.707 | 26.249 | 16.018 | 0.000 | 14.174 | 5.204 | 0.000 | -2.720 | 0.000 | -10.622 | -0.000 |
SMSTORE1 | 0.000 | 0.000 | 0.303 | -73.122 | 0.000 | 0.000 | 11.713 | 39.440 | 13.125 | 7.998 | 0.000 | 7.954 | 0.000 | 0.000 | -1.401 | 0.000 | -5.536 | -0.472 |
SMSTORE2 | 0.000 | 0.000 | 0.660 | -55.763 | 0.000 | 0.000 | 7.064 | 28.854 | 10.421 | 7.950 | 0.000 | 7.825 | 0.136 | 0.000 | -1.472 | 0.000 | -5.675 | -0.000 |
SMSTORE3 | 0.000 | 0.000 | 0.682 | -55.679 | 0.000 | 0.000 | 7.069 | 28.854 | 10.421 | 7.953 | 0.000 | 7.823 | 0.001 | 0.000 | -1.467 | 0.000 | -5.643 | -0.012 |
SMSTORE4 | 0.000 | 0.000 | 0.738 | -53.841 | 0.000 | 0.000 | 7.079 | 28.854 | 10.421 | 7.963 | 0.000 | 7.827 | 0.000 | 0.000 | -1.444 | 0.000 | -5.571 | -2.026 |
LGSTORE2 | 0.000 | 0.000 | 1.111 | -94.566 | 0.000 | 0.000 | 24.335 | 28.624 | 19.173 | 15.909 | 0.000 | 13.740 | 4.298 | 0.000 | -2.791 | 0.000 | -9.833 | -0.001 |
SMSTORE5 | 0.000 | 0.000 | 0.650 | -48.779 | 0.000 | 0.000 | 12.178 | 14.614 | 9.586 | 7.951 | 0.000 | 7.836 | 2.794 | 0.000 | -1.381 | 0.000 | -5.449 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 0.685 | -48.232 | 0.000 | 0.000 | 12.184 | 14.614 | 9.586 | 7.956 | 0.000 | 7.837 | 2.164 | 0.000 | -1.372 | 0.000 | -5.422 | -0.000 |
SMSTORE7 | 0.000 | 0.000 | 0.814 | -47.424 | 0.000 | 0.000 | 12.199 | 14.614 | 9.586 | 7.964 | 0.000 | 7.838 | 1.118 | 0.000 | -1.355 | 0.000 | -5.354 | -0.000 |
SMSTORE8 | 0.000 | 0.000 | 1.400 | -53.385 | 0.000 | 0.000 | 12.212 | 14.614 | 9.586 | 7.951 | 0.000 | 8.043 | 7.346 | 0.000 | -1.307 | 0.000 | -6.459 | -0.000 |
Total Facility | 0.000 | 0.000 | 7.926 | -668.225 | 0.000 | 0.000 | 129.570 | 277.790 | 128.154 | 95.612 | 0.000 | 90.897 | 23.061 | 0.000 | -16.709 | 0.000 | -65.565 | -2.513 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -44117.51 | 0.00 | 0.00 | 176.93 | 75.00 | 74.62 | 0.00 | 0.00 | 0.00 | 43995.72 | 0.00 | -21.10 | 0.00 | -183.65 | 0.00 |
SMSTORE1 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -23369.57 | 0.00 | 0.00 | 87.84 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 23314.49 | 0.00 | -10.86 | 0.00 | -96.72 | 0.00 |
SMSTORE2 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | -22556.19 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 22561.91 | 0.00 | -66.39 | 0.00 | -13.65 | 0.00 |
SMSTORE3 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | -22666.57 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 22672.69 | 0.00 | -66.69 | 0.00 | -13.75 | 0.00 |
SMSTORE4 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | -22392.95 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 22397.48 | 0.00 | -65.65 | 0.00 | -13.20 | 0.00 |
LGSTORE2 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -41195.99 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 41240.02 | 0.00 | -19.48 | 0.00 | -173.19 | 0.00 |
SMSTORE5 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -21509.09 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 21537.48 | 0.00 | -8.96 | 0.00 | -93.75 | 0.00 |
SMSTORE6 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -21400.98 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 21428.56 | 0.00 | -8.70 | 0.00 | -93.19 | 0.00 |
SMSTORE7 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -21386.77 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 21412.70 | 0.00 | -8.61 | 0.00 | -91.63 | 0.00 |
SMSTORE8 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -21219.25 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 21257.73 | 0.00 | -8.99 | 0.00 | -103.82 | 0.00 |
Total Facility | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -200317.31 | 0.00 | 0.00 | 560.28 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 199051.14 | 0.00 | -96.71 | 0.00 | -1099.63 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-FEB-08:61 | 0.00 | 0.00 | 54466.09 | 0.00 | 0.00 | 0.00 | 248.78 | 75.00 | 74.62 | 283.29 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1243.19 | -53904.59 |
SMSTORE1 | 21-DEC-08:61 | 0.00 | 0.00 | 17326.71 | 0.00 | 0.00 | 0.00 | 118.73 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -146.06 | 0.00 | -775.90 | -16598.29 |
SMSTORE2 | 05-FEB-08:61 | 0.00 | 0.00 | 23560.79 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 101.75 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1151.94 | -22585.42 |
SMSTORE3 | 05-FEB-08:61 | 0.00 | 0.00 | 26994.31 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 103.67 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1151.50 | -26021.28 |
SMSTORE4 | 05-FEB-08:61 | 0.00 | 0.00 | 28091.30 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 105.67 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1145.17 | -27126.61 |
LGSTORE2 | 06-FEB-08:61 | 0.00 | 0.00 | 51839.78 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 282.84 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1190.36 | -51080.90 |
SMSTORE5 | 06-FEB-08:61 | 0.00 | 0.00 | 27017.02 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 141.51 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -675.57 | -26557.28 |
SMSTORE6 | 06-FEB-08:61 | 0.00 | 0.00 | 26922.96 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 142.75 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -671.44 | -26468.60 |
SMSTORE7 | 06-FEB-08:61 | 0.00 | 0.00 | 27003.60 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 147.57 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -653.81 | -26571.68 |
SMSTORE8 | 06-FEB-08:61 | 0.00 | 0.00 | 30562.20 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 165.29 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -637.31 | -30164.50 |
Total Facility | 06-FEB-08:61 | 0.00 | 0.00 | 238324.32 | 0.00 | 0.00 | 0.00 | 713.84 | 450.00 | 1452.23 | 1685.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7923.42 | -234702.73 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0129 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0129 | 0.2044 | 1.0000 | Not calculated | 0.4115 | 0.2044 | ||
PSZ-AC_2:2 | 1.0513 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0513 | 0.1957 | 1.0000 | Not calculated | 0.2057 | 0.1957 | ||
PSZ-AC_3:3 | 1.0631 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0631 | 0.1935 | 1.0000 | Not calculated | 0.2057 | 0.1935 | ||
PSZ-AC_4:4 | 1.0675 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0675 | 0.1927 | 1.0000 | Not calculated | 0.2057 | 0.1927 | ||
PSZ-AC_5:5 | 1.0601 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0601 | 0.1941 | 1.0000 | Not calculated | 0.2057 | 0.1941 | ||
PSZ-AC_6:6 | 1.8946 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8946 | 0.2172 | 1.0000 | Not calculated | 0.4115 | 0.2172 | ||
PSZ-AC_7:7 | 0.9948 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9948 | 0.2068 | 1.0000 | Not calculated | 0.2057 | 0.2068 | ||
PSZ-AC_8:8 | 0.9906 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9906 | 0.2077 | 1.0000 | Not calculated | 0.2057 | 0.2077 | ||
PSZ-AC_9:9 | 0.9941 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9941 | 0.2070 | 1.0000 | Not calculated | 0.2057 | 0.2070 | ||
PSZ-AC_10:10 | 1.1545 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1545 | 0.1782 | 1.0000 | Not calculated | 0.2057 | 0.1782 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0129 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0129 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2044 | ||
PSZ-AC_2:2 | 1.0513 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0513 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1957 | ||
PSZ-AC_3:3 | 1.0631 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0631 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1935 | ||
PSZ-AC_4:4 | 1.0675 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0675 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1927 | ||
PSZ-AC_5:5 | 1.0601 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0601 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1941 | ||
PSZ-AC_6:6 | 1.8946 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8946 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2172 | ||
PSZ-AC_7:7 | 0.9948 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9948 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2068 | ||
PSZ-AC_8:8 | 0.9906 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9906 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2077 | ||
PSZ-AC_9:9 | 0.9941 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9941 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2070 | ||
PSZ-AC_10:10 | 1.1545 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1545 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1782 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.003540 | 56.2505 | 0.000610 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.003540 | 56.2505 | 0.000610 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.003540 | 56.25 | 0.000610 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.003540 | 56.25 | 0.000610 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0129 | 2.0129 | 2.0129 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0513 | 1.0513 | 1.0513 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0631 | 1.0631 | 1.0631 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0675 | 1.0675 | 1.0675 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0601 | 1.0601 | 1.0601 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8946 | 1.8946 | 1.8946 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9948 | 0.9948 | 0.9948 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9906 | 0.9906 | 0.9906 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9941 | 0.9941 | 0.9941 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1545 | 1.1545 | 1.1545 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0129 | 2.0129 | 2.0129 | 2.0129 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0513 | 1.0513 | 1.0513 | 1.0513 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0631 | 1.0631 | 1.0631 | 1.0631 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0675 | 1.0675 | 1.0675 | 1.0675 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0601 | 1.0601 | 1.0601 | 1.0601 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8946 | 1.8946 | 1.8946 | 1.8946 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9948 | 0.9948 | 0.9948 | 0.9948 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9906 | 0.9906 | 0.9906 | 0.9906 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9941 | 0.9941 | 0.9941 | 0.9941 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.1545 | 1.1545 | 1.1545 | 1.1545 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0129 | 2.0129 | 2.0129 | No | 0.4115 | 0.5103 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0513 | 1.0513 | 1.0513 | No | 0.2057 | 0.5162 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0631 | 1.0631 | 1.0631 | No | 0.2057 | 0.5121 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0675 | 1.0675 | 1.0675 | No | 0.2057 | 0.5079 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0601 | 1.0601 | 1.0601 | No | 0.2057 | 0.4990 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8946 | 1.8946 | 1.8946 | No | 0.4115 | 0.5317 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9948 | 0.9948 | 0.9948 | No | 0.2057 | 0.4878 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9906 | 0.9906 | 0.9906 | No | 0.2057 | 0.4873 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9941 | 0.9941 | 0.9941 | No | 0.2057 | 0.4728 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1545 | 1.1545 | 1.1545 | No | 0.2057 | 0.3991 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0129 | 2.0129 | 2.0129 | 2.0129 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0513 | 1.0513 | 1.0513 | 1.0513 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0631 | 1.0631 | 1.0631 | 1.0631 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0675 | 1.0675 | 1.0675 | 1.0675 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0601 | 1.0601 | 1.0601 | 1.0601 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8946 | 1.8946 | 1.8946 | 1.8946 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9948 | 0.9948 | 0.9948 | 0.9948 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9906 | 0.9906 | 0.9906 | 0.9906 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9941 | 0.9941 | 0.9941 | 0.9941 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.1545 | 1.1545 | 1.1545 | 1.1545 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 10.93 | 79209.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 293.53 | 61241.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 277.79 | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 40.93 | 3786.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 95.57 | 9982.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 59.84 | 11639.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 895.82 |
Natural Gas | 0.00 | 10.93 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 906.75 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 71.21 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 132.89 |
Space Heating | 0.00 |
Space Cooling | 140.43 |
Fans (All) | 45.72 |
Service Water Heating | 28.63 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 428.56 |
Subtotal | 428.56 |
Natural Gas [MJ/m2] | |
Space Heating | 5.23 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 5.23 |
Subtotal | 5.23 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 30.64 |
Space Heating | 1.21 |
Space Cooling | 32.37 |
Fans (All) | 10.54 |
Service Water Heating | 6.60 |
Receptacle Equipment | 14.13 |
Miscellaneous | 4.51 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3140. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3200. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4323. | 8760. |
LTG_SCH_BASE_LPD1 | 4243. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3479. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8418.50 | 341.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8375.50 | 384.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8431.17 | 328.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8478.50 | 281.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8494.50 | 265.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8501.17 | 258.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8505.00 | 255.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8402.67 | 357.33 | 0.00 | 0.00 | 0.00 |
Min | 8375.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 384.50 | 0.00 | 0.00 | 0.00 |
Average | 8512.12 | 247.88 | 0.00 | 0.00 | 0.00 |
Sum | 85121.17 | 2478.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25431.00 | 44.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25430.50 | 44.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25434.50 | 40.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93061.00 | 150.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45838.00 | 74.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45839.00 | 73.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45839.00 | 73.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45826.00 | 86.00 | 0.00 | 0.00 | 0.00 |
Min | 25430.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93061.00 | 150.00 | 0.00 | 0.00 | 0.00 |
Average | 48551.70 | 58.50 | 0.00 | 0.00 | 0.00 |
Sum | 485517.00 | 585.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 6028.33 | 2731.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 7412.00 | 1348.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 4928.67 | 3831.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 4952.50 | 3807.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 4889.50 | 3870.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 4633.50 | 4126.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 4641.00 | 4119.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 4628.50 | 4131.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 4629.33 | 4130.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 4875.33 | 3884.67 | 0.00 | 0.00 | 0.00 |
Min | 4628.50 | 1348.00 | 0.00 | 0.00 | 0.00 |
Max | 7412.00 | 4131.50 | 0.00 | 0.00 | 0.00 |
Average | 5161.87 | 3598.13 | 0.00 | 0.00 | 0.00 |
Sum | 51618.67 | 35981.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 71996.33 | 17044.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 35557.17 | 8219.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 19102.67 | 6372.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 19170.50 | 6304.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 18753.33 | 6721.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 59925.83 | 33285.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 29155.33 | 16756.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 28968.00 | 16944.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 28716.33 | 17195.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 32005.00 | 13907.00 | 0.00 | 0.00 | 0.00 |
Min | 18753.33 | 6304.50 | 0.00 | 0.00 | 0.00 |
Max | 71996.33 | 33285.17 | 0.00 | 0.00 | 0.00 |
Average | 34335.05 | 14275.15 | 0.00 | 0.00 | 0.00 |
Sum | 343350.50 | 142751.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:24
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.560029E+10 | 10793.82 | 01-JAN-14:00 | 26.00 | 17.88 | 0.128821E+10 | 1685.94 | 29-JAN-18:30 | 19.50 | 15.49 |
February | 0.546631E+10 | 10330.60 | 24-FEB-14:00 | 27.20 | 21.39 | 0.120201E+10 | 1685.92 | 20-FEB-18:30 | 27.20 | 21.39 |
March | 0.644802E+10 | 11069.77 | 26-MAR-14:00 | 30.00 | 19.88 | 0.133897E+10 | 1685.90 | 04-MAR-13:00 | 30.00 | 19.88 |
April | 0.926328E+10 | 22490.05 | 29-APR-07:03 | 24.08 | 22.45 | 0.136058E+10 | 1686.02 | 22-APR-12:00 | 24.08 | 22.45 |
May | 0.147007E+11 | 31336.07 | 30-MAY-07:02 | 26.28 | 23.33 | 0.140162E+10 | 1686.02 | 19-MAY-12:00 | 26.28 | 23.33 |
June | 0.155073E+11 | 33298.92 | 26-JUN-07:02 | 25.68 | 23.94 | 0.135466E+10 | 1686.04 | 25-JUN-12:39 | 25.68 | 23.94 |
July | 0.164763E+11 | 32331.10 | 09-JUL-07:02 | 28.48 | 25.79 | 0.141289E+10 | 1686.03 | 02-JUL-12:09 | 28.48 | 25.79 |
August | 0.173014E+11 | 35314.38 | 31-AUG-07:02 | 25.45 | 23.81 | 0.139420E+10 | 1686.05 | 27-AUG-12:30 | 25.45 | 23.81 |
September | 0.153777E+11 | 31567.43 | 02-SEP-07:02 | 25.97 | 24.31 | 0.136531E+10 | 1686.03 | 09-SEP-12:30 | 31.35 | 24.36 |
October | 0.150933E+11 | 44143.98 | 26-OCT-07:02 | 21.83 | 13.09 | 0.140959E+10 | 1686.07 | 13-OCT-12:50 | 21.83 | 13.09 |
November | 0.914420E+10 | 30170.82 | 03-NOV-07:03 | 21.47 | 21.47 | 0.135883E+10 | 1686.01 | 11-NOV-13:39 | 26.27 | 22.81 |
December | 0.705566E+10 | 25087.64 | 17-DEC-08:62 | 19.83 | 15.88 | 0.135083E+10 | 1686.01 | 10-DEC-13:00 | 19.83 | 15.88 |
Annual Sum or Average | 0.137435E+12 | 0.162377E+11 | ||||||||
Minimum of Months | 0.546631E+10 | 10330.60 | 19.83 | 13.09 | 0.120201E+10 | 1685.90 | 19.50 | 13.09 | ||
Maximum of Months | 0.173014E+11 | 44143.98 | 30.00 | 25.79 | 0.141289E+10 | 1686.07 | 31.35 | 25.79 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.283722E+10 | 13605.85 | 29-JAN-19:06 | 19.00 | 15.30 | 0.667862E+09 | 842.94 | 15-JAN-13:09 | 19.00 | 15.30 |
February | 0.299824E+10 | 11447.58 | 20-FEB-18:23 | 19.65 | 17.65 | 0.613478E+09 | 843.17 | 26-FEB-18:19 | 22.37 | 18.99 |
March | 0.364403E+10 | 15257.54 | 04-MAR-19:08 | 21.42 | 13.84 | 0.679927E+09 | 843.12 | 05-MAR-18:40 | 22.00 | 17.99 |
April | 0.523303E+10 | 15321.01 | 16-APR-17:08 | 19.30 | 13.54 | 0.680210E+09 | 843.13 | 23-APR-17:30 | 26.35 | 21.51 |
May | 0.790152E+10 | 19169.60 | 30-MAY-07:02 | 26.28 | 23.33 | 0.700799E+09 | 843.03 | 14-MAY-17:19 | 26.28 | 23.33 |
June | 0.819252E+10 | 19837.19 | 26-JUN-07:02 | 25.68 | 23.94 | 0.677320E+09 | 843.00 | 16-JUN-12:39 | 25.68 | 23.94 |
July | 0.864360E+10 | 18935.95 | 09-JUL-07:02 | 28.48 | 25.79 | 0.706434E+09 | 843.00 | 16-JUL-16:10 | 31.32 | 25.35 |
August | 0.889178E+10 | 19784.17 | 31-AUG-07:02 | 25.45 | 23.81 | 0.697082E+09 | 843.00 | 26-AUG-12:00 | 25.45 | 23.81 |
September | 0.798563E+10 | 19288.25 | 01-SEP-07:02 | 25.97 | 23.81 | 0.682613E+09 | 843.00 | 09-SEP-12:30 | 31.35 | 24.36 |
October | 0.788301E+10 | 23381.08 | 26-OCT-07:02 | 21.83 | 13.09 | 0.704506E+09 | 843.01 | 09-OCT-12:00 | 21.83 | 13.09 |
November | 0.506185E+10 | 16766.26 | 02-NOV-07:03 | 22.98 | 22.50 | 0.680170E+09 | 842.98 | 11-NOV-13:30 | 26.35 | 22.79 |
December | 0.384995E+10 | 15426.61 | 17-DEC-08:62 | 19.83 | 15.88 | 0.685050E+09 | 842.99 | 10-DEC-13:39 | 19.83 | 15.88 |
Annual Sum or Average | 0.731224E+11 | 0.817545E+10 | ||||||||
Minimum of Months | 0.283722E+10 | 11447.58 | 19.00 | 13.09 | 0.613478E+09 | 842.94 | 19.00 | 13.09 | ||
Maximum of Months | 0.889178E+10 | 23381.08 | 28.48 | 25.79 | 0.706434E+09 | 843.17 | 31.35 | 25.35 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207583E+10 | 8532.99 | 02-JAN-07:03 | 15.83 | 15.23 | 0.387911E+09 | 842.93 | 28-JAN-13:00 | 22.00 | 13.62 |
February | 0.216418E+10 | 7798.07 | 28-FEB-07:03 | 18.90 | 18.08 | 0.362978E+09 | 842.90 | 25-FEB-13:09 | 18.90 | 18.08 |
March | 0.263591E+10 | 7811.26 | 30-MAR-06:03 | 20.50 | 19.29 | 0.414718E+09 | 842.93 | 04-MAR-13:00 | 20.50 | 19.29 |
April | 0.380928E+10 | 14295.27 | 29-APR-06:03 | 22.88 | 21.73 | 0.410146E+09 | 842.99 | 15-APR-12:00 | 22.88 | 21.73 |
May | 0.615829E+10 | 16993.06 | 12-MAY-06:02 | 23.40 | 20.68 | 0.426134E+09 | 842.96 | 27-MAY-12:50 | 27.62 | 23.50 |
June | 0.647181E+10 | 17564.21 | 14-JUN-06:02 | 25.28 | 22.79 | 0.417074E+09 | 842.97 | 17-JUN-12:39 | 28.90 | 25.09 |
July | 0.669825E+10 | 16070.24 | 19-JUL-06:02 | 26.88 | 24.44 | 0.420213E+09 | 842.99 | 08-JUL-12:09 | 26.88 | 24.44 |
August | 0.705723E+10 | 17927.18 | 31-AUG-06:02 | 24.00 | 23.17 | 0.431793E+09 | 843.00 | 26-AUG-12:00 | 24.00 | 23.17 |
September | 0.615683E+10 | 16575.36 | 23-SEP-06:02 | 22.28 | 20.36 | 0.410931E+09 | 843.00 | 09-SEP-12:30 | 22.28 | 20.36 |
October | 0.605977E+10 | 22574.13 | 26-OCT-06:02 | 22.00 | 13.53 | 0.420376E+09 | 842.98 | 14-OCT-12:20 | 22.00 | 13.53 |
November | 0.370189E+10 | 16308.91 | 08-NOV-07:03 | 19.50 | 18.38 | 0.404686E+09 | 842.94 | 25-NOV-13:39 | 20.17 | 14.26 |
December | 0.277499E+10 | 16303.88 | 17-DEC-08:62 | 19.83 | 15.88 | 0.399087E+09 | 842.98 | 16-DEC-13:09 | 19.83 | 15.88 |
Annual Sum or Average | 0.557643E+11 | 0.490605E+10 | ||||||||
Minimum of Months | 0.207583E+10 | 7798.07 | 15.83 | 13.53 | 0.362978E+09 | 842.90 | 18.90 | 13.53 | ||
Maximum of Months | 0.705723E+10 | 22574.13 | 26.88 | 24.44 | 0.431793E+09 | 843.00 | 28.90 | 25.09 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199788E+10 | 8515.47 | 02-JAN-07:03 | 15.83 | 15.23 | 0.385783E+09 | 842.93 | 28-JAN-13:00 | 22.00 | 13.62 |
February | 0.209307E+10 | 7612.18 | 28-FEB-07:03 | 18.90 | 18.08 | 0.361992E+09 | 842.90 | 25-FEB-13:09 | 18.90 | 18.08 |
March | 0.257546E+10 | 7701.71 | 30-MAR-06:03 | 20.50 | 19.29 | 0.414073E+09 | 842.93 | 04-MAR-13:00 | 20.50 | 19.29 |
April | 0.378526E+10 | 14351.89 | 29-APR-06:03 | 22.88 | 21.73 | 0.410116E+09 | 842.99 | 15-APR-12:00 | 22.88 | 21.73 |
May | 0.618812E+10 | 17089.38 | 12-MAY-06:02 | 23.40 | 20.68 | 0.426135E+09 | 842.96 | 27-MAY-12:50 | 27.62 | 23.50 |
June | 0.651074E+10 | 17673.85 | 14-JUN-06:02 | 25.28 | 22.79 | 0.417076E+09 | 842.97 | 17-JUN-12:39 | 28.90 | 25.09 |
July | 0.675094E+10 | 16170.79 | 19-JUL-06:02 | 26.88 | 24.44 | 0.420217E+09 | 842.99 | 08-JUL-12:09 | 26.88 | 24.44 |
August | 0.710353E+10 | 18034.77 | 31-AUG-06:02 | 24.00 | 23.17 | 0.431796E+09 | 843.00 | 26-AUG-12:00 | 24.00 | 23.17 |
September | 0.619936E+10 | 16663.00 | 23-SEP-06:02 | 22.28 | 20.36 | 0.410934E+09 | 842.99 | 09-SEP-12:30 | 22.28 | 20.36 |
October | 0.609098E+10 | 22684.66 | 26-OCT-06:02 | 22.00 | 13.53 | 0.420377E+09 | 842.98 | 14-OCT-12:20 | 22.00 | 13.53 |
November | 0.366833E+10 | 16384.18 | 08-NOV-07:03 | 19.50 | 18.38 | 0.404608E+09 | 842.94 | 25-NOV-13:39 | 20.17 | 14.26 |
December | 0.271675E+10 | 16391.55 | 17-DEC-08:62 | 19.83 | 15.88 | 0.398225E+09 | 842.98 | 16-DEC-13:09 | 19.83 | 15.88 |
Annual Sum or Average | 0.556804E+11 | 0.490133E+10 | ||||||||
Minimum of Months | 0.199788E+10 | 7612.18 | 15.83 | 13.53 | 0.361992E+09 | 842.90 | 18.90 | 13.53 | ||
Maximum of Months | 0.710353E+10 | 22684.66 | 26.88 | 24.44 | 0.431796E+09 | 843.00 | 28.90 | 25.09 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184934E+10 | 7570.58 | 02-JAN-07:03 | 15.83 | 15.23 | 0.381913E+09 | 842.92 | 28-JAN-13:00 | 22.00 | 13.62 |
February | 0.193553E+10 | 6388.26 | 28-FEB-07:03 | 18.90 | 18.08 | 0.359944E+09 | 842.90 | 25-FEB-13:09 | 18.90 | 18.08 |
March | 0.239872E+10 | 6418.61 | 30-MAR-06:03 | 20.50 | 19.29 | 0.412399E+09 | 842.93 | 04-MAR-13:00 | 20.50 | 19.29 |
April | 0.360464E+10 | 13949.58 | 30-APR-07:03 | 21.50 | 20.38 | 0.409997E+09 | 842.99 | 15-APR-12:30 | 21.50 | 20.38 |
May | 0.603687E+10 | 16866.68 | 12-MAY-06:02 | 23.40 | 20.68 | 0.426105E+09 | 842.97 | 27-MAY-12:50 | 27.62 | 23.50 |
June | 0.636845E+10 | 17423.40 | 14-JUN-06:02 | 25.28 | 22.79 | 0.417047E+09 | 842.96 | 17-JUN-12:39 | 28.90 | 25.09 |
July | 0.661557E+10 | 15913.94 | 19-JUL-06:02 | 26.88 | 24.44 | 0.420189E+09 | 842.98 | 08-JUL-12:09 | 26.88 | 24.44 |
August | 0.696432E+10 | 17796.14 | 31-AUG-06:02 | 24.00 | 23.17 | 0.431767E+09 | 842.99 | 26-AUG-12:00 | 24.00 | 23.17 |
September | 0.606862E+10 | 16448.38 | 23-SEP-06:02 | 22.28 | 20.36 | 0.410906E+09 | 842.99 | 09-SEP-12:30 | 22.28 | 20.36 |
October | 0.594940E+10 | 22410.81 | 26-OCT-06:02 | 22.00 | 13.53 | 0.420335E+09 | 842.97 | 14-OCT-12:20 | 22.00 | 13.53 |
November | 0.349689E+10 | 15497.36 | 08-NOV-07:03 | 19.50 | 18.38 | 0.404319E+09 | 842.94 | 25-NOV-13:39 | 20.17 | 14.26 |
December | 0.255397E+10 | 15136.52 | 17-DEC-08:62 | 19.83 | 15.88 | 0.396507E+09 | 842.98 | 16-DEC-13:09 | 19.83 | 15.88 |
Annual Sum or Average | 0.538423E+11 | 0.489143E+10 | ||||||||
Minimum of Months | 0.184934E+10 | 6388.26 | 15.83 | 13.53 | 0.359944E+09 | 842.90 | 18.90 | 13.53 | ||
Maximum of Months | 0.696432E+10 | 22410.81 | 26.88 | 24.44 | 0.431767E+09 | 842.99 | 28.90 | 25.09 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333797E+10 | 9721.41 | 01-JAN-15:10 | 25.00 | 18.55 | 0.128875E+10 | 2247.88 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.338309E+10 | 9447.00 | 02-FEB-13:40 | 27.90 | 20.68 | 0.122108E+10 | 2247.80 | 11-FEB-15:00 | 22.20 | 18.16 |
March | 0.416106E+10 | 9810.07 | 26-MAR-14:10 | 28.97 | 20.05 | 0.140439E+10 | 2247.88 | 04-MAR-15:20 | 28.97 | 20.05 |
April | 0.620013E+10 | 23056.97 | 29-APR-07:03 | 24.08 | 22.45 | 0.140792E+10 | 2248.05 | 29-APR-14:30 | 30.00 | 24.33 |
May | 0.105951E+11 | 29696.69 | 12-MAY-07:03 | 23.98 | 20.89 | 0.145787E+10 | 2248.04 | 06-MAY-14:39 | 23.98 | 20.89 |
June | 0.112352E+11 | 31688.53 | 14-JUN-07:02 | 26.88 | 23.48 | 0.142995E+10 | 2248.05 | 03-JUN-14:00 | 26.88 | 23.48 |
July | 0.116458E+11 | 30217.69 | 19-JUL-07:02 | 28.07 | 25.39 | 0.143856E+10 | 2248.02 | 08-JUL-14:09 | 28.07 | 25.39 |
August | 0.123386E+11 | 32995.78 | 31-AUG-07:02 | 25.45 | 23.81 | 0.148021E+10 | 2248.04 | 26-AUG-14:39 | 25.45 | 23.81 |
September | 0.106841E+11 | 30116.59 | 01-SEP-07:02 | 25.97 | 23.81 | 0.141043E+10 | 2248.03 | 23-SEP-14:50 | 29.08 | 24.10 |
October | 0.105071E+11 | 41223.04 | 26-OCT-07:02 | 21.83 | 13.09 | 0.143507E+10 | 2247.96 | 21-OCT-14:00 | 21.83 | 13.09 |
November | 0.601603E+10 | 28289.24 | 03-NOV-07:03 | 21.47 | 21.47 | 0.137605E+10 | 2247.89 | 25-NOV-15:09 | 19.80 | 14.72 |
December | 0.446348E+10 | 24315.29 | 11-DEC-08:62 | 20.17 | 20.05 | 0.134972E+10 | 2248.02 | 16-DEC-15:00 | 26.00 | 21.88 |
Annual Sum or Average | 0.945676E+11 | 0.167000E+11 | ||||||||
Minimum of Months | 0.333797E+10 | 9447.00 | 20.17 | 13.09 | 0.122108E+10 | 2247.80 | 19.80 | 13.09 | ||
Maximum of Months | 0.123386E+11 | 41223.04 | 28.97 | 25.39 | 0.148021E+10 | 2248.05 | 30.00 | 25.39 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159858E+10 | 5039.79 | 01-JAN-15:10 | 25.00 | 18.55 | 0.640654E+09 | 1123.91 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.165204E+10 | 4917.28 | 02-FEB-13:40 | 27.90 | 20.68 | 0.608091E+09 | 1123.87 | 11-FEB-15:00 | 22.20 | 18.16 |
March | 0.206174E+10 | 5122.32 | 26-MAR-14:10 | 28.97 | 20.05 | 0.699906E+09 | 1123.91 | 04-MAR-15:00 | 28.97 | 20.05 |
April | 0.317162E+10 | 11001.53 | 29-APR-07:03 | 24.08 | 22.45 | 0.703858E+09 | 1123.99 | 29-APR-14:39 | 30.00 | 24.22 |
May | 0.555047E+10 | 15482.51 | 31-MAY-07:03 | 24.87 | 22.53 | 0.728912E+09 | 1123.99 | 06-MAY-14:39 | 24.87 | 22.53 |
June | 0.589171E+10 | 16565.47 | 14-JUN-07:02 | 26.88 | 23.48 | 0.714949E+09 | 1124.00 | 03-JUN-14:00 | 26.88 | 23.48 |
July | 0.610621E+10 | 15801.44 | 19-JUL-07:02 | 28.07 | 25.39 | 0.719245E+09 | 1123.97 | 08-JUL-14:09 | 28.07 | 25.39 |
August | 0.646090E+10 | 17247.62 | 31-AUG-07:02 | 25.45 | 23.81 | 0.740072E+09 | 1123.99 | 26-AUG-14:39 | 25.45 | 23.81 |
September | 0.557487E+10 | 15733.29 | 01-SEP-07:02 | 25.97 | 23.81 | 0.705187E+09 | 1123.98 | 23-SEP-14:50 | 29.08 | 24.10 |
October | 0.546055E+10 | 21523.86 | 26-OCT-07:02 | 21.83 | 13.09 | 0.717504E+09 | 1123.96 | 21-OCT-14:00 | 21.83 | 13.09 |
November | 0.304763E+10 | 13614.45 | 03-NOV-07:03 | 21.47 | 21.47 | 0.687663E+09 | 1123.90 | 25-NOV-15:09 | 19.80 | 14.72 |
December | 0.220286E+10 | 11766.72 | 11-DEC-08:62 | 20.17 | 20.05 | 0.673130E+09 | 1123.97 | 16-DEC-15:50 | 26.17 | 21.93 |
Annual Sum or Average | 0.487792E+11 | 0.833917E+10 | ||||||||
Minimum of Months | 0.159858E+10 | 4917.28 | 20.17 | 13.09 | 0.608091E+09 | 1123.87 | 19.80 | 13.09 | ||
Maximum of Months | 0.646090E+10 | 21523.86 | 28.97 | 25.39 | 0.740072E+09 | 1124.00 | 30.00 | 25.39 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154789E+10 | 4988.16 | 01-JAN-15:10 | 25.00 | 18.55 | 0.638624E+09 | 1123.91 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.160437E+10 | 4860.62 | 02-FEB-13:40 | 27.90 | 20.68 | 0.606556E+09 | 1123.87 | 11-FEB-15:00 | 22.20 | 18.16 |
March | 0.200727E+10 | 5048.56 | 26-MAR-14:10 | 28.97 | 20.05 | 0.698538E+09 | 1123.91 | 04-MAR-15:00 | 28.97 | 20.05 |
April | 0.311639E+10 | 10672.90 | 29-APR-07:03 | 24.08 | 22.45 | 0.703762E+09 | 1123.99 | 29-APR-14:39 | 30.00 | 24.22 |
May | 0.550664E+10 | 15389.85 | 31-MAY-07:03 | 24.87 | 22.53 | 0.728906E+09 | 1123.99 | 06-MAY-14:39 | 24.87 | 22.53 |
June | 0.585103E+10 | 16476.85 | 14-JUN-07:02 | 26.88 | 23.48 | 0.714944E+09 | 1124.00 | 03-JUN-14:00 | 26.88 | 23.48 |
July | 0.607012E+10 | 15711.78 | 19-JUL-07:02 | 28.07 | 25.39 | 0.719239E+09 | 1123.98 | 08-JUL-14:09 | 28.07 | 25.39 |
August | 0.642531E+10 | 17156.68 | 31-AUG-07:02 | 25.45 | 23.81 | 0.740068E+09 | 1123.99 | 26-AUG-14:39 | 25.45 | 23.81 |
September | 0.554054E+10 | 15638.67 | 01-SEP-07:02 | 25.97 | 23.81 | 0.705183E+09 | 1123.98 | 23-SEP-14:50 | 29.08 | 24.10 |
October | 0.541853E+10 | 21415.66 | 26-OCT-07:02 | 21.83 | 13.09 | 0.717486E+09 | 1123.96 | 21-OCT-14:00 | 21.83 | 13.09 |
November | 0.299551E+10 | 13317.65 | 03-NOV-07:03 | 21.47 | 21.47 | 0.687440E+09 | 1123.90 | 25-NOV-15:09 | 19.80 | 14.72 |
December | 0.214944E+10 | 11255.72 | 11-DEC-08:62 | 20.17 | 20.05 | 0.671934E+09 | 1123.98 | 16-DEC-15:50 | 26.17 | 21.93 |
Annual Sum or Average | 0.482330E+11 | 0.833268E+10 | ||||||||
Minimum of Months | 0.154789E+10 | 4860.62 | 20.17 | 13.09 | 0.606556E+09 | 1123.87 | 19.80 | 13.09 | ||
Maximum of Months | 0.642531E+10 | 21415.66 | 28.97 | 25.39 | 0.740068E+09 | 1124.00 | 30.00 | 25.39 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143200E+10 | 4893.38 | 01-JAN-15:10 | 25.00 | 18.55 | 0.634345E+09 | 1123.91 | 28-JAN-15:20 | 23.00 | 14.05 |
February | 0.149062E+10 | 4740.62 | 02-FEB-13:40 | 27.90 | 20.68 | 0.603104E+09 | 1123.87 | 11-FEB-15:00 | 22.20 | 18.16 |
March | 0.187569E+10 | 4933.04 | 26-MAR-14:10 | 28.97 | 20.05 | 0.695339E+09 | 1123.91 | 04-MAR-15:50 | 28.97 | 20.05 |
April | 0.298068E+10 | 9185.71 | 29-APR-07:03 | 24.08 | 22.45 | 0.703371E+09 | 1123.98 | 29-APR-14:39 | 30.00 | 24.22 |
May | 0.545615E+10 | 15346.22 | 31-MAY-07:03 | 24.87 | 22.53 | 0.728900E+09 | 1123.98 | 06-MAY-14:39 | 24.87 | 22.53 |
June | 0.582702E+10 | 16466.80 | 14-JUN-07:02 | 26.88 | 23.48 | 0.714941E+09 | 1123.99 | 03-JUN-14:00 | 26.88 | 23.48 |
July | 0.607513E+10 | 15739.46 | 19-JUL-07:02 | 28.07 | 25.39 | 0.719239E+09 | 1123.98 | 08-JUL-14:09 | 28.07 | 25.39 |
August | 0.644619E+10 | 17199.60 | 31-AUG-07:02 | 25.45 | 23.81 | 0.740070E+09 | 1123.99 | 26-AUG-14:39 | 25.45 | 23.81 |
September | 0.554218E+10 | 15677.45 | 01-SEP-07:02 | 25.97 | 23.81 | 0.705184E+09 | 1123.98 | 23-SEP-14:50 | 29.08 | 24.10 |
October | 0.538928E+10 | 21401.46 | 26-OCT-07:02 | 21.83 | 13.09 | 0.717426E+09 | 1123.94 | 21-OCT-14:50 | 21.83 | 13.09 |
November | 0.288374E+10 | 12500.97 | 03-NOV-07:03 | 21.47 | 21.47 | 0.686821E+09 | 1123.89 | 25-NOV-15:09 | 19.80 | 14.72 |
December | 0.202629E+10 | 9713.09 | 11-DEC-08:62 | 20.17 | 20.05 | 0.668887E+09 | 1123.97 | 16-DEC-15:39 | 26.33 | 21.98 |
Annual Sum or Average | 0.474250E+11 | 0.831763E+10 | ||||||||
Minimum of Months | 0.143200E+10 | 4740.62 | 20.17 | 13.09 | 0.603104E+09 | 1123.87 | 19.80 | 13.09 | ||
Maximum of Months | 0.644619E+10 | 21401.46 | 28.97 | 25.39 | 0.740070E+09 | 1123.99 | 30.00 | 25.39 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132532E+10 | 5207.84 | 01-JAN-15:10 | 25.00 | 18.55 | 0.632449E+09 | 1123.91 | 28-JAN-15:30 | 23.00 | 14.05 |
February | 0.143936E+10 | 5166.65 | 24-FEB-13:40 | 27.37 | 21.42 | 0.599696E+09 | 1123.87 | 11-FEB-15:50 | 27.37 | 21.42 |
March | 0.189904E+10 | 5503.16 | 26-MAR-14:10 | 28.97 | 20.05 | 0.692223E+09 | 1123.91 | 04-MAR-15:00 | 28.97 | 20.05 |
April | 0.318678E+10 | 7486.25 | 28-APR-15:00 | 33.30 | 23.06 | 0.702769E+09 | 1123.98 | 22-APR-14:00 | 33.30 | 23.06 |
May | 0.620435E+10 | 14508.32 | 07-MAY-08:62 | 26.05 | 22.54 | 0.728973E+09 | 1123.94 | 27-MAY-14:00 | 32.20 | 25.37 |
June | 0.676309E+10 | 17930.98 | 16-JUN-07:02 | 27.48 | 24.40 | 0.715039E+09 | 1123.97 | 24-JUN-14:00 | 27.20 | 23.27 |
July | 0.715854E+10 | 17372.56 | 19-JUL-07:02 | 28.07 | 25.39 | 0.719398E+09 | 1124.01 | 08-JUL-14:20 | 28.07 | 25.39 |
August | 0.765103E+10 | 20219.39 | 31-AUG-07:02 | 25.45 | 23.81 | 0.740206E+09 | 1123.99 | 26-AUG-14:00 | 25.45 | 23.81 |
September | 0.648484E+10 | 18310.76 | 01-SEP-07:02 | 25.97 | 23.81 | 0.705340E+09 | 1123.99 | 30-SEP-14:39 | 30.53 | 24.28 |
October | 0.621078E+10 | 21232.26 | 26-OCT-07:02 | 21.83 | 13.09 | 0.717376E+09 | 1123.98 | 21-OCT-14:50 | 21.83 | 13.09 |
November | 0.307535E+10 | 12035.21 | 03-NOV-07:03 | 21.47 | 21.47 | 0.686273E+09 | 1123.87 | 04-NOV-14:00 | 25.50 | 20.83 |
December | 0.198807E+10 | 6602.67 | 16-DEC-13:10 | 27.83 | 22.27 | 0.665451E+09 | 1123.88 | 23-DEC-15:00 | 22.00 | 14.85 |
Annual Sum or Average | 0.533865E+11 | 0.830519E+10 | ||||||||
Minimum of Months | 0.132532E+10 | 5166.65 | 21.47 | 13.09 | 0.599696E+09 | 1123.87 | 21.83 | 13.09 | ||
Maximum of Months | 0.765103E+10 | 21232.26 | 33.30 | 25.39 | 0.740206E+09 | 1124.01 | 33.30 | 25.39 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122244E+09 | 54263.74 | 10-JAN-08:61 | 4.17 |
February | 0.172751E+09 | 54466.11 | 06-FEB-08:61 | 4.87 |
March | 0.207596E+09 | 53994.32 | 11-MAR-08:61 | 7.52 |
April | 44895997.56 | 1524.10 | 29-APR-07:05 | 24.08 |
May | 31587364.73 | 1836.61 | 31-MAY-07:05 | 24.87 |
June | 26984541.95 | 1796.11 | 24-JUN-07:05 | 26.97 |
July | 24847604.43 | 1744.68 | 14-JUL-07:05 | 24.82 |
August | 26362626.83 | 1706.06 | 18-AUG-07:05 | 24.77 |
September | 25785747.02 | 1787.28 | 22-SEP-07:05 | 21.97 |
October | 29384217.40 | 1954.20 | 26-OCT-07:04 | 21.83 |
November | 47227322.57 | 1760.94 | 03-NOV-07:05 | 21.47 |
December | 0.124129E+09 | 54263.18 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.883795E+09 | |||
Minimum of Months | 24847604.43 | 1524.10 | 3.50 | |
Maximum of Months | 0.207596E+09 | 54466.11 | 26.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38846181.51 | 2796.58 | 10-JAN-08:61 | 4.17 |
February | 42407325.62 | 16386.44 | 05-FEB-08:61 | -2.9 |
March | 59746434.01 | 7885.82 | 12-MAR-07:02 | 6.97 |
April | 17973704.35 | 909.00 | 29-APR-07:05 | 24.08 |
May | 16993366.96 | 1035.54 | 31-MAY-07:05 | 24.87 |
June | 14333985.64 | 1037.23 | 24-JUN-07:05 | 26.97 |
July | 11511113.07 | 1021.21 | 14-JUL-07:05 | 24.82 |
August | 12607770.96 | 1013.38 | 18-AUG-07:05 | 24.77 |
September | 13566035.17 | 1032.39 | 21-SEP-07:05 | 22.28 |
October | 15136308.04 | 1077.93 | 26-OCT-07:04 | 21.83 |
November | 18924516.19 | 986.93 | 02-NOV-07:05 | 22.98 |
December | 40525410.04 | 17326.72 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.302572E+09 | |||
Minimum of Months | 11511113.07 | 909.00 | -2.9 | |
Maximum of Months | 59746434.01 | 17326.72 | 26.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42319371.05 | 4111.98 | 10-JAN-07:03 | 3.17 |
February | 58988768.85 | 23560.82 | 05-FEB-08:61 | -2.9 |
March | 67078801.07 | 14704.22 | 12-MAR-07:02 | 6.97 |
April | 26953550.44 | 1084.60 | 22-APR-17:12 | 29.77 |
May | 70372260.20 | 1438.36 | 07-MAY-16:12 | 32.97 |
June | 78236365.28 | 1413.23 | 17-JUN-17:12 | 32.23 |
July | 80139156.84 | 1658.62 | 22-JUL-17:02 | 34.63 |
August | 69698822.76 | 1488.93 | 27-AUG-16:02 | 33.67 |
September | 53019203.11 | 1907.58 | 09-SEP-17:12 | 35.97 |
October | 46046620.57 | 1111.18 | 08-OCT-16:12 | 30.33 |
November | 23839129.31 | 965.82 | 08-NOV-07:05 | 19.50 |
December | 42920094.41 | 6776.27 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 0.659612E+09 | |||
Minimum of Months | 23839129.31 | 965.82 | -2.9 | |
Maximum of Months | 80139156.84 | 23560.82 | 35.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 46057030.99 | 6571.13 | 10-JAN-07:03 | 3.17 |
February | 66838751.83 | 26994.34 | 05-FEB-08:61 | -2.9 |
March | 74094393.57 | 17911.91 | 12-MAR-07:02 | 6.97 |
April | 27800755.57 | 1086.59 | 22-APR-17:12 | 29.77 |
May | 70270623.97 | 1439.74 | 07-MAY-16:12 | 32.97 |
June | 78036754.51 | 1414.89 | 17-JUN-17:12 | 32.23 |
July | 79843696.27 | 1658.87 | 22-JUL-17:02 | 34.63 |
August | 69158171.32 | 1488.69 | 27-AUG-16:02 | 33.67 |
September | 52706728.62 | 1909.09 | 09-SEP-17:12 | 35.97 |
October | 45931012.99 | 1112.54 | 08-OCT-16:12 | 30.33 |
November | 24987235.67 | 971.42 | 08-NOV-07:05 | 19.50 |
December | 46264926.10 | 7846.72 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 0.681990E+09 | |||
Minimum of Months | 24987235.67 | 971.42 | -2.9 | |
Maximum of Months | 79843696.27 | 26994.34 | 35.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55297000.98 | 9307.99 | 10-JAN-07:03 | 3.17 |
February | 80428282.69 | 28091.33 | 05-FEB-08:61 | -2.9 |
March | 87631084.97 | 21593.01 | 12-MAR-07:02 | 6.97 |
April | 29183910.36 | 1087.57 | 22-APR-17:12 | 29.77 |
May | 71290521.30 | 1439.97 | 07-MAY-16:12 | 32.97 |
June | 78727436.73 | 1415.12 | 17-JUN-17:12 | 32.23 |
July | 80843446.29 | 1662.05 | 22-JUL-17:02 | 34.63 |
August | 70969543.49 | 1490.98 | 27-AUG-16:02 | 33.67 |
September | 53575906.24 | 1909.34 | 09-SEP-17:12 | 35.97 |
October | 47548354.67 | 1112.41 | 08-OCT-16:12 | 30.33 |
November | 27633606.87 | 932.46 | 08-NOV-07:05 | 19.50 |
December | 55028425.71 | 9473.59 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 0.738158E+09 | |||
Minimum of Months | 27633606.87 | 932.46 | -2.9 | |
Maximum of Months | 87631084.97 | 28091.33 | 35.97 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135087E+09 | 51657.04 | 10-JAN-08:61 | 4.17 |
February | 0.163397E+09 | 51839.81 | 06-FEB-08:61 | 4.87 |
March | 0.173452E+09 | 51781.86 | 12-MAR-08:61 | 9.18 |
April | 58053005.02 | 2158.08 | 22-APR-17:12 | 29.77 |
May | 72943807.80 | 2993.25 | 28-MAY-16:02 | 33.43 |
June | 71580260.14 | 2838.88 | 17-JUN-17:12 | 32.23 |
July | 84264197.18 | 3459.19 | 22-JUL-17:02 | 34.63 |
August | 59754586.84 | 3115.19 | 27-AUG-16:02 | 33.67 |
September | 72736320.71 | 3886.36 | 09-SEP-17:02 | 36.18 |
October | 56757812.83 | 2216.67 | 08-OCT-16:12 | 30.33 |
November | 49459023.16 | 1624.53 | 03-NOV-07:05 | 21.47 |
December | 0.113839E+09 | 51656.73 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.111133E+10 | |||
Minimum of Months | 49459023.16 | 1624.53 | 3.50 | |
Maximum of Months | 0.173452E+09 | 51839.81 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 85119011.10 | 26918.27 | 10-JAN-08:61 | 4.17 |
February | 0.108211E+09 | 27017.03 | 06-FEB-08:61 | 4.87 |
March | 0.107789E+09 | 26985.20 | 12-MAR-08:61 | 9.18 |
April | 32174729.94 | 1111.47 | 22-APR-17:12 | 29.77 |
May | 38088759.50 | 1501.03 | 28-MAY-16:02 | 33.43 |
June | 36425392.47 | 1455.66 | 17-JUN-17:12 | 32.23 |
July | 43226537.47 | 1746.54 | 22-JUL-17:02 | 34.63 |
August | 30944838.71 | 1565.05 | 27-AUG-16:02 | 33.67 |
September | 37771358.32 | 1964.34 | 09-SEP-17:12 | 35.97 |
October | 29889582.49 | 1134.58 | 07-OCT-17:12 | 30.00 |
November | 27458624.56 | 849.20 | 03-NOV-07:05 | 21.47 |
December | 72914652.01 | 26918.26 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.650013E+09 | |||
Minimum of Months | 27458624.56 | 849.20 | 3.50 | |
Maximum of Months | 0.108211E+09 | 27017.03 | 35.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 94574824.95 | 26825.44 | 10-JAN-08:61 | 4.17 |
February | 0.119546E+09 | 26922.98 | 06-FEB-08:61 | 4.87 |
March | 0.114671E+09 | 26892.19 | 12-MAR-08:61 | 9.18 |
April | 33063744.87 | 1111.01 | 22-APR-17:12 | 29.77 |
May | 38091710.24 | 1501.99 | 28-MAY-16:02 | 33.43 |
June | 36445393.29 | 1455.27 | 17-JUN-17:12 | 32.23 |
July | 43179898.76 | 1747.06 | 22-JUL-17:02 | 34.63 |
August | 30944646.27 | 1565.36 | 27-AUG-16:02 | 33.67 |
September | 37797415.93 | 1963.29 | 09-SEP-17:12 | 35.97 |
October | 30081476.34 | 1134.05 | 07-OCT-17:12 | 30.00 |
November | 27975476.02 | 837.23 | 03-NOV-07:05 | 21.47 |
December | 78698725.98 | 26825.46 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.685071E+09 | |||
Minimum of Months | 27975476.02 | 837.23 | 3.50 | |
Maximum of Months | 0.119546E+09 | 26922.98 | 35.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131372E+09 | 26904.34 | 10-JAN-08:61 | 4.17 |
February | 0.155167E+09 | 27003.62 | 06-FEB-08:61 | 4.87 |
March | 0.142227E+09 | 26968.76 | 12-MAR-08:61 | 9.18 |
April | 36477115.57 | 1113.99 | 22-APR-17:12 | 29.77 |
May | 38504913.81 | 1503.33 | 28-MAY-16:02 | 33.43 |
June | 36948416.63 | 1455.89 | 17-JUN-17:12 | 32.23 |
July | 43447912.18 | 1746.69 | 22-JUL-17:02 | 34.63 |
August | 31032940.30 | 1564.80 | 27-AUG-16:02 | 33.67 |
September | 38180275.47 | 1965.85 | 09-SEP-17:12 | 35.97 |
October | 30668831.88 | 1134.40 | 07-OCT-17:12 | 30.00 |
November | 29876643.98 | 804.87 | 03-NOV-07:05 | 21.47 |
December | 99927330.33 | 26904.31 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.813830E+09 | |||
Minimum of Months | 29876643.98 | 804.87 | 3.50 | |
Maximum of Months | 0.155167E+09 | 27003.62 | 35.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.295160E+09 | 30433.27 | 10-JAN-08:61 | 4.17 |
February | 0.296719E+09 | 30562.21 | 06-FEB-08:61 | 4.87 |
March | 0.285798E+09 | 30520.63 | 12-MAR-08:61 | 9.18 |
April | 46243703.94 | 1153.13 | 22-APR-17:12 | 29.77 |
May | 39918475.20 | 1517.46 | 07-MAY-16:12 | 32.97 |
June | 38443782.08 | 1489.71 | 17-JUN-17:12 | 32.23 |
July | 42960686.22 | 1725.01 | 22-JUL-17:02 | 34.63 |
August | 30268679.71 | 1544.57 | 27-AUG-16:02 | 33.67 |
September | 38180978.25 | 1994.82 | 09-SEP-17:12 | 35.97 |
October | 34415273.01 | 1163.34 | 07-OCT-17:12 | 30.00 |
November | 35840273.74 | 897.35 | 03-NOV-07:05 | 21.47 |
December | 0.215871E+09 | 30432.81 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.139982E+10 | |||
Minimum of Months | 30268679.71 | 897.35 | 3.50 | |
Maximum of Months | 0.296719E+09 | 30562.21 | 35.97 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.549253E+10 | 3421.96 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.496476E+10 | 3421.96 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.549777E+10 | 3421.96 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.532115E+10 | 3421.96 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.549253E+10 | 3421.96 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.532179E+10 | 3421.96 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.549708E+10 | 3421.96 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.549285E+10 | 3421.96 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.532602E+10 | 3421.96 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.549253E+10 | 3421.96 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.530585E+10 | 3421.96 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.550226E+10 | 3421.96 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.647071E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.496476E+10 | 3421.96 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.550226E+10 | 3421.96 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.334781E+10 | 2090.38 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.302613E+10 | 2090.38 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.335104E+10 | 2090.38 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.324334E+10 | 2090.38 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.334781E+10 | 2090.38 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.324377E+10 | 2090.38 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.335056E+10 | 2090.38 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.334803E+10 | 2090.38 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.324631E+10 | 2090.38 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.334781E+10 | 2090.38 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.323401E+10 | 2090.38 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.335375E+10 | 2090.38 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.394404E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.302613E+10 | 2090.38 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.335375E+10 | 2090.38 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.241466E+10 | 2078.11 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.218750E+10 | 2078.11 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.247235E+10 | 2078.11 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.234375E+10 | 2078.11 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.244351E+10 | 2078.11 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.238702E+10 | 2078.11 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.240024E+10 | 2078.11 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.247235E+10 | 2078.11 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.234375E+10 | 2078.11 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.241466E+10 | 2078.11 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.234375E+10 | 2078.11 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.240024E+10 | 2078.11 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.286238E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.218750E+10 | 2078.11 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.247235E+10 | 2078.11 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70559733.85 | 0.259201E+10 |
February | 0.305697E+10 | 0.496476E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122072E+09 | 0.188226E+10 |
March | 0.335708E+10 | 0.549777E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266937E+09 | 0.165453E+10 |
April | 0.327081E+10 | 0.532115E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756046E+09 | 0.580628E+09 |
May | 0.336680E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217233E+10 | 21101908.18 |
June | 0.325380E+10 | 0.532179E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234936E+10 | 18606049.45 |
July | 0.339353E+10 | 0.549708E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228385E+10 | 11803874.49 |
August | 0.334857E+10 | 0.549285E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233877E+10 | 29927583.88 |
September | 0.327932E+10 | 0.532602E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166276E+10 | 63006218.12 |
October | 0.338624E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153562E+10 | 0.360505E+09 |
November | 0.327446E+10 | 0.530585E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373091E+09 | 0.117502E+10 |
December | 0.340325E+10 | 0.550226E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242271E+09 | 0.223270E+10 |
Annual Sum or Average | 0.397770E+11 | 0.647071E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141737E+11 | 0.106221E+11 |
Minimum of Months | 0.305697E+10 | 0.496476E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70559733.85 | 11803874.49 |
Maximum of Months | 0.340325E+10 | 0.550226E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234936E+10 | 0.259201E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39887472.45 | 0.139523E+10 |
February | 0.152844E+10 | 0.302613E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68879574.77 | 0.100428E+10 |
March | 0.167849E+10 | 0.335104E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150071E+09 | 0.864960E+09 |
April | 0.163536E+10 | 0.324334E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426571E+09 | 0.290244E+09 |
May | 0.168335E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121975E+10 | 7431240.69 |
June | 0.162685E+10 | 0.324377E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132175E+10 | 5961733.64 |
July | 0.169671E+10 | 0.335056E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127971E+10 | 5400778.15 |
August | 0.167424E+10 | 0.334803E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131049E+10 | 9825297.69 |
September | 0.163961E+10 | 0.324631E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929525E+09 | 25058470.35 |
October | 0.169307E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859062E+09 | 0.158700E+09 |
November | 0.163718E+10 | 0.323401E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210871E+09 | 0.599094E+09 |
December | 0.170157E+10 | 0.335375E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137016E+09 | 0.117026E+10 |
Annual Sum or Average | 0.198880E+11 | 0.394404E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795359E+10 | 0.553645E+10 |
Minimum of Months | 0.152844E+10 | 0.302613E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39887472.45 | 5400778.15 |
Maximum of Months | 0.170157E+10 | 0.335375E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132175E+10 | 0.139523E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887463.19 | 0.140685E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68806838.14 | 0.101935E+10 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147762E+09 | 0.886580E+09 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422176E+09 | 0.305718E+09 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119939E+10 | 10794214.55 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130476E+10 | 8560140.29 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125472E+10 | 6637692.02 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129414E+10 | 16436780.26 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908466E+09 | 33970995.29 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840762E+09 | 0.173286E+09 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208032E+09 | 0.616460E+09 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136555E+09 | 0.119003E+10 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782545E+10 | 0.567468E+10 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887463.19 | 6637692.02 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130476E+10 | 0.140685E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887459.39 | 0.139266E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68806980.38 | 0.101222E+10 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147769E+09 | 0.881596E+09 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422163E+09 | 0.305303E+09 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119912E+10 | 11115335.94 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130447E+10 | 8845781.23 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125414E+10 | 6917551.64 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129375E+10 | 16917746.55 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908049E+09 | 34541343.61 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840636E+09 | 0.173978E+09 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208032E+09 | 0.615634E+09 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136557E+09 | 0.118365E+10 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782338E+10 | 0.564338E+10 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887459.39 | 6917551.64 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130447E+10 | 0.139266E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887454.05 | 0.136840E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68807530.41 | 0.998869E+09 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147794E+09 | 0.869551E+09 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422255E+09 | 0.303398E+09 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119978E+10 | 10056177.22 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130505E+10 | 8151698.07 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125502E+10 | 6410736.75 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129431E+10 | 15829928.43 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908532E+09 | 33326930.21 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840960E+09 | 0.172174E+09 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208056E+09 | 0.612601E+09 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136560E+09 | 0.117188E+10 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782702E+10 | 0.557065E+10 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887454.05 | 6410736.75 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130505E+10 | 0.136840E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.241466E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69893197.19 | 0.238953E+10 |
February | 0.313522E+10 | 0.218750E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120605E+09 | 0.175021E+10 |
March | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259335E+09 | 0.152945E+10 |
April | 0.338259E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740447E+09 | 0.545227E+09 |
May | 0.349753E+10 | 0.244351E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210643E+10 | 17878583.72 |
June | 0.343071E+10 | 0.238702E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229064E+10 | 15141670.87 |
July | 0.344942E+10 | 0.240024E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220327E+10 | 11111363.58 |
August | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227310E+10 | 28534479.06 |
September | 0.338259E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159496E+10 | 61065383.83 |
October | 0.344359E+10 | 0.241466E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147773E+10 | 0.321539E+09 |
November | 0.331698E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364787E+09 | 0.109451E+10 |
December | 0.344942E+10 | 0.240024E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239278E+09 | 0.206855E+10 |
Annual Sum or Average | 0.410346E+11 | 0.286238E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137405E+11 | 0.983275E+10 |
Minimum of Months | 0.313522E+10 | 0.218750E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69893197.19 | 11111363.58 |
Maximum of Months | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229064E+10 | 0.238953E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887450.54 | 0.132623E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68809486.43 | 0.972990E+09 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147881E+09 | 0.844740E+09 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422562E+09 | 0.302373E+09 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120135E+10 | 8674514.95 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130670E+10 | 7351695.39 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125642E+10 | 5838134.76 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129599E+10 | 14092735.52 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.909028E+09 | 31644006.69 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842427E+09 | 0.173834E+09 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208171E+09 | 0.609686E+09 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136561E+09 | 0.115203E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783578E+10 | 0.544948E+10 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887450.54 | 5838134.76 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130670E+10 | 0.132623E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887448.72 | 0.131840E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68809710.17 | 0.966996E+09 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147898E+09 | 0.839293E+09 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422593E+09 | 0.301487E+09 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120156E+10 | 8475623.31 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130686E+10 | 7239985.83 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125666E+10 | 5775414.92 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129613E+10 | 13940017.52 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.909153E+09 | 31453220.28 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842520E+09 | 0.173385E+09 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208178E+09 | 0.608277E+09 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136562E+09 | 0.114710E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783681E+10 | 0.542182E+10 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887448.72 | 5775414.92 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130686E+10 | 0.131840E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887443.19 | 0.130127E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68810199.25 | 0.952842E+09 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147935E+09 | 0.825891E+09 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422651E+09 | 0.298097E+09 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120209E+10 | 7800980.04 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130715E+10 | 6899139.14 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125688E+10 | 5610692.18 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129617E+10 | 13681070.73 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.909116E+09 | 31025762.68 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842572E+09 | 0.172155E+09 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208190E+09 | 0.604147E+09 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136564E+09 | 0.113442E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783802E+10 | 0.535384E+10 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887443.19 | 5610692.18 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130715E+10 | 0.130127E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40553937.99 | 0.152976E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70153375.27 | 0.110364E+10 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151563E+09 | 0.997515E+09 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430306E+09 | 0.367126E+09 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123455E+10 | 16209629.68 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133764E+10 | 15940886.05 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129156E+10 | 9211241.51 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133230E+10 | 32243749.06 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936752E+09 | 58867446.65 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866835E+09 | 0.260219E+09 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211603E+09 | 0.731954E+09 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138756E+09 | 0.133670E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.804257E+10 | 0.645939E+10 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40553937.99 | 9211241.51 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133764E+10 | 0.152976E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 3421.96 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.20 | 16-JAN-15:00 | 7668.65 | 04-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 3421.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2107.21 | 02-FEB-13:00 | 8462.73 | 04-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 3421.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2854.21 | 26-MAR-14:00 | 7632.19 | 11-MAR-12:10 |
April | 4050.04 | 01-APR-12:09 | 3421.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4371.71 | 28-APR-15:00 | 3428.67 | 02-APR-11:10 |
May | 4050.04 | 05-MAY-12:09 | 3421.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4660.37 | 07-MAY-14:00 | 524.52 | 31-MAY-13:00 |
June | 4050.04 | 02-JUN-12:09 | 3421.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5074.34 | 14-JUN-14:00 | 534.24 | 01-JUN-13:00 |
July | 4050.04 | 01-JUL-12:09 | 3421.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5552.73 | 22-JUL-16:00 | 529.81 | 12-JUL-15:00 |
August | 4050.04 | 04-AUG-12:09 | 3421.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5648.87 | 30-AUG-16:00 | 1008.29 | 16-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 3421.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5771.84 | 09-SEP-17:00 | 1979.94 | 07-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 3421.96 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4643.30 | 05-OCT-15:00 | 3395.50 | 27-OCT-16:00 |
November | 4050.04 | 03-NOV-12:09 | 3421.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2838.62 | 01-NOV-14:00 | 6118.94 | 15-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 3421.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2866.32 | 13-DEC-15:00 | 8685.40 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.20 | 524.52 | |||||
Maximum of Months | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5771.84 | 8685.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2090.38 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 2090.38 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2090.38 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.87 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 2090.38 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.41 | 28-APR-15:00 | 1962.43 | 02-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 2090.38 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.19 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 02-JUN-12:09 | 2090.38 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2090.38 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 04-AUG-12:09 | 2090.38 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.07 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 01-SEP-12:09 | 2090.38 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 2090.38 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.66 | 27-OCT-16:00 |
November | 2024.96 | 03-NOV-12:09 | 2090.38 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.15 | 01-NOV-14:00 | 3506.09 | 15-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2090.38 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.20 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.84 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.37 | 28-APR-15:00 | 1957.56 | 02-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.30 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.58 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.02 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2631.65 | 05-OCT-15:00 | 1915.66 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.06 | 01-NOV-14:00 | 3490.14 | 15-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.15 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.87 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.36 | 28-APR-15:00 | 1954.57 | 02-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.31 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.58 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.03 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2631.66 | 05-OCT-15:00 | 1915.66 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.05 | 01-NOV-14:00 | 3479.72 | 15-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.15 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.11 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.36 | 28-APR-15:00 | 1944.82 | 02-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.33 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.60 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.03 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2631.67 | 05-OCT-15:00 | 1915.66 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.03 | 01-NOV-14:00 | 3448.07 | 15-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.14 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2078.11 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.80 | 16-JAN-15:00 | 7613.97 | 04-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 2078.11 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2070.02 | 02-FEB-13:00 | 8324.27 | 04-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 2078.11 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2831.26 | 26-MAR-14:00 | 7527.14 | 11-MAR-12:10 |
April | 5400.05 | 01-APR-14:09 | 2078.11 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4322.65 | 28-APR-15:00 | 3367.96 | 02-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 2078.11 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4608.35 | 07-MAY-14:00 | 520.08 | 31-MAY-13:00 |
June | 5400.05 | 03-JUN-14:09 | 2078.11 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5045.04 | 14-JUN-14:00 | 525.36 | 01-JUN-13:00 |
July | 5400.05 | 01-JUL-14:09 | 2078.11 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5529.73 | 22-JUL-16:00 | 523.91 | 12-JUL-15:00 |
August | 5400.05 | 05-AUG-14:09 | 2078.11 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5611.65 | 30-AUG-16:00 | 1000.01 | 16-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 2078.11 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5702.99 | 09-SEP-17:00 | 1964.22 | 07-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 2078.11 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4610.19 | 05-OCT-15:00 | 3357.66 | 27-OCT-16:00 |
November | 5400.05 | 04-NOV-14:09 | 2078.11 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2822.97 | 01-NOV-14:00 | 5865.71 | 15-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2078.11 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2842.01 | 13-DEC-15:00 | 8649.42 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.80 | 520.08 | |||||
Maximum of Months | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5702.99 | 8649.42 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.11 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.17 | 28-APR-15:00 | 1901.20 | 02-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.16 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.65 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.13 | 01-NOV-14:00 | 3326.67 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.18 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.11 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.17 | 28-APR-15:00 | 1887.07 | 02-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.16 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.65 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.13 | 01-NOV-14:00 | 3311.64 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.18 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.11 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.19 | 28-APR-15:00 | 1853.62 | 01-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.17 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.65 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.11 | 01-NOV-14:00 | 3278.88 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.17 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 837.55 | 16-JAN-15:00 | 4401.62 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.86 | 02-FEB-13:00 | 4883.41 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1639.54 | 26-MAR-14:00 | 4397.55 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2515.11 | 28-APR-15:00 | 1910.12 | 01-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2681.23 | 07-MAY-14:00 | 301.30 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2910.21 | 14-JUN-14:00 | 308.33 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3181.61 | 22-JUL-16:00 | 304.80 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3241.30 | 30-AUG-16:00 | 579.09 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.12 | 09-SEP-17:00 | 1136.97 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2665.14 | 05-OCT-15:00 | 1953.46 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.57 | 01-NOV-14:00 | 3246.43 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1646.69 | 13-DEC-15:00 | 4976.57 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 837.55 | 301.30 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.12 | 4976.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10793.82 | 01-JAN-14:00 | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 988.02 | 0.00 |
February | 10330.60 | 24-FEB-14:00 | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1559.01 | 0.00 |
March | 11069.77 | 26-MAR-14:00 | 2700.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2854.21 | 0.00 |
April | 22490.05 | 29-APR-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | 0.00 |
May | 31336.07 | 30-MAY-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 122.09 | 0.00 |
June | 33298.92 | 26-JUN-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 73.93 | 0.00 |
July | 32331.10 | 09-JUL-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 243.48 | 0.00 |
August | 35314.38 | 31-AUG-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 54.59 | 0.00 |
September | 31567.43 | 02-SEP-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 98.09 | 0.00 |
October | 44143.98 | 26-OCT-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.65 |
November | 30170.82 | 03-NOV-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.34 |
December | 25087.64 | 17-DEC-08:62 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10330.60 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44143.98 | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2854.21 | 362.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13605.85 | 29-JAN-19:06 | 6749.87 | 10451.90 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.43 |
February | 11447.58 | 20-FEB-18:23 | 12149.77 | 12542.28 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.16 |
March | 15257.54 | 04-MAR-19:08 | 13499.74 | 16723.04 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.46 |
April | 15321.01 | 16-APR-17:08 | 16199.69 | 16723.04 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.78 |
May | 19169.60 | 30-MAY-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 68.46 | 0.00 |
June | 19837.19 | 26-JUN-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 42.74 | 0.00 |
July | 18935.95 | 09-JUL-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 139.19 | 0.00 |
August | 19784.17 | 31-AUG-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 36.60 | 0.00 |
September | 19288.25 | 01-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.85 | 0.00 |
October | 23381.08 | 26-OCT-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.72 |
November | 16766.26 | 02-NOV-07:03 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 |
December | 15426.61 | 17-DEC-08:62 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11447.58 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23381.08 | 16199.69 | 16723.04 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.19 | 185.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8532.99 | 02-JAN-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 |
February | 7798.07 | 28-FEB-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.46 |
March | 7811.26 | 30-MAR-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 |
April | 14295.27 | 29-APR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 |
May | 16993.06 | 12-MAY-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.72 |
June | 17564.21 | 14-JUN-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 | 0.00 |
July | 16070.24 | 19-JUL-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 | 0.00 |
August | 17927.18 | 31-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16575.36 | 23-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 |
October | 22574.13 | 26-OCT-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 |
November | 16308.91 | 08-NOV-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.02 |
December | 16303.88 | 17-DEC-08:62 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7798.07 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22574.13 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 | 185.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8515.47 | 02-JAN-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 |
February | 7612.18 | 28-FEB-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.46 |
March | 7701.71 | 30-MAR-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 |
April | 14351.89 | 29-APR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 |
May | 17089.38 | 12-MAY-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 |
June | 17673.85 | 14-JUN-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 | 0.00 |
July | 16170.79 | 19-JUL-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 | 0.00 |
August | 18034.77 | 31-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16663.00 | 23-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 |
October | 22684.66 | 26-OCT-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.75 |
November | 16384.18 | 08-NOV-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.04 |
December | 16391.55 | 17-DEC-08:62 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7612.18 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22684.66 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 | 185.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7570.58 | 02-JAN-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 |
February | 6388.26 | 28-FEB-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.45 |
March | 6418.61 | 30-MAR-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 |
April | 13949.58 | 30-APR-07:03 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.24 |
May | 16866.68 | 12-MAY-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 |
June | 17423.40 | 14-JUN-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 | 0.00 |
July | 15913.94 | 19-JUL-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 | 0.00 |
August | 17796.14 | 31-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16448.38 | 23-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.44 |
October | 22410.81 | 26-OCT-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.20 |
November | 15497.36 | 08-NOV-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.92 |
December | 15136.52 | 17-DEC-08:62 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6388.26 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22410.81 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 | 185.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9721.41 | 01-JAN-15:10 | 4657.54 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 519.39 | 0.00 |
February | 9447.00 | 02-FEB-13:40 | 4792.55 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1882.00 | 0.00 |
March | 9810.07 | 26-MAR-14:10 | 4657.54 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2362.59 | 0.00 |
April | 23056.97 | 29-APR-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 8.73 | 0.00 |
May | 29696.69 | 12-MAY-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
June | 31688.53 | 14-JUN-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 157.26 | 0.00 |
July | 30217.69 | 19-JUL-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 217.65 | 0.00 |
August | 32995.78 | 31-AUG-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 57.97 | 0.00 |
September | 30116.59 | 01-SEP-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 96.69 | 0.00 |
October | 41223.04 | 26-OCT-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.19 |
November | 28289.24 | 03-NOV-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.34 |
December | 24315.29 | 11-DEC-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9447.00 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41223.04 | 4792.55 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2362.59 | 278.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5039.79 | 01-JAN-15:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 296.61 | 0.00 |
February | 4917.28 | 02-FEB-13:40 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.53 | 0.00 |
March | 5122.32 | 26-MAR-14:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.43 | 0.00 |
April | 11001.53 | 29-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 5.09 | 0.00 |
May | 15482.51 | 31-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 26.53 | 0.00 |
June | 16565.47 | 14-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.96 | 0.00 |
July | 15801.44 | 19-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 126.98 | 0.00 |
August | 17247.62 | 31-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.08 | 0.00 |
September | 15733.29 | 01-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.03 | 0.00 |
October | 21523.86 | 26-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.75 |
November | 13614.45 | 03-NOV-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.81 |
December | 11766.72 | 11-DEC-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4917.28 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21523.86 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.43 | 157.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4988.16 | 01-JAN-15:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 296.61 | 0.00 |
February | 4860.62 | 02-FEB-13:40 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.53 | 0.00 |
March | 5048.56 | 26-MAR-14:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.43 | 0.00 |
April | 10672.90 | 29-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 | 0.00 |
May | 15389.85 | 31-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 27.20 | 0.00 |
June | 16476.85 | 14-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.58 | 0.00 |
July | 15711.78 | 19-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 127.52 | 0.00 |
August | 17156.68 | 31-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.47 | 0.00 |
September | 15638.67 | 01-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.64 | 0.00 |
October | 21415.66 | 26-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.19 |
November | 13317.65 | 03-NOV-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.70 |
December | 11255.72 | 11-DEC-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4860.62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21415.66 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.43 | 157.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4893.38 | 01-JAN-15:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 296.61 | 0.00 |
February | 4740.62 | 02-FEB-13:40 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.53 | 0.00 |
March | 4933.04 | 26-MAR-14:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.43 | 0.00 |
April | 9185.71 | 29-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 5.80 | 0.00 |
May | 15346.22 | 31-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 31.47 | 0.00 |
June | 16466.80 | 14-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.94 | 0.00 |
July | 15739.46 | 19-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 129.39 | 0.00 |
August | 17199.60 | 31-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.92 | 0.00 |
September | 15677.45 | 01-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.25 | 0.00 |
October | 21401.46 | 26-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.63 |
November | 12500.97 | 03-NOV-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.38 |
December | 9713.09 | 11-DEC-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4740.62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21401.46 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.43 | 156.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5207.84 | 01-JAN-15:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 299.48 | 0.00 |
February | 5166.65 | 24-FEB-13:40 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 943.09 | 0.00 |
March | 5503.16 | 26-MAR-14:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1369.70 | 0.00 |
April | 7486.25 | 28-APR-15:00 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2515.11 | 0.00 |
May | 14508.32 | 07-MAY-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 93.17 | 0.00 |
June | 17930.98 | 16-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.74 | 0.00 |
July | 17372.56 | 19-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 137.08 | 0.00 |
August | 20219.39 | 31-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 0.00 |
September | 18310.76 | 01-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.13 | 0.00 |
October | 21232.26 | 26-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.82 |
November | 12035.21 | 03-NOV-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.53 |
December | 6602.67 | 16-DEC-13:10 | 2497.45 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1078.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5166.65 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21232.26 | 2497.45 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2515.11 | 103.82 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.560943E+11 | 61423.37 | 19-JAN-13:20 | 0.247430E+10 | 55746.61 | 10-JAN-08:09 |
February | 0.527563E+11 | 66201.76 | 24-FEB-13:09 | 0.334611E+10 | 79209.54 | 05-FEB-09:09 |
March | 0.608637E+11 | 65146.99 | 28-MAR-12:20 | 0.244836E+10 | 75357.41 | 11-MAR-12:09 |
April | 0.660694E+11 | 75177.59 | 28-APR-16:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.877245E+11 | 78816.94 | 24-MAY-12:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.888555E+11 | 86684.57 | 28-JUN-13:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.939211E+11 | 95361.00 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.953582E+11 | 86837.77 | 03-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.871970E+11 | 101597.74 | 10-SEP-14:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.840212E+11 | 92232.18 | 07-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.629121E+11 | 74068.87 | 02-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.600455E+11 | 68993.11 | 14-DEC-14:39 | 0.266516E+10 | 69865.30 | 20-DEC-17:00 |
Annual Sum or Average | 0.895819E+12 | 0.109339E+11 | ||||
Minimum of Months | 0.527563E+11 | 61423.37 | 0.00 | 0.00 | ||
Maximum of Months | 0.953582E+11 | 101597.74 | 0.334611E+10 | 79209.54 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.438697E+10 | 7894.35 | 23-JAN-12:50 | 0.00 | 0.00 |
February | 0.489157E+10 | 9139.41 | 13-FEB-12:30 | 0.00 | 0.00 |
March | 0.576712E+10 | 10606.30 | 22-MAR-12:30 | 0.00 | 0.00 |
April | 0.687704E+10 | 10852.00 | 10-APR-12:30 | 0.00 | 0.00 |
May | 0.666501E+10 | 10548.58 | 15-MAY-12:30 | 0.00 | 0.00 |
June | 0.706604E+10 | 10636.28 | 09-JUN-12:30 | 0.00 | 0.00 |
July | 0.687210E+10 | 10052.00 | 06-JUL-12:39 | 0.00 | 0.00 |
August | 0.648772E+10 | 10073.65 | 03-AUG-12:30 | 0.00 | 0.00 |
September | 0.544463E+10 | 9407.25 | 03-SEP-12:30 | 0.00 | 0.00 |
October | 0.540352E+10 | 9036.36 | 01-OCT-12:30 | 0.00 | 0.00 |
November | 0.437731E+10 | 8149.59 | 15-NOV-12:20 | 0.00 | 0.00 |
December | 0.398075E+10 | 7266.06 | 26-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.682198E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.398075E+10 | 7266.06 | 0.00 | 0.00 | |
Maximum of Months | 0.706604E+10 | 10852.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.234911E+11 | 0.413844E+10 | 0.108325E+11 | 0.00 | 0.789374E+10 | 0.00 | 0.00 | 0.449437E+10 | 0.00 | 0.00 | 0.00 | 0.524421E+10 | 0.00 |
February | 0.212624E+11 | 0.351184E+10 | 0.980803E+10 | 0.00 | 0.720378E+10 | 0.00 | 0.00 | 0.624334E+10 | 0.00 | 0.00 | 0.00 | 0.472692E+10 | 0.00 |
March | 0.238408E+11 | 0.354771E+10 | 0.110075E+11 | 0.00 | 0.805873E+10 | 0.00 | 0.00 | 0.919194E+10 | 0.00 | 0.00 | 0.00 | 0.521704E+10 | 0.00 |
April | 0.227839E+11 | 0.310332E+10 | 0.105079E+11 | 0.00 | 0.765958E+10 | 0.00 | 0.00 | 0.170779E+11 | 0.00 | 0.00 | 0.00 | 0.493676E+10 | 0.00 |
May | 0.236617E+11 | 0.290928E+10 | 0.109147E+11 | 0.00 | 0.801713E+10 | 0.00 | 0.00 | 0.371991E+11 | 0.00 | 0.00 | 0.00 | 0.502263E+10 | 0.00 |
June | 0.230409E+11 | 0.265346E+10 | 0.106386E+11 | 0.00 | 0.798354E+10 | 0.00 | 0.00 | 0.397291E+11 | 0.00 | 0.00 | 0.00 | 0.480998E+10 | 0.00 |
July | 0.234131E+11 | 0.282749E+10 | 0.107945E+11 | 0.00 | 0.844722E+10 | 0.00 | 0.00 | 0.435298E+11 | 0.00 | 0.00 | 0.00 | 0.490895E+10 | 0.00 |
August | 0.238328E+11 | 0.306832E+10 | 0.110006E+11 | 0.00 | 0.854579E+10 | 0.00 | 0.00 | 0.439584E+11 | 0.00 | 0.00 | 0.00 | 0.495224E+10 | 0.00 |
September | 0.227918E+11 | 0.329417E+10 | 0.105148E+11 | 0.00 | 0.799795E+10 | 0.00 | 0.00 | 0.377836E+11 | 0.00 | 0.00 | 0.00 | 0.481476E+10 | 0.00 |
October | 0.234911E+11 | 0.374992E+10 | 0.108325E+11 | 0.00 | 0.815675E+10 | 0.00 | 0.00 | 0.327484E+11 | 0.00 | 0.00 | 0.00 | 0.504254E+10 | 0.00 |
November | 0.227593E+11 | 0.391670E+10 | 0.104978E+11 | 0.00 | 0.768608E+10 | 0.00 | 0.00 | 0.130897E+11 | 0.00 | 0.00 | 0.00 | 0.496244E+10 | 0.00 |
December | 0.234215E+11 | 0.421341E+10 | 0.108050E+11 | 0.00 | 0.791803E+10 | 0.00 | 0.00 | 0.848802E+10 | 0.00 | 0.00 | 0.00 | 0.519952E+10 | 0.00 |
Annual Sum or Average | 0.277790E+12 | 0.409340E+11 | 0.128154E+12 | 0.00 | 0.955683E+11 | 0.00 | 0.00 | 0.293534E+12 | 0.00 | 0.00 | 0.00 | 0.598380E+11 | 0.00 |
Minimum of Months | 0.212624E+11 | 0.265346E+10 | 0.980803E+10 | 0.00 | 0.720378E+10 | 0.00 | 0.00 | 0.449437E+10 | 0.00 | 0.00 | 0.00 | 0.472692E+10 | 0.00 |
Maximum of Months | 0.238408E+11 | 0.421341E+10 | 0.110075E+11 | 0.00 | 0.854579E+10 | 0.00 | 0.00 | 0.439584E+11 | 0.00 | 0.00 | 0.00 | 0.524421E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.247430E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.334611E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.244836E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.266516E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.109339E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.334611E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17697.17 | 01-JAN-11:09 | 3786.68 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 6474.15 | 10-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 17697.17 | 01-FEB-10:09 | 3786.68 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 6934.70 | 05-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 17697.17 | 01-MAR-10:09 | 3786.68 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 6857.07 | 11-MAR-12:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 17697.17 | 01-APR-09:09 | 3786.68 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 6214.73 | 29-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 17697.17 | 01-MAY-09:09 | 3786.68 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 7048.26 | 22-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 17697.17 | 01-JUN-09:09 | 3786.68 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 7579.25 | 28-JUN-14:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 17697.17 | 01-JUL-09:09 | 3786.68 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 8735.25 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 17697.17 | 01-AUG-09:09 | 3786.68 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 7882.61 | 14-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 17697.17 | 01-SEP-09:09 | 3786.68 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 9982.40 | 10-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 17697.17 | 01-OCT-10:09 | 3786.68 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 9154.11 | 07-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 17697.17 | 01-NOV-09:09 | 3786.68 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 6670.52 | 02-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 17697.17 | 01-DEC-10:09 | 3786.68 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 6750.05 | 20-DEC-17:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 17697.17 | 3786.68 | 8059.50 | 0.00 | 6214.73 | 0.00 | 0.00 | |||||
Maximum of Months | 17697.17 | 3786.68 | 8059.50 | 0.00 | 9982.40 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 25428.62 | 19-JAN-13:00 | 0.00 | 0.00 | 0.00 | 11639.76 | 01-JAN-08:30 | 0.00 | 01-JAN-00:10 |
February | 27520.59 | 24-FEB-13:30 | 0.00 | 0.00 | 0.00 | 7571.08 | 02-FEB-13:00 | 0.00 | 01-FEB-00:10 |
March | 30411.46 | 30-MAR-12:00 | 0.00 | 0.00 | 0.00 | 9682.29 | 21-MAR-13:20 | 0.00 | 01-MAR-00:10 |
April | 40977.53 | 28-APR-16:10 | 0.00 | 0.00 | 0.00 | 7560.45 | 04-APR-13:09 | 0.00 | 01-APR-00:10 |
May | 43841.81 | 24-MAY-12:00 | 0.00 | 0.00 | 0.00 | 7556.66 | 01-MAY-12:30 | 0.00 | 01-MAY-00:10 |
June | 48576.41 | 28-JUN-14:09 | 0.00 | 0.00 | 0.00 | 9632.75 | 30-JUN-16:19 | 0.00 | 01-JUN-00:10 |
July | 55718.10 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 7527.21 | 10-JUL-16:30 | 0.00 | 01-JUL-00:10 |
August | 50054.06 | 03-AUG-16:10 | 0.00 | 0.00 | 0.00 | 7545.16 | 22-AUG-13:39 | 0.00 | 01-AUG-00:10 |
September | 61241.62 | 10-SEP-14:09 | 0.00 | 0.00 | 0.00 | 7549.86 | 22-SEP-13:09 | 0.00 | 01-SEP-00:10 |
October | 55456.41 | 07-OCT-12:00 | 0.00 | 0.00 | 0.00 | 8809.59 | 30-OCT-12:00 | 0.00 | 01-OCT-00:10 |
November | 39005.94 | 02-NOV-12:00 | 0.00 | 0.00 | 0.00 | 8747.62 | 15-NOV-16:40 | 0.00 | 01-NOV-00:10 |
December | 33391.25 | 15-DEC-13:00 | 0.00 | 0.00 | 0.00 | 9258.33 | 30-DEC-13:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 25428.62 | 0.00 | 0.00 | 0.00 | 7527.21 | 0.00 | |||
Maximum of Months | 61241.62 | 0.00 | 0.00 | 0.00 | 11639.76 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 61423.37 | 19-JAN-13:20 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5381.86 | 0.00 | 0.00 | 24833.61 | 0.00 |
February | 66201.76 | 24-FEB-13:09 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5381.86 | 0.00 | 0.00 | 27492.21 | 0.00 |
March | 65146.99 | 28-MAR-12:20 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5381.86 | 0.00 | 0.00 | 27803.22 | 0.00 |
April | 75177.59 | 28-APR-16:40 | 17697.17 | 8059.50 | 0.00 | 0.00 | 6041.08 | 0.00 | 0.00 | 40059.20 | 0.00 |
May | 78816.94 | 24-MAY-12:50 | 17697.17 | 8059.50 | 0.00 | 0.00 | 6578.38 | 0.00 | 0.00 | 43157.31 | 0.00 |
June | 86684.57 | 28-JUN-13:20 | 17697.17 | 8059.50 | 0.00 | 0.00 | 7213.93 | 0.00 | 0.00 | 46460.69 | 0.00 |
July | 95361.00 | 22-JUL-15:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 8735.25 | 0.00 | 0.00 | 55718.10 | 0.00 |
August | 86837.77 | 03-AUG-16:10 | 17697.17 | 8059.50 | 0.00 | 0.00 | 7709.58 | 0.00 | 0.00 | 50054.06 | 0.00 |
September | 101597.74 | 10-SEP-14:39 | 17697.17 | 8059.50 | 0.00 | 0.00 | 9807.80 | 0.00 | 0.00 | 60619.46 | 0.00 |
October | 92232.18 | 07-OCT-12:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 9154.11 | 0.00 | 0.00 | 55456.41 | 0.00 |
November | 74068.87 | 02-NOV-12:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5978.73 | 0.00 | 0.00 | 39005.94 | 0.00 |
December | 68993.11 | 14-DEC-14:39 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5381.86 | 0.00 | 0.00 | 30288.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 61423.37 | 17697.17 | 8059.50 | 0.00 | 0.00 | 5381.86 | 0.00 | 0.00 | 24833.61 | 0.00 | |
Maximum of Months | 101597.74 | 17697.17 | 8059.50 | 0.00 | 0.00 | 9807.80 | 0.00 | 0.00 | 60619.46 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 55746.61 | 10-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 79209.54 | 05-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 75357.41 | 11-MAR-12:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 69865.30 | 20-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 79209.54 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.52 | 0.00 | 24.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.52 | 0.00 | 24.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.52 | 0.00 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 24.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 24.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 24.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.71 | 0.00 | 24.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.71 | 0.00 | 24.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.71 | 0.00 | 24.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.66 | 0.00 | 24.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.66 | 0.00 | 24.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.66 | 0.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.66 | 0.00 | 24.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.66 | 0.00 | 24.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.66 | 0.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.67 | 0.00 | 24.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.67 | 0.00 | 24.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.67 | 0.00 | 24.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.72 | 0.00 | 24.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.50 | 0.00 | 20.50 | 0.33 | 23.32 | 0.00 | 23.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.50 | 0.00 | 20.50 | 0.33 | 24.72 | 0.00 | 24.72 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 345.17 | 22.34 | 154.00 | 22.78 | 40.33 | 22.83 |
February | 272.83 | 22.75 | 216.67 | 23.21 | 74.83 | 23.26 |
March | 261.67 | 22.82 | 198.83 | 23.26 | 45.67 | 23.29 |
April | 87.00 | 23.73 | 336.50 | 23.86 | 44.00 | 23.86 |
May | 98.00 | 23.89 | 495.83 | 23.89 | 98.00 | 23.89 |
June | 74.50 | 23.89 | 481.00 | 23.89 | 74.50 | 23.89 |
July | 178.83 | 23.89 | 495.00 | 23.89 | 178.83 | 23.89 |
August | 102.33 | 23.89 | 497.00 | 23.89 | 102.33 | 23.89 |
September | 137.33 | 23.89 | 479.00 | 23.89 | 137.33 | 23.89 |
October | 102.33 | 23.87 | 436.83 | 23.89 | 88.67 | 23.89 |
November | 108.83 | 23.65 | 276.67 | 23.82 | 37.50 | 23.83 |
December | 234.00 | 22.63 | 203.50 | 23.19 | 32.17 | 23.23 |
Annual Sum or Average | 2002.83 | 23.16 | 4270.83 | 23.65 | 954.17 | 23.67 |
Minimum of Months | 74.50 | 22.34 | 154.00 | 22.78 | 32.17 | 22.83 |
Maximum of Months | 345.17 | 23.89 | 497.00 | 23.89 | 178.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 304.00 | 22.90 | 142.17 | 23.21 | 29.50 | 23.24 |
February | 230.67 | 23.10 | 203.17 | 23.47 | 52.17 | 23.51 |
March | 211.33 | 23.11 | 185.83 | 23.47 | 26.67 | 23.50 |
April | 54.50 | 23.81 | 307.00 | 23.88 | 20.33 | 23.88 |
May | 61.83 | 23.89 | 480.83 | 23.89 | 61.83 | 23.89 |
June | 66.33 | 23.89 | 472.67 | 23.89 | 66.33 | 23.89 |
July | 145.17 | 23.89 | 493.67 | 23.89 | 145.17 | 23.89 |
August | 88.17 | 23.89 | 494.83 | 23.89 | 88.17 | 23.89 |
September | 121.33 | 23.89 | 473.67 | 23.89 | 121.33 | 23.89 |
October | 79.67 | 23.87 | 416.17 | 23.89 | 68.17 | 23.89 |
November | 84.83 | 23.79 | 264.83 | 23.86 | 28.00 | 23.87 |
December | 197.83 | 22.94 | 197.50 | 23.42 | 20.50 | 23.44 |
Annual Sum or Average | 1645.67 | 23.37 | 4132.33 | 23.74 | 728.17 | 23.76 |
Minimum of Months | 54.50 | 22.90 | 142.17 | 23.21 | 20.33 | 23.24 |
Maximum of Months | 304.00 | 23.89 | 494.83 | 23.89 | 145.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 250.00 | 22.56 | 113.83 | 22.98 | 25.50 | 23.03 |
February | 177.67 | 22.83 | 163.83 | 23.35 | 39.67 | 23.38 |
March | 177.83 | 22.93 | 154.17 | 23.43 | 27.00 | 23.48 |
April | 68.67 | 23.90 | 268.50 | 23.99 | 36.33 | 24.00 |
May | 88.33 | 24.18 | 375.00 | 24.08 | 88.33 | 24.09 |
June | 83.00 | 24.31 | 366.00 | 24.11 | 83.00 | 24.14 |
July | 170.17 | 24.19 | 369.00 | 24.11 | 170.17 | 24.13 |
August | 111.33 | 24.21 | 379.00 | 24.10 | 111.33 | 24.12 |
September | 145.83 | 24.19 | 360.00 | 24.09 | 145.83 | 24.11 |
October | 97.83 | 24.10 | 325.67 | 24.07 | 89.83 | 24.08 |
November | 73.67 | 23.82 | 215.33 | 23.96 | 33.50 | 23.98 |
December | 175.00 | 22.73 | 158.83 | 23.32 | 28.33 | 23.36 |
Annual Sum or Average | 1619.33 | 23.47 | 3249.17 | 23.84 | 878.83 | 23.89 |
Minimum of Months | 68.67 | 22.56 | 113.83 | 22.98 | 25.50 | 23.03 |
Maximum of Months | 250.00 | 24.31 | 379.00 | 24.11 | 170.17 | 24.14 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 257.33 | 22.50 | 112.50 | 22.93 | 27.83 | 22.98 |
February | 184.33 | 22.80 | 163.50 | 23.31 | 41.83 | 23.35 |
March | 183.17 | 22.92 | 151.33 | 23.41 | 27.67 | 23.45 |
April | 69.83 | 23.90 | 267.83 | 23.99 | 36.00 | 24.00 |
May | 87.50 | 24.18 | 375.00 | 24.08 | 87.50 | 24.09 |
June | 81.83 | 24.31 | 366.00 | 24.11 | 81.83 | 24.14 |
July | 166.17 | 24.20 | 369.00 | 24.11 | 166.17 | 24.13 |
August | 109.83 | 24.22 | 379.00 | 24.10 | 109.83 | 24.12 |
September | 142.17 | 24.19 | 360.00 | 24.09 | 142.17 | 24.11 |
October | 97.33 | 24.10 | 325.50 | 24.07 | 89.33 | 24.08 |
November | 76.00 | 23.81 | 212.83 | 23.95 | 34.17 | 23.97 |
December | 183.67 | 22.73 | 155.83 | 23.29 | 28.33 | 23.34 |
Annual Sum or Average | 1639.17 | 23.44 | 3238.33 | 23.83 | 872.67 | 23.88 |
Minimum of Months | 69.83 | 22.50 | 112.50 | 22.93 | 27.67 | 22.98 |
Maximum of Months | 257.33 | 24.31 | 379.00 | 24.11 | 166.17 | 24.14 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 275.33 | 22.44 | 108.17 | 22.84 | 36.67 | 22.91 |
February | 198.00 | 22.75 | 162.67 | 23.26 | 45.17 | 23.30 |
March | 199.17 | 22.90 | 144.33 | 23.36 | 32.33 | 23.41 |
April | 81.17 | 23.87 | 264.00 | 23.97 | 43.67 | 23.98 |
May | 93.17 | 24.15 | 375.00 | 24.07 | 93.17 | 24.08 |
June | 90.33 | 24.27 | 366.00 | 24.10 | 90.33 | 24.13 |
July | 179.00 | 24.17 | 369.00 | 24.10 | 179.00 | 24.12 |
August | 116.83 | 24.20 | 379.00 | 24.09 | 116.83 | 24.11 |
September | 151.33 | 24.17 | 360.00 | 24.09 | 151.33 | 24.11 |
October | 101.83 | 24.09 | 324.17 | 24.06 | 93.17 | 24.08 |
November | 89.00 | 23.78 | 207.17 | 23.93 | 41.00 | 23.95 |
December | 196.00 | 22.70 | 151.67 | 23.25 | 33.33 | 23.30 |
Annual Sum or Average | 1771.17 | 23.41 | 3211.17 | 23.80 | 956.00 | 23.85 |
Minimum of Months | 81.17 | 22.44 | 108.17 | 22.84 | 32.33 | 22.91 |
Maximum of Months | 275.33 | 24.27 | 379.00 | 24.10 | 179.00 | 24.13 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 273.00 | 22.34 | 92.50 | 22.70 | 42.83 | 22.80 |
February | 199.67 | 22.68 | 146.83 | 23.15 | 51.33 | 23.20 |
March | 217.17 | 22.91 | 126.50 | 23.27 | 48.50 | 23.34 |
April | 91.67 | 23.86 | 233.33 | 23.91 | 52.00 | 23.92 |
May | 108.33 | 24.04 | 344.00 | 23.97 | 108.33 | 23.98 |
June | 129.50 | 24.00 | 336.00 | 23.96 | 129.50 | 23.97 |
July | 224.00 | 24.01 | 338.00 | 23.99 | 224.00 | 24.00 |
August | 163.83 | 23.98 | 348.00 | 23.96 | 163.83 | 23.96 |
September | 208.00 | 24.01 | 330.00 | 23.98 | 208.00 | 23.99 |
October | 119.67 | 23.99 | 298.33 | 23.96 | 109.50 | 23.97 |
November | 113.50 | 23.74 | 175.17 | 23.85 | 58.33 | 23.87 |
December | 206.00 | 22.70 | 128.00 | 23.15 | 46.67 | 23.23 |
Annual Sum or Average | 2054.33 | 23.39 | 2896.67 | 23.71 | 1242.83 | 23.76 |
Minimum of Months | 91.67 | 22.34 | 92.50 | 22.70 | 42.83 | 22.80 |
Maximum of Months | 273.00 | 24.04 | 348.00 | 23.99 | 224.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 278.83 | 22.32 | 89.50 | 22.66 | 44.83 | 22.76 |
February | 202.83 | 22.64 | 145.00 | 23.11 | 53.83 | 23.16 |
March | 225.67 | 22.89 | 123.50 | 23.25 | 50.83 | 23.32 |
April | 97.83 | 23.86 | 229.00 | 23.91 | 53.83 | 23.92 |
May | 110.17 | 24.03 | 344.00 | 23.97 | 110.17 | 23.98 |
June | 132.67 | 24.00 | 336.00 | 23.96 | 132.67 | 23.97 |
July | 226.00 | 24.01 | 338.00 | 23.99 | 226.00 | 23.99 |
August | 169.67 | 23.97 | 348.00 | 23.95 | 169.67 | 23.96 |
September | 211.00 | 24.00 | 330.00 | 23.98 | 211.00 | 23.99 |
October | 123.50 | 23.98 | 295.83 | 23.96 | 110.17 | 23.97 |
November | 120.17 | 23.73 | 161.33 | 23.84 | 58.83 | 23.86 |
December | 215.17 | 22.71 | 123.00 | 23.13 | 47.33 | 23.21 |
Annual Sum or Average | 2113.50 | 23.38 | 2863.17 | 23.69 | 1269.17 | 23.75 |
Minimum of Months | 97.83 | 22.32 | 89.50 | 22.66 | 44.83 | 22.76 |
Maximum of Months | 278.83 | 24.03 | 348.00 | 23.99 | 226.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 280.50 | 22.29 | 87.33 | 22.63 | 45.50 | 22.73 |
February | 206.67 | 22.62 | 144.67 | 23.08 | 57.17 | 23.14 |
March | 232.00 | 22.88 | 122.17 | 23.23 | 52.67 | 23.30 |
April | 103.67 | 23.85 | 227.17 | 23.90 | 58.17 | 23.92 |
May | 113.33 | 24.03 | 344.00 | 23.97 | 113.33 | 23.98 |
June | 135.50 | 24.00 | 336.00 | 23.96 | 135.50 | 23.97 |
July | 229.33 | 24.01 | 338.00 | 23.99 | 229.33 | 23.99 |
August | 171.83 | 23.97 | 348.00 | 23.95 | 171.83 | 23.96 |
September | 213.67 | 24.00 | 330.00 | 23.98 | 213.67 | 23.99 |
October | 123.67 | 23.98 | 295.17 | 23.96 | 110.33 | 23.97 |
November | 122.67 | 23.72 | 159.00 | 23.83 | 59.17 | 23.85 |
December | 221.33 | 22.71 | 120.83 | 23.11 | 49.00 | 23.19 |
Annual Sum or Average | 2154.17 | 23.37 | 2852.33 | 23.69 | 1295.67 | 23.74 |
Minimum of Months | 103.67 | 22.29 | 87.33 | 22.63 | 45.50 | 22.73 |
Maximum of Months | 280.50 | 24.03 | 348.00 | 23.99 | 229.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 283.83 | 22.22 | 84.00 | 22.55 | 47.83 | 22.66 |
February | 217.00 | 22.58 | 144.83 | 23.02 | 64.50 | 23.08 |
March | 242.50 | 22.84 | 121.33 | 23.18 | 57.17 | 23.25 |
April | 113.50 | 23.81 | 223.50 | 23.89 | 62.33 | 23.90 |
May | 117.83 | 24.02 | 344.00 | 23.97 | 117.83 | 23.98 |
June | 138.00 | 24.00 | 336.00 | 23.96 | 138.00 | 23.97 |
July | 229.33 | 24.01 | 338.00 | 23.99 | 229.33 | 23.99 |
August | 171.17 | 23.97 | 348.00 | 23.95 | 171.17 | 23.96 |
September | 216.00 | 24.00 | 330.00 | 23.98 | 216.00 | 23.99 |
October | 125.17 | 23.97 | 293.83 | 23.96 | 110.83 | 23.97 |
November | 129.33 | 23.68 | 153.67 | 23.81 | 62.17 | 23.84 |
December | 234.83 | 22.68 | 118.33 | 23.07 | 51.50 | 23.15 |
Annual Sum or Average | 2218.50 | 23.34 | 2835.50 | 23.66 | 1328.67 | 23.72 |
Minimum of Months | 113.50 | 22.22 | 84.00 | 22.55 | 47.83 | 22.66 |
Maximum of Months | 283.83 | 24.02 | 348.00 | 23.99 | 229.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 281.33 | 22.15 | 93.67 | 22.50 | 51.17 | 22.58 |
February | 219.50 | 22.47 | 153.83 | 22.91 | 70.33 | 22.93 |
March | 241.67 | 22.73 | 133.17 | 23.06 | 62.83 | 23.11 |
April | 120.17 | 23.74 | 219.33 | 23.86 | 63.50 | 23.87 |
May | 106.50 | 24.05 | 344.00 | 23.97 | 106.50 | 23.99 |
June | 102.50 | 24.06 | 336.00 | 23.98 | 102.50 | 23.99 |
July | 177.50 | 24.06 | 338.00 | 24.01 | 177.50 | 24.02 |
August | 120.83 | 24.04 | 348.00 | 23.97 | 120.83 | 23.99 |
September | 169.50 | 24.05 | 330.00 | 24.00 | 169.50 | 24.01 |
October | 109.50 | 23.98 | 296.00 | 23.96 | 94.33 | 23.98 |
November | 126.50 | 23.62 | 156.33 | 23.79 | 54.50 | 23.82 |
December | 239.00 | 22.58 | 127.83 | 22.98 | 56.17 | 23.05 |
Annual Sum or Average | 2014.50 | 23.23 | 2876.17 | 23.62 | 1129.67 | 23.67 |
Minimum of Months | 102.50 | 22.15 | 93.67 | 22.50 | 51.17 | 22.58 |
Maximum of Months | 281.33 | 24.06 | 348.00 | 24.01 | 177.50 | 24.02 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 22.80691 | 44.46378 | 0.11216 | 7.65391 |
February | 448.00000 | 23.19341 | 48.29897 | 0.23238 | 8.66751 |
March | 497.00000 | 23.32340 | 46.52525 | 0.24955 | 8.39811 |
April | 479.00000 | 23.86069 | 53.05900 | 0.46167 | 9.74924 |
May | 496.00000 | 23.88730 | 60.59409 | -0.2975 | 6.91432 |
June | 481.00000 | 23.88960 | 60.21234 | -0.2771 | 6.69067 |
July | 495.00000 | 23.89011 | 63.84285 | -0.2395 | 6.27541 |
August | 497.00000 | 23.88994 | 61.73840 | -0.2395 | 6.28757 |
September | 479.00000 | 23.89002 | 62.71851 | -0.2497 | 6.41076 |
October | 496.00000 | 23.88450 | 55.59129 | 0.55515 | 11.72334 |
November | 480.00000 | 23.83302 | 48.18208 | 0.43217 | 9.35133 |
December | 496.00000 | 23.28858 | 46.05606 | 0.25759 | 8.44440 |
Annual Sum or Average | 5840.00000 | 23.63746 | 54.30136 | 0.08176 | 8.04190 |
Minimum of Months | 448.00000 | 22.80691 | 44.46378 | -0.2975 | 6.27541 |
Maximum of Months | 497.00000 | 23.89011 | 63.84285 | 0.55515 | 11.72334 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.28072 | 43.55577 | 0.21636 | 7.41737 |
February | 448.00000 | 23.47473 | 47.26911 | 0.29660 | 8.43958 |
March | 497.00000 | 23.55146 | 45.26745 | 0.30238 | 8.16033 |
April | 479.00000 | 23.87700 | 50.54437 | 0.45227 | 9.48499 |
May | 496.00000 | 23.88670 | 57.62940 | -0.3302 | 7.37558 |
June | 481.00000 | 23.88957 | 57.64947 | -0.3137 | 7.17135 |
July | 495.00000 | 23.89043 | 61.32284 | -0.2784 | 6.72964 |
August | 497.00000 | 23.89000 | 59.61371 | -0.2831 | 6.79271 |
September | 479.00000 | 23.88950 | 60.34717 | -0.2897 | 6.89190 |
October | 496.00000 | 23.88331 | 53.59922 | 0.52719 | 11.05731 |
November | 480.00000 | 23.86576 | 46.88256 | 0.43184 | 9.19268 |
December | 496.00000 | 23.50774 | 45.08279 | 0.30435 | 8.27034 |
Annual Sum or Average | 5840.00000 | 23.74117 | 52.42149 | 0.08474 | 8.07774 |
Minimum of Months | 448.00000 | 23.28072 | 43.55577 | -0.3302 | 6.72964 |
Maximum of Months | 497.00000 | 23.89043 | 61.32284 | 0.52719 | 11.05731 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.00679 | 42.16639 | 0.15643 | 7.53586 |
February | 336.00000 | 23.34961 | 46.92395 | 0.27429 | 8.76900 |
March | 379.00000 | 23.47215 | 45.09251 | 0.28731 | 8.53574 |
April | 360.00000 | 23.96848 | 52.31855 | 0.48455 | 10.25170 |
May | 375.00000 | 24.05256 | 60.34648 | -0.2615 | 6.76060 |
June | 366.00000 | 24.06049 | 60.46143 | -0.2416 | 6.60472 |
July | 369.00000 | 24.07167 | 64.49053 | -0.2009 | 6.28433 |
August | 379.00000 | 24.06160 | 62.58456 | -0.2097 | 6.30297 |
September | 360.00000 | 24.05500 | 63.53974 | -0.2166 | 6.38506 |
October | 371.00000 | 24.03347 | 55.47780 | 0.57577 | 12.36021 |
November | 360.00000 | 23.92627 | 47.42707 | 0.45255 | 9.73403 |
December | 369.00000 | 23.37018 | 45.02095 | 0.28069 | 8.60770 |
Annual Sum or Average | 4395.00000 | 23.78760 | 53.86879 | 0.11276 | 8.16676 |
Minimum of Months | 336.00000 | 23.00679 | 42.16639 | -0.2615 | 6.28433 |
Maximum of Months | 379.00000 | 24.07167 | 64.49053 | 0.57577 | 12.36021 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.94235 | 42.36618 | 0.13789 | 7.52628 |
February | 336.00000 | 23.31399 | 47.07489 | 0.26247 | 8.71631 |
March | 379.00000 | 23.45032 | 45.17169 | 0.27942 | 8.51454 |
April | 360.00000 | 23.96594 | 52.34225 | 0.48310 | 10.23022 |
May | 375.00000 | 24.05280 | 60.28344 | -0.2605 | 6.75099 |
June | 366.00000 | 24.06088 | 60.38120 | -0.2402 | 6.59334 |
July | 369.00000 | 24.07226 | 64.37659 | -0.1992 | 6.27446 |
August | 379.00000 | 24.06208 | 62.49067 | -0.2083 | 6.29324 |
September | 360.00000 | 24.05545 | 63.44222 | -0.2152 | 6.37664 |
October | 371.00000 | 24.03366 | 55.41720 | 0.57635 | 12.37611 |
November | 360.00000 | 23.92209 | 47.42468 | 0.45017 | 9.70033 |
December | 369.00000 | 23.34041 | 45.10065 | 0.27112 | 8.58172 |
Annual Sum or Average | 4395.00000 | 23.77470 | 53.86963 | 0.10912 | 8.15061 |
Minimum of Months | 336.00000 | 22.94235 | 42.36618 | -0.2605 | 6.27446 |
Maximum of Months | 379.00000 | 24.07226 | 64.37659 | 0.57635 | 12.37611 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.82808 | 42.82068 | 0.10787 | 7.53985 |
February | 336.00000 | 23.24040 | 47.44348 | 0.24080 | 8.61471 |
March | 379.00000 | 23.39375 | 45.46615 | 0.26176 | 8.44849 |
April | 360.00000 | 23.95543 | 52.69935 | 0.47810 | 10.14716 |
May | 375.00000 | 24.04899 | 60.59944 | -0.2639 | 6.77352 |
June | 366.00000 | 24.05720 | 60.67245 | -0.2434 | 6.60975 |
July | 369.00000 | 24.06874 | 64.67461 | -0.2017 | 6.27887 |
August | 379.00000 | 24.05854 | 62.77639 | -0.2110 | 6.30070 |
September | 360.00000 | 24.05188 | 63.74901 | -0.2178 | 6.38599 |
October | 371.00000 | 24.02896 | 55.65486 | 0.57409 | 12.32248 |
November | 360.00000 | 23.90666 | 47.65538 | 0.44358 | 9.60564 |
December | 369.00000 | 23.28175 | 45.35789 | 0.25364 | 8.52230 |
Annual Sum or Average | 4395.00000 | 23.74558 | 54.17738 | 0.09958 | 8.11928 |
Minimum of Months | 336.00000 | 22.82808 | 42.82068 | -0.2639 | 6.27887 |
Maximum of Months | 379.00000 | 24.06874 | 64.67461 | 0.57409 | 12.32248 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.65068 | 44.58402 | 0.06312 | 7.53688 |
February | 308.00000 | 23.11268 | 49.09656 | 0.20597 | 8.38336 |
March | 348.00000 | 23.28258 | 47.17392 | 0.23113 | 8.26357 |
April | 330.00000 | 23.89604 | 53.93703 | 0.46234 | 9.81319 |
May | 344.00000 | 23.94896 | 62.50568 | -0.2859 | 6.89635 |
June | 336.00000 | 23.94684 | 62.50046 | -0.2663 | 6.69566 |
July | 338.00000 | 23.97181 | 66.61478 | -0.2190 | 6.30698 |
August | 348.00000 | 23.94538 | 64.67661 | -0.2312 | 6.33355 |
September | 330.00000 | 23.96402 | 65.78186 | -0.2321 | 6.44052 |
October | 340.00000 | 23.94118 | 57.39175 | 0.56592 | 12.07554 |
November | 330.00000 | 23.84651 | 49.09124 | 0.42959 | 9.34396 |
December | 338.00000 | 23.16717 | 47.02173 | 0.22502 | 8.37834 |
Annual Sum or Average | 4030.00000 | 23.64168 | 55.91466 | 0.07673 | 8.03053 |
Minimum of Months | 308.00000 | 22.65068 | 44.58402 | -0.2859 | 6.30698 |
Maximum of Months | 348.00000 | 23.97181 | 66.61478 | 0.56592 | 12.07554 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.60189 | 44.61826 | 0.04290 | 7.54002 |
February | 308.00000 | 23.07434 | 49.15930 | 0.18791 | 8.29572 |
March | 348.00000 | 23.25194 | 47.22170 | 0.21492 | 8.16444 |
April | 330.00000 | 23.89352 | 53.99206 | 0.45103 | 9.59647 |
May | 344.00000 | 23.94868 | 62.60105 | -0.3053 | 7.13532 |
June | 336.00000 | 23.94640 | 62.61986 | -0.2873 | 6.93496 |
July | 338.00000 | 23.97094 | 66.80942 | -0.2400 | 6.50268 |
August | 348.00000 | 23.94465 | 64.84991 | -0.2532 | 6.55021 |
September | 330.00000 | 23.96349 | 65.98884 | -0.2525 | 6.63984 |
October | 340.00000 | 23.94061 | 57.51602 | 0.55146 | 11.72873 |
November | 330.00000 | 23.84036 | 49.12615 | 0.41744 | 9.13774 |
December | 338.00000 | 23.14184 | 47.03043 | 0.20936 | 8.26552 |
Annual Sum or Average | 4030.00000 | 23.62887 | 56.01138 | 0.05905 | 8.03398 |
Minimum of Months | 308.00000 | 22.60189 | 44.61826 | -0.3053 | 6.50268 |
Maximum of Months | 348.00000 | 23.97094 | 66.80942 | 0.55146 | 11.72873 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.56837 | 44.73745 | 0.03211 | 7.56437 |
February | 308.00000 | 23.04331 | 49.31395 | 0.17766 | 8.28076 |
March | 348.00000 | 23.22752 | 47.34375 | 0.20633 | 8.14474 |
April | 330.00000 | 23.88996 | 54.09101 | 0.44805 | 9.55114 |
May | 344.00000 | 23.94839 | 62.69866 | -0.3071 | 7.15596 |
June | 336.00000 | 23.94615 | 62.70790 | -0.2890 | 6.95313 |
July | 338.00000 | 23.97062 | 66.89501 | -0.2414 | 6.51444 |
August | 348.00000 | 23.94444 | 64.92630 | -0.2546 | 6.56305 |
September | 330.00000 | 23.96321 | 66.07686 | -0.2538 | 6.65229 |
October | 340.00000 | 23.93983 | 57.59006 | 0.55019 | 11.70129 |
November | 330.00000 | 23.83459 | 49.20603 | 0.41413 | 9.09719 |
December | 338.00000 | 23.11789 | 47.13863 | 0.20117 | 8.24450 |
Annual Sum or Average | 4030.00000 | 23.61861 | 56.11042 | 0.05468 | 8.02847 |
Minimum of Months | 308.00000 | 22.56837 | 44.73745 | -0.3071 | 6.51444 |
Maximum of Months | 348.00000 | 23.97062 | 66.89501 | 0.55019 | 11.70129 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.49714 | 44.99705 | 0.01135 | 7.65001 |
February | 308.00000 | 22.97070 | 49.69359 | 0.15631 | 8.29298 |
March | 348.00000 | 23.16818 | 47.63456 | 0.18797 | 8.13823 |
April | 330.00000 | 23.87531 | 54.35387 | 0.44172 | 9.47759 |
May | 344.00000 | 23.94801 | 62.83345 | -0.3055 | 7.13450 |
June | 336.00000 | 23.94599 | 62.77600 | -0.2864 | 6.92264 |
July | 338.00000 | 23.97065 | 66.90297 | -0.2378 | 6.48015 |
August | 348.00000 | 23.94453 | 64.89583 | -0.2505 | 6.52269 |
September | 330.00000 | 23.96328 | 66.09029 | -0.2505 | 6.62169 |
October | 340.00000 | 23.93751 | 57.63540 | 0.55093 | 11.73300 |
November | 330.00000 | 23.81685 | 49.43761 | 0.40840 | 9.05668 |
December | 338.00000 | 23.05512 | 47.39969 | 0.18285 | 8.23642 |
Annual Sum or Average | 4030.00000 | 23.59379 | 56.26897 | 0.04852 | 8.01548 |
Minimum of Months | 308.00000 | 22.49714 | 44.99705 | -0.3055 | 6.48015 |
Maximum of Months | 348.00000 | 23.97065 | 66.90297 | 0.55093 | 11.73300 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.45165 | 44.82954 | -0.0100 | 7.91824 |
February | 308.00000 | 22.88780 | 49.61311 | 0.12596 | 8.44982 |
March | 348.00000 | 23.09743 | 47.44012 | 0.16282 | 8.32047 |
April | 330.00000 | 23.84646 | 54.23177 | 0.43799 | 9.53677 |
May | 344.00000 | 23.95218 | 62.02652 | -0.2716 | 6.75304 |
June | 336.00000 | 23.95121 | 61.51940 | -0.2451 | 6.50502 |
July | 338.00000 | 23.97953 | 65.27909 | -0.1921 | 6.14733 |
August | 348.00000 | 23.95178 | 63.29306 | -0.2013 | 6.12066 |
September | 330.00000 | 23.97212 | 64.71412 | -0.2085 | 6.30916 |
October | 340.00000 | 23.93650 | 56.64806 | 0.57314 | 12.36141 |
November | 330.00000 | 23.79657 | 49.02451 | 0.40778 | 9.19176 |
December | 338.00000 | 22.97164 | 47.40368 | 0.15609 | 8.46685 |
Annual Sum or Average | 4030.00000 | 23.56928 | 55.54417 | 0.05936 | 7.99849 |
Minimum of Months | 308.00000 | 22.45165 | 44.82954 | -0.2716 | 6.12066 |
Maximum of Months | 348.00000 | 23.97953 | 65.27909 | 0.57314 | 12.36141 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.370820E+10 | 0.911113E+09 | 121.47 | 0.234675E+10 | 0.136145E+10 | 0.00 | 0.76 | 19-JAN-15:00 | 0.00 | 01-JAN-00:05 | 18671.28 | 19-JAN-15:00 | 12496.54 | 01-JAN-14:00 | 7801.08 | 19-JAN-15:00 | 4284.40 | 19-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.484100E+10 | 0.118420E+10 | 153.06 | 0.304755E+10 | 0.179345E+10 | 0.00 | 0.80 | 24-FEB-14:00 | 0.00 | 01-FEB-00:10 | 19852.27 | 24-FEB-14:00 | 12524.10 | 24-FEB-14:00 | 7328.17 | 24-FEB-14:00 | 4653.80 | 24-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.723497E+10 | 0.179057E+10 | 231.89 | 0.472484E+10 | 0.251013E+10 | 0.00 | 0.82 | 30-MAR-13:00 | 0.00 | 01-MAR-00:10 | 20236.50 | 30-MAR-13:00 | 14105.81 | 26-MAR-14:00 | 8008.12 | 07-MAR-08:63 | 4865.11 | 30-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.135487E+11 | 0.335135E+10 | 365.69 | 0.896888E+10 | 0.457977E+10 | 0.00 | 1.00 | 28-APR-07:03 | 0.00 | 01-APR-00:10 | 46191.78 | 29-APR-07:03 | 25890.33 | 29-APR-07:03 | 20301.45 | 29-APR-07:03 | 9551.94 | 29-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.303179E+11 | 0.736746E+10 | 495.38 | 0.187648E+11 | 0.115531E+11 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 55563.23 | 21-MAY-07:02 | 35882.66 | 31-MAY-07:03 | 27146.77 | 21-MAY-07:02 | 11577.36 | 27-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.323439E+11 | 0.781490E+10 | 482.46 | 0.199134E+11 | 0.124306E+11 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 54725.14 | 19-JUN-07:02 | 37326.88 | 26-JUN-07:02 | 24541.68 | 19-JUN-07:02 | 11824.45 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.366984E+11 | 0.870856E+10 | 497.18 | 0.210699E+11 | 0.156285E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 55908.26 | 02-JUL-07:02 | 36289.79 | 09-JUL-07:02 | 27873.09 | 02-JUL-07:03 | 11768.58 | 09-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.365245E+11 | 0.866713E+10 | 497.69 | 0.217118E+11 | 0.148128E+11 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 55591.88 | 16-AUG-07:02 | 39878.94 | 31-AUG-07:02 | 26441.00 | 16-AUG-07:02 | 11605.98 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.324770E+11 | 0.763454E+10 | 481.93 | 0.187636E+11 | 0.137134E+11 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 56412.83 | 05-SEP-07:02 | 36054.17 | 22-SEP-07:03 | 29380.68 | 05-SEP-07:03 | 12289.87 | 10-SEP-07:04 | 0.00 | 01-SEP-00:05 |
October | 0.276833E+11 | 0.655581E+10 | 453.80 | 0.171310E+11 | 0.105522E+11 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 55748.86 | 08-OCT-07:02 | 42546.38 | 26-OCT-07:02 | 27548.46 | 15-OCT-07:02 | 11655.51 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.106043E+11 | 0.255266E+10 | 282.32 | 0.675964E+10 | 0.384463E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 54055.68 | 02-NOV-07:03 | 34799.46 | 03-NOV-07:03 | 23811.27 | 04-NOV-07:03 | 11118.39 | 02-NOV-07:03 | 0.00 | 01-NOV-00:10 |
December | 0.694375E+10 | 0.167770E+10 | 184.25 | 0.439802E+10 | 0.254573E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 42570.10 | 11-DEC-08:62 | 27290.16 | 11-DEC-08:62 | 15279.94 | 11-DEC-08:62 | 8647.71 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.242926E+12 | 0.582160E+11 | 4247.12 | 0.147600E+12 | 0.953257E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.370820E+10 | 0.911113E+09 | 121.47 | 0.234675E+10 | 0.136145E+10 | 0.00 | 0.76 | 0.00 | 18671.28 | 12496.54 | 7328.17 | 4284.40 | 0.00 | |||||||
Maximum of Months | 0.366984E+11 | 0.870856E+10 | 497.69 | 0.217118E+11 | 0.156285E+11 | 0.00 | 1.00 | 0.00 | 56412.83 | 42546.38 | 29380.68 | 12289.87 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.222736E+10 | 0.535129E+09 | 133.41 | 0.144578E+10 | 0.781580E+09 | 0.00 | 1.00 | 01-JAN-18:02 | 0.00 | 01-JAN-00:05 | 27306.75 | 01-JAN-18:02 | 17459.83 | 29-JAN-18:01 | 12820.90 | 01-JAN-18:02 | 5494.76 | 01-JAN-18:02 | 0.00 | 01-JAN-00:05 |
February | 0.287223E+10 | 0.689364E+09 | 171.09 | 0.184901E+10 | 0.102321E+10 | 0.00 | 1.00 | 20-FEB-18:02 | 0.00 | 01-FEB-00:10 | 27368.12 | 20-FEB-18:02 | 14586.02 | 20-FEB-18:02 | 12974.43 | 20-FEB-18:23 | 5503.35 | 20-FEB-18:02 | 0.00 | 01-FEB-00:10 |
March | 0.417983E+10 | 0.101091E+10 | 236.70 | 0.279740E+10 | 0.138243E+10 | 0.00 | 1.00 | 04-MAR-19:01 | 0.00 | 01-MAR-00:10 | 27840.12 | 31-MAR-20:02 | 21855.18 | 04-MAR-19:01 | 14941.73 | 31-MAR-20:02 | 5563.49 | 31-MAR-20:02 | 0.00 | 01-MAR-00:10 |
April | 0.749205E+10 | 0.181943E+10 | 383.35 | 0.509295E+10 | 0.239910E+10 | 0.00 | 1.00 | 08-APR-18:02 | 0.00 | 01-APR-00:10 | 26861.74 | 18-APR-21:03 | 22672.89 | 17-APR-20:01 | 11416.60 | 08-APR-18:10 | 5427.35 | 18-APR-21:03 | 0.00 | 01-APR-00:10 |
May | 0.154468E+11 | 0.370659E+10 | 495.38 | 0.980293E+10 | 0.564383E+10 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 28091.34 | 21-MAY-07:02 | 21482.53 | 30-MAY-07:02 | 10420.07 | 21-MAY-07:02 | 5901.79 | 22-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.163095E+11 | 0.389733E+10 | 483.43 | 0.102561E+11 | 0.605344E+10 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 27519.88 | 04-JUN-07:02 | 22199.74 | 26-JUN-07:02 | 8487.19 | 04-JUN-07:02 | 5986.57 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.183915E+11 | 0.432198E+10 | 498.90 | 0.107907E+11 | 0.760075E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 28130.19 | 03-JUL-07:02 | 21229.06 | 09-JUL-07:02 | 10393.03 | 02-JUL-07:02 | 5977.97 | 04-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.181547E+11 | 0.426744E+10 | 498.57 | 0.109784E+11 | 0.717629E+10 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 28262.00 | 16-AUG-07:02 | 22382.79 | 31-AUG-07:02 | 10748.84 | 16-AUG-07:02 | 5902.95 | 10-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.162286E+11 | 0.377422E+10 | 482.09 | 0.956434E+10 | 0.666424E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 28571.35 | 05-SEP-07:02 | 21838.68 | 01-SEP-07:02 | 16438.87 | 07-SEP-20:03 | 6302.06 | 10-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.140246E+11 | 0.328250E+10 | 455.35 | 0.886121E+10 | 0.516340E+10 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 28239.14 | 08-OCT-07:02 | 22676.70 | 26-OCT-20:01 | 9991.96 | 08-OCT-07:02 | 5934.87 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.574429E+10 | 0.136029E+10 | 291.92 | 0.374792E+10 | 0.199636E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 27546.72 | 29-NOV-21:44 | 19309.30 | 02-NOV-07:03 | 14307.79 | 29-NOV-21:44 | 5527.35 | 29-NOV-21:44 | 0.00 | 01-NOV-00:10 |
December | 0.374111E+10 | 0.889313E+09 | 195.10 | 0.243338E+10 | 0.130773E+10 | 0.00 | 1.00 | 08-DEC-21:52 | 0.00 | 01-DEC-00:10 | 27287.67 | 08-DEC-22:00 | 16330.25 | 11-DEC-08:62 | 13593.36 | 08-DEC-22:00 | 5492.05 | 08-DEC-22:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.124813E+12 | 0.295545E+11 | 4325.30 | 0.776202E+11 | 0.471924E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.222736E+10 | 0.535129E+09 | 133.41 | 0.144578E+10 | 0.781580E+09 | 0.00 | 1.00 | 0.00 | 26861.74 | 14586.02 | 8487.19 | 5427.35 | 0.00 | |||||||
Maximum of Months | 0.183915E+11 | 0.432198E+10 | 498.90 | 0.109784E+11 | 0.760075E+10 | 0.00 | 1.00 | 0.00 | 28571.35 | 22676.70 | 16438.87 | 6302.06 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.168443E+10 | 0.408191E+09 | 104.67 | 0.108814E+10 | 0.596285E+09 | 0.00 | 0.75 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 9650.85 | 19-JAN-14:00 | 6409.90 | 01-JAN-14:00 | 5141.81 | 20-JAN-07:03 | 2185.20 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.231337E+10 | 0.557354E+09 | 142.31 | 0.147278E+10 | 0.840584E+09 | 0.00 | 0.81 | 28-FEB-07:03 | 0.00 | 01-FEB-00:10 | 10599.43 | 28-FEB-07:03 | 6565.38 | 02-FEB-13:30 | 5470.27 | 28-FEB-07:03 | 2336.36 | 24-FEB-13:30 | 0.00 | 01-FEB-00:10 |
March | 0.326772E+10 | 0.794682E+09 | 189.19 | 0.216232E+10 | 0.110540E+10 | 0.00 | 0.99 | 30-MAR-06:03 | 0.00 | 01-MAR-00:10 | 13796.83 | 30-MAR-06:03 | 8886.71 | 30-MAR-06:03 | 5721.93 | 27-MAR-06:03 | 2774.61 | 30-MAR-06:03 | 0.00 | 01-MAR-00:10 |
April | 0.583037E+10 | 0.142055E+10 | 294.21 | 0.392741E+10 | 0.190296E+10 | 0.00 | 1.00 | 22-APR-06:03 | 0.00 | 01-APR-00:10 | 28963.02 | 30-APR-07:03 | 16720.06 | 29-APR-06:03 | 16082.95 | 30-APR-07:03 | 5786.07 | 29-APR-06:03 | 0.00 | 01-APR-00:10 |
May | 0.125590E+11 | 0.300104E+10 | 367.29 | 0.781841E+10 | 0.474058E+10 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:10 | 29793.81 | 21-MAY-07:02 | 19376.04 | 12-MAY-06:02 | 15638.92 | 21-MAY-07:02 | 6005.75 | 28-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.134188E+11 | 0.318670E+10 | 358.76 | 0.826390E+10 | 0.515486E+10 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 30214.43 | 19-JUN-06:02 | 19784.75 | 14-JUN-06:02 | 17125.71 | 19-JUN-06:02 | 6116.08 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.148438E+11 | 0.345981E+10 | 362.87 | 0.849098E+10 | 0.635283E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 30431.28 | 05-JUL-06:02 | 18180.26 | 19-JUL-06:02 | 17369.76 | 05-JUL-06:02 | 6152.26 | 09-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.150152E+11 | 0.350165E+10 | 373.23 | 0.886180E+10 | 0.615338E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 30431.28 | 14-AUG-06:02 | 20170.78 | 31-AUG-06:02 | 17868.33 | 14-AUG-06:03 | 6003.58 | 06-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.130807E+11 | 0.301469E+10 | 354.02 | 0.749220E+10 | 0.558850E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 30457.11 | 05-SEP-06:02 | 18925.17 | 23-SEP-06:02 | 17479.22 | 05-SEP-06:02 | 6386.56 | 10-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.111986E+11 | 0.260743E+10 | 336.85 | 0.692777E+10 | 0.427086E+10 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 30169.91 | 08-OCT-07:02 | 21669.24 | 26-OCT-06:02 | 16168.97 | 08-OCT-07:03 | 6030.15 | 07-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.462488E+10 | 0.109826E+10 | 243.45 | 0.299300E+10 | 0.163188E+10 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 28861.78 | 02-NOV-06:03 | 18016.30 | 01-NOV-06:03 | 15589.93 | 04-NOV-06:03 | 5804.40 | 02-NOV-06:03 | 0.00 | 01-NOV-00:10 |
December | 0.301993E+10 | 0.717788E+09 | 157.22 | 0.193334E+10 | 0.108659E+10 | 0.00 | 1.00 | 11-DEC-07:03 | 0.00 | 01-DEC-00:10 | 28778.27 | 15-DEC-07:03 | 17591.86 | 11-DEC-07:03 | 16375.48 | 16-DEC-07:03 | 5691.68 | 15-DEC-07:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.100857E+12 | 0.237681E+11 | 3284.07 | 0.614321E+11 | 0.394247E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.168443E+10 | 0.408191E+09 | 104.67 | 0.108814E+10 | 0.596285E+09 | 0.00 | 0.75 | 0.00 | 9650.85 | 6409.90 | 5141.81 | 2185.20 | 0.00 | |||||||
Maximum of Months | 0.150152E+11 | 0.350165E+10 | 373.23 | 0.886180E+10 | 0.635283E+10 | 0.00 | 1.00 | 0.00 | 30457.11 | 21669.24 | 17868.33 | 6386.56 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.163341E+10 | 0.396626E+09 | 101.67 | 0.105180E+10 | 0.581607E+09 | 0.00 | 0.74 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 9580.76 | 19-JAN-14:00 | 6399.59 | 01-JAN-14:00 | 4899.20 | 20-JAN-07:03 | 2173.70 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.226126E+10 | 0.545704E+09 | 138.14 | 0.143622E+10 | 0.825038E+09 | 0.00 | 0.79 | 28-FEB-07:03 | 0.00 | 01-FEB-00:10 | 10194.67 | 28-FEB-07:03 | 6532.72 | 02-FEB-13:30 | 5263.92 | 28-FEB-07:03 | 2328.75 | 24-FEB-13:10 | 0.00 | 01-FEB-00:10 |
March | 0.322480E+10 | 0.785211E+09 | 189.19 | 0.212968E+10 | 0.109512E+10 | 0.00 | 0.98 | 30-MAR-06:03 | 0.00 | 01-MAR-00:10 | 13635.15 | 30-MAR-06:03 | 8773.72 | 30-MAR-06:03 | 5458.54 | 27-MAR-06:03 | 2752.78 | 30-MAR-06:03 | 0.00 | 01-MAR-00:10 |
April | 0.580948E+10 | 0.141657E+10 | 292.37 | 0.391097E+10 | 0.189851E+10 | 0.00 | 1.00 | 22-APR-06:03 | 0.00 | 01-APR-00:10 | 29081.63 | 30-APR-07:03 | 16793.44 | 29-APR-06:03 | 16144.28 | 30-APR-07:03 | 5809.74 | 29-APR-06:03 | 0.00 | 01-APR-00:10 |
May | 0.126016E+11 | 0.301230E+10 | 367.26 | 0.785102E+10 | 0.475055E+10 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:10 | 29917.10 | 21-MAY-07:02 | 19489.34 | 12-MAY-06:02 | 15688.95 | 21-MAY-07:02 | 6030.19 | 28-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.134726E+11 | 0.320023E+10 | 358.99 | 0.830539E+10 | 0.516723E+10 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 30343.97 | 19-JUN-06:02 | 19910.48 | 14-JUN-06:02 | 17148.19 | 19-JUN-06:02 | 6141.05 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.149185E+11 | 0.347770E+10 | 363.08 | 0.854673E+10 | 0.637178E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 30555.02 | 05-JUL-06:02 | 18296.17 | 19-JUL-06:02 | 17356.03 | 05-JUL-06:03 | 6177.36 | 09-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.150804E+11 | 0.351738E+10 | 373.39 | 0.891114E+10 | 0.616931E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 30555.02 | 14-AUG-06:02 | 20294.37 | 31-AUG-06:02 | 17873.71 | 14-AUG-06:03 | 6027.86 | 06-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.131417E+11 | 0.302919E+10 | 354.31 | 0.753753E+10 | 0.560417E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 30592.99 | 05-SEP-06:02 | 19031.73 | 23-SEP-06:02 | 17473.95 | 05-SEP-06:02 | 6412.51 | 10-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.112396E+11 | 0.261756E+10 | 336.88 | 0.695940E+10 | 0.428020E+10 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 30301.16 | 08-OCT-07:02 | 21761.95 | 26-OCT-06:02 | 16188.27 | 08-OCT-07:03 | 6054.70 | 07-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.460293E+10 | 0.109380E+10 | 241.95 | 0.297796E+10 | 0.162496E+10 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 28982.60 | 02-NOV-06:03 | 18074.55 | 01-NOV-06:03 | 15650.49 | 04-NOV-06:03 | 5828.21 | 02-NOV-06:03 | 0.00 | 01-NOV-00:10 |
December | 0.299433E+10 | 0.712069E+09 | 155.22 | 0.191393E+10 | 0.108040E+10 | 0.00 | 1.00 | 11-DEC-07:03 | 0.00 | 01-DEC-00:10 | 28897.70 | 15-DEC-07:03 | 17656.38 | 11-DEC-07:03 | 16513.26 | 16-DEC-07:03 | 5715.03 | 15-DEC-07:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.100981E+12 | 0.238043E+11 | 3272.44 | 0.615318E+11 | 0.394489E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.163341E+10 | 0.396626E+09 | 101.67 | 0.105180E+10 | 0.581607E+09 | 0.00 | 0.74 | 0.00 | 9580.76 | 6399.59 | 4899.20 | 2173.70 | 0.00 | |||||||
Maximum of Months | 0.150804E+11 | 0.351738E+10 | 373.39 | 0.891114E+10 | 0.637178E+10 | 0.00 | 1.00 | 0.00 | 30592.99 | 21761.95 | 17873.71 | 6412.51 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.150821E+10 | 0.367590E+09 | 96.50 | 0.965492E+09 | 0.542716E+09 | 0.00 | 0.73 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 9347.01 | 19-JAN-14:00 | 6279.65 | 01-JAN-14:00 | 3916.69 | 19-JAN-14:00 | 2126.72 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.212783E+10 | 0.514913E+09 | 131.47 | 0.134404E+10 | 0.783798E+09 | 0.00 | 0.76 | 24-FEB-14:00 | 0.00 | 01-FEB-00:10 | 9737.71 | 24-FEB-14:00 | 6374.84 | 02-FEB-13:30 | 3987.89 | 28-FEB-07:03 | 2283.61 | 24-FEB-13:10 | 0.00 | 01-FEB-00:10 |
March | 0.307446E+10 | 0.750549E+09 | 183.94 | 0.201887E+10 | 0.105559E+10 | 0.00 | 0.87 | 30-MAR-06:03 | 0.00 | 01-MAR-00:10 | 11583.33 | 30-MAR-06:03 | 7383.37 | 30-MAR-06:03 | 4199.96 | 30-MAR-06:03 | 2543.46 | 30-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.560051E+10 | 0.136797E+10 | 286.54 | 0.375524E+10 | 0.184527E+10 | 0.00 | 1.00 | 24-APR-06:03 | 0.00 | 01-APR-00:10 | 28877.76 | 30-APR-07:03 | 16054.40 | 29-APR-06:03 | 16055.35 | 30-APR-07:03 | 5705.29 | 30-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.123932E+11 | 0.296532E+10 | 367.09 | 0.769479E+10 | 0.469838E+10 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:10 | 29696.25 | 21-MAY-07:02 | 19226.94 | 12-MAY-06:02 | 15694.63 | 21-MAY-07:02 | 5988.44 | 28-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.132794E+11 | 0.315608E+10 | 358.87 | 0.815812E+10 | 0.512130E+10 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 30123.99 | 19-JUN-06:02 | 19631.71 | 14-JUN-06:02 | 17135.63 | 19-JUN-06:02 | 6098.47 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.147256E+11 | 0.343342E+10 | 362.80 | 0.840516E+10 | 0.632039E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 30344.02 | 05-JUL-06:02 | 18018.56 | 19-JUL-06:02 | 17331.11 | 05-JUL-06:02 | 6134.62 | 09-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.148850E+11 | 0.347251E+10 | 372.67 | 0.876513E+10 | 0.611983E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 30344.02 | 14-AUG-06:02 | 20018.02 | 31-AUG-06:02 | 17838.44 | 14-AUG-06:03 | 5986.44 | 06-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.129552E+11 | 0.298763E+10 | 353.93 | 0.740191E+10 | 0.555333E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 30374.12 | 05-SEP-06:02 | 18777.14 | 23-SEP-06:02 | 17410.70 | 05-SEP-06:02 | 6368.18 | 10-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.110675E+11 | 0.257868E+10 | 335.49 | 0.682872E+10 | 0.423882E+10 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 30081.39 | 08-OCT-07:02 | 21578.22 | 26-OCT-06:02 | 16152.60 | 08-OCT-07:03 | 6012.87 | 07-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.444876E+10 | 0.105821E+10 | 233.54 | 0.286241E+10 | 0.158635E+10 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 28779.17 | 02-NOV-06:03 | 17316.60 | 03-NOV-06:02 | 15583.83 | 04-NOV-06:03 | 5787.77 | 02-NOV-06:03 | 0.00 | 01-NOV-00:10 |
December | 0.288773E+10 | 0.687622E+09 | 148.14 | 0.183523E+10 | 0.105250E+10 | 0.00 | 1.00 | 11-DEC-07:03 | 0.00 | 01-DEC-00:10 | 26552.90 | 11-DEC-07:03 | 16187.85 | 11-DEC-07:03 | 14895.10 | 16-DEC-07:03 | 5267.55 | 11-DEC-07:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.989534E+11 | 0.233405E+11 | 3230.99 | 0.600351E+11 | 0.389183E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.150821E+10 | 0.367590E+09 | 96.50 | 0.965492E+09 | 0.542716E+09 | 0.00 | 0.73 | 0.00 | 9347.01 | 6279.65 | 3916.69 | 2126.72 | 0.00 | |||||||
Maximum of Months | 0.148850E+11 | 0.347251E+10 | 372.67 | 0.876513E+10 | 0.632039E+10 | 0.00 | 1.00 | 0.00 | 30374.12 | 21578.22 | 17838.44 | 6368.18 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.258525E+10 | 0.637035E+09 | 89.83 | 0.161423E+10 | 0.971019E+09 | 0.00 | 0.77 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 17993.39 | 19-JAN-14:00 | 11084.89 | 01-JAN-14:10 | 7946.24 | 19-JAN-14:00 | 4094.67 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.381161E+10 | 0.931794E+09 | 120.39 | 0.234534E+10 | 0.146628E+10 | 0.00 | 0.80 | 24-FEB-13:50 | 0.00 | 01-FEB-00:10 | 18780.36 | 24-FEB-13:50 | 12026.64 | 02-FEB-13:30 | 7190.49 | 24-FEB-13:10 | 4396.32 | 24-FEB-13:30 | 0.00 | 01-FEB-00:10 |
March | 0.551951E+10 | 0.135891E+10 | 176.72 | 0.352759E+10 | 0.199192E+10 | 0.00 | 0.88 | 30-MAR-13:00 | 0.00 | 01-MAR-00:10 | 21052.01 | 30-MAR-13:00 | 12808.78 | 26-MAR-14:00 | 8521.34 | 07-MAR-13:50 | 4926.87 | 30-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.103498E+11 | 0.254565E+10 | 281.24 | 0.680295E+10 | 0.354686E+10 | 0.00 | 1.00 | 24-APR-07:03 | 0.00 | 01-APR-00:10 | 45274.91 | 29-APR-07:03 | 26458.63 | 29-APR-07:03 | 19344.43 | 30-APR-08:63 | 9403.12 | 29-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.231180E+11 | 0.553849E+10 | 357.08 | 0.140581E+11 | 0.905982E+10 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 53207.86 | 21-MAY-08:62 | 34001.94 | 12-MAY-07:03 | 28624.08 | 21-MAY-08:62 | 11033.31 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.249498E+11 | 0.594740E+10 | 350.76 | 0.150224E+11 | 0.992733E+10 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 53760.51 | 19-JUN-07:02 | 35735.50 | 14-JUN-07:02 | 30785.53 | 19-JUN-07:02 | 11130.25 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.275915E+11 | 0.646031E+10 | 351.39 | 0.153720E+11 | 0.122195E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 54213.62 | 03-JUL-07:02 | 33802.95 | 19-JUL-07:02 | 31566.30 | 02-JUL-08:62 | 11308.22 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.280493E+11 | 0.658180E+10 | 363.89 | 0.161525E+11 | 0.118968E+11 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 54212.43 | 14-AUG-07:02 | 37148.82 | 31-AUG-07:02 | 31995.24 | 14-AUG-07:03 | 11084.95 | 06-AUG-08:03 | 0.00 | 01-AUG-00:10 |
September | 0.241281E+11 | 0.557505E+10 | 343.07 | 0.133925E+11 | 0.107357E+11 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 54280.11 | 05-SEP-07:02 | 34029.22 | 01-SEP-07:02 | 31262.54 | 05-SEP-07:02 | 11745.17 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.208097E+11 | 0.486983E+10 | 326.81 | 0.125381E+11 | 0.827161E+10 | 0.00 | 1.00 | 01-OCT-08:63 | 0.00 | 01-OCT-00:10 | 53805.81 | 08-OCT-08:62 | 39578.85 | 26-OCT-07:02 | 29436.19 | 22-OCT-08:62 | 10957.03 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.818877E+10 | 0.195726E+10 | 222.74 | 0.512211E+10 | 0.306666E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 50939.36 | 02-NOV-07:03 | 32541.02 | 03-NOV-07:03 | 24129.29 | 08-NOV-08:62 | 10469.77 | 02-NOV-07:03 | 0.00 | 01-NOV-00:10 |
December | 0.527643E+10 | 0.126208E+10 | 136.88 | 0.326446E+10 | 0.201197E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 46573.61 | 11-DEC-08:62 | 27906.21 | 11-DEC-08:62 | 18667.40 | 11-DEC-08:62 | 9400.23 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.184378E+12 | 0.436656E+11 | 3120.80 | 0.109212E+12 | 0.751655E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.258525E+10 | 0.637035E+09 | 89.83 | 0.161423E+10 | 0.971019E+09 | 0.00 | 0.77 | 0.00 | 17993.39 | 11084.89 | 7190.49 | 4094.67 | 0.00 | |||||||
Maximum of Months | 0.280493E+11 | 0.658180E+10 | 363.89 | 0.161525E+11 | 0.122195E+11 | 0.00 | 1.00 | 0.00 | 54280.11 | 39578.85 | 31995.24 | 11745.17 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.130748E+10 | 0.317055E+09 | 88.08 | 0.815925E+09 | 0.491554E+09 | 0.00 | 0.76 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 9279.82 | 19-JAN-14:00 | 5765.52 | 01-JAN-14:10 | 4106.31 | 19-JAN-14:00 | 2081.53 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.193899E+10 | 0.466553E+09 | 117.56 | 0.119271E+10 | 0.746284E+09 | 0.00 | 0.80 | 24-FEB-14:00 | 0.00 | 01-FEB-00:10 | 9736.18 | 24-FEB-13:50 | 6240.71 | 02-FEB-13:30 | 3739.50 | 24-FEB-13:10 | 2245.04 | 24-FEB-13:30 | 0.00 | 01-FEB-00:10 |
March | 0.281852E+10 | 0.682841E+09 | 173.56 | 0.179669E+10 | 0.102183E+10 | 0.00 | 0.88 | 30-MAR-13:00 | 0.00 | 01-MAR-00:10 | 11028.25 | 30-MAR-13:00 | 6687.25 | 26-MAR-14:00 | 4420.41 | 07-MAR-13:50 | 2537.76 | 30-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.533930E+10 | 0.129211E+10 | 277.40 | 0.350987E+10 | 0.182943E+10 | 0.00 | 1.00 | 24-APR-07:03 | 0.00 | 01-APR-00:10 | 21644.92 | 29-APR-07:03 | 12635.56 | 29-APR-07:03 | 9316.67 | 30-APR-08:63 | 4419.32 | 29-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.120466E+11 | 0.284006E+10 | 357.78 | 0.732783E+10 | 0.471876E+10 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 27951.24 | 21-MAY-08:62 | 17883.18 | 31-MAY-07:03 | 15092.05 | 21-MAY-08:62 | 5691.37 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.130087E+11 | 0.305181E+10 | 351.64 | 0.783247E+10 | 0.517620E+10 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 28273.06 | 19-JUN-07:02 | 18770.90 | 14-JUN-07:02 | 16310.31 | 19-JUN-07:02 | 5741.67 | 18-JUN-08:03 | 0.00 | 01-JUN-00:10 |
July | 0.143930E+11 | 0.331765E+10 | 351.79 | 0.801920E+10 | 0.637377E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 28499.44 | 03-JUL-07:02 | 17757.16 | 19-JUL-07:02 | 16692.53 | 02-JUL-08:03 | 5833.29 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.146192E+11 | 0.337679E+10 | 364.17 | 0.841844E+10 | 0.620077E+10 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 28465.13 | 14-AUG-07:02 | 19513.02 | 31-AUG-07:02 | 16948.02 | 14-AUG-07:03 | 5716.81 | 06-AUG-08:03 | 0.00 | 01-AUG-00:10 |
September | 0.125616E+11 | 0.285652E+10 | 343.19 | 0.697344E+10 | 0.558818E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 28517.06 | 05-SEP-07:02 | 17868.81 | 01-SEP-07:02 | 16472.25 | 05-SEP-07:02 | 6058.63 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.108220E+11 | 0.249193E+10 | 326.93 | 0.651793E+10 | 0.430409E+10 | 0.00 | 1.00 | 03-OCT-07:03 | 0.00 | 01-OCT-00:10 | 28268.21 | 08-OCT-08:62 | 20800.68 | 26-OCT-07:02 | 15573.84 | 22-OCT-08:62 | 5652.02 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.421435E+10 | 0.990611E+09 | 217.40 | 0.263153E+10 | 0.158281E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 25108.91 | 02-NOV-07:03 | 15674.60 | 03-NOV-07:03 | 11533.61 | 08-NOV-08:62 | 5072.57 | 02-NOV-07:03 | 0.00 | 01-NOV-00:10 |
December | 0.271483E+10 | 0.638708E+09 | 133.71 | 0.167722E+10 | 0.103761E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 22729.20 | 11-DEC-08:62 | 13528.70 | 11-DEC-08:62 | 9200.50 | 11-DEC-08:62 | 4506.45 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.957846E+11 | 0.223226E+11 | 3103.19 | 0.567133E+11 | 0.390713E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.130748E+10 | 0.317055E+09 | 88.08 | 0.815925E+09 | 0.491554E+09 | 0.00 | 0.76 | 0.00 | 9279.82 | 5765.52 | 3739.50 | 2081.53 | 0.00 | |||||||
Maximum of Months | 0.146192E+11 | 0.337679E+10 | 364.17 | 0.841844E+10 | 0.637377E+10 | 0.00 | 1.00 | 0.00 | 28517.06 | 20800.68 | 16948.02 | 6058.63 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.127564E+10 | 0.309588E+09 | 87.08 | 0.794717E+09 | 0.480927E+09 | 0.00 | 0.75 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 9190.43 | 19-JAN-14:00 | 5710.27 | 01-JAN-14:10 | 4076.09 | 19-JAN-14:00 | 2063.27 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.189405E+10 | 0.456133E+09 | 116.47 | 0.116304E+10 | 0.731013E+09 | 0.00 | 0.79 | 24-FEB-14:00 | 0.00 | 01-FEB-00:10 | 9647.28 | 24-FEB-13:50 | 6182.17 | 02-FEB-13:30 | 3718.38 | 24-FEB-13:10 | 2226.63 | 24-FEB-13:10 | 0.00 | 01-FEB-00:10 |
March | 0.276497E+10 | 0.670296E+09 | 170.31 | 0.175747E+10 | 0.100751E+10 | 0.00 | 0.87 | 30-MAR-13:00 | 0.00 | 01-MAR-00:10 | 10966.89 | 30-MAR-13:00 | 6611.62 | 26-MAR-14:00 | 4385.50 | 07-MAR-13:50 | 2523.94 | 30-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.527504E+10 | 0.127695E+10 | 275.40 | 0.346312E+10 | 0.181192E+10 | 0.00 | 1.00 | 28-APR-12:30 | 0.00 | 01-APR-00:10 | 21042.09 | 29-APR-07:03 | 12236.10 | 29-APR-07:03 | 8997.39 | 30-APR-08:63 | 4296.25 | 29-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.119823E+11 | 0.282462E+10 | 357.61 | 0.728147E+10 | 0.470083E+10 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 27830.76 | 21-MAY-08:62 | 17771.47 | 31-MAY-07:03 | 15053.72 | 21-MAY-08:62 | 5667.43 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.129501E+11 | 0.303748E+10 | 351.71 | 0.778938E+10 | 0.516068E+10 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 28152.01 | 19-JUN-07:02 | 18665.93 | 14-JUN-07:02 | 16267.74 | 19-JUN-07:02 | 5717.49 | 18-JUN-08:03 | 0.00 | 01-JUN-00:10 |
July | 0.143390E+11 | 0.330447E+10 | 351.85 | 0.798091E+10 | 0.635805E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 28378.19 | 03-JUL-07:02 | 17653.43 | 19-JUL-07:02 | 16646.11 | 02-JUL-08:62 | 5808.72 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.145669E+11 | 0.336395E+10 | 364.17 | 0.838060E+10 | 0.618626E+10 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 28345.25 | 14-AUG-07:02 | 19404.67 | 31-AUG-07:02 | 16887.26 | 14-AUG-07:03 | 5692.71 | 06-AUG-08:03 | 0.00 | 01-AUG-00:10 |
September | 0.125083E+11 | 0.284385E+10 | 343.17 | 0.693620E+10 | 0.557209E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 28396.96 | 05-SEP-07:02 | 17757.49 | 01-SEP-07:02 | 16411.37 | 05-SEP-07:02 | 6033.06 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.107677E+11 | 0.247904E+10 | 326.79 | 0.647817E+10 | 0.428955E+10 | 0.00 | 1.00 | 03-OCT-07:03 | 0.00 | 01-OCT-00:10 | 28147.58 | 08-OCT-08:62 | 20705.22 | 26-OCT-07:02 | 15530.18 | 22-OCT-08:62 | 5628.22 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.416649E+10 | 0.979320E+09 | 215.32 | 0.259603E+10 | 0.157046E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 24558.42 | 02-NOV-07:03 | 15316.07 | 03-NOV-07:03 | 11253.34 | 08-NOV-08:62 | 4961.15 | 02-NOV-07:03 | 0.00 | 01-NOV-00:10 |
December | 0.267922E+10 | 0.630462E+09 | 132.54 | 0.165138E+10 | 0.102783E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 21762.04 | 11-DEC-08:62 | 12909.14 | 11-DEC-08:62 | 8852.90 | 11-DEC-08:62 | 4315.61 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.951696E+11 | 0.221762E+11 | 3092.41 | 0.562725E+11 | 0.388971E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.127564E+10 | 0.309588E+09 | 87.08 | 0.794717E+09 | 0.480927E+09 | 0.00 | 0.75 | 0.00 | 9190.43 | 5710.27 | 3718.38 | 2063.27 | 0.00 | |||||||
Maximum of Months | 0.145669E+11 | 0.336395E+10 | 364.17 | 0.838060E+10 | 0.635805E+10 | 0.00 | 1.00 | 0.00 | 28396.96 | 20705.22 | 16887.26 | 6033.06 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.121114E+10 | 0.294652E+09 | 84.58 | 0.752341E+09 | 0.458798E+09 | 0.00 | 0.74 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 9068.82 | 19-JAN-14:00 | 5615.42 | 01-JAN-14:10 | 4033.73 | 19-JAN-14:00 | 2041.99 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.179465E+10 | 0.433506E+09 | 113.42 | 0.109895E+10 | 0.695694E+09 | 0.00 | 0.78 | 24-FEB-14:00 | 0.00 | 01-FEB-00:10 | 9491.88 | 24-FEB-14:00 | 6062.62 | 02-FEB-13:30 | 3681.83 | 24-FEB-13:10 | 2198.48 | 24-FEB-13:10 | 0.00 | 01-FEB-00:10 |
March | 0.265151E+10 | 0.644460E+09 | 165.25 | 0.167550E+10 | 0.976012E+09 | 0.00 | 0.87 | 30-MAR-13:00 | 0.00 | 01-MAR-00:10 | 10862.24 | 30-MAR-13:00 | 6508.37 | 30-MAR-13:00 | 4353.87 | 30-MAR-13:00 | 2506.53 | 30-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.512516E+10 | 0.124327E+10 | 269.07 | 0.335564E+10 | 0.176952E+10 | 0.00 | 1.00 | 28-APR-12:40 | 0.00 | 01-APR-00:10 | 18196.11 | 29-APR-07:03 | 10441.48 | 29-APR-07:03 | 7801.11 | 30-APR-08:63 | 3718.12 | 29-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.119106E+11 | 0.281037E+10 | 357.43 | 0.723090E+10 | 0.467971E+10 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 27913.48 | 21-MAY-08:62 | 17742.32 | 31-MAY-07:03 | 15195.11 | 21-MAY-08:62 | 5687.40 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.129185E+11 | 0.303168E+10 | 351.90 | 0.776575E+10 | 0.515277E+10 | 0.00 | 1.00 | 02-JUN-07:03 | 0.00 | 01-JUN-00:10 | 28235.80 | 19-JUN-07:02 | 18678.08 | 14-JUN-07:02 | 16409.68 | 19-JUN-07:02 | 5737.43 | 18-JUN-08:03 | 0.00 | 01-JUN-00:10 |
July | 0.143461E+11 | 0.330742E+10 | 352.00 | 0.798700E+10 | 0.635906E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 28471.15 | 03-JUL-07:02 | 17696.66 | 19-JUL-07:02 | 16746.50 | 02-JUL-08:62 | 5829.07 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.145976E+11 | 0.337187E+10 | 364.64 | 0.840305E+10 | 0.619453E+10 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 28444.36 | 14-AUG-07:02 | 19459.51 | 31-AUG-07:02 | 16973.22 | 14-AUG-07:03 | 5712.95 | 06-AUG-08:03 | 0.00 | 01-AUG-00:10 |
September | 0.125128E+11 | 0.284599E+10 | 342.97 | 0.693985E+10 | 0.557300E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 28495.60 | 05-SEP-07:02 | 17804.83 | 01-SEP-07:02 | 16483.39 | 05-SEP-07:02 | 6054.12 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.107435E+11 | 0.247465E+10 | 324.94 | 0.646025E+10 | 0.428326E+10 | 0.00 | 1.00 | 03-OCT-07:03 | 0.00 | 01-OCT-00:10 | 28241.28 | 08-OCT-08:62 | 20720.14 | 26-OCT-07:02 | 15633.21 | 22-OCT-08:62 | 5647.62 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.406199E+10 | 0.955397E+09 | 210.74 | 0.251850E+10 | 0.154349E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 22821.92 | 02-NOV-07:03 | 14321.66 | 03-NOV-07:03 | 10296.04 | 08-NOV-08:62 | 4611.70 | 02-NOV-07:03 | 0.00 | 01-NOV-00:10 |
December | 0.260697E+10 | 0.614615E+09 | 128.63 | 0.159922E+10 | 0.100775E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 18830.21 | 11-DEC-08:62 | 11051.01 | 11-DEC-08:62 | 7779.20 | 11-DEC-08:62 | 3737.23 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.944806E+11 | 0.220279E+11 | 3065.56 | 0.557869E+11 | 0.386936E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.121114E+10 | 0.294652E+09 | 84.58 | 0.752341E+09 | 0.458798E+09 | 0.00 | 0.74 | 0.00 | 9068.82 | 5615.42 | 3681.83 | 2041.99 | 0.00 | |||||||
Maximum of Months | 0.145976E+11 | 0.337187E+10 | 364.64 | 0.840305E+10 | 0.635906E+10 | 0.00 | 1.00 | 0.00 | 28495.60 | 20720.14 | 16973.22 | 6054.12 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.129307E+10 | 0.317389E+09 | 81.42 | 0.810573E+09 | 0.482502E+09 | 0.00 | 0.72 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 10038.46 | 19-JAN-14:00 | 6075.92 | 01-JAN-14:10 | 4331.36 | 19-JAN-14:00 | 2285.40 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.189805E+10 | 0.463822E+09 | 109.00 | 0.117205E+10 | 0.726003E+09 | 0.00 | 0.74 | 24-FEB-13:10 | 0.00 | 01-FEB-00:10 | 10380.75 | 24-FEB-13:10 | 6533.73 | 02-FEB-13:10 | 3942.25 | 24-FEB-13:10 | 2444.01 | 24-FEB-13:10 | 0.00 | 01-FEB-00:10 |
March | 0.286752E+10 | 0.703508E+09 | 160.92 | 0.182674E+10 | 0.104078E+10 | 0.00 | 0.82 | 30-MAR-13:00 | 0.00 | 01-MAR-00:10 | 11766.91 | 30-MAR-13:00 | 7157.94 | 26-MAR-14:00 | 4643.85 | 07-MAR-13:40 | 2764.76 | 30-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.547974E+10 | 0.134406E+10 | 261.53 | 0.362334E+10 | 0.185640E+10 | 0.00 | 1.00 | 28-APR-16:10 | 0.00 | 01-APR-00:10 | 15678.16 | 28-APR-16:20 | 10010.90 | 28-APR-15:00 | 6657.54 | 29-APR-14:30 | 3590.36 | 28-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 0.131204E+11 | 0.313283E+10 | 358.16 | 0.806408E+10 | 0.505633E+10 | 0.00 | 1.00 | 01-MAY-14:50 | 0.00 | 01-MAY-00:10 | 32595.22 | 21-MAY-08:62 | 17099.25 | 07-MAY-08:62 | 18494.48 | 21-MAY-08:62 | 6597.31 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.143699E+11 | 0.340546E+10 | 352.29 | 0.878238E+10 | 0.558749E+10 | 0.00 | 1.00 | 02-JUN-07:03 | 0.00 | 01-JUN-00:10 | 32940.55 | 19-JUN-07:02 | 20601.68 | 16-JUN-07:02 | 19759.97 | 19-JUN-07:02 | 6675.04 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.160654E+11 | 0.373844E+10 | 353.65 | 0.915646E+10 | 0.690893E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 33083.78 | 03-JUL-07:02 | 19752.41 | 19-JUL-07:02 | 20449.77 | 02-JUL-08:03 | 6767.49 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.164930E+11 | 0.383791E+10 | 366.64 | 0.969668E+10 | 0.679634E+10 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 33037.48 | 07-AUG-07:02 | 23087.15 | 31-AUG-07:02 | 19921.12 | 14-AUG-07:03 | 6624.19 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.140418E+11 | 0.322196E+10 | 344.34 | 0.796439E+10 | 0.607737E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 33096.32 | 05-SEP-07:02 | 20991.81 | 01-SEP-07:02 | 19450.34 | 05-SEP-07:02 | 7012.41 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.120243E+11 | 0.279094E+10 | 323.65 | 0.735033E+10 | 0.467399E+10 | 0.00 | 1.00 | 03-OCT-07:03 | 0.00 | 01-OCT-00:10 | 32995.54 | 08-OCT-08:62 | 20448.38 | 26-OCT-07:02 | 19080.34 | 22-OCT-08:62 | 6570.80 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.439121E+10 | 0.104394E+10 | 201.32 | 0.275359E+10 | 0.163762E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 23969.41 | 02-NOV-07:03 | 13753.22 | 03-NOV-07:03 | 10748.92 | 02-NOV-07:03 | 4805.46 | 02-NOV-07:03 | 0.00 | 01-NOV-00:10 |
December | 0.274906E+10 | 0.657666E+09 | 127.49 | 0.169594E+10 | 0.105312E+10 | 0.00 | 0.89 | 16-DEC-13:00 | 0.00 | 01-DEC-00:10 | 12983.65 | 16-DEC-13:10 | 7978.01 | 16-DEC-13:00 | 5989.71 | 11-DEC-08:62 | 2940.36 | 15-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.104793E+12 | 0.246579E+11 | 3040.39 | 0.628966E+11 | 0.418969E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.129307E+10 | 0.317389E+09 | 81.42 | 0.810573E+09 | 0.482502E+09 | 0.00 | 0.72 | 0.00 | 10038.46 | 6075.92 | 3942.25 | 2285.40 | 0.00 | |||||||
Maximum of Months | 0.164930E+11 | 0.383791E+10 | 366.64 | 0.969668E+10 | 0.690893E+10 | 0.00 | 1.00 | 0.00 | 33096.32 | 23087.15 | 20449.77 | 7012.41 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.39 | 29.52 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 105.12 | 25.47 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 69.02 | 21.96 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.53 | 14.40 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.96 | 3.24 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 50.04 | 2.83 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 52.59 | 1.79 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 61.40 | 3.11 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 69.17 | 4.39 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 99.41 | 8.96 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 113.14 | 20.37 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.89 | 26.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 79.34 | 13.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.96 | 1.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.39 | 29.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.39 | 29.52 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 105.12 | 25.47 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 69.02 | 21.96 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.53 | 14.40 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.96 | 3.24 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 50.04 | 2.83 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 52.59 | 1.79 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 61.40 | 3.11 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 69.17 | 4.39 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 99.41 | 8.96 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 113.14 | 20.37 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.89 | 26.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 79.34 | 13.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.96 | 1.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.39 | 29.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.39 | 29.52 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 105.12 | 25.47 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 69.02 | 21.96 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.53 | 14.40 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.96 | 3.24 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 50.04 | 2.83 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 52.59 | 1.79 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 61.40 | 3.11 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 69.17 | 4.39 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 99.41 | 8.96 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 113.14 | 20.37 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.89 | 26.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 79.34 | 13.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.96 | 1.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.39 | 29.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.39 | 29.52 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 105.12 | 25.47 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 69.02 | 21.96 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.53 | 14.40 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.96 | 3.24 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 50.04 | 2.83 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 52.59 | 1.79 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 61.40 | 3.11 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 69.17 | 4.39 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 99.41 | 8.96 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 113.14 | 20.37 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.89 | 26.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 79.34 | 13.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.96 | 1.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.39 | 29.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.74 | 54.11 | 21.64 | 137.55 | 35.34 | 0.00 | 0.00 | 0.00 |
February | 67.15 | 43.02 | 24.13 | 126.40 | 30.50 | 0.00 | 0.00 | 0.00 |
March | 41.47 | 17.50 | 23.97 | 82.99 | 26.30 | 0.00 | 0.00 | 0.00 |
April | 30.53 | 5.74 | 24.79 | 66.69 | 17.29 | 0.00 | 0.00 | 0.00 |
May | 24.27 | 0.58 | 23.69 | 59.87 | 3.93 | 0.00 | 0.00 | 0.00 |
June | 24.30 | 0.09 | 24.21 | 59.93 | 3.42 | 0.00 | 0.00 | 0.00 |
July | 25.34 | 0.23 | 25.11 | 62.98 | 2.18 | 0.00 | 0.00 | 0.00 |
August | 29.14 | 2.66 | 26.48 | 73.61 | 3.76 | 0.00 | 0.00 | 0.00 |
September | 34.58 | 7.99 | 26.59 | 82.99 | 5.31 | 0.00 | 0.00 | 0.00 |
October | 54.37 | 27.53 | 26.84 | 119.37 | 10.78 | 0.00 | 0.00 | 0.00 |
November | 71.04 | 48.83 | 22.21 | 135.94 | 24.43 | 0.00 | 0.00 | 0.00 |
December | 74.55 | 53.77 | 20.78 | 136.90 | 31.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.93 | 21.73 | 24.20 | 95.28 | 16.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.27 | 0.09 | 20.78 | 59.87 | 2.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.74 | 54.11 | 26.84 | 137.55 | 35.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.74 | 54.11 | 21.64 | 137.55 | 35.34 | 0.00 | 0.00 | 0.00 |
February | 67.15 | 43.02 | 24.13 | 126.40 | 30.50 | 0.00 | 0.00 | 0.00 |
March | 41.47 | 17.50 | 23.97 | 82.99 | 26.30 | 0.00 | 0.00 | 0.00 |
April | 30.53 | 5.74 | 24.79 | 66.69 | 17.29 | 0.00 | 0.00 | 0.00 |
May | 24.27 | 0.58 | 23.69 | 59.87 | 3.93 | 0.00 | 0.00 | 0.00 |
June | 24.30 | 0.09 | 24.21 | 59.93 | 3.42 | 0.00 | 0.00 | 0.00 |
July | 25.34 | 0.23 | 25.11 | 62.98 | 2.18 | 0.00 | 0.00 | 0.00 |
August | 29.14 | 2.66 | 26.48 | 73.61 | 3.76 | 0.00 | 0.00 | 0.00 |
September | 34.58 | 7.99 | 26.59 | 82.99 | 5.31 | 0.00 | 0.00 | 0.00 |
October | 54.37 | 27.53 | 26.84 | 119.37 | 10.78 | 0.00 | 0.00 | 0.00 |
November | 71.04 | 48.83 | 22.21 | 135.94 | 24.43 | 0.00 | 0.00 | 0.00 |
December | 74.55 | 53.77 | 20.78 | 136.90 | 31.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.93 | 21.73 | 24.20 | 95.28 | 16.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.27 | 0.09 | 20.78 | 59.87 | 2.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.74 | 54.11 | 26.84 | 137.55 | 35.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 113.56 | 30.94 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 104.49 | 26.52 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 68.50 | 22.95 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.38 | 14.75 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 50.09 | 3.32 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 50.28 | 2.87 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 52.89 | 1.79 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 61.75 | 3.02 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 69.42 | 4.32 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 99.54 | 8.95 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 112.91 | 20.64 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.43 | 27.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 79.23 | 13.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 50.09 | 1.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 113.56 | 30.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 113.56 | 30.94 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 104.49 | 26.52 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 68.50 | 22.95 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.38 | 14.75 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 50.09 | 3.32 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 50.28 | 2.87 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 52.89 | 1.79 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 61.75 | 3.02 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 69.42 | 4.32 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 99.54 | 8.95 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 112.91 | 20.64 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.43 | 27.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 79.23 | 13.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 50.09 | 1.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 113.56 | 30.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.74 | 54.11 | 21.64 | 136.59 | 37.01 | 0.00 | 0.00 | 0.00 |
February | 67.15 | 43.02 | 24.13 | 125.65 | 31.76 | 0.00 | 0.00 | 0.00 |
March | 41.47 | 17.50 | 23.97 | 82.38 | 27.48 | 0.00 | 0.00 | 0.00 |
April | 30.53 | 5.74 | 24.79 | 66.52 | 17.71 | 0.00 | 0.00 | 0.00 |
May | 24.27 | 0.58 | 23.69 | 60.03 | 4.02 | 0.00 | 0.00 | 0.00 |
June | 24.30 | 0.09 | 24.21 | 60.22 | 3.48 | 0.00 | 0.00 | 0.00 |
July | 25.34 | 0.23 | 25.11 | 63.35 | 2.19 | 0.00 | 0.00 | 0.00 |
August | 29.14 | 2.66 | 26.48 | 74.03 | 3.66 | 0.00 | 0.00 | 0.00 |
September | 34.58 | 7.99 | 26.59 | 83.29 | 5.24 | 0.00 | 0.00 | 0.00 |
October | 54.37 | 27.53 | 26.84 | 119.54 | 10.77 | 0.00 | 0.00 | 0.00 |
November | 71.04 | 48.83 | 22.21 | 135.69 | 24.76 | 0.00 | 0.00 | 0.00 |
December | 74.55 | 53.77 | 20.78 | 136.37 | 32.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.93 | 21.73 | 24.20 | 95.15 | 16.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.27 | 0.09 | 20.78 | 60.03 | 2.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.74 | 54.11 | 26.84 | 136.59 | 37.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 113.75 | 30.98 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 104.61 | 26.74 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 68.52 | 23.34 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.26 | 15.63 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.48 | 4.28 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 49.60 | 3.85 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 51.76 | 2.53 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.98 | 3.95 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.92 | 5.54 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 99.18 | 10.18 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 112.92 | 21.51 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.55 | 27.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 78.92 | 14.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.48 | 2.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 113.75 | 30.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 113.75 | 30.98 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 104.61 | 26.74 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 68.52 | 23.34 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.26 | 15.63 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.48 | 4.28 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 49.60 | 3.85 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 51.76 | 2.53 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.98 | 3.95 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.92 | 5.54 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 99.18 | 10.18 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 112.92 | 21.51 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.55 | 27.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 78.92 | 14.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.48 | 2.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 113.75 | 30.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.33 | 53.81 | 21.52 | 136.06 | 36.86 | 0.00 | 0.00 | 0.00 |
February | 66.79 | 42.79 | 24.00 | 125.11 | 31.84 | 0.00 | 0.00 | 0.00 |
March | 41.24 | 17.40 | 23.84 | 81.95 | 27.79 | 0.00 | 0.00 | 0.00 |
April | 30.36 | 5.71 | 24.65 | 66.01 | 18.65 | 0.00 | 0.00 | 0.00 |
May | 24.13 | 0.58 | 23.56 | 58.99 | 5.14 | 0.00 | 0.00 | 0.00 |
June | 24.16 | 0.09 | 24.08 | 59.11 | 4.62 | 0.00 | 0.00 | 0.00 |
July | 25.21 | 0.23 | 24.97 | 61.68 | 3.06 | 0.00 | 0.00 | 0.00 |
August | 28.98 | 2.65 | 26.34 | 72.73 | 4.74 | 0.00 | 0.00 | 0.00 |
September | 34.39 | 7.94 | 26.45 | 82.26 | 6.65 | 0.00 | 0.00 | 0.00 |
October | 54.07 | 27.38 | 26.69 | 118.48 | 12.16 | 0.00 | 0.00 | 0.00 |
November | 70.65 | 48.57 | 22.09 | 134.96 | 25.64 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 53.48 | 20.66 | 135.77 | 33.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.68 | 21.61 | 24.07 | 94.27 | 17.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.13 | 0.09 | 20.66 | 58.99 | 3.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.33 | 53.81 | 26.69 | 136.06 | 36.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 113.91 | 30.62 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 104.73 | 26.46 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 68.59 | 23.14 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.28 | 15.58 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.46 | 4.35 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 49.57 | 3.93 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 51.70 | 2.62 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.94 | 4.04 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.89 | 5.63 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 99.17 | 10.25 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 112.95 | 21.44 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.63 | 27.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 78.94 | 14.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.46 | 2.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 113.91 | 30.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 113.91 | 30.62 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 104.73 | 26.46 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 68.59 | 23.14 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.28 | 15.58 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.46 | 4.35 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 49.57 | 3.93 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 51.70 | 2.62 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.94 | 4.04 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.89 | 5.63 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 99.17 | 10.25 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 112.95 | 21.44 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.63 | 27.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 78.94 | 14.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.46 | 2.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 113.91 | 30.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.33 | 53.81 | 21.52 | 136.26 | 36.43 | 0.00 | 0.00 | 0.00 |
February | 66.79 | 42.79 | 24.00 | 125.26 | 31.51 | 0.00 | 0.00 | 0.00 |
March | 41.24 | 17.40 | 23.84 | 82.04 | 27.55 | 0.00 | 0.00 | 0.00 |
April | 30.36 | 5.71 | 24.65 | 66.03 | 18.58 | 0.00 | 0.00 | 0.00 |
May | 24.13 | 0.58 | 23.56 | 58.96 | 5.22 | 0.00 | 0.00 | 0.00 |
June | 24.16 | 0.09 | 24.08 | 59.07 | 4.72 | 0.00 | 0.00 | 0.00 |
July | 25.21 | 0.23 | 24.97 | 61.62 | 3.16 | 0.00 | 0.00 | 0.00 |
August | 28.98 | 2.65 | 26.34 | 72.68 | 4.85 | 0.00 | 0.00 | 0.00 |
September | 34.39 | 7.94 | 26.45 | 82.22 | 6.76 | 0.00 | 0.00 | 0.00 |
October | 54.07 | 27.38 | 26.69 | 118.46 | 12.25 | 0.00 | 0.00 | 0.00 |
November | 70.65 | 48.57 | 22.09 | 134.99 | 25.56 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 53.48 | 20.66 | 135.87 | 32.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.68 | 21.61 | 24.07 | 94.30 | 17.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.13 | 0.09 | 20.66 | 58.96 | 3.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.33 | 53.81 | 26.69 | 136.26 | 36.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.17 | 30.15 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 104.94 | 26.08 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 68.76 | 22.80 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.36 | 15.37 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.52 | 4.21 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 49.63 | 3.80 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 51.77 | 2.52 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.99 | 3.92 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.93 | 5.50 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 99.21 | 10.11 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 113.03 | 21.23 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.78 | 27.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 79.04 | 14.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.52 | 2.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.17 | 30.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.17 | 30.15 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 104.94 | 26.08 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 68.76 | 22.80 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.36 | 15.37 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.52 | 4.21 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 49.63 | 3.80 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 51.77 | 2.52 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.99 | 3.92 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.93 | 5.50 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 99.21 | 10.11 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 113.03 | 21.23 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.78 | 27.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 79.04 | 14.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.52 | 2.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.17 | 30.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.33 | 53.81 | 21.52 | 136.56 | 35.88 | 0.00 | 0.00 | 0.00 |
February | 66.79 | 42.79 | 24.00 | 125.51 | 31.06 | 0.00 | 0.00 | 0.00 |
March | 41.24 | 17.40 | 23.84 | 82.24 | 27.15 | 0.00 | 0.00 | 0.00 |
April | 30.36 | 5.71 | 24.65 | 66.13 | 18.34 | 0.00 | 0.00 | 0.00 |
May | 24.13 | 0.58 | 23.56 | 59.04 | 5.05 | 0.00 | 0.00 | 0.00 |
June | 24.16 | 0.09 | 24.08 | 59.14 | 4.56 | 0.00 | 0.00 | 0.00 |
July | 25.21 | 0.23 | 24.97 | 61.70 | 3.04 | 0.00 | 0.00 | 0.00 |
August | 28.98 | 2.65 | 26.34 | 72.75 | 4.71 | 0.00 | 0.00 | 0.00 |
September | 34.39 | 7.94 | 26.45 | 82.27 | 6.61 | 0.00 | 0.00 | 0.00 |
October | 54.07 | 27.38 | 26.69 | 118.51 | 12.08 | 0.00 | 0.00 | 0.00 |
November | 70.65 | 48.57 | 22.09 | 135.09 | 25.31 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 53.48 | 20.66 | 136.04 | 32.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.68 | 21.61 | 24.07 | 94.43 | 17.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.13 | 0.09 | 20.66 | 59.04 | 3.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.33 | 53.81 | 26.69 | 136.56 | 35.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.50 | 29.33 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 105.21 | 25.36 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 68.92 | 22.09 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.27 | 14.87 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.24 | 3.85 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 49.31 | 3.43 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 51.46 | 2.25 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.68 | 3.58 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.59 | 5.17 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 98.98 | 9.77 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 113.00 | 20.80 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.91 | 26.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 78.96 | 13.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.24 | 2.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.50 | 29.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.50 | 29.33 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 105.21 | 25.36 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 68.92 | 22.09 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.27 | 14.87 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.24 | 3.85 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 49.31 | 3.43 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 51.46 | 2.25 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.68 | 3.58 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.59 | 5.17 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 98.98 | 9.77 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 113.00 | 20.80 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.91 | 26.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 78.96 | 13.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.24 | 2.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.50 | 29.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.50 | 29.33 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 105.21 | 25.36 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 68.92 | 22.09 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.27 | 14.87 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.24 | 3.85 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 49.31 | 3.43 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 51.46 | 2.25 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.68 | 3.58 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.59 | 5.17 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 98.98 | 9.77 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 113.00 | 20.80 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.91 | 26.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 78.96 | 13.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.24 | 2.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.50 | 29.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.50 | 29.33 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 105.21 | 25.36 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 68.92 | 22.09 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.27 | 14.87 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.24 | 3.85 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 49.31 | 3.43 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 51.46 | 2.25 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.68 | 3.58 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.59 | 5.17 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 98.98 | 9.77 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 113.00 | 20.80 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.91 | 26.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 78.96 | 13.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.24 | 2.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.50 | 29.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.33 | 53.81 | 21.52 | 136.93 | 34.91 | 0.00 | 0.00 | 0.00 |
February | 66.79 | 42.79 | 24.00 | 125.81 | 30.19 | 0.00 | 0.00 | 0.00 |
March | 41.24 | 17.40 | 23.84 | 82.43 | 26.30 | 0.00 | 0.00 | 0.00 |
April | 30.36 | 5.71 | 24.65 | 66.02 | 17.73 | 0.00 | 0.00 | 0.00 |
May | 24.13 | 0.58 | 23.56 | 58.71 | 4.62 | 0.00 | 0.00 | 0.00 |
June | 24.16 | 0.09 | 24.08 | 58.77 | 4.11 | 0.00 | 0.00 | 0.00 |
July | 25.21 | 0.23 | 24.97 | 61.34 | 2.72 | 0.00 | 0.00 | 0.00 |
August | 28.98 | 2.65 | 26.34 | 72.37 | 4.30 | 0.00 | 0.00 | 0.00 |
September | 34.39 | 7.94 | 26.45 | 81.86 | 6.20 | 0.00 | 0.00 | 0.00 |
October | 54.07 | 27.38 | 26.69 | 118.23 | 11.67 | 0.00 | 0.00 | 0.00 |
November | 70.65 | 48.57 | 22.09 | 135.04 | 24.79 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 53.48 | 20.66 | 136.18 | 31.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.68 | 21.61 | 24.07 | 94.32 | 16.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.13 | 0.09 | 20.66 | 58.71 | 2.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.33 | 53.81 | 26.69 | 136.93 | 34.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.33 | 53.81 | 21.52 | 136.93 | 34.91 | 0.00 | 0.00 | 0.00 |
February | 66.79 | 42.79 | 24.00 | 125.81 | 30.19 | 0.00 | 0.00 | 0.00 |
March | 41.24 | 17.40 | 23.84 | 82.43 | 26.30 | 0.00 | 0.00 | 0.00 |
April | 30.36 | 5.71 | 24.65 | 66.02 | 17.73 | 0.00 | 0.00 | 0.00 |
May | 24.13 | 0.58 | 23.56 | 58.71 | 4.62 | 0.00 | 0.00 | 0.00 |
June | 24.16 | 0.09 | 24.08 | 58.77 | 4.11 | 0.00 | 0.00 | 0.00 |
July | 25.21 | 0.23 | 24.97 | 61.34 | 2.72 | 0.00 | 0.00 | 0.00 |
August | 28.98 | 2.65 | 26.34 | 72.37 | 4.30 | 0.00 | 0.00 | 0.00 |
September | 34.39 | 7.94 | 26.45 | 81.86 | 6.20 | 0.00 | 0.00 | 0.00 |
October | 54.07 | 27.38 | 26.69 | 118.23 | 11.67 | 0.00 | 0.00 | 0.00 |
November | 70.65 | 48.57 | 22.09 | 135.04 | 24.79 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 53.48 | 20.66 | 136.18 | 31.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.68 | 21.61 | 24.07 | 94.32 | 16.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.13 | 0.09 | 20.66 | 58.71 | 2.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.33 | 53.81 | 26.69 | 136.93 | 34.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.38 | 29.18 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 105.09 | 25.21 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 68.83 | 21.96 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.20 | 14.74 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.27 | 3.70 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 49.37 | 3.28 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 51.56 | 2.12 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.72 | 3.42 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.58 | 4.99 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 98.91 | 9.60 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 112.88 | 20.68 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.79 | 26.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 78.92 | 13.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.27 | 2.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.38 | 29.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.38 | 29.18 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 105.09 | 25.21 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 68.83 | 21.96 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.20 | 14.74 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.27 | 3.70 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 49.37 | 3.28 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 51.56 | 2.12 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.72 | 3.42 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.58 | 4.99 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 98.91 | 9.60 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 112.88 | 20.68 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.79 | 26.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 78.92 | 13.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.27 | 2.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.38 | 29.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.33 | 53.81 | 21.52 | 136.82 | 34.72 | 0.00 | 0.00 | 0.00 |
February | 66.79 | 42.79 | 24.00 | 125.70 | 30.02 | 0.00 | 0.00 | 0.00 |
March | 41.24 | 17.40 | 23.84 | 82.34 | 26.14 | 0.00 | 0.00 | 0.00 |
April | 30.36 | 5.71 | 24.65 | 65.95 | 17.58 | 0.00 | 0.00 | 0.00 |
May | 24.13 | 0.58 | 23.56 | 58.75 | 4.45 | 0.00 | 0.00 | 0.00 |
June | 24.16 | 0.09 | 24.08 | 58.84 | 3.94 | 0.00 | 0.00 | 0.00 |
July | 25.21 | 0.23 | 24.97 | 61.45 | 2.56 | 0.00 | 0.00 | 0.00 |
August | 28.98 | 2.65 | 26.34 | 72.43 | 4.11 | 0.00 | 0.00 | 0.00 |
September | 34.39 | 7.94 | 26.45 | 81.86 | 6.00 | 0.00 | 0.00 | 0.00 |
October | 54.07 | 27.38 | 26.69 | 118.16 | 11.47 | 0.00 | 0.00 | 0.00 |
November | 70.65 | 48.57 | 22.09 | 134.92 | 24.65 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 53.48 | 20.66 | 136.06 | 31.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.68 | 21.61 | 24.07 | 94.28 | 16.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.13 | 0.09 | 20.66 | 58.75 | 2.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.33 | 53.81 | 26.69 | 136.82 | 34.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.48 | 29.00 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 105.20 | 25.04 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 68.92 | 21.80 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.25 | 14.65 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.31 | 3.66 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 49.40 | 3.24 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 51.59 | 2.09 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.75 | 3.39 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.60 | 4.96 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 98.94 | 9.56 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 112.93 | 20.60 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.86 | 26.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 78.97 | 13.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.31 | 2.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.48 | 29.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.48 | 29.00 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 105.20 | 25.04 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 68.92 | 21.80 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.25 | 14.65 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.31 | 3.66 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 49.40 | 3.24 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 51.59 | 2.09 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.75 | 3.39 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.60 | 4.96 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 98.94 | 9.56 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 112.93 | 20.60 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 113.86 | 26.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 78.97 | 13.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.31 | 2.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.48 | 29.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.33 | 53.81 | 21.52 | 136.94 | 34.52 | 0.00 | 0.00 | 0.00 |
February | 66.79 | 42.79 | 24.00 | 125.83 | 29.81 | 0.00 | 0.00 | 0.00 |
March | 41.24 | 17.40 | 23.84 | 82.44 | 25.96 | 0.00 | 0.00 | 0.00 |
April | 30.36 | 5.71 | 24.65 | 66.00 | 17.49 | 0.00 | 0.00 | 0.00 |
May | 24.13 | 0.58 | 23.56 | 58.79 | 4.40 | 0.00 | 0.00 | 0.00 |
June | 24.16 | 0.09 | 24.08 | 58.88 | 3.90 | 0.00 | 0.00 | 0.00 |
July | 25.21 | 0.23 | 24.97 | 61.49 | 2.53 | 0.00 | 0.00 | 0.00 |
August | 28.98 | 2.65 | 26.34 | 72.46 | 4.08 | 0.00 | 0.00 | 0.00 |
September | 34.39 | 7.94 | 26.45 | 81.89 | 5.96 | 0.00 | 0.00 | 0.00 |
October | 54.07 | 27.38 | 26.69 | 118.19 | 11.42 | 0.00 | 0.00 | 0.00 |
November | 70.65 | 48.57 | 22.09 | 134.98 | 24.56 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 53.48 | 20.66 | 136.15 | 31.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.68 | 21.61 | 24.07 | 94.35 | 16.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.13 | 0.09 | 20.66 | 58.79 | 2.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.33 | 53.81 | 26.69 | 136.94 | 34.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.69 | 28.60 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 105.44 | 24.60 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 69.11 | 21.40 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.35 | 14.41 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.32 | 3.61 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 49.39 | 3.22 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 51.55 | 2.10 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.70 | 3.42 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.57 | 4.97 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 98.93 | 9.52 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 113.03 | 20.41 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 114.03 | 25.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 79.04 | 13.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.32 | 2.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.69 | 28.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.69 | 28.60 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 105.44 | 24.60 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 69.11 | 21.40 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.35 | 14.41 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.32 | 3.61 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 49.39 | 3.22 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 51.55 | 2.10 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.70 | 3.42 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.57 | 4.97 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 98.93 | 9.52 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 113.03 | 20.41 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 114.03 | 25.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 79.04 | 13.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 49.32 | 2.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.69 | 28.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.33 | 53.81 | 21.52 | 137.20 | 34.03 | 0.00 | 0.00 | 0.00 |
February | 66.79 | 42.79 | 24.00 | 126.11 | 29.30 | 0.00 | 0.00 | 0.00 |
March | 41.24 | 17.40 | 23.84 | 82.67 | 25.48 | 0.00 | 0.00 | 0.00 |
April | 30.36 | 5.71 | 24.65 | 66.13 | 17.20 | 0.00 | 0.00 | 0.00 |
May | 24.13 | 0.58 | 23.56 | 58.81 | 4.34 | 0.00 | 0.00 | 0.00 |
June | 24.16 | 0.09 | 24.08 | 58.87 | 3.87 | 0.00 | 0.00 | 0.00 |
July | 25.21 | 0.23 | 24.97 | 61.44 | 2.54 | 0.00 | 0.00 | 0.00 |
August | 28.98 | 2.65 | 26.34 | 72.40 | 4.11 | 0.00 | 0.00 | 0.00 |
September | 34.39 | 7.94 | 26.45 | 81.85 | 5.97 | 0.00 | 0.00 | 0.00 |
October | 54.07 | 27.38 | 26.69 | 118.19 | 11.38 | 0.00 | 0.00 | 0.00 |
November | 70.65 | 48.57 | 22.09 | 135.10 | 24.33 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 53.48 | 20.66 | 136.36 | 30.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.68 | 21.61 | 24.07 | 94.43 | 16.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.13 | 0.09 | 20.66 | 58.81 | 2.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.33 | 53.81 | 26.69 | 137.20 | 34.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.99 | 27.33 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 105.83 | 23.25 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 69.38 | 20.08 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.45 | 13.57 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.01 | 3.54 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 48.94 | 3.26 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 50.92 | 2.27 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.06 | 3.74 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.06 | 5.22 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 98.60 | 9.55 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 113.11 | 19.81 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 114.32 | 24.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 78.92 | 12.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 48.94 | 2.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.99 | 27.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.01 | 45.01 | 18.00 | 114.99 | 27.33 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 35.79 | 20.07 | 105.83 | 23.25 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.56 | 19.94 | 69.38 | 20.08 | 0.00 | 0.00 | 0.00 |
April | 25.39 | 4.77 | 20.62 | 55.45 | 13.57 | 0.00 | 0.00 | 0.00 |
May | 20.19 | 0.48 | 19.70 | 49.01 | 3.54 | 0.00 | 0.00 | 0.00 |
June | 20.21 | 0.07 | 20.14 | 48.94 | 3.26 | 0.00 | 0.00 | 0.00 |
July | 21.08 | 0.20 | 20.89 | 50.92 | 2.27 | 0.00 | 0.00 | 0.00 |
August | 24.24 | 2.21 | 22.03 | 60.06 | 3.74 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 6.64 | 22.12 | 68.06 | 5.22 | 0.00 | 0.00 | 0.00 |
October | 45.23 | 22.90 | 22.33 | 98.60 | 9.55 | 0.00 | 0.00 | 0.00 |
November | 59.09 | 40.62 | 18.47 | 113.11 | 19.81 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 44.73 | 17.28 | 114.32 | 24.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 18.08 | 20.13 | 78.92 | 12.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.19 | 0.07 | 17.28 | 48.94 | 2.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.01 | 45.01 | 22.33 | 114.99 | 27.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.33 | 53.81 | 21.52 | 137.56 | 32.54 | 0.00 | 0.00 | 0.00 |
February | 66.79 | 42.79 | 24.00 | 126.58 | 27.69 | 0.00 | 0.00 | 0.00 |
March | 41.24 | 17.40 | 23.84 | 82.99 | 23.92 | 0.00 | 0.00 | 0.00 |
April | 30.36 | 5.71 | 24.65 | 66.25 | 16.20 | 0.00 | 0.00 | 0.00 |
May | 24.13 | 0.58 | 23.56 | 58.43 | 4.25 | 0.00 | 0.00 | 0.00 |
June | 24.16 | 0.09 | 24.08 | 58.32 | 3.92 | 0.00 | 0.00 | 0.00 |
July | 25.21 | 0.23 | 24.97 | 60.68 | 2.75 | 0.00 | 0.00 | 0.00 |
August | 28.98 | 2.65 | 26.34 | 71.62 | 4.50 | 0.00 | 0.00 | 0.00 |
September | 34.39 | 7.94 | 26.45 | 81.24 | 6.27 | 0.00 | 0.00 | 0.00 |
October | 54.07 | 27.38 | 26.69 | 117.78 | 11.42 | 0.00 | 0.00 | 0.00 |
November | 70.65 | 48.57 | 22.09 | 135.19 | 23.62 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 53.48 | 20.66 | 136.70 | 29.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.68 | 21.61 | 24.07 | 94.28 | 15.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.13 | 0.09 | 20.66 | 58.32 | 2.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.33 | 53.81 | 26.69 | 137.56 | 32.54 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.306373E+09 | 79075566.39 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.254318E+09 | 61613174.29 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.184858E+09 | 58816208.06 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143936E+09 | 37324592.13 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.133801E+09 | 8687926.71 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.129698E+09 | 7327945.31 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.140847E+09 | 4803227.48 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.164466E+09 | 8322798.45 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.179294E+09 | 11380014.04 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.266270E+09 | 23993812.78 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.293248E+09 | 52792970.62 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.305040E+09 | 70932217.19 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.250215E+10 | 0.425070E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.129698E+09 | 4803227.48 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.306373E+09 | 79075566.39 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.306373E+09 | 79075566.39 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.254318E+09 | 61613174.29 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.184858E+09 | 58816208.06 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143936E+09 | 37324592.13 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.133801E+09 | 8687926.71 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.129698E+09 | 7327945.31 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.140847E+09 | 4803227.48 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.164466E+09 | 8322798.45 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.179294E+09 | 11380014.04 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.266270E+09 | 23993812.78 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.293248E+09 | 52792970.62 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.305040E+09 | 70932217.19 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.250215E+10 | 0.425070E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.129698E+09 | 4803227.48 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.306373E+09 | 79075566.39 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.306373E+09 | 79075566.39 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.254318E+09 | 61613174.29 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.184858E+09 | 58816208.06 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143936E+09 | 37324592.13 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.133801E+09 | 8687926.71 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.129698E+09 | 7327945.31 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.140847E+09 | 4803227.48 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.164466E+09 | 8322798.45 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.179294E+09 | 11380014.04 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.266270E+09 | 23993812.78 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.293248E+09 | 52792970.62 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.305040E+09 | 70932217.19 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.250215E+10 | 0.425070E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.129698E+09 | 4803227.48 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.306373E+09 | 79075566.39 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.306373E+09 | 79075566.39 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.254318E+09 | 61613174.29 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.184858E+09 | 58816208.06 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143936E+09 | 37324592.13 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.133801E+09 | 8687926.71 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.129698E+09 | 7327945.31 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.140847E+09 | 4803227.48 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.164466E+09 | 8322798.45 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.179294E+09 | 11380014.04 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.266270E+09 | 23993812.78 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.293248E+09 | 52792970.62 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.305040E+09 | 70932217.19 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.250215E+10 | 0.425070E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.129698E+09 | 4803227.48 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.306373E+09 | 79075566.39 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202872E+09 | 0.144917E+09 | 57955411.76 | 0.368414E+09 | 94644156.86 |
February | 0.162459E+09 | 0.104078E+09 | 58381834.55 | 0.305778E+09 | 73789507.80 |
March | 0.111066E+09 | 46871415.78 | 64194319.16 | 0.222276E+09 | 70439027.28 |
April | 79125920.05 | 14872698.22 | 64253221.83 | 0.172861E+09 | 44807357.38 |
May | 64992914.04 | 1552715.27 | 63440198.77 | 0.160345E+09 | 10516833.56 |
June | 62973130.75 | 225205.85 | 62747924.90 | 0.155351E+09 | 8863161.86 |
July | 67883672.42 | 627874.63 | 67255797.79 | 0.168692E+09 | 5850331.03 |
August | 78054526.12 | 7125090.62 | 70929435.50 | 0.197157E+09 | 10081039.94 |
September | 89625144.08 | 20698591.86 | 68926552.22 | 0.215101E+09 | 13774576.02 |
October | 0.145623E+09 | 73735288.41 | 71887721.36 | 0.319732E+09 | 28865764.56 |
November | 0.184135E+09 | 0.126576E+09 | 57559380.64 | 0.352355E+09 | 63322590.95 |
December | 0.199673E+09 | 0.144025E+09 | 55647637.60 | 0.366677E+09 | 84935530.10 |
Annual Sum or Average | 0.144848E+10 | 0.685304E+09 | 0.763179E+09 | 0.300474E+10 | 0.509890E+09 |
Minimum of Months | 62973130.75 | 225205.85 | 55647637.60 | 0.155351E+09 | 5850331.03 |
Maximum of Months | 0.202872E+09 | 0.144917E+09 | 71887721.36 | 0.368414E+09 | 94644156.86 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202872E+09 | 0.144917E+09 | 57955411.76 | 0.368414E+09 | 94644156.86 |
February | 0.162459E+09 | 0.104078E+09 | 58381834.55 | 0.305778E+09 | 73789507.80 |
March | 0.111066E+09 | 46871415.78 | 64194319.16 | 0.222276E+09 | 70439027.28 |
April | 79125920.05 | 14872698.22 | 64253221.83 | 0.172861E+09 | 44807357.38 |
May | 64992914.04 | 1552715.27 | 63440198.77 | 0.160345E+09 | 10516833.56 |
June | 62973130.75 | 225205.85 | 62747924.90 | 0.155351E+09 | 8863161.86 |
July | 67883672.42 | 627874.63 | 67255797.79 | 0.168692E+09 | 5850331.03 |
August | 78054526.12 | 7125090.62 | 70929435.50 | 0.197157E+09 | 10081039.94 |
September | 89625144.08 | 20698591.86 | 68926552.22 | 0.215101E+09 | 13774576.02 |
October | 0.145623E+09 | 73735288.41 | 71887721.36 | 0.319732E+09 | 28865764.56 |
November | 0.184135E+09 | 0.126576E+09 | 57559380.64 | 0.352355E+09 | 63322590.95 |
December | 0.199673E+09 | 0.144025E+09 | 55647637.60 | 0.366677E+09 | 84935530.10 |
Annual Sum or Average | 0.144848E+10 | 0.685304E+09 | 0.763179E+09 | 0.300474E+10 | 0.509890E+09 |
Minimum of Months | 62973130.75 | 225205.85 | 55647637.60 | 0.155351E+09 | 5850331.03 |
Maximum of Months | 0.202872E+09 | 0.144917E+09 | 71887721.36 | 0.368414E+09 | 94644156.86 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.304161E+09 | 82872256.94 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.252772E+09 | 64167771.37 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.183461E+09 | 61468994.11 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143553E+09 | 38239465.61 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.134158E+09 | 8895567.33 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.130325E+09 | 7445470.08 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.141660E+09 | 4800676.33 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.165401E+09 | 8097045.06 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.179933E+09 | 11205985.83 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.266595E+09 | 23984708.91 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292665E+09 | 53498195.87 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.303814E+09 | 73213586.26 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.249850E+10 | 0.437890E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.130325E+09 | 4800676.33 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.304161E+09 | 82872256.94 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.304161E+09 | 82872256.94 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.252772E+09 | 64167771.37 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.183461E+09 | 61468994.11 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143553E+09 | 38239465.61 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.134158E+09 | 8895567.33 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.130325E+09 | 7445470.08 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.141660E+09 | 4800676.33 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.165401E+09 | 8097045.06 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.179933E+09 | 11205985.83 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.266595E+09 | 23984708.91 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292665E+09 | 53498195.87 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.303814E+09 | 73213586.26 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.249850E+10 | 0.437890E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.130325E+09 | 4800676.33 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.304161E+09 | 82872256.94 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202872E+09 | 0.144917E+09 | 57955411.76 | 0.365830E+09 | 99137645.12 |
February | 0.162459E+09 | 0.104078E+09 | 58381834.55 | 0.303976E+09 | 76821936.30 |
March | 0.111066E+09 | 46871415.78 | 64194319.16 | 0.220635E+09 | 73594919.60 |
April | 79125920.05 | 14872698.22 | 64253221.83 | 0.172416E+09 | 45904703.65 |
May | 64992914.04 | 1552715.27 | 63440198.77 | 0.160774E+09 | 10770621.37 |
June | 62973130.75 | 225205.85 | 62747924.90 | 0.156103E+09 | 9008954.75 |
July | 67883672.42 | 627874.63 | 67255797.79 | 0.169667E+09 | 5854246.59 |
August | 78054526.12 | 7125090.62 | 70929435.50 | 0.198293E+09 | 9814542.41 |
September | 89625144.08 | 20698591.86 | 68926552.22 | 0.215890E+09 | 13571421.64 |
October | 0.145623E+09 | 73735288.41 | 71887721.36 | 0.320168E+09 | 28856886.27 |
November | 0.184135E+09 | 0.126576E+09 | 57559380.64 | 0.351703E+09 | 64165749.61 |
December | 0.199673E+09 | 0.144025E+09 | 55647637.60 | 0.365267E+09 | 87639586.62 |
Annual Sum or Average | 0.144848E+10 | 0.685304E+09 | 0.763179E+09 | 0.300072E+10 | 0.525141E+09 |
Minimum of Months | 62973130.75 | 225205.85 | 55647637.60 | 0.156103E+09 | 5854246.59 |
Maximum of Months | 0.202872E+09 | 0.144917E+09 | 71887721.36 | 0.365830E+09 | 99137645.12 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.304663E+09 | 82985407.78 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.253073E+09 | 64700492.42 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.183512E+09 | 62521596.35 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143237E+09 | 40520039.77 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.132533E+09 | 11467592.94 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.128569E+09 | 9978994.07 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.138637E+09 | 6782918.19 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.163322E+09 | 10575098.04 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.178644E+09 | 14362412.59 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.265656E+09 | 27266902.09 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292695E+09 | 55753772.45 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.304122E+09 | 74359665.50 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.248866E+10 | 0.461275E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.128569E+09 | 6782918.19 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.304663E+09 | 82985407.78 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.304663E+09 | 82985407.78 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.253073E+09 | 64700492.42 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.183512E+09 | 62521596.35 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143237E+09 | 40520039.77 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.132533E+09 | 11467592.94 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.128569E+09 | 9978994.07 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.138637E+09 | 6782918.19 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.163322E+09 | 10575098.04 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.178644E+09 | 14362412.59 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.265656E+09 | 27266902.09 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292695E+09 | 55753772.45 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.304122E+09 | 74359665.50 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.248866E+10 | 0.461275E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.128569E+09 | 6782918.19 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.304663E+09 | 82985407.78 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201764E+09 | 0.144125E+09 | 57638715.52 | 0.364430E+09 | 98736049.69 |
February | 0.161572E+09 | 0.103509E+09 | 58062808.13 | 0.302674E+09 | 77030745.31 |
March | 0.110459E+09 | 46615287.82 | 63843530.53 | 0.219493E+09 | 74430451.78 |
April | 78693537.98 | 14791426.65 | 63902111.33 | 0.171105E+09 | 48334143.89 |
May | 64637761.51 | 1544230.49 | 63093531.02 | 0.158005E+09 | 13760344.35 |
June | 62629015.28 | 223975.22 | 62405040.07 | 0.153210E+09 | 11967815.23 |
July | 67512723.39 | 624443.62 | 66888279.77 | 0.165216E+09 | 8188319.75 |
August | 77627998.65 | 7086155.70 | 70541842.95 | 0.194790E+09 | 12702406.97 |
September | 89135389.20 | 20585484.80 | 68549904.40 | 0.213215E+09 | 17232935.50 |
October | 0.144827E+09 | 73332363.34 | 71494892.28 | 0.317333E+09 | 32581052.43 |
November | 0.183129E+09 | 0.125884E+09 | 57244848.50 | 0.349818E+09 | 66465947.95 |
December | 0.198582E+09 | 0.143238E+09 | 55343552.15 | 0.363637E+09 | 88509909.60 |
Annual Sum or Average | 0.144057E+10 | 0.681559E+09 | 0.759009E+09 | 0.297293E+10 | 0.549940E+09 |
Minimum of Months | 62629015.28 | 223975.22 | 55343552.15 | 0.153210E+09 | 8188319.75 |
Maximum of Months | 0.201764E+09 | 0.144125E+09 | 71494892.28 | 0.364430E+09 | 98736049.69 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.305103E+09 | 82006864.20 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.253365E+09 | 64022746.81 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.183713E+09 | 61979508.86 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143277E+09 | 40384096.70 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.132468E+09 | 11644029.30 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.128489E+09 | 10198186.57 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.138479E+09 | 7021960.96 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.163221E+09 | 10826467.44 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.178558E+09 | 14600577.81 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.265612E+09 | 27465417.58 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292760E+09 | 55569804.30 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.304344E+09 | 73763569.51 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.248939E+10 | 0.459483E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.128489E+09 | 7021960.96 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.305103E+09 | 82006864.20 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.305103E+09 | 82006864.20 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.253365E+09 | 64022746.81 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.183713E+09 | 61979508.86 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143277E+09 | 40384096.70 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.132468E+09 | 11644029.30 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.128489E+09 | 10198186.57 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.138479E+09 | 7021960.96 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.163221E+09 | 10826467.44 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.178558E+09 | 14600577.81 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.265612E+09 | 27465417.58 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292760E+09 | 55569804.30 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.304344E+09 | 73763569.51 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.248939E+10 | 0.459483E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.128489E+09 | 7021960.96 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.305103E+09 | 82006864.20 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201764E+09 | 0.144125E+09 | 57638715.52 | 0.364956E+09 | 97575155.86 |
February | 0.161572E+09 | 0.103509E+09 | 58062808.13 | 0.303023E+09 | 76225970.33 |
March | 0.110459E+09 | 46615287.82 | 63843530.53 | 0.219733E+09 | 73786850.79 |
April | 78693537.98 | 14791426.65 | 63902111.33 | 0.171153E+09 | 48171532.91 |
May | 64637761.51 | 1544230.49 | 63093531.02 | 0.157926E+09 | 13970078.90 |
June | 62629015.28 | 223975.22 | 62405040.07 | 0.153114E+09 | 12228086.59 |
July | 67512723.39 | 624443.62 | 66888279.77 | 0.165030E+09 | 8475627.80 |
August | 77627998.65 | 7086155.70 | 70541842.95 | 0.194669E+09 | 13003187.16 |
September | 89135389.20 | 20585484.80 | 68549904.40 | 0.213111E+09 | 17515826.96 |
October | 0.144827E+09 | 73332363.34 | 71494892.28 | 0.317280E+09 | 32816087.09 |
November | 0.183129E+09 | 0.125884E+09 | 57244848.50 | 0.349896E+09 | 66246731.42 |
December | 0.198582E+09 | 0.143238E+09 | 55343552.15 | 0.363904E+09 | 87802456.05 |
Annual Sum or Average | 0.144057E+10 | 0.681559E+09 | 0.759009E+09 | 0.297380E+10 | 0.547818E+09 |
Minimum of Months | 62629015.28 | 223975.22 | 55343552.15 | 0.153114E+09 | 8475627.80 |
Maximum of Months | 0.201764E+09 | 0.144125E+09 | 71494892.28 | 0.364956E+09 | 97575155.86 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.305786E+09 | 80759075.74 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.253868E+09 | 63101850.07 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.184156E+09 | 61067965.93 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143488E+09 | 39841503.79 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.132642E+09 | 11277162.61 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.128645E+09 | 9854761.61 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.138664E+09 | 6741958.77 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.163369E+09 | 10494977.47 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.178670E+09 | 14266438.32 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.265729E+09 | 27082051.31 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292977E+09 | 55036035.34 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.304739E+09 | 72874371.39 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.249273E+10 | 0.452398E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.128645E+09 | 6741958.77 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.305786E+09 | 80759075.74 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.305786E+09 | 80759075.74 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.253868E+09 | 63101850.07 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.184156E+09 | 61067965.93 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143488E+09 | 39841503.79 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.132642E+09 | 11277162.61 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.128645E+09 | 9854761.61 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.138664E+09 | 6741958.77 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.163369E+09 | 10494977.47 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.178670E+09 | 14266438.32 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.265729E+09 | 27082051.31 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292977E+09 | 55036035.34 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.304739E+09 | 72874371.39 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.249273E+10 | 0.452398E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.128645E+09 | 6741958.77 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.305786E+09 | 80759075.74 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201764E+09 | 0.144125E+09 | 57638715.52 | 0.365771E+09 | 96098933.90 |
February | 0.161572E+09 | 0.103509E+09 | 58062808.13 | 0.303626E+09 | 75134882.42 |
March | 0.110459E+09 | 46615287.82 | 63843530.53 | 0.220265E+09 | 72707290.58 |
April | 78693537.98 | 14791426.65 | 63902111.33 | 0.171408E+09 | 47530391.32 |
May | 64637761.51 | 1544230.49 | 63093531.02 | 0.158134E+09 | 13537993.92 |
June | 62629015.28 | 223975.22 | 62405040.07 | 0.153301E+09 | 11822866.28 |
July | 67512723.39 | 624443.62 | 66888279.77 | 0.165249E+09 | 8142614.52 |
August | 77627998.65 | 7086155.70 | 70541842.95 | 0.194846E+09 | 12611554.57 |
September | 89135389.20 | 20585484.80 | 68549904.40 | 0.213246E+09 | 17121902.59 |
October | 0.144827E+09 | 73332363.34 | 71494892.28 | 0.317422E+09 | 32364794.52 |
November | 0.183129E+09 | 0.125884E+09 | 57244848.50 | 0.350157E+09 | 65615174.13 |
December | 0.198582E+09 | 0.143238E+09 | 55343552.15 | 0.364375E+09 | 86749333.56 |
Annual Sum or Average | 0.144057E+10 | 0.681559E+09 | 0.759009E+09 | 0.297780E+10 | 0.539438E+09 |
Minimum of Months | 62629015.28 | 223975.22 | 55343552.15 | 0.153301E+09 | 8142614.52 |
Maximum of Months | 0.201764E+09 | 0.144125E+09 | 71494892.28 | 0.365771E+09 | 96098933.90 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.306664E+09 | 78568186.80 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.254514E+09 | 61339610.19 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.184601E+09 | 59167089.11 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143251E+09 | 38532739.66 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.131886E+09 | 10304892.51 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.127812E+09 | 8892911.43 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.137843E+09 | 6033788.81 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.162515E+09 | 9595994.53 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.177787E+09 | 13401448.64 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.265118E+09 | 26171276.94 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292898E+09 | 53906949.75 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.305099E+09 | 71169670.48 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.248999E+10 | 0.437085E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.127812E+09 | 6033788.81 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.306664E+09 | 78568186.80 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.306664E+09 | 78568186.80 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.254514E+09 | 61339610.19 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.184601E+09 | 59167089.11 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143251E+09 | 38532739.66 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.131886E+09 | 10304892.51 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.127812E+09 | 8892911.43 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.137843E+09 | 6033788.81 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.162515E+09 | 9595994.53 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.177787E+09 | 13401448.64 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.265118E+09 | 26171276.94 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292898E+09 | 53906949.75 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.305099E+09 | 71169670.48 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.248999E+10 | 0.437085E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.127812E+09 | 6033788.81 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.306664E+09 | 78568186.80 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.306664E+09 | 78568186.80 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.254514E+09 | 61339610.19 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.184601E+09 | 59167089.11 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143251E+09 | 38532739.66 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.131886E+09 | 10304892.51 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.127812E+09 | 8892911.43 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.137843E+09 | 6033788.81 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.162515E+09 | 9595994.53 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.177787E+09 | 13401448.64 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.265118E+09 | 26171276.94 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292898E+09 | 53906949.75 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.305099E+09 | 71169670.48 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.248999E+10 | 0.437085E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.127812E+09 | 6033788.81 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.306664E+09 | 78568186.80 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.306664E+09 | 78568186.80 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.254514E+09 | 61339610.19 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.184601E+09 | 59167089.11 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143251E+09 | 38532739.66 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.131886E+09 | 10304892.51 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.127812E+09 | 8892911.43 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.137843E+09 | 6033788.81 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.162515E+09 | 9595994.53 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.177787E+09 | 13401448.64 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.265118E+09 | 26171276.94 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292898E+09 | 53906949.75 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.305099E+09 | 71169670.48 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.248999E+10 | 0.437085E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.127812E+09 | 6033788.81 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.306664E+09 | 78568186.80 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201764E+09 | 0.144125E+09 | 57638715.52 | 0.366761E+09 | 93506384.54 |
February | 0.161572E+09 | 0.103509E+09 | 58062808.13 | 0.304354E+09 | 73042991.31 |
March | 0.110459E+09 | 46615287.82 | 63843530.53 | 0.220770E+09 | 70452227.41 |
April | 78693537.98 | 14791426.65 | 63902111.33 | 0.171122E+09 | 45967437.89 |
May | 64637761.51 | 1544230.49 | 63093531.02 | 0.157249E+09 | 12370214.14 |
June | 62629015.28 | 223975.22 | 62405040.07 | 0.152325E+09 | 10666011.33 |
July | 67512723.39 | 624443.62 | 66888279.77 | 0.164289E+09 | 7286008.05 |
August | 77627998.65 | 7086155.70 | 70541842.95 | 0.193833E+09 | 11529500.88 |
September | 89135389.20 | 20585484.80 | 68549904.40 | 0.212194E+09 | 16080909.21 |
October | 0.144827E+09 | 73332363.34 | 71494892.28 | 0.316661E+09 | 31268264.60 |
November | 0.183129E+09 | 0.125884E+09 | 57244848.50 | 0.350029E+09 | 64265902.15 |
December | 0.198582E+09 | 0.143238E+09 | 55343552.15 | 0.364757E+09 | 84729165.80 |
Annual Sum or Average | 0.144057E+10 | 0.681559E+09 | 0.759009E+09 | 0.297434E+10 | 0.521165E+09 |
Minimum of Months | 62629015.28 | 223975.22 | 55343552.15 | 0.152325E+09 | 7286008.05 |
Maximum of Months | 0.201764E+09 | 0.144125E+09 | 71494892.28 | 0.366761E+09 | 93506384.54 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201764E+09 | 0.144125E+09 | 57638715.52 | 0.366761E+09 | 93506384.54 |
February | 0.161572E+09 | 0.103509E+09 | 58062808.13 | 0.304354E+09 | 73042991.31 |
March | 0.110459E+09 | 46615287.82 | 63843530.53 | 0.220770E+09 | 70452227.41 |
April | 78693537.98 | 14791426.65 | 63902111.33 | 0.171122E+09 | 45967437.89 |
May | 64637761.51 | 1544230.49 | 63093531.02 | 0.157249E+09 | 12370214.14 |
June | 62629015.28 | 223975.22 | 62405040.07 | 0.152325E+09 | 10666011.33 |
July | 67512723.39 | 624443.62 | 66888279.77 | 0.164289E+09 | 7286008.05 |
August | 77627998.65 | 7086155.70 | 70541842.95 | 0.193833E+09 | 11529500.88 |
September | 89135389.20 | 20585484.80 | 68549904.40 | 0.212194E+09 | 16080909.21 |
October | 0.144827E+09 | 73332363.34 | 71494892.28 | 0.316661E+09 | 31268264.60 |
November | 0.183129E+09 | 0.125884E+09 | 57244848.50 | 0.350029E+09 | 64265902.15 |
December | 0.198582E+09 | 0.143238E+09 | 55343552.15 | 0.364757E+09 | 84729165.80 |
Annual Sum or Average | 0.144057E+10 | 0.681559E+09 | 0.759009E+09 | 0.297434E+10 | 0.521165E+09 |
Minimum of Months | 62629015.28 | 223975.22 | 55343552.15 | 0.152325E+09 | 7286008.05 |
Maximum of Months | 0.201764E+09 | 0.144125E+09 | 71494892.28 | 0.366761E+09 | 93506384.54 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.306355E+09 | 78153923.39 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.254245E+09 | 60981067.04 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.184366E+09 | 58804610.23 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143074E+09 | 38198126.28 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.131977E+09 | 9907954.94 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.127973E+09 | 8497830.54 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.138101E+09 | 5667457.77 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.162637E+09 | 9149257.08 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.177758E+09 | 12936033.99 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.264925E+09 | 25712459.54 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292587E+09 | 53599483.99 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.304763E+09 | 70830940.80 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.248876E+10 | 0.432439E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.127973E+09 | 5667457.77 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.306355E+09 | 78153923.39 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.306355E+09 | 78153923.39 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.254245E+09 | 60981067.04 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.184366E+09 | 58804610.23 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143074E+09 | 38198126.28 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.131977E+09 | 9907954.94 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.127973E+09 | 8497830.54 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.138101E+09 | 5667457.77 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.162637E+09 | 9149257.08 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.177758E+09 | 12936033.99 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.264925E+09 | 25712459.54 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292587E+09 | 53599483.99 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.304763E+09 | 70830940.80 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.248876E+10 | 0.432439E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.127973E+09 | 5667457.77 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.306355E+09 | 78153923.39 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201764E+09 | 0.144125E+09 | 57638715.52 | 0.366463E+09 | 93006529.21 |
February | 0.161572E+09 | 0.103509E+09 | 58062808.13 | 0.304090E+09 | 72615241.48 |
March | 0.110459E+09 | 46615287.82 | 63843530.53 | 0.220533E+09 | 70019110.11 |
April | 78693537.98 | 14791426.65 | 63902111.33 | 0.170937E+09 | 45579877.96 |
May | 64637761.51 | 1544230.49 | 63093531.02 | 0.157364E+09 | 11906497.88 |
June | 62629015.28 | 223975.22 | 62405040.07 | 0.152519E+09 | 10204817.20 |
July | 67512723.39 | 624443.62 | 66888279.77 | 0.164596E+09 | 6858502.06 |
August | 77627998.65 | 7086155.70 | 70541842.95 | 0.193991E+09 | 11006691.74 |
September | 89135389.20 | 20585484.80 | 68549904.40 | 0.212181E+09 | 15539546.07 |
October | 0.144827E+09 | 73332363.34 | 71494892.28 | 0.316480E+09 | 30730814.58 |
November | 0.183129E+09 | 0.125884E+09 | 57244848.50 | 0.349712E+09 | 63905225.07 |
December | 0.198582E+09 | 0.143238E+09 | 55343552.15 | 0.364422E+09 | 84322004.36 |
Annual Sum or Average | 0.144057E+10 | 0.681559E+09 | 0.759009E+09 | 0.297329E+10 | 0.515695E+09 |
Minimum of Months | 62629015.28 | 223975.22 | 55343552.15 | 0.152519E+09 | 6858502.06 |
Maximum of Months | 0.201764E+09 | 0.144125E+09 | 71494892.28 | 0.366463E+09 | 93006529.21 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.306628E+09 | 77685621.35 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.254501E+09 | 60565246.93 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.184600E+09 | 58393755.00 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143196E+09 | 37982324.99 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.132068E+09 | 9806004.97 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.128054E+09 | 8409487.19 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.138186E+09 | 5601119.83 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.162704E+09 | 9076722.54 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.177814E+09 | 12851977.09 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.264993E+09 | 25595484.28 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292707E+09 | 53394068.44 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.304964E+09 | 70438867.67 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.249042E+10 | 0.429801E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.128054E+09 | 5601119.83 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.306628E+09 | 77685621.35 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.306628E+09 | 77685621.35 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.254501E+09 | 60565246.93 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.184600E+09 | 58393755.00 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143196E+09 | 37982324.99 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.132068E+09 | 9806004.97 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.128054E+09 | 8409487.19 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.138186E+09 | 5601119.83 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.162704E+09 | 9076722.54 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.177814E+09 | 12851977.09 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.264993E+09 | 25595484.28 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292707E+09 | 53394068.44 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.304964E+09 | 70438867.67 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.249042E+10 | 0.429801E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.128054E+09 | 5601119.83 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.306628E+09 | 77685621.35 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201764E+09 | 0.144125E+09 | 57638715.52 | 0.366791E+09 | 92450746.12 |
February | 0.161572E+09 | 0.103509E+09 | 58062808.13 | 0.304396E+09 | 72121701.25 |
March | 0.110459E+09 | 46615287.82 | 63843530.53 | 0.220814E+09 | 69531960.85 |
April | 78693537.98 | 14791426.65 | 63902111.33 | 0.171084E+09 | 45322067.27 |
May | 64637761.51 | 1544230.49 | 63093531.02 | 0.157472E+09 | 11785091.13 |
June | 62629015.28 | 223975.22 | 62405040.07 | 0.152617E+09 | 10099939.20 |
July | 67512723.39 | 624443.62 | 66888279.77 | 0.164698E+09 | 6779143.20 |
August | 77627998.65 | 7086155.70 | 70541842.95 | 0.194072E+09 | 10920325.43 |
September | 89135389.20 | 20585484.80 | 68549904.40 | 0.212249E+09 | 15438947.06 |
October | 0.144827E+09 | 73332363.34 | 71494892.28 | 0.316561E+09 | 30591704.37 |
November | 0.183129E+09 | 0.125884E+09 | 57244848.50 | 0.349857E+09 | 63660342.34 |
December | 0.198582E+09 | 0.143238E+09 | 55343552.15 | 0.364663E+09 | 83856280.64 |
Annual Sum or Average | 0.144057E+10 | 0.681559E+09 | 0.759009E+09 | 0.297527E+10 | 0.512558E+09 |
Minimum of Months | 62629015.28 | 223975.22 | 55343552.15 | 0.152617E+09 | 6779143.20 |
Maximum of Months | 0.201764E+09 | 0.144125E+09 | 71494892.28 | 0.366791E+09 | 92450746.12 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.307196E+09 | 76591784.35 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.255070E+09 | 59517241.45 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.185114E+09 | 57313354.34 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143470E+09 | 37360089.33 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.132108E+09 | 9672696.75 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.128031E+09 | 8348211.48 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.138075E+09 | 5623578.22 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.162571E+09 | 9150747.04 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.177726E+09 | 12878559.11 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.264984E+09 | 25497370.13 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292969E+09 | 52895146.01 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.305427E+09 | 69441927.11 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.249274E+10 | 0.424291E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.128031E+09 | 5623578.22 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.307196E+09 | 76591784.35 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.307196E+09 | 76591784.35 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.255070E+09 | 59517241.45 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.185114E+09 | 57313354.34 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143470E+09 | 37360089.33 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.132108E+09 | 9672696.75 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.128031E+09 | 8348211.48 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.138075E+09 | 5623578.22 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.162571E+09 | 9150747.04 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.177726E+09 | 12878559.11 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.264984E+09 | 25497370.13 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.292969E+09 | 52895146.01 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.305427E+09 | 69441927.11 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.249274E+10 | 0.424291E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.128031E+09 | 5623578.22 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.307196E+09 | 76591784.35 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201764E+09 | 0.144125E+09 | 57638715.52 | 0.367469E+09 | 91154611.29 |
February | 0.161572E+09 | 0.103509E+09 | 58062808.13 | 0.305076E+09 | 70878888.52 |
March | 0.110459E+09 | 46615287.82 | 63843530.53 | 0.221429E+09 | 68252490.78 |
April | 78693537.98 | 14791426.65 | 63902111.33 | 0.171414E+09 | 44586378.39 |
May | 64637761.51 | 1544230.49 | 63093531.02 | 0.157518E+09 | 11630656.57 |
June | 62629015.28 | 223975.22 | 62405040.07 | 0.152587E+09 | 10030307.95 |
July | 67512723.39 | 624443.62 | 66888279.77 | 0.164562E+09 | 6809224.66 |
August | 77627998.65 | 7086155.70 | 70541842.95 | 0.193911E+09 | 11012724.20 |
September | 89135389.20 | 20585484.80 | 68549904.40 | 0.212143E+09 | 15474743.67 |
October | 0.144827E+09 | 73332363.34 | 71494892.28 | 0.316550E+09 | 30479050.96 |
November | 0.183129E+09 | 0.125884E+09 | 57244848.50 | 0.350171E+09 | 63071382.39 |
December | 0.198582E+09 | 0.143238E+09 | 55343552.15 | 0.365216E+09 | 82675796.49 |
Annual Sum or Average | 0.144057E+10 | 0.681559E+09 | 0.759009E+09 | 0.297805E+10 | 0.506056E+09 |
Minimum of Months | 62629015.28 | 223975.22 | 55343552.15 | 0.152587E+09 | 6809224.66 |
Maximum of Months | 0.201764E+09 | 0.144125E+09 | 71494892.28 | 0.367469E+09 | 91154611.29 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.308001E+09 | 73208769.34 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.256018E+09 | 56242912.26 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.185827E+09 | 53790029.22 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143733E+09 | 35161012.86 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.131261E+09 | 9473753.37 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.126858E+09 | 8448079.58 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.136374E+09 | 6086002.76 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.160852E+09 | 10012422.57 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.176418E+09 | 13526668.18 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.264083E+09 | 25585137.75 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.293187E+09 | 51343544.47 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.306199E+09 | 66365927.12 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.248881E+10 | 0.409244E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.126858E+09 | 6086002.76 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.308001E+09 | 73208769.34 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168757E+09 | 0.120548E+09 | 48209642.13 | 0.308001E+09 | 73208769.34 |
February | 0.135140E+09 | 86575926.36 | 48564357.75 | 0.256018E+09 | 56242912.26 |
March | 92388944.74 | 38989528.54 | 53399416.20 | 0.185827E+09 | 53790029.22 |
April | 65820122.28 | 12371708.47 | 53448413.81 | 0.143733E+09 | 35161012.86 |
May | 54063719.54 | 1291611.01 | 52772108.53 | 0.131261E+09 | 9473753.37 |
June | 52383582.57 | 187335.28 | 52196247.29 | 0.126858E+09 | 8448079.58 |
July | 56468368.60 | 522291.37 | 55946077.24 | 0.136374E+09 | 6086002.76 |
August | 64928893.72 | 5926936.91 | 59001956.81 | 0.160852E+09 | 10012422.57 |
September | 74553799.05 | 17217921.08 | 57335877.96 | 0.176418E+09 | 13526668.18 |
October | 0.121135E+09 | 61335978.11 | 59799097.53 | 0.264083E+09 | 25585137.75 |
November | 0.153171E+09 | 0.105291E+09 | 47880207.52 | 0.293187E+09 | 51343544.47 |
December | 0.166096E+09 | 0.119806E+09 | 46289942.78 | 0.306199E+09 | 66365927.12 |
Annual Sum or Average | 0.120491E+10 | 0.570064E+09 | 0.634843E+09 | 0.248881E+10 | 0.409244E+09 |
Minimum of Months | 52383582.57 | 187335.28 | 46289942.78 | 0.126858E+09 | 6086002.76 |
Maximum of Months | 0.168757E+09 | 0.120548E+09 | 59799097.53 | 0.308001E+09 | 73208769.34 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201764E+09 | 0.144125E+09 | 57638715.52 | 0.368435E+09 | 87147660.68 |
February | 0.161572E+09 | 0.103509E+09 | 58062808.13 | 0.306211E+09 | 66998320.18 |
March | 0.110459E+09 | 46615287.82 | 63843530.53 | 0.222282E+09 | 64077985.67 |
April | 78693537.98 | 14791426.65 | 63902111.33 | 0.171723E+09 | 41978714.90 |
May | 64637761.51 | 1544230.49 | 63093531.02 | 0.156492E+09 | 11395813.55 |
June | 62629015.28 | 223975.22 | 62405040.07 | 0.151169E+09 | 10150183.56 |
July | 67512723.39 | 624443.62 | 66888279.77 | 0.162517E+09 | 7364833.53 |
August | 77627998.65 | 7086155.70 | 70541842.95 | 0.191839E+09 | 12043632.44 |
September | 89135389.20 | 20585484.80 | 68549904.40 | 0.210567E+09 | 16250294.10 |
October | 0.144827E+09 | 73332363.34 | 71494892.28 | 0.315458E+09 | 30592082.35 |
November | 0.183129E+09 | 0.125884E+09 | 57244848.50 | 0.350423E+09 | 61231707.34 |
December | 0.198582E+09 | 0.143238E+09 | 55343552.15 | 0.366139E+09 | 79031595.91 |
Annual Sum or Average | 0.144057E+10 | 0.681559E+09 | 0.759009E+09 | 0.297326E+10 | 0.488263E+09 |
Minimum of Months | 62629015.28 | 223975.22 | 55343552.15 | 0.151169E+09 | 7364833.53 |
Maximum of Months | 0.201764E+09 | 0.144125E+09 | 71494892.28 | 0.368435E+09 | 87147660.68 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 732.65 | 188.77 | 403.52 | 288.24 | 115.27 | 0.00 | 0.00 |
February | 673.29 | 162.88 | 357.75 | 229.19 | 128.56 | 0.00 | 0.00 |
March | 442.05 | 140.44 | 220.91 | 93.23 | 127.68 | 0.00 | 0.00 |
April | 355.50 | 92.17 | 162.63 | 30.57 | 132.06 | 0.00 | 0.00 |
May | 319.55 | 20.83 | 129.27 | 3.09 | 126.18 | 0.00 | 0.00 |
June | 320.02 | 18.15 | 129.43 | 0.46 | 128.97 | 0.00 | 0.00 |
July | 336.31 | 11.54 | 135.02 | 1.25 | 133.77 | 0.00 | 0.00 |
August | 392.84 | 19.96 | 155.25 | 14.17 | 141.08 | 0.00 | 0.00 |
September | 442.66 | 28.19 | 184.21 | 42.54 | 141.67 | 0.00 | 0.00 |
October | 636.40 | 57.39 | 289.65 | 146.66 | 142.99 | 0.00 | 0.00 |
November | 724.42 | 130.33 | 378.45 | 260.15 | 118.30 | 0.00 | 0.00 |
December | 729.36 | 169.35 | 397.15 | 286.47 | 110.68 | 0.00 | 0.00 |
Annual Sum or Average | 507.93 | 86.25 | 244.69 | 115.77 | 128.92 | 0.00 | 0.00 |
Minimum of Months | 319.55 | 11.54 | 129.27 | 0.46 | 110.68 | 0.00 | 0.00 |
Maximum of Months | 732.65 | 188.77 | 403.52 | 288.24 | 142.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 363.71 | 98.90 | 201.76 | 144.12 | 57.64 | 0.00 | 0.00 |
February | 334.62 | 84.80 | 178.88 | 114.60 | 64.28 | 0.00 | 0.00 |
March | 219.37 | 73.38 | 110.46 | 46.61 | 63.84 | 0.00 | 0.00 |
April | 177.28 | 47.22 | 81.31 | 15.28 | 66.03 | 0.00 | 0.00 |
May | 160.20 | 10.66 | 64.64 | 1.54 | 63.09 | 0.00 | 0.00 |
June | 160.78 | 9.22 | 64.71 | 0.23 | 64.48 | 0.00 | 0.00 |
July | 169.13 | 5.77 | 67.51 | 0.62 | 66.89 | 0.00 | 0.00 |
August | 197.54 | 9.71 | 77.63 | 7.09 | 70.54 | 0.00 | 0.00 |
September | 222.13 | 13.88 | 92.10 | 21.27 | 70.83 | 0.00 | 0.00 |
October | 318.61 | 28.68 | 144.82 | 73.33 | 71.49 | 0.00 | 0.00 |
November | 361.51 | 66.03 | 189.23 | 130.08 | 59.15 | 0.00 | 0.00 |
December | 363.24 | 87.39 | 198.58 | 143.23 | 55.34 | 0.00 | 0.00 |
Annual Sum or Average | 253.61 | 44.42 | 122.35 | 57.88 | 64.46 | 0.00 | 0.00 |
Minimum of Months | 160.20 | 5.77 | 64.64 | 0.23 | 55.34 | 0.00 | 0.00 |
Maximum of Months | 363.71 | 98.90 | 201.76 | 144.12 | 71.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 363.56 | 98.83 | 201.34 | 143.83 | 57.52 | 0.00 | 0.00 |
February | 334.33 | 85.33 | 178.51 | 114.36 | 64.15 | 0.00 | 0.00 |
March | 218.98 | 74.47 | 110.23 | 46.52 | 63.71 | 0.00 | 0.00 |
April | 176.54 | 49.91 | 81.15 | 15.25 | 65.89 | 0.00 | 0.00 |
May | 157.96 | 13.70 | 64.50 | 1.54 | 62.96 | 0.00 | 0.00 |
June | 158.31 | 12.32 | 64.58 | 0.23 | 64.35 | 0.00 | 0.00 |
July | 165.21 | 8.12 | 67.37 | 0.62 | 66.75 | 0.00 | 0.00 |
August | 194.68 | 12.64 | 77.47 | 7.07 | 70.39 | 0.00 | 0.00 |
September | 220.10 | 17.73 | 91.91 | 21.23 | 70.69 | 0.00 | 0.00 |
October | 316.85 | 32.52 | 144.53 | 73.18 | 71.35 | 0.00 | 0.00 |
November | 360.81 | 68.66 | 188.84 | 129.81 | 59.03 | 0.00 | 0.00 |
December | 362.86 | 88.57 | 198.17 | 142.94 | 55.23 | 0.00 | 0.00 |
Annual Sum or Average | 252.10 | 46.69 | 122.09 | 57.77 | 64.33 | 0.00 | 0.00 |
Minimum of Months | 157.96 | 8.12 | 64.50 | 0.23 | 55.23 | 0.00 | 0.00 |
Maximum of Months | 363.56 | 98.83 | 201.34 | 143.83 | 71.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 364.08 | 97.67 | 201.34 | 143.83 | 57.52 | 0.00 | 0.00 |
February | 334.72 | 84.44 | 178.51 | 114.36 | 64.15 | 0.00 | 0.00 |
March | 219.22 | 73.83 | 110.23 | 46.52 | 63.71 | 0.00 | 0.00 |
April | 176.58 | 49.75 | 81.15 | 15.25 | 65.89 | 0.00 | 0.00 |
May | 157.88 | 13.91 | 64.50 | 1.54 | 62.96 | 0.00 | 0.00 |
June | 158.21 | 12.59 | 64.58 | 0.23 | 64.35 | 0.00 | 0.00 |
July | 165.02 | 8.41 | 67.37 | 0.62 | 66.75 | 0.00 | 0.00 |
August | 194.56 | 12.94 | 77.47 | 7.07 | 70.39 | 0.00 | 0.00 |
September | 219.99 | 18.02 | 91.91 | 21.23 | 70.69 | 0.00 | 0.00 |
October | 316.79 | 32.76 | 144.53 | 73.18 | 71.35 | 0.00 | 0.00 |
November | 360.89 | 68.44 | 188.84 | 129.81 | 59.03 | 0.00 | 0.00 |
December | 363.12 | 87.86 | 198.17 | 142.94 | 55.23 | 0.00 | 0.00 |
Annual Sum or Average | 252.17 | 46.51 | 122.09 | 57.77 | 64.33 | 0.00 | 0.00 |
Minimum of Months | 157.88 | 8.41 | 64.50 | 0.23 | 55.23 | 0.00 | 0.00 |
Maximum of Months | 364.08 | 97.67 | 201.34 | 143.83 | 71.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 364.90 | 96.18 | 201.34 | 143.83 | 57.52 | 0.00 | 0.00 |
February | 335.38 | 83.23 | 178.51 | 114.36 | 64.15 | 0.00 | 0.00 |
March | 219.75 | 72.75 | 110.23 | 46.52 | 63.71 | 0.00 | 0.00 |
April | 176.85 | 49.08 | 81.15 | 15.25 | 65.89 | 0.00 | 0.00 |
May | 158.09 | 13.48 | 64.50 | 1.54 | 62.96 | 0.00 | 0.00 |
June | 158.41 | 12.17 | 64.58 | 0.23 | 64.35 | 0.00 | 0.00 |
July | 165.24 | 8.07 | 67.37 | 0.62 | 66.75 | 0.00 | 0.00 |
August | 194.74 | 12.55 | 77.47 | 7.07 | 70.39 | 0.00 | 0.00 |
September | 220.13 | 17.61 | 91.91 | 21.23 | 70.69 | 0.00 | 0.00 |
October | 316.94 | 32.31 | 144.53 | 73.18 | 71.35 | 0.00 | 0.00 |
November | 361.15 | 67.78 | 188.84 | 129.81 | 59.03 | 0.00 | 0.00 |
December | 363.59 | 86.80 | 198.17 | 142.94 | 55.23 | 0.00 | 0.00 |
Annual Sum or Average | 252.51 | 45.80 | 122.09 | 57.77 | 64.33 | 0.00 | 0.00 |
Minimum of Months | 158.09 | 8.07 | 64.50 | 0.23 | 55.23 | 0.00 | 0.00 |
Maximum of Months | 364.90 | 96.18 | 201.34 | 143.83 | 71.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 731.85 | 187.16 | 402.69 | 287.65 | 115.04 | 0.00 | 0.00 |
February | 672.44 | 161.81 | 357.02 | 228.72 | 128.30 | 0.00 | 0.00 |
March | 440.54 | 140.97 | 220.46 | 93.04 | 127.42 | 0.00 | 0.00 |
April | 353.10 | 94.93 | 162.29 | 30.51 | 131.79 | 0.00 | 0.00 |
May | 314.38 | 24.63 | 129.01 | 3.08 | 125.92 | 0.00 | 0.00 |
June | 314.77 | 21.95 | 129.16 | 0.46 | 128.70 | 0.00 | 0.00 |
July | 328.54 | 14.45 | 134.74 | 1.25 | 133.50 | 0.00 | 0.00 |
August | 387.44 | 22.94 | 154.93 | 14.14 | 140.79 | 0.00 | 0.00 |
September | 438.09 | 33.09 | 183.83 | 42.45 | 141.37 | 0.00 | 0.00 |
October | 632.39 | 62.43 | 289.05 | 146.36 | 142.69 | 0.00 | 0.00 |
November | 722.09 | 132.78 | 377.68 | 259.62 | 118.06 | 0.00 | 0.00 |
December | 728.01 | 169.56 | 396.34 | 285.88 | 110.46 | 0.00 | 0.00 |
Annual Sum or Average | 504.46 | 88.49 | 244.19 | 115.53 | 128.66 | 0.00 | 0.00 |
Minimum of Months | 314.38 | 14.45 | 129.01 | 0.46 | 110.46 | 0.00 | 0.00 |
Maximum of Months | 731.85 | 187.16 | 402.69 | 287.65 | 142.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 365.58 | 93.08 | 201.34 | 143.83 | 57.52 | 0.00 | 0.00 |
February | 335.89 | 80.43 | 178.51 | 114.36 | 64.15 | 0.00 | 0.00 |
March | 220.01 | 70.05 | 110.23 | 46.52 | 63.71 | 0.00 | 0.00 |
April | 176.34 | 47.06 | 81.15 | 15.25 | 65.89 | 0.00 | 0.00 |
May | 157.30 | 11.84 | 64.50 | 1.54 | 62.96 | 0.00 | 0.00 |
June | 157.59 | 10.49 | 64.58 | 0.23 | 64.35 | 0.00 | 0.00 |
July | 164.58 | 6.79 | 67.37 | 0.62 | 66.75 | 0.00 | 0.00 |
August | 193.87 | 10.94 | 77.47 | 7.07 | 70.39 | 0.00 | 0.00 |
September | 219.02 | 15.98 | 91.91 | 21.23 | 70.69 | 0.00 | 0.00 |
October | 315.98 | 30.67 | 144.53 | 73.18 | 71.35 | 0.00 | 0.00 |
November | 360.68 | 66.01 | 188.84 | 129.81 | 59.03 | 0.00 | 0.00 |
December | 363.63 | 84.37 | 198.17 | 142.94 | 55.23 | 0.00 | 0.00 |
Annual Sum or Average | 252.12 | 43.78 | 122.09 | 57.77 | 64.33 | 0.00 | 0.00 |
Minimum of Months | 157.30 | 6.79 | 64.50 | 0.23 | 55.23 | 0.00 | 0.00 |
Maximum of Months | 365.58 | 93.08 | 201.34 | 143.83 | 71.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 365.91 | 92.53 | 201.34 | 143.83 | 57.52 | 0.00 | 0.00 |
February | 336.23 | 79.88 | 178.51 | 114.36 | 64.15 | 0.00 | 0.00 |
March | 220.29 | 69.56 | 110.23 | 46.52 | 63.71 | 0.00 | 0.00 |
April | 176.50 | 46.79 | 81.15 | 15.25 | 65.89 | 0.00 | 0.00 |
May | 157.41 | 11.72 | 64.50 | 1.54 | 62.96 | 0.00 | 0.00 |
June | 157.69 | 10.39 | 64.58 | 0.23 | 64.35 | 0.00 | 0.00 |
July | 164.68 | 6.71 | 67.37 | 0.62 | 66.75 | 0.00 | 0.00 |
August | 193.95 | 10.85 | 77.47 | 7.07 | 70.39 | 0.00 | 0.00 |
September | 219.09 | 15.87 | 91.91 | 21.23 | 70.69 | 0.00 | 0.00 |
October | 316.06 | 30.53 | 144.53 | 73.18 | 71.35 | 0.00 | 0.00 |
November | 360.83 | 65.76 | 188.84 | 129.81 | 59.03 | 0.00 | 0.00 |
December | 363.87 | 83.91 | 198.17 | 142.94 | 55.23 | 0.00 | 0.00 |
Annual Sum or Average | 252.29 | 43.51 | 122.09 | 57.77 | 64.33 | 0.00 | 0.00 |
Minimum of Months | 157.41 | 6.71 | 64.50 | 0.23 | 55.23 | 0.00 | 0.00 |
Maximum of Months | 365.91 | 92.53 | 201.34 | 143.83 | 71.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 366.58 | 91.23 | 201.34 | 143.83 | 57.52 | 0.00 | 0.00 |
February | 336.98 | 78.50 | 178.51 | 114.36 | 64.15 | 0.00 | 0.00 |
March | 220.90 | 68.28 | 110.23 | 46.52 | 63.71 | 0.00 | 0.00 |
April | 176.83 | 46.03 | 81.15 | 15.25 | 65.89 | 0.00 | 0.00 |
May | 157.46 | 11.57 | 64.50 | 1.54 | 62.96 | 0.00 | 0.00 |
June | 157.66 | 10.31 | 64.58 | 0.23 | 64.35 | 0.00 | 0.00 |
July | 164.54 | 6.74 | 67.37 | 0.62 | 66.75 | 0.00 | 0.00 |
August | 193.79 | 10.94 | 77.47 | 7.07 | 70.39 | 0.00 | 0.00 |
September | 218.98 | 15.91 | 91.91 | 21.23 | 70.69 | 0.00 | 0.00 |
October | 316.05 | 30.42 | 144.53 | 73.18 | 71.35 | 0.00 | 0.00 |
November | 361.15 | 65.15 | 188.84 | 129.81 | 59.03 | 0.00 | 0.00 |
December | 364.42 | 82.72 | 198.17 | 142.94 | 55.23 | 0.00 | 0.00 |
Annual Sum or Average | 252.52 | 42.96 | 122.09 | 57.77 | 64.33 | 0.00 | 0.00 |
Minimum of Months | 157.46 | 6.74 | 64.50 | 0.23 | 55.23 | 0.00 | 0.00 |
Maximum of Months | 366.58 | 91.23 | 201.34 | 143.83 | 71.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 367.55 | 87.20 | 201.34 | 143.83 | 57.52 | 0.00 | 0.00 |
February | 338.23 | 74.19 | 178.51 | 114.36 | 64.15 | 0.00 | 0.00 |
March | 221.75 | 64.09 | 110.23 | 46.52 | 63.71 | 0.00 | 0.00 |
April | 177.16 | 43.33 | 81.15 | 15.25 | 65.89 | 0.00 | 0.00 |
May | 156.44 | 11.33 | 64.50 | 1.54 | 62.96 | 0.00 | 0.00 |
June | 156.21 | 10.43 | 64.58 | 0.23 | 64.35 | 0.00 | 0.00 |
July | 162.51 | 7.29 | 67.37 | 0.62 | 66.75 | 0.00 | 0.00 |
August | 191.73 | 11.97 | 77.47 | 7.07 | 70.39 | 0.00 | 0.00 |
September | 217.36 | 16.71 | 91.91 | 21.23 | 70.69 | 0.00 | 0.00 |
October | 314.97 | 30.53 | 144.53 | 73.18 | 71.35 | 0.00 | 0.00 |
November | 361.42 | 63.24 | 188.84 | 129.81 | 59.03 | 0.00 | 0.00 |
December | 365.34 | 79.06 | 198.17 | 142.94 | 55.23 | 0.00 | 0.00 |
Annual Sum or Average | 252.12 | 41.44 | 122.09 | 57.77 | 64.33 | 0.00 | 0.00 |
Minimum of Months | 156.21 | 7.29 | 64.50 | 0.23 | 55.23 | 0.00 | 0.00 |
Maximum of Months | 367.55 | 87.20 | 201.34 | 143.83 | 71.35 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.196232E+10 | 0.505591E+09 | 0.108077E+10 | 0.772026E+09 | 0.308749E+09 | 0.00 | 0.00 |
February | 0.162883E+10 | 0.394032E+09 | 0.865480E+09 | 0.554459E+09 | 0.311021E+09 | 0.00 | 0.00 |
March | 0.118398E+10 | 0.376143E+09 | 0.591687E+09 | 0.249701E+09 | 0.341986E+09 | 0.00 | 0.00 |
April | 0.921468E+09 | 0.238913E+09 | 0.421532E+09 | 79232230.34 | 0.342300E+09 | 0.00 | 0.00 |
May | 0.855891E+09 | 55784983.04 | 0.346241E+09 | 8271874.58 | 0.337969E+09 | 0.00 | 0.00 |
June | 0.829493E+09 | 47037781.60 | 0.335481E+09 | 1199752.83 | 0.334281E+09 | 0.00 | 0.00 |
July | 0.900774E+09 | 30912975.44 | 0.361641E+09 | 3344914.73 | 0.358296E+09 | 0.00 | 0.00 |
August | 0.105218E+10 | 53452488.87 | 0.415825E+09 | 37957928.87 | 0.377867E+09 | 0.00 | 0.00 |
September | 0.114738E+10 | 73068298.27 | 0.477465E+09 | 0.110269E+09 | 0.367197E+09 | 0.00 | 0.00 |
October | 0.170454E+10 | 0.153706E+09 | 0.775786E+09 | 0.392814E+09 | 0.382972E+09 | 0.00 | 0.00 |
November | 0.187770E+10 | 0.337817E+09 | 0.980954E+09 | 0.674314E+09 | 0.306640E+09 | 0.00 | 0.00 |
December | 0.195351E+10 | 0.453600E+09 | 0.106373E+10 | 0.767274E+09 | 0.296455E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.160181E+11 | 0.272006E+10 | 0.771660E+10 | 0.365086E+10 | 0.406573E+10 | 0.00 | 0.00 |
Minimum of Months | 0.829493E+09 | 30912975.44 | 0.335481E+09 | 1199752.83 | 0.296455E+09 | 0.00 | 0.00 |
Maximum of Months | 0.196232E+10 | 0.505591E+09 | 0.108077E+10 | 0.772026E+09 | 0.382972E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.974152E+09 | 0.264882E+09 | 0.540387E+09 | 0.386013E+09 | 0.154375E+09 | 0.00 | 0.00 |
February | 0.809520E+09 | 0.205157E+09 | 0.432740E+09 | 0.277229E+09 | 0.155511E+09 | 0.00 | 0.00 |
March | 0.587557E+09 | 0.196533E+09 | 0.295844E+09 | 0.124850E+09 | 0.170993E+09 | 0.00 | 0.00 |
April | 0.459522E+09 | 0.122382E+09 | 0.210766E+09 | 39616115.17 | 0.171150E+09 | 0.00 | 0.00 |
May | 0.429090E+09 | 28561405.65 | 0.173120E+09 | 4135937.29 | 0.168984E+09 | 0.00 | 0.00 |
June | 0.416752E+09 | 23899484.86 | 0.167740E+09 | 599876.41 | 0.167140E+09 | 0.00 | 0.00 |
July | 0.452986E+09 | 15454584.50 | 0.180820E+09 | 1672457.36 | 0.179148E+09 | 0.00 | 0.00 |
August | 0.529095E+09 | 26008473.07 | 0.207912E+09 | 18978964.44 | 0.188933E+09 | 0.00 | 0.00 |
September | 0.575755E+09 | 35982923.49 | 0.238733E+09 | 55134434.02 | 0.183598E+09 | 0.00 | 0.00 |
October | 0.853357E+09 | 76824577.46 | 0.387893E+09 | 0.196407E+09 | 0.191486E+09 | 0.00 | 0.00 |
November | 0.937032E+09 | 0.171162E+09 | 0.490477E+09 | 0.337157E+09 | 0.153320E+09 | 0.00 | 0.00 |
December | 0.972894E+09 | 0.234067E+09 | 0.531864E+09 | 0.383637E+09 | 0.148228E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.799771E+10 | 0.140091E+10 | 0.385830E+10 | 0.182543E+10 | 0.203287E+10 | 0.00 | 0.00 |
Minimum of Months | 0.416752E+09 | 15454584.50 | 0.167740E+09 | 599876.41 | 0.148228E+09 | 0.00 | 0.00 |
Maximum of Months | 0.974152E+09 | 0.264882E+09 | 0.540387E+09 | 0.386013E+09 | 0.191486E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.973757E+09 | 0.264707E+09 | 0.539279E+09 | 0.385221E+09 | 0.154058E+09 | 0.00 | 0.00 |
February | 0.808820E+09 | 0.206432E+09 | 0.431852E+09 | 0.276661E+09 | 0.155192E+09 | 0.00 | 0.00 |
March | 0.586517E+09 | 0.199474E+09 | 0.295237E+09 | 0.124594E+09 | 0.170642E+09 | 0.00 | 0.00 |
April | 0.457579E+09 | 0.129374E+09 | 0.210334E+09 | 39534843.60 | 0.170799E+09 | 0.00 | 0.00 |
May | 0.423071E+09 | 36695324.94 | 0.172765E+09 | 4127452.50 | 0.168638E+09 | 0.00 | 0.00 |
June | 0.410348E+09 | 31925770.09 | 0.167396E+09 | 598645.78 | 0.166798E+09 | 0.00 | 0.00 |
July | 0.442489E+09 | 21753715.10 | 0.180449E+09 | 1669026.35 | 0.178780E+09 | 0.00 | 0.00 |
August | 0.521434E+09 | 33852487.98 | 0.207486E+09 | 18940029.52 | 0.188546E+09 | 0.00 | 0.00 |
September | 0.570503E+09 | 45957580.03 | 0.238243E+09 | 55021326.96 | 0.183222E+09 | 0.00 | 0.00 |
October | 0.848645E+09 | 87114789.65 | 0.387097E+09 | 0.196004E+09 | 0.191093E+09 | 0.00 | 0.00 |
November | 0.935209E+09 | 0.177973E+09 | 0.489471E+09 | 0.336465E+09 | 0.153005E+09 | 0.00 | 0.00 |
December | 0.971881E+09 | 0.237229E+09 | 0.530773E+09 | 0.382850E+09 | 0.147923E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.795025E+10 | 0.147249E+10 | 0.385038E+10 | 0.182169E+10 | 0.202870E+10 | 0.00 | 0.00 |
Minimum of Months | 0.410348E+09 | 21753715.10 | 0.167396E+09 | 598645.78 | 0.147923E+09 | 0.00 | 0.00 |
Maximum of Months | 0.973757E+09 | 0.264707E+09 | 0.539279E+09 | 0.385221E+09 | 0.191093E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.975161E+09 | 0.261589E+09 | 0.539279E+09 | 0.385221E+09 | 0.154058E+09 | 0.00 | 0.00 |
February | 0.809753E+09 | 0.204271E+09 | 0.431852E+09 | 0.276661E+09 | 0.155192E+09 | 0.00 | 0.00 |
March | 0.587159E+09 | 0.197746E+09 | 0.295237E+09 | 0.124594E+09 | 0.170642E+09 | 0.00 | 0.00 |
April | 0.457707E+09 | 0.128940E+09 | 0.210334E+09 | 39534843.60 | 0.170799E+09 | 0.00 | 0.00 |
May | 0.422863E+09 | 37258133.41 | 0.172765E+09 | 4127452.50 | 0.168638E+09 | 0.00 | 0.00 |
June | 0.410092E+09 | 32624429.68 | 0.167396E+09 | 598645.78 | 0.166798E+09 | 0.00 | 0.00 |
July | 0.441988E+09 | 22518632.65 | 0.180449E+09 | 1669026.35 | 0.178780E+09 | 0.00 | 0.00 |
August | 0.521111E+09 | 34655897.41 | 0.207486E+09 | 18940029.52 | 0.188546E+09 | 0.00 | 0.00 |
September | 0.570227E+09 | 46716695.72 | 0.238243E+09 | 55021326.96 | 0.183222E+09 | 0.00 | 0.00 |
October | 0.848504E+09 | 87746793.95 | 0.387097E+09 | 0.196004E+09 | 0.191093E+09 | 0.00 | 0.00 |
November | 0.935416E+09 | 0.177386E+09 | 0.489471E+09 | 0.336465E+09 | 0.153005E+09 | 0.00 | 0.00 |
December | 0.972592E+09 | 0.235330E+09 | 0.530773E+09 | 0.382850E+09 | 0.147923E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.795257E+10 | 0.146678E+10 | 0.385038E+10 | 0.182169E+10 | 0.202870E+10 | 0.00 | 0.00 |
Minimum of Months | 0.410092E+09 | 22518632.65 | 0.167396E+09 | 598645.78 | 0.147923E+09 | 0.00 | 0.00 |
Maximum of Months | 0.975161E+09 | 0.261589E+09 | 0.539279E+09 | 0.385221E+09 | 0.191093E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.977343E+09 | 0.257617E+09 | 0.539279E+09 | 0.385221E+09 | 0.154058E+09 | 0.00 | 0.00 |
February | 0.811363E+09 | 0.201338E+09 | 0.431852E+09 | 0.276661E+09 | 0.155192E+09 | 0.00 | 0.00 |
March | 0.588578E+09 | 0.194843E+09 | 0.295237E+09 | 0.124594E+09 | 0.170642E+09 | 0.00 | 0.00 |
April | 0.458383E+09 | 0.127213E+09 | 0.210334E+09 | 39534843.60 | 0.170799E+09 | 0.00 | 0.00 |
May | 0.423417E+09 | 36092196.58 | 0.172765E+09 | 4127452.50 | 0.168638E+09 | 0.00 | 0.00 |
June | 0.410592E+09 | 31532319.95 | 0.167396E+09 | 598645.78 | 0.166798E+09 | 0.00 | 0.00 |
July | 0.442578E+09 | 21625829.33 | 0.180449E+09 | 1669026.35 | 0.178780E+09 | 0.00 | 0.00 |
August | 0.521583E+09 | 33601379.32 | 0.207486E+09 | 18940029.52 | 0.188546E+09 | 0.00 | 0.00 |
September | 0.570586E+09 | 45654691.18 | 0.238243E+09 | 55021326.96 | 0.183222E+09 | 0.00 | 0.00 |
October | 0.848881E+09 | 86528786.77 | 0.387097E+09 | 0.196004E+09 | 0.191093E+09 | 0.00 | 0.00 |
November | 0.936111E+09 | 0.175687E+09 | 0.489471E+09 | 0.336465E+09 | 0.153005E+09 | 0.00 | 0.00 |
December | 0.973853E+09 | 0.232498E+09 | 0.530773E+09 | 0.382850E+09 | 0.147923E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.796327E+10 | 0.144423E+10 | 0.385038E+10 | 0.182169E+10 | 0.202870E+10 | 0.00 | 0.00 |
Minimum of Months | 0.410592E+09 | 21625829.33 | 0.167396E+09 | 598645.78 | 0.147923E+09 | 0.00 | 0.00 |
Maximum of Months | 0.977343E+09 | 0.257617E+09 | 0.539279E+09 | 0.385221E+09 | 0.191093E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.196018E+10 | 0.501285E+09 | 0.107856E+10 | 0.770442E+09 | 0.308116E+09 | 0.00 | 0.00 |
February | 0.162676E+10 | 0.391444E+09 | 0.863704E+09 | 0.553321E+09 | 0.310383E+09 | 0.00 | 0.00 |
March | 0.117994E+10 | 0.377573E+09 | 0.590473E+09 | 0.249189E+09 | 0.341285E+09 | 0.00 | 0.00 |
April | 0.915247E+09 | 0.246066E+09 | 0.420668E+09 | 79069687.19 | 0.341598E+09 | 0.00 | 0.00 |
May | 0.842042E+09 | 65959686.39 | 0.345530E+09 | 8254905.01 | 0.337275E+09 | 0.00 | 0.00 |
June | 0.815896E+09 | 56903517.17 | 0.334792E+09 | 1197291.56 | 0.333595E+09 | 0.00 | 0.00 |
July | 0.879951E+09 | 38706956.58 | 0.360899E+09 | 3338052.71 | 0.357561E+09 | 0.00 | 0.00 |
August | 0.103773E+10 | 61442684.14 | 0.414972E+09 | 37880059.03 | 0.377092E+09 | 0.00 | 0.00 |
September | 0.113554E+10 | 85767292.96 | 0.476486E+09 | 0.110043E+09 | 0.366443E+09 | 0.00 | 0.00 |
October | 0.169380E+10 | 0.167221E+09 | 0.774195E+09 | 0.392009E+09 | 0.382186E+09 | 0.00 | 0.00 |
November | 0.187165E+10 | 0.344160E+09 | 0.978941E+09 | 0.672931E+09 | 0.306011E+09 | 0.00 | 0.00 |
December | 0.194991E+10 | 0.454137E+09 | 0.106155E+10 | 0.765700E+09 | 0.295847E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.159086E+11 | 0.279067E+10 | 0.770077E+10 | 0.364337E+10 | 0.405739E+10 | 0.00 | 0.00 |
Minimum of Months | 0.815896E+09 | 38706956.58 | 0.334792E+09 | 1197291.56 | 0.295847E+09 | 0.00 | 0.00 |
Maximum of Months | 0.196018E+10 | 0.501285E+09 | 0.107856E+10 | 0.770442E+09 | 0.382186E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.979172E+09 | 0.249314E+09 | 0.539279E+09 | 0.385221E+09 | 0.154058E+09 | 0.00 | 0.00 |
February | 0.812579E+09 | 0.194577E+09 | 0.431852E+09 | 0.276661E+09 | 0.155192E+09 | 0.00 | 0.00 |
March | 0.589265E+09 | 0.187628E+09 | 0.295237E+09 | 0.124594E+09 | 0.170642E+09 | 0.00 | 0.00 |
April | 0.457084E+09 | 0.121976E+09 | 0.210334E+09 | 39534843.60 | 0.170799E+09 | 0.00 | 0.00 |
May | 0.421318E+09 | 31722177.16 | 0.172765E+09 | 4127452.50 | 0.168638E+09 | 0.00 | 0.00 |
June | 0.408465E+09 | 27200363.91 | 0.167396E+09 | 598645.78 | 0.166798E+09 | 0.00 | 0.00 |
July | 0.440798E+09 | 18193209.42 | 0.180449E+09 | 1669026.35 | 0.178780E+09 | 0.00 | 0.00 |
August | 0.519266E+09 | 29304991.47 | 0.207486E+09 | 18940029.52 | 0.188546E+09 | 0.00 | 0.00 |
September | 0.567696E+09 | 41411324.06 | 0.238243E+09 | 55021326.96 | 0.183222E+09 | 0.00 | 0.00 |
October | 0.846330E+09 | 82155494.26 | 0.387097E+09 | 0.196004E+09 | 0.191093E+09 | 0.00 | 0.00 |
November | 0.934886E+09 | 0.171104E+09 | 0.489471E+09 | 0.336465E+09 | 0.153005E+09 | 0.00 | 0.00 |
December | 0.973949E+09 | 0.225984E+09 | 0.530773E+09 | 0.382850E+09 | 0.147923E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.795081E+10 | 0.138057E+10 | 0.385038E+10 | 0.182169E+10 | 0.202870E+10 | 0.00 | 0.00 |
Minimum of Months | 0.408465E+09 | 18193209.42 | 0.167396E+09 | 598645.78 | 0.147923E+09 | 0.00 | 0.00 |
Maximum of Months | 0.979172E+09 | 0.249314E+09 | 0.539279E+09 | 0.385221E+09 | 0.191093E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.980047E+09 | 0.247822E+09 | 0.539279E+09 | 0.385221E+09 | 0.154058E+09 | 0.00 | 0.00 |
February | 0.813398E+09 | 0.193252E+09 | 0.431852E+09 | 0.276661E+09 | 0.155192E+09 | 0.00 | 0.00 |
March | 0.590015E+09 | 0.186319E+09 | 0.295237E+09 | 0.124594E+09 | 0.170642E+09 | 0.00 | 0.00 |
April | 0.457476E+09 | 0.121287E+09 | 0.210334E+09 | 39534843.60 | 0.170799E+09 | 0.00 | 0.00 |
May | 0.421608E+09 | 31396972.23 | 0.172765E+09 | 4127452.50 | 0.168638E+09 | 0.00 | 0.00 |
June | 0.408726E+09 | 26918848.64 | 0.167396E+09 | 598645.78 | 0.166798E+09 | 0.00 | 0.00 |
July | 0.441069E+09 | 17980916.67 | 0.180449E+09 | 1669026.35 | 0.178780E+09 | 0.00 | 0.00 |
August | 0.519481E+09 | 29073665.58 | 0.207486E+09 | 18940029.52 | 0.188546E+09 | 0.00 | 0.00 |
September | 0.567876E+09 | 41142676.92 | 0.238243E+09 | 55021326.96 | 0.183222E+09 | 0.00 | 0.00 |
October | 0.846547E+09 | 81782461.88 | 0.387097E+09 | 0.196004E+09 | 0.191093E+09 | 0.00 | 0.00 |
November | 0.935271E+09 | 0.170448E+09 | 0.489471E+09 | 0.336465E+09 | 0.153005E+09 | 0.00 | 0.00 |
December | 0.974591E+09 | 0.224734E+09 | 0.530773E+09 | 0.382850E+09 | 0.147923E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.795610E+10 | 0.137216E+10 | 0.385038E+10 | 0.182169E+10 | 0.202870E+10 | 0.00 | 0.00 |
Minimum of Months | 0.408726E+09 | 17980916.67 | 0.167396E+09 | 598645.78 | 0.147923E+09 | 0.00 | 0.00 |
Maximum of Months | 0.980047E+09 | 0.247822E+09 | 0.539279E+09 | 0.385221E+09 | 0.191093E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.981861E+09 | 0.244338E+09 | 0.539279E+09 | 0.385221E+09 | 0.154058E+09 | 0.00 | 0.00 |
February | 0.815216E+09 | 0.189913E+09 | 0.431852E+09 | 0.276661E+09 | 0.155192E+09 | 0.00 | 0.00 |
March | 0.591656E+09 | 0.182879E+09 | 0.295237E+09 | 0.124594E+09 | 0.170642E+09 | 0.00 | 0.00 |
April | 0.458354E+09 | 0.119307E+09 | 0.210334E+09 | 39534843.60 | 0.170799E+09 | 0.00 | 0.00 |
May | 0.421733E+09 | 30975855.41 | 0.172765E+09 | 4127452.50 | 0.168638E+09 | 0.00 | 0.00 |
June | 0.408648E+09 | 26726637.67 | 0.167396E+09 | 598645.78 | 0.166798E+09 | 0.00 | 0.00 |
July | 0.440711E+09 | 18056072.79 | 0.180449E+09 | 1669026.35 | 0.178780E+09 | 0.00 | 0.00 |
August | 0.519052E+09 | 29314042.42 | 0.207486E+09 | 18940029.52 | 0.188546E+09 | 0.00 | 0.00 |
September | 0.567594E+09 | 41231800.12 | 0.238243E+09 | 55021326.96 | 0.183222E+09 | 0.00 | 0.00 |
October | 0.846519E+09 | 81473559.88 | 0.387097E+09 | 0.196004E+09 | 0.191093E+09 | 0.00 | 0.00 |
November | 0.936108E+09 | 0.168862E+09 | 0.489471E+09 | 0.336465E+09 | 0.153005E+09 | 0.00 | 0.00 |
December | 0.976069E+09 | 0.221560E+09 | 0.530773E+09 | 0.382850E+09 | 0.147923E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.796352E+10 | 0.135464E+10 | 0.385038E+10 | 0.182169E+10 | 0.202870E+10 | 0.00 | 0.00 |
Minimum of Months | 0.408648E+09 | 18056072.79 | 0.167396E+09 | 598645.78 | 0.147923E+09 | 0.00 | 0.00 |
Maximum of Months | 0.981861E+09 | 0.244338E+09 | 0.539279E+09 | 0.385221E+09 | 0.191093E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.984437E+09 | 0.233565E+09 | 0.539279E+09 | 0.385221E+09 | 0.154058E+09 | 0.00 | 0.00 |
February | 0.818248E+09 | 0.179484E+09 | 0.431852E+09 | 0.276661E+09 | 0.155192E+09 | 0.00 | 0.00 |
March | 0.593935E+09 | 0.171658E+09 | 0.295237E+09 | 0.124594E+09 | 0.170642E+09 | 0.00 | 0.00 |
April | 0.459189E+09 | 0.112301E+09 | 0.210334E+09 | 39534843.60 | 0.170799E+09 | 0.00 | 0.00 |
May | 0.419013E+09 | 30343104.48 | 0.172765E+09 | 4127452.50 | 0.168638E+09 | 0.00 | 0.00 |
June | 0.404884E+09 | 27046187.40 | 0.167396E+09 | 598645.78 | 0.166798E+09 | 0.00 | 0.00 |
July | 0.435264E+09 | 19536179.81 | 0.180449E+09 | 1669026.35 | 0.178780E+09 | 0.00 | 0.00 |
August | 0.513542E+09 | 32068315.82 | 0.207486E+09 | 18940029.52 | 0.188546E+09 | 0.00 | 0.00 |
September | 0.563402E+09 | 43303243.72 | 0.238243E+09 | 55021326.96 | 0.183222E+09 | 0.00 | 0.00 |
October | 0.843624E+09 | 81762238.63 | 0.387097E+09 | 0.196004E+09 | 0.191093E+09 | 0.00 | 0.00 |
November | 0.936797E+09 | 0.163919E+09 | 0.489471E+09 | 0.336465E+09 | 0.153005E+09 | 0.00 | 0.00 |
December | 0.978537E+09 | 0.211763E+09 | 0.530773E+09 | 0.382850E+09 | 0.147923E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.795087E+10 | 0.130675E+10 | 0.385038E+10 | 0.182169E+10 | 0.202870E+10 | 0.00 | 0.00 |
Minimum of Months | 0.404884E+09 | 19536179.81 | 0.167396E+09 | 598645.78 | 0.147923E+09 | 0.00 | 0.00 |
Maximum of Months | 0.984437E+09 | 0.233565E+09 | 0.539279E+09 | 0.385221E+09 | 0.191093E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.306558E+09 | -189185475.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117372552.7 | 58.99 | 0.00 | 0.00 |
February | 0.275200E+09 | -170371604.2 | 0.00 | 0.00 | 672.00 | 0.00 | -104828681.8 | 58.99 | 0.00 | 0.00 |
March | 0.299954E+09 | -184438304.7 | 0.00 | 0.00 | 744.00 | 0.00 | -115515623.7 | 58.99 | 0.00 | 0.00 |
April | 0.274898E+09 | -165330798.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109567189.3 | 58.99 | 0.00 | 0.00 |
May | 0.271143E+09 | -159003850.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112138949.1 | 58.99 | 0.00 | 0.00 |
June | 0.254177E+09 | -145799679.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108377811.3 | 58.99 | 0.00 | 0.00 |
July | 0.254550E+09 | -142822802.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111727690.1 | 58.99 | 0.00 | 0.00 |
August | 0.259075E+09 | -147427791.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111647250.9 | 58.99 | 0.00 | 0.00 |
September | 0.256499E+09 | -148304549.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108194931.1 | 58.99 | 0.00 | 0.00 |
October | 0.275119E+09 | -163023300.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112095939.5 | 58.99 | 0.00 | 0.00 |
November | 0.278471E+09 | -168882227.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109589179.9 | 58.99 | 0.00 | 0.00 |
December | 0.300251E+09 | -184810705.6 | 0.00 | 0.00 | 744.00 | 0.00 | -115440260.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.330590E+10 | -0.196940E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133650E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.254177E+09 | -189185475.2 | 0.00 | 0.00 | 672.00 | 0.00 | -117372552.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.306558E+09 | -142822802.7 | 0.00 | 0.00 | 744.00 | 0.00 | -104828681.8 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.304715E+09 | -189191696.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115523353.3 | 58.99 | 0.00 | 0.00 |
February | 0.274050E+09 | -170370959.2 | 0.00 | 0.00 | 672.00 | 0.00 | -103678996.6 | 58.99 | 0.00 | 0.00 |
March | 0.298830E+09 | -184430186.0 | 0.00 | 0.00 | 744.00 | 0.00 | -114400252.9 | 58.99 | 0.00 | 0.00 |
April | 0.274536E+09 | -165335118.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109200870.4 | 58.99 | 0.00 | 0.00 |
May | 0.270994E+09 | -158999837.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111994417.5 | 58.99 | 0.00 | 0.00 |
June | 0.254079E+09 | -145803053.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108275982.3 | 58.99 | 0.00 | 0.00 |
July | 0.254498E+09 | -142828043.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111669865.5 | 58.99 | 0.00 | 0.00 |
August | 0.259075E+09 | -147439332.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111635853.7 | 58.99 | 0.00 | 0.00 |
September | 0.256458E+09 | -148301542.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108156149.6 | 58.99 | 0.00 | 0.00 |
October | 0.275014E+09 | -163023437.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111990312.4 | 58.99 | 0.00 | 0.00 |
November | 0.278104E+09 | -168875459.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109228939.9 | 59.00 | 0.00 | 0.00 |
December | 0.299223E+09 | -184818197.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114404684.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.329958E+10 | -0.196942E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133016E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.254079E+09 | -189191696.1 | 0.00 | 0.00 | 672.00 | 0.00 | -115523353.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.304715E+09 | -142828043.2 | 0.00 | 0.00 | 744.00 | 0.00 | -103678996.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.282495E+09 | -166365294.8 | 0.00 | 0.00 | 744.00 | 0.00 | -116129584.2 | 58.99 | 0.00 | 0.00 |
February | 0.253878E+09 | -149932182.4 | 0.00 | 0.00 | 672.00 | 0.00 | -103946034.5 | 59.00 | 0.00 | 0.00 |
March | 0.278957E+09 | -164581067.3 | 0.00 | 0.00 | 744.00 | 0.00 | -114375883.7 | 59.00 | 0.00 | 0.00 |
April | 0.253825E+09 | -145410173.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108414703.4 | 58.99 | 0.00 | 0.00 |
May | 0.251539E+09 | -141049134.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110489963.4 | 58.99 | 0.00 | 0.00 |
June | 0.236565E+09 | -129844403.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106720831.8 | 58.99 | 0.00 | 0.00 |
July | 0.234732E+09 | -124863273.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109869218.3 | 58.99 | 0.00 | 0.00 |
August | 0.241673E+09 | -131693795.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109978914.6 | 58.99 | 0.00 | 0.00 |
September | 0.236939E+09 | -130371810.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106566730.2 | 58.99 | 0.00 | 0.00 |
October | 0.253910E+09 | -143351069.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110558709.3 | 59.00 | 0.00 | 0.00 |
November | 0.257728E+09 | -149111524.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108616003.9 | 58.99 | 0.00 | 0.00 |
December | 0.275789E+09 | -161322823.6 | 0.00 | 0.00 | 744.00 | 0.00 | -114466326.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.305803E+10 | -0.173790E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132013E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.234732E+09 | -166365294.8 | 0.00 | 0.00 | 672.00 | 0.00 | -116129584.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.282495E+09 | -124863273.2 | 0.00 | 0.00 | 744.00 | 0.00 | -103946034.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.282858E+09 | -166349621.4 | 0.00 | 0.00 | 744.00 | 0.00 | -116508856.2 | 59.00 | 0.00 | 0.00 |
February | 0.254124E+09 | -149963883.1 | 0.00 | 0.00 | 672.00 | 0.00 | -104159730.7 | 58.99 | 0.00 | 0.00 |
March | 0.279136E+09 | -164591461.0 | 0.00 | 0.00 | 744.00 | 0.00 | -114544367.0 | 58.99 | 0.00 | 0.00 |
April | 0.253866E+09 | -145403821.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108461699.3 | 58.99 | 0.00 | 0.00 |
May | 0.251468E+09 | -141019826.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110448494.0 | 59.00 | 0.00 | 0.00 |
June | 0.236486E+09 | -129846943.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106639276.4 | 58.99 | 0.00 | 0.00 |
July | 0.234638E+09 | -124871011.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109767307.3 | 58.99 | 0.00 | 0.00 |
August | 0.241574E+09 | -131702481.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109871841.3 | 58.99 | 0.00 | 0.00 |
September | 0.236858E+09 | -130369915.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106487901.3 | 58.99 | 0.00 | 0.00 |
October | 0.253864E+09 | -143377958.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110486356.8 | 58.99 | 0.00 | 0.00 |
November | 0.257778E+09 | -149102410.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108675862.7 | 58.99 | 0.00 | 0.00 |
December | 0.276000E+09 | -161323045.3 | 0.00 | 0.00 | 744.00 | 0.00 | -114677079.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.305865E+10 | -0.173792E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132073E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.234638E+09 | -166349621.4 | 0.00 | 0.00 | 672.00 | 0.00 | -116508856.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.282858E+09 | -124871011.4 | 0.00 | 0.00 | 744.00 | 0.00 | -104159730.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.275249E+09 | -157238570.3 | 0.00 | 0.00 | 744.00 | 0.00 | -118010363.7 | 58.99 | 0.00 | 0.00 |
February | 0.247138E+09 | -141791553.1 | 0.00 | 0.00 | 672.00 | 0.00 | -105346234.3 | 59.00 | 0.00 | 0.00 |
March | 0.271433E+09 | -155729341.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115703249.7 | 59.00 | 0.00 | 0.00 |
April | 0.246763E+09 | -137588715.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109174607.6 | 59.00 | 0.00 | 0.00 |
May | 0.244334E+09 | -133384312.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110949779.5 | 58.99 | 0.00 | 0.00 |
June | 0.230015E+09 | -122860792.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107154498.4 | 58.99 | 0.00 | 0.00 |
July | 0.228298E+09 | -118091288.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110206981.1 | 58.99 | 0.00 | 0.00 |
August | 0.234989E+09 | -124628521.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110360779.0 | 58.98 | 0.00 | 0.00 |
September | 0.230244E+09 | -123384650.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106859491.2 | 58.99 | 0.00 | 0.00 |
October | 0.246456E+09 | -135523152.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110932884.3 | 58.98 | 0.00 | 0.00 |
November | 0.250162E+09 | -140840366.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109321606.6 | 58.99 | 0.00 | 0.00 |
December | 0.268296E+09 | -152571943.9 | 0.00 | 0.00 | 744.00 | 0.00 | -115724346.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.297338E+10 | -0.164363E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132974E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.228298E+09 | -157238570.3 | 0.00 | 0.00 | 672.00 | 0.00 | -118010363.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.275249E+09 | -118091288.4 | 0.00 | 0.00 | 744.00 | 0.00 | -105346234.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.275431E+09 | -157242683.6 | 0.00 | 0.00 | 744.00 | 0.00 | -118187978.9 | 58.99 | 0.00 | 0.00 |
February | 0.247262E+09 | -141791938.2 | 0.00 | 0.00 | 672.00 | 0.00 | -105470066.1 | 58.99 | 0.00 | 0.00 |
March | 0.271559E+09 | -155753506.3 | 0.00 | 0.00 | 744.00 | 0.00 | -115805149.0 | 58.99 | 0.00 | 0.00 |
April | 0.246818E+09 | -137585623.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109232210.1 | 59.00 | 0.00 | 0.00 |
May | 0.244420E+09 | -133374193.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111046032.9 | 58.99 | 0.00 | 0.00 |
June | 0.230120E+09 | -122868432.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107251828.1 | 58.99 | 0.00 | 0.00 |
July | 0.228396E+09 | -118105243.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110290384.6 | 58.99 | 0.00 | 0.00 |
August | 0.235101E+09 | -124597165.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110504120.5 | 58.99 | 0.00 | 0.00 |
September | 0.230333E+09 | -123363957.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106969165.8 | 58.99 | 0.00 | 0.00 |
October | 0.246553E+09 | -135519272.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111033420.7 | 58.99 | 0.00 | 0.00 |
November | 0.250229E+09 | -140851243.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109377397.6 | 58.98 | 0.00 | 0.00 |
December | 0.268418E+09 | -152567495.7 | 0.00 | 0.00 | 744.00 | 0.00 | -115850427.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.297464E+10 | -0.164362E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133102E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.228396E+09 | -157242683.6 | 0.00 | 0.00 | 672.00 | 0.00 | -118187978.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.275431E+09 | -118105243.5 | 0.00 | 0.00 | 744.00 | 0.00 | -105470066.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.275612E+09 | -157237978.3 | 0.00 | 0.00 | 744.00 | 0.00 | -118373905.3 | 58.99 | 0.00 | 0.00 |
February | 0.247424E+09 | -141807516.7 | 0.00 | 0.00 | 672.00 | 0.00 | -105615994.0 | 58.99 | 0.00 | 0.00 |
March | 0.271704E+09 | -155746412.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115957825.9 | 58.99 | 0.00 | 0.00 |
April | 0.246884E+09 | -137628255.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109255459.0 | 58.98 | 0.00 | 0.00 |
May | 0.244455E+09 | -133381891.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111073544.8 | 58.99 | 0.00 | 0.00 |
June | 0.230144E+09 | -122865571.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107277989.9 | 58.99 | 0.00 | 0.00 |
July | 0.228437E+09 | -118093513.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110343157.2 | 58.99 | 0.00 | 0.00 |
August | 0.235117E+09 | -124622597.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110494194.7 | 58.98 | 0.00 | 0.00 |
September | 0.230364E+09 | -123387534.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106976192.8 | 58.99 | 0.00 | 0.00 |
October | 0.246598E+09 | -135509643.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111088166.3 | 58.99 | 0.00 | 0.00 |
November | 0.250290E+09 | -140817195.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109473298.0 | 58.99 | 0.00 | 0.00 |
December | 0.268563E+09 | -152571024.9 | 0.00 | 0.00 | 744.00 | 0.00 | -115992462.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.297559E+10 | -0.164367E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133192E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.228437E+09 | -157237978.3 | 0.00 | 0.00 | 672.00 | 0.00 | -118373905.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.275612E+09 | -118093513.0 | 0.00 | 0.00 | 744.00 | 0.00 | -105615994.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 307.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 295.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 353.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 390.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 380.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 342.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 308.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.211195E+09 | 54187.42 | 05-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.448462E+09 | 54187.42 | 05-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.305025E+09 | 54187.42 | 11-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.298021E+09 | 54187.42 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.448462E+09 | 54187.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 20129019.17 | 2337.97 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 85086054.68 | 16208.99 | 05-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 76212704.39 | 7640.19 | 12-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 62102074.02 | 17030.81 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85086054.68 | 17030.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 49281411.61 | 6084.93 | 05-JAN-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121890E+09 | 23610.15 | 05-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 97651516.15 | 14734.18 | 12-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82492253.79 | 6725.47 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.351315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121890E+09 | 23610.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 64308439.69 | 6506.94 | 10-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138803E+09 | 27179.82 | 05-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108272E+09 | 18105.53 | 12-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 91720592.53 | 7871.52 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.403103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138803E+09 | 27179.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 97222528.66 | 9438.50 | 10-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170722E+09 | 28319.35 | 05-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128716E+09 | 21991.30 | 12-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118572E+09 | 9616.43 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.515232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.170722E+09 | 28319.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.307505E+09 | 51485.64 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.413671E+09 | 51485.64 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.288698E+09 | 51485.64 | 12-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.346842E+09 | 51485.64 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.413671E+09 | 51485.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.189825E+09 | 26827.59 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242324E+09 | 26827.59 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164537E+09 | 26827.59 | 12-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205356E+09 | 26827.59 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.802042E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.242324E+09 | 26827.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.215819E+09 | 26731.90 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.259666E+09 | 26731.90 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175460E+09 | 26731.90 | 11-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.222238E+09 | 26731.90 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.873182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.259666E+09 | 26731.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.296190E+09 | 26811.03 | 05-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.313021E+09 | 26811.03 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219974E+09 | 26811.03 | 11-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.273384E+09 | 26811.03 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.313021E+09 | 26811.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.527964E+09 | 30476.45 | 05-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.483247E+09 | 30476.45 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.394143E+09 | 30476.45 | 09-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.431404E+09 | 30476.45 | 20-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.527964E+09 | 30476.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.370820E+10 | 0.234675E+10 | 18671.28 | 19-JAN-15:00 | 10870.19 | 0.00 |
February | 0.00 | 0.00 | 0.484100E+10 | 0.304755E+10 | 19852.27 | 24-FEB-14:00 | 12524.10 | 0.00 |
March | 0.00 | 0.00 | 0.723497E+10 | 0.472484E+10 | 20236.50 | 30-MAR-13:00 | 12464.63 | 0.00 |
April | 0.00 | 0.00 | 0.135487E+11 | 0.896888E+10 | 46191.78 | 29-APR-07:03 | 25890.33 | 0.00 |
May | 0.00 | 0.00 | 0.303179E+11 | 0.187648E+11 | 55563.23 | 21-MAY-07:02 | 28416.46 | 0.00 |
June | 0.00 | 0.00 | 0.323439E+11 | 0.199134E+11 | 54725.14 | 19-JUN-07:02 | 30183.47 | 0.00 |
July | 0.00 | 0.00 | 0.366984E+11 | 0.210699E+11 | 55908.26 | 02-JUL-07:02 | 28160.55 | 0.00 |
August | 0.00 | 0.00 | 0.365245E+11 | 0.217118E+11 | 55591.88 | 16-AUG-07:02 | 29150.88 | 0.00 |
September | 0.00 | 0.00 | 0.324770E+11 | 0.187636E+11 | 56412.83 | 05-SEP-07:02 | 27098.62 | 0.00 |
October | 0.00 | 0.00 | 0.276833E+11 | 0.171310E+11 | 55748.86 | 08-OCT-07:02 | 29792.86 | 0.00 |
November | 0.00 | 0.00 | 0.106043E+11 | 0.675964E+10 | 54055.68 | 02-NOV-07:03 | 33391.83 | 0.00 |
December | 0.00 | 0.00 | 0.694375E+10 | 0.439802E+10 | 42570.10 | 11-DEC-08:62 | 27290.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.242926E+12 | 0.147600E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.370820E+10 | 0.234675E+10 | 18671.28 | 10870.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.366984E+11 | 0.217118E+11 | 56412.83 | 33391.83 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.222736E+10 | 0.144578E+10 | 27306.75 | 01-JAN-18:02 | 14485.85 | 0.00 |
February | 0.00 | 0.00 | 0.287223E+10 | 0.184901E+10 | 27368.12 | 20-FEB-18:02 | 14586.02 | 0.00 |
March | 0.00 | 0.00 | 0.417983E+10 | 0.279740E+10 | 27840.12 | 31-MAR-20:02 | 12898.39 | 0.00 |
April | 0.00 | 0.00 | 0.749205E+10 | 0.509295E+10 | 26861.74 | 18-APR-21:03 | 15945.55 | 0.00 |
May | 0.00 | 0.00 | 0.154468E+11 | 0.980293E+10 | 28091.34 | 21-MAY-07:02 | 17671.27 | 0.00 |
June | 0.00 | 0.00 | 0.163095E+11 | 0.102561E+11 | 27519.88 | 04-JUN-07:02 | 19032.69 | 0.00 |
July | 0.00 | 0.00 | 0.183915E+11 | 0.107907E+11 | 28130.19 | 03-JUL-07:02 | 18249.57 | 0.00 |
August | 0.00 | 0.00 | 0.181547E+11 | 0.109784E+11 | 28262.00 | 16-AUG-07:02 | 17513.16 | 0.00 |
September | 0.00 | 0.00 | 0.162286E+11 | 0.956434E+10 | 28571.35 | 05-SEP-07:02 | 17016.78 | 0.00 |
October | 0.00 | 0.00 | 0.140246E+11 | 0.886121E+10 | 28239.14 | 08-OCT-07:02 | 18247.18 | 0.00 |
November | 0.00 | 0.00 | 0.574429E+10 | 0.374792E+10 | 27546.72 | 29-NOV-21:44 | 13238.93 | 0.00 |
December | 0.00 | 0.00 | 0.374111E+10 | 0.243338E+10 | 27287.67 | 08-DEC-22:00 | 13694.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124813E+12 | 0.776202E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.222736E+10 | 0.144578E+10 | 26861.74 | 12898.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.183915E+11 | 0.109784E+11 | 28571.35 | 19032.69 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.168443E+10 | 0.108814E+10 | 9650.85 | 19-JAN-14:00 | 5641.81 | 0.00 |
February | 0.00 | 0.00 | 0.231337E+10 | 0.147278E+10 | 10599.43 | 28-FEB-07:03 | 5129.16 | 0.00 |
March | 0.00 | 0.00 | 0.326772E+10 | 0.216232E+10 | 13796.83 | 30-MAR-06:03 | 8886.71 | 0.00 |
April | 0.00 | 0.00 | 0.583037E+10 | 0.392741E+10 | 28963.02 | 30-APR-07:03 | 12880.06 | 0.00 |
May | 0.00 | 0.00 | 0.125590E+11 | 0.781841E+10 | 29793.81 | 21-MAY-07:02 | 14154.89 | 0.00 |
June | 0.00 | 0.00 | 0.134188E+11 | 0.826390E+10 | 30214.43 | 19-JUN-06:02 | 13088.72 | 0.00 |
July | 0.00 | 0.00 | 0.148438E+11 | 0.849098E+10 | 30431.28 | 05-JUL-06:02 | 13061.52 | 0.00 |
August | 0.00 | 0.00 | 0.150152E+11 | 0.886180E+10 | 30431.28 | 14-AUG-06:02 | 12626.25 | 0.00 |
September | 0.00 | 0.00 | 0.130807E+11 | 0.749220E+10 | 30457.11 | 05-SEP-06:02 | 12977.88 | 0.00 |
October | 0.00 | 0.00 | 0.111986E+11 | 0.692777E+10 | 30169.91 | 08-OCT-07:02 | 14031.19 | 0.00 |
November | 0.00 | 0.00 | 0.462488E+10 | 0.299300E+10 | 28861.78 | 02-NOV-06:03 | 17023.90 | 0.00 |
December | 0.00 | 0.00 | 0.301993E+10 | 0.193334E+10 | 28778.27 | 15-DEC-07:03 | 17037.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.100857E+12 | 0.614321E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.168443E+10 | 0.108814E+10 | 9650.85 | 5129.16 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.150152E+11 | 0.886180E+10 | 30457.11 | 17037.45 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.163341E+10 | 0.105180E+10 | 9580.76 | 19-JAN-14:00 | 5593.79 | 0.00 |
February | 0.00 | 0.00 | 0.226126E+10 | 0.143622E+10 | 10194.67 | 28-FEB-07:03 | 4930.75 | 0.00 |
March | 0.00 | 0.00 | 0.322480E+10 | 0.212968E+10 | 13635.15 | 30-MAR-06:03 | 8773.72 | 0.00 |
April | 0.00 | 0.00 | 0.580948E+10 | 0.391097E+10 | 29081.63 | 30-APR-07:03 | 12937.35 | 0.00 |
May | 0.00 | 0.00 | 0.126016E+11 | 0.785102E+10 | 29917.10 | 21-MAY-07:02 | 14228.15 | 0.00 |
June | 0.00 | 0.00 | 0.134726E+11 | 0.830539E+10 | 30343.97 | 19-JUN-06:02 | 13195.78 | 0.00 |
July | 0.00 | 0.00 | 0.149185E+11 | 0.854673E+10 | 30555.02 | 05-JUL-06:02 | 13205.21 | 0.00 |
August | 0.00 | 0.00 | 0.150804E+11 | 0.891114E+10 | 30555.02 | 14-AUG-06:02 | 12758.21 | 0.00 |
September | 0.00 | 0.00 | 0.131417E+11 | 0.753753E+10 | 30592.99 | 05-SEP-06:02 | 13119.04 | 0.00 |
October | 0.00 | 0.00 | 0.112396E+11 | 0.695940E+10 | 30301.16 | 08-OCT-07:02 | 14148.57 | 0.00 |
November | 0.00 | 0.00 | 0.460293E+10 | 0.297796E+10 | 28982.60 | 02-NOV-06:03 | 17090.20 | 0.00 |
December | 0.00 | 0.00 | 0.299433E+10 | 0.191393E+10 | 28897.70 | 15-DEC-07:03 | 17103.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.100981E+12 | 0.615318E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.163341E+10 | 0.105180E+10 | 9580.76 | 4930.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.150804E+11 | 0.891114E+10 | 30592.99 | 17103.75 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.150821E+10 | 0.965492E+09 | 9347.01 | 19-JAN-14:00 | 5430.32 | 0.00 |
February | 0.00 | 0.00 | 0.212783E+10 | 0.134404E+10 | 9737.71 | 24-FEB-14:00 | 6199.55 | 0.00 |
March | 0.00 | 0.00 | 0.307446E+10 | 0.201887E+10 | 11583.33 | 30-MAR-06:03 | 7383.37 | 0.00 |
April | 0.00 | 0.00 | 0.560051E+10 | 0.375524E+10 | 28877.76 | 30-APR-07:03 | 12822.42 | 0.00 |
May | 0.00 | 0.00 | 0.123932E+11 | 0.769479E+10 | 29696.25 | 21-MAY-07:02 | 14001.62 | 0.00 |
June | 0.00 | 0.00 | 0.132794E+11 | 0.815812E+10 | 30123.99 | 19-JUN-06:02 | 12988.36 | 0.00 |
July | 0.00 | 0.00 | 0.147256E+11 | 0.840516E+10 | 30344.02 | 05-JUL-06:02 | 13012.91 | 0.00 |
August | 0.00 | 0.00 | 0.148850E+11 | 0.876513E+10 | 30344.02 | 14-AUG-06:02 | 12568.42 | 0.00 |
September | 0.00 | 0.00 | 0.129552E+11 | 0.740191E+10 | 30374.12 | 05-SEP-06:02 | 12963.42 | 0.00 |
October | 0.00 | 0.00 | 0.110675E+11 | 0.682872E+10 | 30081.39 | 08-OCT-07:02 | 13955.80 | 0.00 |
November | 0.00 | 0.00 | 0.444876E+10 | 0.286241E+10 | 28779.17 | 02-NOV-06:03 | 16800.36 | 0.00 |
December | 0.00 | 0.00 | 0.288773E+10 | 0.183523E+10 | 26552.90 | 11-DEC-07:03 | 16187.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.989534E+11 | 0.600351E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.150821E+10 | 0.965492E+09 | 9347.01 | 5430.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.148850E+11 | 0.876513E+10 | 30374.12 | 16800.36 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.258525E+10 | 0.161423E+10 | 17993.39 | 19-JAN-14:00 | 10047.15 | 0.00 |
February | 0.00 | 0.00 | 0.381161E+10 | 0.234534E+10 | 18780.36 | 24-FEB-13:50 | 11626.69 | 0.00 |
March | 0.00 | 0.00 | 0.551951E+10 | 0.352759E+10 | 21052.01 | 30-MAR-13:00 | 12674.07 | 0.00 |
April | 0.00 | 0.00 | 0.103498E+11 | 0.680295E+10 | 45274.91 | 29-APR-07:03 | 26458.63 | 0.00 |
May | 0.00 | 0.00 | 0.231180E+11 | 0.140581E+11 | 53207.86 | 21-MAY-08:62 | 24583.78 | 0.00 |
June | 0.00 | 0.00 | 0.249498E+11 | 0.150224E+11 | 53760.51 | 19-JUN-07:02 | 22974.99 | 0.00 |
July | 0.00 | 0.00 | 0.275915E+11 | 0.153720E+11 | 54213.62 | 03-JUL-07:02 | 23332.63 | 0.00 |
August | 0.00 | 0.00 | 0.280493E+11 | 0.161525E+11 | 54212.43 | 14-AUG-07:02 | 22338.32 | 0.00 |
September | 0.00 | 0.00 | 0.241281E+11 | 0.133925E+11 | 54280.11 | 05-SEP-07:02 | 23017.57 | 0.00 |
October | 0.00 | 0.00 | 0.208097E+11 | 0.125381E+11 | 53805.81 | 08-OCT-08:62 | 24423.25 | 0.00 |
November | 0.00 | 0.00 | 0.818877E+10 | 0.512211E+10 | 50939.36 | 02-NOV-07:03 | 30908.47 | 0.00 |
December | 0.00 | 0.00 | 0.527643E+10 | 0.326446E+10 | 46573.61 | 11-DEC-08:62 | 27906.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184378E+12 | 0.109212E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.258525E+10 | 0.161423E+10 | 17993.39 | 10047.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.280493E+11 | 0.161525E+11 | 54280.11 | 30908.47 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.130748E+10 | 0.815925E+09 | 9279.82 | 19-JAN-14:00 | 5173.51 | 0.00 |
February | 0.00 | 0.00 | 0.193899E+10 | 0.119271E+10 | 9736.18 | 24-FEB-13:50 | 6022.02 | 0.00 |
March | 0.00 | 0.00 | 0.281852E+10 | 0.179669E+10 | 11028.25 | 30-MAR-13:00 | 6627.27 | 0.00 |
April | 0.00 | 0.00 | 0.533930E+10 | 0.350987E+10 | 21644.92 | 29-APR-07:03 | 12635.56 | 0.00 |
May | 0.00 | 0.00 | 0.120466E+11 | 0.732783E+10 | 27951.24 | 21-MAY-08:62 | 12859.19 | 0.00 |
June | 0.00 | 0.00 | 0.130087E+11 | 0.783247E+10 | 28273.06 | 19-JUN-07:02 | 11962.76 | 0.00 |
July | 0.00 | 0.00 | 0.143930E+11 | 0.801920E+10 | 28499.44 | 03-JUL-07:02 | 12172.94 | 0.00 |
August | 0.00 | 0.00 | 0.146192E+11 | 0.841844E+10 | 28465.13 | 14-AUG-07:02 | 11585.50 | 0.00 |
September | 0.00 | 0.00 | 0.125616E+11 | 0.697344E+10 | 28517.06 | 05-SEP-07:02 | 12044.81 | 0.00 |
October | 0.00 | 0.00 | 0.108220E+11 | 0.651793E+10 | 28268.21 | 08-OCT-08:62 | 12758.24 | 0.00 |
November | 0.00 | 0.00 | 0.421435E+10 | 0.263153E+10 | 25108.91 | 02-NOV-07:03 | 15242.76 | 0.00 |
December | 0.00 | 0.00 | 0.271483E+10 | 0.167722E+10 | 22729.20 | 11-DEC-08:62 | 13528.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.957846E+11 | 0.567133E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.130748E+10 | 0.815925E+09 | 9279.82 | 5173.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.146192E+11 | 0.841844E+10 | 28517.06 | 15242.76 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.127564E+10 | 0.794717E+09 | 9190.43 | 19-JAN-14:00 | 5114.34 | 0.00 |
February | 0.00 | 0.00 | 0.189405E+10 | 0.116304E+10 | 9647.28 | 24-FEB-13:50 | 5958.20 | 0.00 |
March | 0.00 | 0.00 | 0.276497E+10 | 0.175747E+10 | 10966.89 | 30-MAR-13:00 | 6583.66 | 0.00 |
April | 0.00 | 0.00 | 0.527504E+10 | 0.346312E+10 | 21042.09 | 29-APR-07:03 | 12236.10 | 0.00 |
May | 0.00 | 0.00 | 0.119823E+11 | 0.728147E+10 | 27830.76 | 21-MAY-08:62 | 12777.04 | 0.00 |
June | 0.00 | 0.00 | 0.129501E+11 | 0.778938E+10 | 28152.01 | 19-JUN-07:02 | 11884.27 | 0.00 |
July | 0.00 | 0.00 | 0.143390E+11 | 0.798091E+10 | 28378.19 | 03-JUL-07:02 | 12105.63 | 0.00 |
August | 0.00 | 0.00 | 0.145669E+11 | 0.838060E+10 | 28345.25 | 14-AUG-07:02 | 11525.06 | 0.00 |
September | 0.00 | 0.00 | 0.125083E+11 | 0.693620E+10 | 28396.96 | 05-SEP-07:02 | 11985.59 | 0.00 |
October | 0.00 | 0.00 | 0.107677E+11 | 0.647817E+10 | 28147.58 | 08-OCT-08:62 | 12685.77 | 0.00 |
November | 0.00 | 0.00 | 0.416649E+10 | 0.259603E+10 | 24558.42 | 02-NOV-07:03 | 14858.22 | 0.00 |
December | 0.00 | 0.00 | 0.267922E+10 | 0.165138E+10 | 21762.04 | 11-DEC-08:62 | 12909.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.951696E+11 | 0.562725E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.127564E+10 | 0.794717E+09 | 9190.43 | 5114.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.145669E+11 | 0.838060E+10 | 28396.96 | 14858.22 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.121114E+10 | 0.752341E+09 | 9068.82 | 19-JAN-14:00 | 5035.09 | 0.00 |
February | 0.00 | 0.00 | 0.179465E+10 | 0.109895E+10 | 9491.88 | 24-FEB-14:00 | 5845.74 | 0.00 |
March | 0.00 | 0.00 | 0.265151E+10 | 0.167550E+10 | 10862.24 | 30-MAR-13:00 | 6508.37 | 0.00 |
April | 0.00 | 0.00 | 0.512516E+10 | 0.335564E+10 | 18196.11 | 29-APR-07:03 | 10441.48 | 0.00 |
May | 0.00 | 0.00 | 0.119106E+11 | 0.723090E+10 | 27913.48 | 21-MAY-08:62 | 12718.37 | 0.00 |
June | 0.00 | 0.00 | 0.129185E+11 | 0.776575E+10 | 28235.80 | 19-JUN-07:02 | 11826.12 | 0.00 |
July | 0.00 | 0.00 | 0.143461E+11 | 0.798700E+10 | 28471.15 | 03-JUL-07:02 | 12110.79 | 0.00 |
August | 0.00 | 0.00 | 0.145976E+11 | 0.840305E+10 | 28444.36 | 14-AUG-07:02 | 11539.38 | 0.00 |
September | 0.00 | 0.00 | 0.125128E+11 | 0.693985E+10 | 28495.60 | 05-SEP-07:02 | 12012.21 | 0.00 |
October | 0.00 | 0.00 | 0.107435E+11 | 0.646025E+10 | 28241.28 | 08-OCT-08:62 | 12710.96 | 0.00 |
November | 0.00 | 0.00 | 0.406199E+10 | 0.251850E+10 | 22821.92 | 02-NOV-07:03 | 13688.92 | 0.00 |
December | 0.00 | 0.00 | 0.260697E+10 | 0.159922E+10 | 18830.21 | 11-DEC-08:62 | 11051.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.944806E+11 | 0.557869E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.121114E+10 | 0.752341E+09 | 9068.82 | 5035.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.145976E+11 | 0.840305E+10 | 28495.60 | 13688.92 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.129307E+10 | 0.810573E+09 | 10038.46 | 19-JAN-14:00 | 5707.10 | 0.00 |
February | 0.00 | 0.00 | 0.189805E+10 | 0.117205E+10 | 10380.75 | 24-FEB-13:10 | 6438.50 | 0.00 |
March | 0.00 | 0.00 | 0.286752E+10 | 0.182674E+10 | 11766.91 | 30-MAR-13:00 | 7141.31 | 0.00 |
April | 0.00 | 0.00 | 0.547974E+10 | 0.362334E+10 | 15678.16 | 28-APR-16:20 | 9140.43 | 0.00 |
May | 0.00 | 0.00 | 0.131204E+11 | 0.806408E+10 | 32595.22 | 21-MAY-08:62 | 14100.74 | 0.00 |
June | 0.00 | 0.00 | 0.143699E+11 | 0.878238E+10 | 32940.55 | 19-JUN-07:02 | 13180.58 | 0.00 |
July | 0.00 | 0.00 | 0.160654E+11 | 0.915646E+10 | 33083.78 | 03-JUL-07:02 | 13327.44 | 0.00 |
August | 0.00 | 0.00 | 0.164930E+11 | 0.969668E+10 | 33037.48 | 07-AUG-07:02 | 14161.74 | 0.00 |
September | 0.00 | 0.00 | 0.140418E+11 | 0.796439E+10 | 33096.32 | 05-SEP-07:02 | 13645.99 | 0.00 |
October | 0.00 | 0.00 | 0.120243E+11 | 0.735033E+10 | 32995.54 | 08-OCT-08:62 | 14340.68 | 0.00 |
November | 0.00 | 0.00 | 0.439121E+10 | 0.275359E+10 | 23969.41 | 02-NOV-07:03 | 13220.49 | 0.00 |
December | 0.00 | 0.00 | 0.274906E+10 | 0.169594E+10 | 12983.65 | 16-DEC-13:10 | 7972.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104793E+12 | 0.628966E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.129307E+10 | 0.810573E+09 | 10038.46 | 5707.10 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.164930E+11 | 0.969668E+10 | 33096.32 | 14340.68 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156823E+10 | 0.36 | 2153.87 | 05-JAN-08:61 | 0.88 |
February | 0.142501E+10 | 0.36 | 2153.87 | 05-FEB-08:61 | 0.88 |
March | 0.157667E+10 | 0.36 | 2153.87 | 11-MAR-08:61 | 0.88 |
April | 0.151436E+10 | 0.36 | 1758.67 | 29-APR-07:03 | 0.79 |
May | 0.157395E+10 | 0.36 | 2153.87 | 06-MAY-07:03 | 0.87 |
June | 0.155090E+10 | 0.36 | 2153.87 | 03-JUN-07:02 | 0.86 |
July | 0.164485E+10 | 0.37 | 2153.87 | 01-JUL-07:02 | 0.86 |
August | 0.164412E+10 | 0.37 | 2153.87 | 01-AUG-07:03 | 0.86 |
September | 0.157209E+10 | 0.36 | 2153.87 | 01-SEP-07:02 | 0.87 |
October | 0.160340E+10 | 0.36 | 2153.87 | 04-OCT-07:02 | 0.87 |
November | 0.151193E+10 | 0.36 | 2153.87 | 02-NOV-07:03 | 0.87 |
December | 0.157681E+10 | 0.36 | 2153.87 | 21-DEC-08:61 | 0.88 |
Annual Sum or Average | 0.187623E+11 | 0.36 | |||
Minimum of Months | 0.142501E+10 | 0.36 | 1758.67 | 0.79 | |
Maximum of Months | 0.164485E+10 | 0.37 | 2153.87 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.709219E+09 | 0.35 | 523.63 | 10-JAN-08:61 | 0.59 |
February | 0.678972E+09 | 0.35 | 868.15 | 05-FEB-08:61 | 0.79 |
March | 0.753213E+09 | 0.36 | 655.32 | 12-MAR-07:02 | 0.68 |
April | 0.731072E+09 | 0.37 | 1000.40 | 30-APR-07:03 | 0.84 |
May | 0.733690E+09 | 0.37 | 1163.92 | 06-MAY-07:03 | 0.90 |
June | 0.730055E+09 | 0.38 | 1163.92 | 03-JUN-07:02 | 0.90 |
July | 0.784072E+09 | 0.38 | 1163.92 | 01-JUL-07:02 | 0.90 |
August | 0.781675E+09 | 0.38 | 1163.92 | 01-AUG-07:03 | 0.90 |
September | 0.739359E+09 | 0.38 | 1163.92 | 01-SEP-07:02 | 0.90 |
October | 0.758912E+09 | 0.37 | 1163.92 | 04-OCT-07:02 | 0.90 |
November | 0.757113E+09 | 0.37 | 1101.08 | 02-NOV-07:03 | 0.88 |
December | 0.751595E+09 | 0.36 | 888.56 | 21-DEC-08:61 | 0.80 |
Annual Sum or Average | 0.890895E+10 | 0.37 | |||
Minimum of Months | 0.678972E+09 | 0.35 | 523.63 | 0.59 | |
Maximum of Months | 0.784072E+09 | 0.38 | 1163.92 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.682607E+09 | 0.30 | 622.20 | 05-JAN-08:07 | 0.66 |
February | 0.620004E+09 | 0.30 | 1058.18 | 05-FEB-08:61 | 0.87 |
March | 0.697370E+09 | 0.30 | 837.37 | 12-MAR-07:02 | 0.77 |
April | 0.661551E+09 | 0.30 | 1177.07 | 29-APR-06:03 | 0.89 |
May | 0.692484E+09 | 0.30 | 1177.07 | 01-MAY-06:03 | 0.89 |
June | 0.684654E+09 | 0.30 | 1177.07 | 02-JUN-06:03 | 0.89 |
July | 0.714536E+09 | 0.30 | 1177.07 | 01-JUL-06:02 | 0.89 |
August | 0.725372E+09 | 0.31 | 1177.07 | 01-AUG-06:02 | 0.89 |
September | 0.682163E+09 | 0.30 | 1177.07 | 01-SEP-06:02 | 0.89 |
October | 0.697916E+09 | 0.30 | 1177.07 | 03-OCT-06:03 | 0.90 |
November | 0.661871E+09 | 0.30 | 1177.07 | 01-NOV-06:03 | 0.90 |
December | 0.680563E+09 | 0.29 | 1177.07 | 11-DEC-07:03 | 0.90 |
Annual Sum or Average | 0.820109E+10 | 0.30 | |||
Minimum of Months | 0.620004E+09 | 0.29 | 622.20 | 0.66 | |
Maximum of Months | 0.725372E+09 | 0.31 | 1177.07 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.685753E+09 | 0.30 | 634.71 | 10-JAN-07:03 | 0.66 |
February | 0.622936E+09 | 0.30 | 1149.30 | 05-FEB-08:61 | 0.90 |
March | 0.700462E+09 | 0.30 | 923.42 | 12-MAR-07:02 | 0.81 |
April | 0.664233E+09 | 0.30 | 1181.86 | 29-APR-06:03 | 0.89 |
May | 0.695231E+09 | 0.30 | 1181.86 | 01-MAY-06:03 | 0.89 |
June | 0.687188E+09 | 0.30 | 1181.86 | 02-JUN-06:03 | 0.89 |
July | 0.717362E+09 | 0.30 | 1181.86 | 01-JUL-06:02 | 0.89 |
August | 0.727991E+09 | 0.31 | 1181.86 | 01-AUG-06:02 | 0.89 |
September | 0.684842E+09 | 0.30 | 1181.86 | 01-SEP-06:02 | 0.89 |
October | 0.700601E+09 | 0.30 | 1181.86 | 03-OCT-06:03 | 0.90 |
November | 0.664540E+09 | 0.30 | 1181.86 | 01-NOV-06:03 | 0.90 |
December | 0.683550E+09 | 0.29 | 1181.86 | 11-DEC-07:03 | 0.90 |
Annual Sum or Average | 0.823469E+10 | 0.30 | |||
Minimum of Months | 0.622936E+09 | 0.29 | 634.71 | 0.66 | |
Maximum of Months | 0.727991E+09 | 0.31 | 1181.86 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.681846E+09 | 0.30 | 704.18 | 10-JAN-07:03 | 0.71 |
February | 0.619449E+09 | 0.30 | 1173.69 | 05-FEB-08:61 | 0.91 |
March | 0.696150E+09 | 0.30 | 1016.33 | 12-MAR-07:02 | 0.85 |
April | 0.659557E+09 | 0.30 | 1173.69 | 30-APR-07:03 | 0.89 |
May | 0.690197E+09 | 0.30 | 1173.69 | 02-MAY-06:03 | 0.89 |
June | 0.681785E+09 | 0.30 | 1173.69 | 02-JUN-06:03 | 0.89 |
July | 0.711398E+09 | 0.30 | 1173.69 | 01-JUL-06:02 | 0.89 |
August | 0.721866E+09 | 0.31 | 1173.69 | 01-AUG-06:02 | 0.89 |
September | 0.679607E+09 | 0.30 | 1173.69 | 01-SEP-06:02 | 0.89 |
October | 0.695242E+09 | 0.30 | 1173.69 | 03-OCT-06:03 | 0.90 |
November | 0.659846E+09 | 0.30 | 1173.69 | 02-NOV-06:03 | 0.89 |
December | 0.679389E+09 | 0.29 | 1076.82 | 11-DEC-07:03 | 0.86 |
Annual Sum or Average | 0.817633E+10 | 0.30 | |||
Minimum of Months | 0.619449E+09 | 0.29 | 704.18 | 0.71 | |
Maximum of Months | 0.721866E+09 | 0.31 | 1173.69 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109033E+10 | 0.26 | 2027.30 | 10-JAN-08:61 | 0.88 |
February | 0.990662E+09 | 0.27 | 2027.30 | 05-FEB-09:01 | 0.88 |
March | 0.111324E+10 | 0.27 | 2027.30 | 12-MAR-08:61 | 0.88 |
April | 0.105305E+10 | 0.26 | 1753.70 | 29-APR-07:03 | 0.81 |
May | 0.111794E+10 | 0.27 | 2027.30 | 05-MAY-07:03 | 0.87 |
June | 0.112444E+10 | 0.27 | 2027.30 | 02-JUN-07:03 | 0.87 |
July | 0.119347E+10 | 0.28 | 2027.30 | 01-JUL-07:02 | 0.86 |
August | 0.121513E+10 | 0.28 | 2027.30 | 01-AUG-07:03 | 0.86 |
September | 0.112029E+10 | 0.27 | 2027.30 | 01-SEP-07:02 | 0.87 |
October | 0.113966E+10 | 0.27 | 2027.30 | 04-OCT-07:02 | 0.87 |
November | 0.105381E+10 | 0.26 | 2027.30 | 02-NOV-07:03 | 0.87 |
December | 0.108574E+10 | 0.26 | 2027.30 | 21-DEC-08:61 | 0.88 |
Annual Sum or Average | 0.132978E+11 | 0.27 | |||
Minimum of Months | 0.990662E+09 | 0.26 | 1753.70 | 0.81 | |
Maximum of Months | 0.121513E+10 | 0.28 | 2027.30 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.593079E+09 | 0.27 | 1101.38 | 10-JAN-08:61 | 0.91 |
February | 0.538862E+09 | 0.27 | 1101.38 | 05-FEB-09:01 | 0.91 |
March | 0.605144E+09 | 0.28 | 1101.38 | 12-MAR-08:61 | 0.91 |
April | 0.572028E+09 | 0.27 | 848.73 | 29-APR-07:03 | 0.79 |
May | 0.607467E+09 | 0.28 | 1101.38 | 06-MAY-07:03 | 0.90 |
June | 0.611063E+09 | 0.28 | 1101.38 | 02-JUN-07:03 | 0.90 |
July | 0.648830E+09 | 0.29 | 1101.38 | 01-JUL-07:02 | 0.89 |
August | 0.660265E+09 | 0.29 | 1101.38 | 01-AUG-07:03 | 0.89 |
September | 0.608402E+09 | 0.28 | 1101.38 | 01-SEP-07:02 | 0.90 |
October | 0.618692E+09 | 0.28 | 1101.38 | 04-OCT-07:02 | 0.90 |
November | 0.572334E+09 | 0.27 | 1021.36 | 02-NOV-07:03 | 0.87 |
December | 0.590404E+09 | 0.27 | 1101.38 | 21-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.722657E+10 | 0.28 | |||
Minimum of Months | 0.538862E+09 | 0.27 | 848.73 | 0.79 | |
Maximum of Months | 0.660265E+09 | 0.29 | 1101.38 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.591238E+09 | 0.27 | 1096.74 | 10-JAN-08:61 | 0.91 |
February | 0.537041E+09 | 0.28 | 1096.74 | 05-FEB-09:01 | 0.91 |
March | 0.602879E+09 | 0.28 | 1096.74 | 11-MAR-08:61 | 0.91 |
April | 0.569608E+09 | 0.27 | 819.90 | 29-APR-07:03 | 0.78 |
May | 0.604923E+09 | 0.28 | 1096.74 | 06-MAY-07:03 | 0.90 |
June | 0.608658E+09 | 0.28 | 1096.74 | 03-JUN-07:02 | 0.89 |
July | 0.646535E+09 | 0.29 | 1096.74 | 01-JUL-07:02 | 0.89 |
August | 0.657972E+09 | 0.29 | 1096.74 | 01-AUG-07:03 | 0.89 |
September | 0.606123E+09 | 0.28 | 1096.74 | 01-SEP-07:02 | 0.90 |
October | 0.616263E+09 | 0.28 | 1096.74 | 04-OCT-07:02 | 0.90 |
November | 0.569891E+09 | 0.27 | 994.98 | 02-NOV-07:03 | 0.86 |
December | 0.588336E+09 | 0.27 | 1096.74 | 21-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.719947E+10 | 0.28 | |||
Minimum of Months | 0.537041E+09 | 0.27 | 819.90 | 0.78 | |
Maximum of Months | 0.657972E+09 | 0.29 | 1096.74 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.595270E+09 | 0.28 | 1100.58 | 05-JAN-08:61 | 0.91 |
February | 0.540215E+09 | 0.28 | 1100.58 | 05-FEB-09:01 | 0.91 |
March | 0.606071E+09 | 0.28 | 1100.58 | 11-MAR-08:61 | 0.91 |
April | 0.571430E+09 | 0.27 | 679.63 | 29-APR-07:03 | 0.71 |
May | 0.605954E+09 | 0.28 | 1100.58 | 07-MAY-08:62 | 0.89 |
June | 0.609872E+09 | 0.28 | 1100.58 | 03-JUN-07:02 | 0.89 |
July | 0.648375E+09 | 0.29 | 1100.58 | 01-JUL-07:02 | 0.89 |
August | 0.660071E+09 | 0.29 | 1100.58 | 01-AUG-07:03 | 0.89 |
September | 0.608050E+09 | 0.28 | 1100.58 | 01-SEP-07:02 | 0.90 |
October | 0.618025E+09 | 0.28 | 1100.58 | 04-OCT-07:02 | 0.90 |
November | 0.571664E+09 | 0.27 | 908.88 | 02-NOV-07:03 | 0.82 |
December | 0.591579E+09 | 0.27 | 1100.58 | 21-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.722658E+10 | 0.28 | |||
Minimum of Months | 0.540215E+09 | 0.27 | 679.63 | 0.71 | |
Maximum of Months | 0.660071E+09 | 0.29 | 1100.58 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.696176E+09 | 0.28 | 1278.24 | 05-JAN-08:61 | 0.91 |
February | 0.630627E+09 | 0.28 | 1278.24 | 05-FEB-09:01 | 0.91 |
March | 0.707534E+09 | 0.28 | 1278.24 | 09-MAR-08:62 | 0.91 |
April | 0.662684E+09 | 0.27 | 534.85 | 28-APR-16:10 | 0.56 |
May | 0.695299E+09 | 0.27 | 1278.24 | 08-MAY-07:02 | 0.89 |
June | 0.694921E+09 | 0.28 | 1278.24 | 03-JUN-07:02 | 0.89 |
July | 0.737789E+09 | 0.28 | 1278.24 | 01-JUL-07:02 | 0.89 |
August | 0.751334E+09 | 0.29 | 1278.24 | 01-AUG-07:03 | 0.89 |
September | 0.697014E+09 | 0.28 | 1278.24 | 01-SEP-07:02 | 0.90 |
October | 0.708038E+09 | 0.28 | 1278.24 | 04-OCT-07:02 | 0.90 |
November | 0.663081E+09 | 0.27 | 915.97 | 02-NOV-07:03 | 0.76 |
December | 0.690065E+09 | 0.27 | 1278.24 | 20-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.833456E+10 | 0.28 | |||
Minimum of Months | 0.630627E+09 | 0.27 | 534.85 | 0.56 | |
Maximum of Months | 0.751334E+09 | 0.29 | 1278.24 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.247934E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.260921E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.336724E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.486571E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.894141E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.936580E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.103534E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.103112E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.920663E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.815922E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.406459E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.325451E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.769783E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.247934E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.103534E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.124435E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.136834E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.176412E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.255051E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.444028E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.462738E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.510605E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.504911E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.451358E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.404141E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.211740E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.164091E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.384634E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.124435E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.510605E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.109080E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.117736E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.149205E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.208210E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.369352E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.387135E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.417435E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.422702E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.369686E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.330535E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.176013E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.139835E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.319692E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.109080E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.422702E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.108238E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.116864E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.148567E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.208081E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.370753E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.388742E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.419506E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.424537E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.371403E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.331816E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.175834E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.139562E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.320390E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.108238E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.424537E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.104944E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.113436E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.144670E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.202753E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.365551E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.383787E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.414482E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.419438E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.366723E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.327392E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.171806E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.136701E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.315168E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.104944E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.419438E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.172736E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.192246E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.247215E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.359870E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.665643E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.707184E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.765379E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.779692E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.669534E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.600949E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.301107E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.234781E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.569634E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.172736E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.779692E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.910134E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.100542E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.128799E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.186414E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.344753E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.366288E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.396648E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.403706E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.346492E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.311062E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.156295E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.122911E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.295492E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.910134E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.403706E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.900825E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.993174E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.127317E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.184656E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.342954E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.364614E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.395101E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.402192E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.344997E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.309531E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.154921E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.121880E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.293756E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.900825E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.402192E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.889922E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.973720E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.125053E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.181470E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.341632E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.364155E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.395579E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.403194E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.345404E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.309267E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.152706E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.120619E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.292544E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.889922E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.403194E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.101356E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.109445E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.141104E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.200674E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.382813E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.410038E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.447623E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.458924E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.391897E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.349898E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.170702E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.134773E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.329925E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.101356E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.458924E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156823E+10 | 0.370820E+10 | 0.211195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142501E+10 | 0.484100E+10 | 0.448462E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157667E+10 | 0.723497E+10 | 0.305025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151436E+10 | 0.135487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157395E+10 | 0.303179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155090E+10 | 0.323439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.164485E+10 | 0.366984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164412E+10 | 0.365245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157209E+10 | 0.324770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160340E+10 | 0.276833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151193E+10 | 0.106043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157681E+10 | 0.694375E+10 | 0.298021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187623E+11 | 0.242926E+12 | 0.126270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142501E+10 | 0.370820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164485E+10 | 0.366984E+11 | 0.448462E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.709219E+09 | 0.221613E+10 | 20129019.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.678972E+09 | 0.287037E+10 | 85086054.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.753213E+09 | 0.416089E+10 | 76212704.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.731072E+09 | 0.746258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.733690E+09 | 0.154468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.730055E+09 | 0.163095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.784072E+09 | 0.183915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.781675E+09 | 0.181547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.739359E+09 | 0.162224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.758912E+09 | 0.140044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.757113E+09 | 0.572612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.751595E+09 | 0.374000E+10 | 62102074.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.890895E+10 | 0.124705E+12 | 0.243530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.678972E+09 | 0.221613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.784072E+09 | 0.183915E+11 | 85086054.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.682607E+09 | 0.168443E+10 | 49281411.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.620004E+09 | 0.231337E+10 | 0.121890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.697370E+09 | 0.326772E+10 | 97651516.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.661551E+09 | 0.583037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.692484E+09 | 0.125590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.684654E+09 | 0.134188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.714536E+09 | 0.148438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.725372E+09 | 0.150152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.682163E+09 | 0.130807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.697916E+09 | 0.111986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.661871E+09 | 0.462488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.680563E+09 | 0.301993E+10 | 82492253.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.820109E+10 | 0.100857E+12 | 0.351315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.620004E+09 | 0.168443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.725372E+09 | 0.150152E+11 | 0.121890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.685753E+09 | 0.163341E+10 | 64308439.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.622936E+09 | 0.226126E+10 | 0.138803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.700462E+09 | 0.322480E+10 | 0.108272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.664233E+09 | 0.580948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.695231E+09 | 0.126016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.687188E+09 | 0.134726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.717362E+09 | 0.149185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.727991E+09 | 0.150804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.684842E+09 | 0.131417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.700601E+09 | 0.112396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.664540E+09 | 0.460293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.683550E+09 | 0.299433E+10 | 91720592.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.823469E+10 | 0.100981E+12 | 0.403103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.622936E+09 | 0.163341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.727991E+09 | 0.150804E+11 | 0.138803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.681846E+09 | 0.150821E+10 | 97222528.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.619449E+09 | 0.212783E+10 | 0.170722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.696150E+09 | 0.307446E+10 | 0.128716E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.659557E+09 | 0.560051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.690197E+09 | 0.123932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.681785E+09 | 0.132794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.711398E+09 | 0.147256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.721866E+09 | 0.148850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.679607E+09 | 0.129552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.695242E+09 | 0.110675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.659846E+09 | 0.444876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.679389E+09 | 0.288773E+10 | 0.118572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.817633E+10 | 0.989534E+11 | 0.515232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.619449E+09 | 0.150821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.721866E+09 | 0.148850E+11 | 0.170722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109033E+10 | 0.258525E+10 | 0.307505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.990662E+09 | 0.381161E+10 | 0.413671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111324E+10 | 0.551951E+10 | 0.288698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105305E+10 | 0.103498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111794E+10 | 0.231180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112444E+10 | 0.249498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119347E+10 | 0.275915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.121513E+10 | 0.280493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112029E+10 | 0.241281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113966E+10 | 0.208097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105381E+10 | 0.818877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108574E+10 | 0.527643E+10 | 0.346842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132978E+11 | 0.184378E+12 | 0.135672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.990662E+09 | 0.258525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.121513E+10 | 0.280493E+11 | 0.413671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.593079E+09 | 0.130748E+10 | 0.189825E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.538862E+09 | 0.193899E+10 | 0.242324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.605144E+09 | 0.281852E+10 | 0.164537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.572028E+09 | 0.533930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.607467E+09 | 0.120466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.611063E+09 | 0.130087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.648830E+09 | 0.143930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.660265E+09 | 0.146192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.608402E+09 | 0.125616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.618692E+09 | 0.108220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.572334E+09 | 0.421435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.590404E+09 | 0.271483E+10 | 0.205356E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.722657E+10 | 0.957846E+11 | 0.802042E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.538862E+09 | 0.130748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.660265E+09 | 0.146192E+11 | 0.242324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.591238E+09 | 0.127564E+10 | 0.215819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.537041E+09 | 0.189405E+10 | 0.259666E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.602879E+09 | 0.276497E+10 | 0.175460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.569608E+09 | 0.527504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.604923E+09 | 0.119823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.608658E+09 | 0.129501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.646535E+09 | 0.143390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.657972E+09 | 0.145669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.606123E+09 | 0.125083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.616263E+09 | 0.107677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.569891E+09 | 0.416649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.588336E+09 | 0.267922E+10 | 0.222238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.719947E+10 | 0.951696E+11 | 0.873182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.537041E+09 | 0.127564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.657972E+09 | 0.145669E+11 | 0.259666E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.595270E+09 | 0.121114E+10 | 0.296190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.540215E+09 | 0.179465E+10 | 0.313021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.606071E+09 | 0.265151E+10 | 0.219974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.571430E+09 | 0.512516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.605954E+09 | 0.119106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.609872E+09 | 0.129185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.648375E+09 | 0.143461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.660071E+09 | 0.145976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.608050E+09 | 0.125128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.618025E+09 | 0.107435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.571664E+09 | 0.406199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.591579E+09 | 0.260697E+10 | 0.273384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.722658E+10 | 0.944806E+11 | 0.110257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.540215E+09 | 0.121114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.660071E+09 | 0.145976E+11 | 0.313021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.696176E+09 | 0.129307E+10 | 0.527964E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.630627E+09 | 0.189805E+10 | 0.483247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.707534E+09 | 0.286752E+10 | 0.394143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.662684E+09 | 0.547974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.695299E+09 | 0.131204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.694921E+09 | 0.143699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.737789E+09 | 0.160654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.751334E+09 | 0.164930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.697014E+09 | 0.140418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.708038E+09 | 0.120243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.663081E+09 | 0.439121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.690065E+09 | 0.274906E+10 | 0.431404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.833456E+10 | 0.104793E+12 | 0.183676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.630627E+09 | 0.129307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.751334E+09 | 0.164930E+11 | 0.527964E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.156823E+10 | 0.00 | 0.00 | 0.00 | 0.911113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142501E+10 | 0.00 | 0.00 | 0.00 | 0.118420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157667E+10 | 0.00 | 0.00 | 0.00 | 0.179057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151436E+10 | 0.00 | 0.00 | 0.00 | 0.335135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157395E+10 | 0.00 | 0.00 | 0.00 | 0.736746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155090E+10 | 0.00 | 0.00 | 0.00 | 0.781490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.164485E+10 | 0.00 | 0.00 | 0.00 | 0.870856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164412E+10 | 0.00 | 0.00 | 0.00 | 0.866713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157209E+10 | 0.00 | 0.00 | 0.00 | 0.763454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160340E+10 | 0.00 | 0.00 | 0.00 | 0.655581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151193E+10 | 0.00 | 0.00 | 0.00 | 0.255266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157681E+10 | 0.00 | 0.00 | 0.00 | 0.167770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187623E+11 | 0.00 | 0.00 | 0.00 | 0.582160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142501E+10 | 0.00 | 0.00 | 0.00 | 0.911113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164485E+10 | 0.00 | 0.00 | 0.00 | 0.870856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.709219E+09 | 0.00 | 0.00 | 0.00 | 0.535129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.678972E+09 | 0.00 | 0.00 | 0.00 | 0.689364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.753213E+09 | 0.00 | 0.00 | 0.00 | 0.101091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.731072E+09 | 0.00 | 0.00 | 0.00 | 0.181943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.733690E+09 | 0.00 | 0.00 | 0.00 | 0.370659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.730055E+09 | 0.00 | 0.00 | 0.00 | 0.389733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.784072E+09 | 0.00 | 0.00 | 0.00 | 0.432198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.781675E+09 | 0.00 | 0.00 | 0.00 | 0.426744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.739359E+09 | 0.00 | 0.00 | 0.00 | 0.377422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.758912E+09 | 0.00 | 0.00 | 0.00 | 0.328250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.757113E+09 | 0.00 | 0.00 | 0.00 | 0.136029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.751595E+09 | 0.00 | 0.00 | 0.00 | 0.889313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.890895E+10 | 0.00 | 0.00 | 0.00 | 0.295545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.678972E+09 | 0.00 | 0.00 | 0.00 | 0.535129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.784072E+09 | 0.00 | 0.00 | 0.00 | 0.432198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.682607E+09 | 0.00 | 0.00 | 0.00 | 0.408191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.620004E+09 | 0.00 | 0.00 | 0.00 | 0.557354E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.697370E+09 | 0.00 | 0.00 | 0.00 | 0.794682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.661551E+09 | 0.00 | 0.00 | 0.00 | 0.142055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.692484E+09 | 0.00 | 0.00 | 0.00 | 0.300104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.684654E+09 | 0.00 | 0.00 | 0.00 | 0.318670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.714536E+09 | 0.00 | 0.00 | 0.00 | 0.345981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.725372E+09 | 0.00 | 0.00 | 0.00 | 0.350165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.682163E+09 | 0.00 | 0.00 | 0.00 | 0.301469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.697916E+09 | 0.00 | 0.00 | 0.00 | 0.260743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.661871E+09 | 0.00 | 0.00 | 0.00 | 0.109826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.680563E+09 | 0.00 | 0.00 | 0.00 | 0.717788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.820109E+10 | 0.00 | 0.00 | 0.00 | 0.237681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.620004E+09 | 0.00 | 0.00 | 0.00 | 0.408191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.725372E+09 | 0.00 | 0.00 | 0.00 | 0.350165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.685753E+09 | 0.00 | 0.00 | 0.00 | 0.396626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.622936E+09 | 0.00 | 0.00 | 0.00 | 0.545704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.700462E+09 | 0.00 | 0.00 | 0.00 | 0.785211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.664233E+09 | 0.00 | 0.00 | 0.00 | 0.141657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.695231E+09 | 0.00 | 0.00 | 0.00 | 0.301230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.687188E+09 | 0.00 | 0.00 | 0.00 | 0.320023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.717362E+09 | 0.00 | 0.00 | 0.00 | 0.347770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.727991E+09 | 0.00 | 0.00 | 0.00 | 0.351738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.684842E+09 | 0.00 | 0.00 | 0.00 | 0.302919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.700601E+09 | 0.00 | 0.00 | 0.00 | 0.261756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.664540E+09 | 0.00 | 0.00 | 0.00 | 0.109380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.683550E+09 | 0.00 | 0.00 | 0.00 | 0.712069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.823469E+10 | 0.00 | 0.00 | 0.00 | 0.238043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.622936E+09 | 0.00 | 0.00 | 0.00 | 0.396626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.727991E+09 | 0.00 | 0.00 | 0.00 | 0.351738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.681846E+09 | 0.00 | 0.00 | 0.00 | 0.367590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.619449E+09 | 0.00 | 0.00 | 0.00 | 0.514913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.696150E+09 | 0.00 | 0.00 | 0.00 | 0.750549E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.659557E+09 | 0.00 | 0.00 | 0.00 | 0.136797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.690197E+09 | 0.00 | 0.00 | 0.00 | 0.296532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.681785E+09 | 0.00 | 0.00 | 0.00 | 0.315608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.711398E+09 | 0.00 | 0.00 | 0.00 | 0.343342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.721866E+09 | 0.00 | 0.00 | 0.00 | 0.347251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.679607E+09 | 0.00 | 0.00 | 0.00 | 0.298763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.695242E+09 | 0.00 | 0.00 | 0.00 | 0.257868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.659846E+09 | 0.00 | 0.00 | 0.00 | 0.105821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.679389E+09 | 0.00 | 0.00 | 0.00 | 0.687622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.817633E+10 | 0.00 | 0.00 | 0.00 | 0.233405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.619449E+09 | 0.00 | 0.00 | 0.00 | 0.367590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.721866E+09 | 0.00 | 0.00 | 0.00 | 0.347251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.109033E+10 | 0.00 | 0.00 | 0.00 | 0.637035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.990662E+09 | 0.00 | 0.00 | 0.00 | 0.931794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111324E+10 | 0.00 | 0.00 | 0.00 | 0.135891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105305E+10 | 0.00 | 0.00 | 0.00 | 0.254565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111794E+10 | 0.00 | 0.00 | 0.00 | 0.553849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112444E+10 | 0.00 | 0.00 | 0.00 | 0.594740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119347E+10 | 0.00 | 0.00 | 0.00 | 0.646031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.121513E+10 | 0.00 | 0.00 | 0.00 | 0.658180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112029E+10 | 0.00 | 0.00 | 0.00 | 0.557505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113966E+10 | 0.00 | 0.00 | 0.00 | 0.486983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105381E+10 | 0.00 | 0.00 | 0.00 | 0.195726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108574E+10 | 0.00 | 0.00 | 0.00 | 0.126208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132978E+11 | 0.00 | 0.00 | 0.00 | 0.436656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.990662E+09 | 0.00 | 0.00 | 0.00 | 0.637035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.121513E+10 | 0.00 | 0.00 | 0.00 | 0.658180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.593079E+09 | 0.00 | 0.00 | 0.00 | 0.317055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.538862E+09 | 0.00 | 0.00 | 0.00 | 0.466553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.605144E+09 | 0.00 | 0.00 | 0.00 | 0.682841E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.572028E+09 | 0.00 | 0.00 | 0.00 | 0.129211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.607467E+09 | 0.00 | 0.00 | 0.00 | 0.284006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.611063E+09 | 0.00 | 0.00 | 0.00 | 0.305181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.648830E+09 | 0.00 | 0.00 | 0.00 | 0.331765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.660265E+09 | 0.00 | 0.00 | 0.00 | 0.337679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.608402E+09 | 0.00 | 0.00 | 0.00 | 0.285652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.618692E+09 | 0.00 | 0.00 | 0.00 | 0.249193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.572334E+09 | 0.00 | 0.00 | 0.00 | 0.990611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.590404E+09 | 0.00 | 0.00 | 0.00 | 0.638708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.722657E+10 | 0.00 | 0.00 | 0.00 | 0.223226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.538862E+09 | 0.00 | 0.00 | 0.00 | 0.317055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.660265E+09 | 0.00 | 0.00 | 0.00 | 0.337679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.591238E+09 | 0.00 | 0.00 | 0.00 | 0.309588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.537041E+09 | 0.00 | 0.00 | 0.00 | 0.456133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.602879E+09 | 0.00 | 0.00 | 0.00 | 0.670296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.569608E+09 | 0.00 | 0.00 | 0.00 | 0.127695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.604923E+09 | 0.00 | 0.00 | 0.00 | 0.282462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.608658E+09 | 0.00 | 0.00 | 0.00 | 0.303748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.646535E+09 | 0.00 | 0.00 | 0.00 | 0.330447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.657972E+09 | 0.00 | 0.00 | 0.00 | 0.336395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.606123E+09 | 0.00 | 0.00 | 0.00 | 0.284385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.616263E+09 | 0.00 | 0.00 | 0.00 | 0.247904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.569891E+09 | 0.00 | 0.00 | 0.00 | 0.979320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.588336E+09 | 0.00 | 0.00 | 0.00 | 0.630462E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.719947E+10 | 0.00 | 0.00 | 0.00 | 0.221762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.537041E+09 | 0.00 | 0.00 | 0.00 | 0.309588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.657972E+09 | 0.00 | 0.00 | 0.00 | 0.336395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.595270E+09 | 0.00 | 0.00 | 0.00 | 0.294652E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.540215E+09 | 0.00 | 0.00 | 0.00 | 0.433506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.606071E+09 | 0.00 | 0.00 | 0.00 | 0.644460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.571430E+09 | 0.00 | 0.00 | 0.00 | 0.124327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.605954E+09 | 0.00 | 0.00 | 0.00 | 0.281037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.609872E+09 | 0.00 | 0.00 | 0.00 | 0.303168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.648375E+09 | 0.00 | 0.00 | 0.00 | 0.330742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.660071E+09 | 0.00 | 0.00 | 0.00 | 0.337187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.608050E+09 | 0.00 | 0.00 | 0.00 | 0.284599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.618025E+09 | 0.00 | 0.00 | 0.00 | 0.247465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.571664E+09 | 0.00 | 0.00 | 0.00 | 0.955397E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.591579E+09 | 0.00 | 0.00 | 0.00 | 0.614615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.722658E+10 | 0.00 | 0.00 | 0.00 | 0.220279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.540215E+09 | 0.00 | 0.00 | 0.00 | 0.294652E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.660071E+09 | 0.00 | 0.00 | 0.00 | 0.337187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.696176E+09 | 0.00 | 0.00 | 0.00 | 0.317389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.630627E+09 | 0.00 | 0.00 | 0.00 | 0.463822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.707534E+09 | 0.00 | 0.00 | 0.00 | 0.703508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.662684E+09 | 0.00 | 0.00 | 0.00 | 0.134406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.695299E+09 | 0.00 | 0.00 | 0.00 | 0.313283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.694921E+09 | 0.00 | 0.00 | 0.00 | 0.340546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.737789E+09 | 0.00 | 0.00 | 0.00 | 0.373844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.751334E+09 | 0.00 | 0.00 | 0.00 | 0.383791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.697014E+09 | 0.00 | 0.00 | 0.00 | 0.322196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.708038E+09 | 0.00 | 0.00 | 0.00 | 0.279094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.663081E+09 | 0.00 | 0.00 | 0.00 | 0.104394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.690065E+09 | 0.00 | 0.00 | 0.00 | 0.657666E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.833456E+10 | 0.00 | 0.00 | 0.00 | 0.246579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.630627E+09 | 0.00 | 0.00 | 0.00 | 0.317389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.751334E+09 | 0.00 | 0.00 | 0.00 | 0.383791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.392681E+10 | 0.437635E+09 | 0.00 | 2459652.21 | 2666648.77 | 44579298.80 | 0.135834E+10 | 0.00 | 0.46 |
February | 0.227613E+10 | 0.570570E+09 | 0.00 | 3081794.58 | 0.00 | 0.192815E+09 | 0.192120E+10 | 0.00 | 0.52 |
March | 0.168637E+10 | 0.110282E+10 | 0.00 | 3339833.30 | 399662.31 | 0.173643E+09 | 0.196965E+10 | 0.00 | 0.50 |
April | 0.120725E+09 | 0.268052E+10 | 0.00 | 4328205.09 | 2096988.37 | 0.00 | 0.238511E+10 | 0.00 | 0.57 |
May | 0.00 | 0.878388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.983034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.117667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.109761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.924772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
October | 37778799.78 | 0.707624E+10 | 0.00 | 3064278.84 | 0.00 | 0.00 | 0.110774E+10 | 0.00 | 0.46 |
November | 0.447733E+09 | 0.206719E+10 | 0.00 | 6728090.61 | 1268295.52 | 0.00 | 0.407419E+10 | 0.00 | 0.65 |
December | 0.208073E+10 | 0.124332E+10 | 0.00 | 3561447.18 | 5511046.94 | 0.137710E+09 | 0.280961E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.105763E+11 | 0.657830E+11 | 0.00 | 26563301.82 | 11942641.91 | 0.548747E+09 | 0.156258E+11 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.437635E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.392681E+10 | 0.117667E+11 | 0.00 | 6728090.61 | 5511046.94 | 0.192815E+09 | 0.407419E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131603E+10 | 0.232498E+09 | 0.00 | 1507830.93 | 112418.77 | 0.00 | 0.945920E+09 | 0.00 | 0.41 |
February | 0.700576E+09 | 0.318511E+09 | 0.00 | 1866548.44 | 0.00 | 48092369.40 | 0.123635E+10 | 0.00 | 0.49 |
March | 0.538860E+09 | 0.581936E+09 | 0.00 | 2055739.65 | 12451.14 | 47066847.15 | 0.126314E+10 | 0.00 | 0.49 |
April | 30905177.72 | 0.130095E+10 | 0.00 | 2164584.30 | 184129.60 | 0.00 | 0.121671E+10 | 0.00 | 0.53 |
May | 0.00 | 0.397958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
June | 0.00 | 0.444224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.530386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.495924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.417436E+10 | 0.00 | 100404.85 | 0.00 | 0.00 | 15073746.74 | 0.00 | 0.31 |
October | 11054445.34 | 0.320834E+10 | 0.00 | 1363893.85 | 0.00 | 0.00 | 0.525333E+09 | 0.00 | 0.41 |
November | 0.106153E+09 | 0.975534E+09 | 0.00 | 3729875.11 | 0.00 | 0.00 | 0.225858E+10 | 0.00 | 0.66 |
December | 0.712681E+09 | 0.601615E+09 | 0.00 | 2407198.84 | 68180.29 | 34558612.20 | 0.175627E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.341626E+10 | 0.300787E+11 | 0.00 | 15196075.98 | 377179.80 | 0.129718E+09 | 0.921738E+10 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.232498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.131603E+10 | 0.530386E+10 | 0.00 | 3729875.11 | 184129.60 | 48092369.40 | 0.225858E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135754E+10 | 0.185886E+09 | 0.00 | 641817.09 | 7175702.80 | 16890514.59 | 0.378703E+09 | 0.00 | 0.35 |
February | 0.759362E+09 | 0.254631E+09 | 0.00 | 924936.27 | 4395515.22 | 67153582.25 | 0.563112E+09 | 0.00 | 0.40 |
March | 0.635661E+09 | 0.479027E+09 | 0.00 | 1064382.32 | 9829267.45 | 63984773.53 | 0.630255E+09 | 0.00 | 0.41 |
April | 83928911.22 | 0.999323E+09 | 0.00 | 1326958.81 | 48277378.95 | 0.00 | 0.693457E+09 | 0.00 | 0.45 |
May | 0.00 | 0.315581E+10 | 0.00 | 0.00 | 0.185914E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.355002E+10 | 0.00 | 33251.28 | 0.214967E+09 | 0.00 | 293968.62 | 0.00 | 0.27 |
July | 0.00 | 0.406921E+10 | 0.00 | 0.00 | 0.243572E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.396309E+10 | 0.00 | 0.00 | 0.213973E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 2152868.57 | 0.323431E+10 | 0.00 | 59981.89 | 0.172168E+09 | 0.00 | 8636482.78 | 0.00 | 0.27 |
October | 30351818.75 | 0.253066E+10 | 0.00 | 1193328.85 | 0.137962E+09 | 0.00 | 0.438453E+09 | 0.00 | 0.36 |
November | 0.227216E+09 | 0.783090E+09 | 0.00 | 2282056.94 | 39885988.57 | 0.00 | 0.131777E+10 | 0.00 | 0.53 |
December | 0.834835E+09 | 0.498288E+09 | 0.00 | 1226319.91 | 19319504.41 | 43774928.40 | 0.840517E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.393105E+10 | 0.237033E+11 | 0.00 | 8753033.36 | 0.129744E+10 | 0.191804E+09 | 0.487120E+10 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.185886E+09 | 0.00 | 0.00 | 4395515.22 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.135754E+10 | 0.406921E+10 | 0.00 | 2282056.94 | 0.243572E+09 | 67153582.25 | 0.131777E+10 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135006E+10 | 0.181021E+09 | 0.00 | 590810.36 | 7402353.42 | 29204843.14 | 0.348811E+09 | 0.00 | 0.34 |
February | 0.768790E+09 | 0.250807E+09 | 0.00 | 870348.72 | 4385880.07 | 74345129.36 | 0.527841E+09 | 0.00 | 0.39 |
March | 0.638496E+09 | 0.477018E+09 | 0.00 | 1005019.08 | 9723445.78 | 66648486.23 | 0.607004E+09 | 0.00 | 0.40 |
April | 86495669.60 | 0.998418E+09 | 0.00 | 1306662.17 | 48314776.88 | 0.00 | 0.686807E+09 | 0.00 | 0.45 |
May | 0.00 | 0.316180E+10 | 0.00 | 0.00 | 0.186000E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.355740E+10 | 0.00 | 33774.53 | 0.215094E+09 | 0.00 | 301541.48 | 0.00 | 0.27 |
July | 0.00 | 0.407979E+10 | 0.00 | 0.00 | 0.243792E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.397205E+10 | 0.00 | 0.00 | 0.214130E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 2160050.88 | 0.324319E+10 | 0.00 | 64008.46 | 0.172329E+09 | 0.00 | 8681206.76 | 0.00 | 0.27 |
October | 30665219.42 | 0.253614E+10 | 0.00 | 1214670.39 | 0.138037E+09 | 0.00 | 0.440642E+09 | 0.00 | 0.36 |
November | 0.234363E+09 | 0.784944E+09 | 0.00 | 2224948.98 | 39881312.24 | 0.00 | 0.130099E+10 | 0.00 | 0.52 |
December | 0.838149E+09 | 0.497558E+09 | 0.00 | 1151245.15 | 19697190.92 | 46650507.40 | 0.806540E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.394917E+10 | 0.237401E+11 | 0.00 | 8461487.83 | 0.129879E+10 | 0.216849E+09 | 0.472761E+10 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.181021E+09 | 0.00 | 0.00 | 4385880.07 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.135006E+10 | 0.407979E+10 | 0.00 | 2224948.98 | 0.243792E+09 | 74345129.36 | 0.130099E+10 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133194E+10 | 0.169646E+09 | 0.00 | 541985.49 | 7216454.55 | 52973844.92 | 0.307714E+09 | 0.00 | 0.34 |
February | 0.773052E+09 | 0.240742E+09 | 0.00 | 755740.70 | 4419962.83 | 99071232.35 | 0.459360E+09 | 0.00 | 0.39 |
March | 0.677410E+09 | 0.464511E+09 | 0.00 | 807614.58 | 9337591.29 | 69760734.15 | 0.510992E+09 | 0.00 | 0.39 |
April | 97894823.40 | 0.973875E+09 | 0.00 | 1212699.14 | 47746400.38 | 0.00 | 0.649202E+09 | 0.00 | 0.45 |
May | 0.00 | 0.313347E+10 | 0.00 | 0.00 | 0.184887E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.353199E+10 | 0.00 | 30779.01 | 0.214085E+09 | 0.00 | 273869.61 | 0.00 | 0.27 |
July | 0.00 | 0.405343E+10 | 0.00 | 0.00 | 0.242669E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.394620E+10 | 0.00 | 0.00 | 0.213079E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 2205364.87 | 0.321691E+10 | 0.00 | 57697.62 | 0.171216E+09 | 0.00 | 9283439.04 | 0.00 | 0.27 |
October | 32418046.53 | 0.251674E+10 | 0.00 | 1147577.25 | 0.137200E+09 | 0.00 | 0.424408E+09 | 0.00 | 0.35 |
November | 0.260786E+09 | 0.772468E+09 | 0.00 | 2044375.49 | 39745303.79 | 0.00 | 0.122172E+10 | 0.00 | 0.51 |
December | 0.858086E+09 | 0.487808E+09 | 0.00 | 975234.43 | 19936166.76 | 61330400.78 | 0.707708E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.403379E+10 | 0.235078E+11 | 0.00 | 7573703.71 | 0.129154E+10 | 0.283136E+09 | 0.429066E+10 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.169646E+09 | 0.00 | 0.00 | 4419962.83 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.133194E+10 | 0.405343E+10 | 0.00 | 2044375.49 | 0.242669E+09 | 99071232.35 | 0.122172E+10 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.277968E+10 | 0.321632E+09 | 0.00 | 916046.79 | 14139918.55 | 85274787.41 | 0.600910E+09 | 0.00 | 0.34 |
February | 0.170626E+10 | 0.481546E+09 | 0.00 | 1215528.94 | 7846056.57 | 0.181313E+09 | 0.726820E+09 | 0.00 | 0.37 |
March | 0.143282E+10 | 0.926738E+09 | 0.00 | 1234364.42 | 9638359.51 | 0.184646E+09 | 0.826647E+09 | 0.00 | 0.37 |
April | 0.147289E+09 | 0.205185E+10 | 0.00 | 2002070.32 | 38252456.54 | 0.00 | 0.112711E+10 | 0.00 | 0.41 |
May | 0.00 | 0.663861E+10 | 0.00 | 0.00 | 98758145.77 | 0.00 | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.756692E+10 | 0.00 | 0.00 | 0.102695E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
July | 0.00 | 0.858820E+10 | 0.00 | 0.00 | 0.170671E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.844616E+10 | 0.00 | 0.00 | 96897997.98 | 0.00 | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.678389E+10 | 0.00 | 118857.44 | 0.134771E+09 | 0.00 | 45697348.67 | 0.00 | 0.29 |
October | 33634078.60 | 0.540982E+10 | 0.00 | 1999990.98 | 80680301.67 | 0.00 | 0.707654E+09 | 0.00 | 0.35 |
November | 0.393539E+09 | 0.163536E+10 | 0.00 | 3701748.69 | 19379588.49 | 0.00 | 0.224885E+10 | 0.00 | 0.47 |
December | 0.188751E+10 | 0.100471E+10 | 0.00 | 1524758.63 | 21943376.66 | 0.124384E+09 | 0.113353E+10 | 0.00 | 0.35 |
Annual Sum or Average | 0.838073E+10 | 0.498554E+11 | 0.00 | 12713366.21 | 0.795673E+09 | 0.575617E+09 | 0.741721E+10 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.321632E+09 | 0.00 | 0.00 | 7846056.57 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.277968E+10 | 0.858820E+10 | 0.00 | 3701748.69 | 0.170671E+09 | 0.184646E+09 | 0.224885E+10 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135843E+10 | 0.156356E+09 | 0.00 | 421715.73 | 7925566.20 | 69582232.73 | 0.279383E+09 | 0.00 | 0.34 |
February | 0.802189E+09 | 0.235384E+09 | 0.00 | 578751.25 | 4296726.05 | 0.131453E+09 | 0.358710E+09 | 0.00 | 0.37 |
March | 0.734012E+09 | 0.456072E+09 | 0.00 | 559905.46 | 4745657.31 | 95677868.94 | 0.375052E+09 | 0.00 | 0.37 |
April | 77140746.36 | 0.102057E+10 | 0.00 | 979813.61 | 18829361.19 | 0.00 | 0.563387E+09 | 0.00 | 0.42 |
May | 0.00 | 0.330858E+10 | 0.00 | 0.00 | 48556386.79 | 0.00 | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.377045E+10 | 0.00 | 0.00 | 50616170.83 | 0.00 | 0.00 | 0.00 | 0.28 |
July | 0.00 | 0.427356E+10 | 0.00 | 0.00 | 83668886.46 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.420351E+10 | 0.00 | 0.00 | 47479463.59 | 0.00 | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.337039E+10 | 0.00 | 60526.68 | 65957653.60 | 0.00 | 25148147.59 | 0.00 | 0.29 |
October | 16879240.65 | 0.269056E+10 | 0.00 | 994652.09 | 39355444.60 | 0.00 | 0.356920E+09 | 0.00 | 0.35 |
November | 0.206308E+09 | 0.810674E+09 | 0.00 | 1806472.34 | 9712357.97 | 0.00 | 0.112144E+10 | 0.00 | 0.48 |
December | 0.933776E+09 | 0.497495E+09 | 0.00 | 698194.48 | 11437923.14 | 88799755.95 | 0.528774E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.412873E+10 | 0.247936E+11 | 0.00 | 6100031.64 | 0.392582E+09 | 0.385513E+09 | 0.360881E+10 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.156356E+09 | 0.00 | 0.00 | 4296726.05 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.135843E+10 | 0.427356E+10 | 0.00 | 1806472.34 | 83668886.46 | 0.131453E+09 | 0.112144E+10 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134497E+10 | 0.153125E+09 | 0.00 | 393498.17 | 8195416.48 | 82876983.58 | 0.266350E+09 | 0.00 | 0.34 |
February | 0.788045E+09 | 0.230876E+09 | 0.00 | 558362.58 | 4809784.53 | 0.143372E+09 | 0.350768E+09 | 0.00 | 0.37 |
March | 0.749491E+09 | 0.449946E+09 | 0.00 | 523965.28 | 5112293.79 | 97030452.28 | 0.345609E+09 | 0.00 | 0.37 |
April | 80267001.86 | 0.101316E+10 | 0.00 | 941915.67 | 19037118.95 | 0.00 | 0.551012E+09 | 0.00 | 0.41 |
May | 0.00 | 0.329878E+10 | 0.00 | 0.00 | 48479951.41 | 0.00 | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.376180E+10 | 0.00 | 0.00 | 50551500.32 | 0.00 | 0.00 | 0.00 | 0.28 |
July | 0.00 | 0.426511E+10 | 0.00 | 0.00 | 83567620.59 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.419570E+10 | 0.00 | 0.00 | 47418839.66 | 0.00 | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.336222E+10 | 0.00 | 62276.54 | 65868974.57 | 0.00 | 26280391.75 | 0.00 | 0.29 |
October | 17655450.35 | 0.268376E+10 | 0.00 | 978691.87 | 39276797.40 | 0.00 | 0.352515E+09 | 0.00 | 0.35 |
November | 0.213117E+09 | 0.806179E+09 | 0.00 | 1759666.50 | 9712770.35 | 0.00 | 0.109681E+10 | 0.00 | 0.47 |
December | 0.922978E+09 | 0.493270E+09 | 0.00 | 654279.50 | 11879350.14 | 0.110179E+09 | 0.500032E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.411652E+10 | 0.247139E+11 | 0.00 | 5872656.10 | 0.393910E+09 | 0.433458E+09 | 0.348937E+10 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.153125E+09 | 0.00 | 0.00 | 4809784.53 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.134497E+10 | 0.426511E+10 | 0.00 | 1759666.50 | 83567620.59 | 0.143372E+09 | 0.109681E+10 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130901E+10 | 0.145530E+09 | 0.00 | 346247.51 | 10116043.52 | 0.125438E+09 | 0.236398E+09 | 0.00 | 0.34 |
February | 0.751945E+09 | 0.222027E+09 | 0.00 | 498669.12 | 5539990.75 | 0.184147E+09 | 0.327615E+09 | 0.00 | 0.36 |
March | 0.755864E+09 | 0.436868E+09 | 0.00 | 455745.25 | 6259901.53 | 0.110754E+09 | 0.297490E+09 | 0.00 | 0.36 |
April | 91553083.92 | 0.995096E+09 | 0.00 | 840455.88 | 20576891.83 | 0.00 | 0.517475E+09 | 0.00 | 0.41 |
May | 0.00 | 0.328562E+10 | 0.00 | 0.00 | 48422947.28 | 0.00 | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.375546E+10 | 0.00 | 0.00 | 50556029.16 | 0.00 | 0.00 | 0.00 | 0.28 |
July | 0.00 | 0.426458E+10 | 0.00 | 0.00 | 83636134.75 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.419908E+10 | 0.00 | 0.00 | 47481920.60 | 0.00 | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.336078E+10 | 0.00 | 59892.56 | 65959272.20 | 0.00 | 25314673.63 | 0.00 | 0.29 |
October | 23835442.36 | 0.268072E+10 | 0.00 | 934106.43 | 39310450.28 | 0.00 | 0.337801E+09 | 0.00 | 0.35 |
November | 0.236232E+09 | 0.793986E+09 | 0.00 | 1650658.66 | 10122553.09 | 0.00 | 0.104003E+10 | 0.00 | 0.47 |
December | 0.919549E+09 | 0.484290E+09 | 0.00 | 560211.44 | 12968245.15 | 0.142979E+09 | 0.432899E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.408799E+10 | 0.246240E+11 | 0.00 | 5345986.86 | 0.400950E+09 | 0.563318E+09 | 0.321502E+10 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.145530E+09 | 0.00 | 0.00 | 5539990.75 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.130901E+10 | 0.426458E+10 | 0.00 | 1650658.66 | 83636134.75 | 0.184147E+09 | 0.104003E+10 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119404E+10 | 0.152415E+09 | 0.00 | 335798.25 | 9567211.85 | 0.221032E+09 | 0.233023E+09 | 0.00 | 0.35 |
February | 0.650756E+09 | 0.229598E+09 | 0.00 | 467100.70 | 6787750.23 | 0.270365E+09 | 0.312392E+09 | 0.00 | 0.37 |
March | 0.642871E+09 | 0.449185E+09 | 132040.87 | 457376.43 | 8076340.32 | 0.188934E+09 | 0.306933E+09 | 213.23 | 0.37 |
April | 98844144.10 | 0.101283E+10 | 0.00 | 812522.00 | 22406685.42 | 0.00 | 0.529900E+09 | 0.00 | 0.42 |
May | 0.00 | 0.337165E+10 | 0.00 | 0.00 | 48952829.42 | 0.00 | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.388511E+10 | 0.00 | 8146.12 | 51552671.11 | 0.00 | 26919.11 | 0.00 | 0.28 |
July | 0.00 | 0.442964E+10 | 0.00 | 0.00 | 85826190.36 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.436789E+10 | 0.00 | 0.00 | 48995881.89 | 0.00 | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.349725E+10 | 0.00 | 64368.52 | 68247199.86 | 0.00 | 26263806.67 | 0.00 | 0.29 |
October | 27760973.96 | 0.278010E+10 | 0.00 | 912569.80 | 40618747.53 | 0.00 | 0.336990E+09 | 0.00 | 0.36 |
November | 0.238099E+09 | 0.820884E+09 | 0.00 | 1605436.38 | 10293446.39 | 0.00 | 0.105527E+10 | 0.00 | 0.49 |
December | 0.755450E+09 | 0.484553E+09 | 0.00 | 535226.26 | 11104312.03 | 0.308684E+09 | 0.407969E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.360782E+10 | 0.254811E+11 | 132040.87 | 5198544.45 | 0.412429E+09 | 0.989015E+09 | 0.320876E+10 | 213.23 | 0.34 |
Minimum of Months | 0.00 | 0.152415E+09 | 0.00 | 0.00 | 6787750.23 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.119404E+10 | 0.442964E+10 | 132040.87 | 1605436.38 | 85826190.36 | 0.308684E+09 | 0.105527E+10 | 213.23 | 0.49 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:39:24
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.203490E+12 | 0.154547E+11 | 0.00 | 0.209894E+11 | 0.234234E+11 |
February | 0.227702E+12 | 0.912995E+10 | 0.00 | 0.153305E+11 | 0.326656E+11 |
March | 0.260900E+12 | 0.554459E+10 | 0.00 | 0.110004E+11 | 0.472854E+11 |
April | 0.307220E+12 | -0.875814E+10 | 0.00 | -0.345853E+10 | 0.869280E+11 |
May | 0.314159E+12 | -0.369772E+11 | 0.00 | -0.429677E+11 | 0.192695E+12 |
June | 0.316615E+12 | -0.402093E+11 | 0.00 | -0.486008E+11 | 0.206750E+12 |
July | 0.325538E+12 | -0.470682E+11 | 0.00 | -0.563314E+11 | 0.229842E+12 |
August | 0.301336E+12 | -0.461410E+11 | 0.00 | -0.541587E+11 | 0.231944E+12 |
September | 0.252895E+12 | -0.391929E+11 | 0.00 | -0.442096E+11 | 0.201419E+12 |
October | 0.254596E+12 | -0.291699E+11 | 0.00 | -0.294554E+11 | 0.173129E+12 |
November | 0.186134E+12 | -0.142149E+10 | 0.00 | 0.890010E+10 | 0.681377E+11 |
December | 0.184193E+12 | 0.909837E+10 | 0.00 | 0.155238E+11 | 0.446344E+11 |
Annual Sum or Average | 0.313478E+13 | -0.209710E+12 | 0.00 | -0.207438E+12 | 0.153886E+13 |
Minimum of Months | 0.184193E+12 | -0.470682E+11 | 0.00 | -0.563314E+11 | 0.234234E+11 |
Maximum of Months | 0.325538E+12 | 0.154547E+11 | 0.00 | 0.209894E+11 | 0.231944E+12 |