Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:39
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:39:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1178.66 | 563.87 | 563.87 |
Net Site Energy | 1123.71 | 537.58 | 537.58 |
Total Source Energy | 2678.58 | 1281.42 | 1281.42 |
Net Source Energy | 2504.55 | 1198.17 | 1198.17 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 506.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 48.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 112.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 65.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 672.55 | 506.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 506.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 48.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 41.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 112.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 65.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 506.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 48.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 41.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 112.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 65.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 152.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 107.91 | 242.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 321.74 | 242.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 152.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 107.91 | 242.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 321.74 | 242.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 57.540 | 8.56 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -2.59 | -0.4 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 54.952 | 8.17 |
Electricity Coming From Utility | 617.601 | 91.83 |
Surplus Electricity Going To Utility | 0.007 | 0.00 |
Net Electricity From Utility | 617.594 | 91.83 |
Total On-Site and Utility Electric Sources | 672.545 | 100.00 |
Total Electricity End Uses | 672.545 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 6.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2779.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:39 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 11.5884 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 13.7658 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 7.5320 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 10.0873 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 10.0873 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 11.5884 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 13.7658 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 12.9393 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 12.9393 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 12.9393 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 7.5320 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 7.5557 | 6.19 | 4.3000 | |
Total | 2090.32 | 10.0873 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 10.0873 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 10.0873 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUL-14:39 | 07-FEB-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 201719.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28930.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6569.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7424.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 68681.65 | 201719.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 201719.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 28930.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6569.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7424.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 548.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 152.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 879.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 129.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 355.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 206.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2129.95 | 548.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 262.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 72.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 420.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 170.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1018.96 | 262.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 262.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 72.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 420.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 170.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1018.96 | 262.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.63 |
SMSTORE1 DIRECT AIR | 0.878811 |
SMSTORE2 DIRECT AIR | 1.00 |
SMSTORE3 DIRECT AIR | 1.00 |
SMSTORE4 DIRECT AIR | 1.00 |
LGSTORE2 DIRECT AIR | 1.55 |
SMSTORE5 DIRECT AIR | 0.834219 |
SMSTORE6 DIRECT AIR | 0.826266 |
SMSTORE7 DIRECT AIR | 0.812125 |
SMSTORE8 DIRECT AIR | 0.871905 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 1.00 | 1.00 | 1.63 |
PSZ-AC_2:2 | 0.878811 | 0.878811 | 0.878811 | 0.878811 | 0.889379 | 0.889379 | 1.00 | 0.988118 | 0.889379 |
PSZ-AC_3:3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.000000 | 1.00 |
PSZ-AC_4:4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PSZ-AC_5:5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.000000 | 1.00 |
PSZ-AC_6:6 | 1.55 | 1.55 | 1.55 | 1.55 | 1.60 | 1.60 | 1.00 | 0.968262 | 1.60 |
PSZ-AC_7:7 | 0.834219 | 0.834219 | 0.834219 | 0.834219 | 0.842752 | 0.842752 | 1.00 | 0.989875 | 0.842752 |
PSZ-AC_8:8 | 0.826266 | 0.826266 | 0.826266 | 0.826266 | 0.835623 | 0.835623 | 1.00 | 0.988802 | 0.835623 |
PSZ-AC_9:9 | 0.812125 | 0.812125 | 0.812125 | 0.812125 | 0.823546 | 0.823546 | 1.00 | 0.986132 | 0.823546 |
PSZ-AC_10:10 | 0.871905 | 0.871905 | 0.871905 | 0.871905 | 0.871905 | 0.871905 | 1.00 | 1.00 | 0.871905 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.63 |
PSZ-AC_2:2_OA_CONTROLLER | 0.889379 |
PSZ-AC_3:3_OA_CONTROLLER | 1.00 |
PSZ-AC_4:4_OA_CONTROLLER | 1.00 |
PSZ-AC_5:5_OA_CONTROLLER | 1.00 |
PSZ-AC_6:6_OA_CONTROLLER | 1.60 |
PSZ-AC_7:7_OA_CONTROLLER | 0.842752 |
PSZ-AC_8:8_OA_CONTROLLER | 0.835623 |
PSZ-AC_9:9_OA_CONTROLLER | 0.823546 |
PSZ-AC_10:10_OA_CONTROLLER | 0.871905 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.63 | 1747.18 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 0.889379 | 984.68 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.00 | 1112.23 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.00 | 1110.35 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.00 | 1108.78 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.60 | 1716.76 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.842752 | 933.06 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.835623 | 925.17 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.823546 | 911.80 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 0.871905 | 965.34 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.63 | 1.63 | 1.63 | 1.08 | 36387.11 | 54549.74 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 0.889379 | 0.889379 | 0.889379 | 0.586990 | 19416.12 | 28665.43 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.00 | 1.00 | 1.00 | 0.663021 | 20508.58 | 31468.55 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.00 | 1.00 | 1.00 | 0.661901 | 20337.28 | 31430.73 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.00 | 1.00 | 1.00 | 0.660964 | 20453.96 | 31399.06 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.60 | 1.60 | 1.60 | 1.06 | 35786.82 | 52780.30 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.842752 | 0.842752 | 0.842752 | 0.842752 | 18749.05 | 27671.50 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.835623 | 0.835623 | 0.835623 | 0.835623 | 18630.29 | 27494.23 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.823546 | 0.823546 | 0.823546 | 0.823546 | 18407.69 | 27179.05 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 0.871905 | 0.871905 | 0.871905 | 0.575457 | 19258.83 | 28512.44 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.63 | 0.816403 | 1.09 | 36387.11 | 18193.56 | 0.736100 | 0.736100 |
PSZ-AC_2:2 COOLING COIL | 0.889380 | 0.444689 | 0.592920 | 19416.12 | 9708.06 | 0.743780 | 0.743780 |
PSZ-AC_3:3 COOLING COIL | 1.00 | 0.502289 | 0.669720 | 20508.58 | 10254.29 | 0.768110 | 0.768110 |
PSZ-AC_4:4 COOLING COIL | 1.00 | 0.501440 | 0.668587 | 20337.28 | 10168.64 | 0.771120 | 0.771120 |
PSZ-AC_5:5 COOLING COIL | 1.00 | 0.500730 | 0.667640 | 20453.96 | 10226.98 | 0.767980 | 0.767980 |
PSZ-AC_6:6 COOLING COIL | 1.60 | 0.802191 | 1.07 | 35786.82 | 17893.41 | 0.735850 | 0.735850 |
PSZ-AC_7:7 COOLING COIL | 0.842750 | 0.421376 | 0.561833 | 18749.05 | 9374.52 | 0.736560 | 0.736560 |
PSZ-AC_8:8 COOLING COIL | 0.835620 | 0.417812 | 0.557080 | 18630.29 | 9315.15 | 0.735980 | 0.735980 |
PSZ-AC_9:9 COOLING COIL | 0.823550 | 0.411773 | 0.549033 | 18407.69 | 9203.84 | 0.735280 | 0.735280 |
PSZ-AC_10:10 COOLING COIL | 0.871900 | 0.435952 | 0.581267 | 19258.83 | 9629.42 | 0.739530 | 0.739530 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 54549.74 |
PSZ-AC_2:2 HEATING COIL | 28665.43 |
PSZ-AC_3:3 HEATING COIL | 31468.55 |
PSZ-AC_4:4 HEATING COIL | 31430.73 |
PSZ-AC_5:5 HEATING COIL | 31399.06 |
PSZ-AC_6:6 HEATING COIL | 52780.30 |
PSZ-AC_7:7 HEATING COIL | 27671.50 |
PSZ-AC_8:8 HEATING COIL | 27494.23 |
PSZ-AC_9:9 HEATING COIL | 27179.05 |
PSZ-AC_10:10 HEATING COIL | 28512.44 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 11.588 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.888 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 13.766 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 18.066 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 7.532 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.832 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 2630.745 | 7.551 | 46.768 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2630.745 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1406.513 | 4.037 | 25.004 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1406.513 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1319.493 | 7.575 | 46.916 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1319.493 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1078.411 | 6.191 | 38.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1078.411 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 2624.046 | 7.532 | 46.649 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2624.046 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.4286 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.099 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.37371027E-12 | 0.68594845E-15 | -0.12863262E-12 | 0.13303556E-15 |
23 | 6 | 0.32748130E-07 | 0.12499873E-09 | 0.74678710E-08 | -0.15730520E-12 |
24 | 5 | -0.21059623E-03 | 0.10441617E-05 | -0.10801544E-03 | 0.73682644E-08 |
25 | 4 | 0.31581162 | 0.49728803E-03 | 0.10820905 | -0.36942064E-04 |
26 | 3 | -7.7342764 | 0.15111690E-01 | -2.4778213 | 0.31304292E-01 |
27 | 2 | 42.413636 | 0.52806348E-01 | 15.833102 | -0.35052424 |
28 | 1 | -81.726940 | 0.23470004E-01 | -29.650437 | 1.1037915 |
29 | 0 | 46.824331 | 0.46514506E-03 | 16.279406 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 35 | 1 | VerySmooth | 1.408 | 1.408 | 1.000 | 0.210 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 4.57814E-002 | 0.12126 | 0.67915 | 0.67915 | 0.29000 | 0.15345 | 0.21878 | 0.00000 | 0.84000 | 0.84000 | 8.56546E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 18072.55162 | 21687.06194 | 1.36067 | 1.63281 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.30000 | 1.33670E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 26587.57738 | 31905.09286 | 1.17549 | 1.41058 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 10054.61122 | 12065.53347 | 0.73234 | 0.87881 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 12613.90259 | 15136.68311 | 0.55770 | 0.66924 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11434.68144 | 13721.61772 | 0.83715 | 1.00458 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 12775.69246 | 15330.83096 | 0.56485 | 0.67782 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11417.37367 | 13700.84840 | 0.83573 | 1.00288 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 12870.28928 | 15444.34713 | 0.56903 | 0.68284 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11399.97034 | 13679.96441 | 0.83455 | 1.00146 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 13023.03067 | 15627.63680 | 0.57579 | 0.69094 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 17837.44799 | 21404.93759 | 1.29455 | 1.55346 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 24926.89124 | 29912.26948 | 1.10211 | 1.32253 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 9560.35278 | 11472.42334 | 0.69518 | 0.83422 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 13351.39116 | 16021.66940 | 0.59030 | 0.70837 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 9471.36909 | 11365.64291 | 0.68855 | 0.82627 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 13339.69207 | 16007.63049 | 0.58979 | 0.70774 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 9313.21060 | 11175.85272 | 0.67677 | 0.81212 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 13544.49639 | 16253.39567 | 0.59884 | 0.71861 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 9501.13129 | 11401.35755 | 0.69095 | 0.82914 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 16434.90549 | 19721.88659 | 0.72659 | 0.87190 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 24465.30 | 1.63281 | 1.63281 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 49596.63 | 1.41058 | 1.41058 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 13164.15 | 0.88938 | 0.88938 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 23994.31 | 0.66924 | 0.66924 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 13475.69 | 1.00458 | 1.00458 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 24185.63 | 0.67782 | 0.67782 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 13454.68 | 1.00288 | 1.00288 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 24297.49 | 0.68284 | 0.68284 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 13434.68 | 1.00146 | 1.00146 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 24478.12 | 0.69094 | 0.69094 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 24048.34 | 1.60438 | 1.60438 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 47633.18 | 1.32253 | 1.32253 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 12322.27 | 0.84275 | 0.84275 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 24866.42 | 0.70837 | 0.70837 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 12231.97 | 0.83562 | 0.83562 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 24852.59 | 0.70774 | 0.70774 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 12126.09 | 0.82355 | 0.82355 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 25094.77 | 0.71861 | 0.71861 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 12573.68 | 0.85134 | 0.85134 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 28512.44 | 0.87190 | 0.87190 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.63281 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.87881 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00458 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00288 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00146 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.55346 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83422 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.82627 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.81212 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.87190 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.63281 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.63281 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.63281 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.63281 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.63281 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.63281 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.87881 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.87881 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.87881 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.87881 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.88938 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.88938 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.98812 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00458 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00458 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00458 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00458 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00458 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00458 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00288 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00288 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00288 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00288 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00288 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00288 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00146 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00146 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00146 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00146 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00146 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00146 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.55346 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.55346 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.55346 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.55346 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.60438 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.60438 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 0.96826 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.83422 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.83422 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.83422 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.83422 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.84275 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.84275 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.98988 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.82627 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.82627 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.82627 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.82627 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.83562 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.83562 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.98880 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.81212 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.81212 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.81212 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.81212 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.82355 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.82355 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.98613 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.87190 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.87190 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.87190 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.87190 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.87190 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 0.87190 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.63281 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 0.88938 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.00458 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.00288 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.00146 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.60438 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.84275 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.83562 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.82355 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 0.87190 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.63281 |
102 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.63281 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1747.17965 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.63281 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.63281 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.63281 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.07765 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.63281 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.81640 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.08854 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36387.11000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18193.55500 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73610 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73610 |
115 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36387.11000 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 54549.73613 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
119 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 54549.73613 |
120 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.88938 |
121 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.88938 |
122 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 984.68331 |
123 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.88938 |
124 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.88938 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.88938 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.58699 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.88938 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.44469 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.59292 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19416.12000 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9708.06000 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74378 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74378 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19416.12000 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28665.42953 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
138 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 28665.42953 |
139 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00458 |
140 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00458 |
141 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1112.22672 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00458 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00458 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00458 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66302 |
146 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00458 |
147 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50229 |
148 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66972 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20508.58000 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10254.29000 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76811 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76811 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20508.58000 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31468.55420 |
155 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
157 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 31468.55420 |
158 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00288 |
159 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00288 |
160 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1110.34797 |
161 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00288 |
162 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00288 |
163 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00288 |
164 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66190 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00288 |
166 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50144 |
167 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66859 |
168 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20337.28000 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10168.64000 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77112 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77112 |
172 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20337.28000 |
173 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31430.72876 |
174 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
176 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 31430.72876 |
177 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00146 |
178 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00146 |
179 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1108.77517 |
180 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00146 |
181 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00146 |
182 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00146 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66096 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00146 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50073 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66764 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20453.96000 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10226.98000 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76798 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76798 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20453.96000 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31399.05619 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
194 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
195 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 31399.05619 |
196 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.60438 |
197 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.60438 |
198 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1716.76487 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.60438 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.60438 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.60438 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05889 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.60438 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.80219 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.06959 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 35786.82000 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17893.41000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73585 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73585 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35786.82000 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 52780.29830 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
213 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
214 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 52780.29830 |
215 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.84275 |
216 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.84275 |
217 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 933.05993 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.84275 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.84275 |
220 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.84275 |
221 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.84275 |
222 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.84275 |
223 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.42138 |
224 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.56183 |
225 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18749.05000 |
226 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9374.52500 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73656 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73656 |
229 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18749.05000 |
230 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27671.50203 |
231 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
232 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
233 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 27671.50203 |
234 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.83562 |
235 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.83562 |
236 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 925.16779 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.83562 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.83562 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.83562 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83562 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.83562 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.41781 |
243 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.55708 |
244 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18630.29000 |
245 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9315.14500 |
246 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73598 |
247 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73598 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18630.29000 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27494.23430 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
251 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
252 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 27494.23430 |
253 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.82355 |
254 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.82355 |
255 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 911.79578 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.82355 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.82355 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.82355 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.82355 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.82355 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.41177 |
262 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.54903 |
263 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18407.69000 |
264 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9203.84500 |
265 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73528 |
266 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73528 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18407.69000 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27179.04755 |
269 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
270 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
271 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 27179.04755 |
272 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.87190 |
273 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.87190 |
274 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 965.33720 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.87190 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.87190 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.87190 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.57546 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.87190 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.43595 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.58127 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19258.83000 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9629.41500 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73953 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73953 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19258.83000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28512.43788 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 28512.43788 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 35101.6 | 12.24 | 12.24 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 18716.2 | 12.19 | 12.19 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 19718.8 | 12.05 | 12.05 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 19549.0 | 12.03 | 12.03 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 19666.7 | 12.05 | 12.05 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 34523.7 | 12.24 | 12.24 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 18085.6 | 13.08 | 13.08 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 17972.4 | 13.08 | 13.08 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 17759.3 | 13.09 | 13.09 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 18572.5 | 12.22 | 12.22 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 4.5516303137E-002 | 0.2367577731 | Pass | Pass | 0.8125844463 | 6.2733640613 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.3317568655E-002 | 0.1932611885 | Pass | Pass | 9.4322880816E-002 | 0.4284142400 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 4.5823328746E-002 | 0.2386429417 | Pass | Pass | 9.4715157687E-002 | 0.7244319556 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.0544467689E-002 | 0.2675863542 | Pass | Pass | 9.8365579698E-002 | 0.7877896244 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 5.4308285975E-002 | 0.2909006497 | Pass | Pass | 9.2119575371E-002 | 0.7340126332 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 6.4931612936E-002 | 0.3278756318 | Pass | Pass | 2.7267663899E-002 | 9.9206337960E-002 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 6.4229724407E-002 | 0.3257504897 | Pass | Pass | 2.6043311461E-002 | 9.0109352956E-002 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 6.5203610531E-002 | 0.3308021559 | Pass | Pass | 2.5930273803E-002 | 8.9844529345E-002 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 7.0080923560E-002 | 0.3565178480 | Pass | Pass | 2.5431515541E-002 | 9.0407061250E-002 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 9.4244535365E-002 | 0.4001810803 | Pass | Pass | 2.0335733470E-002 | 7.1451265748E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3943.20 | 267.65 | 0.00 | 421.07 | 316.91 | 4948.87 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 1.408 | 0.210 | 0.290 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 1.408 | 0.210 | 0.290 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 7.5512 | 348.39 | 2630.74 | LightsWired | LTG_SCH_BASE_LPD1 | 81.37 | 168.00 | 80.49 | 0.0000 | Y | 39.75 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 4.0372 | 348.39 | 1406.51 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 24.96 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 7.5749 | 174.19 | 1319.49 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 82.90 | 168.00 | 81.97 | 0.0000 | Y | 20.30 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 6.1909 | 174.19 | 1078.41 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 19.14 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 7.5320 | 348.39 | 2624.05 | LightsWired | LTG_SCH_BASE_LPD2 | 60.23 | 168.00 | 58.11 | 0.0000 | Y | 28.62 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 5.0436 | 4180.64 | 21085.58 | 277.79 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 437.57 | AstronomicalClock | - | 42.04 | 42.04 | 3.45 | |
EXTERIOR_LIGHTS_B | 1882.64 | AstronomicalClock | - | 83.67 | 62.85 | 22.21 | |
EXTERIOR_LIGHTS_C | 1466.47 | AstronomicalClock | - | 83.67 | 55.85 | 15.38 | |
Exterior Lighting Total | 3786.68 | 41.04 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36387.11 | 26784.55 | 9602.56 | 0.74 | 3.99 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19416.12 | 14441.32 | 4974.80 | 0.74 | 3.99 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20508.58 | 15752.85 | 4755.73 | 0.77 | 3.99 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20337.28 | 15682.48 | 4654.80 | 0.77 | 3.99 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20453.96 | 15708.23 | 4745.73 | 0.77 | 3.99 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 35786.82 | 26333.73 | 9453.09 | 0.74 | 3.99 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18749.05 | 13809.80 | 4939.25 | 0.74 | 4.32 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18630.29 | 13711.52 | 4918.77 | 0.74 | 4.32 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18407.69 | 13534.81 | 4872.88 | 0.74 | 4.32 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19258.83 | 14242.48 | 5016.35 | 0.74 | 3.99 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 35101.6 | 12.24 | 12.24 | ||||
PSZ-AC_2:2 COOLING COIL | 18716.2 | 12.19 | 12.19 | ||||
PSZ-AC_3:3 COOLING COIL | 19718.8 | 12.05 | 12.05 | ||||
PSZ-AC_4:4 COOLING COIL | 19549.0 | 12.03 | 12.03 | ||||
PSZ-AC_5:5 COOLING COIL | 19666.7 | 12.05 | 12.05 | ||||
PSZ-AC_6:6 COOLING COIL | 34523.7 | 12.24 | 12.24 | ||||
PSZ-AC_7:7 COOLING COIL | 18085.6 | 13.08 | 13.08 | ||||
PSZ-AC_8:8 COOLING COIL | 17972.4 | 13.08 | 13.08 | ||||
PSZ-AC_9:9 COOLING COIL | 17759.3 | 13.09 | 13.09 | ||||
PSZ-AC_10:10 COOLING COIL | 18572.5 | 12.22 | 12.22 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 54549.74 | 0.88 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 28665.43 | 0.88 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 31468.55 | 0.88 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 31430.73 | 0.88 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 31399.06 | 0.88 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 52780.30 | 0.88 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 27671.50 | 0.88 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 27494.23 | 0.88 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 27179.05 | 0.88 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 28512.44 | 0.88 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.63 | 1747.18 | 1070.05 | 1.00 | 1.35 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.89 | 984.68 | 1107.16 | 1.00 | 1.43 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1112.23 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1110.35 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1108.78 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.60 | 1716.76 | 1070.05 | 1.00 | 1.35 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.84 | 933.06 | 1107.16 | 1.00 | 1.45 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.84 | 925.17 | 1107.16 | 1.00 | 1.45 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.82 | 911.80 | 1107.16 | 1.00 | 1.46 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.87 | 965.34 | 1107.16 | 1.00 | 1.44 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 18072.55 | 21687.06 | 62.25 | 1.361 | 1.633 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 23.89 | 23.89 | 0.00991 | 30.30 | 0.01337 | 0.411 | 0.00 |
SMSTORE1 | 10054.61 | 12065.53 | 69.27 | 0.732 | 0.879 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00973 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE2 | 11434.68 | 13721.62 | 78.77 | 0.837 | 1.005 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.88 | 0.01004 | 25.18 | 0.01336 | 0.206 | 0.00 |
SMSTORE3 | 11417.37 | 13700.85 | 78.65 | 0.836 | 1.003 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.88 | 0.00997 | 25.18 | 0.01336 | 0.206 | 0.00 |
SMSTORE4 | 11399.97 | 13679.96 | 78.53 | 0.835 | 1.001 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.88 | 0.01004 | 25.18 | 0.01336 | 0.206 | 0.00 |
LGSTORE2 | 17837.45 | 21404.94 | 61.44 | 1.295 | 1.553 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.01006 | 26.77 | 0.01336 | 0.411 | 0.00 |
SMSTORE5 | 9560.35 | 11472.42 | 65.86 | 0.695 | 0.834 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00989 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE6 | 9471.37 | 11365.64 | 65.25 | 0.689 | 0.826 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00991 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE7 | 9313.21 | 11175.85 | 64.16 | 0.677 | 0.812 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00996 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE8 | 9501.13 | 11401.36 | 65.45 | 0.691 | 0.829 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00999 | 26.77 | 0.01336 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 26587.58 | 31905.09 | 91.58 | 1.175 | 1.411 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00650 | -16.30 | 0.00092 | 0.411 | 0.00 |
SMSTORE1 | 12613.90 | 15136.68 | 86.90 | 0.558 | 0.669 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00643 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE2 | 12775.69 | 15330.83 | 88.01 | 0.565 | 0.678 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00645 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE3 | 12870.29 | 15444.35 | 88.66 | 0.569 | 0.683 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00645 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE4 | 13023.03 | 15627.64 | 89.71 | 0.576 | 0.691 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00647 | -16.30 | 0.00092 | 0.206 | 0.00 |
LGSTORE2 | 24926.89 | 29912.27 | 85.86 | 1.102 | 1.323 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00654 | -16.30 | 0.00092 | 0.411 | 0.00 |
SMSTORE5 | 13351.39 | 16021.67 | 91.98 | 0.590 | 0.708 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00649 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE6 | 13339.69 | 16007.63 | 91.90 | 0.590 | 0.708 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00649 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE7 | 13544.50 | 16253.40 | 93.31 | 0.599 | 0.719 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00651 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE8 | 16434.91 | 19721.89 | 113.22 | 0.727 | 0.872 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00653 | -16.30 | 0.00092 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.63 | 1.63 | 1.41 | 1.41 | 1.6328 | 1.6328 | 1.6328 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 0.89 | 0.89 | 0.67 | 0.67 | 0.8894 | 0.8788 | 0.8894 | 0.9881 | 1.0000 |
PSZ-AC_3:3 | 1.00 | 1.00 | 0.68 | 0.68 | 1.0046 | 1.0046 | 1.0046 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.00 | 1.00 | 0.68 | 0.68 | 1.0029 | 1.0029 | 1.0029 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.00 | 1.00 | 0.69 | 0.69 | 1.0015 | 1.0015 | 1.0015 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.60 | 1.60 | 1.32 | 1.32 | 1.6044 | 1.5535 | 1.6044 | 0.9683 | 1.0000 |
PSZ-AC_7:7 | 0.84 | 0.84 | 0.71 | 0.71 | 0.8428 | 0.8342 | 0.8428 | 0.9899 | 1.0000 |
PSZ-AC_8:8 | 0.84 | 0.84 | 0.71 | 0.71 | 0.8356 | 0.8263 | 0.8356 | 0.9888 | 1.0000 |
PSZ-AC_9:9 | 0.82 | 0.82 | 0.72 | 0.72 | 0.8235 | 0.8121 | 0.8235 | 0.9861 | 1.0000 |
PSZ-AC_10:10 | 0.85 | 0.85 | 0.87 | 0.87 | 0.8719 | 0.8719 | 0.8719 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 36387.110 | 26784.552 | 1.632810 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 18193.56 | 13228.31 | 1.088540 | 26.39 | 18.78 | 0.01078007 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 37.8012 | 23.89 | 0.00990851 | 52.2414 | 18072.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 54549.736 | 54549.736 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 54549.74 | 54549.74 | 1.632806 | 11.68 | 7.74 | 0.00509558 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 25.2008 | 21.10 | 0.00650101 | 40.8095 | 26587.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 19416.120 | 14441.322 | 0.889380 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 9708.06 | 7165.54 | 0.592920 | 26.29 | 18.64 | 0.01064156 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 34.6990 | 23.89 | 0.00981926 | 51.7777 | 9824.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 28665.430 | 28665.430 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28665.43 | 28665.43 | 0.889379 | 12.45 | 8.17 | 0.00515827 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 23.1327 | 21.10 | 0.00643252 | 40.3833 | 12613.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 20508.580 | 15752.845 | 1.004580 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 10254.29 | 7330.49 | 0.669720 | 25.09 | 18.31 | 0.01071752 | 12.80 | 11.87 | 0.00850000 | 25.18 | 0.01335791 | 20.33 | 30.7199 | 23.88 | 0.01003750 | 52.9208 | 11434.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 31468.554 | 31468.554 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31468.55 | 31468.55 | 1.004577 | 13.44 | 8.80 | 0.00531550 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.4800 | 21.10 | 0.00644648 | 40.4701 | 12775.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 20337.280 | 15682.483 | 1.002880 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 10168.64 | 7322.17 | 0.668587 | 25.09 | 18.27 | 0.01066156 | 12.80 | 11.87 | 0.00850000 | 25.18 | 0.01335791 | 20.33 | 30.7720 | 23.88 | 0.00996565 | 52.5462 | 11417.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 31430.729 | 31430.729 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31430.73 | 31430.73 | 1.002881 | 13.43 | 8.80 | 0.00531986 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.5147 | 21.10 | 0.00645438 | 40.5192 | 12870.29 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 20453.960 | 15708.232 | 1.001460 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 10226.98 | 7307.86 | 0.667640 | 25.09 | 18.32 | 0.01072093 | 12.80 | 11.87 | 0.00850000 | 25.18 | 0.01335791 | 20.33 | 30.8156 | 23.88 | 0.01003913 | 52.9291 | 11399.97 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 31399.056 | 31399.056 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31399.06 | 31399.06 | 1.001460 | 13.42 | 8.81 | 0.00532843 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.5438 | 21.10 | 0.00646719 | 40.5988 | 13023.03 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 35786.820 | 26333.731 | 1.604380 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 17893.41 | 13023.22 | 1.069587 | 26.42 | 18.79 | 0.01077644 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 38.4710 | 23.89 | 0.00988024 | 52.0941 | 17719.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 52780.298 | 52780.298 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 52780.30 | 52780.30 | 1.604382 | 11.51 | 7.67 | 0.00510236 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 25.6473 | 21.10 | 0.00654361 | 41.0725 | 24926.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 18749.050 | 13809.800 | 0.842750 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 9374.52 | 6826.84 | 0.561833 | 26.41 | 18.78 | 0.01076953 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 36.6190 | 23.89 | 0.00990413 | 52.2182 | 9112.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 27671.502 | 27671.502 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27671.50 | 27671.50 | 0.842752 | 11.97 | 7.92 | 0.00513411 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 24.4126 | 21.10 | 0.00649383 | 40.7643 | 13351.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 18630.290 | 13711.521 | 0.835620 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 9315.15 | 6773.36 | 0.557080 | 26.42 | 18.79 | 0.01078415 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 36.9314 | 23.89 | 0.00991390 | 52.2689 | 9035.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 27494.234 | 27494.234 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27494.23 | 27494.23 | 0.835623 | 11.90 | 7.87 | 0.00512184 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 24.6208 | 21.10 | 0.00649293 | 40.7587 | 13339.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 18407.690 | 13534.806 | 0.823550 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 9203.84 | 6680.49 | 0.549033 | 26.44 | 18.81 | 0.01080154 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 37.4727 | 23.89 | 0.00992553 | 52.3292 | 8946.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 27179.048 | 27179.048 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27179.05 | 27179.05 | 0.823546 | 11.76 | 7.80 | 0.00511368 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 24.9819 | 21.10 | 0.00650886 | 40.8577 | 13544.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 19258.830 | 14242.483 | 0.871900 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 9629.42 | 6987.59 | 0.581267 | 26.27 | 18.74 | 0.01077778 | 12.80 | 11.87 | 0.00850000 | 29.91 | 0.01336627 | 21.72 | 35.3947 | 23.89 | 0.00995072 | 52.4606 | 9388.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 28512.438 | 28512.438 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28512.44 | 28512.44 | 0.871905 | 12.28 | 8.15 | 0.00520843 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 23.5963 | 21.10 | 0.00653159 | 41.0019 | 16434.91 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36387.110 | 26784.552 | 1.632810 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8796 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.632806 | 1.91679234 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | Sensible | 18193.56 | 13228.31 | 1.0000 | 1.27786466 | 1.088540 | 26.39 | 18.78 | 0.01078007 | 54008.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18193.56 | 30.30 | 0.01336696 | 21.83 | 0.41148071 | 37.8012 | 23.89 | 0.00990851 | 23.89 | 0.00990851 | 52.2414 | 18072.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 54549.736 | 54549.736 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.632806 | 1.91679234 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 54549.74 | 54549.74 | 1.0000 | 1.91679234 | 1.632806 | 11.68 | 7.74 | 0.00509558 | 24589.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54549.74 | -16.30 | 0.00092409 | -16.30 | 0.41148071 | 25.2008 | 21.11 | 0.00650101 | 21.10 | 0.00650101 | 40.8095 | 26587.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19416.120 | 14441.322 | 0.889380 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6221 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.889379 | 1.04406407 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 9708.06 | 7165.54 | 1.0000 | 0.69604380 | 0.592920 | 26.29 | 18.64 | 0.01064156 | 53554.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9708.06 | 30.30 | 0.01336696 | 21.83 | 0.20573751 | 34.6990 | 23.89 | 0.00981926 | 23.89 | 0.00981926 | 51.7777 | 9824.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28665.430 | 28665.430 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.889379 | 1.04406407 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28665.43 | 28665.43 | 1.0000 | 1.04406407 | 0.889379 | 12.45 | 8.17 | 0.00515827 | 25532.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28665.43 | -16.30 | 0.00092409 | -16.30 | 0.20573751 | 23.1327 | 21.11 | 0.00643252 | 21.10 | 0.00643252 | 40.3833 | 12613.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20508.580 | 15752.845 | 1.004580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7633 | 1004.8586 | 1.1739 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.004577 | 1.17929892 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 10254.29 | 7330.49 | 1.0000 | 0.78620126 | 0.669720 | 25.09 | 18.31 | 0.01071752 | 52517.2 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10254.29 | 25.18 | 0.01335791 | 20.33 | 0.20573751 | 30.7199 | 23.91 | 0.01003750 | 23.88 | 0.01003750 | 52.9208 | 11434.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31468.554 | 31468.554 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.004577 | 1.17929892 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31468.55 | 31468.55 | 1.0000 | 1.17929892 | 1.004577 | 13.44 | 8.80 | 0.00531550 | 26936.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31468.55 | -16.30 | 0.00092409 | -16.30 | 0.20573751 | 20.4800 | 21.11 | 0.00644648 | 21.10 | 0.00644648 | 40.4701 | 12775.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20337.280 | 15682.483 | 1.002880 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6593 | 1004.8586 | 1.1739 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.002881 | 1.17730687 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 10168.64 | 7322.17 | 1.0000 | 0.78487081 | 0.668587 | 25.09 | 18.27 | 0.01066156 | 52376.2 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10168.64 | 25.18 | 0.01335791 | 20.33 | 0.20573751 | 30.7720 | 23.91 | 0.00996565 | 23.88 | 0.00996565 | 52.5462 | 11417.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31430.729 | 31430.729 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.002881 | 1.17730687 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31430.73 | 31430.73 | 1.0000 | 1.17730687 | 1.002881 | 13.43 | 8.80 | 0.00531986 | 26934.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31430.73 | -16.30 | 0.00092409 | -16.30 | 0.20573751 | 20.5147 | 21.11 | 0.00645438 | 21.10 | 0.00645438 | 40.5192 | 12870.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20453.960 | 15708.232 | 1.001460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7697 | 1004.8586 | 1.1739 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.001460 | 1.17563923 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 10226.98 | 7307.86 | 1.0000 | 0.78375950 | 0.667640 | 25.09 | 18.32 | 0.01072093 | 52526.6 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10226.98 | 25.18 | 0.01335791 | 20.33 | 0.20573751 | 30.8156 | 23.91 | 0.01003913 | 23.88 | 0.01003913 | 52.9291 | 11399.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31399.056 | 31399.056 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.001460 | 1.17563923 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31399.06 | 31399.06 | 1.0000 | 1.17563923 | 1.001460 | 13.42 | 8.81 | 0.00532843 | 26945.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31399.06 | -16.30 | 0.00092409 | -16.30 | 0.20573751 | 20.5438 | 21.11 | 0.00646719 | 21.10 | 0.00646719 | 40.5988 | 13023.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 35786.820 | 26333.731 | 1.604380 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8729 | 1004.8586 | 1.1739 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.604382 | 1.88342496 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 17893.41 | 13023.22 | 1.0000 | 1.25561486 | 1.069587 | 26.42 | 18.79 | 0.01077644 | 54032.2 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17893.41 | 30.30 | 0.01336696 | 21.83 | 0.41148071 | 38.4710 | 23.89 | 0.00988024 | 23.89 | 0.00988024 | 52.0941 | 17719.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52780.298 | 52780.298 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.604382 | 1.88342496 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 52780.30 | 52780.30 | 1.0000 | 1.88342496 | 1.604382 | 11.51 | 7.67 | 0.00510236 | 24437.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52780.30 | -16.30 | 0.00092409 | -16.30 | 0.41148071 | 25.6473 | 21.11 | 0.00654361 | 21.10 | 0.00654361 | 41.0725 | 24926.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18749.050 | 13809.800 | 0.842750 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8600 | 1004.8586 | 1.1739 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.842752 | 0.98932757 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 9374.52 | 6826.84 | 1.0000 | 0.65955037 | 0.561833 | 26.41 | 18.78 | 0.01076953 | 53999.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9374.52 | 30.30 | 0.01336696 | 21.83 | 0.20573751 | 36.6190 | 23.89 | 0.00990413 | 23.89 | 0.00990413 | 52.2182 | 9112.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27671.502 | 27671.502 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.842752 | 0.98932757 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27671.50 | 27671.50 | 1.0000 | 0.98932757 | 0.842752 | 11.97 | 7.92 | 0.00513411 | 24986.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27671.50 | -16.30 | 0.00092409 | -16.30 | 0.20573751 | 24.4126 | 21.11 | 0.00649383 | 21.10 | 0.00649383 | 40.7643 | 13351.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18630.290 | 13711.521 | 0.835620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8872 | 1004.8586 | 1.1739 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.835623 | 0.98095951 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 9315.15 | 6773.36 | 1.0000 | 0.65397031 | 0.557080 | 26.42 | 18.79 | 0.01078415 | 54050.5 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9315.15 | 30.30 | 0.01336696 | 21.83 | 0.20573751 | 36.9314 | 23.89 | 0.00991390 | 23.89 | 0.00991390 | 52.2689 | 9035.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27494.234 | 27494.234 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.835623 | 0.98095951 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27494.23 | 27494.23 | 1.0000 | 0.98095951 | 0.835623 | 11.90 | 7.87 | 0.00512184 | 24876.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27494.23 | -16.30 | 0.00092409 | -16.30 | 0.20573751 | 24.6208 | 21.11 | 0.00649293 | 21.10 | 0.00649293 | 40.7587 | 13339.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18407.690 | 13534.806 | 0.823550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9195 | 1004.8586 | 1.1739 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.823546 | 0.96678110 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 9203.84 | 6680.49 | 1.0000 | 0.64452413 | 0.549033 | 26.44 | 18.81 | 0.01080154 | 54111.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9203.84 | 30.30 | 0.01336696 | 21.83 | 0.20573751 | 37.4727 | 23.89 | 0.00992553 | 23.89 | 0.00992553 | 52.3292 | 8946.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27179.048 | 27179.048 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.823546 | 0.96678110 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27179.05 | 27179.05 | 1.0000 | 0.96678110 | 0.823546 | 11.76 | 7.80 | 0.00511368 | 24718.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27179.05 | -16.30 | 0.00092409 | -16.30 | 0.20573751 | 24.9819 | 21.11 | 0.00650886 | 21.10 | 0.00650886 | 40.8577 | 13544.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19258.830 | 14242.483 | 0.871900 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8754 | 1004.8586 | 1.1739 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.871905 | 1.02355131 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 9629.42 | 6987.59 | 1.0000 | 0.68236365 | 0.581267 | 26.27 | 18.74 | 0.01077778 | 53873.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9629.42 | 29.91 | 0.01336627 | 21.72 | 0.20573751 | 35.3947 | 23.89 | 0.00995072 | 23.89 | 0.00995072 | 52.4606 | 9388.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28512.438 | 28512.438 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.871905 | 1.02355131 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28512.44 | 28512.44 | 1.0000 | 1.02355131 | 0.871905 | 12.28 | 8.15 | 0.00520843 | 25482.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28512.44 | -16.30 | 0.00092409 | -16.30 | 0.20573751 | 23.5963 | 21.10 | 0.00653159 | 21.10 | 0.00653159 | 41.0019 | 16434.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.63 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.89 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.00 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.00 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.00 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.60 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.84 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.84 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.82 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.87 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
LGSTORE1 | LGSTORE1_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE1 | SMSTORE1_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE2 | SMSTORE2_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE3 | SMSTORE3_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE4 | SMSTORE4_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LGSTORE2 | LGSTORE2_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE5 | SMSTORE5_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE6 | SMSTORE6_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE7 | SMSTORE7_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE8 | SMSTORE8_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3118.17 | 4254.17 | 2188.50 |
SMSTORE1 | 2419.17 | 3907.00 | 1391.83 |
SMSTORE2 | 2181.33 | 3068.33 | 1385.00 |
SMSTORE3 | 2239.83 | 3096.00 | 1454.17 |
SMSTORE4 | 2289.67 | 3167.00 | 1548.17 |
LGSTORE2 | 2185.50 | 3011.67 | 1604.83 |
SMSTORE5 | 2153.50 | 3033.67 | 1625.00 |
SMSTORE6 | 2157.17 | 3051.67 | 1642.83 |
SMSTORE7 | 2204.67 | 3109.50 | 1715.33 |
SMSTORE8 | 2421.67 | 3215.33 | 1965.67 |
Facility | 3727.50 | 4707.00 | 2779.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 16.17 | 0.00 | 6.00 | 0.00 |
SMSTORE1 | 3.17 | 0.00 | 0.50 | 0.00 |
SMSTORE2 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 2.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 3.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 9.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 9.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 13.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 39.67 | 0.00 | 0.00 | 0.00 |
Facility | 52.00 | 0.00 | 6.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.723 | 0.241 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.646 | 0.252 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.770 | 0.328 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.766 | 0.328 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.754 | 0.328 | 0.000 | 0.000 |
LGSTORE2 | 24.77 | 56.25 | 1805.20 | 0.762 | 0.315 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.914 | 0.350 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.906 | 0.350 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.884 | 0.350 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.748 | 0.377 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.431 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.431 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.431 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.77 | 56.25 | 1805.20 | 0.455 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.455 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.455 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.455 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.454 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.212 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
LGSTORE2 | PSZ-AC_6:6 | 24.77 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.212 |
SMSTORE5 | PSZ-AC_7:7 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE6 | PSZ-AC_8:8 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE7 | PSZ-AC_9:9 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE8 | PSZ-AC_10:10 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
Total Facility | 120.95 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 1.274 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 7521757.58 | 0.00 | 7521757.58 | 2993858.48 | 10515616.05 | 7870781.79 | 3145.96 | 4232.83 | 1381.21 | 20.74 |
SMSTORE1 | 3361462.74 | 0.00 | 3361462.74 | 1454836.47 | 4816299.21 | 3935374.10 | 4285.43 | 3077.33 | 1397.24 | 24.53 |
SMSTORE2 | 3059107.74 | 0.00 | 3059107.74 | 1502250.16 | 4561357.90 | 3701819.01 | 4319.02 | 3428.50 | 1012.48 | 87.78 |
SMSTORE3 | 3042349.06 | 0.00 | 3042349.06 | 1502250.16 | 4544599.22 | 3701819.01 | 4319.14 | 3448.50 | 992.36 | 86.11 |
SMSTORE4 | 2991601.07 | 0.00 | 2991601.07 | 1502250.16 | 4493851.23 | 3701819.01 | 4321.81 | 3490.83 | 947.36 | 83.28 |
LGSTORE2 | 5533841.35 | 0.00 | 5533841.35 | 2777494.96 | 8311336.31 | 7907875.00 | 4690.63 | 3236.08 | 833.29 | 67.33 |
SMSTORE5 | 3344644.99 | 0.00 | 3344644.99 | 1515968.53 | 4860613.52 | 3953920.18 | 4672.91 | 3122.33 | 964.75 | 91.95 |
SMSTORE6 | 3315117.31 | 0.00 | 3315117.31 | 1515968.53 | 4831085.84 | 3953920.18 | 4672.96 | 3137.67 | 949.38 | 89.46 |
SMSTORE7 | 3228026.48 | 0.00 | 3228026.48 | 1515968.53 | 4743995.02 | 3953920.18 | 4675.35 | 3193.50 | 891.15 | 80.22 |
SMSTORE8 | 2698134.60 | 0.00 | 2698134.60 | 1946294.26 | 4644428.86 | 3953920.18 | 4710.73 | 3391.50 | 657.77 | 34.02 |
Total Facility | 38096042.92 | 0.00 | 38096042.92 | 18227140.23 | 56323183.15 | 46635168.64 | 4713.11 | 4779.83 | 1647.71 | 185.30 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.3566 | 0.0000 | 0.3566 | 0.1189 | 0.4755 | 0.2682 | 237.19 | 4232.83 | 1369.98 |
SMSTORE1 | 0.1591 | 0.0000 | 0.1591 | 0.0623 | 0.2214 | 0.1341 | 1380.62 | 3077.33 | 1382.04 |
SMSTORE2 | 0.1896 | 0.0000 | 0.1896 | 0.0811 | 0.2706 | 0.1285 | 0.00 | 3427.67 | 967.33 |
SMSTORE3 | 0.1886 | 0.0000 | 0.1886 | 0.0811 | 0.2696 | 0.1285 | 0.00 | 3448.00 | 947.00 |
SMSTORE4 | 0.1857 | 0.0000 | 0.1857 | 0.0811 | 0.2667 | 0.1285 | 0.00 | 3490.67 | 904.33 |
LGSTORE2 | 0.3754 | 0.0000 | 0.3754 | 0.1559 | 0.5313 | 0.2958 | 0.00 | 3235.50 | 794.50 |
SMSTORE5 | 0.2249 | 0.0000 | 0.2249 | 0.0864 | 0.3113 | 0.1479 | 0.00 | 3121.50 | 908.50 |
SMSTORE6 | 0.2230 | 0.0000 | 0.2230 | 0.0864 | 0.3094 | 0.1479 | 0.00 | 3136.83 | 893.17 |
SMSTORE7 | 0.2177 | 0.0000 | 0.2177 | 0.0864 | 0.3041 | 0.1479 | 0.00 | 3192.67 | 837.33 |
SMSTORE8 | 0.1845 | 0.0000 | 0.1845 | 0.0931 | 0.2776 | 0.1479 | 0.00 | 3391.33 | 638.67 |
Total Facility | 2.3049 | 0.0000 | 2.3049 | 0.9327 | 3.2376 | 1.6752 | 1481.05 | 4775.83 | 1609.94 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 10365967.65 | 0.00 | 10365967.65 | 7870781.79 | 3140.04 | 0.17 | 5619.79 | 20.74 |
PSZ-AC_2:2 | 4632511.35 | 0.00 | 4632511.35 | 3935374.10 | 4243.79 | 2.08 | 4514.12 | 24.53 |
PSZ-AC_3:3 | 4215788.37 | 0.00 | 4215788.37 | 3701819.01 | 4309.35 | 0.83 | 4449.82 | 87.61 |
PSZ-AC_4:4 | 4192692.33 | 0.00 | 4192692.33 | 3701819.01 | 4310.31 | 0.17 | 4449.52 | 85.94 |
PSZ-AC_5:5 | 4122753.80 | 0.00 | 4122753.80 | 3701819.01 | 4313.14 | 1.42 | 4445.44 | 83.11 |
PSZ-AC_6:6 | 7626384.45 | 0.00 | 7626384.45 | 7907875.00 | 4684.96 | 0.67 | 4074.37 | 67.33 |
PSZ-AC_7:7 | 4609257.41 | 0.00 | 4609257.41 | 3953920.18 | 4664.05 | 0.50 | 4095.45 | 91.95 |
PSZ-AC_8:8 | 4568565.29 | 0.00 | 4568565.29 | 3953920.18 | 4664.87 | 0.53 | 4094.60 | 89.29 |
PSZ-AC_9:9 | 4448545.37 | 0.00 | 4448545.37 | 3953920.18 | 4667.52 | 0.33 | 4092.15 | 80.05 |
PSZ-AC_10:10 | 3718337.76 | 0.00 | 3718337.76 | 3953920.18 | 4705.57 | 0.00 | 4054.43 | 33.85 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.4915 | 0.0000 | 0.4915 | 0.2682 | 233.94 | 0.00 | 5606.06 |
PSZ-AC_2:2 | 0.2192 | 0.0000 | 0.2192 | 0.1341 | 1339.65 | 2.08 | 4498.26 |
PSZ-AC_3:3 | 0.2613 | 0.0000 | 0.2613 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2599 | 0.0000 | 0.2599 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2559 | 0.0000 | 0.2559 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5174 | 0.0000 | 0.5174 | 0.2958 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3099 | 0.0000 | 0.3099 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3073 | 0.0000 | 0.3073 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3000 | 0.0000 | 0.3000 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2542 | 0.0000 | 0.2542 | 0.1479 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 813.53 | 645.85 | 0.00 | 0.00 | 0.00 | 4186.75 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 726.59 | 884.86 | 0.00 | 0.00 | 0.00 | 3274.97 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 548.94 | 539.50 | 0.00 | 0.00 | 0.00 | 3394.17 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 543.78 | 520.42 | 0.00 | 0.00 | 0.00 | 3416.75 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 519.65 | 494.21 | 0.00 | 0.00 | 0.00 | 3464.25 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 529.58 | 368.08 | 0.00 | 0.00 | 0.00 | 3199.67 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 472.81 | 527.64 | 0.00 | 0.00 | 0.00 | 3121.50 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 467.95 | 514.51 | 0.00 | 0.00 | 0.00 | 3136.83 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 447.31 | 470.08 | 0.00 | 0.00 | 0.00 | 3192.67 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 426.54 | 268.22 | 0.00 | 0.00 | 0.00 | 3369.08 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.1142 | 0.6497 | 0.0000 | 0.0000 | 0.0000 | 0.3725 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.5965 | 0.3078 | 0.0000 | 0.0000 | 0.0000 | 0.1782 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.6853 | 0.3911 | 0.0000 | 0.0000 | 0.0000 | 0.1765 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.6841 | 0.3924 | 0.0000 | 0.0000 | 0.0000 | 0.1765 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.6838 | 0.3921 | 0.0000 | 0.0000 | 0.0000 | 0.1765 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 1.0959 | 0.6882 | 0.0000 | 0.0000 | 0.0000 | 0.4077 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.8726 | 0.4713 | 0.0000 | 0.0000 | 0.0000 | 0.2041 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.8646 | 0.4693 | 0.0000 | 0.0000 | 0.0000 | 0.2041 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.8512 | 0.4639 | 0.0000 | 0.0000 | 0.0000 | 0.2040 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.5952 | 0.3660 | 0.0000 | 0.0000 | 0.0000 | 0.2037 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 835 |
Defaulted Fields | 817 |
Fields with Defaults | 2693 |
Autosized Fields | 174 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 672.55 | 2102.83 | 01-JAN-08:00 | 68681.65 | 15-JUL-14:40 |
Electricity:Building | 405.94 | 891.83 | 01-JAN-00:20 | 25756.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 90.96 | 148.64 | 01-JAN-00:20 | 4765.21 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 405.94 | 891.83 | 01-JAN-00:20 | 25756.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 64.71 | 75.00 | 01-JAN-00:20 | 3421.96 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 64.71 | 75.00 | 01-JAN-00:20 | 3421.96 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 52.56 | 74.32 | 01-JAN-00:20 | 2762.01 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 39.44 | 37.50 | 01-JAN-00:20 | 2090.38 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 39.44 | 37.50 | 01-JAN-00:20 | 2090.38 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 47.80 | 148.64 | 01-JAN-00:10 | 3421.36 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 28.62 | 75.00 | 01-JAN-00:10 | 2078.11 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 28.62 | 75.00 | 01-JAN-00:10 | 2078.11 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityProduced:Facility | 54.95 | -0.00 | 11-MAY-19:20 | 11250.00 | 14-JUN-11:50 |
ElectricityProduced:Plant | 54.95 | -0.00 | 11-MAY-19:20 | 11250.00 | 14-JUN-11:50 |
Photovoltaic:ElectricityProduced | 57.54 | 0.00 | 01-JAN-00:10 | 11807.23 | 14-JUN-12:20 |
PowerConversion:ElectricityProduced | -2.59 | -557.23 | 14-JUN-12:20 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 65.12 | 1211.00 | 11-JAN-07:10 | 13728.84 | 07-JAN-15:50 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 617.60 | 0.00 | 07-MAY-07:00 | 61938.01 | 15-JUL-14:40 |
ElectricityPurchased:Plant | 617.60 | 0.00 | 07-MAY-07:00 | 61938.01 | 15-JUL-14:40 |
Cogeneration:ElectricityPurchased | 617.60 | 0.00 | 07-MAY-07:00 | 61938.01 | 15-JUL-14:40 |
General:Cogeneration:ElectricityPurchased | 617.60 | 0.00 | 07-MAY-07:00 | 61938.01 | 15-JUL-14:40 |
ElectricitySurplusSold:Facility | 0.01 | 0.00 | 01-JAN-00:10 | 997.76 | 04-JUN-07:00 |
ElectricitySurplusSold:Plant | 0.01 | 0.00 | 01-JAN-00:10 | 997.76 | 04-JUN-07:00 |
Cogeneration:ElectricitySurplusSold | 0.01 | 0.00 | 01-JAN-00:10 | 997.76 | 04-JUN-07:00 |
General:Cogeneration:ElectricitySurplusSold | 0.01 | 0.00 | 01-JAN-00:10 | 997.76 | 04-JUN-07:00 |
ElectricityNet:Facility | 617.59 | -997.76 | 04-JUN-07:00 | 61938.01 | 15-JUL-14:40 |
ElectricityNet:Plant | 617.59 | -997.76 | 04-JUN-07:00 | 61938.01 | 15-JUL-14:40 |
Cogeneration:ElectricityNet | 617.59 | -997.76 | 04-JUN-07:00 | 61938.01 | 15-JUL-14:40 |
General:Cogeneration:ElectricityNet | 617.59 | -997.76 | 04-JUN-07:00 | 61938.01 | 15-JUL-14:40 |
Electricity:HVAC | 160.44 | 0.00 | 01-JAN-00:10 | 36300.73 | 15-JUL-14:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 48.04 | 0.00 | 01-JAN-00:10 | 29572.32 | 15-JUL-14:00 |
General:Cooling:Electricity | 48.04 | 0.00 | 01-JAN-00:10 | 29572.32 | 15-JUL-14:00 |
Fans:Electricity | 112.40 | 0.00 | 01-JAN-00:10 | 8887.61 | 07-FEB-08:10 |
General:Fans:Electricity | 112.40 | 0.00 | 01-JAN-00:10 | 8887.61 | 07-FEB-08:10 |
ExteriorLights:Electricity | 41.04 | 0.00 | 01-JAN-08:00 | 3786.68 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 41.04 | 0.00 | 01-JAN-08:00 | 3786.68 | 01-JAN-06:10 |
WaterSystems:Electricity | 65.12 | 1211.00 | 11-JAN-07:10 | 13728.84 | 07-JAN-15:50 |
Water Heater:WaterSystems:Electricity | 65.12 | 1211.00 | 11-JAN-07:10 | 13728.84 | 07-JAN-15:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 506.12 | 0.00 | 01-JAN-00:10 | 201719.01 | 07-FEB-08:10 |
NaturalGas:HVAC | 506.12 | 0.00 | 01-JAN-00:10 | 201719.01 | 07-FEB-08:10 |
Heating:NaturalGas | 506.12 | 0.00 | 01-JAN-00:10 | 201719.01 | 07-FEB-08:10 |
General:Heating:NaturalGas | 506.12 | 0.00 | 01-JAN-00:10 | 201719.01 | 07-FEB-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1085.05 | 0.00 | 01-JAN-00:10 | 344619.83 | 07-FEB-08:10 |
EnergyTransfer:Building | 431.54 | 0.00 | 01-JAN-00:10 | 167107.10 | 07-FEB-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 82.60 | 0.00 | 01-JAN-00:10 | 32718.27 | 07-FEB-08:10 |
Heating:EnergyTransfer | 218.09 | 0.00 | 01-JAN-00:10 | 167107.10 | 07-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 34.92 | 0.00 | 01-JAN-00:10 | 32718.27 | 07-FEB-08:10 |
General:Heating:EnergyTransfer | 218.09 | 0.00 | 01-JAN-00:10 | 167107.10 | 07-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 34.92 | 0.00 | 01-JAN-00:10 | 32718.27 | 07-FEB-08:10 |
Cooling:EnergyTransfer | 213.44 | 0.00 | 01-JAN-00:10 | 69342.52 | 21-JUL-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 47.67 | 0.00 | 01-JAN-00:10 | 11435.18 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer | 213.44 | 0.00 | 01-JAN-00:10 | 69342.52 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 47.67 | 0.00 | 01-JAN-00:10 | 11435.18 | 21-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 39.19 | 0.00 | 01-JAN-00:10 | 13842.04 | 07-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 12.08 | 0.00 | 01-JAN-00:10 | 13842.04 | 07-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 12.08 | 0.00 | 01-JAN-00:10 | 13842.04 | 07-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 27.10 | 0.00 | 01-JAN-00:10 | 7647.59 | 03-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 27.10 | 0.00 | 01-JAN-00:10 | 7647.59 | 03-JUN-18:20 |
EnergyTransfer:Zone:SMSTORE2 | 33.65 | 0.00 | 01-JAN-00:10 | 14756.55 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 14.30 | 0.00 | 01-JAN-00:10 | 14756.55 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 14.30 | 0.00 | 01-JAN-00:10 | 14756.55 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 19.36 | 0.00 | 01-JAN-00:10 | 5988.43 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 19.36 | 0.00 | 01-JAN-00:10 | 5988.43 | 21-JUL-13:50 |
EnergyTransfer:Zone:SMSTORE3 | 34.13 | 0.00 | 01-JAN-00:10 | 15655.39 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 15.22 | 0.00 | 01-JAN-00:10 | 15655.39 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 15.22 | 0.00 | 01-JAN-00:10 | 15655.39 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 18.91 | 0.00 | 01-JAN-00:10 | 6003.40 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 18.91 | 0.00 | 01-JAN-00:10 | 6003.40 | 21-JUL-13:50 |
EnergyTransfer:Zone:SMSTORE4 | 34.41 | 0.00 | 01-JAN-00:10 | 16278.11 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 16.85 | 0.00 | 01-JAN-00:10 | 16278.11 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 16.85 | 0.00 | 01-JAN-00:10 | 16278.11 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 17.56 | 0.00 | 01-JAN-00:10 | 5886.52 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 17.56 | 0.00 | 01-JAN-00:10 | 5886.52 | 21-JUL-13:50 |
EnergyTransfer:Zone:LGSTORE2 | 62.86 | 0.00 | 01-JAN-00:10 | 32500.52 | 07-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 32.72 | 0.00 | 01-JAN-00:10 | 32500.52 | 07-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 32.72 | 0.00 | 01-JAN-00:10 | 32500.52 | 07-FEB-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 30.14 | 0.00 | 01-JAN-00:10 | 10974.00 | 21-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 30.14 | 0.00 | 01-JAN-00:10 | 10974.00 | 21-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE5 | 32.81 | 0.00 | 01-JAN-00:10 | 16351.02 | 13-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 18.64 | 0.00 | 01-JAN-00:10 | 16351.02 | 13-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 18.64 | 0.00 | 01-JAN-00:10 | 16351.02 | 13-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 14.16 | 0.00 | 01-JAN-00:10 | 5697.12 | 21-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 14.16 | 0.00 | 01-JAN-00:10 | 5697.12 | 21-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 32.83 | 0.00 | 01-JAN-00:10 | 16471.24 | 13-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 19.02 | 0.00 | 01-JAN-00:10 | 16471.24 | 13-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 19.02 | 0.00 | 01-JAN-00:10 | 16471.24 | 13-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 13.81 | 0.00 | 01-JAN-00:10 | 5654.70 | 21-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 13.81 | 0.00 | 01-JAN-00:10 | 5654.70 | 21-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 33.91 | 0.00 | 01-JAN-00:10 | 16999.07 | 21-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 21.28 | 0.00 | 01-JAN-00:10 | 16999.07 | 21-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 21.28 | 0.00 | 01-JAN-00:10 | 16999.07 | 21-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 12.63 | 0.00 | 01-JAN-00:10 | 5600.95 | 21-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 12.63 | 0.00 | 01-JAN-00:10 | 5600.95 | 21-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 45.16 | 0.00 | 01-JAN-00:10 | 19492.81 | 07-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 33.05 | 0.00 | 01-JAN-00:10 | 19492.81 | 07-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 33.05 | 0.00 | 01-JAN-00:10 | 19492.81 | 07-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 12.10 | 0.00 | 01-JAN-00:10 | 6047.26 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 12.10 | 0.00 | 01-JAN-00:10 | 6047.26 | 21-JUL-13:00 |
EnergyTransfer:HVAC | 653.51 | 0.00 | 01-JAN-00:10 | 177512.73 | 07-FEB-08:10 |
HeatingCoils:EnergyTransfer | 445.38 | 0.00 | 01-JAN-00:10 | 177512.73 | 07-FEB-08:10 |
CoolingCoils:EnergyTransfer | 208.13 | 0.00 | 01-JAN-00:10 | 136590.44 | 15-JUL-14:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 34.925 | -47.674 | 0.000 | 0.000 | 25.496 | 64.707 | 26.249 | 10.107 | 0.000 | 1.059 | 0.002 | 0.000 | -7.534 | 0.000 | -44.032 | -63.303 |
SMSTORE1 | 0.000 | 0.000 | 12.083 | -27.104 | 0.000 | 0.000 | 12.599 | 39.440 | 13.125 | 4.997 | 0.000 | 0.566 | 0.001 | 0.000 | -3.930 | 0.000 | -21.201 | -30.574 |
SMSTORE2 | 0.000 | 0.000 | 14.296 | -19.359 | 0.000 | 0.000 | 7.640 | 28.854 | 10.421 | 4.987 | 0.000 | 0.554 | 0.002 | 0.000 | -3.902 | 0.000 | -21.904 | -21.587 |
SMSTORE3 | 0.000 | 0.000 | 15.219 | -18.910 | 0.000 | 0.000 | 7.648 | 28.854 | 10.421 | 4.995 | 0.000 | 0.554 | 0.001 | 0.000 | -3.866 | 0.000 | -21.833 | -23.081 |
SMSTORE4 | 0.000 | 0.000 | 16.850 | -17.555 | 0.000 | 0.000 | 7.662 | 28.854 | 10.421 | 5.010 | 0.000 | 0.554 | 0.003 | 0.000 | -3.825 | 0.000 | -21.735 | -26.237 |
LGSTORE2 | 0.000 | 0.000 | 32.721 | -30.137 | 0.000 | 0.000 | 26.364 | 28.624 | 19.173 | 10.064 | 0.000 | 1.001 | 0.001 | 0.000 | -7.448 | 0.000 | -40.008 | -40.353 |
SMSTORE5 | 0.000 | 0.000 | 18.643 | -14.164 | 0.000 | 0.000 | 13.132 | 14.614 | 9.586 | 5.008 | 0.000 | 0.555 | 0.000 | 0.000 | -3.744 | 0.000 | -21.877 | -21.753 |
SMSTORE6 | 0.000 | 0.000 | 19.021 | -13.808 | 0.000 | 0.000 | 13.138 | 14.614 | 9.586 | 5.013 | 0.000 | 0.555 | 0.001 | 0.000 | -3.731 | 0.000 | -21.850 | -22.538 |
SMSTORE7 | 0.000 | 0.000 | 21.282 | -12.629 | 0.000 | 0.000 | 13.168 | 14.614 | 9.586 | 5.033 | 0.000 | 0.556 | 0.003 | 0.000 | -3.674 | 0.000 | -21.717 | -26.218 |
SMSTORE8 | 0.000 | 0.000 | 33.053 | -12.102 | 0.000 | 0.000 | 13.269 | 14.614 | 9.586 | 5.090 | 0.000 | 0.595 | 0.004 | 0.000 | -3.459 | 0.000 | -27.844 | -32.803 |
Total Facility | 0.000 | 0.000 | 218.093 | -213.441 | 0.000 | 0.000 | 140.115 | 277.790 | 128.154 | 60.304 | 0.000 | 6.550 | 0.017 | 0.000 | -45.114 | 0.000 | -264.003 | -308.448 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 07-AUG-07:03 | 0.00 | 0.00 | 0.00 | -22423.95 | 0.00 | 0.00 | 185.17 | 75.00 | 74.62 | 121.26 | 0.00 | 0.00 | 22114.10 | 0.00 | -0.00 | 0.00 | -146.22 | 0.00 |
SMSTORE1 | 03-JUN-18:08 | 0.00 | 0.00 | 0.00 | -14490.74 | 0.00 | 0.00 | 985.05 | 2090.38 | 671.63 | 20.08 | 0.00 | 0.00 | 10869.82 | 0.00 | -0.00 | 0.00 | -146.21 | 0.00 |
SMSTORE2 | 06-AUG-07:03 | 0.00 | 0.00 | 0.00 | -14778.26 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 61.94 | 0.00 | 0.00 | 14729.93 | 0.00 | -0.00 | 0.00 | -88.42 | 0.00 |
SMSTORE3 | 06-AUG-07:03 | 0.00 | 0.00 | 0.00 | -14964.17 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 61.72 | 0.00 | 0.00 | 14916.11 | 0.00 | -0.00 | 0.00 | -88.47 | 0.00 |
SMSTORE4 | 07-AUG-06:03 | 0.00 | 0.00 | 0.00 | -13854.26 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 13792.54 | 0.00 | -1.17 | 0.00 | -11.43 | 0.00 |
LGSTORE2 | 07-AUG-07:03 | 0.00 | 0.00 | 0.00 | -23341.31 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 114.23 | 0.00 | 0.00 | 23217.43 | 0.00 | -0.00 | 0.00 | -138.98 | 0.00 |
SMSTORE5 | 07-AUG-07:03 | 0.00 | 0.00 | 0.00 | -12169.34 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 57.36 | 0.00 | 0.00 | 12112.41 | 0.00 | -0.00 | 0.00 | -74.76 | 0.00 |
SMSTORE6 | 07-AUG-07:03 | 0.00 | 0.00 | 0.00 | -12060.53 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 57.83 | 0.00 | 0.00 | 12002.39 | 0.00 | -0.00 | 0.00 | -74.01 | 0.00 |
SMSTORE7 | 07-AUG-07:03 | 0.00 | 0.00 | 0.00 | -11808.60 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 59.14 | 0.00 | 0.00 | 11746.26 | 0.00 | -0.00 | 0.00 | -71.12 | 0.00 |
SMSTORE8 | 17-JUL-07:02 | 0.00 | 0.00 | 0.00 | -9882.88 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 118.04 | 0.00 | 0.00 | 9714.53 | 0.00 | -0.00 | 0.00 | -24.01 | 0.00 |
Total Facility | 07-AUG-07:03 | 0.00 | 0.00 | 0.00 | -107298.50 | 0.00 | 0.00 | 571.29 | 450.00 | 1452.23 | 719.97 | 0.00 | 0.00 | 104975.76 | 0.00 | 0.00 | 0.00 | -870.75 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 07-FEB-08:12 | 0.00 | 0.00 | 55021.29 | 0.00 | 0.00 | 0.00 | 231.22 | 180.11 | 74.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -185.36 | 0.00 | -2655.34 | -52666.55 |
SMSTORE1 | 07-MAR-08:61 | 0.00 | 0.00 | 28792.75 | 0.00 | 0.00 | 0.00 | 133.06 | 37.50 | 37.31 | 59.18 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -814.68 | -28245.12 |
SMSTORE2 | 05-MAR-08:61 | 0.00 | 0.00 | 31511.02 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 56.63 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -737.87 | -30904.59 |
SMSTORE3 | 05-MAR-08:61 | 0.00 | 0.00 | 31474.78 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 59.34 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -732.36 | -30876.57 |
SMSTORE4 | 05-MAR-08:61 | 0.00 | 0.00 | 31444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 62.10 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -726.19 | -30855.64 |
LGSTORE2 | 06-FEB-08:12 | 0.00 | 0.00 | 53349.88 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -773.88 | 0.00 | -2079.98 | -50644.66 |
SMSTORE5 | 06-FEB-08:12 | 0.00 | 0.00 | 28011.39 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -388.46 | 0.00 | -1128.44 | -26568.81 |
SMSTORE6 | 06-FEB-08:12 | 0.00 | 0.00 | 27843.26 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -388.19 | 0.00 | -1127.87 | -26401.52 |
SMSTORE7 | 06-FEB-08:12 | 0.00 | 0.00 | 27558.57 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -386.34 | 0.00 | -1121.72 | -26124.82 |
SMSTORE8 | 06-FEB-08:12 | 0.00 | 0.00 | 28970.76 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -378.44 | 0.00 | -1541.28 | -27125.37 |
Total Facility | 06-FEB-08:61 | 0.00 | 0.00 | 269084.07 | 0.00 | 0.00 | 0.00 | 774.53 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4540.94 | 0.00 | -12726.70 | -254493.19 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.6328 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.6328 | 0.2520 | 1.0000 | Not calculated | 0.4115 | 0.2520 | ||
PSZ-AC_2:2 | 0.8788 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8894 | 0.2313 | 1.0000 | Not calculated | 0.2057 | 0.2313 | ||
PSZ-AC_3:3 | 1.0046 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0046 | 0.2048 | 1.0000 | Not calculated | 0.2057 | 0.2048 | ||
PSZ-AC_4:4 | 1.0029 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0029 | 0.2051 | 1.0000 | Not calculated | 0.2057 | 0.2051 | ||
PSZ-AC_5:5 | 1.0015 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0015 | 0.2054 | 1.0000 | Not calculated | 0.2057 | 0.2054 | ||
PSZ-AC_6:6 | 1.5535 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.6044 | 0.2565 | 1.0000 | Not calculated | 0.4115 | 0.2565 | ||
PSZ-AC_7:7 | 0.8342 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8428 | 0.2441 | 1.0000 | Not calculated | 0.2057 | 0.2441 | ||
PSZ-AC_8:8 | 0.8263 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8356 | 0.2462 | 1.0000 | Not calculated | 0.2057 | 0.2462 | ||
PSZ-AC_9:9 | 0.8121 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8235 | 0.2498 | 1.0000 | Not calculated | 0.2057 | 0.2498 | ||
PSZ-AC_10:10 | 0.8719 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8719 | 0.2417 | 1.0000 | Not calculated | 0.2057 | 0.2360 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.6328 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.6328 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2520 | ||
PSZ-AC_2:2 | 0.8788 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8788 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2341 | ||
PSZ-AC_3:3 | 1.0046 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0046 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2048 | ||
PSZ-AC_4:4 | 1.0029 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0029 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2051 | ||
PSZ-AC_5:5 | 1.0015 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0015 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2054 | ||
PSZ-AC_6:6 | 1.5535 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.5535 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2649 | ||
PSZ-AC_7:7 | 0.8342 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8342 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2466 | ||
PSZ-AC_8:8 | 0.8263 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8263 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2490 | ||
PSZ-AC_9:9 | 0.8121 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8121 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2533 | ||
PSZ-AC_10:10 | 0.8719 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8719 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2360 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.003540 | 56.2505 | 0.000610 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.003540 | 56.2505 | 0.000610 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.003540 | 56.25 | 0.000610 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.003540 | 56.25 | 0.000610 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6328 | 1.6328 | 1.6328 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8788 | 0.8788 | 0.8788 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0046 | 1.0046 | 1.0046 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0029 | 1.0029 | 1.0029 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0015 | 1.0015 | 1.0015 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5535 | 1.5535 | 1.5535 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8342 | 0.8342 | 0.8342 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8263 | 0.8263 | 0.8263 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8121 | 0.8121 | 0.8121 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8719 | 0.8719 | 0.8719 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.6328 | 1.6328 | 1.6328 | 1.6328 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.8788 | 0.8894 | 0.8788 | 0.8788 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0046 | 1.0046 | 1.0046 | 1.0046 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0029 | 1.0029 | 1.0029 | 1.0029 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0015 | 1.0015 | 1.0015 | 1.0015 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.5535 | 1.6044 | 1.5535 | 1.5535 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.8342 | 0.8428 | 0.8342 | 0.8342 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.8263 | 0.8356 | 0.8263 | 0.8263 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.8121 | 0.8235 | 0.8121 | 0.8121 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.8719 | 0.8719 | 0.8719 | 0.8719 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6328 | 1.6328 | 1.6328 | No | 0.4115 | 0.2917 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8788 | 0.8788 | 0.8788 | No | 0.2057 | 0.3074 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0046 | 1.0046 | 1.0046 | No | 0.2057 | 0.3035 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0029 | 1.0029 | 1.0029 | No | 0.2057 | 0.3013 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0015 | 1.0015 | 1.0015 | No | 0.2057 | 0.2978 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5535 | 1.5535 | 1.5535 | No | 0.4115 | 0.3111 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8342 | 0.8342 | 0.8342 | No | 0.2057 | 0.2904 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8263 | 0.8263 | 0.8263 | No | 0.2057 | 0.2907 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8121 | 0.8121 | 0.8121 | No | 0.2057 | 0.2863 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8719 | 0.8719 | 0.8719 | No | 0.2057 | 0.2360 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.6328 | 1.6328 | 1.6328 | 1.6328 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.8788 | 0.8788 | 0.8788 | 0.8788 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0046 | 1.0046 | 1.0046 | 1.0046 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0029 | 1.0029 | 1.0029 | 1.0029 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0015 | 1.0015 | 1.0015 | 1.0015 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.5535 | 1.5535 | 1.5535 | 1.5535 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.8342 | 0.8342 | 0.8342 | 0.8342 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.8263 | 0.8263 | 0.8263 | 0.8263 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.8121 | 0.8121 | 0.8121 | 0.8121 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.8719 | 0.8719 | 0.8719 | 0.8719 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 6.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 6.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 506.12 | 201719.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 48.04 | 29572.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 277.79 | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 41.04 | 3786.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 112.40 | 8887.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 65.12 | 13728.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 672.55 |
Natural Gas | 0.00 | 506.12 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1178.66 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 57.54 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 132.89 |
Space Heating | 0.00 |
Space Cooling | 22.98 |
Fans (All) | 53.77 |
Service Water Heating | 31.15 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 321.74 |
Subtotal | 321.74 |
Natural Gas [MJ/m2] | |
Space Heating | 242.12 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 242.12 |
Subtotal | 242.12 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 23.57 |
Space Heating | 42.94 |
Space Cooling | 4.08 |
Fans (All) | 9.54 |
Service Water Heating | 5.52 |
Receptacle Equipment | 10.87 |
Miscellaneous | 3.48 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3140. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3200. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4323. | 8760. |
LTG_SCH_BASE_LPD1 | 4243. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3479. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
Min | 8756.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3.33 | 0.00 | 0.00 | 0.00 |
Average | 8758.07 | 1.93 | 0.00 | 0.00 | 0.00 |
Sum | 87580.67 | 19.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25473.17 | 1.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25473.17 | 1.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25473.67 | 1.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93206.00 | 5.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45907.00 | 5.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45907.00 | 5.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45908.00 | 4.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45909.50 | 2.50 | 0.00 | 0.00 | 0.00 |
Min | 25473.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93206.00 | 5.00 | 0.00 | 0.00 | 0.00 |
Average | 48607.55 | 2.65 | 0.00 | 0.00 | 0.00 |
Sum | 486075.50 | 26.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8216.83 | 543.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8512.00 | 248.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8069.67 | 690.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8064.83 | 695.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8071.50 | 688.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8077.17 | 682.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8037.67 | 722.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8038.00 | 722.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8041.33 | 718.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8106.83 | 653.17 | 0.00 | 0.00 | 0.00 |
Min | 8037.67 | 248.00 | 0.00 | 0.00 | 0.00 |
Max | 8512.00 | 722.33 | 0.00 | 0.00 | 0.00 |
Average | 8123.58 | 636.42 | 0.00 | 0.00 | 0.00 |
Sum | 81235.83 | 6364.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 85679.50 | 3361.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 42669.17 | 1107.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 24414.17 | 1060.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 24406.17 | 1068.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 24369.00 | 1106.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 88647.50 | 4563.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 43330.83 | 2581.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 43303.83 | 2608.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 43174.83 | 2737.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 43329.67 | 2582.33 | 0.00 | 0.00 | 0.00 |
Min | 24369.00 | 1060.83 | 0.00 | 0.00 | 0.00 |
Max | 88647.50 | 4563.50 | 0.00 | 0.00 | 0.00 |
Average | 46332.47 | 2277.73 | 0.00 | 0.00 | 0.00 |
Sum | 463324.67 | 22777.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:16
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200230E+09 | 7377.88 | 01-JAN-18:43 | -0.5 | -1.0 | 0.106519E+10 | 1275.40 | 29-JAN-18:00 | -6.7 | -7.2 |
February | 0.184013E+09 | 7470.65 | 28-FEB-19:53 | -2.2 | -3.7 | 0.961500E+09 | 1275.40 | 26-FEB-18:00 | -2.2 | -3.7 |
March | 0.103941E+10 | 6898.49 | 04-MAR-00:12 | -9.4 | -10.8 | 0.108200E+10 | 1404.91 | 15-MAR-18:00 | 21.10 | 14.77 |
April | 0.199633E+10 | 4253.11 | 09-APR-18:00 | 10.00 | 8.80 | 0.107104E+10 | 1657.72 | 08-APR-12:00 | 10.00 | 8.80 |
May | 0.379821E+10 | 5191.37 | 31-MAY-17:10 | 21.10 | 14.05 | 0.128710E+10 | 1685.90 | 14-MAY-16:40 | 21.10 | 14.05 |
June | 0.737323E+10 | 11765.41 | 18-JUN-07:03 | 23.48 | 21.14 | 0.134830E+10 | 1685.98 | 18-JUN-12:39 | 26.10 | 20.49 |
July | 0.104473E+11 | 20585.49 | 19-JUL-07:03 | 22.20 | 20.31 | 0.141264E+10 | 1686.02 | 21-JUL-12:00 | 30.60 | 22.06 |
August | 0.100813E+11 | 22430.02 | 07-AUG-07:03 | 21.20 | 18.87 | 0.139357E+10 | 1685.98 | 26-AUG-12:50 | 25.37 | 21.15 |
September | 0.694889E+10 | 22131.46 | 17-SEP-07:03 | 22.12 | 19.56 | 0.135201E+10 | 1685.98 | 15-SEP-12:50 | 22.12 | 19.56 |
October | 0.364974E+10 | 5518.72 | 23-OCT-17:10 | 4.40 | 2.51 | 0.118705E+10 | 1685.90 | 22-OCT-12:00 | 4.40 | 2.51 |
November | 0.162866E+10 | 4949.95 | 24-NOV-00:03 | -1.8 | -2.5 | 0.105047E+10 | 1623.20 | 05-NOV-12:00 | -1.8 | -2.5 |
December | 0.326840E+09 | 6863.58 | 29-DEC-00:12 | -9.4 | -10.3 | 0.107060E+10 | 1275.40 | 10-DEC-18:00 | -9.4 | -10.3 |
Annual Sum or Average | 0.476742E+11 | 0.142815E+11 | ||||||||
Minimum of Months | 0.184013E+09 | 4253.11 | -9.4 | -10.8 | 0.961500E+09 | 1275.40 | -9.4 | -10.3 | ||
Maximum of Months | 0.104473E+11 | 22430.02 | 23.48 | 21.14 | 0.141264E+10 | 1686.02 | 30.60 | 22.06 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 84176890.53 | 4718.01 | 30-JAN-20:03 | -12.1 | -13.2 | 0.537487E+09 | 708.78 | 16-JAN-18:00 | -12.1 | -13.2 |
February | 79175719.33 | 4425.98 | 25-FEB-18:03 | -6.2 | -7.4 | 0.484236E+09 | 692.15 | 19-FEB-18:00 | -6.2 | -7.4 |
March | 0.564034E+09 | 11246.83 | 15-MAR-20:01 | 20.73 | 14.37 | 0.555565E+09 | 811.85 | 12-MAR-17:00 | 20.73 | 14.37 |
April | 0.985203E+09 | 2489.15 | 10-APR-17:10 | 2.80 | 2.25 | 0.567100E+09 | 842.90 | 09-APR-17:00 | 2.80 | 2.25 |
May | 0.223876E+10 | 12335.85 | 23-MAY-20:01 | 21.02 | 13.04 | 0.672636E+09 | 842.92 | 13-MAY-12:00 | 21.02 | 13.04 |
June | 0.446502E+10 | 14490.31 | 03-JUN-18:08 | 17.80 | 10.05 | 0.674640E+09 | 842.96 | 11-JUN-12:00 | 25.60 | 18.16 |
July | 0.602691E+10 | 12663.86 | 06-JUL-20:10 | 18.90 | 12.35 | 0.705417E+09 | 842.99 | 21-JUL-12:00 | 30.60 | 22.06 |
August | 0.575796E+10 | 13414.48 | 06-AUG-07:03 | 20.28 | 15.40 | 0.695635E+09 | 842.96 | 26-AUG-12:00 | 25.00 | 21.09 |
September | 0.410069E+10 | 12751.60 | 03-SEP-17:50 | 17.48 | 11.84 | 0.679398E+09 | 842.97 | 15-SEP-12:00 | 25.00 | 20.79 |
October | 0.185821E+10 | 11342.70 | 22-OCT-17:09 | 20.32 | 14.31 | 0.625754E+09 | 842.93 | 22-OCT-12:00 | 20.32 | 14.31 |
November | 0.797096E+09 | 2512.06 | 06-NOV-18:10 | 5.60 | 2.97 | 0.547778E+09 | 842.90 | 05-NOV-17:00 | 5.60 | 2.97 |
December | 0.147007E+09 | 5039.16 | 11-DEC-20:42 | -14.2 | -14.2 | 0.542841E+09 | 707.80 | 24-DEC-18:40 | 4.63 | 2.63 |
Annual Sum or Average | 0.271042E+11 | 0.728849E+10 | ||||||||
Minimum of Months | 79175719.33 | 2489.15 | -14.2 | -14.2 | 0.484236E+09 | 692.15 | -12.1 | -13.2 | ||
Maximum of Months | 0.602691E+10 | 14490.31 | 21.02 | 15.40 | 0.705417E+09 | 842.99 | 30.60 | 22.06 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21820028.76 | 4426.38 | 05-JAN-18:23 | -6.7 | -8.3 | 0.317181E+09 | 637.68 | 14-JAN-13:50 | 3.98 | 3.16 |
February | 21082502.82 | 3764.55 | 27-FEB-18:13 | -3.2 | -4.8 | 0.288103E+09 | 637.68 | 04-FEB-13:09 | -3.2 | -4.8 |
March | 0.372765E+09 | 2513.08 | 17-MAR-17:20 | 6.10 | 3.82 | 0.335810E+09 | 702.45 | 15-MAR-17:40 | 6.10 | 3.82 |
April | 0.734012E+09 | 2159.91 | 10-APR-17:10 | 2.80 | 2.25 | 0.327063E+09 | 842.89 | 08-APR-12:00 | 2.80 | 2.25 |
May | 0.155947E+10 | 3062.23 | 27-MAY-13:00 | 21.70 | 12.35 | 0.399721E+09 | 842.91 | 13-MAY-12:00 | 21.70 | 12.35 |
June | 0.319100E+10 | 9302.24 | 18-JUN-07:03 | 23.48 | 21.14 | 0.415198E+09 | 842.93 | 24-JUN-12:30 | 21.95 | 14.11 |
July | 0.437770E+10 | 13718.00 | 15-JUL-06:03 | 23.72 | 18.90 | 0.419733E+09 | 842.96 | 29-JUL-12:30 | 25.85 | 21.40 |
August | 0.429873E+10 | 14781.41 | 06-AUG-07:03 | 20.28 | 15.40 | 0.431210E+09 | 842.97 | 26-AUG-12:50 | 25.37 | 21.15 |
September | 0.284755E+10 | 12941.14 | 17-SEP-07:03 | 22.12 | 19.56 | 0.407690E+09 | 842.97 | 16-SEP-12:09 | 22.12 | 19.56 |
October | 0.133667E+10 | 2757.17 | 23-OCT-17:20 | 4.40 | 2.51 | 0.358774E+09 | 842.71 | 21-OCT-12:00 | 4.40 | 2.51 |
November | 0.545602E+09 | 2288.95 | 06-NOV-18:10 | 5.60 | 2.97 | 0.313151E+09 | 720.28 | 04-NOV-12:00 | 5.60 | 2.97 |
December | 52469167.87 | 1951.68 | 15-DEC-11:45 | 2.20 | 1.09 | 0.316812E+09 | 637.68 | 02-DEC-13:39 | 2.20 | 1.09 |
Annual Sum or Average | 0.193589E+11 | 0.433045E+10 | ||||||||
Minimum of Months | 21082502.82 | 1951.68 | -6.7 | -8.3 | 0.288103E+09 | 637.68 | -3.2 | -4.8 | ||
Maximum of Months | 0.437770E+10 | 14781.41 | 23.72 | 21.14 | 0.431210E+09 | 842.97 | 25.85 | 21.40 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16023450.48 | 3514.28 | 10-JAN-18:03 | -1.7 | -4.1 | 0.317182E+09 | 637.68 | 07-JAN-13:20 | -1.7 | -4.1 |
February | 15746864.04 | 2436.68 | 17-FEB-19:45 | 0.10 | -0.4 | 0.288103E+09 | 637.68 | 11-FEB-13:09 | 0.10 | -0.4 |
March | 0.341045E+09 | 2503.73 | 03-MAR-11:45 | -2.3 | -4.6 | 0.335398E+09 | 702.45 | 15-MAR-17:40 | 24.27 | 15.74 |
April | 0.663231E+09 | 2121.28 | 11-APR-18:00 | 7.20 | 4.42 | 0.325389E+09 | 842.87 | 08-APR-12:00 | 7.20 | 4.42 |
May | 0.147131E+10 | 2979.56 | 27-MAY-13:00 | 21.70 | 12.35 | 0.396987E+09 | 842.91 | 13-MAY-12:00 | 21.70 | 12.35 |
June | 0.316140E+10 | 9103.74 | 18-JUN-07:03 | 23.48 | 21.14 | 0.415147E+09 | 842.92 | 24-JUN-12:30 | 21.95 | 14.11 |
July | 0.438535E+10 | 13668.54 | 15-JUL-06:03 | 23.72 | 18.90 | 0.419731E+09 | 842.96 | 29-JUL-12:30 | 25.85 | 21.40 |
August | 0.430311E+10 | 14967.36 | 06-AUG-07:03 | 20.28 | 15.40 | 0.431204E+09 | 842.97 | 26-AUG-12:00 | 25.00 | 21.09 |
September | 0.280946E+10 | 12874.85 | 17-SEP-07:03 | 22.12 | 19.56 | 0.407456E+09 | 842.96 | 16-SEP-12:09 | 22.12 | 19.56 |
October | 0.123068E+10 | 2723.68 | 23-OCT-17:20 | 4.40 | 2.51 | 0.356477E+09 | 840.32 | 21-OCT-12:00 | 4.40 | 2.51 |
November | 0.469327E+09 | 2154.40 | 03-NOV-17:40 | 6.83 | 3.84 | 0.312391E+09 | 714.73 | 04-NOV-12:00 | 16.70 | 13.41 |
December | 43363593.54 | 2243.05 | 04-DEC-11:45 | -0.2 | -2.9 | 0.316799E+09 | 637.68 | 02-DEC-13:30 | -0.2 | -2.9 |
Annual Sum or Average | 0.189100E+11 | 0.432226E+10 | ||||||||
Minimum of Months | 15746864.04 | 2121.28 | -2.3 | -4.6 | 0.288103E+09 | 637.68 | -1.7 | -4.1 | ||
Maximum of Months | 0.438535E+10 | 14967.36 | 23.72 | 21.14 | 0.431204E+09 | 842.97 | 25.85 | 21.40 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9959771.62 | 3889.78 | 06-JAN-18:43 | -3.9 | -5.7 | 0.317182E+09 | 637.68 | 14-JAN-13:30 | 4.15 | 3.16 |
February | 9600552.19 | 3218.50 | 14-FEB-18:13 | 0.00 | -3.4 | 0.288103E+09 | 637.68 | 04-FEB-13:50 | 0.00 | -3.4 |
March | 0.276671E+09 | 2424.05 | 17-MAR-17:20 | 6.10 | 3.82 | 0.334701E+09 | 702.44 | 15-MAR-17:10 | 6.10 | 3.82 |
April | 0.551757E+09 | 2028.72 | 11-APR-17:30 | 7.75 | 4.74 | 0.322715E+09 | 842.16 | 08-APR-12:00 | 7.75 | 4.74 |
May | 0.129870E+10 | 2724.62 | 27-MAY-13:00 | 21.70 | 12.35 | 0.391790E+09 | 842.90 | 13-MAY-12:00 | 21.70 | 12.35 |
June | 0.297047E+10 | 7673.82 | 18-JUN-07:03 | 23.48 | 21.14 | 0.414791E+09 | 842.93 | 24-JUN-12:39 | 22.23 | 14.23 |
July | 0.421505E+10 | 12796.12 | 19-JUL-06:03 | 22.20 | 19.71 | 0.419695E+09 | 842.97 | 29-JUL-12:30 | 25.85 | 21.40 |
August | 0.412647E+10 | 13857.64 | 07-AUG-06:03 | 20.68 | 18.73 | 0.431146E+09 | 842.97 | 26-AUG-12:39 | 25.73 | 21.20 |
September | 0.263947E+10 | 12785.74 | 17-SEP-07:03 | 22.12 | 19.56 | 0.406621E+09 | 842.97 | 16-SEP-12:09 | 22.12 | 19.56 |
October | 0.106549E+10 | 2675.96 | 23-OCT-17:20 | 4.40 | 2.51 | 0.352607E+09 | 828.18 | 21-OCT-12:00 | 4.40 | 2.51 |
November | 0.364328E+09 | 2006.43 | 03-NOV-17:20 | 7.57 | 4.23 | 0.311360E+09 | 703.87 | 04-NOV-12:00 | 16.70 | 13.41 |
December | 27138582.11 | 2280.39 | 17-DEC-11:15 | 1.30 | -0.4 | 0.316799E+09 | 637.68 | 02-DEC-13:00 | 1.30 | -0.4 |
Annual Sum or Average | 0.175551E+11 | 0.430751E+10 | ||||||||
Minimum of Months | 9600552.19 | 2006.43 | -3.9 | -5.7 | 0.288103E+09 | 637.68 | 0.00 | -3.4 | ||
Maximum of Months | 0.421505E+10 | 13857.64 | 23.48 | 21.14 | 0.431146E+09 | 842.97 | 25.85 | 21.40 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 | -1.6 | 0.108442E+10 | 1700.53 | 14-JAN-15:39 | 3.50 | 2.95 |
February | 318065.50 | 293.64 | 18-FEB-12:00 | 1.10 | 0.02 | 0.987309E+09 | 1700.53 | 18-FEB-15:30 | 2.50 | 0.26 |
March | 0.378384E+09 | 6398.72 | 23-MAR-10:43 | 0.00 | -2.3 | 0.114647E+10 | 1994.92 | 14-MAR-16:10 | 0.00 | -2.3 |
April | 0.957602E+09 | 4674.74 | 11-APR-12:35 | 7.43 | 4.96 | 0.109577E+10 | 2247.79 | 08-APR-14:20 | 7.43 | 4.96 |
May | 0.243040E+10 | 4741.22 | 27-MAY-14:30 | 21.70 | 12.26 | 0.130704E+10 | 2247.86 | 13-MAY-14:39 | 21.70 | 12.26 |
June | 0.507104E+10 | 15361.25 | 18-JUN-08:63 | 24.50 | 21.64 | 0.141988E+10 | 2247.88 | 10-JUN-14:20 | 24.50 | 21.64 |
July | 0.730845E+10 | 20928.83 | 20-JUL-07:02 | 25.18 | 22.23 | 0.143731E+10 | 2247.94 | 08-JUL-14:09 | 25.18 | 22.23 |
August | 0.714449E+10 | 23347.30 | 07-AUG-07:03 | 21.20 | 18.87 | 0.147869E+10 | 2247.95 | 12-AUG-14:09 | 24.50 | 16.56 |
September | 0.450061E+10 | 18826.12 | 17-SEP-08:63 | 21.70 | 19.45 | 0.139020E+10 | 2247.93 | 16-SEP-14:00 | 21.70 | 19.45 |
October | 0.187954E+10 | 4665.22 | 14-OCT-11:00 | 6.10 | 5.81 | 0.118019E+10 | 2209.45 | 21-OCT-14:00 | 19.40 | 11.82 |
November | 0.454653E+09 | 5040.89 | 21-NOV-18:15 | 2.60 | 0.65 | 0.105726E+10 | 1983.74 | 04-NOV-14:00 | 2.60 | 0.65 |
December | 12049591.76 | 1731.99 | 16-DEC-12:00 | 4.40 | 1.70 | 0.108625E+10 | 1700.53 | 02-DEC-15:30 | 4.40 | 1.70 |
Annual Sum or Average | 0.301376E+11 | 0.146708E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -1.0 | -2.3 | 0.987309E+09 | 1700.53 | 0.00 | -2.3 | ||
Maximum of Months | 0.730845E+10 | 23347.30 | 25.18 | 22.23 | 0.147869E+10 | 2247.95 | 25.18 | 22.23 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 | -1.6 | 0.542193E+09 | 850.24 | 07-JAN-15:50 | -1.7 | -3.7 |
February | 18311.78 | 30.52 | 18-FEB-12:00 | 1.10 | 0.02 | 0.493640E+09 | 850.24 | 04-FEB-15:00 | 1.10 | 0.02 |
March | 0.143287E+09 | 2470.16 | 23-MAR-10:55 | 0.00 | -2.4 | 0.575440E+09 | 997.47 | 15-MAR-16:00 | 0.00 | -2.4 |
April | 0.296216E+09 | 1556.66 | 11-APR-16:55 | 8.30 | 5.05 | 0.555689E+09 | 1123.86 | 08-APR-14:00 | 8.30 | 5.05 |
May | 0.832930E+09 | 2413.28 | 27-MAY-14:30 | 21.70 | 12.26 | 0.671550E+09 | 1123.89 | 13-MAY-14:00 | 21.70 | 12.26 |
June | 0.250479E+10 | 7506.15 | 18-JUN-08:63 | 24.50 | 21.64 | 0.711919E+09 | 1123.89 | 10-JUN-14:20 | 24.50 | 21.64 |
July | 0.373716E+10 | 10860.28 | 19-JUL-07:03 | 22.20 | 20.31 | 0.718768E+09 | 1123.94 | 01-JUL-14:09 | 22.20 | 20.31 |
August | 0.363899E+10 | 12172.63 | 07-AUG-07:03 | 21.20 | 18.87 | 0.739700E+09 | 1123.94 | 26-AUG-14:30 | 26.10 | 21.71 |
September | 0.217182E+10 | 9189.84 | 17-SEP-08:63 | 21.70 | 19.45 | 0.699019E+09 | 1123.93 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.673023E+09 | 2068.24 | 14-OCT-11:00 | 6.10 | 5.81 | 0.602274E+09 | 1123.87 | 21-OCT-14:20 | 19.40 | 12.01 |
November | 0.161058E+09 | 1947.61 | 29-NOV-18:55 | 2.20 | -0.4 | 0.531584E+09 | 1026.15 | 04-NOV-14:00 | 2.20 | -0.4 |
December | 4396143.15 | 813.33 | 16-DEC-12:00 | 4.40 | 1.70 | 0.543129E+09 | 850.24 | 02-DEC-15:09 | 4.40 | 1.70 |
Annual Sum or Average | 0.141637E+11 | 0.738491E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -1.0 | -2.4 | 0.493640E+09 | 850.24 | -1.7 | -3.7 | ||
Maximum of Months | 0.373716E+10 | 12172.63 | 24.50 | 21.64 | 0.739700E+09 | 1123.94 | 26.10 | 21.71 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 | -1.6 | 0.542193E+09 | 850.24 | 07-JAN-15:09 | -1.7 | -3.4 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 | -4.7 | 0.493640E+09 | 850.24 | 11-FEB-15:20 | -1.1 | -3.5 |
March | 0.135594E+09 | 1825.37 | 15-MAR-14:10 | 26.02 | 16.09 | 0.575166E+09 | 997.47 | 15-MAR-16:00 | 25.00 | 15.95 |
April | 0.277893E+09 | 1531.07 | 11-APR-16:45 | 8.48 | 5.18 | 0.554669E+09 | 1123.86 | 08-APR-14:00 | 8.48 | 5.18 |
May | 0.789273E+09 | 2318.93 | 27-MAY-14:40 | 21.70 | 12.23 | 0.668813E+09 | 1123.89 | 13-MAY-14:00 | 21.70 | 12.23 |
June | 0.243011E+10 | 6853.30 | 18-JUN-08:63 | 24.50 | 21.64 | 0.711704E+09 | 1123.89 | 10-JUN-14:20 | 24.50 | 21.64 |
July | 0.367574E+10 | 10756.21 | 19-JUL-07:03 | 22.20 | 20.31 | 0.718758E+09 | 1123.94 | 01-JUL-14:09 | 22.20 | 20.31 |
August | 0.358092E+10 | 12063.78 | 07-AUG-07:03 | 21.20 | 18.87 | 0.739681E+09 | 1123.94 | 26-AUG-14:30 | 26.10 | 21.71 |
September | 0.212311E+10 | 8893.69 | 17-SEP-08:63 | 21.70 | 19.45 | 0.698668E+09 | 1123.93 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.644313E+09 | 2301.00 | 23-OCT-16:55 | 4.40 | 2.51 | 0.600941E+09 | 1123.87 | 21-OCT-14:00 | 4.40 | 2.51 |
November | 0.146457E+09 | 1957.11 | 29-NOV-18:05 | 2.20 | 0.03 | 0.531268E+09 | 1021.98 | 04-NOV-14:00 | 2.20 | 0.03 |
December | 4660224.52 | 2422.62 | 02-DEC-11:45 | 2.30 | 1.25 | 0.543122E+09 | 850.24 | 09-DEC-15:30 | -6.2 | -6.2 |
Annual Sum or Average | 0.138081E+11 | 0.737862E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 0.493640E+09 | 850.24 | -6.2 | -6.2 | ||
Maximum of Months | 0.367574E+10 | 12063.78 | 26.02 | 21.64 | 0.739681E+09 | 1123.94 | 26.10 | 21.71 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 | -1.6 | 0.542193E+09 | 850.24 | 07-JAN-15:20 | -1.7 | -3.5 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 | -4.7 | 0.493640E+09 | 850.24 | 25-FEB-15:39 | -5.8 | -7.0 |
March | 0.101174E+09 | 1778.93 | 21-MAR-17:35 | 3.50 | 0.63 | 0.573907E+09 | 997.46 | 15-MAR-16:19 | 3.50 | 0.63 |
April | 0.204385E+09 | 1477.50 | 05-APR-18:15 | 4.63 | 3.00 | 0.550358E+09 | 1123.87 | 08-APR-14:39 | 19.80 | 13.32 |
May | 0.620236E+09 | 1993.81 | 27-MAY-14:40 | 21.70 | 12.23 | 0.656119E+09 | 1123.88 | 13-MAY-14:00 | 21.70 | 12.23 |
June | 0.218586E+10 | 4875.86 | 27-JUN-13:00 | 30.60 | 23.75 | 0.710476E+09 | 1123.88 | 10-JUN-14:20 | 30.60 | 23.75 |
July | 0.351217E+10 | 10507.73 | 20-JUL-07:02 | 25.18 | 22.23 | 0.718730E+09 | 1123.94 | 01-JUL-14:39 | 25.18 | 22.23 |
August | 0.342503E+10 | 11811.77 | 07-AUG-07:03 | 21.20 | 18.87 | 0.739578E+09 | 1123.94 | 26-AUG-14:30 | 26.10 | 21.71 |
September | 0.195356E+10 | 7781.05 | 17-SEP-08:63 | 21.70 | 19.45 | 0.696560E+09 | 1123.93 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.524329E+09 | 2221.90 | 14-OCT-15:35 | 5.20 | 4.70 | 0.594358E+09 | 1122.21 | 21-OCT-14:00 | 19.40 | 11.82 |
November | 99382640.35 | 2039.89 | 28-NOV-18:05 | 1.70 | -0.1 | 0.529852E+09 | 1004.05 | 04-NOV-14:00 | 1.70 | -0.1 |
December | 2937177.45 | 1205.74 | 01-DEC-18:50 | 6.70 | 4.71 | 0.543103E+09 | 850.24 | 02-DEC-15:20 | 2.97 | 1.38 |
Annual Sum or Average | 0.126291E+11 | 0.734887E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 0.493640E+09 | 850.24 | -5.8 | -7.0 | ||
Maximum of Months | 0.351217E+10 | 11811.77 | 30.60 | 23.75 | 0.739578E+09 | 1123.94 | 30.60 | 23.75 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 | -1.6 | 0.542193E+09 | 850.24 | 07-JAN-15:20 | -1.7 | -3.5 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 | -4.7 | 0.493640E+09 | 850.24 | 11-FEB-15:30 | -1.1 | -3.4 |
March | 58335975.70 | 1881.70 | 17-MAR-18:15 | 5.53 | 3.28 | 0.570503E+09 | 997.43 | 15-MAR-16:00 | 5.53 | 3.28 |
April | 0.153391E+09 | 1376.72 | 22-APR-11:00 | 11.70 | 4.96 | 0.538826E+09 | 1052.40 | 08-APR-14:09 | 11.70 | 4.96 |
May | 0.591750E+09 | 1442.21 | 27-MAY-14:10 | 21.70 | 12.32 | 0.616479E+09 | 1123.87 | 13-MAY-14:00 | 21.70 | 12.32 |
June | 0.198405E+10 | 5054.23 | 27-JUN-13:00 | 30.60 | 23.75 | 0.700700E+09 | 1123.90 | 24-JUN-14:09 | 30.60 | 23.75 |
July | 0.344396E+10 | 9887.06 | 17-JUL-07:02 | 23.40 | 20.98 | 0.718516E+09 | 1123.96 | 29-JUL-14:00 | 25.60 | 21.33 |
August | 0.340432E+10 | 8518.83 | 14-AUG-07:03 | 23.48 | 21.75 | 0.737897E+09 | 1123.95 | 26-AUG-14:00 | 27.20 | 21.83 |
September | 0.188906E+10 | 5238.56 | 17-SEP-08:63 | 21.70 | 19.45 | 0.685712E+09 | 1123.94 | 16-SEP-14:00 | 21.70 | 19.45 |
October | 0.523005E+09 | 2149.87 | 16-OCT-17:45 | 4.68 | 2.35 | 0.574485E+09 | 1066.67 | 21-OCT-14:00 | 19.40 | 11.82 |
November | 54737991.28 | 2006.93 | 06-NOV-18:15 | 5.60 | 2.97 | 0.525460E+09 | 937.08 | 04-NOV-14:00 | 5.60 | 2.97 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.95 | 3.07 | 0.543112E+09 | 850.24 | 02-DEC-15:39 | 3.13 | 1.53 |
Annual Sum or Average | 0.121026E+11 | 0.724752E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 0.493640E+09 | 850.24 | -1.7 | -3.5 | ||
Maximum of Months | 0.344396E+10 | 9887.06 | 30.60 | 23.75 | 0.737897E+09 | 1123.96 | 30.60 | 23.75 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.921860E+10 | 54798.29 | 10-JAN-08:12 | -9.8 |
February | 0.891189E+10 | 55021.24 | 07-FEB-08:12 | -15.6 |
March | 0.473309E+10 | 54792.56 | 07-MAR-08:61 | -10.8 |
April | 0.159822E+10 | 54758.88 | 17-APR-07:01 | -2.9 |
May | 0.132700E+09 | 54724.57 | 08-MAY-07:01 | 5.87 |
June | 39639419.27 | 1024.94 | 18-JUN-07:07 | 23.48 |
July | 18685727.75 | 1204.66 | 19-JUL-07:05 | 22.20 |
August | 19185448.83 | 1228.45 | 07-AUG-07:05 | 21.20 |
September | 43771827.86 | 1229.24 | 17-SEP-07:05 | 22.12 |
October | 0.318069E+09 | 54757.35 | 17-OCT-07:01 | -2.4 |
November | 0.187671E+10 | 54762.32 | 22-NOV-08:61 | 1.10 |
December | 0.801442E+10 | 54817.24 | 26-DEC-08:12 | -12.8 |
Annual Sum or Average | 0.349250E+11 | |||
Minimum of Months | 18685727.75 | 1024.94 | -15.6 | |
Maximum of Months | 0.921860E+10 | 55021.24 | 23.48 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334297E+10 | 28781.76 | 10-JAN-08:61 | -9.9 |
February | 0.325018E+10 | 28780.95 | 10-FEB-08:61 | -9.7 |
March | 0.152528E+10 | 28792.76 | 07-MAR-08:61 | -10.8 |
April | 0.358141E+09 | 28767.79 | 17-APR-07:01 | -2.9 |
May | 36384704.14 | 3132.51 | 01-MAY-07:01 | 6.05 |
June | 12838123.38 | 691.53 | 18-JUN-07:07 | 23.48 |
July | 11231049.62 | 731.39 | 16-JUL-07:05 | 23.48 |
August | 11111151.07 | 745.58 | 06-AUG-07:05 | 20.28 |
September | 13685230.90 | 716.04 | 17-SEP-07:05 | 22.12 |
October | 59258858.92 | 28768.89 | 17-OCT-07:01 | -2.4 |
November | 0.515796E+09 | 28769.28 | 22-NOV-08:61 | 1.10 |
December | 0.294630E+10 | 28787.36 | 11-DEC-08:61 | -14.8 |
Annual Sum or Average | 0.120832E+11 | |||
Minimum of Months | 11111151.07 | 691.53 | -14.8 | |
Maximum of Months | 0.334297E+10 | 28792.76 | 23.48 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.387878E+10 | 31499.38 | 29-JAN-08:61 | -8.1 |
February | 0.369133E+10 | 31509.52 | 05-FEB-08:61 | -13.0 |
March | 0.180887E+10 | 31511.04 | 05-MAR-08:61 | -9.7 |
April | 0.503999E+09 | 31472.28 | 16-APR-07:01 | -3.7 |
May | 45169714.68 | 9990.31 | 01-MAY-06:03 | 2.35 |
June | 19569350.01 | 847.60 | 17-JUN-17:03 | 28.80 |
July | 29644331.20 | 973.91 | 16-JUL-16:03 | 30.03 |
August | 24430247.61 | 888.85 | 06-AUG-07:05 | 20.28 |
September | 14825628.77 | 829.68 | 17-SEP-07:05 | 22.12 |
October | 0.107659E+09 | 29536.25 | 30-OCT-06:02 | -0.4 |
November | 0.759722E+09 | 31220.15 | 24-NOV-07:01 | -3.2 |
December | 0.341156E+10 | 31509.96 | 10-DEC-08:61 | -13.0 |
Annual Sum or Average | 0.142956E+11 | |||
Minimum of Months | 14825628.77 | 829.68 | -13.0 | |
Maximum of Months | 0.387878E+10 | 31511.04 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408484E+10 | 31463.21 | 29-JAN-08:61 | -8.1 |
February | 0.386877E+10 | 31473.26 | 05-FEB-08:61 | -13.0 |
March | 0.194564E+10 | 31474.79 | 05-MAR-08:61 | -9.7 |
April | 0.577573E+09 | 31436.39 | 16-APR-07:01 | -3.7 |
May | 51738401.14 | 13949.83 | 01-MAY-06:03 | 2.35 |
June | 20679955.31 | 849.23 | 17-JUN-17:03 | 28.80 |
July | 29591051.80 | 974.20 | 16-JUL-16:03 | 30.03 |
August | 24414862.29 | 893.69 | 06-AUG-07:05 | 20.28 |
September | 15802209.56 | 826.25 | 17-SEP-07:05 | 22.12 |
October | 0.138547E+09 | 30790.24 | 30-OCT-06:02 | -0.4 |
November | 0.862906E+09 | 31185.09 | 24-NOV-07:01 | -3.2 |
December | 0.359820E+10 | 31473.79 | 10-DEC-08:61 | -13.0 |
Annual Sum or Average | 0.152187E+11 | |||
Minimum of Months | 15802209.56 | 826.25 | -13.0 | |
Maximum of Months | 0.408484E+10 | 31474.79 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.444305E+10 | 31433.37 | 29-JAN-08:61 | -8.1 |
February | 0.419067E+10 | 31443.37 | 05-FEB-08:61 | -13.0 |
March | 0.219495E+10 | 31444.93 | 05-MAR-08:61 | -9.7 |
April | 0.712827E+09 | 31406.51 | 16-APR-07:01 | -3.7 |
May | 64449522.28 | 17439.63 | 01-MAY-06:03 | 2.35 |
June | 24103081.82 | 858.59 | 17-JUN-17:03 | 28.80 |
July | 29880171.24 | 979.55 | 16-JUL-16:03 | 30.03 |
August | 24705565.51 | 868.14 | 13-AUG-16:03 | 29.03 |
September | 20167952.66 | 820.17 | 17-SEP-07:05 | 22.12 |
October | 0.180490E+09 | 30762.99 | 30-OCT-06:02 | -0.4 |
November | 0.103925E+10 | 31156.49 | 24-NOV-07:01 | -3.2 |
December | 0.392577E+10 | 31443.89 | 10-DEC-08:61 | -13.0 |
Annual Sum or Average | 0.168503E+11 | |||
Minimum of Months | 20167952.66 | 820.17 | -13.0 | |
Maximum of Months | 0.444305E+10 | 31444.93 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.863360E+10 | 53174.55 | 30-JAN-08:12 | -10.4 |
February | 0.808281E+10 | 53349.90 | 06-FEB-08:12 | -15.0 |
March | 0.420313E+10 | 53078.27 | 07-MAR-08:61 | -10.8 |
April | 0.142291E+10 | 53040.41 | 17-APR-07:01 | -2.9 |
May | 0.147655E+09 | 53009.74 | 08-MAY-07:01 | 5.87 |
June | 47541635.76 | 1742.67 | 17-JUN-17:03 | 28.80 |
July | 33366492.73 | 2007.51 | 16-JUL-16:03 | 30.03 |
August | 32659805.19 | 1763.14 | 13-AUG-16:03 | 29.03 |
September | 47851377.20 | 1235.75 | 17-SEP-08:07 | 21.70 |
October | 0.401375E+09 | 53038.27 | 17-OCT-07:01 | -2.4 |
November | 0.203437E+10 | 53038.73 | 22-NOV-08:61 | 1.10 |
December | 0.763328E+10 | 53266.60 | 11-DEC-08:12 | -14.6 |
Annual Sum or Average | 0.327205E+11 | |||
Minimum of Months | 32659805.19 | 1235.75 | -15.0 | |
Maximum of Months | 0.863360E+10 | 53349.90 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479297E+10 | 27910.23 | 30-JAN-08:12 | -10.4 |
February | 0.449195E+10 | 28011.40 | 06-FEB-08:12 | -15.0 |
March | 0.243359E+10 | 27826.75 | 07-MAR-08:61 | -10.8 |
April | 0.858523E+09 | 27805.31 | 17-APR-07:01 | -2.9 |
May | 0.134039E+09 | 27788.28 | 08-MAY-07:01 | 5.87 |
June | 51719299.52 | 1316.60 | 17-JUN-17:03 | 28.80 |
July | 39593183.41 | 1429.75 | 16-JUL-16:03 | 30.03 |
August | 33212689.90 | 1358.90 | 07-AUG-07:05 | 21.20 |
September | 48550821.25 | 1282.50 | 17-SEP-08:07 | 21.70 |
October | 0.279727E+09 | 27803.91 | 17-OCT-07:01 | -2.4 |
November | 0.121765E+10 | 27802.85 | 22-NOV-08:61 | 1.10 |
December | 0.426110E+10 | 27958.38 | 11-DEC-08:12 | -14.6 |
Annual Sum or Average | 0.186426E+11 | |||
Minimum of Months | 33212689.90 | 1282.50 | -15.0 | |
Maximum of Months | 0.479297E+10 | 28011.40 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486121E+10 | 27746.74 | 30-JAN-08:12 | -10.4 |
February | 0.454910E+10 | 27843.27 | 06-FEB-08:12 | -15.0 |
March | 0.250085E+10 | 27653.06 | 07-MAR-08:61 | -10.8 |
April | 0.905717E+09 | 27631.44 | 17-APR-07:01 | -2.9 |
May | 0.141249E+09 | 27614.22 | 08-MAY-07:01 | 5.87 |
June | 54706711.12 | 1316.81 | 17-JUN-17:03 | 28.80 |
July | 39132223.93 | 1427.96 | 16-JUL-16:03 | 30.03 |
August | 33010305.34 | 1345.63 | 07-AUG-07:05 | 21.20 |
September | 51445754.86 | 1259.45 | 17-SEP-08:07 | 21.70 |
October | 0.293529E+09 | 27630.36 | 17-OCT-07:01 | -2.4 |
November | 0.126354E+10 | 27629.78 | 22-NOV-08:61 | 1.10 |
December | 0.432777E+10 | 27796.24 | 11-DEC-08:12 | -14.6 |
Annual Sum or Average | 0.190213E+11 | |||
Minimum of Months | 33010305.34 | 1259.45 | -15.0 | |
Maximum of Months | 0.486121E+10 | 27843.27 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.530266E+10 | 27486.34 | 30-JAN-08:12 | -10.4 |
February | 0.494369E+10 | 27558.58 | 06-FEB-08:12 | -15.0 |
March | 0.287897E+10 | 27359.63 | 06-MAR-08:13 | -9.0 |
April | 0.115299E+10 | 27326.21 | 17-APR-07:01 | -2.9 |
May | 0.186781E+09 | 27309.73 | 08-MAY-07:01 | 5.87 |
June | 64122940.18 | 1324.45 | 17-JUN-17:03 | 28.80 |
July | 38029086.43 | 1426.07 | 16-JUL-16:03 | 30.03 |
August | 33413629.91 | 1314.98 | 13-AUG-16:03 | 29.03 |
September | 63805339.80 | 1185.77 | 17-SEP-08:07 | 21.70 |
October | 0.381708E+09 | 27323.80 | 17-OCT-07:01 | -2.4 |
November | 0.150316E+10 | 27323.98 | 22-NOV-08:61 | 1.10 |
December | 0.473240E+10 | 27532.33 | 11-DEC-08:12 | -14.6 |
Annual Sum or Average | 0.212817E+11 | |||
Minimum of Months | 33413629.91 | 1185.77 | -15.0 | |
Maximum of Months | 0.530266E+10 | 27558.58 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.783253E+10 | 28924.09 | 30-JAN-08:12 | -10.4 |
February | 0.751573E+10 | 28970.76 | 06-FEB-08:12 | -15.0 |
March | 0.472062E+10 | 28869.97 | 27-MAR-07:12 | -5.0 |
April | 0.222336E+10 | 28668.53 | 17-APR-07:12 | -2.6 |
May | 0.393991E+09 | 28608.74 | 08-MAY-07:01 | 5.87 |
June | 40734902.37 | 3932.91 | 14-JUN-07:05 | 10.18 |
July | 26341627.57 | 1020.93 | 16-JUL-16:03 | 30.03 |
August | 28922374.37 | 901.58 | 13-AUG-16:03 | 29.03 |
September | 40892744.44 | 16651.23 | 30-SEP-07:03 | 8.17 |
October | 0.738734E+09 | 28627.97 | 17-OCT-07:01 | -2.4 |
November | 0.250066E+10 | 28632.07 | 22-NOV-08:61 | 1.10 |
December | 0.699056E+10 | 28959.25 | 11-DEC-08:12 | -14.6 |
Annual Sum or Average | 0.330531E+11 | |||
Minimum of Months | 26341627.57 | 901.58 | -15.0 | |
Maximum of Months | 0.783253E+10 | 28970.76 | 30.03 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.549253E+10 | 3421.96 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.496476E+10 | 3421.96 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.549777E+10 | 3421.96 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.532115E+10 | 3421.96 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.549253E+10 | 3421.96 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.532179E+10 | 3421.96 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.549708E+10 | 3421.96 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.549285E+10 | 3421.96 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.532602E+10 | 3421.96 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.549253E+10 | 3421.96 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.530585E+10 | 3421.96 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.550226E+10 | 3421.96 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.647071E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.496476E+10 | 3421.96 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.550226E+10 | 3421.96 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.334781E+10 | 2090.38 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.302613E+10 | 2090.38 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.335104E+10 | 2090.38 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.324334E+10 | 2090.38 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.334781E+10 | 2090.38 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.324377E+10 | 2090.38 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.335056E+10 | 2090.38 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.334803E+10 | 2090.38 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.324631E+10 | 2090.38 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.334781E+10 | 2090.38 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.323401E+10 | 2090.38 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.335375E+10 | 2090.38 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.394404E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.302613E+10 | 2090.38 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.335375E+10 | 2090.38 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.241466E+10 | 2078.11 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.218750E+10 | 2078.11 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.247235E+10 | 2078.11 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.234375E+10 | 2078.11 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.244351E+10 | 2078.11 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.238702E+10 | 2078.11 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.240024E+10 | 2078.11 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.247235E+10 | 2078.11 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.234375E+10 | 2078.11 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.241466E+10 | 2078.11 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.234375E+10 | 2078.11 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.240024E+10 | 2078.11 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.286238E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.218750E+10 | 2078.11 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.247235E+10 | 2078.11 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770316E+10 |
February | 0.305697E+10 | 0.496476E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747080E+10 |
March | 0.335708E+10 | 0.549777E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11448227.80 | 0.526540E+10 |
April | 0.327081E+10 | 0.532115E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346573E+10 |
May | 0.336680E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10366659.07 | 0.194859E+10 |
June | 0.325380E+10 | 0.532179E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184214E+09 | 0.103313E+10 |
July | 0.339353E+10 | 0.549708E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444462E+09 | 0.357440E+09 |
August | 0.334857E+10 | 0.549285E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372456E+09 | 0.536109E+09 |
September | 0.327932E+10 | 0.532602E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35646179.45 | 0.133018E+10 |
October | 0.338624E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310973E+10 |
November | 0.327446E+10 | 0.530585E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425266E+10 |
December | 0.340325E+10 | 0.550226E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755889E+10 |
Annual Sum or Average | 0.397770E+11 | 0.647071E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105859E+10 | 0.440318E+11 |
Minimum of Months | 0.305697E+10 | 0.496476E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357440E+09 |
Maximum of Months | 0.340325E+10 | 0.550226E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444462E+09 | 0.770316E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371087E+10 |
February | 0.152844E+10 | 0.302613E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354400E+10 |
March | 0.167849E+10 | 0.335104E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6181794.45 | 0.257110E+10 |
April | 0.163536E+10 | 0.324334E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169084E+10 |
May | 0.168335E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5593736.18 | 0.987218E+09 |
June | 0.162685E+10 | 0.324377E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97860488.96 | 0.473167E+09 |
July | 0.169671E+10 | 0.335056E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236991E+09 | 0.143482E+09 |
August | 0.167424E+10 | 0.334803E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200317E+09 | 0.227908E+09 |
September | 0.163961E+10 | 0.324631E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19256454.40 | 0.638457E+09 |
October | 0.169307E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154041E+10 |
November | 0.163718E+10 | 0.323401E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206123E+10 |
December | 0.170157E+10 | 0.335375E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361277E+10 |
Annual Sum or Average | 0.198880E+11 | 0.394404E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566201E+09 | 0.212015E+11 |
Minimum of Months | 0.152844E+10 | 0.302613E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143482E+09 |
Maximum of Months | 0.170157E+10 | 0.335375E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236991E+09 | 0.371087E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382268E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365703E+10 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6182041.78 | 0.263930E+10 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174887E+10 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593737.09 | 0.102045E+10 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95056343.27 | 0.498244E+09 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231813E+09 | 0.164722E+09 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196342E+09 | 0.250279E+09 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19086858.36 | 0.667082E+09 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157885E+10 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211413E+10 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374241E+10 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554074E+09 | 0.219041E+11 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164722E+09 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231813E+09 | 0.382268E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381660E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365074E+10 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6182538.57 | 0.263347E+10 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173822E+10 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593737.13 | 0.100746E+10 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95063429.01 | 0.497577E+09 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231773E+09 | 0.164881E+09 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196326E+09 | 0.250363E+09 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19086997.51 | 0.665586E+09 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156683E+10 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210595E+10 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373578E+10 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554026E+09 | 0.218334E+11 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164881E+09 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231773E+09 | 0.381660E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381134E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364549E+10 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6182107.08 | 0.262677E+10 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172409E+10 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593736.71 | 0.985113E+09 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95138939.89 | 0.493938E+09 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231962E+09 | 0.162830E+09 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196433E+09 | 0.248409E+09 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19088516.02 | 0.660750E+09 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154943E+10 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209702E+10 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373000E+10 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554398E+09 | 0.217352E+11 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162830E+09 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231962E+09 | 0.381134E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.241466E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703260E+10 |
February | 0.313522E+10 | 0.218750E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675020E+10 |
March | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11201804.14 | 0.483324E+10 |
April | 0.338259E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316184E+10 |
May | 0.349753E+10 | 0.244351E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10070359.15 | 0.175365E+10 |
June | 0.343071E+10 | 0.238702E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171964E+09 | 0.914005E+09 |
July | 0.344942E+10 | 0.240024E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419314E+09 | 0.309625E+09 |
August | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354345E+09 | 0.468559E+09 |
September | 0.338259E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34361693.46 | 0.121296E+10 |
October | 0.344359E+10 | 0.241466E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281424E+10 |
November | 0.331698E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386147E+10 |
December | 0.344942E+10 | 0.240024E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689599E+10 |
Annual Sum or Average | 0.410346E+11 | 0.286238E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100126E+10 | 0.400084E+11 |
Minimum of Months | 0.313522E+10 | 0.218750E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309625E+09 |
Maximum of Months | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419314E+09 | 0.703260E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383477E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367221E+10 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6189172.31 | 0.264295E+10 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173619E+10 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593738.46 | 0.989611E+09 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95119103.39 | 0.496957E+09 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232417E+09 | 0.163784E+09 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196537E+09 | 0.250343E+09 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19086893.72 | 0.667025E+09 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155815E+10 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211089E+10 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375379E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554943E+09 | 0.218767E+11 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163784E+09 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232417E+09 | 0.383477E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383353E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367105E+10 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6195083.27 | 0.264114E+10 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173251E+10 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593738.43 | 0.982348E+09 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95149971.54 | 0.495392E+09 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232487E+09 | 0.163138E+09 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196574E+09 | 0.249767E+09 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19087312.27 | 0.665656E+09 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155437E+10 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210886E+10 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375240E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555087E+09 | 0.218502E+11 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163138E+09 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232487E+09 | 0.383353E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382493E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366307E+10 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6243357.46 | 0.263165E+10 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171594E+10 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5594253.19 | 0.948924E+09 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95267239.76 | 0.488279E+09 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232694E+09 | 0.160665E+09 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196680E+09 | 0.247515E+09 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19088490.43 | 0.658338E+09 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153546E+10 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209921E+10 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374347E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555567E+09 | 0.217174E+11 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160665E+09 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232694E+09 | 0.382493E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488983E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481010E+10 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7238319.44 | 0.329592E+10 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218526E+10 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6116357.38 | 0.111666E+10 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103515E+09 | 0.644451E+09 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250396E+09 | 0.256967E+09 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208189E+09 | 0.373955E+09 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20017503.18 | 0.836163E+09 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190520E+10 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266995E+10 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485968E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595472E+09 | 0.278441E+11 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256967E+09 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250396E+09 | 0.488983E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 3421.96 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 11393.74 | 31-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 3421.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 12700.39 | 06-FEB-17:00 |
March | 4050.04 | 03-MAR-13:09 | 3421.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 659.70 | 15-MAR-14:00 | 10040.83 | 06-MAR-18:00 |
April | 4050.04 | 01-APR-12:09 | 3421.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 8058.18 | 16-APR-11:10 |
May | 4050.04 | 05-MAY-12:09 | 3421.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 675.88 | 14-MAY-15:00 | 3955.51 | 11-MAY-15:00 |
June | 4050.04 | 02-JUN-12:09 | 3421.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2026.08 | 27-JUN-13:00 | 4104.93 | 13-JUN-11:05 |
July | 4050.04 | 01-JUL-12:09 | 3421.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2262.91 | 21-JUL-14:00 | 1647.27 | 02-JUL-11:10 |
August | 4050.04 | 04-AUG-12:09 | 3421.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1958.08 | 10-AUG-14:00 | 2777.62 | 30-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 3421.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1007.69 | 16-SEP-13:00 | 3537.85 | 28-SEP-16:00 |
October | 4050.04 | 01-OCT-12:09 | 3421.96 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5309.52 | 23-OCT-16:55 |
November | 4050.04 | 03-NOV-12:09 | 3421.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6512.23 | 22-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 3421.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 11348.04 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1647.27 | |||||
Maximum of Months | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2262.91 | 12700.39 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2090.38 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 2090.38 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2090.38 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.14 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2090.38 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 2090.38 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2139.48 | 11-MAY-15:00 |
June | 2024.96 | 02-JUN-12:09 | 2090.38 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1080.97 | 27-JUN-13:00 | 2316.50 | 13-JUN-11:05 |
July | 2024.96 | 01-JUL-12:09 | 2090.38 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.24 | 21-JUL-14:00 | 894.50 | 02-JUL-11:10 |
August | 2024.96 | 04-AUG-12:09 | 2090.38 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.02 | 10-AUG-14:00 | 1537.90 | 31-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 2090.38 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.86 | 16-SEP-13:00 | 2019.51 | 28-SEP-16:00 |
October | 2024.96 | 01-OCT-12:09 | 2090.38 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-16:55 |
November | 2024.96 | 03-NOV-12:09 | 2090.38 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2090.38 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.50 | |||||
Maximum of Months | 2024.96 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.24 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.16 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2132.40 | 11-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2337.35 | 13-JUN-11:05 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.36 | 21-JUL-14:00 | 894.49 | 02-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1061.99 | 10-AUG-14:00 | 1540.38 | 31-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.84 | 16-SEP-13:00 | 2023.00 | 28-SEP-16:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.49 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.36 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.17 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2109.05 | 11-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.09 | 27-JUN-13:00 | 2336.86 | 13-JUN-11:05 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.36 | 21-JUL-14:00 | 894.49 | 02-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.00 | 10-AUG-14:00 | 1539.66 | 31-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.84 | 16-SEP-13:00 | 2017.15 | 28-SEP-16:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-16:55 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.49 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.36 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.16 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.10 | 27-JUN-13:00 | 2314.17 | 13-JUN-11:05 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.36 | 21-JUL-14:00 | 894.50 | 02-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1061.99 | 10-AUG-14:00 | 1534.43 | 31-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.84 | 16-SEP-13:00 | 1994.29 | 28-SEP-16:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-16:55 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.50 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.36 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2078.11 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 11118.18 | 31-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 2078.11 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 12216.69 | 06-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 2078.11 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 641.25 | 15-MAR-14:00 | 9818.19 | 06-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 2078.11 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 7828.71 | 16-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 2078.11 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 647.63 | 14-MAY-15:00 | 3797.45 | 11-MAY-15:00 |
June | 5400.05 | 03-JUN-14:09 | 2078.11 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1949.06 | 27-JUN-13:00 | 4001.30 | 13-JUN-11:05 |
July | 5400.05 | 01-JUL-14:09 | 2078.11 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2212.78 | 21-JUL-14:00 | 1609.12 | 02-JUL-11:10 |
August | 5400.05 | 05-AUG-14:09 | 2078.11 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1910.71 | 10-AUG-14:00 | 2714.37 | 31-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 2078.11 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 971.17 | 16-SEP-13:00 | 3439.48 | 28-SEP-16:00 |
October | 5400.05 | 07-OCT-14:09 | 2078.11 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5204.75 | 23-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 2078.11 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6438.11 | 22-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2078.11 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 11218.88 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1609.12 | |||||
Maximum of Months | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2212.78 | 12216.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.17 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4348.64 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.08 | 27-JUN-13:00 | 2291.65 | 13-JUN-11:05 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.38 | 21-JUL-14:00 | 894.52 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.01 | 10-AUG-14:00 | 1533.91 | 31-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.86 | 16-SEP-13:00 | 1982.82 | 28-SEP-16:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.52 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.38 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.17 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4348.64 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.08 | 27-JUN-13:00 | 2283.00 | 13-JUN-11:05 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.38 | 21-JUL-14:00 | 894.52 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.01 | 10-AUG-14:00 | 1532.30 | 31-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.86 | 16-SEP-13:00 | 1976.98 | 28-SEP-16:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2889.27 | 23-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.52 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.38 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.17 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4348.64 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.08 | 27-JUN-13:00 | 2242.15 | 13-JUN-11:05 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.52 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.01 | 10-AUG-14:00 | 1524.72 | 31-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.86 | 16-SEP-13:00 | 1940.94 | 28-SEP-16:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-16:55 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.52 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6455.29 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7285.77 | 06-FEB-17:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 374.79 | 15-MAR-14:00 | 5681.40 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4578.11 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 387.28 | 14-MAY-15:00 | 2263.84 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.29 | 27-JUN-13:00 | 2161.21 | 13-JUN-11:05 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1284.48 | 15-JUL-15:00 | 932.71 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1109.37 | 10-AUG-14:00 | 1527.04 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 575.34 | 16-SEP-13:00 | 1843.81 | 28-SEP-16:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3011.82 | 23-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3659.14 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6376.32 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 932.71 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1284.48 | 7285.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7377.88 | 01-JAN-18:43 | 12150.11 | 10265.87 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1149.62 |
February | 7470.65 | 28-FEB-19:53 | 10125.10 | 10265.87 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1157.04 |
March | 6898.49 | 04-MAR-00:12 | 1687.52 | 9005.18 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.90 |
April | 4253.11 | 09-APR-18:00 | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609.20 |
May | 5191.37 | 31-MAY-17:10 | 3375.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.00 |
June | 11765.41 | 18-JUN-07:03 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 |
July | 20585.49 | 19-JUL-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.62 |
August | 22430.02 | 07-AUG-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.22 |
September | 22131.46 | 17-SEP-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.46 |
October | 5518.72 | 23-OCT-17:10 | 3375.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 932.15 |
November | 4949.95 | 24-NOV-00:03 | 1012.51 | 540.34 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.52 |
December | 6863.58 | 29-DEC-00:12 | 1687.52 | 900.57 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 603.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4253.11 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 | |
Maximum of Months | 22430.02 | 12150.11 | 10265.87 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1157.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4718.01 | 30-JAN-20:03 | 4049.92 | 8361.52 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.98 |
February | 4425.98 | 25-FEB-18:03 | 6749.87 | 8361.52 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.12 |
March | 11246.83 | 15-MAR-20:01 | 7087.36 | 14632.66 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 2489.15 | 10-APR-17:10 | 1687.47 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.99 |
May | 12335.85 | 23-MAY-20:01 | 7087.36 | 14632.66 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 |
June | 14490.31 | 03-JUN-18:08 | 10124.81 | 12542.28 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.21 |
July | 12663.86 | 06-JUL-20:10 | 5062.40 | 10451.90 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 |
August | 13414.48 | 06-AUG-07:03 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.97 |
September | 12751.60 | 03-SEP-17:50 | 6074.88 | 6271.14 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.87 |
October | 11342.70 | 22-OCT-17:09 | 14174.73 | 14632.66 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.67 |
November | 2512.06 | 06-NOV-18:10 | 1687.47 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.23 |
December | 5039.16 | 11-DEC-20:42 | 4049.92 | 8361.52 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2489.15 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 | |
Maximum of Months | 14490.31 | 14174.73 | 14632.66 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4426.38 | 05-JAN-18:23 | 6749.87 | 7811.61 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 711.12 |
February | 3764.55 | 27-FEB-18:13 | 5062.40 | 5858.70 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.48 |
March | 2513.08 | 17-MAR-17:20 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.73 |
April | 2159.91 | 10-APR-17:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.99 |
May | 3062.23 | 27-MAY-13:00 | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.05 |
June | 9302.24 | 18-JUN-07:03 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 |
July | 13718.00 | 15-JUL-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
August | 14781.41 | 06-AUG-07:03 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.42 |
September | 12941.14 | 17-SEP-07:03 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.63 |
October | 2757.17 | 23-OCT-17:20 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.15 |
November | 2288.95 | 06-NOV-18:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.98 |
December | 1951.68 | 15-DEC-11:45 | 674.99 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1951.68 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 | |
Maximum of Months | 14781.41 | 6749.87 | 7811.61 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 711.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3514.28 | 10-JAN-18:03 | 5062.40 | 5858.70 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.05 |
February | 2436.68 | 17-FEB-19:45 | 1349.97 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.24 |
March | 2503.73 | 03-MAR-11:45 | 674.99 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.25 |
April | 2121.28 | 11-APR-18:00 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.55 |
May | 2979.56 | 27-MAY-13:00 | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.05 |
June | 9103.74 | 18-JUN-07:03 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.71 |
July | 13668.54 | 15-JUL-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.51 |
August | 14967.36 | 06-AUG-07:03 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.47 |
September | 12874.85 | 17-SEP-07:03 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.75 |
October | 2723.68 | 23-OCT-17:20 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.25 |
November | 2154.40 | 03-NOV-17:40 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.91 |
December | 2243.05 | 04-DEC-11:45 | 674.99 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 635.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2121.28 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.51 | |
Maximum of Months | 14967.36 | 5062.40 | 5858.70 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3889.78 | 06-JAN-18:43 | 5062.40 | 5858.70 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.48 |
February | 3218.50 | 14-FEB-18:13 | 5062.40 | 5858.70 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540.53 |
March | 2424.05 | 17-MAR-17:20 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.18 |
April | 2028.72 | 11-APR-17:30 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.55 |
May | 2724.62 | 27-MAY-13:00 | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.05 |
June | 7673.82 | 18-JUN-07:03 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.02 |
July | 12796.12 | 19-JUL-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.18 |
August | 13857.64 | 07-AUG-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 |
September | 12785.74 | 17-SEP-07:03 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.71 |
October | 2675.96 | 23-OCT-17:20 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.57 |
November | 2006.43 | 03-NOV-17:20 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.47 |
December | 2280.39 | 17-DEC-11:15 | 1349.97 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2006.43 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.18 | |
Maximum of Months | 13857.64 | 5062.40 | 5858.70 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.92 |
February | 293.64 | 18-FEB-12:00 | 3915.04 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1016.78 |
March | 6398.72 | 23-MAR-10:43 | 8707.58 | 6234.32 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1155.19 |
April | 4674.74 | 11-APR-12:35 | 9585.09 | 4156.22 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4225.31 |
May | 4741.22 | 27-MAY-14:30 | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.10 |
June | 15361.25 | 18-JUN-08:63 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 26.18 | 0.00 |
July | 20928.83 | 20-JUL-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 27.24 | 0.00 |
August | 23347.30 | 07-AUG-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.98 |
September | 18826.12 | 17-SEP-08:63 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.45 |
October | 4665.22 | 14-OCT-11:00 | 3915.04 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 701.07 |
November | 5040.89 | 21-NOV-18:15 | 4590.04 | 4156.22 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 907.30 |
December | 1731.99 | 16-DEC-12:00 | 3915.04 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23347.30 | 9585.09 | 6234.32 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 27.24 | 4225.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.95 |
February | 30.52 | 18-FEB-12:00 | 1957.46 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.94 |
March | 2470.16 | 23-MAR-10:55 | 2902.44 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617.12 |
April | 1556.66 | 11-APR-16:55 | 4792.41 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2176.91 |
May | 2413.28 | 27-MAY-14:30 | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.90 |
June | 7506.15 | 18-JUN-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 0.00 |
July | 10860.28 | 19-JUL-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.41 |
August | 12172.63 | 07-AUG-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.76 |
September | 9189.84 | 17-SEP-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.82 |
October | 2068.24 | 14-OCT-11:00 | 1957.46 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.09 |
November | 1947.61 | 29-NOV-18:55 | 2294.96 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.62 |
December | 813.33 | 16-DEC-12:00 | 1957.46 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12172.63 | 4792.41 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 2176.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.14 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.63 |
March | 1825.37 | 15-MAR-14:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 342.11 | 0.00 |
April | 1531.07 | 11-APR-16:45 | 4792.41 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2145.00 |
May | 2318.93 | 27-MAY-14:40 | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.49 |
June | 6853.30 | 18-JUN-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 14.25 | 0.00 |
July | 10756.21 | 19-JUL-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.59 |
August | 12063.78 | 07-AUG-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.01 |
September | 8893.69 | 17-SEP-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.73 |
October | 2301.00 | 23-OCT-16:55 | 4792.41 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2844.98 |
November | 1957.11 | 29-NOV-18:05 | 2294.96 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.83 |
December | 2422.62 | 02-DEC-11:45 | 3914.92 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12063.78 | 4792.41 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 342.11 | 2844.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.07 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.02 |
March | 1778.93 | 21-MAR-17:35 | 2294.96 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.05 |
April | 1477.50 | 05-APR-18:15 | 1754.97 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.94 |
May | 1993.81 | 27-MAY-14:40 | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.49 |
June | 4875.86 | 27-JUN-13:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.08 | 0.00 |
July | 10507.73 | 20-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.77 | 0.00 |
August | 11811.77 | 07-AUG-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.12 |
September | 7781.05 | 17-SEP-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.41 |
October | 2221.90 | 14-OCT-15:35 | 4994.90 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2692.81 |
November | 2039.89 | 28-NOV-18:05 | 2294.96 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.98 |
December | 1205.74 | 01-DEC-18:50 | 1147.48 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11811.77 | 4994.90 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.08 | 2692.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 673.09 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 857.91 |
March | 1881.70 | 17-MAR-18:15 | 1754.97 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.99 |
April | 1376.72 | 22-APR-11:00 | 1957.46 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.74 |
May | 1442.21 | 27-MAY-14:10 | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.34 |
June | 5054.23 | 27-JUN-13:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.29 | 0.00 |
July | 9887.06 | 17-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.01 |
August | 8518.83 | 14-AUG-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.88 |
September | 5238.56 | 17-SEP-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.69 |
October | 2149.87 | 16-OCT-17:45 | 2294.96 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.62 |
November | 2006.93 | 06-NOV-18:15 | 2294.96 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.23 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9887.06 | 2699.95 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.29 | 857.91 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.552310E+11 | 49045.47 | 07-JAN-17:19 | 0.123362E+12 | 179387.11 | 24-JAN-08:09 |
February | 0.496477E+11 | 44740.01 | 06-FEB-17:49 | 0.115926E+12 | 201719.01 | 07-FEB-08:09 |
March | 0.544777E+11 | 47246.91 | 15-MAR-15:20 | 0.710231E+11 | 170007.44 | 06-MAR-08:09 |
April | 0.506365E+11 | 43859.14 | 04-APR-18:00 | 0.286457E+11 | 123671.65 | 17-APR-07:10 |
May | 0.524699E+11 | 51652.94 | 10-MAY-13:39 | 0.173422E+10 | 48683.67 | 01-MAY-07:10 |
June | 0.584893E+11 | 65823.87 | 27-JUN-12:09 | 2621231.28 | 2195.30 | 14-JUN-07:10 |
July | 0.692325E+11 | 68681.65 | 15-JUL-14:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.669206E+11 | 64843.33 | 13-AUG-14:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.554300E+11 | 57812.02 | 16-SEP-14:30 | 19434945.63 | 4821.90 | 30-SEP-07:10 |
October | 0.528634E+11 | 43547.98 | 16-OCT-17:40 | 0.116451E+11 | 80979.62 | 30-OCT-07:10 |
November | 0.521224E+11 | 45759.27 | 25-NOV-16:40 | 0.412866E+11 | 108346.82 | 24-NOV-08:09 |
December | 0.550244E+11 | 46818.99 | 12-DEC-16:49 | 0.112472E+12 | 188220.67 | 26-DEC-08:09 |
Annual Sum or Average | 0.672545E+12 | 0.506117E+12 | ||||
Minimum of Months | 0.496477E+11 | 43547.98 | 0.00 | 0.00 | ||
Maximum of Months | 0.692325E+11 | 68681.65 | 0.123362E+12 | 201719.01 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.198110E+10 | 6314.94 | 30-JAN-12:30 | 0.00 | 0.00 |
February | 0.282168E+10 | 8133.15 | 28-FEB-12:30 | 0.00 | 0.00 |
March | 0.453752E+10 | 9802.70 | 25-MAR-12:30 | 0.00 | 0.00 |
April | 0.560278E+10 | 10683.22 | 17-APR-12:20 | 0.00 | 0.00 |
May | 0.702899E+10 | 10801.66 | 31-MAY-12:20 | 0.00 | 0.00 |
June | 0.776689E+10 | 11250.00 | 14-JUN-11:50 | 0.00 | 0.00 |
July | 0.734640E+10 | 10583.58 | 01-JUL-12:30 | 0.00 | 0.00 |
August | 0.632164E+10 | 9610.89 | 08-AUG-12:20 | 0.00 | 0.00 |
September | 0.472647E+10 | 8960.71 | 07-SEP-12:30 | 0.00 | 0.00 |
October | 0.322787E+10 | 7272.04 | 11-OCT-11:00 | 0.00 | 0.00 |
November | 0.185015E+10 | 5751.03 | 03-NOV-11:30 | 0.00 | 0.00 |
December | 0.174025E+10 | 5336.22 | 10-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.549517E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.174025E+10 | 5336.22 | 0.00 | 0.00 | |
Maximum of Months | 0.776689E+10 | 11250.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.234911E+11 | 0.466781E+10 | 0.108325E+11 | 0.00 | 0.105277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571199E+10 | 0.00 |
February | 0.212624E+11 | 0.378675E+10 | 0.980803E+10 | 0.00 | 0.959852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519201E+10 | 0.00 |
March | 0.238408E+11 | 0.359997E+10 | 0.110075E+11 | 0.00 | 0.999475E+10 | 0.00 | 0.00 | 0.280268E+09 | 0.00 | 0.00 | 0.00 | 0.575443E+10 | 0.00 |
April | 0.227839E+11 | 0.288520E+10 | 0.105079E+11 | 0.00 | 0.899713E+10 | 0.00 | 0.00 | 610177.12 | 0.00 | 0.00 | 0.00 | 0.546168E+10 | 0.00 |
May | 0.236617E+11 | 0.248909E+10 | 0.109147E+11 | 0.00 | 0.906466E+10 | 0.00 | 0.00 | 0.813362E+09 | 0.00 | 0.00 | 0.00 | 0.552637E+10 | 0.00 |
June | 0.230409E+11 | 0.219785E+10 | 0.106386E+11 | 0.00 | 0.883322E+10 | 0.00 | 0.00 | 0.852951E+10 | 0.00 | 0.00 | 0.00 | 0.524925E+10 | 0.00 |
July | 0.234131E+11 | 0.233158E+10 | 0.107945E+11 | 0.00 | 0.893828E+10 | 0.00 | 0.00 | 0.184482E+11 | 0.00 | 0.00 | 0.00 | 0.530676E+10 | 0.00 |
August | 0.238328E+11 | 0.274569E+10 | 0.110006E+11 | 0.00 | 0.913226E+10 | 0.00 | 0.00 | 0.148810E+11 | 0.00 | 0.00 | 0.00 | 0.532817E+10 | 0.00 |
September | 0.227918E+11 | 0.322600E+10 | 0.105148E+11 | 0.00 | 0.874081E+10 | 0.00 | 0.00 | 0.499761E+10 | 0.00 | 0.00 | 0.00 | 0.515903E+10 | 0.00 |
October | 0.234911E+11 | 0.394759E+10 | 0.108325E+11 | 0.00 | 0.907066E+10 | 0.00 | 0.00 | 93408313.35 | 0.00 | 0.00 | 0.00 | 0.542816E+10 | 0.00 |
November | 0.227593E+11 | 0.435292E+10 | 0.104978E+11 | 0.00 | 0.915273E+10 | 0.00 | 0.00 | 189530.71 | 0.00 | 0.00 | 0.00 | 0.535945E+10 | 0.00 |
December | 0.234215E+11 | 0.481095E+10 | 0.108050E+11 | 0.00 | 0.103446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564237E+10 | 0.00 |
Annual Sum or Average | 0.277790E+12 | 0.410414E+11 | 0.128154E+12 | 0.00 | 0.112395E+12 | 0.00 | 0.00 | 0.480442E+11 | 0.00 | 0.00 | 0.00 | 0.651197E+11 | 0.00 |
Minimum of Months | 0.212624E+11 | 0.219785E+10 | 0.980803E+10 | 0.00 | 0.874081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515903E+10 | 0.00 |
Maximum of Months | 0.238408E+11 | 0.481095E+10 | 0.110075E+11 | 0.00 | 0.105277E+11 | 0.00 | 0.00 | 0.184482E+11 | 0.00 | 0.00 | 0.00 | 0.575443E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.123362E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.115926E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.710231E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.286457E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.173422E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2621231.28 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 19434945.63 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.116451E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.412866E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.112472E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.506117E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.123362E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17697.17 | 01-JAN-11:09 | 3786.68 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 8549.34 | 24-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 17697.17 | 01-FEB-10:09 | 3786.68 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 8887.61 | 07-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 17697.17 | 01-MAR-10:09 | 3786.68 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 8403.76 | 06-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 17697.17 | 01-APR-09:09 | 3786.68 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 7820.34 | 17-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 17697.17 | 01-MAY-09:09 | 3786.68 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 6867.21 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 17697.17 | 01-JUN-09:09 | 3786.68 | 01-JUN-19:49 | 8059.50 | 01-JUN-09:09 | 0.00 | 6570.87 | 27-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 17697.17 | 01-JUL-09:09 | 3786.68 | 01-JUL-19:00 | 8059.50 | 01-JUL-09:09 | 0.00 | 7485.27 | 21-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 17697.17 | 01-AUG-09:09 | 3786.68 | 01-AUG-19:40 | 8059.50 | 01-AUG-09:09 | 0.00 | 7080.24 | 14-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 17697.17 | 01-SEP-09:09 | 3786.68 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 6522.39 | 17-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 17697.17 | 01-OCT-10:09 | 3786.68 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 7292.23 | 30-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 17697.17 | 01-NOV-09:09 | 3786.68 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7640.27 | 24-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 17697.17 | 01-DEC-10:09 | 3786.68 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 8628.97 | 26-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 17697.17 | 3786.68 | 8059.50 | 0.00 | 6522.39 | 0.00 | 0.00 | |||||
Maximum of Months | 17697.17 | 3786.68 | 8059.50 | 0.00 | 8887.61 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 13728.84 | 07-JAN-15:50 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 9743.73 | 28-FEB-13:39 | 0.00 | 01-FEB-00:10 |
March | 9240.56 | 15-MAR-14:09 | 0.00 | 0.00 | 0.00 | 9711.61 | 23-MAR-14:20 | 0.00 | 01-MAR-00:10 |
April | 459.23 | 09-APR-17:19 | 0.00 | 0.00 | 0.00 | 9690.13 | 28-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 12317.08 | 14-MAY-14:00 | 0.00 | 0.00 | 0.00 | 9719.14 | 10-MAY-13:39 | 0.00 | 01-MAY-00:10 |
June | 28524.14 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 11844.92 | 02-JUN-12:00 | 0.00 | 01-JUN-00:10 |
July | 29572.32 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 7582.21 | 01-JUL-12:30 | 0.00 | 01-JUL-00:10 |
August | 27391.05 | 13-AUG-14:00 | 0.00 | 0.00 | 0.00 | 8852.25 | 19-AUG-14:09 | 0.00 | 01-AUG-00:10 |
September | 21376.46 | 16-SEP-13:50 | 0.00 | 0.00 | 0.00 | 9710.46 | 29-SEP-12:50 | 0.00 | 01-SEP-00:10 |
October | 4399.62 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 | 7586.53 | 25-OCT-13:09 | 0.00 | 01-OCT-00:10 |
November | 192.29 | 04-NOV-18:40 | 0.00 | 0.00 | 0.00 | 9730.59 | 25-NOV-13:50 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 9727.32 | 08-DEC-14:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7582.21 | 0.00 | |||
Maximum of Months | 29572.32 | 0.00 | 0.00 | 0.00 | 13728.84 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 49045.47 | 07-JAN-17:19 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 7684.32 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44740.01 | 06-FEB-17:49 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 8757.37 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 47246.91 | 15-MAR-15:20 | 17697.17 | 8059.50 | 0.00 | 0.00 | 6268.15 | 0.00 | 0.00 | 8044.15 | 0.00 |
April | 43859.14 | 04-APR-18:00 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 6750.71 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 51652.94 | 10-MAY-13:39 | 17697.17 | 8059.50 | 0.00 | 0.00 | 6268.15 | 0.00 | 0.00 | 9908.98 | 0.00 |
June | 65823.87 | 27-JUN-12:09 | 17697.17 | 8059.50 | 0.00 | 0.00 | 6320.03 | 0.00 | 0.00 | 26164.25 | 0.00 |
July | 68681.65 | 15-JUL-14:39 | 17697.17 | 8059.50 | 0.00 | 0.00 | 6569.48 | 0.00 | 0.00 | 28930.83 | 0.00 |
August | 64843.33 | 13-AUG-14:39 | 17697.17 | 8059.50 | 0.00 | 0.00 | 6490.84 | 0.00 | 0.00 | 27171.94 | 0.00 |
September | 57812.02 | 16-SEP-14:30 | 17697.17 | 8059.50 | 0.00 | 0.00 | 6268.15 | 0.00 | 0.00 | 20547.42 | 0.00 |
October | 43547.98 | 16-OCT-17:40 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 6447.34 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45759.27 | 25-NOV-16:40 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 6532.51 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 46818.99 | 12-DEC-16:49 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 7635.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 43547.98 | 17697.17 | 8059.50 | 0.00 | 0.00 | 6268.15 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 68681.65 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 8757.37 | 0.00 | 0.00 | 28930.83 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 179387.11 | 24-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 201719.01 | 07-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 170007.44 | 06-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 123671.65 | 17-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 48683.67 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2195.30 | 14-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 4821.90 | 30-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 80979.62 | 30-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 108346.82 | 24-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 188220.67 | 26-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 201719.01 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.00 | 20.40 | 2.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
February | 4.50 | 20.25 | 2.00 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
March | 2.00 | 20.45 | 0.83 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
April | 1.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
November | 0.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
December | 3.00 | 20.37 | 1.17 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Annual Sum or Average | 16.17 | 20.37 | 6.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.00 | 20.55 | 2.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
February | 1.67 | 20.46 | 0.50 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
March | 0.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
April | 0.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 3.17 | 20.48 | 0.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.52 | 0.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Annual Sum or Average | 1.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
February | 1.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
March | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Annual Sum or Average | 2.17 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 1.33 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
March | 0.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Annual Sum or Average | 3.50 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
February | 3.17 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
March | 1.17 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.83 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
Annual Sum or Average | 9.83 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
February | 2.83 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
March | 1.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
Annual Sum or Average | 8.67 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
February | 3.17 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
March | 1.17 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.67 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
Annual Sum or Average | 9.33 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
February | 3.83 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 |
March | 2.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
April | 0.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
Annual Sum or Average | 13.17 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.67 | 17.96 | 0.00 | 17.96 | 0.00 | 17.96 | 0.00 | 17.96 |
February | 14.00 | 16.56 | 0.00 | 16.56 | 0.00 | 16.56 | 0.00 | 16.56 |
March | 5.33 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
April | 2.33 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
November | 0.83 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
December | 8.33 | 17.80 | 0.00 | 17.80 | 0.00 | 17.80 | 0.00 | 17.80 |
Annual Sum or Average | 39.67 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.07 | 472.17 | 21.07 | 472.17 | 21.07 |
February | 448.00 | 21.06 | 445.83 | 21.06 | 445.83 | 21.06 |
March | 495.17 | 21.26 | 298.00 | 21.19 | 298.00 | 21.15 |
April | 479.00 | 21.36 | 90.33 | 21.31 | 90.33 | 21.28 |
May | 413.00 | 22.58 | 11.50 | 22.57 | 7.00 | 22.55 |
June | 157.67 | 23.62 | 227.33 | 23.78 | 71.50 | 23.80 |
July | 124.50 | 23.89 | 447.00 | 23.89 | 122.17 | 23.89 |
August | 88.50 | 23.87 | 363.50 | 23.89 | 78.17 | 23.89 |
September | 131.00 | 23.40 | 195.33 | 23.69 | 44.83 | 23.72 |
October | 445.33 | 21.82 | 22.33 | 21.84 | 13.67 | 21.82 |
November | 480.00 | 21.23 | 112.00 | 21.20 | 112.00 | 21.17 |
December | 496.00 | 21.07 | 432.83 | 21.07 | 432.83 | 21.06 |
Annual Sum or Average | 4254.17 | 21.68 | 3118.17 | 21.89 | 2188.50 | 21.80 |
Minimum of Months | 88.50 | 21.06 | 11.50 | 21.06 | 7.00 | 21.06 |
Maximum of Months | 496.00 | 23.89 | 472.17 | 23.89 | 472.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.18 | 377.50 | 21.15 | 377.50 | 21.14 |
February | 448.00 | 21.16 | 351.00 | 21.14 | 351.00 | 21.13 |
March | 482.00 | 21.49 | 166.33 | 21.40 | 166.33 | 21.34 |
April | 479.00 | 21.94 | 15.33 | 21.91 | 15.33 | 21.89 |
May | 323.17 | 23.10 | 25.00 | 23.16 | 0.00 | 23.16 |
June | 109.33 | 23.74 | 221.00 | 23.83 | 43.00 | 23.84 |
July | 67.50 | 23.88 | 419.50 | 23.87 | 67.17 | 23.87 |
August | 47.50 | 23.86 | 339.00 | 23.87 | 43.83 | 23.87 |
September | 85.33 | 23.64 | 199.00 | 23.80 | 32.00 | 23.81 |
October | 393.17 | 22.30 | 10.50 | 22.34 | 0.67 | 22.34 |
November | 480.00 | 21.67 | 12.17 | 21.66 | 12.17 | 21.65 |
December | 496.00 | 21.23 | 282.83 | 21.18 | 282.83 | 21.16 |
Annual Sum or Average | 3907.00 | 21.85 | 2419.17 | 22.10 | 1391.83 | 21.99 |
Minimum of Months | 47.50 | 21.16 | 10.50 | 21.14 | 0.00 | 21.13 |
Maximum of Months | 496.00 | 23.88 | 419.50 | 23.87 | 377.50 | 23.87 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 331.50 | 21.11 | 331.50 | 21.11 |
February | 336.00 | 21.11 | 308.50 | 21.11 | 308.50 | 21.11 |
March | 369.83 | 21.30 | 175.67 | 21.24 | 175.67 | 21.21 |
April | 360.00 | 21.52 | 29.50 | 21.49 | 29.50 | 21.47 |
May | 255.17 | 22.79 | 15.00 | 22.85 | 0.17 | 22.85 |
June | 100.33 | 23.79 | 193.50 | 23.95 | 52.33 | 23.96 |
July | 88.50 | 24.04 | 345.17 | 24.03 | 88.17 | 24.03 |
August | 55.50 | 24.07 | 303.83 | 24.03 | 52.50 | 24.04 |
September | 85.67 | 23.61 | 161.67 | 23.86 | 36.50 | 23.88 |
October | 317.33 | 21.93 | 11.50 | 21.96 | 4.67 | 21.95 |
November | 360.00 | 21.28 | 35.67 | 21.27 | 35.67 | 21.25 |
December | 369.00 | 21.11 | 269.83 | 21.11 | 269.83 | 21.11 |
Annual Sum or Average | 3068.33 | 21.72 | 2181.33 | 22.04 | 1385.00 | 21.94 |
Minimum of Months | 55.50 | 21.11 | 11.50 | 21.11 | 0.17 | 21.11 |
Maximum of Months | 371.00 | 24.07 | 345.17 | 24.03 | 331.50 | 24.04 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 337.33 | 21.11 | 337.33 | 21.11 |
February | 336.00 | 21.11 | 324.83 | 21.11 | 324.83 | 21.11 |
March | 370.83 | 21.30 | 184.33 | 21.24 | 184.33 | 21.20 |
April | 360.00 | 21.48 | 35.33 | 21.45 | 35.33 | 21.42 |
May | 263.67 | 22.71 | 12.83 | 22.75 | 1.33 | 22.75 |
June | 102.67 | 23.78 | 190.33 | 23.95 | 52.83 | 23.95 |
July | 89.33 | 24.04 | 345.33 | 24.03 | 89.00 | 24.03 |
August | 56.33 | 24.07 | 304.00 | 24.03 | 53.17 | 24.04 |
September | 90.33 | 23.59 | 159.83 | 23.85 | 36.50 | 23.87 |
October | 326.83 | 21.91 | 12.33 | 21.93 | 6.17 | 21.92 |
November | 360.00 | 21.26 | 46.17 | 21.24 | 46.17 | 21.23 |
December | 369.00 | 21.11 | 287.17 | 21.11 | 287.17 | 21.11 |
Annual Sum or Average | 3096.00 | 21.71 | 2239.83 | 22.01 | 1454.17 | 21.92 |
Minimum of Months | 56.33 | 21.11 | 12.33 | 21.11 | 1.33 | 21.11 |
Maximum of Months | 371.00 | 24.07 | 345.33 | 24.03 | 337.33 | 24.04 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 345.00 | 21.11 | 345.00 | 21.11 |
February | 336.00 | 21.11 | 330.83 | 21.11 | 330.83 | 21.11 |
March | 375.83 | 21.31 | 200.33 | 21.24 | 200.33 | 21.21 |
April | 360.00 | 21.41 | 49.00 | 21.37 | 49.00 | 21.35 |
May | 293.00 | 22.64 | 7.83 | 22.65 | 2.67 | 22.63 |
June | 110.50 | 23.75 | 186.00 | 23.93 | 54.50 | 23.94 |
July | 91.17 | 24.04 | 342.83 | 24.02 | 90.50 | 24.03 |
August | 59.67 | 24.05 | 291.33 | 24.03 | 55.50 | 24.03 |
September | 98.83 | 23.52 | 152.00 | 23.80 | 37.67 | 23.83 |
October | 342.00 | 21.87 | 11.00 | 21.87 | 8.67 | 21.85 |
November | 360.00 | 21.23 | 66.33 | 21.21 | 66.33 | 21.20 |
December | 369.00 | 21.11 | 307.17 | 21.11 | 307.17 | 21.11 |
Annual Sum or Average | 3167.00 | 21.71 | 2289.67 | 21.98 | 1548.17 | 21.89 |
Minimum of Months | 59.67 | 21.11 | 7.83 | 21.11 | 2.67 | 21.11 |
Maximum of Months | 375.83 | 24.05 | 345.00 | 24.03 | 345.00 | 24.03 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 327.83 | 21.11 | 327.83 | 21.11 |
February | 308.00 | 21.11 | 305.50 | 21.11 | 305.50 | 21.11 |
March | 348.00 | 21.31 | 216.33 | 21.23 | 216.33 | 21.20 |
April | 330.00 | 21.31 | 62.50 | 21.28 | 62.50 | 21.25 |
May | 314.33 | 22.51 | 7.83 | 22.49 | 7.83 | 22.48 |
June | 116.83 | 23.65 | 157.50 | 23.82 | 54.83 | 23.84 |
July | 86.83 | 23.97 | 302.50 | 23.95 | 86.50 | 23.95 |
August | 67.67 | 23.92 | 240.33 | 23.93 | 63.00 | 23.94 |
September | 99.67 | 23.36 | 122.67 | 23.66 | 38.00 | 23.70 |
October | 332.33 | 21.79 | 9.67 | 21.77 | 9.67 | 21.75 |
November | 330.00 | 21.20 | 118.33 | 21.17 | 118.33 | 21.16 |
December | 338.00 | 21.11 | 314.50 | 21.11 | 314.50 | 21.11 |
Annual Sum or Average | 3011.67 | 21.70 | 2185.50 | 21.90 | 1604.83 | 21.82 |
Minimum of Months | 67.67 | 21.11 | 7.83 | 21.11 | 7.83 | 21.11 |
Maximum of Months | 348.00 | 23.97 | 327.83 | 23.95 | 327.83 | 23.95 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 327.33 | 21.11 | 327.33 | 21.11 |
February | 308.00 | 21.11 | 305.67 | 21.11 | 305.67 | 21.11 |
March | 348.00 | 21.34 | 216.33 | 21.25 | 216.33 | 21.21 |
April | 330.00 | 21.44 | 63.50 | 21.39 | 63.50 | 21.35 |
May | 312.17 | 22.87 | 7.33 | 22.84 | 7.33 | 22.82 |
June | 126.50 | 23.80 | 149.67 | 23.88 | 60.17 | 23.89 |
July | 93.17 | 23.98 | 294.00 | 23.96 | 92.67 | 23.96 |
August | 73.67 | 23.95 | 228.17 | 23.95 | 70.00 | 23.95 |
September | 103.33 | 23.61 | 118.83 | 23.78 | 39.33 | 23.80 |
October | 330.83 | 22.00 | 10.17 | 21.98 | 10.17 | 21.95 |
November | 330.00 | 21.24 | 118.67 | 21.21 | 118.67 | 21.19 |
December | 338.00 | 21.11 | 313.83 | 21.11 | 313.83 | 21.11 |
Annual Sum or Average | 3033.67 | 21.82 | 2153.50 | 21.96 | 1625.00 | 21.87 |
Minimum of Months | 73.67 | 21.11 | 7.33 | 21.11 | 7.33 | 21.11 |
Maximum of Months | 348.00 | 23.98 | 327.33 | 23.96 | 327.33 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 327.67 | 21.11 | 327.67 | 21.11 |
February | 308.00 | 21.11 | 306.00 | 21.11 | 306.00 | 21.11 |
March | 348.00 | 21.34 | 218.67 | 21.25 | 218.67 | 21.21 |
April | 330.00 | 21.42 | 66.67 | 21.37 | 66.67 | 21.33 |
May | 317.67 | 22.83 | 8.00 | 22.81 | 8.00 | 22.78 |
June | 131.83 | 23.79 | 146.33 | 23.87 | 61.17 | 23.88 |
July | 94.33 | 23.98 | 292.17 | 23.96 | 93.50 | 23.96 |
August | 75.17 | 23.95 | 224.00 | 23.95 | 70.83 | 23.95 |
September | 106.17 | 23.60 | 117.33 | 23.77 | 40.00 | 23.79 |
October | 332.50 | 21.99 | 11.33 | 21.96 | 11.33 | 21.93 |
November | 330.00 | 21.24 | 124.50 | 21.20 | 124.50 | 21.18 |
December | 338.00 | 21.11 | 314.50 | 21.11 | 314.50 | 21.11 |
Annual Sum or Average | 3051.67 | 21.82 | 2157.17 | 21.95 | 1642.83 | 21.86 |
Minimum of Months | 75.17 | 21.11 | 8.00 | 21.11 | 8.00 | 21.11 |
Maximum of Months | 348.00 | 23.98 | 327.67 | 23.96 | 327.67 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 329.83 | 21.11 | 329.83 | 21.11 |
February | 308.00 | 21.11 | 308.00 | 21.11 | 308.00 | 21.11 |
March | 348.00 | 21.32 | 230.00 | 21.23 | 230.00 | 21.20 |
April | 330.00 | 21.35 | 85.33 | 21.30 | 85.33 | 21.27 |
May | 337.33 | 22.66 | 10.50 | 22.63 | 10.50 | 22.60 |
June | 148.33 | 23.73 | 140.67 | 23.84 | 62.17 | 23.85 |
July | 100.17 | 23.97 | 289.33 | 23.96 | 98.50 | 23.96 |
August | 80.00 | 23.93 | 220.17 | 23.94 | 72.50 | 23.95 |
September | 115.83 | 23.52 | 113.33 | 23.72 | 41.00 | 23.74 |
October | 333.83 | 21.88 | 15.50 | 21.84 | 15.50 | 21.81 |
November | 330.00 | 21.22 | 145.50 | 21.18 | 145.50 | 21.17 |
December | 338.00 | 21.11 | 316.50 | 21.11 | 316.50 | 21.11 |
Annual Sum or Average | 3109.50 | 21.80 | 2204.67 | 21.92 | 1715.33 | 21.84 |
Minimum of Months | 80.00 | 21.11 | 10.50 | 21.11 | 10.50 | 21.11 |
Maximum of Months | 348.00 | 23.97 | 329.83 | 23.96 | 329.83 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 335.33 | 21.11 | 335.33 | 21.11 |
February | 308.00 | 21.11 | 308.00 | 21.11 | 308.00 | 21.11 |
March | 348.00 | 21.26 | 277.83 | 21.19 | 277.83 | 21.17 |
April | 330.00 | 21.18 | 164.67 | 21.16 | 164.67 | 21.15 |
May | 344.00 | 22.01 | 31.33 | 21.94 | 31.33 | 21.88 |
June | 190.00 | 23.40 | 124.50 | 23.60 | 61.00 | 23.64 |
July | 101.17 | 23.95 | 280.00 | 23.94 | 96.50 | 23.95 |
August | 93.00 | 23.80 | 218.50 | 23.90 | 69.67 | 23.90 |
September | 153.17 | 23.13 | 98.50 | 23.44 | 38.33 | 23.50 |
October | 340.00 | 21.58 | 41.17 | 21.53 | 41.17 | 21.48 |
November | 330.00 | 21.15 | 209.83 | 21.14 | 209.83 | 21.13 |
December | 338.00 | 21.11 | 332.00 | 21.11 | 332.00 | 21.11 |
Annual Sum or Average | 3215.33 | 21.68 | 2421.67 | 21.80 | 1965.67 | 21.72 |
Minimum of Months | 93.00 | 21.11 | 31.33 | 21.11 | 31.33 | 21.11 |
Maximum of Months | 348.00 | 23.95 | 335.33 | 23.94 | 335.33 | 23.95 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.06960 | 17.47503 | -0.6793 | 14.91006 |
February | 448.00000 | 21.06267 | 17.38066 | -0.6860 | 15.08842 |
March | 497.00000 | 21.27227 | 26.64280 | -0.5120 | 11.77322 |
April | 479.00000 | 21.36399 | 32.66550 | -0.4016 | 8.98942 |
May | 496.00000 | 22.79445 | 37.56458 | -1.0147 | 28.90747 |
June | 481.00000 | 23.80055 | 47.29980 | -0.5200 | 11.31032 |
July | 495.00000 | 23.88888 | 56.45534 | -0.3767 | 8.08871 |
August | 497.00000 | 23.88326 | 51.15973 | -0.4205 | 8.85747 |
September | 479.00000 | 23.75203 | 47.41696 | -0.5373 | 11.75257 |
October | 496.00000 | 22.03397 | 37.56995 | -0.1529 | 7.28308 |
November | 480.00000 | 21.23346 | 30.31645 | -0.4462 | 9.64877 |
December | 496.00000 | 21.06858 | 20.95916 | -0.6387 | 13.78438 |
Annual Sum or Average | 5840.00000 | 22.27560 | 35.34118 | -0.5315 | 12.53545 |
Minimum of Months | 448.00000 | 21.06267 | 17.38066 | -1.0147 | 7.28308 |
Maximum of Months | 497.00000 | 23.88888 | 56.45534 | -0.1529 | 28.90747 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.17538 | 19.98612 | -0.5878 | 12.45653 |
February | 448.00000 | 21.15782 | 19.60107 | -0.5968 | 12.62993 |
March | 497.00000 | 21.56201 | 28.39644 | -0.3925 | 9.65872 |
April | 479.00000 | 21.93859 | 34.44011 | -0.2366 | 7.16791 |
May | 496.00000 | 23.37522 | 37.04819 | -0.8073 | 20.18133 |
June | 481.00000 | 23.83688 | 46.00403 | -0.4973 | 10.52870 |
July | 495.00000 | 23.85249 | 54.11212 | -0.3946 | 8.39433 |
August | 497.00000 | 23.85898 | 49.71582 | -0.4306 | 9.01941 |
September | 479.00000 | 23.83280 | 46.50242 | -0.5044 | 10.64649 |
October | 496.00000 | 22.62629 | 38.34184 | -0.0088 | 6.63479 |
November | 480.00000 | 21.67446 | 32.41660 | -0.3134 | 7.87195 |
December | 496.00000 | 21.22646 | 23.23646 | -0.5428 | 11.44935 |
Annual Sum or Average | 5840.00000 | 22.51742 | 35.90408 | -0.4421 | 10.55316 |
Minimum of Months | 448.00000 | 21.15782 | 19.60107 | -0.8073 | 6.63479 |
Maximum of Months | 497.00000 | 23.85898 | 54.11212 | -0.0088 | 20.18133 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10988 | 16.45538 | -0.6356 | 13.60966 |
February | 336.00000 | 21.10982 | 16.39265 | -0.6372 | 13.63879 |
March | 379.00000 | 21.36828 | 25.44659 | -0.4516 | 10.61141 |
April | 360.00000 | 21.52358 | 31.31020 | -0.3383 | 8.07952 |
May | 375.00000 | 23.15439 | 35.70805 | -0.8785 | 23.25076 |
June | 366.00000 | 23.93314 | 46.35545 | -0.4664 | 10.08687 |
July | 369.00000 | 24.01687 | 55.86162 | -0.3341 | 7.60350 |
August | 379.00000 | 23.99616 | 50.44763 | -0.3838 | 8.34060 |
September | 360.00000 | 23.86760 | 46.43790 | -0.4937 | 10.64509 |
October | 371.00000 | 22.21545 | 36.17371 | -0.1034 | 7.04790 |
November | 360.00000 | 21.28383 | 29.72147 | -0.4113 | 9.00523 |
December | 369.00000 | 21.11054 | 20.19594 | -0.5969 | 12.63292 |
Annual Sum or Average | 4395.00000 | 22.40209 | 34.33632 | -0.4769 | 11.21507 |
Minimum of Months | 336.00000 | 21.10982 | 16.39265 | -0.8785 | 7.04790 |
Maximum of Months | 379.00000 | 24.01687 | 55.86162 | -0.1034 | 23.25076 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10995 | 16.45548 | -0.6442 | 13.84248 |
February | 336.00000 | 21.10990 | 16.39265 | -0.6453 | 13.86012 |
March | 379.00000 | 21.35474 | 25.48949 | -0.4625 | 10.78386 |
April | 360.00000 | 21.47925 | 31.38745 | -0.3557 | 8.27531 |
May | 375.00000 | 23.07092 | 35.87904 | -0.9130 | 24.68619 |
June | 366.00000 | 23.92980 | 46.40781 | -0.4689 | 10.14754 |
July | 369.00000 | 24.01663 | 55.90755 | -0.3335 | 7.59426 |
August | 379.00000 | 23.99566 | 50.49260 | -0.3834 | 8.33496 |
September | 360.00000 | 23.85830 | 46.49426 | -0.4987 | 10.78261 |
October | 371.00000 | 22.14509 | 36.34380 | -0.1257 | 7.09792 |
November | 360.00000 | 21.25981 | 29.77496 | -0.4259 | 9.21674 |
December | 369.00000 | 21.11014 | 20.19719 | -0.6056 | 12.85520 |
Annual Sum or Average | 4395.00000 | 22.38113 | 34.39650 | -0.4879 | 11.46029 |
Minimum of Months | 336.00000 | 21.10990 | 16.39265 | -0.9130 | 7.09792 |
Maximum of Months | 379.00000 | 24.01663 | 55.90755 | -0.1257 | 24.68619 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10994 | 16.45556 | -0.6558 | 14.16386 |
February | 336.00000 | 21.10988 | 16.39255 | -0.6568 | 14.18169 |
March | 379.00000 | 21.33261 | 25.55865 | -0.4791 | 11.04959 |
April | 360.00000 | 21.40954 | 31.50890 | -0.3812 | 8.58019 |
May | 375.00000 | 22.91400 | 36.20895 | -0.9740 | 27.20912 |
June | 366.00000 | 23.91107 | 46.56282 | -0.4818 | 10.45569 |
July | 369.00000 | 24.01207 | 56.06488 | -0.3394 | 7.67162 |
August | 379.00000 | 23.99006 | 50.60142 | -0.3903 | 8.44310 |
September | 360.00000 | 23.82664 | 46.67131 | -0.5149 | 11.22394 |
October | 371.00000 | 22.02955 | 36.62473 | -0.1593 | 7.16797 |
November | 360.00000 | 21.22923 | 29.84532 | -0.4442 | 9.49772 |
December | 369.00000 | 21.10992 | 20.19798 | -0.6174 | 13.16217 |
Annual Sum or Average | 4395.00000 | 22.34283 | 34.52011 | -0.5073 | 11.90749 |
Minimum of Months | 336.00000 | 21.10988 | 16.39255 | -0.9740 | 7.16797 |
Maximum of Months | 379.00000 | 24.01207 | 56.06488 | -0.1593 | 27.20912 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 18.01656 | -0.6870 | 15.04407 |
February | 308.00000 | 21.11000 | 17.90989 | -0.6881 | 15.06184 |
March | 348.00000 | 21.30501 | 27.28599 | -0.5119 | 11.66097 |
April | 330.00000 | 21.30814 | 33.30605 | -0.4226 | 9.15217 |
May | 344.00000 | 22.63115 | 38.22673 | -1.0784 | 31.58385 |
June | 336.00000 | 23.82820 | 47.78474 | -0.5179 | 11.24821 |
July | 338.00000 | 23.93661 | 56.67021 | -0.3685 | 8.02426 |
August | 348.00000 | 23.91550 | 51.38465 | -0.4194 | 8.88047 |
September | 330.00000 | 23.73672 | 48.04757 | -0.5519 | 12.16807 |
October | 340.00000 | 21.83377 | 38.65863 | -0.2134 | 7.35534 |
November | 330.00000 | 21.19589 | 31.48595 | -0.4788 | 10.10725 |
December | 338.00000 | 21.11000 | 21.69277 | -0.6489 | 13.99846 |
Annual Sum or Average | 4030.00000 | 22.26206 | 36.00313 | -0.5485 | 12.86905 |
Minimum of Months | 308.00000 | 21.11000 | 17.90989 | -1.0784 | 7.35534 |
Maximum of Months | 348.00000 | 23.93661 | 56.67021 | -0.2134 | 31.58385 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 17.85392 | -0.6809 | 14.86295 |
February | 308.00000 | 21.11000 | 17.74579 | -0.6823 | 14.89027 |
March | 348.00000 | 21.34293 | 26.99534 | -0.5059 | 11.61725 |
April | 330.00000 | 21.43809 | 32.91503 | -0.4054 | 8.99147 |
May | 344.00000 | 22.96194 | 37.26839 | -1.0094 | 28.47112 |
June | 336.00000 | 23.88142 | 47.75561 | -0.5194 | 11.15060 |
July | 338.00000 | 23.94495 | 57.60974 | -0.3783 | 8.20660 |
August | 348.00000 | 23.92686 | 51.96951 | -0.4298 | 9.07783 |
September | 330.00000 | 23.82313 | 47.81232 | -0.5438 | 11.74415 |
October | 340.00000 | 22.05285 | 37.90572 | -0.1815 | 7.30677 |
November | 330.00000 | 21.24257 | 31.20097 | -0.4730 | 10.07802 |
December | 338.00000 | 21.11028 | 21.53190 | -0.6441 | 13.86058 |
Annual Sum or Average | 4030.00000 | 22.33973 | 35.84521 | -0.5374 | 12.52945 |
Minimum of Months | 308.00000 | 21.11000 | 17.74579 | -1.0094 | 7.30677 |
Maximum of Months | 348.00000 | 23.94495 | 57.60974 | -0.1815 | 28.47112 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 17.85479 | -0.6833 | 14.93189 |
February | 308.00000 | 21.11000 | 17.74673 | -0.6845 | 14.95464 |
March | 348.00000 | 21.33837 | 27.01087 | -0.5103 | 11.70288 |
April | 330.00000 | 21.42200 | 32.94408 | -0.4128 | 9.10269 |
May | 344.00000 | 22.91303 | 37.38808 | -1.0302 | 29.34074 |
June | 336.00000 | 23.87615 | 47.82640 | -0.5262 | 11.31999 |
July | 338.00000 | 23.94435 | 57.66219 | -0.3816 | 8.25958 |
August | 348.00000 | 23.92622 | 52.00286 | -0.4331 | 9.13759 |
September | 330.00000 | 23.81632 | 47.86186 | -0.5493 | 11.89573 |
October | 340.00000 | 22.02933 | 37.96785 | -0.1893 | 7.34499 |
November | 330.00000 | 21.23753 | 31.21390 | -0.4775 | 10.15852 |
December | 338.00000 | 21.11011 | 21.53305 | -0.6466 | 13.92906 |
Annual Sum or Average | 4030.00000 | 22.33033 | 35.88292 | -0.5433 | 12.68261 |
Minimum of Months | 308.00000 | 21.11000 | 17.74673 | -1.0302 | 7.34499 |
Maximum of Months | 348.00000 | 23.94435 | 57.66219 | -0.1893 | 29.34074 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 17.85648 | -0.6962 | 15.31389 |
February | 308.00000 | 21.11000 | 17.74849 | -0.6968 | 15.31600 |
March | 348.00000 | 21.31769 | 27.08375 | -0.5293 | 12.07141 |
April | 330.00000 | 21.35207 | 33.06908 | -0.4424 | 9.55278 |
May | 344.00000 | 22.68820 | 37.92451 | -1.1189 | 33.19578 |
June | 336.00000 | 23.84589 | 48.09216 | -0.5500 | 11.99150 |
July | 338.00000 | 23.94265 | 57.82667 | -0.3871 | 8.34962 |
August | 348.00000 | 23.92357 | 52.11643 | -0.4389 | 9.25157 |
September | 330.00000 | 23.77602 | 48.07613 | -0.5713 | 12.59825 |
October | 340.00000 | 21.91553 | 38.26674 | -0.2243 | 7.51606 |
November | 330.00000 | 21.21541 | 31.26780 | -0.4945 | 10.46082 |
December | 338.00000 | 21.10982 | 21.53526 | -0.6591 | 14.27765 |
Annual Sum or Average | 4030.00000 | 22.28600 | 36.03864 | -0.5671 | 13.33953 |
Minimum of Months | 308.00000 | 21.10982 | 17.74849 | -1.1189 | 7.51606 |
Maximum of Months | 348.00000 | 23.94265 | 57.82667 | -0.2243 | 33.19578 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 17.54611 | -0.7602 | 17.31530 |
February | 308.00000 | 21.11000 | 17.49664 | -0.7587 | 17.24442 |
March | 348.00000 | 21.25983 | 27.00625 | -0.6011 | 13.71351 |
April | 330.00000 | 21.18123 | 33.01766 | -0.5272 | 11.11929 |
May | 344.00000 | 22.01016 | 39.48579 | -1.3543 | 44.30113 |
June | 336.00000 | 23.62815 | 48.76854 | -0.6407 | 15.05246 |
July | 338.00000 | 23.93012 | 57.45175 | -0.3998 | 8.55176 |
August | 348.00000 | 23.88414 | 51.86388 | -0.4561 | 9.68145 |
September | 330.00000 | 23.54069 | 48.73134 | -0.6522 | 15.56195 |
October | 340.00000 | 21.57591 | 38.87743 | -0.3174 | 8.25421 |
November | 330.00000 | 21.15167 | 31.15265 | -0.5497 | 11.59109 |
December | 338.00000 | 21.11000 | 21.28012 | -0.7178 | 16.02200 |
Annual Sum or Average | 4030.00000 | 22.13340 | 36.19306 | -0.6445 | 15.72689 |
Minimum of Months | 308.00000 | 21.11000 | 17.49664 | -1.3543 | 8.25421 |
Maximum of Months | 348.00000 | 23.93012 | 57.45175 | -0.3174 | 44.30113 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.180236E+09 | 47807860.71 | 15.00 | 0.150336E+09 | 29899186.31 | 0.00 | 0.41 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 6038.64 | 15-MAR-14:00 | 5386.93 | 15-MAR-14:00 | 1055.82 | 14-MAR-13:30 | 1591.07 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.585501E+09 | 0.150897E+09 | 60.08 | 0.510271E+09 | 75229874.53 | 0.00 | 0.54 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 8672.83 | 14-MAY-15:00 | 6616.01 | 14-MAY-15:00 | 2151.23 | 14-MAY-14:20 | 2170.80 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.703558E+10 | 0.168627E+10 | 292.00 | 0.497668E+10 | 0.205891E+10 | 0.00 | 1.00 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 | 26018.22 | 18-JUN-07:03 | 12836.17 | 12-JUN-14:00 | 13599.83 | 18-JUN-07:03 | 5220.00 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.157051E+11 | 0.367601E+10 | 469.71 | 0.102858E+11 | 0.541932E+10 | 0.00 | 1.00 | 15-JUL-07:03 | 0.00 | 01-JUL-00:10 | 40790.28 | 21-JUL-07:02 | 23410.94 | 20-JUL-07:02 | 22408.86 | 22-JUL-07:03 | 8271.19 | 21-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.121948E+11 | 0.291161E+10 | 418.88 | 0.893989E+10 | 0.325493E+10 | 0.00 | 1.00 | 06-AUG-07:03 | 0.00 | 01-AUG-00:10 | 39982.28 | 14-AUG-07:03 | 22408.49 | 14-AUG-07:03 | 20121.93 | 15-AUG-07:03 | 8031.99 | 14-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.418369E+10 | 0.100527E+10 | 217.12 | 0.280903E+10 | 0.137466E+10 | 0.00 | 1.00 | 16-SEP-07:03 | 0.00 | 01-SEP-00:10 | 39041.35 | 17-SEP-07:03 | 21283.12 | 17-SEP-07:03 | 17758.23 | 17-SEP-07:03 | 7856.21 | 17-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 92671999.68 | 24198326.90 | 13.00 | 78935935.29 | 13736064.39 | 0.00 | 0.25 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 | 3514.27 | 11-OCT-16:10 | 2945.50 | 11-OCT-16:10 | 581.92 | 11-OCT-17:10 | 900.75 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.399776E+11 | 0.950207E+10 | 1485.79 | 0.277509E+11 | 0.122267E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.157051E+11 | 0.367601E+10 | 469.71 | 0.102858E+11 | 0.541932E+10 | 0.00 | 1.00 | 0.00 | 40790.28 | 23410.94 | 22408.86 | 8271.19 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.135493E+09 | 35226949.42 | 16.93 | 0.113497E+09 | 21996000.26 | 0.00 | 1.00 | 15-MAR-20:01 | 0.00 | 01-MAR-00:05 | 19093.58 | 15-MAR-20:01 | 15507.14 | 15-MAR-20:01 | 3586.44 | 15-MAR-20:01 | 3872.09 | 15-MAR-20:01 | 0.00 | 01-MAR-00:05 |
April | 2339604.43 | 608559.75 | 1.17 | 2034980.04 | 304624.38 | 0.00 | 0.24 | 09-APR-17:20 | 0.00 | 01-APR-00:10 | 1807.07 | 09-APR-17:20 | 1483.10 | 09-APR-17:20 | 323.97 | 09-APR-17:20 | 459.23 | 09-APR-17:20 | 0.00 | 01-APR-00:10 |
May | 0.473112E+09 | 0.118278E+09 | 71.27 | 0.416613E+09 | 56499012.39 | 0.00 | 1.00 | 13-MAY-18:01 | 0.00 | 01-MAY-00:10 | 19636.16 | 14-MAY-18:00 | 17901.66 | 23-MAY-22:51 | 7012.69 | 14-MAY-18:00 | 3978.02 | 14-MAY-18:00 | 0.00 | 01-MAY-00:10 |
June | 0.458583E+10 | 0.106668E+10 | 288.03 | 0.330479E+10 | 0.128104E+10 | 0.00 | 1.00 | 01-JUN-20:02 | 0.00 | 01-JUN-00:10 | 21294.51 | 17-JUN-19:03 | 18271.79 | 30-JUN-20:01 | 11290.69 | 27-JUN-20:33 | 4278.29 | 17-JUN-21:47 | 0.00 | 01-JUN-00:10 |
July | 0.964416E+10 | 0.220049E+10 | 433.05 | 0.641453E+10 | 0.322964E+10 | 0.00 | 1.00 | 01-JUL-18:03 | 0.00 | 01-JUL-00:10 | 21275.85 | 21-JUL-20:05 | 16306.62 | 06-JUL-20:10 | 11422.65 | 28-JUL-20:03 | 4401.44 | 21-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.746312E+10 | 0.173904E+10 | 397.75 | 0.549343E+10 | 0.196969E+10 | 0.00 | 1.00 | 01-AUG-20:02 | 0.00 | 01-AUG-00:10 | 21181.79 | 15-AUG-07:03 | 17463.32 | 03-AUG-20:02 | 11660.63 | 28-AUG-20:03 | 4256.40 | 15-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.274724E+10 | 0.642021E+09 | 225.74 | 0.186348E+10 | 0.883762E+09 | 0.00 | 1.00 | 03-SEP-17:02 | 0.00 | 01-SEP-00:10 | 21157.46 | 15-SEP-20:03 | 16208.67 | 07-SEP-20:10 | 11395.05 | 15-SEP-20:03 | 4220.21 | 15-SEP-20:03 | 0.00 | 01-SEP-00:10 |
October | 82895049.13 | 20785688.08 | 16.68 | 70668689.43 | 12226359.70 | 0.00 | 1.00 | 22-OCT-17:01 | 0.00 | 01-OCT-00:10 | 19080.83 | 22-OCT-17:09 | 15218.13 | 22-OCT-17:01 | 4041.26 | 22-OCT-17:20 | 3869.42 | 22-OCT-17:09 | 0.00 | 01-OCT-00:10 |
November | 713206.56 | 189530.71 | 0.56 | 570412.43 | 142794.13 | 0.00 | 0.10 | 04-NOV-18:40 | 0.00 | 01-NOV-00:10 | 728.05 | 04-NOV-18:40 | 554.53 | 04-NOV-18:40 | 173.52 | 04-NOV-18:40 | 192.29 | 04-NOV-18:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.251349E+11 | 0.582332E+10 | 1451.17 | 0.176796E+11 | 0.745530E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.964416E+10 | 0.220049E+10 | 433.05 | 0.641453E+10 | 0.322964E+10 | 0.00 | 1.00 | 0.00 | 21294.51 | 18271.79 | 11660.63 | 4401.44 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.110457E+09 | 29232402.81 | 15.33 | 95744007.97 | 14713354.04 | 0.00 | 0.40 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 3342.30 | 15-MAR-14:00 | 3109.48 | 15-MAR-14:00 | 594.27 | 14-MAR-13:00 | 882.44 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.343076E+09 | 88248001.33 | 61.67 | 0.307949E+09 | 35127412.89 | 0.00 | 0.48 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4292.42 | 14-MAY-15:00 | 3421.13 | 14-MAY-15:00 | 997.34 | 14-MAY-14:00 | 1093.41 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.303468E+10 | 0.733020E+09 | 229.31 | 0.225739E+10 | 0.777297E+09 | 0.00 | 1.00 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 | 20254.37 | 18-JUN-07:03 | 10043.28 | 18-JUN-07:03 | 10211.09 | 18-JUN-07:03 | 4053.80 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.648138E+10 | 0.153102E+10 | 343.69 | 0.445416E+10 | 0.202722E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:10 | 22956.33 | 21-JUL-06:02 | 14873.86 | 15-JUL-06:03 | 12040.29 | 22-JUL-06:03 | 4637.56 | 21-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.517001E+10 | 0.124756E+10 | 325.74 | 0.399735E+10 | 0.117265E+10 | 0.00 | 1.00 | 06-AUG-07:03 | 0.00 | 01-AUG-00:10 | 22866.20 | 14-AUG-06:03 | 12968.09 | 06-AUG-07:03 | 12687.54 | 14-AUG-06:03 | 4516.35 | 14-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.182825E+10 | 0.441585E+09 | 178.62 | 0.128861E+10 | 0.539642E+09 | 0.00 | 1.00 | 14-SEP-06:03 | 0.00 | 01-SEP-00:10 | 22029.16 | 17-SEP-07:03 | 12371.56 | 17-SEP-07:03 | 9657.61 | 17-SEP-07:03 | 4430.31 | 17-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 38507607.01 | 10103524.15 | 12.17 | 34599937.13 | 3907669.88 | 0.00 | 0.22 | 11-OCT-13:00 | 0.00 | 01-OCT-00:10 | 1765.23 | 11-OCT-13:00 | 1644.74 | 11-OCT-13:00 | 209.98 | 11-OCT-16:10 | 458.87 | 11-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.170064E+11 | 0.408077E+10 | 1166.52 | 0.124358E+11 | 0.457056E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.648138E+10 | 0.153102E+10 | 343.69 | 0.445416E+10 | 0.202722E+10 | 0.00 | 1.00 | 0.00 | 22956.33 | 14873.86 | 12687.54 | 4637.56 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.101397E+09 | 26935827.89 | 14.50 | 88290310.93 | 13106619.82 | 0.00 | 0.38 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 3176.55 | 15-MAR-14:00 | 2962.65 | 15-MAR-14:00 | 542.51 | 14-MAR-13:00 | 842.11 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.316423E+09 | 81676109.96 | 59.00 | 0.284661E+09 | 31761838.43 | 0.00 | 0.47 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4090.78 | 14-MAY-15:00 | 3259.83 | 14-MAY-15:00 | 944.01 | 14-MAY-14:00 | 1046.72 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.300890E+10 | 0.726408E+09 | 227.81 | 0.224176E+10 | 0.767142E+09 | 0.00 | 1.00 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 | 19795.43 | 18-JUN-07:03 | 9828.04 | 18-JUN-07:03 | 9967.39 | 18-JUN-07:03 | 3962.18 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.647884E+10 | 0.152850E+10 | 344.02 | 0.446106E+10 | 0.201778E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:10 | 22771.29 | 21-JUL-06:02 | 14813.47 | 15-JUL-06:03 | 11920.01 | 22-JUL-06:03 | 4598.85 | 21-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.516462E+10 | 0.124490E+10 | 325.74 | 0.400237E+10 | 0.116225E+10 | 0.00 | 1.00 | 06-AUG-07:03 | 0.00 | 01-AUG-00:10 | 22676.25 | 14-AUG-06:03 | 13148.35 | 06-AUG-07:03 | 12559.64 | 14-AUG-06:03 | 4478.66 | 14-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.180270E+10 | 0.435316E+09 | 176.12 | 0.127305E+10 | 0.529645E+09 | 0.00 | 1.00 | 14-SEP-06:03 | 0.00 | 01-SEP-00:10 | 21845.55 | 17-SEP-07:03 | 12301.35 | 17-SEP-07:03 | 9544.20 | 17-SEP-07:03 | 4393.34 | 17-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 30527036.82 | 8057411.47 | 11.00 | 27549037.03 | 2977999.79 | 0.00 | 0.19 | 11-OCT-13:00 | 0.00 | 01-OCT-00:10 | 1501.38 | 11-OCT-13:00 | 1403.80 | 11-OCT-13:00 | 176.95 | 11-OCT-16:10 | 393.41 | 11-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.169034E+11 | 0.405179E+10 | 1158.19 | 0.123787E+11 | 0.452466E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.647884E+10 | 0.152850E+10 | 344.02 | 0.446106E+10 | 0.201778E+10 | 0.00 | 1.00 | 0.00 | 22771.29 | 14813.47 | 12559.64 | 4598.85 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 88131686.51 | 23571282.71 | 13.67 | 76621878.78 | 11509807.74 | 0.00 | 0.36 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 2928.76 | 15-MAR-14:00 | 2717.68 | 15-MAR-14:00 | 475.12 | 14-MAR-13:00 | 782.65 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.266404E+09 | 69314152.20 | 52.17 | 0.238849E+09 | 27554510.98 | 0.00 | 0.43 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 3786.38 | 14-MAY-15:00 | 2993.11 | 14-MAY-15:00 | 885.27 | 14-MAY-14:00 | 977.65 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.287499E+10 | 0.697099E+09 | 218.56 | 0.213148E+10 | 0.743512E+09 | 0.00 | 1.00 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 | 16780.40 | 18-JUN-07:03 | 8224.71 | 18-JUN-07:03 | 8555.70 | 18-JUN-07:03 | 3361.35 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.628231E+10 | 0.148881E+10 | 342.22 | 0.431212E+10 | 0.197019E+10 | 0.00 | 1.00 | 15-JUL-06:03 | 0.00 | 01-JUL-00:10 | 22887.61 | 21-JUL-06:02 | 13604.45 | 20-JUL-06:02 | 12032.20 | 22-JUL-06:03 | 4625.18 | 21-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.500028E+10 | 0.121056E+10 | 321.86 | 0.386586E+10 | 0.113443E+10 | 0.00 | 1.00 | 06-AUG-07:03 | 0.00 | 01-AUG-00:10 | 22802.77 | 14-AUG-06:03 | 12112.59 | 07-AUG-06:03 | 12677.21 | 14-AUG-06:03 | 4504.23 | 14-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.169358E+10 | 0.410771E+09 | 166.54 | 0.119130E+10 | 0.502286E+09 | 0.00 | 1.00 | 14-SEP-06:03 | 0.00 | 01-SEP-00:10 | 21967.39 | 17-SEP-07:03 | 12311.26 | 17-SEP-07:03 | 9656.13 | 17-SEP-07:03 | 4418.21 | 17-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 20549901.52 | 5468430.15 | 9.50 | 18508011.17 | 2041890.35 | 0.00 | 0.15 | 11-OCT-13:00 | 0.00 | 01-OCT-00:10 | 1158.75 | 11-OCT-13:00 | 1078.89 | 11-OCT-13:00 | 142.52 | 11-OCT-16:10 | 307.09 | 11-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.162263E+11 | 0.390559E+10 | 1124.51 | 0.118347E+11 | 0.439152E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.628231E+10 | 0.148881E+10 | 342.22 | 0.431212E+10 | 0.197019E+10 | 0.00 | 1.00 | 0.00 | 22887.61 | 13604.45 | 12677.21 | 4625.18 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.152757E+09 | 40685409.48 | 12.67 | 0.125729E+09 | 27028237.07 | 0.00 | 0.40 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 5930.38 | 15-MAR-14:10 | 5227.32 | 15-MAR-14:10 | 986.61 | 14-MAR-13:00 | 1559.18 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.469204E+09 | 0.121668E+09 | 46.83 | 0.407425E+09 | 61779243.28 | 0.00 | 0.51 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 8008.55 | 14-MAY-15:00 | 6008.39 | 14-MAY-15:00 | 2064.77 | 14-MAY-14:30 | 2017.69 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.537695E+10 | 0.128673E+10 | 212.94 | 0.380157E+10 | 0.157538E+10 | 0.00 | 1.00 | 18-JUN-08:63 | 0.00 | 01-JUN-00:10 | 34390.18 | 18-JUN-08:63 | 18039.31 | 18-JUN-08:63 | 16350.87 | 18-JUN-08:63 | 6957.77 | 18-JUN-08:63 | 0.00 | 01-JUN-00:10 |
July | 0.119117E+11 | 0.277859E+10 | 336.34 | 0.784077E+10 | 0.407089E+10 | 0.00 | 1.00 | 15-JUL-07:03 | 0.00 | 01-JUL-00:10 | 39887.47 | 16-JUL-08:62 | 23741.34 | 20-JUL-07:02 | 21199.22 | 22-JUL-07:03 | 8132.06 | 21-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.948224E+10 | 0.226261E+10 | 313.39 | 0.704130E+10 | 0.244094E+10 | 0.00 | 1.00 | 06-AUG-08:63 | 0.00 | 01-AUG-00:10 | 39931.96 | 14-AUG-07:03 | 21060.17 | 07-AUG-07:03 | 19734.40 | 15-AUG-07:03 | 7923.24 | 14-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.314363E+10 | 0.755073E+09 | 160.06 | 0.213183E+10 | 0.101180E+10 | 0.00 | 1.00 | 16-SEP-07:03 | 0.00 | 01-SEP-00:10 | 33406.40 | 17-SEP-08:63 | 17591.67 | 17-SEP-08:63 | 15814.73 | 17-SEP-08:63 | 6696.11 | 17-SEP-08:63 | 0.00 | 01-SEP-00:10 |
October | 39165573.16 | 10380586.79 | 7.33 | 33702446.82 | 5463126.34 | 0.00 | 0.19 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2670.27 | 11-OCT-15:00 | 2275.44 | 11-OCT-15:00 | 394.83 | 11-OCT-15:00 | 699.58 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.305756E+11 | 0.725574E+10 | 1089.56 | 0.213823E+11 | 0.919328E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.119117E+11 | 0.277859E+10 | 336.34 | 0.784077E+10 | 0.407089E+10 | 0.00 | 1.00 | 0.00 | 39931.96 | 23741.34 | 21199.22 | 8132.06 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.102152E+09 | 23545957.42 | 14.00 | 88262180.33 | 13890181.32 | 0.00 | 0.41 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 3509.55 | 15-MAR-14:10 | 3245.98 | 15-MAR-14:10 | 575.57 | 14-MAR-13:00 | 801.41 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 37.96 | 8.96 | 0.17 | 35.36 | 2.60 | 0.00 | 0.00 | 08-APR-13:00 | 0.00 | 01-APR-00:10 | 0.06 | 08-APR-13:00 | 0.06 | 08-APR-13:00 | 0.00 | 08-APR-13:00 | 0.01 | 08-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.263208E+09 | 59330313.02 | 47.17 | 0.234694E+09 | 28513994.98 | 0.00 | 0.52 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4664.68 | 14-MAY-15:00 | 3665.21 | 14-MAY-15:00 | 1030.10 | 14-MAY-14:30 | 1021.89 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.290273E+10 | 0.608561E+09 | 195.08 | 0.215603E+10 | 0.746703E+09 | 0.00 | 1.00 | 18-JUN-08:63 | 0.00 | 01-JUN-00:10 | 17209.82 | 18-JUN-08:63 | 9133.60 | 18-JUN-08:63 | 8076.22 | 18-JUN-08:63 | 3168.97 | 18-JUN-08:63 | 0.00 | 01-JUN-00:10 |
July | 0.644608E+10 | 0.132175E+10 | 329.68 | 0.446022E+10 | 0.198586E+10 | 0.00 | 1.00 | 15-JUL-07:03 | 0.00 | 01-JUL-00:10 | 20904.74 | 16-JUL-08:62 | 12371.42 | 20-JUL-07:02 | 11115.48 | 22-JUL-07:03 | 3931.24 | 21-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.510184E+10 | 0.106856E+10 | 300.21 | 0.397970E+10 | 0.112215E+10 | 0.00 | 1.00 | 06-AUG-08:63 | 0.00 | 01-AUG-00:10 | 20933.03 | 14-AUG-07:03 | 11047.50 | 07-AUG-07:03 | 10336.30 | 15-AUG-07:03 | 3830.44 | 14-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.159442E+10 | 0.335254E+09 | 142.22 | 0.113384E+10 | 0.460577E+09 | 0.00 | 1.00 | 17-SEP-08:63 | 0.00 | 01-SEP-00:10 | 16093.88 | 17-SEP-08:63 | 8579.75 | 17-SEP-08:63 | 7514.13 | 17-SEP-08:63 | 2926.87 | 17-SEP-08:63 | 0.00 | 01-SEP-00:10 |
October | 19674317.95 | 4559075.71 | 9.50 | 18033357.80 | 1640960.15 | 0.00 | 0.18 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1434.60 | 11-OCT-15:00 | 1299.09 | 11-OCT-15:00 | 135.51 | 11-OCT-15:00 | 328.69 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.164301E+11 | 0.342156E+10 | 1038.03 | 0.120708E+11 | 0.435933E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.644608E+10 | 0.132175E+10 | 329.68 | 0.446022E+10 | 0.198586E+10 | 0.00 | 1.00 | 0.00 | 20933.03 | 12371.42 | 11115.48 | 3931.24 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 98898363.66 | 22821826.61 | 13.67 | 85438228.85 | 13460134.81 | 0.00 | 0.41 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 3457.16 | 15-MAR-14:10 | 3194.36 | 15-MAR-14:10 | 553.04 | 14-MAR-13:00 | 790.15 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 2779.79 | 656.20 | 0.33 | 2482.82 | 296.97 | 0.00 | 0.00 | 08-APR-15:10 | 0.00 | 01-APR-00:10 | 4.46 | 08-APR-15:10 | 3.98 | 08-APR-15:10 | 0.48 | 08-APR-15:10 | 1.05 | 08-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 0.248677E+09 | 56159905.84 | 45.17 | 0.221184E+09 | 27492644.09 | 0.00 | 0.51 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4563.48 | 14-MAY-15:00 | 3579.18 | 14-MAY-15:00 | 1012.55 | 14-MAY-14:30 | 1001.63 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.284788E+10 | 0.597564E+09 | 193.47 | 0.211081E+10 | 0.737065E+09 | 0.00 | 1.00 | 18-JUN-08:63 | 0.00 | 01-JUN-00:10 | 15881.40 | 18-JUN-08:63 | 8408.63 | 18-JUN-08:63 | 7472.77 | 18-JUN-08:63 | 2907.53 | 18-JUN-08:63 | 0.00 | 01-JUN-00:10 |
July | 0.636894E+10 | 0.130648E+10 | 328.01 | 0.440167E+10 | 0.196727E+10 | 0.00 | 1.00 | 15-JUL-07:03 | 0.00 | 01-JUL-00:10 | 20769.49 | 16-JUL-08:62 | 12255.81 | 20-JUL-07:02 | 11054.52 | 22-JUL-07:03 | 3906.31 | 21-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.504268E+10 | 0.105652E+10 | 300.25 | 0.393040E+10 | 0.111228E+10 | 0.00 | 1.00 | 06-AUG-08:63 | 0.00 | 01-AUG-00:10 | 20796.85 | 14-AUG-07:03 | 10968.23 | 07-AUG-07:03 | 10281.91 | 15-AUG-07:03 | 3806.09 | 14-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.156543E+10 | 0.329338E+09 | 139.97 | 0.111228E+10 | 0.453152E+09 | 0.00 | 1.00 | 17-SEP-08:63 | 0.00 | 01-SEP-00:10 | 15542.24 | 17-SEP-08:63 | 8286.15 | 17-SEP-08:63 | 7256.09 | 17-SEP-08:63 | 2819.90 | 17-SEP-08:63 | 0.00 | 01-SEP-00:10 |
October | 18479774.64 | 4287551.86 | 9.33 | 16924470.69 | 1555303.94 | 0.00 | 0.18 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1379.39 | 11-OCT-15:00 | 1247.81 | 11-OCT-15:00 | 131.58 | 11-OCT-15:00 | 316.51 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.161910E+11 | 0.337317E+10 | 1030.21 | 0.118787E+11 | 0.431228E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.636894E+10 | 0.130648E+10 | 328.01 | 0.440167E+10 | 0.196727E+10 | 0.00 | 1.00 | 0.00 | 20796.85 | 12255.81 | 11054.52 | 3906.31 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 85345177.90 | 19807571.66 | 12.50 | 73774678.40 | 11570499.50 | 0.00 | 0.39 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 3232.01 | 15-MAR-14:10 | 2977.74 | 15-MAR-14:10 | 476.06 | 14-MAR-14:10 | 742.71 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 4034.00 | 952.21 | 0.17 | 3724.12 | 309.88 | 0.00 | 0.00 | 08-APR-13:20 | 0.00 | 01-APR-00:10 | 6.72 | 08-APR-13:20 | 6.21 | 08-APR-13:20 | 0.52 | 08-APR-13:20 | 1.59 | 08-APR-13:20 | 0.00 | 01-APR-00:10 |
May | 0.196313E+09 | 44678923.05 | 37.33 | 0.173083E+09 | 23230069.08 | 0.00 | 0.48 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4224.75 | 14-MAY-15:00 | 3296.63 | 14-MAY-15:00 | 949.28 | 14-MAY-14:40 | 934.48 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.268488E+10 | 0.565164E+09 | 188.67 | 0.198036E+10 | 0.704524E+09 | 0.00 | 1.00 | 27-JUN-12:30 | 0.00 | 01-JUN-00:10 | 11320.76 | 27-JUN-13:00 | 7214.82 | 27-JUN-13:00 | 4933.23 | 18-JUN-08:63 | 2232.14 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 0.616706E+10 | 0.126694E+10 | 323.72 | 0.425499E+10 | 0.191207E+10 | 0.00 | 1.00 | 15-JUL-13:30 | 0.00 | 01-JUL-00:10 | 20505.95 | 16-JUL-08:62 | 11981.64 | 20-JUL-07:02 | 10946.47 | 22-JUL-07:03 | 3859.52 | 21-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.489454E+10 | 0.102662E+10 | 296.51 | 0.381297E+10 | 0.108157E+10 | 0.00 | 1.00 | 07-AUG-07:03 | 0.00 | 01-AUG-00:10 | 20531.55 | 14-AUG-07:03 | 10810.09 | 07-AUG-07:03 | 10196.16 | 14-AUG-07:03 | 3760.19 | 14-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.147721E+10 | 0.311364E+09 | 135.39 | 0.104850E+10 | 0.428707E+09 | 0.00 | 1.00 | 17-SEP-08:63 | 0.00 | 01-SEP-00:10 | 13420.96 | 17-SEP-08:63 | 7171.87 | 17-SEP-08:63 | 6249.09 | 17-SEP-08:63 | 2405.54 | 17-SEP-08:63 | 0.00 | 01-SEP-00:10 |
October | 13855455.73 | 3233308.57 | 8.17 | 12674463.47 | 1180992.25 | 0.00 | 0.15 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1173.05 | 11-OCT-15:00 | 1059.81 | 11-OCT-15:00 | 113.24 | 11-OCT-15:00 | 270.82 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.155192E+11 | 0.323781E+10 | 1002.46 | 0.113564E+11 | 0.416285E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.616706E+10 | 0.126694E+10 | 323.72 | 0.425499E+10 | 0.191207E+10 | 0.00 | 1.00 | 0.00 | 20531.55 | 11981.64 | 10946.47 | 3859.52 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 39048904.40 | 10632484.92 | 9.17 | 33145343.17 | 5903561.23 | 0.00 | 0.30 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 2309.96 | 15-MAR-14:10 | 2036.89 | 15-MAR-14:10 | 304.93 | 15-MAR-17:00 | 624.62 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 86115582.65 | 23110412.53 | 25.83 | 72272896.60 | 13842686.05 | 0.00 | 0.37 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 3031.40 | 14-MAY-15:00 | 2244.73 | 14-MAY-15:00 | 788.19 | 14-MAY-14:50 | 792.77 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.231502E+10 | 0.562008E+09 | 178.67 | 0.162512E+10 | 0.689902E+09 | 0.00 | 1.00 | 27-JUN-12:10 | 0.00 | 01-JUN-00:10 | 11251.06 | 27-JUN-13:00 | 6917.88 | 27-JUN-13:00 | 4333.17 | 27-JUN-13:00 | 2515.95 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 0.572159E+10 | 0.134964E+10 | 319.64 | 0.379136E+10 | 0.193023E+10 | 0.00 | 1.00 | 15-JUL-13:30 | 0.00 | 01-JUL-00:10 | 21835.10 | 21-JUL-07:02 | 11048.48 | 20-JUL-07:02 | 12120.54 | 21-JUL-07:02 | 4374.94 | 21-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.462766E+10 | 0.111301E+10 | 290.04 | 0.347453E+10 | 0.115313E+10 | 0.00 | 1.00 | 07-AUG-07:03 | 0.00 | 01-AUG-00:10 | 21615.40 | 14-AUG-07:03 | 10070.90 | 14-AUG-07:03 | 11544.50 | 14-AUG-07:03 | 4266.78 | 14-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.136805E+10 | 0.331626E+09 | 131.58 | 0.933655E+09 | 0.434393E+09 | 0.00 | 0.90 | 17-SEP-08:63 | 0.00 | 01-SEP-00:10 | 8938.94 | 17-SEP-08:63 | 5983.99 | 16-SEP-13:40 | 4403.37 | 17-SEP-08:63 | 1889.71 | 16-SEP-13:50 | 0.00 | 01-SEP-00:10 |
October | 8671234.04 | 2334409.67 | 5.50 | 7526662.89 | 1144571.15 | 0.00 | 0.12 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 898.64 | 11-OCT-15:00 | 770.03 | 11-OCT-15:00 | 128.62 | 11-OCT-15:00 | 239.78 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.141662E+11 | 0.339236E+10 | 960.43 | 0.993761E+10 | 0.422854E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.572159E+10 | 0.134964E+10 | 319.64 | 0.379136E+10 | 0.193023E+10 | 0.00 | 1.00 | 0.00 | 21835.10 | 11048.48 | 12120.54 | 4374.94 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.73 | 67.54 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 36.24 | 65.17 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.90 | 46.55 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 51.19 | 35.35 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 49.14 | 24.29 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 53.13 | 16.41 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 61.29 | 10.80 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.87 | 14.58 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.43 | 23.89 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 58.17 | 35.19 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.20 | 44.80 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.73 | 66.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 50.00 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.73 | 10.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.43 | 67.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.73 | 67.54 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 36.24 | 65.17 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.90 | 46.55 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 51.19 | 35.35 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 49.14 | 24.29 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 53.13 | 16.41 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 61.29 | 10.80 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.87 | 14.58 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.43 | 23.89 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 58.17 | 35.19 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.20 | 44.80 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.73 | 66.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 50.00 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.73 | 10.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.43 | 67.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.73 | 67.54 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 36.24 | 65.17 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.90 | 46.55 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 51.19 | 35.35 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 49.14 | 24.29 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 53.13 | 16.41 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 61.29 | 10.80 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.87 | 14.58 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.43 | 23.89 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 58.17 | 35.19 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.20 | 44.80 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.73 | 66.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 50.00 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.73 | 10.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.43 | 67.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.73 | 67.54 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 36.24 | 65.17 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.90 | 46.55 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 51.19 | 35.35 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 49.14 | 24.29 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 53.13 | 16.41 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 61.29 | 10.80 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.87 | 14.58 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.43 | 23.89 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 58.17 | 35.19 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.20 | 44.80 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.73 | 66.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 50.00 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.73 | 10.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.43 | 67.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.90 | 21.87 | 15.03 | 39.57 | 80.35 | 0.00 | 0.00 | 0.00 |
February | 41.60 | 20.26 | 21.35 | 43.93 | 77.46 | 0.00 | 0.00 | 0.00 |
March | 49.93 | 27.89 | 22.04 | 69.90 | 55.49 | 0.00 | 0.00 | 0.00 |
April | 40.34 | 15.32 | 25.02 | 61.73 | 42.16 | 0.00 | 0.00 | 0.00 |
May | 34.84 | 8.97 | 25.87 | 59.18 | 29.04 | 0.00 | 0.00 | 0.00 |
June | 33.91 | 5.99 | 27.92 | 63.90 | 19.68 | 0.00 | 0.00 | 0.00 |
July | 34.63 | 7.23 | 27.39 | 73.64 | 12.97 | 0.00 | 0.00 | 0.00 |
August | 39.08 | 11.64 | 27.44 | 80.36 | 17.50 | 0.00 | 0.00 | 0.00 |
September | 46.21 | 21.99 | 24.22 | 84.71 | 28.60 | 0.00 | 0.00 | 0.00 |
October | 45.37 | 26.00 | 19.37 | 70.10 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 32.90 | 18.81 | 14.09 | 43.68 | 53.39 | 0.00 | 0.00 | 0.00 |
December | 30.83 | 16.26 | 14.57 | 31.16 | 78.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.86 | 16.84 | 22.02 | 60.25 | 44.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.83 | 5.99 | 14.09 | 31.16 | 12.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.93 | 27.89 | 27.92 | 84.71 | 80.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.90 | 21.87 | 15.03 | 39.57 | 80.35 | 0.00 | 0.00 | 0.00 |
February | 41.60 | 20.26 | 21.35 | 43.93 | 77.46 | 0.00 | 0.00 | 0.00 |
March | 49.93 | 27.89 | 22.04 | 69.90 | 55.49 | 0.00 | 0.00 | 0.00 |
April | 40.34 | 15.32 | 25.02 | 61.73 | 42.16 | 0.00 | 0.00 | 0.00 |
May | 34.84 | 8.97 | 25.87 | 59.18 | 29.04 | 0.00 | 0.00 | 0.00 |
June | 33.91 | 5.99 | 27.92 | 63.90 | 19.68 | 0.00 | 0.00 | 0.00 |
July | 34.63 | 7.23 | 27.39 | 73.64 | 12.97 | 0.00 | 0.00 | 0.00 |
August | 39.08 | 11.64 | 27.44 | 80.36 | 17.50 | 0.00 | 0.00 | 0.00 |
September | 46.21 | 21.99 | 24.22 | 84.71 | 28.60 | 0.00 | 0.00 | 0.00 |
October | 45.37 | 26.00 | 19.37 | 70.10 | 42.03 | 0.00 | 0.00 | 0.00 |
November | 32.90 | 18.81 | 14.09 | 43.68 | 53.39 | 0.00 | 0.00 | 0.00 |
December | 30.83 | 16.26 | 14.57 | 31.16 | 78.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.86 | 16.84 | 22.02 | 60.25 | 44.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.83 | 5.99 | 14.09 | 31.16 | 12.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.93 | 27.89 | 27.92 | 84.71 | 80.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.26 | 69.86 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 35.58 | 67.50 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.03 | 48.80 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 50.22 | 37.84 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 47.97 | 26.25 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.70 | 16.94 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 61.13 | 11.03 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.73 | 14.82 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.09 | 24.45 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 57.43 | 37.16 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 35.70 | 47.06 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.32 | 68.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.43 | 39.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.32 | 11.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.09 | 69.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.26 | 69.86 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 35.58 | 67.50 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.03 | 48.80 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 50.22 | 37.84 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 47.97 | 26.25 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.70 | 16.94 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 61.13 | 11.03 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.73 | 14.82 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.09 | 24.45 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 57.43 | 37.16 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 35.70 | 47.06 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.32 | 68.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.43 | 39.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.32 | 11.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.09 | 69.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.90 | 21.87 | 15.03 | 39.02 | 83.09 | 0.00 | 0.00 | 0.00 |
February | 41.60 | 20.26 | 21.35 | 43.15 | 80.22 | 0.00 | 0.00 | 0.00 |
March | 49.93 | 27.89 | 22.04 | 68.88 | 58.15 | 0.00 | 0.00 | 0.00 |
April | 40.34 | 15.32 | 25.02 | 60.59 | 45.10 | 0.00 | 0.00 | 0.00 |
May | 34.84 | 8.97 | 25.87 | 57.80 | 31.37 | 0.00 | 0.00 | 0.00 |
June | 33.91 | 5.99 | 27.92 | 63.40 | 20.30 | 0.00 | 0.00 | 0.00 |
July | 34.63 | 7.23 | 27.39 | 73.45 | 13.25 | 0.00 | 0.00 | 0.00 |
August | 39.08 | 11.64 | 27.44 | 80.20 | 17.78 | 0.00 | 0.00 | 0.00 |
September | 46.21 | 21.99 | 24.22 | 84.32 | 29.27 | 0.00 | 0.00 | 0.00 |
October | 45.37 | 26.00 | 19.37 | 69.22 | 44.35 | 0.00 | 0.00 | 0.00 |
November | 32.90 | 18.81 | 14.09 | 43.08 | 56.06 | 0.00 | 0.00 | 0.00 |
December | 30.83 | 16.26 | 14.57 | 30.67 | 81.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.86 | 16.84 | 22.02 | 59.58 | 46.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.83 | 5.99 | 14.09 | 30.67 | 13.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.93 | 27.89 | 27.92 | 84.32 | 83.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.33 | 68.83 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 35.65 | 66.46 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.12 | 48.08 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 50.36 | 37.12 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 48.07 | 26.17 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.54 | 17.75 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 60.78 | 12.04 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.54 | 15.85 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.07 | 25.20 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 57.61 | 36.61 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 35.85 | 46.17 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.39 | 67.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.44 | 38.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.39 | 12.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.07 | 68.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.33 | 68.83 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 35.65 | 66.46 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.12 | 48.08 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 50.36 | 37.12 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 48.07 | 26.17 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.54 | 17.75 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 60.78 | 12.04 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.54 | 15.85 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.07 | 25.20 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 57.61 | 36.61 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 35.85 | 46.17 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.39 | 67.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.44 | 38.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.39 | 12.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.07 | 68.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.69 | 21.75 | 14.95 | 38.90 | 81.43 | 0.00 | 0.00 | 0.00 |
February | 41.38 | 20.15 | 21.23 | 43.01 | 78.56 | 0.00 | 0.00 | 0.00 |
March | 49.66 | 27.74 | 21.92 | 68.60 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 40.12 | 15.24 | 24.88 | 60.42 | 44.02 | 0.00 | 0.00 | 0.00 |
May | 34.65 | 8.92 | 25.73 | 57.60 | 31.11 | 0.00 | 0.00 | 0.00 |
June | 33.73 | 5.96 | 27.77 | 62.86 | 21.14 | 0.00 | 0.00 | 0.00 |
July | 34.44 | 7.19 | 27.24 | 72.64 | 14.37 | 0.00 | 0.00 | 0.00 |
August | 38.87 | 11.58 | 27.29 | 79.54 | 18.90 | 0.00 | 0.00 | 0.00 |
September | 45.96 | 21.87 | 24.08 | 83.83 | 29.99 | 0.00 | 0.00 | 0.00 |
October | 45.12 | 25.86 | 19.27 | 69.06 | 43.48 | 0.00 | 0.00 | 0.00 |
November | 32.72 | 18.71 | 14.01 | 43.03 | 54.72 | 0.00 | 0.00 | 0.00 |
December | 30.66 | 16.17 | 14.49 | 30.59 | 79.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.65 | 16.75 | 21.90 | 59.27 | 46.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 5.96 | 14.01 | 30.59 | 14.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.66 | 27.74 | 27.77 | 83.83 | 81.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.38 | 68.27 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 35.72 | 65.93 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.22 | 47.61 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 50.52 | 36.60 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 48.28 | 25.71 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.56 | 17.69 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 60.77 | 12.06 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.54 | 15.86 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.10 | 25.09 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 57.78 | 36.09 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 35.95 | 45.62 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.44 | 67.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.52 | 38.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.44 | 12.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.10 | 68.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.38 | 68.27 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 35.72 | 65.93 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.22 | 47.61 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 50.52 | 36.60 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 48.28 | 25.71 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.56 | 17.69 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 60.77 | 12.06 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.54 | 15.86 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.10 | 25.09 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 57.78 | 36.09 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 35.95 | 45.62 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.44 | 67.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.52 | 38.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.44 | 12.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.10 | 68.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.69 | 21.75 | 14.95 | 38.96 | 80.76 | 0.00 | 0.00 | 0.00 |
February | 41.38 | 20.15 | 21.23 | 43.09 | 77.94 | 0.00 | 0.00 | 0.00 |
March | 49.66 | 27.74 | 21.92 | 68.73 | 56.44 | 0.00 | 0.00 | 0.00 |
April | 40.12 | 15.24 | 24.88 | 60.61 | 43.41 | 0.00 | 0.00 | 0.00 |
May | 34.65 | 8.92 | 25.73 | 57.85 | 30.56 | 0.00 | 0.00 | 0.00 |
June | 33.73 | 5.96 | 27.77 | 62.89 | 21.07 | 0.00 | 0.00 | 0.00 |
July | 34.44 | 7.19 | 27.24 | 72.63 | 14.39 | 0.00 | 0.00 | 0.00 |
August | 38.87 | 11.58 | 27.29 | 79.54 | 18.91 | 0.00 | 0.00 | 0.00 |
September | 45.96 | 21.87 | 24.08 | 83.87 | 29.86 | 0.00 | 0.00 | 0.00 |
October | 45.12 | 25.86 | 19.27 | 69.26 | 42.85 | 0.00 | 0.00 | 0.00 |
November | 32.72 | 18.71 | 14.01 | 43.15 | 54.06 | 0.00 | 0.00 | 0.00 |
December | 30.66 | 16.17 | 14.49 | 30.65 | 79.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.65 | 16.75 | 21.90 | 59.36 | 45.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 5.96 | 14.01 | 30.65 | 14.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.66 | 27.74 | 27.77 | 83.87 | 80.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.45 | 67.79 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 35.82 | 65.48 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.37 | 47.15 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 50.73 | 36.08 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 48.64 | 25.09 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.68 | 17.46 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 60.85 | 11.90 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.60 | 15.69 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.20 | 24.83 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 58.02 | 35.51 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.07 | 45.10 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.51 | 66.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.66 | 38.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.51 | 11.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.20 | 67.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.45 | 67.79 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 35.82 | 65.48 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.37 | 47.15 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 50.73 | 36.08 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 48.64 | 25.09 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.68 | 17.46 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 60.85 | 11.90 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.60 | 15.69 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.20 | 24.83 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 58.02 | 35.51 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.07 | 45.10 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.51 | 66.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.66 | 38.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.51 | 11.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.20 | 67.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.69 | 21.75 | 14.95 | 39.04 | 80.19 | 0.00 | 0.00 | 0.00 |
February | 41.38 | 20.15 | 21.23 | 43.20 | 77.40 | 0.00 | 0.00 | 0.00 |
March | 49.66 | 27.74 | 21.92 | 68.91 | 55.89 | 0.00 | 0.00 | 0.00 |
April | 40.12 | 15.24 | 24.88 | 60.87 | 42.79 | 0.00 | 0.00 | 0.00 |
May | 34.65 | 8.92 | 25.73 | 58.27 | 29.83 | 0.00 | 0.00 | 0.00 |
June | 33.73 | 5.96 | 27.77 | 63.03 | 20.80 | 0.00 | 0.00 | 0.00 |
July | 34.44 | 7.19 | 27.24 | 72.72 | 14.20 | 0.00 | 0.00 | 0.00 |
August | 38.87 | 11.58 | 27.29 | 79.62 | 18.70 | 0.00 | 0.00 | 0.00 |
September | 45.96 | 21.87 | 24.08 | 83.99 | 29.55 | 0.00 | 0.00 | 0.00 |
October | 45.12 | 25.86 | 19.27 | 69.55 | 42.18 | 0.00 | 0.00 | 0.00 |
November | 32.72 | 18.71 | 14.01 | 43.30 | 53.44 | 0.00 | 0.00 | 0.00 |
December | 30.66 | 16.17 | 14.49 | 30.73 | 78.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.65 | 16.75 | 21.90 | 59.53 | 45.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 5.96 | 14.01 | 30.73 | 14.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.66 | 27.74 | 27.77 | 83.99 | 80.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.70 | 66.25 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 36.22 | 63.96 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.83 | 45.96 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 51.13 | 34.96 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 49.15 | 23.99 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.71 | 16.91 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 60.70 | 11.47 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.48 | 15.23 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.26 | 24.26 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 58.41 | 34.52 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.34 | 43.96 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.75 | 65.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.89 | 37.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.75 | 11.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.26 | 66.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.70 | 66.25 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 36.22 | 63.96 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.83 | 45.96 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 51.13 | 34.96 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 49.15 | 23.99 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.71 | 16.91 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 60.70 | 11.47 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.48 | 15.23 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.26 | 24.26 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 58.41 | 34.52 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.34 | 43.96 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.75 | 65.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.89 | 37.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.75 | 11.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.26 | 66.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.70 | 66.25 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 36.22 | 63.96 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.83 | 45.96 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 51.13 | 34.96 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 49.15 | 23.99 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.71 | 16.91 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 60.70 | 11.47 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.48 | 15.23 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.26 | 24.26 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 58.41 | 34.52 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.34 | 43.96 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.75 | 65.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.89 | 37.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.75 | 11.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.26 | 66.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.70 | 66.25 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 36.22 | 63.96 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.83 | 45.96 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 51.13 | 34.96 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 49.15 | 23.99 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.71 | 16.91 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 60.70 | 11.47 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.48 | 15.23 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.26 | 24.26 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 58.41 | 34.52 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.34 | 43.96 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.75 | 65.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.89 | 37.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.75 | 11.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.26 | 66.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.69 | 21.75 | 14.95 | 39.33 | 78.41 | 0.00 | 0.00 | 0.00 |
February | 41.38 | 20.15 | 21.23 | 43.67 | 75.63 | 0.00 | 0.00 | 0.00 |
March | 49.66 | 27.74 | 21.92 | 69.43 | 54.49 | 0.00 | 0.00 | 0.00 |
April | 40.12 | 15.24 | 24.88 | 61.33 | 41.47 | 0.00 | 0.00 | 0.00 |
May | 34.65 | 8.92 | 25.73 | 58.88 | 28.53 | 0.00 | 0.00 | 0.00 |
June | 33.73 | 5.96 | 27.77 | 63.06 | 20.15 | 0.00 | 0.00 | 0.00 |
July | 34.44 | 7.19 | 27.24 | 72.54 | 13.69 | 0.00 | 0.00 | 0.00 |
August | 38.87 | 11.58 | 27.29 | 79.46 | 18.15 | 0.00 | 0.00 | 0.00 |
September | 45.96 | 21.87 | 24.08 | 84.04 | 28.88 | 0.00 | 0.00 | 0.00 |
October | 45.12 | 25.86 | 19.27 | 70.00 | 41.01 | 0.00 | 0.00 | 0.00 |
November | 32.72 | 18.71 | 14.01 | 43.60 | 52.11 | 0.00 | 0.00 | 0.00 |
December | 30.66 | 16.17 | 14.49 | 31.01 | 76.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.65 | 16.75 | 21.90 | 59.79 | 43.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 5.96 | 14.01 | 31.01 | 13.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.66 | 27.74 | 27.77 | 84.04 | 78.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.69 | 21.75 | 14.95 | 39.33 | 78.41 | 0.00 | 0.00 | 0.00 |
February | 41.38 | 20.15 | 21.23 | 43.67 | 75.63 | 0.00 | 0.00 | 0.00 |
March | 49.66 | 27.74 | 21.92 | 69.43 | 54.49 | 0.00 | 0.00 | 0.00 |
April | 40.12 | 15.24 | 24.88 | 61.33 | 41.47 | 0.00 | 0.00 | 0.00 |
May | 34.65 | 8.92 | 25.73 | 58.88 | 28.53 | 0.00 | 0.00 | 0.00 |
June | 33.73 | 5.96 | 27.77 | 63.06 | 20.15 | 0.00 | 0.00 | 0.00 |
July | 34.44 | 7.19 | 27.24 | 72.54 | 13.69 | 0.00 | 0.00 | 0.00 |
August | 38.87 | 11.58 | 27.29 | 79.46 | 18.15 | 0.00 | 0.00 | 0.00 |
September | 45.96 | 21.87 | 24.08 | 84.04 | 28.88 | 0.00 | 0.00 | 0.00 |
October | 45.12 | 25.86 | 19.27 | 70.00 | 41.01 | 0.00 | 0.00 | 0.00 |
November | 32.72 | 18.71 | 14.01 | 43.60 | 52.11 | 0.00 | 0.00 | 0.00 |
December | 30.66 | 16.17 | 14.49 | 31.01 | 76.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.65 | 16.75 | 21.90 | 59.79 | 43.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 5.96 | 14.01 | 31.01 | 13.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.66 | 27.74 | 27.77 | 84.04 | 78.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.49 | 66.76 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 35.90 | 64.45 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.49 | 46.20 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 50.80 | 35.16 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 48.70 | 24.27 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.55 | 16.84 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 60.64 | 11.34 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.37 | 15.10 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.03 | 24.27 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 58.03 | 34.80 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.14 | 44.21 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.55 | 65.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.64 | 37.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.55 | 11.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.03 | 66.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.49 | 66.76 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 35.90 | 64.45 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.49 | 46.20 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 50.80 | 35.16 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 48.70 | 24.27 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.55 | 16.84 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 60.64 | 11.34 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.37 | 15.10 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.03 | 24.27 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 58.03 | 34.80 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.14 | 44.21 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.55 | 65.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.64 | 37.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.55 | 11.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.03 | 66.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.69 | 21.75 | 14.95 | 39.09 | 78.97 | 0.00 | 0.00 | 0.00 |
February | 41.38 | 20.15 | 21.23 | 43.32 | 76.19 | 0.00 | 0.00 | 0.00 |
March | 49.66 | 27.74 | 21.92 | 69.06 | 54.76 | 0.00 | 0.00 | 0.00 |
April | 40.12 | 15.24 | 24.88 | 60.96 | 41.70 | 0.00 | 0.00 | 0.00 |
May | 34.65 | 8.92 | 25.73 | 58.36 | 28.85 | 0.00 | 0.00 | 0.00 |
June | 33.73 | 5.96 | 27.77 | 62.88 | 20.07 | 0.00 | 0.00 | 0.00 |
July | 34.44 | 7.19 | 27.24 | 72.47 | 13.54 | 0.00 | 0.00 | 0.00 |
August | 38.87 | 11.58 | 27.29 | 79.35 | 18.01 | 0.00 | 0.00 | 0.00 |
September | 45.96 | 21.87 | 24.08 | 83.80 | 28.89 | 0.00 | 0.00 | 0.00 |
October | 45.12 | 25.86 | 19.27 | 69.57 | 41.33 | 0.00 | 0.00 | 0.00 |
November | 32.72 | 18.71 | 14.01 | 43.38 | 52.39 | 0.00 | 0.00 | 0.00 |
December | 30.66 | 16.17 | 14.49 | 30.79 | 77.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.65 | 16.75 | 21.90 | 59.51 | 44.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 5.96 | 14.01 | 30.79 | 13.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.66 | 27.74 | 27.77 | 83.80 | 78.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.50 | 66.64 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 35.92 | 64.35 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.53 | 46.06 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 50.87 | 34.99 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 48.84 | 24.05 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.63 | 16.73 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 60.68 | 11.28 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.41 | 15.04 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.07 | 24.17 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 58.09 | 34.65 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.17 | 44.07 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.57 | 65.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.69 | 37.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.57 | 11.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.07 | 66.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.50 | 66.64 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 35.92 | 64.35 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.53 | 46.06 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 50.87 | 34.99 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 48.84 | 24.05 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.63 | 16.73 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 60.68 | 11.28 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.41 | 15.04 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.07 | 24.17 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 58.09 | 34.65 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.17 | 44.07 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.57 | 65.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.69 | 37.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.57 | 11.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.07 | 66.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.69 | 21.75 | 14.95 | 39.11 | 78.84 | 0.00 | 0.00 | 0.00 |
February | 41.38 | 20.15 | 21.23 | 43.34 | 76.07 | 0.00 | 0.00 | 0.00 |
March | 49.66 | 27.74 | 21.92 | 69.11 | 54.59 | 0.00 | 0.00 | 0.00 |
April | 40.12 | 15.24 | 24.88 | 61.04 | 41.50 | 0.00 | 0.00 | 0.00 |
May | 34.65 | 8.92 | 25.73 | 58.53 | 28.59 | 0.00 | 0.00 | 0.00 |
June | 33.73 | 5.96 | 27.77 | 62.98 | 19.93 | 0.00 | 0.00 | 0.00 |
July | 34.44 | 7.19 | 27.24 | 72.53 | 13.46 | 0.00 | 0.00 | 0.00 |
August | 38.87 | 11.58 | 27.29 | 79.40 | 17.93 | 0.00 | 0.00 | 0.00 |
September | 45.96 | 21.87 | 24.08 | 83.85 | 28.77 | 0.00 | 0.00 | 0.00 |
October | 45.12 | 25.86 | 19.27 | 69.65 | 41.15 | 0.00 | 0.00 | 0.00 |
November | 32.72 | 18.71 | 14.01 | 43.42 | 52.21 | 0.00 | 0.00 | 0.00 |
December | 30.66 | 16.17 | 14.49 | 30.81 | 77.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.65 | 16.75 | 21.90 | 59.58 | 44.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 5.96 | 14.01 | 30.81 | 13.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.66 | 27.74 | 27.77 | 83.85 | 78.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.59 | 65.93 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 36.04 | 63.70 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.73 | 45.35 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 51.14 | 34.22 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 49.41 | 23.10 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.90 | 16.32 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 60.79 | 11.09 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.49 | 14.85 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.23 | 23.80 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 58.37 | 33.98 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.30 | 43.45 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.65 | 64.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.88 | 36.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.65 | 11.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.23 | 65.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.59 | 65.93 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 36.04 | 63.70 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 57.73 | 45.35 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 51.14 | 34.22 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 49.41 | 23.10 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 52.90 | 16.32 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 60.79 | 11.09 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.49 | 14.85 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.23 | 23.80 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 58.37 | 33.98 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.30 | 43.45 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.65 | 64.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 49.88 | 36.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.65 | 11.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.23 | 65.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.69 | 21.75 | 14.95 | 39.22 | 77.99 | 0.00 | 0.00 | 0.00 |
February | 41.38 | 20.15 | 21.23 | 43.48 | 75.29 | 0.00 | 0.00 | 0.00 |
March | 49.66 | 27.74 | 21.92 | 69.35 | 53.76 | 0.00 | 0.00 | 0.00 |
April | 40.12 | 15.24 | 24.88 | 61.37 | 40.58 | 0.00 | 0.00 | 0.00 |
May | 34.65 | 8.92 | 25.73 | 59.20 | 27.47 | 0.00 | 0.00 | 0.00 |
June | 33.73 | 5.96 | 27.77 | 63.30 | 19.45 | 0.00 | 0.00 | 0.00 |
July | 34.44 | 7.19 | 27.24 | 72.66 | 13.24 | 0.00 | 0.00 | 0.00 |
August | 38.87 | 11.58 | 27.29 | 79.49 | 17.71 | 0.00 | 0.00 | 0.00 |
September | 45.96 | 21.87 | 24.08 | 84.04 | 28.33 | 0.00 | 0.00 | 0.00 |
October | 45.12 | 25.86 | 19.27 | 69.98 | 40.35 | 0.00 | 0.00 | 0.00 |
November | 32.72 | 18.71 | 14.01 | 43.58 | 51.49 | 0.00 | 0.00 | 0.00 |
December | 30.66 | 16.17 | 14.49 | 30.90 | 76.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.65 | 16.75 | 21.90 | 59.81 | 43.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 5.96 | 14.01 | 30.90 | 13.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.66 | 27.74 | 27.77 | 84.04 | 77.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.99 | 62.75 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 36.55 | 60.70 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 58.43 | 42.43 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 51.93 | 31.47 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 50.80 | 20.45 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 53.71 | 14.92 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 61.02 | 10.41 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.66 | 14.17 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.70 | 22.53 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 59.03 | 32.00 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.69 | 41.26 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.98 | 61.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 50.46 | 34.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.98 | 10.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.70 | 62.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.69 | 18.19 | 12.50 | 32.99 | 62.75 | 0.00 | 0.00 | 0.00 |
February | 34.61 | 16.85 | 17.76 | 36.55 | 60.70 | 0.00 | 0.00 | 0.00 |
March | 41.54 | 23.20 | 18.34 | 58.43 | 42.43 | 0.00 | 0.00 | 0.00 |
April | 33.56 | 12.75 | 20.81 | 51.93 | 31.47 | 0.00 | 0.00 | 0.00 |
May | 28.98 | 7.46 | 21.52 | 50.80 | 20.45 | 0.00 | 0.00 | 0.00 |
June | 28.21 | 4.98 | 23.23 | 53.71 | 14.92 | 0.00 | 0.00 | 0.00 |
July | 28.80 | 6.02 | 22.79 | 61.02 | 10.41 | 0.00 | 0.00 | 0.00 |
August | 32.51 | 9.68 | 22.83 | 66.66 | 14.17 | 0.00 | 0.00 | 0.00 |
September | 38.44 | 18.29 | 20.14 | 70.70 | 22.53 | 0.00 | 0.00 | 0.00 |
October | 37.74 | 21.63 | 16.11 | 59.03 | 32.00 | 0.00 | 0.00 | 0.00 |
November | 27.37 | 15.65 | 11.72 | 36.69 | 41.26 | 0.00 | 0.00 | 0.00 |
December | 25.64 | 13.53 | 12.12 | 25.98 | 61.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 14.01 | 18.32 | 50.46 | 34.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.64 | 4.98 | 11.72 | 25.98 | 10.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.54 | 23.20 | 23.23 | 70.70 | 62.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.69 | 21.75 | 14.95 | 39.71 | 74.22 | 0.00 | 0.00 | 0.00 |
February | 41.38 | 20.15 | 21.23 | 44.10 | 71.74 | 0.00 | 0.00 | 0.00 |
March | 49.66 | 27.74 | 21.92 | 70.20 | 50.30 | 0.00 | 0.00 | 0.00 |
April | 40.12 | 15.24 | 24.88 | 62.31 | 37.33 | 0.00 | 0.00 | 0.00 |
May | 34.65 | 8.92 | 25.73 | 60.86 | 24.33 | 0.00 | 0.00 | 0.00 |
June | 33.73 | 5.96 | 27.77 | 64.27 | 17.80 | 0.00 | 0.00 | 0.00 |
July | 34.44 | 7.19 | 27.24 | 72.94 | 12.43 | 0.00 | 0.00 | 0.00 |
August | 38.87 | 11.58 | 27.29 | 79.70 | 16.91 | 0.00 | 0.00 | 0.00 |
September | 45.96 | 21.87 | 24.08 | 84.60 | 26.83 | 0.00 | 0.00 | 0.00 |
October | 45.12 | 25.86 | 19.27 | 70.76 | 38.02 | 0.00 | 0.00 | 0.00 |
November | 32.72 | 18.71 | 14.01 | 44.05 | 48.89 | 0.00 | 0.00 | 0.00 |
December | 30.66 | 16.17 | 14.49 | 31.31 | 72.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.65 | 16.75 | 21.90 | 60.50 | 40.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 5.96 | 14.01 | 31.31 | 12.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.66 | 27.74 | 27.77 | 84.60 | 74.22 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 87657518.19 | 0.180895E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 87665528.41 | 0.157649E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.155067E+09 | 0.124681E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.132676E+09 | 91634405.91 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.131614E+09 | 65050234.00 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.137704E+09 | 42541669.53 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.164169E+09 | 28920802.92 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.179109E+09 | 39058378.30 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.182557E+09 | 61917519.57 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.155804E+09 | 94245659.14 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 93838436.74 | 0.116126E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68919252.61 | 0.177393E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.157678E+10 | 0.118011E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68919252.61 | 28920802.92 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.182557E+09 | 0.180895E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 87657518.19 | 0.180895E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 87665528.41 | 0.157649E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.155067E+09 | 0.124681E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.132676E+09 | 91634405.91 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.131614E+09 | 65050234.00 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.137704E+09 | 42541669.53 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.164169E+09 | 28920802.92 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.179109E+09 | 39058378.30 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.182557E+09 | 61917519.57 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.155804E+09 | 94245659.14 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 93838436.74 | 0.116126E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68919252.61 | 0.177393E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.157678E+10 | 0.118011E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68919252.61 | 28920802.92 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.182557E+09 | 0.180895E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 87657518.19 | 0.180895E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 87665528.41 | 0.157649E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.155067E+09 | 0.124681E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.132676E+09 | 91634405.91 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.131614E+09 | 65050234.00 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.137704E+09 | 42541669.53 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.164169E+09 | 28920802.92 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.179109E+09 | 39058378.30 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.182557E+09 | 61917519.57 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.155804E+09 | 94245659.14 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 93838436.74 | 0.116126E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68919252.61 | 0.177393E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.157678E+10 | 0.118011E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68919252.61 | 28920802.92 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.182557E+09 | 0.180895E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 87657518.19 | 0.180895E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 87665528.41 | 0.157649E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.155067E+09 | 0.124681E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.132676E+09 | 91634405.91 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.131614E+09 | 65050234.00 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.137704E+09 | 42541669.53 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.164169E+09 | 28920802.92 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.179109E+09 | 39058378.30 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.182557E+09 | 61917519.57 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.155804E+09 | 94245659.14 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 93838436.74 | 0.116126E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68919252.61 | 0.177393E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.157678E+10 | 0.118011E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68919252.61 | 28920802.92 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.182557E+09 | 0.180895E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98821196.96 | 58565616.46 | 40255580.50 | 0.105997E+09 | 0.215204E+09 |
February | 0.100650E+09 | 49009545.68 | 51640085.90 | 0.106275E+09 | 0.187400E+09 |
March | 0.133741E+09 | 74698727.79 | 59042150.05 | 0.187214E+09 | 0.148614E+09 |
April | 0.104562E+09 | 39714678.53 | 64847561.08 | 0.160002E+09 | 0.109287E+09 |
May | 93315994.09 | 24015630.55 | 69300363.54 | 0.158510E+09 | 77773632.38 |
June | 87906041.07 | 15527788.35 | 72378252.72 | 0.165622E+09 | 50998089.01 |
July | 92743933.85 | 19371458.53 | 73372475.33 | 0.197233E+09 | 34740657.10 |
August | 0.104677E+09 | 31178140.48 | 73498540.38 | 0.215245E+09 | 46860414.40 |
September | 0.119774E+09 | 57002500.30 | 62771033.76 | 0.219573E+09 | 74139962.42 |
October | 0.121519E+09 | 69635974.16 | 51883019.71 | 0.187746E+09 | 0.112572E+09 |
November | 85280417.17 | 48760810.61 | 36519606.56 | 0.113223E+09 | 0.138397E+09 |
December | 82569637.93 | 43556006.96 | 39013630.97 | 83457353.20 | 0.210921E+09 |
Annual Sum or Average | 0.122556E+10 | 0.531037E+09 | 0.694522E+09 | 0.190010E+10 | 0.140691E+10 |
Minimum of Months | 82569637.93 | 15527788.35 | 36519606.56 | 83457353.20 | 34740657.10 |
Maximum of Months | 0.133741E+09 | 74698727.79 | 73498540.38 | 0.219573E+09 | 0.215204E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98821196.96 | 58565616.46 | 40255580.50 | 0.105997E+09 | 0.215204E+09 |
February | 0.100650E+09 | 49009545.68 | 51640085.90 | 0.106275E+09 | 0.187400E+09 |
March | 0.133741E+09 | 74698727.79 | 59042150.05 | 0.187214E+09 | 0.148614E+09 |
April | 0.104562E+09 | 39714678.53 | 64847561.08 | 0.160002E+09 | 0.109287E+09 |
May | 93315994.09 | 24015630.55 | 69300363.54 | 0.158510E+09 | 77773632.38 |
June | 87906041.07 | 15527788.35 | 72378252.72 | 0.165622E+09 | 50998089.01 |
July | 92743933.85 | 19371458.53 | 73372475.33 | 0.197233E+09 | 34740657.10 |
August | 0.104677E+09 | 31178140.48 | 73498540.38 | 0.215245E+09 | 46860414.40 |
September | 0.119774E+09 | 57002500.30 | 62771033.76 | 0.219573E+09 | 74139962.42 |
October | 0.121519E+09 | 69635974.16 | 51883019.71 | 0.187746E+09 | 0.112572E+09 |
November | 85280417.17 | 48760810.61 | 36519606.56 | 0.113223E+09 | 0.138397E+09 |
December | 82569637.93 | 43556006.96 | 39013630.97 | 83457353.20 | 0.210921E+09 |
Annual Sum or Average | 0.122556E+10 | 0.531037E+09 | 0.694522E+09 | 0.190010E+10 | 0.140691E+10 |
Minimum of Months | 82569637.93 | 15527788.35 | 36519606.56 | 83457353.20 | 34740657.10 |
Maximum of Months | 0.133741E+09 | 74698727.79 | 73498540.38 | 0.219573E+09 | 0.215204E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 86397919.37 | 0.187111E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 86064148.72 | 0.163295E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.152759E+09 | 0.130700E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.130182E+09 | 98075920.39 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.128492E+09 | 70313984.98 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.136609E+09 | 43900931.19 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.163735E+09 | 29553623.98 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.178732E+09 | 39706792.49 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.181684E+09 | 63373420.30 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.153815E+09 | 99516202.40 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 92525482.14 | 0.121977E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 67817201.39 | 0.183804E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.155881E+10 | 0.123133E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 67817201.39 | 29553623.98 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.181684E+09 | 0.187111E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 86397919.37 | 0.187111E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 86064148.72 | 0.163295E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.152759E+09 | 0.130700E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.130182E+09 | 98075920.39 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.128492E+09 | 70313984.98 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.136609E+09 | 43900931.19 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.163735E+09 | 29553623.98 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.178732E+09 | 39706792.49 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.181684E+09 | 63373420.30 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.153815E+09 | 99516202.40 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 92525482.14 | 0.121977E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 67817201.39 | 0.183804E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.155881E+10 | 0.123133E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 67817201.39 | 29553623.98 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.181684E+09 | 0.187111E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98821196.96 | 58565616.46 | 40255580.50 | 0.104502E+09 | 0.222549E+09 |
February | 0.100650E+09 | 49009545.68 | 51640085.90 | 0.104379E+09 | 0.194058E+09 |
March | 0.133741E+09 | 74698727.79 | 59042150.05 | 0.184483E+09 | 0.155738E+09 |
April | 0.104562E+09 | 39714678.53 | 64847561.08 | 0.157041E+09 | 0.116896E+09 |
May | 93315994.09 | 24015630.55 | 69300363.54 | 0.154802E+09 | 84011563.75 |
June | 87906041.07 | 15527788.35 | 72378252.72 | 0.164333E+09 | 52617502.40 |
July | 92743933.85 | 19371458.53 | 73372475.33 | 0.196734E+09 | 35500046.13 |
August | 0.104677E+09 | 31178140.48 | 73498540.38 | 0.214821E+09 | 47635300.06 |
September | 0.119774E+09 | 57002500.30 | 62771033.76 | 0.218567E+09 | 75869919.17 |
October | 0.121519E+09 | 69635974.16 | 51883019.71 | 0.185406E+09 | 0.118783E+09 |
November | 85280417.17 | 48760810.61 | 36519606.56 | 0.111674E+09 | 0.145301E+09 |
December | 82569637.93 | 43556006.96 | 39013630.97 | 82149015.95 | 0.218484E+09 |
Annual Sum or Average | 0.122556E+10 | 0.531037E+09 | 0.694522E+09 | 0.187889E+10 | 0.146744E+10 |
Minimum of Months | 82569637.93 | 15527788.35 | 36519606.56 | 82149015.95 | 35500046.13 |
Maximum of Months | 0.133741E+09 | 74698727.79 | 73498540.38 | 0.218567E+09 | 0.222549E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 86600648.29 | 0.184343E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 86255993.60 | 0.160779E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.152984E+09 | 0.128786E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.130544E+09 | 96221771.29 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.128755E+09 | 70106747.17 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.136176E+09 | 46006809.41 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.162790E+09 | 32255505.90 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.178224E+09 | 42465885.05 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.181614E+09 | 65320507.75 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.154306E+09 | 98068839.17 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 92913671.49 | 0.119684E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68009425.29 | 0.181059E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.155917E+10 | 0.122510E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68009425.29 | 32255505.90 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.181614E+09 | 0.184343E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 86600648.29 | 0.184343E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 86255993.60 | 0.160779E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.152984E+09 | 0.128786E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.130544E+09 | 96221771.29 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.128755E+09 | 70106747.17 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.136176E+09 | 46006809.41 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.162790E+09 | 32255505.90 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.178224E+09 | 42465885.05 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.181614E+09 | 65320507.75 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.154306E+09 | 98068839.17 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 92913671.49 | 0.119684E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68009425.29 | 0.181059E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.155917E+10 | 0.122510E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68009425.29 | 32255505.90 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.181614E+09 | 0.184343E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98281190.42 | 58245585.77 | 40035604.65 | 0.104181E+09 | 0.218091E+09 |
February | 0.100100E+09 | 48741733.96 | 51357899.63 | 0.104045E+09 | 0.190062E+09 |
March | 0.133010E+09 | 74290538.02 | 58719515.35 | 0.183748E+09 | 0.152653E+09 |
April | 0.103991E+09 | 39497658.43 | 64493202.82 | 0.156619E+09 | 0.114104E+09 |
May | 92806070.63 | 23884397.60 | 68921673.03 | 0.154272E+09 | 83319952.46 |
June | 87425680.19 | 15442937.05 | 71982743.14 | 0.162925E+09 | 54804207.89 |
July | 92237136.40 | 19265603.56 | 72971532.84 | 0.194551E+09 | 38488129.52 |
August | 0.104105E+09 | 31007768.12 | 73096909.02 | 0.213049E+09 | 50618996.95 |
September | 0.119119E+09 | 56691011.23 | 62428022.64 | 0.217288E+09 | 77740036.39 |
October | 0.120855E+09 | 69255449.72 | 51599505.94 | 0.184981E+09 | 0.116449E+09 |
November | 84814403.96 | 48494358.10 | 36320045.87 | 0.111533E+09 | 0.141834E+09 |
December | 82118437.73 | 43317995.99 | 38800441.73 | 81935350.41 | 0.214080E+09 |
Annual Sum or Average | 0.121886E+10 | 0.528135E+09 | 0.690727E+09 | 0.186913E+10 | 0.145224E+10 |
Minimum of Months | 82118437.73 | 15442937.05 | 36320045.87 | 81935350.41 | 38488129.52 |
Maximum of Months | 0.133010E+09 | 74290538.02 | 73096909.02 | 0.217288E+09 | 0.218091E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 86735400.02 | 0.182842E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 86418572.88 | 0.159504E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.153258E+09 | 0.127527E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.130940E+09 | 94880058.96 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.129315E+09 | 68867790.69 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.136240E+09 | 45846715.17 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.162771E+09 | 32301787.78 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.178215E+09 | 42488991.69 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.181697E+09 | 65034448.44 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.154754E+09 | 96654870.51 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 93178488.52 | 0.118234E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68141044.27 | 0.179580E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.156166E+10 | 0.121376E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68141044.27 | 32301787.78 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.181697E+09 | 0.182842E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 86735400.02 | 0.182842E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 86418572.88 | 0.159504E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.153258E+09 | 0.127527E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.130940E+09 | 94880058.96 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.129315E+09 | 68867790.69 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.136240E+09 | 45846715.17 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.162771E+09 | 32301787.78 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.178215E+09 | 42488991.69 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.181697E+09 | 65034448.44 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.154754E+09 | 96654870.51 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 93178488.52 | 0.118234E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68141044.27 | 0.179580E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.156166E+10 | 0.121376E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68141044.27 | 32301787.78 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.181697E+09 | 0.182842E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98281190.42 | 58245585.77 | 40035604.65 | 0.104346E+09 | 0.216306E+09 |
February | 0.100100E+09 | 48741733.96 | 51357899.63 | 0.104244E+09 | 0.188550E+09 |
March | 0.133010E+09 | 74290538.02 | 58719515.35 | 0.184080E+09 | 0.151158E+09 |
April | 0.103991E+09 | 39497658.43 | 64493202.82 | 0.157094E+09 | 0.112514E+09 |
May | 92806070.63 | 23884397.60 | 68921673.03 | 0.154942E+09 | 81853678.11 |
June | 87425680.19 | 15442937.05 | 71982743.14 | 0.163003E+09 | 54614514.54 |
July | 92237136.40 | 19265603.56 | 72971532.84 | 0.194528E+09 | 38542927.81 |
August | 0.104105E+09 | 31007768.12 | 73096909.02 | 0.213038E+09 | 50646261.37 |
September | 0.119119E+09 | 56691011.23 | 62428022.64 | 0.217388E+09 | 77401134.37 |
October | 0.120855E+09 | 69255449.72 | 51599505.94 | 0.185519E+09 | 0.114774E+09 |
November | 84814403.96 | 48494358.10 | 36320045.87 | 0.111851E+09 | 0.140112E+09 |
December | 82118437.73 | 43317995.99 | 38800441.73 | 82096773.67 | 0.212324E+09 |
Annual Sum or Average | 0.121886E+10 | 0.528135E+09 | 0.690727E+09 | 0.187213E+10 | 0.143880E+10 |
Minimum of Months | 82118437.73 | 15442937.05 | 36320045.87 | 82096773.67 | 38542927.81 |
Maximum of Months | 0.133010E+09 | 74290538.02 | 73096909.02 | 0.217388E+09 | 0.216306E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 86923190.81 | 0.181557E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 86644226.72 | 0.158406E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.153665E+09 | 0.126292E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.131500E+09 | 93530977.17 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.130270E+09 | 67202113.42 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.136551E+09 | 45260759.10 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.162971E+09 | 31867695.41 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.178389E+09 | 42021460.44 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.181961E+09 | 64355477.90 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.155397E+09 | 95121867.99 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 93501085.76 | 0.116892E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68312607.71 | 0.178266E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.156609E+10 | 0.120077E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68312607.71 | 31867695.41 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.181961E+09 | 0.181557E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 86923190.81 | 0.181557E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 86644226.72 | 0.158406E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.153665E+09 | 0.126292E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.131500E+09 | 93530977.17 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.130270E+09 | 67202113.42 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.136551E+09 | 45260759.10 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.162971E+09 | 31867695.41 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.178389E+09 | 42021460.44 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.181961E+09 | 64355477.90 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.155397E+09 | 95121867.99 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 93501085.76 | 0.116892E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68312607.71 | 0.178266E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.156609E+10 | 0.120077E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68312607.71 | 31867695.41 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.181961E+09 | 0.181557E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98281190.42 | 58245585.77 | 40035604.65 | 0.104575E+09 | 0.214780E+09 |
February | 0.100100E+09 | 48741733.96 | 51357899.63 | 0.104519E+09 | 0.187247E+09 |
March | 0.133010E+09 | 74290538.02 | 58719515.35 | 0.184571E+09 | 0.149694E+09 |
April | 0.103991E+09 | 39497658.43 | 64493202.82 | 0.157767E+09 | 0.110918E+09 |
May | 92806070.63 | 23884397.60 | 68921673.03 | 0.156082E+09 | 79885359.66 |
June | 87425680.19 | 15442937.05 | 71982743.14 | 0.163375E+09 | 53923020.48 |
July | 92237136.40 | 19265603.56 | 72971532.84 | 0.194770E+09 | 38032171.87 |
August | 0.104105E+09 | 31007768.12 | 73096909.02 | 0.213249E+09 | 50095563.81 |
September | 0.119119E+09 | 56691011.23 | 62428022.64 | 0.217705E+09 | 76598900.88 |
October | 0.120855E+09 | 69255449.72 | 51599505.94 | 0.186289E+09 | 0.112963E+09 |
November | 84814403.96 | 48494358.10 | 36320045.87 | 0.112239E+09 | 0.138520E+09 |
December | 82118437.73 | 43317995.99 | 38800441.73 | 82306283.94 | 0.210762E+09 |
Annual Sum or Average | 0.121886E+10 | 0.528135E+09 | 0.690727E+09 | 0.187745E+10 | 0.142342E+10 |
Minimum of Months | 82118437.73 | 15442937.05 | 36320045.87 | 82306283.94 | 38032171.87 |
Maximum of Months | 0.133010E+09 | 74290538.02 | 73096909.02 | 0.217705E+09 | 0.214780E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 87592349.80 | 0.177455E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 87614099.12 | 0.154727E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.154879E+09 | 0.123093E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.132536E+09 | 90612764.80 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.131655E+09 | 64251958.10 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.136633E+09 | 43826187.07 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.162588E+09 | 30716525.57 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.178049E+09 | 40780873.98 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.182101E+09 | 62881294.22 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.156447E+09 | 92459847.73 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 94181119.42 | 0.113953E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68967400.07 | 0.174251E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.157324E+10 | 0.116901E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68967400.07 | 30716525.57 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.182101E+09 | 0.177455E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 87592349.80 | 0.177455E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 87614099.12 | 0.154727E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.154879E+09 | 0.123093E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.132536E+09 | 90612764.80 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.131655E+09 | 64251958.10 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.136633E+09 | 43826187.07 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.162588E+09 | 30716525.57 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.178049E+09 | 40780873.98 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.182101E+09 | 62881294.22 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.156447E+09 | 92459847.73 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 94181119.42 | 0.113953E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68967400.07 | 0.174251E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.157324E+10 | 0.116901E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68967400.07 | 30716525.57 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.182101E+09 | 0.177455E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 87592349.80 | 0.177455E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 87614099.12 | 0.154727E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.154879E+09 | 0.123093E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.132536E+09 | 90612764.80 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.131655E+09 | 64251958.10 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.136633E+09 | 43826187.07 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.162588E+09 | 30716525.57 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.178049E+09 | 40780873.98 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.182101E+09 | 62881294.22 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.156447E+09 | 92459847.73 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 94181119.42 | 0.113953E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68967400.07 | 0.174251E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.157324E+10 | 0.116901E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68967400.07 | 30716525.57 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.182101E+09 | 0.177455E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 87592349.80 | 0.177455E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 87614099.12 | 0.154727E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.154879E+09 | 0.123093E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.132536E+09 | 90612764.80 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.131655E+09 | 64251958.10 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.136633E+09 | 43826187.07 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.162588E+09 | 30716525.57 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.178049E+09 | 40780873.98 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.182101E+09 | 62881294.22 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.156447E+09 | 92459847.73 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 94181119.42 | 0.113953E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68967400.07 | 0.174251E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.157324E+10 | 0.116901E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68967400.07 | 30716525.57 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.182101E+09 | 0.177455E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98281190.42 | 58245585.77 | 40035604.65 | 0.105345E+09 | 0.210001E+09 |
February | 0.100100E+09 | 48741733.96 | 51357899.63 | 0.105638E+09 | 0.182973E+09 |
March | 0.133010E+09 | 74290538.02 | 58719515.35 | 0.185972E+09 | 0.145951E+09 |
April | 0.103991E+09 | 39497658.43 | 64493202.82 | 0.158968E+09 | 0.107494E+09 |
May | 92806070.63 | 23884397.60 | 68921673.03 | 0.157697E+09 | 76403175.51 |
June | 87425680.19 | 15442937.05 | 71982743.14 | 0.163456E+09 | 52223630.59 |
July | 92237136.40 | 19265603.56 | 72971532.84 | 0.194301E+09 | 36662156.17 |
August | 0.104105E+09 | 31007768.12 | 73096909.02 | 0.212824E+09 | 48621293.76 |
September | 0.119119E+09 | 56691011.23 | 62428022.64 | 0.217841E+09 | 74853695.12 |
October | 0.120855E+09 | 69255449.72 | 51599505.94 | 0.187495E+09 | 0.109833E+09 |
November | 84814403.96 | 48494358.10 | 36320045.87 | 0.113021E+09 | 0.135066E+09 |
December | 82118437.73 | 43317995.99 | 38800441.73 | 83062619.64 | 0.206089E+09 |
Annual Sum or Average | 0.121886E+10 | 0.528135E+09 | 0.690727E+09 | 0.188562E+10 | 0.138617E+10 |
Minimum of Months | 82118437.73 | 15442937.05 | 36320045.87 | 83062619.64 | 36662156.17 |
Maximum of Months | 0.133010E+09 | 74290538.02 | 73096909.02 | 0.217841E+09 | 0.210001E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98281190.42 | 58245585.77 | 40035604.65 | 0.105345E+09 | 0.210001E+09 |
February | 0.100100E+09 | 48741733.96 | 51357899.63 | 0.105638E+09 | 0.182973E+09 |
March | 0.133010E+09 | 74290538.02 | 58719515.35 | 0.185972E+09 | 0.145951E+09 |
April | 0.103991E+09 | 39497658.43 | 64493202.82 | 0.158968E+09 | 0.107494E+09 |
May | 92806070.63 | 23884397.60 | 68921673.03 | 0.157697E+09 | 76403175.51 |
June | 87425680.19 | 15442937.05 | 71982743.14 | 0.163456E+09 | 52223630.59 |
July | 92237136.40 | 19265603.56 | 72971532.84 | 0.194301E+09 | 36662156.17 |
August | 0.104105E+09 | 31007768.12 | 73096909.02 | 0.212824E+09 | 48621293.76 |
September | 0.119119E+09 | 56691011.23 | 62428022.64 | 0.217841E+09 | 74853695.12 |
October | 0.120855E+09 | 69255449.72 | 51599505.94 | 0.187495E+09 | 0.109833E+09 |
November | 84814403.96 | 48494358.10 | 36320045.87 | 0.113021E+09 | 0.135066E+09 |
December | 82118437.73 | 43317995.99 | 38800441.73 | 83062619.64 | 0.206089E+09 |
Annual Sum or Average | 0.121886E+10 | 0.528135E+09 | 0.690727E+09 | 0.188562E+10 | 0.138617E+10 |
Minimum of Months | 82118437.73 | 15442937.05 | 36320045.87 | 83062619.64 | 36662156.17 |
Maximum of Months | 0.133010E+09 | 74290538.02 | 73096909.02 | 0.217841E+09 | 0.210001E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 87013809.30 | 0.178804E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 86858581.63 | 0.155924E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.153972E+09 | 0.123734E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.131679E+09 | 91141690.08 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.130447E+09 | 64997401.58 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.136213E+09 | 43654767.41 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.162407E+09 | 30374187.95 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.177769E+09 | 40450046.63 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.181518E+09 | 62903758.28 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.155415E+09 | 93209800.25 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 93666201.47 | 0.114592E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68438053.90 | 0.175571E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.156540E+10 | 0.117536E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68438053.90 | 30374187.95 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.181518E+09 | 0.178804E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 87013809.30 | 0.178804E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 86858581.63 | 0.155924E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.153972E+09 | 0.123734E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.131679E+09 | 91141690.08 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.130447E+09 | 64997401.58 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.136213E+09 | 43654767.41 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.162407E+09 | 30374187.95 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.177769E+09 | 40450046.63 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.181518E+09 | 62903758.28 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.155415E+09 | 93209800.25 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 93666201.47 | 0.114592E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68438053.90 | 0.175571E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.156540E+10 | 0.117536E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68438053.90 | 30374187.95 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.181518E+09 | 0.178804E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98281190.42 | 58245585.77 | 40035604.65 | 0.104696E+09 | 0.211518E+09 |
February | 0.100100E+09 | 48741733.96 | 51357899.63 | 0.104790E+09 | 0.184315E+09 |
March | 0.133010E+09 | 74290538.02 | 58719515.35 | 0.184961E+09 | 0.146667E+09 |
April | 0.103991E+09 | 39497658.43 | 64493202.82 | 0.158006E+09 | 0.108088E+09 |
May | 92806070.63 | 23884397.60 | 68921673.03 | 0.156317E+09 | 77268526.38 |
June | 87425680.19 | 15442937.05 | 71982743.14 | 0.162993E+09 | 52020293.37 |
July | 92237136.40 | 19265603.56 | 72971532.84 | 0.194117E+09 | 36261061.13 |
August | 0.104105E+09 | 31007768.12 | 73096909.02 | 0.212530E+09 | 48232306.70 |
September | 0.119119E+09 | 56691011.23 | 62428022.64 | 0.217198E+09 | 74874181.61 |
October | 0.120855E+09 | 69255449.72 | 51599505.94 | 0.186331E+09 | 0.110692E+09 |
November | 84814403.96 | 48494358.10 | 36320045.87 | 0.112447E+09 | 0.135782E+09 |
December | 82118437.73 | 43317995.99 | 38800441.73 | 82465738.69 | 0.207568E+09 |
Annual Sum or Average | 0.121886E+10 | 0.528135E+09 | 0.690727E+09 | 0.187685E+10 | 0.139329E+10 |
Minimum of Months | 82118437.73 | 15442937.05 | 36320045.87 | 82465738.69 | 36261061.13 |
Maximum of Months | 0.133010E+09 | 74290538.02 | 73096909.02 | 0.217198E+09 | 0.211518E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 87058157.57 | 0.178500E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 86909091.87 | 0.155679E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.154093E+09 | 0.123357E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.131860E+09 | 90693469.67 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.130822E+09 | 64411637.10 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.136420E+09 | 43359661.63 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.162536E+09 | 30199245.81 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.177871E+09 | 40273626.37 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.181632E+09 | 62658070.96 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.155590E+09 | 92818809.91 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 93755530.50 | 0.114219E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68479427.15 | 0.175259E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.156702E+10 | 0.117143E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68479427.15 | 30199245.81 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.181632E+09 | 0.178500E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 87058157.57 | 0.178500E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 86909091.87 | 0.155679E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.154093E+09 | 0.123357E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.131860E+09 | 90693469.67 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.130822E+09 | 64411637.10 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.136420E+09 | 43359661.63 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.162536E+09 | 30199245.81 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.177871E+09 | 40273626.37 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.181632E+09 | 62658070.96 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.155590E+09 | 92818809.91 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 93755530.50 | 0.114219E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68479427.15 | 0.175259E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.156702E+10 | 0.117143E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68479427.15 | 30199245.81 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.181632E+09 | 0.178500E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98281190.42 | 58245585.77 | 40035604.65 | 0.104750E+09 | 0.211156E+09 |
February | 0.100100E+09 | 48741733.96 | 51357899.63 | 0.104852E+09 | 0.184024E+09 |
March | 0.133010E+09 | 74290538.02 | 58719515.35 | 0.185107E+09 | 0.146220E+09 |
April | 0.103991E+09 | 39497658.43 | 64493202.82 | 0.158224E+09 | 0.107556E+09 |
May | 92806070.63 | 23884397.60 | 68921673.03 | 0.156765E+09 | 76574608.44 |
June | 87425680.19 | 15442937.05 | 71982743.14 | 0.163242E+09 | 51670694.88 |
July | 92237136.40 | 19265603.56 | 72971532.84 | 0.194271E+09 | 36052876.33 |
August | 0.104105E+09 | 31007768.12 | 73096909.02 | 0.212653E+09 | 48022946.18 |
September | 0.119119E+09 | 56691011.23 | 62428022.64 | 0.217336E+09 | 74583202.58 |
October | 0.120855E+09 | 69255449.72 | 51599505.94 | 0.186539E+09 | 0.110229E+09 |
November | 84814403.96 | 48494358.10 | 36320045.87 | 0.112554E+09 | 0.135339E+09 |
December | 82118437.73 | 43317995.99 | 38800441.73 | 82516291.50 | 0.207197E+09 |
Annual Sum or Average | 0.121886E+10 | 0.528135E+09 | 0.690727E+09 | 0.187881E+10 | 0.138863E+10 |
Minimum of Months | 82118437.73 | 15442937.05 | 36320045.87 | 82516291.50 | 36052876.33 |
Maximum of Months | 0.133010E+09 | 74290538.02 | 73096909.02 | 0.217336E+09 | 0.211156E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 87299256.82 | 0.176589E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 87185726.14 | 0.154092E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.154617E+09 | 0.121470E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.132563E+09 | 88691601.79 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.132336E+09 | 61874227.79 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.137114E+09 | 42298544.67 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.162814E+09 | 29692599.68 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.178085E+09 | 39779888.47 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.182046E+09 | 61692113.51 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.156332E+09 | 91008188.51 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 94092522.49 | 0.112633E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68688345.82 | 0.173421E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.157317E+10 | 0.115324E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68688345.82 | 29692599.68 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.182046E+09 | 0.176589E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 87299256.82 | 0.176589E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 87185726.14 | 0.154092E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.154617E+09 | 0.121470E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.132563E+09 | 88691601.79 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.132336E+09 | 61874227.79 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.137114E+09 | 42298544.67 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.162814E+09 | 29692599.68 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.178085E+09 | 39779888.47 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.182046E+09 | 61692113.51 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.156332E+09 | 91008188.51 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 94092522.49 | 0.112633E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 68688345.82 | 0.173421E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.157317E+10 | 0.115324E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 68688345.82 | 29692599.68 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.182046E+09 | 0.176589E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98281190.42 | 58245585.77 | 40035604.65 | 0.105045E+09 | 0.208888E+09 |
February | 0.100100E+09 | 48741733.96 | 51357899.63 | 0.105189E+09 | 0.182142E+09 |
March | 0.133010E+09 | 74290538.02 | 58719515.35 | 0.185741E+09 | 0.143984E+09 |
April | 0.103991E+09 | 39497658.43 | 64493202.82 | 0.159069E+09 | 0.105186E+09 |
May | 92806070.63 | 23884397.60 | 68921673.03 | 0.158572E+09 | 73574912.03 |
June | 87425680.19 | 15442937.05 | 71982743.14 | 0.164075E+09 | 50416375.12 |
July | 92237136.40 | 19265603.56 | 72971532.84 | 0.194604E+09 | 35455389.17 |
August | 0.104105E+09 | 31007768.12 | 73096909.02 | 0.212912E+09 | 47440961.16 |
September | 0.119119E+09 | 56691011.23 | 62428022.64 | 0.217833E+09 | 73440768.49 |
October | 0.120855E+09 | 69255449.72 | 51599505.94 | 0.187426E+09 | 0.108087E+09 |
November | 84814403.96 | 48494358.10 | 36320045.87 | 0.112961E+09 | 0.133459E+09 |
December | 82118437.73 | 43317995.99 | 38800441.73 | 82772176.05 | 0.205016E+09 |
Annual Sum or Average | 0.121886E+10 | 0.528135E+09 | 0.690727E+09 | 0.188620E+10 | 0.136709E+10 |
Minimum of Months | 82118437.73 | 15442937.05 | 36320045.87 | 82772176.05 | 35455389.17 |
Maximum of Months | 0.133010E+09 | 74290538.02 | 73096909.02 | 0.217833E+09 | 0.208888E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 88364568.57 | 0.168078E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 88414260.90 | 0.146846E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.156509E+09 | 0.113657E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.134593E+09 | 81568120.19 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.136055E+09 | 54764239.60 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.139228E+09 | 38682128.46 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.163441E+09 | 27874731.10 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.178546E+09 | 37964668.53 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.183266E+09 | 58391327.85 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.158098E+09 | 85718849.81 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 95108695.88 | 0.106943E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 69577126.97 | 0.165324E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.159120E+10 | 0.108581E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 69577126.97 | 27874731.10 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.183266E+09 | 0.168078E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82203445.65 | 48717234.94 | 33486210.70 | 88364568.57 | 0.168078E+09 |
February | 83724411.09 | 40768110.98 | 42956300.11 | 88414260.90 | 0.146846E+09 |
March | 0.111251E+09 | 62137405.72 | 49113634.74 | 0.156509E+09 | 0.113657E+09 |
April | 86979075.79 | 33036266.70 | 53942809.10 | 0.134593E+09 | 81568120.19 |
May | 77623996.51 | 19977167.26 | 57646829.25 | 0.136055E+09 | 54764239.60 |
June | 73123780.03 | 12916638.79 | 60207141.25 | 0.139228E+09 | 38682128.46 |
July | 77148133.80 | 16113958.21 | 61034175.59 | 0.163441E+09 | 27874731.10 |
August | 87074272.63 | 25935231.05 | 61139041.58 | 0.178546E+09 | 37964668.53 |
September | 99632442.23 | 47416972.06 | 52215470.16 | 0.183266E+09 | 58391327.85 |
October | 0.101084E+09 | 57926003.66 | 43158382.22 | 0.158098E+09 | 85718849.81 |
November | 70939680.48 | 40561203.14 | 30378477.34 | 95108695.88 | 0.106943E+09 |
December | 68684745.30 | 36231638.16 | 32453107.14 | 69577126.97 | 0.165324E+09 |
Annual Sum or Average | 0.101947E+10 | 0.441738E+09 | 0.577732E+09 | 0.159120E+10 | 0.108581E+10 |
Minimum of Months | 68684745.30 | 12916638.79 | 30378477.34 | 69577126.97 | 27874731.10 |
Maximum of Months | 0.111251E+09 | 62137405.72 | 61139041.58 | 0.183266E+09 | 0.168078E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98281190.42 | 58245585.77 | 40035604.65 | 0.106349E+09 | 0.198796E+09 |
February | 0.100100E+09 | 48741733.96 | 51357899.63 | 0.106692E+09 | 0.173558E+09 |
March | 0.133010E+09 | 74290538.02 | 58719515.35 | 0.188033E+09 | 0.134735E+09 |
April | 0.103991E+09 | 39497658.43 | 64493202.82 | 0.161519E+09 | 96771516.27 |
May | 92806070.63 | 23884397.60 | 68921673.03 | 0.162997E+09 | 65174789.99 |
June | 87425680.19 | 15442937.05 | 71982743.14 | 0.166592E+09 | 46141786.11 |
July | 92237136.40 | 19265603.56 | 72971532.84 | 0.195354E+09 | 33305870.16 |
August | 0.104105E+09 | 31007768.12 | 73096909.02 | 0.213461E+09 | 45297271.21 |
September | 0.119119E+09 | 56691011.23 | 62428022.64 | 0.219285E+09 | 69539702.90 |
October | 0.120855E+09 | 69255449.72 | 51599505.94 | 0.189534E+09 | 0.101841E+09 |
November | 84814403.96 | 48494358.10 | 36320045.87 | 0.114190E+09 | 0.126730E+09 |
December | 82118437.73 | 43317995.99 | 38800441.73 | 83863938.07 | 0.195430E+09 |
Annual Sum or Average | 0.121886E+10 | 0.528135E+09 | 0.690727E+09 | 0.190787E+10 | 0.128732E+10 |
Minimum of Months | 82118437.73 | 15442937.05 | 36320045.87 | 83863938.07 | 33305870.16 |
Maximum of Months | 0.133010E+09 | 74290538.02 | 73096909.02 | 0.219285E+09 | 0.198796E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 210.06 | 430.85 | 196.56 | 116.49 | 80.07 | 0.00 | 0.00 |
February | 232.81 | 415.59 | 221.64 | 107.92 | 113.72 | 0.00 | 0.00 |
March | 371.38 | 297.17 | 266.01 | 148.58 | 117.44 | 0.00 | 0.00 |
April | 328.20 | 225.74 | 214.91 | 81.63 | 133.28 | 0.00 | 0.00 |
May | 314.92 | 155.22 | 185.61 | 47.77 | 137.84 | 0.00 | 0.00 |
June | 340.30 | 105.00 | 180.67 | 31.91 | 148.76 | 0.00 | 0.00 |
July | 392.45 | 69.13 | 184.47 | 38.53 | 145.94 | 0.00 | 0.00 |
August | 428.21 | 93.32 | 208.20 | 62.01 | 146.19 | 0.00 | 0.00 |
September | 451.15 | 152.76 | 246.17 | 117.16 | 129.01 | 0.00 | 0.00 |
October | 372.87 | 224.81 | 241.70 | 138.51 | 103.20 | 0.00 | 0.00 |
November | 232.18 | 285.99 | 175.28 | 100.22 | 75.06 | 0.00 | 0.00 |
December | 165.24 | 422.42 | 164.23 | 86.63 | 77.60 | 0.00 | 0.00 |
Annual Sum or Average | 320.50 | 238.91 | 207.03 | 89.71 | 117.33 | 0.00 | 0.00 |
Minimum of Months | 165.24 | 69.13 | 164.23 | 31.91 | 75.06 | 0.00 | 0.00 |
Maximum of Months | 451.15 | 430.85 | 266.01 | 148.58 | 148.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 103.53 | 222.81 | 98.28 | 58.24 | 40.03 | 0.00 | 0.00 |
February | 114.30 | 215.21 | 110.82 | 53.96 | 56.86 | 0.00 | 0.00 |
March | 182.95 | 155.74 | 133.01 | 74.29 | 58.72 | 0.00 | 0.00 |
April | 161.04 | 120.77 | 107.45 | 40.81 | 66.64 | 0.00 | 0.00 |
May | 153.74 | 83.87 | 92.80 | 23.88 | 68.92 | 0.00 | 0.00 |
June | 168.81 | 54.17 | 90.34 | 15.96 | 74.38 | 0.00 | 0.00 |
July | 195.72 | 35.32 | 92.23 | 19.26 | 72.97 | 0.00 | 0.00 |
August | 213.67 | 47.43 | 104.10 | 31.01 | 73.09 | 0.00 | 0.00 |
September | 224.51 | 78.17 | 123.09 | 58.58 | 64.51 | 0.00 | 0.00 |
October | 184.08 | 118.66 | 120.85 | 69.25 | 51.60 | 0.00 | 0.00 |
November | 114.48 | 150.17 | 87.64 | 50.11 | 37.53 | 0.00 | 0.00 |
December | 81.31 | 218.82 | 82.12 | 43.32 | 38.80 | 0.00 | 0.00 |
Annual Sum or Average | 158.44 | 124.62 | 103.52 | 44.85 | 58.66 | 0.00 | 0.00 |
Minimum of Months | 81.31 | 35.32 | 82.12 | 15.96 | 37.53 | 0.00 | 0.00 |
Maximum of Months | 224.51 | 222.81 | 133.01 | 74.29 | 74.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 103.56 | 219.08 | 98.08 | 58.12 | 39.95 | 0.00 | 0.00 |
February | 114.32 | 211.48 | 110.59 | 53.85 | 56.74 | 0.00 | 0.00 |
March | 182.84 | 153.16 | 132.73 | 74.14 | 58.60 | 0.00 | 0.00 |
April | 161.15 | 118.27 | 107.23 | 40.73 | 66.50 | 0.00 | 0.00 |
May | 153.74 | 83.46 | 92.61 | 23.83 | 68.78 | 0.00 | 0.00 |
June | 167.93 | 56.64 | 90.15 | 15.92 | 74.23 | 0.00 | 0.00 |
July | 194.20 | 38.46 | 92.05 | 19.23 | 72.82 | 0.00 | 0.00 |
August | 212.63 | 50.61 | 103.89 | 30.94 | 72.94 | 0.00 | 0.00 |
September | 223.96 | 80.39 | 122.83 | 58.46 | 64.37 | 0.00 | 0.00 |
October | 184.29 | 116.71 | 120.60 | 69.11 | 51.49 | 0.00 | 0.00 |
November | 114.72 | 147.07 | 87.46 | 50.01 | 37.45 | 0.00 | 0.00 |
December | 81.37 | 215.13 | 81.95 | 43.23 | 38.72 | 0.00 | 0.00 |
Annual Sum or Average | 158.15 | 123.75 | 103.30 | 44.76 | 58.54 | 0.00 | 0.00 |
Minimum of Months | 81.37 | 38.46 | 81.95 | 15.92 | 37.45 | 0.00 | 0.00 |
Maximum of Months | 223.96 | 219.08 | 132.73 | 74.14 | 74.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 103.72 | 217.29 | 98.08 | 58.12 | 39.95 | 0.00 | 0.00 |
February | 114.53 | 209.80 | 110.59 | 53.85 | 56.74 | 0.00 | 0.00 |
March | 183.17 | 151.66 | 132.73 | 74.14 | 58.60 | 0.00 | 0.00 |
April | 161.64 | 116.62 | 107.23 | 40.73 | 66.50 | 0.00 | 0.00 |
May | 154.41 | 81.99 | 92.61 | 23.83 | 68.78 | 0.00 | 0.00 |
June | 168.01 | 56.45 | 90.15 | 15.92 | 74.23 | 0.00 | 0.00 |
July | 194.17 | 38.51 | 92.05 | 19.23 | 72.82 | 0.00 | 0.00 |
August | 212.61 | 50.64 | 103.89 | 30.94 | 72.94 | 0.00 | 0.00 |
September | 224.07 | 80.04 | 122.83 | 58.46 | 64.37 | 0.00 | 0.00 |
October | 184.82 | 115.03 | 120.60 | 69.11 | 51.49 | 0.00 | 0.00 |
November | 115.05 | 145.29 | 87.46 | 50.01 | 37.45 | 0.00 | 0.00 |
December | 81.53 | 213.37 | 81.95 | 43.23 | 38.72 | 0.00 | 0.00 |
Annual Sum or Average | 158.40 | 122.60 | 103.30 | 44.76 | 58.54 | 0.00 | 0.00 |
Minimum of Months | 81.53 | 38.51 | 81.95 | 15.92 | 37.45 | 0.00 | 0.00 |
Maximum of Months | 224.07 | 217.29 | 132.73 | 74.14 | 74.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 103.95 | 215.76 | 98.08 | 58.12 | 39.95 | 0.00 | 0.00 |
February | 114.83 | 208.36 | 110.59 | 53.85 | 56.74 | 0.00 | 0.00 |
March | 183.65 | 150.19 | 132.73 | 74.14 | 58.60 | 0.00 | 0.00 |
April | 162.33 | 114.96 | 107.23 | 40.73 | 66.50 | 0.00 | 0.00 |
May | 155.55 | 80.01 | 92.61 | 23.83 | 68.78 | 0.00 | 0.00 |
June | 168.39 | 55.73 | 90.15 | 15.92 | 74.23 | 0.00 | 0.00 |
July | 194.41 | 38.00 | 92.05 | 19.23 | 72.82 | 0.00 | 0.00 |
August | 212.82 | 50.08 | 103.89 | 30.94 | 72.94 | 0.00 | 0.00 |
September | 224.39 | 79.21 | 122.83 | 58.46 | 64.37 | 0.00 | 0.00 |
October | 185.59 | 113.20 | 120.60 | 69.11 | 51.49 | 0.00 | 0.00 |
November | 115.45 | 143.64 | 87.46 | 50.01 | 37.45 | 0.00 | 0.00 |
December | 81.74 | 211.80 | 81.95 | 43.23 | 38.72 | 0.00 | 0.00 |
Annual Sum or Average | 158.85 | 121.29 | 103.30 | 44.76 | 58.54 | 0.00 | 0.00 |
Minimum of Months | 81.74 | 38.00 | 81.95 | 15.92 | 37.45 | 0.00 | 0.00 |
Maximum of Months | 224.39 | 215.76 | 132.73 | 74.14 | 74.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 209.47 | 421.83 | 196.15 | 116.25 | 79.90 | 0.00 | 0.00 |
February | 232.20 | 407.10 | 221.19 | 107.70 | 113.48 | 0.00 | 0.00 |
March | 370.17 | 292.81 | 265.47 | 148.27 | 117.19 | 0.00 | 0.00 |
April | 327.19 | 222.78 | 214.47 | 81.46 | 133.01 | 0.00 | 0.00 |
May | 314.37 | 153.01 | 185.23 | 47.67 | 137.56 | 0.00 | 0.00 |
June | 336.98 | 107.93 | 180.30 | 31.85 | 148.45 | 0.00 | 0.00 |
July | 387.90 | 73.25 | 184.09 | 38.45 | 145.64 | 0.00 | 0.00 |
August | 424.82 | 97.21 | 207.78 | 61.89 | 145.89 | 0.00 | 0.00 |
September | 449.11 | 154.80 | 245.67 | 116.92 | 128.75 | 0.00 | 0.00 |
October | 373.65 | 220.10 | 241.21 | 138.22 | 102.98 | 0.00 | 0.00 |
November | 232.55 | 280.07 | 174.92 | 100.01 | 74.91 | 0.00 | 0.00 |
December | 165.02 | 414.12 | 163.89 | 86.46 | 77.44 | 0.00 | 0.00 |
Annual Sum or Average | 319.13 | 236.19 | 206.61 | 89.52 | 117.08 | 0.00 | 0.00 |
Minimum of Months | 165.02 | 73.25 | 163.89 | 31.85 | 74.91 | 0.00 | 0.00 |
Maximum of Months | 449.11 | 421.83 | 265.47 | 148.27 | 148.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 104.06 | 212.49 | 98.08 | 58.12 | 39.95 | 0.00 | 0.00 |
February | 115.12 | 205.09 | 110.59 | 53.85 | 56.74 | 0.00 | 0.00 |
March | 184.03 | 147.15 | 132.73 | 74.14 | 58.60 | 0.00 | 0.00 |
April | 162.56 | 112.03 | 107.23 | 40.73 | 66.50 | 0.00 | 0.00 |
May | 155.77 | 77.38 | 92.61 | 23.83 | 68.78 | 0.00 | 0.00 |
June | 167.99 | 53.75 | 90.15 | 15.92 | 74.23 | 0.00 | 0.00 |
July | 193.75 | 36.22 | 92.05 | 19.23 | 72.82 | 0.00 | 0.00 |
August | 212.09 | 48.21 | 103.89 | 30.94 | 72.94 | 0.00 | 0.00 |
September | 223.86 | 77.42 | 122.83 | 58.46 | 64.37 | 0.00 | 0.00 |
October | 185.62 | 110.93 | 120.60 | 69.11 | 51.49 | 0.00 | 0.00 |
November | 115.66 | 140.80 | 87.46 | 50.01 | 37.45 | 0.00 | 0.00 |
December | 81.89 | 208.60 | 81.95 | 43.23 | 38.72 | 0.00 | 0.00 |
Annual Sum or Average | 158.79 | 118.72 | 103.30 | 44.76 | 58.54 | 0.00 | 0.00 |
Minimum of Months | 81.89 | 36.22 | 81.95 | 15.92 | 37.45 | 0.00 | 0.00 |
Maximum of Months | 223.86 | 212.49 | 132.73 | 74.14 | 74.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 104.12 | 212.12 | 98.08 | 58.12 | 39.95 | 0.00 | 0.00 |
February | 115.19 | 204.77 | 110.59 | 53.85 | 56.74 | 0.00 | 0.00 |
March | 184.17 | 146.70 | 132.73 | 74.14 | 58.60 | 0.00 | 0.00 |
April | 162.79 | 111.47 | 107.23 | 40.73 | 66.50 | 0.00 | 0.00 |
May | 156.22 | 76.69 | 92.61 | 23.83 | 68.78 | 0.00 | 0.00 |
June | 168.24 | 53.39 | 90.15 | 15.92 | 74.23 | 0.00 | 0.00 |
July | 193.90 | 36.01 | 92.05 | 19.23 | 72.82 | 0.00 | 0.00 |
August | 212.21 | 48.00 | 103.89 | 30.94 | 72.94 | 0.00 | 0.00 |
September | 224.00 | 77.12 | 122.83 | 58.46 | 64.37 | 0.00 | 0.00 |
October | 185.83 | 110.46 | 120.60 | 69.11 | 51.49 | 0.00 | 0.00 |
November | 115.77 | 140.35 | 87.46 | 50.01 | 37.45 | 0.00 | 0.00 |
December | 81.94 | 208.23 | 81.95 | 43.23 | 38.72 | 0.00 | 0.00 |
Annual Sum or Average | 158.96 | 118.32 | 103.30 | 44.76 | 58.54 | 0.00 | 0.00 |
Minimum of Months | 81.94 | 36.01 | 81.95 | 15.92 | 37.45 | 0.00 | 0.00 |
Maximum of Months | 224.00 | 212.12 | 132.73 | 74.14 | 74.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 104.41 | 209.85 | 98.08 | 58.12 | 39.95 | 0.00 | 0.00 |
February | 115.56 | 202.68 | 110.59 | 53.85 | 56.74 | 0.00 | 0.00 |
March | 184.80 | 144.46 | 132.73 | 74.14 | 58.60 | 0.00 | 0.00 |
April | 163.66 | 109.02 | 107.23 | 40.73 | 66.50 | 0.00 | 0.00 |
May | 158.02 | 73.67 | 92.61 | 23.83 | 68.78 | 0.00 | 0.00 |
June | 169.10 | 52.09 | 90.15 | 15.92 | 74.23 | 0.00 | 0.00 |
July | 194.23 | 35.41 | 92.05 | 19.23 | 72.82 | 0.00 | 0.00 |
August | 212.47 | 47.42 | 103.89 | 30.94 | 72.94 | 0.00 | 0.00 |
September | 224.51 | 75.94 | 122.83 | 58.46 | 64.37 | 0.00 | 0.00 |
October | 186.71 | 108.31 | 120.60 | 69.11 | 51.49 | 0.00 | 0.00 |
November | 116.18 | 138.40 | 87.46 | 50.01 | 37.45 | 0.00 | 0.00 |
December | 82.19 | 206.04 | 81.95 | 43.23 | 38.72 | 0.00 | 0.00 |
Annual Sum or Average | 159.58 | 116.49 | 103.30 | 44.76 | 58.54 | 0.00 | 0.00 |
Minimum of Months | 82.19 | 35.41 | 81.95 | 15.92 | 37.45 | 0.00 | 0.00 |
Maximum of Months | 224.51 | 209.85 | 132.73 | 74.14 | 74.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 105.69 | 199.73 | 98.08 | 58.12 | 39.95 | 0.00 | 0.00 |
February | 117.19 | 193.14 | 110.59 | 53.85 | 56.74 | 0.00 | 0.00 |
March | 187.07 | 135.17 | 132.73 | 74.14 | 58.60 | 0.00 | 0.00 |
April | 166.17 | 100.27 | 107.23 | 40.73 | 66.50 | 0.00 | 0.00 |
May | 162.45 | 65.23 | 92.61 | 23.83 | 68.78 | 0.00 | 0.00 |
June | 171.70 | 47.65 | 90.15 | 15.92 | 74.23 | 0.00 | 0.00 |
July | 194.98 | 33.25 | 92.05 | 19.23 | 72.82 | 0.00 | 0.00 |
August | 213.02 | 45.26 | 103.89 | 30.94 | 72.94 | 0.00 | 0.00 |
September | 226.01 | 71.88 | 122.83 | 58.46 | 64.37 | 0.00 | 0.00 |
October | 188.82 | 102.03 | 120.60 | 69.11 | 51.49 | 0.00 | 0.00 |
November | 117.44 | 131.41 | 87.46 | 50.01 | 37.45 | 0.00 | 0.00 |
December | 83.26 | 196.41 | 81.95 | 43.23 | 38.72 | 0.00 | 0.00 |
Annual Sum or Average | 161.41 | 109.68 | 103.30 | 44.76 | 58.54 | 0.00 | 0.00 |
Minimum of Months | 83.26 | 33.25 | 81.95 | 15.92 | 37.45 | 0.00 | 0.00 |
Maximum of Months | 226.01 | 199.73 | 132.73 | 74.14 | 74.23 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.562618E+09 | 0.115398E+10 | 0.526456E+09 | 0.312000E+09 | 0.214456E+09 | 0.00 | 0.00 |
February | 0.563205E+09 | 0.100539E+10 | 0.536197E+09 | 0.261092E+09 | 0.275105E+09 | 0.00 | 0.00 |
March | 0.994696E+09 | 0.795950E+09 | 0.712486E+09 | 0.397947E+09 | 0.314539E+09 | 0.00 | 0.00 |
April | 0.850706E+09 | 0.585111E+09 | 0.557041E+09 | 0.211574E+09 | 0.345466E+09 | 0.00 | 0.00 |
May | 0.843475E+09 | 0.415748E+09 | 0.497128E+09 | 0.127940E+09 | 0.369188E+09 | 0.00 | 0.00 |
June | 0.882058E+09 | 0.272163E+09 | 0.468307E+09 | 82722131.86 | 0.385585E+09 | 0.00 | 0.00 |
July | 0.105114E+10 | 0.185164E+09 | 0.494080E+09 | 0.103199E+09 | 0.390882E+09 | 0.00 | 0.00 |
August | 0.114693E+10 | 0.249954E+09 | 0.557650E+09 | 0.166097E+09 | 0.391553E+09 | 0.00 | 0.00 |
September | 0.116937E+10 | 0.395950E+09 | 0.638077E+09 | 0.303673E+09 | 0.334404E+09 | 0.00 | 0.00 |
October | 0.998707E+09 | 0.602125E+09 | 0.647376E+09 | 0.370976E+09 | 0.276400E+09 | 0.00 | 0.00 |
November | 0.601800E+09 | 0.741294E+09 | 0.454320E+09 | 0.259766E+09 | 0.194553E+09 | 0.00 | 0.00 |
December | 0.442587E+09 | 0.113141E+10 | 0.439878E+09 | 0.232039E+09 | 0.207840E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101073E+11 | 0.753424E+10 | 0.652900E+10 | 0.282903E+10 | 0.369997E+10 | 0.00 | 0.00 |
Minimum of Months | 0.442587E+09 | 0.185164E+09 | 0.439878E+09 | 82722131.86 | 0.194553E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116937E+10 | 0.115398E+10 | 0.712486E+09 | 0.397947E+09 | 0.391553E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.277296E+09 | 0.596769E+09 | 0.263228E+09 | 0.156000E+09 | 0.107228E+09 | 0.00 | 0.00 |
February | 0.276505E+09 | 0.520645E+09 | 0.268098E+09 | 0.130546E+09 | 0.137553E+09 | 0.00 | 0.00 |
March | 0.490000E+09 | 0.417137E+09 | 0.356243E+09 | 0.198974E+09 | 0.157269E+09 | 0.00 | 0.00 |
April | 0.417403E+09 | 0.313047E+09 | 0.278520E+09 | 0.105787E+09 | 0.172733E+09 | 0.00 | 0.00 |
May | 0.411785E+09 | 0.224639E+09 | 0.248564E+09 | 63969965.07 | 0.184594E+09 | 0.00 | 0.00 |
June | 0.437551E+09 | 0.140419E+09 | 0.234154E+09 | 41361065.93 | 0.192793E+09 | 0.00 | 0.00 |
July | 0.524204E+09 | 94607185.66 | 0.247040E+09 | 51599374.94 | 0.195441E+09 | 0.00 | 0.00 |
August | 0.572285E+09 | 0.127049E+09 | 0.278825E+09 | 83048602.58 | 0.195777E+09 | 0.00 | 0.00 |
September | 0.581935E+09 | 0.202617E+09 | 0.319038E+09 | 0.151836E+09 | 0.167202E+09 | 0.00 | 0.00 |
October | 0.493035E+09 | 0.317815E+09 | 0.323688E+09 | 0.185488E+09 | 0.138200E+09 | 0.00 | 0.00 |
November | 0.296724E+09 | 0.389253E+09 | 0.227160E+09 | 0.129883E+09 | 97276561.24 | 0.00 | 0.00 |
December | 0.217780E+09 | 0.586088E+09 | 0.219939E+09 | 0.116019E+09 | 0.103920E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.499650E+10 | 0.393008E+10 | 0.326450E+10 | 0.141451E+10 | 0.184999E+10 | 0.00 | 0.00 |
Minimum of Months | 0.217780E+09 | 94607185.66 | 0.219939E+09 | 41361065.93 | 97276561.24 | 0.00 | 0.00 |
Maximum of Months | 0.581935E+09 | 0.596769E+09 | 0.356243E+09 | 0.198974E+09 | 0.195777E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.277381E+09 | 0.586775E+09 | 0.262688E+09 | 0.155680E+09 | 0.107008E+09 | 0.00 | 0.00 |
February | 0.276554E+09 | 0.511617E+09 | 0.267548E+09 | 0.130278E+09 | 0.137270E+09 | 0.00 | 0.00 |
March | 0.489716E+09 | 0.410225E+09 | 0.355512E+09 | 0.198565E+09 | 0.156947E+09 | 0.00 | 0.00 |
April | 0.417707E+09 | 0.306547E+09 | 0.277949E+09 | 0.105570E+09 | 0.172379E+09 | 0.00 | 0.00 |
May | 0.411781E+09 | 0.223533E+09 | 0.248054E+09 | 63838732.12 | 0.184215E+09 | 0.00 | 0.00 |
June | 0.435276E+09 | 0.146817E+09 | 0.233673E+09 | 41276214.63 | 0.192397E+09 | 0.00 | 0.00 |
July | 0.520132E+09 | 0.102999E+09 | 0.246533E+09 | 51493519.98 | 0.195040E+09 | 0.00 | 0.00 |
August | 0.569497E+09 | 0.135551E+09 | 0.278253E+09 | 82878230.23 | 0.195375E+09 | 0.00 | 0.00 |
September | 0.580515E+09 | 0.208381E+09 | 0.318384E+09 | 0.151525E+09 | 0.166859E+09 | 0.00 | 0.00 |
October | 0.493594E+09 | 0.312587E+09 | 0.323024E+09 | 0.185107E+09 | 0.137916E+09 | 0.00 | 0.00 |
November | 0.297359E+09 | 0.381202E+09 | 0.226694E+09 | 0.129617E+09 | 97077000.55 | 0.00 | 0.00 |
December | 0.217952E+09 | 0.576195E+09 | 0.219488E+09 | 0.115781E+09 | 0.103707E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.498746E+10 | 0.390243E+10 | 0.325780E+10 | 0.141161E+10 | 0.184619E+10 | 0.00 | 0.00 |
Minimum of Months | 0.217952E+09 | 0.102999E+09 | 0.219488E+09 | 41276214.63 | 97077000.55 | 0.00 | 0.00 |
Maximum of Months | 0.580515E+09 | 0.586775E+09 | 0.355512E+09 | 0.198565E+09 | 0.195375E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.277814E+09 | 0.581988E+09 | 0.262688E+09 | 0.155680E+09 | 0.107008E+09 | 0.00 | 0.00 |
February | 0.277078E+09 | 0.507556E+09 | 0.267548E+09 | 0.130278E+09 | 0.137270E+09 | 0.00 | 0.00 |
March | 0.490595E+09 | 0.406211E+09 | 0.355512E+09 | 0.198565E+09 | 0.156947E+09 | 0.00 | 0.00 |
April | 0.418973E+09 | 0.302273E+09 | 0.277949E+09 | 0.105570E+09 | 0.172379E+09 | 0.00 | 0.00 |
May | 0.413573E+09 | 0.219589E+09 | 0.248054E+09 | 63838732.12 | 0.184215E+09 | 0.00 | 0.00 |
June | 0.435484E+09 | 0.146308E+09 | 0.233673E+09 | 41276214.63 | 0.192397E+09 | 0.00 | 0.00 |
July | 0.520069E+09 | 0.103146E+09 | 0.246533E+09 | 51493519.98 | 0.195040E+09 | 0.00 | 0.00 |
August | 0.569467E+09 | 0.135624E+09 | 0.278253E+09 | 82878230.23 | 0.195375E+09 | 0.00 | 0.00 |
September | 0.580781E+09 | 0.207470E+09 | 0.318384E+09 | 0.151525E+09 | 0.166859E+09 | 0.00 | 0.00 |
October | 0.495027E+09 | 0.308084E+09 | 0.323024E+09 | 0.185107E+09 | 0.137916E+09 | 0.00 | 0.00 |
November | 0.298208E+09 | 0.376580E+09 | 0.226694E+09 | 0.129617E+09 | 97077000.55 | 0.00 | 0.00 |
December | 0.218377E+09 | 0.571482E+09 | 0.219488E+09 | 0.115781E+09 | 0.103707E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.499545E+10 | 0.386631E+10 | 0.325780E+10 | 0.141161E+10 | 0.184619E+10 | 0.00 | 0.00 |
Minimum of Months | 0.218377E+09 | 0.103146E+09 | 0.219488E+09 | 41276214.63 | 97077000.55 | 0.00 | 0.00 |
Maximum of Months | 0.580781E+09 | 0.581988E+09 | 0.355512E+09 | 0.198565E+09 | 0.195375E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.278421E+09 | 0.577893E+09 | 0.262688E+09 | 0.155680E+09 | 0.107008E+09 | 0.00 | 0.00 |
February | 0.277806E+09 | 0.504057E+09 | 0.267548E+09 | 0.130278E+09 | 0.137270E+09 | 0.00 | 0.00 |
March | 0.491901E+09 | 0.402277E+09 | 0.355512E+09 | 0.198565E+09 | 0.156947E+09 | 0.00 | 0.00 |
April | 0.420764E+09 | 0.297978E+09 | 0.277949E+09 | 0.105570E+09 | 0.172379E+09 | 0.00 | 0.00 |
May | 0.416622E+09 | 0.214289E+09 | 0.248054E+09 | 63838732.12 | 0.184215E+09 | 0.00 | 0.00 |
June | 0.436477E+09 | 0.144444E+09 | 0.233673E+09 | 41276214.63 | 0.192397E+09 | 0.00 | 0.00 |
July | 0.520712E+09 | 0.101768E+09 | 0.246533E+09 | 51493519.98 | 0.195040E+09 | 0.00 | 0.00 |
August | 0.570027E+09 | 0.134138E+09 | 0.278253E+09 | 82878230.23 | 0.195375E+09 | 0.00 | 0.00 |
September | 0.581627E+09 | 0.205310E+09 | 0.318384E+09 | 0.151525E+09 | 0.166859E+09 | 0.00 | 0.00 |
October | 0.497083E+09 | 0.303207E+09 | 0.323024E+09 | 0.185107E+09 | 0.137916E+09 | 0.00 | 0.00 |
November | 0.299240E+09 | 0.372303E+09 | 0.226694E+09 | 0.129617E+09 | 97077000.55 | 0.00 | 0.00 |
December | 0.218930E+09 | 0.567292E+09 | 0.219488E+09 | 0.115781E+09 | 0.103707E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.500961E+10 | 0.382496E+10 | 0.325780E+10 | 0.141161E+10 | 0.184619E+10 | 0.00 | 0.00 |
Minimum of Months | 0.218930E+09 | 0.101768E+09 | 0.219488E+09 | 41276214.63 | 97077000.55 | 0.00 | 0.00 |
Maximum of Months | 0.581627E+09 | 0.577893E+09 | 0.355512E+09 | 0.198565E+09 | 0.195375E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.561054E+09 | 0.112982E+10 | 0.525376E+09 | 0.311360E+09 | 0.214016E+09 | 0.00 | 0.00 |
February | 0.561727E+09 | 0.984850E+09 | 0.535097E+09 | 0.260556E+09 | 0.274541E+09 | 0.00 | 0.00 |
March | 0.991461E+09 | 0.784272E+09 | 0.711024E+09 | 0.397131E+09 | 0.313894E+09 | 0.00 | 0.00 |
April | 0.848078E+09 | 0.577438E+09 | 0.555898E+09 | 0.211140E+09 | 0.344758E+09 | 0.00 | 0.00 |
May | 0.842014E+09 | 0.409814E+09 | 0.496108E+09 | 0.127677E+09 | 0.368431E+09 | 0.00 | 0.00 |
June | 0.873444E+09 | 0.279752E+09 | 0.467346E+09 | 82552429.26 | 0.384794E+09 | 0.00 | 0.00 |
July | 0.103896E+10 | 0.196190E+09 | 0.493067E+09 | 0.102987E+09 | 0.390080E+09 | 0.00 | 0.00 |
August | 0.113784E+10 | 0.260366E+09 | 0.556506E+09 | 0.165756E+09 | 0.390750E+09 | 0.00 | 0.00 |
September | 0.116409E+10 | 0.401232E+09 | 0.636768E+09 | 0.303050E+09 | 0.333718E+09 | 0.00 | 0.00 |
October | 0.100078E+10 | 0.589506E+09 | 0.646047E+09 | 0.370215E+09 | 0.275833E+09 | 0.00 | 0.00 |
November | 0.602766E+09 | 0.725943E+09 | 0.453388E+09 | 0.259234E+09 | 0.194154E+09 | 0.00 | 0.00 |
December | 0.441990E+09 | 0.110918E+10 | 0.438976E+09 | 0.231563E+09 | 0.207413E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100642E+11 | 0.744836E+10 | 0.651560E+10 | 0.282322E+10 | 0.369238E+10 | 0.00 | 0.00 |
Minimum of Months | 0.441990E+09 | 0.196190E+09 | 0.438976E+09 | 82552429.26 | 0.194154E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116409E+10 | 0.112982E+10 | 0.711024E+09 | 0.397131E+09 | 0.390750E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.278723E+09 | 0.569125E+09 | 0.262688E+09 | 0.155680E+09 | 0.107008E+09 | 0.00 | 0.00 |
February | 0.278505E+09 | 0.496160E+09 | 0.267548E+09 | 0.130278E+09 | 0.137270E+09 | 0.00 | 0.00 |
March | 0.492904E+09 | 0.394133E+09 | 0.355512E+09 | 0.198565E+09 | 0.156947E+09 | 0.00 | 0.00 |
April | 0.421363E+09 | 0.290371E+09 | 0.277949E+09 | 0.105570E+09 | 0.172379E+09 | 0.00 | 0.00 |
May | 0.417211E+09 | 0.207263E+09 | 0.248054E+09 | 63838732.12 | 0.184215E+09 | 0.00 | 0.00 |
June | 0.435419E+09 | 0.139330E+09 | 0.233673E+09 | 41276214.63 | 0.192397E+09 | 0.00 | 0.00 |
July | 0.518930E+09 | 97009125.03 | 0.246533E+09 | 51493519.98 | 0.195040E+09 | 0.00 | 0.00 |
August | 0.568067E+09 | 0.129132E+09 | 0.278253E+09 | 82878230.23 | 0.195375E+09 | 0.00 | 0.00 |
September | 0.580233E+09 | 0.200682E+09 | 0.318384E+09 | 0.151525E+09 | 0.166859E+09 | 0.00 | 0.00 |
October | 0.497161E+09 | 0.297112E+09 | 0.323024E+09 | 0.185107E+09 | 0.137916E+09 | 0.00 | 0.00 |
November | 0.299779E+09 | 0.364965E+09 | 0.226694E+09 | 0.129617E+09 | 97077000.55 | 0.00 | 0.00 |
December | 0.219339E+09 | 0.558708E+09 | 0.219488E+09 | 0.115781E+09 | 0.103707E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.500764E+10 | 0.374399E+10 | 0.325780E+10 | 0.141161E+10 | 0.184619E+10 | 0.00 | 0.00 |
Minimum of Months | 0.219339E+09 | 97009125.03 | 0.219488E+09 | 41276214.63 | 97077000.55 | 0.00 | 0.00 |
Maximum of Months | 0.580233E+09 | 0.569125E+09 | 0.355512E+09 | 0.198565E+09 | 0.195375E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.278866E+09 | 0.568154E+09 | 0.262688E+09 | 0.155680E+09 | 0.107008E+09 | 0.00 | 0.00 |
February | 0.278667E+09 | 0.495380E+09 | 0.267548E+09 | 0.130278E+09 | 0.137270E+09 | 0.00 | 0.00 |
March | 0.493291E+09 | 0.392933E+09 | 0.355512E+09 | 0.198565E+09 | 0.156947E+09 | 0.00 | 0.00 |
April | 0.421944E+09 | 0.288942E+09 | 0.277949E+09 | 0.105570E+09 | 0.172379E+09 | 0.00 | 0.00 |
May | 0.418409E+09 | 0.205398E+09 | 0.248054E+09 | 63838732.12 | 0.184215E+09 | 0.00 | 0.00 |
June | 0.436081E+09 | 0.138390E+09 | 0.233673E+09 | 41276214.63 | 0.192397E+09 | 0.00 | 0.00 |
July | 0.519343E+09 | 96451029.99 | 0.246533E+09 | 51493519.98 | 0.195040E+09 | 0.00 | 0.00 |
August | 0.568394E+09 | 0.128570E+09 | 0.278253E+09 | 82878230.23 | 0.195375E+09 | 0.00 | 0.00 |
September | 0.580599E+09 | 0.199899E+09 | 0.318384E+09 | 0.151525E+09 | 0.166859E+09 | 0.00 | 0.00 |
October | 0.497719E+09 | 0.295866E+09 | 0.323024E+09 | 0.185107E+09 | 0.137916E+09 | 0.00 | 0.00 |
November | 0.300065E+09 | 0.363778E+09 | 0.226694E+09 | 0.129617E+09 | 97077000.55 | 0.00 | 0.00 |
December | 0.219472E+09 | 0.557713E+09 | 0.219488E+09 | 0.115781E+09 | 0.103707E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.501285E+10 | 0.373147E+10 | 0.325780E+10 | 0.141161E+10 | 0.184619E+10 | 0.00 | 0.00 |
Minimum of Months | 0.219472E+09 | 96451029.99 | 0.219488E+09 | 41276214.63 | 97077000.55 | 0.00 | 0.00 |
Maximum of Months | 0.580599E+09 | 0.568154E+09 | 0.355512E+09 | 0.198565E+09 | 0.195375E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.279641E+09 | 0.562064E+09 | 0.262688E+09 | 0.155680E+09 | 0.107008E+09 | 0.00 | 0.00 |
February | 0.279559E+09 | 0.490325E+09 | 0.267548E+09 | 0.130278E+09 | 0.137270E+09 | 0.00 | 0.00 |
March | 0.494974E+09 | 0.386923E+09 | 0.355512E+09 | 0.198565E+09 | 0.156947E+09 | 0.00 | 0.00 |
April | 0.424195E+09 | 0.282569E+09 | 0.277949E+09 | 0.105570E+09 | 0.172379E+09 | 0.00 | 0.00 |
May | 0.423244E+09 | 0.197323E+09 | 0.248054E+09 | 63838732.12 | 0.184215E+09 | 0.00 | 0.00 |
June | 0.438303E+09 | 0.135013E+09 | 0.233673E+09 | 41276214.63 | 0.192397E+09 | 0.00 | 0.00 |
July | 0.520231E+09 | 94840151.73 | 0.246533E+09 | 51493519.98 | 0.195040E+09 | 0.00 | 0.00 |
August | 0.569081E+09 | 0.127001E+09 | 0.278253E+09 | 82878230.23 | 0.195375E+09 | 0.00 | 0.00 |
September | 0.581924E+09 | 0.196825E+09 | 0.318384E+09 | 0.151525E+09 | 0.166859E+09 | 0.00 | 0.00 |
October | 0.500090E+09 | 0.290102E+09 | 0.323024E+09 | 0.185107E+09 | 0.137916E+09 | 0.00 | 0.00 |
November | 0.301146E+09 | 0.358725E+09 | 0.226694E+09 | 0.129617E+09 | 97077000.55 | 0.00 | 0.00 |
December | 0.220145E+09 | 0.551854E+09 | 0.219488E+09 | 0.115781E+09 | 0.103707E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.503253E+10 | 0.367356E+10 | 0.325780E+10 | 0.141161E+10 | 0.184619E+10 | 0.00 | 0.00 |
Minimum of Months | 0.220145E+09 | 94840151.73 | 0.219488E+09 | 41276214.63 | 97077000.55 | 0.00 | 0.00 |
Maximum of Months | 0.581924E+09 | 0.562064E+09 | 0.355512E+09 | 0.198565E+09 | 0.195375E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.283076E+09 | 0.534951E+09 | 0.262688E+09 | 0.155680E+09 | 0.107008E+09 | 0.00 | 0.00 |
February | 0.283517E+09 | 0.467246E+09 | 0.267548E+09 | 0.130278E+09 | 0.137270E+09 | 0.00 | 0.00 |
March | 0.501049E+09 | 0.362048E+09 | 0.355512E+09 | 0.198565E+09 | 0.156947E+09 | 0.00 | 0.00 |
April | 0.430702E+09 | 0.259905E+09 | 0.277949E+09 | 0.105570E+09 | 0.172379E+09 | 0.00 | 0.00 |
May | 0.435106E+09 | 0.174703E+09 | 0.248054E+09 | 63838732.12 | 0.184215E+09 | 0.00 | 0.00 |
June | 0.445047E+09 | 0.123506E+09 | 0.233673E+09 | 41276214.63 | 0.192397E+09 | 0.00 | 0.00 |
July | 0.522236E+09 | 89055106.91 | 0.246533E+09 | 51493519.98 | 0.195040E+09 | 0.00 | 0.00 |
August | 0.570552E+09 | 0.121227E+09 | 0.278253E+09 | 82878230.23 | 0.195375E+09 | 0.00 | 0.00 |
September | 0.585817E+09 | 0.186322E+09 | 0.318384E+09 | 0.151525E+09 | 0.166859E+09 | 0.00 | 0.00 |
October | 0.505729E+09 | 0.273278E+09 | 0.323024E+09 | 0.185107E+09 | 0.137916E+09 | 0.00 | 0.00 |
November | 0.304406E+09 | 0.340615E+09 | 0.226694E+09 | 0.129617E+09 | 97077000.55 | 0.00 | 0.00 |
December | 0.223016E+09 | 0.526076E+09 | 0.219488E+09 | 0.115781E+09 | 0.103707E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.509026E+10 | 0.345893E+10 | 0.325780E+10 | 0.141161E+10 | 0.184619E+10 | 0.00 | 0.00 |
Minimum of Months | 0.223016E+09 | 89055106.91 | 0.219488E+09 | 41276214.63 | 97077000.55 | 0.00 | 0.00 |
Maximum of Months | 0.585817E+09 | 0.534951E+09 | 0.355512E+09 | 0.198565E+09 | 0.195375E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.379257E+09 | -253687814.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125569466.9 | 58.99 | 0.00 | 0.00 |
February | 0.347415E+09 | -233692104.6 | 0.00 | 0.00 | 672.00 | 0.00 | -113723329.5 | 59.00 | 0.00 | 0.00 |
March | 0.383474E+09 | -259377504.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124096209.5 | 59.00 | 0.00 | 0.00 |
April | 0.357117E+09 | -237979433.5 | 0.00 | 0.00 | 720.00 | 0.00 | -119137769.3 | 58.99 | 0.00 | 0.00 |
May | 0.350126E+09 | -232226402.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117899556.9 | 58.99 | 0.00 | 0.00 |
June | 0.323087E+09 | -213007155.9 | 0.00 | 0.00 | 720.00 | 0.00 | -110080323.3 | 58.99 | 0.00 | 0.00 |
July | 0.317964E+09 | -205144936.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112819433.4 | 58.99 | 0.00 | 0.00 |
August | 0.318326E+09 | -205437961.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112888236.5 | 58.99 | 0.00 | 0.00 |
September | 0.310236E+09 | -200153429.4 | 0.00 | 0.00 | 720.00 | 0.00 | -110082558.2 | 58.99 | 0.00 | 0.00 |
October | 0.335076E+09 | -215137650.0 | 0.00 | 0.00 | 744.00 | 0.00 | -119938732.7 | 58.99 | 0.00 | 0.00 |
November | 0.340363E+09 | -221154712.9 | 0.00 | 0.00 | 720.00 | 0.00 | -119208475.1 | 58.99 | 0.00 | 0.00 |
December | 0.368763E+09 | -243524626.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125238302.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.413121E+10 | -0.272052E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141068E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.310236E+09 | -259377504.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125569466.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.383474E+09 | -200153429.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110080323.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.377986E+09 | -253692689.3 | 0.00 | 0.00 | 744.00 | 0.00 | -124293774.4 | 58.99 | 0.00 | 0.00 |
February | 0.346218E+09 | -233700270.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112517653.9 | 58.99 | 0.00 | 0.00 |
March | 0.381794E+09 | -259383927.4 | 0.00 | 0.00 | 744.00 | 0.00 | -122409630.8 | 59.00 | 0.00 | 0.00 |
April | 0.354799E+09 | -237978978.2 | 0.00 | 0.00 | 720.00 | 0.00 | -116819877.8 | 58.99 | 0.00 | 0.00 |
May | 0.347790E+09 | -232230098.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115560185.9 | 58.99 | 0.00 | 0.00 |
June | 0.322572E+09 | -213015562.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109556491.8 | 58.99 | 0.00 | 0.00 |
July | 0.317830E+09 | -205139863.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112690003.1 | 58.99 | 0.00 | 0.00 |
August | 0.318142E+09 | -205443676.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112698084.2 | 58.99 | 0.00 | 0.00 |
September | 0.309693E+09 | -200156876.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109535630.5 | 58.99 | 0.00 | 0.00 |
October | 0.332893E+09 | -215142820.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117750538.0 | 58.99 | 0.00 | 0.00 |
November | 0.338518E+09 | -221147822.4 | 0.00 | 0.00 | 720.00 | 0.00 | -117370239.1 | 58.99 | 0.00 | 0.00 |
December | 0.367399E+09 | -243522645.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123876338.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.411563E+10 | -0.272056E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139508E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.309693E+09 | -259383927.4 | 0.00 | 0.00 | 672.00 | 0.00 | -124293774.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.381794E+09 | -200156876.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109535630.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.348963E+09 | -223086996.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125875560.4 | 58.99 | 0.00 | 0.00 |
February | 0.319627E+09 | -205660808.4 | 0.00 | 0.00 | 672.00 | 0.00 | -113965995.6 | 59.00 | 0.00 | 0.00 |
March | 0.355196E+09 | -231492216.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123703374.8 | 59.00 | 0.00 | 0.00 |
April | 0.327534E+09 | -209288821.8 | 0.00 | 0.00 | 720.00 | 0.00 | -118245171.6 | 59.00 | 0.00 | 0.00 |
May | 0.322170E+09 | -205991215.7 | 0.00 | 0.00 | 744.00 | 0.00 | -116178399.6 | 58.99 | 0.00 | 0.00 |
June | 0.298487E+09 | -189702345.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108784715.2 | 58.99 | 0.00 | 0.00 |
July | 0.290692E+09 | -179316690.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111375439.8 | 59.00 | 0.00 | 0.00 |
August | 0.295088E+09 | -183513288.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111574362.8 | 58.99 | 0.00 | 0.00 |
September | 0.284969E+09 | -175909360.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109059227.3 | 59.00 | 0.00 | 0.00 |
October | 0.308192E+09 | -189214408.8 | 0.00 | 0.00 | 744.00 | 0.00 | -118977604.8 | 58.99 | 0.00 | 0.00 |
November | 0.314099E+09 | -195255848.3 | 0.00 | 0.00 | 720.00 | 0.00 | -118843522.0 | 58.99 | 0.00 | 0.00 |
December | 0.338016E+09 | -212556261.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125459426.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.380303E+10 | -0.240099E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140204E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284969E+09 | -231492216.4 | 0.00 | 0.00 | 672.00 | 0.00 | -125875560.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.355196E+09 | -175909360.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108784715.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.349311E+09 | -223088013.4 | 0.00 | 0.00 | 744.00 | 0.00 | -126222742.0 | 58.99 | 0.00 | 0.00 |
February | 0.319921E+09 | -205672754.5 | 0.00 | 0.00 | 672.00 | 0.00 | -114248251.5 | 58.99 | 0.00 | 0.00 |
March | 0.355530E+09 | -231506207.7 | 0.00 | 0.00 | 744.00 | 0.00 | -124023407.4 | 58.99 | 0.00 | 0.00 |
April | 0.327943E+09 | -209289919.3 | 0.00 | 0.00 | 720.00 | 0.00 | -118653411.5 | 59.00 | 0.00 | 0.00 |
May | 0.322631E+09 | -205962729.4 | 0.00 | 0.00 | 744.00 | 0.00 | -116668398.8 | 59.00 | 0.00 | 0.00 |
June | 0.298537E+09 | -189704506.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108832611.2 | 58.99 | 0.00 | 0.00 |
July | 0.290670E+09 | -179342676.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111327537.9 | 58.99 | 0.00 | 0.00 |
August | 0.295091E+09 | -183502237.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111588871.6 | 58.99 | 0.00 | 0.00 |
September | 0.285046E+09 | -175917364.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109129042.4 | 58.99 | 0.00 | 0.00 |
October | 0.308651E+09 | -189223717.7 | 0.00 | 0.00 | 744.00 | 0.00 | -119427362.9 | 58.99 | 0.00 | 0.00 |
November | 0.314476E+09 | -195247579.2 | 0.00 | 0.00 | 720.00 | 0.00 | -119228377.7 | 59.00 | 0.00 | 0.00 |
December | 0.338350E+09 | -212564355.3 | 0.00 | 0.00 | 744.00 | 0.00 | -125785238.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.380616E+10 | -0.240102E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140514E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.285046E+09 | -231506207.7 | 0.00 | 0.00 | 672.00 | 0.00 | -126222742.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.355530E+09 | -175917364.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108832611.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.338538E+09 | -210849925.6 | 0.00 | 0.00 | 744.00 | 0.00 | -127688465.3 | 58.99 | 0.00 | 0.00 |
February | 0.310117E+09 | -194481429.8 | 0.00 | 0.00 | 672.00 | 0.00 | -115635094.6 | 59.00 | 0.00 | 0.00 |
March | 0.344487E+09 | -219053552.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125433527.4 | 58.99 | 0.00 | 0.00 |
April | 0.318193E+09 | -198070468.4 | 0.00 | 0.00 | 720.00 | 0.00 | -120122676.2 | 58.99 | 0.00 | 0.00 |
May | 0.313513E+09 | -194801727.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118711487.4 | 58.99 | 0.00 | 0.00 |
June | 0.289146E+09 | -179505766.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109640687.0 | 58.99 | 0.00 | 0.00 |
July | 0.281545E+09 | -169600675.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111944364.2 | 58.99 | 0.00 | 0.00 |
August | 0.285829E+09 | -173624967.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112204450.3 | 58.99 | 0.00 | 0.00 |
September | 0.276439E+09 | -166462847.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109976530.7 | 59.00 | 0.00 | 0.00 |
October | 0.299911E+09 | -178841203.8 | 0.00 | 0.00 | 744.00 | 0.00 | -121069707.3 | 58.99 | 0.00 | 0.00 |
November | 0.304852E+09 | -184431975.2 | 0.00 | 0.00 | 720.00 | 0.00 | -120419559.9 | 58.99 | 0.00 | 0.00 |
December | 0.328227E+09 | -201025411.8 | 0.00 | 0.00 | 744.00 | 0.00 | -127201545.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.369080E+10 | -0.227075E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.142005E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.276439E+09 | -219053552.8 | 0.00 | 0.00 | 672.00 | 0.00 | -127688465.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.344487E+09 | -166462847.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109640687.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.338383E+09 | -210845872.2 | 0.00 | 0.00 | 744.00 | 0.00 | -127537332.4 | 58.99 | 0.00 | 0.00 |
February | 0.309977E+09 | -194478334.8 | 0.00 | 0.00 | 672.00 | 0.00 | -115498392.7 | 59.00 | 0.00 | 0.00 |
March | 0.344324E+09 | -219041548.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125282239.7 | 59.00 | 0.00 | 0.00 |
April | 0.317903E+09 | -198069713.0 | 0.00 | 0.00 | 720.00 | 0.00 | -119833423.9 | 58.99 | 0.00 | 0.00 |
May | 0.312808E+09 | -194807427.0 | 0.00 | 0.00 | 744.00 | 0.00 | -118000982.6 | 58.99 | 0.00 | 0.00 |
June | 0.289071E+09 | -179486097.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109585160.7 | 59.00 | 0.00 | 0.00 |
July | 0.281582E+09 | -169594756.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111986954.3 | 58.99 | 0.00 | 0.00 |
August | 0.285859E+09 | -173626191.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112233064.1 | 58.99 | 0.00 | 0.00 |
September | 0.276277E+09 | -166472206.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109805280.3 | 59.00 | 0.00 | 0.00 |
October | 0.299416E+09 | -178866952.2 | 0.00 | 0.00 | 744.00 | 0.00 | -120549432.4 | 58.98 | 0.00 | 0.00 |
November | 0.304716E+09 | -184407293.1 | 0.00 | 0.00 | 720.00 | 0.00 | -120308743.1 | 59.00 | 0.00 | 0.00 |
December | 0.328088E+09 | -201042812.7 | 0.00 | 0.00 | 744.00 | 0.00 | -127044882.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.368841E+10 | -0.227074E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141767E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.276277E+09 | -219041548.6 | 0.00 | 0.00 | 672.00 | 0.00 | -127537332.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.344324E+09 | -166472206.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109585160.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.338451E+09 | -210848042.3 | 0.00 | 0.00 | 744.00 | 0.00 | -127603009.8 | 58.99 | 0.00 | 0.00 |
February | 0.310032E+09 | -194478751.5 | 0.00 | 0.00 | 672.00 | 0.00 | -115553051.0 | 59.00 | 0.00 | 0.00 |
March | 0.344422E+09 | -219045514.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125376936.0 | 58.99 | 0.00 | 0.00 |
April | 0.318042E+09 | -198059937.0 | 0.00 | 0.00 | 720.00 | 0.00 | -119981798.6 | 59.00 | 0.00 | 0.00 |
May | 0.313043E+09 | -194799014.3 | 0.00 | 0.00 | 744.00 | 0.00 | -118244320.6 | 58.99 | 0.00 | 0.00 |
June | 0.289159E+09 | -179514342.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109644803.0 | 58.99 | 0.00 | 0.00 |
July | 0.281633E+09 | -169595846.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112037076.3 | 58.99 | 0.00 | 0.00 |
August | 0.285917E+09 | -173633158.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112283460.7 | 58.99 | 0.00 | 0.00 |
September | 0.276337E+09 | -166498280.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109839171.8 | 58.98 | 0.00 | 0.00 |
October | 0.299566E+09 | -178807754.2 | 0.00 | 0.00 | 744.00 | 0.00 | -120758346.7 | 59.01 | 0.00 | 0.00 |
November | 0.304806E+09 | -184429219.6 | 0.00 | 0.00 | 720.00 | 0.00 | -120376355.2 | 58.99 | 0.00 | 0.00 |
December | 0.328158E+09 | -201031159.3 | 0.00 | 0.00 | 744.00 | 0.00 | -127126915.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.368957E+10 | -0.227074E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141883E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.276337E+09 | -219045514.2 | 0.00 | 0.00 | 672.00 | 0.00 | -127603009.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.344422E+09 | -166498280.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109644803.0 | 59.01 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 255.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 262.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 339.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 371.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 332.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 430.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 289.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 314.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 258.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.204136E+11 | 54549.74 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193553E+11 | 54549.74 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119274E+11 | 54549.74 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.485847E+10 | 54549.74 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.206096E+09 | 54549.74 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180641E+10 | 54549.74 | 16-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.662517E+10 | 54549.74 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186563E+11 | 54549.74 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.838487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.204136E+11 | 54549.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.737560E+10 | 28665.43 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.698528E+10 | 28665.43 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.396892E+10 | 28665.43 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123657E+10 | 28665.43 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2975314.13 | 2746.18 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.340453E+09 | 28665.43 | 17-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198717E+10 | 28665.43 | 03-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.670064E+10 | 28665.43 | 02-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.737560E+10 | 28665.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.791214E+10 | 31468.55 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.743349E+10 | 31468.55 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.436157E+10 | 31468.55 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152368E+10 | 31468.55 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23319896.51 | 9991.77 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.515959E+09 | 30111.94 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.237175E+10 | 31468.55 | 23-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.718114E+10 | 31468.55 | 02-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.313231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.791214E+10 | 31468.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.812160E+10 | 31430.73 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.761442E+10 | 31430.73 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.451731E+10 | 31430.73 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165570E+10 | 31430.73 | 01-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38157763.17 | 14178.82 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.606532E+09 | 31430.73 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.254449E+10 | 31430.73 | 12-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.737486E+10 | 31430.73 | 02-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.324731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.812160E+10 | 31430.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.848022E+10 | 31399.06 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.793742E+10 | 31399.06 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.480894E+10 | 31399.06 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188201E+10 | 31399.06 | 01-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72343949.15 | 17889.25 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.744864E+09 | 31399.06 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.281573E+10 | 31399.06 | 11-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.771338E+10 | 31399.06 | 02-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.848022E+10 | 31399.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.175569E+11 | 52780.30 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163674E+11 | 52780.30 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101989E+11 | 52780.30 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.431396E+10 | 52780.30 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.253889E+09 | 52780.30 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202303E+10 | 52780.30 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.642037E+10 | 52780.30 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160838E+11 | 52780.30 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.732182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.175569E+11 | 52780.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.863855E+10 | 27671.50 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.808077E+10 | 27671.50 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.481433E+10 | 27671.50 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179824E+10 | 27671.50 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 59255800.20 | 27671.50 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.715826E+09 | 27671.50 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.278506E+10 | 27671.50 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.786183E+10 | 27671.50 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.347539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.863855E+10 | 27671.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.871743E+10 | 27494.23 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.814756E+10 | 27494.23 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.489570E+10 | 27494.23 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186980E+10 | 27494.23 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69896012.28 | 27494.23 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.754883E+09 | 27494.23 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.285490E+10 | 27494.23 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.793883E+10 | 27494.23 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.352490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.871743E+10 | 27494.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.917772E+10 | 27179.05 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.855885E+10 | 27179.05 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.530895E+10 | 27179.05 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219027E+10 | 27179.05 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130482E+09 | 27179.05 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.922777E+09 | 27179.05 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.315558E+10 | 27179.05 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.836385E+10 | 27179.05 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.917772E+10 | 27179.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121652E+11 | 28512.44 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115341E+11 | 28512.44 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.769834E+10 | 28512.44 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.387951E+10 | 28512.44 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.669695E+09 | 28512.44 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2306683.52 | 3863.72 | 14-JUN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17102752.15 | 16973.10 | 30-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181699E+10 | 28512.44 | 08-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.477199E+10 | 28512.44 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111011E+11 | 28512.44 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.536564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121652E+11 | 28512.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.180236E+09 | 0.150336E+09 | 6038.64 | 15-MAR-14:00 | 5386.93 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.585501E+09 | 0.510271E+09 | 8672.83 | 14-MAY-15:00 | 6616.01 | 0.00 |
June | 0.00 | 0.00 | 0.703558E+10 | 0.497668E+10 | 26018.22 | 18-JUN-07:03 | 12418.38 | 0.00 |
July | 0.00 | 0.00 | 0.157051E+11 | 0.102858E+11 | 40790.28 | 21-JUL-07:02 | 20274.71 | 0.00 |
August | 0.00 | 0.00 | 0.121948E+11 | 0.893989E+10 | 39982.28 | 14-AUG-07:03 | 22408.49 | 0.00 |
September | 0.00 | 0.00 | 0.418369E+10 | 0.280903E+10 | 39041.35 | 17-SEP-07:03 | 21283.12 | 0.00 |
October | 0.00 | 0.00 | 92671999.68 | 78935935.29 | 3514.27 | 11-OCT-16:10 | 2945.50 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.399776E+11 | 0.277509E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.157051E+11 | 0.102858E+11 | 40790.28 | 22408.49 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.135493E+09 | 0.113497E+09 | 19093.58 | 15-MAR-20:01 | 15507.14 | 0.00 |
April | 0.00 | 0.00 | 2339604.43 | 2034980.04 | 1807.07 | 09-APR-17:20 | 1483.10 | 0.00 |
May | 0.00 | 0.00 | 0.473112E+09 | 0.416613E+09 | 19636.16 | 14-MAY-18:00 | 12623.47 | 0.00 |
June | 0.00 | 0.00 | 0.458583E+10 | 0.330479E+10 | 21294.51 | 17-JUN-19:03 | 10131.28 | 0.00 |
July | 0.00 | 0.00 | 0.964416E+10 | 0.641453E+10 | 21275.85 | 21-JUL-20:05 | 10179.58 | 0.00 |
August | 0.00 | 0.00 | 0.746312E+10 | 0.549343E+10 | 21181.79 | 15-AUG-07:03 | 11060.69 | 0.00 |
September | 0.00 | 0.00 | 0.274724E+10 | 0.186348E+10 | 21157.46 | 15-SEP-20:03 | 9762.42 | 0.00 |
October | 0.00 | 0.00 | 82895049.13 | 70668689.43 | 19080.83 | 22-OCT-17:09 | 15211.92 | 0.00 |
November | 0.00 | 0.00 | 713206.56 | 570412.43 | 728.05 | 04-NOV-18:40 | 554.53 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.251349E+11 | 0.176796E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.964416E+10 | 0.641453E+10 | 21294.51 | 15507.14 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.110457E+09 | 95744007.97 | 3342.30 | 15-MAR-14:00 | 3109.48 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.343076E+09 | 0.307949E+09 | 4292.42 | 14-MAY-15:00 | 3421.13 | 0.00 |
June | 0.00 | 0.00 | 0.303468E+10 | 0.225739E+10 | 20254.37 | 18-JUN-07:03 | 10043.28 | 0.00 |
July | 0.00 | 0.00 | 0.648138E+10 | 0.445416E+10 | 22956.33 | 21-JUL-06:02 | 12345.08 | 0.00 |
August | 0.00 | 0.00 | 0.517001E+10 | 0.399735E+10 | 22866.20 | 14-AUG-06:03 | 10178.66 | 0.00 |
September | 0.00 | 0.00 | 0.182825E+10 | 0.128861E+10 | 22029.16 | 17-SEP-07:03 | 12371.56 | 0.00 |
October | 0.00 | 0.00 | 38507607.01 | 34599937.13 | 1765.23 | 11-OCT-13:00 | 1644.74 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.170064E+11 | 0.124358E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.648138E+10 | 0.445416E+10 | 22956.33 | 12371.56 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.101397E+09 | 88290310.93 | 3176.55 | 15-MAR-14:00 | 2962.65 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.316423E+09 | 0.284661E+09 | 4090.78 | 14-MAY-15:00 | 3259.83 | 0.00 |
June | 0.00 | 0.00 | 0.300890E+10 | 0.224176E+10 | 19795.43 | 18-JUN-07:03 | 9828.04 | 0.00 |
July | 0.00 | 0.00 | 0.647884E+10 | 0.446106E+10 | 22771.29 | 21-JUL-06:02 | 12299.66 | 0.00 |
August | 0.00 | 0.00 | 0.516462E+10 | 0.400237E+10 | 22676.25 | 14-AUG-06:03 | 10116.61 | 0.00 |
September | 0.00 | 0.00 | 0.180270E+10 | 0.127305E+10 | 21845.55 | 17-SEP-07:03 | 12301.35 | 0.00 |
October | 0.00 | 0.00 | 30527036.82 | 27549037.03 | 1501.38 | 11-OCT-13:00 | 1403.80 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169034E+11 | 0.123787E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.647884E+10 | 0.446106E+10 | 22771.29 | 12301.35 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 88131686.51 | 76621878.78 | 2928.76 | 15-MAR-14:00 | 2717.68 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.266404E+09 | 0.238849E+09 | 3786.38 | 14-MAY-15:00 | 2993.11 | 0.00 |
June | 0.00 | 0.00 | 0.287499E+10 | 0.213148E+10 | 16780.40 | 18-JUN-07:03 | 8224.71 | 0.00 |
July | 0.00 | 0.00 | 0.628231E+10 | 0.431212E+10 | 22887.61 | 21-JUL-06:02 | 12207.61 | 0.00 |
August | 0.00 | 0.00 | 0.500028E+10 | 0.386586E+10 | 22802.77 | 14-AUG-06:03 | 10125.55 | 0.00 |
September | 0.00 | 0.00 | 0.169358E+10 | 0.119130E+10 | 21967.39 | 17-SEP-07:03 | 12311.26 | 0.00 |
October | 0.00 | 0.00 | 20549901.52 | 18508011.17 | 1158.75 | 11-OCT-13:00 | 1078.89 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.162263E+11 | 0.118347E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.628231E+10 | 0.431212E+10 | 22887.61 | 12311.26 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.152757E+09 | 0.125729E+09 | 5930.38 | 15-MAR-14:10 | 5227.32 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.469204E+09 | 0.407425E+09 | 8008.55 | 14-MAY-15:00 | 6008.39 | 0.00 |
June | 0.00 | 0.00 | 0.537695E+10 | 0.380157E+10 | 34390.18 | 18-JUN-08:63 | 18039.31 | 0.00 |
July | 0.00 | 0.00 | 0.119117E+11 | 0.784077E+10 | 39887.47 | 16-JUL-08:62 | 20332.66 | 0.00 |
August | 0.00 | 0.00 | 0.948224E+10 | 0.704130E+10 | 39931.96 | 14-AUG-07:03 | 20426.45 | 0.00 |
September | 0.00 | 0.00 | 0.314363E+10 | 0.213183E+10 | 33406.40 | 17-SEP-08:63 | 17591.67 | 0.00 |
October | 0.00 | 0.00 | 39165573.16 | 33702446.82 | 2670.27 | 11-OCT-15:00 | 2275.44 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.305756E+11 | 0.213823E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.119117E+11 | 0.784077E+10 | 39931.96 | 20426.45 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.102152E+09 | 88262180.33 | 3509.55 | 15-MAR-14:10 | 3245.98 | 0.00 |
April | 0.00 | 0.00 | 37.96 | 35.36 | 0.06 | 08-APR-13:00 | 0.06 | 0.00 |
May | 0.00 | 0.00 | 0.263208E+09 | 0.234694E+09 | 4664.68 | 14-MAY-15:00 | 3665.21 | 0.00 |
June | 0.00 | 0.00 | 0.290273E+10 | 0.215603E+10 | 17209.82 | 18-JUN-08:63 | 9133.60 | 0.00 |
July | 0.00 | 0.00 | 0.644608E+10 | 0.446022E+10 | 20904.74 | 16-JUL-08:62 | 10637.61 | 0.00 |
August | 0.00 | 0.00 | 0.510184E+10 | 0.397970E+10 | 20933.03 | 14-AUG-07:03 | 10698.29 | 0.00 |
September | 0.00 | 0.00 | 0.159442E+10 | 0.113384E+10 | 16093.88 | 17-SEP-08:63 | 8579.75 | 0.00 |
October | 0.00 | 0.00 | 19674317.95 | 18033357.80 | 1434.60 | 11-OCT-15:00 | 1299.09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.164301E+11 | 0.120708E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.644608E+10 | 0.446022E+10 | 20933.03 | 10698.29 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 98898363.66 | 85438228.85 | 3457.16 | 15-MAR-14:10 | 3194.36 | 0.00 |
April | 0.00 | 0.00 | 2779.79 | 2482.82 | 4.46 | 08-APR-15:10 | 3.98 | 0.00 |
May | 0.00 | 0.00 | 0.248677E+09 | 0.221184E+09 | 4563.48 | 14-MAY-15:00 | 3579.18 | 0.00 |
June | 0.00 | 0.00 | 0.284788E+10 | 0.211081E+10 | 15881.40 | 18-JUN-08:63 | 8408.63 | 0.00 |
July | 0.00 | 0.00 | 0.636894E+10 | 0.440167E+10 | 20769.49 | 16-JUL-08:62 | 10533.37 | 0.00 |
August | 0.00 | 0.00 | 0.504268E+10 | 0.393040E+10 | 20796.85 | 14-AUG-07:03 | 10595.76 | 0.00 |
September | 0.00 | 0.00 | 0.156543E+10 | 0.111228E+10 | 15542.24 | 17-SEP-08:63 | 8286.15 | 0.00 |
October | 0.00 | 0.00 | 18479774.64 | 16924470.69 | 1379.39 | 11-OCT-15:00 | 1247.81 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161910E+11 | 0.118787E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.636894E+10 | 0.440167E+10 | 20796.85 | 10595.76 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 85345177.90 | 73774678.40 | 3232.01 | 15-MAR-14:10 | 2977.74 | 0.00 |
April | 0.00 | 0.00 | 4034.00 | 3724.12 | 6.72 | 08-APR-13:20 | 6.21 | 0.00 |
May | 0.00 | 0.00 | 0.196313E+09 | 0.173083E+09 | 4224.75 | 14-MAY-15:00 | 3296.63 | 0.00 |
June | 0.00 | 0.00 | 0.268488E+10 | 0.198036E+10 | 11320.76 | 27-JUN-13:00 | 7214.82 | 0.00 |
July | 0.00 | 0.00 | 0.616706E+10 | 0.425499E+10 | 20505.95 | 16-JUL-08:62 | 10269.45 | 0.00 |
August | 0.00 | 0.00 | 0.489454E+10 | 0.381297E+10 | 20531.55 | 14-AUG-07:03 | 10335.39 | 0.00 |
September | 0.00 | 0.00 | 0.147721E+10 | 0.104850E+10 | 13420.96 | 17-SEP-08:63 | 7171.87 | 0.00 |
October | 0.00 | 0.00 | 13855455.73 | 12674463.47 | 1173.05 | 11-OCT-15:00 | 1059.81 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.155192E+11 | 0.113564E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.616706E+10 | 0.425499E+10 | 20531.55 | 10335.39 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 39048904.40 | 33145343.17 | 2309.96 | 15-MAR-14:10 | 2036.89 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 86115582.65 | 72272896.60 | 3031.40 | 14-MAY-15:00 | 2244.73 | 0.00 |
June | 0.00 | 0.00 | 0.231502E+10 | 0.162512E+10 | 11251.06 | 27-JUN-13:00 | 6917.88 | 0.00 |
July | 0.00 | 0.00 | 0.572159E+10 | 0.379136E+10 | 21835.10 | 21-JUL-07:02 | 9714.56 | 0.00 |
August | 0.00 | 0.00 | 0.462766E+10 | 0.347453E+10 | 21615.40 | 14-AUG-07:03 | 10070.90 | 0.00 |
September | 0.00 | 0.00 | 0.136805E+10 | 0.933655E+09 | 8938.94 | 17-SEP-08:63 | 4535.57 | 0.00 |
October | 0.00 | 0.00 | 8671234.04 | 7526662.89 | 898.64 | 11-OCT-15:00 | 770.03 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.141662E+11 | 0.993761E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.572159E+10 | 0.379136E+10 | 21835.10 | 10070.90 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166410E+10 | 0.45 | 1747.18 | 01-JAN-08:61 | 0.90 |
February | 0.152315E+10 | 0.45 | 1747.18 | 01-FEB-08:61 | 0.90 |
March | 0.150463E+10 | 0.42 | 1747.18 | 01-MAR-08:61 | 0.90 |
April | 0.132197E+10 | 0.39 | 1747.18 | 01-APR-07:01 | 0.90 |
May | 0.127199E+10 | 0.37 | 1747.18 | 01-MAY-07:01 | 0.89 |
June | 0.123297E+10 | 0.37 | 1012.81 | 18-JUN-07:03 | 0.67 |
July | 0.127102E+10 | 0.37 | 1747.18 | 16-JUL-07:03 | 0.88 |
August | 0.127175E+10 | 0.37 | 1747.18 | 14-AUG-07:03 | 0.88 |
September | 0.123047E+10 | 0.37 | 1747.18 | 17-SEP-07:03 | 0.89 |
October | 0.130285E+10 | 0.38 | 1747.18 | 16-OCT-07:01 | 0.90 |
November | 0.135307E+10 | 0.39 | 1747.18 | 02-NOV-07:01 | 0.90 |
December | 0.163458E+10 | 0.44 | 1747.18 | 01-DEC-08:61 | 0.90 |
Annual Sum or Average | 0.165826E+11 | 0.40 | |||
Minimum of Months | 0.123047E+10 | 0.37 | 1012.81 | 0.67 | |
Maximum of Months | 0.166410E+10 | 0.45 | 1747.18 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.688552E+09 | 0.39 | 984.68 | 01-JAN-08:61 | 0.93 |
February | 0.630023E+09 | 0.41 | 984.68 | 01-FEB-08:61 | 0.93 |
March | 0.632767E+09 | 0.34 | 984.68 | 01-MAR-08:61 | 0.93 |
April | 0.553559E+09 | 0.31 | 984.68 | 01-APR-07:01 | 0.93 |
May | 0.635767E+09 | 0.37 | 450.47 | 01-MAY-07:01 | 0.61 |
June | 0.636126E+09 | 0.37 | 860.65 | 18-JUN-07:03 | 0.86 |
July | 0.631904E+09 | 0.36 | 984.68 | 16-JUL-07:03 | 0.92 |
August | 0.647468E+09 | 0.37 | 984.68 | 07-AUG-07:03 | 0.92 |
September | 0.658066E+09 | 0.38 | 984.68 | 17-SEP-07:03 | 0.92 |
October | 0.590863E+09 | 0.33 | 984.68 | 17-OCT-07:01 | 0.93 |
November | 0.562298E+09 | 0.31 | 984.68 | 03-NOV-07:01 | 0.93 |
December | 0.671380E+09 | 0.37 | 984.68 | 02-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.753877E+10 | 0.36 | |||
Minimum of Months | 0.553559E+09 | 0.31 | 450.47 | 0.61 | |
Maximum of Months | 0.688552E+09 | 0.41 | 984.68 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.811634E+09 | 0.35 | 1112.23 | 01-JAN-08:61 | 0.93 |
February | 0.740623E+09 | 0.36 | 1112.23 | 01-FEB-07:01 | 0.93 |
March | 0.749152E+09 | 0.34 | 1112.23 | 01-MAR-07:01 | 0.93 |
April | 0.656938E+09 | 0.32 | 1112.23 | 03-APR-06:01 | 0.93 |
May | 0.650747E+09 | 0.31 | 656.78 | 01-MAY-06:03 | 0.71 |
June | 0.634375E+09 | 0.31 | 971.41 | 18-JUN-07:03 | 0.86 |
July | 0.641732E+09 | 0.30 | 1112.23 | 16-JUL-07:03 | 0.91 |
August | 0.657264E+09 | 0.31 | 1112.23 | 07-AUG-06:03 | 0.92 |
September | 0.624825E+09 | 0.30 | 1112.23 | 17-SEP-07:03 | 0.92 |
October | 0.654787E+09 | 0.31 | 1083.46 | 30-OCT-06:02 | 0.92 |
November | 0.674923E+09 | 0.32 | 1112.23 | 23-NOV-08:62 | 0.93 |
December | 0.792929E+09 | 0.35 | 1112.23 | 02-DEC-07:01 | 0.93 |
Annual Sum or Average | 0.828993E+10 | 0.32 | |||
Minimum of Months | 0.624825E+09 | 0.30 | 656.78 | 0.71 | |
Maximum of Months | 0.811634E+09 | 0.36 | 1112.23 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.814904E+09 | 0.35 | 1110.35 | 01-JAN-08:61 | 0.93 |
February | 0.743396E+09 | 0.36 | 1110.35 | 01-FEB-07:01 | 0.93 |
March | 0.751299E+09 | 0.34 | 1110.35 | 01-MAR-07:01 | 0.93 |
April | 0.658666E+09 | 0.32 | 1110.35 | 01-APR-06:02 | 0.93 |
May | 0.649963E+09 | 0.31 | 744.67 | 01-MAY-06:03 | 0.76 |
June | 0.633304E+09 | 0.31 | 952.67 | 18-JUN-07:03 | 0.85 |
July | 0.640719E+09 | 0.30 | 1110.35 | 15-JUL-06:03 | 0.92 |
August | 0.656168E+09 | 0.31 | 1110.35 | 07-AUG-06:03 | 0.92 |
September | 0.623767E+09 | 0.30 | 1110.35 | 17-SEP-07:03 | 0.92 |
October | 0.655614E+09 | 0.31 | 1110.35 | 30-OCT-06:02 | 0.93 |
November | 0.677505E+09 | 0.32 | 1110.35 | 12-NOV-08:62 | 0.93 |
December | 0.795879E+09 | 0.35 | 1110.35 | 02-DEC-07:01 | 0.93 |
Annual Sum or Average | 0.830118E+10 | 0.32 | |||
Minimum of Months | 0.623767E+09 | 0.30 | 744.67 | 0.76 | |
Maximum of Months | 0.814904E+09 | 0.36 | 1110.35 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.821522E+09 | 0.36 | 1108.78 | 01-JAN-08:61 | 0.93 |
February | 0.749349E+09 | 0.36 | 1108.78 | 01-FEB-07:01 | 0.93 |
March | 0.756510E+09 | 0.34 | 1108.78 | 01-MAR-07:01 | 0.93 |
April | 0.662563E+09 | 0.32 | 1108.78 | 01-APR-06:02 | 0.93 |
May | 0.649767E+09 | 0.31 | 822.54 | 01-MAY-06:03 | 0.80 |
June | 0.632340E+09 | 0.31 | 768.04 | 18-JUN-07:03 | 0.77 |
July | 0.639517E+09 | 0.30 | 1108.78 | 16-JUL-07:03 | 0.91 |
August | 0.655154E+09 | 0.31 | 1108.78 | 07-AUG-06:03 | 0.92 |
September | 0.622828E+09 | 0.30 | 1108.78 | 17-SEP-07:03 | 0.92 |
October | 0.657630E+09 | 0.31 | 1108.78 | 30-OCT-06:02 | 0.93 |
November | 0.682346E+09 | 0.32 | 1108.78 | 11-NOV-08:62 | 0.93 |
December | 0.802081E+09 | 0.35 | 1108.78 | 02-DEC-07:01 | 0.93 |
Annual Sum or Average | 0.833161E+10 | 0.32 | |||
Minimum of Months | 0.622828E+09 | 0.30 | 768.04 | 0.77 | |
Maximum of Months | 0.821522E+09 | 0.36 | 1108.78 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.125980E+10 | 0.33 | 1716.76 | 01-JAN-09:01 | 0.90 |
February | 0.115030E+10 | 0.33 | 1716.76 | 01-FEB-08:61 | 0.90 |
March | 0.113598E+10 | 0.31 | 1716.76 | 01-MAR-08:61 | 0.90 |
April | 0.974162E+09 | 0.29 | 1716.76 | 01-APR-07:01 | 0.90 |
May | 0.932008E+09 | 0.27 | 1716.76 | 01-MAY-07:01 | 0.89 |
June | 0.905393E+09 | 0.27 | 1451.79 | 18-JUN-08:63 | 0.82 |
July | 0.918566E+09 | 0.27 | 1716.76 | 16-JUL-08:62 | 0.88 |
August | 0.937914E+09 | 0.28 | 1716.76 | 07-AUG-07:03 | 0.89 |
September | 0.890130E+09 | 0.27 | 1449.43 | 17-SEP-08:63 | 0.82 |
October | 0.956646E+09 | 0.28 | 1716.76 | 09-OCT-08:61 | 0.90 |
November | 0.101527E+10 | 0.30 | 1716.76 | 02-NOV-07:01 | 0.90 |
December | 0.122611E+10 | 0.32 | 1716.76 | 01-DEC-08:61 | 0.90 |
Annual Sum or Average | 0.123023E+11 | 0.29 | |||
Minimum of Months | 0.890130E+09 | 0.27 | 1449.43 | 0.82 | |
Maximum of Months | 0.125980E+10 | 0.33 | 1716.76 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.124619E+10 | 0.47 | 933.06 | 05-JAN-12:40 | 0.93 |
February | 0.112885E+10 | 0.47 | 933.06 | 06-FEB-19:50 | 0.94 |
March | 0.127307E+10 | 0.47 | 933.06 | 01-MAR-10:20 | 0.93 |
April | 0.120925E+10 | 0.46 | 933.06 | 04-APR-16:20 | 0.93 |
May | 0.125963E+10 | 0.47 | 933.06 | 01-MAY-07:02 | 0.93 |
June | 0.122940E+10 | 0.47 | 933.06 | 20-JUN-19:17 | 0.92 |
July | 0.123948E+10 | 0.46 | 933.06 | 05-JUL-13:10 | 0.91 |
August | 0.127307E+10 | 0.47 | 933.06 | 01-AUG-18:40 | 0.93 |
September | 0.120925E+10 | 0.46 | 933.06 | 09-SEP-11:40 | 0.92 |
October | 0.124619E+10 | 0.46 | 933.06 | 08-OCT-09:20 | 0.93 |
November | 0.120925E+10 | 0.47 | 933.06 | 17-NOV-20:10 | 0.93 |
December | 0.123948E+10 | 0.46 | 933.06 | 12-DEC-10:10 | 0.94 |
Annual Sum or Average | 0.147631E+11 | 0.47 | |||
Minimum of Months | 0.112885E+10 | 0.46 | 933.06 | 0.91 | |
Maximum of Months | 0.127307E+10 | 0.47 | 933.06 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.123565E+10 | 0.47 | 925.17 | 06-JAN-18:10 | 0.93 |
February | 0.111931E+10 | 0.47 | 925.17 | 01-FEB-08:10 | 0.93 |
March | 0.126230E+10 | 0.47 | 925.17 | 15-MAR-19:20 | 0.92 |
April | 0.119902E+10 | 0.46 | 925.17 | 01-APR-07:08 | 0.93 |
May | 0.124898E+10 | 0.47 | 925.17 | 01-MAY-08:00 | 0.93 |
June | 0.121900E+10 | 0.47 | 925.17 | 01-JUN-14:10 | 0.92 |
July | 0.122899E+10 | 0.46 | 925.17 | 01-JUL-09:30 | 0.92 |
August | 0.126230E+10 | 0.47 | 925.17 | 07-AUG-08:00 | 0.92 |
September | 0.119902E+10 | 0.46 | 925.17 | 05-SEP-16:00 | 0.93 |
October | 0.123565E+10 | 0.46 | 925.17 | 20-OCT-10:30 | 0.93 |
November | 0.119902E+10 | 0.47 | 925.17 | 29-NOV-20:50 | 0.93 |
December | 0.122899E+10 | 0.46 | 925.17 | 14-DEC-19:20 | 0.93 |
Annual Sum or Average | 0.146382E+11 | 0.47 | |||
Minimum of Months | 0.111931E+10 | 0.46 | 925.17 | 0.92 | |
Maximum of Months | 0.126230E+10 | 0.47 | 925.17 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.121779E+10 | 0.47 | 911.80 | 02-JAN-20:10 | 0.93 |
February | 0.110365E+10 | 0.47 | 911.80 | 06-FEB-09:40 | 0.94 |
March | 0.124405E+10 | 0.47 | 911.80 | 02-MAR-15:40 | 0.93 |
April | 0.118169E+10 | 0.46 | 911.80 | 01-APR-13:10 | 0.93 |
May | 0.123092E+10 | 0.47 | 911.80 | 01-MAY-07:40 | 0.93 |
June | 0.120138E+10 | 0.47 | 911.80 | 16-JUN-14:20 | 0.92 |
July | 0.121123E+10 | 0.46 | 911.80 | 05-JUL-09:40 | 0.92 |
August | 0.124405E+10 | 0.47 | 911.80 | 19-AUG-09:00 | 0.92 |
September | 0.118169E+10 | 0.46 | 911.80 | 14-SEP-16:50 | 0.92 |
October | 0.121779E+10 | 0.46 | 911.80 | 14-OCT-18:00 | 0.93 |
November | 0.118169E+10 | 0.47 | 911.80 | 02-NOV-07:08 | 0.93 |
December | 0.121123E+10 | 0.46 | 911.80 | 04-DEC-11:30 | 0.93 |
Annual Sum or Average | 0.144272E+11 | 0.47 | |||
Minimum of Months | 0.110365E+10 | 0.46 | 911.80 | 0.92 | |
Maximum of Months | 0.124405E+10 | 0.47 | 911.80 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.767509E+09 | 0.41 | 965.34 | 01-JAN-09:01 | 0.93 |
February | 0.709878E+09 | 0.44 | 965.34 | 01-FEB-08:61 | 0.93 |
March | 0.684990E+09 | 0.36 | 965.34 | 01-MAR-08:61 | 0.94 |
April | 0.579316E+09 | 0.31 | 965.34 | 01-APR-07:01 | 0.93 |
May | 0.534886E+09 | 0.29 | 965.34 | 01-MAY-07:01 | 0.93 |
June | 0.508927E+09 | 0.28 | 464.62 | 14-JUN-07:05 | 0.63 |
July | 0.515130E+09 | 0.28 | 965.34 | 17-JUL-07:02 | 0.91 |
August | 0.527125E+09 | 0.28 | 965.34 | 14-AUG-07:03 | 0.91 |
September | 0.500778E+09 | 0.28 | 730.93 | 30-SEP-07:03 | 0.82 |
October | 0.552632E+09 | 0.29 | 965.34 | 08-OCT-08:61 | 0.93 |
November | 0.597369E+09 | 0.31 | 965.34 | 01-NOV-07:01 | 0.93 |
December | 0.741913E+09 | 0.38 | 965.34 | 01-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.722045E+10 | 0.33 | |||
Minimum of Months | 0.500778E+09 | 0.28 | 464.62 | 0.63 | |
Maximum of Months | 0.767509E+09 | 0.44 | 965.34 | 0.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.166410E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.152315E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.155244E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.132197E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.142289E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.291924E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.494703E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.418336E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.223573E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.132705E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.135307E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.163458E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.260846E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.132197E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.494703E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.688552E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.630023E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.667994E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.554168E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.754046E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.170281E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.283239E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.238651E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.130009E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.611648E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.562488E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.671380E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.133621E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.554168E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.283239E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.811634E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.740623E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.778384E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.656938E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.738995E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.136740E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.217276E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.190482E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.106641E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.664891E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.674923E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.792929E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.123707E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.656938E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.217276E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.814904E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.743396E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.778235E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.658666E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.731639E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.135971E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.216922E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.190107E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.105908E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.663672E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.677505E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.795879E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.123530E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.658666E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.216922E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.821522E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.749349E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.780081E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.662563E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.719081E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.132944E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.212833E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.186571E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.103360E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.663098E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.682346E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.802081E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.122372E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.662563E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.212833E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.125980E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.115030E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.117667E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.974162E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.105368E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.219213E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.369716E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.320053E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.164520E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.967026E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.101527E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.122611E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.195580E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.967026E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.369716E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.124619E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.112885E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.129661E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.120925E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.131896E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.183796E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.256123E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.234162E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.154450E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.125075E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.120925E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.123948E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.181847E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.112885E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.256123E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.123565E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.111931E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.128512E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.119902E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.130514E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.181657E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.253547E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.231882E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.152836E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.123994E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.119902E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.122899E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.180114E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.111931E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.253547E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.121779E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.110365E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.126386E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.118169E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.127560E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.176655E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.247817E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.227068E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.149305E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.122103E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.118169E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.121123E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.176650E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.110365E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.247817E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.767509E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.709878E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.695622E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.579316E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.557997E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.107093E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.186477E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.164014E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.832405E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.554966E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.597369E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.741913E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.106128E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.554966E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.186477E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166410E+10 | 0.00 | 0.204136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152315E+10 | 0.00 | 0.193553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150463E+10 | 0.180236E+09 | 0.119274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132197E+10 | 0.00 | 0.485847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127199E+10 | 0.585501E+09 | 0.206096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123297E+10 | 0.703558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127102E+10 | 0.157051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127175E+10 | 0.121948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123047E+10 | 0.418369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130285E+10 | 92671999.68 | 0.180641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135307E+10 | 0.00 | 0.662517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163458E+10 | 0.00 | 0.186563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165826E+11 | 0.399776E+11 | 0.838487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166410E+10 | 0.157051E+11 | 0.204136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.688552E+09 | 0.00 | 0.737560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.630023E+09 | 0.00 | 0.698528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.632767E+09 | 0.134936E+09 | 0.396892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.553559E+09 | 2339604.43 | 0.123657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.635767E+09 | 0.464002E+09 | 2975314.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.636126E+09 | 0.434293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.631904E+09 | 0.910708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.647468E+09 | 0.712863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.658066E+09 | 0.263380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.590863E+09 | 79838158.42 | 0.340453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.562298E+09 | 713206.56 | 0.198717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671380E+09 | 0.00 | 0.670064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.753877E+10 | 0.238943E+11 | 0.285976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.553559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.688552E+09 | 0.910708E+10 | 0.737560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.811634E+09 | 0.00 | 0.791214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.740623E+09 | 0.00 | 0.743349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.749152E+09 | 0.110457E+09 | 0.436157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.656938E+09 | 0.00 | 0.152368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.650747E+09 | 0.343076E+09 | 23319896.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.634375E+09 | 0.303468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.641732E+09 | 0.648138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.657264E+09 | 0.517001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.624825E+09 | 0.182825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.654787E+09 | 38507607.01 | 0.515959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.674923E+09 | 0.00 | 0.237175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.792929E+09 | 0.00 | 0.718114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.828993E+10 | 0.170064E+11 | 0.313231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.624825E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.811634E+09 | 0.648138E+10 | 0.791214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.814904E+09 | 0.00 | 0.812160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.743396E+09 | 0.00 | 0.761442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.751299E+09 | 0.101397E+09 | 0.451731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.658666E+09 | 0.00 | 0.165570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.649963E+09 | 0.316423E+09 | 38157763.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.633304E+09 | 0.300890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.640719E+09 | 0.647884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.656168E+09 | 0.516462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.623767E+09 | 0.180270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.655614E+09 | 30527036.82 | 0.606532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.677505E+09 | 0.00 | 0.254449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.795879E+09 | 0.00 | 0.737486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.830118E+10 | 0.169034E+11 | 0.324731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.623767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.814904E+09 | 0.647884E+10 | 0.812160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.821522E+09 | 0.00 | 0.848022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.749349E+09 | 0.00 | 0.793742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.756510E+09 | 88131686.51 | 0.480894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.662563E+09 | 0.00 | 0.188201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.649767E+09 | 0.266404E+09 | 72343949.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.632340E+09 | 0.287499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.639517E+09 | 0.628231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.655154E+09 | 0.500028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.622828E+09 | 0.169358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.657630E+09 | 20549901.52 | 0.744864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.682346E+09 | 0.00 | 0.281573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.802081E+09 | 0.00 | 0.771338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.833161E+10 | 0.162263E+11 | 0.344549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.622828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.821522E+09 | 0.628231E+10 | 0.848022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.125980E+10 | 0.00 | 0.175569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115030E+10 | 0.00 | 0.163674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113598E+10 | 0.152757E+09 | 0.101989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.974162E+09 | 0.00 | 0.431396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.932008E+09 | 0.469204E+09 | 0.253889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.905393E+09 | 0.537695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.918566E+09 | 0.119117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.937914E+09 | 0.948224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.890130E+09 | 0.314363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.956646E+09 | 39165573.16 | 0.202303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101527E+10 | 0.00 | 0.642037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122611E+10 | 0.00 | 0.160838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123023E+11 | 0.305756E+11 | 0.732182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.890130E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125980E+10 | 0.119117E+11 | 0.175569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.124619E+10 | 0.00 | 0.863855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112885E+10 | 0.00 | 0.808077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127307E+10 | 0.102152E+09 | 0.481433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120925E+10 | 37.96 | 0.179824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125963E+10 | 0.263208E+09 | 59255800.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122940E+10 | 0.290273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123948E+10 | 0.644608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127307E+10 | 0.510184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120925E+10 | 0.159442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124619E+10 | 19674317.95 | 0.715826E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120925E+10 | 0.00 | 0.278506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123948E+10 | 0.00 | 0.786183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147631E+11 | 0.164301E+11 | 0.347539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.112885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127307E+10 | 0.644608E+10 | 0.863855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.123565E+10 | 0.00 | 0.871743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111931E+10 | 0.00 | 0.814756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126230E+10 | 98898363.66 | 0.489570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119902E+10 | 2779.79 | 0.186980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124898E+10 | 0.248677E+09 | 69896012.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121900E+10 | 0.284788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122899E+10 | 0.636894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126230E+10 | 0.504268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119902E+10 | 0.156543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123565E+10 | 18479774.64 | 0.754883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119902E+10 | 0.00 | 0.285490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122899E+10 | 0.00 | 0.793883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146382E+11 | 0.161910E+11 | 0.352490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126230E+10 | 0.636894E+10 | 0.871743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.121779E+10 | 0.00 | 0.917772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110365E+10 | 0.00 | 0.855885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124405E+10 | 85345177.90 | 0.530895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118169E+10 | 4034.00 | 0.219027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123092E+10 | 0.196313E+09 | 0.130482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120138E+10 | 0.268488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121123E+10 | 0.616706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124405E+10 | 0.489454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118169E+10 | 0.147721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121779E+10 | 13855455.73 | 0.922777E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118169E+10 | 0.00 | 0.315558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121123E+10 | 0.00 | 0.836385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144272E+11 | 0.155192E+11 | 0.378085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124405E+10 | 0.616706E+10 | 0.917772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.767509E+09 | 0.00 | 0.121652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.709878E+09 | 0.00 | 0.115341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.684990E+09 | 39048904.40 | 0.769834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.579316E+09 | 0.00 | 0.387951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.534886E+09 | 86115582.65 | 0.669695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.508927E+09 | 0.231502E+10 | 2306683.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.515130E+09 | 0.572159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.527125E+09 | 0.462766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.500778E+09 | 0.136805E+10 | 17102752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.552632E+09 | 8671234.04 | 0.181699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.597369E+09 | 0.00 | 0.477199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.741913E+09 | 0.00 | 0.111011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.722045E+10 | 0.141662E+11 | 0.536564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.500778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.767509E+09 | 0.572159E+10 | 0.121652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.166410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150463E+10 | 0.00 | 0.00 | 0.00 | 47807860.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127199E+10 | 0.00 | 0.00 | 0.00 | 0.150897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123297E+10 | 0.00 | 0.00 | 0.00 | 0.168627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127102E+10 | 0.00 | 0.00 | 0.00 | 0.367601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127175E+10 | 0.00 | 0.00 | 0.00 | 0.291161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123047E+10 | 0.00 | 0.00 | 0.00 | 0.100527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130285E+10 | 0.00 | 0.00 | 0.00 | 24198326.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165826E+11 | 0.00 | 0.00 | 0.00 | 0.950207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166410E+10 | 0.00 | 0.00 | 0.00 | 0.367601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.688552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.630023E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.632767E+09 | 0.00 | 0.00 | 0.00 | 35226949.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.553559E+09 | 0.00 | 0.00 | 0.00 | 608559.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.635767E+09 | 0.00 | 0.00 | 0.00 | 0.118278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.636126E+09 | 0.00 | 0.00 | 0.00 | 0.106668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.631904E+09 | 0.00 | 0.00 | 0.00 | 0.220049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.647468E+09 | 0.00 | 0.00 | 0.00 | 0.173904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.658066E+09 | 0.00 | 0.00 | 0.00 | 0.642021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.590863E+09 | 0.00 | 0.00 | 0.00 | 20785688.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.562298E+09 | 0.00 | 0.00 | 0.00 | 189530.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.753877E+10 | 0.00 | 0.00 | 0.00 | 0.582332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.553559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.688552E+09 | 0.00 | 0.00 | 0.00 | 0.220049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.811634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.740623E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.749152E+09 | 0.00 | 0.00 | 0.00 | 29232402.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.656938E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.650747E+09 | 0.00 | 0.00 | 0.00 | 88248001.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.634375E+09 | 0.00 | 0.00 | 0.00 | 0.733020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.641732E+09 | 0.00 | 0.00 | 0.00 | 0.153102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.657264E+09 | 0.00 | 0.00 | 0.00 | 0.124756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.624825E+09 | 0.00 | 0.00 | 0.00 | 0.441585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.654787E+09 | 0.00 | 0.00 | 0.00 | 10103524.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.674923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.792929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.828993E+10 | 0.00 | 0.00 | 0.00 | 0.408077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.624825E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.811634E+09 | 0.00 | 0.00 | 0.00 | 0.153102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.814904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.743396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.751299E+09 | 0.00 | 0.00 | 0.00 | 26935827.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.658666E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.649963E+09 | 0.00 | 0.00 | 0.00 | 81676109.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.633304E+09 | 0.00 | 0.00 | 0.00 | 0.726408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.640719E+09 | 0.00 | 0.00 | 0.00 | 0.152850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.656168E+09 | 0.00 | 0.00 | 0.00 | 0.124490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.623767E+09 | 0.00 | 0.00 | 0.00 | 0.435316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.655614E+09 | 0.00 | 0.00 | 0.00 | 8057411.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.677505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.795879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.830118E+10 | 0.00 | 0.00 | 0.00 | 0.405179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.623767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.814904E+09 | 0.00 | 0.00 | 0.00 | 0.152850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.821522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.749349E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.756510E+09 | 0.00 | 0.00 | 0.00 | 23571282.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.662563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.649767E+09 | 0.00 | 0.00 | 0.00 | 69314152.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.632340E+09 | 0.00 | 0.00 | 0.00 | 0.697099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.639517E+09 | 0.00 | 0.00 | 0.00 | 0.148881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.655154E+09 | 0.00 | 0.00 | 0.00 | 0.121056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.622828E+09 | 0.00 | 0.00 | 0.00 | 0.410771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.657630E+09 | 0.00 | 0.00 | 0.00 | 5468430.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.682346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.802081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.833161E+10 | 0.00 | 0.00 | 0.00 | 0.390559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.622828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.821522E+09 | 0.00 | 0.00 | 0.00 | 0.148881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.125980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113598E+10 | 0.00 | 0.00 | 0.00 | 40685409.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.974162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.932008E+09 | 0.00 | 0.00 | 0.00 | 0.121668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.905393E+09 | 0.00 | 0.00 | 0.00 | 0.128673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.918566E+09 | 0.00 | 0.00 | 0.00 | 0.277859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.937914E+09 | 0.00 | 0.00 | 0.00 | 0.226261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.890130E+09 | 0.00 | 0.00 | 0.00 | 0.755073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.956646E+09 | 0.00 | 0.00 | 0.00 | 10380586.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123023E+11 | 0.00 | 0.00 | 0.00 | 0.725574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.890130E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125980E+10 | 0.00 | 0.00 | 0.00 | 0.277859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.124619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127307E+10 | 0.00 | 0.00 | 0.00 | 23545957.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120925E+10 | 0.00 | 0.00 | 0.00 | 8.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125963E+10 | 0.00 | 0.00 | 0.00 | 59330313.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122940E+10 | 0.00 | 0.00 | 0.00 | 0.608561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123948E+10 | 0.00 | 0.00 | 0.00 | 0.132175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127307E+10 | 0.00 | 0.00 | 0.00 | 0.106856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120925E+10 | 0.00 | 0.00 | 0.00 | 0.335254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124619E+10 | 0.00 | 0.00 | 0.00 | 4559075.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147631E+11 | 0.00 | 0.00 | 0.00 | 0.342156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.112885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127307E+10 | 0.00 | 0.00 | 0.00 | 0.132175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.123565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126230E+10 | 0.00 | 0.00 | 0.00 | 22821826.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119902E+10 | 0.00 | 0.00 | 0.00 | 656.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124898E+10 | 0.00 | 0.00 | 0.00 | 56159905.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121900E+10 | 0.00 | 0.00 | 0.00 | 0.597564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122899E+10 | 0.00 | 0.00 | 0.00 | 0.130648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126230E+10 | 0.00 | 0.00 | 0.00 | 0.105652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119902E+10 | 0.00 | 0.00 | 0.00 | 0.329338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123565E+10 | 0.00 | 0.00 | 0.00 | 4287551.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146382E+11 | 0.00 | 0.00 | 0.00 | 0.337317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126230E+10 | 0.00 | 0.00 | 0.00 | 0.130648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.121779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124405E+10 | 0.00 | 0.00 | 0.00 | 19807571.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118169E+10 | 0.00 | 0.00 | 0.00 | 952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123092E+10 | 0.00 | 0.00 | 0.00 | 44678923.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120138E+10 | 0.00 | 0.00 | 0.00 | 0.565164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121123E+10 | 0.00 | 0.00 | 0.00 | 0.126694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124405E+10 | 0.00 | 0.00 | 0.00 | 0.102662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118169E+10 | 0.00 | 0.00 | 0.00 | 0.311364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121779E+10 | 0.00 | 0.00 | 0.00 | 3233308.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144272E+11 | 0.00 | 0.00 | 0.00 | 0.323781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124405E+10 | 0.00 | 0.00 | 0.00 | 0.126694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.767509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.709878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.684990E+09 | 0.00 | 0.00 | 0.00 | 10632484.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.579316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.534886E+09 | 0.00 | 0.00 | 0.00 | 23110412.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.508927E+09 | 0.00 | 0.00 | 0.00 | 0.562008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.515130E+09 | 0.00 | 0.00 | 0.00 | 0.134964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.527125E+09 | 0.00 | 0.00 | 0.00 | 0.111301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.500778E+09 | 0.00 | 0.00 | 0.00 | 0.331626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.552632E+09 | 0.00 | 0.00 | 0.00 | 2334409.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.597369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.741913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.722045E+10 | 0.00 | 0.00 | 0.00 | 0.339236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.500778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.767509E+09 | 0.00 | 0.00 | 0.00 | 0.134964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.984225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127917E+11 | 0.00 | 0.00 | 0.34 |
February | 0.598420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121815E+11 | 0.00 | 0.00 | 0.35 |
March | 0.334258E+10 | 5892197.60 | 0.00 | 170210.05 | 1274121.91 | 0.685429E+10 | 86641952.07 | 0.00 | 0.35 |
April | 0.476996E+10 | 0.00 | 0.00 | 3162.96 | 0.00 | 0.254316E+10 | 7275246.28 | 0.00 | 0.35 |
May | 0.355592E+10 | 21136083.76 | 0.00 | 2678345.64 | 1303758.13 | 63116311.89 | 0.191757E+10 | 0.00 | 0.45 |
June | 0.506714E+09 | 0.105594E+10 | 0.00 | 9228564.14 | 67900.01 | 0.00 | 0.357615E+10 | 0.00 | 0.69 |
July | 3197085.49 | 0.302582E+10 | 0.00 | 7484075.82 | 1360390.93 | 0.00 | 0.130247E+10 | 0.00 | 0.73 |
August | 60668863.29 | 0.177830E+10 | 0.00 | 10714793.45 | 628561.25 | 0.00 | 0.266152E+10 | 0.00 | 0.73 |
September | 0.770720E+09 | 0.385669E+09 | 0.00 | 9467947.45 | 23344.80 | 0.00 | 0.488817E+10 | 0.00 | 0.73 |
October | 0.569319E+10 | 0.00 | 0.00 | 1030491.97 | 0.00 | 0.624373E+09 | 0.873681E+09 | 0.00 | 0.39 |
November | 0.490586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355823E+10 | 0.00 | 0.00 | 0.35 |
December | 0.215752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111713E+11 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.273490E+11 | 0.627277E+10 | 0.00 | 40777591.49 | 4658077.02 | 0.497876E+11 | 0.153135E+11 | 0.00 | 0.48 |
Minimum of Months | 3197085.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.569319E+10 | 0.302582E+10 | 0.00 | 10714793.45 | 1360390.93 | 0.127917E+11 | 0.488817E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.708556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439398E+10 | 0.00 | 0.00 | 0.25 |
February | 0.694296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400112E+10 | 0.00 | 0.00 | 0.26 |
March | 0.132257E+10 | 3978116.69 | 0.00 | 134137.17 | 10360.42 | 0.242767E+10 | 80305750.21 | 0.00 | 0.27 |
April | 0.190462E+10 | 0.00 | 0.00 | 107764.48 | 0.00 | 0.739923E+09 | 0.103431E+09 | 0.00 | 0.27 |
May | 0.111823E+10 | 13032555.31 | 0.00 | 2476783.30 | 189225.56 | 0.00 | 0.177645E+10 | 0.00 | 0.48 |
June | 0.132103E+09 | 0.589647E+09 | 0.00 | 4332593.58 | 0.00 | 0.00 | 0.202920E+10 | 0.00 | 0.69 |
July | 651280.07 | 0.167293E+10 | 0.00 | 2093957.63 | 0.00 | 0.00 | 0.451265E+09 | 0.00 | 0.64 |
August | 5849438.36 | 0.930373E+09 | 0.00 | 4260080.75 | 535317.53 | 0.00 | 0.114605E+10 | 0.00 | 0.68 |
September | 0.157561E+09 | 0.240042E+09 | 0.00 | 5106548.13 | 100865.04 | 0.00 | 0.289634E+10 | 0.00 | 0.78 |
October | 0.208479E+10 | 0.00 | 0.00 | 1117235.76 | 0.00 | 52111259.57 | 0.918935E+09 | 0.00 | 0.35 |
November | 0.181045E+10 | 0.00 | 0.00 | 37781.74 | 0.00 | 0.129421E+10 | 43408602.48 | 0.00 | 0.26 |
December | 0.873892E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398861E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.108136E+11 | 0.345001E+10 | 0.00 | 19666882.54 | 835768.55 | 0.168976E+11 | 0.944539E+10 | 0.00 | 0.43 |
Minimum of Months | 651280.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.208479E+10 | 0.167293E+10 | 0.00 | 5106548.13 | 535317.53 | 0.439398E+10 | 0.289634E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.221894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481402E+10 | 0.00 | 0.00 | 0.26 |
February | 0.214573E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443513E+10 | 0.00 | 0.00 | 0.26 |
March | 0.973405E+09 | 3218726.97 | 0.00 | 56077.15 | 611406.29 | 0.275437E+10 | 24982153.02 | 0.00 | 0.27 |
April | 0.165951E+10 | 0.00 | 0.00 | 13857.35 | 0.00 | 0.908893E+09 | 18250344.08 | 0.00 | 0.26 |
May | 0.121020E+10 | 10891954.10 | 0.00 | 1240656.20 | 485138.94 | 13135958.28 | 0.897595E+09 | 0.00 | 0.39 |
June | 0.222200E+09 | 0.421884E+09 | 0.00 | 2665999.92 | 15962305.40 | 0.00 | 0.152802E+10 | 0.00 | 0.60 |
July | 13173473.66 | 0.111980E+10 | 0.00 | 1632095.55 | 48923444.05 | 0.00 | 0.521927E+09 | 0.00 | 0.59 |
August | 44269629.27 | 0.667934E+09 | 0.00 | 2795233.22 | 22239837.50 | 0.00 | 0.103868E+10 | 0.00 | 0.61 |
September | 0.328276E+09 | 0.159230E+09 | 0.00 | 3051977.15 | 2586377.60 | 0.00 | 0.187839E+10 | 0.00 | 0.66 |
October | 0.198985E+10 | 0.00 | 0.00 | 438976.34 | 0.00 | 0.203487E+09 | 0.374340E+09 | 0.00 | 0.30 |
November | 0.155592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144302E+10 | 0.00 | 0.00 | 0.26 |
December | 0.360892E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442311E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.879417E+10 | 0.238296E+10 | 0.00 | 11894872.87 | 90808509.78 | 0.189952E+11 | 0.628218E+10 | 0.00 | 0.39 |
Minimum of Months | 13173473.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.198985E+10 | 0.111980E+10 | 0.00 | 3051977.15 | 48923444.05 | 0.481402E+10 | 0.187839E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.153010E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488294E+10 | 0.00 | 0.00 | 0.26 |
February | 0.199677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445003E+10 | 0.00 | 0.00 | 0.26 |
March | 0.885246E+09 | 2900619.38 | 0.00 | 52936.32 | 741780.55 | 0.284175E+10 | 22267499.54 | 0.00 | 0.27 |
April | 0.156691E+10 | 0.00 | 0.00 | 10455.19 | 0.00 | 0.993025E+09 | 15310012.05 | 0.00 | 0.26 |
May | 0.122483E+10 | 10179260.80 | 0.00 | 1099375.74 | 849645.07 | 16693930.96 | 0.820627E+09 | 0.00 | 0.39 |
June | 0.226468E+09 | 0.417749E+09 | 0.00 | 2634201.07 | 15801099.87 | 0.00 | 0.151007E+10 | 0.00 | 0.60 |
July | 13259026.61 | 0.111546E+10 | 0.00 | 1647153.29 | 48502526.67 | 0.00 | 0.522324E+09 | 0.00 | 0.59 |
August | 44380818.38 | 0.663540E+09 | 0.00 | 2811443.35 | 21900506.93 | 0.00 | 0.103897E+10 | 0.00 | 0.61 |
September | 0.355621E+09 | 0.155762E+09 | 0.00 | 3008801.61 | 2587520.19 | 0.00 | 0.183019E+10 | 0.00 | 0.65 |
October | 0.195601E+10 | 0.00 | 0.00 | 362059.00 | 0.00 | 0.253674E+09 | 0.317924E+09 | 0.00 | 0.30 |
November | 0.144110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155276E+10 | 0.00 | 0.00 | 0.26 |
December | 0.294292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448964E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.836080E+10 | 0.236559E+10 | 0.00 | 11626425.58 | 90383079.28 | 0.194805E+11 | 0.607768E+10 | 0.00 | 0.39 |
Minimum of Months | 13259026.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.195601E+10 | 0.111546E+10 | 0.00 | 3008801.61 | 48502526.67 | 0.488294E+10 | 0.183019E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492573E+10 | 0.00 | 0.00 | 0.26 |
February | 98066619.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455162E+10 | 0.00 | 0.00 | 0.26 |
March | 0.719989E+09 | 2695018.87 | 0.00 | 50572.96 | 945808.45 | 0.300424E+10 | 19188007.55 | 0.00 | 0.27 |
April | 0.136744E+10 | 0.00 | 0.00 | 5108.35 | 0.00 | 0.118013E+10 | 9568395.35 | 0.00 | 0.26 |
May | 0.127590E+10 | 9596709.65 | 0.00 | 831979.34 | 1436293.70 | 34977622.23 | 0.643052E+09 | 0.00 | 0.37 |
June | 0.256333E+09 | 0.409028E+09 | 0.00 | 2421484.56 | 15830374.44 | 0.00 | 0.140439E+10 | 0.00 | 0.58 |
July | 13540753.84 | 0.109094E+10 | 0.00 | 1556612.07 | 48379724.67 | 0.00 | 0.516469E+09 | 0.00 | 0.58 |
August | 53614648.69 | 0.653526E+09 | 0.00 | 2622015.74 | 22045772.65 | 0.00 | 0.100375E+10 | 0.00 | 0.60 |
September | 0.410290E+09 | 0.146278E+09 | 0.00 | 2769940.62 | 2475451.40 | 0.00 | 0.169367E+10 | 0.00 | 0.63 |
October | 0.189243E+10 | 0.00 | 0.00 | 246176.24 | 0.00 | 0.348193E+09 | 0.226614E+09 | 0.00 | 0.29 |
November | 0.124521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174207E+10 | 0.00 | 0.00 | 0.26 |
December | 0.220825E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456307E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.766386E+10 | 0.231206E+10 | 0.00 | 10503889.90 | 91113425.31 | 0.203500E+11 | 0.551669E+10 | 0.00 | 0.39 |
Minimum of Months | 13540753.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.189243E+10 | 0.109094E+10 | 0.00 | 2769940.62 | 48379724.67 | 0.492573E+10 | 0.169367E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107938E+11 | 0.00 | 0.00 | 0.27 |
February | 24502807.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995431E+10 | 0.00 | 0.00 | 0.27 |
March | 0.990800E+09 | 1991099.73 | 0.00 | 100059.29 | 1767935.82 | 0.699479E+10 | 34573782.28 | 0.00 | 0.28 |
April | 0.277042E+10 | 0.00 | 0.00 | 7363.11 | 0.00 | 0.266776E+10 | 15361158.09 | 0.00 | 0.27 |
May | 0.292736E+10 | 13237572.75 | 0.00 | 1125808.72 | 6469230.77 | 52955093.12 | 0.913777E+09 | 0.00 | 0.34 |
June | 0.517886E+09 | 0.841320E+09 | 0.00 | 4129329.96 | 13983472.68 | 0.00 | 0.237884E+10 | 0.00 | 0.48 |
July | 8287510.63 | 0.227123E+10 | 0.00 | 2489915.57 | 27384374.62 | 0.00 | 0.730068E+09 | 0.00 | 0.49 |
August | 58680518.52 | 0.133243E+10 | 0.00 | 4601100.57 | 19620609.58 | 0.00 | 0.159516E+10 | 0.00 | 0.51 |
September | 0.736938E+09 | 0.242854E+09 | 0.00 | 4860280.27 | 4001797.62 | 0.00 | 0.294829E+10 | 0.00 | 0.52 |
October | 0.401795E+10 | 0.00 | 0.00 | 297871.05 | 0.00 | 0.791517E+09 | 0.322000E+09 | 0.00 | 0.29 |
November | 0.199636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446985E+10 | 0.00 | 0.00 | 0.27 |
December | 0.100459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102030E+11 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.141497E+11 | 0.470306E+10 | 0.00 | 17611728.52 | 73227421.10 | 0.459279E+11 | 0.893807E+10 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.401795E+10 | 0.227123E+10 | 0.00 | 4860280.27 | 27384374.62 | 0.107938E+11 | 0.294829E+10 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538172E+10 | 0.00 | 0.00 | 0.27 |
February | 2473096.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497331E+10 | 0.00 | 0.00 | 0.27 |
March | 0.477968E+09 | 905793.15 | 0.00 | 48919.52 | 896436.77 | 0.350970E+10 | 23624380.58 | 0.00 | 0.29 |
April | 0.129896E+10 | 0.00 | 0.00 | 4770.34 | 0.00 | 0.143112E+10 | 17518956.30 | 0.00 | 0.28 |
May | 0.137613E+10 | 7487823.74 | 0.00 | 654321.03 | 2571470.84 | 32883696.15 | 0.793629E+09 | 0.00 | 0.41 |
June | 0.217180E+09 | 0.401847E+09 | 0.00 | 2223271.11 | 10220186.82 | 0.00 | 0.172142E+10 | 0.00 | 0.67 |
July | 12555822.80 | 0.107248E+10 | 0.00 | 1458419.18 | 14986793.98 | 0.00 | 0.627967E+09 | 0.00 | 0.68 |
August | 33184082.32 | 0.630844E+09 | 0.00 | 2566825.90 | 11236429.29 | 0.00 | 0.123168E+10 | 0.00 | 0.71 |
September | 0.344656E+09 | 0.106870E+09 | 0.00 | 2719754.75 | 1925821.38 | 0.00 | 0.211499E+10 | 0.00 | 0.74 |
October | 0.186587E+10 | 0.00 | 0.00 | 198074.44 | 0.00 | 0.505156E+09 | 0.312916E+09 | 0.00 | 0.31 |
November | 0.930273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229840E+10 | 0.00 | 0.00 | 0.27 |
December | 44588648.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509243E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.660384E+10 | 0.222043E+10 | 0.00 | 9874356.28 | 41837139.07 | 0.232247E+11 | 0.684375E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.186587E+10 | 0.107248E+10 | 0.00 | 2719754.75 | 14986793.98 | 0.538172E+10 | 0.211499E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538182E+10 | 0.00 | 0.00 | 0.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497587E+10 | 0.00 | 0.00 | 0.27 |
March | 0.450230E+09 | 896210.70 | 0.00 | 45348.87 | 938227.82 | 0.353845E+10 | 21102814.72 | 0.00 | 0.28 |
April | 0.124461E+10 | 0.00 | 0.00 | 3827.77 | 0.00 | 0.148238E+10 | 15870252.43 | 0.00 | 0.28 |
May | 0.140403E+10 | 7071917.79 | 0.00 | 584481.15 | 2956049.98 | 41646603.44 | 0.716472E+09 | 0.00 | 0.40 |
June | 0.223176E+09 | 0.397402E+09 | 0.00 | 2134970.11 | 11765262.33 | 0.00 | 0.167389E+10 | 0.00 | 0.66 |
July | 14290928.05 | 0.106364E+10 | 0.00 | 1427410.26 | 14995784.25 | 0.00 | 0.620116E+09 | 0.00 | 0.67 |
August | 38415104.11 | 0.627079E+09 | 0.00 | 2509414.39 | 10990504.56 | 0.00 | 0.121108E+10 | 0.00 | 0.71 |
September | 0.350067E+09 | 0.105343E+09 | 0.00 | 2653656.73 | 1724707.59 | 0.00 | 0.207231E+10 | 0.00 | 0.73 |
October | 0.182110E+10 | 0.00 | 0.00 | 183218.12 | 0.00 | 0.552509E+09 | 0.295863E+09 | 0.00 | 0.31 |
November | 0.870498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235705E+10 | 0.00 | 0.00 | 0.27 |
December | 38185042.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509887E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.645461E+10 | 0.220143E+10 | 0.00 | 9542327.40 | 43370536.54 | 0.234286E+11 | 0.662670E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.182110E+10 | 0.106364E+10 | 0.00 | 2653656.73 | 14995784.25 | 0.538182E+10 | 0.207231E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538200E+10 | 0.00 | 0.00 | 0.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497603E+10 | 0.00 | 0.00 | 0.27 |
March | 0.328138E+09 | 785744.27 | 0.00 | 31465.04 | 1143359.26 | 0.365852E+10 | 16159485.84 | 0.00 | 0.28 |
April | 0.102114E+10 | 0.00 | 0.00 | 55.04 | 0.00 | 0.169887E+10 | 2523580.44 | 0.00 | 0.27 |
May | 0.146545E+10 | 5729682.16 | 0.00 | 367930.23 | 4224581.75 | 74491265.36 | 0.486739E+09 | 0.00 | 0.38 |
June | 0.260217E+09 | 0.380415E+09 | 0.00 | 1846688.62 | 16915891.08 | 0.00 | 0.150097E+10 | 0.00 | 0.62 |
July | 18970651.98 | 0.103655E+10 | 0.00 | 1350378.14 | 17387198.23 | 0.00 | 0.602038E+09 | 0.00 | 0.66 |
August | 50738791.05 | 0.617006E+09 | 0.00 | 2338938.51 | 9135855.53 | 0.00 | 0.115408E+10 | 0.00 | 0.69 |
September | 0.373256E+09 | 99434793.87 | 0.00 | 2416106.91 | 2437385.44 | 0.00 | 0.192246E+10 | 0.00 | 0.69 |
October | 0.163694E+10 | 0.00 | 0.00 | 118091.31 | 0.00 | 0.759402E+09 | 0.211912E+09 | 0.00 | 0.30 |
November | 0.695895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252632E+10 | 0.00 | 0.00 | 0.27 |
December | 26036274.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511112E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.587679E+10 | 0.213992E+10 | 0.00 | 8469653.81 | 51244271.29 | 0.241868E+11 | 0.589689E+10 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.163694E+10 | 0.103655E+10 | 0.00 | 2416106.91 | 17387198.23 | 0.538200E+10 | 0.192246E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535758E+10 | 0.00 | 0.00 | 0.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495771E+10 | 0.00 | 0.00 | 0.27 |
March | 0.130906E+09 | 782698.64 | 191731.59 | 15540.01 | 1228860.53 | 0.382720E+10 | 3883040.54 | 636.06 | 0.28 |
April | 0.469612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218263E+10 | 0.00 | 0.00 | 0.27 |
May | 0.122084E+10 | 3616131.20 | 683204.41 | 142029.23 | 3433254.75 | 0.293152E+09 | 0.177384E+09 | 2855.08 | 0.31 |
June | 0.468113E+09 | 0.363846E+09 | 0.00 | 1255997.12 | 10717668.54 | 0.00 | 0.747232E+09 | 0.00 | 0.44 |
July | 11535289.47 | 0.102097E+10 | 0.00 | 1115803.75 | 15410161.74 | 0.00 | 0.375850E+09 | 0.00 | 0.49 |
August | 0.108545E+09 | 0.629097E+09 | 0.00 | 1918456.66 | 9187043.43 | 0.00 | 0.684164E+09 | 0.00 | 0.51 |
September | 0.507601E+09 | 0.102407E+09 | 0.00 | 1881177.24 | 2175994.66 | 3172372.45 | 0.115752E+10 | 0.00 | 0.50 |
October | 0.124293E+10 | 0.00 | 0.00 | 41400.04 | 0.00 | 0.115650E+10 | 47556165.44 | 0.00 | 0.28 |
November | 0.218807E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296624E+10 | 0.00 | 0.00 | 0.27 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511678E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.437889E+10 | 0.212072E+10 | 874936.00 | 6370404.04 | 42152983.66 | 0.258610E+11 | 0.319359E+10 | 3491.14 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.124293E+10 | 0.102097E+10 | 683204.41 | 1918456.66 | 15410161.74 | 0.535758E+10 | 0.115752E+10 | 2855.08 | 0.51 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:39:16
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.104620E+12 | 0.487367E+11 | 0.00 | 0.676784E+11 | 0.148035E+11 |
February | 0.196378E+12 | 0.467131E+11 | 0.00 | 0.623872E+11 | 0.139111E+11 |
March | 0.330001E+12 | 0.339753E+11 | 0.00 | 0.508223E+11 | 0.989696E+10 |
April | 0.417981E+12 | 0.231365E+11 | 0.00 | 0.353022E+11 | 0.344044E+10 |
May | 0.537071E+12 | 0.137427E+11 | 0.00 | 0.265885E+11 | 0.426950E+10 |
June | 0.595292E+12 | 0.389885E+10 | 0.00 | 0.157383E+11 | 0.451973E+11 |
July | 0.557290E+12 | -0.603370E+10 | 0.00 | -0.838256E+10 | 0.996554E+11 |
August | 0.467918E+12 | -0.135201E+10 | 0.00 | 0.463070E+10 | 0.790228E+11 |
September | 0.342445E+12 | 0.807133E+10 | 0.00 | 0.260153E+11 | 0.264041E+11 |
October | 0.211687E+12 | 0.211075E+11 | 0.00 | 0.341416E+11 | 0.185582E+10 |
November | 0.925591E+11 | 0.278382E+11 | 0.00 | 0.412937E+11 | 0.495530E+10 |
December | 0.899617E+11 | 0.478205E+11 | 0.00 | 0.648585E+11 | 0.134967E+11 |
Annual Sum or Average | 0.394320E+13 | 0.267655E+12 | 0.00 | 0.421074E+12 | 0.316909E+12 |
Minimum of Months | 0.899617E+11 | -0.603370E+10 | 0.00 | -0.838256E+10 | 0.185582E+10 |
Maximum of Months | 0.595292E+12 | 0.487367E+11 | 0.00 | 0.676784E+11 | 0.996554E+11 |