Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:39
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 08:39:09
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1012.62 | 484.43 | 484.43 |
Net Site Energy | 947.30 | 453.19 | 453.19 |
Total Source Energy | 2697.80 | 1290.61 | 1290.61 |
Net Source Energy | 2490.94 | 1191.66 | 1191.66 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 244.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 64.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 192.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 64.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 768.18 | 244.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 244.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 64.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 41.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 192.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 64.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 244.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 64.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 277.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 41.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 192.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 64.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 152.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 153.62 | 116.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 367.49 | 116.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 152.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 153.62 | 116.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 367.49 | 116.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 68.226 | 8.88 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -2.91 | -0.4 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 65.316 | 8.50 |
Electricity Coming From Utility | 702.887 | 91.50 |
Surplus Electricity Going To Utility | 0.023 | 0.00 |
Net Electricity From Utility | 702.864 | 91.50 |
Total On-Site and Utility Electric Sources | 768.180 | 100.00 |
Total Electricity End Uses | 768.180 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1.17 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1945.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:39 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 11.5884 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 13.7658 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 7.5320 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 10.0873 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 10.0873 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 11.5884 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 13.7658 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 12.9393 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 12.9393 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 12.9393 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 7.5320 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 7.5557 | 6.19 | 4.3000 | |
Total | 2090.32 | 10.0873 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 10.0873 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 10.0873 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-14:09 | 21-DEC-17:00 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 185265.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 30701.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11825.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7561.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 75845.60 | 185265.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 185265.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 30701.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11825.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7561.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 264.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 203.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 879.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 130.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 608.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 204.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2432.82 | 264.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 126.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 97.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 420.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 291.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1163.85 | 126.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 126.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 97.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 420.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 291.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1163.85 | 126.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.03 |
SMSTORE1 DIRECT AIR | 1.10 |
SMSTORE2 DIRECT AIR | 1.12 |
SMSTORE3 DIRECT AIR | 1.13 |
SMSTORE4 DIRECT AIR | 1.12 |
LGSTORE2 DIRECT AIR | 1.99 |
SMSTORE5 DIRECT AIR | 1.00 |
SMSTORE6 DIRECT AIR | 0.990995 |
SMSTORE7 DIRECT AIR | 1.01 |
SMSTORE8 DIRECT AIR | 1.04 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.03 | 2.03 | 2.03 | 2.03 | 2.03 | 2.03 | 1.00 | 1.00 | 2.03 |
PSZ-AC_2:2 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.00 | 1.00 | 1.10 |
PSZ-AC_3:3 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.00 | 1.000000 | 1.12 |
PSZ-AC_4:4 | 1.13 | 1.13 | 1.13 | 1.13 | 1.13 | 1.13 | 1.00 | 1.00 | 1.13 |
PSZ-AC_5:5 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.00 | 1.00 | 1.12 |
PSZ-AC_6:6 | 1.99 | 1.99 | 1.99 | 1.99 | 1.99 | 1.99 | 1.00 | 1.00 | 1.99 |
PSZ-AC_7:7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.03 | 1.03 | 1.00 | 0.974821 | 1.03 |
PSZ-AC_8:8 | 0.990995 | 0.990995 | 0.990995 | 0.990995 | 1.02 | 1.02 | 1.00 | 0.973459 | 1.02 |
PSZ-AC_9:9 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.00 | 1.000000 | 1.01 |
PSZ-AC_10:10 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.03 |
PSZ-AC_2:2_OA_CONTROLLER | 1.10 |
PSZ-AC_3:3_OA_CONTROLLER | 1.12 |
PSZ-AC_4:4_OA_CONTROLLER | 1.13 |
PSZ-AC_5:5_OA_CONTROLLER | 1.12 |
PSZ-AC_6:6_OA_CONTROLLER | 1.99 |
PSZ-AC_7:7_OA_CONTROLLER | 1.03 |
PSZ-AC_8:8_OA_CONTROLLER | 1.02 |
PSZ-AC_9:9_OA_CONTROLLER | 1.01 |
PSZ-AC_10:10_OA_CONTROLLER | 1.04 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.03 | 2172.55 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.10 | 1221.06 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.12 | 1244.73 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.13 | 1252.07 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.12 | 1240.41 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.99 | 2129.28 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1136.52 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1127.10 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1115.63 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1156.50 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.03 | 2.03 | 2.03 | 1.34 | 33609.22 | 53441.83 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.10 | 1.10 | 1.10 | 1.10 | 18256.49 | 28348.36 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 1.12 | 18610.40 | 28745.11 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.13 | 1.13 | 1.13 | 1.13 | 18720.19 | 28868.18 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 1.12 | 18545.88 | 28672.76 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.99 | 1.99 | 1.99 | 1.31 | 32939.86 | 52690.89 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 1.03 | 16992.54 | 26451.75 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 1.02 | 16851.75 | 26272.15 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 1.01 | 16680.22 | 26581.26 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 1.04 | 17291.27 | 27266.79 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.03 | 1.02 | 1.35 | 33609.22 | 16804.61 | 0.800660 | 0.800660 |
PSZ-AC_2:2 COOLING COIL | 1.10 | 0.551437 | 0.735247 | 18256.49 | 9128.25 | 0.800660 | 0.800660 |
PSZ-AC_3:3 COOLING COIL | 1.12 | 0.562127 | 0.749500 | 18610.40 | 9305.20 | 0.800660 | 0.800660 |
PSZ-AC_4:4 COOLING COIL | 1.13 | 0.565443 | 0.753927 | 18720.19 | 9360.09 | 0.800660 | 0.800660 |
PSZ-AC_5:5 COOLING COIL | 1.12 | 0.560178 | 0.746907 | 18545.88 | 9272.94 | 0.800660 | 0.800660 |
PSZ-AC_6:6 COOLING COIL | 1.99 | 0.994948 | 1.33 | 32939.86 | 16469.93 | 0.800660 | 0.800660 |
PSZ-AC_7:7 COOLING COIL | 1.03 | 0.513260 | 0.684347 | 16992.54 | 8496.27 | 0.800660 | 0.800660 |
PSZ-AC_8:8 COOLING COIL | 1.02 | 0.509007 | 0.678673 | 16851.75 | 8425.88 | 0.800660 | 0.800660 |
PSZ-AC_9:9 COOLING COIL | 1.01 | 0.503826 | 0.671767 | 16680.22 | 8340.11 | 0.800660 | 0.800660 |
PSZ-AC_10:10 COOLING COIL | 1.04 | 0.522283 | 0.696380 | 17291.27 | 8645.64 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 53441.83 |
PSZ-AC_2:2 HEATING COIL | 28348.36 |
PSZ-AC_3:3 HEATING COIL | 28745.11 |
PSZ-AC_4:4 HEATING COIL | 28868.18 |
PSZ-AC_5:5 HEATING COIL | 28672.76 |
PSZ-AC_6:6 HEATING COIL | 52690.89 |
PSZ-AC_7:7 HEATING COIL | 26451.75 |
PSZ-AC_8:8 HEATING COIL | 26272.15 |
PSZ-AC_9:9 HEATING COIL | 26581.26 |
PSZ-AC_10:10 HEATING COIL | 27266.79 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 11.588 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.888 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 13.766 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 18.066 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 7.532 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.832 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 2630.745 | 7.551 | 46.768 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2630.745 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1406.513 | 4.037 | 25.004 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1406.513 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1319.493 | 7.575 | 46.916 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1319.493 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1078.411 | 6.191 | 38.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1078.411 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 2624.046 | 7.532 | 46.649 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2624.046 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.4286 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.099 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.37371027E-12 | 0.68594845E-15 | -0.12863262E-12 | 0.13303556E-15 |
23 | 6 | 0.32748130E-07 | 0.12499873E-09 | 0.74678710E-08 | -0.15730520E-12 |
24 | 5 | -0.21059623E-03 | 0.10441617E-05 | -0.10801544E-03 | 0.73682644E-08 |
25 | 4 | 0.31581162 | 0.49728803E-03 | 0.10820905 | -0.36942064E-04 |
26 | 3 | -7.7342764 | 0.15111690E-01 | -2.4778213 | 0.31304292E-01 |
27 | 2 | 42.413636 | 0.52806348E-01 | 15.833102 | -0.35052424 |
28 | 1 | -81.726940 | 0.23470004E-01 | -29.650437 | 1.1037915 |
29 | 0 | 46.824331 | 0.46514506E-03 | 16.279406 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 35 | 1 | VerySmooth | 1.408 | 1.408 | 1.000 | 0.210 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 4.57814E-002 | 0.12126 | 0.67915 | 0.67915 | 0.29000 | 0.15345 | 0.21878 | 0.00000 | 0.84000 | 0.84000 | 8.56546E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 18665.34309 | 22398.41171 | 1.69194 | 2.03033 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90000 | 5.47527E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 23376.44032 | 28051.72838 | 1.24134 | 1.48961 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 10139.06198 | 12166.87438 | 0.91906 | 1.10287 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.77667 | 5.47508E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 11221.27300 | 13465.52760 | 0.59588 | 0.71505 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 10335.58375 | 12402.70050 | 0.93688 | 1.12425 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 11377.93673 | 13653.52408 | 0.60420 | 0.72504 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 10396.55558 | 12475.86670 | 0.94241 | 1.13089 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 11493.16768 | 13791.80121 | 0.61032 | 0.73238 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 10299.74948 | 12359.69937 | 0.93363 | 1.12036 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 11667.93749 | 14001.52499 | 0.61960 | 0.74352 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 18293.39473 | 21952.07368 | 1.65825 | 1.98990 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 22450.82594 | 26940.99113 | 1.19221 | 1.43066 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 9467.96481 | 11361.55777 | 0.83389 | 1.00067 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 28.27600 | 5.46666E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 12008.73980 | 14410.48776 | 0.63770 | 0.76524 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 9378.92198 | 11254.70638 | 0.82583 | 0.99099 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 28.27600 | 5.46666E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 11997.12530 | 14396.55036 | 0.63708 | 0.76449 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 9263.60959 | 11116.33151 | 0.83971 | 1.00765 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 12212.65730 | 14655.18876 | 0.64852 | 0.77823 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 9602.63118 | 11523.15742 | 0.87047 | 1.04457 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 33.16000 | 5.47412E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 14395.79107 | 17274.94929 | 0.76443 | 0.91732 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 26158.59 | 2.03033 | 2.03033 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 43407.51 | 1.48961 | 1.48961 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 14030.24 | 1.10287 | 1.10287 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 21151.49 | 0.71505 | 0.71505 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 14255.40 | 1.12425 | 1.12425 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 21336.75 | 0.72504 | 0.72504 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 14325.89 | 1.13089 | 1.13089 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 21473.01 | 0.73238 | 0.73238 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 14211.68 | 1.12036 | 1.12036 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 21679.68 | 0.74352 | 0.74352 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 25692.85 | 1.98990 | 1.98990 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 42313.10 | 1.43066 | 1.43066 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 13189.71 | 1.02652 | 1.02652 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 22082.69 | 0.76524 | 0.76524 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 13097.87 | 1.01801 | 1.01801 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 22068.96 | 0.76449 | 0.76449 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 12985.71 | 1.00765 | 1.00765 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 22323.83 | 0.77823 | 0.77823 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 13304.01 | 1.04457 | 1.04457 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 24905.31 | 0.91732 | 0.91732 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.03033 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.10287 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.12425 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.13089 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.12036 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.98990 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00067 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99099 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00765 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04457 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.03033 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.03033 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.03033 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.03033 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.03033 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.03033 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.10287 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.10287 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.10287 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.10287 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10287 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.10287 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12425 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12425 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.12425 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12425 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.12425 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.12425 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.13089 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.13089 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.13089 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.13089 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.13089 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.13089 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12036 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12036 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.12036 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12036 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.12036 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.12036 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.98990 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.98990 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.98990 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.98990 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.98990 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.98990 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00067 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00067 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00067 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00067 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02652 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02652 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.97482 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99099 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99099 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99099 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99099 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01801 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01801 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.97346 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00765 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00765 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00765 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00765 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00765 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00765 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04457 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04457 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04457 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04457 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04457 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04457 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.03033 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.10287 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.12425 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.13089 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.12036 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.98990 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.02652 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.01801 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.00765 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.04457 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.03033 |
102 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.03033 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2172.55257 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.03033 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.03033 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.03033 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.34002 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.03033 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.01517 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.35355 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33609.22000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16804.61000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
115 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33609.22000 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 53441.83210 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
119 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 53441.83210 |
120 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10287 |
121 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10287 |
122 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1221.05735 |
123 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10287 |
124 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10287 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10287 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10287 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10287 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55144 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.73525 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18256.49000 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9128.24500 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18256.49000 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28348.35935 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
138 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 28348.35935 |
139 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.12425 |
140 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.12425 |
141 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1244.72823 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.12425 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.12425 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.12425 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.12425 |
146 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.12425 |
147 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56213 |
148 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74950 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18610.40000 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9305.20000 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18610.40000 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28745.10734 |
155 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
157 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 28745.10734 |
158 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.13089 |
159 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.13089 |
160 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1252.07101 |
161 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.13089 |
162 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.13089 |
163 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.13089 |
164 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.13089 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.13089 |
166 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56544 |
167 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.75393 |
168 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18720.19000 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9360.09500 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
172 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18720.19000 |
173 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28868.17797 |
174 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
176 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 28868.17797 |
177 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.12036 |
178 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.12036 |
179 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1240.41261 |
180 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.12036 |
181 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.12036 |
182 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.12036 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.12036 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.12036 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56018 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74691 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18545.88000 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9272.94000 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18545.88000 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28672.76439 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
194 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
195 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 28672.76439 |
196 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.98990 |
197 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.98990 |
198 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2129.28365 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.98990 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.98990 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.98990 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.31333 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.98990 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.99495 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.32660 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32939.86000 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16469.93000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32939.86000 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 52690.88718 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
213 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
214 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 52690.88718 |
215 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02652 |
216 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02652 |
217 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1136.51998 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02652 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02652 |
220 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02652 |
221 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02652 |
222 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02652 |
223 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51326 |
224 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68435 |
225 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16992.54000 |
226 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8496.27000 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
229 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16992.54000 |
230 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26451.74727 |
231 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
232 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
233 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 26451.74727 |
234 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01801 |
235 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01801 |
236 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1127.10327 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01801 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01801 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01801 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.01801 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01801 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50901 |
243 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67867 |
244 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16851.75000 |
245 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8425.87500 |
246 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
247 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16851.75000 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26272.15234 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
251 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
252 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 26272.15234 |
253 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00765 |
254 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00765 |
255 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1115.63069 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00765 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00765 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00765 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00765 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00765 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50383 |
262 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67177 |
263 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16680.22000 |
264 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8340.11000 |
265 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
266 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16680.22000 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26581.26118 |
269 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
270 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
271 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 26581.26118 |
272 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04457 |
273 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04457 |
274 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1156.50018 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04457 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04457 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04457 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.04457 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04457 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52228 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69638 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17291.27000 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8645.63500 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17291.27000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27266.79275 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 27266.79275 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 32018.0 | 11.54 | 11.54 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 17392.2 | 12.29 | 12.29 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 17729.3 | 12.29 | 12.29 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 17833.9 | 12.29 | 12.29 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 17667.8 | 12.29 | 12.29 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 31380.4 | 11.54 | 11.54 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 16188.0 | 12.29 | 12.29 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 16053.9 | 12.29 | 12.29 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 15890.5 | 12.29 | 12.29 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 16472.6 | 12.29 | 12.29 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.429 | 0.403 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 3.5742530645E-002 | 0.2093098232 | Pass | Pass | 0.4811675268 | 2.5755210500 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.8431074460E-002 | 0.1693202454 | Pass | Pass | 0.2831728644 | 1.0143104839 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.5974903474E-002 | 0.1832139903 | Pass | Pass | 0.1918312899 | 0.9164491712 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.9548077363E-002 | 0.2181189178 | Pass | Pass | 0.2294129425 | 1.6004212567 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 4.3583124114E-002 | 0.2468197702 | Pass | Pass | 0.1407744001 | 0.4338727702 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 5.0708462455E-002 | 0.2511458866 | Pass | Pass | 6.0925047020E-002 | 0.1455534645 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 5.0740088668E-002 | 0.2541350996 | Pass | Pass | 5.2364298412E-002 | 0.1247325852 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 5.2119332099E-002 | 0.2627047461 | Pass | Pass | 4.9931462037E-002 | 0.1183543208 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.7647945480E-002 | 0.2972255298 | Pass | Pass | 4.4209284327E-002 | 0.1049380972 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 7.8051213281E-002 | 0.3887808314 | Pass | Pass | 3.5700868426E-002 | 9.2543917440E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4655.77 | 183.86 | 0.00 | 361.38 | 369.48 | 5570.50 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.403 | 0.429 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 1.408 | 0.210 | 0.290 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 1.408 | 0.210 | 0.290 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 7.5512 | 348.39 | 2630.74 | LightsWired | LTG_SCH_BASE_LPD1 | 81.37 | 168.00 | 80.49 | 0.0000 | Y | 39.75 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 4.0372 | 348.39 | 1406.51 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 24.96 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 7.5749 | 174.19 | 1319.49 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 82.90 | 168.00 | 81.97 | 0.0000 | Y | 20.30 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 6.1909 | 174.19 | 1078.41 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 19.14 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 66.71 | 168.00 | 64.60 | 0.0000 | Y | 15.96 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 7.5320 | 348.39 | 2624.05 | LightsWired | LTG_SCH_BASE_LPD2 | 60.23 | 168.00 | 58.11 | 0.0000 | Y | 28.62 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 61.36 | 168.00 | 59.15 | 0.0000 | Y | 14.61 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 5.0436 | 4180.64 | 21085.58 | 277.79 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 437.57 | AstronomicalClock | - | 42.26 | 42.26 | 3.47 | |
EXTERIOR_LIGHTS_B | 1882.64 | AstronomicalClock | - | 83.67 | 62.97 | 22.25 | |
EXTERIOR_LIGHTS_C | 1466.47 | AstronomicalClock | - | 83.67 | 55.97 | 15.41 | |
Exterior Lighting Total | 3786.68 | 41.13 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33609.22 | 26909.56 | 6699.66 | 0.80 | 3.99 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18256.49 | 14617.24 | 3639.25 | 0.80 | 4.32 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18610.40 | 14900.60 | 3709.80 | 0.80 | 4.32 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18720.19 | 14988.51 | 3731.68 | 0.80 | 4.32 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18545.88 | 14848.94 | 3696.94 | 0.80 | 4.32 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32939.86 | 26373.63 | 6566.23 | 0.80 | 3.99 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16992.54 | 13605.25 | 3387.29 | 0.80 | 4.32 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16851.75 | 13492.52 | 3359.23 | 0.80 | 4.32 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16680.22 | 13355.18 | 3325.04 | 0.80 | 4.32 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17291.27 | 13844.43 | 3446.84 | 0.80 | 4.32 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 32018.0 | 11.54 | 11.54 | ||||
PSZ-AC_2:2 COOLING COIL | 17392.2 | 12.29 | 12.29 | ||||
PSZ-AC_3:3 COOLING COIL | 17729.3 | 12.29 | 12.29 | ||||
PSZ-AC_4:4 COOLING COIL | 17833.9 | 12.29 | 12.29 | ||||
PSZ-AC_5:5 COOLING COIL | 17667.8 | 12.29 | 12.29 | ||||
PSZ-AC_6:6 COOLING COIL | 31380.4 | 11.54 | 11.54 | ||||
PSZ-AC_7:7 COOLING COIL | 16188.0 | 12.29 | 12.29 | ||||
PSZ-AC_8:8 COOLING COIL | 16053.9 | 12.29 | 12.29 | ||||
PSZ-AC_9:9 COOLING COIL | 15890.5 | 12.29 | 12.29 | ||||
PSZ-AC_10:10 COOLING COIL | 16472.6 | 12.29 | 12.29 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 53441.83 | 0.88 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 28348.36 | 0.88 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 28745.11 | 0.88 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 28868.18 | 0.88 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 28672.76 | 0.88 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 52690.89 | 0.88 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 26451.75 | 0.88 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 26272.15 | 0.88 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 26581.26 | 0.88 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 27266.79 | 0.88 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.03 | 2172.55 | 1070.05 | 1.00 | 1.31 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.10 | 1221.06 | 1107.16 | 1.00 | 1.38 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.12 | 1244.73 | 1107.16 | 1.00 | 1.37 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.13 | 1252.07 | 1107.16 | 1.00 | 1.37 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.12 | 1240.41 | 1107.16 | 1.00 | 1.38 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.99 | 2129.28 | 1070.05 | 1.00 | 1.32 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1136.52 | 1107.16 | 1.00 | 1.40 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1127.10 | 1107.16 | 1.00 | 1.40 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1115.63 | 1107.16 | 1.00 | 1.40 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1156.50 | 1107.16 | 1.00 | 1.39 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 18665.34 | 22398.41 | 64.29 | 1.692 | 2.030 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 23.89 | 23.89 | 0.00737 | 33.90 | 0.00548 | 0.411 | 0.00 |
SMSTORE1 | 10139.06 | 12166.87 | 69.85 | 0.919 | 1.103 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00734 | 33.78 | 0.00548 | 0.206 | 0.00 |
SMSTORE2 | 10335.58 | 12402.70 | 71.20 | 0.937 | 1.124 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00733 | 33.65 | 0.00547 | 0.206 | 0.00 |
SMSTORE3 | 10396.56 | 12475.87 | 71.62 | 0.942 | 1.131 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00733 | 33.65 | 0.00547 | 0.206 | 0.00 |
SMSTORE4 | 10299.75 | 12359.70 | 70.95 | 0.934 | 1.120 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00733 | 33.65 | 0.00547 | 0.206 | 0.00 |
LGSTORE2 | 18293.39 | 21952.07 | 63.01 | 1.658 | 1.990 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00740 | 33.65 | 0.00547 | 0.411 | 0.00 |
SMSTORE5 | 9467.96 | 11361.56 | 65.22 | 0.834 | 1.001 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00803 | 28.28 | 0.00547 | 0.206 | 0.00 |
SMSTORE6 | 9378.92 | 11254.71 | 64.61 | 0.826 | 0.991 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00805 | 28.28 | 0.00547 | 0.206 | 0.00 |
SMSTORE7 | 9263.61 | 11116.33 | 63.82 | 0.840 | 1.008 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00736 | 33.65 | 0.00547 | 0.206 | 0.00 |
SMSTORE8 | 9602.63 | 11523.16 | 66.15 | 0.870 | 1.045 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.89 | 0.00733 | 33.16 | 0.00547 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 23376.44 | 28051.73 | 80.52 | 1.241 | 1.490 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00668 | -17.90 | 0.00096 | 0.411 | 0.00 |
SMSTORE1 | 11221.27 | 13465.53 | 77.30 | 0.596 | 0.715 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00657 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE2 | 11377.94 | 13653.52 | 78.38 | 0.604 | 0.725 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00659 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE3 | 11493.17 | 13791.80 | 79.18 | 0.610 | 0.732 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00660 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE4 | 11667.94 | 14001.52 | 80.38 | 0.620 | 0.744 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00661 | -17.90 | 0.00096 | 0.206 | 0.00 |
LGSTORE2 | 22450.83 | 26940.99 | 77.33 | 1.192 | 1.431 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00669 | -17.90 | 0.00096 | 0.411 | 0.00 |
SMSTORE5 | 12008.74 | 14410.49 | 82.73 | 0.638 | 0.765 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00664 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE6 | 11997.13 | 14396.55 | 82.65 | 0.637 | 0.764 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00664 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE7 | 12212.66 | 14655.19 | 84.13 | 0.649 | 0.778 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00665 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE8 | 14395.79 | 17274.95 | 99.17 | 0.764 | 0.917 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00672 | -17.90 | 0.00096 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.03 | 2.03 | 1.49 | 1.49 | 2.0303 | 2.0303 | 2.0303 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.10 | 1.10 | 0.72 | 0.72 | 1.1029 | 1.1029 | 1.1029 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.12 | 1.12 | 0.73 | 0.73 | 1.1243 | 1.1243 | 1.1243 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.13 | 1.13 | 0.73 | 0.73 | 1.1309 | 1.1309 | 1.1309 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.12 | 1.12 | 0.74 | 0.74 | 1.1204 | 1.1204 | 1.1204 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.99 | 1.99 | 1.43 | 1.43 | 1.9899 | 1.9899 | 1.9899 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.03 | 1.03 | 0.77 | 0.77 | 1.0265 | 1.0007 | 1.0265 | 0.9748 | 1.0000 |
PSZ-AC_8:8 | 1.02 | 1.02 | 0.76 | 0.76 | 1.0180 | 0.9910 | 1.0180 | 0.9735 | 1.0000 |
PSZ-AC_9:9 | 1.01 | 1.01 | 0.78 | 0.78 | 1.0077 | 1.0077 | 1.0077 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.04 | 1.04 | 0.92 | 0.92 | 1.0446 | 1.0446 | 1.0446 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 33609.220 | 26909.558 | 2.030330 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 16804.61 | 16804.61 | 1.353553 | 26.99 | 14.02 | 0.00698812 | 12.80 | 8.75 | 0.00698812 | 33.90 | 0.00547527 | 15.07 | 30.4000 | 23.89 | 0.00737266 | 32.4895 | 18665.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 53441.832 | 53441.832 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 53441.83 | 53441.83 | 2.030333 | 13.20 | 7.40 | 0.00551744 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 20.2667 | 21.10 | 0.00667706 | 34.8874 | 23376.44 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 18256.490 | 14617.241 | 1.102870 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 9128.25 | 9128.25 | 0.735247 | 26.87 | 13.98 | 0.00698923 | 12.80 | 8.75 | 0.00698923 | 33.90 | 0.00547527 | 15.07 | 27.9821 | 23.89 | 0.00733658 | 32.3322 | 10135.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 28348.359 | 28348.359 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28348.36 | 28348.36 | 1.102875 | 13.83 | 7.68 | 0.00552480 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 18.6547 | 21.10 | 0.00657273 | 34.3481 | 11221.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 18610.400 | 14900.603 | 1.124250 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 9305.20 | 9305.20 | 0.749500 | 26.84 | 13.97 | 0.00699121 | 12.80 | 8.75 | 0.00699121 | 33.90 | 0.00547527 | 15.07 | 27.4500 | 23.89 | 0.00733117 | 32.3086 | 10325.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 28745.107 | 28745.107 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28745.11 | 28745.11 | 1.124255 | 13.97 | 7.77 | 0.00555573 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 18.2999 | 21.10 | 0.00658619 | 34.4177 | 11377.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 18720.190 | 14988.507 | 1.130890 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 9360.09 | 9360.09 | 0.753927 | 26.82 | 13.96 | 0.00699180 | 12.80 | 8.75 | 0.00699180 | 33.90 | 0.00547527 | 15.07 | 27.2888 | 23.89 | 0.00732951 | 32.3014 | 10384.97 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 28868.178 | 28868.178 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28868.18 | 28868.18 | 1.130887 | 14.01 | 7.80 | 0.00556973 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 18.1926 | 21.10 | 0.00659591 | 34.4680 | 11493.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 18545.880 | 14848.944 | 1.120360 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 9272.94 | 9272.94 | 0.746907 | 26.84 | 13.97 | 0.00699084 | 12.80 | 8.75 | 0.00699084 | 33.90 | 0.00547527 | 15.07 | 27.5453 | 23.89 | 0.00733221 | 32.3131 | 10288.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 28672.764 | 28672.764 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28672.76 | 28672.76 | 1.120357 | 13.94 | 7.78 | 0.00557202 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 18.3636 | 21.10 | 0.00661053 | 34.5436 | 11667.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 32939.860 | 26373.628 | 1.989900 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 16469.93 | 16469.93 | 1.326600 | 27.04 | 14.04 | 0.00699721 | 12.80 | 8.75 | 0.00699721 | 33.90 | 0.00547527 | 15.07 | 31.0177 | 23.89 | 0.00739454 | 32.5849 | 18272.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 52690.887 | 52690.887 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 52690.89 | 52690.89 | 1.989897 | 13.04 | 7.32 | 0.00550658 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 20.6785 | 21.10 | 0.00669308 | 34.9695 | 22450.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 16992.540 | 13605.247 | 1.026520 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 8496.27 | 8496.27 | 0.684347 | 27.01 | 14.02 | 0.00698062 | 12.80 | 8.74 | 0.00698062 | 33.90 | 0.00547527 | 15.07 | 30.0633 | 23.89 | 0.00735852 | 32.4277 | 9425.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 26451.747 | 26451.747 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 26451.75 | 26451.75 | 1.026519 | 13.29 | 7.42 | 0.00549912 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 20.0422 | 21.10 | 0.00663809 | 34.6861 | 12008.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 16851.750 | 13492.522 | 1.018010 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 8425.88 | 8425.88 | 0.678673 | 27.03 | 14.02 | 0.00697954 | 12.80 | 8.74 | 0.00697954 | 33.90 | 0.00547527 | 15.07 | 30.3147 | 23.89 | 0.00736109 | 32.4389 | 9348.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 26272.152 | 26272.152 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 26272.15 | 26272.15 | 1.018014 | 13.22 | 7.38 | 0.00548889 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 20.2097 | 21.10 | 0.00663719 | 34.6815 | 11997.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 16680.220 | 13355.185 | 1.007650 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 8340.11 | 8340.11 | 0.671767 | 27.05 | 14.03 | 0.00697818 | 12.80 | 8.74 | 0.00697818 | 33.90 | 0.00547527 | 15.07 | 30.6263 | 23.89 | 0.00736429 | 32.4528 | 9253.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 26581.261 | 26581.261 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 26581.26 | 26581.26 | 1.007652 | 13.14 | 7.35 | 0.00549040 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 20.4175 | 21.10 | 0.00665393 | 34.7680 | 12212.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 17291.270 | 13844.428 | 1.044570 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 8645.64 | 8645.63 | 0.696380 | 26.96 | 13.98 | 0.00696043 | 12.80 | 8.72 | 0.00696043 | 33.78 | 0.00547508 | 15.03 | 29.5439 | 23.89 | 0.00732758 | 32.2927 | 9543.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 27266.793 | 27266.793 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 27266.79 | 27266.79 | 1.044566 | 13.42 | 7.57 | 0.00558471 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 19.6960 | 21.10 | 0.00672017 | 35.1118 | 14395.79 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33609.220 | 26909.558 | 2.030330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8306 | 1004.8586 | 0.9774 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.030333 | 1.98452410 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 16804.61 | 16804.61 | 1.0000 | 1.32301394 | 1.353553 | 26.99 | 14.02 | 0.00698812 | 44951.3 | 12.80 | 8.75 | 0.00698812 | 30505.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16804.61 | 33.90 | 0.00547527 | 15.07 | 0.41148071 | 30.4000 | 23.89 | 0.00737266 | 23.89 | 0.00737266 | 32.4895 | 18665.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 53441.832 | 53441.832 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.030333 | 1.98452410 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 53441.83 | 53441.83 | 1.0000 | 1.98452410 | 2.030333 | 13.20 | 7.40 | 0.00551744 | 27199.0 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 53441.83 | -17.90 | 0.00095524 | -17.90 | 0.41148071 | 20.2667 | 21.11 | 0.00667706 | 21.10 | 0.00667706 | 34.8874 | 23376.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18256.490 | 14617.241 | 1.102870 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8326 | 1004.8586 | 0.9774 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.102875 | 1.07799120 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 9128.25 | 9128.25 | 1.0000 | 0.71865775 | 0.735247 | 26.87 | 13.98 | 0.00698923 | 44828.6 | 12.80 | 8.75 | 0.00698923 | 30507.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9128.25 | 33.90 | 0.00547527 | 15.07 | 0.20573751 | 27.9821 | 23.89 | 0.00733658 | 23.89 | 0.00733658 | 32.3322 | 10135.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28348.359 | 28348.359 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.102875 | 1.07799120 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28348.36 | 28348.36 | 1.0000 | 1.07799120 | 1.102875 | 13.83 | 7.68 | 0.00552480 | 27855.9 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28348.36 | -17.90 | 0.00095524 | -17.90 | 0.20573751 | 18.6547 | 21.11 | 0.00657273 | 21.10 | 0.00657273 | 34.3481 | 11221.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18610.400 | 14900.603 | 1.124250 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8363 | 1004.8586 | 0.9774 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.124255 | 1.09888867 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 9305.20 | 9305.20 | 1.0000 | 0.73258949 | 0.749500 | 26.84 | 13.97 | 0.00699121 | 44798.6 | 12.80 | 8.75 | 0.00699121 | 30512.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9305.20 | 33.90 | 0.00547527 | 15.07 | 0.20573751 | 27.4500 | 23.89 | 0.00733117 | 23.89 | 0.00733117 | 32.3086 | 10325.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28745.107 | 28745.107 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.124255 | 1.09888867 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28745.11 | 28745.11 | 1.0000 | 1.09888867 | 1.124255 | 13.97 | 7.77 | 0.00555573 | 28074.6 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28745.11 | -17.90 | 0.00095524 | -17.90 | 0.20573751 | 18.2999 | 21.11 | 0.00658619 | 21.10 | 0.00658619 | 34.4177 | 11377.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18720.190 | 14988.507 | 1.130890 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8374 | 1004.8586 | 0.9774 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.130887 | 1.10537112 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 9360.09 | 9360.09 | 1.0000 | 0.73691628 | 0.753927 | 26.82 | 13.96 | 0.00699180 | 44789.4 | 12.80 | 8.75 | 0.00699180 | 30514.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9360.09 | 33.90 | 0.00547527 | 15.07 | 0.20573751 | 27.2888 | 23.89 | 0.00732951 | 23.89 | 0.00732951 | 32.3014 | 10384.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28868.178 | 28868.178 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.130887 | 1.10537112 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28868.18 | 28868.18 | 1.0000 | 1.10537112 | 1.130887 | 14.01 | 7.80 | 0.00556973 | 28152.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28868.18 | -17.90 | 0.00095524 | -17.90 | 0.20573751 | 18.1926 | 21.11 | 0.00659591 | 21.10 | 0.00659591 | 34.4680 | 11493.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18545.880 | 14848.944 | 1.120360 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8356 | 1004.8586 | 0.9774 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.120357 | 1.09507869 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 9272.94 | 9272.94 | 1.0000 | 0.73005467 | 0.746907 | 26.84 | 13.97 | 0.00699084 | 44804.4 | 12.80 | 8.75 | 0.00699084 | 30512.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9272.94 | 33.90 | 0.00547527 | 15.07 | 0.20573751 | 27.5453 | 23.89 | 0.00733221 | 23.89 | 0.00733221 | 32.3131 | 10288.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28672.764 | 28672.764 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.120357 | 1.09507869 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28672.76 | 28672.76 | 1.0000 | 1.09507869 | 1.120357 | 13.94 | 7.78 | 0.00557202 | 28090.5 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28672.76 | -17.90 | 0.00095524 | -17.90 | 0.20573751 | 18.3636 | 21.11 | 0.00661053 | 21.10 | 0.00661053 | 34.5436 | 11667.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32939.860 | 26373.628 | 1.989900 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8475 | 1004.8586 | 0.9774 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.989897 | 1.94499999 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 16469.93 | 16469.93 | 1.0000 | 1.29666874 | 1.326600 | 27.04 | 14.04 | 0.00699721 | 45018.8 | 12.80 | 8.75 | 0.00699721 | 30528.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16469.93 | 33.90 | 0.00547527 | 15.07 | 0.41148071 | 31.0177 | 23.89 | 0.00739454 | 23.89 | 0.00739454 | 32.5849 | 18272.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52690.887 | 52690.887 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.989897 | 1.94499999 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 52690.89 | 52690.89 | 1.0000 | 1.94499999 | 1.989897 | 13.04 | 7.32 | 0.00550658 | 27008.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52690.89 | -17.90 | 0.00095524 | -17.90 | 0.41148071 | 20.6785 | 21.11 | 0.00669308 | 21.10 | 0.00669308 | 34.9695 | 22450.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16992.540 | 13605.247 | 1.026520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8166 | 1004.8586 | 0.9774 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.026519 | 1.00335873 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 8496.27 | 8496.27 | 1.0000 | 0.66890617 | 0.684347 | 27.01 | 14.02 | 0.00698062 | 44949.8 | 12.80 | 8.74 | 0.00698062 | 30486.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8496.27 | 33.90 | 0.00547527 | 15.07 | 0.20573751 | 30.0633 | 23.89 | 0.00735852 | 23.89 | 0.00735852 | 32.4277 | 9425.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26451.747 | 26451.747 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.026519 | 1.00335873 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 26451.75 | 26451.75 | 1.0000 | 1.00335873 | 1.026519 | 13.29 | 7.42 | 0.00549912 | 27241.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26451.75 | -17.90 | 0.00095524 | -17.90 | 0.20573751 | 20.0422 | 21.11 | 0.00663809 | 21.10 | 0.00663809 | 34.6861 | 12008.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16851.750 | 13492.522 | 1.018010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8146 | 1004.8586 | 0.9774 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.018014 | 0.99504533 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 8425.88 | 8425.88 | 1.0000 | 0.66336084 | 0.678673 | 27.03 | 14.02 | 0.00697954 | 44964.0 | 12.80 | 8.74 | 0.00697954 | 30483.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8425.88 | 33.90 | 0.00547527 | 15.07 | 0.20573751 | 30.3147 | 23.89 | 0.00736109 | 23.89 | 0.00736109 | 32.4389 | 9348.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26272.152 | 26272.152 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.018014 | 0.99504533 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 26272.15 | 26272.15 | 1.0000 | 0.99504533 | 1.018014 | 13.22 | 7.38 | 0.00548889 | 27149.5 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26272.15 | -17.90 | 0.00095524 | -17.90 | 0.20573751 | 20.2097 | 21.11 | 0.00663719 | 21.10 | 0.00663719 | 34.6815 | 11997.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16680.220 | 13355.185 | 1.007650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8121 | 1004.8586 | 0.9774 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.007652 | 0.98491694 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 8340.11 | 8340.11 | 1.0000 | 0.65661001 | 0.671767 | 27.05 | 14.03 | 0.00697818 | 44981.6 | 12.80 | 8.74 | 0.00697818 | 30480.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8340.11 | 33.90 | 0.00547527 | 15.07 | 0.20573751 | 30.6263 | 23.89 | 0.00736429 | 23.89 | 0.00736429 | 32.4528 | 9253.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26581.261 | 26581.261 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.007652 | 0.98491694 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 26581.26 | 26581.26 | 1.0000 | 0.98491694 | 1.007652 | 13.14 | 7.35 | 0.00549040 | 27071.1 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26581.26 | -17.90 | 0.00095524 | -17.90 | 0.20573751 | 20.4175 | 21.11 | 0.00665393 | 21.10 | 0.00665393 | 34.7680 | 12212.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17291.270 | 13844.428 | 1.044570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7791 | 1004.8586 | 0.9774 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.044566 | 1.02099793 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 8645.64 | 8645.63 | 1.0000 | 0.68066800 | 0.696380 | 26.96 | 13.98 | 0.00696043 | 44848.3 | 12.80 | 8.72 | 0.00696043 | 30435.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8645.64 | 33.78 | 0.00547508 | 15.03 | 0.20573751 | 29.5439 | 23.89 | 0.00732758 | 23.89 | 0.00732758 | 32.2927 | 9543.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27266.793 | 27266.793 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.044566 | 1.02099793 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 27266.79 | 27266.79 | 1.0000 | 1.02099793 | 1.044566 | 13.42 | 7.57 | 0.00558471 | 27594.5 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27266.79 | -17.90 | 0.00095524 | -17.90 | 0.20573751 | 19.6960 | 21.11 | 0.00672017 | 21.10 | 0.00672017 | 35.1118 | 14395.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 2.03 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.10 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.12 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.13 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.12 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.99 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.03 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.02 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.01 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.04 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
LGSTORE1 | LGSTORE1_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE1 | SMSTORE1_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE2 | SMSTORE2_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE3 | SMSTORE3_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE4 | SMSTORE4_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LGSTORE2 | LGSTORE2_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE5 | SMSTORE5_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE6 | SMSTORE6_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE7 | SMSTORE7_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE8 | SMSTORE8_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1837.00 | 4041.83 | 1286.50 |
SMSTORE1 | 1091.00 | 3916.67 | 586.17 |
SMSTORE2 | 1167.50 | 2821.33 | 652.17 |
SMSTORE3 | 1225.33 | 2841.00 | 707.17 |
SMSTORE4 | 1290.17 | 2912.00 | 794.00 |
LGSTORE2 | 1331.33 | 2795.83 | 951.00 |
SMSTORE5 | 1275.17 | 2859.50 | 945.83 |
SMSTORE6 | 1299.67 | 2879.00 | 979.50 |
SMSTORE7 | 1400.67 | 2921.33 | 1091.67 |
SMSTORE8 | 1731.50 | 2947.33 | 1416.00 |
Facility | 2611.33 | 4470.67 | 1945.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 6.83 | 0.00 | 1.17 | 0.00 |
SMSTORE1 | 2.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 2.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 2.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 2.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 3.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 21.00 | 0.00 | 0.00 | 0.00 |
Facility | 29.00 | 0.00 | 1.17 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.784 | 0.230 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.926 | 0.245 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.002 | 0.320 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.997 | 0.320 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.965 | 0.320 | 0.000 | 0.000 |
LGSTORE2 | 24.78 | 56.25 | 1805.20 | 0.794 | 0.307 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.965 | 0.341 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.957 | 0.341 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.931 | 0.341 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.913 | 0.359 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.438 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.438 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.438 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.78 | 56.25 | 1805.20 | 0.461 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.461 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.461 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.461 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.461 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.212 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
LGSTORE2 | PSZ-AC_6:6 | 24.78 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.212 |
SMSTORE5 | PSZ-AC_7:7 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE6 | PSZ-AC_8:8 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE7 | PSZ-AC_9:9 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE8 | PSZ-AC_10:10 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
Total Facility | 120.98 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 1.274 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 8221377.52 | 0.00 | 8221377.52 | 2812665.34 | 11034042.87 | 7870781.79 | 3128.28 | 4202.00 | 1429.72 | 24.14 |
SMSTORE1 | 4875302.47 | 0.00 | 4875302.47 | 1400999.48 | 6276301.95 | 3935374.10 | 4061.26 | 2838.96 | 1859.78 | 36.36 |
SMSTORE2 | 4090362.11 | 0.00 | 4090362.11 | 1437500.89 | 5527863.00 | 3701819.01 | 4260.42 | 3183.31 | 1316.28 | 137.56 |
SMSTORE3 | 4070622.01 | 0.00 | 4070622.01 | 1437500.89 | 5508122.89 | 3701819.01 | 4261.69 | 3209.75 | 1288.56 | 134.08 |
SMSTORE4 | 3937403.42 | 0.00 | 3937403.42 | 1437500.89 | 5374904.30 | 3701819.01 | 4263.50 | 3287.50 | 1209.00 | 123.47 |
LGSTORE2 | 5871539.59 | 0.00 | 5871539.59 | 2643892.63 | 8515432.22 | 7907875.00 | 4672.64 | 3270.33 | 817.03 | 83.44 |
SMSTORE5 | 3615928.10 | 0.00 | 3615928.10 | 1448728.57 | 5064656.67 | 3953920.18 | 4640.75 | 3130.17 | 989.08 | 100.25 |
SMSTORE6 | 3581502.54 | 0.00 | 3581502.54 | 1448728.57 | 5030231.12 | 3953920.18 | 4641.83 | 3144.00 | 974.17 | 98.83 |
SMSTORE7 | 3480401.68 | 0.00 | 3480401.68 | 1448728.57 | 4929130.25 | 3953920.18 | 4647.13 | 3202.67 | 910.21 | 94.21 |
SMSTORE8 | 3395687.98 | 0.00 | 3395687.98 | 1784553.10 | 5180241.08 | 3953920.18 | 4665.26 | 3297.33 | 797.40 | 76.38 |
Total Facility | 45140127.42 | 0.00 | 45140127.42 | 17300798.94 | 62440926.36 | 46635168.64 | 4683.90 | 4616.43 | 2139.78 | 247.11 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.3893 | 0.0000 | 0.3893 | 0.1144 | 0.5036 | 0.2682 | 222.83 | 4201.83 | 1415.33 |
SMSTORE1 | 0.2297 | 0.0000 | 0.2297 | 0.0609 | 0.2907 | 0.1341 | 1169.62 | 2838.54 | 1831.84 |
SMSTORE2 | 0.2487 | 0.0000 | 0.2487 | 0.0795 | 0.3281 | 0.1285 | 0.00 | 3182.75 | 1212.25 |
SMSTORE3 | 0.2474 | 0.0000 | 0.2474 | 0.0795 | 0.3269 | 0.1285 | 0.00 | 3209.33 | 1185.67 |
SMSTORE4 | 0.2396 | 0.0000 | 0.2396 | 0.0795 | 0.3190 | 0.1285 | 0.00 | 3286.58 | 1108.42 |
LGSTORE2 | 0.3946 | 0.0000 | 0.3946 | 0.1526 | 0.5472 | 0.2958 | 0.00 | 3269.50 | 760.50 |
SMSTORE5 | 0.2397 | 0.0000 | 0.2397 | 0.0848 | 0.3244 | 0.1479 | 0.00 | 3129.50 | 900.50 |
SMSTORE6 | 0.2375 | 0.0000 | 0.2375 | 0.0848 | 0.3223 | 0.1479 | 0.00 | 3143.17 | 886.83 |
SMSTORE7 | 0.2312 | 0.0000 | 0.2312 | 0.0848 | 0.3160 | 0.1479 | 0.00 | 3202.17 | 827.83 |
SMSTORE8 | 0.2268 | 0.0000 | 0.2268 | 0.0893 | 0.3161 | 0.1479 | 0.00 | 3296.83 | 733.17 |
Total Facility | 2.6845 | 0.0000 | 2.6845 | 0.9099 | 3.5945 | 1.6752 | 1291.27 | 4611.96 | 2049.49 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 7854646.49 | 0.00 | 7854646.49 | 7870781.79 | 7339.61 | 8.00 | 1412.39 | 23.97 |
PSZ-AC_2:2 | 4657787.29 | 0.00 | 4657787.29 | 3935374.10 | 6911.22 | 7.83 | 1840.95 | 36.19 |
PSZ-AC_3:3 | 3907867.69 | 0.00 | 3907867.69 | 3701819.01 | 7450.19 | 4.42 | 1305.39 | 137.31 |
PSZ-AC_4:4 | 3889008.30 | 0.00 | 3889008.30 | 3701819.01 | 7475.86 | 4.08 | 1280.06 | 133.92 |
PSZ-AC_5:5 | 3761733.35 | 0.00 | 3761733.35 | 3701819.01 | 7555.83 | 5.33 | 1198.83 | 123.14 |
PSZ-AC_6:6 | 5609622.31 | 0.00 | 5609622.31 | 7907875.00 | 7946.06 | 4.50 | 809.44 | 83.44 |
PSZ-AC_7:7 | 3454600.88 | 0.00 | 3454600.88 | 3953920.18 | 7773.31 | 4.67 | 982.03 | 100.08 |
PSZ-AC_8:8 | 3421711.25 | 0.00 | 3421711.25 | 3953920.18 | 7787.83 | 5.42 | 966.75 | 98.83 |
PSZ-AC_9:9 | 3325121.07 | 0.00 | 3325121.07 | 3953920.18 | 7854.63 | 4.67 | 900.71 | 94.21 |
PSZ-AC_10:10 | 3244186.93 | 0.00 | 3244186.93 | 3953920.18 | 7966.68 | 2.00 | 791.32 | 76.29 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.3719 | 0.0000 | 0.3719 | 0.2682 | 4433.50 | 8.00 | 1398.50 |
PSZ-AC_2:2 | 0.2195 | 0.0000 | 0.2195 | 0.1341 | 4019.08 | 7.75 | 1813.17 |
PSZ-AC_3:3 | 0.2376 | 0.0000 | 0.2376 | 0.1285 | 3188.17 | 3.83 | 1203.00 |
PSZ-AC_4:4 | 0.2364 | 0.0000 | 0.2364 | 0.1285 | 3213.08 | 3.00 | 1178.92 |
PSZ-AC_5:5 | 0.2289 | 0.0000 | 0.2289 | 0.1285 | 3290.92 | 4.83 | 1099.25 |
PSZ-AC_6:6 | 0.3770 | 0.0000 | 0.3770 | 0.2958 | 3271.50 | 3.83 | 754.67 |
PSZ-AC_7:7 | 0.2290 | 0.0000 | 0.2290 | 0.1479 | 3131.50 | 3.67 | 894.83 |
PSZ-AC_8:8 | 0.2269 | 0.0000 | 0.2269 | 0.1479 | 3144.33 | 4.17 | 881.50 |
PSZ-AC_9:9 | 0.2209 | 0.0000 | 0.2209 | 0.1479 | 3206.50 | 3.83 | 819.67 |
PSZ-AC_10:10 | 0.2166 | 0.0000 | 0.2166 | 0.1479 | 3300.17 | 1.83 | 728.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 740.17 | 790.50 | 0.00 | 0.00 | 0.00 | 4135.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 586.79 | 1432.77 | 0.00 | 0.00 | 0.00 | 2989.47 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 472.76 | 878.79 | 0.00 | 0.00 | 0.00 | 3180.75 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 466.40 | 854.85 | 0.00 | 0.00 | 0.00 | 3207.67 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 442.06 | 791.17 | 0.00 | 0.00 | 0.00 | 3284.92 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 450.94 | 425.92 | 0.00 | 0.00 | 0.00 | 3236.58 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 416.47 | 584.11 | 0.00 | 0.00 | 0.00 | 3129.50 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 410.72 | 574.94 | 0.00 | 0.00 | 0.00 | 3143.17 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 390.35 | 533.03 | 0.00 | 0.00 | 0.00 | 3200.83 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 364.63 | 445.50 | 0.00 | 0.00 | 0.00 | 3296.17 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.9604 | 0.5168 | 0.0000 | 0.0000 | 0.0000 | 0.2581 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.7797 | 0.3229 | 0.0000 | 0.0000 | 0.0000 | 0.1261 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.8056 | 0.3782 | 0.0000 | 0.0000 | 0.0000 | 0.1224 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.8109 | 0.3822 | 0.0000 | 0.0000 | 0.0000 | 0.1224 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.8043 | 0.3818 | 0.0000 | 0.0000 | 0.0000 | 0.1224 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.9421 | 0.5516 | 0.0000 | 0.0000 | 0.0000 | 0.2828 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.7355 | 0.3770 | 0.0000 | 0.0000 | 0.0000 | 0.1415 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.7298 | 0.3754 | 0.0000 | 0.0000 | 0.0000 | 0.1414 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.7237 | 0.3717 | 0.0000 | 0.0000 | 0.0000 | 0.1415 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.7490 | 0.3812 | 0.0000 | 0.0000 | 0.0000 | 0.1414 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 835 |
Defaulted Fields | 817 |
Fields with Defaults | 2693 |
Autosized Fields | 174 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 768.18 | 2102.83 | 01-JAN-07:40 | 75845.60 | 26-JUN-14:10 |
Electricity:Building | 405.94 | 891.83 | 01-JAN-00:20 | 25756.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 90.96 | 148.64 | 01-JAN-00:20 | 4765.21 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 405.94 | 891.83 | 01-JAN-00:20 | 25756.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 64.71 | 75.00 | 01-JAN-00:20 | 3421.96 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 64.71 | 75.00 | 01-JAN-00:20 | 3421.96 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 277.79 | 450.00 | 01-JAN-00:20 | 17697.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 52.56 | 74.32 | 01-JAN-00:20 | 2762.01 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 39.44 | 37.50 | 01-JAN-00:20 | 2090.38 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 39.44 | 37.50 | 01-JAN-00:20 | 2090.38 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 39.28 | 74.32 | 01-JAN-00:10 | 2624.53 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 28.85 | 37.50 | 01-JAN-00:10 | 1952.90 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 47.80 | 148.64 | 01-JAN-00:10 | 3421.36 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 28.62 | 75.00 | 01-JAN-00:10 | 2078.11 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 28.62 | 75.00 | 01-JAN-00:10 | 2078.11 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 24.20 | 74.32 | 01-JAN-00:10 | 1733.63 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 14.61 | 37.50 | 01-JAN-00:10 | 1062.01 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityProduced:Facility | 65.32 | -0.00 | 27-AUG-18:30 | 11248.97 | 26-APR-12:30 |
ElectricityProduced:Plant | 65.32 | -0.00 | 27-AUG-18:30 | 11248.97 | 26-APR-12:30 |
Photovoltaic:ElectricityProduced | 68.23 | 0.00 | 01-JAN-00:10 | 11717.66 | 26-APR-12:30 |
PowerConversion:ElectricityProduced | -2.91 | -468.70 | 26-APR-12:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 64.64 | 1211.00 | 04-JAN-07:10 | 12970.36 | 07-JAN-13:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 702.89 | 0.00 | 05-MAR-08:00 | 68394.98 | 26-JUN-16:40 |
ElectricityPurchased:Plant | 702.89 | 0.00 | 05-MAR-08:00 | 68394.98 | 26-JUN-16:40 |
Cogeneration:ElectricityPurchased | 702.89 | 0.00 | 05-MAR-08:00 | 68394.98 | 26-JUN-16:40 |
General:Cogeneration:ElectricityPurchased | 702.89 | 0.00 | 05-MAR-08:00 | 68394.98 | 26-JUN-16:40 |
ElectricitySurplusSold:Facility | 0.02 | 0.00 | 01-JAN-00:10 | 2025.13 | 11-JUN-07:00 |
ElectricitySurplusSold:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 2025.13 | 11-JUN-07:00 |
Cogeneration:ElectricitySurplusSold | 0.02 | 0.00 | 01-JAN-00:10 | 2025.13 | 11-JUN-07:00 |
General:Cogeneration:ElectricitySurplusSold | 0.02 | 0.00 | 01-JAN-00:10 | 2025.13 | 11-JUN-07:00 |
ElectricityNet:Facility | 702.86 | -2025.13 | 11-JUN-07:00 | 68394.98 | 26-JUN-16:40 |
ElectricityNet:Plant | 702.86 | -2025.13 | 11-JUN-07:00 | 68394.98 | 26-JUN-16:40 |
Cogeneration:ElectricityNet | 702.86 | -2025.13 | 11-JUN-07:00 | 68394.98 | 26-JUN-16:40 |
General:Cogeneration:ElectricityNet | 702.86 | -2025.13 | 11-JUN-07:00 | 68394.98 | 26-JUN-16:40 |
Electricity:HVAC | 256.47 | 0.00 | 01-JAN-00:10 | 45447.25 | 26-JUN-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 64.28 | 0.00 | 01-JAN-00:10 | 33380.97 | 26-JUN-15:00 |
General:Cooling:Electricity | 64.28 | 0.00 | 01-JAN-00:10 | 33380.97 | 26-JUN-15:00 |
Fans:Electricity | 192.18 | 0.00 | 01-JAN-00:10 | 12608.69 | 23-DEC-08:10 |
General:Fans:Electricity | 192.18 | 0.00 | 01-JAN-00:10 | 12608.69 | 23-DEC-08:10 |
ExteriorLights:Electricity | 41.13 | 0.00 | 01-JAN-07:30 | 3786.68 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 41.13 | 0.00 | 01-JAN-07:30 | 3786.68 | 01-JAN-06:10 |
WaterSystems:Electricity | 64.64 | 1211.00 | 04-JAN-07:10 | 12970.36 | 07-JAN-13:10 |
Water Heater:WaterSystems:Electricity | 64.64 | 1211.00 | 04-JAN-07:10 | 12970.36 | 07-JAN-13:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 244.44 | 0.00 | 01-JAN-00:10 | 185265.24 | 21-DEC-18:00 |
NaturalGas:HVAC | 244.44 | 0.00 | 01-JAN-00:10 | 185265.24 | 21-DEC-18:00 |
Heating:NaturalGas | 244.44 | 0.00 | 01-JAN-00:10 | 185265.24 | 21-DEC-18:00 |
General:Heating:NaturalGas | 244.44 | 0.00 | 01-JAN-00:10 | 185265.24 | 21-DEC-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 889.82 | 0.00 | 01-JAN-00:10 | 301654.96 | 23-DEC-08:10 |
EnergyTransfer:Building | 398.85 | 0.00 | 01-JAN-00:10 | 147983.97 | 23-DEC-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 79.46 | 0.00 | 01-JAN-00:10 | 30355.22 | 23-DEC-08:10 |
Heating:EnergyTransfer | 115.69 | 0.00 | 01-JAN-00:10 | 147983.97 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 17.48 | 0.00 | 01-JAN-00:10 | 30355.22 | 23-DEC-08:10 |
General:Heating:EnergyTransfer | 115.69 | 0.00 | 01-JAN-00:10 | 147983.97 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 17.48 | 0.00 | 01-JAN-00:10 | 30355.22 | 23-DEC-08:10 |
Cooling:EnergyTransfer | 283.15 | 0.00 | 01-JAN-00:10 | 77523.54 | 26-JUN-15:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 61.98 | 0.00 | 01-JAN-00:10 | 12999.89 | 16-AUG-16:10 |
General:Cooling:EnergyTransfer | 283.15 | 0.00 | 01-JAN-00:10 | 77523.54 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 61.98 | 0.00 | 01-JAN-00:10 | 12999.89 | 16-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 40.23 | 0.00 | 01-JAN-00:10 | 11683.02 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 5.54 | 0.00 | 01-JAN-00:10 | 11683.02 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 5.54 | 0.00 | 01-JAN-00:10 | 11683.02 | 23-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 34.68 | 0.00 | 01-JAN-00:10 | 9959.83 | 12-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 34.68 | 0.00 | 01-JAN-00:10 | 9959.83 | 12-AUG-18:20 |
EnergyTransfer:Zone:SMSTORE2 | 32.12 | 0.00 | 01-JAN-00:10 | 12528.55 | 24-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 7.17 | 0.00 | 01-JAN-00:10 | 12528.55 | 24-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 7.17 | 0.00 | 01-JAN-00:10 | 12528.55 | 24-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 24.95 | 0.00 | 01-JAN-00:10 | 6760.78 | 26-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 24.95 | 0.00 | 01-JAN-00:10 | 6760.78 | 26-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 32.34 | 0.00 | 01-JAN-00:10 | 13058.87 | 24-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 7.78 | 0.00 | 01-JAN-00:10 | 13058.87 | 24-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 7.78 | 0.00 | 01-JAN-00:10 | 13058.87 | 24-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 24.55 | 0.00 | 01-JAN-00:10 | 6797.10 | 26-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 24.55 | 0.00 | 01-JAN-00:10 | 6797.10 | 26-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE4 | 31.69 | 0.00 | 01-JAN-00:10 | 13641.82 | 24-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 8.98 | 0.00 | 01-JAN-00:10 | 13641.82 | 24-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 8.98 | 0.00 | 01-JAN-00:10 | 13641.82 | 24-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 22.71 | 0.00 | 01-JAN-00:10 | 6694.71 | 26-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 22.71 | 0.00 | 01-JAN-00:10 | 6694.71 | 26-JUN-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 57.65 | 0.00 | 01-JAN-00:10 | 27848.47 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 16.54 | 0.00 | 01-JAN-00:10 | 27848.47 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 16.54 | 0.00 | 01-JAN-00:10 | 27848.47 | 23-DEC-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 41.12 | 0.00 | 01-JAN-00:10 | 12593.25 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 41.12 | 0.00 | 01-JAN-00:10 | 12593.25 | 26-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 29.33 | 0.00 | 01-JAN-00:10 | 14297.96 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 9.90 | 0.00 | 01-JAN-00:10 | 14297.96 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 9.90 | 0.00 | 01-JAN-00:10 | 14297.96 | 23-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 19.43 | 0.00 | 01-JAN-00:10 | 6642.44 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 19.43 | 0.00 | 01-JAN-00:10 | 6642.44 | 26-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 29.25 | 0.00 | 01-JAN-00:10 | 14364.52 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 10.23 | 0.00 | 01-JAN-00:10 | 14364.52 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 10.23 | 0.00 | 01-JAN-00:10 | 14364.52 | 23-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 19.02 | 0.00 | 01-JAN-00:10 | 6594.37 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 19.02 | 0.00 | 01-JAN-00:10 | 6594.37 | 26-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 29.69 | 0.00 | 01-JAN-00:10 | 15040.45 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 11.98 | 0.00 | 01-JAN-00:10 | 15040.45 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 11.98 | 0.00 | 01-JAN-00:10 | 15040.45 | 23-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 17.71 | 0.00 | 01-JAN-00:10 | 6498.62 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 17.71 | 0.00 | 01-JAN-00:10 | 6498.62 | 26-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 37.08 | 0.00 | 01-JAN-00:10 | 17233.90 | 19-MAR-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 20.10 | 0.00 | 01-JAN-00:10 | 17233.90 | 19-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 20.10 | 0.00 | 01-JAN-00:10 | 17233.90 | 19-MAR-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 16.99 | 0.00 | 01-JAN-00:10 | 6771.24 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 16.99 | 0.00 | 01-JAN-00:10 | 6771.24 | 26-JUN-15:00 |
EnergyTransfer:HVAC | 490.97 | 0.00 | 01-JAN-00:10 | 163033.41 | 21-DEC-18:00 |
HeatingCoils:EnergyTransfer | 215.11 | 0.00 | 01-JAN-00:10 | 163033.41 | 21-DEC-18:00 |
CoolingCoils:EnergyTransfer | 275.87 | 0.00 | 01-JAN-00:10 | 118563.02 | 26-JUN-16:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 17.481 | -61.984 | 0.000 | 0.000 | 25.080 | 64.707 | 26.249 | 17.181 | 0.000 | 3.048 | 0.003 | 0.000 | -7.995 | 0.000 | -29.487 | -54.282 |
SMSTORE1 | 0.000 | 0.000 | 5.544 | -34.683 | 0.000 | 0.000 | 12.300 | 39.440 | 13.125 | 8.515 | 0.000 | 1.650 | 0.001 | 0.000 | -4.167 | 0.000 | -14.547 | -27.179 |
SMSTORE2 | 0.000 | 0.000 | 7.166 | -24.953 | 0.000 | 0.000 | 7.429 | 28.854 | 10.421 | 8.494 | 0.000 | 1.627 | 0.001 | 0.000 | -4.178 | 0.000 | -15.021 | -19.840 |
SMSTORE3 | 0.000 | 0.000 | 7.784 | -24.551 | 0.000 | 0.000 | 7.438 | 28.854 | 10.421 | 8.502 | 0.000 | 1.627 | 0.002 | 0.000 | -4.148 | 0.000 | -14.974 | -20.954 |
SMSTORE4 | 0.000 | 0.000 | 8.981 | -22.712 | 0.000 | 0.000 | 7.460 | 28.854 | 10.421 | 8.521 | 0.000 | 1.628 | 0.001 | 0.000 | -4.101 | 0.000 | -14.878 | -24.174 |
LGSTORE2 | 0.000 | 0.000 | 16.538 | -41.117 | 0.000 | 0.000 | 25.872 | 28.624 | 19.173 | 17.119 | 0.000 | 2.938 | 0.004 | 0.000 | -7.967 | 0.000 | -26.978 | -34.201 |
SMSTORE5 | 0.000 | 0.000 | 9.902 | -19.431 | 0.000 | 0.000 | 12.864 | 14.614 | 9.586 | 8.535 | 0.000 | 1.631 | 0.002 | 0.000 | -3.998 | 0.000 | -14.815 | -18.889 |
SMSTORE6 | 0.000 | 0.000 | 10.226 | -19.021 | 0.000 | 0.000 | 12.871 | 14.614 | 9.586 | 8.541 | 0.000 | 1.631 | 0.002 | 0.000 | -3.985 | 0.000 | -14.794 | -19.668 |
SMSTORE7 | 0.000 | 0.000 | 11.977 | -17.712 | 0.000 | 0.000 | 12.902 | 14.614 | 9.586 | 8.562 | 0.000 | 1.631 | 0.001 | 0.000 | -3.932 | 0.000 | -14.697 | -22.932 |
SMSTORE8 | 0.000 | 0.000 | 20.097 | -16.988 | 0.000 | 0.000 | 12.957 | 14.614 | 9.586 | 8.612 | 0.000 | 1.712 | 0.003 | 0.000 | -3.737 | 0.000 | -18.644 | -28.208 |
Total Facility | 0.000 | 0.000 | 115.695 | -283.151 | 0.000 | 0.000 | 137.174 | 277.790 | 128.154 | 102.584 | 0.000 | 19.123 | 0.019 | 0.000 | -48.207 | 0.000 | -178.835 | -270.328 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 18-JUL-07:03 | 0.00 | 0.00 | 0.00 | -19965.20 | 0.00 | 0.00 | 184.44 | 75.00 | 74.62 | 291.97 | 0.00 | 16.16 | 19323.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 16-SEP-18:34 | 0.00 | 0.00 | 0.00 | -20026.58 | 0.00 | 0.00 | 1073.09 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 16400.08 | 0.00 | -103.25 | 0.00 | -105.34 | 0.00 |
SMSTORE2 | 16-JUL-07:03 | 0.00 | 0.00 | 0.00 | -13838.64 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 146.82 | 0.00 | 57.26 | 13559.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 16-JUL-07:03 | 0.00 | 0.00 | 0.00 | -14406.95 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 146.08 | 0.00 | 57.14 | 14128.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 16-JUL-07:03 | 0.00 | 0.00 | 0.00 | -13201.20 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 147.23 | 0.00 | 57.43 | 12921.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 17-JUL-07:03 | 0.00 | 0.00 | 0.00 | -25960.73 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 252.05 | 0.00 | 57.27 | 25502.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 16-JUL-08:62 | 0.00 | 0.00 | 0.00 | -13281.64 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 288.51 | 0.00 | 126.92 | 12791.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 16-JUL-08:62 | 0.00 | 0.00 | 0.00 | -13171.27 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 289.06 | 0.00 | 127.65 | 12680.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 16-JUL-08:62 | 0.00 | 0.00 | 0.00 | -13017.74 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 290.52 | 0.00 | 130.56 | 12522.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 16-JUL-08:62 | 0.00 | 0.00 | 0.00 | -13581.36 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 291.24 | 0.00 | 169.08 | 13046.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-JUL-07:03 | 0.00 | 0.00 | 0.00 | -104736.62 | 0.00 | 0.00 | 572.76 | 450.00 | 1452.23 | 1561.56 | 0.00 | 391.10 | 100308.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 22-DEC-08:12 | 0.00 | 0.00 | 53927.23 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 1271.02 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1799.05 | -53547.83 |
SMSTORE1 | 22-DEC-08:61 | 0.00 | 0.00 | 28501.39 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 456.41 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -846.00 | -28186.13 |
SMSTORE2 | 24-DEC-08:61 | 0.00 | 0.00 | 28892.93 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 484.49 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -742.59 | -28709.64 |
SMSTORE3 | 24-DEC-08:61 | 0.00 | 0.00 | 29012.64 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 487.53 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -737.43 | -28837.55 |
SMSTORE4 | 24-DEC-08:61 | 0.00 | 0.00 | 28824.04 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 490.30 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -731.98 | -28657.17 |
LGSTORE2 | 22-DEC-08:61 | 0.00 | 0.00 | 53027.30 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 942.68 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1484.13 | -52634.48 |
SMSTORE5 | 22-DEC-08:61 | 0.00 | 0.00 | 26664.45 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 469.42 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -820.00 | -26388.20 |
SMSTORE6 | 22-DEC-08:61 | 0.00 | 0.00 | 26489.14 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 470.11 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -818.72 | -26214.84 |
SMSTORE7 | 22-DEC-08:12 | 0.00 | 0.00 | 26948.09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 634.13 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -911.86 | -26744.68 |
SMSTORE8 | 22-DEC-08:12 | 0.00 | 0.00 | 27787.78 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 644.88 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1041.11 | -27465.87 |
Total Facility | 23-DEC-08:61 | 0.00 | 0.00 | 260123.21 | 0.00 | 0.00 | 0.00 | 346.82 | 450.00 | 1450.75 | 5107.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10961.09 | -256517.53 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0303 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0303 | 0.2027 | 1.0000 | Not calculated | 0.4115 | 0.2027 | ||
PSZ-AC_2:2 | 1.1029 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1029 | 0.1865 | 1.0000 | Not calculated | 0.2057 | 0.1865 | ||
PSZ-AC_3:3 | 1.1243 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1243 | 0.1830 | 1.0000 | Not calculated | 0.2057 | 0.1830 | ||
PSZ-AC_4:4 | 1.1309 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1309 | 0.1819 | 1.0000 | Not calculated | 0.2057 | 0.1819 | ||
PSZ-AC_5:5 | 1.1204 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1204 | 0.1836 | 1.0000 | Not calculated | 0.2057 | 0.1836 | ||
PSZ-AC_6:6 | 1.9899 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9899 | 0.2068 | 1.0000 | Not calculated | 0.4115 | 0.2068 | ||
PSZ-AC_7:7 | 1.0007 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0265 | 0.2004 | 1.0000 | Not calculated | 0.2057 | 0.2004 | ||
PSZ-AC_8:8 | 0.9910 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0180 | 0.2021 | 1.0000 | Not calculated | 0.2057 | 0.2021 | ||
PSZ-AC_9:9 | 1.0077 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0077 | 0.2042 | 1.0000 | Not calculated | 0.2057 | 0.2042 | ||
PSZ-AC_10:10 | 1.0446 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0446 | 0.1970 | 1.0000 | Not calculated | 0.2057 | 0.1970 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0303 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0303 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2027 | ||
PSZ-AC_2:2 | 1.1029 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1029 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1865 | ||
PSZ-AC_3:3 | 1.1243 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1243 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1830 | ||
PSZ-AC_4:4 | 1.1309 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1309 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1819 | ||
PSZ-AC_5:5 | 1.1204 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1204 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1836 | ||
PSZ-AC_6:6 | 1.9899 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9899 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2068 | ||
PSZ-AC_7:7 | 1.0007 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0007 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2056 | ||
PSZ-AC_8:8 | 0.9910 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9910 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2076 | ||
PSZ-AC_9:9 | 1.0077 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0077 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2042 | ||
PSZ-AC_10:10 | 1.0446 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0446 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1970 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.003540 | 56.2505 | 0.000610 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.003540 | 56.2505 | 0.000610 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.003540 | 56.25 | 0.000610 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.003540 | 56.25 | 0.000610 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0303 | 2.0303 | 2.0303 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1029 | 1.1029 | 1.1029 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1243 | 1.1243 | 1.1243 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1309 | 1.1309 | 1.1309 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1204 | 1.1204 | 1.1204 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9899 | 1.9899 | 1.9899 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0007 | 1.0007 | 1.0007 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9910 | 0.9910 | 0.9910 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0077 | 1.0077 | 1.0077 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0446 | 1.0446 | 1.0446 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0303 | 2.0303 | 2.0303 | 2.0303 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1029 | 1.1029 | 1.1029 | 1.1029 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1243 | 1.1243 | 1.1243 | 1.1243 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1309 | 1.1309 | 1.1309 | 1.1309 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1204 | 1.1204 | 1.1204 | 1.1204 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9899 | 1.9899 | 1.9899 | 1.9899 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0007 | 1.0265 | 1.0007 | 1.0007 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9910 | 1.0180 | 0.9910 | 0.9910 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0077 | 1.0077 | 1.0077 | 1.0077 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0446 | 1.0446 | 1.0446 | 1.0446 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0303 | 2.0303 | 2.0303 | No | 0.4115 | 0.2762 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1029 | 1.1029 | 1.1029 | No | 0.2057 | 0.2877 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1243 | 1.1243 | 1.1243 | No | 0.2057 | 0.2838 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1309 | 1.1309 | 1.1309 | No | 0.2057 | 0.2809 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1204 | 1.1204 | 1.1204 | No | 0.2057 | 0.2767 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9899 | 1.9899 | 1.9899 | No | 0.4115 | 0.2876 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0007 | 1.0007 | 1.0007 | No | 0.2057 | 0.2689 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9910 | 0.9910 | 0.9910 | No | 0.2057 | 0.2691 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0077 | 1.0077 | 1.0077 | No | 0.2057 | 0.2644 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0446 | 1.0446 | 1.0446 | No | 0.2057 | 0.2243 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0303 | 2.0303 | 2.0303 | 2.0303 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1029 | 1.1029 | 1.1029 | 1.1029 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1243 | 1.1243 | 1.1243 | 1.1243 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1309 | 1.1309 | 1.1309 | 1.1309 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1204 | 1.1204 | 1.1204 | 1.1204 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9899 | 1.9899 | 1.9899 | 1.9899 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0007 | 1.0007 | 1.0007 | 1.0007 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9910 | 0.9910 | 0.9910 | 0.9910 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0077 | 1.0077 | 1.0077 | 1.0077 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0446 | 1.0446 | 1.0446 | 1.0446 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 1.17 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 1.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 244.44 | 185265.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 64.28 | 33380.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 277.79 | 17697.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 41.13 | 3786.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 192.18 | 12608.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 64.64 | 12970.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 768.18 |
Natural Gas | 0.00 | 244.44 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1012.62 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 68.23 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 132.89 |
Space Heating | 0.00 |
Space Cooling | 30.75 |
Fans (All) | 91.94 |
Service Water Heating | 30.92 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 367.49 |
Subtotal | 367.49 |
Natural Gas [MJ/m2] | |
Space Heating | 116.94 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 116.94 |
Subtotal | 116.94 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 27.43 |
Space Heating | 24.14 |
Space Cooling | 6.35 |
Fans (All) | 18.98 |
Service Water Heating | 6.38 |
Receptacle Equipment | 12.66 |
Miscellaneous | 4.06 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3140. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3200. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4323. | 8760. |
LTG_SCH_BASE_LPD1 | 4243. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3479. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8759.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.50 | 0.00 | 0.00 | 0.00 |
Average | 8759.87 | 0.13 | 0.00 | 0.00 | 0.00 |
Sum | 87598.67 | 1.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25474.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25474.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25474.67 | 0.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93211.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 25474.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93211.00 | 0.50 | 0.00 | 0.00 | 0.00 |
Average | 48610.07 | 0.13 | 0.00 | 0.00 | 0.00 |
Sum | 486100.67 | 1.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8737.83 | 22.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8732.33 | 27.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8719.50 | 40.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8718.83 | 41.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8724.17 | 35.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8737.50 | 22.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8734.83 | 25.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8735.17 | 24.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8739.67 | 20.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8749.17 | 10.83 | 0.00 | 0.00 | 0.00 |
Min | 8718.83 | 10.83 | 0.00 | 0.00 | 0.00 |
Max | 8749.17 | 41.17 | 0.00 | 0.00 | 0.00 |
Average | 8732.90 | 27.10 | 0.00 | 0.00 | 0.00 |
Sum | 87329.00 | 271.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 88929.33 | 111.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43719.83 | 57.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25432.83 | 42.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25432.50 | 42.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25433.00 | 42.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93126.33 | 84.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45855.67 | 56.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45855.67 | 56.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45853.00 | 59.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45851.50 | 60.50 | 0.00 | 0.00 | 0.00 |
Min | 25432.50 | 42.00 | 0.00 | 0.00 | 0.00 |
Max | 93126.33 | 111.67 | 0.00 | 0.00 | 0.00 |
Average | 48548.97 | 61.23 | 0.00 | 0.00 | 0.00 |
Sum | 485489.67 | 612.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:09
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153487E+10 | 6721.44 | 06-JAN-00:12 | -15.7 | -15.7 | 0.109075E+10 | 1685.82 | 20-JAN-13:00 | 21.00 | 6.96 |
February | 0.111150E+10 | 5469.60 | 10-FEB-22:33 | -4.0 | -6.2 | 0.980888E+09 | 1685.77 | 18-FEB-13:00 | 20.00 | 7.73 |
March | 0.199730E+10 | 5032.08 | 14-MAR-13:30 | 23.50 | 7.75 | 0.114884E+10 | 1685.83 | 12-MAR-16:10 | 23.50 | 7.75 |
April | 0.190360E+10 | 4154.25 | 10-APR-19:00 | 5.00 | -1.2 | 0.113014E+10 | 1685.82 | 07-APR-12:00 | 5.00 | -1.2 |
May | 0.445772E+10 | 7360.14 | 31-MAY-16:10 | 27.83 | 14.82 | 0.135303E+10 | 1685.88 | 21-MAY-16:10 | 27.83 | 14.82 |
June | 0.103572E+11 | 13916.05 | 14-JUN-07:03 | 28.30 | 11.72 | 0.135444E+10 | 1685.97 | 17-JUN-12:30 | 24.65 | 16.62 |
July | 0.108603E+11 | 19964.44 | 18-JUL-07:03 | 24.33 | 12.85 | 0.141261E+10 | 1685.98 | 23-JUL-17:40 | 22.33 | 16.56 |
August | 0.112557E+11 | 13177.05 | 03-AUG-07:03 | 21.33 | 15.03 | 0.139390E+10 | 1686.02 | 11-AUG-12:39 | 33.00 | 12.19 |
September | 0.964392E+10 | 14324.24 | 13-SEP-07:03 | 20.18 | 12.26 | 0.135460E+10 | 1685.94 | 01-SEP-12:00 | 20.18 | 12.26 |
October | 0.465167E+10 | 8919.30 | 11-OCT-14:00 | 27.00 | 9.73 | 0.127562E+10 | 1685.85 | 07-OCT-12:00 | 27.00 | 9.73 |
November | 0.278308E+10 | 4957.21 | 19-NOV-18:35 | 3.33 | 1.15 | 0.109616E+10 | 1685.85 | 05-NOV-12:00 | 3.33 | 1.15 |
December | 0.142627E+10 | 7671.69 | 22-DEC-00:12 | -20.3 | -20.4 | 0.110577E+10 | 1685.82 | 02-DEC-13:50 | -20.3 | -20.4 |
Annual Sum or Average | 0.619832E+11 | 0.146967E+11 | ||||||||
Minimum of Months | 0.111150E+10 | 4154.25 | -20.3 | -20.4 | 0.980888E+09 | 1685.77 | -20.3 | -20.4 | ||
Maximum of Months | 0.112557E+11 | 19964.44 | 28.30 | 15.03 | 0.141261E+10 | 1686.02 | 33.00 | 16.62 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.606206E+09 | 3493.21 | 04-JAN-18:33 | -12.3 | -12.3 | 0.584329E+09 | 842.90 | 20-JAN-13:00 | 21.00 | 6.96 |
February | 0.493901E+09 | 1918.04 | 28-FEB-18:20 | 2.00 | 2.00 | 0.516706E+09 | 842.90 | 18-FEB-13:09 | 2.00 | 2.00 |
March | 0.104804E+10 | 3451.92 | 14-MAR-13:30 | 23.50 | 7.75 | 0.604257E+09 | 842.90 | 12-MAR-17:00 | 23.50 | 7.75 |
April | 0.849820E+09 | 2219.52 | 20-APR-17:10 | 18.67 | 8.36 | 0.606535E+09 | 842.90 | 08-APR-12:20 | 18.67 | 8.36 |
May | 0.287109E+10 | 19872.98 | 28-MAY-17:33 | 18.00 | 9.79 | 0.693588E+09 | 842.91 | 21-MAY-16:10 | 18.00 | 9.79 |
June | 0.611405E+10 | 19023.39 | 12-JUN-21:42 | 19.45 | 9.76 | 0.672439E+09 | 842.95 | 03-JUN-12:09 | 19.45 | 9.76 |
July | 0.641361E+10 | 19413.07 | 01-JUL-21:35 | 18.93 | 7.12 | 0.701750E+09 | 842.95 | 30-JUL-12:09 | 25.50 | 19.38 |
August | 0.653442E+10 | 19786.63 | 18-AUG-21:22 | 18.50 | 8.58 | 0.691396E+09 | 842.94 | 27-AUG-16:10 | 21.00 | 14.98 |
September | 0.554214E+10 | 20026.38 | 16-SEP-18:34 | 18.30 | 8.89 | 0.677053E+09 | 842.93 | 01-SEP-12:00 | 18.30 | 8.89 |
October | 0.249400E+10 | 19267.29 | 09-OCT-17:47 | 18.50 | 8.00 | 0.664333E+09 | 842.90 | 08-OCT-12:00 | 18.50 | 8.00 |
November | 0.114200E+10 | 3103.24 | 07-NOV-14:30 | 22.00 | 7.34 | 0.593386E+09 | 842.90 | 05-NOV-17:00 | 22.00 | 7.34 |
December | 0.573618E+09 | 2521.99 | 05-DEC-18:10 | -2.2 | -2.9 | 0.582023E+09 | 842.90 | 01-DEC-13:09 | -2.2 | -2.9 |
Annual Sum or Average | 0.346829E+11 | 0.758780E+10 | ||||||||
Minimum of Months | 0.493901E+09 | 1918.04 | -12.3 | -12.3 | 0.516706E+09 | 842.90 | -2.2 | -2.9 | ||
Maximum of Months | 0.653442E+10 | 20026.38 | 23.50 | 9.79 | 0.701750E+09 | 842.95 | 25.50 | 19.38 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.419175E+09 | 1798.44 | 27-JAN-18:15 | 4.00 | 3.02 | 0.341616E+09 | 842.56 | 21-JAN-13:00 | 4.00 | 3.02 |
February | 0.321313E+09 | 1862.81 | 28-FEB-18:20 | 2.00 | 2.00 | 0.302542E+09 | 842.90 | 18-FEB-13:09 | 2.00 | 2.00 |
March | 0.718262E+09 | 3394.04 | 14-MAR-13:00 | 24.00 | 7.90 | 0.366333E+09 | 842.89 | 11-MAR-13:09 | 24.00 | 7.90 |
April | 0.566510E+09 | 2146.64 | 20-APR-17:10 | 18.67 | 8.36 | 0.358769E+09 | 842.90 | 08-APR-12:09 | 18.67 | 8.36 |
May | 0.189923E+10 | 4046.14 | 17-MAY-13:00 | 29.00 | 11.92 | 0.419722E+09 | 842.90 | 06-MAY-12:00 | 29.00 | 11.92 |
June | 0.453509E+10 | 8735.22 | 27-JUN-06:03 | 20.78 | 8.99 | 0.417015E+09 | 842.96 | 03-JUN-12:09 | 20.78 | 8.99 |
July | 0.471032E+10 | 13838.63 | 16-JUL-07:03 | 26.67 | 13.28 | 0.420138E+09 | 842.95 | 29-JUL-12:20 | 24.33 | 18.51 |
August | 0.488356E+10 | 8433.89 | 20-AUG-07:03 | 21.00 | 14.01 | 0.431660E+09 | 842.91 | 05-AUG-12:09 | 21.00 | 14.01 |
September | 0.400626E+10 | 12335.77 | 13-SEP-06:03 | 18.58 | 11.47 | 0.409323E+09 | 842.90 | 02-SEP-12:09 | 18.58 | 11.47 |
October | 0.169928E+10 | 4769.73 | 11-OCT-14:00 | 27.00 | 9.73 | 0.391397E+09 | 842.90 | 07-OCT-12:50 | 27.00 | 9.73 |
November | 0.815093E+09 | 2894.98 | 07-NOV-14:00 | 22.00 | 7.34 | 0.344698E+09 | 821.76 | 18-NOV-13:00 | 10.00 | 5.07 |
December | 0.378960E+09 | 2462.09 | 05-DEC-19:00 | -3.0 | -3.0 | 0.337644E+09 | 842.90 | 02-DEC-13:00 | -3.0 | -3.0 |
Annual Sum or Average | 0.249531E+11 | 0.454086E+10 | ||||||||
Minimum of Months | 0.321313E+09 | 1798.44 | -3.0 | -3.0 | 0.302542E+09 | 821.76 | -3.0 | -3.0 | ||
Maximum of Months | 0.488356E+10 | 13838.63 | 29.00 | 14.01 | 0.431660E+09 | 842.96 | 29.00 | 18.51 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.364669E+09 | 1749.95 | 27-JAN-18:15 | 4.00 | 3.02 | 0.340035E+09 | 835.04 | 21-JAN-13:00 | 4.00 | 3.02 |
February | 0.280305E+09 | 1892.53 | 11-FEB-11:45 | -6.8 | -7.2 | 0.301308E+09 | 842.90 | 18-FEB-13:09 | 20.00 | 7.74 |
March | 0.658285E+09 | 3280.82 | 14-MAR-13:00 | 24.00 | 7.90 | 0.365427E+09 | 842.89 | 11-MAR-13:09 | 24.00 | 7.90 |
April | 0.497937E+09 | 2048.84 | 20-APR-17:10 | 18.67 | 8.36 | 0.357527E+09 | 842.90 | 08-APR-12:09 | 18.67 | 8.36 |
May | 0.182630E+10 | 3997.04 | 17-MAY-13:00 | 29.00 | 11.92 | 0.419098E+09 | 842.90 | 13-MAY-12:50 | 29.00 | 11.92 |
June | 0.455553E+10 | 9144.08 | 27-JUN-06:03 | 20.78 | 8.99 | 0.417016E+09 | 842.96 | 03-JUN-12:09 | 20.78 | 8.99 |
July | 0.474754E+10 | 14406.95 | 16-JUL-07:03 | 26.67 | 13.28 | 0.420142E+09 | 842.96 | 29-JUL-12:20 | 24.33 | 18.51 |
August | 0.491288E+10 | 8895.90 | 21-AUG-06:03 | 19.75 | 12.40 | 0.431663E+09 | 842.91 | 05-AUG-12:09 | 19.75 | 12.40 |
September | 0.401305E+10 | 12758.67 | 13-SEP-06:03 | 18.58 | 11.47 | 0.409297E+09 | 842.90 | 02-SEP-12:09 | 18.58 | 11.47 |
October | 0.163572E+10 | 4733.75 | 11-OCT-14:00 | 27.00 | 9.73 | 0.390660E+09 | 842.90 | 07-OCT-12:50 | 27.00 | 9.73 |
November | 0.734223E+09 | 2717.75 | 07-NOV-14:00 | 22.00 | 7.34 | 0.342819E+09 | 811.69 | 18-NOV-13:00 | 10.00 | 5.07 |
December | 0.324609E+09 | 2360.97 | 05-DEC-18:20 | -2.3 | -2.9 | 0.336464E+09 | 842.90 | 02-DEC-13:00 | -2.3 | -2.9 |
Annual Sum or Average | 0.245510E+11 | 0.453146E+10 | ||||||||
Minimum of Months | 0.280305E+09 | 1749.95 | -6.8 | -7.2 | 0.301308E+09 | 811.69 | -2.3 | -2.9 | ||
Maximum of Months | 0.491288E+10 | 14406.95 | 29.00 | 13.28 | 0.431663E+09 | 842.96 | 29.00 | 18.51 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.277397E+09 | 1638.39 | 26-JAN-18:15 | 5.00 | 1.68 | 0.336424E+09 | 809.49 | 21-JAN-13:00 | 5.00 | 1.68 |
February | 0.211228E+09 | 1723.22 | 28-FEB-18:10 | 2.00 | 2.00 | 0.299235E+09 | 842.90 | 18-FEB-13:09 | 2.00 | 2.00 |
March | 0.522265E+09 | 2975.06 | 14-MAR-13:00 | 24.00 | 7.90 | 0.363197E+09 | 842.90 | 11-MAR-13:09 | 24.00 | 7.90 |
April | 0.364148E+09 | 1863.06 | 14-APR-18:00 | 1.00 | 0.07 | 0.354252E+09 | 842.90 | 08-APR-12:39 | 1.00 | 0.07 |
May | 0.157566E+10 | 3794.78 | 17-MAY-13:00 | 29.00 | 11.92 | 0.417441E+09 | 842.90 | 06-MAY-12:30 | 29.00 | 11.92 |
June | 0.436504E+10 | 8242.87 | 27-JUN-06:03 | 20.78 | 8.99 | 0.416976E+09 | 842.95 | 03-JUN-12:09 | 20.78 | 8.99 |
July | 0.457113E+10 | 13201.20 | 16-JUL-07:03 | 26.67 | 13.28 | 0.420102E+09 | 842.96 | 29-JUL-12:20 | 24.33 | 18.51 |
August | 0.472841E+10 | 8153.58 | 21-AUG-06:03 | 19.75 | 12.40 | 0.431623E+09 | 842.92 | 05-AUG-12:09 | 19.75 | 12.40 |
September | 0.382549E+10 | 11720.24 | 11-SEP-06:03 | 19.00 | 9.04 | 0.409001E+09 | 842.90 | 02-SEP-12:09 | 19.00 | 9.04 |
October | 0.143578E+10 | 4567.86 | 11-OCT-14:00 | 27.00 | 9.73 | 0.388306E+09 | 842.90 | 07-OCT-12:00 | 27.00 | 9.73 |
November | 0.595004E+09 | 2393.87 | 07-NOV-14:00 | 22.00 | 7.34 | 0.338774E+09 | 786.81 | 25-NOV-13:00 | 15.00 | 4.95 |
December | 0.240329E+09 | 1995.70 | 05-DEC-18:10 | -2.2 | -2.9 | 0.334203E+09 | 842.90 | 02-DEC-13:00 | -2.2 | -2.9 |
Annual Sum or Average | 0.227119E+11 | 0.450953E+10 | ||||||||
Minimum of Months | 0.211228E+09 | 1638.39 | -2.2 | -2.9 | 0.299235E+09 | 786.81 | -2.2 | -2.9 | ||
Maximum of Months | 0.472841E+10 | 13201.20 | 29.00 | 13.28 | 0.431623E+09 | 842.96 | 29.00 | 18.51 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.684235E+09 | 5305.78 | 31-JAN-18:23 | -2.5 | -2.5 | 0.111768E+10 | 2006.76 | 21-JAN-15:20 | -2.5 | -2.5 |
February | 0.447281E+09 | 4007.22 | 15-FEB-13:25 | 6.00 | 1.29 | 0.100703E+10 | 2245.53 | 18-FEB-15:09 | 18.83 | 7.90 |
March | 0.111860E+10 | 5094.32 | 14-MAR-13:00 | 24.00 | 7.90 | 0.121297E+10 | 2247.74 | 11-MAR-15:09 | 24.00 | 7.90 |
April | 0.966457E+09 | 3110.89 | 29-APR-11:00 | 9.00 | 8.38 | 0.116530E+10 | 2166.93 | 08-APR-14:00 | 9.00 | 8.38 |
May | 0.287878E+10 | 6762.94 | 17-MAY-14:10 | 28.67 | 11.73 | 0.139473E+10 | 2247.80 | 13-MAY-14:20 | 28.67 | 11.73 |
June | 0.754821E+10 | 25831.07 | 25-JUN-08:62 | 28.08 | 13.27 | 0.142937E+10 | 2247.92 | 03-JUN-14:00 | 28.08 | 13.27 |
July | 0.789457E+10 | 25960.72 | 17-JUL-07:03 | 25.50 | 12.20 | 0.143789E+10 | 2247.93 | 15-JUL-14:30 | 25.50 | 12.20 |
August | 0.821927E+10 | 16747.97 | 20-AUG-08:63 | 23.50 | 14.21 | 0.147952E+10 | 2247.95 | 05-AUG-14:30 | 23.50 | 14.21 |
September | 0.666327E+10 | 16383.04 | 11-SEP-07:03 | 20.63 | 10.22 | 0.139759E+10 | 2247.80 | 30-SEP-14:00 | 17.20 | 13.90 |
October | 0.284278E+10 | 8436.43 | 11-OCT-14:10 | 26.83 | 9.68 | 0.128612E+10 | 2247.80 | 07-OCT-14:09 | 26.83 | 9.68 |
November | 0.133204E+10 | 6125.78 | 10-NOV-17:03 | 0.00 | -0.0 | 0.111179E+10 | 1994.92 | 09-NOV-13:00 | 0.00 | -0.0 |
December | 0.521114E+09 | 5104.34 | 05-DEC-13:53 | 3.00 | -2.6 | 0.112310E+10 | 2247.80 | 02-DEC-15:20 | 3.00 | -2.6 |
Annual Sum or Average | 0.411166E+11 | 0.151631E+11 | ||||||||
Minimum of Months | 0.447281E+09 | 3110.89 | -2.5 | -2.6 | 0.100703E+10 | 1994.92 | -2.5 | -2.6 | ||
Maximum of Months | 0.821927E+10 | 25960.72 | 28.67 | 14.21 | 0.147952E+10 | 2247.95 | 28.67 | 14.21 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196742E+09 | 2203.12 | 12-JAN-18:15 | -5.7 | -5.7 | 0.566392E+09 | 1059.40 | 21-JAN-15:20 | 13.67 | 5.40 |
February | 0.128983E+09 | 1448.17 | 16-FEB-19:25 | -0.5 | -2.3 | 0.507729E+09 | 1123.86 | 18-FEB-15:00 | 18.00 | 7.48 |
March | 0.368549E+09 | 2598.54 | 14-MAR-13:00 | 24.00 | 7.90 | 0.614644E+09 | 1123.85 | 11-MAR-15:20 | 24.00 | 7.90 |
April | 0.242641E+09 | 1894.65 | 22-APR-15:25 | 2.50 | 1.79 | 0.594874E+09 | 1123.86 | 08-APR-14:20 | 2.50 | 1.79 |
May | 0.122600E+10 | 3491.10 | 17-MAY-14:10 | 28.67 | 11.73 | 0.706865E+09 | 1123.87 | 13-MAY-14:39 | 28.67 | 11.73 |
June | 0.386777E+10 | 12557.55 | 25-JUN-08:62 | 28.08 | 13.27 | 0.714784E+09 | 1123.91 | 17-JUN-14:00 | 28.08 | 13.27 |
July | 0.405525E+10 | 13281.66 | 16-JUL-08:62 | 30.50 | 14.31 | 0.719079E+09 | 1123.88 | 29-JUL-14:09 | 23.00 | 17.56 |
August | 0.421422E+10 | 7777.46 | 20-AUG-08:63 | 23.50 | 14.21 | 0.739857E+09 | 1123.94 | 05-AUG-14:39 | 23.50 | 14.21 |
September | 0.336673E+10 | 7862.86 | 11-SEP-07:03 | 20.63 | 10.22 | 0.700655E+09 | 1123.87 | 02-SEP-14:09 | 20.63 | 10.22 |
October | 0.116427E+10 | 4368.40 | 11-OCT-14:10 | 26.83 | 9.68 | 0.654433E+09 | 1123.87 | 07-OCT-14:20 | 26.83 | 9.68 |
November | 0.452631E+09 | 2028.87 | 07-NOV-14:00 | 22.00 | 7.34 | 0.565539E+09 | 1000.65 | 25-NOV-15:09 | 13.50 | 4.91 |
December | 0.147230E+09 | 2796.93 | 18-DEC-18:43 | -9.7 | -10.0 | 0.567497E+09 | 1123.87 | 02-DEC-15:20 | -9.7 | -10.0 |
Annual Sum or Average | 0.194310E+11 | 0.765235E+10 | ||||||||
Minimum of Months | 0.128983E+09 | 1448.17 | -9.7 | -10.0 | 0.507729E+09 | 1000.65 | -9.7 | -10.0 | ||
Maximum of Months | 0.421422E+10 | 13281.66 | 30.50 | 14.31 | 0.739857E+09 | 1123.94 | 28.67 | 17.56 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185296E+09 | 2075.40 | 12-JAN-11:05 | -2.8 | -2.8 | 0.565502E+09 | 1055.18 | 21-JAN-15:20 | 13.67 | 5.40 |
February | 0.117177E+09 | 1772.65 | 02-FEB-11:25 | -0.5 | -5.0 | 0.507183E+09 | 1123.86 | 18-FEB-15:00 | 18.00 | 7.48 |
March | 0.346258E+09 | 2511.26 | 14-MAR-13:00 | 24.00 | 7.90 | 0.613797E+09 | 1123.85 | 11-MAR-15:20 | 24.00 | 7.90 |
April | 0.225723E+09 | 1511.61 | 22-APR-11:00 | 2.00 | 1.10 | 0.593688E+09 | 1123.86 | 08-APR-14:00 | 2.00 | 1.10 |
May | 0.117123E+10 | 3419.60 | 17-MAY-14:10 | 28.67 | 11.73 | 0.705809E+09 | 1123.87 | 06-MAY-14:39 | 28.67 | 11.73 |
June | 0.380072E+10 | 12040.02 | 25-JUN-08:62 | 28.08 | 13.27 | 0.714775E+09 | 1123.91 | 17-JUN-14:00 | 28.08 | 13.27 |
July | 0.399453E+10 | 13171.29 | 16-JUL-08:62 | 30.50 | 14.31 | 0.719068E+09 | 1123.88 | 29-JUL-14:09 | 23.00 | 17.56 |
August | 0.415482E+10 | 7501.75 | 20-AUG-08:63 | 23.50 | 14.21 | 0.739849E+09 | 1123.94 | 05-AUG-14:39 | 23.50 | 14.21 |
September | 0.331813E+10 | 7649.75 | 11-SEP-07:03 | 20.63 | 10.22 | 0.700552E+09 | 1123.87 | 16-SEP-14:39 | 23.67 | 10.69 |
October | 0.113644E+10 | 4310.83 | 11-OCT-14:10 | 26.83 | 9.68 | 0.653606E+09 | 1123.87 | 07-OCT-14:50 | 26.83 | 9.68 |
November | 0.436078E+09 | 1981.84 | 07-NOV-14:00 | 22.00 | 7.34 | 0.564636E+09 | 997.43 | 06-NOV-13:00 | 22.00 | 7.34 |
December | 0.134968E+09 | 1527.85 | 16-DEC-11:40 | 4.67 | 0.30 | 0.566973E+09 | 1123.87 | 02-DEC-15:20 | 4.67 | 0.30 |
Annual Sum or Average | 0.190214E+11 | 0.764544E+10 | ||||||||
Minimum of Months | 0.117177E+09 | 1511.61 | -2.8 | -5.0 | 0.507183E+09 | 997.43 | 2.00 | 0.30 | ||
Maximum of Months | 0.415482E+10 | 13171.29 | 30.50 | 14.31 | 0.739849E+09 | 1123.94 | 28.67 | 17.56 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132075E+09 | 1264.17 | 21-JAN-17:00 | 7.00 | 3.14 | 0.561908E+09 | 1030.98 | 21-JAN-15:20 | 7.00 | 3.14 |
February | 74696423.21 | 972.56 | 22-FEB-12:00 | 7.00 | 3.14 | 0.505093E+09 | 1123.87 | 18-FEB-15:30 | 7.00 | 3.14 |
March | 0.264555E+09 | 2208.40 | 14-MAR-13:00 | 24.00 | 7.90 | 0.609940E+09 | 1123.86 | 11-MAR-15:20 | 24.00 | 7.90 |
April | 0.157054E+09 | 1160.84 | 22-APR-11:00 | 2.00 | 1.10 | 0.588129E+09 | 1113.07 | 08-APR-14:00 | 2.00 | 1.10 |
May | 0.959205E+09 | 3230.00 | 17-MAY-14:10 | 28.67 | 11.73 | 0.701038E+09 | 1123.87 | 13-MAY-14:50 | 28.67 | 11.73 |
June | 0.362844E+10 | 10074.26 | 25-JUN-08:62 | 28.08 | 13.27 | 0.714751E+09 | 1123.91 | 17-JUN-14:00 | 28.08 | 13.27 |
July | 0.383682E+10 | 13017.76 | 16-JUL-08:62 | 30.50 | 14.31 | 0.719043E+09 | 1123.87 | 29-JUL-14:09 | 23.00 | 17.56 |
August | 0.401515E+10 | 6548.55 | 20-AUG-08:63 | 23.50 | 14.21 | 0.739834E+09 | 1123.94 | 05-AUG-14:39 | 23.50 | 14.21 |
September | 0.319078E+10 | 6809.04 | 11-SEP-07:03 | 20.63 | 10.22 | 0.700024E+09 | 1123.87 | 09-SEP-14:20 | 20.63 | 10.22 |
October | 0.100530E+10 | 4160.57 | 11-OCT-14:10 | 26.83 | 9.68 | 0.649251E+09 | 1123.87 | 07-OCT-14:09 | 26.83 | 9.68 |
November | 0.352080E+09 | 1784.14 | 07-NOV-14:00 | 22.00 | 7.34 | 0.560959E+09 | 997.43 | 06-NOV-13:00 | 22.00 | 7.34 |
December | 96217920.24 | 1894.66 | 06-DEC-11:35 | -1.3 | -3.1 | 0.564559E+09 | 1123.87 | 02-DEC-15:09 | -1.3 | -3.1 |
Annual Sum or Average | 0.177124E+11 | 0.761453E+10 | ||||||||
Minimum of Months | 74696423.21 | 972.56 | -1.3 | -3.1 | 0.505093E+09 | 997.43 | -1.3 | -3.1 | ||
Maximum of Months | 0.401515E+10 | 13017.76 | 30.50 | 14.31 | 0.739834E+09 | 1123.94 | 28.67 | 17.56 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44306044.72 | 950.15 | 21-JAN-16:40 | 8.33 | 3.61 | 0.555984E+09 | 997.38 | 20-JAN-13:00 | 8.33 | 3.61 |
February | 23419400.48 | 700.80 | 27-FEB-19:40 | 5.33 | 0.64 | 0.501477E+09 | 1105.55 | 18-FEB-15:09 | 5.33 | 0.64 |
March | 0.117127E+09 | 1896.32 | 14-MAR-13:00 | 24.00 | 7.90 | 0.602947E+09 | 1123.87 | 11-MAR-15:20 | 24.00 | 7.90 |
April | 55739570.32 | 904.01 | 20-APR-13:00 | 22.00 | 9.15 | 0.579183E+09 | 1065.06 | 08-APR-14:00 | 22.00 | 9.15 |
May | 0.647549E+09 | 3113.33 | 17-MAY-14:10 | 28.67 | 11.73 | 0.689526E+09 | 1123.87 | 06-MAY-14:20 | 28.67 | 11.73 |
June | 0.366427E+10 | 8706.75 | 25-JUN-08:62 | 28.08 | 13.27 | 0.714721E+09 | 1123.92 | 17-JUN-14:00 | 28.08 | 13.27 |
July | 0.387728E+10 | 13581.37 | 16-JUL-08:62 | 30.50 | 14.31 | 0.719054E+09 | 1123.87 | 22-JUL-14:00 | 30.00 | 16.48 |
August | 0.418722E+10 | 6749.51 | 16-AUG-14:10 | 36.83 | 16.33 | 0.739845E+09 | 1123.93 | 05-AUG-14:39 | 36.83 | 16.33 |
September | 0.329507E+10 | 6305.33 | 09-SEP-13:10 | 32.43 | 12.96 | 0.698776E+09 | 1123.87 | 02-SEP-14:30 | 32.43 | 12.96 |
October | 0.822252E+09 | 4205.80 | 11-OCT-14:10 | 26.83 | 9.68 | 0.642170E+09 | 1123.87 | 07-OCT-14:20 | 26.83 | 9.68 |
November | 0.213436E+09 | 1637.08 | 07-NOV-14:00 | 22.00 | 7.34 | 0.556160E+09 | 997.43 | 06-NOV-13:00 | 22.00 | 7.34 |
December | 40488984.52 | 944.89 | 16-DEC-15:00 | 8.00 | 2.14 | 0.560273E+09 | 1123.87 | 02-DEC-15:09 | 8.00 | 2.14 |
Annual Sum or Average | 0.169882E+11 | 0.756012E+10 | ||||||||
Minimum of Months | 23419400.48 | 700.80 | 5.33 | 0.64 | 0.501477E+09 | 997.38 | 5.33 | 0.64 | ||
Maximum of Months | 0.418722E+10 | 13581.37 | 36.83 | 16.33 | 0.739845E+09 | 1123.93 | 36.83 | 16.48 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.278474E+10 | 53751.77 | 05-JAN-08:61 | -17.0 |
February | 0.354145E+10 | 53752.30 | 12-FEB-08:61 | -16.5 |
March | 0.247625E+10 | 53736.42 | 29-MAR-07:01 | -5.5 |
April | 0.162184E+10 | 53730.85 | 17-APR-07:01 | -5.5 |
May | 0.167713E+09 | 53710.20 | 03-MAY-07:01 | 4.33 |
June | 16825677.52 | 1295.04 | 14-JUN-07:07 | 28.30 |
July | 15982679.63 | 1417.35 | 18-JUL-07:05 | 24.33 |
August | 14130074.91 | 1265.06 | 03-AUG-07:07 | 21.33 |
September | 28792484.15 | 2094.07 | 22-SEP-07:03 | 0.37 |
October | 0.105830E+10 | 53741.85 | 31-OCT-07:01 | -9.0 |
November | 0.148084E+10 | 53741.06 | 29-NOV-08:61 | -9.8 |
December | 0.427450E+10 | 53927.25 | 22-DEC-08:12 | -20.0 |
Annual Sum or Average | 0.174814E+11 | |||
Minimum of Months | 14130074.91 | 1265.06 | -20.0 | |
Maximum of Months | 0.427450E+10 | 53927.25 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.838790E+09 | 28493.66 | 05-JAN-08:61 | -17.0 |
February | 0.112850E+10 | 28496.72 | 12-FEB-08:61 | -16.5 |
March | 0.690567E+09 | 28489.88 | 29-MAR-07:01 | -5.5 |
April | 0.428382E+09 | 28484.97 | 17-APR-07:01 | -5.5 |
May | 83211402.10 | 15269.61 | 03-MAY-07:01 | 4.33 |
June | 8313541.20 | 1534.99 | 14-JUN-07:07 | 28.30 |
July | 12317655.58 | 1738.63 | 18-JUL-07:05 | 24.33 |
August | 10779116.67 | 1542.55 | 03-AUG-07:07 | 21.33 |
September | 18391795.07 | 1531.91 | 13-SEP-07:07 | 20.18 |
October | 0.376845E+09 | 28490.16 | 31-OCT-07:01 | -9.0 |
November | 0.472836E+09 | 28489.53 | 29-NOV-08:61 | -9.8 |
December | 0.147518E+10 | 28501.44 | 22-DEC-08:61 | -20.0 |
Annual Sum or Average | 0.554411E+10 | |||
Minimum of Months | 8313541.20 | 1531.91 | -20.0 | |
Maximum of Months | 0.147518E+10 | 28501.44 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110605E+10 | 28881.30 | 16-JAN-08:61 | -8.8 |
February | 0.136090E+10 | 28891.31 | 12-FEB-08:61 | -16.5 |
March | 0.857193E+09 | 28862.67 | 19-MAR-07:01 | -15.2 |
April | 0.560129E+09 | 28863.04 | 17-APR-06:01 | -7.7 |
May | 0.120457E+09 | 11463.24 | 02-MAY-06:02 | 0.17 |
June | 96884300.00 | 2176.81 | 26-JUN-19:12 | 34.57 |
July | 0.110657E+09 | 2067.44 | 15-JUL-17:12 | 33.67 |
August | 92063427.02 | 1769.51 | 26-AUG-17:12 | 30.67 |
September | 73912741.72 | 1830.29 | 10-SEP-16:12 | 31.63 |
October | 0.447623E+09 | 28604.53 | 31-OCT-06:01 | -9.0 |
November | 0.598176E+09 | 28854.02 | 30-NOV-07:01 | -11.3 |
December | 0.174154E+10 | 28892.93 | 24-DEC-08:61 | -15.7 |
Annual Sum or Average | 0.716559E+10 | |||
Minimum of Months | 73912741.72 | 1769.51 | -16.5 | |
Maximum of Months | 0.174154E+10 | 28892.93 | 34.57 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122488E+10 | 29001.07 | 16-JAN-08:61 | -8.8 |
February | 0.146509E+10 | 29011.00 | 12-FEB-08:61 | -16.5 |
March | 0.942031E+09 | 28982.33 | 19-MAR-07:01 | -15.2 |
April | 0.630258E+09 | 28983.04 | 17-APR-06:01 | -7.7 |
May | 0.135765E+09 | 15315.47 | 02-MAY-06:02 | 0.17 |
June | 97706879.87 | 2182.67 | 26-JUN-19:12 | 34.57 |
July | 0.111703E+09 | 2073.34 | 15-JUL-17:12 | 33.67 |
August | 92833270.74 | 1775.58 | 26-AUG-17:12 | 30.67 |
September | 75910110.21 | 1836.43 | 10-SEP-16:12 | 31.63 |
October | 0.484340E+09 | 28721.62 | 31-OCT-06:01 | -9.0 |
November | 0.661468E+09 | 28973.51 | 30-NOV-07:01 | -11.3 |
December | 0.186215E+10 | 29012.64 | 24-DEC-08:61 | -15.7 |
Annual Sum or Average | 0.778413E+10 | |||
Minimum of Months | 75910110.21 | 1775.58 | -16.5 | |
Maximum of Months | 0.186215E+10 | 29012.64 | 34.57 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143436E+10 | 28812.83 | 16-JAN-08:61 | -8.8 |
February | 0.167088E+10 | 28822.34 | 12-FEB-08:61 | -16.5 |
March | 0.111623E+10 | 28794.14 | 19-MAR-07:01 | -15.2 |
April | 0.775961E+09 | 28795.10 | 17-APR-06:01 | -7.7 |
May | 0.171842E+09 | 21088.64 | 02-MAY-06:02 | 0.17 |
June | 97495184.25 | 2176.25 | 26-JUN-19:12 | 34.57 |
July | 0.109798E+09 | 2067.10 | 15-JUL-17:12 | 33.67 |
August | 91501678.76 | 1769.14 | 26-AUG-17:12 | 30.67 |
September | 79000301.12 | 1829.53 | 10-SEP-16:12 | 31.63 |
October | 0.551612E+09 | 28537.93 | 31-OCT-06:01 | -9.0 |
November | 0.788292E+09 | 28785.54 | 30-NOV-07:01 | -11.3 |
December | 0.209357E+10 | 28824.04 | 24-DEC-08:61 | -15.7 |
Annual Sum or Average | 0.898054E+10 | |||
Minimum of Months | 79000301.12 | 1769.14 | -16.5 | |
Maximum of Months | 0.209357E+10 | 28824.04 | 34.57 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279307E+10 | 53020.53 | 05-JAN-08:61 | -17.0 |
February | 0.322182E+10 | 53017.21 | 06-FEB-08:61 | -7.5 |
March | 0.211714E+10 | 53014.69 | 29-MAR-07:01 | -5.5 |
April | 0.146365E+10 | 53012.16 | 17-APR-07:01 | -5.5 |
May | 0.167156E+09 | 52987.90 | 03-MAY-07:01 | 4.33 |
June | 47662504.25 | 2503.91 | 25-JUN-16:12 | 32.70 |
July | 65914393.94 | 2798.73 | 16-JUL-16:02 | 34.33 |
August | 36327749.18 | 2124.04 | 26-AUG-17:12 | 30.67 |
September | 53688093.25 | 2271.78 | 10-SEP-16:12 | 31.63 |
October | 0.102639E+10 | 53017.23 | 30-OCT-07:01 | -10.0 |
November | 0.152734E+10 | 53014.13 | 29-NOV-08:61 | -9.8 |
December | 0.401747E+10 | 53027.32 | 22-DEC-08:61 | -20.0 |
Annual Sum or Average | 0.165376E+11 | |||
Minimum of Months | 36327749.18 | 2124.04 | -20.0 | |
Maximum of Months | 0.401747E+10 | 53027.32 | 34.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163866E+10 | 26659.28 | 05-JAN-08:61 | -17.0 |
February | 0.185468E+10 | 26657.43 | 06-FEB-08:61 | -7.5 |
March | 0.126497E+10 | 26656.19 | 29-MAR-07:01 | -5.5 |
April | 0.921574E+09 | 26654.81 | 17-APR-07:01 | -5.5 |
May | 0.182722E+09 | 26640.89 | 03-MAY-07:01 | 4.33 |
June | 43352394.21 | 1895.79 | 25-JUN-16:12 | 32.70 |
July | 57255253.78 | 2032.20 | 15-JUL-17:12 | 33.67 |
August | 33467234.06 | 1710.50 | 26-AUG-17:12 | 30.67 |
September | 59029109.61 | 1782.66 | 10-SEP-16:12 | 31.63 |
October | 0.625752E+09 | 26657.33 | 30-OCT-07:01 | -10.0 |
November | 0.922585E+09 | 26655.61 | 29-NOV-08:61 | -9.8 |
December | 0.229799E+10 | 26664.46 | 22-DEC-08:61 | -20.0 |
Annual Sum or Average | 0.990203E+10 | |||
Minimum of Months | 33467234.06 | 1710.50 | -20.0 | |
Maximum of Months | 0.229799E+10 | 26664.46 | 33.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170206E+10 | 26483.67 | 05-JAN-08:61 | -17.0 |
February | 0.191312E+10 | 26482.17 | 06-FEB-08:61 | -7.5 |
March | 0.131530E+10 | 26480.83 | 29-MAR-07:01 | -5.5 |
April | 0.961547E+09 | 26479.44 | 17-APR-07:01 | -5.5 |
May | 0.191163E+09 | 26465.85 | 03-MAY-07:01 | 4.33 |
June | 43583029.63 | 1888.81 | 25-JUN-16:12 | 32.70 |
July | 56638647.30 | 2025.04 | 15-JUL-17:12 | 33.67 |
August | 33128110.61 | 1702.91 | 26-AUG-17:12 | 30.67 |
September | 59800289.89 | 1775.17 | 10-SEP-16:12 | 31.63 |
October | 0.641855E+09 | 26481.81 | 30-OCT-07:01 | -10.0 |
November | 0.959131E+09 | 26480.14 | 29-NOV-08:61 | -9.8 |
December | 0.234832E+10 | 26489.15 | 22-DEC-08:61 | -20.0 |
Annual Sum or Average | 0.102256E+11 | |||
Minimum of Months | 33128110.61 | 1702.91 | -20.0 | |
Maximum of Months | 0.234832E+10 | 26489.15 | 33.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201798E+10 | 26783.67 | 05-JAN-08:61 | -17.0 |
February | 0.222215E+10 | 26813.06 | 06-FEB-08:13 | -7.0 |
March | 0.158885E+10 | 26780.41 | 29-MAR-07:01 | -5.5 |
April | 0.119328E+10 | 26778.79 | 17-APR-07:01 | -5.5 |
May | 0.232687E+09 | 26766.56 | 03-MAY-07:01 | 4.33 |
June | 47716130.91 | 1882.13 | 25-JUN-16:12 | 32.70 |
July | 55739734.13 | 2018.20 | 15-JUL-17:12 | 33.67 |
August | 32716502.01 | 1696.02 | 26-AUG-17:12 | 30.67 |
September | 64811991.46 | 1767.81 | 10-SEP-16:12 | 31.63 |
October | 0.731232E+09 | 26781.66 | 30-OCT-07:01 | -10.0 |
November | 0.113655E+10 | 26779.84 | 29-NOV-08:61 | -9.8 |
December | 0.265362E+10 | 26948.10 | 22-DEC-08:12 | -20.0 |
Annual Sum or Average | 0.119773E+11 | |||
Minimum of Months | 32716502.01 | 1696.02 | -20.0 | |
Maximum of Months | 0.265362E+10 | 26948.10 | 33.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336694E+10 | 27601.24 | 05-JAN-08:13 | -17.0 |
February | 0.374236E+10 | 27656.39 | 06-FEB-08:13 | -7.0 |
March | 0.282578E+10 | 27768.33 | 19-MAR-08:12 | -13.0 |
April | 0.222045E+10 | 27560.96 | 17-APR-07:12 | -5.0 |
May | 0.413221E+09 | 27433.34 | 03-MAY-07:01 | 4.33 |
June | 70882392.04 | 1919.20 | 25-JUN-16:12 | 32.70 |
July | 72351553.00 | 2046.88 | 15-JUL-17:12 | 33.67 |
August | 48604655.06 | 1724.99 | 26-AUG-17:12 | 30.67 |
September | 88045499.90 | 13245.80 | 22-SEP-07:03 | 0.37 |
October | 0.115830E+10 | 27453.96 | 31-OCT-07:01 | -9.0 |
November | 0.188736E+10 | 27499.12 | 30-NOV-08:13 | -7.3 |
December | 0.420231E+10 | 27787.78 | 22-DEC-08:12 | -20.0 |
Annual Sum or Average | 0.200966E+11 | |||
Minimum of Months | 48604655.06 | 1724.99 | -20.0 | |
Maximum of Months | 0.420231E+10 | 27787.78 | 33.67 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.549253E+10 | 3421.96 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.496476E+10 | 3421.96 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.549777E+10 | 3421.96 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.532115E+10 | 3421.96 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.549253E+10 | 3421.96 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.532179E+10 | 3421.96 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.549708E+10 | 3421.96 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.549285E+10 | 3421.96 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.532602E+10 | 3421.96 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.549253E+10 | 3421.96 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.530585E+10 | 3421.96 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.550226E+10 | 3421.96 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.647071E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.496476E+10 | 3421.96 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.550226E+10 | 3421.96 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.334781E+10 | 2090.38 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.302613E+10 | 2090.38 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.335104E+10 | 2090.38 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.324334E+10 | 2090.38 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.334781E+10 | 2090.38 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.324377E+10 | 2090.38 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.335056E+10 | 2090.38 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.334803E+10 | 2090.38 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.324631E+10 | 2090.38 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.334781E+10 | 2090.38 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.323401E+10 | 2090.38 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.335375E+10 | 2090.38 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.394404E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.302613E+10 | 2090.38 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.335375E+10 | 2090.38 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.243497E+10 | 1952.90 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.220556E+10 | 1952.90 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.249013E+10 | 1952.90 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.236310E+10 | 1952.90 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.246255E+10 | 1952.90 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.240447E+10 | 1952.90 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.242118E+10 | 1952.90 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.249013E+10 | 1952.90 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.236310E+10 | 1952.90 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.243497E+10 | 1952.90 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.236310E+10 | 1952.90 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.242118E+10 | 1952.90 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.288544E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.220556E+10 | 1952.90 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.249013E+10 | 1952.90 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.241466E+10 | 2078.11 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.218750E+10 | 2078.11 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.247235E+10 | 2078.11 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.234375E+10 | 2078.11 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.244351E+10 | 2078.11 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.238702E+10 | 2078.11 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.240024E+10 | 2078.11 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.247235E+10 | 2078.11 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.234375E+10 | 2078.11 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.241466E+10 | 2078.11 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.234375E+10 | 2078.11 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.240024E+10 | 2078.11 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.286238E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.218750E+10 | 2078.11 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.247235E+10 | 2078.11 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123280E+10 | 1062.01 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.111682E+10 | 1062.01 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.126230E+10 | 1062.01 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.119660E+10 | 1062.01 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.124755E+10 | 1062.01 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.121873E+10 | 1062.01 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.122542E+10 | 1062.01 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.126230E+10 | 1062.01 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.119660E+10 | 1062.01 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.123280E+10 | 1062.01 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.119660E+10 | 1062.01 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.122542E+10 | 1062.01 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.146139E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.111682E+10 | 1062.01 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.126230E+10 | 1062.01 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378230E+10 |
February | 0.305697E+10 | 0.496476E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402667E+10 |
March | 0.335708E+10 | 0.549777E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14988.76 | 0.356533E+10 |
April | 0.327081E+10 | 0.532115E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327118E+10 |
May | 0.336680E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62244206.50 | 0.153603E+10 |
June | 0.325380E+10 | 0.532179E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858872E+09 | 0.354112E+09 |
July | 0.339353E+10 | 0.549708E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913784E+09 | 0.355217E+09 |
August | 0.334857E+10 | 0.549285E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778294E+09 | 0.400355E+09 |
September | 0.327932E+10 | 0.532602E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424058E+09 | 0.761512E+09 |
October | 0.338624E+10 | 0.549253E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11031803.90 | 0.294087E+10 |
November | 0.327446E+10 | 0.530585E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348307E+10 |
December | 0.340325E+10 | 0.550226E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501037E+10 |
Annual Sum or Average | 0.397770E+11 | 0.647071E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304830E+10 | 0.294870E+11 |
Minimum of Months | 0.305697E+10 | 0.496476E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354112E+09 |
Maximum of Months | 0.340325E+10 | 0.550226E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913784E+09 | 0.501037E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198667E+10 |
February | 0.152844E+10 | 0.302613E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202467E+10 |
March | 0.167849E+10 | 0.335104E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.174641E+10 |
April | 0.163536E+10 | 0.324334E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159957E+10 |
May | 0.168335E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33847408.48 | 0.733969E+09 |
June | 0.162685E+10 | 0.324377E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463530E+09 | 0.128895E+09 |
July | 0.169671E+10 | 0.335056E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493103E+09 | 0.130666E+09 |
August | 0.167424E+10 | 0.334803E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422763E+09 | 0.152899E+09 |
September | 0.163961E+10 | 0.324631E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231184E+09 | 0.319901E+09 |
October | 0.169307E+10 | 0.334781E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.146264E+10 |
November | 0.163718E+10 | 0.323401E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179522E+10 |
December | 0.170157E+10 | 0.335375E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246503E+10 |
Annual Sum or Average | 0.198880E+11 | 0.394404E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165046E+10 | 0.145465E+11 |
Minimum of Months | 0.152844E+10 | 0.302613E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128895E+09 |
Maximum of Months | 0.170157E+10 | 0.335375E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493103E+09 | 0.246503E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201546E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207734E+10 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.179697E+10 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166081E+10 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33842655.31 | 0.770818E+09 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458368E+09 | 0.150996E+09 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484556E+09 | 0.149447E+09 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418942E+09 | 0.173222E+09 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225519E+09 | 0.348535E+09 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.151226E+10 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182286E+10 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254216E+10 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162726E+10 | 0.150209E+11 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149447E+09 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484556E+09 | 0.254216E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200923E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207077E+10 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.179119E+10 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165366E+10 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33842685.38 | 0.767155E+09 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458323E+09 | 0.151328E+09 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484447E+09 | 0.149989E+09 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418917E+09 | 0.173664E+09 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225486E+09 | 0.348570E+09 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.150846E+10 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181505E+10 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253460E+10 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162705E+10 | 0.149737E+11 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149989E+09 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484447E+09 | 0.253460E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199753E+10 |
February | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206191E+10 |
March | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.178086E+10 |
April | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163967E+10 |
May | 0.102058E+10 | 0.246255E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33842775.14 | 0.758459E+09 |
June | 0.998711E+09 | 0.240447E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458502E+09 | 0.149529E+09 |
July | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484711E+09 | 0.148223E+09 |
August | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419004E+09 | 0.171960E+09 |
September | 0.984131E+09 | 0.236310E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225569E+09 | 0.345781E+09 |
October | 0.100722E+10 | 0.243497E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.149916E+10 |
November | 0.973196E+09 | 0.236310E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180092E+10 |
December | 0.100600E+10 | 0.242118E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252384E+10 |
Annual Sum or Average | 0.119700E+11 | 0.288544E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162767E+10 | 0.148778E+11 |
Minimum of Months | 0.914877E+09 | 0.220556E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148223E+09 |
Maximum of Months | 0.103395E+10 | 0.249013E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484711E+09 | 0.252384E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.241466E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358436E+10 |
February | 0.313522E+10 | 0.218750E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375154E+10 |
March | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14786.40 | 0.323930E+10 |
April | 0.338259E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296222E+10 |
May | 0.349753E+10 | 0.244351E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60869493.03 | 0.135180E+10 |
June | 0.343071E+10 | 0.238702E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.827918E+09 | 0.286851E+09 |
July | 0.344942E+10 | 0.240024E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875965E+09 | 0.285201E+09 |
August | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755216E+09 | 0.329913E+09 |
September | 0.338259E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406839E+09 | 0.647333E+09 |
October | 0.344359E+10 | 0.241466E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10835055.43 | 0.270250E+10 |
November | 0.331698E+10 | 0.234375E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322913E+10 |
December | 0.344942E+10 | 0.240024E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460736E+10 |
Annual Sum or Average | 0.410346E+11 | 0.286238E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293766E+10 | 0.269775E+11 |
Minimum of Months | 0.313522E+10 | 0.218750E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285201E+09 |
Maximum of Months | 0.355148E+10 | 0.247235E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875965E+09 | 0.460736E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198524E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206038E+10 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.177650E+10 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162793E+10 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33843010.43 | 0.746087E+09 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459441E+09 | 0.148786E+09 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485828E+09 | 0.148183E+09 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419546E+09 | 0.173036E+09 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225866E+09 | 0.346836E+09 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.149195E+10 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178601E+10 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252438E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163056E+10 | 0.148153E+11 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148183E+09 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485828E+09 | 0.252438E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198318E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205862E+10 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.177390E+10 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162478E+10 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33843040.14 | 0.743008E+09 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459517E+09 | 0.148185E+09 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485918E+09 | 0.147635E+09 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419576E+09 | 0.172560E+09 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225894E+09 | 0.346145E+09 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.148987E+10 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178391E+10 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252250E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163078E+10 | 0.147943E+11 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147635E+09 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485918E+09 | 0.252250E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197439E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205056E+10 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.176180E+10 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160913E+10 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33843446.57 | 0.729305E+09 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459740E+09 | 0.145948E+09 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486167E+09 | 0.145539E+09 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419645E+09 | 0.170841E+09 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225958E+09 | 0.343146E+09 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.147898E+10 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177493E+10 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251271E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163139E+10 | 0.146973E+11 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145539E+09 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486167E+09 | 0.251271E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226293E+10 |
February | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251200E+10 |
March | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8433.60 | 0.224861E+10 |
April | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209488E+10 |
May | 0.174872E+10 | 0.124755E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35216366.47 | 0.978681E+09 |
June | 0.171530E+10 | 0.121873E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485564E+09 | 0.266112E+09 |
July | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513178E+09 | 0.262631E+09 |
August | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437427E+09 | 0.295970E+09 |
September | 0.169125E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234150E+09 | 0.546569E+09 |
October | 0.172174E+10 | 0.123280E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6224638.93 | 0.186814E+10 |
November | 0.165844E+10 | 0.119660E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212384E+10 |
December | 0.172466E+10 | 0.122542E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318389E+10 |
Annual Sum or Average | 0.205167E+11 | 0.146139E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171177E+10 | 0.186443E+11 |
Minimum of Months | 0.156756E+10 | 0.111682E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262631E+09 |
Maximum of Months | 0.177569E+10 | 0.126230E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513178E+09 | 0.318389E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 3421.96 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 10692.65 | 05-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 3421.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 9042.84 | 11-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 3421.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.98 | 14-MAR-13:00 | 8386.82 | 04-MAR-13:00 |
April | 4050.04 | 01-APR-12:09 | 3421.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6954.34 | 16-APR-15:00 |
May | 4050.04 | 05-MAY-12:09 | 3421.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1251.05 | 17-MAY-13:00 | 3815.30 | 26-MAY-11:05 |
June | 4050.04 | 02-JUN-12:09 | 3421.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3669.08 | 26-JUN-15:00 | 2016.29 | 02-JUN-15:00 |
July | 4050.04 | 01-JUL-12:09 | 3421.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3092.90 | 16-JUL-13:00 | 1777.06 | 19-JUL-16:00 |
August | 4050.04 | 04-AUG-12:09 | 3421.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3091.48 | 16-AUG-14:00 | 2079.26 | 29-AUG-16:00 |
September | 4050.04 | 01-SEP-12:09 | 3421.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2110.26 | 10-SEP-13:00 | 5631.28 | 21-SEP-16:00 |
October | 4050.04 | 01-OCT-12:09 | 3421.96 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 758.05 | 11-OCT-14:00 | 8111.92 | 31-OCT-15:00 |
November | 4050.04 | 03-NOV-12:09 | 3421.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 9331.47 | 29-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 3421.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 12802.01 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1777.06 | |||||
Maximum of Months | 4050.04 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3669.08 | 12802.01 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2090.38 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 2090.38 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4990.43 | 11-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2090.38 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2024.96 | 01-APR-12:09 | 2090.38 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3707.84 | 02-APR-13:00 |
May | 2024.96 | 05-MAY-12:09 | 2090.38 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2167.39 | 26-MAY-11:05 |
June | 2024.96 | 02-JUN-12:09 | 2090.38 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 26-JUN-15:00 | 1093.59 | 02-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 2090.38 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.59 | 16-JUL-13:00 | 963.84 | 19-JUL-16:00 |
August | 2024.96 | 04-AUG-12:09 | 2090.38 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.71 | 16-AUG-14:00 | 1117.40 | 29-AUG-16:00 |
September | 2024.96 | 01-SEP-12:09 | 2090.38 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.11 | 10-SEP-13:00 | 3187.99 | 21-SEP-16:00 |
October | 2024.96 | 01-OCT-12:09 | 2090.38 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2024.96 | 03-NOV-12:09 | 2090.38 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 5137.04 | 29-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2090.38 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 963.84 | |||||
Maximum of Months | 2024.96 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4990.43 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3707.84 | 02-APR-13:00 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2169.70 | 26-MAY-11:05 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 26-JUN-15:00 | 1093.59 | 02-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.59 | 16-JUL-13:00 | 1162.12 | 30-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.71 | 16-AUG-14:00 | 1117.40 | 29-AUG-16:00 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.11 | 10-SEP-13:00 | 3196.95 | 21-SEP-16:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 5137.04 | 29-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.59 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4990.43 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3707.84 | 02-APR-13:00 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2169.06 | 26-MAY-11:05 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 26-JUN-15:00 | 1093.59 | 02-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.59 | 16-JUL-13:00 | 1162.55 | 30-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.71 | 16-AUG-14:00 | 1117.40 | 29-AUG-16:00 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.11 | 10-SEP-13:00 | 3195.82 | 21-SEP-16:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 5137.04 | 29-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.59 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1952.90 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 1952.90 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4990.43 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1952.90 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2024.96 | 01-APR-12:09 | 1952.90 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3707.84 | 02-APR-13:00 |
May | 2024.96 | 06-MAY-12:09 | 1952.90 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2163.85 | 26-MAY-11:05 |
June | 2024.96 | 03-JUN-12:09 | 1952.90 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 26-JUN-15:00 | 1093.59 | 02-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 1952.90 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.59 | 16-JUL-13:00 | 1150.51 | 30-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 1952.90 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.71 | 16-AUG-14:00 | 1117.40 | 29-AUG-16:00 |
September | 2024.96 | 02-SEP-12:09 | 1952.90 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.11 | 10-SEP-13:00 | 3175.18 | 21-SEP-16:00 |
October | 2024.96 | 07-OCT-12:09 | 1952.90 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2024.96 | 04-NOV-12:09 | 1952.90 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 5137.04 | 29-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 1952.90 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.59 | |||||
Maximum of Months | 2024.96 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2078.11 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 10621.64 | 05-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 2078.11 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 8959.29 | 11-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 2078.11 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 | 14-MAR-13:00 | 8255.99 | 04-MAR-13:00 |
April | 5400.05 | 01-APR-14:09 | 2078.11 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6670.90 | 02-APR-13:00 |
May | 5400.05 | 06-MAY-14:09 | 2078.11 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1223.82 | 17-MAY-13:00 | 3669.73 | 26-MAY-11:05 |
June | 5400.05 | 03-JUN-14:09 | 2078.11 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3596.68 | 26-JUN-15:00 | 1967.49 | 02-JUN-15:00 |
July | 5400.05 | 01-JUL-14:09 | 2078.11 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3051.22 | 16-JUL-13:00 | 1859.26 | 30-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 2078.11 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3043.28 | 16-AUG-14:00 | 2012.61 | 29-AUG-16:00 |
September | 5400.05 | 02-SEP-14:09 | 2078.11 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2077.42 | 10-SEP-13:00 | 5476.28 | 21-SEP-16:00 |
October | 5400.05 | 07-OCT-14:09 | 2078.11 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 743.09 | 11-OCT-14:00 | 7915.73 | 31-OCT-15:00 |
November | 5400.05 | 04-NOV-14:09 | 2078.11 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 9225.27 | 29-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2078.11 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 12441.64 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1859.26 | |||||
Maximum of Months | 5400.05 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3596.68 | 12441.64 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4990.43 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3707.84 | 02-APR-13:00 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2125.64 | 26-MAY-11:05 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 26-JUN-15:00 | 1093.57 | 02-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.59 | 16-JUL-13:00 | 1108.45 | 30-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.71 | 16-AUG-14:00 | 1117.39 | 29-AUG-16:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.11 | 10-SEP-13:00 | 3084.18 | 21-SEP-16:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 5137.04 | 29-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.57 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4990.43 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3707.84 | 02-APR-13:00 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2115.53 | 26-MAY-11:05 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 26-JUN-15:00 | 1093.57 | 02-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.59 | 16-JUL-13:00 | 1104.08 | 30-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.71 | 16-AUG-14:00 | 1117.39 | 29-AUG-16:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.11 | 10-SEP-13:00 | 3081.27 | 21-SEP-16:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 5137.04 | 29-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.57 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4990.43 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3707.84 | 02-APR-13:00 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2071.78 | 26-MAY-11:05 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 26-JUN-15:00 | 1093.57 | 02-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.59 | 16-JUL-13:00 | 1090.28 | 30-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.71 | 16-AUG-14:00 | 1117.39 | 29-AUG-16:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.11 | 10-SEP-13:00 | 3067.00 | 21-SEP-16:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 5137.04 | 29-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1090.28 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1062.01 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5989.55 | 05-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1062.01 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5073.99 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1062.01 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 14-MAR-13:00 | 4725.37 | 04-MAR-13:00 |
April | 2699.95 | 01-APR-14:09 | 1062.01 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3989.46 | 16-APR-15:40 |
May | 2699.95 | 06-MAY-14:09 | 1062.01 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 707.70 | 17-MAY-13:00 | 2144.33 | 26-MAY-11:05 |
June | 2699.95 | 03-JUN-14:09 | 1062.01 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2072.92 | 26-JUN-15:00 | 1142.34 | 02-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1062.01 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1740.35 | 16-JUL-13:00 | 1117.78 | 30-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1062.01 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1741.94 | 16-AUG-14:00 | 1184.01 | 29-AUG-16:00 |
September | 2699.95 | 02-SEP-14:09 | 1062.01 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1189.03 | 10-SEP-13:00 | 3177.69 | 21-SEP-16:00 |
October | 2699.95 | 07-OCT-14:09 | 1062.01 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 428.25 | 11-OCT-14:00 | 4595.92 | 31-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1062.01 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 5243.24 | 29-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1062.01 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 7271.71 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1117.78 | |||||
Maximum of Months | 2699.95 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2072.92 | 7271.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6721.44 | 06-JAN-00:12 | 2025.02 | 1080.68 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.68 |
February | 5469.60 | 10-FEB-22:33 | 6075.06 | 10265.87 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.86 |
March | 5032.08 | 14-MAR-13:30 | 2700.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 |
April | 4154.25 | 10-APR-19:00 | 3375.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.07 |
May | 7360.14 | 31-MAY-16:10 | 3375.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 970.07 | 0.00 |
June | 13916.05 | 14-JUN-07:03 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 204.62 | 0.00 |
July | 19964.44 | 18-JUL-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 16.16 | 0.00 |
August | 13177.05 | 03-AUG-07:03 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.79 |
September | 14324.24 | 13-SEP-07:03 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.17 |
October | 8919.30 | 11-OCT-14:00 | 2700.03 | 3421.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 758.05 | 0.00 |
November | 4957.21 | 19-NOV-18:35 | 8100.08 | 6843.92 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.16 |
December | 7671.69 | 22-DEC-00:12 | 2025.02 | 1080.68 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4154.25 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19964.44 | 8100.08 | 10265.87 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 970.07 | 666.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3493.21 | 04-JAN-18:33 | 5062.40 | 6271.14 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 703.81 |
February | 1918.04 | 28-FEB-18:20 | 1687.47 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.87 |
March | 3451.92 | 14-MAR-13:30 | 1349.97 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.20 |
April | 2219.52 | 20-APR-17:10 | 1687.47 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.75 |
May | 19872.98 | 28-MAY-17:33 | 20249.61 | 20903.80 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.47 |
June | 19023.39 | 12-JUN-21:42 | 10124.81 | 20903.80 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.79 |
July | 19413.07 | 01-JUL-21:35 | 10124.81 | 20903.80 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.81 |
August | 19786.63 | 18-AUG-21:22 | 10124.81 | 20903.80 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 |
September | 20026.38 | 16-SEP-18:34 | 16874.68 | 20903.80 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.34 |
October | 19267.29 | 09-OCT-17:47 | 8099.84 | 8361.52 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.32 |
November | 3103.24 | 07-NOV-14:30 | 1349.97 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.60 |
December | 2521.99 | 05-DEC-18:10 | 1687.47 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1918.04 | 1349.97 | 2090.38 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.79 | |
Maximum of Months | 20026.38 | 20249.61 | 20903.80 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 703.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1798.44 | 27-JAN-18:15 | 3374.94 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.33 |
February | 1862.81 | 28-FEB-18:20 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.78 |
March | 3394.04 | 14-MAR-13:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 0.00 |
April | 2146.64 | 20-APR-17:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.75 |
May | 4046.14 | 17-MAY-13:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 0.00 |
June | 8735.22 | 27-JUN-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.72 |
July | 13838.63 | 16-JUL-07:03 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 57.26 | 0.00 |
August | 8433.89 | 20-AUG-07:03 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.34 |
September | 12335.77 | 13-SEP-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.12 |
October | 4769.73 | 11-OCT-14:00 | 1012.48 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 0.00 |
November | 2894.98 | 07-NOV-14:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 |
December | 2462.09 | 05-DEC-19:00 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1798.44 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13838.63 | 3374.94 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 491.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1749.95 | 27-JAN-18:15 | 3374.94 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.51 |
February | 1892.53 | 11-FEB-11:45 | 1349.97 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.31 |
March | 3280.82 | 14-MAR-13:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 0.00 |
April | 2048.84 | 20-APR-17:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.75 |
May | 3997.04 | 17-MAY-13:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 0.00 |
June | 9144.08 | 27-JUN-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 |
July | 14406.95 | 16-JUL-07:03 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 57.14 | 0.00 |
August | 8895.90 | 21-AUG-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 |
September | 12758.67 | 13-SEP-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.13 |
October | 4733.75 | 11-OCT-14:00 | 1012.48 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 0.00 |
November | 2717.75 | 07-NOV-14:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 |
December | 2360.97 | 05-DEC-18:20 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1749.95 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14406.95 | 3374.94 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 662.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1638.39 | 26-JAN-18:15 | 3374.94 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.98 |
February | 1723.22 | 28-FEB-18:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.53 |
March | 2975.06 | 14-MAR-13:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 0.00 |
April | 1863.06 | 14-APR-18:00 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.01 |
May | 3794.78 | 17-MAY-13:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 0.00 |
June | 8242.87 | 27-JUN-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.69 |
July | 13201.20 | 16-JUL-07:03 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 57.43 | 0.00 |
August | 8153.58 | 21-AUG-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.28 |
September | 11720.24 | 11-SEP-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 |
October | 4567.86 | 11-OCT-14:00 | 1012.48 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 0.00 |
November | 2393.87 | 07-NOV-14:00 | 1349.97 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 |
December | 1995.70 | 05-DEC-18:10 | 1687.47 | 1952.90 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1638.39 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13201.20 | 3374.94 | 3905.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 516.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5305.78 | 31-JAN-18:23 | 6885.06 | 6234.32 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 871.71 |
February | 4007.22 | 15-FEB-13:25 | 9585.09 | 4156.22 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3795.06 |
March | 5094.32 | 14-MAR-13:00 | 4792.55 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 | 0.00 |
April | 3110.89 | 29-APR-11:00 | 3915.04 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.18 |
May | 6762.94 | 17-MAY-14:10 | 4657.54 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1145.96 | 0.00 |
June | 25831.07 | 25-JUN-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 154.30 | 0.00 |
July | 25960.72 | 17-JUL-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 57.27 | 0.00 |
August | 16747.97 | 20-AUG-08:63 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 |
September | 16383.04 | 11-SEP-07:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.32 |
October | 8436.43 | 11-OCT-14:10 | 4657.54 | 2078.11 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 704.33 | 0.00 |
November | 6125.78 | 10-NOV-17:03 | 14377.64 | 6234.32 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5513.18 |
December | 5104.34 | 05-DEC-13:53 | 14377.64 | 6234.32 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4656.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3110.89 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25960.72 | 14377.64 | 6234.32 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1145.96 | 5513.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2203.12 | 12-JAN-18:15 | 2294.96 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.70 |
February | 1448.17 | 16-FEB-19:25 | 1754.97 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.76 |
March | 2598.54 | 14-MAR-13:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 0.00 |
April | 1894.65 | 22-APR-15:25 | 4994.90 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2614.32 |
May | 3491.10 | 17-MAY-14:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 0.00 |
June | 12557.55 | 25-JUN-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 84.61 | 0.00 |
July | 13281.66 | 16-JUL-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.92 | 0.00 |
August | 7777.46 | 20-AUG-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.30 |
September | 7862.86 | 11-SEP-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.88 |
October | 4368.40 | 11-OCT-14:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 391.69 | 0.00 |
November | 2028.87 | 07-NOV-14:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 |
December | 2796.93 | 18-DEC-18:43 | 3442.43 | 3186.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 771.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1448.17 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13281.66 | 4994.90 | 3186.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 2614.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2075.40 | 12-JAN-11:05 | 2902.44 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.84 |
February | 1772.65 | 02-FEB-11:25 | 2902.44 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.32 |
March | 2511.26 | 14-MAR-13:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 0.00 |
April | 1511.61 | 22-APR-11:00 | 1957.46 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.47 |
May | 3419.60 | 17-MAY-14:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 0.00 |
June | 12040.02 | 25-JUN-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 84.71 | 0.00 |
July | 13171.29 | 16-JUL-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.65 | 0.00 |
August | 7501.75 | 20-AUG-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 |
September | 7649.75 | 11-SEP-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.82 |
October | 4310.83 | 11-OCT-14:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 391.69 | 0.00 |
November | 1981.84 | 07-NOV-14:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 |
December | 1527.85 | 16-DEC-11:40 | 1957.46 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1511.61 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13171.29 | 2902.44 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 520.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1264.17 | 21-JAN-17:00 | 2497.45 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.96 |
February | 972.56 | 22-FEB-12:00 | 1451.22 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.53 |
March | 2208.40 | 14-MAR-13:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 0.00 |
April | 1160.84 | 22-APR-11:00 | 1957.46 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.47 |
May | 3230.00 | 17-MAY-14:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 0.00 |
June | 10074.26 | 25-JUN-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 85.02 | 0.00 |
July | 13017.76 | 16-JUL-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.56 | 0.00 |
August | 6548.55 | 20-AUG-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 |
September | 6809.04 | 11-SEP-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.54 |
October | 4160.57 | 11-OCT-14:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 391.69 | 0.00 |
November | 1784.14 | 07-NOV-14:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 |
December | 1894.66 | 06-DEC-11:35 | 2902.44 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 972.56 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13017.76 | 2902.44 | 2124.01 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 2002.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 950.15 | 21-JAN-16:40 | 2497.45 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1828.75 |
February | 700.80 | 27-FEB-19:40 | 877.48 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.70 |
March | 1896.32 | 14-MAR-13:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 0.00 |
April | 904.01 | 20-APR-13:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.99 |
May | 3113.33 | 17-MAY-14:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 664.31 | 0.00 |
June | 8706.75 | 25-JUN-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 107.33 | 0.00 |
July | 13581.37 | 16-JUL-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.08 | 0.00 |
August | 6749.51 | 16-AUG-14:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1712.66 | 0.00 |
September | 6305.33 | 09-SEP-13:10 | 2598.70 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1148.75 | 0.00 |
October | 4205.80 | 11-OCT-14:10 | 2328.71 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 406.42 | 0.00 |
November | 1637.08 | 07-NOV-14:00 | 2396.20 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.79 |
December | 944.89 | 16-DEC-15:00 | 2598.70 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1944.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 700.80 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13581.37 | 2598.70 | 1062.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1712.66 | 1944.72 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.607235E+11 | 51070.21 | 07-JAN-17:10 | 0.431085E+11 | 157314.82 | 05-JAN-17:00 |
February | 0.547032E+11 | 48851.63 | 01-FEB-17:49 | 0.475500E+11 | 150150.30 | 06-FEB-08:09 |
March | 0.609513E+11 | 51497.28 | 13-MAR-13:00 | 0.315526E+11 | 126891.89 | 19-MAR-08:09 |
April | 0.573586E+11 | 48314.06 | 13-APR-18:49 | 0.218563E+11 | 118895.27 | 17-APR-07:10 |
May | 0.617741E+11 | 57138.86 | 17-MAY-13:50 | 0.104236E+10 | 57047.52 | 02-MAY-07:10 |
June | 0.733443E+11 | 75845.60 | 26-JUN-14:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.752015E+11 | 69055.79 | 18-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.755758E+11 | 73216.10 | 16-AUG-14:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.682271E+11 | 65823.07 | 09-SEP-12:30 | 37167881.71 | 7006.52 | 21-SEP-16:00 |
October | 0.609629E+11 | 57935.73 | 11-OCT-14:09 | 0.151884E+11 | 107014.69 | 31-OCT-16:10 |
November | 0.585754E+11 | 49062.46 | 30-NOV-19:30 | 0.260927E+11 | 124805.97 | 29-NOV-17:00 |
December | 0.607821E+11 | 52649.63 | 26-DEC-18:49 | 0.580107E+11 | 185265.24 | 21-DEC-17:00 |
Annual Sum or Average | 0.768180E+12 | 0.244439E+12 | ||||
Minimum of Months | 0.547032E+11 | 48314.06 | 0.00 | 0.00 | ||
Maximum of Months | 0.755758E+11 | 75845.60 | 0.580107E+11 | 185265.24 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.319257E+10 | 7132.58 | 31-JAN-12:30 | 0.00 | 0.00 |
February | 0.403225E+10 | 8499.94 | 24-FEB-12:30 | 0.00 | 0.00 |
March | 0.543777E+10 | 10759.11 | 28-MAR-12:09 | 0.00 | 0.00 |
April | 0.570801E+10 | 11248.97 | 26-APR-12:30 | 0.00 | 0.00 |
May | 0.723114E+10 | 10338.61 | 27-MAY-11:30 | 0.00 | 0.00 |
June | 0.829782E+10 | 10854.39 | 16-JUN-11:00 | 0.00 | 0.00 |
July | 0.751721E+10 | 11002.22 | 01-JUL-11:50 | 0.00 | 0.00 |
August | 0.740303E+10 | 10081.88 | 04-AUG-11:50 | 0.00 | 0.00 |
September | 0.583252E+10 | 9280.19 | 05-SEP-11:00 | 0.00 | 0.00 |
October | 0.453591E+10 | 8905.13 | 01-OCT-11:30 | 0.00 | 0.00 |
November | 0.337877E+10 | 7625.28 | 01-NOV-11:30 | 0.00 | 0.00 |
December | 0.274873E+10 | 5908.79 | 22-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.653157E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.274873E+10 | 5908.79 | 0.00 | 0.00 | |
Maximum of Months | 0.829782E+10 | 11248.97 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.234911E+11 | 0.453149E+10 | 0.108325E+11 | 0.00 | 0.162107E+11 | 0.00 | 0.00 | 1041211.44 | 0.00 | 0.00 | 0.00 | 0.565671E+10 | 0.00 |
February | 0.212624E+11 | 0.371859E+10 | 0.980803E+10 | 0.00 | 0.147737E+11 | 0.00 | 0.00 | 146732.75 | 0.00 | 0.00 | 0.00 | 0.514041E+10 | 0.00 |
March | 0.238408E+11 | 0.358861E+10 | 0.110075E+11 | 0.00 | 0.165420E+11 | 0.00 | 0.00 | 0.276210E+09 | 0.00 | 0.00 | 0.00 | 0.569622E+10 | 0.00 |
April | 0.227839E+11 | 0.293746E+10 | 0.105079E+11 | 0.00 | 0.157017E+11 | 0.00 | 0.00 | 18835885.40 | 0.00 | 0.00 | 0.00 | 0.540875E+10 | 0.00 |
May | 0.236617E+11 | 0.262904E+10 | 0.109147E+11 | 0.00 | 0.164692E+11 | 0.00 | 0.00 | 0.262205E+10 | 0.00 | 0.00 | 0.00 | 0.547734E+10 | 0.00 |
June | 0.230409E+11 | 0.235628E+10 | 0.106386E+11 | 0.00 | 0.159234E+11 | 0.00 | 0.00 | 0.161694E+11 | 0.00 | 0.00 | 0.00 | 0.521573E+10 | 0.00 |
July | 0.234131E+11 | 0.248971E+10 | 0.107945E+11 | 0.00 | 0.160962E+11 | 0.00 | 0.00 | 0.171234E+11 | 0.00 | 0.00 | 0.00 | 0.528457E+10 | 0.00 |
August | 0.238328E+11 | 0.282976E+10 | 0.110006E+11 | 0.00 | 0.164241E+11 | 0.00 | 0.00 | 0.161822E+11 | 0.00 | 0.00 | 0.00 | 0.530628E+10 | 0.00 |
September | 0.227918E+11 | 0.323964E+10 | 0.105148E+11 | 0.00 | 0.157555E+11 | 0.00 | 0.00 | 0.107882E+11 | 0.00 | 0.00 | 0.00 | 0.513728E+10 | 0.00 |
October | 0.234911E+11 | 0.389987E+10 | 0.108325E+11 | 0.00 | 0.163239E+11 | 0.00 | 0.00 | 0.102338E+10 | 0.00 | 0.00 | 0.00 | 0.539213E+10 | 0.00 |
November | 0.227593E+11 | 0.424614E+10 | 0.104978E+11 | 0.00 | 0.156734E+11 | 0.00 | 0.00 | 73949810.03 | 0.00 | 0.00 | 0.00 | 0.532479E+10 | 0.00 |
December | 0.234215E+11 | 0.466327E+10 | 0.108050E+11 | 0.00 | 0.162889E+11 | 0.00 | 0.00 | 5212958.27 | 0.00 | 0.00 | 0.00 | 0.559818E+10 | 0.00 |
Annual Sum or Average | 0.277790E+12 | 0.411299E+11 | 0.128154E+12 | 0.00 | 0.192183E+12 | 0.00 | 0.00 | 0.642840E+11 | 0.00 | 0.00 | 0.00 | 0.646384E+11 | 0.00 |
Minimum of Months | 0.212624E+11 | 0.235628E+10 | 0.980803E+10 | 0.00 | 0.147737E+11 | 0.00 | 0.00 | 146732.75 | 0.00 | 0.00 | 0.00 | 0.513728E+10 | 0.00 |
Maximum of Months | 0.238408E+11 | 0.466327E+10 | 0.110075E+11 | 0.00 | 0.165420E+11 | 0.00 | 0.00 | 0.171234E+11 | 0.00 | 0.00 | 0.00 | 0.569622E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.431085E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.475500E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.315526E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.218563E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.104236E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 37167881.71 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.151884E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.260927E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.580107E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.244439E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.580107E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17697.17 | 01-JAN-11:09 | 3786.68 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 12331.11 | 05-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 17697.17 | 01-FEB-10:09 | 3786.68 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 12381.38 | 06-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 17697.17 | 01-MAR-10:09 | 3786.68 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 12114.44 | 19-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 17697.17 | 01-APR-09:09 | 3786.68 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 12145.97 | 17-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 17697.17 | 01-MAY-09:09 | 3786.68 | 01-MAY-18:49 | 8059.50 | 01-MAY-09:09 | 0.00 | 11684.13 | 02-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 17697.17 | 01-JUN-09:09 | 3786.68 | 01-JUN-19:19 | 8059.50 | 01-JUN-09:09 | 0.00 | 12075.15 | 26-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 17697.17 | 01-JUL-09:09 | 3786.68 | 01-JUL-19:30 | 8059.50 | 01-JUL-09:09 | 0.00 | 11613.34 | 17-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 17697.17 | 01-AUG-09:09 | 3786.68 | 01-AUG-19:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 11824.72 | 16-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 17697.17 | 01-SEP-09:09 | 3786.68 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 11356.90 | 09-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 17697.17 | 01-OCT-10:09 | 3786.68 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 11994.72 | 31-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 17697.17 | 01-NOV-09:09 | 3786.68 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 12152.03 | 30-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 17697.17 | 01-DEC-10:09 | 3786.68 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 12608.69 | 23-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 17697.17 | 3786.68 | 8059.50 | 0.00 | 11356.90 | 0.00 | 0.00 | |||||
Maximum of Months | 17697.17 | 3786.68 | 8059.50 | 0.00 | 12608.69 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 274.64 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 | 12970.36 | 07-JAN-13:09 | 0.00 | 01-JAN-00:10 |
February | 140.27 | 26-FEB-18:10 | 0.00 | 0.00 | 0.00 | 9739.43 | 14-FEB-13:00 | 0.00 | 01-FEB-00:10 |
March | 9858.09 | 14-MAR-12:00 | 0.00 | 0.00 | 0.00 | 9735.83 | 20-MAR-12:00 | 0.00 | 01-MAR-00:10 |
April | 3205.40 | 20-APR-12:00 | 0.00 | 0.00 | 0.00 | 9729.09 | 03-APR-13:09 | 0.00 | 01-APR-00:10 |
May | 15059.95 | 17-MAY-12:00 | 0.00 | 0.00 | 0.00 | 9717.36 | 04-MAY-13:39 | 0.00 | 01-MAY-00:10 |
June | 33380.97 | 26-JUN-14:00 | 0.00 | 0.00 | 0.00 | 7582.11 | 19-JUN-12:50 | 0.00 | 01-JUN-00:10 |
July | 27827.37 | 17-JUL-12:00 | 0.00 | 0.00 | 0.00 | 7578.12 | 13-JUL-12:30 | 0.00 | 01-JUL-00:10 |
August | 29916.50 | 16-AUG-16:10 | 0.00 | 0.00 | 0.00 | 7576.18 | 30-AUG-12:39 | 0.00 | 01-AUG-00:10 |
September | 24024.33 | 09-SEP-12:00 | 0.00 | 0.00 | 0.00 | 7579.78 | 27-SEP-12:00 | 0.00 | 01-SEP-00:10 |
October | 15378.79 | 11-OCT-13:00 | 0.00 | 0.00 | 0.00 | 9643.57 | 22-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 5204.37 | 07-NOV-13:00 | 0.00 | 0.00 | 0.00 | 10086.02 | 30-NOV-12:09 | 0.00 | 01-NOV-00:10 |
December | 1904.13 | 02-DEC-14:00 | 0.00 | 0.00 | 0.00 | 12434.07 | 05-DEC-13:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 140.27 | 0.00 | 0.00 | 0.00 | 7576.18 | 0.00 | |||
Maximum of Months | 33380.97 | 0.00 | 0.00 | 0.00 | 12970.36 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 51070.21 | 07-JAN-17:10 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 11835.59 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 48851.63 | 01-FEB-17:49 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 11846.01 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 51497.28 | 13-MAR-13:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 11214.76 | 0.00 | 0.00 | 6925.13 | 0.00 |
April | 48314.06 | 13-APR-18:49 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 11214.76 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57138.86 | 17-MAY-13:50 | 17697.17 | 8059.50 | 0.00 | 0.00 | 11214.76 | 0.00 | 0.00 | 14704.92 | 0.00 |
June | 75845.60 | 26-JUN-14:09 | 17697.17 | 8059.50 | 0.00 | 0.00 | 11825.62 | 0.00 | 0.00 | 30701.57 | 0.00 |
July | 69055.79 | 18-JUL-12:00 | 17697.17 | 8059.50 | 0.00 | 0.00 | 11483.56 | 0.00 | 0.00 | 26360.26 | 0.00 |
August | 73216.10 | 16-AUG-14:50 | 17697.17 | 8059.50 | 0.00 | 0.00 | 11678.74 | 0.00 | 0.00 | 28223.04 | 0.00 |
September | 65823.07 | 09-SEP-12:30 | 17697.17 | 8059.50 | 0.00 | 0.00 | 11291.95 | 0.00 | 0.00 | 23410.28 | 0.00 |
October | 57935.73 | 11-OCT-14:09 | 17697.17 | 8059.50 | 0.00 | 0.00 | 11214.76 | 0.00 | 0.00 | 15357.52 | 0.00 |
November | 49062.46 | 30-NOV-19:30 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 11514.12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 52649.63 | 26-DEC-18:49 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 11386.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 48314.06 | 17697.17 | 8059.50 | 0.00 | 0.00 | 11214.76 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75845.60 | 17697.17 | 8059.50 | 3786.68 | 0.00 | 11846.01 | 0.00 | 0.00 | 30701.57 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 157314.82 | 05-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 150150.30 | 06-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 126891.89 | 19-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 118895.27 | 17-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 57047.52 | 02-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 7006.52 | 21-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 107014.69 | 31-OCT-16:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 124805.97 | 29-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 185265.24 | 21-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 185265.24 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
February | 1.83 | 20.41 | 0.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
March | 0.67 | 20.45 | 0.17 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
April | 0.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
May | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
November | 0.50 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
December | 1.67 | 20.29 | 0.50 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
Annual Sum or Average | 6.83 | 20.41 | 1.17 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.51 | 0.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
February | 0.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 1.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
April | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Annual Sum or Average | 2.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Annual Sum or Average | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Annual Sum or Average | 0.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Annual Sum or Average | 0.67 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
March | 0.17 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
Annual Sum or Average | 2.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
March | 0.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 2.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
March | 0.17 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
Annual Sum or Average | 2.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 1.17 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
March | 0.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
April | 0.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
Annual Sum or Average | 3.50 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 19.70 | 0.00 | 19.70 | 0.00 | 19.70 | 0.00 | 19.70 |
February | 4.33 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
March | 3.50 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
April | 1.50 | 19.68 | 0.00 | 19.68 | 0.00 | 19.68 | 0.00 | 19.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
November | 1.17 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
December | 7.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
Annual Sum or Average | 21.00 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.27 | 200.67 | 21.20 | 200.67 | 21.17 |
February | 448.00 | 21.21 | 250.67 | 21.16 | 250.67 | 21.13 |
March | 497.00 | 21.76 | 192.00 | 21.56 | 192.00 | 21.46 |
April | 479.00 | 21.82 | 106.00 | 21.69 | 106.00 | 21.59 |
May | 376.33 | 23.19 | 12.00 | 23.13 | 10.83 | 23.08 |
June | 51.67 | 23.88 | 156.17 | 23.89 | 13.67 | 23.89 |
July | 102.33 | 23.89 | 214.67 | 23.89 | 72.83 | 23.89 |
August | 47.67 | 23.89 | 216.67 | 23.89 | 21.00 | 23.89 |
September | 132.67 | 23.52 | 69.33 | 23.65 | 0.00 | 23.65 |
October | 435.50 | 22.52 | 48.67 | 22.38 | 48.67 | 22.27 |
November | 479.67 | 21.62 | 88.67 | 21.53 | 88.67 | 21.47 |
December | 496.00 | 21.31 | 281.50 | 21.21 | 281.50 | 21.17 |
Annual Sum or Average | 4041.83 | 21.95 | 1837.00 | 21.99 | 1286.50 | 21.87 |
Minimum of Months | 47.67 | 21.21 | 12.00 | 21.16 | 0.00 | 21.13 |
Maximum of Months | 497.00 | 23.89 | 281.50 | 23.89 | 281.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.94 | 68.17 | 21.84 | 68.17 | 21.76 |
February | 448.00 | 21.73 | 150.50 | 21.58 | 150.50 | 21.48 |
March | 497.00 | 22.33 | 41.33 | 22.23 | 41.33 | 22.15 |
April | 473.67 | 22.59 | 21.17 | 22.53 | 21.17 | 22.47 |
May | 265.33 | 23.64 | 4.33 | 23.64 | 0.00 | 23.64 |
June | 61.33 | 23.52 | 147.67 | 23.77 | 12.50 | 23.78 |
July | 103.33 | 23.70 | 200.33 | 23.81 | 64.00 | 23.82 |
August | 62.17 | 23.51 | 195.00 | 23.79 | 18.67 | 23.80 |
September | 133.50 | 23.68 | 52.67 | 23.74 | 0.00 | 23.74 |
October | 411.00 | 23.09 | 27.17 | 22.97 | 27.17 | 22.86 |
November | 469.33 | 22.41 | 35.17 | 22.32 | 35.17 | 22.24 |
December | 496.00 | 21.85 | 147.50 | 21.67 | 147.50 | 21.57 |
Annual Sum or Average | 3916.67 | 22.48 | 1091.00 | 22.51 | 586.17 | 22.41 |
Minimum of Months | 61.33 | 21.73 | 4.33 | 21.58 | 0.00 | 21.48 |
Maximum of Months | 497.00 | 23.70 | 200.33 | 23.81 | 150.50 | 23.82 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.73 | 87.33 | 21.61 | 87.33 | 21.53 |
February | 336.00 | 21.51 | 149.67 | 21.39 | 149.67 | 21.32 |
March | 377.50 | 22.16 | 64.50 | 22.00 | 64.50 | 21.89 |
April | 354.33 | 22.38 | 48.00 | 22.23 | 48.00 | 22.11 |
May | 194.33 | 23.56 | 12.33 | 23.60 | 2.17 | 23.58 |
June | 25.50 | 23.95 | 145.67 | 24.24 | 8.83 | 24.23 |
July | 54.83 | 24.06 | 181.17 | 24.19 | 46.67 | 24.18 |
August | 21.83 | 24.03 | 182.83 | 24.18 | 13.17 | 24.18 |
September | 69.17 | 23.71 | 63.67 | 24.08 | 0.00 | 24.08 |
October | 293.83 | 22.88 | 29.17 | 22.72 | 28.67 | 22.59 |
November | 354.00 | 22.12 | 50.50 | 21.99 | 50.50 | 21.90 |
December | 369.00 | 21.64 | 152.67 | 21.48 | 152.67 | 21.40 |
Annual Sum or Average | 2821.33 | 22.26 | 1167.50 | 22.39 | 652.17 | 22.25 |
Minimum of Months | 21.83 | 21.51 | 12.33 | 21.39 | 0.00 | 21.32 |
Maximum of Months | 377.50 | 24.06 | 182.83 | 24.24 | 152.67 | 24.23 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.68 | 101.50 | 21.56 | 101.50 | 21.48 |
February | 336.00 | 21.47 | 158.50 | 21.35 | 158.50 | 21.29 |
March | 377.67 | 22.13 | 76.83 | 21.96 | 76.83 | 21.84 |
April | 357.83 | 22.35 | 51.67 | 22.19 | 51.67 | 22.07 |
May | 202.00 | 23.54 | 11.50 | 23.57 | 2.67 | 23.54 |
June | 24.50 | 23.95 | 145.83 | 24.24 | 8.83 | 24.23 |
July | 54.67 | 24.06 | 182.17 | 24.19 | 46.67 | 24.18 |
August | 21.33 | 24.03 | 184.50 | 24.18 | 13.17 | 24.18 |
September | 71.17 | 23.71 | 65.00 | 24.07 | 0.00 | 24.07 |
October | 299.83 | 22.87 | 30.17 | 22.72 | 29.67 | 22.58 |
November | 356.00 | 22.07 | 52.50 | 21.95 | 52.50 | 21.85 |
December | 369.00 | 21.60 | 165.17 | 21.45 | 165.17 | 21.37 |
Annual Sum or Average | 2841.00 | 22.23 | 1225.33 | 22.35 | 707.17 | 22.21 |
Minimum of Months | 21.33 | 21.47 | 11.50 | 21.35 | 0.00 | 21.29 |
Maximum of Months | 377.67 | 24.06 | 184.50 | 24.24 | 165.17 | 24.23 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.58 | 121.33 | 21.47 | 121.33 | 21.40 |
February | 336.00 | 21.40 | 171.83 | 21.30 | 171.83 | 21.25 |
March | 378.67 | 22.07 | 93.67 | 21.88 | 93.67 | 21.75 |
April | 360.00 | 22.25 | 59.50 | 22.08 | 59.50 | 21.96 |
May | 232.67 | 23.51 | 10.67 | 23.52 | 4.00 | 23.48 |
June | 27.50 | 23.94 | 140.83 | 24.23 | 9.17 | 24.22 |
July | 56.17 | 24.05 | 178.83 | 24.19 | 47.17 | 24.17 |
August | 22.83 | 24.02 | 179.33 | 24.18 | 13.50 | 24.17 |
September | 83.00 | 23.70 | 60.17 | 24.03 | 0.00 | 24.03 |
October | 317.50 | 22.84 | 32.00 | 22.69 | 31.83 | 22.56 |
November | 357.67 | 21.97 | 58.17 | 21.85 | 58.17 | 21.76 |
December | 369.00 | 21.54 | 183.83 | 21.40 | 183.83 | 21.32 |
Annual Sum or Average | 2912.00 | 22.19 | 1290.17 | 22.28 | 794.00 | 22.14 |
Minimum of Months | 22.83 | 21.40 | 10.67 | 21.30 | 0.00 | 21.25 |
Maximum of Months | 378.67 | 24.05 | 183.83 | 24.23 | 183.83 | 24.22 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.31 | 148.50 | 21.25 | 148.50 | 21.21 |
February | 308.00 | 21.24 | 179.83 | 21.19 | 179.83 | 21.17 |
March | 348.00 | 21.77 | 137.83 | 21.58 | 137.83 | 21.48 |
April | 330.00 | 21.82 | 77.83 | 21.69 | 77.83 | 21.59 |
May | 280.33 | 23.21 | 9.83 | 23.14 | 9.83 | 23.07 |
June | 28.50 | 23.89 | 108.33 | 23.98 | 8.33 | 23.98 |
July | 54.67 | 23.93 | 154.33 | 23.99 | 46.00 | 23.98 |
August | 25.67 | 23.93 | 142.00 | 23.97 | 11.67 | 23.97 |
September | 101.33 | 23.56 | 41.67 | 23.74 | 0.00 | 23.74 |
October | 311.33 | 22.50 | 40.17 | 22.34 | 40.17 | 22.21 |
November | 330.00 | 21.60 | 76.33 | 21.51 | 76.33 | 21.45 |
December | 338.00 | 21.33 | 214.67 | 21.25 | 214.67 | 21.21 |
Annual Sum or Average | 2795.83 | 21.96 | 1331.33 | 22.00 | 951.00 | 21.87 |
Minimum of Months | 25.67 | 21.24 | 9.83 | 21.19 | 0.00 | 21.17 |
Maximum of Months | 348.00 | 23.93 | 214.67 | 23.99 | 214.67 | 23.98 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.42 | 146.67 | 21.33 | 146.67 | 21.28 |
February | 308.00 | 21.30 | 181.00 | 21.23 | 181.00 | 21.20 |
March | 348.00 | 21.92 | 135.33 | 21.69 | 135.33 | 21.57 |
April | 330.00 | 22.04 | 77.67 | 21.87 | 77.67 | 21.74 |
May | 291.00 | 23.46 | 9.83 | 23.39 | 9.17 | 23.33 |
June | 40.83 | 23.89 | 98.33 | 24.00 | 10.50 | 23.99 |
July | 58.83 | 23.94 | 144.17 | 24.02 | 45.83 | 24.00 |
August | 36.83 | 23.93 | 123.67 | 23.99 | 12.33 | 23.99 |
September | 115.33 | 23.69 | 31.17 | 23.84 | 0.00 | 23.84 |
October | 322.67 | 22.78 | 39.17 | 22.60 | 39.17 | 22.45 |
November | 330.00 | 21.77 | 77.17 | 21.65 | 77.17 | 21.56 |
December | 338.00 | 21.43 | 211.00 | 21.30 | 211.00 | 21.25 |
Annual Sum or Average | 2859.50 | 22.15 | 1275.17 | 22.12 | 945.83 | 21.97 |
Minimum of Months | 36.83 | 21.30 | 9.83 | 21.23 | 0.00 | 21.20 |
Maximum of Months | 348.00 | 23.94 | 211.00 | 24.02 | 211.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.41 | 154.83 | 21.31 | 154.83 | 21.27 |
February | 308.00 | 21.29 | 184.33 | 21.22 | 184.33 | 21.19 |
March | 348.00 | 21.90 | 141.17 | 21.67 | 141.17 | 21.55 |
April | 330.00 | 22.02 | 80.67 | 21.84 | 80.67 | 21.72 |
May | 300.17 | 23.45 | 11.33 | 23.38 | 10.67 | 23.30 |
June | 42.50 | 23.89 | 96.83 | 24.00 | 10.50 | 23.99 |
July | 60.50 | 23.93 | 142.50 | 24.01 | 45.83 | 24.00 |
August | 38.83 | 23.93 | 119.00 | 23.99 | 12.33 | 23.99 |
September | 117.67 | 23.69 | 29.83 | 23.84 | 0.00 | 23.84 |
October | 325.33 | 22.77 | 40.83 | 22.59 | 40.83 | 22.44 |
November | 330.00 | 21.76 | 82.00 | 21.63 | 82.00 | 21.54 |
December | 338.00 | 21.42 | 216.33 | 21.30 | 216.33 | 21.25 |
Annual Sum or Average | 2879.00 | 22.15 | 1299.67 | 22.10 | 979.50 | 21.95 |
Minimum of Months | 38.83 | 21.29 | 11.33 | 21.22 | 0.00 | 21.19 |
Maximum of Months | 348.00 | 23.93 | 216.33 | 24.01 | 216.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.35 | 179.00 | 21.27 | 179.00 | 21.23 |
February | 308.00 | 21.26 | 194.00 | 21.20 | 194.00 | 21.18 |
March | 348.00 | 21.83 | 166.67 | 21.60 | 166.67 | 21.48 |
April | 330.00 | 21.92 | 93.50 | 21.75 | 93.50 | 21.63 |
May | 322.00 | 23.38 | 18.83 | 23.26 | 18.83 | 23.15 |
June | 49.17 | 23.89 | 94.00 | 23.99 | 11.00 | 23.98 |
July | 63.67 | 23.93 | 140.00 | 24.01 | 46.00 | 24.00 |
August | 43.00 | 23.92 | 115.83 | 23.99 | 12.33 | 23.99 |
September | 121.67 | 23.67 | 28.50 | 23.81 | 0.00 | 23.81 |
October | 327.83 | 22.69 | 43.67 | 22.51 | 43.67 | 22.36 |
November | 330.00 | 21.69 | 99.00 | 21.56 | 99.00 | 21.47 |
December | 338.00 | 21.38 | 227.67 | 21.27 | 227.67 | 21.23 |
Annual Sum or Average | 2921.33 | 22.11 | 1400.67 | 22.05 | 1091.67 | 21.89 |
Minimum of Months | 43.00 | 21.26 | 18.83 | 21.20 | 0.00 | 21.18 |
Maximum of Months | 348.00 | 23.93 | 227.67 | 24.01 | 227.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.27 | 241.17 | 21.21 | 241.17 | 21.18 |
February | 308.00 | 21.21 | 246.00 | 21.17 | 246.00 | 21.15 |
March | 348.00 | 21.71 | 216.33 | 21.48 | 216.33 | 21.38 |
April | 330.00 | 21.77 | 151.17 | 21.56 | 151.17 | 21.46 |
May | 336.00 | 23.16 | 29.17 | 23.00 | 29.17 | 22.86 |
June | 56.33 | 23.89 | 87.83 | 23.99 | 11.33 | 23.98 |
July | 67.17 | 23.92 | 139.00 | 24.01 | 46.67 | 24.00 |
August | 43.17 | 23.92 | 124.17 | 23.98 | 12.33 | 23.98 |
September | 121.00 | 23.61 | 35.17 | 23.76 | 0.33 | 23.76 |
October | 329.67 | 22.54 | 66.33 | 22.30 | 66.33 | 22.13 |
November | 330.00 | 21.61 | 130.67 | 21.47 | 130.67 | 21.39 |
December | 338.00 | 21.32 | 264.50 | 21.23 | 264.50 | 21.19 |
Annual Sum or Average | 2947.33 | 22.02 | 1731.50 | 21.93 | 1416.00 | 21.77 |
Minimum of Months | 43.17 | 21.21 | 29.17 | 21.17 | 0.33 | 21.15 |
Maximum of Months | 348.00 | 23.92 | 264.50 | 24.01 | 264.50 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.26669 | 21.85354 | -0.5159 | 11.14482 |
February | 448.00000 | 21.21489 | 19.20993 | -0.5606 | 12.15212 |
March | 497.00000 | 21.75618 | 19.21821 | -0.4109 | 10.05979 |
April | 479.00000 | 21.81594 | 24.27636 | -0.3543 | 8.96595 |
May | 496.00000 | 23.35663 | 27.74403 | -0.8861 | 23.20473 |
June | 481.00000 | 23.88907 | 32.67765 | -0.5460 | 11.38072 |
July | 495.00000 | 23.88895 | 35.89033 | -0.5206 | 10.83908 |
August | 497.00000 | 23.88970 | 33.60917 | -0.5242 | 10.87917 |
September | 479.00000 | 23.78724 | 25.44043 | -0.6345 | 14.13182 |
October | 496.00000 | 22.69026 | 21.27299 | -0.1001 | 7.24428 |
November | 480.00000 | 21.61978 | 23.12776 | -0.3755 | 9.13430 |
December | 496.00000 | 21.30806 | 15.41377 | -0.5561 | 12.33549 |
Annual Sum or Average | 5840.00000 | 22.54858 | 25.00987 | -0.4984 | 11.79581 |
Minimum of Months | 448.00000 | 21.21489 | 15.41377 | -0.8861 | 7.24428 |
Maximum of Months | 497.00000 | 23.88970 | 35.89033 | -0.1001 | 23.20473 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.94344 | 24.21780 | -0.3221 | 8.37041 |
February | 448.00000 | 21.73490 | 21.18707 | -0.3995 | 9.48271 |
March | 497.00000 | 22.32628 | 20.40035 | -0.2464 | 7.83902 |
April | 479.00000 | 22.60720 | 24.89454 | -0.1507 | 7.00412 |
May | 496.00000 | 23.75256 | 26.70071 | -0.7354 | 17.18938 |
June | 481.00000 | 23.82139 | 32.75754 | -0.5565 | 11.68944 |
July | 495.00000 | 23.82154 | 36.01499 | -0.5300 | 11.11615 |
August | 497.00000 | 23.80967 | 33.55979 | -0.5441 | 11.40829 |
September | 479.00000 | 23.81812 | 25.25580 | -0.6216 | 13.40148 |
October | 496.00000 | 23.22817 | 21.06667 | 0.03005 | 6.49213 |
November | 480.00000 | 22.44350 | 24.62593 | -0.1717 | 7.07790 |
December | 496.00000 | 21.84575 | 17.35349 | -0.3981 | 9.66599 |
Annual Sum or Average | 5840.00000 | 22.93648 | 25.69319 | -0.3872 | 10.06901 |
Minimum of Months | 448.00000 | 21.73490 | 17.35349 | -0.7354 | 6.49213 |
Maximum of Months | 497.00000 | 23.82154 | 36.01499 | 0.03005 | 17.18938 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.72808 | 20.07747 | -0.3871 | 9.32703 |
February | 336.00000 | 21.51079 | 17.57654 | -0.4652 | 10.47912 |
March | 379.00000 | 22.16823 | 17.51535 | -0.2922 | 8.59825 |
April | 360.00000 | 22.40403 | 21.86312 | -0.2063 | 7.64858 |
May | 375.00000 | 23.78033 | 24.99268 | -0.7393 | 17.66537 |
June | 366.00000 | 24.05372 | 31.26741 | -0.4976 | 10.56896 |
July | 369.00000 | 24.06243 | 34.62362 | -0.4670 | 9.99067 |
August | 379.00000 | 24.04743 | 31.96686 | -0.4827 | 10.22223 |
September | 360.00000 | 23.99147 | 23.85709 | -0.5770 | 12.52401 |
October | 371.00000 | 23.11487 | 19.10386 | -0.0015 | 6.86264 |
November | 360.00000 | 22.15155 | 21.00076 | -0.2468 | 7.85297 |
December | 369.00000 | 21.63929 | 13.84289 | -0.4613 | 10.67190 |
Annual Sum or Average | 4395.00000 | 22.89926 | 23.18898 | -0.4020 | 10.20859 |
Minimum of Months | 336.00000 | 21.51079 | 13.84289 | -0.7393 | 6.86264 |
Maximum of Months | 379.00000 | 24.06243 | 34.62362 | -0.0015 | 17.66537 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.68357 | 20.13615 | -0.4058 | 9.56994 |
February | 336.00000 | 21.46920 | 17.62790 | -0.4819 | 10.74033 |
March | 379.00000 | 22.14004 | 17.54702 | -0.3056 | 8.76527 |
April | 360.00000 | 22.35978 | 21.93869 | -0.2237 | 7.80054 |
May | 375.00000 | 23.76037 | 25.02185 | -0.7519 | 18.15685 |
June | 366.00000 | 24.05401 | 31.26692 | -0.4965 | 10.54673 |
July | 369.00000 | 24.06301 | 34.62043 | -0.4651 | 9.95211 |
August | 379.00000 | 24.04787 | 31.96469 | -0.4812 | 10.19313 |
September | 360.00000 | 23.99047 | 23.85818 | -0.5772 | 12.54345 |
October | 371.00000 | 23.09197 | 19.14085 | -0.0112 | 6.90987 |
November | 360.00000 | 22.09561 | 21.08190 | -0.2669 | 8.03704 |
December | 369.00000 | 21.60387 | 13.87763 | -0.4774 | 10.92706 |
Annual Sum or Average | 4395.00000 | 22.87511 | 23.22155 | -0.4120 | 10.35233 |
Minimum of Months | 336.00000 | 21.46920 | 13.87763 | -0.7519 | 6.90987 |
Maximum of Months | 379.00000 | 24.06301 | 34.62043 | -0.0112 | 18.15685 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.58454 | 20.26310 | -0.4399 | 9.99609 |
February | 336.00000 | 21.40123 | 17.71352 | -0.5080 | 11.15766 |
March | 379.00000 | 22.06855 | 17.64424 | -0.3337 | 9.07049 |
April | 360.00000 | 22.24546 | 22.13879 | -0.2615 | 8.10590 |
May | 375.00000 | 23.70250 | 25.14814 | -0.7865 | 19.43158 |
June | 366.00000 | 24.04890 | 31.29270 | -0.5049 | 10.70738 |
July | 369.00000 | 24.05813 | 34.65775 | -0.4722 | 10.07783 |
August | 379.00000 | 24.04296 | 31.99169 | -0.4886 | 10.32906 |
September | 360.00000 | 23.97649 | 23.87931 | -0.5891 | 12.87924 |
October | 371.00000 | 23.01507 | 19.28337 | -0.0380 | 6.97958 |
November | 360.00000 | 21.97919 | 21.25031 | -0.3041 | 8.36731 |
December | 369.00000 | 21.53614 | 13.94745 | -0.5041 | 11.35246 |
Annual Sum or Average | 4395.00000 | 22.81697 | 23.31539 | -0.4358 | 10.71212 |
Minimum of Months | 336.00000 | 21.40123 | 13.94745 | -0.7865 | 6.97958 |
Maximum of Months | 379.00000 | 24.05813 | 34.65775 | -0.0380 | 19.43158 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.30679 | 22.20281 | -0.5192 | 11.14057 |
February | 308.00000 | 21.23537 | 19.45906 | -0.5658 | 12.16105 |
March | 348.00000 | 21.76708 | 19.53068 | -0.4140 | 9.99799 |
April | 330.00000 | 21.82098 | 24.35986 | -0.3647 | 8.98774 |
May | 344.00000 | 23.34058 | 27.23257 | -0.9109 | 24.14072 |
June | 336.00000 | 23.93045 | 32.43116 | -0.5426 | 11.34167 |
July | 338.00000 | 23.95178 | 35.83201 | -0.5050 | 10.55710 |
August | 348.00000 | 23.92594 | 32.91607 | -0.5242 | 10.91553 |
September | 330.00000 | 23.83134 | 25.22936 | -0.6343 | 14.19032 |
October | 340.00000 | 22.62189 | 21.25920 | -0.1274 | 7.33819 |
November | 330.00000 | 21.60255 | 23.22248 | -0.3981 | 9.35370 |
December | 338.00000 | 21.33208 | 15.74331 | -0.5699 | 12.48736 |
Annual Sum or Average | 4030.00000 | 22.56756 | 24.99929 | -0.5064 | 11.89727 |
Minimum of Months | 308.00000 | 21.23537 | 15.74331 | -0.9109 | 7.33819 |
Maximum of Months | 348.00000 | 23.95178 | 35.83201 | -0.1274 | 24.14072 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.41876 | 21.93642 | -0.5020 | 10.91557 |
February | 308.00000 | 21.30106 | 19.22323 | -0.5560 | 12.01359 |
March | 348.00000 | 21.91656 | 19.12210 | -0.3934 | 9.77017 |
April | 330.00000 | 22.04221 | 23.79805 | -0.3326 | 8.74520 |
May | 344.00000 | 23.54318 | 26.42513 | -0.8755 | 22.62482 |
June | 336.00000 | 23.93767 | 32.39237 | -0.5598 | 11.76805 |
July | 338.00000 | 23.96100 | 35.86160 | -0.5212 | 10.94643 |
August | 348.00000 | 23.93323 | 32.89373 | -0.5418 | 11.33680 |
September | 330.00000 | 23.87557 | 24.89762 | -0.6425 | 14.28492 |
October | 340.00000 | 22.84632 | 20.59842 | -0.0970 | 7.15705 |
November | 330.00000 | 21.77040 | 22.81001 | -0.3746 | 9.13270 |
December | 338.00000 | 21.42563 | 15.46123 | -0.5543 | 12.24802 |
Annual Sum or Average | 4030.00000 | 22.67649 | 24.66555 | -0.4959 | 11.75696 |
Minimum of Months | 308.00000 | 21.30106 | 15.46123 | -0.8755 | 7.15705 |
Maximum of Months | 348.00000 | 23.96100 | 35.86160 | -0.0970 | 22.62482 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.40542 | 21.95166 | -0.5087 | 11.03684 |
February | 308.00000 | 21.29199 | 19.23309 | -0.5617 | 12.12754 |
March | 348.00000 | 21.90147 | 19.14670 | -0.4004 | 9.87062 |
April | 330.00000 | 22.02154 | 23.83566 | -0.3403 | 8.84202 |
May | 344.00000 | 23.52199 | 26.48555 | -0.8879 | 23.09585 |
June | 336.00000 | 23.93714 | 32.40267 | -0.5640 | 11.86680 |
July | 338.00000 | 23.96037 | 35.87560 | -0.5248 | 11.02369 |
August | 348.00000 | 23.93281 | 32.90357 | -0.5451 | 11.41266 |
September | 330.00000 | 23.87318 | 24.90516 | -0.6464 | 14.39670 |
October | 340.00000 | 22.83059 | 20.63221 | -0.1029 | 7.18735 |
November | 330.00000 | 21.75521 | 22.83146 | -0.3810 | 9.22453 |
December | 338.00000 | 21.41739 | 15.47273 | -0.5591 | 12.34597 |
Annual Sum or Average | 4030.00000 | 22.66628 | 24.68703 | -0.5019 | 11.88142 |
Minimum of Months | 308.00000 | 21.29199 | 15.47273 | -0.8879 | 7.18735 |
Maximum of Months | 348.00000 | 23.96037 | 35.87560 | -0.1029 | 23.09585 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.35281 | 22.00158 | -0.5342 | 11.51277 |
February | 308.00000 | 21.25959 | 19.26600 | -0.5833 | 12.58947 |
March | 348.00000 | 21.83105 | 19.25013 | -0.4298 | 10.30100 |
April | 330.00000 | 21.92463 | 23.99763 | -0.3744 | 9.27527 |
May | 344.00000 | 23.42279 | 26.75355 | -0.9382 | 25.07576 |
June | 336.00000 | 23.93570 | 32.43102 | -0.5717 | 12.05127 |
July | 338.00000 | 23.95886 | 35.91303 | -0.5308 | 11.15402 |
August | 348.00000 | 23.93189 | 32.92762 | -0.5496 | 11.51751 |
September | 330.00000 | 23.86138 | 24.92888 | -0.6554 | 14.71227 |
October | 340.00000 | 22.74575 | 20.79414 | -0.1311 | 7.35069 |
November | 330.00000 | 21.69204 | 22.91772 | -0.4058 | 9.58213 |
December | 338.00000 | 21.37910 | 15.52470 | -0.5796 | 12.77278 |
Annual Sum or Average | 4030.00000 | 22.62005 | 24.77343 | -0.5237 | 12.33859 |
Minimum of Months | 308.00000 | 21.25959 | 15.52470 | -0.9382 | 7.35069 |
Maximum of Months | 348.00000 | 23.95886 | 35.91303 | -0.1311 | 25.07576 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.27207 | 21.77057 | -0.6073 | 13.20565 |
February | 308.00000 | 21.20822 | 18.94610 | -0.6527 | 14.36881 |
March | 348.00000 | 21.70523 | 19.09757 | -0.5079 | 11.80946 |
April | 330.00000 | 21.77068 | 23.86714 | -0.4546 | 10.67475 |
May | 344.00000 | 23.17998 | 27.22711 | -1.0584 | 30.22415 |
June | 336.00000 | 23.93405 | 32.40991 | -0.5778 | 12.19840 |
July | 338.00000 | 23.95941 | 35.94215 | -0.5332 | 11.21222 |
August | 348.00000 | 23.93248 | 32.89572 | -0.5421 | 11.37273 |
September | 330.00000 | 23.83751 | 24.89195 | -0.6591 | 15.06057 |
October | 340.00000 | 22.58763 | 20.87747 | -0.1933 | 8.02143 |
November | 330.00000 | 21.60847 | 22.72392 | -0.4628 | 10.66206 |
December | 338.00000 | 21.31551 | 15.23431 | -0.6423 | 14.36160 |
Annual Sum or Average | 4030.00000 | 22.53760 | 24.70777 | -0.5743 | 13.61317 |
Minimum of Months | 308.00000 | 21.20822 | 15.23431 | -1.0584 | 8.02143 |
Maximum of Months | 348.00000 | 23.95941 | 35.94215 | -0.1933 | 30.22415 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 255.49 | 68.78 | 0.17 | 255.49 | 0.00 | 0.00 | 0.00 | 20-JAN-13:10 | 0.00 | 01-JAN-00:10 | 0.43 | 20-JAN-13:10 | 0.43 | 20-JAN-13:10 | 0.00 | 20-JAN-13:10 | 0.11 | 20-JAN-13:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.176986E+09 | 45312811.59 | 17.83 | 0.176986E+09 | -0.0 | 0.00 | 0.45 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 5842.80 | 14-MAR-13:00 | 5842.80 | 14-MAR-13:00 | 0.00 | 13-MAR-16:20 | 1475.37 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 8926767.90 | 2378058.02 | 3.50 | 8926767.90 | -0.0 | 0.00 | 0.14 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 1680.86 | 20-APR-13:00 | 1680.86 | 20-APR-13:00 | 0.00 | 19-APR-14:00 | 443.91 | 20-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.167021E+10 | 0.431279E+09 | 134.27 | 0.165780E+10 | 12414799.95 | 0.00 | 0.69 | 17-MAY-14:00 | 0.00 | 01-MAY-00:05 | 9452.82 | 31-MAY-16:10 | 9452.82 | 31-MAY-16:10 | 597.90 | 31-MAY-18:40 | 2447.60 | 17-MAY-14:00 | 0.00 | 01-MAY-00:05 |
June | 0.116181E+11 | 0.300583E+10 | 415.92 | 0.110893E+11 | 0.528757E+09 | 0.00 | 1.00 | 13-JUN-13:30 | 0.00 | 01-JUN-00:10 | 18609.69 | 26-JUN-16:10 | 18609.69 | 26-JUN-16:10 | 3667.90 | 18-JUN-12:10 | 5588.21 | 26-JUN-16:10 | 0.00 | 01-JUN-00:10 |
July | 0.125285E+11 | 0.322213E+10 | 435.33 | 0.117745E+11 | 0.754056E+09 | 0.00 | 1.00 | 09-JUL-14:00 | 0.00 | 01-JUL-00:05 | 22179.50 | 18-JUL-07:03 | 22179.50 | 18-JUL-07:03 | 4629.75 | 30-JUL-12:40 | 4900.46 | 16-JUL-13:00 | 0.00 | 01-JUL-00:05 |
August | 0.119297E+11 | 0.303032E+10 | 438.97 | 0.113719E+11 | 0.557779E+09 | 0.00 | 1.00 | 11-AUG-12:10 | 0.00 | 01-AUG-00:10 | 18211.63 | 16-AUG-16:10 | 18211.63 | 16-AUG-16:10 | 4366.69 | 05-AUG-14:30 | 5199.39 | 16-AUG-16:10 | 0.00 | 01-AUG-00:10 |
September | 0.802283E+10 | 0.201001E+10 | 339.31 | 0.792978E+10 | 93041526.60 | 0.00 | 1.00 | 09-SEP-12:10 | 0.00 | 01-SEP-00:05 | 15668.99 | 10-SEP-13:00 | 15668.99 | 10-SEP-13:00 | 1451.28 | 01-SEP-14:00 | 4056.30 | 10-SEP-13:00 | 0.00 | 01-SEP-00:05 |
October | 0.775034E+09 | 0.191386E+09 | 54.83 | 0.775023E+09 | 11245.00 | 0.00 | 0.76 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 10680.75 | 11-OCT-14:00 | 10680.75 | 11-OCT-14:00 | 5.82 | 01-OCT-14:50 | 2618.82 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 61061126.95 | 15825126.11 | 14.50 | 61061126.95 | 0.00 | 0.00 | 0.29 | 07-NOV-15:00 | 0.00 | 01-NOV-00:03 | 3749.66 | 07-NOV-15:00 | 3749.66 | 07-NOV-15:00 | 0.00 | 07-NOV-15:10 | 950.04 | 07-NOV-15:00 | 0.00 | 01-NOV-00:03 |
December | 1503574.43 | 403683.29 | 1.17 | 1503574.43 | -0.0 | 0.00 | 0.08 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 | 982.44 | 02-DEC-15:00 | 982.44 | 02-DEC-15:00 | 0.00 | 04-DEC-13:00 | 263.23 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.467928E+11 | 0.119549E+11 | 1855.79 | 0.448467E+11 | 0.194606E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.125285E+11 | 0.322213E+10 | 438.97 | 0.117745E+11 | 0.754056E+09 | 0.00 | 1.00 | 0.00 | 22179.50 | 22179.50 | 4629.75 | 5588.21 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 3420715.07 | 785959.34 | 11.08 | 3420715.07 | -0.0 | 0.00 | 0.12 | 25-JAN-21:20 | 0.00 | 01-JAN-00:10 | 834.40 | 25-JAN-21:20 | 834.40 | 25-JAN-21:20 | 0.00 | 21-JAN-19:20 | 190.21 | 25-JAN-21:20 | 0.00 | 01-JAN-00:10 |
February | 647387.34 | 146246.82 | 4.33 | 647387.34 | 0.00 | 0.00 | 0.17 | 26-FEB-18:10 | 0.00 | 01-FEB-00:05 | 1248.28 | 26-FEB-18:10 | 1248.28 | 26-FEB-18:10 | 0.00 | 26-FEB-11:30 | 280.55 | 26-FEB-18:10 | 0.00 | 01-FEB-00:05 |
March | 0.149239E+09 | 32523597.93 | 24.58 | 0.149233E+09 | 5567.11 | 0.00 | 0.58 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4668.74 | 14-MAR-13:00 | 4668.74 | 14-MAR-13:00 | 9.28 | 17-MAR-21:00 | 989.85 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 22532687.94 | 5144276.76 | 23.67 | 22519561.01 | 13126.93 | 0.00 | 0.25 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 1864.69 | 20-APR-13:00 | 1864.69 | 20-APR-13:00 | 43.74 | 29-APR-18:40 | 416.93 | 20-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.136278E+10 | 0.297822E+09 | 151.93 | 0.135722E+10 | 5567246.45 | 0.00 | 1.00 | 06-MAY-18:01 | 0.00 | 01-MAY-00:05 | 17217.44 | 21-MAY-17:07 | 17180.52 | 06-MAY-18:01 | 2141.37 | 21-MAY-18:20 | 3204.76 | 21-MAY-17:07 | 0.00 | 01-MAY-00:05 |
June | 0.758372E+10 | 0.167862E+10 | 378.40 | 0.728551E+10 | 0.298212E+09 | 0.00 | 1.00 | 01-JUN-20:01 | 0.00 | 01-JUN-00:10 | 18492.32 | 17-JUN-18:32 | 17247.54 | 14-JUN-20:47 | 6678.74 | 03-JUN-20:20 | 3587.74 | 17-JUN-18:32 | 0.00 | 01-JUN-00:10 |
July | 0.818896E+10 | 0.180244E+10 | 396.86 | 0.774799E+10 | 0.440969E+09 | 0.00 | 1.00 | 01-JUL-19:31 | 0.00 | 01-JUL-00:05 | 19065.39 | 29-JUL-18:02 | 17230.28 | 14-JUL-22:24 | 8173.29 | 29-JUL-22:13 | 3611.52 | 29-JUL-18:02 | 0.00 | 01-JUL-00:05 |
August | 0.775201E+10 | 0.168425E+10 | 384.99 | 0.742897E+10 | 0.323037E+09 | 0.00 | 1.00 | 01-AUG-20:01 | 0.00 | 01-AUG-00:10 | 18637.07 | 04-AUG-22:18 | 17305.48 | 26-AUG-19:38 | 7572.73 | 04-AUG-22:18 | 3533.97 | 25-AUG-22:09 | 0.00 | 01-AUG-00:10 |
September | 0.521096E+10 | 0.111895E+10 | 312.56 | 0.517103E+10 | 39924825.67 | 0.00 | 1.00 | 02-SEP-19:11 | 0.00 | 01-SEP-00:05 | 17745.74 | 02-SEP-20:05 | 17319.76 | 12-SEP-20:07 | 3946.56 | 02-SEP-23:00 | 3428.42 | 02-SEP-19:17 | 0.00 | 01-SEP-00:05 |
October | 0.501823E+09 | 0.106661E+09 | 58.62 | 0.501819E+09 | 3553.71 | 0.00 | 1.00 | 09-OCT-17:01 | 0.00 | 01-OCT-00:10 | 17180.52 | 09-OCT-17:06 | 17180.52 | 09-OCT-17:01 | 5.91 | 01-OCT-07:10 | 3196.38 | 09-OCT-17:01 | 0.00 | 01-OCT-00:10 |
November | 57656934.13 | 12882066.60 | 22.25 | 57656874.82 | 59.31 | 0.00 | 0.36 | 07-NOV-14:30 | 0.00 | 01-NOV-00:03 | 2782.57 | 07-NOV-14:30 | 2782.57 | 07-NOV-14:30 | 0.20 | 18-NOV-19:20 | 603.61 | 07-NOV-14:30 | 0.00 | 01-NOV-00:03 |
December | 7060356.47 | 1624279.26 | 7.42 | 7060356.47 | -0.0 | 0.00 | 0.19 | 17-DEC-18:20 | 0.00 | 01-DEC-00:05 | 1410.91 | 17-DEC-18:20 | 1410.91 | 17-DEC-18:20 | 0.00 | 02-DEC-13:30 | 315.35 | 17-DEC-18:20 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.308408E+11 | 0.674184E+10 | 1776.69 | 0.297331E+11 | 0.110773E+10 | 0.00 | ||||||||||||||
Minimum of Months | 647387.34 | 146246.82 | 4.33 | 647387.34 | -0.0 | 0.00 | 0.12 | 0.00 | 834.40 | 834.40 | 0.00 | 190.21 | 0.00 | |||||||
Maximum of Months | 0.818896E+10 | 0.180244E+10 | 396.86 | 0.774799E+10 | 0.440969E+09 | 0.00 | 1.00 | 0.00 | 19065.39 | 17319.76 | 8173.29 | 3611.52 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 806790.47 | 187823.63 | 8.67 | 806790.47 | -0.0 | 0.00 | 0.04 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 313.19 | 20-JAN-14:00 | 313.19 | 20-JAN-14:00 | 0.00 | 20-JAN-13:10 | 72.72 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 988.64 | 232.06 | 2.83 | 988.64 | 0.00 | 0.00 | 0.00 | 26-FEB-11:50 | 0.00 | 01-FEB-00:05 | 0.25 | 26-FEB-11:50 | 0.25 | 26-FEB-11:50 | 0.00 | 26-FEB-12:20 | 0.06 | 26-FEB-11:50 | 0.00 | 01-FEB-00:05 |
March | 0.140846E+09 | 30858102.56 | 22.50 | 0.140846E+09 | -0.0 | 0.00 | 0.57 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4654.32 | 14-MAR-13:00 | 4654.32 | 14-MAR-13:00 | 0.00 | 13-MAR-16:00 | 989.93 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 16016644.35 | 3667887.16 | 17.50 | 16016639.26 | 5.09 | 0.00 | 0.24 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 1797.35 | 20-APR-13:00 | 1797.35 | 20-APR-13:00 | 0.00 | 28-APR-15:00 | 403.24 | 20-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.121034E+10 | 0.267933E+09 | 138.08 | 0.120798E+10 | 2363179.65 | 0.00 | 0.72 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 | 6027.51 | 17-MAY-13:00 | 6027.51 | 17-MAY-13:00 | 171.44 | 30-MAY-17:10 | 1363.26 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 |
June | 0.601100E+10 | 0.136028E+10 | 328.58 | 0.581286E+10 | 0.198135E+09 | 0.00 | 1.00 | 13-JUN-14:00 | 0.00 | 01-JUN-00:10 | 10932.87 | 25-JUN-07:03 | 10932.87 | 25-JUN-07:03 | 2019.96 | 18-JUN-07:03 | 2753.27 | 26-JUN-16:10 | 0.00 | 01-JUN-00:10 |
July | 0.639220E+10 | 0.143516E+10 | 335.08 | 0.609870E+10 | 0.293501E+09 | 0.00 | 1.00 | 15-JUL-12:10 | 0.00 | 01-JUL-00:05 | 16445.04 | 16-JUL-07:03 | 16445.04 | 16-JUL-07:03 | 2577.40 | 30-JUL-10:50 | 3402.20 | 16-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.601564E+10 | 0.133855E+10 | 333.64 | 0.584641E+10 | 0.169234E+09 | 0.00 | 1.00 | 11-AUG-13:50 | 0.00 | 01-AUG-00:10 | 9913.96 | 16-AUG-16:10 | 9913.96 | 16-AUG-16:10 | 2769.44 | 05-AUG-06:03 | 2516.54 | 16-AUG-16:10 | 0.00 | 01-AUG-00:10 |
September | 0.422878E+10 | 0.924762E+09 | 275.67 | 0.421144E+10 | 17342949.27 | 0.00 | 1.00 | 09-SEP-12:30 | 0.00 | 01-SEP-00:05 | 10108.61 | 13-SEP-06:03 | 9338.95 | 13-SEP-06:03 | 769.66 | 13-SEP-06:03 | 2071.43 | 09-SEP-13:00 | 0.00 | 01-SEP-00:05 |
October | 0.447593E+09 | 95913101.66 | 51.75 | 0.447574E+09 | 18829.04 | 0.00 | 0.75 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 6430.90 | 11-OCT-14:00 | 6430.90 | 11-OCT-14:00 | 31.37 | 01-OCT-07:10 | 1376.23 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 41772212.68 | 9383324.11 | 18.50 | 41772212.68 | 0.00 | 0.00 | 0.33 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 | 2567.48 | 07-NOV-14:00 | 2567.48 | 07-NOV-14:00 | 0.00 | 07-NOV-14:40 | 561.77 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 |
December | 4560876.20 | 1053571.88 | 5.92 | 4560876.20 | -0.0 | 0.00 | 0.16 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 | 1187.81 | 02-DEC-15:00 | 1187.81 | 02-DEC-15:00 | 0.00 | 02-DEC-14:30 | 271.95 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.245096E+11 | 0.546775E+10 | 1538.72 | 0.238290E+11 | 0.680595E+09 | 0.00 | ||||||||||||||
Minimum of Months | 988.64 | 232.06 | 2.83 | 988.64 | -0.0 | 0.00 | 0.00 | 0.00 | 0.25 | 0.25 | 0.00 | 0.06 | 0.00 | |||||||
Maximum of Months | 0.639220E+10 | 0.143516E+10 | 335.08 | 0.609870E+10 | 0.293501E+09 | 0.00 | 1.00 | 0.00 | 16445.04 | 16445.04 | 2769.44 | 3402.20 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 259409.63 | 60655.96 | 7.17 | 259409.63 | -0.0 | 0.00 | 0.02 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 149.75 | 20-JAN-14:00 | 149.75 | 20-JAN-14:00 | 0.00 | 20-JAN-12:40 | 34.97 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 708.07 | 166.20 | 3.67 | 708.07 | 0.00 | 0.00 | 0.00 | 26-FEB-12:50 | 0.00 | 01-FEB-00:05 | 0.18 | 26-FEB-12:50 | 0.18 | 26-FEB-12:50 | 0.00 | 26-FEB-12:50 | 0.04 | 26-FEB-12:50 | 0.00 | 01-FEB-00:05 |
March | 0.133554E+09 | 29368832.08 | 23.00 | 0.133554E+09 | 0.00 | 0.00 | 0.55 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4548.46 | 14-MAR-13:00 | 4548.46 | 14-MAR-13:00 | 0.00 | 13-MAR-15:30 | 971.33 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 12821690.40 | 2945631.82 | 16.00 | 12821680.30 | 10.10 | 0.00 | 0.22 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 1671.19 | 20-APR-13:00 | 1671.19 | 20-APR-13:00 | 0.01 | 28-APR-15:00 | 376.62 | 20-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.117932E+10 | 0.261720E+09 | 136.50 | 0.117723E+10 | 2092105.17 | 0.00 | 0.71 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 | 5985.77 | 17-MAY-13:00 | 5985.77 | 17-MAY-13:00 | 153.89 | 30-MAY-17:10 | 1356.92 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 |
June | 0.603462E+10 | 0.136616E+10 | 328.67 | 0.583617E+10 | 0.198446E+09 | 0.00 | 1.00 | 13-JUN-14:00 | 0.00 | 01-JUN-00:10 | 11272.95 | 25-JUN-07:03 | 11272.95 | 25-JUN-07:03 | 2187.76 | 18-JUN-07:03 | 2764.56 | 26-JUN-16:10 | 0.00 | 01-JUN-00:10 |
July | 0.643217E+10 | 0.144425E+10 | 335.08 | 0.613779E+10 | 0.294373E+09 | 0.00 | 1.00 | 15-JUL-12:10 | 0.00 | 01-JUL-00:05 | 17084.44 | 16-JUL-07:03 | 17084.44 | 16-JUL-07:03 | 2582.34 | 30-JUL-10:50 | 3541.99 | 16-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.604446E+10 | 0.134533E+10 | 334.11 | 0.587399E+10 | 0.170466E+09 | 0.00 | 1.00 | 11-AUG-13:50 | 0.00 | 01-AUG-00:10 | 9934.14 | 16-AUG-16:10 | 9934.14 | 16-AUG-16:10 | 2911.28 | 05-AUG-06:03 | 2520.79 | 16-AUG-16:10 | 0.00 | 01-AUG-00:10 |
September | 0.423835E+10 | 0.927341E+09 | 276.08 | 0.422074E+10 | 17606691.95 | 0.00 | 1.00 | 09-SEP-12:30 | 0.00 | 01-SEP-00:05 | 10571.31 | 13-SEP-06:03 | 10094.09 | 11-SEP-06:03 | 820.45 | 13-SEP-06:03 | 2077.81 | 09-SEP-13:00 | 0.00 | 01-SEP-00:05 |
October | 0.436607E+09 | 93693054.44 | 49.42 | 0.436591E+09 | 16366.36 | 0.00 | 0.75 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 6402.28 | 11-OCT-14:00 | 6402.28 | 11-OCT-14:00 | 27.27 | 01-OCT-07:10 | 1372.77 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 34248772.87 | 7716373.71 | 16.33 | 34248772.87 | 0.00 | 0.00 | 0.31 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 | 2388.44 | 07-NOV-14:00 | 2388.44 | 07-NOV-14:00 | 0.00 | 06-NOV-13:40 | 525.85 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 |
December | 3448212.45 | 799167.78 | 6.42 | 3448212.45 | -0.0 | 0.00 | 0.14 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 | 1059.84 | 02-DEC-15:00 | 1059.84 | 02-DEC-15:00 | 0.00 | 02-DEC-14:40 | 243.75 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.245499E+11 | 0.547938E+10 | 1532.44 | 0.238669E+11 | 0.683000E+09 | 0.00 | ||||||||||||||
Minimum of Months | 708.07 | 166.20 | 3.67 | 708.07 | -0.0 | 0.00 | 0.00 | 0.00 | 0.18 | 0.18 | 0.00 | 0.04 | 0.00 | |||||||
Maximum of Months | 0.643217E+10 | 0.144425E+10 | 335.08 | 0.613779E+10 | 0.294373E+09 | 0.00 | 1.00 | 0.00 | 17084.44 | 17084.44 | 2911.28 | 3541.99 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 1404.86 | 329.75 | 3.00 | 1404.86 | -0.0 | 0.00 | 0.00 | 23-JAN-13:10 | 0.00 | 01-JAN-00:10 | 0.30 | 23-JAN-13:10 | 0.30 | 23-JAN-13:10 | 0.00 | 25-JAN-14:10 | 0.07 | 23-JAN-13:10 | 0.00 | 01-JAN-00:10 |
February | 199.97 | 46.94 | 0.83 | 199.97 | 0.00 | 0.00 | 0.00 | 18-FEB-12:30 | 0.00 | 01-FEB-00:05 | 0.11 | 18-FEB-12:30 | 0.11 | 18-FEB-12:30 | 0.00 | 18-FEB-12:50 | 0.02 | 18-FEB-12:30 | 0.00 | 01-FEB-00:05 |
March | 0.115375E+09 | 25556194.94 | 22.83 | 0.115375E+09 | 0.00 | 0.00 | 0.52 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4231.06 | 14-MAR-13:00 | 4231.06 | 14-MAR-13:00 | 0.00 | 14-MAR-13:30 | 911.22 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 7390497.67 | 1709109.01 | 12.17 | 7390497.67 | 0.00 | 0.00 | 0.18 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 1359.05 | 20-APR-13:00 | 1359.05 | 20-APR-13:00 | 0.00 | 20-APR-13:10 | 309.33 | 20-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.107642E+10 | 0.240286E+09 | 133.92 | 0.107489E+10 | 1524085.17 | 0.00 | 0.70 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 | 5771.90 | 17-MAY-13:00 | 5771.90 | 17-MAY-13:00 | 128.02 | 31-MAY-18:40 | 1314.69 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 |
June | 0.585931E+10 | 0.133038E+10 | 325.83 | 0.566876E+10 | 0.190549E+09 | 0.00 | 1.00 | 14-JUN-12:10 | 0.00 | 01-JUN-00:10 | 10207.13 | 26-JUN-16:10 | 10207.13 | 26-JUN-16:10 | 1812.17 | 21-JUN-17:00 | 2733.45 | 26-JUN-16:10 | 0.00 | 01-JUN-00:10 |
July | 0.625901E+10 | 0.140912E+10 | 333.36 | 0.597612E+10 | 0.282889E+09 | 0.00 | 1.00 | 15-JUL-12:10 | 0.00 | 01-JUL-00:05 | 15725.46 | 16-JUL-07:03 | 15725.46 | 16-JUL-07:03 | 2486.71 | 30-JUL-10:50 | 3244.17 | 16-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.588313E+10 | 0.131282E+10 | 331.19 | 0.571947E+10 | 0.163665E+09 | 0.00 | 1.00 | 11-AUG-14:00 | 0.00 | 01-AUG-00:10 | 9804.21 | 16-AUG-16:10 | 9804.21 | 16-AUG-16:10 | 2480.20 | 05-AUG-14:30 | 2486.50 | 16-AUG-16:10 | 0.00 | 01-AUG-00:10 |
September | 0.409590E+10 | 0.898786E+09 | 273.64 | 0.407935E+10 | 16556737.88 | 0.00 | 1.00 | 09-SEP-12:40 | 0.00 | 01-SEP-00:05 | 9162.88 | 13-SEP-06:03 | 9100.20 | 11-SEP-06:03 | 678.31 | 13-SEP-06:03 | 2042.92 | 09-SEP-13:00 | 0.00 | 01-SEP-00:05 |
October | 0.403463E+09 | 86817794.88 | 48.42 | 0.403460E+09 | 3348.02 | 0.00 | 0.74 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 6224.75 | 11-OCT-14:00 | 6224.75 | 11-OCT-14:00 | 5.58 | 01-OCT-07:10 | 1339.36 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 23984712.14 | 5430935.69 | 11.33 | 23984712.14 | 0.00 | 0.00 | 0.27 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 | 2067.80 | 07-NOV-14:00 | 2067.80 | 07-NOV-14:00 | 0.00 | 07-NOV-14:10 | 459.71 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 |
December | 1493962.15 | 347818.34 | 4.50 | 1493962.15 | -0.0 | 0.00 | 0.11 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 | 800.11 | 02-DEC-15:00 | 800.11 | 02-DEC-15:00 | 0.00 | 02-DEC-14:30 | 185.59 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.237255E+11 | 0.531124E+10 | 1501.03 | 0.230703E+11 | 0.655186E+09 | 0.00 | ||||||||||||||
Minimum of Months | 199.97 | 46.94 | 0.83 | 199.97 | -0.0 | 0.00 | 0.00 | 0.00 | 0.11 | 0.11 | 0.00 | 0.02 | 0.00 | |||||||
Maximum of Months | 0.625901E+10 | 0.140912E+10 | 333.36 | 0.597612E+10 | 0.282889E+09 | 0.00 | 1.00 | 0.00 | 15725.46 | 15725.46 | 2486.71 | 3244.17 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 80.09 | 21.56 | 0.17 | 80.09 | -0.0 | 0.00 | 0.00 | 20-JAN-13:10 | 0.00 | 01-JAN-00:10 | 0.13 | 20-JAN-13:10 | 0.13 | 20-JAN-13:10 | 0.00 | 01-JAN-00:10 | 0.04 | 20-JAN-13:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.164788E+09 | 42294717.85 | 16.83 | 0.164788E+09 | 0.00 | 0.00 | 0.46 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 5982.49 | 14-MAR-13:00 | 5982.49 | 14-MAR-13:00 | 0.00 | 14-MAR-13:30 | 1503.17 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 4328958.28 | 1152118.91 | 2.17 | 4328958.28 | -0.0 | 0.00 | 0.14 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 1726.67 | 20-APR-13:00 | 1726.67 | 20-APR-13:00 | 0.00 | 20-APR-12:30 | 455.26 | 20-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.147640E+10 | 0.382384E+09 | 111.33 | 0.146890E+10 | 7500280.08 | 0.00 | 0.70 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 | 9374.25 | 17-MAY-13:00 | 9374.25 | 17-MAY-13:00 | 356.15 | 31-MAY-18:40 | 2449.04 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 |
June | 0.957934E+10 | 0.249579E+10 | 326.71 | 0.915161E+10 | 0.427735E+09 | 0.00 | 1.00 | 13-JUN-12:40 | 0.00 | 01-JUN-00:10 | 30192.31 | 25-JUN-08:62 | 30192.31 | 25-JUN-08:62 | 3404.13 | 18-JUN-12:00 | 7005.09 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.101770E+11 | 0.262307E+10 | 327.18 | 0.958000E+10 | 0.597012E+09 | 0.00 | 1.00 | 09-JUL-14:10 | 0.00 | 01-JUL-00:05 | 31045.64 | 23-JUL-08:62 | 30311.38 | 17-JUL-07:03 | 4198.69 | 24-JUL-07:03 | 7306.56 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.982652E+10 | 0.250962E+10 | 335.14 | 0.941855E+10 | 0.407963E+09 | 0.00 | 1.00 | 10-AUG-14:10 | 0.00 | 01-AUG-00:10 | 19442.20 | 20-AUG-08:63 | 17915.67 | 16-AUG-14:10 | 4959.12 | 05-AUG-14:30 | 5140.03 | 16-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.654514E+10 | 0.164791E+10 | 274.47 | 0.648241E+10 | 62731347.97 | 0.00 | 1.00 | 09-SEP-12:10 | 0.00 | 01-SEP-00:05 | 15204.95 | 09-SEP-13:00 | 15204.95 | 09-SEP-13:00 | 1517.55 | 03-SEP-08:63 | 3936.27 | 09-SEP-13:00 | 0.00 | 01-SEP-00:05 |
October | 0.637460E+09 | 0.158245E+09 | 44.67 | 0.637455E+09 | 4201.24 | 0.00 | 0.75 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 | 10298.48 | 11-OCT-14:10 | 10298.48 | 11-OCT-14:10 | 3.40 | 01-OCT-15:00 | 2524.30 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 35675162.39 | 9333036.52 | 8.33 | 35675162.39 | -0.0 | 0.00 | 0.24 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 | 2936.69 | 07-NOV-14:00 | 2936.69 | 07-NOV-14:00 | 0.00 | 07-NOV-15:20 | 755.24 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 |
December | 1466270.29 | 394128.01 | 1.00 | 1466270.29 | 0.00 | 0.00 | 0.08 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 | 894.34 | 02-DEC-15:00 | 894.34 | 02-DEC-15:00 | 0.00 | 02-DEC-14:40 | 239.97 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.384481E+11 | 0.987019E+10 | 1447.99 | 0.369452E+11 | 0.150295E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.101770E+11 | 0.262307E+10 | 335.14 | 0.958000E+10 | 0.597012E+09 | 0.00 | 1.00 | 0.00 | 31045.64 | 30311.38 | 4959.12 | 7306.56 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 25506.24 | 5982.09 | 0.67 | 25506.24 | 0.00 | 0.00 | 0.00 | 24-JAN-14:30 | 0.00 | 01-JAN-00:10 | 24.35 | 24-JAN-14:30 | 24.35 | 24-JAN-14:30 | 0.00 | 23-JAN-14:10 | 5.71 | 24-JAN-14:30 | 0.00 | 01-JAN-00:10 |
February | 129.97 | 30.51 | 0.50 | 129.97 | -0.0 | 0.00 | 0.00 | 18-FEB-13:10 | 0.00 | 01-FEB-00:05 | 0.14 | 18-FEB-13:10 | 0.14 | 18-FEB-13:10 | 0.00 | 01-FEB-00:05 | 0.03 | 18-FEB-13:10 | 0.00 | 01-FEB-00:05 |
March | 94511002.69 | 21015298.13 | 19.83 | 94511002.69 | 0.00 | 0.00 | 0.51 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3753.78 | 14-MAR-13:00 | 3753.78 | 14-MAR-13:00 | 0.00 | 14-MAR-14:40 | 811.79 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 3236217.16 | 753447.07 | 6.00 | 3236217.16 | 0.00 | 0.00 | 0.16 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 1054.28 | 20-APR-13:00 | 1054.28 | 20-APR-13:00 | 0.00 | 20-APR-13:00 | 241.65 | 20-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.913919E+09 | 0.204477E+09 | 117.67 | 0.912567E+09 | 1352032.21 | 0.00 | 0.72 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 | 5500.69 | 17-MAY-13:00 | 5500.69 | 17-MAY-13:00 | 123.59 | 31-MAY-18:40 | 1245.57 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 |
June | 0.553158E+10 | 0.125425E+10 | 315.89 | 0.534569E+10 | 0.185885E+09 | 0.00 | 1.00 | 13-JUN-12:30 | 0.00 | 01-JUN-00:10 | 14802.54 | 25-JUN-08:62 | 14802.54 | 25-JUN-08:62 | 1684.84 | 18-JUN-12:10 | 3158.21 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.586750E+10 | 0.131637E+10 | 321.06 | 0.559775E+10 | 0.269749E+09 | 0.00 | 1.00 | 09-JUL-14:00 | 0.00 | 01-JUL-00:05 | 15392.17 | 23-JUL-08:62 | 15361.94 | 16-JUL-08:62 | 2166.64 | 29-JUL-11:50 | 3476.58 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.562062E+10 | 0.124978E+10 | 326.19 | 0.545429E+10 | 0.166334E+09 | 0.00 | 1.00 | 10-AUG-14:10 | 0.00 | 01-AUG-00:10 | 9772.36 | 16-AUG-14:10 | 9772.36 | 16-AUG-14:10 | 2555.45 | 05-AUG-14:30 | 2504.89 | 16-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.376629E+10 | 0.823598E+09 | 262.81 | 0.375117E+10 | 15121153.75 | 0.00 | 1.00 | 09-SEP-12:20 | 0.00 | 01-SEP-00:05 | 8506.12 | 09-SEP-13:00 | 8506.12 | 09-SEP-13:00 | 451.56 | 01-SEP-12:20 | 1929.04 | 09-SEP-13:00 | 0.00 | 01-SEP-00:05 |
October | 0.356542E+09 | 76542425.20 | 41.42 | 0.356542E+09 | 6.07 | 0.00 | 0.77 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 | 6010.99 | 11-OCT-14:10 | 6010.99 | 11-OCT-14:10 | 0.01 | 01-OCT-08:15 | 1276.33 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 17727937.59 | 4028242.48 | 8.33 | 17727937.59 | -0.0 | 0.00 | 0.25 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 | 1729.60 | 07-NOV-14:00 | 1729.60 | 07-NOV-14:00 | 0.00 | 06-NOV-13:40 | 386.80 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 |
December | 1083556.15 | 252967.25 | 2.00 | 1083556.15 | 0.00 | 0.00 | 0.10 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 | 653.07 | 02-DEC-15:00 | 653.07 | 02-DEC-15:00 | 0.00 | 02-DEC-14:40 | 151.94 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.221730E+11 | 0.495107E+10 | 1422.36 | 0.215346E+11 | 0.638442E+09 | 0.00 | ||||||||||||||
Minimum of Months | 129.97 | 30.51 | 0.50 | 129.97 | -0.0 | 0.00 | 0.00 | 0.00 | 0.14 | 0.14 | 0.00 | 0.03 | 0.00 | |||||||
Maximum of Months | 0.586750E+10 | 0.131637E+10 | 326.19 | 0.559775E+10 | 0.269749E+09 | 0.00 | 1.00 | 0.00 | 15392.17 | 15361.94 | 2555.45 | 3476.58 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 1397.93 | 328.11 | 0.33 | 1397.93 | 0.00 | 0.00 | 0.00 | 23-JAN-14:00 | 0.00 | 01-JAN-00:10 | 1.79 | 23-JAN-14:00 | 1.79 | 23-JAN-14:00 | 0.00 | 23-JAN-14:00 | 0.42 | 23-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 43.57 | 10.23 | 0.33 | 43.57 | 0.00 | 0.00 | 0.00 | 18-FEB-13:30 | 0.00 | 01-FEB-00:05 | 0.07 | 18-FEB-13:30 | 0.07 | 18-FEB-13:30 | 0.00 | 18-FEB-13:40 | 0.02 | 18-FEB-13:30 | 0.00 | 01-FEB-00:05 |
March | 90184799.45 | 20090899.92 | 19.33 | 90184799.45 | 0.00 | 0.00 | 0.50 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3657.09 | 14-MAR-13:00 | 3657.09 | 14-MAR-13:00 | 0.00 | 14-MAR-13:50 | 792.66 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 2753089.48 | 640803.47 | 6.17 | 2753089.48 | 0.00 | 0.00 | 0.15 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 1014.95 | 20-APR-13:00 | 1014.95 | 20-APR-13:00 | 0.00 | 20-APR-13:10 | 232.90 | 20-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.886273E+09 | 0.198583E+09 | 114.50 | 0.885068E+09 | 1205634.17 | 0.00 | 0.71 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 | 5422.62 | 17-MAY-13:00 | 5422.62 | 17-MAY-13:00 | 120.66 | 31-MAY-18:40 | 1229.21 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 |
June | 0.546310E+10 | 0.123947E+10 | 315.72 | 0.528009E+10 | 0.183015E+09 | 0.00 | 1.00 | 13-JUN-12:30 | 0.00 | 01-JUN-00:10 | 14220.83 | 25-JUN-08:62 | 14220.83 | 25-JUN-08:62 | 1674.27 | 18-JUN-12:10 | 3027.50 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.580111E+10 | 0.130198E+10 | 319.78 | 0.553555E+10 | 0.265564E+09 | 0.00 | 1.00 | 09-JUL-14:00 | 0.00 | 01-JUL-00:05 | 15226.38 | 16-JUL-08:62 | 15226.38 | 16-JUL-08:62 | 2134.71 | 29-JUL-11:50 | 3445.90 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.556111E+10 | 0.123688E+10 | 326.25 | 0.539712E+10 | 0.163991E+09 | 0.00 | 1.00 | 10-AUG-14:10 | 0.00 | 01-AUG-00:10 | 9715.23 | 16-AUG-14:10 | 9715.23 | 16-AUG-14:10 | 2531.19 | 05-AUG-14:30 | 2490.78 | 16-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.372311E+10 | 0.814338E+09 | 261.89 | 0.370828E+10 | 14837544.37 | 0.00 | 1.00 | 09-SEP-12:20 | 0.00 | 01-SEP-00:05 | 8453.13 | 09-SEP-13:00 | 8453.13 | 09-SEP-13:00 | 446.73 | 01-SEP-12:20 | 1917.47 | 09-SEP-13:00 | 0.00 | 01-SEP-00:05 |
October | 0.349145E+09 | 75010624.98 | 42.67 | 0.349145E+09 | 4.79 | 0.00 | 0.77 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 | 5944.01 | 11-OCT-14:10 | 5944.01 | 11-OCT-14:10 | 0.00 | 01-OCT-09:10 | 1262.80 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 16832294.82 | 3827704.76 | 8.00 | 16832294.82 | -0.0 | 0.00 | 0.24 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 | 1685.06 | 07-NOV-14:00 | 1685.06 | 07-NOV-14:00 | 0.00 | 07-NOV-14:00 | 377.26 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 |
December | 969192.95 | 226434.21 | 1.50 | 969192.95 | -0.0 | 0.00 | 0.09 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 | 620.55 | 02-DEC-15:00 | 620.55 | 02-DEC-15:00 | 0.00 | 02-DEC-14:50 | 144.52 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.218946E+11 | 0.489105E+10 | 1416.47 | 0.212660E+11 | 0.628613E+09 | 0.00 | ||||||||||||||
Minimum of Months | 43.57 | 10.23 | 0.33 | 43.57 | -0.0 | 0.00 | 0.00 | 0.00 | 0.07 | 0.07 | 0.00 | 0.02 | 0.00 | |||||||
Maximum of Months | 0.580111E+10 | 0.130198E+10 | 326.25 | 0.553555E+10 | 0.265564E+09 | 0.00 | 1.00 | 0.00 | 15226.38 | 15226.38 | 2531.19 | 3445.90 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 179.88 | 42.22 | 0.67 | 179.88 | 0.00 | 0.00 | 0.00 | 20-JAN-13:30 | 0.00 | 01-JAN-00:10 | 0.17 | 20-JAN-13:30 | 0.17 | 20-JAN-13:30 | 0.00 | 20-JAN-13:50 | 0.04 | 20-JAN-13:30 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 74815021.29 | 16803051.57 | 16.83 | 74815021.29 | 0.00 | 0.00 | 0.47 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3342.80 | 14-MAR-13:00 | 3342.80 | 14-MAR-13:00 | 0.00 | 14-MAR-14:10 | 731.54 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 1296271.58 | 301871.16 | 3.83 | 1296271.58 | 0.00 | 0.00 | 0.12 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 807.46 | 20-APR-13:00 | 807.46 | 20-APR-13:00 | 0.00 | 20-APR-12:50 | 186.67 | 20-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.793407E+09 | 0.178908E+09 | 106.42 | 0.792652E+09 | 754955.71 | 0.00 | 0.69 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 | 5211.37 | 17-MAY-13:00 | 5211.37 | 17-MAY-13:00 | 111.69 | 31-MAY-18:40 | 1187.49 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 |
June | 0.530217E+10 | 0.120624E+10 | 312.50 | 0.512651E+10 | 0.175665E+09 | 0.00 | 1.00 | 13-JUN-12:40 | 0.00 | 01-JUN-00:10 | 12065.61 | 25-JUN-08:62 | 12065.61 | 25-JUN-08:62 | 1652.02 | 18-JUN-12:00 | 2839.53 | 26-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.564467E+10 | 0.126979E+10 | 317.42 | 0.539056E+10 | 0.254107E+09 | 0.00 | 1.00 | 09-JUL-14:10 | 0.00 | 01-JUL-00:05 | 15043.12 | 16-JUL-08:62 | 15043.12 | 16-JUL-08:62 | 2086.51 | 30-JUL-12:30 | 3404.43 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.543700E+10 | 0.121109E+10 | 323.81 | 0.527843E+10 | 0.158571E+09 | 0.00 | 1.00 | 10-AUG-14:10 | 0.00 | 01-AUG-00:10 | 9633.72 | 16-AUG-14:10 | 9633.72 | 16-AUG-14:10 | 2495.23 | 05-AUG-14:30 | 2470.23 | 16-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.362462E+10 | 0.794004E+09 | 259.14 | 0.361045E+10 | 14165669.40 | 0.00 | 1.00 | 09-SEP-12:20 | 0.00 | 01-SEP-00:05 | 8391.28 | 09-SEP-13:00 | 8391.28 | 09-SEP-13:00 | 438.67 | 01-SEP-12:20 | 1904.06 | 09-SEP-13:00 | 0.00 | 01-SEP-00:05 |
October | 0.324626E+09 | 69991636.78 | 38.33 | 0.324626E+09 | 4.53 | 0.00 | 0.76 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 | 5782.32 | 11-OCT-14:10 | 5782.32 | 11-OCT-14:10 | 0.01 | 01-OCT-09:10 | 1232.51 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 13428420.29 | 3068980.11 | 6.67 | 13428420.29 | 0.00 | 0.00 | 0.22 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 | 1490.53 | 07-NOV-14:00 | 1490.53 | 07-NOV-14:00 | 0.00 | 07-NOV-14:10 | 335.89 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 |
December | 459608.02 | 108054.47 | 1.50 | 459608.02 | 0.00 | 0.00 | 0.06 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 | 414.42 | 02-DEC-15:00 | 414.42 | 02-DEC-15:00 | 0.00 | 02-DEC-15:00 | 97.26 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.212165E+11 | 0.475030E+10 | 1387.11 | 0.206132E+11 | 0.603263E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.564467E+10 | 0.126979E+10 | 323.81 | 0.539056E+10 | 0.254107E+09 | 0.00 | 1.00 | 0.00 | 15043.12 | 15043.12 | 2495.23 | 3404.43 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 54409473.73 | 12386546.76 | 13.67 | 54409473.73 | -0.0 | 0.00 | 0.42 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3071.67 | 14-MAR-13:00 | 3071.67 | 14-MAR-13:00 | 0.00 | 14-MAR-13:30 | 681.23 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 609527.41 | 142682.01 | 0.83 | 609527.41 | -0.0 | 0.00 | 0.09 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 595.52 | 20-APR-13:00 | 595.52 | 20-APR-13:00 | 0.00 | 20-APR-13:10 | 138.90 | 20-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.696300E+09 | 0.158656E+09 | 93.44 | 0.695649E+09 | 651037.82 | 0.00 | 0.67 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 | 5129.32 | 17-MAY-13:00 | 5129.32 | 17-MAY-13:00 | 96.77 | 31-MAY-18:40 | 1179.08 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 |
June | 0.540098E+10 | 0.123237E+10 | 309.36 | 0.522875E+10 | 0.172224E+09 | 0.00 | 1.00 | 13-JUN-12:20 | 0.00 | 01-JUN-00:10 | 10641.15 | 25-JUN-08:62 | 10641.15 | 25-JUN-08:62 | 1698.46 | 18-JUN-12:00 | 2925.67 | 26-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.575995E+10 | 0.129910E+10 | 311.81 | 0.551376E+10 | 0.246182E+09 | 0.00 | 1.00 | 09-JUL-14:10 | 0.00 | 01-JUL-00:05 | 15717.06 | 16-JUL-08:62 | 15717.06 | 16-JUL-08:62 | 2113.88 | 30-JUL-12:20 | 3554.13 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.568189E+10 | 0.126354E+10 | 321.39 | 0.551774E+10 | 0.164151E+09 | 0.00 | 1.00 | 10-AUG-14:10 | 0.00 | 01-AUG-00:10 | 10155.38 | 16-AUG-14:10 | 10155.38 | 16-AUG-14:10 | 2693.56 | 05-AUG-14:30 | 2608.63 | 16-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.379216E+10 | 0.828488E+09 | 256.42 | 0.377748E+10 | 14678060.71 | 0.00 | 1.00 | 09-SEP-11:40 | 0.00 | 01-SEP-00:05 | 9022.97 | 09-SEP-13:00 | 9022.97 | 09-SEP-13:00 | 471.77 | 01-SEP-12:20 | 2056.38 | 09-SEP-13:00 | 0.00 | 01-SEP-00:05 |
October | 0.319441E+09 | 69124386.88 | 34.83 | 0.319441E+09 | -0.0 | 0.00 | 0.74 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 | 5868.47 | 11-OCT-14:10 | 5868.47 | 11-OCT-14:10 | 0.00 | 11-OCT-14:40 | 1255.84 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 10662026.43 | 2454019.94 | 5.67 | 10662026.43 | 0.00 | 0.00 | 0.19 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 | 1332.96 | 07-NOV-14:00 | 1332.96 | 07-NOV-14:00 | 0.00 | 07-NOV-14:40 | 302.67 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 |
December | 11976.82 | 2853.77 | 0.50 | 11976.82 | 0.00 | 0.00 | 0.00 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 | 19.81 | 02-DEC-15:00 | 19.81 | 02-DEC-15:00 | 0.00 | 02-DEC-15:00 | 4.72 | 02-DEC-15:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.217164E+11 | 0.486626E+10 | 1347.92 | 0.211185E+11 | 0.597886E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.575995E+10 | 0.129910E+10 | 321.39 | 0.551774E+10 | 0.246182E+09 | 0.00 | 1.00 | 0.00 | 15717.06 | 15717.06 | 2693.56 | 3554.13 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 117.75 | 57.61 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 111.65 | 59.97 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 83.20 | 48.17 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 48.82 | 44.21 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 49.12 | 27.69 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 59.21 | 15.10 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 62.23 | 13.51 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 78.01 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 93.16 | 24.37 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.81 | 50.02 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.85 | 55.20 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 105.68 | 65.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 85.05 | 39.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 48.82 | 13.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 117.75 | 65.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 117.75 | 57.61 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 111.65 | 59.97 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 83.20 | 48.17 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 48.82 | 44.21 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 49.12 | 27.69 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 59.21 | 15.10 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 62.23 | 13.51 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 78.01 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 93.16 | 24.37 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.81 | 50.02 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.85 | 55.20 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 105.68 | 65.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 85.05 | 39.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 48.82 | 13.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 117.75 | 65.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 117.75 | 57.61 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 111.65 | 59.97 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 83.20 | 48.17 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 48.82 | 44.21 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 49.12 | 27.69 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 59.21 | 15.10 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 62.23 | 13.51 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 78.01 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 93.16 | 24.37 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.81 | 50.02 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.85 | 55.20 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 105.68 | 65.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 85.05 | 39.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 48.82 | 13.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 117.75 | 65.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 117.75 | 57.61 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 111.65 | 59.97 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 83.20 | 48.17 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 48.82 | 44.21 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 49.12 | 27.69 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 59.21 | 15.10 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 62.23 | 13.51 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 78.01 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 93.16 | 24.37 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.81 | 50.02 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.85 | 55.20 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 105.68 | 65.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 85.05 | 39.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 48.82 | 13.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 117.75 | 65.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.90 | 72.68 | 15.22 | 141.70 | 68.77 | 0.00 | 0.00 | 0.00 |
February | 83.03 | 66.35 | 16.69 | 134.46 | 71.52 | 0.00 | 0.00 | 0.00 |
March | 59.42 | 38.67 | 20.76 | 100.16 | 57.47 | 0.00 | 0.00 | 0.00 |
April | 37.78 | 14.28 | 23.50 | 58.81 | 52.72 | 0.00 | 0.00 | 0.00 |
May | 34.75 | 5.33 | 29.42 | 59.09 | 33.09 | 0.00 | 0.00 | 0.00 |
June | 31.67 | 4.53 | 27.14 | 71.02 | 18.15 | 0.00 | 0.00 | 0.00 |
July | 33.23 | 4.85 | 28.38 | 74.66 | 16.24 | 0.00 | 0.00 | 0.00 |
August | 41.69 | 16.08 | 25.61 | 93.65 | 18.89 | 0.00 | 0.00 | 0.00 |
September | 54.84 | 29.81 | 25.03 | 111.93 | 29.25 | 0.00 | 0.00 | 0.00 |
October | 67.41 | 47.74 | 19.67 | 117.62 | 59.74 | 0.00 | 0.00 | 0.00 |
November | 84.16 | 67.42 | 16.73 | 139.41 | 65.89 | 0.00 | 0.00 | 0.00 |
December | 81.07 | 66.03 | 15.04 | 127.27 | 78.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.94 | 35.98 | 21.96 | 102.30 | 47.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.67 | 4.53 | 15.04 | 58.81 | 16.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.90 | 72.68 | 29.42 | 141.70 | 78.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.90 | 72.68 | 15.22 | 141.70 | 68.77 | 0.00 | 0.00 | 0.00 |
February | 83.03 | 66.35 | 16.69 | 134.46 | 71.52 | 0.00 | 0.00 | 0.00 |
March | 59.42 | 38.67 | 20.76 | 100.16 | 57.47 | 0.00 | 0.00 | 0.00 |
April | 37.78 | 14.28 | 23.50 | 58.81 | 52.72 | 0.00 | 0.00 | 0.00 |
May | 34.75 | 5.33 | 29.42 | 59.09 | 33.09 | 0.00 | 0.00 | 0.00 |
June | 31.67 | 4.53 | 27.14 | 71.02 | 18.15 | 0.00 | 0.00 | 0.00 |
July | 33.23 | 4.85 | 28.38 | 74.66 | 16.24 | 0.00 | 0.00 | 0.00 |
August | 41.69 | 16.08 | 25.61 | 93.65 | 18.89 | 0.00 | 0.00 | 0.00 |
September | 54.84 | 29.81 | 25.03 | 111.93 | 29.25 | 0.00 | 0.00 | 0.00 |
October | 67.41 | 47.74 | 19.67 | 117.62 | 59.74 | 0.00 | 0.00 | 0.00 |
November | 84.16 | 67.42 | 16.73 | 139.41 | 65.89 | 0.00 | 0.00 | 0.00 |
December | 81.07 | 66.03 | 15.04 | 127.27 | 78.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.94 | 35.98 | 21.96 | 102.30 | 47.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.67 | 4.53 | 15.04 | 58.81 | 16.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.90 | 72.68 | 29.42 | 141.70 | 78.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 116.55 | 60.30 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 110.49 | 62.45 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 82.12 | 50.76 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 47.73 | 47.30 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 48.07 | 29.26 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 59.10 | 15.27 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 62.13 | 13.68 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.95 | 15.79 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.95 | 24.70 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.01 | 51.97 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 114.68 | 57.87 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 104.66 | 68.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.30 | 41.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 47.73 | 13.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 116.55 | 68.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 116.55 | 60.30 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 110.49 | 62.45 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 82.12 | 50.76 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 47.73 | 47.30 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 48.07 | 29.26 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 59.10 | 15.27 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 62.13 | 13.68 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.95 | 15.79 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.95 | 24.70 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.01 | 51.97 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 114.68 | 57.87 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 104.66 | 68.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.30 | 41.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 47.73 | 13.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 116.55 | 68.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.90 | 72.68 | 15.22 | 140.28 | 71.97 | 0.00 | 0.00 | 0.00 |
February | 83.03 | 66.35 | 16.69 | 133.10 | 74.45 | 0.00 | 0.00 | 0.00 |
March | 59.42 | 38.67 | 20.76 | 98.89 | 60.54 | 0.00 | 0.00 | 0.00 |
April | 37.78 | 14.28 | 23.50 | 57.53 | 56.38 | 0.00 | 0.00 | 0.00 |
May | 34.75 | 5.33 | 29.42 | 57.84 | 34.96 | 0.00 | 0.00 | 0.00 |
June | 31.67 | 4.53 | 27.14 | 70.89 | 18.36 | 0.00 | 0.00 | 0.00 |
July | 33.23 | 4.85 | 28.38 | 74.54 | 16.45 | 0.00 | 0.00 | 0.00 |
August | 41.69 | 16.08 | 25.61 | 93.58 | 18.97 | 0.00 | 0.00 | 0.00 |
September | 54.84 | 29.81 | 25.03 | 111.69 | 29.64 | 0.00 | 0.00 | 0.00 |
October | 67.41 | 47.74 | 19.67 | 116.69 | 62.05 | 0.00 | 0.00 | 0.00 |
November | 84.16 | 67.42 | 16.73 | 138.04 | 69.04 | 0.00 | 0.00 | 0.00 |
December | 81.07 | 66.03 | 15.04 | 126.09 | 81.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.94 | 35.98 | 21.96 | 101.41 | 49.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.67 | 4.53 | 15.04 | 57.53 | 16.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.90 | 72.68 | 29.42 | 140.28 | 81.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 116.68 | 59.66 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 110.62 | 61.70 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 82.19 | 50.40 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 47.80 | 46.88 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 48.00 | 29.71 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 58.80 | 16.50 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.73 | 14.96 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.76 | 17.15 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.79 | 25.92 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.01 | 52.18 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 114.83 | 57.42 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 104.81 | 67.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.27 | 41.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 47.80 | 14.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 116.68 | 67.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 116.68 | 59.66 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 110.62 | 61.70 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 82.19 | 50.40 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 47.80 | 46.88 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 48.00 | 29.71 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 58.80 | 16.50 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.73 | 14.96 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.76 | 17.15 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.79 | 25.92 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.01 | 52.18 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 114.83 | 57.42 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 104.81 | 67.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.27 | 41.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 47.80 | 14.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 116.68 | 67.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.42 | 72.28 | 15.14 | 139.68 | 70.83 | 0.00 | 0.00 | 0.00 |
February | 82.58 | 65.98 | 16.60 | 132.52 | 73.17 | 0.00 | 0.00 | 0.00 |
March | 59.10 | 38.46 | 20.64 | 98.43 | 59.80 | 0.00 | 0.00 | 0.00 |
April | 37.57 | 14.20 | 23.37 | 57.30 | 55.59 | 0.00 | 0.00 | 0.00 |
May | 34.56 | 5.30 | 29.25 | 57.44 | 35.30 | 0.00 | 0.00 | 0.00 |
June | 31.50 | 4.51 | 26.99 | 70.14 | 19.71 | 0.00 | 0.00 | 0.00 |
July | 33.05 | 4.83 | 28.22 | 73.66 | 17.86 | 0.00 | 0.00 | 0.00 |
August | 41.47 | 15.99 | 25.47 | 92.85 | 20.46 | 0.00 | 0.00 | 0.00 |
September | 54.54 | 29.64 | 24.89 | 110.89 | 30.90 | 0.00 | 0.00 | 0.00 |
October | 67.04 | 47.48 | 19.56 | 116.05 | 61.96 | 0.00 | 0.00 | 0.00 |
November | 83.70 | 67.05 | 16.64 | 137.47 | 68.14 | 0.00 | 0.00 | 0.00 |
December | 80.63 | 65.67 | 14.95 | 125.57 | 80.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.62 | 35.78 | 21.84 | 100.82 | 49.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 4.51 | 14.95 | 57.30 | 17.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.42 | 72.28 | 29.25 | 139.68 | 80.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 116.85 | 59.09 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 110.76 | 61.17 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 82.30 | 49.94 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 47.93 | 46.34 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 48.09 | 29.46 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 58.78 | 16.54 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.70 | 15.03 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.74 | 17.21 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.79 | 25.92 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.07 | 51.86 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.00 | 56.88 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 104.94 | 67.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.35 | 41.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 47.93 | 15.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 116.85 | 67.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 116.85 | 59.09 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 110.76 | 61.17 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 82.30 | 49.94 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 47.93 | 46.34 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 48.09 | 29.46 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 58.78 | 16.54 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.70 | 15.03 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.74 | 17.21 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.79 | 25.92 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.07 | 51.86 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.00 | 56.88 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 104.94 | 67.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.35 | 41.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 47.93 | 15.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 116.85 | 67.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.42 | 72.28 | 15.14 | 139.87 | 70.15 | 0.00 | 0.00 | 0.00 |
February | 82.58 | 65.98 | 16.60 | 132.70 | 72.54 | 0.00 | 0.00 | 0.00 |
March | 59.10 | 38.46 | 20.64 | 98.57 | 59.26 | 0.00 | 0.00 | 0.00 |
April | 37.57 | 14.20 | 23.37 | 57.45 | 54.95 | 0.00 | 0.00 | 0.00 |
May | 34.56 | 5.30 | 29.25 | 57.56 | 35.00 | 0.00 | 0.00 | 0.00 |
June | 31.50 | 4.51 | 26.99 | 70.13 | 19.76 | 0.00 | 0.00 | 0.00 |
July | 33.05 | 4.83 | 28.22 | 73.62 | 17.95 | 0.00 | 0.00 | 0.00 |
August | 41.47 | 15.99 | 25.47 | 92.83 | 20.54 | 0.00 | 0.00 | 0.00 |
September | 54.54 | 29.64 | 24.89 | 110.89 | 30.91 | 0.00 | 0.00 | 0.00 |
October | 67.04 | 47.48 | 19.56 | 116.12 | 61.58 | 0.00 | 0.00 | 0.00 |
November | 83.70 | 67.05 | 16.64 | 137.67 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 80.63 | 65.67 | 14.95 | 125.73 | 79.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.62 | 35.78 | 21.84 | 100.91 | 49.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 4.51 | 14.95 | 57.45 | 17.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.42 | 72.28 | 29.25 | 139.87 | 79.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 117.11 | 58.43 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 110.98 | 60.62 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 82.53 | 49.34 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 48.19 | 45.59 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 48.35 | 28.97 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 58.87 | 16.34 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.78 | 14.85 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.81 | 17.02 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.88 | 25.68 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.25 | 51.31 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.28 | 56.20 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 105.14 | 66.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.53 | 40.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 48.19 | 14.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 117.11 | 66.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 117.11 | 58.43 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 110.98 | 60.62 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 82.53 | 49.34 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 48.19 | 45.59 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 48.35 | 28.97 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 58.87 | 16.34 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.78 | 14.85 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.81 | 17.02 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.88 | 25.68 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.25 | 51.31 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.28 | 56.20 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 105.14 | 66.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.53 | 40.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 48.19 | 14.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 117.11 | 66.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.42 | 72.28 | 15.14 | 140.19 | 69.37 | 0.00 | 0.00 | 0.00 |
February | 82.58 | 65.98 | 16.60 | 132.96 | 71.89 | 0.00 | 0.00 | 0.00 |
March | 59.10 | 38.46 | 20.64 | 98.84 | 58.54 | 0.00 | 0.00 | 0.00 |
April | 37.57 | 14.20 | 23.37 | 57.76 | 54.06 | 0.00 | 0.00 | 0.00 |
May | 34.56 | 5.30 | 29.25 | 57.86 | 34.42 | 0.00 | 0.00 | 0.00 |
June | 31.50 | 4.51 | 26.99 | 70.23 | 19.52 | 0.00 | 0.00 | 0.00 |
July | 33.05 | 4.83 | 28.22 | 73.72 | 17.74 | 0.00 | 0.00 | 0.00 |
August | 41.47 | 15.99 | 25.47 | 92.91 | 20.32 | 0.00 | 0.00 | 0.00 |
September | 54.54 | 29.64 | 24.89 | 111.00 | 30.62 | 0.00 | 0.00 | 0.00 |
October | 67.04 | 47.48 | 19.56 | 116.34 | 60.93 | 0.00 | 0.00 | 0.00 |
November | 83.70 | 67.05 | 16.64 | 138.00 | 66.69 | 0.00 | 0.00 | 0.00 |
December | 80.63 | 65.67 | 14.95 | 125.98 | 78.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.62 | 35.78 | 21.84 | 101.13 | 48.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 4.51 | 14.95 | 57.76 | 17.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.42 | 72.28 | 29.25 | 140.19 | 78.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 117.81 | 56.97 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 111.65 | 59.27 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 83.17 | 47.84 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 48.84 | 43.82 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 48.94 | 27.74 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 58.74 | 15.74 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.62 | 14.32 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.66 | 16.44 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.88 | 25.00 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.76 | 49.94 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.97 | 54.68 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 105.80 | 64.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.92 | 39.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 48.84 | 14.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 117.81 | 64.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 117.81 | 56.97 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 111.65 | 59.27 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 83.17 | 47.84 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 48.84 | 43.82 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 48.94 | 27.74 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 58.74 | 15.74 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.62 | 14.32 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.66 | 16.44 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.88 | 25.00 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.76 | 49.94 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.97 | 54.68 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 105.80 | 64.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.92 | 39.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 48.84 | 14.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 117.81 | 64.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 117.81 | 56.97 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 111.65 | 59.27 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 83.17 | 47.84 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 48.84 | 43.82 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 48.94 | 27.74 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 58.74 | 15.74 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.62 | 14.32 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.66 | 16.44 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.88 | 25.00 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.76 | 49.94 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.97 | 54.68 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 105.80 | 64.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.92 | 39.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 48.84 | 14.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 117.81 | 64.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 117.81 | 56.97 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 111.65 | 59.27 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 83.17 | 47.84 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 48.84 | 43.82 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 48.94 | 27.74 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 58.74 | 15.74 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.62 | 14.32 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.66 | 16.44 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.88 | 25.00 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.76 | 49.94 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.97 | 54.68 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 105.80 | 64.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.92 | 39.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 48.84 | 14.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 117.81 | 64.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.42 | 72.28 | 15.14 | 141.00 | 67.65 | 0.00 | 0.00 | 0.00 |
February | 82.58 | 65.98 | 16.60 | 133.72 | 70.31 | 0.00 | 0.00 | 0.00 |
March | 59.10 | 38.46 | 20.64 | 99.58 | 56.78 | 0.00 | 0.00 | 0.00 |
April | 37.57 | 14.20 | 23.37 | 58.51 | 51.97 | 0.00 | 0.00 | 0.00 |
May | 34.56 | 5.30 | 29.25 | 58.56 | 32.97 | 0.00 | 0.00 | 0.00 |
June | 31.50 | 4.51 | 26.99 | 70.08 | 18.81 | 0.00 | 0.00 | 0.00 |
July | 33.05 | 4.83 | 28.22 | 73.53 | 17.10 | 0.00 | 0.00 | 0.00 |
August | 41.47 | 15.99 | 25.47 | 92.73 | 19.63 | 0.00 | 0.00 | 0.00 |
September | 54.54 | 29.64 | 24.89 | 110.99 | 29.82 | 0.00 | 0.00 | 0.00 |
October | 67.04 | 47.48 | 19.56 | 116.92 | 59.31 | 0.00 | 0.00 | 0.00 |
November | 83.70 | 67.05 | 16.64 | 138.80 | 64.92 | 0.00 | 0.00 | 0.00 |
December | 80.63 | 65.67 | 14.95 | 126.73 | 77.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.62 | 35.78 | 21.84 | 101.58 | 47.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 4.51 | 14.95 | 58.51 | 17.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.42 | 72.28 | 29.25 | 141.00 | 77.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.42 | 72.28 | 15.14 | 141.00 | 67.65 | 0.00 | 0.00 | 0.00 |
February | 82.58 | 65.98 | 16.60 | 133.72 | 70.31 | 0.00 | 0.00 | 0.00 |
March | 59.10 | 38.46 | 20.64 | 99.58 | 56.78 | 0.00 | 0.00 | 0.00 |
April | 37.57 | 14.20 | 23.37 | 58.51 | 51.97 | 0.00 | 0.00 | 0.00 |
May | 34.56 | 5.30 | 29.25 | 58.56 | 32.97 | 0.00 | 0.00 | 0.00 |
June | 31.50 | 4.51 | 26.99 | 70.08 | 18.81 | 0.00 | 0.00 | 0.00 |
July | 33.05 | 4.83 | 28.22 | 73.53 | 17.10 | 0.00 | 0.00 | 0.00 |
August | 41.47 | 15.99 | 25.47 | 92.73 | 19.63 | 0.00 | 0.00 | 0.00 |
September | 54.54 | 29.64 | 24.89 | 110.99 | 29.82 | 0.00 | 0.00 | 0.00 |
October | 67.04 | 47.48 | 19.56 | 116.92 | 59.31 | 0.00 | 0.00 | 0.00 |
November | 83.70 | 67.05 | 16.64 | 138.80 | 64.92 | 0.00 | 0.00 | 0.00 |
December | 80.63 | 65.67 | 14.95 | 126.73 | 77.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.62 | 35.78 | 21.84 | 101.58 | 47.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 4.51 | 14.95 | 58.51 | 17.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.42 | 72.28 | 29.25 | 141.00 | 77.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 117.47 | 57.21 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 111.29 | 59.56 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 82.84 | 48.12 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 48.51 | 44.17 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 48.64 | 27.88 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 58.74 | 15.59 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.62 | 14.18 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.61 | 16.29 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.74 | 24.93 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.41 | 50.25 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.60 | 54.96 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 105.44 | 65.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.67 | 39.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 48.51 | 14.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 117.47 | 65.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 117.47 | 57.21 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 111.29 | 59.56 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 82.84 | 48.12 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 48.51 | 44.17 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 48.64 | 27.88 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 58.74 | 15.59 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.62 | 14.18 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.61 | 16.29 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.74 | 24.93 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.41 | 50.25 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.60 | 54.96 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 105.44 | 65.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.67 | 39.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 48.51 | 14.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 117.47 | 65.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.42 | 72.28 | 15.14 | 140.62 | 67.92 | 0.00 | 0.00 | 0.00 |
February | 82.58 | 65.98 | 16.60 | 133.34 | 70.63 | 0.00 | 0.00 | 0.00 |
March | 59.10 | 38.46 | 20.64 | 99.21 | 57.09 | 0.00 | 0.00 | 0.00 |
April | 37.57 | 14.20 | 23.37 | 58.15 | 52.38 | 0.00 | 0.00 | 0.00 |
May | 34.56 | 5.30 | 29.25 | 58.22 | 33.13 | 0.00 | 0.00 | 0.00 |
June | 31.50 | 4.51 | 26.99 | 70.08 | 18.64 | 0.00 | 0.00 | 0.00 |
July | 33.05 | 4.83 | 28.22 | 73.53 | 16.94 | 0.00 | 0.00 | 0.00 |
August | 41.47 | 15.99 | 25.47 | 92.68 | 19.46 | 0.00 | 0.00 | 0.00 |
September | 54.54 | 29.64 | 24.89 | 110.84 | 29.73 | 0.00 | 0.00 | 0.00 |
October | 67.04 | 47.48 | 19.56 | 116.53 | 59.67 | 0.00 | 0.00 | 0.00 |
November | 83.70 | 67.05 | 16.64 | 138.40 | 65.23 | 0.00 | 0.00 | 0.00 |
December | 80.63 | 65.67 | 14.95 | 126.33 | 77.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.62 | 35.78 | 21.84 | 101.31 | 47.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 4.51 | 14.95 | 58.15 | 16.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.42 | 72.28 | 29.25 | 140.62 | 77.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 117.53 | 57.05 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 111.36 | 59.41 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 82.90 | 47.95 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 48.57 | 44.00 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 48.74 | 27.72 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 58.79 | 15.52 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.66 | 14.12 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.65 | 16.23 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.78 | 24.86 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.46 | 50.12 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.66 | 54.83 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 105.48 | 65.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.73 | 39.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 48.57 | 14.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 117.53 | 65.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 117.53 | 57.05 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 111.36 | 59.41 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 82.90 | 47.95 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 48.57 | 44.00 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 48.74 | 27.72 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 58.79 | 15.52 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.66 | 14.12 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.65 | 16.23 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.78 | 24.86 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.46 | 50.12 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.66 | 54.83 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 105.48 | 65.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.73 | 39.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 48.57 | 14.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 117.53 | 65.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.42 | 72.28 | 15.14 | 140.70 | 67.73 | 0.00 | 0.00 | 0.00 |
February | 82.58 | 65.98 | 16.60 | 133.41 | 70.45 | 0.00 | 0.00 | 0.00 |
March | 59.10 | 38.46 | 20.64 | 99.29 | 56.89 | 0.00 | 0.00 | 0.00 |
April | 37.57 | 14.20 | 23.37 | 58.22 | 52.17 | 0.00 | 0.00 | 0.00 |
May | 34.56 | 5.30 | 29.25 | 58.34 | 32.94 | 0.00 | 0.00 | 0.00 |
June | 31.50 | 4.51 | 26.99 | 70.15 | 18.55 | 0.00 | 0.00 | 0.00 |
July | 33.05 | 4.83 | 28.22 | 73.58 | 16.87 | 0.00 | 0.00 | 0.00 |
August | 41.47 | 15.99 | 25.47 | 92.73 | 19.38 | 0.00 | 0.00 | 0.00 |
September | 54.54 | 29.64 | 24.89 | 110.89 | 29.65 | 0.00 | 0.00 | 0.00 |
October | 67.04 | 47.48 | 19.56 | 116.59 | 59.52 | 0.00 | 0.00 | 0.00 |
November | 83.70 | 67.05 | 16.64 | 138.47 | 65.07 | 0.00 | 0.00 | 0.00 |
December | 80.63 | 65.67 | 14.95 | 126.39 | 77.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.62 | 35.78 | 21.84 | 101.38 | 47.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 4.51 | 14.95 | 58.22 | 16.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.42 | 72.28 | 29.25 | 140.70 | 77.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 117.79 | 56.34 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 111.59 | 58.69 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 83.17 | 47.16 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 48.83 | 43.14 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 49.15 | 27.05 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 58.92 | 15.29 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.76 | 13.93 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.72 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.87 | 24.64 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.68 | 49.51 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.89 | 54.21 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 105.68 | 64.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.94 | 39.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 48.83 | 13.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 117.79 | 64.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 117.79 | 56.34 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 111.59 | 58.69 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 83.17 | 47.16 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 48.83 | 43.14 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 49.15 | 27.05 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 58.92 | 15.29 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.76 | 13.93 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.72 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.87 | 24.64 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 97.68 | 49.51 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 115.89 | 54.21 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 105.68 | 64.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 84.94 | 39.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 48.83 | 13.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 117.79 | 64.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.42 | 72.28 | 15.14 | 141.01 | 66.88 | 0.00 | 0.00 | 0.00 |
February | 82.58 | 65.98 | 16.60 | 133.70 | 69.61 | 0.00 | 0.00 | 0.00 |
March | 59.10 | 38.46 | 20.64 | 99.62 | 55.96 | 0.00 | 0.00 | 0.00 |
April | 37.57 | 14.20 | 23.37 | 58.53 | 51.15 | 0.00 | 0.00 | 0.00 |
May | 34.56 | 5.30 | 29.25 | 58.83 | 32.15 | 0.00 | 0.00 | 0.00 |
June | 31.50 | 4.51 | 26.99 | 70.30 | 18.28 | 0.00 | 0.00 | 0.00 |
July | 33.05 | 4.83 | 28.22 | 73.70 | 16.64 | 0.00 | 0.00 | 0.00 |
August | 41.47 | 15.99 | 25.47 | 92.81 | 19.18 | 0.00 | 0.00 | 0.00 |
September | 54.54 | 29.64 | 24.89 | 110.99 | 29.40 | 0.00 | 0.00 | 0.00 |
October | 67.04 | 47.48 | 19.56 | 116.86 | 58.79 | 0.00 | 0.00 | 0.00 |
November | 83.70 | 67.05 | 16.64 | 138.74 | 64.34 | 0.00 | 0.00 | 0.00 |
December | 80.63 | 65.67 | 14.95 | 126.62 | 76.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.62 | 35.78 | 21.84 | 101.63 | 46.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 4.51 | 14.95 | 58.53 | 16.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.42 | 72.28 | 29.25 | 141.01 | 76.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 118.58 | 53.66 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 112.35 | 55.83 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 83.88 | 44.22 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 49.43 | 40.11 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 50.15 | 24.93 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 59.13 | 14.45 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.93 | 13.19 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.75 | 15.45 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.95 | 23.90 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 98.17 | 47.45 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 116.46 | 52.08 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 106.28 | 62.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 85.43 | 37.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 49.43 | 13.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 118.58 | 62.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.12 | 60.46 | 12.66 | 118.58 | 53.66 | 0.00 | 0.00 | 0.00 |
February | 69.07 | 55.19 | 13.88 | 112.35 | 55.83 | 0.00 | 0.00 | 0.00 |
March | 49.43 | 32.16 | 17.27 | 83.88 | 44.22 | 0.00 | 0.00 | 0.00 |
April | 31.43 | 11.88 | 19.55 | 49.43 | 40.11 | 0.00 | 0.00 | 0.00 |
May | 28.90 | 4.43 | 24.47 | 50.15 | 24.93 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 3.77 | 22.57 | 59.13 | 14.45 | 0.00 | 0.00 | 0.00 |
July | 27.64 | 4.04 | 23.61 | 61.93 | 13.19 | 0.00 | 0.00 | 0.00 |
August | 34.68 | 13.38 | 21.31 | 77.75 | 15.45 | 0.00 | 0.00 | 0.00 |
September | 45.61 | 24.80 | 20.82 | 92.95 | 23.90 | 0.00 | 0.00 | 0.00 |
October | 56.07 | 39.71 | 16.36 | 98.17 | 47.45 | 0.00 | 0.00 | 0.00 |
November | 70.00 | 56.08 | 13.92 | 116.46 | 52.08 | 0.00 | 0.00 | 0.00 |
December | 67.44 | 54.93 | 12.51 | 106.28 | 62.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.20 | 29.93 | 18.27 | 85.43 | 37.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 3.77 | 12.51 | 49.43 | 13.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.12 | 60.46 | 24.47 | 118.58 | 62.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.42 | 72.28 | 15.14 | 141.96 | 63.71 | 0.00 | 0.00 | 0.00 |
February | 82.58 | 65.98 | 16.60 | 134.60 | 66.21 | 0.00 | 0.00 | 0.00 |
March | 59.10 | 38.46 | 20.64 | 100.47 | 52.48 | 0.00 | 0.00 | 0.00 |
April | 37.57 | 14.20 | 23.37 | 59.25 | 47.56 | 0.00 | 0.00 | 0.00 |
May | 34.56 | 5.30 | 29.25 | 60.02 | 29.64 | 0.00 | 0.00 | 0.00 |
June | 31.50 | 4.51 | 26.99 | 70.56 | 17.29 | 0.00 | 0.00 | 0.00 |
July | 33.05 | 4.83 | 28.22 | 73.91 | 15.77 | 0.00 | 0.00 | 0.00 |
August | 41.47 | 15.99 | 25.47 | 92.85 | 18.46 | 0.00 | 0.00 | 0.00 |
September | 54.54 | 29.64 | 24.89 | 111.09 | 28.53 | 0.00 | 0.00 | 0.00 |
October | 67.04 | 47.48 | 19.56 | 117.44 | 56.35 | 0.00 | 0.00 | 0.00 |
November | 83.70 | 67.05 | 16.64 | 139.42 | 61.81 | 0.00 | 0.00 | 0.00 |
December | 80.63 | 65.67 | 14.95 | 127.34 | 73.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.62 | 35.78 | 21.84 | 102.23 | 44.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 4.51 | 14.95 | 59.25 | 15.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.42 | 72.28 | 29.25 | 141.96 | 73.54 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.315392E+09 | 0.154294E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.270102E+09 | 0.145076E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.222841E+09 | 0.129012E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.126533E+09 | 0.114586E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.131556E+09 | 74159669.59 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.153461E+09 | 39128581.41 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.166688E+09 | 36178564.89 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208947E+09 | 42104889.20 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.241476E+09 | 63174628.00 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.261966E+09 | 0.133967E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.300281E+09 | 0.143090E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.283046E+09 | 0.176566E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.268229E+10 | 0.125134E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.126533E+09 | 36178564.89 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.315392E+09 | 0.176566E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.315392E+09 | 0.154294E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.270102E+09 | 0.145076E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.222841E+09 | 0.129012E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.126533E+09 | 0.114586E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.131556E+09 | 74159669.59 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.153461E+09 | 39128581.41 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.166688E+09 | 36178564.89 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208947E+09 | 42104889.20 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.241476E+09 | 63174628.00 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.261966E+09 | 0.133967E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.300281E+09 | 0.143090E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.283046E+09 | 0.176566E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.268229E+10 | 0.125134E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.126533E+09 | 36178564.89 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.315392E+09 | 0.176566E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.315392E+09 | 0.154294E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.270102E+09 | 0.145076E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.222841E+09 | 0.129012E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.126533E+09 | 0.114586E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.131556E+09 | 74159669.59 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.153461E+09 | 39128581.41 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.166688E+09 | 36178564.89 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208947E+09 | 42104889.20 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.241476E+09 | 63174628.00 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.261966E+09 | 0.133967E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.300281E+09 | 0.143090E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.283046E+09 | 0.176566E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.268229E+10 | 0.125134E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.126533E+09 | 36178564.89 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.315392E+09 | 0.176566E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.315392E+09 | 0.154294E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.270102E+09 | 0.145076E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.222841E+09 | 0.129012E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.126533E+09 | 0.114586E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.131556E+09 | 74159669.59 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.153461E+09 | 39128581.41 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.166688E+09 | 36178564.89 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208947E+09 | 42104889.20 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.241476E+09 | 63174628.00 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.261966E+09 | 0.133967E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.300281E+09 | 0.143090E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.283046E+09 | 0.176566E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.268229E+10 | 0.125134E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.126533E+09 | 36178564.89 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.315392E+09 | 0.176566E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.235442E+09 | 0.194672E+09 | 40770450.51 | 0.379536E+09 | 0.184202E+09 |
February | 0.200874E+09 | 0.160506E+09 | 40368493.78 | 0.325277E+09 | 0.173009E+09 |
March | 0.159160E+09 | 0.103564E+09 | 55595844.31 | 0.268279E+09 | 0.153936E+09 |
April | 97922187.96 | 37012519.66 | 60909668.31 | 0.152432E+09 | 0.136651E+09 |
May | 93062866.84 | 14277140.30 | 78785726.54 | 0.158261E+09 | 88638725.21 |
June | 82090701.13 | 11751213.54 | 70339487.58 | 0.184074E+09 | 47043576.40 |
July | 89004801.18 | 12999743.80 | 76005057.38 | 0.199964E+09 | 43488257.47 |
August | 0.111674E+09 | 43073345.63 | 68600952.26 | 0.250845E+09 | 50588137.72 |
September | 0.142134E+09 | 77261282.07 | 64873191.88 | 0.290125E+09 | 75806457.95 |
October | 0.180539E+09 | 0.127863E+09 | 52676289.77 | 0.315028E+09 | 0.160009E+09 |
November | 0.218133E+09 | 0.174760E+09 | 43373458.81 | 0.361355E+09 | 0.170797E+09 |
December | 0.217136E+09 | 0.176864E+09 | 40272569.37 | 0.340892E+09 | 0.210559E+09 |
Annual Sum or Average | 0.182717E+10 | 0.113460E+10 | 0.692571E+09 | 0.322607E+10 | 0.149473E+10 |
Minimum of Months | 82090701.13 | 11751213.54 | 40272569.37 | 0.152432E+09 | 43488257.47 |
Maximum of Months | 0.235442E+09 | 0.194672E+09 | 78785726.54 | 0.379536E+09 | 0.210559E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.235442E+09 | 0.194672E+09 | 40770450.51 | 0.379536E+09 | 0.184202E+09 |
February | 0.200874E+09 | 0.160506E+09 | 40368493.78 | 0.325277E+09 | 0.173009E+09 |
March | 0.159160E+09 | 0.103564E+09 | 55595844.31 | 0.268279E+09 | 0.153936E+09 |
April | 97922187.96 | 37012519.66 | 60909668.31 | 0.152432E+09 | 0.136651E+09 |
May | 93062866.84 | 14277140.30 | 78785726.54 | 0.158261E+09 | 88638725.21 |
June | 82090701.13 | 11751213.54 | 70339487.58 | 0.184074E+09 | 47043576.40 |
July | 89004801.18 | 12999743.80 | 76005057.38 | 0.199964E+09 | 43488257.47 |
August | 0.111674E+09 | 43073345.63 | 68600952.26 | 0.250845E+09 | 50588137.72 |
September | 0.142134E+09 | 77261282.07 | 64873191.88 | 0.290125E+09 | 75806457.95 |
October | 0.180539E+09 | 0.127863E+09 | 52676289.77 | 0.315028E+09 | 0.160009E+09 |
November | 0.218133E+09 | 0.174760E+09 | 43373458.81 | 0.361355E+09 | 0.170797E+09 |
December | 0.217136E+09 | 0.176864E+09 | 40272569.37 | 0.340892E+09 | 0.210559E+09 |
Annual Sum or Average | 0.182717E+10 | 0.113460E+10 | 0.692571E+09 | 0.322607E+10 | 0.149473E+10 |
Minimum of Months | 82090701.13 | 11751213.54 | 40272569.37 | 0.152432E+09 | 43488257.47 |
Maximum of Months | 0.235442E+09 | 0.194672E+09 | 78785726.54 | 0.379536E+09 | 0.210559E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.312164E+09 | 0.161510E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.267294E+09 | 0.151081E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.219947E+09 | 0.135944E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.123725E+09 | 0.122603E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.128751E+09 | 78381530.36 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.153182E+09 | 39574303.22 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.166415E+09 | 36640703.35 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208772E+09 | 42291112.00 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240916E+09 | 64017651.61 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.259839E+09 | 0.139195E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.297250E+09 | 0.149987E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.280335E+09 | 0.183232E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.265859E+10 | 0.130446E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.123725E+09 | 36640703.35 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.312164E+09 | 0.183232E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.312164E+09 | 0.161510E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.267294E+09 | 0.151081E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.219947E+09 | 0.135944E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.123725E+09 | 0.122603E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.128751E+09 | 78381530.36 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.153182E+09 | 39574303.22 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.166415E+09 | 36640703.35 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208772E+09 | 42291112.00 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240916E+09 | 64017651.61 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.259839E+09 | 0.139195E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.297250E+09 | 0.149987E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.280335E+09 | 0.183232E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.265859E+10 | 0.130446E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.123725E+09 | 36640703.35 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.312164E+09 | 0.183232E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.235442E+09 | 0.194672E+09 | 40770450.51 | 0.375733E+09 | 0.192753E+09 |
February | 0.200874E+09 | 0.160506E+09 | 40368493.78 | 0.321985E+09 | 0.180113E+09 |
March | 0.159160E+09 | 0.103564E+09 | 55595844.31 | 0.264866E+09 | 0.162151E+09 |
April | 97922187.96 | 37012519.66 | 60909668.31 | 0.149106E+09 | 0.146146E+09 |
May | 93062866.84 | 14277140.30 | 78785726.54 | 0.154923E+09 | 93643165.87 |
June | 82090701.13 | 11751213.54 | 70339487.58 | 0.183740E+09 | 47588520.73 |
July | 89004801.18 | 12999743.80 | 76005057.38 | 0.199637E+09 | 44052413.36 |
August | 0.111674E+09 | 43073345.63 | 68600952.26 | 0.250654E+09 | 50820006.23 |
September | 0.142134E+09 | 77261282.07 | 64873191.88 | 0.289490E+09 | 76814184.28 |
October | 0.180539E+09 | 0.127863E+09 | 52676289.77 | 0.312545E+09 | 0.166193E+09 |
November | 0.218133E+09 | 0.174760E+09 | 43373458.81 | 0.357806E+09 | 0.178953E+09 |
December | 0.217136E+09 | 0.176864E+09 | 40272569.37 | 0.337726E+09 | 0.218432E+09 |
Annual Sum or Average | 0.182717E+10 | 0.113460E+10 | 0.692571E+09 | 0.319821E+10 | 0.155766E+10 |
Minimum of Months | 82090701.13 | 11751213.54 | 40272569.37 | 0.149106E+09 | 44052413.36 |
Maximum of Months | 0.235442E+09 | 0.194672E+09 | 78785726.54 | 0.375733E+09 | 0.218432E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.312529E+09 | 0.159799E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.267605E+09 | 0.149262E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.220125E+09 | 0.134983E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.123910E+09 | 0.121516E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.128567E+09 | 79584454.72 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.152400E+09 | 42761553.44 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165339E+09 | 40072566.36 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208262E+09 | 45922519.96 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240518E+09 | 67172139.34 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.259837E+09 | 0.139767E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.297647E+09 | 0.148820E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.280714E+09 | 0.181043E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.265745E+10 | 0.131070E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.123910E+09 | 40072566.36 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.312529E+09 | 0.181043E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.312529E+09 | 0.159799E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.267605E+09 | 0.149262E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.220125E+09 | 0.134983E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.123910E+09 | 0.121516E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.128567E+09 | 79584454.72 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.152400E+09 | 42761553.44 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165339E+09 | 40072566.36 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208262E+09 | 45922519.96 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240518E+09 | 67172139.34 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.259837E+09 | 0.139767E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.297647E+09 | 0.148820E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.280714E+09 | 0.181043E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.265745E+10 | 0.131070E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.123910E+09 | 40072566.36 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.312529E+09 | 0.181043E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234156E+09 | 0.193608E+09 | 40547661.16 | 0.374122E+09 | 0.189707E+09 |
February | 0.199776E+09 | 0.159629E+09 | 40147900.92 | 0.320604E+09 | 0.177015E+09 |
March | 0.158290E+09 | 0.102998E+09 | 55292041.89 | 0.263634E+09 | 0.160156E+09 |
April | 97387094.04 | 36810265.45 | 60576828.59 | 0.148512E+09 | 0.144090E+09 |
May | 92554326.58 | 14199123.13 | 78355203.44 | 0.153858E+09 | 94550037.19 |
June | 81642118.06 | 11686999.26 | 69955118.80 | 0.181815E+09 | 51076752.56 |
July | 88518436.14 | 12928706.94 | 75589729.20 | 0.197283E+09 | 47849415.26 |
August | 0.111064E+09 | 42837972.16 | 68226083.67 | 0.248681E+09 | 54812324.35 |
September | 0.141358E+09 | 76839089.28 | 64518693.56 | 0.287439E+09 | 80103200.91 |
October | 0.179553E+09 | 0.127164E+09 | 52388441.19 | 0.310833E+09 | 0.165964E+09 |
November | 0.216941E+09 | 0.173805E+09 | 43136445.37 | 0.356326E+09 | 0.176619E+09 |
December | 0.215950E+09 | 0.175897E+09 | 40052500.69 | 0.336339E+09 | 0.214692E+09 |
Annual Sum or Average | 0.181719E+10 | 0.112840E+10 | 0.688787E+09 | 0.317945E+10 | 0.155663E+10 |
Minimum of Months | 81642118.06 | 11686999.26 | 40052500.69 | 0.148512E+09 | 47849415.26 |
Maximum of Months | 0.234156E+09 | 0.193608E+09 | 78355203.44 | 0.374122E+09 | 0.214692E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.312961E+09 | 0.158276E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.267959E+09 | 0.147976E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.220441E+09 | 0.133769E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.124234E+09 | 0.120123E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.128817E+09 | 78911962.15 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.152362E+09 | 42874215.55 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165267E+09 | 40257726.69 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208217E+09 | 46087764.68 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240513E+09 | 67185207.64 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.260000E+09 | 0.138913E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.298075E+09 | 0.147438E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.281063E+09 | 0.179549E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.265991E+10 | 0.130136E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.124234E+09 | 40257726.69 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.312961E+09 | 0.179549E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.312961E+09 | 0.158276E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.267959E+09 | 0.147976E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.220441E+09 | 0.133769E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.124234E+09 | 0.120123E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.128817E+09 | 78911962.15 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.152362E+09 | 42874215.55 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165267E+09 | 40257726.69 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208217E+09 | 46087764.68 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240513E+09 | 67185207.64 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.260000E+09 | 0.138913E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.298075E+09 | 0.147438E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.281063E+09 | 0.179549E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.265991E+10 | 0.130136E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.124234E+09 | 40257726.69 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.312961E+09 | 0.179549E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234156E+09 | 0.193608E+09 | 40547661.16 | 0.374641E+09 | 0.187897E+09 |
February | 0.199776E+09 | 0.159629E+09 | 40147900.92 | 0.321028E+09 | 0.175489E+09 |
March | 0.158290E+09 | 0.102998E+09 | 55292041.89 | 0.264014E+09 | 0.158715E+09 |
April | 97387094.04 | 36810265.45 | 60576828.59 | 0.148902E+09 | 0.142437E+09 |
May | 92554326.58 | 14199123.13 | 78355203.44 | 0.154160E+09 | 93754418.66 |
June | 81642118.06 | 11686999.26 | 69955118.80 | 0.181769E+09 | 51210474.50 |
July | 88518436.14 | 12928706.94 | 75589729.20 | 0.197196E+09 | 48068913.25 |
August | 0.111064E+09 | 42837972.16 | 68226083.67 | 0.248627E+09 | 55008322.84 |
September | 0.141358E+09 | 76839089.28 | 64518693.56 | 0.287432E+09 | 80118690.31 |
October | 0.179553E+09 | 0.127164E+09 | 52388441.19 | 0.311029E+09 | 0.164948E+09 |
November | 0.216941E+09 | 0.173805E+09 | 43136445.37 | 0.356839E+09 | 0.174976E+09 |
December | 0.215950E+09 | 0.175897E+09 | 40052500.69 | 0.336758E+09 | 0.212919E+09 |
Annual Sum or Average | 0.181719E+10 | 0.112840E+10 | 0.688787E+09 | 0.318240E+10 | 0.154554E+10 |
Minimum of Months | 81642118.06 | 11686999.26 | 40052500.69 | 0.148902E+09 | 48068913.25 |
Maximum of Months | 0.234156E+09 | 0.193608E+09 | 78355203.44 | 0.374641E+09 | 0.212919E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.313669E+09 | 0.156501E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.268487E+09 | 0.146644E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.221050E+09 | 0.132149E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.124902E+09 | 0.118162E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.129500E+09 | 77591506.93 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.152592E+09 | 42359488.59 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165473E+09 | 39782089.40 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208399E+09 | 45583162.47 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240738E+09 | 66555101.92 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.260485E+09 | 0.137423E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.298794E+09 | 0.145662E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.281611E+09 | 0.177976E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.266570E+10 | 0.128639E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.124902E+09 | 39782089.40 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.313669E+09 | 0.177976E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.313669E+09 | 0.156501E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.268487E+09 | 0.146644E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.221050E+09 | 0.132149E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.124902E+09 | 0.118162E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.129500E+09 | 77591506.93 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.152592E+09 | 42359488.59 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165473E+09 | 39782089.40 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208399E+09 | 45583162.47 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240738E+09 | 66555101.92 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.260485E+09 | 0.137423E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.298794E+09 | 0.145662E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.281611E+09 | 0.177976E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.266570E+10 | 0.128639E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.124902E+09 | 39782089.40 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.313669E+09 | 0.177976E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234156E+09 | 0.193608E+09 | 40547661.16 | 0.375490E+09 | 0.185791E+09 |
February | 0.199776E+09 | 0.159629E+09 | 40147900.92 | 0.321662E+09 | 0.173910E+09 |
March | 0.158290E+09 | 0.102998E+09 | 55292041.89 | 0.264746E+09 | 0.156794E+09 |
April | 97387094.04 | 36810265.45 | 60576828.59 | 0.149702E+09 | 0.140112E+09 |
May | 92554326.58 | 14199123.13 | 78355203.44 | 0.154982E+09 | 92193922.47 |
June | 81642118.06 | 11686999.26 | 69955118.80 | 0.182046E+09 | 50603338.51 |
July | 88518436.14 | 12928706.94 | 75589729.20 | 0.197444E+09 | 47508787.37 |
August | 0.111064E+09 | 42837972.16 | 68226083.67 | 0.248847E+09 | 54413332.95 |
September | 0.141358E+09 | 76839089.28 | 64518693.56 | 0.287703E+09 | 79375063.58 |
October | 0.179553E+09 | 0.127164E+09 | 52388441.19 | 0.311610E+09 | 0.163182E+09 |
November | 0.216941E+09 | 0.173805E+09 | 43136445.37 | 0.357699E+09 | 0.172868E+09 |
December | 0.215950E+09 | 0.175897E+09 | 40052500.69 | 0.337414E+09 | 0.211055E+09 |
Annual Sum or Average | 0.181719E+10 | 0.112840E+10 | 0.688787E+09 | 0.318935E+10 | 0.152781E+10 |
Minimum of Months | 81642118.06 | 11686999.26 | 40052500.69 | 0.149702E+09 | 47508787.37 |
Maximum of Months | 0.234156E+09 | 0.193608E+09 | 78355203.44 | 0.375490E+09 | 0.211055E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.315544E+09 | 0.152583E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.270100E+09 | 0.143390E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.222764E+09 | 0.128138E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.126584E+09 | 0.113572E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.131094E+09 | 74296774.49 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.152252E+09 | 40801344.65 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165051E+09 | 38355562.65 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208000E+09 | 44032753.02 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240753E+09 | 64805878.21 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.261845E+09 | 0.133749E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.300599E+09 | 0.141742E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.283385E+09 | 0.174068E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.267797E+10 | 0.124954E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.126584E+09 | 38355562.65 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.315544E+09 | 0.174068E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.315544E+09 | 0.152583E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.270100E+09 | 0.143390E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.222764E+09 | 0.128138E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.126584E+09 | 0.113572E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.131094E+09 | 74296774.49 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.152252E+09 | 40801344.65 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165051E+09 | 38355562.65 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208000E+09 | 44032753.02 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240753E+09 | 64805878.21 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.261845E+09 | 0.133749E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.300599E+09 | 0.141742E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.283385E+09 | 0.174068E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.267797E+10 | 0.124954E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.126584E+09 | 38355562.65 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.315544E+09 | 0.174068E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.315544E+09 | 0.152583E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.270100E+09 | 0.143390E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.222764E+09 | 0.128138E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.126584E+09 | 0.113572E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.131094E+09 | 74296774.49 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.152252E+09 | 40801344.65 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165051E+09 | 38355562.65 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208000E+09 | 44032753.02 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240753E+09 | 64805878.21 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.261845E+09 | 0.133749E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.300599E+09 | 0.141742E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.283385E+09 | 0.174068E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.267797E+10 | 0.124954E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.126584E+09 | 38355562.65 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.315544E+09 | 0.174068E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.315544E+09 | 0.152583E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.270100E+09 | 0.143390E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.222764E+09 | 0.128138E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.126584E+09 | 0.113572E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.131094E+09 | 74296774.49 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.152252E+09 | 40801344.65 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165051E+09 | 38355562.65 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208000E+09 | 44032753.02 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240753E+09 | 64805878.21 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.261845E+09 | 0.133749E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.300599E+09 | 0.141742E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.283385E+09 | 0.174068E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.267797E+10 | 0.124954E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.126584E+09 | 38355562.65 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.315544E+09 | 0.174068E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234156E+09 | 0.193608E+09 | 40547661.16 | 0.377652E+09 | 0.181185E+09 |
February | 0.199776E+09 | 0.159629E+09 | 40147900.92 | 0.323503E+09 | 0.170095E+09 |
March | 0.158290E+09 | 0.102998E+09 | 55292041.89 | 0.266728E+09 | 0.152082E+09 |
April | 97387094.04 | 36810265.45 | 60576828.59 | 0.151666E+09 | 0.134718E+09 |
May | 92554326.58 | 14199123.13 | 78355203.44 | 0.156857E+09 | 88314038.20 |
June | 81642118.06 | 11686999.26 | 69955118.80 | 0.181652E+09 | 48751377.94 |
July | 88518436.14 | 12928706.94 | 75589729.20 | 0.196947E+09 | 45812714.58 |
August | 0.111064E+09 | 42837972.16 | 68226083.67 | 0.248364E+09 | 52571741.03 |
September | 0.141358E+09 | 76839089.28 | 64518693.56 | 0.287696E+09 | 77302906.05 |
October | 0.179553E+09 | 0.127164E+09 | 52388441.19 | 0.313171E+09 | 0.158864E+09 |
November | 0.216941E+09 | 0.173805E+09 | 43136445.37 | 0.359772E+09 | 0.168263E+09 |
December | 0.215950E+09 | 0.175897E+09 | 40052500.69 | 0.339442E+09 | 0.206477E+09 |
Annual Sum or Average | 0.181719E+10 | 0.112840E+10 | 0.688787E+09 | 0.320345E+10 | 0.148444E+10 |
Minimum of Months | 81642118.06 | 11686999.26 | 40052500.69 | 0.151666E+09 | 45812714.58 |
Maximum of Months | 0.234156E+09 | 0.193608E+09 | 78355203.44 | 0.377652E+09 | 0.206477E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234156E+09 | 0.193608E+09 | 40547661.16 | 0.377652E+09 | 0.181185E+09 |
February | 0.199776E+09 | 0.159629E+09 | 40147900.92 | 0.323503E+09 | 0.170095E+09 |
March | 0.158290E+09 | 0.102998E+09 | 55292041.89 | 0.266728E+09 | 0.152082E+09 |
April | 97387094.04 | 36810265.45 | 60576828.59 | 0.151666E+09 | 0.134718E+09 |
May | 92554326.58 | 14199123.13 | 78355203.44 | 0.156857E+09 | 88314038.20 |
June | 81642118.06 | 11686999.26 | 69955118.80 | 0.181652E+09 | 48751377.94 |
July | 88518436.14 | 12928706.94 | 75589729.20 | 0.196947E+09 | 45812714.58 |
August | 0.111064E+09 | 42837972.16 | 68226083.67 | 0.248364E+09 | 52571741.03 |
September | 0.141358E+09 | 76839089.28 | 64518693.56 | 0.287696E+09 | 77302906.05 |
October | 0.179553E+09 | 0.127164E+09 | 52388441.19 | 0.313171E+09 | 0.158864E+09 |
November | 0.216941E+09 | 0.173805E+09 | 43136445.37 | 0.359772E+09 | 0.168263E+09 |
December | 0.215950E+09 | 0.175897E+09 | 40052500.69 | 0.339442E+09 | 0.206477E+09 |
Annual Sum or Average | 0.181719E+10 | 0.112840E+10 | 0.688787E+09 | 0.320345E+10 | 0.148444E+10 |
Minimum of Months | 81642118.06 | 11686999.26 | 40052500.69 | 0.151666E+09 | 45812714.58 |
Maximum of Months | 0.234156E+09 | 0.193608E+09 | 78355203.44 | 0.377652E+09 | 0.206477E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.314620E+09 | 0.153244E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.269242E+09 | 0.144081E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.221871E+09 | 0.128882E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.125745E+09 | 0.114492E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.130274E+09 | 74667681.68 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.152249E+09 | 40420693.54 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165033E+09 | 37985820.12 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.207866E+09 | 43637118.44 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240387E+09 | 64606002.43 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.260900E+09 | 0.134581E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.299644E+09 | 0.142469E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.282405E+09 | 0.175027E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.267024E+10 | 0.125409E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.125745E+09 | 37985820.12 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.314620E+09 | 0.175027E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.314620E+09 | 0.153244E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.269242E+09 | 0.144081E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.221871E+09 | 0.128882E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.125745E+09 | 0.114492E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.130274E+09 | 74667681.68 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.152249E+09 | 40420693.54 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165033E+09 | 37985820.12 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.207866E+09 | 43637118.44 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240387E+09 | 64606002.43 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.260900E+09 | 0.134581E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.299644E+09 | 0.142469E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.282405E+09 | 0.175027E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.267024E+10 | 0.125409E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.125745E+09 | 37985820.12 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.314620E+09 | 0.175027E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234156E+09 | 0.193608E+09 | 40547661.16 | 0.376636E+09 | 0.181923E+09 |
February | 0.199776E+09 | 0.159629E+09 | 40147900.92 | 0.322569E+09 | 0.170869E+09 |
March | 0.158290E+09 | 0.102998E+09 | 55292041.89 | 0.265736E+09 | 0.152920E+09 |
April | 97387094.04 | 36810265.45 | 60576828.59 | 0.150718E+09 | 0.135763E+09 |
May | 92554326.58 | 14199123.13 | 78355203.44 | 0.155925E+09 | 88736576.10 |
June | 81642118.06 | 11686999.26 | 69955118.80 | 0.181658E+09 | 48309594.39 |
July | 88518436.14 | 12928706.94 | 75589729.20 | 0.196939E+09 | 45382270.62 |
August | 0.111064E+09 | 42837972.16 | 68226083.67 | 0.248234E+09 | 52110517.10 |
September | 0.141358E+09 | 76839089.28 | 64518693.56 | 0.287307E+09 | 77070651.93 |
October | 0.179553E+09 | 0.127164E+09 | 52388441.19 | 0.312117E+09 | 0.159810E+09 |
November | 0.216941E+09 | 0.173805E+09 | 43136445.37 | 0.358722E+09 | 0.169078E+09 |
December | 0.215950E+09 | 0.175897E+09 | 40052500.69 | 0.338366E+09 | 0.207556E+09 |
Annual Sum or Average | 0.181719E+10 | 0.112840E+10 | 0.688787E+09 | 0.319493E+10 | 0.148953E+10 |
Minimum of Months | 81642118.06 | 11686999.26 | 40052500.69 | 0.150718E+09 | 45382270.62 |
Maximum of Months | 0.234156E+09 | 0.193608E+09 | 78355203.44 | 0.376636E+09 | 0.207556E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.314797E+09 | 0.152811E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.269391E+09 | 0.143719E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.222048E+09 | 0.128424E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.125902E+09 | 0.114037E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.130555E+09 | 74240757.12 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.152390E+09 | 40221067.72 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165157E+09 | 37809847.37 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.207968E+09 | 43464928.37 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240480E+09 | 64428931.85 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.261031E+09 | 0.134248E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.299798E+09 | 0.142109E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.282528E+09 | 0.174680E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.267205E+10 | 0.125019E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.125902E+09 | 37809847.37 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.314797E+09 | 0.174680E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.314797E+09 | 0.152811E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.269391E+09 | 0.143719E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.222048E+09 | 0.128424E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.125902E+09 | 0.114037E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.130555E+09 | 74240757.12 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.152390E+09 | 40221067.72 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165157E+09 | 37809847.37 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.207968E+09 | 43464928.37 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240480E+09 | 64428931.85 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.261031E+09 | 0.134248E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.299798E+09 | 0.142109E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.282528E+09 | 0.174680E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.267205E+10 | 0.125019E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.125902E+09 | 37809847.37 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.314797E+09 | 0.174680E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234156E+09 | 0.193608E+09 | 40547661.16 | 0.376849E+09 | 0.181409E+09 |
February | 0.199776E+09 | 0.159629E+09 | 40147900.92 | 0.322748E+09 | 0.170438E+09 |
March | 0.158290E+09 | 0.102998E+09 | 55292041.89 | 0.265950E+09 | 0.152377E+09 |
April | 97387094.04 | 36810265.45 | 60576828.59 | 0.150906E+09 | 0.135224E+09 |
May | 92554326.58 | 14199123.13 | 78355203.44 | 0.156262E+09 | 88230337.96 |
June | 81642118.06 | 11686999.26 | 69955118.80 | 0.181829E+09 | 48072586.40 |
July | 88518436.14 | 12928706.94 | 75589729.20 | 0.197089E+09 | 45173448.39 |
August | 0.111064E+09 | 42837972.16 | 68226083.67 | 0.248358E+09 | 51906457.24 |
September | 0.141358E+09 | 76839089.28 | 64518693.56 | 0.287419E+09 | 76860728.80 |
October | 0.179553E+09 | 0.127164E+09 | 52388441.19 | 0.312274E+09 | 0.159414E+09 |
November | 0.216941E+09 | 0.173805E+09 | 43136445.37 | 0.358907E+09 | 0.168650E+09 |
December | 0.215950E+09 | 0.175897E+09 | 40052500.69 | 0.338514E+09 | 0.207145E+09 |
Annual Sum or Average | 0.181719E+10 | 0.112840E+10 | 0.688787E+09 | 0.319710E+10 | 0.148490E+10 |
Minimum of Months | 81642118.06 | 11686999.26 | 40052500.69 | 0.150906E+09 | 45173448.39 |
Maximum of Months | 0.234156E+09 | 0.193608E+09 | 78355203.44 | 0.376849E+09 | 0.207145E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.315492E+09 | 0.150892E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.269970E+09 | 0.141995E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.222764E+09 | 0.126312E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.126570E+09 | 0.111809E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.131651E+09 | 72449599.12 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.152713E+09 | 39638413.40 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165425E+09 | 37303483.65 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208153E+09 | 43018272.69 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240709E+09 | 63870420.99 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.261638E+09 | 0.132595E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.300396E+09 | 0.140514E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.283057E+09 | 0.172923E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.267854E+10 | 0.123332E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.126570E+09 | 37303483.65 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.315492E+09 | 0.172923E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.315492E+09 | 0.150892E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.269970E+09 | 0.141995E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.222764E+09 | 0.126312E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.126570E+09 | 0.111809E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.131651E+09 | 72449599.12 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.152713E+09 | 39638413.40 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165425E+09 | 37303483.65 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208153E+09 | 43018272.69 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240709E+09 | 63870420.99 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.261638E+09 | 0.132595E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.300396E+09 | 0.140514E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.283057E+09 | 0.172923E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.267854E+10 | 0.123332E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.126570E+09 | 37303483.65 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.315492E+09 | 0.172923E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234156E+09 | 0.193608E+09 | 40547661.16 | 0.377686E+09 | 0.179133E+09 |
February | 0.199776E+09 | 0.159629E+09 | 40147900.92 | 0.323443E+09 | 0.168392E+09 |
March | 0.158290E+09 | 0.102998E+09 | 55292041.89 | 0.266811E+09 | 0.149874E+09 |
April | 97387094.04 | 36810265.45 | 60576828.59 | 0.151708E+09 | 0.132584E+09 |
May | 92554326.58 | 14199123.13 | 78355203.44 | 0.157573E+09 | 86112719.22 |
June | 81642118.06 | 11686999.26 | 69955118.80 | 0.182216E+09 | 47384225.75 |
July | 88518436.14 | 12928706.94 | 75589729.20 | 0.197410E+09 | 44576455.73 |
August | 0.111064E+09 | 42837972.16 | 68226083.67 | 0.248581E+09 | 51380168.79 |
September | 0.141358E+09 | 76839089.28 | 64518693.56 | 0.287694E+09 | 76201824.34 |
October | 0.179553E+09 | 0.127164E+09 | 52388441.19 | 0.313000E+09 | 0.157456E+09 |
November | 0.216941E+09 | 0.173805E+09 | 43136445.37 | 0.359624E+09 | 0.166759E+09 |
December | 0.215950E+09 | 0.175897E+09 | 40052500.69 | 0.339150E+09 | 0.205063E+09 |
Annual Sum or Average | 0.181719E+10 | 0.112840E+10 | 0.688787E+09 | 0.320490E+10 | 0.146491E+10 |
Minimum of Months | 81642118.06 | 11686999.26 | 40052500.69 | 0.151708E+09 | 44576455.73 |
Maximum of Months | 0.234156E+09 | 0.193608E+09 | 78355203.44 | 0.377686E+09 | 0.205063E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.317604E+09 | 0.143733E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.271786E+09 | 0.135069E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.224668E+09 | 0.118444E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.128119E+09 | 0.103956E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.134320E+09 | 66765245.40 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.153275E+09 | 37454831.01 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165883E+09 | 35323534.81 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208241E+09 | 41381851.45 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240920E+09 | 61953332.24 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.262940E+09 | 0.127083E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.301857E+09 | 0.134997E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.284652E+09 | 0.166092E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.269426E+10 | 0.117225E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.128119E+09 | 35323534.81 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.317604E+09 | 0.166092E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195850E+09 | 0.161936E+09 | 33914500.28 | 0.317604E+09 | 0.143733E+09 |
February | 0.167095E+09 | 0.133515E+09 | 33580136.51 | 0.271786E+09 | 0.135069E+09 |
March | 0.132396E+09 | 86148749.63 | 46246859.04 | 0.224668E+09 | 0.118444E+09 |
April | 81455613.81 | 30788502.28 | 50667111.53 | 0.128119E+09 | 0.103956E+09 |
May | 77413435.08 | 11876299.44 | 65537135.64 | 0.134320E+09 | 66765245.40 |
June | 68286346.41 | 9775131.99 | 58511214.42 | 0.153275E+09 | 37454831.01 |
July | 74037772.87 | 10813709.66 | 63224063.21 | 0.165883E+09 | 35323534.81 |
August | 92895171.88 | 35830141.06 | 57065030.82 | 0.208241E+09 | 41381851.45 |
September | 0.118233E+09 | 64269041.43 | 53964129.83 | 0.240920E+09 | 61953332.24 |
October | 0.150180E+09 | 0.106362E+09 | 43818256.17 | 0.262940E+09 | 0.127083E+09 |
November | 0.181452E+09 | 0.145372E+09 | 36079787.27 | 0.301857E+09 | 0.134997E+09 |
December | 0.180623E+09 | 0.147122E+09 | 33500342.73 | 0.284652E+09 | 0.166092E+09 |
Annual Sum or Average | 0.151992E+10 | 0.943809E+09 | 0.576109E+09 | 0.269426E+10 | 0.117225E+10 |
Minimum of Months | 68286346.41 | 9775131.99 | 33500342.73 | 0.128119E+09 | 35323534.81 |
Maximum of Months | 0.195850E+09 | 0.161936E+09 | 65537135.64 | 0.317604E+09 | 0.166092E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234156E+09 | 0.193608E+09 | 40547661.16 | 0.380232E+09 | 0.170638E+09 |
February | 0.199776E+09 | 0.159629E+09 | 40147900.92 | 0.325631E+09 | 0.160178E+09 |
March | 0.158290E+09 | 0.102998E+09 | 55292041.89 | 0.269101E+09 | 0.140550E+09 |
April | 97387094.04 | 36810265.45 | 60576828.59 | 0.153574E+09 | 0.123287E+09 |
May | 92554326.58 | 14199123.13 | 78355203.44 | 0.160767E+09 | 79399071.41 |
June | 81642118.06 | 11686999.26 | 69955118.80 | 0.182886E+09 | 44803201.35 |
July | 88518436.14 | 12928706.94 | 75589729.20 | 0.197957E+09 | 42236265.97 |
August | 0.111064E+09 | 42837972.16 | 68226083.67 | 0.248682E+09 | 49448365.32 |
September | 0.141358E+09 | 76839089.28 | 64518693.56 | 0.287942E+09 | 73942592.01 |
October | 0.179553E+09 | 0.127164E+09 | 52388441.19 | 0.314559E+09 | 0.150929E+09 |
November | 0.216941E+09 | 0.173805E+09 | 43136445.37 | 0.361377E+09 | 0.160215E+09 |
December | 0.215950E+09 | 0.175897E+09 | 40052500.69 | 0.341071E+09 | 0.196967E+09 |
Annual Sum or Average | 0.181719E+10 | 0.112840E+10 | 0.688787E+09 | 0.322378E+10 | 0.139259E+10 |
Minimum of Months | 81642118.06 | 11686999.26 | 40052500.69 | 0.153574E+09 | 42236265.97 |
Maximum of Months | 0.234156E+09 | 0.193608E+09 | 78355203.44 | 0.380232E+09 | 0.196967E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 754.42 | 367.97 | 468.30 | 387.20 | 81.09 | 0.00 | 0.00 |
February | 715.51 | 382.90 | 442.35 | 353.45 | 88.90 | 0.00 | 0.00 |
March | 533.12 | 307.62 | 316.57 | 205.99 | 110.58 | 0.00 | 0.00 |
April | 312.88 | 282.27 | 201.26 | 76.07 | 125.19 | 0.00 | 0.00 |
May | 314.64 | 176.94 | 185.10 | 28.40 | 156.71 | 0.00 | 0.00 |
June | 378.85 | 96.68 | 168.72 | 24.15 | 144.57 | 0.00 | 0.00 |
July | 398.25 | 86.50 | 177.03 | 25.86 | 151.17 | 0.00 | 0.00 |
August | 499.36 | 100.66 | 222.12 | 85.67 | 136.45 | 0.00 | 0.00 |
September | 596.51 | 155.98 | 292.13 | 158.80 | 133.33 | 0.00 | 0.00 |
October | 626.46 | 319.55 | 359.09 | 254.32 | 104.77 | 0.00 | 0.00 |
November | 742.22 | 352.61 | 448.33 | 359.19 | 89.15 | 0.00 | 0.00 |
December | 677.26 | 420.92 | 431.89 | 351.78 | 80.10 | 0.00 | 0.00 |
Annual Sum or Average | 544.81 | 253.51 | 308.66 | 191.67 | 117.00 | 0.00 | 0.00 |
Minimum of Months | 312.88 | 86.50 | 168.72 | 24.15 | 80.10 | 0.00 | 0.00 |
Maximum of Months | 754.42 | 420.92 | 468.30 | 387.20 | 156.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 373.38 | 192.57 | 234.15 | 193.60 | 40.55 | 0.00 | 0.00 |
February | 354.07 | 199.35 | 221.17 | 176.73 | 44.45 | 0.00 | 0.00 |
March | 263.13 | 162.05 | 158.29 | 102.99 | 55.29 | 0.00 | 0.00 |
April | 152.99 | 150.98 | 100.63 | 38.04 | 62.59 | 0.00 | 0.00 |
May | 153.98 | 93.49 | 92.55 | 14.20 | 78.35 | 0.00 | 0.00 |
June | 189.08 | 48.90 | 84.36 | 12.08 | 72.28 | 0.00 | 0.00 |
July | 198.80 | 43.81 | 88.52 | 12.93 | 75.59 | 0.00 | 0.00 |
August | 249.48 | 50.55 | 111.06 | 42.84 | 68.22 | 0.00 | 0.00 |
September | 297.58 | 79.03 | 146.07 | 79.40 | 66.67 | 0.00 | 0.00 |
October | 310.72 | 165.99 | 179.55 | 127.16 | 52.39 | 0.00 | 0.00 |
November | 367.40 | 184.77 | 224.17 | 179.59 | 44.57 | 0.00 | 0.00 |
December | 335.42 | 218.38 | 215.94 | 175.89 | 40.05 | 0.00 | 0.00 |
Annual Sum or Average | 270.02 | 132.12 | 154.33 | 95.83 | 58.50 | 0.00 | 0.00 |
Minimum of Months | 152.99 | 43.81 | 84.36 | 12.08 | 40.05 | 0.00 | 0.00 |
Maximum of Months | 373.38 | 218.38 | 234.15 | 193.60 | 78.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 373.05 | 190.15 | 233.67 | 193.20 | 40.46 | 0.00 | 0.00 |
February | 353.76 | 196.57 | 220.72 | 176.36 | 44.36 | 0.00 | 0.00 |
March | 262.80 | 160.59 | 157.96 | 102.78 | 55.18 | 0.00 | 0.00 |
April | 152.91 | 149.35 | 100.42 | 37.96 | 62.47 | 0.00 | 0.00 |
May | 153.45 | 94.73 | 92.36 | 14.17 | 78.19 | 0.00 | 0.00 |
June | 187.74 | 52.70 | 84.19 | 12.05 | 72.14 | 0.00 | 0.00 |
July | 197.12 | 47.79 | 88.33 | 12.90 | 75.43 | 0.00 | 0.00 |
August | 248.36 | 54.76 | 110.83 | 42.75 | 68.08 | 0.00 | 0.00 |
September | 296.48 | 82.73 | 145.77 | 79.24 | 66.53 | 0.00 | 0.00 |
October | 310.08 | 166.33 | 179.18 | 126.90 | 52.28 | 0.00 | 0.00 |
November | 367.14 | 182.97 | 223.71 | 179.22 | 44.48 | 0.00 | 0.00 |
December | 335.19 | 215.34 | 215.50 | 175.53 | 39.97 | 0.00 | 0.00 |
Annual Sum or Average | 269.35 | 132.48 | 154.02 | 95.64 | 58.38 | 0.00 | 0.00 |
Minimum of Months | 152.91 | 47.79 | 84.19 | 12.05 | 39.97 | 0.00 | 0.00 |
Maximum of Months | 373.05 | 215.34 | 233.67 | 193.20 | 78.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 373.57 | 188.34 | 233.67 | 193.20 | 40.46 | 0.00 | 0.00 |
February | 354.23 | 194.88 | 220.72 | 176.36 | 44.36 | 0.00 | 0.00 |
March | 263.18 | 159.14 | 157.96 | 102.78 | 55.18 | 0.00 | 0.00 |
April | 153.31 | 147.64 | 100.42 | 37.96 | 62.47 | 0.00 | 0.00 |
May | 153.75 | 93.93 | 92.36 | 14.17 | 78.19 | 0.00 | 0.00 |
June | 187.69 | 52.84 | 84.19 | 12.05 | 72.14 | 0.00 | 0.00 |
July | 197.03 | 48.01 | 88.33 | 12.90 | 75.43 | 0.00 | 0.00 |
August | 248.31 | 54.95 | 110.83 | 42.75 | 68.08 | 0.00 | 0.00 |
September | 296.47 | 82.75 | 145.77 | 79.24 | 66.53 | 0.00 | 0.00 |
October | 310.27 | 165.31 | 179.18 | 126.90 | 52.28 | 0.00 | 0.00 |
November | 367.67 | 181.27 | 223.71 | 179.22 | 44.48 | 0.00 | 0.00 |
December | 335.61 | 213.57 | 215.50 | 175.53 | 39.97 | 0.00 | 0.00 |
Annual Sum or Average | 269.60 | 131.54 | 154.02 | 95.64 | 58.38 | 0.00 | 0.00 |
Minimum of Months | 153.31 | 48.01 | 84.19 | 12.05 | 39.97 | 0.00 | 0.00 |
Maximum of Months | 373.57 | 213.57 | 233.67 | 193.20 | 78.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 374.41 | 186.23 | 233.67 | 193.20 | 40.46 | 0.00 | 0.00 |
February | 354.93 | 193.12 | 220.72 | 176.36 | 44.36 | 0.00 | 0.00 |
March | 263.91 | 157.22 | 157.96 | 102.78 | 55.18 | 0.00 | 0.00 |
April | 154.13 | 145.23 | 100.42 | 37.96 | 62.47 | 0.00 | 0.00 |
May | 154.56 | 92.36 | 92.36 | 14.17 | 78.19 | 0.00 | 0.00 |
June | 187.97 | 52.21 | 84.19 | 12.05 | 72.14 | 0.00 | 0.00 |
July | 197.28 | 47.44 | 88.33 | 12.90 | 75.43 | 0.00 | 0.00 |
August | 248.52 | 54.35 | 110.83 | 42.75 | 68.08 | 0.00 | 0.00 |
September | 296.75 | 81.98 | 145.77 | 79.24 | 66.53 | 0.00 | 0.00 |
October | 310.85 | 163.54 | 179.18 | 126.90 | 52.28 | 0.00 | 0.00 |
November | 368.55 | 179.09 | 223.71 | 179.22 | 44.48 | 0.00 | 0.00 |
December | 336.26 | 211.70 | 215.50 | 175.53 | 39.97 | 0.00 | 0.00 |
Annual Sum or Average | 270.19 | 130.03 | 154.02 | 95.64 | 58.38 | 0.00 | 0.00 |
Minimum of Months | 154.13 | 47.44 | 84.19 | 12.05 | 39.97 | 0.00 | 0.00 |
Maximum of Months | 374.41 | 211.70 | 233.67 | 193.20 | 78.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 753.24 | 363.16 | 467.34 | 386.41 | 80.93 | 0.00 | 0.00 |
February | 714.04 | 377.71 | 441.44 | 352.73 | 88.71 | 0.00 | 0.00 |
March | 531.85 | 304.93 | 315.92 | 205.57 | 110.35 | 0.00 | 0.00 |
April | 312.37 | 279.21 | 200.85 | 75.92 | 124.93 | 0.00 | 0.00 |
May | 312.91 | 176.90 | 184.72 | 28.34 | 156.38 | 0.00 | 0.00 |
June | 375.12 | 100.58 | 168.38 | 24.10 | 144.27 | 0.00 | 0.00 |
July | 393.56 | 91.49 | 176.67 | 25.80 | 150.86 | 0.00 | 0.00 |
August | 496.09 | 105.02 | 221.67 | 85.50 | 136.17 | 0.00 | 0.00 |
September | 593.52 | 159.66 | 291.53 | 158.47 | 133.06 | 0.00 | 0.00 |
October | 624.90 | 318.37 | 358.36 | 253.80 | 104.56 | 0.00 | 0.00 |
November | 741.49 | 348.57 | 447.41 | 358.45 | 88.96 | 0.00 | 0.00 |
December | 676.68 | 414.14 | 431.00 | 351.06 | 79.94 | 0.00 | 0.00 |
Annual Sum or Average | 542.83 | 252.63 | 308.03 | 191.27 | 116.76 | 0.00 | 0.00 |
Minimum of Months | 312.37 | 91.49 | 168.38 | 24.10 | 79.94 | 0.00 | 0.00 |
Maximum of Months | 753.24 | 414.14 | 467.34 | 386.41 | 156.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 375.55 | 182.35 | 233.67 | 193.20 | 40.46 | 0.00 | 0.00 |
February | 355.92 | 189.74 | 220.72 | 176.36 | 44.36 | 0.00 | 0.00 |
March | 264.89 | 153.33 | 157.96 | 102.78 | 55.18 | 0.00 | 0.00 |
April | 155.17 | 140.72 | 100.42 | 37.96 | 62.47 | 0.00 | 0.00 |
May | 155.49 | 88.89 | 92.36 | 14.17 | 78.19 | 0.00 | 0.00 |
June | 187.56 | 49.83 | 84.19 | 12.05 | 72.14 | 0.00 | 0.00 |
July | 196.76 | 45.31 | 88.33 | 12.90 | 75.43 | 0.00 | 0.00 |
August | 247.90 | 52.04 | 110.83 | 42.75 | 68.08 | 0.00 | 0.00 |
September | 296.33 | 79.58 | 145.77 | 79.24 | 66.53 | 0.00 | 0.00 |
October | 311.35 | 160.16 | 179.18 | 126.90 | 52.28 | 0.00 | 0.00 |
November | 369.60 | 175.16 | 223.71 | 179.22 | 44.48 | 0.00 | 0.00 |
December | 337.21 | 208.19 | 215.50 | 175.53 | 39.97 | 0.00 | 0.00 |
Annual Sum or Average | 270.66 | 126.77 | 154.02 | 95.64 | 58.38 | 0.00 | 0.00 |
Minimum of Months | 155.17 | 45.31 | 84.19 | 12.05 | 39.97 | 0.00 | 0.00 |
Maximum of Months | 375.55 | 208.19 | 233.67 | 193.20 | 78.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 375.76 | 181.84 | 233.67 | 193.20 | 40.46 | 0.00 | 0.00 |
February | 356.12 | 189.27 | 220.72 | 176.36 | 44.36 | 0.00 | 0.00 |
March | 265.10 | 152.79 | 157.96 | 102.78 | 55.18 | 0.00 | 0.00 |
April | 155.37 | 140.16 | 100.42 | 37.96 | 62.47 | 0.00 | 0.00 |
May | 155.83 | 88.38 | 92.36 | 14.17 | 78.19 | 0.00 | 0.00 |
June | 187.74 | 49.58 | 84.19 | 12.05 | 72.14 | 0.00 | 0.00 |
July | 196.91 | 45.10 | 88.33 | 12.90 | 75.43 | 0.00 | 0.00 |
August | 248.02 | 51.84 | 110.83 | 42.75 | 68.08 | 0.00 | 0.00 |
September | 296.44 | 79.37 | 145.77 | 79.24 | 66.53 | 0.00 | 0.00 |
October | 311.51 | 159.76 | 179.18 | 126.90 | 52.28 | 0.00 | 0.00 |
November | 369.79 | 174.72 | 223.71 | 179.22 | 44.48 | 0.00 | 0.00 |
December | 337.35 | 207.78 | 215.50 | 175.53 | 39.97 | 0.00 | 0.00 |
Annual Sum or Average | 270.84 | 126.37 | 154.02 | 95.64 | 58.38 | 0.00 | 0.00 |
Minimum of Months | 155.37 | 45.10 | 84.19 | 12.05 | 39.97 | 0.00 | 0.00 |
Maximum of Months | 375.76 | 207.78 | 233.67 | 193.20 | 78.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 376.59 | 179.55 | 233.67 | 193.20 | 40.46 | 0.00 | 0.00 |
February | 356.89 | 187.00 | 220.72 | 176.36 | 44.36 | 0.00 | 0.00 |
March | 265.96 | 150.28 | 157.96 | 102.78 | 55.18 | 0.00 | 0.00 |
April | 156.19 | 137.42 | 100.42 | 37.96 | 62.47 | 0.00 | 0.00 |
May | 157.14 | 86.25 | 92.36 | 14.17 | 78.19 | 0.00 | 0.00 |
June | 188.13 | 48.87 | 84.19 | 12.05 | 72.14 | 0.00 | 0.00 |
July | 197.23 | 44.50 | 88.33 | 12.90 | 75.43 | 0.00 | 0.00 |
August | 248.24 | 51.31 | 110.83 | 42.75 | 68.08 | 0.00 | 0.00 |
September | 296.73 | 78.68 | 145.77 | 79.24 | 66.53 | 0.00 | 0.00 |
October | 312.23 | 157.80 | 179.18 | 126.90 | 52.28 | 0.00 | 0.00 |
November | 370.53 | 172.76 | 223.71 | 179.22 | 44.48 | 0.00 | 0.00 |
December | 337.99 | 205.69 | 215.50 | 175.53 | 39.97 | 0.00 | 0.00 |
Annual Sum or Average | 271.50 | 124.67 | 154.02 | 95.64 | 58.38 | 0.00 | 0.00 |
Minimum of Months | 156.19 | 44.50 | 84.19 | 12.05 | 39.97 | 0.00 | 0.00 |
Maximum of Months | 376.59 | 205.69 | 233.67 | 193.20 | 78.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 379.12 | 171.04 | 233.67 | 193.20 | 40.46 | 0.00 | 0.00 |
February | 359.29 | 177.87 | 220.72 | 176.36 | 44.36 | 0.00 | 0.00 |
March | 268.23 | 140.92 | 157.96 | 102.78 | 55.18 | 0.00 | 0.00 |
April | 158.11 | 127.78 | 100.42 | 37.96 | 62.47 | 0.00 | 0.00 |
May | 160.32 | 79.50 | 92.36 | 14.17 | 78.19 | 0.00 | 0.00 |
June | 188.83 | 46.19 | 84.19 | 12.05 | 72.14 | 0.00 | 0.00 |
July | 197.78 | 42.15 | 88.33 | 12.90 | 75.43 | 0.00 | 0.00 |
August | 248.34 | 49.36 | 110.83 | 42.75 | 68.08 | 0.00 | 0.00 |
September | 296.98 | 76.33 | 145.77 | 79.24 | 66.53 | 0.00 | 0.00 |
October | 313.78 | 151.25 | 179.18 | 126.90 | 52.28 | 0.00 | 0.00 |
November | 372.33 | 165.98 | 223.71 | 179.22 | 44.48 | 0.00 | 0.00 |
December | 339.89 | 197.56 | 215.50 | 175.53 | 39.97 | 0.00 | 0.00 |
Annual Sum or Average | 273.09 | 118.50 | 154.02 | 95.64 | 58.38 | 0.00 | 0.00 |
Minimum of Months | 158.11 | 42.15 | 84.19 | 12.05 | 39.97 | 0.00 | 0.00 |
Maximum of Months | 379.12 | 197.56 | 233.67 | 193.20 | 78.19 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.202064E+10 | 0.985579E+09 | 0.125428E+10 | 0.103709E+10 | 0.217199E+09 | 0.00 | 0.00 |
February | 0.173096E+10 | 0.926323E+09 | 0.107013E+10 | 0.855071E+09 | 0.215058E+09 | 0.00 | 0.00 |
March | 0.142792E+10 | 0.823920E+09 | 0.847902E+09 | 0.551723E+09 | 0.296179E+09 | 0.00 | 0.00 |
April | 0.810993E+09 | 0.731644E+09 | 0.521667E+09 | 0.197179E+09 | 0.324488E+09 | 0.00 | 0.00 |
May | 0.842744E+09 | 0.473916E+09 | 0.495779E+09 | 76059478.35 | 0.419720E+09 | 0.00 | 0.00 |
June | 0.981991E+09 | 0.250601E+09 | 0.437327E+09 | 62602955.06 | 0.374724E+09 | 0.00 | 0.00 |
July | 0.106668E+10 | 0.231691E+09 | 0.474161E+09 | 69254326.25 | 0.404906E+09 | 0.00 | 0.00 |
August | 0.133748E+10 | 0.269596E+09 | 0.594929E+09 | 0.229467E+09 | 0.365462E+09 | 0.00 | 0.00 |
September | 0.154615E+10 | 0.404311E+09 | 0.757202E+09 | 0.411599E+09 | 0.345603E+09 | 0.00 | 0.00 |
October | 0.167792E+10 | 0.855886E+09 | 0.961799E+09 | 0.681173E+09 | 0.280626E+09 | 0.00 | 0.00 |
November | 0.192383E+10 | 0.913953E+09 | 0.116207E+10 | 0.931008E+09 | 0.231066E+09 | 0.00 | 0.00 |
December | 0.181397E+10 | 0.112738E+10 | 0.115676E+10 | 0.942218E+09 | 0.214547E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.171813E+11 | 0.799480E+10 | 0.973402E+10 | 0.604444E+10 | 0.368958E+10 | 0.00 | 0.00 |
Minimum of Months | 0.810993E+09 | 0.231691E+09 | 0.437327E+09 | 62602955.06 | 0.214547E+09 | 0.00 | 0.00 |
Maximum of Months | 0.202064E+10 | 0.112738E+10 | 0.125428E+10 | 0.103709E+10 | 0.419720E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100006E+10 | 0.515772E+09 | 0.627142E+09 | 0.518543E+09 | 0.108599E+09 | 0.00 | 0.00 |
February | 0.856573E+09 | 0.482275E+09 | 0.535064E+09 | 0.427536E+09 | 0.107529E+09 | 0.00 | 0.00 |
March | 0.704760E+09 | 0.434038E+09 | 0.423951E+09 | 0.275862E+09 | 0.148090E+09 | 0.00 | 0.00 |
April | 0.396555E+09 | 0.391352E+09 | 0.260833E+09 | 98589524.21 | 0.162244E+09 | 0.00 | 0.00 |
May | 0.412425E+09 | 0.250406E+09 | 0.247890E+09 | 38029739.18 | 0.209860E+09 | 0.00 | 0.00 |
June | 0.490105E+09 | 0.126737E+09 | 0.218663E+09 | 31301477.53 | 0.187362E+09 | 0.00 | 0.00 |
July | 0.532467E+09 | 0.117334E+09 | 0.237080E+09 | 34627163.12 | 0.202453E+09 | 0.00 | 0.00 |
August | 0.668197E+09 | 0.135402E+09 | 0.297465E+09 | 0.114734E+09 | 0.182731E+09 | 0.00 | 0.00 |
September | 0.771321E+09 | 0.204849E+09 | 0.378601E+09 | 0.205799E+09 | 0.172801E+09 | 0.00 | 0.00 |
October | 0.832224E+09 | 0.444583E+09 | 0.480899E+09 | 0.340587E+09 | 0.140313E+09 | 0.00 | 0.00 |
November | 0.952306E+09 | 0.478927E+09 | 0.581037E+09 | 0.465504E+09 | 0.115533E+09 | 0.00 | 0.00 |
December | 0.898395E+09 | 0.584896E+09 | 0.578382E+09 | 0.471109E+09 | 0.107273E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.851539E+10 | 0.416657E+10 | 0.486701E+10 | 0.302222E+10 | 0.184479E+10 | 0.00 | 0.00 |
Minimum of Months | 0.396555E+09 | 0.117334E+09 | 0.218663E+09 | 31301477.53 | 0.107273E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100006E+10 | 0.584896E+09 | 0.627142E+09 | 0.518543E+09 | 0.209860E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.999179E+09 | 0.509305E+09 | 0.625856E+09 | 0.517479E+09 | 0.108377E+09 | 0.00 | 0.00 |
February | 0.855813E+09 | 0.475539E+09 | 0.533967E+09 | 0.426659E+09 | 0.107308E+09 | 0.00 | 0.00 |
March | 0.703883E+09 | 0.430121E+09 | 0.423081E+09 | 0.275296E+09 | 0.147786E+09 | 0.00 | 0.00 |
April | 0.396331E+09 | 0.387123E+09 | 0.260298E+09 | 98387270.00 | 0.161911E+09 | 0.00 | 0.00 |
May | 0.410992E+09 | 0.253719E+09 | 0.247381E+09 | 37951722.02 | 0.209429E+09 | 0.00 | 0.00 |
June | 0.486616E+09 | 0.136600E+09 | 0.218215E+09 | 31237263.25 | 0.186978E+09 | 0.00 | 0.00 |
July | 0.527962E+09 | 0.127994E+09 | 0.236594E+09 | 34556126.27 | 0.202038E+09 | 0.00 | 0.00 |
August | 0.665205E+09 | 0.146657E+09 | 0.296854E+09 | 0.114498E+09 | 0.182356E+09 | 0.00 | 0.00 |
September | 0.768476E+09 | 0.214447E+09 | 0.377824E+09 | 0.205377E+09 | 0.172447E+09 | 0.00 | 0.00 |
October | 0.830506E+09 | 0.445498E+09 | 0.479913E+09 | 0.339888E+09 | 0.140025E+09 | 0.00 | 0.00 |
November | 0.951619E+09 | 0.474258E+09 | 0.579845E+09 | 0.464549E+09 | 0.115296E+09 | 0.00 | 0.00 |
December | 0.897768E+09 | 0.576777E+09 | 0.577196E+09 | 0.470142E+09 | 0.107053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.849435E+10 | 0.417804E+10 | 0.485702E+10 | 0.301602E+10 | 0.184100E+10 | 0.00 | 0.00 |
Minimum of Months | 0.396331E+09 | 0.127994E+09 | 0.218215E+09 | 31237263.25 | 0.107053E+09 | 0.00 | 0.00 |
Maximum of Months | 0.999179E+09 | 0.576777E+09 | 0.625856E+09 | 0.517479E+09 | 0.209429E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100056E+10 | 0.504449E+09 | 0.625856E+09 | 0.517479E+09 | 0.108377E+09 | 0.00 | 0.00 |
February | 0.856946E+09 | 0.471442E+09 | 0.533967E+09 | 0.426659E+09 | 0.107308E+09 | 0.00 | 0.00 |
March | 0.704895E+09 | 0.426254E+09 | 0.423081E+09 | 0.275296E+09 | 0.147786E+09 | 0.00 | 0.00 |
April | 0.397370E+09 | 0.382684E+09 | 0.260298E+09 | 98387270.00 | 0.161911E+09 | 0.00 | 0.00 |
May | 0.411792E+09 | 0.251578E+09 | 0.247381E+09 | 37951722.02 | 0.209429E+09 | 0.00 | 0.00 |
June | 0.486493E+09 | 0.136959E+09 | 0.218215E+09 | 31237263.25 | 0.186978E+09 | 0.00 | 0.00 |
July | 0.527730E+09 | 0.128584E+09 | 0.236594E+09 | 34556126.27 | 0.202038E+09 | 0.00 | 0.00 |
August | 0.665061E+09 | 0.147184E+09 | 0.296854E+09 | 0.114498E+09 | 0.182356E+09 | 0.00 | 0.00 |
September | 0.768458E+09 | 0.214489E+09 | 0.377824E+09 | 0.205377E+09 | 0.172447E+09 | 0.00 | 0.00 |
October | 0.831030E+09 | 0.442773E+09 | 0.479913E+09 | 0.339888E+09 | 0.140025E+09 | 0.00 | 0.00 |
November | 0.952990E+09 | 0.469852E+09 | 0.579845E+09 | 0.464549E+09 | 0.115296E+09 | 0.00 | 0.00 |
December | 0.898885E+09 | 0.572016E+09 | 0.577196E+09 | 0.470142E+09 | 0.107053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.850221E+10 | 0.414826E+10 | 0.485702E+10 | 0.301602E+10 | 0.184100E+10 | 0.00 | 0.00 |
Minimum of Months | 0.397370E+09 | 0.128584E+09 | 0.218215E+09 | 31237263.25 | 0.107053E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100056E+10 | 0.572016E+09 | 0.625856E+09 | 0.517479E+09 | 0.209429E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100283E+10 | 0.498794E+09 | 0.625856E+09 | 0.517479E+09 | 0.108377E+09 | 0.00 | 0.00 |
February | 0.858636E+09 | 0.467198E+09 | 0.533967E+09 | 0.426659E+09 | 0.107308E+09 | 0.00 | 0.00 |
March | 0.706846E+09 | 0.421092E+09 | 0.423081E+09 | 0.275296E+09 | 0.147786E+09 | 0.00 | 0.00 |
April | 0.399505E+09 | 0.376436E+09 | 0.260298E+09 | 98387270.00 | 0.161911E+09 | 0.00 | 0.00 |
May | 0.413981E+09 | 0.247377E+09 | 0.247381E+09 | 37951722.02 | 0.209429E+09 | 0.00 | 0.00 |
June | 0.487229E+09 | 0.135322E+09 | 0.218215E+09 | 31237263.25 | 0.186978E+09 | 0.00 | 0.00 |
July | 0.528390E+09 | 0.127073E+09 | 0.236594E+09 | 34556126.27 | 0.202038E+09 | 0.00 | 0.00 |
August | 0.665644E+09 | 0.145580E+09 | 0.296854E+09 | 0.114498E+09 | 0.182356E+09 | 0.00 | 0.00 |
September | 0.769178E+09 | 0.212485E+09 | 0.377824E+09 | 0.205377E+09 | 0.172447E+09 | 0.00 | 0.00 |
October | 0.832580E+09 | 0.438028E+09 | 0.479913E+09 | 0.339888E+09 | 0.140025E+09 | 0.00 | 0.00 |
November | 0.955287E+09 | 0.464192E+09 | 0.579845E+09 | 0.464549E+09 | 0.115296E+09 | 0.00 | 0.00 |
December | 0.900637E+09 | 0.567007E+09 | 0.577196E+09 | 0.470142E+09 | 0.107053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.852074E+10 | 0.410058E+10 | 0.485702E+10 | 0.301602E+10 | 0.184100E+10 | 0.00 | 0.00 |
Minimum of Months | 0.399505E+09 | 0.127073E+09 | 0.218215E+09 | 31237263.25 | 0.107053E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100283E+10 | 0.567007E+09 | 0.625856E+09 | 0.517479E+09 | 0.209429E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.201748E+10 | 0.972701E+09 | 0.125171E+10 | 0.103496E+10 | 0.216753E+09 | 0.00 | 0.00 |
February | 0.172741E+10 | 0.913751E+09 | 0.106793E+10 | 0.853317E+09 | 0.214616E+09 | 0.00 | 0.00 |
March | 0.142451E+10 | 0.816716E+09 | 0.846163E+09 | 0.550591E+09 | 0.295572E+09 | 0.00 | 0.00 |
April | 0.809668E+09 | 0.723722E+09 | 0.520597E+09 | 0.196775E+09 | 0.323822E+09 | 0.00 | 0.00 |
May | 0.838090E+09 | 0.473815E+09 | 0.494762E+09 | 75903444.03 | 0.418859E+09 | 0.00 | 0.00 |
June | 0.972313E+09 | 0.260708E+09 | 0.436430E+09 | 62474526.49 | 0.373955E+09 | 0.00 | 0.00 |
July | 0.105410E+10 | 0.245047E+09 | 0.473188E+09 | 69112252.54 | 0.404076E+09 | 0.00 | 0.00 |
August | 0.132873E+10 | 0.281274E+09 | 0.593709E+09 | 0.228997E+09 | 0.364712E+09 | 0.00 | 0.00 |
September | 0.153840E+10 | 0.413829E+09 | 0.755648E+09 | 0.410754E+09 | 0.344894E+09 | 0.00 | 0.00 |
October | 0.167372E+10 | 0.852724E+09 | 0.959826E+09 | 0.679776E+09 | 0.280050E+09 | 0.00 | 0.00 |
November | 0.192194E+10 | 0.903495E+09 | 0.115969E+10 | 0.929098E+09 | 0.230592E+09 | 0.00 | 0.00 |
December | 0.181242E+10 | 0.110923E+10 | 0.115439E+10 | 0.940285E+09 | 0.214106E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.171188E+11 | 0.796701E+10 | 0.971405E+10 | 0.603204E+10 | 0.368201E+10 | 0.00 | 0.00 |
Minimum of Months | 0.809668E+09 | 0.245047E+09 | 0.436430E+09 | 62474526.49 | 0.214106E+09 | 0.00 | 0.00 |
Maximum of Months | 0.201748E+10 | 0.110923E+10 | 0.125171E+10 | 0.103496E+10 | 0.418859E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100588E+10 | 0.488410E+09 | 0.625856E+09 | 0.517479E+09 | 0.108377E+09 | 0.00 | 0.00 |
February | 0.861054E+09 | 0.459031E+09 | 0.533967E+09 | 0.426659E+09 | 0.107308E+09 | 0.00 | 0.00 |
March | 0.709477E+09 | 0.410682E+09 | 0.423081E+09 | 0.275296E+09 | 0.147786E+09 | 0.00 | 0.00 |
April | 0.402209E+09 | 0.364746E+09 | 0.260298E+09 | 98387270.00 | 0.161911E+09 | 0.00 | 0.00 |
May | 0.416473E+09 | 0.238072E+09 | 0.247381E+09 | 37951722.02 | 0.209429E+09 | 0.00 | 0.00 |
June | 0.486156E+09 | 0.129151E+09 | 0.218215E+09 | 31237263.25 | 0.186978E+09 | 0.00 | 0.00 |
July | 0.527005E+09 | 0.121354E+09 | 0.236594E+09 | 34556126.27 | 0.202038E+09 | 0.00 | 0.00 |
August | 0.663965E+09 | 0.139385E+09 | 0.296854E+09 | 0.114498E+09 | 0.182356E+09 | 0.00 | 0.00 |
September | 0.768081E+09 | 0.206283E+09 | 0.377824E+09 | 0.205377E+09 | 0.172447E+09 | 0.00 | 0.00 |
October | 0.833916E+09 | 0.428972E+09 | 0.479913E+09 | 0.339888E+09 | 0.140025E+09 | 0.00 | 0.00 |
November | 0.958008E+09 | 0.454014E+09 | 0.579845E+09 | 0.464549E+09 | 0.115296E+09 | 0.00 | 0.00 |
December | 0.903176E+09 | 0.557608E+09 | 0.577196E+09 | 0.470142E+09 | 0.107053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.853540E+10 | 0.399771E+10 | 0.485702E+10 | 0.301602E+10 | 0.184100E+10 | 0.00 | 0.00 |
Minimum of Months | 0.402209E+09 | 0.121354E+09 | 0.218215E+09 | 31237263.25 | 0.107053E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100588E+10 | 0.557608E+09 | 0.625856E+09 | 0.517479E+09 | 0.209429E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100644E+10 | 0.487030E+09 | 0.625856E+09 | 0.517479E+09 | 0.108377E+09 | 0.00 | 0.00 |
February | 0.861530E+09 | 0.457877E+09 | 0.533967E+09 | 0.426659E+09 | 0.107308E+09 | 0.00 | 0.00 |
March | 0.710045E+09 | 0.409225E+09 | 0.423081E+09 | 0.275296E+09 | 0.147786E+09 | 0.00 | 0.00 |
April | 0.402710E+09 | 0.363298E+09 | 0.260298E+09 | 98387270.00 | 0.161911E+09 | 0.00 | 0.00 |
May | 0.417372E+09 | 0.236712E+09 | 0.247381E+09 | 37951722.02 | 0.209429E+09 | 0.00 | 0.00 |
June | 0.486610E+09 | 0.128515E+09 | 0.218215E+09 | 31237263.25 | 0.186978E+09 | 0.00 | 0.00 |
July | 0.527403E+09 | 0.120793E+09 | 0.236594E+09 | 34556126.27 | 0.202038E+09 | 0.00 | 0.00 |
August | 0.664294E+09 | 0.138836E+09 | 0.296854E+09 | 0.114498E+09 | 0.182356E+09 | 0.00 | 0.00 |
September | 0.768380E+09 | 0.205718E+09 | 0.377824E+09 | 0.205377E+09 | 0.172447E+09 | 0.00 | 0.00 |
October | 0.834335E+09 | 0.427910E+09 | 0.479913E+09 | 0.339888E+09 | 0.140025E+09 | 0.00 | 0.00 |
November | 0.958501E+09 | 0.452866E+09 | 0.579845E+09 | 0.464549E+09 | 0.115296E+09 | 0.00 | 0.00 |
December | 0.903569E+09 | 0.556505E+09 | 0.577196E+09 | 0.470142E+09 | 0.107053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.854119E+10 | 0.398528E+10 | 0.485702E+10 | 0.301602E+10 | 0.184100E+10 | 0.00 | 0.00 |
Minimum of Months | 0.402710E+09 | 0.120793E+09 | 0.218215E+09 | 31237263.25 | 0.107053E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100644E+10 | 0.556505E+09 | 0.625856E+09 | 0.517479E+09 | 0.209429E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100867E+10 | 0.480916E+09 | 0.625856E+09 | 0.517479E+09 | 0.108377E+09 | 0.00 | 0.00 |
February | 0.863383E+09 | 0.452380E+09 | 0.533967E+09 | 0.426659E+09 | 0.107308E+09 | 0.00 | 0.00 |
March | 0.712339E+09 | 0.402498E+09 | 0.423081E+09 | 0.275296E+09 | 0.147786E+09 | 0.00 | 0.00 |
April | 0.404847E+09 | 0.356201E+09 | 0.260298E+09 | 98387270.00 | 0.161911E+09 | 0.00 | 0.00 |
May | 0.420875E+09 | 0.231012E+09 | 0.247381E+09 | 37951722.02 | 0.209429E+09 | 0.00 | 0.00 |
June | 0.487643E+09 | 0.126661E+09 | 0.218215E+09 | 31237263.25 | 0.186978E+09 | 0.00 | 0.00 |
July | 0.528259E+09 | 0.119183E+09 | 0.236594E+09 | 34556126.27 | 0.202038E+09 | 0.00 | 0.00 |
August | 0.664887E+09 | 0.137416E+09 | 0.296854E+09 | 0.114498E+09 | 0.182356E+09 | 0.00 | 0.00 |
September | 0.769112E+09 | 0.203943E+09 | 0.377824E+09 | 0.205377E+09 | 0.172447E+09 | 0.00 | 0.00 |
October | 0.836275E+09 | 0.422646E+09 | 0.479913E+09 | 0.339888E+09 | 0.140025E+09 | 0.00 | 0.00 |
November | 0.960416E+09 | 0.447786E+09 | 0.579845E+09 | 0.464549E+09 | 0.115296E+09 | 0.00 | 0.00 |
December | 0.905264E+09 | 0.550907E+09 | 0.577196E+09 | 0.470142E+09 | 0.107053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.856197E+10 | 0.393155E+10 | 0.485702E+10 | 0.301602E+10 | 0.184100E+10 | 0.00 | 0.00 |
Minimum of Months | 0.404847E+09 | 0.119183E+09 | 0.218215E+09 | 31237263.25 | 0.107053E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100867E+10 | 0.550907E+09 | 0.625856E+09 | 0.517479E+09 | 0.209429E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101544E+10 | 0.458105E+09 | 0.625856E+09 | 0.517479E+09 | 0.108377E+09 | 0.00 | 0.00 |
February | 0.869202E+09 | 0.430315E+09 | 0.533967E+09 | 0.426659E+09 | 0.107308E+09 | 0.00 | 0.00 |
March | 0.718436E+09 | 0.377437E+09 | 0.423081E+09 | 0.275296E+09 | 0.147786E+09 | 0.00 | 0.00 |
April | 0.409812E+09 | 0.331199E+09 | 0.260298E+09 | 98387270.00 | 0.161911E+09 | 0.00 | 0.00 |
May | 0.429407E+09 | 0.212929E+09 | 0.247381E+09 | 37951722.02 | 0.209429E+09 | 0.00 | 0.00 |
June | 0.489436E+09 | 0.119713E+09 | 0.218215E+09 | 31237263.25 | 0.186978E+09 | 0.00 | 0.00 |
July | 0.529723E+09 | 0.112883E+09 | 0.236594E+09 | 34556126.27 | 0.202038E+09 | 0.00 | 0.00 |
August | 0.665164E+09 | 0.132212E+09 | 0.296854E+09 | 0.114498E+09 | 0.182356E+09 | 0.00 | 0.00 |
September | 0.769781E+09 | 0.197849E+09 | 0.377824E+09 | 0.205377E+09 | 0.172447E+09 | 0.00 | 0.00 |
October | 0.840439E+09 | 0.405095E+09 | 0.479913E+09 | 0.339888E+09 | 0.140025E+09 | 0.00 | 0.00 |
November | 0.965091E+09 | 0.430209E+09 | 0.579845E+09 | 0.464549E+09 | 0.115296E+09 | 0.00 | 0.00 |
December | 0.910374E+09 | 0.529150E+09 | 0.577196E+09 | 0.470142E+09 | 0.107053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.861230E+10 | 0.373710E+10 | 0.485702E+10 | 0.301602E+10 | 0.184100E+10 | 0.00 | 0.00 |
Minimum of Months | 0.409812E+09 | 0.112883E+09 | 0.218215E+09 | 31237263.25 | 0.107053E+09 | 0.00 | 0.00 |
Maximum of Months | 0.101544E+10 | 0.529150E+09 | 0.625856E+09 | 0.517479E+09 | 0.209429E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.371609E+09 | -247794447.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123814890.3 | 58.99 | 0.00 | 0.00 |
February | 0.340138E+09 | -227785899.2 | 0.00 | 0.00 | 672.00 | 0.00 | -112352298.6 | 59.00 | 0.00 | 0.00 |
March | 0.374861E+09 | -252568459.8 | 0.00 | 0.00 | 744.00 | 0.00 | -122292590.3 | 58.99 | 0.00 | 0.00 |
April | 0.349695E+09 | -231744394.2 | 0.00 | 0.00 | 720.00 | 0.00 | -117950190.9 | 58.99 | 0.00 | 0.00 |
May | 0.342756E+09 | -226501141.4 | 0.00 | 0.00 | 744.00 | 0.00 | -116254920.3 | 58.99 | 0.00 | 0.00 |
June | 0.317884E+09 | -208350812.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109533332.2 | 58.99 | 0.00 | 0.00 |
July | 0.314350E+09 | -201335303.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113014677.4 | 58.99 | 0.00 | 0.00 |
August | 0.315144E+09 | -202215603.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112928115.5 | 58.99 | 0.00 | 0.00 |
September | 0.307126E+09 | -197248692.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109877431.2 | 58.99 | 0.00 | 0.00 |
October | 0.329909E+09 | -211848182.3 | 0.00 | 0.00 | 744.00 | 0.00 | -118061213.5 | 58.99 | 0.00 | 0.00 |
November | 0.335399E+09 | -217274192.8 | 0.00 | 0.00 | 720.00 | 0.00 | -118124730.3 | 58.99 | 0.00 | 0.00 |
December | 0.362581E+09 | -238554691.0 | 0.00 | 0.00 | 744.00 | 0.00 | -124026311.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.406145E+10 | -0.266322E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139823E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.307126E+09 | -252568459.8 | 0.00 | 0.00 | 672.00 | 0.00 | -124026311.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.374861E+09 | -197248692.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109533332.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.368956E+09 | -247799195.4 | 0.00 | 0.00 | 744.00 | 0.00 | -121157106.7 | 58.99 | 0.00 | 0.00 |
February | 0.338088E+09 | -227796167.2 | 0.00 | 0.00 | 672.00 | 0.00 | -110292093.9 | 58.99 | 0.00 | 0.00 |
March | 0.372446E+09 | -252564231.3 | 0.00 | 0.00 | 744.00 | 0.00 | -119881667.2 | 58.99 | 0.00 | 0.00 |
April | 0.346764E+09 | -231748378.7 | 0.00 | 0.00 | 720.00 | 0.00 | -115015582.0 | 58.99 | 0.00 | 0.00 |
May | 0.340908E+09 | -226505097.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114403109.0 | 58.99 | 0.00 | 0.00 |
June | 0.317680E+09 | -208356134.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109323917.5 | 58.99 | 0.00 | 0.00 |
July | 0.314180E+09 | -201342314.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112837616.1 | 58.99 | 0.00 | 0.00 |
August | 0.315045E+09 | -202206964.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112837983.8 | 58.99 | 0.00 | 0.00 |
September | 0.306712E+09 | -197246732.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109464820.0 | 58.99 | 0.00 | 0.00 |
October | 0.327830E+09 | -211849730.6 | 0.00 | 0.00 | 744.00 | 0.00 | -115980722.8 | 58.99 | 0.00 | 0.00 |
November | 0.332572E+09 | -217273759.0 | 0.00 | 0.00 | 720.00 | 0.00 | -115297927.4 | 58.99 | 0.00 | 0.00 |
December | 0.360313E+09 | -238556349.9 | 0.00 | 0.00 | 744.00 | 0.00 | -121756994.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.404149E+10 | -0.266325E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137825E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.306712E+09 | -252564231.3 | 0.00 | 0.00 | 672.00 | 0.00 | -121756994.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.372446E+09 | -197246732.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109323917.5 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.340410E+09 | -217906073.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122504015.2 | 58.99 | 0.00 | 0.00 |
February | 0.312062E+09 | -200481232.5 | 0.00 | 0.00 | 672.00 | 0.00 | -111581011.9 | 58.99 | 0.00 | 0.00 |
March | 0.346245E+09 | -225415936.2 | 0.00 | 0.00 | 744.00 | 0.00 | -120828593.4 | 58.99 | 0.00 | 0.00 |
April | 0.319905E+09 | -203839620.0 | 0.00 | 0.00 | 720.00 | 0.00 | -116065004.4 | 58.99 | 0.00 | 0.00 |
May | 0.315156E+09 | -200895969.9 | 0.00 | 0.00 | 744.00 | 0.00 | -114259955.1 | 58.99 | 0.00 | 0.00 |
June | 0.293537E+09 | -185559967.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107977497.5 | 58.99 | 0.00 | 0.00 |
July | 0.287323E+09 | -176048192.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111274998.8 | 58.98 | 0.00 | 0.00 |
August | 0.292035E+09 | -180610232.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111424766.2 | 58.99 | 0.00 | 0.00 |
September | 0.281728E+09 | -173403214.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108324722.9 | 58.98 | 0.00 | 0.00 |
October | 0.302589E+09 | -186321359.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116267587.2 | 58.99 | 0.00 | 0.00 |
November | 0.308277E+09 | -191827546.1 | 0.00 | 0.00 | 720.00 | 0.00 | -116449935.6 | 59.00 | 0.00 | 0.00 |
December | 0.331487E+09 | -208208760.3 | 0.00 | 0.00 | 744.00 | 0.00 | -123278352.0 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.373075E+10 | -0.235052E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138024E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.281728E+09 | -225415936.2 | 0.00 | 0.00 | 672.00 | 0.00 | -123278352.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.346245E+09 | -173403214.1 | 0.00 | 0.00 | 744.00 | 0.00 | -107977497.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.340859E+09 | -217906723.5 | 0.00 | 0.00 | 744.00 | 0.00 | -122952179.0 | 58.99 | 0.00 | 0.00 |
February | 0.312458E+09 | -200476719.1 | 0.00 | 0.00 | 672.00 | 0.00 | -111980792.6 | 59.00 | 0.00 | 0.00 |
March | 0.346585E+09 | -225413232.2 | 0.00 | 0.00 | 744.00 | 0.00 | -121172173.2 | 58.99 | 0.00 | 0.00 |
April | 0.320298E+09 | -203849387.6 | 0.00 | 0.00 | 720.00 | 0.00 | -116448460.8 | 58.98 | 0.00 | 0.00 |
May | 0.315374E+09 | -200889966.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114483638.4 | 59.00 | 0.00 | 0.00 |
June | 0.293507E+09 | -185564020.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107943060.5 | 58.99 | 0.00 | 0.00 |
July | 0.287268E+09 | -175994068.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111273965.1 | 59.00 | 0.00 | 0.00 |
August | 0.291980E+09 | -180631491.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111348645.0 | 58.98 | 0.00 | 0.00 |
September | 0.281734E+09 | -173355366.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108378742.9 | 59.00 | 0.00 | 0.00 |
October | 0.302826E+09 | -186326573.2 | 0.00 | 0.00 | 744.00 | 0.00 | -116499084.6 | 58.99 | 0.00 | 0.00 |
November | 0.308709E+09 | -191839635.1 | 0.00 | 0.00 | 720.00 | 0.00 | -116869252.4 | 58.99 | 0.00 | 0.00 |
December | 0.331911E+09 | -208217769.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123693258.9 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.373351E+10 | -0.235046E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138304E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.281734E+09 | -225413232.2 | 0.00 | 0.00 | 672.00 | 0.00 | -123693258.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.346585E+09 | -173355366.6 | 0.00 | 0.00 | 744.00 | 0.00 | -107943060.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.331157E+09 | -205918313.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125238934.6 | 59.01 | 0.00 | 0.00 |
February | 0.303264E+09 | -189599249.0 | 0.00 | 0.00 | 672.00 | 0.00 | -113664882.2 | 58.99 | 0.00 | 0.00 |
March | 0.336664E+09 | -213285261.8 | 0.00 | 0.00 | 744.00 | 0.00 | -123378347.5 | 58.99 | 0.00 | 0.00 |
April | 0.311888E+09 | -192875396.8 | 0.00 | 0.00 | 720.00 | 0.00 | -119012242.3 | 58.99 | 0.00 | 0.00 |
May | 0.306582E+09 | -189992759.2 | 0.00 | 0.00 | 744.00 | 0.00 | -116589104.9 | 58.99 | 0.00 | 0.00 |
June | 0.284399E+09 | -175563019.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108836354.6 | 59.00 | 0.00 | 0.00 |
July | 0.278495E+09 | -166455378.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112039785.5 | 58.99 | 0.00 | 0.00 |
August | 0.283092E+09 | -170903667.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112188371.5 | 58.99 | 0.00 | 0.00 |
September | 0.273382E+09 | -164079610.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109302165.3 | 58.98 | 0.00 | 0.00 |
October | 0.294712E+09 | -176124896.4 | 0.00 | 0.00 | 744.00 | 0.00 | -118587440.4 | 58.98 | 0.00 | 0.00 |
November | 0.300348E+09 | -181180901.5 | 0.00 | 0.00 | 720.00 | 0.00 | -119166619.5 | 58.99 | 0.00 | 0.00 |
December | 0.322604E+09 | -196945431.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125658867.3 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.362659E+10 | -0.222292E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140366E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.273382E+09 | -213285261.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125658867.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.336664E+09 | -164079610.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108836354.6 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.330908E+09 | -205922121.2 | 0.00 | 0.00 | 744.00 | 0.00 | -124985669.3 | 59.00 | 0.00 | 0.00 |
February | 0.303100E+09 | -189582336.8 | 0.00 | 0.00 | 672.00 | 0.00 | -113518110.6 | 58.99 | 0.00 | 0.00 |
March | 0.336311E+09 | -213308381.8 | 0.00 | 0.00 | 744.00 | 0.00 | -123002895.8 | 58.98 | 0.00 | 0.00 |
April | 0.311411E+09 | -192884803.6 | 0.00 | 0.00 | 720.00 | 0.00 | -118525717.6 | 58.99 | 0.00 | 0.00 |
May | 0.306144E+09 | -189986251.5 | 0.00 | 0.00 | 744.00 | 0.00 | -116157734.7 | 58.99 | 0.00 | 0.00 |
June | 0.284435E+09 | -175569985.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108865259.0 | 58.99 | 0.00 | 0.00 |
July | 0.278524E+09 | -166458178.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112065342.8 | 58.99 | 0.00 | 0.00 |
August | 0.283138E+09 | -170899920.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112237760.0 | 58.99 | 0.00 | 0.00 |
September | 0.273330E+09 | -164065877.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109264260.0 | 58.99 | 0.00 | 0.00 |
October | 0.294227E+09 | -176085165.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118141741.3 | 59.00 | 0.00 | 0.00 |
November | 0.300010E+09 | -181184840.7 | 0.00 | 0.00 | 720.00 | 0.00 | -118825039.9 | 58.99 | 0.00 | 0.00 |
December | 0.322346E+09 | -196939171.3 | 0.00 | 0.00 | 744.00 | 0.00 | -125406343.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.362388E+10 | -0.222289E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140100E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.273330E+09 | -213308381.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125406343.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.336311E+09 | -164065877.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108865259.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.331040E+09 | -205920955.3 | 0.00 | 0.00 | 744.00 | 0.00 | -125118873.6 | 59.01 | 0.00 | 0.00 |
February | 0.303202E+09 | -189590320.9 | 0.00 | 0.00 | 672.00 | 0.00 | -113611628.2 | 58.99 | 0.00 | 0.00 |
March | 0.336445E+09 | -213295983.3 | 0.00 | 0.00 | 744.00 | 0.00 | -123148696.0 | 58.99 | 0.00 | 0.00 |
April | 0.311547E+09 | -192875419.2 | 0.00 | 0.00 | 720.00 | 0.00 | -118671749.6 | 58.99 | 0.00 | 0.00 |
May | 0.306302E+09 | -189996825.7 | 0.00 | 0.00 | 744.00 | 0.00 | -116305004.3 | 58.99 | 0.00 | 0.00 |
June | 0.284494E+09 | -175591602.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108902833.3 | 58.98 | 0.00 | 0.00 |
July | 0.278584E+09 | -166468475.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112115262.5 | 58.99 | 0.00 | 0.00 |
August | 0.283183E+09 | -170900091.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112282586.8 | 58.99 | 0.00 | 0.00 |
September | 0.273384E+09 | -164041087.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109342989.6 | 59.00 | 0.00 | 0.00 |
October | 0.294329E+09 | -176091216.1 | 0.00 | 0.00 | 744.00 | 0.00 | -118238025.1 | 58.99 | 0.00 | 0.00 |
November | 0.300129E+09 | -181170642.8 | 0.00 | 0.00 | 720.00 | 0.00 | -118958088.1 | 59.00 | 0.00 | 0.00 |
December | 0.322443E+09 | -196939878.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125502916.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.362508E+10 | -0.222288E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140220E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.273384E+09 | -213295983.3 | 0.00 | 0.00 | 672.00 | 0.00 | -125502916.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.336445E+09 | -164041087.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108902833.3 | 59.01 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 415.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 421.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 394.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 354.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 262.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 257.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 251.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3902.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.804123E+10 | 53441.83 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.889333E+10 | 53441.83 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.604509E+10 | 53441.83 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.430272E+10 | 53441.83 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200960E+09 | 53441.83 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8805054.28 | 3257.37 | 22-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.272927E+10 | 53441.83 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.478908E+10 | 53441.83 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105416E+11 | 53441.83 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.455521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105416E+11 | 53441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173552E+10 | 28348.36 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208802E+10 | 28348.36 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121955E+10 | 28348.36 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.716789E+09 | 28348.36 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3262678.59 | 14634.26 | 03-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.667702E+09 | 28348.36 | 25-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.938046E+09 | 28348.36 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.277130E+10 | 28348.36 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.277130E+10 | 28348.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.205493E+10 | 28745.11 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236638E+10 | 28745.11 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142717E+10 | 28745.11 | 02-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.860604E+09 | 28745.11 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10084743.01 | 11118.29 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.747303E+09 | 28745.11 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112447E+10 | 28745.11 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.305934E+10 | 28745.11 | 08-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.305934E+10 | 28745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.219255E+10 | 28868.18 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248831E+10 | 28868.18 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152197E+10 | 28868.18 | 02-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.939606E+09 | 28868.18 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15852458.92 | 15262.70 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.788906E+09 | 28868.18 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121634E+10 | 28868.18 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.320328E+10 | 28868.18 | 07-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.320328E+10 | 28868.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.245678E+10 | 28672.76 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275482E+10 | 28672.76 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173340E+10 | 28672.76 | 02-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111072E+10 | 28672.76 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30316454.83 | 21472.12 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.874146E+09 | 28672.76 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140981E+10 | 28672.76 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.349745E+10 | 28672.76 | 07-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.349745E+10 | 28672.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.695955E+10 | 52690.89 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.748039E+10 | 52690.89 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.505988E+10 | 52690.89 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.362842E+10 | 52690.89 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.210302E+09 | 52690.89 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9432920.15 | 2111.63 | 21-SEP-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.247338E+10 | 52690.89 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.452391E+10 | 52690.89 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.904236E+10 | 52690.89 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.393876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.904236E+10 | 52690.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.303407E+10 | 26451.75 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332707E+10 | 26451.75 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218005E+10 | 26451.75 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149070E+10 | 26451.75 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 58960615.88 | 26451.75 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 432023.88 | 343.64 | 21-SEP-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109003E+10 | 26451.75 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187589E+10 | 26451.75 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.412657E+10 | 26451.75 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.412657E+10 | 26451.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.311731E+10 | 26272.15 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.340667E+10 | 26272.15 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.224621E+10 | 26272.15 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154634E+10 | 26272.15 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66190665.65 | 26272.15 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 540133.89 | 399.27 | 21-SEP-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111238E+10 | 26272.15 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193204E+10 | 26272.15 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.419777E+10 | 26272.15 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.419777E+10 | 26272.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.348830E+10 | 26581.26 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.376421E+10 | 26581.26 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.254743E+10 | 26581.26 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180954E+10 | 26581.26 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97859120.11 | 26581.26 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1231490.44 | 606.49 | 21-SEP-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121847E+10 | 26581.26 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.217250E+10 | 26581.26 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.454041E+10 | 26581.26 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.454041E+10 | 26581.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.485521E+10 | 27266.79 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.527483E+10 | 27266.79 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.378551E+10 | 27266.79 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.282807E+10 | 27266.79 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223489E+09 | 27266.79 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12266113.27 | 13220.04 | 22-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166423E+10 | 27266.79 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297950E+10 | 27266.79 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.606928E+10 | 27266.79 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.606928E+10 | 27266.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 255.49 | 255.49 | 0.43 | 20-JAN-13:10 | 0.43 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.176986E+09 | 0.176986E+09 | 5842.80 | 14-MAR-13:00 | 5842.80 | 0.00 |
April | 0.00 | 0.00 | 8926767.90 | 8926767.90 | 1680.86 | 20-APR-13:00 | 1680.86 | 0.00 |
May | 0.00 | 0.00 | 0.167021E+10 | 0.165780E+10 | 9452.82 | 31-MAY-16:10 | 9452.82 | 0.00 |
June | 0.00 | 0.00 | 0.116181E+11 | 0.110893E+11 | 18609.69 | 26-JUN-16:10 | 18609.69 | 0.00 |
July | 0.00 | 0.00 | 0.125285E+11 | 0.117745E+11 | 22179.50 | 18-JUL-07:03 | 22179.50 | 0.00 |
August | 0.00 | 0.00 | 0.119297E+11 | 0.113719E+11 | 18211.63 | 16-AUG-16:10 | 18211.63 | 0.00 |
September | 0.00 | 0.00 | 0.802283E+10 | 0.792978E+10 | 15668.99 | 10-SEP-13:00 | 15668.99 | 0.00 |
October | 0.00 | 0.00 | 0.775034E+09 | 0.775023E+09 | 10680.75 | 11-OCT-14:00 | 10680.75 | 0.00 |
November | 0.00 | 0.00 | 61061126.95 | 61061126.95 | 3749.66 | 07-NOV-15:00 | 3749.66 | 0.00 |
December | 0.00 | 0.00 | 1503574.43 | 1503574.43 | 982.44 | 02-DEC-15:00 | 982.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.467928E+11 | 0.448467E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.125285E+11 | 0.117745E+11 | 22179.50 | 22179.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3420715.07 | 3420715.07 | 834.40 | 25-JAN-21:20 | 834.40 | 0.00 |
February | 0.00 | 0.00 | 647387.34 | 647387.34 | 1248.28 | 26-FEB-18:10 | 1248.28 | 0.00 |
March | 0.00 | 0.00 | 0.149239E+09 | 0.149233E+09 | 4668.74 | 14-MAR-13:00 | 4668.74 | 0.00 |
April | 0.00 | 0.00 | 22532687.94 | 22519561.01 | 1864.69 | 20-APR-13:00 | 1864.69 | 0.00 |
May | 0.00 | 0.00 | 0.136278E+10 | 0.135722E+10 | 17217.44 | 21-MAY-17:07 | 16269.41 | 0.00 |
June | 0.00 | 0.00 | 0.758372E+10 | 0.728551E+10 | 18492.32 | 17-JUN-18:32 | 14097.68 | 0.00 |
July | 0.00 | 0.00 | 0.818896E+10 | 0.774799E+10 | 19065.39 | 29-JUL-18:02 | 11818.40 | 0.00 |
August | 0.00 | 0.00 | 0.775201E+10 | 0.742897E+10 | 18637.07 | 04-AUG-22:18 | 11064.34 | 0.00 |
September | 0.00 | 0.00 | 0.521096E+10 | 0.517103E+10 | 17745.74 | 02-SEP-20:05 | 15513.28 | 0.00 |
October | 0.00 | 0.00 | 0.501823E+09 | 0.501819E+09 | 17180.52 | 09-OCT-17:06 | 17180.52 | 0.00 |
November | 0.00 | 0.00 | 57656934.13 | 57656874.82 | 2782.57 | 07-NOV-14:30 | 2782.57 | 0.00 |
December | 0.00 | 0.00 | 7060356.47 | 7060356.47 | 1410.91 | 17-DEC-18:20 | 1410.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.308408E+11 | 0.297331E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 647387.34 | 647387.34 | 834.40 | 834.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.818896E+10 | 0.774799E+10 | 19065.39 | 17180.52 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 806790.47 | 806790.47 | 313.19 | 20-JAN-14:00 | 313.19 | 0.00 |
February | 0.00 | 0.00 | 988.64 | 988.64 | 0.25 | 26-FEB-11:50 | 0.25 | 0.00 |
March | 0.00 | 0.00 | 0.140846E+09 | 0.140846E+09 | 4654.32 | 14-MAR-13:00 | 4654.32 | 0.00 |
April | 0.00 | 0.00 | 16016644.35 | 16016639.26 | 1797.35 | 20-APR-13:00 | 1797.35 | 0.00 |
May | 0.00 | 0.00 | 0.121034E+10 | 0.120798E+10 | 6027.51 | 17-MAY-13:00 | 6027.51 | 0.00 |
June | 0.00 | 0.00 | 0.601100E+10 | 0.581286E+10 | 10932.87 | 25-JUN-07:03 | 10932.87 | 0.00 |
July | 0.00 | 0.00 | 0.639220E+10 | 0.609870E+10 | 16445.04 | 16-JUL-07:03 | 16445.04 | 0.00 |
August | 0.00 | 0.00 | 0.601564E+10 | 0.584641E+10 | 9913.96 | 16-AUG-16:10 | 9913.96 | 0.00 |
September | 0.00 | 0.00 | 0.422878E+10 | 0.421144E+10 | 10108.61 | 13-SEP-06:03 | 9338.95 | 0.00 |
October | 0.00 | 0.00 | 0.447593E+09 | 0.447574E+09 | 6430.90 | 11-OCT-14:00 | 6430.90 | 0.00 |
November | 0.00 | 0.00 | 41772212.68 | 41772212.68 | 2567.48 | 07-NOV-14:00 | 2567.48 | 0.00 |
December | 0.00 | 0.00 | 4560876.20 | 4560876.20 | 1187.81 | 02-DEC-15:00 | 1187.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.245096E+11 | 0.238290E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 988.64 | 988.64 | 0.25 | 0.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.639220E+10 | 0.609870E+10 | 16445.04 | 16445.04 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 259409.63 | 259409.63 | 149.75 | 20-JAN-14:00 | 149.75 | 0.00 |
February | 0.00 | 0.00 | 708.07 | 708.07 | 0.18 | 26-FEB-12:50 | 0.18 | 0.00 |
March | 0.00 | 0.00 | 0.133554E+09 | 0.133554E+09 | 4548.46 | 14-MAR-13:00 | 4548.46 | 0.00 |
April | 0.00 | 0.00 | 12821690.40 | 12821680.30 | 1671.19 | 20-APR-13:00 | 1671.19 | 0.00 |
May | 0.00 | 0.00 | 0.117932E+10 | 0.117723E+10 | 5985.77 | 17-MAY-13:00 | 5985.77 | 0.00 |
June | 0.00 | 0.00 | 0.603462E+10 | 0.583617E+10 | 11272.95 | 25-JUN-07:03 | 11272.95 | 0.00 |
July | 0.00 | 0.00 | 0.643217E+10 | 0.613779E+10 | 17084.44 | 16-JUL-07:03 | 17084.44 | 0.00 |
August | 0.00 | 0.00 | 0.604446E+10 | 0.587399E+10 | 9934.14 | 16-AUG-16:10 | 9934.14 | 0.00 |
September | 0.00 | 0.00 | 0.423835E+10 | 0.422074E+10 | 10571.31 | 13-SEP-06:03 | 9750.86 | 0.00 |
October | 0.00 | 0.00 | 0.436607E+09 | 0.436591E+09 | 6402.28 | 11-OCT-14:00 | 6402.28 | 0.00 |
November | 0.00 | 0.00 | 34248772.87 | 34248772.87 | 2388.44 | 07-NOV-14:00 | 2388.44 | 0.00 |
December | 0.00 | 0.00 | 3448212.45 | 3448212.45 | 1059.84 | 02-DEC-15:00 | 1059.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.245499E+11 | 0.238669E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 708.07 | 708.07 | 0.18 | 0.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.643217E+10 | 0.613779E+10 | 17084.44 | 17084.44 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1404.86 | 1404.86 | 0.30 | 23-JAN-13:10 | 0.30 | 0.00 |
February | 0.00 | 0.00 | 199.97 | 199.97 | 0.11 | 18-FEB-12:30 | 0.11 | 0.00 |
March | 0.00 | 0.00 | 0.115375E+09 | 0.115375E+09 | 4231.06 | 14-MAR-13:00 | 4231.06 | 0.00 |
April | 0.00 | 0.00 | 7390497.67 | 7390497.67 | 1359.05 | 20-APR-13:00 | 1359.05 | 0.00 |
May | 0.00 | 0.00 | 0.107642E+10 | 0.107489E+10 | 5771.90 | 17-MAY-13:00 | 5771.90 | 0.00 |
June | 0.00 | 0.00 | 0.585931E+10 | 0.566876E+10 | 10207.13 | 26-JUN-16:10 | 10207.13 | 0.00 |
July | 0.00 | 0.00 | 0.625901E+10 | 0.597612E+10 | 15725.46 | 16-JUL-07:03 | 15725.46 | 0.00 |
August | 0.00 | 0.00 | 0.588313E+10 | 0.571947E+10 | 9804.21 | 16-AUG-16:10 | 9804.21 | 0.00 |
September | 0.00 | 0.00 | 0.409590E+10 | 0.407935E+10 | 9162.88 | 13-SEP-06:03 | 8484.56 | 0.00 |
October | 0.00 | 0.00 | 0.403463E+09 | 0.403460E+09 | 6224.75 | 11-OCT-14:00 | 6224.75 | 0.00 |
November | 0.00 | 0.00 | 23984712.14 | 23984712.14 | 2067.80 | 07-NOV-14:00 | 2067.80 | 0.00 |
December | 0.00 | 0.00 | 1493962.15 | 1493962.15 | 800.11 | 02-DEC-15:00 | 800.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.237255E+11 | 0.230703E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 199.97 | 199.97 | 0.11 | 0.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.625901E+10 | 0.597612E+10 | 15725.46 | 15725.46 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 80.09 | 80.09 | 0.13 | 20-JAN-13:10 | 0.13 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.164788E+09 | 0.164788E+09 | 5982.49 | 14-MAR-13:00 | 5982.49 | 0.00 |
April | 0.00 | 0.00 | 4328958.28 | 4328958.28 | 1726.67 | 20-APR-13:00 | 1726.67 | 0.00 |
May | 0.00 | 0.00 | 0.147640E+10 | 0.146890E+10 | 9374.25 | 17-MAY-13:00 | 9374.25 | 0.00 |
June | 0.00 | 0.00 | 0.957934E+10 | 0.915161E+10 | 30192.31 | 25-JUN-08:62 | 30192.31 | 0.00 |
July | 0.00 | 0.00 | 0.101770E+11 | 0.958000E+10 | 31045.64 | 23-JUL-08:62 | 29321.32 | 0.00 |
August | 0.00 | 0.00 | 0.982652E+10 | 0.941855E+10 | 19442.20 | 20-AUG-08:63 | 17697.74 | 0.00 |
September | 0.00 | 0.00 | 0.654514E+10 | 0.648241E+10 | 15204.95 | 09-SEP-13:00 | 15204.95 | 0.00 |
October | 0.00 | 0.00 | 0.637460E+09 | 0.637455E+09 | 10298.48 | 11-OCT-14:10 | 10298.48 | 0.00 |
November | 0.00 | 0.00 | 35675162.39 | 35675162.39 | 2936.69 | 07-NOV-14:00 | 2936.69 | 0.00 |
December | 0.00 | 0.00 | 1466270.29 | 1466270.29 | 894.34 | 02-DEC-15:00 | 894.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.384481E+11 | 0.369452E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101770E+11 | 0.958000E+10 | 31045.64 | 30192.31 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 25506.24 | 25506.24 | 24.35 | 24-JAN-14:30 | 24.35 | 0.00 |
February | 0.00 | 0.00 | 129.97 | 129.97 | 0.14 | 18-FEB-13:10 | 0.14 | 0.00 |
March | 0.00 | 0.00 | 94511002.69 | 94511002.69 | 3753.78 | 14-MAR-13:00 | 3753.78 | 0.00 |
April | 0.00 | 0.00 | 3236217.16 | 3236217.16 | 1054.28 | 20-APR-13:00 | 1054.28 | 0.00 |
May | 0.00 | 0.00 | 0.913919E+09 | 0.912567E+09 | 5500.69 | 17-MAY-13:00 | 5500.69 | 0.00 |
June | 0.00 | 0.00 | 0.553158E+10 | 0.534569E+10 | 14802.54 | 25-JUN-08:62 | 14802.54 | 0.00 |
July | 0.00 | 0.00 | 0.586750E+10 | 0.559775E+10 | 15392.17 | 23-JUL-08:62 | 14591.46 | 0.00 |
August | 0.00 | 0.00 | 0.562062E+10 | 0.545429E+10 | 9772.36 | 16-AUG-14:10 | 9772.36 | 0.00 |
September | 0.00 | 0.00 | 0.376629E+10 | 0.375117E+10 | 8506.12 | 09-SEP-13:00 | 8506.12 | 0.00 |
October | 0.00 | 0.00 | 0.356542E+09 | 0.356542E+09 | 6010.99 | 11-OCT-14:10 | 6010.99 | 0.00 |
November | 0.00 | 0.00 | 17727937.59 | 17727937.59 | 1729.60 | 07-NOV-14:00 | 1729.60 | 0.00 |
December | 0.00 | 0.00 | 1083556.15 | 1083556.15 | 653.07 | 02-DEC-15:00 | 653.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.221730E+11 | 0.215346E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 129.97 | 129.97 | 0.14 | 0.14 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.586750E+10 | 0.559775E+10 | 15392.17 | 14802.54 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1397.93 | 1397.93 | 1.79 | 23-JAN-14:00 | 1.79 | 0.00 |
February | 0.00 | 0.00 | 43.57 | 43.57 | 0.07 | 18-FEB-13:30 | 0.07 | 0.00 |
March | 0.00 | 0.00 | 90184799.45 | 90184799.45 | 3657.09 | 14-MAR-13:00 | 3657.09 | 0.00 |
April | 0.00 | 0.00 | 2753089.48 | 2753089.48 | 1014.95 | 20-APR-13:00 | 1014.95 | 0.00 |
May | 0.00 | 0.00 | 0.886273E+09 | 0.885068E+09 | 5422.62 | 17-MAY-13:00 | 5422.62 | 0.00 |
June | 0.00 | 0.00 | 0.546310E+10 | 0.528009E+10 | 14220.83 | 25-JUN-08:62 | 14220.83 | 0.00 |
July | 0.00 | 0.00 | 0.580111E+10 | 0.553555E+10 | 15226.38 | 16-JUL-08:62 | 15226.38 | 0.00 |
August | 0.00 | 0.00 | 0.556111E+10 | 0.539712E+10 | 9715.23 | 16-AUG-14:10 | 9715.23 | 0.00 |
September | 0.00 | 0.00 | 0.372311E+10 | 0.370828E+10 | 8453.13 | 09-SEP-13:00 | 8453.13 | 0.00 |
October | 0.00 | 0.00 | 0.349145E+09 | 0.349145E+09 | 5944.01 | 11-OCT-14:10 | 5944.01 | 0.00 |
November | 0.00 | 0.00 | 16832294.82 | 16832294.82 | 1685.06 | 07-NOV-14:00 | 1685.06 | 0.00 |
December | 0.00 | 0.00 | 969192.95 | 969192.95 | 620.55 | 02-DEC-15:00 | 620.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.218946E+11 | 0.212660E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 43.57 | 43.57 | 0.07 | 0.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.580111E+10 | 0.553555E+10 | 15226.38 | 15226.38 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 179.88 | 179.88 | 0.17 | 20-JAN-13:30 | 0.17 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 74815021.29 | 74815021.29 | 3342.80 | 14-MAR-13:00 | 3342.80 | 0.00 |
April | 0.00 | 0.00 | 1296271.58 | 1296271.58 | 807.46 | 20-APR-13:00 | 807.46 | 0.00 |
May | 0.00 | 0.00 | 0.793407E+09 | 0.792652E+09 | 5211.37 | 17-MAY-13:00 | 5211.37 | 0.00 |
June | 0.00 | 0.00 | 0.530217E+10 | 0.512651E+10 | 12065.61 | 25-JUN-08:62 | 12065.61 | 0.00 |
July | 0.00 | 0.00 | 0.564467E+10 | 0.539056E+10 | 15043.12 | 16-JUL-08:62 | 15043.12 | 0.00 |
August | 0.00 | 0.00 | 0.543700E+10 | 0.527843E+10 | 9633.72 | 16-AUG-14:10 | 9633.72 | 0.00 |
September | 0.00 | 0.00 | 0.362462E+10 | 0.361045E+10 | 8391.28 | 09-SEP-13:00 | 8391.28 | 0.00 |
October | 0.00 | 0.00 | 0.324626E+09 | 0.324626E+09 | 5782.32 | 11-OCT-14:10 | 5782.32 | 0.00 |
November | 0.00 | 0.00 | 13428420.29 | 13428420.29 | 1490.53 | 07-NOV-14:00 | 1490.53 | 0.00 |
December | 0.00 | 0.00 | 459608.02 | 459608.02 | 414.42 | 02-DEC-15:00 | 414.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.212165E+11 | 0.206132E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.564467E+10 | 0.539056E+10 | 15043.12 | 15043.12 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 54409473.73 | 54409473.73 | 3071.67 | 14-MAR-13:00 | 3071.67 | 0.00 |
April | 0.00 | 0.00 | 609527.41 | 609527.41 | 595.52 | 20-APR-13:00 | 595.52 | 0.00 |
May | 0.00 | 0.00 | 0.696300E+09 | 0.695649E+09 | 5129.32 | 17-MAY-13:00 | 5129.32 | 0.00 |
June | 0.00 | 0.00 | 0.540098E+10 | 0.522875E+10 | 10641.15 | 25-JUN-08:62 | 10641.15 | 0.00 |
July | 0.00 | 0.00 | 0.575995E+10 | 0.551376E+10 | 15717.06 | 16-JUL-08:62 | 15717.06 | 0.00 |
August | 0.00 | 0.00 | 0.568189E+10 | 0.551774E+10 | 10155.38 | 16-AUG-14:10 | 10155.38 | 0.00 |
September | 0.00 | 0.00 | 0.379216E+10 | 0.377748E+10 | 9022.97 | 09-SEP-13:00 | 9022.97 | 0.00 |
October | 0.00 | 0.00 | 0.319441E+09 | 0.319441E+09 | 5868.47 | 11-OCT-14:10 | 5868.47 | 0.00 |
November | 0.00 | 0.00 | 10662026.43 | 10662026.43 | 1332.96 | 07-NOV-14:00 | 1332.96 | 0.00 |
December | 0.00 | 0.00 | 11976.82 | 11976.82 | 19.81 | 02-DEC-15:00 | 19.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.217164E+11 | 0.211185E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.575995E+10 | 0.551774E+10 | 15717.06 | 15717.06 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.177438E+10 | 0.48 | 2172.55 | 01-JAN-08:61 | 1.08 |
February | 0.164592E+10 | 0.50 | 2172.55 | 01-FEB-08:61 | 1.08 |
March | 0.173217E+10 | 0.48 | 2172.55 | 01-MAR-08:61 | 1.08 |
April | 0.163282E+10 | 0.47 | 2172.55 | 01-APR-07:01 | 1.08 |
May | 0.158176E+10 | 0.44 | 2172.55 | 01-MAY-07:01 | 1.08 |
June | 0.154129E+10 | 0.44 | 1296.52 | 26-JUN-16:10 | 0.84 |
July | 0.158093E+10 | 0.44 | 1394.52 | 18-JUL-07:03 | 0.87 |
August | 0.158529E+10 | 0.44 | 1204.72 | 16-AUG-16:10 | 0.80 |
September | 0.153035E+10 | 0.44 | 950.63 | 09-SEP-13:00 | 0.69 |
October | 0.164408E+10 | 0.46 | 2172.55 | 23-OCT-07:01 | 1.08 |
November | 0.164145E+10 | 0.47 | 2172.55 | 01-NOV-07:01 | 1.08 |
December | 0.184232E+10 | 0.50 | 2172.55 | 01-DEC-08:61 | 1.08 |
Annual Sum or Average | 0.197328E+11 | 0.46 | |||
Minimum of Months | 0.153035E+10 | 0.44 | 950.63 | 0.69 | |
Maximum of Months | 0.184232E+10 | 0.50 | 2172.55 | 1.08 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166275E+10 | 0.60 | 1221.06 | 01-JAN-09:06 | 1.11 |
February | 0.152598E+10 | 0.62 | 1221.06 | 01-FEB-10:50 | 1.12 |
March | 0.181837E+10 | 0.63 | 1221.06 | 01-MAR-14:40 | 1.12 |
April | 0.175103E+10 | 0.64 | 1221.06 | 01-APR-12:20 | 1.12 |
May | 0.214694E+10 | 0.74 | 1221.06 | 02-MAY-08:20 | 1.12 |
June | 0.194491E+10 | 0.72 | 1221.06 | 03-JUN-09:30 | 1.10 |
July | 0.196985E+10 | 0.72 | 1221.06 | 01-JUL-15:00 | 1.12 |
August | 0.196559E+10 | 0.71 | 1221.06 | 02-AUG-13:20 | 1.11 |
September | 0.199546E+10 | 0.73 | 1221.06 | 01-SEP-14:50 | 1.11 |
October | 0.201587E+10 | 0.71 | 1221.06 | 03-OCT-11:20 | 1.11 |
November | 0.169284E+10 | 0.62 | 1221.06 | 01-NOV-16:10 | 1.12 |
December | 0.167942E+10 | 0.63 | 1221.06 | 06-DEC-14:30 | 1.12 |
Annual Sum or Average | 0.221690E+11 | 0.67 | |||
Minimum of Months | 0.152598E+10 | 0.60 | 1221.06 | 1.10 | |
Maximum of Months | 0.214694E+10 | 0.74 | 1221.06 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.180137E+10 | 0.60 | 1244.73 | 01-JAN-16:20 | 1.12 |
February | 0.163109E+10 | 0.61 | 1244.73 | 01-FEB-11:00 | 1.12 |
March | 0.183722E+10 | 0.62 | 1244.73 | 01-MAR-09:50 | 1.12 |
April | 0.174760E+10 | 0.61 | 1244.73 | 01-APR-08:15 | 1.12 |
May | 0.181929E+10 | 0.61 | 1244.73 | 07-MAY-12:00 | 1.12 |
June | 0.177448E+10 | 0.61 | 1244.73 | 03-JUN-06:30 | 1.11 |
July | 0.179241E+10 | 0.60 | 1244.73 | 05-JUL-08:30 | 1.11 |
August | 0.183722E+10 | 0.61 | 1244.73 | 02-AUG-07:40 | 1.12 |
September | 0.174760E+10 | 0.60 | 1244.73 | 01-SEP-18:00 | 1.11 |
October | 0.180137E+10 | 0.60 | 1244.73 | 18-OCT-15:20 | 1.12 |
November | 0.174760E+10 | 0.61 | 1244.73 | 01-NOV-10:10 | 1.12 |
December | 0.179241E+10 | 0.60 | 1244.73 | 05-DEC-16:30 | 1.12 |
Annual Sum or Average | 0.213297E+11 | 0.61 | |||
Minimum of Months | 0.163109E+10 | 0.60 | 1244.73 | 1.11 | |
Maximum of Months | 0.183722E+10 | 0.62 | 1244.73 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.181200E+10 | 0.60 | 1252.07 | 01-JAN-09:03 | 1.12 |
February | 0.164071E+10 | 0.61 | 1252.07 | 01-FEB-07:09 | 1.12 |
March | 0.184806E+10 | 0.62 | 1252.07 | 01-MAR-13:00 | 1.12 |
April | 0.175791E+10 | 0.61 | 1252.07 | 01-APR-08:00 | 1.12 |
May | 0.183003E+10 | 0.61 | 1252.07 | 01-MAY-07:09 | 1.12 |
June | 0.178495E+10 | 0.61 | 1252.07 | 03-JUN-08:40 | 1.10 |
July | 0.180298E+10 | 0.60 | 1252.07 | 01-JUL-06:50 | 1.12 |
August | 0.184806E+10 | 0.61 | 1252.07 | 03-AUG-07:00 | 1.11 |
September | 0.175791E+10 | 0.60 | 1252.07 | 01-SEP-07:05 | 1.11 |
October | 0.181200E+10 | 0.60 | 1252.07 | 07-OCT-10:30 | 1.12 |
November | 0.175791E+10 | 0.61 | 1252.07 | 01-NOV-07:00 | 1.12 |
December | 0.180298E+10 | 0.60 | 1252.07 | 01-DEC-08:02 | 1.12 |
Annual Sum or Average | 0.214555E+11 | 0.61 | |||
Minimum of Months | 0.164071E+10 | 0.60 | 1252.07 | 1.10 | |
Maximum of Months | 0.184806E+10 | 0.62 | 1252.07 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.179513E+10 | 0.60 | 1240.41 | 01-JAN-10:10 | 1.12 |
February | 0.162544E+10 | 0.61 | 1240.41 | 01-FEB-11:30 | 1.12 |
March | 0.183085E+10 | 0.62 | 1240.41 | 01-MAR-09:50 | 1.12 |
April | 0.174154E+10 | 0.61 | 1240.41 | 01-APR-14:00 | 1.12 |
May | 0.181299E+10 | 0.61 | 1240.41 | 02-MAY-08:00 | 1.12 |
June | 0.176833E+10 | 0.61 | 1240.41 | 04-JUN-10:20 | 1.11 |
July | 0.178619E+10 | 0.60 | 1240.41 | 01-JUL-06:40 | 1.12 |
August | 0.183085E+10 | 0.61 | 1240.41 | 02-AUG-08:50 | 1.12 |
September | 0.174154E+10 | 0.60 | 1240.41 | 03-SEP-08:30 | 1.11 |
October | 0.179513E+10 | 0.60 | 1240.41 | 23-OCT-18:00 | 1.12 |
November | 0.174154E+10 | 0.61 | 1240.41 | 01-NOV-17:50 | 1.12 |
December | 0.178619E+10 | 0.60 | 1240.41 | 05-DEC-18:10 | 1.12 |
Annual Sum or Average | 0.212557E+11 | 0.61 | |||
Minimum of Months | 0.162544E+10 | 0.60 | 1240.41 | 1.11 | |
Maximum of Months | 0.183085E+10 | 0.62 | 1240.41 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.130629E+10 | 0.36 | 2129.28 | 01-JAN-09:01 | 1.08 |
February | 0.121161E+10 | 0.36 | 2129.28 | 01-FEB-08:61 | 1.08 |
March | 0.128476E+10 | 0.36 | 2129.28 | 01-MAR-08:61 | 1.08 |
April | 0.119180E+10 | 0.34 | 2129.28 | 01-APR-07:01 | 1.08 |
May | 0.115491E+10 | 0.33 | 2129.28 | 01-MAY-07:01 | 1.08 |
June | 0.113316E+10 | 0.33 | 2129.28 | 25-JUN-08:62 | 1.08 |
July | 0.113849E+10 | 0.32 | 2129.28 | 16-JUL-08:62 | 1.08 |
August | 0.116852E+10 | 0.33 | 1199.93 | 16-AUG-14:10 | 0.81 |
September | 0.110430E+10 | 0.33 | 912.24 | 09-SEP-13:00 | 0.68 |
October | 0.119752E+10 | 0.34 | 2129.28 | 23-OCT-07:01 | 1.08 |
November | 0.121351E+10 | 0.35 | 2129.28 | 01-NOV-07:01 | 1.08 |
December | 0.135066E+10 | 0.36 | 2129.28 | 01-DEC-08:61 | 1.08 |
Annual Sum or Average | 0.144555E+11 | 0.34 | |||
Minimum of Months | 0.110430E+10 | 0.32 | 912.24 | 0.68 | |
Maximum of Months | 0.135066E+10 | 0.36 | 2129.28 | 1.08 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151794E+10 | 0.56 | 1136.52 | 01-JAN-11:40 | 1.12 |
February | 0.137473E+10 | 0.56 | 1136.52 | 01-FEB-11:20 | 1.12 |
March | 0.155067E+10 | 0.57 | 1136.52 | 01-MAR-09:20 | 1.12 |
April | 0.147293E+10 | 0.56 | 1136.52 | 01-APR-13:30 | 1.12 |
May | 0.153430E+10 | 0.56 | 1136.52 | 01-MAY-07:40 | 1.12 |
June | 0.149748E+10 | 0.57 | 1136.52 | 01-JUN-09:10 | 1.11 |
July | 0.150975E+10 | 0.55 | 1136.52 | 01-JUL-15:00 | 1.12 |
August | 0.155067E+10 | 0.57 | 1136.52 | 01-AUG-08:70 | 1.11 |
September | 0.147293E+10 | 0.56 | 1136.52 | 01-SEP-17:40 | 1.11 |
October | 0.151794E+10 | 0.56 | 1136.52 | 02-OCT-17:00 | 1.11 |
November | 0.147293E+10 | 0.56 | 1136.52 | 01-NOV-08:50 | 1.12 |
December | 0.150975E+10 | 0.56 | 1136.52 | 05-DEC-09:05 | 1.12 |
Annual Sum or Average | 0.179820E+11 | 0.56 | |||
Minimum of Months | 0.137473E+10 | 0.55 | 1136.52 | 1.11 | |
Maximum of Months | 0.155067E+10 | 0.57 | 1136.52 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150536E+10 | 0.56 | 1127.10 | 01-JAN-11:00 | 1.12 |
February | 0.136334E+10 | 0.56 | 1127.10 | 01-FEB-08:03 | 1.12 |
March | 0.153782E+10 | 0.57 | 1127.10 | 01-MAR-09:20 | 1.12 |
April | 0.146073E+10 | 0.56 | 1127.10 | 01-APR-09:30 | 1.12 |
May | 0.152159E+10 | 0.56 | 1127.10 | 01-MAY-07:50 | 1.12 |
June | 0.148507E+10 | 0.57 | 1127.10 | 01-JUN-09:20 | 1.11 |
July | 0.149724E+10 | 0.55 | 1127.10 | 01-JUL-07:03 | 1.12 |
August | 0.153782E+10 | 0.57 | 1127.10 | 01-AUG-08:00 | 1.11 |
September | 0.146073E+10 | 0.56 | 1127.10 | 01-SEP-08:20 | 1.11 |
October | 0.150536E+10 | 0.56 | 1127.10 | 07-OCT-11:50 | 1.12 |
November | 0.146073E+10 | 0.56 | 1127.10 | 01-NOV-07:09 | 1.12 |
December | 0.149724E+10 | 0.56 | 1127.10 | 01-DEC-08:15 | 1.12 |
Annual Sum or Average | 0.178330E+11 | 0.56 | |||
Minimum of Months | 0.136334E+10 | 0.55 | 1127.10 | 1.11 | |
Maximum of Months | 0.153782E+10 | 0.57 | 1127.10 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149004E+10 | 0.56 | 1115.63 | 01-JAN-09:07 | 1.12 |
February | 0.134947E+10 | 0.56 | 1115.63 | 20-FEB-10:00 | 1.12 |
March | 0.152217E+10 | 0.57 | 1115.63 | 18-MAR-07:08 | 1.12 |
April | 0.144586E+10 | 0.56 | 1115.63 | 01-APR-07:08 | 1.12 |
May | 0.150610E+10 | 0.56 | 1115.63 | 01-MAY-07:30 | 1.12 |
June | 0.146995E+10 | 0.57 | 1115.63 | 01-JUN-09:40 | 1.11 |
July | 0.148200E+10 | 0.55 | 1115.63 | 01-JUL-07:10 | 1.12 |
August | 0.152217E+10 | 0.57 | 1115.63 | 01-AUG-08:70 | 1.11 |
September | 0.144586E+10 | 0.56 | 1115.63 | 01-SEP-08:30 | 1.11 |
October | 0.149004E+10 | 0.56 | 1115.63 | 01-OCT-09:10 | 1.11 |
November | 0.144586E+10 | 0.56 | 1115.63 | 20-NOV-20:10 | 1.12 |
December | 0.148209E+10 | 0.56 | 1115.63 | 01-DEC-08:50 | 1.12 |
Annual Sum or Average | 0.176516E+11 | 0.56 | |||
Minimum of Months | 0.134947E+10 | 0.55 | 1115.63 | 1.11 | |
Maximum of Months | 0.152217E+10 | 0.57 | 1115.63 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154544E+10 | 0.56 | 1156.50 | 06-JAN-13:10 | 1.12 |
February | 0.140536E+10 | 0.59 | 1156.50 | 06-FEB-17:00 | 1.12 |
March | 0.157993E+10 | 0.58 | 1156.50 | 01-MAR-08:08 | 1.12 |
April | 0.149950E+10 | 0.56 | 1156.50 | 05-APR-17:30 | 1.12 |
May | 0.156128E+10 | 0.56 | 1156.50 | 09-MAY-16:40 | 1.12 |
June | 0.152380E+10 | 0.57 | 1156.50 | 02-JUN-14:10 | 1.11 |
July | 0.153629E+10 | 0.55 | 1156.50 | 01-JUL-07:10 | 1.12 |
August | 0.157793E+10 | 0.57 | 1156.50 | 01-AUG-13:40 | 1.12 |
September | 0.149882E+10 | 0.56 | 1156.50 | 05-SEP-07:50 | 1.11 |
October | 0.154462E+10 | 0.56 | 1156.50 | 02-OCT-11:10 | 1.11 |
November | 0.149901E+10 | 0.56 | 1156.50 | 02-NOV-13:30 | 1.12 |
December | 0.154587E+10 | 0.59 | 1156.50 | 01-DEC-08:09 | 1.12 |
Annual Sum or Average | 0.183179E+11 | 0.57 | |||
Minimum of Months | 0.140536E+10 | 0.55 | 1156.50 | 1.11 | |
Maximum of Months | 0.157993E+10 | 0.59 | 1156.50 | 1.12 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.177438E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.164592E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.177748E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.163520E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.201304E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.454713E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.480306E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.461560E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.354036E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.183546E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.165727E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.184272E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.316876E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.163520E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.480306E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.166354E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.152613E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.185089E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.175617E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.244477E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.362353E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.377229E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.364984E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.311441E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.212253E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.170572E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.168105E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.289109E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.152613E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.377229E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.180156E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.163109E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.186808E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.175127E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.208723E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.313476E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.322757E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.317577E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.267236E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.189728E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.175698E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.179346E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.267974E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.163109E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.322757E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.181206E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.164071E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.187743E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.176085E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.209175E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.315111E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.324723E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.319339E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.268525E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.190569E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.176562E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.180378E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.269349E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.164071E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.324723E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.179513E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.162544E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.185641E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.174325E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.205327E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.309871E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.319531E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.314366E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.264033E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.188194E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.174697E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.178654E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.265670E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.162544E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.319531E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.130629E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.121161E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.132706E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.119295E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.153730E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.362896E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.376156E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.367814E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.275221E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.135576E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.122284E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.135106E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.243257E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.119295E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.376156E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.151794E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.137473E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.157168E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.147368E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.173878E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.275173E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.282612E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.280045E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.229653E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.159448E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.147696E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.151001E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.229331E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.137473E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.282612E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.150536E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.136334E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.155791E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.146137E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.172017E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.272454E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.279923E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.277470E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.227506E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.158037E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.146455E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.149747E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.227241E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.136334E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.279923E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.149004E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134947E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.153897E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.144616E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.168501E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.267620E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.275179E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.273325E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.223986E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.156003E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.144893E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.148220E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.224019E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.134947E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.275179E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.154544E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.140536E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159232E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.149964E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.171993E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.275617E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.283539E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.284147E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.232731E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.161375E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.150146E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.154587E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.231841E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.140536E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.284147E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.177438E+10 | 255.49 | 0.804123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164592E+10 | 0.00 | 0.889333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173217E+10 | 0.176986E+09 | 0.604509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163282E+10 | 8926767.90 | 0.430272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158176E+10 | 0.167021E+10 | 0.200960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154129E+10 | 0.116181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158093E+10 | 0.125285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158529E+10 | 0.119297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153035E+10 | 0.802283E+10 | 8805054.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164408E+10 | 0.775034E+09 | 0.272927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164145E+10 | 61061126.95 | 0.478908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184232E+10 | 1503574.43 | 0.105416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197328E+11 | 0.467928E+11 | 0.455521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184232E+10 | 0.125285E+11 | 0.105416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166275E+10 | 3420715.07 | 0.173552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152598E+10 | 647387.34 | 0.208802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181837E+10 | 0.149239E+09 | 0.121955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.175103E+10 | 22532687.94 | 0.716789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214694E+10 | 0.136278E+10 | 3262678.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194491E+10 | 0.758372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.196985E+10 | 0.818896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196559E+10 | 0.775201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.199546E+10 | 0.521096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201587E+10 | 0.501823E+09 | 0.667702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169284E+10 | 57656934.13 | 0.938046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167942E+10 | 7060356.47 | 0.277130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221690E+11 | 0.308408E+11 | 0.101402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152598E+10 | 647387.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.214694E+10 | 0.818896E+10 | 0.277130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.180137E+10 | 806790.47 | 0.205493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163109E+10 | 988.64 | 0.236638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183722E+10 | 0.140846E+09 | 0.142717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174760E+10 | 16016644.35 | 0.860604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181929E+10 | 0.121034E+10 | 10084743.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.177448E+10 | 0.601100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.179241E+10 | 0.639220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.183722E+10 | 0.601564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174760E+10 | 0.422878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180137E+10 | 0.447593E+09 | 0.747303E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174760E+10 | 41772212.68 | 0.112447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179241E+10 | 4560876.20 | 0.305934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213297E+11 | 0.245096E+11 | 0.116503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.163109E+10 | 988.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.183722E+10 | 0.639220E+10 | 0.305934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.181200E+10 | 259409.63 | 0.219255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164071E+10 | 708.07 | 0.248831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184806E+10 | 0.133554E+09 | 0.152197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.175791E+10 | 12821690.40 | 0.939606E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183003E+10 | 0.117932E+10 | 15852458.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.178495E+10 | 0.603462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.180298E+10 | 0.643217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.184806E+10 | 0.604446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.175791E+10 | 0.423835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181200E+10 | 0.436607E+09 | 0.788906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175791E+10 | 34248772.87 | 0.121634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180298E+10 | 3448212.45 | 0.320328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214555E+11 | 0.245499E+11 | 0.123668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.164071E+10 | 708.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184806E+10 | 0.643217E+10 | 0.320328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.179513E+10 | 1404.86 | 0.245678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162544E+10 | 199.97 | 0.275482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183085E+10 | 0.115375E+09 | 0.173340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174154E+10 | 7390497.67 | 0.111072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181299E+10 | 0.107642E+10 | 30316454.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.176833E+10 | 0.585931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178619E+10 | 0.625901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.183085E+10 | 0.588313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174154E+10 | 0.409590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179513E+10 | 0.403463E+09 | 0.874146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174154E+10 | 23984712.14 | 0.140981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178619E+10 | 1493962.15 | 0.349745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212557E+11 | 0.237255E+11 | 0.138674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162544E+10 | 199.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.183085E+10 | 0.625901E+10 | 0.349745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.130629E+10 | 80.09 | 0.695955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121161E+10 | 0.00 | 0.748039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128476E+10 | 0.164788E+09 | 0.505988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119180E+10 | 4328958.28 | 0.362842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115491E+10 | 0.147640E+10 | 0.210302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113316E+10 | 0.957934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113849E+10 | 0.101770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116852E+10 | 0.982652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110430E+10 | 0.654514E+10 | 9432920.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119752E+10 | 0.637460E+09 | 0.247338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121351E+10 | 35675162.39 | 0.452391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135066E+10 | 1466270.29 | 0.904236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144555E+11 | 0.384481E+11 | 0.393876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135066E+10 | 0.101770E+11 | 0.904236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151794E+10 | 25506.24 | 0.303407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137473E+10 | 129.97 | 0.332707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155067E+10 | 94511002.69 | 0.218005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147293E+10 | 3236217.16 | 0.149070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153430E+10 | 0.913919E+09 | 58960615.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149748E+10 | 0.553158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150975E+10 | 0.586750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155067E+10 | 0.562062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147293E+10 | 0.376629E+10 | 432023.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151794E+10 | 0.356542E+09 | 0.109003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147293E+10 | 17727937.59 | 0.187589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150975E+10 | 1083556.15 | 0.412657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179820E+11 | 0.221730E+11 | 0.171838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137473E+10 | 129.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155067E+10 | 0.586750E+10 | 0.412657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150536E+10 | 1397.93 | 0.311731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136334E+10 | 43.57 | 0.340667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153782E+10 | 90184799.45 | 0.224621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146073E+10 | 2753089.48 | 0.154634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152159E+10 | 0.886273E+09 | 66190665.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148507E+10 | 0.546310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149724E+10 | 0.580111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153782E+10 | 0.556111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146073E+10 | 0.372311E+10 | 540133.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150536E+10 | 0.349145E+09 | 0.111238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146073E+10 | 16832294.82 | 0.193204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149724E+10 | 969192.95 | 0.419777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178330E+11 | 0.218946E+11 | 0.176255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136334E+10 | 43.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153782E+10 | 0.580111E+10 | 0.419777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149004E+10 | 179.88 | 0.348830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134947E+10 | 0.00 | 0.376421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152217E+10 | 74815021.29 | 0.254743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144586E+10 | 1296271.58 | 0.180954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150610E+10 | 0.793407E+09 | 97859120.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146995E+10 | 0.530217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148200E+10 | 0.564467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152217E+10 | 0.543700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144586E+10 | 0.362462E+10 | 1231490.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149004E+10 | 0.324626E+09 | 0.121847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144586E+10 | 13428420.29 | 0.217250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148209E+10 | 459608.02 | 0.454041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176516E+11 | 0.212165E+11 | 0.196400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152217E+10 | 0.564467E+10 | 0.454041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154544E+10 | 0.00 | 0.485521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140536E+10 | 0.00 | 0.527483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157993E+10 | 54409473.73 | 0.378551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149950E+10 | 609527.41 | 0.282807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156128E+10 | 0.696300E+09 | 0.223489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152380E+10 | 0.540098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153629E+10 | 0.575995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157793E+10 | 0.568189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149882E+10 | 0.379216E+10 | 12266113.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154462E+10 | 0.319441E+09 | 0.166423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149901E+10 | 10662026.43 | 0.297950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154587E+10 | 11976.82 | 0.606928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183179E+11 | 0.217164E+11 | 0.276924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157993E+10 | 0.575995E+10 | 0.606928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.177438E+10 | 0.00 | 0.00 | 0.00 | 68.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173217E+10 | 0.00 | 0.00 | 0.00 | 45312811.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163282E+10 | 0.00 | 0.00 | 0.00 | 2378058.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158176E+10 | 0.00 | 0.00 | 0.00 | 0.431279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154129E+10 | 0.00 | 0.00 | 0.00 | 0.300583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158093E+10 | 0.00 | 0.00 | 0.00 | 0.322213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158529E+10 | 0.00 | 0.00 | 0.00 | 0.303032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153035E+10 | 0.00 | 0.00 | 0.00 | 0.201001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164408E+10 | 0.00 | 0.00 | 0.00 | 0.191386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164145E+10 | 0.00 | 0.00 | 0.00 | 15825126.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184232E+10 | 0.00 | 0.00 | 0.00 | 403683.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197328E+11 | 0.00 | 0.00 | 0.00 | 0.119549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184232E+10 | 0.00 | 0.00 | 0.00 | 0.322213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.166275E+10 | 0.00 | 0.00 | 0.00 | 785959.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152598E+10 | 0.00 | 0.00 | 0.00 | 146246.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181837E+10 | 0.00 | 0.00 | 0.00 | 32523597.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.175103E+10 | 0.00 | 0.00 | 0.00 | 5144276.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214694E+10 | 0.00 | 0.00 | 0.00 | 0.297822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194491E+10 | 0.00 | 0.00 | 0.00 | 0.167862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.196985E+10 | 0.00 | 0.00 | 0.00 | 0.180244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196559E+10 | 0.00 | 0.00 | 0.00 | 0.168425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.199546E+10 | 0.00 | 0.00 | 0.00 | 0.111895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201587E+10 | 0.00 | 0.00 | 0.00 | 0.106661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169284E+10 | 0.00 | 0.00 | 0.00 | 12882066.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167942E+10 | 0.00 | 0.00 | 0.00 | 1624279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221690E+11 | 0.00 | 0.00 | 0.00 | 0.674184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152598E+10 | 0.00 | 0.00 | 0.00 | 146246.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.214694E+10 | 0.00 | 0.00 | 0.00 | 0.180244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.180137E+10 | 0.00 | 0.00 | 0.00 | 187823.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163109E+10 | 0.00 | 0.00 | 0.00 | 232.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183722E+10 | 0.00 | 0.00 | 0.00 | 30858102.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174760E+10 | 0.00 | 0.00 | 0.00 | 3667887.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181929E+10 | 0.00 | 0.00 | 0.00 | 0.267933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.177448E+10 | 0.00 | 0.00 | 0.00 | 0.136028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.179241E+10 | 0.00 | 0.00 | 0.00 | 0.143516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.183722E+10 | 0.00 | 0.00 | 0.00 | 0.133855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174760E+10 | 0.00 | 0.00 | 0.00 | 0.924762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180137E+10 | 0.00 | 0.00 | 0.00 | 95913101.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174760E+10 | 0.00 | 0.00 | 0.00 | 9383324.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179241E+10 | 0.00 | 0.00 | 0.00 | 1053571.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213297E+11 | 0.00 | 0.00 | 0.00 | 0.546775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.163109E+10 | 0.00 | 0.00 | 0.00 | 232.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.183722E+10 | 0.00 | 0.00 | 0.00 | 0.143516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.181200E+10 | 0.00 | 0.00 | 0.00 | 60655.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164071E+10 | 0.00 | 0.00 | 0.00 | 166.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184806E+10 | 0.00 | 0.00 | 0.00 | 29368832.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.175791E+10 | 0.00 | 0.00 | 0.00 | 2945631.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183003E+10 | 0.00 | 0.00 | 0.00 | 0.261720E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.178495E+10 | 0.00 | 0.00 | 0.00 | 0.136616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.180298E+10 | 0.00 | 0.00 | 0.00 | 0.144425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.184806E+10 | 0.00 | 0.00 | 0.00 | 0.134533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.175791E+10 | 0.00 | 0.00 | 0.00 | 0.927341E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181200E+10 | 0.00 | 0.00 | 0.00 | 93693054.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175791E+10 | 0.00 | 0.00 | 0.00 | 7716373.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180298E+10 | 0.00 | 0.00 | 0.00 | 799167.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214555E+11 | 0.00 | 0.00 | 0.00 | 0.547938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.164071E+10 | 0.00 | 0.00 | 0.00 | 166.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184806E+10 | 0.00 | 0.00 | 0.00 | 0.144425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.179513E+10 | 0.00 | 0.00 | 0.00 | 329.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162544E+10 | 0.00 | 0.00 | 0.00 | 46.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183085E+10 | 0.00 | 0.00 | 0.00 | 25556194.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174154E+10 | 0.00 | 0.00 | 0.00 | 1709109.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181299E+10 | 0.00 | 0.00 | 0.00 | 0.240286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.176833E+10 | 0.00 | 0.00 | 0.00 | 0.133038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178619E+10 | 0.00 | 0.00 | 0.00 | 0.140912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.183085E+10 | 0.00 | 0.00 | 0.00 | 0.131282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174154E+10 | 0.00 | 0.00 | 0.00 | 0.898786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179513E+10 | 0.00 | 0.00 | 0.00 | 86817794.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174154E+10 | 0.00 | 0.00 | 0.00 | 5430935.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178619E+10 | 0.00 | 0.00 | 0.00 | 347818.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212557E+11 | 0.00 | 0.00 | 0.00 | 0.531124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162544E+10 | 0.00 | 0.00 | 0.00 | 46.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.183085E+10 | 0.00 | 0.00 | 0.00 | 0.140912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.130629E+10 | 0.00 | 0.00 | 0.00 | 21.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128476E+10 | 0.00 | 0.00 | 0.00 | 42294717.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119180E+10 | 0.00 | 0.00 | 0.00 | 1152118.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115491E+10 | 0.00 | 0.00 | 0.00 | 0.382384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113316E+10 | 0.00 | 0.00 | 0.00 | 0.249579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113849E+10 | 0.00 | 0.00 | 0.00 | 0.262307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116852E+10 | 0.00 | 0.00 | 0.00 | 0.250962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110430E+10 | 0.00 | 0.00 | 0.00 | 0.164791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119752E+10 | 0.00 | 0.00 | 0.00 | 0.158245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121351E+10 | 0.00 | 0.00 | 0.00 | 9333036.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135066E+10 | 0.00 | 0.00 | 0.00 | 394128.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144555E+11 | 0.00 | 0.00 | 0.00 | 0.987019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135066E+10 | 0.00 | 0.00 | 0.00 | 0.262307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.151794E+10 | 0.00 | 0.00 | 0.00 | 5982.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137473E+10 | 0.00 | 0.00 | 0.00 | 30.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155067E+10 | 0.00 | 0.00 | 0.00 | 21015298.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147293E+10 | 0.00 | 0.00 | 0.00 | 753447.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153430E+10 | 0.00 | 0.00 | 0.00 | 0.204477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149748E+10 | 0.00 | 0.00 | 0.00 | 0.125425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150975E+10 | 0.00 | 0.00 | 0.00 | 0.131637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155067E+10 | 0.00 | 0.00 | 0.00 | 0.124978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147293E+10 | 0.00 | 0.00 | 0.00 | 0.823598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151794E+10 | 0.00 | 0.00 | 0.00 | 76542425.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147293E+10 | 0.00 | 0.00 | 0.00 | 4028242.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150975E+10 | 0.00 | 0.00 | 0.00 | 252967.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179820E+11 | 0.00 | 0.00 | 0.00 | 0.495107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137473E+10 | 0.00 | 0.00 | 0.00 | 30.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155067E+10 | 0.00 | 0.00 | 0.00 | 0.131637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.150536E+10 | 0.00 | 0.00 | 0.00 | 328.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136334E+10 | 0.00 | 0.00 | 0.00 | 10.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153782E+10 | 0.00 | 0.00 | 0.00 | 20090899.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146073E+10 | 0.00 | 0.00 | 0.00 | 640803.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152159E+10 | 0.00 | 0.00 | 0.00 | 0.198583E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148507E+10 | 0.00 | 0.00 | 0.00 | 0.123947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149724E+10 | 0.00 | 0.00 | 0.00 | 0.130198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153782E+10 | 0.00 | 0.00 | 0.00 | 0.123688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146073E+10 | 0.00 | 0.00 | 0.00 | 0.814338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150536E+10 | 0.00 | 0.00 | 0.00 | 75010624.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146073E+10 | 0.00 | 0.00 | 0.00 | 3827704.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149724E+10 | 0.00 | 0.00 | 0.00 | 226434.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178330E+11 | 0.00 | 0.00 | 0.00 | 0.489105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136334E+10 | 0.00 | 0.00 | 0.00 | 10.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153782E+10 | 0.00 | 0.00 | 0.00 | 0.130198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149004E+10 | 0.00 | 0.00 | 0.00 | 42.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152217E+10 | 0.00 | 0.00 | 0.00 | 16803051.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144586E+10 | 0.00 | 0.00 | 0.00 | 301871.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150610E+10 | 0.00 | 0.00 | 0.00 | 0.178908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146995E+10 | 0.00 | 0.00 | 0.00 | 0.120624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148200E+10 | 0.00 | 0.00 | 0.00 | 0.126979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152217E+10 | 0.00 | 0.00 | 0.00 | 0.121109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144586E+10 | 0.00 | 0.00 | 0.00 | 0.794004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149004E+10 | 0.00 | 0.00 | 0.00 | 69991636.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144586E+10 | 0.00 | 0.00 | 0.00 | 3068980.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148209E+10 | 0.00 | 0.00 | 0.00 | 108054.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176516E+11 | 0.00 | 0.00 | 0.00 | 0.475030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152217E+10 | 0.00 | 0.00 | 0.00 | 0.126979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157993E+10 | 0.00 | 0.00 | 0.00 | 12386546.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149950E+10 | 0.00 | 0.00 | 0.00 | 142682.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156128E+10 | 0.00 | 0.00 | 0.00 | 0.158656E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152380E+10 | 0.00 | 0.00 | 0.00 | 0.123237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153629E+10 | 0.00 | 0.00 | 0.00 | 0.129910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157793E+10 | 0.00 | 0.00 | 0.00 | 0.126354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149882E+10 | 0.00 | 0.00 | 0.00 | 0.828488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154462E+10 | 0.00 | 0.00 | 0.00 | 69124386.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149901E+10 | 0.00 | 0.00 | 0.00 | 2454019.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154587E+10 | 0.00 | 0.00 | 0.00 | 2853.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183179E+11 | 0.00 | 0.00 | 0.00 | 0.486626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157993E+10 | 0.00 | 0.00 | 0.00 | 0.129910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.453772E+10 | 0.00 | 0.00 | 28405.55 | 0.00 | 0.475360E+10 | 46116548.55 | 0.00 | 0.35 |
February | 0.342634E+10 | 0.00 | 0.00 | 7528.23 | 0.00 | 0.532146E+10 | 14153481.27 | 0.00 | 0.35 |
March | 0.359982E+10 | 0.00 | 0.00 | 1120452.72 | 0.00 | 0.340384E+10 | 0.903136E+09 | 0.00 | 0.40 |
April | 0.385515E+10 | 0.00 | 0.00 | 403131.18 | 0.00 | 0.258447E+10 | 0.488777E+09 | 0.00 | 0.38 |
May | 0.190173E+10 | 31331835.63 | 0.00 | 5735606.88 | 0.00 | 71839964.63 | 0.344088E+10 | 0.00 | 0.60 |
June | 19475292.83 | 0.105977E+10 | 0.00 | 11466302.20 | 225163.81 | 0.00 | 0.237258E+10 | 0.00 | 0.70 |
July | 13230792.64 | 0.124095E+10 | 0.00 | 11379386.88 | 5278.62 | 0.00 | 0.225767E+10 | 0.00 | 0.70 |
August | 9249971.32 | 0.929544E+09 | 0.00 | 14935388.44 | 0.00 | 0.00 | 0.291266E+10 | 0.00 | 0.76 |
September | 0.470910E+09 | 0.321624E+09 | 0.00 | 14623753.80 | 0.00 | 1275728.70 | 0.394087E+10 | 0.00 | 0.80 |
October | 0.328186E+10 | 1768587.46 | 0.00 | 4651285.08 | 0.00 | 0.159982E+10 | 0.325961E+10 | 0.00 | 0.51 |
November | 0.526400E+10 | 0.00 | 0.00 | 688470.43 | 0.00 | 0.251697E+10 | 0.664256E+09 | 0.00 | 0.39 |
December | 0.413874E+10 | 0.00 | 0.00 | 74604.85 | 0.00 | 0.602820E+10 | 0.110979E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.305182E+11 | 0.358499E+10 | 0.00 | 65114316.24 | 230442.44 | 0.262815E+11 | 0.204117E+11 | 0.00 | 0.53 |
Minimum of Months | 9249971.32 | 0.00 | 0.00 | 7528.23 | 0.00 | 0.00 | 14153481.27 | 0.00 | 0.35 |
Maximum of Months | 0.526400E+10 | 0.124095E+10 | 0.00 | 14935388.44 | 225163.81 | 0.602820E+10 | 0.394087E+10 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186545E+10 | 0.00 | 0.00 | 178266.23 | 0.00 | 0.137369E+10 | 0.322332E+09 | 0.00 | 0.29 |
February | 0.161551E+10 | 0.00 | 0.00 | 109140.20 | 0.00 | 0.146173E+10 | 0.212192E+09 | 0.00 | 0.28 |
March | 0.122931E+10 | 0.00 | 0.00 | 1209614.21 | 0.00 | 0.111799E+10 | 0.128811E+10 | 0.00 | 0.45 |
April | 0.131232E+10 | 0.00 | 0.00 | 885294.44 | 0.00 | 0.630140E+09 | 0.128198E+10 | 0.00 | 0.43 |
May | 0.353925E+09 | 16693951.97 | 0.00 | 4477788.12 | 0.00 | 0.00 | 0.378595E+10 | 0.00 | 0.97 |
June | 13699729.86 | 0.523416E+09 | 0.00 | 4462402.36 | 283188.63 | 0.00 | 0.157632E+10 | 0.00 | 0.85 |
July | 12484212.48 | 0.622003E+09 | 0.00 | 4097146.79 | 1665221.67 | 0.00 | 0.141826E+10 | 0.00 | 0.81 |
August | 24491397.35 | 0.475830E+09 | 0.00 | 5610121.17 | 175657.15 | 0.00 | 0.182619E+10 | 0.00 | 0.90 |
September | 0.140916E+09 | 0.161101E+09 | 0.00 | 6490541.04 | 0.00 | 0.00 | 0.286505E+10 | 0.00 | 1.09 |
October | 0.952077E+09 | 1186363.97 | 0.00 | 3636094.02 | 0.00 | 0.506291E+09 | 0.334625E+10 | 0.00 | 0.70 |
November | 0.202645E+10 | 0.00 | 0.00 | 824179.19 | 0.00 | 0.688449E+09 | 0.928487E+09 | 0.00 | 0.39 |
December | 0.149677E+10 | 0.00 | 0.00 | 230779.01 | 0.00 | 0.203325E+10 | 0.360035E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.110434E+11 | 0.180023E+10 | 0.00 | 32211366.78 | 2124067.45 | 0.781153E+10 | 0.192112E+11 | 0.00 | 0.62 |
Minimum of Months | 12484212.48 | 0.00 | 0.00 | 109140.20 | 0.00 | 0.00 | 0.212192E+09 | 0.00 | 0.28 |
Maximum of Months | 0.202645E+10 | 0.622003E+09 | 0.00 | 6490541.04 | 1665221.67 | 0.203325E+10 | 0.378595E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147649E+10 | 0.00 | 0.00 | 104247.50 | 0.00 | 0.167194E+10 | 0.217553E+09 | 0.00 | 0.29 |
February | 0.125351E+10 | 0.00 | 0.00 | 35617.61 | 0.00 | 0.176579E+10 | 95469838.05 | 0.00 | 0.27 |
March | 0.112694E+10 | 0.00 | 0.00 | 799319.15 | 0.00 | 0.123913E+10 | 0.832985E+09 | 0.00 | 0.41 |
April | 0.128041E+10 | 0.00 | 0.00 | 490896.86 | 0.00 | 0.740189E+09 | 0.767432E+09 | 0.00 | 0.39 |
May | 0.488019E+09 | 17352386.59 | 0.00 | 2586161.88 | 0.00 | 9700327.19 | 0.220381E+10 | 0.00 | 0.76 |
June | 41178923.89 | 0.475069E+09 | 0.00 | 2007648.99 | 14008440.23 | 0.00 | 0.957610E+09 | 0.00 | 0.67 |
July | 42913015.36 | 0.544179E+09 | 0.00 | 1691177.74 | 19331759.60 | 0.00 | 0.811189E+09 | 0.00 | 0.65 |
August | 48564087.51 | 0.421961E+09 | 0.00 | 2566713.89 | 5602274.64 | 0.00 | 0.134194E+10 | 0.00 | 0.72 |
September | 0.206490E+09 | 0.150778E+09 | 0.00 | 3501911.08 | 2578234.90 | 0.00 | 0.165080E+10 | 0.00 | 0.85 |
October | 0.103630E+10 | 1392720.33 | 0.00 | 2197573.87 | 0.00 | 0.574586E+09 | 0.202653E+10 | 0.00 | 0.58 |
November | 0.174494E+10 | 0.00 | 0.00 | 519119.94 | 0.00 | 0.897856E+09 | 0.601800E+09 | 0.00 | 0.37 |
December | 0.129780E+10 | 0.00 | 0.00 | 98910.32 | 0.00 | 0.217149E+10 | 0.195770E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.100436E+11 | 0.161073E+10 | 0.00 | 16599298.84 | 41520709.37 | 0.907068E+10 | 0.117029E+11 | 0.00 | 0.52 |
Minimum of Months | 41178923.89 | 0.00 | 0.00 | 35617.61 | 0.00 | 0.00 | 95469838.05 | 0.00 | 0.27 |
Maximum of Months | 0.174494E+10 | 0.544179E+09 | 0.00 | 3501911.08 | 19331759.60 | 0.217149E+10 | 0.220381E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137913E+10 | 0.00 | 0.00 | 72096.66 | 0.00 | 0.179054E+10 | 0.169089E+09 | 0.00 | 0.28 |
February | 0.116353E+10 | 0.00 | 0.00 | 24397.85 | 0.00 | 0.186432E+10 | 71859852.40 | 0.00 | 0.27 |
March | 0.108737E+10 | 0.00 | 0.00 | 738417.27 | 0.00 | 0.128894E+10 | 0.788624E+09 | 0.00 | 0.41 |
April | 0.120958E+10 | 0.00 | 0.00 | 423171.17 | 0.00 | 0.833121E+09 | 0.696049E+09 | 0.00 | 0.38 |
May | 0.501882E+09 | 17354358.31 | 0.00 | 2477797.68 | 0.00 | 18883089.13 | 0.213839E+10 | 0.00 | 0.75 |
June | 40988107.59 | 0.475207E+09 | 0.00 | 2019323.43 | 13975974.53 | 0.00 | 0.964235E+09 | 0.00 | 0.68 |
July | 42704740.17 | 0.544799E+09 | 0.00 | 1715542.56 | 19292589.02 | 0.00 | 0.818543E+09 | 0.00 | 0.66 |
August | 48533478.22 | 0.422418E+09 | 0.00 | 2596653.12 | 5596213.95 | 0.00 | 0.135305E+10 | 0.00 | 0.72 |
September | 0.207043E+09 | 0.150779E+09 | 0.00 | 3505735.58 | 2561900.19 | 0.00 | 0.165537E+10 | 0.00 | 0.85 |
October | 0.102691E+10 | 1396171.60 | 0.00 | 2114601.87 | 0.00 | 0.596259E+09 | 0.197536E+10 | 0.00 | 0.57 |
November | 0.168789E+10 | 0.00 | 0.00 | 461604.46 | 0.00 | 0.962727E+09 | 0.557444E+09 | 0.00 | 0.36 |
December | 0.124142E+10 | 0.00 | 0.00 | 74143.22 | 0.00 | 0.223928E+10 | 0.163249E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.963699E+10 | 0.161195E+10 | 0.00 | 16223484.85 | 41426677.69 | 0.959406E+10 | 0.113513E+11 | 0.00 | 0.52 |
Minimum of Months | 40988107.59 | 0.00 | 0.00 | 24397.85 | 0.00 | 0.00 | 71859852.40 | 0.00 | 0.27 |
Maximum of Months | 0.168789E+10 | 0.544799E+09 | 0.00 | 3505735.58 | 19292589.02 | 0.223928E+10 | 0.213839E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125797E+10 | 0.00 | 0.00 | 27415.32 | 0.00 | 0.194679E+10 | 81005710.64 | 0.00 | 0.27 |
February | 0.101247E+10 | 0.00 | 0.00 | 12104.88 | 0.00 | 0.202882E+10 | 32843311.55 | 0.00 | 0.27 |
March | 0.102422E+10 | 0.00 | 0.00 | 579968.55 | 0.00 | 0.139397E+10 | 0.644675E+09 | 0.00 | 0.39 |
April | 0.110864E+10 | 0.00 | 0.00 | 268766.86 | 0.00 | 0.989693E+09 | 0.515731E+09 | 0.00 | 0.35 |
May | 0.557833E+09 | 17336988.56 | 0.00 | 2089951.92 | 0.00 | 28017747.41 | 0.188196E+10 | 0.00 | 0.71 |
June | 42963730.11 | 0.473342E+09 | 0.00 | 1873955.48 | 14164858.81 | 0.00 | 0.927387E+09 | 0.00 | 0.66 |
July | 41911063.85 | 0.540039E+09 | 0.00 | 1608658.54 | 19520465.03 | 0.00 | 0.795311E+09 | 0.00 | 0.65 |
August | 48515567.76 | 0.420647E+09 | 0.00 | 2435611.80 | 5710295.27 | 0.00 | 0.131132E+10 | 0.00 | 0.71 |
September | 0.215166E+09 | 0.150791E+09 | 0.00 | 3281582.44 | 2637737.85 | 0.00 | 0.158198E+10 | 0.00 | 0.83 |
October | 0.103262E+10 | 1390750.44 | 0.00 | 1798821.32 | 0.00 | 0.646332E+09 | 0.174874E+10 | 0.00 | 0.54 |
November | 0.153784E+10 | 0.00 | 0.00 | 349877.14 | 0.00 | 0.113101E+10 | 0.456919E+09 | 0.00 | 0.35 |
December | 0.109935E+10 | 0.00 | 0.00 | 41096.54 | 0.00 | 0.239637E+10 | 0.109308E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.897951E+10 | 0.160355E+10 | 0.00 | 14367810.79 | 42033356.96 | 0.105610E+11 | 0.100872E+11 | 0.00 | 0.50 |
Minimum of Months | 41911063.85 | 0.00 | 0.00 | 12104.88 | 0.00 | 0.00 | 32843311.55 | 0.00 | 0.27 |
Maximum of Months | 0.153784E+10 | 0.540039E+09 | 0.00 | 3281582.44 | 19520465.03 | 0.239637E+10 | 0.188196E+10 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.204119E+10 | 0.00 | 0.00 | 14467.84 | 0.00 | 0.476464E+10 | 30250836.53 | 0.00 | 0.27 |
February | 0.164657E+10 | 0.00 | 0.00 | 9723.20 | 0.00 | 0.482896E+10 | 20559402.62 | 0.00 | 0.27 |
March | 0.188995E+10 | 0.00 | 0.00 | 709161.45 | 0.00 | 0.343721E+10 | 0.594830E+09 | 0.00 | 0.32 |
April | 0.233280E+10 | 0.00 | 0.00 | 159247.95 | 0.00 | 0.238312E+10 | 0.280453E+09 | 0.00 | 0.29 |
May | 0.152096E+10 | 15834740.41 | 0.00 | 3028965.98 | 0.00 | 74329751.05 | 0.198632E+10 | 0.00 | 0.44 |
June | 15523635.51 | 0.902831E+09 | 0.00 | 3320416.33 | 11017543.66 | 0.00 | 0.104755E+10 | 0.00 | 0.46 |
July | 8928316.33 | 0.102341E+10 | 0.00 | 3044198.15 | 23879728.86 | 0.00 | 0.912459E+09 | 0.00 | 0.44 |
August | 24819195.85 | 0.748495E+09 | 0.00 | 4332508.91 | 2212352.27 | 0.00 | 0.142980E+10 | 0.00 | 0.49 |
September | 0.398306E+09 | 0.236815E+09 | 0.00 | 6363345.14 | 3478155.91 | 0.00 | 0.198807E+10 | 0.00 | 0.55 |
October | 0.233758E+10 | 8546.95 | 0.00 | 2554718.17 | 0.00 | 0.156440E+10 | 0.184469E+10 | 0.00 | 0.38 |
November | 0.288244E+10 | 0.00 | 0.00 | 363749.51 | 0.00 | 0.293965E+10 | 0.373733E+09 | 0.00 | 0.30 |
December | 0.173940E+10 | 0.00 | 0.00 | 34272.92 | 0.00 | 0.573245E+10 | 67402578.55 | 0.00 | 0.27 |
Annual Sum or Average | 0.168385E+11 | 0.292740E+10 | 0.00 | 23934775.55 | 40587780.70 | 0.257248E+11 | 0.105761E+11 | 0.00 | 0.37 |
Minimum of Months | 8928316.33 | 0.00 | 0.00 | 9723.20 | 0.00 | 0.00 | 20559402.62 | 0.00 | 0.27 |
Maximum of Months | 0.288244E+10 | 0.102341E+10 | 0.00 | 6363345.14 | 23879728.86 | 0.573245E+10 | 0.198807E+10 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.951621E+09 | 0.00 | 0.00 | 7906.21 | 0.00 | 0.245714E+10 | 31200752.09 | 0.00 | 0.28 |
February | 0.733537E+09 | 0.00 | 0.00 | 4762.05 | 0.00 | 0.249819E+10 | 22208978.30 | 0.00 | 0.27 |
March | 0.826640E+09 | 0.00 | 0.00 | 388520.61 | 0.00 | 0.178732E+10 | 0.491949E+09 | 0.00 | 0.36 |
April | 0.107584E+10 | 0.00 | 0.00 | 101828.47 | 0.00 | 0.124638E+10 | 0.289109E+09 | 0.00 | 0.32 |
May | 0.666139E+09 | 8778616.76 | 0.00 | 1598051.71 | 0.00 | 43413625.47 | 0.151394E+10 | 0.00 | 0.61 |
June | 26253089.97 | 0.454562E+09 | 0.00 | 1702864.50 | 6325762.25 | 0.00 | 0.756063E+09 | 0.00 | 0.60 |
July | 15912589.08 | 0.509513E+09 | 0.00 | 1595715.55 | 12830953.40 | 0.00 | 0.663174E+09 | 0.00 | 0.57 |
August | 30003776.41 | 0.380009E+09 | 0.00 | 2296893.79 | 854011.64 | 0.00 | 0.103654E+10 | 0.00 | 0.65 |
September | 0.189994E+09 | 0.123813E+09 | 0.00 | 3203130.29 | 1511022.12 | 0.00 | 0.142763E+10 | 0.00 | 0.76 |
October | 0.103149E+10 | 47516.03 | 0.00 | 1425477.57 | 0.00 | 0.785406E+09 | 0.142996E+10 | 0.00 | 0.48 |
November | 0.134442E+10 | 0.00 | 0.00 | 206009.49 | 0.00 | 0.153578E+10 | 0.319429E+09 | 0.00 | 0.33 |
December | 0.831924E+09 | 0.00 | 0.00 | 19277.76 | 0.00 | 0.289970E+10 | 65194158.14 | 0.00 | 0.28 |
Annual Sum or Average | 0.772377E+10 | 0.147672E+10 | 0.00 | 12550438.00 | 21521749.41 | 0.132533E+11 | 0.804641E+10 | 0.00 | 0.46 |
Minimum of Months | 15912589.08 | 0.00 | 0.00 | 4762.05 | 0.00 | 0.00 | 22208978.30 | 0.00 | 0.27 |
Maximum of Months | 0.134442E+10 | 0.509513E+09 | 0.00 | 3203130.29 | 12830953.40 | 0.289970E+10 | 0.151394E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.914583E+09 | 0.00 | 0.00 | 6296.08 | 0.00 | 0.249386E+10 | 26348249.06 | 0.00 | 0.28 |
February | 0.684520E+09 | 0.00 | 0.00 | 3604.62 | 0.00 | 0.254766E+10 | 18856084.52 | 0.00 | 0.27 |
March | 0.791555E+09 | 0.00 | 0.00 | 363789.62 | 0.00 | 0.183283E+10 | 0.464779E+09 | 0.00 | 0.36 |
April | 0.104766E+10 | 0.00 | 0.00 | 89341.81 | 0.00 | 0.128019E+10 | 0.269114E+09 | 0.00 | 0.32 |
May | 0.670174E+09 | 8762287.10 | 0.00 | 1508664.99 | 0.00 | 53493886.28 | 0.145541E+10 | 0.00 | 0.60 |
June | 27645957.57 | 0.453725E+09 | 0.00 | 1660875.72 | 6388995.64 | 0.00 | 0.741640E+09 | 0.00 | 0.59 |
July | 18395545.02 | 0.507945E+09 | 0.00 | 1556218.17 | 12905739.69 | 0.00 | 0.652072E+09 | 0.00 | 0.57 |
August | 32885401.76 | 0.379218E+09 | 0.00 | 2246167.72 | 862955.82 | 0.00 | 0.101954E+10 | 0.00 | 0.64 |
September | 0.191423E+09 | 0.123811E+09 | 0.00 | 3143773.50 | 1525049.29 | 0.00 | 0.140726E+10 | 0.00 | 0.76 |
October | 0.102766E+10 | 46976.34 | 0.00 | 1377374.90 | 0.00 | 0.800679E+09 | 0.138961E+10 | 0.00 | 0.47 |
November | 0.130833E+10 | 0.00 | 0.00 | 195808.32 | 0.00 | 0.157217E+10 | 0.309890E+09 | 0.00 | 0.33 |
December | 0.789576E+09 | 0.00 | 0.00 | 16994.28 | 0.00 | 0.294246E+10 | 60321059.56 | 0.00 | 0.28 |
Annual Sum or Average | 0.750441E+10 | 0.147351E+10 | 0.00 | 12168909.73 | 21682740.44 | 0.135233E+11 | 0.781484E+10 | 0.00 | 0.46 |
Minimum of Months | 18395545.02 | 0.00 | 0.00 | 3604.62 | 0.00 | 0.00 | 18856084.52 | 0.00 | 0.27 |
Maximum of Months | 0.130833E+10 | 0.507945E+09 | 0.00 | 3143773.50 | 12905739.69 | 0.294246E+10 | 0.145541E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.745660E+09 | 0.00 | 0.00 | 1464.41 | 0.00 | 0.265800E+10 | 13859617.06 | 0.00 | 0.28 |
February | 0.517763E+09 | 0.00 | 0.00 | 318.82 | 0.00 | 0.271760E+10 | 5258216.00 | 0.00 | 0.27 |
March | 0.695903E+09 | 0.00 | 0.00 | 271346.78 | 0.00 | 0.196857E+10 | 0.363041E+09 | 0.00 | 0.35 |
April | 0.987230E+09 | 0.00 | 0.00 | 41349.36 | 0.00 | 0.140856E+10 | 0.144036E+09 | 0.00 | 0.31 |
May | 0.722878E+09 | 8688810.16 | 0.00 | 1178856.97 | 0.00 | 88972664.03 | 0.120779E+10 | 0.00 | 0.56 |
June | 34732319.68 | 0.452270E+09 | 0.00 | 1528898.16 | 6043697.73 | 0.00 | 0.699206E+09 | 0.00 | 0.58 |
July | 24030325.09 | 0.504130E+09 | 0.00 | 1440217.84 | 12833915.99 | 0.00 | 0.623833E+09 | 0.00 | 0.56 |
August | 43370334.03 | 0.377870E+09 | 0.00 | 2106468.11 | 860268.23 | 0.00 | 0.974335E+09 | 0.00 | 0.63 |
September | 0.207778E+09 | 0.123747E+09 | 0.00 | 2972673.74 | 1553273.92 | 0.00 | 0.134017E+10 | 0.00 | 0.74 |
October | 0.100872E+10 | 46342.63 | 0.00 | 1171438.39 | 0.00 | 0.887853E+09 | 0.120638E+10 | 0.00 | 0.45 |
November | 0.115625E+10 | 0.00 | 0.00 | 151525.31 | 0.00 | 0.174874E+10 | 0.248542E+09 | 0.00 | 0.32 |
December | 0.644983E+09 | 0.00 | 0.00 | 7681.19 | 0.00 | 0.309704E+10 | 30142788.34 | 0.00 | 0.28 |
Annual Sum or Average | 0.678930E+10 | 0.146675E+10 | 0.00 | 10872239.08 | 21291155.87 | 0.145753E+11 | 0.685659E+10 | 0.00 | 0.44 |
Minimum of Months | 24030325.09 | 0.00 | 0.00 | 318.82 | 0.00 | 0.00 | 5258216.00 | 0.00 | 0.27 |
Maximum of Months | 0.115625E+10 | 0.504130E+09 | 0.00 | 2972673.74 | 12833915.99 | 0.309704E+10 | 0.134017E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.378764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298894E+10 | 0.00 | 0.00 | 0.27 |
February | 0.233424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296653E+10 | 0.00 | 0.00 | 0.27 |
March | 0.493747E+09 | 0.00 | 0.00 | 144098.46 | 0.00 | 0.220795E+10 | 0.216180E+09 | 0.00 | 0.34 |
April | 0.664737E+09 | 0.00 | 0.00 | 14324.36 | 0.00 | 0.172469E+10 | 51862061.03 | 0.00 | 0.29 |
May | 0.795064E+09 | 8604890.66 | 0.00 | 727601.09 | 0.00 | 0.173518E+09 | 0.786770E+09 | 0.00 | 0.50 |
June | 39471035.06 | 0.454116E+09 | 0.00 | 1427775.81 | 5874073.15 | 0.00 | 0.653645E+09 | 0.00 | 0.57 |
July | 35106124.58 | 0.501224E+09 | 0.00 | 1286999.47 | 11598588.23 | 0.00 | 0.563201E+09 | 0.00 | 0.55 |
August | 49289847.85 | 0.383671E+09 | 0.00 | 2059635.84 | 835015.62 | 0.00 | 0.956615E+09 | 0.00 | 0.63 |
September | 0.216038E+09 | 0.124679E+09 | 0.00 | 2949477.34 | 1503588.05 | 7446553.82 | 0.129648E+10 | 0.00 | 0.75 |
October | 0.972493E+09 | 62419.91 | 0.00 | 967347.84 | 0.00 | 0.997928E+09 | 0.995430E+09 | 0.00 | 0.43 |
November | 0.800177E+09 | 0.00 | 0.00 | 112099.61 | 0.00 | 0.209425E+10 | 0.198535E+09 | 0.00 | 0.32 |
December | 0.369965E+09 | 0.00 | 0.00 | 1801.93 | 0.00 | 0.333920E+10 | 12063053.62 | 0.00 | 0.27 |
Annual Sum or Average | 0.504827E+10 | 0.147236E+10 | 0.00 | 9691161.74 | 19811265.06 | 0.165005E+11 | 0.573078E+10 | 0.00 | 0.43 |
Minimum of Months | 35106124.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.972493E+09 | 0.501224E+09 | 0.00 | 2949477.34 | 11598588.23 | 0.333920E+10 | 0.129648E+10 | 0.00 | 0.75 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:39:09
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.228777E+12 | 0.257576E+11 | 0.00 | 0.448502E+11 | 0.517857E+10 |
February | 0.301573E+12 | 0.267497E+11 | 0.00 | 0.419775E+11 | 0.570680E+10 |
March | 0.396907E+12 | 0.237834E+11 | 0.00 | 0.401018E+11 | 0.525723E+10 |
April | 0.428677E+12 | 0.220491E+11 | 0.00 | 0.343767E+11 | 0.272150E+10 |
May | 0.531850E+12 | 0.105544E+11 | 0.00 | 0.290903E+11 | 0.140125E+11 |
June | 0.582088E+12 | -0.165000E+10 | 0.00 | 0.524802E+10 | 0.845533E+11 |
July | 0.538631E+12 | -0.238732E+10 | 0.00 | 0.315134E+10 | 0.901745E+11 |
August | 0.528156E+12 | -827954844.7 | 0.00 | 0.961922E+10 | 0.859342E+11 |
September | 0.386792E+12 | 0.368408E+10 | 0.00 | 0.200047E+11 | 0.580408E+11 |
October | 0.307137E+12 | 0.199063E+11 | 0.00 | 0.423294E+11 | 0.739773E+10 |
November | 0.252128E+12 | 0.235269E+11 | 0.00 | 0.416612E+11 | 0.351812E+10 |
December | 0.173050E+12 | 0.327138E+11 | 0.00 | 0.489743E+11 | 0.698855E+10 |
Annual Sum or Average | 0.465577E+13 | 0.183860E+12 | 0.00 | 0.361385E+12 | 0.369484E+12 |
Minimum of Months | 0.173050E+12 | -0.238732E+10 | 0.00 | 0.315134E+10 | 0.272150E+10 |
Maximum of Months | 0.582088E+12 | 0.327138E+11 | 0.00 | 0.489743E+11 | 0.901745E+11 |