Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:39
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 08:39:22
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 886.70 | 424.19 | 424.19 |
Net Site Energy | 837.13 | 400.48 | 400.48 |
Total Source Energy | 2355.86 | 1127.03 | 1127.03 |
Net Source Energy | 2198.87 | 1051.93 | 1051.93 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 217.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 256.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 159.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 64.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 669.55 | 217.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 217.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 256.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 41.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 159.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 64.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 217.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 256.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 41.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 159.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 64.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 116.66 | 103.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 320.31 | 103.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 116.66 | 103.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 320.31 | 103.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 51.998 | 7.77 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -2.43 | -0.4 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 49.569 | 7.40 |
Electricity Coming From Utility | 619.989 | 92.60 |
Surplus Electricity Going To Utility | 0.007 | 0.00 |
Net Electricity From Utility | 619.982 | 92.60 |
Total On-Site and Utility Electric Sources | 669.551 | 100.00 |
Total Electricity End Uses | 669.551 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1535.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:39 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 11.5884 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 13.7658 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 12.9393 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 7.5320 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 7.5557 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 10.0873 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 10.0873 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 11.5884 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 13.7658 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 12.9393 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 12.9393 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 12.9393 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 7.5320 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 7.5557 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 7.5557 | 6.19 | 4.3000 | |
Total | 2090.32 | 10.0873 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 10.0873 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 10.0873 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-16:49 | 16-JAN-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 114340.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 21367.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 16248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9451.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5436.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 60563.28 | 114340.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 114340.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 21367.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 16248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9451.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5436.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 235.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 64.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 811.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 130.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 504.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 203.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2120.47 | 235.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 112.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 30.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 388.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 241.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1014.42 | 112.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 112.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 30.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 388.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 241.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1014.42 | 112.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.62 |
SMSTORE1 DIRECT AIR | 0.864949 |
SMSTORE2 DIRECT AIR | 0.981809 |
SMSTORE3 DIRECT AIR | 0.980404 |
SMSTORE4 DIRECT AIR | 0.978665 |
LGSTORE2 DIRECT AIR | 1.59 |
SMSTORE5 DIRECT AIR | 0.818991 |
SMSTORE6 DIRECT AIR | 0.810615 |
SMSTORE7 DIRECT AIR | 0.796883 |
SMSTORE8 DIRECT AIR | 0.831079 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.62 | 1.62 | 1.62 | 1.62 | 1.62 | 1.62 | 1.00 | 1.00 | 1.62 |
PSZ-AC_2:2 | 0.864949 | 0.864949 | 0.864949 | 0.864949 | 0.882562 | 0.882562 | 1.00 | 0.980043 | 0.882562 |
PSZ-AC_3:3 | 0.981809 | 0.981809 | 0.981809 | 0.981809 | 0.981809 | 0.981809 | 1.00 | 1.00 | 0.981809 |
PSZ-AC_4:4 | 0.980404 | 0.980404 | 0.980404 | 0.980404 | 0.980404 | 0.980404 | 1.00 | 1.00 | 0.980404 |
PSZ-AC_5:5 | 0.978665 | 0.978665 | 0.978665 | 0.978665 | 0.978665 | 0.978665 | 1.00 | 1.000000 | 0.978665 |
PSZ-AC_6:6 | 1.59 | 1.59 | 1.59 | 1.59 | 1.59 | 1.59 | 1.00 | 1.00 | 1.59 |
PSZ-AC_7:7 | 0.818991 | 0.818991 | 0.818991 | 0.818991 | 0.831782 | 0.831782 | 1.00 | 0.984622 | 0.831782 |
PSZ-AC_8:8 | 0.810615 | 0.810615 | 0.810615 | 0.810615 | 0.824354 | 0.824354 | 1.00 | 0.983333 | 0.824354 |
PSZ-AC_9:9 | 0.796883 | 0.796883 | 0.796883 | 0.796883 | 0.812811 | 0.812811 | 1.00 | 0.980405 | 0.812811 |
PSZ-AC_10:10 | 0.831079 | 0.831079 | 0.831079 | 0.831079 | 0.855730 | 0.855730 | 1.00 | 0.971193 | 0.855730 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.62 |
PSZ-AC_2:2_OA_CONTROLLER | 0.882562 |
PSZ-AC_3:3_OA_CONTROLLER | 0.981809 |
PSZ-AC_4:4_OA_CONTROLLER | 0.980404 |
PSZ-AC_5:5_OA_CONTROLLER | 0.978665 |
PSZ-AC_6:6_OA_CONTROLLER | 1.59 |
PSZ-AC_7:7_OA_CONTROLLER | 0.831782 |
PSZ-AC_8:8_OA_CONTROLLER | 0.824354 |
PSZ-AC_9:9_OA_CONTROLLER | 0.812811 |
PSZ-AC_10:10_OA_CONTROLLER | 0.855730 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.62 | 1735.79 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 0.882562 | 977.14 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 0.981809 | 1087.02 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.980404 | 1085.46 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 0.978665 | 1083.54 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.59 | 1703.76 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.831782 | 920.92 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.824354 | 912.69 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.812811 | 899.91 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 0.855730 | 947.43 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.62 | 1.62 | 1.62 | 1.07 | 28877.00 | 48975.70 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 0.882562 | 0.882562 | 0.882562 | 0.882562 | 15549.14 | 25701.50 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 0.981809 | 0.981809 | 0.981809 | 0.981809 | 17260.42 | 28334.86 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 0.980404 | 0.980404 | 0.980404 | 0.980404 | 17223.88 | 28303.21 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 0.978665 | 0.978665 | 0.978665 | 0.978665 | 17212.89 | 28263.99 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.59 | 1.59 | 1.59 | 1.05 | 28424.08 | 48300.60 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.831782 | 0.831782 | 0.831782 | 0.831782 | 14790.39 | 24665.82 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.824354 | 0.824354 | 0.824354 | 0.824354 | 14673.89 | 24477.08 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.812811 | 0.812811 | 0.812811 | 0.812811 | 14485.21 | 24167.63 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 0.855730 | 0.855730 | 0.855730 | 0.855730 | 15041.62 | 24938.78 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.62 | 0.811081 | 1.08 | 28877.00 | 14438.50 | 0.800880 | 0.800880 |
PSZ-AC_2:2 COOLING COIL | 0.882560 | 0.441281 | 0.588373 | 15549.14 | 7774.57 | 0.800440 | 0.800440 |
PSZ-AC_3:3 COOLING COIL | 0.981810 | 0.490904 | 0.654540 | 17260.42 | 8630.21 | 0.800180 | 0.800180 |
PSZ-AC_4:4 COOLING COIL | 0.980400 | 0.490202 | 0.653600 | 17223.88 | 8611.94 | 0.800420 | 0.800420 |
PSZ-AC_5:5 COOLING COIL | 0.978660 | 0.489332 | 0.652440 | 17212.89 | 8606.44 | 0.800030 | 0.800030 |
PSZ-AC_6:6 COOLING COIL | 1.59 | 0.796115 | 1.06 | 28424.08 | 14212.04 | 0.800920 | 0.800920 |
PSZ-AC_7:7 COOLING COIL | 0.831780 | 0.415891 | 0.554520 | 14790.39 | 7395.19 | 0.800260 | 0.800260 |
PSZ-AC_8:8 COOLING COIL | 0.824350 | 0.412177 | 0.549567 | 14673.89 | 7336.94 | 0.800900 | 0.800900 |
PSZ-AC_9:9 COOLING COIL | 0.812810 | 0.406405 | 0.541873 | 14485.21 | 7242.60 | 0.800500 | 0.800500 |
PSZ-AC_10:10 COOLING COIL | 0.855730 | 0.427865 | 0.570487 | 15041.62 | 7520.81 | 0.800240 | 0.800240 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 48975.70 |
PSZ-AC_2:2 HEATING COIL | 25701.50 |
PSZ-AC_3:3 HEATING COIL | 28334.86 |
PSZ-AC_4:4 HEATING COIL | 28303.21 |
PSZ-AC_5:5 HEATING COIL | 28263.99 |
PSZ-AC_6:6 HEATING COIL | 48300.60 |
PSZ-AC_7:7 HEATING COIL | 24665.82 |
PSZ-AC_8:8 HEATING COIL | 24477.08 |
PSZ-AC_9:9 HEATING COIL | 24167.63 |
PSZ-AC_10:10 HEATING COIL | 24938.78 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 11.588 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.888 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 13.766 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 18.066 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 12.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.239 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 7.532 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.832 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 7.556 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 11.856 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 2630.745 | 7.551 | 46.768 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2630.745 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1406.513 | 4.037 | 25.004 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1406.513 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1319.493 | 7.575 | 46.916 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1319.493 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1078.411 | 6.191 | 38.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1078.411 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 937.785 | 5.384 | 33.344 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 937.785 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 2624.046 | 7.532 | 46.649 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2624.046 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1316.145 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1316.145 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.4870 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.820 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.35310903E-12 | 0.85742444E-15 | -0.12095608E-12 | 0.11097053E-15 |
23 | 6 | 0.32072860E-07 | 0.14128196E-09 | 0.73188034E-08 | -0.15356329E-12 |
24 | 5 | -0.20722947E-03 | 0.11845957E-05 | -0.10633849E-03 | 0.72234760E-08 |
25 | 4 | 0.31196324 | 0.56606413E-03 | 0.10682068 | -0.36389636E-04 |
26 | 3 | -7.6582721 | 0.17253001E-01 | -2.4552526 | 0.30931228E-01 |
27 | 2 | 42.163210 | 0.60449582E-01 | 15.741047 | -0.34773384 |
28 | 1 | -81.535291 | 0.26930198E-01 | -29.568050 | 1.0997069 |
29 | 0 | 46.824333 | 0.53495338E-03 | 16.281276 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 35 | 1 | VerySmooth | 1.408 | 1.408 | 1.000 | 0.210 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 4.57814E-002 | 0.12126 | 0.67915 | 0.67915 | 0.29000 | 0.15345 | 0.21878 | 0.00000 | 0.84000 | 0.84000 | 8.56546E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 18158.71492 | 21790.45790 | 1.35180 | 1.62216 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 18213.10928 | 21855.73113 | 0.79645 | 0.95574 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 10011.83618 | 12014.20342 | 0.72079 | 0.86495 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 8522.68849 | 10227.22619 | 0.37270 | 0.44724 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11303.73423 | 13564.48108 | 0.81817 | 0.98181 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 8622.37588 | 10346.85105 | 0.37706 | 0.45247 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11289.50102 | 13547.40122 | 0.81700 | 0.98040 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 8712.61967 | 10455.14361 | 0.38100 | 0.45720 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11268.33694 | 13522.00433 | 0.81555 | 0.97866 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 8879.68030 | 10655.61636 | 0.38831 | 0.46597 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 17823.59221 | 21388.31066 | 1.32686 | 1.59223 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 17171.98825 | 20606.38590 | 0.75094 | 0.90112 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 9494.71820 | 11393.66184 | 0.68249 | 0.81899 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 9153.44408 | 10984.13289 | 0.40028 | 0.48034 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 9400.03796 | 11280.04556 | 0.67551 | 0.81062 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 9159.36859 | 10991.24231 | 0.40054 | 0.48065 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 9244.86209 | 11093.83450 | 0.66407 | 0.79688 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 9443.97994 | 11332.77593 | 0.41299 | 0.49558 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 9629.43223 | 11555.31868 | 0.69257 | 0.83108 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 11643.19253 | 13971.83104 | 0.50914 | 0.61096 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 24158.79 | 1.62216 | 1.62216 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 33957.96 | 0.95574 | 0.95574 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 13022.08 | 0.88256 | 0.88256 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 16288.52 | 0.44724 | 0.44724 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 13236.18 | 0.98181 | 0.98181 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 16406.41 | 0.45247 | 0.45247 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 13305.70 | 0.98040 | 0.98040 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 16513.12 | 0.45720 | 0.45720 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 13190.94 | 0.97866 | 0.97866 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 16710.68 | 0.46597 | 0.46597 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 23741.97 | 1.59223 | 1.59223 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 32727.02 | 0.90112 | 0.90112 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 12162.91 | 0.83178 | 0.83178 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 17034.41 | 0.48034 | 0.48034 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 12069.81 | 0.82435 | 0.82435 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 17041.42 | 0.48065 | 0.48065 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 11969.40 | 0.81281 | 0.81281 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 17377.98 | 0.49558 | 0.49558 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 12456.93 | 0.85573 | 0.85573 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 19978.41 | 0.61096 | 0.61096 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.62216 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.86495 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98181 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98040 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97866 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.59223 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.81899 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.81062 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.79688 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83108 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.62216 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.62216 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.62216 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.62216 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.62216 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.62216 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.86495 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.86495 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.86495 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.86495 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.88256 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.88256 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.98004 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98181 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98181 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98181 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98181 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98181 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98181 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98040 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98040 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98040 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98040 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98040 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98040 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97866 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97866 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97866 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97866 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97866 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97866 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.59223 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.59223 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.59223 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.59223 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.59223 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.59223 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.81899 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.81899 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.81899 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.81899 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.83178 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.83178 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.98462 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.81062 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.81062 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.81062 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.81062 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.82435 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.82435 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.98333 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.79688 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.79688 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.79688 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.79688 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.81281 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.81281 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.98040 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.83108 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.83108 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.83108 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.83108 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.85573 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 0.85573 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.97119 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.62216 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 0.88256 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 0.98181 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 0.98040 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 0.97866 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.59223 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.83178 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.82435 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.81281 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 0.85573 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.62216 |
102 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.62216 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1735.78955 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.62216 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.62216 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.62216 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.07063 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.62216 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.81108 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.08144 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28877.00000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14438.50000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80088 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80088 |
115 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28877.00000 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 48975.69644 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
119 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 48975.69644 |
120 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.88256 |
121 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.88256 |
122 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 977.13663 |
123 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.88256 |
124 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.88256 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.88256 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.88256 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.88256 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.44128 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.58837 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15549.14000 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7774.57000 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80044 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80044 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15549.14000 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25701.49626 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
138 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 25701.49626 |
139 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98181 |
140 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98181 |
141 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1087.01829 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98181 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98181 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98181 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98181 |
146 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98181 |
147 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49090 |
148 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65454 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17260.42000 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8630.21000 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80018 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80018 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17260.42000 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28334.86147 |
155 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
157 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 28334.86147 |
158 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98040 |
159 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98040 |
160 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1085.46341 |
161 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98040 |
162 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98040 |
163 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98040 |
164 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98040 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98040 |
166 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49020 |
167 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65360 |
168 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17223.88000 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8611.94000 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80042 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80042 |
172 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17223.88000 |
173 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28303.21227 |
174 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
176 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 28303.21227 |
177 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97866 |
178 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97866 |
179 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1083.53711 |
180 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97866 |
181 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97866 |
182 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97866 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97866 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97866 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48933 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65244 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17212.89000 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8606.44500 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80003 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80003 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17212.89000 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28263.99369 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
194 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
195 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 28263.99369 |
196 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.59223 |
197 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.59223 |
198 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1703.76068 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.59223 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.59223 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.59223 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05087 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.59223 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.79611 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.06149 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28424.08000 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14212.04000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80092 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80092 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28424.08000 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 48300.60055 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
213 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
214 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 48300.60055 |
215 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.83178 |
216 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.83178 |
217 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 920.91500 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.83178 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.83178 |
220 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.83178 |
221 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83178 |
222 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.83178 |
223 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.41589 |
224 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.55452 |
225 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 14790.39000 |
226 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7395.19500 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80026 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80026 |
229 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 14790.39000 |
230 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24665.81950 |
231 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
232 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
233 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 24665.81950 |
234 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.82435 |
235 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.82435 |
236 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 912.69123 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.82435 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.82435 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.82435 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.82435 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.82435 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.41218 |
243 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.54957 |
244 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 14673.89000 |
245 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7336.94500 |
246 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80090 |
247 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80090 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 14673.89000 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24477.07735 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
251 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
252 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 24477.07735 |
253 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.81281 |
254 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.81281 |
255 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 899.91059 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.81281 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.81281 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.81281 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.81281 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.81281 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.40641 |
262 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.54187 |
263 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 14485.21000 |
264 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7242.60500 |
265 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80050 |
266 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80050 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 14485.21000 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24167.63116 |
269 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
270 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
271 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 24167.63116 |
272 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.85573 |
273 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.85573 |
274 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 947.42934 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.85573 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.85573 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.85573 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85573 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.85573 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.42787 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.57049 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15041.62000 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7520.81000 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80024 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80024 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15041.62000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24938.77895 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 24938.77895 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 27604.4 | 11.73 | 11.73 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 14856.9 | 12.47 | 12.47 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 16490.3 | 12.46 | 12.46 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 16454.9 | 12.46 | 12.46 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 16445.3 | 12.46 | 12.46 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 27174.9 | 11.73 | 11.73 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 14137.9 | 12.50 | 12.50 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 14027.2 | 12.50 | 12.50 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 13847.6 | 12.50 | 12.50 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 14370.4 | 12.46 | 12.46 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.487 | 0.454 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 3.4192339038E-002 | 0.2087796224 | Pass | Pass | 0.1568884719 | 0.7903643569 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 3.9270184718E-002 | 0.1342444040 | Pass | Pass | 0.2334697136 | 1.5271968014 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.3701355827E-002 | 0.1919696828 | Pass | Pass | 7.6872764048E-002 | 0.2541837896 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.8529539101E-002 | 0.2279067673 | Pass | Pass | 5.1341626988E-002 | 0.1737758427 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 4.1809420802E-002 | 0.2396111203 | Pass | Pass | 7.1114340732E-002 | 0.3975226093 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.9018817344E-002 | 0.2598987096 | Pass | Pass | 3.0097598718E-002 | 9.8352977900E-002 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.8603023588E-002 | 0.2603639547 | Pass | Pass | 2.8287283257E-002 | 8.8313957088E-002 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.9613823647E-002 | 0.2627125606 | Pass | Pass | 2.8360576729E-002 | 9.0555201175E-002 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.4481701509E-002 | 0.2841106358 | Pass | Pass | 2.7494618313E-002 | 9.3118765190E-002 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 7.1455401002E-002 | 0.3633496478 | Pass | Pass | 2.1552314812E-002 | 7.3801798517E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3399.44 | 211.41 | 0.00 | 415.07 | 139.15 | 4165.09 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.454 | 0.487 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.408 | 0.210 | 0.290 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.248_SHGC_0.21 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.408 | 0.210 | 0.290 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 1.408 | 0.210 | 0.290 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 1.408 | 0.210 | 0.290 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 7.5512 | 348.39 | 2630.74 | LightsWired | LTG_SCH_BASE_LPD1 | 72.52 | 168.00 | 71.91 | 0.0000 | Y | 35.51 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 4.0372 | 348.39 | 1406.51 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 24.96 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 7.5749 | 174.19 | 1319.49 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 73.56 | 168.00 | 72.92 | 0.0000 | Y | 18.06 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 6.1909 | 174.19 | 1078.41 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 19.14 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 58.93 | 168.00 | 57.34 | 0.0000 | Y | 14.17 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 58.93 | 168.00 | 57.34 | 0.0000 | Y | 14.17 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 58.93 | 168.00 | 57.34 | 0.0000 | Y | 14.17 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 5.3836 | 174.19 | 937.78 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 12.89 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 7.5320 | 348.39 | 2624.05 | LightsWired | LTG_SCH_BASE_LPD2 | 53.44 | 168.00 | 51.85 | 0.0000 | Y | 25.54 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 54.20 | 168.00 | 52.55 | 0.0000 | Y | 12.98 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 54.20 | 168.00 | 52.55 | 0.0000 | Y | 12.98 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 54.20 | 168.00 | 52.55 | 0.0000 | Y | 12.98 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 7.5557 | 174.19 | 1316.15 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 54.20 | 168.00 | 52.55 | 0.0000 | Y | 12.98 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 5.0436 | 4180.64 | 21085.58 | 256.32 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 437.57 | AstronomicalClock | - | 42.59 | 42.59 | 3.50 | |
EXTERIOR_LIGHTS_B | 1882.64 | AstronomicalClock | - | 83.55 | 63.07 | 22.29 | |
EXTERIOR_LIGHTS_C | 1466.47 | AstronomicalClock | - | 83.55 | 56.07 | 15.43 | |
Exterior Lighting Total | 3786.68 | 41.22 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28877.00 | 23127.01 | 5749.99 | 0.80 | 3.99 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15549.14 | 12446.15 | 3102.99 | 0.80 | 4.32 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17260.42 | 13811.44 | 3448.98 | 0.80 | 4.32 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17223.88 | 13786.34 | 3437.54 | 0.80 | 4.32 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17212.89 | 13770.83 | 3442.06 | 0.80 | 4.32 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28424.08 | 22765.41 | 5658.67 | 0.80 | 3.99 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 14790.39 | 11836.16 | 2954.23 | 0.80 | 4.32 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 14673.89 | 11752.32 | 2921.57 | 0.80 | 4.32 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 14485.21 | 11595.41 | 2889.80 | 0.80 | 4.32 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15041.62 | 12036.91 | 3004.71 | 0.80 | 4.32 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 27604.4 | 11.73 | 11.73 | ||||
PSZ-AC_2:2 COOLING COIL | 14856.9 | 12.47 | 12.47 | ||||
PSZ-AC_3:3 COOLING COIL | 16490.3 | 12.46 | 12.46 | ||||
PSZ-AC_4:4 COOLING COIL | 16454.9 | 12.46 | 12.46 | ||||
PSZ-AC_5:5 COOLING COIL | 16445.3 | 12.46 | 12.46 | ||||
PSZ-AC_6:6 COOLING COIL | 27174.9 | 11.73 | 11.73 | ||||
PSZ-AC_7:7 COOLING COIL | 14137.9 | 12.50 | 12.50 | ||||
PSZ-AC_8:8 COOLING COIL | 14027.2 | 12.50 | 12.50 | ||||
PSZ-AC_9:9 COOLING COIL | 13847.6 | 12.50 | 12.50 | ||||
PSZ-AC_10:10 COOLING COIL | 14370.4 | 12.46 | 12.46 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 48975.70 | 0.88 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 25701.50 | 0.88 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 28334.86 | 0.88 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 28303.21 | 0.88 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 28263.99 | 0.88 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 48300.60 | 0.88 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 24665.82 | 0.88 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 24477.08 | 0.88 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 24167.63 | 0.88 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 24938.78 | 0.88 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.62 | 1735.79 | 1070.05 | 1.00 | 1.35 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.88 | 977.14 | 1107.16 | 1.00 | 1.44 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1087.02 | 1107.16 | 1.00 | 1.41 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1085.46 | 1107.16 | 1.00 | 1.41 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1083.54 | 1107.16 | 1.00 | 1.41 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.59 | 1703.76 | 1070.05 | 1.00 | 1.35 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.83 | 920.92 | 1107.16 | 1.00 | 1.45 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.82 | 912.69 | 1107.16 | 1.00 | 1.45 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.81 | 899.91 | 1107.16 | 1.00 | 1.46 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.86 | 947.43 | 1107.16 | 1.00 | 1.44 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 18158.71 | 21790.46 | 62.55 | 1.352 | 1.622 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 23.89 | 23.89 | 0.00913 | 29.40 | 0.00882 | 0.411 | 0.00 |
SMSTORE1 | 10011.84 | 12014.20 | 68.97 | 0.721 | 0.865 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00958 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE2 | 11303.73 | 13564.48 | 77.87 | 0.818 | 0.982 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.88 | 0.00996 | 23.68 | 0.00881 | 0.206 | 0.00 |
SMSTORE3 | 11289.50 | 13547.40 | 77.77 | 0.817 | 0.980 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.88 | 0.00988 | 23.68 | 0.00881 | 0.206 | 0.00 |
SMSTORE4 | 11268.34 | 13522.00 | 77.63 | 0.816 | 0.979 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.88 | 0.00996 | 23.68 | 0.00881 | 0.206 | 0.00 |
LGSTORE2 | 17823.59 | 21388.31 | 61.39 | 1.327 | 1.592 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00914 | 29.23 | 0.00882 | 0.411 | 0.00 |
SMSTORE5 | 9494.72 | 11393.66 | 65.41 | 0.682 | 0.819 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.88 | 0.00973 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE6 | 9400.04 | 11280.05 | 64.76 | 0.676 | 0.811 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.88 | 0.00976 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE7 | 9244.86 | 11093.83 | 63.69 | 0.664 | 0.797 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.88 | 0.00981 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE8 | 9629.43 | 11555.32 | 66.34 | 0.693 | 0.831 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.88 | 0.00965 | 25.45 | 0.00882 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 18213.11 | 21855.73 | 62.73 | 0.796 | 0.956 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00665 | -4.20 | 0.00269 | 0.411 | 0.00 |
SMSTORE1 | 8522.69 | 10227.23 | 58.71 | 0.373 | 0.447 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00657 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE2 | 8622.38 | 10346.85 | 59.40 | 0.377 | 0.452 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00659 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE3 | 8712.62 | 10455.14 | 60.02 | 0.381 | 0.457 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00660 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE4 | 8879.68 | 10655.62 | 61.17 | 0.388 | 0.466 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00661 | -4.20 | 0.00269 | 0.206 | 0.00 |
LGSTORE2 | 17171.99 | 20606.39 | 59.15 | 0.751 | 0.901 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -4.20 | 0.00269 | 0.411 | 0.00 |
SMSTORE5 | 9153.44 | 10984.13 | 63.06 | 0.400 | 0.480 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00664 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE6 | 9159.37 | 10991.24 | 63.10 | 0.401 | 0.481 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00664 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE7 | 9443.98 | 11332.78 | 65.06 | 0.413 | 0.496 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00667 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE8 | 11643.19 | 13971.83 | 80.21 | 0.509 | 0.611 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -4.20 | 0.00269 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.62 | 1.62 | 0.96 | 0.96 | 1.6222 | 1.6222 | 1.6222 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 0.88 | 0.88 | 0.45 | 0.45 | 0.8826 | 0.8649 | 0.8826 | 0.9800 | 1.0000 |
PSZ-AC_3:3 | 0.98 | 0.98 | 0.45 | 0.45 | 0.9818 | 0.9818 | 0.9818 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 0.98 | 0.98 | 0.46 | 0.46 | 0.9804 | 0.9804 | 0.9804 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 0.98 | 0.98 | 0.47 | 0.47 | 0.9787 | 0.9787 | 0.9787 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.59 | 1.59 | 0.90 | 0.90 | 1.5922 | 1.5922 | 1.5922 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.83 | 0.83 | 0.48 | 0.48 | 0.8318 | 0.8190 | 0.8318 | 0.9846 | 1.0000 |
PSZ-AC_8:8 | 0.82 | 0.82 | 0.48 | 0.48 | 0.8244 | 0.8106 | 0.8244 | 0.9833 | 1.0000 |
PSZ-AC_9:9 | 0.81 | 0.81 | 0.50 | 0.50 | 0.8128 | 0.7969 | 0.8128 | 0.9804 | 1.0000 |
PSZ-AC_10:10 | 0.86 | 0.86 | 0.61 | 0.61 | 0.8557 | 0.8311 | 0.8557 | 0.9712 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 28877.000 | 23127.012 | 1.622160 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 14438.50 | 13212.55 | 1.081440 | 26.17 | 17.45 | 0.00904925 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 38.0493 | 23.89 | 0.00912666 | 48.7075 | 18158.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 48975.696 | 48975.696 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 48975.70 | 48975.70 | 1.622162 | 14.69 | 9.81 | 0.00564382 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 25.3662 | 21.11 | 0.00664765 | 42.1779 | 18213.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 15549.140 | 12446.154 | 0.882560 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 7774.57 | 7141.67 | 0.588373 | 26.09 | 17.40 | 0.00902171 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 34.9672 | 23.89 | 0.00908258 | 48.4755 | 9877.29 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 25701.496 | 25701.496 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 25701.50 | 25701.50 | 0.882562 | 15.21 | 10.07 | 0.00566911 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 23.3114 | 21.11 | 0.00657458 | 41.7188 | 8522.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 17260.420 | 13811.443 | 0.981810 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8630.21 | 7933.78 | 0.654540 | 26.06 | 17.39 | 0.00901595 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 31.4324 | 23.89 | 0.00907370 | 48.4288 | 10466.26 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 28334.861 | 28334.861 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28334.86 | 28334.86 | 0.981809 | 15.80 | 10.43 | 0.00576960 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.9549 | 21.11 | 0.00658592 | 41.7900 | 8622.38 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 17223.880 | 13786.338 | 0.980400 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8611.94 | 7918.95 | 0.653600 | 26.06 | 17.38 | 0.00901411 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 31.4776 | 23.89 | 0.00907087 | 48.4139 | 11289.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 28303.212 | 28303.212 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28303.21 | 28303.21 | 0.980404 | 15.80 | 10.44 | 0.00577571 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.9850 | 21.11 | 0.00659513 | 41.8478 | 8712.62 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 17212.890 | 13770.828 | 0.978660 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8606.44 | 7910.66 | 0.652440 | 26.07 | 17.39 | 0.00901715 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 31.5336 | 23.89 | 0.00907554 | 48.4385 | 10431.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 28263.994 | 28263.994 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28263.99 | 28263.99 | 0.978665 | 15.79 | 10.45 | 0.00578819 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 21.0223 | 21.11 | 0.00661278 | 41.9587 | 8879.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 28424.080 | 22765.414 | 1.592230 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 14212.04 | 12989.70 | 1.061487 | 26.20 | 17.47 | 0.00905806 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 38.7646 | 23.89 | 0.00914061 | 48.7809 | 17805.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 48300.601 | 48300.601 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 48300.60 | 48300.60 | 1.592229 | 14.57 | 9.77 | 0.00565750 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 25.8431 | 21.11 | 0.00669154 | 42.4524 | 17171.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 14790.390 | 11836.158 | 0.831780 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 7395.19 | 6771.82 | 0.554520 | 26.19 | 17.46 | 0.00904564 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 37.1019 | 23.89 | 0.00912104 | 48.6777 | 9494.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 24665.820 | 24665.820 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 24665.82 | 24665.82 | 0.831782 | 14.85 | 9.90 | 0.00566202 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 24.7345 | 21.11 | 0.00663861 | 42.1209 | 9153.44 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 14673.890 | 11752.319 | 0.824350 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 7336.94 | 6716.14 | 0.549567 | 26.20 | 17.46 | 0.00904834 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 37.4363 | 23.89 | 0.00912552 | 48.7013 | 9400.04 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 24477.077 | 24477.077 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 24477.08 | 24477.08 | 0.824354 | 14.79 | 9.87 | 0.00565374 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 24.9574 | 21.11 | 0.00663931 | 42.1252 | 9159.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 14485.210 | 11595.411 | 0.812810 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 7242.60 | 6627.29 | 0.541873 | 26.21 | 17.47 | 0.00905126 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 37.9678 | 23.89 | 0.00913044 | 48.7272 | 9244.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 24167.631 | 24167.631 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 24167.63 | 24167.63 | 0.812811 | 14.70 | 9.83 | 0.00565956 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 25.3119 | 21.11 | 0.00666583 | 42.2918 | 9443.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 15041.620 | 12036.906 | 0.855730 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 7520.81 | 6897.22 | 0.570487 | 26.06 | 17.40 | 0.00903120 | 12.80 | 11.97 | 0.00850000 | 29.05 | 0.00882094 | 18.23 | 36.0635 | 23.89 | 0.00909876 | 48.5605 | 9487.03 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 24938.779 | 24938.779 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 24938.78 | 24938.78 | 0.855730 | 15.02 | 10.05 | 0.00573002 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 24.0423 | 21.11 | 0.00669215 | 42.4591 | 11643.19 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28877.000 | 23127.012 | 1.622160 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6621 | 1004.8586 | 1.1870 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.622162 | 1.92549082 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 14438.50 | 13212.55 | 1.0000 | 1.28365931 | 1.081440 | 26.17 | 17.45 | 0.00904925 | 49367.0 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14438.50 | 29.40 | 0.00882150 | 18.34 | 0.41148071 | 38.0493 | 23.89 | 0.00912666 | 23.89 | 0.00912666 | 48.7075 | 18158.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 48975.696 | 48975.696 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.622162 | 1.92549082 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 48975.70 | 48975.70 | 1.0000 | 1.92549082 | 1.622162 | 14.69 | 9.81 | 0.00564382 | 29027.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48975.70 | -4.20 | 0.00269032 | -4.20 | 0.41148071 | 25.3662 | 21.11 | 0.00664765 | 21.11 | 0.00664765 | 42.1779 | 18213.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15549.140 | 12446.154 | 0.882560 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6109 | 1004.8586 | 1.1870 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.882562 | 1.04759339 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 7774.57 | 7141.67 | 1.0000 | 0.69839372 | 0.588373 | 26.09 | 17.40 | 0.00902171 | 49212.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7774.57 | 29.40 | 0.00882150 | 18.34 | 0.20573751 | 34.9672 | 23.89 | 0.00908258 | 23.89 | 0.00908258 | 48.4755 | 9877.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25701.496 | 25701.496 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.882562 | 1.04759339 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 25701.50 | 25701.50 | 1.0000 | 1.04759339 | 0.882562 | 15.21 | 10.07 | 0.00566911 | 29619.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25701.50 | -4.20 | 0.00269032 | -4.20 | 0.20573751 | 23.3114 | 21.11 | 0.00657458 | 21.11 | 0.00657458 | 41.7188 | 8522.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17260.420 | 13811.443 | 0.981810 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6002 | 1004.8586 | 1.1870 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.981809 | 1.16539810 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | Sensible | 8630.21 | 7933.78 | 1.0000 | 0.77693295 | 0.654540 | 26.06 | 17.39 | 0.00901595 | 49174.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8630.21 | 29.40 | 0.00882150 | 18.34 | 0.20573751 | 31.4324 | 23.89 | 0.00907370 | 23.89 | 0.00907370 | 48.4288 | 10466.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28334.861 | 28334.861 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.981809 | 1.16539810 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28334.86 | 28334.86 | 1.0000 | 1.16539810 | 0.981809 | 15.80 | 10.43 | 0.00576960 | 30479.5 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28334.86 | -4.20 | 0.00269032 | -4.20 | 0.20573751 | 20.9549 | 21.11 | 0.00658592 | 21.11 | 0.00658592 | 41.7900 | 8622.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17223.880 | 13786.338 | 0.980400 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5968 | 1004.8586 | 1.1870 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.980404 | 1.16373111 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | Sensible | 8611.94 | 7918.95 | 1.0000 | 0.77581718 | 0.653600 | 26.06 | 17.38 | 0.00901411 | 49162.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8611.94 | 29.40 | 0.00882150 | 18.34 | 0.20573751 | 31.4776 | 23.89 | 0.00907087 | 23.89 | 0.00907087 | 48.4139 | 11289.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28303.212 | 28303.212 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.980404 | 1.16373111 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28303.21 | 28303.21 | 1.0000 | 1.16373111 | 0.980404 | 15.80 | 10.44 | 0.00577571 | 30487.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28303.21 | -4.20 | 0.00269032 | -4.20 | 0.20573751 | 20.9850 | 21.11 | 0.00659513 | 21.11 | 0.00659513 | 41.8478 | 8712.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17212.890 | 13770.828 | 0.978660 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6024 | 1004.8586 | 1.1870 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.978665 | 1.16166591 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | Sensible | 8606.44 | 7910.66 | 1.0000 | 0.77444027 | 0.652440 | 26.07 | 17.39 | 0.00901715 | 49182.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8606.44 | 29.40 | 0.00882150 | 18.34 | 0.20573751 | 31.5336 | 23.89 | 0.00907554 | 23.89 | 0.00907554 | 48.4385 | 10431.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28263.994 | 28263.994 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.978665 | 1.16166591 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28263.99 | 28263.99 | 1.0000 | 1.16166591 | 0.978665 | 15.79 | 10.45 | 0.00578819 | 30509.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28263.99 | -4.20 | 0.00269032 | -4.20 | 0.20573751 | 21.0223 | 21.11 | 0.00661278 | 21.11 | 0.00661278 | 41.9587 | 8879.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28424.080 | 22765.414 | 1.592230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6785 | 1004.8586 | 1.1870 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.592229 | 1.88996158 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 14212.04 | 12989.70 | 1.0000 | 1.25997489 | 1.061487 | 26.20 | 17.47 | 0.00905806 | 49417.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14212.04 | 29.40 | 0.00882150 | 18.34 | 0.41148071 | 38.7646 | 23.89 | 0.00914061 | 23.89 | 0.00914061 | 48.7809 | 17805.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 48300.601 | 48300.601 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.592229 | 1.88996158 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 48300.60 | 48300.60 | 1.0000 | 1.88996158 | 1.592229 | 14.57 | 9.77 | 0.00565750 | 28940.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48300.60 | -4.20 | 0.00269032 | -4.20 | 0.41148071 | 25.8431 | 21.11 | 0.00669154 | 21.11 | 0.00669154 | 42.4524 | 17171.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14790.390 | 11836.158 | 0.831780 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6554 | 1004.8586 | 1.1870 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.831782 | 0.98731788 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 7395.19 | 6771.82 | 1.0000 | 0.65821013 | 0.554520 | 26.19 | 17.46 | 0.00904564 | 49378.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7395.19 | 29.40 | 0.00882150 | 18.34 | 0.20573751 | 37.1019 | 23.89 | 0.00912104 | 23.89 | 0.00912104 | 48.6777 | 9494.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24665.820 | 24665.820 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.831782 | 0.98731788 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 24665.82 | 24665.82 | 1.0000 | 0.98731788 | 0.831782 | 14.85 | 9.90 | 0.00566202 | 29236.1 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24665.82 | -4.20 | 0.00269032 | -4.20 | 0.20573751 | 24.7345 | 21.11 | 0.00663861 | 21.11 | 0.00663861 | 42.1209 | 9153.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14673.890 | 11752.319 | 0.824350 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6604 | 1004.8586 | 1.1870 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.824354 | 0.97850113 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 7336.94 | 6716.14 | 1.0000 | 0.65233057 | 0.549567 | 26.20 | 17.46 | 0.00904834 | 49397.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7336.94 | 29.40 | 0.00882150 | 18.34 | 0.20573751 | 37.4363 | 23.89 | 0.00912552 | 23.89 | 0.00912552 | 48.7013 | 9400.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24477.077 | 24477.077 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.824354 | 0.97850113 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 24477.08 | 24477.08 | 1.0000 | 0.97850113 | 0.824354 | 14.79 | 9.87 | 0.00565374 | 29157.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24477.08 | -4.20 | 0.00269032 | -4.20 | 0.20573751 | 24.9574 | 21.11 | 0.00663931 | 21.11 | 0.00663931 | 42.1252 | 9159.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14485.210 | 11595.411 | 0.812810 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6658 | 1004.8586 | 1.1870 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.812811 | 0.96479894 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 7242.60 | 6627.29 | 1.0000 | 0.64319865 | 0.541873 | 26.21 | 17.47 | 0.00905126 | 49418.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7242.60 | 29.40 | 0.00882150 | 18.34 | 0.20573751 | 37.9678 | 23.89 | 0.00913044 | 23.89 | 0.00913044 | 48.7272 | 9244.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24167.631 | 24167.631 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.812811 | 0.96479894 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 24167.63 | 24167.63 | 1.0000 | 0.96479894 | 0.812811 | 14.70 | 9.83 | 0.00565956 | 29081.5 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24167.63 | -4.20 | 0.00269032 | -4.20 | 0.20573751 | 25.3119 | 21.11 | 0.00666583 | 21.11 | 0.00666583 | 42.2918 | 9443.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15041.620 | 12036.906 | 0.855730 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6286 | 1004.8586 | 1.1870 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.855730 | 1.01574404 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 7520.81 | 6897.22 | 1.0000 | 0.67716242 | 0.570487 | 26.06 | 17.40 | 0.00903120 | 49207.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7520.81 | 29.05 | 0.00882094 | 18.23 | 0.20573751 | 36.0635 | 23.89 | 0.00909876 | 23.89 | 0.00909876 | 48.5605 | 9487.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24938.779 | 24938.779 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.855730 | 1.01574404 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 24938.78 | 24938.78 | 1.0000 | 1.01574404 | 0.855730 | 15.02 | 10.05 | 0.00573002 | 29585.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24938.78 | -4.20 | 0.00269032 | -4.20 | 0.20573751 | 24.0423 | 21.11 | 0.00669215 | 21.11 | 0.00669215 | 42.4591 | 11643.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.62 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.88 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.98 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.98 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.98 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 1.59 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.83 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.82 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.81 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.86 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
LGSTORE1 | LGSTORE1_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE1 | SMSTORE1_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE2 | SMSTORE2_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE3 | SMSTORE3_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE4 | SMSTORE4_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LGSTORE2 | LGSTORE2_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE5 | SMSTORE5_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE6 | SMSTORE6_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE7 | SMSTORE7_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
SMSTORE8 | SMSTORE8_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1380.33 | 4158.50 | 722.00 |
SMSTORE1 | 829.83 | 3656.50 | 111.33 |
SMSTORE2 | 955.17 | 2727.00 | 265.50 |
SMSTORE3 | 1000.50 | 2771.00 | 326.33 |
SMSTORE4 | 1032.33 | 2918.00 | 415.50 |
LGSTORE2 | 1032.67 | 2964.00 | 590.17 |
SMSTORE5 | 968.50 | 2939.33 | 587.50 |
SMSTORE6 | 981.33 | 2968.17 | 619.17 |
SMSTORE7 | 1067.33 | 3058.17 | 736.50 |
SMSTORE8 | 1514.67 | 3222.00 | 1226.67 |
Facility | 2372.17 | 4657.17 | 1535.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 4.50 | 0.00 | 0.17 | 0.00 |
SMSTORE1 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 1.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 13.33 | 0.00 | 0.00 | 0.00 |
Facility | 18.33 | 0.00 | 0.17 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.703 | 0.230 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.836 | 0.245 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.938 | 0.320 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.931 | 0.320 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.904 | 0.320 | 0.000 | 0.000 |
LGSTORE2 | 24.80 | 56.25 | 1805.20 | 0.752 | 0.307 | 0.000 | 0.000 |
SMSTORE5 | 12.40 | 28.12 | 902.60 | 0.898 | 0.341 | 0.000 | 0.000 |
SMSTORE6 | 12.40 | 28.12 | 902.60 | 0.889 | 0.341 | 0.000 | 0.000 |
SMSTORE7 | 12.40 | 28.12 | 902.60 | 0.865 | 0.341 | 0.000 | 0.000 |
SMSTORE8 | 12.40 | 28.12 | 902.60 | 0.855 | 0.359 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.436 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.436 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.436 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.80 | 56.25 | 1805.20 | 0.461 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.40 | 28.12 | 902.60 | 0.461 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.40 | 28.12 | 902.60 | 0.461 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.40 | 28.12 | 902.60 | 0.461 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.40 | 28.12 | 902.60 | 0.461 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.212 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE2 | PSZ-AC_3:3 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE3 | PSZ-AC_4:4 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE4 | PSZ-AC_5:5 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
LGSTORE2 | PSZ-AC_6:6 | 24.80 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.212 |
SMSTORE5 | PSZ-AC_7:7 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE6 | PSZ-AC_8:8 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE7 | PSZ-AC_9:9 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
SMSTORE8 | PSZ-AC_10:10 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.106 |
Total Facility | 121.06 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 1.274 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 7281161.21 | 0.00 | 7281161.21 | 2751432.93 | 10032594.14 | 7870781.79 | 3175.08 | 4137.33 | 1447.58 | 10.00 |
SMSTORE1 | 4330288.07 | 0.00 | 4330288.07 | 1379627.48 | 5709915.54 | 3935374.10 | 4049.32 | 2654.67 | 2056.01 | 33.50 |
SMSTORE2 | 3696503.62 | 0.00 | 3696503.62 | 1417008.46 | 5113512.08 | 3701819.01 | 4320.97 | 2990.92 | 1448.11 | 124.22 |
SMSTORE3 | 3669570.81 | 0.00 | 3669570.81 | 1417008.46 | 5086579.28 | 3701819.01 | 4322.81 | 3025.92 | 1411.28 | 118.50 |
SMSTORE4 | 3556984.08 | 0.00 | 3556984.08 | 1417008.46 | 4973992.54 | 3701819.01 | 4330.81 | 3143.58 | 1285.61 | 106.06 |
LGSTORE2 | 5400803.80 | 0.00 | 5400803.80 | 2601582.32 | 8002386.12 | 7907875.00 | 4721.42 | 3192.08 | 846.50 | 45.58 |
SMSTORE5 | 3233060.05 | 0.00 | 3233060.05 | 1426750.59 | 4659810.65 | 3953920.18 | 4711.58 | 3005.75 | 1042.67 | 75.92 |
SMSTORE6 | 3200272.60 | 0.00 | 3200272.60 | 1426750.59 | 4627023.20 | 3953920.18 | 4712.50 | 3028.50 | 1019.00 | 71.50 |
SMSTORE7 | 3106009.23 | 0.00 | 3106009.23 | 1426750.59 | 4532759.83 | 3953920.18 | 4717.50 | 3111.83 | 930.67 | 53.92 |
SMSTORE8 | 3065818.80 | 0.00 | 3065818.80 | 1741532.12 | 4807350.92 | 3953920.18 | 4720.33 | 3220.17 | 819.50 | 18.42 |
Total Facility | 40540472.27 | 0.00 | 40540472.27 | 17005452.03 | 57545924.30 | 46635168.64 | 4722.75 | 4641.92 | 2262.61 | 211.47 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.3462 | 0.0000 | 0.3462 | 0.1134 | 0.4596 | 0.2682 | 255.92 | 4137.33 | 1446.75 |
SMSTORE1 | 0.2054 | 0.0000 | 0.2054 | 0.0605 | 0.2659 | 0.1341 | 1139.49 | 2654.33 | 2046.18 |
SMSTORE2 | 0.2306 | 0.0000 | 0.2306 | 0.0789 | 0.3095 | 0.1285 | 0.00 | 2988.58 | 1406.42 |
SMSTORE3 | 0.2290 | 0.0000 | 0.2290 | 0.0789 | 0.3079 | 0.1285 | 0.00 | 3024.42 | 1370.58 |
SMSTORE4 | 0.2224 | 0.0000 | 0.2224 | 0.0789 | 0.3012 | 0.1285 | 0.00 | 3141.75 | 1253.25 |
LGSTORE2 | 0.3707 | 0.0000 | 0.3707 | 0.1515 | 0.5222 | 0.2958 | 0.00 | 3191.75 | 838.25 |
SMSTORE5 | 0.2209 | 0.0000 | 0.2209 | 0.0841 | 0.3051 | 0.1479 | 0.00 | 3005.00 | 1025.00 |
SMSTORE6 | 0.2188 | 0.0000 | 0.2188 | 0.0841 | 0.3030 | 0.1479 | 0.00 | 3028.00 | 1002.00 |
SMSTORE7 | 0.2128 | 0.0000 | 0.2128 | 0.0841 | 0.2970 | 0.1479 | 0.00 | 3111.67 | 918.33 |
SMSTORE8 | 0.2106 | 0.0000 | 0.2106 | 0.0886 | 0.2993 | 0.1479 | 0.00 | 3220.17 | 809.83 |
Total Facility | 2.4676 | 0.0000 | 2.4676 | 0.9031 | 3.3707 | 1.6752 | 1261.91 | 4635.83 | 2224.17 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 10258846.33 | 0.00 | 10258846.33 | 7870781.79 | 3173.83 | 0.00 | 5586.17 | 10.00 |
PSZ-AC_2:2 | 6101147.05 | 0.00 | 6101147.05 | 3935374.10 | 3983.35 | 4.42 | 4772.24 | 33.50 |
PSZ-AC_3:3 | 5208178.12 | 0.00 | 5208178.12 | 3701819.01 | 4283.14 | 2.17 | 4474.69 | 123.97 |
PSZ-AC_4:4 | 5170231.23 | 0.00 | 5170231.23 | 3701819.01 | 4287.14 | 1.67 | 4471.19 | 118.50 |
PSZ-AC_5:5 | 5011602.47 | 0.00 | 5011602.47 | 3701819.01 | 4298.31 | 2.00 | 4459.69 | 106.06 |
PSZ-AC_6:6 | 7609485.67 | 0.00 | 7609485.67 | 7907875.00 | 4720.33 | 0.00 | 4039.67 | 45.42 |
PSZ-AC_7:7 | 4555210.65 | 0.00 | 4555210.65 | 3953920.18 | 4694.83 | 1.17 | 4064.00 | 75.83 |
PSZ-AC_8:8 | 4509014.86 | 0.00 | 4509014.86 | 3953920.18 | 4698.67 | 1.17 | 4060.17 | 71.33 |
PSZ-AC_9:9 | 4376202.76 | 0.00 | 4376202.76 | 3953920.18 | 4708.50 | 0.67 | 4050.83 | 53.75 |
PSZ-AC_10:10 | 4319576.57 | 0.00 | 4319576.57 | 3953920.18 | 4719.08 | 0.00 | 4040.92 | 18.25 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.4878 | 0.0000 | 0.4878 | 0.2682 | 254.67 | 0.00 | 5585.33 |
PSZ-AC_2:2 | 0.2894 | 0.0000 | 0.2894 | 0.1341 | 1083.85 | 3.75 | 4752.40 |
PSZ-AC_3:3 | 0.3250 | 0.0000 | 0.3250 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3227 | 0.0000 | 0.3227 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3133 | 0.0000 | 0.3133 | 0.1285 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5224 | 0.0000 | 0.5224 | 0.2958 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3113 | 0.0000 | 0.3113 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3083 | 0.0000 | 0.3083 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2999 | 0.0000 | 0.2999 | 0.1479 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2968 | 0.0000 | 0.2968 | 0.1479 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 646.50 | 927.17 | 0.00 | 0.00 | 0.00 | 4047.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 531.67 | 1759.75 | 0.00 | 0.00 | 0.00 | 2688.97 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 408.69 | 1124.36 | 0.00 | 0.00 | 0.00 | 2985.92 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 406.44 | 1083.81 | 0.00 | 0.00 | 0.00 | 3023.25 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 386.03 | 974.94 | 0.00 | 0.00 | 0.00 | 3140.08 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 466.25 | 471.50 | 0.00 | 0.00 | 0.00 | 3137.67 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 395.83 | 705.00 | 0.00 | 0.00 | 0.00 | 3005.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 389.00 | 684.33 | 0.00 | 0.00 | 0.00 | 3028.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 370.33 | 601.75 | 0.00 | 0.00 | 0.00 | 3111.67 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 340.67 | 487.42 | 0.00 | 0.00 | 0.00 | 3220.17 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.1322 | 0.6400 | 0.0000 | 0.0000 | 0.0000 | 0.3782 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.9146 | 0.4020 | 0.0000 | 0.0000 | 0.0000 | 0.1900 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 1.0383 | 0.4680 | 0.0000 | 0.0000 | 0.0000 | 0.1797 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 1.0360 | 0.4707 | 0.0000 | 0.0000 | 0.0000 | 0.1797 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 1.0364 | 0.4759 | 0.0000 | 0.0000 | 0.0000 | 0.1797 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 1.1117 | 0.6812 | 0.0000 | 0.0000 | 0.0000 | 0.4138 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.8797 | 0.4514 | 0.0000 | 0.0000 | 0.0000 | 0.2074 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.8726 | 0.4507 | 0.0000 | 0.0000 | 0.0000 | 0.2074 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.8597 | 0.4489 | 0.0000 | 0.0000 | 0.0000 | 0.2072 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.9060 | 0.4730 | 0.0000 | 0.0000 | 0.0000 | 0.2069 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 835 |
Defaulted Fields | 817 |
Fields with Defaults | 2693 |
Autosized Fields | 174 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 669.55 | 2102.83 | 15-JAN-08:00 | 60563.28 | 10-AUG-16:50 |
Electricity:Building | 384.48 | 891.83 | 01-JAN-00:20 | 24308.12 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 86.72 | 148.64 | 01-JAN-00:20 | 4538.38 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 384.48 | 891.83 | 01-JAN-00:20 | 24308.12 | 01-JAN-11:10 |
InteriorLights:Electricity | 256.32 | 450.00 | 01-JAN-00:20 | 16248.62 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 60.47 | 75.00 | 01-JAN-00:20 | 3195.13 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 256.32 | 450.00 | 01-JAN-00:20 | 16248.62 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 256.32 | 450.00 | 01-JAN-00:20 | 16248.62 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 60.47 | 75.00 | 01-JAN-00:20 | 3195.13 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 256.32 | 450.00 | 01-JAN-00:20 | 16248.62 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 50.32 | 74.32 | 01-JAN-00:20 | 2641.91 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 37.20 | 37.50 | 01-JAN-00:20 | 1970.29 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 37.20 | 37.50 | 01-JAN-00:20 | 1970.29 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 37.48 | 74.32 | 01-JAN-00:10 | 2500.62 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 27.06 | 37.50 | 01-JAN-00:10 | 1829.00 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 27.06 | 37.50 | 01-JAN-00:10 | 1829.00 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 37.48 | 74.32 | 01-JAN-00:10 | 2500.62 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 27.06 | 37.50 | 01-JAN-00:10 | 1829.00 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 27.06 | 37.50 | 01-JAN-00:10 | 1829.00 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 37.48 | 74.32 | 01-JAN-00:10 | 2500.62 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 27.06 | 37.50 | 01-JAN-00:10 | 1829.00 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 27.06 | 37.50 | 01-JAN-00:10 | 1829.00 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 44.71 | 148.64 | 01-JAN-00:10 | 3187.05 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 25.54 | 75.00 | 01-JAN-00:10 | 1843.80 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 25.54 | 75.00 | 01-JAN-00:10 | 1843.80 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 22.57 | 74.32 | 01-JAN-00:10 | 1609.73 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 12.98 | 37.50 | 01-JAN-00:10 | 938.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 12.98 | 37.50 | 01-JAN-00:10 | 938.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 22.57 | 74.32 | 01-JAN-00:10 | 1609.73 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 12.98 | 37.50 | 01-JAN-00:10 | 938.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 12.98 | 37.50 | 01-JAN-00:10 | 938.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 22.57 | 74.32 | 01-JAN-00:10 | 1609.73 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 12.98 | 37.50 | 01-JAN-00:10 | 938.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 12.98 | 37.50 | 01-JAN-00:10 | 938.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 22.57 | 74.32 | 01-JAN-00:10 | 1609.73 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 12.98 | 37.50 | 01-JAN-00:10 | 938.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 12.98 | 37.50 | 01-JAN-00:10 | 938.10 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityProduced:Facility | 49.57 | -0.00 | 17-APR-18:50 | 11250.00 | 10-MAY-11:30 |
ElectricityProduced:Plant | 49.57 | -0.00 | 17-APR-18:50 | 11250.00 | 10-MAY-11:30 |
Photovoltaic:ElectricityProduced | 52.00 | 0.00 | 01-JAN-00:10 | 12106.99 | 18-MAY-11:30 |
PowerConversion:ElectricityProduced | -2.43 | -856.99 | 18-MAY-11:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 64.23 | 1211.00 | 05-JAN-07:10 | 12189.75 | 08-JAN-14:30 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 619.99 | 0.00 | 07-MAY-07:00 | 57396.36 | 29-AUG-17:00 |
ElectricityPurchased:Plant | 619.99 | 0.00 | 07-MAY-07:00 | 57396.36 | 29-AUG-17:00 |
Cogeneration:ElectricityPurchased | 619.99 | 0.00 | 07-MAY-07:00 | 57396.36 | 29-AUG-17:00 |
General:Cogeneration:ElectricityPurchased | 619.99 | 0.00 | 07-MAY-07:00 | 57396.36 | 29-AUG-17:00 |
ElectricitySurplusSold:Facility | 0.01 | 0.00 | 01-JAN-00:10 | 1604.73 | 25-JUN-07:00 |
ElectricitySurplusSold:Plant | 0.01 | 0.00 | 01-JAN-00:10 | 1604.73 | 25-JUN-07:00 |
Cogeneration:ElectricitySurplusSold | 0.01 | 0.00 | 01-JAN-00:10 | 1604.73 | 25-JUN-07:00 |
General:Cogeneration:ElectricitySurplusSold | 0.01 | 0.00 | 01-JAN-00:10 | 1604.73 | 25-JUN-07:00 |
ElectricityNet:Facility | 619.98 | -1604.73 | 25-JUN-07:00 | 57396.36 | 29-AUG-17:00 |
ElectricityNet:Plant | 619.98 | -1604.73 | 25-JUN-07:00 | 57396.36 | 29-AUG-17:00 |
Cogeneration:ElectricityNet | 619.98 | -1604.73 | 25-JUN-07:00 | 57396.36 | 29-AUG-17:00 |
General:Cogeneration:ElectricityNet | 619.98 | -1604.73 | 25-JUN-07:00 | 57396.36 | 29-AUG-17:00 |
Electricity:HVAC | 179.62 | 0.00 | 01-JAN-00:10 | 30819.47 | 10-AUG-16:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 20.45 | 0.00 | 01-JAN-00:10 | 21367.29 | 10-AUG-16:50 |
General:Cooling:Electricity | 20.45 | 0.00 | 01-JAN-00:10 | 21367.29 | 10-AUG-16:50 |
Fans:Electricity | 159.17 | 0.00 | 01-JAN-00:10 | 10028.61 | 26-DEC-08:10 |
General:Fans:Electricity | 159.17 | 0.00 | 01-JAN-00:10 | 10028.61 | 26-DEC-08:10 |
ExteriorLights:Electricity | 41.22 | 0.00 | 01-JAN-08:10 | 3786.68 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 41.22 | 0.00 | 01-JAN-08:10 | 3786.68 | 01-JAN-06:10 |
WaterSystems:Electricity | 64.23 | 1211.00 | 05-JAN-07:10 | 12189.75 | 08-JAN-14:30 |
Water Heater:WaterSystems:Electricity | 64.23 | 1211.00 | 05-JAN-07:10 | 12189.75 | 08-JAN-14:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 217.15 | 0.00 | 01-JAN-00:10 | 114340.00 | 16-JAN-09:10 |
NaturalGas:HVAC | 217.15 | 0.00 | 01-JAN-00:10 | 114340.00 | 16-JAN-09:10 |
Heating:NaturalGas | 217.15 | 0.00 | 01-JAN-00:10 | 114340.00 | 16-JAN-09:10 |
General:Heating:NaturalGas | 217.15 | 0.00 | 01-JAN-00:10 | 114340.00 | 16-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 564.87 | 0.00 | 01-JAN-00:10 | 198185.32 | 26-DEC-08:10 |
EnergyTransfer:Building | 281.14 | 0.00 | 01-JAN-00:10 | 98161.56 | 26-DEC-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 58.92 | 0.00 | 01-JAN-00:10 | 21642.65 | 19-FEB-08:10 |
Heating:EnergyTransfer | 92.53 | 0.00 | 01-JAN-00:10 | 98161.56 | 26-DEC-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 13.04 | 0.00 | 01-JAN-00:10 | 21642.65 | 19-FEB-08:10 |
General:Heating:EnergyTransfer | 92.53 | 0.00 | 01-JAN-00:10 | 98161.56 | 26-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 13.04 | 0.00 | 01-JAN-00:10 | 21642.65 | 19-FEB-08:10 |
Cooling:EnergyTransfer | 188.61 | 0.00 | 01-JAN-00:10 | 66421.71 | 10-AUG-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 45.88 | 0.00 | 01-JAN-00:10 | 11388.09 | 10-AUG-17:00 |
General:Cooling:EnergyTransfer | 188.61 | 0.00 | 01-JAN-00:10 | 66421.71 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 45.88 | 0.00 | 01-JAN-00:10 | 11388.09 | 10-AUG-17:00 |
EnergyTransfer:Zone:SMSTORE1 | 28.70 | 0.00 | 01-JAN-00:10 | 8523.88 | 09-AUG-21:20 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 3.88 | 0.00 | 01-JAN-00:10 | 7406.56 | 19-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 3.88 | 0.00 | 01-JAN-00:10 | 7406.56 | 19-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 24.82 | 0.00 | 01-JAN-00:10 | 8523.88 | 09-AUG-21:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 24.82 | 0.00 | 01-JAN-00:10 | 8523.88 | 09-AUG-21:20 |
EnergyTransfer:Zone:SMSTORE2 | 21.99 | 0.00 | 01-JAN-00:10 | 8853.50 | 19-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 5.24 | 0.00 | 01-JAN-00:10 | 8853.50 | 19-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 5.24 | 0.00 | 01-JAN-00:10 | 8853.50 | 19-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 16.75 | 0.00 | 01-JAN-00:10 | 5864.04 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 16.75 | 0.00 | 01-JAN-00:10 | 5864.04 | 10-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 22.05 | 0.00 | 01-JAN-00:10 | 9423.93 | 19-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 5.84 | 0.00 | 01-JAN-00:10 | 9423.93 | 19-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 5.84 | 0.00 | 01-JAN-00:10 | 9423.93 | 19-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 16.21 | 0.00 | 01-JAN-00:10 | 5874.91 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 16.21 | 0.00 | 01-JAN-00:10 | 5874.91 | 10-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE4 | 21.36 | 0.00 | 01-JAN-00:10 | 10113.67 | 19-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 6.96 | 0.00 | 01-JAN-00:10 | 10113.67 | 19-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 6.96 | 0.00 | 01-JAN-00:10 | 10113.67 | 19-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 14.40 | 0.00 | 01-JAN-00:10 | 5753.98 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 14.40 | 0.00 | 01-JAN-00:10 | 5753.98 | 10-AUG-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 41.17 | 0.00 | 01-JAN-00:10 | 21635.83 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 13.47 | 0.00 | 01-JAN-00:10 | 21635.83 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 13.47 | 0.00 | 01-JAN-00:10 | 21635.83 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 27.70 | 0.00 | 01-JAN-00:10 | 10363.42 | 10-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 27.70 | 0.00 | 01-JAN-00:10 | 10363.42 | 10-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 20.17 | 0.00 | 01-JAN-00:10 | 11191.39 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 8.14 | 0.00 | 01-JAN-00:10 | 11191.39 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 8.14 | 0.00 | 01-JAN-00:10 | 11191.39 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 12.03 | 0.00 | 01-JAN-00:10 | 5383.21 | 10-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 12.03 | 0.00 | 01-JAN-00:10 | 5383.21 | 10-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 20.14 | 0.00 | 01-JAN-00:10 | 11397.51 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 8.47 | 0.00 | 01-JAN-00:10 | 11397.51 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 8.47 | 0.00 | 01-JAN-00:10 | 11397.51 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 11.67 | 0.00 | 01-JAN-00:10 | 5337.57 | 10-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 11.67 | 0.00 | 01-JAN-00:10 | 5337.57 | 10-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 20.55 | 0.00 | 01-JAN-00:10 | 12273.16 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 10.15 | 0.00 | 01-JAN-00:10 | 12273.16 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 10.15 | 0.00 | 01-JAN-00:10 | 12273.16 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 10.40 | 0.00 | 01-JAN-00:10 | 5271.88 | 10-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 10.40 | 0.00 | 01-JAN-00:10 | 5271.88 | 10-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 26.09 | 0.00 | 01-JAN-00:10 | 16135.46 | 19-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 17.34 | 0.00 | 01-JAN-00:10 | 16135.46 | 19-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 17.34 | 0.00 | 01-JAN-00:10 | 16135.46 | 19-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 8.75 | 0.00 | 01-JAN-00:10 | 5562.40 | 10-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 8.75 | 0.00 | 01-JAN-00:10 | 5562.40 | 10-AUG-15:00 |
EnergyTransfer:HVAC | 283.73 | 0.00 | 01-JAN-00:10 | 100619.20 | 16-JAN-09:10 |
HeatingCoils:EnergyTransfer | 191.09 | 0.00 | 01-JAN-00:10 | 100619.20 | 16-JAN-09:10 |
CoolingCoils:EnergyTransfer | 92.64 | 0.00 | 01-JAN-00:10 | 97260.96 | 29-AUG-15:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 13.042 | -45.879 | 0.000 | 0.000 | 25.445 | 60.470 | 26.249 | 10.675 | 0.000 | 0.453 | 0.002 | 0.000 | -6.450 | 0.000 | -31.188 | -52.816 |
SMSTORE1 | 0.000 | 0.000 | 3.882 | -24.818 | 0.000 | 0.000 | 12.413 | 37.197 | 13.125 | 5.260 | 0.000 | 0.246 | 0.001 | 0.000 | -3.419 | 0.000 | -15.844 | -28.041 |
SMSTORE2 | 0.000 | 0.000 | 5.240 | -16.745 | 0.000 | 0.000 | 7.531 | 27.061 | 10.421 | 5.247 | 0.000 | 0.241 | 0.001 | 0.000 | -3.414 | 0.000 | -16.338 | -19.244 |
SMSTORE3 | 0.000 | 0.000 | 5.841 | -16.214 | 0.000 | 0.000 | 7.545 | 27.061 | 10.421 | 5.256 | 0.000 | 0.241 | 0.001 | 0.000 | -3.377 | 0.000 | -16.257 | -20.517 |
SMSTORE4 | 0.000 | 0.000 | 6.961 | -14.398 | 0.000 | 0.000 | 7.578 | 27.061 | 10.421 | 5.277 | 0.000 | 0.241 | 0.002 | 0.000 | -3.321 | 0.000 | -16.097 | -23.723 |
LGSTORE2 | 0.000 | 0.000 | 13.466 | -27.702 | 0.000 | 0.000 | 26.377 | 25.540 | 19.173 | 10.641 | 0.000 | 0.436 | 0.005 | 0.000 | -6.391 | 0.000 | -28.821 | -32.719 |
SMSTORE5 | 0.000 | 0.000 | 8.138 | -12.031 | 0.000 | 0.000 | 13.120 | 12.983 | 9.586 | 5.298 | 0.000 | 0.242 | 0.002 | 0.000 | -3.207 | 0.000 | -15.883 | -18.247 |
SMSTORE6 | 0.000 | 0.000 | 8.472 | -11.670 | 0.000 | 0.000 | 13.130 | 12.983 | 9.586 | 5.304 | 0.000 | 0.242 | 0.002 | 0.000 | -3.193 | 0.000 | -15.850 | -19.005 |
SMSTORE7 | 0.000 | 0.000 | 10.146 | -10.400 | 0.000 | 0.000 | 13.170 | 12.983 | 9.586 | 5.325 | 0.000 | 0.242 | 0.000 | 0.000 | -3.135 | 0.000 | -15.717 | -22.201 |
SMSTORE8 | 0.000 | 0.000 | 17.339 | -8.754 | 0.000 | 0.000 | 13.235 | 12.983 | 9.586 | 5.377 | 0.000 | 0.252 | 0.004 | 0.000 | -2.941 | 0.000 | -19.262 | -27.816 |
Total Facility | 0.000 | 0.000 | 92.526 | -188.612 | 0.000 | 0.000 | 139.544 | 256.325 | 128.154 | 63.660 | 0.000 | 2.836 | 0.020 | 0.000 | -38.848 | 0.000 | -191.258 | -264.329 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 10-AUG-17:00 | 0.00 | 0.00 | 0.00 | -11388.02 | 0.00 | 0.00 | 1970.03 | 3195.13 | 1343.25 | 423.71 | 0.00 | 2236.40 | 2219.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 07-JUL-21:15 | 0.00 | 0.00 | 0.00 | -16676.32 | 0.00 | 0.00 | 630.37 | 1970.29 | 671.63 | 0.00 | 0.00 | 0.00 | 13501.08 | 0.00 | -84.60 | 0.00 | -12.44 | 0.00 |
SMSTORE2 | 10-AUG-06:03 | 0.00 | 0.00 | 0.00 | -7797.59 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 7803.51 | 0.00 | -65.91 | 0.00 | -14.33 | 0.00 |
SMSTORE3 | 10-AUG-06:03 | 0.00 | 0.00 | 0.00 | -8049.76 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 8056.04 | 0.00 | -66.26 | 0.00 | -14.34 | 0.00 |
SMSTORE4 | 10-AUG-06:03 | 0.00 | 0.00 | 0.00 | -6835.44 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 6840.34 | 0.00 | -64.92 | 0.00 | -14.31 | 0.00 |
LGSTORE2 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | -10362.86 | 0.00 | 0.00 | 2718.69 | 1843.80 | 1343.25 | 1631.30 | 0.00 | 1780.05 | 1045.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | -5382.87 | 0.00 | 0.00 | 1359.37 | 938.10 | 671.63 | 814.82 | 0.00 | 991.02 | 607.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | -5337.23 | 0.00 | 0.00 | 1359.37 | 938.10 | 671.63 | 815.00 | 0.00 | 991.02 | 562.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | -5271.54 | 0.00 | 0.00 | 1359.37 | 938.10 | 671.63 | 815.11 | 0.00 | 991.02 | 496.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | -5562.06 | 0.00 | 0.00 | 1359.36 | 938.10 | 671.63 | 814.09 | 0.00 | 1015.38 | 763.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-16:10 | 0.00 | 0.00 | 0.00 | -66419.92 | 0.00 | 0.00 | 14302.99 | 16248.62 | 8059.50 | 5030.34 | 0.00 | 13366.97 | 9411.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 15-JAN-08:61 | 0.00 | 0.00 | 49344.30 | 0.00 | 0.00 | 0.00 | 265.29 | 75.00 | 74.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -398.01 | 0.00 | -1126.20 | -48235.00 |
SMSTORE1 | 15-JAN-08:61 | 0.00 | 0.00 | 25897.90 | 0.00 | 0.00 | 0.00 | 126.83 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -213.94 | 0.00 | -606.62 | -25278.99 |
SMSTORE2 | 15-JAN-08:61 | 0.00 | 0.00 | 28473.53 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -208.40 | 0.00 | -597.46 | -27742.49 |
SMSTORE3 | 15-JAN-08:61 | 0.00 | 0.00 | 28443.04 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -205.57 | 0.00 | -591.95 | -27720.33 |
SMSTORE4 | 15-JAN-08:61 | 0.00 | 0.00 | 28405.61 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -202.70 | 0.00 | -585.80 | -27691.93 |
LGSTORE2 | 17-JAN-08:61 | 0.00 | 0.00 | 48677.34 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -359.26 | 0.00 | -743.82 | -47722.90 |
SMSTORE5 | 17-JAN-08:61 | 0.00 | 0.00 | 24880.20 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -180.14 | 0.00 | -411.93 | -24362.44 |
SMSTORE6 | 17-JAN-08:61 | 0.00 | 0.00 | 24693.97 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -179.09 | 0.00 | -409.94 | -24179.26 |
SMSTORE7 | 16-JAN-09:12 | 0.00 | 0.00 | 24448.95 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -131.58 | 0.00 | -566.04 | -23825.66 |
SMSTORE8 | 16-JAN-09:12 | 0.00 | 0.00 | 25364.17 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -120.05 | 0.00 | -662.14 | -24656.30 |
Total Facility | 17-JAN-08:61 | 0.00 | 0.00 | 232975.73 | 0.00 | 0.00 | 0.00 | 733.27 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2251.60 | 0.00 | -5110.39 | -228249.23 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.6222 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.6222 | 0.2537 | 1.0000 | Not calculated | 0.4115 | 0.2537 | ||
PSZ-AC_2:2 | 0.8649 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8826 | 0.2331 | 1.0000 | Not calculated | 0.2057 | 0.2331 | ||
PSZ-AC_3:3 | 0.9818 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9818 | 0.2095 | 1.0000 | Not calculated | 0.2057 | 0.2095 | ||
PSZ-AC_4:4 | 0.9804 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9804 | 0.2098 | 1.0000 | Not calculated | 0.2057 | 0.2098 | ||
PSZ-AC_5:5 | 0.9787 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9787 | 0.2102 | 1.0000 | Not calculated | 0.2057 | 0.2102 | ||
PSZ-AC_6:6 | 1.5922 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.5922 | 0.2584 | 1.0000 | Not calculated | 0.4115 | 0.2584 | ||
PSZ-AC_7:7 | 0.8190 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8318 | 0.2473 | 1.0000 | Not calculated | 0.2057 | 0.2473 | ||
PSZ-AC_8:8 | 0.8106 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8244 | 0.2496 | 1.0000 | Not calculated | 0.2057 | 0.2496 | ||
PSZ-AC_9:9 | 0.7969 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8128 | 0.2531 | 1.0000 | Not calculated | 0.2057 | 0.2531 | ||
PSZ-AC_10:10 | 0.8311 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8557 | 0.2404 | 1.0000 | Not calculated | 0.2057 | 0.2404 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.6222 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.6222 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2537 | ||
PSZ-AC_2:2 | 0.8649 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8649 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2379 | ||
PSZ-AC_3:3 | 0.9818 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9818 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2095 | ||
PSZ-AC_4:4 | 0.9804 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9804 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2098 | ||
PSZ-AC_5:5 | 0.9787 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9787 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2102 | ||
PSZ-AC_6:6 | 1.5922 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.5922 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2584 | ||
PSZ-AC_7:7 | 0.8190 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8190 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2512 | ||
PSZ-AC_8:8 | 0.8106 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8106 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2538 | ||
PSZ-AC_9:9 | 0.7969 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.7969 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2582 | ||
PSZ-AC_10:10 | 0.8311 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8311 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2476 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.003540 | 56.2505 | 0.000610 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.003540 | 56.2505 | 0.000610 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.003540 | 28.1245 | 0.000610 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.003540 | 56.25 | 0.000610 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.003540 | 56.25 | 0.000610 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.003540 | 28.12 | 0.000610 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6222 | 1.6222 | 1.6222 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8649 | 0.8649 | 0.8649 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9818 | 0.9818 | 0.9818 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9804 | 0.9804 | 0.9804 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9787 | 0.9787 | 0.9787 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5922 | 1.5922 | 1.5922 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8190 | 0.8190 | 0.8190 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8106 | 0.8106 | 0.8106 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7969 | 0.7969 | 0.7969 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8311 | 0.8311 | 0.8311 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.6222 | 1.6222 | 1.6222 | 1.6222 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.8649 | 0.8826 | 0.8649 | 0.8649 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9818 | 0.9818 | 0.9818 | 0.9818 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9804 | 0.9804 | 0.9804 | 0.9804 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9787 | 0.9787 | 0.9787 | 0.9787 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.5922 | 1.5922 | 1.5922 | 1.5922 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.8190 | 0.8318 | 0.8190 | 0.8190 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.8106 | 0.8244 | 0.8106 | 0.8106 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.7969 | 0.8128 | 0.7969 | 0.7969 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.8311 | 0.8557 | 0.8311 | 0.8311 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6222 | 1.6222 | 1.6222 | No | 0.4115 | 0.4305 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8649 | 0.8649 | 0.8649 | No | 0.2057 | 0.4600 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9818 | 0.9818 | 0.9818 | No | 0.2057 | 0.4547 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9804 | 0.9804 | 0.9804 | No | 0.2057 | 0.4500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9787 | 0.9787 | 0.9787 | No | 0.2057 | 0.4415 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5922 | 1.5922 | 1.5922 | No | 0.4115 | 0.4566 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8190 | 0.8190 | 0.8190 | No | 0.2057 | 0.4283 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8106 | 0.8106 | 0.8106 | No | 0.2057 | 0.4280 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7969 | 0.7969 | 0.7969 | No | 0.2057 | 0.4151 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8311 | 0.8311 | 0.8311 | No | 0.2057 | 0.3367 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.6222 | 1.6222 | 1.6222 | 1.6222 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.8649 | 0.8649 | 0.8649 | 0.8649 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9818 | 0.9818 | 0.9818 | 0.9818 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9804 | 0.9804 | 0.9804 | 0.9804 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9787 | 0.9787 | 0.9787 | 0.9787 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.5922 | 1.5922 | 1.5922 | 1.5922 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.8190 | 0.8190 | 0.8190 | 0.8190 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.8106 | 0.8106 | 0.8106 | 0.8106 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.7969 | 0.7969 | 0.7969 | 0.7969 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.8311 | 0.8311 | 0.8311 | 0.8311 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 217.15 | 114340.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 20.45 | 21367.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 256.32 | 16248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 41.22 | 3786.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 159.17 | 10028.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 64.23 | 12189.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 669.55 |
Natural Gas | 0.00 | 217.15 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 886.70 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 52.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 122.62 |
Space Heating | 0.00 |
Space Cooling | 9.78 |
Fans (All) | 76.15 |
Service Water Heating | 30.73 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 320.31 |
Subtotal | 320.31 |
Natural Gas [MJ/m2] | |
Space Heating | 103.88 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 103.88 |
Subtotal | 103.88 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 28.91 |
Space Heating | 24.49 |
Space Cooling | 2.31 |
Fans (All) | 17.95 |
Service Water Heating | 7.24 |
Receptacle Equipment | 14.45 |
Miscellaneous | 4.65 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 2786. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 2826. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 3836. | 8760. |
LTG_SCH_BASE_LPD1 | 3781. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3073. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
Min | 8758.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1.33 | 0.00 | 0.00 | 0.00 |
Average | 8759.58 | 0.42 | 0.00 | 0.00 | 0.00 |
Sum | 87595.83 | 4.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25474.17 | 0.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25474.17 | 0.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25474.50 | 0.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93211.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45911.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45911.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45911.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45911.50 | 0.50 | 0.00 | 0.00 | 0.00 |
Min | 25474.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93211.00 | 0.83 | 0.00 | 0.00 | 0.00 |
Average | 48609.78 | 0.42 | 0.00 | 0.00 | 0.00 |
Sum | 486097.83 | 4.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8747.17 | 12.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
Min | 8747.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 13.00 | 0.00 | 0.00 | 0.00 |
Average | 8753.93 | 6.07 | 0.00 | 0.00 | 0.00 |
Sum | 87539.33 | 60.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25470.50 | 4.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25470.50 | 4.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25471.50 | 3.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93203.00 | 8.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45905.50 | 6.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45905.50 | 6.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45906.00 | 6.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45906.00 | 6.00 | 0.00 | 0.00 | 0.00 |
Min | 25470.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93203.00 | 8.00 | 0.00 | 0.00 | 0.00 |
Average | 48605.65 | 4.55 | 0.00 | 0.00 | 0.00 |
Sum | 486056.50 | 45.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:39:22
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.583745E+09 | 5688.33 | 14-JAN-22:03 | 0.50 | -2.5 | 0.106556E+10 | 1275.40 | 08-JAN-18:00 | 0.50 | -2.5 |
February | 0.101375E+10 | 4881.47 | 18-FEB-00:12 | -1.0 | -2.0 | 0.969208E+09 | 1322.96 | 27-FEB-17:10 | 18.62 | 12.15 |
March | 0.214158E+10 | 4093.92 | 01-MAR-18:30 | 8.30 | 4.02 | 0.107376E+10 | 1452.23 | 18-MAR-12:00 | 17.20 | 10.94 |
April | 0.330009E+10 | 6652.70 | 27-APR-16:10 | 27.02 | 16.89 | 0.113568E+10 | 1685.86 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.475697E+10 | 6862.02 | 15-MAY-16:40 | 24.23 | 12.96 | 0.129153E+10 | 1685.94 | 06-MAY-12:00 | 24.23 | 12.96 |
June | 0.563248E+10 | 8420.58 | 28-JUN-17:00 | 26.70 | 16.74 | 0.133341E+10 | 1685.92 | 11-JUN-12:30 | 26.70 | 16.74 |
July | 0.790519E+10 | 10006.41 | 31-JUL-16:10 | 28.80 | 19.11 | 0.141048E+10 | 1685.94 | 14-JUL-12:00 | 28.80 | 19.11 |
August | 0.836633E+10 | 11388.09 | 10-AUG-17:00 | 31.80 | 18.70 | 0.139259E+10 | 1685.94 | 25-AUG-12:09 | 24.62 | 18.30 |
September | 0.572683E+10 | 8236.18 | 14-SEP-16:20 | 24.60 | 16.93 | 0.133044E+10 | 1685.95 | 15-SEP-12:00 | 21.70 | 16.73 |
October | 0.384816E+10 | 5822.98 | 04-OCT-17:10 | 20.13 | 11.18 | 0.120411E+10 | 1685.85 | 08-OCT-16:30 | 19.15 | 12.85 |
November | 0.173918E+10 | 3646.43 | 08-NOV-18:10 | 9.32 | 7.68 | 0.105444E+10 | 1685.50 | 04-NOV-12:00 | 9.32 | 7.68 |
December | 0.864931E+09 | 5173.68 | 25-DEC-22:25 | 0.30 | 0.30 | 0.107099E+10 | 1275.40 | 25-DEC-18:00 | 0.30 | 0.30 |
Annual Sum or Average | 0.458792E+11 | 0.143322E+11 | ||||||||
Minimum of Months | 0.583745E+09 | 3646.43 | -1.0 | -2.5 | 0.969208E+09 | 1275.40 | 0.30 | -2.5 | ||
Maximum of Months | 0.836633E+10 | 11388.09 | 31.80 | 19.11 | 0.141048E+10 | 1685.95 | 28.80 | 19.11 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.320073E+09 | 1670.47 | 20-JAN-13:25 | 6.70 | 4.72 | 0.545727E+09 | 739.04 | 29-JAN-18:00 | 9.40 | 5.55 |
February | 0.426761E+09 | 1731.37 | 07-FEB-18:10 | 6.02 | 2.70 | 0.507837E+09 | 817.21 | 26-FEB-18:00 | 10.00 | 7.75 |
March | 0.884262E+09 | 1962.14 | 01-MAR-20:00 | 6.10 | 2.75 | 0.583985E+09 | 842.88 | 19-MAR-17:00 | 10.00 | 6.56 |
April | 0.141537E+10 | 15525.27 | 01-APR-21:02 | 21.02 | 10.06 | 0.625087E+09 | 842.91 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.245403E+10 | 15524.34 | 14-MAY-18:29 | 21.10 | 11.58 | 0.688195E+09 | 842.93 | 07-MAY-17:10 | 21.10 | 11.58 |
June | 0.348136E+10 | 16409.15 | 09-JUN-20:08 | 19.45 | 12.64 | 0.674799E+09 | 842.92 | 11-JUN-12:20 | 21.70 | 15.49 |
July | 0.467341E+10 | 16677.82 | 07-JUL-21:15 | 19.27 | 12.03 | 0.704561E+09 | 842.93 | 15-JUL-12:00 | 20.60 | 16.71 |
August | 0.495281E+10 | 15622.38 | 14-AUG-21:16 | 19.37 | 13.15 | 0.694416E+09 | 842.94 | 26-AUG-12:30 | 22.20 | 17.29 |
September | 0.332028E+10 | 15630.10 | 10-SEP-19:54 | 18.30 | 13.40 | 0.678696E+09 | 842.94 | 23-SEP-12:50 | 21.83 | 17.05 |
October | 0.171879E+10 | 3374.63 | 04-OCT-14:00 | 21.10 | 11.41 | 0.659883E+09 | 842.90 | 01-OCT-17:00 | 21.10 | 11.41 |
November | 0.751735E+09 | 2018.22 | 10-NOV-19:00 | 5.00 | 4.51 | 0.559488E+09 | 842.90 | 05-NOV-17:00 | 5.00 | 4.51 |
December | 0.419194E+09 | 1756.44 | 04-DEC-18:10 | 5.60 | 3.62 | 0.552447E+09 | 764.28 | 03-DEC-18:00 | 5.60 | 3.62 |
Annual Sum or Average | 0.248181E+11 | 0.747512E+10 | ||||||||
Minimum of Months | 0.320073E+09 | 1670.47 | 5.00 | 2.70 | 0.507837E+09 | 739.04 | 5.00 | 3.62 | ||
Maximum of Months | 0.495281E+10 | 16677.82 | 21.10 | 13.40 | 0.704561E+09 | 842.94 | 22.20 | 17.29 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154763E+09 | 1294.85 | 12-JAN-18:10 | 6.42 | 5.08 | 0.317512E+09 | 637.68 | 07-JAN-13:09 | 6.42 | 5.08 |
February | 0.249712E+09 | 1553.85 | 08-FEB-18:10 | 5.60 | 2.86 | 0.295783E+09 | 723.81 | 25-FEB-13:39 | 14.60 | 11.76 |
March | 0.646251E+09 | 1699.62 | 22-MAR-17:20 | 6.70 | 5.33 | 0.346341E+09 | 811.75 | 18-MAR-12:00 | 6.70 | 5.33 |
April | 0.959163E+09 | 3863.30 | 27-APR-16:10 | 27.02 | 16.89 | 0.365267E+09 | 842.90 | 01-APR-12:00 | 27.02 | 16.89 |
May | 0.161137E+10 | 3788.84 | 06-MAY-13:00 | 23.90 | 17.58 | 0.416586E+09 | 842.93 | 06-MAY-12:00 | 23.90 | 17.58 |
June | 0.232578E+10 | 4374.40 | 28-JUN-16:20 | 26.30 | 16.44 | 0.415586E+09 | 842.91 | 10-JUN-12:09 | 26.30 | 16.44 |
July | 0.320212E+10 | 5275.76 | 24-JUL-14:00 | 29.40 | 18.12 | 0.419575E+09 | 842.94 | 08-JUL-12:20 | 29.40 | 18.12 |
August | 0.357999E+10 | 7797.97 | 10-AUG-06:03 | 17.43 | 14.93 | 0.431261E+09 | 842.95 | 26-AUG-12:20 | 22.20 | 17.39 |
September | 0.216954E+10 | 4307.08 | 14-SEP-16:10 | 24.50 | 16.99 | 0.408055E+09 | 842.94 | 23-SEP-12:00 | 22.20 | 17.16 |
October | 0.112881E+10 | 3161.19 | 04-OCT-14:00 | 21.10 | 11.41 | 0.384450E+09 | 842.89 | 07-OCT-12:09 | 16.28 | 11.84 |
November | 0.484362E+09 | 1905.84 | 10-NOV-18:50 | 5.10 | 4.53 | 0.321407E+09 | 842.90 | 04-NOV-12:09 | 5.10 | 4.53 |
December | 0.233195E+09 | 1496.25 | 05-DEC-18:10 | 5.00 | 3.89 | 0.317561E+09 | 669.73 | 02-DEC-13:00 | 5.00 | 3.89 |
Annual Sum or Average | 0.167451E+11 | 0.443938E+10 | ||||||||
Minimum of Months | 0.154763E+09 | 1294.85 | 5.00 | 2.86 | 0.295783E+09 | 637.68 | 5.00 | 3.89 | ||
Maximum of Months | 0.357999E+10 | 7797.97 | 29.40 | 18.12 | 0.431261E+09 | 842.95 | 29.40 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125878E+09 | 1446.13 | 18-JAN-19:05 | 2.88 | 1.53 | 0.317445E+09 | 637.68 | 14-JAN-13:00 | 2.88 | 1.53 |
February | 0.215212E+09 | 1465.79 | 08-FEB-18:10 | 5.60 | 2.86 | 0.294948E+09 | 715.54 | 25-FEB-13:39 | 14.60 | 11.76 |
March | 0.582990E+09 | 1665.92 | 22-MAR-17:20 | 6.70 | 5.33 | 0.343752E+09 | 804.57 | 18-MAR-12:00 | 6.70 | 5.33 |
April | 0.893681E+09 | 3733.44 | 27-APR-16:10 | 27.02 | 16.89 | 0.361733E+09 | 842.90 | 01-APR-12:00 | 27.02 | 16.89 |
May | 0.153926E+10 | 3753.80 | 06-MAY-13:00 | 23.90 | 17.58 | 0.415363E+09 | 842.93 | 06-MAY-12:00 | 23.90 | 17.58 |
June | 0.228064E+10 | 4358.85 | 28-JUN-16:20 | 26.30 | 16.44 | 0.415474E+09 | 842.91 | 10-JUN-12:09 | 26.30 | 16.44 |
July | 0.318161E+10 | 5284.35 | 24-JUL-14:00 | 29.40 | 18.12 | 0.419565E+09 | 842.93 | 08-JUL-12:20 | 29.40 | 18.12 |
August | 0.357651E+10 | 8050.22 | 10-AUG-06:03 | 17.43 | 14.93 | 0.431255E+09 | 842.95 | 26-AUG-12:20 | 22.20 | 17.39 |
September | 0.212403E+10 | 4295.53 | 14-SEP-16:10 | 24.50 | 16.99 | 0.407766E+09 | 842.94 | 23-SEP-12:00 | 22.20 | 17.16 |
October | 0.106823E+10 | 3083.81 | 04-OCT-14:00 | 21.10 | 11.41 | 0.380678E+09 | 842.89 | 07-OCT-12:09 | 16.28 | 11.84 |
November | 0.427660E+09 | 1844.83 | 10-NOV-18:10 | 5.50 | 4.58 | 0.319679E+09 | 842.90 | 04-NOV-12:09 | 5.50 | 4.58 |
December | 0.198150E+09 | 1374.63 | 05-DEC-18:10 | 5.00 | 3.89 | 0.317351E+09 | 664.45 | 02-DEC-13:00 | 5.00 | 3.89 |
Annual Sum or Average | 0.162139E+11 | 0.442501E+10 | ||||||||
Minimum of Months | 0.125878E+09 | 1374.63 | 2.88 | 1.53 | 0.294948E+09 | 637.68 | 2.88 | 1.53 | ||
Maximum of Months | 0.357651E+10 | 8050.22 | 29.40 | 18.12 | 0.431255E+09 | 842.95 | 29.40 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 84247403.23 | 1591.40 | 19-JAN-19:45 | 1.78 | 0.84 | 0.317358E+09 | 637.68 | 07-JAN-13:20 | 1.78 | 0.84 |
February | 0.164209E+09 | 1528.21 | 16-FEB-19:05 | 2.20 | 0.79 | 0.293507E+09 | 699.00 | 25-FEB-13:39 | 14.60 | 11.76 |
March | 0.465674E+09 | 1604.42 | 01-MAR-19:00 | 7.20 | 2.85 | 0.339070E+09 | 787.77 | 18-MAR-12:00 | 17.20 | 10.94 |
April | 0.744452E+09 | 3403.41 | 27-APR-16:10 | 27.02 | 16.89 | 0.354442E+09 | 842.90 | 29-APR-12:09 | 18.58 | 14.14 |
May | 0.129346E+10 | 3551.00 | 06-MAY-13:00 | 23.90 | 17.58 | 0.410142E+09 | 842.93 | 06-MAY-12:00 | 23.90 | 17.58 |
June | 0.203374E+10 | 4222.23 | 28-JUN-16:20 | 26.30 | 16.44 | 0.414685E+09 | 842.91 | 10-JUN-12:09 | 26.30 | 16.44 |
July | 0.297597E+10 | 5160.35 | 24-JUL-14:00 | 29.40 | 18.12 | 0.419501E+09 | 842.93 | 08-JUL-12:20 | 29.40 | 18.12 |
August | 0.337546E+10 | 6835.58 | 10-AUG-06:03 | 17.43 | 14.93 | 0.431201E+09 | 842.95 | 26-AUG-12:20 | 22.20 | 17.39 |
September | 0.189841E+10 | 4166.05 | 14-SEP-16:10 | 24.50 | 16.99 | 0.406132E+09 | 842.94 | 23-SEP-12:00 | 22.20 | 17.16 |
October | 0.894232E+09 | 2858.85 | 04-OCT-17:10 | 20.13 | 11.18 | 0.372412E+09 | 842.90 | 07-OCT-12:09 | 16.28 | 11.84 |
November | 0.328038E+09 | 1578.79 | 10-NOV-18:10 | 5.50 | 4.58 | 0.316590E+09 | 842.90 | 04-NOV-12:20 | 5.50 | 4.58 |
December | 0.140360E+09 | 1181.84 | 05-DEC-18:10 | 5.00 | 3.89 | 0.317033E+09 | 653.01 | 02-DEC-13:00 | 5.00 | 3.89 |
Annual Sum or Average | 0.143982E+11 | 0.439207E+10 | ||||||||
Minimum of Months | 84247403.23 | 1181.84 | 1.78 | 0.79 | 0.293507E+09 | 637.68 | 1.78 | 0.84 | ||
Maximum of Months | 0.337546E+10 | 6835.58 | 29.40 | 18.12 | 0.431201E+09 | 842.95 | 29.40 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44362749.12 | 4348.69 | 31-JAN-18:45 | 5.10 | 4.78 | 0.108439E+10 | 1700.53 | 07-JAN-15:20 | 5.10 | 4.78 |
February | 0.299572E+09 | 4410.77 | 06-FEB-19:05 | 3.90 | 2.96 | 0.993041E+09 | 1819.41 | 27-FEB-15:50 | 19.50 | 12.39 |
March | 0.102041E+10 | 3527.38 | 16-MAR-14:35 | 10.40 | 7.14 | 0.112972E+10 | 2186.22 | 18-MAR-14:00 | 20.00 | 10.34 |
April | 0.190222E+10 | 5825.69 | 27-APR-15:00 | 27.20 | 17.29 | 0.114806E+10 | 2247.87 | 29-APR-14:00 | 22.20 | 15.23 |
May | 0.312607E+10 | 6186.93 | 06-MAY-14:10 | 23.90 | 16.75 | 0.131288E+10 | 2247.91 | 06-MAY-14:00 | 23.90 | 17.27 |
June | 0.370717E+10 | 7699.11 | 28-JUN-15:00 | 26.10 | 15.54 | 0.139494E+10 | 2247.83 | 03-JUN-14:09 | 26.10 | 15.54 |
July | 0.515525E+10 | 10033.87 | 24-JUL-15:00 | 30.60 | 18.78 | 0.143264E+10 | 2247.94 | 15-JUL-14:00 | 30.60 | 18.78 |
August | 0.582444E+10 | 10363.42 | 10-AUG-15:00 | 30.20 | 18.90 | 0.147699E+10 | 2247.92 | 26-AUG-14:50 | 20.25 | 16.60 |
September | 0.371718E+10 | 7719.63 | 14-SEP-14:30 | 23.90 | 17.04 | 0.134885E+10 | 2247.93 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.220212E+10 | 5032.28 | 04-OCT-15:00 | 21.70 | 11.49 | 0.119173E+10 | 2247.73 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.596844E+09 | 2789.64 | 07-NOV-11:40 | 11.47 | 10.45 | 0.105780E+10 | 2247.81 | 04-NOV-14:50 | 11.47 | 10.45 |
December | 0.106230E+09 | 4368.24 | 13-DEC-18:55 | 5.00 | 2.61 | 0.108625E+10 | 1700.53 | 02-DEC-15:20 | 5.00 | 2.61 |
Annual Sum or Average | 0.277019E+11 | 0.146573E+11 | ||||||||
Minimum of Months | 44362749.12 | 2789.64 | 3.90 | 2.61 | 0.993041E+09 | 1700.53 | 5.00 | 2.61 | ||
Maximum of Months | 0.582444E+10 | 10363.42 | 30.60 | 18.90 | 0.147699E+10 | 2247.94 | 30.60 | 18.78 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14774459.46 | 719.98 | 11-JAN-17:40 | 12.60 | 9.50 | 0.542186E+09 | 850.24 | 07-JAN-15:39 | 12.60 | 9.50 |
February | 0.101079E+09 | 1650.81 | 09-FEB-19:05 | 3.48 | 1.81 | 0.498223E+09 | 934.89 | 27-FEB-15:50 | 19.50 | 12.39 |
March | 0.369793E+09 | 1405.79 | 01-MAR-12:00 | 8.30 | 4.65 | 0.568776E+09 | 1118.50 | 18-MAR-14:00 | 20.00 | 10.34 |
April | 0.658854E+09 | 3008.95 | 27-APR-15:00 | 27.20 | 17.29 | 0.584200E+09 | 1123.89 | 29-APR-14:00 | 22.20 | 15.23 |
May | 0.113779E+10 | 3145.29 | 06-MAY-14:10 | 23.90 | 16.75 | 0.673694E+09 | 1123.90 | 06-MAY-14:00 | 23.90 | 17.27 |
June | 0.165951E+10 | 3953.24 | 28-JUN-15:00 | 26.10 | 15.54 | 0.704875E+09 | 1123.87 | 03-JUN-14:09 | 26.10 | 15.54 |
July | 0.253880E+10 | 5233.43 | 24-JUL-15:00 | 30.60 | 18.78 | 0.717821E+09 | 1123.92 | 15-JUL-14:30 | 30.60 | 18.78 |
August | 0.291280E+10 | 5383.21 | 10-AUG-15:00 | 30.20 | 18.90 | 0.739335E+09 | 1123.90 | 26-AUG-14:09 | 20.45 | 16.60 |
September | 0.161390E+10 | 3949.36 | 14-SEP-14:30 | 23.90 | 17.04 | 0.685290E+09 | 1123.92 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.773566E+09 | 2613.16 | 04-OCT-15:00 | 21.70 | 11.49 | 0.608274E+09 | 1123.85 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.207841E+09 | 1424.24 | 10-NOV-15:45 | 9.08 | 6.54 | 0.531024E+09 | 1123.85 | 04-NOV-14:09 | 9.08 | 6.54 |
December | 42615257.99 | 1401.75 | 04-DEC-19:25 | 5.30 | 3.68 | 0.543127E+09 | 850.24 | 02-DEC-15:09 | 5.30 | 3.68 |
Annual Sum or Average | 0.120313E+11 | 0.739683E+10 | ||||||||
Minimum of Months | 14774459.46 | 719.98 | 3.48 | 1.81 | 0.498223E+09 | 850.24 | 5.30 | 3.68 | ||
Maximum of Months | 0.291280E+10 | 5383.21 | 30.60 | 18.90 | 0.739335E+09 | 1123.92 | 30.60 | 18.78 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13269868.91 | 1153.87 | 25-JAN-18:50 | 7.30 | 6.18 | 0.542183E+09 | 850.24 | 14-JAN-15:09 | 7.30 | 6.18 |
February | 94064036.99 | 1029.80 | 01-FEB-13:30 | 10.85 | 8.01 | 0.497943E+09 | 930.24 | 27-FEB-15:50 | 19.50 | 12.39 |
March | 0.344414E+09 | 1595.48 | 24-MAR-12:55 | 8.30 | 2.54 | 0.568105E+09 | 1112.93 | 18-MAR-14:00 | 8.30 | 2.54 |
April | 0.629654E+09 | 2937.12 | 27-APR-15:00 | 27.20 | 17.29 | 0.582521E+09 | 1123.89 | 29-APR-14:00 | 22.20 | 15.23 |
May | 0.110110E+10 | 3073.43 | 06-MAY-14:10 | 23.90 | 16.75 | 0.670413E+09 | 1123.90 | 06-MAY-14:00 | 23.90 | 17.27 |
June | 0.160470E+10 | 3896.37 | 28-JUN-15:00 | 26.10 | 15.54 | 0.703965E+09 | 1123.87 | 03-JUN-14:09 | 26.10 | 15.54 |
July | 0.247673E+10 | 5181.80 | 24-JUL-15:00 | 30.60 | 18.78 | 0.717704E+09 | 1123.92 | 15-JUL-14:39 | 30.60 | 18.78 |
August | 0.285444E+10 | 5337.57 | 10-AUG-15:00 | 30.20 | 18.90 | 0.739290E+09 | 1123.90 | 26-AUG-14:09 | 20.45 | 16.60 |
September | 0.157640E+10 | 3902.37 | 14-SEP-14:30 | 23.90 | 17.04 | 0.684142E+09 | 1123.92 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.742241E+09 | 2533.28 | 04-OCT-15:00 | 21.70 | 11.49 | 0.606423E+09 | 1123.85 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.195046E+09 | 2059.43 | 13-NOV-11:05 | 3.07 | 2.87 | 0.530698E+09 | 1123.86 | 04-NOV-14:09 | 3.07 | 2.87 |
December | 37581451.24 | 1591.97 | 07-DEC-18:15 | 5.00 | 4.43 | 0.543121E+09 | 850.24 | 02-DEC-15:09 | 5.00 | 4.43 |
Annual Sum or Average | 0.116696E+11 | 0.738651E+10 | ||||||||
Minimum of Months | 13269868.91 | 1029.80 | 3.07 | 2.54 | 0.497943E+09 | 850.24 | 3.07 | 2.54 | ||
Maximum of Months | 0.285444E+10 | 5337.57 | 30.60 | 18.90 | 0.739290E+09 | 1123.92 | 30.60 | 18.78 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5832527.40 | 2244.59 | 14-JAN-11:45 | 3.72 | 1.58 | 0.542181E+09 | 850.24 | 07-JAN-15:20 | 3.72 | 1.58 |
February | 60277437.87 | 1914.19 | 09-FEB-18:05 | 2.88 | 1.32 | 0.497062E+09 | 913.56 | 27-FEB-15:50 | 19.50 | 12.39 |
March | 0.242525E+09 | 1263.47 | 27-MAR-10:10 | 7.48 | 4.38 | 0.566065E+09 | 1094.14 | 18-MAR-14:00 | 7.48 | 4.38 |
April | 0.517876E+09 | 2735.87 | 27-APR-15:00 | 27.20 | 17.29 | 0.576875E+09 | 1123.88 | 29-APR-14:00 | 22.20 | 15.23 |
May | 0.967245E+09 | 2871.77 | 06-MAY-14:10 | 23.90 | 16.75 | 0.658038E+09 | 1123.90 | 06-MAY-14:00 | 23.90 | 17.27 |
June | 0.142316E+10 | 3747.83 | 28-JUN-15:00 | 26.10 | 15.54 | 0.699573E+09 | 1123.87 | 03-JUN-14:09 | 26.10 | 15.54 |
July | 0.228475E+10 | 5081.14 | 24-JUL-15:00 | 30.60 | 18.78 | 0.717064E+09 | 1123.92 | 15-JUL-14:50 | 30.60 | 18.78 |
August | 0.268236E+10 | 5271.88 | 10-AUG-15:00 | 30.20 | 18.90 | 0.739032E+09 | 1123.90 | 26-AUG-14:09 | 20.45 | 16.60 |
September | 0.143547E+10 | 3799.87 | 14-SEP-14:30 | 23.90 | 17.04 | 0.678224E+09 | 1123.92 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.625271E+09 | 2282.51 | 04-OCT-15:00 | 21.70 | 11.49 | 0.599464E+09 | 1123.85 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.135301E+09 | 1733.73 | 28-NOV-11:15 | 5.20 | 4.21 | 0.529655E+09 | 1123.86 | 04-NOV-14:09 | 5.20 | 4.21 |
December | 19685629.06 | 1445.66 | 01-DEC-18:55 | 6.10 | 5.59 | 0.543092E+09 | 850.24 | 02-DEC-15:09 | 11.52 | 5.36 |
Annual Sum or Average | 0.103998E+11 | 0.734632E+10 | ||||||||
Minimum of Months | 5832527.40 | 1263.47 | 2.88 | 1.32 | 0.497062E+09 | 850.24 | 3.72 | 1.58 | ||
Maximum of Months | 0.268236E+10 | 5271.88 | 30.60 | 18.90 | 0.739032E+09 | 1123.92 | 30.60 | 18.78 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 | 4.99 | 0.542193E+09 | 850.24 | 14-JAN-15:30 | 4.45 | 0.96 |
February | 15029829.06 | 820.64 | 03-FEB-11:20 | 10.20 | 7.37 | 0.495906E+09 | 884.27 | 27-FEB-15:50 | 19.50 | 12.39 |
March | 64917526.18 | 986.39 | 24-MAR-17:40 | 8.17 | 2.23 | 0.563542E+09 | 1059.90 | 18-MAR-14:00 | 8.17 | 2.23 |
April | 0.312244E+09 | 2674.48 | 27-APR-15:00 | 27.20 | 17.29 | 0.569750E+09 | 1123.88 | 29-APR-14:00 | 22.20 | 15.23 |
May | 0.715234E+09 | 2787.67 | 06-MAY-13:40 | 23.90 | 16.96 | 0.639761E+09 | 1123.91 | 06-MAY-14:00 | 23.90 | 17.27 |
June | 0.122382E+10 | 3710.64 | 28-JUN-15:00 | 26.10 | 15.54 | 0.690197E+09 | 1123.87 | 03-JUN-14:09 | 26.10 | 15.54 |
July | 0.211605E+10 | 5326.01 | 24-JUL-15:00 | 30.60 | 18.78 | 0.714621E+09 | 1123.92 | 15-JUL-14:50 | 30.60 | 18.78 |
August | 0.259590E+10 | 5562.40 | 10-AUG-15:00 | 30.20 | 18.90 | 0.737802E+09 | 1123.89 | 26-AUG-14:09 | 20.45 | 16.60 |
September | 0.127318E+10 | 3868.09 | 14-SEP-14:10 | 23.90 | 17.09 | 0.665828E+09 | 1123.92 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.391096E+09 | 1980.87 | 04-OCT-15:00 | 21.70 | 11.49 | 0.590142E+09 | 1123.86 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 45189685.26 | 781.31 | 06-NOV-17:50 | 12.12 | 11.43 | 0.528511E+09 | 1123.86 | 04-NOV-14:09 | 12.12 | 11.43 |
December | 1691991.18 | 517.67 | 02-DEC-12:00 | 12.20 | 6.13 | 0.543112E+09 | 850.24 | 02-DEC-15:50 | 10.78 | 4.73 |
Annual Sum or Average | 0.875436E+10 | 0.728136E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 5.92 | 2.23 | 0.495906E+09 | 850.24 | 4.45 | 0.96 | ||
Maximum of Months | 0.259590E+10 | 5562.40 | 30.60 | 18.90 | 0.737802E+09 | 1123.92 | 30.60 | 18.78 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.394334E+10 | 49344.27 | 15-JAN-08:61 | -3.7 |
February | 0.253294E+10 | 49318.77 | 08-FEB-08:61 | -0.4 |
March | 0.112726E+10 | 49321.13 | 25-MAR-07:01 | 2.15 |
April | 0.375906E+09 | 49313.83 | 19-APR-07:01 | 4.18 |
May | 76303534.95 | 15947.61 | 19-MAY-07:02 | 8.40 |
June | 59977186.91 | 656.42 | 15-JUN-07:15 | 10.97 |
July | 40794678.87 | 864.69 | 24-JUL-07:10 | 19.37 |
August | 31236035.50 | 859.13 | 10-AUG-07:10 | 19.83 |
September | 58595063.66 | 675.68 | 26-SEP-08:00 | 12.80 |
October | 0.173985E+09 | 49151.30 | 30-OCT-07:01 | 7.20 |
November | 0.149676E+10 | 49332.87 | 24-NOV-08:61 | 1.97 |
December | 0.312462E+10 | 49334.32 | 11-DEC-08:61 | 2.88 |
Annual Sum or Average | 0.130417E+11 | |||
Minimum of Months | 31236035.50 | 656.42 | -3.7 | |
Maximum of Months | 0.394334E+10 | 49344.27 | 19.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126333E+10 | 25897.92 | 15-JAN-08:61 | -3.7 |
February | 0.728396E+09 | 25883.96 | 08-FEB-08:61 | -0.4 |
March | 0.192468E+09 | 25887.42 | 25-MAR-07:01 | 2.15 |
April | 0.101408E+09 | 24291.20 | 19-APR-07:01 | 4.18 |
May | 75995819.12 | 939.38 | 19-MAY-07:02 | 8.40 |
June | 24798818.01 | 911.57 | 15-JUN-07:15 | 10.97 |
July | 4467147.00 | 1147.75 | 24-JUL-07:10 | 19.37 |
August | 8397986.67 | 1135.83 | 10-AUG-07:10 | 19.83 |
September | 28691892.93 | 920.34 | 28-SEP-07:15 | 9.27 |
October | 85976576.45 | 947.71 | 30-OCT-07:01 | 7.20 |
November | 0.409186E+09 | 25889.31 | 24-NOV-08:61 | 1.97 |
December | 0.958704E+09 | 25890.76 | 22-DEC-08:61 | 0.10 |
Annual Sum or Average | 0.388182E+10 | |||
Minimum of Months | 4467147.00 | 911.57 | -3.7 | |
Maximum of Months | 0.126333E+10 | 25897.92 | 19.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164072E+10 | 28473.54 | 15-JAN-08:61 | -3.7 |
February | 0.976908E+09 | 28448.20 | 20-FEB-08:61 | 0.18 |
March | 0.288463E+09 | 28048.42 | 05-MAR-08:61 | 2.38 |
April | 0.122103E+09 | 12756.67 | 19-APR-06:03 | 2.48 |
May | 80163432.15 | 1011.65 | 28-MAY-08:00 | 8.30 |
June | 35536276.81 | 861.58 | 18-JUN-07:10 | 11.28 |
July | 34654093.10 | 1328.07 | 23-JUL-16:12 | 27.43 |
August | 47343296.92 | 1488.73 | 10-AUG-19:12 | 28.47 |
September | 30802970.19 | 1009.83 | 28-SEP-07:00 | 8.90 |
October | 90626556.38 | 1037.70 | 22-OCT-08:00 | 7.80 |
November | 0.611465E+09 | 27865.74 | 24-NOV-07:02 | 1.20 |
December | 0.128165E+10 | 28224.48 | 26-DEC-07:01 | -1.6 |
Annual Sum or Average | 0.524043E+10 | |||
Minimum of Months | 30802970.19 | 861.58 | -3.7 | |
Maximum of Months | 0.164072E+10 | 28473.54 | 28.47 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180316E+10 | 28443.05 | 15-JAN-08:61 | -3.7 |
February | 0.108506E+10 | 28417.92 | 20-FEB-08:61 | 0.18 |
March | 0.355580E+09 | 28018.97 | 05-MAR-08:61 | 2.38 |
April | 0.137530E+09 | 15428.08 | 19-APR-06:03 | 2.48 |
May | 84710966.59 | 1010.76 | 28-MAY-08:00 | 8.30 |
June | 40586785.42 | 896.47 | 15-JUN-06:40 | 10.20 |
July | 35856222.79 | 1327.57 | 23-JUL-16:12 | 27.43 |
August | 48447679.56 | 1487.44 | 10-AUG-19:12 | 28.47 |
September | 36443909.27 | 1011.19 | 27-SEP-07:00 | 8.90 |
October | 96350244.82 | 3978.66 | 30-OCT-06:03 | 7.20 |
November | 0.698548E+09 | 27840.06 | 26-NOV-08:62 | 3.98 |
December | 0.141859E+10 | 28195.33 | 26-DEC-07:01 | -1.6 |
Annual Sum or Average | 0.584087E+10 | |||
Minimum of Months | 35856222.79 | 896.47 | -3.7 | |
Maximum of Months | 0.180316E+10 | 28443.05 | 28.47 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207753E+10 | 28405.62 | 15-JAN-08:61 | -3.7 |
February | 0.128639E+10 | 28380.65 | 20-FEB-08:61 | 0.18 |
March | 0.493436E+09 | 27983.39 | 05-MAR-08:61 | 2.38 |
April | 0.180932E+09 | 19218.27 | 19-APR-06:03 | 2.48 |
May | 95081088.85 | 1010.76 | 28-MAY-08:00 | 8.30 |
June | 56724486.76 | 985.47 | 14-JUN-07:00 | 10.60 |
July | 40491238.32 | 1330.34 | 23-JUL-16:12 | 27.43 |
August | 53123017.40 | 1490.72 | 10-AUG-19:12 | 28.47 |
September | 51895201.03 | 1011.99 | 27-SEP-07:00 | 8.90 |
October | 0.115584E+09 | 8147.35 | 30-OCT-06:03 | 7.20 |
November | 0.851661E+09 | 27804.65 | 26-NOV-08:62 | 3.98 |
December | 0.165767E+10 | 28159.34 | 26-DEC-07:01 | -1.6 |
Annual Sum or Average | 0.696052E+10 | |||
Minimum of Months | 40491238.32 | 985.47 | -3.7 | |
Maximum of Months | 0.207753E+10 | 28405.62 | 28.47 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408833E+10 | 48677.33 | 17-JAN-08:61 | 1.70 |
February | 0.249563E+10 | 48662.37 | 06-FEB-08:61 | 3.90 |
March | 0.108613E+10 | 48664.10 | 25-MAR-07:01 | 2.15 |
April | 0.386429E+09 | 48657.84 | 19-APR-07:01 | 4.18 |
May | 76413310.16 | 23451.81 | 29-MAY-08:61 | 10.60 |
June | 58256113.97 | 657.15 | 15-JUN-07:15 | 10.97 |
July | 43225689.48 | 1387.31 | 23-JUL-16:12 | 27.43 |
August | 37521685.14 | 1517.30 | 13-AUG-16:03 | 28.08 |
September | 55564689.45 | 666.97 | 26-SEP-08:00 | 12.80 |
October | 0.240297E+09 | 48501.40 | 30-OCT-07:01 | 7.20 |
November | 0.165300E+10 | 48671.66 | 24-NOV-08:61 | 1.97 |
December | 0.324492E+10 | 48673.46 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.134657E+11 | |||
Minimum of Months | 37521685.14 | 657.15 | -1.1 | |
Maximum of Months | 0.408833E+10 | 48677.33 | 28.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234446E+10 | 24880.19 | 17-JAN-08:61 | 1.70 |
February | 0.146969E+10 | 24872.65 | 08-FEB-08:61 | -0.4 |
March | 0.675465E+09 | 24874.01 | 25-MAR-07:01 | 2.15 |
April | 0.262050E+09 | 24870.10 | 19-APR-07:01 | 4.18 |
May | 96295732.31 | 13360.68 | 29-MAY-08:61 | 10.60 |
June | 67537584.81 | 865.17 | 15-JUN-07:15 | 10.97 |
July | 41125687.06 | 1226.37 | 30-JUL-16:12 | 27.43 |
August | 35737195.18 | 1219.00 | 13-AUG-16:23 | 27.85 |
September | 65117340.72 | 883.11 | 26-SEP-08:00 | 12.80 |
October | 0.184458E+09 | 24786.92 | 30-OCT-07:01 | 7.20 |
November | 0.100965E+10 | 24877.42 | 24-NOV-08:61 | 1.97 |
December | 0.188668E+10 | 24878.74 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.813826E+10 | |||
Minimum of Months | 35737195.18 | 865.17 | -1.1 | |
Maximum of Months | 0.234446E+10 | 24880.19 | 27.85 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241131E+10 | 24693.96 | 17-JAN-08:61 | 1.70 |
February | 0.152443E+10 | 24687.15 | 08-FEB-08:61 | -0.4 |
March | 0.725231E+09 | 24688.68 | 25-MAR-07:01 | 2.15 |
April | 0.284644E+09 | 24684.66 | 19-APR-07:01 | 4.18 |
May | 98837574.56 | 16374.38 | 29-MAY-08:61 | 10.60 |
June | 70815205.80 | 858.93 | 15-JUN-07:15 | 10.97 |
July | 46046723.77 | 1218.30 | 30-JUL-16:12 | 27.43 |
August | 38337922.55 | 1212.93 | 13-AUG-16:23 | 27.85 |
September | 67379563.03 | 875.97 | 26-SEP-08:00 | 12.80 |
October | 0.198613E+09 | 24602.78 | 30-OCT-07:01 | 7.20 |
November | 0.105872E+10 | 24691.98 | 24-NOV-08:61 | 1.97 |
December | 0.194719E+10 | 24693.25 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.847155E+10 | |||
Minimum of Months | 38337922.55 | 858.93 | -1.1 | |
Maximum of Months | 0.241131E+10 | 24693.96 | 27.85 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.278760E+10 | 24448.96 | 16-JAN-09:12 | -0.4 |
February | 0.181297E+10 | 24406.99 | 19-FEB-09:12 | -2.9 |
March | 0.945662E+09 | 24385.95 | 25-MAR-07:01 | 2.15 |
April | 0.395812E+09 | 24383.06 | 19-APR-07:01 | 4.18 |
May | 0.115743E+09 | 24083.70 | 29-MAY-08:61 | 10.60 |
June | 81680550.21 | 850.22 | 15-JUN-07:15 | 10.97 |
July | 65149659.67 | 1210.31 | 23-JUL-16:12 | 27.43 |
August | 49505764.41 | 1205.16 | 13-AUG-16:23 | 27.85 |
September | 76687853.06 | 1591.65 | 28-SEP-07:03 | 9.08 |
October | 0.271687E+09 | 24303.14 | 30-OCT-07:01 | 7.20 |
November | 0.127057E+10 | 24389.65 | 24-NOV-08:61 | 1.97 |
December | 0.227280E+10 | 24390.93 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.101459E+11 | |||
Minimum of Months | 49505764.41 | 850.22 | -2.9 | |
Maximum of Months | 0.278760E+10 | 24448.96 | 27.85 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.440741E+10 | 25364.18 | 16-JAN-09:12 | -0.4 |
February | 0.306926E+10 | 25323.07 | 19-FEB-09:12 | -2.9 |
March | 0.192636E+10 | 25143.23 | 16-MAR-07:01 | 4.60 |
April | 0.875704E+09 | 25139.75 | 19-APR-07:01 | 4.18 |
May | 0.271221E+09 | 24821.25 | 29-MAY-08:61 | 10.60 |
June | 96199555.20 | 8986.33 | 15-JUN-07:03 | 10.78 |
July | 88787812.60 | 1246.76 | 30-JUL-16:12 | 27.43 |
August | 76605716.20 | 1246.28 | 13-AUG-16:23 | 27.85 |
September | 99693646.86 | 16814.05 | 28-SEP-07:03 | 9.08 |
October | 0.596306E+09 | 25056.77 | 30-OCT-07:01 | 7.20 |
November | 0.216717E+10 | 25153.62 | 13-NOV-08:61 | 0.78 |
December | 0.366403E+10 | 25213.08 | 26-DEC-08:13 | -1.1 |
Annual Sum or Average | 0.173387E+11 | |||
Minimum of Months | 76605716.20 | 1246.28 | -2.9 | |
Maximum of Months | 0.440741E+10 | 25364.18 | 27.85 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.513289E+10 | 3195.13 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.463968E+10 | 3195.13 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.513777E+10 | 3195.13 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.497275E+10 | 3195.13 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.513289E+10 | 3195.13 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.497331E+10 | 3195.13 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.513715E+10 | 3195.13 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.513317E+10 | 3195.13 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.497729E+10 | 3195.13 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.513289E+10 | 3195.13 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.495844E+10 | 3195.13 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.514197E+10 | 3195.13 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.604702E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.463968E+10 | 3195.13 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.514197E+10 | 3195.13 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.315740E+10 | 1970.29 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.285401E+10 | 1970.29 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.316044E+10 | 1970.29 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.305887E+10 | 1970.29 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.315740E+10 | 1970.29 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.305927E+10 | 1970.29 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.316000E+10 | 1970.29 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.315760E+10 | 1970.29 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.306167E+10 | 1970.29 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.315740E+10 | 1970.29 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.305007E+10 | 1970.29 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.316300E+10 | 1970.29 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.371971E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.285401E+10 | 1970.29 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.316300E+10 | 1970.29 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.228368E+10 | 1829.00 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.206850E+10 | 1829.00 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.233527E+10 | 1829.00 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.221625E+10 | 1829.00 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.230947E+10 | 1829.00 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.225495E+10 | 1829.00 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.227078E+10 | 1829.00 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.233527E+10 | 1829.00 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.221625E+10 | 1829.00 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.228368E+10 | 1829.00 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.221625E+10 | 1829.00 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.227078E+10 | 1829.00 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.270611E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.206850E+10 | 1829.00 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.233527E+10 | 1829.00 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.228368E+10 | 1829.00 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.206850E+10 | 1829.00 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.233527E+10 | 1829.00 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.221625E+10 | 1829.00 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.230947E+10 | 1829.00 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.225495E+10 | 1829.00 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.227078E+10 | 1829.00 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.233527E+10 | 1829.00 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.221625E+10 | 1829.00 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.228368E+10 | 1829.00 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.221625E+10 | 1829.00 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.227078E+10 | 1829.00 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.270611E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.206850E+10 | 1829.00 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.233527E+10 | 1829.00 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.228368E+10 | 1829.00 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.206850E+10 | 1829.00 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.233527E+10 | 1829.00 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.221625E+10 | 1829.00 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.230947E+10 | 1829.00 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.225495E+10 | 1829.00 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.227078E+10 | 1829.00 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.233527E+10 | 1829.00 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.221625E+10 | 1829.00 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.228368E+10 | 1829.00 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.221625E+10 | 1829.00 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.227078E+10 | 1829.00 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.270611E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.206850E+10 | 1829.00 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.233527E+10 | 1829.00 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.215471E+10 | 1843.80 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.195194E+10 | 1843.80 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.220565E+10 | 1843.80 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.209137E+10 | 1843.80 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.218018E+10 | 1843.80 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.212957E+10 | 1843.80 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.214197E+10 | 1843.80 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.220565E+10 | 1843.80 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.209137E+10 | 1843.80 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.215471E+10 | 1843.80 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.209137E+10 | 1843.80 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.214197E+10 | 1843.80 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.255405E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.195194E+10 | 1843.80 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.220565E+10 | 1843.80 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.109533E+10 | 938.10 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.992258E+09 | 938.10 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.112127E+10 | 938.10 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.106313E+10 | 938.10 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.110830E+10 | 938.10 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.108259E+10 | 938.10 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.108884E+10 | 938.10 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.112127E+10 | 938.10 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.106313E+10 | 938.10 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.109533E+10 | 938.10 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.106313E+10 | 938.10 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.108884E+10 | 938.10 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.129834E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.992258E+09 | 938.10 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.112127E+10 | 938.10 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.109533E+10 | 938.10 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.992258E+09 | 938.10 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.112127E+10 | 938.10 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.106313E+10 | 938.10 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.110830E+10 | 938.10 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.108259E+10 | 938.10 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.108884E+10 | 938.10 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.112127E+10 | 938.10 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.106313E+10 | 938.10 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.109533E+10 | 938.10 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.106313E+10 | 938.10 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.108884E+10 | 938.10 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.129834E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.992258E+09 | 938.10 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.112127E+10 | 938.10 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.109533E+10 | 938.10 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.992258E+09 | 938.10 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.112127E+10 | 938.10 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.106313E+10 | 938.10 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.110830E+10 | 938.10 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.108259E+10 | 938.10 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.108884E+10 | 938.10 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.112127E+10 | 938.10 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.106313E+10 | 938.10 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.109533E+10 | 938.10 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.106313E+10 | 938.10 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.108884E+10 | 938.10 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.129834E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.992258E+09 | 938.10 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.112127E+10 | 938.10 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.109533E+10 | 938.10 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.992258E+09 | 938.10 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.112127E+10 | 938.10 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.106313E+10 | 938.10 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.110830E+10 | 938.10 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.108259E+10 | 938.10 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.108884E+10 | 938.10 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.112127E+10 | 938.10 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.106313E+10 | 938.10 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.109533E+10 | 938.10 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.106313E+10 | 938.10 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.108884E+10 | 938.10 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.129834E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.992258E+09 | 938.10 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.112127E+10 | 938.10 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.513289E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448597E+10 |
February | 0.305697E+10 | 0.463968E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356768E+10 |
March | 0.335708E+10 | 0.513777E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318875E+10 |
April | 0.327081E+10 | 0.497275E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24394465.01 | 0.247006E+10 |
May | 0.336680E+10 | 0.513289E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2651590.32 | 0.212378E+10 |
June | 0.325380E+10 | 0.497331E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13745535.51 | 0.162601E+10 |
July | 0.339353E+10 | 0.513715E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130177E+09 | 0.112618E+10 |
August | 0.334857E+10 | 0.513317E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278918E+09 | 0.929315E+09 |
September | 0.327932E+10 | 0.497729E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3240272.85 | 0.153259E+10 |
October | 0.338624E+10 | 0.513289E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255991E+10 |
November | 0.327446E+10 | 0.495844E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348023E+10 |
December | 0.340325E+10 | 0.514197E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409784E+10 |
Annual Sum or Average | 0.397770E+11 | 0.604702E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453127E+09 | 0.311883E+11 |
Minimum of Months | 0.305697E+10 | 0.463968E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929315E+09 |
Maximum of Months | 0.340325E+10 | 0.514197E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278918E+09 | 0.448597E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.315740E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225531E+10 |
February | 0.152844E+10 | 0.285401E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179842E+10 |
March | 0.167849E+10 | 0.316044E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162802E+10 |
April | 0.163536E+10 | 0.305887E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13250422.38 | 0.128793E+10 |
May | 0.168335E+10 | 0.315740E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1457539.56 | 0.111937E+10 |
June | 0.162685E+10 | 0.305927E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7466548.10 | 0.787876E+09 |
July | 0.169671E+10 | 0.316000E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70594588.02 | 0.518087E+09 |
August | 0.167424E+10 | 0.315760E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151707E+09 | 0.416705E+09 |
September | 0.163961E+10 | 0.306167E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1785657.25 | 0.812772E+09 |
October | 0.169307E+10 | 0.315740E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135763E+10 |
November | 0.163718E+10 | 0.305007E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177611E+10 |
December | 0.170157E+10 | 0.316300E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208621E+10 |
Annual Sum or Average | 0.198880E+11 | 0.371971E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246262E+09 | 0.158444E+11 |
Minimum of Months | 0.152844E+10 | 0.285401E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416705E+09 |
Maximum of Months | 0.170157E+10 | 0.316300E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151707E+09 | 0.225531E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.228368E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231360E+10 |
February | 0.914877E+09 | 0.206850E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184571E+10 |
March | 0.103395E+10 | 0.233527E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166802E+10 |
April | 0.984131E+09 | 0.221625E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13130435.27 | 0.133377E+10 |
May | 0.102058E+10 | 0.230947E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455996.52 | 0.116807E+10 |
June | 0.998711E+09 | 0.225495E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466409.04 | 0.824944E+09 |
July | 0.100600E+10 | 0.227078E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67467234.33 | 0.553315E+09 |
August | 0.103395E+10 | 0.233527E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149824E+09 | 0.446281E+09 |
September | 0.984131E+09 | 0.221625E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785480.34 | 0.839450E+09 |
October | 0.100722E+10 | 0.228368E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139730E+10 |
November | 0.973196E+09 | 0.221625E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181093E+10 |
December | 0.100600E+10 | 0.227078E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213651E+10 |
Annual Sum or Average | 0.119700E+11 | 0.270611E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241130E+09 | 0.163379E+11 |
Minimum of Months | 0.914877E+09 | 0.206850E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446281E+09 |
Maximum of Months | 0.103395E+10 | 0.233527E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149824E+09 | 0.231360E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.228368E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230927E+10 |
February | 0.914877E+09 | 0.206850E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183945E+10 |
March | 0.103395E+10 | 0.233527E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165556E+10 |
April | 0.984131E+09 | 0.221625E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13142121.95 | 0.131711E+10 |
May | 0.102058E+10 | 0.230947E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455996.29 | 0.116163E+10 |
June | 0.998711E+09 | 0.225495E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466409.68 | 0.823709E+09 |
July | 0.100600E+10 | 0.227078E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67466232.82 | 0.552939E+09 |
August | 0.103395E+10 | 0.233527E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149818E+09 | 0.446158E+09 |
September | 0.984131E+09 | 0.221625E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785482.21 | 0.837774E+09 |
October | 0.100722E+10 | 0.228368E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138005E+10 |
November | 0.973196E+09 | 0.221625E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180111E+10 |
December | 0.100600E+10 | 0.227078E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213260E+10 |
Annual Sum or Average | 0.119700E+11 | 0.270611E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241134E+09 | 0.162574E+11 |
Minimum of Months | 0.914877E+09 | 0.206850E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446158E+09 |
Maximum of Months | 0.103395E+10 | 0.233527E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149818E+09 | 0.230927E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.228368E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230517E+10 |
February | 0.914877E+09 | 0.206850E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183140E+10 |
March | 0.103395E+10 | 0.233527E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163590E+10 |
April | 0.984131E+09 | 0.221625E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13168558.47 | 0.128510E+10 |
May | 0.102058E+10 | 0.230947E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455978.11 | 0.113800E+10 |
June | 0.998711E+09 | 0.225495E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466407.86 | 0.817786E+09 |
July | 0.100600E+10 | 0.227078E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67528769.96 | 0.550448E+09 |
August | 0.103395E+10 | 0.233527E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149856E+09 | 0.443923E+09 |
September | 0.984131E+09 | 0.221625E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785451.92 | 0.830062E+09 |
October | 0.100722E+10 | 0.228368E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134464E+10 |
November | 0.973196E+09 | 0.221625E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178584E+10 |
December | 0.100600E+10 | 0.227078E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212850E+10 |
Annual Sum or Average | 0.119700E+11 | 0.270611E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241261E+09 | 0.160968E+11 |
Minimum of Months | 0.914877E+09 | 0.206850E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443923E+09 |
Maximum of Months | 0.103395E+10 | 0.233527E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149856E+09 | 0.230517E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.215471E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421456E+10 |
February | 0.313522E+10 | 0.195194E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333236E+10 |
March | 0.355148E+10 | 0.220565E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294588E+10 |
April | 0.338259E+10 | 0.209137E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23908098.89 | 0.223751E+10 |
May | 0.349753E+10 | 0.218018E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2614353.06 | 0.192131E+10 |
June | 0.343071E+10 | 0.212957E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13429521.53 | 0.146376E+10 |
July | 0.344942E+10 | 0.214197E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122382E+09 | 0.101490E+10 |
August | 0.355148E+10 | 0.220565E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270080E+09 | 0.824781E+09 |
September | 0.338259E+10 | 0.209137E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3204899.40 | 0.143224E+10 |
October | 0.344359E+10 | 0.215471E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232429E+10 |
November | 0.331698E+10 | 0.209137E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322701E+10 |
December | 0.344942E+10 | 0.214197E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388222E+10 |
Annual Sum or Average | 0.410346E+11 | 0.255405E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435619E+09 | 0.288208E+11 |
Minimum of Months | 0.313522E+10 | 0.195194E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824781E+09 |
Maximum of Months | 0.355148E+10 | 0.220565E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270080E+09 | 0.421456E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.109533E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231158E+10 |
February | 0.156756E+10 | 0.992258E+09 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182840E+10 |
March | 0.177569E+10 | 0.112127E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161690E+10 |
April | 0.169125E+10 | 0.106313E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13252255.56 | 0.123746E+10 |
May | 0.174872E+10 | 0.110830E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455931.11 | 0.107882E+10 |
June | 0.171530E+10 | 0.108259E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466475.21 | 0.808090E+09 |
July | 0.172466E+10 | 0.108884E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67797867.24 | 0.550894E+09 |
August | 0.177569E+10 | 0.112127E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150048E+09 | 0.445329E+09 |
September | 0.169125E+10 | 0.106313E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785479.70 | 0.807370E+09 |
October | 0.172174E+10 | 0.109533E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129254E+10 |
November | 0.165844E+10 | 0.106313E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177271E+10 |
December | 0.172466E+10 | 0.108884E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213273E+10 |
Annual Sum or Average | 0.205167E+11 | 0.129834E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241806E+09 | 0.158828E+11 |
Minimum of Months | 0.156756E+10 | 0.992258E+09 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445329E+09 |
Maximum of Months | 0.177569E+10 | 0.112127E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150048E+09 | 0.231158E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.109533E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231065E+10 |
February | 0.156756E+10 | 0.992258E+09 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182700E+10 |
March | 0.177569E+10 | 0.112127E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161433E+10 |
April | 0.169125E+10 | 0.106313E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13260018.22 | 0.123265E+10 |
May | 0.174872E+10 | 0.110830E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455930.00 | 0.107086E+10 |
June | 0.171530E+10 | 0.108259E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466482.22 | 0.805180E+09 |
July | 0.172466E+10 | 0.108884E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67827238.10 | 0.549804E+09 |
August | 0.177569E+10 | 0.112127E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150062E+09 | 0.444565E+09 |
September | 0.169125E+10 | 0.106313E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785484.40 | 0.804581E+09 |
October | 0.172174E+10 | 0.109533E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128765E+10 |
November | 0.165844E+10 | 0.106313E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177106E+10 |
December | 0.172466E+10 | 0.108884E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213195E+10 |
Annual Sum or Average | 0.205167E+11 | 0.129834E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241858E+09 | 0.158503E+11 |
Minimum of Months | 0.156756E+10 | 0.992258E+09 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444565E+09 |
Maximum of Months | 0.177569E+10 | 0.112127E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150062E+09 | 0.231065E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.109533E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230543E+10 |
February | 0.156756E+10 | 0.992258E+09 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182080E+10 |
March | 0.177569E+10 | 0.112127E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160524E+10 |
April | 0.169125E+10 | 0.106313E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13289810.90 | 0.121548E+10 |
May | 0.174872E+10 | 0.110830E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455913.35 | 0.104054E+10 |
June | 0.171530E+10 | 0.108259E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466480.00 | 0.792009E+09 |
July | 0.172466E+10 | 0.108884E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67914865.77 | 0.545060E+09 |
August | 0.177569E+10 | 0.112127E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150097E+09 | 0.441327E+09 |
September | 0.169125E+10 | 0.106313E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785470.71 | 0.790438E+09 |
October | 0.172174E+10 | 0.109533E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126878E+10 |
November | 0.165844E+10 | 0.106313E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176443E+10 |
December | 0.172466E+10 | 0.108884E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212769E+10 |
Annual Sum or Average | 0.205167E+11 | 0.129834E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242010E+09 | 0.157172E+11 |
Minimum of Months | 0.156756E+10 | 0.992258E+09 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441327E+09 |
Maximum of Months | 0.177569E+10 | 0.112127E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150097E+09 | 0.230543E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.109533E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276236E+10 |
February | 0.156756E+10 | 0.992258E+09 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220514E+10 |
March | 0.177569E+10 | 0.112127E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197473E+10 |
April | 0.169125E+10 | 0.106313E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14027089.70 | 0.154121E+10 |
May | 0.174872E+10 | 0.110830E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1492844.34 | 0.128915E+10 |
June | 0.171530E+10 | 0.108259E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7781980.45 | 0.102465E+10 |
July | 0.172466E+10 | 0.108884E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70956368.97 | 0.744106E+09 |
August | 0.177569E+10 | 0.112127E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156124E+09 | 0.624569E+09 |
September | 0.169125E+10 | 0.106313E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1820384.42 | 0.908277E+09 |
October | 0.172174E+10 | 0.109533E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156101E+10 |
November | 0.165844E+10 | 0.106313E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211671E+10 |
December | 0.172466E+10 | 0.108884E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250972E+10 |
Annual Sum or Average | 0.205167E+11 | 0.129834E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252203E+09 | 0.192616E+11 |
Minimum of Months | 0.156756E+10 | 0.992258E+09 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624569E+09 |
Maximum of Months | 0.177569E+10 | 0.112127E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156124E+09 | 0.276236E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 3195.13 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6851.57 | 07-JAN-12:10 |
February | 4050.04 | 03-FEB-13:09 | 3195.13 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 7078.81 | 18-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 3195.13 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5122.21 | 22-MAR-11:10 |
April | 4050.04 | 01-APR-12:09 | 3195.13 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.74 | 01-APR-16:00 | 4438.64 | 18-APR-17:00 |
May | 4050.04 | 05-MAY-12:09 | 3195.13 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.48 | 05-MAY-16:00 | 4021.47 | 23-MAY-17:00 |
June | 4050.04 | 02-JUN-12:09 | 3195.13 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 818.13 | 28-JUN-17:00 | 3604.98 | 13-JUN-11:10 |
July | 4050.04 | 01-JUL-12:09 | 3195.13 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1924.14 | 24-JUL-15:00 | 2990.24 | 09-JUL-13:00 |
August | 4050.04 | 04-AUG-12:09 | 3195.13 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2236.40 | 10-AUG-17:00 | 3125.29 | 01-AUG-11:10 |
September | 4050.04 | 01-SEP-12:09 | 3195.13 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 323.74 | 14-SEP-17:00 | 3446.10 | 16-SEP-11:10 |
October | 4050.04 | 01-OCT-12:09 | 3195.13 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3842.84 | 31-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 3195.13 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5652.45 | 12-NOV-17:00 |
December | 4050.04 | 01-DEC-13:09 | 3195.13 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6746.90 | 26-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 3195.13 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2990.24 | |||||
Maximum of Months | 4050.04 | 3195.13 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2236.40 | 7078.81 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 1970.29 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 03-FEB-13:09 | 1970.29 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 1970.29 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 1970.29 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 05-MAY-12:09 | 1970.29 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 05-MAY-16:00 | 2407.97 | 23-MAY-17:00 |
June | 2024.96 | 02-JUN-12:09 | 1970.29 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2114.43 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 1970.29 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.66 | 24-JUL-15:00 | 1677.42 | 09-JUL-13:00 |
August | 2024.96 | 04-AUG-12:09 | 1970.29 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1737.80 | 01-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 1970.29 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 2012.31 | 16-SEP-11:10 |
October | 2024.96 | 01-OCT-12:09 | 1970.29 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2087.57 | 29-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 1970.29 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 01-DEC-13:09 | 1970.29 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1970.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.42 | |||||
Maximum of Months | 2024.96 | 1970.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1829.00 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 1829.00 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1829.00 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 1829.00 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 1829.00 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 05-MAY-16:00 | 2427.38 | 23-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 1829.00 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2122.94 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 1829.00 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.66 | 24-JUL-15:00 | 1677.44 | 09-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 1829.00 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1742.22 | 01-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 1829.00 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 2020.17 | 16-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 1829.00 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2101.49 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 1829.00 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 1829.00 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.44 | |||||
Maximum of Months | 2024.96 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1829.00 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 1829.00 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1829.00 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 1829.00 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 1829.00 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 05-MAY-16:00 | 2410.88 | 23-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 1829.00 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2122.15 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 1829.00 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.66 | 24-JUL-15:00 | 1677.44 | 09-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 1829.00 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1742.22 | 01-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 1829.00 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 2020.15 | 16-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 1829.00 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2074.86 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 1829.00 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 1829.00 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.44 | |||||
Maximum of Months | 2024.96 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 1829.00 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 1829.00 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 1829.00 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 1829.00 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.03 | 18-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 1829.00 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 05-MAY-16:00 | 2353.01 | 23-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 1829.00 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2113.98 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 1829.00 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.66 | 24-JUL-15:00 | 1677.44 | 09-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 1829.00 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1741.34 | 01-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 1829.00 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.79 | 14-SEP-17:00 | 2014.16 | 16-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 1829.00 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 1829.00 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 1829.00 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.44 | |||||
Maximum of Months | 2024.96 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 1843.80 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6800.61 | 07-JAN-12:10 |
February | 5400.05 | 04-FEB-15:09 | 1843.80 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6907.61 | 18-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 1843.80 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5000.04 | 22-MAR-11:10 |
April | 5400.05 | 01-APR-14:09 | 1843.80 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 966.74 | 01-APR-16:00 | 4340.23 | 18-APR-17:00 |
May | 5400.05 | 06-MAY-14:09 | 1843.80 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 317.80 | 05-MAY-16:00 | 3925.90 | 23-MAY-17:00 |
June | 5400.05 | 03-JUN-14:09 | 1843.80 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 807.08 | 28-JUN-17:00 | 3490.92 | 13-JUN-11:10 |
July | 5400.05 | 01-JUL-14:09 | 1843.80 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1898.11 | 24-JUL-15:00 | 2876.79 | 09-JUL-13:00 |
August | 5400.05 | 05-AUG-14:09 | 1843.80 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2211.08 | 10-AUG-17:00 | 3052.44 | 01-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 1843.80 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 319.35 | 14-SEP-17:00 | 3399.58 | 16-SEP-11:10 |
October | 5400.05 | 07-OCT-14:09 | 1843.80 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3682.21 | 31-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 1843.80 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5588.12 | 12-NOV-17:00 |
December | 5400.05 | 02-DEC-15:09 | 1843.80 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6644.20 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 1843.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2876.79 | |||||
Maximum of Months | 5400.05 | 1843.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2211.08 | 6907.61 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 938.10 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3788.98 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 938.10 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 938.10 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 938.10 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 938.10 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.99 | 05-MAY-16:00 | 2196.16 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 938.10 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.29 | 28-JUN-17:00 | 2007.29 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 938.10 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 24-JUL-15:00 | 1652.42 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 938.10 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1718.29 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 938.10 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 1958.97 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 938.10 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 938.10 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 938.10 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1652.42 | |||||
Maximum of Months | 2699.95 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 938.10 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3788.98 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 938.10 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 938.10 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 938.10 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 938.10 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.99 | 05-MAY-16:00 | 2186.80 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 938.10 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.29 | 28-JUN-17:00 | 1998.34 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 938.10 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 24-JUL-15:00 | 1645.82 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 938.10 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1716.73 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 938.10 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 1953.44 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 938.10 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 938.10 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 938.10 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1645.82 | |||||
Maximum of Months | 2699.95 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 938.10 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3788.98 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 938.10 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 938.10 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 938.10 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 938.10 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.99 | 05-MAY-16:00 | 2184.16 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 938.10 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.29 | 28-JUN-17:00 | 1956.21 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 938.10 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 24-JUL-15:00 | 1620.08 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 938.10 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1711.31 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 938.10 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 1928.12 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 938.10 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 938.10 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 938.10 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1620.08 | |||||
Maximum of Months | 2699.95 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 938.10 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3839.94 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 938.10 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4010.60 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 938.10 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2901.44 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 938.10 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 566.87 | 01-APR-16:00 | 2511.52 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 938.10 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.65 | 05-MAY-16:00 | 2254.79 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 938.10 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 460.34 | 28-JUN-17:00 | 1946.85 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 938.10 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.65 | 24-JUL-15:00 | 1597.57 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 938.10 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.76 | 10-AUG-17:00 | 1770.28 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 938.10 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.16 | 14-SEP-17:00 | 1896.12 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 938.10 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2201.94 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 938.10 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3176.04 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 938.10 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3817.59 | 26-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1597.57 | |||||
Maximum of Months | 2699.95 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.76 | 4010.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5688.33 | 14-JAN-22:03 | 6075.06 | 9585.39 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.87 |
February | 4881.47 | 18-FEB-00:12 | 1350.01 | 6726.61 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.92 |
March | 4093.92 | 01-MAR-18:30 | 3375.03 | 3195.13 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.80 |
April | 6652.70 | 27-APR-16:10 | 3375.03 | 3195.13 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 911.81 | 0.00 |
May | 6862.02 | 15-MAY-16:40 | 3375.03 | 3195.13 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 98.66 | 0.00 |
June | 8420.58 | 28-JUN-17:00 | 3375.03 | 3195.13 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 818.13 | 0.00 |
July | 10006.41 | 31-JUL-16:10 | 3375.03 | 3195.13 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1441.36 | 0.00 |
August | 11388.09 | 10-AUG-17:00 | 3375.03 | 3195.13 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2236.40 | 0.00 |
September | 8236.18 | 14-SEP-16:20 | 3375.03 | 3195.13 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 205.62 | 0.00 |
October | 5822.98 | 04-OCT-17:10 | 3375.03 | 3195.13 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.19 |
November | 3646.43 | 08-NOV-18:10 | 3375.03 | 3195.13 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 635.70 |
December | 5173.68 | 25-DEC-22:25 | 2700.03 | 6390.26 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3646.43 | 1350.01 | 3195.13 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11388.09 | 6075.06 | 9585.39 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 2236.40 | 635.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1670.47 | 20-JAN-13:25 | 4049.92 | 3940.57 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2429.87 |
February | 1731.37 | 07-FEB-18:10 | 1687.47 | 1970.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.10 |
March | 1962.14 | 01-MAR-20:00 | 1687.47 | 1970.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.38 |
April | 15525.27 | 01-APR-21:02 | 10124.81 | 19702.87 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.41 |
May | 15524.34 | 14-MAY-18:29 | 10799.79 | 15762.29 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.88 |
June | 16409.15 | 09-JUN-20:08 | 9112.33 | 17732.58 | 6044.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.44 |
July | 16677.82 | 07-JUL-21:15 | 8099.84 | 15762.29 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 |
August | 15622.38 | 14-AUG-21:16 | 7087.36 | 13792.01 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.85 |
September | 15630.10 | 10-SEP-19:54 | 9449.82 | 13792.01 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.05 |
October | 3374.63 | 04-OCT-14:00 | 1349.97 | 1970.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.74 |
November | 2018.22 | 10-NOV-19:00 | 1687.47 | 1970.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.89 |
December | 1756.44 | 04-DEC-18:10 | 1687.47 | 1970.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1670.47 | 1349.97 | 1970.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 | |
Maximum of Months | 16677.82 | 10799.79 | 19702.87 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2429.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1294.85 | 12-JAN-18:10 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.81 |
February | 1553.85 | 08-FEB-18:10 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.09 |
March | 1699.62 | 22-MAR-17:20 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.40 |
April | 3863.30 | 27-APR-16:10 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 498.94 | 0.00 |
May | 3788.84 | 06-MAY-13:00 | 2024.96 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 | 0.00 |
June | 4374.40 | 28-JUN-16:20 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 387.72 | 0.00 |
July | 5275.76 | 24-JUL-14:00 | 1012.48 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 877.76 | 0.00 |
August | 7797.97 | 10-AUG-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 |
September | 4307.08 | 14-SEP-16:10 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 96.97 | 0.00 |
October | 3161.19 | 04-OCT-14:00 | 1012.48 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.74 |
November | 1905.84 | 10-NOV-18:50 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.94 |
December | 1496.25 | 05-DEC-18:10 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1294.85 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7797.97 | 2024.96 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 877.76 | 455.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1446.13 | 18-JAN-19:05 | 1349.97 | 3657.99 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.32 |
February | 1465.79 | 08-FEB-18:10 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.09 |
March | 1665.92 | 22-MAR-17:20 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.19 |
April | 3733.44 | 27-APR-16:10 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 498.94 | 0.00 |
May | 3753.80 | 06-MAY-13:00 | 2024.96 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 | 0.00 |
June | 4358.85 | 28-JUN-16:20 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 387.72 | 0.00 |
July | 5284.35 | 24-JUL-14:00 | 1012.48 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 877.76 | 0.00 |
August | 8050.22 | 10-AUG-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.34 |
September | 4295.53 | 14-SEP-16:10 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 96.97 | 0.00 |
October | 3083.81 | 04-OCT-14:00 | 1012.48 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.74 |
November | 1844.83 | 10-NOV-18:10 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.13 |
December | 1374.63 | 05-DEC-18:10 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1374.63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8050.22 | 2024.96 | 3657.99 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 877.76 | 455.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1591.40 | 19-JAN-19:45 | 1349.97 | 3657.99 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.13 |
February | 1528.21 | 16-FEB-19:05 | 1349.97 | 3657.99 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.92 |
March | 1604.42 | 01-MAR-19:00 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.94 |
April | 3403.41 | 27-APR-16:10 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 498.93 | 0.00 |
May | 3551.00 | 06-MAY-13:00 | 2024.96 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 | 0.00 |
June | 4222.23 | 28-JUN-16:20 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 387.72 | 0.00 |
July | 5160.35 | 24-JUL-14:00 | 1012.48 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 877.76 | 0.00 |
August | 6835.58 | 10-AUG-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.31 |
September | 4166.05 | 14-SEP-16:10 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 96.97 | 0.00 |
October | 2858.85 | 04-OCT-17:10 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.33 |
November | 1578.79 | 10-NOV-18:10 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.14 |
December | 1181.84 | 05-DEC-18:10 | 1687.47 | 1829.00 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1181.84 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6835.58 | 2024.96 | 3657.99 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 877.76 | 526.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4348.69 | 31-JAN-18:45 | 4590.04 | 3687.60 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 747.26 |
February | 4410.77 | 06-FEB-19:05 | 3510.03 | 3687.60 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 811.22 |
March | 3527.38 | 16-MAR-14:35 | 9315.09 | 3687.60 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3237.28 |
April | 5825.69 | 27-APR-15:00 | 4657.54 | 1843.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 950.37 | 0.00 |
May | 6186.93 | 06-MAY-14:10 | 5400.05 | 1843.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 | 0.00 |
June | 7699.11 | 28-JUN-15:00 | 4657.54 | 1843.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 641.04 | 0.00 |
July | 10033.87 | 24-JUL-15:00 | 4657.54 | 1843.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1898.11 | 0.00 |
August | 10363.42 | 10-AUG-15:00 | 4657.54 | 1843.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1780.05 | 0.00 |
September | 7719.63 | 14-SEP-14:30 | 4657.54 | 1843.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 0.00 |
October | 5032.28 | 04-OCT-15:00 | 4657.54 | 1843.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 646.25 |
November | 2789.64 | 07-NOV-11:40 | 2902.53 | 1843.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.80 |
December | 4368.24 | 13-DEC-18:55 | 4590.04 | 3687.60 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 687.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2789.64 | 2902.53 | 1843.80 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10363.42 | 9315.09 | 3687.60 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1898.11 | 3237.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 719.98 | 11-JAN-17:40 | 2396.20 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1415.11 |
February | 1650.81 | 09-FEB-19:05 | 1754.97 | 1876.20 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.40 |
March | 1405.79 | 01-MAR-12:00 | 1451.22 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.09 |
April | 3008.95 | 27-APR-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 0.00 |
May | 3145.29 | 06-MAY-14:10 | 2699.95 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
June | 3953.24 | 28-JUN-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 356.54 | 0.00 |
July | 5233.43 | 24-JUL-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 0.00 |
August | 5383.21 | 10-AUG-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 991.02 | 0.00 |
September | 3949.36 | 14-SEP-14:30 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
October | 2613.16 | 04-OCT-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.31 |
November | 1424.24 | 10-NOV-15:45 | 4657.41 | 1876.20 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2020.24 |
December | 1401.75 | 04-DEC-19:25 | 1754.97 | 1876.20 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 719.98 | 1451.22 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5383.21 | 4657.41 | 1876.20 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 2020.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1153.87 | 25-JAN-18:50 | 1147.48 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.26 |
February | 1029.80 | 01-FEB-13:30 | 2396.20 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1689.69 |
March | 1595.48 | 24-MAR-12:55 | 4792.41 | 1876.20 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2186.46 |
April | 2937.12 | 27-APR-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 0.00 |
May | 3073.43 | 06-MAY-14:10 | 2699.95 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
June | 3896.37 | 28-JUN-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 356.54 | 0.00 |
July | 5181.80 | 24-JUL-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 0.00 |
August | 5337.57 | 10-AUG-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 991.02 | 0.00 |
September | 3902.37 | 14-SEP-14:30 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
October | 2533.28 | 04-OCT-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.31 |
November | 2059.43 | 13-NOV-11:05 | 2902.44 | 1876.20 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.42 |
December | 1591.97 | 07-DEC-18:15 | 2294.96 | 1876.20 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1029.80 | 1147.48 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5337.57 | 4792.41 | 1876.20 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 2186.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2244.59 | 14-JAN-11:45 | 3914.92 | 1876.20 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.34 |
February | 1914.19 | 09-FEB-18:05 | 2294.96 | 1876.20 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.39 |
March | 1263.47 | 27-MAR-10:10 | 1451.22 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.64 |
April | 2735.87 | 27-APR-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 0.00 |
May | 2871.77 | 06-MAY-14:10 | 2699.95 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
June | 3747.83 | 28-JUN-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 356.54 | 0.00 |
July | 5081.14 | 24-JUL-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 0.00 |
August | 5271.88 | 10-AUG-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 991.02 | 0.00 |
September | 3799.87 | 14-SEP-14:30 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
October | 2282.51 | 04-OCT-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.31 |
November | 1733.73 | 28-NOV-11:15 | 2902.44 | 1876.20 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.95 |
December | 1445.66 | 01-DEC-18:55 | 2294.96 | 1876.20 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1263.47 | 1451.22 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5271.88 | 3914.92 | 1876.20 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 476.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 720.27 |
February | 820.64 | 03-FEB-11:20 | 1451.22 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.17 |
March | 986.39 | 24-MAR-17:40 | 1147.48 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.04 |
April | 2674.48 | 27-APR-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 545.86 | 0.00 |
May | 2787.67 | 06-MAY-13:40 | 2598.70 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
June | 3710.64 | 28-JUN-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 369.44 | 0.00 |
July | 5326.01 | 24-JUL-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.65 | 0.00 |
August | 5562.40 | 10-AUG-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1015.38 | 0.00 |
September | 3868.09 | 14-SEP-14:10 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
October | 1980.87 | 04-OCT-15:00 | 2328.71 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.96 |
November | 781.31 | 06-NOV-17:50 | 2396.20 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1547.20 |
December | 517.67 | 02-DEC-12:00 | 1957.46 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5562.40 | 2598.70 | 938.10 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.65 | 1547.20 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.565202E+11 | 47762.52 | 08-JAN-16:30 | 0.612712E+11 | 114340.00 | 16-JAN-09:09 |
February | 0.505634E+11 | 49084.28 | 08-FEB-17:30 | 0.410828E+11 | 113524.99 | 19-FEB-09:09 |
March | 0.557812E+11 | 45036.91 | 24-MAR-18:49 | 0.209599E+11 | 77818.00 | 25-MAR-07:10 |
April | 0.531513E+11 | 52243.55 | 27-APR-16:00 | 0.712607E+10 | 61543.38 | 19-APR-07:10 |
May | 0.552940E+11 | 51211.69 | 05-MAY-13:00 | 0.594997E+09 | 20026.04 | 29-MAY-08:09 |
June | 0.547071E+11 | 52157.30 | 28-JUN-14:00 | 6211338.99 | 3369.05 | 15-JUN-07:10 |
July | 0.592498E+11 | 57772.78 | 24-JUL-14:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.629633E+11 | 60563.28 | 10-AUG-16:49 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.551945E+11 | 54245.49 | 12-SEP-14:09 | 16557684.30 | 5075.23 | 28-SEP-07:10 |
October | 0.553528E+11 | 45030.97 | 28-OCT-16:00 | 0.444882E+10 | 37777.92 | 30-OCT-07:10 |
November | 0.543378E+11 | 47390.62 | 24-NOV-17:30 | 0.300335E+11 | 79956.16 | 24-NOV-08:09 |
December | 0.564357E+11 | 49538.50 | 23-DEC-16:30 | 0.516068E+11 | 113663.36 | 26-DEC-08:09 |
Annual Sum or Average | 0.669551E+12 | 0.217147E+12 | ||||
Minimum of Months | 0.505634E+11 | 45030.97 | 0.00 | 0.00 | ||
Maximum of Months | 0.629633E+11 | 60563.28 | 0.612712E+11 | 114340.00 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.126222E+10 | 4141.79 | 30-JAN-11:30 | 0.00 | 0.00 |
February | 0.205266E+10 | 5886.20 | 27-FEB-12:30 | 0.00 | 0.00 |
March | 0.359256E+10 | 8289.92 | 24-MAR-12:30 | 0.00 | 0.00 |
April | 0.531067E+10 | 9727.97 | 25-APR-12:09 | 0.00 | 0.00 |
May | 0.686300E+10 | 11250.00 | 10-MAY-11:30 | 0.00 | 0.00 |
June | 0.711765E+10 | 10459.28 | 19-JUN-12:09 | 0.00 | 0.00 |
July | 0.757024E+10 | 10545.60 | 05-JUL-10:30 | 0.00 | 0.00 |
August | 0.613978E+10 | 9526.41 | 06-AUG-12:30 | 0.00 | 0.00 |
September | 0.436894E+10 | 8327.32 | 07-SEP-12:30 | 0.00 | 0.00 |
October | 0.281747E+10 | 7093.63 | 03-OCT-11:00 | 0.00 | 0.00 |
November | 0.139387E+10 | 4318.14 | 11-NOV-12:20 | 0.00 | 0.00 |
December | 0.108025E+10 | 3446.48 | 01-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.495693E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.108025E+10 | 3446.48 | 0.00 | 0.00 | |
Maximum of Months | 0.757024E+10 | 11250.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.216773E+11 | 0.487911E+10 | 0.108325E+11 | 0.00 | 0.135590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557231E+10 | 0.00 |
February | 0.196202E+11 | 0.389808E+10 | 0.980803E+10 | 0.00 | 0.121861E+11 | 0.00 | 0.00 | 13337.03 | 0.00 | 0.00 | 0.00 | 0.505097E+10 | 0.00 |
March | 0.219947E+11 | 0.361815E+10 | 0.110075E+11 | 0.00 | 0.135588E+11 | 0.00 | 0.00 | 58037.67 | 0.00 | 0.00 | 0.00 | 0.560198E+10 | 0.00 |
April | 0.210243E+11 | 0.280114E+10 | 0.105079E+11 | 0.00 | 0.129119E+11 | 0.00 | 0.00 | 0.573570E+09 | 0.00 | 0.00 | 0.00 | 0.533256E+10 | 0.00 |
May | 0.218321E+11 | 0.237022E+10 | 0.109147E+11 | 0.00 | 0.135911E+11 | 0.00 | 0.00 | 0.114725E+10 | 0.00 | 0.00 | 0.00 | 0.543864E+10 | 0.00 |
June | 0.212573E+11 | 0.203720E+10 | 0.106386E+11 | 0.00 | 0.132979E+11 | 0.00 | 0.00 | 0.226305E+10 | 0.00 | 0.00 | 0.00 | 0.521300E+10 | 0.00 |
July | 0.216068E+11 | 0.219357E+10 | 0.107945E+11 | 0.00 | 0.134475E+11 | 0.00 | 0.00 | 0.590475E+10 | 0.00 | 0.00 | 0.00 | 0.530256E+10 | 0.00 |
August | 0.219873E+11 | 0.262279E+10 | 0.110006E+11 | 0.00 | 0.136888E+11 | 0.00 | 0.00 | 0.832920E+10 | 0.00 | 0.00 | 0.00 | 0.533457E+10 | 0.00 |
September | 0.210316E+11 | 0.319647E+10 | 0.105148E+11 | 0.00 | 0.131269E+11 | 0.00 | 0.00 | 0.216562E+10 | 0.00 | 0.00 | 0.00 | 0.515912E+10 | 0.00 |
October | 0.216773E+11 | 0.402711E+10 | 0.108325E+11 | 0.00 | 0.133582E+11 | 0.00 | 0.00 | 65579729.19 | 0.00 | 0.00 | 0.00 | 0.539212E+10 | 0.00 |
November | 0.210012E+11 | 0.453241E+10 | 0.104978E+11 | 0.00 | 0.130041E+11 | 0.00 | 0.00 | 2234969.26 | 0.00 | 0.00 | 0.00 | 0.530001E+10 | 0.00 |
December | 0.216147E+11 | 0.504497E+10 | 0.108050E+11 | 0.00 | 0.134412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552984E+10 | 0.00 |
Annual Sum or Average | 0.256325E+12 | 0.412212E+11 | 0.128154E+12 | 0.00 | 0.159171E+12 | 0.00 | 0.00 | 0.204513E+11 | 0.00 | 0.00 | 0.00 | 0.642277E+11 | 0.00 |
Minimum of Months | 0.196202E+11 | 0.203720E+10 | 0.980803E+10 | 0.00 | 0.121861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505097E+10 | 0.00 |
Maximum of Months | 0.219947E+11 | 0.504497E+10 | 0.110075E+11 | 0.00 | 0.136888E+11 | 0.00 | 0.00 | 0.832920E+10 | 0.00 | 0.00 | 0.00 | 0.560198E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.612712E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.410828E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.209599E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.712607E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.594997E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 6211338.99 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 16557684.30 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.444882E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.300335E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.516068E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.217147E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.612712E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 16248.62 | 01-JAN-11:09 | 3786.68 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 10021.04 | 09-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 16248.62 | 01-FEB-10:09 | 3786.68 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 10008.77 | 18-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 16248.62 | 01-MAR-10:09 | 3786.68 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 9840.28 | 25-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 16248.62 | 01-APR-09:09 | 3786.68 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 9723.55 | 19-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 16248.62 | 01-MAY-09:09 | 3786.68 | 01-MAY-19:19 | 8059.50 | 01-MAY-09:09 | 0.00 | 9411.17 | 18-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 16248.62 | 01-JUN-09:09 | 3786.68 | 01-JUN-19:00 | 8059.50 | 01-JUN-09:09 | 0.00 | 9289.92 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 16248.62 | 01-JUL-09:09 | 3786.68 | 01-JUL-20:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 9313.11 | 24-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 16248.62 | 01-AUG-09:09 | 3786.68 | 01-AUG-19:40 | 8059.50 | 01-AUG-09:09 | 0.00 | 9452.25 | 10-AUG-16:40 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 16248.62 | 01-SEP-09:09 | 3786.68 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 9290.56 | 28-SEP-08:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 16248.62 | 01-OCT-10:09 | 3786.68 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 9554.85 | 30-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 16248.62 | 01-NOV-09:09 | 3786.68 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 9825.76 | 24-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 16248.62 | 01-DEC-10:09 | 3786.68 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 10028.61 | 26-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 16248.62 | 3786.68 | 8059.50 | 0.00 | 9289.92 | 0.00 | 0.00 | |||||
Maximum of Months | 16248.62 | 3786.68 | 8059.50 | 0.00 | 10028.61 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 12189.75 | 08-JAN-14:30 | 0.00 | 01-JAN-00:10 |
February | 22.19 | 28-FEB-21:49 | 0.00 | 0.00 | 0.00 | 11852.33 | 04-FEB-13:00 | 0.00 | 01-FEB-00:10 |
March | 46.79 | 19-MAR-19:10 | 0.00 | 0.00 | 0.00 | 9727.66 | 31-MAR-12:20 | 0.00 | 01-MAR-00:10 |
April | 12800.94 | 27-APR-16:10 | 0.00 | 0.00 | 0.00 | 11795.66 | 14-APR-17:00 | 0.00 | 01-APR-00:10 |
May | 12242.40 | 06-MAY-12:00 | 0.00 | 0.00 | 0.00 | 9588.09 | 08-MAY-18:00 | 0.00 | 01-MAY-00:10 |
June | 14356.29 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 11832.87 | 01-JUN-12:00 | 0.00 | 01-JUN-00:10 |
July | 19619.00 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 9664.57 | 11-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 21367.29 | 10-AUG-16:49 | 0.00 | 0.00 | 0.00 | 7575.49 | 01-AUG-13:30 | 0.00 | 01-AUG-00:10 |
September | 14000.58 | 14-SEP-16:19 | 0.00 | 0.00 | 0.00 | 7581.11 | 15-SEP-12:30 | 0.00 | 01-SEP-00:10 |
October | 5182.80 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 10201.90 | 28-OCT-12:20 | 0.00 | 01-OCT-00:10 |
November | 450.34 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 | 11841.46 | 29-NOV-14:09 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 11848.94 | 13-DEC-13:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7575.49 | 0.00 | |||
Maximum of Months | 21367.29 | 0.00 | 0.00 | 0.00 | 12189.75 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 47762.52 | 08-JAN-16:30 | 16248.62 | 8059.50 | 3786.68 | 0.00 | 9693.24 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 49084.28 | 08-FEB-17:30 | 16248.62 | 8059.50 | 3786.68 | 0.00 | 9568.29 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45036.91 | 24-MAR-18:49 | 16248.62 | 8059.50 | 3786.68 | 0.00 | 9383.83 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52243.55 | 27-APR-16:00 | 16248.62 | 8059.50 | 0.00 | 0.00 | 9289.92 | 0.00 | 0.00 | 11811.83 | 0.00 |
May | 51211.69 | 05-MAY-13:00 | 16248.62 | 8059.50 | 0.00 | 0.00 | 9289.92 | 0.00 | 0.00 | 10703.69 | 0.00 |
June | 52157.30 | 28-JUN-14:00 | 16248.62 | 8059.50 | 0.00 | 0.00 | 9289.92 | 0.00 | 0.00 | 13434.72 | 0.00 |
July | 57772.78 | 24-JUL-14:20 | 16248.62 | 8059.50 | 0.00 | 0.00 | 9289.92 | 0.00 | 0.00 | 18944.55 | 0.00 |
August | 60563.28 | 10-AUG-16:49 | 16248.62 | 8059.50 | 0.00 | 0.00 | 9451.51 | 0.00 | 0.00 | 21367.29 | 0.00 |
September | 54245.49 | 12-SEP-14:09 | 16248.62 | 8059.50 | 0.00 | 0.00 | 9289.92 | 0.00 | 0.00 | 13087.16 | 0.00 |
October | 45030.97 | 28-OCT-16:00 | 16248.62 | 8059.50 | 3786.68 | 0.00 | 9378.41 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 47390.62 | 24-NOV-17:30 | 16248.62 | 8059.50 | 3786.68 | 0.00 | 9617.76 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49538.50 | 23-DEC-16:30 | 16248.62 | 8059.50 | 3786.68 | 0.00 | 9642.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 45030.97 | 16248.62 | 8059.50 | 0.00 | 0.00 | 9289.92 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 60563.28 | 16248.62 | 8059.50 | 3786.68 | 0.00 | 9693.24 | 0.00 | 0.00 | 21367.29 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 114340.00 | 16-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 113524.99 | 19-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 77818.00 | 25-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 61543.38 | 19-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 20026.04 | 29-MAY-08:09 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 3369.05 | 15-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 5075.23 | 28-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 37777.92 | 30-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 79956.16 | 24-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 113663.36 | 26-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 114340.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
February | 1.00 | 20.48 | 0.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
March | 0.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
April | 0.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
December | 1.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Annual Sum or Average | 4.50 | 20.49 | 0.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 20.52 | 0.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
February | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
February | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
February | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
February | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 0.50 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 1.83 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
February | 3.33 | 20.01 | 0.00 | 20.01 | 0.00 | 20.01 | 0.00 | 20.01 |
March | 1.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
April | 0.33 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
December | 3.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Annual Sum or Average | 13.33 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.08 | 267.33 | 21.07 | 267.33 | 21.07 |
February | 448.00 | 21.14 | 182.83 | 21.12 | 182.83 | 21.10 |
March | 497.00 | 21.20 | 60.67 | 21.18 | 60.67 | 21.16 |
April | 450.00 | 21.73 | 11.83 | 21.71 | 11.83 | 21.69 |
May | 387.83 | 22.56 | 29.17 | 22.66 | 0.00 | 22.66 |
June | 192.83 | 23.26 | 38.33 | 23.36 | 0.00 | 23.36 |
July | 66.00 | 23.63 | 211.33 | 23.83 | 0.00 | 23.83 |
August | 36.00 | 23.52 | 260.00 | 23.84 | 0.00 | 23.84 |
September | 185.00 | 23.02 | 117.00 | 23.35 | 0.00 | 23.35 |
October | 428.83 | 21.87 | 2.50 | 21.88 | 0.00 | 21.88 |
November | 475.00 | 21.25 | 42.83 | 21.23 | 42.83 | 21.21 |
December | 496.00 | 21.08 | 156.50 | 21.07 | 156.50 | 21.06 |
Annual Sum or Average | 4158.50 | 21.66 | 1380.33 | 21.84 | 722.00 | 21.75 |
Minimum of Months | 36.00 | 21.08 | 2.50 | 21.07 | 0.00 | 21.06 |
Maximum of Months | 497.00 | 23.63 | 267.33 | 23.84 | 267.33 | 23.84 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.34 | 53.17 | 21.31 | 53.17 | 21.30 |
February | 448.00 | 21.60 | 36.17 | 21.56 | 36.17 | 21.53 |
March | 497.00 | 22.01 | 1.17 | 22.01 | 1.17 | 22.01 |
April | 422.00 | 22.77 | 9.67 | 22.79 | 0.00 | 22.79 |
May | 272.33 | 23.51 | 39.33 | 23.56 | 0.00 | 23.56 |
June | 74.33 | 23.75 | 49.17 | 23.80 | 0.00 | 23.80 |
July | 29.00 | 23.80 | 214.33 | 23.87 | 0.00 | 23.87 |
August | 15.67 | 23.64 | 258.83 | 23.87 | 0.00 | 23.87 |
September | 72.83 | 23.59 | 141.67 | 23.79 | 0.00 | 23.79 |
October | 378.33 | 22.95 | 5.50 | 22.97 | 0.00 | 22.97 |
November | 455.00 | 21.79 | 1.50 | 21.79 | 1.50 | 21.79 |
December | 496.00 | 21.41 | 19.33 | 21.40 | 19.33 | 21.39 |
Annual Sum or Average | 3656.50 | 22.14 | 829.83 | 22.40 | 111.33 | 22.37 |
Minimum of Months | 15.67 | 21.34 | 1.17 | 21.31 | 0.00 | 21.30 |
Maximum of Months | 497.00 | 23.80 | 258.83 | 23.87 | 53.17 | 23.87 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 104.67 | 21.12 | 104.67 | 21.12 |
February | 336.00 | 21.33 | 76.50 | 21.29 | 76.50 | 21.26 |
March | 379.00 | 21.63 | 13.67 | 21.61 | 13.67 | 21.59 |
April | 316.83 | 22.43 | 11.67 | 22.48 | 0.17 | 22.48 |
May | 184.33 | 23.38 | 39.17 | 23.52 | 0.00 | 23.52 |
June | 50.17 | 23.73 | 59.50 | 24.02 | 0.00 | 24.02 |
July | 17.00 | 23.88 | 199.17 | 24.06 | 0.00 | 24.06 |
August | 8.33 | 23.85 | 250.83 | 24.05 | 0.00 | 24.05 |
September | 60.00 | 23.56 | 125.67 | 23.90 | 0.00 | 23.90 |
October | 285.50 | 22.66 | 3.83 | 22.68 | 0.00 | 22.68 |
November | 349.83 | 21.49 | 12.83 | 21.48 | 12.83 | 21.47 |
December | 369.00 | 21.13 | 57.67 | 21.13 | 57.67 | 21.12 |
Annual Sum or Average | 2727.00 | 21.86 | 955.17 | 22.22 | 265.50 | 22.15 |
Minimum of Months | 8.33 | 21.12 | 3.83 | 21.12 | 0.00 | 21.12 |
Maximum of Months | 379.00 | 23.88 | 250.83 | 24.06 | 104.67 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 126.50 | 21.12 | 126.50 | 21.11 |
February | 336.00 | 21.30 | 93.33 | 21.26 | 93.33 | 21.23 |
March | 379.00 | 21.56 | 16.83 | 21.54 | 16.83 | 21.52 |
April | 320.00 | 22.32 | 9.33 | 22.37 | 1.00 | 22.36 |
May | 208.33 | 23.37 | 36.33 | 23.49 | 0.00 | 23.49 |
June | 53.00 | 23.72 | 58.00 | 24.01 | 0.00 | 24.01 |
July | 17.83 | 23.88 | 196.67 | 24.06 | 0.00 | 24.06 |
August | 8.50 | 23.84 | 250.17 | 24.05 | 0.00 | 24.05 |
September | 65.67 | 23.54 | 121.33 | 23.88 | 0.00 | 23.88 |
October | 291.33 | 22.55 | 3.33 | 22.56 | 0.00 | 22.56 |
November | 351.33 | 21.45 | 17.17 | 21.43 | 17.17 | 21.42 |
December | 369.00 | 21.12 | 71.50 | 21.12 | 71.50 | 21.12 |
Annual Sum or Average | 2771.00 | 21.83 | 1000.50 | 22.17 | 326.33 | 22.09 |
Minimum of Months | 8.50 | 21.12 | 3.33 | 21.12 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.88 | 250.17 | 24.06 | 126.50 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 150.33 | 21.11 | 150.33 | 21.11 |
February | 336.00 | 21.26 | 115.67 | 21.22 | 115.67 | 21.20 |
March | 379.00 | 21.43 | 26.00 | 21.41 | 26.00 | 21.39 |
April | 333.00 | 22.15 | 6.50 | 22.16 | 3.67 | 22.15 |
May | 257.00 | 23.25 | 29.50 | 23.34 | 0.00 | 23.34 |
June | 86.83 | 23.68 | 51.33 | 23.91 | 0.00 | 23.91 |
July | 23.33 | 23.86 | 182.67 | 24.06 | 0.00 | 24.06 |
August | 12.00 | 23.81 | 240.67 | 24.05 | 0.00 | 24.05 |
September | 92.00 | 23.46 | 107.67 | 23.78 | 0.00 | 23.78 |
October | 304.67 | 22.31 | 2.17 | 22.33 | 0.00 | 22.33 |
November | 354.17 | 21.37 | 24.83 | 21.35 | 24.83 | 21.33 |
December | 369.00 | 21.11 | 95.00 | 21.11 | 95.00 | 21.11 |
Annual Sum or Average | 2918.00 | 21.82 | 1032.33 | 22.10 | 415.50 | 22.00 |
Minimum of Months | 12.00 | 21.11 | 2.17 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.86 | 240.67 | 24.06 | 150.33 | 24.06 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 209.50 | 21.11 | 209.50 | 21.11 |
February | 308.00 | 21.15 | 139.50 | 21.14 | 139.50 | 21.13 |
March | 348.00 | 21.18 | 46.33 | 21.17 | 46.33 | 21.16 |
April | 314.33 | 21.61 | 6.33 | 21.60 | 6.33 | 21.59 |
May | 283.17 | 22.43 | 15.83 | 22.52 | 0.00 | 22.52 |
June | 157.67 | 23.24 | 21.17 | 23.32 | 0.00 | 23.32 |
July | 42.83 | 23.56 | 140.17 | 23.85 | 0.00 | 23.85 |
August | 21.00 | 23.44 | 191.33 | 23.88 | 0.00 | 23.88 |
September | 156.50 | 22.83 | 74.00 | 23.19 | 0.00 | 23.19 |
October | 324.50 | 21.83 | 0.33 | 21.83 | 0.33 | 21.83 |
November | 330.00 | 21.19 | 40.50 | 21.19 | 40.50 | 21.18 |
December | 338.00 | 21.11 | 147.67 | 21.11 | 147.67 | 21.11 |
Annual Sum or Average | 2964.00 | 21.65 | 1032.67 | 21.82 | 590.17 | 21.73 |
Minimum of Months | 21.00 | 21.11 | 0.33 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.56 | 209.50 | 23.88 | 209.50 | 23.88 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 205.50 | 21.11 | 205.50 | 21.11 |
February | 308.00 | 21.18 | 140.67 | 21.16 | 140.67 | 21.15 |
March | 348.00 | 21.24 | 49.67 | 21.22 | 49.67 | 21.21 |
April | 312.50 | 21.78 | 8.50 | 21.77 | 7.83 | 21.76 |
May | 283.17 | 22.80 | 13.17 | 22.86 | 0.00 | 22.86 |
June | 156.67 | 23.55 | 12.00 | 23.59 | 0.00 | 23.59 |
July | 40.33 | 23.81 | 119.33 | 23.93 | 0.00 | 23.93 |
August | 18.83 | 23.76 | 171.67 | 23.92 | 0.00 | 23.92 |
September | 144.83 | 23.19 | 64.17 | 23.43 | 0.00 | 23.43 |
October | 319.00 | 22.04 | 0.50 | 22.03 | 0.50 | 22.03 |
November | 330.00 | 21.24 | 40.83 | 21.23 | 40.83 | 21.22 |
December | 338.00 | 21.11 | 142.50 | 21.11 | 142.50 | 21.11 |
Annual Sum or Average | 2939.33 | 21.77 | 968.50 | 21.88 | 587.50 | 21.78 |
Minimum of Months | 18.83 | 21.11 | 0.50 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.81 | 205.50 | 23.93 | 205.50 | 23.93 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 211.00 | 21.11 | 211.00 | 21.11 |
February | 308.00 | 21.17 | 144.33 | 21.15 | 144.33 | 21.14 |
March | 348.00 | 21.23 | 54.00 | 21.21 | 54.00 | 21.20 |
April | 313.83 | 21.76 | 10.00 | 21.75 | 9.33 | 21.73 |
May | 288.33 | 22.76 | 12.17 | 22.81 | 0.00 | 22.81 |
June | 164.50 | 23.53 | 9.67 | 23.57 | 0.00 | 23.57 |
July | 44.00 | 23.80 | 112.83 | 23.93 | 0.00 | 23.93 |
August | 21.67 | 23.75 | 165.83 | 23.92 | 0.00 | 23.92 |
September | 149.50 | 23.17 | 61.00 | 23.40 | 0.00 | 23.40 |
October | 322.33 | 22.02 | 0.83 | 22.02 | 0.83 | 22.02 |
November | 330.00 | 21.24 | 46.67 | 21.22 | 46.67 | 21.21 |
December | 338.00 | 21.11 | 153.00 | 21.11 | 153.00 | 21.11 |
Annual Sum or Average | 2968.17 | 21.77 | 981.33 | 21.87 | 619.17 | 21.76 |
Minimum of Months | 21.67 | 21.11 | 0.83 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.80 | 211.00 | 23.93 | 211.00 | 23.93 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 230.67 | 21.11 | 230.67 | 21.11 |
February | 308.00 | 21.16 | 157.00 | 21.14 | 157.00 | 21.13 |
March | 348.00 | 21.20 | 73.00 | 21.18 | 73.00 | 21.17 |
April | 316.67 | 21.68 | 14.83 | 21.66 | 14.83 | 21.63 |
May | 301.67 | 22.57 | 9.33 | 22.61 | 0.00 | 22.61 |
June | 182.33 | 23.41 | 7.50 | 23.44 | 0.00 | 23.44 |
July | 61.17 | 23.74 | 105.33 | 23.89 | 0.00 | 23.89 |
August | 30.67 | 23.71 | 156.67 | 23.90 | 0.00 | 23.90 |
September | 170.50 | 23.06 | 52.00 | 23.27 | 0.00 | 23.27 |
October | 331.17 | 21.95 | 1.33 | 21.94 | 1.33 | 21.94 |
November | 330.00 | 21.21 | 70.00 | 21.19 | 70.00 | 21.18 |
December | 338.00 | 21.11 | 189.67 | 21.11 | 189.67 | 21.11 |
Annual Sum or Average | 3058.17 | 21.75 | 1067.33 | 21.82 | 736.50 | 21.71 |
Minimum of Months | 30.67 | 21.11 | 1.33 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.74 | 230.67 | 23.90 | 230.67 | 23.90 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 325.67 | 21.11 | 325.67 | 21.11 |
February | 308.00 | 21.14 | 219.00 | 21.13 | 219.00 | 21.12 |
March | 348.00 | 21.16 | 168.67 | 21.15 | 168.67 | 21.14 |
April | 320.00 | 21.57 | 53.83 | 21.51 | 53.83 | 21.46 |
May | 313.83 | 22.28 | 5.00 | 22.29 | 2.00 | 22.28 |
June | 225.33 | 23.22 | 1.83 | 23.23 | 0.00 | 23.23 |
July | 98.00 | 23.57 | 95.00 | 23.77 | 0.00 | 23.77 |
August | 59.17 | 23.57 | 140.83 | 23.83 | 0.00 | 23.83 |
September | 201.67 | 22.81 | 47.33 | 23.03 | 0.00 | 23.03 |
October | 340.00 | 21.82 | 11.83 | 21.80 | 11.83 | 21.78 |
November | 330.00 | 21.19 | 153.83 | 21.16 | 153.83 | 21.15 |
December | 338.00 | 21.11 | 291.83 | 21.11 | 291.83 | 21.11 |
Annual Sum or Average | 3222.00 | 21.74 | 1514.67 | 21.71 | 1226.67 | 21.59 |
Minimum of Months | 59.17 | 21.11 | 1.83 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.57 | 325.67 | 23.83 | 325.67 | 23.83 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.08176 | 31.26031 | -0.5432 | 11.30102 |
February | 448.00000 | 21.14032 | 33.08066 | -0.4902 | 10.40850 |
March | 497.00000 | 21.20115 | 34.47769 | -0.4230 | 9.02521 |
April | 479.00000 | 21.85597 | 37.82863 | -0.2124 | 7.28059 |
May | 496.00000 | 22.85118 | 40.91171 | -0.9376 | 25.41236 |
June | 481.00000 | 23.63395 | 41.34637 | -0.6470 | 14.43999 |
July | 495.00000 | 23.85125 | 44.88860 | -0.5091 | 10.67783 |
August | 497.00000 | 23.85786 | 47.97172 | -0.4835 | 10.10280 |
September | 479.00000 | 23.54037 | 47.38652 | -0.6360 | 14.46480 |
October | 496.00000 | 22.14106 | 41.89720 | -0.1019 | 6.67754 |
November | 480.00000 | 21.27726 | 40.09865 | -0.3789 | 8.70403 |
December | 496.00000 | 21.08218 | 33.51922 | -0.5117 | 10.57363 |
Annual Sum or Average | 5840.00000 | 22.29913 | 39.58463 | -0.4898 | 11.60294 |
Minimum of Months | 448.00000 | 21.08176 | 31.26031 | -0.9376 | 6.67754 |
Maximum of Months | 497.00000 | 23.85786 | 47.97172 | -0.1019 | 25.41236 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.33599 | 33.80255 | -0.4279 | 9.03220 |
February | 448.00000 | 21.59970 | 34.96886 | -0.3426 | 8.27097 |
March | 497.00000 | 22.01197 | 35.46560 | -0.2144 | 6.68042 |
April | 479.00000 | 22.89587 | 37.33637 | 0.02738 | 6.05054 |
May | 496.00000 | 23.67604 | 38.98259 | -0.6752 | 15.12225 |
June | 481.00000 | 23.85661 | 40.26624 | -0.5617 | 11.74013 |
July | 495.00000 | 23.86905 | 44.63975 | -0.4927 | 10.22274 |
August | 497.00000 | 23.85670 | 47.82811 | -0.4719 | 9.78810 |
September | 479.00000 | 23.83261 | 46.12670 | -0.5358 | 11.24234 |
October | 496.00000 | 23.17533 | 40.57995 | 0.12915 | 6.07985 |
November | 480.00000 | 21.90095 | 41.36521 | -0.2084 | 7.10576 |
December | 496.00000 | 21.40724 | 36.08727 | -0.3867 | 8.37818 |
Annual Sum or Average | 5840.00000 | 22.79074 | 39.80997 | -0.3471 | 9.15126 |
Minimum of Months | 448.00000 | 21.33599 | 33.80255 | -0.6752 | 6.05054 |
Maximum of Months | 497.00000 | 23.86905 | 47.82811 | 0.12915 | 15.12225 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11985 | 30.81855 | -0.4983 | 10.28982 |
February | 336.00000 | 21.32642 | 31.99659 | -0.4190 | 9.31311 |
March | 379.00000 | 21.62581 | 32.70061 | -0.3046 | 7.53170 |
April | 360.00000 | 22.60819 | 35.24936 | -0.0399 | 6.29398 |
May | 375.00000 | 23.67978 | 38.18027 | -0.6704 | 15.17248 |
June | 366.00000 | 23.94640 | 39.30701 | -0.5401 | 11.33974 |
July | 369.00000 | 23.99837 | 44.22812 | -0.4570 | 9.64309 |
August | 379.00000 | 24.00235 | 47.58603 | -0.4290 | 9.09583 |
September | 360.00000 | 23.89579 | 45.37912 | -0.5202 | 11.02361 |
October | 371.00000 | 22.95663 | 38.62636 | 0.07779 | 6.06333 |
November | 360.00000 | 21.56151 | 38.51890 | -0.2964 | 7.91597 |
December | 369.00000 | 21.12771 | 32.65774 | -0.4701 | 9.69423 |
Annual Sum or Average | 4395.00000 | 22.66451 | 37.97758 | -0.3810 | 9.45566 |
Minimum of Months | 336.00000 | 21.11985 | 30.81855 | -0.6704 | 6.06333 |
Maximum of Months | 379.00000 | 24.00235 | 47.58603 | 0.07779 | 15.17248 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11800 | 30.82270 | -0.5083 | 10.50302 |
February | 336.00000 | 21.29980 | 32.06476 | -0.4332 | 9.50605 |
March | 379.00000 | 21.55617 | 32.83449 | -0.3271 | 7.78215 |
April | 360.00000 | 22.50145 | 35.46592 | -0.0693 | 6.42410 |
May | 375.00000 | 23.64016 | 38.29028 | -0.6886 | 15.77851 |
June | 366.00000 | 23.94142 | 39.33121 | -0.5445 | 11.44911 |
July | 369.00000 | 23.99729 | 44.23567 | -0.4584 | 9.67449 |
August | 379.00000 | 24.00166 | 47.58947 | -0.4295 | 9.10498 |
September | 360.00000 | 23.88518 | 45.42483 | -0.5266 | 11.19338 |
October | 371.00000 | 22.84531 | 38.89310 | 0.04847 | 6.12198 |
November | 360.00000 | 21.50685 | 38.66114 | -0.3170 | 8.08613 |
December | 369.00000 | 21.12207 | 32.66708 | -0.4803 | 9.89628 |
Annual Sum or Average | 4395.00000 | 22.62841 | 38.06345 | -0.3949 | 9.63467 |
Minimum of Months | 336.00000 | 21.11800 | 30.82270 | -0.6886 | 6.12198 |
Maximum of Months | 379.00000 | 24.00166 | 47.58947 | 0.04847 | 15.77851 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11510 | 30.82975 | -0.5215 | 10.78618 |
February | 336.00000 | 21.25538 | 32.17670 | -0.4542 | 9.80078 |
March | 379.00000 | 21.43444 | 33.07685 | -0.3648 | 8.22355 |
April | 360.00000 | 22.28658 | 35.90263 | -0.1269 | 6.69348 |
May | 375.00000 | 23.48019 | 38.71202 | -0.7555 | 18.10842 |
June | 366.00000 | 23.91047 | 39.46310 | -0.5667 | 12.02112 |
July | 369.00000 | 23.99081 | 44.29113 | -0.4685 | 9.87219 |
August | 379.00000 | 23.99539 | 47.64002 | -0.4389 | 9.27556 |
September | 360.00000 | 23.83032 | 45.64260 | -0.5559 | 11.99178 |
October | 371.00000 | 22.60454 | 39.48012 | -0.0145 | 6.26664 |
November | 360.00000 | 21.40728 | 38.92629 | -0.3507 | 8.36128 |
December | 369.00000 | 21.11456 | 32.67961 | -0.4941 | 10.17664 |
Annual Sum or Average | 4395.00000 | 22.54575 | 38.27542 | -0.4264 | 10.14266 |
Minimum of Months | 336.00000 | 21.11456 | 30.82975 | -0.7555 | 6.26664 |
Maximum of Months | 379.00000 | 23.99539 | 47.64002 | -0.0145 | 18.10842 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10970 | 32.50061 | -0.5520 | 11.46133 |
February | 308.00000 | 21.15075 | 34.07503 | -0.5007 | 10.52093 |
March | 348.00000 | 21.17881 | 35.20926 | -0.4378 | 9.21385 |
April | 330.00000 | 21.71539 | 38.65831 | -0.2534 | 7.54395 |
May | 344.00000 | 22.69560 | 42.10682 | -0.9897 | 27.47642 |
June | 336.00000 | 23.59097 | 41.73416 | -0.6701 | 15.12372 |
July | 338.00000 | 23.86437 | 45.80319 | -0.5112 | 10.73701 |
August | 348.00000 | 23.87548 | 48.89478 | -0.4816 | 10.06364 |
September | 330.00000 | 23.38723 | 48.38769 | -0.6908 | 16.34810 |
October | 340.00000 | 21.92542 | 42.68433 | -0.1627 | 6.84312 |
November | 330.00000 | 21.19445 | 41.14746 | -0.4195 | 9.11481 |
December | 338.00000 | 21.10980 | 34.32459 | -0.5246 | 10.82238 |
Annual Sum or Average | 4030.00000 | 22.24278 | 40.50140 | -0.5169 | 12.13035 |
Minimum of Months | 308.00000 | 21.10970 | 32.50061 | -0.9897 | 6.84312 |
Maximum of Months | 348.00000 | 23.87548 | 48.89478 | -0.1627 | 27.47642 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10998 | 32.34340 | -0.5499 | 11.41026 |
February | 308.00000 | 21.17812 | 33.84804 | -0.4972 | 10.48947 |
March | 348.00000 | 21.23979 | 34.93182 | -0.4336 | 9.19625 |
April | 330.00000 | 21.89756 | 38.06085 | -0.2330 | 7.40275 |
May | 344.00000 | 23.00325 | 41.15523 | -0.9318 | 24.89706 |
June | 336.00000 | 23.74751 | 40.96171 | -0.6483 | 14.24548 |
July | 338.00000 | 23.91048 | 45.55926 | -0.5170 | 10.80751 |
August | 348.00000 | 23.90751 | 48.84605 | -0.4893 | 10.17996 |
September | 330.00000 | 23.59581 | 47.54422 | -0.6537 | 14.87753 |
October | 340.00000 | 22.14967 | 41.93278 | -0.1338 | 6.80350 |
November | 330.00000 | 21.24265 | 40.83916 | -0.4153 | 9.10284 |
December | 338.00000 | 21.10994 | 34.16627 | -0.5237 | 10.79974 |
Annual Sum or Average | 4030.00000 | 22.35099 | 40.05661 | -0.5029 | 11.70648 |
Minimum of Months | 308.00000 | 21.10994 | 32.34340 | -0.9318 | 6.80350 |
Maximum of Months | 348.00000 | 23.91048 | 48.84605 | -0.1338 | 24.89706 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10974 | 32.34461 | -0.5529 | 11.47926 |
February | 308.00000 | 21.17373 | 33.85912 | -0.5016 | 10.57260 |
March | 348.00000 | 21.22971 | 34.95370 | -0.4400 | 9.30512 |
April | 330.00000 | 21.86890 | 38.12521 | -0.2428 | 7.49582 |
May | 344.00000 | 22.94754 | 41.29206 | -0.9538 | 25.82651 |
June | 336.00000 | 23.72934 | 41.03349 | -0.6588 | 14.57271 |
July | 338.00000 | 23.90720 | 45.60344 | -0.5223 | 10.92927 |
August | 348.00000 | 23.90555 | 48.88647 | -0.4935 | 10.27018 |
September | 330.00000 | 23.57509 | 47.62732 | -0.6635 | 15.20156 |
October | 340.00000 | 22.11798 | 42.01651 | -0.1440 | 6.85572 |
November | 330.00000 | 21.23527 | 40.86190 | -0.4204 | 9.18162 |
December | 338.00000 | 21.10985 | 34.16702 | -0.5268 | 10.86793 |
Annual Sum or Average | 4030.00000 | 22.33572 | 40.10537 | -0.5107 | 11.90341 |
Minimum of Months | 308.00000 | 21.10974 | 32.34461 | -0.9538 | 6.85572 |
Maximum of Months | 348.00000 | 23.90720 | 48.88647 | -0.1440 | 25.82651 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10970 | 32.34569 | -0.5654 | 11.78023 |
February | 308.00000 | 21.16036 | 33.89098 | -0.5176 | 10.89259 |
March | 348.00000 | 21.19925 | 35.01776 | -0.4603 | 9.65765 |
April | 330.00000 | 21.77301 | 38.34158 | -0.2743 | 7.80698 |
May | 344.00000 | 22.73861 | 41.79162 | -1.0321 | 29.26794 |
June | 336.00000 | 23.64251 | 41.32481 | -0.6988 | 15.93301 |
July | 338.00000 | 23.88982 | 45.73663 | -0.5381 | 11.33035 |
August | 348.00000 | 23.89562 | 48.97471 | -0.5045 | 10.53356 |
September | 330.00000 | 23.46857 | 48.00146 | -0.7068 | 16.75562 |
October | 340.00000 | 21.99657 | 42.32584 | -0.1804 | 7.02160 |
November | 330.00000 | 21.21309 | 40.93193 | -0.4366 | 9.43746 |
December | 338.00000 | 21.10962 | 34.16828 | -0.5389 | 11.14287 |
Annual Sum or Average | 4030.00000 | 22.27602 | 40.27945 | -0.5386 | 12.65799 |
Minimum of Months | 308.00000 | 21.10962 | 32.34569 | -1.0321 | 7.02160 |
Maximum of Months | 348.00000 | 23.89562 | 48.97471 | -0.1804 | 29.26794 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 32.05578 | -0.6216 | 13.21323 |
February | 308.00000 | 21.14254 | 33.64392 | -0.5752 | 12.22985 |
March | 348.00000 | 21.16308 | 34.84462 | -0.5179 | 10.82413 |
April | 330.00000 | 21.64594 | 38.40438 | -0.3368 | 8.61026 |
May | 344.00000 | 22.42296 | 42.26771 | -1.1681 | 35.65370 |
June | 336.00000 | 23.45366 | 41.71528 | -0.7833 | 19.17475 |
July | 338.00000 | 23.82330 | 45.81115 | -0.5793 | 12.56657 |
August | 348.00000 | 23.85639 | 49.01165 | -0.5293 | 11.27412 |
September | 330.00000 | 23.24019 | 48.52685 | -0.8012 | 20.54671 |
October | 340.00000 | 21.82268 | 42.48420 | -0.2505 | 7.57028 |
November | 330.00000 | 21.18731 | 40.66190 | -0.4857 | 10.38879 |
December | 338.00000 | 21.11000 | 33.88161 | -0.5906 | 12.39364 |
Annual Sum or Average | 4030.00000 | 22.17405 | 40.31916 | -0.6041 | 14.57013 |
Minimum of Months | 308.00000 | 21.11000 | 32.05578 | -1.1681 | 7.57028 |
Maximum of Months | 348.00000 | 23.85639 | 49.01165 | -0.2505 | 35.65370 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.404427E+09 | 0.103361E+09 | 27.67 | 0.386225E+09 | 18201755.27 | 0.00 | 0.69 | 27-APR-16:10 | 0.00 | 01-APR-00:10 | 8979.00 | 27-APR-16:10 | 8524.68 | 27-APR-16:10 | 653.34 | 27-APR-17:00 | 2203.25 | 27-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 0.975706E+09 | 0.240396E+09 | 73.83 | 0.864834E+09 | 0.110871E+09 | 0.00 | 0.66 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 8730.08 | 06-MAY-13:00 | 7730.07 | 15-MAY-17:00 | 1782.09 | 06-MAY-12:50 | 2040.22 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.189714E+10 | 0.465689E+09 | 137.75 | 0.177779E+10 | 0.119351E+09 | 0.00 | 0.80 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 10602.76 | 28-JUN-17:00 | 10172.59 | 28-JUN-17:00 | 1048.14 | 21-JUN-17:10 | 2510.52 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.515841E+10 | 0.123343E+10 | 264.92 | 0.443613E+10 | 0.722279E+09 | 0.00 | 0.99 | 31-JUL-16:10 | 0.00 | 01-JUL-00:10 | 14348.68 | 31-JUL-16:10 | 12589.14 | 24-JUL-15:00 | 2762.36 | 15-JUL-18:00 | 3268.64 | 31-JUL-16:10 | 0.00 | 01-JUL-00:10 |
August | 0.696446E+10 | 0.165664E+10 | 312.58 | 0.600273E+10 | 0.961734E+09 | 0.00 | 1.00 | 09-AUG-16:10 | 0.00 | 01-AUG-00:10 | 15616.37 | 10-AUG-17:00 | 15172.25 | 10-AUG-17:00 | 2951.81 | 30-AUG-13:00 | 3778.28 | 10-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.187399E+10 | 0.447393E+09 | 117.83 | 0.152907E+10 | 0.344920E+09 | 0.00 | 0.78 | 14-SEP-16:30 | 0.00 | 01-SEP-00:10 | 10647.84 | 14-SEP-16:30 | 9236.48 | 14-SEP-16:40 | 2631.51 | 14-SEP-13:00 | 2434.45 | 14-SEP-16:30 | 0.00 | 01-SEP-00:10 |
October | 60855854.55 | 15333614.73 | 7.50 | 60687469.17 | 168385.38 | 0.00 | 0.34 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3809.69 | 04-OCT-15:00 | 3809.69 | 04-OCT-15:00 | 111.89 | 08-OCT-14:00 | 947.80 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 48445.74 | 13076.56 | 0.17 | 36304.60 | 12141.14 | 0.00 | 0.01 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 80.74 | 04-NOV-14:00 | 60.51 | 04-NOV-14:00 | 20.24 | 04-NOV-14:00 | 21.79 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.173350E+11 | 0.416225E+10 | 942.25 | 0.150575E+11 | 0.227754E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.696446E+10 | 0.165664E+10 | 312.58 | 0.600273E+10 | 0.961734E+09 | 0.00 | 1.00 | 0.00 | 15616.37 | 15172.25 | 2951.81 | 3778.28 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 56666.16 | 13322.46 | 0.67 | 55036.00 | 1630.16 | 0.00 | 0.02 | 28-FEB-21:50 | 0.00 | 01-FEB-00:10 | 94.39 | 28-FEB-21:50 | 91.67 | 28-FEB-21:50 | 2.72 | 28-FEB-21:50 | 22.19 | 28-FEB-21:50 | 0.00 | 01-FEB-00:10 |
March | 244490.98 | 57154.53 | 1.75 | 238166.53 | 6324.45 | 0.00 | 0.04 | 19-MAR-17:50 | 0.00 | 01-MAR-00:10 | 237.92 | 19-MAR-17:50 | 237.92 | 19-MAR-17:50 | 10.54 | 10-MAR-21:40 | 55.37 | 19-MAR-17:50 | 0.00 | 01-MAR-00:10 |
April | 0.303675E+09 | 66227958.54 | 33.88 | 0.297297E+09 | 6377706.75 | 0.00 | 1.00 | 01-APR-18:31 | 0.00 | 01-APR-00:10 | 14785.44 | 01-APR-18:31 | 14785.44 | 01-APR-18:31 | 750.79 | 30-APR-17:10 | 2887.95 | 01-APR-18:31 | 0.00 | 01-APR-00:10 |
May | 0.665905E+09 | 0.139926E+09 | 77.07 | 0.608029E+09 | 57876007.72 | 0.00 | 1.00 | 06-MAY-18:01 | 0.00 | 01-MAY-00:10 | 15789.28 | 07-MAY-17:02 | 14809.65 | 14-MAY-17:36 | 5019.18 | 06-MAY-18:45 | 2968.44 | 07-MAY-17:02 | 0.00 | 01-MAY-00:10 |
June | 0.124166E+10 | 0.260319E+09 | 137.99 | 0.119459E+10 | 47067677.79 | 0.00 | 1.00 | 02-JUN-20:04 | 0.00 | 01-JUN-00:10 | 15570.50 | 11-JUN-17:57 | 15021.86 | 25-JUN-17:09 | 3598.77 | 28-JUN-20:40 | 2949.41 | 10-JUN-18:09 | 0.00 | 01-JUN-00:10 |
July | 0.305594E+10 | 0.631137E+09 | 246.92 | 0.273471E+10 | 0.321229E+09 | 0.00 | 1.00 | 07-JUL-20:01 | 0.00 | 01-JUL-00:10 | 16185.80 | 15-JUL-18:02 | 14824.07 | 07-JUL-21:00 | 5606.10 | 15-JUL-20:03 | 3061.82 | 15-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 0.425086E+10 | 0.872214E+09 | 276.47 | 0.380032E+10 | 0.450543E+09 | 0.00 | 1.00 | 05-AUG-18:01 | 0.00 | 01-AUG-00:10 | 16069.21 | 26-AUG-18:02 | 15183.98 | 08-AUG-22:00 | 6192.91 | 26-AUG-19:03 | 3089.16 | 24-AUG-20:52 | 0.00 | 01-AUG-00:10 |
September | 0.110560E+10 | 0.227564E+09 | 113.79 | 0.947588E+09 | 0.158012E+09 | 0.00 | 1.00 | 02-SEP-18:01 | 0.00 | 01-SEP-00:10 | 15942.00 | 23-SEP-18:02 | 14809.25 | 10-SEP-17:01 | 4936.86 | 23-SEP-18:02 | 2974.07 | 23-SEP-18:02 | 0.00 | 01-SEP-00:10 |
October | 38065679.90 | 8372951.22 | 13.42 | 37846680.50 | 218999.40 | 0.00 | 0.36 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2428.53 | 04-OCT-15:00 | 2428.53 | 04-OCT-15:00 | 139.80 | 26-OCT-20:20 | 523.48 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 4777306.48 | 1102984.45 | 4.00 | 3835691.94 | 941614.54 | 0.00 | 0.12 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 830.32 | 04-NOV-14:00 | 659.06 | 04-NOV-14:00 | 171.26 | 04-NOV-14:00 | 189.64 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.106668E+11 | 0.220693E+10 | 905.97 | 0.962451E+10 | 0.104227E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.425086E+10 | 0.872214E+09 | 276.47 | 0.380032E+10 | 0.450543E+09 | 0.00 | 1.00 | 0.00 | 16185.80 | 15183.98 | 6192.91 | 3089.16 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 29.28 | 6.90 | 0.50 | 29.28 | -0.0 | 0.00 | 0.00 | 27-FEB-14:20 | 0.00 | 01-FEB-00:10 | 0.03 | 27-FEB-14:20 | 0.03 | 27-FEB-14:20 | 0.00 | 01-FEB-00:10 | 0.01 | 27-FEB-14:20 | 0.00 | 01-FEB-00:10 |
March | 824.48 | 193.98 | 1.50 | 824.48 | -0.0 | 0.00 | 0.00 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 0.37 | 18-MAR-14:00 | 0.37 | 18-MAR-14:00 | 0.00 | 14-MAR-18:20 | 0.09 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.264274E+09 | 58376967.98 | 27.83 | 0.259505E+09 | 4768730.40 | 0.00 | 0.67 | 27-APR-16:10 | 0.00 | 01-APR-00:10 | 5633.98 | 27-APR-16:10 | 5539.92 | 27-APR-16:10 | 214.91 | 27-APR-17:00 | 1213.44 | 27-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 0.513492E+09 | 0.110474E+09 | 69.83 | 0.474440E+09 | 39052400.29 | 0.00 | 0.66 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 5783.86 | 06-MAY-13:00 | 4875.55 | 06-MAY-13:00 | 943.60 | 06-MAY-12:50 | 1175.32 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.918728E+09 | 0.198065E+09 | 120.33 | 0.897119E+09 | 21608208.72 | 0.00 | 0.71 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5996.41 | 28-JUN-17:00 | 5986.45 | 28-JUN-17:00 | 379.94 | 21-JUN-17:10 | 1271.79 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.230215E+10 | 0.487957E+09 | 209.00 | 0.208591E+10 | 0.216237E+09 | 0.00 | 0.88 | 31-JUL-16:10 | 0.00 | 01-JUL-00:10 | 8014.25 | 31-JUL-16:10 | 7339.91 | 24-JUL-15:00 | 1155.21 | 27-JUL-18:40 | 1652.54 | 31-JUL-16:10 | 0.00 | 01-JUL-00:10 |
August | 0.325176E+10 | 0.685497E+09 | 229.36 | 0.293566E+10 | 0.316099E+09 | 0.00 | 0.94 | 10-AUG-16:30 | 0.00 | 01-AUG-00:10 | 8569.65 | 10-AUG-16:10 | 8366.70 | 10-AUG-16:30 | 1643.35 | 30-AUG-13:00 | 1834.48 | 10-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.884526E+09 | 0.186083E+09 | 99.33 | 0.762537E+09 | 0.121990E+09 | 0.00 | 0.71 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 | 6309.06 | 14-SEP-14:00 | 5511.37 | 14-SEP-16:20 | 1430.02 | 23-SEP-14:00 | 1262.97 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 29070727.86 | 6464253.95 | 9.67 | 29070711.23 | 16.63 | 0.00 | 0.30 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2196.61 | 04-OCT-15:00 | 2196.61 | 04-OCT-15:00 | 0.03 | 02-OCT-09:50 | 481.62 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 2432622.36 | 565338.13 | 3.33 | 1927640.61 | 504981.75 | 0.00 | 0.08 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 582.00 | 04-NOV-14:00 | 461.68 | 04-NOV-14:00 | 120.32 | 04-NOV-14:00 | 134.47 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.816643E+10 | 0.173348E+10 | 770.69 | 0.744617E+10 | 0.720260E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.325176E+10 | 0.685497E+09 | 229.36 | 0.293566E+10 | 0.316099E+09 | 0.00 | 0.94 | 0.00 | 8569.65 | 8366.70 | 1643.35 | 1834.48 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 32.53 | 7.67 | 0.33 | 32.53 | 0.00 | 0.00 | 0.00 | 27-FEB-14:50 | 0.00 | 01-FEB-00:10 | 0.03 | 27-FEB-14:50 | 0.03 | 27-FEB-14:50 | 0.00 | 27-FEB-14:50 | 0.01 | 27-FEB-14:50 | 0.00 | 01-FEB-00:10 |
March | 1066.24 | 250.76 | 2.17 | 1066.24 | 0.00 | 0.00 | 0.00 | 18-MAR-13:50 | 0.00 | 01-MAR-00:10 | 0.39 | 18-MAR-13:50 | 0.39 | 18-MAR-13:50 | 0.00 | 18-MAR-13:50 | 0.09 | 18-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 0.253726E+09 | 56250348.05 | 25.17 | 0.249169E+09 | 4557192.86 | 0.00 | 0.66 | 27-APR-16:10 | 0.00 | 01-APR-00:10 | 5500.34 | 27-APR-16:10 | 5408.52 | 27-APR-16:10 | 209.77 | 27-APR-17:00 | 1188.95 | 27-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 0.496667E+09 | 0.106965E+09 | 68.83 | 0.459018E+09 | 37649530.24 | 0.00 | 0.66 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 5740.64 | 06-MAY-13:00 | 4838.99 | 06-MAY-13:00 | 935.60 | 06-MAY-12:50 | 1167.57 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.905480E+09 | 0.195274E+09 | 118.17 | 0.884268E+09 | 21211953.20 | 0.00 | 0.71 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5975.96 | 28-JUN-17:00 | 5967.20 | 28-JUN-17:00 | 377.23 | 21-JUN-17:10 | 1267.74 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.229327E+10 | 0.486016E+09 | 207.83 | 0.207770E+10 | 0.215577E+09 | 0.00 | 0.88 | 31-JUL-16:10 | 0.00 | 01-JUL-00:10 | 8021.32 | 31-JUL-16:10 | 7342.67 | 24-JUL-15:00 | 1151.74 | 27-JUL-18:40 | 1652.90 | 31-JUL-16:10 | 0.00 | 01-JUL-00:10 |
August | 0.324834E+10 | 0.684608E+09 | 229.11 | 0.293238E+10 | 0.315961E+09 | 0.00 | 0.95 | 10-AUG-16:30 | 0.00 | 01-AUG-00:10 | 8577.35 | 10-AUG-16:10 | 8373.33 | 10-AUG-16:30 | 1642.51 | 30-AUG-13:00 | 1834.40 | 10-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.874465E+09 | 0.183989E+09 | 99.50 | 0.753752E+09 | 0.120713E+09 | 0.00 | 0.71 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 | 6291.07 | 14-SEP-14:00 | 5498.28 | 14-SEP-16:20 | 1417.28 | 23-SEP-14:00 | 1259.53 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 27571807.42 | 6144689.23 | 10.50 | 27571798.89 | 8.53 | 0.00 | 0.29 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2121.63 | 04-OCT-15:00 | 2121.63 | 04-OCT-15:00 | 0.00 | 06-OCT-09:00 | 466.31 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 1105898.71 | 258653.19 | 2.17 | 877632.18 | 228266.52 | 0.00 | 0.05 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 360.98 | 04-NOV-14:00 | 286.27 | 04-NOV-14:00 | 74.71 | 04-NOV-14:00 | 84.03 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.810063E+10 | 0.171951E+10 | 763.78 | 0.738474E+10 | 0.715898E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.324834E+10 | 0.684608E+09 | 229.11 | 0.293238E+10 | 0.315961E+09 | 0.00 | 0.95 | 0.00 | 8577.35 | 8373.33 | 1642.51 | 1834.40 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 1654.60 | 388.80 | 2.83 | 1654.60 | -0.0 | 0.00 | 0.00 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 0.73 | 18-MAR-14:00 | 0.73 | 18-MAR-14:00 | 0.00 | 18-MAR-15:20 | 0.17 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.226759E+09 | 50763510.11 | 24.00 | 0.222830E+09 | 3929061.29 | 0.00 | 0.62 | 27-APR-16:10 | 0.00 | 01-APR-00:10 | 5165.89 | 27-APR-16:10 | 5076.62 | 27-APR-16:10 | 199.32 | 27-APR-17:00 | 1127.80 | 27-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 0.443149E+09 | 95957776.03 | 60.17 | 0.409531E+09 | 33617854.10 | 0.00 | 0.64 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 5505.16 | 06-MAY-13:00 | 4634.42 | 06-MAY-13:00 | 897.10 | 06-MAY-12:50 | 1127.16 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.839934E+09 | 0.181806E+09 | 111.50 | 0.820681E+09 | 19252920.15 | 0.00 | 0.69 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5840.89 | 28-JUN-17:00 | 5830.63 | 28-JUN-17:00 | 365.59 | 21-JUN-17:10 | 1243.91 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.218968E+10 | 0.465702E+09 | 201.67 | 0.198407E+10 | 0.205611E+09 | 0.00 | 0.87 | 31-JUL-16:10 | 0.00 | 01-JUL-00:10 | 7898.69 | 31-JUL-16:10 | 7224.89 | 24-JUL-15:00 | 1117.52 | 27-JUL-18:40 | 1632.83 | 31-JUL-16:10 | 0.00 | 01-JUL-00:10 |
August | 0.312987E+10 | 0.661987E+09 | 221.11 | 0.282540E+10 | 0.304472E+09 | 0.00 | 0.94 | 10-AUG-16:30 | 0.00 | 01-AUG-00:10 | 8456.14 | 10-AUG-16:10 | 8251.25 | 10-AUG-16:30 | 1593.06 | 30-AUG-13:00 | 1814.19 | 10-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.819423E+09 | 0.173039E+09 | 89.42 | 0.706286E+09 | 0.113137E+09 | 0.00 | 0.70 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 | 6130.83 | 14-SEP-14:00 | 5367.40 | 14-SEP-16:20 | 1357.15 | 23-SEP-14:00 | 1232.88 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 22463279.80 | 5045127.61 | 8.67 | 22463159.78 | 120.02 | 0.00 | 0.26 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1876.61 | 04-OCT-15:00 | 1876.61 | 04-OCT-15:00 | 0.03 | 01-OCT-15:00 | 415.96 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 64.34 | 15.15 | 0.33 | 53.01 | 11.33 | 0.00 | 0.00 | 04-NOV-17:00 | 0.00 | 01-NOV-00:10 | 0.07 | 04-NOV-17:00 | 0.06 | 04-NOV-17:00 | 0.01 | 04-NOV-17:00 | 0.02 | 04-NOV-17:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.767128E+10 | 0.163430E+10 | 719.69 | 0.699126E+10 | 0.680020E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.312987E+10 | 0.661987E+09 | 221.11 | 0.282540E+10 | 0.304472E+09 | 0.00 | 0.94 | 0.00 | 8456.14 | 8251.25 | 1593.06 | 1814.19 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.324572E+09 | 83482464.52 | 22.50 | 0.307119E+09 | 17453475.96 | 0.00 | 0.67 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 8577.20 | 27-APR-15:00 | 7905.44 | 27-APR-15:00 | 690.82 | 27-APR-17:00 | 2117.31 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.685186E+09 | 0.169928E+09 | 52.83 | 0.605492E+09 | 79693885.06 | 0.00 | 0.66 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 8567.90 | 06-MAY-13:30 | 6863.95 | 06-MAY-14:10 | 1773.00 | 06-MAY-13:10 | 2003.12 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.146675E+10 | 0.362940E+09 | 108.67 | 0.137493E+10 | 91814739.24 | 0.00 | 0.76 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 9837.92 | 28-JUN-17:00 | 9322.84 | 28-JUN-17:00 | 961.35 | 21-JUN-17:00 | 2354.31 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.397885E+10 | 0.956195E+09 | 208.50 | 0.341006E+10 | 0.568788E+09 | 0.00 | 1.00 | 24-JUL-14:40 | 0.00 | 01-JUL-00:10 | 14449.86 | 24-JUL-15:00 | 13575.14 | 24-JUL-15:00 | 2499.24 | 27-JUL-17:00 | 3399.76 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.558888E+10 | 0.133228E+10 | 242.08 | 0.478877E+10 | 0.800111E+09 | 0.00 | 1.00 | 10-AUG-14:10 | 0.00 | 01-AUG-00:10 | 15601.90 | 29-AUG-15:00 | 14261.53 | 10-AUG-16:30 | 3091.52 | 30-AUG-13:00 | 3648.07 | 29-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.150475E+10 | 0.359984E+09 | 92.50 | 0.121814E+10 | 0.286610E+09 | 0.00 | 0.77 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 10440.85 | 14-SEP-14:10 | 8456.13 | 12-SEP-14:30 | 2775.46 | 14-SEP-13:00 | 2356.98 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 44177982.40 | 11234970.94 | 6.00 | 44157358.55 | 20623.84 | 0.00 | 0.33 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3633.50 | 04-OCT-15:00 | 3633.50 | 04-OCT-15:00 | 34.37 | 08-OCT-14:10 | 906.44 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 1092631.52 | 293508.59 | 1.17 | 814837.30 | 277794.21 | 0.00 | 0.03 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 315.85 | 04-NOV-14:40 | 235.75 | 04-NOV-14:40 | 80.10 | 04-NOV-14:40 | 84.78 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.135943E+11 | 0.327633E+10 | 734.25 | 0.117495E+11 | 0.184477E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.558888E+10 | 0.133228E+10 | 242.08 | 0.478877E+10 | 0.800111E+09 | 0.00 | 1.00 | 0.00 | 15601.90 | 14261.53 | 3091.52 | 3648.07 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 211.21 | 49.59 | 0.50 | 211.21 | -0.0 | 0.00 | 0.00 | 18-MAR-15:40 | 0.00 | 01-MAR-00:10 | 0.14 | 18-MAR-15:40 | 0.14 | 18-MAR-15:40 | 0.00 | 01-MAR-00:10 | 0.03 | 18-MAR-15:40 | 0.00 | 01-MAR-00:10 |
April | 0.188908E+09 | 42245208.50 | 22.50 | 0.184187E+09 | 4721017.06 | 0.00 | 0.67 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 4842.10 | 27-APR-15:00 | 4629.82 | 27-APR-15:00 | 238.21 | 27-APR-17:00 | 1043.19 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.364617E+09 | 78721451.98 | 47.83 | 0.334579E+09 | 30038185.40 | 0.00 | 0.65 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 4831.00 | 06-MAY-13:30 | 4065.38 | 06-MAY-14:10 | 798.83 | 06-MAY-13:20 | 985.41 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.745757E+09 | 0.160901E+09 | 99.67 | 0.727243E+09 | 18513571.29 | 0.00 | 0.74 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5451.89 | 28-JUN-17:00 | 5348.72 | 28-JUN-17:00 | 335.71 | 21-JUN-17:00 | 1142.56 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.203778E+10 | 0.428525E+09 | 186.75 | 0.183048E+10 | 0.207299E+09 | 0.00 | 0.99 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 | 7917.79 | 24-JUL-15:00 | 7574.18 | 24-JUL-15:00 | 1156.09 | 27-JUL-17:00 | 1630.83 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.298344E+10 | 0.621829E+09 | 218.58 | 0.266577E+10 | 0.317669E+09 | 0.00 | 1.00 | 10-AUG-14:10 | 0.00 | 01-AUG-00:10 | 8555.06 | 29-AUG-15:00 | 7896.71 | 10-AUG-16:40 | 1471.95 | 30-AUG-13:00 | 1755.87 | 29-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.735677E+09 | 0.153912E+09 | 79.33 | 0.630199E+09 | 0.105478E+09 | 0.00 | 0.75 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 5764.55 | 14-SEP-14:10 | 4910.62 | 12-SEP-14:30 | 1264.47 | 23-SEP-14:00 | 1140.38 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 18921542.06 | 4236189.66 | 7.00 | 18920020.99 | 1521.06 | 0.00 | 0.30 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1889.49 | 04-OCT-15:00 | 1889.49 | 04-OCT-15:00 | 1.93 | 05-OCT-18:00 | 414.19 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 3222.14 | 757.57 | 0.33 | 2587.22 | 634.92 | 0.00 | 0.00 | 04-NOV-16:50 | 0.00 | 01-NOV-00:10 | 5.34 | 04-NOV-16:50 | 4.29 | 04-NOV-16:50 | 1.05 | 04-NOV-16:50 | 1.26 | 04-NOV-16:50 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.707510E+10 | 0.149037E+10 | 662.50 | 0.639138E+10 | 0.683721E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.298344E+10 | 0.621829E+09 | 218.58 | 0.266577E+10 | 0.317669E+09 | 0.00 | 1.00 | 0.00 | 8555.06 | 7896.71 | 1471.95 | 1755.87 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.183074E+09 | 41001971.25 | 22.33 | 0.178594E+09 | 4480162.64 | 0.00 | 0.66 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 4753.88 | 27-APR-15:00 | 4549.80 | 27-APR-15:00 | 230.41 | 27-APR-17:00 | 1025.93 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.350544E+09 | 75807482.71 | 47.17 | 0.321781E+09 | 28763100.15 | 0.00 | 0.64 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 4729.58 | 06-MAY-13:30 | 3985.36 | 06-MAY-14:10 | 780.60 | 06-MAY-13:20 | 966.77 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.724472E+09 | 0.156471E+09 | 99.33 | 0.707001E+09 | 17471727.48 | 0.00 | 0.73 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5383.70 | 28-JUN-17:00 | 5287.67 | 28-JUN-17:00 | 326.01 | 21-JUN-17:00 | 1129.22 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.199847E+10 | 0.420529E+09 | 184.08 | 0.179665E+10 | 0.201813E+09 | 0.00 | 0.99 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 | 7847.52 | 24-JUL-15:00 | 7514.36 | 24-JUL-15:00 | 1143.09 | 27-JUL-17:00 | 1616.63 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.293863E+10 | 0.612757E+09 | 215.17 | 0.262781E+10 | 0.310817E+09 | 0.00 | 1.00 | 10-AUG-14:10 | 0.00 | 01-AUG-00:10 | 8484.39 | 29-AUG-15:00 | 7846.16 | 10-AUG-17:00 | 1447.96 | 30-AUG-13:00 | 1740.87 | 29-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.720035E+09 | 0.150753E+09 | 79.00 | 0.617318E+09 | 0.102717E+09 | 0.00 | 0.75 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 5695.97 | 14-SEP-14:10 | 4848.52 | 12-SEP-14:30 | 1239.40 | 23-SEP-14:00 | 1127.65 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 17644885.07 | 3958144.99 | 6.17 | 17643499.76 | 1385.31 | 0.00 | 0.29 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1816.10 | 04-OCT-15:00 | 1816.10 | 04-OCT-15:00 | 1.98 | 06-OCT-10:50 | 399.05 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 2668.94 | 627.09 | 0.33 | 2099.52 | 569.42 | 0.00 | 0.00 | 04-NOV-12:40 | 0.00 | 01-NOV-00:10 | 4.31 | 04-NOV-12:40 | 3.39 | 04-NOV-12:40 | 0.92 | 04-NOV-12:40 | 1.01 | 04-NOV-12:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.693287E+10 | 0.146128E+10 | 653.58 | 0.626681E+10 | 0.666064E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.293863E+10 | 0.612757E+09 | 215.17 | 0.262781E+10 | 0.310817E+09 | 0.00 | 1.00 | 0.00 | 8484.39 | 7846.16 | 1447.96 | 1740.87 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.165886E+09 | 37368349.84 | 21.33 | 0.161878E+09 | 4007666.59 | 0.00 | 0.64 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 4531.65 | 27-APR-15:00 | 4335.84 | 27-APR-15:00 | 220.58 | 27-APR-17:00 | 983.50 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.311213E+09 | 67657805.87 | 44.67 | 0.285507E+09 | 25706212.31 | 0.00 | 0.62 | 06-MAY-13:40 | 0.00 | 01-MAY-00:10 | 4481.19 | 06-MAY-13:30 | 3771.10 | 06-MAY-14:10 | 745.69 | 06-MAY-13:20 | 921.88 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.665115E+09 | 0.144134E+09 | 94.83 | 0.649518E+09 | 15596692.34 | 0.00 | 0.72 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5228.55 | 28-JUN-17:00 | 5135.24 | 28-JUN-17:00 | 312.47 | 21-JUN-17:00 | 1099.93 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.189650E+10 | 0.399901E+09 | 176.83 | 0.170543E+10 | 0.191078E+09 | 0.00 | 0.99 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 | 7728.34 | 24-JUL-15:00 | 7400.94 | 24-JUL-15:00 | 1122.47 | 27-JUL-17:00 | 1592.88 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.283645E+10 | 0.592161E+09 | 208.08 | 0.253591E+10 | 0.300541E+09 | 0.00 | 1.00 | 10-AUG-14:10 | 0.00 | 01-AUG-00:10 | 8345.59 | 29-AUG-15:00 | 7767.99 | 10-AUG-17:00 | 1402.73 | 30-AUG-13:00 | 1711.15 | 29-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.677805E+09 | 0.142281E+09 | 75.08 | 0.581013E+09 | 96792471.56 | 0.00 | 0.74 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 5564.38 | 14-SEP-14:10 | 4709.45 | 12-SEP-14:40 | 1204.81 | 14-SEP-13:00 | 1103.72 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 13363878.66 | 3019897.24 | 5.67 | 13362986.69 | 891.97 | 0.00 | 0.26 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1575.51 | 04-OCT-15:00 | 1575.51 | 04-OCT-15:00 | 1.49 | 09-OCT-14:50 | 349.30 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.656634E+10 | 0.138652E+10 | 626.50 | 0.593262E+10 | 0.633723E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.283645E+10 | 0.592161E+09 | 208.08 | 0.253591E+10 | 0.300541E+09 | 0.00 | 1.00 | 0.00 | 8345.59 | 7767.99 | 1402.73 | 1711.15 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.152219E+09 | 34492694.33 | 20.17 | 0.148530E+09 | 3689083.85 | 0.00 | 0.62 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 4530.09 | 27-APR-15:00 | 4322.01 | 27-APR-15:00 | 226.43 | 27-APR-17:00 | 989.22 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.280535E+09 | 61413972.73 | 39.33 | 0.257607E+09 | 22927757.24 | 0.00 | 0.60 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 4478.11 | 06-MAY-13:30 | 3734.59 | 06-MAY-13:40 | 754.20 | 06-MAY-13:20 | 926.67 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.632000E+09 | 0.137455E+09 | 88.25 | 0.616775E+09 | 15224691.63 | 0.00 | 0.70 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5190.66 | 28-JUN-17:00 | 5122.95 | 28-JUN-15:00 | 310.65 | 21-JUN-17:00 | 1100.84 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.187223E+10 | 0.395351E+09 | 169.39 | 0.168443E+10 | 0.187801E+09 | 0.00 | 0.99 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 | 8055.23 | 24-JUL-15:00 | 7693.27 | 24-JUL-15:00 | 1124.87 | 27-JUL-17:00 | 1659.37 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.292376E+10 | 0.609234E+09 | 197.92 | 0.261044E+10 | 0.313324E+09 | 0.00 | 1.00 | 10-AUG-14:10 | 0.00 | 01-AUG-00:10 | 8618.30 | 29-AUG-15:00 | 8037.93 | 10-AUG-16:30 | 1389.44 | 29-AUG-13:00 | 1767.71 | 29-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.667246E+09 | 0.140625E+09 | 75.75 | 0.569908E+09 | 97338475.92 | 0.00 | 0.74 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 5725.31 | 14-SEP-14:10 | 4813.95 | 14-SEP-14:10 | 1282.05 | 14-SEP-13:00 | 1137.63 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 7746144.26 | 1769889.62 | 7.00 | 7744647.07 | 1497.19 | 0.00 | 0.20 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1236.88 | 04-OCT-15:00 | 1236.88 | 04-OCT-15:00 | 0.99 | 06-OCT-16:30 | 278.66 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 36.25 | 8.52 | 0.17 | 28.26 | 7.99 | 0.00 | 0.00 | 04-NOV-13:10 | 0.00 | 01-NOV-00:10 | 0.06 | 04-NOV-13:10 | 0.05 | 04-NOV-13:10 | 0.01 | 04-NOV-13:10 | 0.01 | 04-NOV-13:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.653574E+10 | 0.138034E+10 | 597.97 | 0.589543E+10 | 0.640307E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.292376E+10 | 0.609234E+09 | 197.92 | 0.261044E+10 | 0.313324E+09 | 0.00 | 1.00 | 0.00 | 8618.30 | 8037.93 | 1389.44 | 1767.71 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.92 | 48.10 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.49 | 41.79 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 55.53 | 35.07 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 62.27 | 29.40 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 56.81 | 25.95 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 52.46 | 21.12 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.62 | 19.16 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.99 | 18.43 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 73.15 | 25.91 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 61.22 | 32.23 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 30.03 | 39.15 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.19 | 48.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.83 | 32.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.92 | 18.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 73.15 | 48.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.92 | 48.10 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.49 | 41.79 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 55.53 | 35.07 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 62.27 | 29.40 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 56.81 | 25.95 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 52.46 | 21.12 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.62 | 19.16 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.99 | 18.43 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 73.15 | 25.91 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 61.22 | 32.23 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 30.03 | 39.15 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.19 | 48.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.83 | 32.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.92 | 18.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 73.15 | 48.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.92 | 48.10 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.49 | 41.79 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 55.53 | 35.07 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 62.27 | 29.40 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 56.81 | 25.95 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 52.46 | 21.12 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.62 | 19.16 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.99 | 18.43 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 73.15 | 25.91 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 61.22 | 32.23 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 30.03 | 39.15 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.19 | 48.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.83 | 32.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.92 | 18.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 73.15 | 48.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.92 | 48.10 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.49 | 41.79 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 55.53 | 35.07 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 62.27 | 29.40 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 56.81 | 25.95 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 52.46 | 21.12 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.62 | 19.16 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.99 | 18.43 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 73.15 | 25.91 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 61.22 | 32.23 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 30.03 | 39.15 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.19 | 48.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.83 | 32.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.92 | 18.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 73.15 | 48.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.14 | 16.38 | 10.76 | 32.50 | 57.30 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 25.92 | 15.52 | 58.45 | 49.84 | 0.00 | 0.00 | 0.00 |
March | 43.91 | 23.46 | 20.45 | 66.88 | 41.84 | 0.00 | 0.00 | 0.00 |
April | 45.25 | 19.07 | 26.18 | 75.00 | 35.10 | 0.00 | 0.00 | 0.00 |
May | 40.90 | 11.20 | 29.70 | 68.42 | 30.99 | 0.00 | 0.00 | 0.00 |
June | 37.16 | 8.85 | 28.31 | 63.16 | 25.25 | 0.00 | 0.00 | 0.00 |
July | 40.28 | 13.53 | 26.75 | 76.51 | 22.92 | 0.00 | 0.00 | 0.00 |
August | 43.76 | 19.56 | 24.20 | 85.34 | 22.07 | 0.00 | 0.00 | 0.00 |
September | 49.55 | 27.05 | 22.50 | 87.94 | 31.00 | 0.00 | 0.00 | 0.00 |
October | 45.95 | 28.54 | 17.41 | 73.71 | 38.51 | 0.00 | 0.00 | 0.00 |
November | 27.47 | 15.98 | 11.49 | 36.20 | 46.69 | 0.00 | 0.00 | 0.00 |
December | 28.93 | 18.99 | 9.93 | 38.79 | 57.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.29 | 19.00 | 20.29 | 63.60 | 38.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.14 | 8.85 | 9.93 | 32.50 | 22.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.55 | 28.54 | 29.70 | 87.94 | 57.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.14 | 16.38 | 10.76 | 32.50 | 57.30 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 25.92 | 15.52 | 58.45 | 49.84 | 0.00 | 0.00 | 0.00 |
March | 43.91 | 23.46 | 20.45 | 66.88 | 41.84 | 0.00 | 0.00 | 0.00 |
April | 45.25 | 19.07 | 26.18 | 75.00 | 35.10 | 0.00 | 0.00 | 0.00 |
May | 40.90 | 11.20 | 29.70 | 68.42 | 30.99 | 0.00 | 0.00 | 0.00 |
June | 37.16 | 8.85 | 28.31 | 63.16 | 25.25 | 0.00 | 0.00 | 0.00 |
July | 40.28 | 13.53 | 26.75 | 76.51 | 22.92 | 0.00 | 0.00 | 0.00 |
August | 43.76 | 19.56 | 24.20 | 85.34 | 22.07 | 0.00 | 0.00 | 0.00 |
September | 49.55 | 27.05 | 22.50 | 87.94 | 31.00 | 0.00 | 0.00 | 0.00 |
October | 45.95 | 28.54 | 17.41 | 73.71 | 38.51 | 0.00 | 0.00 | 0.00 |
November | 27.47 | 15.98 | 11.49 | 36.20 | 46.69 | 0.00 | 0.00 | 0.00 |
December | 28.93 | 18.99 | 9.93 | 38.79 | 57.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.29 | 19.00 | 20.29 | 63.60 | 38.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.14 | 8.85 | 9.93 | 32.50 | 22.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.55 | 28.54 | 29.70 | 87.94 | 57.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.51 | 50.43 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 47.77 | 44.15 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 54.55 | 38.10 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 60.78 | 32.27 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 55.31 | 28.08 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 51.72 | 22.06 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.33 | 19.59 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.74 | 18.79 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 72.54 | 26.89 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 60.02 | 35.12 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 29.40 | 41.73 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 31.80 | 50.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.06 | 33.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.51 | 18.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 72.54 | 50.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.51 | 50.43 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 47.77 | 44.15 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 54.55 | 38.10 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 60.78 | 32.27 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 55.31 | 28.08 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 51.72 | 22.06 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.33 | 19.59 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.74 | 18.79 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 72.54 | 26.89 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 60.02 | 35.12 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 29.40 | 41.73 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 31.80 | 50.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.06 | 33.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.51 | 18.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 72.54 | 50.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.14 | 16.38 | 10.76 | 32.00 | 60.06 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 25.92 | 15.52 | 57.59 | 52.63 | 0.00 | 0.00 | 0.00 |
March | 43.91 | 23.46 | 20.45 | 65.72 | 45.43 | 0.00 | 0.00 | 0.00 |
April | 45.25 | 19.07 | 26.18 | 73.23 | 38.49 | 0.00 | 0.00 | 0.00 |
May | 40.90 | 11.20 | 29.70 | 66.64 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 37.16 | 8.85 | 28.31 | 62.29 | 26.36 | 0.00 | 0.00 | 0.00 |
July | 40.28 | 13.53 | 26.75 | 76.18 | 23.44 | 0.00 | 0.00 | 0.00 |
August | 43.76 | 19.56 | 24.20 | 85.05 | 22.51 | 0.00 | 0.00 | 0.00 |
September | 49.55 | 27.05 | 22.50 | 87.22 | 32.17 | 0.00 | 0.00 | 0.00 |
October | 45.95 | 28.54 | 17.41 | 72.29 | 41.93 | 0.00 | 0.00 | 0.00 |
November | 27.47 | 15.98 | 11.49 | 35.45 | 49.73 | 0.00 | 0.00 | 0.00 |
December | 28.93 | 18.99 | 9.93 | 38.32 | 60.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.29 | 19.00 | 20.29 | 62.69 | 40.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.14 | 8.85 | 9.93 | 32.00 | 22.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.55 | 28.54 | 29.70 | 87.22 | 60.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.59 | 49.54 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 47.89 | 43.41 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 54.63 | 37.54 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 60.79 | 32.08 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 55.15 | 28.57 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 51.57 | 22.82 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.16 | 20.53 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.60 | 19.81 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 72.46 | 27.65 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 60.01 | 35.15 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 29.49 | 41.10 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 31.89 | 50.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.04 | 33.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.59 | 19.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 72.46 | 50.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.59 | 49.54 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 47.89 | 43.41 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 54.63 | 37.54 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 60.79 | 32.08 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 55.15 | 28.57 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 51.57 | 22.82 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.16 | 20.53 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.60 | 19.81 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 72.46 | 27.65 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 60.01 | 35.15 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 29.49 | 41.10 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 31.89 | 50.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.04 | 33.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.59 | 19.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 72.46 | 50.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.99 | 16.29 | 10.70 | 31.92 | 58.69 | 0.00 | 0.00 | 0.00 |
February | 41.21 | 25.78 | 15.44 | 57.42 | 51.49 | 0.00 | 0.00 | 0.00 |
March | 43.67 | 23.33 | 20.34 | 65.45 | 44.53 | 0.00 | 0.00 | 0.00 |
April | 45.00 | 18.97 | 26.04 | 72.84 | 38.06 | 0.00 | 0.00 | 0.00 |
May | 40.68 | 11.14 | 29.54 | 66.08 | 33.91 | 0.00 | 0.00 | 0.00 |
June | 36.96 | 8.80 | 28.16 | 61.76 | 27.10 | 0.00 | 0.00 | 0.00 |
July | 40.06 | 13.45 | 26.60 | 75.55 | 24.41 | 0.00 | 0.00 | 0.00 |
August | 43.53 | 19.45 | 24.07 | 84.41 | 23.58 | 0.00 | 0.00 | 0.00 |
September | 49.28 | 26.91 | 22.38 | 86.64 | 32.88 | 0.00 | 0.00 | 0.00 |
October | 45.70 | 28.38 | 17.32 | 71.89 | 41.74 | 0.00 | 0.00 | 0.00 |
November | 27.32 | 15.89 | 11.43 | 35.37 | 48.73 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.89 | 9.88 | 38.23 | 59.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.07 | 18.90 | 20.18 | 62.32 | 40.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.99 | 8.80 | 9.88 | 31.92 | 23.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.28 | 28.38 | 29.54 | 86.64 | 59.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.65 | 48.99 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.00 | 42.90 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 54.77 | 36.96 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 61.01 | 31.53 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 55.27 | 28.29 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 51.61 | 22.70 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.17 | 20.48 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.60 | 19.80 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 72.49 | 27.51 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 60.18 | 34.59 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 29.61 | 40.50 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 31.95 | 49.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.13 | 33.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.65 | 19.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 72.49 | 49.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.65 | 48.99 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.00 | 42.90 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 54.77 | 36.96 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 61.01 | 31.53 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 55.27 | 28.29 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 51.61 | 22.70 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.17 | 20.48 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.60 | 19.80 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 72.49 | 27.51 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 60.18 | 34.59 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 29.61 | 40.50 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 31.95 | 49.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.13 | 33.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.65 | 19.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 72.49 | 49.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.99 | 16.29 | 10.70 | 31.99 | 58.04 | 0.00 | 0.00 | 0.00 |
February | 41.21 | 25.78 | 15.44 | 57.56 | 50.87 | 0.00 | 0.00 | 0.00 |
March | 43.67 | 23.33 | 20.34 | 65.63 | 43.85 | 0.00 | 0.00 | 0.00 |
April | 45.00 | 18.97 | 26.04 | 73.11 | 37.41 | 0.00 | 0.00 | 0.00 |
May | 40.68 | 11.14 | 29.54 | 66.23 | 33.57 | 0.00 | 0.00 | 0.00 |
June | 36.96 | 8.80 | 28.16 | 61.81 | 26.97 | 0.00 | 0.00 | 0.00 |
July | 40.06 | 13.45 | 26.60 | 75.57 | 24.36 | 0.00 | 0.00 | 0.00 |
August | 43.53 | 19.45 | 24.07 | 84.41 | 23.57 | 0.00 | 0.00 | 0.00 |
September | 49.28 | 26.91 | 22.38 | 86.69 | 32.71 | 0.00 | 0.00 | 0.00 |
October | 45.70 | 28.38 | 17.32 | 72.09 | 41.08 | 0.00 | 0.00 | 0.00 |
November | 27.32 | 15.89 | 11.43 | 35.51 | 48.02 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.89 | 9.88 | 38.30 | 58.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.07 | 18.90 | 20.18 | 62.43 | 39.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.99 | 8.80 | 9.88 | 31.99 | 23.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.28 | 28.38 | 29.54 | 86.69 | 58.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.73 | 48.48 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.16 | 42.38 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 55.02 | 36.24 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 61.44 | 30.70 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 55.68 | 27.59 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 51.78 | 22.35 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.26 | 20.25 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.68 | 19.58 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 72.66 | 27.09 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 60.55 | 33.61 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 29.80 | 39.79 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.03 | 48.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.33 | 33.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.73 | 19.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 72.66 | 48.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.73 | 48.48 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.16 | 42.38 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 55.02 | 36.24 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 61.44 | 30.70 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 55.68 | 27.59 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 51.78 | 22.35 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.26 | 20.25 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.68 | 19.58 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 72.66 | 27.09 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 60.55 | 33.61 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 29.80 | 39.79 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.03 | 48.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.33 | 33.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.73 | 19.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 72.66 | 48.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.99 | 16.29 | 10.70 | 32.09 | 57.44 | 0.00 | 0.00 | 0.00 |
February | 41.21 | 25.78 | 15.44 | 57.75 | 50.26 | 0.00 | 0.00 | 0.00 |
March | 43.67 | 23.33 | 20.34 | 65.92 | 43.00 | 0.00 | 0.00 | 0.00 |
April | 45.00 | 18.97 | 26.04 | 73.63 | 36.43 | 0.00 | 0.00 | 0.00 |
May | 40.68 | 11.14 | 29.54 | 66.73 | 32.74 | 0.00 | 0.00 | 0.00 |
June | 36.96 | 8.80 | 28.16 | 62.03 | 26.56 | 0.00 | 0.00 | 0.00 |
July | 40.06 | 13.45 | 26.60 | 75.68 | 24.09 | 0.00 | 0.00 | 0.00 |
August | 43.53 | 19.45 | 24.07 | 84.51 | 23.31 | 0.00 | 0.00 | 0.00 |
September | 49.28 | 26.91 | 22.38 | 86.89 | 32.22 | 0.00 | 0.00 | 0.00 |
October | 45.70 | 28.38 | 17.32 | 72.53 | 39.93 | 0.00 | 0.00 | 0.00 |
November | 27.32 | 15.89 | 11.43 | 35.74 | 47.18 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.89 | 9.88 | 38.40 | 58.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.07 | 18.90 | 20.18 | 62.68 | 39.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.99 | 8.80 | 9.88 | 32.09 | 23.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.28 | 28.38 | 29.54 | 86.89 | 58.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.91 | 47.23 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.52 | 41.17 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 55.48 | 34.82 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 62.29 | 29.07 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 56.78 | 25.91 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 52.23 | 21.37 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.31 | 19.61 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.69 | 18.94 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 73.10 | 25.98 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 61.35 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 30.14 | 38.38 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.20 | 47.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.76 | 31.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.91 | 18.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 73.10 | 47.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.91 | 47.23 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.52 | 41.17 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 55.48 | 34.82 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 62.29 | 29.07 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 56.78 | 25.91 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 52.23 | 21.37 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.31 | 19.61 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.69 | 18.94 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 73.10 | 25.98 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 61.35 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 30.14 | 38.38 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.20 | 47.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.76 | 31.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.91 | 18.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 73.10 | 47.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.91 | 47.23 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.52 | 41.17 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 55.48 | 34.82 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 62.29 | 29.07 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 56.78 | 25.91 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 52.23 | 21.37 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.31 | 19.61 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.69 | 18.94 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 73.10 | 25.98 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 61.35 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 30.14 | 38.38 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.20 | 47.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.76 | 31.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.91 | 18.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 73.10 | 47.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.91 | 47.23 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.52 | 41.17 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 55.48 | 34.82 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 62.29 | 29.07 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 56.78 | 25.91 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 52.23 | 21.37 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.31 | 19.61 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.69 | 18.94 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 73.10 | 25.98 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 61.35 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 30.14 | 38.38 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.20 | 47.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.76 | 31.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.91 | 18.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 73.10 | 47.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.99 | 16.29 | 10.70 | 32.30 | 55.97 | 0.00 | 0.00 | 0.00 |
February | 41.21 | 25.78 | 15.44 | 58.16 | 48.84 | 0.00 | 0.00 | 0.00 |
March | 43.67 | 23.33 | 20.34 | 66.46 | 41.33 | 0.00 | 0.00 | 0.00 |
April | 45.00 | 18.97 | 26.04 | 74.61 | 34.51 | 0.00 | 0.00 | 0.00 |
May | 40.68 | 11.14 | 29.54 | 68.01 | 30.77 | 0.00 | 0.00 | 0.00 |
June | 36.96 | 8.80 | 28.16 | 62.54 | 25.40 | 0.00 | 0.00 | 0.00 |
July | 40.06 | 13.45 | 26.60 | 75.73 | 23.33 | 0.00 | 0.00 | 0.00 |
August | 43.53 | 19.45 | 24.07 | 84.51 | 22.55 | 0.00 | 0.00 | 0.00 |
September | 49.28 | 26.91 | 22.38 | 87.40 | 30.91 | 0.00 | 0.00 | 0.00 |
October | 45.70 | 28.38 | 17.32 | 73.46 | 37.72 | 0.00 | 0.00 | 0.00 |
November | 27.32 | 15.89 | 11.43 | 36.13 | 45.52 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.89 | 9.88 | 38.59 | 56.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.07 | 18.90 | 20.18 | 63.18 | 37.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.99 | 8.80 | 9.88 | 32.30 | 22.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.28 | 28.38 | 29.54 | 87.40 | 56.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.99 | 16.29 | 10.70 | 32.30 | 55.97 | 0.00 | 0.00 | 0.00 |
February | 41.21 | 25.78 | 15.44 | 58.16 | 48.84 | 0.00 | 0.00 | 0.00 |
March | 43.67 | 23.33 | 20.34 | 66.46 | 41.33 | 0.00 | 0.00 | 0.00 |
April | 45.00 | 18.97 | 26.04 | 74.61 | 34.51 | 0.00 | 0.00 | 0.00 |
May | 40.68 | 11.14 | 29.54 | 68.01 | 30.77 | 0.00 | 0.00 | 0.00 |
June | 36.96 | 8.80 | 28.16 | 62.54 | 25.40 | 0.00 | 0.00 | 0.00 |
July | 40.06 | 13.45 | 26.60 | 75.73 | 23.33 | 0.00 | 0.00 | 0.00 |
August | 43.53 | 19.45 | 24.07 | 84.51 | 22.55 | 0.00 | 0.00 | 0.00 |
September | 49.28 | 26.91 | 22.38 | 87.40 | 30.91 | 0.00 | 0.00 | 0.00 |
October | 45.70 | 28.38 | 17.32 | 73.46 | 37.72 | 0.00 | 0.00 | 0.00 |
November | 27.32 | 15.89 | 11.43 | 36.13 | 45.52 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.89 | 9.88 | 38.59 | 56.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.07 | 18.90 | 20.18 | 63.18 | 37.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.99 | 8.80 | 9.88 | 32.30 | 22.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.28 | 28.38 | 29.54 | 87.40 | 56.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.76 | 47.52 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.31 | 41.36 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 55.27 | 34.91 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 61.98 | 29.17 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 56.37 | 26.08 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 51.94 | 21.41 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.15 | 19.54 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.54 | 18.85 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 72.80 | 26.11 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 61.03 | 31.91 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 30.00 | 38.54 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.08 | 48.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.54 | 31.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.76 | 18.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 72.80 | 48.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.76 | 47.52 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.31 | 41.36 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 55.27 | 34.91 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 61.98 | 29.17 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 56.37 | 26.08 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 51.94 | 21.41 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.15 | 19.54 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.54 | 18.85 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 72.80 | 26.11 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 61.03 | 31.91 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 30.00 | 38.54 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.08 | 48.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.54 | 31.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.76 | 18.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 72.80 | 48.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.99 | 16.29 | 10.70 | 32.13 | 56.29 | 0.00 | 0.00 | 0.00 |
February | 41.21 | 25.78 | 15.44 | 57.93 | 49.05 | 0.00 | 0.00 | 0.00 |
March | 43.67 | 23.33 | 20.34 | 66.23 | 41.42 | 0.00 | 0.00 | 0.00 |
April | 45.00 | 18.97 | 26.04 | 74.27 | 34.62 | 0.00 | 0.00 | 0.00 |
May | 40.68 | 11.14 | 29.54 | 67.55 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 36.96 | 8.80 | 28.16 | 62.21 | 25.45 | 0.00 | 0.00 | 0.00 |
July | 40.06 | 13.45 | 26.60 | 75.56 | 23.24 | 0.00 | 0.00 | 0.00 |
August | 43.53 | 19.45 | 24.07 | 84.35 | 22.44 | 0.00 | 0.00 | 0.00 |
September | 49.28 | 26.91 | 22.38 | 87.07 | 31.05 | 0.00 | 0.00 | 0.00 |
October | 45.70 | 28.38 | 17.32 | 73.10 | 37.90 | 0.00 | 0.00 | 0.00 |
November | 27.32 | 15.89 | 11.43 | 35.98 | 45.69 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.89 | 9.88 | 38.46 | 56.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.07 | 18.90 | 20.18 | 62.92 | 37.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.99 | 8.80 | 9.88 | 32.13 | 22.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.28 | 28.38 | 29.54 | 87.07 | 56.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.78 | 47.39 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.35 | 41.23 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 55.33 | 34.74 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 62.07 | 28.99 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 56.51 | 25.87 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 52.03 | 21.28 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.21 | 19.44 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.58 | 18.76 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 72.86 | 25.98 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 61.11 | 31.72 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 30.03 | 38.38 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.10 | 47.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.60 | 31.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.78 | 18.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 72.86 | 47.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.78 | 47.39 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.35 | 41.23 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 55.33 | 34.74 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 62.07 | 28.99 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 56.51 | 25.87 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 52.03 | 21.28 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.21 | 19.44 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.58 | 18.76 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 72.86 | 25.98 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 61.11 | 31.72 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 30.03 | 38.38 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.10 | 47.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.60 | 31.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.78 | 18.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 72.86 | 47.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.99 | 16.29 | 10.70 | 32.15 | 56.14 | 0.00 | 0.00 | 0.00 |
February | 41.21 | 25.78 | 15.44 | 57.98 | 48.89 | 0.00 | 0.00 | 0.00 |
March | 43.67 | 23.33 | 20.34 | 66.30 | 41.21 | 0.00 | 0.00 | 0.00 |
April | 45.00 | 18.97 | 26.04 | 74.38 | 34.41 | 0.00 | 0.00 | 0.00 |
May | 40.68 | 11.14 | 29.54 | 67.71 | 30.71 | 0.00 | 0.00 | 0.00 |
June | 36.96 | 8.80 | 28.16 | 62.32 | 25.29 | 0.00 | 0.00 | 0.00 |
July | 40.06 | 13.45 | 26.60 | 75.62 | 23.13 | 0.00 | 0.00 | 0.00 |
August | 43.53 | 19.45 | 24.07 | 84.41 | 22.34 | 0.00 | 0.00 | 0.00 |
September | 49.28 | 26.91 | 22.38 | 87.14 | 30.91 | 0.00 | 0.00 | 0.00 |
October | 45.70 | 28.38 | 17.32 | 73.20 | 37.68 | 0.00 | 0.00 | 0.00 |
November | 27.32 | 15.89 | 11.43 | 36.02 | 45.51 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.89 | 9.88 | 38.48 | 56.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.07 | 18.90 | 20.18 | 63.00 | 37.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.99 | 8.80 | 9.88 | 32.15 | 22.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.28 | 28.38 | 29.54 | 87.14 | 56.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.86 | 46.75 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.50 | 40.61 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 55.50 | 34.08 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 62.35 | 28.33 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 57.00 | 25.09 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 52.34 | 20.79 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.37 | 19.11 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.70 | 18.50 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 73.11 | 25.46 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 61.38 | 31.01 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 30.15 | 37.81 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.18 | 47.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.80 | 31.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.86 | 18.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 73.11 | 47.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 26.86 | 46.75 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 48.50 | 40.61 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 55.50 | 34.08 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 62.35 | 28.33 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 57.00 | 25.09 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 52.34 | 20.79 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.37 | 19.11 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.70 | 18.50 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 73.11 | 25.46 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 61.38 | 31.01 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 30.15 | 37.81 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.18 | 47.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 52.80 | 31.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 26.86 | 18.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 73.11 | 47.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.99 | 16.29 | 10.70 | 32.26 | 55.38 | 0.00 | 0.00 | 0.00 |
February | 41.21 | 25.78 | 15.44 | 58.17 | 48.16 | 0.00 | 0.00 | 0.00 |
March | 43.67 | 23.33 | 20.34 | 66.51 | 40.43 | 0.00 | 0.00 | 0.00 |
April | 45.00 | 18.97 | 26.04 | 74.72 | 33.63 | 0.00 | 0.00 | 0.00 |
May | 40.68 | 11.14 | 29.54 | 68.29 | 29.79 | 0.00 | 0.00 | 0.00 |
June | 36.96 | 8.80 | 28.16 | 62.70 | 24.71 | 0.00 | 0.00 | 0.00 |
July | 40.06 | 13.45 | 26.60 | 75.82 | 22.73 | 0.00 | 0.00 | 0.00 |
August | 43.53 | 19.45 | 24.07 | 84.55 | 22.03 | 0.00 | 0.00 | 0.00 |
September | 49.28 | 26.91 | 22.38 | 87.43 | 30.29 | 0.00 | 0.00 | 0.00 |
October | 45.70 | 28.38 | 17.32 | 73.53 | 36.85 | 0.00 | 0.00 | 0.00 |
November | 27.32 | 15.89 | 11.43 | 36.17 | 44.83 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.89 | 9.88 | 38.59 | 56.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.07 | 18.90 | 20.18 | 63.25 | 37.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.99 | 8.80 | 9.88 | 32.26 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.28 | 28.38 | 29.54 | 87.43 | 56.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 27.22 | 44.09 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 49.05 | 38.15 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 56.03 | 31.71 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 62.98 | 26.23 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 57.92 | 22.99 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 53.05 | 19.25 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.78 | 17.92 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.96 | 17.51 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 73.66 | 23.95 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 61.96 | 29.06 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 30.50 | 35.80 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.51 | 44.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 53.32 | 29.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 27.22 | 17.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 73.66 | 44.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.58 | 13.62 | 8.95 | 27.22 | 44.09 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 21.56 | 12.91 | 49.05 | 38.15 | 0.00 | 0.00 | 0.00 |
March | 36.53 | 19.51 | 17.01 | 56.03 | 31.71 | 0.00 | 0.00 | 0.00 |
April | 37.64 | 15.86 | 21.78 | 62.98 | 26.23 | 0.00 | 0.00 | 0.00 |
May | 34.03 | 9.32 | 24.71 | 57.92 | 22.99 | 0.00 | 0.00 | 0.00 |
June | 30.91 | 7.36 | 23.55 | 53.05 | 19.25 | 0.00 | 0.00 | 0.00 |
July | 33.50 | 11.25 | 22.25 | 63.78 | 17.92 | 0.00 | 0.00 | 0.00 |
August | 36.40 | 16.27 | 20.13 | 70.96 | 17.51 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 22.50 | 18.72 | 73.66 | 23.95 | 0.00 | 0.00 | 0.00 |
October | 38.23 | 23.74 | 14.48 | 61.96 | 29.06 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 13.29 | 9.56 | 30.50 | 35.80 | 0.00 | 0.00 | 0.00 |
December | 24.06 | 15.80 | 8.26 | 32.51 | 44.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.68 | 15.81 | 16.88 | 53.32 | 29.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.58 | 7.36 | 8.26 | 27.22 | 17.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.22 | 23.74 | 24.71 | 73.66 | 44.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.99 | 16.29 | 10.70 | 32.70 | 52.23 | 0.00 | 0.00 | 0.00 |
February | 41.21 | 25.78 | 15.44 | 58.84 | 45.24 | 0.00 | 0.00 | 0.00 |
March | 43.67 | 23.33 | 20.34 | 67.15 | 37.63 | 0.00 | 0.00 | 0.00 |
April | 45.00 | 18.97 | 26.04 | 75.47 | 31.15 | 0.00 | 0.00 | 0.00 |
May | 40.68 | 11.14 | 29.54 | 69.39 | 27.32 | 0.00 | 0.00 | 0.00 |
June | 36.96 | 8.80 | 28.16 | 63.54 | 22.89 | 0.00 | 0.00 | 0.00 |
July | 40.06 | 13.45 | 26.60 | 76.31 | 21.33 | 0.00 | 0.00 | 0.00 |
August | 43.53 | 19.45 | 24.07 | 84.86 | 20.87 | 0.00 | 0.00 | 0.00 |
September | 49.28 | 26.91 | 22.38 | 88.09 | 28.50 | 0.00 | 0.00 | 0.00 |
October | 45.70 | 28.38 | 17.32 | 74.22 | 34.54 | 0.00 | 0.00 | 0.00 |
November | 27.32 | 15.89 | 11.43 | 36.59 | 42.44 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.89 | 9.88 | 38.98 | 53.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.07 | 18.90 | 20.18 | 63.86 | 34.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.99 | 8.80 | 9.88 | 32.70 | 20.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.28 | 28.38 | 29.54 | 88.09 | 53.25 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 72115091.26 | 0.128837E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.117314E+09 | 0.101103E+09 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.148736E+09 | 93926681.40 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.161415E+09 | 76204472.17 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.152164E+09 | 69501178.41 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.135982E+09 | 54753999.78 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.170406E+09 | 51309616.74 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.190149E+09 | 49355731.82 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.189616E+09 | 67152218.31 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.163972E+09 | 86326069.30 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 77846519.99 | 0.101480E+09 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 86215533.75 | 0.129808E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.166593E+10 | 0.100976E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 72115091.26 | 49355731.82 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.190149E+09 | 0.129808E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 72115091.26 | 0.128837E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.117314E+09 | 0.101103E+09 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.148736E+09 | 93926681.40 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.161415E+09 | 76204472.17 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.152164E+09 | 69501178.41 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.135982E+09 | 54753999.78 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.170406E+09 | 51309616.74 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.190149E+09 | 49355731.82 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.189616E+09 | 67152218.31 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.163972E+09 | 86326069.30 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 77846519.99 | 0.101480E+09 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 86215533.75 | 0.129808E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.166593E+10 | 0.100976E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 72115091.26 | 49355731.82 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.190149E+09 | 0.129808E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 72115091.26 | 0.128837E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.117314E+09 | 0.101103E+09 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.148736E+09 | 93926681.40 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.161415E+09 | 76204472.17 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.152164E+09 | 69501178.41 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.135982E+09 | 54753999.78 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.170406E+09 | 51309616.74 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.190149E+09 | 49355731.82 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.189616E+09 | 67152218.31 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.163972E+09 | 86326069.30 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 77846519.99 | 0.101480E+09 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 86215533.75 | 0.129808E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.166593E+10 | 0.100976E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 72115091.26 | 49355731.82 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.190149E+09 | 0.129808E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 72115091.26 | 0.128837E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.117314E+09 | 0.101103E+09 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.148736E+09 | 93926681.40 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.161415E+09 | 76204472.17 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.152164E+09 | 69501178.41 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.135982E+09 | 54753999.78 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.170406E+09 | 51309616.74 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.190149E+09 | 49355731.82 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.189616E+09 | 67152218.31 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.163972E+09 | 86326069.30 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 77846519.99 | 0.101480E+09 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 86215533.75 | 0.129808E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.166593E+10 | 0.100976E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 72115091.26 | 49355731.82 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.190149E+09 | 0.129808E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72690476.28 | 43870228.98 | 28820247.30 | 87035339.70 | 0.153485E+09 |
February | 0.100251E+09 | 62703672.62 | 37547525.70 | 0.141404E+09 | 0.120571E+09 |
March | 0.117607E+09 | 62827491.38 | 54779625.78 | 0.179141E+09 | 0.112073E+09 |
April | 0.117288E+09 | 49432594.19 | 67855290.87 | 0.194409E+09 | 90970949.19 |
May | 0.109557E+09 | 30001094.82 | 79555911.55 | 0.183248E+09 | 83007804.98 |
June | 96322631.87 | 22932795.95 | 73389835.93 | 0.163710E+09 | 65452117.24 |
July | 0.107879E+09 | 36229739.62 | 71649523.96 | 0.204933E+09 | 61402078.64 |
August | 0.117218E+09 | 52394325.82 | 64824131.57 | 0.228570E+09 | 59124305.31 |
September | 0.128441E+09 | 70125190.19 | 58316077.12 | 0.227948E+09 | 80355191.95 |
October | 0.123080E+09 | 76441910.71 | 46637896.90 | 0.197416E+09 | 0.103150E+09 |
November | 71195678.71 | 41418441.13 | 29777237.58 | 93838238.57 | 0.121011E+09 |
December | 77484467.81 | 50875001.26 | 26609466.55 | 0.103888E+09 | 0.154789E+09 |
Annual Sum or Average | 0.123902E+10 | 0.599252E+09 | 0.639763E+09 | 0.200554E+10 | 0.120539E+10 |
Minimum of Months | 71195678.71 | 22932795.95 | 26609466.55 | 87035339.70 | 59124305.31 |
Maximum of Months | 0.128441E+09 | 76441910.71 | 79555911.55 | 0.228570E+09 | 0.154789E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72690476.28 | 43870228.98 | 28820247.30 | 87035339.70 | 0.153485E+09 |
February | 0.100251E+09 | 62703672.62 | 37547525.70 | 0.141404E+09 | 0.120571E+09 |
March | 0.117607E+09 | 62827491.38 | 54779625.78 | 0.179141E+09 | 0.112073E+09 |
April | 0.117288E+09 | 49432594.19 | 67855290.87 | 0.194409E+09 | 90970949.19 |
May | 0.109557E+09 | 30001094.82 | 79555911.55 | 0.183248E+09 | 83007804.98 |
June | 96322631.87 | 22932795.95 | 73389835.93 | 0.163710E+09 | 65452117.24 |
July | 0.107879E+09 | 36229739.62 | 71649523.96 | 0.204933E+09 | 61402078.64 |
August | 0.117218E+09 | 52394325.82 | 64824131.57 | 0.228570E+09 | 59124305.31 |
September | 0.128441E+09 | 70125190.19 | 58316077.12 | 0.227948E+09 | 80355191.95 |
October | 0.123080E+09 | 76441910.71 | 46637896.90 | 0.197416E+09 | 0.103150E+09 |
November | 71195678.71 | 41418441.13 | 29777237.58 | 93838238.57 | 0.121011E+09 |
December | 77484467.81 | 50875001.26 | 26609466.55 | 0.103888E+09 | 0.154789E+09 |
Annual Sum or Average | 0.123902E+10 | 0.599252E+09 | 0.639763E+09 | 0.200554E+10 | 0.120539E+10 |
Minimum of Months | 71195678.71 | 22932795.95 | 26609466.55 | 87035339.70 | 59124305.31 |
Maximum of Months | 0.128441E+09 | 76441910.71 | 79555911.55 | 0.228570E+09 | 0.154789E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 71009662.27 | 0.135060E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.115557E+09 | 0.106812E+09 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.146120E+09 | 0.102047E+09 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.157531E+09 | 83638503.47 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.148139E+09 | 75199815.57 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.134068E+09 | 57187543.73 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169626E+09 | 52481892.42 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.189475E+09 | 50331124.87 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.188027E+09 | 69701457.65 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.160762E+09 | 94072558.72 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 76208335.40 | 0.108156E+09 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 85169011.00 | 0.136054E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.164169E+10 | 0.107074E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 71009662.27 | 50331124.87 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.189475E+09 | 0.136054E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 71009662.27 | 0.135060E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.115557E+09 | 0.106812E+09 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.146120E+09 | 0.102047E+09 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.157531E+09 | 83638503.47 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.148139E+09 | 75199815.57 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.134068E+09 | 57187543.73 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169626E+09 | 52481892.42 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.189475E+09 | 50331124.87 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.188027E+09 | 69701457.65 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.160762E+09 | 94072558.72 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 76208335.40 | 0.108156E+09 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 85169011.00 | 0.136054E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.164169E+10 | 0.107074E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 71009662.27 | 50331124.87 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.189475E+09 | 0.136054E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72690476.28 | 43870228.98 | 28820247.30 | 85713634.84 | 0.160865E+09 |
February | 0.100251E+09 | 62703672.62 | 37547525.70 | 0.139318E+09 | 0.127330E+09 |
March | 0.117607E+09 | 62827491.38 | 54779625.78 | 0.176035E+09 | 0.121681E+09 |
April | 0.117288E+09 | 49432594.19 | 67855290.87 | 0.189814E+09 | 99754172.88 |
May | 0.109557E+09 | 30001094.82 | 79555911.55 | 0.178485E+09 | 89747631.44 |
June | 96322631.87 | 22932795.95 | 73389835.93 | 0.161454E+09 | 68336935.21 |
July | 0.107879E+09 | 36229739.62 | 71649523.96 | 0.204030E+09 | 62789511.37 |
August | 0.117218E+09 | 52394325.82 | 64824131.57 | 0.227793E+09 | 60286887.40 |
September | 0.128441E+09 | 70125190.19 | 58316077.12 | 0.226077E+09 | 83384813.93 |
October | 0.123080E+09 | 76441910.71 | 46637896.90 | 0.193624E+09 | 0.112311E+09 |
November | 71195678.71 | 41418441.13 | 29777237.58 | 91891635.13 | 0.128908E+09 |
December | 77484467.81 | 50875001.26 | 26609466.55 | 0.102642E+09 | 0.162205E+09 |
Annual Sum or Average | 0.123902E+10 | 0.599252E+09 | 0.639763E+09 | 0.197688E+10 | 0.127760E+10 |
Minimum of Months | 71195678.71 | 22932795.95 | 26609466.55 | 85713634.84 | 60286887.40 |
Maximum of Months | 0.128441E+09 | 76441910.71 | 79555911.55 | 0.227793E+09 | 0.162205E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 71223448.41 | 0.132679E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.115857E+09 | 0.105028E+09 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.146309E+09 | 0.100545E+09 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.157558E+09 | 83143234.33 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.147705E+09 | 76521733.60 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.133664E+09 | 59137044.30 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169155E+09 | 54980161.88 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.189086E+09 | 53061193.34 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.187807E+09 | 71661873.53 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.160742E+09 | 94149257.89 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 76449301.33 | 0.106527E+09 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 85421840.79 | 0.133927E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.164098E+10 | 0.107136E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 71223448.41 | 53061193.34 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.189086E+09 | 0.133927E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 71223448.41 | 0.132679E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.115857E+09 | 0.105028E+09 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.146309E+09 | 0.100545E+09 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.157558E+09 | 83143234.33 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.147705E+09 | 76521733.60 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.133664E+09 | 59137044.30 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169155E+09 | 54980161.88 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.189086E+09 | 53061193.34 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.187807E+09 | 71661873.53 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.160742E+09 | 94149257.89 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 76449301.33 | 0.106527E+09 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 85421840.79 | 0.133927E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.164098E+10 | 0.107136E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 71223448.41 | 53061193.34 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.189086E+09 | 0.133927E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72293260.57 | 43630500.95 | 28662759.61 | 85505675.77 | 0.157197E+09 |
February | 99703377.57 | 62361029.60 | 37342347.97 | 0.138922E+09 | 0.124554E+09 |
March | 0.116964E+09 | 62484171.76 | 54480283.56 | 0.175304E+09 | 0.119278E+09 |
April | 0.116647E+09 | 49162470.72 | 67484496.93 | 0.188811E+09 | 98651836.55 |
May | 0.108958E+09 | 29837154.42 | 79121179.80 | 0.176996E+09 | 90821216.20 |
June | 95796278.69 | 22807480.12 | 72988798.57 | 0.160091E+09 | 70253229.08 |
July | 0.107290E+09 | 36031762.90 | 71257996.51 | 0.202360E+09 | 65380129.19 |
August | 0.116578E+09 | 52108018.02 | 64469901.35 | 0.226087E+09 | 63164695.94 |
September | 0.127739E+09 | 69741992.43 | 57997410.03 | 0.224579E+09 | 85231140.78 |
October | 0.122407E+09 | 76024195.35 | 46383045.01 | 0.192543E+09 | 0.111806E+09 |
November | 70806631.28 | 41192110.85 | 29614520.43 | 91681670.71 | 0.126307E+09 |
December | 77061055.42 | 50596995.79 | 26464059.63 | 0.102387E+09 | 0.158831E+09 |
Annual Sum or Average | 0.123224E+10 | 0.595978E+09 | 0.636267E+09 | 0.196527E+10 | 0.127147E+10 |
Minimum of Months | 70806631.28 | 22807480.12 | 26464059.63 | 85505675.77 | 63164695.94 |
Maximum of Months | 0.127739E+09 | 76024195.35 | 79121179.80 | 0.226087E+09 | 0.158831E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 71378707.22 | 0.131203E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.116129E+09 | 0.103780E+09 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.146708E+09 | 99005524.56 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.158136E+09 | 81714277.08 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.148032E+09 | 75760846.44 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.133761E+09 | 58850330.25 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169188E+09 | 54866876.70 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.189092E+09 | 53027896.67 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.187904E+09 | 71296628.75 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.161197E+09 | 92643368.28 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 76752620.54 | 0.104974E+09 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 85583840.52 | 0.132529E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.164386E+10 | 0.105965E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 71378707.22 | 53027896.67 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.189092E+09 | 0.132529E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 71378707.22 | 0.131203E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.116129E+09 | 0.103780E+09 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.146708E+09 | 99005524.56 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.158136E+09 | 81714277.08 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.148032E+09 | 75760846.44 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.133761E+09 | 58850330.25 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169188E+09 | 54866876.70 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.189092E+09 | 53027896.67 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.187904E+09 | 71296628.75 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.161197E+09 | 92643368.28 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 76752620.54 | 0.104974E+09 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 85583840.52 | 0.132529E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.164386E+10 | 0.105965E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 71378707.22 | 53027896.67 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.189092E+09 | 0.132529E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72293260.57 | 43630500.95 | 28662759.61 | 85694799.82 | 0.155441E+09 |
February | 99703377.57 | 62361029.60 | 37342347.97 | 0.139252E+09 | 0.123074E+09 |
March | 0.116964E+09 | 62484171.76 | 54480283.56 | 0.175783E+09 | 0.117453E+09 |
April | 0.116647E+09 | 49162470.72 | 67484496.93 | 0.189502E+09 | 96962043.73 |
May | 0.108958E+09 | 29837154.42 | 79121179.80 | 0.177388E+09 | 89920678.00 |
June | 95796278.69 | 22807480.12 | 72988798.57 | 0.160208E+09 | 69913391.20 |
July | 0.107290E+09 | 36031762.90 | 71257996.51 | 0.202400E+09 | 65246100.65 |
August | 0.116578E+09 | 52108018.02 | 64469901.35 | 0.226094E+09 | 63124982.64 |
September | 0.127739E+09 | 69741992.43 | 57997410.03 | 0.224696E+09 | 84797051.32 |
October | 0.122407E+09 | 76024195.35 | 46383045.01 | 0.193087E+09 | 0.110024E+09 |
November | 70806631.28 | 41192110.85 | 29614520.43 | 92047076.35 | 0.124464E+09 |
December | 77061055.42 | 50596995.79 | 26464059.63 | 0.102584E+09 | 0.157167E+09 |
Annual Sum or Average | 0.123224E+10 | 0.595978E+09 | 0.636267E+09 | 0.196874E+10 | 0.125759E+10 |
Minimum of Months | 70806631.28 | 22807480.12 | 26464059.63 | 85694799.82 | 63124982.64 |
Maximum of Months | 0.127739E+09 | 76024195.35 | 79121179.80 | 0.226094E+09 | 0.157167E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 71584015.99 | 0.129850E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.116508E+09 | 0.102529E+09 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.147352E+09 | 97072756.46 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.159257E+09 | 79576996.80 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.149145E+09 | 73885572.53 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.134226E+09 | 57935125.73 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169429E+09 | 54248776.96 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.189308E+09 | 52438464.78 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.188335E+09 | 70218123.59 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.162185E+09 | 90032734.23 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 77237337.49 | 0.103144E+09 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 85800192.60 | 0.131189E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.165037E+10 | 0.104212E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 71584015.99 | 52438464.78 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.189308E+09 | 0.131189E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 71584015.99 | 0.129850E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.116508E+09 | 0.102529E+09 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.147352E+09 | 97072756.46 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.159257E+09 | 79576996.80 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.149145E+09 | 73885572.53 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.134226E+09 | 57935125.73 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169429E+09 | 54248776.96 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.189308E+09 | 52438464.78 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.188335E+09 | 70218123.59 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.162185E+09 | 90032734.23 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 77237337.49 | 0.103144E+09 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 85800192.60 | 0.131189E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.165037E+10 | 0.104212E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 71584015.99 | 52438464.78 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.189308E+09 | 0.131189E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72293260.57 | 43630500.95 | 28662759.61 | 85945726.54 | 0.153834E+09 |
February | 99703377.57 | 62361029.60 | 37342347.97 | 0.139708E+09 | 0.121592E+09 |
March | 0.116964E+09 | 62484171.76 | 54480283.56 | 0.176557E+09 | 0.115166E+09 |
April | 0.116647E+09 | 49162470.72 | 67484496.93 | 0.190840E+09 | 94435385.91 |
May | 0.108958E+09 | 29837154.42 | 79121179.80 | 0.178720E+09 | 87704026.22 |
June | 95796278.69 | 22807480.12 | 72988798.57 | 0.160769E+09 | 68831165.92 |
July | 0.107290E+09 | 36031762.90 | 71257996.51 | 0.202691E+09 | 64516165.40 |
August | 0.116578E+09 | 52108018.02 | 64469901.35 | 0.226356E+09 | 62428864.27 |
September | 0.127739E+09 | 69741992.43 | 57997410.03 | 0.225217E+09 | 83520148.81 |
October | 0.122407E+09 | 76024195.35 | 46383045.01 | 0.194269E+09 | 0.106939E+09 |
November | 70806631.28 | 41192110.85 | 29614520.43 | 92628271.57 | 0.122295E+09 |
December | 77061055.42 | 50596995.79 | 26464059.63 | 0.102846E+09 | 0.155574E+09 |
Annual Sum or Average | 0.123224E+10 | 0.595978E+09 | 0.636267E+09 | 0.197655E+10 | 0.123684E+10 |
Minimum of Months | 70806631.28 | 22807480.12 | 26464059.63 | 85945726.54 | 62428864.27 |
Maximum of Months | 0.127739E+09 | 76024195.35 | 79121179.80 | 0.226356E+09 | 0.155574E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 72069550.13 | 0.126498E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.117374E+09 | 99604208.40 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.148598E+09 | 93268591.76 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.161451E+09 | 75351344.31 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.152076E+09 | 69393582.87 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.135374E+09 | 55403239.43 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169577E+09 | 52528222.62 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.189328E+09 | 50727485.07 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.189468E+09 | 67349163.58 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.164320E+09 | 85019605.18 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 78113002.81 | 99486541.52 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 86246928.95 | 0.128010E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.166399E+10 | 0.100264E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 72069550.13 | 50727485.07 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.189468E+09 | 0.128010E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 72069550.13 | 0.126498E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.117374E+09 | 99604208.40 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.148598E+09 | 93268591.76 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.161451E+09 | 75351344.31 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.152076E+09 | 69393582.87 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.135374E+09 | 55403239.43 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169577E+09 | 52528222.62 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.189328E+09 | 50727485.07 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.189468E+09 | 67349163.58 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.164320E+09 | 85019605.18 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 78113002.81 | 99486541.52 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 86246928.95 | 0.128010E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.166399E+10 | 0.100264E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 72069550.13 | 50727485.07 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.189468E+09 | 0.128010E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 72069550.13 | 0.126498E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.117374E+09 | 99604208.40 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.148598E+09 | 93268591.76 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.161451E+09 | 75351344.31 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.152076E+09 | 69393582.87 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.135374E+09 | 55403239.43 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169577E+09 | 52528222.62 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.189328E+09 | 50727485.07 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.189468E+09 | 67349163.58 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.164320E+09 | 85019605.18 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 78113002.81 | 99486541.52 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 86246928.95 | 0.128010E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.166399E+10 | 0.100264E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 72069550.13 | 50727485.07 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.189468E+09 | 0.128010E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 72069550.13 | 0.126498E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.117374E+09 | 99604208.40 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.148598E+09 | 93268591.76 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.161451E+09 | 75351344.31 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.152076E+09 | 69393582.87 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.135374E+09 | 55403239.43 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169577E+09 | 52528222.62 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.189328E+09 | 50727485.07 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.189468E+09 | 67349163.58 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.164320E+09 | 85019605.18 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 78113002.81 | 99486541.52 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 86246928.95 | 0.128010E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.166399E+10 | 0.100264E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 72069550.13 | 50727485.07 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.189468E+09 | 0.128010E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72293260.57 | 43630500.95 | 28662759.61 | 86512217.75 | 0.149902E+09 |
February | 99703377.57 | 62361029.60 | 37342347.97 | 0.140712E+09 | 0.118154E+09 |
March | 0.116964E+09 | 62484171.76 | 54480283.56 | 0.178008E+09 | 0.110686E+09 |
April | 0.116647E+09 | 49162470.72 | 67484496.93 | 0.193396E+09 | 89461393.52 |
May | 0.108958E+09 | 29837154.42 | 79121179.80 | 0.182147E+09 | 82414998.88 |
June | 95796278.69 | 22807480.12 | 72988798.57 | 0.162100E+09 | 65847943.24 |
July | 0.107290E+09 | 36031762.90 | 71257996.51 | 0.202839E+09 | 62485419.65 |
August | 0.116578E+09 | 52108018.02 | 64469901.35 | 0.226355E+09 | 60404191.32 |
September | 0.127739E+09 | 69741992.43 | 57997410.03 | 0.226534E+09 | 80127741.46 |
October | 0.122407E+09 | 76024195.35 | 46383045.01 | 0.196760E+09 | 0.101030E+09 |
November | 70806631.28 | 41192110.85 | 29614520.43 | 93651623.98 | 0.117988E+09 |
December | 77061055.42 | 50596995.79 | 26464059.63 | 0.103367E+09 | 0.151829E+09 |
Annual Sum or Average | 0.123224E+10 | 0.595978E+09 | 0.636267E+09 | 0.199238E+10 | 0.119033E+10 |
Minimum of Months | 70806631.28 | 22807480.12 | 26464059.63 | 86512217.75 | 60404191.32 |
Maximum of Months | 0.127739E+09 | 76024195.35 | 79121179.80 | 0.226534E+09 | 0.151829E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72293260.57 | 43630500.95 | 28662759.61 | 86512217.75 | 0.149902E+09 |
February | 99703377.57 | 62361029.60 | 37342347.97 | 0.140712E+09 | 0.118154E+09 |
March | 0.116964E+09 | 62484171.76 | 54480283.56 | 0.178008E+09 | 0.110686E+09 |
April | 0.116647E+09 | 49162470.72 | 67484496.93 | 0.193396E+09 | 89461393.52 |
May | 0.108958E+09 | 29837154.42 | 79121179.80 | 0.182147E+09 | 82414998.88 |
June | 95796278.69 | 22807480.12 | 72988798.57 | 0.162100E+09 | 65847943.24 |
July | 0.107290E+09 | 36031762.90 | 71257996.51 | 0.202839E+09 | 62485419.65 |
August | 0.116578E+09 | 52108018.02 | 64469901.35 | 0.226355E+09 | 60404191.32 |
September | 0.127739E+09 | 69741992.43 | 57997410.03 | 0.226534E+09 | 80127741.46 |
October | 0.122407E+09 | 76024195.35 | 46383045.01 | 0.196760E+09 | 0.101030E+09 |
November | 70806631.28 | 41192110.85 | 29614520.43 | 93651623.98 | 0.117988E+09 |
December | 77061055.42 | 50596995.79 | 26464059.63 | 0.103367E+09 | 0.151829E+09 |
Annual Sum or Average | 0.123224E+10 | 0.595978E+09 | 0.636267E+09 | 0.199238E+10 | 0.119033E+10 |
Minimum of Months | 70806631.28 | 22807480.12 | 26464059.63 | 86512217.75 | 60404191.32 |
Maximum of Months | 0.127739E+09 | 76024195.35 | 79121179.80 | 0.226534E+09 | 0.151829E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 71669010.58 | 0.127278E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.116867E+09 | 0.100063E+09 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.148045E+09 | 93509494.03 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.160660E+09 | 75608256.41 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.150981E+09 | 69848928.14 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.134623E+09 | 55503948.34 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169146E+09 | 52335082.92 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.188936E+09 | 50476628.25 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.188708E+09 | 67667711.75 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.163465E+09 | 85456320.96 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 77751303.30 | 99887693.05 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 85917309.00 | 0.128674E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.165677E+10 | 0.100631E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 71669010.58 | 50476628.25 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.188936E+09 | 0.128674E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 71669010.58 | 0.127278E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.116867E+09 | 0.100063E+09 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.148045E+09 | 93509494.03 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.160660E+09 | 75608256.41 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.150981E+09 | 69848928.14 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.134623E+09 | 55503948.34 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169146E+09 | 52335082.92 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.188936E+09 | 50476628.25 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.188708E+09 | 67667711.75 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.163465E+09 | 85456320.96 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 77751303.30 | 99887693.05 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 85917309.00 | 0.128674E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.165677E+10 | 0.100631E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 71669010.58 | 50476628.25 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.188936E+09 | 0.128674E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72293260.57 | 43630500.95 | 28662759.61 | 86061057.79 | 0.150779E+09 |
February | 99703377.57 | 62361029.60 | 37342347.97 | 0.140151E+09 | 0.118667E+09 |
March | 0.116964E+09 | 62484171.76 | 54480283.56 | 0.177399E+09 | 0.110943E+09 |
April | 0.116647E+09 | 49162470.72 | 67484496.93 | 0.192519E+09 | 89742188.02 |
May | 0.108958E+09 | 29837154.42 | 79121179.80 | 0.180914E+09 | 82927851.06 |
June | 95796278.69 | 22807480.12 | 72988798.57 | 0.161261E+09 | 65955433.07 |
July | 0.107290E+09 | 36031762.90 | 71257996.51 | 0.202376E+09 | 62250705.52 |
August | 0.116578E+09 | 52108018.02 | 64469901.35 | 0.225935E+09 | 60105376.54 |
September | 0.127739E+09 | 69741992.43 | 57997410.03 | 0.225679E+09 | 80490967.26 |
October | 0.122407E+09 | 76024195.35 | 46383045.01 | 0.195804E+09 | 0.101522E+09 |
November | 70806631.28 | 41192110.85 | 29614520.43 | 93250842.83 | 0.118430E+09 |
December | 77061055.42 | 50596995.79 | 26464059.63 | 0.102999E+09 | 0.152580E+09 |
Annual Sum or Average | 0.123224E+10 | 0.595978E+09 | 0.636267E+09 | 0.198435E+10 | 0.119439E+10 |
Minimum of Months | 70806631.28 | 22807480.12 | 26464059.63 | 86061057.79 | 60105376.54 |
Maximum of Months | 0.127739E+09 | 76024195.35 | 79121179.80 | 0.225935E+09 | 0.152580E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 71720258.85 | 0.126938E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.116965E+09 | 99732522.23 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.148189E+09 | 93039133.99 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.160890E+09 | 75143714.33 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.151359E+09 | 69282110.07 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.134854E+09 | 55162129.81 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169289E+09 | 52072930.63 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.189051E+09 | 50256243.64 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.188864E+09 | 67350538.35 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.163672E+09 | 84947473.25 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 77848670.76 | 99492286.24 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 85974425.02 | 0.128340E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.165868E+10 | 0.100176E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 71720258.85 | 50256243.64 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.189051E+09 | 0.128340E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 71720258.85 | 0.126938E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.116965E+09 | 99732522.23 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.148189E+09 | 93039133.99 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.160890E+09 | 75143714.33 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.151359E+09 | 69282110.07 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.134854E+09 | 55162129.81 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169289E+09 | 52072930.63 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.189051E+09 | 50256243.64 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.188864E+09 | 67350538.35 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.163672E+09 | 84947473.25 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 77848670.76 | 99492286.24 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 85974425.02 | 0.128340E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.165868E+10 | 0.100176E+10 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 71720258.85 | 50256243.64 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.189051E+09 | 0.128340E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72293260.57 | 43630500.95 | 28662759.61 | 86123869.27 | 0.150376E+09 |
February | 99703377.57 | 62361029.60 | 37342347.97 | 0.140269E+09 | 0.118275E+09 |
March | 0.116964E+09 | 62484171.76 | 54480283.56 | 0.177573E+09 | 0.110384E+09 |
April | 0.116647E+09 | 49162470.72 | 67484496.93 | 0.192794E+09 | 89191708.49 |
May | 0.108958E+09 | 29837154.42 | 79121179.80 | 0.181366E+09 | 82257435.59 |
June | 95796278.69 | 22807480.12 | 72988798.57 | 0.161538E+09 | 65549857.63 |
July | 0.107290E+09 | 36031762.90 | 71257996.51 | 0.202549E+09 | 61940112.37 |
August | 0.116578E+09 | 52108018.02 | 64469901.35 | 0.226074E+09 | 59844128.86 |
September | 0.127739E+09 | 69741992.43 | 57997410.03 | 0.225867E+09 | 80115207.71 |
October | 0.122407E+09 | 76024195.35 | 46383045.01 | 0.196052E+09 | 0.100919E+09 |
November | 70806631.28 | 41192110.85 | 29614520.43 | 93367824.07 | 0.117960E+09 |
December | 77061055.42 | 50596995.79 | 26464059.63 | 0.103069E+09 | 0.152182E+09 |
Annual Sum or Average | 0.123224E+10 | 0.595978E+09 | 0.636267E+09 | 0.198664E+10 | 0.118899E+10 |
Minimum of Months | 70806631.28 | 22807480.12 | 26464059.63 | 86123869.27 | 59844128.86 |
Maximum of Months | 0.127739E+09 | 76024195.35 | 79121179.80 | 0.226074E+09 | 0.152182E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 71949946.12 | 0.125221E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.117339E+09 | 98236030.87 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.148655E+09 | 91273805.85 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.161616E+09 | 73443829.68 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.152657E+09 | 67194303.85 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.135676E+09 | 53881243.23 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169722E+09 | 51179911.15 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.189362E+09 | 49543732.33 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.189500E+09 | 66000771.62 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.164407E+09 | 83060594.02 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 78159535.45 | 98002436.04 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 86203398.10 | 0.126748E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.166525E+10 | 0.983786E+09 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 71949946.12 | 49543732.33 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.189500E+09 | 0.126748E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 71949946.12 | 0.125221E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.117339E+09 | 98236030.87 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.148655E+09 | 91273805.85 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.161616E+09 | 73443829.68 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.152657E+09 | 67194303.85 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.135676E+09 | 53881243.23 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.169722E+09 | 51179911.15 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.189362E+09 | 49543732.33 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.189500E+09 | 66000771.62 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.164407E+09 | 83060594.02 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 78159535.45 | 98002436.04 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 86203398.10 | 0.126748E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.166525E+10 | 0.983786E+09 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 71949946.12 | 49543732.33 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.189500E+09 | 0.126748E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72293260.57 | 43630500.95 | 28662759.61 | 86404992.95 | 0.148339E+09 |
February | 99703377.57 | 62361029.60 | 37342347.97 | 0.140723E+09 | 0.116501E+09 |
March | 0.116964E+09 | 62484171.76 | 54480283.56 | 0.178136E+09 | 0.108291E+09 |
April | 0.116647E+09 | 49162470.72 | 67484496.93 | 0.193664E+09 | 87181531.93 |
May | 0.108958E+09 | 29837154.42 | 79121179.80 | 0.182913E+09 | 79788511.62 |
June | 95796278.69 | 22807480.12 | 72988798.57 | 0.162522E+09 | 64037718.36 |
July | 0.107290E+09 | 36031762.90 | 71257996.51 | 0.203071E+09 | 60885552.02 |
August | 0.116578E+09 | 52108018.02 | 64469901.35 | 0.226449E+09 | 59002307.33 |
September | 0.127739E+09 | 69741992.43 | 57997410.03 | 0.226629E+09 | 78516765.01 |
October | 0.122407E+09 | 76024195.35 | 46383045.01 | 0.196930E+09 | 98685727.16 |
November | 70806631.28 | 41192110.85 | 29614520.43 | 93742692.47 | 0.116193E+09 |
December | 77061055.42 | 50596995.79 | 26464059.63 | 0.103347E+09 | 0.150292E+09 |
Annual Sum or Average | 0.123224E+10 | 0.595978E+09 | 0.636267E+09 | 0.199453E+10 | 0.116771E+10 |
Minimum of Months | 70806631.28 | 22807480.12 | 26464059.63 | 86404992.95 | 59002307.33 |
Maximum of Months | 0.127739E+09 | 76024195.35 | 79121179.80 | 0.226629E+09 | 0.150292E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 72906331.03 | 0.118086E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.118672E+09 | 92280974.77 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.150067E+09 | 84943700.61 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.163240E+09 | 67987705.85 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.155121E+09 | 61589309.66 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.137498E+09 | 49899899.23 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.170830E+09 | 47994652.98 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.190060E+09 | 46910921.11 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.190921E+09 | 62071180.84 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.165947E+09 | 77835451.88 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 79063123.68 | 92787684.08 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 87067595.15 | 0.120300E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.168139E+10 | 0.922688E+09 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 72906331.03 | 46910921.11 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.190921E+09 | 0.120300E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60466861.36 | 36493020.67 | 23973840.69 | 72906331.03 | 0.118086E+09 |
February | 83392978.28 | 52159436.46 | 31233541.82 | 0.118672E+09 | 92280974.77 |
March | 97830329.53 | 52262433.89 | 45567895.64 | 0.150067E+09 | 84943700.61 |
April | 97564779.43 | 41120019.74 | 56444759.69 | 0.163240E+09 | 67987705.85 |
May | 91133923.65 | 24956117.14 | 66177806.51 | 0.155121E+09 | 61589309.66 |
June | 80125038.73 | 19076421.89 | 61048616.84 | 0.137498E+09 | 49899899.23 |
July | 89738309.72 | 30137354.36 | 59600955.36 | 0.170830E+09 | 47994652.98 |
August | 97507026.70 | 43583707.21 | 53923319.49 | 0.190060E+09 | 46910921.11 |
September | 0.106843E+09 | 58332953.22 | 48509658.08 | 0.190921E+09 | 62071180.84 |
October | 0.102383E+09 | 63587455.38 | 38795278.15 | 0.165947E+09 | 77835451.88 |
November | 59223428.63 | 34453524.94 | 24769903.68 | 79063123.68 | 92787684.08 |
December | 64454696.30 | 42319871.95 | 22134824.35 | 87067595.15 | 0.120300E+09 |
Annual Sum or Average | 0.103066E+10 | 0.498482E+09 | 0.532180E+09 | 0.168139E+10 | 0.922688E+09 |
Minimum of Months | 59223428.63 | 19076421.89 | 22134824.35 | 72906331.03 | 46910921.11 |
Maximum of Months | 0.106843E+09 | 63587455.38 | 66177806.51 | 0.190921E+09 | 0.120300E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72293260.57 | 43630500.95 | 28662759.61 | 87571475.01 | 0.139880E+09 |
February | 99703377.57 | 62361029.60 | 37342347.97 | 0.142337E+09 | 0.109443E+09 |
March | 0.116964E+09 | 62484171.76 | 54480283.56 | 0.179852E+09 | 0.100799E+09 |
April | 0.116647E+09 | 49162470.72 | 67484496.93 | 0.195621E+09 | 80734682.25 |
May | 0.108958E+09 | 29837154.42 | 79121179.80 | 0.185864E+09 | 73169670.01 |
June | 95796278.69 | 22807480.12 | 72988798.57 | 0.164698E+09 | 59339130.44 |
July | 0.107290E+09 | 36031762.90 | 71257996.51 | 0.204401E+09 | 57124750.11 |
August | 0.116578E+09 | 52108018.02 | 64469901.35 | 0.227286E+09 | 55891940.02 |
September | 0.127739E+09 | 69741992.43 | 57997410.03 | 0.228332E+09 | 73861747.16 |
October | 0.122407E+09 | 76024195.35 | 46383045.01 | 0.198779E+09 | 92502200.69 |
November | 70806631.28 | 41192110.85 | 29614520.43 | 94838810.75 | 0.110015E+09 |
December | 77061055.42 | 50596995.79 | 26464059.63 | 0.104398E+09 | 0.142637E+09 |
Annual Sum or Average | 0.123224E+10 | 0.595978E+09 | 0.636267E+09 | 0.201398E+10 | 0.109540E+10 |
Minimum of Months | 70806631.28 | 22807480.12 | 26464059.63 | 87571475.01 | 55891940.02 |
Maximum of Months | 0.127739E+09 | 76024195.35 | 79121179.80 | 0.228332E+09 | 0.142637E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 172.69 | 307.02 | 144.58 | 87.26 | 57.32 | 0.00 | 0.00 |
February | 310.87 | 266.85 | 220.76 | 138.08 | 82.68 | 0.00 | 0.00 |
March | 355.89 | 223.96 | 233.92 | 124.96 | 108.96 | 0.00 | 0.00 |
April | 399.10 | 187.79 | 241.06 | 101.60 | 139.46 | 0.00 | 0.00 |
May | 364.08 | 165.78 | 217.91 | 59.67 | 158.24 | 0.00 | 0.00 |
June | 336.17 | 135.00 | 197.97 | 47.13 | 150.84 | 0.00 | 0.00 |
July | 407.52 | 122.48 | 214.57 | 72.06 | 142.51 | 0.00 | 0.00 |
August | 454.65 | 117.86 | 233.15 | 104.21 | 128.94 | 0.00 | 0.00 |
September | 468.50 | 165.63 | 263.99 | 144.13 | 119.86 | 0.00 | 0.00 |
October | 392.29 | 205.95 | 244.81 | 152.04 | 92.76 | 0.00 | 0.00 |
November | 192.54 | 249.98 | 146.33 | 85.13 | 61.20 | 0.00 | 0.00 |
December | 206.33 | 309.44 | 154.12 | 101.19 | 52.93 | 0.00 | 0.00 |
Annual Sum or Average | 338.50 | 204.52 | 209.31 | 101.23 | 108.07 | 0.00 | 0.00 |
Minimum of Months | 172.69 | 117.86 | 144.58 | 47.13 | 52.93 | 0.00 | 0.00 |
Maximum of Months | 468.50 | 309.44 | 263.99 | 152.04 | 158.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 85.03 | 160.91 | 72.29 | 43.63 | 28.66 | 0.00 | 0.00 |
February | 153.12 | 140.94 | 110.38 | 69.04 | 41.34 | 0.00 | 0.00 |
March | 174.83 | 121.63 | 116.96 | 62.48 | 54.48 | 0.00 | 0.00 |
April | 194.78 | 103.02 | 120.53 | 50.80 | 69.73 | 0.00 | 0.00 |
May | 177.26 | 89.66 | 108.95 | 29.84 | 79.12 | 0.00 | 0.00 |
June | 165.74 | 70.49 | 98.99 | 23.57 | 75.42 | 0.00 | 0.00 |
July | 202.84 | 62.63 | 107.29 | 36.03 | 71.26 | 0.00 | 0.00 |
August | 226.53 | 60.09 | 116.57 | 52.11 | 64.47 | 0.00 | 0.00 |
September | 232.30 | 85.95 | 131.99 | 72.06 | 59.93 | 0.00 | 0.00 |
October | 192.33 | 112.18 | 122.40 | 76.02 | 46.38 | 0.00 | 0.00 |
November | 94.25 | 133.19 | 73.16 | 42.56 | 30.60 | 0.00 | 0.00 |
December | 101.92 | 162.15 | 77.06 | 50.60 | 26.46 | 0.00 | 0.00 |
Annual Sum or Average | 166.80 | 108.42 | 104.65 | 50.62 | 54.04 | 0.00 | 0.00 |
Minimum of Months | 85.03 | 60.09 | 72.29 | 23.57 | 26.46 | 0.00 | 0.00 |
Maximum of Months | 232.30 | 162.15 | 131.99 | 76.02 | 79.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 85.11 | 157.76 | 72.14 | 43.54 | 28.60 | 0.00 | 0.00 |
February | 153.21 | 138.31 | 110.16 | 68.90 | 41.26 | 0.00 | 0.00 |
March | 174.70 | 119.61 | 116.72 | 62.35 | 54.37 | 0.00 | 0.00 |
April | 194.42 | 102.21 | 120.28 | 50.70 | 69.59 | 0.00 | 0.00 |
May | 176.38 | 91.05 | 108.73 | 29.78 | 78.96 | 0.00 | 0.00 |
June | 164.90 | 72.73 | 98.78 | 23.52 | 75.26 | 0.00 | 0.00 |
July | 201.86 | 65.46 | 107.07 | 35.96 | 71.11 | 0.00 | 0.00 |
August | 225.60 | 63.20 | 116.34 | 52.00 | 64.34 | 0.00 | 0.00 |
September | 231.56 | 88.18 | 131.72 | 71.92 | 59.81 | 0.00 | 0.00 |
October | 191.92 | 112.05 | 122.15 | 75.87 | 46.29 | 0.00 | 0.00 |
November | 94.36 | 130.93 | 73.01 | 42.48 | 30.54 | 0.00 | 0.00 |
December | 102.01 | 159.31 | 76.90 | 50.49 | 26.41 | 0.00 | 0.00 |
Annual Sum or Average | 166.39 | 108.26 | 104.44 | 50.51 | 53.93 | 0.00 | 0.00 |
Minimum of Months | 85.11 | 63.20 | 72.14 | 23.52 | 26.41 | 0.00 | 0.00 |
Maximum of Months | 231.56 | 159.31 | 131.72 | 75.87 | 78.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 85.29 | 156.01 | 72.14 | 43.54 | 28.60 | 0.00 | 0.00 |
February | 153.57 | 136.67 | 110.16 | 68.90 | 41.26 | 0.00 | 0.00 |
March | 175.18 | 117.78 | 116.72 | 62.35 | 54.37 | 0.00 | 0.00 |
April | 195.13 | 100.46 | 120.28 | 50.70 | 69.59 | 0.00 | 0.00 |
May | 176.77 | 90.14 | 108.73 | 29.78 | 78.96 | 0.00 | 0.00 |
June | 165.02 | 72.38 | 98.78 | 23.52 | 75.26 | 0.00 | 0.00 |
July | 201.90 | 65.33 | 107.07 | 35.96 | 71.11 | 0.00 | 0.00 |
August | 225.61 | 63.16 | 116.34 | 52.00 | 64.34 | 0.00 | 0.00 |
September | 231.68 | 87.73 | 131.72 | 71.92 | 59.81 | 0.00 | 0.00 |
October | 192.46 | 110.26 | 122.15 | 75.87 | 46.29 | 0.00 | 0.00 |
November | 94.73 | 129.02 | 73.01 | 42.48 | 30.54 | 0.00 | 0.00 |
December | 102.21 | 157.64 | 76.90 | 50.49 | 26.41 | 0.00 | 0.00 |
Annual Sum or Average | 166.68 | 107.08 | 104.44 | 50.51 | 53.93 | 0.00 | 0.00 |
Minimum of Months | 85.29 | 63.16 | 72.14 | 23.52 | 26.41 | 0.00 | 0.00 |
Maximum of Months | 231.68 | 157.64 | 131.72 | 75.87 | 78.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 85.54 | 154.40 | 72.14 | 43.54 | 28.60 | 0.00 | 0.00 |
February | 154.07 | 135.02 | 110.16 | 68.90 | 41.26 | 0.00 | 0.00 |
March | 175.95 | 115.48 | 116.72 | 62.35 | 54.37 | 0.00 | 0.00 |
April | 196.51 | 97.84 | 120.28 | 50.70 | 69.59 | 0.00 | 0.00 |
May | 178.10 | 87.92 | 108.73 | 29.78 | 78.96 | 0.00 | 0.00 |
June | 165.59 | 71.26 | 98.78 | 23.52 | 75.26 | 0.00 | 0.00 |
July | 202.19 | 64.60 | 107.07 | 35.96 | 71.11 | 0.00 | 0.00 |
August | 225.87 | 62.46 | 116.34 | 52.00 | 64.34 | 0.00 | 0.00 |
September | 232.21 | 86.40 | 131.72 | 71.92 | 59.81 | 0.00 | 0.00 |
October | 193.64 | 107.16 | 122.15 | 75.87 | 46.29 | 0.00 | 0.00 |
November | 95.33 | 126.77 | 73.01 | 42.48 | 30.54 | 0.00 | 0.00 |
December | 102.47 | 156.04 | 76.90 | 50.49 | 26.41 | 0.00 | 0.00 |
Annual Sum or Average | 167.34 | 105.31 | 104.44 | 50.51 | 53.93 | 0.00 | 0.00 |
Minimum of Months | 85.54 | 62.46 | 72.14 | 23.52 | 26.41 | 0.00 | 0.00 |
Maximum of Months | 232.21 | 156.04 | 131.72 | 75.87 | 78.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 172.23 | 300.85 | 144.29 | 87.08 | 57.21 | 0.00 | 0.00 |
February | 310.40 | 262.37 | 220.31 | 137.80 | 82.51 | 0.00 | 0.00 |
March | 354.84 | 221.94 | 233.44 | 124.71 | 108.73 | 0.00 | 0.00 |
April | 398.38 | 185.31 | 240.57 | 101.39 | 139.18 | 0.00 | 0.00 |
May | 363.13 | 165.17 | 217.46 | 59.55 | 157.91 | 0.00 | 0.00 |
June | 333.99 | 136.31 | 197.57 | 47.04 | 150.53 | 0.00 | 0.00 |
July | 404.71 | 125.11 | 214.13 | 71.91 | 142.22 | 0.00 | 0.00 |
August | 451.77 | 120.86 | 232.67 | 104.00 | 128.67 | 0.00 | 0.00 |
September | 467.18 | 165.76 | 263.44 | 143.83 | 119.61 | 0.00 | 0.00 |
October | 392.32 | 202.41 | 244.30 | 151.73 | 92.57 | 0.00 | 0.00 |
November | 192.81 | 244.57 | 146.03 | 84.95 | 61.08 | 0.00 | 0.00 |
December | 205.99 | 304.55 | 153.80 | 100.98 | 52.82 | 0.00 | 0.00 |
Annual Sum or Average | 337.42 | 202.66 | 208.88 | 101.02 | 107.85 | 0.00 | 0.00 |
Minimum of Months | 172.23 | 120.86 | 144.29 | 47.04 | 52.82 | 0.00 | 0.00 |
Maximum of Months | 467.18 | 304.55 | 263.44 | 151.73 | 157.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 85.65 | 151.33 | 72.14 | 43.54 | 28.60 | 0.00 | 0.00 |
February | 154.55 | 131.78 | 110.16 | 68.90 | 41.26 | 0.00 | 0.00 |
March | 176.78 | 111.25 | 116.72 | 62.35 | 54.37 | 0.00 | 0.00 |
April | 198.24 | 92.96 | 120.28 | 50.70 | 69.59 | 0.00 | 0.00 |
May | 180.29 | 83.12 | 108.73 | 29.78 | 78.96 | 0.00 | 0.00 |
June | 166.09 | 68.27 | 98.78 | 23.52 | 75.26 | 0.00 | 0.00 |
July | 201.86 | 62.32 | 107.07 | 35.96 | 71.11 | 0.00 | 0.00 |
August | 225.44 | 60.13 | 116.34 | 52.00 | 64.34 | 0.00 | 0.00 |
September | 232.68 | 83.27 | 131.72 | 71.92 | 59.81 | 0.00 | 0.00 |
October | 195.17 | 101.72 | 122.15 | 75.87 | 46.29 | 0.00 | 0.00 |
November | 95.97 | 122.76 | 73.01 | 42.48 | 30.54 | 0.00 | 0.00 |
December | 102.61 | 153.05 | 76.90 | 50.49 | 26.41 | 0.00 | 0.00 |
Annual Sum or Average | 167.99 | 101.69 | 104.44 | 50.51 | 53.93 | 0.00 | 0.00 |
Minimum of Months | 85.65 | 60.13 | 72.14 | 23.52 | 26.41 | 0.00 | 0.00 |
Maximum of Months | 232.68 | 153.05 | 131.72 | 75.87 | 78.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 85.71 | 150.93 | 72.14 | 43.54 | 28.60 | 0.00 | 0.00 |
February | 154.68 | 131.34 | 110.16 | 68.90 | 41.26 | 0.00 | 0.00 |
March | 176.95 | 110.69 | 116.72 | 62.35 | 54.37 | 0.00 | 0.00 |
April | 198.52 | 92.39 | 120.28 | 50.70 | 69.59 | 0.00 | 0.00 |
May | 180.74 | 82.45 | 108.73 | 29.78 | 78.96 | 0.00 | 0.00 |
June | 166.38 | 67.85 | 98.78 | 23.52 | 75.26 | 0.00 | 0.00 |
July | 202.03 | 62.01 | 107.07 | 35.96 | 71.11 | 0.00 | 0.00 |
August | 225.57 | 59.87 | 116.34 | 52.00 | 64.34 | 0.00 | 0.00 |
September | 232.87 | 82.88 | 131.72 | 71.92 | 59.81 | 0.00 | 0.00 |
October | 195.41 | 101.11 | 122.15 | 75.87 | 46.29 | 0.00 | 0.00 |
November | 96.09 | 122.28 | 73.01 | 42.48 | 30.54 | 0.00 | 0.00 |
December | 102.68 | 152.65 | 76.90 | 50.49 | 26.41 | 0.00 | 0.00 |
Annual Sum or Average | 168.19 | 101.23 | 104.44 | 50.51 | 53.93 | 0.00 | 0.00 |
Minimum of Months | 85.71 | 59.87 | 72.14 | 23.52 | 26.41 | 0.00 | 0.00 |
Maximum of Months | 232.87 | 152.65 | 131.72 | 75.87 | 78.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 85.99 | 148.89 | 72.14 | 43.54 | 28.60 | 0.00 | 0.00 |
February | 155.18 | 129.37 | 110.16 | 68.90 | 41.26 | 0.00 | 0.00 |
March | 177.51 | 108.59 | 116.72 | 62.35 | 54.37 | 0.00 | 0.00 |
April | 199.42 | 90.30 | 120.28 | 50.70 | 69.59 | 0.00 | 0.00 |
May | 182.28 | 79.96 | 108.73 | 29.78 | 78.96 | 0.00 | 0.00 |
June | 167.39 | 66.28 | 98.78 | 23.52 | 75.26 | 0.00 | 0.00 |
July | 202.55 | 60.95 | 107.07 | 35.96 | 71.11 | 0.00 | 0.00 |
August | 225.95 | 59.02 | 116.34 | 52.00 | 64.34 | 0.00 | 0.00 |
September | 233.65 | 81.22 | 131.72 | 71.92 | 59.81 | 0.00 | 0.00 |
October | 196.29 | 98.87 | 122.15 | 75.87 | 46.29 | 0.00 | 0.00 |
November | 96.47 | 120.45 | 73.01 | 42.48 | 30.54 | 0.00 | 0.00 |
December | 102.95 | 150.76 | 76.90 | 50.49 | 26.41 | 0.00 | 0.00 |
Annual Sum or Average | 168.86 | 99.42 | 104.44 | 50.51 | 53.93 | 0.00 | 0.00 |
Minimum of Months | 85.99 | 59.02 | 72.14 | 23.52 | 26.41 | 0.00 | 0.00 |
Maximum of Months | 233.65 | 150.76 | 131.72 | 75.87 | 78.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 87.14 | 140.40 | 72.14 | 43.54 | 28.60 | 0.00 | 0.00 |
February | 156.94 | 121.53 | 110.16 | 68.90 | 41.26 | 0.00 | 0.00 |
March | 179.21 | 101.06 | 116.72 | 62.35 | 54.37 | 0.00 | 0.00 |
April | 201.43 | 83.61 | 120.28 | 50.70 | 69.59 | 0.00 | 0.00 |
May | 185.22 | 73.31 | 108.73 | 29.78 | 78.96 | 0.00 | 0.00 |
June | 169.64 | 61.40 | 98.78 | 23.52 | 75.26 | 0.00 | 0.00 |
July | 203.88 | 57.17 | 107.07 | 35.96 | 71.11 | 0.00 | 0.00 |
August | 226.78 | 55.90 | 116.34 | 52.00 | 64.34 | 0.00 | 0.00 |
September | 235.41 | 76.39 | 131.72 | 71.92 | 59.81 | 0.00 | 0.00 |
October | 198.13 | 92.66 | 122.15 | 75.87 | 46.29 | 0.00 | 0.00 |
November | 97.59 | 114.04 | 73.01 | 42.48 | 30.54 | 0.00 | 0.00 |
December | 103.99 | 143.08 | 76.90 | 50.49 | 26.41 | 0.00 | 0.00 |
Annual Sum or Average | 170.50 | 93.25 | 104.44 | 50.51 | 53.93 | 0.00 | 0.00 |
Minimum of Months | 87.14 | 55.90 | 72.14 | 23.52 | 26.41 | 0.00 | 0.00 |
Maximum of Months | 235.41 | 143.08 | 131.72 | 75.87 | 78.96 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.462530E+09 | 0.822315E+09 | 0.387248E+09 | 0.233713E+09 | 0.153536E+09 | 0.00 | 0.00 |
February | 0.752062E+09 | 0.645555E+09 | 0.534074E+09 | 0.334045E+09 | 0.200029E+09 | 0.00 | 0.00 |
March | 0.953227E+09 | 0.599852E+09 | 0.626536E+09 | 0.334705E+09 | 0.291831E+09 | 0.00 | 0.00 |
April | 0.103448E+10 | 0.486759E+09 | 0.624835E+09 | 0.263345E+09 | 0.361490E+09 | 0.00 | 0.00 |
May | 0.975153E+09 | 0.444020E+09 | 0.583650E+09 | 0.159827E+09 | 0.423823E+09 | 0.00 | 0.00 |
June | 0.871346E+09 | 0.349919E+09 | 0.513145E+09 | 0.122171E+09 | 0.390974E+09 | 0.00 | 0.00 |
July | 0.109149E+10 | 0.328042E+09 | 0.574712E+09 | 0.193009E+09 | 0.381703E+09 | 0.00 | 0.00 |
August | 0.121773E+10 | 0.315671E+09 | 0.624465E+09 | 0.279123E+09 | 0.345342E+09 | 0.00 | 0.00 |
September | 0.121436E+10 | 0.429319E+09 | 0.684253E+09 | 0.373582E+09 | 0.310671E+09 | 0.00 | 0.00 |
October | 0.105072E+10 | 0.551605E+09 | 0.655691E+09 | 0.407234E+09 | 0.248457E+09 | 0.00 | 0.00 |
November | 0.499062E+09 | 0.647941E+09 | 0.379285E+09 | 0.220651E+09 | 0.158634E+09 | 0.00 | 0.00 |
December | 0.552636E+09 | 0.828809E+09 | 0.412788E+09 | 0.271029E+09 | 0.141758E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106748E+11 | 0.644981E+10 | 0.660068E+10 | 0.319243E+10 | 0.340825E+10 | 0.00 | 0.00 |
Minimum of Months | 0.462530E+09 | 0.315671E+09 | 0.379285E+09 | 0.122171E+09 | 0.141758E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121773E+10 | 0.828809E+09 | 0.684253E+09 | 0.407234E+09 | 0.423823E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.227732E+09 | 0.430984E+09 | 0.193624E+09 | 0.116856E+09 | 76767928.68 | 0.00 | 0.00 |
February | 0.370431E+09 | 0.340953E+09 | 0.267037E+09 | 0.167023E+09 | 0.100015E+09 | 0.00 | 0.00 |
March | 0.468274E+09 | 0.325775E+09 | 0.313268E+09 | 0.167352E+09 | 0.145915E+09 | 0.00 | 0.00 |
April | 0.504876E+09 | 0.267031E+09 | 0.312417E+09 | 0.131673E+09 | 0.180745E+09 | 0.00 | 0.00 |
May | 0.474763E+09 | 0.240147E+09 | 0.291825E+09 | 79913329.11 | 0.211912E+09 | 0.00 | 0.00 |
June | 0.429589E+09 | 0.182712E+09 | 0.256573E+09 | 61085639.73 | 0.195487E+09 | 0.00 | 0.00 |
July | 0.543281E+09 | 0.167753E+09 | 0.287356E+09 | 96504448.34 | 0.190851E+09 | 0.00 | 0.00 |
August | 0.606744E+09 | 0.160949E+09 | 0.312233E+09 | 0.139562E+09 | 0.172671E+09 | 0.00 | 0.00 |
September | 0.602131E+09 | 0.222787E+09 | 0.342126E+09 | 0.186791E+09 | 0.155335E+09 | 0.00 | 0.00 |
October | 0.515148E+09 | 0.300456E+09 | 0.327845E+09 | 0.203617E+09 | 0.124228E+09 | 0.00 | 0.00 |
November | 0.244308E+09 | 0.345221E+09 | 0.189643E+09 | 0.110325E+09 | 79317044.95 | 0.00 | 0.00 |
December | 0.272980E+09 | 0.434313E+09 | 0.206394E+09 | 0.135515E+09 | 70879115.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.526026E+10 | 0.341908E+10 | 0.330034E+10 | 0.159622E+10 | 0.170412E+10 | 0.00 | 0.00 |
Minimum of Months | 0.227732E+09 | 0.160949E+09 | 0.189643E+09 | 61085639.73 | 70879115.25 | 0.00 | 0.00 |
Maximum of Months | 0.606744E+09 | 0.434313E+09 | 0.342126E+09 | 0.203617E+09 | 0.211912E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.227952E+09 | 0.422554E+09 | 0.193227E+09 | 0.116617E+09 | 76610440.99 | 0.00 | 0.00 |
February | 0.370635E+09 | 0.334609E+09 | 0.266489E+09 | 0.166680E+09 | 99809431.61 | 0.00 | 0.00 |
March | 0.467922E+09 | 0.320368E+09 | 0.312625E+09 | 0.167009E+09 | 0.145616E+09 | 0.00 | 0.00 |
April | 0.503927E+09 | 0.264938E+09 | 0.311777E+09 | 0.131403E+09 | 0.180374E+09 | 0.00 | 0.00 |
May | 0.472405E+09 | 0.243864E+09 | 0.291226E+09 | 79749388.70 | 0.211477E+09 | 0.00 | 0.00 |
June | 0.427418E+09 | 0.188527E+09 | 0.256046E+09 | 60960323.90 | 0.195086E+09 | 0.00 | 0.00 |
July | 0.540669E+09 | 0.175340E+09 | 0.286766E+09 | 96306471.62 | 0.190460E+09 | 0.00 | 0.00 |
August | 0.604258E+09 | 0.169287E+09 | 0.311592E+09 | 0.139275E+09 | 0.172317E+09 | 0.00 | 0.00 |
September | 0.600192E+09 | 0.228554E+09 | 0.341425E+09 | 0.186408E+09 | 0.155017E+09 | 0.00 | 0.00 |
October | 0.514027E+09 | 0.300104E+09 | 0.327173E+09 | 0.203199E+09 | 0.123974E+09 | 0.00 | 0.00 |
November | 0.244580E+09 | 0.339361E+09 | 0.189253E+09 | 0.110099E+09 | 79154327.80 | 0.00 | 0.00 |
December | 0.273230E+09 | 0.426684E+09 | 0.205970E+09 | 0.135237E+09 | 70733708.33 | 0.00 | 0.00 |
Annual Sum or Average | 0.524722E+10 | 0.341419E+10 | 0.329357E+10 | 0.159294E+10 | 0.170063E+10 | 0.00 | 0.00 |
Minimum of Months | 0.227952E+09 | 0.169287E+09 | 0.189253E+09 | 60960323.90 | 70733708.33 | 0.00 | 0.00 |
Maximum of Months | 0.604258E+09 | 0.426684E+09 | 0.341425E+09 | 0.203199E+09 | 0.211477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.228451E+09 | 0.417845E+09 | 0.193227E+09 | 0.116617E+09 | 76610440.99 | 0.00 | 0.00 |
February | 0.371509E+09 | 0.330633E+09 | 0.266489E+09 | 0.166680E+09 | 99809431.61 | 0.00 | 0.00 |
March | 0.469198E+09 | 0.315463E+09 | 0.312625E+09 | 0.167009E+09 | 0.145616E+09 | 0.00 | 0.00 |
April | 0.505772E+09 | 0.260390E+09 | 0.311777E+09 | 0.131403E+09 | 0.180374E+09 | 0.00 | 0.00 |
May | 0.473452E+09 | 0.241441E+09 | 0.291226E+09 | 79749388.70 | 0.211477E+09 | 0.00 | 0.00 |
June | 0.427729E+09 | 0.187614E+09 | 0.256046E+09 | 60960323.90 | 0.195086E+09 | 0.00 | 0.00 |
July | 0.540775E+09 | 0.174980E+09 | 0.286766E+09 | 96306471.62 | 0.190460E+09 | 0.00 | 0.00 |
August | 0.604277E+09 | 0.169181E+09 | 0.311592E+09 | 0.139275E+09 | 0.172317E+09 | 0.00 | 0.00 |
September | 0.600503E+09 | 0.227390E+09 | 0.341425E+09 | 0.186408E+09 | 0.155017E+09 | 0.00 | 0.00 |
October | 0.515480E+09 | 0.295309E+09 | 0.327173E+09 | 0.203199E+09 | 0.123974E+09 | 0.00 | 0.00 |
November | 0.245552E+09 | 0.334412E+09 | 0.189253E+09 | 0.110099E+09 | 79154327.80 | 0.00 | 0.00 |
December | 0.273751E+09 | 0.422225E+09 | 0.205970E+09 | 0.135237E+09 | 70733708.33 | 0.00 | 0.00 |
Annual Sum or Average | 0.525645E+10 | 0.337688E+10 | 0.329357E+10 | 0.159294E+10 | 0.170063E+10 | 0.00 | 0.00 |
Minimum of Months | 0.228451E+09 | 0.169181E+09 | 0.189253E+09 | 60960323.90 | 70733708.33 | 0.00 | 0.00 |
Maximum of Months | 0.604277E+09 | 0.422225E+09 | 0.341425E+09 | 0.203199E+09 | 0.211477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.229113E+09 | 0.413533E+09 | 0.193227E+09 | 0.116617E+09 | 76610440.99 | 0.00 | 0.00 |
February | 0.372723E+09 | 0.326649E+09 | 0.266489E+09 | 0.166680E+09 | 99809431.61 | 0.00 | 0.00 |
March | 0.471261E+09 | 0.309311E+09 | 0.312625E+09 | 0.167009E+09 | 0.145616E+09 | 0.00 | 0.00 |
April | 0.509354E+09 | 0.253589E+09 | 0.311777E+09 | 0.131403E+09 | 0.180374E+09 | 0.00 | 0.00 |
May | 0.477010E+09 | 0.235475E+09 | 0.291226E+09 | 79749388.70 | 0.211477E+09 | 0.00 | 0.00 |
June | 0.429220E+09 | 0.184701E+09 | 0.256046E+09 | 60960323.90 | 0.195086E+09 | 0.00 | 0.00 |
July | 0.541549E+09 | 0.173014E+09 | 0.286766E+09 | 96306471.62 | 0.190460E+09 | 0.00 | 0.00 |
August | 0.604972E+09 | 0.167306E+09 | 0.311592E+09 | 0.139275E+09 | 0.172317E+09 | 0.00 | 0.00 |
September | 0.601887E+09 | 0.223956E+09 | 0.341425E+09 | 0.186408E+09 | 0.155017E+09 | 0.00 | 0.00 |
October | 0.518638E+09 | 0.287004E+09 | 0.327173E+09 | 0.203199E+09 | 0.123974E+09 | 0.00 | 0.00 |
November | 0.247103E+09 | 0.328582E+09 | 0.189253E+09 | 0.110099E+09 | 79154327.80 | 0.00 | 0.00 |
December | 0.274446E+09 | 0.417950E+09 | 0.205970E+09 | 0.135237E+09 | 70733708.33 | 0.00 | 0.00 |
Annual Sum or Average | 0.527728E+10 | 0.332107E+10 | 0.329357E+10 | 0.159294E+10 | 0.170063E+10 | 0.00 | 0.00 |
Minimum of Months | 0.229113E+09 | 0.167306E+09 | 0.189253E+09 | 60960323.90 | 70733708.33 | 0.00 | 0.00 |
Maximum of Months | 0.604972E+09 | 0.417950E+09 | 0.341425E+09 | 0.203199E+09 | 0.211477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.461300E+09 | 0.805794E+09 | 0.386454E+09 | 0.233233E+09 | 0.153221E+09 | 0.00 | 0.00 |
February | 0.750916E+09 | 0.634725E+09 | 0.532979E+09 | 0.333360E+09 | 0.199619E+09 | 0.00 | 0.00 |
March | 0.950409E+09 | 0.594446E+09 | 0.625250E+09 | 0.334018E+09 | 0.291232E+09 | 0.00 | 0.00 |
April | 0.103260E+10 | 0.480328E+09 | 0.623553E+09 | 0.262805E+09 | 0.360748E+09 | 0.00 | 0.00 |
May | 0.972597E+09 | 0.442404E+09 | 0.582452E+09 | 0.159499E+09 | 0.422954E+09 | 0.00 | 0.00 |
June | 0.865694E+09 | 0.353308E+09 | 0.512093E+09 | 0.121921E+09 | 0.390172E+09 | 0.00 | 0.00 |
July | 0.108398E+10 | 0.335083E+09 | 0.573533E+09 | 0.192613E+09 | 0.380920E+09 | 0.00 | 0.00 |
August | 0.121002E+10 | 0.323717E+09 | 0.623184E+09 | 0.278551E+09 | 0.344633E+09 | 0.00 | 0.00 |
September | 0.121094E+10 | 0.429652E+09 | 0.682849E+09 | 0.372816E+09 | 0.310033E+09 | 0.00 | 0.00 |
October | 0.105080E+10 | 0.542138E+09 | 0.654345E+09 | 0.406398E+09 | 0.247947E+09 | 0.00 | 0.00 |
November | 0.499754E+09 | 0.633921E+09 | 0.378507E+09 | 0.220198E+09 | 0.158309E+09 | 0.00 | 0.00 |
December | 0.551719E+09 | 0.815697E+09 | 0.411941E+09 | 0.270473E+09 | 0.141467E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106407E+11 | 0.639121E+10 | 0.658714E+10 | 0.318589E+10 | 0.340126E+10 | 0.00 | 0.00 |
Minimum of Months | 0.461300E+09 | 0.323717E+09 | 0.378507E+09 | 0.121921E+09 | 0.141467E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121094E+10 | 0.815697E+09 | 0.682849E+09 | 0.406398E+09 | 0.422954E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.229398E+09 | 0.405333E+09 | 0.193227E+09 | 0.116617E+09 | 76610440.99 | 0.00 | 0.00 |
February | 0.373886E+09 | 0.318792E+09 | 0.266489E+09 | 0.166680E+09 | 99809431.61 | 0.00 | 0.00 |
March | 0.473488E+09 | 0.297961E+09 | 0.312625E+09 | 0.167009E+09 | 0.145616E+09 | 0.00 | 0.00 |
April | 0.513838E+09 | 0.240958E+09 | 0.311777E+09 | 0.131403E+09 | 0.180374E+09 | 0.00 | 0.00 |
May | 0.482875E+09 | 0.222625E+09 | 0.291226E+09 | 79749388.70 | 0.211477E+09 | 0.00 | 0.00 |
June | 0.430508E+09 | 0.176963E+09 | 0.256046E+09 | 60960323.90 | 0.195086E+09 | 0.00 | 0.00 |
July | 0.540667E+09 | 0.166921E+09 | 0.286766E+09 | 96306471.62 | 0.190460E+09 | 0.00 | 0.00 |
August | 0.603807E+09 | 0.161058E+09 | 0.311592E+09 | 0.139275E+09 | 0.172317E+09 | 0.00 | 0.00 |
September | 0.603096E+09 | 0.215826E+09 | 0.341425E+09 | 0.186408E+09 | 0.155017E+09 | 0.00 | 0.00 |
October | 0.522734E+09 | 0.272434E+09 | 0.327173E+09 | 0.203199E+09 | 0.123974E+09 | 0.00 | 0.00 |
November | 0.248753E+09 | 0.318205E+09 | 0.189253E+09 | 0.110099E+09 | 79154327.80 | 0.00 | 0.00 |
December | 0.274833E+09 | 0.409928E+09 | 0.205970E+09 | 0.135237E+09 | 70733708.33 | 0.00 | 0.00 |
Annual Sum or Average | 0.529788E+10 | 0.320701E+10 | 0.329357E+10 | 0.159294E+10 | 0.170063E+10 | 0.00 | 0.00 |
Minimum of Months | 0.229398E+09 | 0.161058E+09 | 0.189253E+09 | 60960323.90 | 70733708.33 | 0.00 | 0.00 |
Maximum of Months | 0.603807E+09 | 0.409928E+09 | 0.341425E+09 | 0.203199E+09 | 0.211477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.229563E+09 | 0.404252E+09 | 0.193227E+09 | 0.116617E+09 | 76610440.99 | 0.00 | 0.00 |
February | 0.374198E+09 | 0.317739E+09 | 0.266489E+09 | 0.166680E+09 | 99809431.61 | 0.00 | 0.00 |
March | 0.473951E+09 | 0.296462E+09 | 0.312625E+09 | 0.167009E+09 | 0.145616E+09 | 0.00 | 0.00 |
April | 0.514573E+09 | 0.239479E+09 | 0.311777E+09 | 0.131403E+09 | 0.180374E+09 | 0.00 | 0.00 |
May | 0.484084E+09 | 0.220821E+09 | 0.291226E+09 | 79749388.70 | 0.211477E+09 | 0.00 | 0.00 |
June | 0.431245E+09 | 0.175874E+09 | 0.256046E+09 | 60960323.90 | 0.195086E+09 | 0.00 | 0.00 |
July | 0.541128E+09 | 0.166086E+09 | 0.286766E+09 | 96306471.62 | 0.190460E+09 | 0.00 | 0.00 |
August | 0.604176E+09 | 0.160356E+09 | 0.311592E+09 | 0.139275E+09 | 0.172317E+09 | 0.00 | 0.00 |
September | 0.603595E+09 | 0.214816E+09 | 0.341425E+09 | 0.186408E+09 | 0.155017E+09 | 0.00 | 0.00 |
October | 0.523397E+09 | 0.270814E+09 | 0.327173E+09 | 0.203199E+09 | 0.123974E+09 | 0.00 | 0.00 |
November | 0.249065E+09 | 0.316944E+09 | 0.189253E+09 | 0.110099E+09 | 79154327.80 | 0.00 | 0.00 |
December | 0.275017E+09 | 0.408861E+09 | 0.205970E+09 | 0.135237E+09 | 70733708.33 | 0.00 | 0.00 |
Annual Sum or Average | 0.530399E+10 | 0.319250E+10 | 0.329357E+10 | 0.159294E+10 | 0.170063E+10 | 0.00 | 0.00 |
Minimum of Months | 0.229563E+09 | 0.160356E+09 | 0.189253E+09 | 60960323.90 | 70733708.33 | 0.00 | 0.00 |
Maximum of Months | 0.604176E+09 | 0.408861E+09 | 0.341425E+09 | 0.203199E+09 | 0.211477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.230303E+09 | 0.398779E+09 | 0.193227E+09 | 0.116617E+09 | 76610440.99 | 0.00 | 0.00 |
February | 0.375400E+09 | 0.312972E+09 | 0.266489E+09 | 0.166680E+09 | 99809431.61 | 0.00 | 0.00 |
March | 0.475447E+09 | 0.290838E+09 | 0.312625E+09 | 0.167009E+09 | 0.145616E+09 | 0.00 | 0.00 |
April | 0.516897E+09 | 0.234069E+09 | 0.311777E+09 | 0.131403E+09 | 0.180374E+09 | 0.00 | 0.00 |
May | 0.488226E+09 | 0.214177E+09 | 0.291226E+09 | 79749388.70 | 0.211477E+09 | 0.00 | 0.00 |
June | 0.433873E+09 | 0.171800E+09 | 0.256046E+09 | 60960323.90 | 0.195086E+09 | 0.00 | 0.00 |
July | 0.542515E+09 | 0.163245E+09 | 0.286766E+09 | 96306471.62 | 0.190460E+09 | 0.00 | 0.00 |
August | 0.605173E+09 | 0.158089E+09 | 0.311592E+09 | 0.139275E+09 | 0.172317E+09 | 0.00 | 0.00 |
September | 0.605630E+09 | 0.210518E+09 | 0.341425E+09 | 0.186408E+09 | 0.155017E+09 | 0.00 | 0.00 |
October | 0.525742E+09 | 0.264806E+09 | 0.327173E+09 | 0.203199E+09 | 0.123974E+09 | 0.00 | 0.00 |
November | 0.250061E+09 | 0.312198E+09 | 0.189253E+09 | 0.110099E+09 | 79154327.80 | 0.00 | 0.00 |
December | 0.275753E+09 | 0.403787E+09 | 0.205970E+09 | 0.135237E+09 | 70733708.33 | 0.00 | 0.00 |
Annual Sum or Average | 0.532502E+10 | 0.313528E+10 | 0.329357E+10 | 0.159294E+10 | 0.170063E+10 | 0.00 | 0.00 |
Minimum of Months | 0.230303E+09 | 0.158089E+09 | 0.189253E+09 | 60960323.90 | 70733708.33 | 0.00 | 0.00 |
Maximum of Months | 0.605630E+09 | 0.403787E+09 | 0.341425E+09 | 0.203199E+09 | 0.211477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.233383E+09 | 0.376050E+09 | 0.193227E+09 | 0.116617E+09 | 76610440.99 | 0.00 | 0.00 |
February | 0.379681E+09 | 0.294005E+09 | 0.266489E+09 | 0.166680E+09 | 99809431.61 | 0.00 | 0.00 |
March | 0.479984E+09 | 0.270685E+09 | 0.312625E+09 | 0.167009E+09 | 0.145616E+09 | 0.00 | 0.00 |
April | 0.522101E+09 | 0.216710E+09 | 0.311777E+09 | 0.131403E+09 | 0.180374E+09 | 0.00 | 0.00 |
May | 0.496106E+09 | 0.196348E+09 | 0.291226E+09 | 79749388.70 | 0.211477E+09 | 0.00 | 0.00 |
June | 0.439694E+09 | 0.159139E+09 | 0.256046E+09 | 60960323.90 | 0.195086E+09 | 0.00 | 0.00 |
July | 0.546061E+09 | 0.153114E+09 | 0.286766E+09 | 96306471.62 | 0.190460E+09 | 0.00 | 0.00 |
August | 0.607406E+09 | 0.149714E+09 | 0.311592E+09 | 0.139275E+09 | 0.172317E+09 | 0.00 | 0.00 |
September | 0.610173E+09 | 0.198004E+09 | 0.341425E+09 | 0.186408E+09 | 0.155017E+09 | 0.00 | 0.00 |
October | 0.530673E+09 | 0.248173E+09 | 0.327173E+09 | 0.203199E+09 | 0.123974E+09 | 0.00 | 0.00 |
November | 0.252964E+09 | 0.295590E+09 | 0.189253E+09 | 0.110099E+09 | 79154327.80 | 0.00 | 0.00 |
December | 0.278533E+09 | 0.383237E+09 | 0.205970E+09 | 0.135237E+09 | 70733708.33 | 0.00 | 0.00 |
Annual Sum or Average | 0.537676E+10 | 0.294077E+10 | 0.329357E+10 | 0.159294E+10 | 0.170063E+10 | 0.00 | 0.00 |
Minimum of Months | 0.233383E+09 | 0.149714E+09 | 0.189253E+09 | 60960323.90 | 70733708.33 | 0.00 | 0.00 |
Maximum of Months | 0.610173E+09 | 0.383237E+09 | 0.341425E+09 | 0.203199E+09 | 0.211477E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.357647E+09 | -233291642.4 | 0.00 | 0.00 | 744.00 | 0.00 | -124355670.5 | 59.00 | 0.00 | 0.00 |
February | 0.325286E+09 | -213320890.2 | 0.00 | 0.00 | 672.00 | 0.00 | -111965551.3 | 58.99 | 0.00 | 0.00 |
March | 0.360597E+09 | -237338953.8 | 0.00 | 0.00 | 744.00 | 0.00 | -123257562.0 | 58.99 | 0.00 | 0.00 |
April | 0.337545E+09 | -220458116.4 | 0.00 | 0.00 | 720.00 | 0.00 | -117087345.7 | 58.99 | 0.00 | 0.00 |
May | 0.337022E+09 | -219628394.5 | 0.00 | 0.00 | 744.00 | 0.00 | -117393465.0 | 58.99 | 0.00 | 0.00 |
June | 0.317465E+09 | -206547544.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110917659.6 | 58.99 | 0.00 | 0.00 |
July | 0.316791E+09 | -203263961.4 | 0.00 | 0.00 | 744.00 | 0.00 | -113527051.7 | 58.99 | 0.00 | 0.00 |
August | 0.319127E+09 | -205765095.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113361770.7 | 58.99 | 0.00 | 0.00 |
September | 0.310485E+09 | -199583074.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110901769.9 | 58.99 | 0.00 | 0.00 |
October | 0.330265E+09 | -210814643.9 | 0.00 | 0.00 | 744.00 | 0.00 | -119450109.3 | 58.99 | 0.00 | 0.00 |
November | 0.330506E+09 | -211661131.5 | 0.00 | 0.00 | 720.00 | 0.00 | -118844952.3 | 58.99 | 0.00 | 0.00 |
December | 0.351861E+09 | -227817947.2 | 0.00 | 0.00 | 744.00 | 0.00 | -124043267.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.399460E+10 | -0.258949E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140511E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.310485E+09 | -237338953.8 | 0.00 | 0.00 | 672.00 | 0.00 | -124355670.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.360597E+09 | -199583074.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110901769.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.356173E+09 | -233295232.6 | 0.00 | 0.00 | 744.00 | 0.00 | -122877955.6 | 58.99 | 0.00 | 0.00 |
February | 0.323485E+09 | -213318549.7 | 0.00 | 0.00 | 672.00 | 0.00 | -110166523.7 | 58.99 | 0.00 | 0.00 |
March | 0.357588E+09 | -237338996.3 | 0.00 | 0.00 | 744.00 | 0.00 | -120249349.1 | 58.99 | 0.00 | 0.00 |
April | 0.334091E+09 | -220461902.3 | 0.00 | 0.00 | 720.00 | 0.00 | -113629345.3 | 58.99 | 0.00 | 0.00 |
May | 0.334084E+09 | -219627536.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114456458.5 | 58.99 | 0.00 | 0.00 |
June | 0.316335E+09 | -206550712.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109784762.4 | 58.99 | 0.00 | 0.00 |
July | 0.316344E+09 | -203259678.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113084667.8 | 59.00 | 0.00 | 0.00 |
August | 0.318775E+09 | -205770861.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113003953.7 | 58.99 | 0.00 | 0.00 |
September | 0.309317E+09 | -199581096.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109735984.4 | 58.99 | 0.00 | 0.00 |
October | 0.326839E+09 | -210811492.0 | 0.00 | 0.00 | 744.00 | 0.00 | -116027621.2 | 58.99 | 0.00 | 0.00 |
November | 0.328219E+09 | -211650410.7 | 0.00 | 0.00 | 720.00 | 0.00 | -116568868.1 | 59.00 | 0.00 | 0.00 |
December | 0.350254E+09 | -227816140.2 | 0.00 | 0.00 | 744.00 | 0.00 | -122438220.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.397151E+10 | -0.258948E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138202E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.309317E+09 | -237338996.3 | 0.00 | 0.00 | 672.00 | 0.00 | -122877955.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.357588E+09 | -199581096.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109735984.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.329435E+09 | -205157398.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124277962.9 | 58.99 | 0.00 | 0.00 |
February | 0.299177E+09 | -187701579.2 | 0.00 | 0.00 | 672.00 | 0.00 | -111475240.9 | 59.01 | 0.00 | 0.00 |
March | 0.333311E+09 | -211837254.4 | 0.00 | 0.00 | 744.00 | 0.00 | -121473251.6 | 58.99 | 0.00 | 0.00 |
April | 0.308320E+09 | -193895102.5 | 0.00 | 0.00 | 720.00 | 0.00 | -114425384.1 | 58.99 | 0.00 | 0.00 |
May | 0.309088E+09 | -194782663.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114305436.3 | 58.99 | 0.00 | 0.00 |
June | 0.293171E+09 | -183956620.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109214267.4 | 58.99 | 0.00 | 0.00 |
July | 0.289876E+09 | -177704448.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112171663.5 | 58.99 | 0.00 | 0.00 |
August | 0.295821E+09 | -183784228.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112036967.8 | 58.99 | 0.00 | 0.00 |
September | 0.284669E+09 | -175432549.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109236266.9 | 58.98 | 0.00 | 0.00 |
October | 0.302000E+09 | -185406372.5 | 0.00 | 0.00 | 744.00 | 0.00 | -116593695.4 | 58.99 | 0.00 | 0.00 |
November | 0.304640E+09 | -186876726.3 | 0.00 | 0.00 | 720.00 | 0.00 | -117763634.7 | 58.99 | 0.00 | 0.00 |
December | 0.322695E+09 | -198881166.6 | 0.00 | 0.00 | 744.00 | 0.00 | -123813449.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.367220E+10 | -0.228542E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138679E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284669E+09 | -211837254.4 | 0.00 | 0.00 | 672.00 | 0.00 | -124277962.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.333311E+09 | -175432549.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109214267.4 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.329773E+09 | -205166883.2 | 0.00 | 0.00 | 744.00 | 0.00 | -124605656.8 | 58.99 | 0.00 | 0.00 |
February | 0.299497E+09 | -187745666.1 | 0.00 | 0.00 | 672.00 | 0.00 | -111751823.3 | 58.99 | 0.00 | 0.00 |
March | 0.333807E+09 | -211774980.9 | 0.00 | 0.00 | 744.00 | 0.00 | -122032061.3 | 59.01 | 0.00 | 0.00 |
April | 0.308840E+09 | -193904700.1 | 0.00 | 0.00 | 720.00 | 0.00 | -114935210.9 | 58.99 | 0.00 | 0.00 |
May | 0.309355E+09 | -194782113.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114572782.6 | 58.99 | 0.00 | 0.00 |
June | 0.293251E+09 | -183961257.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109289499.3 | 58.99 | 0.00 | 0.00 |
July | 0.289922E+09 | -177692858.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112228740.7 | 59.00 | 0.00 | 0.00 |
August | 0.295828E+09 | -183783731.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112044036.7 | 58.99 | 0.00 | 0.00 |
September | 0.284771E+09 | -175400781.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109369936.4 | 58.99 | 0.00 | 0.00 |
October | 0.302520E+09 | -185408563.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117111736.3 | 58.99 | 0.00 | 0.00 |
November | 0.305080E+09 | -186878499.0 | 0.00 | 0.00 | 720.00 | 0.00 | -118201556.1 | 58.99 | 0.00 | 0.00 |
December | 0.323032E+09 | -198848138.2 | 0.00 | 0.00 | 744.00 | 0.00 | -124183659.9 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367567E+10 | -0.228535E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139033E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284771E+09 | -211774980.9 | 0.00 | 0.00 | 672.00 | 0.00 | -124605656.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.333807E+09 | -175400781.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109289499.3 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319789E+09 | -193896623.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125892265.1 | 59.00 | 0.00 | 0.00 |
February | 0.290688E+09 | -177534053.5 | 0.00 | 0.00 | 672.00 | 0.00 | -113153663.6 | 58.99 | 0.00 | 0.00 |
March | 0.324462E+09 | -200430834.2 | 0.00 | 0.00 | 744.00 | 0.00 | -124031130.3 | 58.99 | 0.00 | 0.00 |
April | 0.301349E+09 | -183479270.7 | 0.00 | 0.00 | 720.00 | 0.00 | -117869769.5 | 58.99 | 0.00 | 0.00 |
May | 0.302101E+09 | -184199891.0 | 0.00 | 0.00 | 744.00 | 0.00 | -117900700.2 | 58.99 | 0.00 | 0.00 |
June | 0.284965E+09 | -174048927.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110915790.4 | 58.99 | 0.00 | 0.00 |
July | 0.281221E+09 | -168054370.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113167034.3 | 59.00 | 0.00 | 0.00 |
August | 0.286858E+09 | -173893766.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112964514.9 | 59.00 | 0.00 | 0.00 |
September | 0.277201E+09 | -165961535.2 | 0.00 | 0.00 | 720.00 | 0.00 | -111239293.3 | 59.00 | 0.00 | 0.00 |
October | 0.295618E+09 | -175255799.3 | 0.00 | 0.00 | 744.00 | 0.00 | -120362419.4 | 58.99 | 0.00 | 0.00 |
November | 0.296522E+09 | -176494885.8 | 0.00 | 0.00 | 720.00 | 0.00 | -120027117.0 | 58.99 | 0.00 | 0.00 |
December | 0.313459E+09 | -188070308.4 | 0.00 | 0.00 | 744.00 | 0.00 | -125388313.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.357423E+10 | -0.216132E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141291E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.277201E+09 | -200430834.2 | 0.00 | 0.00 | 672.00 | 0.00 | -125892265.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.324462E+09 | -165961535.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110915790.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319707E+09 | -193895870.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125810923.6 | 59.00 | 0.00 | 0.00 |
February | 0.290594E+09 | -177535890.0 | 0.00 | 0.00 | 672.00 | 0.00 | -113058029.2 | 58.99 | 0.00 | 0.00 |
March | 0.324354E+09 | -200430690.8 | 0.00 | 0.00 | 744.00 | 0.00 | -123923345.3 | 58.99 | 0.00 | 0.00 |
April | 0.301036E+09 | -183479588.5 | 0.00 | 0.00 | 720.00 | 0.00 | -117556363.0 | 58.99 | 0.00 | 0.00 |
May | 0.301518E+09 | -184192756.0 | 0.00 | 0.00 | 744.00 | 0.00 | -117325656.7 | 59.00 | 0.00 | 0.00 |
June | 0.284672E+09 | -174072311.7 | 0.00 | 0.00 | 720.00 | 0.00 | -110600129.1 | 58.99 | 0.00 | 0.00 |
July | 0.281160E+09 | -168082896.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113077354.7 | 58.99 | 0.00 | 0.00 |
August | 0.286828E+09 | -173923403.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112904811.7 | 58.98 | 0.00 | 0.00 |
September | 0.276805E+09 | -166023957.9 | 0.00 | 0.00 | 720.00 | 0.00 | -110781086.0 | 58.98 | 0.00 | 0.00 |
October | 0.295202E+09 | -175211050.9 | 0.00 | 0.00 | 744.00 | 0.00 | -119991017.8 | 59.00 | 0.00 | 0.00 |
November | 0.296426E+09 | -176498214.5 | 0.00 | 0.00 | 720.00 | 0.00 | -119928201.5 | 58.99 | 0.00 | 0.00 |
December | 0.313393E+09 | -188072331.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125321082.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.357170E+10 | -0.216142E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141028E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.276805E+09 | -200430690.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125810923.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.324354E+09 | -166023957.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110600129.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319780E+09 | -193896488.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125883855.8 | 59.00 | 0.00 | 0.00 |
February | 0.290681E+09 | -177534103.7 | 0.00 | 0.00 | 672.00 | 0.00 | -113147275.8 | 58.99 | 0.00 | 0.00 |
March | 0.324476E+09 | -200431532.2 | 0.00 | 0.00 | 744.00 | 0.00 | -124044627.8 | 58.99 | 0.00 | 0.00 |
April | 0.301197E+09 | -183485349.9 | 0.00 | 0.00 | 720.00 | 0.00 | -117711700.6 | 58.99 | 0.00 | 0.00 |
May | 0.301746E+09 | -184214829.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117531220.3 | 58.99 | 0.00 | 0.00 |
June | 0.284807E+09 | -174064499.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110742894.2 | 58.99 | 0.00 | 0.00 |
July | 0.281237E+09 | -168069686.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113167631.4 | 58.99 | 0.00 | 0.00 |
August | 0.286897E+09 | -173904972.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112991855.3 | 58.99 | 0.00 | 0.00 |
September | 0.276920E+09 | -166004642.9 | 0.00 | 0.00 | 720.00 | 0.00 | -110915280.7 | 58.99 | 0.00 | 0.00 |
October | 0.295374E+09 | -175237027.8 | 0.00 | 0.00 | 744.00 | 0.00 | -120137046.7 | 58.99 | 0.00 | 0.00 |
November | 0.296523E+09 | -176495436.8 | 0.00 | 0.00 | 720.00 | 0.00 | -120027455.2 | 58.99 | 0.00 | 0.00 |
December | 0.313467E+09 | -188071793.7 | 0.00 | 0.00 | 744.00 | 0.00 | -125395007.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.357311E+10 | -0.216141E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141170E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.276920E+09 | -200431532.2 | 0.00 | 0.00 | 672.00 | 0.00 | -125883855.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.324476E+09 | -166004642.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110742894.2 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107094E+11 | 48975.70 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.743998E+10 | 48975.70 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.403592E+10 | 48975.70 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136666E+10 | 48975.70 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 60514886.03 | 15491.42 | 19-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.731436E+09 | 48975.70 | 28-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.529673E+10 | 48975.70 | 10-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.916680E+10 | 48975.70 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.388074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107094E+11 | 48975.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.281531E+10 | 25701.50 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172061E+10 | 25701.50 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.411805E+09 | 25701.50 | 06-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33623714.00 | 24061.72 | 19-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2154272.74 | 468.63 | 31-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104169E+10 | 25701.50 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221439E+10 | 25701.50 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.823959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.281531E+10 | 25701.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.316032E+10 | 28334.86 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195615E+10 | 28334.86 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.538788E+09 | 28334.86 | 05-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65310423.89 | 12727.68 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3848045.93 | 605.69 | 31-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122800E+10 | 28334.86 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.252036E+10 | 28334.86 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.947277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.316032E+10 | 28334.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.335484E+10 | 28303.21 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.209222E+10 | 28303.21 | 05-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.652995E+09 | 28303.21 | 05-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96671284.17 | 15617.47 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11340039.27 | 3346.96 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135793E+10 | 28303.21 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.269452E+10 | 28303.21 | 03-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.335484E+10 | 28303.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.367444E+10 | 28263.99 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.233559E+10 | 28263.99 | 05-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.878671E+09 | 28263.99 | 05-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181029E+09 | 19714.67 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 51933672.61 | 7964.08 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158416E+10 | 28263.99 | 11-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.299416E+10 | 28263.99 | 01-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.367444E+10 | 28263.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.968403E+10 | 48300.60 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.663280E+10 | 48300.60 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.392175E+10 | 48300.60 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149329E+10 | 48300.60 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 92053416.88 | 23061.06 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31141.12 | 30.17 | 28-SEP-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107494E+10 | 48300.60 | 16-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.528093E+10 | 48300.60 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.838248E+10 | 48300.60 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.365623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.968403E+10 | 48300.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.447775E+10 | 24665.82 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.296155E+10 | 24665.82 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149896E+10 | 24665.82 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.483829E+09 | 24665.82 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16628313.32 | 13000.98 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304094E+09 | 24665.82 | 16-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223634E+10 | 24665.82 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.378427E+10 | 24665.82 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.447775E+10 | 24665.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.455715E+10 | 24477.08 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303249E+10 | 24477.08 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158286E+10 | 24477.08 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.530345E+09 | 24477.08 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23078152.11 | 16142.95 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.340833E+09 | 24477.08 | 16-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.230643E+10 | 24477.08 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386096E+10 | 24477.08 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.455715E+10 | 24477.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.495900E+10 | 24167.63 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.336833E+10 | 24167.63 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191630E+10 | 24167.63 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.719969E+09 | 24167.63 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57274132.64 | 24167.63 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 118467.56 | 789.78 | 28-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.481659E+09 | 24167.63 | 16-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.258793E+10 | 24167.63 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.422240E+10 | 24167.63 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.495900E+10 | 24167.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.652645E+10 | 24938.78 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.461318E+10 | 24938.78 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.300670E+10 | 24938.78 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130022E+10 | 24938.78 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.274048E+09 | 24938.78 | 11-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5465978.31 | 8894.30 | 15-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14421153.51 | 17075.04 | 28-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.912719E+09 | 24938.78 | 14-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.350933E+10 | 24938.78 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.557367E+10 | 24938.78 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.257362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.652645E+10 | 24938.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.404427E+09 | 0.386225E+09 | 8979.00 | 27-APR-16:10 | 8524.68 | 0.00 |
May | 0.00 | 0.00 | 0.975706E+09 | 0.864834E+09 | 8730.08 | 06-MAY-13:00 | 6964.35 | 0.00 |
June | 0.00 | 0.00 | 0.189714E+10 | 0.177779E+10 | 10602.76 | 28-JUN-17:00 | 10172.59 | 0.00 |
July | 0.00 | 0.00 | 0.515841E+10 | 0.443613E+10 | 14348.68 | 31-JUL-16:10 | 12552.26 | 0.00 |
August | 0.00 | 0.00 | 0.696446E+10 | 0.600273E+10 | 15616.37 | 10-AUG-17:00 | 15172.25 | 0.00 |
September | 0.00 | 0.00 | 0.187399E+10 | 0.152907E+10 | 10647.84 | 14-SEP-16:30 | 9224.97 | 0.00 |
October | 0.00 | 0.00 | 60855854.55 | 60687469.17 | 3809.69 | 04-OCT-15:00 | 3809.69 | 0.00 |
November | 0.00 | 0.00 | 48445.74 | 36304.60 | 80.74 | 04-NOV-14:00 | 60.51 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.173350E+11 | 0.150575E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.696446E+10 | 0.600273E+10 | 15616.37 | 15172.25 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 56666.16 | 55036.00 | 94.39 | 28-FEB-21:50 | 91.67 | 0.00 |
March | 0.00 | 0.00 | 244490.98 | 238166.53 | 237.92 | 19-MAR-17:50 | 237.92 | 0.00 |
April | 0.00 | 0.00 | 0.303675E+09 | 0.297297E+09 | 14785.44 | 01-APR-18:31 | 14785.44 | 0.00 |
May | 0.00 | 0.00 | 0.665905E+09 | 0.608029E+09 | 15789.28 | 07-MAY-17:02 | 12441.92 | 0.00 |
June | 0.00 | 0.00 | 0.124166E+10 | 0.119459E+10 | 15570.50 | 11-JUN-17:57 | 12921.90 | 0.00 |
July | 0.00 | 0.00 | 0.305594E+10 | 0.273471E+10 | 16185.80 | 15-JUL-18:02 | 11607.68 | 0.00 |
August | 0.00 | 0.00 | 0.425086E+10 | 0.380032E+10 | 16069.21 | 26-AUG-18:02 | 10509.57 | 0.00 |
September | 0.00 | 0.00 | 0.110560E+10 | 0.947588E+09 | 15942.00 | 23-SEP-18:02 | 11005.15 | 0.00 |
October | 0.00 | 0.00 | 38065679.90 | 37846680.50 | 2428.53 | 04-OCT-15:00 | 2428.53 | 0.00 |
November | 0.00 | 0.00 | 4777306.48 | 3835691.94 | 830.32 | 04-NOV-14:00 | 659.06 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.106668E+11 | 0.962451E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.425086E+10 | 0.380032E+10 | 16185.80 | 14785.44 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 29.28 | 29.28 | 0.03 | 27-FEB-14:20 | 0.03 | 0.00 |
March | 0.00 | 0.00 | 824.48 | 824.48 | 0.37 | 18-MAR-14:00 | 0.37 | 0.00 |
April | 0.00 | 0.00 | 0.264274E+09 | 0.259505E+09 | 5633.98 | 27-APR-16:10 | 5539.92 | 0.00 |
May | 0.00 | 0.00 | 0.513492E+09 | 0.474440E+09 | 5783.86 | 06-MAY-13:00 | 4875.55 | 0.00 |
June | 0.00 | 0.00 | 0.918728E+09 | 0.897119E+09 | 5996.41 | 28-JUN-17:00 | 5986.45 | 0.00 |
July | 0.00 | 0.00 | 0.230215E+10 | 0.208591E+10 | 8014.25 | 31-JUL-16:10 | 7249.70 | 0.00 |
August | 0.00 | 0.00 | 0.325176E+10 | 0.293566E+10 | 8569.65 | 10-AUG-16:10 | 8349.62 | 0.00 |
September | 0.00 | 0.00 | 0.884526E+09 | 0.762537E+09 | 6309.06 | 14-SEP-14:00 | 5317.04 | 0.00 |
October | 0.00 | 0.00 | 29070727.86 | 29070711.23 | 2196.61 | 04-OCT-15:00 | 2196.61 | 0.00 |
November | 0.00 | 0.00 | 2432622.36 | 1927640.61 | 582.00 | 04-NOV-14:00 | 461.68 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.816643E+10 | 0.744617E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.325176E+10 | 0.293566E+10 | 8569.65 | 8349.62 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 32.53 | 32.53 | 0.03 | 27-FEB-14:50 | 0.03 | 0.00 |
March | 0.00 | 0.00 | 1066.24 | 1066.24 | 0.39 | 18-MAR-13:50 | 0.39 | 0.00 |
April | 0.00 | 0.00 | 0.253726E+09 | 0.249169E+09 | 5500.34 | 27-APR-16:10 | 5408.52 | 0.00 |
May | 0.00 | 0.00 | 0.496667E+09 | 0.459018E+09 | 5740.64 | 06-MAY-13:00 | 4838.99 | 0.00 |
June | 0.00 | 0.00 | 0.905480E+09 | 0.884268E+09 | 5975.96 | 28-JUN-17:00 | 5967.20 | 0.00 |
July | 0.00 | 0.00 | 0.229327E+10 | 0.207770E+10 | 8021.32 | 31-JUL-16:10 | 7257.44 | 0.00 |
August | 0.00 | 0.00 | 0.324834E+10 | 0.293238E+10 | 8577.35 | 10-AUG-16:10 | 8358.94 | 0.00 |
September | 0.00 | 0.00 | 0.874465E+09 | 0.753752E+09 | 6291.07 | 14-SEP-14:00 | 5302.28 | 0.00 |
October | 0.00 | 0.00 | 27571807.42 | 27571798.89 | 2121.63 | 04-OCT-15:00 | 2121.63 | 0.00 |
November | 0.00 | 0.00 | 1105898.71 | 877632.18 | 360.98 | 04-NOV-14:00 | 286.27 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.810063E+10 | 0.738474E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.324834E+10 | 0.293238E+10 | 8577.35 | 8358.94 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1654.60 | 1654.60 | 0.73 | 18-MAR-14:00 | 0.73 | 0.00 |
April | 0.00 | 0.00 | 0.226759E+09 | 0.222830E+09 | 5165.89 | 27-APR-16:10 | 5076.62 | 0.00 |
May | 0.00 | 0.00 | 0.443149E+09 | 0.409531E+09 | 5505.16 | 06-MAY-13:00 | 4634.42 | 0.00 |
June | 0.00 | 0.00 | 0.839934E+09 | 0.820681E+09 | 5840.89 | 28-JUN-17:00 | 5830.63 | 0.00 |
July | 0.00 | 0.00 | 0.218968E+10 | 0.198407E+10 | 7898.69 | 31-JUL-16:10 | 7140.26 | 0.00 |
August | 0.00 | 0.00 | 0.312987E+10 | 0.282540E+10 | 8456.14 | 10-AUG-16:10 | 8236.10 | 0.00 |
September | 0.00 | 0.00 | 0.819423E+09 | 0.706286E+09 | 6130.83 | 14-SEP-14:00 | 5161.17 | 0.00 |
October | 0.00 | 0.00 | 22463279.80 | 22463159.78 | 1876.61 | 04-OCT-15:00 | 1876.61 | 0.00 |
November | 0.00 | 0.00 | 64.34 | 53.01 | 0.07 | 04-NOV-17:00 | 0.06 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.767128E+10 | 0.699126E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.312987E+10 | 0.282540E+10 | 8456.14 | 8236.10 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.324572E+09 | 0.307119E+09 | 8577.20 | 27-APR-15:00 | 7905.44 | 0.00 |
May | 0.00 | 0.00 | 0.685186E+09 | 0.605492E+09 | 8567.90 | 06-MAY-13:30 | 6821.36 | 0.00 |
June | 0.00 | 0.00 | 0.146675E+10 | 0.137493E+10 | 9837.92 | 28-JUN-17:00 | 9322.84 | 0.00 |
July | 0.00 | 0.00 | 0.397885E+10 | 0.341006E+10 | 14449.86 | 24-JUL-15:00 | 13575.14 | 0.00 |
August | 0.00 | 0.00 | 0.558888E+10 | 0.478877E+10 | 15601.90 | 29-AUG-15:00 | 13573.21 | 0.00 |
September | 0.00 | 0.00 | 0.150475E+10 | 0.121814E+10 | 10440.85 | 14-SEP-14:10 | 8369.12 | 0.00 |
October | 0.00 | 0.00 | 44177982.40 | 44157358.55 | 3633.50 | 04-OCT-15:00 | 3633.50 | 0.00 |
November | 0.00 | 0.00 | 1092631.52 | 814837.30 | 315.85 | 04-NOV-14:40 | 235.75 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.135943E+11 | 0.117495E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.558888E+10 | 0.478877E+10 | 15601.90 | 13575.14 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 211.21 | 211.21 | 0.14 | 18-MAR-15:40 | 0.14 | 0.00 |
April | 0.00 | 0.00 | 0.188908E+09 | 0.184187E+09 | 4842.10 | 27-APR-15:00 | 4629.82 | 0.00 |
May | 0.00 | 0.00 | 0.364617E+09 | 0.334579E+09 | 4831.00 | 06-MAY-13:30 | 4036.36 | 0.00 |
June | 0.00 | 0.00 | 0.745757E+09 | 0.727243E+09 | 5451.89 | 28-JUN-17:00 | 5348.72 | 0.00 |
July | 0.00 | 0.00 | 0.203778E+10 | 0.183048E+10 | 7917.79 | 24-JUL-15:00 | 7574.18 | 0.00 |
August | 0.00 | 0.00 | 0.298344E+10 | 0.266577E+10 | 8555.06 | 29-AUG-15:00 | 7541.24 | 0.00 |
September | 0.00 | 0.00 | 0.735677E+09 | 0.630199E+09 | 5764.55 | 14-SEP-14:10 | 4853.52 | 0.00 |
October | 0.00 | 0.00 | 18921542.06 | 18920020.99 | 1889.49 | 04-OCT-15:00 | 1889.49 | 0.00 |
November | 0.00 | 0.00 | 3222.14 | 2587.22 | 5.34 | 04-NOV-16:50 | 4.29 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.707510E+10 | 0.639138E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.298344E+10 | 0.266577E+10 | 8555.06 | 7574.18 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.183074E+09 | 0.178594E+09 | 4753.88 | 27-APR-15:00 | 4549.80 | 0.00 |
May | 0.00 | 0.00 | 0.350544E+09 | 0.321781E+09 | 4729.58 | 06-MAY-13:30 | 3952.70 | 0.00 |
June | 0.00 | 0.00 | 0.724472E+09 | 0.707001E+09 | 5383.70 | 28-JUN-17:00 | 5287.67 | 0.00 |
July | 0.00 | 0.00 | 0.199847E+10 | 0.179665E+10 | 7847.52 | 24-JUL-15:00 | 7514.36 | 0.00 |
August | 0.00 | 0.00 | 0.293863E+10 | 0.262781E+10 | 8484.39 | 29-AUG-15:00 | 7484.53 | 0.00 |
September | 0.00 | 0.00 | 0.720035E+09 | 0.617318E+09 | 5695.97 | 14-SEP-14:10 | 4798.08 | 0.00 |
October | 0.00 | 0.00 | 17644885.07 | 17643499.76 | 1816.10 | 04-OCT-15:00 | 1816.10 | 0.00 |
November | 0.00 | 0.00 | 2668.94 | 2099.52 | 4.31 | 04-NOV-12:40 | 3.39 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.693287E+10 | 0.626681E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.293863E+10 | 0.262781E+10 | 8484.39 | 7514.36 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.165886E+09 | 0.161878E+09 | 4531.65 | 27-APR-15:00 | 4335.84 | 0.00 |
May | 0.00 | 0.00 | 0.311213E+09 | 0.285507E+09 | 4481.19 | 06-MAY-13:30 | 3738.34 | 0.00 |
June | 0.00 | 0.00 | 0.665115E+09 | 0.649518E+09 | 5228.55 | 28-JUN-17:00 | 5135.24 | 0.00 |
July | 0.00 | 0.00 | 0.189650E+10 | 0.170543E+10 | 7728.34 | 24-JUL-15:00 | 7400.94 | 0.00 |
August | 0.00 | 0.00 | 0.283645E+10 | 0.253591E+10 | 8345.59 | 29-AUG-15:00 | 7360.50 | 0.00 |
September | 0.00 | 0.00 | 0.677805E+09 | 0.581013E+09 | 5564.38 | 14-SEP-14:10 | 4682.33 | 0.00 |
October | 0.00 | 0.00 | 13363878.66 | 13362986.69 | 1575.51 | 04-OCT-15:00 | 1575.51 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.656634E+10 | 0.593262E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.283645E+10 | 0.253591E+10 | 8345.59 | 7400.94 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.152219E+09 | 0.148530E+09 | 4530.09 | 27-APR-15:00 | 4322.01 | 0.00 |
May | 0.00 | 0.00 | 0.280535E+09 | 0.257607E+09 | 4478.11 | 06-MAY-13:30 | 3727.64 | 0.00 |
June | 0.00 | 0.00 | 0.632000E+09 | 0.616775E+09 | 5190.66 | 28-JUN-17:00 | 5083.94 | 0.00 |
July | 0.00 | 0.00 | 0.187223E+10 | 0.168443E+10 | 8055.23 | 24-JUL-15:00 | 7693.27 | 0.00 |
August | 0.00 | 0.00 | 0.292376E+10 | 0.261044E+10 | 8618.30 | 29-AUG-15:00 | 7586.76 | 0.00 |
September | 0.00 | 0.00 | 0.667246E+09 | 0.569908E+09 | 5725.31 | 14-SEP-14:10 | 4813.95 | 0.00 |
October | 0.00 | 0.00 | 7746144.26 | 7744647.07 | 1236.88 | 04-OCT-15:00 | 1236.88 | 0.00 |
November | 0.00 | 0.00 | 36.25 | 28.26 | 0.06 | 04-NOV-13:10 | 0.05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.653574E+10 | 0.589543E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.292376E+10 | 0.261044E+10 | 8618.30 | 7693.27 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148885E+10 | 0.41 | 1735.79 | 01-JAN-08:61 | 0.89 |
February | 0.129910E+10 | 0.40 | 1735.79 | 01-FEB-08:61 | 0.89 |
March | 0.135107E+10 | 0.38 | 1735.79 | 01-MAR-08:61 | 0.89 |
April | 0.124902E+10 | 0.37 | 1735.79 | 01-APR-07:01 | 0.89 |
May | 0.126105E+10 | 0.36 | 1023.74 | 19-MAY-07:02 | 0.68 |
June | 0.122477E+10 | 0.37 | 694.32 | 25-JUN-12:10 | 0.54 |
July | 0.125977E+10 | 0.36 | 694.32 | 23-JUL-16:23 | 0.54 |
August | 0.126294E+10 | 0.36 | 803.05 | 10-AUG-17:00 | 0.59 |
September | 0.122227E+10 | 0.36 | 694.32 | 08-SEP-12:40 | 0.54 |
October | 0.127535E+10 | 0.37 | 1735.79 | 28-OCT-07:01 | 0.89 |
November | 0.133040E+10 | 0.39 | 1735.79 | 10-NOV-08:61 | 0.89 |
December | 0.146077E+10 | 0.41 | 1735.79 | 01-DEC-08:61 | 0.89 |
Annual Sum or Average | 0.156854E+11 | 0.38 | |||
Minimum of Months | 0.122227E+10 | 0.36 | 694.32 | 0.54 | |
Maximum of Months | 0.148885E+10 | 0.41 | 1735.79 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132655E+10 | 0.47 | 977.14 | 01-JAN-10:10 | 0.92 |
February | 0.120294E+10 | 0.47 | 977.14 | 01-FEB-13:40 | 0.92 |
March | 0.136671E+10 | 0.49 | 977.14 | 02-MAR-09:40 | 0.92 |
April | 0.140604E+10 | 0.56 | 977.14 | 01-APR-08:20 | 0.92 |
May | 0.167975E+10 | 0.61 | 977.14 | 03-MAY-15:40 | 0.92 |
June | 0.168337E+10 | 0.62 | 977.14 | 27-JUN-07:50 | 0.91 |
July | 0.170397E+10 | 0.61 | 977.14 | 02-JUL-08:70 | 0.92 |
August | 0.166680E+10 | 0.60 | 977.14 | 01-AUG-15:20 | 0.91 |
September | 0.167944E+10 | 0.62 | 977.14 | 02-SEP-16:10 | 0.91 |
October | 0.152146E+10 | 0.58 | 977.14 | 04-OCT-14:50 | 0.92 |
November | 0.133677E+10 | 0.49 | 977.14 | 04-NOV-13:20 | 0.91 |
December | 0.131931E+10 | 0.46 | 977.14 | 04-DEC-19:50 | 0.92 |
Annual Sum or Average | 0.178931E+11 | 0.55 | |||
Minimum of Months | 0.120294E+10 | 0.46 | 977.14 | 0.91 | |
Maximum of Months | 0.170397E+10 | 0.62 | 977.14 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157313E+10 | 0.50 | 1087.02 | 01-JAN-09:08 | 0.92 |
February | 0.142443E+10 | 0.50 | 1087.02 | 01-FEB-08:05 | 0.92 |
March | 0.160444E+10 | 0.51 | 1087.02 | 01-MAR-09:00 | 0.92 |
April | 0.152617E+10 | 0.50 | 1087.02 | 01-APR-07:04 | 0.92 |
May | 0.158879E+10 | 0.50 | 1087.02 | 03-MAY-14:10 | 0.92 |
June | 0.154965E+10 | 0.50 | 1087.02 | 02-JUN-17:20 | 0.92 |
July | 0.156531E+10 | 0.49 | 1087.02 | 01-JUL-06:40 | 0.91 |
August | 0.160444E+10 | 0.50 | 1087.02 | 01-AUG-15:10 | 0.91 |
September | 0.152617E+10 | 0.50 | 1087.02 | 02-SEP-07:40 | 0.91 |
October | 0.157313E+10 | 0.50 | 1087.02 | 03-OCT-09:00 | 0.92 |
November | 0.152617E+10 | 0.50 | 1087.02 | 09-NOV-15:20 | 0.92 |
December | 0.156531E+10 | 0.49 | 1087.02 | 01-DEC-07:40 | 0.92 |
Annual Sum or Average | 0.186271E+11 | 0.50 | |||
Minimum of Months | 0.142443E+10 | 0.49 | 1087.02 | 0.91 | |
Maximum of Months | 0.160444E+10 | 0.51 | 1087.02 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157088E+10 | 0.50 | 1085.46 | 04-JAN-19:30 | 0.92 |
February | 0.142239E+10 | 0.50 | 1085.46 | 01-FEB-20:40 | 0.92 |
March | 0.160214E+10 | 0.51 | 1085.46 | 03-MAR-14:00 | 0.92 |
April | 0.152399E+10 | 0.50 | 1085.46 | 01-APR-06:03 | 0.92 |
May | 0.158651E+10 | 0.50 | 1085.46 | 01-MAY-06:10 | 0.92 |
June | 0.154744E+10 | 0.50 | 1085.46 | 14-JUN-10:10 | 0.92 |
July | 0.156307E+10 | 0.49 | 1085.46 | 28-JUL-14:40 | 0.91 |
August | 0.160214E+10 | 0.50 | 1085.46 | 01-AUG-15:10 | 0.91 |
September | 0.152399E+10 | 0.50 | 1085.46 | 10-SEP-09:10 | 0.91 |
October | 0.157088E+10 | 0.50 | 1085.46 | 12-OCT-14:40 | 0.92 |
November | 0.152399E+10 | 0.50 | 1085.46 | 19-NOV-15:50 | 0.92 |
December | 0.156307E+10 | 0.49 | 1085.46 | 01-DEC-09:40 | 0.92 |
Annual Sum or Average | 0.186005E+11 | 0.50 | |||
Minimum of Months | 0.142239E+10 | 0.49 | 1085.46 | 0.91 | |
Maximum of Months | 0.160214E+10 | 0.51 | 1085.46 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156809E+10 | 0.50 | 1083.54 | 02-JAN-08:04 | 0.92 |
February | 0.141987E+10 | 0.50 | 1083.54 | 01-FEB-09:40 | 0.92 |
March | 0.159930E+10 | 0.51 | 1083.54 | 02-MAR-07:30 | 0.92 |
April | 0.152129E+10 | 0.50 | 1083.54 | 01-APR-07:00 | 0.92 |
May | 0.158370E+10 | 0.50 | 1083.54 | 03-MAY-14:00 | 0.92 |
June | 0.154469E+10 | 0.50 | 1083.54 | 01-JUN-09:20 | 0.92 |
July | 0.156029E+10 | 0.49 | 1083.54 | 02-JUL-08:40 | 0.92 |
August | 0.159930E+10 | 0.50 | 1083.54 | 01-AUG-15:00 | 0.91 |
September | 0.152129E+10 | 0.50 | 1083.54 | 02-SEP-15:50 | 0.91 |
October | 0.156809E+10 | 0.50 | 1083.54 | 04-OCT-12:10 | 0.92 |
November | 0.152129E+10 | 0.50 | 1083.54 | 02-NOV-08:00 | 0.92 |
December | 0.156029E+10 | 0.49 | 1083.54 | 01-DEC-10:30 | 0.92 |
Annual Sum or Average | 0.185675E+11 | 0.50 | |||
Minimum of Months | 0.141987E+10 | 0.49 | 1083.54 | 0.91 | |
Maximum of Months | 0.159930E+10 | 0.51 | 1083.54 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.111517E+10 | 0.31 | 1703.76 | 01-JAN-09:01 | 0.89 |
February | 0.964727E+09 | 0.30 | 1703.76 | 01-FEB-08:61 | 0.89 |
March | 0.101285E+10 | 0.29 | 1703.76 | 01-MAR-08:61 | 0.89 |
April | 0.914834E+09 | 0.27 | 1703.76 | 01-APR-07:01 | 0.89 |
May | 0.921979E+09 | 0.27 | 1169.58 | 29-MAY-08:61 | 0.74 |
June | 0.897950E+09 | 0.27 | 681.50 | 25-JUN-13:10 | 0.54 |
July | 0.905334E+09 | 0.27 | 704.69 | 24-JUL-15:00 | 0.55 |
August | 0.930876E+09 | 0.27 | 768.01 | 29-AUG-15:00 | 0.58 |
September | 0.883230E+09 | 0.27 | 682.14 | 28-SEP-08:30 | 0.54 |
October | 0.932968E+09 | 0.27 | 1703.76 | 16-OCT-07:01 | 0.89 |
November | 0.994998E+09 | 0.29 | 1703.76 | 01-NOV-07:01 | 0.89 |
December | 0.108272E+10 | 0.30 | 1703.76 | 01-DEC-08:61 | 0.89 |
Annual Sum or Average | 0.115576E+11 | 0.28 | |||
Minimum of Months | 0.883230E+09 | 0.27 | 681.50 | 0.54 | |
Maximum of Months | 0.111517E+10 | 0.31 | 1703.76 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.122997E+10 | 0.46 | 920.92 | 01-JAN-09:40 | 0.92 |
February | 0.111394E+10 | 0.46 | 920.92 | 01-FEB-08:40 | 0.92 |
March | 0.125650E+10 | 0.47 | 920.92 | 01-MAR-13:30 | 0.92 |
April | 0.119351E+10 | 0.46 | 920.92 | 01-APR-15:10 | 0.92 |
May | 0.124324E+10 | 0.46 | 920.92 | 03-MAY-15:50 | 0.92 |
June | 0.121340E+10 | 0.47 | 920.92 | 09-JUN-12:20 | 0.92 |
July | 0.122334E+10 | 0.45 | 920.92 | 07-JUL-11:10 | 0.91 |
August | 0.125650E+10 | 0.47 | 920.92 | 07-AUG-09:50 | 0.91 |
September | 0.119351E+10 | 0.46 | 920.92 | 08-SEP-14:30 | 0.92 |
October | 0.122997E+10 | 0.46 | 920.92 | 15-OCT-09:30 | 0.92 |
November | 0.119351E+10 | 0.46 | 920.92 | 03-NOV-14:40 | 0.91 |
December | 0.122334E+10 | 0.46 | 920.92 | 01-DEC-13:00 | 0.92 |
Annual Sum or Average | 0.145707E+11 | 0.46 | |||
Minimum of Months | 0.111394E+10 | 0.45 | 920.92 | 0.91 | |
Maximum of Months | 0.125650E+10 | 0.47 | 920.92 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.121899E+10 | 0.46 | 912.69 | 01-JAN-09:40 | 0.92 |
February | 0.110399E+10 | 0.46 | 912.69 | 01-FEB-10:40 | 0.92 |
March | 0.124528E+10 | 0.47 | 912.69 | 07-MAR-12:10 | 0.92 |
April | 0.118285E+10 | 0.46 | 912.69 | 01-APR-08:50 | 0.92 |
May | 0.123213E+10 | 0.46 | 912.69 | 03-MAY-14:40 | 0.92 |
June | 0.120256E+10 | 0.47 | 912.69 | 01-JUN-20:00 | 0.92 |
July | 0.121242E+10 | 0.45 | 912.69 | 02-JUL-14:10 | 0.92 |
August | 0.124528E+10 | 0.47 | 912.69 | 01-AUG-14:50 | 0.91 |
September | 0.118285E+10 | 0.46 | 912.69 | 01-SEP-10:00 | 0.91 |
October | 0.121899E+10 | 0.46 | 912.69 | 04-OCT-16:50 | 0.92 |
November | 0.118285E+10 | 0.46 | 912.69 | 01-NOV-14:30 | 0.91 |
December | 0.121242E+10 | 0.46 | 912.69 | 01-DEC-08:07 | 0.92 |
Annual Sum or Average | 0.144406E+11 | 0.46 | |||
Minimum of Months | 0.110399E+10 | 0.45 | 912.69 | 0.91 | |
Maximum of Months | 0.124528E+10 | 0.47 | 912.69 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.120192E+10 | 0.46 | 899.91 | 01-JAN-11:00 | 0.92 |
February | 0.108853E+10 | 0.46 | 899.91 | 02-FEB-08:50 | 0.92 |
March | 0.122784E+10 | 0.47 | 899.91 | 01-MAR-16:50 | 0.92 |
April | 0.116628E+10 | 0.46 | 899.91 | 01-APR-08:00 | 0.92 |
May | 0.121488E+10 | 0.46 | 899.91 | 04-MAY-15:00 | 0.92 |
June | 0.118572E+10 | 0.47 | 899.91 | 03-JUN-15:50 | 0.92 |
July | 0.119544E+10 | 0.45 | 899.91 | 01-JUL-13:20 | 0.92 |
August | 0.122784E+10 | 0.47 | 899.91 | 01-AUG-16:10 | 0.91 |
September | 0.116628E+10 | 0.46 | 899.91 | 04-SEP-10:00 | 0.91 |
October | 0.120192E+10 | 0.46 | 899.91 | 15-OCT-10:40 | 0.92 |
November | 0.116628E+10 | 0.46 | 899.91 | 01-NOV-14:00 | 0.91 |
December | 0.119544E+10 | 0.46 | 899.91 | 01-DEC-08:10 | 0.92 |
Annual Sum or Average | 0.142384E+11 | 0.46 | |||
Minimum of Months | 0.108853E+10 | 0.45 | 899.91 | 0.91 | |
Maximum of Months | 0.122784E+10 | 0.47 | 899.91 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.126543E+10 | 0.46 | 947.43 | 02-JAN-09:40 | 0.92 |
February | 0.114622E+10 | 0.46 | 947.43 | 02-FEB-20:10 | 0.92 |
March | 0.129267E+10 | 0.47 | 947.43 | 01-MAR-10:30 | 0.92 |
April | 0.122787E+10 | 0.46 | 947.43 | 02-APR-09:20 | 0.92 |
May | 0.127903E+10 | 0.46 | 947.43 | 17-MAY-14:30 | 0.92 |
June | 0.124833E+10 | 0.47 | 947.43 | 03-JUN-13:40 | 0.92 |
July | 0.125857E+10 | 0.45 | 947.43 | 08-JUL-12:30 | 0.91 |
August | 0.129267E+10 | 0.47 | 947.43 | 05-AUG-09:50 | 0.91 |
September | 0.122787E+10 | 0.46 | 947.43 | 05-SEP-15:10 | 0.92 |
October | 0.126539E+10 | 0.46 | 947.43 | 02-OCT-08:50 | 0.92 |
November | 0.122787E+10 | 0.46 | 947.43 | 02-NOV-12:10 | 0.92 |
December | 0.125857E+10 | 0.46 | 947.43 | 04-DEC-11:20 | 0.92 |
Annual Sum or Average | 0.149905E+11 | 0.46 | |||
Minimum of Months | 0.114622E+10 | 0.45 | 947.43 | 0.91 | |
Maximum of Months | 0.129267E+10 | 0.47 | 947.43 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.148885E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.129910E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.135107E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.135238E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.150145E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.169046E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.249320E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.291958E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.166967E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.129069E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.133042E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.146077E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.198476E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.129069E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.291958E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.132655E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.120295E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.136677E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.147227E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.181968E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.194369E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.233511E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.253901E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.190700E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.152983E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.133787E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.131931E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.201000E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.120295E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.253901E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.157313E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.142443E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.160444E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.158455E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.169926E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.174772E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.205326E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.228994E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.171226E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.157960E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.152674E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.156531E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.203606E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.142443E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.228994E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.157088E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.142239E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.160214E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.158024E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.169348E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.174271E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.204908E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.228675E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.170798E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.157703E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.152425E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.156307E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.203200E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.142239E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.228675E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156809E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.141987E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159930E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.157205E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.167966E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.172650E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.202600E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.226129E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.169433E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.157314E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.152129E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.156029E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.202018E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.141987E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.226129E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.111517E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.964727E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.101285E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.998317E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.109191E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.126089E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.186153E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.226315E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.124321E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.944203E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.995291E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.108272E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.148340E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.944203E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.226315E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.122997E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.111394E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.125650E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.123575E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.132196E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.137430E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.165187E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.187833E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.134742E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.123421E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.119351E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.122334E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.160611E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.111394E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.187833E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.121899E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.110399E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.124528E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.122385E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.130794E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.135903E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.163295E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.185803E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.133360E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.122295E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.118285E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.121242E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.159019E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.110399E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.185803E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.120192E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.108853E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.122784E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.120365E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.128254E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.132986E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.159534E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.182000E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.130857E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.120494E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.116628E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.119544E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.156249E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.108853E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.182000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.126543E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.114622E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.129267E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.126236E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.134044E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.138579E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.165392E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.190191E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.136849E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.126716E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.122787E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.125857E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.163708E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.114622E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.190191E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148885E+10 | 0.00 | 0.107094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129910E+10 | 0.00 | 0.743998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135107E+10 | 0.00 | 0.403592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124902E+10 | 0.404427E+09 | 0.136666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126105E+10 | 0.975706E+09 | 60514886.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122477E+10 | 0.189714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125977E+10 | 0.515841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126294E+10 | 0.696446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122227E+10 | 0.187399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127535E+10 | 60855854.55 | 0.731436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133040E+10 | 48445.74 | 0.529673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146077E+10 | 0.00 | 0.916680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156854E+11 | 0.173350E+11 | 0.388074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148885E+10 | 0.696446E+10 | 0.107094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132655E+10 | 0.00 | 0.281531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120294E+10 | 56666.16 | 0.172061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136671E+10 | 244490.98 | 0.411805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140604E+10 | 0.303675E+09 | 33623714.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167975E+10 | 0.665905E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168337E+10 | 0.124166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.170397E+10 | 0.305594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166680E+10 | 0.425086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167944E+10 | 0.110560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152146E+10 | 38065679.90 | 2154272.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133677E+10 | 4777306.48 | 0.104169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131931E+10 | 0.00 | 0.221439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178931E+11 | 0.106668E+11 | 0.823959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170397E+10 | 0.425086E+10 | 0.281531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157313E+10 | 0.00 | 0.316032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142443E+10 | 29.28 | 0.195615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160444E+10 | 824.48 | 0.538788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152617E+10 | 0.264274E+09 | 65310423.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158879E+10 | 0.513492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154965E+10 | 0.918728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156531E+10 | 0.230215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160444E+10 | 0.325176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152617E+10 | 0.884526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157313E+10 | 29070727.86 | 3848045.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152617E+10 | 2432622.36 | 0.122800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156531E+10 | 0.00 | 0.252036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186271E+11 | 0.816643E+10 | 0.947277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160444E+10 | 0.325176E+10 | 0.316032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157088E+10 | 0.00 | 0.335484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142239E+10 | 32.53 | 0.209222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160214E+10 | 1066.24 | 0.652995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152399E+10 | 0.253726E+09 | 96671284.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158651E+10 | 0.496667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154744E+10 | 0.905480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156307E+10 | 0.229327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160214E+10 | 0.324834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152399E+10 | 0.874465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157088E+10 | 27571807.42 | 11340039.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152399E+10 | 1105898.71 | 0.135793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156307E+10 | 0.00 | 0.269452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186005E+11 | 0.810063E+10 | 0.102605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160214E+10 | 0.324834E+10 | 0.335484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156809E+10 | 0.00 | 0.367444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141987E+10 | 0.00 | 0.233559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159930E+10 | 1654.60 | 0.878671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152129E+10 | 0.226759E+09 | 0.181029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158370E+10 | 0.443149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154469E+10 | 0.839934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156029E+10 | 0.218968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159930E+10 | 0.312987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152129E+10 | 0.819423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156809E+10 | 22463279.80 | 51933672.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152129E+10 | 64.34 | 0.158416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156029E+10 | 0.00 | 0.299416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185675E+11 | 0.767128E+10 | 0.117000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159930E+10 | 0.312987E+10 | 0.367444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.111517E+10 | 0.00 | 0.968403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.964727E+09 | 0.00 | 0.663280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101285E+10 | 0.00 | 0.392175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.914834E+09 | 0.324572E+09 | 0.149329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.921979E+09 | 0.685186E+09 | 92053416.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.897950E+09 | 0.146675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.905334E+09 | 0.397885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.930876E+09 | 0.558888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.883230E+09 | 0.150475E+10 | 31141.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.932968E+09 | 44177982.40 | 0.107494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.994998E+09 | 1092631.52 | 0.528093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108272E+10 | 0.00 | 0.838248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115576E+11 | 0.135943E+11 | 0.365623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.883230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111517E+10 | 0.558888E+10 | 0.968403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.122997E+10 | 0.00 | 0.447775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111394E+10 | 0.00 | 0.296155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125650E+10 | 211.21 | 0.149896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119351E+10 | 0.188908E+09 | 0.483829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124324E+10 | 0.364617E+09 | 16628313.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121340E+10 | 0.745757E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122334E+10 | 0.203778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125650E+10 | 0.298344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119351E+10 | 0.735677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122997E+10 | 18921542.06 | 0.304094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119351E+10 | 3222.14 | 0.223634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122334E+10 | 0.00 | 0.378427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145707E+11 | 0.707510E+10 | 0.157634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125650E+10 | 0.298344E+10 | 0.447775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.121899E+10 | 0.00 | 0.455715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110399E+10 | 0.00 | 0.303249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124528E+10 | 0.00 | 0.158286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118285E+10 | 0.183074E+09 | 0.530345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123213E+10 | 0.350544E+09 | 23078152.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120256E+10 | 0.724472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121242E+10 | 0.199847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124528E+10 | 0.293863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118285E+10 | 0.720035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121899E+10 | 17644885.07 | 0.340833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118285E+10 | 2668.94 | 0.230643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121242E+10 | 0.00 | 0.386096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144406E+11 | 0.693287E+10 | 0.162341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124528E+10 | 0.293863E+10 | 0.455715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.120192E+10 | 0.00 | 0.495900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108853E+10 | 0.00 | 0.336833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122784E+10 | 0.00 | 0.191630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116628E+10 | 0.165886E+09 | 0.719969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121488E+10 | 0.311213E+09 | 57274132.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118572E+10 | 0.665115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119544E+10 | 0.189650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122784E+10 | 0.283645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116628E+10 | 0.677805E+09 | 118467.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120192E+10 | 13363878.66 | 0.481659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116628E+10 | 0.00 | 0.258793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119544E+10 | 0.00 | 0.422240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142384E+11 | 0.656634E+10 | 0.183130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122784E+10 | 0.283645E+10 | 0.495900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.126543E+10 | 0.00 | 0.652645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114622E+10 | 0.00 | 0.461318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129267E+10 | 0.00 | 0.300670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122787E+10 | 0.152219E+09 | 0.130022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127903E+10 | 0.280535E+09 | 0.274048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124833E+10 | 0.632000E+09 | 5465978.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125857E+10 | 0.187223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129267E+10 | 0.292376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122787E+10 | 0.667246E+09 | 14421153.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126539E+10 | 7746144.26 | 0.912719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122787E+10 | 36.25 | 0.350933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125857E+10 | 0.00 | 0.557367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149905E+11 | 0.653574E+10 | 0.257362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129267E+10 | 0.292376E+10 | 0.652645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124902E+10 | 0.00 | 0.00 | 0.00 | 0.103361E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126105E+10 | 0.00 | 0.00 | 0.00 | 0.240396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122477E+10 | 0.00 | 0.00 | 0.00 | 0.465689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125977E+10 | 0.00 | 0.00 | 0.00 | 0.123343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126294E+10 | 0.00 | 0.00 | 0.00 | 0.165664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122227E+10 | 0.00 | 0.00 | 0.00 | 0.447393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127535E+10 | 0.00 | 0.00 | 0.00 | 15333614.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133040E+10 | 0.00 | 0.00 | 0.00 | 13076.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156854E+11 | 0.00 | 0.00 | 0.00 | 0.416225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148885E+10 | 0.00 | 0.00 | 0.00 | 0.165664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.132655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120294E+10 | 0.00 | 0.00 | 0.00 | 13322.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136671E+10 | 0.00 | 0.00 | 0.00 | 57154.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140604E+10 | 0.00 | 0.00 | 0.00 | 66227958.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167975E+10 | 0.00 | 0.00 | 0.00 | 0.139926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168337E+10 | 0.00 | 0.00 | 0.00 | 0.260319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.170397E+10 | 0.00 | 0.00 | 0.00 | 0.631137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166680E+10 | 0.00 | 0.00 | 0.00 | 0.872214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167944E+10 | 0.00 | 0.00 | 0.00 | 0.227564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152146E+10 | 0.00 | 0.00 | 0.00 | 8372951.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133677E+10 | 0.00 | 0.00 | 0.00 | 1102984.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178931E+11 | 0.00 | 0.00 | 0.00 | 0.220693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170397E+10 | 0.00 | 0.00 | 0.00 | 0.872214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.157313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142443E+10 | 0.00 | 0.00 | 0.00 | 6.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160444E+10 | 0.00 | 0.00 | 0.00 | 193.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152617E+10 | 0.00 | 0.00 | 0.00 | 58376967.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158879E+10 | 0.00 | 0.00 | 0.00 | 0.110474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154965E+10 | 0.00 | 0.00 | 0.00 | 0.198065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156531E+10 | 0.00 | 0.00 | 0.00 | 0.487957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160444E+10 | 0.00 | 0.00 | 0.00 | 0.685497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152617E+10 | 0.00 | 0.00 | 0.00 | 0.186083E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157313E+10 | 0.00 | 0.00 | 0.00 | 6464253.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152617E+10 | 0.00 | 0.00 | 0.00 | 565338.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186271E+11 | 0.00 | 0.00 | 0.00 | 0.173348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160444E+10 | 0.00 | 0.00 | 0.00 | 0.685497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.157088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142239E+10 | 0.00 | 0.00 | 0.00 | 7.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160214E+10 | 0.00 | 0.00 | 0.00 | 250.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152399E+10 | 0.00 | 0.00 | 0.00 | 56250348.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158651E+10 | 0.00 | 0.00 | 0.00 | 0.106965E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154744E+10 | 0.00 | 0.00 | 0.00 | 0.195274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156307E+10 | 0.00 | 0.00 | 0.00 | 0.486016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160214E+10 | 0.00 | 0.00 | 0.00 | 0.684608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152399E+10 | 0.00 | 0.00 | 0.00 | 0.183989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157088E+10 | 0.00 | 0.00 | 0.00 | 6144689.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152399E+10 | 0.00 | 0.00 | 0.00 | 258653.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186005E+11 | 0.00 | 0.00 | 0.00 | 0.171951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160214E+10 | 0.00 | 0.00 | 0.00 | 0.684608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.156809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159930E+10 | 0.00 | 0.00 | 0.00 | 388.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152129E+10 | 0.00 | 0.00 | 0.00 | 50763510.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158370E+10 | 0.00 | 0.00 | 0.00 | 95957776.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154469E+10 | 0.00 | 0.00 | 0.00 | 0.181806E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156029E+10 | 0.00 | 0.00 | 0.00 | 0.465702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159930E+10 | 0.00 | 0.00 | 0.00 | 0.661987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152129E+10 | 0.00 | 0.00 | 0.00 | 0.173039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156809E+10 | 0.00 | 0.00 | 0.00 | 5045127.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152129E+10 | 0.00 | 0.00 | 0.00 | 15.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185675E+11 | 0.00 | 0.00 | 0.00 | 0.163430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159930E+10 | 0.00 | 0.00 | 0.00 | 0.661987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.111517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.964727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.914834E+09 | 0.00 | 0.00 | 0.00 | 83482464.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.921979E+09 | 0.00 | 0.00 | 0.00 | 0.169928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.897950E+09 | 0.00 | 0.00 | 0.00 | 0.362940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.905334E+09 | 0.00 | 0.00 | 0.00 | 0.956195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.930876E+09 | 0.00 | 0.00 | 0.00 | 0.133228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.883230E+09 | 0.00 | 0.00 | 0.00 | 0.359984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.932968E+09 | 0.00 | 0.00 | 0.00 | 11234970.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.994998E+09 | 0.00 | 0.00 | 0.00 | 293508.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115576E+11 | 0.00 | 0.00 | 0.00 | 0.327633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.883230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111517E+10 | 0.00 | 0.00 | 0.00 | 0.133228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.122997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125650E+10 | 0.00 | 0.00 | 0.00 | 49.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119351E+10 | 0.00 | 0.00 | 0.00 | 42245208.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124324E+10 | 0.00 | 0.00 | 0.00 | 78721451.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121340E+10 | 0.00 | 0.00 | 0.00 | 0.160901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122334E+10 | 0.00 | 0.00 | 0.00 | 0.428525E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125650E+10 | 0.00 | 0.00 | 0.00 | 0.621829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119351E+10 | 0.00 | 0.00 | 0.00 | 0.153912E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122997E+10 | 0.00 | 0.00 | 0.00 | 4236189.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119351E+10 | 0.00 | 0.00 | 0.00 | 757.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145707E+11 | 0.00 | 0.00 | 0.00 | 0.149037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125650E+10 | 0.00 | 0.00 | 0.00 | 0.621829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.121899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118285E+10 | 0.00 | 0.00 | 0.00 | 41001971.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123213E+10 | 0.00 | 0.00 | 0.00 | 75807482.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120256E+10 | 0.00 | 0.00 | 0.00 | 0.156471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121242E+10 | 0.00 | 0.00 | 0.00 | 0.420529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124528E+10 | 0.00 | 0.00 | 0.00 | 0.612757E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118285E+10 | 0.00 | 0.00 | 0.00 | 0.150753E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121899E+10 | 0.00 | 0.00 | 0.00 | 3958144.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118285E+10 | 0.00 | 0.00 | 0.00 | 627.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144406E+11 | 0.00 | 0.00 | 0.00 | 0.146128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124528E+10 | 0.00 | 0.00 | 0.00 | 0.612757E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.120192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116628E+10 | 0.00 | 0.00 | 0.00 | 37368349.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121488E+10 | 0.00 | 0.00 | 0.00 | 67657805.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118572E+10 | 0.00 | 0.00 | 0.00 | 0.144134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119544E+10 | 0.00 | 0.00 | 0.00 | 0.399901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122784E+10 | 0.00 | 0.00 | 0.00 | 0.592161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116628E+10 | 0.00 | 0.00 | 0.00 | 0.142281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120192E+10 | 0.00 | 0.00 | 0.00 | 3019897.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142384E+11 | 0.00 | 0.00 | 0.00 | 0.138652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122784E+10 | 0.00 | 0.00 | 0.00 | 0.592161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.126543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122787E+10 | 0.00 | 0.00 | 0.00 | 34492694.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127903E+10 | 0.00 | 0.00 | 0.00 | 61413972.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124833E+10 | 0.00 | 0.00 | 0.00 | 0.137455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125857E+10 | 0.00 | 0.00 | 0.00 | 0.395351E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129267E+10 | 0.00 | 0.00 | 0.00 | 0.609234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122787E+10 | 0.00 | 0.00 | 0.00 | 0.140625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126539E+10 | 0.00 | 0.00 | 0.00 | 1769889.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122787E+10 | 0.00 | 0.00 | 0.00 | 8.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149905E+11 | 0.00 | 0.00 | 0.00 | 0.138034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129267E+10 | 0.00 | 0.00 | 0.00 | 0.609234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.367967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590632E+10 | 0.00 | 0.00 | 0.35 |
February | 0.358214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429601E+10 | 0.00 | 0.00 | 0.35 |
March | 0.507815E+10 | 0.00 | 0.00 | 7099.59 | 0.00 | 0.205125E+10 | 13607173.74 | 0.00 | 0.35 |
April | 0.486717E+10 | 16601830.56 | 0.00 | 941366.81 | 0.00 | 0.458333E+09 | 0.611139E+09 | 0.00 | 0.38 |
May | 0.397835E+10 | 7358877.20 | 0.00 | 3782332.22 | 0.00 | 3521921.97 | 0.199912E+10 | 0.00 | 0.47 |
June | 0.144695E+10 | 15249903.12 | 0.00 | 8771651.64 | 0.00 | 0.00 | 0.447128E+10 | 0.00 | 0.62 |
July | 0.308573E+09 | 0.220950E+09 | 0.00 | 12415878.89 | 0.00 | 0.00 | 0.512641E+10 | 0.00 | 0.74 |
August | 0.243437E+09 | 0.510569E+09 | 0.00 | 12641228.76 | 0.00 | 0.00 | 0.422180E+10 | 0.00 | 0.71 |
September | 0.184104E+10 | 15922303.42 | 0.00 | 7871860.46 | 0.00 | 0.00 | 0.426763E+10 | 0.00 | 0.59 |
October | 0.476910E+10 | 0.00 | 0.00 | 1526541.49 | 0.00 | 0.225661E+09 | 0.147013E+10 | 0.00 | 0.38 |
November | 0.458721E+10 | 0.00 | 0.00 | 65580.50 | 0.00 | 0.292477E+10 | 95226307.56 | 0.00 | 0.35 |
December | 0.414179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497519E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.385236E+11 | 0.786652E+09 | 0.00 | 48023540.36 | 0.00 | 0.208411E+11 | 0.222763E+11 | 0.00 | 0.47 |
Minimum of Months | 0.243437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.507815E+10 | 0.510569E+09 | 0.00 | 12641228.76 | 0.00 | 0.590632E+10 | 0.512641E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235628E+10 | 0.00 | 0.00 | 0.26 |
February | 0.144044E+10 | 0.00 | 0.00 | 36093.23 | 0.00 | 0.142770E+10 | 59265732.53 | 0.00 | 0.26 |
March | 0.236367E+10 | 0.00 | 0.00 | 66155.99 | 0.00 | 0.355663E+09 | 0.111622E+09 | 0.00 | 0.27 |
April | 0.191018E+10 | 8057384.71 | 0.00 | 1011141.93 | 0.00 | 8322554.43 | 0.932838E+09 | 0.00 | 0.38 |
May | 0.890896E+09 | 3919601.54 | 0.00 | 3514521.22 | 0.00 | 0.00 | 0.301921E+10 | 0.00 | 0.64 |
June | 0.187072E+09 | 7473287.19 | 0.00 | 5857383.53 | 0.00 | 0.00 | 0.427143E+10 | 0.00 | 0.96 |
July | 23935087.30 | 97200567.65 | 0.00 | 6728702.13 | 0.00 | 0.00 | 0.404552E+10 | 0.00 | 1.09 |
August | 21545924.21 | 0.234439E+09 | 0.00 | 6114097.48 | 0.00 | 0.00 | 0.326561E+10 | 0.00 | 0.98 |
September | 0.362145E+09 | 6056404.24 | 0.00 | 5349969.88 | 0.00 | 0.00 | 0.408199E+10 | 0.00 | 0.89 |
October | 0.168207E+10 | 0.00 | 0.00 | 1775486.30 | 0.00 | 0.00 | 0.188201E+10 | 0.00 | 0.43 |
November | 0.178942E+10 | 0.00 | 0.00 | 189587.63 | 0.00 | 0.103367E+10 | 0.247953E+09 | 0.00 | 0.29 |
December | 0.141472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192472E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.132624E+11 | 0.357146E+09 | 0.00 | 30643139.31 | 0.00 | 0.710635E+10 | 0.219175E+11 | 0.00 | 0.56 |
Minimum of Months | 21545924.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.236367E+10 | 0.234439E+09 | 0.00 | 6728702.13 | 0.00 | 0.235628E+10 | 0.427143E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.874364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254687E+10 | 0.00 | 0.00 | 0.26 |
February | 0.109387E+10 | 0.00 | 0.00 | 8606.39 | 0.00 | 0.168731E+10 | 25887176.11 | 0.00 | 0.26 |
March | 0.213747E+10 | 0.00 | 0.00 | 15535.19 | 0.00 | 0.509494E+09 | 45985618.36 | 0.00 | 0.27 |
April | 0.188386E+10 | 8475456.04 | 0.00 | 443320.71 | 0.00 | 43279556.84 | 0.420474E+09 | 0.00 | 0.33 |
May | 0.104936E+10 | 4315228.16 | 0.00 | 1990840.92 | 0.00 | 0.00 | 0.181147E+10 | 0.00 | 0.53 |
June | 0.303048E+09 | 8863338.79 | 0.00 | 3554071.89 | 12785.18 | 0.00 | 0.292369E+10 | 0.00 | 0.77 |
July | 99673203.02 | 93589845.18 | 0.00 | 3950739.94 | 1657830.49 | 0.00 | 0.276446E+10 | 0.00 | 0.89 |
August | 99305527.57 | 0.223402E+09 | 0.00 | 3365552.24 | 3073466.84 | 0.00 | 0.240713E+10 | 0.00 | 0.82 |
September | 0.501410E+09 | 6976147.67 | 0.00 | 3151574.38 | 0.00 | 0.00 | 0.258115E+10 | 0.00 | 0.70 |
October | 0.175016E+10 | 0.00 | 0.00 | 921323.07 | 0.00 | 0.00 | 0.105909E+10 | 0.00 | 0.36 |
November | 0.160123E+10 | 0.00 | 0.00 | 57662.15 | 0.00 | 0.111735E+10 | 80413509.50 | 0.00 | 0.27 |
December | 0.109200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212203E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.124857E+11 | 0.345622E+09 | 0.00 | 17459226.86 | 4744082.51 | 0.802632E+10 | 0.141198E+11 | 0.00 | 0.48 |
Minimum of Months | 99305527.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.213747E+10 | 0.223402E+09 | 0.00 | 3950739.94 | 3073466.84 | 0.254687E+10 | 0.292369E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.762949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265786E+10 | 0.00 | 0.00 | 0.26 |
February | 0.100806E+10 | 0.00 | 0.00 | 3154.86 | 0.00 | 0.178120E+10 | 8438170.80 | 0.00 | 0.26 |
March | 0.200200E+10 | 0.00 | 0.00 | 10727.05 | 0.00 | 0.634212E+09 | 37751882.21 | 0.00 | 0.27 |
April | 0.188309E+10 | 8459580.65 | 0.00 | 396845.96 | 0.00 | 60197462.72 | 0.360168E+09 | 0.00 | 0.32 |
May | 0.110389E+10 | 4261467.50 | 0.00 | 1856530.82 | 0.00 | 0.00 | 0.169091E+10 | 0.00 | 0.52 |
June | 0.328955E+09 | 8849440.38 | 0.00 | 3473678.52 | 12943.44 | 0.00 | 0.285692E+10 | 0.00 | 0.77 |
July | 0.107225E+09 | 93556364.43 | 0.00 | 3919871.32 | 1656817.18 | 0.00 | 0.274118E+10 | 0.00 | 0.88 |
August | 0.104528E+09 | 0.223296E+09 | 0.00 | 3362461.71 | 3068770.74 | 0.00 | 0.239793E+10 | 0.00 | 0.82 |
September | 0.520436E+09 | 6875380.80 | 0.00 | 3070614.24 | 0.00 | 0.00 | 0.251685E+10 | 0.00 | 0.69 |
October | 0.176134E+10 | 0.00 | 0.00 | 846156.83 | 0.00 | 4732810.51 | 0.979113E+09 | 0.00 | 0.35 |
November | 0.151307E+10 | 0.00 | 0.00 | 46886.12 | 0.00 | 0.120354E+10 | 66028950.09 | 0.00 | 0.27 |
December | 0.985889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222689E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.120814E+11 | 0.345298E+09 | 0.00 | 16986927.44 | 4738531.35 | 0.856863E+10 | 0.136553E+11 | 0.00 | 0.47 |
Minimum of Months | 0.104528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.200200E+10 | 0.223296E+09 | 0.00 | 3919871.32 | 3068770.74 | 0.265786E+10 | 0.285692E+10 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.586073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283415E+10 | 0.00 | 0.00 | 0.26 |
February | 0.864245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192112E+10 | 0.00 | 0.00 | 0.26 |
March | 0.177956E+10 | 0.00 | 0.00 | 2383.76 | 0.00 | 0.840359E+09 | 20388792.79 | 0.00 | 0.27 |
April | 0.177498E+10 | 8437273.02 | 0.00 | 296636.71 | 0.00 | 0.158663E+09 | 0.281235E+09 | 0.00 | 0.31 |
May | 0.129969E+10 | 4035665.60 | 0.00 | 1408411.49 | 0.00 | 0.00 | 0.127806E+10 | 0.00 | 0.49 |
June | 0.424520E+09 | 8831671.12 | 0.00 | 3037102.83 | 13690.40 | 0.00 | 0.255393E+10 | 0.00 | 0.73 |
July | 0.131917E+09 | 92539379.09 | 0.00 | 3626035.31 | 1667880.84 | 0.00 | 0.260224E+10 | 0.00 | 0.86 |
August | 0.132347E+09 | 0.221312E+09 | 0.00 | 3100231.86 | 3083646.87 | 0.00 | 0.227458E+10 | 0.00 | 0.80 |
September | 0.656876E+09 | 6384173.60 | 0.00 | 2666836.38 | 0.00 | 0.00 | 0.218391E+10 | 0.00 | 0.66 |
October | 0.176113E+10 | 0.00 | 0.00 | 635244.93 | 0.00 | 51992510.87 | 0.773042E+09 | 0.00 | 0.33 |
November | 0.131609E+10 | 0.00 | 0.00 | 30374.86 | 0.00 | 0.138732E+10 | 48434051.09 | 0.00 | 0.27 |
December | 0.785711E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242533E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.115131E+11 | 0.341540E+09 | 0.00 | 14803258.13 | 4765218.11 | 0.961894E+10 | 0.120158E+11 | 0.00 | 0.46 |
Minimum of Months | 0.131917E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.177956E+10 | 0.221312E+09 | 0.00 | 3626035.31 | 3083646.87 | 0.283415E+10 | 0.260224E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.464956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692447E+10 | 0.00 | 0.00 | 0.27 |
February | 0.127170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470803E+10 | 0.00 | 0.00 | 0.27 |
March | 0.337457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218706E+10 | 0.00 | 0.00 | 0.28 |
April | 0.350675E+10 | 10912450.72 | 0.00 | 381090.91 | 0.00 | 0.529768E+09 | 0.259996E+09 | 0.00 | 0.29 |
May | 0.328901E+10 | 1959534.00 | 0.00 | 1593012.32 | 0.00 | 12997081.64 | 0.925171E+09 | 0.00 | 0.35 |
June | 0.141684E+10 | 7640420.62 | 0.00 | 4422258.50 | 6338.62 | 0.00 | 0.265645E+10 | 0.00 | 0.44 |
July | 0.380646E+09 | 0.176125E+09 | 0.00 | 6079442.17 | 2260399.15 | 0.00 | 0.298986E+10 | 0.00 | 0.51 |
August | 0.222217E+09 | 0.441679E+09 | 0.00 | 5154273.19 | 2196781.45 | 0.00 | 0.264260E+10 | 0.00 | 0.49 |
September | 0.190921E+10 | 3450129.40 | 0.00 | 3884979.01 | 0.00 | 0.00 | 0.210865E+10 | 0.00 | 0.41 |
October | 0.373448E+10 | 0.00 | 0.00 | 524186.99 | 0.00 | 0.381300E+09 | 0.554368E+09 | 0.00 | 0.29 |
November | 0.217980E+10 | 0.00 | 0.00 | 37018.08 | 0.00 | 0.361624E+10 | 52581601.64 | 0.00 | 0.28 |
December | 0.829399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613958E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.225796E+11 | 0.641767E+09 | 0.00 | 22076261.17 | 4463519.23 | 0.244994E+11 | 0.121897E+11 | 0.00 | 0.35 |
Minimum of Months | 0.222217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.373448E+10 | 0.441679E+09 | 0.00 | 6079442.17 | 2260399.15 | 0.692447E+10 | 0.298986E+10 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351918E+10 | 0.00 | 0.00 | 0.27 |
February | 0.583837E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239869E+10 | 0.00 | 0.00 | 0.27 |
March | 0.155315E+10 | 0.00 | 0.00 | 168.67 | 0.00 | 0.122661E+10 | 3609394.37 | 0.00 | 0.28 |
April | 0.168554E+10 | 5532992.29 | 0.00 | 205981.53 | 0.00 | 0.339658E+09 | 0.196810E+09 | 0.00 | 0.31 |
May | 0.158598E+10 | 873199.66 | 0.00 | 890810.36 | 0.00 | 6736575.39 | 0.761240E+09 | 0.00 | 0.42 |
June | 0.593946E+09 | 3683510.28 | 0.00 | 2358087.88 | 0.00 | 0.00 | 0.196870E+10 | 0.00 | 0.61 |
July | 0.148972E+09 | 77966474.92 | 0.00 | 3182811.02 | 868193.50 | 0.00 | 0.218111E+10 | 0.00 | 0.73 |
August | 94646864.66 | 0.203262E+09 | 0.00 | 2745281.58 | 857825.52 | 0.00 | 0.189628E+10 | 0.00 | 0.68 |
September | 0.826075E+09 | 1089458.94 | 0.00 | 2131978.66 | 0.00 | 0.00 | 0.166565E+10 | 0.00 | 0.55 |
October | 0.171139E+10 | 0.00 | 0.00 | 368425.02 | 0.00 | 0.241069E+09 | 0.518097E+09 | 0.00 | 0.31 |
November | 0.101652E+10 | 0.00 | 0.00 | 17711.10 | 0.00 | 0.187508E+10 | 37448041.15 | 0.00 | 0.28 |
December | 0.343490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312619E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.103044E+11 | 0.292407E+09 | 0.00 | 11901255.82 | 1726019.03 | 0.127332E+11 | 0.922894E+10 | 0.00 | 0.42 |
Minimum of Months | 94646864.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.171139E+10 | 0.203262E+09 | 0.00 | 3182811.02 | 868193.50 | 0.351918E+10 | 0.218111E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.149940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353010E+10 | 0.00 | 0.00 | 0.27 |
February | 0.556926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242462E+10 | 0.00 | 0.00 | 0.27 |
March | 0.150502E+10 | 0.00 | 0.00 | 4.83 | 0.00 | 0.127412E+10 | 1142522.89 | 0.00 | 0.28 |
April | 0.165272E+10 | 5479742.37 | 0.00 | 193099.18 | 0.00 | 0.369342E+09 | 0.188391E+09 | 0.00 | 0.31 |
May | 0.160609E+10 | 814623.77 | 0.00 | 831664.64 | 0.00 | 7357572.64 | 0.706995E+09 | 0.00 | 0.42 |
June | 0.623131E+09 | 3630182.01 | 0.00 | 2254124.42 | 0.00 | 0.00 | 0.188805E+10 | 0.00 | 0.60 |
July | 0.159341E+09 | 76972601.25 | 0.00 | 3085018.39 | 862997.16 | 0.00 | 0.212796E+10 | 0.00 | 0.72 |
August | 99193387.93 | 0.201249E+09 | 0.00 | 2675677.85 | 854102.70 | 0.00 | 0.185895E+10 | 0.00 | 0.67 |
September | 0.843333E+09 | 995633.13 | 0.00 | 2057248.87 | 0.00 | 0.00 | 0.161033E+10 | 0.00 | 0.55 |
October | 0.167365E+10 | 0.00 | 0.00 | 336055.05 | 0.00 | 0.294633E+09 | 0.481629E+09 | 0.00 | 0.31 |
November | 0.941828E+09 | 0.00 | 0.00 | 16224.10 | 0.00 | 0.194990E+10 | 34539512.08 | 0.00 | 0.28 |
December | 0.301162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316856E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.101123E+11 | 0.289142E+09 | 0.00 | 11449117.33 | 1717099.85 | 0.130186E+11 | 0.889799E+10 | 0.00 | 0.41 |
Minimum of Months | 99193387.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.167365E+10 | 0.201249E+09 | 0.00 | 3085018.39 | 862997.16 | 0.353010E+10 | 0.212796E+10 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 49086872.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363106E+10 | 0.00 | 0.00 | 0.27 |
February | 0.390532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258785E+10 | 0.00 | 0.00 | 0.27 |
March | 0.123516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153669E+10 | 0.00 | 0.00 | 0.28 |
April | 0.147477E+10 | 5420345.27 | 0.00 | 146132.68 | 0.00 | 0.544341E+09 | 0.153770E+09 | 0.00 | 0.30 |
May | 0.160894E+10 | 700793.33 | 0.00 | 665565.58 | 0.00 | 42357098.41 | 0.561970E+09 | 0.00 | 0.40 |
June | 0.717326E+09 | 3577510.36 | 0.00 | 1919204.32 | 0.00 | 0.00 | 0.163025E+10 | 0.00 | 0.56 |
July | 0.207236E+09 | 75805259.41 | 0.00 | 2772625.53 | 869989.30 | 0.00 | 0.194291E+10 | 0.00 | 0.69 |
August | 0.125160E+09 | 0.199059E+09 | 0.00 | 2428603.11 | 860320.90 | 0.00 | 0.172371E+10 | 0.00 | 0.65 |
September | 0.936129E+09 | 853813.46 | 0.00 | 1806042.57 | 0.00 | 0.00 | 0.138043E+10 | 0.00 | 0.52 |
October | 0.161992E+10 | 0.00 | 0.00 | 221994.80 | 0.00 | 0.424384E+09 | 0.335717E+09 | 0.00 | 0.30 |
November | 0.720697E+09 | 0.00 | 0.00 | 11750.91 | 0.00 | 0.216869E+10 | 28568880.61 | 0.00 | 0.28 |
December | 0.163274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330649E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.924823E+10 | 0.285417E+09 | 0.00 | 9971919.50 | 1730310.20 | 0.142419E+11 | 0.775732E+10 | 0.00 | 0.40 |
Minimum of Months | 49086872.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.161992E+10 | 0.199059E+09 | 0.00 | 2772625.53 | 869989.30 | 0.363106E+10 | 0.194291E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365619E+10 | 0.00 | 0.00 | 0.27 |
February | 0.134608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281774E+10 | 0.00 | 0.00 | 0.27 |
March | 0.495159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224574E+10 | 0.00 | 0.00 | 0.28 |
April | 0.101283E+10 | 5614673.08 | 0.00 | 94301.02 | 0.00 | 0.999783E+09 | 0.100065E+09 | 0.00 | 0.30 |
May | 0.146185E+10 | 682688.00 | 0.00 | 522898.94 | 0.00 | 0.163421E+09 | 0.448443E+09 | 0.00 | 0.39 |
June | 0.792279E+09 | 3848715.93 | 0.00 | 1614335.09 | 0.00 | 0.00 | 0.140365E+10 | 0.00 | 0.55 |
July | 0.266030E+09 | 78961356.36 | 0.00 | 2431177.47 | 899068.11 | 0.00 | 0.174057E+10 | 0.00 | 0.68 |
August | 0.182834E+09 | 0.207638E+09 | 0.00 | 2103885.63 | 873436.80 | 0.00 | 0.151861E+10 | 0.00 | 0.63 |
September | 0.993667E+09 | 957793.83 | 0.00 | 1606290.07 | 0.00 | 8998409.88 | 0.117718E+10 | 0.00 | 0.51 |
October | 0.125323E+10 | 0.00 | 0.00 | 133623.68 | 0.00 | 0.799970E+09 | 0.230135E+09 | 0.00 | 0.30 |
November | 0.273664E+09 | 0.00 | 0.00 | 7465.93 | 0.00 | 0.258391E+10 | 23575319.82 | 0.00 | 0.28 |
December | 17365677.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342899E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.688351E+10 | 0.297703E+09 | 0.00 | 8513977.81 | 1772504.91 | 0.167047E+11 | 0.664224E+10 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.146185E+10 | 0.207638E+09 | 0.00 | 2431177.47 | 899068.11 | 0.365619E+10 | 0.174057E+10 | 0.00 | 0.68 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:39:22
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.400546E+11 | 0.298074E+11 | 0.00 | 0.470620E+11 | 0.735255E+10 |
February | 0.116210E+12 | 0.239884E+11 | 0.00 | 0.384236E+11 | 0.493001E+10 |
March | 0.231549E+12 | 0.217888E+11 | 0.00 | 0.358192E+11 | 0.251550E+10 |
April | 0.387089E+12 | 0.173172E+11 | 0.00 | 0.290964E+11 | 0.389622E+10 |
May | 0.525799E+12 | 0.152330E+11 | 0.00 | 0.313480E+11 | 0.630566E+10 |
June | 0.536616E+12 | 0.114754E+11 | 0.00 | 0.334349E+11 | 0.123008E+11 |
July | 0.571779E+12 | 0.696742E+10 | 0.00 | 0.290658E+11 | 0.326880E+11 |
August | 0.441357E+12 | 0.442894E+10 | 0.00 | 0.229143E+11 | 0.464457E+11 |
September | 0.300349E+12 | 0.111877E+11 | 0.00 | 0.329669E+11 | 0.120311E+11 |
October | 0.170893E+12 | 0.181210E+11 | 0.00 | 0.327293E+11 | 0.879320E+09 |
November | 0.560902E+11 | 0.235051E+11 | 0.00 | 0.376895E+11 | 0.361572E+10 |
December | 0.216534E+11 | 0.275931E+11 | 0.00 | 0.445215E+11 | 0.619282E+10 |
Annual Sum or Average | 0.339944E+13 | 0.211413E+12 | 0.00 | 0.415072E+12 | 0.139153E+12 |
Minimum of Months | 0.216534E+11 | 0.442894E+10 | 0.00 | 0.229143E+11 | 0.879320E+09 |
Maximum of Months | 0.571779E+12 | 0.298074E+11 | 0.00 | 0.470620E+11 | 0.464457E+11 |