Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2023-10-16 10:41:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1069.74 | 221.24 | 221.24 |
Net Site Energy | 1069.74 | 221.24 | 221.24 |
Total Source Energy | 2105.92 | 435.54 | 435.54 |
Net Source Energy | 2105.92 | 435.54 | 435.54 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 615.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 29.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 454.30 | 615.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 615.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 22.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 147.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 27.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 615.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 22.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 147.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 92.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 29.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 25.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 49.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.96 | 127.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 93.96 | 127.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 49.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.96 | 127.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 93.96 | 127.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 454.304 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 454.304 | 100.00 |
Total On-Site and Utility Electric Sources | 454.304 | 100.00 |
Total Electricity End Uses | 454.304 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 57.17 |
Time Setpoint Not Met During Occupied Cooling | 15.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3155.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 76.79 |
Skylight-Roof Ratio [%] | 1.67 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.8432 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.2431 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.6162 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.6162 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.8432 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 10.2257 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.2431 | 46.45 | 2.5587 | |
Total | 4835.13 | 7.6162 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 7.6162 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 7.6162 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-AUG-14:50 | 06-FEB-00:49 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 302990.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12347.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9715.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4146.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1727.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 37971.60 | 302990.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 302990.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 12347.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 9715.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1840.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1727.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 667.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 69.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 468.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 293.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 93.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 80.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1438.78 | 667.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 137.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 96.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 297.57 | 137.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 137.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 96.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 297.57 | 137.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.09 |
ZONE2 FINE STORAGE DIRECT AIR | 2.55 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 5.05 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 5.05 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 206454.46 |
PSZ-OFFICE HEATING COIL | 29007.56 |
PSZ-FINE STORAGE HEATING COIL | 88947.31 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 206454.46 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.00 | 1.00 | 1.09 |
PSZ-FINE STORAGE | 2.55 | 2.55 | 2.55 | 2.55 | 2.55 | 2.55 | 1.00 | 1.000000 | 2.55 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.09 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.55 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.09 | 1211.42 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.55 | 2730.73 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.09 | 1.09 | 1.09 | 0.722155 | 21456.82 | 29007.56 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.55 | 2.55 | 2.55 | 1.68 | 63371.41 | 88947.31 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.09 | 0.547087 | 0.729447 | 21456.82 | 10728.41 | 0.784350 | 0.784350 |
PSZ-FINE STORAGE COOLING COIL | 2.55 | 1.28 | 1.70 | 63371.41 | 31685.71 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.843 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.917 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 10.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.226 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.243 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.802 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2568.536 | 10.843 | 201.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2568.536 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 14248.589 | 10.226 | 474.953 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 14248.589 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 20008.023 | 6.243 | 289.971 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20008.023 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2163 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.4974 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4322 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.622 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.010 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.214 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.18741198E-13 | -0.13599760E-18 | 0.18147593E-18 | 0.0000000 |
2 | 1 | -5.2160601 | 0.51384690E-04 | -0.74050972E-04 | 0.35929797E-14 |
3 | 0 | 5.4323994 | 0.21628790 | 0.21641333 | |
4 | 2 | 0.53330648E-11 | 0.17872838E-15 | 0.22136589E-15 | 0.0000000 |
5 | 1 | -5.2159880 | 0.41449123E-04 | -0.32205733E-04 | 0.68736940E-11 |
6 | 0 | 5.7134214 | 0.49739196 | 0.49746561 | |
7 | 4 | 0.79186034E-12 | 0.10405078E-15 | -0.20960309E-14 | 0.11445272E-15 |
8 | 3 | -0.38819576E-03 | 0.30481201E-06 | -0.56344247E-04 | 0.15193845E-12 |
9 | 2 | 1.7477700 | 0.66393353E-02 | 1.1467116 | -0.74423695E-04 |
10 | 1 | -7.1178476 | 0.17160399 | -17.138090 | 0.33498210 |
11 | 0 | 5.6579463 | 0.10923685 | 16.278915 | |
12 | 4 | 0.65556131E-12 | 0.57298371E-15 | -0.14028959E-14 | 0.12439065E-15 |
13 | 3 | -0.34087882E-03 | 0.75102955E-06 | -0.49042705E-04 | 0.12583838E-12 |
14 | 2 | 1.6337693 | 0.17263784E-01 | 1.0601096 | -0.65347397E-04 |
15 | 1 | -7.2734424 | 0.46143774 | -16.581274 | 0.31301327 |
16 | 0 | 6.4190060 | 0.30028979 | 16.300205 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.14028959E-14 | 0.57298371E-15 | 0.65556131E-12 | 0.12439065E-15 |
85 | 3 | -0.49042705E-04 | 0.75102955E-06 | -0.34087882E-03 | 0.12583838E-12 |
86 | 2 | 1.0601096 | 0.17263784E-01 | 1.6337693 | -0.65347397E-04 |
87 | 1 | -16.581274 | 0.46143774 | -7.2734424 | 0.31301327 |
88 | 0 | 16.300205 | 0.30028979 | 6.4190060 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.419_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.419_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.419_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.419_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_0.5_SHGC_0.4 | 38 | 1 | VerySmooth | 2.843 | 2.843 | 1.000 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | CurtainWall | 2.775 | 0.408 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.537 | 0.515 | 0.496 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.4369E-005 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4584E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4608E-005 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8270E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4960E-005 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6099E-004 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5724E-005 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5867E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5904E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.3770E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3291E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.7612E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5138E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8677E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3414E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4540E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5905E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5802E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9979E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7510E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.5972E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2051E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8792E-004 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6675E-005 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7996E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8809E-005 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1397E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.5410E-005 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0560E-003 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3417E-005 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3392E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0724E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.0152E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3696E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.2539E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6347E-005 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.9325E-004 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9057E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9718E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6272E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.9691E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.3974E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.3982E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5117E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5631E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4056E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7955E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4789E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0245E-003 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5531E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2350E-003 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7062E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1788E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4469E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3679E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4861E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8475E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8692E-005 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0848E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2621E-005 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8803E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0430E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1133E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6508E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5615E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0845E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4589E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2022E-004 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3236E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.9051E-005 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5808E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1684E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8563E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5628E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.8425E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0011E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.3306E-004 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5040E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6286E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1734E-005 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0322E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.3680E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6654E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0113E-003 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9028E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.7191E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3102E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8162E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3113E-005 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7135E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1067E-005 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9788E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0450E-005 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5473E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0760E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8446E-004 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2075E-005 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7588E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7703E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7201E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8419E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5064E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7398E-005 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1825E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0046E-005 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2793E-004 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.6225E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.7630E-004 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7432E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1203E-003 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5431E-005 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2422E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9249E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3186E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2820E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0388E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1763E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5406E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1321E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9767E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9313E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8592E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7543E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9782E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3130E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7768E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4814E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2243E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8961E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0313E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2690E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8709E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2185E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0422E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1298E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2681E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9734E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8332E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4441E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0345E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9011E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3830E-004 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5955E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2983E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0758E-004 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4489E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1242E-004 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3430E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6713E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2844E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1757E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1077E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1526E-004 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6257E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2212E-004 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5781E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9377E-005 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7059E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1734E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2731E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2852E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4457E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8503E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5765E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9642E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0392E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5935E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1887E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5531E-004 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3445E-003 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5813E-004 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6463E-003 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6119E-004 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0539E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6979E-005 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3777E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6160E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1749E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6593E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4649E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9780E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8740E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0720E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4148E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4151E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2161E-005 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6981E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1446E-005 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1936E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5572E-005 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0708E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6592E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6678E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9294E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7233E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8141E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6683E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1341E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6898E-005 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5662E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3129E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0709E-004 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4668E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0211E-004 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3450E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2484E-004 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2032E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0902E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2094E-003 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7738E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3343E-003 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9145E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2960E-003 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7864E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2112E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4671E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1828E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1361E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1364E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9397E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6867E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4853E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7473E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9066E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0554E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1942E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9849E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5530E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5878E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9271E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7498E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5506E-004 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2910E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1588E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0897E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8990E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2424E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5587E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7446E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1536E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4169E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0979E-004 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3837E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0042E-004 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0540E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3670E-004 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2227E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1450E-004 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3594E-003 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1274E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3149E-003 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7688E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9945E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8015E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2269E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1533E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2044E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2801E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9924E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2919E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1262E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1378E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7501E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6479E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8536E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9809E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6068E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7004E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4890E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2794E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7296E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1506E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8271E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1238E-003 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5753E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5709E-004 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4105E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5543E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7351E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5793E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0086E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7604E-005 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8249E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6963E-005 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1557E-003 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1616E-004 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1889E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1418E-004 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9216E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6447E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7247E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1188E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1305E-003 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3210E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1930E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0887E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2668E-004 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0741E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0747E-004 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2746E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3537E-004 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3907E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7289E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2588E-004 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3690E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0386E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7224E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6884E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6653E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2909E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0178E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4028E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9086E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9869E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7433E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5924E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3427E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6601E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4795E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1676E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2654E-004 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6712E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0780E-004 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4124E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3875E-004 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8059E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7264E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8999E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3775E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6354E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2104E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3201E-004 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5852E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3722E-004 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5891E-005 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3195E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4809E-004 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1111E-004 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2042E-004 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2968E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2531E-004 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9354E-005 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0257E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3913E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3307E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3300E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1947E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1175E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7051E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3593E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5813E-005 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5594E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3614E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8607E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7231E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9681E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7213E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2843E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0101E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0338E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4750E-004 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1576E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2017E-004 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5333E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2650E-004 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8920E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0246E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6189E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 6.2385E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 7.3294E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.5971E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.6478E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.3542E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.3887E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.1458E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.5232E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.4883E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.7517E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.9594E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.6933E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.5233E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.7210E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.4603E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.2309E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 5.6094E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 4.0252E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.1892E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1679E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.7599E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.3988E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.9456E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.3643E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.6643E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.0273E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.2151E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1690E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.7000E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.3976E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.9455E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.3643E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11076.41604 | 13291.69924 | 0.91181 | 1.09417 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 31.55733 | 1.41187E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 11340.22479 | 13608.26975 | 0.31847 | 0.38216 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70000 | 1.50390E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 33137.30475 | 39764.76570 | 2.12664 | 2.55197 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 39580.33148 | 47496.39778 | 0.93612 | 1.12335 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -10.70000 | 1.50390E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 172045.38146 | 206454.45776 | 4.20504 | 5.04605 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16696.07 | 1.09417 | 1.09417 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 12687.15 | 0.38216 | 0.38216 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 48134.33 | 2.55197 | 2.55197 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 46702.03 | 1.12335 | 1.12335 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09417 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.55197 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.04605 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 5.04605 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 206454.45760 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 206454.45776 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.09417 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.09417 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.09417 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.09417 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.09417 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.09417 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.55197 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.55197 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.55197 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.55197 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.55197 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.55197 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.09417 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.55197 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.09417 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.09417 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1211.42492 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.09417 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.09417 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.09417 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.72216 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.09417 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54709 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.72945 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21456.82000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10728.41000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78435 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78435 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21456.82000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29007.55752 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29007.55752 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.55197 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.55197 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2730.72505 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.55197 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.55197 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.55197 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.68430 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.55197 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.27598 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.70131 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 63371.41000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 31685.70500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 63371.41000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 88947.30578 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 88947.30578 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 20607.3 | 11.78 | 11.52 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 61387.8 | 12.06 | 11.79 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.4089397657 | 0.3903416881 | Pass | Pass | 0.9458659114 | 1.0879307697 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.7993513129 | 0.7901893268 | Pass | Pass | 0.7798873484 | 0.7095737391 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.6272623141E-004 | 2.8065117810E-004 | Pass | Pass | 2.3829282459E-002 | 1.8705452523E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8503.38 | 654.20 | 0.00 | 50.66 | 260.95 | 9469.25 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.210 | 0.216 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.466 | 0.497 | 3204.84 | 3148.87 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.419_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.381 | 0.401 | 0.442 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.419_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.381 | 0.401 | 0.442 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.419_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.381 | 0.401 | 0.442 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.419_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.381 | 0.401 | 0.442 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 94.45 | 4.508 | 0.490 | 0.498 | |||||||||||||||||
North Total or Average | 6.51 | 2.381 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 87.94 | 4.666 | 0.496 | 0.502 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.8432 | 236.88 | 2568.54 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 43.13 | 0.0000 | Y | 20.79 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 10.2257 | 1393.41 | 14248.59 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 22.32 | 0.0000 | Y | 59.71 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.2431 | 3204.84 | 20008.02 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 17.93 | 0.0000 | Y | 67.34 |
Interior Lighting Total | 7.6162 | 4835.13 | 36825.15 | 147.84 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 14248.59 | 3562.15 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 14248.59 | 3562.15 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 20008.02 | 5002.01 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 20008.02 | 5002.01 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.29 | 2568.54 | 744.88 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.10 | 2568.54 | 256.85 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 125.92 | AstronomicalClock | - | 42.43 | 42.43 | 1.00 | |
EXTERIOR_LIGHTS_B | 6860.50 | AstronomicalClock | - | 83.64 | 71.28 | 91.80 | |
Exterior Lighting Total | 6986.42 | 92.80 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21456.82 | 16829.66 | 4627.16 | 0.78 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 63371.41 | 44428.43 | 18942.98 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 20607.3 | 11.78 | 11.52 | ||||
PSZ-FINE STORAGE COOLING COIL | 61387.8 | 12.06 | 11.79 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 206454.46 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29007.56 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 88947.31 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 5.05 | 468.83 | 92.91 | 1.00 | 3.15 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.09 | 1211.42 | 1107.16 | 1.00 | 1.38 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.55 | 2730.73 | 1070.05 | 1.00 | 1.28 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11076.42 | 13291.70 | 56.11 | 0.912 | 1.094 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 23.90 | 23.90 | 0.00859 | 31.56 | 0.01412 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 33137.30 | 39764.77 | 28.54 | 2.127 | 2.552 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 26.70 | 26.70 | 0.00923 | 32.10 | 0.01412 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 0.00 | 32.76 | 0.01419 | 32.10 | 0.01412 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11340.22 | 13608.27 | 57.45 | 0.318 | 0.382 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00693 | -10.70 | 0.00150 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 39580.33 | 47496.40 | 34.09 | 0.936 | 1.123 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00544 | -10.70 | 0.00150 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 172045.38 | 206454.46 | 64.42 | 4.205 | 5.046 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 9.99 | 0.00481 | -10.70 | 0.00150 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.09 | 1.09 | 0.38 | 0.38 | 1.0942 | 1.0942 | 1.0942 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.55 | 2.55 | 1.12 | 1.12 | 2.5520 | 2.5520 | 2.5520 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 206454.458 | 206454.458 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 206454.46 | 206454.46 | 5.046053 | 9.99 | 6.78 | 0.00480580 | 43.33 | 22.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 9.99 | 0.00480580 | 63.2537 | 206454.46 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 21456.820 | 16829.657 | 1.094170 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 10728.41 | 9045.94 | 0.729447 | 25.52 | 17.42 | 0.00910395 | 12.00 | 11.25 | 0.00800000 | 31.66 | 0.01411884 | 23.01 | 14.0222 | 23.90 | 0.00858651 | 46.4783 | 11070.46 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29007.558 | 29007.558 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 29007.56 | 29007.56 | 1.094175 | 18.08 | 12.19 | 0.00642516 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 9.3481 | 21.10 | 0.00693264 | 44.6087 | 11340.22 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 63371.410 | 44428.428 | 2.551970 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31685.71 | 24609.57 | 1.701313 | 28.46 | 19.15 | 0.01004059 | 12.00 | 11.25 | 0.00800000 | 32.10 | 0.01411964 | 23.13 | 24.9637 | 26.70 | 0.00922620 | 42.2408 | 33137.30 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 88947.306 | 88947.306 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 88947.31 | 88947.31 | 2.551967 | 11.18 | 7.33 | 0.00478200 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 16.6425 | 15.55 | 0.00543648 | 49.6626 | 39580.33 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 206454.458 | 206454.458 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 5.046053 | 6.07340466 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 206454.46 | 206454.46 | 1.0000 | 6.07340466 | 5.046053 | 9.99 | 6.78 | 0.00480580 | 22150.6 | 43.33 | 22.14 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 206454.46 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 9.99 | 0.00480580 | 9.99 | 0.00480580 | 63.2537 | 206454.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21456.820 | 16829.657 | 1.094170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7638 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.094175 | 1.31694300 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | Sensible | 10728.41 | 9045.94 | 1.0000 | 0.87795835 | 0.729447 | 25.52 | 17.42 | 0.00910395 | 48847.6 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10728.41 | 31.66 | 0.01411884 | 23.01 | 0.10228463 | 14.0222 | 23.90 | 0.00858651 | 23.90 | 0.00858651 | 46.4783 | 11070.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29007.558 | 29007.558 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.094175 | 1.31694300 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 29007.56 | 29007.56 | 1.0000 | 1.31694300 | 1.094175 | 18.08 | 12.19 | 0.00642516 | 34452.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29007.56 | -10.70 | 0.00150390 | -10.70 | 0.10228463 | 9.3481 | 21.05 | 0.00693264 | 21.10 | 0.00693264 | 44.6087 | 11340.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 63371.410 | 44428.428 | 2.551970 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5049 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.551967 | 3.07153436 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 31685.71 | 24609.57 | 1.0000 | 2.04769219 | 1.701313 | 28.46 | 19.15 | 0.01004059 | 54243.9 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31685.71 | 32.10 | 0.01411964 | 23.13 | 0.42471127 | 24.9637 | 26.70 | 0.00922620 | 26.70 | 0.00922620 | 42.2408 | 33137.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 88947.306 | 88947.306 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.551967 | 3.07153436 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 88947.31 | 88947.31 | 1.0000 | 3.07153436 | 2.551967 | 11.18 | 7.33 | 0.00478200 | 23294.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 88947.31 | -10.70 | 0.00150390 | -10.70 | 0.42471127 | 16.6425 | 15.55 | 0.00543648 | 15.55 | 0.00543648 | 49.6626 | 39580.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialEnthalpy | 0.10 | 1.09 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialEnthalpy | 0.42 | 2.55 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2859.50 | 2473.33 | 1840.17 |
ZONE2 FINE STORAGE | 3187.50 | 3297.17 | 2902.67 |
ZONE3 BULK STORAGE | 3254.17 | 3461.50 | 3116.67 |
Facility | 3337.67 | 3494.50 | 3155.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 83.50 | 15.83 | 48.67 | 15.83 |
ZONE2 FINE STORAGE | 381.67 | 27.67 | 20.33 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 433.83 | 43.50 | 57.17 | 15.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.491 | 0.334 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.42 | 30.00 | 2953.02 | 0.510 | 0.298 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.182 | 0.000 | 0.328 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.42 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.42 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.53 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1773750.49 | 0.00 | 1773750.49 | 2091642.67 | 3865393.16 | 3225648.14 | 5697.19 | 2501.00 | 561.81 | 0.08 |
ZONE2 FINE STORAGE | 5425432.68 | 0.00 | 5425432.68 | 8344355.04 | 13769787.71 | 13393694.68 | 5705.07 | 2715.62 | 339.30 | 6.43 |
ZONE3 BULK STORAGE | 0.00 | 59388436.22 | 59388436.22 | 47698967.53 | 0.11E+09 | 30805497.77 | 7183.84 | 81.50 | 1494.66 | 4981.50 |
Total Facility | 7199183.17 | 59388436.22 | 66587619.39 | 58134965.24 | 0.12E+09 | 47424840.58 | 7980.19 | 2999.83 | 2230.43 | 4981.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1355 | 0.0000 | 0.1355 | 0.0923 | 0.2278 | 0.1023 | 573.27 | 2501.00 | 561.73 |
ZONE2 FINE STORAGE | 0.4124 | 0.0000 | 0.4124 | 0.2424 | 0.6548 | 0.4247 | 587.50 | 2715.62 | 332.88 |
ZONE3 BULK STORAGE | 0.0000 | 3.0754 | 3.0754 | 1.7774 | 4.8528 | 0.9768 | 2800.55 | 36.50 | 798.95 |
Total Facility | 0.5479 | 3.0754 | 3.6233 | 2.1121 | 5.7355 | 1.5038 | 2856.19 | 2954.83 | 1528.90 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2569445.64 | 0.00 | 2569445.64 | 3225648.14 | 5695.02 | 0.00 | 3064.98 | 0.08 |
PSZ-FINE STORAGE | 7859424.78 | 0.00 | 7859424.78 | 13393694.68 | 5701.74 | 0.00 | 3058.26 | 6.43 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1963 | 0.0000 | 0.1963 | 0.1023 | 571.10 | 0.00 | 3064.90 |
PSZ-FINE STORAGE | 0.5974 | 0.0000 | 0.5974 | 0.4247 | 584.17 | 0.00 | 3051.83 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2833.62 | 234.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2928.89 | 134.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2172 | 0.4202 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6935 | 1.0884 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 429 |
Defaulted Fields | 391 |
Fields with Defaults | 1171 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 454.30 | 1924.59 | 16-APR-13:30 | 37971.60 | 02-AUG-14:50 |
Electricity:Building | 286.94 | 1443.59 | 16-APR-13:30 | 24347.90 | 03-JAN-15:50 |
Electricity:Zone:ZONE1 OFFICE | 49.96 | 694.23 | 12-FEB-16:10 | 3408.44 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 284.35 | 1443.59 | 16-APR-13:30 | 24347.90 | 03-JAN-15:50 |
InteriorLights:Electricity | 147.85 | 973.71 | 16-APR-13:30 | 14312.73 | 03-JAN-15:50 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 20.79 | 224.35 | 12-FEB-16:10 | 1573.38 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 147.85 | 973.71 | 16-APR-13:30 | 14312.73 | 03-JAN-15:50 |
LightsWired:InteriorLights:Electricity | 147.85 | 973.71 | 16-APR-13:30 | 14312.73 | 03-JAN-15:50 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 20.79 | 224.35 | 12-FEB-16:10 | 1573.38 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 147.85 | 973.71 | 16-APR-13:30 | 14312.73 | 03-JAN-15:50 |
Electricity:Zone:ZONE2 FINE STORAGE | 59.71 | 311.69 | 12-MAR-11:20 | 5298.77 | 02-JAN-14:30 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 59.71 | 311.69 | 12-MAR-11:20 | 5298.77 | 02-JAN-14:30 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 59.71 | 311.69 | 12-MAR-11:20 | 5298.77 | 02-JAN-14:30 |
Electricity:Zone:ZONE3 BULK STORAGE | 177.27 | 437.68 | 01-JAN-10:20 | 15640.70 | 02-JAN-15:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 67.34 | 437.68 | 01-JAN-10:20 | 7440.58 | 02-JAN-15:50 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 67.34 | 437.68 | 01-JAN-10:20 | 7440.58 | 02-JAN-15:50 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 29.65 | 0.00 | 17-JAN-18:10 | 4215.76 | 02-AUG-15:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 2.59 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-JUL-15:30 |
Ventilation (simple):Fans:Electricity | 2.59 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-JUL-15:30 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 2.59 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-JUL-15:30 |
ElectricityPurchased:Facility | 454.30 | 1924.59 | 16-APR-13:30 | 37971.60 | 02-AUG-14:50 |
ElectricityPurchased:Plant | 454.30 | 1924.59 | 16-APR-13:30 | 37971.60 | 02-AUG-14:50 |
Cogeneration:ElectricityPurchased | 454.30 | 1924.59 | 16-APR-13:30 | 37971.60 | 02-AUG-14:50 |
General:Cogeneration:ElectricityPurchased | 454.30 | 1924.59 | 16-APR-13:30 | 37971.60 | 02-AUG-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 454.30 | 1924.59 | 16-APR-13:30 | 37971.60 | 02-AUG-14:50 |
ElectricityNet:Plant | 454.30 | 1924.59 | 16-APR-13:30 | 37971.60 | 02-AUG-14:50 |
Cogeneration:ElectricityNet | 454.30 | 1924.59 | 16-APR-13:30 | 37971.60 | 02-AUG-14:50 |
General:Cogeneration:ElectricityNet | 454.30 | 1924.59 | 16-APR-13:30 | 37971.60 | 02-AUG-14:50 |
Electricity:HVAC | 49.13 | 0.00 | 17-JAN-18:10 | 14548.44 | 02-AUG-15:10 |
General:Fans:Electricity | 27.07 | 0.00 | 17-JAN-18:10 | 3373.15 | 06-FEB-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 22.06 | 0.00 | 01-JAN-00:10 | 12637.98 | 02-AUG-15:10 |
General:Cooling:Electricity | 22.06 | 0.00 | 01-JAN-00:10 | 12637.98 | 02-AUG-15:10 |
ExteriorLights:Electricity | 92.80 | 0.00 | 01-JAN-07:30 | 6986.42 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.80 | 0.00 | 01-JAN-07:30 | 6986.42 | 01-JAN-06:10 |
Electricity:Plant | 25.44 | 481.00 | 07-APR-05:10 | 2475.04 | 06-FEB-12:50 |
WaterSystems:Electricity | 25.44 | 481.00 | 07-APR-05:10 | 2475.04 | 06-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 25.44 | 481.00 | 07-APR-05:10 | 2475.04 | 06-FEB-12:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 615.44 | 0.00 | 17-JAN-18:10 | 302990.44 | 06-FEB-00:50 |
NaturalGas:HVAC | 615.44 | 0.00 | 17-JAN-18:10 | 302990.44 | 06-FEB-00:50 |
Heating:NaturalGas | 615.44 | 0.00 | 17-JAN-18:10 | 302990.44 | 06-FEB-00:50 |
General:Heating:NaturalGas | 615.44 | 0.00 | 17-JAN-18:10 | 302990.44 | 06-FEB-00:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1090.51 | 0.00 | 17-JAN-18:10 | 478068.44 | 06-FEB-00:50 |
EnergyTransfer:Building | 529.43 | 0.00 | 17-JAN-18:10 | 239627.51 | 06-FEB-00:50 |
EnergyTransfer:Zone:ZONE1 OFFICE | 55.59 | 0.00 | 01-JAN-00:40 | 22751.96 | 06-FEB-07:10 |
Heating:EnergyTransfer | 454.18 | 0.00 | 17-JAN-18:10 | 239627.51 | 06-FEB-00:50 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 28.20 | 0.00 | 01-JAN-00:40 | 22751.96 | 06-FEB-07:10 |
General:Heating:EnergyTransfer | 454.18 | 0.00 | 17-JAN-18:10 | 239627.51 | 06-FEB-00:50 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 28.20 | 0.00 | 01-JAN-00:40 | 22751.96 | 06-FEB-07:10 |
Cooling:EnergyTransfer | 75.25 | 0.00 | 01-JAN-00:10 | 31885.74 | 18-AUG-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 27.39 | 0.00 | 01-JAN-00:10 | 11127.94 | 10-JUL-05:10 |
General:Cooling:EnergyTransfer | 75.25 | 0.00 | 01-JAN-00:10 | 31885.74 | 18-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 27.39 | 0.00 | 01-JAN-00:10 | 11127.94 | 10-JUL-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 142.64 | 0.00 | 01-JAN-00:40 | 50893.17 | 06-FEB-00:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 94.77 | 0.00 | 01-JAN-00:40 | 50893.17 | 06-FEB-00:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 94.77 | 0.00 | 01-JAN-00:40 | 50893.17 | 06-FEB-00:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 47.86 | 0.00 | 01-JAN-00:10 | 22623.43 | 18-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 47.86 | 0.00 | 01-JAN-00:10 | 22623.43 | 18-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 331.20 | 0.00 | 02-JAN-11:00 | 182630.05 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 331.20 | 0.00 | 02-JAN-11:00 | 182630.05 | 06-FEB-01:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 331.20 | 0.00 | 02-JAN-11:00 | 182630.05 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 561.08 | 0.00 | 17-JAN-18:10 | 238440.93 | 06-FEB-00:50 |
HeatingCoils:EnergyTransfer | 468.82 | 0.00 | 17-JAN-18:10 | 238440.93 | 06-FEB-00:50 |
CoolingCoils:EnergyTransfer | 92.26 | 0.00 | 01-JAN-00:10 | 53438.97 | 02-AUG-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 28.202 | -27.385 | 0.000 | 0.000 | 9.964 | 20.795 | 29.165 | 12.181 | 0.000 | 0.908 | 0.001 | 0.000 | -7.189 | 0.000 | -25.246 | -41.394 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 94.772 | -47.862 | 0.000 | 0.000 | 25.144 | 59.710 | 0.000 | 32.226 | 0.000 | 1.126 | 0.003 | 0.000 | -11.752 | 0.000 | -86.963 | -66.402 |
ZONE3 BULK STORAGE | 331.201 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 60.206 | 67.341 | 107.344 | 476.951 | 0.000 | 5.274 | 0.003 | 0.000 | -174.328 | 0.000 | -522.970 | -351.019 |
Total Facility | 331.201 | 0.000 | 122.974 | -75.247 | 0.000 | 0.000 | 95.314 | 147.846 | 136.508 | 521.358 | 0.000 | 7.308 | 0.007 | 0.000 | -193.269 | 0.000 | -635.179 | -458.815 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 11-SEP-05:02 | 0.00 | 0.00 | 0.00 | -26408.11 | 0.00 | 0.00 | 89.99 | 469.96 | 550.52 | 0.00 | 0.00 | 0.00 | 26772.33 | 0.00 | -542.34 | 0.00 | -932.35 | 0.00 |
ZONE2 FINE STORAGE | 13-AUG-16:13 | 0.00 | 0.00 | 0.00 | -53197.28 | 0.00 | 0.00 | 0.00 | 519.48 | 0.00 | 2214.03 | 0.00 | 824.10 | 49639.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 13-AUG-16:13 | 0.00 | 0.00 | 0.00 | -53197.28 | 0.00 | 0.00 | 0.00 | 1254.45 | 469.88 | 41280.85 | 0.00 | 824.10 | 33115.44 | 0.00 | 0.00 | 0.00 | -23747.43 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 06-FEB-06:11 | 0.00 | 0.00 | 29829.77 | 0.00 | 0.00 | 0.00 | 118.54 | 469.96 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1097.91 | 0.00 | -4171.28 | -25699.61 |
ZONE2 FINE STORAGE | 31-JAN-01:22 | 0.00 | 0.00 | 92309.78 | 0.00 | 0.00 | 0.00 | 0.00 | 623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1274.23 | 0.00 | -16810.47 | -74848.46 |
ZONE3 BULK STORAGE | 06-FEB-01:00 | 182628.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18368.15 | 0.00 | -124299.96 | -42886.10 |
Total Facility | 06-FEB-00:41 | 181352.81 | 0.00 | 117674.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1866.52 | 2519.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -33204.57 | 0.00 | -147979.82 | -122229.44 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0942 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0942 | 0.0935 | 1.0000 | Not calculated | 0.1023 | 0.0935 | ||
PSZ-FINE STORAGE | 2.5520 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.5520 | 0.1664 | 1.0000 | Not calculated | 0.4247 | 0.1664 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0942 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0942 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0935 | ||
PSZ-FINE STORAGE | 2.5520 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.5520 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1664 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0942 | 1.0942 | 1.0942 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5520 | 2.5520 | 2.5520 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0942 | 1.0942 | 1.0942 | 1.0942 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.5520 | 2.5520 | 2.5520 | 2.5520 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0942 | 1.0942 | 1.0942 | No | 0.1023 | 0.2676 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5520 | 2.5520 | 2.5520 | No | 0.4247 | 0.3781 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0942 | 1.0942 | 1.0942 | 1.0942 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.5520 | 2.5520 | 2.5520 | 2.5520 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 57.17 |
Number of hours cooling loads not met | 15.83 |
Number of hours not met | 73.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 615.44 | 302990.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 22.06 | 12637.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 147.85 | 14312.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.80 | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 2.59 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 27.07 | 3373.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.44 | 2475.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 454.30 |
Natural Gas | 0.00 | 615.44 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 1069.74 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 30.58 |
Space Heating | 0.00 |
Space Cooling | 4.56 |
Fans (All) | 6.13 |
Service Water Heating | 5.26 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 93.96 |
Subtotal | 93.96 |
Natural Gas [MJ/m2] | |
Space Heating | 127.28 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 127.28 |
Subtotal | 127.28 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.82 |
Space Heating | 57.53 |
Space Cooling | 2.06 |
Fans (All) | 2.77 |
Service Water Heating | 2.38 |
Receptacle Equipment | 12.76 |
Miscellaneous | 8.67 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 7746.00 | 1009.33 | 4.67 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7182.50 | 1577.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6642.00 | 1768.50 | 349.50 | 0.00 | 0.00 |
Min | 6642.00 | 1009.33 | 0.00 | 0.00 | 0.00 |
Max | 7746.00 | 1768.50 | 349.50 | 0.00 | 0.00 |
Average | 7190.17 | 1451.78 | 118.06 | 0.00 | 0.00 |
Sum | 21570.50 | 4355.33 | 354.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 63696.00 | 19023.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 138923.67 | 40283.17 | 11986.17 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 138923.67 | 40283.17 | 11986.17 | 0.00 | 0.00 |
Average | 78548.89 | 19768.72 | 3995.39 | 0.00 | 0.00 |
Sum | 235646.67 | 59306.17 | 11986.17 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7290.00 | 1470.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 6563.17 | 2196.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6410.67 | 2223.00 | 126.33 | 0.00 | 0.00 |
Min | 6410.67 | 1470.00 | 0.00 | 0.00 | 0.00 |
Max | 7290.00 | 2223.00 | 126.33 | 0.00 | 0.00 |
Average | 6754.61 | 1963.28 | 42.11 | 0.00 | 0.00 |
Sum | 20263.83 | 5889.83 | 126.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32060.33 | 966.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 59414.00 | 23305.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 134441.33 | 51668.33 | 5083.33 | 0.00 | 0.00 |
Min | 32060.33 | 966.67 | 0.00 | 0.00 | 0.00 |
Max | 134441.33 | 51668.33 | 5083.33 | 0.00 | 0.00 |
Average | 75305.22 | 25313.33 | 1694.44 | 0.00 | 0.00 |
Sum | 225915.67 | 75940.00 | 5083.33 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 | -11.5 | 0.497047E+09 | 603.25 | 18-JAN-08:09 | 9.08 | 8.76 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 | -4.2 | 0.457319E+09 | 603.25 | 24-FEB-08:09 | 5.00 | 4.19 |
March | 38896203.84 | 865.75 | 29-MAR-15:00 | 7.20 | 5.20 | 0.538493E+09 | 696.57 | 27-MAR-15:00 | 7.20 | 5.20 |
April | 0.238707E+09 | 2252.30 | 10-APR-15:00 | 20.00 | 11.58 | 0.527334E+09 | 768.99 | 08-APR-13:39 | 20.00 | 11.58 |
May | 0.135996E+10 | 14679.64 | 31-MAY-05:03 | 16.38 | 14.99 | 0.622736E+09 | 769.02 | 31-MAY-10:39 | 25.60 | 19.79 |
June | 0.509621E+10 | 20253.64 | 23-JUN-05:01 | 20.68 | 16.42 | 0.660177E+09 | 769.05 | 19-JUN-10:20 | 20.68 | 16.42 |
July | 0.673436E+10 | 21813.24 | 11-JUL-05:01 | 19.60 | 15.11 | 0.635101E+09 | 769.07 | 10-JUL-14:09 | 19.60 | 15.11 |
August | 0.751604E+10 | 23805.41 | 25-AUG-05:01 | 18.72 | 13.40 | 0.685782E+09 | 769.07 | 18-AUG-14:50 | 18.72 | 13.40 |
September | 0.461483E+10 | 26409.35 | 11-SEP-05:02 | 12.12 | 8.97 | 0.634156E+09 | 769.06 | 07-SEP-15:39 | 12.12 | 8.97 |
October | 0.166720E+10 | 9566.28 | 06-OCT-05:45 | 19.40 | 17.99 | 0.605206E+09 | 769.03 | 05-OCT-15:50 | 19.40 | 17.99 |
November | 0.119730E+09 | 869.38 | 04-NOV-07:20 | 10.33 | 8.63 | 0.489206E+09 | 768.96 | 04-NOV-14:20 | 16.87 | 12.94 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 | 2.86 | 0.497142E+09 | 603.25 | 04-DEC-08:09 | 6.28 | 6.01 |
Annual Sum or Average | 0.273859E+11 | 0.684970E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -9.6 | -11.5 | 0.457319E+09 | 603.25 | 5.00 | 4.19 | ||
Maximum of Months | 0.751604E+10 | 26409.35 | 20.68 | 17.99 | 0.685782E+09 | 769.07 | 25.60 | 19.79 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.672996E+09 | 4534.65 | 26-JAN-11:40 | 3.70 | 0.27 | 0.653631E+09 | 928.73 | 17-JAN-14:50 | 3.70 | 0.27 |
February | 0.740711E+09 | 4866.85 | 22-FEB-13:10 | 4.08 | -1.3 | 0.600367E+09 | 871.26 | 17-FEB-14:30 | 4.08 | -1.3 |
March | 0.173709E+10 | 6914.59 | 17-MAR-13:05 | -1.0 | -1.9 | 0.762846E+09 | 1287.19 | 27-MAR-15:00 | 22.20 | 16.34 |
April | 0.156750E+10 | 5128.99 | 12-APR-08:15 | 5.97 | 0.47 | 0.895537E+09 | 1757.65 | 08-APR-12:50 | 5.97 | 0.47 |
May | 0.154267E+10 | 8960.95 | 31-MAY-14:00 | 27.20 | 20.39 | 0.135344E+10 | 2246.87 | 30-MAY-15:30 | 27.20 | 20.39 |
June | 0.592356E+10 | 44376.20 | 19-JUN-17:43 | 32.38 | 23.44 | 0.187586E+10 | 2246.93 | 19-JUN-15:00 | 32.38 | 23.44 |
July | 0.125114E+11 | 51128.83 | 04-JUL-13:53 | 27.80 | 18.40 | 0.185366E+10 | 2246.94 | 21-JUL-13:09 | 28.98 | 25.17 |
August | 0.142412E+11 | 53196.88 | 13-AUG-16:13 | 29.80 | 20.56 | 0.199918E+10 | 2246.94 | 14-AUG-12:30 | 29.15 | 23.58 |
September | 0.489342E+10 | 43410.96 | 10-SEP-16:21 | 23.05 | 12.79 | 0.172922E+10 | 2246.90 | 01-SEP-12:09 | 23.05 | 12.79 |
October | 0.180392E+10 | 5196.15 | 28-OCT-07:10 | 4.27 | 1.31 | 0.130937E+10 | 2246.79 | 04-OCT-15:20 | 4.27 | 1.31 |
November | 0.137931E+10 | 4486.45 | 20-NOV-11:20 | 4.80 | 2.68 | 0.733586E+09 | 1429.11 | 04-NOV-13:09 | 4.80 | 2.68 |
December | 0.850049E+09 | 5113.43 | 21-DEC-14:00 | 3.30 | -1.6 | 0.654548E+09 | 883.55 | 16-DEC-14:50 | 3.30 | -1.6 |
Annual Sum or Average | 0.478638E+11 | 0.144213E+11 | ||||||||
Minimum of Months | 0.672996E+09 | 4486.45 | -1.0 | -1.9 | 0.600367E+09 | 871.26 | 3.30 | -1.6 | ||
Maximum of Months | 0.142412E+11 | 53196.88 | 32.38 | 23.44 | 0.199918E+10 | 2246.94 | 32.38 | 25.17 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 | -11.5 | 0.701385E+09 | 1203.06 | 17-JAN-14:50 | 10.68 | 5.08 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 | -4.2 | 0.633977E+09 | 1140.97 | 17-FEB-14:20 | 6.50 | 2.07 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 | 4.35 | 0.983784E+09 | 2024.72 | 27-MAR-15:00 | 22.20 | 16.34 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 | 0.154900E+10 | 3356.21 | 10-APR-14:39 | 20.20 | 11.22 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 | 0.286351E+10 | 5947.98 | 31-MAY-14:20 | 26.83 | 20.08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.59 | 0.472463E+10 | 8774.83 | 19-JUN-12:20 | 36.13 | 24.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.29 | 0.517881E+10 | 8025.47 | 07-JUL-12:20 | 33.53 | 23.31 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 | 0.562708E+10 | 8043.27 | 24-AUG-15:39 | 33.90 | 19.89 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 | 0.416366E+10 | 7056.46 | 01-SEP-14:20 | 30.93 | 17.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 | 0.257166E+10 | 4780.96 | 04-OCT-14:20 | 24.23 | 19.01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 | 0.110046E+10 | 2673.86 | 04-NOV-13:20 | 17.43 | 12.80 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 | 2.86 | 0.696627E+09 | 1198.25 | 20-DEC-11:00 | 8.90 | 5.16 |
Annual Sum or Average | 0.00 | 0.307946E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -9.6 | -11.5 | 0.633977E+09 | 1140.97 | 6.50 | 2.07 | ||
Maximum of Months | 0.00 | 0.00 | 23.90 | 21.46 | 0.562708E+10 | 8774.83 | 36.13 | 24.17 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.678140E+10 | 29715.32 | 02-JAN-06:12 | -11.7 |
February | 0.657839E+10 | 29829.71 | 06-FEB-06:11 | -13.0 |
March | 0.450240E+10 | 29636.17 | 13-MAR-05:12 | -0.6 |
April | 0.191864E+10 | 29353.41 | 04-APR-05:12 | 3.70 |
May | 0.311538E+09 | 29220.55 | 02-MAY-05:01 | 8.40 |
June | 9820058.27 | 680.54 | 02-JUN-06:20 | 14.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 529161.93 | 337.42 | 08-AUG-06:15 | 17.93 |
September | 17631632.45 | 719.11 | 11-SEP-06:10 | 12.07 |
October | 0.204760E+09 | 28861.19 | 31-OCT-05:01 | 4.60 |
November | 0.284440E+10 | 29468.55 | 22-NOV-06:12 | -2.2 |
December | 0.503252E+10 | 29572.41 | 31-DEC-23:22 | -8.1 |
Annual Sum or Average | 0.282020E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.0 | |
Maximum of Months | 0.678140E+10 | 29829.71 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.268046E+11 | 92308.86 | 31-JAN-01:22 | -5.5 |
February | 0.244523E+11 | 92192.78 | 05-FEB-08:42 | -5.6 |
March | 0.120443E+11 | 90753.88 | 22-MAR-05:42 | -2.7 |
April | 0.301159E+10 | 61477.40 | 02-APR-05:33 | 3.50 |
May | 0.110900E+09 | 1411.34 | 09-MAY-16:20 | 22.60 |
June | 64310284.48 | 1050.32 | 17-JUN-07:00 | 20.60 |
July | 9361867.52 | 1229.49 | 18-JUL-06:10 | 24.40 |
August | 37523803.06 | 1273.17 | 15-AUG-06:10 | 24.40 |
September | 65834087.85 | 1115.09 | 25-SEP-07:00 | 14.40 |
October | 90999398.94 | 1156.36 | 27-OCT-06:50 | 6.02 |
November | 0.858795E+10 | 90749.81 | 23-NOV-01:22 | -2.5 |
December | 0.194929E+11 | 92304.44 | 31-DEC-21:22 | -7.0 |
Annual Sum or Average | 0.947726E+11 | |||
Minimum of Months | 9361867.52 | 1050.32 | -7.0 | |
Maximum of Months | 0.268046E+11 | 92308.86 | 24.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109199E+12 | 156587.37 | 01-JAN-21:00 | -8.3 |
February | 0.103540E+12 | 182630.05 | 06-FEB-01:00 | -13.3 |
March | 0.266192E+11 | 95438.76 | 22-MAR-05:51 | -2.8 |
April | 0.121187E+10 | 27897.84 | 02-APR-06:00 | 3.30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.221047E+11 | 103808.20 | 23-NOV-01:53 | -2.8 |
December | 0.685266E+11 | 157759.80 | 31-DEC-21:53 | -7.2 |
Annual Sum or Average | 0.331202E+12 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.109199E+12 | 182630.05 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.191053E+10 | 1573.38 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.167091E+10 | 1573.38 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.181155E+10 | 1573.38 | 02-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.169060E+10 | 1573.38 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.167320E+10 | 1573.38 | 04-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.161952E+10 | 1573.38 | 29-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.161234E+10 | 1573.38 | 15-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.168090E+10 | 1573.38 | 16-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.169243E+10 | 1573.38 | 09-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.171252E+10 | 1573.38 | 06-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.179004E+10 | 1573.38 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.193034E+10 | 1573.38 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.207949E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.161234E+10 | 1573.38 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.193034E+10 | 1573.38 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.561792E+10 | 5298.77 | 02-JAN-14:30 | 0.00 | 0.00 |
February | 0.499291E+10 | 5298.77 | 01-FEB-15:00 | 0.00 | 0.00 |
March | 0.534016E+10 | 5298.77 | 04-MAR-09:09 | 0.00 | 0.00 |
April | 0.477064E+10 | 5298.77 | 03-APR-08:09 | 0.00 | 0.00 |
May | 0.458482E+10 | 4857.20 | 04-MAY-08:09 | 0.00 | 0.00 |
June | 0.441344E+10 | 4857.20 | 16-JUN-08:09 | 0.00 | 0.00 |
July | 0.428925E+10 | 4857.20 | 05-JUL-08:09 | 0.00 | 0.00 |
August | 0.478589E+10 | 5298.77 | 10-AUG-08:09 | 0.00 | 0.00 |
September | 0.484125E+10 | 5298.77 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.512615E+10 | 5298.77 | 05-OCT-08:09 | 0.00 | 0.00 |
November | 0.524721E+10 | 5298.77 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.570038E+10 | 5298.77 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.597100E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.428925E+10 | 4857.20 | 0.00 | 0.00 | |
Maximum of Months | 0.570038E+10 | 5298.77 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.663138E+10 | 7440.58 | 02-JAN-15:50 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.564967E+10 | 7440.58 | 02-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.584144E+10 | 6565.03 | 02-MAR-16:49 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.515446E+10 | 5470.86 | 01-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.503865E+10 | 5470.86 | 04-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.494219E+10 | 4923.77 | 16-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.488943E+10 | 5470.86 | 15-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.530288E+10 | 5470.86 | 16-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.530458E+10 | 6017.95 | 30-SEP-15:00 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.568313E+10 | 6565.03 | 06-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.596722E+10 | 7440.58 | 06-NOV-15:50 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.693592E+10 | 7440.58 | 01-DEC-15:39 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.673409E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.488943E+10 | 4923.77 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.693592E+10 | 7440.58 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.191053E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437189E+10 |
February | 0.127628E+10 | 0.167091E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408253E+10 |
March | 0.149825E+10 | 0.181155E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333596E+10 |
April | 0.138726E+10 | 0.169060E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9277975.14 | 0.193821E+10 |
May | 0.144276E+10 | 0.167320E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20147403.61 | 0.121093E+10 |
June | 0.144276E+10 | 0.161952E+10 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143514E+09 | 0.689346E+09 |
July | 0.138726E+10 | 0.161234E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295250E+09 | 0.253213E+09 |
August | 0.149825E+10 | 0.168090E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378053E+09 | 0.322801E+09 |
September | 0.138726E+10 | 0.169243E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60676065.18 | 0.775402E+09 |
October | 0.138726E+10 | 0.171252E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1058586.41 | 0.169709E+10 |
November | 0.133177E+10 | 0.179004E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283569E+10 |
December | 0.138726E+10 | 0.193034E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373320E+10 |
Annual Sum or Average | 0.168137E+11 | 0.207949E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907978E+09 | 0.252463E+11 |
Minimum of Months | 0.127628E+10 | 0.161234E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253213E+09 |
Maximum of Months | 0.149825E+10 | 0.193034E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378053E+09 | 0.437189E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.561792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155071E+11 |
February | 0.300332E+10 | 0.499291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141505E+11 |
March | 0.352563E+10 | 0.534016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10498316.85 | 0.102862E+11 |
April | 0.326447E+10 | 0.477064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64752151.72 | 0.568272E+10 |
May | 0.339505E+10 | 0.458482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21571905.54 | 0.380309E+10 |
June | 0.339505E+10 | 0.441344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166704E+09 | 0.350009E+10 |
July | 0.326447E+10 | 0.428925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313237E+09 | 0.141960E+10 |
August | 0.352563E+10 | 0.478589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512021E+09 | 0.169931E+10 |
September | 0.326447E+10 | 0.484125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37461321.24 | 0.336413E+10 |
October | 0.326447E+10 | 0.512615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594686E+10 |
November | 0.313390E+10 | 0.524721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.889801E+10 |
December | 0.326447E+10 | 0.570038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127050E+11 |
Annual Sum or Average | 0.395654E+11 | 0.597100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112625E+10 | 0.869627E+11 |
Minimum of Months | 0.300332E+10 | 0.428925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141960E+10 |
Maximum of Months | 0.352563E+10 | 0.570038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512021E+09 | 0.155071E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.663138E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50973420.49 | 0.537958E+11 |
February | 0.690763E+10 | 0.564967E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530006E+11 |
March | 0.810895E+10 | 0.584144E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526229E+09 | 0.320138E+11 |
April | 0.750829E+10 | 0.515446E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116056E+10 | 0.195609E+11 |
May | 0.780862E+10 | 0.503865E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180847E+09 | 0.169447E+11 |
June | 0.780862E+10 | 0.494219E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148594E+09 | 0.217810E+11 |
July | 0.750829E+10 | 0.488943E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7891051.57 | 0.133124E+11 |
August | 0.810895E+10 | 0.530288E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31915082.27 | 0.147850E+11 |
September | 0.750829E+10 | 0.530458E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1169156.35 | 0.194843E+11 |
October | 0.750829E+10 | 0.568313E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40191023.48 | 0.249760E+11 |
November | 0.720796E+10 | 0.596722E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81751636.67 | 0.282452E+11 |
December | 0.750829E+10 | 0.693592E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4129261.03 | 0.398660E+11 |
Annual Sum or Average | 0.910005E+11 | 0.673409E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223425E+10 | 0.337766E+12 |
Minimum of Months | 0.690763E+10 | 0.488943E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133124E+11 |
Maximum of Months | 0.810895E+10 | 0.693592E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116056E+10 | 0.537958E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1573.38 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 11166.42 | 31-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1573.38 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 12534.20 | 06-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1573.38 | 02-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 10513.15 | 22-MAR-07:00 |
April | 1680.92 | 01-APR-07:10 | 1573.38 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 670.75 | 07-APR-17:00 | 6016.85 | 12-APR-07:00 |
May | 1680.92 | 01-MAY-07:10 | 1573.38 | 04-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1263.46 | 30-MAY-12:00 | 3843.40 | 01-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1573.38 | 29-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2965.88 | 19-JUN-12:00 | 3016.08 | 02-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1573.38 | 15-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2252.02 | 07-JUL-12:00 | 818.85 | 11-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 1573.38 | 16-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3212.40 | 24-AUG-17:00 | 1705.04 | 08-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 1573.38 | 09-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.23 | 14-SEP-16:10 | 3324.08 | 11-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 1573.38 | 06-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.04 | 25-OCT-11:10 | 5144.04 | 27-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 1573.38 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 8712.40 | 22-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1573.38 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 8356.58 | 01-DEC-17:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1573.38 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 818.85 | |||||
Maximum of Months | 1680.92 | 1573.38 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 3212.40 | 12534.20 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 5298.77 | 02-JAN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 24188.90 | 14-JAN-17:00 |
February | 3955.50 | 01-FEB-08:09 | 5298.77 | 01-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 22388.33 | 06-FEB-01:00 |
March | 3955.50 | 01-MAR-08:09 | 5298.77 | 04-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1178.21 | 27-MAR-16:00 | 22828.64 | 22-MAR-07:00 |
April | 3955.50 | 01-APR-07:10 | 5298.77 | 03-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1810.83 | 07-APR-17:00 | 9731.01 | 21-APR-06:10 |
May | 3955.50 | 01-MAY-07:10 | 4857.20 | 04-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 950.95 | 29-MAY-12:00 | 5273.02 | 11-MAY-17:00 |
June | 3955.50 | 01-JUN-07:10 | 4857.20 | 16-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3739.13 | 19-JUN-17:00 | 5606.00 | 06-JUN-15:10 |
July | 3955.50 | 01-JUL-07:10 | 4857.20 | 05-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3310.79 | 10-JUL-15:10 | 2728.04 | 15-JUL-08:00 |
August | 3955.50 | 01-AUG-07:10 | 5298.77 | 10-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5441.84 | 24-AUG-17:00 | 3444.84 | 20-AUG-06:00 |
September | 3955.50 | 01-SEP-07:10 | 5298.77 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1694.29 | 01-SEP-15:10 | 4439.37 | 23-SEP-07:00 |
October | 3955.50 | 02-OCT-07:10 | 5298.77 | 05-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 9819.89 | 26-OCT-17:00 |
November | 3955.50 | 01-NOV-07:10 | 5298.77 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 15693.08 | 23-NOV-01:52 |
December | 3955.50 | 01-DEC-08:09 | 5298.77 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 21795.95 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 4857.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2728.04 | ||||
Maximum of Months | 3955.50 | 5298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5441.84 | 24188.90 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 7440.58 | 02-JAN-15:50 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3209.82 | 18-JAN-16:00 | 88856.68 | 14-JAN-17:00 |
February | 9097.65 | 01-FEB-08:09 | 7440.58 | 02-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 85409.83 | 06-FEB-01:00 |
March | 9097.65 | 01-MAR-08:09 | 6565.03 | 02-MAR-16:49 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16345.10 | 27-MAR-16:00 | 76414.28 | 22-MAR-07:10 |
April | 9097.65 | 01-APR-07:10 | 5470.86 | 01-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17028.97 | 07-APR-13:50 | 35059.52 | 12-APR-07:10 |
May | 9097.65 | 01-MAY-07:10 | 5470.86 | 04-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4498.85 | 29-MAY-12:00 | 21804.99 | 11-MAY-16:00 |
June | 9097.65 | 01-JUN-07:10 | 4923.77 | 16-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4644.61 | 07-JUN-14:00 | 26085.29 | 03-JUN-16:00 |
July | 9097.65 | 01-JUL-07:10 | 5470.86 | 15-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 637.33 | 07-JUL-11:00 | 18918.72 | 11-JUL-08:00 |
August | 9097.65 | 01-AUG-07:10 | 5470.86 | 16-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.80 | 04-AUG-18:53 | 22055.68 | 19-AUG-09:00 |
September | 9097.65 | 01-SEP-07:10 | 6017.95 | 30-SEP-15:00 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 834.35 | 14-SEP-14:00 | 21778.92 | 23-SEP-09:00 |
October | 9097.65 | 02-OCT-07:10 | 6565.03 | 06-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4364.13 | 25-OCT-14:00 | 40094.44 | 28-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 7440.58 | 06-NOV-15:50 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3877.22 | 26-NOV-15:13 | 52771.05 | 23-NOV-01:52 |
December | 9097.65 | 01-DEC-08:09 | 7440.58 | 01-DEC-15:39 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 716.96 | 25-DEC-08:55 | 79369.19 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 4923.77 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18918.72 | |||||
Maximum of Months | 9097.65 | 7440.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 17028.97 | 88856.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 2574.52 | 3289.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2848.34 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 1471.15 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 914.33 |
March | 865.75 | 29-MAR-15:00 | 1680.92 | 959.76 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 998.02 |
April | 2252.30 | 10-APR-15:00 | 1680.92 | 959.76 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.49 |
May | 14679.64 | 31-MAY-05:03 | 739.61 | 1698.14 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.88 |
June | 20253.64 | 23-JUN-05:01 | 1294.31 | 3289.75 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.09 |
July | 21813.24 | 11-JUL-05:01 | 1479.21 | 3759.72 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 565.16 |
August | 23805.41 | 25-AUG-05:01 | 1479.21 | 3759.72 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.81 |
September | 26409.35 | 11-SEP-05:02 | 924.51 | 2349.82 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 932.35 |
October | 9566.28 | 06-OCT-05:45 | 369.80 | 939.93 | 1101.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.46 |
November | 869.38 | 04-NOV-07:20 | 1680.92 | 1573.38 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.61 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1103.37 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1075.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 939.93 | 1101.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.88 | |
Maximum of Months | 26409.35 | 1680.92 | 3759.72 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2848.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4534.65 | 26-JAN-11:40 | 3955.50 | 4415.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1477.65 |
February | 4866.85 | 22-FEB-13:10 | 3955.50 | 4415.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2202.32 |
March | 6914.59 | 17-MAR-13:05 | 7911.00 | 6181.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2866.16 |
April | 5128.99 | 12-APR-08:15 | 7911.00 | 10597.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2956.68 |
May | 8960.95 | 31-MAY-14:00 | 3955.50 | 3090.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.52 | 0.00 |
June | 44376.20 | 19-JUN-17:43 | 0.00 | 1870.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2200.32 | 0.00 |
July | 51128.83 | 04-JUL-13:53 | 0.00 | 1090.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.01 | 0.00 |
August | 53196.88 | 13-AUG-16:13 | 0.00 | 1558.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 824.10 | 0.00 |
September | 43410.96 | 10-SEP-16:21 | 0.00 | 4987.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1535.98 |
October | 5196.15 | 28-OCT-07:10 | 3955.50 | 4675.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5169.33 |
November | 4486.45 | 20-NOV-11:20 | 3955.50 | 4415.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1866.58 |
December | 5113.43 | 21-DEC-14:00 | 3955.50 | 5298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2142.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4486.45 | 0.00 | 1090.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53196.88 | 7911.00 | 10597.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2200.32 | 5169.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 6127.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63246.21 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 3501.40 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17585.80 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 2626.05 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6526.09 |
April | 0.00 | 01-APR-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7492.58 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3621.74 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6294.68 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7227.79 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4661.87 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5703.74 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 875.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14988.76 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9205.62 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 2626.05 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12104.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 875.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3621.74 | |
Maximum of Months | 0.00 | 0.00 | 6127.46 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63246.21 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.412241E+11 | 34369.95 | 14-JAN-16:00 | 0.191137E+12 | 263176.62 | 01-JAN-20:49 |
February | 0.362930E+11 | 27467.37 | 04-FEB-15:00 | 0.180578E+12 | 302990.44 | 06-FEB-00:49 |
March | 0.381546E+11 | 27089.07 | 16-MAR-08:30 | 0.607546E+11 | 176559.00 | 22-MAR-06:10 |
April | 0.336007E+11 | 25316.84 | 21-APR-07:19 | 0.947961E+10 | 61852.93 | 02-APR-05:40 |
May | 0.333197E+11 | 26961.32 | 31-MAY-13:00 | 0.416219E+09 | 14245.04 | 01-MAY-05:10 |
June | 0.355765E+11 | 35838.78 | 19-JUN-12:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.405376E+11 | 35010.52 | 07-JUL-14:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.437341E+11 | 37971.60 | 02-AUG-14:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.365025E+11 | 33224.34 | 01-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.363625E+11 | 26966.53 | 06-OCT-08:09 | 0.278195E+09 | 9676.06 | 31-OCT-05:10 |
November | 0.374646E+11 | 34036.55 | 22-NOV-16:00 | 0.463804E+11 | 172097.02 | 23-NOV-02:09 |
December | 0.415341E+11 | 34035.44 | 30-DEC-16:40 | 0.126416E+12 | 259783.24 | 31-DEC-22:10 |
Annual Sum or Average | 0.454304E+12 | 0.615440E+12 | ||||
Minimum of Months | 0.333197E+11 | 25316.84 | 0.00 | 0.00 | ||
Maximum of Months | 0.437341E+11 | 37971.60 | 0.191137E+12 | 302990.44 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.141598E+11 | 0.988908E+10 | 0.112984E+11 | 0.00 | 0.362626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225059E+10 | 0.00 |
February | 0.123135E+11 | 0.819877E+10 | 0.103734E+11 | 0.00 | 0.335275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205459E+10 | 0.00 |
March | 0.129931E+11 | 0.806982E+10 | 0.121089E+11 | 0.00 | 0.268053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230214E+10 | 0.00 |
April | 0.116157E+11 | 0.680075E+10 | 0.112578E+11 | 0.00 | 0.176347E+10 | 0.00 | 0.00 | 18267440.45 | 0.00 | 0.00 | 0.00 | 0.214476E+10 | 0.00 |
May | 0.112967E+11 | 0.621836E+10 | 0.117000E+11 | 0.00 | 0.163287E+10 | 0.00 | 0.00 | 0.314141E+09 | 0.00 | 0.00 | 0.00 | 0.215770E+10 | 0.00 |
June | 0.109751E+11 | 0.560639E+10 | 0.116594E+11 | 0.00 | 0.190188E+10 | 0.00 | 0.00 | 0.338553E+10 | 0.00 | 0.00 | 0.00 | 0.204821E+10 | 0.00 |
July | 0.107910E+11 | 0.594694E+10 | 0.112984E+11 | 0.00 | 0.275105E+10 | 0.00 | 0.00 | 0.772203E+10 | 0.00 | 0.00 | 0.00 | 0.202822E+10 | 0.00 |
August | 0.117697E+11 | 0.662599E+10 | 0.121016E+11 | 0.00 | 0.311456E+10 | 0.00 | 0.00 | 0.805454E+10 | 0.00 | 0.00 | 0.00 | 0.206774E+10 | 0.00 |
September | 0.118383E+11 | 0.736665E+10 | 0.112504E+11 | 0.00 | 0.170099E+10 | 0.00 | 0.00 | 0.234944E+10 | 0.00 | 0.00 | 0.00 | 0.199674E+10 | 0.00 |
October | 0.125218E+11 | 0.866087E+10 | 0.113057E+11 | 0.00 | 0.156680E+10 | 0.00 | 0.00 | 0.214436E+09 | 0.00 | 0.00 | 0.00 | 0.209288E+10 | 0.00 |
November | 0.130045E+11 | 0.930329E+10 | 0.108562E+11 | 0.00 | 0.221898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208164E+10 | 0.00 |
December | 0.145666E+11 | 0.101113E+11 | 0.112984E+11 | 0.00 | 0.334472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221315E+10 | 0.00 |
Annual Sum or Average | 0.147846E+12 | 0.927982E+11 | 0.136508E+12 | 0.00 | 0.296549E+11 | 0.00 | 0.00 | 0.220584E+11 | 0.00 | 0.00 | 0.00 | 0.254384E+11 | 0.00 |
Minimum of Months | 0.107910E+11 | 0.560639E+10 | 0.103734E+11 | 0.00 | 0.156680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199674E+10 | 0.00 |
Maximum of Months | 0.145666E+11 | 0.101113E+11 | 0.121089E+11 | 0.00 | 0.362626E+10 | 0.00 | 0.00 | 0.805454E+10 | 0.00 | 0.00 | 0.00 | 0.230214E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.191137E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.180578E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.607546E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.947961E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.416219E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.278195E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.463804E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.126416E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.615440E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.191137E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 14312.73 | 03-JAN-15:50 | 6986.42 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 3132.96 | 31-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 13804.00 | 02-FEB-15:00 | 6986.42 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 3373.15 | 06-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 13072.63 | 04-MAR-09:09 | 6986.42 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2980.69 | 22-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 11719.49 | 01-APR-07:10 | 6986.42 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2491.45 | 03-APR-06:19 | 0.00 | 0.00 | 01-APR-00:10 |
May | 11719.49 | 04-MAY-07:10 | 6986.42 | 01-MAY-18:49 | 10035.17 | 01-MAY-07:10 | 0.00 | 1742.11 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 11172.40 | 29-JUN-07:10 | 6986.42 | 01-JUN-19:19 | 10035.17 | 01-JUN-07:10 | 0.00 | 4170.00 | 19-JUN-11:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 11719.49 | 15-JUL-07:10 | 6986.42 | 01-JUL-19:30 | 10035.17 | 01-JUL-07:10 | 0.00 | 4081.82 | 07-JUL-11:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 11719.49 | 16-AUG-07:10 | 6986.42 | 01-AUG-19:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4215.76 | 02-AUG-15:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 12452.59 | 27-SEP-08:09 | 6986.42 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 3896.67 | 14-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 13072.63 | 06-OCT-08:09 | 6986.42 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 1724.01 | 31-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 14312.73 | 09-NOV-15:00 | 6986.42 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2871.06 | 22-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 14312.73 | 04-DEC-15:50 | 6986.42 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2786.53 | 01-DEC-17:49 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 11172.40 | 6986.42 | 10035.17 | 0.00 | 1724.01 | 0.00 | 0.00 | |||||
Maximum of Months | 14312.73 | 6986.42 | 10035.17 | 0.00 | 4215.76 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2468.41 | 30-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2475.04 | 06-FEB-12:50 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2442.87 | 01-MAR-12:20 | 0.00 |
April | 817.39 | 07-APR-14:39 | 0.00 | 0.00 | 0.00 | 2275.19 | 01-APR-11:30 | 0.00 |
May | 5858.43 | 31-MAY-13:00 | 0.00 | 0.00 | 0.00 | 1968.85 | 03-MAY-11:50 | 0.00 |
June | 12378.67 | 19-JUN-11:00 | 0.00 | 0.00 | 0.00 | 1790.41 | 01-JUN-11:09 | 0.00 |
July | 11688.08 | 08-JUL-12:09 | 0.00 | 0.00 | 0.00 | 1769.94 | 01-JUL-11:50 | 0.00 |
August | 12637.98 | 02-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1761.65 | 31-AUG-11:09 | 0.00 |
September | 9319.09 | 07-SEP-13:00 | 0.00 | 0.00 | 0.00 | 1776.48 | 30-SEP-11:09 | 0.00 |
October | 2545.57 | 06-OCT-05:49 | 0.00 | 0.00 | 0.00 | 1801.17 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2091.76 | 29-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2347.47 | 30-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1761.65 | 0.00 | ||
Maximum of Months | 12637.98 | 0.00 | 0.00 | 0.00 | 2475.04 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 34369.95 | 14-JAN-16:00 | 12813.66 | 10035.17 | 6986.42 | 0.00 | 3027.01 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27467.37 | 04-FEB-15:00 | 13072.63 | 10035.17 | 0.00 | 0.00 | 2405.64 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27089.07 | 16-MAR-08:30 | 13072.63 | 10035.17 | 0.00 | 0.00 | 2294.80 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25316.84 | 21-APR-07:19 | 11719.49 | 10035.17 | 0.00 | 0.00 | 1921.12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26961.32 | 31-MAY-13:00 | 7771.00 | 10035.17 | 0.00 | 0.00 | 1576.86 | 0.00 | 0.00 | 5858.43 | 0.00 |
June | 35838.78 | 19-JUN-12:20 | 8317.46 | 10035.17 | 0.00 | 0.00 | 4001.08 | 0.00 | 0.00 | 11856.45 | 0.00 |
July | 35010.52 | 07-JUL-14:09 | 7771.00 | 10035.17 | 0.00 | 0.00 | 4009.32 | 0.00 | 0.00 | 11461.54 | 0.00 |
August | 37971.60 | 02-AUG-14:50 | 9715.74 | 10035.17 | 0.00 | 0.00 | 4146.03 | 0.00 | 0.00 | 12347.55 | 0.00 |
September | 33224.34 | 01-SEP-14:00 | 9715.74 | 10035.17 | 0.00 | 0.00 | 3882.15 | 0.00 | 0.00 | 7861.75 | 0.00 |
October | 26966.53 | 06-OCT-08:09 | 13072.63 | 10035.17 | 0.00 | 0.00 | 1576.86 | 0.00 | 0.00 | 628.58 | 0.00 |
November | 34036.55 | 22-NOV-16:00 | 12813.66 | 10035.17 | 6986.42 | 0.00 | 2593.91 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34035.44 | 30-DEC-16:40 | 12813.66 | 10035.17 | 6986.42 | 0.00 | 2585.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25316.84 | 7771.00 | 10035.17 | 0.00 | 0.00 | 1576.86 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37971.60 | 13072.63 | 10035.17 | 6986.42 | 0.00 | 4146.03 | 0.00 | 0.00 | 12347.55 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 263176.62 | 01-JAN-20:49 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 302990.44 | 06-FEB-00:49 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 176559.00 | 22-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 61852.93 | 02-APR-05:40 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 14245.04 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 9676.06 | 31-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 172097.02 | 23-NOV-02:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 259783.24 | 31-DEC-22:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 302990.44 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.17 | 16.80 | 9.33 | 17.58 | 0.00 | 17.58 | 0.00 | 17.58 |
February | 24.00 | 16.37 | 8.00 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
March | 11.33 | 18.87 | 9.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
April | 6.17 | 19.79 | 5.83 | 19.92 | 0.00 | 19.92 | 0.00 | 19.92 |
May | 0.83 | 20.36 | 0.83 | 20.36 | 0.17 | 20.74 | 0.17 | 21.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.55 | 1.50 | 24.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 24.68 | 7.17 | 24.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.80 | 4.83 | 24.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.60 | 2.17 | 24.60 |
October | 0.17 | 20.47 | 0.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
November | 7.50 | 19.32 | 6.67 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
December | 11.33 | 18.48 | 8.67 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
Annual Sum or Average | 83.50 | 17.68 | 48.67 | 18.40 | 15.83 | 19.08 | 15.83 | 19.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.11 | 0.00 | 17.11 |
Maximum of Months | 24.00 | 20.47 | 9.33 | 20.47 | 7.17 | 24.80 | 7.17 | 24.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 98.83 | 14.49 | 4.50 | 14.49 | 0.00 | 14.49 | 0.00 | 14.49 |
February | 93.67 | 14.48 | 4.17 | 14.48 | 0.00 | 14.48 | 0.00 | 14.48 |
March | 52.67 | 14.76 | 3.50 | 14.76 | 0.00 | 14.76 | 0.00 | 14.76 |
April | 11.83 | 14.91 | 1.67 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.31 | 0.00 | 27.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.35 | 0.00 | 27.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.35 | 0.00 | 27.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.29 | 0.00 | 27.29 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 34.17 | 14.71 | 2.00 | 14.71 | 0.00 | 14.71 | 0.00 | 14.71 |
December | 90.50 | 14.70 | 4.50 | 14.70 | 0.00 | 14.70 | 0.00 | 14.70 |
Annual Sum or Average | 381.67 | 14.61 | 20.33 | 14.61 | 27.67 | 15.43 | 0.00 | 15.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 98.83 | 14.91 | 4.50 | 14.91 | 12.83 | 27.35 | 0.00 | 27.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
February | 276.00 | 21.04 | 276.00 | 21.04 | 276.00 | 21.04 |
March | 324.00 | 21.09 | 319.33 | 21.08 | 319.33 | 21.08 |
April | 300.00 | 21.62 | 205.50 | 21.40 | 205.50 | 21.31 |
May | 289.17 | 22.90 | 63.33 | 22.84 | 48.33 | 22.76 |
June | 51.67 | 23.91 | 270.67 | 23.91 | 40.17 | 23.91 |
July | 39.83 | 24.05 | 300.00 | 23.94 | 39.83 | 23.95 |
August | 17.33 | 24.09 | 316.83 | 23.93 | 16.83 | 23.94 |
September | 63.67 | 23.75 | 185.83 | 23.87 | 12.17 | 23.88 |
October | 223.67 | 22.87 | 91.67 | 22.91 | 51.67 | 22.82 |
November | 288.00 | 21.29 | 230.33 | 21.19 | 230.33 | 21.15 |
December | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
Annual Sum or Average | 2473.33 | 21.73 | 2859.50 | 22.00 | 1840.17 | 21.82 |
Minimum of Months | 17.33 | 21.04 | 63.33 | 21.04 | 12.17 | 21.04 |
Maximum of Months | 324.00 | 24.09 | 319.33 | 23.94 | 319.33 | 23.95 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.59 | 300.00 | 15.59 | 300.00 | 15.59 |
February | 276.00 | 15.57 | 276.00 | 15.57 | 276.00 | 15.57 |
March | 324.00 | 16.12 | 324.00 | 16.12 | 324.00 | 16.12 |
April | 300.00 | 18.01 | 255.83 | 17.69 | 255.83 | 17.57 |
May | 272.33 | 21.38 | 137.50 | 21.23 | 116.83 | 20.97 |
June | 229.00 | 26.25 | 298.50 | 26.27 | 222.33 | 26.29 |
July | 296.67 | 26.68 | 300.00 | 26.68 | 296.67 | 26.68 |
August | 275.83 | 26.71 | 324.00 | 26.67 | 275.83 | 26.68 |
September | 172.50 | 25.49 | 232.00 | 25.93 | 123.17 | 26.06 |
October | 262.83 | 21.57 | 155.33 | 21.62 | 127.67 | 21.48 |
November | 288.00 | 16.71 | 284.33 | 16.68 | 284.33 | 16.67 |
December | 300.00 | 15.60 | 300.00 | 15.60 | 300.00 | 15.60 |
Annual Sum or Average | 3297.17 | 20.10 | 3187.50 | 20.22 | 2902.67 | 20.09 |
Minimum of Months | 172.50 | 15.57 | 137.50 | 15.57 | 116.83 | 15.57 |
Maximum of Months | 324.00 | 26.71 | 324.00 | 26.68 | 324.00 | 26.68 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.39 | 300.00 | 10.39 | 300.00 | 10.39 |
February | 276.00 | 10.30 | 276.00 | 10.30 | 276.00 | 10.30 |
March | 324.00 | 11.72 | 324.00 | 11.72 | 324.00 | 11.72 |
April | 300.00 | 15.36 | 290.00 | 15.27 | 290.00 | 15.23 |
May | 298.33 | 20.66 | 154.17 | 20.26 | 148.00 | 20.00 |
June | 257.00 | 27.62 | 296.67 | 27.53 | 248.50 | 27.60 |
July | 300.00 | 29.29 | 300.00 | 29.29 | 300.00 | 29.29 |
August | 313.83 | 29.44 | 324.00 | 29.39 | 313.83 | 29.40 |
September | 220.50 | 26.27 | 211.83 | 26.78 | 152.83 | 27.08 |
October | 283.83 | 19.92 | 189.50 | 19.65 | 175.50 | 19.42 |
November | 288.00 | 13.09 | 288.00 | 13.09 | 288.00 | 13.09 |
December | 300.00 | 10.34 | 300.00 | 10.34 | 300.00 | 10.34 |
Annual Sum or Average | 3461.50 | 18.48 | 3254.17 | 18.45 | 3116.67 | 18.33 |
Minimum of Months | 220.50 | 10.30 | 154.17 | 10.30 | 148.00 | 10.30 |
Maximum of Months | 324.00 | 29.44 | 324.00 | 29.39 | 324.00 | 29.40 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 71958689.29 | 18267440.45 | 15.50 | 65056619.83 | 6902069.46 | 0.00 | 0.34 | 07-APR-14:40 | 0.00 | 01-APR-00:10 | 3249.54 | 07-APR-14:40 | 3207.43 | 07-APR-14:40 | 330.65 | 08-APR-13:00 | 817.39 | 07-APR-14:40 | 0.00 | 01-APR-00:10 |
May | 0.746074E+09 | 0.181335E+09 | 68.96 | 0.655543E+09 | 90530693.77 | 0.00 | 1.00 | 31-MAY-05:03 | 0.00 | 01-MAY-00:10 | 15721.06 | 31-MAY-05:03 | 9964.94 | 31-MAY-05:03 | 5756.12 | 31-MAY-05:03 | 3425.19 | 31-MAY-05:03 | 0.00 | 01-MAY-00:10 |
June | 0.692930E+10 | 0.161388E+10 | 275.85 | 0.504477E+10 | 0.188454E+10 | 0.00 | 1.00 | 01-JUN-05:03 | 0.00 | 01-JUN-00:10 | 26743.86 | 19-JUN-05:01 | 18697.30 | 22-JUN-05:57 | 14957.64 | 27-JUN-05:04 | 5537.21 | 19-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.109233E+11 | 0.250992E+10 | 293.41 | 0.760253E+10 | 0.332081E+10 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 27866.50 | 20-JUL-05:01 | 17743.54 | 05-JUL-05:03 | 16830.34 | 22-JUL-05:03 | 5679.13 | 22-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.110652E+11 | 0.258081E+10 | 311.36 | 0.834419E+10 | 0.272100E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 27776.34 | 04-AUG-05:01 | 22522.45 | 31-AUG-05:01 | 16311.37 | 04-AUG-05:02 | 5671.77 | 17-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.515543E+10 | 0.118917E+10 | 227.36 | 0.390661E+10 | 0.124882E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 26597.92 | 14-SEP-05:01 | 18751.85 | 02-SEP-05:01 | 15546.48 | 14-SEP-05:04 | 5510.21 | 14-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.903539E+09 | 0.214436E+09 | 81.00 | 0.630004E+09 | 0.273535E+09 | 0.00 | 1.00 | 06-OCT-05:45 | 0.00 | 01-OCT-00:10 | 23707.72 | 06-OCT-05:45 | 11992.12 | 06-OCT-05:45 | 11715.60 | 06-OCT-05:45 | 5091.14 | 06-OCT-05:45 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.357948E+11 | 0.830781E+10 | 1273.44 | 0.262487E+11 | 0.954613E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.110652E+11 | 0.258081E+10 | 311.36 | 0.834419E+10 | 0.332081E+10 | 0.00 | 1.00 | 0.00 | 27866.50 | 22522.45 | 16830.34 | 5679.13 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.513494E+09 | 0.132805E+09 | 16.50 | 0.399203E+09 | 0.114292E+09 | 0.00 | 0.47 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 | 15087.83 | 31-MAY-14:00 | 12817.09 | 30-MAY-13:50 | 4798.21 | 31-MAY-13:50 | 3764.49 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 |
June | 0.715714E+10 | 0.177165E+10 | 147.48 | 0.486142E+10 | 0.229572E+10 | 0.00 | 1.00 | 01-JUN-17:35 | 0.00 | 01-JUN-00:10 | 80781.56 | 25-JUN-08:15 | 61316.57 | 01-JUN-17:35 | 47797.47 | 25-JUN-08:15 | 17026.13 | 19-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.215932E+11 | 0.521212E+10 | 330.04 | 0.135570E+11 | 0.803620E+10 | 0.00 | 1.00 | 02-JUL-10:45 | 0.00 | 01-JUL-00:10 | 80366.06 | 30-JUL-08:55 | 57069.30 | 11-JUL-18:25 | 45348.34 | 30-JUL-08:55 | 17021.95 | 30-JUL-08:55 | 0.00 | 01-JUL-00:10 |
August | 0.224278E+11 | 0.547373E+10 | 334.67 | 0.154525E+11 | 0.697532E+10 | 0.00 | 1.00 | 01-AUG-17:08 | 0.00 | 01-AUG-00:10 | 77121.54 | 27-AUG-09:15 | 61881.76 | 20-AUG-12:32 | 38864.27 | 27-AUG-09:15 | 16870.56 | 04-AUG-17:08 | 0.00 | 01-AUG-00:10 |
September | 0.477753E+10 | 0.116027E+10 | 100.98 | 0.337198E+10 | 0.140555E+10 | 0.00 | 1.00 | 01-SEP-17:10 | 0.00 | 01-SEP-00:10 | 70490.39 | 04-SEP-08:35 | 61245.44 | 10-SEP-14:45 | 27210.03 | 02-SEP-18:05 | 15631.20 | 14-SEP-18:05 | 0.00 | 01-SEP-00:10 |
October | 234.85 | 61.00 | 0.17 | 153.72 | 81.13 | 0.00 | 0.00 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 | 0.39 | 04-OCT-13:00 | 0.26 | 04-OCT-13:00 | 0.14 | 04-OCT-13:00 | 0.10 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.564692E+11 | 0.137506E+11 | 929.83 | 0.376421E+11 | 0.188271E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.224278E+11 | 0.547373E+10 | 334.67 | 0.154525E+11 | 0.803620E+10 | 0.00 | 1.00 | 0.00 | 80781.56 | 61881.76 | 47797.47 | 17026.13 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.98 | 27.52 | 39.46 | 45.44 | 135.72 | 0.00 | 0.00 | 0.00 |
February | 98.17 | 43.07 | 55.10 | 73.99 | 137.31 | 0.00 | 0.00 | 0.00 |
March | 146.07 | 67.72 | 78.35 | 143.97 | 81.63 | 0.00 | 0.00 | 0.00 |
April | 158.48 | 67.66 | 90.82 | 175.81 | 57.24 | 0.00 | 0.00 | 0.00 |
May | 185.23 | 70.38 | 114.85 | 223.30 | 40.50 | 0.00 | 0.00 | 0.00 |
June | 202.71 | 81.95 | 120.77 | 259.64 | 32.16 | 0.00 | 0.00 | 0.00 |
July | 189.61 | 71.40 | 118.21 | 257.75 | 21.74 | 0.00 | 0.00 | 0.00 |
August | 209.64 | 96.97 | 112.67 | 285.46 | 29.21 | 0.00 | 0.00 | 0.00 |
September | 149.14 | 65.16 | 83.98 | 181.71 | 48.44 | 0.00 | 0.00 | 0.00 |
October | 147.32 | 71.51 | 75.80 | 168.17 | 70.62 | 0.00 | 0.00 | 0.00 |
November | 69.48 | 20.16 | 49.32 | 54.97 | 90.94 | 0.00 | 0.00 | 0.00 |
December | 61.70 | 26.73 | 34.97 | 43.66 | 122.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.67 | 59.32 | 81.35 | 160.10 | 71.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 61.70 | 20.16 | 34.97 | 43.66 | 21.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.64 | 96.97 | 120.77 | 285.46 | 137.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.98 | 27.52 | 39.46 | 45.44 | 135.72 | 0.00 | 0.00 | 0.00 |
February | 98.17 | 43.07 | 55.10 | 73.99 | 137.31 | 0.00 | 0.00 | 0.00 |
March | 146.07 | 67.72 | 78.35 | 143.97 | 81.63 | 0.00 | 0.00 | 0.00 |
April | 158.48 | 67.66 | 90.82 | 175.81 | 57.24 | 0.00 | 0.00 | 0.00 |
May | 185.23 | 70.38 | 114.85 | 223.30 | 40.50 | 0.00 | 0.00 | 0.00 |
June | 202.71 | 81.95 | 120.77 | 259.64 | 32.16 | 0.00 | 0.00 | 0.00 |
July | 189.61 | 71.40 | 118.21 | 257.75 | 21.74 | 0.00 | 0.00 | 0.00 |
August | 209.64 | 96.97 | 112.67 | 285.46 | 29.21 | 0.00 | 0.00 | 0.00 |
September | 149.14 | 65.16 | 83.98 | 181.71 | 48.44 | 0.00 | 0.00 | 0.00 |
October | 147.32 | 71.51 | 75.80 | 168.17 | 70.62 | 0.00 | 0.00 | 0.00 |
November | 69.48 | 20.16 | 49.32 | 54.97 | 90.94 | 0.00 | 0.00 | 0.00 |
December | 61.70 | 26.73 | 34.97 | 43.66 | 122.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.67 | 59.32 | 81.35 | 160.10 | 71.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 61.70 | 20.16 | 34.97 | 43.66 | 21.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.64 | 96.97 | 120.77 | 285.46 | 137.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.87 | 0.00 | 18.87 | 2.28 | 84.06 | 0.00 | 0.00 | 0.00 |
February | 25.82 | 0.00 | 25.82 | 4.14 | 85.98 | 0.00 | 0.00 | 0.00 |
March | 35.82 | 0.00 | 35.82 | 18.04 | 50.56 | 0.00 | 0.00 | 0.00 |
April | 43.04 | 0.14 | 42.90 | 34.61 | 33.85 | 0.00 | 0.00 | 0.00 |
May | 57.29 | 2.07 | 55.22 | 59.41 | 22.89 | 0.00 | 0.00 | 0.00 |
June | 60.41 | 3.15 | 57.26 | 71.48 | 18.04 | 0.00 | 0.00 | 0.00 |
July | 58.62 | 2.22 | 56.39 | 78.13 | 12.42 | 0.00 | 0.00 | 0.00 |
August | 51.91 | 0.70 | 51.21 | 67.73 | 16.80 | 0.00 | 0.00 | 0.00 |
September | 39.08 | 0.02 | 39.06 | 39.01 | 28.77 | 0.00 | 0.00 | 0.00 |
October | 33.80 | 0.00 | 33.80 | 26.19 | 42.27 | 0.00 | 0.00 | 0.00 |
November | 23.71 | 0.00 | 23.71 | 10.01 | 54.97 | 0.00 | 0.00 | 0.00 |
December | 16.46 | 0.00 | 16.46 | 1.70 | 75.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.81 | 0.70 | 38.11 | 34.60 | 43.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.46 | 0.00 | 16.46 | 1.70 | 12.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.41 | 3.15 | 57.26 | 78.13 | 85.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.87 | 0.00 | 18.87 | 2.28 | 84.06 | 0.00 | 0.00 | 0.00 |
February | 25.82 | 0.00 | 25.82 | 4.14 | 85.98 | 0.00 | 0.00 | 0.00 |
March | 35.82 | 0.00 | 35.82 | 18.04 | 50.56 | 0.00 | 0.00 | 0.00 |
April | 43.04 | 0.14 | 42.89 | 34.61 | 33.85 | 0.00 | 0.00 | 0.00 |
May | 57.29 | 2.07 | 55.22 | 59.41 | 22.89 | 0.00 | 0.00 | 0.00 |
June | 60.41 | 3.15 | 57.26 | 71.48 | 18.04 | 0.00 | 0.00 | 0.00 |
July | 58.61 | 2.22 | 56.39 | 78.13 | 12.42 | 0.00 | 0.00 | 0.00 |
August | 51.91 | 0.70 | 51.20 | 67.73 | 16.80 | 0.00 | 0.00 | 0.00 |
September | 39.08 | 0.02 | 39.06 | 39.01 | 28.77 | 0.00 | 0.00 | 0.00 |
October | 33.80 | 0.00 | 33.80 | 26.19 | 42.27 | 0.00 | 0.00 | 0.00 |
November | 23.71 | 0.00 | 23.71 | 10.01 | 54.97 | 0.00 | 0.00 | 0.00 |
December | 16.46 | 0.00 | 16.46 | 1.70 | 75.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.81 | 0.70 | 38.11 | 34.60 | 43.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.46 | 0.00 | 16.46 | 1.70 | 12.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.41 | 3.15 | 57.26 | 78.13 | 85.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.08 | 8.94 | 14.14 | 17.10 | 45.18 | 0.00 | 0.00 | 0.00 |
February | 38.22 | 20.23 | 18.00 | 32.83 | 45.90 | 0.00 | 0.00 | 0.00 |
March | 58.58 | 32.43 | 26.14 | 62.89 | 28.10 | 0.00 | 0.00 | 0.00 |
April | 73.06 | 41.40 | 31.66 | 84.43 | 21.17 | 0.00 | 0.00 | 0.00 |
May | 92.63 | 50.76 | 41.87 | 112.42 | 16.42 | 0.17 | 0.00 | 0.00 |
June | 101.53 | 58.48 | 43.05 | 124.30 | 14.81 | 0.00 | 0.00 | 0.00 |
July | 97.83 | 53.99 | 43.85 | 124.11 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 100.19 | 63.58 | 36.61 | 126.56 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 68.18 | 39.96 | 28.21 | 80.58 | 20.86 | 0.00 | 0.00 | 0.00 |
October | 55.79 | 32.29 | 23.49 | 64.06 | 27.83 | 0.00 | 0.00 | 0.00 |
November | 29.77 | 11.29 | 18.48 | 28.60 | 32.03 | 0.00 | 0.00 | 0.00 |
December | 20.17 | 8.59 | 11.58 | 14.96 | 41.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.40 | 35.26 | 28.15 | 72.99 | 26.62 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 20.17 | 8.59 | 11.58 | 14.96 | 11.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.53 | 63.58 | 43.85 | 126.56 | 45.90 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.08 | 8.94 | 14.14 | 17.10 | 45.18 | 0.00 | 0.00 | 0.00 |
February | 38.22 | 20.23 | 18.00 | 32.83 | 45.90 | 0.00 | 0.00 | 0.00 |
March | 58.58 | 32.43 | 26.14 | 62.89 | 28.10 | 0.00 | 0.00 | 0.00 |
April | 73.06 | 41.40 | 31.66 | 84.43 | 21.17 | 0.00 | 0.00 | 0.00 |
May | 92.63 | 50.76 | 41.87 | 112.42 | 16.42 | 0.17 | 0.00 | 0.00 |
June | 101.53 | 58.48 | 43.05 | 124.30 | 14.81 | 0.00 | 0.00 | 0.00 |
July | 97.83 | 53.99 | 43.85 | 124.11 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 100.19 | 63.58 | 36.61 | 126.56 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 68.18 | 39.96 | 28.21 | 80.58 | 20.86 | 0.00 | 0.00 | 0.00 |
October | 55.79 | 32.29 | 23.49 | 64.06 | 27.83 | 0.00 | 0.00 | 0.00 |
November | 29.77 | 11.29 | 18.48 | 28.60 | 32.03 | 0.00 | 0.00 | 0.00 |
December | 20.17 | 8.59 | 11.58 | 14.96 | 41.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.40 | 35.26 | 28.15 | 72.99 | 26.62 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 20.17 | 8.59 | 11.58 | 14.96 | 11.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.53 | 63.58 | 43.85 | 126.56 | 45.90 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.08 | 8.94 | 14.14 | 17.10 | 45.18 | 0.00 | 0.00 | 0.00 |
February | 38.22 | 20.23 | 18.00 | 32.83 | 45.90 | 0.00 | 0.00 | 0.00 |
March | 58.58 | 32.43 | 26.14 | 62.89 | 28.10 | 0.00 | 0.00 | 0.00 |
April | 73.06 | 41.40 | 31.66 | 84.43 | 21.17 | 0.00 | 0.00 | 0.00 |
May | 92.63 | 50.76 | 41.87 | 112.42 | 16.42 | 0.17 | 0.00 | 0.00 |
June | 101.53 | 58.48 | 43.05 | 124.30 | 14.81 | 0.00 | 0.00 | 0.00 |
July | 97.83 | 53.99 | 43.85 | 124.11 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 100.19 | 63.58 | 36.61 | 126.56 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 68.18 | 39.96 | 28.21 | 80.58 | 20.86 | 0.00 | 0.00 | 0.00 |
October | 55.79 | 32.29 | 23.49 | 64.06 | 27.83 | 0.00 | 0.00 | 0.00 |
November | 29.77 | 11.29 | 18.48 | 28.60 | 32.03 | 0.00 | 0.00 | 0.00 |
December | 20.17 | 8.59 | 11.58 | 14.96 | 41.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.40 | 35.26 | 28.15 | 72.99 | 26.62 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 20.17 | 8.59 | 11.58 | 14.96 | 11.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.53 | 63.58 | 43.85 | 126.56 | 45.90 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.08 | 8.94 | 14.14 | 17.10 | 45.18 | 0.00 | 0.00 | 0.00 |
February | 38.22 | 20.23 | 18.00 | 32.83 | 45.90 | 0.00 | 0.00 | 0.00 |
March | 58.58 | 32.43 | 26.14 | 62.89 | 28.10 | 0.00 | 0.00 | 0.00 |
April | 73.06 | 41.40 | 31.66 | 84.43 | 21.17 | 0.00 | 0.00 | 0.00 |
May | 92.63 | 50.76 | 41.87 | 112.42 | 16.42 | 0.17 | 0.00 | 0.00 |
June | 101.53 | 58.48 | 43.05 | 124.30 | 14.81 | 0.00 | 0.00 | 0.00 |
July | 97.83 | 53.99 | 43.85 | 124.11 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 100.19 | 63.58 | 36.61 | 126.56 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 68.18 | 39.96 | 28.21 | 80.58 | 20.86 | 0.00 | 0.00 | 0.00 |
October | 55.79 | 32.29 | 23.49 | 64.06 | 27.83 | 0.00 | 0.00 | 0.00 |
November | 29.77 | 11.29 | 18.48 | 28.60 | 32.03 | 0.00 | 0.00 | 0.00 |
December | 20.17 | 8.59 | 11.58 | 14.96 | 41.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.40 | 35.26 | 28.15 | 72.99 | 26.62 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 20.17 | 8.59 | 11.58 | 14.96 | 11.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.53 | 63.58 | 43.85 | 126.56 | 45.90 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.08 | 8.94 | 14.14 | 17.10 | 45.18 | 0.00 | 0.00 | 0.00 |
February | 38.22 | 20.23 | 18.00 | 32.83 | 45.90 | 0.00 | 0.00 | 0.00 |
March | 58.58 | 32.43 | 26.14 | 62.89 | 28.10 | 0.00 | 0.00 | 0.00 |
April | 73.06 | 41.40 | 31.66 | 84.43 | 21.17 | 0.00 | 0.00 | 0.00 |
May | 92.63 | 50.76 | 41.87 | 112.42 | 16.42 | 0.17 | 0.00 | 0.00 |
June | 101.53 | 58.48 | 43.05 | 124.30 | 14.81 | 0.00 | 0.00 | 0.00 |
July | 97.83 | 53.99 | 43.85 | 124.11 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 100.19 | 63.58 | 36.61 | 126.56 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 68.18 | 39.96 | 28.21 | 80.58 | 20.86 | 0.00 | 0.00 | 0.00 |
October | 55.79 | 32.29 | 23.49 | 64.06 | 27.83 | 0.00 | 0.00 | 0.00 |
November | 29.77 | 11.29 | 18.48 | 28.60 | 32.03 | 0.00 | 0.00 | 0.00 |
December | 20.17 | 8.59 | 11.58 | 14.96 | 41.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.40 | 35.26 | 28.15 | 72.99 | 26.62 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 20.17 | 8.59 | 11.58 | 14.96 | 11.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.53 | 63.58 | 43.85 | 126.56 | 45.90 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.08 | 8.94 | 14.14 | 17.10 | 45.18 | 0.00 | 0.00 | 0.00 |
February | 38.22 | 20.23 | 18.00 | 32.83 | 45.90 | 0.00 | 0.00 | 0.00 |
March | 58.58 | 32.43 | 26.14 | 62.89 | 28.10 | 0.00 | 0.00 | 0.00 |
April | 73.06 | 41.40 | 31.66 | 84.43 | 21.17 | 0.00 | 0.00 | 0.00 |
May | 92.63 | 50.76 | 41.87 | 112.42 | 16.42 | 0.17 | 0.00 | 0.00 |
June | 101.53 | 58.48 | 43.05 | 124.30 | 14.81 | 0.00 | 0.00 | 0.00 |
July | 97.83 | 53.99 | 43.85 | 124.11 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 100.19 | 63.58 | 36.61 | 126.56 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 68.18 | 39.96 | 28.21 | 80.58 | 20.86 | 0.00 | 0.00 | 0.00 |
October | 55.79 | 32.29 | 23.49 | 64.06 | 27.83 | 0.00 | 0.00 | 0.00 |
November | 29.77 | 11.29 | 18.48 | 28.60 | 32.03 | 0.00 | 0.00 | 0.00 |
December | 20.17 | 8.59 | 11.58 | 14.96 | 41.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.40 | 35.26 | 28.15 | 72.99 | 26.62 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 20.17 | 8.59 | 11.58 | 14.96 | 11.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.53 | 63.58 | 43.85 | 126.56 | 45.90 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.08 | 8.94 | 14.14 | 17.10 | 45.18 | 0.00 | 0.00 | 0.00 |
February | 38.22 | 20.23 | 18.00 | 32.83 | 45.90 | 0.00 | 0.00 | 0.00 |
March | 58.58 | 32.43 | 26.14 | 62.89 | 28.10 | 0.00 | 0.00 | 0.00 |
April | 73.06 | 41.40 | 31.66 | 84.43 | 21.17 | 0.00 | 0.00 | 0.00 |
May | 92.63 | 50.76 | 41.87 | 112.42 | 16.42 | 0.17 | 0.00 | 0.00 |
June | 101.53 | 58.48 | 43.05 | 124.30 | 14.81 | 0.00 | 0.00 | 0.00 |
July | 97.83 | 53.99 | 43.85 | 124.11 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 100.19 | 63.58 | 36.61 | 126.56 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 68.18 | 39.96 | 28.21 | 80.58 | 20.86 | 0.00 | 0.00 | 0.00 |
October | 55.79 | 32.29 | 23.49 | 64.06 | 27.83 | 0.00 | 0.00 | 0.00 |
November | 29.77 | 11.29 | 18.48 | 28.60 | 32.03 | 0.00 | 0.00 | 0.00 |
December | 20.17 | 8.59 | 11.58 | 14.96 | 41.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.40 | 35.26 | 28.15 | 72.99 | 26.62 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 20.17 | 8.59 | 11.58 | 14.96 | 11.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.53 | 63.58 | 43.85 | 126.56 | 45.90 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.08 | 8.94 | 14.14 | 17.10 | 45.18 | 0.00 | 0.00 | 0.00 |
February | 38.22 | 20.23 | 18.00 | 32.83 | 45.90 | 0.00 | 0.00 | 0.00 |
March | 58.58 | 32.43 | 26.14 | 62.89 | 28.10 | 0.00 | 0.00 | 0.00 |
April | 73.06 | 41.40 | 31.66 | 84.43 | 21.17 | 0.00 | 0.00 | 0.00 |
May | 92.63 | 50.76 | 41.87 | 112.42 | 16.42 | 0.17 | 0.00 | 0.00 |
June | 101.53 | 58.48 | 43.05 | 124.30 | 14.81 | 0.00 | 0.00 | 0.00 |
July | 97.83 | 53.99 | 43.85 | 124.11 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 100.19 | 63.58 | 36.61 | 126.56 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 68.18 | 39.96 | 28.21 | 80.58 | 20.86 | 0.00 | 0.00 | 0.00 |
October | 55.79 | 32.29 | 23.49 | 64.06 | 27.83 | 0.00 | 0.00 | 0.00 |
November | 29.77 | 11.29 | 18.48 | 28.60 | 32.03 | 0.00 | 0.00 | 0.00 |
December | 20.17 | 8.59 | 11.58 | 14.96 | 41.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.40 | 35.26 | 28.15 | 72.99 | 26.62 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 20.17 | 8.59 | 11.58 | 14.96 | 11.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.53 | 63.58 | 43.85 | 126.56 | 45.90 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.08 | 8.94 | 14.14 | 17.10 | 45.18 | 0.00 | 0.00 | 0.00 |
February | 38.22 | 20.23 | 18.00 | 32.83 | 45.90 | 0.00 | 0.00 | 0.00 |
March | 58.58 | 32.43 | 26.14 | 62.89 | 28.10 | 0.00 | 0.00 | 0.00 |
April | 73.06 | 41.40 | 31.66 | 84.43 | 21.17 | 0.00 | 0.00 | 0.00 |
May | 92.63 | 50.76 | 41.87 | 112.42 | 16.42 | 0.17 | 0.00 | 0.00 |
June | 101.53 | 58.48 | 43.05 | 124.30 | 14.81 | 0.00 | 0.00 | 0.00 |
July | 97.83 | 53.99 | 43.85 | 124.11 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 100.19 | 63.58 | 36.61 | 126.56 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 68.18 | 39.96 | 28.21 | 80.58 | 20.86 | 0.00 | 0.00 | 0.00 |
October | 55.79 | 32.29 | 23.49 | 64.06 | 27.83 | 0.00 | 0.00 | 0.00 |
November | 29.77 | 11.29 | 18.48 | 28.60 | 32.03 | 0.00 | 0.00 | 0.00 |
December | 20.17 | 8.59 | 11.58 | 14.96 | 41.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.40 | 35.26 | 28.15 | 72.99 | 26.62 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 20.17 | 8.59 | 11.58 | 14.96 | 11.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.53 | 63.58 | 43.85 | 126.56 | 45.90 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.08 | 8.94 | 14.14 | 17.10 | 45.18 | 0.00 | 0.00 | 0.00 |
February | 38.22 | 20.23 | 18.00 | 32.83 | 45.90 | 0.00 | 0.00 | 0.00 |
March | 58.58 | 32.43 | 26.14 | 62.89 | 28.10 | 0.00 | 0.00 | 0.00 |
April | 73.06 | 41.40 | 31.66 | 84.43 | 21.17 | 0.00 | 0.00 | 0.00 |
May | 92.63 | 50.76 | 41.87 | 112.42 | 16.42 | 0.17 | 0.00 | 0.00 |
June | 101.53 | 58.48 | 43.05 | 124.30 | 14.81 | 0.00 | 0.00 | 0.00 |
July | 97.83 | 53.99 | 43.85 | 124.11 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 100.19 | 63.58 | 36.61 | 126.56 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 68.18 | 39.96 | 28.21 | 80.58 | 20.86 | 0.00 | 0.00 | 0.00 |
October | 55.79 | 32.29 | 23.49 | 64.06 | 27.83 | 0.00 | 0.00 | 0.00 |
November | 29.77 | 11.29 | 18.48 | 28.60 | 32.03 | 0.00 | 0.00 | 0.00 |
December | 20.17 | 8.59 | 11.58 | 14.96 | 41.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.40 | 35.26 | 28.15 | 72.99 | 26.62 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 20.17 | 8.59 | 11.58 | 14.96 | 11.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.53 | 63.58 | 43.85 | 126.56 | 45.90 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.08 | 8.94 | 14.14 | 17.10 | 45.18 | 0.00 | 0.00 | 0.00 |
February | 38.22 | 20.23 | 18.00 | 32.83 | 45.90 | 0.00 | 0.00 | 0.00 |
March | 58.58 | 32.43 | 26.14 | 62.89 | 28.10 | 0.00 | 0.00 | 0.00 |
April | 73.06 | 41.40 | 31.66 | 84.43 | 21.17 | 0.00 | 0.00 | 0.00 |
May | 92.63 | 50.76 | 41.87 | 112.42 | 16.42 | 0.17 | 0.00 | 0.00 |
June | 101.53 | 58.48 | 43.05 | 124.30 | 14.81 | 0.00 | 0.00 | 0.00 |
July | 97.83 | 53.99 | 43.85 | 124.11 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 100.19 | 63.58 | 36.61 | 126.56 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 68.18 | 39.96 | 28.21 | 80.58 | 20.86 | 0.00 | 0.00 | 0.00 |
October | 55.79 | 32.29 | 23.49 | 64.06 | 27.83 | 0.00 | 0.00 | 0.00 |
November | 29.77 | 11.29 | 18.48 | 28.60 | 32.03 | 0.00 | 0.00 | 0.00 |
December | 20.17 | 8.59 | 11.58 | 14.96 | 41.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.40 | 35.26 | 28.15 | 72.99 | 26.62 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 20.17 | 8.59 | 11.58 | 14.96 | 11.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.53 | 63.58 | 43.85 | 126.56 | 45.90 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.08 | 8.94 | 14.14 | 17.10 | 45.18 | 0.00 | 0.00 | 0.00 |
February | 38.22 | 20.23 | 18.00 | 32.83 | 45.90 | 0.00 | 0.00 | 0.00 |
March | 58.58 | 32.43 | 26.14 | 62.89 | 28.10 | 0.00 | 0.00 | 0.00 |
April | 73.06 | 41.40 | 31.66 | 84.43 | 21.17 | 0.00 | 0.00 | 0.00 |
May | 92.63 | 50.76 | 41.87 | 112.42 | 16.42 | 0.17 | 0.00 | 0.00 |
June | 101.53 | 58.48 | 43.05 | 124.30 | 14.81 | 0.00 | 0.00 | 0.00 |
July | 97.83 | 53.99 | 43.85 | 124.11 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 100.19 | 63.58 | 36.61 | 126.56 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 68.18 | 39.96 | 28.21 | 80.58 | 20.86 | 0.00 | 0.00 | 0.00 |
October | 55.79 | 32.29 | 23.49 | 64.06 | 27.83 | 0.00 | 0.00 | 0.00 |
November | 29.77 | 11.29 | 18.48 | 28.60 | 32.03 | 0.00 | 0.00 | 0.00 |
December | 20.17 | 8.59 | 11.58 | 14.96 | 41.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.40 | 35.26 | 28.15 | 72.99 | 26.62 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 20.17 | 8.59 | 11.58 | 14.96 | 11.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.53 | 63.58 | 43.85 | 126.56 | 45.90 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.08 | 8.94 | 14.14 | 17.10 | 45.18 | 0.00 | 0.00 | 0.00 |
February | 38.22 | 20.23 | 18.00 | 32.83 | 45.90 | 0.00 | 0.00 | 0.00 |
March | 58.58 | 32.43 | 26.14 | 62.89 | 28.10 | 0.00 | 0.00 | 0.00 |
April | 73.06 | 41.40 | 31.66 | 84.43 | 21.17 | 0.00 | 0.00 | 0.00 |
May | 92.63 | 50.76 | 41.87 | 112.42 | 16.42 | 0.17 | 0.00 | 0.00 |
June | 101.53 | 58.48 | 43.05 | 124.30 | 14.81 | 0.00 | 0.00 | 0.00 |
July | 97.83 | 53.99 | 43.85 | 124.11 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 100.19 | 63.58 | 36.61 | 126.56 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 68.18 | 39.96 | 28.21 | 80.58 | 20.86 | 0.00 | 0.00 | 0.00 |
October | 55.79 | 32.29 | 23.49 | 64.06 | 27.83 | 0.00 | 0.00 | 0.00 |
November | 29.77 | 11.29 | 18.48 | 28.60 | 32.03 | 0.00 | 0.00 | 0.00 |
December | 20.17 | 8.59 | 11.58 | 14.96 | 41.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.40 | 35.26 | 28.15 | 72.99 | 26.62 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 20.17 | 8.59 | 11.58 | 14.96 | 11.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.53 | 63.58 | 43.85 | 126.56 | 45.90 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.08 | 8.94 | 14.14 | 17.10 | 45.18 | 0.00 | 0.00 | 0.00 |
February | 38.22 | 20.23 | 18.00 | 32.83 | 45.90 | 0.00 | 0.00 | 0.00 |
March | 58.58 | 32.43 | 26.14 | 62.89 | 28.10 | 0.00 | 0.00 | 0.00 |
April | 73.06 | 41.40 | 31.66 | 84.43 | 21.17 | 0.00 | 0.00 | 0.00 |
May | 92.63 | 50.76 | 41.87 | 112.42 | 16.42 | 0.17 | 0.00 | 0.00 |
June | 101.53 | 58.48 | 43.05 | 124.30 | 14.81 | 0.00 | 0.00 | 0.00 |
July | 97.83 | 53.99 | 43.85 | 124.11 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 100.19 | 63.58 | 36.61 | 126.56 | 15.72 | 0.00 | 0.00 | 0.00 |
September | 68.18 | 39.96 | 28.21 | 80.58 | 20.86 | 0.00 | 0.00 | 0.00 |
October | 55.79 | 32.29 | 23.49 | 64.06 | 27.83 | 0.00 | 0.00 | 0.00 |
November | 29.77 | 11.29 | 18.48 | 28.60 | 32.03 | 0.00 | 0.00 | 0.00 |
December | 20.17 | 8.59 | 11.58 | 14.96 | 41.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.40 | 35.26 | 28.15 | 72.99 | 26.62 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 20.17 | 8.59 | 11.58 | 14.96 | 11.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.53 | 63.58 | 43.85 | 126.56 | 45.90 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 13.33 | 18.87 | 31.04 | 59.51 | 44.17 | 0.00 | 0.00 |
February | 52.40 | 28.39 | 24.01 | 54.28 | 62.54 | 0.00 | 0.00 | 0.00 |
March | 78.25 | 43.36 | 34.89 | 99.11 | 34.44 | 12.50 | 0.00 | 0.00 |
April | 96.63 | 54.38 | 42.24 | 127.21 | 29.41 | 53.83 | 0.00 | 0.00 |
May | 121.89 | 66.02 | 55.87 | 165.14 | 26.05 | 31.17 | 0.00 | 0.00 |
June | 133.15 | 75.70 | 57.44 | 177.52 | 27.92 | 4.67 | 0.00 | 0.00 |
July | 128.43 | 69.92 | 58.51 | 174.69 | 25.23 | 14.00 | 0.00 | 0.00 |
August | 131.80 | 82.95 | 48.85 | 179.00 | 33.47 | 5.17 | 0.00 | 0.00 |
September | 90.40 | 52.75 | 37.65 | 115.67 | 37.96 | 6.33 | 0.00 | 0.00 |
October | 75.47 | 44.12 | 31.35 | 97.06 | 42.63 | 99.67 | 0.00 | 0.00 |
November | 41.00 | 16.35 | 24.66 | 47.19 | 42.05 | 29.67 | 0.00 | 0.00 |
December | 28.62 | 13.16 | 15.45 | 28.28 | 50.88 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.38 | 46.82 | 37.56 | 108.36 | 39.21 | 310.50 | 0.00 | 0.00 |
Minimum of Months | 28.62 | 13.16 | 15.45 | 28.28 | 25.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.15 | 82.95 | 58.51 | 179.00 | 62.54 | 99.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179394E+09 | 73698419.61 | 0.105696E+09 | 0.121714E+09 | 0.363512E+09 |
February | 0.237492E+09 | 0.104189E+09 | 0.133303E+09 | 0.178991E+09 | 0.332180E+09 |
March | 0.391244E+09 | 0.181380E+09 | 0.209864E+09 | 0.385622E+09 | 0.218641E+09 |
April | 0.410778E+09 | 0.175368E+09 | 0.235410E+09 | 0.455687E+09 | 0.148368E+09 |
May | 0.496111E+09 | 0.188501E+09 | 0.307610E+09 | 0.598096E+09 | 0.108464E+09 |
June | 0.525437E+09 | 0.212403E+09 | 0.313034E+09 | 0.672979E+09 | 83349416.01 |
July | 0.507864E+09 | 0.191251E+09 | 0.316613E+09 | 0.690351E+09 | 58235963.20 |
August | 0.561496E+09 | 0.259726E+09 | 0.301770E+09 | 0.764563E+09 | 78242531.06 |
September | 0.386558E+09 | 0.168883E+09 | 0.217675E+09 | 0.470989E+09 | 0.125548E+09 |
October | 0.394574E+09 | 0.191543E+09 | 0.203031E+09 | 0.450414E+09 | 0.189157E+09 |
November | 0.180104E+09 | 52254950.93 | 0.127849E+09 | 0.142489E+09 | 0.235704E+09 |
December | 0.165270E+09 | 71598160.95 | 93671926.80 | 0.116930E+09 | 0.327165E+09 |
Annual Sum or Average | 0.443632E+10 | 0.187079E+10 | 0.256553E+10 | 0.504883E+10 | 0.226857E+10 |
Minimum of Months | 0.165270E+09 | 52254950.93 | 93671926.80 | 0.116930E+09 | 58235963.20 |
Maximum of Months | 0.561496E+09 | 0.259726E+09 | 0.316613E+09 | 0.764563E+09 | 0.363512E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179394E+09 | 73698419.61 | 0.105696E+09 | 0.121714E+09 | 0.363512E+09 |
February | 0.237492E+09 | 0.104189E+09 | 0.133303E+09 | 0.178991E+09 | 0.332180E+09 |
March | 0.391244E+09 | 0.181380E+09 | 0.209864E+09 | 0.385622E+09 | 0.218641E+09 |
April | 0.410778E+09 | 0.175368E+09 | 0.235410E+09 | 0.455687E+09 | 0.148368E+09 |
May | 0.496111E+09 | 0.188501E+09 | 0.307610E+09 | 0.598096E+09 | 0.108464E+09 |
June | 0.525437E+09 | 0.212403E+09 | 0.313034E+09 | 0.672979E+09 | 83349416.01 |
July | 0.507864E+09 | 0.191251E+09 | 0.316613E+09 | 0.690351E+09 | 58235963.20 |
August | 0.561496E+09 | 0.259726E+09 | 0.301770E+09 | 0.764563E+09 | 78242531.06 |
September | 0.386558E+09 | 0.168883E+09 | 0.217675E+09 | 0.470989E+09 | 0.125548E+09 |
October | 0.394574E+09 | 0.191543E+09 | 0.203031E+09 | 0.450414E+09 | 0.189157E+09 |
November | 0.180104E+09 | 52254950.93 | 0.127849E+09 | 0.142489E+09 | 0.235704E+09 |
December | 0.165270E+09 | 71598160.95 | 93671926.80 | 0.116930E+09 | 0.327165E+09 |
Annual Sum or Average | 0.443632E+10 | 0.187079E+10 | 0.256553E+10 | 0.504883E+10 | 0.226857E+10 |
Minimum of Months | 0.165270E+09 | 52254950.93 | 93671926.80 | 0.116930E+09 | 58235963.20 |
Maximum of Months | 0.561496E+09 | 0.259726E+09 | 0.316613E+09 | 0.764563E+09 | 0.363512E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 50539940.45 | 0.00 | 50539940.45 | 6118669.71 | 0.225134E+09 |
February | 62468760.43 | 0.00 | 62468760.43 | 10021450.54 | 0.207996E+09 |
March | 95940333.05 | 5485.93 | 95934847.13 | 48331305.94 | 0.135431E+09 |
April | 0.111551E+09 | 366472.76 | 0.111185E+09 | 89712485.94 | 87739576.91 |
May | 0.153450E+09 | 5553385.69 | 0.147897E+09 | 0.159129E+09 | 61302889.57 |
June | 0.156582E+09 | 8158391.97 | 0.148424E+09 | 0.185272E+09 | 46764236.48 |
July | 0.156998E+09 | 5952044.75 | 0.151046E+09 | 0.209277E+09 | 33265272.23 |
August | 0.139036E+09 | 1886066.89 | 0.137150E+09 | 0.181414E+09 | 44994016.08 |
September | 0.101298E+09 | 47134.96 | 0.101251E+09 | 0.101110E+09 | 74584096.52 |
October | 90532510.95 | 0.00 | 90532510.95 | 70138243.70 | 0.113218E+09 |
November | 61451384.58 | 0.00 | 61451384.58 | 25953632.81 | 0.142493E+09 |
December | 44084273.64 | 0.00 | 44084273.64 | 4560098.54 | 0.202340E+09 |
Annual Sum or Average | 0.122393E+10 | 21968982.95 | 0.120196E+10 | 0.109104E+10 | 0.137526E+10 |
Minimum of Months | 44084273.64 | 0.00 | 44084273.64 | 4560098.54 | 33265272.23 |
Maximum of Months | 0.156998E+09 | 8158391.97 | 0.151046E+09 | 0.209277E+09 | 0.225134E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 50538286.35 | 0.00 | 50538286.35 | 6117931.45 | 0.225135E+09 |
February | 62466850.58 | 0.00 | 62466850.58 | 10020556.55 | 0.207996E+09 |
March | 95937430.31 | 5485.67 | 95931944.65 | 48328557.47 | 0.135432E+09 |
April | 0.111548E+09 | 366455.58 | 0.111182E+09 | 89708807.69 | 87739313.71 |
May | 0.153445E+09 | 5553125.39 | 0.147892E+09 | 0.159123E+09 | 61302453.80 |
June | 0.156578E+09 | 8158009.58 | 0.148420E+09 | 0.185266E+09 | 46763830.55 |
July | 0.156993E+09 | 5951765.77 | 0.151041E+09 | 0.209270E+09 | 33264819.69 |
August | 0.139032E+09 | 1885978.49 | 0.137147E+09 | 0.181409E+09 | 44993382.17 |
September | 0.101295E+09 | 47132.75 | 0.101248E+09 | 0.101106E+09 | 74583560.17 |
October | 90529842.70 | 0.00 | 90529842.70 | 70135408.14 | 0.113217E+09 |
November | 61449370.14 | 0.00 | 61449370.14 | 25951842.97 | 0.142493E+09 |
December | 44082860.69 | 0.00 | 44082860.69 | 4559587.98 | 0.202340E+09 |
Annual Sum or Average | 0.122390E+10 | 21967953.23 | 0.120193E+10 | 0.109100E+10 | 0.137526E+10 |
Minimum of Months | 44082860.69 | 0.00 | 44082860.69 | 4559587.98 | 33264819.69 |
Maximum of Months | 0.156993E+09 | 8158009.58 | 0.151041E+09 | 0.209270E+09 | 0.225135E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61819348.44 | 23949918.70 | 37869429.75 | 45790198.24 | 0.121003E+09 |
February | 92470820.50 | 48936092.02 | 43534728.48 | 79421099.05 | 0.111031E+09 |
March | 0.156890E+09 | 86868678.27 | 70021330.81 | 0.168448E+09 | 75250193.06 |
April | 0.189359E+09 | 0.107308E+09 | 82051852.43 | 0.218832E+09 | 54878471.31 |
May | 0.248098E+09 | 0.135964E+09 | 0.112134E+09 | 0.301094E+09 | 43968827.53 |
June | 0.263163E+09 | 0.151588E+09 | 0.111575E+09 | 0.322192E+09 | 38379597.68 |
July | 0.262038E+09 | 0.144598E+09 | 0.117440E+09 | 0.332418E+09 | 30735510.78 |
August | 0.268346E+09 | 0.170297E+09 | 98049293.67 | 0.338975E+09 | 42095467.97 |
September | 0.176717E+09 | 0.103588E+09 | 73129497.73 | 0.208862E+09 | 54081017.34 |
October | 0.149425E+09 | 86497473.00 | 62927287.32 | 0.171581E+09 | 74533836.16 |
November | 77157632.97 | 29262818.78 | 47894814.19 | 74141581.86 | 83008855.54 |
December | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 0.110441E+09 |
Annual Sum or Average | 0.199952E+10 | 0.111187E+10 | 0.887646E+09 | 0.230183E+10 | 0.839407E+09 |
Minimum of Months | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 30735510.78 |
Maximum of Months | 0.268346E+09 | 0.170297E+09 | 0.117440E+09 | 0.338975E+09 | 0.121003E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61819348.44 | 23949918.70 | 37869429.75 | 45790198.24 | 0.121003E+09 |
February | 92470820.50 | 48936092.02 | 43534728.48 | 79421099.05 | 0.111031E+09 |
March | 0.156890E+09 | 86868678.27 | 70021330.81 | 0.168448E+09 | 75250193.06 |
April | 0.189359E+09 | 0.107308E+09 | 82051852.43 | 0.218832E+09 | 54878471.31 |
May | 0.248098E+09 | 0.135964E+09 | 0.112134E+09 | 0.301094E+09 | 43968827.53 |
June | 0.263163E+09 | 0.151588E+09 | 0.111575E+09 | 0.322192E+09 | 38379597.68 |
July | 0.262038E+09 | 0.144598E+09 | 0.117440E+09 | 0.332418E+09 | 30735510.78 |
August | 0.268346E+09 | 0.170297E+09 | 98049293.67 | 0.338975E+09 | 42095467.97 |
September | 0.176717E+09 | 0.103588E+09 | 73129497.73 | 0.208862E+09 | 54081017.34 |
October | 0.149425E+09 | 86497473.00 | 62927287.32 | 0.171581E+09 | 74533836.16 |
November | 77157632.97 | 29262818.78 | 47894814.19 | 74141581.86 | 83008855.54 |
December | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 0.110441E+09 |
Annual Sum or Average | 0.199952E+10 | 0.111187E+10 | 0.887646E+09 | 0.230183E+10 | 0.839407E+09 |
Minimum of Months | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 30735510.78 |
Maximum of Months | 0.268346E+09 | 0.170297E+09 | 0.117440E+09 | 0.338975E+09 | 0.121003E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61819348.44 | 23949918.70 | 37869429.75 | 45790198.24 | 0.121003E+09 |
February | 92470820.50 | 48936092.02 | 43534728.48 | 79421099.05 | 0.111031E+09 |
March | 0.156890E+09 | 86868678.27 | 70021330.81 | 0.168448E+09 | 75250193.06 |
April | 0.189359E+09 | 0.107308E+09 | 82051852.43 | 0.218832E+09 | 54878471.31 |
May | 0.248098E+09 | 0.135964E+09 | 0.112134E+09 | 0.301094E+09 | 43968827.53 |
June | 0.263163E+09 | 0.151588E+09 | 0.111575E+09 | 0.322192E+09 | 38379597.68 |
July | 0.262038E+09 | 0.144598E+09 | 0.117440E+09 | 0.332418E+09 | 30735510.78 |
August | 0.268346E+09 | 0.170297E+09 | 98049293.67 | 0.338975E+09 | 42095467.97 |
September | 0.176717E+09 | 0.103588E+09 | 73129497.73 | 0.208862E+09 | 54081017.34 |
October | 0.149425E+09 | 86497473.00 | 62927287.32 | 0.171581E+09 | 74533836.16 |
November | 77157632.97 | 29262818.78 | 47894814.19 | 74141581.86 | 83008855.54 |
December | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 0.110441E+09 |
Annual Sum or Average | 0.199952E+10 | 0.111187E+10 | 0.887646E+09 | 0.230183E+10 | 0.839407E+09 |
Minimum of Months | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 30735510.78 |
Maximum of Months | 0.268346E+09 | 0.170297E+09 | 0.117440E+09 | 0.338975E+09 | 0.121003E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61819348.44 | 23949918.70 | 37869429.75 | 45790198.24 | 0.121003E+09 |
February | 92470820.50 | 48936092.02 | 43534728.48 | 79421099.05 | 0.111031E+09 |
March | 0.156890E+09 | 86868678.27 | 70021330.81 | 0.168448E+09 | 75250193.06 |
April | 0.189359E+09 | 0.107308E+09 | 82051852.43 | 0.218832E+09 | 54878471.31 |
May | 0.248098E+09 | 0.135964E+09 | 0.112134E+09 | 0.301094E+09 | 43968827.53 |
June | 0.263163E+09 | 0.151588E+09 | 0.111575E+09 | 0.322192E+09 | 38379597.68 |
July | 0.262038E+09 | 0.144598E+09 | 0.117440E+09 | 0.332418E+09 | 30735510.78 |
August | 0.268346E+09 | 0.170297E+09 | 98049293.67 | 0.338975E+09 | 42095467.97 |
September | 0.176717E+09 | 0.103588E+09 | 73129497.73 | 0.208862E+09 | 54081017.34 |
October | 0.149425E+09 | 86497473.00 | 62927287.32 | 0.171581E+09 | 74533836.16 |
November | 77157632.97 | 29262818.78 | 47894814.19 | 74141581.86 | 83008855.54 |
December | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 0.110441E+09 |
Annual Sum or Average | 0.199952E+10 | 0.111187E+10 | 0.887646E+09 | 0.230183E+10 | 0.839407E+09 |
Minimum of Months | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 30735510.78 |
Maximum of Months | 0.268346E+09 | 0.170297E+09 | 0.117440E+09 | 0.338975E+09 | 0.121003E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61819348.44 | 23949918.70 | 37869429.75 | 45790198.24 | 0.121003E+09 |
February | 92470820.50 | 48936092.02 | 43534728.48 | 79421099.05 | 0.111031E+09 |
March | 0.156890E+09 | 86868678.27 | 70021330.81 | 0.168448E+09 | 75250193.06 |
April | 0.189359E+09 | 0.107308E+09 | 82051852.43 | 0.218832E+09 | 54878471.31 |
May | 0.248098E+09 | 0.135964E+09 | 0.112134E+09 | 0.301094E+09 | 43968827.53 |
June | 0.263163E+09 | 0.151588E+09 | 0.111575E+09 | 0.322192E+09 | 38379597.68 |
July | 0.262038E+09 | 0.144598E+09 | 0.117440E+09 | 0.332418E+09 | 30735510.78 |
August | 0.268346E+09 | 0.170297E+09 | 98049293.67 | 0.338975E+09 | 42095467.97 |
September | 0.176717E+09 | 0.103588E+09 | 73129497.73 | 0.208862E+09 | 54081017.34 |
October | 0.149425E+09 | 86497473.00 | 62927287.32 | 0.171581E+09 | 74533836.16 |
November | 77157632.97 | 29262818.78 | 47894814.19 | 74141581.86 | 83008855.54 |
December | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 0.110441E+09 |
Annual Sum or Average | 0.199952E+10 | 0.111187E+10 | 0.887646E+09 | 0.230183E+10 | 0.839407E+09 |
Minimum of Months | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 30735510.78 |
Maximum of Months | 0.268346E+09 | 0.170297E+09 | 0.117440E+09 | 0.338975E+09 | 0.121003E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61819348.44 | 23949918.70 | 37869429.75 | 45790198.24 | 0.121003E+09 |
February | 92470820.50 | 48936092.02 | 43534728.48 | 79421099.05 | 0.111031E+09 |
March | 0.156890E+09 | 86868678.27 | 70021330.81 | 0.168448E+09 | 75250193.06 |
April | 0.189359E+09 | 0.107308E+09 | 82051852.43 | 0.218832E+09 | 54878471.31 |
May | 0.248098E+09 | 0.135964E+09 | 0.112134E+09 | 0.301094E+09 | 43968827.53 |
June | 0.263163E+09 | 0.151588E+09 | 0.111575E+09 | 0.322192E+09 | 38379597.68 |
July | 0.262038E+09 | 0.144598E+09 | 0.117440E+09 | 0.332418E+09 | 30735510.78 |
August | 0.268346E+09 | 0.170297E+09 | 98049293.67 | 0.338975E+09 | 42095467.97 |
September | 0.176717E+09 | 0.103588E+09 | 73129497.73 | 0.208862E+09 | 54081017.34 |
October | 0.149425E+09 | 86497473.00 | 62927287.32 | 0.171581E+09 | 74533836.16 |
November | 77157632.97 | 29262818.78 | 47894814.19 | 74141581.86 | 83008855.54 |
December | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 0.110441E+09 |
Annual Sum or Average | 0.199952E+10 | 0.111187E+10 | 0.887646E+09 | 0.230183E+10 | 0.839407E+09 |
Minimum of Months | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 30735510.78 |
Maximum of Months | 0.268346E+09 | 0.170297E+09 | 0.117440E+09 | 0.338975E+09 | 0.121003E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61819348.44 | 23949918.70 | 37869429.75 | 45790198.24 | 0.121003E+09 |
February | 92470820.50 | 48936092.02 | 43534728.48 | 79421099.05 | 0.111031E+09 |
March | 0.156890E+09 | 86868678.27 | 70021330.81 | 0.168448E+09 | 75250193.06 |
April | 0.189359E+09 | 0.107308E+09 | 82051852.43 | 0.218832E+09 | 54878471.31 |
May | 0.248098E+09 | 0.135964E+09 | 0.112134E+09 | 0.301094E+09 | 43968827.53 |
June | 0.263163E+09 | 0.151588E+09 | 0.111575E+09 | 0.322192E+09 | 38379597.68 |
July | 0.262038E+09 | 0.144598E+09 | 0.117440E+09 | 0.332418E+09 | 30735510.78 |
August | 0.268346E+09 | 0.170297E+09 | 98049293.67 | 0.338975E+09 | 42095467.97 |
September | 0.176717E+09 | 0.103588E+09 | 73129497.73 | 0.208862E+09 | 54081017.34 |
October | 0.149425E+09 | 86497473.00 | 62927287.32 | 0.171581E+09 | 74533836.16 |
November | 77157632.97 | 29262818.78 | 47894814.19 | 74141581.86 | 83008855.54 |
December | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 0.110441E+09 |
Annual Sum or Average | 0.199952E+10 | 0.111187E+10 | 0.887646E+09 | 0.230183E+10 | 0.839407E+09 |
Minimum of Months | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 30735510.78 |
Maximum of Months | 0.268346E+09 | 0.170297E+09 | 0.117440E+09 | 0.338975E+09 | 0.121003E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61819348.44 | 23949918.70 | 37869429.75 | 45790198.24 | 0.121003E+09 |
February | 92470820.50 | 48936092.02 | 43534728.48 | 79421099.05 | 0.111031E+09 |
March | 0.156890E+09 | 86868678.27 | 70021330.81 | 0.168448E+09 | 75250193.06 |
April | 0.189359E+09 | 0.107308E+09 | 82051852.43 | 0.218832E+09 | 54878471.31 |
May | 0.248098E+09 | 0.135964E+09 | 0.112134E+09 | 0.301094E+09 | 43968827.53 |
June | 0.263163E+09 | 0.151588E+09 | 0.111575E+09 | 0.322192E+09 | 38379597.68 |
July | 0.262038E+09 | 0.144598E+09 | 0.117440E+09 | 0.332418E+09 | 30735510.78 |
August | 0.268346E+09 | 0.170297E+09 | 98049293.67 | 0.338975E+09 | 42095467.97 |
September | 0.176717E+09 | 0.103588E+09 | 73129497.73 | 0.208862E+09 | 54081017.34 |
October | 0.149425E+09 | 86497473.00 | 62927287.32 | 0.171581E+09 | 74533836.16 |
November | 77157632.97 | 29262818.78 | 47894814.19 | 74141581.86 | 83008855.54 |
December | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 0.110441E+09 |
Annual Sum or Average | 0.199952E+10 | 0.111187E+10 | 0.887646E+09 | 0.230183E+10 | 0.839407E+09 |
Minimum of Months | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 30735510.78 |
Maximum of Months | 0.268346E+09 | 0.170297E+09 | 0.117440E+09 | 0.338975E+09 | 0.121003E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61819348.44 | 23949918.70 | 37869429.75 | 45790198.24 | 0.121003E+09 |
February | 92470820.50 | 48936092.02 | 43534728.48 | 79421099.05 | 0.111031E+09 |
March | 0.156890E+09 | 86868678.27 | 70021330.81 | 0.168448E+09 | 75250193.06 |
April | 0.189359E+09 | 0.107308E+09 | 82051852.43 | 0.218832E+09 | 54878471.31 |
May | 0.248098E+09 | 0.135964E+09 | 0.112134E+09 | 0.301094E+09 | 43968827.53 |
June | 0.263163E+09 | 0.151588E+09 | 0.111575E+09 | 0.322192E+09 | 38379597.68 |
July | 0.262038E+09 | 0.144598E+09 | 0.117440E+09 | 0.332418E+09 | 30735510.78 |
August | 0.268346E+09 | 0.170297E+09 | 98049293.67 | 0.338975E+09 | 42095467.97 |
September | 0.176717E+09 | 0.103588E+09 | 73129497.73 | 0.208862E+09 | 54081017.34 |
October | 0.149425E+09 | 86497473.00 | 62927287.32 | 0.171581E+09 | 74533836.16 |
November | 77157632.97 | 29262818.78 | 47894814.19 | 74141581.86 | 83008855.54 |
December | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 0.110441E+09 |
Annual Sum or Average | 0.199952E+10 | 0.111187E+10 | 0.887646E+09 | 0.230183E+10 | 0.839407E+09 |
Minimum of Months | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 30735510.78 |
Maximum of Months | 0.268346E+09 | 0.170297E+09 | 0.117440E+09 | 0.338975E+09 | 0.121003E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61819348.44 | 23949918.70 | 37869429.75 | 45790198.24 | 0.121003E+09 |
February | 92470820.50 | 48936092.02 | 43534728.48 | 79421099.05 | 0.111031E+09 |
March | 0.156890E+09 | 86868678.27 | 70021330.81 | 0.168448E+09 | 75250193.06 |
April | 0.189359E+09 | 0.107308E+09 | 82051852.43 | 0.218832E+09 | 54878471.31 |
May | 0.248098E+09 | 0.135964E+09 | 0.112134E+09 | 0.301094E+09 | 43968827.53 |
June | 0.263163E+09 | 0.151588E+09 | 0.111575E+09 | 0.322192E+09 | 38379597.68 |
July | 0.262038E+09 | 0.144598E+09 | 0.117440E+09 | 0.332418E+09 | 30735510.78 |
August | 0.268346E+09 | 0.170297E+09 | 98049293.67 | 0.338975E+09 | 42095467.97 |
September | 0.176717E+09 | 0.103588E+09 | 73129497.73 | 0.208862E+09 | 54081017.34 |
October | 0.149425E+09 | 86497473.00 | 62927287.32 | 0.171581E+09 | 74533836.16 |
November | 77157632.97 | 29262818.78 | 47894814.19 | 74141581.86 | 83008855.54 |
December | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 0.110441E+09 |
Annual Sum or Average | 0.199952E+10 | 0.111187E+10 | 0.887646E+09 | 0.230183E+10 | 0.839407E+09 |
Minimum of Months | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 30735510.78 |
Maximum of Months | 0.268346E+09 | 0.170297E+09 | 0.117440E+09 | 0.338975E+09 | 0.121003E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61819348.44 | 23949918.70 | 37869429.75 | 45790198.24 | 0.121003E+09 |
February | 92470820.50 | 48936092.02 | 43534728.48 | 79421099.05 | 0.111031E+09 |
March | 0.156890E+09 | 86868678.27 | 70021330.81 | 0.168448E+09 | 75250193.06 |
April | 0.189359E+09 | 0.107308E+09 | 82051852.43 | 0.218832E+09 | 54878471.31 |
May | 0.248098E+09 | 0.135964E+09 | 0.112134E+09 | 0.301094E+09 | 43968827.53 |
June | 0.263163E+09 | 0.151588E+09 | 0.111575E+09 | 0.322192E+09 | 38379597.68 |
July | 0.262038E+09 | 0.144598E+09 | 0.117440E+09 | 0.332418E+09 | 30735510.78 |
August | 0.268346E+09 | 0.170297E+09 | 98049293.67 | 0.338975E+09 | 42095467.97 |
September | 0.176717E+09 | 0.103588E+09 | 73129497.73 | 0.208862E+09 | 54081017.34 |
October | 0.149425E+09 | 86497473.00 | 62927287.32 | 0.171581E+09 | 74533836.16 |
November | 77157632.97 | 29262818.78 | 47894814.19 | 74141581.86 | 83008855.54 |
December | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 0.110441E+09 |
Annual Sum or Average | 0.199952E+10 | 0.111187E+10 | 0.887646E+09 | 0.230183E+10 | 0.839407E+09 |
Minimum of Months | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 30735510.78 |
Maximum of Months | 0.268346E+09 | 0.170297E+09 | 0.117440E+09 | 0.338975E+09 | 0.121003E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61819348.44 | 23949918.70 | 37869429.75 | 45790198.24 | 0.121003E+09 |
February | 92470820.50 | 48936092.02 | 43534728.48 | 79421099.05 | 0.111031E+09 |
March | 0.156890E+09 | 86868678.27 | 70021330.81 | 0.168448E+09 | 75250193.06 |
April | 0.189359E+09 | 0.107308E+09 | 82051852.43 | 0.218832E+09 | 54878471.31 |
May | 0.248098E+09 | 0.135964E+09 | 0.112134E+09 | 0.301094E+09 | 43968827.53 |
June | 0.263163E+09 | 0.151588E+09 | 0.111575E+09 | 0.322192E+09 | 38379597.68 |
July | 0.262038E+09 | 0.144598E+09 | 0.117440E+09 | 0.332418E+09 | 30735510.78 |
August | 0.268346E+09 | 0.170297E+09 | 98049293.67 | 0.338975E+09 | 42095467.97 |
September | 0.176717E+09 | 0.103588E+09 | 73129497.73 | 0.208862E+09 | 54081017.34 |
October | 0.149425E+09 | 86497473.00 | 62927287.32 | 0.171581E+09 | 74533836.16 |
November | 77157632.97 | 29262818.78 | 47894814.19 | 74141581.86 | 83008855.54 |
December | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 0.110441E+09 |
Annual Sum or Average | 0.199952E+10 | 0.111187E+10 | 0.887646E+09 | 0.230183E+10 | 0.839407E+09 |
Minimum of Months | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 30735510.78 |
Maximum of Months | 0.268346E+09 | 0.170297E+09 | 0.117440E+09 | 0.338975E+09 | 0.121003E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61819348.44 | 23949918.70 | 37869429.75 | 45790198.24 | 0.121003E+09 |
February | 92470820.50 | 48936092.02 | 43534728.48 | 79421099.05 | 0.111031E+09 |
March | 0.156890E+09 | 86868678.27 | 70021330.81 | 0.168448E+09 | 75250193.06 |
April | 0.189359E+09 | 0.107308E+09 | 82051852.43 | 0.218832E+09 | 54878471.31 |
May | 0.248098E+09 | 0.135964E+09 | 0.112134E+09 | 0.301094E+09 | 43968827.53 |
June | 0.263163E+09 | 0.151588E+09 | 0.111575E+09 | 0.322192E+09 | 38379597.68 |
July | 0.262038E+09 | 0.144598E+09 | 0.117440E+09 | 0.332418E+09 | 30735510.78 |
August | 0.268346E+09 | 0.170297E+09 | 98049293.67 | 0.338975E+09 | 42095467.97 |
September | 0.176717E+09 | 0.103588E+09 | 73129497.73 | 0.208862E+09 | 54081017.34 |
October | 0.149425E+09 | 86497473.00 | 62927287.32 | 0.171581E+09 | 74533836.16 |
November | 77157632.97 | 29262818.78 | 47894814.19 | 74141581.86 | 83008855.54 |
December | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 0.110441E+09 |
Annual Sum or Average | 0.199952E+10 | 0.111187E+10 | 0.887646E+09 | 0.230183E+10 | 0.839407E+09 |
Minimum of Months | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 30735510.78 |
Maximum of Months | 0.268346E+09 | 0.170297E+09 | 0.117440E+09 | 0.338975E+09 | 0.121003E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61819348.44 | 23949918.70 | 37869429.75 | 45790198.24 | 0.121003E+09 |
February | 92470820.50 | 48936092.02 | 43534728.48 | 79421099.05 | 0.111031E+09 |
March | 0.156890E+09 | 86868678.27 | 70021330.81 | 0.168448E+09 | 75250193.06 |
April | 0.189359E+09 | 0.107308E+09 | 82051852.43 | 0.218832E+09 | 54878471.31 |
May | 0.248098E+09 | 0.135964E+09 | 0.112134E+09 | 0.301094E+09 | 43968827.53 |
June | 0.263163E+09 | 0.151588E+09 | 0.111575E+09 | 0.322192E+09 | 38379597.68 |
July | 0.262038E+09 | 0.144598E+09 | 0.117440E+09 | 0.332418E+09 | 30735510.78 |
August | 0.268346E+09 | 0.170297E+09 | 98049293.67 | 0.338975E+09 | 42095467.97 |
September | 0.176717E+09 | 0.103588E+09 | 73129497.73 | 0.208862E+09 | 54081017.34 |
October | 0.149425E+09 | 86497473.00 | 62927287.32 | 0.171581E+09 | 74533836.16 |
November | 77157632.97 | 29262818.78 | 47894814.19 | 74141581.86 | 83008855.54 |
December | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 0.110441E+09 |
Annual Sum or Average | 0.199952E+10 | 0.111187E+10 | 0.887646E+09 | 0.230183E+10 | 0.839407E+09 |
Minimum of Months | 54033118.94 | 23014629.97 | 31018488.97 | 40071405.60 | 30735510.78 |
Maximum of Months | 0.268346E+09 | 0.170297E+09 | 0.117440E+09 | 0.338975E+09 | 0.121003E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86236989.71 | 35700737.93 | 50536251.79 | 83141813.45 | 0.159403E+09 |
February | 0.126775E+09 | 68678544.03 | 58096517.82 | 0.131322E+09 | 0.151297E+09 |
March | 0.209576E+09 | 0.116134E+09 | 93442537.37 | 0.265467E+09 | 92249621.65 |
April | 0.250460E+09 | 0.140963E+09 | 0.109497E+09 | 0.329727E+09 | 76221608.20 |
May | 0.326476E+09 | 0.176835E+09 | 0.149642E+09 | 0.442324E+09 | 69768979.77 |
June | 0.345123E+09 | 0.196227E+09 | 0.148896E+09 | 0.460121E+09 | 72361206.77 |
July | 0.343989E+09 | 0.187268E+09 | 0.156722E+09 | 0.467880E+09 | 67567971.57 |
August | 0.353007E+09 | 0.222161E+09 | 0.130845E+09 | 0.479437E+09 | 89652571.27 |
September | 0.234313E+09 | 0.136722E+09 | 97590344.91 | 0.299817E+09 | 98399194.36 |
October | 0.202137E+09 | 0.118161E+09 | 83975630.41 | 0.259954E+09 | 0.114192E+09 |
November | 0.106285E+09 | 42369695.21 | 63914994.38 | 0.122313E+09 | 0.108993E+09 |
December | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 0.136274E+09 |
Annual Sum or Average | 0.266102E+10 | 0.147647E+10 | 0.118455E+10 | 0.341725E+10 | 0.123638E+10 |
Minimum of Months | 76644083.80 | 35250321.63 | 41393762.17 | 75747722.41 | 67567971.57 |
Maximum of Months | 0.353007E+09 | 0.222161E+09 | 0.156722E+09 | 0.479437E+09 | 0.159403E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 88.33 | 432.42 | 171.69 | 55.03 | 116.66 | 0.00 | 0.00 |
February | 147.58 | 437.90 | 247.98 | 86.13 | 161.85 | 0.00 | 0.00 |
March | 319.15 | 259.50 | 363.79 | 135.44 | 228.34 | 0.00 | 0.00 |
April | 419.57 | 180.92 | 403.03 | 135.60 | 267.43 | 0.00 | 0.00 |
May | 564.25 | 125.59 | 485.03 | 144.90 | 340.13 | 0.00 | 0.00 |
June | 661.15 | 99.32 | 526.25 | 170.19 | 356.06 | 0.00 | 0.00 |
July | 671.19 | 67.75 | 496.46 | 147.25 | 349.21 | 0.00 | 0.00 |
August | 706.00 | 91.65 | 523.10 | 195.35 | 327.75 | 0.00 | 0.00 |
September | 440.60 | 153.59 | 376.43 | 130.35 | 246.08 | 0.00 | 0.00 |
October | 386.63 | 223.72 | 362.24 | 143.03 | 219.21 | 0.00 | 0.00 |
November | 127.07 | 288.92 | 186.38 | 40.32 | 146.06 | 0.00 | 0.00 |
December | 83.87 | 388.54 | 156.33 | 53.46 | 102.86 | 0.00 | 0.00 |
Annual Sum or Average | 386.26 | 227.97 | 358.97 | 120.04 | 238.93 | 0.00 | 0.00 |
Minimum of Months | 83.87 | 67.75 | 156.33 | 40.32 | 102.86 | 0.00 | 0.00 |
Maximum of Months | 706.00 | 437.90 | 526.25 | 195.35 | 356.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 239.35 | 632.48 | 323.13 | 125.19 | 197.94 | 0.00 | 0.00 |
February | 459.61 | 642.54 | 535.13 | 283.19 | 251.94 | 0.00 | 0.00 |
March | 880.48 | 393.33 | 820.06 | 454.06 | 366.00 | 0.00 | 0.00 |
April | 1181.96 | 296.41 | 1022.77 | 579.59 | 443.18 | 0.00 | 0.00 |
May | 1573.82 | 229.83 | 1296.81 | 710.68 | 586.13 | 0.00 | 0.00 |
June | 1740.23 | 207.30 | 1421.41 | 818.76 | 602.64 | 0.00 | 0.00 |
July | 1737.55 | 160.65 | 1369.67 | 755.81 | 613.86 | 0.00 | 0.00 |
August | 1771.82 | 220.03 | 1402.64 | 890.14 | 512.50 | 0.00 | 0.00 |
September | 1128.11 | 292.10 | 954.49 | 559.50 | 394.99 | 0.00 | 0.00 |
October | 896.85 | 389.59 | 781.04 | 452.12 | 328.92 | 0.00 | 0.00 |
November | 400.46 | 448.35 | 416.75 | 158.06 | 258.69 | 0.00 | 0.00 |
December | 209.45 | 577.27 | 282.43 | 120.30 | 162.13 | 0.00 | 0.00 |
Annual Sum or Average | 1021.87 | 372.64 | 887.66 | 493.60 | 394.06 | 0.00 | 0.00 |
Minimum of Months | 209.45 | 160.65 | 282.43 | 120.30 | 162.13 | 0.00 | 0.00 |
Maximum of Months | 1771.82 | 642.54 | 1421.41 | 890.14 | 613.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4750.26 | 14016.12 | 1030.31 | 426.53 | 603.78 | 0.00 | 0.00 |
February | 8193.92 | 15207.80 | 1676.92 | 908.45 | 768.47 | 0.00 | 0.00 |
March | 13730.45 | 6892.38 | 2503.90 | 1387.50 | 1116.40 | 0.00 | 0.00 |
April | 16128.03 | 3978.13 | 3092.10 | 1740.29 | 1351.82 | 0.00 | 0.00 |
May | 20876.73 | 2545.99 | 3900.55 | 2112.72 | 1787.83 | 0.00 | 0.00 |
June | 24984.41 | 2773.73 | 4260.78 | 2422.56 | 1838.22 | 0.00 | 0.00 |
July | 29500.23 | 2711.34 | 4109.79 | 2237.37 | 1872.42 | 0.00 | 0.00 |
August | 30748.06 | 3991.98 | 4217.52 | 2654.26 | 1563.27 | 0.00 | 0.00 |
September | 16613.19 | 3965.69 | 2892.75 | 1687.93 | 1204.82 | 0.00 | 0.00 |
October | 12646.09 | 4297.53 | 2415.01 | 1411.72 | 1003.29 | 0.00 | 0.00 |
November | 6339.35 | 7220.31 | 1312.16 | 523.08 | 789.07 | 0.00 | 0.00 |
December | 4052.04 | 10452.30 | 915.70 | 421.15 | 494.55 | 0.00 | 0.00 |
Annual Sum or Average | 15772.05 | 6455.04 | 2700.17 | 1498.19 | 1201.98 | 0.00 | 0.00 |
Minimum of Months | 4052.04 | 2545.99 | 915.70 | 421.15 | 494.55 | 0.00 | 0.00 |
Maximum of Months | 30748.06 | 15207.80 | 4260.78 | 2654.26 | 1872.42 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.236578E+09 | 0.115821E+10 | 0.459866E+09 | 0.147397E+09 | 0.312469E+09 | 0.00 | 0.00 |
February | 0.357032E+09 | 0.105936E+10 | 0.599920E+09 | 0.208378E+09 | 0.391542E+09 | 0.00 | 0.00 |
March | 0.854811E+09 | 0.695053E+09 | 0.974366E+09 | 0.362770E+09 | 0.611596E+09 | 0.00 | 0.00 |
April | 0.108753E+10 | 0.468953E+09 | 0.104465E+10 | 0.351468E+09 | 0.693187E+09 | 0.00 | 0.00 |
May | 0.151128E+10 | 0.336374E+09 | 0.129912E+10 | 0.388108E+09 | 0.911009E+09 | 0.00 | 0.00 |
June | 0.171370E+10 | 0.257431E+09 | 0.136403E+10 | 0.441122E+09 | 0.922912E+09 | 0.00 | 0.00 |
July | 0.179771E+10 | 0.181465E+09 | 0.132972E+10 | 0.394406E+09 | 0.935314E+09 | 0.00 | 0.00 |
August | 0.189095E+10 | 0.245475E+09 | 0.140106E+10 | 0.523223E+09 | 0.877838E+09 | 0.00 | 0.00 |
September | 0.114205E+10 | 0.398117E+09 | 0.975709E+09 | 0.337860E+09 | 0.637849E+09 | 0.00 | 0.00 |
October | 0.103555E+10 | 0.599200E+09 | 0.970210E+09 | 0.383086E+09 | 0.587124E+09 | 0.00 | 0.00 |
November | 0.329370E+09 | 0.748881E+09 | 0.483109E+09 | 0.104510E+09 | 0.378599E+09 | 0.00 | 0.00 |
December | 0.224626E+09 | 0.104066E+10 | 0.418707E+09 | 0.143196E+09 | 0.275511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.121812E+11 | 0.718917E+10 | 0.113205E+11 | 0.378552E+10 | 0.753495E+10 | 0.00 | 0.00 |
Minimum of Months | 0.224626E+09 | 0.181465E+09 | 0.418707E+09 | 0.104510E+09 | 0.275511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.189095E+10 | 0.115821E+10 | 0.140106E+10 | 0.523223E+09 | 0.935314E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.641063E+09 | 0.169404E+10 | 0.865471E+09 | 0.335299E+09 | 0.530172E+09 | 0.00 | 0.00 |
February | 0.111190E+10 | 0.155444E+10 | 0.129459E+10 | 0.685105E+09 | 0.609486E+09 | 0.00 | 0.00 |
March | 0.235827E+10 | 0.105350E+10 | 0.219646E+10 | 0.121616E+10 | 0.980299E+09 | 0.00 | 0.00 |
April | 0.306364E+10 | 0.768299E+09 | 0.265103E+10 | 0.150231E+10 | 0.114873E+10 | 0.00 | 0.00 |
May | 0.421532E+10 | 0.615564E+09 | 0.347338E+10 | 0.190350E+10 | 0.156988E+10 | 0.00 | 0.00 |
June | 0.451068E+10 | 0.537314E+09 | 0.368428E+10 | 0.212223E+10 | 0.156205E+10 | 0.00 | 0.00 |
July | 0.465385E+10 | 0.430297E+09 | 0.366853E+10 | 0.202437E+10 | 0.164416E+10 | 0.00 | 0.00 |
August | 0.474565E+10 | 0.589337E+09 | 0.375684E+10 | 0.238415E+10 | 0.137269E+10 | 0.00 | 0.00 |
September | 0.292407E+10 | 0.757134E+09 | 0.247404E+10 | 0.145023E+10 | 0.102381E+10 | 0.00 | 0.00 |
October | 0.240213E+10 | 0.104347E+10 | 0.209195E+10 | 0.121096E+10 | 0.880982E+09 | 0.00 | 0.00 |
November | 0.103798E+10 | 0.116212E+10 | 0.108021E+10 | 0.409679E+09 | 0.670527E+09 | 0.00 | 0.00 |
December | 0.561000E+09 | 0.154617E+10 | 0.756464E+09 | 0.322205E+09 | 0.434259E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.322256E+11 | 0.117517E+11 | 0.279932E+11 | 0.155662E+11 | 0.124270E+11 | 0.00 | 0.00 |
Minimum of Months | 0.561000E+09 | 0.430297E+09 | 0.756464E+09 | 0.322205E+09 | 0.434259E+09 | 0.00 | 0.00 |
Maximum of Months | 0.474565E+10 | 0.169404E+10 | 0.375684E+10 | 0.238415E+10 | 0.164416E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.127231E+11 | 0.375408E+11 | 0.275958E+10 | 0.114242E+10 | 0.161716E+10 | 0.00 | 0.00 |
February | 0.198227E+11 | 0.367907E+11 | 0.405680E+10 | 0.219771E+10 | 0.185909E+10 | 0.00 | 0.00 |
March | 0.367756E+11 | 0.184606E+11 | 0.670644E+10 | 0.371628E+10 | 0.299016E+10 | 0.00 | 0.00 |
April | 0.418039E+11 | 0.103113E+11 | 0.801473E+10 | 0.451083E+10 | 0.350391E+10 | 0.00 | 0.00 |
May | 0.559162E+11 | 0.681917E+10 | 0.104472E+11 | 0.565871E+10 | 0.478853E+10 | 0.00 | 0.00 |
June | 0.647596E+11 | 0.718951E+10 | 0.110439E+11 | 0.627926E+10 | 0.476467E+10 | 0.00 | 0.00 |
July | 0.790134E+11 | 0.726204E+10 | 0.110077E+11 | 0.599256E+10 | 0.501510E+10 | 0.00 | 0.00 |
August | 0.823556E+11 | 0.106921E+11 | 0.112962E+11 | 0.710916E+10 | 0.418706E+10 | 0.00 | 0.00 |
September | 0.430614E+11 | 0.102791E+11 | 0.749800E+10 | 0.437511E+10 | 0.312289E+10 | 0.00 | 0.00 |
October | 0.338713E+11 | 0.115105E+11 | 0.646837E+10 | 0.378115E+10 | 0.268722E+10 | 0.00 | 0.00 |
November | 0.164316E+11 | 0.187150E+11 | 0.340111E+10 | 0.135583E+10 | 0.204528E+10 | 0.00 | 0.00 |
December | 0.108530E+11 | 0.279954E+11 | 0.245261E+10 | 0.112801E+10 | 0.132460E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.497387E+12 | 0.203566E+12 | 0.851527E+11 | 0.472470E+11 | 0.379057E+11 | 0.00 | 0.00 |
Minimum of Months | 0.108530E+11 | 0.681917E+10 | 0.245261E+10 | 0.112801E+10 | 0.132460E+10 | 0.00 | 0.00 |
Maximum of Months | 0.823556E+11 | 0.375408E+11 | 0.112962E+11 | 0.710916E+10 | 0.501510E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.962463E+09 | -874646822.1 | 0.00 | 0.00 | 744.00 | 0.00 | -87816010.8 | 58.99 | 0.00 | 0.00 |
February | 0.890800E+09 | -811504280.8 | 0.00 | 0.00 | 672.00 | 0.00 | -79295769.2 | 59.00 | 0.00 | 0.00 |
March | 0.101369E+10 | -926994220.1 | 0.00 | 0.00 | 744.00 | 0.00 | -86690831.7 | 58.99 | 0.00 | 0.00 |
April | 0.898378E+09 | -817017061.6 | 0.00 | 0.00 | 720.00 | 0.00 | -81360879.6 | 58.99 | 0.00 | 0.00 |
May | 0.869238E+09 | -790953894.5 | 0.00 | 0.00 | 744.00 | 0.00 | -78284024.1 | 58.99 | 0.00 | 0.00 |
June | 0.801048E+09 | -730935324.3 | 0.00 | 0.00 | 720.00 | 0.00 | -70113015.6 | 58.99 | 0.00 | 0.00 |
July | 0.739690E+09 | -669104220.3 | 0.00 | 0.00 | 744.00 | 0.00 | -70586146.6 | 58.99 | 0.00 | 0.00 |
August | 0.779459E+09 | -708599311.2 | 0.00 | 0.00 | 744.00 | 0.00 | -70859514.7 | 58.99 | 0.00 | 0.00 |
September | 0.749929E+09 | -679649384.6 | 0.00 | 0.00 | 720.00 | 0.00 | -70279604.7 | 58.99 | 0.00 | 0.00 |
October | 0.804398E+09 | -726384803.5 | 0.00 | 0.00 | 744.00 | 0.00 | -78013069.7 | 58.99 | 0.00 | 0.00 |
November | 0.835107E+09 | -752106829.8 | 0.00 | 0.00 | 720.00 | 0.00 | -83000205.4 | 58.99 | 0.00 | 0.00 |
December | 0.924318E+09 | -836729290.7 | 0.00 | 0.00 | 744.00 | 0.00 | -87588791.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.102685E+11 | -0.932463E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -943887863.2 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.739690E+09 | -926994220.1 | 0.00 | 0.00 | 672.00 | 0.00 | -87816010.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.101369E+10 | -669104220.3 | 0.00 | 0.00 | 744.00 | 0.00 | -70113015.6 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.92 | 0.75 | 01-JAN-11:00 | 114.07 | 0.00 | 0.00 | 0.00 | 92.70 | 0.00 | 0.00 | 0.00 |
February | 216.00 | 0.90 | 0.58 | 13-FEB-11:00 | 123.67 | 0.00 | 0.00 | 1.33 | 103.94 | 0.00 | 0.00 | 0.00 |
March | 275.00 | 0.82 | 0.50 | 10-MAR-13:20 | 176.58 | 0.00 | 0.00 | 29.00 | 697.52 | 0.00 | 0.00 | 32.50 |
April | 261.17 | 0.82 | 0.50 | 02-APR-11:30 | 189.55 | 0.00 | 0.00 | 43.17 | 153.12 | 0.00 | 0.00 | 15.67 |
May | 372.00 | 0.77 | 0.50 | 01-MAY-10:39 | 237.32 | 0.00 | 0.00 | 112.33 | 184.20 | 0.00 | 0.00 | 61.33 |
June | 351.83 | 0.76 | 0.50 | 01-JUN-09:20 | 253.10 | 0.00 | 0.00 | 133.50 | 1027.23 | 0.00 | 0.00 | 76.17 |
July | 365.17 | 0.74 | 0.50 | 01-JUL-10:50 | 266.34 | 0.00 | 0.00 | 150.33 | 1056.23 | 0.00 | 0.00 | 99.00 |
August | 389.17 | 0.78 | 0.50 | 02-AUG-10:20 | 221.95 | 0.00 | 0.00 | 97.83 | 179.05 | 0.00 | 0.00 | 57.83 |
September | 285.33 | 0.82 | 0.50 | 08-SEP-10:09 | 183.75 | 0.00 | 0.00 | 38.67 | 656.29 | 0.00 | 0.00 | 26.83 |
October | 305.50 | 0.84 | 0.50 | 02-OCT-10:00 | 162.11 | 0.00 | 0.00 | 5.33 | 413.75 | 0.00 | 0.00 | 9.50 |
November | 240.83 | 0.89 | 0.67 | 01-NOV-11:20 | 133.94 | 0.00 | 0.00 | 0.00 | 108.52 | 0.00 | 0.00 | 0.00 |
December | 211.17 | 0.95 | 0.67 | 01-DEC-11:20 | 86.17 | 0.00 | 0.00 | 0.00 | 71.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3472.67 | 0.82 | 190.32 | 0.00 | 0.00 | 611.50 | 435.65 | 0.00 | 0.00 | 378.83 | ||
Minimum of Months | 199.50 | 0.74 | 0.50 | 86.17 | 0.00 | 0.00 | 0.00 | 71.05 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 389.17 | 0.95 | 0.75 | 266.34 | 0.00 | 0.00 | 150.33 | 1056.23 | 0.00 | 0.00 | 99.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.70 | 0.50 | 01-JAN-10:20 | 555.36 | 12.50 | 0.00 | 90.50 | 476.39 | 16.03 | 3.83 | 62.67 |
February | 216.00 | 0.68 | 0.50 | 01-FEB-09:20 | 760.48 | 12.80 | 0.00 | 137.00 | 755.19 | 16.64 | 26.50 | 99.17 |
March | 275.00 | 0.62 | 0.50 | 01-MAR-08:00 | 738.85 | 15.81 | 24.83 | 216.17 | 1250.05 | 17.66 | 67.00 | 163.50 |
April | 261.17 | 0.62 | 0.50 | 02-APR-07:00 | 312.01 | 14.20 | 0.00 | 254.17 | 259.32 | 18.15 | 73.50 | 211.67 |
May | 372.00 | 0.59 | 0.50 | 01-MAY-06:00 | 1820.34 | 16.54 | 45.17 | 315.33 | 322.22 | 18.74 | 110.00 | 274.17 |
June | 351.83 | 0.60 | 0.50 | 01-JUN-06:40 | 3041.77 | 16.20 | 43.33 | 314.83 | 1642.40 | 18.51 | 100.50 | 273.17 |
July | 365.17 | 0.59 | 0.50 | 01-JUL-07:10 | 3343.55 | 16.80 | 51.83 | 315.33 | 1808.66 | 20.40 | 122.00 | 291.33 |
August | 389.17 | 0.61 | 0.50 | 01-AUG-07:10 | 1156.95 | 15.13 | 14.50 | 291.83 | 304.48 | 18.63 | 122.83 | 250.33 |
September | 285.33 | 0.62 | 0.50 | 01-SEP-08:09 | 1199.83 | 14.00 | 0.50 | 235.00 | 428.87 | 18.85 | 78.00 | 198.17 |
October | 305.50 | 0.63 | 0.50 | 02-OCT-07:49 | 876.23 | 14.01 | 0.00 | 210.00 | 338.02 | 18.47 | 84.17 | 168.17 |
November | 240.83 | 0.66 | 0.50 | 01-NOV-08:00 | 223.65 | 13.54 | 0.00 | 144.67 | 185.53 | 17.01 | 28.17 | 100.17 |
December | 211.17 | 0.78 | 0.50 | 01-DEC-10:09 | 147.05 | 11.03 | 0.00 | 51.83 | 120.70 | 14.60 | 0.00 | 20.50 |
Annual Sum or Average | 3472.67 | 0.63 | 1345.72 | 14.70 | 180.17 | 2576.67 | 703.24 | 18.08 | 816.50 | 2113.00 | ||
Minimum of Months | 199.50 | 0.59 | 0.50 | 147.05 | 11.03 | 0.00 | 51.83 | 120.70 | 14.60 | 0.00 | 20.50 | |
Maximum of Months | 389.17 | 0.78 | 0.50 | 3343.55 | 16.80 | 51.83 | 315.33 | 1808.66 | 20.40 | 122.83 | 291.33 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.83 | 0.64 | 05-JAN-14:30 | 356.73 | 24.23 | 117.00 | 39.17 | 137.59 | 21.49 | 113.50 | 0.00 |
February | 216.00 | 0.80 | 0.61 | 11-FEB-16:19 | 582.82 | 25.22 | 141.50 | 67.83 | 197.06 | 23.36 | 149.83 | 17.67 |
March | 275.00 | 0.75 | 0.61 | 01-MAR-14:20 | 552.16 | 25.92 | 204.33 | 113.17 | 420.46 | 26.22 | 241.50 | 66.67 |
April | 261.17 | 0.76 | 0.61 | 01-APR-15:20 | 475.78 | 23.44 | 206.33 | 109.50 | 543.26 | 25.38 | 252.33 | 74.83 |
May | 372.00 | 0.74 | 0.61 | 01-MAY-13:30 | 395.76 | 22.46 | 256.00 | 180.00 | 333.64 | 23.64 | 305.50 | 101.83 |
June | 351.83 | 0.72 | 0.61 | 01-JUN-13:39 | 422.45 | 22.60 | 256.33 | 201.50 | 395.62 | 23.82 | 299.83 | 116.83 |
July | 365.17 | 0.72 | 0.61 | 01-JUL-13:00 | 424.22 | 22.67 | 272.83 | 223.67 | 374.36 | 23.77 | 310.00 | 107.50 |
August | 389.17 | 0.73 | 0.61 | 01-AUG-13:00 | 407.08 | 22.68 | 279.33 | 197.33 | 577.10 | 23.91 | 321.33 | 125.50 |
September | 285.33 | 0.76 | 0.61 | 01-SEP-13:50 | 528.69 | 23.86 | 210.67 | 113.33 | 512.92 | 25.82 | 249.33 | 74.33 |
October | 305.50 | 0.75 | 0.61 | 01-OCT-15:50 | 633.80 | 26.18 | 226.50 | 134.67 | 312.82 | 24.37 | 256.50 | 61.17 |
November | 240.83 | 0.82 | 0.61 | 02-NOV-14:30 | 289.70 | 23.98 | 154.00 | 45.33 | 143.65 | 21.84 | 153.33 | 0.17 |
December | 211.17 | 0.86 | 0.64 | 14-DEC-14:20 | 248.50 | 23.18 | 109.67 | 24.17 | 114.76 | 20.60 | 92.83 | 0.00 |
Annual Sum or Average | 3472.67 | 0.76 | 446.07 | 23.73 | 2434.50 | 1449.67 | 360.78 | 23.83 | 2745.83 | 746.50 | ||
Minimum of Months | 199.50 | 0.72 | 0.61 | 248.50 | 22.46 | 109.67 | 24.17 | 114.76 | 20.60 | 92.83 | 0.00 | |
Maximum of Months | 389.17 | 0.86 | 0.64 | 633.80 | 26.18 | 279.33 | 223.67 | 577.10 | 26.22 | 321.33 | 125.50 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.815002E+10 | 29007.56 | 02-JAN-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.795343E+10 | 29007.56 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.553339E+10 | 29007.56 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.230797E+10 | 29007.56 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.281772E+09 | 29007.56 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185707E+09 | 29007.56 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.351477E+10 | 29007.56 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.628904E+10 | 29007.56 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.815002E+10 | 29007.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.304129E+11 | 88947.31 | 01-JAN-00:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281854E+11 | 88947.31 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135746E+11 | 88947.31 | 10-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.309112E+10 | 61302.32 | 02-APR-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.953823E+10 | 88947.31 | 21-NOV-01:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224199E+11 | 88947.31 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.304129E+11 | 88947.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108189E+12 | 156119.59 | 01-JAN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102603E+12 | 182161.15 | 06-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261529E+11 | 94969.93 | 22-MAR-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116295E+10 | 27434.95 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.217489E+11 | 103339.37 | 23-NOV-01:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.675215E+11 | 157290.96 | 31-DEC-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327379E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108189E+12 | 182161.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 71958689.29 | 65056619.83 | 3249.54 | 07-APR-14:40 | 3207.43 | 0.00 |
May | 0.00 | 0.00 | 0.746074E+09 | 0.655543E+09 | 15721.06 | 31-MAY-05:03 | 9964.94 | 0.00 |
June | 0.00 | 0.00 | 0.692930E+10 | 0.504477E+10 | 26743.86 | 19-JUN-05:01 | 12741.04 | 0.00 |
July | 0.00 | 0.00 | 0.109233E+11 | 0.760253E+10 | 27866.50 | 20-JUL-05:01 | 11109.06 | 0.00 |
August | 0.00 | 0.00 | 0.110652E+11 | 0.834419E+10 | 27776.34 | 04-AUG-05:01 | 11472.23 | 0.00 |
September | 0.00 | 0.00 | 0.515543E+10 | 0.390661E+10 | 26597.92 | 14-SEP-05:01 | 11085.89 | 0.00 |
October | 0.00 | 0.00 | 0.903539E+09 | 0.630004E+09 | 23707.72 | 06-OCT-05:45 | 11992.12 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.357948E+11 | 0.262487E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.110652E+11 | 0.834419E+10 | 27866.50 | 12741.04 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.513494E+09 | 0.399203E+09 | 15087.83 | 31-MAY-14:00 | 10302.47 | 0.00 |
June | 0.00 | 0.00 | 0.715714E+10 | 0.486142E+10 | 80781.56 | 25-JUN-08:15 | 32984.09 | 0.00 |
July | 0.00 | 0.00 | 0.215932E+11 | 0.135570E+11 | 80366.06 | 30-JUL-08:55 | 35017.72 | 0.00 |
August | 0.00 | 0.00 | 0.224278E+11 | 0.154525E+11 | 77121.54 | 27-AUG-09:15 | 38257.27 | 0.00 |
September | 0.00 | 0.00 | 0.477753E+10 | 0.337198E+10 | 70490.39 | 04-SEP-08:35 | 45957.69 | 0.00 |
October | 0.00 | 0.00 | 234.85 | 153.72 | 0.39 | 04-OCT-13:00 | 0.26 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.564692E+11 | 0.376421E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.224278E+11 | 0.154525E+11 | 80781.56 | 45957.69 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.100747E+10 | 0.06 | 468.83 | 01-JAN-00:01 | 0.08 |
February | 0.933208E+09 | 0.06 | 468.83 | 01-FEB-00:03 | 0.08 |
March | 0.464494E+09 | 0.03 | 468.83 | 01-MAR-00:03 | 0.08 |
April | 48524017.71 | 0.00 | 468.83 | 01-APR-03:30 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.354811E+09 | 0.02 | 468.83 | 18-NOV-00:50 | 0.08 |
December | 0.100222E+10 | 0.06 | 468.83 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.381073E+10 | 0.02 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100747E+10 | 0.06 | 468.83 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.718537E+09 | 0.41 | 1211.42 | 02-JAN-02:62 | 0.91 |
February | 0.673174E+09 | 0.41 | 1211.42 | 01-FEB-06:01 | 0.91 |
March | 0.674285E+09 | 0.31 | 1211.42 | 01-MAR-06:01 | 0.91 |
April | 0.546197E+09 | 0.25 | 1211.42 | 01-APR-05:01 | 0.91 |
May | 0.508245E+09 | 0.22 | 1211.42 | 01-MAY-05:01 | 0.90 |
June | 0.515286E+09 | 0.22 | 1211.42 | 08-JUN-05:02 | 0.90 |
July | 0.527173E+09 | 0.22 | 1211.42 | 01-JUL-05:02 | 0.89 |
August | 0.579326E+09 | 0.24 | 1211.42 | 01-AUG-05:01 | 0.89 |
September | 0.492192E+09 | 0.22 | 1211.42 | 01-SEP-05:01 | 0.89 |
October | 0.485428E+09 | 0.21 | 1211.42 | 28-OCT-05:01 | 0.91 |
November | 0.560891E+09 | 0.27 | 1211.42 | 01-NOV-05:01 | 0.91 |
December | 0.655834E+09 | 0.31 | 1211.42 | 01-DEC-06:01 | 0.91 |
Annual Sum or Average | 0.693657E+10 | 0.27 | |||
Minimum of Months | 0.485428E+09 | 0.21 | 1211.42 | 0.89 | |
Maximum of Months | 0.718537E+09 | 0.41 | 1211.42 | 0.91 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.190025E+10 | 0.58 | 2730.73 | 01-JAN-00:04 | 0.88 |
February | 0.174636E+10 | 0.57 | 2730.73 | 01-FEB-00:03 | 0.88 |
March | 0.154175E+10 | 0.48 | 2730.73 | 10-MAR-06:01 | 0.88 |
April | 0.116875E+10 | 0.29 | 1882.01 | 02-APR-05:33 | 0.88 |
May | 0.112462E+10 | 0.20 | 1092.29 | 30-MAY-12:30 | 0.53 |
June | 0.115867E+10 | 0.22 | 2730.73 | 19-JUN-17:08 | 0.87 |
July | 0.121381E+10 | 0.25 | 2730.73 | 09-JUL-10:43 | 0.86 |
August | 0.129141E+10 | 0.26 | 2730.73 | 02-AUG-17:08 | 0.86 |
September | 0.110524E+10 | 0.21 | 1828.72 | 07-SEP-17:10 | 0.71 |
October | 0.108137E+10 | 0.20 | 1092.29 | 04-OCT-13:00 | 0.53 |
November | 0.130328E+10 | 0.39 | 2730.73 | 21-NOV-01:23 | 0.88 |
December | 0.168666E+10 | 0.54 | 2730.73 | 01-DEC-06:01 | 0.88 |
Annual Sum or Average | 0.163222E+11 | 0.35 | |||
Minimum of Months | 0.108137E+10 | 0.20 | 1092.29 | 0.53 | |
Maximum of Months | 0.190025E+10 | 0.58 | 2730.73 | 0.88 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.718537E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.673174E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.674285E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.564464E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.689580E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.212917E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.303709E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.316013E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.168136E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.699864E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.560891E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.655834E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.152444E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.560891E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.316013E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.190025E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.174636E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.154175E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.116875E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.125743E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.293032E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.642593E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.676515E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.226551E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.108137E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.130328E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.168666E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.300728E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.108137E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.676515E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.718537E+09 | 0.00 | 0.815002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.673174E+09 | 0.00 | 0.795343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.674285E+09 | 0.00 | 0.553339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.546197E+09 | 71958689.29 | 0.230797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.508245E+09 | 0.746074E+09 | 0.281772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.515286E+09 | 0.689765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.527173E+09 | 0.109152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.579326E+09 | 0.110232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.492192E+09 | 0.513900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.485428E+09 | 0.901121E+09 | 0.185707E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.560891E+09 | 0.00 | 0.351477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.655834E+09 | 0.00 | 0.628904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.693657E+10 | 0.356942E+11 | 0.342161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.485428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.718537E+09 | 0.110232E+11 | 0.815002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.190025E+10 | 0.00 | 0.304129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174636E+10 | 0.00 | 0.281854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154175E+10 | 0.00 | 0.135746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116875E+10 | 0.00 | 0.309112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112462E+10 | 0.513494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115867E+10 | 0.709112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121381E+10 | 0.215066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129141E+10 | 0.222186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110524E+10 | 0.463955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108137E+10 | 234.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130328E+10 | 0.00 | 0.953823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168666E+10 | 0.00 | 0.224199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163222E+11 | 0.559694E+11 | 0.107222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.190025E+10 | 0.222186E+11 | 0.304129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.718537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.673174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.674285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.546197E+09 | 0.00 | 0.00 | 0.00 | 18267440.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.508245E+09 | 0.00 | 0.00 | 0.00 | 0.181335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.515286E+09 | 0.00 | 0.00 | 0.00 | 0.161388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.527173E+09 | 0.00 | 0.00 | 0.00 | 0.250992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.579326E+09 | 0.00 | 0.00 | 0.00 | 0.258081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.492192E+09 | 0.00 | 0.00 | 0.00 | 0.118917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.485428E+09 | 0.00 | 0.00 | 0.00 | 0.214436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.560891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.655834E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.693657E+10 | 0.00 | 0.00 | 0.00 | 0.830781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.485428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.718537E+09 | 0.00 | 0.00 | 0.00 | 0.258081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.190025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112462E+10 | 0.00 | 0.00 | 0.00 | 0.132805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115867E+10 | 0.00 | 0.00 | 0.00 | 0.177165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121381E+10 | 0.00 | 0.00 | 0.00 | 0.521212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129141E+10 | 0.00 | 0.00 | 0.00 | 0.547373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110524E+10 | 0.00 | 0.00 | 0.00 | 0.116027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108137E+10 | 0.00 | 0.00 | 0.00 | 61.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163222E+11 | 0.00 | 0.00 | 0.00 | 0.137506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.190025E+10 | 0.00 | 0.00 | 0.00 | 0.547373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226597E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221539E+10 | 0.00 | 0.00 | 0.13 |
March | 0.146976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178937E+10 | 0.00 | 0.00 | 0.13 |
April | 0.460248E+09 | 1290473.29 | 0.00 | 118251.30 | 0.00 | 0.760450E+09 | 0.116737E+09 | 0.00 | 0.15 |
May | 0.401562E+09 | 41831171.88 | 0.00 | 1488557.77 | 0.00 | 44520801.63 | 0.111843E+10 | 0.00 | 0.29 |
June | 359238.90 | 0.656399E+09 | 0.00 | 3703020.20 | 0.00 | 0.00 | 0.669838E+09 | 0.00 | 0.32 |
July | 0.00 | 0.161493E+10 | 0.00 | 4669123.21 | 0.00 | 0.00 | 17929400.98 | 0.00 | 0.14 |
August | 34601.48 | 0.135305E+10 | 0.00 | 4545532.64 | 0.00 | 0.00 | 0.186057E+09 | 0.00 | 0.21 |
September | 11725242.51 | 0.395140E+09 | 0.00 | 5222933.17 | 0.00 | 0.00 | 0.137385E+10 | 0.00 | 0.39 |
October | 0.433592E+09 | 30733475.16 | 0.00 | 1900933.97 | 0.00 | 26350779.79 | 0.127131E+10 | 0.00 | 0.31 |
November | 0.339069E+09 | 0.00 | 0.00 | 6596.94 | 0.00 | 0.120727E+10 | 12038586.02 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212401E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.179357E+10 | 0.409337E+10 | 0.00 | 21654949.20 | 0.00 | 0.104333E+11 | 0.476619E+10 | 0.00 | 0.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.460248E+09 | 0.161493E+10 | 0.00 | 5222933.17 | 0.00 | 0.226597E+10 | 0.137385E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.181221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447458E+10 | 0.00 | 0.00 | 0.17 |
February | 0.179010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452748E+10 | 0.00 | 0.00 | 0.18 |
March | 0.343177E+10 | 0.00 | 0.00 | 0.00 | 9707944.56 | 0.156423E+10 | 0.00 | 0.00 | 0.19 |
April | 0.293445E+10 | 0.00 | 0.00 | 0.00 | 19313550.41 | 0.264294E+09 | 0.00 | 0.00 | 0.18 |
May | 0.276605E+10 | 29671339.41 | 0.00 | 112414.78 | 871406.29 | 0.00 | 31151726.29 | 0.00 | 0.19 |
June | 0.856060E+09 | 0.684465E+09 | 0.00 | 3836827.52 | 2125480.86 | 0.00 | 0.211586E+10 | 0.00 | 0.31 |
July | 13630858.75 | 0.312403E+10 | 0.00 | 2099243.85 | 0.00 | 0.00 | 0.621111E+09 | 0.00 | 0.24 |
August | 72003245.41 | 0.324176E+10 | 0.00 | 6568715.55 | 0.00 | 0.00 | 0.114215E+10 | 0.00 | 0.30 |
September | 0.177466E+10 | 0.364578E+09 | 0.00 | 3412579.48 | 0.00 | 0.00 | 0.163346E+10 | 0.00 | 0.27 |
October | 0.330902E+10 | 0.00 | 0.00 | 38406.47 | 0.00 | 0.00 | 63951842.33 | 0.00 | 0.18 |
November | 0.291116E+10 | 0.00 | 0.00 | 0.00 | 8543.36 | 0.102743E+10 | 0.00 | 0.00 | 0.17 |
December | 0.230834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335300E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.239795E+11 | 0.744451E+10 | 0.00 | 16068187.66 | 32026925.48 | 0.152110E+11 | 0.560768E+10 | 0.00 | 0.21 |
Minimum of Months | 13630858.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.343177E+10 | 0.324176E+10 | 0.00 | 6568715.55 | 19313550.41 | 0.452748E+10 | 0.211586E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.243680E+12 | 0.980162E+11 | 0.00 | 0.855276E+10 | 0.443815E+11 |
February | 0.421769E+12 | 0.944286E+11 | 0.00 | 0.853297E+10 | 0.418360E+11 |
March | 0.752632E+12 | 0.600123E+11 | 0.00 | 0.698867E+10 | 0.154937E+11 |
April | 0.824673E+12 | 0.357220E+11 | 0.00 | 0.452957E+10 | 0.300780E+10 |
May | 0.110294E+13 | 0.318832E+11 | 0.00 | 0.431988E+10 | 0.170816E+10 |
June | 0.110409E+13 | 0.399716E+11 | 0.00 | 0.233808E+10 | 0.174720E+11 |
July | 0.109510E+13 | 0.382115E+11 | 0.00 | -0.402617E+10 | 0.402386E+11 |
August | 0.107014E+13 | 0.427508E+11 | 0.00 | -0.301688E+10 | 0.415476E+11 |
September | 0.741634E+12 | 0.380343E+11 | 0.00 | 0.408013E+10 | 0.122824E+11 |
October | 0.674912E+12 | 0.463592E+11 | 0.00 | 0.507543E+10 | 0.121046E+10 |
November | 0.291706E+12 | 0.541439E+11 | 0.00 | 0.549696E+10 | 0.115785E+11 |
December | 0.180116E+12 | 0.746680E+11 | 0.00 | 0.778535E+10 | 0.301853E+11 |
Annual Sum or Average | 0.850338E+13 | 0.654202E+12 | 0.00 | 0.506567E+11 | 0.260942E+12 |
Minimum of Months | 0.180116E+12 | 0.318832E+11 | 0.00 | -0.402617E+10 | 0.121046E+10 |