Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 10:41:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1436.01 | 296.99 | 296.99 |
Net Site Energy | 1436.01 | 296.99 | 296.99 |
Total Source Energy | 2551.52 | 527.70 | 527.70 |
Net Source Energy | 2551.52 | 527.70 | 527.70 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 958.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 30.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 477.62 | 958.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 958.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 5.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 185.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 29.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 958.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 5.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 185.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 92.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 30.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 26.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 57.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 12.94 | 198.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 98.78 | 198.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 57.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 12.94 | 198.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 98.78 | 198.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 477.623 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 477.623 | 100.00 |
Total On-Site and Utility Electric Sources | 477.623 | 100.00 |
Total Electricity End Uses | 477.623 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 83.33 |
Time Setpoint Not Met During Occupied Cooling | 1.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2983.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.8432 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.2431 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.6162 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.6162 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.8432 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 10.2257 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.2431 | 46.45 | 2.5587 | |
Total | 4835.13 | 7.6162 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 7.6162 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 7.6162 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-14:09 | 05-JAN-17:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 318529.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8260.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 13092.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3942.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1772.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 37104.34 | 318529.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 318529.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 8260.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 13092.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1637.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1772.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1038.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 17.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 588.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 293.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 96.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 84.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1512.63 | 1038.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 214.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 121.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 312.84 | 214.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 214.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 121.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 312.84 | 214.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.17 |
ZONE2 FINE STORAGE DIRECT AIR | 2.36 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 4.80 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 4.80 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 171838.60 |
PSZ-OFFICE HEATING COIL | 28752.89 |
PSZ-FINE STORAGE HEATING COIL | 80351.64 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 171838.60 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.00 | 1.000000 | 1.17 |
PSZ-FINE STORAGE | 2.36 | 2.36 | 2.36 | 2.36 | 2.36 | 2.36 | 1.00 | 1.00 | 2.36 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.17 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.36 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.17 | 1296.68 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.36 | 2521.30 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.17 | 1.17 | 1.17 | 0.772980 | 19387.23 | 28752.89 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.36 | 2.36 | 2.36 | 1.56 | 45995.68 | 80351.64 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.17 | 0.585591 | 0.780787 | 19387.23 | 9693.61 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 2.36 | 1.18 | 1.57 | 45995.68 | 22997.84 | 0.785770 | 0.785770 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.843 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.917 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 10.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.226 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.243 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.802 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2568.536 | 10.843 | 201.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2568.536 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 14248.589 | 10.226 | 474.953 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 14248.589 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 20008.023 | 6.243 | 289.971 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20008.023 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1804 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3574 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.3694 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.544 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.798 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.608 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.60435670E-09 | 0.47630797E-14 | 0.24204839E-14 | 0.0000000 |
2 | 1 | -5.2160796 | 0.57881174E-04 | -0.88809346E-04 | 0.11586416E-09 |
3 | 0 | 5.3964676 | 0.18033005 | 0.18047674 | |
4 | 2 | 0.92894805E-09 | 0.33911764E-13 | 0.21779261E-14 | 0.0000000 |
5 | 1 | -5.2160150 | 0.41827095E-04 | -0.44821328E-04 | 0.18401191E-09 |
6 | 0 | 5.5734381 | 0.35738136 | 0.35746801 | |
7 | 4 | 0.80462617E-12 | 0.82840410E-16 | -0.20078756E-14 | 0.11271485E-15 |
8 | 3 | -0.39242815E-03 | 0.26180773E-06 | -0.56999769E-04 | 0.15438257E-12 |
9 | 2 | 1.7577325 | 0.56772723E-02 | 1.1542901 | -0.75235290E-04 |
10 | 1 | -7.1048256 | 0.14632850 | -17.186369 | 0.33689683 |
11 | 0 | 5.5924660 | 0.92974441E-01 | 16.277116 | |
12 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
13 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
14 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
15 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
16 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.25659737E-14 | 0.20825084E-15 | 0.74747876E-12 | 0.12362927E-15 |
85 | 3 | -0.54038165E-04 | 0.45238042E-06 | -0.37328678E-03 | 0.14344535E-12 |
86 | 2 | 1.1198054 | 0.10013958E-01 | 1.7123825 | -0.71564441E-04 |
87 | 1 | -16.966117 | 0.26145347 | -7.1648294 | 0.32817431 |
88 | 0 | 16.285382 | 0.16754891 | 5.8918369 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.419_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.419_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.419_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.419_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_0.5_SHGC_0.4 | 38 | 1 | VerySmooth | 2.843 | 2.843 | 1.000 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 39 | 1 | VerySmooth | 4.827 | 4.827 | 1.000 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 0.13907 | 0.13907 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 5.00274E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.614 | 0.549 | 0.552 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0725E-004 |
2 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7648E-004 |
3 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6840E-004 |
4 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2079E-004 |
5 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8676E-004 |
6 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9231E-004 |
7 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4175E-004 |
8 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4320E-003 |
9 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0968E-003 |
10 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2843E-004 |
11 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5877E-003 |
12 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4692E-003 |
13 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1835E-004 |
14 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3213E-004 |
15 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6812E-004 |
16 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4320E-003 |
17 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2100E-004 |
18 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9407E-004 |
19 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1829E-004 |
20 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2079E-004 |
21 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3708E-004 |
22 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1225E-004 |
23 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4956E-004 |
24 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2079E-004 |
25 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1063E-004 |
26 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4978E-004 |
27 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3135E-003 |
28 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4320E-003 |
29 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0134E-003 |
30 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9943E-003 |
31 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9675E-003 |
32 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4692E-003 |
33 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0330E-003 |
34 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0112E-003 |
35 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5570E-003 |
36 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4320E-003 |
37 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9596E-004 |
38 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7922E-004 |
39 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2357E-004 |
40 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2079E-004 |
41 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.9961E-003 |
42 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 7.2556E-004 |
43 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.3190E-003 |
44 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.4622E-004 |
45 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.1378E-003 |
46 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.1793E-004 |
47 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.1458E-003 |
48 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.5232E-004 |
49 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.4087E-004 |
50 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.8724E-003 |
51 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.7962E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.7462E-003 |
53 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.3084E-004 |
54 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.5670E-003 |
55 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.4603E-004 |
56 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.2309E-003 |
57 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 6.0189E-003 |
58 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 4.3438E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.5681E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.4286E-004 |
61 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.1620E-003 |
62 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.5582E-004 |
63 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.9456E-003 |
64 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.3643E-004 |
65 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.4015E-003 |
66 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.3573E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.7596E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.4358E-004 |
69 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.8014E-003 |
70 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.5505E-004 |
71 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.9455E-003 |
72 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.3643E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10375.42371 | 12450.50845 | 0.97599 | 1.17118 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.16000 | 6.30335E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 11320.90898 | 13585.09077 | 0.36347 | 0.43616 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60000 | 3.41898E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 26779.11476 | 32134.93772 | 1.96354 | 2.35625 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.08000 | 6.30633E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 36032.57950 | 43239.09540 | 0.97409 | 1.16890 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -27.60000 | 3.41898E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 143198.83664 | 171838.60397 | 4.00028 | 4.80033 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15559.37 | 1.17118 | 1.17118 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 14012.83 | 0.43616 | 0.43616 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 39580.16 | 2.35625 | 2.35625 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 49635.15 | 1.16890 | 1.16890 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.17118 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.35625 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.80033 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 4.80033 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 171838.59613 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 171838.60397 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.17118 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.17118 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.17118 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.17118 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.17118 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.17118 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.35625 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.35625 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.35625 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.35625 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.35625 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.35625 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.17118 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.35625 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.17118 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.17118 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1296.68479 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.17118 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.17118 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.17118 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77298 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.17118 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58559 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.78079 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19387.23000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9693.61500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19387.23000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28752.88630 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28752.88630 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.35625 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.35625 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2521.30120 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.35625 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.35625 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.35625 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.55513 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.35625 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.17813 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.57083 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 45995.68000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22997.84000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78577 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78577 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 45995.68000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 80351.64155 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 80351.64155 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 18478.4 | 11.40 | 11.14 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 44166.2 | 11.60 | 11.34 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1949830015 | 0.1882099940 | Pass | Pass | 1.4506381735 | 5.9671100373 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4193321873 | 0.4085589242 | Pass | Pass | 0.7880500474 | 2.5782427198 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.3263911630E-003 | 8.2061557326E-003 | Pass | Pass | 7.7541131982E-002 | 0.1990948530 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8313.70 | 710.99 | 0.00 | 74.58 | 251.80 | 9351.11 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.176 | 0.180 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.341 | 0.357 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.565 | 0.653 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.565 | 0.653 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.419_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.381 | 0.401 | 0.442 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.419_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.381 | 0.401 | 0.442 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.419_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.381 | 0.401 | 0.442 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.419_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.381 | 0.401 | 0.442 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.499 | 0.469 | 0.492 | |||||||||||||||||
North Total or Average | 6.51 | 2.381 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.778 | 0.486 | 0.504 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.8432 | 236.88 | 2568.54 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 44.00 | 0.0000 | Y | 21.22 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 10.2257 | 1393.41 | 14248.59 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 26.54 | 0.0000 | Y | 71.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.2431 | 3204.84 | 20008.02 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 24.96 | 0.0000 | Y | 93.76 |
Interior Lighting Total | 7.6162 | 4835.13 | 36825.15 | 185.97 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.12 | 20008.02 | 2320.93 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.29 | 2568.54 | 744.88 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.10 | 2568.54 | 256.85 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 125.92 | AstronomicalClock | - | 42.11 | 42.11 | 1.00 | |
EXTERIOR_LIGHTS_B | 6860.50 | AstronomicalClock | - | 83.57 | 71.13 | 91.60 | |
Exterior Lighting Total | 6986.42 | 92.60 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19387.23 | 15522.58 | 3864.65 | 0.80 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 45995.68 | 36142.03 | 9853.65 | 0.79 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 18478.4 | 11.40 | 11.14 | ||||
PSZ-FINE STORAGE COOLING COIL | 44166.2 | 11.60 | 11.34 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 171838.60 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28752.89 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 80351.64 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 4.80 | 446.00 | 92.91 | 1.00 | 3.17 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.17 | 1296.68 | 1107.16 | 1.00 | 1.37 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.36 | 2521.30 | 1070.05 | 1.00 | 1.29 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10375.42 | 12450.51 | 52.56 | 0.976 | 1.171 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00821 | 31.16 | 0.00630 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 26779.11 | 32134.94 | 23.06 | 1.964 | 2.356 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 26.70 | 26.70 | 0.00811 | 33.08 | 0.00631 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 33.38 | 0.00639 | 33.24 | 0.00631 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11320.91 | 13585.09 | 57.35 | 0.363 | 0.436 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00773 | -27.60 | 0.00034 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 36032.58 | 43239.10 | 31.03 | 0.974 | 1.169 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00651 | -27.60 | 0.00034 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 143198.84 | 171838.60 | 53.62 | 4.000 | 4.800 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00584 | -27.60 | 0.00034 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.17 | 1.17 | 0.44 | 0.44 | 1.1712 | 1.1712 | 1.1712 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.36 | 2.36 | 1.17 | 1.17 | 2.3563 | 2.3563 | 2.3563 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 171838.596 | 171838.596 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 171838.60 | 171838.60 | 4.800334 | 10.00 | 6.95 | 0.00583935 | 43.33 | 20.56 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 10.00 | 0.00583935 | 67.1291 | 171838.60 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 19387.230 | 15522.580 | 1.171180 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 9693.61 | 9637.27 | 0.780787 | 25.60 | 15.18 | 0.00803953 | 12.00 | 10.08 | 0.00800000 | 31.59 | 0.00630401 | 15.77 | 13.1002 | 23.90 | 0.00820587 | 38.8856 | 10360.84 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28752.886 | 28752.886 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28752.89 | 28752.89 | 1.171182 | 16.80 | 11.12 | 0.00708520 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 8.7335 | 21.10 | 0.00773048 | 43.4617 | 11320.91 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 45995.680 | 36142.025 | 2.356250 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 22997.84 | 22997.84 | 1.570833 | 28.91 | 16.08 | 0.00778703 | 12.00 | 9.87 | 0.00778703 | 33.40 | 0.00630683 | 16.37 | 27.0373 | 26.70 | 0.00811342 | 32.5530 | 26716.86 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 80351.642 | 80351.642 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 80351.64 | 80351.64 | 2.356252 | 7.78 | 5.41 | 0.00539804 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 18.0249 | 15.55 | 0.00650980 | 51.9308 | 36032.58 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 171838.596 | 171838.596 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 4.800334 | 5.05542284 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 171838.60 | 171838.60 | 1.0000 | 5.05542284 | 4.800334 | 10.00 | 6.95 | 0.00583935 | 24756.9 | 43.33 | 20.56 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 171838.60 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 10.00 | 0.00583935 | 10.00 | 0.00583935 | 67.1291 | 171838.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19387.230 | 15522.580 | 1.171180 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7851 | 1004.8586 | 1.0531 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.171182 | 1.23341885 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 9693.61 | 9637.27 | 1.0000 | 0.82227758 | 0.780787 | 25.60 | 15.18 | 0.00803953 | 46215.3 | 12.00 | 10.08 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9693.61 | 31.59 | 0.00630401 | 15.77 | 0.10228463 | 13.1002 | 23.90 | 0.00820587 | 23.90 | 0.00820587 | 38.8856 | 10360.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28752.886 | 28752.886 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.171182 | 1.23341885 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 28752.89 | 28752.89 | 1.0000 | 1.23341885 | 1.171182 | 16.80 | 11.12 | 0.00708520 | 34823.5 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28752.89 | -27.60 | 0.00034190 | -27.60 | 0.10228463 | 8.7335 | 21.05 | 0.00773048 | 21.10 | 0.00773048 | 43.4617 | 11320.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 45995.680 | 36142.025 | 2.356250 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3157 | 1004.8586 | 1.0531 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.356252 | 2.48146313 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 22997.84 | 22997.84 | 1.0000 | 1.65430723 | 1.570833 | 28.91 | 16.08 | 0.00778703 | 48940.3 | 12.00 | 9.87 | 0.00778703 | 31706.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22997.84 | 33.40 | 0.00630683 | 16.37 | 0.42471127 | 27.0373 | 26.70 | 0.00811342 | 26.70 | 0.00811342 | 32.5530 | 26716.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 80351.642 | 80351.642 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.356252 | 2.48146313 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 80351.64 | 80351.64 | 1.0000 | 2.48146313 | 2.356252 | 7.78 | 5.41 | 0.00539804 | 21391.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 80351.64 | -27.60 | 0.00034190 | -27.60 | 0.42471127 | 18.0249 | 15.55 | 0.00650980 | 15.55 | 0.00650980 | 51.9308 | 36032.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.17 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.36 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2550.00 | 3073.67 | 2283.33 |
ZONE2 FINE STORAGE | 3130.67 | 3038.83 | 2602.83 |
ZONE3 BULK STORAGE | 3266.50 | 3286.00 | 2976.83 |
Facility | 3324.67 | 3358.00 | 2983.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 149.17 | 1.00 | 69.17 | 1.00 |
ZONE2 FINE STORAGE | 528.33 | 4.17 | 28.33 | 0.00 |
ZONE3 BULK STORAGE | 2.00 | 0.00 | 2.00 | 0.00 |
Facility | 637.17 | 5.17 | 83.33 | 1.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.486 | 0.352 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.458 | 0.325 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.199 | 0.000 | 0.161 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.47 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.29 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.03 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1759519.23 | 0.00 | 1759519.23 | 2217108.45 | 3976627.68 | 3225648.14 | 5701.10 | 2561.25 | 497.65 | 0.00 |
ZONE2 FINE STORAGE | 4909887.01 | 0.00 | 4909887.01 | 8997871.09 | 13907758.10 | 13393694.68 | 5729.06 | 2894.39 | 136.56 | 0.94 |
ZONE3 BULK STORAGE | 0.00 | 36735256.43 | 36735256.43 | 51863308.99 | 88598565.42 | 30805497.77 | 6763.55 | 86.67 | 1909.78 | 5019.00 |
Total Facility | 6669406.24 | 36735256.43 | 43404662.67 | 63078288.53 | 0.11E+09 | 47424840.58 | 7764.66 | 3035.67 | 2398.06 | 5019.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1344 | 0.0000 | 0.1344 | 0.0976 | 0.2320 | 0.1023 | 577.10 | 2561.25 | 497.65 |
ZONE2 FINE STORAGE | 0.3748 | 0.0000 | 0.3748 | 0.2666 | 0.6414 | 0.4247 | 606.00 | 2894.39 | 135.61 |
ZONE3 BULK STORAGE | 0.0000 | 1.5526 | 1.5526 | 1.9741 | 3.5267 | 0.9768 | 2540.99 | 40.33 | 1054.67 |
Total Facility | 0.5092 | 1.5526 | 2.0619 | 2.3383 | 4.4001 | 1.5038 | 2640.66 | 2989.33 | 1542.15 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1951429.73 | 0.00 | 1951429.73 | 3225648.14 | 5699.94 | 0.50 | 3059.56 | 0.00 |
PSZ-FINE STORAGE | 5445544.23 | 0.00 | 5445544.23 | 13393694.68 | 5729.06 | 0.00 | 3030.94 | 0.94 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1491 | 0.0000 | 0.1491 | 0.1023 | 575.94 | 0.50 | 3059.56 |
PSZ-FINE STORAGE | 0.4157 | 0.0000 | 0.4157 | 0.4247 | 606.00 | 0.00 | 3030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2863.57 | 202.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2989.44 | 41.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1648 | 0.3478 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.4943 | 0.8411 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 389 |
Defaulted Fields | 319 |
Fields with Defaults | 1046 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 477.62 | 2572.41 | 26-MAR-14:20 | 37104.34 | 17-JUL-14:10 |
Electricity:Building | 323.46 | 2091.41 | 05-MAR-13:20 | 25925.70 | 25-JUL-10:30 |
Electricity:Zone:ZONE1 OFFICE | 50.38 | 694.23 | 05-MAR-13:20 | 3408.44 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 322.48 | 2091.41 | 05-MAR-13:20 | 24347.90 | 02-JAN-09:10 |
InteriorLights:Electricity | 185.97 | 1621.54 | 05-MAR-13:20 | 14312.73 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 21.22 | 224.35 | 05-MAR-13:20 | 1573.38 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 185.97 | 1621.54 | 05-MAR-13:20 | 14312.73 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 185.97 | 1621.54 | 05-MAR-13:20 | 14312.73 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 21.22 | 224.35 | 05-MAR-13:20 | 1573.38 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 185.97 | 1621.54 | 05-MAR-13:20 | 14312.73 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 71.00 | 623.38 | 01-JAN-00:10 | 5298.77 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 71.00 | 623.38 | 01-JAN-00:10 | 5298.77 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 71.00 | 623.38 | 01-JAN-00:10 | 5298.77 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 202.08 | 773.81 | 08-JAN-10:50 | 17370.59 | 25-JUL-10:30 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 93.76 | 773.81 | 08-JAN-10:50 | 7440.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 93.76 | 773.81 | 08-JAN-10:50 | 7440.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 30.32 | 0.00 | 01-JAN-12:40 | 4223.01 | 17-JUL-16:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.98 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-JUL-13:20 |
Ventilation (simple):Fans:Electricity | 0.98 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-JUL-13:20 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.98 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-JUL-13:20 |
ElectricityPurchased:Facility | 477.62 | 2572.41 | 26-MAR-14:20 | 37104.34 | 17-JUL-14:10 |
ElectricityPurchased:Plant | 477.62 | 2572.41 | 26-MAR-14:20 | 37104.34 | 17-JUL-14:10 |
Cogeneration:ElectricityPurchased | 477.62 | 2572.41 | 26-MAR-14:20 | 37104.34 | 17-JUL-14:10 |
General:Cogeneration:ElectricityPurchased | 477.62 | 2572.41 | 26-MAR-14:20 | 37104.34 | 17-JUL-14:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 477.62 | 2572.41 | 26-MAR-14:20 | 37104.34 | 17-JUL-14:10 |
ElectricityNet:Plant | 477.62 | 2572.41 | 26-MAR-14:20 | 37104.34 | 17-JUL-14:10 |
Cogeneration:ElectricityNet | 477.62 | 2572.41 | 26-MAR-14:20 | 37104.34 | 17-JUL-14:10 |
General:Cogeneration:ElectricityNet | 477.62 | 2572.41 | 26-MAR-14:20 | 37104.34 | 17-JUL-14:10 |
Electricity:HVAC | 34.92 | 0.00 | 01-JAN-12:40 | 11732.11 | 17-JUL-16:00 |
General:Fans:Electricity | 29.34 | 0.00 | 01-JAN-12:40 | 3637.51 | 05-JAN-17:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 5.58 | 0.00 | 01-JAN-00:10 | 9814.39 | 17-JUL-16:00 |
General:Cooling:Electricity | 5.58 | 0.00 | 01-JAN-00:10 | 9814.39 | 17-JUL-16:00 |
ExteriorLights:Electricity | 92.60 | 0.00 | 01-JAN-08:20 | 6986.42 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.60 | 0.00 | 01-JAN-08:20 | 6986.42 | 01-JAN-06:10 |
Electricity:Plant | 26.64 | 481.00 | 05-JAN-20:00 | 2852.03 | 17-FEB-12:50 |
WaterSystems:Electricity | 26.64 | 481.00 | 05-JAN-20:00 | 2852.03 | 17-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 26.64 | 481.00 | 05-JAN-20:00 | 2852.03 | 17-FEB-12:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 958.38 | 0.00 | 01-JAN-12:40 | 318529.19 | 05-JAN-17:10 |
NaturalGas:HVAC | 958.38 | 0.00 | 01-JAN-12:40 | 318529.19 | 05-JAN-17:10 |
Heating:NaturalGas | 958.38 | 0.00 | 01-JAN-12:40 | 318529.19 | 05-JAN-17:10 |
General:Heating:NaturalGas | 958.38 | 0.00 | 01-JAN-12:40 | 318529.19 | 05-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1496.60 | 0.00 | 01-JAN-12:40 | 482676.66 | 05-JAN-17:10 |
EnergyTransfer:Building | 741.46 | 0.00 | 01-JAN-12:40 | 232485.61 | 05-JAN-17:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 55.77 | 0.00 | 01-JAN-00:10 | 23653.91 | 09-JAN-07:20 |
Heating:EnergyTransfer | 709.07 | 0.00 | 01-JAN-12:40 | 232485.61 | 05-JAN-17:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 43.15 | 0.00 | 01-JAN-00:10 | 23653.91 | 09-JAN-07:20 |
General:Heating:EnergyTransfer | 709.07 | 0.00 | 01-JAN-12:40 | 232485.61 | 05-JAN-17:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 43.15 | 0.00 | 01-JAN-00:10 | 23653.91 | 09-JAN-07:20 |
Cooling:EnergyTransfer | 32.39 | 0.00 | 01-JAN-00:10 | 25448.07 | 17-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 12.63 | 0.00 | 01-JAN-00:10 | 9325.48 | 17-JUL-16:10 |
General:Cooling:EnergyTransfer | 32.39 | 0.00 | 01-JAN-00:10 | 25448.07 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 12.63 | 0.00 | 01-JAN-00:10 | 9325.48 | 17-JUL-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 159.56 | 0.00 | 01-JAN-00:40 | 49423.30 | 05-JAN-22:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 139.80 | 0.00 | 01-JAN-00:40 | 49423.30 | 05-JAN-22:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 139.80 | 0.00 | 01-JAN-00:40 | 49423.30 | 05-JAN-22:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 19.76 | 0.00 | 01-JAN-00:10 | 16675.88 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 19.76 | 0.00 | 01-JAN-00:10 | 16675.88 | 17-JUL-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 526.13 | 0.00 | 01-JAN-12:40 | 173763.76 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 526.13 | 0.00 | 01-JAN-12:40 | 173763.76 | 05-JAN-16:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 526.13 | 0.00 | 01-JAN-12:40 | 173763.76 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 755.14 | 0.00 | 01-JAN-12:40 | 250191.05 | 05-JAN-17:10 |
HeatingCoils:EnergyTransfer | 733.65 | 0.00 | 01-JAN-12:40 | 250191.05 | 05-JAN-17:10 |
CoolingCoils:EnergyTransfer | 21.49 | 0.00 | 01-JAN-00:10 | 33572.24 | 17-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 43.146 | -12.625 | 0.000 | 0.000 | 10.229 | 21.216 | 29.165 | 11.966 | 0.000 | 0.604 | 0.000 | 0.000 | -10.732 | 0.000 | -31.409 | -61.561 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 139.795 | -19.765 | 0.000 | 0.000 | 27.389 | 70.998 | 0.000 | 0.000 | 0.000 | 1.389 | 0.001 | 0.000 | 0.000 | 0.000 | -104.602 | -115.204 |
ZONE3 BULK STORAGE | 526.125 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 68.794 | 93.757 | 107.344 | 134.691 | 0.000 | 27.649 | 0.000 | 0.000 | -71.574 | 0.000 | -573.599 | -313.186 |
Total Facility | 526.125 | 0.000 | 182.942 | -32.390 | 0.000 | 0.000 | 106.412 | 185.970 | 136.508 | 146.657 | 0.000 | 29.642 | 0.001 | 0.000 | -82.306 | 0.000 | -709.610 | -489.951 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 12-AUG-05:02 | 0.00 | 0.00 | 0.00 | -26177.49 | 0.00 | 0.00 | 85.56 | 469.96 | 550.52 | 0.00 | 0.00 | 0.00 | 25850.63 | 0.00 | -513.00 | 0.00 | -266.19 | 0.00 |
ZONE2 FINE STORAGE | 19-JUL-17:10 | 0.00 | 0.00 | 0.00 | -40127.07 | 0.00 | 0.00 | 0.00 | 623.38 | 0.00 | 0.00 | 0.00 | 1939.85 | 37563.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 19-JUL-17:10 | 0.00 | 0.00 | 0.00 | -40127.07 | 0.00 | 0.00 | 0.00 | 1621.54 | 2519.91 | 31507.51 | 0.00 | 2464.16 | 12571.04 | 0.00 | 0.00 | 0.00 | -10557.09 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 30-JAN-06:12 | 0.00 | 0.00 | 29598.35 | 0.00 | 0.00 | 0.00 | 118.54 | 469.96 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1163.96 | 0.00 | -3801.86 | -25771.56 |
ZONE2 FINE STORAGE | 06-JAN-02:61 | 0.00 | 0.00 | 83981.78 | 0.00 | 0.00 | 0.00 | 0.00 | 623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -12900.51 | -71704.64 |
ZONE3 BULK STORAGE | 05-JAN-16:00 | 173754.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8402.86 | 7440.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 17.52 | 0.00 | -6318.05 | 0.00 | -191497.75 | 0.00 |
Total Facility | 06-JAN-06:41 | 160410.44 | 0.00 | 108916.26 | 0.00 | 0.00 | 0.00 | 1417.56 | 1968.69 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11758.25 | 0.00 | -120434.07 | -143121.18 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1712 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1712 | 0.0873 | 1.0000 | Not calculated | 0.1023 | 0.0873 | ||
PSZ-FINE STORAGE | 2.3563 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.3563 | 0.1802 | 1.0000 | Not calculated | 0.4247 | 0.1802 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1712 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1712 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0873 | ||
PSZ-FINE STORAGE | 2.3563 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.3563 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1802 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1712 | 1.1712 | 1.1712 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.3563 | 2.3563 | 2.3563 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1712 | 1.1712 | 1.1712 | 1.1712 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.3563 | 2.3563 | 2.3563 | 2.3563 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1712 | 1.1712 | 1.1712 | No | 0.1023 | 0.2345 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.3563 | 2.3563 | 2.3563 | No | 0.4247 | 0.3633 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1712 | 1.1712 | 1.1712 | 1.1712 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.3563 | 2.3563 | 2.3563 | 2.3563 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 83.33 |
Number of hours cooling loads not met | 1.00 |
Number of hours not met | 84.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 958.38 | 318529.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 5.58 | 9814.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 185.97 | 14312.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.60 | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.98 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 29.34 | 3637.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.64 | 2852.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 477.62 |
Natural Gas | 0.00 | 958.38 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 1436.01 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 38.46 |
Space Heating | 0.00 |
Space Cooling | 1.15 |
Fans (All) | 6.27 |
Service Water Heating | 5.51 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 98.78 |
Subtotal | 98.78 |
Natural Gas [MJ/m2] | |
Space Heating | 198.21 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 198.21 |
Subtotal | 198.21 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.95 |
Space Heating | 66.74 |
Space Cooling | 0.39 |
Fans (All) | 2.11 |
Service Water Heating | 1.86 |
Receptacle Equipment | 9.51 |
Miscellaneous | 6.45 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8667.83 | 92.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8727.17 | 32.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8315.67 | 443.00 | 1.33 | 0.00 | 0.00 |
Min | 8315.67 | 32.83 | 0.00 | 0.00 | 0.00 |
Max | 8727.17 | 443.00 | 1.33 | 0.00 | 0.00 |
Average | 8570.22 | 189.33 | 0.44 | 0.00 | 0.00 |
Sum | 25710.67 | 568.00 | 1.33 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 82032.00 | 687.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 175654.67 | 15477.67 | 60.67 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 175654.67 | 15477.67 | 60.67 | 0.00 | 0.00 |
Average | 96904.56 | 5388.22 | 20.22 | 0.00 | 0.00 |
Sum | 290713.67 | 16164.67 | 60.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8721.00 | 39.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8691.17 | 68.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8535.33 | 224.67 | 0.00 | 0.00 | 0.00 |
Min | 8535.33 | 39.00 | 0.00 | 0.00 | 0.00 |
Max | 8721.00 | 224.67 | 0.00 | 0.00 | 0.00 |
Average | 8649.17 | 110.83 | 0.00 | 0.00 | 0.00 |
Sum | 25947.50 | 332.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 81495.50 | 1223.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 181946.33 | 9246.67 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 181946.33 | 9246.67 | 0.00 | 0.00 | 0.00 |
Average | 98822.94 | 3490.06 | 0.00 | 0.00 | 0.00 |
Sum | 296468.83 | 10470.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 33027.00 | 0.00 |
Average | 0.00 | 63731.00 | 11009.00 | 0.00 |
Sum | 0.00 | 191193.00 | 33027.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.3 | 0.496860E+09 | 603.25 | 21-JAN-08:09 | -1.1 | -3.7 |
February | 1491030.11 | 311.47 | 28-FEB-16:00 | 11.10 | 4.84 | 0.457400E+09 | 640.63 | 27-FEB-16:10 | 11.10 | 4.84 |
March | 679390.49 | 482.97 | 02-MAR-15:00 | 11.10 | 4.79 | 0.536779E+09 | 603.25 | 11-MAR-08:09 | 6.97 | 2.53 |
April | 17151073.87 | 483.31 | 26-APR-13:00 | 11.10 | 4.73 | 0.501746E+09 | 716.42 | 06-APR-15:00 | 11.10 | 4.73 |
May | 0.200764E+09 | 3175.39 | 19-MAY-16:00 | 27.80 | 14.54 | 0.550985E+09 | 768.98 | 19-MAY-13:00 | 27.80 | 14.54 |
June | 0.196586E+10 | 6598.81 | 29-JUN-15:10 | 32.02 | 14.63 | 0.635125E+09 | 769.01 | 22-JUN-09:09 | 32.02 | 14.63 |
July | 0.445170E+10 | 23163.94 | 27-JUL-05:02 | 13.80 | 9.62 | 0.633573E+09 | 769.04 | 17-JUL-14:20 | 13.80 | 9.62 |
August | 0.401903E+10 | 26177.86 | 12-AUG-05:02 | 13.07 | 6.78 | 0.680104E+09 | 769.01 | 10-AUG-15:20 | 13.07 | 6.78 |
September | 0.172410E+10 | 22264.28 | 05-SEP-05:01 | 18.40 | 11.40 | 0.588810E+09 | 769.03 | 06-SEP-10:00 | 18.90 | 15.66 |
October | 0.219911E+09 | 1899.49 | 18-OCT-16:00 | 24.40 | 11.02 | 0.527302E+09 | 768.96 | 18-OCT-15:39 | 24.40 | 11.02 |
November | 24355218.14 | 793.68 | 09-NOV-15:00 | 9.00 | 3.82 | 0.478482E+09 | 675.66 | 04-NOV-15:09 | 9.00 | 3.82 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -2.1 | -4.2 | 0.497041E+09 | 603.25 | 06-DEC-08:09 | 6.10 | 3.51 |
Annual Sum or Average | 0.126250E+11 | 0.658421E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.2 | 0.457400E+09 | 603.25 | -1.1 | -3.7 | ||
Maximum of Months | 0.445170E+10 | 26177.86 | 32.02 | 14.63 | 0.680104E+09 | 769.04 | 32.02 | 15.66 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116314E+09 | 2648.97 | 02-JAN-14:00 | 6.70 | 1.59 | 0.650429E+09 | 876.19 | 14-JAN-15:50 | 10.10 | 4.67 |
February | 0.379543E+09 | 4494.96 | 28-FEB-10:50 | 3.43 | 0.87 | 0.613372E+09 | 1141.26 | 27-FEB-15:00 | 3.43 | 0.87 |
March | 0.106727E+10 | 4518.07 | 24-MAR-14:30 | 3.35 | -0.7 | 0.727019E+09 | 1032.98 | 14-MAR-14:09 | 3.35 | -0.7 |
April | 0.111334E+10 | 4634.43 | 29-APR-13:00 | 3.30 | -2.3 | 0.753325E+09 | 1331.14 | 07-APR-14:39 | 3.30 | -2.3 |
May | 0.132861E+10 | 6068.50 | 22-MAY-09:00 | 0.00 | -0.6 | 0.938244E+09 | 1947.08 | 20-MAY-15:00 | 0.00 | -0.6 |
June | 0.156942E+10 | 16565.60 | 30-JUN-17:40 | 29.60 | 14.57 | 0.147633E+10 | 2249.26 | 22-JUN-12:09 | 29.60 | 14.57 |
July | 0.465376E+10 | 40129.28 | 19-JUL-17:10 | 30.77 | 16.46 | 0.175458E+10 | 2246.89 | 19-JUL-12:20 | 30.77 | 16.46 |
August | 0.404603E+10 | 37401.52 | 10-AUG-17:08 | 32.02 | 13.58 | 0.180071E+10 | 2246.84 | 08-AUG-12:09 | 32.02 | 13.58 |
September | 0.234978E+10 | 28740.23 | 02-SEP-17:12 | 33.67 | 16.35 | 0.127054E+10 | 2246.86 | 06-SEP-12:39 | 23.17 | 17.43 |
October | 0.171414E+10 | 6703.63 | 21-OCT-08:70 | -0.5 | -1.4 | 0.866289E+09 | 1623.50 | 18-OCT-15:39 | -0.5 | -1.4 |
November | 0.107402E+10 | 5072.48 | 20-NOV-15:10 | 1.98 | -2.9 | 0.672521E+09 | 1161.69 | 04-NOV-14:50 | 1.98 | -2.9 |
December | 0.352725E+09 | 7010.22 | 22-DEC-14:05 | -3.3 | -6.1 | 0.653378E+09 | 899.76 | 06-DEC-13:39 | -3.3 | -6.1 |
Annual Sum or Average | 0.197649E+11 | 0.121767E+11 | ||||||||
Minimum of Months | 0.116314E+09 | 2648.97 | -3.3 | -6.1 | 0.613372E+09 | 876.19 | -3.3 | -6.1 | ||
Maximum of Months | 0.465376E+10 | 40129.28 | 33.67 | 16.46 | 0.180071E+10 | 2249.26 | 32.02 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.3 | 0.648943E+09 | 1012.93 | 14-JAN-15:50 | 10.10 | 4.67 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -12.4 | -13.9 | 0.646832E+09 | 1579.37 | 27-FEB-15:00 | 18.90 | 7.06 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -3.0 | -4.1 | 0.807359E+09 | 1410.66 | 14-MAR-14:20 | 14.07 | 6.61 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.55 | 0.102319E+10 | 2211.24 | 07-APR-14:50 | 21.97 | 9.03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -3.0 | 0.149120E+10 | 3541.74 | 19-MAY-15:00 | 27.80 | 14.54 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.36 | 0.308621E+10 | 5880.26 | 29-JUN-15:20 | 31.83 | 14.57 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.32 | 0.450110E+10 | 8724.24 | 17-JUL-15:00 | 37.20 | 17.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.96 | 0.448808E+10 | 8043.80 | 05-AUG-15:00 | 35.60 | 17.65 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.59 | 0.260830E+10 | 6100.40 | 02-SEP-15:20 | 34.23 | 16.29 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.94 | 0.141693E+10 | 2774.71 | 18-OCT-15:09 | 24.90 | 11.51 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.54 | 0.820448E+09 | 1789.20 | 04-NOV-14:39 | 16.87 | 8.04 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -2.1 | -4.2 | 0.668125E+09 | 1147.49 | 06-DEC-13:50 | 11.88 | 5.75 |
Annual Sum or Average | 0.00 | 0.222067E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.9 | 0.646832E+09 | 1012.93 | 10.10 | 4.67 | ||
Maximum of Months | 0.00 | 0.00 | 19.45 | 13.32 | 0.450110E+10 | 8724.24 | 37.20 | 17.65 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100609E+11 | 29598.30 | 30-JAN-06:12 | -15.7 |
February | 0.685575E+10 | 29341.87 | 10-FEB-06:22 | -19.7 |
March | 0.639322E+10 | 29544.38 | 06-MAR-06:12 | -17.1 |
April | 0.351323E+10 | 29212.63 | 29-APR-05:12 | -7.6 |
May | 0.238000E+10 | 29094.52 | 22-MAY-05:12 | -0.6 |
June | 0.194566E+09 | 28869.92 | 17-JUN-05:01 | 2.35 |
July | 19184072.05 | 735.45 | 05-JUL-06:20 | 9.40 |
August | 46112124.01 | 7002.58 | 18-AUG-05:03 | 7.30 |
September | 0.534029E+09 | 29004.48 | 19-SEP-05:01 | 2.20 |
October | 0.159561E+10 | 29133.22 | 11-OCT-05:12 | -0.4 |
November | 0.423413E+10 | 29478.40 | 27-NOV-06:12 | -14.4 |
December | 0.731967E+10 | 29344.03 | 26-DEC-06:12 | -8.0 |
Annual Sum or Average | 0.431464E+11 | |||
Minimum of Months | 19184072.05 | 735.45 | -19.7 | |
Maximum of Months | 0.100609E+11 | 29598.30 | 9.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388679E+11 | 83981.60 | 06-JAN-02:61 | -25.7 |
February | 0.241581E+11 | 83107.81 | 04-FEB-23:22 | -20.0 |
March | 0.189713E+11 | 83087.16 | 04-MAR-02:42 | -18.3 |
April | 0.783824E+10 | 80962.79 | 29-APR-05:01 | -7.7 |
May | 0.427598E+10 | 80933.04 | 01-MAY-05:11 | -0.4 |
June | 0.236451E+09 | 2664.76 | 20-JUN-16:20 | 29.40 |
July | 0.102784E+09 | 1546.18 | 10-JUL-15:00 | 27.80 |
August | 0.136151E+09 | 2278.50 | 24-AUG-17:00 | 29.40 |
September | 0.479286E+09 | 53769.90 | 21-SEP-05:01 | 6.60 |
October | 0.244871E+10 | 63419.21 | 11-OCT-05:31 | -0.2 |
November | 0.142150E+11 | 83105.03 | 27-NOV-04:02 | -15.8 |
December | 0.280655E+11 | 83906.32 | 31-DEC-08:41 | -26.9 |
Annual Sum or Average | 0.139795E+12 | |||
Minimum of Months | 0.102784E+09 | 1546.18 | -26.9 | |
Maximum of Months | 0.388679E+11 | 83981.60 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181027E+12 | 173763.76 | 05-JAN-16:00 | -19.4 |
February | 0.959509E+11 | 120232.53 | 03-FEB-18:55 | -16.7 |
March | 0.645862E+11 | 124569.76 | 06-MAR-03:51 | -18.3 |
April | 0.846981E+10 | 58858.38 | 29-APR-04:52 | -7.8 |
May | 0.661939E+10 | 50314.69 | 08-MAY-05:51 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.948481E+09 | 24779.98 | 11-OCT-06:00 | 0.00 |
November | 0.471812E+11 | 108615.89 | 27-NOV-05:00 | -15.6 |
December | 0.121342E+12 | 171225.27 | 31-DEC-03:00 | -24.4 |
Annual Sum or Average | 0.526126E+12 | |||
Minimum of Months | 0.00 | 0.00 | -24.4 | |
Maximum of Months | 0.181027E+12 | 173763.76 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.194040E+10 | 1573.38 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.168253E+10 | 1573.38 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.180438E+10 | 1573.38 | 02-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.170377E+10 | 1573.38 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.170031E+10 | 1573.38 | 03-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.164171E+10 | 1421.29 | 01-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.166575E+10 | 1573.38 | 07-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.177348E+10 | 1573.38 | 04-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.172215E+10 | 1573.38 | 05-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.180798E+10 | 1573.38 | 02-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.182631E+10 | 1573.38 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.194699E+10 | 1573.38 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.212158E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.164171E+10 | 1421.29 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.194699E+10 | 1573.38 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.590552E+10 | 5298.77 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.540507E+10 | 5298.77 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.624439E+10 | 5298.77 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.585166E+10 | 5298.77 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.607496E+10 | 5298.77 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.602110E+10 | 5298.77 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.590552E+10 | 5298.77 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.624439E+10 | 5298.77 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.585166E+10 | 5298.77 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.590552E+10 | 5298.77 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.568223E+10 | 5298.77 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.590552E+10 | 5298.77 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.709975E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.540507E+10 | 5298.77 | 0.00 | 0.00 | |
Maximum of Months | 0.624439E+10 | 5298.77 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.804520E+10 | 7440.58 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.729788E+10 | 7440.58 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.816050E+10 | 7440.58 | 06-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.759327E+10 | 7152.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.778718E+10 | 7152.88 | 02-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.768167E+10 | 7152.88 | 23-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.757367E+10 | 7152.88 | 03-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.810472E+10 | 7152.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.771041E+10 | 7440.58 | 16-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.793009E+10 | 7440.58 | 10-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.775426E+10 | 7440.58 | 02-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.811832E+10 | 7440.58 | 01-DEC-14:20 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.937572E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.729788E+10 | 7152.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.816050E+10 | 7440.58 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.194040E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549670E+10 |
February | 0.127628E+10 | 0.168253E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392893E+10 |
March | 0.149825E+10 | 0.180438E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362440E+10 |
April | 0.138726E+10 | 0.170377E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1425942.42 | 0.218532E+10 |
May | 0.144276E+10 | 0.170031E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19325527.16 | 0.209045E+10 |
June | 0.144276E+10 | 0.164171E+10 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102834E+09 | 0.116383E+10 |
July | 0.138726E+10 | 0.166575E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240093E+09 | 0.732430E+09 |
August | 0.149825E+10 | 0.177348E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184818E+09 | 0.985034E+09 |
September | 0.138726E+10 | 0.172215E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51522704.40 | 0.162116E+10 |
October | 0.138726E+10 | 0.180798E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4348295.52 | 0.210436E+10 |
November | 0.133177E+10 | 0.182631E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317751E+10 |
December | 0.138726E+10 | 0.194699E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429855E+10 |
Annual Sum or Average | 0.168137E+11 | 0.212158E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604368E+09 | 0.314087E+11 |
Minimum of Months | 0.127628E+10 | 0.164171E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732430E+09 |
Maximum of Months | 0.149825E+10 | 0.194699E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240093E+09 | 0.549670E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.590552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188262E+11 |
February | 0.300332E+10 | 0.540507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56276.63 | 0.131465E+11 |
March | 0.352563E+10 | 0.624439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116957E+11 |
April | 0.326447E+10 | 0.585166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41585619.33 | 0.661929E+10 |
May | 0.339505E+10 | 0.607496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156116E+09 | 0.634907E+10 |
June | 0.339505E+10 | 0.602110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165350E+09 | 0.409416E+10 |
July | 0.326447E+10 | 0.590552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408617E+09 | 0.329300E+10 |
August | 0.352563E+10 | 0.624439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362049E+09 | 0.387372E+10 |
September | 0.326447E+10 | 0.585166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196924E+09 | 0.552623E+10 |
October | 0.326447E+10 | 0.590552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58388085.10 | 0.619274E+10 |
November | 0.313390E+10 | 0.568223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102811E+11 |
December | 0.326447E+10 | 0.590552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147039E+11 |
Annual Sum or Average | 0.395654E+11 | 0.709975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138909E+10 | 0.104602E+12 |
Minimum of Months | 0.300332E+10 | 0.540507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329300E+10 |
Maximum of Months | 0.352563E+10 | 0.624439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408617E+09 | 0.188262E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.804520E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791271E+11 |
February | 0.690763E+10 | 0.729788E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595244E+09 | 0.463111E+11 |
March | 0.810895E+10 | 0.816050E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69438163.01 | 0.409628E+11 |
April | 0.750829E+10 | 0.759327E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206664E+10 | 0.203830E+11 |
May | 0.780862E+10 | 0.778718E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298379E+10 | 0.210208E+11 |
June | 0.780862E+10 | 0.768167E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134759E+10 | 0.179141E+11 |
July | 0.750829E+10 | 0.757367E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822494E+09 | 0.186613E+11 |
August | 0.810895E+10 | 0.810472E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527703E+09 | 0.221943E+11 |
September | 0.750829E+10 | 0.771041E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179220E+10 | 0.253768E+11 |
October | 0.750829E+10 | 0.793009E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230163E+10 | 0.214183E+11 |
November | 0.720796E+10 | 0.775426E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133062E+10 | 0.337556E+11 |
December | 0.750829E+10 | 0.811832E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238953E+09 | 0.541690E+11 |
Annual Sum or Average | 0.910005E+11 | 0.937572E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140763E+11 | 0.401294E+12 |
Minimum of Months | 0.690763E+10 | 0.729788E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179141E+11 |
Maximum of Months | 0.810895E+10 | 0.816050E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298379E+10 | 0.791271E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1573.38 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 14861.85 | 05-JAN-17:10 |
February | 1680.92 | 01-FEB-08:09 | 1573.38 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 11260.32 | 01-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1573.38 | 02-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 10645.31 | 06-MAR-07:10 |
April | 1680.92 | 01-APR-07:10 | 1573.38 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.46 | 16-APR-14:00 | 6650.88 | 28-APR-16:10 |
May | 1680.92 | 01-MAY-07:10 | 1573.38 | 03-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.10 | 19-MAY-16:10 | 9097.43 | 22-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1421.29 | 01-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2023.17 | 29-JUN-16:10 | 4604.06 | 16-JUN-07:00 |
July | 1680.92 | 01-JUL-07:10 | 1573.38 | 07-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.51 | 17-JUL-16:10 | 3378.95 | 05-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 1573.38 | 04-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2315.18 | 09-AUG-17:00 | 4235.50 | 17-AUG-16:03 |
September | 1680.92 | 01-SEP-07:10 | 1573.38 | 05-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.61 | 01-SEP-16:10 | 5863.20 | 18-SEP-16:10 |
October | 1680.92 | 02-OCT-07:10 | 1573.38 | 02-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.74 | 15-OCT-14:00 | 7255.45 | 10-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 1573.38 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9706.58 | 27-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1573.38 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 12276.47 | 28-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1421.29 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3378.95 | |||||
Maximum of Months | 1680.92 | 1573.38 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.51 | 14861.85 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 5298.77 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 34591.08 | 05-JAN-16:10 |
February | 3955.50 | 01-FEB-08:09 | 5298.77 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.32 | 27-FEB-15:00 | 18426.96 | 01-FEB-17:00 |
March | 3955.50 | 01-MAR-08:09 | 5298.77 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 16030.00 | 30-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 5298.77 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1074.62 | 07-APR-15:10 | 11622.56 | 28-APR-16:00 |
May | 3955.50 | 01-MAY-07:10 | 5298.77 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3465.93 | 19-MAY-15:10 | 21383.14 | 22-MAY-06:10 |
June | 3955.50 | 01-JUN-07:10 | 5298.77 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4012.15 | 29-JUN-15:10 | 8201.38 | 14-JUN-08:00 |
July | 3955.50 | 01-JUL-07:10 | 5298.77 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4301.46 | 25-JUL-15:10 | 6366.57 | 08-JUL-07:00 |
August | 3955.50 | 01-AUG-07:10 | 5298.77 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3702.66 | 09-AUG-17:00 | 12612.82 | 17-AUG-15:05 |
September | 3955.50 | 01-SEP-07:10 | 5298.77 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3983.39 | 02-SEP-15:10 | 11048.39 | 12-SEP-03:00 |
October | 3955.50 | 02-OCT-07:10 | 5298.77 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2240.33 | 15-OCT-14:00 | 9517.28 | 31-OCT-16:00 |
November | 3955.50 | 01-NOV-07:10 | 5298.77 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 15775.39 | 28-NOV-08:00 |
December | 3955.50 | 01-DEC-08:09 | 5298.77 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 18016.18 | 31-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 5298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6366.57 | ||||
Maximum of Months | 3955.50 | 5298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4301.46 | 34591.08 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 7440.58 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 142025.71 | 05-JAN-16:00 |
February | 9097.65 | 01-FEB-08:09 | 7440.58 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11156.98 | 27-FEB-13:10 | 77248.53 | 01-FEB-15:00 |
March | 9097.65 | 01-MAR-08:09 | 7440.58 | 06-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5901.00 | 14-MAR-12:10 | 62487.15 | 03-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 7152.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22378.56 | 07-APR-12:10 | 43930.31 | 27-APR-11:00 |
May | 9097.65 | 01-MAY-07:10 | 7152.88 | 02-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28715.83 | 19-MAY-16:00 | 69533.50 | 22-MAY-08:00 |
June | 9097.65 | 01-JUN-07:10 | 7152.88 | 23-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14476.73 | 29-JUN-13:00 | 36082.06 | 14-JUN-08:00 |
July | 9097.65 | 01-JUL-07:10 | 7152.88 | 03-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9858.05 | 13-JUL-16:00 | 29213.87 | 08-JUL-10:00 |
August | 9097.65 | 01-AUG-07:10 | 7152.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9217.80 | 25-AUG-16:00 | 65335.24 | 17-AUG-12:05 |
September | 9097.65 | 01-SEP-07:10 | 7440.58 | 16-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15995.33 | 23-SEP-14:00 | 51498.62 | 12-SEP-11:00 |
October | 9097.65 | 02-OCT-07:10 | 7440.58 | 10-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22752.30 | 12-OCT-12:10 | 31943.12 | 03-OCT-09:00 |
November | 9097.65 | 01-NOV-07:10 | 7440.58 | 02-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14317.20 | 17-NOV-14:00 | 57695.76 | 27-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 7440.58 | 01-DEC-14:20 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12265.92 | 10-DEC-01:55 | 100542.64 | 27-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 7152.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29213.87 | |||||
Maximum of Months | 9097.65 | 7440.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 28715.83 | 142025.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1103.37 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.12 |
February | 311.47 | 28-FEB-16:00 | 1680.92 | 1012.21 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.01 |
March | 482.97 | 02-MAR-15:00 | 1680.92 | 959.76 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.72 |
April | 483.31 | 26-APR-13:00 | 1680.92 | 1216.75 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.79 |
May | 3175.39 | 19-MAY-16:00 | 1680.92 | 959.76 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 750.58 | 0.00 |
June | 6598.81 | 29-JUN-15:10 | 1680.92 | 959.76 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1214.73 | 0.00 |
July | 23163.94 | 27-JUL-05:02 | 1109.41 | 2819.79 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.05 |
August | 26177.86 | 12-AUG-05:02 | 1109.41 | 2819.79 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.19 |
September | 22264.28 | 05-SEP-05:01 | 1479.21 | 3759.72 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.04 |
October | 1899.49 | 18-OCT-16:00 | 1680.92 | 1012.21 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 60.53 | 0.00 |
November | 793.68 | 09-NOV-15:00 | 1680.92 | 1216.75 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.25 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1471.15 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1732.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 959.76 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26177.86 | 1680.92 | 3759.72 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1214.73 | 1732.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2648.97 | 02-JAN-14:00 | 3955.50 | 5298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2082.79 |
February | 4494.96 | 28-FEB-10:50 | 3955.50 | 5298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1217.19 |
March | 4518.07 | 24-MAR-14:30 | 3955.50 | 5298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 946.49 |
April | 4634.43 | 29-APR-13:00 | 3955.50 | 5298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1474.73 |
May | 6068.50 | 22-MAY-09:00 | 3955.50 | 5298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6062.49 |
June | 16565.60 | 30-JUN-17:40 | 0.00 | 1870.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 644.44 | 0.00 |
July | 40129.28 | 19-JUL-17:10 | 0.00 | 2493.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1939.85 | 0.00 |
August | 37401.52 | 10-AUG-17:08 | 0.00 | 3116.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2313.57 | 0.00 |
September | 28740.23 | 02-SEP-17:12 | 0.00 | 2493.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1846.05 | 0.00 |
October | 6703.63 | 21-OCT-08:70 | 3955.50 | 5298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1418.08 |
November | 5072.48 | 20-NOV-15:10 | 3955.50 | 5298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.04 |
December | 7010.22 | 22-DEC-14:05 | 7911.00 | 10597.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1902.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2648.97 | 0.00 | 1870.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40129.28 | 7911.00 | 10597.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2313.57 | 6062.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 2626.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5743.14 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 4376.75 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44680.21 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 1750.70 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9192.96 |
April | 0.00 | 01-APR-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11793.71 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12204.58 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1628.77 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6894.70 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6275.04 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6596.01 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 875.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14841.85 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13379.21 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 3501.40 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34164.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 875.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1628.77 | |
Maximum of Months | 0.00 | 0.00 | 4376.75 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44680.21 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.442048E+11 | 34815.28 | 05-JAN-16:00 | 0.307614E+12 | 318529.19 | 05-JAN-17:10 |
February | 0.387089E+11 | 28845.70 | 01-FEB-09:20 | 0.171479E+12 | 207777.29 | 01-FEB-17:00 |
March | 0.421899E+11 | 28695.19 | 06-MAR-09:09 | 0.122497E+12 | 212438.63 | 06-MAR-03:49 |
April | 0.373765E+11 | 28010.67 | 20-APR-08:09 | 0.290628E+11 | 121227.90 | 29-APR-05:10 |
May | 0.371973E+11 | 27723.67 | 08-MAY-08:09 | 0.185044E+11 | 111678.00 | 08-MAY-05:40 |
June | 0.363898E+11 | 31112.80 | 29-JUN-14:00 | 0.246900E+09 | 9432.84 | 17-JUN-05:10 |
July | 0.383266E+11 | 37104.34 | 17-JUL-14:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.407698E+11 | 36236.47 | 10-AUG-14:00 | 17666549.77 | 4213.77 | 18-AUG-06:10 |
September | 0.380758E+11 | 32846.36 | 02-SEP-14:00 | 0.127449E+10 | 26966.96 | 20-SEP-05:10 |
October | 0.396856E+11 | 33213.75 | 30-OCT-07:10 | 0.765805E+10 | 65594.35 | 11-OCT-05:10 |
November | 0.406365E+11 | 34159.07 | 27-NOV-16:49 | 0.889999E+11 | 192316.76 | 27-NOV-04:10 |
December | 0.440621E+11 | 34640.70 | 28-DEC-08:09 | 0.211028E+12 | 261330.55 | 31-DEC-02:49 |
Annual Sum or Average | 0.477623E+12 | 0.958383E+12 | ||||
Minimum of Months | 0.363898E+11 | 27723.67 | 0.00 | 0.00 | ||
Maximum of Months | 0.442048E+11 | 37104.34 | 0.307614E+12 | 318529.19 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.158911E+11 | 0.104256E+11 | 0.112984E+11 | 0.00 | 0.425649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233315E+10 | 0.00 |
February | 0.143855E+11 | 0.850058E+10 | 0.103734E+11 | 0.00 | 0.331111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213838E+10 | 0.00 |
March | 0.162093E+11 | 0.812850E+10 | 0.121089E+11 | 0.00 | 0.333298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241019E+10 | 0.00 |
April | 0.151487E+11 | 0.657020E+10 | 0.112578E+11 | 0.00 | 0.214291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225688E+10 | 0.00 |
May | 0.155624E+11 | 0.568179E+10 | 0.117000E+11 | 0.00 | 0.192726E+10 | 0.00 | 0.00 | 43162537.84 | 0.00 | 0.00 | 0.00 | 0.228266E+10 | 0.00 |
June | 0.153445E+11 | 0.497367E+10 | 0.116594E+11 | 0.00 | 0.157832E+10 | 0.00 | 0.00 | 0.661163E+09 | 0.00 | 0.00 | 0.00 | 0.217281E+10 | 0.00 |
July | 0.151449E+11 | 0.535378E+10 | 0.112984E+11 | 0.00 | 0.199788E+10 | 0.00 | 0.00 | 0.238973E+10 | 0.00 | 0.00 | 0.00 | 0.214187E+10 | 0.00 |
August | 0.161226E+11 | 0.627151E+10 | 0.121016E+11 | 0.00 | 0.220846E+10 | 0.00 | 0.00 | 0.188381E+10 | 0.00 | 0.00 | 0.00 | 0.218185E+10 | 0.00 |
September | 0.152842E+11 | 0.729958E+10 | 0.112504E+11 | 0.00 | 0.155324E+10 | 0.00 | 0.00 | 0.593707E+09 | 0.00 | 0.00 | 0.00 | 0.209467E+10 | 0.00 |
October | 0.156436E+11 | 0.887465E+10 | 0.113057E+11 | 0.00 | 0.167216E+10 | 0.00 | 0.00 | 6660493.50 | 0.00 | 0.00 | 0.00 | 0.218283E+10 | 0.00 |
November | 0.152628E+11 | 0.976020E+10 | 0.108562E+11 | 0.00 | 0.259851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215877E+10 | 0.00 |
December | 0.159708E+11 | 0.107568E+11 | 0.112984E+11 | 0.00 | 0.374541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229065E+10 | 0.00 |
Annual Sum or Average | 0.185970E+12 | 0.925969E+11 | 0.136508E+12 | 0.00 | 0.303247E+11 | 0.00 | 0.00 | 0.557824E+10 | 0.00 | 0.00 | 0.00 | 0.266447E+11 | 0.00 |
Minimum of Months | 0.143855E+11 | 0.497367E+10 | 0.103734E+11 | 0.00 | 0.155324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209467E+10 | 0.00 |
Maximum of Months | 0.162093E+11 | 0.107568E+11 | 0.121089E+11 | 0.00 | 0.425649E+10 | 0.00 | 0.00 | 0.238973E+10 | 0.00 | 0.00 | 0.00 | 0.241019E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.307614E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.171479E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.122497E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.290628E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.185044E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.246900E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 17666549.77 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.127449E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.765805E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.889999E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.211028E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.958383E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.307614E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 14312.73 | 02-JAN-09:09 | 6986.42 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 3637.51 | 05-JAN-17:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 14312.73 | 01-FEB-09:09 | 6986.42 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 3210.30 | 09-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 14312.73 | 06-MAR-09:09 | 6986.42 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 3111.41 | 06-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 14025.03 | 01-APR-08:09 | 6986.42 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2554.05 | 29-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 13872.93 | 02-MAY-08:09 | 6986.42 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 2700.44 | 08-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 13872.93 | 23-JUN-08:09 | 6986.42 | 01-JUN-20:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 1657.03 | 16-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 14025.03 | 07-JUL-08:09 | 6986.42 | 01-JUL-20:30 | 10035.17 | 01-JUL-07:10 | 0.00 | 4223.01 | 17-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 13872.93 | 01-AUG-08:09 | 6986.42 | 01-AUG-19:00 | 10035.17 | 01-AUG-07:10 | 0.00 | 3957.75 | 10-AUG-15:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 14160.64 | 16-SEP-08:09 | 6986.42 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 1884.10 | 20-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 14312.73 | 11-OCT-08:09 | 6986.42 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 2556.83 | 10-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 14312.73 | 02-NOV-08:09 | 6986.42 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2967.14 | 27-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 14312.73 | 05-DEC-15:00 | 6986.42 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 3296.20 | 29-DEC-17:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 13872.93 | 6986.42 | 10035.17 | 0.00 | 1657.03 | 0.00 | 0.00 | |||||
Maximum of Months | 14312.73 | 6986.42 | 10035.17 | 0.00 | 4223.01 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2830.49 | 30-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2852.03 | 17-FEB-12:50 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2844.00 | 02-MAR-12:30 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 2749.94 | 01-APR-11:39 | 0.00 |
May | 1125.65 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2560.84 | 01-MAY-11:30 | 0.00 |
June | 5545.63 | 29-JUN-15:09 | 0.00 | 0.00 | 0.00 | 2245.27 | 06-JUN-11:39 | 0.00 |
July | 9814.39 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2028.42 | 01-JUL-11:00 | 0.00 |
August | 8023.57 | 10-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1840.18 | 02-AUG-11:00 | 0.00 |
September | 6971.55 | 02-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1960.02 | 29-SEP-11:50 | 0.00 |
October | 612.35 | 18-OCT-15:50 | 0.00 | 0.00 | 0.00 | 2190.45 | 27-OCT-11:09 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2490.64 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2704.02 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1840.18 | 0.00 | ||
Maximum of Months | 9814.39 | 0.00 | 0.00 | 0.00 | 2852.03 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 34815.28 | 05-JAN-16:00 | 12813.66 | 10035.17 | 6986.42 | 0.00 | 3355.81 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28845.70 | 01-FEB-09:20 | 14312.73 | 10035.17 | 0.00 | 0.00 | 2788.08 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28695.19 | 06-MAR-09:09 | 14312.73 | 10035.17 | 0.00 | 0.00 | 2637.62 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28010.67 | 20-APR-08:09 | 14025.03 | 10035.17 | 0.00 | 0.00 | 2251.82 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27723.67 | 08-MAY-08:09 | 13585.23 | 10035.17 | 0.00 | 0.00 | 2411.25 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31112.80 | 29-JUN-14:00 | 12836.00 | 10035.17 | 0.00 | 0.00 | 1527.19 | 0.00 | 0.00 | 4933.21 | 0.00 |
July | 37104.34 | 17-JUL-14:09 | 13092.99 | 10035.17 | 0.00 | 0.00 | 3942.61 | 0.00 | 0.00 | 8260.91 | 0.00 |
August | 36236.47 | 10-AUG-14:00 | 12836.00 | 10035.17 | 0.00 | 0.00 | 3919.60 | 0.00 | 0.00 | 7679.44 | 0.00 |
September | 32846.36 | 02-SEP-14:00 | 13176.15 | 10035.17 | 0.00 | 0.00 | 1527.19 | 0.00 | 0.00 | 6340.62 | 0.00 |
October | 33213.75 | 30-OCT-07:10 | 12813.66 | 10035.17 | 6986.42 | 0.00 | 1734.16 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 34159.07 | 27-NOV-16:49 | 12813.66 | 10035.17 | 6986.42 | 0.00 | 2706.76 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34640.70 | 28-DEC-08:09 | 12813.66 | 10035.17 | 6986.42 | 0.00 | 3144.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 27723.67 | 12813.66 | 10035.17 | 0.00 | 0.00 | 1527.19 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37104.34 | 14312.73 | 10035.17 | 6986.42 | 0.00 | 3942.61 | 0.00 | 0.00 | 8260.91 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 318529.19 | 05-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 207777.29 | 01-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 212438.63 | 06-MAR-03:49 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 121227.90 | 29-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 111678.00 | 08-MAY-05:40 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 9432.84 | 17-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 4213.77 | 18-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 26966.96 | 20-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 65594.35 | 11-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 192316.76 | 27-NOV-04:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 261330.55 | 31-DEC-02:49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 318529.19 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.67 | 15.71 | 10.17 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 |
February | 23.83 | 16.50 | 9.00 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
March | 19.50 | 17.11 | 10.00 | 17.83 | 0.00 | 17.83 | 0.00 | 17.83 |
April | 10.00 | 18.85 | 8.33 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
May | 7.33 | 19.55 | 7.00 | 19.66 | 0.00 | 19.66 | 0.00 | 19.66 |
June | 0.67 | 20.44 | 0.67 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.51 | 0.50 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
September | 1.83 | 20.26 | 1.83 | 20.26 | 0.33 | 20.61 | 0.33 | 20.92 |
October | 5.00 | 20.13 | 5.00 | 20.13 | 0.00 | 20.13 | 0.00 | 20.13 |
November | 12.83 | 17.89 | 8.00 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 |
December | 21.50 | 16.79 | 9.17 | 17.54 | 0.00 | 17.54 | 0.00 | 17.54 |
Annual Sum or Average | 149.17 | 16.99 | 69.17 | 17.76 | 1.00 | 17.80 | 1.00 | 17.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.30 | 0.00 | 16.30 |
Maximum of Months | 46.67 | 20.44 | 10.17 | 20.44 | 0.50 | 24.51 | 0.50 | 24.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 111.50 | 14.17 | 4.33 | 14.16 | 0.00 | 14.16 | 0.00 | 14.16 |
February | 89.50 | 14.42 | 4.33 | 14.42 | 0.00 | 14.42 | 0.00 | 14.42 |
March | 89.00 | 14.60 | 5.67 | 14.60 | 0.00 | 14.60 | 0.00 | 14.60 |
April | 37.67 | 14.85 | 3.67 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
May | 21.83 | 14.79 | 2.33 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.31 | 0.00 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.33 | 0.00 | 27.33 |
September | 0.33 | 14.99 | 0.00 | 14.99 | 0.83 | 23.77 | 0.00 | 23.77 |
October | 8.83 | 14.86 | 0.50 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
November | 59.67 | 14.59 | 3.17 | 14.59 | 0.00 | 14.59 | 0.00 | 14.59 |
December | 110.00 | 14.42 | 4.33 | 14.42 | 0.00 | 14.42 | 0.00 | 14.42 |
Annual Sum or Average | 528.33 | 14.47 | 28.33 | 14.47 | 4.17 | 14.57 | 0.00 | 14.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.50 | 14.99 | 5.67 | 14.99 | 1.83 | 27.33 | 0.00 | 27.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 8.90 | 2.00 | 8.90 | 0.00 | 8.90 | 0.00 | 8.90 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 8.90 | 2.00 | 8.90 | 0.00 | 8.90 | 0.00 | 8.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 8.90 | 2.00 | 8.90 | 0.00 | 8.90 | 0.00 | 8.90 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.02 | 300.00 | 21.02 | 300.00 | 21.02 |
February | 276.00 | 21.03 | 276.00 | 21.03 | 276.00 | 21.03 |
March | 324.00 | 21.04 | 324.00 | 21.04 | 324.00 | 21.04 |
April | 300.00 | 21.15 | 285.50 | 21.12 | 285.50 | 21.11 |
May | 312.00 | 21.67 | 220.17 | 21.43 | 220.17 | 21.33 |
June | 238.17 | 23.04 | 43.00 | 22.93 | 24.17 | 22.78 |
July | 66.33 | 23.60 | 128.17 | 23.80 | 0.00 | 23.80 |
August | 138.33 | 23.46 | 77.17 | 23.61 | 0.33 | 23.61 |
September | 230.83 | 22.53 | 110.17 | 22.46 | 67.33 | 22.27 |
October | 300.00 | 21.63 | 202.17 | 21.42 | 202.17 | 21.34 |
November | 288.00 | 21.08 | 283.67 | 21.07 | 283.67 | 21.07 |
December | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
Annual Sum or Average | 3073.67 | 21.61 | 2550.00 | 21.50 | 2283.33 | 21.37 |
Minimum of Months | 66.33 | 21.02 | 43.00 | 21.02 | 0.00 | 21.02 |
Maximum of Months | 324.00 | 23.60 | 324.00 | 23.80 | 324.00 | 23.80 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.55 | 300.00 | 15.55 | 300.00 | 15.55 |
February | 276.00 | 15.72 | 276.00 | 15.72 | 276.00 | 15.72 |
March | 324.00 | 15.78 | 324.00 | 15.78 | 324.00 | 15.78 |
April | 300.00 | 16.63 | 300.00 | 16.63 | 300.00 | 16.63 |
May | 312.00 | 18.08 | 266.00 | 17.72 | 266.00 | 17.59 |
June | 217.17 | 21.54 | 146.50 | 22.20 | 65.50 | 21.77 |
July | 71.83 | 24.50 | 236.17 | 25.92 | 29.83 | 25.99 |
August | 116.17 | 23.17 | 202.50 | 25.07 | 19.67 | 25.07 |
September | 233.67 | 20.33 | 201.50 | 20.69 | 143.83 | 20.29 |
October | 300.00 | 17.78 | 290.00 | 17.71 | 290.00 | 17.69 |
November | 288.00 | 16.07 | 288.00 | 16.07 | 288.00 | 16.07 |
December | 300.00 | 15.58 | 300.00 | 15.58 | 300.00 | 15.58 |
Annual Sum or Average | 3038.83 | 17.53 | 3130.67 | 17.92 | 2602.83 | 17.55 |
Minimum of Months | 71.83 | 15.55 | 146.50 | 15.55 | 19.67 | 15.55 |
Maximum of Months | 324.00 | 24.50 | 324.00 | 25.92 | 324.00 | 25.99 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.03 | 300.00 | 10.03 | 300.00 | 10.03 |
February | 276.00 | 10.38 | 276.00 | 10.38 | 276.00 | 10.38 |
March | 324.00 | 10.70 | 324.00 | 10.70 | 324.00 | 10.70 |
April | 300.00 | 12.43 | 300.00 | 12.43 | 300.00 | 12.43 |
May | 312.00 | 14.66 | 301.00 | 14.54 | 301.00 | 14.50 |
June | 245.67 | 20.59 | 186.00 | 20.88 | 132.17 | 20.50 |
July | 190.50 | 27.70 | 240.50 | 27.89 | 143.67 | 28.26 |
August | 205.33 | 26.03 | 201.50 | 26.87 | 109.33 | 27.35 |
September | 244.50 | 18.90 | 249.50 | 19.33 | 202.67 | 19.04 |
October | 300.00 | 14.80 | 300.00 | 14.80 | 300.00 | 14.80 |
November | 288.00 | 11.39 | 288.00 | 11.39 | 288.00 | 11.39 |
December | 300.00 | 10.16 | 300.00 | 10.16 | 300.00 | 10.16 |
Annual Sum or Average | 3286.00 | 14.83 | 3266.50 | 14.97 | 2976.83 | 14.69 |
Minimum of Months | 190.50 | 10.03 | 186.00 | 10.03 | 109.33 | 10.03 |
Maximum of Months | 324.00 | 27.70 | 324.00 | 27.89 | 324.00 | 28.26 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.168224E+09 | 43162537.84 | 24.67 | 0.164666E+09 | 3557733.06 | 0.00 | 0.51 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 4203.57 | 20-MAY-16:00 | 4181.83 | 20-MAY-16:00 | 169.33 | 19-MAY-14:00 | 1125.65 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.175074E+10 | 0.437593E+09 | 126.92 | 0.165347E+10 | 97272968.19 | 0.00 | 0.95 | 29-JUN-15:10 | 0.00 | 01-JUN-00:10 | 8001.34 | 29-JUN-15:10 | 8001.34 | 29-JUN-15:10 | 1193.88 | 20-JUN-16:00 | 2101.20 | 29-JUN-15:10 | 0.00 | 01-JUN-00:10 |
July | 0.449457E+10 | 0.111411E+10 | 234.89 | 0.428254E+10 | 0.212031E+09 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 20281.79 | 19-JUL-05:01 | 18031.82 | 25-JUL-05:02 | 7202.28 | 19-JUL-05:45 | 4399.35 | 19-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.363632E+10 | 0.904183E+09 | 217.16 | 0.357789E+10 | 58424021.78 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 17871.23 | 08-AUG-05:02 | 17834.42 | 07-AUG-05:01 | 3465.70 | 01-AUG-05:02 | 3898.25 | 08-AUG-05:02 | 0.00 | 01-AUG-00:10 |
September | 0.131595E+10 | 0.320158E+09 | 89.61 | 0.117985E+10 | 0.136104E+09 | 0.00 | 1.00 | 01-SEP-05:05 | 0.00 | 01-SEP-00:10 | 18994.26 | 07-SEP-05:02 | 17241.48 | 05-SEP-05:01 | 6848.43 | 07-SEP-05:03 | 4145.23 | 07-SEP-05:02 | 0.00 | 01-SEP-00:10 |
October | 26471280.76 | 6660493.50 | 6.17 | 26471280.76 | -0.0 | 0.00 | 0.31 | 18-OCT-16:00 | 0.00 | 01-OCT-00:10 | 2472.04 | 18-OCT-16:00 | 2472.04 | 18-OCT-16:00 | 0.00 | 18-OCT-15:10 | 612.35 | 18-OCT-15:50 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.113923E+11 | 0.282587E+10 | 699.41 | 0.108849E+11 | 0.507390E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.449457E+10 | 0.111411E+10 | 234.89 | 0.428254E+10 | 0.212031E+09 | 0.00 | 1.00 | 0.00 | 20281.79 | 18031.82 | 7202.28 | 4399.35 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.804896E+09 | 0.223570E+09 | 39.61 | 0.795581E+09 | 9314695.30 | 0.00 | 0.87 | 30-JUN-17:40 | 0.00 | 01-JUN-00:10 | 18158.22 | 30-JUN-17:40 | 18158.22 | 30-JUN-17:40 | 493.93 | 22-JUN-15:00 | 4640.30 | 30-JUN-17:40 | 0.00 | 01-JUN-00:10 |
July | 0.469733E+10 | 0.127562E+10 | 150.33 | 0.461131E+10 | 86022179.62 | 0.00 | 1.00 | 02-JUL-17:25 | 0.00 | 01-JUL-00:10 | 47456.72 | 16-JUL-11:05 | 45078.35 | 19-JUL-17:45 | 6063.53 | 16-JUL-11:05 | 11723.66 | 17-JUL-17:43 | 0.00 | 01-JUL-00:10 |
August | 0.358651E+10 | 0.979629E+09 | 109.62 | 0.357876E+10 | 7753529.57 | 0.00 | 1.00 | 04-AUG-17:17 | 0.00 | 01-AUG-00:10 | 44719.37 | 08-AUG-20:05 | 44719.37 | 08-AUG-20:05 | 777.14 | 08-AUG-12:00 | 10925.02 | 10-AUG-17:08 | 0.00 | 01-AUG-00:10 |
September | 0.100710E+10 | 0.273549E+09 | 39.04 | 0.938316E+09 | 68780261.04 | 0.00 | 1.00 | 02-SEP-17:12 | 0.00 | 01-SEP-00:10 | 31282.76 | 02-SEP-17:12 | 31282.76 | 02-SEP-17:12 | 3720.68 | 07-SEP-15:40 | 8527.04 | 02-SEP-17:12 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.100958E+11 | 0.275237E+10 | 338.60 | 0.992396E+10 | 0.171871E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.469733E+10 | 0.127562E+10 | 150.33 | 0.461131E+10 | 86022179.62 | 0.00 | 1.00 | 0.00 | 47456.72 | 45078.35 | 6063.53 | 11723.66 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.70 | 24.66 | 36.04 | 32.71 | 231.97 | 0.00 | 0.00 | 0.00 |
February | 102.84 | 50.61 | 52.23 | 85.72 | 158.97 | 0.00 | 0.00 | 0.00 |
March | 132.02 | 48.49 | 83.53 | 115.69 | 125.47 | 0.00 | 0.00 | 0.00 |
April | 172.04 | 76.00 | 96.04 | 185.33 | 80.32 | 0.00 | 0.00 | 0.00 |
May | 212.84 | 97.10 | 115.74 | 246.44 | 63.50 | 0.00 | 0.00 | 0.00 |
June | 231.39 | 106.25 | 125.14 | 287.17 | 50.60 | 0.00 | 0.00 | 0.00 |
July | 237.28 | 119.95 | 117.33 | 310.39 | 51.05 | 0.00 | 0.00 | 0.00 |
August | 201.05 | 98.41 | 102.65 | 256.24 | 54.56 | 0.00 | 0.00 | 0.00 |
September | 161.88 | 81.79 | 80.08 | 193.41 | 69.31 | 0.00 | 0.00 | 0.00 |
October | 115.93 | 57.62 | 58.30 | 121.99 | 90.67 | 0.00 | 0.00 | 0.00 |
November | 81.92 | 40.64 | 41.27 | 70.56 | 129.53 | 0.00 | 0.00 | 0.00 |
December | 54.95 | 23.15 | 31.80 | 31.92 | 192.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 147.27 | 68.79 | 78.48 | 161.84 | 108.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.95 | 23.15 | 31.80 | 31.92 | 50.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.28 | 119.95 | 125.14 | 310.39 | 231.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.70 | 24.66 | 36.04 | 32.71 | 231.97 | 0.00 | 0.00 | 0.00 |
February | 102.84 | 50.61 | 52.23 | 85.72 | 158.97 | 0.00 | 0.00 | 0.00 |
March | 132.02 | 48.49 | 83.53 | 115.69 | 125.47 | 0.00 | 0.00 | 0.00 |
April | 172.04 | 76.00 | 96.04 | 185.33 | 80.32 | 0.00 | 0.00 | 0.00 |
May | 212.84 | 97.10 | 115.74 | 246.44 | 63.50 | 0.00 | 0.00 | 0.00 |
June | 231.39 | 106.25 | 125.14 | 287.17 | 50.60 | 0.00 | 0.00 | 0.00 |
July | 237.28 | 119.95 | 117.33 | 310.39 | 51.05 | 0.00 | 0.00 | 0.00 |
August | 201.05 | 98.41 | 102.65 | 256.24 | 54.56 | 0.00 | 0.00 | 0.00 |
September | 161.88 | 81.79 | 80.08 | 193.41 | 69.31 | 0.00 | 0.00 | 0.00 |
October | 115.93 | 57.62 | 58.30 | 121.99 | 90.67 | 0.00 | 0.00 | 0.00 |
November | 81.92 | 40.64 | 41.27 | 70.56 | 129.53 | 0.00 | 0.00 | 0.00 |
December | 54.95 | 23.15 | 31.80 | 31.92 | 192.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 147.27 | 68.79 | 78.48 | 161.84 | 108.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.95 | 23.15 | 31.80 | 31.92 | 50.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.28 | 119.95 | 125.14 | 310.39 | 231.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.92 | 0.00 | 16.92 | 0.82 | 142.59 | 0.00 | 0.00 | 0.00 |
February | 23.89 | 0.00 | 23.89 | 5.87 | 99.66 | 0.00 | 0.00 | 0.00 |
March | 38.81 | 0.00 | 38.81 | 17.11 | 75.23 | 0.00 | 0.00 | 0.00 |
April | 44.38 | 0.34 | 44.05 | 30.97 | 46.74 | 0.00 | 0.00 | 0.00 |
May | 58.06 | 3.40 | 54.67 | 52.36 | 35.32 | 0.00 | 0.00 | 0.00 |
June | 67.58 | 7.72 | 59.86 | 73.55 | 26.52 | 0.00 | 0.00 | 0.00 |
July | 61.73 | 5.71 | 56.02 | 73.90 | 27.38 | 0.00 | 0.00 | 0.00 |
August | 50.05 | 1.81 | 48.24 | 54.62 | 30.24 | 0.00 | 0.00 | 0.00 |
September | 37.13 | 0.03 | 37.10 | 33.51 | 40.65 | 0.00 | 0.00 | 0.00 |
October | 27.06 | 0.00 | 27.06 | 15.80 | 54.12 | 0.00 | 0.00 | 0.00 |
November | 18.39 | 0.00 | 18.39 | 4.61 | 80.23 | 0.00 | 0.00 | 0.00 |
December | 14.19 | 0.00 | 14.19 | 0.51 | 118.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.26 | 1.59 | 36.67 | 30.44 | 64.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.19 | 0.00 | 14.19 | 0.51 | 26.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.58 | 7.72 | 59.86 | 73.90 | 142.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.92 | 0.00 | 16.92 | 0.82 | 142.59 | 0.00 | 0.00 | 0.00 |
February | 23.89 | 0.00 | 23.89 | 5.87 | 99.66 | 0.00 | 0.00 | 0.00 |
March | 38.81 | 0.00 | 38.81 | 17.11 | 75.23 | 0.00 | 0.00 | 0.00 |
April | 44.38 | 0.34 | 44.04 | 30.97 | 46.74 | 0.00 | 0.00 | 0.00 |
May | 58.06 | 3.40 | 54.66 | 52.36 | 35.32 | 0.00 | 0.00 | 0.00 |
June | 67.58 | 7.72 | 59.86 | 73.54 | 26.52 | 0.00 | 0.00 | 0.00 |
July | 61.73 | 5.71 | 56.02 | 73.90 | 27.38 | 0.00 | 0.00 | 0.00 |
August | 50.05 | 1.81 | 48.24 | 54.62 | 30.24 | 0.00 | 0.00 | 0.00 |
September | 37.13 | 0.03 | 37.10 | 33.51 | 40.65 | 0.00 | 0.00 | 0.00 |
October | 27.06 | 0.00 | 27.06 | 15.80 | 54.12 | 0.00 | 0.00 | 0.00 |
November | 18.39 | 0.00 | 18.39 | 4.61 | 80.23 | 0.00 | 0.00 | 0.00 |
December | 14.19 | 0.00 | 14.19 | 0.51 | 118.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.26 | 1.59 | 36.67 | 30.44 | 64.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.19 | 0.00 | 14.19 | 0.51 | 26.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.58 | 7.72 | 59.86 | 73.90 | 142.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 19.34 | 88.79 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 49.68 | 60.84 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 92.34 | 47.89 | 0.00 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 124.46 | 31.30 | 0.83 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 166.08 | 25.72 | 0.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 200.09 | 26.74 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 205.68 | 33.77 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 168.20 | 35.56 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 116.21 | 34.88 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 68.81 | 38.92 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 35.01 | 49.21 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 15.58 | 72.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 105.42 | 45.50 | 0.83 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 15.58 | 25.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 205.68 | 88.79 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 19.34 | 88.79 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 49.68 | 60.84 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 92.34 | 47.89 | 0.00 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 124.46 | 31.30 | 0.83 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 166.08 | 25.72 | 0.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 200.09 | 26.74 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 205.68 | 33.77 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 168.20 | 35.56 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 116.21 | 34.88 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 68.81 | 38.92 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 35.01 | 49.21 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 15.58 | 72.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 105.42 | 45.50 | 0.83 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 15.58 | 25.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 205.68 | 88.79 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 19.34 | 88.79 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 49.68 | 60.84 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 92.34 | 47.89 | 0.00 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 124.46 | 31.30 | 0.83 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 166.08 | 25.72 | 0.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 200.09 | 26.74 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 205.68 | 33.77 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 168.20 | 35.56 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 116.21 | 34.88 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 68.81 | 38.92 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 35.01 | 49.21 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 15.58 | 72.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 105.42 | 45.50 | 0.83 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 15.58 | 25.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 205.68 | 88.79 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 19.34 | 88.79 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 49.68 | 60.84 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 92.34 | 47.89 | 0.00 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 124.46 | 31.30 | 0.83 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 166.08 | 25.72 | 0.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 200.09 | 26.74 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 205.68 | 33.77 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 168.20 | 35.56 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 116.21 | 34.88 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 68.81 | 38.92 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 35.01 | 49.21 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 15.58 | 72.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 105.42 | 45.50 | 0.83 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 15.58 | 25.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 205.68 | 88.79 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 19.34 | 88.79 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 49.68 | 60.84 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 92.34 | 47.89 | 0.00 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 124.46 | 31.30 | 0.83 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 166.08 | 25.72 | 0.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 200.09 | 26.74 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 205.68 | 33.77 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 168.20 | 35.56 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 116.21 | 34.88 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 68.81 | 38.92 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 35.01 | 49.21 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 15.58 | 72.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 105.42 | 45.50 | 0.83 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 15.58 | 25.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 205.68 | 88.79 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 19.34 | 88.79 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 49.68 | 60.84 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 92.34 | 47.89 | 0.00 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 124.46 | 31.30 | 0.83 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 166.08 | 25.72 | 0.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 200.09 | 26.74 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 205.68 | 33.77 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 168.20 | 35.56 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 116.21 | 34.88 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 68.81 | 38.92 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 35.01 | 49.21 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 15.58 | 72.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 105.42 | 45.50 | 0.83 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 15.58 | 25.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 205.68 | 88.79 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 19.34 | 88.79 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 49.68 | 60.84 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 92.34 | 47.89 | 0.00 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 124.46 | 31.30 | 0.83 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 166.08 | 25.72 | 0.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 200.09 | 26.74 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 205.68 | 33.77 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 168.20 | 35.56 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 116.21 | 34.88 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 68.81 | 38.92 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 35.01 | 49.21 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 15.58 | 72.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 105.42 | 45.50 | 0.83 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 15.58 | 25.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 205.68 | 88.79 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 19.34 | 88.79 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 49.68 | 60.84 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 92.34 | 47.89 | 0.00 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 124.46 | 31.30 | 0.83 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 166.08 | 25.72 | 0.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 200.09 | 26.74 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 205.68 | 33.77 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 168.20 | 35.56 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 116.21 | 34.88 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 68.81 | 38.92 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 35.01 | 49.21 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 15.58 | 72.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 105.42 | 45.50 | 0.83 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 15.58 | 25.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 205.68 | 88.79 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 19.34 | 88.79 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 49.68 | 60.84 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 92.34 | 47.89 | 0.00 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 124.46 | 31.30 | 0.83 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 166.08 | 25.72 | 0.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 200.09 | 26.74 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 205.68 | 33.77 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 168.20 | 35.56 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 116.21 | 34.88 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 68.81 | 38.92 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 35.01 | 49.21 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 15.58 | 72.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 105.42 | 45.50 | 0.83 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 15.58 | 25.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 205.68 | 88.79 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 19.34 | 88.79 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 49.68 | 60.84 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 92.34 | 47.89 | 0.00 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 124.46 | 31.30 | 0.83 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 166.08 | 25.72 | 0.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 200.09 | 26.74 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 205.68 | 33.77 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 168.20 | 35.56 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 116.21 | 34.88 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 68.81 | 38.92 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 35.01 | 49.21 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 15.58 | 72.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 105.42 | 45.50 | 0.83 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 15.58 | 25.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 205.68 | 88.79 | 0.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.162577E+09 | 66037905.05 | 96539375.11 | 87616468.25 | 0.621305E+09 |
February | 0.248787E+09 | 0.122439E+09 | 0.126349E+09 | 0.207386E+09 | 0.384588E+09 |
March | 0.353601E+09 | 0.129872E+09 | 0.223729E+09 | 0.309871E+09 | 0.336058E+09 |
April | 0.445933E+09 | 0.196986E+09 | 0.248947E+09 | 0.480388E+09 | 0.208202E+09 |
May | 0.570079E+09 | 0.260071E+09 | 0.310008E+09 | 0.660059E+09 | 0.170068E+09 |
June | 0.599755E+09 | 0.275395E+09 | 0.324360E+09 | 0.744342E+09 | 0.131147E+09 |
July | 0.635532E+09 | 0.321287E+09 | 0.314245E+09 | 0.831337E+09 | 0.136727E+09 |
August | 0.538498E+09 | 0.263569E+09 | 0.274928E+09 | 0.686320E+09 | 0.146133E+09 |
September | 0.419581E+09 | 0.212003E+09 | 0.207578E+09 | 0.501330E+09 | 0.179640E+09 |
October | 0.310496E+09 | 0.154341E+09 | 0.156155E+09 | 0.326747E+09 | 0.242855E+09 |
November | 0.212327E+09 | 0.105344E+09 | 0.106983E+09 | 0.182900E+09 | 0.335734E+09 |
December | 0.147186E+09 | 62016452.46 | 85169427.26 | 85501309.11 | 0.514555E+09 |
Annual Sum or Average | 0.464435E+10 | 0.216936E+10 | 0.247499E+10 | 0.510380E+10 | 0.340701E+10 |
Minimum of Months | 0.147186E+09 | 62016452.46 | 85169427.26 | 85501309.11 | 0.131147E+09 |
Maximum of Months | 0.635532E+09 | 0.321287E+09 | 0.324360E+09 | 0.831337E+09 | 0.621305E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.162577E+09 | 66037905.05 | 96539375.11 | 87616468.25 | 0.621305E+09 |
February | 0.248787E+09 | 0.122439E+09 | 0.126349E+09 | 0.207386E+09 | 0.384588E+09 |
March | 0.353601E+09 | 0.129872E+09 | 0.223729E+09 | 0.309871E+09 | 0.336058E+09 |
April | 0.445933E+09 | 0.196986E+09 | 0.248947E+09 | 0.480388E+09 | 0.208202E+09 |
May | 0.570079E+09 | 0.260071E+09 | 0.310008E+09 | 0.660059E+09 | 0.170068E+09 |
June | 0.599755E+09 | 0.275395E+09 | 0.324360E+09 | 0.744342E+09 | 0.131147E+09 |
July | 0.635532E+09 | 0.321287E+09 | 0.314245E+09 | 0.831337E+09 | 0.136727E+09 |
August | 0.538498E+09 | 0.263569E+09 | 0.274928E+09 | 0.686320E+09 | 0.146133E+09 |
September | 0.419581E+09 | 0.212003E+09 | 0.207578E+09 | 0.501330E+09 | 0.179640E+09 |
October | 0.310496E+09 | 0.154341E+09 | 0.156155E+09 | 0.326747E+09 | 0.242855E+09 |
November | 0.212327E+09 | 0.105344E+09 | 0.106983E+09 | 0.182900E+09 | 0.335734E+09 |
December | 0.147186E+09 | 62016452.46 | 85169427.26 | 85501309.11 | 0.514555E+09 |
Annual Sum or Average | 0.464435E+10 | 0.216936E+10 | 0.247499E+10 | 0.510380E+10 | 0.340701E+10 |
Minimum of Months | 0.147186E+09 | 62016452.46 | 85169427.26 | 85501309.11 | 0.131147E+09 |
Maximum of Months | 0.635532E+09 | 0.321287E+09 | 0.324360E+09 | 0.831337E+09 | 0.621305E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45315351.18 | 0.00 | 45315351.18 | 2186324.94 | 0.381907E+09 |
February | 57790609.70 | 0.00 | 57790609.70 | 14192348.92 | 0.241094E+09 |
March | 0.103949E+09 | 5392.55 | 0.103944E+09 | 45827207.72 | 0.201507E+09 |
April | 0.115036E+09 | 869215.31 | 0.114167E+09 | 80266955.03 | 0.121144E+09 |
May | 0.155521E+09 | 9102545.10 | 0.146419E+09 | 0.140243E+09 | 94594733.49 |
June | 0.175168E+09 | 20008153.08 | 0.155160E+09 | 0.190629E+09 | 68738304.82 |
July | 0.165333E+09 | 15282220.08 | 0.150051E+09 | 0.197935E+09 | 73325300.40 |
August | 0.134048E+09 | 4836218.95 | 0.129212E+09 | 0.146297E+09 | 80985917.40 |
September | 96248574.06 | 84013.27 | 96164560.79 | 86862683.71 | 0.105357E+09 |
October | 72473966.78 | 0.00 | 72473966.78 | 42325715.90 | 0.144947E+09 |
November | 47679171.03 | 0.00 | 47679171.03 | 11952915.99 | 0.207955E+09 |
December | 37999475.76 | 0.00 | 37999475.76 | 1366379.42 | 0.318201E+09 |
Annual Sum or Average | 0.120656E+10 | 50187758.32 | 0.115637E+10 | 0.960085E+09 | 0.203975E+10 |
Minimum of Months | 37999475.76 | 0.00 | 37999475.76 | 1366379.42 | 68738304.82 |
Maximum of Months | 0.175168E+09 | 20008153.08 | 0.155160E+09 | 0.197935E+09 | 0.381907E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45313889.90 | 0.00 | 45313889.90 | 2186054.86 | 0.381907E+09 |
February | 57788869.36 | 0.00 | 57788869.36 | 14191468.86 | 0.241094E+09 |
March | 0.103946E+09 | 5392.29 | 0.103940E+09 | 45824241.96 | 0.201507E+09 |
April | 0.115033E+09 | 869174.57 | 0.114164E+09 | 80263521.69 | 0.121144E+09 |
May | 0.155516E+09 | 9102118.45 | 0.146414E+09 | 0.140238E+09 | 94594511.02 |
June | 0.175163E+09 | 20007215.27 | 0.155156E+09 | 0.190623E+09 | 68737944.80 |
July | 0.165328E+09 | 15281503.78 | 0.150047E+09 | 0.197929E+09 | 73324654.62 |
August | 0.134044E+09 | 4835992.27 | 0.129208E+09 | 0.146293E+09 | 80985396.46 |
September | 96245820.49 | 84009.33 | 96161811.16 | 86859910.95 | 0.105356E+09 |
October | 72471771.98 | 0.00 | 72471771.98 | 42323707.37 | 0.144946E+09 |
November | 47677675.86 | 0.00 | 47677675.86 | 11952177.34 | 0.207954E+09 |
December | 37998233.75 | 0.00 | 37998233.75 | 1366192.82 | 0.318201E+09 |
Annual Sum or Average | 0.120653E+10 | 50185405.95 | 0.115634E+10 | 0.960050E+09 | 0.203975E+10 |
Minimum of Months | 37998233.75 | 0.00 | 37998233.75 | 1366192.82 | 68737944.80 |
Maximum of Months | 0.175163E+09 | 20007215.27 | 0.155156E+09 | 0.197929E+09 | 0.381907E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 51805136.85 | 0.237826E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.120174E+09 | 0.147184E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.247313E+09 | 0.128278E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.322590E+09 | 81133440.61 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.444818E+09 | 68899838.53 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.518622E+09 | 69315208.08 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.550888E+09 | 90451197.33 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.450503E+09 | 95244975.72 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.301214E+09 | 90410093.27 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.184294E+09 | 0.104240E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 90735028.71 | 0.127553E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 0.194478E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.332467E+10 | 0.143501E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 68899838.53 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.550888E+09 | 0.237826E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 51805136.85 | 0.237826E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.120174E+09 | 0.147184E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.247313E+09 | 0.128278E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.322590E+09 | 81133440.61 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.444818E+09 | 68899838.53 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.518622E+09 | 69315208.08 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.550888E+09 | 90451197.33 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.450503E+09 | 95244975.72 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.301214E+09 | 90410093.27 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.184294E+09 | 0.104240E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 90735028.71 | 0.127553E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 0.194478E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.332467E+10 | 0.143501E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 68899838.53 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.550888E+09 | 0.237826E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 51805136.85 | 0.237826E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.120174E+09 | 0.147184E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.247313E+09 | 0.128278E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.322590E+09 | 81133440.61 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.444818E+09 | 68899838.53 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.518622E+09 | 69315208.08 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.550888E+09 | 90451197.33 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.450503E+09 | 95244975.72 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.301214E+09 | 90410093.27 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.184294E+09 | 0.104240E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 90735028.71 | 0.127553E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 0.194478E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.332467E+10 | 0.143501E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 68899838.53 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.550888E+09 | 0.237826E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 51805136.85 | 0.237826E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.120174E+09 | 0.147184E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.247313E+09 | 0.128278E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.322590E+09 | 81133440.61 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.444818E+09 | 68899838.53 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.518622E+09 | 69315208.08 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.550888E+09 | 90451197.33 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.450503E+09 | 95244975.72 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.301214E+09 | 90410093.27 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.184294E+09 | 0.104240E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 90735028.71 | 0.127553E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 0.194478E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.332467E+10 | 0.143501E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 68899838.53 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.550888E+09 | 0.237826E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 51805136.85 | 0.237826E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.120174E+09 | 0.147184E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.247313E+09 | 0.128278E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.322590E+09 | 81133440.61 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.444818E+09 | 68899838.53 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.518622E+09 | 69315208.08 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.550888E+09 | 90451197.33 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.450503E+09 | 95244975.72 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.301214E+09 | 90410093.27 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.184294E+09 | 0.104240E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 90735028.71 | 0.127553E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 0.194478E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.332467E+10 | 0.143501E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 68899838.53 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.550888E+09 | 0.237826E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 51805136.85 | 0.237826E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.120174E+09 | 0.147184E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.247313E+09 | 0.128278E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.322590E+09 | 81133440.61 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.444818E+09 | 68899838.53 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.518622E+09 | 69315208.08 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.550888E+09 | 90451197.33 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.450503E+09 | 95244975.72 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.301214E+09 | 90410093.27 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.184294E+09 | 0.104240E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 90735028.71 | 0.127553E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 0.194478E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.332467E+10 | 0.143501E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 68899838.53 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.550888E+09 | 0.237826E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 51805136.85 | 0.237826E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.120174E+09 | 0.147184E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.247313E+09 | 0.128278E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.322590E+09 | 81133440.61 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.444818E+09 | 68899838.53 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.518622E+09 | 69315208.08 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.550888E+09 | 90451197.33 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.450503E+09 | 95244975.72 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.301214E+09 | 90410093.27 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.184294E+09 | 0.104240E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 90735028.71 | 0.127553E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 0.194478E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.332467E+10 | 0.143501E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 68899838.53 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.550888E+09 | 0.237826E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 51805136.85 | 0.237826E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.120174E+09 | 0.147184E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.247313E+09 | 0.128278E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.322590E+09 | 81133440.61 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.444818E+09 | 68899838.53 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.518622E+09 | 69315208.08 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.550888E+09 | 90451197.33 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.450503E+09 | 95244975.72 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.301214E+09 | 90410093.27 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.184294E+09 | 0.104240E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 90735028.71 | 0.127553E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 0.194478E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.332467E+10 | 0.143501E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 68899838.53 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.550888E+09 | 0.237826E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 51805136.85 | 0.237826E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.120174E+09 | 0.147184E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.247313E+09 | 0.128278E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.322590E+09 | 81133440.61 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.444818E+09 | 68899838.53 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.518622E+09 | 69315208.08 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.550888E+09 | 90451197.33 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.450503E+09 | 95244975.72 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.301214E+09 | 90410093.27 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.184294E+09 | 0.104240E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 90735028.71 | 0.127553E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 0.194478E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.332467E+10 | 0.143501E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 68899838.53 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.550888E+09 | 0.237826E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 51805136.85 | 0.237826E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.120174E+09 | 0.147184E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.247313E+09 | 0.128278E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.322590E+09 | 81133440.61 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.444818E+09 | 68899838.53 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.518622E+09 | 69315208.08 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.550888E+09 | 90451197.33 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.450503E+09 | 95244975.72 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.301214E+09 | 90410093.27 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.184294E+09 | 0.104240E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 90735028.71 | 0.127553E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 0.194478E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.332467E+10 | 0.143501E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 41718053.06 | 68899838.53 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.550888E+09 | 0.237826E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 56.59 | 738.64 | 155.24 | 49.31 | 105.92 | 0.00 | 0.00 |
February | 173.62 | 507.70 | 253.45 | 101.22 | 152.23 | 0.00 | 0.00 |
March | 262.26 | 398.06 | 341.66 | 96.98 | 244.68 | 0.00 | 0.00 |
April | 431.50 | 253.02 | 432.85 | 152.67 | 280.18 | 0.00 | 0.00 |
May | 595.19 | 195.23 | 541.81 | 201.00 | 340.82 | 0.00 | 0.00 |
June | 716.20 | 149.01 | 597.93 | 227.93 | 370.00 | 0.00 | 0.00 |
July | 763.44 | 151.72 | 598.02 | 251.32 | 346.69 | 0.00 | 0.00 |
August | 620.01 | 167.88 | 502.20 | 200.42 | 301.78 | 0.00 | 0.00 |
September | 452.84 | 218.90 | 398.02 | 163.65 | 234.37 | 0.00 | 0.00 |
October | 272.87 | 286.86 | 285.97 | 115.25 | 170.72 | 0.00 | 0.00 |
November | 141.66 | 410.82 | 200.62 | 81.28 | 119.34 | 0.00 | 0.00 |
December | 54.44 | 611.40 | 138.28 | 46.31 | 91.97 | 0.00 | 0.00 |
Annual Sum or Average | 379.44 | 340.31 | 371.06 | 140.76 | 230.30 | 0.00 | 0.00 |
Minimum of Months | 54.44 | 149.01 | 138.28 | 46.31 | 91.97 | 0.00 | 0.00 |
Maximum of Months | 763.44 | 738.64 | 598.02 | 251.32 | 370.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 986.20 | 7834.33 | 284.32 | 118.29 | 166.03 | 0.00 | 0.00 |
February | 2204.26 | 4898.41 | 469.19 | 258.09 | 211.09 | 0.00 | 0.00 |
March | 4109.61 | 3399.04 | 767.60 | 365.69 | 401.91 | 0.00 | 0.00 |
April | 5094.95 | 1721.28 | 951.72 | 532.06 | 419.66 | 0.00 | 0.00 |
May | 6632.21 | 1175.67 | 1221.81 | 696.94 | 524.86 | 0.00 | 0.00 |
June | 8071.52 | 829.57 | 1471.36 | 944.56 | 526.79 | 0.00 | 0.00 |
July | 8353.35 | 1072.84 | 1523.26 | 1065.85 | 457.41 | 0.00 | 0.00 |
August | 7006.54 | 1131.91 | 1268.17 | 864.56 | 403.61 | 0.00 | 0.00 |
September | 4715.25 | 1170.99 | 880.26 | 558.11 | 322.16 | 0.00 | 0.00 |
October | 2783.94 | 1562.21 | 548.39 | 304.94 | 243.45 | 0.00 | 0.00 |
November | 1497.49 | 3111.04 | 332.00 | 163.36 | 168.65 | 0.00 | 0.00 |
December | 754.12 | 5475.10 | 222.95 | 87.31 | 135.64 | 0.00 | 0.00 |
Annual Sum or Average | 4363.02 | 2776.24 | 830.49 | 498.03 | 332.46 | 0.00 | 0.00 |
Minimum of Months | 754.12 | 829.57 | 222.95 | 87.31 | 135.64 | 0.00 | 0.00 |
Maximum of Months | 8353.35 | 7834.33 | 1523.26 | 1065.85 | 526.79 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.151558E+09 | 0.197838E+10 | 0.415784E+09 | 0.132076E+09 | 0.283708E+09 | 0.00 | 0.00 |
February | 0.420017E+09 | 0.122823E+10 | 0.613154E+09 | 0.244877E+09 | 0.368277E+09 | 0.00 | 0.00 |
March | 0.702441E+09 | 0.106618E+10 | 0.915097E+09 | 0.259755E+09 | 0.655341E+09 | 0.00 | 0.00 |
April | 0.111844E+10 | 0.655821E+09 | 0.112193E+10 | 0.395710E+09 | 0.726225E+09 | 0.00 | 0.00 |
May | 0.159417E+10 | 0.522895E+09 | 0.145120E+10 | 0.538347E+09 | 0.912849E+09 | 0.00 | 0.00 |
June | 0.185640E+10 | 0.386230E+09 | 0.154984E+10 | 0.590805E+09 | 0.959035E+09 | 0.00 | 0.00 |
July | 0.204481E+10 | 0.406377E+09 | 0.160173E+10 | 0.673138E+09 | 0.928587E+09 | 0.00 | 0.00 |
August | 0.166063E+10 | 0.449641E+09 | 0.134509E+10 | 0.536811E+09 | 0.808276E+09 | 0.00 | 0.00 |
September | 0.117377E+10 | 0.567382E+09 | 0.103166E+10 | 0.424174E+09 | 0.607482E+09 | 0.00 | 0.00 |
October | 0.730858E+09 | 0.768319E+09 | 0.765938E+09 | 0.308683E+09 | 0.457255E+09 | 0.00 | 0.00 |
November | 0.367179E+09 | 0.106485E+10 | 0.520010E+09 | 0.210688E+09 | 0.309323E+09 | 0.00 | 0.00 |
December | 0.145803E+09 | 0.163758E+10 | 0.370369E+09 | 0.124033E+09 | 0.246337E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.119661E+11 | 0.107319E+11 | 0.117018E+11 | 0.443910E+10 | 0.726269E+10 | 0.00 | 0.00 |
Minimum of Months | 0.145803E+09 | 0.386230E+09 | 0.370369E+09 | 0.124033E+09 | 0.246337E+09 | 0.00 | 0.00 |
Maximum of Months | 0.204481E+10 | 0.197838E+10 | 0.160173E+10 | 0.673138E+09 | 0.959035E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.264145E+10 | 0.209835E+11 | 0.761513E+09 | 0.316816E+09 | 0.444697E+09 | 0.00 | 0.00 |
February | 0.533255E+10 | 0.118502E+11 | 0.113506E+10 | 0.624380E+09 | 0.510681E+09 | 0.00 | 0.00 |
March | 0.110072E+11 | 0.910398E+10 | 0.205594E+10 | 0.979468E+09 | 0.107647E+10 | 0.00 | 0.00 |
April | 0.132061E+11 | 0.446157E+10 | 0.246686E+10 | 0.137909E+10 | 0.108777E+10 | 0.00 | 0.00 |
May | 0.177637E+11 | 0.314892E+10 | 0.327249E+10 | 0.186669E+10 | 0.140580E+10 | 0.00 | 0.00 |
June | 0.209214E+11 | 0.215024E+10 | 0.381375E+10 | 0.244831E+10 | 0.136544E+10 | 0.00 | 0.00 |
July | 0.223736E+11 | 0.287351E+10 | 0.407990E+10 | 0.285478E+10 | 0.122512E+10 | 0.00 | 0.00 |
August | 0.187663E+11 | 0.303171E+10 | 0.339667E+10 | 0.231564E+10 | 0.108103E+10 | 0.00 | 0.00 |
September | 0.122219E+11 | 0.303522E+10 | 0.228164E+10 | 0.144661E+10 | 0.835029E+09 | 0.00 | 0.00 |
October | 0.745651E+10 | 0.418421E+10 | 0.146882E+10 | 0.816754E+09 | 0.652061E+09 | 0.00 | 0.00 |
November | 0.388149E+10 | 0.806381E+10 | 0.860545E+09 | 0.423416E+09 | 0.437129E+09 | 0.00 | 0.00 |
December | 0.201985E+10 | 0.146645E+11 | 0.597150E+09 | 0.233860E+09 | 0.363291E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.137592E+12 | 0.875514E+11 | 0.261903E+11 | 0.157058E+11 | 0.104845E+11 | 0.00 | 0.00 |
Minimum of Months | 0.201985E+10 | 0.215024E+10 | 0.597150E+09 | 0.233860E+09 | 0.363291E+09 | 0.00 | 0.00 |
Maximum of Months | 0.223736E+11 | 0.209835E+11 | 0.407990E+10 | 0.285478E+10 | 0.140580E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.104536E+10 | -957256347.7 | 0.00 | 0.00 | 744.00 | 0.00 | -88102914.7 | 58.99 | 0.00 | 0.00 |
February | 0.974090E+09 | -894740188.6 | 0.00 | 0.00 | 672.00 | 0.00 | -79349373.6 | 58.99 | 0.00 | 0.00 |
March | 0.112232E+10 | -0.103490E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87424907.6 | 58.99 | 0.00 | 0.00 |
April | 0.101009E+10 | -926365884.0 | 0.00 | 0.00 | 720.00 | 0.00 | -83725728.5 | 58.99 | 0.00 | 0.00 |
May | 0.994028E+09 | -910533486.0 | 0.00 | 0.00 | 744.00 | 0.00 | -83494063.6 | 58.99 | 0.00 | 0.00 |
June | 0.925748E+09 | -851143898.2 | 0.00 | 0.00 | 720.00 | 0.00 | -74604546.7 | 58.99 | 0.00 | 0.00 |
July | 0.853698E+09 | -780886487.7 | 0.00 | 0.00 | 744.00 | 0.00 | -72811147.1 | 59.00 | 0.00 | 0.00 |
August | 0.893475E+09 | -819676481.3 | 0.00 | 0.00 | 744.00 | 0.00 | -73798911.0 | 58.99 | 0.00 | 0.00 |
September | 0.847720E+09 | -772509971.1 | 0.00 | 0.00 | 720.00 | 0.00 | -75209662.7 | 58.99 | 0.00 | 0.00 |
October | 0.894419E+09 | -810503927.9 | 0.00 | 0.00 | 744.00 | 0.00 | -83915336.8 | 58.99 | 0.00 | 0.00 |
November | 0.911850E+09 | -827626703.1 | 0.00 | 0.00 | 720.00 | 0.00 | -84223151.2 | 59.00 | 0.00 | 0.00 |
December | 0.100258E+10 | -914641495.0 | 0.00 | 0.00 | 744.00 | 0.00 | -87934886.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.114754E+11 | -0.105008E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -974594630.2 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.847720E+09 | -0.103490E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88102914.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.112232E+10 | -772509971.1 | 0.00 | 0.00 | 744.00 | 0.00 | -72811147.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.96 | 0.88 | 04-JAN-11:20 | 114.85 | 8.43 | 0.00 | 31.17 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.95 | 0.88 | 03-FEB-11:09 | 121.08 | 8.90 | 0.00 | 35.67 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.92 | 0.88 | 02-MAR-09:09 | 224.66 | 11.96 | 0.00 | 161.83 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.92 | 0.88 | 01-APR-09:09 | 234.44 | 11.90 | 0.00 | 180.67 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.91 | 0.88 | 01-MAY-08:20 | 1042.70 | 13.12 | 18.67 | 251.17 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.92 | 0.88 | 01-JUN-13:39 | 3246.97 | 14.23 | 51.33 | 267.83 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.91 | 0.88 | 01-JUL-07:19 | 2559.75 | 13.84 | 33.83 | 253.83 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.93 | 0.88 | 01-AUG-08:00 | 215.64 | 11.35 | 0.00 | 177.33 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.93 | 0.88 | 03-SEP-08:39 | 174.58 | 10.59 | 0.00 | 112.50 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.95 | 0.88 | 01-OCT-12:39 | 137.38 | 9.33 | 0.00 | 65.33 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.96 | 0.88 | 01-NOV-10:30 | 104.63 | 8.04 | 0.00 | 17.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.97 | 0.88 | 04-DEC-11:30 | 87.20 | 7.20 | 0.00 | 7.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | 0.93 | 839.42 | 11.15 | 103.83 | 1562.17 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 226.83 | 0.91 | 0.88 | 87.20 | 7.20 | 0.00 | 7.83 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 434.17 | 0.97 | 0.88 | 3246.97 | 14.23 | 51.33 | 267.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.88 | 0.64 | 14-JAN-15:30 | 202.58 | 20.49 | 104.83 | 9.17 | 112.68 | 20.49 | 97.67 | 0.00 |
February | 275.00 | 0.84 | 0.61 | 21-FEB-15:39 | 321.30 | 23.14 | 146.50 | 51.17 | 138.62 | 21.34 | 133.83 | 1.50 |
March | 304.00 | 0.76 | 0.61 | 01-MAR-15:20 | 515.80 | 24.85 | 224.83 | 128.67 | 387.35 | 25.38 | 249.17 | 62.83 |
April | 325.17 | 0.77 | 0.61 | 01-APR-15:09 | 472.93 | 23.14 | 205.00 | 125.50 | 500.76 | 24.24 | 243.83 | 82.17 |
May | 385.83 | 0.75 | 0.61 | 01-MAY-15:09 | 382.33 | 22.35 | 248.50 | 169.83 | 627.92 | 23.48 | 291.67 | 106.83 |
June | 434.17 | 0.76 | 0.61 | 01-JUN-14:20 | 371.17 | 22.07 | 263.00 | 179.17 | 347.59 | 23.29 | 323.67 | 113.83 |
July | 417.33 | 0.75 | 0.61 | 01-JUL-14:50 | 380.63 | 22.40 | 252.83 | 176.00 | 525.84 | 23.51 | 316.00 | 118.00 |
August | 421.33 | 0.78 | 0.61 | 01-AUG-14:39 | 371.35 | 22.04 | 228.33 | 139.00 | 493.47 | 23.16 | 275.83 | 100.83 |
September | 352.17 | 0.79 | 0.61 | 01-SEP-15:20 | 561.79 | 24.05 | 205.00 | 112.17 | 494.77 | 25.14 | 236.67 | 69.00 |
October | 317.67 | 0.82 | 0.61 | 02-OCT-14:00 | 548.96 | 24.75 | 187.83 | 80.17 | 216.92 | 23.50 | 188.50 | 26.33 |
November | 269.50 | 0.86 | 0.64 | 01-NOV-14:09 | 308.72 | 23.63 | 142.00 | 34.00 | 114.91 | 20.57 | 116.00 | 0.00 |
December | 236.83 | 0.89 | 0.68 | 01-DEC-15:09 | 212.63 | 22.47 | 108.33 | 14.33 | 94.28 | 19.88 | 75.17 | 0.00 |
Annual Sum or Average | 3965.83 | 0.79 | 397.06 | 22.93 | 2317.00 | 1219.17 | 368.46 | 23.05 | 2548.00 | 681.33 | ||
Minimum of Months | 226.83 | 0.75 | 0.61 | 202.58 | 20.49 | 104.83 | 9.17 | 94.28 | 19.88 | 75.17 | 0.00 | |
Maximum of Months | 434.17 | 0.89 | 0.68 | 561.79 | 24.85 | 263.00 | 179.17 | 627.92 | 25.38 | 323.67 | 118.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120066E+11 | 28752.89 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.811890E+10 | 28752.89 | 01-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.752394E+10 | 28752.89 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.405133E+10 | 28752.89 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.273066E+10 | 28752.89 | 01-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165648E+09 | 28752.89 | 02-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11559038.80 | 6883.14 | 18-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.586457E+09 | 28752.89 | 13-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189198E+10 | 28752.89 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.505106E+10 | 28752.89 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.883754E+10 | 28752.89 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.509756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120066E+11 | 28752.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.461423E+11 | 80351.64 | 01-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.284166E+11 | 80351.64 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219158E+11 | 80351.64 | 02-MAR-21:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.866099E+10 | 80351.64 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.435532E+10 | 80351.64 | 01-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.267216E+09 | 52992.26 | 21-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.249421E+10 | 63064.72 | 11-OCT-05:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160287E+11 | 80351.64 | 12-NOV-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.332488E+11 | 80351.64 | 01-DEC-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161530E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.461423E+11 | 80351.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.179868E+12 | 171838.60 | 05-JAN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.950466E+11 | 119786.53 | 03-FEB-18:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.637185E+11 | 124123.94 | 06-MAR-03:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.820721E+10 | 58412.66 | 29-APR-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.647389E+10 | 49869.16 | 08-MAY-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.917619E+09 | 24333.85 | 11-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.466351E+11 | 108169.83 | 27-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120277E+12 | 170779.81 | 31-DEC-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.521145E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.179868E+12 | 171838.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.168224E+09 | 0.164666E+09 | 4203.57 | 20-MAY-16:00 | 4181.83 | 0.00 |
June | 0.00 | 0.00 | 0.175074E+10 | 0.165347E+10 | 8001.34 | 29-JUN-15:10 | 8001.34 | 0.00 |
July | 0.00 | 0.00 | 0.449457E+10 | 0.428254E+10 | 20281.79 | 19-JUL-05:01 | 13210.67 | 0.00 |
August | 0.00 | 0.00 | 0.363632E+10 | 0.357789E+10 | 17871.23 | 08-AUG-05:02 | 17012.38 | 0.00 |
September | 0.00 | 0.00 | 0.131595E+10 | 0.117985E+10 | 18994.26 | 07-SEP-05:02 | 12423.87 | 0.00 |
October | 0.00 | 0.00 | 26471280.76 | 26471280.76 | 2472.04 | 18-OCT-16:00 | 2472.04 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.113923E+11 | 0.108849E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.449457E+10 | 0.428254E+10 | 20281.79 | 17012.38 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.804896E+09 | 0.795581E+09 | 18158.22 | 30-JUN-17:40 | 18158.22 | 0.00 |
July | 0.00 | 0.00 | 0.469733E+10 | 0.461131E+10 | 47456.72 | 16-JUL-11:05 | 41393.18 | 0.00 |
August | 0.00 | 0.00 | 0.358651E+10 | 0.357876E+10 | 44719.37 | 08-AUG-20:05 | 44719.37 | 0.00 |
September | 0.00 | 0.00 | 0.100710E+10 | 0.938316E+09 | 31282.76 | 02-SEP-17:12 | 31282.76 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.100958E+11 | 0.992396E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.469733E+10 | 0.461131E+10 | 47456.72 | 44719.37 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.115804E+10 | 0.08 | 446.00 | 01-JAN-00:03 | 0.09 |
February | 0.901904E+09 | 0.07 | 446.00 | 01-FEB-00:02 | 0.09 |
March | 0.864484E+09 | 0.06 | 446.00 | 01-MAR-00:05 | 0.09 |
April | 0.260875E+09 | 0.02 | 446.00 | 01-APR-00:10 | 0.09 |
May | 0.144861E+09 | 0.01 | 446.00 | 01-MAY-00:10 | 0.09 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 30595679.04 | 0.00 | 446.00 | 10-OCT-00:40 | 0.09 |
November | 0.544897E+09 | 0.04 | 446.00 | 09-NOV-05:20 | 0.09 |
December | 0.106389E+10 | 0.08 | 446.00 | 01-DEC-00:03 | 0.09 |
Annual Sum or Average | 0.496955E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115804E+10 | 0.08 | 446.00 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.894868E+09 | 0.60 | 1296.68 | 02-JAN-06:01 | 1.04 |
February | 0.727643E+09 | 0.52 | 1296.68 | 01-FEB-06:11 | 1.04 |
March | 0.788026E+09 | 0.44 | 1296.68 | 01-MAR-06:01 | 1.04 |
April | 0.637770E+09 | 0.31 | 1296.68 | 01-APR-05:01 | 1.04 |
May | 0.619738E+09 | 0.31 | 1296.68 | 01-MAY-05:11 | 1.04 |
June | 0.539706E+09 | 0.26 | 1296.68 | 02-JUN-05:02 | 1.03 |
July | 0.526060E+09 | 0.24 | 1296.68 | 15-JUL-05:02 | 1.03 |
August | 0.561887E+09 | 0.25 | 1296.68 | 07-AUG-05:01 | 1.04 |
September | 0.534515E+09 | 0.25 | 1296.68 | 05-SEP-05:01 | 1.03 |
October | 0.572338E+09 | 0.27 | 1296.68 | 02-OCT-05:01 | 1.04 |
November | 0.649906E+09 | 0.36 | 1296.68 | 01-NOV-05:01 | 1.04 |
December | 0.791925E+09 | 0.52 | 1296.68 | 01-DEC-06:01 | 1.04 |
Annual Sum or Average | 0.784438E+10 | 0.36 | |||
Minimum of Months | 0.526060E+09 | 0.24 | 1296.68 | 1.03 | |
Maximum of Months | 0.894868E+09 | 0.60 | 1296.68 | 1.04 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.220358E+10 | 0.70 | 2521.30 | 01-JAN-06:03 | 1.01 |
February | 0.168156E+10 | 0.65 | 2521.30 | 01-FEB-00:02 | 1.01 |
March | 0.168047E+10 | 0.63 | 2521.30 | 02-MAR-21:33 | 1.00 |
April | 0.124426E+10 | 0.49 | 2521.30 | 01-APR-05:01 | 1.01 |
May | 0.116266E+10 | 0.35 | 2521.30 | 01-MAY-05:11 | 1.01 |
June | 0.103862E+10 | 0.24 | 1008.52 | 24-JUN-14:00 | 0.60 |
July | 0.102972E+10 | 0.24 | 2521.30 | 17-JUL-17:06 | 1.00 |
August | 0.110564E+10 | 0.26 | 2521.30 | 10-AUG-17:08 | 1.00 |
September | 0.101872E+10 | 0.25 | 1782.06 | 02-SEP-17:12 | 0.85 |
October | 0.106923E+10 | 0.31 | 1978.87 | 11-OCT-05:31 | 1.01 |
November | 0.140371E+10 | 0.55 | 2521.30 | 12-NOV-00:42 | 1.01 |
December | 0.188960E+10 | 0.67 | 2521.30 | 01-DEC-02:62 | 1.01 |
Annual Sum or Average | 0.165278E+11 | 0.44 | |||
Minimum of Months | 0.101872E+10 | 0.24 | 1008.52 | 0.60 | |
Maximum of Months | 0.220358E+10 | 0.70 | 2521.30 | 1.01 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.894868E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.727643E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.788026E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.637770E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.662901E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.977299E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.164017E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.146607E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.854674E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.578999E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.649906E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.791925E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.106703E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.578999E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.164017E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.220358E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.168156E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.168047E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.124426E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.116266E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.126219E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.230534E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.208527E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.129227E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.106923E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.140371E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.188960E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.192801E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.106923E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.230534E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.894868E+09 | 0.00 | 0.120066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.727643E+09 | 0.00 | 0.811890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.788026E+09 | 0.00 | 0.752394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.637770E+09 | 0.00 | 0.405133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.619738E+09 | 0.168224E+09 | 0.273066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.539706E+09 | 0.175074E+10 | 0.165648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.526060E+09 | 0.447729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.561887E+09 | 0.362358E+10 | 11559038.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.534515E+09 | 0.131255E+10 | 0.586457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.572338E+09 | 26471280.76 | 0.189198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.649906E+09 | 0.00 | 0.505106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.791925E+09 | 0.00 | 0.883754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.784438E+10 | 0.113589E+11 | 0.509756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.526060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.894868E+09 | 0.447729E+10 | 0.120066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.220358E+10 | 0.00 | 0.461423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168156E+10 | 0.00 | 0.284166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168047E+10 | 0.00 | 0.219158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124426E+10 | 0.00 | 0.866099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116266E+10 | 0.00 | 0.435532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103862E+10 | 0.804896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102972E+10 | 0.465960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110564E+10 | 0.357298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101872E+10 | 0.100710E+10 | 0.267216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106923E+10 | 0.00 | 0.249421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140371E+10 | 0.00 | 0.160287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188960E+10 | 0.00 | 0.332488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165278E+11 | 0.100446E+11 | 0.161530E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220358E+10 | 0.465960E+10 | 0.461423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.894868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.727643E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.788026E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.637770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.619738E+09 | 0.00 | 0.00 | 0.00 | 43162537.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.539706E+09 | 0.00 | 0.00 | 0.00 | 0.437593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.526060E+09 | 0.00 | 0.00 | 0.00 | 0.111411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.561887E+09 | 0.00 | 0.00 | 0.00 | 0.904183E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.534515E+09 | 0.00 | 0.00 | 0.00 | 0.320158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.572338E+09 | 0.00 | 0.00 | 0.00 | 6660493.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.649906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.791925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.784438E+10 | 0.00 | 0.00 | 0.00 | 0.282587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.526060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.894868E+09 | 0.00 | 0.00 | 0.00 | 0.111411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.220358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103862E+10 | 0.00 | 0.00 | 0.00 | 0.223570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102972E+10 | 0.00 | 0.00 | 0.00 | 0.127562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110564E+10 | 0.00 | 0.00 | 0.00 | 0.979629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101872E+10 | 0.00 | 0.00 | 0.00 | 0.273549E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165278E+11 | 0.00 | 0.00 | 0.00 | 0.275237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220358E+10 | 0.00 | 0.00 | 0.00 | 0.127562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301765E+10 | 0.00 | 0.00 | 0.12 |
February | 16662099.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215189E+10 | 0.00 | 0.00 | 0.13 |
March | 4962006.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211864E+10 | 0.00 | 0.00 | 0.13 |
April | 0.140092E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127512E+10 | 0.00 | 0.00 | 0.13 |
May | 0.331693E+09 | 616427.92 | 501772.71 | 205216.68 | 1281497.83 | 0.830376E+09 | 0.114830E+09 | 4102.96 | 0.16 |
June | 0.346117E+09 | 57660293.88 | 0.00 | 1814418.30 | 0.00 | 12292365.13 | 0.883418E+09 | 0.00 | 0.31 |
July | 9054811.32 | 0.138341E+09 | 0.00 | 4651838.28 | 0.00 | 0.00 | 0.112615E+10 | 0.00 | 0.37 |
August | 73549029.58 | 85663766.33 | 0.00 | 4152541.86 | 0.00 | 4229056.60 | 0.139102E+10 | 0.00 | 0.41 |
September | 0.405181E+09 | 42381874.95 | 0.00 | 2023376.04 | 0.00 | 0.170664E+09 | 0.830029E+09 | 0.00 | 0.28 |
October | 0.651164E+09 | 0.00 | 0.00 | 55056.64 | 0.00 | 0.587370E+09 | 55089750.16 | 0.00 | 0.13 |
November | 0.140992E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154524E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250640E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.211947E+10 | 0.324663E+09 | 501772.71 | 12902447.81 | 1281497.83 | 0.142199E+11 | 0.440053E+10 | 4102.96 | 0.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.651164E+09 | 0.138341E+09 | 501772.71 | 4651838.28 | 1281497.83 | 0.301765E+10 | 0.139102E+10 | 4102.96 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.357075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935554E+10 | 0.00 | 0.00 | 0.17 |
February | 0.116371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531984E+10 | 0.00 | 0.00 | 0.17 |
March | 0.245085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345103E+10 | 0.00 | 0.00 | 0.19 |
April | 0.251003E+10 | 0.00 | 0.00 | 0.00 | 7294591.13 | 0.103069E+10 | 0.00 | 0.00 | 0.18 |
May | 0.267663E+10 | 0.00 | 0.00 | 0.00 | 34241316.98 | 0.421891E+09 | 0.00 | 0.00 | 0.18 |
June | 0.234000E+10 | 21164217.73 | 0.00 | 571225.64 | 34982906.21 | 0.00 | 0.162174E+09 | 0.00 | 0.20 |
July | 0.122374E+10 | 0.175157E+09 | 0.00 | 3467273.38 | 0.00 | 0.00 | 0.122546E+10 | 0.00 | 0.24 |
August | 0.192602E+10 | 0.113802E+09 | 0.00 | 1863010.16 | 0.00 | 0.00 | 0.752625E+09 | 0.00 | 0.23 |
September | 0.250387E+10 | 29568526.55 | 0.00 | 802983.97 | 3904059.27 | 13770847.99 | 0.304321E+09 | 0.00 | 0.20 |
October | 0.301366E+10 | 0.00 | 0.00 | 0.00 | 9538631.67 | 0.213905E+09 | 0.00 | 0.00 | 0.17 |
November | 0.229703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224044E+10 | 0.00 | 0.00 | 0.17 |
December | 0.107994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650927E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.235426E+11 | 0.339693E+09 | 0.00 | 6704493.15 | 89961505.25 | 0.285564E+11 | 0.244458E+10 | 0.00 | 0.19 |
Minimum of Months | 0.357075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.301366E+10 | 0.175157E+09 | 0.00 | 3467273.38 | 34982906.21 | 0.935554E+10 | 0.122546E+10 | 0.00 | 0.24 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.238460E+12 | 0.138084E+12 | 0.00 | 0.127303E+11 | 0.695957E+11 |
February | 0.391083E+12 | 0.830494E+11 | 0.00 | 0.865210E+10 | 0.398970E+11 |
March | 0.725513E+12 | 0.752164E+11 | 0.00 | 0.802547E+10 | 0.293389E+11 |
April | 0.793940E+12 | 0.365898E+11 | 0.00 | 0.494864E+10 | 0.814323E+10 |
May | 0.109211E+13 | 0.359936E+11 | 0.00 | 0.433898E+10 | 0.515591E+10 |
June | 0.122717E+13 | 0.322294E+11 | 0.00 | 0.363258E+10 | 0.329805E+10 |
July | 0.125711E+13 | 0.309004E+11 | 0.00 | 0.330141E+10 | 0.115816E+11 |
August | 0.105120E+13 | 0.384549E+11 | 0.00 | 0.396216E+10 | 0.911275E+10 |
September | 0.748351E+12 | 0.439511E+11 | 0.00 | 0.415859E+10 | 0.333757E+10 |
October | 0.449930E+12 | 0.379161E+11 | 0.00 | 0.451170E+10 | 0.238737E+10 |
November | 0.212569E+12 | 0.611842E+11 | 0.00 | 0.622370E+10 | 0.212850E+11 |
December | 0.126262E+12 | 0.974160E+11 | 0.00 | 0.100956E+11 | 0.486646E+11 |
Annual Sum or Average | 0.831370E+13 | 0.710985E+12 | 0.00 | 0.745812E+11 | 0.251798E+12 |
Minimum of Months | 0.126262E+12 | 0.309004E+11 | 0.00 | 0.330141E+10 | 0.238737E+10 |
Maximum of Months | 0.125711E+13 | 0.138084E+12 | 0.00 | 0.127303E+11 | 0.695957E+11 |