Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 10:41:48
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 549.87 | 113.72 | 113.72 |
Net Site Energy | 549.87 | 113.72 | 113.72 |
Total Source Energy | 1741.14 | 360.10 | 360.10 |
Net Source Energy | 1741.14 | 360.10 | 360.10 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 112.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 143.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 41.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 549.73 | 0.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 112.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 143.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 16.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 25.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 112.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 143.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 92.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 41.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 22.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 48.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 36.58 | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 113.69 | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 48.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 36.58 | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 113.69 | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 549.728 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 549.728 | 100.00 |
Total On-Site and Utility Electric Sources | 549.728 | 100.00 |
Total Electricity End Uses | 549.728 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 65.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3140.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 119.93 |
Skylight-Roof Ratio [%] | 2.61 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.8432 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.2431 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.6162 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.6162 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.8432 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 10.2257 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.2431 | 46.45 | 2.5587 | |
Total | 4835.13 | 7.6162 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 7.6162 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 7.6162 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-JUN-15:50 | 16-MAR-06:19 | - | - | - | - | - | - | - | - | - | - | 19-APR-11:50 |
Heating | 0.00 | 7951.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15674.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10373.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4497.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1576.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 42157.75 | 7951.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 7951.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 15674.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 10373.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2192.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1576.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 356.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 454.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 293.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 131.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 71.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1740.99 | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 73.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 94.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 360.07 | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 73.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 94.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 360.07 | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.19 |
ZONE2 FINE STORAGE DIRECT AIR | 3.03 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.976836 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.976836 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 39930.82 |
PSZ-OFFICE HEATING COIL | 28932.32 |
PSZ-FINE STORAGE HEATING COIL | 92891.20 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 25010.45 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.19 | 1.19 | 1.19 | 1.19 | 1.19 | 1.19 | 1.00 | 1.00 | 1.19 |
PSZ-FINE STORAGE | 3.03 | 3.03 | 3.03 | 3.03 | 3.03 | 3.03 | 1.00 | 1.00 | 3.03 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.19 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.03 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.19 | 1322.66 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.03 | 3237.48 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.19 | 1.19 | 1.19 | 0.788467 | 24330.07 | 28932.32 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.03 | 3.03 | 3.03 | 2.00 | 75131.64 | 92891.20 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.19 | 0.597323 | 0.796433 | 24330.07 | 12165.03 | 0.768830 | 0.768830 |
PSZ-FINE STORAGE COOLING COIL | 3.03 | 1.51 | 2.02 | 75131.64 | 37565.82 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.843 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.917 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 10.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.226 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.243 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.802 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2568.536 | 10.843 | 201.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2568.536 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 14248.589 | 10.226 | 474.953 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 14248.589 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 20008.023 | 6.243 | 289.971 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20008.023 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.7173 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 2.825 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 2.825 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.394 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2546 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2546 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.53311453E-11 | 0.59398160E-16 | 0.15345153E-15 | 0.0000000 |
5 | 1 | -5.2159564 | 0.46378490E-04 | -0.22332804E-04 | 0.68713370E-11 |
6 | 0 | 5.9333026 | 0.71729982 | 0.71736853 | |
7 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
8 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
9 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
10 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
11 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
12 | 4 | 0.33466332E-12 | 0.89461943E-14 | -0.12859024E-13 | 0.20877214E-15 |
13 | 3 | -0.22871403E-03 | 0.15053116E-05 | -0.31975464E-04 | 0.68322840E-13 |
14 | 2 | 1.3386772 | 0.41030944E-01 | 0.83718830 | -0.43809927E-04 |
15 | 1 | -7.7424045 | 1.2165027 | -15.097018 | 0.25560053 |
16 | 0 | 8.5066984 | 0.84520726 | 16.362604 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.12859024E-13 | 0.89461943E-14 | 0.33466332E-12 | 0.20877214E-15 |
85 | 3 | -0.31975464E-04 | 0.15053116E-05 | -0.22871403E-03 | 0.68322840E-13 |
86 | 2 | 0.83718830 | 0.41030944E-01 | 1.3386772 | -0.43809927E-04 |
87 | 1 | -15.097018 | 1.2165027 | -7.7424045 | 0.25560053 |
88 | 0 | 16.362604 | 0.84520726 | 8.5066984 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.569_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 3.235 | 3.235 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.569_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 3.235 | 3.235 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.569_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 3.235 | 3.235 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.569_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.235 | 3.235 | 1.000 | 0.251 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.35 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.356 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60218 | 0.60218 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43216E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60218 | 0.60218 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43216E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60218 | 0.60218 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43216E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60218 | 0.60218 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43216E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.099 | 0.350 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.799 | 0.390 | 0.214 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.0949E-005 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9114E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.2242E-005 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0729E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8207E-005 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0456E-004 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0405E-004 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.7737E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6184E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6802E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3824E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8105E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4517E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6610E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4902E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5698E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6525E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2864E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0880E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3349E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.1370E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1863E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0972E-004 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.3095E-005 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1994E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1751E-005 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5591E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.3763E-005 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7946E-004 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6559E-005 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3671E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4800E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.6771E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5051E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7692E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6173E-005 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3108E-004 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3210E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1725E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9365E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2081E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8398E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3632E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9221E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2869E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8332E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9265E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7452E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3484E-004 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9589E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7028E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0622E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2120E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8860E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5174E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7546E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3390E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8437E-005 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.9697E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0181E-005 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6407E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4804E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1384E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9663E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1776E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3404E-005 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1824E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7664E-005 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8129E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.2426E-005 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6075E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5940E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2223E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8063E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2937E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9625E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.3927E-004 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4675E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6603E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8724E-005 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0125E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9683E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6998E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8482E-004 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8833E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5306E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.4798E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9480E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8404E-005 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1915E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.8113E-005 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.8520E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.4818E-005 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1973E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1688E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0623E-004 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.9158E-005 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6265E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5575E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7680E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3156E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1980E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.2593E-005 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2186E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7407E-005 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6496E-004 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.4204E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1512E-004 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1815E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0462E-003 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.0323E-005 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2689E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2400E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6758E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8623E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9550E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6055E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5652E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4578E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7839E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7822E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2998E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3675E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1243E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1964E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0270E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8568E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9587E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7604E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9717E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3099E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1745E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3988E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2687E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1366E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5771E-005 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2321E-005 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7078E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2055E-005 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8848E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1104E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3439E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1043E-005 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5148E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4959E-005 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5127E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0471E-005 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4376E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6456E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4952E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8222E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5981E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2658E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0610E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2533E-005 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6184E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0274E-005 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4762E-004 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8837E-005 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3233E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2479E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4198E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5346E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6445E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0513E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1190E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9377E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1215E-005 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6809E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1490E-005 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7524E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9265E-005 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2917E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7834E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3465E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7396E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2173E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7459E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4227E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.5699E-005 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6552E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3398E-005 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2083E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1093E-005 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0070E-004 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3181E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6508E-004 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6090E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8535E-004 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5755E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8345E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9661E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8481E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8660E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0144E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9974E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3154E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2919E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2358E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7322E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5687E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7440E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9358E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9744E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8267E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8267E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4236E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0452E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5105E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.7783E-005 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5882E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2032E-005 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8457E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9374E-005 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0923E-003 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7070E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0782E-003 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6085E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4449E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1830E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5136E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4245E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3531E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6063E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8865E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8638E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4617E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7997E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2985E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6377E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8050E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8404E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2902E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3448E-004 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1116E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2605E-004 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4585E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1721E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7615E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5253E-005 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0031E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8307E-005 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9354E-004 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3487E-005 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0501E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9659E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2255E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6213E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6203E-004 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9545E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9034E-005 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8292E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6171E-005 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3298E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4353E-005 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9709E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3240E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4646E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9105E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2441E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3533E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6137E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4204E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6335E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7724E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4274E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4735E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3885E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2194E-005 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5251E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0360E-005 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3831E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8243E-005 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5030E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8939E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0891E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1607E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0443E-005 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0030E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2303E-005 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9495E-005 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6406E-005 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2895E-005 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5837E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2352E-005 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9534E-005 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8766E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2493E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2143E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1439E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4649E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1906E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3693E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8108E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9712E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2549E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5913E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9201E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9024E-005 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4665E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3139E-005 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1084E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6858E-005 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2366E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.2634E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.0578E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.7935E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.5685E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.6030E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.4125E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.9731E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.4928E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.0453E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.7966E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.6092E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1059E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.4724E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.7732E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.4525E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.6476E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.0331E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.2879E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.3130E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.8331E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.5999E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.4029E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.4770E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.1257E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1323E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.2926E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.3460E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.8354E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.4204E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.4000E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.4769E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1257E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 12084.58392 | 14501.50070 | 0.99554 | 1.19465 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.35133 | 1.71656E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 6334.98447 | 7601.98136 | 0.17778 | 0.21334 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 8.70000 | 6.99286E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 39256.38447 | 47107.66137 | 2.52129 | 3.02555 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.13300 | 1.71671E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 12065.32928 | 14478.39514 | 0.28564 | 0.42471 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 8.70000 | 6.99286E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.20000 | 1.71672E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 20842.04308 | 25010.45170 | 0.50986 | 0.97684 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 18230.88 | 1.19465 | 1.19465 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 6417.30 | 0.21334 | 0.21334 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 57041.27 | 3.02555 | 3.02555 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 16066.25 | 0.42471 | 0.42471 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.19465 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.02555 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 39930.81694 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 25010.45170 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.19465 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.19465 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.19465 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.19465 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.19465 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.19465 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.02555 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.02555 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.02555 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.02555 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.02555 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.02555 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.19465 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.02555 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.19465 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.19465 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1322.66331 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.19465 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.19465 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.19465 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.78847 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.19465 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.59732 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.79643 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24330.07000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12165.03500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76883 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76883 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24330.07000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28932.32145 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28932.32145 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.02555 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.02555 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3237.48258 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.02555 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.02555 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.02555 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.99686 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.02555 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.51278 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.01703 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 75131.64000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 37565.82000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 75131.64000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 92891.20161 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 92891.20161 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 23402.3 | 11.86 | 11.59 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 72779.9 | 11.12 | 10.87 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 3.4733063443E-002 | 2.6693374314E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 9.8438497760E-002 | 0.1479200999 | Pass | Pass | 0.1906033172 | 1.5156394581 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 6.7337007427E-002 | 6.9469797272E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 10327.51 | 540.25 | 0.00 | -75.2 | 551.48 | 11344.07 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.653 | 0.717 | 3204.84 | 3105.72 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.685 | 2.825 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.685 | 2.825 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.569_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.235 | 0.251 | 0.276 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.569_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.235 | 0.251 | 0.276 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.569_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.235 | 0.251 | 0.276 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.569_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.235 | 0.251 | 0.276 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 137.59 | 5.237 | 0.483 | 0.385 | |||||||||||||||||
North Total or Average | 6.51 | 3.235 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 131.09 | 5.337 | 0.494 | 0.391 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.8432 | 236.88 | 2568.54 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 44.68 | 0.0000 | Y | 21.54 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 10.2257 | 1393.41 | 14248.59 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 20.56 | 0.0000 | Y | 55.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.2431 | 3204.84 | 20008.02 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 17.87 | 0.0000 | Y | 67.11 |
Interior Lighting Total | 7.6162 | 4835.13 | 36825.15 | 143.65 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 14248.59 | 3562.15 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 14248.59 | 3562.15 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 20008.02 | 5002.01 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 20008.02 | 5002.01 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.29 | 2568.54 | 744.88 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.10 | 2568.54 | 256.85 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 125.92 | AstronomicalClock | - | 41.82 | 41.82 | 0.99 | |
EXTERIOR_LIGHTS_B | 6860.50 | AstronomicalClock | - | 83.82 | 71.22 | 91.72 | |
Exterior Lighting Total | 6986.42 | 92.71 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24330.07 | 18705.69 | 5624.38 | 0.77 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 75131.64 | 52673.29 | 22458.35 | 0.70 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 23402.3 | 11.86 | 11.59 | ||||
PSZ-FINE STORAGE COOLING COIL | 72779.9 | 11.12 | 10.87 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 39930.82 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28932.32 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 92891.20 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.19 | 1322.66 | 1107.16 | 1.00 | 1.36 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 3.03 | 3237.48 | 1070.05 | 1.00 | 1.26 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12084.58 | 14501.50 | 61.22 | 0.996 | 1.195 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 23.90 | 23.90 | 0.00860 | 32.35 | 0.01717 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 39256.38 | 47107.66 | 33.81 | 2.521 | 3.026 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.70 | 0.00925 | 33.13 | 0.01717 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 0.00 | 34.06 | 0.01724 | 33.20 | 0.01717 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 6334.98 | 7601.98 | 32.09 | 0.178 | 0.213 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00818 | 8.70 | 0.00699 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 12065.33 | 14478.40 | 10.39 | 0.286 | 0.425 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00750 | 8.70 | 0.00699 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 20842.04 | 25010.45 | 7.80 | 0.510 | 0.977 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00721 | 8.70 | 0.00699 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.19 | 1.19 | 0.21 | 0.21 | 1.1946 | 1.1946 | 1.1946 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.03 | 3.03 | 0.42 | 0.42 | 3.0256 | 3.0256 | 3.0256 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 39930.817 | 39930.817 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 39930.82 | 39930.82 | 0.976836 | 10.00 | 9.53 | 0.00720739 | 43.33 | 22.13 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 10.00 | 0.00720739 | 94.3968 | 25010.45 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 24330.070 | 18705.688 | 1.194650 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 12165.03 | 9930.60 | 0.796433 | 25.53 | 17.61 | 0.00933701 | 12.00 | 11.25 | 0.00800000 | 32.44 | 0.01716576 | 25.13 | 12.8428 | 23.90 | 0.00860381 | 46.5383 | 12082.36 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28932.321 | 28932.321 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28932.32 | 28932.32 | 1.194646 | 19.96 | 14.52 | 0.00807626 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 8.5619 | 21.10 | 0.00817771 | 52.4646 | 6334.98 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 75131.640 | 52673.290 | 3.025550 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37565.82 | 28190.28 | 2.017033 | 28.48 | 19.39 | 0.01036346 | 12.00 | 11.25 | 0.00800000 | 33.20 | 0.01716721 | 25.32 | 21.0562 | 26.70 | 0.00925164 | 42.3274 | 39232.71 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 92891.202 | 92891.202 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 92891.20 | 92891.20 | 3.025551 | 14.60 | 11.75 | 0.00742585 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 14.0375 | 15.56 | 0.00749656 | 68.1684 | 11821.24 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 39930.817 | 39930.817 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.976836 | 1.17487860 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 39930.82 | 39930.82 | 1.0000 | 1.17487860 | 0.976836 | 10.00 | 9.53 | 0.00720739 | 28207.4 | 43.33 | 22.13 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39930.82 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 10.00 | 0.00720739 | 10.00 | 0.00720739 | 94.3968 | 25010.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24330.070 | 18705.688 | 1.194650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1970 | 1004.8586 | 1.2027 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.194646 | 1.43684786 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | Sensible | 12165.03 | 9930.60 | 1.0000 | 0.95790138 | 0.796433 | 25.53 | 17.61 | 0.00933701 | 49447.6 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12165.03 | 32.44 | 0.01716576 | 25.13 | 0.10228463 | 12.8428 | 23.90 | 0.00860381 | 23.90 | 0.00860381 | 46.5383 | 12082.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28932.321 | 28932.321 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.194646 | 1.43684786 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 28932.32 | 28932.32 | 1.0000 | 1.43684786 | 1.194646 | 19.96 | 14.52 | 0.00807626 | 40555.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28932.32 | 8.70 | 0.00699286 | 8.70 | 0.10228463 | 8.5619 | 21.02 | 0.00817771 | 21.10 | 0.00817771 | 52.4646 | 6334.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 75131.640 | 52673.290 | 3.025550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1052 | 1004.8586 | 1.2027 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.025551 | 3.63894798 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 37565.82 | 28190.28 | 1.0000 | 2.42596452 | 2.017033 | 28.48 | 19.39 | 0.01036346 | 55082.4 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37565.82 | 33.20 | 0.01716721 | 25.32 | 0.42471127 | 21.0562 | 26.70 | 0.00925164 | 26.70 | 0.00925164 | 42.3274 | 39232.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 92891.202 | 92891.202 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.025551 | 3.63894798 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 92891.20 | 92891.20 | 1.0000 | 3.63894798 | 3.025551 | 14.60 | 11.75 | 0.00742585 | 33440.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92891.20 | 8.70 | 0.00699286 | 8.70 | 0.42471127 | 14.0375 | 15.56 | 0.00749656 | 15.56 | 0.00749656 | 68.1684 | 11821.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3209.33 | 737.33 | 510.00 |
ZONE2 FINE STORAGE | 3390.33 | 3181.00 | 2995.50 |
ZONE3 BULK STORAGE | 3373.67 | 3328.33 | 3117.00 |
Facility | 3411.83 | 3387.00 | 3140.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 67.00 | 0.00 | 64.83 |
ZONE2 FINE STORAGE | 0.00 | 201.83 | 0.00 | 0.67 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 268.83 | 0.00 | 65.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.351 | 0.424 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.492 | 0.251 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 0.000 | 0.160 | 0.000 | 1.386 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.56 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1262970.31 | 0.00 | 1262970.31 | 2211417.14 | 3474387.45 | 3225648.14 | 5389.36 | 3370.64 | 0.00 | 36.83 |
ZONE2 FINE STORAGE | 5598288.74 | 0.00 | 5598288.74 | 6521899.17 | 12120187.90 | 13393694.68 | 5409.88 | 3350.12 | 0.00 | 1265.53 |
ZONE3 BULK STORAGE | 0.00 | 0.26E+09 | 0.26E+09 | 38196385.74 | 0.30E+09 | 30805497.77 | 6481.91 | 41.56 | 2236.54 | 4868.49 |
Total Facility | 6861259.04 | 0.26E+09 | 0.27E+09 | 46929702.05 | 0.32E+09 | 47424840.58 | 7295.69 | 3401.98 | 2236.54 | 4902.31 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0963 | 0.0000 | 0.0963 | 0.1163 | 0.2126 | 0.1023 | 265.36 | 3370.64 | 0.00 |
ZONE2 FINE STORAGE | 0.3899 | 0.0000 | 0.3899 | 0.1990 | 0.5890 | 0.4247 | 302.42 | 3333.58 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 12.8308 | 12.8308 | 1.5043 | 14.3351 | 0.9768 | 2167.12 | 27.69 | 1441.18 |
Total Facility | 0.4862 | 12.8308 | 13.3170 | 1.8197 | 15.1367 | 1.5038 | 2171.69 | 3371.58 | 1441.18 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1826993.52 | 0.00 | 1826993.52 | 3225648.14 | 5372.78 | 1.14 | 3386.08 | 35.86 |
PSZ-FINE STORAGE | 8098389.67 | 0.00 | 8098389.67 | 13393694.68 | 5373.36 | 5.76 | 3380.88 | 1264.30 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1393 | 0.0000 | 0.1393 | 0.1023 | 249.92 | 0.97 | 3385.10 |
PSZ-FINE STORAGE | 0.5641 | 0.0000 | 0.5641 | 0.4247 | 302.09 | 0.08 | 3333.83 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3561.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 4627.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1437 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6098 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 429 |
Defaulted Fields | 391 |
Fields with Defaults | 1171 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 549.73 | 1936.85 | 23-APR-14:00 | 42157.75 | 09-JUN-15:50 |
Electricity:Building | 296.46 | 1443.59 | 23-APR-15:50 | 25624.07 | 07-NOV-15:50 |
Electricity:Zone:ZONE1 OFFICE | 50.71 | 694.23 | 19-FEB-16:10 | 3408.44 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 280.16 | 1443.59 | 23-APR-15:40 | 24347.90 | 29-DEC-09:10 |
InteriorLights:Electricity | 143.65 | 973.71 | 23-APR-15:40 | 14312.73 | 29-DEC-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 21.54 | 224.35 | 19-FEB-16:10 | 1573.38 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 143.65 | 973.71 | 23-APR-15:40 | 14312.73 | 29-DEC-09:10 |
LightsWired:InteriorLights:Electricity | 143.65 | 973.71 | 23-APR-15:40 | 14312.73 | 29-DEC-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 21.54 | 224.35 | 19-FEB-16:10 | 1573.38 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 143.65 | 973.71 | 23-APR-15:40 | 14312.73 | 29-DEC-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 55.00 | 311.69 | 01-JAN-12:00 | 5298.77 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 55.00 | 311.69 | 01-JAN-12:00 | 5298.77 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 55.00 | 311.69 | 01-JAN-12:00 | 5298.77 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 190.75 | 437.68 | 01-JAN-10:40 | 17325.95 | 07-NOV-15:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 67.11 | 437.68 | 01-JAN-10:40 | 7440.58 | 29-DEC-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 67.11 | 437.68 | 01-JAN-10:40 | 7440.58 | 29-DEC-09:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 41.64 | 0.00 | 01-JAN-00:10 | 4899.75 | 27-JUL-16:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 16.30 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-APR-10:40 |
Ventilation (simple):Fans:Electricity | 16.30 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-APR-10:40 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 16.30 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-APR-10:40 |
ElectricityPurchased:Facility | 549.73 | 1936.85 | 23-APR-14:00 | 42157.75 | 09-JUN-15:50 |
ElectricityPurchased:Plant | 549.73 | 1936.85 | 23-APR-14:00 | 42157.75 | 09-JUN-15:50 |
Cogeneration:ElectricityPurchased | 549.73 | 1936.85 | 23-APR-14:00 | 42157.75 | 09-JUN-15:50 |
General:Cogeneration:ElectricityPurchased | 549.73 | 1936.85 | 23-APR-14:00 | 42157.75 | 09-JUN-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 549.73 | 1936.85 | 23-APR-14:00 | 42157.75 | 09-JUN-15:50 |
ElectricityNet:Plant | 549.73 | 1936.85 | 23-APR-14:00 | 42157.75 | 09-JUN-15:50 |
Cogeneration:ElectricityNet | 549.73 | 1936.85 | 23-APR-14:00 | 42157.75 | 09-JUN-15:50 |
General:Cogeneration:ElectricityNet | 549.73 | 1936.85 | 23-APR-14:00 | 42157.75 | 09-JUN-15:50 |
Electricity:HVAC | 137.83 | 0.00 | 01-JAN-00:10 | 20813.32 | 27-JUL-16:10 |
General:Fans:Electricity | 25.34 | 0.00 | 01-JAN-00:10 | 2594.45 | 27-JUL-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 112.48 | 0.00 | 01-JAN-00:10 | 18218.87 | 27-JUL-16:10 |
General:Cooling:Electricity | 112.48 | 0.00 | 01-JAN-00:10 | 18218.87 | 27-JUL-16:10 |
ExteriorLights:Electricity | 92.71 | 0.00 | 01-JAN-07:20 | 6986.42 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.71 | 0.00 | 01-JAN-07:20 | 6986.42 | 01-JAN-06:10 |
Electricity:Plant | 22.73 | 481.00 | 27-MAR-05:10 | 1739.24 | 18-JAN-12:40 |
WaterSystems:Electricity | 22.73 | 481.00 | 27-MAR-05:10 | 1739.24 | 18-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 22.73 | 481.00 | 27-MAR-05:10 | 1739.24 | 18-JAN-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.14 | 0.00 | 01-JAN-00:10 | 7951.38 | 16-MAR-06:20 |
NaturalGas:HVAC | 0.14 | 0.00 | 01-JAN-00:10 | 7951.38 | 16-MAR-06:20 |
Heating:NaturalGas | 0.14 | 0.00 | 01-JAN-00:10 | 7951.38 | 16-MAR-06:20 |
General:Heating:NaturalGas | 0.14 | 0.00 | 01-JAN-00:10 | 7951.38 | 16-MAR-06:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-APR-11:50 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-APR-11:50 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-APR-11:50 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-APR-11:50 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-APR-11:50 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-APR-11:50 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-APR-11:50 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-APR-11:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 697.53 | 0.00 | 01-JAN-00:10 | 104247.10 | 27-JUL-16:10 |
EnergyTransfer:Building | 258.49 | 0.00 | 01-JAN-00:10 | 39004.74 | 27-JUL-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 82.40 | 0.00 | 01-JAN-00:10 | 13512.45 | 18-SEP-05:10 |
Heating:EnergyTransfer | 0.14 | 0.00 | 01-JAN-00:10 | 4205.88 | 16-MAR-06:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.07 | 0.00 | 01-JAN-00:10 | 4205.88 | 16-MAR-06:20 |
General:Heating:EnergyTransfer | 0.14 | 0.00 | 01-JAN-00:10 | 4205.88 | 16-MAR-06:20 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.07 | 0.00 | 01-JAN-00:10 | 4205.88 | 16-MAR-06:20 |
Cooling:EnergyTransfer | 258.35 | 0.00 | 01-JAN-00:10 | 39004.74 | 27-JUL-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 82.34 | 0.00 | 01-JAN-00:10 | 13512.45 | 18-SEP-05:10 |
General:Cooling:EnergyTransfer | 258.35 | 0.00 | 01-JAN-00:10 | 39004.74 | 27-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 82.34 | 0.00 | 01-JAN-00:10 | 13512.45 | 18-SEP-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 176.09 | 0.00 | 01-JAN-00:10 | 29046.69 | 29-JUL-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.07 | 0.00 | 01-JAN-00:10 | 1145.12 | 23-JAN-17:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.07 | 0.00 | 01-JAN-00:10 | 1145.12 | 23-JAN-17:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 176.01 | 0.00 | 01-JAN-00:10 | 29046.69 | 29-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 176.01 | 0.00 | 01-JAN-00:10 | 29046.69 | 29-JUL-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 439.04 | 0.00 | 01-JAN-00:10 | 65242.35 | 27-JUL-16:10 |
HeatingCoils:EnergyTransfer | 0.09 | 0.00 | 01-JAN-00:10 | 5322.94 | 16-MAR-06:20 |
CoolingCoils:EnergyTransfer | 438.95 | 0.00 | 01-JAN-00:10 | 65242.35 | 27-JUL-16:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.065 | -82.335 | 0.000 | 0.000 | 9.130 | 21.542 | 29.165 | 11.237 | 0.000 | 5.059 | 15.057 | 0.000 | -3.883 | 0.000 | -5.037 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.072 | -176.004 | 0.000 | 0.000 | 17.578 | 54.996 | 0.000 | 41.237 | 0.000 | 5.470 | 85.222 | 0.000 | -9.276 | 0.000 | -19.295 | -0.001 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.698 | 67.111 | 107.344 | 694.223 | 0.000 | 0.427 | 0.005 | 0.000 | -151.246 | 0.000 | -532.483 | -216.074 |
Total Facility | 0.000 | 0.000 | 0.138 | -258.339 | 0.000 | 0.000 | 57.406 | 143.649 | 136.508 | 746.697 | 0.000 | 10.956 | 100.284 | 0.000 | -164.405 | 0.000 | -556.815 | -216.075 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | -22952.87 | 0.00 | 0.00 | 87.82 | 469.96 | 550.52 | 0.00 | 0.00 | 0.00 | 23157.42 | 0.00 | -558.40 | 0.00 | -754.46 | 0.00 |
ZONE2 FINE STORAGE | 16-APR-15:53 | 0.00 | 0.00 | 0.00 | -61901.91 | 0.00 | 0.00 | 0.00 | 467.53 | 0.00 | 2687.09 | 0.00 | 533.13 | 58214.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-JUL-05:01 | 0.00 | 0.00 | 0.00 | -70104.35 | 0.00 | 0.00 | 555.17 | 1968.69 | 2600.55 | 0.00 | 0.00 | 0.00 | 80220.60 | 0.00 | -10937.47 | 0.00 | -4303.20 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 25-JAN-07:10 | 0.00 | 0.00 | 4520.62 | 0.00 | 0.00 | 0.00 | 220.43 | 858.20 | 917.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -649.87 | 0.00 | -5072.40 | -794.51 |
ZONE2 FINE STORAGE | 02-OCT-06:10 | 0.00 | 0.00 | 1383.21 | 0.00 | 0.00 | 0.00 | 341.47 | 3740.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -315.16 | 0.00 | -8.17 | -5141.60 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-JAN-07:10 | -3855.62 | 3855.62 | 4520.62 | -3855.62 | 0.00 | 0.00 | 2132.36 | 9850.56 | 2967.56 | 0.00 | 0.00 | 0.00 | 62733.57 | 0.00 | -47249.74 | 0.00 | -31099.31 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1946 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1946 | 0.0856 | 1.0000 | Not calculated | 0.1023 | 0.0856 | ||
PSZ-FINE STORAGE | 3.0256 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.0256 | 0.1404 | 1.0000 | Not calculated | 0.4247 | 0.1404 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1946 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1946 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0856 | ||
PSZ-FINE STORAGE | 3.0256 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.0256 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1404 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1946 | 1.1946 | 1.1946 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.0256 | 3.0256 | 3.0256 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1946 | 1.1946 | 1.1946 | 1.1946 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.0256 | 3.0256 | 3.0256 | 3.0256 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1946 | 1.1946 | 1.1946 | No | 0.1023 | 0.4794 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.0256 | 3.0256 | 3.0256 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1946 | 1.1946 | 1.1946 | 1.1946 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.0256 | 3.0256 | 3.0256 | 3.0256 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 65.50 |
Number of hours not met | 65.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.14 | 7951.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 112.48 | 18218.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 143.65 | 14312.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.71 | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 16.30 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 25.34 | 2594.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.73 | 1739.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 549.73 |
Natural Gas | 0.00 | 0.14 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 549.87 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 29.71 |
Space Heating | 0.00 |
Space Cooling | 23.26 |
Fans (All) | 8.61 |
Service Water Heating | 4.70 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 113.69 |
Subtotal | 113.69 |
Natural Gas [MJ/m2] | |
Space Heating | 0.03 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.03 |
Subtotal | 0.03 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 26.12 |
Space Heating | 0.03 |
Space Cooling | 20.46 |
Fans (All) | 7.57 |
Service Water Heating | 4.13 |
Receptacle Equipment | 24.83 |
Miscellaneous | 16.86 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 5133.17 | 3504.50 | 122.33 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 2690.33 | 6069.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2252.50 | 3345.67 | 3161.00 | 0.83 | 0.00 |
Min | 2252.50 | 3345.67 | 0.00 | 0.00 | 0.00 |
Max | 5133.17 | 6069.67 | 3161.00 | 0.83 | 0.00 |
Average | 3358.67 | 4306.61 | 1094.44 | 0.28 | 0.00 |
Sum | 10076.00 | 12919.83 | 3283.33 | 0.83 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33026.67 | 0.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 15596.00 | 67123.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 31471.00 | 74847.83 | 84816.67 | 57.50 | 0.00 |
Min | 15596.00 | 0.33 | 0.00 | 0.00 | 0.00 |
Max | 33026.67 | 74847.83 | 84816.67 | 57.50 | 0.00 |
Average | 26697.89 | 47323.72 | 28272.22 | 19.17 | 0.00 |
Sum | 80093.67 | 141971.17 | 84816.67 | 57.50 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 3889.00 | 4866.50 | 4.50 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 1449.50 | 7310.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1393.33 | 5792.00 | 1574.67 | 0.00 | 0.00 |
Min | 1393.33 | 4866.50 | 0.00 | 0.00 | 0.00 |
Max | 3889.00 | 7310.50 | 1574.67 | 0.00 | 0.00 |
Average | 2243.94 | 5989.67 | 526.39 | 0.00 | 0.00 |
Sum | 6731.83 | 17969.00 | 1579.17 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 30652.50 | 2374.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 10775.50 | 71943.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 23247.17 | 115778.50 | 52167.33 | 0.00 | 0.00 |
Min | 10775.50 | 2374.50 | 0.00 | 0.00 | 0.00 |
Max | 30652.50 | 115778.50 | 52167.33 | 0.00 | 0.00 |
Average | 21558.39 | 63365.50 | 17389.11 | 0.00 | 0.00 |
Sum | 64675.17 | 190096.50 | 52167.33 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.386893E+10 | 18114.96 | 19-JAN-06:03 | 18.30 | 16.26 | 0.630690E+09 | 769.04 | 04-JAN-15:00 | 18.30 | 16.26 |
February | 0.415489E+10 | 21720.05 | 28-FEB-06:02 | 16.88 | 13.54 | 0.581313E+09 | 769.04 | 13-FEB-13:50 | 16.88 | 13.54 |
March | 0.542874E+10 | 19094.72 | 03-MAR-06:02 | 21.10 | 16.96 | 0.682461E+09 | 769.04 | 14-MAR-12:00 | 23.30 | 19.97 |
April | 0.683952E+10 | 22952.83 | 19-APR-05:02 | 15.10 | 11.88 | 0.635060E+09 | 769.07 | 15-APR-15:50 | 15.10 | 11.88 |
May | 0.830252E+10 | 19643.79 | 08-MAY-05:01 | 23.90 | 19.12 | 0.660611E+09 | 769.07 | 18-MAY-14:30 | 30.85 | 23.00 |
June | 0.863645E+10 | 17210.39 | 14-JUN-05:01 | 24.22 | 22.42 | 0.660689E+09 | 769.07 | 03-JUN-14:50 | 24.22 | 22.42 |
July | 0.889122E+10 | 17434.79 | 06-JUL-05:01 | 23.90 | 22.23 | 0.635310E+09 | 769.07 | 08-JUL-14:20 | 31.50 | 25.19 |
August | 0.932762E+10 | 18046.93 | 30-AUG-05:01 | 24.90 | 22.92 | 0.686141E+09 | 769.07 | 29-AUG-15:30 | 24.90 | 22.92 |
September | 0.849207E+10 | 17353.66 | 06-SEP-05:01 | 22.88 | 22.46 | 0.635296E+09 | 769.07 | 09-SEP-13:39 | 31.30 | 25.48 |
October | 0.789944E+10 | 20504.52 | 18-OCT-05:01 | 24.50 | 18.64 | 0.635237E+09 | 769.07 | 10-OCT-10:00 | 24.50 | 18.64 |
November | 0.613548E+10 | 18787.86 | 07-NOV-06:01 | 20.10 | 19.76 | 0.609046E+09 | 769.05 | 10-NOV-13:30 | 28.05 | 24.05 |
December | 0.436077E+10 | 21383.11 | 12-DEC-06:02 | 12.02 | 9.57 | 0.631669E+09 | 769.04 | 14-DEC-15:39 | 21.67 | 18.17 |
Annual Sum or Average | 0.823377E+11 | 0.768352E+10 | ||||||||
Minimum of Months | 0.386893E+10 | 17210.39 | 12.02 | 9.57 | 0.581313E+09 | 769.04 | 15.10 | 11.88 | ||
Maximum of Months | 0.932762E+10 | 22952.83 | 24.90 | 22.92 | 0.686141E+09 | 769.07 | 31.50 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323195E+10 | 26122.10 | 01-JAN-13:45 | 26.28 | 21.78 | 0.171098E+10 | 2246.82 | 09-JAN-16:49 | 20.78 | 13.08 |
February | 0.411772E+10 | 51704.38 | 19-FEB-14:33 | 27.20 | 21.86 | 0.160902E+10 | 2246.90 | 21-FEB-13:30 | 25.00 | 14.70 |
March | 0.711779E+10 | 53403.03 | 26-MAR-14:23 | 27.80 | 22.07 | 0.191608E+10 | 2246.90 | 11-MAR-14:30 | 27.80 | 22.07 |
April | 0.136848E+11 | 61901.07 | 16-APR-15:53 | 30.60 | 20.93 | 0.184897E+10 | 2246.98 | 07-APR-15:20 | 30.60 | 20.93 |
May | 0.198162E+11 | 56161.71 | 21-MAY-15:33 | 27.97 | 21.66 | 0.192840E+10 | 2246.97 | 04-MAY-14:39 | 27.97 | 21.66 |
June | 0.228317E+11 | 56682.15 | 11-JUN-11:23 | 31.10 | 23.40 | 0.192904E+10 | 2246.97 | 16-JUN-13:09 | 29.90 | 23.62 |
July | 0.265911E+11 | 57270.52 | 16-JUL-12:32 | 30.93 | 24.10 | 0.185478E+10 | 2247.05 | 28-JUL-14:00 | 35.00 | 25.27 |
August | 0.241864E+11 | 54682.84 | 20-AUG-17:03 | 30.50 | 24.78 | 0.200314E+10 | 2247.01 | 16-AUG-15:00 | 30.50 | 24.78 |
September | 0.228991E+11 | 57273.75 | 03-SEP-13:53 | 24.40 | 21.27 | 0.185477E+10 | 2246.98 | 20-SEP-14:09 | 32.12 | 25.35 |
October | 0.175688E+11 | 57954.41 | 15-OCT-16:33 | 28.50 | 20.76 | 0.185441E+10 | 2246.98 | 23-OCT-14:39 | 28.50 | 23.12 |
November | 0.892972E+10 | 51299.58 | 05-NOV-15:23 | 27.80 | 23.97 | 0.175964E+10 | 2246.98 | 10-NOV-14:20 | 28.90 | 24.19 |
December | 0.503871E+10 | 52299.62 | 10-DEC-15:23 | 28.60 | 22.59 | 0.171822E+10 | 2246.87 | 13-DEC-15:50 | 21.20 | 14.95 |
Annual Sum or Average | 0.176014E+12 | 0.219875E+11 | ||||||||
Minimum of Months | 0.323195E+10 | 26122.10 | 24.40 | 20.76 | 0.160902E+10 | 2246.82 | 20.78 | 13.08 | ||
Maximum of Months | 0.265911E+11 | 61901.07 | 31.10 | 24.78 | 0.200314E+10 | 2247.05 | 35.00 | 25.35 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 | 0.401443E+10 | 6360.30 | 02-JAN-13:00 | 28.90 | 24.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 | 0.387978E+10 | 6346.60 | 22-FEB-14:30 | 27.50 | 14.21 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 | 13.44 | 0.479960E+10 | 6361.38 | 28-MAR-14:20 | 27.03 | 20.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 | 18.63 | 0.503742E+10 | 7608.30 | 17-APR-15:20 | 32.03 | 19.94 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 20.01 | 0.554947E+10 | 8461.46 | 22-MAY-13:20 | 34.23 | 23.41 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 | 24.42 | 0.567066E+10 | 7579.86 | 10-JUN-15:30 | 31.70 | 24.28 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 | 23.72 | 0.577759E+10 | 9045.05 | 29-JUL-15:00 | 35.60 | 24.39 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 | 25.82 | 0.605725E+10 | 8401.19 | 23-AUG-13:09 | 33.62 | 25.44 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 | 24.00 | 0.551133E+10 | 7776.41 | 13-SEP-14:09 | 32.12 | 24.21 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 | 23.96 | 0.526388E+10 | 7642.78 | 14-OCT-13:30 | 31.95 | 24.19 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 | 21.03 | 0.461283E+10 | 6588.18 | 03-NOV-13:39 | 29.40 | 24.36 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 | 21.22 | 0.412824E+10 | 6389.49 | 02-DEC-13:00 | 26.70 | 20.63 |
Annual Sum or Average | 0.00 | 0.603025E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 16.65 | 13.10 | 0.387978E+10 | 6346.60 | 26.70 | 14.21 | ||
Maximum of Months | 0.00 | 0.00 | 28.60 | 25.82 | 0.605725E+10 | 9045.05 | 35.60 | 25.44 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18148115.35 | 4520.85 | 25-JAN-07:10 | 9.50 |
February | 6879806.41 | 2066.28 | 04-FEB-07:05 | 5.28 |
March | 19797283.37 | 4326.65 | 16-MAR-06:10 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 180605.28 | 150.04 | 28-NOV-07:10 | 20.68 |
December | 20137667.26 | 4403.88 | 15-DEC-07:10 | 7.88 |
Annual Sum or Average | 65143477.67 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 20137667.26 | 4520.85 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9321136.84 | 1145.12 | 23-JAN-17:10 | 26.32 |
February | 27184753.56 | 941.86 | 07-FEB-12:30 | 25.85 |
March | 79943.72 | 112.40 | 23-MAR-06:05 | 21.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 1162423.11 | 715.44 | 31-MAY-06:10 | 25.28 |
June | 1075124.08 | 1134.05 | 07-JUN-06:10 | 26.20 |
July | 618500.43 | 1172.22 | 15-JUL-06:10 | 26.20 |
August | 974135.42 | 927.15 | 09-AUG-06:10 | 26.28 |
September | 322424.15 | 250.11 | 15-SEP-06:10 | 24.40 |
October | 1285225.59 | 1383.15 | 02-OCT-06:10 | 26.70 |
November | 3395929.48 | 511.08 | 30-NOV-07:10 | 25.60 |
December | 26943134.56 | 670.92 | 22-DEC-12:30 | 25.00 |
Annual Sum or Average | 72362730.93 | |||
Minimum of Months | 0.00 | 0.00 | 21.70 | |
Maximum of Months | 27184753.56 | 1383.15 | 26.70 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.189425E+10 | 1573.38 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.167378E+10 | 1573.38 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.187351E+10 | 1573.38 | 01-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.175554E+10 | 1573.38 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.180617E+10 | 1573.38 | 06-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.177678E+10 | 1573.38 | 03-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.172965E+10 | 1573.38 | 05-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.181487E+10 | 1573.38 | 03-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.175336E+10 | 1573.38 | 02-SEP-09:09 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.180602E+10 | 1573.38 | 02-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.178006E+10 | 1573.38 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.187843E+10 | 1573.38 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.215424E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.167378E+10 | 1573.38 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.189425E+10 | 1573.38 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.508953E+10 | 5298.77 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.441564E+10 | 5298.77 | 07-FEB-09:09 | 0.00 | 0.00 |
March | 0.491300E+10 | 5298.77 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.436935E+10 | 5298.77 | 03-APR-08:09 | 0.00 | 0.00 |
May | 0.447579E+10 | 5298.77 | 02-MAY-08:09 | 0.00 | 0.00 |
June | 0.438353E+10 | 5298.77 | 03-JUN-08:09 | 0.00 | 0.00 |
July | 0.419697E+10 | 4857.20 | 05-JUL-08:09 | 0.00 | 0.00 |
August | 0.444341E+10 | 4857.20 | 02-AUG-08:09 | 0.00 | 0.00 |
September | 0.429350E+10 | 5298.77 | 26-SEP-08:09 | 0.00 | 0.00 |
October | 0.466681E+10 | 5298.77 | 05-OCT-08:09 | 0.00 | 0.00 |
November | 0.464339E+10 | 5298.77 | 02-NOV-08:09 | 0.00 | 0.00 |
December | 0.510491E+10 | 5298.77 | 01-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.549958E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.419697E+10 | 4857.20 | 0.00 | 0.00 | |
Maximum of Months | 0.510491E+10 | 5298.77 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.617197E+10 | 6820.53 | 09-JAN-15:30 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.541129E+10 | 6565.03 | 07-FEB-08:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.597939E+10 | 6565.03 | 01-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.528721E+10 | 6565.03 | 12-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.539258E+10 | 5580.44 | 17-MAY-14:00 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.530496E+10 | 6565.03 | 03-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.512371E+10 | 5470.86 | 05-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.548604E+10 | 6565.03 | 28-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.529953E+10 | 6565.03 | 27-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.569549E+10 | 6565.03 | 06-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.572366E+10 | 6820.53 | 07-NOV-15:39 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.623486E+10 | 7440.58 | 29-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.671107E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.512371E+10 | 5470.86 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.623486E+10 | 7440.58 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.189425E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53014680.68 | 0.932818E+09 |
February | 0.127628E+10 | 0.167378E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114017E+09 | 0.780034E+09 |
March | 0.149825E+10 | 0.187351E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129840E+09 | 0.894867E+09 |
April | 0.138726E+10 | 0.175554E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282832E+09 | 0.407869E+09 |
May | 0.144276E+10 | 0.180617E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643334E+09 | 0.208197E+09 |
June | 0.144276E+10 | 0.177678E+10 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697451E+09 | 66930022.09 |
July | 0.138726E+10 | 0.172965E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771157E+09 | 68925496.07 |
August | 0.149825E+10 | 0.181487E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841709E+09 | 54915744.57 |
September | 0.138726E+10 | 0.175336E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654374E+09 | 69451397.18 |
October | 0.138726E+10 | 0.180602E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520832E+09 | 0.153839E+09 |
November | 0.133177E+10 | 0.178006E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287026E+09 | 0.486290E+09 |
December | 0.138726E+10 | 0.187843E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63320777.16 | 0.913019E+09 |
Annual Sum or Average | 0.168137E+11 | 0.215424E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505891E+10 | 0.503716E+10 |
Minimum of Months | 0.127628E+10 | 0.167378E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53014680.68 | 54915744.57 |
Maximum of Months | 0.149825E+10 | 0.189425E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841709E+09 | 0.932818E+09 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.508953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9386274.68 | 0.277219E+10 |
February | 0.300332E+10 | 0.441564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15760489.63 | 0.334472E+10 |
March | 0.352563E+10 | 0.491300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37862490.11 | 0.365837E+10 |
April | 0.326447E+10 | 0.436935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174582E+09 | 0.201375E+10 |
May | 0.339505E+10 | 0.447579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683715E+09 | 0.948703E+09 |
June | 0.339505E+10 | 0.438353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.922001E+09 | 0.275422E+09 |
July | 0.326447E+10 | 0.419697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.980707E+09 | 0.201880E+09 |
August | 0.352563E+10 | 0.444341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108996E+10 | 0.195659E+09 |
September | 0.326447E+10 | 0.429350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985969E+09 | 0.295003E+09 |
October | 0.326447E+10 | 0.466681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472307E+09 | 0.646551E+09 |
November | 0.313390E+10 | 0.464339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78783853.53 | 0.210146E+10 |
December | 0.326447E+10 | 0.510491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18706815.77 | 0.284116E+10 |
Annual Sum or Average | 0.395654E+11 | 0.549958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546975E+10 | 0.192949E+11 |
Minimum of Months | 0.300332E+10 | 0.419697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9386274.68 | 0.195659E+09 |
Maximum of Months | 0.352563E+10 | 0.510491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108996E+10 | 0.365837E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.617197E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21467357.88 | 0.154507E+11 |
February | 0.690763E+10 | 0.541129E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25727639.36 | 0.180564E+11 |
March | 0.810895E+10 | 0.597939E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238388E+11 |
April | 0.750829E+10 | 0.528721E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171243E+11 |
May | 0.780862E+10 | 0.539258E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9168579.16 | 0.122339E+11 |
June | 0.780862E+10 | 0.530496E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649407E+10 |
July | 0.750829E+10 | 0.512371E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1909349.75 | 0.468824E+10 |
August | 0.810895E+10 | 0.548604E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 552485.34 | 0.531165E+10 |
September | 0.750829E+10 | 0.529953E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 427175.87 | 0.561470E+10 |
October | 0.750829E+10 | 0.569549E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 861841.87 | 0.851952E+10 |
November | 0.720796E+10 | 0.572366E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144226E+11 |
December | 0.750829E+10 | 0.623486E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14462102.14 | 0.162506E+11 |
Annual Sum or Average | 0.910005E+11 | 0.671107E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 74576531.37 | 0.148005E+12 |
Minimum of Months | 0.690763E+10 | 0.512371E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468824E+10 |
Maximum of Months | 0.810895E+10 | 0.623486E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25727639.36 | 0.238388E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1573.38 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.09 | 02-JAN-12:10 | 5096.32 | 25-JAN-07:05 |
February | 1680.92 | 01-FEB-08:09 | 1573.38 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1520.37 | 02-FEB-13:00 | 5362.13 | 03-FEB-07:03 |
March | 1680.92 | 01-MAR-08:09 | 1573.38 | 01-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2362.25 | 13-MAR-16:50 | 6733.64 | 16-MAR-06:03 |
April | 1680.92 | 01-APR-07:10 | 1573.38 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3005.12 | 17-APR-17:00 | 3305.00 | 19-APR-06:05 |
May | 1680.92 | 01-MAY-07:10 | 1573.38 | 06-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3916.87 | 22-MAY-16:10 | 1142.78 | 01-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1573.38 | 03-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2946.52 | 09-JUN-16:10 | 404.19 | 18-JUN-20:00 |
July | 1680.92 | 01-JUL-07:10 | 1573.38 | 05-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4529.71 | 27-JUL-16:10 | 419.96 | 14-JUL-16:55 |
August | 1680.92 | 01-AUG-07:10 | 1573.38 | 03-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3412.96 | 23-AUG-12:00 | 628.65 | 28-AUG-12:00 |
September | 1680.92 | 01-SEP-07:10 | 1573.38 | 02-SEP-09:09 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3396.17 | 18-SEP-16:10 | 588.94 | 05-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 1573.38 | 02-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3159.52 | 03-OCT-16:10 | 857.97 | 31-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1573.38 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1844.77 | 03-NOV-16:05 | 5318.15 | 27-NOV-07:03 |
December | 1680.92 | 01-DEC-08:09 | 1573.38 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.19 | 08-DEC-13:00 | 6122.10 | 15-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1573.38 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.09 | 404.19 | |||||
Maximum of Months | 1680.92 | 1573.38 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 4529.71 | 6733.64 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 5298.77 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.26 | 07-JAN-13:00 | 6582.96 | 24-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 5298.77 | 07-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.29 | 02-FEB-14:00 | 7800.57 | 03-FEB-09:00 |
March | 3955.50 | 01-MAR-08:09 | 5298.77 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1740.71 | 13-MAR-17:00 | 8204.15 | 15-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 5298.77 | 03-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2837.83 | 15-APR-17:00 | 4029.72 | 18-APR-08:00 |
May | 3955.50 | 01-MAY-07:10 | 5298.77 | 02-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4590.30 | 22-MAY-15:20 | 3096.15 | 10-MAY-15:10 |
June | 3955.50 | 01-JUN-07:10 | 5298.77 | 03-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2396.57 | 08-JUN-16:00 | 1893.79 | 18-JUN-20:00 |
July | 3955.50 | 01-JUL-07:10 | 4857.20 | 05-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3973.78 | 27-JUL-16:00 | 1552.33 | 02-JUL-15:50 |
August | 3955.50 | 01-AUG-07:10 | 4857.20 | 02-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3069.73 | 16-AUG-16:00 | 2143.21 | 12-AUG-08:00 |
September | 3955.50 | 01-SEP-07:10 | 5298.77 | 26-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3067.41 | 18-SEP-16:00 | 1341.00 | 19-SEP-23:10 |
October | 3955.50 | 02-OCT-07:10 | 5298.77 | 05-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3023.78 | 03-OCT-15:10 | 2213.44 | 16-OCT-07:00 |
November | 3955.50 | 01-NOV-07:10 | 5298.77 | 02-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.47 | 03-NOV-16:00 | 7706.26 | 11-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 5298.77 | 01-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1261.49 | 10-DEC-14:47 | 7164.23 | 27-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 4857.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.26 | 1341.00 | ||||
Maximum of Months | 3955.50 | 5298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4590.30 | 8204.15 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 6820.53 | 09-JAN-15:30 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1659.61 | 29-JAN-13:00 | 30565.79 | 24-JAN-09:00 |
February | 9097.65 | 01-FEB-08:09 | 6565.03 | 07-FEB-08:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2393.34 | 08-FEB-13:10 | 35133.15 | 03-FEB-09:00 |
March | 9097.65 | 01-MAR-08:09 | 6565.03 | 01-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 41720.09 | 15-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 6565.03 | 12-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 26957.40 | 18-APR-09:00 |
May | 9097.65 | 01-MAY-07:10 | 5580.44 | 17-MAY-14:00 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1547.93 | 29-MAY-12:53 | 28731.64 | 10-MAY-15:00 |
June | 9097.65 | 01-JUN-07:10 | 6565.03 | 03-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 20957.00 | 22-JUN-09:00 |
July | 9097.65 | 01-JUL-07:10 | 5470.86 | 05-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 655.32 | 31-JUL-17:55 | 14112.88 | 14-JUL-14:55 |
August | 9097.65 | 01-AUG-07:10 | 6565.03 | 28-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 809.08 | 07-AUG-14:55 | 15527.98 | 12-AUG-08:00 |
September | 9097.65 | 01-SEP-07:10 | 6565.03 | 27-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 396.01 | 07-SEP-17:55 | 13463.81 | 02-SEP-12:10 |
October | 9097.65 | 02-OCT-07:10 | 6565.03 | 06-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 591.53 | 09-OCT-10:45 | 16420.22 | 10-OCT-13:00 |
November | 9097.65 | 01-NOV-07:10 | 6820.53 | 07-NOV-15:39 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 36630.38 | 11-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 7440.58 | 29-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1086.19 | 24-DEC-11:00 | 30302.86 | 27-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 5470.86 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13463.81 | |||||
Maximum of Months | 9097.65 | 7440.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 2393.34 | 41720.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18114.96 | 19-JAN-06:03 | 739.61 | 1879.86 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.37 |
February | 21720.05 | 28-FEB-06:02 | 924.51 | 2349.82 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.46 |
March | 19094.72 | 03-MAR-06:02 | 924.51 | 2349.82 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.44 |
April | 22952.83 | 19-APR-05:02 | 1109.41 | 2819.79 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 754.46 |
May | 19643.79 | 08-MAY-05:01 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.49 |
June | 17210.39 | 14-JUN-05:01 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.97 |
July | 17434.79 | 06-JUL-05:01 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.25 |
August | 18046.93 | 30-AUG-05:01 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.32 |
September | 17353.66 | 06-SEP-05:01 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.07 |
October | 20504.52 | 18-OCT-05:01 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.82 |
November | 18787.86 | 07-NOV-06:01 | 1664.11 | 4229.68 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.01 |
December | 21383.11 | 12-DEC-06:02 | 924.51 | 2349.82 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 956.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17210.39 | 739.61 | 1879.86 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.97 | |
Maximum of Months | 22952.83 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 956.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26122.10 | 01-JAN-13:45 | 0.00 | 831.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.69 |
February | 51704.38 | 19-FEB-14:33 | 0.00 | 1558.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.56 | 0.00 |
March | 53403.03 | 26-MAR-14:23 | 0.00 | 935.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.75 | 0.00 |
April | 61901.07 | 16-APR-15:53 | 0.00 | 1870.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.13 | 0.00 |
May | 56161.71 | 21-MAY-15:33 | 0.00 | 1402.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.42 | 0.00 |
June | 56682.15 | 11-JUN-11:23 | 0.00 | 1454.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1074.77 | 0.00 |
July | 57270.52 | 16-JUL-12:32 | 0.00 | 1246.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.94 | 0.00 |
August | 54682.84 | 20-AUG-17:03 | 0.00 | 2285.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 848.82 | 0.00 |
September | 57273.75 | 03-SEP-13:53 | 0.00 | 935.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 699.16 |
October | 57954.41 | 15-OCT-16:33 | 0.00 | 1714.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.67 | 0.00 |
November | 51299.58 | 05-NOV-15:23 | 0.00 | 1558.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.23 | 0.00 |
December | 52299.62 | 10-DEC-15:23 | 0.00 | 1558.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 786.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26122.10 | 0.00 | 831.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 61901.07 | 0.00 | 2285.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1074.77 | 699.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 875.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7443.86 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6366.34 |
April | 0.00 | 01-APR-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6849.22 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4970.53 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2563.35 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1125.70 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 850.98 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 1750.70 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2351.12 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 1750.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1145.17 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6553.21 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2852.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 875.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1750.70 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7443.86 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.394614E+11 | 35616.21 | 02-JAN-14:20 | 38025329.43 | 6531.30 | 25-JAN-07:19 |
February | 0.360349E+11 | 35088.52 | 11-FEB-14:20 | 17534023.39 | 3662.85 | 03-FEB-07:00 |
March | 0.414515E+11 | 35447.26 | 27-MAR-14:00 | 41550108.48 | 7951.38 | 16-MAR-06:19 |
April | 0.424056E+11 | 38528.49 | 15-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.485066E+11 | 39690.90 | 17-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.512340E+11 | 42157.75 | 09-JUN-15:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.531636E+11 | 42111.16 | 27-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.542800E+11 | 40485.65 | 17-AUG-15:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.515232E+11 | 40758.53 | 18-SEP-15:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.488477E+11 | 39792.19 | 25-OCT-14:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.421251E+11 | 39389.45 | 07-NOV-15:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.406949E+11 | 36765.74 | 08-DEC-15:50 | 43035181.78 | 7033.08 | 15-DEC-07:19 |
Annual Sum or Average | 0.549728E+12 | 0.140145E+09 | ||||
Minimum of Months | 0.360349E+11 | 35088.52 | 0.00 | 0.00 | ||
Maximum of Months | 0.542800E+11 | 42157.75 | 43035181.78 | 7951.38 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.131557E+11 | 0.902556E+10 | 0.112984E+11 | 0.00 | 0.183774E+10 | 0.00 | 0.00 | 0.217085E+10 | 0.00 | 0.00 | 0.00 | 0.197316E+10 | 0.00 |
February | 0.115007E+11 | 0.772928E+10 | 0.103734E+11 | 0.00 | 0.171525E+10 | 0.00 | 0.00 | 0.292941E+10 | 0.00 | 0.00 | 0.00 | 0.178682E+10 | 0.00 |
March | 0.127659E+11 | 0.798598E+10 | 0.121089E+11 | 0.00 | 0.207730E+10 | 0.00 | 0.00 | 0.452168E+10 | 0.00 | 0.00 | 0.00 | 0.199171E+10 | 0.00 |
April | 0.114121E+11 | 0.716964E+10 | 0.112578E+11 | 0.00 | 0.270128E+10 | 0.00 | 0.00 | 0.799069E+10 | 0.00 | 0.00 | 0.00 | 0.187410E+10 | 0.00 |
May | 0.116745E+11 | 0.690448E+10 | 0.117000E+11 | 0.00 | 0.401014E+10 | 0.00 | 0.00 | 0.123070E+11 | 0.00 | 0.00 | 0.00 | 0.191051E+10 | 0.00 |
June | 0.114653E+11 | 0.645283E+10 | 0.116594E+11 | 0.00 | 0.517801E+10 | 0.00 | 0.00 | 0.146357E+11 | 0.00 | 0.00 | 0.00 | 0.184277E+10 | 0.00 |
July | 0.110503E+11 | 0.674100E+10 | 0.112984E+11 | 0.00 | 0.574061E+10 | 0.00 | 0.00 | 0.164743E+11 | 0.00 | 0.00 | 0.00 | 0.185895E+10 | 0.00 |
August | 0.117443E+11 | 0.718534E+10 | 0.121016E+11 | 0.00 | 0.548075E+10 | 0.00 | 0.00 | 0.158653E+11 | 0.00 | 0.00 | 0.00 | 0.190273E+10 | 0.00 |
September | 0.113464E+11 | 0.749241E+10 | 0.112504E+11 | 0.00 | 0.507045E+10 | 0.00 | 0.00 | 0.145233E+11 | 0.00 | 0.00 | 0.00 | 0.184026E+10 | 0.00 |
October | 0.121683E+11 | 0.832133E+10 | 0.113057E+11 | 0.00 | 0.376043E+10 | 0.00 | 0.00 | 0.113792E+11 | 0.00 | 0.00 | 0.00 | 0.191269E+10 | 0.00 |
November | 0.121471E+11 | 0.856971E+10 | 0.108562E+11 | 0.00 | 0.216543E+10 | 0.00 | 0.00 | 0.651221E+10 | 0.00 | 0.00 | 0.00 | 0.187445E+10 | 0.00 |
December | 0.132182E+11 | 0.913455E+10 | 0.112984E+11 | 0.00 | 0.190708E+10 | 0.00 | 0.00 | 0.317203E+10 | 0.00 | 0.00 | 0.00 | 0.196469E+10 | 0.00 |
Annual Sum or Average | 0.143649E+12 | 0.927121E+11 | 0.136508E+12 | 0.00 | 0.416445E+11 | 0.00 | 0.00 | 0.112482E+12 | 0.00 | 0.00 | 0.00 | 0.227328E+11 | 0.00 |
Minimum of Months | 0.110503E+11 | 0.645283E+10 | 0.103734E+11 | 0.00 | 0.171525E+10 | 0.00 | 0.00 | 0.217085E+10 | 0.00 | 0.00 | 0.00 | 0.178682E+10 | 0.00 |
Maximum of Months | 0.132182E+11 | 0.913455E+10 | 0.121089E+11 | 0.00 | 0.574061E+10 | 0.00 | 0.00 | 0.164743E+11 | 0.00 | 0.00 | 0.00 | 0.199171E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 38025329.43 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 17534023.39 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 41550108.48 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 43035181.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.140145E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 43035181.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 13488.14 | 09-JAN-15:30 | 6986.42 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 4129.35 | 02-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 13072.63 | 07-FEB-09:09 | 6986.42 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 4129.35 | 11-FEB-12:39 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 13072.63 | 01-MAR-09:09 | 6986.42 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 4170.92 | 13-MAR-16:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 12813.66 | 12-APR-07:10 | 6986.42 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 4318.18 | 13-APR-11:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 11719.49 | 06-MAY-07:10 | 6986.42 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 4454.75 | 22-MAY-11:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 13072.63 | 15-JUN-08:09 | 6986.42 | 01-JUN-05:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 4530.47 | 08-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 11719.49 | 05-JUL-07:10 | 6986.42 | 01-JUL-05:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 4899.75 | 27-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 12813.66 | 28-AUG-07:10 | 6986.42 | 01-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4651.21 | 16-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 13072.63 | 27-SEP-08:09 | 6986.42 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 4575.48 | 18-SEP-15:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 13072.63 | 06-OCT-08:09 | 6986.42 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 4499.02 | 03-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 13283.60 | 07-NOV-15:39 | 6986.42 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 4235.98 | 03-NOV-11:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 14312.73 | 29-DEC-09:09 | 6986.42 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 4129.35 | 08-DEC-13:39 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 11719.49 | 6986.42 | 10035.17 | 0.00 | 4129.35 | 0.00 | 0.00 | |||||
Maximum of Months | 14312.73 | 6986.42 | 10035.17 | 0.00 | 4899.75 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 10007.79 | 02-JAN-14:39 | 0.00 | 0.00 | 0.00 | 1739.24 | 18-JAN-12:39 | 0.00 |
February | 10158.82 | 11-FEB-14:30 | 0.00 | 0.00 | 0.00 | 1738.51 | 01-FEB-12:39 | 0.00 |
March | 10720.43 | 27-MAR-15:09 | 0.00 | 0.00 | 0.00 | 1733.19 | 01-MAR-12:20 | 0.00 |
April | 14000.87 | 15-APR-15:00 | 0.00 | 0.00 | 0.00 | 1723.00 | 01-APR-11:20 | 0.00 |
May | 15213.66 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1711.43 | 01-MAY-11:39 | 0.00 |
June | 16031.23 | 08-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1700.80 | 01-JUN-11:30 | 0.00 |
July | 18218.87 | 27-JUL-16:10 | 0.00 | 0.00 | 0.00 | 1694.70 | 01-JUL-11:30 | 0.00 |
August | 16705.50 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1699.23 | 31-AUG-11:30 | 0.00 |
September | 16283.36 | 18-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1708.89 | 30-SEP-11:20 | 0.00 |
October | 14864.95 | 03-OCT-11:39 | 0.00 | 0.00 | 0.00 | 1720.73 | 31-OCT-11:30 | 0.00 |
November | 12166.96 | 10-NOV-13:00 | 0.00 | 0.00 | 0.00 | 1731.35 | 30-NOV-12:00 | 0.00 |
December | 10125.56 | 08-DEC-14:20 | 0.00 | 0.00 | 0.00 | 1737.92 | 30-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10007.79 | 0.00 | 0.00 | 0.00 | 1694.70 | 0.00 | ||
Maximum of Months | 18218.87 | 0.00 | 0.00 | 0.00 | 1739.24 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 35616.21 | 02-JAN-14:20 | 9972.73 | 10035.17 | 0.00 | 0.00 | 4129.35 | 0.00 | 0.00 | 9796.65 | 0.00 |
February | 35088.52 | 11-FEB-14:20 | 9089.60 | 10035.17 | 0.00 | 0.00 | 4129.35 | 0.00 | 0.00 | 10152.89 | 0.00 |
March | 35447.26 | 27-MAR-14:00 | 8885.06 | 10035.17 | 0.00 | 0.00 | 4129.35 | 0.00 | 0.00 | 10699.76 | 0.00 |
April | 38528.49 | 15-APR-15:00 | 9779.58 | 10035.17 | 0.00 | 0.00 | 4231.87 | 0.00 | 0.00 | 14000.87 | 0.00 |
May | 39690.90 | 17-MAY-15:00 | 9984.12 | 10035.17 | 0.00 | 0.00 | 4288.33 | 0.00 | 0.00 | 13804.99 | 0.00 |
June | 42157.75 | 09-JUN-15:50 | 10373.72 | 10035.17 | 0.00 | 0.00 | 4497.85 | 0.00 | 0.00 | 15674.50 | 0.00 |
July | 42111.16 | 27-JUL-15:00 | 7516.59 | 10035.17 | 0.00 | 0.00 | 4839.12 | 0.00 | 0.00 | 18145.05 | 0.00 |
August | 40485.65 | 17-AUG-15:39 | 7906.20 | 10035.17 | 0.00 | 0.00 | 4594.45 | 0.00 | 0.00 | 16373.92 | 0.00 |
September | 40758.53 | 18-SEP-15:50 | 8295.80 | 10035.17 | 0.00 | 0.00 | 4575.48 | 0.00 | 0.00 | 16274.06 | 0.00 |
October | 39792.19 | 25-OCT-14:30 | 11212.82 | 10035.17 | 0.00 | 0.00 | 4183.67 | 0.00 | 0.00 | 12667.45 | 0.00 |
November | 39389.45 | 07-NOV-15:50 | 13283.60 | 10035.17 | 0.00 | 0.00 | 4129.35 | 0.00 | 0.00 | 10244.02 | 0.00 |
December | 36765.74 | 08-DEC-15:50 | 13336.05 | 10035.17 | 0.00 | 0.00 | 1824.06 | 0.00 | 0.00 | 9865.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 35088.52 | 7516.59 | 10035.17 | 0.00 | 0.00 | 1824.06 | 0.00 | 0.00 | 9796.65 | 0.00 | |
Maximum of Months | 42157.75 | 13336.05 | 10035.17 | 0.00 | 0.00 | 4839.12 | 0.00 | 0.00 | 18145.05 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 6531.30 | 25-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 3662.85 | 03-FEB-07:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 7951.38 | 16-MAR-06:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 7033.08 | 15-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 7951.38 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.53 | 0.17 | 24.53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.53 | 2.00 | 24.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.62 | 5.17 | 24.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.90 | 8.17 | 24.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 25.00 | 8.00 | 25.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 25.53 | 8.50 | 25.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 25.35 | 9.17 | 25.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 25.34 | 8.50 | 25.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 24.98 | 8.50 | 24.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.68 | 4.50 | 24.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.63 | 2.00 | 24.63 |
Annual Sum or Average | 0.00 | 0.00 | 67.00 | 25.08 | 64.83 | 25.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 25.53 | 9.17 | 25.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.28 | 0.00 | 27.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.39 | 0.00 | 27.39 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.36 | 0.00 | 27.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.46 | 0.00 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 27.44 | 0.00 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 27.45 | 0.00 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 | 27.56 | 0.50 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 27.46 | 0.17 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 27.51 | 0.00 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 27.44 | 0.00 | 27.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.35 | 0.00 | 27.35 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.43 | 0.00 | 27.43 |
Annual Sum or Average | 0.00 | 0.00 | 201.83 | 27.47 | 0.67 | 27.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.28 | 0.00 | 27.28 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 | 27.56 | 0.50 | 27.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 84.83 | 23.39 | 170.33 | 23.73 | 12.67 | 23.74 |
February | 70.50 | 23.50 | 199.17 | 23.78 | 24.33 | 23.77 |
March | 70.50 | 23.47 | 237.67 | 23.81 | 21.67 | 23.82 |
April | 12.67 | 24.09 | 295.17 | 23.92 | 12.67 | 23.93 |
May | 44.33 | 24.08 | 312.00 | 23.95 | 44.33 | 23.96 |
June | 73.83 | 24.06 | 312.00 | 23.96 | 73.83 | 23.98 |
July | 67.50 | 24.07 | 300.00 | 23.96 | 67.50 | 23.98 |
August | 79.00 | 24.06 | 324.00 | 23.97 | 79.00 | 23.98 |
September | 66.17 | 24.08 | 300.00 | 23.96 | 66.17 | 23.98 |
October | 51.17 | 24.05 | 300.00 | 23.95 | 51.17 | 23.96 |
November | 44.67 | 23.84 | 271.33 | 23.91 | 37.17 | 23.92 |
December | 72.17 | 23.43 | 187.67 | 23.77 | 19.50 | 23.78 |
Annual Sum or Average | 737.33 | 23.80 | 3209.33 | 23.90 | 510.00 | 23.92 |
Minimum of Months | 12.67 | 23.39 | 170.33 | 23.73 | 12.67 | 23.74 |
Maximum of Months | 84.83 | 24.09 | 324.00 | 23.97 | 79.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 177.00 | 25.02 | 226.83 | 25.58 | 122.00 | 25.69 |
February | 206.00 | 25.56 | 226.50 | 25.86 | 168.83 | 25.94 |
March | 246.17 | 25.92 | 276.17 | 26.19 | 207.83 | 26.29 |
April | 270.00 | 26.67 | 300.00 | 26.64 | 270.00 | 26.65 |
May | 310.17 | 26.71 | 312.00 | 26.70 | 310.17 | 26.70 |
June | 312.00 | 26.72 | 312.00 | 26.72 | 312.00 | 26.72 |
July | 300.00 | 26.72 | 300.00 | 26.72 | 300.00 | 26.72 |
August | 322.67 | 26.72 | 324.00 | 26.72 | 322.67 | 26.72 |
September | 299.83 | 26.72 | 300.00 | 26.72 | 299.83 | 26.72 |
October | 295.33 | 26.71 | 300.00 | 26.71 | 295.33 | 26.71 |
November | 246.50 | 26.48 | 277.83 | 26.52 | 238.67 | 26.55 |
December | 195.33 | 25.40 | 235.00 | 25.78 | 148.17 | 25.91 |
Annual Sum or Average | 3181.00 | 26.38 | 3390.33 | 26.46 | 2995.50 | 26.51 |
Minimum of Months | 177.00 | 25.02 | 226.50 | 25.58 | 122.00 | 25.69 |
Maximum of Months | 322.67 | 26.72 | 324.00 | 26.72 | 322.67 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 198.67 | 25.27 | 220.67 | 25.84 | 135.50 | 26.02 |
February | 241.50 | 26.17 | 223.17 | 26.47 | 197.00 | 26.62 |
March | 262.50 | 27.15 | 280.83 | 27.35 | 227.00 | 27.52 |
April | 287.67 | 28.94 | 300.00 | 28.88 | 287.67 | 28.90 |
May | 312.00 | 29.71 | 312.00 | 29.71 | 312.00 | 29.71 |
June | 312.00 | 30.12 | 312.00 | 30.12 | 312.00 | 30.12 |
July | 300.00 | 30.94 | 300.00 | 30.94 | 300.00 | 30.94 |
August | 324.00 | 30.51 | 324.00 | 30.51 | 324.00 | 30.51 |
September | 300.00 | 30.25 | 300.00 | 30.25 | 300.00 | 30.25 |
October | 300.00 | 29.52 | 300.00 | 29.52 | 300.00 | 29.52 |
November | 262.00 | 28.26 | 277.00 | 28.25 | 253.17 | 28.32 |
December | 228.00 | 26.03 | 224.00 | 26.41 | 168.67 | 26.64 |
Annual Sum or Average | 3328.33 | 28.81 | 3373.67 | 28.90 | 3117.00 | 29.01 |
Minimum of Months | 198.67 | 25.27 | 220.67 | 25.84 | 135.50 | 26.02 |
Maximum of Months | 324.00 | 30.94 | 324.00 | 30.94 | 324.00 | 30.94 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.545992E+10 | 0.127839E+10 | 251.10 | 0.404683E+10 | 0.141309E+10 | 0.00 | 1.00 | 02-JAN-06:01 | 0.00 | 01-JAN-00:10 | 30503.13 | 07-JAN-06:01 | 20145.61 | 19-JAN-06:03 | 14893.52 | 07-JAN-06:04 | 6289.80 | 07-JAN-06:01 | 0.00 | 01-JAN-00:10 |
February | 0.606839E+10 | 0.141878E+10 | 239.57 | 0.455352E+10 | 0.151486E+10 | 0.00 | 1.00 | 02-FEB-06:03 | 0.00 | 01-FEB-00:10 | 30590.07 | 11-FEB-06:02 | 23631.89 | 28-FEB-06:02 | 14987.63 | 11-FEB-06:03 | 6300.68 | 11-FEB-06:02 | 0.00 | 01-FEB-00:10 |
March | 0.803162E+10 | 0.185092E+10 | 288.63 | 0.584071E+10 | 0.219091E+10 | 0.00 | 1.00 | 03-MAR-06:02 | 0.00 | 01-MAR-00:10 | 31107.39 | 06-MAR-06:01 | 21288.65 | 03-MAR-06:02 | 15574.35 | 06-MAR-06:04 | 6359.48 | 06-MAR-06:01 | 0.00 | 01-MAR-00:10 |
April | 0.102941E+11 | 0.238051E+10 | 293.42 | 0.759004E+10 | 0.270401E+10 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 30852.28 | 13-APR-05:01 | 24432.48 | 19-APR-05:02 | 14076.94 | 13-APR-05:06 | 6356.39 | 13-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.136967E+11 | 0.318128E+10 | 309.64 | 0.943715E+10 | 0.425960E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 31663.96 | 30-MAY-05:02 | 21200.09 | 08-MAY-05:01 | 17102.30 | 27-MAY-05:04 | 6439.61 | 27-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.152859E+11 | 0.353420E+10 | 310.75 | 0.990430E+10 | 0.538160E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 31614.40 | 19-JUN-05:01 | 18667.62 | 14-JUN-05:01 | 16380.80 | 19-JUN-05:03 | 6556.29 | 08-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.156597E+11 | 0.369938E+10 | 305.61 | 0.103384E+11 | 0.532133E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 31453.77 | 24-JUL-05:01 | 18833.71 | 06-JUL-05:01 | 15064.17 | 31-JUL-05:06 | 6499.94 | 10-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.166164E+11 | 0.388502E+10 | 326.05 | 0.107751E+11 | 0.584134E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 31752.59 | 14-AUG-05:01 | 19619.84 | 30-AUG-05:01 | 16864.41 | 28-AUG-05:06 | 6544.22 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.148718E+11 | 0.345373E+10 | 304.80 | 0.973862E+10 | 0.513315E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:05 | 31487.75 | 20-SEP-05:01 | 18653.10 | 06-SEP-05:01 | 16511.69 | 23-SEP-05:06 | 6536.33 | 22-SEP-05:01 | 0.00 | 01-SEP-00:05 |
October | 0.132610E+11 | 0.306340E+10 | 297.85 | 0.897251E+10 | 0.428850E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:05 | 31377.95 | 05-OCT-05:01 | 22183.70 | 18-OCT-05:01 | 17775.17 | 30-OCT-05:07 | 6511.24 | 30-OCT-05:01 | 0.00 | 01-OCT-00:05 |
November | 0.100265E+11 | 0.229813E+10 | 274.82 | 0.683518E+10 | 0.319129E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 31441.44 | 24-NOV-06:01 | 20262.79 | 28-NOV-06:02 | 17334.15 | 30-NOV-06:04 | 6464.89 | 30-NOV-06:01 | 0.00 | 01-NOV-00:10 |
December | 0.629019E+10 | 0.145940E+10 | 259.22 | 0.460474E+10 | 0.168545E+10 | 0.00 | 1.00 | 01-DEC-06:01 | 0.00 | 01-DEC-00:10 | 31206.96 | 11-DEC-06:01 | 22666.39 | 12-DEC-06:02 | 15416.80 | 26-DEC-06:01 | 6381.63 | 09-DEC-06:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.135562E+12 | 0.315031E+11 | 3461.47 | 0.926371E+11 | 0.429251E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.545992E+10 | 0.127839E+10 | 239.57 | 0.404683E+10 | 0.141309E+10 | 0.00 | 1.00 | 0.00 | 30503.13 | 18653.10 | 14076.94 | 6289.80 | 0.00 | |||||||
Maximum of Months | 0.166164E+11 | 0.388502E+10 | 326.05 | 0.107751E+11 | 0.584134E+10 | 0.00 | 1.00 | 0.00 | 31752.59 | 24432.48 | 17775.17 | 6556.29 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.328836E+10 | 0.892463E+09 | 102.50 | 0.207557E+10 | 0.121279E+10 | 0.00 | 0.98 | 01-JAN-13:45 | 0.00 | 01-JAN-00:10 | 41467.66 | 01-JAN-13:45 | 28126.02 | 01-JAN-13:45 | 14489.52 | 01-JAN-11:10 | 10240.38 | 01-JAN-13:45 | 0.00 | 01-JAN-00:10 |
February | 0.552633E+10 | 0.151063E+10 | 157.92 | 0.390183E+10 | 0.162450E+10 | 0.00 | 1.00 | 19-FEB-14:33 | 0.00 | 01-FEB-00:10 | 86130.88 | 19-FEB-14:33 | 57078.45 | 19-FEB-14:33 | 29052.43 | 19-FEB-14:33 | 21299.41 | 19-FEB-14:33 | 0.00 | 01-FEB-00:10 |
March | 0.100047E+11 | 0.267076E+10 | 209.99 | 0.651664E+10 | 0.348805E+10 | 0.00 | 1.00 | 05-MAR-11:10 | 0.00 | 01-MAR-00:10 | 85798.88 | 26-MAR-13:43 | 58997.79 | 26-MAR-14:23 | 28229.19 | 26-MAR-13:43 | 21382.78 | 26-MAR-13:43 | 0.00 | 01-MAR-00:10 |
April | 0.209831E+11 | 0.561018E+10 | 313.82 | 0.145242E+11 | 0.645896E+10 | 0.00 | 1.00 | 01-APR-17:08 | 0.00 | 01-APR-00:10 | 85977.21 | 13-APR-17:06 | 67715.35 | 09-APR-12:23 | 29850.95 | 01-APR-17:08 | 21654.08 | 15-APR-17:06 | 0.00 | 01-APR-00:10 |
May | 0.341643E+11 | 0.912569E+10 | 420.45 | 0.221711E+11 | 0.119932E+11 | 0.00 | 1.00 | 01-MAY-17:08 | 0.00 | 01-MAY-00:10 | 89773.06 | 20-MAY-05:10 | 62209.38 | 21-MAY-15:33 | 37131.28 | 20-MAY-05:10 | 22518.40 | 29-MAY-11:03 | 0.00 | 01-MAY-00:10 |
June | 0.418173E+11 | 0.111015E+11 | 487.67 | 0.257821E+11 | 0.160352E+11 | 0.00 | 1.00 | 01-JUN-17:08 | 0.00 | 01-JUN-00:10 | 91024.95 | 08-JUN-05:08 | 63129.00 | 11-JUN-13:23 | 41995.31 | 08-JUN-05:08 | 22246.72 | 08-JUN-05:08 | 0.00 | 01-JUN-00:10 |
July | 0.475647E+11 | 0.127749E+11 | 520.98 | 0.304093E+11 | 0.171553E+11 | 0.00 | 1.00 | 01-JUL-13:10 | 0.00 | 01-JUL-00:15 | 90712.45 | 27-JUL-05:08 | 62831.27 | 16-JUL-13:13 | 38826.07 | 15-JUL-05:01 | 22543.21 | 27-JUL-17:06 | 0.00 | 01-JUL-00:10 |
August | 0.449561E+11 | 0.119803E+11 | 513.90 | 0.276385E+11 | 0.173176E+11 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:15 | 90662.92 | 05-AUG-05:01 | 62427.87 | 06-AUG-13:13 | 39826.62 | 18-AUG-05:07 | 22544.15 | 20-AUG-11:43 | 0.00 | 01-AUG-00:10 |
September | 0.415884E+11 | 0.110696E+11 | 478.89 | 0.258701E+11 | 0.157183E+11 | 0.00 | 1.00 | 01-SEP-13:40 | 0.00 | 01-SEP-00:15 | 90708.85 | 23-SEP-05:06 | 63253.89 | 04-SEP-10:53 | 40458.90 | 22-SEP-05:06 | 22335.93 | 18-SEP-17:43 | 0.00 | 01-SEP-00:05 |
October | 0.312102E+11 | 0.831582E+10 | 403.64 | 0.197247E+11 | 0.114855E+11 | 0.00 | 1.00 | 01-OCT-10:45 | 0.00 | 01-OCT-00:15 | 94851.60 | 04-OCT-05:06 | 64515.49 | 15-OCT-16:33 | 49235.10 | 04-OCT-05:06 | 22379.78 | 29-OCT-11:13 | 0.00 | 01-OCT-00:05 |
November | 0.158588E+11 | 0.421409E+10 | 258.12 | 0.962269E+10 | 0.623613E+10 | 0.00 | 1.00 | 01-NOV-17:10 | 0.00 | 01-NOV-00:10 | 88953.67 | 23-NOV-13:23 | 56938.77 | 05-NOV-15:23 | 35513.36 | 23-NOV-13:23 | 21706.50 | 23-NOV-13:23 | 0.00 | 01-NOV-00:10 |
December | 0.642642E+10 | 0.171263E+10 | 129.86 | 0.413469E+10 | 0.229174E+10 | 0.00 | 1.00 | 10-DEC-09:23 | 0.00 | 01-DEC-00:10 | 87383.18 | 10-DEC-12:43 | 58232.49 | 10-DEC-15:23 | 32674.21 | 10-DEC-12:43 | 21750.64 | 10-DEC-12:43 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.303389E+12 | 0.809785E+11 | 3997.74 | 0.192371E+12 | 0.111017E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.328836E+10 | 0.892463E+09 | 102.50 | 0.207557E+10 | 0.121279E+10 | 0.00 | 0.98 | 0.00 | 41467.66 | 28126.02 | 14489.52 | 10240.38 | 0.00 | |||||||
Maximum of Months | 0.475647E+11 | 0.127749E+11 | 520.98 | 0.304093E+11 | 0.173176E+11 | 0.00 | 1.00 | 0.00 | 94851.60 | 67715.35 | 49235.10 | 22544.15 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.51 | 26.65 | 34.86 | 84.22 | 72.76 | 0.00 | 0.00 | 0.00 |
February | 76.78 | 34.86 | 41.91 | 118.35 | 60.35 | 0.00 | 0.00 | 0.00 |
March | 95.57 | 43.72 | 51.85 | 146.88 | 52.99 | 0.00 | 0.00 | 0.00 |
April | 104.67 | 48.35 | 56.32 | 173.63 | 40.99 | 0.00 | 0.00 | 0.00 |
May | 95.85 | 37.00 | 58.84 | 172.84 | 26.12 | 0.00 | 0.00 | 0.00 |
June | 81.16 | 22.81 | 58.36 | 153.16 | 15.72 | 0.00 | 0.00 | 0.00 |
July | 90.64 | 28.09 | 62.54 | 176.60 | 20.37 | 0.00 | 0.00 | 0.00 |
August | 90.36 | 29.40 | 60.96 | 168.48 | 18.01 | 0.00 | 0.00 | 0.00 |
September | 77.05 | 22.74 | 54.31 | 146.68 | 21.42 | 0.00 | 0.00 | 0.00 |
October | 76.62 | 29.88 | 46.74 | 136.33 | 31.68 | 0.00 | 0.00 | 0.00 |
November | 63.14 | 23.10 | 40.04 | 102.27 | 45.64 | 0.00 | 0.00 | 0.00 |
December | 63.47 | 28.44 | 35.03 | 92.43 | 63.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.44 | 31.25 | 50.19 | 139.44 | 39.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 61.51 | 22.74 | 34.86 | 84.22 | 15.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.67 | 48.35 | 62.54 | 176.60 | 72.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.51 | 26.65 | 34.86 | 84.22 | 72.76 | 0.00 | 0.00 | 0.00 |
February | 76.78 | 34.86 | 41.91 | 118.35 | 60.35 | 0.00 | 0.00 | 0.00 |
March | 95.57 | 43.72 | 51.85 | 146.88 | 52.99 | 0.00 | 0.00 | 0.00 |
April | 104.67 | 48.35 | 56.32 | 173.63 | 40.99 | 0.00 | 0.00 | 0.00 |
May | 95.85 | 37.00 | 58.84 | 172.84 | 26.12 | 0.00 | 0.00 | 0.00 |
June | 81.16 | 22.81 | 58.36 | 153.16 | 15.72 | 0.00 | 0.00 | 0.00 |
July | 90.64 | 28.09 | 62.54 | 176.60 | 20.37 | 0.00 | 0.00 | 0.00 |
August | 90.36 | 29.40 | 60.96 | 168.48 | 18.01 | 0.00 | 0.00 | 0.00 |
September | 77.05 | 22.74 | 54.31 | 146.68 | 21.42 | 0.00 | 0.00 | 0.00 |
October | 76.62 | 29.88 | 46.74 | 136.33 | 31.68 | 0.00 | 0.00 | 0.00 |
November | 63.14 | 23.10 | 40.04 | 102.27 | 45.64 | 0.00 | 0.00 | 0.00 |
December | 63.47 | 28.44 | 35.03 | 92.43 | 63.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.44 | 31.25 | 50.19 | 139.44 | 39.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 61.51 | 22.74 | 34.86 | 84.22 | 15.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.67 | 48.35 | 62.54 | 176.60 | 72.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.50 | 0.00 | 16.50 | 15.05 | 43.80 | 0.00 | 0.00 | 0.00 |
February | 19.53 | 0.00 | 19.53 | 23.56 | 35.91 | 0.00 | 0.00 | 0.00 |
March | 23.30 | 0.00 | 23.30 | 27.98 | 31.74 | 0.00 | 0.00 | 0.00 |
April | 26.16 | 0.15 | 26.02 | 38.43 | 24.06 | 0.00 | 0.00 | 0.00 |
May | 29.70 | 1.19 | 28.50 | 53.70 | 14.81 | 0.00 | 0.00 | 0.00 |
June | 31.79 | 2.22 | 29.57 | 61.76 | 8.60 | 0.00 | 0.00 | 0.00 |
July | 32.15 | 1.49 | 30.66 | 65.68 | 11.62 | 0.00 | 0.00 | 0.00 |
August | 28.61 | 0.32 | 28.28 | 54.65 | 10.30 | 0.00 | 0.00 | 0.00 |
September | 25.31 | 0.01 | 25.30 | 49.37 | 12.31 | 0.00 | 0.00 | 0.00 |
October | 21.19 | 0.00 | 21.19 | 36.72 | 18.40 | 0.00 | 0.00 | 0.00 |
November | 18.43 | 0.00 | 18.43 | 25.77 | 26.75 | 0.00 | 0.00 | 0.00 |
December | 16.32 | 0.00 | 16.32 | 16.91 | 38.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.11 | 0.45 | 23.66 | 39.21 | 23.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.32 | 0.00 | 16.32 | 15.05 | 8.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.15 | 2.22 | 30.66 | 65.68 | 43.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.50 | 0.00 | 16.50 | 15.05 | 43.80 | 0.00 | 0.00 | 0.00 |
February | 19.53 | 0.00 | 19.53 | 23.56 | 35.91 | 0.00 | 0.00 | 0.00 |
March | 23.30 | 0.00 | 23.30 | 27.98 | 31.74 | 0.00 | 0.00 | 0.00 |
April | 26.16 | 0.15 | 26.02 | 38.43 | 24.06 | 0.00 | 0.00 | 0.00 |
May | 29.70 | 1.19 | 28.50 | 53.70 | 14.81 | 0.00 | 0.00 | 0.00 |
June | 31.79 | 2.22 | 29.57 | 61.76 | 8.60 | 0.00 | 0.00 | 0.00 |
July | 32.15 | 1.49 | 30.65 | 65.68 | 11.62 | 0.00 | 0.00 | 0.00 |
August | 28.60 | 0.32 | 28.28 | 54.65 | 10.30 | 0.00 | 0.00 | 0.00 |
September | 25.31 | 0.01 | 25.30 | 49.37 | 12.31 | 0.00 | 0.00 | 0.00 |
October | 21.19 | 0.00 | 21.19 | 36.72 | 18.40 | 0.00 | 0.00 | 0.00 |
November | 18.43 | 0.00 | 18.43 | 25.77 | 26.75 | 0.00 | 0.00 | 0.00 |
December | 16.32 | 0.00 | 16.32 | 16.91 | 38.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.11 | 0.45 | 23.65 | 39.21 | 23.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.32 | 0.00 | 16.32 | 15.05 | 8.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.15 | 2.22 | 30.65 | 65.68 | 43.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.54 | 33.08 | 0.00 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 75.80 | 28.52 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 94.78 | 25.92 | 0.50 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 115.53 | 22.52 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 118.27 | 16.03 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 114.39 | 12.14 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 127.21 | 13.81 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 111.16 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 100.62 | 14.34 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 84.43 | 20.17 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 64.10 | 24.56 | 0.00 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.94 | 28.40 | 16.83 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 93.40 | 21.01 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.94 | 12.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 127.21 | 33.08 | 16.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.54 | 33.08 | 0.00 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 75.80 | 28.52 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 94.78 | 25.92 | 0.50 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 115.53 | 22.52 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 118.27 | 16.03 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 114.39 | 12.14 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 127.21 | 13.81 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 111.16 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 100.62 | 14.34 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 84.43 | 20.17 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 64.10 | 24.56 | 0.00 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.94 | 28.40 | 16.83 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 93.40 | 21.01 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.94 | 12.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 127.21 | 33.08 | 16.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.54 | 33.08 | 0.00 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 75.80 | 28.52 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 94.78 | 25.92 | 0.50 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 115.53 | 22.52 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 118.27 | 16.03 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 114.39 | 12.14 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 127.21 | 13.81 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 111.16 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 100.62 | 14.34 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 84.43 | 20.17 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 64.10 | 24.56 | 0.00 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.94 | 28.40 | 16.83 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 93.40 | 21.01 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.94 | 12.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 127.21 | 33.08 | 16.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.54 | 33.08 | 0.00 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 75.80 | 28.52 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 94.78 | 25.92 | 0.50 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 115.53 | 22.52 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 118.27 | 16.03 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 114.39 | 12.14 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 127.21 | 13.81 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 111.16 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 100.62 | 14.34 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 84.43 | 20.17 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 64.10 | 24.56 | 0.00 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.94 | 28.40 | 16.83 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 93.40 | 21.01 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.94 | 12.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 127.21 | 33.08 | 16.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.54 | 33.08 | 0.00 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 75.80 | 28.52 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 94.78 | 25.92 | 0.50 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 115.53 | 22.52 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 118.27 | 16.03 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 114.39 | 12.14 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 127.21 | 13.81 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 111.16 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 100.62 | 14.34 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 84.43 | 20.17 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 64.10 | 24.56 | 0.00 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.94 | 28.40 | 16.83 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 93.40 | 21.01 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.94 | 12.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 127.21 | 33.08 | 16.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.54 | 33.08 | 0.00 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 75.80 | 28.52 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 94.78 | 25.92 | 0.50 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 115.53 | 22.52 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 118.27 | 16.03 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 114.39 | 12.14 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 127.21 | 13.81 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 111.16 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 100.62 | 14.34 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 84.43 | 20.17 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 64.10 | 24.56 | 0.00 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.94 | 28.40 | 16.83 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 93.40 | 21.01 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.94 | 12.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 127.21 | 33.08 | 16.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.54 | 33.08 | 0.00 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 75.80 | 28.52 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 94.78 | 25.92 | 0.50 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 115.53 | 22.52 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 118.27 | 16.03 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 114.39 | 12.14 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 127.21 | 13.81 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 111.16 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 100.62 | 14.34 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 84.43 | 20.17 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 64.10 | 24.56 | 0.00 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.94 | 28.40 | 16.83 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 93.40 | 21.01 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.94 | 12.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 127.21 | 33.08 | 16.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.54 | 33.08 | 0.00 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 75.80 | 28.52 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 94.78 | 25.92 | 0.50 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 115.53 | 22.52 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 118.27 | 16.03 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 114.39 | 12.14 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 127.21 | 13.81 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 111.16 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 100.62 | 14.34 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 84.43 | 20.17 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 64.10 | 24.56 | 0.00 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.94 | 28.40 | 16.83 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 93.40 | 21.01 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.94 | 12.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 127.21 | 33.08 | 16.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.54 | 33.08 | 0.00 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 75.80 | 28.52 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 94.78 | 25.92 | 0.50 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 115.53 | 22.52 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 118.27 | 16.03 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 114.39 | 12.14 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 127.21 | 13.81 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 111.16 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 100.62 | 14.34 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 84.43 | 20.17 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 64.10 | 24.56 | 0.00 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.94 | 28.40 | 16.83 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 93.40 | 21.01 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.94 | 12.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 127.21 | 33.08 | 16.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.54 | 33.08 | 0.00 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 75.80 | 28.52 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 94.78 | 25.92 | 0.50 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 115.53 | 22.52 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 118.27 | 16.03 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 114.39 | 12.14 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 127.21 | 13.81 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 111.16 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 100.62 | 14.34 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 84.43 | 20.17 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 64.10 | 24.56 | 0.00 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.94 | 28.40 | 16.83 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 93.40 | 21.01 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.94 | 12.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 127.21 | 33.08 | 16.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.54 | 33.08 | 0.00 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 75.80 | 28.52 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 94.78 | 25.92 | 0.50 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 115.53 | 22.52 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 118.27 | 16.03 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 114.39 | 12.14 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 127.21 | 13.81 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 111.16 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 100.62 | 14.34 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 84.43 | 20.17 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 64.10 | 24.56 | 0.00 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.94 | 28.40 | 16.83 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 93.40 | 21.01 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.94 | 12.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 127.21 | 33.08 | 16.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.54 | 33.08 | 0.00 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 75.80 | 28.52 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 94.78 | 25.92 | 0.50 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 115.53 | 22.52 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 118.27 | 16.03 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 114.39 | 12.14 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 127.21 | 13.81 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 111.16 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 100.62 | 14.34 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 84.43 | 20.17 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 64.10 | 24.56 | 0.00 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.94 | 28.40 | 16.83 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 93.40 | 21.01 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.94 | 12.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 127.21 | 33.08 | 16.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.54 | 33.08 | 0.00 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 75.80 | 28.52 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 94.78 | 25.92 | 0.50 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 115.53 | 22.52 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 118.27 | 16.03 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 114.39 | 12.14 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 127.21 | 13.81 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 111.16 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 100.62 | 14.34 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 84.43 | 20.17 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 64.10 | 24.56 | 0.00 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.94 | 28.40 | 16.83 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 93.40 | 21.01 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.94 | 12.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 127.21 | 33.08 | 16.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.54 | 33.08 | 0.00 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 75.80 | 28.52 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 94.78 | 25.92 | 0.50 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 115.53 | 22.52 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 118.27 | 16.03 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 114.39 | 12.14 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 127.21 | 13.81 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 111.16 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 100.62 | 14.34 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 84.43 | 20.17 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 64.10 | 24.56 | 0.00 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.94 | 28.40 | 16.83 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 93.40 | 21.01 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.94 | 12.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 127.21 | 33.08 | 16.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.61 | 54.76 | 45.50 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 118.95 | 47.18 | 14.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.49 | 3.50 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.93 | 42.63 | 7.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.93 | 33.29 | 1.67 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.27 | 28.23 | 7.50 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 187.94 | 31.09 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.63 | 30.98 | 13.00 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 148.96 | 32.20 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.51 | 41.65 | 14.50 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.42 | 44.37 | 41.33 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.61 | 47.10 | 38.50 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.20 | 39.80 | 196.33 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.61 | 28.23 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 187.94 | 54.76 | 45.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164749E+09 | 71392666.40 | 93356002.58 | 0.225587E+09 | 0.194870E+09 |
February | 0.185738E+09 | 84338084.82 | 0.101400E+09 | 0.286309E+09 | 0.145987E+09 |
March | 0.255964E+09 | 0.117096E+09 | 0.138868E+09 | 0.393391E+09 | 0.141915E+09 |
April | 0.271300E+09 | 0.125316E+09 | 0.145984E+09 | 0.450041E+09 | 0.106236E+09 |
May | 0.256714E+09 | 99106069.09 | 0.157608E+09 | 0.462933E+09 | 69957019.19 |
June | 0.210375E+09 | 59111613.78 | 0.151263E+09 | 0.396991E+09 | 40742490.32 |
July | 0.242760E+09 | 75242658.89 | 0.167517E+09 | 0.472998E+09 | 54567670.28 |
August | 0.242021E+09 | 78738705.95 | 0.163282E+09 | 0.451249E+09 | 48227812.10 |
September | 0.199712E+09 | 58945310.18 | 0.140766E+09 | 0.380196E+09 | 55527657.39 |
October | 0.205221E+09 | 80021493.34 | 0.125200E+09 | 0.365146E+09 | 84856260.41 |
November | 0.163672E+09 | 59878912.06 | 0.103793E+09 | 0.265096E+09 | 0.118301E+09 |
December | 0.169989E+09 | 76169279.17 | 93820015.02 | 0.247559E+09 | 0.170339E+09 |
Annual Sum or Average | 0.256821E+10 | 0.985357E+09 | 0.158286E+10 | 0.439750E+10 | 0.123153E+10 |
Minimum of Months | 0.163672E+09 | 58945310.18 | 93356002.58 | 0.225587E+09 | 40742490.32 |
Maximum of Months | 0.271300E+09 | 0.125316E+09 | 0.167517E+09 | 0.472998E+09 | 0.194870E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164749E+09 | 71392666.40 | 93356002.58 | 0.225587E+09 | 0.194870E+09 |
February | 0.185738E+09 | 84338084.82 | 0.101400E+09 | 0.286309E+09 | 0.145987E+09 |
March | 0.255964E+09 | 0.117096E+09 | 0.138868E+09 | 0.393391E+09 | 0.141915E+09 |
April | 0.271300E+09 | 0.125316E+09 | 0.145984E+09 | 0.450041E+09 | 0.106236E+09 |
May | 0.256714E+09 | 99106069.09 | 0.157608E+09 | 0.462933E+09 | 69957019.19 |
June | 0.210375E+09 | 59111613.78 | 0.151263E+09 | 0.396991E+09 | 40742490.32 |
July | 0.242760E+09 | 75242658.89 | 0.167517E+09 | 0.472998E+09 | 54567670.28 |
August | 0.242021E+09 | 78738705.95 | 0.163282E+09 | 0.451249E+09 | 48227812.10 |
September | 0.199712E+09 | 58945310.18 | 0.140766E+09 | 0.380196E+09 | 55527657.39 |
October | 0.205221E+09 | 80021493.34 | 0.125200E+09 | 0.365146E+09 | 84856260.41 |
November | 0.163672E+09 | 59878912.06 | 0.103793E+09 | 0.265096E+09 | 0.118301E+09 |
December | 0.169989E+09 | 76169279.17 | 93820015.02 | 0.247559E+09 | 0.170339E+09 |
Annual Sum or Average | 0.256821E+10 | 0.985357E+09 | 0.158286E+10 | 0.439750E+10 | 0.123153E+10 |
Minimum of Months | 0.163672E+09 | 58945310.18 | 93356002.58 | 0.225587E+09 | 40742490.32 |
Maximum of Months | 0.271300E+09 | 0.125316E+09 | 0.167517E+09 | 0.472998E+09 | 0.194870E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44200942.80 | 0.00 | 44200942.80 | 40306774.18 | 0.117326E+09 |
February | 47255766.37 | 0.00 | 47255766.37 | 57002836.14 | 86876032.88 |
March | 62417380.03 | 4141.41 | 62413238.62 | 74947769.47 | 85012571.09 |
April | 67815532.76 | 378857.14 | 67436675.63 | 99610266.39 | 62355337.97 |
May | 79537874.93 | 3197547.58 | 76340327.35 | 0.143827E+09 | 39670930.67 |
June | 82399703.48 | 5762947.00 | 76636756.48 | 0.160083E+09 | 22288496.13 |
July | 86110223.25 | 4003386.61 | 82106836.64 | 0.175923E+09 | 31114774.45 |
August | 76616653.93 | 863217.67 | 75753436.26 | 0.146371E+09 | 27579111.41 |
September | 65602266.60 | 13154.38 | 65589112.23 | 0.127969E+09 | 31897817.27 |
October | 56766728.86 | 0.00 | 56766728.86 | 98351211.24 | 49272549.39 |
November | 47766746.87 | 0.00 | 47766746.87 | 66806426.14 | 69347231.99 |
December | 43720244.59 | 0.00 | 43720244.59 | 45302122.37 | 0.102602E+09 |
Annual Sum or Average | 0.760210E+09 | 14223251.78 | 0.745987E+09 | 0.123650E+10 | 0.725343E+09 |
Minimum of Months | 43720244.59 | 0.00 | 43720244.59 | 40306774.18 | 22288496.13 |
Maximum of Months | 86110223.25 | 5762947.00 | 82106836.64 | 0.175923E+09 | 0.117326E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44199655.73 | 0.00 | 44199655.73 | 40305390.92 | 0.117325E+09 |
February | 47254414.45 | 0.00 | 47254414.45 | 57001193.26 | 86875194.63 |
March | 62415613.29 | 4141.22 | 62411472.07 | 74945470.50 | 85011684.06 |
April | 67813648.65 | 378839.38 | 67434809.27 | 99607747.91 | 62354534.73 |
May | 79535459.88 | 3197397.70 | 76338062.18 | 0.143824E+09 | 39670166.99 |
June | 82397054.97 | 5762676.89 | 76634378.09 | 0.160079E+09 | 22287796.57 |
July | 86107547.34 | 4003198.96 | 82104348.38 | 0.175919E+09 | 31113985.58 |
August | 76614306.39 | 863177.21 | 75751129.18 | 0.146367E+09 | 27578350.54 |
September | 65600260.41 | 13153.76 | 65587106.65 | 0.127966E+09 | 31897057.63 |
October | 56765046.97 | 0.00 | 56765046.97 | 98348955.76 | 49271532.17 |
November | 47765281.59 | 0.00 | 47765281.59 | 66804510.30 | 69346290.12 |
December | 43718921.59 | 0.00 | 43718921.59 | 45300523.39 | 0.102601E+09 |
Annual Sum or Average | 0.760187E+09 | 14222585.12 | 0.745965E+09 | 0.123647E+10 | 0.725333E+09 |
Minimum of Months | 43718921.59 | 0.00 | 43718921.59 | 40305390.92 | 22287796.57 |
Maximum of Months | 86107547.34 | 5762676.89 | 82104348.38 | 0.175919E+09 | 0.117325E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.156798E+09 | 88593063.76 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.183381E+09 | 68983824.04 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.253871E+09 | 69426457.31 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.299453E+09 | 58366499.66 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.316779E+09 | 42946177.19 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.296507E+09 | 31465819.22 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.340718E+09 | 36990232.47 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.297725E+09 | 34890050.75 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.260803E+09 | 37165364.52 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.226150E+09 | 54022534.83 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.166157E+09 | 63658941.29 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.147158E+09 | 76073099.51 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.294550E+10 | 0.662582E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.147158E+09 | 31465819.22 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.340718E+09 | 88593063.76 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.156798E+09 | 88593063.76 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.183381E+09 | 68983824.04 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.253871E+09 | 69426457.31 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.299453E+09 | 58366499.66 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.316779E+09 | 42946177.19 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.296507E+09 | 31465819.22 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.340718E+09 | 36990232.47 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.297725E+09 | 34890050.75 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.260803E+09 | 37165364.52 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.226150E+09 | 54022534.83 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.166157E+09 | 63658941.29 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.147158E+09 | 76073099.51 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.294550E+10 | 0.662582E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.147158E+09 | 31465819.22 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.340718E+09 | 88593063.76 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.156798E+09 | 88593063.76 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.183381E+09 | 68983824.04 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.253871E+09 | 69426457.31 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.299453E+09 | 58366499.66 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.316779E+09 | 42946177.19 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.296507E+09 | 31465819.22 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.340718E+09 | 36990232.47 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.297725E+09 | 34890050.75 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.260803E+09 | 37165364.52 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.226150E+09 | 54022534.83 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.166157E+09 | 63658941.29 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.147158E+09 | 76073099.51 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.294550E+10 | 0.662582E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.147158E+09 | 31465819.22 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.340718E+09 | 88593063.76 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.156798E+09 | 88593063.76 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.183381E+09 | 68983824.04 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.253871E+09 | 69426457.31 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.299453E+09 | 58366499.66 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.316779E+09 | 42946177.19 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.296507E+09 | 31465819.22 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.340718E+09 | 36990232.47 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.297725E+09 | 34890050.75 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.260803E+09 | 37165364.52 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.226150E+09 | 54022534.83 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.166157E+09 | 63658941.29 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.147158E+09 | 76073099.51 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.294550E+10 | 0.662582E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.147158E+09 | 31465819.22 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.340718E+09 | 88593063.76 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.156798E+09 | 88593063.76 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.183381E+09 | 68983824.04 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.253871E+09 | 69426457.31 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.299453E+09 | 58366499.66 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.316779E+09 | 42946177.19 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.296507E+09 | 31465819.22 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.340718E+09 | 36990232.47 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.297725E+09 | 34890050.75 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.260803E+09 | 37165364.52 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.226150E+09 | 54022534.83 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.166157E+09 | 63658941.29 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.147158E+09 | 76073099.51 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.294550E+10 | 0.662582E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.147158E+09 | 31465819.22 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.340718E+09 | 88593063.76 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.156798E+09 | 88593063.76 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.183381E+09 | 68983824.04 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.253871E+09 | 69426457.31 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.299453E+09 | 58366499.66 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.316779E+09 | 42946177.19 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.296507E+09 | 31465819.22 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.340718E+09 | 36990232.47 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.297725E+09 | 34890050.75 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.260803E+09 | 37165364.52 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.226150E+09 | 54022534.83 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.166157E+09 | 63658941.29 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.147158E+09 | 76073099.51 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.294550E+10 | 0.662582E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.147158E+09 | 31465819.22 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.340718E+09 | 88593063.76 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.156798E+09 | 88593063.76 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.183381E+09 | 68983824.04 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.253871E+09 | 69426457.31 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.299453E+09 | 58366499.66 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.316779E+09 | 42946177.19 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.296507E+09 | 31465819.22 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.340718E+09 | 36990232.47 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.297725E+09 | 34890050.75 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.260803E+09 | 37165364.52 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.226150E+09 | 54022534.83 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.166157E+09 | 63658941.29 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.147158E+09 | 76073099.51 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.294550E+10 | 0.662582E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.147158E+09 | 31465819.22 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.340718E+09 | 88593063.76 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.156798E+09 | 88593063.76 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.183381E+09 | 68983824.04 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.253871E+09 | 69426457.31 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.299453E+09 | 58366499.66 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.316779E+09 | 42946177.19 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.296507E+09 | 31465819.22 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.340718E+09 | 36990232.47 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.297725E+09 | 34890050.75 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.260803E+09 | 37165364.52 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.226150E+09 | 54022534.83 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.166157E+09 | 63658941.29 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.147158E+09 | 76073099.51 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.294550E+10 | 0.662582E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.147158E+09 | 31465819.22 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.340718E+09 | 88593063.76 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.156798E+09 | 88593063.76 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.183381E+09 | 68983824.04 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.253871E+09 | 69426457.31 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.299453E+09 | 58366499.66 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.316779E+09 | 42946177.19 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.296507E+09 | 31465819.22 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.340718E+09 | 36990232.47 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.297725E+09 | 34890050.75 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.260803E+09 | 37165364.52 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.226150E+09 | 54022534.83 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.166157E+09 | 63658941.29 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.147158E+09 | 76073099.51 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.294550E+10 | 0.662582E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.147158E+09 | 31465819.22 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.340718E+09 | 88593063.76 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.156798E+09 | 88593063.76 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.183381E+09 | 68983824.04 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.253871E+09 | 69426457.31 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.299453E+09 | 58366499.66 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.316779E+09 | 42946177.19 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.296507E+09 | 31465819.22 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.340718E+09 | 36990232.47 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.297725E+09 | 34890050.75 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.260803E+09 | 37165364.52 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.226150E+09 | 54022534.83 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.166157E+09 | 63658941.29 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.147158E+09 | 76073099.51 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.294550E+10 | 0.662582E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.147158E+09 | 31465819.22 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.340718E+09 | 88593063.76 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.156798E+09 | 88593063.76 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.183381E+09 | 68983824.04 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.253871E+09 | 69426457.31 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.299453E+09 | 58366499.66 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.316779E+09 | 42946177.19 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.296507E+09 | 31465819.22 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.340718E+09 | 36990232.47 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.297725E+09 | 34890050.75 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.260803E+09 | 37165364.52 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.226150E+09 | 54022534.83 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.166157E+09 | 63658941.29 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.147158E+09 | 76073099.51 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.294550E+10 | 0.662582E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.147158E+09 | 31465819.22 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.340718E+09 | 88593063.76 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.156798E+09 | 88593063.76 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.183381E+09 | 68983824.04 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.253871E+09 | 69426457.31 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.299453E+09 | 58366499.66 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.316779E+09 | 42946177.19 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.296507E+09 | 31465819.22 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.340718E+09 | 36990232.47 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.297725E+09 | 34890050.75 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.260803E+09 | 37165364.52 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.226150E+09 | 54022534.83 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.166157E+09 | 63658941.29 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.147158E+09 | 76073099.51 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.294550E+10 | 0.662582E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.147158E+09 | 31465819.22 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.340718E+09 | 88593063.76 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.156798E+09 | 88593063.76 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.183381E+09 | 68983824.04 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.253871E+09 | 69426457.31 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.299453E+09 | 58366499.66 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.316779E+09 | 42946177.19 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.296507E+09 | 31465819.22 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.340718E+09 | 36990232.47 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.297725E+09 | 34890050.75 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.260803E+09 | 37165364.52 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.226150E+09 | 54022534.83 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.166157E+09 | 63658941.29 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.147158E+09 | 76073099.51 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.294550E+10 | 0.662582E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.147158E+09 | 31465819.22 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.340718E+09 | 88593063.76 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.156798E+09 | 88593063.76 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.183381E+09 | 68983824.04 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.253871E+09 | 69426457.31 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.299453E+09 | 58366499.66 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.316779E+09 | 42946177.19 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.296507E+09 | 31465819.22 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.340718E+09 | 36990232.47 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.297725E+09 | 34890050.75 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.260803E+09 | 37165364.52 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.226150E+09 | 54022534.83 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.166157E+09 | 63658941.29 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.147158E+09 | 76073099.51 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.294550E+10 | 0.662582E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.147158E+09 | 31465819.22 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.340718E+09 | 88593063.76 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248043E+09 | 0.146671E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287770E+09 | 0.114139E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394913E+09 | 0.119160E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456012E+09 | 0.110497E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476578E+09 | 89164125.22 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441342E+09 | 73160678.36 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503371E+09 | 83265250.68 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435595E+09 | 82986146.52 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386114E+09 | 83465904.65 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336163E+09 | 0.111550E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255108E+09 | 0.115013E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.231987E+09 | 0.126140E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445300E+10 | 0.125521E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.231987E+09 | 73160678.36 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503371E+09 | 0.146671E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 196.01 | 230.59 | 156.03 | 53.31 | 102.72 | 0.00 | 0.00 |
February | 282.55 | 191.24 | 192.62 | 69.72 | 122.90 | 0.00 | 0.00 |
March | 347.84 | 167.57 | 237.74 | 87.44 | 150.30 | 0.00 | 0.00 |
April | 423.03 | 129.00 | 261.66 | 96.99 | 164.68 | 0.00 | 0.00 |
May | 452.47 | 81.26 | 251.08 | 76.39 | 174.69 | 0.00 | 0.00 |
June | 428.98 | 47.78 | 225.91 | 50.06 | 175.85 | 0.00 | 0.00 |
July | 484.14 | 63.57 | 245.57 | 59.17 | 186.40 | 0.00 | 0.00 |
August | 446.07 | 56.42 | 237.93 | 59.44 | 178.49 | 0.00 | 0.00 |
September | 392.04 | 67.39 | 204.72 | 45.49 | 159.22 | 0.00 | 0.00 |
October | 345.85 | 99.91 | 195.63 | 59.75 | 135.88 | 0.00 | 0.00 |
November | 255.61 | 144.30 | 163.15 | 46.20 | 116.94 | 0.00 | 0.00 |
December | 216.62 | 201.75 | 159.58 | 56.88 | 102.70 | 0.00 | 0.00 |
Annual Sum or Average | 356.33 | 123.13 | 211.09 | 63.39 | 147.69 | 0.00 | 0.00 |
Minimum of Months | 196.01 | 47.78 | 156.03 | 45.49 | 102.70 | 0.00 | 0.00 |
Maximum of Months | 484.14 | 230.59 | 261.66 | 96.99 | 186.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 819.58 | 463.08 | 524.76 | 316.12 | 208.63 | 0.00 | 0.00 |
February | 1061.23 | 399.21 | 643.03 | 391.46 | 251.57 | 0.00 | 0.00 |
March | 1326.98 | 362.89 | 803.22 | 489.70 | 313.51 | 0.00 | 0.00 |
April | 1617.42 | 315.25 | 936.20 | 582.26 | 353.94 | 0.00 | 0.00 |
May | 1655.80 | 224.48 | 924.59 | 521.01 | 403.59 | 0.00 | 0.00 |
June | 1601.50 | 169.95 | 878.77 | 439.89 | 438.88 | 0.00 | 0.00 |
July | 1780.93 | 193.35 | 957.37 | 502.60 | 454.77 | 0.00 | 0.00 |
August | 1556.21 | 182.37 | 870.38 | 431.79 | 438.59 | 0.00 | 0.00 |
September | 1408.66 | 200.74 | 766.92 | 374.31 | 392.61 | 0.00 | 0.00 |
October | 1182.08 | 282.38 | 673.64 | 376.67 | 296.97 | 0.00 | 0.00 |
November | 897.45 | 343.84 | 536.70 | 279.01 | 257.69 | 0.00 | 0.00 |
December | 769.20 | 397.63 | 480.70 | 263.75 | 216.95 | 0.00 | 0.00 |
Annual Sum or Average | 1307.62 | 294.14 | 750.24 | 414.18 | 336.06 | 0.00 | 0.00 |
Minimum of Months | 769.20 | 169.95 | 480.70 | 263.75 | 208.63 | 0.00 | 0.00 |
Maximum of Months | 1780.93 | 463.08 | 957.37 | 582.26 | 454.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12022.07 | 5929.82 | 2357.72 | 1421.78 | 935.95 | 0.00 | 0.00 |
February | 16203.57 | 5068.51 | 2882.25 | 1753.66 | 1128.58 | 0.00 | 0.00 |
March | 21143.76 | 4937.23 | 3593.74 | 2187.27 | 1406.47 | 0.00 | 0.00 |
April | 31488.77 | 5044.99 | 4184.81 | 2596.99 | 1587.81 | 0.00 | 0.00 |
May | 29516.32 | 4629.51 | 4133.06 | 2322.51 | 1810.55 | 0.00 | 0.00 |
June | 30105.05 | 4687.70 | 3929.80 | 1960.91 | 1968.88 | 0.00 | 0.00 |
July | 35205.84 | 5542.07 | 4279.45 | 2239.26 | 2040.18 | 0.00 | 0.00 |
August | 29182.87 | 5370.58 | 3891.64 | 1924.05 | 1967.59 | 0.00 | 0.00 |
September | 27842.14 | 5122.71 | 3430.15 | 1668.84 | 1761.31 | 0.00 | 0.00 |
October | 20948.82 | 5773.75 | 3016.62 | 1684.37 | 1332.26 | 0.00 | 0.00 |
November | 15396.60 | 5157.04 | 2408.57 | 1252.52 | 1156.05 | 0.00 | 0.00 |
December | 12635.35 | 5159.19 | 2161.35 | 1188.09 | 973.27 | 0.00 | 0.00 |
Annual Sum or Average | 23504.06 | 5205.20 | 3358.20 | 1850.60 | 1507.61 | 0.00 | 0.00 |
Minimum of Months | 12022.07 | 4629.51 | 2161.35 | 1188.09 | 935.95 | 0.00 | 0.00 |
Maximum of Months | 35205.84 | 5929.82 | 4279.45 | 2596.99 | 2040.18 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.524995E+09 | 0.617602E+09 | 0.417898E+09 | 0.142785E+09 | 0.275113E+09 | 0.00 | 0.00 |
February | 0.683551E+09 | 0.462655E+09 | 0.465986E+09 | 0.168676E+09 | 0.297310E+09 | 0.00 | 0.00 |
March | 0.931650E+09 | 0.448829E+09 | 0.636761E+09 | 0.234200E+09 | 0.402561E+09 | 0.00 | 0.00 |
April | 0.109649E+10 | 0.334369E+09 | 0.678229E+09 | 0.251390E+09 | 0.426839E+09 | 0.00 | 0.00 |
May | 0.121191E+10 | 0.217644E+09 | 0.672501E+09 | 0.204607E+09 | 0.467894E+09 | 0.00 | 0.00 |
June | 0.111192E+10 | 0.123839E+09 | 0.585547E+09 | 0.129749E+09 | 0.455798E+09 | 0.00 | 0.00 |
July | 0.129673E+10 | 0.170259E+09 | 0.657737E+09 | 0.158492E+09 | 0.499246E+09 | 0.00 | 0.00 |
August | 0.119475E+10 | 0.151125E+09 | 0.637272E+09 | 0.159204E+09 | 0.478068E+09 | 0.00 | 0.00 |
September | 0.101616E+10 | 0.174683E+09 | 0.530626E+09 | 0.117917E+09 | 0.412709E+09 | 0.00 | 0.00 |
October | 0.926331E+09 | 0.267596E+09 | 0.523975E+09 | 0.160043E+09 | 0.363932E+09 | 0.00 | 0.00 |
November | 0.662543E+09 | 0.374035E+09 | 0.422875E+09 | 0.119758E+09 | 0.303117E+09 | 0.00 | 0.00 |
December | 0.580199E+09 | 0.540360E+09 | 0.427418E+09 | 0.152339E+09 | 0.275079E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112372E+11 | 0.388300E+10 | 0.665682E+10 | 0.199916E+10 | 0.465767E+10 | 0.00 | 0.00 |
Minimum of Months | 0.524995E+09 | 0.123839E+09 | 0.417898E+09 | 0.117917E+09 | 0.275079E+09 | 0.00 | 0.00 |
Maximum of Months | 0.129673E+10 | 0.617602E+09 | 0.678229E+09 | 0.251390E+09 | 0.499246E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.219518E+10 | 0.124030E+10 | 0.140550E+10 | 0.846708E+09 | 0.558796E+09 | 0.00 | 0.00 |
February | 0.256734E+10 | 0.965774E+09 | 0.155562E+10 | 0.947017E+09 | 0.608598E+09 | 0.00 | 0.00 |
March | 0.355419E+10 | 0.971970E+09 | 0.215133E+10 | 0.131162E+10 | 0.839717E+09 | 0.00 | 0.00 |
April | 0.419235E+10 | 0.817131E+09 | 0.242662E+10 | 0.150922E+10 | 0.917404E+09 | 0.00 | 0.00 |
May | 0.443490E+10 | 0.601246E+09 | 0.247643E+10 | 0.139547E+10 | 0.108096E+10 | 0.00 | 0.00 |
June | 0.415110E+10 | 0.440521E+09 | 0.227778E+10 | 0.114020E+10 | 0.113758E+10 | 0.00 | 0.00 |
July | 0.477006E+10 | 0.517863E+09 | 0.256423E+10 | 0.134616E+10 | 0.121807E+10 | 0.00 | 0.00 |
August | 0.416815E+10 | 0.488461E+09 | 0.233123E+10 | 0.115651E+10 | 0.117472E+10 | 0.00 | 0.00 |
September | 0.365125E+10 | 0.520315E+09 | 0.198787E+10 | 0.970221E+09 | 0.101765E+10 | 0.00 | 0.00 |
October | 0.316609E+10 | 0.756315E+09 | 0.180427E+10 | 0.100886E+10 | 0.795407E+09 | 0.00 | 0.00 |
November | 0.232619E+10 | 0.891225E+09 | 0.139113E+10 | 0.723193E+09 | 0.667941E+09 | 0.00 | 0.00 |
December | 0.206022E+10 | 0.106502E+10 | 0.128751E+10 | 0.706435E+09 | 0.581077E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.412370E+11 | 0.927615E+10 | 0.236595E+11 | 0.130616E+11 | 0.105979E+11 | 0.00 | 0.00 |
Minimum of Months | 0.206022E+10 | 0.440521E+09 | 0.128751E+10 | 0.706435E+09 | 0.558796E+09 | 0.00 | 0.00 |
Maximum of Months | 0.477006E+10 | 0.124030E+10 | 0.256423E+10 | 0.150922E+10 | 0.121807E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.321999E+11 | 0.158824E+11 | 0.631493E+10 | 0.380808E+10 | 0.250684E+10 | 0.00 | 0.00 |
February | 0.391997E+11 | 0.122617E+11 | 0.697273E+10 | 0.424246E+10 | 0.273026E+10 | 0.00 | 0.00 |
March | 0.566314E+11 | 0.132239E+11 | 0.962548E+10 | 0.585839E+10 | 0.376710E+10 | 0.00 | 0.00 |
April | 0.816189E+11 | 0.130766E+11 | 0.108470E+11 | 0.673141E+10 | 0.411561E+10 | 0.00 | 0.00 |
May | 0.790565E+11 | 0.123997E+11 | 0.110700E+11 | 0.622061E+10 | 0.484937E+10 | 0.00 | 0.00 |
June | 0.780323E+11 | 0.121505E+11 | 0.101860E+11 | 0.508269E+10 | 0.510334E+10 | 0.00 | 0.00 |
July | 0.942953E+11 | 0.148439E+11 | 0.114621E+11 | 0.599764E+10 | 0.546443E+10 | 0.00 | 0.00 |
August | 0.781634E+11 | 0.143846E+11 | 0.104234E+11 | 0.515337E+10 | 0.526999E+10 | 0.00 | 0.00 |
September | 0.721668E+11 | 0.132781E+11 | 0.889095E+10 | 0.432562E+10 | 0.456532E+10 | 0.00 | 0.00 |
October | 0.561093E+11 | 0.154644E+11 | 0.807973E+10 | 0.451141E+10 | 0.356831E+10 | 0.00 | 0.00 |
November | 0.399080E+11 | 0.133671E+11 | 0.624302E+10 | 0.324654E+10 | 0.299648E+10 | 0.00 | 0.00 |
December | 0.338425E+11 | 0.138184E+11 | 0.578897E+10 | 0.318217E+10 | 0.260680E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.741224E+12 | 0.164151E+12 | 0.105904E+12 | 0.583604E+11 | 0.475439E+11 | 0.00 | 0.00 |
Minimum of Months | 0.321999E+11 | 0.121505E+11 | 0.578897E+10 | 0.318217E+10 | 0.250684E+10 | 0.00 | 0.00 |
Maximum of Months | 0.942953E+11 | 0.158824E+11 | 0.114621E+11 | 0.673141E+10 | 0.546443E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.685325E+09 | -611938997.3 | 0.00 | 0.00 | 744.00 | 0.00 | -73385913.7 | 58.99 | 0.00 | 0.00 |
February | 0.623046E+09 | -556836258.3 | 0.00 | 0.00 | 672.00 | 0.00 | -66209497.7 | 58.99 | 0.00 | 0.00 |
March | 0.703114E+09 | -630613858.0 | 0.00 | 0.00 | 744.00 | 0.00 | -72499713.0 | 58.99 | 0.00 | 0.00 |
April | 0.627303E+09 | -558832619.9 | 0.00 | 0.00 | 720.00 | 0.00 | -68470394.2 | 58.99 | 0.00 | 0.00 |
May | 0.622260E+09 | -552219649.2 | 0.00 | 0.00 | 744.00 | 0.00 | -70040243.0 | 58.99 | 0.00 | 0.00 |
June | 0.595510E+09 | -527947310.4 | 0.00 | 0.00 | 720.00 | 0.00 | -67562817.9 | 58.99 | 0.00 | 0.00 |
July | 0.570465E+09 | -501278405.6 | 0.00 | 0.00 | 744.00 | 0.00 | -69186320.5 | 58.98 | 0.00 | 0.00 |
August | 0.614518E+09 | -544824312.5 | 0.00 | 0.00 | 744.00 | 0.00 | -69694002.7 | 58.99 | 0.00 | 0.00 |
September | 0.593195E+09 | -525953100.1 | 0.00 | 0.00 | 720.00 | 0.00 | -67241676.4 | 58.98 | 0.00 | 0.00 |
October | 0.624148E+09 | -554362320.4 | 0.00 | 0.00 | 744.00 | 0.00 | -69785613.7 | 58.98 | 0.00 | 0.00 |
November | 0.627997E+09 | -559018208.7 | 0.00 | 0.00 | 720.00 | 0.00 | -68978812.4 | 58.99 | 0.00 | 0.00 |
December | 0.675892E+09 | -603013641.6 | 0.00 | 0.00 | 744.00 | 0.00 | -72878722.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.756277E+10 | -0.672684E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -835933727.4 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.570465E+09 | -630613858.0 | 0.00 | 0.00 | 672.00 | 0.00 | -73385913.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.703114E+09 | -501278405.6 | 0.00 | 0.00 | 744.00 | 0.00 | -66209497.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.83 | 0.50 | 01-JAN-11:00 | 163.99 | 0.00 | 0.00 | 28.17 | 668.15 | 0.00 | 0.00 | 20.83 |
February | 304.33 | 0.80 | 0.50 | 01-FEB-11:39 | 1199.59 | 0.00 | 0.00 | 61.83 | 475.46 | 0.00 | 0.00 | 35.83 |
March | 362.67 | 0.78 | 0.50 | 03-MAR-10:00 | 312.33 | 0.00 | 0.00 | 105.33 | 183.28 | 0.00 | 0.00 | 58.50 |
April | 357.50 | 0.74 | 0.50 | 04-APR-10:30 | 259.31 | 0.00 | 0.00 | 118.17 | 768.48 | 0.00 | 0.00 | 98.67 |
May | 389.00 | 0.74 | 0.50 | 01-MAY-10:00 | 1082.40 | 0.00 | 0.00 | 177.17 | 200.59 | 0.00 | 0.00 | 72.50 |
June | 388.17 | 0.74 | 0.50 | 01-JUN-10:30 | 314.93 | 0.00 | 0.00 | 170.67 | 201.48 | 0.00 | 0.00 | 88.00 |
July | 403.83 | 0.72 | 0.50 | 01-JUL-10:20 | 662.85 | 0.00 | 0.00 | 193.33 | 217.18 | 0.00 | 0.00 | 106.50 |
August | 348.33 | 0.71 | 0.50 | 01-AUG-10:20 | 1034.99 | 0.00 | 0.00 | 193.67 | 242.52 | 0.00 | 0.00 | 116.00 |
September | 349.67 | 0.72 | 0.50 | 01-SEP-10:09 | 288.62 | 0.00 | 0.00 | 150.67 | 231.01 | 0.00 | 0.00 | 105.17 |
October | 323.50 | 0.77 | 0.50 | 02-OCT-11:39 | 227.01 | 0.00 | 0.00 | 98.67 | 262.65 | 0.00 | 0.00 | 54.83 |
November | 314.83 | 0.79 | 0.50 | 01-NOV-10:39 | 199.58 | 0.00 | 0.00 | 55.83 | 611.97 | 0.00 | 0.00 | 44.67 |
December | 282.67 | 0.82 | 0.50 | 01-DEC-12:30 | 181.45 | 0.00 | 0.00 | 21.67 | 151.79 | 0.00 | 0.00 | 3.17 |
Annual Sum or Average | 4111.50 | 0.76 | 505.43 | 0.00 | 0.00 | 1375.17 | 342.31 | 0.00 | 0.00 | 804.67 | ||
Minimum of Months | 282.67 | 0.71 | 0.50 | 163.99 | 0.00 | 0.00 | 21.67 | 151.79 | 0.00 | 0.00 | 3.17 | |
Maximum of Months | 403.83 | 0.83 | 0.50 | 1199.59 | 0.00 | 0.00 | 193.67 | 768.48 | 0.00 | 0.00 | 116.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.70 | 0.50 | 01-JAN-10:39 | 639.80 | 11.75 | 0.00 | 129.17 | 403.75 | 18.01 | 42.50 | 122.00 |
February | 304.33 | 0.68 | 0.50 | 01-FEB-09:50 | 486.88 | 12.46 | 0.00 | 148.00 | 184.01 | 16.11 | 32.17 | 114.00 |
March | 362.67 | 0.66 | 0.50 | 01-MAR-13:30 | 259.85 | 12.87 | 0.00 | 208.00 | 218.33 | 16.66 | 62.17 | 162.17 |
April | 357.50 | 0.63 | 0.50 | 01-APR-08:50 | 289.09 | 13.41 | 0.00 | 237.33 | 1043.71 | 17.15 | 83.33 | 195.17 |
May | 389.00 | 0.63 | 0.50 | 01-MAY-08:20 | 304.40 | 13.60 | 0.00 | 262.17 | 263.16 | 17.21 | 82.33 | 216.17 |
June | 388.17 | 0.63 | 0.50 | 01-JUN-08:09 | 318.55 | 13.38 | 0.00 | 259.50 | 278.79 | 16.86 | 80.33 | 223.00 |
July | 403.83 | 0.61 | 0.50 | 01-JUL-07:30 | 337.08 | 14.13 | 0.00 | 285.33 | 291.65 | 17.68 | 100.17 | 240.00 |
August | 348.33 | 0.61 | 0.50 | 01-AUG-07:00 | 539.89 | 14.12 | 0.00 | 275.50 | 449.40 | 17.70 | 94.17 | 230.50 |
September | 349.67 | 0.62 | 0.50 | 01-SEP-08:09 | 962.62 | 14.17 | 0.00 | 248.50 | 832.41 | 17.68 | 94.83 | 205.00 |
October | 323.50 | 0.65 | 0.50 | 02-OCT-11:39 | 259.74 | 13.26 | 0.00 | 208.50 | 215.54 | 16.93 | 60.50 | 166.33 |
November | 314.83 | 0.67 | 0.50 | 01-NOV-08:50 | 228.24 | 12.92 | 0.00 | 168.00 | 189.58 | 16.44 | 35.67 | 125.33 |
December | 282.67 | 0.68 | 0.50 | 01-DEC-09:20 | 209.98 | 12.36 | 0.00 | 140.50 | 173.87 | 15.81 | 19.50 | 99.00 |
Annual Sum or Average | 4111.50 | 0.64 | 400.70 | 13.27 | 0.00 | 2570.50 | 383.98 | 17.05 | 787.67 | 2098.67 | ||
Minimum of Months | 282.67 | 0.61 | 0.50 | 209.98 | 11.75 | 0.00 | 129.17 | 173.87 | 15.81 | 19.50 | 99.00 | |
Maximum of Months | 403.83 | 0.70 | 0.50 | 962.62 | 14.17 | 0.00 | 285.33 | 1043.71 | 18.01 | 100.17 | 240.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.87 | 0.64 | 02-JAN-15:09 | 278.45 | 22.63 | 137.00 | 33.00 | 112.85 | 20.25 | 112.50 | 0.00 |
February | 304.33 | 0.85 | 0.61 | 10-FEB-16:10 | 367.37 | 23.05 | 142.83 | 51.17 | 253.81 | 22.61 | 141.50 | 21.33 |
March | 362.67 | 0.82 | 0.61 | 01-MAR-16:10 | 407.31 | 23.18 | 172.00 | 81.83 | 337.70 | 23.85 | 191.00 | 56.67 |
April | 357.50 | 0.81 | 0.61 | 01-APR-16:19 | 261.43 | 21.13 | 150.33 | 63.67 | 241.06 | 22.33 | 193.00 | 55.33 |
May | 389.00 | 0.82 | 0.61 | 01-MAY-15:20 | 262.33 | 20.54 | 140.17 | 59.67 | 213.62 | 21.85 | 194.83 | 51.83 |
June | 388.17 | 0.83 | 0.61 | 01-JUN-14:20 | 258.02 | 19.84 | 120.83 | 63.33 | 189.10 | 21.12 | 183.50 | 38.17 |
July | 403.83 | 0.80 | 0.61 | 01-JUL-15:39 | 284.50 | 20.71 | 162.17 | 84.33 | 213.28 | 21.93 | 230.00 | 55.00 |
August | 348.33 | 0.79 | 0.61 | 01-AUG-16:30 | 289.08 | 21.09 | 166.17 | 83.50 | 218.40 | 22.22 | 220.50 | 56.83 |
September | 349.67 | 0.82 | 0.61 | 01-SEP-14:00 | 286.04 | 21.72 | 166.33 | 70.33 | 194.60 | 22.45 | 205.67 | 34.67 |
October | 323.50 | 0.82 | 0.61 | 02-OCT-15:20 | 310.44 | 23.63 | 181.00 | 78.67 | 219.49 | 24.04 | 196.33 | 31.67 |
November | 314.83 | 0.85 | 0.61 | 01-NOV-16:10 | 238.96 | 22.82 | 166.83 | 43.50 | 142.32 | 22.19 | 162.33 | 8.50 |
December | 282.67 | 0.85 | 0.64 | 01-DEC-14:00 | 259.96 | 23.68 | 149.67 | 40.33 | 126.27 | 21.29 | 130.83 | 0.00 |
Annual Sum or Average | 4111.50 | 0.83 | 291.83 | 21.89 | 1855.33 | 753.33 | 208.33 | 22.19 | 2162.00 | 410.00 | ||
Minimum of Months | 282.67 | 0.79 | 0.61 | 238.96 | 19.84 | 120.83 | 33.00 | 112.85 | 20.25 | 112.50 | 0.00 | |
Maximum of Months | 403.83 | 0.87 | 0.64 | 407.31 | 23.68 | 181.00 | 84.33 | 337.70 | 24.04 | 230.00 | 56.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 24961335.12 | 5240.62 | 25-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11421273.17 | 3647.31 | 04-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27386294.15 | 5423.05 | 16-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28229556.94 | 5352.71 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91998459.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28229556.94 | 5423.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.545992E+10 | 0.404683E+10 | 30503.13 | 07-JAN-06:01 | 15675.95 | 0.00 |
February | 0.00 | 0.00 | 0.606839E+10 | 0.455352E+10 | 30590.07 | 11-FEB-06:02 | 15630.62 | 0.00 |
March | 0.00 | 0.00 | 0.803162E+10 | 0.584071E+10 | 31107.39 | 06-MAR-06:01 | 15580.36 | 0.00 |
April | 0.00 | 0.00 | 0.102941E+11 | 0.759004E+10 | 30852.28 | 13-APR-05:01 | 17074.27 | 0.00 |
May | 0.00 | 0.00 | 0.136967E+11 | 0.943715E+10 | 31663.96 | 30-MAY-05:02 | 15921.15 | 0.00 |
June | 0.00 | 0.00 | 0.152859E+11 | 0.990430E+10 | 31614.40 | 19-JUN-05:01 | 15517.26 | 0.00 |
July | 0.00 | 0.00 | 0.156597E+11 | 0.103384E+11 | 31453.77 | 24-JUL-05:01 | 17277.92 | 0.00 |
August | 0.00 | 0.00 | 0.166164E+11 | 0.107751E+11 | 31752.59 | 14-AUG-05:01 | 15837.31 | 0.00 |
September | 0.00 | 0.00 | 0.148718E+11 | 0.973862E+10 | 31487.75 | 20-SEP-05:01 | 16612.55 | 0.00 |
October | 0.00 | 0.00 | 0.132610E+11 | 0.897251E+10 | 31377.95 | 05-OCT-05:01 | 16278.68 | 0.00 |
November | 0.00 | 0.00 | 0.100265E+11 | 0.683518E+10 | 31441.44 | 24-NOV-06:01 | 15605.47 | 0.00 |
December | 0.00 | 0.00 | 0.629019E+10 | 0.460474E+10 | 31206.96 | 11-DEC-06:01 | 16391.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.135562E+12 | 0.926371E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.545992E+10 | 0.404683E+10 | 30503.13 | 15517.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.166164E+11 | 0.107751E+11 | 31752.59 | 17277.92 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.328836E+10 | 0.207557E+10 | 41467.66 | 01-JAN-13:45 | 28126.02 | 0.00 |
February | 0.00 | 0.00 | 0.552633E+10 | 0.390183E+10 | 86130.88 | 19-FEB-14:33 | 57078.45 | 0.00 |
March | 0.00 | 0.00 | 0.100047E+11 | 0.651664E+10 | 85798.88 | 26-MAR-13:43 | 57569.68 | 0.00 |
April | 0.00 | 0.00 | 0.209831E+11 | 0.145242E+11 | 85977.21 | 13-APR-17:06 | 56674.35 | 0.00 |
May | 0.00 | 0.00 | 0.341643E+11 | 0.221711E+11 | 89773.06 | 20-MAY-05:10 | 52641.78 | 0.00 |
June | 0.00 | 0.00 | 0.418173E+11 | 0.257821E+11 | 91024.95 | 08-JUN-05:08 | 49029.64 | 0.00 |
July | 0.00 | 0.00 | 0.475647E+11 | 0.304093E+11 | 90712.45 | 27-JUL-05:08 | 51963.61 | 0.00 |
August | 0.00 | 0.00 | 0.449561E+11 | 0.276385E+11 | 90662.92 | 05-AUG-05:01 | 51717.92 | 0.00 |
September | 0.00 | 0.00 | 0.415884E+11 | 0.258701E+11 | 90708.85 | 23-SEP-05:06 | 50273.07 | 0.00 |
October | 0.00 | 0.00 | 0.312102E+11 | 0.197247E+11 | 94851.60 | 04-OCT-05:06 | 45616.50 | 0.00 |
November | 0.00 | 0.00 | 0.158588E+11 | 0.962269E+10 | 88953.67 | 23-NOV-13:23 | 53440.31 | 0.00 |
December | 0.00 | 0.00 | 0.642642E+10 | 0.413469E+10 | 87383.18 | 10-DEC-12:43 | 54708.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.303389E+12 | 0.192371E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.328836E+10 | 0.207557E+10 | 41467.66 | 28126.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.475647E+11 | 0.304093E+11 | 94851.60 | 57569.68 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.531660E+09 | 0.21 | 1322.66 | 02-JAN-06:01 | 0.89 |
February | 0.489726E+09 | 0.21 | 1322.66 | 02-FEB-06:03 | 0.89 |
March | 0.580886E+09 | 0.23 | 1322.66 | 03-MAR-06:02 | 0.90 |
April | 0.555018E+09 | 0.23 | 1322.66 | 01-APR-05:01 | 0.90 |
May | 0.618629E+09 | 0.24 | 1322.66 | 01-MAY-05:01 | 0.89 |
June | 0.659688E+09 | 0.25 | 1322.66 | 01-JUN-05:01 | 0.89 |
July | 0.686055E+09 | 0.25 | 1322.66 | 01-JUL-05:01 | 0.89 |
August | 0.728185E+09 | 0.27 | 1322.66 | 01-AUG-05:01 | 0.89 |
September | 0.647303E+09 | 0.25 | 1322.66 | 01-SEP-05:01 | 0.89 |
October | 0.598089E+09 | 0.23 | 1322.66 | 02-OCT-05:01 | 0.89 |
November | 0.527947E+09 | 0.21 | 1322.66 | 01-NOV-05:01 | 0.89 |
December | 0.535935E+09 | 0.21 | 1322.66 | 01-DEC-06:01 | 0.89 |
Annual Sum or Average | 0.715912E+10 | 0.23 | |||
Minimum of Months | 0.489726E+09 | 0.21 | 1322.66 | 0.89 | |
Maximum of Months | 0.728185E+09 | 0.27 | 1322.66 | 0.90 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.129063E+10 | 0.20 | 1294.99 | 05-JAN-11:30 | 0.53 |
February | 0.119821E+10 | 0.21 | 3237.48 | 19-FEB-14:33 | 0.87 |
March | 0.142091E+10 | 0.23 | 3237.48 | 26-MAR-13:43 | 0.87 |
April | 0.141820E+10 | 0.26 | 3237.48 | 09-APR-12:23 | 0.87 |
May | 0.161371E+10 | 0.31 | 3237.48 | 05-MAY-17:06 | 0.87 |
June | 0.173581E+10 | 0.37 | 3237.48 | 02-JUN-05:01 | 0.87 |
July | 0.182127E+10 | 0.39 | 3237.48 | 01-JUL-17:06 | 0.87 |
August | 0.183446E+10 | 0.38 | 3237.48 | 01-AUG-17:08 | 0.86 |
September | 0.171323E+10 | 0.37 | 3237.48 | 01-SEP-17:06 | 0.87 |
October | 0.153385E+10 | 0.30 | 3237.48 | 03-OCT-17:08 | 0.86 |
November | 0.129538E+10 | 0.22 | 3237.48 | 05-NOV-14:03 | 0.86 |
December | 0.130916E+10 | 0.21 | 3237.48 | 10-DEC-12:43 | 0.86 |
Annual Sum or Average | 0.181848E+11 | 0.29 | |||
Minimum of Months | 0.119821E+10 | 0.20 | 1294.99 | 0.53 | |
Maximum of Months | 0.183446E+10 | 0.39 | 3237.48 | 0.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.181005E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.190850E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.243181E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.293553E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.379991E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.419389E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.438543E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.461320E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.410104E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.366149E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.282607E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.199534E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.386623E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.181005E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.461320E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.218309E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.270884E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.409167E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.702838E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.107394E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.128373E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.145962E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.138148E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.127828E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.984967E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.550946E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.302179E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.991634E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.218309E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.145962E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.531660E+09 | 0.545992E+10 | 24961335.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.489726E+09 | 0.606839E+10 | 11421273.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.580886E+09 | 0.803162E+10 | 27386294.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.555018E+09 | 0.102941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.618629E+09 | 0.136967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.659688E+09 | 0.152859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.686055E+09 | 0.156597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.728185E+09 | 0.166164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.647303E+09 | 0.148718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.598089E+09 | 0.132610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.527947E+09 | 0.100265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.535935E+09 | 0.629019E+10 | 28229556.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.715912E+10 | 0.135562E+12 | 91998459.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.489726E+09 | 0.545992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.728185E+09 | 0.166164E+11 | 28229556.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.129063E+10 | 0.328836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119821E+10 | 0.552633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142091E+10 | 0.100047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141820E+10 | 0.209831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161371E+10 | 0.341643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173581E+10 | 0.418173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182127E+10 | 0.475647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.183446E+10 | 0.449561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.171323E+10 | 0.415884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153385E+10 | 0.312102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129538E+10 | 0.158588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130916E+10 | 0.642642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181848E+11 | 0.303389E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119821E+10 | 0.328836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.183446E+10 | 0.475647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.531660E+09 | 0.00 | 0.00 | 0.00 | 0.127839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.489726E+09 | 0.00 | 0.00 | 0.00 | 0.141878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.580886E+09 | 0.00 | 0.00 | 0.00 | 0.185092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.555018E+09 | 0.00 | 0.00 | 0.00 | 0.238051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.618629E+09 | 0.00 | 0.00 | 0.00 | 0.318128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.659688E+09 | 0.00 | 0.00 | 0.00 | 0.353420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.686055E+09 | 0.00 | 0.00 | 0.00 | 0.369938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.728185E+09 | 0.00 | 0.00 | 0.00 | 0.388502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.647303E+09 | 0.00 | 0.00 | 0.00 | 0.345373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.598089E+09 | 0.00 | 0.00 | 0.00 | 0.306340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.527947E+09 | 0.00 | 0.00 | 0.00 | 0.229813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.535935E+09 | 0.00 | 0.00 | 0.00 | 0.145940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.715912E+10 | 0.00 | 0.00 | 0.00 | 0.315031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.489726E+09 | 0.00 | 0.00 | 0.00 | 0.127839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.728185E+09 | 0.00 | 0.00 | 0.00 | 0.388502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.129063E+10 | 0.00 | 0.00 | 0.00 | 0.892463E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119821E+10 | 0.00 | 0.00 | 0.00 | 0.151063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142091E+10 | 0.00 | 0.00 | 0.00 | 0.267076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141820E+10 | 0.00 | 0.00 | 0.00 | 0.561018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161371E+10 | 0.00 | 0.00 | 0.00 | 0.912569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173581E+10 | 0.00 | 0.00 | 0.00 | 0.111015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182127E+10 | 0.00 | 0.00 | 0.00 | 0.127749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.183446E+10 | 0.00 | 0.00 | 0.00 | 0.119803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.171323E+10 | 0.00 | 0.00 | 0.00 | 0.110696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153385E+10 | 0.00 | 0.00 | 0.00 | 0.831582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129538E+10 | 0.00 | 0.00 | 0.00 | 0.421409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130916E+10 | 0.00 | 0.00 | 0.00 | 0.171263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181848E+11 | 0.00 | 0.00 | 0.00 | 0.809785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119821E+10 | 0.00 | 0.00 | 0.00 | 0.892463E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.183446E+10 | 0.00 | 0.00 | 0.00 | 0.127749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110697E+09 | 0.435830E+09 | 0.00 | 2670425.19 | 75944.10 | 13014466.27 | 0.290850E+09 | 0.00 | 0.14 |
February | 65615389.81 | 0.515364E+09 | 0.00 | 2385361.54 | 33619.79 | 8783846.40 | 0.129723E+09 | 0.00 | 0.14 |
March | 80037562.05 | 0.725140E+09 | 0.00 | 3121930.77 | 6183.52 | 14453180.35 | 0.199997E+09 | 0.00 | 0.15 |
April | 2820273.67 | 0.115588E+10 | 0.00 | 2858477.90 | 0.00 | 0.00 | 35354956.51 | 0.00 | 0.15 |
May | 0.00 | 0.197249E+10 | 0.00 | 1227105.38 | 0.00 | 0.00 | 45090.52 | 0.00 | 0.15 |
June | 0.00 | 0.261372E+10 | 0.00 | 179812.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.289983E+10 | 0.00 | 37295.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
August | 0.00 | 0.295215E+10 | 0.00 | 160439.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.259052E+10 | 0.00 | 282530.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.204531E+10 | 0.00 | 777864.36 | 0.00 | 0.00 | 263104.11 | 0.00 | 0.14 |
November | 15708549.67 | 0.136641E+10 | 0.00 | 2399709.95 | 111426.65 | 0.00 | 19815075.46 | 0.00 | 0.14 |
December | 81932665.41 | 0.571559E+09 | 0.00 | 3256465.83 | 203053.63 | 15842031.10 | 0.268014E+09 | 0.00 | 0.14 |
Annual Sum or Average | 0.356811E+09 | 0.198442E+11 | 0.00 | 19357418.94 | 430227.69 | 52093524.12 | 0.944063E+09 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.435830E+09 | 0.00 | 37295.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.110697E+09 | 0.295215E+10 | 0.00 | 3256465.83 | 203053.63 | 15842031.10 | 0.290850E+09 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.245936E+10 | 0.252896E+09 | 0.00 | 1246173.66 | 6302273.36 | 0.00 | 0.437569E+09 | 0.00 | 0.20 |
February | 0.103681E+10 | 0.291327E+09 | 0.00 | 4136482.96 | 577416.88 | 0.00 | 0.621968E+09 | 0.00 | 0.20 |
March | 0.139411E+10 | 0.749724E+09 | 0.00 | 3543435.42 | 50679.27 | 0.00 | 0.737088E+09 | 0.00 | 0.22 |
April | 0.222429E+09 | 0.227823E+10 | 0.00 | 4900692.24 | 263675.87 | 0.00 | 0.414257E+09 | 0.00 | 0.22 |
May | 18805352.80 | 0.537989E+10 | 0.00 | 483160.37 | 3470015.33 | 0.00 | 42999266.95 | 0.00 | 0.23 |
June | 0.00 | 0.885395E+10 | 0.00 | 75888.44 | 12324069.73 | 0.00 | 6241554.50 | 0.00 | 0.25 |
July | 0.00 | 0.110460E+11 | 0.00 | 0.00 | 12477234.84 | 0.00 | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.101428E+11 | 0.00 | 187431.69 | 19691545.71 | 0.00 | 15633629.41 | 0.00 | 0.25 |
September | 0.00 | 0.881311E+10 | 0.00 | 53597.26 | 5087404.22 | 0.00 | 8350974.79 | 0.00 | 0.25 |
October | 19912756.09 | 0.559351E+10 | 0.00 | 562132.75 | 11053418.88 | 0.00 | 75103696.07 | 0.00 | 0.22 |
November | 0.375160E+09 | 0.261099E+10 | 0.00 | 1468269.24 | 3101570.77 | 0.00 | 0.304769E+09 | 0.00 | 0.20 |
December | 0.200936E+10 | 0.651931E+09 | 0.00 | 2085291.62 | 3190633.21 | 0.00 | 0.520789E+09 | 0.00 | 0.20 |
Annual Sum or Average | 0.753596E+10 | 0.566643E+11 | 0.00 | 18742555.66 | 77589938.07 | 0.00 | 0.318477E+10 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 0.252896E+09 | 0.00 | 0.00 | 50679.27 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.245936E+10 | 0.110460E+11 | 0.00 | 4900692.24 | 19691545.71 | 0.00 | 0.737088E+09 | 0.00 | 0.25 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.640060E+12 | 0.304337E+11 | 0.00 | 0.900347E+10 | 0.109322E+11 |
February | 0.694530E+12 | 0.333411E+11 | 0.00 | 0.561202E+10 | 0.145302E+11 |
March | 0.961984E+12 | 0.433796E+11 | 0.00 | 0.461325E+10 | 0.225722E+11 |
April | 0.105655E+13 | 0.479820E+11 | 0.00 | -0.152857E+10 | 0.392679E+11 |
May | 0.103708E+13 | 0.501080E+11 | 0.00 | -0.983914E+10 | 0.601680E+11 |
June | 0.943769E+12 | 0.566909E+11 | 0.00 | -0.175704E+11 | 0.717389E+11 |
July | 0.103607E+13 | 0.635280E+11 | 0.00 | -0.210480E+11 | 0.796987E+11 |
August | 0.108467E+13 | 0.535085E+11 | 0.00 | -0.199176E+11 | 0.774378E+11 |
September | 0.839915E+12 | 0.529958E+11 | 0.00 | -0.174224E+11 | 0.709834E+11 |
October | 0.813571E+12 | 0.420189E+11 | 0.00 | -0.117799E+11 | 0.558505E+11 |
November | 0.606395E+12 | 0.338430E+11 | 0.00 | -0.163879E+10 | 0.323975E+11 |
December | 0.612932E+12 | 0.324178E+11 | 0.00 | 0.633746E+10 | 0.159035E+11 |
Annual Sum or Average | 0.103275E+14 | 0.540247E+12 | 0.00 | -0.751786E+11 | 0.551481E+12 |
Minimum of Months | 0.606395E+12 | 0.304337E+11 | 0.00 | -0.210480E+11 | 0.109322E+11 |
Maximum of Months | 0.108467E+13 | 0.635280E+11 | 0.00 | 0.900347E+10 | 0.796987E+11 |