Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 10:42:37
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 880.90 | 182.19 | 182.19 |
Net Site Energy | 880.90 | 182.19 | 182.19 |
Total Source Energy | 1715.28 | 354.75 | 354.75 |
Net Source Energy | 1715.28 | 354.75 | 354.75 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 515.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 96.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 365.05 | 515.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 515.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 96.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 3.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 27.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 515.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 96.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 31.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 25.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 32.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 14.48 | 106.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 75.50 | 106.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 32.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 14.48 | 106.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 75.50 | 106.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 365.047 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 365.047 | 100.00 |
Total On-Site and Utility Electric Sources | 365.047 | 100.00 |
Total Electricity End Uses | 365.047 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 66.00 |
Time Setpoint Not Met During Occupied Cooling | 3.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3118.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 9.3385 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.7674 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 5.0950 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 5.0950 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 9.3385 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.7674 | 46.45 | 2.5587 | |
Total | 4835.13 | 5.0950 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 5.0950 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 5.0950 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-15:09 | 21-DEC-17:00 | - | - | - | - | - | - | - | - | - | - | 22-AUG-11:09 |
Heating | 0.00 | 259838.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 11617.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5967.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4675.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1602.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 33897.57 | 259838.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 259838.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 11617.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5967.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2370.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1602.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 559.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 41.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 305.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 196.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 98.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 82.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1156.10 | 559.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 115.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 63.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 239.10 | 115.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 115.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 63.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 239.10 | 115.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.24 |
ZONE2 FINE STORAGE DIRECT AIR | 2.62 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 3.95 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 3.95 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 131231.96 |
PSZ-OFFICE HEATING COIL | 27006.34 |
PSZ-FINE STORAGE HEATING COIL | 76751.89 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 131231.97 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.00 | 1.00 | 1.24 |
PSZ-FINE STORAGE | 2.62 | 2.62 | 2.62 | 2.62 | 2.62 | 2.62 | 1.00 | 1.00 | 2.62 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.24 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.62 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.24 | 1373.73 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.62 | 2798.72 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 0.818908 | 20539.15 | 27006.34 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.62 | 2.62 | 2.62 | 1.73 | 49267.09 | 76751.89 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.24 | 0.620385 | 0.827180 | 20539.15 | 10269.58 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 2.62 | 1.31 | 1.74 | 49267.09 | 24633.54 | 0.800100 | 0.800100 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 9.339 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 17.412 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.767 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.326 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2212.108 | 9.339 | 173.516 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2212.108 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 12073.795 | 3.767 | 174.983 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 12073.795 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2163 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.4974 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.3694 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.044 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.622 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.010 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.608 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4892 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.18741198E-13 | -0.13599760E-18 | 0.18147593E-18 | 0.0000000 |
2 | 1 | -5.2160601 | 0.51384690E-04 | -0.74050972E-04 | 0.35929797E-14 |
3 | 0 | 5.4323994 | 0.21628790 | 0.21641333 | |
4 | 2 | 0.53330648E-11 | 0.17872838E-15 | 0.22136589E-15 | 0.0000000 |
5 | 1 | -5.2159880 | 0.41449123E-04 | -0.32205733E-04 | 0.68736940E-11 |
6 | 0 | 5.7134214 | 0.49739196 | 0.49746561 | |
7 | 4 | 0.80462617E-12 | 0.82840410E-16 | -0.20078756E-14 | 0.11271485E-15 |
8 | 3 | -0.39242815E-03 | 0.26180773E-06 | -0.56999769E-04 | 0.15438257E-12 |
9 | 2 | 1.7577325 | 0.56772723E-02 | 1.1542901 | -0.75235290E-04 |
10 | 1 | -7.1048256 | 0.14632850 | -17.186369 | 0.33689683 |
11 | 0 | 5.5924660 | 0.92974441E-01 | 16.277116 | |
12 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
13 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
14 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
15 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
16 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.0441747 | 2.0441747 | 2.0441747 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.25659737E-14 | 0.20825084E-15 | 0.74747876E-12 | 0.12362927E-15 |
85 | 3 | -0.54038165E-04 | 0.45238042E-06 | -0.37328678E-03 | 0.14344535E-12 |
86 | 2 | 1.1198054 | 0.10013958E-01 | 1.7123825 | -0.71564441E-04 |
87 | 1 | -16.966117 | 0.26145347 | -7.1648294 | 0.32817431 |
88 | 0 | 16.285382 | 0.16754891 | 5.8918369 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.379_SHGC_SOUTH_0.38 | 34 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 | ||
2 | NONRESWINDOW_U_0.379_SHGC_NORTH_0.38 | 35 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 | ||
3 | NONRESWINDOW_U_0.379_SHGC_EAST_0.38 | 36 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 | ||
4 | NONRESWINDOW_U_0.379_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 | ||
5 | SKYLIGHT_U_0.5_SHGC_0.4 | 38 | 1 | VerySmooth | 2.843 | 2.843 | 1.000 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | 39 | 1 | VerySmooth | 5.556 | 5.556 | 1.000 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 0.10078 | 0.10078 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.14909 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | CurtainWall | 2.775 | 0.408 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.268 | 0.549 | 0.552 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.4791E-005 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.7194E-004 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4670E-005 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1653E-004 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.5841E-005 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7606E-004 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5724E-005 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5867E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6096E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.6607E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3424E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.1358E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5567E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9348E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3414E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4540E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6296E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7376E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0327E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9593E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.7744E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2308E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8792E-004 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6675E-005 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.8656E-004 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.5258E-005 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2153E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0396E-004 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0886E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.4263E-005 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3392E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0724E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.2404E-004 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6071E-005 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.5427E-004 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.9519E-005 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.1125E-004 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9301E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9718E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6272E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.2683E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4723E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.7927E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6143E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6433E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4089E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7955E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4789E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.0626E-004 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6027E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0836E-003 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7769E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8310E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4442E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3679E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4861E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6723E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0501E-005 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8637E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.5089E-005 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7889E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0506E-005 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1133E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6508E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4915E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1357E-004 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3793E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2719E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2881E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.9327E-005 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5808E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1684E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9024E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6507E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.8627E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1248E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4292E-004 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4999E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6286E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1734E-005 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0742E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.4990E-004 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6916E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0030E-004 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9319E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.4780E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3102E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8162E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4163E-005 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5379E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1496E-005 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7558E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1016E-005 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4663E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0760E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8446E-004 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2071E-005 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6584E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7392E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6019E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8484E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4444E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7398E-005 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1825E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9867E-005 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3670E-004 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.5813E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8666E-004 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7581E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1513E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5431E-005 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2422E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9451E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4524E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2876E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1174E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2479E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6103E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1321E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9767E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0309E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9587E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8132E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0280E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4034E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7947E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4814E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2243E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9585E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0209E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2930E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8455E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2234E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0359E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1298E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2681E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3733E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7545E-004 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9760E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9369E-004 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9564E-004 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3529E-004 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5955E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2983E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1534E-004 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9165E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2237E-004 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9744E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9134E-005 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3166E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1757E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1077E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1093E-004 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5483E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1679E-004 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4854E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7649E-005 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6790E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1734E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2731E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1790E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2320E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7217E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.3169E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9201E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9535E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5935E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1887E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6516E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2042E-003 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7046E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4671E-003 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6611E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6703E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6979E-005 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3777E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1684E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9704E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3991E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2100E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0693E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7826E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0720E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4148E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7478E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9091E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8508E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.7793E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9580E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4096E-005 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0708E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6592E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5874E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8445E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6252E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7141E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6294E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1004E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6898E-005 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5662E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1844E-003 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0372E-004 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3049E-003 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8240E-005 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2787E-003 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2286E-004 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2032E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0902E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2364E-003 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4509E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3714E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5217E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3042E-003 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5905E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2112E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4671E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0783E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0555E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0134E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8462E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6219E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4491E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7473E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9066E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1494E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0091E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0972E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3188E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6785E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8401E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7498E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5506E-004 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2149E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0971E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0049E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8258E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1832E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5274E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7446E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1536E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3256E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0740E-004 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2762E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7745E-005 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9892E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3498E-004 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2227E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1450E-004 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3566E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8850E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3126E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4941E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0227E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6112E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2269E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1533E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2644E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1578E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0595E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1455E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2515E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0683E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7501E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6479E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8374E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9451E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5851E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6517E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4671E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2577E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7296E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1506E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8541E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1145E-003 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6039E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4568E-004 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5139E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5741E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7351E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5793E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9035E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6913E-005 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6988E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.5996E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1524E-003 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1531E-004 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1889E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1418E-004 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9588E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6036E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7589E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0670E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1673E-003 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2754E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1930E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0887E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2791E-004 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1558E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0865E-004 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3304E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4056E-004 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4882E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7289E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2588E-004 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4259E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0699E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7667E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7056E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7942E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2955E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0178E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4028E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0414E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0131E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8179E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5916E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3861E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6575E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4795E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1676E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2786E-004 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6551E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0837E-004 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3810E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3855E-004 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7928E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7264E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8999E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4360E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6730E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2549E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3452E-004 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7852E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3980E-004 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5891E-005 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3195E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5078E-004 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1339E-004 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2233E-004 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4315E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2864E-004 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9823E-005 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0257E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3913E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4557E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3211E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2590E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0926E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7149E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3510E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5813E-005 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5594E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4274E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8960E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7643E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9661E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7608E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2603E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0101E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0338E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5103E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2056E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2242E-004 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5461E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2793E-004 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8871E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0246E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6189E-005 |
369 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 6.2718E-003 |
370 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 7.2486E-004 |
371 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.7130E-003 |
372 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.6557E-004 |
373 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.3364E-003 |
374 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.2888E-004 |
375 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9885E-003 |
376 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.2476E-004 |
377 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.4650E-004 |
378 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.6295E-003 |
379 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.0400E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.6522E-003 |
381 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.4222E-004 |
382 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.7198E-003 |
383 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.1878E-004 |
384 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.0194E-003 |
385 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 5.5249E-003 |
386 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.9120E-004 |
387 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.1143E-003 |
388 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0747E-004 |
389 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.6462E-003 |
390 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.3194E-004 |
391 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.7483E-003 |
392 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1965E-004 |
393 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.4950E-003 |
394 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.9109E-004 |
395 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.0998E-003 |
396 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.0741E-004 |
397 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.6768E-003 |
398 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.3200E-004 |
399 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.7482E-003 |
400 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1965E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10201.71974 | 12242.06368 | 1.03398 | 1.24077 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 32.42000 | 5.47299E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 9359.90538 | 11231.88646 | 0.32371 | 0.38845 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90000 | 9.55238E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 27588.89160 | 33106.66992 | 2.17959 | 2.61551 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.90000 | 5.47527E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 29071.20744 | 34885.44892 | 0.84679 | 1.01615 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -17.90000 | 9.55238E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 109359.97324 | 131231.96789 | 3.29169 | 3.95003 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15379.49 | 1.24077 | 1.24077 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 11142.99 | 0.38845 | 0.38845 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 40765.86 | 2.61551 | 2.61551 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 38352.63 | 1.01615 | 1.01615 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24077 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.61551 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.95003 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 3.95003 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 131231.96026 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 131231.96789 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24077 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24077 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24077 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24077 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.24077 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.24077 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.61551 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.61551 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.61551 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.61551 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.61551 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.61551 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.24077 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.61551 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.24077 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.24077 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1373.72963 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.24077 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.24077 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.24077 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.81891 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.24077 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62039 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.82718 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20539.15000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10269.57500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20539.15000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27006.34122 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 27006.34122 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.61551 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.61551 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2798.71955 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.61551 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.61551 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.61551 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.72624 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.61551 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.30776 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.74367 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 49267.09000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 24633.54500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80010 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80010 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 49267.09000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 76751.88602 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 76751.88602 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 19576.4 | 11.40 | 11.14 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 47236.6 | 11.53 | 11.27 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1882782091 | 0.1838359596 | Pass | Pass | 1.3030382113 | 7.3351111190 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4301361789 | 0.4250610600 | Pass | Pass | 1.6899006934 | 9.4586094052 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.0134785314E-002 | 2.2850887614E-002 | Pass | Pass | 5.2711315362E-002 | 0.1374761502 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 9892.94 | 485.54 | 0.00 | 59.08 | 187.46 | 10625.05 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.210 | 0.216 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.466 | 0.497 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.565 | 0.653 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.565 | 0.653 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.379_SHGC_WEST_0.38 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.153 | 0.381 | 0.420 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.379_SHGC_WEST_0.38 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.153 | 0.381 | 0.420 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.379_SHGC_NORTH_0.38 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.153 | 0.381 | 0.420 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.379_SHGC_NORTH_0.38 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.153 | 0.381 | 0.420 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 4.201 | 0.480 | 0.488 | |||||||||||||||||
North Total or Average | 6.51 | 2.153 | 0.381 | 0.420 | |||||||||||||||||
Non-North Total or Average | 79.53 | 4.369 | 0.488 | 0.494 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 9.3385 | 236.88 | 2212.11 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 32.18 | 0.0000 | Y | 13.36 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 21.44 | 0.0000 | Y | 41.65 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.7674 | 3204.84 | 12073.79 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 18.34 | 0.0000 | Y | 41.56 |
Interior Lighting Total | 5.0950 | 4835.13 | 24634.88 | 96.57 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10348.98 | 2587.24 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10348.98 | 2587.24 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 12073.79 | 3018.45 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 12073.79 | 3018.45 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.29 | 2212.11 | 641.51 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.10 | 2212.11 | 221.21 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 42.26 | 42.26 | 0.98 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.67 | 62.97 | 50.89 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.67 | 49.13 | 10.07 | |
Exterior Lighting Total | 5520.82 | 61.94 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20539.15 | 16444.88 | 4094.27 | 0.80 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 49267.09 | 39418.60 | 9848.49 | 0.80 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 19576.4 | 11.40 | 11.14 | ||||
PSZ-FINE STORAGE COOLING COIL | 47236.6 | 11.53 | 11.27 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 131231.96 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 27006.34 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 76751.89 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.95 | 367.00 | 92.91 | 1.00 | 3.24 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.24 | 1373.73 | 1107.16 | 1.00 | 1.35 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.62 | 2798.72 | 1070.05 | 1.00 | 1.28 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10201.72 | 12242.06 | 51.68 | 1.034 | 1.241 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 23.90 | 23.90 | 0.00821 | 32.42 | 0.00547 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 27588.89 | 33106.67 | 23.76 | 2.180 | 2.616 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 26.70 | 26.70 | 0.00811 | 33.90 | 0.00548 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 0.00 | 33.99 | 0.00557 | 33.90 | 0.00548 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9359.91 | 11231.89 | 47.42 | 0.324 | 0.388 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00780 | -17.90 | 0.00096 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 29071.21 | 34885.45 | 25.04 | 0.847 | 1.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00660 | -17.90 | 0.00096 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 109359.97 | 131231.97 | 40.95 | 3.292 | 3.950 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00605 | -17.90 | 0.00096 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.24 | 1.24 | 0.39 | 0.39 | 1.2408 | 1.2408 | 1.2408 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.62 | 2.62 | 1.02 | 1.02 | 2.6155 | 2.6155 | 2.6155 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 131231.960 | 131231.960 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 131231.96 | 131231.96 | 3.950033 | 10.00 | 6.58 | 0.00605311 | 43.33 | 19.68 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 10.00 | 0.00605311 | 64.5580 | 131231.97 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 20539.150 | 16444.876 | 1.240770 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 10269.58 | 10269.58 | 0.827180 | 25.75 | 14.41 | 0.00798517 | 12.00 | 9.41 | 0.00798517 | 32.81 | 0.00547359 | 14.72 | 12.3655 | 23.90 | 0.00821111 | 36.1133 | 10189.57 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 27006.341 | 27006.341 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 27006.34 | 27006.34 | 1.240770 | 17.84 | 10.96 | 0.00723373 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 8.2436 | 21.10 | 0.00779781 | 40.6836 | 9359.91 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 49267.090 | 39418.599 | 2.615510 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24633.54 | 24633.54 | 1.743673 | 28.94 | 15.22 | 0.00768301 | 12.00 | 9.11 | 0.00768301 | 33.90 | 0.00547527 | 15.07 | 24.3573 | 26.70 | 0.00811101 | 30.2041 | 27588.89 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 76751.886 | 76751.886 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 76751.89 | 76751.89 | 2.615510 | 10.12 | 6.24 | 0.00568585 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 16.2382 | 15.56 | 0.00660293 | 48.8767 | 29071.21 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 131231.960 | 131231.960 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 3.950033 | 3.86091060 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 131231.96 | 131231.96 | 1.0000 | 3.86091060 | 3.950033 | 10.00 | 6.58 | 0.00605311 | 25296.5 | 43.33 | 19.68 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 131231.96 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 10.00 | 0.00605311 | 10.00 | 0.00605311 | 64.5580 | 131231.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20539.150 | 16444.876 | 1.240770 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6840 | 1004.8586 | 0.9774 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.240770 | 1.21277552 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | Sensible | 10269.58 | 10269.58 | 1.0000 | 0.80851684 | 0.827180 | 25.75 | 14.41 | 0.00798517 | 46223.0 | 12.00 | 9.41 | 0.00798517 | 32206.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10269.58 | 32.81 | 0.00547359 | 14.72 | 0.10228463 | 12.3655 | 23.90 | 0.00821111 | 23.90 | 0.00821111 | 36.1133 | 10189.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27006.341 | 27006.341 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.240770 | 1.21277552 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 27006.34 | 27006.34 | 1.0000 | 1.21277552 | 1.240770 | 17.84 | 10.96 | 0.00723373 | 36256.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27006.34 | -17.90 | 0.00095524 | -17.90 | 0.10228463 | 8.2436 | 21.05 | 0.00779781 | 21.10 | 0.00779781 | 40.6836 | 9359.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 49267.090 | 39418.599 | 2.615510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1223 | 1004.8586 | 0.9774 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.615510 | 2.55649804 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 24633.54 | 24633.54 | 1.0000 | 1.70433190 | 1.743673 | 28.94 | 15.22 | 0.00768301 | 48711.3 | 12.00 | 9.11 | 0.00768301 | 31444.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24633.54 | 33.90 | 0.00547527 | 15.07 | 0.42471127 | 24.3573 | 26.70 | 0.00811101 | 26.70 | 0.00811101 | 30.2041 | 27588.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 76751.886 | 76751.886 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.615510 | 2.55649804 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 76751.89 | 76751.89 | 1.0000 | 2.55649804 | 2.615510 | 10.12 | 6.24 | 0.00568585 | 24498.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 76751.89 | -17.90 | 0.00095524 | -17.90 | 0.42471127 | 16.2382 | 15.56 | 0.00660293 | 15.56 | 0.00660293 | 48.8767 | 29071.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.24 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.62 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2493.00 | 2613.00 | 1865.00 |
ZONE2 FINE STORAGE | 3177.33 | 2812.33 | 2433.83 |
ZONE3 BULK STORAGE | 3320.50 | 3379.50 | 3110.17 |
Facility | 3359.33 | 3463.50 | 3118.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 90.00 | 3.50 | 56.17 | 3.50 |
ZONE2 FINE STORAGE | 405.00 | 16.83 | 24.50 | 0.00 |
ZONE3 BULK STORAGE | 3.50 | 0.00 | 0.00 | 0.00 |
Facility | 470.33 | 20.33 | 66.00 | 3.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.547 | 0.305 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.501 | 0.237 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.122 | 0.000 | 0.389 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.47 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.29 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.04 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1991459.19 | 0.00 | 1991459.19 | 1841849.66 | 3833308.85 | 3225648.14 | 5657.69 | 2509.22 | 593.09 | 0.00 |
ZONE2 FINE STORAGE | 5381604.20 | 0.00 | 5381604.20 | 6789202.86 | 12170807.06 | 13393694.68 | 5721.67 | 2733.50 | 304.83 | 6.83 |
ZONE3 BULK STORAGE | 0.00 | 72374429.91 | 72374429.91 | 32958882.24 | 0.11E+09 | 30805497.77 | 7834.56 | 35.83 | 889.61 | 5116.83 |
Total Facility | 7373063.39 | 72374429.91 | 79747493.29 | 41589934.76 | 0.12E+09 | 47424840.58 | 8202.69 | 2906.81 | 1603.22 | 5116.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1521 | 0.0000 | 0.1521 | 0.0849 | 0.2371 | 0.1023 | 533.69 | 2509.22 | 593.09 |
ZONE2 FINE STORAGE | 0.4090 | 0.0000 | 0.4090 | 0.1939 | 0.6028 | 0.4247 | 604.17 | 2733.50 | 298.33 |
ZONE3 BULK STORAGE | 0.0000 | 3.7186 | 3.7186 | 1.1978 | 4.9164 | 0.9768 | 3058.86 | 17.33 | 559.81 |
Total Facility | 0.5611 | 3.7186 | 4.2797 | 1.4766 | 5.7563 | 1.5038 | 3078.69 | 2888.31 | 1267.73 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1902564.67 | 0.00 | 1902564.67 | 3225648.14 | 8167.74 | 0.67 | 591.59 | 0.00 |
PSZ-FINE STORAGE | 5141487.39 | 0.00 | 5141487.39 | 13393694.68 | 8456.17 | 0.33 | 303.50 | 6.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1453 | 0.0000 | 0.1453 | 0.1023 | 3043.74 | 0.67 | 591.59 |
PSZ-FINE STORAGE | 0.3907 | 0.0000 | 0.3907 | 0.4247 | 3338.67 | 0.33 | 297.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2913.65 | 201.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2949.47 | 90.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1601 | 0.3096 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.4592 | 0.7735 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 446 |
Defaulted Fields | 391 |
Fields with Defaults | 1172 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 365.05 | 1565.96 | 29-JAN-09:30 | 33897.57 | 26-JUN-15:10 |
Electricity:Building | 236.67 | 1084.96 | 08-JAN-11:00 | 19728.80 | 04-JAN-15:10 |
Electricity:Zone:ZONE1 OFFICE | 42.53 | 520.87 | 01-JAN-00:10 | 3190.10 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 233.08 | 1084.96 | 08-JAN-11:00 | 19728.80 | 04-JAN-15:10 |
InteriorLights:Electricity | 96.57 | 615.08 | 08-JAN-11:00 | 9693.63 | 04-JAN-15:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 13.36 | 51.00 | 01-JAN-00:10 | 1355.05 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 96.57 | 615.08 | 08-JAN-11:00 | 9693.63 | 04-JAN-15:10 |
LightsWired:InteriorLights:Electricity | 96.57 | 615.08 | 08-JAN-11:00 | 9693.63 | 04-JAN-15:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 13.36 | 51.00 | 01-JAN-00:10 | 1355.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 96.57 | 615.08 | 08-JAN-11:00 | 9693.63 | 04-JAN-15:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 41.65 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 41.65 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 41.65 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 152.50 | 264.11 | 08-JAN-11:00 | 13476.65 | 24-JUN-16:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 41.56 | 264.11 | 08-JAN-11:00 | 4490.00 | 02-JAN-15:50 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 41.56 | 264.11 | 08-JAN-11:00 | 4490.00 | 02-JAN-15:50 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 31.05 | 0.00 | 01-JAN-09:30 | 4675.45 | 26-JUN-15:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 3.60 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-09:50 |
Ventilation (simple):Fans:Electricity | 3.60 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-09:50 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 3.60 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-09:50 |
ElectricityPurchased:Facility | 365.05 | 1565.96 | 11-JUN-13:00 | 33897.57 | 26-JUN-15:10 |
ElectricityPurchased:Plant | 365.05 | 1565.96 | 11-JUN-13:00 | 33897.57 | 26-JUN-15:10 |
Cogeneration:ElectricityPurchased | 365.05 | 1565.96 | 11-JUN-13:00 | 33897.57 | 26-JUN-15:10 |
General:Cogeneration:ElectricityPurchased | 365.05 | 1565.96 | 11-JUN-13:00 | 33897.57 | 26-JUN-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 365.05 | 1565.96 | 11-JUN-13:00 | 33897.57 | 26-JUN-15:10 |
ElectricityNet:Plant | 365.05 | 1565.96 | 11-JUN-13:00 | 33897.57 | 26-JUN-15:10 |
Cogeneration:ElectricityNet | 365.05 | 1565.96 | 11-JUN-13:00 | 33897.57 | 26-JUN-15:10 |
General:Cogeneration:ElectricityNet | 365.05 | 1565.96 | 11-JUN-13:00 | 33897.57 | 26-JUN-15:10 |
Electricity:HVAC | 40.44 | 0.00 | 01-JAN-09:30 | 13987.56 | 26-JUN-15:10 |
General:Fans:Electricity | 27.46 | 0.00 | 01-JAN-09:30 | 3792.58 | 21-DEC-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 12.98 | 0.00 | 01-JAN-00:10 | 11617.39 | 26-JUN-15:10 |
General:Cooling:Electricity | 12.98 | 0.00 | 01-JAN-00:10 | 11617.39 | 26-JUN-15:10 |
ExteriorLights:Electricity | 61.94 | 0.00 | 01-JAN-07:30 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.94 | 0.00 | 01-JAN-07:30 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 25.99 | 481.00 | 06-FEB-07:00 | 2602.69 | 10-FEB-12:20 |
WaterSystems:Electricity | 25.99 | 481.00 | 06-FEB-07:00 | 2602.69 | 10-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 25.99 | 481.00 | 06-FEB-07:00 | 2602.69 | 10-FEB-12:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 515.85 | 0.00 | 01-JAN-09:30 | 259838.89 | 21-DEC-18:00 |
NaturalGas:HVAC | 515.85 | 0.00 | 01-JAN-09:30 | 259838.89 | 21-DEC-18:00 |
Heating:NaturalGas | 515.85 | 0.00 | 01-JAN-09:30 | 259838.89 | 21-DEC-18:00 |
General:Heating:NaturalGas | 515.85 | 0.00 | 01-JAN-09:30 | 259838.89 | 21-DEC-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 22-AUG-11:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 22-AUG-11:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 22-AUG-11:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 22-AUG-11:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 22-AUG-11:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 22-AUG-11:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 22-AUG-11:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 22-AUG-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 877.16 | 0.00 | 01-JAN-09:30 | 390799.09 | 21-DEC-18:00 |
EnergyTransfer:Building | 436.56 | 0.00 | 01-JAN-09:30 | 190253.96 | 23-DEC-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 49.39 | 0.00 | 01-JAN-00:10 | 19477.62 | 21-DEC-07:10 |
Heating:EnergyTransfer | 380.33 | 0.00 | 01-JAN-09:30 | 190253.96 | 23-DEC-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 27.87 | 0.00 | 01-JAN-00:10 | 19477.62 | 21-DEC-07:10 |
General:Heating:EnergyTransfer | 380.33 | 0.00 | 01-JAN-09:30 | 190253.96 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 27.87 | 0.00 | 01-JAN-00:10 | 19477.62 | 21-DEC-07:10 |
Cooling:EnergyTransfer | 56.23 | 0.00 | 01-JAN-00:10 | 27908.67 | 26-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 21.52 | 0.00 | 01-JAN-00:10 | 9376.31 | 26-JUN-17:00 |
General:Cooling:EnergyTransfer | 56.23 | 0.00 | 01-JAN-00:10 | 27908.67 | 26-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 21.52 | 0.00 | 01-JAN-00:10 | 9376.31 | 26-JUN-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 127.01 | 0.00 | 01-JAN-00:10 | 46347.17 | 19-MAR-07:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 92.30 | 0.00 | 01-JAN-00:10 | 46347.17 | 19-MAR-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 92.30 | 0.00 | 01-JAN-00:10 | 46347.17 | 19-MAR-07:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 34.71 | 0.00 | 01-JAN-00:10 | 19335.26 | 26-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 34.71 | 0.00 | 01-JAN-00:10 | 19335.26 | 26-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 260.15 | 0.00 | 01-JAN-09:30 | 132168.82 | 21-DEC-18:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 260.15 | 0.00 | 01-JAN-09:30 | 132168.82 | 21-DEC-18:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 260.15 | 0.00 | 01-JAN-09:30 | 132168.82 | 21-DEC-18:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 440.60 | 0.00 | 01-JAN-09:30 | 203224.56 | 21-DEC-18:00 |
HeatingCoils:EnergyTransfer | 390.98 | 0.00 | 01-JAN-09:30 | 203224.56 | 21-DEC-18:00 |
CoolingCoils:EnergyTransfer | 49.61 | 0.00 | 01-JAN-00:10 | 37105.24 | 26-JUN-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 27.869 | -21.523 | 0.000 | 0.000 | 10.003 | 13.363 | 29.165 | 13.540 | 0.000 | 1.047 | 0.000 | 0.000 | -8.622 | 0.000 | -20.761 | -44.080 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 92.304 | -34.709 | 0.000 | 0.000 | 25.438 | 41.648 | 0.000 | 37.764 | 0.000 | 1.725 | 0.001 | 0.000 | -15.203 | 0.000 | -67.647 | -81.319 |
ZONE3 BULK STORAGE | 260.153 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 60.605 | 41.557 | 107.344 | 545.121 | 0.000 | 22.822 | 0.000 | 0.000 | -215.768 | 0.000 | -386.269 | -435.565 |
Total Facility | 260.153 | 0.000 | 120.172 | -56.232 | 0.000 | 0.000 | 96.046 | 96.568 | 136.508 | 596.425 | 0.000 | 25.593 | 0.001 | 0.000 | -239.592 | 0.000 | -474.677 | -560.964 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-AUG-05:02 | 0.00 | 0.00 | 0.00 | -27644.62 | 0.00 | 0.00 | 86.24 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 27857.11 | 0.00 | -484.68 | 0.00 | -415.56 | 0.00 |
ZONE2 FINE STORAGE | 24-JUL-17:08 | 0.00 | 0.00 | 0.00 | -41431.86 | 0.00 | 0.00 | 0.00 | 452.77 | 0.00 | 1823.94 | 0.00 | 1375.68 | 37779.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-17:08 | 0.00 | 0.00 | 0.00 | -41431.86 | 0.00 | 0.00 | 0.00 | 1042.16 | 2519.91 | 71297.44 | 0.00 | 7103.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -40530.83 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 20-DEC-06:31 | 0.00 | 0.00 | 27811.45 | 0.00 | 0.00 | 0.00 | 118.54 | 404.75 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1184.91 | 0.00 | -3205.18 | -24495.18 |
ZONE2 FINE STORAGE | 18-MAR-21:42 | 0.00 | 0.00 | 79716.72 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1289.01 | 0.00 | -16764.41 | -61963.28 |
ZONE3 BULK STORAGE | 21-DEC-18:00 | 132166.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2666.10 | 3169.37 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -33270.00 | 0.00 | -88909.42 | -17872.31 |
Total Facility | 23-DEC-06:01 | 131606.27 | 0.00 | 105174.91 | 0.00 | 0.00 | 0.00 | 1451.20 | 879.19 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -35867.32 | 0.00 | -81900.61 | -123944.19 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2408 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2408 | 0.0824 | 1.0000 | Not calculated | 0.1023 | 0.0824 | ||
PSZ-FINE STORAGE | 2.6155 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.6155 | 0.1624 | 1.0000 | Not calculated | 0.4247 | 0.1624 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2408 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2408 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0824 | ||
PSZ-FINE STORAGE | 2.6155 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.6155 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1624 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2408 | 1.2408 | 1.2408 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6155 | 2.6155 | 2.6155 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2408 | 1.2408 | 1.2408 | 1.2408 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.6155 | 2.6155 | 2.6155 | 2.6155 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2408 | 1.2408 | 1.2408 | No | 0.1023 | 0.2633 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6155 | 2.6155 | 2.6155 | No | 0.4247 | 0.4180 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2408 | 1.2408 | 1.2408 | 1.2408 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.6155 | 2.6155 | 2.6155 | 2.6155 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 66.00 |
Number of hours cooling loads not met | 3.50 |
Number of hours not met | 69.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 515.85 | 259838.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 12.98 | 11617.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 96.57 | 9693.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.94 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 3.60 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 27.46 | 3792.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.99 | 2602.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 365.05 |
Natural Gas | 0.00 | 515.85 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 880.90 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 19.97 |
Space Heating | 0.00 |
Space Cooling | 2.69 |
Fans (All) | 6.42 |
Service Water Heating | 5.38 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 75.50 |
Subtotal | 75.50 |
Natural Gas [MJ/m2] | |
Space Heating | 106.69 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 106.69 |
Subtotal | 106.69 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.96 |
Space Heating | 58.56 |
Space Cooling | 1.47 |
Fans (All) | 3.53 |
Service Water Heating | 2.95 |
Receptacle Equipment | 15.50 |
Miscellaneous | 7.03 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8635.00 | 125.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8664.50 | 95.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7238.83 | 1512.33 | 8.83 | 0.00 | 0.00 |
Min | 7238.83 | 95.50 | 0.00 | 0.00 | 0.00 |
Max | 8664.50 | 1512.33 | 8.83 | 0.00 | 0.00 |
Average | 8179.44 | 577.61 | 2.94 | 0.00 | 0.00 |
Sum | 24538.33 | 1732.83 | 8.83 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 80703.00 | 2016.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 143398.33 | 47382.67 | 412.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 143398.33 | 47382.67 | 412.00 | 0.00 | 0.00 |
Average | 85709.44 | 16466.22 | 137.33 | 0.00 | 0.00 |
Sum | 257128.33 | 49398.67 | 412.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8662.83 | 97.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8540.83 | 219.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7926.17 | 833.83 | 0.00 | 0.00 | 0.00 |
Min | 7926.17 | 97.17 | 0.00 | 0.00 | 0.00 |
Max | 8662.83 | 833.83 | 0.00 | 0.00 | 0.00 |
Average | 8376.61 | 383.39 | 0.00 | 0.00 | 0.00 |
Sum | 25129.83 | 1150.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33026.33 | 0.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 79643.50 | 3075.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 163421.33 | 27771.67 | 0.00 | 0.00 | 0.00 |
Min | 33026.33 | 0.67 | 0.00 | 0.00 | 0.00 |
Max | 163421.33 | 27771.67 | 0.00 | 0.00 | 0.00 |
Average | 92030.39 | 10282.61 | 0.00 | 0.00 | 0.00 |
Sum | 276091.17 | 30847.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19535144.99 | 834.76 | 21-JAN-17:00 | 7.00 | 3.14 | 0.501363E+09 | 706.22 | 20-JAN-15:50 | 7.00 | 3.14 |
February | 12003010.63 | 457.88 | 25-FEB-15:00 | 12.00 | 3.79 | 0.459261E+09 | 700.74 | 18-FEB-15:09 | 12.00 | 3.79 |
March | 60261450.71 | 1366.67 | 15-MAR-16:00 | 19.00 | 5.38 | 0.555604E+09 | 768.96 | 14-MAR-15:39 | 19.00 | 5.38 |
April | 40039038.25 | 577.32 | 10-APR-15:00 | 10.00 | 1.40 | 0.515465E+09 | 768.91 | 07-APR-15:00 | 10.00 | 1.40 |
May | 0.773898E+09 | 3677.93 | 31-MAY-16:00 | 28.00 | 14.86 | 0.613736E+09 | 768.98 | 31-MAY-15:00 | 28.00 | 14.86 |
June | 0.502965E+10 | 24955.95 | 28-JUN-05:02 | 15.27 | 6.83 | 0.659514E+09 | 769.05 | 26-JUN-14:20 | 15.27 | 6.83 |
July | 0.517450E+10 | 23037.66 | 01-JUL-05:02 | 17.50 | 6.40 | 0.634676E+09 | 769.04 | 27-JUL-14:00 | 18.00 | 14.77 |
August | 0.561187E+10 | 27647.43 | 17-AUG-05:02 | 12.00 | 4.88 | 0.685412E+09 | 769.04 | 21-AUG-15:00 | 19.00 | 16.33 |
September | 0.401725E+10 | 23425.06 | 11-SEP-05:01 | 17.88 | 8.62 | 0.630506E+09 | 769.03 | 01-SEP-14:09 | 17.88 | 8.62 |
October | 0.685452E+09 | 4026.98 | 11-OCT-15:10 | 25.67 | 9.32 | 0.559920E+09 | 768.96 | 07-OCT-14:09 | 25.67 | 9.32 |
November | 82513695.52 | 981.50 | 18-NOV-17:00 | 5.00 | 4.46 | 0.493656E+09 | 768.96 | 09-NOV-14:00 | 5.00 | 4.46 |
December | 16166684.23 | 652.09 | 16-DEC-13:30 | 8.00 | 2.19 | 0.501557E+09 | 732.31 | 02-DEC-15:30 | 8.00 | 2.19 |
Annual Sum or Average | 0.215231E+11 | 0.681067E+10 | ||||||||
Minimum of Months | 12003010.63 | 457.88 | 5.00 | 1.40 | 0.459261E+09 | 700.74 | 5.00 | 1.40 | ||
Maximum of Months | 0.561187E+10 | 27647.43 | 28.00 | 14.86 | 0.685412E+09 | 769.05 | 28.00 | 16.33 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114166E+10 | 5590.58 | 11-JAN-11:10 | -0.7 | -0.7 | 0.715651E+09 | 1256.28 | 20-JAN-14:30 | 20.50 | 6.87 |
February | 0.116392E+10 | 4886.22 | 09-FEB-14:00 | 1.00 | -4.2 | 0.645219E+09 | 1283.39 | 18-FEB-14:39 | 19.33 | 7.91 |
March | 0.971059E+09 | 5883.83 | 27-MAR-12:05 | -2.2 | -2.2 | 0.857575E+09 | 1619.78 | 15-MAR-15:09 | -2.2 | -2.2 |
April | 0.115892E+10 | 5461.98 | 22-APR-08:70 | 0.00 | -0.1 | 0.817385E+09 | 1467.60 | 20-APR-13:30 | 0.00 | -0.1 |
May | 0.916807E+09 | 4251.40 | 19-MAY-07:10 | 6.33 | 4.13 | 0.125855E+10 | 2086.70 | 31-MAY-15:00 | 28.00 | 14.86 |
June | 0.698193E+10 | 39603.54 | 27-JUN-17:06 | 32.62 | 14.59 | 0.187306E+10 | 2246.92 | 26-JUN-15:20 | 32.62 | 14.59 |
July | 0.767954E+10 | 41432.61 | 24-JUL-17:08 | 32.50 | 16.48 | 0.183184E+10 | 2246.89 | 27-JUL-14:09 | 24.67 | 16.66 |
August | 0.764820E+10 | 41309.83 | 20-AUG-15:03 | 28.00 | 13.92 | 0.196557E+10 | 2246.90 | 04-AUG-10:00 | 28.00 | 13.92 |
September | 0.348988E+10 | 39424.03 | 10-SEP-14:43 | 31.78 | 12.50 | 0.169992E+10 | 2246.85 | 01-SEP-12:20 | 31.78 | 12.50 |
October | 0.151360E+10 | 6608.54 | 12-OCT-08:20 | 1.33 | 0.89 | 0.101995E+10 | 2104.17 | 11-OCT-14:39 | 1.33 | 0.89 |
November | 0.123286E+10 | 5506.00 | 21-NOV-13:30 | 0.00 | -0.5 | 0.742907E+09 | 1434.03 | 09-NOV-13:39 | 0.00 | -0.5 |
December | 0.811855E+09 | 4345.09 | 18-DEC-15:35 | 2.33 | -0.7 | 0.700227E+09 | 1267.67 | 02-DEC-15:09 | 2.33 | -0.7 |
Annual Sum or Average | 0.347102E+11 | 0.141278E+11 | ||||||||
Minimum of Months | 0.811855E+09 | 4251.40 | -2.2 | -4.2 | 0.645219E+09 | 1256.28 | -2.2 | -2.2 | ||
Maximum of Months | 0.767954E+10 | 41432.61 | 32.62 | 16.48 | 0.196557E+10 | 2246.92 | 32.62 | 16.66 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 | -1.8 | 0.865020E+09 | 1684.14 | 24-JAN-14:00 | 17.00 | 6.48 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -5.3 | -5.3 | 0.775878E+09 | 1806.76 | 18-FEB-14:39 | 19.33 | 7.91 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 | 0.118256E+10 | 2909.87 | 15-MAR-14:39 | 20.33 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.10 | 0.120796E+10 | 2508.24 | 21-APR-13:50 | 15.17 | 5.71 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 | 0.253574E+10 | 4453.69 | 31-MAY-14:00 | 28.00 | 14.63 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.26 | 0.515660E+10 | 9097.65 | 26-JUN-13:50 | 37.52 | 15.25 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.91 | 0.528480E+10 | 8826.36 | 17-JUL-13:09 | 35.83 | 14.79 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.43 | 0.554382E+10 | 8986.96 | 16-AUG-14:20 | 36.67 | 16.29 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.64 | 0.419013E+10 | 7318.82 | 09-SEP-13:09 | 32.43 | 12.96 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.03 | 0.191578E+10 | 4169.40 | 11-OCT-14:50 | 26.17 | 9.50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 | 0.948542E+09 | 2157.40 | 09-NOV-11:00 | 20.00 | 9.32 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 2.77 | -0.5 | 0.788272E+09 | 1731.53 | 04-DEC-14:30 | 19.50 | 6.42 |
Annual Sum or Average | 0.00 | 0.303951E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -5.7 | -5.7 | 0.775878E+09 | 1684.14 | 15.17 | 5.71 | ||
Maximum of Months | 0.00 | 0.00 | 22.27 | 15.43 | 0.554382E+10 | 9097.65 | 37.52 | 16.29 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.455131E+10 | 27619.55 | 05-JAN-06:12 | -17.0 |
February | 0.502081E+10 | 27664.77 | 07-FEB-06:12 | -6.7 |
March | 0.415042E+10 | 27576.14 | 29-MAR-05:12 | -7.3 |
April | 0.303736E+10 | 27693.99 | 17-APR-05:12 | -8.0 |
May | 0.730503E+09 | 27393.64 | 02-MAY-05:01 | 1.67 |
June | 13340432.74 | 761.37 | 23-JUN-06:10 | 14.08 |
July | 5381946.87 | 909.52 | 10-JUL-06:05 | 18.33 |
August | 12005490.39 | 991.75 | 22-AUG-06:05 | 14.17 |
September | 42613610.21 | 6534.11 | 22-SEP-06:05 | -1.4 |
October | 0.166220E+10 | 27399.00 | 30-OCT-05:01 | -10.0 |
November | 0.309338E+10 | 27634.82 | 30-NOV-06:12 | -12.0 |
December | 0.554940E+10 | 27811.43 | 20-DEC-06:31 | -19.0 |
Annual Sum or Average | 0.278687E+11 | |||
Minimum of Months | 5381946.87 | 761.37 | -19.0 | |
Maximum of Months | 0.554940E+10 | 27811.43 | 18.33 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155310E+11 | 78492.55 | 05-JAN-20:42 | -17.0 |
February | 0.177298E+11 | 79463.40 | 12-FEB-04:42 | -19.8 |
March | 0.119336E+11 | 79713.67 | 18-MAR-21:42 | -9.9 |
April | 0.835436E+10 | 78391.49 | 17-APR-04:22 | -8.0 |
May | 0.127092E+10 | 50164.40 | 04-MAY-05:07 | 8.17 |
June | 0.122754E+09 | 1467.00 | 01-JUN-16:20 | 27.00 |
July | 74281337.87 | 1061.91 | 20-JUL-06:50 | 14.17 |
August | 89612621.72 | 1124.03 | 24-AUG-07:00 | 15.00 |
September | 0.194155E+09 | 2023.69 | 26-SEP-12:00 | 28.30 |
October | 0.454676E+10 | 78293.68 | 31-OCT-23:42 | -5.9 |
November | 0.959138E+10 | 78518.08 | 01-NOV-03:02 | -3.5 |
December | 0.228653E+11 | 79595.52 | 19-DEC-19:22 | -18.2 |
Annual Sum or Average | 0.923040E+11 | |||
Minimum of Months | 74281337.87 | 1061.91 | -19.8 | |
Maximum of Months | 0.228653E+11 | 79713.67 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.425759E+11 | 81017.20 | 05-JAN-19:52 | -17.0 |
February | 0.567831E+11 | 108782.64 | 12-FEB-05:51 | -19.0 |
March | 0.265802E+11 | 119836.87 | 19-MAR-06:51 | -15.6 |
April | 0.131934E+11 | 56876.24 | 17-APR-04:52 | -8.0 |
May | 430174.56 | 482.27 | 03-MAY-03:53 | 2.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.897648E+10 | 65901.58 | 31-OCT-24:00 | -5.8 |
November | 0.242749E+11 | 101489.29 | 30-NOV-05:52 | -12.0 |
December | 0.877693E+11 | 132168.82 | 21-DEC-18:00 | -22.0 |
Annual Sum or Average | 0.260154E+12 | |||
Minimum of Months | 0.00 | 0.00 | -22.0 | |
Maximum of Months | 0.877693E+11 | 132168.82 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.119921E+10 | 1355.05 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.106838E+10 | 1355.05 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.120427E+10 | 1355.05 | 04-MAR-09:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.107544E+10 | 1355.05 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.104642E+10 | 1224.06 | 01-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.105109E+10 | 1224.06 | 05-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.101723E+10 | 1224.06 | 01-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.113960E+10 | 1355.05 | 28-AUG-15:00 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.107000E+10 | 1355.05 | 21-SEP-15:00 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.113546E+10 | 1355.05 | 02-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.114887E+10 | 1355.05 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.120724E+10 | 1355.05 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.133632E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.101723E+10 | 1224.06 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.120724E+10 | 1355.05 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.389596E+10 | 3848.58 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.350563E+10 | 3848.58 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.371484E+10 | 3848.58 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.322615E+10 | 3848.58 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.305285E+10 | 3848.58 | 09-MAY-08:09 | 0.00 | 0.00 |
June | 0.313920E+10 | 3527.86 | 05-JUN-08:09 | 0.00 | 0.00 |
July | 0.296364E+10 | 3848.58 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.348808E+10 | 3848.58 | 05-AUG-08:09 | 0.00 | 0.00 |
September | 0.335079E+10 | 3848.58 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.366363E+10 | 3848.58 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.373175E+10 | 3848.58 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.391520E+10 | 3848.58 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.416477E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.296364E+10 | 3527.86 | 0.00 | 0.00 | |
Maximum of Months | 0.391520E+10 | 3848.58 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.417619E+10 | 4490.00 | 02-JAN-15:50 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.361983E+10 | 4490.00 | 02-FEB-15:50 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.360233E+10 | 3961.65 | 02-MAR-16:49 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.309080E+10 | 3741.67 | 03-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.304600E+10 | 3301.38 | 16-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299385E+10 | 2993.34 | 23-JUN-08:30 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.296993E+10 | 3301.38 | 01-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.323786E+10 | 3301.38 | 28-AUG-15:00 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.320303E+10 | 3631.52 | 23-SEP-15:00 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.358341E+10 | 3961.65 | 12-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.387529E+10 | 4490.00 | 06-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.415879E+10 | 4490.00 | 01-DEC-14:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.415573E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.296993E+10 | 2993.34 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.417619E+10 | 4490.00 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.119921E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204559E+10 |
February | 0.127628E+10 | 0.106838E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9102.88 | 0.259639E+10 |
March | 0.149825E+10 | 0.120427E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2170.19 | 0.252155E+10 |
April | 0.138726E+10 | 0.107544E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222732E+10 |
May | 0.144276E+10 | 0.104642E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23587105.13 | 0.123448E+10 |
June | 0.144276E+10 | 0.105109E+10 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334793E+09 | 0.523987E+09 |
July | 0.138726E+10 | 0.101723E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289997E+09 | 0.525454E+09 |
August | 0.149825E+10 | 0.113960E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274928E+09 | 0.608609E+09 |
September | 0.138726E+10 | 0.107000E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119898E+09 | 0.895065E+09 |
October | 0.138726E+10 | 0.113546E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3111069.62 | 0.206477E+10 |
November | 0.133177E+10 | 0.114887E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 176047.61 | 0.212980E+10 |
December | 0.138726E+10 | 0.120724E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26280.80 | 0.338813E+10 |
Annual Sum or Average | 0.168137E+11 | 0.133632E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104653E+10 | 0.207611E+11 |
Minimum of Months | 0.127628E+10 | 0.101723E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523987E+09 |
Maximum of Months | 0.149825E+10 | 0.120724E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334793E+09 | 0.338813E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.389596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902709.59 | 0.491707E+10 |
February | 0.300332E+10 | 0.350563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242963.06 | 0.795758E+10 |
March | 0.352563E+10 | 0.371484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3386883.44 | 0.816168E+10 |
April | 0.326447E+10 | 0.322615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2694141.62 | 0.770843E+10 |
May | 0.339505E+10 | 0.305285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54642942.26 | 0.396598E+10 |
June | 0.339505E+10 | 0.313920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564071E+09 | 0.249048E+10 |
July | 0.326447E+10 | 0.296364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589456E+09 | 0.263541E+10 |
August | 0.352563E+10 | 0.348808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366588E+09 | 0.271532E+10 |
September | 0.326447E+10 | 0.335079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128504E+09 | 0.373997E+10 |
October | 0.326447E+10 | 0.366363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1585989.33 | 0.637682E+10 |
November | 0.313390E+10 | 0.373175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4602469.27 | 0.558388E+10 |
December | 0.326447E+10 | 0.391520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8571532.83 | 0.113944E+11 |
Annual Sum or Average | 0.395654E+11 | 0.416477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172525E+10 | 0.676470E+11 |
Minimum of Months | 0.300332E+10 | 0.296364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242963.06 | 0.249048E+10 |
Maximum of Months | 0.352563E+10 | 0.391520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589456E+09 | 0.113944E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.417619E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327635E+09 | 0.148856E+11 |
February | 0.690763E+10 | 0.361983E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211849E+09 | 0.253706E+11 |
March | 0.810895E+10 | 0.360233E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403504E+09 | 0.251333E+11 |
April | 0.750829E+10 | 0.309080E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109484E+10 | 0.227856E+11 |
May | 0.780862E+10 | 0.304600E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115177E+10 | 0.141860E+11 |
June | 0.780862E+10 | 0.299385E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674199E+09 | 0.130312E+11 |
July | 0.750829E+10 | 0.296993E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147389E+09 | 0.158296E+11 |
August | 0.810895E+10 | 0.323786E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90294656.31 | 0.153833E+11 |
September | 0.750829E+10 | 0.320303E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321829E+09 | 0.179634E+11 |
October | 0.750829E+10 | 0.358341E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101137E+09 | 0.233722E+11 |
November | 0.720796E+10 | 0.387529E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350560E+09 | 0.175983E+11 |
December | 0.750829E+10 | 0.415879E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787117E+09 | 0.370022E+11 |
Annual Sum or Average | 0.910005E+11 | 0.415573E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566212E+10 | 0.242541E+12 |
Minimum of Months | 0.690763E+10 | 0.296993E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90294656.31 | 0.130312E+11 |
Maximum of Months | 0.810895E+10 | 0.417619E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115177E+10 | 0.370022E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1355.05 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 8498.62 | 05-JAN-18:00 |
February | 1680.92 | 01-FEB-08:09 | 1355.05 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 26-FEB-13:00 | 7734.71 | 13-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1355.05 | 04-MAR-09:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 | 14-MAR-13:00 | 7745.29 | 27-MAR-16:10 |
April | 1680.92 | 01-APR-07:10 | 1355.05 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 7316.53 | 17-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1224.06 | 01-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 893.61 | 31-MAY-16:10 | 5790.73 | 02-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1224.06 | 05-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3015.49 | 26-JUN-17:00 | 3008.70 | 09-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1224.06 | 01-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.46 | 17-JUL-12:00 | 2992.73 | 03-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 1355.05 | 28-AUG-15:00 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2517.93 | 16-AUG-17:00 | 2571.05 | 23-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 1355.05 | 21-SEP-15:00 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1577.71 | 12-SEP-16:10 | 5639.73 | 21-SEP-16:03 |
October | 1680.92 | 02-OCT-07:10 | 1355.05 | 02-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.21 | 10-OCT-17:00 | 7481.10 | 30-OCT-16:10 |
November | 1680.92 | 01-NOV-07:10 | 1355.05 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.88 | 05-NOV-15:00 | 7837.12 | 29-NOV-18:00 |
December | 1680.92 | 01-DEC-08:09 | 1355.05 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.44 | 17-DEC-13:00 | 12794.62 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1224.06 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2571.05 | |||||
Maximum of Months | 1680.92 | 1355.05 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 3015.49 | 12794.62 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3848.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.25 | 23-JAN-13:00 | 7912.74 | 07-JAN-08:00 |
February | 3955.50 | 01-FEB-08:09 | 3848.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.44 | 26-FEB-16:00 | 11585.03 | 11-FEB-16:10 |
March | 3955.50 | 01-MAR-08:09 | 3848.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.68 | 13-MAR-16:00 | 21630.61 | 19-MAR-06:51 |
April | 3955.50 | 01-APR-07:10 | 3848.58 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.67 | 19-APR-13:00 | 15527.39 | 14-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 3848.58 | 09-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 928.71 | 04-MAY-15:10 | 8470.85 | 02-MAY-06:02 |
June | 3955.50 | 01-JUN-07:10 | 3527.86 | 05-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3882.11 | 06-JUN-16:40 | 6071.26 | 20-JUN-16:55 |
July | 3955.50 | 01-JUL-07:10 | 3848.58 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3797.38 | 15-JUL-15:10 | 4941.65 | 03-JUL-03:00 |
August | 3955.50 | 01-AUG-07:10 | 3848.58 | 05-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4031.59 | 02-AUG-16:00 | 5815.79 | 27-AUG-18:00 |
September | 3955.50 | 01-SEP-07:10 | 3848.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2015.20 | 09-SEP-15:10 | 11408.82 | 21-SEP-15:05 |
October | 3955.50 | 02-OCT-07:10 | 3848.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.63 | 10-OCT-17:00 | 11183.03 | 29-OCT-19:00 |
November | 3955.50 | 01-NOV-07:10 | 3848.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.52 | 05-NOV-15:00 | 13380.04 | 01-NOV-07:00 |
December | 3955.50 | 01-DEC-08:09 | 3848.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.99 | 17-DEC-13:00 | 21146.19 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3527.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.44 | 4941.65 | ||||
Maximum of Months | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4031.59 | 21630.61 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 4490.00 | 02-JAN-15:50 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5871.28 | 19-JAN-14:00 | 28674.34 | 07-JAN-12:00 |
February | 9097.65 | 01-FEB-08:09 | 4490.00 | 02-FEB-15:50 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6388.79 | 18-FEB-14:00 | 50040.41 | 11-FEB-15:00 |
March | 9097.65 | 01-MAR-08:09 | 3961.65 | 02-MAR-16:49 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6163.64 | 31-MAR-14:00 | 73333.95 | 19-MAR-06:51 |
April | 9097.65 | 01-APR-07:10 | 3741.67 | 03-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12787.03 | 07-APR-16:00 | 44251.03 | 14-APR-07:10 |
May | 9097.65 | 01-MAY-07:10 | 3301.38 | 16-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8912.23 | 04-MAY-15:00 | 40620.73 | 26-MAY-11:00 |
June | 9097.65 | 01-JUN-07:10 | 2993.34 | 23-JUN-08:30 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9891.51 | 06-JUN-14:00 | 25142.95 | 20-JUN-16:55 |
July | 9097.65 | 01-JUL-07:10 | 3301.38 | 01-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2227.18 | 16-JUL-11:53 | 22891.03 | 03-JUL-03:00 |
August | 9097.65 | 01-AUG-07:10 | 3301.38 | 28-AUG-15:00 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2334.42 | 02-AUG-12:55 | 27382.58 | 27-AUG-18:00 |
September | 9097.65 | 01-SEP-07:10 | 3631.52 | 23-SEP-15:00 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7916.82 | 26-SEP-12:10 | 49135.72 | 21-SEP-14:50 |
October | 9097.65 | 02-OCT-07:10 | 3961.65 | 12-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4305.89 | 11-OCT-14:00 | 40276.61 | 03-OCT-15:00 |
November | 9097.65 | 01-NOV-07:10 | 4490.00 | 06-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7114.56 | 07-NOV-14:00 | 41094.38 | 01-NOV-10:00 |
December | 9097.65 | 01-DEC-08:09 | 4490.00 | 01-DEC-14:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17947.46 | 02-DEC-12:00 | 64614.78 | 21-DEC-19:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2993.34 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 2227.18 | 22891.03 | |||||
Maximum of Months | 9097.65 | 4490.00 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 17947.46 | 73333.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 834.76 | 21-JAN-17:00 | 1680.92 | 1355.05 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.69 |
February | 457.88 | 25-FEB-15:00 | 1680.92 | 1002.74 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.81 |
March | 1366.67 | 15-MAR-16:00 | 1680.92 | 826.58 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.88 |
April | 577.32 | 10-APR-15:00 | 1680.92 | 826.58 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 713.32 |
May | 3677.93 | 31-MAY-16:00 | 1680.92 | 826.58 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 315.46 | 0.00 |
June | 24955.95 | 28-JUN-05:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.67 |
July | 23037.66 | 01-JUL-05:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.59 |
August | 27647.43 | 17-AUG-05:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.56 |
September | 23425.06 | 11-SEP-05:01 | 1294.31 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.73 |
October | 4026.98 | 11-OCT-15:10 | 1680.92 | 826.58 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 156.17 | 0.00 |
November | 981.50 | 18-NOV-17:00 | 1680.92 | 1355.05 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 636.08 |
December | 652.09 | 16-DEC-13:30 | 1680.92 | 1178.89 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 457.88 | 1109.41 | 305.97 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27647.43 | 1680.92 | 1355.05 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 315.46 | 713.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5590.58 | 11-JAN-11:10 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.46 |
February | 4886.22 | 09-FEB-14:00 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 948.16 |
March | 5883.83 | 27-MAR-12:05 | 7911.00 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7590.26 |
April | 5461.98 | 22-APR-08:70 | 3955.50 | 3527.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2477.61 |
May | 4251.40 | 19-MAY-07:10 | 3955.50 | 3112.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3794.39 |
June | 39603.54 | 27-JUN-17:06 | 0.00 | 2263.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1221.50 | 0.00 |
July | 41432.61 | 24-JUL-17:08 | 0.00 | 2263.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.68 | 0.00 |
August | 41309.83 | 20-AUG-15:03 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.54 | 0.00 |
September | 39424.03 | 10-SEP-14:43 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.25 | 0.00 |
October | 6608.54 | 12-OCT-08:20 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2245.43 |
November | 5506.00 | 21-NOV-13:30 | 3955.50 | 3207.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 723.97 |
December | 4345.09 | 18-DEC-15:35 | 7911.00 | 7697.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3732.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4251.40 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41432.61 | 7911.00 | 7697.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.68 | 7590.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 1056.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2407.76 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 1584.69 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8116.44 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7177.65 |
April | 0.00 | 01-APR-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3377.71 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4946.12 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3541.61 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8337.12 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10005.25 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5434.82 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 528.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8612.06 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24802.69 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1584.69 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8241.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 528.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2407.76 | |
Maximum of Months | 0.00 | 0.00 | 1584.69 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24802.69 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.325628E+11 | 28620.83 | 05-JAN-16:49 | 0.856227E+11 | 147816.90 | 05-JAN-17:00 |
February | 0.291157E+11 | 24130.00 | 06-FEB-15:00 | 0.107069E+12 | 182263.87 | 12-FEB-06:30 |
March | 0.311356E+11 | 22978.03 | 20-MAR-07:10 | 0.588811E+11 | 213861.43 | 19-MAR-07:10 |
April | 0.275425E+11 | 23283.41 | 03-APR-08:09 | 0.340808E+11 | 124997.45 | 17-APR-05:19 |
May | 0.269640E+11 | 21448.39 | 09-MAY-08:09 | 0.213485E+10 | 36588.33 | 02-MAY-05:10 |
June | 0.308707E+11 | 33897.57 | 26-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.311351E+11 | 30130.67 | 15-JUL-14:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.329698E+11 | 32195.27 | 16-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.293962E+11 | 29118.39 | 12-SEP-15:00 | 31458432.37 | 6000.99 | 22-SEP-06:10 |
October | 0.297140E+11 | 23254.43 | 30-OCT-08:20 | 0.216569E+11 | 120566.34 | 31-OCT-23:49 |
November | 0.304662E+11 | 28544.98 | 28-NOV-16:49 | 0.513643E+11 | 183848.34 | 30-NOV-06:10 |
December | 0.331741E+11 | 29034.40 | 21-DEC-16:00 | 0.155008E+12 | 259838.89 | 21-DEC-17:00 |
Annual Sum or Average | 0.365047E+12 | 0.515849E+12 | ||||
Minimum of Months | 0.269640E+11 | 21448.39 | 0.00 | 0.00 | ||
Maximum of Months | 0.331741E+11 | 33897.57 | 0.155008E+12 | 259838.89 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.927135E+10 | 0.677387E+10 | 0.112984E+11 | 0.00 | 0.294223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227701E+10 | 0.00 |
February | 0.819384E+10 | 0.557252E+10 | 0.103734E+11 | 0.00 | 0.289486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208111E+10 | 0.00 |
March | 0.852144E+10 | 0.539918E+10 | 0.121089E+11 | 0.00 | 0.276441E+10 | 0.00 | 0.00 | 1837439.19 | 0.00 | 0.00 | 0.00 | 0.233981E+10 | 0.00 |
April | 0.739238E+10 | 0.444444E+10 | 0.112578E+11 | 0.00 | 0.225649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219140E+10 | 0.00 |
May | 0.714527E+10 | 0.399505E+10 | 0.117000E+11 | 0.00 | 0.177099E+10 | 0.00 | 0.00 | 0.137012E+09 | 0.00 | 0.00 | 0.00 | 0.221575E+10 | 0.00 |
June | 0.718415E+10 | 0.359992E+10 | 0.116594E+11 | 0.00 | 0.274001E+10 | 0.00 | 0.00 | 0.357658E+10 | 0.00 | 0.00 | 0.00 | 0.211067E+10 | 0.00 |
July | 0.695080E+10 | 0.380519E+10 | 0.112984E+11 | 0.00 | 0.313612E+10 | 0.00 | 0.00 | 0.385170E+10 | 0.00 | 0.00 | 0.00 | 0.209295E+10 | 0.00 |
August | 0.786553E+10 | 0.429281E+10 | 0.121016E+11 | 0.00 | 0.289578E+10 | 0.00 | 0.00 | 0.367962E+10 | 0.00 | 0.00 | 0.00 | 0.213447E+10 | 0.00 |
September | 0.762382E+10 | 0.488500E+10 | 0.112504E+11 | 0.00 | 0.190096E+10 | 0.00 | 0.00 | 0.168455E+10 | 0.00 | 0.00 | 0.00 | 0.205146E+10 | 0.00 |
October | 0.838249E+10 | 0.585299E+10 | 0.113057E+11 | 0.00 | 0.197823E+10 | 0.00 | 0.00 | 53452166.91 | 0.00 | 0.00 | 0.00 | 0.214107E+10 | 0.00 |
November | 0.875590E+10 | 0.635244E+10 | 0.108562E+11 | 0.00 | 0.238515E+10 | 0.00 | 0.00 | 50.55 | 0.00 | 0.00 | 0.00 | 0.211659E+10 | 0.00 |
December | 0.928123E+10 | 0.696599E+10 | 0.112984E+11 | 0.00 | 0.338663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224193E+10 | 0.00 |
Annual Sum or Average | 0.965682E+11 | 0.619394E+11 | 0.136508E+12 | 0.00 | 0.310519E+11 | 0.00 | 0.00 | 0.129847E+11 | 0.00 | 0.00 | 0.00 | 0.259942E+11 | 0.00 |
Minimum of Months | 0.695080E+10 | 0.359992E+10 | 0.103734E+11 | 0.00 | 0.177099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205146E+10 | 0.00 |
Maximum of Months | 0.928123E+10 | 0.696599E+10 | 0.121089E+11 | 0.00 | 0.338663E+10 | 0.00 | 0.00 | 0.385170E+10 | 0.00 | 0.00 | 0.00 | 0.233981E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.856227E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.107069E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.588811E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.340808E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.213485E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 31458432.37 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.216569E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.513643E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.155008E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.515849E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.155008E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 9693.63 | 04-JAN-15:09 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 3194.24 | 05-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 9693.63 | 06-FEB-15:50 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 3068.18 | 06-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8945.30 | 18-MAR-08:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2866.94 | 27-MAR-16:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 8945.30 | 03-APR-08:09 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2985.59 | 17-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 8065.97 | 09-MAY-08:09 | 5520.82 | 01-MAY-18:49 | 10035.17 | 01-MAY-07:10 | 0.00 | 2250.15 | 02-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7745.26 | 23-JUN-08:30 | 4975.14 | 01-JUN-19:19 | 10035.17 | 01-JUN-07:10 | 0.00 | 4675.45 | 26-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 8065.97 | 01-JUL-08:09 | 4975.14 | 01-JUL-19:30 | 10035.17 | 01-JUL-07:10 | 0.00 | 4139.89 | 15-JUL-15:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 8065.97 | 05-AUG-08:09 | 5520.82 | 09-AUG-18:00 | 10035.17 | 01-AUG-07:10 | 0.00 | 4211.72 | 16-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 8440.14 | 16-SEP-08:09 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 3977.67 | 12-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 8945.30 | 12-OCT-08:09 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 2961.82 | 30-OCT-16:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 9693.63 | 09-NOV-15:30 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 3028.16 | 29-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 9693.63 | 06-DEC-15:00 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 3792.58 | 21-DEC-17:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 7745.26 | 4975.14 | 10035.17 | 0.00 | 2250.15 | 0.00 | 0.00 | |||||
Maximum of Months | 9693.63 | 5520.82 | 10035.17 | 0.00 | 4675.45 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2590.98 | 31-JAN-12:20 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2602.69 | 10-FEB-12:20 | 0.00 |
March | 185.84 | 13-MAR-15:00 | 0.00 | 0.00 | 0.00 | 2586.77 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 2468.04 | 01-APR-11:09 | 0.00 |
May | 1242.75 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2258.18 | 01-MAY-11:50 | 0.00 |
June | 11617.39 | 26-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1971.45 | 01-JUN-11:00 | 0.00 |
July | 8957.11 | 15-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1797.85 | 01-JUL-11:30 | 0.00 |
August | 9499.41 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1787.14 | 30-AUG-11:09 | 0.00 |
September | 6312.22 | 12-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1798.61 | 29-SEP-11:09 | 0.00 |
October | 1161.01 | 11-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1967.05 | 27-OCT-11:00 | 0.00 |
November | 0.07 | 07-NOV-14:20 | 0.00 | 0.00 | 0.00 | 2222.29 | 24-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2467.08 | 28-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1787.14 | 0.00 | ||
Maximum of Months | 11617.39 | 0.00 | 0.00 | 0.00 | 2602.69 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 28620.83 | 05-JAN-16:49 | 8712.41 | 10035.17 | 5520.82 | 0.00 | 2733.98 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24130.00 | 06-FEB-15:00 | 9693.63 | 10035.17 | 0.00 | 0.00 | 2572.81 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22978.03 | 20-MAR-07:10 | 8712.41 | 10035.17 | 0.00 | 0.00 | 2575.52 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23283.41 | 03-APR-08:09 | 8945.30 | 10035.17 | 0.00 | 0.00 | 2612.89 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21448.39 | 09-MAY-08:09 | 8065.97 | 10035.17 | 0.00 | 0.00 | 1668.98 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33897.57 | 26-JUN-15:09 | 5967.30 | 10035.17 | 0.00 | 0.00 | 4675.45 | 0.00 | 0.00 | 11617.39 | 0.00 |
July | 30130.67 | 15-JUL-14:50 | 5958.01 | 10035.17 | 0.00 | 0.00 | 4014.35 | 0.00 | 0.00 | 8368.28 | 0.00 |
August | 32195.27 | 16-AUG-14:09 | 6829.05 | 10035.17 | 0.00 | 0.00 | 4189.78 | 0.00 | 0.00 | 9391.44 | 0.00 |
September | 29118.39 | 12-SEP-15:00 | 7193.53 | 10035.17 | 0.00 | 0.00 | 3977.67 | 0.00 | 0.00 | 6312.22 | 0.00 |
October | 23254.43 | 30-OCT-08:20 | 8945.30 | 10035.17 | 0.00 | 0.00 | 2602.89 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28544.98 | 28-NOV-16:49 | 8712.41 | 10035.17 | 5520.82 | 0.00 | 2664.35 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29034.40 | 21-DEC-16:00 | 8712.41 | 10035.17 | 5520.82 | 0.00 | 3149.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 21448.39 | 5958.01 | 10035.17 | 0.00 | 0.00 | 1668.98 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33897.57 | 9693.63 | 10035.17 | 5520.82 | 0.00 | 4675.45 | 0.00 | 0.00 | 11617.39 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 147816.90 | 05-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 182263.87 | 12-FEB-06:30 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 213861.43 | 19-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 124997.45 | 17-APR-05:19 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 36588.33 | 02-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 6000.99 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 120566.34 | 31-OCT-23:49 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 183848.34 | 30-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 259838.89 | 21-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 259838.89 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.50 | 18.77 | 8.67 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
February | 18.50 | 16.95 | 8.33 | 17.72 | 0.00 | 17.72 | 0.00 | 17.72 |
March | 13.67 | 17.89 | 8.83 | 18.54 | 0.00 | 18.54 | 0.00 | 18.54 |
April | 9.00 | 18.98 | 7.67 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
May | 3.00 | 19.82 | 2.83 | 19.96 | 0.00 | 19.96 | 0.00 | 19.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.54 | 0.67 | 24.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.53 | 1.33 | 24.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.57 | 0.67 | 24.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.51 | 0.83 | 24.51 |
October | 4.00 | 19.90 | 4.00 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
November | 7.67 | 19.35 | 7.00 | 19.55 | 0.00 | 19.55 | 0.00 | 19.55 |
December | 23.67 | 16.61 | 8.83 | 17.39 | 0.00 | 17.39 | 0.00 | 17.39 |
Annual Sum or Average | 90.00 | 17.85 | 56.17 | 18.53 | 3.50 | 18.67 | 3.50 | 18.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.39 | 0.00 | 17.39 |
Maximum of Months | 23.67 | 19.90 | 8.83 | 19.96 | 1.33 | 24.57 | 1.33 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.17 | 14.60 | 4.17 | 14.60 | 0.00 | 14.60 | 0.00 | 14.60 |
February | 76.33 | 14.45 | 4.17 | 14.45 | 0.00 | 14.45 | 0.00 | 14.45 |
March | 59.33 | 14.59 | 4.00 | 14.59 | 0.00 | 14.59 | 0.00 | 14.59 |
April | 42.83 | 14.65 | 2.83 | 14.65 | 0.00 | 14.65 | 0.00 | 14.65 |
May | 5.17 | 14.89 | 0.67 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.41 | 0.00 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.40 | 0.00 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.34 | 0.00 | 27.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.33 | 0.00 | 27.33 |
October | 20.00 | 14.63 | 1.50 | 14.63 | 0.00 | 14.63 | 0.00 | 14.63 |
November | 43.00 | 14.65 | 2.83 | 14.65 | 0.00 | 14.65 | 0.00 | 14.65 |
December | 86.17 | 14.36 | 4.33 | 14.36 | 0.00 | 14.36 | 0.00 | 14.36 |
Annual Sum or Average | 405.00 | 14.54 | 24.50 | 14.54 | 16.83 | 15.02 | 0.00 | 15.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 | 0.00 | 14.36 |
Maximum of Months | 86.17 | 14.89 | 4.33 | 14.89 | 6.67 | 27.41 | 0.00 | 27.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.50 | 9.15 | 0.00 | 9.15 | 0.00 | 9.15 | 0.00 | 9.15 |
Annual Sum or Average | 3.50 | 9.15 | 0.00 | 9.15 | 0.00 | 9.15 | 0.00 | 9.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 9.15 | 0.00 | 9.15 | 0.00 | 9.15 | 0.00 | 9.15 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.13 | 292.33 | 21.11 | 292.33 | 21.11 |
February | 276.00 | 21.08 | 272.17 | 21.07 | 272.17 | 21.07 |
March | 324.00 | 21.37 | 278.33 | 21.25 | 278.33 | 21.20 |
April | 300.00 | 21.39 | 244.83 | 21.27 | 244.83 | 21.22 |
May | 312.00 | 22.77 | 70.83 | 22.46 | 70.83 | 22.25 |
June | 52.00 | 23.63 | 148.50 | 23.83 | 3.50 | 23.83 |
July | 33.33 | 23.78 | 215.17 | 23.88 | 25.50 | 23.88 |
August | 15.83 | 23.65 | 221.33 | 23.89 | 5.00 | 23.89 |
September | 111.83 | 23.48 | 79.17 | 23.62 | 2.17 | 23.59 |
October | 300.00 | 22.22 | 133.50 | 21.88 | 133.50 | 21.70 |
November | 288.00 | 21.36 | 245.33 | 21.24 | 245.33 | 21.20 |
December | 300.00 | 21.13 | 291.50 | 21.10 | 291.50 | 21.10 |
Annual Sum or Average | 2613.00 | 21.73 | 2493.00 | 21.78 | 1865.00 | 21.61 |
Minimum of Months | 15.83 | 21.08 | 70.83 | 21.07 | 2.17 | 21.07 |
Maximum of Months | 324.00 | 23.78 | 292.33 | 23.89 | 292.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 16.20 | 300.00 | 16.20 | 300.00 | 16.20 |
February | 276.00 | 16.06 | 276.00 | 16.06 | 276.00 | 16.06 |
March | 324.00 | 16.99 | 311.67 | 16.89 | 311.67 | 16.85 |
April | 300.00 | 17.23 | 296.00 | 17.20 | 296.00 | 17.19 |
May | 294.33 | 20.77 | 126.50 | 20.20 | 120.33 | 19.82 |
June | 106.67 | 25.93 | 278.83 | 26.26 | 87.50 | 26.32 |
July | 126.50 | 26.49 | 291.00 | 26.45 | 125.67 | 26.47 |
August | 112.33 | 26.51 | 308.67 | 26.41 | 109.17 | 26.45 |
September | 88.50 | 23.10 | 206.17 | 25.11 | 25.00 | 24.95 |
October | 296.00 | 19.13 | 196.67 | 18.52 | 196.67 | 18.26 |
November | 288.00 | 16.77 | 285.83 | 16.75 | 285.83 | 16.74 |
December | 300.00 | 16.04 | 300.00 | 16.04 | 300.00 | 16.04 |
Annual Sum or Average | 2812.33 | 18.68 | 3177.33 | 19.39 | 2433.83 | 19.01 |
Minimum of Months | 88.50 | 16.04 | 126.50 | 16.04 | 25.00 | 16.04 |
Maximum of Months | 324.00 | 26.51 | 311.67 | 26.45 | 311.67 | 26.47 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 11.39 | 300.00 | 11.39 | 300.00 | 11.39 |
February | 276.00 | 11.26 | 276.00 | 11.26 | 276.00 | 11.26 |
March | 324.00 | 12.72 | 324.00 | 12.72 | 324.00 | 12.72 |
April | 300.00 | 13.46 | 300.00 | 13.46 | 300.00 | 13.46 |
May | 309.17 | 19.42 | 181.83 | 18.71 | 181.83 | 18.38 |
June | 238.67 | 29.16 | 276.17 | 29.10 | 215.17 | 29.33 |
July | 279.33 | 29.68 | 300.00 | 29.56 | 279.33 | 29.60 |
August | 267.00 | 29.58 | 324.00 | 29.26 | 267.00 | 29.36 |
September | 197.33 | 26.16 | 200.00 | 26.66 | 128.33 | 26.93 |
October | 300.00 | 16.98 | 250.50 | 16.53 | 250.50 | 16.36 |
November | 288.00 | 12.14 | 288.00 | 12.14 | 288.00 | 12.14 |
December | 300.00 | 10.91 | 300.00 | 10.91 | 300.00 | 10.91 |
Annual Sum or Average | 3379.50 | 18.01 | 3320.50 | 18.09 | 3110.17 | 17.94 |
Minimum of Months | 197.33 | 10.91 | 181.83 | 10.91 | 128.33 | 10.91 |
Maximum of Months | 324.00 | 29.68 | 324.00 | 29.56 | 324.00 | 29.60 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 7220035.95 | 1837439.19 | 5.00 | 7220035.95 | -0.0 | 0.00 | 0.09 | 13-MAR-16:00 | 0.00 | 01-MAR-00:10 | 733.24 | 13-MAR-16:00 | 733.24 | 13-MAR-16:00 | 0.00 | 14-MAR-12:50 | 185.84 | 13-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.540879E+09 | 0.137012E+09 | 78.58 | 0.537206E+09 | 3672917.89 | 0.00 | 0.55 | 31-MAY-16:00 | 0.00 | 01-MAY-00:10 | 4860.34 | 31-MAY-16:00 | 4643.13 | 31-MAY-16:00 | 217.21 | 31-MAY-16:00 | 1242.75 | 31-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.560240E+10 | 0.142049E+10 | 264.77 | 0.529919E+10 | 0.303213E+09 | 0.00 | 1.00 | 06-JUN-05:55 | 0.00 | 01-JUN-00:10 | 19985.88 | 22-JUN-05:03 | 18894.07 | 14-JUN-05:21 | 7944.72 | 17-JUN-05:02 | 4362.73 | 22-JUN-05:03 | 0.00 | 01-JUN-00:10 |
July | 0.600892E+10 | 0.149800E+10 | 267.02 | 0.552781E+10 | 0.481107E+09 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 21336.04 | 28-JUL-05:03 | 18894.07 | 01-JUL-05:02 | 10186.60 | 28-JUL-05:55 | 4632.51 | 28-JUL-05:03 | 0.00 | 01-JUL-00:10 |
August | 0.593938E+10 | 0.148323E+10 | 276.10 | 0.559717E+10 | 0.342205E+09 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 21526.64 | 04-AUG-05:02 | 18894.07 | 17-AUG-05:02 | 10826.16 | 04-AUG-05:45 | 4668.13 | 04-AUG-05:02 | 0.00 | 01-AUG-00:10 |
September | 0.370156E+10 | 0.908724E+09 | 217.12 | 0.364531E+10 | 56253594.10 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 18986.09 | 13-SEP-05:01 | 18894.07 | 11-SEP-05:01 | 5973.84 | 01-SEP-05:03 | 4142.10 | 13-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.216956E+09 | 53452166.91 | 27.50 | 0.216956E+09 | -0.0 | 0.00 | 0.56 | 11-OCT-15:10 | 0.00 | 01-OCT-00:10 | 4753.21 | 11-OCT-15:10 | 4753.21 | 11-OCT-15:10 | 0.00 | 11-OCT-14:40 | 1161.01 | 11-OCT-15:10 | 0.00 | 01-OCT-00:10 |
November | 196.74 | 50.55 | 0.33 | 196.74 | 0.00 | 0.00 | 0.00 | 07-NOV-14:20 | 0.00 | 01-NOV-00:10 | 0.26 | 07-NOV-14:20 | 0.26 | 07-NOV-14:20 | 0.00 | 01-NOV-00:10 | 0.07 | 07-NOV-14:20 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.220173E+11 | 0.550275E+10 | 1136.43 | 0.208309E+11 | 0.118645E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.600892E+10 | 0.149800E+10 | 276.10 | 0.559717E+10 | 0.481107E+09 | 0.00 | 1.00 | 0.00 | 21526.64 | 18894.07 | 10826.16 | 4668.13 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.785492E+10 | 0.215609E+10 | 210.08 | 0.770408E+10 | 0.150839E+09 | 0.00 | 1.00 | 07-JUN-17:12 | 0.00 | 01-JUN-00:10 | 53284.58 | 18-JUN-09:55 | 47542.71 | 15-JUN-19:15 | 15907.73 | 18-JUN-09:55 | 12529.74 | 26-JUN-17:43 | 0.00 | 01-JUN-00:10 |
July | 0.868071E+10 | 0.235370E+10 | 238.49 | 0.849625E+10 | 0.184464E+09 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:10 | 55012.36 | 30-JUL-11:25 | 47432.67 | 26-JUL-17:30 | 20288.16 | 30-JUL-11:25 | 12343.67 | 23-JUL-13:33 | 0.00 | 01-JUL-00:10 |
August | 0.816800E+10 | 0.219638E+10 | 218.36 | 0.804539E+10 | 0.122604E+09 | 0.00 | 1.00 | 02-AUG-17:10 | 0.00 | 01-AUG-00:10 | 49085.00 | 27-AUG-11:55 | 47765.93 | 27-AUG-13:32 | 4890.80 | 27-AUG-11:55 | 12277.18 | 16-AUG-17:06 | 0.00 | 01-AUG-00:10 |
September | 0.289217E+10 | 0.775824E+09 | 114.72 | 0.288801E+10 | 4156579.46 | 0.00 | 1.00 | 02-SEP-17:12 | 0.00 | 01-SEP-00:10 | 47485.17 | 03-SEP-16:45 | 47485.17 | 03-SEP-16:45 | 563.04 | 01-SEP-12:10 | 11571.17 | 10-SEP-14:43 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.275958E+11 | 0.748200E+10 | 781.65 | 0.271337E+11 | 0.462063E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.868071E+10 | 0.235370E+10 | 238.49 | 0.849625E+10 | 0.184464E+09 | 0.00 | 1.00 | 0.00 | 55012.36 | 47765.93 | 20288.16 | 12529.74 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.09 | 69.73 | 40.36 | 115.32 | 127.88 | 0.00 | 0.00 | 0.00 |
February | 133.67 | 83.07 | 50.60 | 138.13 | 130.30 | 0.00 | 0.00 | 0.00 |
March | 155.81 | 86.03 | 69.78 | 171.05 | 94.79 | 0.00 | 0.00 | 0.00 |
April | 146.04 | 61.60 | 84.44 | 155.75 | 80.27 | 0.00 | 0.00 | 0.00 |
May | 179.03 | 63.09 | 115.95 | 219.56 | 51.28 | 0.00 | 0.00 | 0.00 |
June | 219.24 | 105.59 | 113.65 | 301.15 | 40.21 | 0.00 | 0.00 | 0.00 |
July | 178.32 | 65.22 | 113.10 | 244.33 | 38.49 | 0.00 | 0.00 | 0.00 |
August | 186.62 | 92.33 | 94.29 | 251.35 | 44.37 | 0.00 | 0.00 | 0.00 |
September | 165.69 | 79.63 | 86.05 | 214.67 | 62.96 | 0.00 | 0.00 | 0.00 |
October | 138.54 | 79.04 | 59.50 | 157.65 | 106.64 | 0.00 | 0.00 | 0.00 |
November | 113.86 | 69.06 | 44.79 | 121.82 | 117.59 | 0.00 | 0.00 | 0.00 |
December | 92.06 | 54.37 | 37.69 | 87.88 | 149.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.62 | 75.63 | 75.99 | 181.73 | 86.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 92.06 | 54.37 | 37.69 | 87.88 | 38.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.24 | 105.59 | 115.95 | 301.15 | 149.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.09 | 69.73 | 40.36 | 115.32 | 127.88 | 0.00 | 0.00 | 0.00 |
February | 133.67 | 83.07 | 50.60 | 138.13 | 130.30 | 0.00 | 0.00 | 0.00 |
March | 155.81 | 86.03 | 69.78 | 171.05 | 94.79 | 0.00 | 0.00 | 0.00 |
April | 146.04 | 61.60 | 84.44 | 155.75 | 80.27 | 0.00 | 0.00 | 0.00 |
May | 179.03 | 63.09 | 115.95 | 219.56 | 51.28 | 0.00 | 0.00 | 0.00 |
June | 219.24 | 105.59 | 113.65 | 301.15 | 40.21 | 0.00 | 0.00 | 0.00 |
July | 178.32 | 65.22 | 113.10 | 244.33 | 38.49 | 0.00 | 0.00 | 0.00 |
August | 186.62 | 92.33 | 94.29 | 251.35 | 44.37 | 0.00 | 0.00 | 0.00 |
September | 165.69 | 79.63 | 86.05 | 214.67 | 62.96 | 0.00 | 0.00 | 0.00 |
October | 138.54 | 79.04 | 59.50 | 157.65 | 106.64 | 0.00 | 0.00 | 0.00 |
November | 113.86 | 69.06 | 44.79 | 121.82 | 117.59 | 0.00 | 0.00 | 0.00 |
December | 92.06 | 54.37 | 37.69 | 87.88 | 149.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.62 | 75.63 | 75.99 | 181.73 | 86.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 92.06 | 54.37 | 37.69 | 87.88 | 38.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.24 | 105.59 | 115.95 | 301.15 | 149.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.30 | 0.00 | 19.30 | 6.01 | 78.93 | 0.00 | 0.00 | 0.00 |
February | 24.26 | 0.00 | 24.26 | 7.56 | 79.99 | 0.00 | 0.00 | 0.00 |
March | 33.02 | 0.00 | 33.02 | 20.22 | 57.57 | 0.00 | 0.00 | 0.00 |
April | 41.47 | 0.26 | 41.22 | 29.58 | 47.19 | 0.00 | 0.00 | 0.00 |
May | 56.69 | 1.90 | 54.78 | 59.53 | 28.38 | 0.00 | 0.00 | 0.00 |
June | 62.01 | 6.79 | 55.21 | 82.34 | 21.57 | 0.00 | 0.00 | 0.00 |
July | 58.85 | 3.90 | 54.95 | 78.43 | 21.16 | 0.00 | 0.00 | 0.00 |
August | 46.94 | 1.28 | 45.66 | 58.83 | 25.31 | 0.00 | 0.00 | 0.00 |
September | 39.30 | 0.03 | 39.27 | 43.74 | 36.88 | 0.00 | 0.00 | 0.00 |
October | 28.12 | 0.00 | 28.12 | 17.66 | 63.79 | 0.00 | 0.00 | 0.00 |
November | 21.35 | 0.00 | 21.35 | 8.86 | 71.52 | 0.00 | 0.00 | 0.00 |
December | 18.06 | 0.00 | 18.06 | 4.79 | 92.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.52 | 1.18 | 36.33 | 34.95 | 51.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.06 | 0.00 | 18.06 | 4.79 | 21.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.01 | 6.79 | 55.21 | 82.34 | 92.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.30 | 0.00 | 19.30 | 6.01 | 78.93 | 0.00 | 0.00 | 0.00 |
February | 24.26 | 0.00 | 24.26 | 7.55 | 79.99 | 0.00 | 0.00 | 0.00 |
March | 33.02 | 0.00 | 33.02 | 20.22 | 57.57 | 0.00 | 0.00 | 0.00 |
April | 41.47 | 0.26 | 41.22 | 29.58 | 47.19 | 0.00 | 0.00 | 0.00 |
May | 56.69 | 1.90 | 54.78 | 59.53 | 28.38 | 0.00 | 0.00 | 0.00 |
June | 62.01 | 6.79 | 55.21 | 82.34 | 21.57 | 0.00 | 0.00 | 0.00 |
July | 58.85 | 3.90 | 54.94 | 78.43 | 21.16 | 0.00 | 0.00 | 0.00 |
August | 46.94 | 1.28 | 45.66 | 58.83 | 25.31 | 0.00 | 0.00 | 0.00 |
September | 39.30 | 0.03 | 39.27 | 43.74 | 36.88 | 0.00 | 0.00 | 0.00 |
October | 28.12 | 0.00 | 28.12 | 17.66 | 63.79 | 0.00 | 0.00 | 0.00 |
November | 21.35 | 0.00 | 21.35 | 8.86 | 71.52 | 0.00 | 0.00 | 0.00 |
December | 18.06 | 0.00 | 18.06 | 4.79 | 92.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.52 | 1.18 | 36.33 | 34.95 | 51.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.06 | 0.00 | 18.06 | 4.79 | 21.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.01 | 6.79 | 55.21 | 82.34 | 92.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.38 | 23.80 | 10.58 | 35.20 | 48.39 | 0.00 | 0.00 | 0.00 |
February | 52.35 | 39.89 | 12.47 | 55.37 | 48.65 | 0.00 | 0.00 | 0.00 |
March | 69.77 | 48.84 | 20.94 | 77.87 | 36.16 | 0.00 | 0.00 | 0.00 |
April | 76.18 | 44.83 | 31.36 | 85.11 | 29.90 | 0.00 | 0.00 | 0.00 |
May | 97.71 | 52.64 | 45.07 | 117.42 | 21.70 | 0.00 | 0.00 | 0.00 |
June | 122.95 | 86.46 | 36.49 | 154.18 | 20.25 | 0.00 | 0.00 | 0.00 |
July | 106.29 | 63.94 | 42.35 | 133.28 | 19.02 | 0.00 | 0.00 | 0.00 |
August | 105.72 | 75.95 | 29.77 | 132.13 | 21.64 | 0.00 | 0.00 | 0.00 |
September | 82.27 | 55.26 | 27.01 | 99.71 | 28.79 | 0.00 | 0.00 | 0.00 |
October | 57.74 | 40.66 | 17.08 | 64.26 | 40.36 | 0.00 | 0.00 | 0.00 |
November | 40.29 | 28.52 | 11.76 | 43.68 | 43.38 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.26 | 10.52 | 26.58 | 55.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.96 | 48.26 | 24.69 | 85.53 | 34.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.77 | 18.26 | 10.52 | 26.58 | 19.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.95 | 86.46 | 45.07 | 154.18 | 55.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.38 | 23.80 | 10.58 | 35.20 | 48.39 | 0.00 | 0.00 | 0.00 |
February | 52.35 | 39.89 | 12.47 | 55.37 | 48.65 | 0.00 | 0.00 | 0.00 |
March | 69.77 | 48.84 | 20.94 | 77.87 | 36.16 | 0.00 | 0.00 | 0.00 |
April | 76.18 | 44.83 | 31.36 | 85.11 | 29.90 | 0.00 | 0.00 | 0.00 |
May | 97.71 | 52.64 | 45.07 | 117.42 | 21.70 | 0.00 | 0.00 | 0.00 |
June | 122.95 | 86.46 | 36.49 | 154.18 | 20.25 | 0.00 | 0.00 | 0.00 |
July | 106.29 | 63.94 | 42.35 | 133.28 | 19.02 | 0.00 | 0.00 | 0.00 |
August | 105.72 | 75.95 | 29.77 | 132.13 | 21.64 | 0.00 | 0.00 | 0.00 |
September | 82.27 | 55.26 | 27.01 | 99.71 | 28.79 | 0.00 | 0.00 | 0.00 |
October | 57.74 | 40.66 | 17.08 | 64.26 | 40.36 | 0.00 | 0.00 | 0.00 |
November | 40.29 | 28.52 | 11.76 | 43.68 | 43.38 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.26 | 10.52 | 26.58 | 55.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.96 | 48.26 | 24.69 | 85.53 | 34.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.77 | 18.26 | 10.52 | 26.58 | 19.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.95 | 86.46 | 45.07 | 154.18 | 55.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.38 | 23.80 | 10.58 | 35.20 | 48.39 | 0.00 | 0.00 | 0.00 |
February | 52.35 | 39.89 | 12.47 | 55.37 | 48.65 | 0.00 | 0.00 | 0.00 |
March | 69.77 | 48.84 | 20.94 | 77.87 | 36.16 | 0.00 | 0.00 | 0.00 |
April | 76.18 | 44.83 | 31.36 | 85.11 | 29.90 | 0.00 | 0.00 | 0.00 |
May | 97.71 | 52.64 | 45.07 | 117.42 | 21.70 | 0.00 | 0.00 | 0.00 |
June | 122.95 | 86.46 | 36.49 | 154.18 | 20.25 | 0.00 | 0.00 | 0.00 |
July | 106.29 | 63.94 | 42.35 | 133.28 | 19.02 | 0.00 | 0.00 | 0.00 |
August | 105.72 | 75.95 | 29.77 | 132.13 | 21.64 | 0.00 | 0.00 | 0.00 |
September | 82.27 | 55.26 | 27.01 | 99.71 | 28.79 | 0.00 | 0.00 | 0.00 |
October | 57.74 | 40.66 | 17.08 | 64.26 | 40.36 | 0.00 | 0.00 | 0.00 |
November | 40.29 | 28.52 | 11.76 | 43.68 | 43.38 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.26 | 10.52 | 26.58 | 55.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.96 | 48.26 | 24.69 | 85.53 | 34.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.77 | 18.26 | 10.52 | 26.58 | 19.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.95 | 86.46 | 45.07 | 154.18 | 55.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.38 | 23.80 | 10.58 | 35.20 | 48.39 | 0.00 | 0.00 | 0.00 |
February | 52.35 | 39.89 | 12.47 | 55.37 | 48.65 | 0.00 | 0.00 | 0.00 |
March | 69.77 | 48.84 | 20.94 | 77.87 | 36.16 | 0.00 | 0.00 | 0.00 |
April | 76.18 | 44.83 | 31.36 | 85.11 | 29.90 | 0.00 | 0.00 | 0.00 |
May | 97.71 | 52.64 | 45.07 | 117.42 | 21.70 | 0.00 | 0.00 | 0.00 |
June | 122.95 | 86.46 | 36.49 | 154.18 | 20.25 | 0.00 | 0.00 | 0.00 |
July | 106.29 | 63.94 | 42.35 | 133.28 | 19.02 | 0.00 | 0.00 | 0.00 |
August | 105.72 | 75.95 | 29.77 | 132.13 | 21.64 | 0.00 | 0.00 | 0.00 |
September | 82.27 | 55.26 | 27.01 | 99.71 | 28.79 | 0.00 | 0.00 | 0.00 |
October | 57.74 | 40.66 | 17.08 | 64.26 | 40.36 | 0.00 | 0.00 | 0.00 |
November | 40.29 | 28.52 | 11.76 | 43.68 | 43.38 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.26 | 10.52 | 26.58 | 55.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.96 | 48.26 | 24.69 | 85.53 | 34.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.77 | 18.26 | 10.52 | 26.58 | 19.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.95 | 86.46 | 45.07 | 154.18 | 55.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.38 | 23.80 | 10.58 | 35.20 | 48.39 | 0.00 | 0.00 | 0.00 |
February | 52.35 | 39.89 | 12.47 | 55.37 | 48.65 | 0.00 | 0.00 | 0.00 |
March | 69.77 | 48.84 | 20.94 | 77.87 | 36.16 | 0.00 | 0.00 | 0.00 |
April | 76.18 | 44.83 | 31.36 | 85.11 | 29.90 | 0.00 | 0.00 | 0.00 |
May | 97.71 | 52.64 | 45.07 | 117.42 | 21.70 | 0.00 | 0.00 | 0.00 |
June | 122.95 | 86.46 | 36.49 | 154.18 | 20.25 | 0.00 | 0.00 | 0.00 |
July | 106.29 | 63.94 | 42.35 | 133.28 | 19.02 | 0.00 | 0.00 | 0.00 |
August | 105.72 | 75.95 | 29.77 | 132.13 | 21.64 | 0.00 | 0.00 | 0.00 |
September | 82.27 | 55.26 | 27.01 | 99.71 | 28.79 | 0.00 | 0.00 | 0.00 |
October | 57.74 | 40.66 | 17.08 | 64.26 | 40.36 | 0.00 | 0.00 | 0.00 |
November | 40.29 | 28.52 | 11.76 | 43.68 | 43.38 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.26 | 10.52 | 26.58 | 55.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.96 | 48.26 | 24.69 | 85.53 | 34.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.77 | 18.26 | 10.52 | 26.58 | 19.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.95 | 86.46 | 45.07 | 154.18 | 55.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.38 | 23.80 | 10.58 | 35.20 | 48.39 | 0.00 | 0.00 | 0.00 |
February | 52.35 | 39.89 | 12.47 | 55.37 | 48.65 | 0.00 | 0.00 | 0.00 |
March | 69.77 | 48.84 | 20.94 | 77.87 | 36.16 | 0.00 | 0.00 | 0.00 |
April | 76.18 | 44.83 | 31.36 | 85.11 | 29.90 | 0.00 | 0.00 | 0.00 |
May | 97.71 | 52.64 | 45.07 | 117.42 | 21.70 | 0.00 | 0.00 | 0.00 |
June | 122.95 | 86.46 | 36.49 | 154.18 | 20.25 | 0.00 | 0.00 | 0.00 |
July | 106.29 | 63.94 | 42.35 | 133.28 | 19.02 | 0.00 | 0.00 | 0.00 |
August | 105.72 | 75.95 | 29.77 | 132.13 | 21.64 | 0.00 | 0.00 | 0.00 |
September | 82.27 | 55.26 | 27.01 | 99.71 | 28.79 | 0.00 | 0.00 | 0.00 |
October | 57.74 | 40.66 | 17.08 | 64.26 | 40.36 | 0.00 | 0.00 | 0.00 |
November | 40.29 | 28.52 | 11.76 | 43.68 | 43.38 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.26 | 10.52 | 26.58 | 55.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.96 | 48.26 | 24.69 | 85.53 | 34.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.77 | 18.26 | 10.52 | 26.58 | 19.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.95 | 86.46 | 45.07 | 154.18 | 55.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.38 | 23.80 | 10.58 | 35.20 | 48.39 | 0.00 | 0.00 | 0.00 |
February | 52.35 | 39.89 | 12.47 | 55.37 | 48.65 | 0.00 | 0.00 | 0.00 |
March | 69.77 | 48.84 | 20.94 | 77.87 | 36.16 | 0.00 | 0.00 | 0.00 |
April | 76.18 | 44.83 | 31.36 | 85.11 | 29.90 | 0.00 | 0.00 | 0.00 |
May | 97.71 | 52.64 | 45.07 | 117.42 | 21.70 | 0.00 | 0.00 | 0.00 |
June | 122.95 | 86.46 | 36.49 | 154.18 | 20.25 | 0.00 | 0.00 | 0.00 |
July | 106.29 | 63.94 | 42.35 | 133.28 | 19.02 | 0.00 | 0.00 | 0.00 |
August | 105.72 | 75.95 | 29.77 | 132.13 | 21.64 | 0.00 | 0.00 | 0.00 |
September | 82.27 | 55.26 | 27.01 | 99.71 | 28.79 | 0.00 | 0.00 | 0.00 |
October | 57.74 | 40.66 | 17.08 | 64.26 | 40.36 | 0.00 | 0.00 | 0.00 |
November | 40.29 | 28.52 | 11.76 | 43.68 | 43.38 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.26 | 10.52 | 26.58 | 55.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.96 | 48.26 | 24.69 | 85.53 | 34.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.77 | 18.26 | 10.52 | 26.58 | 19.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.95 | 86.46 | 45.07 | 154.18 | 55.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.38 | 23.80 | 10.58 | 35.20 | 48.39 | 0.00 | 0.00 | 0.00 |
February | 52.35 | 39.89 | 12.47 | 55.37 | 48.65 | 0.00 | 0.00 | 0.00 |
March | 69.77 | 48.84 | 20.94 | 77.87 | 36.16 | 0.00 | 0.00 | 0.00 |
April | 76.18 | 44.83 | 31.36 | 85.11 | 29.90 | 0.00 | 0.00 | 0.00 |
May | 97.71 | 52.64 | 45.07 | 117.42 | 21.70 | 0.00 | 0.00 | 0.00 |
June | 122.95 | 86.46 | 36.49 | 154.18 | 20.25 | 0.00 | 0.00 | 0.00 |
July | 106.29 | 63.94 | 42.35 | 133.28 | 19.02 | 0.00 | 0.00 | 0.00 |
August | 105.72 | 75.95 | 29.77 | 132.13 | 21.64 | 0.00 | 0.00 | 0.00 |
September | 82.27 | 55.26 | 27.01 | 99.71 | 28.79 | 0.00 | 0.00 | 0.00 |
October | 57.74 | 40.66 | 17.08 | 64.26 | 40.36 | 0.00 | 0.00 | 0.00 |
November | 40.29 | 28.52 | 11.76 | 43.68 | 43.38 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.26 | 10.52 | 26.58 | 55.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.96 | 48.26 | 24.69 | 85.53 | 34.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.77 | 18.26 | 10.52 | 26.58 | 19.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.95 | 86.46 | 45.07 | 154.18 | 55.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.38 | 23.80 | 10.58 | 35.20 | 48.39 | 0.00 | 0.00 | 0.00 |
February | 52.35 | 39.89 | 12.47 | 55.37 | 48.65 | 0.00 | 0.00 | 0.00 |
March | 69.77 | 48.84 | 20.94 | 77.87 | 36.16 | 0.00 | 0.00 | 0.00 |
April | 76.18 | 44.83 | 31.36 | 85.11 | 29.90 | 0.00 | 0.00 | 0.00 |
May | 97.71 | 52.64 | 45.07 | 117.42 | 21.70 | 0.00 | 0.00 | 0.00 |
June | 122.95 | 86.46 | 36.49 | 154.18 | 20.25 | 0.00 | 0.00 | 0.00 |
July | 106.29 | 63.94 | 42.35 | 133.28 | 19.02 | 0.00 | 0.00 | 0.00 |
August | 105.72 | 75.95 | 29.77 | 132.13 | 21.64 | 0.00 | 0.00 | 0.00 |
September | 82.27 | 55.26 | 27.01 | 99.71 | 28.79 | 0.00 | 0.00 | 0.00 |
October | 57.74 | 40.66 | 17.08 | 64.26 | 40.36 | 0.00 | 0.00 | 0.00 |
November | 40.29 | 28.52 | 11.76 | 43.68 | 43.38 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.26 | 10.52 | 26.58 | 55.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.96 | 48.26 | 24.69 | 85.53 | 34.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.77 | 18.26 | 10.52 | 26.58 | 19.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.95 | 86.46 | 45.07 | 154.18 | 55.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.38 | 23.80 | 10.58 | 35.20 | 48.39 | 0.00 | 0.00 | 0.00 |
February | 52.35 | 39.89 | 12.47 | 55.37 | 48.65 | 0.00 | 0.00 | 0.00 |
March | 69.77 | 48.84 | 20.94 | 77.87 | 36.16 | 0.00 | 0.00 | 0.00 |
April | 76.18 | 44.83 | 31.36 | 85.11 | 29.90 | 0.00 | 0.00 | 0.00 |
May | 97.71 | 52.64 | 45.07 | 117.42 | 21.70 | 0.00 | 0.00 | 0.00 |
June | 122.95 | 86.46 | 36.49 | 154.18 | 20.25 | 0.00 | 0.00 | 0.00 |
July | 106.29 | 63.94 | 42.35 | 133.28 | 19.02 | 0.00 | 0.00 | 0.00 |
August | 105.72 | 75.95 | 29.77 | 132.13 | 21.64 | 0.00 | 0.00 | 0.00 |
September | 82.27 | 55.26 | 27.01 | 99.71 | 28.79 | 0.00 | 0.00 | 0.00 |
October | 57.74 | 40.66 | 17.08 | 64.26 | 40.36 | 0.00 | 0.00 | 0.00 |
November | 40.29 | 28.52 | 11.76 | 43.68 | 43.38 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.26 | 10.52 | 26.58 | 55.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.96 | 48.26 | 24.69 | 85.53 | 34.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.77 | 18.26 | 10.52 | 26.58 | 19.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.95 | 86.46 | 45.07 | 154.18 | 55.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.38 | 23.80 | 10.58 | 35.20 | 48.39 | 0.00 | 0.00 | 0.00 |
February | 52.35 | 39.89 | 12.47 | 55.37 | 48.65 | 0.00 | 0.00 | 0.00 |
March | 69.77 | 48.84 | 20.94 | 77.87 | 36.16 | 0.00 | 0.00 | 0.00 |
April | 76.18 | 44.83 | 31.36 | 85.11 | 29.90 | 0.00 | 0.00 | 0.00 |
May | 97.71 | 52.64 | 45.07 | 117.42 | 21.70 | 0.00 | 0.00 | 0.00 |
June | 122.95 | 86.46 | 36.49 | 154.18 | 20.25 | 0.00 | 0.00 | 0.00 |
July | 106.29 | 63.94 | 42.35 | 133.28 | 19.02 | 0.00 | 0.00 | 0.00 |
August | 105.72 | 75.95 | 29.77 | 132.13 | 21.64 | 0.00 | 0.00 | 0.00 |
September | 82.27 | 55.26 | 27.01 | 99.71 | 28.79 | 0.00 | 0.00 | 0.00 |
October | 57.74 | 40.66 | 17.08 | 64.26 | 40.36 | 0.00 | 0.00 | 0.00 |
November | 40.29 | 28.52 | 11.76 | 43.68 | 43.38 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.26 | 10.52 | 26.58 | 55.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.96 | 48.26 | 24.69 | 85.53 | 34.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.77 | 18.26 | 10.52 | 26.58 | 19.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.95 | 86.46 | 45.07 | 154.18 | 55.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.38 | 23.80 | 10.58 | 35.20 | 48.39 | 0.00 | 0.00 | 0.00 |
February | 52.35 | 39.89 | 12.47 | 55.37 | 48.65 | 0.00 | 0.00 | 0.00 |
March | 69.77 | 48.84 | 20.94 | 77.87 | 36.16 | 0.00 | 0.00 | 0.00 |
April | 76.18 | 44.83 | 31.36 | 85.11 | 29.90 | 0.00 | 0.00 | 0.00 |
May | 97.71 | 52.64 | 45.07 | 117.42 | 21.70 | 0.00 | 0.00 | 0.00 |
June | 122.95 | 86.46 | 36.49 | 154.18 | 20.25 | 0.00 | 0.00 | 0.00 |
July | 106.29 | 63.94 | 42.35 | 133.28 | 19.02 | 0.00 | 0.00 | 0.00 |
August | 105.72 | 75.95 | 29.77 | 132.13 | 21.64 | 0.00 | 0.00 | 0.00 |
September | 82.27 | 55.26 | 27.01 | 99.71 | 28.79 | 0.00 | 0.00 | 0.00 |
October | 57.74 | 40.66 | 17.08 | 64.26 | 40.36 | 0.00 | 0.00 | 0.00 |
November | 40.29 | 28.52 | 11.76 | 43.68 | 43.38 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.26 | 10.52 | 26.58 | 55.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.96 | 48.26 | 24.69 | 85.53 | 34.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.77 | 18.26 | 10.52 | 26.58 | 19.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.95 | 86.46 | 45.07 | 154.18 | 55.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.38 | 23.80 | 10.58 | 35.20 | 48.39 | 0.00 | 0.00 | 0.00 |
February | 52.35 | 39.89 | 12.47 | 55.37 | 48.65 | 0.00 | 0.00 | 0.00 |
March | 69.77 | 48.84 | 20.94 | 77.87 | 36.16 | 0.00 | 0.00 | 0.00 |
April | 76.18 | 44.83 | 31.36 | 85.11 | 29.90 | 0.00 | 0.00 | 0.00 |
May | 97.71 | 52.64 | 45.07 | 117.42 | 21.70 | 0.00 | 0.00 | 0.00 |
June | 122.95 | 86.46 | 36.49 | 154.18 | 20.25 | 0.00 | 0.00 | 0.00 |
July | 106.29 | 63.94 | 42.35 | 133.28 | 19.02 | 0.00 | 0.00 | 0.00 |
August | 105.72 | 75.95 | 29.77 | 132.13 | 21.64 | 0.00 | 0.00 | 0.00 |
September | 82.27 | 55.26 | 27.01 | 99.71 | 28.79 | 0.00 | 0.00 | 0.00 |
October | 57.74 | 40.66 | 17.08 | 64.26 | 40.36 | 0.00 | 0.00 | 0.00 |
November | 40.29 | 28.52 | 11.76 | 43.68 | 43.38 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.26 | 10.52 | 26.58 | 55.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.96 | 48.26 | 24.69 | 85.53 | 34.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.77 | 18.26 | 10.52 | 26.58 | 19.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.95 | 86.46 | 45.07 | 154.18 | 55.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.38 | 23.80 | 10.58 | 35.20 | 48.39 | 0.00 | 0.00 | 0.00 |
February | 52.35 | 39.89 | 12.47 | 55.37 | 48.65 | 0.00 | 0.00 | 0.00 |
March | 69.77 | 48.84 | 20.94 | 77.87 | 36.16 | 0.00 | 0.00 | 0.00 |
April | 76.18 | 44.83 | 31.36 | 85.11 | 29.90 | 0.00 | 0.00 | 0.00 |
May | 97.71 | 52.64 | 45.07 | 117.42 | 21.70 | 0.00 | 0.00 | 0.00 |
June | 122.95 | 86.46 | 36.49 | 154.18 | 20.25 | 0.00 | 0.00 | 0.00 |
July | 106.29 | 63.94 | 42.35 | 133.28 | 19.02 | 0.00 | 0.00 | 0.00 |
August | 105.72 | 75.95 | 29.77 | 132.13 | 21.64 | 0.00 | 0.00 | 0.00 |
September | 82.27 | 55.26 | 27.01 | 99.71 | 28.79 | 0.00 | 0.00 | 0.00 |
October | 57.74 | 40.66 | 17.08 | 64.26 | 40.36 | 0.00 | 0.00 | 0.00 |
November | 40.29 | 28.52 | 11.76 | 43.68 | 43.38 | 0.00 | 0.00 | 0.00 |
December | 28.77 | 18.26 | 10.52 | 26.58 | 55.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.96 | 48.26 | 24.69 | 85.53 | 34.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.77 | 18.26 | 10.52 | 26.58 | 19.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.95 | 86.46 | 45.07 | 154.18 | 55.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 60.29 | 58.73 | 3.83 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 88.52 | 60.36 | 3.50 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 121.05 | 44.89 | 11.17 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 130.66 | 37.00 | 7.83 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 173.92 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 220.05 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 186.72 | 37.92 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 187.06 | 40.97 | 1.50 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 144.43 | 48.17 | 1.50 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 97.34 | 56.48 | 12.50 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 72.42 | 51.96 | 5.50 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 47.21 | 70.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 127.64 | 47.78 | 47.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 47.21 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 220.05 | 70.40 | 12.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294875E+09 | 0.186761E+09 | 0.108114E+09 | 0.308863E+09 | 0.342520E+09 |
February | 0.323380E+09 | 0.200971E+09 | 0.122409E+09 | 0.334172E+09 | 0.315212E+09 |
March | 0.417328E+09 | 0.230425E+09 | 0.186903E+09 | 0.458128E+09 | 0.253898E+09 |
April | 0.378524E+09 | 0.159656E+09 | 0.218869E+09 | 0.403696E+09 | 0.208056E+09 |
May | 0.479526E+09 | 0.168972E+09 | 0.310554E+09 | 0.588068E+09 | 0.137340E+09 |
June | 0.568265E+09 | 0.273688E+09 | 0.294577E+09 | 0.780590E+09 | 0.104226E+09 |
July | 0.477620E+09 | 0.174692E+09 | 0.302927E+09 | 0.654427E+09 | 0.103101E+09 |
August | 0.499844E+09 | 0.247305E+09 | 0.252539E+09 | 0.673228E+09 | 0.118851E+09 |
September | 0.429456E+09 | 0.206413E+09 | 0.223043E+09 | 0.556413E+09 | 0.163196E+09 |
October | 0.371075E+09 | 0.211713E+09 | 0.159363E+09 | 0.422255E+09 | 0.285638E+09 |
November | 0.295113E+09 | 0.179007E+09 | 0.116106E+09 | 0.315754E+09 | 0.304790E+09 |
December | 0.246574E+09 | 0.145623E+09 | 0.100951E+09 | 0.235385E+09 | 0.399181E+09 |
Annual Sum or Average | 0.478158E+10 | 0.238523E+10 | 0.239635E+10 | 0.573098E+10 | 0.273601E+10 |
Minimum of Months | 0.246574E+09 | 0.145623E+09 | 0.100951E+09 | 0.235385E+09 | 0.103101E+09 |
Maximum of Months | 0.568265E+09 | 0.273688E+09 | 0.310554E+09 | 0.780590E+09 | 0.399181E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294875E+09 | 0.186761E+09 | 0.108114E+09 | 0.308863E+09 | 0.342520E+09 |
February | 0.323380E+09 | 0.200971E+09 | 0.122409E+09 | 0.334172E+09 | 0.315212E+09 |
March | 0.417328E+09 | 0.230425E+09 | 0.186903E+09 | 0.458128E+09 | 0.253898E+09 |
April | 0.378524E+09 | 0.159656E+09 | 0.218869E+09 | 0.403696E+09 | 0.208056E+09 |
May | 0.479526E+09 | 0.168972E+09 | 0.310554E+09 | 0.588068E+09 | 0.137340E+09 |
June | 0.568265E+09 | 0.273688E+09 | 0.294577E+09 | 0.780590E+09 | 0.104226E+09 |
July | 0.477620E+09 | 0.174692E+09 | 0.302927E+09 | 0.654427E+09 | 0.103101E+09 |
August | 0.499844E+09 | 0.247305E+09 | 0.252539E+09 | 0.673228E+09 | 0.118851E+09 |
September | 0.429456E+09 | 0.206413E+09 | 0.223043E+09 | 0.556413E+09 | 0.163196E+09 |
October | 0.371075E+09 | 0.211713E+09 | 0.159363E+09 | 0.422255E+09 | 0.285638E+09 |
November | 0.295113E+09 | 0.179007E+09 | 0.116106E+09 | 0.315754E+09 | 0.304790E+09 |
December | 0.246574E+09 | 0.145623E+09 | 0.100951E+09 | 0.235385E+09 | 0.399181E+09 |
Annual Sum or Average | 0.478158E+10 | 0.238523E+10 | 0.239635E+10 | 0.573098E+10 | 0.273601E+10 |
Minimum of Months | 0.246574E+09 | 0.145623E+09 | 0.100951E+09 | 0.235385E+09 | 0.103101E+09 |
Maximum of Months | 0.568265E+09 | 0.273688E+09 | 0.310554E+09 | 0.780590E+09 | 0.399181E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51696522.48 | 0.00 | 51696522.48 | 16086068.71 | 0.211404E+09 |
February | 58688327.64 | 0.00 | 58688327.64 | 18277842.98 | 0.193501E+09 |
March | 88445065.16 | 9657.97 | 88435407.19 | 54167483.08 | 0.154183E+09 |
April | 0.107503E+09 | 663703.27 | 0.106839E+09 | 76664013.70 | 0.122324E+09 |
May | 0.151830E+09 | 5094460.50 | 0.146735E+09 | 0.159444E+09 | 76022263.96 |
June | 0.160724E+09 | 17609727.71 | 0.143114E+09 | 0.213420E+09 | 55909067.24 |
July | 0.157617E+09 | 10448747.20 | 0.147168E+09 | 0.210070E+09 | 56664648.86 |
August | 0.125727E+09 | 3436598.59 | 0.122290E+09 | 0.157574E+09 | 67801890.14 |
September | 0.101861E+09 | 67031.71 | 0.101794E+09 | 0.113382E+09 | 95582720.88 |
October | 75323517.12 | 0.00 | 75323517.12 | 47293854.82 | 0.170843E+09 |
November | 55335578.97 | 0.00 | 55335578.97 | 22957779.28 | 0.185374E+09 |
December | 48368524.34 | 0.00 | 48368524.34 | 12819429.60 | 0.248510E+09 |
Annual Sum or Average | 0.118312E+10 | 37329926.96 | 0.114579E+10 | 0.110216E+10 | 0.163812E+10 |
Minimum of Months | 48368524.34 | 0.00 | 48368524.34 | 12819429.60 | 55909067.24 |
Maximum of Months | 0.160724E+09 | 17609727.71 | 0.147168E+09 | 0.213420E+09 | 0.248510E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51695158.16 | 0.00 | 51695158.16 | 16085226.57 | 0.211403E+09 |
February | 58686880.96 | 0.00 | 58686880.96 | 18276994.94 | 0.193501E+09 |
March | 88442677.75 | 9657.52 | 88433020.23 | 54165448.41 | 0.154183E+09 |
April | 0.107500E+09 | 663672.16 | 0.106836E+09 | 76660865.67 | 0.122324E+09 |
May | 0.151825E+09 | 5094221.72 | 0.146731E+09 | 0.159438E+09 | 76021860.63 |
June | 0.160719E+09 | 17608902.32 | 0.143110E+09 | 0.213414E+09 | 55908478.36 |
July | 0.157612E+09 | 10448257.45 | 0.147164E+09 | 0.210064E+09 | 56664151.91 |
August | 0.125724E+09 | 3436437.51 | 0.122287E+09 | 0.157570E+09 | 67801311.38 |
September | 0.101858E+09 | 67028.57 | 0.101791E+09 | 0.113379E+09 | 95581976.25 |
October | 75321502.17 | 0.00 | 75321502.17 | 47292230.94 | 0.170843E+09 |
November | 55334122.69 | 0.00 | 55334122.69 | 22956780.59 | 0.185373E+09 |
December | 48367171.72 | 0.00 | 48367171.72 | 12818848.60 | 0.248510E+09 |
Annual Sum or Average | 0.118309E+10 | 37328177.25 | 0.114576E+10 | 0.110212E+10 | 0.163812E+10 |
Minimum of Months | 48367171.72 | 0.00 | 48367171.72 | 12818848.60 | 55908478.36 |
Maximum of Months | 0.160719E+09 | 17608902.32 | 0.147164E+09 | 0.213414E+09 | 0.248510E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92089080.81 | 63745832.02 | 28343248.78 | 94272577.32 | 0.129603E+09 |
February | 0.126657E+09 | 96495509.33 | 30161542.02 | 0.133955E+09 | 0.117689E+09 |
March | 0.186884E+09 | 0.130809E+09 | 56074822.59 | 0.208573E+09 | 96858320.39 |
April | 0.197470E+09 | 0.116189E+09 | 81280533.89 | 0.220606E+09 | 77512087.19 |
May | 0.261701E+09 | 0.140996E+09 | 0.120704E+09 | 0.314497E+09 | 58109901.49 |
June | 0.318697E+09 | 0.224106E+09 | 94590756.41 | 0.399641E+09 | 52484419.24 |
July | 0.284684E+09 | 0.171254E+09 | 0.113430E+09 | 0.356970E+09 | 50941874.37 |
August | 0.283169E+09 | 0.203430E+09 | 79739390.22 | 0.353910E+09 | 57949766.66 |
September | 0.213248E+09 | 0.143237E+09 | 70010726.83 | 0.258453E+09 | 74630219.10 |
October | 0.154654E+09 | 0.108896E+09 | 45758686.50 | 0.172101E+09 | 0.108089E+09 |
November | 0.104424E+09 | 73929701.65 | 30494009.67 | 0.113231E+09 | 0.112430E+09 |
December | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 0.149598E+09 |
Annual Sum or Average | 0.230074E+10 | 0.152199E+10 | 0.778756E+09 | 0.269740E+10 | 0.108590E+10 |
Minimum of Months | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 50941874.37 |
Maximum of Months | 0.318697E+09 | 0.224106E+09 | 0.120704E+09 | 0.399641E+09 | 0.149598E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92089080.81 | 63745832.02 | 28343248.78 | 94272577.32 | 0.129603E+09 |
February | 0.126657E+09 | 96495509.33 | 30161542.02 | 0.133955E+09 | 0.117689E+09 |
March | 0.186884E+09 | 0.130809E+09 | 56074822.59 | 0.208573E+09 | 96858320.39 |
April | 0.197470E+09 | 0.116189E+09 | 81280533.89 | 0.220606E+09 | 77512087.19 |
May | 0.261701E+09 | 0.140996E+09 | 0.120704E+09 | 0.314497E+09 | 58109901.49 |
June | 0.318697E+09 | 0.224106E+09 | 94590756.41 | 0.399641E+09 | 52484419.24 |
July | 0.284684E+09 | 0.171254E+09 | 0.113430E+09 | 0.356970E+09 | 50941874.37 |
August | 0.283169E+09 | 0.203430E+09 | 79739390.22 | 0.353910E+09 | 57949766.66 |
September | 0.213248E+09 | 0.143237E+09 | 70010726.83 | 0.258453E+09 | 74630219.10 |
October | 0.154654E+09 | 0.108896E+09 | 45758686.50 | 0.172101E+09 | 0.108089E+09 |
November | 0.104424E+09 | 73929701.65 | 30494009.67 | 0.113231E+09 | 0.112430E+09 |
December | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 0.149598E+09 |
Annual Sum or Average | 0.230074E+10 | 0.152199E+10 | 0.778756E+09 | 0.269740E+10 | 0.108590E+10 |
Minimum of Months | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 50941874.37 |
Maximum of Months | 0.318697E+09 | 0.224106E+09 | 0.120704E+09 | 0.399641E+09 | 0.149598E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92089080.81 | 63745832.02 | 28343248.78 | 94272577.32 | 0.129603E+09 |
February | 0.126657E+09 | 96495509.33 | 30161542.02 | 0.133955E+09 | 0.117689E+09 |
March | 0.186884E+09 | 0.130809E+09 | 56074822.59 | 0.208573E+09 | 96858320.39 |
April | 0.197470E+09 | 0.116189E+09 | 81280533.89 | 0.220606E+09 | 77512087.19 |
May | 0.261701E+09 | 0.140996E+09 | 0.120704E+09 | 0.314497E+09 | 58109901.49 |
June | 0.318697E+09 | 0.224106E+09 | 94590756.41 | 0.399641E+09 | 52484419.24 |
July | 0.284684E+09 | 0.171254E+09 | 0.113430E+09 | 0.356970E+09 | 50941874.37 |
August | 0.283169E+09 | 0.203430E+09 | 79739390.22 | 0.353910E+09 | 57949766.66 |
September | 0.213248E+09 | 0.143237E+09 | 70010726.83 | 0.258453E+09 | 74630219.10 |
October | 0.154654E+09 | 0.108896E+09 | 45758686.50 | 0.172101E+09 | 0.108089E+09 |
November | 0.104424E+09 | 73929701.65 | 30494009.67 | 0.113231E+09 | 0.112430E+09 |
December | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 0.149598E+09 |
Annual Sum or Average | 0.230074E+10 | 0.152199E+10 | 0.778756E+09 | 0.269740E+10 | 0.108590E+10 |
Minimum of Months | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 50941874.37 |
Maximum of Months | 0.318697E+09 | 0.224106E+09 | 0.120704E+09 | 0.399641E+09 | 0.149598E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92089080.81 | 63745832.02 | 28343248.78 | 94272577.32 | 0.129603E+09 |
February | 0.126657E+09 | 96495509.33 | 30161542.02 | 0.133955E+09 | 0.117689E+09 |
March | 0.186884E+09 | 0.130809E+09 | 56074822.59 | 0.208573E+09 | 96858320.39 |
April | 0.197470E+09 | 0.116189E+09 | 81280533.89 | 0.220606E+09 | 77512087.19 |
May | 0.261701E+09 | 0.140996E+09 | 0.120704E+09 | 0.314497E+09 | 58109901.49 |
June | 0.318697E+09 | 0.224106E+09 | 94590756.41 | 0.399641E+09 | 52484419.24 |
July | 0.284684E+09 | 0.171254E+09 | 0.113430E+09 | 0.356970E+09 | 50941874.37 |
August | 0.283169E+09 | 0.203430E+09 | 79739390.22 | 0.353910E+09 | 57949766.66 |
September | 0.213248E+09 | 0.143237E+09 | 70010726.83 | 0.258453E+09 | 74630219.10 |
October | 0.154654E+09 | 0.108896E+09 | 45758686.50 | 0.172101E+09 | 0.108089E+09 |
November | 0.104424E+09 | 73929701.65 | 30494009.67 | 0.113231E+09 | 0.112430E+09 |
December | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 0.149598E+09 |
Annual Sum or Average | 0.230074E+10 | 0.152199E+10 | 0.778756E+09 | 0.269740E+10 | 0.108590E+10 |
Minimum of Months | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 50941874.37 |
Maximum of Months | 0.318697E+09 | 0.224106E+09 | 0.120704E+09 | 0.399641E+09 | 0.149598E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92089080.81 | 63745832.02 | 28343248.78 | 94272577.32 | 0.129603E+09 |
February | 0.126657E+09 | 96495509.33 | 30161542.02 | 0.133955E+09 | 0.117689E+09 |
March | 0.186884E+09 | 0.130809E+09 | 56074822.59 | 0.208573E+09 | 96858320.39 |
April | 0.197470E+09 | 0.116189E+09 | 81280533.89 | 0.220606E+09 | 77512087.19 |
May | 0.261701E+09 | 0.140996E+09 | 0.120704E+09 | 0.314497E+09 | 58109901.49 |
June | 0.318697E+09 | 0.224106E+09 | 94590756.41 | 0.399641E+09 | 52484419.24 |
July | 0.284684E+09 | 0.171254E+09 | 0.113430E+09 | 0.356970E+09 | 50941874.37 |
August | 0.283169E+09 | 0.203430E+09 | 79739390.22 | 0.353910E+09 | 57949766.66 |
September | 0.213248E+09 | 0.143237E+09 | 70010726.83 | 0.258453E+09 | 74630219.10 |
October | 0.154654E+09 | 0.108896E+09 | 45758686.50 | 0.172101E+09 | 0.108089E+09 |
November | 0.104424E+09 | 73929701.65 | 30494009.67 | 0.113231E+09 | 0.112430E+09 |
December | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 0.149598E+09 |
Annual Sum or Average | 0.230074E+10 | 0.152199E+10 | 0.778756E+09 | 0.269740E+10 | 0.108590E+10 |
Minimum of Months | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 50941874.37 |
Maximum of Months | 0.318697E+09 | 0.224106E+09 | 0.120704E+09 | 0.399641E+09 | 0.149598E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92089080.81 | 63745832.02 | 28343248.78 | 94272577.32 | 0.129603E+09 |
February | 0.126657E+09 | 96495509.33 | 30161542.02 | 0.133955E+09 | 0.117689E+09 |
March | 0.186884E+09 | 0.130809E+09 | 56074822.59 | 0.208573E+09 | 96858320.39 |
April | 0.197470E+09 | 0.116189E+09 | 81280533.89 | 0.220606E+09 | 77512087.19 |
May | 0.261701E+09 | 0.140996E+09 | 0.120704E+09 | 0.314497E+09 | 58109901.49 |
June | 0.318697E+09 | 0.224106E+09 | 94590756.41 | 0.399641E+09 | 52484419.24 |
July | 0.284684E+09 | 0.171254E+09 | 0.113430E+09 | 0.356970E+09 | 50941874.37 |
August | 0.283169E+09 | 0.203430E+09 | 79739390.22 | 0.353910E+09 | 57949766.66 |
September | 0.213248E+09 | 0.143237E+09 | 70010726.83 | 0.258453E+09 | 74630219.10 |
October | 0.154654E+09 | 0.108896E+09 | 45758686.50 | 0.172101E+09 | 0.108089E+09 |
November | 0.104424E+09 | 73929701.65 | 30494009.67 | 0.113231E+09 | 0.112430E+09 |
December | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 0.149598E+09 |
Annual Sum or Average | 0.230074E+10 | 0.152199E+10 | 0.778756E+09 | 0.269740E+10 | 0.108590E+10 |
Minimum of Months | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 50941874.37 |
Maximum of Months | 0.318697E+09 | 0.224106E+09 | 0.120704E+09 | 0.399641E+09 | 0.149598E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92089080.81 | 63745832.02 | 28343248.78 | 94272577.32 | 0.129603E+09 |
February | 0.126657E+09 | 96495509.33 | 30161542.02 | 0.133955E+09 | 0.117689E+09 |
March | 0.186884E+09 | 0.130809E+09 | 56074822.59 | 0.208573E+09 | 96858320.39 |
April | 0.197470E+09 | 0.116189E+09 | 81280533.89 | 0.220606E+09 | 77512087.19 |
May | 0.261701E+09 | 0.140996E+09 | 0.120704E+09 | 0.314497E+09 | 58109901.49 |
June | 0.318697E+09 | 0.224106E+09 | 94590756.41 | 0.399641E+09 | 52484419.24 |
July | 0.284684E+09 | 0.171254E+09 | 0.113430E+09 | 0.356970E+09 | 50941874.37 |
August | 0.283169E+09 | 0.203430E+09 | 79739390.22 | 0.353910E+09 | 57949766.66 |
September | 0.213248E+09 | 0.143237E+09 | 70010726.83 | 0.258453E+09 | 74630219.10 |
October | 0.154654E+09 | 0.108896E+09 | 45758686.50 | 0.172101E+09 | 0.108089E+09 |
November | 0.104424E+09 | 73929701.65 | 30494009.67 | 0.113231E+09 | 0.112430E+09 |
December | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 0.149598E+09 |
Annual Sum or Average | 0.230074E+10 | 0.152199E+10 | 0.778756E+09 | 0.269740E+10 | 0.108590E+10 |
Minimum of Months | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 50941874.37 |
Maximum of Months | 0.318697E+09 | 0.224106E+09 | 0.120704E+09 | 0.399641E+09 | 0.149598E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92089080.81 | 63745832.02 | 28343248.78 | 94272577.32 | 0.129603E+09 |
February | 0.126657E+09 | 96495509.33 | 30161542.02 | 0.133955E+09 | 0.117689E+09 |
March | 0.186884E+09 | 0.130809E+09 | 56074822.59 | 0.208573E+09 | 96858320.39 |
April | 0.197470E+09 | 0.116189E+09 | 81280533.89 | 0.220606E+09 | 77512087.19 |
May | 0.261701E+09 | 0.140996E+09 | 0.120704E+09 | 0.314497E+09 | 58109901.49 |
June | 0.318697E+09 | 0.224106E+09 | 94590756.41 | 0.399641E+09 | 52484419.24 |
July | 0.284684E+09 | 0.171254E+09 | 0.113430E+09 | 0.356970E+09 | 50941874.37 |
August | 0.283169E+09 | 0.203430E+09 | 79739390.22 | 0.353910E+09 | 57949766.66 |
September | 0.213248E+09 | 0.143237E+09 | 70010726.83 | 0.258453E+09 | 74630219.10 |
October | 0.154654E+09 | 0.108896E+09 | 45758686.50 | 0.172101E+09 | 0.108089E+09 |
November | 0.104424E+09 | 73929701.65 | 30494009.67 | 0.113231E+09 | 0.112430E+09 |
December | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 0.149598E+09 |
Annual Sum or Average | 0.230074E+10 | 0.152199E+10 | 0.778756E+09 | 0.269740E+10 | 0.108590E+10 |
Minimum of Months | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 50941874.37 |
Maximum of Months | 0.318697E+09 | 0.224106E+09 | 0.120704E+09 | 0.399641E+09 | 0.149598E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92089080.81 | 63745832.02 | 28343248.78 | 94272577.32 | 0.129603E+09 |
February | 0.126657E+09 | 96495509.33 | 30161542.02 | 0.133955E+09 | 0.117689E+09 |
March | 0.186884E+09 | 0.130809E+09 | 56074822.59 | 0.208573E+09 | 96858320.39 |
April | 0.197470E+09 | 0.116189E+09 | 81280533.89 | 0.220606E+09 | 77512087.19 |
May | 0.261701E+09 | 0.140996E+09 | 0.120704E+09 | 0.314497E+09 | 58109901.49 |
June | 0.318697E+09 | 0.224106E+09 | 94590756.41 | 0.399641E+09 | 52484419.24 |
July | 0.284684E+09 | 0.171254E+09 | 0.113430E+09 | 0.356970E+09 | 50941874.37 |
August | 0.283169E+09 | 0.203430E+09 | 79739390.22 | 0.353910E+09 | 57949766.66 |
September | 0.213248E+09 | 0.143237E+09 | 70010726.83 | 0.258453E+09 | 74630219.10 |
October | 0.154654E+09 | 0.108896E+09 | 45758686.50 | 0.172101E+09 | 0.108089E+09 |
November | 0.104424E+09 | 73929701.65 | 30494009.67 | 0.113231E+09 | 0.112430E+09 |
December | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 0.149598E+09 |
Annual Sum or Average | 0.230074E+10 | 0.152199E+10 | 0.778756E+09 | 0.269740E+10 | 0.108590E+10 |
Minimum of Months | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 50941874.37 |
Maximum of Months | 0.318697E+09 | 0.224106E+09 | 0.120704E+09 | 0.399641E+09 | 0.149598E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92089080.81 | 63745832.02 | 28343248.78 | 94272577.32 | 0.129603E+09 |
February | 0.126657E+09 | 96495509.33 | 30161542.02 | 0.133955E+09 | 0.117689E+09 |
March | 0.186884E+09 | 0.130809E+09 | 56074822.59 | 0.208573E+09 | 96858320.39 |
April | 0.197470E+09 | 0.116189E+09 | 81280533.89 | 0.220606E+09 | 77512087.19 |
May | 0.261701E+09 | 0.140996E+09 | 0.120704E+09 | 0.314497E+09 | 58109901.49 |
June | 0.318697E+09 | 0.224106E+09 | 94590756.41 | 0.399641E+09 | 52484419.24 |
July | 0.284684E+09 | 0.171254E+09 | 0.113430E+09 | 0.356970E+09 | 50941874.37 |
August | 0.283169E+09 | 0.203430E+09 | 79739390.22 | 0.353910E+09 | 57949766.66 |
September | 0.213248E+09 | 0.143237E+09 | 70010726.83 | 0.258453E+09 | 74630219.10 |
October | 0.154654E+09 | 0.108896E+09 | 45758686.50 | 0.172101E+09 | 0.108089E+09 |
November | 0.104424E+09 | 73929701.65 | 30494009.67 | 0.113231E+09 | 0.112430E+09 |
December | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 0.149598E+09 |
Annual Sum or Average | 0.230074E+10 | 0.152199E+10 | 0.778756E+09 | 0.269740E+10 | 0.108590E+10 |
Minimum of Months | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 50941874.37 |
Maximum of Months | 0.318697E+09 | 0.224106E+09 | 0.120704E+09 | 0.399641E+09 | 0.149598E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92089080.81 | 63745832.02 | 28343248.78 | 94272577.32 | 0.129603E+09 |
February | 0.126657E+09 | 96495509.33 | 30161542.02 | 0.133955E+09 | 0.117689E+09 |
March | 0.186884E+09 | 0.130809E+09 | 56074822.59 | 0.208573E+09 | 96858320.39 |
April | 0.197470E+09 | 0.116189E+09 | 81280533.89 | 0.220606E+09 | 77512087.19 |
May | 0.261701E+09 | 0.140996E+09 | 0.120704E+09 | 0.314497E+09 | 58109901.49 |
June | 0.318697E+09 | 0.224106E+09 | 94590756.41 | 0.399641E+09 | 52484419.24 |
July | 0.284684E+09 | 0.171254E+09 | 0.113430E+09 | 0.356970E+09 | 50941874.37 |
August | 0.283169E+09 | 0.203430E+09 | 79739390.22 | 0.353910E+09 | 57949766.66 |
September | 0.213248E+09 | 0.143237E+09 | 70010726.83 | 0.258453E+09 | 74630219.10 |
October | 0.154654E+09 | 0.108896E+09 | 45758686.50 | 0.172101E+09 | 0.108089E+09 |
November | 0.104424E+09 | 73929701.65 | 30494009.67 | 0.113231E+09 | 0.112430E+09 |
December | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 0.149598E+09 |
Annual Sum or Average | 0.230074E+10 | 0.152199E+10 | 0.778756E+09 | 0.269740E+10 | 0.108590E+10 |
Minimum of Months | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 50941874.37 |
Maximum of Months | 0.318697E+09 | 0.224106E+09 | 0.120704E+09 | 0.399641E+09 | 0.149598E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92089080.81 | 63745832.02 | 28343248.78 | 94272577.32 | 0.129603E+09 |
February | 0.126657E+09 | 96495509.33 | 30161542.02 | 0.133955E+09 | 0.117689E+09 |
March | 0.186884E+09 | 0.130809E+09 | 56074822.59 | 0.208573E+09 | 96858320.39 |
April | 0.197470E+09 | 0.116189E+09 | 81280533.89 | 0.220606E+09 | 77512087.19 |
May | 0.261701E+09 | 0.140996E+09 | 0.120704E+09 | 0.314497E+09 | 58109901.49 |
June | 0.318697E+09 | 0.224106E+09 | 94590756.41 | 0.399641E+09 | 52484419.24 |
July | 0.284684E+09 | 0.171254E+09 | 0.113430E+09 | 0.356970E+09 | 50941874.37 |
August | 0.283169E+09 | 0.203430E+09 | 79739390.22 | 0.353910E+09 | 57949766.66 |
September | 0.213248E+09 | 0.143237E+09 | 70010726.83 | 0.258453E+09 | 74630219.10 |
October | 0.154654E+09 | 0.108896E+09 | 45758686.50 | 0.172101E+09 | 0.108089E+09 |
November | 0.104424E+09 | 73929701.65 | 30494009.67 | 0.113231E+09 | 0.112430E+09 |
December | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 0.149598E+09 |
Annual Sum or Average | 0.230074E+10 | 0.152199E+10 | 0.778756E+09 | 0.269740E+10 | 0.108590E+10 |
Minimum of Months | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 50941874.37 |
Maximum of Months | 0.318697E+09 | 0.224106E+09 | 0.120704E+09 | 0.399641E+09 | 0.149598E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92089080.81 | 63745832.02 | 28343248.78 | 94272577.32 | 0.129603E+09 |
February | 0.126657E+09 | 96495509.33 | 30161542.02 | 0.133955E+09 | 0.117689E+09 |
March | 0.186884E+09 | 0.130809E+09 | 56074822.59 | 0.208573E+09 | 96858320.39 |
April | 0.197470E+09 | 0.116189E+09 | 81280533.89 | 0.220606E+09 | 77512087.19 |
May | 0.261701E+09 | 0.140996E+09 | 0.120704E+09 | 0.314497E+09 | 58109901.49 |
June | 0.318697E+09 | 0.224106E+09 | 94590756.41 | 0.399641E+09 | 52484419.24 |
July | 0.284684E+09 | 0.171254E+09 | 0.113430E+09 | 0.356970E+09 | 50941874.37 |
August | 0.283169E+09 | 0.203430E+09 | 79739390.22 | 0.353910E+09 | 57949766.66 |
September | 0.213248E+09 | 0.143237E+09 | 70010726.83 | 0.258453E+09 | 74630219.10 |
October | 0.154654E+09 | 0.108896E+09 | 45758686.50 | 0.172101E+09 | 0.108089E+09 |
November | 0.104424E+09 | 73929701.65 | 30494009.67 | 0.113231E+09 | 0.112430E+09 |
December | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 0.149598E+09 |
Annual Sum or Average | 0.230074E+10 | 0.152199E+10 | 0.778756E+09 | 0.269740E+10 | 0.108590E+10 |
Minimum of Months | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 50941874.37 |
Maximum of Months | 0.318697E+09 | 0.224106E+09 | 0.120704E+09 | 0.399641E+09 | 0.149598E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92089080.81 | 63745832.02 | 28343248.78 | 94272577.32 | 0.129603E+09 |
February | 0.126657E+09 | 96495509.33 | 30161542.02 | 0.133955E+09 | 0.117689E+09 |
March | 0.186884E+09 | 0.130809E+09 | 56074822.59 | 0.208573E+09 | 96858320.39 |
April | 0.197470E+09 | 0.116189E+09 | 81280533.89 | 0.220606E+09 | 77512087.19 |
May | 0.261701E+09 | 0.140996E+09 | 0.120704E+09 | 0.314497E+09 | 58109901.49 |
June | 0.318697E+09 | 0.224106E+09 | 94590756.41 | 0.399641E+09 | 52484419.24 |
July | 0.284684E+09 | 0.171254E+09 | 0.113430E+09 | 0.356970E+09 | 50941874.37 |
August | 0.283169E+09 | 0.203430E+09 | 79739390.22 | 0.353910E+09 | 57949766.66 |
September | 0.213248E+09 | 0.143237E+09 | 70010726.83 | 0.258453E+09 | 74630219.10 |
October | 0.154654E+09 | 0.108896E+09 | 45758686.50 | 0.172101E+09 | 0.108089E+09 |
November | 0.104424E+09 | 73929701.65 | 30494009.67 | 0.113231E+09 | 0.112430E+09 |
December | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 0.149598E+09 |
Annual Sum or Average | 0.230074E+10 | 0.152199E+10 | 0.778756E+09 | 0.269740E+10 | 0.108590E+10 |
Minimum of Months | 77066964.09 | 48898877.35 | 28168086.74 | 71189402.83 | 50941874.37 |
Maximum of Months | 0.318697E+09 | 0.224106E+09 | 0.120704E+09 | 0.399641E+09 | 0.149598E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.161485E+09 | 0.157301E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.214135E+09 | 0.146013E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.324227E+09 | 0.120233E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.338676E+09 | 95903255.90 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.465833E+09 | 82926011.04 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.570378E+09 | 93555554.26 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.500099E+09 | 0.101577E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.501031E+09 | 0.109735E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.374362E+09 | 0.124869E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.260721E+09 | 0.151279E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.187720E+09 | 0.134684E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 0.188565E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.402510E+10 | 0.150664E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.126436E+09 | 82926011.04 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.570378E+09 | 0.188565E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 234.32 | 405.30 | 258.79 | 139.46 | 119.33 | 0.00 | 0.00 |
February | 282.88 | 412.06 | 315.86 | 166.15 | 149.72 | 0.00 | 0.00 |
March | 378.96 | 301.14 | 377.67 | 172.07 | 205.60 | 0.00 | 0.00 |
April | 369.26 | 253.54 | 375.02 | 123.70 | 251.32 | 0.00 | 0.00 |
May | 556.14 | 157.29 | 471.44 | 129.98 | 341.46 | 0.00 | 0.00 |
June | 763.40 | 119.98 | 562.49 | 224.77 | 337.72 | 0.00 | 0.00 |
July | 643.11 | 116.88 | 474.34 | 138.25 | 336.09 | 0.00 | 0.00 |
August | 619.54 | 138.55 | 467.12 | 187.23 | 279.89 | 0.00 | 0.00 |
September | 516.05 | 198.91 | 409.97 | 159.32 | 250.65 | 0.00 | 0.00 |
October | 348.32 | 338.56 | 333.33 | 158.09 | 175.24 | 0.00 | 0.00 |
November | 255.68 | 372.54 | 270.41 | 138.12 | 132.28 | 0.00 | 0.00 |
December | 176.25 | 474.55 | 220.24 | 108.74 | 111.50 | 0.00 | 0.00 |
Annual Sum or Average | 429.34 | 273.39 | 378.28 | 153.64 | 224.64 | 0.00 | 0.00 |
Minimum of Months | 176.25 | 116.88 | 220.24 | 108.74 | 111.50 | 0.00 | 0.00 |
Maximum of Months | 763.40 | 474.55 | 562.49 | 224.77 | 341.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 492.76 | 677.44 | 481.35 | 333.20 | 148.15 | 0.00 | 0.00 |
February | 775.20 | 681.07 | 732.97 | 558.42 | 174.55 | 0.00 | 0.00 |
March | 1090.21 | 506.28 | 976.84 | 683.74 | 293.10 | 0.00 | 0.00 |
April | 1191.54 | 418.66 | 1066.58 | 627.56 | 439.02 | 0.00 | 0.00 |
May | 1643.88 | 303.74 | 1367.91 | 736.99 | 630.92 | 0.00 | 0.00 |
June | 2158.55 | 283.48 | 1721.36 | 1210.45 | 510.91 | 0.00 | 0.00 |
July | 1865.88 | 266.27 | 1488.05 | 895.15 | 592.90 | 0.00 | 0.00 |
August | 1849.89 | 302.90 | 1480.13 | 1063.33 | 416.80 | 0.00 | 0.00 |
September | 1395.97 | 403.10 | 1151.80 | 773.66 | 378.14 | 0.00 | 0.00 |
October | 899.57 | 564.98 | 808.38 | 569.20 | 239.18 | 0.00 | 0.00 |
November | 611.59 | 607.26 | 564.02 | 399.31 | 164.71 | 0.00 | 0.00 |
December | 372.11 | 781.95 | 402.83 | 255.59 | 147.23 | 0.00 | 0.00 |
Annual Sum or Average | 1197.48 | 482.07 | 1021.39 | 675.67 | 345.72 | 0.00 | 0.00 |
Minimum of Months | 372.11 | 266.27 | 402.83 | 255.59 | 147.23 | 0.00 | 0.00 |
Maximum of Months | 2158.55 | 781.95 | 1721.36 | 1210.45 | 630.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8158.17 | 12273.99 | 1578.53 | 1126.63 | 451.90 | 0.00 | 0.00 |
February | 11922.38 | 14368.18 | 2302.97 | 1770.56 | 532.41 | 0.00 | 0.00 |
March | 16174.93 | 9060.39 | 2982.48 | 2088.44 | 894.04 | 0.00 | 0.00 |
April | 17639.90 | 6644.56 | 3223.99 | 1884.88 | 1339.11 | 0.00 | 0.00 |
May | 22770.84 | 3369.96 | 4116.04 | 2191.56 | 1924.47 | 0.00 | 0.00 |
June | 33020.84 | 3751.47 | 5150.58 | 3592.18 | 1558.40 | 0.00 | 0.00 |
July | 29591.63 | 3980.97 | 4465.21 | 2656.72 | 1808.49 | 0.00 | 0.00 |
August | 28554.10 | 4392.43 | 4441.86 | 3170.52 | 1271.34 | 0.00 | 0.00 |
September | 18694.31 | 4909.11 | 3489.21 | 2335.78 | 1153.44 | 0.00 | 0.00 |
October | 12903.05 | 7497.54 | 2494.55 | 1764.99 | 729.56 | 0.00 | 0.00 |
November | 9289.81 | 9550.54 | 1810.99 | 1308.60 | 502.39 | 0.00 | 0.00 |
December | 6420.86 | 17222.18 | 1333.06 | 883.95 | 449.10 | 0.00 | 0.00 |
Annual Sum or Average | 17958.78 | 8053.97 | 3119.15 | 2064.62 | 1054.53 | 0.00 | 0.00 |
Minimum of Months | 6420.86 | 3369.96 | 1333.06 | 883.95 | 449.10 | 0.00 | 0.00 |
Maximum of Months | 33020.84 | 17222.18 | 5150.58 | 3592.18 | 1924.47 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.627610E+09 | 0.108556E+10 | 0.693141E+09 | 0.373522E+09 | 0.319619E+09 | 0.00 | 0.00 |
February | 0.684334E+09 | 0.996861E+09 | 0.764135E+09 | 0.401941E+09 | 0.362194E+09 | 0.00 | 0.00 |
March | 0.101501E+10 | 0.806578E+09 | 0.101154E+10 | 0.460870E+09 | 0.550674E+09 | 0.00 | 0.00 |
April | 0.957130E+09 | 0.657174E+09 | 0.972051E+09 | 0.320639E+09 | 0.651413E+09 | 0.00 | 0.00 |
May | 0.148957E+10 | 0.421278E+09 | 0.126271E+10 | 0.348133E+09 | 0.914575E+09 | 0.00 | 0.00 |
June | 0.197874E+10 | 0.310993E+09 | 0.145797E+10 | 0.582595E+09 | 0.875378E+09 | 0.00 | 0.00 |
July | 0.172250E+10 | 0.313043E+09 | 0.127047E+10 | 0.370282E+09 | 0.900187E+09 | 0.00 | 0.00 |
August | 0.165938E+10 | 0.371087E+09 | 0.125114E+10 | 0.501484E+09 | 0.749656E+09 | 0.00 | 0.00 |
September | 0.133760E+10 | 0.515570E+09 | 0.106263E+10 | 0.412959E+09 | 0.649672E+09 | 0.00 | 0.00 |
October | 0.932946E+09 | 0.906812E+09 | 0.892796E+09 | 0.423425E+09 | 0.469371E+09 | 0.00 | 0.00 |
November | 0.662729E+09 | 0.965633E+09 | 0.700895E+09 | 0.358014E+09 | 0.342881E+09 | 0.00 | 0.00 |
December | 0.472070E+09 | 0.127104E+10 | 0.589884E+09 | 0.291245E+09 | 0.298638E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135396E+11 | 0.862163E+10 | 0.119294E+11 | 0.484511E+10 | 0.708426E+10 | 0.00 | 0.00 |
Minimum of Months | 0.472070E+09 | 0.310993E+09 | 0.589884E+09 | 0.291245E+09 | 0.298638E+09 | 0.00 | 0.00 |
Maximum of Months | 0.197874E+10 | 0.127104E+10 | 0.145797E+10 | 0.582595E+09 | 0.914575E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.131982E+10 | 0.181445E+10 | 0.128925E+10 | 0.892442E+09 | 0.396805E+09 | 0.00 | 0.00 |
February | 0.187538E+10 | 0.164764E+10 | 0.177320E+10 | 0.135094E+10 | 0.422262E+09 | 0.00 | 0.00 |
March | 0.292002E+10 | 0.135602E+10 | 0.261637E+10 | 0.183133E+10 | 0.785048E+09 | 0.00 | 0.00 |
April | 0.308848E+10 | 0.108517E+10 | 0.276457E+10 | 0.162665E+10 | 0.113793E+10 | 0.00 | 0.00 |
May | 0.440296E+10 | 0.813539E+09 | 0.366381E+10 | 0.197395E+10 | 0.168986E+10 | 0.00 | 0.00 |
June | 0.559497E+10 | 0.734782E+09 | 0.446175E+10 | 0.313748E+10 | 0.132427E+10 | 0.00 | 0.00 |
July | 0.499758E+10 | 0.713186E+09 | 0.398558E+10 | 0.239756E+10 | 0.158802E+10 | 0.00 | 0.00 |
August | 0.495474E+10 | 0.811297E+09 | 0.396437E+10 | 0.284802E+10 | 0.111635E+10 | 0.00 | 0.00 |
September | 0.361835E+10 | 0.104482E+10 | 0.298547E+10 | 0.200532E+10 | 0.980150E+09 | 0.00 | 0.00 |
October | 0.240941E+10 | 0.151324E+10 | 0.216516E+10 | 0.152454E+10 | 0.640622E+09 | 0.00 | 0.00 |
November | 0.158524E+10 | 0.157402E+10 | 0.146193E+10 | 0.103502E+10 | 0.426916E+09 | 0.00 | 0.00 |
December | 0.996652E+09 | 0.209437E+10 | 0.107894E+10 | 0.684584E+09 | 0.394353E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.377636E+11 | 0.152025E+11 | 0.322104E+11 | 0.213078E+11 | 0.109026E+11 | 0.00 | 0.00 |
Minimum of Months | 0.996652E+09 | 0.713186E+09 | 0.107894E+10 | 0.684584E+09 | 0.394353E+09 | 0.00 | 0.00 |
Maximum of Months | 0.559497E+10 | 0.209437E+10 | 0.446175E+10 | 0.313748E+10 | 0.168986E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.218508E+11 | 0.328746E+11 | 0.422793E+10 | 0.301757E+10 | 0.121036E+10 | 0.00 | 0.00 |
February | 0.288426E+11 | 0.347595E+11 | 0.557134E+10 | 0.428333E+10 | 0.128801E+10 | 0.00 | 0.00 |
March | 0.433229E+11 | 0.242673E+11 | 0.798827E+10 | 0.559368E+10 | 0.239460E+10 | 0.00 | 0.00 |
April | 0.457226E+11 | 0.172227E+11 | 0.835659E+10 | 0.488562E+10 | 0.347097E+10 | 0.00 | 0.00 |
May | 0.609894E+11 | 0.902610E+10 | 0.110244E+11 | 0.586988E+10 | 0.515451E+10 | 0.00 | 0.00 |
June | 0.855900E+11 | 0.972381E+10 | 0.133503E+11 | 0.931094E+10 | 0.403936E+10 | 0.00 | 0.00 |
July | 0.792582E+11 | 0.106626E+11 | 0.119596E+11 | 0.711576E+10 | 0.484386E+10 | 0.00 | 0.00 |
August | 0.764793E+11 | 0.117647E+11 | 0.118971E+11 | 0.849192E+10 | 0.340516E+10 | 0.00 | 0.00 |
September | 0.484557E+11 | 0.127244E+11 | 0.904404E+10 | 0.605433E+10 | 0.298971E+10 | 0.00 | 0.00 |
October | 0.345595E+11 | 0.200814E+11 | 0.668141E+10 | 0.472735E+10 | 0.195406E+10 | 0.00 | 0.00 |
November | 0.240792E+11 | 0.247550E+11 | 0.469408E+10 | 0.339188E+10 | 0.130220E+10 | 0.00 | 0.00 |
December | 0.171976E+11 | 0.461279E+11 | 0.357046E+10 | 0.236758E+10 | 0.120288E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.566348E+12 | 0.253990E+12 | 0.983655E+11 | 0.651098E+11 | 0.332557E+11 | 0.00 | 0.00 |
Minimum of Months | 0.171976E+11 | 0.902610E+10 | 0.357046E+10 | 0.236758E+10 | 0.120288E+10 | 0.00 | 0.00 |
Maximum of Months | 0.855900E+11 | 0.461279E+11 | 0.133503E+11 | 0.931094E+10 | 0.515451E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.988944E+09 | -901547941.9 | 0.00 | 0.00 | 744.00 | 0.00 | -87395925.5 | 58.99 | 0.00 | 0.00 |
February | 0.917417E+09 | -838401607.5 | 0.00 | 0.00 | 672.00 | 0.00 | -79015313.3 | 58.99 | 0.00 | 0.00 |
March | 0.105137E+10 | -965413516.0 | 0.00 | 0.00 | 744.00 | 0.00 | -85955176.6 | 58.99 | 0.00 | 0.00 |
April | 0.944900E+09 | -861666937.9 | 0.00 | 0.00 | 720.00 | 0.00 | -83232646.3 | 58.99 | 0.00 | 0.00 |
May | 0.926895E+09 | -846626290.0 | 0.00 | 0.00 | 744.00 | 0.00 | -80268369.6 | 58.99 | 0.00 | 0.00 |
June | 0.864137E+09 | -793589116.8 | 0.00 | 0.00 | 720.00 | 0.00 | -70548345.2 | 58.99 | 0.00 | 0.00 |
July | 0.804281E+09 | -732131711.6 | 0.00 | 0.00 | 744.00 | 0.00 | -72149412.6 | 58.99 | 0.00 | 0.00 |
August | 0.845976E+09 | -773646001.6 | 0.00 | 0.00 | 744.00 | 0.00 | -72329919.7 | 58.99 | 0.00 | 0.00 |
September | 0.804607E+09 | -733232075.1 | 0.00 | 0.00 | 720.00 | 0.00 | -71375055.4 | 58.99 | 0.00 | 0.00 |
October | 0.852843E+09 | -771061092.7 | 0.00 | 0.00 | 744.00 | 0.00 | -81782142.0 | 59.00 | 0.00 | 0.00 |
November | 0.869838E+09 | -786508554.1 | 0.00 | 0.00 | 720.00 | 0.00 | -83329685.9 | 58.99 | 0.00 | 0.00 |
December | 0.953442E+09 | -866028140.6 | 0.00 | 0.00 | 744.00 | 0.00 | -87414263.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.108246E+11 | -0.986985E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -954796255.5 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.804281E+09 | -965413516.0 | 0.00 | 0.00 | 672.00 | 0.00 | -87414263.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.105137E+10 | -732131711.6 | 0.00 | 0.00 | 744.00 | 0.00 | -70548345.2 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.96 | 0.67 | 31-JAN-11:00 | 85.12 | 0.00 | 0.00 | 0.00 | 71.18 | 0.00 | 0.00 | 0.00 |
February | 245.50 | 0.93 | 0.58 | 28-FEB-11:09 | 101.37 | 0.00 | 0.00 | 0.83 | 85.67 | 0.00 | 0.00 | 0.00 |
March | 296.17 | 0.85 | 0.50 | 06-MAR-13:09 | 148.58 | 0.00 | 0.00 | 25.33 | 955.67 | 0.00 | 0.00 | 32.83 |
April | 296.67 | 0.80 | 0.50 | 03-APR-11:00 | 202.38 | 0.00 | 0.00 | 57.83 | 159.29 | 0.00 | 0.00 | 23.67 |
May | 415.33 | 0.76 | 0.50 | 02-MAY-10:20 | 244.44 | 0.00 | 0.00 | 141.67 | 557.46 | 0.00 | 0.00 | 81.33 |
June | 421.50 | 0.79 | 0.50 | 01-JUN-11:20 | 210.16 | 0.00 | 0.00 | 84.50 | 1903.12 | 0.00 | 0.00 | 76.67 |
July | 430.33 | 0.77 | 0.50 | 02-JUL-10:09 | 233.82 | 0.00 | 0.00 | 129.17 | 1091.15 | 0.00 | 0.00 | 92.33 |
August | 394.50 | 0.82 | 0.50 | 01-AUG-10:00 | 185.97 | 0.00 | 0.00 | 51.67 | 150.07 | 0.00 | 0.00 | 30.67 |
September | 354.00 | 0.84 | 0.50 | 01-SEP-12:30 | 170.11 | 0.00 | 0.00 | 41.17 | 137.58 | 0.00 | 0.00 | 17.83 |
October | 262.67 | 0.89 | 0.58 | 01-OCT-12:30 | 132.30 | 0.00 | 0.00 | 0.33 | 110.89 | 0.00 | 0.00 | 0.00 |
November | 257.67 | 0.94 | 0.67 | 01-NOV-11:09 | 95.02 | 0.00 | 0.00 | 0.00 | 80.86 | 0.00 | 0.00 | 0.00 |
December | 251.17 | 0.96 | 0.75 | 06-DEC-10:30 | 84.54 | 0.00 | 0.00 | 0.00 | 70.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3902.00 | 0.85 | 168.44 | 0.00 | 0.00 | 532.50 | 525.35 | 0.00 | 0.00 | 355.33 | ||
Minimum of Months | 245.50 | 0.76 | 0.50 | 84.54 | 0.00 | 0.00 | 0.00 | 70.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 430.33 | 0.96 | 0.75 | 244.44 | 0.00 | 0.00 | 141.67 | 1903.12 | 0.00 | 0.00 | 92.33 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.79 | 0.50 | 02-JAN-10:30 | 145.25 | 10.00 | 0.00 | 62.33 | 688.53 | 13.65 | 4.50 | 52.17 |
February | 245.50 | 0.74 | 0.50 | 01-FEB-10:39 | 172.93 | 11.28 | 0.00 | 53.83 | 530.74 | 15.22 | 15.00 | 43.17 |
March | 296.17 | 0.65 | 0.50 | 01-MAR-10:39 | 991.38 | 15.24 | 28.67 | 209.33 | 1798.35 | 16.68 | 46.17 | 142.00 |
April | 296.67 | 0.61 | 0.50 | 03-APR-09:39 | 327.97 | 14.38 | 0.00 | 251.33 | 276.91 | 18.21 | 83.33 | 213.67 |
May | 415.33 | 0.60 | 0.50 | 01-MAY-07:40 | 2204.91 | 16.44 | 55.17 | 314.17 | 925.26 | 19.39 | 129.33 | 284.83 |
June | 421.50 | 0.61 | 0.50 | 01-JUN-06:30 | 1649.94 | 14.75 | 19.17 | 301.67 | 3310.31 | 20.56 | 120.00 | 283.50 |
July | 430.33 | 0.61 | 0.50 | 01-JUL-08:50 | 2868.06 | 15.73 | 36.67 | 315.33 | 2198.37 | 18.38 | 122.83 | 276.17 |
August | 394.50 | 0.61 | 0.50 | 01-AUG-07:19 | 991.20 | 13.93 | 0.00 | 284.33 | 1931.18 | 19.41 | 113.50 | 229.33 |
September | 354.00 | 0.64 | 0.50 | 01-SEP-09:09 | 278.25 | 13.42 | 0.00 | 230.67 | 519.33 | 18.68 | 85.33 | 203.83 |
October | 262.67 | 0.66 | 0.50 | 01-OCT-09:09 | 223.58 | 12.81 | 0.00 | 163.83 | 399.32 | 17.69 | 55.00 | 124.00 |
November | 257.67 | 0.74 | 0.50 | 01-NOV-08:00 | 163.53 | 11.05 | 0.00 | 68.67 | 370.24 | 16.60 | 30.33 | 62.33 |
December | 251.17 | 0.77 | 0.50 | 01-DEC-10:09 | 145.98 | 10.65 | 0.00 | 57.83 | 232.40 | 15.25 | 11.83 | 45.33 |
Annual Sum or Average | 3902.00 | 0.66 | 1011.28 | 13.65 | 139.67 | 2313.33 | 1246.90 | 17.81 | 817.17 | 1960.33 | ||
Minimum of Months | 245.50 | 0.60 | 0.50 | 145.25 | 10.00 | 0.00 | 53.83 | 232.40 | 13.65 | 4.50 | 43.17 | |
Maximum of Months | 430.33 | 0.79 | 0.50 | 2868.06 | 16.44 | 55.17 | 315.33 | 3310.31 | 20.56 | 129.33 | 284.83 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.85 | 0.61 | 30-JAN-15:20 | 472.51 | 23.84 | 125.17 | 53.17 | 120.26 | 20.15 | 79.33 | 0.33 |
February | 245.50 | 0.81 | 0.61 | 01-FEB-15:30 | 909.49 | 25.70 | 115.17 | 68.33 | 261.48 | 23.71 | 112.00 | 23.33 |
March | 296.17 | 0.79 | 0.61 | 01-MAR-16:10 | 544.69 | 24.80 | 163.50 | 102.00 | 454.84 | 25.23 | 176.17 | 60.83 |
April | 296.67 | 0.77 | 0.61 | 04-APR-14:09 | 471.44 | 22.90 | 172.50 | 100.17 | 530.05 | 25.02 | 219.17 | 64.83 |
May | 415.33 | 0.75 | 0.61 | 01-MAY-14:39 | 365.50 | 21.94 | 256.17 | 174.50 | 289.88 | 23.01 | 302.00 | 112.33 |
June | 421.50 | 0.75 | 0.61 | 01-JUN-14:09 | 358.37 | 22.00 | 247.67 | 162.17 | 399.89 | 23.28 | 325.33 | 115.00 |
July | 430.33 | 0.76 | 0.61 | 01-JUL-15:30 | 355.71 | 21.89 | 254.67 | 168.67 | 327.46 | 23.06 | 316.83 | 104.83 |
August | 394.50 | 0.78 | 0.61 | 01-AUG-14:00 | 325.47 | 21.90 | 214.67 | 115.67 | 343.91 | 23.27 | 289.00 | 78.33 |
September | 354.00 | 0.78 | 0.61 | 01-SEP-13:39 | 355.68 | 23.06 | 205.67 | 124.50 | 390.05 | 25.07 | 237.67 | 82.50 |
October | 262.67 | 0.79 | 0.61 | 01-OCT-13:00 | 636.68 | 24.98 | 157.83 | 78.83 | 211.49 | 23.14 | 187.83 | 30.00 |
November | 257.67 | 0.83 | 0.61 | 01-NOV-14:20 | 412.61 | 24.63 | 130.83 | 54.00 | 138.88 | 21.11 | 107.17 | 1.50 |
December | 251.17 | 0.85 | 0.64 | 05-DEC-15:20 | 331.67 | 23.99 | 124.50 | 39.17 | 121.64 | 20.62 | 75.83 | 0.00 |
Annual Sum or Average | 3902.00 | 0.79 | 441.36 | 23.21 | 2168.33 | 1241.17 | 311.35 | 23.15 | 2428.33 | 673.83 | ||
Minimum of Months | 245.50 | 0.75 | 0.61 | 325.47 | 21.89 | 115.17 | 39.17 | 120.26 | 20.15 | 75.83 | 0.00 | |
Maximum of Months | 430.33 | 0.85 | 0.64 | 909.49 | 25.70 | 256.17 | 174.50 | 530.05 | 25.23 | 325.33 | 115.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.534898E+10 | 27006.34 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.581737E+10 | 27006.34 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.470926E+10 | 27006.34 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.340896E+10 | 27006.34 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.688751E+09 | 27006.34 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20641628.72 | 6207.27 | 22-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193990E+10 | 27006.34 | 04-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.370836E+10 | 27006.34 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.651501E+10 | 27006.34 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.321572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.651501E+10 | 27006.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173542E+11 | 76751.89 | 01-JAN-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195170E+11 | 76751.89 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132104E+11 | 76751.89 | 02-MAR-03:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.879868E+10 | 76751.89 | 02-APR-03:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.757820E+09 | 49432.65 | 03-MAY-03:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.529255E+10 | 76751.89 | 24-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109034E+11 | 76751.89 | 01-NOV-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.255885E+11 | 76751.89 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101422E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.255885E+11 | 76751.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.420358E+11 | 80650.83 | 05-JAN-19:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.562506E+11 | 108426.02 | 12-FEB-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261960E+11 | 119469.87 | 19-MAR-06:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130060E+11 | 56509.33 | 17-APR-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 60736.81 | 111.67 | 03-MAY-03:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.888243E+10 | 65534.62 | 31-OCT-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.239536E+11 | 101122.61 | 30-NOV-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.870783E+11 | 131231.96 | 21-DEC-17:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.257403E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.870783E+11 | 131231.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 7220035.95 | 7220035.95 | 733.24 | 13-MAR-16:00 | 733.24 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.540879E+09 | 0.537206E+09 | 4860.34 | 31-MAY-16:00 | 4643.13 | 0.00 |
June | 0.00 | 0.00 | 0.560240E+10 | 0.529919E+10 | 19985.88 | 22-JUN-05:03 | 12654.87 | 0.00 |
July | 0.00 | 0.00 | 0.600892E+10 | 0.552781E+10 | 21336.04 | 28-JUL-05:03 | 11441.34 | 0.00 |
August | 0.00 | 0.00 | 0.593938E+10 | 0.559717E+10 | 21526.64 | 04-AUG-05:02 | 10942.53 | 0.00 |
September | 0.00 | 0.00 | 0.370156E+10 | 0.364531E+10 | 18986.09 | 13-SEP-05:01 | 18174.81 | 0.00 |
October | 0.00 | 0.00 | 0.216956E+09 | 0.216956E+09 | 4753.21 | 11-OCT-15:10 | 4753.21 | 0.00 |
November | 0.00 | 0.00 | 196.74 | 196.74 | 0.26 | 07-NOV-14:20 | 0.26 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.220173E+11 | 0.208309E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.600892E+10 | 0.559717E+10 | 21526.64 | 18174.81 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.785492E+10 | 0.770408E+10 | 53284.58 | 18-JUN-09:55 | 37376.85 | 0.00 |
July | 0.00 | 0.00 | 0.868071E+10 | 0.849625E+10 | 55012.36 | 30-JUL-11:25 | 34724.20 | 0.00 |
August | 0.00 | 0.00 | 0.816800E+10 | 0.804539E+10 | 49085.00 | 27-AUG-11:55 | 44194.20 | 0.00 |
September | 0.00 | 0.00 | 0.289217E+10 | 0.288801E+10 | 47485.17 | 03-SEP-16:45 | 47485.17 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.275958E+11 | 0.271337E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.868071E+10 | 0.849625E+10 | 55012.36 | 47485.17 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.537019E+09 | 0.05 | 367.00 | 01-JAN-00:05 | 0.09 |
February | 0.530277E+09 | 0.06 | 367.00 | 01-FEB-00:03 | 0.09 |
March | 0.382707E+09 | 0.04 | 367.00 | 01-MAR-00:10 | 0.09 |
April | 0.186436E+09 | 0.02 | 367.00 | 01-APR-19:07 | 0.09 |
May | 366999.31 | 0.00 | 367.00 | 03-MAY-03:47 | 0.09 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 94025224.20 | 0.01 | 367.00 | 25-OCT-04:00 | 0.09 |
November | 0.320178E+09 | 0.03 | 367.00 | 01-NOV-00:10 | 0.09 |
December | 0.688197E+09 | 0.07 | 367.00 | 01-DEC-00:03 | 0.09 |
Annual Sum or Average | 0.273921E+10 | 0.02 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.688197E+09 | 0.07 | 367.00 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.732243E+09 | 0.42 | 1373.73 | 02-JAN-06:01 | 1.12 |
February | 0.708958E+09 | 0.48 | 1373.73 | 01-FEB-06:01 | 1.12 |
March | 0.755375E+09 | 0.42 | 1373.73 | 01-MAR-06:01 | 1.12 |
April | 0.667279E+09 | 0.38 | 1373.73 | 01-APR-05:01 | 1.12 |
May | 0.591651E+09 | 0.28 | 1373.73 | 01-MAY-05:01 | 1.12 |
June | 0.580473E+09 | 0.28 | 1373.73 | 14-JUN-05:02 | 1.12 |
July | 0.556957E+09 | 0.26 | 1373.73 | 01-JUL-05:02 | 1.12 |
August | 0.606781E+09 | 0.28 | 1373.73 | 03-AUG-05:02 | 1.11 |
September | 0.550203E+09 | 0.26 | 1373.73 | 11-SEP-05:01 | 1.12 |
October | 0.611593E+09 | 0.31 | 1373.73 | 04-OCT-05:02 | 1.12 |
November | 0.650456E+09 | 0.33 | 1373.73 | 01-NOV-05:01 | 1.12 |
December | 0.776800E+09 | 0.46 | 1373.73 | 01-DEC-06:01 | 1.12 |
Annual Sum or Average | 0.778877E+10 | 0.35 | |||
Minimum of Months | 0.550203E+09 | 0.26 | 1373.73 | 1.11 | |
Maximum of Months | 0.776800E+09 | 0.48 | 1373.73 | 1.12 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.167297E+10 | 0.64 | 2798.72 | 01-JAN-06:53 | 1.08 |
February | 0.165562E+10 | 0.66 | 2798.72 | 01-FEB-06:01 | 1.08 |
March | 0.162633E+10 | 0.54 | 2798.72 | 02-MAR-03:23 | 1.08 |
April | 0.140278E+10 | 0.49 | 2798.72 | 02-APR-03:53 | 1.08 |
May | 0.117897E+10 | 0.28 | 1802.54 | 03-MAY-03:13 | 1.08 |
June | 0.121715E+10 | 0.29 | 2798.72 | 25-JUN-12:33 | 1.08 |
July | 0.119330E+10 | 0.28 | 2798.72 | 09-JUL-13:43 | 1.08 |
August | 0.124417E+10 | 0.28 | 2798.72 | 10-AUG-17:08 | 1.08 |
September | 0.112744E+10 | 0.26 | 2798.72 | 10-SEP-14:43 | 1.08 |
October | 0.127262E+10 | 0.35 | 2798.72 | 24-OCT-05:01 | 1.08 |
November | 0.141451E+10 | 0.53 | 2798.72 | 01-NOV-00:22 | 1.08 |
December | 0.192163E+10 | 0.68 | 2798.72 | 06-DEC-06:01 | 1.08 |
Annual Sum or Average | 0.169275E+11 | 0.44 | |||
Minimum of Months | 0.112744E+10 | 0.26 | 1802.54 | 1.08 | |
Maximum of Months | 0.192163E+10 | 0.68 | 2798.72 | 1.08 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.732243E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.708958E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.757213E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.667279E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.728663E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.200096E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.205496E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.209001E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.145893E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.665045E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.650456E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.776800E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.132915E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.650456E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.209001E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.167297E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.165562E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.162633E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.140278E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.117897E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.337324E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.354700E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.344056E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.190327E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.127262E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.141451E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.192163E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.244095E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.117897E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.354700E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.732243E+09 | 0.00 | 0.534898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.708958E+09 | 0.00 | 0.581737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.755375E+09 | 7220035.95 | 0.470926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.667279E+09 | 0.00 | 0.340896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.591651E+09 | 0.540879E+09 | 0.688751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.580473E+09 | 0.558158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.556957E+09 | 0.598047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.606781E+09 | 0.591996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.550203E+09 | 0.369202E+10 | 20641628.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.611593E+09 | 0.216956E+09 | 0.193990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.650456E+09 | 196.74 | 0.370836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.776800E+09 | 0.00 | 0.651501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.778877E+10 | 0.219391E+11 | 0.321572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.550203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.776800E+09 | 0.598047E+10 | 0.651501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.167297E+10 | 0.00 | 0.173542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165562E+10 | 0.00 | 0.195170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162633E+10 | 0.00 | 0.132104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140278E+10 | 0.00 | 0.879868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117897E+10 | 0.00 | 0.757820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121715E+10 | 0.775223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119330E+10 | 0.858304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124417E+10 | 0.805562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112744E+10 | 0.284906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127262E+10 | 0.00 | 0.529255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141451E+10 | 0.00 | 0.109034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192163E+10 | 0.00 | 0.255885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169275E+11 | 0.272400E+11 | 0.101422E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.112744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.192163E+10 | 0.858304E+10 | 0.255885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.732243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.708958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.755375E+09 | 0.00 | 0.00 | 0.00 | 1837439.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.667279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.591651E+09 | 0.00 | 0.00 | 0.00 | 0.137012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.580473E+09 | 0.00 | 0.00 | 0.00 | 0.142049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.556957E+09 | 0.00 | 0.00 | 0.00 | 0.149800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.606781E+09 | 0.00 | 0.00 | 0.00 | 0.148323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.550203E+09 | 0.00 | 0.00 | 0.00 | 0.908724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.611593E+09 | 0.00 | 0.00 | 0.00 | 53452166.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.650456E+09 | 0.00 | 0.00 | 0.00 | 50.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.776800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.778877E+10 | 0.00 | 0.00 | 0.00 | 0.550275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.550203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.776800E+09 | 0.00 | 0.00 | 0.00 | 0.149800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.167297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121715E+10 | 0.00 | 0.00 | 0.00 | 0.215609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119330E+10 | 0.00 | 0.00 | 0.00 | 0.235370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124417E+10 | 0.00 | 0.00 | 0.00 | 0.219638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112744E+10 | 0.00 | 0.00 | 0.00 | 0.775824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169275E+11 | 0.00 | 0.00 | 0.00 | 0.748200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.112744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.192163E+10 | 0.00 | 0.00 | 0.00 | 0.235370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164471E+10 | 0.00 | 0.00 | 0.12 |
February | 73619327.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163589E+10 | 0.00 | 0.00 | 0.13 |
March | 0.271847E+09 | 0.00 | 0.00 | 29871.56 | 0.00 | 0.130145E+10 | 56520588.35 | 0.00 | 0.15 |
April | 0.293159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100285E+10 | 0.00 | 0.00 | 0.13 |
May | 0.421453E+09 | 2084551.33 | 0.00 | 939022.86 | 0.00 | 0.129007E+09 | 0.624671E+09 | 0.00 | 0.25 |
June | 4334420.71 | 0.192641E+09 | 0.00 | 3922483.70 | 0.00 | 0.00 | 0.743342E+09 | 0.00 | 0.36 |
July | 1979634.04 | 0.235280E+09 | 0.00 | 4291454.00 | 0.00 | 0.00 | 0.511502E+09 | 0.00 | 0.33 |
August | 1780047.09 | 0.172206E+09 | 0.00 | 5961607.95 | 0.00 | 0.00 | 0.110875E+10 | 0.00 | 0.39 |
September | 67130895.13 | 24020951.07 | 0.00 | 5082773.86 | 0.00 | 6305583.92 | 0.126452E+10 | 0.00 | 0.42 |
October | 0.566827E+09 | 0.00 | 0.00 | 752001.12 | 0.00 | 0.564310E+09 | 0.585061E+09 | 0.00 | 0.20 |
November | 0.325048E+09 | 0.00 | 0.00 | 9138.27 | 0.00 | 0.122049E+10 | 31551220.04 | 0.00 | 0.13 |
December | 0.116121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184620E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.227684E+10 | 0.626232E+09 | 0.00 | 20988353.32 | 0.00 | 0.935120E+10 | 0.492592E+10 | 0.00 | 0.23 |
Minimum of Months | 1780047.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.566827E+09 | 0.235280E+09 | 0.00 | 5961607.95 | 0.00 | 0.184620E+10 | 0.126452E+10 | 0.00 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.252450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243510E+10 | 0.00 | 0.00 | 0.17 |
February | 0.242535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241165E+10 | 0.00 | 0.00 | 0.18 |
March | 0.236437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192415E+10 | 0.00 | 0.00 | 0.19 |
April | 0.252425E+10 | 0.00 | 0.00 | 0.00 | 129098.75 | 0.807075E+09 | 0.00 | 0.00 | 0.18 |
May | 0.236335E+10 | 0.00 | 0.00 | 0.00 | 5264954.46 | 25308560.44 | 0.00 | 0.00 | 0.18 |
June | 0.659253E+09 | 0.254877E+09 | 0.00 | 6319501.18 | 7592.17 | 0.00 | 0.143431E+10 | 0.00 | 0.28 |
July | 0.385285E+09 | 0.201650E+09 | 0.00 | 7238741.05 | 0.00 | 0.00 | 0.149962E+10 | 0.00 | 0.28 |
August | 0.668044E+09 | 0.199611E+09 | 0.00 | 9024905.11 | 0.00 | 0.00 | 0.225072E+10 | 0.00 | 0.29 |
September | 0.141721E+10 | 6110970.00 | 0.00 | 4006132.24 | 859999.26 | 0.00 | 0.141177E+10 | 0.00 | 0.25 |
October | 0.319120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996875E+09 | 0.00 | 0.00 | 0.17 |
November | 0.267642E+10 | 0.00 | 0.00 | 0.00 | 7271.88 | 0.166651E+10 | 0.00 | 0.00 | 0.17 |
December | 0.180070E+10 | 0.00 | 0.00 | 0.00 | 2234832.20 | 0.387608E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.229999E+11 | 0.662249E+09 | 0.00 | 26589279.58 | 8503748.71 | 0.141427E+11 | 0.659641E+10 | 0.00 | 0.21 |
Minimum of Months | 0.385285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.319120E+10 | 0.254877E+09 | 0.00 | 9024905.11 | 5264954.46 | 0.387608E+10 | 0.225072E+10 | 0.00 | 0.29 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.515407E+12 | 0.301649E+11 | 0.00 | 0.673785E+10 | 0.208820E+11 |
February | 0.664028E+12 | 0.494873E+11 | 0.00 | 0.654651E+10 | 0.254843E+11 |
March | 0.842770E+12 | 0.497332E+11 | 0.00 | 0.591837E+10 | 0.147745E+11 |
April | 0.873067E+12 | 0.441147E+11 | 0.00 | 0.462720E+10 | 0.886711E+10 |
May | 0.109422E+13 | 0.277121E+11 | 0.00 | 0.355738E+10 | 0.136611E+10 |
June | 0.121141E+13 | 0.260523E+11 | 0.00 | 0.241349E+10 | 0.170339E+11 |
July | 0.112075E+13 | 0.360049E+11 | 0.00 | 0.197542E+10 | 0.185413E+11 |
August | 0.111790E+13 | 0.353411E+11 | 0.00 | 0.368326E+10 | 0.177870E+11 |
September | 0.827701E+12 | 0.352562E+11 | 0.00 | 0.416022E+10 | 0.828910E+10 |
October | 0.671168E+12 | 0.463043E+11 | 0.00 | 0.590503E+10 | 0.581241E+10 |
November | 0.554431E+12 | 0.350361E+11 | 0.00 | 0.592002E+10 | 0.127990E+11 |
December | 0.400099E+12 | 0.703317E+11 | 0.00 | 0.763686E+10 | 0.358260E+11 |
Annual Sum or Average | 0.989294E+13 | 0.485539E+12 | 0.00 | 0.590816E+11 | 0.187463E+12 |
Minimum of Months | 0.400099E+12 | 0.260523E+11 | 0.00 | 0.197542E+10 | 0.136611E+10 |
Maximum of Months | 0.121141E+13 | 0.703317E+11 | 0.00 | 0.763686E+10 | 0.358260E+11 |