Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 10:42:37
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 440.68 | 91.14 | 91.14 |
Net Site Energy | 440.68 | 91.14 | 91.14 |
Total Source Energy | 1317.59 | 272.50 | 272.50 |
Net Source Energy | 1317.59 | 272.50 | 272.50 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 37.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 44.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 97.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 403.21 | 37.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 37.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 44.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 97.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 12.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 26.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 37.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 44.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 97.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 38.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 24.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 32.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 22.24 | 7.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 83.39 | 7.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 32.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 22.24 | 7.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 83.39 | 7.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 403.214 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 403.214 | 100.00 |
Total On-Site and Utility Electric Sources | 403.214 | 100.00 |
Total Electricity End Uses | 403.214 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 35.17 |
Time Setpoint Not Met During Occupied Cooling | 19.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2939.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 113.33 |
Skylight-Roof Ratio [%] | 2.46 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 9.3385 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.7674 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 5.0950 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 5.0950 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 9.3385 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.7674 | 46.45 | 2.5587 | |
Total | 4835.13 | 5.0950 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 5.0950 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 5.0950 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUN-15:00 | 27-DEC-06:30 | - | - | - | - | - | - | - | - | - | - | 29-JUN-11:20 |
Heating | 0.00 | 75706.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15177.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6803.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5280.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1150.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 38447.39 | 75706.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 75706.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 15177.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 6803.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2975.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1150.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 40.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 140.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 308.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 195.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 122.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 76.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1276.98 | 40.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 29.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 63.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 264.10 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 29.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 63.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 264.10 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.32 |
ZONE2 FINE STORAGE DIRECT AIR | 3.25 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 2.47 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 2.47 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 87824.80 |
PSZ-OFFICE HEATING COIL | 29069.09 |
PSZ-FINE STORAGE HEATING COIL | 92653.88 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 87824.80 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.32 | 1.32 | 1.32 | 1.32 | 1.32 | 1.32 | 1.00 | 1.00 | 1.32 |
PSZ-FINE STORAGE | 3.25 | 3.25 | 3.25 | 3.25 | 3.25 | 3.25 | 1.00 | 1.000000 | 3.25 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.32 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.25 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.32 | 1461.61 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.25 | 3479.26 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.32 | 1.32 | 1.32 | 0.871295 | 22540.17 | 29069.09 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.25 | 3.25 | 3.25 | 2.15 | 67410.51 | 92653.88 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.32 | 0.660072 | 0.880093 | 22540.17 | 11270.08 | 0.800450 | 0.800450 |
PSZ-FINE STORAGE COOLING COIL | 3.25 | 1.63 | 2.17 | 67410.51 | 33705.25 | 0.762550 | 0.762550 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 9.339 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 17.412 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.767 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.326 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2212.108 | 9.339 | 173.516 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2212.108 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 12073.795 | 3.767 | 174.983 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 12073.795 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5892 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.044 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.697 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4892 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.53319589E-11 | 0.95168195E-16 | 0.18684196E-15 | 0.0000000 |
5 | 1 | -5.2159738 | 0.43009049E-04 | -0.27188221E-04 | 0.68723469E-11 |
6 | 0 | 5.8052090 | 0.58919217 | 0.58926237 | |
7 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
8 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
9 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
10 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
11 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
12 | 4 | 0.65556131E-12 | 0.57298371E-15 | -0.14028959E-14 | 0.12439065E-15 |
13 | 3 | -0.34087882E-03 | 0.75102955E-06 | -0.49042705E-04 | 0.12583838E-12 |
14 | 2 | 1.6337693 | 0.17263784E-01 | 1.0601096 | -0.65347397E-04 |
15 | 1 | -7.2734424 | 0.46143774 | -16.581274 | 0.31301327 |
16 | 0 | 6.4190060 | 0.30028979 | 16.300205 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.0441747 | 2.0441747 | 2.0441747 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.14028959E-14 | 0.57298371E-15 | 0.65556131E-12 | 0.12439065E-15 |
85 | 3 | -0.49042705E-04 | 0.75102955E-06 | -0.34087882E-03 | 0.12583838E-12 |
86 | 2 | 1.0601096 | 0.17263784E-01 | 1.6337693 | -0.65347397E-04 |
87 | 1 | -16.581274 | 0.46143774 | -7.2734424 | 0.31301327 |
88 | 0 | 16.300205 | 0.30028979 | 6.4190060 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.449_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 2.552 | 2.552 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.449_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 2.552 | 2.552 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.449_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 2.552 | 2.552 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.449_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.552 | 2.552 | 1.000 | 0.251 | ||
5 | SKYLIGHT_U_0.55_SHGC_0.35 | 38 | 1 | VerySmooth | 3.127 | 3.127 | 1.000 | 0.351 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.67979E-002 | 0.16139 | 0.61739 | 0.61739 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12139 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.67979E-002 | 0.16139 | 0.61739 | 0.61739 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12139 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.67979E-002 | 0.16139 | 0.61739 | 0.61739 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12139 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.67979E-002 | 0.16139 | 0.61739 | 0.61739 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12139 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.15759E-002 | 0.26293 | 0.50711 | 0.50711 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 7.71143E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.55_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.043 | 0.356 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.767 | 0.405 | 0.231 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3341E-005 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8427E-004 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4611E-005 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2925E-004 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4040E-005 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7892E-004 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5724E-005 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5867E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5484E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.3285E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3077E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.6864E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4666E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8721E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3414E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4540E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5692E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4753E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0013E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6104E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.4522E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1879E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8792E-004 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6675E-005 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1589E-004 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.3584E-005 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5423E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8442E-005 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0576E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2691E-005 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3392E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0724E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4913E-004 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1872E-005 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8300E-004 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3868E-005 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.1517E-004 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8938E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9718E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6272E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.9812E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.3744E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.3992E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4728E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5889E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4205E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7955E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4789E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.9538E-004 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4672E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1905E-003 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5847E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2950E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4546E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3679E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4861E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1435E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4861E-005 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4565E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.7502E-005 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0387E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0072E-005 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1133E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6508E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7041E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.5456E-005 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6235E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0302E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3861E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7361E-005 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5808E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1684E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8263E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0917E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.8537E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3765E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.0827E-004 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4397E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6286E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1734E-005 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9657E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.4211E-004 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6275E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8279E-004 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8305E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.6538E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3102E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8162E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.1530E-005 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9823E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0686E-005 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3170E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.9140E-005 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6786E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0760E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8446E-004 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2334E-005 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9575E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8585E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9569E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8357E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6227E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7398E-005 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1825E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0430E-005 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7351E-004 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7195E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2847E-004 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7443E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1312E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5431E-005 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2422E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2552E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8759E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8315E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0282E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7180E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6531E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6118E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8985E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8335E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3113E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5005E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1182E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2453E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9640E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8273E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8634E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7342E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9321E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9352E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2106E-004 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2008E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3185E-004 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3504E-004 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7657E-005 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6131E-005 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5360E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8990E-005 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9579E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9400E-005 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5683E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8788E-005 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3577E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2311E-005 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3243E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0454E-005 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3948E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0169E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2358E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3062E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2854E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3712E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0182E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1240E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1269E-004 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1417E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1056E-003 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1585E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1808E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7724E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1979E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4960E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3722E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6671E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0486E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0709E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5443E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8810E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4585E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7586E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7767E-005 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1673E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5843E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1950E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5045E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1818E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6897E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0181E-003 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7009E-005 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1438E-003 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.3275E-005 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0144E-003 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8057E-005 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6709E-004 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4805E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0786E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5788E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8980E-004 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1606E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5697E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7453E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5316E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6098E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9006E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9288E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5183E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9357E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4703E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2875E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8592E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5559E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6705E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7716E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5248E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5927E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2768E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9744E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1132E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9594E-005 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1044E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2827E-005 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5304E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5900E-005 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0851E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8131E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0703E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5633E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5024E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5625E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6340E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8889E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4836E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9464E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2286E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4314E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3444E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6471E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1675E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4553E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7312E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7783E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3323E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4458E-004 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1535E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2688E-004 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6995E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1149E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9494E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0775E-005 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1084E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3190E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1991E-004 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.1275E-005 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9062E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6623E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0594E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2858E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0926E-004 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7161E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0677E-005 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8720E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7409E-005 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3264E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5165E-005 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0566E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3789E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4517E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9372E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2082E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5588E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5865E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6040E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6237E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8299E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3627E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5116E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3524E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0705E-005 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4234E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7605E-005 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2495E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6498E-005 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4523E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9716E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1410E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1860E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3000E-005 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3800E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5914E-005 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0355E-004 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8644E-005 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5043E-005 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6335E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7874E-005 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9552E-005 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9568E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1773E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1823E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0385E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4264E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1475E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3776E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6822E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9388E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0591E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5809E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8239E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0336E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4529E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4969E-005 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0280E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8327E-005 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1896E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
369 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.8143E-003 |
370 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.5337E-004 |
371 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.4014E-003 |
372 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.1073E-004 |
373 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.2287E-003 |
374 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.9464E-004 |
375 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.9731E-003 |
376 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.4928E-004 |
377 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.5956E-004 |
378 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.1366E-003 |
379 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.2478E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.4790E-003 |
381 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.0269E-004 |
382 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.4264E-003 |
383 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.4525E-004 |
384 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.6476E-003 |
385 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.3319E-003 |
386 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.4266E-004 |
387 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.4935E-003 |
388 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9195E-004 |
389 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.6296E-003 |
390 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.4596E-004 |
391 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.4770E-003 |
392 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.1257E-004 |
393 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.3477E-003 |
394 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.4273E-004 |
395 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.5005E-003 |
396 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9198E-004 |
397 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.6096E-003 |
398 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.4592E-004 |
399 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.4769E-003 |
400 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1257E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11597.07076 | 13916.48491 | 1.10012 | 1.32014 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 37.14667 | 6.86994E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8374.19450 | 10049.03340 | 0.27096 | 0.32516 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20000 | 2.80840E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 36643.56172 | 43972.27407 | 2.70958 | 3.25150 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10000 | 6.87148E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 22923.32386 | 27507.98864 | 0.62497 | 0.74997 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -5.20000 | 2.80840E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 73187.33699 | 87824.80438 | 2.06188 | 2.47425 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 17920.92 | 1.32014 | 1.32014 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9283.53 | 0.32516 | 0.32516 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 55237.30 | 3.25150 | 3.25150 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 28488.42 | 0.74997 | 0.74997 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.32014 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.25150 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.47425 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 2.47425 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 87824.79926 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 87824.80438 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.32014 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.32014 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.32014 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.32014 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.32014 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.32014 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.25150 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.25150 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.25150 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.25150 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.25150 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.25150 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.32014 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.25150 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.32014 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.32014 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1461.60886 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.32014 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.32014 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.32014 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.87129 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.32014 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.66007 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.88009 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22540.17000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11270.08500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80045 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80045 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22540.17000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29069.09017 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29069.09017 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.25150 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.25150 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3479.25861 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.25150 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.25150 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.25150 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.14599 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.25150 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.62575 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.16767 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 67410.51000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 33705.25500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76255 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76255 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 67410.51000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 92653.87645 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 92653.87645 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 21515.7 | 11.47 | 11.21 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 64885.3 | 11.73 | 11.46 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.9331899743E-002 | 3.2149456062E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 6.1558076328E-002 | 5.1688857505E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 6.2674294258E-002 | 5.1808578704E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 11313.57 | 446.38 | 0.00 | 31.20 | 228.54 | 12019.76 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.545 | 0.589 | 3204.84 | 3112.33 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.449_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.552 | 0.251 | 0.276 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.449_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.552 | 0.251 | 0.276 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.449_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.552 | 0.251 | 0.276 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.449_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.552 | 0.251 | 0.276 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.55_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.351 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.356 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.55_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.351 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.356 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.55_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.351 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.356 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.55_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.351 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.356 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.55_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.351 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.356 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.55_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.351 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.356 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.55_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.351 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.356 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.55_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.351 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.356 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.55_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.351 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.356 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.55_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.351 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.356 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.55_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.351 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.356 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.55_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.351 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.356 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.55_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.351 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.356 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.55_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.351 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.356 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.40 | 0.00 | 2.89 | 2.89 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.767 | 0.405 | 0.231 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 130.99 | 4.936 | 0.479 | 0.384 | |||||||||||||||||
North Total or Average | 6.51 | 2.552 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 124.48 | 5.061 | 0.490 | 0.390 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 9.3385 | 236.88 | 2212.11 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 34.11 | 0.0000 | Y | 14.16 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 20.88 | 0.0000 | Y | 40.57 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.7674 | 3204.84 | 12073.79 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 18.86 | 0.0000 | Y | 42.75 |
Interior Lighting Total | 5.0950 | 4835.13 | 24634.88 | 97.48 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10348.98 | 2587.24 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10348.98 | 2587.24 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 12073.79 | 3018.45 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 12073.79 | 3018.45 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.29 | 2212.11 | 641.51 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.10 | 2212.11 | 221.21 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 41.77 | 41.77 | 0.97 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.77 | 62.77 | 50.73 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.77 | 48.79 | 10.00 | |
Exterior Lighting Total | 5520.82 | 61.70 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22540.17 | 18042.28 | 4497.89 | 0.80 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 67410.51 | 51403.88 | 16006.63 | 0.76 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 21515.7 | 11.47 | 11.21 | ||||
PSZ-FINE STORAGE COOLING COIL | 64885.3 | 11.73 | 11.46 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 87824.80 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29069.09 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 92653.88 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.47 | 229.88 | 92.91 | 1.00 | 3.46 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.32 | 1461.61 | 1107.16 | 1.00 | 1.34 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 3.25 | 3479.26 | 1070.05 | 1.00 | 1.26 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11597.07 | 13916.48 | 58.75 | 1.100 | 1.320 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 23.90 | 23.90 | 0.00822 | 37.15 | 0.00687 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 36643.56 | 43972.27 | 31.56 | 2.710 | 3.251 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00818 | 38.10 | 0.00687 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 37.68 | 0.00696 | 37.97 | 0.00687 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8374.19 | 10049.03 | 42.42 | 0.271 | 0.325 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00791 | -5.20 | 0.00281 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 22923.32 | 27507.99 | 19.74 | 0.625 | 0.750 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00686 | -5.20 | 0.00281 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 73187.34 | 87824.80 | 27.40 | 2.062 | 2.474 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00624 | -5.20 | 0.00281 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.32 | 1.32 | 0.33 | 0.33 | 1.3201 | 1.3201 | 1.3201 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.25 | 3.25 | 0.75 | 0.75 | 3.2515 | 3.2515 | 3.2515 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 87824.799 | 87824.799 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 87824.80 | 87824.80 | 2.474254 | 10.00 | 7.32 | 0.00623628 | 43.33 | 20.46 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 10.00 | 0.00623628 | 71.0371 | 87824.80 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 22540.170 | 18042.279 | 1.320140 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 11270.08 | 11087.00 | 0.880093 | 25.98 | 15.28 | 0.00811494 | 12.00 | 10.01 | 0.00800000 | 37.32 | 0.00687023 | 17.93 | 11.6220 | 23.90 | 0.00821951 | 38.6240 | 11594.13 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29069.090 | 29069.090 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 29069.09 | 29069.09 | 1.320144 | 19.02 | 12.29 | 0.00751306 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 7.7480 | 21.10 | 0.00790819 | 44.0743 | 8374.19 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 67410.510 | 51403.884 | 3.251500 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33705.25 | 33658.82 | 2.167667 | 29.19 | 16.26 | 0.00801135 | 12.00 | 10.01 | 0.00800000 | 38.10 | 0.00687148 | 18.17 | 19.5930 | 26.70 | 0.00818261 | 32.5531 | 36643.56 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 92653.876 | 92653.876 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 92653.88 | 92653.88 | 3.251500 | 12.85 | 8.67 | 0.00633372 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 13.0620 | 15.56 | 0.00686338 | 54.2532 | 22923.32 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 87824.799 | 87824.799 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 2.474254 | 2.58394241 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 87824.80 | 87824.80 | 1.0000 | 2.58394241 | 2.474254 | 10.00 | 7.32 | 0.00623628 | 25759.2 | 43.33 | 20.46 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87824.80 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 10.00 | 0.00623628 | 10.00 | 0.00623628 | 71.0371 | 87824.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22540.170 | 18042.279 | 1.320140 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9253 | 1004.8586 | 1.0443 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.320144 | 1.37866817 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | Sensible | 11270.08 | 11087.00 | 1.0000 | 0.91910939 | 0.880093 | 25.98 | 15.28 | 0.00811494 | 46791.2 | 12.00 | 10.01 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11270.08 | 37.32 | 0.00687023 | 17.93 | 0.10228463 | 11.6220 | 23.90 | 0.00821951 | 23.90 | 0.00821951 | 38.6240 | 11594.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29069.090 | 29069.090 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.320144 | 1.37866817 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 29069.09 | 29069.09 | 1.0000 | 1.37866817 | 1.320144 | 19.02 | 12.29 | 0.00751306 | 38164.4 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29069.09 | -5.20 | 0.00280840 | -5.20 | 0.10228463 | 7.7480 | 21.05 | 0.00790819 | 21.10 | 0.00790819 | 44.0743 | 8374.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 67410.510 | 51403.884 | 3.251500 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7327 | 1004.8586 | 1.0443 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.251500 | 3.39564453 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 33705.25 | 33658.82 | 1.0000 | 2.26376308 | 2.167667 | 29.19 | 16.26 | 0.00801135 | 49805.2 | 12.00 | 10.01 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33705.25 | 38.10 | 0.00687148 | 18.17 | 0.42471127 | 19.5930 | 26.70 | 0.00818261 | 26.70 | 0.00818261 | 32.5531 | 36643.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 92653.876 | 92653.876 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.251500 | 3.39564453 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 92653.88 | 92653.88 | 1.0000 | 3.39564453 | 3.251500 | 12.85 | 8.67 | 0.00633372 | 28899.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92653.88 | -5.20 | 0.00280840 | -5.20 | 0.42471127 | 13.0620 | 15.56 | 0.00686338 | 15.56 | 0.00686338 | 54.2532 | 22923.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.32 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 3.25 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2418.00 | 1916.00 | 1007.67 |
ZONE2 FINE STORAGE | 3070.83 | 2916.83 | 2433.83 |
ZONE3 BULK STORAGE | 3214.33 | 3287.83 | 2933.00 |
Facility | 3253.17 | 3447.67 | 2939.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 28.83 | 19.33 | 28.83 | 19.17 |
ZONE2 FINE STORAGE | 62.67 | 120.67 | 9.33 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 88.50 | 140.00 | 35.17 | 19.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.683 | 0.292 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.624 | 0.220 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.116 | 0.000 | 0.941 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.54 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2465643.33 | 0.00 | 2465643.33 | 1717458.42 | 4183101.75 | 3225648.14 | 5604.39 | 2298.67 | 856.94 | 0.16 |
ZONE2 FINE STORAGE | 6767209.85 | 0.00 | 6767209.85 | 6171176.23 | 12938386.07 | 13393694.68 | 5638.92 | 2525.83 | 595.25 | 37.83 |
ZONE3 BULK STORAGE | 0.00 | 0.21E+09 | 0.21E+09 | 30267012.76 | 0.24E+09 | 30805497.77 | 6666.67 | 30.08 | 2063.24 | 4863.53 |
Total Facility | 9232853.18 | 0.21E+09 | 0.22E+09 | 38155647.40 | 0.26E+09 | 47424840.58 | 7640.15 | 2816.64 | 3074.96 | 4864.57 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1883 | 0.0000 | 0.1883 | 0.0806 | 0.2689 | 0.1023 | 480.55 | 2298.67 | 856.78 |
ZONE2 FINE STORAGE | 0.5015 | 0.0000 | 0.5015 | 0.1773 | 0.6787 | 0.4247 | 552.58 | 2525.83 | 557.58 |
ZONE3 BULK STORAGE | 0.0000 | 8.8075 | 8.8075 | 1.1166 | 9.9241 | 0.9768 | 2493.87 | 14.86 | 1127.26 |
Total Facility | 0.6898 | 8.8075 | 9.4973 | 1.3745 | 10.8718 | 1.5038 | 2516.15 | 2801.42 | 2109.56 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2689053.62 | 0.00 | 2689053.62 | 3225648.14 | 5603.23 | 0.33 | 3156.44 | 0.16 |
PSZ-FINE STORAGE | 7380510.45 | 0.00 | 7380510.45 | 13393694.68 | 5637.38 | 0.33 | 3122.29 | 37.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2054 | 0.0000 | 0.2054 | 0.1023 | 479.39 | 0.33 | 3156.28 |
PSZ-FINE STORAGE | 0.5469 | 0.0000 | 0.5469 | 0.4247 | 551.04 | 0.33 | 3084.62 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2865.84 | 300.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2955.38 | 183.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2217 | 0.3727 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6214 | 0.9611 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 446 |
Defaulted Fields | 391 |
Fields with Defaults | 1172 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 403.21 | 1565.96 | 08-JAN-09:30 | 38447.39 | 15-JUN-16:00 |
Electricity:Building | 246.55 | 1084.96 | 08-JAN-09:30 | 20370.43 | 18-SEP-16:00 |
Electricity:Zone:ZONE1 OFFICE | 43.33 | 520.87 | 01-JAN-00:10 | 3190.10 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 233.98 | 1084.96 | 08-JAN-09:30 | 19728.80 | 04-NOV-08:10 |
InteriorLights:Electricity | 97.48 | 615.08 | 08-JAN-09:30 | 9693.63 | 04-NOV-08:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 14.16 | 51.00 | 01-JAN-00:10 | 1355.05 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 97.48 | 615.08 | 08-JAN-09:30 | 9693.63 | 04-NOV-08:10 |
LightsWired:InteriorLights:Electricity | 97.48 | 615.08 | 08-JAN-09:30 | 9693.63 | 04-NOV-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 14.16 | 51.00 | 01-JAN-00:10 | 1355.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 97.48 | 615.08 | 08-JAN-09:30 | 9693.63 | 04-NOV-08:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 40.57 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 40.57 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 40.57 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 162.66 | 264.11 | 08-JAN-09:30 | 14136.93 | 18-SEP-16:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 42.75 | 264.11 | 08-JAN-09:30 | 4490.00 | 02-JAN-15:30 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 42.75 | 264.11 | 08-JAN-09:30 | 4490.00 | 02-JAN-15:30 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 38.83 | 0.00 | 01-JAN-00:10 | 5307.27 | 15-JUN-15:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 12.57 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-APR-15:30 |
Ventilation (simple):Fans:Electricity | 12.57 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-APR-15:30 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 12.57 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-APR-15:30 |
ElectricityPurchased:Facility | 403.21 | 1565.96 | 30-APR-11:30 | 38447.39 | 15-JUN-16:00 |
ElectricityPurchased:Plant | 403.21 | 1565.96 | 30-APR-11:30 | 38447.39 | 15-JUN-16:00 |
Cogeneration:ElectricityPurchased | 403.21 | 1565.96 | 30-APR-11:30 | 38447.39 | 15-JUN-16:00 |
General:Cogeneration:ElectricityPurchased | 403.21 | 1565.96 | 30-APR-11:30 | 38447.39 | 15-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 403.21 | 1565.96 | 30-APR-11:30 | 38447.39 | 15-JUN-16:00 |
ElectricityNet:Plant | 403.21 | 1565.96 | 30-APR-11:30 | 38447.39 | 15-JUN-16:00 |
Cogeneration:ElectricityNet | 403.21 | 1565.96 | 30-APR-11:30 | 38447.39 | 15-JUN-16:00 |
General:Cogeneration:ElectricityNet | 403.21 | 1565.96 | 30-APR-11:30 | 38447.39 | 15-JUN-16:00 |
Electricity:HVAC | 70.75 | 0.00 | 01-JAN-00:10 | 18408.09 | 15-JUN-15:10 |
General:Fans:Electricity | 26.26 | 0.00 | 01-JAN-00:10 | 3001.98 | 15-JUN-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 44.49 | 0.00 | 01-JAN-00:10 | 15406.12 | 15-JUN-15:10 |
General:Cooling:Electricity | 44.49 | 0.00 | 01-JAN-00:10 | 15406.12 | 15-JUN-15:10 |
ExteriorLights:Electricity | 61.70 | 0.00 | 01-JAN-07:20 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.70 | 0.00 | 01-JAN-07:20 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 24.21 | 481.00 | 14-MAR-05:10 | 1970.40 | 25-JAN-12:30 |
WaterSystems:Electricity | 24.21 | 481.00 | 14-MAR-05:10 | 1970.40 | 25-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 24.21 | 481.00 | 14-MAR-05:10 | 1970.40 | 25-JAN-12:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 37.47 | 0.00 | 01-JAN-00:10 | 75706.91 | 27-DEC-06:30 |
NaturalGas:HVAC | 37.47 | 0.00 | 01-JAN-00:10 | 75706.91 | 27-DEC-06:30 |
Heating:NaturalGas | 37.47 | 0.00 | 01-JAN-00:10 | 75706.91 | 27-DEC-06:30 |
General:Heating:NaturalGas | 37.47 | 0.00 | 01-JAN-00:10 | 75706.91 | 27-DEC-06:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUN-11:20 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUN-11:20 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUN-11:20 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUN-11:20 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUN-11:20 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUN-11:20 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUN-11:20 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUN-11:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 375.54 | 0.00 | 01-JAN-00:10 | 114019.36 | 27-DEC-06:30 |
EnergyTransfer:Building | 177.62 | 0.00 | 01-JAN-00:10 | 57513.08 | 27-DEC-06:30 |
EnergyTransfer:Zone:ZONE1 OFFICE | 53.59 | 0.00 | 01-JAN-00:10 | 16227.29 | 02-FEB-06:10 |
Heating:EnergyTransfer | 26.24 | 0.00 | 01-JAN-00:10 | 57513.08 | 27-DEC-06:30 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 8.03 | 0.00 | 01-JAN-00:10 | 16227.29 | 02-FEB-06:10 |
General:Heating:EnergyTransfer | 26.24 | 0.00 | 01-JAN-00:10 | 57513.08 | 27-DEC-06:30 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 8.03 | 0.00 | 01-JAN-00:10 | 16227.29 | 02-FEB-06:10 |
Cooling:EnergyTransfer | 151.38 | 0.00 | 01-JAN-00:10 | 40541.90 | 15-JUN-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 45.56 | 0.00 | 01-JAN-00:10 | 11901.19 | 03-JUL-05:10 |
General:Cooling:EnergyTransfer | 151.38 | 0.00 | 01-JAN-00:10 | 40541.90 | 15-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 45.56 | 0.00 | 01-JAN-00:10 | 11901.19 | 03-JUL-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 121.02 | 0.00 | 01-JAN-00:10 | 30110.90 | 15-JUN-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 15.21 | 0.00 | 01-JAN-00:10 | 24435.36 | 28-JAN-05:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 15.21 | 0.00 | 01-JAN-00:10 | 24435.36 | 28-JAN-05:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 105.81 | 0.00 | 01-JAN-00:10 | 30110.90 | 15-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 105.81 | 0.00 | 01-JAN-00:10 | 30110.90 | 15-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 3.00 | 0.00 | 01-JAN-00:10 | 36460.69 | 31-DEC-07:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 3.00 | 0.00 | 01-JAN-00:10 | 36460.69 | 31-DEC-07:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 3.00 | 0.00 | 01-JAN-00:10 | 36460.69 | 31-DEC-07:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 197.92 | 0.00 | 01-JAN-00:10 | 56506.27 | 27-DEC-06:30 |
HeatingCoils:EnergyTransfer | 25.67 | 0.00 | 01-JAN-00:10 | 56506.27 | 27-DEC-06:30 |
CoolingCoils:EnergyTransfer | 172.25 | 0.00 | 01-JAN-00:10 | 50245.46 | 15-JUN-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 8.031 | -45.560 | 0.000 | 0.000 | 9.591 | 14.163 | 29.165 | 11.800 | 0.000 | 2.419 | 0.000 | 0.000 | -6.287 | 0.000 | -10.483 | -12.839 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 15.208 | -105.811 | 0.000 | 0.000 | 21.892 | 40.566 | 0.000 | 44.081 | 0.000 | 5.371 | 22.969 | 0.000 | -12.315 | 0.000 | -31.961 | -0.001 |
ZONE3 BULK STORAGE | 3.001 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 45.272 | 42.747 | 107.344 | 725.577 | 0.000 | 17.281 | 0.035 | 0.000 | -222.706 | 0.000 | -383.577 | -334.939 |
Total Facility | 3.001 | 0.000 | 23.239 | -151.370 | 0.000 | 0.000 | 76.755 | 97.476 | 136.508 | 781.458 | 0.000 | 25.071 | 23.004 | 0.000 | -241.308 | 0.000 | -426.020 | -347.779 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-MAY-05:01 | 0.00 | 0.00 | 0.00 | -29190.92 | 0.00 | 0.00 | 84.66 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 29325.24 | 0.00 | -515.14 | 0.00 | -305.36 | 0.00 |
ZONE2 FINE STORAGE | 04-JUL-16:41 | 0.00 | 0.00 | 0.00 | -59534.01 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 1449.44 | 0.00 | 541.41 | 57243.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-JUL-16:41 | 0.00 | 0.00 | 0.00 | -73180.22 | 0.00 | 0.00 | 0.00 | 747.14 | 469.88 | 27451.97 | 0.00 | 541.41 | 193324.80 | 0.00 | 0.00 | 0.00 | -149354.98 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-FEB-06:12 | 0.00 | 0.00 | 29485.85 | 0.00 | 0.00 | 0.00 | 118.54 | 404.75 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -830.31 | 0.00 | -1448.99 | -28280.36 |
ZONE2 FINE STORAGE | 26-DEC-06:01 | 0.00 | 0.00 | 93037.46 | 0.00 | 0.00 | 0.00 | 362.99 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -907.63 | 0.00 | -4826.18 | -87966.61 |
ZONE3 BULK STORAGE | 31-DEC-07:00 | 36459.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.23 | 0.00 | 0.00 | 0.00 | 0.00 | 2286.55 | 0.00 | -14916.30 | 0.00 | -24358.46 | 0.00 |
Total Facility | 26-DEC-06:01 | 10483.84 | 0.00 | 122388.10 | 0.00 | 0.00 | 0.00 | 1427.70 | 879.19 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18441.88 | 0.00 | -25825.73 | -93511.78 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3201 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.3201 | 0.0775 | 1.0000 | Not calculated | 0.1023 | 0.0775 | ||
PSZ-FINE STORAGE | 3.2515 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.2515 | 0.1306 | 1.0000 | Not calculated | 0.4247 | 0.1306 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3201 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.3201 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0775 | ||
PSZ-FINE STORAGE | 3.2515 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.2515 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1306 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3201 | 1.3201 | 1.3201 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.2515 | 3.2515 | 3.2515 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3201 | 1.3201 | 1.3201 | 1.3201 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.2515 | 3.2515 | 3.2515 | 3.2515 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3201 | 1.3201 | 1.3201 | No | 0.1023 | 0.3146 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.2515 | 3.2515 | 3.2515 | No | 0.4247 | 0.5663 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3201 | 1.3201 | 1.3201 | 1.3201 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.2515 | 3.2515 | 3.2515 | 3.2515 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 35.17 |
Number of hours cooling loads not met | 19.17 |
Number of hours not met | 54.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 37.47 | 75706.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 44.49 | 15406.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 97.48 | 9693.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.70 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 12.57 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 26.26 | 3001.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.21 | 1970.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 403.21 |
Natural Gas | 0.00 | 37.47 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 440.68 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 20.16 |
Space Heating | 0.00 |
Space Cooling | 9.20 |
Fans (All) | 8.03 |
Service Water Heating | 5.01 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 83.39 |
Subtotal | 83.39 |
Natural Gas [MJ/m2] | |
Space Heating | 7.75 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 7.75 |
Subtotal | 7.75 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 22.12 |
Space Heating | 8.50 |
Space Cooling | 10.10 |
Fans (All) | 8.81 |
Service Water Heating | 5.49 |
Receptacle Equipment | 30.98 |
Miscellaneous | 14.00 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 7315.50 | 1444.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7728.50 | 1031.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5230.83 | 3314.17 | 215.00 | 0.00 | 0.00 |
Min | 5230.83 | 1031.50 | 0.00 | 0.00 | 0.00 |
Max | 7728.50 | 3314.17 | 215.00 | 0.00 | 0.00 |
Average | 6758.28 | 1930.06 | 71.67 | 0.00 | 0.00 |
Sum | 20274.83 | 5790.17 | 215.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 69703.50 | 13015.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 107103.00 | 74990.67 | 9099.33 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 107103.00 | 74990.67 | 9099.33 | 0.00 | 0.00 |
Average | 69944.50 | 29335.39 | 3033.11 | 0.00 | 0.00 |
Sum | 209833.50 | 88006.17 | 9099.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7606.17 | 1153.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7442.33 | 1317.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5831.50 | 2928.50 | 0.00 | 0.00 | 0.00 |
Min | 5831.50 | 1153.83 | 0.00 | 0.00 | 0.00 |
Max | 7606.17 | 2928.50 | 0.00 | 0.00 | 0.00 |
Average | 6960.00 | 1800.00 | 0.00 | 0.00 | 0.00 |
Sum | 20880.00 | 5400.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32921.50 | 105.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 66769.00 | 15950.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 120314.33 | 70878.67 | 0.00 | 0.00 | 0.00 |
Min | 32921.50 | 105.50 | 0.00 | 0.00 | 0.00 |
Max | 120314.33 | 70878.67 | 0.00 | 0.00 | 0.00 |
Average | 73334.94 | 28978.06 | 0.00 | 0.00 | 0.00 |
Sum | 220004.83 | 86934.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:37
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113306E+09 | 768.69 | 27-JAN-15:50 | 9.40 | 0.75 | 0.513647E+09 | 768.95 | 12-JAN-16:10 | 9.40 | 0.75 |
February | 0.134756E+09 | 1240.48 | 23-FEB-15:00 | 21.10 | 7.10 | 0.487464E+09 | 768.96 | 22-FEB-16:40 | 21.10 | 7.10 |
March | 0.528306E+09 | 3033.72 | 16-MAR-15:40 | 22.40 | 8.49 | 0.613931E+09 | 768.96 | 09-MAR-16:40 | 22.40 | 8.49 |
April | 0.300537E+10 | 15683.88 | 29-APR-05:03 | 17.70 | 12.15 | 0.626524E+09 | 769.00 | 29-APR-08:50 | 22.02 | 14.06 |
May | 0.595251E+10 | 29191.85 | 17-MAY-05:01 | 14.08 | 5.19 | 0.659842E+09 | 769.04 | 30-MAY-15:50 | 33.98 | 17.51 |
June | 0.795890E+10 | 28613.43 | 13-JUN-05:01 | 15.18 | 4.59 | 0.660301E+09 | 769.09 | 26-JUN-15:00 | 33.30 | 17.35 |
July | 0.787722E+10 | 22448.54 | 11-JUL-05:01 | 21.70 | 15.06 | 0.635113E+09 | 769.09 | 15-JUL-15:00 | 32.80 | 18.12 |
August | 0.807834E+10 | 24993.76 | 23-AUG-05:01 | 20.00 | 11.78 | 0.685797E+09 | 769.09 | 28-AUG-15:20 | 30.60 | 17.78 |
September | 0.682505E+10 | 26586.89 | 12-SEP-05:01 | 15.13 | 10.46 | 0.634838E+09 | 769.08 | 05-SEP-14:00 | 15.13 | 10.46 |
October | 0.400363E+10 | 23017.57 | 02-OCT-05:01 | 23.72 | 15.10 | 0.632686E+09 | 769.04 | 02-OCT-08:00 | 21.70 | 16.51 |
November | 0.948702E+09 | 4416.06 | 03-NOV-16:00 | 23.90 | 13.45 | 0.560406E+09 | 768.99 | 03-NOV-12:00 | 23.90 | 13.45 |
December | 0.134448E+09 | 748.46 | 19-DEC-15:00 | 9.40 | 0.54 | 0.512020E+09 | 736.45 | 16-DEC-16:10 | 9.40 | 0.54 |
Annual Sum or Average | 0.455605E+11 | 0.722257E+10 | ||||||||
Minimum of Months | 0.113306E+09 | 748.46 | 9.40 | 0.54 | 0.487464E+09 | 736.45 | 9.40 | 0.54 | ||
Maximum of Months | 0.807834E+10 | 29191.85 | 23.90 | 15.10 | 0.685797E+09 | 769.09 | 33.98 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145037E+10 | 4657.83 | 27-JAN-10:20 | 2.03 | -3.7 | 0.835992E+09 | 1445.34 | 12-JAN-15:39 | 2.03 | -3.7 |
February | 0.112616E+10 | 4956.34 | 09-FEB-09:20 | 2.57 | -1.4 | 0.850032E+09 | 1662.68 | 23-FEB-14:50 | 21.28 | 7.21 |
March | 0.120443E+10 | 4986.72 | 24-MAR-07:10 | 2.77 | -0.9 | 0.120430E+10 | 1954.99 | 16-MAR-15:09 | 2.77 | -0.9 |
April | 0.271696E+10 | 49240.69 | 30-APR-15:03 | 30.10 | 12.65 | 0.162801E+10 | 2246.83 | 29-APR-10:39 | 30.10 | 12.65 |
May | 0.119095E+11 | 55777.64 | 20-MAY-17:06 | 32.12 | 15.22 | 0.189422E+10 | 2246.94 | 24-MAY-13:39 | 29.27 | 18.80 |
June | 0.228771E+11 | 59439.86 | 25-JUN-14:13 | 30.97 | 16.72 | 0.192769E+10 | 2246.96 | 15-JUN-15:30 | 30.97 | 16.72 |
July | 0.228193E+11 | 59534.05 | 04-JUL-16:41 | 28.32 | 18.59 | 0.185455E+10 | 2247.02 | 26-JUL-14:09 | 36.70 | 20.66 |
August | 0.203721E+11 | 59189.79 | 13-AUG-17:03 | 31.10 | 18.43 | 0.200051E+10 | 2246.96 | 07-AUG-15:00 | 31.10 | 18.43 |
September | 0.143456E+11 | 58895.17 | 17-SEP-13:32 | 32.03 | 15.98 | 0.184253E+10 | 2246.95 | 01-SEP-12:09 | 32.03 | 15.98 |
October | 0.407948E+10 | 52490.47 | 01-OCT-13:43 | 32.02 | 15.31 | 0.169079E+10 | 2246.95 | 04-OCT-12:00 | 28.90 | 18.99 |
November | 0.140294E+10 | 4818.64 | 17-NOV-08:50 | 4.72 | 0.97 | 0.112867E+10 | 2163.84 | 03-NOV-15:20 | 4.72 | 0.97 |
December | 0.151060E+10 | 4772.22 | 19-DEC-09:40 | 1.87 | -3.7 | 0.816502E+09 | 1310.05 | 16-DEC-15:20 | 1.87 | -3.7 |
Annual Sum or Average | 0.105815E+12 | 0.176738E+11 | ||||||||
Minimum of Months | 0.112616E+10 | 4657.83 | 1.87 | -3.7 | 0.816502E+09 | 1310.05 | 1.87 | -3.7 | ||
Maximum of Months | 0.228771E+11 | 59534.05 | 32.12 | 18.59 | 0.200051E+10 | 2247.02 | 36.70 | 20.66 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.92 | 0.145199E+10 | 2868.01 | 03-JAN-15:09 | 20.50 | 8.33 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 | 1.84 | 0.153860E+10 | 3267.31 | 23-FEB-14:50 | 21.28 | 7.21 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.40 | 0.250172E+10 | 4113.32 | 22-MAR-13:50 | 24.50 | 9.16 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.41 | 0.381599E+10 | 7096.07 | 21-APR-15:09 | 32.02 | 15.38 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.41 | 0.528470E+10 | 8503.20 | 19-MAY-14:20 | 34.80 | 17.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.56 | 0.627175E+10 | 9097.65 | 01-JUN-14:00 | 36.70 | 14.74 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.63 | 17.07 | 0.581887E+10 | 9097.65 | 01-JUL-13:30 | 36.65 | 19.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.12 | 0.603845E+10 | 9097.65 | 07-AUG-15:39 | 36.47 | 18.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.18 | 0.529534E+10 | 8178.24 | 19-SEP-14:20 | 33.70 | 16.73 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.67 | 0.407890E+10 | 7559.75 | 03-OCT-14:20 | 32.43 | 19.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.64 | 0.233449E+10 | 4652.05 | 03-NOV-15:09 | 23.40 | 13.55 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.46 | 0.129734E+10 | 2264.08 | 01-DEC-13:00 | 14.40 | 6.57 |
Annual Sum or Average | 0.00 | 0.457281E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 6.42 | 1.84 | 0.129734E+10 | 2264.08 | 14.40 | 6.57 | ||
Maximum of Months | 0.00 | 0.00 | 27.63 | 18.12 | 0.627175E+10 | 9097.65 | 36.70 | 19.82 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.223151E+10 | 29352.21 | 06-JAN-06:01 | 0.10 |
February | 0.164252E+10 | 29485.82 | 02-FEB-06:12 | -3.7 |
March | 0.100520E+10 | 29359.92 | 02-MAR-06:01 | -3.5 |
April | 91135480.17 | 28572.57 | 01-APR-05:02 | 11.10 |
May | 11377269.07 | 843.50 | 02-MAY-06:20 | 10.33 |
June | 859252.54 | 410.08 | 21-JUN-06:01 | 21.23 |
July | 6670.75 | 33.35 | 10-JUL-06:03 | 22.67 |
August | 422947.63 | 350.36 | 17-AUG-06:03 | 17.30 |
September | 2799050.03 | 677.39 | 25-SEP-06:10 | 10.55 |
October | 36998228.40 | 891.26 | 11-OCT-06:15 | 7.23 |
November | 0.669362E+09 | 29346.41 | 28-NOV-06:01 | 1.02 |
December | 0.233891E+10 | 29394.61 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.803111E+10 | |||
Minimum of Months | 6670.75 | 33.35 | -3.7 | |
Maximum of Months | 0.233891E+10 | 29485.82 | 22.67 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.441891E+10 | 82864.61 | 28-JAN-05:42 | -3.2 |
February | 0.239919E+10 | 78869.26 | 03-FEB-06:01 | -3.7 |
March | 0.883379E+09 | 58822.53 | 02-MAR-06:31 | -2.4 |
April | 0.216800E+09 | 3172.09 | 01-APR-17:00 | 28.90 |
May | 87333670.36 | 1330.35 | 01-MAY-07:00 | 15.00 |
June | 18942534.64 | 1607.30 | 17-JUN-06:04 | 23.07 |
July | 3109302.76 | 1447.12 | 10-JUL-06:07 | 22.67 |
August | 34054523.41 | 1507.16 | 01-AUG-06:07 | 22.48 |
September | 72313527.92 | 1291.54 | 08-SEP-07:00 | 17.80 |
October | 0.112344E+09 | 1508.49 | 13-OCT-07:00 | 14.40 |
November | 0.623007E+09 | 53700.25 | 29-NOV-06:10 | 8.40 |
December | 0.633879E+10 | 93037.66 | 26-DEC-06:01 | -0.6 |
Annual Sum or Average | 0.152082E+11 | |||
Minimum of Months | 3109302.76 | 1291.54 | -3.7 | |
Maximum of Months | 0.633879E+10 | 93037.66 | 28.90 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335607E+09 | 24098.82 | 28-JAN-06:00 | -3.3 |
February | 0.200819E+09 | 17287.41 | 03-FEB-05:00 | -3.9 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.246460E+10 | 36460.69 | 31-DEC-07:00 | -2.8 |
Annual Sum or Average | 0.300103E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.9 | |
Maximum of Months | 0.246460E+10 | 36460.69 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.122273E+10 | 1355.05 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.110264E+10 | 1355.05 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.123965E+10 | 1355.05 | 03-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.114043E+10 | 1355.05 | 04-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.117570E+10 | 1355.05 | 03-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.118425E+10 | 1224.06 | 01-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.114482E+10 | 1355.05 | 03-JUL-15:39 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.123300E+10 | 1355.05 | 14-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.115333E+10 | 1355.05 | 01-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.117167E+10 | 1355.05 | 02-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.117045E+10 | 1355.05 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.122468E+10 | 1355.05 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.141634E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.110264E+10 | 1224.06 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.123965E+10 | 1355.05 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.365033E+10 | 3848.58 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.326766E+10 | 3848.58 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.351116E+10 | 3848.58 | 01-MAR-15:50 | 0.00 | 0.00 |
April | 0.320205E+10 | 3848.58 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.319691E+10 | 3527.86 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.320104E+10 | 3527.86 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.310258E+10 | 3527.86 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.337357E+10 | 3848.58 | 24-AUG-08:09 | 0.00 | 0.00 |
September | 0.333032E+10 | 3848.58 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.344227E+10 | 3848.58 | 03-OCT-08:09 | 0.00 | 0.00 |
November | 0.356520E+10 | 3848.58 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.372278E+10 | 3848.58 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.405659E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.310258E+10 | 3527.86 | 0.00 | 0.00 | |
Maximum of Months | 0.372278E+10 | 3848.58 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.400491E+10 | 4490.00 | 02-JAN-15:30 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.347246E+10 | 4490.00 | 04-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.373809E+10 | 3961.65 | 01-MAR-16:00 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.324438E+10 | 3741.67 | 20-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.325344E+10 | 3169.37 | 03-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.321922E+10 | 3301.38 | 26-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.323318E+10 | 3741.67 | 07-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.342738E+10 | 3741.67 | 24-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.352183E+10 | 3961.65 | 05-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.369755E+10 | 3961.65 | 02-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.390701E+10 | 4490.00 | 04-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.402742E+10 | 4490.00 | 02-DEC-15:20 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.427469E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.321922E+10 | 3169.37 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.402742E+10 | 4490.00 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.122273E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167749E+10 |
February | 0.127628E+10 | 0.110264E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2842356.91 | 0.140394E+10 |
March | 0.149825E+10 | 0.123965E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2739491.81 | 0.142021E+10 |
April | 0.138726E+10 | 0.114043E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151195E+09 | 0.829896E+09 |
May | 0.144276E+10 | 0.117570E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358004E+09 | 0.460248E+09 |
June | 0.144276E+10 | 0.118425E+10 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668024E+09 | 0.180437E+09 |
July | 0.138726E+10 | 0.114482E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501962E+09 | 0.146251E+09 |
August | 0.149825E+10 | 0.123300E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429722E+09 | 0.223492E+09 |
September | 0.138726E+10 | 0.115333E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245988E+09 | 0.296655E+09 |
October | 0.138726E+10 | 0.117167E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58539586.20 | 0.832012E+09 |
November | 0.133177E+10 | 0.117045E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137981E+10 |
December | 0.138726E+10 | 0.122468E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163222E+10 |
Annual Sum or Average | 0.168137E+11 | 0.141634E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241902E+10 | 0.104827E+11 |
Minimum of Months | 0.127628E+10 | 0.110264E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146251E+09 |
Maximum of Months | 0.149825E+10 | 0.123965E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668024E+09 | 0.167749E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.365033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1417218.08 | 0.428900E+10 |
February | 0.300332E+10 | 0.326766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32482012.11 | 0.366849E+10 |
March | 0.352563E+10 | 0.351116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21113366.33 | 0.396976E+10 |
April | 0.326447E+10 | 0.320205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288815E+09 | 0.317678E+10 |
May | 0.339505E+10 | 0.319691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823074E+09 | 0.215548E+10 |
June | 0.339505E+10 | 0.320104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169135E+10 | 0.836069E+09 |
July | 0.326447E+10 | 0.310258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122427E+10 | 0.682887E+09 |
August | 0.352563E+10 | 0.337357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960182E+09 | 0.954591E+09 |
September | 0.326447E+10 | 0.333032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259754E+09 | 0.112364E+10 |
October | 0.326447E+10 | 0.344227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68141713.57 | 0.319714E+10 |
November | 0.313390E+10 | 0.356520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91791.81 | 0.405313E+10 |
December | 0.326447E+10 | 0.372278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385385E+10 |
Annual Sum or Average | 0.395654E+11 | 0.405659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537069E+10 | 0.319608E+11 |
Minimum of Months | 0.300332E+10 | 0.310258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682887E+09 |
Maximum of Months | 0.352563E+10 | 0.372278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169135E+10 | 0.428900E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.400491E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63763330.70 | 0.136244E+11 |
February | 0.690763E+10 | 0.347246E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759763E+09 | 0.121426E+11 |
March | 0.810895E+10 | 0.373809E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511081E+09 | 0.157933E+11 |
April | 0.750829E+10 | 0.324438E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103930E+10 | 0.149954E+11 |
May | 0.780862E+10 | 0.325344E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73303744.29 | 0.141900E+11 |
June | 0.780862E+10 | 0.321922E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174986E+09 | 0.733872E+10 |
July | 0.750829E+10 | 0.323318E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80460780.94 | 0.648909E+10 |
August | 0.810895E+10 | 0.342738E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36972423.71 | 0.756849E+10 |
September | 0.750829E+10 | 0.352183E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1960615.71 | 0.751172E+10 |
October | 0.750829E+10 | 0.369755E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21201255.43 | 0.155457E+11 |
November | 0.720796E+10 | 0.390701E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18958709.48 | 0.157196E+11 |
December | 0.750829E+10 | 0.402742E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115362E+09 | 0.111538E+11 |
Annual Sum or Average | 0.910005E+11 | 0.427469E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289712E+10 | 0.142073E+12 |
Minimum of Months | 0.690763E+10 | 0.321922E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1960615.71 | 0.648909E+10 |
Maximum of Months | 0.810895E+10 | 0.402742E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103930E+10 | 0.157933E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1355.05 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6436.60 | 27-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1355.05 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 122.86 | 19-FEB-14:00 | 6215.01 | 01-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1355.05 | 03-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 256.23 | 21-MAR-16:10 | 5584.56 | 27-MAR-07:00 |
April | 1680.92 | 01-APR-07:10 | 1355.05 | 04-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2448.66 | 21-APR-16:10 | 3890.40 | 11-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1355.05 | 03-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2969.40 | 19-MAY-17:00 | 3295.14 | 02-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1224.06 | 01-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3887.68 | 05-JUN-17:00 | 1510.73 | 29-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1355.05 | 03-JUL-15:39 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3664.79 | 03-JUL-17:00 | 1391.82 | 05-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 1355.05 | 14-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3156.52 | 07-AUG-16:10 | 1644.02 | 31-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 1355.05 | 01-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1971.86 | 18-SEP-17:00 | 2879.76 | 25-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 1355.05 | 02-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1684.45 | 05-OCT-16:10 | 3639.83 | 25-OCT-06:05 |
November | 1680.92 | 01-NOV-07:10 | 1355.05 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5228.64 | 28-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1355.05 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6000.27 | 27-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1224.06 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1391.82 | |||||
Maximum of Months | 1680.92 | 1355.05 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 3887.68 | 6436.60 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3848.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.04 | 03-JAN-17:20 | 8543.41 | 25-JAN-22:57 |
February | 3955.50 | 01-FEB-08:09 | 3848.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.64 | 20-FEB-16:00 | 12471.24 | 08-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 3848.58 | 01-MAR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1494.75 | 03-MAR-16:10 | 10237.34 | 27-MAR-07:00 |
April | 3955.50 | 01-APR-07:10 | 3848.58 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5701.38 | 21-APR-15:10 | 12628.85 | 22-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 3527.86 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4922.97 | 19-MAY-17:00 | 6028.95 | 01-MAY-08:00 |
June | 3955.50 | 01-JUN-07:10 | 3527.86 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7023.19 | 05-JUN-17:00 | 5106.68 | 28-JUN-02:00 |
July | 3955.50 | 01-JUL-07:10 | 3527.86 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5589.03 | 03-JUL-17:00 | 3452.18 | 18-JUL-21:00 |
August | 3955.50 | 01-AUG-07:10 | 3848.58 | 24-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4864.10 | 26-AUG-15:10 | 4170.02 | 14-AUG-01:00 |
September | 3955.50 | 01-SEP-07:10 | 3848.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1608.02 | 18-SEP-17:00 | 3558.84 | 23-SEP-17:00 |
October | 3955.50 | 02-OCT-07:10 | 3848.58 | 03-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1935.57 | 01-OCT-14:53 | 6291.77 | 23-OCT-18:00 |
November | 3955.50 | 01-NOV-07:10 | 3848.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.12 | 23-NOV-16:00 | 6914.00 | 15-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 3848.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9800.82 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3527.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3452.18 | ||||
Maximum of Months | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7023.19 | 12628.85 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 4490.00 | 02-JAN-15:30 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6790.26 | 03-JAN-17:00 | 21450.52 | 05-JAN-09:00 |
February | 9097.65 | 01-FEB-08:09 | 4490.00 | 04-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9262.37 | 06-FEB-22:00 | 34612.39 | 09-FEB-00:55 |
March | 9097.65 | 01-MAR-08:09 | 3961.65 | 01-MAR-16:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14632.08 | 03-MAR-16:00 | 35609.87 | 27-MAR-07:10 |
April | 9097.65 | 01-APR-07:10 | 3741.67 | 20-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15181.12 | 01-APR-15:00 | 49416.08 | 22-APR-07:10 |
May | 9097.65 | 01-MAY-07:10 | 3169.37 | 03-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.81 | 19-MAY-14:00 | 30181.90 | 01-MAY-10:00 |
June | 9097.65 | 01-JUN-07:10 | 3301.38 | 26-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2137.87 | 02-JUN-16:00 | 25926.74 | 28-JUN-02:00 |
July | 9097.65 | 01-JUL-07:10 | 3741.67 | 07-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2234.12 | 02-JUL-21:53 | 18431.42 | 18-JUL-21:00 |
August | 9097.65 | 01-AUG-07:10 | 3741.67 | 24-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1461.57 | 07-AUG-16:00 | 20776.07 | 14-AUG-01:00 |
September | 9097.65 | 01-SEP-07:10 | 3961.65 | 05-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.89 | 10-SEP-14:43 | 14872.93 | 23-SEP-17:00 |
October | 9097.65 | 02-OCT-07:10 | 3961.65 | 02-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1761.44 | 18-OCT-16:00 | 32666.19 | 06-OCT-09:00 |
November | 9097.65 | 01-NOV-07:10 | 4490.00 | 04-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1732.07 | 23-NOV-16:00 | 26149.48 | 15-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 4490.00 | 02-DEC-15:20 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3780.68 | 10-DEC-15:00 | 25494.61 | 18-DEC-08:70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 3169.37 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 327.89 | 14872.93 | |||||
Maximum of Months | 9097.65 | 4490.00 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 15181.12 | 49416.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 768.69 | 27-JAN-15:50 | 1680.92 | 1047.90 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.31 |
February | 1240.48 | 23-FEB-15:00 | 1680.92 | 1047.90 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.55 |
March | 3033.72 | 16-MAR-15:40 | 1680.92 | 871.75 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.21 |
April | 15683.88 | 29-APR-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.80 |
May | 29191.85 | 17-MAY-05:01 | 1294.31 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.36 |
June | 28613.43 | 13-JUN-05:01 | 1294.31 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.54 |
July | 22448.54 | 11-JUL-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.17 |
August | 24993.76 | 23-AUG-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.80 |
September | 26586.89 | 12-SEP-05:01 | 1294.31 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.68 |
October | 23017.57 | 02-OCT-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.59 |
November | 4416.06 | 03-NOV-16:00 | 1680.92 | 916.92 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
December | 748.46 | 19-DEC-15:00 | 1680.92 | 1047.90 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 748.46 | 739.61 | 203.98 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 | |
Maximum of Months | 29191.85 | 1849.01 | 1047.90 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4657.83 | 27-JAN-10:20 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1757.07 |
February | 4956.34 | 09-FEB-09:20 | 3955.50 | 3527.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 929.32 |
March | 4986.72 | 24-MAR-07:10 | 3955.50 | 3395.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 49240.69 | 30-APR-15:03 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.39 | 0.00 |
May | 55777.64 | 20-MAY-17:06 | 0.00 | 2263.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1866.49 | 0.00 |
June | 59439.86 | 25-JUN-14:13 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.52 | 0.00 |
July | 59534.05 | 04-JUL-16:41 | 0.00 | 2699.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.41 | 0.00 |
August | 59189.79 | 13-AUG-17:03 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.67 | 0.00 |
September | 58895.17 | 17-SEP-13:32 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 826.67 | 0.00 |
October | 52490.47 | 01-OCT-13:43 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 744.04 | 0.00 |
November | 4818.64 | 17-NOV-08:50 | 3955.50 | 3395.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.00 |
December | 4772.22 | 19-DEC-09:40 | 3955.50 | 3207.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4657.83 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 59534.05 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1866.49 | 1757.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 528.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6127.63 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 1056.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10611.39 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7405.21 |
April | 0.00 | 01-APR-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3473.33 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3585.88 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5802.09 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 1056.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.88 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1591.25 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6408.25 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 528.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2512.38 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8791.02 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2729.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 528.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.88 | |
Maximum of Months | 0.00 | 0.00 | 1056.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10611.39 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.309298E+11 | 23179.76 | 26-JAN-15:00 | 0.107099E+11 | 71269.59 | 28-JAN-06:30 |
February | 0.274913E+11 | 23061.70 | 04-FEB-15:00 | 0.608116E+10 | 53826.06 | 02-FEB-06:19 |
March | 0.303588E+11 | 22625.75 | 29-MAR-08:20 | 0.227113E+10 | 38719.67 | 02-MAR-06:10 |
April | 0.288549E+11 | 28972.20 | 21-APR-14:50 | 63329205.92 | 6056.06 | 01-APR-05:10 |
May | 0.344948E+11 | 33395.27 | 19-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.407863E+11 | 38447.39 | 15-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.411968E+11 | 36459.30 | 26-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.408759E+11 | 35672.57 | 07-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.363602E+11 | 34110.57 | 01-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.311280E+11 | 32650.63 | 05-OCT-14:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.294997E+11 | 27844.50 | 27-NOV-16:00 | 0.173173E+10 | 32261.00 | 28-NOV-06:19 |
December | 0.312379E+11 | 27849.32 | 18-DEC-16:00 | 0.166098E+11 | 75706.91 | 27-DEC-06:30 |
Annual Sum or Average | 0.403214E+12 | 0.374670E+11 | ||||
Minimum of Months | 0.274913E+11 | 22625.75 | 0.00 | 0.00 | ||
Maximum of Months | 0.411968E+11 | 38447.39 | 0.166098E+11 | 75706.91 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.887797E+10 | 0.639293E+10 | 0.112984E+11 | 0.00 | 0.220368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215684E+10 | 0.00 |
February | 0.784276E+10 | 0.536714E+10 | 0.103734E+11 | 0.00 | 0.194654E+10 | 0.00 | 0.00 | 2837471.93 | 0.00 | 0.00 | 0.00 | 0.195866E+10 | 0.00 |
March | 0.848890E+10 | 0.536275E+10 | 0.121089E+11 | 0.00 | 0.216927E+10 | 0.00 | 0.00 | 50254521.63 | 0.00 | 0.00 | 0.00 | 0.217874E+10 | 0.00 |
April | 0.758686E+10 | 0.460676E+10 | 0.112578E+11 | 0.00 | 0.211728E+10 | 0.00 | 0.00 | 0.126561E+10 | 0.00 | 0.00 | 0.00 | 0.202068E+10 | 0.00 |
May | 0.762605E+10 | 0.425969E+10 | 0.117000E+11 | 0.00 | 0.374390E+10 | 0.00 | 0.00 | 0.513459E+10 | 0.00 | 0.00 | 0.00 | 0.203059E+10 | 0.00 |
June | 0.760451E+10 | 0.387400E+10 | 0.116594E+11 | 0.00 | 0.580882E+10 | 0.00 | 0.00 | 0.991011E+10 | 0.00 | 0.00 | 0.00 | 0.192954E+10 | 0.00 |
July | 0.748058E+10 | 0.411357E+10 | 0.112984E+11 | 0.00 | 0.563362E+10 | 0.00 | 0.00 | 0.107477E+11 | 0.00 | 0.00 | 0.00 | 0.192297E+10 | 0.00 |
August | 0.803396E+10 | 0.453794E+10 | 0.121016E+11 | 0.00 | 0.511830E+10 | 0.00 | 0.00 | 0.911813E+10 | 0.00 | 0.00 | 0.00 | 0.196599E+10 | 0.00 |
September | 0.800548E+10 | 0.493138E+10 | 0.112504E+11 | 0.00 | 0.365639E+10 | 0.00 | 0.00 | 0.660642E+10 | 0.00 | 0.00 | 0.00 | 0.191010E+10 | 0.00 |
October | 0.831149E+10 | 0.570393E+10 | 0.113057E+11 | 0.00 | 0.219227E+10 | 0.00 | 0.00 | 0.160596E+10 | 0.00 | 0.00 | 0.00 | 0.200859E+10 | 0.00 |
November | 0.864265E+10 | 0.602781E+10 | 0.108562E+11 | 0.00 | 0.192034E+10 | 0.00 | 0.00 | 52011697.40 | 0.00 | 0.00 | 0.00 | 0.200072E+10 | 0.00 |
December | 0.897487E+10 | 0.651881E+10 | 0.112984E+11 | 0.00 | 0.231848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212735E+10 | 0.00 |
Annual Sum or Average | 0.974761E+11 | 0.616967E+11 | 0.136508E+12 | 0.00 | 0.388289E+11 | 0.00 | 0.00 | 0.444936E+11 | 0.00 | 0.00 | 0.00 | 0.242108E+11 | 0.00 |
Minimum of Months | 0.748058E+10 | 0.387400E+10 | 0.103734E+11 | 0.00 | 0.192034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191010E+10 | 0.00 |
Maximum of Months | 0.897487E+10 | 0.651881E+10 | 0.121089E+11 | 0.00 | 0.580882E+10 | 0.00 | 0.00 | 0.107477E+11 | 0.00 | 0.00 | 0.00 | 0.217874E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.107099E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.608116E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.227113E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 63329205.92 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.173173E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.166098E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.374670E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.166098E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 9386.49 | 26-JAN-15:00 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2941.04 | 27-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 9386.49 | 04-FEB-15:00 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2847.93 | 03-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8945.30 | 17-MAR-08:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2556.63 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 8624.58 | 20-APR-08:09 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 4281.64 | 21-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7745.26 | 04-MAY-08:09 | 5520.82 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 4422.92 | 19-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7921.15 | 26-JUN-07:10 | 4975.14 | 01-JUN-19:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 5307.27 | 15-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 8624.58 | 07-JUL-08:09 | 5520.82 | 06-JUL-05:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 4724.04 | 26-JUL-14:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 8945.30 | 24-AUG-08:09 | 5520.82 | 01-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4902.34 | 07-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 8945.30 | 01-SEP-08:09 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 4422.37 | 05-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 8945.30 | 14-OCT-08:09 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 4337.50 | 05-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 9693.63 | 04-NOV-08:09 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2412.40 | 28-NOV-07:19 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 9693.63 | 02-DEC-15:20 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2944.66 | 27-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 7745.26 | 4975.14 | 10035.17 | 0.00 | 2412.40 | 0.00 | 0.00 | |||||
Maximum of Months | 9693.63 | 5520.82 | 10035.17 | 0.00 | 5307.27 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 1970.40 | 25-JAN-12:30 | 0.00 |
February | 195.36 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 | 1969.97 | 02-FEB-12:00 | 0.00 |
March | 890.35 | 21-MAR-15:00 | 0.00 | 0.00 | 0.00 | 1814.59 | 10-MAR-12:50 | 0.00 |
April | 7753.13 | 21-APR-15:09 | 0.00 | 0.00 | 0.00 | 1790.34 | 01-APR-11:09 | 0.00 |
May | 10757.05 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1765.44 | 01-MAY-11:39 | 0.00 |
June | 15406.12 | 15-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1740.44 | 01-JUN-11:50 | 0.00 |
July | 13506.79 | 26-JUL-14:30 | 0.00 | 0.00 | 0.00 | 1723.49 | 01-JUL-11:50 | 0.00 |
August | 13956.62 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1723.65 | 31-AUG-11:30 | 0.00 |
September | 10588.13 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1740.78 | 30-SEP-11:09 | 0.00 |
October | 9560.32 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 1765.79 | 31-OCT-11:50 | 0.00 |
November | 1187.78 | 03-NOV-15:00 | 0.00 | 0.00 | 0.00 | 1791.49 | 30-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 1858.62 | 27-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1723.49 | 0.00 | ||
Maximum of Months | 15406.12 | 0.00 | 0.00 | 0.00 | 1970.40 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 23179.76 | 26-JAN-15:00 | 9386.49 | 10035.17 | 0.00 | 0.00 | 1982.04 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23061.70 | 04-FEB-15:00 | 9386.49 | 10035.17 | 0.00 | 0.00 | 1976.35 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22625.75 | 29-MAR-08:20 | 8945.30 | 10035.17 | 0.00 | 0.00 | 1986.25 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28972.20 | 21-APR-14:50 | 6056.64 | 10035.17 | 0.00 | 0.00 | 4281.64 | 0.00 | 0.00 | 6858.75 | 0.00 |
May | 33395.27 | 19-MAY-15:00 | 6627.58 | 10035.17 | 0.00 | 0.00 | 4385.63 | 0.00 | 0.00 | 10757.05 | 0.00 |
June | 38447.39 | 15-JUN-15:00 | 6803.73 | 10035.17 | 0.00 | 0.00 | 5280.90 | 0.00 | 0.00 | 15177.53 | 0.00 |
July | 36459.30 | 26-JUL-13:00 | 6553.51 | 10035.17 | 0.00 | 0.00 | 4713.61 | 0.00 | 0.00 | 13489.49 | 0.00 |
August | 35672.57 | 07-AUG-15:00 | 6297.44 | 10035.17 | 0.00 | 0.00 | 4902.34 | 0.00 | 0.00 | 13956.62 | 0.00 |
September | 34110.57 | 01-SEP-14:00 | 7577.39 | 10035.17 | 0.00 | 0.00 | 4366.82 | 0.00 | 0.00 | 10433.57 | 0.00 |
October | 32650.63 | 05-OCT-14:50 | 7577.39 | 10035.17 | 0.00 | 0.00 | 4291.14 | 0.00 | 0.00 | 9031.91 | 0.00 |
November | 27844.50 | 27-NOV-16:00 | 8712.41 | 10035.17 | 5520.82 | 0.00 | 1976.35 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27849.32 | 18-DEC-16:00 | 8712.41 | 10035.17 | 5520.82 | 0.00 | 1977.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 22625.75 | 6056.64 | 10035.17 | 0.00 | 0.00 | 1976.35 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38447.39 | 9386.49 | 10035.17 | 5520.82 | 0.00 | 5280.90 | 0.00 | 0.00 | 15177.53 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 71269.59 | 28-JAN-06:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 53826.06 | 02-FEB-06:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 38719.67 | 02-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 6056.06 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 32261.00 | 28-NOV-06:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 75706.91 | 27-DEC-06:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 75706.91 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.83 | 19.82 | 7.83 | 19.82 | 0.00 | 19.82 | 0.00 | 19.82 |
February | 6.50 | 20.01 | 6.50 | 20.01 | 0.00 | 20.01 | 0.00 | 20.01 |
March | 4.33 | 20.21 | 4.33 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.52 | 0.17 | 24.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.26 | 1.17 | 24.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.66 | 3.83 | 24.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.69 | 5.67 | 24.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.71 | 4.50 | 24.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.61 | 3.17 | 24.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.60 | 0.67 | 24.60 |
November | 2.33 | 20.19 | 2.33 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 |
December | 7.83 | 19.87 | 7.83 | 19.87 | 0.00 | 19.87 | 0.00 | 19.87 |
Annual Sum or Average | 28.83 | 19.96 | 28.83 | 19.96 | 19.33 | 21.16 | 19.17 | 21.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 | 0.00 | 19.82 |
Maximum of Months | 7.83 | 20.21 | 7.83 | 20.21 | 5.67 | 25.26 | 5.67 | 24.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.00 | 14.87 | 2.67 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
February | 9.67 | 14.86 | 1.67 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
March | 3.17 | 14.89 | 0.50 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.41 | 0.00 | 27.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.52 | 0.00 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 27.62 | 0.00 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 27.63 | 0.00 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 27.62 | 0.00 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.53 | 0.00 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.47 | 0.00 | 27.47 |
November | 2.17 | 14.89 | 0.33 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
December | 29.67 | 14.84 | 4.17 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
Annual Sum or Average | 62.67 | 14.86 | 9.33 | 14.85 | 120.67 | 22.83 | 0.00 | 22.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.84 | 0.00 | 14.84 |
Maximum of Months | 29.67 | 14.89 | 4.17 | 14.89 | 35.17 | 27.63 | 0.00 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.36 | 253.33 | 21.26 | 253.33 | 21.22 |
February | 276.00 | 21.66 | 191.50 | 21.45 | 191.50 | 21.37 |
March | 324.00 | 22.40 | 137.50 | 22.04 | 137.50 | 21.84 |
April | 213.33 | 23.49 | 36.83 | 23.44 | 10.00 | 23.35 |
May | 53.50 | 23.76 | 163.33 | 23.87 | 0.00 | 23.87 |
June | 2.00 | 22.77 | 276.67 | 23.90 | 0.00 | 23.90 |
July | 38.50 | 23.93 | 300.00 | 23.91 | 38.50 | 23.92 |
August | 12.83 | 23.91 | 321.33 | 23.91 | 12.83 | 23.91 |
September | 18.50 | 23.83 | 272.83 | 23.90 | 15.33 | 23.90 |
October | 100.83 | 23.64 | 120.17 | 23.78 | 4.17 | 23.78 |
November | 276.50 | 22.61 | 89.50 | 22.25 | 89.50 | 22.04 |
December | 300.00 | 21.32 | 255.00 | 21.23 | 255.00 | 21.20 |
Annual Sum or Average | 1916.00 | 22.27 | 2418.00 | 22.59 | 1007.67 | 22.35 |
Minimum of Months | 2.00 | 21.32 | 36.83 | 21.23 | 0.00 | 21.20 |
Maximum of Months | 324.00 | 23.93 | 321.33 | 23.91 | 255.00 | 23.92 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 17.42 | 298.67 | 17.41 | 298.67 | 17.40 |
February | 276.00 | 18.26 | 257.83 | 18.13 | 257.83 | 18.08 |
March | 324.00 | 20.14 | 191.67 | 19.54 | 191.67 | 19.27 |
April | 132.17 | 22.79 | 159.50 | 24.33 | 28.00 | 24.12 |
May | 148.17 | 26.32 | 278.50 | 26.48 | 130.17 | 26.53 |
June | 241.50 | 26.70 | 312.00 | 26.69 | 241.50 | 26.69 |
July | 288.00 | 26.71 | 300.00 | 26.71 | 288.00 | 26.71 |
August | 288.83 | 26.68 | 324.00 | 26.67 | 288.83 | 26.68 |
September | 222.17 | 26.67 | 291.00 | 26.62 | 219.67 | 26.65 |
October | 128.83 | 24.24 | 204.83 | 25.47 | 49.83 | 25.61 |
November | 267.17 | 20.29 | 152.83 | 19.81 | 139.67 | 19.46 |
December | 300.00 | 17.20 | 300.00 | 17.20 | 300.00 | 17.20 |
Annual Sum or Average | 2916.83 | 22.35 | 3070.83 | 22.75 | 2433.83 | 22.61 |
Minimum of Months | 128.83 | 17.20 | 152.83 | 17.20 | 28.00 | 17.20 |
Maximum of Months | 324.00 | 26.71 | 324.00 | 26.71 | 300.00 | 26.71 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 14.84 | 300.00 | 14.84 | 300.00 | 14.84 |
February | 276.00 | 15.95 | 276.00 | 15.95 | 276.00 | 15.95 |
March | 324.00 | 19.02 | 251.83 | 18.63 | 251.83 | 18.48 |
April | 175.50 | 23.84 | 155.33 | 24.84 | 68.17 | 24.93 |
May | 256.83 | 29.43 | 292.83 | 29.30 | 245.33 | 29.42 |
June | 312.00 | 31.63 | 312.00 | 31.63 | 312.00 | 31.63 |
July | 300.00 | 31.11 | 300.00 | 31.11 | 300.00 | 31.11 |
August | 324.00 | 30.46 | 324.00 | 30.46 | 324.00 | 30.46 |
September | 280.17 | 29.79 | 300.00 | 29.67 | 280.17 | 29.71 |
October | 158.00 | 25.52 | 201.67 | 26.41 | 78.17 | 26.80 |
November | 281.33 | 19.31 | 200.67 | 18.82 | 197.33 | 18.58 |
December | 300.00 | 13.96 | 300.00 | 13.96 | 300.00 | 13.96 |
Annual Sum or Average | 3287.83 | 23.67 | 3214.33 | 23.85 | 2933.00 | 23.83 |
Minimum of Months | 158.00 | 13.96 | 155.33 | 13.96 | 68.17 | 13.96 |
Maximum of Months | 324.00 | 31.63 | 324.00 | 31.63 | 324.00 | 31.63 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 11153892.53 | 2837471.93 | 7.33 | 11153892.53 | 0.00 | 0.00 | 0.09 | 21-FEB-16:00 | 0.00 | 01-FEB-00:05 | 770.34 | 21-FEB-16:00 | 770.34 | 21-FEB-16:00 | 0.00 | 21-FEB-15:50 | 195.36 | 21-FEB-16:00 | 0.00 | 01-FEB-00:05 |
March | 0.202168E+09 | 50254521.63 | 42.33 | 0.202168E+09 | 0.00 | 0.00 | 0.39 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 | 3598.85 | 21-MAR-16:00 | 3598.85 | 21-MAR-16:00 | 0.00 | 14-MAR-15:10 | 890.35 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.259770E+10 | 0.650624E+09 | 174.43 | 0.258151E+10 | 16185551.15 | 0.00 | 1.00 | 20-APR-05:03 | 0.00 | 01-APR-00:10 | 20734.83 | 20-APR-05:03 | 20734.83 | 20-APR-05:03 | 1713.57 | 29-APR-05:03 | 4522.31 | 20-APR-05:03 | 0.00 | 01-APR-00:10 |
May | 0.649543E+10 | 0.161132E+10 | 271.88 | 0.626446E+10 | 0.230975E+09 | 0.00 | 1.00 | 01-MAY-05:03 | 0.00 | 01-MAY-00:10 | 22508.17 | 23-MAY-05:01 | 21360.18 | 31-MAY-05:01 | 6531.02 | 24-MAY-05:02 | 4906.76 | 23-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.967626E+10 | 0.250347E+10 | 304.02 | 0.914963E+10 | 0.526629E+09 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 23381.84 | 28-JUN-05:02 | 21929.59 | 17-JUN-05:01 | 9174.50 | 29-JUN-05:45 | 5077.63 | 28-JUN-05:02 | 0.00 | 01-JUN-00:10 |
July | 0.112772E+11 | 0.276196E+10 | 299.82 | 0.902515E+10 | 0.225201E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:05 | 26740.56 | 22-JUL-05:01 | 22524.09 | 03-JUL-05:01 | 15988.01 | 21-JUL-05:05 | 5724.81 | 30-JUL-17:23 | 0.00 | 01-JUL-00:05 |
August | 0.104946E+11 | 0.256361E+10 | 318.97 | 0.883909E+10 | 0.165549E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 25839.92 | 03-AUG-05:01 | 22082.88 | 24-AUG-05:01 | 12718.99 | 02-AUG-05:09 | 5497.68 | 03-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.845843E+10 | 0.203801E+10 | 278.03 | 0.719607E+10 | 0.126236E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 25198.89 | 22-SEP-05:01 | 22304.89 | 04-SEP-17:25 | 12822.59 | 22-SEP-05:09 | 5548.06 | 04-SEP-17:25 | 0.00 | 01-SEP-00:10 |
October | 0.336211E+10 | 0.804300E+09 | 184.42 | 0.298211E+10 | 0.380007E+09 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 23765.26 | 04-OCT-05:02 | 21766.94 | 02-OCT-05:01 | 10766.64 | 04-OCT-05:03 | 5148.97 | 04-OCT-05:02 | 0.00 | 01-OCT-00:10 |
November | 0.212301E+09 | 52011697.40 | 32.08 | 0.209112E+09 | 3188747.11 | 0.00 | 0.51 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 | 4997.04 | 03-NOV-16:00 | 4997.04 | 03-NOV-16:00 | 258.26 | 03-NOV-13:00 | 1187.78 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.527873E+11 | 0.130384E+11 | 1913.33 | 0.464604E+11 | 0.632684E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.112772E+11 | 0.276196E+10 | 318.97 | 0.914963E+10 | 0.225201E+10 | 0.00 | 1.00 | 0.00 | 26740.56 | 22524.09 | 15988.01 | 5724.81 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.226139E+10 | 0.614982E+09 | 86.38 | 0.225924E+10 | 2149892.30 | 0.00 | 1.00 | 21-APR-17:10 | 0.00 | 01-APR-00:10 | 64207.73 | 30-APR-10:15 | 64145.83 | 30-APR-10:15 | 320.40 | 29-APR-10:30 | 14899.58 | 30-APR-11:51 | 0.00 | 01-APR-00:10 |
May | 0.132286E+11 | 0.352327E+10 | 264.75 | 0.128580E+11 | 0.370592E+09 | 0.00 | 1.00 | 06-MAY-18:15 | 0.00 | 01-MAY-00:10 | 71699.25 | 28-MAY-08:55 | 63715.00 | 29-MAY-20:05 | 20230.23 | 28-MAY-08:55 | 16707.37 | 19-MAY-17:06 | 0.00 | 01-MAY-00:10 |
June | 0.270683E+11 | 0.740664E+10 | 401.95 | 0.261306E+11 | 0.937693E+09 | 0.00 | 1.00 | 01-JUN-14:50 | 0.00 | 01-JUN-00:10 | 74802.10 | 19-JUN-18:00 | 65217.65 | 26-JUN-22:31 | 27434.34 | 19-JUN-18:00 | 17504.52 | 18-JUN-16:03 | 0.00 | 01-JUN-00:10 |
July | 0.307325E+11 | 0.798575E+10 | 417.64 | 0.258291E+11 | 0.490337E+10 | 0.00 | 1.00 | 01-JUL-17:06 | 0.00 | 01-JUL-00:05 | 79515.70 | 21-JUL-21:15 | 65332.97 | 04-JUL-16:41 | 38693.53 | 21-JUL-21:15 | 17942.45 | 02-JUL-16:03 | 0.00 | 01-JUL-00:05 |
August | 0.251779E+11 | 0.655452E+10 | 373.04 | 0.222910E+11 | 0.288693E+10 | 0.00 | 1.00 | 01-AUG-00:41 | 0.00 | 01-AUG-00:15 | 76557.15 | 01-AUG-21:25 | 65567.12 | 24-AUG-01:55 | 34803.94 | 01-AUG-21:25 | 17446.10 | 06-AUG-15:23 | 0.00 | 01-AUG-00:10 |
September | 0.178830E+11 | 0.456840E+10 | 275.58 | 0.155929E+11 | 0.229009E+10 | 0.00 | 1.00 | 01-SEP-17:06 | 0.00 | 01-SEP-00:10 | 75042.83 | 03-SEP-08:42 | 64990.24 | 10-SEP-20:15 | 31455.57 | 03-SEP-07:45 | 16631.11 | 10-SEP-10:30 | 0.00 | 01-SEP-00:10 |
October | 0.311118E+10 | 0.801660E+09 | 79.25 | 0.273306E+10 | 0.378129E+09 | 0.00 | 1.00 | 01-OCT-09:45 | 0.00 | 01-OCT-00:10 | 70809.10 | 08-OCT-13:25 | 64754.74 | 22-OCT-13:35 | 16074.90 | 08-OCT-13:25 | 15983.12 | 08-OCT-15:33 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.119463E+12 | 0.314552E+11 | 1898.60 | 0.107694E+12 | 0.117690E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.307325E+11 | 0.798575E+10 | 417.64 | 0.261306E+11 | 0.490337E+10 | 0.00 | 1.00 | 0.00 | 79515.70 | 65567.12 | 38693.53 | 17942.45 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.77 | 39.33 | 30.44 | 85.80 | 95.86 | 0.00 | 0.00 | 0.00 |
February | 78.52 | 41.66 | 36.86 | 102.79 | 85.07 | 0.00 | 0.00 | 0.00 |
March | 107.12 | 57.40 | 49.71 | 149.36 | 76.54 | 0.00 | 0.00 | 0.00 |
April | 122.98 | 66.33 | 56.65 | 187.67 | 55.97 | 0.00 | 0.00 | 0.00 |
May | 132.45 | 70.77 | 61.67 | 218.81 | 41.73 | 0.00 | 0.00 | 0.00 |
June | 129.25 | 69.46 | 59.79 | 237.09 | 25.29 | 0.00 | 0.00 | 0.00 |
July | 114.79 | 57.10 | 57.69 | 209.59 | 22.46 | 0.00 | 0.00 | 0.00 |
August | 110.91 | 56.45 | 54.46 | 195.46 | 29.44 | 0.00 | 0.00 | 0.00 |
September | 113.74 | 63.45 | 50.29 | 191.35 | 51.47 | 0.00 | 0.00 | 0.00 |
October | 97.68 | 56.99 | 40.69 | 144.79 | 70.88 | 0.00 | 0.00 | 0.00 |
November | 81.45 | 49.39 | 32.06 | 105.38 | 95.34 | 0.00 | 0.00 | 0.00 |
December | 66.09 | 35.90 | 30.19 | 76.74 | 109.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 102.15 | 55.39 | 46.76 | 158.96 | 63.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.09 | 35.90 | 30.19 | 76.74 | 22.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.45 | 70.77 | 61.67 | 237.09 | 109.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.77 | 39.33 | 30.44 | 85.80 | 95.86 | 0.00 | 0.00 | 0.00 |
February | 78.52 | 41.66 | 36.86 | 102.79 | 85.07 | 0.00 | 0.00 | 0.00 |
March | 107.12 | 57.40 | 49.71 | 149.36 | 76.54 | 0.00 | 0.00 | 0.00 |
April | 122.98 | 66.33 | 56.65 | 187.67 | 55.97 | 0.00 | 0.00 | 0.00 |
May | 132.45 | 70.77 | 61.67 | 218.81 | 41.73 | 0.00 | 0.00 | 0.00 |
June | 129.25 | 69.46 | 59.79 | 237.09 | 25.29 | 0.00 | 0.00 | 0.00 |
July | 114.79 | 57.10 | 57.69 | 209.59 | 22.46 | 0.00 | 0.00 | 0.00 |
August | 110.91 | 56.45 | 54.46 | 195.46 | 29.44 | 0.00 | 0.00 | 0.00 |
September | 113.74 | 63.45 | 50.29 | 191.35 | 51.47 | 0.00 | 0.00 | 0.00 |
October | 97.68 | 56.99 | 40.69 | 144.79 | 70.88 | 0.00 | 0.00 | 0.00 |
November | 81.45 | 49.39 | 32.06 | 105.38 | 95.34 | 0.00 | 0.00 | 0.00 |
December | 66.09 | 35.90 | 30.19 | 76.74 | 109.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 102.15 | 55.39 | 46.76 | 158.96 | 63.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.09 | 35.90 | 30.19 | 76.74 | 22.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.45 | 70.77 | 61.67 | 237.09 | 109.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.43 | 0.00 | 14.43 | 5.70 | 58.52 | 0.00 | 0.00 | 0.00 |
February | 17.62 | 0.00 | 17.62 | 11.67 | 51.36 | 0.00 | 0.00 | 0.00 |
March | 23.07 | 0.00 | 23.07 | 19.97 | 45.90 | 0.00 | 0.00 | 0.00 |
April | 26.72 | 0.29 | 26.43 | 30.74 | 32.35 | 0.00 | 0.00 | 0.00 |
May | 31.63 | 2.33 | 29.30 | 47.99 | 22.90 | 0.00 | 0.00 | 0.00 |
June | 33.51 | 4.06 | 29.45 | 65.74 | 14.05 | 0.00 | 0.00 | 0.00 |
July | 30.91 | 2.88 | 28.02 | 59.38 | 12.54 | 0.00 | 0.00 | 0.00 |
August | 26.33 | 0.68 | 25.65 | 45.97 | 16.53 | 0.00 | 0.00 | 0.00 |
September | 22.86 | 0.02 | 22.84 | 34.55 | 30.03 | 0.00 | 0.00 | 0.00 |
October | 18.96 | 0.00 | 18.96 | 17.81 | 42.38 | 0.00 | 0.00 | 0.00 |
November | 15.31 | 0.00 | 15.31 | 6.33 | 58.37 | 0.00 | 0.00 | 0.00 |
December | 14.32 | 0.00 | 14.32 | 3.98 | 67.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.00 | 0.86 | 22.14 | 29.24 | 37.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.32 | 0.00 | 14.32 | 3.98 | 12.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.51 | 4.06 | 29.45 | 65.74 | 67.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.43 | 0.00 | 14.43 | 5.70 | 58.52 | 0.00 | 0.00 | 0.00 |
February | 17.62 | 0.00 | 17.62 | 11.67 | 51.36 | 0.00 | 0.00 | 0.00 |
March | 23.07 | 0.00 | 23.06 | 19.97 | 45.90 | 0.00 | 0.00 | 0.00 |
April | 26.72 | 0.29 | 26.43 | 30.74 | 32.35 | 0.00 | 0.00 | 0.00 |
May | 31.63 | 2.33 | 29.30 | 47.99 | 22.90 | 0.00 | 0.00 | 0.00 |
June | 33.51 | 4.06 | 29.45 | 65.74 | 14.05 | 0.00 | 0.00 | 0.00 |
July | 30.91 | 2.88 | 28.02 | 59.38 | 12.54 | 0.00 | 0.00 | 0.00 |
August | 26.33 | 0.68 | 25.65 | 45.97 | 16.53 | 0.00 | 0.00 | 0.00 |
September | 22.86 | 0.02 | 22.84 | 34.55 | 30.03 | 0.00 | 0.00 | 0.00 |
October | 18.96 | 0.00 | 18.96 | 17.81 | 42.38 | 0.00 | 0.00 | 0.00 |
November | 15.30 | 0.00 | 15.30 | 6.33 | 58.37 | 0.00 | 0.00 | 0.00 |
December | 14.32 | 0.00 | 14.32 | 3.98 | 67.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.00 | 0.86 | 22.14 | 29.24 | 37.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.32 | 0.00 | 14.32 | 3.98 | 12.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.51 | 4.06 | 29.45 | 65.74 | 67.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.93 | 29.75 | 13.18 | 49.68 | 36.01 | 0.00 | 0.00 | 0.00 |
February | 56.07 | 39.53 | 16.54 | 66.82 | 33.97 | 0.00 | 0.00 | 0.00 |
March | 79.63 | 56.43 | 23.20 | 97.97 | 32.22 | 0.00 | 0.00 | 0.00 |
April | 99.86 | 74.48 | 25.38 | 125.71 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 110.48 | 82.66 | 27.83 | 143.23 | 23.80 | 0.00 | 0.00 | 0.00 |
June | 117.04 | 91.34 | 25.70 | 157.77 | 16.64 | 0.00 | 0.00 | 0.00 |
July | 101.07 | 73.44 | 27.64 | 137.58 | 13.38 | 0.00 | 0.00 | 0.00 |
August | 94.34 | 68.53 | 25.81 | 126.26 | 16.53 | 0.00 | 0.00 | 0.00 |
September | 85.78 | 64.41 | 21.37 | 112.76 | 24.89 | 0.00 | 0.00 | 0.00 |
October | 63.82 | 46.33 | 17.49 | 78.94 | 30.72 | 0.00 | 0.00 | 0.00 |
November | 48.96 | 36.07 | 12.89 | 56.60 | 37.56 | 0.00 | 0.00 | 0.00 |
December | 39.49 | 25.82 | 13.67 | 43.32 | 41.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.37 | 57.45 | 20.92 | 99.84 | 27.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.49 | 25.82 | 12.89 | 43.32 | 13.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.04 | 91.34 | 27.83 | 157.77 | 41.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.93 | 29.75 | 13.18 | 49.68 | 36.01 | 0.00 | 0.00 | 0.00 |
February | 56.07 | 39.53 | 16.54 | 66.82 | 33.97 | 0.00 | 0.00 | 0.00 |
March | 79.63 | 56.43 | 23.20 | 97.97 | 32.22 | 0.00 | 0.00 | 0.00 |
April | 99.86 | 74.48 | 25.38 | 125.71 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 110.48 | 82.66 | 27.83 | 143.23 | 23.80 | 0.00 | 0.00 | 0.00 |
June | 117.04 | 91.34 | 25.70 | 157.77 | 16.64 | 0.00 | 0.00 | 0.00 |
July | 101.07 | 73.44 | 27.64 | 137.58 | 13.38 | 0.00 | 0.00 | 0.00 |
August | 94.34 | 68.53 | 25.81 | 126.26 | 16.53 | 0.00 | 0.00 | 0.00 |
September | 85.78 | 64.41 | 21.37 | 112.76 | 24.89 | 0.00 | 0.00 | 0.00 |
October | 63.82 | 46.33 | 17.49 | 78.94 | 30.72 | 0.00 | 0.00 | 0.00 |
November | 48.96 | 36.07 | 12.89 | 56.60 | 37.56 | 0.00 | 0.00 | 0.00 |
December | 39.49 | 25.82 | 13.67 | 43.32 | 41.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.37 | 57.45 | 20.92 | 99.84 | 27.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.49 | 25.82 | 12.89 | 43.32 | 13.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.04 | 91.34 | 27.83 | 157.77 | 41.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.93 | 29.75 | 13.18 | 49.68 | 36.01 | 0.00 | 0.00 | 0.00 |
February | 56.07 | 39.53 | 16.54 | 66.82 | 33.97 | 0.00 | 0.00 | 0.00 |
March | 79.63 | 56.43 | 23.20 | 97.97 | 32.22 | 0.00 | 0.00 | 0.00 |
April | 99.86 | 74.48 | 25.38 | 125.71 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 110.48 | 82.66 | 27.83 | 143.23 | 23.80 | 0.00 | 0.00 | 0.00 |
June | 117.04 | 91.34 | 25.70 | 157.77 | 16.64 | 0.00 | 0.00 | 0.00 |
July | 101.07 | 73.44 | 27.64 | 137.58 | 13.38 | 0.00 | 0.00 | 0.00 |
August | 94.34 | 68.53 | 25.81 | 126.26 | 16.53 | 0.00 | 0.00 | 0.00 |
September | 85.78 | 64.41 | 21.37 | 112.76 | 24.89 | 0.00 | 0.00 | 0.00 |
October | 63.82 | 46.33 | 17.49 | 78.94 | 30.72 | 0.00 | 0.00 | 0.00 |
November | 48.96 | 36.07 | 12.89 | 56.60 | 37.56 | 0.00 | 0.00 | 0.00 |
December | 39.49 | 25.82 | 13.67 | 43.32 | 41.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.37 | 57.45 | 20.92 | 99.84 | 27.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.49 | 25.82 | 12.89 | 43.32 | 13.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.04 | 91.34 | 27.83 | 157.77 | 41.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.93 | 29.75 | 13.18 | 49.68 | 36.01 | 0.00 | 0.00 | 0.00 |
February | 56.07 | 39.53 | 16.54 | 66.82 | 33.97 | 0.00 | 0.00 | 0.00 |
March | 79.63 | 56.43 | 23.20 | 97.97 | 32.22 | 0.00 | 0.00 | 0.00 |
April | 99.86 | 74.48 | 25.38 | 125.71 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 110.48 | 82.66 | 27.83 | 143.23 | 23.80 | 0.00 | 0.00 | 0.00 |
June | 117.04 | 91.34 | 25.70 | 157.77 | 16.64 | 0.00 | 0.00 | 0.00 |
July | 101.07 | 73.44 | 27.64 | 137.58 | 13.38 | 0.00 | 0.00 | 0.00 |
August | 94.34 | 68.53 | 25.81 | 126.26 | 16.53 | 0.00 | 0.00 | 0.00 |
September | 85.78 | 64.41 | 21.37 | 112.76 | 24.89 | 0.00 | 0.00 | 0.00 |
October | 63.82 | 46.33 | 17.49 | 78.94 | 30.72 | 0.00 | 0.00 | 0.00 |
November | 48.96 | 36.07 | 12.89 | 56.60 | 37.56 | 0.00 | 0.00 | 0.00 |
December | 39.49 | 25.82 | 13.67 | 43.32 | 41.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.37 | 57.45 | 20.92 | 99.84 | 27.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.49 | 25.82 | 12.89 | 43.32 | 13.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.04 | 91.34 | 27.83 | 157.77 | 41.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.93 | 29.75 | 13.18 | 49.68 | 36.01 | 0.00 | 0.00 | 0.00 |
February | 56.07 | 39.53 | 16.54 | 66.82 | 33.97 | 0.00 | 0.00 | 0.00 |
March | 79.63 | 56.43 | 23.20 | 97.97 | 32.22 | 0.00 | 0.00 | 0.00 |
April | 99.86 | 74.48 | 25.38 | 125.71 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 110.48 | 82.66 | 27.83 | 143.23 | 23.80 | 0.00 | 0.00 | 0.00 |
June | 117.04 | 91.34 | 25.70 | 157.77 | 16.64 | 0.00 | 0.00 | 0.00 |
July | 101.07 | 73.44 | 27.64 | 137.58 | 13.38 | 0.00 | 0.00 | 0.00 |
August | 94.34 | 68.53 | 25.81 | 126.26 | 16.53 | 0.00 | 0.00 | 0.00 |
September | 85.78 | 64.41 | 21.37 | 112.76 | 24.89 | 0.00 | 0.00 | 0.00 |
October | 63.82 | 46.33 | 17.49 | 78.94 | 30.72 | 0.00 | 0.00 | 0.00 |
November | 48.96 | 36.07 | 12.89 | 56.60 | 37.56 | 0.00 | 0.00 | 0.00 |
December | 39.49 | 25.82 | 13.67 | 43.32 | 41.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.37 | 57.45 | 20.92 | 99.84 | 27.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.49 | 25.82 | 12.89 | 43.32 | 13.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.04 | 91.34 | 27.83 | 157.77 | 41.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.93 | 29.75 | 13.18 | 49.68 | 36.01 | 0.00 | 0.00 | 0.00 |
February | 56.07 | 39.53 | 16.54 | 66.82 | 33.97 | 0.00 | 0.00 | 0.00 |
March | 79.63 | 56.43 | 23.20 | 97.97 | 32.22 | 0.00 | 0.00 | 0.00 |
April | 99.86 | 74.48 | 25.38 | 125.71 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 110.48 | 82.66 | 27.83 | 143.23 | 23.80 | 0.00 | 0.00 | 0.00 |
June | 117.04 | 91.34 | 25.70 | 157.77 | 16.64 | 0.00 | 0.00 | 0.00 |
July | 101.07 | 73.44 | 27.64 | 137.58 | 13.38 | 0.00 | 0.00 | 0.00 |
August | 94.34 | 68.53 | 25.81 | 126.26 | 16.53 | 0.00 | 0.00 | 0.00 |
September | 85.78 | 64.41 | 21.37 | 112.76 | 24.89 | 0.00 | 0.00 | 0.00 |
October | 63.82 | 46.33 | 17.49 | 78.94 | 30.72 | 0.00 | 0.00 | 0.00 |
November | 48.96 | 36.07 | 12.89 | 56.60 | 37.56 | 0.00 | 0.00 | 0.00 |
December | 39.49 | 25.82 | 13.67 | 43.32 | 41.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.37 | 57.45 | 20.92 | 99.84 | 27.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.49 | 25.82 | 12.89 | 43.32 | 13.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.04 | 91.34 | 27.83 | 157.77 | 41.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.93 | 29.75 | 13.18 | 49.68 | 36.01 | 0.00 | 0.00 | 0.00 |
February | 56.07 | 39.53 | 16.54 | 66.82 | 33.97 | 0.00 | 0.00 | 0.00 |
March | 79.63 | 56.43 | 23.20 | 97.97 | 32.22 | 0.00 | 0.00 | 0.00 |
April | 99.86 | 74.48 | 25.38 | 125.71 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 110.48 | 82.66 | 27.83 | 143.23 | 23.80 | 0.00 | 0.00 | 0.00 |
June | 117.04 | 91.34 | 25.70 | 157.77 | 16.64 | 0.00 | 0.00 | 0.00 |
July | 101.07 | 73.44 | 27.64 | 137.58 | 13.38 | 0.00 | 0.00 | 0.00 |
August | 94.34 | 68.53 | 25.81 | 126.26 | 16.53 | 0.00 | 0.00 | 0.00 |
September | 85.78 | 64.41 | 21.37 | 112.76 | 24.89 | 0.00 | 0.00 | 0.00 |
October | 63.82 | 46.33 | 17.49 | 78.94 | 30.72 | 0.00 | 0.00 | 0.00 |
November | 48.96 | 36.07 | 12.89 | 56.60 | 37.56 | 0.00 | 0.00 | 0.00 |
December | 39.49 | 25.82 | 13.67 | 43.32 | 41.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.37 | 57.45 | 20.92 | 99.84 | 27.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.49 | 25.82 | 12.89 | 43.32 | 13.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.04 | 91.34 | 27.83 | 157.77 | 41.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.93 | 29.75 | 13.18 | 49.68 | 36.01 | 0.00 | 0.00 | 0.00 |
February | 56.07 | 39.53 | 16.54 | 66.82 | 33.97 | 0.00 | 0.00 | 0.00 |
March | 79.63 | 56.43 | 23.20 | 97.97 | 32.22 | 0.00 | 0.00 | 0.00 |
April | 99.86 | 74.48 | 25.38 | 125.71 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 110.48 | 82.66 | 27.83 | 143.23 | 23.80 | 0.00 | 0.00 | 0.00 |
June | 117.04 | 91.34 | 25.70 | 157.77 | 16.64 | 0.00 | 0.00 | 0.00 |
July | 101.07 | 73.44 | 27.64 | 137.58 | 13.38 | 0.00 | 0.00 | 0.00 |
August | 94.34 | 68.53 | 25.81 | 126.26 | 16.53 | 0.00 | 0.00 | 0.00 |
September | 85.78 | 64.41 | 21.37 | 112.76 | 24.89 | 0.00 | 0.00 | 0.00 |
October | 63.82 | 46.33 | 17.49 | 78.94 | 30.72 | 0.00 | 0.00 | 0.00 |
November | 48.96 | 36.07 | 12.89 | 56.60 | 37.56 | 0.00 | 0.00 | 0.00 |
December | 39.49 | 25.82 | 13.67 | 43.32 | 41.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.37 | 57.45 | 20.92 | 99.84 | 27.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.49 | 25.82 | 12.89 | 43.32 | 13.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.04 | 91.34 | 27.83 | 157.77 | 41.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.93 | 29.75 | 13.18 | 49.68 | 36.01 | 0.00 | 0.00 | 0.00 |
February | 56.07 | 39.53 | 16.54 | 66.82 | 33.97 | 0.00 | 0.00 | 0.00 |
March | 79.63 | 56.43 | 23.20 | 97.97 | 32.22 | 0.00 | 0.00 | 0.00 |
April | 99.86 | 74.48 | 25.38 | 125.71 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 110.48 | 82.66 | 27.83 | 143.23 | 23.80 | 0.00 | 0.00 | 0.00 |
June | 117.04 | 91.34 | 25.70 | 157.77 | 16.64 | 0.00 | 0.00 | 0.00 |
July | 101.07 | 73.44 | 27.64 | 137.58 | 13.38 | 0.00 | 0.00 | 0.00 |
August | 94.34 | 68.53 | 25.81 | 126.26 | 16.53 | 0.00 | 0.00 | 0.00 |
September | 85.78 | 64.41 | 21.37 | 112.76 | 24.89 | 0.00 | 0.00 | 0.00 |
October | 63.82 | 46.33 | 17.49 | 78.94 | 30.72 | 0.00 | 0.00 | 0.00 |
November | 48.96 | 36.07 | 12.89 | 56.60 | 37.56 | 0.00 | 0.00 | 0.00 |
December | 39.49 | 25.82 | 13.67 | 43.32 | 41.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.37 | 57.45 | 20.92 | 99.84 | 27.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.49 | 25.82 | 12.89 | 43.32 | 13.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.04 | 91.34 | 27.83 | 157.77 | 41.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.93 | 29.75 | 13.18 | 49.68 | 36.01 | 0.00 | 0.00 | 0.00 |
February | 56.07 | 39.53 | 16.54 | 66.82 | 33.97 | 0.00 | 0.00 | 0.00 |
March | 79.63 | 56.43 | 23.20 | 97.97 | 32.22 | 0.00 | 0.00 | 0.00 |
April | 99.86 | 74.48 | 25.38 | 125.71 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 110.48 | 82.66 | 27.83 | 143.23 | 23.80 | 0.00 | 0.00 | 0.00 |
June | 117.04 | 91.34 | 25.70 | 157.77 | 16.64 | 0.00 | 0.00 | 0.00 |
July | 101.07 | 73.44 | 27.64 | 137.58 | 13.38 | 0.00 | 0.00 | 0.00 |
August | 94.34 | 68.53 | 25.81 | 126.26 | 16.53 | 0.00 | 0.00 | 0.00 |
September | 85.78 | 64.41 | 21.37 | 112.76 | 24.89 | 0.00 | 0.00 | 0.00 |
October | 63.82 | 46.33 | 17.49 | 78.94 | 30.72 | 0.00 | 0.00 | 0.00 |
November | 48.96 | 36.07 | 12.89 | 56.60 | 37.56 | 0.00 | 0.00 | 0.00 |
December | 39.49 | 25.82 | 13.67 | 43.32 | 41.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.37 | 57.45 | 20.92 | 99.84 | 27.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.49 | 25.82 | 12.89 | 43.32 | 13.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.04 | 91.34 | 27.83 | 157.77 | 41.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.93 | 29.75 | 13.18 | 49.68 | 36.01 | 0.00 | 0.00 | 0.00 |
February | 56.07 | 39.53 | 16.54 | 66.82 | 33.97 | 0.00 | 0.00 | 0.00 |
March | 79.63 | 56.43 | 23.20 | 97.97 | 32.22 | 0.00 | 0.00 | 0.00 |
April | 99.86 | 74.48 | 25.38 | 125.71 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 110.48 | 82.66 | 27.83 | 143.23 | 23.80 | 0.00 | 0.00 | 0.00 |
June | 117.04 | 91.34 | 25.70 | 157.77 | 16.64 | 0.00 | 0.00 | 0.00 |
July | 101.07 | 73.44 | 27.64 | 137.58 | 13.38 | 0.00 | 0.00 | 0.00 |
August | 94.34 | 68.53 | 25.81 | 126.26 | 16.53 | 0.00 | 0.00 | 0.00 |
September | 85.78 | 64.41 | 21.37 | 112.76 | 24.89 | 0.00 | 0.00 | 0.00 |
October | 63.82 | 46.33 | 17.49 | 78.94 | 30.72 | 0.00 | 0.00 | 0.00 |
November | 48.96 | 36.07 | 12.89 | 56.60 | 37.56 | 0.00 | 0.00 | 0.00 |
December | 39.49 | 25.82 | 13.67 | 43.32 | 41.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.37 | 57.45 | 20.92 | 99.84 | 27.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.49 | 25.82 | 12.89 | 43.32 | 13.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.04 | 91.34 | 27.83 | 157.77 | 41.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.93 | 29.75 | 13.18 | 49.68 | 36.01 | 0.00 | 0.00 | 0.00 |
February | 56.07 | 39.53 | 16.54 | 66.82 | 33.97 | 0.00 | 0.00 | 0.00 |
March | 79.63 | 56.43 | 23.20 | 97.97 | 32.22 | 0.00 | 0.00 | 0.00 |
April | 99.86 | 74.48 | 25.38 | 125.71 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 110.48 | 82.66 | 27.83 | 143.23 | 23.80 | 0.00 | 0.00 | 0.00 |
June | 117.04 | 91.34 | 25.70 | 157.77 | 16.64 | 0.00 | 0.00 | 0.00 |
July | 101.07 | 73.44 | 27.64 | 137.58 | 13.38 | 0.00 | 0.00 | 0.00 |
August | 94.34 | 68.53 | 25.81 | 126.26 | 16.53 | 0.00 | 0.00 | 0.00 |
September | 85.78 | 64.41 | 21.37 | 112.76 | 24.89 | 0.00 | 0.00 | 0.00 |
October | 63.82 | 46.33 | 17.49 | 78.94 | 30.72 | 0.00 | 0.00 | 0.00 |
November | 48.96 | 36.07 | 12.89 | 56.60 | 37.56 | 0.00 | 0.00 | 0.00 |
December | 39.49 | 25.82 | 13.67 | 43.32 | 41.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.37 | 57.45 | 20.92 | 99.84 | 27.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.49 | 25.82 | 12.89 | 43.32 | 13.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.04 | 91.34 | 27.83 | 157.77 | 41.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.93 | 29.75 | 13.18 | 49.68 | 36.01 | 0.00 | 0.00 | 0.00 |
February | 56.07 | 39.53 | 16.54 | 66.82 | 33.97 | 0.00 | 0.00 | 0.00 |
March | 79.63 | 56.43 | 23.20 | 97.97 | 32.22 | 0.00 | 0.00 | 0.00 |
April | 99.86 | 74.48 | 25.38 | 125.71 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 110.48 | 82.66 | 27.83 | 143.23 | 23.80 | 0.00 | 0.00 | 0.00 |
June | 117.04 | 91.34 | 25.70 | 157.77 | 16.64 | 0.00 | 0.00 | 0.00 |
July | 101.07 | 73.44 | 27.64 | 137.58 | 13.38 | 0.00 | 0.00 | 0.00 |
August | 94.34 | 68.53 | 25.81 | 126.26 | 16.53 | 0.00 | 0.00 | 0.00 |
September | 85.78 | 64.41 | 21.37 | 112.76 | 24.89 | 0.00 | 0.00 | 0.00 |
October | 63.82 | 46.33 | 17.49 | 78.94 | 30.72 | 0.00 | 0.00 | 0.00 |
November | 48.96 | 36.07 | 12.89 | 56.60 | 37.56 | 0.00 | 0.00 | 0.00 |
December | 39.49 | 25.82 | 13.67 | 43.32 | 41.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.37 | 57.45 | 20.92 | 99.84 | 27.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.49 | 25.82 | 12.89 | 43.32 | 13.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.04 | 91.34 | 27.83 | 157.77 | 41.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.93 | 29.75 | 13.18 | 49.68 | 36.01 | 0.00 | 0.00 | 0.00 |
February | 56.07 | 39.53 | 16.54 | 66.82 | 33.97 | 0.00 | 0.00 | 0.00 |
March | 79.63 | 56.43 | 23.20 | 97.97 | 32.22 | 0.00 | 0.00 | 0.00 |
April | 99.86 | 74.48 | 25.38 | 125.71 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 110.48 | 82.66 | 27.83 | 143.23 | 23.80 | 0.00 | 0.00 | 0.00 |
June | 117.04 | 91.34 | 25.70 | 157.77 | 16.64 | 0.00 | 0.00 | 0.00 |
July | 101.07 | 73.44 | 27.64 | 137.58 | 13.38 | 0.00 | 0.00 | 0.00 |
August | 94.34 | 68.53 | 25.81 | 126.26 | 16.53 | 0.00 | 0.00 | 0.00 |
September | 85.78 | 64.41 | 21.37 | 112.76 | 24.89 | 0.00 | 0.00 | 0.00 |
October | 63.82 | 46.33 | 17.49 | 78.94 | 30.72 | 0.00 | 0.00 | 0.00 |
November | 48.96 | 36.07 | 12.89 | 56.60 | 37.56 | 0.00 | 0.00 | 0.00 |
December | 39.49 | 25.82 | 13.67 | 43.32 | 41.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.37 | 57.45 | 20.92 | 99.84 | 27.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.49 | 25.82 | 12.89 | 43.32 | 13.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.04 | 91.34 | 27.83 | 157.77 | 41.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 88.89 | 62.70 | 1.50 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 116.71 | 60.33 | 7.33 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 164.72 | 62.70 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 207.59 | 57.43 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 230.47 | 56.54 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 249.57 | 46.25 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 218.24 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 201.09 | 44.69 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 181.87 | 59.72 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 130.87 | 64.78 | 0.17 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 97.98 | 72.67 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 80.01 | 70.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 164.17 | 57.95 | 9.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 80.01 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 249.57 | 72.67 | 7.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186862E+09 | 0.105330E+09 | 81531223.12 | 0.229815E+09 | 0.256745E+09 |
February | 0.189951E+09 | 0.100776E+09 | 89174474.56 | 0.248669E+09 | 0.205791E+09 |
March | 0.286902E+09 | 0.153748E+09 | 0.133155E+09 | 0.400040E+09 | 0.205008E+09 |
April | 0.318756E+09 | 0.171921E+09 | 0.146835E+09 | 0.486435E+09 | 0.145065E+09 |
May | 0.354743E+09 | 0.189558E+09 | 0.165186E+09 | 0.586048E+09 | 0.111768E+09 |
June | 0.335014E+09 | 0.180051E+09 | 0.154963E+09 | 0.614535E+09 | 65542552.78 |
July | 0.307442E+09 | 0.152935E+09 | 0.154508E+09 | 0.561372E+09 | 60151149.56 |
August | 0.297050E+09 | 0.151193E+09 | 0.145858E+09 | 0.523533E+09 | 78863310.63 |
September | 0.294810E+09 | 0.164463E+09 | 0.130346E+09 | 0.495982E+09 | 0.133415E+09 |
October | 0.261623E+09 | 0.152639E+09 | 0.108984E+09 | 0.387797E+09 | 0.189847E+09 |
November | 0.211128E+09 | 0.128023E+09 | 83105568.41 | 0.273136E+09 | 0.247112E+09 |
December | 0.177016E+09 | 96155759.73 | 80860322.06 | 0.205545E+09 | 0.293242E+09 |
Annual Sum or Average | 0.322130E+10 | 0.174679E+10 | 0.147451E+10 | 0.501291E+10 | 0.199255E+10 |
Minimum of Months | 0.177016E+09 | 96155759.73 | 80860322.06 | 0.205545E+09 | 60151149.56 |
Maximum of Months | 0.354743E+09 | 0.189558E+09 | 0.165186E+09 | 0.614535E+09 | 0.293242E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186862E+09 | 0.105330E+09 | 81531223.12 | 0.229815E+09 | 0.256745E+09 |
February | 0.189951E+09 | 0.100776E+09 | 89174474.56 | 0.248669E+09 | 0.205791E+09 |
March | 0.286902E+09 | 0.153748E+09 | 0.133155E+09 | 0.400040E+09 | 0.205008E+09 |
April | 0.318756E+09 | 0.171921E+09 | 0.146835E+09 | 0.486435E+09 | 0.145065E+09 |
May | 0.354743E+09 | 0.189558E+09 | 0.165186E+09 | 0.586048E+09 | 0.111768E+09 |
June | 0.335014E+09 | 0.180051E+09 | 0.154963E+09 | 0.614535E+09 | 65542552.78 |
July | 0.307442E+09 | 0.152935E+09 | 0.154508E+09 | 0.561372E+09 | 60151149.56 |
August | 0.297050E+09 | 0.151193E+09 | 0.145858E+09 | 0.523533E+09 | 78863310.63 |
September | 0.294810E+09 | 0.164463E+09 | 0.130346E+09 | 0.495982E+09 | 0.133415E+09 |
October | 0.261623E+09 | 0.152639E+09 | 0.108984E+09 | 0.387797E+09 | 0.189847E+09 |
November | 0.211128E+09 | 0.128023E+09 | 83105568.41 | 0.273136E+09 | 0.247112E+09 |
December | 0.177016E+09 | 96155759.73 | 80860322.06 | 0.205545E+09 | 0.293242E+09 |
Annual Sum or Average | 0.322130E+10 | 0.174679E+10 | 0.147451E+10 | 0.501291E+10 | 0.199255E+10 |
Minimum of Months | 0.177016E+09 | 96155759.73 | 80860322.06 | 0.205545E+09 | 60151149.56 |
Maximum of Months | 0.354743E+09 | 0.189558E+09 | 0.165186E+09 | 0.614535E+09 | 0.293242E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38650826.57 | 0.00 | 38650826.57 | 15269775.43 | 0.156744E+09 |
February | 42629329.24 | 0.00 | 42629329.24 | 28242586.20 | 0.124260E+09 |
March | 61785000.29 | 6925.16 | 61778075.14 | 53491424.21 | 0.122929E+09 |
April | 69251959.12 | 748395.50 | 68503563.62 | 79690644.89 | 83858066.85 |
May | 84714655.88 | 6242423.55 | 78472232.32 | 0.128535E+09 | 61334181.89 |
June | 86858169.44 | 10533716.25 | 76324453.19 | 0.170397E+09 | 36422291.81 |
July | 82784501.55 | 7722763.83 | 75061737.72 | 0.159045E+09 | 33590625.71 |
August | 70531133.29 | 1817921.11 | 68713212.18 | 0.123127E+09 | 44276328.22 |
September | 59249700.15 | 55765.71 | 59193934.44 | 89544972.34 | 77830120.61 |
October | 50778777.08 | 0.00 | 50778777.08 | 47696307.18 | 0.113514E+09 |
November | 39671081.77 | 0.00 | 39671081.77 | 16403248.82 | 0.151302E+09 |
December | 38351488.79 | 0.00 | 38351488.79 | 10648332.91 | 0.179976E+09 |
Annual Sum or Average | 0.725257E+09 | 27127911.12 | 0.698129E+09 | 0.922091E+09 | 0.118604E+10 |
Minimum of Months | 38351488.79 | 0.00 | 38351488.79 | 10648332.91 | 33590625.71 |
Maximum of Months | 86858169.44 | 10533716.25 | 78472232.32 | 0.170397E+09 | 0.179976E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38649788.77 | 0.00 | 38649788.77 | 15268996.64 | 0.156743E+09 |
February | 42628207.63 | 0.00 | 42628207.63 | 28241694.59 | 0.124259E+09 |
March | 61783405.35 | 6924.83 | 61776480.52 | 53489828.26 | 0.122927E+09 |
April | 69250255.87 | 748360.42 | 68501895.45 | 79689059.85 | 83857166.43 |
May | 84712419.12 | 6242130.96 | 78470288.15 | 0.128532E+09 | 61333148.48 |
June | 86855859.48 | 10533222.52 | 76322636.95 | 0.170394E+09 | 36421496.88 |
July | 82782208.32 | 7722401.86 | 75059806.46 | 0.159042E+09 | 33589991.59 |
August | 70529311.95 | 1817835.90 | 68711476.05 | 0.123125E+09 | 44275635.34 |
September | 59248266.05 | 55763.10 | 59192502.95 | 89543485.29 | 77829179.48 |
October | 50777470.78 | 0.00 | 50777470.78 | 47695018.03 | 0.113513E+09 |
November | 39670069.84 | 0.00 | 39670069.84 | 16402636.80 | 0.151301E+09 |
December | 38350424.67 | 0.00 | 38350424.67 | 10647733.22 | 0.179975E+09 |
Annual Sum or Average | 0.725238E+09 | 27126639.59 | 0.698111E+09 | 0.922071E+09 | 0.118602E+10 |
Minimum of Months | 38350424.67 | 0.00 | 38350424.67 | 10647733.22 | 33589991.59 |
Maximum of Months | 86855859.48 | 10533222.52 | 78470288.15 | 0.170394E+09 | 0.179975E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114980E+09 | 79691597.10 | 35288321.31 | 0.133061E+09 | 96439629.94 |
February | 0.135645E+09 | 95634890.70 | 40009855.64 | 0.161662E+09 | 82181003.80 |
March | 0.213277E+09 | 0.151139E+09 | 62138279.22 | 0.262397E+09 | 86293291.31 |
April | 0.258830E+09 | 0.193052E+09 | 65777733.02 | 0.325845E+09 | 71867170.23 |
May | 0.295923E+09 | 0.221396E+09 | 74526710.24 | 0.383634E+09 | 63757245.43 |
June | 0.303369E+09 | 0.236766E+09 | 66603153.22 | 0.408931E+09 | 43120416.82 |
July | 0.270718E+09 | 0.196699E+09 | 74018387.01 | 0.368500E+09 | 35827273.67 |
August | 0.252690E+09 | 0.183556E+09 | 69134362.96 | 0.338172E+09 | 44283134.82 |
September | 0.222346E+09 | 0.166952E+09 | 55393203.54 | 0.292271E+09 | 64506366.84 |
October | 0.170938E+09 | 0.124085E+09 | 46852902.75 | 0.211433E+09 | 82274355.28 |
November | 0.126909E+09 | 93494860.10 | 33413896.22 | 0.146713E+09 | 97344273.54 |
December | 0.105758E+09 | 69152124.52 | 36605653.01 | 0.116024E+09 | 0.111760E+09 |
Annual Sum or Average | 0.247138E+10 | 0.181162E+10 | 0.659762E+09 | 0.314864E+10 | 0.879654E+09 |
Minimum of Months | 0.105758E+09 | 69152124.52 | 33413896.22 | 0.116024E+09 | 35827273.67 |
Maximum of Months | 0.303369E+09 | 0.236766E+09 | 74526710.24 | 0.408931E+09 | 0.111760E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114980E+09 | 79691597.10 | 35288321.31 | 0.133061E+09 | 96439629.94 |
February | 0.135645E+09 | 95634890.70 | 40009855.64 | 0.161662E+09 | 82181003.80 |
March | 0.213277E+09 | 0.151139E+09 | 62138279.22 | 0.262397E+09 | 86293291.31 |
April | 0.258830E+09 | 0.193052E+09 | 65777733.02 | 0.325845E+09 | 71867170.23 |
May | 0.295923E+09 | 0.221396E+09 | 74526710.24 | 0.383634E+09 | 63757245.43 |
June | 0.303369E+09 | 0.236766E+09 | 66603153.22 | 0.408931E+09 | 43120416.82 |
July | 0.270718E+09 | 0.196699E+09 | 74018387.01 | 0.368500E+09 | 35827273.67 |
August | 0.252690E+09 | 0.183556E+09 | 69134362.96 | 0.338172E+09 | 44283134.82 |
September | 0.222346E+09 | 0.166952E+09 | 55393203.54 | 0.292271E+09 | 64506366.84 |
October | 0.170938E+09 | 0.124085E+09 | 46852902.75 | 0.211433E+09 | 82274355.28 |
November | 0.126909E+09 | 93494860.10 | 33413896.22 | 0.146713E+09 | 97344273.54 |
December | 0.105758E+09 | 69152124.52 | 36605653.01 | 0.116024E+09 | 0.111760E+09 |
Annual Sum or Average | 0.247138E+10 | 0.181162E+10 | 0.659762E+09 | 0.314864E+10 | 0.879654E+09 |
Minimum of Months | 0.105758E+09 | 69152124.52 | 33413896.22 | 0.116024E+09 | 35827273.67 |
Maximum of Months | 0.303369E+09 | 0.236766E+09 | 74526710.24 | 0.408931E+09 | 0.111760E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114980E+09 | 79691597.10 | 35288321.31 | 0.133061E+09 | 96439629.94 |
February | 0.135645E+09 | 95634890.70 | 40009855.64 | 0.161662E+09 | 82181003.80 |
March | 0.213277E+09 | 0.151139E+09 | 62138279.22 | 0.262397E+09 | 86293291.31 |
April | 0.258830E+09 | 0.193052E+09 | 65777733.02 | 0.325845E+09 | 71867170.23 |
May | 0.295923E+09 | 0.221396E+09 | 74526710.24 | 0.383634E+09 | 63757245.43 |
June | 0.303369E+09 | 0.236766E+09 | 66603153.22 | 0.408931E+09 | 43120416.82 |
July | 0.270718E+09 | 0.196699E+09 | 74018387.01 | 0.368500E+09 | 35827273.67 |
August | 0.252690E+09 | 0.183556E+09 | 69134362.96 | 0.338172E+09 | 44283134.82 |
September | 0.222346E+09 | 0.166952E+09 | 55393203.54 | 0.292271E+09 | 64506366.84 |
October | 0.170938E+09 | 0.124085E+09 | 46852902.75 | 0.211433E+09 | 82274355.28 |
November | 0.126909E+09 | 93494860.10 | 33413896.22 | 0.146713E+09 | 97344273.54 |
December | 0.105758E+09 | 69152124.52 | 36605653.01 | 0.116024E+09 | 0.111760E+09 |
Annual Sum or Average | 0.247138E+10 | 0.181162E+10 | 0.659762E+09 | 0.314864E+10 | 0.879654E+09 |
Minimum of Months | 0.105758E+09 | 69152124.52 | 33413896.22 | 0.116024E+09 | 35827273.67 |
Maximum of Months | 0.303369E+09 | 0.236766E+09 | 74526710.24 | 0.408931E+09 | 0.111760E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114980E+09 | 79691597.10 | 35288321.31 | 0.133061E+09 | 96439629.94 |
February | 0.135645E+09 | 95634890.70 | 40009855.64 | 0.161662E+09 | 82181003.80 |
March | 0.213277E+09 | 0.151139E+09 | 62138279.22 | 0.262397E+09 | 86293291.31 |
April | 0.258830E+09 | 0.193052E+09 | 65777733.02 | 0.325845E+09 | 71867170.23 |
May | 0.295923E+09 | 0.221396E+09 | 74526710.24 | 0.383634E+09 | 63757245.43 |
June | 0.303369E+09 | 0.236766E+09 | 66603153.22 | 0.408931E+09 | 43120416.82 |
July | 0.270718E+09 | 0.196699E+09 | 74018387.01 | 0.368500E+09 | 35827273.67 |
August | 0.252690E+09 | 0.183556E+09 | 69134362.96 | 0.338172E+09 | 44283134.82 |
September | 0.222346E+09 | 0.166952E+09 | 55393203.54 | 0.292271E+09 | 64506366.84 |
October | 0.170938E+09 | 0.124085E+09 | 46852902.75 | 0.211433E+09 | 82274355.28 |
November | 0.126909E+09 | 93494860.10 | 33413896.22 | 0.146713E+09 | 97344273.54 |
December | 0.105758E+09 | 69152124.52 | 36605653.01 | 0.116024E+09 | 0.111760E+09 |
Annual Sum or Average | 0.247138E+10 | 0.181162E+10 | 0.659762E+09 | 0.314864E+10 | 0.879654E+09 |
Minimum of Months | 0.105758E+09 | 69152124.52 | 33413896.22 | 0.116024E+09 | 35827273.67 |
Maximum of Months | 0.303369E+09 | 0.236766E+09 | 74526710.24 | 0.408931E+09 | 0.111760E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114980E+09 | 79691597.10 | 35288321.31 | 0.133061E+09 | 96439629.94 |
February | 0.135645E+09 | 95634890.70 | 40009855.64 | 0.161662E+09 | 82181003.80 |
March | 0.213277E+09 | 0.151139E+09 | 62138279.22 | 0.262397E+09 | 86293291.31 |
April | 0.258830E+09 | 0.193052E+09 | 65777733.02 | 0.325845E+09 | 71867170.23 |
May | 0.295923E+09 | 0.221396E+09 | 74526710.24 | 0.383634E+09 | 63757245.43 |
June | 0.303369E+09 | 0.236766E+09 | 66603153.22 | 0.408931E+09 | 43120416.82 |
July | 0.270718E+09 | 0.196699E+09 | 74018387.01 | 0.368500E+09 | 35827273.67 |
August | 0.252690E+09 | 0.183556E+09 | 69134362.96 | 0.338172E+09 | 44283134.82 |
September | 0.222346E+09 | 0.166952E+09 | 55393203.54 | 0.292271E+09 | 64506366.84 |
October | 0.170938E+09 | 0.124085E+09 | 46852902.75 | 0.211433E+09 | 82274355.28 |
November | 0.126909E+09 | 93494860.10 | 33413896.22 | 0.146713E+09 | 97344273.54 |
December | 0.105758E+09 | 69152124.52 | 36605653.01 | 0.116024E+09 | 0.111760E+09 |
Annual Sum or Average | 0.247138E+10 | 0.181162E+10 | 0.659762E+09 | 0.314864E+10 | 0.879654E+09 |
Minimum of Months | 0.105758E+09 | 69152124.52 | 33413896.22 | 0.116024E+09 | 35827273.67 |
Maximum of Months | 0.303369E+09 | 0.236766E+09 | 74526710.24 | 0.408931E+09 | 0.111760E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114980E+09 | 79691597.10 | 35288321.31 | 0.133061E+09 | 96439629.94 |
February | 0.135645E+09 | 95634890.70 | 40009855.64 | 0.161662E+09 | 82181003.80 |
March | 0.213277E+09 | 0.151139E+09 | 62138279.22 | 0.262397E+09 | 86293291.31 |
April | 0.258830E+09 | 0.193052E+09 | 65777733.02 | 0.325845E+09 | 71867170.23 |
May | 0.295923E+09 | 0.221396E+09 | 74526710.24 | 0.383634E+09 | 63757245.43 |
June | 0.303369E+09 | 0.236766E+09 | 66603153.22 | 0.408931E+09 | 43120416.82 |
July | 0.270718E+09 | 0.196699E+09 | 74018387.01 | 0.368500E+09 | 35827273.67 |
August | 0.252690E+09 | 0.183556E+09 | 69134362.96 | 0.338172E+09 | 44283134.82 |
September | 0.222346E+09 | 0.166952E+09 | 55393203.54 | 0.292271E+09 | 64506366.84 |
October | 0.170938E+09 | 0.124085E+09 | 46852902.75 | 0.211433E+09 | 82274355.28 |
November | 0.126909E+09 | 93494860.10 | 33413896.22 | 0.146713E+09 | 97344273.54 |
December | 0.105758E+09 | 69152124.52 | 36605653.01 | 0.116024E+09 | 0.111760E+09 |
Annual Sum or Average | 0.247138E+10 | 0.181162E+10 | 0.659762E+09 | 0.314864E+10 | 0.879654E+09 |
Minimum of Months | 0.105758E+09 | 69152124.52 | 33413896.22 | 0.116024E+09 | 35827273.67 |
Maximum of Months | 0.303369E+09 | 0.236766E+09 | 74526710.24 | 0.408931E+09 | 0.111760E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114980E+09 | 79691597.10 | 35288321.31 | 0.133061E+09 | 96439629.94 |
February | 0.135645E+09 | 95634890.70 | 40009855.64 | 0.161662E+09 | 82181003.80 |
March | 0.213277E+09 | 0.151139E+09 | 62138279.22 | 0.262397E+09 | 86293291.31 |
April | 0.258830E+09 | 0.193052E+09 | 65777733.02 | 0.325845E+09 | 71867170.23 |
May | 0.295923E+09 | 0.221396E+09 | 74526710.24 | 0.383634E+09 | 63757245.43 |
June | 0.303369E+09 | 0.236766E+09 | 66603153.22 | 0.408931E+09 | 43120416.82 |
July | 0.270718E+09 | 0.196699E+09 | 74018387.01 | 0.368500E+09 | 35827273.67 |
August | 0.252690E+09 | 0.183556E+09 | 69134362.96 | 0.338172E+09 | 44283134.82 |
September | 0.222346E+09 | 0.166952E+09 | 55393203.54 | 0.292271E+09 | 64506366.84 |
October | 0.170938E+09 | 0.124085E+09 | 46852902.75 | 0.211433E+09 | 82274355.28 |
November | 0.126909E+09 | 93494860.10 | 33413896.22 | 0.146713E+09 | 97344273.54 |
December | 0.105758E+09 | 69152124.52 | 36605653.01 | 0.116024E+09 | 0.111760E+09 |
Annual Sum or Average | 0.247138E+10 | 0.181162E+10 | 0.659762E+09 | 0.314864E+10 | 0.879654E+09 |
Minimum of Months | 0.105758E+09 | 69152124.52 | 33413896.22 | 0.116024E+09 | 35827273.67 |
Maximum of Months | 0.303369E+09 | 0.236766E+09 | 74526710.24 | 0.408931E+09 | 0.111760E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114980E+09 | 79691597.10 | 35288321.31 | 0.133061E+09 | 96439629.94 |
February | 0.135645E+09 | 95634890.70 | 40009855.64 | 0.161662E+09 | 82181003.80 |
March | 0.213277E+09 | 0.151139E+09 | 62138279.22 | 0.262397E+09 | 86293291.31 |
April | 0.258830E+09 | 0.193052E+09 | 65777733.02 | 0.325845E+09 | 71867170.23 |
May | 0.295923E+09 | 0.221396E+09 | 74526710.24 | 0.383634E+09 | 63757245.43 |
June | 0.303369E+09 | 0.236766E+09 | 66603153.22 | 0.408931E+09 | 43120416.82 |
July | 0.270718E+09 | 0.196699E+09 | 74018387.01 | 0.368500E+09 | 35827273.67 |
August | 0.252690E+09 | 0.183556E+09 | 69134362.96 | 0.338172E+09 | 44283134.82 |
September | 0.222346E+09 | 0.166952E+09 | 55393203.54 | 0.292271E+09 | 64506366.84 |
October | 0.170938E+09 | 0.124085E+09 | 46852902.75 | 0.211433E+09 | 82274355.28 |
November | 0.126909E+09 | 93494860.10 | 33413896.22 | 0.146713E+09 | 97344273.54 |
December | 0.105758E+09 | 69152124.52 | 36605653.01 | 0.116024E+09 | 0.111760E+09 |
Annual Sum or Average | 0.247138E+10 | 0.181162E+10 | 0.659762E+09 | 0.314864E+10 | 0.879654E+09 |
Minimum of Months | 0.105758E+09 | 69152124.52 | 33413896.22 | 0.116024E+09 | 35827273.67 |
Maximum of Months | 0.303369E+09 | 0.236766E+09 | 74526710.24 | 0.408931E+09 | 0.111760E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114980E+09 | 79691597.10 | 35288321.31 | 0.133061E+09 | 96439629.94 |
February | 0.135645E+09 | 95634890.70 | 40009855.64 | 0.161662E+09 | 82181003.80 |
March | 0.213277E+09 | 0.151139E+09 | 62138279.22 | 0.262397E+09 | 86293291.31 |
April | 0.258830E+09 | 0.193052E+09 | 65777733.02 | 0.325845E+09 | 71867170.23 |
May | 0.295923E+09 | 0.221396E+09 | 74526710.24 | 0.383634E+09 | 63757245.43 |
June | 0.303369E+09 | 0.236766E+09 | 66603153.22 | 0.408931E+09 | 43120416.82 |
July | 0.270718E+09 | 0.196699E+09 | 74018387.01 | 0.368500E+09 | 35827273.67 |
August | 0.252690E+09 | 0.183556E+09 | 69134362.96 | 0.338172E+09 | 44283134.82 |
September | 0.222346E+09 | 0.166952E+09 | 55393203.54 | 0.292271E+09 | 64506366.84 |
October | 0.170938E+09 | 0.124085E+09 | 46852902.75 | 0.211433E+09 | 82274355.28 |
November | 0.126909E+09 | 93494860.10 | 33413896.22 | 0.146713E+09 | 97344273.54 |
December | 0.105758E+09 | 69152124.52 | 36605653.01 | 0.116024E+09 | 0.111760E+09 |
Annual Sum or Average | 0.247138E+10 | 0.181162E+10 | 0.659762E+09 | 0.314864E+10 | 0.879654E+09 |
Minimum of Months | 0.105758E+09 | 69152124.52 | 33413896.22 | 0.116024E+09 | 35827273.67 |
Maximum of Months | 0.303369E+09 | 0.236766E+09 | 74526710.24 | 0.408931E+09 | 0.111760E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114980E+09 | 79691597.10 | 35288321.31 | 0.133061E+09 | 96439629.94 |
February | 0.135645E+09 | 95634890.70 | 40009855.64 | 0.161662E+09 | 82181003.80 |
March | 0.213277E+09 | 0.151139E+09 | 62138279.22 | 0.262397E+09 | 86293291.31 |
April | 0.258830E+09 | 0.193052E+09 | 65777733.02 | 0.325845E+09 | 71867170.23 |
May | 0.295923E+09 | 0.221396E+09 | 74526710.24 | 0.383634E+09 | 63757245.43 |
June | 0.303369E+09 | 0.236766E+09 | 66603153.22 | 0.408931E+09 | 43120416.82 |
July | 0.270718E+09 | 0.196699E+09 | 74018387.01 | 0.368500E+09 | 35827273.67 |
August | 0.252690E+09 | 0.183556E+09 | 69134362.96 | 0.338172E+09 | 44283134.82 |
September | 0.222346E+09 | 0.166952E+09 | 55393203.54 | 0.292271E+09 | 64506366.84 |
October | 0.170938E+09 | 0.124085E+09 | 46852902.75 | 0.211433E+09 | 82274355.28 |
November | 0.126909E+09 | 93494860.10 | 33413896.22 | 0.146713E+09 | 97344273.54 |
December | 0.105758E+09 | 69152124.52 | 36605653.01 | 0.116024E+09 | 0.111760E+09 |
Annual Sum or Average | 0.247138E+10 | 0.181162E+10 | 0.659762E+09 | 0.314864E+10 | 0.879654E+09 |
Minimum of Months | 0.105758E+09 | 69152124.52 | 33413896.22 | 0.116024E+09 | 35827273.67 |
Maximum of Months | 0.303369E+09 | 0.236766E+09 | 74526710.24 | 0.408931E+09 | 0.111760E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114980E+09 | 79691597.10 | 35288321.31 | 0.133061E+09 | 96439629.94 |
February | 0.135645E+09 | 95634890.70 | 40009855.64 | 0.161662E+09 | 82181003.80 |
March | 0.213277E+09 | 0.151139E+09 | 62138279.22 | 0.262397E+09 | 86293291.31 |
April | 0.258830E+09 | 0.193052E+09 | 65777733.02 | 0.325845E+09 | 71867170.23 |
May | 0.295923E+09 | 0.221396E+09 | 74526710.24 | 0.383634E+09 | 63757245.43 |
June | 0.303369E+09 | 0.236766E+09 | 66603153.22 | 0.408931E+09 | 43120416.82 |
July | 0.270718E+09 | 0.196699E+09 | 74018387.01 | 0.368500E+09 | 35827273.67 |
August | 0.252690E+09 | 0.183556E+09 | 69134362.96 | 0.338172E+09 | 44283134.82 |
September | 0.222346E+09 | 0.166952E+09 | 55393203.54 | 0.292271E+09 | 64506366.84 |
October | 0.170938E+09 | 0.124085E+09 | 46852902.75 | 0.211433E+09 | 82274355.28 |
November | 0.126909E+09 | 93494860.10 | 33413896.22 | 0.146713E+09 | 97344273.54 |
December | 0.105758E+09 | 69152124.52 | 36605653.01 | 0.116024E+09 | 0.111760E+09 |
Annual Sum or Average | 0.247138E+10 | 0.181162E+10 | 0.659762E+09 | 0.314864E+10 | 0.879654E+09 |
Minimum of Months | 0.105758E+09 | 69152124.52 | 33413896.22 | 0.116024E+09 | 35827273.67 |
Maximum of Months | 0.303369E+09 | 0.236766E+09 | 74526710.24 | 0.408931E+09 | 0.111760E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114980E+09 | 79691597.10 | 35288321.31 | 0.133061E+09 | 96439629.94 |
February | 0.135645E+09 | 95634890.70 | 40009855.64 | 0.161662E+09 | 82181003.80 |
March | 0.213277E+09 | 0.151139E+09 | 62138279.22 | 0.262397E+09 | 86293291.31 |
April | 0.258830E+09 | 0.193052E+09 | 65777733.02 | 0.325845E+09 | 71867170.23 |
May | 0.295923E+09 | 0.221396E+09 | 74526710.24 | 0.383634E+09 | 63757245.43 |
June | 0.303369E+09 | 0.236766E+09 | 66603153.22 | 0.408931E+09 | 43120416.82 |
July | 0.270718E+09 | 0.196699E+09 | 74018387.01 | 0.368500E+09 | 35827273.67 |
August | 0.252690E+09 | 0.183556E+09 | 69134362.96 | 0.338172E+09 | 44283134.82 |
September | 0.222346E+09 | 0.166952E+09 | 55393203.54 | 0.292271E+09 | 64506366.84 |
October | 0.170938E+09 | 0.124085E+09 | 46852902.75 | 0.211433E+09 | 82274355.28 |
November | 0.126909E+09 | 93494860.10 | 33413896.22 | 0.146713E+09 | 97344273.54 |
December | 0.105758E+09 | 69152124.52 | 36605653.01 | 0.116024E+09 | 0.111760E+09 |
Annual Sum or Average | 0.247138E+10 | 0.181162E+10 | 0.659762E+09 | 0.314864E+10 | 0.879654E+09 |
Minimum of Months | 0.105758E+09 | 69152124.52 | 33413896.22 | 0.116024E+09 | 35827273.67 |
Maximum of Months | 0.303369E+09 | 0.236766E+09 | 74526710.24 | 0.408931E+09 | 0.111760E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114980E+09 | 79691597.10 | 35288321.31 | 0.133061E+09 | 96439629.94 |
February | 0.135645E+09 | 95634890.70 | 40009855.64 | 0.161662E+09 | 82181003.80 |
March | 0.213277E+09 | 0.151139E+09 | 62138279.22 | 0.262397E+09 | 86293291.31 |
April | 0.258830E+09 | 0.193052E+09 | 65777733.02 | 0.325845E+09 | 71867170.23 |
May | 0.295923E+09 | 0.221396E+09 | 74526710.24 | 0.383634E+09 | 63757245.43 |
June | 0.303369E+09 | 0.236766E+09 | 66603153.22 | 0.408931E+09 | 43120416.82 |
July | 0.270718E+09 | 0.196699E+09 | 74018387.01 | 0.368500E+09 | 35827273.67 |
August | 0.252690E+09 | 0.183556E+09 | 69134362.96 | 0.338172E+09 | 44283134.82 |
September | 0.222346E+09 | 0.166952E+09 | 55393203.54 | 0.292271E+09 | 64506366.84 |
October | 0.170938E+09 | 0.124085E+09 | 46852902.75 | 0.211433E+09 | 82274355.28 |
November | 0.126909E+09 | 93494860.10 | 33413896.22 | 0.146713E+09 | 97344273.54 |
December | 0.105758E+09 | 69152124.52 | 36605653.01 | 0.116024E+09 | 0.111760E+09 |
Annual Sum or Average | 0.247138E+10 | 0.181162E+10 | 0.659762E+09 | 0.314864E+10 | 0.879654E+09 |
Minimum of Months | 0.105758E+09 | 69152124.52 | 33413896.22 | 0.116024E+09 | 35827273.67 |
Maximum of Months | 0.303369E+09 | 0.236766E+09 | 74526710.24 | 0.408931E+09 | 0.111760E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114980E+09 | 79691597.10 | 35288321.31 | 0.133061E+09 | 96439629.94 |
February | 0.135645E+09 | 95634890.70 | 40009855.64 | 0.161662E+09 | 82181003.80 |
March | 0.213277E+09 | 0.151139E+09 | 62138279.22 | 0.262397E+09 | 86293291.31 |
April | 0.258830E+09 | 0.193052E+09 | 65777733.02 | 0.325845E+09 | 71867170.23 |
May | 0.295923E+09 | 0.221396E+09 | 74526710.24 | 0.383634E+09 | 63757245.43 |
June | 0.303369E+09 | 0.236766E+09 | 66603153.22 | 0.408931E+09 | 43120416.82 |
July | 0.270718E+09 | 0.196699E+09 | 74018387.01 | 0.368500E+09 | 35827273.67 |
August | 0.252690E+09 | 0.183556E+09 | 69134362.96 | 0.338172E+09 | 44283134.82 |
September | 0.222346E+09 | 0.166952E+09 | 55393203.54 | 0.292271E+09 | 64506366.84 |
October | 0.170938E+09 | 0.124085E+09 | 46852902.75 | 0.211433E+09 | 82274355.28 |
November | 0.126909E+09 | 93494860.10 | 33413896.22 | 0.146713E+09 | 97344273.54 |
December | 0.105758E+09 | 69152124.52 | 36605653.01 | 0.116024E+09 | 0.111760E+09 |
Annual Sum or Average | 0.247138E+10 | 0.181162E+10 | 0.659762E+09 | 0.314864E+10 | 0.879654E+09 |
Minimum of Months | 0.105758E+09 | 69152124.52 | 33413896.22 | 0.116024E+09 | 35827273.67 |
Maximum of Months | 0.303369E+09 | 0.236766E+09 | 74526710.24 | 0.408931E+09 | 0.111760E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.238077E+09 | 0.167946E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.282342E+09 | 0.145959E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.441188E+09 | 0.167935E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.538063E+09 | 0.148860E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.617294E+09 | 0.151440E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.646898E+09 | 0.119879E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.584531E+09 | 99974742.73 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.538594E+09 | 0.119701E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.471395E+09 | 0.154807E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.350514E+09 | 0.173514E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.253974E+09 | 0.188359E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.214292E+09 | 0.189262E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.517716E+10 | 0.182764E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.214292E+09 | 99974742.73 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.646898E+09 | 0.189262E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 178.56 | 304.31 | 168.39 | 78.65 | 89.74 | 0.00 | 0.00 |
February | 225.75 | 269.68 | 192.28 | 83.31 | 108.96 | 0.00 | 0.00 |
March | 336.34 | 242.56 | 260.37 | 114.81 | 145.56 | 0.00 | 0.00 |
April | 435.82 | 175.64 | 299.39 | 133.23 | 166.16 | 0.00 | 0.00 |
May | 532.25 | 127.92 | 328.15 | 146.21 | 181.94 | 0.00 | 0.00 |
June | 604.61 | 77.63 | 325.52 | 147.06 | 178.46 | 0.00 | 0.00 |
July | 536.89 | 68.94 | 291.39 | 119.97 | 171.42 | 0.00 | 0.00 |
August | 482.31 | 91.39 | 274.48 | 114.26 | 160.22 | 0.00 | 0.00 |
September | 451.49 | 162.69 | 273.19 | 126.94 | 146.25 | 0.00 | 0.00 |
October | 323.49 | 224.82 | 233.27 | 113.98 | 119.30 | 0.00 | 0.00 |
November | 218.99 | 303.00 | 193.52 | 98.78 | 94.73 | 0.00 | 0.00 |
December | 156.05 | 347.97 | 160.82 | 71.80 | 89.02 | 0.00 | 0.00 |
Annual Sum or Average | 374.17 | 199.36 | 250.29 | 112.50 | 137.79 | 0.00 | 0.00 |
Minimum of Months | 156.05 | 68.94 | 160.82 | 71.80 | 89.02 | 0.00 | 0.00 |
Maximum of Months | 604.61 | 347.97 | 328.15 | 147.06 | 181.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 695.51 | 504.09 | 601.00 | 416.55 | 184.45 | 0.00 | 0.00 |
February | 935.54 | 475.58 | 784.98 | 553.44 | 231.54 | 0.00 | 0.00 |
March | 1371.55 | 451.06 | 1114.80 | 790.00 | 324.80 | 0.00 | 0.00 |
April | 1759.97 | 388.17 | 1398.00 | 1042.72 | 355.28 | 0.00 | 0.00 |
May | 2005.26 | 333.26 | 1546.79 | 1157.24 | 389.55 | 0.00 | 0.00 |
June | 2208.73 | 232.90 | 1638.57 | 1278.83 | 359.74 | 0.00 | 0.00 |
July | 1926.15 | 187.27 | 1415.04 | 1028.15 | 386.89 | 0.00 | 0.00 |
August | 1767.63 | 231.47 | 1320.81 | 959.45 | 361.37 | 0.00 | 0.00 |
September | 1578.62 | 348.41 | 1200.94 | 901.75 | 299.19 | 0.00 | 0.00 |
October | 1105.16 | 430.05 | 893.49 | 648.59 | 244.90 | 0.00 | 0.00 |
November | 792.43 | 525.78 | 685.46 | 504.99 | 180.48 | 0.00 | 0.00 |
December | 606.46 | 584.17 | 552.80 | 361.46 | 191.34 | 0.00 | 0.00 |
Annual Sum or Average | 1397.80 | 390.51 | 1097.14 | 804.25 | 292.89 | 0.00 | 0.00 |
Minimum of Months | 606.46 | 187.27 | 552.80 | 361.46 | 180.48 | 0.00 | 0.00 |
Maximum of Months | 2208.73 | 584.17 | 1638.57 | 1278.83 | 389.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11210.03 | 9537.31 | 2253.88 | 1581.24 | 672.64 | 0.00 | 0.00 |
February | 14759.45 | 8459.91 | 2883.55 | 2039.20 | 844.35 | 0.00 | 0.00 |
March | 21687.81 | 7241.71 | 4025.75 | 2841.31 | 1184.44 | 0.00 | 0.00 |
April | 26402.92 | 5648.12 | 5007.57 | 3711.96 | 1295.61 | 0.00 | 0.00 |
May | 34247.99 | 6438.28 | 5521.07 | 4100.49 | 1420.58 | 0.00 | 0.00 |
June | 44852.09 | 7952.42 | 5829.83 | 4517.97 | 1311.86 | 0.00 | 0.00 |
July | 38630.01 | 6577.45 | 5045.61 | 3634.73 | 1410.89 | 0.00 | 0.00 |
August | 34564.83 | 7288.56 | 4717.94 | 3400.15 | 1317.79 | 0.00 | 0.00 |
September | 29501.08 | 7606.43 | 4319.41 | 3228.35 | 1091.06 | 0.00 | 0.00 |
October | 16131.68 | 6681.65 | 3258.62 | 2365.54 | 893.08 | 0.00 | 0.00 |
November | 12819.66 | 8112.73 | 2554.57 | 1896.43 | 658.14 | 0.00 | 0.00 |
December | 10140.70 | 11663.08 | 2090.41 | 1392.66 | 697.75 | 0.00 | 0.00 |
Annual Sum or Average | 24617.92 | 7766.41 | 3962.72 | 2894.63 | 1068.09 | 0.00 | 0.00 |
Minimum of Months | 10140.70 | 5648.12 | 2090.41 | 1392.66 | 658.14 | 0.00 | 0.00 |
Maximum of Months | 44852.09 | 11663.08 | 5829.83 | 4517.97 | 1420.58 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.478267E+09 | 0.815076E+09 | 0.451024E+09 | 0.210661E+09 | 0.240363E+09 | 0.00 | 0.00 |
February | 0.546133E+09 | 0.652411E+09 | 0.465159E+09 | 0.201552E+09 | 0.263606E+09 | 0.00 | 0.00 |
March | 0.900866E+09 | 0.649678E+09 | 0.697373E+09 | 0.307509E+09 | 0.389864E+09 | 0.00 | 0.00 |
April | 0.112965E+10 | 0.455249E+09 | 0.776014E+09 | 0.345338E+09 | 0.430675E+09 | 0.00 | 0.00 |
May | 0.142559E+10 | 0.342628E+09 | 0.878914E+09 | 0.391600E+09 | 0.487314E+09 | 0.00 | 0.00 |
June | 0.156715E+10 | 0.201211E+09 | 0.843742E+09 | 0.381168E+09 | 0.462574E+09 | 0.00 | 0.00 |
July | 0.143800E+10 | 0.184654E+09 | 0.780452E+09 | 0.321315E+09 | 0.459137E+09 | 0.00 | 0.00 |
August | 0.129181E+10 | 0.244776E+09 | 0.735161E+09 | 0.306021E+09 | 0.429140E+09 | 0.00 | 0.00 |
September | 0.117025E+10 | 0.421689E+09 | 0.708117E+09 | 0.329038E+09 | 0.379079E+09 | 0.00 | 0.00 |
October | 0.866430E+09 | 0.602164E+09 | 0.624803E+09 | 0.305279E+09 | 0.319524E+09 | 0.00 | 0.00 |
November | 0.567625E+09 | 0.785374E+09 | 0.501598E+09 | 0.256046E+09 | 0.245552E+09 | 0.00 | 0.00 |
December | 0.417963E+09 | 0.932011E+09 | 0.430734E+09 | 0.192312E+09 | 0.238423E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.117997E+11 | 0.628692E+10 | 0.789309E+10 | 0.354784E+10 | 0.434525E+10 | 0.00 | 0.00 |
Minimum of Months | 0.417963E+09 | 0.184654E+09 | 0.430734E+09 | 0.192312E+09 | 0.238423E+09 | 0.00 | 0.00 |
Maximum of Months | 0.156715E+10 | 0.932011E+09 | 0.878914E+09 | 0.391600E+09 | 0.487314E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.186285E+10 | 0.135015E+10 | 0.160972E+10 | 0.111568E+10 | 0.494036E+09 | 0.00 | 0.00 |
February | 0.226326E+10 | 0.115053E+10 | 0.189903E+10 | 0.133889E+10 | 0.560138E+09 | 0.00 | 0.00 |
March | 0.367356E+10 | 0.120811E+10 | 0.298588E+10 | 0.211594E+10 | 0.869936E+09 | 0.00 | 0.00 |
April | 0.456183E+10 | 0.100614E+10 | 0.362362E+10 | 0.270273E+10 | 0.920888E+09 | 0.00 | 0.00 |
May | 0.537088E+10 | 0.892601E+09 | 0.414292E+10 | 0.309955E+10 | 0.104337E+10 | 0.00 | 0.00 |
June | 0.572503E+10 | 0.603686E+09 | 0.424717E+10 | 0.331472E+10 | 0.932444E+09 | 0.00 | 0.00 |
July | 0.515900E+10 | 0.501582E+09 | 0.379005E+10 | 0.275379E+10 | 0.103626E+10 | 0.00 | 0.00 |
August | 0.473441E+10 | 0.619964E+09 | 0.353766E+10 | 0.256978E+10 | 0.967881E+09 | 0.00 | 0.00 |
September | 0.409179E+10 | 0.903089E+09 | 0.311284E+10 | 0.233733E+10 | 0.775505E+09 | 0.00 | 0.00 |
October | 0.296006E+10 | 0.115184E+10 | 0.239313E+10 | 0.173719E+10 | 0.655941E+09 | 0.00 | 0.00 |
November | 0.205398E+10 | 0.136282E+10 | 0.177672E+10 | 0.130893E+10 | 0.467795E+09 | 0.00 | 0.00 |
December | 0.162433E+10 | 0.156464E+10 | 0.148061E+10 | 0.968130E+09 | 0.512479E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.440810E+11 | 0.123152E+11 | 0.345993E+11 | 0.253627E+11 | 0.923667E+10 | 0.00 | 0.00 |
Minimum of Months | 0.162433E+10 | 0.501582E+09 | 0.148061E+10 | 0.968130E+09 | 0.467795E+09 | 0.00 | 0.00 |
Maximum of Months | 0.572503E+10 | 0.156464E+10 | 0.424717E+10 | 0.331472E+10 | 0.104337E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.300249E+11 | 0.255447E+11 | 0.603680E+10 | 0.423519E+10 | 0.180161E+10 | 0.00 | 0.00 |
February | 0.357061E+11 | 0.204662E+11 | 0.697589E+10 | 0.493323E+10 | 0.204266E+10 | 0.00 | 0.00 |
March | 0.580886E+11 | 0.193962E+11 | 0.107826E+11 | 0.761016E+10 | 0.317240E+10 | 0.00 | 0.00 |
April | 0.684364E+11 | 0.146399E+11 | 0.129796E+11 | 0.962141E+10 | 0.335821E+10 | 0.00 | 0.00 |
May | 0.917298E+11 | 0.172443E+11 | 0.147876E+11 | 0.109828E+11 | 0.380488E+10 | 0.00 | 0.00 |
June | 0.116257E+12 | 0.206127E+11 | 0.151109E+11 | 0.117106E+11 | 0.340035E+10 | 0.00 | 0.00 |
July | 0.103467E+12 | 0.176171E+11 | 0.135142E+11 | 0.973525E+10 | 0.377893E+10 | 0.00 | 0.00 |
August | 0.925784E+11 | 0.195217E+11 | 0.126365E+11 | 0.910696E+10 | 0.352958E+10 | 0.00 | 0.00 |
September | 0.764668E+11 | 0.197159E+11 | 0.111959E+11 | 0.836788E+10 | 0.282804E+10 | 0.00 | 0.00 |
October | 0.432071E+11 | 0.178961E+11 | 0.872788E+10 | 0.633586E+10 | 0.239202E+10 | 0.00 | 0.00 |
November | 0.332285E+11 | 0.210282E+11 | 0.662145E+10 | 0.491554E+10 | 0.170591E+10 | 0.00 | 0.00 |
December | 0.271608E+11 | 0.312384E+11 | 0.559896E+10 | 0.373010E+10 | 0.186886E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.776351E+12 | 0.244921E+12 | 0.124968E+12 | 0.912849E+11 | 0.336834E+11 | 0.00 | 0.00 |
Minimum of Months | 0.271608E+11 | 0.146399E+11 | 0.559896E+10 | 0.373010E+10 | 0.170591E+10 | 0.00 | 0.00 |
Maximum of Months | 0.116257E+12 | 0.312384E+11 | 0.151109E+11 | 0.117106E+11 | 0.380488E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.868573E+09 | -782882670.7 | 0.00 | 0.00 | 744.00 | 0.00 | -85690759.6 | 59.00 | 0.00 | 0.00 |
February | 0.794849E+09 | -718609606.2 | 0.00 | 0.00 | 672.00 | 0.00 | -76239253.8 | 58.99 | 0.00 | 0.00 |
March | 0.890394E+09 | -808956275.1 | 0.00 | 0.00 | 744.00 | 0.00 | -81437604.6 | 59.00 | 0.00 | 0.00 |
April | 0.774240E+09 | -701672235.6 | 0.00 | 0.00 | 720.00 | 0.00 | -72568260.2 | 58.99 | 0.00 | 0.00 |
May | 0.741745E+09 | -670064273.6 | 0.00 | 0.00 | 744.00 | 0.00 | -71680229.7 | 58.99 | 0.00 | 0.00 |
June | 0.682696E+09 | -614641727.0 | 0.00 | 0.00 | 720.00 | 0.00 | -68054311.4 | 58.99 | 0.00 | 0.00 |
July | 0.634573E+09 | -564861324.2 | 0.00 | 0.00 | 744.00 | 0.00 | -69711627.9 | 58.98 | 0.00 | 0.00 |
August | 0.677602E+09 | -607217346.8 | 0.00 | 0.00 | 744.00 | 0.00 | -70384465.6 | 58.99 | 0.00 | 0.00 |
September | 0.663134E+09 | -594570677.4 | 0.00 | 0.00 | 720.00 | 0.00 | -68563043.9 | 58.99 | 0.00 | 0.00 |
October | 0.720102E+09 | -646570165.9 | 0.00 | 0.00 | 744.00 | 0.00 | -73531928.9 | 58.99 | 0.00 | 0.00 |
November | 0.754080E+09 | -676114788.8 | 0.00 | 0.00 | 720.00 | 0.00 | -77965331.0 | 58.99 | 0.00 | 0.00 |
December | 0.839272E+09 | -753455154.6 | 0.00 | 0.00 | 744.00 | 0.00 | -85816386.1 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.904126E+10 | -0.813962E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -901643202.6 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.634573E+09 | -808956275.1 | 0.00 | 0.00 | 672.00 | 0.00 | -85816386.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.890394E+09 | -564861324.2 | 0.00 | 0.00 | 744.00 | 0.00 | -68054311.4 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.88 | 0.58 | 08-JAN-13:09 | 806.52 | 0.00 | 0.00 | 34.33 | 106.04 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.86 | 0.50 | 16-FEB-11:30 | 149.66 | 0.00 | 0.00 | 14.00 | 125.76 | 0.00 | 0.00 | 4.33 |
March | 351.83 | 0.82 | 0.50 | 02-MAR-11:20 | 186.39 | 0.00 | 0.00 | 62.50 | 152.12 | 0.00 | 0.00 | 36.67 |
April | 373.83 | 0.81 | 0.50 | 02-APR-10:20 | 195.03 | 0.00 | 0.00 | 51.33 | 159.40 | 0.00 | 0.00 | 30.50 |
May | 408.83 | 0.79 | 0.50 | 01-MAY-10:20 | 942.51 | 0.00 | 0.00 | 82.17 | 1533.98 | 0.00 | 0.00 | 53.17 |
June | 398.00 | 0.80 | 0.50 | 02-JUN-10:39 | 3568.84 | 0.00 | 0.00 | 114.67 | 150.67 | 0.00 | 0.00 | 15.17 |
July | 400.17 | 0.78 | 0.50 | 01-JUL-11:50 | 1527.87 | 0.00 | 0.00 | 123.33 | 163.34 | 0.00 | 0.00 | 37.67 |
August | 377.83 | 0.79 | 0.50 | 01-AUG-10:50 | 604.03 | 0.00 | 0.00 | 74.00 | 165.91 | 0.00 | 0.00 | 34.67 |
September | 365.83 | 0.83 | 0.50 | 03-SEP-10:39 | 176.18 | 0.00 | 0.00 | 57.50 | 146.11 | 0.00 | 0.00 | 24.17 |
October | 318.83 | 0.84 | 0.50 | 02-OCT-10:09 | 158.06 | 0.00 | 0.00 | 27.00 | 1134.57 | 0.00 | 0.00 | 46.83 |
November | 295.83 | 0.91 | 0.58 | 02-NOV-10:30 | 116.93 | 0.00 | 0.00 | 1.17 | 98.29 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.90 | 0.67 | 01-DEC-10:00 | 124.86 | 0.00 | 0.00 | 0.00 | 104.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | 0.83 | 783.60 | 0.00 | 0.00 | 642.00 | 355.34 | 0.00 | 0.00 | 283.17 | ||
Minimum of Months | 268.33 | 0.78 | 0.50 | 116.93 | 0.00 | 0.00 | 0.00 | 98.29 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 408.83 | 0.91 | 0.67 | 3568.84 | 0.00 | 0.00 | 123.33 | 1533.98 | 0.00 | 0.00 | 53.17 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.74 | 0.50 | 06-JAN-10:20 | 153.63 | 10.60 | 0.00 | 60.67 | 1037.21 | 18.39 | 51.83 | 85.17 |
February | 268.33 | 0.71 | 0.50 | 06-FEB-09:20 | 1255.94 | 13.71 | 31.33 | 98.83 | 382.14 | 16.64 | 33.67 | 81.17 |
March | 351.83 | 0.69 | 0.50 | 01-MAR-11:09 | 292.01 | 11.96 | 1.83 | 154.33 | 185.31 | 15.71 | 36.00 | 118.00 |
April | 373.83 | 0.65 | 0.50 | 01-APR-08:00 | 1557.58 | 12.32 | 0.00 | 220.83 | 2868.38 | 18.04 | 90.17 | 169.67 |
May | 408.83 | 0.64 | 0.50 | 01-MAY-07:00 | 245.19 | 12.54 | 0.00 | 252.67 | 1657.41 | 16.50 | 83.00 | 197.83 |
June | 398.00 | 0.64 | 0.50 | 01-JUN-08:39 | 233.02 | 12.39 | 0.00 | 241.83 | 198.75 | 16.38 | 67.50 | 182.17 |
July | 400.17 | 0.65 | 0.50 | 01-JUL-08:20 | 246.29 | 12.45 | 0.00 | 233.83 | 211.08 | 16.40 | 76.00 | 180.00 |
August | 377.83 | 0.64 | 0.50 | 01-AUG-08:30 | 1377.70 | 12.65 | 0.00 | 234.83 | 1418.19 | 16.59 | 75.17 | 180.33 |
September | 365.83 | 0.70 | 0.50 | 01-SEP-11:09 | 210.80 | 11.49 | 0.00 | 155.50 | 177.29 | 15.40 | 39.83 | 115.50 |
October | 318.83 | 0.71 | 0.50 | 02-OCT-08:50 | 855.42 | 11.40 | 0.00 | 139.50 | 159.67 | 15.23 | 32.83 | 76.00 |
November | 295.83 | 0.78 | 0.50 | 01-NOV-13:20 | 143.24 | 10.26 | 0.00 | 50.17 | 121.03 | 14.03 | 2.33 | 26.83 |
December | 289.50 | 0.74 | 0.50 | 01-DEC-10:50 | 153.78 | 10.98 | 0.00 | 64.67 | 968.23 | 17.76 | 46.17 | 81.00 |
Annual Sum or Average | 4125.67 | 0.69 | 560.73 | 11.95 | 33.17 | 1907.67 | 808.61 | 16.41 | 634.50 | 1493.67 | ||
Minimum of Months | 268.33 | 0.64 | 0.50 | 143.24 | 10.26 | 0.00 | 50.17 | 121.03 | 14.03 | 2.33 | 26.83 | |
Maximum of Months | 408.83 | 0.78 | 0.50 | 1557.58 | 13.71 | 31.33 | 252.67 | 2868.38 | 18.39 | 90.17 | 197.83 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.87 | 0.64 | 12-JAN-15:30 | 421.32 | 23.97 | 117.83 | 42.17 | 109.85 | 20.28 | 77.83 | 0.00 |
February | 268.33 | 0.86 | 0.61 | 10-FEB-16:10 | 310.70 | 23.08 | 109.50 | 40.50 | 189.53 | 22.31 | 98.50 | 13.67 |
March | 351.83 | 0.83 | 0.61 | 01-MAR-16:10 | 444.50 | 23.05 | 144.33 | 75.67 | 385.76 | 23.62 | 156.00 | 46.17 |
April | 373.83 | 0.83 | 0.61 | 01-APR-15:20 | 313.90 | 21.35 | 137.17 | 60.17 | 509.10 | 22.45 | 165.50 | 65.50 |
May | 408.83 | 0.83 | 0.61 | 01-MAY-15:50 | 251.23 | 20.64 | 139.00 | 63.33 | 275.87 | 22.13 | 193.33 | 69.33 |
June | 398.00 | 0.84 | 0.61 | 02-JUN-15:20 | 246.79 | 20.56 | 120.67 | 40.33 | 288.32 | 22.03 | 176.33 | 58.50 |
July | 400.17 | 0.83 | 0.61 | 01-JUL-15:20 | 244.16 | 20.51 | 129.50 | 46.00 | 266.99 | 21.97 | 198.83 | 58.00 |
August | 377.83 | 0.83 | 0.61 | 01-AUG-15:39 | 242.17 | 20.62 | 133.50 | 49.17 | 251.94 | 22.05 | 177.67 | 53.17 |
September | 365.83 | 0.84 | 0.61 | 02-SEP-15:09 | 301.13 | 21.46 | 153.83 | 61.50 | 362.22 | 23.52 | 175.17 | 54.17 |
October | 318.83 | 0.84 | 0.61 | 01-OCT-15:09 | 607.72 | 24.47 | 138.17 | 63.17 | 213.20 | 23.26 | 137.83 | 27.33 |
November | 295.83 | 0.88 | 0.64 | 02-NOV-14:30 | 420.63 | 23.27 | 110.83 | 44.00 | 104.96 | 20.00 | 73.17 | 0.00 |
December | 289.50 | 0.88 | 0.64 | 05-DEC-15:30 | 361.52 | 23.38 | 118.17 | 37.17 | 101.18 | 19.94 | 71.50 | 0.00 |
Annual Sum or Average | 4125.67 | 0.84 | 338.59 | 22.02 | 1552.50 | 623.17 | 266.07 | 22.04 | 1701.67 | 445.83 | ||
Minimum of Months | 268.33 | 0.83 | 0.61 | 242.17 | 20.51 | 109.50 | 37.17 | 101.18 | 19.94 | 71.50 | 0.00 | |
Maximum of Months | 408.83 | 0.88 | 0.64 | 607.72 | 24.47 | 153.83 | 75.67 | 509.10 | 23.62 | 198.83 | 69.33 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.251835E+10 | 29069.09 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176901E+10 | 29069.09 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100488E+10 | 29069.09 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42149668.88 | 29069.09 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.678753E+09 | 29069.09 | 06-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.268315E+10 | 29069.09 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.869630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.268315E+10 | 29069.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.439228E+10 | 82826.84 | 28-JAN-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216586E+10 | 78081.81 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.532401E+09 | 58290.20 | 02-MAR-06:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.484355E+09 | 52716.83 | 29-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.645483E+10 | 92614.23 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.645483E+10 | 92614.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.330309E+09 | 23868.87 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.194468E+09 | 17057.96 | 03-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.242312E+10 | 36230.79 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.242312E+10 | 36230.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 11153892.53 | 11153892.53 | 770.34 | 21-FEB-16:00 | 770.34 | 0.00 |
March | 0.00 | 0.00 | 0.202168E+09 | 0.202168E+09 | 3598.85 | 21-MAR-16:00 | 3598.85 | 0.00 |
April | 0.00 | 0.00 | 0.259770E+10 | 0.258151E+10 | 20734.83 | 20-APR-05:03 | 20734.83 | 0.00 |
May | 0.00 | 0.00 | 0.649543E+10 | 0.626446E+10 | 22508.17 | 23-MAY-05:01 | 17886.15 | 0.00 |
June | 0.00 | 0.00 | 0.967626E+10 | 0.914963E+10 | 23381.84 | 28-JUN-05:02 | 14570.13 | 0.00 |
July | 0.00 | 0.00 | 0.112772E+11 | 0.902515E+10 | 26740.56 | 22-JUL-05:01 | 11883.32 | 0.00 |
August | 0.00 | 0.00 | 0.104946E+11 | 0.883909E+10 | 25839.92 | 03-AUG-05:01 | 14730.75 | 0.00 |
September | 0.00 | 0.00 | 0.845843E+10 | 0.719607E+10 | 25198.89 | 22-SEP-05:01 | 13310.12 | 0.00 |
October | 0.00 | 0.00 | 0.336211E+10 | 0.298211E+10 | 23765.26 | 04-OCT-05:02 | 13313.57 | 0.00 |
November | 0.00 | 0.00 | 0.212301E+09 | 0.209112E+09 | 4997.04 | 03-NOV-16:00 | 4997.04 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.527873E+11 | 0.464604E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.112772E+11 | 0.914963E+10 | 26740.56 | 20734.83 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.226139E+10 | 0.225924E+10 | 64207.73 | 30-APR-10:15 | 64145.83 | 0.00 |
May | 0.00 | 0.00 | 0.132286E+11 | 0.128580E+11 | 71699.25 | 28-MAY-08:55 | 51469.02 | 0.00 |
June | 0.00 | 0.00 | 0.270683E+11 | 0.261306E+11 | 74802.10 | 19-JUN-18:00 | 47367.75 | 0.00 |
July | 0.00 | 0.00 | 0.307325E+11 | 0.258291E+11 | 79515.70 | 21-JUL-21:15 | 40822.17 | 0.00 |
August | 0.00 | 0.00 | 0.251779E+11 | 0.222910E+11 | 76557.15 | 01-AUG-21:25 | 41753.21 | 0.00 |
September | 0.00 | 0.00 | 0.178830E+11 | 0.155929E+11 | 75042.83 | 03-SEP-08:42 | 47121.67 | 0.00 |
October | 0.00 | 0.00 | 0.311118E+10 | 0.273306E+10 | 70809.10 | 08-OCT-13:25 | 54734.20 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.119463E+12 | 0.107694E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.307325E+11 | 0.261306E+11 | 79515.70 | 64145.83 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 5267629.64 | 0.00 | 229.88 | 27-JAN-06:30 | 0.09 |
February | 6331007.75 | 0.00 | 229.88 | 02-FEB-03:00 | 0.09 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 41264193.55 | 0.01 | 229.88 | 22-DEC-05:00 | 0.09 |
Annual Sum or Average | 52862830.94 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41264193.55 | 0.01 | 229.88 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.667195E+09 | 0.27 | 1461.61 | 02-JAN-06:01 | 1.04 |
February | 0.596152E+09 | 0.27 | 1461.61 | 01-FEB-06:01 | 1.05 |
March | 0.662578E+09 | 0.28 | 1461.61 | 01-MAR-06:01 | 1.05 |
April | 0.581261E+09 | 0.24 | 1461.61 | 01-APR-05:02 | 1.05 |
May | 0.616976E+09 | 0.25 | 1461.61 | 09-MAY-05:02 | 1.05 |
June | 0.671034E+09 | 0.28 | 1461.61 | 01-JUN-05:01 | 1.05 |
July | 0.656302E+09 | 0.27 | 1461.61 | 01-JUL-05:01 | 1.04 |
August | 0.683498E+09 | 0.28 | 1461.61 | 01-AUG-05:01 | 1.03 |
September | 0.606461E+09 | 0.26 | 1461.61 | 01-SEP-05:01 | 1.03 |
October | 0.583367E+09 | 0.24 | 1461.61 | 02-OCT-05:01 | 1.04 |
November | 0.580411E+09 | 0.25 | 1461.61 | 06-NOV-06:02 | 1.05 |
December | 0.672644E+09 | 0.28 | 1461.61 | 01-DEC-06:01 | 1.05 |
Annual Sum or Average | 0.757788E+10 | 0.26 | |||
Minimum of Months | 0.580411E+09 | 0.24 | 1461.61 | 1.03 | |
Maximum of Months | 0.683498E+09 | 0.28 | 1461.61 | 1.05 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153122E+10 | 0.39 | 3110.24 | 28-JAN-05:42 | 1.02 |
February | 0.134406E+10 | 0.32 | 2932.06 | 03-FEB-06:01 | 1.02 |
March | 0.150669E+10 | 0.26 | 2188.86 | 02-MAR-06:31 | 1.02 |
April | 0.139472E+10 | 0.24 | 2958.77 | 30-APR-15:03 | 0.94 |
May | 0.158511E+10 | 0.29 | 3479.26 | 19-MAY-17:06 | 1.01 |
June | 0.180023E+10 | 0.37 | 3479.26 | 01-JUN-17:06 | 1.01 |
July | 0.180242E+10 | 0.36 | 3479.26 | 01-JUL-17:06 | 1.00 |
August | 0.178886E+10 | 0.35 | 3479.26 | 01-AUG-17:06 | 1.00 |
September | 0.153088E+10 | 0.28 | 3479.26 | 03-SEP-11:53 | 1.00 |
October | 0.139902E+10 | 0.23 | 3288.09 | 01-OCT-13:43 | 0.98 |
November | 0.133993E+10 | 0.25 | 1979.58 | 29-NOV-06:10 | 1.01 |
December | 0.160457E+10 | 0.44 | 3477.77 | 26-DEC-06:01 | 1.01 |
Annual Sum or Average | 0.186277E+11 | 0.32 | |||
Minimum of Months | 0.133993E+10 | 0.23 | 1979.58 | 0.94 | |
Maximum of Months | 0.180242E+10 | 0.44 | 3479.26 | 1.02 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.667195E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.598989E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.712833E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.123189E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.222829E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.317451E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.341826E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.324711E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.264448E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.138767E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.632422E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.672644E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.206163E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.598989E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.341826E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.153122E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134406E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.150669E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.200970E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.510838E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.920687E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.978817E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.834338E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.609928E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.220068E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.133993E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.160457E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.500829E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.133993E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.978817E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.667195E+09 | 0.00 | 0.251835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.596152E+09 | 11153892.53 | 0.176901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.662578E+09 | 0.202168E+09 | 0.100488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.581261E+09 | 0.259629E+10 | 42149668.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.616976E+09 | 0.647103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.671034E+09 | 0.961697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.656302E+09 | 0.111685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.683498E+09 | 0.104163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.606461E+09 | 0.841351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.583367E+09 | 0.334931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.580411E+09 | 0.212301E+09 | 0.678753E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.672644E+09 | 0.00 | 0.268315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.757788E+10 | 0.524576E+11 | 0.869630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.580411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.683498E+09 | 0.111685E+11 | 0.268315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153122E+10 | 0.00 | 0.439228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134406E+10 | 0.00 | 0.216586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150669E+10 | 0.00 | 0.532401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139472E+10 | 0.224224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158511E+10 | 0.129843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.180023E+10 | 0.265383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.180242E+10 | 0.298344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178886E+10 | 0.244801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153088E+10 | 0.172826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139902E+10 | 0.303856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133993E+10 | 0.00 | 0.484355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160457E+10 | 0.00 | 0.645483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186277E+11 | 0.116401E+12 | 0.140297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180242E+10 | 0.298344E+11 | 0.645483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.667195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.596152E+09 | 0.00 | 0.00 | 0.00 | 2837471.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.662578E+09 | 0.00 | 0.00 | 0.00 | 50254521.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.581261E+09 | 0.00 | 0.00 | 0.00 | 0.650624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.616976E+09 | 0.00 | 0.00 | 0.00 | 0.161132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.671034E+09 | 0.00 | 0.00 | 0.00 | 0.250347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.656302E+09 | 0.00 | 0.00 | 0.00 | 0.276196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.683498E+09 | 0.00 | 0.00 | 0.00 | 0.256361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.606461E+09 | 0.00 | 0.00 | 0.00 | 0.203801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.583367E+09 | 0.00 | 0.00 | 0.00 | 0.804300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.580411E+09 | 0.00 | 0.00 | 0.00 | 52011697.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.672644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.757788E+10 | 0.00 | 0.00 | 0.00 | 0.130384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.580411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.683498E+09 | 0.00 | 0.00 | 0.00 | 0.276196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.153122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139472E+10 | 0.00 | 0.00 | 0.00 | 0.614982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158511E+10 | 0.00 | 0.00 | 0.00 | 0.352327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.180023E+10 | 0.00 | 0.00 | 0.00 | 0.740664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.180242E+10 | 0.00 | 0.00 | 0.00 | 0.798575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178886E+10 | 0.00 | 0.00 | 0.00 | 0.655452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153088E+10 | 0.00 | 0.00 | 0.00 | 0.456840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139902E+10 | 0.00 | 0.00 | 0.00 | 0.801660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186277E+11 | 0.00 | 0.00 | 0.00 | 0.314552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180242E+10 | 0.00 | 0.00 | 0.00 | 0.798575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.510181E+09 | 0.00 | 0.00 | 72.05 | 0.00 | 0.786571E+09 | 1195612.43 | 0.00 | 0.12 |
February | 0.523240E+09 | 0.00 | 0.00 | 50546.23 | 0.00 | 0.481117E+09 | 87218695.90 | 0.00 | 0.15 |
March | 0.661914E+09 | 0.00 | 0.00 | 567439.94 | 0.00 | 0.162995E+09 | 0.511430E+09 | 0.00 | 0.25 |
April | 95008163.60 | 40604824.22 | 0.00 | 3480257.97 | 0.00 | 0.00 | 0.126183E+10 | 0.00 | 0.37 |
May | 3959308.94 | 0.225510E+09 | 0.00 | 4879231.36 | 0.00 | 0.00 | 0.727456E+09 | 0.00 | 0.35 |
June | 12305.18 | 0.581299E+09 | 0.00 | 5355609.79 | 0.00 | 0.00 | 0.153119E+09 | 0.00 | 0.26 |
July | 0.00 | 0.146475E+10 | 0.00 | 2866630.45 | 0.00 | 0.00 | 15502032.90 | 0.00 | 0.26 |
August | 40598.96 | 0.854124E+09 | 0.00 | 4749990.36 | 0.00 | 0.00 | 0.204595E+09 | 0.00 | 0.35 |
September | 719643.47 | 0.642884E+09 | 0.00 | 4770274.05 | 67.16 | 0.00 | 0.436361E+09 | 0.00 | 0.35 |
October | 19989549.48 | 0.132139E+09 | 0.00 | 4913223.98 | 0.00 | 0.00 | 0.195502E+10 | 0.00 | 0.51 |
November | 0.494360E+09 | 0.00 | 0.00 | 1284715.68 | 0.00 | 0.135737E+09 | 0.102627E+10 | 0.00 | 0.29 |
December | 0.554248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842088E+09 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.286367E+10 | 0.394131E+10 | 0.00 | 32917991.84 | 67.16 | 0.240851E+10 | 0.637999E+10 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.661914E+09 | 0.146475E+10 | 0.00 | 5355609.79 | 67.16 | 0.842088E+09 | 0.195502E+10 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.315861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217161E+09 | 0.00 | 0.00 | 0.17 |
February | 0.262819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83981119.63 | 0.00 | 0.00 | 0.18 |
March | 0.286969E+10 | 0.00 | 0.00 | 0.00 | 1150480.44 | 28372439.16 | 0.00 | 0.00 | 0.19 |
April | 0.190825E+10 | 42382547.76 | 0.00 | 1920470.10 | 10505634.67 | 0.00 | 0.630179E+09 | 0.00 | 0.23 |
May | 0.438078E+09 | 0.310772E+09 | 0.00 | 8259885.19 | 0.00 | 0.00 | 0.156338E+10 | 0.00 | 0.33 |
June | 15023773.21 | 0.121170E+10 | 0.00 | 10232671.73 | 1710.83 | 0.00 | 0.116285E+10 | 0.00 | 0.35 |
July | 1159698.46 | 0.237466E+10 | 0.00 | 4895002.11 | 129153.54 | 0.00 | 0.774200E+09 | 0.00 | 0.35 |
August | 62564517.98 | 0.129220E+10 | 0.00 | 9458730.09 | 8692.47 | 0.00 | 0.166150E+10 | 0.00 | 0.39 |
September | 0.171875E+09 | 0.801519E+09 | 0.00 | 10190448.74 | 0.00 | 0.00 | 0.155971E+10 | 0.00 | 0.36 |
October | 0.197214E+10 | 0.124747E+09 | 0.00 | 2974906.93 | 0.00 | 0.00 | 0.187764E+10 | 0.00 | 0.30 |
November | 0.311121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19569947.05 | 0.00 | 0.00 | 0.17 |
December | 0.331588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349369E+09 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.196527E+11 | 0.615799E+10 | 0.00 | 47932114.90 | 11795671.95 | 0.698453E+09 | 0.922947E+10 | 0.00 | 0.27 |
Minimum of Months | 1159698.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.331588E+10 | 0.237466E+10 | 0.00 | 10232671.73 | 10505634.67 | 0.349369E+09 | 0.187764E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:42:37
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.627145E+12 | 0.285855E+11 | 0.00 | 0.467372E+10 | 0.346895E+10 |
February | 0.663279E+12 | 0.238036E+11 | 0.00 | 0.380380E+10 | 0.196581E+10 |
March | 0.102656E+13 | 0.316400E+11 | 0.00 | 0.423382E+10 | 0.986269E+09 |
April | 0.114469E+13 | 0.286150E+11 | 0.00 | 0.380816E+10 | 0.614587E+10 |
May | 0.125613E+13 | 0.417021E+11 | 0.00 | 0.223110E+10 | 0.248586E+11 |
June | 0.124455E+13 | 0.559414E+11 | 0.00 | -442175550.7 | 0.466546E+11 |
July | 0.118204E+13 | 0.537203E+11 | 0.00 | -0.305375E+10 | 0.527573E+11 |
August | 0.110014E+13 | 0.526519E+11 | 0.00 | -234932068.1 | 0.447906E+11 |
September | 0.100680E+13 | 0.409752E+11 | 0.00 | 0.754293E+09 | 0.329478E+11 |
October | 0.865008E+12 | 0.328937E+11 | 0.00 | 0.557931E+10 | 0.807926E+10 |
November | 0.661549E+12 | 0.316701E+11 | 0.00 | 0.478843E+10 | 0.832935E+09 |
December | 0.535658E+12 | 0.241830E+11 | 0.00 | 0.506158E+10 | 0.504867E+10 |
Annual Sum or Average | 0.113136E+14 | 0.446382E+12 | 0.00 | 0.312034E+11 | 0.228537E+12 |
Minimum of Months | 0.535658E+12 | 0.238036E+11 | 0.00 | -0.305375E+10 | 0.832935E+09 |
Maximum of Months | 0.125613E+13 | 0.559414E+11 | 0.00 | 0.557931E+10 | 0.527573E+11 |