Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 10:41:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 581.29 | 120.22 | 120.22 |
Net Site Energy | 581.29 | 120.22 | 120.22 |
Total Source Energy | 1411.53 | 291.93 | 291.93 |
Net Source Energy | 1411.53 | 291.93 | 291.93 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 206.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 96.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 375.14 | 206.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 206.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 23.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 96.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 6.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 25.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 206.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 23.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 96.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 31.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 25.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 32.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 16.71 | 42.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 77.59 | 42.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 32.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 16.71 | 42.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 77.59 | 42.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 375.138 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 375.138 | 100.00 |
Total On-Site and Utility Electric Sources | 375.138 | 100.00 |
Total Electricity End Uses | 375.138 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 52.67 |
Time Setpoint Not Met During Occupied Cooling | 10.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2965.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 76.79 |
Skylight-Roof Ratio [%] | 1.67 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 9.3385 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.7674 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 5.0950 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 5.0950 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 9.3385 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.7674 | 46.45 | 2.5587 | |
Total | 4835.13 | 5.0950 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 5.0950 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 5.0950 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-15:00 | 16-JAN-17:49 | - | - | - | - | - | - | - | - | - | - | 19-JUN-11:50 |
Heating | 0.00 | 137230.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13243.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6910.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5053.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 481.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 35723.96 | 137230.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 137230.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 13243.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 6910.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2748.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 481.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 223.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 74.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 304.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 195.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 101.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 79.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1188.06 | 223.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 46.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 62.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 245.71 | 46.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 46.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 62.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 245.71 | 46.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.29 |
ZONE2 FINE STORAGE DIRECT AIR | 2.87 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 3.08 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 3.08 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 103667.89 |
PSZ-OFFICE HEATING COIL | 27323.28 |
PSZ-FINE STORAGE HEATING COIL | 79698.44 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 103667.90 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.00 | 1.000000 | 1.29 |
PSZ-FINE STORAGE | 2.87 | 2.87 | 2.87 | 2.87 | 2.87 | 2.87 | 1.00 | 1.00 | 2.87 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.29 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.87 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.29 | 1431.06 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.87 | 3069.48 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.29 | 1.29 | 1.29 | 0.853082 | 21396.27 | 27323.28 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.87 | 2.87 | 2.87 | 1.89 | 55383.80 | 79698.44 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.29 | 0.646274 | 0.861700 | 21396.27 | 10698.14 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 2.87 | 1.43 | 1.91 | 55383.80 | 27691.90 | 0.790220 | 0.790220 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 9.339 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 17.412 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.767 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.326 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2212.108 | 9.339 | 173.516 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2212.108 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 12073.795 | 3.767 | 174.983 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 12073.795 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2163 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.4974 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4322 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.044 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.622 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.010 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.214 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4892 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.18741198E-13 | -0.13599760E-18 | 0.18147593E-18 | 0.0000000 |
2 | 1 | -5.2160601 | 0.51384690E-04 | -0.74050972E-04 | 0.35929797E-14 |
3 | 0 | 5.4323994 | 0.21628790 | 0.21641333 | |
4 | 2 | 0.53330648E-11 | 0.17872838E-15 | 0.22136589E-15 | 0.0000000 |
5 | 1 | -5.2159880 | 0.41449123E-04 | -0.32205733E-04 | 0.68736940E-11 |
6 | 0 | 5.7134214 | 0.49739196 | 0.49746561 | |
7 | 4 | 0.79186034E-12 | 0.10405078E-15 | -0.20960309E-14 | 0.11445272E-15 |
8 | 3 | -0.38819576E-03 | 0.30481201E-06 | -0.56344247E-04 | 0.15193845E-12 |
9 | 2 | 1.7477700 | 0.66393353E-02 | 1.1467116 | -0.74423695E-04 |
10 | 1 | -7.1178476 | 0.17160399 | -17.138090 | 0.33498210 |
11 | 0 | 5.6579463 | 0.10923685 | 16.278915 | |
12 | 4 | 0.65556131E-12 | 0.57298371E-15 | -0.14028959E-14 | 0.12439065E-15 |
13 | 3 | -0.34087882E-03 | 0.75102955E-06 | -0.49042705E-04 | 0.12583838E-12 |
14 | 2 | 1.6337693 | 0.17263784E-01 | 1.0601096 | -0.65347397E-04 |
15 | 1 | -7.2734424 | 0.46143774 | -16.581274 | 0.31301327 |
16 | 0 | 6.4190060 | 0.30028979 | 16.300205 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.0441747 | 2.0441747 | 2.0441747 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.14028959E-14 | 0.57298371E-15 | 0.65556131E-12 | 0.12439065E-15 |
85 | 3 | -0.49042705E-04 | 0.75102955E-06 | -0.34087882E-03 | 0.12583838E-12 |
86 | 2 | 1.0601096 | 0.17263784E-01 | 1.6337693 | -0.65347397E-04 |
87 | 1 | -16.581274 | 0.46143774 | -7.2734424 | 0.31301327 |
88 | 0 | 16.300205 | 0.30028979 | 6.4190060 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.379_SHGC_SOUTH_0.36 | 34 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.361 | ||
2 | NONRESWINDOW_U_0.379_SHGC_NORTH_0.36 | 35 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.361 | ||
3 | NONRESWINDOW_U_0.379_SHGC_EAST_0.36 | 36 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.361 | ||
4 | NONRESWINDOW_U_0.379_SHGC_WEST_0.36 | 37 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.361 | ||
5 | SKYLIGHT_U_0.5_SHGC_0.4 | 38 | 1 | VerySmooth | 2.843 | 2.843 | 1.000 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.46913E-002 | 0.27318 | 0.51792 | 0.51792 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.46913E-002 | 0.27318 | 0.51792 | 0.51792 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.46913E-002 | 0.27318 | 0.51792 | 0.51792 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.46913E-002 | 0.27318 | 0.51792 | 0.51792 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | CurtainWall | 2.775 | 0.408 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.537 | 0.515 | 0.496 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3947E-005 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6815E-004 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4636E-005 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1005E-004 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4600E-005 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7255E-004 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5724E-005 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5867E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5723E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.4087E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3202E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.7967E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4958E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8900E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3414E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4540E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5804E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5546E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9994E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7155E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.5447E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2040E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8792E-004 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6675E-005 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.9630E-004 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.7113E-005 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3226E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3115E-005 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0592E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3276E-005 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3392E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0724E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.2697E-004 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3077E-005 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.5640E-004 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5493E-005 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.0662E-004 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9048E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9718E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6272E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.0334E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.3934E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.4747E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5027E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5990E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4124E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7955E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4789E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0273E-003 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5140E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2360E-003 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6512E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2652E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4497E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3679E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4861E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9542E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6978E-005 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2187E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0325E-005 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9375E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0294E-005 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1133E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6508E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6129E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0262E-004 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5180E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1248E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3382E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8407E-005 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5808E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1684E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8359E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3493E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.8397E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7172E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.2089E-004 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4793E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6286E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1734E-005 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0046E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0663E-004 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6497E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.6971E-004 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8710E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.7213E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3102E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8162E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2497E-005 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8114E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0952E-005 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1020E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.9870E-005 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5958E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0760E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8446E-004 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2216E-005 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8306E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8109E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8053E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8374E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5417E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7398E-005 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1825E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0226E-005 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.4906E-004 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.6662E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0045E-004 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7430E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1279E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5431E-005 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2422E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8942E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2227E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2784E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9905E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1533E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4800E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1321E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9767E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8431E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8136E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7119E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9621E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2631E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7242E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4814E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2243E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8770E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0525E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2707E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9016E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1789E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0358E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1298E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2681E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8894E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7542E-004 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3292E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9306E-004 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8973E-004 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3664E-004 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5955E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2983E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0737E-004 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0296E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1208E-004 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7848E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6648E-005 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2385E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1757E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1077E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1189E-004 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6170E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1777E-004 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5695E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8295E-005 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6878E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1734E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2731E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0549E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.3202E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5440E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4193E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9339E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9772E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5935E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1887E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5643E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4523E-003 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5942E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7834E-003 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6132E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.3606E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6979E-005 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3777E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7287E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0957E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7919E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3603E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0491E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8481E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0720E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4148E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2234E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0944E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4334E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9973E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1885E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4478E-005 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0708E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6592E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6340E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9232E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6803E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8098E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6485E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1053E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6898E-005 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5662E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3410E-003 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0625E-004 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5007E-003 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0116E-004 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3620E-003 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2308E-004 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2032E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0902E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2710E-003 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7521E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4110E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8844E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3288E-003 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7466E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2112E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4671E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1626E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1365E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1117E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9443E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6511E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4460E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7473E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9066E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0834E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3682E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0174E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7739E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5890E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0070E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7498E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5506E-004 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2852E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1668E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0834E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9129E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1876E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5142E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7446E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1536E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4551E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0939E-004 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4288E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0002E-004 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0650E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3442E-004 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2227E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1450E-004 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4168E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1511E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3827E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7951E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0262E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7125E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2269E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1533E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2308E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3986E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0220E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4351E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1153E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2083E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7501E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6479E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8484E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9943E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6027E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7211E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4372E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2392E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7296E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1506E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8314E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1368E-003 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5827E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7207E-004 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3888E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5406E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7351E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5793E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0583E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7382E-005 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8848E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6818E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1393E-003 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1409E-004 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1889E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1418E-004 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0010E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6432E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8187E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1200E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1236E-003 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2158E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1930E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0887E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2584E-004 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0194E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0709E-004 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2409E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3385E-004 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3076E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7289E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2588E-004 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3258E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0206E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6968E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6764E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6072E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2397E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0178E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4028E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8295E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9894E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7053E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6092E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2809E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6355E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4795E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1676E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2578E-004 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6877E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0732E-004 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4372E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3592E-004 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7772E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7264E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8999E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3063E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6079E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1789E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3031E-004 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5191E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3495E-004 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5891E-005 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3195E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4568E-004 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0995E-004 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1897E-004 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2284E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2354E-004 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7651E-005 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0257E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3913E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2787E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3487E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1700E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1454E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5920E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3432E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5813E-005 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5594E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3217E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8418E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6977E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9628E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6413E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.1549E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0101E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0338E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4533E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1474E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1882E-004 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5388E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2425E-004 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8302E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0246E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6189E-005 |
369 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.5894E-003 |
370 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.5632E-004 |
371 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.0095E-003 |
372 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.9573E-004 |
373 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.7709E-003 |
374 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.7206E-004 |
375 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.8313E-003 |
376 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.9720E-004 |
377 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.6842E-004 |
378 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.0420E-003 |
379 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.2046E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.0946E-003 |
381 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.8389E-004 |
382 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.0854E-003 |
383 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.9154E-004 |
384 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.8079E-003 |
385 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.9438E-003 |
386 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.5607E-004 |
387 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.6935E-003 |
388 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.8073E-004 |
389 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.4174E-003 |
390 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.1259E-004 |
391 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.5511E-003 |
392 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0287E-004 |
393 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.9725E-003 |
394 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.5618E-004 |
395 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.7067E-003 |
396 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.8078E-004 |
397 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.3843E-003 |
398 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1253E-004 |
399 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.5510E-003 |
400 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.0287E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10768.54250 | 12922.25100 | 1.07712 | 1.29255 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 33.75000 | 5.69729E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8388.33267 | 10065.99920 | 0.28623 | 0.34348 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90000 | 2.34317E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 30659.70311 | 36791.64374 | 2.39045 | 2.86854 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.69938E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 23604.16536 | 28324.99844 | 0.67855 | 0.81426 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -7.90000 | 2.34317E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.96500 | 5.69918E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 86389.91660 | 103667.89992 | 2.56628 | 3.07953 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16329.98 | 1.29255 | 1.29255 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9424.68 | 0.34348 | 0.34348 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 45516.03 | 2.86854 | 2.86854 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 29723.09 | 0.81426 | 0.81426 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.29255 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.86854 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.07953 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 3.07953 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 103667.89273 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 103667.89992 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.29255 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.29255 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.29255 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.29255 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.29255 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.29255 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.86854 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.86854 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.86854 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.86854 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.86854 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.86854 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.29255 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.86854 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.29255 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.29255 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1431.05639 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.29255 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.29255 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.29255 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85308 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.29255 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64627 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.86170 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21396.27000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10698.13500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21396.27000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27323.27552 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 27323.27552 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.86854 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.86854 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3069.47783 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.86854 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.86854 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.86854 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.89324 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.86854 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.43427 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.91236 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 55383.80000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 27691.90000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79022 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79022 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 55383.80000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 79698.44238 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 79698.44238 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 20393.3 | 11.40 | 11.14 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 53156.7 | 11.58 | 11.32 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1274530576 | 0.1352297230 | Pass | Pass | 0.1875789748 | 0.5343668887 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2965677792 | 0.3523218994 | Pass | Pass | 1.3612164320 | 8.2414971225 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 5.2552674922E-002 | 6.3161114660E-002 | Pass | Pass | 3.9568988542E-002 | 0.1217923417 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 11182.63 | 442.06 | 0.00 | 49.10 | 168.51 | 11842.35 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.210 | 0.216 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.466 | 0.497 | 3204.84 | 3148.87 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.379_SHGC_WEST_0.36 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.153 | 0.361 | 0.397 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.379_SHGC_WEST_0.36 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.153 | 0.361 | 0.397 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.379_SHGC_NORTH_0.36 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.153 | 0.361 | 0.397 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.379_SHGC_NORTH_0.36 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.153 | 0.361 | 0.397 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.26 | 0.00 | 1.75 | 1.75 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.537 | 0.515 | 0.496 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 94.45 | 4.466 | 0.482 | 0.490 | |||||||||||||||||
North Total or Average | 6.51 | 2.153 | 0.361 | 0.397 | |||||||||||||||||
Non-North Total or Average | 87.94 | 4.637 | 0.491 | 0.497 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 9.3385 | 236.88 | 2212.11 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 32.39 | 0.0000 | Y | 13.45 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 21.36 | 0.0000 | Y | 41.49 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.7674 | 3204.84 | 12073.79 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 18.17 | 0.0000 | Y | 41.18 |
Interior Lighting Total | 5.0950 | 4835.13 | 24634.88 | 96.12 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10348.98 | 2587.24 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10348.98 | 2587.24 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 12073.79 | 3018.45 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 12073.79 | 3018.45 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.29 | 2212.11 | 641.51 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.10 | 2212.11 | 221.21 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 41.81 | 41.81 | 0.97 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.71 | 62.76 | 50.72 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.71 | 48.85 | 10.01 | |
Exterior Lighting Total | 5520.82 | 61.70 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21396.27 | 17131.14 | 4265.13 | 0.80 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 55383.80 | 43765.39 | 11618.41 | 0.79 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 20393.3 | 11.40 | 11.14 | ||||
PSZ-FINE STORAGE COOLING COIL | 53156.7 | 11.58 | 11.32 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 103667.89 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 27323.28 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 79698.44 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.08 | 286.12 | 92.91 | 1.00 | 3.35 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.29 | 1431.06 | 1107.16 | 1.00 | 1.34 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.87 | 3069.48 | 1070.05 | 1.00 | 1.27 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10768.54 | 12922.25 | 54.55 | 1.077 | 1.293 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 23.90 | 23.90 | 0.00819 | 33.75 | 0.00570 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 30659.70 | 36791.64 | 26.40 | 2.390 | 2.869 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00807 | 35.10 | 0.00570 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 35.01 | 0.00579 | 34.97 | 0.00570 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8388.33 | 10066.00 | 42.49 | 0.286 | 0.343 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00772 | -7.90 | 0.00234 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 23604.17 | 28325.00 | 20.33 | 0.679 | 0.814 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00644 | -7.90 | 0.00234 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 86389.92 | 103667.90 | 32.35 | 2.566 | 3.080 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00587 | -7.90 | 0.00234 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.29 | 1.29 | 0.34 | 0.34 | 1.2925 | 1.2925 | 1.2925 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.87 | 2.87 | 0.81 | 0.81 | 2.8685 | 2.8685 | 2.8685 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 103667.893 | 103667.893 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 103667.89 | 103667.89 | 3.079534 | 10.00 | 6.49 | 0.00586957 | 43.33 | 19.83 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 10.00 | 0.00586957 | 63.4482 | 103667.90 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 21396.270 | 17131.138 | 1.292550 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 10698.14 | 10698.13 | 0.861700 | 25.80 | 14.58 | 0.00799235 | 12.00 | 9.53 | 0.00799235 | 34.11 | 0.00569784 | 15.46 | 11.8701 | 23.90 | 0.00818976 | 36.4985 | 10757.14 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 27323.276 | 27323.276 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 27323.28 | 27323.28 | 1.292549 | 18.76 | 11.49 | 0.00729562 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 7.9134 | 21.10 | 0.00772121 | 40.8240 | 8388.33 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 55383.800 | 43765.386 | 2.868540 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27691.90 | 27691.90 | 1.912360 | 29.00 | 15.41 | 0.00771998 | 12.00 | 9.26 | 0.00771998 | 35.10 | 0.00569938 | 15.77 | 22.2088 | 26.70 | 0.00807114 | 30.4563 | 30659.70 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 79698.442 | 79698.442 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 79698.44 | 79698.44 | 2.868544 | 12.08 | 7.37 | 0.00583675 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 14.8058 | 15.56 | 0.00644390 | 48.3435 | 23604.17 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 103667.893 | 103667.893 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 3.079534 | 3.04999766 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 103667.89 | 103667.89 | 1.0000 | 3.04999766 | 3.079534 | 10.00 | 6.49 | 0.00586957 | 24834.5 | 43.33 | 19.83 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 103667.89 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 10.00 | 0.00586957 | 10.00 | 0.00586957 | 63.4482 | 103667.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21396.270 | 17131.138 | 1.292550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6974 | 1004.8586 | 0.9904 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.292549 | 1.28015156 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | Sensible | 10698.14 | 10698.13 | 1.0000 | 0.85343534 | 0.861700 | 25.80 | 14.58 | 0.00799235 | 46301.0 | 12.00 | 9.53 | 0.00799235 | 32224.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10698.14 | 34.11 | 0.00569784 | 15.46 | 0.10228463 | 11.8701 | 23.90 | 0.00818976 | 23.90 | 0.00818976 | 36.4985 | 10757.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27323.276 | 27323.276 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.292549 | 1.28015156 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 27323.28 | 27323.28 | 1.0000 | 1.28015156 | 1.292549 | 18.76 | 11.49 | 0.00729562 | 37350.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27323.28 | -7.90 | 0.00234317 | -7.90 | 0.10228463 | 7.9134 | 21.05 | 0.00772121 | 21.10 | 0.00772121 | 40.8240 | 8388.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 55383.800 | 43765.386 | 2.868540 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1911 | 1004.8586 | 0.9904 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.868544 | 2.84103163 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 27691.90 | 27691.90 | 1.0000 | 1.89401835 | 1.912360 | 29.00 | 15.41 | 0.00771998 | 48867.4 | 12.00 | 9.26 | 0.00771998 | 31537.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27691.90 | 35.10 | 0.00569938 | 15.77 | 0.42471127 | 22.2088 | 26.70 | 0.00807114 | 26.70 | 0.00807114 | 30.4563 | 30659.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 79698.442 | 79698.442 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.868544 | 2.84103163 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 79698.44 | 79698.44 | 1.0000 | 2.84103163 | 2.868544 | 12.08 | 7.37 | 0.00583675 | 26869.9 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 79698.44 | -7.90 | 0.00234317 | -7.90 | 0.42471127 | 14.8058 | 15.56 | 0.00644390 | 15.56 | 0.00644390 | 48.3435 | 23604.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.29 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.87 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2610.00 | 2273.00 | 1525.33 |
ZONE2 FINE STORAGE | 3170.17 | 2855.00 | 2500.83 |
ZONE3 BULK STORAGE | 3254.17 | 3274.67 | 2962.33 |
Facility | 3283.83 | 3391.50 | 2965.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 50.83 | 10.67 | 44.00 | 10.50 |
ZONE2 FINE STORAGE | 251.50 | 50.50 | 19.33 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 287.50 | 61.17 | 52.67 | 10.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.638 | 0.297 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.560 | 0.226 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.117 | 0.000 | 0.563 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.54 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2310938.39 | 0.00 | 2310938.39 | 1813110.89 | 4124049.28 | 3225648.14 | 5626.60 | 2363.02 | 770.38 | 0.00 |
ZONE2 FINE STORAGE | 6042085.50 | 0.00 | 6042085.50 | 6671322.63 | 12713408.12 | 13393694.68 | 5689.37 | 2597.92 | 472.71 | 21.47 |
ZONE3 BULK STORAGE | 0.00 | 0.11E+09 | 0.11E+09 | 32230562.95 | 0.14E+09 | 30805497.77 | 7256.93 | 33.59 | 1469.48 | 4974.41 |
Total Facility | 8353023.89 | 0.11E+09 | 0.12E+09 | 40714996.47 | 0.16E+09 | 47424840.58 | 7936.64 | 2850.77 | 2356.69 | 4974.51 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1765 | 0.0000 | 0.1765 | 0.0826 | 0.2591 | 0.1023 | 502.60 | 2363.02 | 770.38 |
ZONE2 FINE STORAGE | 0.4538 | 0.0000 | 0.4538 | 0.1837 | 0.6375 | 0.4247 | 586.67 | 2597.92 | 451.41 |
ZONE3 BULK STORAGE | 0.0000 | 5.3036 | 5.3036 | 1.1374 | 6.4409 | 0.9768 | 2781.59 | 12.58 | 841.83 |
Total Facility | 0.6303 | 5.3036 | 5.9339 | 1.4036 | 7.3375 | 1.5038 | 2812.64 | 2829.77 | 1711.62 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2266763.54 | 0.00 | 2266763.54 | 3225648.14 | 7989.62 | 0.67 | 769.72 | 0.00 |
PSZ-FINE STORAGE | 5926719.94 | 0.00 | 5926719.94 | 13393694.68 | 8287.29 | 1.00 | 471.71 | 21.47 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1732 | 0.0000 | 0.1732 | 0.1023 | 2865.62 | 0.67 | 769.72 |
PSZ-FINE STORAGE | 0.4451 | 0.0000 | 0.4451 | 0.4247 | 3184.59 | 1.00 | 450.41 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2898.25 | 249.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2949.52 | 138.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1900 | 0.3173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5166 | 0.7680 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 446 |
Defaulted Fields | 391 |
Fields with Defaults | 1172 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 375.14 | 1565.96 | 16-JAN-11:40 | 35723.96 | 28-JUN-16:00 |
Electricity:Building | 238.80 | 1084.96 | 16-JAN-09:30 | 20559.28 | 27-SEP-15:00 |
Electricity:Zone:ZONE1 OFFICE | 42.61 | 520.87 | 01-JAN-00:10 | 3190.10 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 232.63 | 1084.96 | 16-JAN-09:30 | 19728.80 | 21-DEC-15:40 |
InteriorLights:Electricity | 96.12 | 615.08 | 16-JAN-09:30 | 9693.63 | 21-DEC-15:40 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 13.45 | 51.00 | 01-JAN-00:10 | 1355.05 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 96.12 | 615.08 | 16-JAN-09:30 | 9693.63 | 21-DEC-15:40 |
LightsWired:InteriorLights:Electricity | 96.12 | 615.08 | 16-JAN-09:30 | 9693.63 | 21-DEC-15:40 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 13.45 | 51.00 | 01-JAN-00:10 | 1355.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 96.12 | 615.08 | 16-JAN-09:30 | 9693.63 | 21-DEC-15:40 |
Electricity:Zone:ZONE2 FINE STORAGE | 41.49 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 41.49 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 41.49 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 154.70 | 264.11 | 16-JAN-09:30 | 13872.92 | 20-SEP-14:40 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 41.18 | 264.11 | 16-JAN-09:30 | 4490.00 | 02-JAN-15:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 41.18 | 264.11 | 16-JAN-09:30 | 4490.00 | 02-JAN-15:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 31.97 | 0.00 | 01-JAN-08:50 | 5053.40 | 28-JUN-16:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 6.17 | 0.00 | 01-JAN-00:10 | 2305.29 | 12-JUN-17:10 |
Ventilation (simple):Fans:Electricity | 6.17 | 0.00 | 01-JAN-00:10 | 2305.29 | 12-JUN-17:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 6.17 | 0.00 | 01-JAN-00:10 | 2305.29 | 12-JUN-17:10 |
ElectricityPurchased:Facility | 375.14 | 1565.96 | 16-JAN-14:20 | 35723.96 | 28-JUN-16:00 |
ElectricityPurchased:Plant | 375.14 | 1565.96 | 16-JAN-14:20 | 35723.96 | 28-JUN-16:00 |
Cogeneration:ElectricityPurchased | 375.14 | 1565.96 | 16-JAN-14:20 | 35723.96 | 28-JUN-16:00 |
General:Cogeneration:ElectricityPurchased | 375.14 | 1565.96 | 16-JAN-14:20 | 35723.96 | 28-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 375.14 | 1565.96 | 16-JAN-14:20 | 35723.96 | 28-JUN-16:00 |
ElectricityNet:Plant | 375.14 | 1565.96 | 16-JAN-14:20 | 35723.96 | 28-JUN-16:00 |
Cogeneration:ElectricityNet | 375.14 | 1565.96 | 16-JAN-14:20 | 35723.96 | 28-JUN-16:00 |
General:Cogeneration:ElectricityNet | 375.14 | 1565.96 | 16-JAN-14:20 | 35723.96 | 28-JUN-16:00 |
Electricity:HVAC | 49.46 | 0.00 | 01-JAN-08:50 | 15991.94 | 28-JUN-16:00 |
General:Fans:Electricity | 25.80 | 0.00 | 01-JAN-08:50 | 3142.33 | 17-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 23.66 | 0.00 | 01-JAN-00:10 | 13243.84 | 28-JUN-16:00 |
General:Cooling:Electricity | 23.66 | 0.00 | 01-JAN-00:10 | 13243.84 | 28-JUN-16:00 |
ExteriorLights:Electricity | 61.70 | 0.00 | 01-JAN-07:20 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.70 | 0.00 | 01-JAN-07:20 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 25.17 | 481.00 | 17-JAN-06:30 | 2361.98 | 07-FEB-12:20 |
WaterSystems:Electricity | 25.17 | 481.00 | 17-JAN-06:30 | 2361.98 | 07-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 25.17 | 481.00 | 17-JAN-06:30 | 2361.98 | 07-FEB-12:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 206.15 | 0.00 | 01-JAN-08:50 | 137230.45 | 16-JAN-17:50 |
NaturalGas:HVAC | 206.15 | 0.00 | 01-JAN-08:50 | 137230.45 | 16-JAN-17:50 |
Heating:NaturalGas | 206.15 | 0.00 | 01-JAN-08:50 | 137230.45 | 16-JAN-17:50 |
General:Heating:NaturalGas | 206.15 | 0.00 | 01-JAN-08:50 | 137230.45 | 16-JAN-17:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-11:50 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-11:50 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-11:50 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-11:50 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-11:50 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-11:50 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-11:50 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-11:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 490.22 | 0.00 | 01-JAN-08:50 | 214909.36 | 16-JAN-17:50 |
EnergyTransfer:Building | 244.85 | 0.00 | 01-JAN-08:50 | 108063.30 | 16-JAN-17:50 |
EnergyTransfer:Zone:ZONE1 OFFICE | 47.41 | 0.00 | 01-JAN-00:10 | 17498.33 | 17-JAN-06:10 |
Heating:EnergyTransfer | 150.87 | 0.00 | 01-JAN-08:50 | 108063.30 | 16-JAN-17:50 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 15.83 | 0.00 | 01-JAN-00:10 | 17498.33 | 17-JAN-06:10 |
General:Heating:EnergyTransfer | 150.87 | 0.00 | 01-JAN-08:50 | 108063.30 | 16-JAN-17:50 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 15.83 | 0.00 | 01-JAN-00:10 | 17498.33 | 17-JAN-06:10 |
Cooling:EnergyTransfer | 93.97 | 0.00 | 01-JAN-00:10 | 35355.51 | 22-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 31.58 | 0.00 | 01-JAN-00:10 | 10068.64 | 21-JUL-17:00 |
General:Cooling:EnergyTransfer | 93.97 | 0.00 | 01-JAN-00:10 | 35355.51 | 22-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 31.58 | 0.00 | 01-JAN-00:10 | 10068.64 | 21-JUL-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 109.61 | 0.00 | 01-JAN-00:10 | 33957.82 | 16-JAN-17:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 47.21 | 0.00 | 01-JAN-00:10 | 33957.82 | 16-JAN-17:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 47.21 | 0.00 | 01-JAN-00:10 | 33957.82 | 16-JAN-17:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 62.40 | 0.00 | 01-JAN-00:10 | 26035.96 | 22-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 62.40 | 0.00 | 01-JAN-00:10 | 26035.96 | 22-JUL-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 87.83 | 0.00 | 01-JAN-08:30 | 75892.47 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 87.83 | 0.00 | 01-JAN-08:30 | 75892.47 | 14-DEC-04:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 87.83 | 0.00 | 01-JAN-08:30 | 75892.47 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 245.37 | 0.00 | 01-JAN-08:50 | 106846.07 | 16-JAN-17:50 |
HeatingCoils:EnergyTransfer | 153.34 | 0.00 | 01-JAN-08:50 | 106846.07 | 16-JAN-17:50 |
CoolingCoils:EnergyTransfer | 92.04 | 0.00 | 01-JAN-00:10 | 44277.43 | 22-JUL-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 15.829 | -31.576 | 0.000 | 0.000 | 9.841 | 13.450 | 29.165 | 15.188 | 0.000 | 1.411 | 0.000 | 0.000 | -6.960 | 0.000 | -15.440 | -30.908 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 47.212 | -62.395 | 0.000 | 0.000 | 23.913 | 41.489 | 0.000 | 47.133 | 0.000 | 2.620 | 0.002 | 0.000 | -13.525 | 0.000 | -49.029 | -37.417 |
ZONE3 BULK STORAGE | 87.833 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 53.932 | 41.181 | 107.344 | 672.769 | 0.000 | 12.000 | 0.010 | 0.000 | -198.547 | 0.000 | -354.057 | -422.455 |
Total Facility | 87.833 | 0.000 | 63.041 | -93.971 | 0.000 | 0.000 | 87.686 | 96.120 | 136.508 | 735.089 | 0.000 | 16.031 | 0.013 | 0.000 | -219.031 | 0.000 | -418.526 | -490.780 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 19-JUN-05:02 | 0.00 | 0.00 | 0.00 | -28405.76 | 0.00 | 0.00 | 85.92 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 28582.98 | 0.00 | -165.07 | 0.00 | -699.58 | 0.00 |
ZONE2 FINE STORAGE | 13-JUL-17:06 | 0.00 | 0.00 | 0.00 | -48124.34 | 0.00 | 0.00 | 0.00 | 415.04 | 0.00 | 1871.76 | 0.00 | 1846.68 | 43990.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-JUL-15:32 | 0.00 | 0.00 | 0.00 | -50081.70 | 0.00 | 0.00 | 0.00 | 659.10 | 469.88 | 59112.12 | 0.00 | 2145.07 | 38926.50 | 0.00 | 0.00 | 0.00 | -51230.96 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 06-FEB-06:12 | 0.00 | 0.00 | 27995.83 | 0.00 | 0.00 | 0.00 | 118.54 | 404.75 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -735.62 | 0.00 | -2104.41 | -26229.62 |
ZONE2 FINE STORAGE | 16-JAN-17:42 | 0.00 | 0.00 | 81656.67 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -987.48 | 0.00 | -13238.29 | -67730.87 |
ZONE3 BULK STORAGE | 14-DEC-04:00 | 75896.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 9975.65 | 0.00 | -24106.89 | 0.00 | -64343.40 | 0.00 |
Total Facility | 16-JAN-17:42 | 69400.50 | 0.00 | 101918.08 | 0.00 | 0.00 | 0.00 | 0.00 | 879.19 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17970.92 | 0.00 | -75013.21 | -79683.52 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2925 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2925 | 0.0791 | 1.0000 | Not calculated | 0.1023 | 0.0791 | ||
PSZ-FINE STORAGE | 2.8685 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.8685 | 0.1481 | 1.0000 | Not calculated | 0.4247 | 0.1481 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2925 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2925 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0791 | ||
PSZ-FINE STORAGE | 2.8685 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.8685 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1481 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2925 | 1.2925 | 1.2925 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8685 | 2.8685 | 2.8685 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2925 | 1.2925 | 1.2925 | 1.2925 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.8685 | 2.8685 | 2.8685 | 2.8685 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2925 | 1.2925 | 1.2925 | No | 0.1023 | 0.2978 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8685 | 2.8685 | 2.8685 | No | 0.4247 | 0.5216 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2925 | 1.2925 | 1.2925 | 1.2925 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.8685 | 2.8685 | 2.8685 | 2.8685 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 52.67 |
Number of hours cooling loads not met | 10.50 |
Number of hours not met | 63.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 206.15 | 137230.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 23.66 | 13243.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 96.12 | 9693.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.70 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 6.17 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 25.80 | 3142.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.17 | 2361.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 375.14 |
Natural Gas | 0.00 | 206.15 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 581.29 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 19.88 |
Space Heating | 0.00 |
Space Cooling | 4.89 |
Fans (All) | 6.61 |
Service Water Heating | 5.21 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 77.59 |
Subtotal | 77.59 |
Natural Gas [MJ/m2] | |
Space Heating | 42.64 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 42.64 |
Subtotal | 42.64 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 16.54 |
Space Heating | 35.46 |
Space Cooling | 4.07 |
Fans (All) | 5.50 |
Service Water Heating | 4.33 |
Receptacle Equipment | 23.48 |
Miscellaneous | 10.62 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8214.17 | 545.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8447.17 | 312.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6494.17 | 2221.33 | 44.50 | 0.00 | 0.00 |
Min | 6494.17 | 312.83 | 0.00 | 0.00 | 0.00 |
Max | 8447.17 | 2221.33 | 44.50 | 0.00 | 0.00 |
Average | 7718.50 | 1026.67 | 14.83 | 0.00 | 0.00 |
Sum | 23155.50 | 3080.00 | 44.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 77502.50 | 5216.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 129886.33 | 58974.00 | 2332.67 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 129886.33 | 58974.00 | 2332.67 | 0.00 | 0.00 |
Average | 80138.61 | 21396.83 | 777.56 | 0.00 | 0.00 |
Sum | 240415.83 | 64190.50 | 2332.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8426.67 | 333.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8294.83 | 465.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6974.00 | 1786.00 | 0.00 | 0.00 | 0.00 |
Min | 6974.00 | 333.33 | 0.00 | 0.00 | 0.00 |
Max | 8426.67 | 1786.00 | 0.00 | 0.00 | 0.00 |
Average | 7898.50 | 861.50 | 0.00 | 0.00 | 0.00 |
Sum | 23695.50 | 2584.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 75987.50 | 6731.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 141532.83 | 49660.17 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 141532.83 | 49660.17 | 0.00 | 0.00 | 0.00 |
Average | 83515.78 | 18797.22 | 0.00 | 0.00 | 0.00 |
Sum | 250547.33 | 56391.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36833434.99 | 619.83 | 21-JAN-16:00 | 9.40 | 1.90 | 0.498752E+09 | 663.59 | 05-JAN-16:10 | 9.40 | 1.90 |
February | 36835574.27 | 437.97 | 25-FEB-14:30 | 11.95 | 3.78 | 0.464627E+09 | 767.68 | 14-FEB-16:40 | 11.95 | 3.78 |
March | 48882988.56 | 538.61 | 28-MAR-16:00 | 10.00 | 7.05 | 0.559719E+09 | 768.97 | 08-MAR-16:10 | 10.00 | 7.05 |
April | 0.938553E+09 | 4100.76 | 29-APR-16:00 | 25.60 | 10.03 | 0.584892E+09 | 768.97 | 10-APR-15:00 | 25.60 | 10.03 |
May | 0.280937E+10 | 15513.95 | 19-MAY-05:03 | 16.78 | 9.42 | 0.648048E+09 | 769.01 | 23-MAY-14:30 | 18.05 | 13.93 |
June | 0.575082E+10 | 28405.58 | 19-JUN-05:02 | 12.57 | 5.17 | 0.659587E+09 | 769.08 | 26-JUN-15:30 | 35.55 | 15.63 |
July | 0.696509E+10 | 23308.43 | 21-JUL-05:01 | 20.37 | 11.73 | 0.634870E+09 | 769.08 | 05-JUL-14:50 | 20.37 | 11.73 |
August | 0.705307E+10 | 23073.68 | 19-AUG-05:01 | 19.22 | 11.93 | 0.685635E+09 | 769.08 | 21-AUG-14:09 | 32.20 | 18.41 |
September | 0.526609E+10 | 24064.52 | 13-SEP-05:02 | 14.32 | 9.69 | 0.634655E+09 | 769.05 | 05-SEP-10:09 | 14.32 | 9.69 |
October | 0.241731E+10 | 23786.64 | 06-OCT-05:02 | 12.80 | 7.64 | 0.604258E+09 | 769.03 | 03-OCT-10:30 | 12.80 | 7.64 |
November | 0.209529E+09 | 1346.99 | 02-NOV-15:00 | 17.20 | 9.31 | 0.499223E+09 | 768.96 | 02-NOV-15:00 | 16.70 | 9.78 |
December | 44830705.46 | 750.89 | 06-DEC-14:00 | 6.70 | 0.35 | 0.498330E+09 | 660.60 | 02-DEC-15:50 | 6.70 | 0.35 |
Annual Sum or Average | 0.315772E+11 | 0.697260E+10 | ||||||||
Minimum of Months | 36833434.99 | 437.97 | 6.70 | 0.35 | 0.464627E+09 | 660.60 | 6.70 | 0.35 | ||
Maximum of Months | 0.705307E+10 | 28405.58 | 25.60 | 11.93 | 0.685635E+09 | 769.08 | 35.55 | 18.41 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123565E+10 | 5633.78 | 20-JAN-11:25 | -1.7 | -1.8 | 0.719120E+09 | 1139.63 | 05-JAN-15:30 | -1.7 | -1.8 |
February | 0.132467E+10 | 4439.17 | 04-FEB-11:30 | 2.20 | -2.8 | 0.692085E+09 | 1403.11 | 14-FEB-15:00 | 22.20 | 7.86 |
March | 0.110388E+10 | 4080.56 | 24-MAR-07:10 | 1.75 | -1.4 | 0.928379E+09 | 1450.02 | 08-MAR-14:00 | 1.75 | -1.4 |
April | 0.114856E+10 | 4435.02 | 06-APR-08:70 | 4.08 | -1.7 | 0.122652E+10 | 2213.38 | 28-APR-14:50 | 24.90 | 10.40 |
May | 0.234303E+10 | 34065.96 | 28-MAY-13:45 | 24.90 | 13.71 | 0.164895E+10 | 2246.80 | 22-MAY-12:39 | 24.90 | 13.71 |
June | 0.108513E+11 | 47083.88 | 25-JUN-11:53 | 31.70 | 17.43 | 0.187501E+10 | 2246.95 | 28-JUN-15:50 | 38.80 | 14.19 |
July | 0.168047E+11 | 48124.81 | 13-JUL-17:06 | 30.13 | 17.07 | 0.185297E+10 | 2246.95 | 22-JUL-15:20 | 37.77 | 16.43 |
August | 0.145605E+11 | 47699.37 | 06-AUG-12:13 | 29.63 | 16.08 | 0.199450E+10 | 2246.93 | 15-AUG-10:00 | 26.70 | 18.28 |
September | 0.656898E+10 | 47000.28 | 03-SEP-12:03 | 30.68 | 16.87 | 0.180678E+10 | 2246.90 | 06-SEP-14:20 | 25.77 | 15.89 |
October | 0.277517E+10 | 35636.69 | 01-OCT-10:45 | 23.43 | 13.48 | 0.139731E+10 | 2246.86 | 03-OCT-13:09 | 24.60 | 14.84 |
November | 0.175151E+10 | 5114.82 | 04-NOV-08:30 | 1.70 | 0.61 | 0.812792E+09 | 1523.65 | 02-NOV-15:09 | 1.70 | 0.61 |
December | 0.192946E+10 | 5151.86 | 22-DEC-12:00 | 0.60 | -3.3 | 0.698198E+09 | 1110.06 | 02-DEC-15:09 | 0.60 | -3.3 |
Annual Sum or Average | 0.623974E+11 | 0.156526E+11 | ||||||||
Minimum of Months | 0.110388E+10 | 4080.56 | -1.7 | -3.3 | 0.692085E+09 | 1110.06 | -1.7 | -3.3 | ||
Maximum of Months | 0.168047E+11 | 48124.81 | 31.70 | 17.43 | 0.199450E+10 | 2246.95 | 38.80 | 18.28 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 | -1.2 | 0.920315E+09 | 1671.07 | 05-JAN-15:20 | 16.10 | 6.84 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.2 | -5.2 | 0.962935E+09 | 2201.80 | 15-FEB-15:30 | 17.20 | 6.59 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 2.47 | -0.8 | 0.160597E+10 | 2649.69 | 16-MAR-14:20 | 20.40 | 8.73 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.84 | 0.259616E+10 | 4879.31 | 29-APR-13:20 | 23.53 | 9.38 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.92 | 0.385895E+10 | 6401.54 | 19-MAY-15:50 | 30.00 | 12.57 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.96 | 0.539846E+10 | 9097.65 | 26-JUN-15:09 | 36.32 | 15.33 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.90 | 0.571133E+10 | 9097.65 | 20-JUL-13:50 | 36.93 | 15.64 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.86 | 0.579039E+10 | 8525.93 | 01-AUG-15:50 | 35.00 | 16.30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.47 | 0.473543E+10 | 7170.48 | 02-SEP-15:30 | 31.40 | 16.12 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.88 | 0.319534E+10 | 6302.49 | 02-OCT-14:09 | 26.78 | 15.45 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.34 | 0.139726E+10 | 2941.29 | 02-NOV-14:39 | 16.67 | 9.19 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.84 | 0.895969E+09 | 1695.07 | 02-DEC-14:39 | 11.67 | 3.46 |
Annual Sum or Average | 0.00 | 0.370685E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.2 | -5.2 | 0.895969E+09 | 1671.07 | 11.67 | 3.46 | ||
Maximum of Months | 0.00 | 0.00 | 21.95 | 16.86 | 0.579039E+10 | 9097.65 | 36.93 | 16.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.399772E+10 | 27907.78 | 23-JAN-06:22 | -3.6 |
February | 0.330216E+10 | 27995.79 | 06-FEB-06:12 | -4.8 |
March | 0.228617E+10 | 27684.22 | 06-MAR-06:01 | -2.9 |
April | 0.543020E+09 | 27649.53 | 07-APR-05:01 | 4.22 |
May | 0.102808E+09 | 27199.63 | 05-MAY-05:01 | 5.68 |
June | 13151949.52 | 766.31 | 09-JUN-06:20 | 9.63 |
July | 728295.72 | 764.76 | 21-JUL-06:05 | 22.95 |
August | 1262217.66 | 539.15 | 31-AUG-06:10 | 13.63 |
September | 10113027.48 | 797.48 | 20-SEP-06:10 | 11.33 |
October | 0.317703E+09 | 27662.35 | 26-OCT-05:01 | -2.5 |
November | 0.162515E+10 | 27752.05 | 27-NOV-06:01 | -4.4 |
December | 0.362919E+10 | 27857.68 | 22-DEC-06:12 | -6.1 |
Annual Sum or Average | 0.158292E+11 | |||
Minimum of Months | 728295.72 | 539.15 | -6.1 | |
Maximum of Months | 0.399772E+10 | 27995.79 | 22.95 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146581E+11 | 81656.27 | 16-JAN-17:42 | -1.5 |
February | 0.106124E+11 | 81496.71 | 06-FEB-05:22 | -4.4 |
March | 0.370163E+10 | 80460.25 | 04-MAR-06:11 | -1.7 |
April | 0.395933E+09 | 52731.63 | 01-APR-05:01 | 6.10 |
May | 0.164625E+09 | 2237.85 | 08-MAY-17:00 | 27.80 |
June | 63774970.33 | 1177.50 | 05-JUN-06:50 | 15.50 |
July | 25056473.23 | 1189.60 | 17-JUL-07:00 | 19.40 |
August | 55336894.71 | 1181.46 | 30-AUG-07:00 | 16.10 |
September | 94781436.14 | 1344.75 | 01-SEP-07:00 | 18.90 |
October | 0.135498E+09 | 3474.07 | 27-OCT-06:10 | -0.5 |
November | 0.354982E+10 | 80142.82 | 26-NOV-06:33 | 0.20 |
December | 0.137549E+11 | 81543.09 | 14-DEC-03:32 | -0.5 |
Annual Sum or Average | 0.472119E+11 | |||
Minimum of Months | 25056473.23 | 1177.50 | -4.4 | |
Maximum of Months | 0.146581E+11 | 81656.27 | 27.80 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331626E+11 | 72948.45 | 16-JAN-18:00 | -1.7 |
February | 0.195248E+11 | 71467.61 | 06-FEB-05:00 | -4.4 |
March | 0.162435E+10 | 33600.25 | 04-MAR-06:00 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.114523E+10 | 25599.94 | 28-NOV-04:53 | -1.1 |
December | 0.323768E+11 | 75900.75 | 14-DEC-04:00 | -1.1 |
Annual Sum or Average | 0.878337E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.331626E+11 | 75900.75 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118028E+10 | 1355.05 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.104151E+10 | 1355.05 | 01-FEB-16:00 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.119001E+10 | 1355.05 | 07-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.104623E+10 | 1224.06 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.110809E+10 | 1355.05 | 22-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.113438E+10 | 1355.05 | 01-JUN-15:50 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.107014E+10 | 1355.05 | 07-JUL-15:30 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.112290E+10 | 1224.06 | 01-AUG-10:30 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.109269E+10 | 1355.05 | 08-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.114358E+10 | 1355.05 | 04-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.111829E+10 | 1355.05 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.120209E+10 | 1355.05 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.134502E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.104151E+10 | 1224.06 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.120209E+10 | 1355.05 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.376021E+10 | 3848.58 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.335201E+10 | 3848.58 | 02-FEB-09:09 | 0.00 | 0.00 |
March | 0.362056E+10 | 3848.58 | 01-MAR-15:30 | 0.00 | 0.00 |
April | 0.321630E+10 | 3848.58 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.329339E+10 | 3527.86 | 02-MAY-08:09 | 0.00 | 0.00 |
June | 0.329229E+10 | 3848.58 | 03-JUN-08:09 | 0.00 | 0.00 |
July | 0.316391E+10 | 3848.58 | 03-JUL-08:09 | 0.00 | 0.00 |
August | 0.334161E+10 | 3848.58 | 02-AUG-08:09 | 0.00 | 0.00 |
September | 0.334335E+10 | 3848.58 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.363349E+10 | 3848.58 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.358062E+10 | 3848.58 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.389095E+10 | 3848.58 | 01-DEC-15:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.414887E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.316391E+10 | 3527.86 | 0.00 | 0.00 | |
Maximum of Months | 0.389095E+10 | 3848.58 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387783E+10 | 4490.00 | 02-JAN-15:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.338618E+10 | 4115.84 | 04-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.360672E+10 | 3961.65 | 04-MAR-16:40 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.306453E+10 | 3301.38 | 01-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.311959E+10 | 3301.38 | 22-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.318960E+10 | 3741.67 | 08-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.308187E+10 | 3301.38 | 03-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.320313E+10 | 3301.38 | 02-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.328538E+10 | 3961.65 | 08-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.370937E+10 | 3961.65 | 04-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.365662E+10 | 4490.00 | 06-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.400003E+10 | 4490.00 | 02-DEC-15:39 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.411808E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.306453E+10 | 3301.38 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.400003E+10 | 4490.00 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.118028E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231442E+10 |
February | 0.127628E+10 | 0.104151E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204024E+10 |
March | 0.149825E+10 | 0.119001E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182489E+10 |
April | 0.138726E+10 | 0.104623E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14711810.98 | 0.117096E+10 |
May | 0.144276E+10 | 0.110809E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74182483.68 | 0.101273E+10 |
June | 0.144276E+10 | 0.113438E+10 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395287E+09 | 0.515369E+09 |
July | 0.138726E+10 | 0.107014E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453263E+09 | 0.279262E+09 |
August | 0.149825E+10 | 0.112290E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319122E+09 | 0.425883E+09 |
September | 0.138726E+10 | 0.109269E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127367E+09 | 0.619197E+09 |
October | 0.138726E+10 | 0.114358E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26815015.61 | 0.125312E+10 |
November | 0.133177E+10 | 0.111829E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175510E+10 |
December | 0.138726E+10 | 0.120209E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222865E+10 |
Annual Sum or Average | 0.168137E+11 | 0.134502E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141075E+10 | 0.154398E+11 |
Minimum of Months | 0.127628E+10 | 0.104151E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279262E+09 |
Maximum of Months | 0.149825E+10 | 0.120209E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453263E+09 | 0.231442E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.376021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665192E+10 |
February | 0.300332E+10 | 0.335201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2337144.64 | 0.613930E+10 |
March | 0.352563E+10 | 0.362056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7622148.68 | 0.520300E+10 |
April | 0.326447E+10 | 0.321630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46251835.60 | 0.378688E+10 |
May | 0.339505E+10 | 0.329339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90163858.14 | 0.386324E+10 |
June | 0.339505E+10 | 0.329229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.793854E+09 | 0.234875E+10 |
July | 0.326447E+10 | 0.316391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102991E+10 | 0.144609E+10 |
August | 0.352563E+10 | 0.334161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529356E+09 | 0.204689E+10 |
September | 0.326447E+10 | 0.334335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110337E+09 | 0.269243E+10 |
October | 0.326447E+10 | 0.363349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9813284.32 | 0.406802E+10 |
November | 0.313390E+10 | 0.358062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480921E+10 |
December | 0.326447E+10 | 0.389095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597298E+10 |
Annual Sum or Average | 0.395654E+11 | 0.414887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261965E+10 | 0.490287E+11 |
Minimum of Months | 0.300332E+10 | 0.316391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144609E+10 |
Maximum of Months | 0.352563E+10 | 0.389095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102991E+10 | 0.665192E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.387783E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81262197.13 | 0.186763E+11 |
February | 0.690763E+10 | 0.338618E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202741E+09 | 0.177058E+11 |
March | 0.810895E+10 | 0.360672E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482624E+09 | 0.159713E+11 |
April | 0.750829E+10 | 0.306453E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533762E+09 | 0.148602E+11 |
May | 0.780862E+10 | 0.311959E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274003E+09 | 0.182599E+11 |
June | 0.780862E+10 | 0.318960E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181964E+09 | 0.130843E+11 |
July | 0.750829E+10 | 0.308187E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118459E+09 | 0.102969E+11 |
August | 0.810895E+10 | 0.320313E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14828770.51 | 0.132934E+11 |
September | 0.750829E+10 | 0.328538E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3652556.90 | 0.144089E+11 |
October | 0.750829E+10 | 0.370937E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87835478.89 | 0.179698E+11 |
November | 0.720796E+10 | 0.365662E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30016436.84 | 0.153203E+11 |
December | 0.750829E+10 | 0.400003E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3232935.15 | 0.172889E+11 |
Annual Sum or Average | 0.910005E+11 | 0.411808E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201438E+10 | 0.187136E+12 |
Minimum of Months | 0.690763E+10 | 0.306453E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3232935.15 | 0.102969E+11 |
Maximum of Months | 0.810895E+10 | 0.400003E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533762E+09 | 0.186763E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1355.05 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7814.93 | 17-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 1355.05 | 01-FEB-16:00 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6925.68 | 06-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1355.05 | 07-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6022.11 | 14-MAR-07:00 |
April | 1680.92 | 01-APR-07:10 | 1224.06 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 514.80 | 13-APR-17:00 | 4271.70 | 06-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1355.05 | 22-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1660.69 | 19-MAY-17:00 | 4437.55 | 05-MAY-07:00 |
June | 1680.92 | 01-JUN-07:10 | 1355.05 | 01-JUN-15:50 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2993.89 | 28-JUN-16:10 | 3391.00 | 09-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1355.05 | 07-JUL-15:30 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2890.88 | 21-JUL-17:00 | 1257.46 | 28-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 1224.06 | 01-AUG-10:30 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2393.45 | 01-AUG-16:10 | 2212.31 | 31-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 1355.05 | 08-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1550.32 | 20-SEP-17:00 | 2832.78 | 27-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 1355.05 | 04-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 856.18 | 06-OCT-16:10 | 6044.09 | 24-OCT-17:00 |
November | 1680.92 | 01-NOV-07:10 | 1355.05 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5571.73 | 27-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1355.05 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6939.86 | 22-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1224.06 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1257.46 | |||||
Maximum of Months | 1680.92 | 1355.05 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2993.89 | 7814.93 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3848.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 14715.79 | 16-JAN-18:00 |
February | 3955.50 | 01-FEB-08:09 | 3848.58 | 02-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.48 | 14-FEB-16:10 | 11588.72 | 05-FEB-01:00 |
March | 3955.50 | 01-MAR-08:09 | 3848.58 | 01-MAR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.24 | 08-MAR-17:00 | 11824.76 | 14-MAR-07:00 |
April | 3955.50 | 01-APR-07:10 | 3848.58 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.77 | 01-APR-17:00 | 11999.32 | 15-APR-15:05 |
May | 3955.50 | 01-MAY-07:10 | 3527.86 | 02-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2115.40 | 19-MAY-15:10 | 9352.52 | 05-MAY-08:00 |
June | 3955.50 | 01-JUN-07:10 | 3848.58 | 03-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5374.70 | 17-JUN-16:00 | 5994.96 | 09-JUN-06:10 |
July | 3955.50 | 01-JUL-07:10 | 3848.58 | 03-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4840.69 | 04-JUL-14:58 | 3941.94 | 15-JUL-19:00 |
August | 3955.50 | 01-AUG-07:10 | 3848.58 | 02-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3094.15 | 02-AUG-17:00 | 4328.97 | 25-AUG-20:00 |
September | 3955.50 | 01-SEP-07:10 | 3848.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1481.60 | 03-SEP-14:47 | 5134.58 | 07-SEP-15:10 |
October | 3955.50 | 02-OCT-07:10 | 3848.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 725.14 | 31-OCT-15:10 | 12910.13 | 24-OCT-15:05 |
November | 3955.50 | 01-NOV-07:10 | 3848.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10981.19 | 26-NOV-05:55 |
December | 3955.50 | 01-DEC-08:09 | 3848.58 | 01-DEC-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 15529.35 | 14-DEC-03:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3527.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3941.94 | ||||
Maximum of Months | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5374.70 | 15529.35 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 4490.00 | 02-JAN-15:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4847.94 | 24-JAN-15:00 | 40847.15 | 17-JAN-08:70 |
February | 9097.65 | 01-FEB-08:09 | 4115.84 | 04-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8358.38 | 14-FEB-17:00 | 32394.75 | 05-FEB-01:22 |
March | 9097.65 | 01-MAR-08:09 | 3961.65 | 04-MAR-16:40 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10076.19 | 08-MAR-17:00 | 33851.73 | 21-MAR-10:55 |
April | 9097.65 | 01-APR-07:10 | 3301.38 | 01-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8813.52 | 01-APR-17:00 | 52333.37 | 15-APR-12:10 |
May | 9097.65 | 01-MAY-07:10 | 3301.38 | 22-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5295.96 | 22-MAY-13:00 | 38768.12 | 05-MAY-08:00 |
June | 9097.65 | 01-JUN-07:10 | 3741.67 | 08-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3713.32 | 06-JUN-16:00 | 23615.44 | 01-JUN-07:10 |
July | 9097.65 | 01-JUL-07:10 | 3301.38 | 03-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2109.25 | 21-JUL-13:55 | 21131.80 | 15-JUL-19:00 |
August | 9097.65 | 01-AUG-07:10 | 3301.38 | 02-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 638.47 | 01-AUG-16:00 | 23143.52 | 22-AUG-21:00 |
September | 9097.65 | 01-SEP-07:10 | 3961.65 | 08-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 593.59 | 20-SEP-17:00 | 25011.41 | 07-SEP-15:00 |
October | 9097.65 | 02-OCT-07:10 | 3961.65 | 04-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8043.43 | 31-OCT-16:00 | 51310.87 | 24-OCT-15:00 |
November | 9097.65 | 01-NOV-07:10 | 4490.00 | 06-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5027.66 | 09-NOV-14:00 | 28600.81 | 03-NOV-24:00 |
December | 9097.65 | 01-DEC-08:09 | 4490.00 | 02-DEC-15:39 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1402.14 | 24-DEC-15:00 | 42073.81 | 14-DEC-03:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 3301.38 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 593.59 | 21131.80 | |||||
Maximum of Months | 9097.65 | 4490.00 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 10076.19 | 52333.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 619.83 | 21-JAN-16:00 | 1680.92 | 916.92 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.33 |
February | 437.97 | 25-FEB-14:30 | 1680.92 | 1002.74 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.45 |
March | 538.61 | 28-MAR-16:00 | 1680.92 | 1355.05 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 629.93 |
April | 4100.76 | 29-APR-16:00 | 1680.92 | 826.58 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 228.40 | 0.00 |
May | 15513.95 | 19-MAY-05:03 | 554.70 | 152.99 | 1651.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.05 |
June | 28405.58 | 19-JUN-05:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 699.58 |
July | 23308.43 | 21-JUL-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.08 |
August | 23073.68 | 19-AUG-05:01 | 1479.21 | 407.96 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.11 |
September | 24064.52 | 13-SEP-05:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.79 |
October | 23786.64 | 06-OCT-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.11 |
November | 1346.99 | 02-NOV-15:00 | 1680.92 | 1002.74 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.59 |
December | 750.89 | 06-DEC-14:00 | 1680.92 | 1047.90 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 437.97 | 554.70 | 152.99 | 1651.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28405.58 | 1680.92 | 1355.05 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 228.40 | 699.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5633.78 | 20-JAN-11:25 | 7911.00 | 5772.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.65 |
February | 4439.17 | 04-FEB-11:30 | 3955.50 | 3527.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1397.97 |
March | 4080.56 | 24-MAR-07:10 | 3955.50 | 3395.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1779.05 |
April | 4435.02 | 06-APR-08:70 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.08 |
May | 34065.96 | 28-MAY-13:45 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.24 |
June | 47083.88 | 25-JUN-11:53 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1245.75 | 0.00 |
July | 48124.81 | 13-JUL-17:06 | 0.00 | 2075.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1846.68 | 0.00 |
August | 47699.37 | 06-AUG-12:13 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.44 | 0.00 |
September | 47000.28 | 03-SEP-12:03 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.85 | 0.00 |
October | 35636.69 | 01-OCT-10:45 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.20 |
November | 5114.82 | 04-NOV-08:30 | 3955.50 | 3527.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1399.74 |
December | 5151.86 | 22-DEC-12:00 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 709.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4080.56 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48124.81 | 7911.00 | 5772.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1846.68 | 1779.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 1056.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7915.23 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 1584.69 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13769.45 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 1056.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2413.28 |
April | 0.00 | 01-APR-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3621.05 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8259.42 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8432.32 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6695.08 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5804.04 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6367.81 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 528.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5788.10 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1903.89 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2759.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 528.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1903.89 | |
Maximum of Months | 0.00 | 0.00 | 1584.69 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13769.45 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.317504E+11 | 23108.74 | 03-JAN-14:00 | 0.705377E+11 | 137230.45 | 16-JAN-17:49 |
February | 0.280110E+11 | 23199.63 | 04-FEB-08:09 | 0.457723E+11 | 132275.80 | 06-FEB-02:49 |
March | 0.303491E+11 | 22541.87 | 24-MAR-08:20 | 0.108946E+11 | 83994.97 | 04-MAR-06:19 |
April | 0.271989E+11 | 21597.05 | 01-APR-08:09 | 0.886437E+09 | 22062.42 | 01-APR-05:10 |
May | 0.282705E+11 | 27364.72 | 19-MAY-15:09 | 92848678.10 | 7470.20 | 05-MAY-05:10 |
June | 0.336899E+11 | 35723.96 | 28-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.367296E+11 | 35215.72 | 21-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.365631E+11 | 32223.95 | 21-AUG-14:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.309897E+11 | 30287.72 | 02-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.301115E+11 | 26866.23 | 06-OCT-15:09 | 0.513313E+09 | 16277.54 | 26-OCT-06:10 |
November | 0.293571E+11 | 27694.92 | 14-NOV-16:00 | 0.936448E+10 | 63180.75 | 26-NOV-06:40 |
December | 0.321168E+11 | 27932.14 | 08-DEC-16:49 | 0.680912E+11 | 130969.28 | 14-DEC-03:39 |
Annual Sum or Average | 0.375138E+12 | 0.206153E+12 | ||||
Minimum of Months | 0.271989E+11 | 21597.05 | 0.00 | 0.00 | ||
Maximum of Months | 0.367296E+11 | 35723.96 | 0.705377E+11 | 137230.45 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.881832E+10 | 0.651218E+10 | 0.112984E+11 | 0.00 | 0.289362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222793E+10 | 0.00 |
February | 0.777970E+10 | 0.543671E+10 | 0.103734E+11 | 0.00 | 0.239007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203112E+10 | 0.00 |
March | 0.841729E+10 | 0.537600E+10 | 0.121089E+11 | 0.00 | 0.217446E+10 | 0.00 | 0.00 | 58.11 | 0.00 | 0.00 | 0.00 | 0.227246E+10 | 0.00 |
April | 0.732706E+10 | 0.454382E+10 | 0.112578E+11 | 0.00 | 0.180560E+10 | 0.00 | 0.00 | 0.148845E+09 | 0.00 | 0.00 | 0.00 | 0.211583E+10 | 0.00 |
May | 0.752106E+10 | 0.414058E+10 | 0.117000E+11 | 0.00 | 0.188258E+10 | 0.00 | 0.00 | 0.897252E+09 | 0.00 | 0.00 | 0.00 | 0.212906E+10 | 0.00 |
June | 0.761628E+10 | 0.376274E+10 | 0.116594E+11 | 0.00 | 0.363398E+10 | 0.00 | 0.00 | 0.499278E+10 | 0.00 | 0.00 | 0.00 | 0.202479E+10 | 0.00 |
July | 0.731592E+10 | 0.399028E+10 | 0.112984E+11 | 0.00 | 0.450393E+10 | 0.00 | 0.00 | 0.761197E+10 | 0.00 | 0.00 | 0.00 | 0.200909E+10 | 0.00 |
August | 0.766764E+10 | 0.444187E+10 | 0.121016E+11 | 0.00 | 0.388897E+10 | 0.00 | 0.00 | 0.641375E+10 | 0.00 | 0.00 | 0.00 | 0.204935E+10 | 0.00 |
September | 0.772142E+10 | 0.492475E+10 | 0.112504E+11 | 0.00 | 0.219179E+10 | 0.00 | 0.00 | 0.292067E+10 | 0.00 | 0.00 | 0.00 | 0.198066E+10 | 0.00 |
October | 0.848644E+10 | 0.575693E+10 | 0.113057E+11 | 0.00 | 0.181278E+10 | 0.00 | 0.00 | 0.673715E+09 | 0.00 | 0.00 | 0.00 | 0.207585E+10 | 0.00 |
November | 0.835554E+10 | 0.614706E+10 | 0.108562E+11 | 0.00 | 0.193377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206457E+10 | 0.00 |
December | 0.909307E+10 | 0.667118E+10 | 0.112984E+11 | 0.00 | 0.286138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219282E+10 | 0.00 |
Annual Sum or Average | 0.961197E+11 | 0.617041E+11 | 0.136508E+12 | 0.00 | 0.319729E+11 | 0.00 | 0.00 | 0.236590E+11 | 0.00 | 0.00 | 0.00 | 0.251735E+11 | 0.00 |
Minimum of Months | 0.731592E+10 | 0.376274E+10 | 0.103734E+11 | 0.00 | 0.180560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198066E+10 | 0.00 |
Maximum of Months | 0.909307E+10 | 0.667118E+10 | 0.121089E+11 | 0.00 | 0.450393E+10 | 0.00 | 0.00 | 0.761197E+10 | 0.00 | 0.00 | 0.00 | 0.227246E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.705377E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.457723E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.108946E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.886437E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 92848678.10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.513313E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.936448E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.680912E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.206153E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.705377E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 9517.47 | 03-JAN-14:00 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 3142.33 | 17-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 9319.46 | 16-FEB-15:39 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 3071.04 | 06-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8945.30 | 08-MAR-09:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2635.96 | 04-MAR-07:19 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 8065.97 | 01-APR-08:09 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2038.22 | 06-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 8052.13 | 22-MAY-07:10 | 5520.82 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 4105.51 | 19-MAY-16:19 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 8945.30 | 08-JUN-08:09 | 4975.14 | 01-JUN-19:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 5053.40 | 28-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 8065.97 | 03-JUL-08:09 | 5520.82 | 19-JUL-05:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 4975.21 | 22-JUL-15:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 8065.97 | 02-AUG-08:09 | 5520.82 | 01-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4255.97 | 01-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 8945.30 | 26-SEP-08:09 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 4105.51 | 01-SEP-14:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 8945.30 | 10-OCT-08:09 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 2952.86 | 05-OCT-15:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 9255.50 | 06-NOV-15:00 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2653.72 | 27-NOV-07:19 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 9693.63 | 21-DEC-15:39 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2962.08 | 22-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 8052.13 | 4975.14 | 10035.17 | 0.00 | 2038.22 | 0.00 | 0.00 | |||||
Maximum of Months | 9693.63 | 5520.82 | 10035.17 | 0.00 | 5053.40 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2357.99 | 31-JAN-12:39 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2361.98 | 07-FEB-12:20 | 0.00 |
March | 0.05 | 08-MAR-16:19 | 0.00 | 0.00 | 0.00 | 2320.62 | 01-MAR-12:00 | 0.00 |
April | 1184.19 | 29-APR-15:00 | 0.00 | 0.00 | 0.00 | 2102.61 | 05-APR-11:00 | 0.00 |
May | 6067.66 | 21-MAY-12:20 | 0.00 | 0.00 | 0.00 | 1821.77 | 02-MAY-11:00 | 0.00 |
June | 13243.84 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1780.52 | 01-JUN-11:30 | 0.00 |
July | 13204.06 | 22-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1760.84 | 01-JUL-11:50 | 0.00 |
August | 9925.16 | 01-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1754.43 | 31-AUG-11:09 | 0.00 |
September | 7538.28 | 02-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1769.58 | 30-SEP-11:00 | 0.00 |
October | 6144.39 | 01-OCT-12:20 | 0.00 | 0.00 | 0.00 | 1793.64 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 1971.82 | 27-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2232.18 | 28-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1754.43 | 0.00 | ||
Maximum of Months | 13243.84 | 0.00 | 0.00 | 0.00 | 2361.98 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 23108.74 | 03-JAN-14:00 | 9517.47 | 10035.17 | 0.00 | 0.00 | 1800.21 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23199.63 | 04-FEB-08:09 | 8712.41 | 10035.17 | 0.00 | 0.00 | 2802.95 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22541.87 | 24-MAR-08:20 | 8945.30 | 10035.17 | 0.00 | 0.00 | 1882.70 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21597.05 | 01-APR-08:09 | 8065.97 | 10035.17 | 0.00 | 0.00 | 1819.42 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27364.72 | 19-MAY-15:09 | 5967.30 | 10035.17 | 0.00 | 0.00 | 4105.51 | 0.00 | 0.00 | 5656.88 | 0.00 |
June | 35723.96 | 28-JUN-15:00 | 6910.55 | 10035.17 | 0.00 | 0.00 | 5053.40 | 0.00 | 0.00 | 13243.84 | 0.00 |
July | 35215.72 | 21-JUL-13:00 | 6874.22 | 10035.17 | 0.00 | 0.00 | 4656.77 | 0.00 | 0.00 | 11956.56 | 0.00 |
August | 32223.95 | 21-AUG-14:39 | 6698.06 | 10035.17 | 0.00 | 0.00 | 4225.77 | 0.00 | 0.00 | 9543.54 | 0.00 |
September | 30287.72 | 02-SEP-15:00 | 7193.53 | 10035.17 | 0.00 | 0.00 | 4105.51 | 0.00 | 0.00 | 7362.46 | 0.00 |
October | 26866.23 | 06-OCT-15:09 | 7238.70 | 10035.17 | 0.00 | 0.00 | 2952.86 | 0.00 | 0.00 | 5043.82 | 0.00 |
November | 27694.92 | 14-NOV-16:00 | 8712.41 | 10035.17 | 5520.82 | 0.00 | 1822.70 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27932.14 | 08-DEC-16:49 | 8712.41 | 10035.17 | 5520.82 | 0.00 | 2055.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 21597.05 | 5967.30 | 10035.17 | 0.00 | 0.00 | 1800.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35723.96 | 9517.47 | 10035.17 | 5520.82 | 0.00 | 5053.40 | 0.00 | 0.00 | 13243.84 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 137230.45 | 16-JAN-17:49 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 132275.80 | 06-FEB-02:49 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 83994.97 | 04-MAR-06:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 22062.42 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 7470.20 | 05-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 16277.54 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 63180.75 | 26-NOV-06:40 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 130969.28 | 14-DEC-03:39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 137230.45 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.67 | 18.13 | 9.33 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
February | 10.00 | 18.49 | 7.67 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
March | 8.67 | 19.86 | 8.67 | 19.86 | 0.00 | 19.86 | 0.00 | 19.86 |
April | 2.17 | 20.21 | 2.17 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
May | 0.17 | 20.52 | 0.17 | 20.52 | 0.33 | 22.52 | 0.33 | 23.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.10 | 1.67 | 24.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.65 | 3.83 | 24.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.66 | 3.00 | 24.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.51 | 1.33 | 24.51 |
October | 1.00 | 20.26 | 1.00 | 20.26 | 0.33 | 20.88 | 0.33 | 21.34 |
November | 6.50 | 19.78 | 6.17 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 |
December | 9.67 | 19.17 | 8.83 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Annual Sum or Average | 50.83 | 19.04 | 44.00 | 19.33 | 10.67 | 19.88 | 10.50 | 20.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.60 | 0.00 | 18.60 |
Maximum of Months | 12.67 | 20.52 | 9.33 | 20.52 | 3.83 | 25.10 | 3.83 | 24.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 81.50 | 14.70 | 6.17 | 14.69 | 0.00 | 14.69 | 0.00 | 14.69 |
February | 56.83 | 14.70 | 4.00 | 14.69 | 0.00 | 14.69 | 0.00 | 14.69 |
March | 16.00 | 14.85 | 1.67 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 |
April | 0.67 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.00 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.50 | 0.00 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.57 | 0.00 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.50 | 0.00 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.45 | 0.00 | 27.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.27 | 0.00 | 27.27 |
November | 15.33 | 14.83 | 1.50 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
December | 81.17 | 14.74 | 6.00 | 14.74 | 0.00 | 14.74 | 0.00 | 14.74 |
Annual Sum or Average | 251.50 | 14.73 | 19.33 | 14.73 | 50.50 | 16.74 | 0.00 | 16.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.69 | 0.00 | 14.69 |
Maximum of Months | 81.50 | 14.98 | 6.17 | 14.98 | 21.00 | 27.57 | 0.00 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.07 | 298.33 | 21.07 | 298.33 | 21.07 |
February | 276.00 | 21.20 | 259.50 | 21.15 | 259.50 | 21.13 |
March | 324.00 | 21.45 | 261.50 | 21.31 | 261.50 | 21.26 |
April | 300.00 | 22.71 | 98.33 | 22.34 | 98.33 | 22.11 |
May | 207.17 | 23.37 | 24.17 | 23.27 | 13.67 | 23.16 |
June | 30.33 | 23.51 | 192.50 | 23.85 | 0.00 | 23.85 |
July | 11.00 | 23.90 | 297.33 | 23.90 | 11.00 | 23.90 |
August | 10.50 | 23.91 | 318.67 | 23.90 | 10.50 | 23.90 |
September | 15.67 | 23.60 | 223.67 | 23.88 | 2.33 | 23.88 |
October | 210.33 | 22.84 | 112.50 | 22.81 | 46.67 | 22.60 |
November | 288.00 | 21.47 | 225.00 | 21.34 | 225.00 | 21.28 |
December | 300.00 | 21.07 | 298.50 | 21.07 | 298.50 | 21.07 |
Annual Sum or Average | 2273.00 | 21.86 | 2610.00 | 22.09 | 1525.33 | 21.87 |
Minimum of Months | 10.50 | 21.07 | 24.17 | 21.07 | 0.00 | 21.07 |
Maximum of Months | 324.00 | 23.91 | 318.67 | 23.90 | 298.50 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 16.23 | 300.00 | 16.23 | 300.00 | 16.23 |
February | 276.00 | 16.57 | 276.00 | 16.57 | 276.00 | 16.57 |
March | 324.00 | 17.66 | 324.00 | 17.66 | 324.00 | 17.66 |
April | 268.83 | 20.66 | 158.33 | 20.22 | 146.83 | 19.89 |
May | 135.00 | 22.07 | 173.00 | 23.79 | 29.83 | 23.44 |
June | 125.17 | 26.20 | 281.67 | 26.36 | 108.33 | 26.43 |
July | 255.83 | 26.69 | 300.00 | 26.67 | 255.83 | 26.68 |
August | 257.83 | 26.67 | 324.00 | 26.62 | 257.83 | 26.64 |
September | 124.83 | 26.45 | 271.67 | 26.40 | 115.50 | 26.46 |
October | 199.50 | 21.06 | 182.83 | 21.67 | 108.00 | 21.22 |
November | 288.00 | 17.55 | 278.67 | 17.49 | 278.67 | 17.47 |
December | 300.00 | 16.02 | 300.00 | 16.02 | 300.00 | 16.02 |
Annual Sum or Average | 2855.00 | 20.33 | 3170.17 | 20.85 | 2500.83 | 20.60 |
Minimum of Months | 124.83 | 16.02 | 158.33 | 16.02 | 29.83 | 16.02 |
Maximum of Months | 324.00 | 26.69 | 324.00 | 26.67 | 324.00 | 26.68 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 11.75 | 300.00 | 11.75 | 300.00 | 11.75 |
February | 276.00 | 12.51 | 276.00 | 12.51 | 276.00 | 12.51 |
March | 324.00 | 15.03 | 324.00 | 15.03 | 324.00 | 15.03 |
April | 285.33 | 19.91 | 178.17 | 19.30 | 175.50 | 19.00 |
May | 191.00 | 23.37 | 190.33 | 24.20 | 99.50 | 24.13 |
June | 231.83 | 30.24 | 289.00 | 29.87 | 217.67 | 30.12 |
July | 300.00 | 30.75 | 300.00 | 30.75 | 300.00 | 30.75 |
August | 316.67 | 29.86 | 324.00 | 29.82 | 316.67 | 29.84 |
September | 210.00 | 28.78 | 284.33 | 28.34 | 208.00 | 28.49 |
October | 251.83 | 21.71 | 200.33 | 21.87 | 157.00 | 21.63 |
November | 288.00 | 14.87 | 288.00 | 14.87 | 288.00 | 14.87 |
December | 300.00 | 11.61 | 300.00 | 11.61 | 300.00 | 11.61 |
Annual Sum or Average | 3274.67 | 20.45 | 3254.17 | 20.59 | 2962.33 | 20.47 |
Minimum of Months | 191.00 | 11.61 | 178.17 | 11.61 | 99.50 | 11.61 |
Maximum of Months | 324.00 | 30.75 | 324.00 | 30.75 | 324.00 | 30.75 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 226.17 | 58.11 | 0.67 | 226.17 | 0.00 | 0.00 | 0.00 | 08-MAR-16:20 | 0.00 | 01-MAR-00:05 | 0.19 | 08-MAR-16:20 | 0.19 | 08-MAR-16:20 | 0.00 | 08-MAR-16:20 | 0.05 | 08-MAR-16:20 | 0.00 | 01-MAR-00:05 |
April | 0.604627E+09 | 0.148845E+09 | 73.50 | 0.604627E+09 | 0.00 | 0.00 | 0.54 | 29-APR-16:00 | 0.00 | 01-APR-00:10 | 4845.91 | 29-APR-16:00 | 4845.91 | 29-APR-16:00 | 0.00 | 29-APR-15:40 | 1184.19 | 29-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.223836E+10 | 0.548153E+09 | 166.26 | 0.221283E+10 | 25533246.50 | 0.00 | 1.00 | 19-MAY-05:03 | 0.00 | 01-MAY-00:10 | 19891.85 | 22-MAY-05:03 | 19369.23 | 19-MAY-05:03 | 4348.25 | 22-MAY-05:03 | 4340.95 | 22-MAY-05:03 | 0.00 | 01-MAY-00:10 |
June | 0.626496E+10 | 0.160890E+10 | 264.46 | 0.608574E+10 | 0.179226E+09 | 0.00 | 1.00 | 07-JUN-05:03 | 0.00 | 01-JUN-00:10 | 21645.74 | 29-JUN-05:01 | 19682.53 | 13-JUN-05:21 | 5602.93 | 24-JUN-05:25 | 4752.93 | 29-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.895704E+10 | 0.223058E+10 | 289.72 | 0.782477E+10 | 0.113227E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 22482.61 | 01-JUL-05:01 | 19969.37 | 22-JUL-05:01 | 9931.02 | 01-JUL-05:45 | 4873.59 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.862652E+10 | 0.209399E+10 | 303.94 | 0.744511E+10 | 0.118141E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 22785.59 | 14-AUG-05:01 | 18706.25 | 19-AUG-05:01 | 10734.18 | 26-AUG-05:03 | 4928.74 | 14-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.538987E+10 | 0.129233E+10 | 250.57 | 0.486628E+10 | 0.523596E+09 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 21722.29 | 05-SEP-05:01 | 18212.78 | 26-SEP-05:03 | 9512.71 | 06-SEP-05:02 | 4728.81 | 05-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.169145E+10 | 0.403628E+09 | 110.73 | 0.157936E+10 | 0.112094E+09 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 20245.19 | 02-OCT-05:01 | 17982.21 | 07-OCT-05:02 | 4842.31 | 02-OCT-05:45 | 4420.37 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.337728E+11 | 0.832642E+10 | 1459.84 | 0.306187E+11 | 0.315412E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.895704E+10 | 0.223058E+10 | 303.94 | 0.782477E+10 | 0.118141E+10 | 0.00 | 1.00 | 0.00 | 22785.59 | 19969.37 | 10734.18 | 4928.74 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.131917E+10 | 0.349099E+09 | 65.49 | 0.131892E+10 | 247203.87 | 0.00 | 1.00 | 19-MAY-17:10 | 0.00 | 01-MAY-00:10 | 53242.80 | 28-MAY-13:45 | 53242.80 | 28-MAY-13:45 | 89.08 | 22-MAY-12:10 | 12135.32 | 21-MAY-12:15 | 0.00 | 01-MAY-00:10 |
June | 0.123560E+11 | 0.338388E+10 | 241.07 | 0.122588E+11 | 97134159.75 | 0.00 | 1.00 | 04-JUN-14:35 | 0.00 | 01-JUN-00:10 | 55341.21 | 25-JUN-08:61 | 53792.46 | 28-JUN-23:55 | 6011.52 | 25-JUN-08:09 | 13949.72 | 27-JUN-17:06 | 0.00 | 01-JUN-00:10 |
July | 0.204361E+11 | 0.538139E+10 | 338.38 | 0.190006E+11 | 0.143552E+10 | 0.00 | 1.00 | 01-JUL-17:22 | 0.00 | 01-JUL-00:10 | 61300.93 | 01-JUL-17:22 | 53812.78 | 23-JUL-20:15 | 26291.22 | 01-JUL-17:22 | 14327.63 | 23-JUL-14:13 | 0.00 | 01-JUL-00:10 |
August | 0.167666E+11 | 0.431976E+10 | 300.80 | 0.155780E+11 | 0.118865E+10 | 0.00 | 1.00 | 01-AUG-17:06 | 0.00 | 01-AUG-00:10 | 60100.12 | 13-AUG-08:25 | 53820.62 | 07-AUG-19:45 | 24687.17 | 13-AUG-08:25 | 13981.17 | 20-AUG-15:43 | 0.00 | 01-AUG-00:10 |
September | 0.633368E+10 | 0.162834E+10 | 172.17 | 0.607730E+10 | 0.256379E+09 | 0.00 | 1.00 | 01-SEP-17:10 | 0.00 | 01-SEP-00:10 | 57272.60 | 04-SEP-10:35 | 53734.80 | 10-SEP-13:15 | 11246.54 | 10-SEP-11:45 | 13231.19 | 03-SEP-12:03 | 0.00 | 01-SEP-00:10 |
October | 0.105180E+10 | 0.270087E+09 | 44.76 | 0.103579E+10 | 16008964.82 | 0.00 | 1.00 | 01-OCT-10:45 | 0.00 | 01-OCT-00:10 | 53147.01 | 01-OCT-11:41 | 53147.01 | 01-OCT-11:41 | 652.92 | 03-OCT-13:00 | 12288.79 | 01-OCT-12:15 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.582633E+11 | 0.153326E+11 | 1162.66 | 0.552694E+11 | 0.299393E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.204361E+11 | 0.538139E+10 | 338.38 | 0.190006E+11 | 0.143552E+10 | 0.00 | 1.00 | 0.00 | 61300.93 | 53820.62 | 26291.22 | 14327.63 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.00 | 62.68 | 47.32 | 116.55 | 115.65 | 0.00 | 0.00 | 0.00 |
February | 141.23 | 81.42 | 59.81 | 159.45 | 101.49 | 0.00 | 0.00 | 0.00 |
March | 158.38 | 84.33 | 74.06 | 190.21 | 75.79 | 0.00 | 0.00 | 0.00 |
April | 201.78 | 107.24 | 94.54 | 252.06 | 55.56 | 0.00 | 0.00 | 0.00 |
May | 192.31 | 99.37 | 92.95 | 246.43 | 49.71 | 0.00 | 0.00 | 0.00 |
June | 205.01 | 114.24 | 90.76 | 289.03 | 40.14 | 0.00 | 0.00 | 0.00 |
July | 185.24 | 90.66 | 94.58 | 270.86 | 29.99 | 0.00 | 0.00 | 0.00 |
August | 189.07 | 87.29 | 101.77 | 267.58 | 34.12 | 0.00 | 0.00 | 0.00 |
September | 171.55 | 90.55 | 81.00 | 229.87 | 53.30 | 0.00 | 0.00 | 0.00 |
October | 156.28 | 97.07 | 59.20 | 190.99 | 78.64 | 0.00 | 0.00 | 0.00 |
November | 122.59 | 72.03 | 50.56 | 135.77 | 89.65 | 0.00 | 0.00 | 0.00 |
December | 106.04 | 66.44 | 39.60 | 108.45 | 119.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.64 | 87.74 | 73.90 | 204.90 | 70.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.04 | 62.68 | 39.60 | 108.45 | 29.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.01 | 114.24 | 101.77 | 289.03 | 119.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.00 | 62.68 | 47.32 | 116.55 | 115.65 | 0.00 | 0.00 | 0.00 |
February | 141.23 | 81.42 | 59.81 | 159.45 | 101.49 | 0.00 | 0.00 | 0.00 |
March | 158.38 | 84.33 | 74.06 | 190.21 | 75.79 | 0.00 | 0.00 | 0.00 |
April | 201.78 | 107.24 | 94.54 | 252.06 | 55.56 | 0.00 | 0.00 | 0.00 |
May | 192.31 | 99.37 | 92.95 | 246.43 | 49.71 | 0.00 | 0.00 | 0.00 |
June | 205.01 | 114.24 | 90.76 | 289.03 | 40.14 | 0.00 | 0.00 | 0.00 |
July | 185.24 | 90.66 | 94.58 | 270.86 | 29.99 | 0.00 | 0.00 | 0.00 |
August | 189.07 | 87.29 | 101.77 | 267.58 | 34.12 | 0.00 | 0.00 | 0.00 |
September | 171.55 | 90.55 | 81.00 | 229.87 | 53.30 | 0.00 | 0.00 | 0.00 |
October | 156.28 | 97.07 | 59.20 | 190.99 | 78.64 | 0.00 | 0.00 | 0.00 |
November | 122.59 | 72.03 | 50.56 | 135.77 | 89.65 | 0.00 | 0.00 | 0.00 |
December | 106.04 | 66.44 | 39.60 | 108.45 | 119.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.64 | 87.74 | 73.90 | 204.90 | 70.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.04 | 62.68 | 39.60 | 108.45 | 29.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.01 | 114.24 | 101.77 | 289.03 | 119.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.49 | 0.00 | 22.49 | 8.32 | 69.84 | 0.00 | 0.00 | 0.00 |
February | 28.11 | 0.00 | 28.11 | 15.31 | 60.93 | 0.00 | 0.00 | 0.00 |
March | 35.47 | 0.00 | 35.46 | 29.71 | 44.92 | 0.00 | 0.00 | 0.00 |
April | 45.08 | 0.47 | 44.61 | 42.78 | 31.85 | 0.00 | 0.00 | 0.00 |
May | 49.01 | 3.24 | 45.77 | 53.05 | 27.68 | 0.00 | 0.00 | 0.00 |
June | 55.59 | 9.13 | 46.46 | 77.68 | 21.62 | 0.00 | 0.00 | 0.00 |
July | 50.89 | 4.13 | 46.76 | 75.69 | 16.67 | 0.00 | 0.00 | 0.00 |
August | 47.49 | 1.24 | 46.25 | 64.13 | 19.00 | 0.00 | 0.00 | 0.00 |
September | 37.86 | 0.02 | 37.84 | 43.19 | 31.15 | 0.00 | 0.00 | 0.00 |
October | 28.23 | 0.00 | 28.23 | 20.78 | 46.79 | 0.00 | 0.00 | 0.00 |
November | 23.97 | 0.00 | 23.97 | 10.97 | 54.36 | 0.00 | 0.00 | 0.00 |
December | 19.14 | 0.00 | 19.14 | 3.31 | 73.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.98 | 1.52 | 35.45 | 37.18 | 41.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.14 | 0.00 | 19.14 | 3.31 | 16.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.59 | 9.13 | 46.76 | 77.68 | 73.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.49 | 0.00 | 22.49 | 8.32 | 69.84 | 0.00 | 0.00 | 0.00 |
February | 28.11 | 0.00 | 28.11 | 15.31 | 60.93 | 0.00 | 0.00 | 0.00 |
March | 35.46 | 0.00 | 35.46 | 29.71 | 44.92 | 0.00 | 0.00 | 0.00 |
April | 45.08 | 0.47 | 44.61 | 42.78 | 31.85 | 0.00 | 0.00 | 0.00 |
May | 49.01 | 3.24 | 45.77 | 53.05 | 27.68 | 0.00 | 0.00 | 0.00 |
June | 55.59 | 9.13 | 46.46 | 77.68 | 21.62 | 0.00 | 0.00 | 0.00 |
July | 50.89 | 4.13 | 46.76 | 75.69 | 16.67 | 0.00 | 0.00 | 0.00 |
August | 47.49 | 1.24 | 46.25 | 64.13 | 19.00 | 0.00 | 0.00 | 0.00 |
September | 37.86 | 0.02 | 37.84 | 43.19 | 31.15 | 0.00 | 0.00 | 0.00 |
October | 28.23 | 0.00 | 28.23 | 20.78 | 46.79 | 0.00 | 0.00 | 0.00 |
November | 23.97 | 0.00 | 23.97 | 10.97 | 54.36 | 0.00 | 0.00 | 0.00 |
December | 19.14 | 0.00 | 19.14 | 3.31 | 73.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.98 | 1.52 | 35.45 | 37.18 | 41.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.14 | 0.00 | 19.14 | 3.31 | 16.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.59 | 9.13 | 46.76 | 77.68 | 73.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.56 | 30.65 | 14.91 | 48.24 | 45.33 | 0.00 | 0.00 | 0.00 |
February | 63.07 | 44.61 | 18.46 | 70.62 | 40.19 | 0.00 | 0.00 | 0.00 |
March | 83.36 | 57.94 | 25.42 | 98.44 | 31.41 | 0.00 | 0.00 | 0.00 |
April | 112.98 | 81.74 | 31.23 | 136.03 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 123.56 | 93.81 | 29.76 | 149.39 | 24.90 | 0.00 | 0.00 | 0.00 |
June | 131.02 | 103.86 | 27.15 | 164.38 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 127.59 | 96.66 | 30.93 | 163.81 | 16.98 | 0.00 | 0.00 | 0.00 |
August | 119.20 | 86.18 | 33.02 | 150.87 | 17.96 | 0.00 | 0.00 | 0.00 |
September | 96.43 | 70.76 | 25.66 | 118.54 | 25.93 | 0.00 | 0.00 | 0.00 |
October | 71.90 | 55.77 | 16.13 | 83.45 | 34.07 | 0.00 | 0.00 | 0.00 |
November | 49.67 | 34.56 | 15.11 | 54.57 | 36.46 | 0.00 | 0.00 | 0.00 |
December | 39.88 | 29.36 | 10.51 | 40.72 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.80 | 65.59 | 23.21 | 106.75 | 30.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.88 | 29.36 | 10.51 | 40.72 | 16.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.02 | 103.86 | 33.02 | 164.38 | 46.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.56 | 30.65 | 14.91 | 48.24 | 45.33 | 0.00 | 0.00 | 0.00 |
February | 63.07 | 44.61 | 18.46 | 70.62 | 40.19 | 0.00 | 0.00 | 0.00 |
March | 83.36 | 57.94 | 25.42 | 98.44 | 31.41 | 0.00 | 0.00 | 0.00 |
April | 112.98 | 81.74 | 31.23 | 136.03 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 123.56 | 93.81 | 29.76 | 149.39 | 24.90 | 0.00 | 0.00 | 0.00 |
June | 131.02 | 103.86 | 27.15 | 164.38 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 127.59 | 96.66 | 30.93 | 163.81 | 16.98 | 0.00 | 0.00 | 0.00 |
August | 119.20 | 86.18 | 33.02 | 150.87 | 17.96 | 0.00 | 0.00 | 0.00 |
September | 96.43 | 70.76 | 25.66 | 118.54 | 25.93 | 0.00 | 0.00 | 0.00 |
October | 71.90 | 55.77 | 16.13 | 83.45 | 34.07 | 0.00 | 0.00 | 0.00 |
November | 49.67 | 34.56 | 15.11 | 54.57 | 36.46 | 0.00 | 0.00 | 0.00 |
December | 39.88 | 29.36 | 10.51 | 40.72 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.80 | 65.59 | 23.21 | 106.75 | 30.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.88 | 29.36 | 10.51 | 40.72 | 16.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.02 | 103.86 | 33.02 | 164.38 | 46.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.56 | 30.65 | 14.91 | 48.24 | 45.33 | 0.00 | 0.00 | 0.00 |
February | 63.07 | 44.61 | 18.46 | 70.62 | 40.19 | 0.00 | 0.00 | 0.00 |
March | 83.36 | 57.94 | 25.42 | 98.44 | 31.41 | 0.00 | 0.00 | 0.00 |
April | 112.98 | 81.74 | 31.23 | 136.03 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 123.56 | 93.81 | 29.76 | 149.39 | 24.90 | 0.00 | 0.00 | 0.00 |
June | 131.02 | 103.86 | 27.15 | 164.38 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 127.59 | 96.66 | 30.93 | 163.81 | 16.98 | 0.00 | 0.00 | 0.00 |
August | 119.20 | 86.18 | 33.02 | 150.87 | 17.96 | 0.00 | 0.00 | 0.00 |
September | 96.43 | 70.76 | 25.66 | 118.54 | 25.93 | 0.00 | 0.00 | 0.00 |
October | 71.90 | 55.77 | 16.13 | 83.45 | 34.07 | 0.00 | 0.00 | 0.00 |
November | 49.67 | 34.56 | 15.11 | 54.57 | 36.46 | 0.00 | 0.00 | 0.00 |
December | 39.88 | 29.36 | 10.51 | 40.72 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.80 | 65.59 | 23.21 | 106.75 | 30.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.88 | 29.36 | 10.51 | 40.72 | 16.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.02 | 103.86 | 33.02 | 164.38 | 46.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.56 | 30.65 | 14.91 | 48.24 | 45.33 | 0.00 | 0.00 | 0.00 |
February | 63.07 | 44.61 | 18.46 | 70.62 | 40.19 | 0.00 | 0.00 | 0.00 |
March | 83.36 | 57.94 | 25.42 | 98.44 | 31.41 | 0.00 | 0.00 | 0.00 |
April | 112.98 | 81.74 | 31.23 | 136.03 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 123.56 | 93.81 | 29.76 | 149.39 | 24.90 | 0.00 | 0.00 | 0.00 |
June | 131.02 | 103.86 | 27.15 | 164.38 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 127.59 | 96.66 | 30.93 | 163.81 | 16.98 | 0.00 | 0.00 | 0.00 |
August | 119.20 | 86.18 | 33.02 | 150.87 | 17.96 | 0.00 | 0.00 | 0.00 |
September | 96.43 | 70.76 | 25.66 | 118.54 | 25.93 | 0.00 | 0.00 | 0.00 |
October | 71.90 | 55.77 | 16.13 | 83.45 | 34.07 | 0.00 | 0.00 | 0.00 |
November | 49.67 | 34.56 | 15.11 | 54.57 | 36.46 | 0.00 | 0.00 | 0.00 |
December | 39.88 | 29.36 | 10.51 | 40.72 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.80 | 65.59 | 23.21 | 106.75 | 30.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.88 | 29.36 | 10.51 | 40.72 | 16.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.02 | 103.86 | 33.02 | 164.38 | 46.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.56 | 30.65 | 14.91 | 48.24 | 45.33 | 0.00 | 0.00 | 0.00 |
February | 63.07 | 44.61 | 18.46 | 70.62 | 40.19 | 0.00 | 0.00 | 0.00 |
March | 83.36 | 57.94 | 25.42 | 98.44 | 31.41 | 0.00 | 0.00 | 0.00 |
April | 112.98 | 81.74 | 31.23 | 136.03 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 123.56 | 93.81 | 29.76 | 149.39 | 24.90 | 0.00 | 0.00 | 0.00 |
June | 131.02 | 103.86 | 27.15 | 164.38 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 127.59 | 96.66 | 30.93 | 163.81 | 16.98 | 0.00 | 0.00 | 0.00 |
August | 119.20 | 86.18 | 33.02 | 150.87 | 17.96 | 0.00 | 0.00 | 0.00 |
September | 96.43 | 70.76 | 25.66 | 118.54 | 25.93 | 0.00 | 0.00 | 0.00 |
October | 71.90 | 55.77 | 16.13 | 83.45 | 34.07 | 0.00 | 0.00 | 0.00 |
November | 49.67 | 34.56 | 15.11 | 54.57 | 36.46 | 0.00 | 0.00 | 0.00 |
December | 39.88 | 29.36 | 10.51 | 40.72 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.80 | 65.59 | 23.21 | 106.75 | 30.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.88 | 29.36 | 10.51 | 40.72 | 16.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.02 | 103.86 | 33.02 | 164.38 | 46.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.56 | 30.65 | 14.91 | 48.24 | 45.33 | 0.00 | 0.00 | 0.00 |
February | 63.07 | 44.61 | 18.46 | 70.62 | 40.19 | 0.00 | 0.00 | 0.00 |
March | 83.36 | 57.94 | 25.42 | 98.44 | 31.41 | 0.00 | 0.00 | 0.00 |
April | 112.98 | 81.74 | 31.23 | 136.03 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 123.56 | 93.81 | 29.76 | 149.39 | 24.90 | 0.00 | 0.00 | 0.00 |
June | 131.02 | 103.86 | 27.15 | 164.38 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 127.59 | 96.66 | 30.93 | 163.81 | 16.98 | 0.00 | 0.00 | 0.00 |
August | 119.20 | 86.18 | 33.02 | 150.87 | 17.96 | 0.00 | 0.00 | 0.00 |
September | 96.43 | 70.76 | 25.66 | 118.54 | 25.93 | 0.00 | 0.00 | 0.00 |
October | 71.90 | 55.77 | 16.13 | 83.45 | 34.07 | 0.00 | 0.00 | 0.00 |
November | 49.67 | 34.56 | 15.11 | 54.57 | 36.46 | 0.00 | 0.00 | 0.00 |
December | 39.88 | 29.36 | 10.51 | 40.72 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.80 | 65.59 | 23.21 | 106.75 | 30.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.88 | 29.36 | 10.51 | 40.72 | 16.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.02 | 103.86 | 33.02 | 164.38 | 46.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.56 | 30.65 | 14.91 | 48.24 | 45.33 | 0.00 | 0.00 | 0.00 |
February | 63.07 | 44.61 | 18.46 | 70.62 | 40.19 | 0.00 | 0.00 | 0.00 |
March | 83.36 | 57.94 | 25.42 | 98.44 | 31.41 | 0.00 | 0.00 | 0.00 |
April | 112.98 | 81.74 | 31.23 | 136.03 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 123.56 | 93.81 | 29.76 | 149.39 | 24.90 | 0.00 | 0.00 | 0.00 |
June | 131.02 | 103.86 | 27.15 | 164.38 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 127.59 | 96.66 | 30.93 | 163.81 | 16.98 | 0.00 | 0.00 | 0.00 |
August | 119.20 | 86.18 | 33.02 | 150.87 | 17.96 | 0.00 | 0.00 | 0.00 |
September | 96.43 | 70.76 | 25.66 | 118.54 | 25.93 | 0.00 | 0.00 | 0.00 |
October | 71.90 | 55.77 | 16.13 | 83.45 | 34.07 | 0.00 | 0.00 | 0.00 |
November | 49.67 | 34.56 | 15.11 | 54.57 | 36.46 | 0.00 | 0.00 | 0.00 |
December | 39.88 | 29.36 | 10.51 | 40.72 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.80 | 65.59 | 23.21 | 106.75 | 30.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.88 | 29.36 | 10.51 | 40.72 | 16.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.02 | 103.86 | 33.02 | 164.38 | 46.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.56 | 30.65 | 14.91 | 48.24 | 45.33 | 0.00 | 0.00 | 0.00 |
February | 63.07 | 44.61 | 18.46 | 70.62 | 40.19 | 0.00 | 0.00 | 0.00 |
March | 83.36 | 57.94 | 25.42 | 98.44 | 31.41 | 0.00 | 0.00 | 0.00 |
April | 112.98 | 81.74 | 31.23 | 136.03 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 123.56 | 93.81 | 29.76 | 149.39 | 24.90 | 0.00 | 0.00 | 0.00 |
June | 131.02 | 103.86 | 27.15 | 164.38 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 127.59 | 96.66 | 30.93 | 163.81 | 16.98 | 0.00 | 0.00 | 0.00 |
August | 119.20 | 86.18 | 33.02 | 150.87 | 17.96 | 0.00 | 0.00 | 0.00 |
September | 96.43 | 70.76 | 25.66 | 118.54 | 25.93 | 0.00 | 0.00 | 0.00 |
October | 71.90 | 55.77 | 16.13 | 83.45 | 34.07 | 0.00 | 0.00 | 0.00 |
November | 49.67 | 34.56 | 15.11 | 54.57 | 36.46 | 0.00 | 0.00 | 0.00 |
December | 39.88 | 29.36 | 10.51 | 40.72 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.80 | 65.59 | 23.21 | 106.75 | 30.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.88 | 29.36 | 10.51 | 40.72 | 16.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.02 | 103.86 | 33.02 | 164.38 | 46.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.56 | 30.65 | 14.91 | 48.24 | 45.33 | 0.00 | 0.00 | 0.00 |
February | 63.07 | 44.61 | 18.46 | 70.62 | 40.19 | 0.00 | 0.00 | 0.00 |
March | 83.36 | 57.94 | 25.42 | 98.44 | 31.41 | 0.00 | 0.00 | 0.00 |
April | 112.98 | 81.74 | 31.23 | 136.03 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 123.56 | 93.81 | 29.76 | 149.39 | 24.90 | 0.00 | 0.00 | 0.00 |
June | 131.02 | 103.86 | 27.15 | 164.38 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 127.59 | 96.66 | 30.93 | 163.81 | 16.98 | 0.00 | 0.00 | 0.00 |
August | 119.20 | 86.18 | 33.02 | 150.87 | 17.96 | 0.00 | 0.00 | 0.00 |
September | 96.43 | 70.76 | 25.66 | 118.54 | 25.93 | 0.00 | 0.00 | 0.00 |
October | 71.90 | 55.77 | 16.13 | 83.45 | 34.07 | 0.00 | 0.00 | 0.00 |
November | 49.67 | 34.56 | 15.11 | 54.57 | 36.46 | 0.00 | 0.00 | 0.00 |
December | 39.88 | 29.36 | 10.51 | 40.72 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.80 | 65.59 | 23.21 | 106.75 | 30.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.88 | 29.36 | 10.51 | 40.72 | 16.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.02 | 103.86 | 33.02 | 164.38 | 46.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.56 | 30.65 | 14.91 | 48.24 | 45.33 | 0.00 | 0.00 | 0.00 |
February | 63.07 | 44.61 | 18.46 | 70.62 | 40.19 | 0.00 | 0.00 | 0.00 |
March | 83.36 | 57.94 | 25.42 | 98.44 | 31.41 | 0.00 | 0.00 | 0.00 |
April | 112.98 | 81.74 | 31.23 | 136.03 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 123.56 | 93.81 | 29.76 | 149.39 | 24.90 | 0.00 | 0.00 | 0.00 |
June | 131.02 | 103.86 | 27.15 | 164.38 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 127.59 | 96.66 | 30.93 | 163.81 | 16.98 | 0.00 | 0.00 | 0.00 |
August | 119.20 | 86.18 | 33.02 | 150.87 | 17.96 | 0.00 | 0.00 | 0.00 |
September | 96.43 | 70.76 | 25.66 | 118.54 | 25.93 | 0.00 | 0.00 | 0.00 |
October | 71.90 | 55.77 | 16.13 | 83.45 | 34.07 | 0.00 | 0.00 | 0.00 |
November | 49.67 | 34.56 | 15.11 | 54.57 | 36.46 | 0.00 | 0.00 | 0.00 |
December | 39.88 | 29.36 | 10.51 | 40.72 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.80 | 65.59 | 23.21 | 106.75 | 30.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.88 | 29.36 | 10.51 | 40.72 | 16.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.02 | 103.86 | 33.02 | 164.38 | 46.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.56 | 30.65 | 14.91 | 48.24 | 45.33 | 0.00 | 0.00 | 0.00 |
February | 63.07 | 44.61 | 18.46 | 70.62 | 40.19 | 0.00 | 0.00 | 0.00 |
March | 83.36 | 57.94 | 25.42 | 98.44 | 31.41 | 0.00 | 0.00 | 0.00 |
April | 112.98 | 81.74 | 31.23 | 136.03 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 123.56 | 93.81 | 29.76 | 149.39 | 24.90 | 0.00 | 0.00 | 0.00 |
June | 131.02 | 103.86 | 27.15 | 164.38 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 127.59 | 96.66 | 30.93 | 163.81 | 16.98 | 0.00 | 0.00 | 0.00 |
August | 119.20 | 86.18 | 33.02 | 150.87 | 17.96 | 0.00 | 0.00 | 0.00 |
September | 96.43 | 70.76 | 25.66 | 118.54 | 25.93 | 0.00 | 0.00 | 0.00 |
October | 71.90 | 55.77 | 16.13 | 83.45 | 34.07 | 0.00 | 0.00 | 0.00 |
November | 49.67 | 34.56 | 15.11 | 54.57 | 36.46 | 0.00 | 0.00 | 0.00 |
December | 39.88 | 29.36 | 10.51 | 40.72 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.80 | 65.59 | 23.21 | 106.75 | 30.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.88 | 29.36 | 10.51 | 40.72 | 16.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.02 | 103.86 | 33.02 | 164.38 | 46.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.56 | 30.65 | 14.91 | 48.24 | 45.33 | 0.00 | 0.00 | 0.00 |
February | 63.07 | 44.61 | 18.46 | 70.62 | 40.19 | 0.00 | 0.00 | 0.00 |
March | 83.36 | 57.94 | 25.42 | 98.44 | 31.41 | 0.00 | 0.00 | 0.00 |
April | 112.98 | 81.74 | 31.23 | 136.03 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 123.56 | 93.81 | 29.76 | 149.39 | 24.90 | 0.00 | 0.00 | 0.00 |
June | 131.02 | 103.86 | 27.15 | 164.38 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 127.59 | 96.66 | 30.93 | 163.81 | 16.98 | 0.00 | 0.00 | 0.00 |
August | 119.20 | 86.18 | 33.02 | 150.87 | 17.96 | 0.00 | 0.00 | 0.00 |
September | 96.43 | 70.76 | 25.66 | 118.54 | 25.93 | 0.00 | 0.00 | 0.00 |
October | 71.90 | 55.77 | 16.13 | 83.45 | 34.07 | 0.00 | 0.00 | 0.00 |
November | 49.67 | 34.56 | 15.11 | 54.57 | 36.46 | 0.00 | 0.00 | 0.00 |
December | 39.88 | 29.36 | 10.51 | 40.72 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.80 | 65.59 | 23.21 | 106.75 | 30.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.88 | 29.36 | 10.51 | 40.72 | 16.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.02 | 103.86 | 33.02 | 164.38 | 46.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.56 | 30.65 | 14.91 | 48.24 | 45.33 | 0.00 | 0.00 | 0.00 |
February | 63.07 | 44.61 | 18.46 | 70.62 | 40.19 | 0.00 | 0.00 | 0.00 |
March | 83.36 | 57.94 | 25.42 | 98.44 | 31.41 | 0.00 | 0.00 | 0.00 |
April | 112.98 | 81.74 | 31.23 | 136.03 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 123.56 | 93.81 | 29.76 | 149.39 | 24.90 | 0.00 | 0.00 | 0.00 |
June | 131.02 | 103.86 | 27.15 | 164.38 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 127.59 | 96.66 | 30.93 | 163.81 | 16.98 | 0.00 | 0.00 | 0.00 |
August | 119.20 | 86.18 | 33.02 | 150.87 | 17.96 | 0.00 | 0.00 | 0.00 |
September | 96.43 | 70.76 | 25.66 | 118.54 | 25.93 | 0.00 | 0.00 | 0.00 |
October | 71.90 | 55.77 | 16.13 | 83.45 | 34.07 | 0.00 | 0.00 | 0.00 |
November | 49.67 | 34.56 | 15.11 | 54.57 | 36.46 | 0.00 | 0.00 | 0.00 |
December | 39.88 | 29.36 | 10.51 | 40.72 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.80 | 65.59 | 23.21 | 106.75 | 30.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.88 | 29.36 | 10.51 | 40.72 | 16.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.02 | 103.86 | 33.02 | 164.38 | 46.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.56 | 30.65 | 14.91 | 48.24 | 45.33 | 0.00 | 0.00 | 0.00 |
February | 63.07 | 44.61 | 18.46 | 70.62 | 40.19 | 0.00 | 0.00 | 0.00 |
March | 83.36 | 57.94 | 25.42 | 98.44 | 31.41 | 0.00 | 0.00 | 0.00 |
April | 112.98 | 81.74 | 31.23 | 136.03 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 123.56 | 93.81 | 29.76 | 149.39 | 24.90 | 0.00 | 0.00 | 0.00 |
June | 131.02 | 103.86 | 27.15 | 164.38 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 127.59 | 96.66 | 30.93 | 163.81 | 16.98 | 0.00 | 0.00 | 0.00 |
August | 119.20 | 86.18 | 33.02 | 150.87 | 17.96 | 0.00 | 0.00 | 0.00 |
September | 96.43 | 70.76 | 25.66 | 118.54 | 25.93 | 0.00 | 0.00 | 0.00 |
October | 71.90 | 55.77 | 16.13 | 83.45 | 34.07 | 0.00 | 0.00 | 0.00 |
November | 49.67 | 34.56 | 15.11 | 54.57 | 36.46 | 0.00 | 0.00 | 0.00 |
December | 39.88 | 29.36 | 10.51 | 40.72 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.80 | 65.59 | 23.21 | 106.75 | 30.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.88 | 29.36 | 10.51 | 40.72 | 16.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.02 | 103.86 | 33.02 | 164.38 | 46.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 78.54 | 60.73 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 110.28 | 54.02 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 148.17 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 199.07 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 215.06 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 233.02 | 42.32 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 229.97 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 212.76 | 38.44 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 169.57 | 48.29 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 122.11 | 57.81 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 85.16 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 67.31 | 62.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 156.12 | 48.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 67.31 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 233.02 | 62.21 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294623E+09 | 0.167889E+09 | 0.126733E+09 | 0.312162E+09 | 0.309745E+09 |
February | 0.341664E+09 | 0.196981E+09 | 0.144683E+09 | 0.385737E+09 | 0.245534E+09 |
March | 0.424212E+09 | 0.225857E+09 | 0.198355E+09 | 0.509467E+09 | 0.202989E+09 |
April | 0.523019E+09 | 0.277973E+09 | 0.245047E+09 | 0.653346E+09 | 0.144007E+09 |
May | 0.515092E+09 | 0.266140E+09 | 0.248952E+09 | 0.660027E+09 | 0.133141E+09 |
June | 0.531373E+09 | 0.296111E+09 | 0.235262E+09 | 0.749172E+09 | 0.104052E+09 |
July | 0.496145E+09 | 0.242822E+09 | 0.253322E+09 | 0.725480E+09 | 80315033.43 |
August | 0.506398E+09 | 0.233810E+09 | 0.272588E+09 | 0.716676E+09 | 91374115.65 |
September | 0.444653E+09 | 0.234711E+09 | 0.209941E+09 | 0.595825E+09 | 0.138147E+09 |
October | 0.418568E+09 | 0.260004E+09 | 0.158563E+09 | 0.511555E+09 | 0.210640E+09 |
November | 0.317753E+09 | 0.186709E+09 | 0.131044E+09 | 0.351925E+09 | 0.232366E+09 |
December | 0.284028E+09 | 0.177958E+09 | 0.106070E+09 | 0.290470E+09 | 0.320689E+09 |
Annual Sum or Average | 0.509753E+10 | 0.276697E+10 | 0.233056E+10 | 0.646184E+10 | 0.221300E+10 |
Minimum of Months | 0.284028E+09 | 0.167889E+09 | 0.106070E+09 | 0.290470E+09 | 80315033.43 |
Maximum of Months | 0.531373E+09 | 0.296111E+09 | 0.272588E+09 | 0.749172E+09 | 0.320689E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294623E+09 | 0.167889E+09 | 0.126733E+09 | 0.312162E+09 | 0.309745E+09 |
February | 0.341664E+09 | 0.196981E+09 | 0.144683E+09 | 0.385737E+09 | 0.245534E+09 |
March | 0.424212E+09 | 0.225857E+09 | 0.198355E+09 | 0.509467E+09 | 0.202989E+09 |
April | 0.523019E+09 | 0.277973E+09 | 0.245047E+09 | 0.653346E+09 | 0.144007E+09 |
May | 0.515092E+09 | 0.266140E+09 | 0.248952E+09 | 0.660027E+09 | 0.133141E+09 |
June | 0.531373E+09 | 0.296111E+09 | 0.235262E+09 | 0.749172E+09 | 0.104052E+09 |
July | 0.496145E+09 | 0.242822E+09 | 0.253322E+09 | 0.725480E+09 | 80315033.43 |
August | 0.506398E+09 | 0.233810E+09 | 0.272588E+09 | 0.716676E+09 | 91374115.65 |
September | 0.444653E+09 | 0.234711E+09 | 0.209941E+09 | 0.595825E+09 | 0.138147E+09 |
October | 0.418568E+09 | 0.260004E+09 | 0.158563E+09 | 0.511555E+09 | 0.210640E+09 |
November | 0.317753E+09 | 0.186709E+09 | 0.131044E+09 | 0.351925E+09 | 0.232366E+09 |
December | 0.284028E+09 | 0.177958E+09 | 0.106070E+09 | 0.290470E+09 | 0.320689E+09 |
Annual Sum or Average | 0.509753E+10 | 0.276697E+10 | 0.233056E+10 | 0.646184E+10 | 0.221300E+10 |
Minimum of Months | 0.284028E+09 | 0.167889E+09 | 0.106070E+09 | 0.290470E+09 | 80315033.43 |
Maximum of Months | 0.531373E+09 | 0.296111E+09 | 0.272588E+09 | 0.749172E+09 | 0.320689E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60237889.17 | 0.00 | 60237889.17 | 22285221.26 | 0.187071E+09 |
February | 68001379.00 | 0.00 | 68001379.00 | 37040844.89 | 0.147411E+09 |
March | 94991853.51 | 9264.21 | 94982589.30 | 79577431.90 | 0.120307E+09 |
April | 0.116841E+09 | 1219975.40 | 0.115621E+09 | 0.110899E+09 | 82557632.01 |
May | 0.131280E+09 | 8679367.36 | 0.122600E+09 | 0.142081E+09 | 74132477.18 |
June | 0.144083E+09 | 23663385.93 | 0.120419E+09 | 0.201357E+09 | 56032578.47 |
July | 0.136302E+09 | 11070197.43 | 0.125232E+09 | 0.202724E+09 | 44650323.04 |
August | 0.127204E+09 | 3318261.79 | 0.123886E+09 | 0.171777E+09 | 50877319.26 |
September | 98136883.24 | 59033.19 | 98077850.05 | 0.111961E+09 | 80731749.18 |
October | 75608876.71 | 0.00 | 75608876.71 | 55647647.35 | 0.125325E+09 |
November | 62138539.86 | 0.00 | 62138539.86 | 28442873.91 | 0.140892E+09 |
December | 51271545.87 | 0.00 | 51271545.87 | 8861752.08 | 0.197401E+09 |
Annual Sum or Average | 0.116610E+10 | 48019485.30 | 0.111808E+10 | 0.117265E+10 | 0.130739E+10 |
Minimum of Months | 51271545.87 | 0.00 | 51271545.87 | 8861752.08 | 44650323.04 |
Maximum of Months | 0.144083E+09 | 23663385.93 | 0.125232E+09 | 0.202724E+09 | 0.197401E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60236248.86 | 0.00 | 60236248.86 | 22283952.45 | 0.187071E+09 |
February | 67999603.24 | 0.00 | 67999603.24 | 37039292.49 | 0.147410E+09 |
March | 94989318.65 | 9263.77 | 94980054.88 | 79574806.32 | 0.120307E+09 |
April | 0.116838E+09 | 1219918.22 | 0.115618E+09 | 0.110895E+09 | 82556849.80 |
May | 0.131276E+09 | 8678960.54 | 0.122597E+09 | 0.142077E+09 | 74131695.48 |
June | 0.144079E+09 | 23662276.79 | 0.120417E+09 | 0.201352E+09 | 56031868.58 |
July | 0.136299E+09 | 11069678.55 | 0.125229E+09 | 0.202720E+09 | 44649691.67 |
August | 0.127201E+09 | 3318106.26 | 0.123883E+09 | 0.171773E+09 | 50876719.45 |
September | 98134413.09 | 59030.42 | 98075382.66 | 0.111959E+09 | 80730996.04 |
October | 75607065.88 | 0.00 | 75607065.88 | 55646075.51 | 0.125324E+09 |
November | 62136883.34 | 0.00 | 62136883.34 | 28441469.20 | 0.140891E+09 |
December | 51270248.51 | 0.00 | 51270248.51 | 8861072.52 | 0.197401E+09 |
Annual Sum or Average | 0.116607E+10 | 48017234.57 | 0.111805E+10 | 0.117262E+10 | 0.130738E+10 |
Minimum of Months | 51270248.51 | 0.00 | 51270248.51 | 8861072.52 | 44649691.67 |
Maximum of Months | 0.144079E+09 | 23662276.79 | 0.125229E+09 | 0.202720E+09 | 0.197401E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122026E+09 | 82100994.72 | 39924759.85 | 0.129206E+09 | 0.121415E+09 |
February | 0.152590E+09 | 0.107932E+09 | 44657459.97 | 0.170856E+09 | 97225196.65 |
March | 0.223276E+09 | 0.155187E+09 | 68088983.82 | 0.263651E+09 | 84124968.40 |
April | 0.292842E+09 | 0.211883E+09 | 80959381.15 | 0.352587E+09 | 69430459.24 |
May | 0.330953E+09 | 0.251253E+09 | 79699922.47 | 0.400138E+09 | 66682842.85 |
June | 0.339596E+09 | 0.269216E+09 | 70379057.22 | 0.426072E+09 | 55057685.82 |
July | 0.341739E+09 | 0.258892E+09 | 82846693.70 | 0.438759E+09 | 45491255.14 |
August | 0.319263E+09 | 0.230819E+09 | 88443936.85 | 0.404094E+09 | 48113024.41 |
September | 0.249941E+09 | 0.183421E+09 | 66520778.72 | 0.307254E+09 | 67220996.40 |
October | 0.192578E+09 | 0.149378E+09 | 43200748.53 | 0.223505E+09 | 91263801.85 |
November | 0.128734E+09 | 89572288.15 | 39161301.06 | 0.141445E+09 | 94511242.23 |
December | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 0.125509E+09 |
Annual Sum or Average | 0.280035E+10 | 0.206831E+10 | 0.732042E+09 | 0.336662E+10 | 0.966045E+09 |
Minimum of Months | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 45491255.14 |
Maximum of Months | 0.341739E+09 | 0.269216E+09 | 88443936.85 | 0.438759E+09 | 0.125509E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122026E+09 | 82100994.72 | 39924759.85 | 0.129206E+09 | 0.121415E+09 |
February | 0.152590E+09 | 0.107932E+09 | 44657459.97 | 0.170856E+09 | 97225196.65 |
March | 0.223276E+09 | 0.155187E+09 | 68088983.82 | 0.263651E+09 | 84124968.40 |
April | 0.292842E+09 | 0.211883E+09 | 80959381.15 | 0.352587E+09 | 69430459.24 |
May | 0.330953E+09 | 0.251253E+09 | 79699922.47 | 0.400138E+09 | 66682842.85 |
June | 0.339596E+09 | 0.269216E+09 | 70379057.22 | 0.426072E+09 | 55057685.82 |
July | 0.341739E+09 | 0.258892E+09 | 82846693.70 | 0.438759E+09 | 45491255.14 |
August | 0.319263E+09 | 0.230819E+09 | 88443936.85 | 0.404094E+09 | 48113024.41 |
September | 0.249941E+09 | 0.183421E+09 | 66520778.72 | 0.307254E+09 | 67220996.40 |
October | 0.192578E+09 | 0.149378E+09 | 43200748.53 | 0.223505E+09 | 91263801.85 |
November | 0.128734E+09 | 89572288.15 | 39161301.06 | 0.141445E+09 | 94511242.23 |
December | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 0.125509E+09 |
Annual Sum or Average | 0.280035E+10 | 0.206831E+10 | 0.732042E+09 | 0.336662E+10 | 0.966045E+09 |
Minimum of Months | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 45491255.14 |
Maximum of Months | 0.341739E+09 | 0.269216E+09 | 88443936.85 | 0.438759E+09 | 0.125509E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122026E+09 | 82100994.72 | 39924759.85 | 0.129206E+09 | 0.121415E+09 |
February | 0.152590E+09 | 0.107932E+09 | 44657459.97 | 0.170856E+09 | 97225196.65 |
March | 0.223276E+09 | 0.155187E+09 | 68088983.82 | 0.263651E+09 | 84124968.40 |
April | 0.292842E+09 | 0.211883E+09 | 80959381.15 | 0.352587E+09 | 69430459.24 |
May | 0.330953E+09 | 0.251253E+09 | 79699922.47 | 0.400138E+09 | 66682842.85 |
June | 0.339596E+09 | 0.269216E+09 | 70379057.22 | 0.426072E+09 | 55057685.82 |
July | 0.341739E+09 | 0.258892E+09 | 82846693.70 | 0.438759E+09 | 45491255.14 |
August | 0.319263E+09 | 0.230819E+09 | 88443936.85 | 0.404094E+09 | 48113024.41 |
September | 0.249941E+09 | 0.183421E+09 | 66520778.72 | 0.307254E+09 | 67220996.40 |
October | 0.192578E+09 | 0.149378E+09 | 43200748.53 | 0.223505E+09 | 91263801.85 |
November | 0.128734E+09 | 89572288.15 | 39161301.06 | 0.141445E+09 | 94511242.23 |
December | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 0.125509E+09 |
Annual Sum or Average | 0.280035E+10 | 0.206831E+10 | 0.732042E+09 | 0.336662E+10 | 0.966045E+09 |
Minimum of Months | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 45491255.14 |
Maximum of Months | 0.341739E+09 | 0.269216E+09 | 88443936.85 | 0.438759E+09 | 0.125509E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122026E+09 | 82100994.72 | 39924759.85 | 0.129206E+09 | 0.121415E+09 |
February | 0.152590E+09 | 0.107932E+09 | 44657459.97 | 0.170856E+09 | 97225196.65 |
March | 0.223276E+09 | 0.155187E+09 | 68088983.82 | 0.263651E+09 | 84124968.40 |
April | 0.292842E+09 | 0.211883E+09 | 80959381.15 | 0.352587E+09 | 69430459.24 |
May | 0.330953E+09 | 0.251253E+09 | 79699922.47 | 0.400138E+09 | 66682842.85 |
June | 0.339596E+09 | 0.269216E+09 | 70379057.22 | 0.426072E+09 | 55057685.82 |
July | 0.341739E+09 | 0.258892E+09 | 82846693.70 | 0.438759E+09 | 45491255.14 |
August | 0.319263E+09 | 0.230819E+09 | 88443936.85 | 0.404094E+09 | 48113024.41 |
September | 0.249941E+09 | 0.183421E+09 | 66520778.72 | 0.307254E+09 | 67220996.40 |
October | 0.192578E+09 | 0.149378E+09 | 43200748.53 | 0.223505E+09 | 91263801.85 |
November | 0.128734E+09 | 89572288.15 | 39161301.06 | 0.141445E+09 | 94511242.23 |
December | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 0.125509E+09 |
Annual Sum or Average | 0.280035E+10 | 0.206831E+10 | 0.732042E+09 | 0.336662E+10 | 0.966045E+09 |
Minimum of Months | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 45491255.14 |
Maximum of Months | 0.341739E+09 | 0.269216E+09 | 88443936.85 | 0.438759E+09 | 0.125509E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122026E+09 | 82100994.72 | 39924759.85 | 0.129206E+09 | 0.121415E+09 |
February | 0.152590E+09 | 0.107932E+09 | 44657459.97 | 0.170856E+09 | 97225196.65 |
March | 0.223276E+09 | 0.155187E+09 | 68088983.82 | 0.263651E+09 | 84124968.40 |
April | 0.292842E+09 | 0.211883E+09 | 80959381.15 | 0.352587E+09 | 69430459.24 |
May | 0.330953E+09 | 0.251253E+09 | 79699922.47 | 0.400138E+09 | 66682842.85 |
June | 0.339596E+09 | 0.269216E+09 | 70379057.22 | 0.426072E+09 | 55057685.82 |
July | 0.341739E+09 | 0.258892E+09 | 82846693.70 | 0.438759E+09 | 45491255.14 |
August | 0.319263E+09 | 0.230819E+09 | 88443936.85 | 0.404094E+09 | 48113024.41 |
September | 0.249941E+09 | 0.183421E+09 | 66520778.72 | 0.307254E+09 | 67220996.40 |
October | 0.192578E+09 | 0.149378E+09 | 43200748.53 | 0.223505E+09 | 91263801.85 |
November | 0.128734E+09 | 89572288.15 | 39161301.06 | 0.141445E+09 | 94511242.23 |
December | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 0.125509E+09 |
Annual Sum or Average | 0.280035E+10 | 0.206831E+10 | 0.732042E+09 | 0.336662E+10 | 0.966045E+09 |
Minimum of Months | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 45491255.14 |
Maximum of Months | 0.341739E+09 | 0.269216E+09 | 88443936.85 | 0.438759E+09 | 0.125509E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122026E+09 | 82100994.72 | 39924759.85 | 0.129206E+09 | 0.121415E+09 |
February | 0.152590E+09 | 0.107932E+09 | 44657459.97 | 0.170856E+09 | 97225196.65 |
March | 0.223276E+09 | 0.155187E+09 | 68088983.82 | 0.263651E+09 | 84124968.40 |
April | 0.292842E+09 | 0.211883E+09 | 80959381.15 | 0.352587E+09 | 69430459.24 |
May | 0.330953E+09 | 0.251253E+09 | 79699922.47 | 0.400138E+09 | 66682842.85 |
June | 0.339596E+09 | 0.269216E+09 | 70379057.22 | 0.426072E+09 | 55057685.82 |
July | 0.341739E+09 | 0.258892E+09 | 82846693.70 | 0.438759E+09 | 45491255.14 |
August | 0.319263E+09 | 0.230819E+09 | 88443936.85 | 0.404094E+09 | 48113024.41 |
September | 0.249941E+09 | 0.183421E+09 | 66520778.72 | 0.307254E+09 | 67220996.40 |
October | 0.192578E+09 | 0.149378E+09 | 43200748.53 | 0.223505E+09 | 91263801.85 |
November | 0.128734E+09 | 89572288.15 | 39161301.06 | 0.141445E+09 | 94511242.23 |
December | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 0.125509E+09 |
Annual Sum or Average | 0.280035E+10 | 0.206831E+10 | 0.732042E+09 | 0.336662E+10 | 0.966045E+09 |
Minimum of Months | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 45491255.14 |
Maximum of Months | 0.341739E+09 | 0.269216E+09 | 88443936.85 | 0.438759E+09 | 0.125509E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122026E+09 | 82100994.72 | 39924759.85 | 0.129206E+09 | 0.121415E+09 |
February | 0.152590E+09 | 0.107932E+09 | 44657459.97 | 0.170856E+09 | 97225196.65 |
March | 0.223276E+09 | 0.155187E+09 | 68088983.82 | 0.263651E+09 | 84124968.40 |
April | 0.292842E+09 | 0.211883E+09 | 80959381.15 | 0.352587E+09 | 69430459.24 |
May | 0.330953E+09 | 0.251253E+09 | 79699922.47 | 0.400138E+09 | 66682842.85 |
June | 0.339596E+09 | 0.269216E+09 | 70379057.22 | 0.426072E+09 | 55057685.82 |
July | 0.341739E+09 | 0.258892E+09 | 82846693.70 | 0.438759E+09 | 45491255.14 |
August | 0.319263E+09 | 0.230819E+09 | 88443936.85 | 0.404094E+09 | 48113024.41 |
September | 0.249941E+09 | 0.183421E+09 | 66520778.72 | 0.307254E+09 | 67220996.40 |
October | 0.192578E+09 | 0.149378E+09 | 43200748.53 | 0.223505E+09 | 91263801.85 |
November | 0.128734E+09 | 89572288.15 | 39161301.06 | 0.141445E+09 | 94511242.23 |
December | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 0.125509E+09 |
Annual Sum or Average | 0.280035E+10 | 0.206831E+10 | 0.732042E+09 | 0.336662E+10 | 0.966045E+09 |
Minimum of Months | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 45491255.14 |
Maximum of Months | 0.341739E+09 | 0.269216E+09 | 88443936.85 | 0.438759E+09 | 0.125509E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122026E+09 | 82100994.72 | 39924759.85 | 0.129206E+09 | 0.121415E+09 |
February | 0.152590E+09 | 0.107932E+09 | 44657459.97 | 0.170856E+09 | 97225196.65 |
March | 0.223276E+09 | 0.155187E+09 | 68088983.82 | 0.263651E+09 | 84124968.40 |
April | 0.292842E+09 | 0.211883E+09 | 80959381.15 | 0.352587E+09 | 69430459.24 |
May | 0.330953E+09 | 0.251253E+09 | 79699922.47 | 0.400138E+09 | 66682842.85 |
June | 0.339596E+09 | 0.269216E+09 | 70379057.22 | 0.426072E+09 | 55057685.82 |
July | 0.341739E+09 | 0.258892E+09 | 82846693.70 | 0.438759E+09 | 45491255.14 |
August | 0.319263E+09 | 0.230819E+09 | 88443936.85 | 0.404094E+09 | 48113024.41 |
September | 0.249941E+09 | 0.183421E+09 | 66520778.72 | 0.307254E+09 | 67220996.40 |
October | 0.192578E+09 | 0.149378E+09 | 43200748.53 | 0.223505E+09 | 91263801.85 |
November | 0.128734E+09 | 89572288.15 | 39161301.06 | 0.141445E+09 | 94511242.23 |
December | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 0.125509E+09 |
Annual Sum or Average | 0.280035E+10 | 0.206831E+10 | 0.732042E+09 | 0.336662E+10 | 0.966045E+09 |
Minimum of Months | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 45491255.14 |
Maximum of Months | 0.341739E+09 | 0.269216E+09 | 88443936.85 | 0.438759E+09 | 0.125509E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122026E+09 | 82100994.72 | 39924759.85 | 0.129206E+09 | 0.121415E+09 |
February | 0.152590E+09 | 0.107932E+09 | 44657459.97 | 0.170856E+09 | 97225196.65 |
March | 0.223276E+09 | 0.155187E+09 | 68088983.82 | 0.263651E+09 | 84124968.40 |
April | 0.292842E+09 | 0.211883E+09 | 80959381.15 | 0.352587E+09 | 69430459.24 |
May | 0.330953E+09 | 0.251253E+09 | 79699922.47 | 0.400138E+09 | 66682842.85 |
June | 0.339596E+09 | 0.269216E+09 | 70379057.22 | 0.426072E+09 | 55057685.82 |
July | 0.341739E+09 | 0.258892E+09 | 82846693.70 | 0.438759E+09 | 45491255.14 |
August | 0.319263E+09 | 0.230819E+09 | 88443936.85 | 0.404094E+09 | 48113024.41 |
September | 0.249941E+09 | 0.183421E+09 | 66520778.72 | 0.307254E+09 | 67220996.40 |
October | 0.192578E+09 | 0.149378E+09 | 43200748.53 | 0.223505E+09 | 91263801.85 |
November | 0.128734E+09 | 89572288.15 | 39161301.06 | 0.141445E+09 | 94511242.23 |
December | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 0.125509E+09 |
Annual Sum or Average | 0.280035E+10 | 0.206831E+10 | 0.732042E+09 | 0.336662E+10 | 0.966045E+09 |
Minimum of Months | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 45491255.14 |
Maximum of Months | 0.341739E+09 | 0.269216E+09 | 88443936.85 | 0.438759E+09 | 0.125509E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122026E+09 | 82100994.72 | 39924759.85 | 0.129206E+09 | 0.121415E+09 |
February | 0.152590E+09 | 0.107932E+09 | 44657459.97 | 0.170856E+09 | 97225196.65 |
March | 0.223276E+09 | 0.155187E+09 | 68088983.82 | 0.263651E+09 | 84124968.40 |
April | 0.292842E+09 | 0.211883E+09 | 80959381.15 | 0.352587E+09 | 69430459.24 |
May | 0.330953E+09 | 0.251253E+09 | 79699922.47 | 0.400138E+09 | 66682842.85 |
June | 0.339596E+09 | 0.269216E+09 | 70379057.22 | 0.426072E+09 | 55057685.82 |
July | 0.341739E+09 | 0.258892E+09 | 82846693.70 | 0.438759E+09 | 45491255.14 |
August | 0.319263E+09 | 0.230819E+09 | 88443936.85 | 0.404094E+09 | 48113024.41 |
September | 0.249941E+09 | 0.183421E+09 | 66520778.72 | 0.307254E+09 | 67220996.40 |
October | 0.192578E+09 | 0.149378E+09 | 43200748.53 | 0.223505E+09 | 91263801.85 |
November | 0.128734E+09 | 89572288.15 | 39161301.06 | 0.141445E+09 | 94511242.23 |
December | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 0.125509E+09 |
Annual Sum or Average | 0.280035E+10 | 0.206831E+10 | 0.732042E+09 | 0.336662E+10 | 0.966045E+09 |
Minimum of Months | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 45491255.14 |
Maximum of Months | 0.341739E+09 | 0.269216E+09 | 88443936.85 | 0.438759E+09 | 0.125509E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122026E+09 | 82100994.72 | 39924759.85 | 0.129206E+09 | 0.121415E+09 |
February | 0.152590E+09 | 0.107932E+09 | 44657459.97 | 0.170856E+09 | 97225196.65 |
March | 0.223276E+09 | 0.155187E+09 | 68088983.82 | 0.263651E+09 | 84124968.40 |
April | 0.292842E+09 | 0.211883E+09 | 80959381.15 | 0.352587E+09 | 69430459.24 |
May | 0.330953E+09 | 0.251253E+09 | 79699922.47 | 0.400138E+09 | 66682842.85 |
June | 0.339596E+09 | 0.269216E+09 | 70379057.22 | 0.426072E+09 | 55057685.82 |
July | 0.341739E+09 | 0.258892E+09 | 82846693.70 | 0.438759E+09 | 45491255.14 |
August | 0.319263E+09 | 0.230819E+09 | 88443936.85 | 0.404094E+09 | 48113024.41 |
September | 0.249941E+09 | 0.183421E+09 | 66520778.72 | 0.307254E+09 | 67220996.40 |
October | 0.192578E+09 | 0.149378E+09 | 43200748.53 | 0.223505E+09 | 91263801.85 |
November | 0.128734E+09 | 89572288.15 | 39161301.06 | 0.141445E+09 | 94511242.23 |
December | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 0.125509E+09 |
Annual Sum or Average | 0.280035E+10 | 0.206831E+10 | 0.732042E+09 | 0.336662E+10 | 0.966045E+09 |
Minimum of Months | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 45491255.14 |
Maximum of Months | 0.341739E+09 | 0.269216E+09 | 88443936.85 | 0.438759E+09 | 0.125509E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122026E+09 | 82100994.72 | 39924759.85 | 0.129206E+09 | 0.121415E+09 |
February | 0.152590E+09 | 0.107932E+09 | 44657459.97 | 0.170856E+09 | 97225196.65 |
March | 0.223276E+09 | 0.155187E+09 | 68088983.82 | 0.263651E+09 | 84124968.40 |
April | 0.292842E+09 | 0.211883E+09 | 80959381.15 | 0.352587E+09 | 69430459.24 |
May | 0.330953E+09 | 0.251253E+09 | 79699922.47 | 0.400138E+09 | 66682842.85 |
June | 0.339596E+09 | 0.269216E+09 | 70379057.22 | 0.426072E+09 | 55057685.82 |
July | 0.341739E+09 | 0.258892E+09 | 82846693.70 | 0.438759E+09 | 45491255.14 |
August | 0.319263E+09 | 0.230819E+09 | 88443936.85 | 0.404094E+09 | 48113024.41 |
September | 0.249941E+09 | 0.183421E+09 | 66520778.72 | 0.307254E+09 | 67220996.40 |
October | 0.192578E+09 | 0.149378E+09 | 43200748.53 | 0.223505E+09 | 91263801.85 |
November | 0.128734E+09 | 89572288.15 | 39161301.06 | 0.141445E+09 | 94511242.23 |
December | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 0.125509E+09 |
Annual Sum or Average | 0.280035E+10 | 0.206831E+10 | 0.732042E+09 | 0.336662E+10 | 0.966045E+09 |
Minimum of Months | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 45491255.14 |
Maximum of Months | 0.341739E+09 | 0.269216E+09 | 88443936.85 | 0.438759E+09 | 0.125509E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122026E+09 | 82100994.72 | 39924759.85 | 0.129206E+09 | 0.121415E+09 |
February | 0.152590E+09 | 0.107932E+09 | 44657459.97 | 0.170856E+09 | 97225196.65 |
March | 0.223276E+09 | 0.155187E+09 | 68088983.82 | 0.263651E+09 | 84124968.40 |
April | 0.292842E+09 | 0.211883E+09 | 80959381.15 | 0.352587E+09 | 69430459.24 |
May | 0.330953E+09 | 0.251253E+09 | 79699922.47 | 0.400138E+09 | 66682842.85 |
June | 0.339596E+09 | 0.269216E+09 | 70379057.22 | 0.426072E+09 | 55057685.82 |
July | 0.341739E+09 | 0.258892E+09 | 82846693.70 | 0.438759E+09 | 45491255.14 |
August | 0.319263E+09 | 0.230819E+09 | 88443936.85 | 0.404094E+09 | 48113024.41 |
September | 0.249941E+09 | 0.183421E+09 | 66520778.72 | 0.307254E+09 | 67220996.40 |
October | 0.192578E+09 | 0.149378E+09 | 43200748.53 | 0.223505E+09 | 91263801.85 |
November | 0.128734E+09 | 89572288.15 | 39161301.06 | 0.141445E+09 | 94511242.23 |
December | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 0.125509E+09 |
Annual Sum or Average | 0.280035E+10 | 0.206831E+10 | 0.732042E+09 | 0.336662E+10 | 0.966045E+09 |
Minimum of Months | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 45491255.14 |
Maximum of Months | 0.341739E+09 | 0.269216E+09 | 88443936.85 | 0.438759E+09 | 0.125509E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122026E+09 | 82100994.72 | 39924759.85 | 0.129206E+09 | 0.121415E+09 |
February | 0.152590E+09 | 0.107932E+09 | 44657459.97 | 0.170856E+09 | 97225196.65 |
March | 0.223276E+09 | 0.155187E+09 | 68088983.82 | 0.263651E+09 | 84124968.40 |
April | 0.292842E+09 | 0.211883E+09 | 80959381.15 | 0.352587E+09 | 69430459.24 |
May | 0.330953E+09 | 0.251253E+09 | 79699922.47 | 0.400138E+09 | 66682842.85 |
June | 0.339596E+09 | 0.269216E+09 | 70379057.22 | 0.426072E+09 | 55057685.82 |
July | 0.341739E+09 | 0.258892E+09 | 82846693.70 | 0.438759E+09 | 45491255.14 |
August | 0.319263E+09 | 0.230819E+09 | 88443936.85 | 0.404094E+09 | 48113024.41 |
September | 0.249941E+09 | 0.183421E+09 | 66520778.72 | 0.307254E+09 | 67220996.40 |
October | 0.192578E+09 | 0.149378E+09 | 43200748.53 | 0.223505E+09 | 91263801.85 |
November | 0.128734E+09 | 89572288.15 | 39161301.06 | 0.141445E+09 | 94511242.23 |
December | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 0.125509E+09 |
Annual Sum or Average | 0.280035E+10 | 0.206831E+10 | 0.732042E+09 | 0.336662E+10 | 0.966045E+09 |
Minimum of Months | 0.106811E+09 | 78651140.89 | 28159428.50 | 0.109058E+09 | 45491255.14 |
Maximum of Months | 0.341739E+09 | 0.269216E+09 | 88443936.85 | 0.438759E+09 | 0.125509E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.210358E+09 | 0.162669E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.266788E+09 | 0.130690E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.396867E+09 | 0.121385E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.516002E+09 | 0.112544E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.576027E+09 | 0.116847E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.603981E+09 | 0.109684E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.615963E+09 | 0.101707E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.569858E+09 | 0.102949E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.439523E+09 | 0.125179E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.327070E+09 | 0.154838E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.220744E+09 | 0.135610E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.166610E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.492347E+10 | 0.154071E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.180289E+09 | 0.101707E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.615963E+09 | 0.166610E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 246.04 | 367.28 | 264.98 | 125.37 | 139.61 | 0.00 | 0.00 |
February | 346.58 | 321.92 | 338.68 | 162.85 | 175.83 | 0.00 | 0.00 |
March | 438.42 | 239.98 | 387.70 | 168.66 | 219.04 | 0.00 | 0.00 |
April | 588.53 | 173.66 | 493.72 | 215.43 | 278.29 | 0.00 | 0.00 |
May | 597.14 | 152.96 | 482.65 | 205.21 | 277.44 | 0.00 | 0.00 |
June | 729.01 | 119.10 | 521.18 | 246.74 | 274.44 | 0.00 | 0.00 |
July | 691.50 | 91.72 | 472.26 | 189.59 | 282.67 | 0.00 | 0.00 |
August | 662.18 | 104.98 | 473.12 | 177.07 | 296.05 | 0.00 | 0.00 |
September | 545.78 | 168.54 | 418.82 | 181.15 | 237.67 | 0.00 | 0.00 |
October | 421.67 | 249.00 | 369.01 | 194.15 | 174.86 | 0.00 | 0.00 |
November | 290.00 | 284.52 | 293.13 | 144.07 | 149.06 | 0.00 | 0.00 |
December | 216.59 | 379.94 | 250.37 | 132.88 | 117.49 | 0.00 | 0.00 |
Annual Sum or Average | 481.60 | 220.68 | 397.24 | 178.53 | 218.71 | 0.00 | 0.00 |
Minimum of Months | 216.59 | 91.72 | 250.37 | 125.37 | 117.49 | 0.00 | 0.00 |
Maximum of Months | 729.01 | 379.94 | 521.18 | 246.74 | 296.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 675.36 | 634.63 | 637.83 | 429.14 | 208.69 | 0.00 | 0.00 |
February | 988.75 | 562.65 | 883.04 | 624.61 | 258.43 | 0.00 | 0.00 |
March | 1378.11 | 439.72 | 1167.06 | 811.16 | 355.90 | 0.00 | 0.00 |
April | 1904.40 | 375.01 | 1581.71 | 1144.43 | 437.28 | 0.00 | 0.00 |
May | 2091.52 | 348.55 | 1729.89 | 1313.30 | 416.59 | 0.00 | 0.00 |
June | 2301.32 | 297.38 | 1834.23 | 1454.10 | 380.13 | 0.00 | 0.00 |
July | 2293.39 | 237.78 | 1786.27 | 1353.23 | 433.04 | 0.00 | 0.00 |
August | 2112.20 | 251.49 | 1668.79 | 1206.49 | 462.30 | 0.00 | 0.00 |
September | 1659.55 | 363.08 | 1349.99 | 990.70 | 359.29 | 0.00 | 0.00 |
October | 1168.26 | 477.04 | 1006.61 | 780.80 | 225.81 | 0.00 | 0.00 |
November | 763.98 | 510.48 | 695.32 | 483.80 | 211.52 | 0.00 | 0.00 |
December | 570.05 | 656.04 | 558.30 | 411.11 | 147.19 | 0.00 | 0.00 |
Annual Sum or Average | 1494.57 | 428.86 | 1243.18 | 918.20 | 324.98 | 0.00 | 0.00 |
Minimum of Months | 570.05 | 237.78 | 558.30 | 411.11 | 147.19 | 0.00 | 0.00 |
Maximum of Months | 2301.32 | 656.04 | 1834.23 | 1454.10 | 462.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10152.70 | 12405.82 | 2022.82 | 1386.27 | 636.55 | 0.00 | 0.00 |
February | 14118.89 | 10788.78 | 2732.56 | 1944.27 | 788.29 | 0.00 | 0.00 |
March | 19080.71 | 6599.19 | 3539.28 | 2453.69 | 1085.59 | 0.00 | 0.00 |
April | 25768.17 | 4601.29 | 4757.73 | 3423.91 | 1333.82 | 0.00 | 0.00 |
May | 27138.29 | 4301.08 | 5164.65 | 3893.94 | 1270.71 | 0.00 | 0.00 |
June | 35435.85 | 5049.46 | 5471.60 | 4312.10 | 1159.51 | 0.00 | 0.00 |
July | 41347.11 | 5327.63 | 5323.22 | 4002.34 | 1320.88 | 0.00 | 0.00 |
August | 36085.35 | 5026.80 | 4991.78 | 3581.66 | 1410.12 | 0.00 | 0.00 |
September | 23954.34 | 5244.36 | 4066.12 | 2970.18 | 1095.94 | 0.00 | 0.00 |
October | 15816.80 | 6013.82 | 3090.08 | 2401.30 | 688.78 | 0.00 | 0.00 |
November | 10896.40 | 7595.39 | 2196.57 | 1551.38 | 645.19 | 0.00 | 0.00 |
December | 8790.98 | 12285.86 | 1808.04 | 1359.08 | 448.97 | 0.00 | 0.00 |
Annual Sum or Average | 22432.17 | 7089.22 | 3768.24 | 2776.97 | 991.27 | 0.00 | 0.00 |
Minimum of Months | 8790.98 | 4301.08 | 1808.04 | 1359.08 | 448.97 | 0.00 | 0.00 |
Maximum of Months | 41347.11 | 12405.82 | 5471.60 | 4312.10 | 1410.12 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.658981E+09 | 0.983719E+09 | 0.709720E+09 | 0.335779E+09 | 0.373941E+09 | 0.00 | 0.00 |
February | 0.838447E+09 | 0.778783E+09 | 0.819328E+09 | 0.393961E+09 | 0.425367E+09 | 0.00 | 0.00 |
March | 0.117427E+10 | 0.642771E+09 | 0.103840E+10 | 0.451732E+09 | 0.586673E+09 | 0.00 | 0.00 |
April | 0.152548E+10 | 0.450122E+09 | 0.127972E+10 | 0.558385E+09 | 0.721332E+09 | 0.00 | 0.00 |
May | 0.159937E+10 | 0.409699E+09 | 0.129274E+10 | 0.549638E+09 | 0.743101E+09 | 0.00 | 0.00 |
June | 0.188959E+10 | 0.308706E+09 | 0.135091E+10 | 0.639548E+09 | 0.711361E+09 | 0.00 | 0.00 |
July | 0.185212E+10 | 0.245650E+09 | 0.126489E+10 | 0.507785E+09 | 0.757105E+09 | 0.00 | 0.00 |
August | 0.177359E+10 | 0.281188E+09 | 0.126720E+10 | 0.474257E+09 | 0.792944E+09 | 0.00 | 0.00 |
September | 0.141466E+10 | 0.436843E+09 | 0.108558E+10 | 0.469541E+09 | 0.616036E+09 | 0.00 | 0.00 |
October | 0.112939E+10 | 0.666914E+09 | 0.988351E+09 | 0.520009E+09 | 0.468343E+09 | 0.00 | 0.00 |
November | 0.751683E+09 | 0.737464E+09 | 0.759782E+09 | 0.373417E+09 | 0.386364E+09 | 0.00 | 0.00 |
December | 0.580127E+09 | 0.101764E+10 | 0.670598E+09 | 0.355917E+09 | 0.314681E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.151877E+11 | 0.695950E+10 | 0.125272E+11 | 0.562997E+10 | 0.689725E+10 | 0.00 | 0.00 |
Minimum of Months | 0.580127E+09 | 0.245650E+09 | 0.670598E+09 | 0.335779E+09 | 0.314681E+09 | 0.00 | 0.00 |
Maximum of Months | 0.188959E+10 | 0.101764E+10 | 0.135091E+10 | 0.639548E+09 | 0.792944E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180888E+10 | 0.169981E+10 | 0.170836E+10 | 0.114941E+10 | 0.558947E+09 | 0.00 | 0.00 |
February | 0.239198E+10 | 0.136115E+10 | 0.213626E+10 | 0.151105E+10 | 0.625204E+09 | 0.00 | 0.00 |
March | 0.369112E+10 | 0.117775E+10 | 0.312586E+10 | 0.217262E+10 | 0.953246E+09 | 0.00 | 0.00 |
April | 0.493621E+10 | 0.972026E+09 | 0.409979E+10 | 0.296636E+10 | 0.113343E+10 | 0.00 | 0.00 |
May | 0.560193E+10 | 0.933560E+09 | 0.463334E+10 | 0.351754E+10 | 0.111580E+10 | 0.00 | 0.00 |
June | 0.596501E+10 | 0.770808E+09 | 0.475434E+10 | 0.376903E+10 | 0.985307E+09 | 0.00 | 0.00 |
July | 0.614262E+10 | 0.636878E+09 | 0.478435E+10 | 0.362449E+10 | 0.115985E+10 | 0.00 | 0.00 |
August | 0.565731E+10 | 0.673582E+09 | 0.446968E+10 | 0.323146E+10 | 0.123822E+10 | 0.00 | 0.00 |
September | 0.430155E+10 | 0.941094E+09 | 0.349918E+10 | 0.256789E+10 | 0.931291E+09 | 0.00 | 0.00 |
October | 0.312907E+10 | 0.127769E+10 | 0.269610E+10 | 0.209129E+10 | 0.604810E+09 | 0.00 | 0.00 |
November | 0.198023E+10 | 0.132316E+10 | 0.180227E+10 | 0.125401E+10 | 0.548258E+09 | 0.00 | 0.00 |
December | 0.152681E+10 | 0.175713E+10 | 0.149535E+10 | 0.110112E+10 | 0.394232E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.471327E+11 | 0.135246E+11 | 0.392049E+11 | 0.289563E+11 | 0.102486E+11 | 0.00 | 0.00 |
Minimum of Months | 0.152681E+10 | 0.636878E+09 | 0.149535E+10 | 0.110112E+10 | 0.394232E+09 | 0.00 | 0.00 |
Maximum of Months | 0.614262E+10 | 0.175713E+10 | 0.478435E+10 | 0.376903E+10 | 0.123822E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.271930E+11 | 0.332277E+11 | 0.541792E+10 | 0.371299E+10 | 0.170493E+10 | 0.00 | 0.00 |
February | 0.341564E+11 | 0.261002E+11 | 0.661061E+10 | 0.470358E+10 | 0.190703E+10 | 0.00 | 0.00 |
March | 0.511058E+11 | 0.176753E+11 | 0.947960E+10 | 0.657196E+10 | 0.290764E+10 | 0.00 | 0.00 |
April | 0.667911E+11 | 0.119265E+11 | 0.123320E+11 | 0.887478E+10 | 0.345726E+10 | 0.00 | 0.00 |
May | 0.726872E+11 | 0.115200E+11 | 0.138330E+11 | 0.104295E+11 | 0.340347E+10 | 0.00 | 0.00 |
June | 0.918497E+11 | 0.130882E+11 | 0.141824E+11 | 0.111770E+11 | 0.300544E+10 | 0.00 | 0.00 |
July | 0.110744E+12 | 0.142695E+11 | 0.142577E+11 | 0.107199E+11 | 0.353785E+10 | 0.00 | 0.00 |
August | 0.966510E+11 | 0.134638E+11 | 0.133700E+11 | 0.959311E+10 | 0.377687E+10 | 0.00 | 0.00 |
September | 0.620897E+11 | 0.135934E+11 | 0.105394E+11 | 0.769871E+10 | 0.284068E+10 | 0.00 | 0.00 |
October | 0.423637E+11 | 0.161074E+11 | 0.827646E+10 | 0.643164E+10 | 0.184483E+10 | 0.00 | 0.00 |
November | 0.282435E+11 | 0.196872E+11 | 0.569351E+10 | 0.402118E+10 | 0.167233E+10 | 0.00 | 0.00 |
December | 0.235458E+11 | 0.329064E+11 | 0.484267E+10 | 0.364016E+10 | 0.120251E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.707421E+12 | 0.223566E+12 | 0.118835E+12 | 0.875745E+11 | 0.312608E+11 | 0.00 | 0.00 |
Minimum of Months | 0.235458E+11 | 0.115200E+11 | 0.484267E+10 | 0.364016E+10 | 0.120251E+10 | 0.00 | 0.00 |
Maximum of Months | 0.110744E+12 | 0.332277E+11 | 0.142577E+11 | 0.111770E+11 | 0.377687E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.939711E+09 | -852334448.3 | 0.00 | 0.00 | 744.00 | 0.00 | -87376561.2 | 58.99 | 0.00 | 0.00 |
February | 0.867482E+09 | -789014822.8 | 0.00 | 0.00 | 672.00 | 0.00 | -78467408.5 | 58.99 | 0.00 | 0.00 |
March | 0.984379E+09 | -899301248.9 | 0.00 | 0.00 | 744.00 | 0.00 | -85077403.3 | 58.99 | 0.00 | 0.00 |
April | 0.868738E+09 | -791275306.8 | 0.00 | 0.00 | 720.00 | 0.00 | -77462372.4 | 58.99 | 0.00 | 0.00 |
May | 0.840901E+09 | -765539856.4 | 0.00 | 0.00 | 744.00 | 0.00 | -75361323.2 | 58.99 | 0.00 | 0.00 |
June | 0.777832E+09 | -707999490.7 | 0.00 | 0.00 | 720.00 | 0.00 | -69832437.0 | 59.00 | 0.00 | 0.00 |
July | 0.720222E+09 | -649626525.7 | 0.00 | 0.00 | 744.00 | 0.00 | -70595733.8 | 58.99 | 0.00 | 0.00 |
August | 0.761311E+09 | -690155429.0 | 0.00 | 0.00 | 744.00 | 0.00 | -71155416.3 | 58.99 | 0.00 | 0.00 |
September | 0.733654E+09 | -663837808.7 | 0.00 | 0.00 | 720.00 | 0.00 | -69815990.6 | 58.99 | 0.00 | 0.00 |
October | 0.787274E+09 | -710470848.7 | 0.00 | 0.00 | 744.00 | 0.00 | -76802918.7 | 58.99 | 0.00 | 0.00 |
November | 0.817828E+09 | -735517330.0 | 0.00 | 0.00 | 720.00 | 0.00 | -82310546.8 | 58.99 | 0.00 | 0.00 |
December | 0.904394E+09 | -817181122.2 | 0.00 | 0.00 | 744.00 | 0.00 | -87212617.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.100037E+11 | -0.907225E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -931470729.1 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.720222E+09 | -899301248.9 | 0.00 | 0.00 | 672.00 | 0.00 | -87376561.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.984379E+09 | -649626525.7 | 0.00 | 0.00 | 744.00 | 0.00 | -69815990.6 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.92 | 0.58 | 12-JAN-11:50 | 112.23 | 0.00 | 0.00 | 1.67 | 92.22 | 0.00 | 0.00 | 0.00 |
February | 282.00 | 0.88 | 0.50 | 05-FEB-12:30 | 136.11 | 0.00 | 0.00 | 13.50 | 114.29 | 0.00 | 0.00 | 2.50 |
March | 351.33 | 0.84 | 0.50 | 01-MAR-11:09 | 174.08 | 0.00 | 0.00 | 57.83 | 139.64 | 0.00 | 0.00 | 27.33 |
April | 381.83 | 0.81 | 0.50 | 01-APR-11:30 | 192.81 | 0.00 | 0.00 | 59.83 | 156.77 | 0.00 | 0.00 | 24.83 |
May | 378.00 | 0.80 | 0.50 | 03-MAY-09:50 | 196.34 | 0.00 | 0.00 | 49.83 | 2489.64 | 0.00 | 0.00 | 64.00 |
June | 412.83 | 0.82 | 0.50 | 01-JUN-09:50 | 1260.19 | 0.00 | 0.00 | 87.83 | 2201.37 | 0.00 | 0.00 | 68.50 |
July | 395.33 | 0.80 | 0.50 | 01-JUL-09:39 | 997.31 | 0.00 | 0.00 | 94.83 | 740.95 | 0.00 | 0.00 | 62.83 |
August | 408.83 | 0.80 | 0.50 | 03-AUG-14:09 | 206.29 | 0.00 | 0.00 | 76.00 | 489.27 | 0.00 | 0.00 | 55.17 |
September | 359.33 | 0.83 | 0.50 | 04-SEP-10:30 | 881.48 | 0.00 | 0.00 | 67.17 | 141.25 | 0.00 | 0.00 | 26.00 |
October | 329.00 | 0.89 | 0.50 | 22-OCT-11:09 | 468.10 | 0.00 | 0.00 | 23.00 | 103.69 | 0.00 | 0.00 | 2.00 |
November | 284.17 | 0.91 | 0.58 | 03-NOV-11:09 | 113.99 | 0.00 | 0.00 | 2.83 | 95.63 | 0.00 | 0.00 | 0.00 |
December | 265.67 | 0.96 | 0.67 | 01-DEC-11:30 | 86.44 | 0.00 | 0.00 | 0.00 | 73.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4149.83 | 0.85 | 435.24 | 0.00 | 0.00 | 534.33 | 636.99 | 0.00 | 0.00 | 333.17 | ||
Minimum of Months | 265.67 | 0.80 | 0.50 | 86.44 | 0.00 | 0.00 | 0.00 | 73.67 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 412.83 | 0.96 | 0.67 | 1260.19 | 0.00 | 0.00 | 94.83 | 2489.64 | 0.00 | 0.00 | 68.50 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.73 | 0.50 | 02-JAN-12:20 | 588.54 | 11.36 | 0.00 | 108.67 | 156.47 | 15.11 | 17.00 | 75.83 |
February | 282.00 | 0.68 | 0.50 | 01-FEB-08:00 | 591.28 | 12.26 | 0.00 | 133.83 | 190.41 | 16.05 | 42.17 | 98.00 |
March | 351.33 | 0.66 | 0.50 | 01-MAR-07:00 | 280.27 | 13.15 | 0.00 | 196.83 | 236.95 | 17.04 | 58.67 | 152.50 |
April | 381.83 | 0.62 | 0.50 | 01-APR-09:20 | 320.00 | 14.20 | 0.00 | 262.33 | 1584.85 | 19.96 | 121.83 | 232.17 |
May | 378.00 | 0.60 | 0.50 | 01-MAY-06:00 | 2183.04 | 13.95 | 0.00 | 289.00 | 2566.62 | 17.97 | 98.67 | 246.67 |
June | 412.83 | 0.64 | 0.50 | 01-JUN-06:40 | 278.11 | 12.68 | 3.67 | 246.00 | 240.72 | 16.69 | 58.17 | 203.67 |
July | 395.33 | 0.61 | 0.50 | 01-JUL-07:10 | 1464.93 | 13.68 | 4.17 | 279.50 | 1485.76 | 17.68 | 83.83 | 236.50 |
August | 408.83 | 0.61 | 0.50 | 01-AUG-07:10 | 2343.17 | 14.17 | 1.67 | 292.33 | 2244.17 | 19.70 | 101.83 | 253.83 |
September | 359.33 | 0.64 | 0.50 | 01-SEP-08:39 | 284.18 | 13.08 | 0.00 | 222.17 | 238.18 | 17.00 | 72.00 | 179.50 |
October | 329.00 | 0.71 | 0.50 | 01-OCT-10:30 | 202.71 | 11.39 | 0.00 | 135.00 | 171.14 | 15.36 | 22.67 | 100.67 |
November | 284.17 | 0.71 | 0.50 | 01-NOV-11:09 | 192.70 | 11.98 | 0.00 | 113.17 | 161.52 | 15.84 | 24.00 | 76.83 |
December | 265.67 | 0.74 | 0.50 | 01-DEC-08:00 | 3000.22 | 10.33 | 0.00 | 109.83 | 1872.61 | 13.97 | 11.33 | 67.33 |
Annual Sum or Average | 4149.83 | 0.66 | 978.97 | 12.83 | 9.50 | 2388.67 | 975.70 | 17.06 | 712.17 | 1923.50 | ||
Minimum of Months | 265.67 | 0.60 | 0.50 | 192.70 | 10.33 | 0.00 | 108.67 | 156.47 | 13.97 | 11.33 | 67.33 | |
Maximum of Months | 412.83 | 0.74 | 0.50 | 3000.22 | 14.20 | 4.17 | 292.33 | 2566.62 | 19.96 | 121.83 | 253.83 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.85 | 0.61 | 20-JAN-15:30 | 577.90 | 24.06 | 145.50 | 58.50 | 130.05 | 20.77 | 119.67 | 0.17 |
February | 282.00 | 0.81 | 0.61 | 02-FEB-15:09 | 630.18 | 24.58 | 153.00 | 84.33 | 289.35 | 23.36 | 157.17 | 30.17 |
March | 351.33 | 0.80 | 0.61 | 01-MAR-16:10 | 547.81 | 23.66 | 184.17 | 110.00 | 468.09 | 24.21 | 200.00 | 54.00 |
April | 381.83 | 0.77 | 0.61 | 01-APR-15:09 | 468.37 | 22.83 | 222.50 | 130.33 | 731.52 | 23.87 | 281.50 | 90.67 |
May | 378.00 | 0.77 | 0.61 | 01-MAY-15:20 | 326.28 | 21.79 | 177.50 | 110.33 | 354.26 | 23.13 | 275.50 | 86.83 |
June | 412.83 | 0.80 | 0.61 | 01-JUN-13:00 | 286.84 | 20.74 | 144.33 | 114.83 | 419.59 | 22.12 | 202.17 | 82.00 |
July | 395.33 | 0.78 | 0.61 | 02-JUL-14:50 | 320.81 | 21.42 | 185.00 | 143.17 | 363.50 | 22.68 | 238.17 | 86.33 |
August | 408.83 | 0.77 | 0.61 | 01-AUG-15:09 | 348.43 | 21.97 | 215.83 | 155.00 | 353.57 | 23.30 | 266.50 | 113.83 |
September | 359.33 | 0.79 | 0.61 | 01-SEP-14:09 | 408.70 | 22.65 | 177.83 | 117.50 | 435.89 | 24.48 | 210.83 | 78.83 |
October | 329.00 | 0.82 | 0.61 | 01-OCT-14:20 | 766.39 | 24.36 | 161.00 | 90.00 | 271.64 | 23.27 | 162.83 | 39.83 |
November | 284.17 | 0.83 | 0.61 | 01-NOV-14:50 | 523.90 | 24.60 | 149.83 | 66.67 | 144.92 | 21.49 | 130.67 | 2.67 |
December | 265.67 | 0.85 | 0.64 | 01-DEC-14:00 | 467.83 | 24.10 | 123.67 | 48.33 | 118.34 | 20.15 | 78.00 | 0.00 |
Annual Sum or Average | 4149.83 | 0.80 | 459.40 | 22.90 | 2040.17 | 1229.00 | 356.30 | 22.83 | 2323.00 | 665.33 | ||
Minimum of Months | 265.67 | 0.77 | 0.61 | 286.84 | 20.74 | 123.67 | 48.33 | 118.34 | 20.15 | 78.00 | 0.00 | |
Maximum of Months | 412.83 | 0.85 | 0.64 | 766.39 | 24.60 | 222.50 | 155.00 | 731.52 | 24.48 | 281.50 | 113.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.461090E+10 | 27323.28 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.376208E+10 | 27323.28 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.245989E+10 | 27323.28 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.526377E+09 | 27323.28 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 62038996.21 | 27323.28 | 05-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.334821E+09 | 27323.28 | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.186317E+10 | 27323.28 | 02-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.442815E+10 | 27323.28 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.461090E+10 | 27323.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.156294E+11 | 79698.44 | 11-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110245E+11 | 79698.44 | 01-FEB-03:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.354825E+10 | 79698.44 | 04-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72187218.70 | 51760.29 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11342603.35 | 3834.10 | 27-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.350376E+10 | 79698.44 | 26-NOV-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147371E+11 | 79698.44 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.485266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156294E+11 | 79698.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.327683E+11 | 72662.42 | 16-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193051E+11 | 71181.43 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159444E+10 | 33314.11 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112005E+10 | 25313.82 | 28-NOV-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.319748E+11 | 75614.63 | 14-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.867626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.327683E+11 | 75614.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 226.17 | 226.17 | 0.19 | 08-MAR-16:20 | 0.19 | 0.00 |
April | 0.00 | 0.00 | 0.604627E+09 | 0.604627E+09 | 4845.91 | 29-APR-16:00 | 4845.91 | 0.00 |
May | 0.00 | 0.00 | 0.223836E+10 | 0.221283E+10 | 19891.85 | 22-MAY-05:03 | 15543.60 | 0.00 |
June | 0.00 | 0.00 | 0.626496E+10 | 0.608574E+10 | 21645.74 | 29-JUN-05:01 | 19323.87 | 0.00 |
July | 0.00 | 0.00 | 0.895704E+10 | 0.782477E+10 | 22482.61 | 01-JUL-05:01 | 13015.04 | 0.00 |
August | 0.00 | 0.00 | 0.862652E+10 | 0.744511E+10 | 22785.59 | 14-AUG-05:01 | 13153.89 | 0.00 |
September | 0.00 | 0.00 | 0.538987E+10 | 0.486628E+10 | 21722.29 | 05-SEP-05:01 | 12463.32 | 0.00 |
October | 0.00 | 0.00 | 0.169145E+10 | 0.157936E+10 | 20245.19 | 02-OCT-05:01 | 16021.88 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.337728E+11 | 0.306187E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.895704E+10 | 0.782477E+10 | 22785.59 | 19323.87 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.131917E+10 | 0.131892E+10 | 53242.80 | 28-MAY-13:45 | 53242.80 | 0.00 |
June | 0.00 | 0.00 | 0.123560E+11 | 0.122588E+11 | 55341.21 | 25-JUN-08:61 | 49500.98 | 0.00 |
July | 0.00 | 0.00 | 0.204361E+11 | 0.190006E+11 | 61300.93 | 01-JUL-17:22 | 35009.71 | 0.00 |
August | 0.00 | 0.00 | 0.167666E+11 | 0.155780E+11 | 60100.12 | 13-AUG-08:25 | 35412.95 | 0.00 |
September | 0.00 | 0.00 | 0.633368E+10 | 0.607730E+10 | 57272.60 | 04-SEP-10:35 | 46080.68 | 0.00 |
October | 0.00 | 0.00 | 0.105180E+10 | 0.103579E+10 | 53147.01 | 01-OCT-11:41 | 53147.01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.582633E+11 | 0.552694E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.204361E+11 | 0.190006E+11 | 61300.93 | 53242.80 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.391722E+09 | 0.05 | 286.12 | 01-JAN-00:05 | 0.09 |
February | 0.218545E+09 | 0.03 | 286.12 | 01-FEB-00:03 | 0.09 |
March | 29842406.07 | 0.00 | 286.12 | 01-MAR-03:00 | 0.09 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 25006963.48 | 0.00 | 286.12 | 26-NOV-03:17 | 0.09 |
December | 0.400254E+09 | 0.05 | 286.12 | 03-DEC-06:37 | 0.09 |
Annual Sum or Average | 0.106537E+10 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.400254E+09 | 0.05 | 286.12 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.733614E+09 | 0.37 | 1431.06 | 02-JAN-06:01 | 1.11 |
February | 0.658158E+09 | 0.36 | 1431.06 | 01-FEB-06:01 | 1.11 |
March | 0.703159E+09 | 0.32 | 1431.06 | 01-MAR-06:01 | 1.11 |
April | 0.587363E+09 | 0.27 | 1431.06 | 01-APR-05:01 | 1.11 |
May | 0.592520E+09 | 0.26 | 1431.06 | 05-MAY-05:01 | 1.11 |
June | 0.617666E+09 | 0.28 | 1431.06 | 15-JUN-05:02 | 1.10 |
July | 0.611448E+09 | 0.27 | 1431.06 | 01-JUL-05:01 | 1.09 |
August | 0.643205E+09 | 0.28 | 1431.06 | 01-AUG-05:01 | 1.09 |
September | 0.579501E+09 | 0.26 | 1431.06 | 01-SEP-05:01 | 1.09 |
October | 0.581785E+09 | 0.26 | 1431.06 | 02-OCT-05:01 | 1.09 |
November | 0.612598E+09 | 0.28 | 1431.06 | 02-NOV-05:02 | 1.10 |
December | 0.723395E+09 | 0.33 | 1431.06 | 01-DEC-06:01 | 1.11 |
Annual Sum or Average | 0.764441E+10 | 0.29 | |||
Minimum of Months | 0.579501E+09 | 0.26 | 1431.06 | 1.09 | |
Maximum of Months | 0.733614E+09 | 0.37 | 1431.06 | 1.11 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.176829E+10 | 0.63 | 3069.48 | 11-JAN-06:11 | 1.07 |
February | 0.151337E+10 | 0.58 | 3069.48 | 01-FEB-03:23 | 1.07 |
March | 0.144146E+10 | 0.40 | 3069.48 | 04-MAR-06:11 | 1.07 |
April | 0.121824E+10 | 0.25 | 1993.48 | 01-APR-05:01 | 1.07 |
May | 0.127023E+10 | 0.25 | 1641.21 | 19-MAY-17:10 | 0.77 |
June | 0.140804E+10 | 0.31 | 3069.48 | 16-JUN-17:06 | 1.07 |
July | 0.147828E+10 | 0.33 | 3069.48 | 02-JUL-13:33 | 1.06 |
August | 0.147996E+10 | 0.32 | 3069.48 | 01-AUG-17:06 | 1.06 |
September | 0.125487E+10 | 0.26 | 3069.48 | 03-SEP-12:03 | 1.06 |
October | 0.122188E+10 | 0.24 | 1316.39 | 27-OCT-07:10 | 0.68 |
November | 0.129617E+10 | 0.39 | 3069.48 | 26-NOV-05:53 | 1.07 |
December | 0.173773E+10 | 0.64 | 3069.48 | 04-DEC-06:01 | 1.07 |
Annual Sum or Average | 0.170885E+11 | 0.38 | |||
Minimum of Months | 0.121824E+10 | 0.24 | 1316.39 | 0.68 | |
Maximum of Months | 0.176829E+10 | 0.64 | 3069.48 | 1.07 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.733614E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.658158E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.703159E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.736208E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.114067E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.222657E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.284203E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.273719E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.187183E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.985413E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.612598E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.723395E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.159708E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.612598E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.284203E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.176829E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.151337E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.144146E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.121824E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.161933E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.479192E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.685967E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.579972E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.288321E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.149197E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.129617E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.173773E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.324211E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.121824E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.685967E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.733614E+09 | 0.00 | 0.461090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.658158E+09 | 0.00 | 0.376208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.703159E+09 | 226.17 | 0.245989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.587363E+09 | 0.604627E+09 | 0.526377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.592520E+09 | 0.223601E+10 | 62038996.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.617666E+09 | 0.623758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.611448E+09 | 0.889183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.643205E+09 | 0.857978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.579501E+09 | 0.537015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.581785E+09 | 0.168841E+10 | 0.334821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.612598E+09 | 0.00 | 0.186317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.723395E+09 | 0.00 | 0.442815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.764441E+10 | 0.336084E+11 | 0.180474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.579501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.733614E+09 | 0.889183E+10 | 0.461090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.176829E+10 | 0.00 | 0.156294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151337E+10 | 0.00 | 0.110245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144146E+10 | 0.00 | 0.354825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121824E+10 | 0.00 | 72187218.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127023E+10 | 0.129582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140804E+10 | 0.121961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147828E+10 | 0.199140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147996E+10 | 0.162990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125487E+10 | 0.612668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122188E+10 | 0.102939E+10 | 11342603.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129617E+10 | 0.00 | 0.350376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173773E+10 | 0.00 | 0.147371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170885E+11 | 0.568610E+11 | 0.485266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176829E+10 | 0.199140E+11 | 0.156294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.733614E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.658158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.703159E+09 | 0.00 | 0.00 | 0.00 | 58.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.587363E+09 | 0.00 | 0.00 | 0.00 | 0.148845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.592520E+09 | 0.00 | 0.00 | 0.00 | 0.548153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.617666E+09 | 0.00 | 0.00 | 0.00 | 0.160890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.611448E+09 | 0.00 | 0.00 | 0.00 | 0.223058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.643205E+09 | 0.00 | 0.00 | 0.00 | 0.209399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.579501E+09 | 0.00 | 0.00 | 0.00 | 0.129233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.581785E+09 | 0.00 | 0.00 | 0.00 | 0.403628E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.612598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.723395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.764441E+10 | 0.00 | 0.00 | 0.00 | 0.832642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.579501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.733614E+09 | 0.00 | 0.00 | 0.00 | 0.223058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.176829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127023E+10 | 0.00 | 0.00 | 0.00 | 0.349099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140804E+10 | 0.00 | 0.00 | 0.00 | 0.338388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147828E+10 | 0.00 | 0.00 | 0.00 | 0.538139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147996E+10 | 0.00 | 0.00 | 0.00 | 0.431976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125487E+10 | 0.00 | 0.00 | 0.00 | 0.162834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122188E+10 | 0.00 | 0.00 | 0.00 | 0.270087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170885E+11 | 0.00 | 0.00 | 0.00 | 0.153326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176829E+10 | 0.00 | 0.00 | 0.00 | 0.538139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.190769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140774E+10 | 0.00 | 0.00 | 0.12 |
February | 0.210132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116055E+10 | 0.00 | 0.00 | 0.13 |
March | 0.444240E+09 | 0.00 | 0.00 | 130.01 | 0.00 | 0.738357E+09 | 5056111.57 | 0.00 | 0.14 |
April | 0.497715E+09 | 132946.80 | 0.00 | 1293042.95 | 0.00 | 96045294.55 | 0.670776E+09 | 0.00 | 0.26 |
May | 0.177354E+09 | 6094544.89 | 0.00 | 4039373.85 | 0.00 | 8682953.92 | 0.140687E+10 | 0.00 | 0.40 |
June | 7492765.02 | 0.202482E+09 | 0.00 | 4744793.05 | 0.00 | 0.00 | 0.816840E+09 | 0.00 | 0.37 |
July | 76000.04 | 0.644774E+09 | 0.00 | 4094653.27 | 25241.12 | 0.00 | 0.104713E+09 | 0.00 | 0.29 |
August | 349794.31 | 0.465946E+09 | 0.00 | 5184901.90 | 0.00 | 0.00 | 0.429955E+09 | 0.00 | 0.39 |
September | 1894544.88 | 88871499.11 | 0.00 | 6077623.83 | 0.00 | 0.00 | 0.112274E+10 | 0.00 | 0.45 |
October | 0.361166E+09 | 9562928.50 | 0.00 | 3495876.81 | 0.00 | 84809233.85 | 0.137742E+10 | 0.00 | 0.36 |
November | 0.679749E+09 | 0.00 | 0.00 | 16547.04 | 0.00 | 0.585851E+09 | 25424755.78 | 0.00 | 0.12 |
December | 0.213919E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159601E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.278486E+10 | 0.141786E+10 | 0.00 | 28946942.71 | 25241.12 | 0.567805E+10 | 0.595979E+10 | 0.00 | 0.26 |
Minimum of Months | 76000.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.679749E+09 | 0.644774E+09 | 0.00 | 6077623.83 | 25241.12 | 0.159601E+10 | 0.140687E+10 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.275933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148494E+10 | 0.00 | 0.00 | 0.17 |
February | 0.284922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741312E+09 | 0.00 | 0.00 | 0.18 |
March | 0.275180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137913E+09 | 0.00 | 0.00 | 0.19 |
April | 0.269208E+10 | 0.00 | 0.00 | 0.00 | 927264.30 | 0.00 | 0.00 | 0.00 | 0.18 |
May | 0.232382E+10 | 539312.53 | 0.00 | 2055045.22 | 692438.18 | 0.00 | 0.932517E+09 | 0.00 | 0.24 |
June | 0.763146E+09 | 0.315516E+09 | 0.00 | 7027116.43 | 0.00 | 0.00 | 0.109002E+10 | 0.00 | 0.28 |
July | 19994398.64 | 0.693608E+09 | 0.00 | 8475796.56 | 0.00 | 0.00 | 0.112531E+10 | 0.00 | 0.31 |
August | 0.167431E+09 | 0.307032E+09 | 0.00 | 13163177.35 | 0.00 | 0.00 | 0.199555E+10 | 0.00 | 0.37 |
September | 0.743373E+09 | 10971283.96 | 0.00 | 9732639.75 | 0.00 | 0.00 | 0.240981E+10 | 0.00 | 0.34 |
October | 0.305294E+10 | 0.00 | 0.00 | 2041612.47 | 0.00 | 0.00 | 0.835134E+09 | 0.00 | 0.23 |
November | 0.335228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102876E+09 | 0.00 | 0.00 | 0.17 |
December | 0.371321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127850E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.251886E+11 | 0.132767E+10 | 0.00 | 42495387.77 | 1619702.49 | 0.374554E+10 | 0.838834E+10 | 0.00 | 0.24 |
Minimum of Months | 19994398.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.371321E+10 | 0.693608E+09 | 0.00 | 13163177.35 | 927264.30 | 0.148494E+10 | 0.240981E+10 | 0.00 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.556974E+12 | 0.385810E+11 | 0.00 | 0.584278E+10 | 0.175285E+11 |
February | 0.688187E+12 | 0.357318E+11 | 0.00 | 0.496122E+10 | 0.116806E+11 |
March | 0.918755E+12 | 0.323350E+11 | 0.00 | 0.407737E+10 | 0.329201E+10 |
April | 0.116374E+13 | 0.296885E+11 | 0.00 | 0.395685E+10 | 0.104134E+10 |
May | 0.126256E+13 | 0.357777E+11 | 0.00 | 0.485544E+10 | 0.448559E+10 |
June | 0.121481E+13 | 0.341872E+11 | 0.00 | 0.216670E+10 | 0.236137E+11 |
July | 0.125013E+13 | 0.484385E+11 | 0.00 | -76561548.6 | 0.370051E+11 |
August | 0.122371E+13 | 0.516833E+11 | 0.00 | 0.182919E+10 | 0.318069E+11 |
September | 0.988034E+12 | 0.326588E+11 | 0.00 | 0.422500E+10 | 0.146442E+11 |
October | 0.798957E+12 | 0.360406E+11 | 0.00 | 0.571099E+10 | 0.358412E+10 |
November | 0.595787E+12 | 0.312923E+11 | 0.00 | 0.474620E+10 | 0.287750E+10 |
December | 0.521000E+12 | 0.356464E+11 | 0.00 | 0.680164E+10 | 0.169512E+11 |
Annual Sum or Average | 0.111826E+14 | 0.442061E+12 | 0.00 | 0.490968E+11 | 0.168511E+12 |
Minimum of Months | 0.521000E+12 | 0.296885E+11 | 0.00 | -76561548.6 | 0.104134E+10 |
Maximum of Months | 0.126256E+13 | 0.516833E+11 | 0.00 | 0.680164E+10 | 0.370051E+11 |